supertech - Environmental Clearance

40

Transcript of supertech - Environmental Clearance

Ambient Air Quality  MonitoringTest Report No. : Issue Date 30/04/2016EK0/EV-AA/109/260416

TEST REPORT

Sample Description

Sample Received on

26/04/2016 To 30/04/2016

RESULTS

26/04/2016

SUPERTECH LIMITEDSUPERTECH HOUSEB-28-29, SECTOR - 58, NOIDA - 201307Proj. Name- Cape Town at Plot GH-01

Issued To

Sector - 74, Noida (U.P.)

Analysis Duration

Sample Drawn on 25/04/2016 To 26/04/2016

Ambient Air

EPEPL(Mr. Praduman Sharma)Sample Drawn by

On Project SiteSampling LocationSOP-AAQ/15Sampling Plan & Procedure

24 Hrs.Sampling Time34.0Ambient Temprature (deg ºC)1.1Average Flow Rate of SPM (m³/min)1.0Average Flow Rate of Gases (lpm.)ClearWeather Conditions

Remark (if any) NA

PARAMETERS.No. ResultsTest Methods LIMIT AS PER EPA*

Units

Particulate Matter (PM10)1 89.7IS:5182 (P-23) 100.0µg/m3

Particulate Matter (PM2.5)2 55.2SOP-AAQ/89/01 60.0µg/m3

Sulphur dioxide (as SO2)3 14.6IS:5182 (P-2) Improved West & Geake

80.0µg/m3

Nitrogen Dioxide (as NO2)4 27.0IS:5182 (P-6) 80.0µg/m3

Carbon Monoxide (as CO)5 < 1.15IS:5182 (P-10) Grab Method 4.0mg/m3

Lead (as Pb)6 < 0.1IS:5182 (P-22) 1.0µg/m3

Nickel as Ni7 < 15.0SOP-AAQ/89/02 20.0ng/m3

Arsenic (as As)8 < 5.0SOP-AAQ/89/03 6.0ng/m3

Ozone (as O3)9 < 10.0IS:5182 (P-9) Chemical Method 180.0µg/m3

Ammonia (as NH3)10 < 20.0APHA--AIR Indophenol Blue Method

400.0µg/m3

Benzene (as C6H6)11 < 1.0IS:5182 (P-11) 5.0µg/m3

Benzo (alpha) Pyrine-Particulate Phase only

12 < 1.0IS:5182 (P-12) 1.0ng/m3

Authorized Signatory

Page No. 1/2

For EKO PRO ENGINEERS PVT. LTD

Test Report No. : Issue Date 30/04/2016EK0/EV-AA/109/260416*Details as per EPA-1986 National Ambient Air Quality Standards,date 18.11.2009

Notes :1. The results given above are ralated to the tested sample, as received  & mentioned parameters.

The customer asked for the above tests only.2. This test report will not be generated again, either wholly or in part, without written permission of the Laboratory.3. This test report will not be use for any publicity/legal purpose.

**End of Report**

4. This test samples will be disposed off after two weeks from the date of issue of test report, unless until specified by the customer.5. Responsibility of the Laboratory is limited to the invoiced amount only.

Authorized Signatory

Page No. 2/2

For EKO PRO ENGINEERS PVT. LTD

Soil Sample  Analysis

Test Report No. : 30/04/2016Issue DateEK0/EV-S0/102/260416

TEST REPORT

Sample Description

Sample Received on

26/04/2016 To 30/04/2016

RESULTS

26/04/2016

500 gmSample Quantity

SUPERTECH LIMITEDSUPERTECH HOUSEB-28-29, SECTOR - 58, NOIDA - 201307Proj. Name- Cape Town at Plot GH-01

Issued To

Sector - 74, Noida (U.P.)

Analysis Duration

SOP-S/50

Sample Drawn on 25/04/2016

Soil Sample

EPEPL(Mr. Praduman Sharma)Sample Drawn by

Sampling Plan & Procedure

NormalEnvironmental Condition

Remark (if any) NA

On Project SiteSampling Location

PARAMETERS.No. Results UnitsTest Methods

pH (1 : 2.5 Suspension)1 7.29 -IS : 2720 (P-26)

Conductivity (1:5 Susp.)2 542.0 µs/cmIS : 2720 (P-21)

Water Holding Capacity3 51.8 % by massSOP-S/92/21

Bulk Density4 1.12 gm/ccSOP-S/92/12

Sodium Available (as Na)5 179.8 mg/kgMinistry of Agriculture Manual 2011

Potassium Available (as K)6 246.2 mg/kgMinistry of Agriculture Manual 2011

Organic Matter7 0.52 % by massIS : 2720 (P-22)

Total Kjehldal Nitrogen8 1468.7 mg/kgSOP-S/92/06

Phosphorus (as P)9 63.8 mg/kgMinistry of Agriculture Manual 2011

Lead (as Pb)10 < 1.0 mg/kgSOP-S/96/11

Copper (as Cu)11 < 1.0 mg/kgSOP-S/96/11

Cation Exchange Capacity12 12.5 meq/100gmSOP-S/95/20

Moisture content13 9.4 % by massIS : 2720 (P-2)

Iron (as Fe)14 0.119 % by massSOP-S/96/11

Authorized Signatory

For EKO PRO ENGINEERS PVT. LTD

Page No. 1/2

Test Report No. : 30/04/2016Issue DateEK0/EV-S0/102/260416

Notes :1. The results given above are ralated to the tested sample, as received  & mentioned parameters.

The customer asked for the above tests only.2. This test report will not be generated again, either wholly or in part, without written permission of the Laboratory.3. This test report will not be use for any publicity/legal purpose.4. This test samples will be disposed off after two weeks from the date of issue of test report, unless until specified by the customer.

Sample received for biological tests will be destroyed after 7 days from the date of issue of test report.5. Responsibility of the Laboratory is limited to the invoiced amount only.

**End of Report**

Authorized Signatory

For EKO PRO ENGINEERS PVT. LTD

Page No. 2/2

Water Sample  Analysis

Test Report No. : Issue Date 30/04/2016EK0/EV-WA/113/260416

TEST REPORT

Sample Description

Sample Received on

26/04/2016 To 30/04/2016

RESULTS

26/04/2016

5.0 LitreSample Quantity

SUPERTECH LIMITEDSUPERTECH HOUSEB-28-29, SECTOR - 58, NOIDA - 201307Proj. Name- Cape Town at Plot GH-01

Issued To

Sector - 74, Noida (U.P.)

Analysis Duration

SOP-W/66

Sample Drawn on 25/04/2016

Ground Water

EPEPL(Mr. Praduman Sharma)Sample Drawn by

Sampling Plan & Procedure

NormalEnvironmental Condition

Remark (if any) NA

From Village SarfabadSampling Location

PARAMETERS.No. ResultTest Methods Units

PermissibleAcceptable

IS: 10500 : 2012 (Limits)

Colour1 < 5.0IS : 3025 (P-4) Hazen 15.05.0

Odour2 AgreeableIS : 3025 (P-5) - AgreeableAgreeable

Taste3 AgreeableIS : 3025 (P-7) - AgreeableAgreeable

Turbidity4 < 1.0IS : 3025 (P-10) NTU 5.01.0

pH5 7.39IS : 3025 (P-11) - No relaxation6.5-8.5

Total Hardness (as CaCO3)

6 294.0IS : 3025 (P-21) mg/L 600.0200.0

Calcium (as Ca)7 62.8IS : 3025 (P-40) mg/L 200.075.0

Iron (as Fe)8 0.13IS : 3025 (P-53) mg/L No relaxation0.3

Chloride (as Cl)9 112.7IS : 3025 (P-32) mg/L 1000.0250.0

Residual Free Chlorine10 < 0.2IS : 3025 (P-26) mg/L 1.00.2

Fluoride (as F)11 < 1.0IS : 3025 (P-60) mg/L 1.51.0

Total Dissolved Solids12 640.0IS : 3025 (P-16) mg/L 2000.0500.0

Magnesium (as Mg)13 33.5IS : 3025 (P-46) mg/L 100.030.0

Copper (as Cu)14 < 0.01IS : 3025 (P-42) mg/L 1.50.05

Manganese (as Mn)15 < 0.1IS : 3025 (P-59) mg/L 0.30.1

Sulphate (as SO4)16 104.8IS : 3025 (P-24) mg/L 400.0200.0

Authorized Signatory

For EKO PRO ENGINEERS PVT. LTD

Page No. 1/2

Test Report No. : Issue Date 30/04/2016EK0/EV-WA/113/260416

PARAMETERS.No. ResultTest Methods Units

PermissibleAcceptable

IS: 10500 : 2012 (Limits)

Nitrate (as NO3)17 8.62IS : 3025 (P-34) mg/L No relaxation45.0

Phenolic Compounds (as C6H5OH)

18 < 0.001IS : 3025 (P-43) mg/L 0.0020.001

Mercury (as Hg)19 < 0.001IS : 3025 (P-48) mg/L No relaxation0.001

Selenium (as Se)20 < 0.005IS : 3025 (P-56) mg/L No relaxation0.01

Arsenic (as As)21 < 0.005IS : 3025 (P-37) mg/L 0.050.01

Cyanide (as CN)22 < 0.05APHA 4500 CN-C mg/L No relaxation0.05

Lead (as Pb)23 < 0.005IS : 3025 (P-47) mg/L No relaxation0.01

Zinc (as Zn)24 < 0.05IS : 3025 (P-49) mg/L 15.05.0

Total Chromium (as Cr)25 < 0.01IS : 3025 (P-52) mg/L No relaxation0.05

Total Alkalinity (as CaCO3)

26 328.0IS : 3025 (P-23) mg/L 600.0200.0

Aluminium (as Al)27 < 0.01IS : 3025 (P-55) mg/L 0.20.03

Boron (as B)28 < 0.25IS : 3025 (P-57) mg/L 1.00.5

Cadmium (as Cd)29 < 0.001IS : 3025 (P-41) mg/L No relaxation0.003

Anionic Detergents (as MBAS)

30 < 0.05APHA 5540-C mg/L 1.00.2

Total Coliform31 AbsentIS : 1622 MPN/100 mL -Shall not be detectable in 100ml sample

E.coli32 AbsentIS : 1622 Per 100 mL -Shall not be detectable in 100ml sample

Notes :1. The results given above are ralated to the tested sample, as received  & mentioned parameters.

The customer asked for the above tests only.2. This test report will not be generated again, either wholly or in part, without written permission of the Laboratory.3. This test report will not be use for any publicity/legal purpose.4. This test samples will be disposed off after two weeks from the date of issue of test report, unless until specified by the customer.

Sample received for biological tests will be destroyed after 7 days from the date of issue of test report.5. Responsibility of the Laboratory is limited to the invoiced amount only.

**End of Report**

Authorized Signatory

For EKO PRO ENGINEERS PVT. LTD

Page No. 2/2

Stack Emission  Analysis

Test Report No. : Issue Date 30/04/2016EK0/EV-SE/103/260416

TEST REPORT

Sample Description

Sample Received on

26/04/2016 To 30/04/2016

RESULTS

26/04/201630Time of Sampling (minutes)

SUPERTECH LIMITEDSUPERTECH HOUSEB-28-29, SECTOR - 58, NOIDA - 201307Proj. Name- Cape Town at Plot GH-01

Issued To

Sector - 74, Noida (U.P.)

Analysis Duration

SOP-SE/09

Sample Drawn on 25/04/2016Stack Emission

EPEPL(Mr. Praduman Sharma)Sample Drawn by

Sampling Plan & Procedure

Stack Attached To DG Set(Sr.No.-2217)Source of Emission250 KVACapacityNormalOperating LoadAs per requirementNormal Operation ScheduleMetal/CircularType of Stack0.1Diameter of Stack (meter)2.4Height of Stack from Ground Level (meter)-Height of Stack from Roof Level (meter)Sampling done from top of the StackHeight of Sampling Location (meter)HSDType of Fuel Used25.0 lphFuel Consumed per Hour34.0Ambient Temperature (ºC)136.0Stack Temperature (ºC)13.2Average Velocity of Fuel Emission (m/sec)17.6Average Flow Rate (lpm)NilControl Measures (if any)

Remark (if any) Temporary Installed DG Set

NASampling Location

PARAMETERS.No. ResultTest Method LIMITS AS PER EPA*

Unit

Particulate Matter (as PM)1 29.8Gravimetric Method 150.0mg/Nm³

Sulphur Dioxide (as SO2)2 15.0Titrametric Method -mg/Nm³

Carbon monoxide (as CO)3 < 0.2Orsat Method 1.0% V/V

Lead (as Pb)4 < 1.0ICP Method 10.0mg/Nm³

Oxides of Nitrogen (as NOx)5 73.6Spectrophotometric Method -mg/Nm³

Authorized Signatory

Page No. 1/2

For EKO PRO ENGINEERS PVT. LTD

Test Report No. : Issue Date 30/04/2016EK0/EV-SE/103/260416

* Details as per EPA-1986 Schedule-VI Part-D

Notes :1. The results given above are ralated to the tested sample, as received  & mentioned parameters.

The customer asked for the above tests only.2. This test report will not be generated again, either wholly or in part, without written permission of the Laboratory.3. This test report will not be use for any publicity/legal purpose.

**End of Report**

4. This test samples will be disposed off after two weeks from the date of issue of test report, unless until specified by the customer.5. Responsibility of the Laboratory is limited to the invoiced amount only.

Authorized Signatory

Page No. 2/2

For EKO PRO ENGINEERS PVT. LTD

Stack Emission  Analysis

Test Report No. : Issue Date 30/04/2016EK0/EV-SE/104/260416

TEST REPORT

Sample Description

Sample Received on

26/04/2016 To 30/04/2016

RESULTS

26/04/201630Time of Sampling (minutes)

SUPERTECH LIMITEDSUPERTECH HOUSEB-28-29, SECTOR - 58, NOIDA - 201307Proj. Name- Cape Town at Plot GH-01

Issued To

Sector - 74, Noida (U.P.)

Analysis Duration

SOP-SE/09

Sample Drawn on 25/04/2016Stack Emission

EPEPL(Mr. Praduman Sharma)Sample Drawn by

Sampling Plan & Procedure

Stack Attached To DG Set(SR.No.CJK-15070333)Source of Emission500 KVACapacityNormalOperating LoadAs per requirementNormal Operation ScheduleMetal/CircularType of Stack0.1Diameter of Stack (meter)2.4Height of Stack from Ground Level (meter)-Height of Stack from Roof Level (meter)Sampling done from top of the StackHeight of Sampling Location (meter)HSDType of Fuel Used60.0 lphFuel Consumed per Hour34.0Ambient Temperature (ºC)163.0Stack Temperature (ºC)15.8Average Velocity of Fuel Emission (m/sec)19.2Average Flow Rate (lpm)NilControl Measures (if any)

Remark (if any) Temporary Installed DG Set

NASampling Location

PARAMETERS.No. ResultTest Method LIMITS AS PER EPA*

Unit

Particulate Matter (as PM)1 34.6Gravimetric Method 150.0mg/Nm³

Sulphur Dioxide (as SO2)2 17.4Titrametric Method -mg/Nm³

Carbon monoxide (as CO)3 < 0.2Orsat Method 1.0% V/V

Lead (as Pb)4 < 1.0ICP Method 10.0mg/Nm³

Oxides of Nitrogen (as NOx)5 85.3Spectrophotometric Method -mg/Nm³

Authorized Signatory

Page No. 1/2

For EKO PRO ENGINEERS PVT. LTD

Test Report No. : Issue Date 30/04/2016EK0/EV-SE/104/260416

* Details as per EPA-1986 Schedule-VI Part-D

Notes :1. The results given above are ralated to the tested sample, as received  & mentioned parameters.

The customer asked for the above tests only.2. This test report will not be generated again, either wholly or in part, without written permission of the Laboratory.3. This test report will not be use for any publicity/legal purpose.

**End of Report**

4. This test samples will be disposed off after two weeks from the date of issue of test report, unless until specified by the customer.5. Responsibility of the Laboratory is limited to the invoiced amount only.

Authorized Signatory

Page No. 2/2

For EKO PRO ENGINEERS PVT. LTD

Noise  Monitoring

Test Report No. : Issue Date 28/04/2016EK0/EV-NM/113/260416

TEST REPORT

Sample Description

Sample Received on

26/04/2016 To 27/04/2016

RESULTS

26/04/2016

SUPERTECH LIMITEDSUPERTECH HOUSEB-28-29, SECTOR - 58, NOIDA - 201307Proj. Name- Cape Town at Plot GH-01

Issued To

Sector - 74, Noida (U.P.)

Analysis Duration

Sample Drawn on 25/04/2016 To 26/04/2016

Ambient Noise

EPEPL(Mr. Praduman Sharma)Sample Drawn by

On Project SiteSampling Location

SOP-N/01Sampling Plan & ProcedureNormalEnvironmental Condition

Remark (if any) NA

PARAMETERS.No. ResultsTest Methods LIMITS AS PER EPA *

Units

L Day1 62.8SOP-N/94/01 65.0dB (A)

L Night2 51.4SOP-N/94/01 55.0dB (A)

* Details as per EPA -1986 Ambient Noise Quality Standards, Schedule-III, (Rule-3)

Notes :1. The results given above are ralated to the tested sample, as received  & mentioned parameters.

The customer asked for the above tests only.2. This test report will not be generated again, either wholly or in part, without written permission of the Laboratory.3. This test report will not be use for any publicity/legal purpose.4. Responsibility of the Laboratory is limited to the invoiced amount only.

**End of Report**

Authorized Signatory

Page No. 1/1

For EKO PRO ENGINEERS PVT. LTD