Transcript of Split System Rating
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Air Handling Unit Tag: Split AHU # 1
CFA-007-A-A-8-DC00H:A-D0-E0-00-000-L-FE00-00E0G00-0A000DB Condensing Unit Tag: Split CU # 1
Job Information Unit Information
Job Name: Approx. Weights AHU/CU: Job Number: Supply CFM/ESP: Site Altitude: Refrigerant
Ambient Temperature: Return Temperature:
BCH Life Guard 659 / 474 lbs. (±5%)H-19 900 / 0.5 in. wg.0 ftR-410A
93 ºF DB / 79 ºF WB80 ºF DB / 67 ºF WB
Static Pressure
External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Total:
0.50 in. wg. 0.00 in. wg.0.29 in. wg. 0.03 in. wg.0.04 in. wg. 0.00 in. wg.0.15 in. wg. 1.01 in. wg.
Cooling Section Heating Section
Gross Net Total Capacity: Sensible Capacity: Latent Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Evap Suction Temp: Supply Air Fan: SA Fan RPM / Width:
Evaporator Coil: Evaporator Face Velocity:
68.27 67.43 MBH33.82 32.98 MBH34.45 MBH93.00 ºF DB 79.00 ºF WB93.00 ºF DB 79.00 ºF WB56.50 ºF DB 56.44 ºF WB57.33 ºF DB 56.76 ºF WB46.58 ºF1 x 250AY @ 0.28 BHP2237 / 3.150"
3.7 ft² / 6 Rows / 12 FPI245.5 fpm
PreHeat Type: Std (No Preheat)
Auxiliary Heating Type*: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty (Hi/Low): Electric Heat FLA:
Electric Heat90035.8 MBH40.0 DB / 33.0ºF WB75.0 ºF DB / 65.0 ºF WB40.0 ºF DB / 33.0 ºF WB76.9 ºF DB / 51.5 ºF WB10.5 kW229.1
Re-Heat Coil: Capacity: 18 MBH LA DB / WB: 75.00 ºF / 63.21 ºF RH: 52%
EER - ARI Listing Information
Application EER @ Op. Conditions: Condensing Unit EER @ Op. Conditions:11.9 12.7
AH Electrical Data
Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:
208/3/60 4031.9 40
CU Electrical Data
Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:
208/3/60 2823 45
Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 208 3 20.4 Condenser Fans: 1 0.33 208 1 1075 2.8 Supply Fan: 1 1.10 208 3 3450 2.8
*Motor heat is not included.
Connection Sizes
System Suction Line Liquid Line Hot Gas Reheat1 1.13" 0.5" 0.88"
Split System Rating
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Air Handling Unit Tag: Split AHU # 1
CFA-007-A-A-8-DC00H:A-D0-E0-00-000-L-FE00-00E0G00-0A000DB Condensing Unit Tag: Split CU # 1
Job Information
Job Name: BCH Life Guard Job Number: H-19
Reheat Line Data
Elbow Qty: 4 Line Length: 30'
Oil return to be installed at the lowest point of the system.
PipeOD
Equiv.Length
Temp.Loss (ºF)
Velocity(fpm)
Min TonsFor Oil Return
" '
Suction Line Data
Elbow Qty: 4 Line Length: 30' Flow Direction of Suction Line: Down
PipeOD
Equiv.Length
Temp.Loss (ºF)
Velocity(fpm)
Min TonsFor Oil Return
Qty. ofReq. Traps
" '
Liquid Line Data
Elbow Qty: 4 Line Length: 30' Vertical Lift: 10'
PipeOD
Equiv.Length
Temp.Loss (ºF)
Velocity(fpm)
Min SubcoolingFor Vertical Lift
" '
Line Sizing Information
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Air Handling Unit Tag: Split AHU # 1
CFA-007-A-A-8-DC00H:A-D0-E0-00-000-L-FE00-00E0G00-0A000DB Condensing Unit Tag: Split CU # 1
Job Information
Job Name: BCH Life Guard Job Number: H-19
Factory Supplied / Factory Installed
Quantity Description Part #: Location
Factory Supplied / Field Installed
Quantity Description Part #: Location- N/A - -
Field Supplied / Field Installed
Quantity Description Part #: Location- P-Trap(s) AHU
Refrigeration Accessories
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM
Circuit #: 1
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM
203 Gum Springs Road - Longview, TX 75602 - Ph. (903) 236-4403 Fax (903) 236-4463AAONEcat32 Ver. 4.282 (SN: 6092064-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Tag: Split AHU # 1
Job Name: BCH Life Guard Unit Submittal For: Job Number: H-19 Unit Submittal Date: May 01, 2019
Base Option Description
V Series Vertical Unit
3 Generation Third Generation
B Unit Size Up to 2,000 cfm
R Unit Orientation Right Hand Connections - Top Discharge, Back Intake (Vertical)
B Revision Second Revision
8 Voltage 208V/3Ø/60Hz
0 Corrosion Protection None
1 Cooling Type R-410A DX Cooling
6 Cooling Rows 6 Row Coil
1 Cooling Stages Single Circuit
C Cooling FPI 12 fpi
3 Heating Type Electric Heat
B Heating Designation 14 kW (10.5 kW @ 208V)
2 Heating Stages 2 Stage
Feature Option Description
A 1A. SA Blower Configuration 1 Blower + 1 High Efficiency EC Motor
D 1B. SA Blower Model 250 mm Backward Curved Plenum
F 1C. SA Blower Motor 800 W
E 1D. SA Blower Control/Contol Vendor VCC-X Orion Controls System
H 2. Refrigeration Options Modulating Hot Gas Reheat (MHGR)
E 3. Special Controls Make Up Air Controller - CV Cool + CV Heat
H 4. Additional Controls Remote Safety Shutdown Terminals
0 5A. Mixing Box - RA Damper Position Standard - None
0 5B. Mixing Box - OA Damper Position Standard - None
0 5C. Mixing Box - Damper Control Standard - None
0 6A. Filter Box - Pre Filter Box Standard - None
A 6B. Filter Box - Unit Filter 2" Pleated - 30% Eff.
0 6C. Filter Box - Final Filter Box Standard - None
0 7. Filter Options Standard - None
0 8. Coil Coating Standard - None
A 9. Expansion Valve Thermal Expansion Valves
0 10. Expansion Valve Controls None
0 11. External Paint Standard - None
F 12. Tonnage 7 ton Capacity
0 13. Energy Recovery Type Standard - None
0 14A. GPM Cooling Coil Standard
0 14B. GPM Heating Coil Standard
B 15. Control Panel Medium Control Panel - 25" x 22"
0 16. Shipping Splits Standard (No Shipping Split)
0 17. Energy Recovery Cabinet Standard - None
0 18. Preheat Standard - None
0 19. Exhaust Fan Standard - None
0 20. Crating Standard
0 21. Pulley Combination Standard - None
0 22. Warranty Standard - 1 Year Parts
0 23. Type Standard
Unit Submittal
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:27 PM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)
1A
1B
1C
1D
2
3
4
5A
5B
5C 6A
6B
6C
7
8
9
10
11
12
13
14A
14B
15
16
17
18
19
20
21
22
23
V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Tag: Split AHU # 1 Job Name: BCH Life Guard VCCX For: Job Number: H-19 VCCX Date: May 01, 2019
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet PointV87900 VCCX CONTROLLERV13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9V17180 EBUS DIST HUB EBUS5 distribution hub N/A
Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22R62330 Proof of Air Flow VCCX control point BI 1 BI:6
Safety Shut Down VCCX control point BI 8 BI:26Supply Fan Configured Relay point BI:63Heat 1 Configured Relay Point BI:64Heat 2 Configured Relay Point BI:65
VCCX Components
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:27 PM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)
JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:
Inertia:
BCH Life Guard 3,450Split AHU # 1 11.2 in. x 1
90005/01/2019 6,548 FPM
3 WR²
OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:
VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:
900 CFM 1.1 / No1.01 in. Wg. ECM0.00 in. Wg. 1760
208/3/601.01 in. Wg. Premium / 0.8550.00 Ft ODP1.01 in. Wg. 27 WR²
FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 69 / 73 dB
Max Duct SP with Blocked Airway: 1.9 in. Wg. @ 2237 rpm
22370.2851.1% 64 62 66 66 63 60 60 613913/1169 FPM 64 64 68 70 71 68 65 6310 FPM
RPM
BHP
SYSTEM
Efficiency
SP Surge
CFM Min
Supply Fan Model: 250AY @ 2237 RPM and 100% WidthDesign Conditions: 900 CFM @ 1.01" SP
CFM x 100010
SP1
0
BH
P
1
0
40%
20%
0%
RPM: 2237
BHP: 0.28
EFFICIENCY: 51.06
25.0" STAR Plenum
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:28 PM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)
A1
A2
A3
A4
A5
1
2A
2B 3A
3B
4
5
6A
6B
6C
7
8A
8B
8C
8D
9
10
11
12
13
14
15
16
17
18
19
20
21
22
C FA -007-A -A-8 -D C00H :A-D0- E0 -00- 00 0-L- FE 00-0 0E 0G00-0 A0 00DB Tag: Split CU # 1
Job Name: BCH Life Guard Unit Submittal For: Job Number: H-19 Unit Submittal Date: May 01, 2019
Base Option Description
CF Generation CF - Condensing Unit
A Major Rev Major Revision
007 Unit Size Seven
A Series A Cabinet
A Revision Minor Revision
8 Voltage 208V/3Ø/60Hz
D Compressor Style R-410A Variable Capacity Scroll Comp
C Condenser Style Air-Cooled Condenser (Fin and Tube)
0 Configuration Standard
0 Coating Standard
H Staging 1 Variable Refrig System
Feature Option Description
A 1. Unit Orientation Horizontal Condenser Discharge Standard Access
D 2A. Refrigeration Control Adjustable Compressor Lockout
0 2B. Blank Standard
E 3A. Refrigeration Options Modulating Hot Gas Reheat [MHGR]
0 3B. Blank Standard
0 4. Refrigeration Accessories Standard
0 5. Blank Standard
0 6A. Unit Disconnect Type Standard Single Point Power Block
0 6B. Disconnect Size None
0 6C. Blank Standard
L 7. Accessories Phase & Brown Out Protection + Suction Pressure Transducer on Each Refrigeration System
F 8A. Control Sequence Makeup Air Unit Controller - CAV Cool + CAV Heat
E 8B. Control suppliers VCC-X (Main Controller in Air Handling Unit)
0 8C. Control Supplier Options Standard
0 8D. BMS Connection and Diagnostics Standard
0 9. Blank Standard
0 10. Blank Standard
E 11. Maintenance Accessories Remote Unit Start/Stop Terminals
0 12. Code Options Standard ETL U.S.A. Listing
G 13.Air Cooled Condenser Accessories Condenser Coil Guard + ECM Cond Fan / Head Pressure Control
0 14. Blank Standard
0 15. Blank Standard
0 16. Electrical Options Standard
A 17. Shipping Options Crating
0 18. Blank Standard
0 19. Blank Standard
0 20. Cabinet Material Standard - Galvanized Steel Cabinet
D 21. Warranty Extended Compressor Warranty - Years 2-5
B 22. Paint and SPAs Premium AAON Gray Paint Exterior
Unit Submittal
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:51 PM
2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)
A1
A2
A3
A4
A5
1
2A
2B 3A
3B
4
5
6A
6B
6C
7
8A
8B
8C
8D
9
10
11
12
13
14
15
16
17
18
19
20
21
22
C FA -007-A -A-8 -D C00H :A-D0- E0 -00- 00 0-L- FE 00-0 0E 0G00-0 A0 00DB
Tag: Split CU # 1 Job Name: BCH Life Guard VCCX For: Job Number: H-19 VCCX Date: May 01, 2019
Hardware Included For VCCX Controller
Part # Included Parts Assigned Channel BACnet PointV61520 DIGITAL REFRIGERATION MODULER42680 Comp Discharge Temp A RSMD point TEMP1 AI:56V38391 Suction Pressure Sensor A RSMD point AI1 AI:48V38410 Discharge Pressure Sensor A RSMD point HP-1 AI:50R63950 Modulated Condenser Signal A RSMD point AO1 BI:
Comp Status Input A RSMD point BIN1Emergency Shutdown RSMD point BIN4 BI:81,82Condenser Enable AB RSMD Fixed Relay point BI:78,BI:85Comp Enable A RSMD Fixed Relay point AI:46
V12100 MODULATING HOT GAS REHEAT MODULEReheat HGR Valve MHGRV-X AI:42
VCCX Components
Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:51 PM