V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Air Handling Unit Tag: Split AHU # 1

CFA-007-A-A-8-DC00H:A-D0-E0-00-000-L-FE00-00E0G00-0A000DB Condensing Unit Tag: Split CU # 1

Job Information Unit Information

Job Name: Approx. Weights AHU/CU: Job Number: Supply CFM/ESP: Site Altitude: Refrigerant

Ambient Temperature: Return Temperature:

BCH Life Guard 659 / 474 lbs. (±5%)H-19 900 / 0.5 in. wg.0 ftR-410A

93 ºF DB / 79 ºF WB80 ºF DB / 67 ºF WB

Static Pressure

External: Economizer: Evaporator: Heating: Filters Clean: Cabinet: Dirt Allowance Total:

0.50 in. wg. 0.00 in. wg.0.29 in. wg. 0.03 in. wg.0.04 in. wg. 0.00 in. wg.0.15 in. wg. 1.01 in. wg.

Cooling Section Heating Section

Gross Net Total Capacity: Sensible Capacity: Latent Capacity: Mixed Air Temp: Entering Air Temp: Lv Air Temp (Coil): Lv Air Temp (Unit) Evap Suction Temp: Supply Air Fan: SA Fan RPM / Width:

Evaporator Coil: Evaporator Face Velocity:

68.27 67.43 MBH33.82 32.98 MBH34.45 MBH93.00 ºF DB 79.00 ºF WB93.00 ºF DB 79.00 ºF WB56.50 ºF DB 56.44 ºF WB57.33 ºF DB 56.76 ºF WB46.58 ºF1 x 250AY @ 0.28 BHP2237 / 3.150"

3.7 ft² / 6 Rows / 12 FPI245.5 fpm

PreHeat Type: Std (No Preheat)

Auxiliary Heating Type*: Heating CFM: Total Capacity: OA Temp: RA Temp: Entering Air Temp: Leaving Air Temp: Input: Heater Qty (Hi/Low): Electric Heat FLA:

Electric Heat90035.8 MBH40.0 DB / 33.0ºF WB75.0 ºF DB / 65.0 ºF WB40.0 ºF DB / 33.0 ºF WB76.9 ºF DB / 51.5 ºF WB10.5 kW229.1

Re-Heat Coil: Capacity: 18 MBH LA DB / WB: 75.00 ºF / 63.21 ºF RH: 52%

EER - ARI Listing Information

Application EER @ Op. Conditions: Condensing Unit EER @ Op. Conditions:11.9 12.7

AH Electrical Data

Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:

208/3/60 4031.9 40

CU Electrical Data

Rating: Minimum Circuit Amp: Unit FLA: Maximum Overcurrent:

208/3/60 2823 45

Qty HP VAC Phase RPM FLA RLA Compressor 1: 1 208 3 20.4 Condenser Fans: 1 0.33 208 1 1075 2.8 Supply Fan: 1 1.10 208 3 3450 2.8

*Motor heat is not included.

Connection Sizes

System Suction Line Liquid Line Hot Gas Reheat1 1.13" 0.5" 0.88"

Split System Rating

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)

1A

1B

1C

1D

2

3

4

5A

5B

5C 6A

6B

6C

7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Air Handling Unit Tag: Split AHU # 1

CFA-007-A-A-8-DC00H:A-D0-E0-00-000-L-FE00-00E0G00-0A000DB Condensing Unit Tag: Split CU # 1

Job Information

Job Name: BCH Life Guard Job Number: H-19

Reheat Line Data

Elbow Qty: 4 Line Length: 30'

Oil return to be installed at the lowest point of the system.

PipeOD

Equiv.Length

Temp.Loss (ºF)

Velocity(fpm)

Min TonsFor Oil Return

" '

Suction Line Data

Elbow Qty: 4 Line Length: 30' Flow Direction of Suction Line: Down

PipeOD

Equiv.Length

Temp.Loss (ºF)

Velocity(fpm)

Min TonsFor Oil Return

Qty. ofReq. Traps

" '

Liquid Line Data

Elbow Qty: 4 Line Length: 30' Vertical Lift: 10'

PipeOD

Equiv.Length

Temp.Loss (ºF)

Velocity(fpm)

Min SubcoolingFor Vertical Lift

" '

Line Sizing Information

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)

1A

1B

1C

1D

2

3

4

5A

5B

5C 6A

6B

6C

7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Air Handling Unit Tag: Split AHU # 1

CFA-007-A-A-8-DC00H:A-D0-E0-00-000-L-FE00-00E0G00-0A000DB Condensing Unit Tag: Split CU # 1

Job Information

Job Name: BCH Life Guard Job Number: H-19

Factory Supplied / Factory Installed

Quantity Description Part #: Location

Factory Supplied / Field Installed

Quantity Description Part #: Location- N/A - -

Field Supplied / Field Installed

Quantity Description Part #: Location- P-Trap(s) AHU

Refrigeration Accessories

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM

Circuit #: 1

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:25 PM

203 Gum Springs Road - Longview, TX 75602 - Ph. (903) 236-4403 Fax (903) 236-4463AAONEcat32 Ver. 4.282 (SN: 6092064-)

1A

1B

1C

1D

2

3

4

5A

5B

5C 6A

6B

6C

7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Tag: Split AHU # 1

Job Name: BCH Life Guard Unit Submittal For: Job Number: H-19 Unit Submittal Date: May 01, 2019

Base Option Description

V Series Vertical Unit

3 Generation Third Generation

B Unit Size Up to 2,000 cfm

R Unit Orientation Right Hand Connections - Top Discharge, Back Intake (Vertical)

B Revision Second Revision

8 Voltage 208V/3Ø/60Hz

0 Corrosion Protection None

1 Cooling Type R-410A DX Cooling

6 Cooling Rows 6 Row Coil

1 Cooling Stages Single Circuit

C Cooling FPI 12 fpi

3 Heating Type Electric Heat

B Heating Designation 14 kW (10.5 kW @ 208V)

2 Heating Stages 2 Stage

Feature Option Description

A 1A. SA Blower Configuration 1 Blower + 1 High Efficiency EC Motor

D 1B. SA Blower Model 250 mm Backward Curved Plenum

F 1C. SA Blower Motor 800 W

E 1D. SA Blower Control/Contol Vendor VCC-X Orion Controls System

H 2. Refrigeration Options Modulating Hot Gas Reheat (MHGR)

E 3. Special Controls Make Up Air Controller - CV Cool + CV Heat

H 4. Additional Controls Remote Safety Shutdown Terminals

0 5A. Mixing Box - RA Damper Position Standard - None

0 5B. Mixing Box - OA Damper Position Standard - None

0 5C. Mixing Box - Damper Control Standard - None

0 6A. Filter Box - Pre Filter Box Standard - None

A 6B. Filter Box - Unit Filter 2" Pleated - 30% Eff.

0 6C. Filter Box - Final Filter Box Standard - None

0 7. Filter Options Standard - None

0 8. Coil Coating Standard - None

A 9. Expansion Valve Thermal Expansion Valves

0 10. Expansion Valve Controls None

0 11. External Paint Standard - None

F 12. Tonnage 7 ton Capacity

0 13. Energy Recovery Type Standard - None

0 14A. GPM Cooling Coil Standard

0 14B. GPM Heating Coil Standard

B 15. Control Panel Medium Control Panel - 25" x 22"

0 16. Shipping Splits Standard (No Shipping Split)

0 17. Energy Recovery Cabinet Standard - None

0 18. Preheat Standard - None

0 19. Exhaust Fan Standard - None

0 20. Crating Standard

0 21. Pulley Combination Standard - None

0 22. Warranty Standard - 1 Year Parts

0 23. Type Standard

Unit Submittal

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:27 PM

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)

1A

1B

1C

1D

2

3

4

5A

5B

5C 6A

6B

6C

7

8

9

10

11

12

13

14A

14B

15

16

17

18

19

20

21

22

23

V 3- BRB-8- 0-16 1C -3B2 :ADFE- HE H-00 0- 0A0- 00 A00F 0- 00-B00 00 0000 Tag: Split AHU # 1 Job Name: BCH Life Guard VCCX For: Job Number: H-19 VCCX Date: May 01, 2019

Hardware Included For VCCX Controller

Part # Included Parts Assigned Channel BACnet PointV87900 VCCX CONTROLLERV13050 OSA Temp/Hum Sensor EBUS2 communicating sensor AI:16,AI:17,AI:18,AI:19R82890 Supply Temp Sensor - Field Installed VCCX control point AI 3 AI:9V17180 EBUS DIST HUB EBUS5 distribution hub N/A

Supply Fan Control Signal 0-10VDC VCCX control point AO 1 AI:22R62330 Proof of Air Flow VCCX control point BI 1 BI:6

Safety Shut Down VCCX control point BI 8 BI:26Supply Fan Configured Relay point BI:63Heat 1 Configured Relay Point BI:64Heat 2 Configured Relay Point BI:65

VCCX Components

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:27 PM

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)

JOB INFORMATION: WHEEL SPECIFICATION: Job Name: Max RPM: Job Tag: Diameter x Qty: Rep Firm: CFM: Date: Tip Speed:

Inertia:

BCH Life Guard 3,450Split AHU # 1 11.2 in. x 1

90005/01/2019 6,548 FPM

3 WR²

OPERATING CONDITIONS: MOTOR SELECTION: Air Flow: Rated HP / Bypass: Static Pressure: Frame Size: Relief Dampers DP: Nominal RPM:

VAC/PH/HZ: TSP: Efficiency Site Altitude: Enclosure Type: TSP @ Sea Level: Max Inertial Load:

900 CFM 1.1 / No1.01 in. Wg. ECM0.00 in. Wg. 1760

208/3/601.01 in. Wg. Premium / 0.8550.00 Ft ODP1.01 in. Wg. 27 WR²

FAN PERFORMANCE: FAN SOUND POWER (Inlet/Outlet): RPM: Octave Band: (Re 10^-12 watts) BHP: 1 2 3 4 5 6 7 8 Efficiency: In/Out Velocity: Plenum Out Velocity: SOUND POWER A-Weighted: 69 / 73 dB

Max Duct SP with Blocked Airway: 1.9 in. Wg. @ 2237 rpm

22370.2851.1% 64 62 66 66 63 60 60 613913/1169 FPM 64 64 68 70 71 68 65 6310 FPM

RPM

BHP

SYSTEM

Efficiency

SP Surge

CFM Min

Supply Fan Model: 250AY @ 2237 RPM and 100% WidthDesign Conditions: 900 CFM @ 1.01" SP

CFM x 100010

SP1

0

BH

P

1

0

40%

20%

0%

RPM: 2237

BHP: 0.28

EFFICIENCY: 51.06

25.0" STAR Plenum

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:28 PM

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)

A1

A2

A3

A4

A5

1

2A

2B 3A

3B

4

5

6A

6B

6C

7

8A

8B

8C

8D

9

10

11

12

13

14

15

16

17

18

19

20

21

22

C FA -007-A -A-8 -D C00H :A-D0- E0 -00- 00 0-L- FE 00-0 0E 0G00-0 A0 00DB Tag: Split CU # 1

Job Name: BCH Life Guard Unit Submittal For: Job Number: H-19 Unit Submittal Date: May 01, 2019

Base Option Description

CF Generation CF - Condensing Unit

A Major Rev Major Revision

007 Unit Size Seven

A Series A Cabinet

A Revision Minor Revision

8 Voltage 208V/3Ø/60Hz

D Compressor Style R-410A Variable Capacity Scroll Comp

C Condenser Style Air-Cooled Condenser (Fin and Tube)

0 Configuration Standard

0 Coating Standard

H Staging 1 Variable Refrig System

Feature Option Description

A 1. Unit Orientation Horizontal Condenser Discharge Standard Access

D 2A. Refrigeration Control Adjustable Compressor Lockout

0 2B. Blank Standard

E 3A. Refrigeration Options Modulating Hot Gas Reheat [MHGR]

0 3B. Blank Standard

0 4. Refrigeration Accessories Standard

0 5. Blank Standard

0 6A. Unit Disconnect Type Standard Single Point Power Block

0 6B. Disconnect Size None

0 6C. Blank Standard

L 7. Accessories Phase & Brown Out Protection + Suction Pressure Transducer on Each Refrigeration System

F 8A. Control Sequence Makeup Air Unit Controller - CAV Cool + CAV Heat

E 8B. Control suppliers VCC-X (Main Controller in Air Handling Unit)

0 8C. Control Supplier Options Standard

0 8D. BMS Connection and Diagnostics Standard

0 9. Blank Standard

0 10. Blank Standard

E 11. Maintenance Accessories Remote Unit Start/Stop Terminals

0 12. Code Options Standard ETL U.S.A. Listing

G 13.Air Cooled Condenser Accessories Condenser Coil Guard + ECM Cond Fan / Head Pressure Control

0 14. Blank Standard

0 15. Blank Standard

0 16. Electrical Options Standard

A 17. Shipping Options Crating

0 18. Blank Standard

0 19. Blank Standard

0 20. Cabinet Material Standard - Galvanized Steel Cabinet

D 21. Warranty Extended Compressor Warranty - Years 2-5

B 22. Paint and SPAs Premium AAON Gray Paint Exterior

Unit Submittal

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:51 PM

2425 South Yukon Ave - Tulsa, Oklahoma 74107-2728 - Ph. (918) 583-2266 Fax (918) 583-6094AAONEcat32 Ver. 4.282 (SN: 6092064-)

A1

A2

A3

A4

A5

1

2A

2B 3A

3B

4

5

6A

6B

6C

7

8A

8B

8C

8D

9

10

11

12

13

14

15

16

17

18

19

20

21

22

C FA -007-A -A-8 -D C00H :A-D0- E0 -00- 00 0-L- FE 00-0 0E 0G00-0 A0 00DB

Tag: Split CU # 1 Job Name: BCH Life Guard VCCX For: Job Number: H-19 VCCX Date: May 01, 2019

Hardware Included For VCCX Controller

Part # Included Parts Assigned Channel BACnet PointV61520 DIGITAL REFRIGERATION MODULER42680 Comp Discharge Temp A RSMD point TEMP1 AI:56V38391 Suction Pressure Sensor A RSMD point AI1 AI:48V38410 Discharge Pressure Sensor A RSMD point HP-1 AI:50R63950 Modulated Condenser Signal A RSMD point AO1 BI:

Comp Status Input A RSMD point BIN1Emergency Shutdown RSMD point BIN4 BI:81,82Condenser Enable AB RSMD Fixed Relay point BI:78,BI:85Comp Enable A RSMD Fixed Relay point AI:46

V12100 MODULATING HOT GAS REHEAT MODULEReheat HGR Valve MHGRV-X AI:42

VCCX Components

Date Created/Modified: 5/1/2019 1:00:50 PM Using Ver 4.282 (OSN# 0123456) Date Printed: 5/1/2019 1:06:51 PM