630 series 1.3 IEC 61850 Protocol Implementation ... - ABB
-
Upload
khangminh22 -
Category
Documents
-
view
2 -
download
0
Transcript of 630 series 1.3 IEC 61850 Protocol Implementation ... - ABB
Relion® Protection and control
630 series 1.3 IEC 61850 Protocol Implementation eXtra Information for Testing
Table of content:
1 Introduction ................................................................................................................ 2 1.1 Contents of this document.............................................................................. 2
2 Related documents .................................................................................................... 2
3 PIXIT for Association model ..................................................................................... 3
4 PIXIT for Logical device model ................................................................................. 4
5 PIXIT for Logical node model .................................................................................... 4
6 PIXIT for Server model ............................................................................................... 4
7 PIXIT for Data set model ............................................................................................ 5
8 PIXIT for Substitution model ..................................................................................... 6
9 PIXIT for Setting group control model ..................................................................... 6
10 PIXIT for Reporting model ......................................................................................... 7
11 PIXIT for Logging model ............................................................................................ 8
12 PIXIT for Generic substation events model ............................................................. 8
13 PIXIT for Control model ........................................................................................... 10
14 PIXIT for Time and time synchronization model ................................................... 13
15 PIXIT for File transfer model ................................................................................... 14
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
2
1 Introduction
This document serves as the PIXIT document for the IEC 61850 implementation in the ABB 630 Series products.
The intention is to declare how the IEC 61850 is applied and used in the ABB 630 Series, version 1.3. The document is organized according to the IEC 61850 standard and lists the different aspects within the defined scope of this paper.
1.1 Contents of this document
Each chapter specifies the PIXIT for each applicable ACSI service model as structured in IEC 61850-10.
2 Related documents
Document Id Title
IEC 61850-5 (2003) Communication Networks and Systems in Substations – Part 5: Communication requirements for functions and device models
IEC 61850-6 (2003) Communication Networks and Systems in Substations Part 6: Configuration description language for communication in electrical substations related to IEDs
IEC 61850-7-1 (2003) Communication Networks and Systems in Substations Part 7-1: Basic communication structure for substation and feeder equipment – Principles and models
IEC 61850-7-2 (2003) Communication Networks and Systems in Substations Part 7-2: Basic communication structure for substations and feeder equipment – Abstract communication service interface (ACSI)
IEC 61850-7-3 (2003) Communication Networks and Systems in Substations Part 7-3: Basic communication structure for substation and feeder equipment – Common data classes
IEC 61850-7-4 (2003) Communication Networks and Systems in Substations Part 7-4: Basic communication structure for substation and feeder equipment – Compatible logical node classes and data classes
IEC 61850-8-1 (2003) Communication Networks and Systems in Substations Part 8-1: Specific communication service mapping (SCSM) – Mapping to MMS(ISO/IEC 9506 Part 1 and Part 2)
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
3
Document Id Title
IEC 61850-10 (2005) Communication Networks and Systems in Substations Part 10: Conformance testing
ABB 1MRS189725 630 series ver 1.3 - IEC 61850 MICS; Model Implementation conformance statement
ABB 1MRS189726 630 series ver 1.3 - IEC 61850 PICS; Protocol Implementation conformance statement
ABB 1MRS189728 630 series ver 1.3 – IEC 61850 TICS; Tissue Implementation conformance statement
3 PIXIT for Association model
Description Value / Clarification
Maximum number of clients that
can set-up an association
simultaneously
8
TCP_KEEPALIVE value 5 seconds
Lost connection detection time TCP_KEEPIDLE = 10 s TCP_KEEPCNT = 3 TCP_KEEPINIT = 10 s TCP_KEEPINTVL = 5s 10s after association start to begin sending keepalive, and 15s (3 * 5s) to detect lost connection.
Is authentication supported N
What association parameters are
necessary for successful
association
Transport selector Y
Session selector Y
Presentation selector Y
AP Title N
AE Qualifier N
If association parameters are
necessary for association,
describe the correct values e.g.
Transport selector 0001 (default)
Session selector 0001 (default)
Presentation selector 00000001 (default)
AP Title n/a
AE Qualifier n/a
What is the maximum and
minimum MMS PDU size
Max MMS PDU size 32000 bytes
Min MMS PDU size 128 bytes
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
4
Description Value / Clarification
What is the maximum startup time
after a power supply interrupt
2 minutes
4 PIXIT for Logical device model
Description Value / Clarification LD properties In addition to LD0, other LDs are
used to group LNs that belongs to a certain ‘aggregated’ functionality, for example distance protection.
5 PIXIT for Logical node model
Description Value / Clarification LPL Included, according to definitions
in ICD file. Health Always OK Beh - Supported values are ON,
Blocked, Test, Test/Blocked and OFF. However, the Test, Test/Blocked and OFF can only be set from Local HMI or PCM 600 (IED tool) - Test/Blocked also disables reporting
Mod Only values ON and Blocked are accepted. Other values results in negative response.
6 PIXIT for Server model
Description Value / Clarification
Which analogue value (MX)
quality bits are supported (can be
set by server)
Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
Y Overflow
Y OutofRange
N BadReference
N Oscillatory
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
5
Description Value / Clarification
N Failure
Y OldData
N Inconsistent
N Inaccurate
Source:
Y Process
Y Substituted
Y Test
Y OperatorBlocked
Which status value (ST) quality
bits are supported (can be set by
server)
Validity:
Y Good,
Y Invalid,
N Reserved,
Y Questionable
N BadReference
N Oscillatory
N Failure
Y OldData
N Inconsistent
N Inaccurate
Source:
Y Process
Y Substituted
Y Test
Y OperatorBlocked
What is the maximum number of
data values in one
GetDataValues request
Stack does not limit the amount of the data
values. MMS PDU is the limit
What is the maximum number of
data values in one SetDataValues
request
Stack does not limit the amount of the data
values. MMS PDU is the limit
7 PIXIT for Data set model
Description Value / Clarification
What is the maximum number of
data elements in one data set
(compare ICD setting)
maxAttributes = 300
maximum FCDAs = 150
-> whatever limit is reached first.
How many persistent data sets No online creation
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
6
can be created by one or more
clients
How many non-persistent data
sets can be created by one or
more clients
No online creation
8 PIXIT for Substitution model
Description Value / Clarification
Substitution Substitution of value is supported. The quality can not be substituted The subID is not used.
9 PIXIT for Setting group control model
Description Value / Clarification
What is the number of supported
setting groups for each logical
device (compare NumSG in the
SGCB)
Maximum 4, default value = 1 Same
setting group control block is used in all
LDs.
The amount of setting groups is set in the
configuration.
What is the effect of when and
how the non-volatile storage is
updated
(compare IEC 61850-8-1 $16.2.4)
Editing of setting group is not supported
using IEC 61850
Can multiple clients edit the same
setting group
Editing of setting group is not supported
using IEC 61850
What happens if the association
is lost while editing a setting
group
Editing of setting group is not supported
using IEC 61850
Is EditSG value 0 allowed? Editing of setting group is not supported
using IEC 61850
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
7
10 PIXIT for Reporting model
Description Value / Clarification
The supported trigger conditions
are
(compare PICS)
integrity Y
data change Y
quality change Y (*)
data update N (*)
general interrogation Y/
The supported optional fields are sequence-number Y
report-time-stamp Y
reason-for-inclusion Y
data-set-name Y
data-reference Y
buffer-overflow Y
entryID Y
conf-rev Y
segmentation Y
Can the server send segmented
reports
Y
Mechanism on second internal
data change notification of the
same analogue data value within
buffer period (Compare IEC
61850-7-2 $14.2.2.9)
Send report immediately
Multi client URCB approach
(compare IEC 61850-7-2 $14.2.1)
Each instance URCB is visible to one client
only, (allows also multiple clients on
one/same instance or one client/instance)
What is the format of EntryID Octet string 8
What is the buffer size for each
BRCB or how many reports can
be buffered
50000 bytes for each used BRCB (max.
100 BRCB instances)
Pre-configured RCB attributes
that cannot be changed online
when RptEna = FALSE
(see also the ICD report settings)
- DatSet
- ConfRev
- SqNum
- TimeofEntry
May the reported data set
contain:
- structured data objects?
- data attributes?
- timestamp data attributes?
Y
Y
Y
What is the scan cycle for binary 5 mseconds
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
8
events?
Is this fixed, configurable
Fixed
Supported FC’s Only functional constraints MX and ST can be included in datasets for reporting
Segmentation properties 1. In buffered reports the the max_pdu_size is stored after first connection to this buffered report. 2. If the reports is released by the client and another client enabling with bigger pdu_size the report still keeps the max_pdu_size set by the first client, which was enabling first. 3. If the reports is released by the client and enabled with smaller pdu_size, buffer is purged and enabled with the smaller size.
(*) accepted by server and will be reported as data-change.
11 PIXIT for Logging model
Description Value / Clarification
General Logging model is not supported
12 PIXIT for Generic substation events model
Description Value / Clarification
What elements of a subscribed
GOOSE header are checked to
decide the message is valid and
the allData values are accepted?
If yes, describe the conditions.
Note: the VLAN tag may be
removed by a ynchron switch
and should not be checked
N source MAC address
Y destination MAC address
Y Ethertype = 0x88B8
Y gocbRef
Y timeAllowedtoLive
Y datSet
Y goID
N t
Y stNum
Y sqNum
Y test
Y confRev
N ndsCom (value is ignored)
Y numDatSetEntries
Can the test flag in the published
GOOSE be turned on / off
N
What is the behavior when the N/A
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
9
Description Value / Clarification
GOOSE publish configuration is
incorrect
When is a subscribed GOOSE
marked as lost?
(TAL = time allowed to live value
from the last received GOOSE
message)
Message does not arrive prior to 2*TAL,
then the message is marked as lost at the
receiver. (Time allowed to live = MaxTime
as defined in IEC 61850 part 6).
Note that erroneous GOOSE telegrams
are discarded, and valid telegrams are
supervised according to TAL.
What is the behavior when one or
more subscribed GOOSE
messages isn’t received or
syntactically incorrect (missing
GOOSE)
Is ignored. Internal data is set to invalid if time allowed to live times out.
What is the behavior when a
subscribed GOOSE message is
out-of-order
Is ignored
What is the behavior when a
subscribed GOOSE message is
duplicated
Is ignored
Does the device subscribe to
GOOSE messages with/without
the VLAN tag?
Y, with the VLAN tag
Y, without the VLAN tag
May the GOOSE data set contain:
- structured data objects?
- data attributes?
- timestamp data attributes?
Subscribed Published
Y Y
Y Y
Y (*) Y
* not used in applications
What is the slow retransmission
time?
Is it fixed or configurable?
Configured by IED tool (have to be > than
the fast retransmission time, and =<60 000
ms) Can not be set <100ms.
What is the fast retransmission
scheme?
Is it fixed or configurable?
Configured by IED tool (>1ms)
Can the Goose publish be turned
on / off by using
SetGoCBValues(GoEna)
N
Properties of updated
messages/data.
The value, quality and time is handled as
one property, e.g. if one of these changes,
there will be a data update sent for all.
Is AppId required in Goose Y
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
10
Description Value / Clarification
message?
How does the receving IED treat
Goose message with T = true and
needs commissioning?
The received data will be treated as
invalid.
TAL = Time Allowed to Live
13 PIXIT for Control model
Description Value / Clarification
What control modes are
supported
(compare PICS)
Y status-only
Y direct-with-normal-security
N sbo-with-normal-security
N direct-with-enhanced-security
Y sbo-with-enhanced-security (only for
DPC)
Is the control model fixed,
configurable and/or online
changeable?
Fixed.
Can be changed for some functions using
the PCM 600 IED tool.
Is Time activated operate
(operTm) supported
N
Is “operate-many” supported N
What is the behavior of the DUT
when the test attribute is set in
the SelectWithValue and/or
Operate request
Test mode is not supported
What are the conditions for the
time (T) attribute in the
SelectWithValue and/or Operate
request
Not supported
Is pulse configuration supported N
What is the behavior of the DUT
when the check conditions are set
Is this behavior fixed,
configurable, online changeable?
Y synchrocheck
Y interlock-check
This is only applicable for CSWI.pos,
otherwise ignored. Note also the both
conditions are checked during operate
phase. When supported, these checks can
not be configured.
What additional cause diagnosis
are supported
Y Blocked-by-switching-hierarchy
N Select-failed
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
11
Description Value / Clarification
Y Invalid-position
Y Position-reached
Y Parameter-change-in-execution
Y/N Step-limit
Y Blocked-by-Mode
Y Blocked-by-process
Y Blocked-by-interlocking
Y Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
Y 1-of-n-control
Y Abortion-by-cancel
N Time-limit-over
N Abortion-by-trip
Y Object-not-selected
How to force a “test-not-ok”
respond with SelectWithValue
request?
Not supported
How to force a “test-not-ok”
respond with Select request?
Not supported
How to force a “test-not-ok”
respond with Operate request?
Not supported
Which origin categories are
supported?
Bay-Control, Station-Control, Remote-
Control, Automatic-Bay.
orCat is only checked for DPC and SPC
DATA’s for the logical node types
GNRLCSWI, LSHDPFRQ, OLATCC,
SPC8GGIO, VSGGIO and SLGGIO (*).
This means that the check of
Local/Remote switch will only occur for
these attributes.
What happens if the orCat is not
supported?
DOns: Rejected for the above(*)
SBOns: Not Supported
DOes: Not Supported
SBOes: Rejected for the above(*)
Rejected means returning addCause
Blocked-by-switching-hierarchy
Does the IED accept a
selectwithvalue/operate with the
same ctlVal as the current status
value?
DOns: Y
SBOns: Not Supported
DOes: Not Supported
SBOes: Y
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
12
Description Value / Clarification
- The “position reached” is generated as a cmdTerm. This addCause is not responded for select nor operate.
- For CSWI.pos; To change a 1,1 or 0,0 position requires additionally a interlock bypass, i.e. no interlock check.
Does the IED accept a
select/operate on the same
control object from 2 different
clients at the same time?
DOns: N
SBOns: Not Supported
DOes: Not Supported
SBOes: N
Does the IED accept a
select/selectwithvalue from the
same client when the control
object is already selected (tissue
334)
SBOns: Not Supported
SBOes: N
Is for SBOes the internal
validation performed during the
SelectWithValue and/or Operate
step?
The Check synchrocheck/interlock is made
during Operate phase. For others, e.g.
blocked, the evaluation is done during
select phase.
Can a control operation be
blocked by Mod=Off or Blocked
Mod = off is not supported.
Control operation is blocked in Block state
(Y)
Does the IED support local /
remote operation?
Y
Vendor Specific additional cause
diagnosis
(note: all these addCauses have negative value)
- 23 blockedForCommand
- 24 blocked-for-open-command
- 25 blocked-for-close-command
- 30 longOperationTime
- 31 switch-not-start-moving
- 32 persistent-intermediate-state
- 33 switch-returned-to-initial-position
- 34 switch-in-bad-state
- 35 not-expected-final-position
Handling of cancel - Cancel is only accepted in select phase - Cancel is accepted from other clients
(different from the client making a select)
Handling of ctlNum - Is not checked/evaluated by the server
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
13
14 PIXIT for Time and time synchronization model
Description Value / Clarification
What quality bits are supported N LeapSecondsKnown
Y ClockFailure
Y ClockNotSynchronized
Describe the behavior when the
time synchronization
signal/messages are lost
The ABB 630 Series can have 2 configured SNTP Servers. If the first fails, the second is taken into use. There is an automatic switch ‘back’ if an erroneous one comes operable. If all SNTP servers are off-line the event timestamps get ClockFailure and ClockNotSynchronized status. The time to detect error and change to 2nd server is 2 seconds. If no backup server is defined, there is a
timeout of 5 minutes.
When is the time quality bit “Clock
failure” set?
Upon start of the IED, until synchronization is received. As the time system is self-adjusted, the clock failure is set when the estimated deviation exceeds a certain value. Due to the good internal accuracy, this deviation occurs in the order of > 30 days.
When is the time quality bit “Clock
not ynchronized” set?
Loss of time synchronization
Is the timestamp of a binary event
adjusted to the configured scan
cycle?
N
Does the device support time
zone and daylight saving?
Y
Which attibutes of the SNTP
response packet are validated?
Y Leap indicator not equal to 3
N Mode is equal to SERVER
Y OriginateTimestamp is equal to
value sent by the SNTP client as
Transmit Timestamp
Y RX/TX timestamp fields are
checked for reasonableness
Y SNTP version 4
Document ID: 1MRS189727 630 series protection and control IED
Issued: 2014-06-10 IEC 61850 Protocol Implementation eXtra Information for Testing
Revision: E
14
15 PIXIT for File transfer model
Description Value / Clarification
What is structure of files and
directories?
/COMTRADE/<files>
Is the IETF FTP protocol also
implemented
Y
Directory names are separated
from the file name by
“/” or “\” works for FTP transfer
“/” for MMS
The maximum file name size
including path (recommended 64
chars)
Not defined
Are directory/file name case
sensitive
N
Maximum file size Not defined, free space varies and
depends on size of the configuration.
~800kB.
Is the requested file path included
in the file name of the MMS
fileDirectory respond?
Y
Is the wild char supported MMS
fileDirectory request?
Yes, wild card = * or *.* or empty string
Is it allowed that 2 client get a file
at the same time?
N
FTP authentication Y