PREPARED FOR: BUNCOMBE COUNTY FACILITIES DEPARTMENT
PRELIMINARY PROJECT DESCRIPTION: BUNCOMBE COUNTY COMMUNITY HIGH SCHOOL
235 OLD US HIGHWAY 70SWANNANOA, NORTH CAROLINA 28778
Executive Summary ............................................................................... 3
Basic Assessment of Existing Conditions .......................................... 4
Basic Site Assessment .......................................................................................... 4
Basic Exterior Assessment .................................................................................... 5
Basic Interior Assessment of Gymnasium ............................................................. 6
Design Approach ................................................................................... 7 Option 1 Proposal: Conceptual Site Plan .............................................................. 8
Option 1 Proposal: Conceptual Floor Plan ............................................................ 9
Option 1 Proposal: Conceptual Images ............................................................... 10
Option 1 Proposal: Gymnasium Improvements ................................................... 13
Option 2 Proposal: Conceptual Site Plan ............................................................ 14
Option 2 Proposal: Conceptual Floor Plan .......................................................... 15
Option 2 Proposal: Conceptual 3D Images ......................................................... 16
Basic Project Program and Design Criteria ...................................... 19
Survey and Basic Site Analysis ........................................................................... 21
Exterior Walls and Openings ............................................................................... 22
Structure and Wall Assembly ............................................................................... 23
Floor Assembly .................................................................................................... 24
Roof Assembly ..................................................................................................... 25
Mechanical and Electrical .................................................................................... 26
Doors and Openings ............................................................................................ 27
Interior Finishes ................................................................................................... 27
Vertical Circulation ............................................................................................... 27
Existing Masonry Facade .................................................................................... 27
Building Code Summary ................................................................... 28
Option 1 ............................................................................................................... 29
Option 2 ............................................................................................................... 31
Cost Study .......................................................................................... 33
Option 1 ............................................................................................................... 34
Option 2 ............................................................................................................... 38
Appendix A ......................................................................................... 41
Report of Preliminary Geeotechnical Evaluation ................................................. 42
Document Prepared & Authored By:
Aiton Anderson Architecture 12 Church Street Asheville, NC 28801 828.989.5154
Sparc Design, PC 35 Haywood Street, Suite 203 Asheville, NC 28801 828.774.5029
For the Sole Use By:
Owner Buncombe County Schools Facilities and Planning 175 Bingham Road Asheville, NC 28806
SPARC DESIGN
PRELIMINARY PROJECT DESCRIPTION TABLE OF CONTENTS
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
PRELIMINARY DESIGN APPROACH FOR OPTION 1This approach aims to preserve the gymnasium and front facade of the existing building and construct a new two story classroom building and cafeteria and kitchen located behind the original facade. A new “front porch” will connect the existing building to the new addition. The project will involve phased construction.
New construction aims to be efficient and cost effective by taking cues from industrial metal buildings. The new building will be located east of the existing building. Patterning and color selections add variation and a pleasing aesthetic.
The probable construction cost for Option 1 is $7.9 million dollars.
EXECUTIVE SUMMARY
EXISTING FACILITYThe existing facility poses significant challenges to bring up to building code and achieve compliance with the accessibility code. However, the existing gymnasium is in good condition. In addition, the building on the site has been a proud fixture of the Swannanoa community since 1926.
The existing 8.97 acre site is relatively flat and offers potential for expansion, renovation or new construction.
PRELIMINARY DESIGN APPROACH FOR OPTION 2This approach takes advantage of the existing relatively flat site on the existing property, north of the existing school. An entirely new facility would be constructed.
Like Option 1, new construction aims to be efficient and cost effective by taking cues from industrial metal buildings. Patterning and color selections add variation and a pleasing aesthetic.
The probable construction cost for Option 2 is $8.9 million dollars.
OPTION 1
OPTION 2
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 3 of 55
BASIC ASSESSMENTSITE
• Site is cleared and already graded, relatively flat.
• Floodplain encroaches on the south side of the site.
• Site has access from Old Highway 70, as well as Bee Tree Road.
• An existing 36” underground storm water culvert runs through the site to the west of the existing school building.
• BCS records show a gymnasium was demolished to the east of the existing school building and the current gym was previously an auditorium with a sloped floor. Refer to geotechnical report for further information.
• The site is zoned ‘PS’ Public Service according to the current Buncombe County Zoning Map and Ordinance, as well as the adjacent property to the west. Properties across the street to the south are zoned Residential ‘R-3’ and ‘R-1’ to the east.
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
AERIAL IMAGE OF EXISTING PROPERTY
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 4 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
• The building has been a fixture of Swannanoa since 1926.
• Overall, the existing brick veneer is in fair condition.
• The existing accessible ramp and front porch in poor condition and need of repair.
• The main entry to the building is not clear to new visitors or guests. The entry is not directly adjacent to the administrative area, which is not ideal.
• There are currently two portable classrooms to the east of the primary building serving as classrooms. The cafeteria is also located in a portable building located north of the main building.
• The current programmatic needs of the high school are currently not being met within the existing building footprint.
BASIC ASSESSMENTEXTERIOR
EXISTING FRONT FACADE OF COMMUNITY HIGH SCHOOL
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 5 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
BASIC ASSESSMENTINTERIOR - GYMNASIUM
• The overall interior of Community High School has been documented as in need of major repairs to bring the building into code compliance, both from a building code and accessibility aspect.
• The existing entry lobby to the gymnasium is suitable for re-use with minimal interior improvements.
• The existing gymnasium is in good condition and is suitable for reuse. There is the need for a new roof, new hvac system, exterior windows and doors, and new interior paint.
EXISTING GYMNASIUM LOBBY
EXISTING GYMNASIUM INTERIOR COURT
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 6 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
DESIGN APPROACH
SITEThe site is nearly 9 acres and relatively flat. This provides a good opportunity for additions, expansions and also phased construction. Both design options capitalize on the existing owned site.
EXISTING FACILITYThe cost to upgrade the existing high school to be compliant from an accessibility and building code aspect would be very costly. Unfortunately, the facility would still not house all the program needed as there are currently 3 portable buildings to supplement space needs.
However, the gymnasium is in good condition. In addition, the building itself holds tradition for the community of Swannanoa.
As such, the first design option proposes to work with strengths of the existing building and preserve the existing gymnasium and front facade. An efficient two-story volume addition with code-compliant and properly sized classrooms and auxiliary programs will be constructed.
CUES FROM A METAL BUILDINGTasked with the challenge of creating an efficient, well-functioning school that serves the needs of the existing Community High School, the construction approach of the two preliminary options takes cues from industrial metal buildings. An industrial approach of repetitive structural bays, structural strategies and metal cladding will allow this project to be constructed in a budget less than that of a traditional new high school.
The overall aesthetic of the exterior remains high quality and one that students and faculty can be proud to call their school.
The overall interior finishes are highly functional. Each material is present for functional reasons, such as acoustic dampening, durability, or low maintenance. Excess finishing and trim can add additional costs, and is therefore not part of this approach.
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 7 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
BEE TREE ROAD
PROPERTY LINESETBACK OLD US HIGHWAY 70
OPTION FORFUTURE ADDITION
OPTION FORFUTURE
ADDITION
PLAYING FIELDS
AGRICULTURALBUILDINGS AND GARDEN
ADDITIONALPARKING
• Maintain existing driveway accessed from Old US Highway 70.
• Maintain use of existing gymnatorium.
• Retain front brick wall facade of existing school.
• Provide a new two story classroom building to the west of the gymnatorium. The angular placement allows there to be daylight and green space between the existing gym and proposed addition, while maintaining property setbacks.
• Provide a new cafeteria and kitchen behind the existing school facade.
• Existing fields in the north west remain untouched.
• Existing agricultural buildings remain.
• Phased construction will be used so that the primary high school can maintain operations during construction of the two story space. The existing portable cafeteria can be demolished once the new cafeteria is built.
• A preliminary geotechnical report revealed that the proposed new construction is located on generally consistent soils which is good for shallow foundations. As expected, construction debris was found in test pits. Of the construction debris found, the majority can be compacted, crushed and remain on site. The existing water table related to Option 1 is approximately 10’-0” below grade. See Appendix A for more detailed information.
OPTION 1 PROPOSALSITE PLAN
CONCEPTUAL SITE PLAN
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 8 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
CAFETERIA
EXISTINGGYMNATORIUM
DAYCARE
ADMINISTRATION
KITCHEN
MAIN ENTRANCE
COURTYARD
PATIO PARKING
MEDIA CENTER
LEVEL 2
ALTERNATIVEPROGRAM
ADMINISTRATION
GYMNATORIUM
MEDIA CENTER / CAFETERIA / DAYCARE
CLASSROOMS
ALTERNATIVE PROGRAM
SERVICE0 10 20 50
• The main new building is an efficient double loaded corridor with classrooms, administration, and media center.
• The gymnatorium will remain.
• A new cafeteria and kitchen are provided behind the existing facade of the old high school.
• A new centralized entrance is provided with improved accessible ramp and widened stairs. Visitor check in and administration is visible from the main entrance.
• The angled two story volume allows for windows and daylight both in the new building and existing gymnatorium.
OPTION 1 PROPOSALFLOOR PLAN
FLOOR PLANS LEVEL 1 AND LEVEL 2
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 9 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
• Existing gymnatorium will remain intact.
• The brick front facade will remain and be infilled with the cafeteria and kitchen.
• A new “front porch” ties the existing gymnatorium with the addition. This will support the visual connection of the traditional building and new elements.
• The addition honors the gymnatorium with building placement. The addition allows the gymnatorium to be in front.
• The gymnatorium informs scale and building proportion of the new building. The two story classroom addition will be the same height. The window heights and brick horizontal detailing create datums that are carried into the new addition.
• The new entry is highly visible from the road and is also directly adjacent to the visitor check-in administration area.
• The addition is largely clad with metal panels. Visual interest is efficiently created with pattern and color. A clay or brick color is interspersed throughout the exterior, and a gradient of transition works it’s way from the rear corner.
OPTION 1 PROPOSALCONCEPTUAL IMAGE
BIRDS EYE VIEW
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 10 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
OPTION 1 PROPOSALCONCEPTUAL IMAGE
PERSPECTIVE FROM US HIGHWAY 70 ENTRY
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 11 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
OPTION 1 PROPOSALCONCEPTUAL IMAGES
PERSPECTIVE OF OPTION 1 FRONT ENTRY PERSPECTIVE OF OPTION 1 GYM / ADDITION CONNECTION AND FRONT PORCH
BIRDS EYE VIEW OF OPTION 1PERSPECTIVE OF OPTION 1 RE-PURPOSED BRICK FACADE
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 12 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
Option 1 will connect to the existing gymnasium lobby at the stairs. Stairs will be demolished with new open stairs to be located inside the low portion of the gym.
The gym floor and entry lobby have approximately 4” elevation difference. To provide a compliant entrance, create a new 4’ ramp inside.
Exterior facade improvements include demolishing the existing ramp system, repair existing porch and baluster, replace all windows of the gymnasium
The existing gym will remain largely untouched.
This portion of the existing exterior facade will face Option 1. The existing yard will become a planted courtyard.
There is a rear exit and side (rear) exit that come out on wood stairs. The project will bring stairs/handrails into compliance.
OPTION 1 PROPOSALGYMNASIUM IMPROVEMENTS
EXISTING GYMNASIUM LOBBY EXISTING GYMNASIUM INTERIOR COURT
EXISTING ENTRY TO GYMNASIUM EXISTING EAST FACADE OF GYMNASIUM
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 13 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
• New entry and parking with access from Bee Tree Road.
• Utilize the relatively flat north field on the existing property to construct a new one story high school.
• All current programs and accessory buildings of the current Community High School will remain in operation throughout construction of new building.
• Agricultural buildings are unaffected.
• Overall form of new building based on existing property lines and setbacks.
• A preliminary geotechnical report revealed that the proposed new construction is located on generally softer soils which poses challenges for construction. It is assumed that this portion of the site was old farm land, thus softer soils are expected. To prepare the area for new foundations, removal and replacement of unsuitable soils will need to occur. The existing water table of the site related to Option 2 is approximately 5’-0” below grade. See Appendix A for more detailed information.
OPTION 2 PROPOSALSITE PLAN
CONCEPTUAL SITE PLAN
BEE TREE ROAD
PROPERTY LINESETBACK OLD US HIGHWAY 70
OPTION FORFUTURE
ADDITION
OPTION FORFUTURE
ADDITION
AGRICULTURALBUILDINGS AND GARDEN OPTION TO DEMOLISH
EXISTING BUILDING
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 14 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
• The new one story building takes it’s form from the borders of the property. There are two main volumes that include an efficient double loaded corridor.
• One story reduces the need for an elevator and ground floor exits are easily provided.
• The building fronts Bee Tree Road with communal and public programs near the entry.
• A new gymnatorium is oriented such that after hours use is possible while locking the rest of the school.
• Main entry is adjacent to visitor check-in / administration.
OPTION 2 PROPOSALFLOOR PLAN
OPTION 2 FLOOR PLAN
CAFETERIA
KITCHEN
DAYCARE
GYMNATORIUM
ADMINISTRATION
MEDIA CENTER
COURTYARD
MAIN ENTRANCE
PARKING
BEE TREE ROAD
ALTERNATIVEPROGRAM
ADMINISTRATION
GYMNATORIUM
MEDIA CENTER / CAFETERIA / DAYCARE
CLASSROOMS
ALTERNATIVE PROGRAM0 10 20 50
SERVICE
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 15 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
• The one story building has several taller areas to provide a sense of scale and create identity.
• The gymnatorium is a two story volume for functional reasons.
• The main entry is made prominent with a taller space and low sloped roof.
• The cafeteria is also a higher volume.
• Similar to Option 1, the building is largely clad with metal panels and glazing. The metal panel patterns are used to create visual interest. Colors are used to block out programmatic areas.
• Public and communal spaces, such as the media center and cafeteria, have increased glazing to allow more natural daylight.
OPTION 2 PROPOSALCONCEPTUAL IMAGE
BIRDS EYE VIEW
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 16 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
OPTION 2 PROPOSALCONCEPTUAL IMAGE
PERSPECTIVE FROM BEE TREE ROAD
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 17 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
OPTION 2 PROPOSALCONCEPTUAL IMAGES
PERSPECTIVE OF OPTION 2 FRONT ENTRY PERSPECTIVE OF OPTION 2 ADMINISTRATIVE AREA
BIRDS EYE OF OPTION 2 BIRDS EYE OF OPTION 2
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 18 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
PROGRAM AND DESIGN CRITERIA
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 19 of 55
PROGRAM AND DESIGN CRITERIABASIC OVERVIEW AND SCOPE
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
THE PROJECT
This preliminary project description document defines the scope of work for the construction and renovations of two distinct options for the Community High School in Swannanoa, North Carolina. Both options utilize the existing site at 235 Old U.S. Highway 70. One option preserves a portion of the existing 1926 historic structure and facade with the addition of a two story classroom wing. Another option is an entirely new one story high school facility. Based on the program information provided by Buncombe County Schools facilities planning department, both options are approximately 50,000 gross square feet in area. For comparison, the existing facility is 38,800 square feet plus about 7,200 square feet in portable classrooms.
DESIGN CRITERIA
Building Codes Summary:• Building Code edition: Currently NC 2012 (IBC 2009 with state
amendments) until 2018.• Building construction summary: non-combustible materials
throughout; structural steel frame construction with bar joists and concrete floor slab on grade with composite concrete slab on metal deck for elevated floors.
• Construction Classification - Type II-B (IBC Chapter 6). Non-fire-rated non-combustible structure and exterior walls.
• Life safety systems and fire protection requirements: Fire alarm notification system throughout with pull stations adjacent to exits. Fire sprinkler system throughout (NFPA-13). 2 hour fire rated stair and elevator shafts of 8” CMU, with 90 minute rated steel fire doors. Corridors are not required to be rated because of fire sprinkler system.
The following authorities have jurisdiction over the plan review and code approvals for the project:
• Buncombe County Planning & Development – Zoning Ordinance of Buncombe County
• Building permits & fire marshal – Buncombe County Permits & Inspections Department and Buncombe County Fire Marshal.
• NC Department of Public Instruction requires facilities to meet the Public Facilities of North Carolina Facilities Guidelines.
PROGRAM
The following evaluation of the Owner’s architectural program for the facility has been derived from facility usage diagrams of the existing building, diagrammatic building plans provided by the Facilities Planning department, and the Public Schools of North Carolina Facilities Guidelines. An official programming analysis is recommended should the project be approved to move forward.
PROGRAM - SITE
The Owner’s program for outdoor facilities is based largely on the existing site and current outdoor program activities. Unless otherwise noted in the specifications narrative description for specific area, outdoor facilities are existing to remain.
GENERAL REQUIREMENTSThe terms for the construction shall be AIA Document “A201 General Conditions for the Contract for Construction” and the associated AIA contracts and forms, along with the Owner’s supplemental general conditions.
The contractor shall be responsible for procuring and paying for all permits relative to the demolition, clearing, sitework and construction of the facility. The contractor shall include full-time on-site supervision throughout the project. Temporary facilities including a jobsite trailer with toilet and appropriate temporary worker sanitation facilities shall be provided. Contractor shall be responsible for removal of all demolition waste and construction debris.
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 20 of 55
SITE
The site has been cleared and graded for the existingfacilities, and is generally flat. Clearing and gradingwork is expected to be fairly minimal for this site.Grading and earthwork will include foundationexcavation, backfill and rough and fine grading toaccomplish the building construction. Earthworkoperations will be performed in accordance with therecommendations of the Owner's local geotechnical andcivil engineers. Final site design to achieve balancedcut/fill on site. Areas to receive bituminous and concretepaving outside the areas of the building structure shallbe cut and filled to the grades designed by the Engineerof record. Fill work in these areas will be with on-sitematerial, compacted to 95% Proctor density. A smallstormwater raingarden is anticipated for stormwatercontrols in compliance with state of North Carolinaregulations. New parking area and court paving shall be6” stone base course with 1 1/2” FABC asphalt topping,with 18” concrete curb and gutter around perimeter.Entry drive for school bus dropoff shall be heavy dutypaving, 2” asphalt on 8” stone base.
Utilities shall be installed in accordance with local codesand utility company specifications. Provide a new2” water line for domestic service, and an 8” water linefor fire sprinkler system. Assume adequate pressure isavailable for the fire suppression system, and a firepump is not necessary. Provide 6” sanitary sewerconnection to the existing 8” line in Old Hwy 70.Assume sheet flow of stormwater to the raingarden.Existing 36” storm pipe thru the site shall be reroutedaround the footprint of new construction. The powercompany shall provide new service and transformer forthe new construction. Assume the gas company willprovide new 2” pressurized gas line to the new building.
Provide 8' high visual screening fence along westproperty line for the portion of the site being developedwith new building. New sidewalks shall be 4” broomfinished 4,000 psi concrete with joints at 5' on center.
The existing daycare facility building shall bedemolished.
PROGRAM AND DESIGN CRITERIASITE
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
The site has been cleared and graded for the existing facilities, and is generally flat. Clearing and grading work is expected to be fairly minimal for this site. Grading and earthwork will include foundation excavation, backfill and rough and fine grading to accomplish the building construction. Earthwork operations will be performed in accordance with the recommendations of the Owner’s local geotechnical and civil engineers. Final site design to achieve balanced cut/fill on site. Areas to receive bituminous and concrete paving outside the areas of the building structure shall be cut and filled to the grades designed by the Engineer of record. Fill work in these areas will be with on-site material, compacted to 95% Proctor density. A small storm water rain-garden is anticipated for stormwater controls in compliance with state of North Carolina regulations. New parking area and court paving shall be 6” stone base course with 1 1/2” FABC asphalt topping, with 18” concrete curb and gutter around perimeter. Entry drive for school bus dropoff shall be heavy duty paving, 2” asphalt on 8” stone base.
Utilities shall be installed in accordance with local codes and utility company specifications. Provide a new 2” water line for domestic service, and an 8” water line for fire sprinkler system. Assume adequate pressure is available for the fire suppression system, and a fire pump is not necessary. Provide 6” sanitary sewer connection to the existing 8” line in Old Hwy 70. Assume sheet flow of storm water to the rain-garden. Existing 36” storm pipe thru the site shall be rerouted around the footprint of new construction. The power company shall provide new service and transformer for the new construction. Assume the gas company will provide new 2” pressurized gas line to the new building.
Provide 8’ high visual screening fence along west property line for the portion of the site being developed with new building. New sidewalks shall be 4” broom finished 4,000 psi concrete with joints at 5’ on center.
The existing daycare facility building shall be demolished.
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 21 of 55
EXTERIOR WALLS & OPENINGS
INSULATED METAL PANELS
ALUMINUM WINDOWS
INSULATED METAL PANELS
FULL HEIGHT ALUMINUMSTOREFRONT WINDOWS
NEW GYM MEDIA CENTER CLASSROOMS CAFETERIA
2 STORY ADDITIONNEW ENTRYWAYEXISTING GYM
INSULATED METAL PANELS
ALUMINUM WINDOWS
EXISTING GYM WINDOWSTO BE REGLAZED
FULL HEIGHT ALUMINUMSTOREFRONT ENTRY
ARCHITECTURAL CMUSITE WALLS
PROGRAM AND DESIGN CRITERIAEXTERIOR WALLS AND OPENINGS
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
All insulation values shall meet the prescriptive requirements of the North Carolina Energy codes. No additional insulation, energy efficiency requirements or LEED certification is assumed.
Exterior walls shall be finished with architectural insulated metal wall panels. Panels are concealed fastener, 26 gauge interior and exterior metal faced insulated sandwich panels. The basis of design is MBCI EcoFicient panel, 42” wide and 2.5” thick, installed vertically screwed to horizontal steel wall girts. The building will utilize two different color/texture of metal panels in the design of the exterior walls. Interior face of panels shall be white.
All doors shall be 36”x84”x1 3/4”. Exterior doors shall be heavy duty insulated steel doors with 14 gauge hollow metal steel frames, doors and frames painted. Door hardware shall be heavy duty ADA with USD32 finish. No overhead doors will be provided.
All windows and glass entry shall be thermally broken aluminum storefront system, Kawneer trifab 451T or equal. Clear anodized finish. Entry doors shall be heavy duty medium stile aluminum and glass entry doors with ADA hardware and proprietary keying. All windows shall be fixed pane, no operable windows.
All exterior glazing shall be 1” insulated glazing units with low-e coating, Solarban 70 or equal.
The site walls along the front of the building shall be 8” thick shot-blast face architectural concrete masonry units. Reinforcing shall be provided in accordance with NC code requirements for seismic design, assume #4 bars installed vertically with fully grouted cores at 48” on center, and ladder reinforcing at 24” on center. Bond beams at top of walls with two #4 bars continuous, and a solid cap ½ high block on top.
OPTION 2
OPTION 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 22 of 55
ALUMINUM WINDOW W/1" INSULATED GLAZING
METAL FACEDINSULATEDWALL PANEL
CONTINUOUSHORIZONTAL8" ZEE GIRT,14 GAUGE STEEL
8" CEE GIRT,14 GAUGE STEELWINDOW HEAD,JAMB & SILL
CONTINUOUS STEELBASE ANGLE
14'-0
"14
'-0"
ALUMINUM WINDOW W/1" INSULATED GLAZING
METAL FACEDINSULATEDWALL PANEL
CONTINUOUSHORIZONTAL8" ZEE GIRT,14 GAUGE STEEL
8" CEE GIRT,14 GAUGE STEELWINDOW HEAD,JAMB & SILL
CONTINUOUS STEELBASE ANGLE
18'-0
"
(VA
RIE
S)
STRUCTURE & WALL ASSEMBLY
FOUNDATIONDRAIN PIPE
PROGRAM AND DESIGN CRITERIASTRUCTURE AND WALL ASSEMBLY
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
The building is designed with a conventional structural steel frame, wide flange columns and beams with steel bar joists and girders with composite concrete elevated slabs on metal deck. The structural system does not require fire rated protection. Columns are generally spaced 30’ to 40’ apart, with exterior wall wind columns at ½ span. Assume columns to be W12x50’s. Exterior walls shall have 8” steel Z-girts installed horizontally at 60” on center, welded with steel angle supports to exterior wall columns. All structural steel shall be primer gray finish, unpainted.
The building is designed with a shallow foundation system and assumes no major geotechnical issues or groundwater issues on the site. All foundations shall be installed below frostline, min. 18” deep. Column footing assumptions: For two story and hi-bay areas, the column footings shall be 96”x96”x20” with nine #6 steel reinforcing bars each way. For single story areas, the footings shall be 60”x60”x16” with five #5 bars each way.
Concrete perimeter foundation walls shall be minimum 8” thick with #4 bars at 12” on center horizontal and vertical. Perimeter foundation walls shall bear on 24”x12” concrete footing with three #5 bars continuous, and #5 L dowels at 18” on center.
OPTION 2 OPTION 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 23 of 55
BAR JOISTS
FLOOR ASSEMBLY
CONCRETE SLAB ONMETAL FLOOR DECKING
4" CONCRETE SLAB ON GRADE
WELDED WIRE FABRIC
10 MIL. POLY. V.B.
WASHED STONE
PROGRAM AND DESIGN CRITERIAFLOOR ASSEMBLY
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
Elevated floor slab shall be 5” total thickness concrete composite slabs on corrugated metal floor decking on bar joists and girders. Floors shall be designed to accommodate a live load of 100 psf with a maximum total deflection of L/360.
Floor slab on grade shall be 4” thick 3,000 psi concrete with welded wire fabric and 10 mil polyethylene vapor barrier with a 4” washed stone base. Turndown exterior perimeter slab edge to 12” thick. 1/4” per 10’ tolerance for flatness, and sawcut joints around columns and along column lines and at midpoints between column lines, approximately 20’ apart.
Concrete perimeter foundation walls shall be minimum 8” thick with #4 bars at 12” on center horizontal and vertical. Perimeter foundation walls shall bear on 24”x12” concrete footing with three #5 bars continuous, and #5 L dowels at 18” on center.
OPTION 1 & 2
OPTION 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 24 of 55
SINGLE PLYMEMBRANE ROOF
ROOF ASSEMBLY
All insulation values shall meet the prescriptiverequirements of the North Carolina Energy codes. Noadditional insulation, energy efficiency requirements orLEED certification is assumed.
Roof system shall be single ply membrane,mechanically attached TPO roof system with a 60 milmembrane. Roofer shall provide rigid insulation meetinga minimum of R-30 with 1/2” high densitypolyisocyanurate cover board.not be requiredperimeter of flat roof areasfabricated and finished metal roof coping with integraldrip edge around roofing perimeter. One roof hatch36”x96” shall be installed with a ships ladder for roofaccess.
The roof structure shall be sloped to drains or guttersFlat roof areas shall be drained by roof drains withintegral overflow drain. Drains shall be located near thecenter structural line of the building and spaceapproximately 30' apart.
METAL SOFFIT PANEL
METAL COPING
BAR JOISTS
12" COVER
BOARDR-30 POLY-ISOCYANURATE
INSULATIONMETAL DECK
122
121/4
121/2TAPERED INSULATION
AROUND PERIMETERROOF DRAIN W/OVERFLOW
PROGRAM AND DESIGN CRITERIAROOF ASSEMBLY
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
All insulation values shall meet the prescriptive requirements of the North Carolina Energy codes. No additional insulation, energy efficiency requirements or LEED certification is assumed.
Roof system shall be single ply membrane, mechanically attached TPO roof system with a 60 mil membrane. Roofing contractor shall provide rigid insulation meeting a minimum of R-30 with 1/2” high density polyisocyanurate cover board. Tapered insulation will not be required except for 4’ wide section of the perimeter of flat roof areas. Include a two-piece factory fabricated and finished metal roof coping with integral drip edge around roofing perimeter. One roof hatch 36”x96” shall be installed with a ships ladder for roof access.
The roof structure shall be sloped to drains or gutters. Flat roof areas shall be drained by roof drains with integral overflow drain. Drains shall be located near the center structural line of the building and space approximately 30’ apart.
OPTION 2
OPTION 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 25 of 55
SPIRAL DUCT,PAINTED
FOUNDATIONDRAIN PIPE
SUSPENDED LED LIGHTING,BASIS OF DESIGN- PHILIPSLEDALITE FLOATPLANE EDGE
10'-0
"
ROOF DRAINS
PVC PIPINGTO STORMWATERPIPING UNDERSLAB
PROGRAM AND DESIGN CRITERIA MECHANICAL AND ELECTRICAL
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
The building is designed with an automatic fire sprinkler system throughout in accordance with NFPA-13. The system shall include emergency monitoring, and be coordinated with the fire alarm system.
All domestic water piping shall be cross-linked polyethylene (PEX) with brass fittings. Waste piping shall be PVC. All horizontal piping insulated in accordance with codes.
Plumbing fixtures shall all be ADA type vitreous china, wall mounted with heavy duty steel wall brackets. Provide two student restrooms for each sex with each restroom to include: four water closets, with one meeting ADA clearance requirements, and two ADA lavatories. Provide one male and one female employees restrooms, each with two water closets, with one meeting ADA requirements, and two lavatories. Provide two ADA hi/lo electric water coolers with bottle fillers.
A roof drain system with PVC piping shall be provided to the existing storm drain system.
Heating and cooling shall be provided to the building with rooftop packaged heat pump units with 2 stage gas heat. Assume five rooftop units with 30 ton capacity each. Air supply shall be provided with exposed oval spiral duct and louvers, painted.
Based on historical data for similar projects, the building is assumed to require no more than 1,600 Amp service for lighting receptacle loads and HVAC equipment. Lighting shall be all LED fixtures with classrooms lighting to have dimming drivers and controls systems.
The building will have an automatic fire alarm system with smoke detection and manual pull stations in corridors.
The building will have infrastructure for communications and data systems. The technology cabling and equipment shall be provided for by a pricing allowance at this point. Security systems shall be provided by allowance.
OPTION 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 26 of 55
PROGRAM AND DESIGN CRITERIAINTERIOR AND FINISHES
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
PRELIMINARY ROOM SCHEDULEROOM TYPE FLOOR FINISH WALL BASE INTERIOR WALL FINISH CEILING FINISH
Corridors Polished Concrete CMU, Paint CMU, Paint Open to Structure
Classrooms Polished Concrete CMU, Rubber base CMU, UL419 gwb partition ACT
Media Center Carpet Tile Rubber base CMU, UL419 gwb partition ACT
Cafeteria, Dining Polished Concrete Rubber Base ACT
Cafeteria, Kitchen Epoxy Epoxy Combination of gwb, paint& FRP Scrubbable ACT
Restrooms Polished Concrete Rubber base UL419 gwb partition, paint Open to Structure
Administrative Carpet Tile Rubber Base UL419 gwb partition, paint ACT
DOORS AND OPENINGSAll doors shall be 36”x84”x1 3/4”. Exterior doors shall be heavy duty insulated steel doors with 14 gauge hollow metal steel frames, doors and frames painted. Interior classroom and office doors shall be solid wood stained birch with 4”x30” tempered glass lites. Stairwells shall have 90 minute fire rated steel doors with tempered fire glass lites. Door hardware shall be heavy duty ADA with USD32 finish.
No overhead doors will be provided.
All entry glazing shall be thermally broken aluminum storefront system, Kawneer trifab 451T or equal. Clear anodized finish. Entry doors shall be heavy duty medium stile aluminum and glass entry doors with ADA hardware and proprietary keying. All windows shall be fixed pane, no operable windows.
All exterior glazing shall be 1” insulated glazing units with low-e coating, Solarban 70 or equal.
Each classroom shall have one operable window for fire egress within larger storefront window opening:
Basis of Design: Efco 3500T heavy duty slider with automatic latching hardware, low-e insulated glazing units.
INTERIOR FINISHESThe floor finish will be a combination of exposed polished concrete and carpet tile. Carpet tile should be an installed price of no more than $24/sy.
Interior partitions between classrooms and in administrative areas will be 3-5/8” metal studs with 5/8” abuse resistant gypsum board on either side with batt insulation. All gypsum board to be Level 4 finish.
Masonry walls shall be provided inside the building for unrated corridors and at fire rated stairwells and elevator shafts. Walls shall be 8” CMU running bond, full height to floor or roof deck, UL assembly #U905 for stair and elevator shaft walls. Continuous bond beam at top of wall and at 2nd floor level. Seismic reinforcing around openings and at corners, and at 48” on center.
Wall base for any gypsum board wall will be 4” rubber base.
Ceilings will be a combination of Open-To-Structure and 2x2 Acoustic Ceiling Tile. Basis of Design for ACT: Armstrong School Zone Fine Fissured. The metal deck of Open-To-Structure areas will be painted, and the structural steel will remain unfinished.
A preliminary room finish schedule has been provided below:
ROOM SIGNAGEProvide an allowance for room signage. Sign will be made of 1 piece of acrylic with a painted second surface attached with adhesive.
EXISTING MASONRY FACADEOPTION 1 ONLY
Provide W-shapes suitable to support existing structural brick masonry wall. Exposed steel to be galvanized and run the full height of the wall on 10 ft. centers. Provide adequate plates and anchors to allow for suitable attachment to the brick masonry.
VERTICAL CIRCULATIONOPTION 1 ONLY
Metal stairs shall be 48” clear width pre-engineered steel stairs with steel channel stringers and concrete pan filled treads and landings. 1.5” steel pipe handrails welded onto 1.5”, 42” high fall protection railings with 1/4” pickets at 4” on center. A pre-engineered ships ladder shall be provided for roof access of the two story portion of the building.
Option 1 will include (1) elevator. Basis of Design: Holeless hydraulic elevator system, 2,500 lb. capacity 100 fpm speed, vandal resistant finishes and fixtures, Otis Hydrofit or equal by major north american elevator manufacturer.
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 27 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
BUILDING CODE SUMMARY
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 28 of 55
PRELIMINARY BUILDING CODE SUMMARYOPTION 1
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
DN
UP
F
E
D
1
2
3
4
5
6
7
9
10
A B C
8
11
12
13
14
15
16
17
18
19
20
21
BUILDING CODE SUMMARY
1
3
5
Frontage area increases from Section 506.2 are computed thus:a. Perimeter which fronts a public way or open space having 20 feet minimum widthb. Total Building Perimeterc. Ratio (F/P)d. W = Minimum width of public waye. Percent of frontage increase I = 100 [ F/P - 0.25] x W/30
= (F)= (P)= 1.0 (F/P)= 30' (W)= 75 (%)
Unlimited area applicable under conditions of Sections 507.
The maximum area of open parking garages must comply with 406.3.5. The maximum area of airtraffic control towers must comply with 412.1.2.
f
INCIDENTAL USES (Table 508.2.5):
ALLOWABLE HEIGHT
Type of Construction
Building Height in Feet
Building Height in Stories
ALLOWABLE(TABLE 503)
INCREASE FORSPRINKLERS
SHOWN ONPLANS
CODEREFERENCE
Type II-B
55 ft Feet = H + 20' = 75' 35'
2 Stories Stories + 1 = 3 2 Stories
Type II-B Table 601
Table 503
Table 503
Name of Project: Community High SchoolAddress: 235 Old US Hwy 70, Swannanoa, NC 28778
Owner/Authorized Agent:Owned By:Code Enforcement Jurisdiction:
Proposed Use: High SchoolBuncombe County Board of Education
City/County PrivatePhone: -
StateCity: - County: Buncombe
BASIC BUILDING DATAI-A II-A III-A IV V-AConstruction Type (Table 601):
No PartialSprinklers (Chapter 9):Standpipes (Section 905):Fire District (Local Ordinance):Building Height (Table 503):Gross Building Area:
NFPA 13 NFPA 13R NFPA 13DNo YesNo Yes (Primary)
Class I II III Wet Dry
35'-0"
FLOOR EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL (SQ FT)1st Floor2nd Floor3rd Floor
Primary Occupancy (Chapter 3):Assembly: A-1 A-2 A-3 A-4 A-5
Business
HazardousInstitutional
Mercantile
Storage
Utility and Miscellaneous
H-1 DetonateI-1
ResidentialS-1 Moderate
FactoryH-2 Deflagrate
I-21
R-1S-2 Low
I-3 Condition
H-3 Combust H-4 HealthF-1 Moderate F-2 Low
H-5 HPMI-3 I-4
R-2 R-3 R-4High-Piled
Parking Garage Open Enclosed Repair Garage
Mixed Occupancy: No Yes Separation: N/A Exception: IBC 303.1 Ex.4
Non-Separated Use (508.3)The required type of construction for the building shall be determined byapplying the height and area limitations for each of the applicable occupanciesto the entire building. The most restrictive type of construction, sodetermined, shall apply to the entire building.Separated Use (508.4) - See below for area calculationsFor each story, the area of the occupancy shall be such that the sum of theratios of the actual floor area of each use divided by the allowable floor area foreach use shall not exceed 1.
STORY NO. DESCRIPTIONAND USE
(A)BLDG AREAPER STORY(ACTUAL)
(B)TABLE 503
AREA
(C)AREA FOR
OPEN SPACEINCREASE
(D)AREA FOR
SPRINKLERINCREASE
(E)ALLOWABLE
AREA ORUNLIMITED
(F)MAXIMUMBUILDING
AREA5
1 2 3 4
1st Floor Education (E) 32,200 SF 14,500 SF 10,875 SF 29,000 SF 54,375 SF
2
4
The sprinkler increase per Section 506.3 is as follows:a. Multi-story building I = 200 percentb. Single story building I = 300 percent
Maximum Building Area = total number of stories in the building x E (506.4).
FIRE PROTECTION REQUIREMENTS*
Structural frame, Includingcolumns, girders, trussesBearing walls
ExteriorNorthEastWestSouth
InteriorNonbearing walls andpartitions
ExteriorNorthEastWestSouth
Interior Wallsand Partitions
Floor construction Including supporting beams and joistsRoof construction Including supporting beams and joistsShafts Enclosures - ExitShafts Enclosures- OtherCorridor SeparationOccupancy SeparationParty/Fire Wall SeparationSmoke Barrier Separation
Incidental Use Separation
0
0
0
2 HR
-
LIFE SAFETY SYSTEM REQUIREMENTS:No Yes
BUILDING ELEMENT
FIRESEPARATIO
NDISTANCE
(FEET)
RATING
REQ'D(HR.)
PROVIDED(W/________*REDUCTION)
DETAIL #AND
SHEET #
DESIGN #FOR
RATEDASSEMBLY
DESIGN #FOR RATED
PENETRATION
DESIGN #FOR RATED
JOINTS
Emergency Lighting (S1006):No YesNo YesNo YesNo Yes
--
E-mail: -
Yes
No YesFlood Hazard Area (Appendix G):
ALLOWABLE AREA/OCCUPANCY CLASSIFICATION
Incidental Use Separation (508.2.5)This separation is not exempt as a Non-Separated Use (see exceptions).
2 HR
Tenant Separation
X > 30
Partial
State
I-B II-B III-B V-B
20,000 SF20,000 SF
N/A
N/AN/AN/A
TOTAL 40,000 SFN/A
2 3 4 5
Accessory Occupancy (Section 508):Assembly: A-1 A-2 A-3 A-4 A-5
Business
HazardousInstitutional
Mercantile
Storage
Utility and Miscellaneous
Educational
H-1 DetonateI-1
ResidentialS-1 Moderate
FactoryH-2 Deflagrate
I-21
R-1S-2 Low
I-3 Condition
H-3 Combust H-4 HealthF-1 Moderate F-2 Low
H-5 HPMI-3 I-4
R-2 R-3 R-4High-Piled
Parking Garage Open Enclosed Repair Garage
2 3 4 5
Educational
ss
Exit Signs (S1011):Fire Alarm (S907, NFPA 72-07):Smoke Detection Systems (S907):Panic Hardware (S1008.1.10):
N/AN/AN/AN/A
2 HR2 HR
--
-
-----
-----
-
-
-
-
-
----
-----
-----
-
-
-
U905
----
-----
-----
-
-
-
-
-
----
-----
-----
-
-
-
-
--
----
000
-
- No Incidental OR Special Uses -
163,125 SF
- - -
- U411 - -
X > 30
X > 30
PROJECT SUMMARY:PROJECT INFORMATION:
WALL LEGENDS:
Fire Walls 706Fire Barriers 707Shaft Enclosure 708Fire Partitions 709
Check if the following are present and indicated by a wall legend on all plans:Smoke Barriers 710Smoke Partitions 711No rated walls are present
No YesLife Safety System Generator: (S2702.2):
NUMBER AND ARRANGEMENT OF EXITS
FLOOR, ROOMOR SPACE
DESIGNATION
MINIMUM NUMBER OF EXITS
Level 1 - Classrooms 2 250 ft
TRAVEL DISTANCE
REQUIREDT1020.1
(SINGLE EXIT1021.2)
SHOWNON
PLANS
ALLOWABLETRAVEL
DISTANCE(TABLE 1016.1)
ACTUAL TRAVELDISTANCESHOWN ON
PLANS
ARRANGEMENT MEANS OF EGRESS(SECTION 1015.2)
REQUIREDDISTANCE
BETWEEN EXITDOORS
ACTUALDISTANCESHOWN ON
PLANS
2 160 ft 225'/3 = 75 ft 200 ft
2 1,3
12
3
Corridor dead ends (Section 1018.4)Buildings with single exits (Table 1021.2), Spaces with one means of egress (Table 1015.1).Common Path of Travel (Section 1014.3)
X > 30X > 30X > 30
X > 30
N/A
N/A
N/A
-
- -
(EXISTING CONDITIONS: ARRANGEMENT AND NUMBER OF EXITS UNCHANGED)
-
RENO/ALT (SQ FT)12,200 SF
N/AN/A
12,200 SF
32,200 SF20,000 SF
N/A
52,200 SF
Building/Space Description:
Approximately 50,000 square foot high school facility in two stories on anexisting school site including renovated gymnasium and historic facadeelements.
2nd Floor 20,000 SF 14,500 SF 29,000 SF 54,375 SF
52,200 SF 3 STORIES x 54,375 SFTOTAL
* Life Safety components shall remain operational during all phases of construction.
X > 30
Education (E) 10,875 SF
54,375 SF
00000
N/AN/AN/AN/A
Level 2 - ClassroomsGymnasium
2 22 2
250 ft 165 ft 225'/3 = 75 ft 175 ft250 ft 95 ft 140'/3 = 47 ft 125 ft
224'
158'
2nd Floor ClassroomsMax. occupancy per IBC Table 1004.1.1= approx. 800
Max. exit access distance = 110'158' Exit separation
- -
2 HR FIRE BARRIERW/ 90 MIN. DOORSIN CORRIDOR
1st Floor ClassroomsMax. occupancy per IBC Table 1004.1.1= approx. 700
Max. exit access distance = 145'199' Exit separation
199'
GymnasiumMax. occupancy per IBC Table 1004.1.1= approx. 350
Max. exit access distance = 95'125' Exit separation
CafeteriaMax. occupancy per IBC Table 1004.1.1= approx. 185
Max. exit access distance = 75'132' Exit separation
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 29 of 55
PRELIMINARY BUILDING CODE SUMMARYOPTION 1
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
0 10 20 50 0 10 20 50
DN
2nd Floor ClassroomsMax. occupancy per IBC Table 1004.1.1= approx. 800
Max. exit access distance = 110'158' Exit separation
1st Floor ClassroomsMax. occupancy per IBC Table 1004.1.1= approx. 700
Max. exit access distance = 145'199' Exit separation
GymnasiumMax. occupancy per IBC Table 1004.1.1= approx. 350
Max. exit access distance = 95'125' Exit separation
CafeteriaMax. occupancy per IBC Table 1004.1.1= approx. 185
Max. exit access distance = 75'132' Exit separation
199’
158’
224’2 HR FIRE BARRIERW/ 90 MIN. DOORS
IN CORRIDOR
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 30 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
BUILDING CODE SUMMARY
1
3
5
Frontage area increases from Section 506.2 are computed thus:a. Perimeter which fronts a public way or open space having 20 feet minimum widthb. Total Building Perimeterc. Ratio (F/P)d. W = Minimum width of public waye. Percent of frontage increase I = 100 [ F/P - 0.25] x W/30
= (F)= (P)= 1.0 (F/P)= 30' (W)= 75 (%)
Unlimited area applicable under conditions of Sections 507.
The maximum area of open parking garages must comply with 406.3.5. The maximum area of airtraffic control towers must comply with 412.1.2.
f
INCIDENTAL USES (Table 508.2.5):
ALLOWABLE HEIGHT
Type of Construction
Building Height in Feet
Building Height in Stories
ALLOWABLE(TABLE 503)
INCREASE FORSPRINKLERS
SHOWN ONPLANS
CODEREFERENCE
Type II-B
55 ft Feet = H + 20' = 75' 25'
2 Stories Stories + 1 = 3 1 Story
Type II-B Table 601
Table 503
Table 503
Name of Project: Community High SchoolAddress: 235 Old US Hwy 70, Swannanoa, NC 28778
Owner/Authorized Agent:Owned By:Code Enforcement Jurisdiction:
Proposed Use: High SchoolBuncombe County Board of Education
City/County PrivatePhone: -
StateCity: - County: Buncombe
BASIC BUILDING DATAI-A II-A III-A IV V-AConstruction Type (Table 601):
No PartialSprinklers (Chapter 9):Standpipes (Section 905):Fire District (Local Ordinance):Building Height (Table 503):Gross Building Area:
NFPA 13 NFPA 13R NFPA 13DNo YesNo Yes (Primary)
Class I II III Wet Dry
35'-0"
FLOOR EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL (SQ FT)1st Floor2nd Floor3rd Floor
Primary Occupancy (Chapter 3):Assembly: A-1 A-2 A-3 A-4 A-5
Business
HazardousInstitutional
Mercantile
Storage
Utility and Miscellaneous
H-1 DetonateI-1
ResidentialS-1 Moderate
FactoryH-2 Deflagrate
I-21
R-1S-2 Low
I-3 Condition
H-3 Combust H-4 HealthF-1 Moderate F-2 Low
H-5 HPMI-3 I-4
R-2 R-3 R-4High-Piled
Parking Garage Open Enclosed Repair Garage
Mixed Occupancy: No Yes Separation: N/A Exception: IBC 303.1 Ex.4
Non-Separated Use (508.3)The required type of construction for the building shall be determined byapplying the height and area limitations for each of the applicable occupanciesto the entire building. The most restrictive type of construction, sodetermined, shall apply to the entire building.Separated Use (508.4) - See below for area calculationsFor each story, the area of the occupancy shall be such that the sum of theratios of the actual floor area of each use divided by the allowable floor area foreach use shall not exceed 1.
STORY NO. DESCRIPTIONAND USE
(A)BLDG AREAPER STORY(ACTUAL)
(B)TABLE 503
AREA
(C)AREA FOR
OPEN SPACEINCREASE
(D)AREA FOR
SPRINKLERINCREASE
(E)ALLOWABLE
AREA ORUNLIMITED
(F)MAXIMUMBUILDING
AREA5
1 2 3 4
1st Floor Education (E) 58,200 SF 14,500 SF 10,875 SF 43,500 SF 68,875 SF
2
4
The sprinkler increase per Section 506.3 is as follows:a. Multi-story building I = 200 percentb. Single story building I = 300 percent
Maximum Building Area = total number of stories in the building x E (506.4).
FIRE PROTECTION REQUIREMENTS*
Structural frame, Includingcolumns, girders, trussesBearing walls
ExteriorNorthEastWestSouth
InteriorNonbearing walls andpartitions
ExteriorNorthEastWestSouth
Interior Wallsand Partitions
Floor construction Including supporting beams and joistsRoof construction Including supporting beams and joistsShafts Enclosures - ExitShafts Enclosures- OtherCorridor SeparationOccupancy SeparationParty/Fire Wall SeparationSmoke Barrier Separation
Incidental Use Separation
0
0
0
2 HR
-
LIFE SAFETY SYSTEM REQUIREMENTS: (EXISTING OR NEW)*No Yes
BUILDING ELEMENT
FIRESEPARATIO
NDISTANCE
(FEET)
RATING
REQ'D(HR.)
PROVIDED(W/________*REDUCTION)
DETAIL #AND
SHEET #
DESIGN #FOR
RATEDASSEMBLY
DESIGN #FOR RATED
PENETRATION
DESIGN #FOR RATED
JOINTS
Emergency Lighting (S1006):No YesNo YesNo YesNo Yes
--
E-mail: -
Yes
No YesFlood Hazard Area (Appendix G):
ALLOWABLE AREA/OCCUPANCY CLASSIFICATION
Incidental Use Separation (508.2.5)This separation is not exempt as a Non-Separated Use (see exceptions).
2 HR
Tenant Separation
X > 30
Partial
State
I-B II-B III-B V-B
58,200 SFN/AN/A
N/AN/AN/A
TOTAL 58,200 SF-
2 3 4 5
Accessory Occupancy (Section 508):Assembly: A-1 A-2 A-3 A-4 A-5
Business
HazardousInstitutional
Mercantile
Storage
Utility and Miscellaneous
Educational
H-1 DetonateI-1
ResidentialS-1 Moderate
FactoryH-2 Deflagrate
I-21
R-1S-2 Low
I-3 Condition
H-3 Combust H-4 HealthF-1 Moderate F-2 Low
H-5 HPMI-3 I-4
R-2 R-3 R-4High-Piled
Parking Garage Open Enclosed Repair Garage
2 3 4 5
Educational
ss
Exit Signs (S1011):Fire Alarm (S907, NFPA 72-07):Smoke Detection Systems (S907):Panic Hardware (S1008.1.10):
N/AN/AN/AN/A
2 HR2 HR
--
-
-----
-----
-
-
-
-
-
----
-----
-----
-
-
-
U905
----
-----
-----
-
-
-
-
-
----
-----
-----
-
-
-
-
--
----
000
-
- No Incidental OR Special Uses -
68,875 SF
- - -
- U411 - -
X > 30
X > 30
PROJECT SUMMARY:PROJECT INFORMATION:
WALL LEGENDS: (EXISTING OR NEW)
Fire Walls 706Fire Barriers 707Shaft Enclosure 708Fire Partitions 709
Check if the following are present and indicated by a wall legend on all plans:Smoke Barriers 710Smoke Partitions 711No rated walls are present
No YesLife Safety System Generator: (S2702.2):
NUMBER AND ARRANGEMENT OF EXITS
FLOOR, ROOMOR SPACE
DESIGNATION
MINIMUM NUMBER OF EXITS
Level 1 - Classrooms 4 250 ft
TRAVEL DISTANCE
REQUIREDT1020.1
(SINGLE EXIT1021.2)
SHOWNON
PLANS
ALLOWABLETRAVEL
DISTANCE(TABLE 1016.1)
ACTUAL TRAVELDISTANCESHOWN ON
PLANS
ARRANGEMENT MEANS OF EGRESS(SECTION 1015.2)
REQUIREDDISTANCE
BETWEEN EXITDOORS
ACTUALDISTANCESHOWN ON
PLANS
5 160 ft 225'/3 = 75 ft 200 ft
2 1,3
12
3
Corridor dead ends (Section 1018.4)Buildings with single exits (Table 1021.2), Spaces with one means of egress (Table 1015.1).Common Path of Travel (Section 1014.3)
1 HR 1 HR
X > 30X > 30X > 30
X > 30
N/A
N/A
N/A
-
- -
(EXISTING CONDITIONS: ARRANGEMENT AND NUMBER OF EXITS UNCHANGED)
-
RENO/ALT (SQ FT)N/AN/AN/A
-
58,200 SFN/AN/A
58,200 SF
Building/Space Description:
Approximately 50,000 square foot high school facility in one story on anexisting school site including new gymnasium.
58,200 SF 68,875 SFTOTAL
* Life Safety components shall remain operational during all phases of construction.
X > 30
00000
N/AN/AN/AN/A
U905
Gymnasium 2 2 250 ft 95 ft 140'/3 = 47 ft 125 ft
280'
South WingMax. occupancy per IBC Table 1004.1.1= approx. 900
Max. exit access distance = 110'235' Exit separation
358'
GymnasiumMax. occupancy per IBC Table 1004.1.1= approx. 350
Max. exit access distance = 65'125' Exit separation
North WingMax. occupancy per IBC Table 1004.1.1= approx. 785,
excluding gymMax. exit access distance = 175'
225' Exit separation
130'
PRELIMINARY BUILDING CODE SUMMARYOPTION 2
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 31 of 55
0 10 20 50
28 ’
58’
1’
North WingMax. occupancy per IBC Table 1004.1.1= approx. 785,
excluding gymMax. exit access distance = 175'
225' Exit separation
South WingMax. occupancy per IBC Table 1004.1.1= approx. 900
Max. exit access distance = 110'235' Exit separation
GymnasiumMax. occupancy per IBC Table 1004.1.1= approx. 350
Max. exit access distance = 65'125' Exit separation
PRELIMINARY BUILDING CODE SUMMARYOPTION 2
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 32 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
CONCEPTUAL DESIGN COST STUDY
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 33 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
1
LOCATION: Swannanoa, North Carolina 15 - December - 2015
Option 1: Building Areas
+ First Floor 24,816 SF
+ Second Floor 20,000 SF
Total Building Area 44,816 SF
*** Note: Existing Gymnasium (7,192 SF)
Option 1: Probable Construction Cost Summary TOTAL COST COST / SF % OF COST02 SITE WORK $513,802 $11.46 6.46%02 SELECTIVE DEMOLITION $9,385 $0.21 0.12%
03 CONCRETE $723,871 $16.15 9.10% 04 MASONRY $253,836 $5.66 3.19% 05 METALS $947,132 $21.13 11.91% 06 WOOD & PLASTICS $164,693 $3.67 2.07% 07 MOISTURE & THERMAL PROTECTION $681,790 $15.21 8.57% 08 DOORS AND WINDOWS $388,888 $8.68 4.89% 09 FINISHES $313,351 $6.99 3.94% 10 SPECIALTIES $23,900 $0.53 0.30% 11 EQUIPMENT $125,000 $2.79 1.57% 12 FURNISHINGS $55,286 $1.23 0.70%
14 CONVEYING SYSTEMS $85,000 $1.90 1.07% 15 PLUMBING $277,000 $6.18 3.48% 15 FIRE PROTECTION $167,500 $3.74 2.11% 15 HVAC (Includes New HVAC @ Gym) $1,009,000 $22.51 12.68%
16 ELECTRICAL SYSTEMS $827,000 $18.45 10.40% SUBTOTAL $6,566,434 $146.52 82.55% MARK-UPS - Sales Tax $22,768 $0.51 0.29% - Labor Burden $39,138 $0.87 0.49%
- Overhead & Profit $463,984 $10.35 5.83% - Bonding & Insurance $109,931 $2.45 1.38%
Subtotal $7,202,255 $160.71 90.55%
- Design / Estimating Contingency 1 LS $500,000 $11.16 6.29% - Escalation Contingency (12 months) 3.50% $252,079 $5.62 3.17%Total Estimated Probable Construction Cost: Option 1 $7,954,334 $177.49 100.00%
+ Owners Costs & Allowances 1 1 LS $1,510,000 Includes : FF&E, Technology , Security , Design Fees , Permits & Inspections, Test & Balance , Geotech Eng. , DOT Requirements , Owners Contingency
* * * Total Estimated Project Cost $9,464,334
+ + + + + + + + + + +
Clemson, SC 29631
E-Mail: [email protected]
Tel.: 864/653-6320 Project No: 41-15
C O S T P L U S
OWNER: Buncombe County Schools
PROJECT: Community High School
ARCHITECT: SPARC Desgn
Conceptual Design Cost Study
203 Prince Ranier Street
Estimator: R. Roark
2
02 SITE WORK TOTAL COST
Item Description Quantity u/m u/c Total u/c Total u/c TotalMobilization & Staking 1 LS 0 0 35,000 35,000 35,000Construction Fencing / Gates 1 LS 0 0 15,000 15,000 15,000Construction Entrance 60 TN 0 0 32 1,920 1,920Site Demolition: (Incl. Haul & Dump)
- buildings 16,400 SF 0 0 7.50 123,000 123,000 - mobile units 6,920 SF 0 0 1.50 10,380 10,380 - wood ramps / porches 1,400 SF 0 0 0.75 1,050 1,050 - front entry ramp / stairs 1 LS 0 0 5,430 5,430 5,430 - concrete walks 2,400 SF 0 0 1.25 3,000 3,000 - canopies 2,080 SF 0 0 1.50 3,120 3,120 - inlet structures 11 EA 0 0 415 4,565 4,565 - storm pipe 450 LF 0 0 9.85 4,433 4,433 - fencing 380 LF 0 0 1.25 475 475 - hazardous material abatement N.I.C. 0 0 0 0 - miscellaneous items 1 LS 0 0 7,773 7,773 7,773Erosion Control: 1 LS 0 0 6,250 6,250 6,250Grading: - Rough Grading:( cut / fill / excavate) 1 LS 0 0 35,600 35,600 35,600 - Excavate / Grind / Re-compaction 740 CY 0 0 11.40 8,436 8,436 - Excavate / Remove Foundation Conc. 20 CY 0 0 20.25 405 405 - Final Grading 1 LS 0 0 8,900 8,900 8,900Stormwater Systems: - raingarden 10,000 SF 0 0 6.85 68,500 68,500 - inlet structures 8 EA 0 0 1,850 14,800 14,800 - storm pipe 380 LF 0 0 30 11,400 11,400 - roof drain leaders 600 LF 0 0 12 7,200 7,200Site Utilities: - Water Distribution 1 LS 0 0 16,335 16,335 16,335 - Sanitary Sewer 1 LS 0 0 6,500 6,500 6,500 - Electrical Service By Others 0 0 0 0 - Gas Service By Others 0 0 0 0 - Telecom / Ductbank 1 LS 0 0 4,500 4,500 4,500 - Site Lighting 1 LS 0 0 15,000 15,000 15,000Drives / Parking / Walks: - curb & gutter N/A 0 0 14.25 0 0 - asphalt parking lot 900 SY 0 0 28.25 25,425 25,425 - concrete walks 3,500 SF 0 0 4.15 14,525 14,525 - striping N/A 0 0 0.75 0 0 - handicap signs / symbols N/A 0 0 210 0 0 - signs N/A 0 0 180 0 0Improvements: - Screening Fence 930 LF 0 0 16 14,880 14,880 - school monument sign 1 EA 0 0 7,500 7,500 7,500Landscaping (trees / shrubs) 1 LS 0 0 25,000 25,000 25,000Seeding / Sod 1 LS 0 0 7,500 7,500 7,500Irrigation Systems N/A 0 0 0 0SUBTOTAL - SITE WORK 0 0 513,802 $513,802
MATERIAL SUBCONTRACTLABOR
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 34 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
3
02 SELECTIVE DEMOLITION
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Remove: (Incl. Haul & Dump) - windows @ "façade Wall" 1,110 SF 0 0 3.50 3,885 3,885 - demo. Stairs @ Gymnasium 1 LS 0 0 3,000 3,000 3,000 - miscellaneous items 1 LS 0 0 2,500 2,500 2,500Hazardous Material Abatement N.I.C. 0 0 0 0SUBTOTAL - SELECTIVE DEMOLITION 0 0 9,385 $9,385
03 CONCRETE TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total
Wall Footings: - excavation/backfill 576 CY 0 28 16,128 0 16,128 - trim sides 6,405 SF 0 0.38 2,434 0 2,434 - concrete 288 CY 116 33,408 32 9,216 0 42,624 - rebar 9.22 TN 975 8,986 380 3,502 0 12,488
Column Footings: 0 - excavation/backfill 176 CY 0 32 5,632 0 5,632 - trim sides 1,446 SF 0 0.38 549 0 549 - concrete 88 CY 116 10,208 40 3,520 0 13,728 - rebar 3.78 TN 975 3,689 380 1,438 0 5,127 - set base plates / anchor bolts 36 EA 50 1,800 30 1,080 0 2,880Elevator Pit(s): 0 - excavation/backfill 18 CY 0 13.50 240 0 240 - cast-in-place walls 162 SF 0 0 29.25 4,739 4,739 - structural slab 96 SF 4.48 430 3.05 293 0 723 - sump pump pit / grating 1 EA 0 0 1060 1,060 1,060Foundation Wall(s) : (8" thick, C.I.P.) 9,790 SF 0 0 23.84 233,394 233,394Concrete Stairs 320 LF 0 0 26.50 8,480 8,480Compacted Structural Fill 8,424 CY 0 0 19.50 164,268 164,268Ramp(s) / Porches 3,450 SF 0 0 7.88 27,169 27,169
Slab on Grade : - soil poisoning 24,816 SF 0 0 0.16 3,971 3,971
- concrete 309 CY 120 37,125 15 4,641 0 41,766 - rebar 4.95 TN 975 4,826 380 1,881 0 6,707
- crusher run base, 4" tk 425 TN 32 13,588 10 4,246 0 17,834 - vapor barrier 26,057 SF 0.05 1,303 0.03 782 0 2,085
- welded wire mesh 26,057 SF 0.43 11,204 0.15 3,909 0 15,113 - perimeter insulation 3,176 LF 1.72 5,463 0.48 1,524 0 6,987
- place & finish 24,816 SF 0 0 0.52 12,904 12,904 - protect & cure 24,816 SF 0.03 744 0.03 744 0 1,488
- expansion joint 4,128 LF 0.85 3,509 0.70 2,890 0 6,399 - control joint 780 LF 0.15 117 0.54 421 0 538
Elevated Floor(s): - concrete 206 CY 120 24,720 55 11,330 0 36,050 - place & finish 20,000 SF 0 0 0.92 18,400 18,400 - control joint 700 LF 0.15 105 0.54 378 0 483Elevator Shaft Cap @ 8" tk 120 SF 0 0 11.78 1,414 1,414Concrete Fill @ Stairs / Landings 6.50 CY 134 871 135 878 0 1,749Rear Porch / Stairs @ Classroom Bldg. 1 LS 0 0 6720 6,720 6,720
SUBCONTRACT
LABOR SUBCONTRACT
MATERIAL LABOR
MATERIAL
4
03 CONCRETE - Continued TOTAL COST
Item Description Quantity u/m u/c Total u/c Total u/c TotalNew Ramp @ Gym Entry 1 LS 0 0 1600 1,600 1,600
SUBTOTAL - CONCRETE 162,096 77,656 $484,119 $723,871
04 MASONRY TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total
Masonry Walls: - 8" c.m.u. 20,447 EA 1.70 34,760 0 4.10 83,833 118,593 - mortar 613 BG 11.45 7,024 0 0 7,024 - sand 102 TN 32 3,272 0 0 3,272 - grout fill 121 CY 135 16,358 0 108 13,086 29,444 - rebar 6.36 TN 995 6,329 0 415 2,640 8,969 - clean masonry 35,560 SF 0 0 0.34 12,090 12,090Pt./Patch/Repair/Clean @ "Gymnasium" 1 LS 0 0 44,954 44,954 44,954Cast Stone Repair @ "Gymnasium" 1 LS 0 0 7,200 7,200 7,200Repair Entry Porch / Ballastrade 1 LS 0 0 5,000 5,000 5,000Pt./Patch/Repair/Clean @ "Façade Wall" 1 LS 0 0 17,290 17,290 17,290
SUBTOTAL - MASONRY 67,743 0 $186,093 $253,836
05 METALS TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total Structural Steel:
- columns 17.90 TN 0 0 3,700 66,230 66,230 - floor structure 80.00 TN 0 0 3,750 300,000 300,000
- roof structure (beams / joists) 69.47 TN 0 0 3,725 258,776 258,776 - 8" steel z-girts 5,256 LF 0 0 6.40 33,638 33,638 - misc. 1 LS 0 0 18,750 18,750 18,750Work @ "façade wall" - shoring / bracing 5,320 SF 0 0 5.35 28,462 28,462 - steel vertical supports 1 LS 0 0 31,500 31,500 31,500 - steel horizontal supports 1 LS 0 0 17,640 17,640 17,640
Metal Decking: - floor 21,000 SF 0 0 2.40 50,400 50,400 - roof 18,216 SF 0 0 2.26 41,168 41,168 - roof (Acoustical) 7,934 SF 0 0 2.64 20,946 20,946Stair Structures: - treads @ 4'-0" wide w/railings 63 Trd 0 0 435 27,405 27,405 - landings 240 SF 0 0 58 13,920 13,920 - wall rails 96 LF 0 0 30 2,880 2,880Hoist Beam 1 EA 0 0 2,980 2,980 2,980Railings @ Porch / Ramp(s) 516 LF 0 0 62 31,992 31,992Pit Ladder 1 EA 0 0 445 445 445
SUBTOTAL - METALS 0 0 $947,132 $947,132
SUBCONTRACT
LABOR SUBCONTRACTMATERIAL
MATERIAL LABOR
MATERIAL LABOR SUBCONTRACT
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 35 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
5
06 WOOD & PLASTICS TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total Treated Blocking / Plywood 6,580 BF 0.99 6,485 0.95 6,218 0 12,703
Casework: - base cabinets 430 LF 0 0 225 96,750 96,750 - wall cabinets 300 LF 0 0 150 45,000 45,000 - vanity 24 LF 0 0 135 3,240 3,240Rough Hardware 1 LS 3,500 3,500 0 0 3,500Upgrade Rear Entry Stairs @ Gymnasium 1 LS 0 0 3,500 3,500 3,500
SUBTOTAL - WOOD & PLASTICS 9,985 6,218 $148,490 $164,693
07 MOISTURE & THERMAL PROTECTION
TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total
TPO (single-ply membrane) w/ insulation 254 SQ 0 860 218,440 218,440Remove / Replace Gymnasium Roofing 74 SQ 0 965 71,410 71,410Metal Wall Coping 948 LF 0 8.35 7,916 7,916Roof Hatch w/ ladder 2 EA 0 925 1,850 1,850Expansion Joint 56 LF 0 22 1,232 1,232Gutters 318 LF 0 10.80 3,434 3,434Downspouts 272 LF 0 8.65 2,353 2,353Metal Wall Panels (insulated) 20,306 SF 0 16.85 342,156 342,156Waterproofing @ Foundation Walls 8,982 SF 0 2.85 25,599 25,599Caulking & Sealants 1 LS 0 0 7,400 7,400 7,400Sprayed-on Firefroofing N/A 0 0 0 0
SUBTOTAL - MOISTURE & THERMAL PROTECTION 0 0 $681,790 $681,790
08 DOORS & WINDOWS
TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total Aluminum Doors:
- entry doors (full glass) 7 PR 3,100 21,700 300 2100 0 23,800Hollow Metal Doors: w/ frames
- insulated steel 5 EA 490 2,450 125 625 0 3,075Interior Wood Doors w/ Frames:
- flush 17 EA 220 3,740 90 1530 0 5,270 - w/ view glass 30 EA 270 8,100 90 2700 0 10,800 - rated (90min.) 2 EA 310 620 90 180 0 800Door Hardware 1 LS 32,975 32,975 4,690 4,690 7,500 7,500 45,165Door Replacement @ Gym (complete) 1 LS 0 0 35,650 35,650 35,650Interior Frames / Glass 210 SF 0 0 30 6,300 6,300Exterior Window System 4,538 SF 0 0 46 208,748 208,748Replace Glass @ Gymnasium 1,120 SF 0 0 44 49,280 49,280
SUBTOTAL - DOORS & WINDOWS 69,585 11,825 $307,478 $388,888
LABORMATERIAL
LABOR
SUBCONTRACT
MATERIAL SUBCONTRACT
MATERIAL LABOR SUBCONTRACT
6
09 FINISHES
TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total Floors:
- carpet tile 578 SY 0 0 24 13,867 13,867 - polished concrete 35,318 SF 0 0 0.85 30,020 30,020 - epoxy 4,298 SF 0 0 5.45 23,424 23,424
Base: - rubber 6,220 LF 0 0 1.56 9,703 9,703 Interior Walls:
- 3 5/8" metal studs 15,280 SF 0 0 2.45 37,436 37,436 - 5/8" gwb 28,440 SF 0 0 1.64 46,642 46,642 - sound batt 12,224 SF 0 0 0.60 7,334 7,334
Ceilings: - ACT (2' x 2'), nrc .95 32,584 SF 0 0 2.40 78,202 78,202 - ACT (2' x 2'), vinyl coated 4,298 SF 0 0 2.65 11,390 11,390
Painting / Wall Covering: - painting (walls) 48,104 SF 0 0 0.60 28,862 28,862
- exposed structure 7,934 SF 0 0 0.75 5,951 5,951 - paint existing gymnasium 1 LS 0 0 9,000 9,000 9,000
- doors / frames 59 EA 0 0 55 3,245 3,245 - stair structure(s) 1 LS 0 0 5,775 5,775 5,775
- miscellaneous 1 LS 0 0 2,500 2,500 2,500 SUBTOTAL - FINISHES 0 0 $313,351 $313,351 10 SPECIALTIES
TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total Toilet Partitions : - standard 6 EA 835 5,010 65 390 0 5,400 - handicap 4 EA 980 3,920 80 320 0 4,240
Urinal Screen 2 EA 325 650 40 80 0 730 Toilet Accessories :
- grab bars, 18" 4 EA 40 160 12 48 0 208 - grab bars, 36" 4 EA 60 240 12 48 0 288 - grab bars, 42" 4 EA 72 288 12 48 0 336 - toilet tissue disp. 14 EA 44 616 10 140 0 756 - soap dispenser 10 EA 38 380 12 120 0 500 - MR (24 x 60") 4 EA 150 600 15 60 0 660 - MR (18" x 36") 10 EA 85 850 10 100 0 950 - paper towel dispenser 6 EA 135 810 10 60 0 870 - sanitary napkin disposal 6 EA 35 210 12 72 0 282Fire Extinguishers / Cabinets 8 EA 235 1,880 75 600 0 2,480Fire Extinguishers w/ bracket 2 EA 120 240 30 60 0 300Interior Signage 1 LS 0 0 3,400 3,400 3,400Exterior Signage 1 LS 0 0 2,500 2,500 2,500
SUBTOTAL - SPECIALTIES 15,854 2,146 $5,900 $23,900
MATERIAL LABOR SUBCONTRACT
LABORMATERIAL SUBCONTRACT
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 36 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
7
11 EQUIPMENT
TOTAL COST Item Description Quantity u/m u/c Total u/c Total u/c Total
Food Service Equipment 1 LS 0 0 125,000 125,000 125,000Residential Appliances By Owner 0 0 0 0Educational Audio / Video By Owner 0 0 0 0Visual Display Equipment By Owner 0 0 0 0Science Lab Equipment By Owner 0 0 0 0Student Lockers N/A 0 0 0 0
SUBTOTAL - EQUIPMENT 0 0 $125,000 $125,000
12 FURNISHINGS
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Cafeteria (Tables & Chairs) By Owner 0 0 0 0Media Center FFE By Owner 0 0 0 0Acoustical Panels (Allowance) 1,960 SF 0 0 12 23,520 23,520Window Treatments 4,538 SF 0 0 7 31,766 31,766
SUBTOTAL - FURNISHINGS 0 0 $55,286 $55,286
14 CONVEYING SYSTEMS
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Elevator (2-stop) 1 LS 0 0 85,000 85,000 85,000SUBTOTAL - CONVEYING SYSTEMS 0 0 $85,000 $85,000
15 PLUMBING 1 LS 0 0 277,000 277,000 $277,000 15 FIRE PROTECTION 1 LS 0 0 167,500 167,500 $167,500 15 H.V.A.C. (Includes New HVAC @ Gym) 1 LS 0 0 1,009,000 1,009,000 $1,009,000 16 ELECTRICAL 1 LS 0 0 827,000 827,000 $827,000
SUBTOTAL $325,263 $97,845 $6,143,326 $6,566,434 MARK-UPS: - Sales Tax 7.00% $22,768 $22,768 - Labor Burden 40.00% $39,138 $39,138
SUBTOTAL $6,628,340 - Overhead & Profit 7.00% $463,984 $463,984SUBTOTAL $7,092,324 - Payment & Performance Bond 1.25% $88,654 $88,654 - Builders Risk Insurance 0.30% $21,277 $21,277
SUBTOTAL - Option 1 $7,202,255 - Design / Estimating Contingency 1 LS $500,000 - Escalation Contingency (12 months) 3.50% $252,079TOTAL ESTIMATED PROBABLE CONSTRUCTION COST: Option 1 $7,954,334 $177.49 per sq. ft.
LABOR
SUBCONTRACT
SUBCONTRACT
MATERIAL LABOR
MATERIAL SUBCONTRACT
MATERIAL
LABOR
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 37 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
9
02 SITE WORK TOTAL COST
Item Description Quantity u/m u/c Total u/c Total u/c TotalMobilization & Staking 1 LS 0 0 35,000 35,000 35,000Construction Fencing / Gates 1 LS 0 0 28,000 28,000 28,000Construction Entrance 60 TN 0 0 32 1,920 1,920Site Demolition: (Incl. Haul & Dump)
- buildings 23,592 SF 0 0 7.50 176,940 176,940 - mobile units 6,920 SF 0 0 1.50 10,380 10,380 - wood ramps / porches 1,400 SF 0 0 0.75 1,050 1,050 - front entry ramp / stairs 1 LS 0 0 5,430 5,430 5,430 - concrete walks 6,270 SF 0 0 1.25 7,838 7,838 - canopies 2,080 SF 0 0 1.50 3,120 3,120 - inlet structures 12 EA 0 0 415 4,980 4,980 - storm pipe 1,510 LF 0 0 9.85 14,874 14,874 - fencing 380 LF 0 0 1.25 475 475 - hazardous material abatement N.I.C. 0 0 0 0 - misc. utilities 1 LS 0 0 3,500 3,500 3,500 - miscellaneous items 1 LS 0 0 11,254 11,254 11,254Erosion Control: 1 LS 0 0 7,500 7,500 7,500Grading: - Rough Grading:( cut / fill / excavate) 1 LS 0 0 27,090 27,090 27,090 - Remove & Replace Unsuitable Soils 11,110 CY 0 0 28.35 314,969 314,969 - Final Grading 1 LS 0 0 7,900 7,900 7,900Stormwater Systems: - raingarden 10,000 SF 0 0 6.85 68,500 68,500 - inlet structures 12 EA 0 0 1,850 22,200 22,200 - storm pipe 800 LF 0 0 30 24,000 24,000 - roof drain leaders 600 LF 0 0 12 7,200 7,200Site Utilities: - Water Distribution 1 LS 0 0 21,236 21,236 21,236 - Sanitary Sewer 1 LS 0 0 8,125 8,125 8,125 - Electrical Service By Others 0 0 0 0 - Gas Service By Others 0 0 0 0 - Telecom / Ductbank 1 LS 0 0 5,000 5,000 5,000 - Site Lighting 1 LS 0 0 20,000 20,000 20,000Drives / Parking / Walks: - 18" curb & gutter 1,200 LF 0 0 14.25 17,100 17,100 - asphalt pavement 2,567 SY 0 0 26.40 67,769 67,769 - signage / pavement markings 1 LS 0 0 2,475 2,475 2,475 - concrete walks 9,000 SF 0 0 4.15 37,350 37,350Improvements: - Screening Fence 950 LF 0 0 16 15,200 15,200 - school monument sign 1 EA 0 0 7,500 7,500 7,500Landscaping (trees / shrubs) 1 LS 0 0 40,000 40,000 40,000Seeding / Sod 1 LS 0 0 15,000 15,000 15,000Irrigation Systems N/A 0 0 0 0SUBTOTAL - SITE WORK 0 0 1,040,875 $1,040,875
MATERIAL LABOR SUBCONTRACT
8
Option 2: Building Areas
+ First Floor 58,074 SFTotal Building Area 58,074 SF
Option 2: Probable Construction Cost Summary TOTAL COST COST / SF % OF COST02 SITE WORK $1,040,875 $17.92 11.76%03 CONCRETE $305,273 $5.26 3.45%04 MASONRY $227,971 $3.93 2.58%05 METALS $911,736 $15.70 10.31%06 WOOD & PLASTICS $189,180 $3.26 2.14%07 MOISTURE & THERMAL PROTECTION $1,034,126 $17.81 11.69%08 DOORS AND WINDOWS $273,983 $4.72 3.10%09 FINISHES $300,809 $5.18 3.40%10 SPECIALTIES $24,325 $0.42 0.27%11 EQUIPMENT $125,000 $2.15 1.41%12 FURNISHINGS $72,156 $1.24 0.82%15 PLUMBING $312,000 $5.37 3.53%15 FIRE PROTECTION $215,000 $3.70 2.43%15 HVAC $1,200,000 $20.66 13.56%16 ELECTRICAL SYSTEMS $1,125,500 $19.38 12.72%SUBTOTAL $7,357,934 $126.70 83.16%MARK-UPS - Sales Tax $29,094 $0.50 0.33% - Labor Burden $35,466 $0.61 0.40% - Overhead & Profit $519,575 $8.95 5.87% - Bonding & Insurance $123,102 $2.12 1.39%Subtotal $8,065,170 $138.88 91.16% - Design / Estimating Contingency 1 LS $500,000 $8.61 5.65% - Escalation Contingency (12 months) 3.50% $282,281 $4.86 3.19%Total Estimated Probable Construction Cost $8,847,451 $152.35 100.00%
+ Owners Costs & Allowances 1 1 LS $1,510,000 Includes : FF&E, Technology , Security , Design Fees , Permits & Inspections, Test & Balance , Geotech Eng. , DOT Requirements , Owners Contingency
* * * Total Estimated Project Cost $10,357,451
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 38 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
11
06 WOOD & PLASTICS
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Treated Blocking / Plywood 7,542 BF 0.99 7,433 0.95 7,127 0 14,560Casework: - base cabinets 480 LF 0 0 225 108,000 108,000 - wall cabinets 400 LF 0 0 150 60,000 60,000 - vanity 12 LF 0 0 135 1,620 1,620Rough Hardware 1 LS 5,000 5,000 0 0 5,000SUBTOTAL - WOOD & PLASTICS 12,433 7,127 $169,620 $189,180
07 MOISTURE & THERMAL PROTECTION
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
TPO (single-ply membrane) w/ insulation 610 SQ 0 860 524,600 524,600Metal Wall Coping 2,228 LF 0 8.35 18,604 18,604Roof Hatch w/ ladder 1 EA 0 925 925 925Expansion Joint 660 LF 0 22 14,520 14,520Gutters 300 LF 0 10.80 3,240 3,240Downspouts 170 LF 0 8.65 1,471 1,471Metal Wall Panels (insulated) 27,452 SF 0 16.85 462,566 462,566Caulking & Sealants 1 LS 0 0 8,200 8,200 8,200Sprayed-on Firefroofing N/A 0 0 0 0SUBTOTAL - MOISTURE & THERMAL PROTECTION 0 0 $1,034,126 $1,034,126
08 DOORS & WINDOWS
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Aluminum Doors: - entry doors (full glass) 13 PR 3,100 40,300 300 3900 0 44,200Insulated Steel Door w/ Frame 3 EA 490 1,470 125 375 0 1,845Interior Wood Doors w/ Frames:
- flush 5 EA 220 1,100 90 450 0 1,550 - w/ view glass 31 EA 270 8,370 90 2790 0 11,160 - glass 9 EA 580 5,220 90 810 0 6,030Door Hardware 1 LS 45,050 45,050 5,540 5,540 7,500 7,500 58,090Interior Frames / Glass 150 SF 0 0 30 4,500 4,500Exterior Window System 1,948 SF 0 0 46 89,608 89,608Exterior Storefront 1,140 SF 0 0 50 57,000 57,000SUBTOTAL - DOORS & WINDOWS 101,510 13,865 $158,608 $273,983
MATERIAL LABOR SUBCONTRACT
MATERIAL LABOR SUBCONTRACT
MATERIAL LABOR SUBCONTRACT
10
03 CONCRETE TOTAL COST
Item Description Quantity u/m u/c Total u/c Total u/c TotalColumn Footings: - excavation/backfill 292 CY 0 32 9,344 0 9,344 - trim sides 2,424 SF 0 0.38 921 0 921 - concrete 146 CY 116 16,936 40 5,840 0 22,776 - rebar 6.27 TN 975 6,113 380 2,383 0 8,496 - set base plates / anchor bolts 72 EA 50 3,600 30 2,160 0 5,760Slab on Grade : - soil poisoning 58,074 SF 0 0 0.16 9,292 9,292 - excavate thickened slab 121 CY 0 32 3,872 0 3,872 - concrete 845 CY 120 101,399 15 12,675 0 114,074 - rebar 2.72 TN 975 2,654 380 1,035 0 3,689 - crusher run base, 4" tk 994 TN 32 31,799 10 9,937 0 41,736 - vapor barrier 63,881 SF 0.05 3,194 0.03 1,916 0 5,110 - welded wire mesh 63,881 SF 0.43 27,469 0.15 9,582 0 37,051 - perimeter insulation 1,676 LF 1.72 2,883 0.48 804 0 3,687 - place & finish 58,074 SF 0 0 0.52 30,198 30,198 - protect & cure 58,074 SF 0.03 1,742 0.03 1,742 0 3,484 - expansion joint 2,360 LF 0.85 2,006 0.70 1,652 0 3,658 - control joint 3,080 LF 0.15 462 0.54 1,663 0 2,125SUBTOTAL - CONCRETE 200,257 65,526 $39,490 $305,273
04 MASONRY TOTAL COST
Item Description Quantity u/m u/c Total u/c Total u/c TotalMasonry Walls: - 8" c.m.u. 25,829 EA 1.70 43,909 0 4.10 105,899 149,808 - mortar 775 BG 11.45 8,872 0 0 8,872 - sand 129 TN 32 4,133 0 0 4,133 - grout fill 153 CY 135 20,663 0 108 16,531 37,194 - rebar 8.04 TN 995 7,996 0 415 3,335 11,331 - clean masonry 48,920 SF 0 0 0.34 16,633 16,633SUBTOTAL - MASONRY 85,573 0 $142,398 $227,971
05 METALS
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Structural Steel: - columns 35.70 TN 0 0 3,700 132,090 132,090 - roof structure (beams / joists) 142.72 TN 0 0 3,725 531,632 531,632 - 8" steel z-girts 11,744 LF 0 0 6.40 75,162 75,162 - misc. 1 LS 0 0 19,912 19,912 19,912Metal Decking: - roof 42,948 SF 0 0 2.26 97,062 97,062 - roof (Acoustical) 21,166 SF 0 0 2.64 55,878 55,878SUBTOTAL - METALS 0 0 $911,736 $911,736
MATERIAL LABOR SUBCONTRACT
MATERIAL LABOR SUBCONTRACT
MATERIAL LABOR SUBCONTRACT
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 39 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
13
11 EQUIPMENT
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Food Service Equipment 1 LS 0 0 125,000 125,000 125,000Gymnasium Equipment By Owner 0 0 0 0Residential Appliances By Owner 0 0 0 0Educational Audio / Video (Allowance) By Owner 0 0 0 0Visual Display Equipment By Owner 0 0 0 0Science Lab Equipment By Owner 0 0 0 0Student Lockers N/A 0 0 0 0SUBTOTAL - EQUIPMENT 0 0 $125,000 $125,000
12 FURNISHINGS
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Cafeteria (Tables & Chairs) By Owner 0 0 0 0Media Center FFE (Allowance) 1 LS 0 0 35,000 35,000 35,000Acoustical Panels (Allowance) 1,960 SF 0 0 12 23,520 23,520Window Treatments 1,948 SF 0 0 7 13,636 13,636SUBTOTAL - FURNISHINGS 0 0 $72,156 $72,156
15 PLUMBING 1 LS 0 0 312,000 312,000 $312,000
15 FIRE PROTECTION 1 LS 0 0 215,000 215,000 $215,000
15 H.V.A.C. 1 LS 0 0 1,200,000 1,200,000 $1,200,000
16 ELECTRICAL 1 LS 0 0 1,125,500 1,125,500 $1,125,500
SUBTOTAL $415,627 $88,664 $6,853,643 $7,357,934MARK-UPS: - Sales Tax 7.00% $29,094 $29,094 - Labor Burden 40.00% $35,466 $35,466SUBTOTAL $7,422,493 - Overhead & Profit 7.00% $519,575 $519,575SUBTOTAL $7,942,068 - Payment & Performance Bond 1.25% $99,276 $99,276 - Builders Risk Insurance 0.30% $23,826 $23,826SUBTOTAL - Option 1 $8,065,170 - Design / Estimating Contingency 1 LS $500,000 - Escalation Contingency (12 months) 3.50% $282,281TOTAL ESTIMATED PROBABLE CONSTRUCTION COST: Option 2 $8,847,451 $152.35 per sq. ft.
MATERIAL LABOR SUBCONTRACT
MATERIAL LABOR SUBCONTRACT
12
09 FINISHES
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Floors: - carpet tile 694 SY 0 0 24 16,656 16,656 - polished concrete 47,584 SF 0 0 0.85 40,446 40,446 - epoxy 4,246 SF 0 0 5.45 23,141 23,141Rubber Base 4,528 LF 0 0 1.56 7,064 7,064Interior Walls: - 3 5/8" metal studs 9,528 SF 0 0 2.45 23,344 23,344 - 5/8" gwb 19,056 SF 0 0 1.64 31,252 31,252 - sound batt 7,622 SF 0 0 0.60 4,573 4,573Ceilings: - ACT (2' x 2'), nrc .95 35,758 SF 0 0 2.40 85,819 85,819 - ACT (2' x 2'), vinyl coated 4,246 SF 0 0 2.65 11,252 11,252Painting / Wall Covering: - painting (walls) 63,440 SF 0 0 0.60 38,064 38,064 - exposed structure 18,070 SF 0 0 0.75 13,553 13,553 - doors / frames 39 EA 0 0 55 2,145 2,145 - miscellaneous 1 LS 0 0 3,500 3,500 3,500SUBTOTAL - FINISHES 0 0 $300,809 $300,809
10 SPECIALTIES
TOTAL COSTItem Description Quantity u/m u/c Total u/c Total u/c Total
Toilet Partitions : - standard 6 EA 835 5,010 65 390 0 5,400 - handicap 4 EA 980 3,920 80 320 0 4,240Urinal Screen 2 EA 325 650 40 80 0 730Toilet Accessories : - grab bars, 18" 4 EA 40 160 12 48 0 208 - grab bars, 36" 4 EA 60 240 12 48 0 288 - grab bars, 42" 4 EA 72 288 12 48 0 336 - toilet tissue disp. 14 EA 44 616 10 140 0 756 - soap dispenser 10 EA 38 380 12 120 0 500 - MR (24 x 60") 4 EA 150 600 15 60 0 660 - MR (18" x 36") 10 EA 85 850 10 100 0 950 - paper towel dispenser 6 EA 135 810 10 60 0 870 - sanitary napkin disposal 6 EA 35 210 12 72 0 282Fire Extinguishers / Cabinets 8 EA 235 1,880 75 600 0 2,480Fire Extinguishers w/ bracket 2 EA 120 240 30 60 0 300Interior Signage 1 LS 0 0 3,825 3,825 3,825Exterior Signage 1 LS 0 0 2,500 2,500 2,500SUBTOTAL - SPECIALTIES 15,854 2,146 $6,325 $24,325
LABOR SUBCONTRACTMATERIAL
MATERIAL LABOR SUBCONTRACT
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 40 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
APPENDIX AREPORT OF
PRELIMINARY GEOTECHNICAL
EVALUATION
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 41 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-2-
PROJECT INFORMATION
Our understanding of the project is based on telephone and email correspondences between you and David G. Marsh, PE with ECS. It is our understanding that an addition is proposed for the existing Community High School. Two proposed building layouts have been developed and provided to us (Option 1 and Option 2, from Sparc Design/Aiton Anderson Architecture, dated September 29, 2015) that show different building layouts for the site. Option 1 is described as two-story construction that will partially reuse existing buildings on the site and will generally lie in the eastern portion of the site. Option 2 is described as one-story new construction and will generally lie in the northwestern portion of the site.
Figure 2 – Site Option 1 (after Sparc Design/Aiton Anderson Architecture, 2015)
Presently, the area of Option 1 (see Figure 2, above) is developed with the existing permanent site buildings, modular classroom buildings, gravel parking areas, and some grassed areas. The area is generally flat with ground surface elevations in the area ranging from approximately 2185 to 2190.
Presently, the area of Option 2 (see Figure 3, below) is largely undeveloped. The area is primarily flat, open grass fields. The area is generally flat with ground surface elevations in the area ranging from approximately 2180 to 2185.
1900 Hendersonville Road, Suite 10, Asheville, NC 28803 • T: 828-665-2307 • F: 828-665-8128 • www.ecslimited.comECS Mid-Atlantic, LLC • ECS Carolinas, LLP • ECS Florida, LLC • ECS Illinois, LLC • ECS Southeast, LLC • ECS Texas, LLP
December 29, 2015
Mr. Tim Fierle, AIA Director of Facilities Buncombe County Schools 175 Bingham Road Asheville, NC 28806
Reference: Report of Preliminary Geotechnical Evaluation Community High School Addition
Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
Mr. Fierle:
As authorized by your acceptance of our Proposal No. 31-4258-PR, ECS Carolinas, LLP (ECS) has completed a preliminary geotechnical evaluation at the above-referenced property. This report summarizes the results of the exploration and presents our preliminary recommendations regarding development at the project site.
The subject site is located at the intersection of Bee Tree Road and Old US Highway 70 in Swannanoa, North Carolina. The site is currently developed with permanent and modular school buildings generally within the central and eastern portions of the site. The northwestern portion of the site is undeveloped fields.
Figure 1 – Aerial Photograph of Subject Site (after Google Earth, 2015)
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 42 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-4-
SUBSURFACE SOIL BORING EXPLORATION
Our preliminary subsurface exploration within the areas of Options 1 and 2 consisted of performing a total of six (6) geotechnical soil test borings designated as Borings B-1 through B-7. Boring B-1, B-3, and B-4 were generally located in the area of the Option 2 layout, while Borings B-5, B-6, and B-7 were generally located in the area of the Option 1 layout. Please note that Boring B-2 had to be eliminated from the drilling scope at the time of drilling. We understood from Mr. Fierle that rutting of the field within the area of Option 2 was unacceptable; at the time of our exploration, the field was very wet and soft. To avoid rutting of the field, Boring B-2 was removed and borings B-1, B-3, and B-4 were offset from their original locations.
The borings were performed at the approximate locations shown on the Boring Location Diagram attached to this report. The boring locations were widely-spaced and were selected by ECS to provide a preliminary and general characterization of the soils across the site. The borings were located in the field based on referencing prominent landmarks and pacing distances. The boring locations indicated on the Boring and Test Pit Location Diagram are for illustrative purposes only and should be considered approximate.
Drilling was performed by a B-56 truck-mounted drill rig using continuous-flight hollow stem augers. Soil samples were obtained by means of the split-barrel sampling procedures in general accordance with ASTM D1586. In the split-barrel sampling procedure, a 2-inch O.D., split-barrel sampler is driven into the soil a distance of 18 inches by means of a 140-pound hammer falling 30 inches. The number of blows required to drive the sampler through a 12-inch interval is termed the Standard Penetration Test (SPT) value and is indicated for each sample on the boring logs. This value can be used to provide a qualitative indication of the in-place relative density of cohesionless soils. In a less reliable way, it also indicates the consistency of cohesive soils. This indication is qualitative, since many factors can significantly affect the SPT value and prevent a direct correlation between drill crews, drill rigs, drilling procedures, and hammer-rod-sampler assemblies.
Representative portions of each SPT sample were sealed in airtight containers and returned to our Asheville laboratory for classification, testing, and storage. Laboratory index testing was performed on representative samples, and included natural moisture content determinations, washes over a No. 200 sieve, and Atterberg limit testing performed in general conformance with ASTM standards. The soil samples and laboratory results were reviewed by the project geotechnical engineer, and were visually classified in general accordance with the Unified Soil Classification System (USCS). The basic elements of the USCS are described on a legend sheet attached to this report. Additional information from each soil boring is provided on the individual soil test boring logs and laboratory reports also attached to this report.
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-3-
Figure 3 – Site Option 2 (after Sparc Design/Aiton Anderson Architecture, 2015)
The project is still conceptual at this time, so no proposed finished floor elevations (FFE), anticipated building loads, etc. have been developed. However, the site is being considered for one- or two-story school buildings, so we assume that the buildings will most likely be conventional steel-framed or structural masonry buildings with concrete slab-on-grade lower floors. We also assume that final site grades will generally try to match existing grades. Therefore, maximum cut or fill depths should be on the order of 5 feet or less to prepare a level building pad across the site.
The purpose of this preliminary study was to explore the general subsurface conditions at the site and evaluate those conditions with respect to potential construction of new school buildings and related site improvements. The exploration included drilling soil test borings, digging test pits, performing engineering evaluations, and developing this report of our findings and preliminary recommendations. This report should not be solely relied upon for structural, architectural, or site grading purposes. A design-level geotechnical study will need to be performed to guide these designs, and should be performed once additional site plans with proposed building locations, site grades, retaining walls, slopes, etc. have been developed.
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 43 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-6-
SITE AND SUBSURFACE CONDITIONS
Area of Option 1: The area of Option 1 generally consists of a combination of buildings, gravel drive and parking areas, and grassed areas. A thin surficial layer of topsoil approximately 2”-3” thick was encountered in the grassed areas, and a layer of gravel between approximately 6” and 13” thick was encountered within parking and drive areas.
The upper 2 to 5 feet of the soil subgrade within the area of the test pits T-1 through T-3 contained construction debris. The soil encountered in the test pits was typically sandy lean clay or clayey sand.
The construction debris was not encountered in the soil test borings B-5 through B-7 or within test pit T-4. Typically, clayey or silty fine to medium sand was encountered at these locations from the ground surface to 8 to 12 feet below ground surface (BGS). Below the clayey or silty sand was a layer of silty fine or clayey coarse sand to the termination of the boring. The N-values within the soil test borings ranged from 5 to 19 bpf with typical values from 12 to 19 bpf. Auger refusal on rock or large obstacles was not encountered in the borings.
Brick and construction debris was encountered in T-1, T-2, and T-3. Typically, the debris encountered was red bricks. In addition, a concrete structure was encountered at approximately 1 foot below the ground surface in T-2 and was too large to be removed by the excavator. This object was possibly a portion of the prior gymnasium’s concrete foundations. The buried concrete structure was not continuous and did not cause refusal of the excavator bucket. Also, no other large concrete structures were encountered at locations T-1, T-3, and T-4. Location T-4 did not encounter any buried construction debris.
Groundwater was encountered at depths ranging from approximately 8 to 11 feet below ground surface in soil test borings B-5 through B-7 at the time of drilling. In addition, water was encountered at approximately 5 feet below ground surface in test pits T-1 and T-2. The water encountered in the test pits may be indicative of trapped or perched water within the debris-laden fill. Groundwater elevations should be expected to vary depending on seasonal fluctuations in precipitation, surface water absorption characteristics, and other factors. Due to the site’s proximity to the Swannanoa River and the possibility of perched water within debris-laden fill areas, we recommend that borings in subsequent design-level geotechnical studies remain open for a minimum of 48 hours to evaluate stabilized groundwater levels.
Laboratory test results indicate the in-situ moisture contents of the tested samples ranged from approximately 11.7 to 26.6 percent within the area of Option 1. A grain size analysis performed on a selected sample from boring B-5 indicated approximately 46 percent passing the No. 200 sieve which is indicative of a primarily coarse-grained material. Atterberg limits testing on this select sample from boring B-5 indicated a liquid limit (LL) of 39 percent and a plastic index (PI)
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-5-
SUBSURFACE TEST PIT EXPLORATION
Our preliminary subsurface exploration within the general area of Option 1 also included the excavation of four (4) test pits. We understand from information provided to us that a gymnasium was located east of the main building partially in the area of the existing modular school buildings. (The attached Boring and Test Pit Location Diagram shows an approximation of the gymnasium footprint based on the drawing provided by Buncombe County Schools, dated 1965.) We understand from conversations with Mr. Fierle that the foundation structures for the gymnasium may not have been completely removed when the building was demolished (date of demolition is unknown). Therefore, the test pits were included in this scope and located in an effort to assess whether buried foundation structures may still be present on site.
The test pit excavations were performed at the locations shown approximately on the attached Boring and Test Pit Location Diagram. The test pits were performed using a John Deere mini-excavator and were extended to a termination depth of 5.5 to 6 feet below the existing grade.
Figure 4 – View of Test Pit 2 with Concrete Object Highlighted
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 44 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-8-
CONCLUSIONS AND PRELIMINARY RECOMMENDATIONS Based on the subsurface conditions encountered during this preliminary evaluation, we offer the following preliminary geotechnical recommendations to help guide future site planning and preliminary architectural and structural designs for site structures:
x Option 1 Area
o Three of the four test pits excavated in this area (T-1, T-2, and T-3) encountered buried construction debris. One of the test pits (T-4) and the three soil test borings in this area did not encounter buried construction debris. The buried construction debris seems to be concentrated in the southeastern portion of this area, but zones of buried debris could be located outside of the specific exploration areas. It should be anticipated that debris-laden fill will be present within new building areas, the extents of which should be further delineated with respect to the final building layout during a subsequent design-level geotechnical study.
o The debris-laden fill should be considered unsuitable for support of new structures. Since the debris-laden zone was encountered at relatively shallow depths (within the upper 2 to 5 feet), we anticipate that the most efficient and cost-effective means of improving the ground in these areas would be to simply overexcavate the debris-laden fill and replace it. Undercutting and replacement to depths of up to 5 feet should be anticipated within a portion of the new building area. The amount of undercut and replace is difficult to quantify at this early stage given the limited data from this preliminary study. The information from the subsequent design-level study could be used to include undercut and replacement quantities in the construction documents. The undercut soil could be considered suitable and could be replaced as compacted fill provided that the inert construction debris is either removed or is crushed to no larger than 4 inches. Any organic or deleterious debris should be removed prior to backfilling.
o The soils encountered in the remaining locations (without debris) are suitable for support of typical light- to moderately-loaded structures supported by conventional shallow foundations. Similarly, once the debris-laden soils have been undercut and properly backfilled, they would also be suitable for support of such structures on conventional shallow foundations. Shallow foundations can likely be sized for allowable bearing pressures on the order of 2000 to 3000 psf for the Option 1 development area. Once a specific building plan and structural loading is available, this value should be reassessed.
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-7-
ranging of 20 percent indicating clayey sand. The laboratory test results are included on the Laboratory Testing Summary attached to this report.
Area of Option 2: The area of Option 2 generally consists of undeveloped grassed areas that appear to have had prior use as agricultural fields. A surficial layer of topsoil approximately 3”-5” thick was encountered.
The soil below the surficial topsoil layer typically consisted of sandy clay or clayey sand. The sandy clay samples also varied in plasticity from lean to fat. The sand encountered in the samples was typically micaceous. The N-values within the soil test borings ranged from weight of hammer to 41 bpf with typical values from 5 to 17 bpf. Auger refusal on rock or other large obstacles was not encountered in the borings.
It should be noted that very low to low consistency soil was encountered in borings B-3 and B-4 from the ground surface to approximately 5 to 8 feet BGS. The N-values of this soil ranged from weight of hammer to 7 bpf indicating very soft to medium consistency soil.
Groundwater was encountered at depths ranging from approximately 5 to 9 feet below the ground surface in soil test borings B-1, B-3, and B-4 at the time of drilling. Groundwater elevations should be expected to vary depending on seasonal fluctuations in precipitation, surface water absorption characteristics, and other factors. Due to the site’s proximity to the Swannanoa River, we recommend that borings in subsequent design-level geotechnical studies remain open for a minimum of 48 hours to evaluate stabilized groundwater levels. Groundwater is also more likely to be encountered if deep excavations are present on the Option 2 portion of the site, as the elevations of this area are typically 5 to 10 feet lower than the area of Option 1.
Laboratory test results indicate the in-situ moisture contents of the tested samples ranged from approximately 8.6 to 37 percent with a typical range of approximately 17 to 28 percent within the area of Option 2. A grain size analysis performed on a selected sample from boring B-1 indicated approximately 52 percent passing the No. 200 sieve which is indicative of a primarily fine-grained material. Atterberg limits testing on this select sample from boring B-1 indicated a liquid limit (LL) of 40 percent and a plastic index (PI) ranging of 23 percent indicating low to moderately plastic clay. The laboratory test results are included on the Laboratory Testing Summary attached to this report.
The above paragraphs provide a general summary of the subsurface conditions encountered at specific boring locations at the time of our exploration. The Boring Logs attached to this report contain more detailed information regarding the subsurface conditions encountered at each boring location. These Boring Logs represent our visual classification of the samples retrieved during the field exploration. The stratification lines on the Boring Logs designate approximate boundaries between various subsurface strata, and the actual in-situ transitions are expected to be more gradual. Subsurface conditions intermediate of the actual boring locations may vary.
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 45 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-10-
retaining walls or below-grade walls should be evaluated once site plans are further developed, and should be provided by ECS in a design-level geotechnical report.
x Based on the initial SPT data from the borings, we can estimate a seismic site classification of ‘D’ per the 2012 North Carolina Building Code. This value is for planning purposes only and would need to be refined based on a specific building layout in a future geotechnical study. In addition, a site specific Refraction Microtremor (ReMi) survey can be performed to calculate average shear wave velocity values at the site in lieu of calculation of the site classification using SPT data. The ReMi survey typically provides a less conservative measurement and may be able to improve the site classification during a design-level geotechnical study.
ADDITIONAL GEOTECHNICAL EXPLORATIONOnce project details have been developed and construction type and structural loads have been determined, ECS should perform a design-level geotechnical evaluation to develop any specific site preparation and foundation design recommendations. The design-level evaluation may include additional subsurface exploration as deemed appropriate by the ECS Geotechnical Engineer and other project designers and may consist of additional soil test borings, test pit excavations, laboratory testing, or a combination thereof.
Report of Preliminary Geotechnical Evaluation Community High School Addition Swannanoa, Buncombe County, North Carolina ECS Project Number 31-3002
-9-
x Option 2 Area
o The majority of the Option 2 area appears to have been used for agricultural purposes. As such, a surficial layer of cultivated soil should be anticipated up to approximately 2 to 3 feet thick. Cultivated soil is typically very loose and is not suitable for direct support of structures, pavements, or new fills. As such, the cultivated soil would most likely have to be stripped and replaced in a properly compacted manner.
o Zones of high-plastic clay were encountered at various depths within the soil test borings in this area (B-1, B-3, and B-4). The high-plastic clay should generally not be reused as compacted fill unless thoroughly blended with the more sandy soils. The high-plastic clay should also be considered unsuitable for direct support of building foundations, floor slabs, and pavements. In general, high-plastic clay should not be present within 2 feet of the bottom of footings or the subgrade elevation for slabs and pavements. Therefore, some undercutting of the high-plastic clay and replacement with the more sandy soils should be anticipated. The amount of undercut and replace is difficult to quantify at this early stage given the limited data from this preliminary study. The information from the subsequent design-level study could be used to include undercut and replacement quantities in the construction documents. The remaining soils encountered within the Option 2 area should be suitable for reuse as structural fill provided areas of high-plastic clay are removed.
o We anticipate that typical light- to moderately-loaded structures can be supported on conventional shallow foundations sized for an allowable bearing pressure on the order of 2000 to 2500 psf for the Option 2 development area. Once a specific building plan and structural loading is available, this value should be reassessed.
x Although groundwater is expected to rise during winter months, we would not anticipate typical seasonal fluctuations of the groundwater table to rise to an elevation above that which is expected for conventional construction for the site. Some perched water may be encountered within loose zones of the debris-laden fill, and this water may be released during excavations which may still require localized dewatering.
x No shallow rock was encountered in the soil borings or test pit locations.
x Based on the existing site grades, we do not anticipate site retaining walls or below-grade walls will be required for the development. In the event these structures are required, lateral earth pressures and coefficients of friction used for the design of site
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 46 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
BORING AND TEST PIT LOCATION DIAGRAM
PROPOSED COMMUNITY HIGH SCHOOL ADDITION235 OLD US 70
SWANNANOA, NORTH CAROLINAECS PROPOSAL NO. 31-3002
LEGEND
APPROX. TEST PIT LOCATION
NOT TO SCALE
BORING LOCATION DIAGRAM ADAPTED FROM GOOGLE EARTH IMAGERY
FOR ILLUSTRATIVE PURPOSES ONLY
Possible Prior Gym Location
T-3
T-1
T-4
T-2
B-1 APPROX. SOIL BORING LOCATION
T-1
B-1
B-4
B-3
B-6B-7
B-5
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 47 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
0
5
10
15
20
25
30
S-1
S-2
S-3
S-4
S-5
SS
SS
SS
SS
SS
18
18
18
18
18
16
13
18
18
18
Topsoil Depth [5"](CH) SANDY FAT CLAY, Contains Slight Mica,Gray and Brown, Moist, Very Soft to Soft
(CL/CH) SANDY LEAN TO FAT CLAY, Brownand Gray, Moist, Medium Stiff
(SC) CLAYEY SAND, Contains Slight Mica,Brown and Gray, Moist, Medium Dense
(CH) SANDY FAT CLAY, Contains Slight Mica,Gray and Black, Moist, Medium Stiff
END OF BORING @ 15'
wohwohwoh
woh24
5811
343
323
0
6
19
7
5
CLIENT
Buncombe County Schools
JOB #
31:3002
BORING #
B-3
SHEET
PROJECT NAMECommunity High School Addition PreliminaryGeotech
ARCHITECT-ENGINEER
Buncombe County SchoolsSITE LOCATION
235 Old US 70, Swannanoa, Buncombe County, NCNORTHING EASTING STATION
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
WL WS WD BORING STARTED 11/20/15 CAVE IN DEPTH @ 10.17'
WL(BCR) 11.00 WL(ACR) 7.00 BORING COMPLETED 11/20/15 HAMMER TYPE Auto
WL RIG B-58 FOREMAN MAH DRILLING METHOD HSADRILLING METHOD HSA
DE
PTH
(FT)
SA
MP
LE N
O.
SA
MP
LE T
YP
E
SA
MP
LE D
IST.
(IN
)
RE
CO
VE
RY
(IN
)
SURFACE ELEVATION
DESCRIPTION OF MATERIAL
WA
TER
LE
VE
LS
ELE
VA
TIO
N (F
T)
BLO
WS
/6"
10 20 30 40 50+
20% 40% 60% 80% 100%
1 2 3 4 5+
ENGLISH UNITS
BOTTOM OF CASING LOSS OF CIRCULATION
CALIBRATED PENETROMETER TONS/FT2
PLASTICLIMIT %
WATERCONTENT %
LIQUIDLIMIT %
ROCK QUALITY DESIGNATION & RECOVERYRQD% REC.%
STANDARD PENETRATIONBLOWS/FT
1 OF 1
0
5
10
15
20
25
30
S-1
S-2
S-3
S-4
S-5
SS
SS
SS
SS
SS
18
18
18
18
18
18
18
18
18
18
Topsoil Depth [5"](CL) SANDY LEAN CLAY, Brown and GrayMottled, Moist, Stiff
(SC) CLAYEY SAND, Contains Slight Mica,Brown and Gray, Moist, Medium Dense
(CH) FAT CLAY WITH SAND, Contains SlightMica, Gray, Moist, Medium Stiff
(SP-SC) MEDIUM TO COARSE SAND WITHCLAY, Trace Gravel, Contains Mica, Brown,Moist, Dense
END OF BORING @ 15'
459
468
545
234
132021
14 4017
16.6
1422.9
9 27.9
737.0
4113.4
CLIENT
Buncombe County Schools
JOB #
31:3002
BORING #
B-1
SHEET
PROJECT NAMECommunity High School Addition PreliminaryGeotech
ARCHITECT-ENGINEER
Buncombe County SchoolsSITE LOCATION
235 Old US 70, Swannanoa, Buncombe County, NCNORTHING EASTING STATION
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
WL WS WD BORING STARTED 11/20/15 CAVE IN DEPTH @ 11.43'
WL(BCR) 12.50 WL(ACR) 9.33 BORING COMPLETED 11/20/15 HAMMER TYPE Auto
WL RIG B-58 FOREMAN MAH DRILLING METHOD HSADRILLING METHOD HSA
DE
PTH
(FT)
SA
MP
LE N
O.
SA
MP
LE T
YP
E
SA
MP
LE D
IST.
(IN
)
RE
CO
VE
RY
(IN
)
SURFACE ELEVATION
DESCRIPTION OF MATERIAL
WA
TER
LE
VE
LS
ELE
VA
TIO
N (F
T)
BLO
WS
/6"
10 20 30 40 50+
20% 40% 60% 80% 100%
1 2 3 4 5+
ENGLISH UNITS
BOTTOM OF CASING LOSS OF CIRCULATION
CALIBRATED PENETROMETER TONS/FT2
PLASTICLIMIT %
WATERCONTENT %
LIQUIDLIMIT %
ROCK QUALITY DESIGNATION & RECOVERYRQD% REC.%
STANDARD PENETRATIONBLOWS/FT
1 OF 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 48 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
0
5
10
15
20
25
30
S-1
S-2
S-3
S-4
S-5
SS
SS
SS
SS
SS
18
18
18
18
18
18
18
18
4
18
Gravel Depth [13"]
(SM) SILTY FINE TO MEDIUM SAND, ContainsSlight Mica, Brown and Black, Moist, MediumDense(SC) CLAYEY FINE TO MEDIUM SAND, Grayand Brown, Moist, Medium Dense
(SP/GP) SAND WITH GRAVEL/GRAVEL WITHSAND, Brown and Tan, Moist, Medium Dense
(SM) SILTY FINE SAND, Brown, Moist, MediumDense
END OF BORING @ 15'
679
589
557
1299
657
16 25.3
17 3919
18.6
12 24.8
1811.7
12 26.6
CLIENT
Buncombe County Schools
JOB #
31:3002
BORING #
B-5
SHEET
PROJECT NAMECommunity High School Addition PreliminaryGeotech
ARCHITECT-ENGINEER
Buncombe County SchoolsSITE LOCATION
235 Old US 70, Swannanoa, Buncombe County, NCNORTHING EASTING STATION
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
WL WS WD BORING STARTED 11/20/15 CAVE IN DEPTH @ 10.00'
WL(BCR) 10.33 WL(ACR) 7.75 BORING COMPLETED 11/20/15 HAMMER TYPE Auto
WL RIG B-58 FOREMAN MAH DRILLING METHOD HSADRILLING METHOD HSA
DE
PTH
(FT)
SA
MP
LE N
O.
SA
MP
LE T
YP
E
SA
MP
LE D
IST.
(IN
)
RE
CO
VE
RY
(IN
)
SURFACE ELEVATION
DESCRIPTION OF MATERIAL
WA
TER
LE
VE
LS
ELE
VA
TIO
N (F
T)
BLO
WS
/6"
10 20 30 40 50+
20% 40% 60% 80% 100%
1 2 3 4 5+
ENGLISH UNITS
BOTTOM OF CASING LOSS OF CIRCULATION
CALIBRATED PENETROMETER TONS/FT2
PLASTICLIMIT %
WATERCONTENT %
LIQUIDLIMIT %
ROCK QUALITY DESIGNATION & RECOVERYRQD% REC.%
STANDARD PENETRATIONBLOWS/FT
1 OF 1
0
5
10
15
20
25
30
S-1
S-2
S-3
S-4
S-5
S-6
SS
SS
SS
SS
SS
SS
18
18
18
18
18
18
9
18
18
14
18
18
Topsoil Depth [3"](CL) SANDY LEAN CLAY, Contains Slight Micaand Roots, Brown, Moist, Medium Stiff
(CH) FAT CLAY WITH SAND, Contains SlightMica, Dark Gray, Moist, Medium Stiff
(SP-SC) FINE TO MEDIUM SAND WITH CLAY,Contains Slight Mica, Gray, Moist, Loose
(SP-SC) SAND WITH CLAY, Contains RockFragments, Gray, Moist, Medium Dense
(SP) MEDIUM TO COARSE SAND WITHGRAVEL, Contains Mica, Tan and Brown, Wet,Medium Dense
END OF BORING @ 20'
323
334
333
698
151010
788
5 22.6
725.5
6 20.4
178.6
20 22.1
16 17.4
CLIENT
Buncombe County Schools
JOB #
31:3002
BORING #
B-4
SHEET
PROJECT NAMECommunity High School Addition PreliminaryGeotech
ARCHITECT-ENGINEER
Buncombe County SchoolsSITE LOCATION
235 Old US 70, Swannanoa, Buncombe County, NCNORTHING EASTING STATION
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
WL WS WD BORING STARTED 11/20/15 CAVE IN DEPTH @ 6.93'
WL(BCR) 6.08 WL(ACR) 5.00 BORING COMPLETED 11/20/15 HAMMER TYPE Auto
WL RIG B-58 FOREMAN MAH DRILLING METHOD HSADRILLING METHOD HSA
DE
PTH
(FT)
SA
MP
LE N
O.
SA
MP
LE T
YP
E
SA
MP
LE D
IST.
(IN
)
RE
CO
VE
RY
(IN
)
SURFACE ELEVATION
DESCRIPTION OF MATERIAL
WA
TER
LE
VE
LS
ELE
VA
TIO
N (F
T)
BLO
WS
/6"
10 20 30 40 50+
20% 40% 60% 80% 100%
1 2 3 4 5+
ENGLISH UNITS
BOTTOM OF CASING LOSS OF CIRCULATION
CALIBRATED PENETROMETER TONS/FT2
PLASTICLIMIT %
WATERCONTENT %
LIQUIDLIMIT %
ROCK QUALITY DESIGNATION & RECOVERYRQD% REC.%
STANDARD PENETRATIONBLOWS/FT
1 OF 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 49 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
0
5
10
15
20
25
30
S-1
S-2
S-3
S-4
S-5
SS
SS
SS
SS
SS
18
18
18
18
18
12
18
18
18
18
Gravel Depth [8"](SC) CLAYEY FINE TO MEDIUM SAND, Tan,Moist, Medium Dense
(SC) CLAYEY FINE TO MEDIUM SAND, Tanand Brown Mottled, Moist, Medium Dense
(SM) SILTY FINE SAND, Contains Mica,Brown, Moist, Medium Dense
END OF BORING @ 15'
459
5810
699
369
6109
14
18
18
15
19
CLIENT
Buncombe County Schools
JOB #
31:3002
BORING #
B-7
SHEET
PROJECT NAMECommunity High School Addition PreliminaryGeotech
ARCHITECT-ENGINEER
Buncombe County SchoolsSITE LOCATION
235 Old US 70, Swannanoa, Buncombe County, NCNORTHING EASTING STATION
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
WL WS WD BORING STARTED 11/19/15 CAVE IN DEPTH @ 11.50'
WL(BCR) 12.00 WL(ACR) 10.75 BORING COMPLETED 11/19/15 HAMMER TYPE Auto
WL RIG B-58 FOREMAN MAH DRILLING METHOD HSADRILLING METHOD HSA
DE
PTH
(FT)
SA
MP
LE N
O.
SA
MP
LE T
YP
E
SA
MP
LE D
IST.
(IN
)
RE
CO
VE
RY
(IN
)
SURFACE ELEVATION
DESCRIPTION OF MATERIAL
WA
TER
LE
VE
LS
ELE
VA
TIO
N (F
T)
BLO
WS
/6"
10 20 30 40 50+
20% 40% 60% 80% 100%
1 2 3 4 5+
ENGLISH UNITS
BOTTOM OF CASING LOSS OF CIRCULATION
CALIBRATED PENETROMETER TONS/FT2
PLASTICLIMIT %
WATERCONTENT %
LIQUIDLIMIT %
ROCK QUALITY DESIGNATION & RECOVERYRQD% REC.%
STANDARD PENETRATIONBLOWS/FT
1 OF 1
0
5
10
15
20
25
30
S-1
S-2
S-3
S-4
S-5
SS
SS
SS
SS
SS
18
18
18
18
18
16
18
18
18
18
Topsoil Depth [3"](SM) SILTY FINE SAND, Contains Slight Mica,Tan, Moist, Loose
(SC) CLAYEY FINE TO MEDIUM SAND,Contains Slight Mica, Tan, Moist, Loose toMedium Dense
(SC) CLAYEY MEDIUM TO COARSE SAND,Gray and Brown, Wet, Medium Dense
END OF BORING @ 15'
323
4811
467
345
3413
5
19
13
9
17
CLIENT
Buncombe County Schools
JOB #
31:3002
BORING #
B-6
SHEET
PROJECT NAMECommunity High School Addition PreliminaryGeotech
ARCHITECT-ENGINEER
Buncombe County SchoolsSITE LOCATION
235 Old US 70, Swannanoa, Buncombe County, NCNORTHING EASTING STATION
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
WL WS WD BORING STARTED 11/19/15 CAVE IN DEPTH @ 11.83'
WL(BCR) 12.83 WL(ACR) 11.25 BORING COMPLETED 11/19/15 HAMMER TYPE Auto
WL RIG B-58 FOREMAN MAH DRILLING METHOD HSADRILLING METHOD HSA
DE
PTH
(FT)
SA
MP
LE N
O.
SA
MP
LE T
YP
E
SA
MP
LE D
IST.
(IN
)
RE
CO
VE
RY
(IN
)
SURFACE ELEVATION
DESCRIPTION OF MATERIAL
WA
TER
LE
VE
LS
ELE
VA
TIO
N (F
T)
BLO
WS
/6"
10 20 30 40 50+
20% 40% 60% 80% 100%
1 2 3 4 5+
ENGLISH UNITS
BOTTOM OF CASING LOSS OF CIRCULATION
CALIBRATED PENETROMETER TONS/FT2
PLASTICLIMIT %
WATERCONTENT %
LIQUIDLIMIT %
ROCK QUALITY DESIGNATION & RECOVERYRQD% REC.%
STANDARD PENETRATIONBLOWS/FT
1 OF 1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 50 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
0
2
4
6
8
10
12
Topsoil Depth [2"](SC FILL) CLAYEY SAND, Contains Significant Construction Debris andConcrete, Red- Tan, Moist, Medium Dense
END OF TEST PIT @ 5'
PROJECT NAME:
Community High School Addition Preliminary Geotech
TEST PIT #:
T-2CLIENT:
Buncombe County Schools
JOB #:
31:3002
SURFACEELEVATION
LOCATION:235 Old US 70, Swannanoa, Buncombe
County, NC
ARCH/ENG:
Buncombe County Schools
DESCRIPTION OF MATERIAL
REMARKS:
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
GROUND WATER: FIRST CHECK SECOND CHECK EXCAVATION EFFORT: E - EASY M - MEDIUM D - DIFFICULT VD - VERY DIFFICULTCONTRACTOR: OPERATOR: MAKE:
John DeereMODEL: REACH: CAPACITY:
ECS REP.:
DM
DATE:
12/03/15
UNITS:
DEPTH(FT.)
ELEV.(FT.)
EXCAV.EFFORT DCP QP
(TSF)SAMPLE
NO.
MOIST.CONT.
(%)
0
2
4
6
8
10
12
Gravel Depth [6"]
(SC FILL) CLAYEY SAND, Contains Brick and Construction Debris, Tan-Brown, Moist
(CL) SANDY LEAN CLAY, Red- Tan, Moist, Medium Stiff
(CL) SANDY LEAN CLAY, Mottled Gray and Tan, Moist, Medium Stiff
END OF TEST PIT @ 6.5'
PROJECT NAME:
Community High School Addition Preliminary Geotech
TEST PIT #:
T-1CLIENT:
Buncombe County Schools
JOB #:
31:3002
SURFACEELEVATION
LOCATION:235 Old US 70, Swannanoa, Buncombe
County, NC
ARCH/ENG:
Buncombe County Schools
DESCRIPTION OF MATERIAL
REMARKS:
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
GROUND WATER: FIRST CHECK SECOND CHECK EXCAVATION EFFORT: E - EASY M - MEDIUM D - DIFFICULT VD - VERY DIFFICULTCONTRACTOR: OPERATOR: MAKE:
John DeereMODEL: REACH: CAPACITY:
ECS REP.:
DM
DATE:
12/03/15
UNITS:
DEPTH(FT.)
ELEV.(FT.)
EXCAV.EFFORT DCP QP
(TSF)SAMPLE
NO.
MOIST.CONT.
(%)
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 51 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
0
2
4
6
8
10
12
Topsoil Depth [3"](SC) CLAYEY SAND, Red- Tan, Moist, Medium Dense
(CL) SANDY LEAN CLAY, Mottled Gray and Tan, Moist, Medium Stiff
END OF TEST PIT @ 5.5'
PROJECT NAME:
Community High School Addition Preliminary Geotech
TEST PIT #:
T-4CLIENT:
Buncombe County Schools
JOB #:
31:3002
SURFACEELEVATION
LOCATION:235 Old US 70, Swannanoa, Buncombe
County, NC
ARCH/ENG:
Buncombe County Schools
DESCRIPTION OF MATERIAL
REMARKS:
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
GROUND WATER: FIRST CHECK SECOND CHECK EXCAVATION EFFORT: E - EASY M - MEDIUM D - DIFFICULT VD - VERY DIFFICULTCONTRACTOR: OPERATOR: MAKE:
John DeereMODEL: REACH: CAPACITY:
ECS REP.:
DM
DATE:
12/03/15
UNITS:
DEPTH(FT.)
ELEV.(FT.)
EXCAV.EFFORT DCP QP
(TSF)SAMPLE
NO.
MOIST.CONT.
(%)
0
2
4
6
8
10
12
Topsoil Depth [2"](SC FILL) CLAYEY SAND, Contains Brick, Red- Tan, Moist, Medium Dense
(SC) CLAYEY SAND, Red- Tan, Moist, Medium Dense
(CL) SANDY LEAN CLAY, Mottled Gray and Tan, Moist, Medium Stiff
END OF TEST PIT @ 5.5'
PROJECT NAME:
Community High School Addition Preliminary Geotech
TEST PIT #:
T-3CLIENT:
Buncombe County Schools
JOB #:
31:3002
SURFACEELEVATION
LOCATION:235 Old US 70, Swannanoa, Buncombe
County, NC
ARCH/ENG:
Buncombe County Schools
DESCRIPTION OF MATERIAL
REMARKS:
THE STRATIFICATION LINES REPRESENT THE APPROXIMATE BOUNDARY LINES BETWEEN SOIL TYPES. IN-SITU THE TRANSITION MAY BE GRADUAL.
GROUND WATER: FIRST CHECK SECOND CHECK EXCAVATION EFFORT: E - EASY M - MEDIUM D - DIFFICULT VD - VERY DIFFICULTCONTRACTOR: OPERATOR: MAKE:
John DeereMODEL: REACH: CAPACITY:
ECS REP.:
DM
DATE:
12/03/15
UNITS:
DEPTH(FT.)
ELEV.(FT.)
EXCAV.EFFORT DCP QP
(TSF)SAMPLE
NO.
MOIST.CONT.
(%)
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 52 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
UNIFIED SOIL CLASSIFICATION SYSTEM (ASTM D 2487)
Major Divisions Group Symbols Typical Names Laboratory Classification Criteria
Coa
rse-
grai
ned
soils
(M
ore
than
hal
f of m
ater
ial i
s la
rger
than
No.
200
Sie
ve s
ize)
Gra
vels
(Mor
e th
an h
alf o
f coa
rse
fract
ion
is
larg
er th
an N
o. 4
sie
ve s
ize)
Cle
an g
rave
ls
(Litt
le o
r no
fines
)
GW
Well-graded gravels, gravel-sand mixtures, little or no fines
Det
erm
ine
perc
enta
ges
of s
and
and
grav
el fr
om g
rain
-siz
e cu
rve.
D
epen
ding
on
perc
enta
ge o
f fin
es (f
ract
ion
smal
ler t
han
No.
200
sie
ve s
ize)
, coa
rse-
grai
ned
soils
ar
e cl
assi
fied
as fo
llow
s:
Less
than
5 p
erce
nt
G
W, G
P, S
W, S
P
Mor
e th
an 1
2 pe
rcen
t
GM
, GC
, SM
, SC
5
to 1
2 pe
rcen
t
B
orde
rline
cas
es re
quiri
ng d
ual s
ymbo
ls b
Cu = D60/D10 greater than 4 Cc = (D30)2/(D10xD60) between 1 and 3
GP
Poorly graded gravels, gravel-sand mixtures, little or no fines
Not meeting all gradation requirements for GW
Gra
vels
with
fine
s (A
ppre
ciab
le a
mou
nt o
f fin
es)
GMa
d
Silty gravels, gravel-sand mixtures
Atterberg limits below “A” line or P.I. less than 4 Above “A” line with P.I.
between 4 and 7 are borderline cases requiring use of dual symbols
u
GC Clayey gravels, gravel-sand-clay mixtures
Atterberg limits below “A” line or P.I. less than 7
San
ds(M
ore
than
hal
f of c
oars
e fra
ctio
n is
sm
alle
r tha
n N
o. 4
sie
ve s
ize)
Cle
an s
ands
(L
ittle
or n
o fin
es)
SW Well-graded sands, gravelly sands, little or no fines
Cu = D60/D10 greater than 6 Cc = (D30)2/(D10xD60) between 1 and 3
SP Poorly graded sands, gravelly sands, little or no fines
Not meeting all gradation requirements for SW
San
ds w
ith fi
nes
(App
reci
able
am
ount
of
fines
)
SMa
d
Silty sands, sand-silt mixtures Atterberg limits above “A” line or P.I. less than 4 Limits plotting in CL-ML
zone with P.I. between 4 and 7 are borderline cases requiring use of dual symbols
u
SC Clayey sands, sand-clay mixtures
Atterberg limits above “A” line with P.I. greater than 7
Fine
-gra
ined
soi
ls
(Mor
e th
an h
alf m
ater
ial i
s sm
alle
r tha
n N
o. 2
00 S
ieve
)
Silt
s an
d cl
ays
(Liq
uid
limit
less
than
50)
ML
Inorganic silts and very fine sands, rock flour, silty or clayey fine sands, or clayey silts with slight plasticity
Plasticity Chart
0
10
20
30
40
50
60
0 10 20 30 40 50 60 70 80 90 100
Liquid Limit
Plas
ticity
Inde
x
"A" line
CH
MH and OH
CL
ML and OLCL-ML
CL
Inorganic clays of low to medium plasticity, gravelly clays, sandy clays, silty clays, lean clays
OL Organic silts and organic silty clays of low plasticity
Silt
s an
d cl
ays
(Liq
uid
limit
grea
ter t
han
50)
MH
Inorganic silts, micaceous or diatomaceous fine sandy or silty soils, elastic silts
CH Inorganic clays of high plasticity, fat clays
OH Organic clays of medium to high plasticity, organic silts
Hig
hly
Org
anic
so
ils
Pt Peat and other highly organic soils
a Division of GM and SM groups into subdivisions of d and u are for roads and airfields only. Subdivision is based on Atterberg limits; suffix d used when L.L. is 28 or less and the P.I. is 6 or less; the suffix u used when L.L. is greater than 28. b Borderline classifications, used for soils possessing characteristics of two groups, are designated by combinations of group symbols. For example: GW-GC,well-graded gravel-sand mixture with clay binder. (From Table 2.16 - Winterkorn and Fang, 1975)
B-1
S-1
1.0
0 -
2.5
016
.6C
L40
17
23
51.8
S-2
3.5
0 -
5.0
022
.9
S-3
6.0
0 -
7.5
027
.9
S-4
8.5
0 -
10.0
037
.0
S-5
13
.50 -
15.0
013
.4
B-4
S-1
1.0
0 -
2.5
022
.6
S-2
3.5
0 -
5.0
025
.5
S-3
6.0
0 -
7.5
020
.4
S-4
8.5
0 -
10.0
08.6
S-5
13
.50 -
15.0
022
.1
S-6
18
.50 -
20.0
017
.4
B-5
S-1
1.0
0 -
2.5
025
.3
S-2
3.5
0 -
5.0
018
.6S
C39
19
20
45.9
S-3
6.0
0 -
7.5
024
.8
S-4
8.5
0 -
10.0
011
.7
S-5
13
.50 -
15.0
026
.6
Lab
ora
tory
Te
sti
ng
Su
mm
ary
No
tes:
1.
AS
TM
D 2
21
6,
2.
AS
TM
D 2
48
7,
3.
AS
TM
D 4
318
, 4
. A
ST
M D
11
40,
5.
Se
e t
est
re
port
s fo
r te
st m
eth
od
, 6.
Se
e t
est
re
po
rts
for
test
meth
od
De
fin
itio
ns
:M
C:
Mo
istu
re C
on
ten
t, S
oil
Typ
e:
US
CS
(U
nifi
ed S
oil
Cla
ssifi
catio
n S
yste
m),
LL
: L
iqu
id L
imit,
PL
: P
last
ic L
imit,
PI:
Pla
stic
ity I
nde
x, C
BR
: C
alif
orn
ia B
eari
ng
Ra
tio,
OC
: O
rga
nic
Co
nte
nt
(AS
TM
D 2
97
4)
Pro
jec
t N
o.
30
02
Pro
jec
t N
am
e:
Co
mm
un
ity
Hig
h S
ch
oo
l A
dd
itio
n P
reli
min
ary
Ge
ote
ch
PM
:D
av
id M
ars
h
PE
:M
att
hew
S. F
og
lem
an
Pri
nte
d O
n:
Tu
es
da
y,
De
cem
ber
08
, 20
15
Sam
ple
So
urc
e
Sam
ple
Nu
mb
er
De
pth
(feet)
MC
1
(%)
So
il
Typ
e2
LL
Att
erb
erg
Lim
its3
PL
PI
Perc
en
t
Pa
ssin
g
No
. 20
0
Sie
ve
4
Max
imu
m
Den
sit
y
(pc
f)
Mo
istu
re -
De
ns
ity
(C
orr
.)5
Op
tim
um
Mo
istu
re
(%)
CB
R
Va
lue
6O
ther
Pag
e 1
of
1
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 53 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
1
Photo 1 View of Test Pit TP-1
Photo 2 View of Test Pit TP-2
TEST PIT PHOTOGRAPHSDECEMBER 3, 2015
COMMUNITY HIGH SCHOOL ADDITION SWANNANOA, NORTH CAROLINA
ECS PROJECT NO. 31-3002
REFERENCE NOTES FOR BORING LOGS
I. Drilling Sampling Symbols
SS Split Spoon Sampler ST Shelby Tube Sampler RC Rock Core, NX, BX, AX PM Pressuremeter DC Dutch Cone Penetrometer RD Rock Bit Drilling BS Bulk Sample of Cuttings PA Power Auger (no sample) HSA Hollow Stem Auger WS Wash sample REC Rock Sample Recovery % RQD Rock Quality Designation %
II. Correlation of Penetration Resistances to Soil Properties Standard Penetration (blows/ft) refers to the blows per foot of a 140 lb. hammer falling 30 inches on a 2-inch OD split-spoon sampler, as specified in ASTM D 1586. The blow count is commonly referred to as the N-value.
A. Non-Cohesive Soils (Silt, Sand, Gravel and Combinations)
Density Relative Properties Under 4 blows/ft Very Loose Adjective Form 12% to 49% 5 to 10 blows/ft Loose With 5% to 12% 11 to 30 blows/ft Medium Dense 31 to 50 blows/ft Dense Over 51 blows/ft Very Dense
Particle Size IdentificationBoulders 8 inches or larger Cobbles 3 to 8 inches Gravel Coarse 1 to 3 inches Medium ½ to 1 inch Fine ¼ to ½ inch Sand Coarse 2.00 mm to ¼ inch (dia. of lead pencil) Medium 0.42 to 2.00 mm (dia. of broom straw) Fine 0.074 to 0.42 mm (dia. of human hair) Silt and Clay 0.0 to 0.074 mm (particles cannot be seen)
B. Cohesive Soils (Clay, Silt, and Combinations)
Blows/ft Consistency Unconfined
Comp. Strength Qp (tsf)
Degree of Plasticity
Plasticity Index
Under 2 Very Soft Under 0.25 None to slight 0 – 4 3 to 4 Soft 0.25-0.49 Slight 5 – 7 5 to 8 Medium Stiff 0.50-0.99 Medium 8 – 22
9 to 15 Stiff 1.00-1.99 High to Very High Over 22 16 to 30 Very Stiff 2.00-3.00 31 to 50 Hard 4.00–8.00 Over 51 Very Hard Over 8.00
III. Water Level Measurement Symbols
WL Water Level BCR Before Casing Removal DCI Dry Cave-In WS While Sampling ACR After Casing Removal WCI Wet Cave-In WD While Drilling Est. Groundwater Level Est. Seasonal High GWT
The water levels are those levels actually measured in the borehole at the times indicated by the symbol. The measurements are relatively reliable when augering, without adding fluids, in a granular soil. In clay and plastic silts, the accurate determination of water levels may require several days for the water level to stabilize. In such cases, additional methods of measurement are generally applied.
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 54 of 55
S P A R C D E S I G N T U R N I N G I D E A S I N T O A R C H I T E C T U R E ®
35 Haywood Street / Suite 203 Asheville / NC / 28801828.774.5029www.sparc-design.com
3
Photo 5 View of Test Pit TP-4
TEST PIT PHOTOGRAPHSDECEMBER 3, 2015
COMMUNITY HIGH SCHOOL ADDITION SWANNANOA, NORTH CAROLINA
ECS PROJECT NO. 31-3002
2
Photo 3 View of Brick Debris in Test Pit TP-3
Photo 4 View of Test Pit TP-3
TEST PIT PHOTOGRAPHSDECEMBER 3, 2015
COMMUNITY HIGH SCHOOL ADDITION SWANNANOA, NORTH CAROLINA
ECS PROJECT NO. 31-3002
BUNCOMBE COUNTY SCHOOLS - COMMUNITY HIGH SCHOOL 01.04.2016 55 of 55