RESULT: IEEE 5 Bus system:- (5 bus system) There are 2 generator and 3 compensator present in the system. Solution: Absolute value of the slack bus real power mismatch, dpslack = 0.0009 pu Power Flow Solution by Newton-Raphson Method Maximum Power Mismatch = 1.90285e-008 No. of Iterations = 2 Bus Voltage Angle ------Load------ --- Generation--- Injected No. Mag. Degree MW Mvar MW Mvar Mvar 1 1.060 0.000 0.000 0.000 23.649 25.727 0.000

Transcript of New project

RESULT: IEEE 5 Bus system:-

(5 bus system)

There are 2 generator and 3 compensator present in the

system.

Solution:Absolute value of the slack bus real power mismatch, dpslack =

0.0009 pu

Power Flow Solution by Newton-Raphson

Method

Maximum Power Mismatch = 1.90285e-008

No. of Iterations = 2

Bus Voltage Angle ------Load------ ---

Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar

Mvar

1 1.060 0.000 0.000 0.000 23.649

25.727 0.000

2 1.045 -0.282 20.000 10.000 69.518

30.767 0.000

3 1.030 -0.495 20.000 15.000 58.990

14.052 0.000

4 1.019 -1.208 50.000 30.000 0.000

0.000 0.000

5 0.990 -2.729 60.000 40.000 0.000

0.000 0.000

Total 150.000 95.000 152.157

70.545 0.000

Total generation cost = 1596.96 $/h

IEEE 14 BUS System:-

Absolute value of the slack bus real power mismatch, dpslack =

0.0001 pu

1

Power Flow Solution by Newton-Raphson

Method

Maximum Power Mismatch = 8.98377e-005

No. of Iterations = 7

Bus Voltage Angle ------Load------ ---

Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar

Mvar

1 1.060 0.000 0.000 150.000 138.195

176.755 0.000

2 1.035 -2.578 21.700 12.700 80.000

28.926 0.000

3 0.969 -9.642 94.200 19.000 0.000

0.000 0.000

4 0.994 -6.804 47.800 -3.900 0.000

0.000 0.000

5 1.008 -5.445 7.600 1.600 0.000

0.000 0.000

6 1.000 -6.996 11.200 7.500 50.000

23.703 0.000

7 0.964 -9.047 0.000 0.000 0.000

0.000 0.000

8 0.964 -9.047 0.000 0.000 0.000

0.000 0.000

9 0.949 -10.283 29.500 16.600 0.000

0.000 0.000

2

10 0.949 -10.017 9.000 5.800 0.000

0.000 0.000

11 0.970 -8.636 3.500 1.800 0.000

0.000 0.000

12 0.982 -8.170 6.100 1.600 0.000

0.000 0.000

13 0.973 -8.402 13.500 5.800 0.000

0.000 0.000

14 0.939 -10.657 14.900 5.000 0.000

0.000 0.000

Total 259.000 223.500 268.195

229.384 0.000

Total generation cost = 2472796.22 $/h

IEEE 26 Bus system:-

3

Solution:-Absolute value of the slack bus real power mismatch, dpslack =

0.0009 pu

Power Flow Solution by Newton-Raphson

Method

Maximum Power Mismatch = 2.50139e-005

No. of Iterations = 2

Bus Voltage Angle ------Load------ ---

Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar

Mvar

1 1.025 0.000 51.000 41.000 447.665

254.743 4.000

2 1.020 -0.178 22.000 15.000 173.103

56.267 0.000

4

3 1.045 -0.540 64.000 50.000 263.084

77.306 0.000

4 1.050 -1.974 25.000 10.000 137.886

30.766 2.000

5 1.045 -1.627 50.000 30.000 166.798

146.392 5.000

6 1.000 -3.049 76.000 29.000 0.000

0.000 2.000

7 0.995 -2.351 0.000 0.000 0.000

0.000 0.000

8 0.999 -2.186 0.000 0.000 0.000

0.000 0.000

9 1.011 -4.210 89.000 50.000 0.000

0.000 3.000

10 0.992 -3.989 0.000 0.000 0.000

0.000 0.000

11 0.997 -3.009 25.000 15.000 0.000

0.000 1.500

12 0.995 -3.083 89.000 48.000 0.000

0.000 2.000

13 1.023 -1.153 31.000 15.000 0.000

0.000 0.000

14 1.008 -2.306 24.000 12.000 0.000

0.000 0.000

15 0.999 -3.074 70.000 31.000 0.000

0.000 0.500

16 0.991 -3.813 55.000 27.000 0.000

0.000 0.000

5

17 0.981 -4.374 78.000 38.000 0.000

0.000 0.000

18 1.007 -1.936 153.000 67.000 0.000

0.000 0.000

19 1.002 -6.935 75.000 15.000 0.000

0.000 5.000

20 0.984 -4.395 48.000 27.000 0.000

0.000 0.000

21 0.974 -5.823 46.000 23.000 0.000

0.000 0.000

22 0.983 -4.557 45.000 22.000 0.000

0.000 0.000

23 0.978 -8.640 25.000 12.000 0.000

0.000 0.000

24 0.959 -8.404 54.000 27.000 0.000

0.000 0.000

25 0.970 -6.744 28.000 13.000 0.000

0.000 0.000

26 1.015 -0.372 40.000 20.000 87.785

28.788 0.000

Total 1263.000 637.000 1276.321

594.262 25.000

Total generation cost = 15454.26 $/h

6

IEEE 30 BUS BYSTEM:-

7

Absolute value of the slack bus real power mismatch, dpslack =

0.0006 pu

Power Flow Solution by Newton-Raphson

Method

Maximum Power Mismatch = 5.11125e-008

No. of Iterations = 9

Bus Voltage Angle ------Load------ ---

Generation--- Injected

No. Mag. Degree MW Mvar MW Mvar

Mvar

8

1 1.060 0.000 0.000 0.000 166.158

55.638 0.000

2 1.025 -2.957 21.700 12.700 80.000

52.952 0.000

3 0.987 -5.182 2.400 1.200 0.000

0.000 0.000

4 0.971 -6.220 7.600 1.600 0.000

0.000 0.000

5 0.937 -11.077 94.200 19.000 0.000

0.000 0.000

6 0.963 -7.224 0.000 0.000 0.000

0.000 0.000

7 0.944 -9.395 22.800 10.900 0.000

0.000 0.000

8 0.970 -6.963 30.000 30.000 50.000

41.841 0.000

9 0.952 -10.825 0.000 0.000 0.000

0.000 0.000

10 0.936 -12.829 5.800 2.000 0.000

0.000 0.190

11 0.952 -10.825 0.000 0.000 0.000

0.000 0.000

12 0.962 -12.527 11.200 7.500 0.000

0.000 0.000

13 0.962 -12.527 0.000 0.000 0.000

0.000 0.000

14 0.943 -13.543 6.200 1.600 0.000

0.000 0.000

9

15 0.936 -13.529 8.200 2.500 0.000

0.000 0.000

16 0.943 -12.982 3.500 1.800 0.000

0.000 0.000

17 0.932 -13.129 9.000 5.800 0.000

0.000 0.000

18 0.923 -14.144 3.200 0.900 0.000

0.000 0.000

19 0.918 -14.273 9.500 3.400 0.000

0.000 0.000

20 0.922 -13.981 2.200 0.700 0.000

0.000 0.000

21 0.921 -13.361 17.500 11.200 0.000

0.000 0.000

22 0.921 -13.336 0.000 0.000 0.000

0.000 0.000

23 0.919 -13.777 3.200 1.600 0.000

0.000 0.000

24 0.905 -13.676 8.700 6.700 0.000

0.000 0.043

25 0.902 -13.059 0.000 0.000 0.000

0.000 0.000

26 0.882 -13.595 3.500 2.300 0.000

0.000 0.000

27 0.910 -12.346 0.000 0.000 0.000

0.000 0.000

28 0.961 -7.665 0.000 0.000 0.000

0.000 0.000

10

29 0.887 -13.910 2.400 0.900 0.000

0.000 0.000

30 0.874 -15.043 10.600 1.900 0.000

0.000 0.000

Total 283.400 126.200 296.158

150.431 0.233

Total generation cost = NaN $/h.

11