Modeling and simulation of the industrial numerical distance ...
-
Upload
khangminh22 -
Category
Documents
-
view
5 -
download
0
Transcript of Modeling and simulation of the industrial numerical distance ...
Simulation
Simulation: Transactions of the Society for
Modeling and Simulation International
1–27
� 2014 The Society for Modeling and
Simulation International
DOI: 10.1177/0037549714532961
sim.sagepub.com
Modeling and simulation of theindustrial numerical distance relayaimed at knowledge discoveryin resident event reporting
Mohammad Lutfi Othman, Ishak Aris and Noor Izzri Abdul Wahab
AbstractIn the motivation of tapping the strong potential of computational intelligence in discovering knowledge of protectiverelay operations using data mining, modeling and simulation of an actual industrial numerical distance relay and itsrecording facility are a vital requisite. This is justified by the practicality and necessity of divulging the decision algorithmhidden in the recorded relay event report using computational intelligence-based data mining. Thus, this paper studiesthe detailed modeling and simulation of an industrial AREVA MiCOM P441 distance relay, accommodated together withits own simulated event report recording facility. The idea is to provide the flexibility of allowing the simulated eventreport to have sufficiently significant depth and breadth for data mining purposes. The modeled relay has operated cor-rectly and discriminatively in deciding circuit breaker pole(s) to be tripped in stipulated assertion times as per theMalaysian licensee’s requirements for various faults and protected zones along a transmission line. It has subsequentlybeen validated successfully by the performance of the real field AREVA MiCOM P441 distance relay belonging to theMalaysian licensee. With the successful modeling and simulation of the AREVA MiCOM P441 distance relay and itsrecording facility, such subsequent works as data extraction and preparation, computational intelligence-based data min-ing for relay decision algorithm discovery and finally a relay analysis expert system development can certainly be exe-cuted. These subsequent applications are briefly explored as a demonstration of the benefit offered after the successfulmodeling of the relay.
KeywordsDistance protection, numerical protective relay, data mining, computational intelligence, Knowledge Discovery inDatabases, association rule, Rough Set Theory, relay modeling
1. Introduction
Using a suitable data mining strategy, the decision algo-
rithm of a numerical protective relay (such as a distance
relay) in the form of rules of operation logic underpinning
its event report can be intelligently discovered. An intelli-
gent data analysis process called Knowledge Discovery in
Databases (KDD) has been successfully employed to intel-
ligently discover, from the distance relay resident event
report, the hidden relay decision algorithm. This algorithm
is made up of a collection of prediction rules (C)pred
D) and
the subsequently filtered relay association rules (C)assoc
D)
related to the faults the relay has operated on. The single
relay association rule that has been successfully discov-
ered is the ultimate knowledge domain of distance protec-
tive relay behavior to be divulged from each fault. It being
a single rule is in essence the much desired
hypothesization of the relay operation characteristic. This
rule and others can then be collated to form a rule base in
the distance protective relay performance analysis expert
system.1,2
Getting to know the predetermined operation character-
istics is the first step in any analysis of relay performance
of a distance protective relay. These can be identified by a
Center for Advanced Power and Energy Research, Department of
Electrical and Electronic Engineering, Faculty of Engineering, Universiti
Putra Malaysia, Malaysia
Corresponding author:
Mohammad Lutfi Othman, Center for Advanced Power and Energy
Research, Department of Electrical and Electronic Engineering, Faculty of
Engineering, Universiti Putra Malaysia, 43400 UPM Serdang, Selangor,
Malaysia.
Email: [email protected]
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
process known as hypothesization of expected relay beha-
vior.1–4 Hypothesization of relay behavior can be imple-
mented in a number of ways:
i. soliciting expert knowledge from protection
engineers;
ii. extracting information from manufacturer’s relay
operation manuals and technical specifications;
iii. divulging information hidden in the recorded
relay event report.
The first two strategies are hard to carry out. Engineers’
expertise differs from person to person while operation
manuals usually present information that is too much to
churn out. The third strategy offers a rather challenging
approach. However, with intelligent data mining under the
framework of KDD, hypothesization can be invoked to
discover the expected relay behavior.1,2 This last approach
is more preferable since the hidden knowledge to be dis-
covered is a sure portrayal of exactly how the relay should
or has operated as designed. Othman et al.1,2 laid out a
novel data mining technique employing the integrated
computational intelligence of Rough Set Theory, the
Genetic Algorithm and Rule Quality Measure in deducing
the operation behavior of a distance relay in the form of
association rules (symbolized as C)assoc
D). C denotes the
attribute set of various multifunctional protection elements
that correlate partially or wholly to the decision class D,
that is, attribute for trip assertion status. The KDD process
involves the selection, preprocessing and transformation
of relay data resident in the event report, data mining and
interpretation of discovered knowledge.1,2,5
Data mining is particularly crucial in the overall process
of KDD. It functions as a pattern (model, or decision algo-
rithm) extractor by applying some specific computational
intelligence on data.6 In power system faults and protec-
tion analysis, data mining has gained considerable atten-
tion among protection engineers and researchers.7–9 The
growing volume of data available in digital form has accel-
erated this interest.
In the motivation of tapping the strong potential of the
integrated computational intelligence of Rough Set
Theory, the Genetic Algorithm and Rule Quality Measure
demonstrated by Othman et al.,1,2 modeling and simula-
tion of the industrial numerical distance relay and its
recording facility are necessary. Looking at the actual pro-
prietary event report retrieved from an SEL-321 digital
distance protective relay device shown in Figure 1,10 for
example, the relay decision system where the relay opera-
tion is recorded is rather concise for data mining manipu-
lation. (The relay decision system is also called relay DT,
essentially taken from ‘decision table’, an alternative term
for event report.) Thus, it is necessary that the relay
recording facility be modeled so that flexibility is gained
in allowing the modeled distance relay to be able to
‘record’ the event report with depth and breadth.
Over the years, many modeling practices have focused
on the functional aspects of relay operations and their
dynamic simulations in power system contingencies.11–13
None has emphasized the modeling of its internal relay
recording facility in order to record every possible multi-
functional protective element and show how its behavior
is dictated by its functional design and protection para-
meter settings.
The strength of data mining strategy in relay knowledge
discovery is tested based on the complexity of the relay
event report.1,2 Thus, the modeling approaches of the relay
and its recording facility must be able to make available
substantial amounts of detail in terms of:
i. number of attributes representing multifunctional
protective elements’ measured/calculated data
and logical operands (i.e. breadth in columns);
and
ii. time-tagged events (i.e. depth in rows).
It is necessary that modeling of the relay and its record-
ing facility be made based on an actual industrial numeri-
cal relay that allows a sufficiently large event report to be
simulated. This is due to the numerously available multi-
functional protective elements in a single device. In this
regard a numerical distance relay is suitable considering its
built-in multiple protection-specific and protection-support
functions.
2. Modeling and simulation of actualindustrial distance relay and itsrecording facility
In order to emulate a real numerical relay, a distance relay
is modeled and simulated using PSCAD/EMTDC to pro-
vide the simulated relay event report and the parameter
recording in a universal IEEE COMTRADE format. This
‘recorded’ relay event report in a raw form can then be
extracted and converted into a pre-data-mining decision
system DT during the KDD process.1,2 The following tasks
shall be carried out.
i. Modeling and simulation of a numerical distance
protective relay and its data recording system
based mainly on the commercial AREVA
MiCOM P441 relay that is used by TNB (Tenaga
Nasional Berhad; the Malaysian power licensee)
in their transmission line protection.14 Where
design details are not explicitly divulged, some
related features from the Schweitzer Engineering
Laboratories Inc.’s SEL321 relay are refered to.15
This cross-referencing approach is merely for
2 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
academic purposes so that any desired multifunc-
tional elements of the distance relay can be rea-
sonably modeled, parameters tuned and simulated
results studied. The intended records shall con-
sists of time signals of oscillographic measure-
ments (filtered and secondary), binary signals of
internal protective element states, external input
of various devices and relay trip output, and set-
ting parameters.
ii. Modeling and simulation of a transmission net-
work based on a 500 kV double-sourced parallel
circuit as practiced by TNB and recommended
by Conseil International des Grands Reseaux
Electriques (CIGRE).16,17 The primary instanta-
neous currents and voltages under fault condi-
tions are then applied on the modeled distance
relay (for functional and dynamic tests), and
played back on a real TNB’s AREVA MiCOM
Figure 1. SEL-321 proprietary event report depicting the relay decision system (relay DT).
Othman et al. 3
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
P441 distance relay (for the purpose of validating
the relay model).
iii. Validation of the functional and dynamic perfor-
mance of the modeled distance relay using
OMICRON’s PC-controlled test set (comprising
TEST UNIVERSE software and CMC 256 test
equipment set18) to playback captured simulated
currents and voltages into TNB’s real AREVA
MiCOM P441 distance relay. If the performance of
the modeled relay is validated, the ‘recording’ of
the simulated IEEE COMTRADE relay event
report and setting files will be used in KDD for dis-
covering the knowledge of distance relay
operations.
2.1. Development of the distance relay model
AREVA’s MiCOM P441 is a modern numerical distance
relay that operates using its phase and ground distance
quadrilateral protective elements. The exact emulation of
the AREVA relay and its application in line with TNB’s
practice imply that the modeled relay and its COMTRADE
event recording facility comply with the Institute of
Electrical and Electronics Engineers (IEEE), International
Electrotechnical Commission (IEC), CIGRE, and TNB
guidelines and standards stipulated in Monseu,17
IEEE,19,20 IEC21 and TNB.22
The quadrilateral type of distance relay as opposed to
the mho distance relay is preferably used by TNB in high-
voltage (HV) and extra high-voltage (EHV) transmission
line protection particularly because of the following:
i. the quadrilateral type is more flexible in provid-
ing sufficient resistive coverage to faults with
high resistance, particularly in ground faults;
ii. the mho type must be provided with a blinder for
load restriction on impedance, whereas the resis-
tive reach settings in the quadrilateral type can
act as a blinder at the same time;23
iii. the quadrilateral type provides high-speed tripping
of resistive faults when a pilot channel is not
present.
iv. the quadrilateral type is fairly immune to in-line
load switching.24
The disadvantages of using the quadrilateral type as
compared to the mho distance relay are as follows:
i. the quadrilateral type is affected by errors in the
current and voltage measurements when the resis-
tive reach is much greater than the reactive reach;
ii. the quadrilateral type is affected by system non-
homogeneity (i.e. unequal source and line impe-
dance angles);
iii. the quadrilateral type is affected by zero-
sequence mutual coupling in parallel lines.24
From the survey, no detailed modeling of modern
AREVA MiCOM P441 distance relay has ever been made.
Modeling this protective relay using PSCAD/EMTDC
involves creating numerous modules/submodules, each of
which is designated for either protection-specific or
protection-support function. The features imbedded in the
modeled distance relay are summarized in Table 1 and
shown in Figure 2.
The Basic Distance Protection comprises the following:
i. Quadrilateral Phase–Phase Distance Elements
(21P, i.e. 21AB, 21BC and 21CA) that measure
the positive sequence impedance of the faulted
line for phase–phase faults (AB, BC, and CA),
phase–phase–ground faults (ABG, BCG and
CAG) and three-phase faults (ABC);
ii. Quadrilateral Phase–Ground Distance Elements
(21G, i.e. 21AG, 21BG and 21CG) that measure
the positive sequence impedance of the faulted
line for phase–ground faults (AG, BG, and CG)
and three-phase faults (ABC).
Since both types of distance elements have four-zone
directional quadrilateral operation characteristics, there are
a total of:
i. twelve measuring elements in 21P; and
ii. twelve measuring elements in 21G.
The aforementioned Basic Distance Protection schemes
are suitable for standalone applications where no signaling
channels are available. As illustrated in Figure 3, the Basic
Distance scheme is suitable for single or double circuit
lines fed from one or both ends. In general, zones 1 and 2
provide main protection for the line in times Z1onT and
Z2onT, respectively, with zone 3 reaching further to pro-
vide backup protection in time Z3onT for faults on adja-
cent circuits and zone 4 in providing the reverse protection
in time Z4onT for faults behind the relay.
The phase–phase fault quadrilateral characteristics illu-
strated in Figure 4 are used in conjunction with the phase-
to-phase impedance loop measurement, the model of
which is represented in the equations shown in Table 2
that are derived according to Figure 5.
The phase–ground fault quadrilateral characteristics
illustrated in Figure 4 are used in conjunction with the
phase-to-ground impedance loop measurement, the model
of which is represented in the equations shown in Table 3
that are derived according to Figure 5.
The coordination between zones is determined to satisfy
the following conditions:
4 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
i. zone reaches: ImpedanceZone1-fwd \ImpedanceZone2-fwd \ ImpedanceZone3-fwd (each
zone operation can be manually enabled or dis-
abled as desired);
ii. time coordination: TimeZone1-fwd \ TimeZone2-fwd\ TimeZone3-fwd (each of these zone operation
times is initiated as soon as the relay picks up
when the impedance measurement enters the
above corresponding zone operation characteristic);
iii. ImpedanceZone4-rev is independent;
iv. TimeZone4-rev = TimeZone3-fwd;
v. resistive reaches of 21P elements: R1g(Zone1)
\ R2g(Zone2) \ R34g(Zone3/4) \ minimum
load impedance of the heaviest load;
vi. resistive reaches of 21G elements: R1ph(Zone1)
\ R2ph(Zone2) \ R34ph(Zone3/4) \ mini-
mum load impedance of heaviest load (i.e.
(Vnom. ph-ph(min) / O3) / (1.2 3 Inom. load(max)),
where 1.2 factor is to approximate the heaviest
load);
Table 1. Features of the distance relay model for various protection-specific or protection-support functions.
Basic distance • Phase–Phase Quadrilateral Distance Elements (21G): Measure Z1 of faulted line forphase–phase faults (3), phase–phase–ground faults (3) and three-phase fault (1).
• Phase–Ground Quadrilateral Distance Elements (21P): Measure Z1 of faulted line forphase–ground faults (3) and three-phase fault (1)
• The two types of impedance measurement element consist of:- Zone 1 forward directional instantaneous- Zone 2 forward directional time-delayed zone- Zone 3 forward directional time-delayed zone- Zone 4 reverse directional time-delayed zone
Schemes • Basic Distance schemes (21P/21G)• Channel-aided Distance schemes:
- Permissive Underreach Transfer Trip Protection accelerating Z2 (PUP Z2)- Permissive Underreach Transfer Trip Protection via forward start (PUP Fwd)- Permissive Overreach Transfer Trip Protection with overreaching Z2 (POP Z2)- Permissive Overreach Transfer Trip Protection with overreaching Z1 (POP Z1)- Blocking Overreach Transfer Trip Protection with overreaching Z2 (BOP Z2)- Blocking Overreach Transfer Trip Protection with overreaching Z1 (BOP Z1)- Current Reversal Guard to prevent maloperation of POP Z1, POP Z2, BOP Z1 and
BOP Z2- Weak Infeed scheme (WI) to supplement permissive overreach:
- Weak Infeed activation- Weak Infeed Echo
Standby (backup) DirectionalEarth Fault (DEF) protection
• Element 1: Definite-Time (DT) or Inverse-Definite-Minimum-Time (IDMT) time delayedDEF scheme
• Element 2: Definite-Time (DT) time delayed DEF scheme• Channel-aided DEF scheme:
- Permissive Overreach Transfer Trip Protection DEF (POP DEF)- Blocking Overreach Transfer Trip Protection DEF (BOP DEF)- Weak Infeed scheme (WI) to supplement permissive overreach DEF:
- Weak Infeed DEF activation- Weak Infeed DEF echo
Features • Pole Dead Supervision (PDS)• Directional Negative Sequence Overcurrent Supervision (NSOC, 67Q)• Negative Sequence Directional Element (NSD, 32Q)• Current Transformer Supervision (CTS)• Voltage Transformer Supervision (VTS)• Load Encroachment Supervision (LES)• Fault Type Identification Scheme (FTIS)• Power Swing Blocking (PSB)• Phase Distance Overcurrent Supervision (PPOC, 50P)• Ground Distance Overcurrent Supervision (PGOC, 50G)• Trip Decision Logic Module• Trip Setting/Resetting Logic Module• Switch Onto Fault Protection (SOTF)• Trip On Reclose (TOR)
Non-protection features • Event reports- Fault records- Oscillography records
• Setting records
Othman et al. 5
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Figure 2. Part illustrations of various protection-specific or protection-support functions featured in the distance relay model.
6 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
vii. the protection tripping time varies according to
the zone of operation as practiced by TNB.
Determining the four-sided polygon shape of the quad-
rilateral distance elements of both phase and ground units
requires using the zone and resistive reaches. Figure 6
illustrates the PSCAD-derived vertexes of the polygonally
shaped quadrilateral distance elements, the derivations of
which are shown in Figure 7. The calculated polygon ver-
texes can then be used to set the operation characteristics
of the quadrilateral distance elements.
The power system that the modeled distance relay is to
protect is a 500 kV double-sourced transmission system, as
shown in Figure 8. This transmission system layout is used
by TNB in their dynamic performance evaluation of the dis-
tance relay using a real-time digital simulator, RTDS,16 which
is adopting from CIGRE’s guidelines.17 The pertinent trans-
mission system parameters, models for current transformers
(CTs) (2000A/1A), capacitor coupled voltage transformers
(CCVTs) (500 kV/110 V), and the circuit breaker auxiliary
contacts are as shown. With these parameters, the zone
reaches used in Figure 7 are derived as shown in Figure 9.
The resistive reaches are set independently of the impe-
dance reach along the protected line. Rph defines the maxi-
mum amount of fault resistance additional to the line
impedance for which a phase-distance zone will trip,
regardless of the location of the fault within the zone. The
resistive reach setting of the ground distance elements, Rg,
is set to cover the desired level of earth fault resistance,
but to avoid operation with minimum load impedance.
Fault resistance would comprise arc-resistance and tower
footing resistance.
(a)
(b)
Z1onT
Relay1 Relay2
R1-Z1
R1-Z2
R2-Z1R2-Z2
Total line impedance
R1-Z3
R2-Z3
R1-Z4
R2-Z4
time
time
Z2onT
Z3onTZ4onT
Z1onT
Z2onT
Z3onTZ4onT
R1-Z1
Z1onT
R1-Z2
Z2onT
R1-Z3
Z3onT
R1-Z4
Z4onT
Trip CB1
Relay 1
R2-Z1
Z1onT
R2-Z2
Z2onT
R2-Z3
Z3onT
R2-Z4
Z4onT
Trip CB2
Relay 2
CB1
Bus1
CB2
Bus2
Relay 1 Relay 2
Figure 3. (a) Main and backup protections in the basic distance scheme where no signaling channels are needed. (b) Trip logic.
Othman et al. 7
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
No distance elements may operate in situations where
faults occur with high fault resistance. In this case, such
backup protections as channel-aided Directional Earth
Fault (DEF) protection and Negative Sequence
Overcurrent (NSOC) protection are modeled as submo-
dules that provide greater sensitivity to high resistivity, as
identified in Table 1.
In the case of power swing (oscillation in power flow)
following a power system disturbance, the impedance pre-
sented to a distance relay may move away from the normal
load area and into one or more of its tripping (start-up)
characteristics. The Power Swing Blocking (PSB) element
is thus modeled as a protection-support feature, as stated
in Table 1 that indentifies power swings following a power
system disturbance. There are basically trip-blocking and
trip-unblocking modes that are implemented with respect
to the different nature of the power swing, that is:
i. the relay should be blocked from tripping in the
event of a stable power swing;
ii. the relay should also be blocked from tripping
during loss of stability (loss of synchronism/out
of step condition) since there may be a utility
strategy for a controlled system break up during
such an event;
iii. the relay should be unblocked for tripping
(allowed to trip) in the case of faults evolving
during the occurrence of a power swing.
The PSB element detects a stable power swing or loss
of synchronism condition when all three phase–phase
measured impedances (Zab, Zbc and Zca) take longer than
at least 5 milliseconds to pass through the DR (resistive)
and DX (reactive) impedance band that surrounds the
entire phase-distance fault trip characteristic defined by
zones 3 and 4, as shown in Figure 10. In this case the dis-
tance relay should be blocked from tripping provided that
the thresholds of Ir, I2 and Iph are not exceeded, which are
indications of imminent faults. In the modeling, the inner
boundary of the DR-DX band that is made up of zones 3
and 4 is renamed zone 5 while the outer boundary is
named zone 6.
When high-speed fault clearance of all transient or per-
manent faults is required over the entire length of a pro-
tected line, a Channel-aided Distance Protection scheme
can be employed if selected in the simulation run.
Fault type identification is particularly important in
single-pole tripping schemes. Pole tripping involving
either one or all of the three phases requires that proper
phase selection is made so as to select the correct phase
and ground distance elements.25 Thus, the Fault Type
Identification Scheme (FTIS) element is modeled to deter-
mine the types of fault involved (phase–ground, phase–
phase–ground, phase–phase or three-phase) and to assist
Figure 4. Operation characteristics and resistive reaches ofphase–phase and phase–ground quadrilateral distance elements.
Table 2. Models used for the phase-to-phase impedance loopmeasurements.
Description Formula usedin the modeling
Fault impedance seen by distance relay Vαβ / (Iα– Iβ)Measured phase–phase faultimpedance loop
ZF = Z1+ (RFph / 2)
Fault resistance reach RFph / 2Quadrilateral start element angle θSE = :Z1
Vαβ : voltage of phases A-to-B, B-to-C or C-to-A; Iα or Iβ : current of
phase A, B or C; Z1: positive sequence impedance of line; RFph: fault arc
(flashover) resistance.
8 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
the Trip_Decision_Module (trip decision logic) in decid-
ing the faulted phase and setting the correct single-pole or
three-pole tripping according to TNB’s requirements,22
shown in Table 4.
In some power system configurations, an earth fault
relay may not be able to detect residual current, and phase
overcurrent elements may not operate because they have
been set higher than the maximum load current, thereby
Figure 5. Phase-to-phase and phase-to-ground impedance loops.
Othman et al. 9
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
limiting the relay’s sensitivity. Therefore, a NSOC element
is modeled to provide time-delayed backup protection for
any uncleared asymmetrical (phase–phase, phase–ground
and phase–phase–ground) faults downstream where nega-
tive sequence currents are always present. The NSOC ele-
ment gives greater sensitivity to resistive phase–phase
faults, where phase overcurrent elements may not operate.
In order to emulate a real numerical relay event record-
ing, the modeled distance relay is provided with a relay
event report and parameter recording in a universal IEEE
COMTRADE format, as shown in Figure 11. The record-
ing time step is based on the common 16 samples-per-
cycle, which is settable in the AREVA MiCOM P441 relay
and the SEL321 relay. This ‘recorded’ relay event report
in a raw form is then extracted and converted into a pre-
data-mining decision system DT by a data management
software, DIAdem, from National Instruments.26 In the
DIAdem environment, Visual Basics scripts are coded to
run the whole process of importing, selecting, preproces-
sing, transforming and finally converting and saving the
relay data, as shown in Figure 12.
2.2. Validation of the distance relay model
The modeled distance relay’s operations are validated by
comparing them with results found in the real AREVA
MiCOM P441 distance relay. The COMTRADE transient
records of the transmission system model that have been
applied to the modeled relay are played back in the actual
AREVA relay using OMICRON’s PC-controlled test set
comprising TEST UNIVERSE software and the CMC 256
test equipment set, as shown in Figure 13.
Table 5 shows that the actual relay has to be set appro-
priately to operate in the expected transmission system
similar to the settings made on the modeled relay. The
AREVA MiCOM P441 relay accepts phase-to-neutral sec-
ondary voltage injections and not those of phase-to-phase
voltages. It is important to note that during the recordings
for the playback procedure, the modeled relay is disabled
Table 3. Comparison of models used in the modeling and in the AREVA relay for the phase-to-ground impedance loopmeasurements.
Description Formula used in the modeling Formula used in AREVA relay
Fault impedance seen by distance relay VαG / (Iα+ I0k0), I0 iszero-sequence current
VαG / (Iα+ IResk0), IRes isresidual current (= 3I0)
Measured phase–ground fault impedance loop ZF = Z1+ RFg / (1 + (k0/3)) ZF = Z1+ RFg / (1 + k0)Fault resistance reach RFg / (1 + (k0/3)) RFg / (1 + k0)Residual compensation factor k0 = (Z0–Z1) / Z1 k0 = (Z0–Z1) / 3Z1Quadrilateral start element anglea θSE = : ((2Z1+Z0) / 3) θSE = : (2Z1+Z0)
aBoth equations are essentially equal; VαG: voltage of phase A-to-ground, B-to-ground or C-to-ground; Iα: current of phase A, B or C; Z1: positive
sequence impedance of line; Z0: zero-sequence impedance of line; RFg: ground fault resistance.
Figure 6. Vertexes of phase and ground quadrilateral distanceelements.
10 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
so that any measurements are without signal changes in
response to modeled relay operations. The reaction of the
AREVA MiCOM P441 distance protective relay tested
with such signals should generate the following relay resi-
dent COMTRADE records logged in its own internal non-
volatile RAM or EEPROM, ready for retrieval:
i. event records;
ii. fault (type and location) records;
iii. disturbance (oscillographic analog/digital wave-
form) records, compressed or uncompressed; and
iv. setting (configuration data) files.
3. Results and discussion
In order to understand the novel supervised learning tech-
nique of hypothesizing expected relay behavior within the
purview of integrated computational intelligence of Rough
Set Theory, the Genetic Algorithm and Rule Quality
Measure as desired by Othman et al.,1,2 the modeled dis-
tance protective relay has been subjected to the following
fault characteristics. In these cases, communication-aided
protection of the remote relay (Relay 2) is not simulated.
i. AG fault: 40 km forward (20% B2-B3, zone 1),
simulation time 1 s, fault inception at 0.5 s, fault
duration 0.1 s. For other faults such as the follow-
ing, different recording duration settings are used
to correspond to various fault durations and fault
clearance times.
ii. AB fault: 40 km forward (20% B2-B3, zone 1),
simulation time 1 s, fault inception at 0.5 s, fault
duration 0.1 s.
iii. ABG fault: 40 km forward (20% B2-B3, zone 1),
simulation time 2 s, fault inception at 0.5 s, fault
duration 0.1 s.
iv. ABC fault: 40 km forward (20% B2-B3, zone 1),
simulation time 1 s, fault inception at 0.5 s, fault
duration 0.1 s.
Figure 7. Calculations for determining vertexes of quadrilateral distance elements (only those for ground distance elements areshown).
Othman et al. 11
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
v. AG fault: 205 km forward (103% B2-B3, zone
2), simulation time 2 s, fault inception at 0.5 s,
fault duration 0.7 s (0.5 s also ok).
vi. AG fault: 250 km forward (125% B2-B3, zone
3), simulation time 5 s, fault inception at 0.5 s,
fault duration 3.5 s.
vii. AG fault: 32 km reverse (40% B2-B1, zone 4),
simulation time 5 s, fault inception at 0.5 s, fault
duration 3.5 s.
Table 6 summarizes the results of the modeled relay’s
(i.e. Relay 1) behavior in response to various fault condi-
tions. Figures 14–16 illustrate some sample plots in
response to AG, ABG and ABC faults in 40 km forward
(20% B2-B3, zone 1).
It is obvious that the corresponding Phase–Phase
Quadrilateral Distance Elements (21AB, 21BC or 21CA)
have correctly picked up a phase–phase fault in the faulted
zone of the B2-B3 section of the transmission system:
i. AB phase–phase fault by I_Z1PhDist_TripLogic
module as demonstrated by the attribute
Dist_pp_Z1 (i.e. specifically Dist_ab_Z1);
ii. ABG phase–phase–ground fault by
I_Z1PhDist_TripLogic module as demonstrated
by the attribute Dist_pp_Z1 (i.e. specifically
Dist_ab_Z1); and
iii. ABC three-phase fault by I_Z1PhDist_TripLogic
module as demonstrated by the attribute
Dist_pp_Z1 (i.e. specifically Dist_ab_Z1,
Dist_bc_Z1, and Dist_ca_Z1 together).
The corresponding Phase–Ground Quadrilateral
Distance Elements (in this case only 21AG) have also cor-
rectly picked up phase–ground faults in various faulted
zones of the transmission system:
i. AG phase–ground fault by
I_Z1GndDist_TripLogic module as demonstrated
by the corresponding attributes Dist_pg_Z1 (i.e.
specifically Dist_ag_Z1), Dist_pg_Z2 (i.e.
Dist_ag_Z2), Dist_pg_Z3 (i.e. Dist_ag_Z3) and
Dist_pg_Z4 (i.e. Dist_ag_Z4).
In the case of the ABG phase–phase–ground fault and
ABC three-phase fault, from the plots of ground impe-
dance versus ground distance characteristics in Figures 15
and 16, the Phase–Ground Quadrilateral Distance
Elements seem to have wrongfully picked up the faults
as shown by the measured trajectory locus of the
Auxillary contacts of Breaker CB1
CRZ1CRZ2CRZ4
CB52a
VI
CSZ1
CSZ2CSZ4
Distance Relay R1
WI_CS
WI_CR
VTmcb_aux
DEF_CR
DEF_CS
CB52b
DEF_WI_CR
DEF_WI_CS
Trip_PhATrip_PhBTrip_PhC
I_Relay_R1
CB1A_CB1B_CB1C_
V_CB1secI_CB1sec
VTmcb1
CB52a_1CB52b_1
CSZ1_CB1CSZ2_CB1CSZ4_CB1
WI_CS_CB1DEF_CB1
DEF_WI_CS_CB1
CSZ1_CB2CSZ2_CB2CSZ4_CB2
WI_CS_CB2DEF_CB2
DEF_WI_CS_CB2
CRZ1CRZ2CRZ4
CB52a
VI
CSZ1
CSZ2CSZ4
Distance Relay R2
WI_CS
WI_CR
VTmcb_aux
DEF_CR
DEF_CS
CB52b
DEF_WI_CR
DEF_WI_CS
Trip_PhATrip_PhBTrip_PhC
II_Relay_R2
CB2A_CB2B_CB2C_
V_CB2secI_CB2sec
VTmcb2
CB52a_2CB52b_2
CSZ1_CB1CSZ2_CB1CSZ4_CB1
WI_CS_CB1DEF_CB1
DEF_WI_CS_CB1
CSZ1_CB2CSZ2_CB2CSZ4_CB2
WI_CS_CB2DEF_CB2
DEF_WI_CS_CB2
VB_CB1
CB52a_1A
CB52a_1BCB52b_1A
CB52b_1B
123
IC_CB1IB_CB1
IA_CB1
VC_CB1
1
V_CB1
3
2
VA_CB1
Auxillary contacts of Breaker CB2CB52a_2A
CB52a_2B
CB52a_2C
CB52b_2A
CB52b_2B
CB52b_2C
1 2 3
VA_CB1(sec)VB_CB1(sec)VC_CB1(sec)
IA_CB1(sec)IB_CB1(sec)IC_CB1(sec)
V_CB1sec
I_CB1sec
IC_CB2IB_CB2
IA_CB2
VC_CB2
VB_CB2
1
V_CB2
3
2
VA_CB2
1 2 3
VA_CB2(sec)VB_CB2(sec)VC_CB2(sec)
IA_CB2(sec)IB_CB2(sec)IC_CB2(sec)
I_CB2sec
V_CB2sec
VTmcb1 VTmcb2
123
123
CB52a_1CCB52b_1C
CB52a_1 CB52b_1
123
123
CB52a_2 CB52b_2
CT
VT
2000/1A
500kV/110V
CT
VT
2000/1A
500kV/110VI_CB1 I_CB2
B_CB1
C_CB1
A_CB2
B_CB2
C_CB2
VTmcb2_AVTmcb2_BVTmcb2_C
VTmcb1_AVTmcb1_BVTmcb1_C
0Simulating healthy VT
00
123
0Simulating healthy VT
00
L
L
L
L
L
L
Z1 = 59.63 [ohm] /_ 88.08 [deg]
VPh
500.0 [kV], 50.0 [Hz]100.0 [MVA]
Z1 = 39.92 [ohm] /_ 87.90 [deg]
V Ph
500.0 [kV], 50.0 [Hz]100.0 [MVA]
Ph
Angl
e
Volta
ge
Ph Angle
Voltage
B3B2
VA
CB1 CB2
CB3 CB4
B1
S22T
S12T
B4
S32T
S31T
S21T
Fault Zone 120% B2-B3
LINE 1, 80km
LINE 2, 200km
LINE 3, 60km
LINE 4, 200km
S41T
Fault Zone 2103% B2-B3 (8.3% B3-B4)
S11T
Fault Zone 440% B2-B1
Power Source 1 Power Source 2
VA
VA
VA
CB6
VA
CB5 CB7
VA
CB8
F1tpF2tpF1tmF2tm
F5tpF5tm
32km48km
200km
160km40km
VA
VA
Relay 1 Relay 2
5km 45km
A_CB1
S33T
Fault Zone 496%(B2-B3 + B3-B4) or (83% B3-B4)
F7tmF7tp
10km
V Ph
Bx
CBx
VA
SxyT- Three-phase power
source model
- Variable input slider
- Bus (substation)
- Three-phase circuit breaker
- Transmission line (e.g from bus x to bus y)
- Multimeter
- fault
LEGEND:
L- CCVT (Capacitor coupled voltage transformer)
- CT (Current transformer)
Source positive sequence impedance:Z1GA = 39.92/_87.90deg ohmZ1GB = 59.63/_88.08deg ohmSource negative sequence impedance:Z2GA = Z1GASource zero sequence impedance:Z0GA = 31.92/_88.03deg ohmZ0GB = 71.54/_87.99deg ohmLine positive sequence impedance:Z1L = 7.9982e-5 + j 2.7299e-4 ohm/mLine positive charging susceptance:B1L = 4.1692e-9 S/m, orX1L = 239.854e6 ohm.mLine zero sequence impedance:Z0L = 3.0917e-4 + j 9.2995e-4 ohm/mLine zero charging susceptance:B0L = 2.3231e-9 S/m, orX0L = 430.459e6 ohm.mZero sequence mutual impedance:Z0mL = 2.3005e-4 + j 6.2796e-4 ohm/m
Figure 8. Double-sourced transmission system single line and distance relay models (500 kV).
12 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Zone 1 (forward) = 0.8 x Z1sec = 0.8 x [7.0384 + j24.0231 Ω (or 25.0329∡73.67º Ω)] = 5.6307 +j19.2185 (or 20.0263∡73.67 º Ω)
Zone 2 (forward) = 100% (B2-B3 line 2) + 50 %( B3-B4 line 3) = (200km + 50%.60km) x Z1sec Ω/m = (200km + 30km) x (Z1prim Ω/m x CT/VT) = 230km x (Z1prim Ω/m x CT/VT) = 230km x (7.9982e-5 + j 2.7299e-4 Ω/m) x 0.44 = 8.0942 +j27.6266 Ω (or 28.7879∡73.67º Ω)
Zone 3 (forward) = 100% of the protected line + 120% of the longest adjacent line = 100 %( B2-B3 line 2) + 120 %( B3-B4 line 4) = (100%200km + 120%200km) x Z1sec Ω/m = 440km x (Z1prim Ω/m x CT/VT) = 440km x (7.9982e-5 + j 2.7299e-4 Ω/m) x 0.44 = 15.4845 + j52.8509 Ω (or 55.0726∡73.67º Ω)
Zone 4 (reverse) ≥ ((Remote zone 2 reach (i.e. relay 2 at CB2)) x 120%) minus the protected line impedance. ≥ [(100% (B3-B2 line 2) + 50 %( B2-B1 line 1)) x 120%] - 100%(B3-B2 line 2) ≥ [(100%200km + 50%80km) x 1.2) - 100%200km] x Z1sec Ω/m ≥ 88km x (Z1prim Ω/m x CT/VT) ≥ 88km x (7.9982e-5 + j 2.7299e-4 Ω/m) x 0.44 ≥ 3.0970 + j 10.5702 Ω (or 11.0145∡73.67º Ω) i.e. ≤ -3.0970 - j 10.5702 Ω (reverse)
Z1 = R1 + jX1 (secondary +ve seqimpedance, ohm)
Z1 = Z1m(/_Z1p) (secondary +veseq impedance, ohm)
X1secperm
R1secperm*
N
D
N/D
*
R1prim/m
X1prim/m
R1sec_ProtL
CT/VT
*
*
R1prim/m x CT/VT= R1sec/m
X1prim/m x CT/VT= X1sec/m
R1sec_ProtL
X1sec_ProtL
ZONE 1 PHASE REACH SETTINGS
Zone1 % of TL_ProtL (eg, 80%)
*
*
R1_Zone1
X1_Zone1
TL_ProtL
X1sec_ProtL
R1sec_ProtL
X1sec_ProtLR1_Zone1
X1_Zone1
I_DistProt_Settings_...R1_Zone1
5.63073
X1_Zone1
19.2185
CT
VT
R1primperm
X1primperm
I_DistProt_Settings_Module ...
54321
Zone1 % of TL_ProtL (eg, 80%)
0.8
Y
X
MP
M
PY
X Z1m
Z1p
I_DistProt_Settings_Module : Contr...R1sec_ProtL
7.03842
X1sec_ProtL
24.0231
Z1p
73.6702
Characteristic angle of transmission line(Same angle repeated for all zones)
Z1p
X1sec_ProtLR1sec_ProtL
CHARACTERISTIC IMPEDANCEOF TRANSMISSION LINE
ZONE 2 PHASE REACH SETTINGS
D +
F
+
Length of shortest adjacent line (eg. 60km)
TL_ShrtAdjL
% of TL_ShrtAdjL, (eg, 50%)
*% TL_ShrtAdjL
*
*
R1sec_ProtLX1sec_ProtL
D +
F
+
R1_Zone2
X1_Zone2
R1secperm
X1secperm
R1_Zone2
X1_Zone2
I DistProt Settings ...R1_Zone2
8.09418
X1_Zone2
27.6266
I DistProt Settings Module ...
500000
0
Length of short...
60000
m
4
3
2
1
% of TL_ShrtA...
0.5
ProtL +LongAdjL
*
If AREVA is adopted
ProtL + 1.2 x LongAdjL
*
ZONE 3 PHASE REACH SETTINGS
D +
F+
Length of longest adjacent line (eg. 200km)
TL_LongAdjL
*
*
R1sec_ProtLX1sec_ProtL
D +
F
+
R1_Zone3
X1_Zone3
R1secperm
X1secperm
*
% of (ProtL + LongAdjL), (eg. 120%)
R1_Zone3
X1_Zone3
I_DistProt_Settings_Module ...
500000
0
Length of longe...
200000
m
3
2
1
% of (ProtL + L...
1.2
% of TL_LongAdjL, (eg. 120%)
TL_LongAdjL
If AREVA is adopted
ProtL +LongAdjL
ProtL + 1.2 x LongAdjL
TNB approach
SignalName
SignalName I_DistProt_Settings_...R1_Zone3
15.4845
X1_Zone3
52.8509
ZONE 4 PHASE REACH SETTINGS D +
F
+
Length of shortest line behind relay (eg. 80km)
TL_ShrtBhndL
% of TL_ShrtBhndL, (eg, 50%)
*% TL_ShrtBhndL
*
*
R1sec_ProtLX1sec_ProtL
D +
F
+
R1secperm
X1secperm*
R1_Zone4
X1_Zone4
*ProtL +
ShrtBhndL
ProtL +ShrtBhndL
D +
F
-
D +
F
-
(ProtL +ShrtBhndL) x 120%
[(ProtL + ShrtBhndL) x120%] - ProtL
(ProtL +ShrtBhndL) x 120%
X1_Zone4
R1_Zone4
1.2120%
*-1
*-1
I_DistProt_Settings_...R1_Zone4
-3.0969
X1_Zone4
-10.5702
R1_Zone4 & X1_Zone4 haveto ve numbers
I_DistProt_Settings_Module ...
500000
0
Length of short...
80000
m
4
3
2
1
% of TL_ShrtB...
0.5
Figure 9. Setting calculations of zone reaches for zone 1, 2, 3 and 4.
Othman et al. 13
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
phase–ground impedance loops of ground distance units
that traverse within the characteristics. This, however,
would not cause misoperations unexpectedly of the
I_Z1GndDist_TripLogic module, because its invocation is
blocked by the supposedly unasserted AGflt signal input
from the FTIS element (see Figure 2). Figure 15(b) illus-
trates the output signals of the FTIS module where in the
case of the ABG fault, ABGflt is asserted while the AGflt
signal is not in order to enable the pick-up signal produced
in the Dist_ab_Z1 attribute.
The modeled Relay 1 has also operated correctly in
sending signals to the circuit breaker and deciding which
pole(s) of the circuit breaker CB1 is (are) to be tripped.
The operations are agreeable to what have been stipulated
by TNB, as shown in Table 4.22
In terms of relay tripping time, the simulation results
have also demonstrated the correctness of the modeled
Relay 1’s time taken in asserting the trip signals upon
detection of the simulated faults. All the read relay trip-
ping times are in accordance to what have been set in theFigure 10. Power swing detection characteristics.
Table 4. Pole tripping schemes.
Fault types Number of pole to be opened according to TNB guidelines
≥ 275 kV 132 kV
Z1F Z1BkUp Z2F Z3F Z4R POP PUP Z1F Z1BkUp Z2F Z3F Z4R POP PUP
Ph-G (3) 1 3 3 3 3 1 1 3 3 3 3 3 3 3Ph-Ph-G (3) 3 3 3 3 3 3 3 3 3 3 3 3 3 33Ph-G (1) 3 3 3 3 3 3 3 3 3 3 3 3 3 3Ph-Ph (3) 3 3 3 3 3 3 3 3 3 3 3 3 3 33Ph (1) 3 3 3 3 3 3 3 3 3 3 3 3 3 3
TNB: Tenaga Nasional Berhad.
Table 5. Important parameters set in both the relay model and the actual AREVA MiCOM P441 relay.
Parameter Value
• Line positive sequence secondary impedance, Z1 25.033;73.67��• Line length 200 km• CT 2 kA:1 A• VT 500 kV:110 V• Zone 1 secondary impedance reach 20.026;73.67��• Zone 2 secondary impedance reach 28.788;73.67��• Zone 3 secondary impedance reach 55.073;73.67��• Zone 4 secondary impedance reach 11.015;-106.33��• Phase-distance secondary resistive reach, Rph/2 Zone 1: 4 �, Zone 2: 12.5 �, Zone 3/4: 19 �• Ground distance secondary resistive reach, R1g / (1 + k1 / 3) Zone 1: 5.2 �, Zone 2: 10 �, Zone 3/4: 14.32 �• Residual compensation factor, k0 (= k1 = k2 = k34) 2.4459;–2.9021�• Tripping time delay Zone 1: instantaneous, Zone 2: 450 ms, Zone 3/4: 3000 ms• Power swing impedance band DR (resistive): 2 �, DX (reactive): 2 �• Power swing block time delay 5 ms
14 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Figure 11. Recording of time signals of oscillographic measurements (filtered and secondary), binary signals of internal protectiveelement states, external input of various devices and relay trip output. Recording for setting parameters is not shown.
Othman et al. 15
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
relay and in fact in accordance to TNB’s requirements for
different zones of faults.
The average duration of circuit breaker operation time
of 44.2 ms is close to the set time delay in the circuit
breaker simulation of 40 ms.
In the validation of the modeled distance protective
relay operations, Figure 14(b) shows the logical plot of the
zone 1 trip signal of the actual AREVA P441 relay against
the played back secondary voltages and currents for A-G
zone 1 fault. DistGenTrp is named by TNB for any general
trip, which for this fault condition represents the zone 1
trip. It is discovered that the tripping time of the AREVA
relay is 46.47 ms, which is slower than 0.3 and 25 ms of
the relay model and TNB requirement, respectively. This
proves that the relay model has operated desirably accord-
ing to the TNB requirements but the actual AREVA relay
PSCAD ‘relay-generated’ COMTRADE files fromthe 12-channel recorder components
(analog and digital signals or setting parameters)
Select from PSCAD‘.emt’ folder directory
Import intoDIAdem
Concatenate filesinto single files
Segregation to form relaydecision system, DT, of:i. condition attributes (C)ii. decision attributes (D)
Data stability analysis toform a single- instanced
table of parametersettings
Data cleaning againstnoise and missing
values.(Differentiation betweenreal, absolute interger/zero,and binary values)
Data cleaning againstnoise and missing
values(Differentiation betweenreal, absolute interger/zero,and binary values)
Create attribute ‘time’for relay DT
Construct newcontinuous-valued
attibutes (e.g. ph-ph andph-gnd impedances from
voltages and currents
Construct newbinary-valued
attibutes
Novel discretization ofph-ph and ph-gnd
impedancesPhase comparatorof zone quadrilateral
characteristics
Syntesization byAND-compoundingimpedance pick-up
Data valueconditioning
Simplificationaccording to
zonal representation
Prepared relay DTsaved in ‘.xls’ and ‘.tdm’
(e.g. R1.xls, R1.tdm)
Relay parameters settingssaved in ‘.xls’(e.g. R1set.xls)
(Categorical data)
(Continuous data)
(Categoricaldata)
(Rough-Set-Theorybased data mining )
Raw relay datasaved in ‘.tdm’
(e.g. R1raw.tdm)
(PRAY Expert System)
Figure 12. Flowchart of data preparation strategy of relaydecision system DT.
Table
6.Resultsoftherelay’sbehaviorinrespondingto
variousfaultconditions.
Fault
type
Location
offault
Distance
unit
pickupa
Timeof
distance
unitpick
up(s)
Timeof
tripping
signalassertion
(s)
Pole(s)to
betripped
Durationof
relay
tripping
time
(ms)
Timeof
circuit
breaker
operation(s)
Durationof
circuitbreaker
operationtime
(ms)
Duration
offault
clearance
time(m
s)
Compliance
withTNB’s
required
tripped
pole?
Compliance
withTNB’srequired
relaytripping
time
accordingto
zone?
AB
CD
EF
G=(E
–D)
HI=(H
–E)
J=(H
-D)
AG
Zone1
Dist_pg_Z1
0.5149
0.5154
A0.5
0.5614
46
46.5
Yes
Yes(25ms)
AB
Zone1
Dist_pp_Z1
0.5136
0.5139
ABC
0.3
0.5607
47.1
47.1
Yes
Yes(25ms)
ABG
Zone1
Dist_pp_Z1
0.5136
0.5139
ABC
0.3
0.5609
47
47.3
Yes
Yes(25ms)
ABC
Zone1
Dist_pp_Z1
0.5136
0.5139
ABC
0.3
0.5551
41.2
41.4
Yes
Yes(25ms)
AG
Zone2
Dist_pg_Z2
0.5186
0.9689
ABC
450
1.0101
41.2
491.5
Yes
Yes(450ms)
AG
Zone3
Dist_pg_Z3
0.5186
3.5194
ABC
3000
3.5636
44.2
3045
Yes
Yes(3000ms)
AG
Zone4
Dist_pg_Z4
0.5199
3.5204
ABC
3000
3.5631
42.7
3043
Yes
Yes(3000ms)
Ave.=
44.2
a ‘Dist_pp’meansphase–phaseand‘Dist_pg’means
phase–ground
typeofthedistance
elem
ents.
TNB:TenagaNasionalBerhad.
16 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
has not been able to do so. The significant difference
between the tripping time of the AREVA relay and that of
the relay model is attributed to the fact that the tripping
time of the former takes into account delays due to its algo-
rithm execution processes and hardware operations, such
as microprocessor and trip contact motions. There is hardly
any delay in the relay model tripping time, which is mainly
due to the FORTRAN program execution in the PSCAD/
EMTDC tool that might take at least a time step, thus
instantaneous tripping is impossible for zone 1. Table 7
compares different relay tripping times between TNB
requirements, the actual AREVA MiCOM P441 distance
relay and its PSCAD/EMTDC model. It is apparent that
the tripping times of the relay model comply satisfactorily
with the TNB requirements and are faster than those of the
actual AREVA relay device. It can be seen that the actual
AREVA relay device operates in an average of approxi-
mately 40 ms from the preset time of instantaneous, 450
and 3000 ms for zone 1, zone 2 and zone 3=4, respectively.This is, as mentioned, due to the inherent hardware and
program execution delays.
The modeled relay event report and parameter record-
ings in universal IEEE COMTRADE format have also
been successfully implemented. Table 8 shows how the
Visual Basics scripts coded in DIAdem for data prepara-
tion are able to:
i. extract data from the modeled relay;
ii. select the recorded vast COMTRADE files;
iii. preprocess to form attributes as shown in the left-
hand column of Table 8; and
iv. transform, convert and save the extracted data
into the attributes shown in the right-hand column
of Table 8 – the required format, ready to be data
mined using the intended techniques employing
integrated computational intelligence of Rough
Set Theory, the Genetic Algorithm and Rule
Quality Measure in deducing the operation beha-
vior of a distance relay in the form of association
rules.
Figure 17 shows how the successful relay and recording
facility models as well as the subsequent data preparation
can then set into motion the strategy of divulging informa-
tion hidden in the recorded relay event report. With the
aforementioned intelligent data mining under the frame-
work of KDD, hypothesization of the decision algorithm
of the modeled AREVA distance relay in the form of
1. PSCAD:Transmissionsystem model& Comtradetransientrecords
2. OMICRON-TEST UNIVERSE:Playback ofComtrade transientrecords
Secondary analogsignals
OMICRON-CMC 256,playback test set& signal amplifier
AREVA MiCOMP 441 distance relay(Comtrade event,fault, disturbance,setting records)
OMICRON
Digital transient record
PSCAD
Figure 13. Preparation and playback of simulated transient fault signals into the AREVA MiCOM P441 distance protective relay.(Inset shows the experimental set up in the Tenaga Nasional Berhad (TNB) laboratory.)
Othman et al. 17
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Figure14. (a) Plots in response to the AG fault: 40 km forward (20% B2-B3, zone 1). (b) Plot of zone 1 trip signal of AREVA P441relay under test against played back voltages and currents for the A-G zone 1 fault. The inset depicts the actual light-emitting diodeannunciation and liquid crystal display of the relay after its zone 1 operation.
18 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Figure 15. (a) Plots in response to the ABG fault: 40 km forward (20% B2-B3, zone 1). (b) Output signals of FTIS_Module in thecase of the ABG fault.
Othman et al. 19
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
association rules can be practically realized as meticu-
lously discussed by the authors in other papers.1,2 The dis-
covered algorithm (for the shown AG fault), symbolized as
C)assoc
D, stipulates exactly what the condition-attribute set
of various multifunctional protection elements is in corre-
lation to the decision class D – that is, the attribute for trip
assertion status.
As discussed by the authors in other papers,1,2 by collat-
ing all the necessary relay association rules discovered
from relevantly possible contingencies trained on the relay,
a maintainable rule base for the inference strategy of a
protective-relay-analysis expert system can be conveni-
ently developed. Figure 18 demonstrates a screen shot of
an expert system called the Protective Relay Analysis
sYstem (PRAY) that is used to analyze the operation of a
protective relay (in this case, distance relay) based on the
decision algorithm discovered from the very same relay
that has been trained earlier under known (and possibly
exhaustive) fault conditions. PRAY is developed using
LabVIEW from National Instruments.27 It runs its relay
Figure 16. Plots in response to the ABC fault: 40 km forward (20% B2-B3, zone 1).
20 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
analysis by, firstly, validating whether the protective relay
under test operates correctly as expected by way of com-
parison between hypothesized and actual behavior. Then,
in the case of relay maloperations or misoperations, it diag-
noses the presented symptoms by identifying their causes.
4. Conclusion
This paper discussed the successful modeling and simulation
of an industrial AREVA MiCOM P441 numerical distance
relay, including its recording facility, that was used by the
Malaysian licensee TNB in their transmission line protection.
The protective relay modeling strategy was meticulously
aimed at producing great depth and breadth in the ‘recorded’
event report that is suitable for data mining execution in dis-
covering knowledge of protective relay operations.
The modeled relay had operated correctly and discrimi-
natively in deciding the intended circuit breaker pole(s) to
be tripped in the stipulated assertion times as per TNB’s
requirements for various faults in different zones and,
importantly, emulating the operation of the actual AREVA
MiCOM P441 numerical distance relay. The Phase–Phase
and Phase–Ground Quadrilateral Distance Elements had
correctly picked up respective phase–phase and phase–
ground faults in the faulted zone.
The successful relay and event recording facility mod-
els, as well as the subsequent data preparation, could then
readily facilitate the intelligent data mining strategy under
the KDD framework in order to hypothesize the decision
algorithm of the modeled AREVA distance relay in the
form of association rules.
Finally, an easily maintainable rule base for inference
strategy of a protective-relay-analysis expert system
(PRAY) could be developed using the discovered relay
association rules.
Table 7. Comparison of relay tripping time between Tenaga Nasional Berhad (TNB) requirements, the actual AREVA MiCOM P441distance relay and its PSCAD/EMTDC model.
Fault type Fault location Relay tripping time (ms) % difference(modeled and actual relay)
TNB’srequirement
PSCAD- modeledAREVA relay
Actual AREVAMiCOM P441
AG Zone 1 25a 0.5 46.5 99.9AB Zone 1 25 0.3 64.0 99.5ABG Zone 1 25 0.3 50.2 99.4ABC Zone 1 25 0.3 69.5 99.6AG Zone 2 450 450 494.5 9.0AG Zone 3 3000 3000 3048 1.6AG Zone 4 3000 3000 —b (not available)
aZone 1 is by default set as instantaneous.bThe actual AREVA MiCOM P441 unit has malfunctional zone 4 reverse element. Thus, a test for AG-zone-4 fault has not been carried out.
Figure 17. Integrated execution of Rough Set Theory, GeneticAlgorithm and Rule-Quality Measure-based data mining indeducing the operation behavior of a distance relay in the formof association rule.
Othman et al. 21
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Table 8. Construction of new attributes to collectively represent the simplified and discretized version of originally extractedattributes for ease of data mining process.
Attributes prior totransformation,i.e. Q (Attribute name)
Attributes after transformation, i.e. Q’
Attribute name: Attributedescription, Attribute unit
Attribute domain (set of values),i.e. V = Uq∈Q’ Vq
time* (continuous)va_filtvb_filtvc_filtia_filtib_filtic_filt
(These attributes will notinvolve in data mining butare useful for plottingreconstructed waveforms)
irirpVamvbmvcmvapvbpvcpiamibmicmiapibpicp
Zabm: AB_sec_imped, ohm(sec)Zbcm: BC_sec_imped, ohm(sec)Zcam: CA_sec_imped, ohm(sec)Zabp: AB_sec_imped, degZbcp: BC_sec_imped, degZcap: CA_sec_imped, degZagm: AG_sec_imped, ohm(sec)Zbgm: BG_sec_imped, ohm(sec)Zcgm: CG_sec_imped, ohm(sec)Zagp: AG_sec_imped, degZbgp: BG_sec_imped, degZcgp: CG_sec_imped, deg
(continuous)(continuous)(continuous)(continuous)(continuous)(continuous)(continuous)(continuous)(continuous)(continuous)(continuous)(continuous)
CB52a_ACB52b_A
CB52_A: Status of Circuit Breaker, status {Unknown, open, closed, failed}
CB52a_BCB52b_B
CB52_B: Status of Circuit Breaker, status {Unknown, open, closed, failed}
CB52a_CCB52b_C
CB52_C: Status of Circuit Breaker, status {Unknown, open, closed, failed}
VTmcb_AVTmcb_BVTmcb_C
VTmcb: Status of VT mcb, phase(open) {0, A, B, C, AB, CA, BC, ABC}
VTSfail_cnfm VTSfail_cnfm: VTSfail_cnfm, logic {0, 1}CRZ1CRZ2CRZ4WI_CRDEF_CRDEF_WI_CR
CR: Carrier received fromremote relay, carrier receive
{0, DEF_WI, DEF, (DEF,DEF_WI), WI,(WI,DEF_WI),(WI,DEF), .........(Z1,Z2,Z4,WI,DEF,DEF_WI)}Note: 26 possible combinations of CRZ1,CRZ2, CRZ4, WI_CR, DEF_CR, andDEF_WI_CR
pg_Z1PkUppg_Z2PkUppg_Z3PkUppg_Z4PkUp
pg_PkUp: Ground DistancePick Up, zone
{0, 3, 4, 23, 123}
pp_Z1PkUppp_Z2PkUppp_Z3PkUppp_Z4PkUp
pp_PkUp: Phase-distancePick Up, zone
{0, 3, 4, 23, 123}
AGfltBGfltCGfltABGfltBCGfltCAGfltABfltBCfltCAfltABC_ABCGflt
FltType: Fault type, phase {no fault, AGflt, BGflt, CGflt, ABGflt, BCGflt,CAGflt, ABflt, BCflt, CAflt, ABC_ABCGflt}
(continued)
Con
stru
ctio
n, d
iscr
etiz
atio
n an
d si
mpl
ifica
tion
of a
ttri
bute
s
22 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Table 8. (Continued)
Attributes prior totransformation,i.e. Q (Attribute name)
Attributes after transformation, i.e. Q’
Attribute name: Attributedescription, Attribute unit
Attribute domain (set of values),i.e. V = Uq∈Q’ Vq
ab50_Z1bc50_Z1ca50_Z1
pp50_Z1: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
ab50_Z2bc50_Z2ca50_Z2
pp50_Z2: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
ab50_Z3bc50_Z3ca50_Z3
pp50_Z3: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
ab50_Z4bc50_Z4ca50_Z4
pp50_Z4: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
a50_Z1b50_Z1c50_Z1
p50_Z1: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
a50_Z2b50_Z2c50_Z2
p50_Z2: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
a50_Z3b50_Z3c50_Z3
p50_Z3: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
a50_Z4b50_Z4c50_Z4
p50_Z4: Phase Overcurrentsupervision in zone, phase
{0, A, B, C, AB, BC, CA, ABC}
r50_Z1r50_Z2r50_Z3r50_Z4
r50: Residual Overcurrentsupervision in zone, zone
{0, 1, 2, 3, 4, 12, 13, 14, 23, 24, 34,123, 134, 234, 124, 1234}
PSB_Z1ppPSB_Z2ppPSB_Z3ppPSB_Z4pp
PSB: Zone blocked by PSB, zone {0, 1, 2, 3, 4, 12, 13, 14, 23, 24, 34, 123, 134,234, 124, 1234}
QF32QR32
Q32: Negative sequencedirectionality, direction
{0, Fwd, Rev}
Zload_fwdZload_rev
Zload: Impedance encroachingload characteristic, direction
{0, Fwd, Rev}
Q50_1Q50_2Q50_3Q50_4
Q50: Zone having NonDirNeq Seq OvrCurrt, zone
{0, 1, 2, 3, 4, 12, 13, 14, 23, 24, 34, 123, 134,234, 124, 1234}
Dist_ab_Z1Dist_ab_Z2Dist_ab_Z3Dist_ab_Z4
Dist_ab: Zone of Ph Dist flt, zone {0, 3, 4, 23, 123}
Dist_bc_Z1Dist_bc_Z2Dist_bc_Z3Dist_bc_Z4
Dist_bc: Zone of Ph Dist flt, zone {0, 3, 4, 23, 123}
Dist_ca_Z1Dist_ca_Z2Dist_ca_Z3Dist_ca_Z4
Dist_ca: Zone of Ph Dist flt, zone {0, 3, 4, 23, 123}
(continued)
Con
stru
ctio
n, d
iscr
etiz
atio
n an
d si
mpl
ifica
tion
of a
ttri
bute
s
Othman et al. 23
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Table 8. (Continued)
Attributes prior totransformation,i.e. Q (Attribute name)
Attributes after transformation, i.e. Q’
Attribute name: Attributedescription, Attribute unit
Attribute domain (set of values),i.e. V = Uq∈Q’ Vq
Dist_ag_Z1Dist_ag_Z2Dist_ag_Z3Dist_ag_Z4
Dist_ag: Zone of Gnd Dist flt, zone {0, 3, 4, 23, 123}
Dist_bg_Z1Dist_bg_Z2Dist_bg_Z3Dist_bg_Z4
Dist_bg: Zone of Gnd Dist flt, zone {0, 3, 4, 23, 123}
Dist_cg_Z1Dist_cg_Z2Dist_cg_Z3Dist_cg_Z4
Dist_cg: Zone of Gnd Dist flt, zone {0, 3, 4, 23, 123}
pg_TrpZ1fpg_TrpZ2fpg_TrpZ3fpg_TrpZ4r
pg_Trp: Ground Distance Trip, zone {0, 3, 4, 23, 123}
pp_TrpZ1fpp_TrpZ2fpp_TrpZ3fpp_TrpZ4r
pp_Trp: Phase-distance Trip, zone {0, 3, 4, 23, 123}
TrpPUPZ2TrpPUPFwdTrpPOPZ2POPZ2TrpPOPZ1
Trip_CAPerm: Channel-aidedpermissive trip signals, PUP_POP
{0, POPZ1, POPZ2, (POPZ2,POPZ1), PUPFwd,(PUPFwd,POPZ1), ..............PUPZ2,PUPFwd,POPZ2,POPZ1}Note: 24 possible combinations of TrpPUPZ2,TrpPUPFwd, TrpPOPZ2, TrpPOPZ1
TrpBOPZ2TrpBOPZ1
Trip_CABlck: Channel-aidedtrip-blocking signals, BOP
{0, BOPZ1, BOPZ2, (BOPZ2,BOPZ1)}
WI_TrpAWI_TrpBWI_TrpC
WI_Trp: Weak Infeed trip pole, phase {0, A, B, C, AB, BC, CA, ABC}
WI_CRTrp WI_CRTrp : WI_CRTrp, logic {0, 1}DEFelem1_trpDEFelem2_trp
DEFelem_Trp: DEF element trip signals, element {0, 1, 2, 12}
DEF_WI_CRTrp DEF_WI_CRTrp: DEF_WI_CRTrp, logic {0, 1}TrpPOP_DEFTrpBOP_DEF
Trip_DEF_CA: DEF Channel-aided permissive/blocking signals, POP/BOP
{0, BOP, POP}
DEF_WI_TrpADEF_WI_TrpBDEF_WI_TrpC
DEF_WI_Trp: Directional Earth FaultWeak Infeed trip pole, phase
{0, A, B, C, AB, BC, CA, ABC}
Trip_PhATrip_PhBTrip_PhC
Trip: Relay pole trip signals, phase {0, A, B, C, ABC}
Con
stru
ctio
n, d
iscr
etiz
atio
n an
d si
mpl
ifica
tion
of a
ttri
bute
s
24 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
Acknowledgement
The authors thank TNB, the main Malaysian power licensee, for
assistance rendered in providing invaluable information regarding
the technical requirements in modeling the distance protective
relay based on AREVA and SEL and in modeling a transmission
line based on the practice by CIGRE as adopted by TNB.
Funding
The authors gratefully acknowledge the Universiti Putra
Malaysia for the Research University Grant Scheme (RUGS 2-
2012) [project no. 05-02-12-2204RU and vote no. 9377400].
References
1. Othman ML, Aris I, Abdullah SM, et al. Knowledge discov-
ery in distance relay event report: a comparative data-mining
strategy of rough set theory with decision tree. IEEE Trans
Power Delivery 2010; 25: 2264–2287.
2. Othman ML, Aris I, Othman MR, et al. Rough-set-and-
genetic-algorithm based data mining and rule quality measure
to hypothesize distance protective relay operation characteris-
tics from relay event report. Int J Electr Power Energy Syst
2011; 33:1437–1456.
3. MAAC. Requirements for protection system operation report-
ing and analysis. Document C-3, Mid Atlantic Area Council
planning document, 2003.
4. Kezunovic M and Luo X. Automated analysis of protective
relay data. In: proceedings of the CIRED 18th international
conference electricity distribution, session 3, Turin, 6–9 June
2005.
5. Fayyad U, Shapiro GP and Smyth P. From data mining to
knowledge discovery in database. AI Magazine, American
Association for Artificial Intelligence, Fall 1996, pp.37–54.
6. Mitra S and Pal SK. Data mining in soft computing frame-
work: a survey. IEEE Trans Neural Networks 2002; 13:
3–14.
7. Othman ML, Aris I, Othman MR, et al. Rough-Set-based
timing characteristic analyses of distance protective relay.
Appl Soft Comput J 2012; 12: 2053–2062.
8. Hor CL and Crossley PA. Extracting knowledge from substa-
tion for decision system. IEEE Trans Power Delivery 2005;
20: 595–602.
9. Xu X and Peters JF. Rough set methods in power system
fault classification. In: IEEE proceedings of the Canadian
conference on electrical and computer engineering, 2002,
pp.100–105.
10. Costello D. Understanding and analyzing event report infor-
mation. Technical paper, Schweitzer Engineering
Laboratories Inc., Pullman, Washington, 2000, http://
www.selinc.com/techpprs.htm.
11. Abu Bakar AH, Fazilah MY, Sallehuddin Y, et al. Analysis
of overload conditions in distance relay under severe system
contingencies. Int J Electr Power Energy Syst 2010; 32:
345–350.
Figure 18. Association rules discovered from Knowledge Discovery in Databases involving hybrid Rough Set Theory, GeneticAlgorithm and Rule Quality Measure-based data mining can be employed as a rule base for the inference strategy of the ProtectiveRelay Analysis sYstem (PRAY).
Othman et al. 25
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
12. McLaren PG, Mustaphi K, Benmouyal G, et al. Software
models for Relays. IEEE Trans Power Delivery 2001; 16:
238–245.
13. Kezunovic M. A survey of engineering tools for protective
relaying. Electra – Task Force Report, TF BF.03, 2006,
(225), pp.26–30.
14. AREVA. MiCOM P441/P442/P444 numerical distance pro-
tection technical manual, version B1.2. Publication: P44x/
EN T/E33. AREVA T & D Worldwide Contact Center,
http://dc434.4shared.com/doc/nPROOdqs/preview.html (2006).
Accessed July 3, 2009.
15. SEL. SEL-321/SEL-321-1 phase and ground distance relay
directional overcurrent relay and fault locator: Instruction
manual, Date Code: 20070122, Schweitzer Engineering Lab.
Inc., Pullman, Washington, https://customer.selinc.com/
metadot/index.pl?iid=2533 (2007). Accessed July 3, 2009.
16. TNB. Dynamic performance evaluation of distance relay
using real time digital simulator (RTDS). TNB, Engineering
Department, Selangor, Malaysia, Work Instruction no.
ENGR-750-03-WI-10, 2007.
17. Monseu M. Evaluation of characteristics and performance of
power system protection relays and protective systems. In:
CIGRE working group 04 of study committee 34 (protection),
Paris, 1986.
18. OMICRON. OMICRON Test Universe and CM-Line
Secondary Testing catalog. OMICRON Electonics Corp.,
http://www.omicron.at/en/products/secondary (2007). Accessed
July 3, 2009.
19. IEEE. IEEE guide for protective relay applications to trans-
mission line. New York: Institute of Electrical and
Electronics Engineers, 1999.
20. IEEE. IEEE standard common format for transient data
exchange (COMTRADE) for power systems (IEEE Standard
C37.111, 1999). New York: Power Systems Relay
Committee of the IEEE Power Engineering Society, Institute
of Electrical and Electronics Engineers, 1999.
21. IEC. IEC 60255-24 Ed. 1.0: Electrical relays - part 24: com-
mon format for transient data exchange (COMTRADE) for
power systems. Geneva: International Electrotechnical
Commission, 2001.
22. TNB. TNB protection and control code of practice. Petaling
Jaya, Selangor, Malaysia: Tenaga Nasional Berhad, 2003.
23. Elmore WA. Protective relaying theory and applications.
New York: ABB Power T&D Company Inc. and Marcel
Dekker Inc., 1994.
24. Mooney JB and Peer JM. Application guidelines for ground
fault protection. Schweitzer Engineering Laboratories Inc.,
Pullman, Washington, Tech. paper, 1997, http://www.
selinc.com/techpprs.htm.
25. Calero F. Rebirth of negative-sequence quantities in protec-
tive relaying with microprocessor-based relays. In: 30th
annual western protective relay conference, Spokane,
Washington, 2003.
26. National Instruments. DIAdem: Data mining, analysis, and
report generation. Austin, Texas, USA: National Instruments
Corp., 2007.
27. National Instruments. LabVIEW basics I introduction course
manual. Austin, Texas, USA: National Instruments Corp.,
2006.
Author biographies
Mohammad Lutfi Othman received his BSc degree
with honor distinction (Magna Cum Laude) in electrical
engineering from the University of Arizona (UofA),
Tucson, Arizona, USA, in 1990, his MSc and PhD degrees
in electrical power engineering from the Universiti Putra
Malaysia (UPM), Serdang, Malaysia, in 2004 and 2011,
respectively. Currently, he is a Senior Lecturer at the
Department of Electrical and Electronics Engineering,
Faculty of Engineering, Universiti Putra Malaysia. He is a
Researcher and the founding member of the Centre for
Advanced Power and Energy Research (CAPER), UPM.
His areas of research interest include, among others, mod-
eling, simulation and operation analysis of power system
protection and numerical protective relays using computa-
tional intelligent-based data mining and expert system
approaches. He is an advocator of Rough Set Theory
applications in electrical power system researches. Due to
his rich involvement in building services installation
works, his researches also involve building energy man-
agement studies. He has developed protection related soft-
ware such as Power System Protection (PSP, a power
system protection interactive multimedia simulator and
expert system software) and Protective Relay Analysis
sYstem (PRAY, a distance protective relay performance
analysis expert system). He is a principal author of numer-
ous manuscripts of high impact factor journals such as
Simulation: Transactions of the Society for Modeling and
Simulation International, IEEE Transaction on Power
Delivery, International Journals of Electrical Power and
Energy Systems (Elsevier), Applied Soft Computing
(Elsevier) and other SCOPUS indexed journals and con-
ference proceedings. He is a technical editor for journals
of the Asian Network for Scientific Information, a
reviewer of various manuscripts submitted for journal and
conference proceeding publications and a technical eva-
luator of university research grant applications. He has
been a Keynote Speaker and Session Chair of an interna-
tional IEEE conference. He is a Professional Engineer reg-
istered under the Board of Engineers Malaysia (BEM), a
corporate member of the Institution of Engineers Malaysia
(IEM), a member of the IEEE USA, a member of the
IEEE Power and Energy Society (IEEE-PES), a member
of the IEEE Computational Intelligence Society (IEEE-
CIS), a member of the Institution of Engineering and
Technology (IET) UK, a member of the International
Rough Set Society (IRSS) and a member of Phi Kappa
Phi (FKF) Honor Society, The University of Arizona. As
a Professional Engineer, he is a Mentor and Professional
Interviewer for IEM/BEM Professional Engineer
aspirants.
Ishak Aris received his BSc degree in Electrical
Engineering from the George Washington University in
26 Simulation: Transactions of the Society for Modeling and Simulation International
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from
1988 and MSc and PhD degrees in power-electronics
engineering from the University of Bradford, UK, in 1991
and 1995, respectively. Currently he is a professor at the
Department of Electrical and Electronic Engineering,
Universiti Putra Malaysia. His areas of interest include
power electronics and drive systems, robotics, artificial
intelligence, vision systems, automotive electronics and
avionics.
Noor Izzri Abdul Wahab graduated from the
University of Manchester Institute of Science and
Technology (UMIST), UK, in Electrical and Electronic
Engineering (1998), received his MSc in Electrical Power
Engineering from the Universiti Putra Malaysia (UPM)
(2002) and his PhD (Electrical, Electronic and System
Engineering) from Universiti Kebangsaan Malaysia
(UKM) (2010). He is a Senior Lecturer in the Electrical
and Electronic Engineering Department, UPM. His areas
of interest include power system quality, power system
stability studies and application of artificial intelligence in
power systems.
Othman et al. 27
at PENNSYLVANIA STATE UNIV on September 18, 2016sim.sagepub.comDownloaded from