ctrlX DRIVEDrive Controllers, Supply Units
Instruction Manual
DOK-XDRV**-X*****UL***-IN02-EN-P
RS-7f6c9a51f782d20fc0a802862510a79d-2-en-US-2
Purpose of Documentation This documentation provides information on the installation and operation ofthe described products, by persons trained and qualified to work with electri‐cal installations.
Copyright © Bosch Rexroth AG 2021All rights reserved, also regarding any disposal, exploitation, reproduction,editing, distribution, as well as in the event of applications for industrial prop‐erty rights.
Liability The specified data is intended for product description purposes only and shallnot be deemed to be a guaranteed characteristic unless expressly stipulatedin the contract. All rights are reserved with respect to the content of this docu‐mentation and the availability of the product.
Title
Type of Documentation
Document Typecode
Internal File Reference
ctrlX DRIVE Drive Controllers, Supply Units
Table of ContentsPage
1 Important notes.............................................................................................................. 11.1 Safety instructions.................................................................................................................................. 11.1.1 General information............................................................................................................................. 11.1.2 Protection against contact with electrical parts and housings............................................................. 21.1.3 Battery safety....................................................................................................................................... 31.2 Intended use........................................................................................................................................... 4
2 Ratings and dimensions................................................................................................. 52.1 Ambient and operating conditions.......................................................................................................... 52.2 Drive controllers...................................................................................................................................... 82.3 Supply units.......................................................................................................................................... 172.4 China RoHS 2....................................................................................................................................... 19
3 Overview of documentations........................................................................................ 213.1 Motors................................................................................................................................................... 21
4 Instructions for use....................................................................................................... 234.1 Overcurrent protection.......................................................................................................................... 234.2 Connection............................................................................................................................................ 234.2.1 General information........................................................................................................................... 234.2.2 Overall connection diagram XCS*-W0054…W0070......................................................................... 244.2.3 Overall connection diagram XCS*-W01xx......................................................................................... 254.2.4 Overall connection diagram XCS*-W02xx......................................................................................... 264.2.5 Overall connection diagram XCD...................................................................................................... 274.2.6 Overall connection diagram XMS*-W0006…W0036......................................................................... 284.2.7 Overall connection diagram XMS*-W0054…W0090......................................................................... 294.2.8 Overall connection diagram XMS*-W0100…W0280......................................................................... 304.2.9 Overall connection diagram XMD*-W0606…W2323......................................................................... 314.2.10 Overall connection diagram XMD*-W5454…W7070......................................................................... 324.2.11 Overall connection diagram XMQ*-WQ001....................................................................................... 334.2.12 Overall connection diagram XMQ*-WQ002....................................................................................... 344.2.13 Overall connection diagram XVR...................................................................................................... 354.2.14 Symbols (connection diagram).......................................................................................................... 364.2.15 Connection points.............................................................................................................................. 37
5 Service and support..................................................................................................... 39
Index............................................................................................................................ 41
ctrlX DRIVE Drive Controllers, Supply Units I
Table of Contents
R911392530_Edition 02 Bosch Rexroth AG
1 Important notes1.1 Safety instructions1.1.1 General information
● Do not attempt to install and operate the components of the electricdrive and control system without first reading all documentation providedwith the product. Read and understand these safety instructions and alluser documentation prior to working with these components. If you donot have the user documentation for the components, contact ourRexroth sales representative. Ask for these documents to be sent imme‐diately to the person or persons responsible for the safe operation of thecomponents.
● If the supplied documents contain some information you do not under‐stand, it is absolutely necessary that you ask Rexroth for explanationbefore you start working at or with the components.
● If the component is resold, rented and/or passed on to others in any oth‐er form, these safety instructions must be delivered with the componentin the official language of the user's country.
● Only qualified persons may work with components of the electric driveand control system or within its proximity.In terms of this Instruction Manual, qualified persons are those personswho are familiar with the installation, mounting, commissioning and op‐eration of the components of the electric drive and control system, aswell as with the hazards this implies, and who possess the qualificationstheir work requires. To comply with these qualifications, it is necessary,among other things,– to be trained, instructed or authorized to switch electric circuits and
components safely on and off, to ground them and to mark them,– to be trained or instructed to maintain and use adequate safety
equipment,– to attend a course of instruction in first aid.
● The technical data, connection and installation conditions of the compo‐nents are specified in the respective application documentations andmust be followed at all times.
● If the components take the form of hardware, then they must remain intheir original state, in other words, no structural changes are permitted.It is not permitted to decompile software components or alter source co‐des.
● Do not mount damaged or faulty components or use them in operation.● Only use accessories and spare parts approved by Rexroth.● Follow the safety regulations and requirements of the country in which
the electric components of the electric drive and control system are op‐erated.
● Proper and correct transport, storage, mounting and installation, as wellas care in operation and maintenance, are prerequisites for optimal andsafe operation of the component.
Improper use of these components, failure to follow the safety instructions inthis document or tampering with the product, including disabling of safety de‐vices, could result in property damage, injury, electric shock or even death.
ctrlX DRIVE Drive Controllers, Supply Units 1/43
Important notes
R911392530_Edition 02 Bosch Rexroth AG
1.1.2 Protection against contact with electrical parts and housings
This section concerns components of the electric drive and con‐trol system with voltages of more than 50 volts.
Contact with parts conducting voltages above 50 volts can cause personaldanger and electric shock. When operating components of the electric driveand control system, it is unavoidable that some parts of these componentsconduct dangerous voltage. High electrical voltage! Danger to life, risk of injury by electric shock or seri‐ous injury!● Only qualified persons are allowed to operate, maintain and/or repair the
components of the electric drive and control system.● Follow the general installation and safety regulations when working on
power installations.● Before switching on, the equipment grounding conductor must have
been permanently connected to all electric components in accordancewith the connection diagram.
● Even for brief measurements or tests, operation is only allowed if theequipment grounding conductor has been permanently connected to thepoints of the components provided for this purpose.
● Before accessing electrical parts with voltage potentials higher than50 V, you must disconnect electric components from the mains or fromthe power supply unit. Secure the electric component from reconnec‐tion.
● With electric components, observe the following aspects:Always wait 30 minutes after switching off power to allow live capacitorsto discharge before accessing an electric component. Measure the elec‐trical voltage of live parts before beginning to work to make sure that theequipment is safe to touch.
● Install the covers and guards provided for this purpose before switchingon.
● Never touch any electrical connection points of the components whilepower is turned on.
● Do not remove or plug in connectors when the component has beenpowered.
● Under specific conditions, electric drive systems can be operated atmains protected by residual-current-operated circuit-breakers sensitiveto universal current (RCDs/RCMs).
● Secure built-in devices from penetrating foreign objects and water, aswell as from direct contact, by providing an external housing, for exam‐ple a control cabinet.
High housing voltage and high leakage current! Danger to life, risk of injuryby electric shock!● Before switching on and before commissioning, ground or connect the
components of the electric drive and control system to the equipmentgrounding conductor at the grounding points.
2/43
Important notes
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
● Connect the equipment grounding conductor of the components of theelectric drive and control system permanently to the main power supplyat all times. The leakage current is greater than 3.5 mA.
● Establish an equipment grounding connection with a minimum crosssection according to the table below. With an outer conductor cross sec‐tion smaller than 10 mm2 (8 AWG), the alternative connection of twoequipment grounding conductors is allowed, each having the samecross section as the outer conductors.
Cross section outer con‐ductor
Minimum cross section equipment grounding conductorLeakage current ≥ 3.5 mA
1 equipment groundingconductor
2 equipment groundingconductors
1.5 mm2 (16 AWG)
10 mm2 (8 AWG)
2 × 1.5 mm2 (16 AWG)
2.5 mm2 (14 AWG) 2 × 2.5 mm2 (14 AWG)
4 mm2 (12 AWG) 2 × 4 mm2 (12 AWG)
6 mm2 (10 AWG) 2 × 6 mm2 (10 AWG)
10 mm2 (8 AWG) -
16 mm2 (6 AWG)
16 mm2 (6 AWG)
-
25 mm2 (4 AWG) -
35 mm2 (2 AWG) -
50 mm2 (1/0 AWG) 25 mm2 (4 AWG) -
70 mm2 (2/0 AWG) 35 mm2 (2 AWG) -
... ... ...
Tab. 1-1: Minimum cross section of the equipment grounding connection
1.1.3 Battery safetyBatteries consist of active chemicals in a solid housing. Therefore, improperhandling can cause injury or property damage.Risk of injury by improper handling!● Do not attempt to reactivate low batteries by heating or other methods
(risk of explosion and cauterization).● Do not attempt to recharge the batteries as this may cause leakage or
explosion.● Do not throw batteries into open flames.● Do not dismantle batteries.● When replacing the battery/batteries, do not damage the electrical parts
installed in the devices.● Only use the battery types specified for the product.
ctrlX DRIVE Drive Controllers, Supply Units 3/43
Important notes
R911392530_Edition 02 Bosch Rexroth AG
Environmental protection and disposal! The batteries contained inthe product are considered dangerous goods during land, air, andsea transport (risk of explosion) in the sense of the legal regula‐tions. Dispose of used batteries separately from other waste. Ob‐serve the national regulations of your country.
1.2 Intended useThis product may only be used for the mentioned applications under thespecified application, ambient and operating conditions.This product is exclusively intended for use in machines and systems in anindustrial environment. This is to be understood as applications according toIEC 60204-1 "Safety of machinery, Electric equipment of machines" andNFPA 79 "Electrical Standard for Industrial Machinery".
Components of the ctrlX DRIVE system are products of Catego‐ry C3 (with restricted distribution) in accordance withIEC 61800‑3. This Category comprises EMC limit values for line-based and radiated noise emission. Compliance with this Catego‐ry (limit values) requires the appropriate measures of interferencesuppression to be used in the drive system (e.g., mains filters,shielding measures).These components are not provided for use in a public low-volt‐age mains supplying residential areas. If these components areused in such a mains, high-frequency interference is to be expec‐ted. This can require additional measures of interference suppres‐sion.
4/43
Important notes
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
2 Ratings and dimensions2.1 Ambient and operating conditions
Lethal electric shock by live parts with morethan 50 V!
WARNING
Only operate the device● with the connectors plugged on (even if no lines have been connected
to the connectors) and● with the equipment grounding conductor connected!
Control cabinet The devices in the ctrlX DRIVE product range, as well as their additionalcomponents (except for some braking resistors), have to be mounted in con‐trol cabinets.Check that the ambient and operating conditions, in particular the controlcabinet temperature, are complied with by calculating the heat levels in thecontrol cabinet. Afterwards, make the corresponding measurements to con‐firm that ambient and operating conditions have actually been observed. Inthe technical data of the individual components, the power dissipation isspecified as an important input value for calculating the heat levels.Ambient and operating conditions
Description Symbol Unit Value
Conductive dirt contamination Not allowed(Conductive dirt contamination can be prevented, forexample, by mounting the devices in control cabinetsof the degree of protection IP54 in accordance with
IEC529.)
Degree of protection (IEC529) IP20 2)
Use within scope of CSA / UL For use in NFPA 79 Applications only!
Installation altitude hnenn m 1000
Ambient temperature range Ta_work °C 0 … 40
Derating vs. ambient temperature:The performance data are reduced by the fac‐tor FTa in the ambient temperature rangeTa_work_red:
FTA = 1 - [(Ta - 40) × fTa]
Example: With an ambient temperatureTa = 50 °C and a capacity utilization factorfTa = 2%, the rated power is reduced to
PDC_cont_red = PDC_cont × FTa =
PDC_cont x (1 - [(50 - 40) x 0.02]) = PDC_cont x 0.8
Operation at ambient temperatures outside ofTa_work and Ta_work_red is not allowed!
Ta_work_red °C 40 … 55
fTa %/K 2
ctrlX DRIVE Drive Controllers, Supply Units 5/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
Description Symbol Unit Value
Derating vs. installation altitude:At an installation altitude h > hnenn, the availa‐ble performance data are reduced by the fac‐tor f1).At an installation altitude in the rangehmax_ohne to hmax, voltage-limiting measures(overvoltage limiters) have to be installed atthe mains connection of the drive system.Use above hmax is not allowed! hmax_ohne m 2000
hmax m 4000
Simultaneous derating for ambient tempera‐ture [°C] and installation altitude [m]
Allowed;reduce performance data with the product f × FTa
Derating factors (for fTa = 2 %/K)
[°C] [m]
1000 2000 4000
25 1 1 0.82
30 1 0.96 0.76
35 1 0.88 0.69
40 1 0.8 0.62
45 0.9 0.72 0.57
50 0.8 0.64 0.5
55 0.7 0.56 0.44
Relative humidity % 5 … 95
Absolute humidity g/m3 1 … 29
Moisture condensation Not allowed
Climatic category (IEC 60721‑3‑3) 3K3
Allowed pollution degree (IEC 60664‑1) 2
Resistance to chemically active substances(IEC 60721‑3‑3)
Class 3C1 3)
Vibration sine: amplitude (peak-peak) at10 … 57 Hz
mm 0.15
Vibration sine: acceleration at 57 … 150 Hz g 1
Overvoltage category III (according to IEC60664-1)
1) Reduced performance data for drive controllers: allowed DCbus continuous power, braking resistor continuous power, con‐tinuous current; additionally for converters: allowed mains volt‐age
2) Prerequisite for IP20: connector plugged in at the device, allphases connected and touch guard of DC bus connectionavailable at the device; without connector at the device, phasesnot connected (e.g., 1-phase mains connection) or withouttouch guard of DC bus connection at the device: IP10
6/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
3) Resistance to hydrogen sulfide H2S tested according to ANSI/ISA‑71.04 (Class G3) for 10 years
Tab. 2-1: Ambient and operating conditions
ctrlX DRIVE Drive Controllers, Supply Units 7/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
2.2 Drive controllersUL ratings and dimensions (XCS)
Description Symbol Unit XCS*-W0054
XCS*-W0070
XCS*-W0100
XCS*-W0120
XCS*-W0150
XCS*-W0180
XCS*-W0210
XCS*-W0250
XCS*-W0280
Listing in accordance withUL standard UL 61800-5-1
Listing in accordance withCSA standard C22.2 No. 274-17
UL‑Files E134201 E328841 E134201
Pollution degree 2
Ambient temperaturerange with nominal data Tamax °C 40
Mass m kg 5.8 10.3 17 27
Device height1) H mm 309 340.5
Device depth2) T mm 196.5
Device width3) B mm 100 225 350
Minimum distance on thetop of the device4) dtop mm 80
Minimum distance on thebottom of the device5) dbot mm 80
Horizontal spacing at thedevice6) dhor mm
0 (for devices of the ctrlX DRIVE product group in the DC bus group (central supply))1.5 (for devices of the ctrlX DRIVE product group outside of the DC bus group (individualsupply))10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage in‐put7) UN3 V 24
Rated control current in‐put8) IN3 A 5.6 4.6 4 6.9
Short circuit current rating SCCR A rms 42000
Rated input voltage, pow‐er9) ULN_nenn V AC 200Y/115V … 500Y/289V
Mains frequency fLN Hz 50 … 60
Rated input current ILN A AC 26.6 AC 34.5 AC 78 AC 101 AC 115 AC 148 AC 160 AC 176
Branch circuit protectionfuse10)
35 AClass J
50 AClass J 100 A class J 150 A Class J 250 A Class J
Required wire size in ac‐cordance with UL 508 A(internal wiring);11)
ALN AWG 8 3 1/0 kcmil 250
Field wiring material (ma‐terial; conductor tempera‐ture; class)
Cu; 75 °C; 1
Output voltage Uout VAC 0 … 500
DC 280 … 710
Output current Iout AAC 27
DC 29.4AC 35
DC 38.2AC 67DC 87
AC 71DC 87
AC 100DC 118
AC 120DC 133
AC 140DC 163
AC 147DC 176
AC 165DC 195
Maximum allowed DC buspower (ULN AC 400V) Pout kW 31.8 41.2 67.5 90 88.3 106 167 192 210
Output frequency range12) fout Hz 0 … 1600
1) 2) 3) Housing dimensions4) 5) 6) See fig. "Air intake and air outlet at device"7) Comply with supply voltage for motor holding brake;
8/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
The following power supply unit has to be used in the scope ofCSA/UL: ● UL508-certified ● output voltage: DC 24V ● outputcurrent: ≤ 31 A; for power supply units with output current >31 A: install fuses in accordance with UL248
8) See information on "Rated power consumption control voltageinput at UN3"
9) Mains input L1, L2, L3; For use on a solidly grounded wyesource only.
10) Use cUL-listed fuses. Suitable for use on a circuit capable ofdelivering not more than 42000 rms symmetrical amperes,500 Volts maximum. If using inverse-time circuit breakers (inthis case, you are obligated to prove opposite UL that an ap‐propriate circuit breaker was used) or type E combination mo‐tor controllers instead of recommended fuses, see UL61800-5-1, section 5.2.3.6.2DV.4.1.3.
11) Copper wire; PVC-insulation (conductor temperature 75 °C;Ta ≤ 40 °C) in accordance with NFPA 79 chapter 12 andUL 508A chapter 28
12) Depending on switching frequency which was set in parameterP‑0‑0001
Tab. 2-2: UL ratings and dimensionsUL ratings and dimensions (XCD)
Description Symbol Unit XCD*-W2323
Listing in accordance with ULstandard UL 61800-5-1
Listing in accordance with CSAstandard C22.2 No. 274-17
UL‑Files E134201
Pollution degree 2
Ambient temperature range withnominal data Tamax °C 40
Mass m kg 5.7
Device height1) H mm 309
Device depth2) T mm 196.5
Device width3) B mm 100
Minimum distance on the top ofthe device4) dtop mm 80
Minimum distance on the bottomof the device5) dbot mm 80
Horizontal spacing at the device6) dhor mm
0 (for devices of the ctrlX DRIVE product group in the DC busgroup (central supply))1.5 (for devices of the ctrlX DRIVE product group outside of theDC bus group (individual supply))10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage input7) UN3 V 24
Rated control current input8) IN3 A 6.6
ctrlX DRIVE Drive Controllers, Supply Units 9/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
Description Symbol Unit XCD*-W2323
Short circuit current rating SCCR A rms 42000
Rated input voltage, power9) ULN_nenn V AC 200Y/115V … 500Y/289V
Mains frequency fLN Hz 50 … 60
Rated input current ILN A 26.6
Branch circuit protection fuse10) 35 A Class J
Required wire size in accordancewith UL 508 A (internal wiring);11) ALN AWG 8
Field wiring material (material;conductor temperature; class) Cu; 75 °C; 1
Output voltage Uout VAC 0 … 500
DC 280 … 710
Output current Iout A2 × AC 7.7DC 29.4
Maximum allowed DC bus power(ULN AC 400V) Pout kW 31.8
Output frequency range12) fout Hz 0 … 1600
1) 2) 3) Housing dimensions4) 5) 6) See fig. "Air intake and air outlet at device"7) Comply with supply voltage for motor holding brake;
The following power supply unit has to be used in the scope ofCSA/UL: ● UL508-certified ● output voltage: DC 24V ● outputcurrent: ≤ 31 A; for power supply units with output current >31 A: install fuses in accordance with UL248
8) See information on "Rated power consumption control voltageinput at UN3"
9) Mains input L1, L2, L3; For use on a solidly grounded wyesource only.
10) Use cUL-listed fuses. Suitable for use on a circuit capable ofdelivering not more than 42000 rms symmetrical amperes,500 Volts maximum. If using inverse-time circuit breakers (inthis case, you are obligated to prove opposite UL that an ap‐propriate circuit breaker was used) or type E combination mo‐tor controllers instead of recommended fuses, see UL61800-5-1, section 5.2.3.6.2DV.4.1.3.
11) Copper wire; PVC-insulation (conductor temperature 75 °C;Ta ≤ 40 °C) in accordance with NFPA 79 chapter 12 andUL 508A chapter 28
12) Depending on switching frequency which was set in parameterP‑0‑0001
Tab. 2-3: UL ratings and dimensions
10/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
UL ratings and dimensions (XMS*-W0006 … 0036)
Description Symbol Unit XMS*-W0006
XMS*-W0010
XMS*-W0016
XMS*-W0023
XMS*-W0030
XMS*-W0036
Listing in accordance with ULstandard UL 61800-5-1
Listing in accordance with CSAstandard C22.2 No. 274-17
UL‑Files E134201
Pollution degree 2
Ambient temperature range withnominal data Tamax °C 40
Mass m kg 2.8
Device height1) H mm 309
Device depth2) T mm 196.5
Device width3) B mm 50
Minimum distance on the top ofthe device4) dtop mm 80
Minimum distance on the bottomof the device5) dbot mm 80
Horizontal spacing at the device6) dhor mm
0 (for devices of the ctrlX DRIVE product group in the DC busgroup (central supply))1.5 (for devices of the ctrlX DRIVE product group outside of theDC bus group (individual supply))10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage input7) UN3 V 24
Rated control current input8) IN3 A 3.3
Short circuit current rating SCCR A rms 42000
Rated input voltage, power9) ULN_nom V DC 254 ... 750
Rated input current ILN A DC 2.4 DC 4.1 DC 6.5 DC 9.4 DC 14.6 DC 22
Field wiring material (material;conductor temperature; class) Cu; 75 °C; 1
Output voltage Uout V AC 0 … 500
Output current Iout A AC 2 AC 3.3 AC 5.3 AC 7.7 AC 12 AC 18
Output frequency range11) fout Hz 0 ... 1600
1) 2) 3) Housing dimensions4) 5) 6) See fig. "Air intake and air outlet at device"7) Comply with supply voltage for motor holding brake;
The following power supply unit has to be used in the scope ofCSA/UL: ● UL508-certified ● output voltage: DC 24V ● outputcurrent: ≤ 31 A; for power supply units with output current >31 A: install fuses in accordance with UL248
8) See information on "Rated power consumption control voltageinput at UN3"
ctrlX DRIVE Drive Controllers, Supply Units 11/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
9) Mains input L1, L2, L3; For use on a solidly grounded wyesource only.
10) Copper wire; PVC-insulation (conductor temperature 75 °C;Ta ≤ 40 °C) in accordance with NFPA 79 chapter 12 andUL 508A chapter 28
11) Depending on switching frequency which was set in parameterP‑0‑0001
Tab. 2-4: UL ratings and dimensionsUL ratings and dimensions (XMS*-W0054 … 0280)
Description Symbol Unit XMS*-W0054
XMS*-W0070
XMS*-W0090
XMS*-W0100
XMS*-W0120
XMS*-W0210
XMS*-W0250
XMS*-W0280
Listing in accordance with ULstandard UL 61800-5-1
Listing in accordance with CSAstandard C22.2 No. 274-17
UL‑Files E134201
Pollution degree 2
Ambient temperature rangewith nominal data Tamax °C 40
Mass m kg 4.25 6.2 18.9
Device height1) H mm 309
Device depth2) T mm 196.5
Device width3) B mm 75 125 250
Minimum distance on the top ofthe device4) dtop mm 80
Minimum distance on the bot‐tom of the device5) dbot mm 80
Horizontal spacing at the de‐vice6) dhor mm
0 (for devices of the ctrlX DRIVE product group in the DC bus group(central supply))1.5 (for devices of the ctrlX DRIVE product group outside of the DCbus group (individual supply))10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage input7) UN3 V 24
Rated control current input8) IN3 A 4.3 6.4
Short circuit current rating SCCR A rms 42000
Rated input voltage, power9) ULN_nom V DC 254 ... 750
Rated input current ILN A DC29.4
DC38.2
DC49.1 DC 73 DC 77 DC
153DC161
DC180
Field wiring material (material;conductor temperature; class) Cu; 60/75 °C; 1
Output voltage Uout V AC 0 … 500
12/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
Description Symbol Unit XMS*-W0054
XMS*-W0070
XMS*-W0090
XMS*-W0100
XMS*-W0120
XMS*-W0210
XMS*-W0250
XMS*-W0280
Output current Iout A AC 27 AC 35 AC 45 AC 67 AC 71 AC140
AC147
AC165
Output frequency range11) fout Hz 0 ... 1600
1) 2) 3) Housing dimensions4) 5) 6) See fig. "Air intake and air outlet at device"7) Comply with supply voltage for motor holding brake;
The following power supply unit has to be used in the scope ofCSA/UL: ● UL508-certified ● output voltage: DC 24V ● outputcurrent: ≤ 31 A; for power supply units with output current >31 A: install fuses in accordance with UL248
8) See information on "Rated power consumption control voltageinput at UN3"
9) Mains input L1, L2, L3; For use on a solidly grounded wyesource only.
10) Copper wire; PVC-insulation (conductor temperature 75 °C;Ta ≤ 40 °C) in accordance with NFPA 79 chapter 12 andUL 508A chapter 28
11) Depending on switching frequency which was set in parameterP‑0‑0001
Tab. 2-5: UL ratings and dimensionsUL ratings and dimensions (XMD*)
Description Symbol Unit XMD*-W0606
XMD*-W1010
XMD*-W1616
XMD*-W2323
XMD*-W5454
XMD*-W7070
Listing in accordance with ULstandard UL 61800-5-1
Listing in accordance with CSAstandard C22.2 No. 274-17
UL‑Files E134201
Pollution degree 2
Ambient temperature range withnominal data Tamax °C 40
Mass m kg 3.3 6.7
Device height1) H mm 309
Device depth2) T mm 196.5
Device width3) B mm 50 150
Minimum distance on the top ofthe device4) dtop mm 80
Minimum distance on the bottomof the device5) dbot mm 80
Horizontal spacing at the device6) dhor mm
0 (for devices of the ctrlX DRIVE product group in the DC busgroup (central supply))1.5 (for devices of the ctrlX DRIVE product group outside of theDC bus group (individual supply))10 (for everything else (control cabinet wall, other devices, etc.))
ctrlX DRIVE Drive Controllers, Supply Units 13/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
Description Symbol Unit XMD*-W0606
XMD*-W1010
XMD*-W1616
XMD*-W2323
XMD*-W5454
XMD*-W7070
Rated control voltage input7) UN3 V 24
Rated control current input8) IN3 A 5.3 6.7
Short circuit current rating SCCR A rms 42000
Rated input voltage, power9) ULN_nom V DC 254 ... 750
Rated input current ILN A DC 4.9 DC 8.1 DC 12.9 DC 18.8 DC 47.6 DC 61.7
Field wiring material (material;conductor temperature; class) Cu; 75 °C; 1
Output voltage Uout V AC 0 ... 500
Output current Iout A
Axis 1:AC 2
Axis 2:AC 2
Axis 1:AC 3.3Axis 2:AC 3.3
Axis 1:AC 5.3Axis 2:AC 5.3
Axis 1:AC 7.7Axis 2:AC 7.7
Axis 1:AC 27Axis 2:AC 27
Axis 1:AC 35Axis 2:AC 35
Output frequency range10) fout Hz 0 ... 800 0 ... 1600
1) 2) 3) Housing dimensions4) 5) 6) See fig. "Air intake and air outlet at device"7) Comply with supply voltage for motor holding brake;
The following power supply unit has to be used in the scope ofCSA/UL: ● UL508-certified ● output voltage: DC 24V ● outputcurrent: ≤ 31 A; for power supply units with output current >31 A: install fuses in accordance with UL248
8) See information on "Rated power consumption control voltageinput at UN3"
9) Mains input L1, L2, L3; For use on a solidly grounded wyesource only.
10) Depending on switching frequency which was set in parameterP‑0‑0001
Tab. 2-6: UL ratings and dimensionsUL ratings and dimensions (XMQ*)
Description Symbol Unit XMQ*-WQ001 XMQ*-WQ002
Listing in accordance with ULstandard UL 61800-5-1
Listing in accordance with CSAstandard C22.2 No. 274-17
UL‑Files E134201
Pollution degree 2
Ambient temperature range withnominal data Tamax °C 40
Mass m kg 10 15
Device height1) H mm 309
Device depth2) T mm 196.5
Device width3) B mm 200 325
14/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
Description Symbol Unit XMQ*-WQ001 XMQ*-WQ002
Minimum distance on the top ofthe device4) dtop mm 80
Minimum distance on the bottomof the device5) dbot mm 80
Horizontal spacing at the device6) dhor mm
0 (for devices of the ctrlX DRIVE product group in the DC busgroup (central supply))1.5 (for devices of the ctrlX DRIVE product group outside of theDC bus group (individual supply))10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage input7) UN3 V 24
Rated control current input8) IN3 A 12 14.3
Short circuit current rating SCCR A rms 42000
Rated input voltage, power9) ULN_nom V DC 254 ... 750
Rated input current ILN A DC 64 DC 162
Required wire size in accordancewith NFPA 79 and UL 508 A (in‐ternal wiring);10)
ALN AWG
Axis 1: 8Axis 2: 10Axis 3: 14Axis 4: 14
Axis 1: 4Axis 2: 8
Axis 3: 10Axis 4: 14
Field wiring material (material;conductor temperature; class) Cu; 75 °C; 1
Output voltage Uout V AC 0 ... 500
Output current Iout A
Axis 1: AC 27Axis 2: AC 18Axis 3: AC 6.7Axis 4: AC 3.3
Axis 1: AC 67Axis 2: AC 35Axis 3: AC 18Axis 4: AC 3.3
Output frequency range11) fout Hz 0 ... 1600
1) 2) 3) Housing dimensions4) 5) 6) See fig. "Air intake and air outlet at device"7) Comply with supply voltage for motor holding brake;
The following power supply unit has to be used in the scope ofCSA/UL: ● UL508-certified ● output voltage: DC 24V ● outputcurrent: ≤ 31 A; for power supply units with output current >31 A: install fuses in accordance with UL248
8) See information on "Rated power consumption control voltageinput at UN3"
9) Mains input L1, L2, L3; For use on a solidly grounded wyesource only.
10) Copper wire; PVC-insulation (conductor temperature 75 °C;Ta ≤ 40 °C) in accordance with NFPA 79 chapter 12 andUL 508A chapter 28
11) Depending on switching frequency which was set in parameterP‑0‑0001
Tab. 2-7: UL ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units 15/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
Rated power consumption control voltage input at UN3
Plus motor holding brake and control section, plus safety option
Distances
A Air intakeB Air outletC Mounting surface in control cabinetD Touch guard plate at device (thickness: 1.5 mm = dhor for indi‐
vidual supply); thus, with two individually supplied devicesmounted side by side there is no distance (0 mm) between thetouch guard plates, and below the touch guard plates there is adistance of 3 mm (2 × 1.5 mm)
dtop Distance topdbot Distance bottomdhor Distance horizontalFig. 2-1: Air intake and air outlet at device
16/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
2.3 Supply unitsUL ratings and dimensions (XVR)
Description Symbol Unit XVR*-W0048 XVR*-W0072 XVR*-W0100
Listing in accordance with ULstandard UL 61800-5-1
Listing in accordance with CSAstandard C22.2 No. 274-17
UL‑Files E328841
Pollution degree 2
Ambient temperature range withnominal data Tamax °C 40
Mass m kg 16 20 27
Device height1) H mm 309 340.5
Device depth2) T mm 196.5
Device width3) B mm 225 250 350
Minimum distance on the top ofthe device4) dtop mm 80
Minimum distance on the bottomof the device5) dbot mm 80
Horizontal spacing at the device6) dhor mm
0 (for devices of the ctrlX DRIVE product group in the DC busgroup (central supply))1.5 (for devices of the ctrlX DRIVE product group outside of theDC bus group (individual supply))10 (for everything else (control cabinet wall, other devices, etc.))
Rated control voltage input7) UN3 V 24
Rated control current input IN3 A 4
Short circuit current rating SCCR A rms 42000
Rated input voltage, power8) ULN_nenn V AC 380Y/220V … 500Y/288V
Mains frequency fLN Hz 50 … 60
Rated input current ILN A 76 109 150
Branch circuit protection fuse9) Class J Fuse 100A Class J Fuse 125A Class J Fuse 200A
Required wire size in accordancewith UL 508 A (internal wiring);10) ALN AWG 3 1/0 3/0
Field wiring material (material;conductor temperature; class) Cu; 75 °C; 1
Output voltage Uout V DC 0 … 750
Output current Iout A 64 96 133
ctrlX DRIVE Drive Controllers, Supply Units 17/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
Description Symbol Unit XVR*-W0048 XVR*-W0072 XVR*-W0100
Maximum allowed DC bus power(ULN AC 400V) Pout kW 120 180 250
Output frequency range11) fout Hz 0 … 1600
1) 2) 3) Housing dimensions4) 5) 6) See fig. "Air intake and air outlet at device"7) Comply with supply voltage for motor holding brake;
The following power supply unit has to be used in the scope ofCSA/UL: ● UL508-certified ● output voltage: DC 24V ● outputcurrent: ≤ 31 A; for power supply units with output current >31 A: install fuses in accordance with UL248
8) Mains input L1, L2, L3; For use on a solidly grounded wyesource only.
9) Use cUL-listed fuses. Suitable for use on a circuit capable ofdelivering not more than 42000 rms symmetrical amperes,500 Volts maximum. If using inverse-time circuit breakers (inthis case, you are obligated to prove opposite UL that an ap‐propriate circuit breaker was used) or type E combination mo‐tor controllers instead of recommended fuses, see UL61800-5-1, section 5.2.3.6.2DV.4.1.3.
10) Copper wire; PVC-insulation (conductor temperature 75 °C;Ta ≤ 40 °C) in accordance with NFPA 79 chapter 12 andUL 508A chapter 28
11) Depending on switching frequency which was set in parameterP‑0‑0001
Tab. 2-8: UL ratings and dimensionsDistances
A Air intakeB Air outletC Mounting surface in control cabinetD Touch guard plate at device (thickness: 1.5 mm = dhor for indi‐
vidual supply); thus, with two individually supplied devicesmounted side by side there is no distance (0 mm) between thetouch guard plates, and below the touch guard plates there is adistance of 3 mm (2 × 1.5 mm)
dtop Distance topdbot Distance bottomdhor Distance horizontalFig. 2-2: Air intake and air outlet at device
18/43
Ratings and dimensions
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
2.4 China RoHS 2www.boschrexroth.com.cn/zh/cn/home_2/china_rohs2
ctrlX DRIVE Drive Controllers, Supply Units 19/43
Ratings and dimensions
R911392530_Edition 02 Bosch Rexroth AG
3 Overview of documentations3.1 MotorsTitle Type of documentation Document typecode1)
DOK-MOTOR*-…
Material number
MS2NSynchronous Servomotors
Project Planning Manual MS2N*******-PRxx-EN-P R911347583
MS2SSynchronous Servomotors
Project Planning Manual MS2S*******-PRxx-EN-P R911410075
MS2ESynchronous Servomotorsacc. to ATEX Directive 2014/34/EU
Project Planning Manual MS2E*******-PRxx-EN-P R911394140
MSKSynchronous Servomotors
Project Planning Manual MSK********-PRxx-EN-P R911296289
MSKSynchronous Servomotorsfor Potentially Explosive Areas
Project Planning Manual MSK*EXGIIK3-PRxx-EN-P R911312709
MKE Synchronous MotorsSynchronous Servo Motorsfor Potentially Explosive Areasacc. to ATEX and UL / CSA
Project Planning Manual MKE*GEN2***-PRxx-EN-P R911297663
MAD / MAFAsynchronous Motors MAD / MAF
Project Planning Manual MAD/MAF****-PRxx-EN-P R911295781
MLFSynchronous Linear Motors
Project Planning Manual MLF********-PRxx-EN-P R911293635
ML3Self-Cooled Linear Motors
Project Planning Manual ML3X*******-PRxx-EN-P R911389760
MCLIronless Linear Motors MCL
Project Planning Manual MCL********-PRxx-EN-P R911330592
1) In the documentation typecodes, "xx" is a placeholder for thecurrent edition of the documentation (e.g.: PR01 is the first edi‐tion of a Project Planning Manual)
Tab. 3-1: Documentations – motors
ctrlX DRIVE Drive Controllers, Supply Units 21/43
Overview of documentations
R911392530_Edition 02 Bosch Rexroth AG
4 Instructions for use4.1 Overcurrent protection
Protect the components against overcurrent:● Branch circuit protection has to be provided externally.
For the North American sales region, individual branch circuit protectionon the mains side is mandatory before each device.
● Dimension the branch circuit protection according to the "Branch circuitprotection fuse" data (see Ratings and dimensions)
Lethal electric shock from live parts with morethan 50 V!Risk of burns by hot housing surfaces! Riskof fire!
WARNING
The opening of the branch-circuit protective device may be an indication thata fault current has been interrupted. To reduce the risk of fire or electricshock, current-carrying parts and other components of the controller shouldbe examined and replaced if damaged. If burnout of the current element ofan overload relay occurs, the complete overload relay must be replaced.
4.2 Connection4.2.1 General information
Apart from the indicated connections, it is necessary to wire theBb contact at the control section for signaling the readiness foroperation of the drive controller (see Project Planning Manual"Rexroth IndraDrive Drive Controllers Control Sections").
For proper function of the motor thermal management connect the motorthermal sensor as described in the wiring diagram. Otherwise motor overtem‐perature sensing is not provided by the drive.For Rexroth motors with data memory in the motor encoder, such as MSK,the motor overload protection level is set automatically while connecting themotor to the drive. There is no adjustment necessary. Otherwise refer to theRexroth firmware documentation.
ctrlX DRIVE Drive Controllers, Supply Units 23/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
4.2.2 Overall connection diagram XCS*-W0054…W0070
XD01 MainsXD02 DC busXD03 MotorXD04 Internal/external braking resistorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyFig. 4-1: Overall connection diagram XCS*-W0054…W0070 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
24/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
4.2.3 Overall connection diagram XCS*-W01xx
XD01 MainsXD02 DC busXD03 MotorXD04 Internal/external braking resistorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyFig. 4-2: Overall connection diagram XCS*-W01xx Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
ctrlX DRIVE Drive Controllers, Supply Units 25/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
4.2.4 Overall connection diagram XCS*-W02xx
XD01 MainsXD02 DC busXD03 MotorXD04 Internal/external braking resistorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyFig. 4-3: Overall connection diagram XCS*-W02xx Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
26/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
4.2.5 Overall connection diagram XCD
XD01 MainsXD02 DC busXD04 Internal/external braking resistorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyXZ03 Motor, motor temperature monitoring, motor holding brakeFig. 4-4: Overall connection diagram XCD Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
ctrlX DRIVE Drive Controllers, Supply Units 27/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
4.2.6 Overall connection diagram XMS*-W0006…W0036
XD02 DC busXD10 Control voltageXF21, XF22 CommunicationXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyXZ03 Motor, motor temperature monitoring, motor holding brakeFig. 4-5: Overall connection diagram XMS*-W0006…W0036 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
28/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
4.2.7 Overall connection diagram XMS*-W0054…W0090
XD02 DC busXD03 MotorXD10 Control voltageXF21, XF22 CommunicationXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyFig. 4-6: Overall connection diagram XMS*-W0054…W0090 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
ctrlX DRIVE Drive Controllers, Supply Units 29/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
4.2.8 Overall connection diagram XMS*-W0100…W0280
XD02 DC busXD03 MotorXD10 Control voltageXF21, XF22 CommunicationXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyFig. 4-7: Overall connection diagram XMS*-W0100…W0280 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
30/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
4.2.9 Overall connection diagram XMD*-W0606…W2323
XD02 DC busXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyXZ03 Motor, motor temperature monitoring, motor holding brakeFig. 4-8: Overall connection diagram XMD*-W0606…W2323 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
ctrlX DRIVE Drive Controllers, Supply Units 31/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
4.2.10 Overall connection diagram XMD*-W5454…W7070
XD02 DC busXD03 MotorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyFig. 4-9: Overall connection diagram XMD*-W5454…W7070 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
32/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
4.2.11 Overall connection diagram XMQ*-WQ001
X…A, X…B Connection points of axis module A or BXxxx.1/2.A/B Xxxx.1.A (Axis1: 54 A); Xxxx.2.A (Axis2: 36 A);
Xxxx.1.B (Axis3: 20 A); Xxxx.2.B (Axis4: 10 A)XD02 DC busXD03 MotorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyXZ03 Motor, motor temperature monitoring, motor holding brakeFig. 4-10: Overall connection diagram XMQ*-WQ001 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
ctrlX DRIVE Drive Controllers, Supply Units 33/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
4.2.12 Overall connection diagram XMQ*-WQ002
X…A, X…B, X…C Connection points of axis module A, B or CXxxx.A/C; Xxxx.1/2.B Xxxx.A (Axis1: 100 A); Xxxx.1.B (Axis2: 70 A);
Xxxx.2.B (Axis3: 36 A); Xxxx.C (Axis4: 10 A)XD02 DC busXD03 MotorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG03 Motor temperature monitoring and motor holding brakeXG20 Digital encoderXG21 Multi-encoder (optional)XG31 Digital inputs/outputs; analog inputXG4x Safety technologyXZ03 Motor, motor temperature monitoring, motor holding
brakeFig. 4-11: Overall connection diagram XMQ*-WQ002 Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
34/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
4.2.13 Overall connection diagram XVR
XD01 MainsXD02 DC busXD03 XLI-XVR mainsXD04 External or internal braking resistorXD10 Control voltageXF21, XF22 CommunicationXG02 Ready for operation relay contactXG20 XLI busXG31 Digital inputs/outputs; analog inputXLI Mains connection moduleXVR Supply unitFig. 4-12: Overall connection diagram XVR Symbols: See chapter 4.2.14 "Symbols (connection diagram)" on page 36
ctrlX DRIVE Drive Controllers, Supply Units 35/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
4.2.14 Symbols (connection diagram)
Symbol Description
Pin
Female connector
Male connector (pin at connector; female [device])
Spring terminal (female [connector], pin at device)
Screw terminal (female [connector], pin at device)
Screw connection at device
Electrical connection at device housing (e.g., for cable shield con‐nection)
Tab. 4-1: Symbols (connection diagram)
36/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
4.2.15 Connection points
Symbols used to describe the connection points
Screw terminalblock
Spring terminal Thread Max. connection cross section Strippedlength
Max. tighteningtorque
Tab. 4-2: Symbols
Connection point Device 1)
AWG (mm2) in (mm) lbf in (Nm)
A, B, C, D, E, F, G,H, I, J, K, L
Ring cable lug M5 - 24.8 (2.8)
A Ring cable lug M5 - 44.3 (5)
E Ring cable lug M8 - 70.8 (8)
H, I, J, K Ring cable lug M6 - 44.3 (5)
D 6 (16) 0.5 (12) 13 (1.5)
G 8 (10) 0.6 (15) -
XD01 A , I 4 (35) 0.71 (18) 39.9 (4.5)
D 6 (16) 0.5 (12) 13 (1.5)
E, K 4/0 (120); M10 - 177 (20)
G 8 (10) 0.6 (15) -
H, J 1/0 (50); M6 - 44.3 (5)
XD03 A , F 4 (35) 0.7 (18) 39.9 (4.5)
B, D, F 8 (10) 0.6 (14) 16 (1.8)
L 6 (16) 0.5 (12) 13 (1.5)
E 4/0 (120); M10 - 177 (20)
G 8 (10) 0.6 (14) -
H 1/0 (50); M6 - 44.3 (5)
XZ03 2) B, C, F, G 8 (10) 0.5 (12) -
XG03 B, D, F, L 16 (1.5) 0.4 (10) -
A, E, F, H 12 (2.5) 0.4 (10) -
XZ03 3) B, C, F, G 16 (1.5) 0.4 (10) -
XD04 D, G 8 (10) 0.5 (12) -
A, H, I, J 6 (16) 0.6 (14) 16 (1.8)
E, K 4 (35) 0.71 (18) 39.9 (4.5)
ctrlX DRIVE Drive Controllers, Supply Units 37/43
Instructions for use
R911392530_Edition 02 Bosch Rexroth AG
Connection point Device 1)
AWG (mm2) in (mm) lbf in (Nm)
XD02 A, B, C, D, E, F, G,H, I, J, K, L
- - 24.8 (2.8)
XD10 A, B, C, D, E, F, G,H, I, J, K, L
8 (6) 0.4 (10) -
1) Device:A XCS*-W0100, -0120; XMS*-W0100, -0120B XMQ*-WQ001C XMS*-W0006, -0010, -0016, -0023, -0036; XMD*-W0606,
-1010, -1616, -2323, -3636D XCS*-W0054, -0070; XMS*-W0054, -0070; XMD*-W5454,
-7070E XCS*-W0210, -0250, -0280; XMS*-W0210, -0250, -0280F XMQ*-WQ002G XCD*-W2323H XCS*-W0150, -0180I XVR*-W0048J XVR*-W0072K XVR*-W0100L XMS*-W00902) Motor3) Motor temperature monitoring, motor holding brakeTab. 4-3: Connection points
38/43
Instructions for use
ctrlX DRIVE Drive Controllers, Supply Units
Bosch Rexroth AG R911392530_Edition 02
5 Service and supportOur worldwide service network provides an optimized and efficient support.Our experts offer you advice and assistance should you have any queries.You can contact us 24/7.
Service Germany Our technology-oriented Competence Center in Lohr, Germany, is responsi‐ble for all your service-related queries for electric drive and controls.Contact the Service Hotline and Service Helpdesk under:
Phone: +49 9352 40 5060Fax: +49 9352 18 4941E-mail: [email protected]: http://www.boschrexroth.com
Additional information on service, repair (e.g. delivery addresses) and trainingcan be found on our internet sites.
Service worldwide Outside Germany, please contact your local service office first. For hotlinenumbers, refer to the sales office addresses on the internet.
Preparing information To be able to help you more quickly and efficiently, please have the followinginformation ready:● Detailed description of malfunction and circumstances● Type plate specifications of the affected products, in particular type co‐
des and serial numbers● Your contact data (phone and fax number as well as your e-mail ad‐
dress)
ctrlX DRIVE Drive Controllers, Supply Units 39/43
Service and support
R911392530_Edition 02 Bosch Rexroth AG
IndexAAdditional documentations.................................. 21Ambient conditions................................................ 5
CConditions
Ambient and operating conditions.................... 5Connection
Connection diagram (XCD)............................ 27Connection diagram (XCS)................ 24, 25, 26Connection diagram (XMD)..................... 31, 32Connection diagram (XMQ*-WQ001)............ 33Connection diagram (XMQ*-WQ002)............ 34Connection diagram (XMS)............................ 28Connection diagram (XVR)............................ 35
Connection diagramSymbols......................................................... 36XCD............................................................... 27XCS.................................................... 24, 25, 26XMD......................................................... 31, 32XMQ*-WQ001................................................ 33XMQ*-WQ002................................................ 34XMS............................................................... 28XVR................................................................ 35
Connection points............................................... 37
DData
Ambient conditions........................................... 5Operating conditions........................................ 5
Dimensions........................................................... 5Distances...................................................... 16, 18Documentation
Motors............................................................ 21Overview........................................................ 21Reference documentations............................ 21
HHelpdesk............................................................. 39Hotline................................................................. 39
IInstructions for use.............................................. 23Intended use......................................................... 4
MMotor
Documentation............................................... 21
OOperating conditions............................................. 5Overcurrent protection........................................ 23
PPower consumption.............................................. 5Project Planning Manuals................................... 21
RRatings.................................................................. 5Ratings and dimensions........................................ 5Reference documentations................................. 21RoHS
China RoHS 2................................................ 19
SSafety instructions................................................. 1Service hotline.................................................... 39Support............................................................... 39Symbols
Connection diagram....................................... 36
UUse
Instructions..................................................... 23Intended........................................................... 4
VVoltage load capacity............................................ 5
XXCD
Connection diagram....................................... 27XCS
Connection diagram........................... 24, 25, 26XD01................................................................... 37XD02................................................................... 37XD03................................................................... 37XD04................................................................... 37XD10................................................................... 37XG03................................................................... 37XMD
Connection diagram................................. 31, 32XMQ*-WQ001
Connection diagram....................................... 33XMQ*-WQ002
Connection diagram....................................... 34XMS
Connection diagram....................................... 28XVR
Connection diagram....................................... 35XZ03................................................................... 37
ctrlX DRIVE Drive Controllers, Supply Units 41/43
Index
Bosch Rexroth AGP.O. Box 13 5797803 Lohr a.Main, GermanyBgm.-Dr.-Nebel-Str. 297816 Lohr a.Main, GermanyPhone +49 9352 18 0Fax +49 9352 18 8400www.boschrexroth.com/electrics
*R911392530*R911392530
DOK-XDRV**-X*****UL***-IN02-EN-P