ADVANCED SEISMIC ANALYSIS METHODS AND APPLICATION TO EARTHQUAKE DAMAGED BUILDINGS' STRENGTHENING...
-
Upload
independent -
Category
Documents
-
view
0 -
download
0
Transcript of ADVANCED SEISMIC ANALYSIS METHODS AND APPLICATION TO EARTHQUAKE DAMAGED BUILDINGS' STRENGTHENING...
1 Zheng Ping Wu, Harrison Grierson Consultants Ltd, Christchurch. Email: [email protected]
ADVANCED SEISMIC ANALYSIS METHODS AND APPLICATION TO
EARTHQUAKE DAMAGED BUILDINGS’ STRENGTHENING DESIGN
Zheng Ping Wu1
ABSTRACT: Using advanced modal response spectrum methods, the current practice of the New Zealand standards
and the guidelines/regulations of the national and regional authorities, this paper presents the investigations on the
buildings subjected to seismic damages and proposes respective strengthening methodologies. Two engineering cases
were investigated: one five story office building and one L-shaped two storey retail building. Detailed strength
capacities in terms of New Building Standard (NBS) as well as the overall behavior of the buildings were achieved
based on the detail modal response spectrum analysis. Strengthening was designed successfully based on the latest
engineering standards and regulations. It was found to be imperative to employ advanced modal response spectrum
analysis for all the horizontally and/or vertically irregular buildings. Further researches were recommended: (a) to
refine the formula for seismic shear distribution to roof in New Zealand standard, and; (b) to better understand the
energy dissipation mechanism in the connection details of the concentric braced frames.
KEYWORDS: Modal response spectrum analysis (RSA), concentric braced frame (CBF), New Zealand standards
1. INTRODUCTION
A comprehensive structural assessment for an existing
building is always a complex task, especially for an
earthquake damaged existing tall buildings. They were
constructed decades ago and normally only limited
engineering documents are available. For a structurally
irregular building, it requires the structural engineers even
more to utilize an advanced analysis tool such as
commercially available software ETABS or SAP 2000 to
carry out the full modal response spectrum analysis.
Indeed, the response of any building under the coarse
seismic actions is very complex. It is hard to understand
the overall structural response of the building without
detail computer analysis of the whole structure. It is
required to “collect” sufficient modal responses of the
structure before an almost “true” and “full” response of
the building could be achieved.
Using the advanced modal response spectrum analysis
methods, the current practice of the New Zealand
Standards and the guidelines/regulations of the national
and regional authorities, the purpose of this paper is
threefold:
• To study the structural layout of the building and its
necessity using advanced analysis tool when
carrying out structural seismic response assessment.
• To assess the building’s structural response under
the seismic actions and propose respective repair and
strengthening methodologies. This is to bring the
earthquake damaged building back to its intended
service while being able to sustain the code required
seismic actions.
• To investigate the earthquake resistance capacity of
the individual element and to carry out its
strengthening design if needed.
Engineering projects used are the comprehensive
structural assessments and strengthening methodologies
for two buildings in Christchurch damaged in the
September 2010 and February 2011 earthquakes and
aftershocks. One is a five storey reinforced concrete
office building and another is an L-shaped two storey
reinforced concrete commercial retail building. This paper
also outlines the criteria used in the modal analysis, and;
the guidelines/ regulations in relations to the seismic
modal analysis and the strengthening design.
For both engineering projects, it was aimed to establish:
a) the current condition of the building structures,
including its seismic resistance strength of the individual
structural elements and the building as whole, and; b) the
repair and strengthening methodologies. Based on the site
investigation and the detail modal analysis, the
comprehensive assessment for the building’s strength
capacity was achieved, from which repair and
strengthening methodologies were designed successfully.
Different strengthening concepts were adopted for these
two buildings. While individual column strengthening
was chosen for the five storey building and the upper
level of the two storey L-shaped building, the concentric
bracing frames were adopted for the ground floor of the
two storey building. Discussions were given to the
seismic load distribution to the roof level and the plastic
energy dissipation design of concentric braced frame,
whereby further researches were recommended.
2. STRUCTURAL SEISMIC ANALYSIS
In this paper, modal response spectrum analysis [1]
(RSA) was used. It is an approximate method of dynamic
analysis. For a single degree freedom system (SDOF)
with the same damping ratio and different natural
frequencies, it gives the maximum (peak) response
(acceleration, velocity or displacement) when responding
to a specific seismic excitation. For a structure with n-
degree of freedom, it is transformed to n single-degree
systems, whereby response spectra principles could be
applied to the systems with multiple degrees of freedom.
In general, for a multi-degree freedom (MDOF) system
subjected to ground seismic action, its equation of motion
is expressed as
[ ]{ } [ ]{ } [ ]{ } [ ]{ }g
uBMuKuCuM ɺɺɺɺɺ −=++ (1)
Where [ ]M is the mass matrix. By neglecting the mass
coupling effect, it is a diagonal or uncoupled mass matrix
in the form of tributary lump masses to the corresponding
displacement degree of freedoms. [ ]K is the stiffness
matrix. [ ]C is the damping matrix accounting for all the
energy dissipating mechanism in the structure. { }B is the
displacement transformation vector defining the degrees
of freedoms that the seismic action applies. In general
term, the displacement { }u , velocities { }uɺ acceleration
{ }uɺɺ of the structure and the ground motion g
uɺɺ are all
function of time. In explicit matrix form, the mass,
damping and stiffness are expressed as the follows.
[ ]
=
nnm
m
m
M
⋯
⋮⋮⋮⋮
⋯
⋯
00
00
00
22
11
(2)
[ ]
=
nnnn
n
n
ccc
ccc
ccc
C
⋯
⋮⋮⋮⋮
⋯
⋯
21
22221
11211
(3)
[ ]
=
nnnn
n
n
kkk
kkk
kkk
K
⋯
⋮⋮⋮⋮
⋯
⋯
21
22221
11211
(4)
For a multi-degree of freedom (MDOF) system, it is often
accurate enough for a general structural engineering
application not to carry out a response history analysis.
These structures are often excited by a single component
of the ground motion at one time (e.g. acceleration in
either x-x or y-y direction), where multiple support
excitation is not considered. In other words, the
simultaneous action of other two components is not
considered. Also, all the supports of the building structure
are assumed to be excited simultaneously by the same
excitation. Based on these assumptions, the response
spectrum analysis procedure calculates the peak response
values of forces and deformations over the duration of the
earthquake-induced excitation directly from the
earthquake response spectrum without undertaking
response history analysis of the structure. By doing so, the
dynamic analysis is reduced to a series of static analyses.
For each mode, the static analysis for a structure subjected
to forces, fn, produces the respective modal response, n
φ .
It is then multiplied by the spectral ordinate, n
A , to
obtained the peak modal response rno, i.e.
{ }nnno
Ar φ= (5)
In order to find out the modal response n
φ of the
structure, [ ]C and g
uɺɺ are set to be zero in Equation (1), it
then becomes
[ ]{ } [ ]{ } 0=+ uKuM ɺɺ (6) It is further rearranged to
[ ] [ ] { } 02 =
n
MK φω (7)
Where { }
nφ is the deflected shape matrix, i.e.
dimensionless natural mode shapes. Solution to this
equation is obtained using its corresponding natural
frequencies i
ω by setting
[ ] [ ] 02 =
MK ω (8)
Having achieved the mode shapes { }n
φ , the maximum
(peak) response can be established using the method
shown in Equation (5) or graphically shown in Figure 1
below.
Figure 1: Resultant response and modal components Mode shapes of low-order mathematical expression tend
to provide the greatest contribution to structural response.
As orders increase, mode shapes contribute less, and are
predicted less reliably. It is reasonable to truncate analysis
when the number of mode shapes is sufficient.
In the above procedure, one fact is worthwhile to be noted
that, although the response spectrum analysis solves a
series of static analyses, it is still a dynamic analysis
procedure due to that it adopts the vibration properties in
its procedure development. These properties are natural
frequencies, natural modes and damping ratio. These are
the dynamic related nature of the structure. It also uses the
dynamic characteristics of the ground motion through its
response (design) spectrum. One of the main advantages
of RSA is that these dynamic features have been done in
developing earthquake response spectrum, whereby the
earthquake excitation has been characterized by the
smooth design spectrum.
3. ANALYSIS CRITERIA FROM THE
CODES AND STANDARDS
In order to ensure the reliability of the structural seismic
analysis, especially the commonly used modal response
spectrum methods, the structural design codes and
standards of every country/region provide a full set of
criteria that governs and verifies the results of the
computer analysis. In New Zealand codes, these are
mainly given in AS/NZS 1770.5: 2004 [2]. They are a)
the mass participation ratio; b) the base shear ratio, and;
c) methods of the modal combination. In addition, NZS
3101 [4] requires: d) reduction factor for the reinforced
concrete structural members: beams, columns, walls and
floor slabs.
3.1 MASS PARTICIPATION RATIO
For the modal response spectrum analysis, it is required
by AS/NZS 1170.5:2004, that sufficient number of modes
shall be included to ensure the minimum 90% of the total
mass participated in the dynamic calculation. It is
particularly important for each of the structure’s
orthogonal principal directions.
3.2 BASE SHEAR RATIO
Theoretically, the design spectrum used in the modal
response analysis consists of pairs of values: period
versus acceleration or period versus displacement. These
acceleration or displacement values obtained from the
geological data for the particular site have often been
normalized. It means that the values of acceleration or
displacement have been divided by a number (i.e.
normalization factor) which represents some reference
value. One of the commonly used normalization factors is
'g', the gravity acceleration. In order to reinstate the actual
seismic magnitude, a scale factor is required in the
computer analysis. It can be initially calculated as the
follows for the units of kN-m.
µk
SfactorScale
p×= 81.9 (6)
Where p
S is the structural performance factor. In
accordance with AS/NZS1770.5:2004, µk is given as the
follows. For soil classes A, B, C and D
µk µ= For sT 7.0
1≥ (7a)
1
7.0
)1(1 +
−=
Tµ For sTs 7.04.0
1<≤ (7b)
For soil class E
µk µ= For sTs 5.10.1
1<≤ (7c)
1
7.0
)1(1 +
−=
Tµ
For sTs 0.14.01
<≤
and sT 5.11
≥ (7d)
If kip-in units are used in the computer analysis, 9.81
shall be replaced by 386.4 (in/sec2) in Equation (6).
After initial analysis, this initial calculated scale factor
should be reviewed based on the resulted base shear due
to all modes (i.e. the sufficient number of modes that
achieves 90% mass participation). The scale factor shall
then be adjusted to a value such that the dynamic base
shear reaches more than 80% of the base shear calculated
using static equivalent method.
3.3 MODAL COMBINATION
To achieve the maximum (peak) response of the structure
under the ground seismic actions, various modal
combination methods are available, namely: i) square root
of the sum of the square (SRSS); ii) root mean square
method; iii) complete quadratic combination (CQC)
method, and; iv) absolute sum (ABSSUM) method.
Research had shown that ABSSUM gives always an
overestimate the response. Commonly adopted ones are
hence CQC and SRSS methods.
In AS/NZS 1170.5:2004, it is recommended that: a) When
the modal responses for different modes are not coupled,
SRSS shall be used; and b) When the modal responses for
different modes are coupled, CQC combination method
shall be used. In practice, due to the complex of the
structure layout, CQC shall be used in most situations.
In engineering application, the seismic actions in two or
more orthogonal horizontal directions are often analyzed
and combined for design. To combine the effects of these
orthogonal directions, either SRSS combination method
or by using the load combinations could be used.
3.4 MEMBER REDUCTION FACTOR
For the concrete structural members, cracking shall be
taken into account in the seismic response analysis to
obtain the reliable computer results. This can be
facilitated by using the effective section properties for the
respective forces, for which the guidelines could be found
in Section 6 of NZS3101: Part2:2006.
For the applications presented in this paper, the following
reduction factors were adopted: For wall: a) 1.0 (i.e. no
reduction) for the horizontal axial forces, shear forces of
both in-plane and out-of plane; b) 0.33 for vertical axial
forces; and c) 0.25 for the in-plane and out-of-plane
moment forces. Reduction factor of 0.8 and 0.4 were used
for the concrete columns and beams, respectively.
4. EARTHQUAKE DAMAGED
BUILGINGS’ ASSESSMENT
Two cases were analyzed using the modal response
spectrum method based engineering software ETABS:
one two storey L-shaped commercial retail building and
one 5 storey office building. Both buildings were
damaged in September 2010 and February 2011
earthquakes and aftershocks. The purpose was to carry
out structural assessment and propose strengthening
methodologies to bring the buildings back to service
while meeting current statutory requirements of the
structural strength capacity, i.e. minimum 67% strength of
New Building Standard (NBS).
For the two storey L-shape building, its L-shape layout
produces the horizontal torsion deformations under
seismic actions. On the first floor level, there are
terminations of the masonry walls for the stair wells at the
both ends of the L-shape and the terminations of the
centre core walls. All these together produce both
horizontal and vertical structural irregularity of the
building.
For the five storey office building, its core walls were
arranged on one side of the building, which makes the
structure subjecting to large stiffness eccentricity in
horizontal plan, hence producing torsion deformation
under seismic actions. In vertical elevation, the irregular
window openings and the reinforced concrete wall filled
external wall have all accumulated up the vertical
irregularity.
Hence, in accordance with Section C4.5 of NZS1170.5
Supp 1:2004, both buildings shall be analyzed using a
rigorous method for its seismic response.
For both cases, accidental eccentricity considered was
± 0.1 times the plan dimension of the structure
perpendicular to the action of the seismic acceleration.
Based on AS/NZS1170.0:2002 [3], following load
combinations were analyzed for the earthquake effects to
the building structures.
1) G +ΨE Q + Ex-direction + 0.3 Ey-direction
2) G +ΨE Q + 0.3 Ex-direction + Ey-direction Where ΨE is the earthquake combination factor for the
live loads.
4.1 APPLICATION I: FIVE STOREY OFFICE
BUILDING
As shown in Figure 2, the five storey building,
approximately 20 m x 30 m in plan, was constructed in
1952 as an extension from its two storey existing factory
building next. It was the main building of the
entertainment complex called “Sol Square” in the centre
Figure 2: Five storey reinforced concrete framed office
building (Typical floor plan layout) of Christchurch before the major earthquakes. It had a
reinforced concrete beam and column frame system to
resist vertical and horizontal loads with reinforced
concrete floor slabs throughout all floors providing
diaphragm actions. Core-wells were arranged on one side
of the building at the front and rear for the access stairs
and the lifts. External wall were of brick infill to the
frames, except the rear walls were of reinforced concrete
wall on 3rd
and 4th
floor. The front wall was of brick
veneer wall supported on the frame beams. The
foundations were separate footings for the internal
columns and strip footings on the perimeters. The internal
footings were tied in both directions by the gird beams in
both directions. The building had gone through the
alterations on the ground floor and the top floor in around
1995 and 2000.
4.1.1 Summary of the Earthquake Damages Site inspections were carried out in July and August 2013
to identify the damage extents to the building. It was
found that the damage was of substantially structural to
the reinforced concrete walls and the columns throughout.
Typical damage cracks are shown in Figure 3.
a) Horizontal cracks in column at the beam’s soffit
b) Cracks in reinforced concrete stair well wall Figure 3: Typical earthquake damage
4.1.2 Structural Assessment and Strengthening
Design Based on the existing drawings and the site inspection,
ETABS models was set up to analysis the structural
response under the seismic actions, as shown in Figure 4.
To achieve 95% mass participation ratio, 20 modes were
included in the calculation. The first five modes are
shown in Figure 5 to Figure 9. It was seen that the
building undergoes substantial twisting in the primary
responses. The transverse direction of the core wall (i.e.
x-direction) subjects to large deformation as a result of
the twisting. It was also shown that the external reinforced
concrete parapet wall on each floor level was weak in its
out-of plane direction during response to the earthquake.
Based on the ETABS results, the beams and columns
were all checked. The results were expressed as the
strength capacity over the force demands in terms of
percentage of the New Building Standard (%NBS). Figure
10 shows the results for the frame at the front wall. It was
Figure 4: ETABS analysis model
Figure 5: Mode 1
Figure 6: Mode 2
Figure 7: Mode 3
Figure 8: Mode 4
Figure 9: Mode 5 found that the building was weak in resisting lateral
seismic loads. This is quite common for the old buildings
in Christchurch. Historically, the old buildings were
designed based on much smaller seismic resistance
requirements than it is in the current practice. The
engineer at old time found that the building design was
actually governed by the vertical gravity load other than
the seismic lateral loads.
To strengthen the building, two schemes were proposed
for the upper structure: 1) to strengthen all weak columns;
and 2) to strengthen the selected columns in combination
of adding several shear walls. The first scheme maintains
the current seismic resistant frame system; whilst in the
second scheme, the shear walls would be added and
become more effective in reducing the twisting of the
building. Figure 11 shows the typical strengthening
design for the columns. Both schemes require the
foundation strengthening.
For the foundation strengthening, a raft foundation was
proposed. It aimed to reduce the bearing pressure as the
geotechnical investigation found that the bearing capacity
of the ground was actually much lower than the required
capacity, especially for the service limit state. By using
the raft foundation, it would also improve the building
behavior during seismic induced liquefaction events by
bridging over the liquefied zone in the instance of strong
earthquake.
Figure 10: Strength %NBS for the front frame
Figure 11: Front and rear frame column strengthening
These proposed strengthening designs were carried out
successfully and presented to the client in time. However,
due the significant cost of the strengthening, the decision
was made to demolish the building for the redevelopment
by its new owner.
4.2 APPLICATION II: L-SHAPED TWO STOREY
RETAIL COMMERCIAL BUILDING
As shown in Figure 12, the L-shaped two storey
commercial retail building located in the north of
Christchurch was constructed in 1987 with the ground
floor being un-reinforced concrete slab-on-grade. The
first floor was constructed of 75 mm reinforced concrete
topping on 75 mm thick precast planks spanned on
reinforced concrete beams. The north and west ends of the
building have precast concrete and reinforced masonry
concrete walls surrounding stair wells for accessing to the
upper floor. The central lift core located on one side of the
“L” shape corner was constructed using reinforced
concrete masonry. The lateral load resisting system for
the lower floor consists of the concrete shear walls
located in the middle and two building ends, whilst the
upper floor’s lateral resistance is dependent on the
cantilever capacity of the individual columns due to the
fact that there was no roof bracing constructed. The
building is founded on 150mm square by 9.5 m long
precast reinforced concrete driven piles.
Figure 12: L-shaped two storey retail commercial
building (Ground floor plan layout)
a) Cracks in reinforced concrete column at first floor
beams’ soffit
b) Vertical cracks in ground masonry wall Figure 13: Typical earthquake damage
4.2.1 Summary of the Earthquake Damages Series of site inspections were carried out since the major
earthquake in September 2010 and the interim detail
engineering evaluation (DEE) reports were produced for
the client to monitor the status of the building and to
assess the building’s suitability for its service continuity.
The latest site inspections were conducted in May and
June 2013. Structural damages are: a) substantial
subsidence of the un-reinforced concrete ground slab; b)
horizontal cracks in the columns at the soffit of the first
floor beams, and; c) cracks in the ground masonry walls.
Figure 13 shows the typical damages.
4.2.2 Structural Assessment and Strengthening
Design Based on the existing drawings obtained from the
Christchurch City Council and the site inspection, ETABS
model as shown in Figure 14 was set up to analysis the
structural response under the seismic actions so as to
establish the strength status of the building.
Figure 14: ETABS analysis model At the beginning of computer analysis, 15 modes were
included in the calculation. However, this could only
achieve around 75% mass participation. After few trials,
90 modes were included in calculation. It achieved more
than 97% mass participation for the lateral translational
actions and more than 95% mass participation for the
rotational action in all x-x, y-y and z-z direction. To
include so many modes in achieving the required mass
participation shows that the structure’s seismic response
was mathematically highly loosely ‘scattered”, or
structurally extremely “irregular”. It proves again that the
modal response spectrum analysis was imperative in such
Figure 15: Mode 1
Figure 16: Mode 2
Figure 17: Mode 3
Figure 18: Mode 4
Figure 19: Mode 5
Figure 20: Mode 6
structural layout. Figure 15 to Figure 20 show the first six
modes. It was seen that the primary modes exhibited
substantial twisting and “open-up/close-down” of the “L”
shape.
With regards to the base shear and the share distribution
to the storey levels, Table 1 and Table 2 show the seismic
load distribution to the roof and the first floor calculated
based on the ETABS calculation and the static equivalent
methods.
Table 1: Seismic Loads Based on ETABS (kN)
DL SDL LL Mass: DL
+ SDL +
0.3 LL
Seismic
force for
ETABS
Total
seismic
force
Roof 831.1 274.8 0.0 1105.9 694.4 6315.5
First
Storey
7258.9 955.8 2723.9 9031.8 5621.2
Table 2: Seismic Loads Distribution: static equivalent (kN)
Height
(m)
Mass x
Height
0.08 x
Base
shear
0.92 *
Contribution
ratio
Storey
seismic
force
Based on
Cd(T1) x
mass
Roof 2.55 2820.0 505.2 482.2 987.4 688.9
First
Storey
3.45 31159.9 5328.1 5328.1 5626.6
Based on the ETABS calculation, the primary period T1 =
0.536 second and the total mass ( G + ΨE Q ) for seismic
action is 10137.7 kN. The resulted Cd (T1) = 0.696, and
the base shear = 7055.9 kN, respectively. The base shear
from ETABES is 6315.6 kN. Hence the ratio of ETABS
calculated base shear to that of the static equivalent
method was 89.5%. It is greater than the code required
80%, hence satisfactory.
With regards to the seismic shear distributed to the roof, it
was seen that the static calculation was 43.3% greater
than that of the ETABS calculation. However, the ETABS
result agrees very well with the results of the roof mass
multiplies )(1
TCd
.
Based on the ETABS results, the strength checks were
carried out. It is found that the existing columns had
approximately 60% of the current New Zealand Standard
required strength, i.e. 60% New Building Standard,
(NBS). It would explain very well why the upper columns
and walls did not crack during the two major Christchurch
earthquakes in 2010 and 2011. Based on the static
equivalent calculation, the strength would be around
40%NBS. If that were the case, the upper columns should
have been failed. There should be at least some hairline
cracks on the surface of the upper columns, which was
not the case based on the detailed series of site
inspections. To strengthen the upper columns and wall to
100%NBS, box jacketing to the half height of the upper
columns and steel member (PFC) strengthening to the full
height of the upper wall were adopted.
Based on the detailed site inspections and comprehensive
structural analyses, concentric braced frames (CBF) on
the ground floor were selected together with the ground
tie beams system.
Figure 21 shows the strengthening plan layout, where the
CBFs were designed to enhance the lateral seismic load
resistance from the upper level to the ground. The tie
beams were designed as the collectors to ensure the
diaphragm actions of the first floor being transferred to
the CBFs. They were to be fixed to the transverse
reinforced concrete frame beams and the first floor slabs.
These collector beams also worked as perimeter ties of
the building.
Figure 22 shows the typical layout of the CBFs. The
connection details to the base were given in Figure 23,
where clear space of 40 mm (i.e. two times of the
connection plate thickness) was given to facilitate the
plastic deformation of the connection during seismic
events.
Figure 21: Strengthening layout plan Based on the geotechnical investigation, the site is
subjected to liquefaction in the layers from 1.8 m to 2.6 m
and 7.0 m to 8.2 m. Both layers are well within the depth
of the piles. It was hence imperative to ensure the
robustness of the critical columns in the strong earthquake
events. As such, ground tie beams were designed to
bridge these critical columns to the adjacent pile
foundations. Figure 24 shows the details of the ground
beams at the location of these critical columns, which in
this case was defined as the columns located close to the
location of the CBFs.
Figure 22: Conccentric bracing frame (CBF)
Figure 23: Strengthening layout plan
Figure 24: Ground tie beam details considering
liquefaction
5. DISCUSSION AND FURTHER
RESEARCH RECOMMENDATION
5.1 VERTICAL DISTRIBUTION OF THE BASE
SHEAR
The total base shear is distributed to each storey in
according to the contribution of the storey mass
production with its height from the base. For a building
with the uniform floor mass and uniform storey heights,
the distribution shape is an inverted triangle. Furthermore,
AS/NZS code for seismic action recognizes that the first
mode distribution fails to account for the effect of the
higher modes. It tends to increase the shear in the upper
storeys. It defines the shear distribution as given in
Equation below.
+= ∑
=
n
iiiiiti
hWhWVFF1
)(/92.0 (8)
Where VF
t08.0= at the top level and zero elsewhere.
V is the total base shear. i
W and i
h are the storey mass
and its height from the base.
Similar consideration has been given in the Uniform
Building Code (UBC) [5] and in the National Building
Code of Canada (NBCC) [6, 7].
In addition, NBCC and UBC recognize the influence of
the building’s primary period, which reflects the overall
stiffness of the building structure. The distribution of
shear is given as
−+= ∑
=
n
iiiiitti
hWhWFVFF1
)(/)( (9)
Where t
F is defined as follows.
0=t
F 7.01
≤T (10a)
VTFt 1
07.0= 6.37.01
<< T (10b)
VFt
25.0= 6.31
≥T (10c)
It is seen that, in NBCC and UBC, extra distribution to
the roof level increases with the increases of the primary
period or the decrease of the overall building stiffness.
Furthermore, it is worthwhile to note that UBC has been
replaced by the new International Building Code (IBC).
Its Section 1613 uses the earthquake forces calculation of
ASCE 7 [8]. It defines the vertical distribution of the base
shear as below.
VW
WF
i
i
i
∑= (11)
This distribution refers to the effective mass only.
By comparing these four codes, it is found that the static
equivalent method formula given in NZS1170.5:2004
gives the greatest forces for the lower period building and
the lowest force for the higher period building. In the
second case study of this paper, it shows the
overestimation was substantially around 45%. As this
formula is a primary base for the daily seismic
engineering design. It would be of greatly worthwhile to
investigate further on this issue to avoid both under
estimate and over estimate of the base shear distribution
to the roof level.
5.2 CONCENTRIC BRACED FRAMES
In order to resist the seismic lateral forces, concentrically
braced frames (CBFs) [9, 10] or eccentrically braced
frames (EBFs) are the commonly used. Historically EBFs
have been developed to accommodate the architectural
requirements for openings, where its bracing members are
required to be offsite from the column or avoid the
intersecting with the floor beams. In design, both frames
need the appropriate selection of its local (e.g. plate/wall
thickness) and global (i.e. member itself) slenderness of
the bracing members such that adequate post-buckling
inelastic deformation could be facilitated. Apart from this,
the difference lies in their connection details. Figure 25
and Figure 26 are the different connection configurations
for EBFs and CBFs. While the EBFs use the “link
element”, the CBFs use the linear or elliptical clearance to
establish a plastic hinge zone to dissipate the energy when
subject to seismic actions.
(a) EBF’s connection I (b) EBF’s connection II Figure 25: Different connection configurations of EBFs
(a) CBF’s connection I (b) CBF’s connection II
(c) CBF’s connection III Figure 26: Different connection configurations of CBFs From these connections layout, it is found that the
connections for CBFs are simplest and most cost
effective. It hence becomes a practical and economical
structural solution for many applications. In HERA
Report R4-76, Figure 26 (a) is recommended as the
connection detail for the CBFs. However, if the complete
understanding could be established for the connection
shown in Figure 26 (b), it would made the CBFs much
more preferred seismic resistant bracing frame.
6. CONCLUSION AND REMARKS
Using advanced modal response spectrum analysis, the
current practice of the New Zealand standards and the
guidelines/regulations of the national and regional
authorities, this paper presents the investigations on the
structural response subject to the seismic actions and
proposes respective repair and strengthening
methodologies. Two engineering cases were investigated:
one five story reinforced concrete office building and one
L-shaped two storey reinforced concrete commercial
retail building. Detailed member capacities in terms of
New Building Standard (NBS) as well as the overall
behavior of the buildings were achieved based on the
detail modal response spectrum analysis results.
Strengthening of the building’s overall capacity as well as
the individual member were designed successfully based
on the latest engineering standards, guidelines and
regulations. It was found to be imperative to employ
modal response spectrum analysis for all the buildings
with vertical and/or horizontal irregularities so as to
establish its reliable structural response under seismic
actions. This is true even for the two storey irregular
buildings. In addition, discussion was given to the seismic
shear distribution to the roof level and the plastic energy
dissipation design of the concentric bracing frame
connections, from which recommendations for further
research were given.
REFERENCE
[1] Chopra A.K.: Dynamics of Structures –theory and
applications to Earthquake Engineering, 3rd
edition,
Person Prentice Hall, New Jersey, 2007.
[2] AS/NZS 1170.5:2004, Structural Actions Part 5:
Earthquake Actions-New Zealand, the Council of
Standards New Zealand.
[3] AS/NZS 1170.0:2002, Structural Actions Part 0:
General Principles, the Council of Standards
Australia and the Council of Standards New
Zealand.
[4] NZS 3101: Part 1 2006: Concrete Structures
Standard, Part 1 –the Design of Concrete Structures,
the Standards Council, New Zealand.
[5] UBC 1997: Uniform Building Code, International
Conference of Building Officials, California, USA.
[6] NBCC. 1995: National Building Code of Canada,
Institute of Research in Construction, National
Research Council of Canada, Ottawa, Canada.
[7] Humar J.M. and Mahgoub M.A. 2003:
Determination of Seismic Design Forces by
Equivalent Static Load Method, Can. J. Civ. Eng.
Vol.30, pp.287-307.
[8] ASCE/SEI 7-10: Minimum Design Loads for
Buildings and Other Structures, American Society of
Civil Engineers/Structural Engineering Institute,
Virginia, USA, 2010.
[9] HERA Report R4-76: Seismic Design Procedures
for Steel Structures, New Zealand Heavy
Engineering Research Association, Manukau City,
New Zealand.
[10] Sabelli R., Roeder C.W. and Hajjar J.F.: Seismic
Design of Steel Special Concentrically Braced
Frame Systems –a guide for practicing engineers,
NEHRP Seismic Design Technical Brief No.8,
National Institute of Standards and Technology,
(NIST) GCR 13-917-24, US. Department of
Commerce.