Elementary Students' Understanding of Geometrical ... - ERIC
A geometrical approach for network reconfiguration based loss minimization in distribution systems
-
Upload
independent -
Category
Documents
-
view
2 -
download
0
Transcript of A geometrical approach for network reconfiguration based loss minimization in distribution systems
A geometrical approach for network recon®guration based lossminimization in distribution systems
M.A. Kashem*, V. Ganapathy, G.B. Jasmon
Multimedia University, 63100 Cyberjaya, Selangor, Malaysia
Received 10 May 1999; revised 4 February 2000; accepted 29 May 2000
Abstract
Network recon®guration is one of the feasible methods for reducing the distribution network loss in which the power ¯ow in the
distribution network is altered by opening or closing the appropriate switches on the feeders. A geometrical approach for loss minimization
is presented in this paper. In this method, each loop in a network is represented as a circle, which is derived from the relationship between the
change of loss due to the branch-exchange and the power-¯ows in the branches. If there is no change of loss in the system, then all the circles
touch each other at the (0,0) coordinate and the circles with no loss-change are called zero loss-change circles. The maximum loss-reduction
loop in the network is identi®ed by comparing the radii of all the zero loss-change circles. The corresponding loop of the largest zero loss-
change circle gives the maximum loss reduction in the network. Then the possible branch-exchanges in the maximum loss-reduction loop are
investigated by comparing the size of the circle for every branch-exchange. If the power losses are reduced due to a branch exchange, the size
of the circle diminishes and hence the smallest circle gives the maximum loss-reduction and the corresponding branch-exchange is
considered to be the best candidate for maximum loss-reduction. The performance of the proposed technique is tested on a 69-bus
distribution system, and test results show that the method is found to reduce the computational effort and time considerably by reducing
the numerous load-¯ow studies as compared to the method of Baran and Wu [IEEE Trans. Power Delivery, 4(2) (1989) 1401). q 2001
Elsevier Science Ltd. All rights reserved.
Keywords: Distribution networks; Loss-reduction; Geometry; Network recon®guration
1. Introduction
The increase in power demand and high load density in
the urban areas makes the operation of distribution systems
complicated. To meet the load demand, the system is
required to expand by increasing the substation capacity
and the number of feeders. However, this may not be easily
achieved for many utilities due to various constraints.
Therefore, to provide more capacity margin for the substa-
tion to meet load demand, system loss minimization tech-
niques are employed.
With the advent of fast computing systems, the advanced
control of electrical power systems has become a viable one.
Distribution systems are normally con®gured radially for
effective coordination of their protective systems. Most
distribution networks use sectionalizing-switches that are
normally closed, and tie-switches that are normally opened.
From time to time, modifying the radial structure of the
feeders by changing the on/off status of the sectionalizing
and tie switches to transfer loads from one feeder to another,
may signi®cantly improve the operating conditions of the
overall system. Feeders in a distribution system normally
have a mixture of industrial, commercial, residential and
lighting loads. The peak load on the substation transformers
and feeders occur at different times of the day. Conse-
quently, the distribution system becomes heavily loaded at
certain times of the day and lightly loaded at other times.
Reduction in power losses is obtained by transferring loads
from the heavily loaded feeders to lightly loaded feeders by
recon®guring the network so that the radial structure of the
distribution feeders can be modi®ed from time to time. This
is done in order to reschedule the loads more ef®ciently for
minimizing the losses in the system. Recon®guration also
allows smoothing out the peak demands, improving the
voltage pro®le in the feeders and increasing the network
reliability. A number of researches have been done on the
recon®guration of the network by closing/opening the tie
and sectionalizing switches, respectively, to minimize
losses in a distribution system.
A branch exchange type heuristic algorithm has been
suggested by Civanlar et al. [1], where, a simple formula
Electrical Power and Energy Systems 23 (2001) 295±304
0142-0615/01/$ - see front matter q 2001 Elsevier Science Ltd. All rights reserved.
PII: S0142-0615(00)00044-2
www.elsevier.com/locate/ijepes
* Corresponding author. Tel.: 1603-8312-5434; fax: 1603-8318-3029.
E-mail address: [email protected] (M.A. Kashem).
has been developed for determination of change in power
loss due to a branch exchange. A different method has been
proposed by Baran and Wu [2] to identify the branches to be
exchanged using heuristic approach to minimize the search
for selecting the switching options. Merlin and Back [3]
have used the branch and bound type optimization technique
to ®nd the minimum loss con®guration. Following the
method of Ref. [3], Shirmohammdi and Hong [4] have
developed a heuristic algorithm. In their method, the solu-
tion is obtained by ®rst closing all the switches, which are
then opened one after another so as to establish the optimum
¯ow pattern in the network. Goswami and Basu [5] also
have proposed a heuristic algorithm for feeder recon®gura-
tion by solving the KVL and KCL equations for the network
with line impedances replaced by their corresponding resis-
tances only. Also, instead of closing all the switches to form
a meshed network and opening the switches one after
another, the authors of Ref. [5] adapted the method of clos-
ing one switch at a time and back to the radial con®guration
by opening the same, or a different switch of the loop,
depending upon the result of the optimal ¯ow pattern
through the switches of the same loop. Broadwater et al.
[6] have applied the Civanlar's method [1] and Huddle-
ston's quadratic loss function and multiple switching pair
operation method [7] to solve the minimum loss recon®-
guration problem. Peponis et al. [8] have used the switch-
exchange and sequential switch opening methods for
recon®guration of the network for loss reduction. The meth-
ods proposed by Rubin Taleski et al. [9] and Kashem et al.
[10] are based on branch-exchange technique for recon®-
guration to minimize distribution losses. Methods in Refs.
[11,12] have been suggested to implement on-line control
strategies for power system planing and operations based on
continuous network recon®guration for loss minimization.
In this paper, a geometrical method for the network
recon®guration based loss minimization problem is devel-
oped and presented. The ®rst stage of the method determines
the maximum loss-reduction loop by comparing the size of
the circle for every loop. In a distribution system, a loop is
associated by a tie-line and hence there are several loops in
the system. To obtain the maximum loss-reduction loop, the
size of the modi®ed zero loss-change circles are compared,
and the loop with the largest circle is identi®ed for maximum
loss-reduction. The second stage determines the switching-
operation to be executed in that loop to reach a minimum loss
network con®guration by comparing the size of the loop
circle for each branch-exchange. The smallest circle is iden-
ti®ed for the best solution, as the size of the loop circle is
reduced when the losses are minimized. By utilizing this
proposed method, an optimal or near optimal con®guration
for loss reduction can be obtained with reduced computa-
tional effort because it does not have to check the branches
in all the loops to obtain maximum loss-reduction as used in
Ref. [2]. The proposed geometrical method will be a useful
tool for distribution engineers to quickly solve the problem in
network recon®guration for loss minimization.
2. Formulation of the loss reduction problem
Feeder recon®guration is performed by changing the
open/close status of the sectionalizing and tie switches.
Distribution systems are normally con®gured radially. The
system is recon®gured for many purposes. In system recon-
®guration, a whole feeder or part of a feeder is transferred to
another feeder by closing a tie switch connecting the two
while an appropriate sectionalizing switch must be opened
to preserve the radial structure. The loss minimization
problem addressed in this paper determines the open/close
states of the tie and sectionalizing switches in order to achieve
a maximum reduction in power losses. The change in losses
can be easily estimated from the two power ¯ow solutions,
before and after feeder recon®guration. However, the number
of switching options even for a moderate size distribution
system is so large that a large number of load ¯ow solutions
have to be executed for all the possible options. It becomes not
only inef®cient from a computational point of view, but also
unrealistic as a feeder recon®guration strategy. Therefore, it is
desirable to propose a method that can provide a criterion that
may be used to eliminate undesirable switching options.
3. Proposed geometrical method for power lossreduction
A radial distribution network can be represented by
several loops. The number of loops is equal to the number
of tie-lines because one tie-line can only make one loop
when it is connected. The proposed method will estimate
the loss reduction of a network from a switching operation
by considering several loops in a distribution system. A loop
in a radial network is created with reference to a tie-line t as
shown in Fig. 1. There is a voltage difference across the
normally open tie switch in the tie-line. The higher voltage
drop side of the tie switch is called the lower voltage side
(lv-side) and the lower voltage drop side of the tie switch is
called higher voltage side (hv-side) of the loop. The lower
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304296
Fig. 1. A typical loop
voltage and higher voltage-sides in the ®gure are denoted by
l and h, respectively.
Consider the branch exchange between branches t and m
where t is the open branch and m is the closed branch in Fig.
1. The loop is divided into two parts by the open branch t in
which the ®rst part consisting the branches in the loop that
extends between nodes 0 to l and the second part consisting
the branches that extends between nodes 0 to h. The loss
reduction formula due to this branch exchange as given in
Ref. [2] is rewritten as follows:
DLPtm � 2Pm
XrlPl 2
XrhPh
� �1 2Qm
XrlQl 2
XrhQh
� �2 P2
m 1 Q2m
� �rloop
�1�where DLPtm is the incremental power loss reduction due to
branch exchange t±m, Pm the real power ¯ow in branch m
(to be removed), Qm the reactive power ¯ow in branch m (to
be removed), rlPl the product of rP on the lv-side of the loop,
rhPh the product of rP on the hv-side of the loop and rloop the
total branch resistance around the loop at which the branch-
¯ows exist. If DLPtm . 0; loss reduction is positive and
hence losses are reduced, and if DLPtm , 0; loss reduction
is negative and hence losses are increased.
Eq. (1) can be rearranged as shown below to be repre-
sented by a circle:
Pm 2A
C
� �2
1 Qm 2B
C
� �2
� A2 1 B2
C22
DLPtm
C�2�
where A � PrlPl 2
PrhPh; B � P
rlQl 2P
rhQh and
C � rloop.
This is called the loop circle. The center of the loop circle
is �A=C; B=C� and its radius is
A2 1 B2
C22
DLPtm
C
" #1=2
The zero loss change loop circle is the one which gives the
change in loss to be zero (i.e.DLPtm � 0). It can be repre-
sented as follows:
Pm 2A
C
� �2
1 Qm 2B
C
� �2
� A2 1 B2
C2�3�
Hence the radius of the loop circle is ��A2 1 B2�=�C2��1=2 for
zero loss change (i.e. DLPtm � 0) and is decreased if loss-
reduction occurs in the loop.
Again, Eq. (1) can be rearranged by separating the lv and
hv-sides and using the fact that rloop � rl 1 rh. Eq. (1)
becomes
DLPtm � DLPl 1 DLPh
�"
2Pm
XrlPl
!1 2Qm
XrlQl
!2
P2
m 1 Q2m
!Xrl
#
1
"22Pm
XrhPh
!22Qm
XrhQh
!2
P2
m1 Q2m
!Xrh
#�4a�
where
DLPl � 2Pm
XrlPl
� �1 2Qm
XrlQl
� �2 P2
m 1 Q2m
� �Xrl
�4b�DLPh � 22Pm
XrhPh
� �22Qm
XrhQh
� �2 P2
m 1 Q2m
� �Xrh �4c�
DLPl is the loss reduction for the lv-side, DLPh the loss
reduction for hv-side and rl and rh the resistances at lv and
hv-sides, respectively.
Eqs. (4b) and (4c) can also be rearranged to represent
circle-equations as
lv-side circle:
Pm 2X
rlPl
� ��Xrl
� �2
1 Qm 2X
rlQl
� ��Xrl
� �2
�X
rlPl
� ��Xrl
� �2
1X
rlQl
� ��Xrl
� �2
2DLPl=X
rl
�5a�
hv-side circle:
Pm 1X
rhPh
� ��Xrh
� �2
1 Qm 1X
rhQh
� ��Xrh
� �2
�X
rhPh
� ��Xrh
� �2
1X
rhQh
� ��Xrh
� �2
2DLPh=X
rh (5b)
If the loss-change is zero due to the branch-exchange,
then DLPtm � 0. One of the typical cases is DLP1 � 0 and
DLPh � 0. The equations (5a) and (5b) will now become
Zero loss-change lv-side circle:
Pm 2X
rlPl
� ��Xrl
� �2
1 Qm 2X
rlQl
� ��Xrl
� �2
�X
rlPl
� ��Xrl
� �2
1X
rlQl
� ��Xrl
� �2
(6a)
Zero loss-change hv-side circle:
Pm 1X
rhPh
� ��Xrh
� �2
1 Qm 1X
rhQh
� ��Xrh
� �2
�X
rhPh
� ��Xrh
� �2
1X
rhQh
� ��Xrh
� �2
�6b�
The proposed geometrical method is developed based on the
formation of circles from Eqs. (1)±(6). The equations are
represented by a set of circles. The lv-side and hv-side
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304 297
circles are drawn from the relationship between the loss
reduction (DLPl, DLPh) and the power transfer (Pm, Qm).
The loop circle is the resultant of the two circles which
can also be drawn by using Equation (2). For the above
typical case where DLPtm � 0, DLPl � 0 and DLPh � 0,
all the circles touch each other at the (0,0) coordinate as
shown in Fig. 2. These circles are called zero loss-change
circles.
It is proven that if the values of the termsP
rlPl andPrlQl are greater than the values of the terms
PrhPh andP
rhQh; respectively, then the loop circle will be in lv-side
circle as shown in Fig. 2(a). In this case, positive loss-reduc-
tion is obtained and losses will be reduced for a switching
operation in the loop. On the other hand, if the values of the
termsP
rlPl andP
rlQl are smaller than the values of the
termsP
rhPh andP
rhQh; respectively, then the loss reduc-
tion value, DLPtm in Eq. (1) will be negative and hence the
loop circle will be in hv-side circle as shown in Fig. 2(b).
For this case, losses will not be reduced for any switching
operation in the loop because of negative loss-reduction.
It was mentioned that the individual branch power ¯ow
(Pm, Qm) in the loop are represented as several points in the
P±Q plane. The zero-loss change loop circle is redrawn
separately in Fig. 3 to show that if losses are reduced,
then the radius of the circle is reduced and if losses are
increased, the radius is increased. It can be visualized that
losses are reduced for those points which are inside the zero-
loss change loop circle. S (Pm, Qm) is such a point inside the
circle and C (P0, Q0) is the center of the circle. Therefore, in
the periphery of the circle, loss-reduction DLPtm � 0; inside
the circle, DLPtm . 0 and outside the circle, DLPtm , 0:
The above technique is applied to ®nd the branch asso-
ciated with sectionalizing switch to be exchanged with tie-
line at which the sizes of the circles drawn for every possible
switching operation are compared. The smallest circle is
considered the best for maximum loss-reduction and is
chosen to minimize losses by exchanging the corresponding
branch with the tie-line.
3.1. Determination of the maximum loss reduction loop
Network recon®guration for optimal or near optimal
con®guration can be achieved by performing the switching
operations on the feeders. These switching-operations are
determined by implementing a minimal tree-search of possi-
ble con®gurations. The feasible solution among all possible
trees involves a selection which maximizes the loss-reduc-
tion without violating the constraints such as voltage, capa-
city of lines/and transformers and reliability constraints. The
basic idea of the proposed search scheme is ®rst to identify
the maximum loss-reduction loop in the network and then a
switching-option is determined for the loop that gives a
maximum loss reduction.
Eq. (2) can be rearranged as
DLPtm � �A2 1 B2�=C 2 C{�Pm 2 A=C�2 1 �Qm 2 B=C�2}
�7�From Eq. (7), it is evident that the change in loss, DLPtm will
be maximum when Pm � A=C and Qm � B=C: Therefore,
the maximum value of DLPtm in a loop is
DLPtm loop � �A2 1 B2�=C �8�Rearranging Eq. (3), we get the modi®ed zero-loss
change circle as
P 0m 2A���Cp
� �2
1 Q 0m 2B���Cp
� �2
� A2 1 B2���Cp �9�
where P 0m ����Cp
Pm and Q 0m ����Cp
Qm:
The radius of the above circle is ��A2 1 B2=C��1=2; which
is the square root of DLPtm loop value in Eq. (8). The modi®ed
zero-loss change loop circles can be drawn using Eq. (9) for
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304298
Fig. 2. Zero loss change circles as a function of power transfer
Fig. 3. Zero loss-change loop circle
all the loops in the system and the largest circle will give the
maximum loss reduction loop among all the circles drawn
for all the loops in the network.
The drawback of Eq. (8) is that the value of the DLPtm loop
is always a positive constant for a particular loop as it is
independent of Pm and Qm. However, loss-reduction
depends on the value of DLPtm, i.e. if it is positive, losses
are reduced and if it is negative, losses are increased [2].
Whether the loss is reduced or increased cannot be shown by
Eq. (8) because it is always positive. Therefore, to ensure
that the largest circle gives the maximum loss reduction, the
nominal branch is considered. The nominal branch is the
®rst adjacent branch to the tie branch on the lv-side of
the loop and the nominal loss is the loss which occurs by
exchanging the open branch with the nominal branch. If the
nominal loss is negative, then there is no branch in the loop
that can be a candidate for branch exchange [2]. If the
nominal loss is positive, it means that loss reduction can
be achieved and the branch in the loop for branch exchange
is determined.
Eq. (7) can be rewritten for nominal branch exchange as
DLPtk � �A2 1 B2�=C 2 C{�Pk 2 A=C�2 1 �Qk 2 B=C�2}
�10�where, Pk and Qk are the power ¯ows in the nominal branch k.
Using Eq. (10) the nominal loop circle can be drawn for
nominal branch exchange and compared with the zero loss
change circle drawn by using Eq. (3) in the respective loop.
If the nominal loop circle is reduced in size, then the
nominal loss is positive and the branch exchange in the
loop gives the maximum loss-reduction. Otherwise
the next largest circle is considered and checked as above.
3.2. Determination of switching-option for loss reduction
Network recon®guration is implemented by closing a
single tie switch and opening a single sectionalizing switch
to conserve the radial structure of the feeders. A switching-
option is carried out between a tie and a sectionalizing
switch. Multiple switching-options are possible for optimal
or near optimal con®guration where several tie and sectio-
nalizing switches are simultaneously closed and/or opened
by the successive application of the proposed scheme. The
best switching-option to be implemented is chosen in each
successive operation that minimizes losses the most, with-
out any constraint violation.
Civanlar and Grainger [1] have established a rule for the
switching exchange of switches by considering the lv and
hv-side of the loop. In Ref. [1], loss reduction is achieved
when loads are transferred from the lv-side of a loop to the
hv-side of that loop. It was noted that each line contains a
sectionalizing switch to be operated for network recon®-
guration. Therefore, switching-option can also be referred
to as branch-exchange, as an open branch (tie-line) is
exchanged with a closed branch by a switching operation.
In this paper also, branches of lv-side of a loop are consid-
ered for branch exchange and the most suitable switching-
exchange is found by the proposed method as described
below.
After determining the loop that would give the maximum
loss-reduction by the procedure described in the previous
section, a branch-exchange is identi®ed in that loop. The
sizes of various circles are compared which are obtained
by using Eq. (2) for all the branches in the lv-side of the
loop. The size of the circle depends on the value of the
DLPtm. It gets reduced as the DLPtm value is positive and
increased if DLPtm is negative. When DLPtm is positive
maximum for a branch-exchange, then the corresponding
circle will be the smallest one. Therefore, the smallest circle
will give the best solution and the corresponding branch-
exchange will give the maximum loss-reduction. A search
for the selection of the best branch-exchange is made by
determining and comparing the radii of the loop circles
(Eq. (2)) starting from the nominal branch k and moving
backward in the lv-side of the selected loop until the radius
of the circle is found minimum with all constraints satis®ed.
In this way, the proposed method determines the appropriate
switching-option that minimizes the losses.
4. Solution technique
The procedure to determine the loop, which gives the
maximum loss reduction, is summarized below:
(i) Run the load ¯ow program to obtain the estimates of
the power ¯ows in the branches.
(ii) Determine the radii of the modi®ed zero-loss change
circles for all the loops in the system (Eq. (9)) and
compare. Select the largest circle and the corresponding
loop.
(iii) Check the nominal branch-exchange in the selected
loop whether it contributes positive loss-reduction or not.
This is done by comparing the radius of the nominal loop
circle (Eq. (10)) with the radius of zero-loss change circle
(Eq. (3)). If nominal loop circle is reduced in size, then go
to step (v). Otherwise select the next largest circle and
repeat step (iii).
(iv) If all the nominal loop circles are increased in size
compared to their respective zero-loss change circles,
then stop.
(v) Identify the loop of the corresponding circle and
declare it as the maximum loss-reduction loop. Having
found the loop which would give the maximum loss
reduction, the next step is to determine the branch to be
exchanged.
(vi) Start from the nominal branch of the selected loop in
step (v) and search the branches backward on the lower
voltage-side of the loop until the radius of the loop circle
(Eq. (2)) is found to be minimum. Identify the corre-
sponding branch-exchange.
(vii) Check the selected branch-exchange for constraints
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304 299
violation. If all the constraints are satis®ed, go to step
(viii); otherwise discard the selected branch-exchange
and continue the search forward and backward (one by
one), until the constraints are satis®ed and the radius is
found to be minimum.
(viii) Declare the selected branch-exchange for maximum
loss reduction.
(ix) Repeat steps (i) to (viii) using the selected branch-
exchange.
5. Test results and discussion
The test system is a hypothetical 12.66 kV radial distri-
bution system with 69 buses and 7 laterals which has been
derived from a portion of the PG&E distribution system
[13]. The schematic diagram of the test system is shown
in Fig. 4. The system data of the base con®guration are
given in Appendix A. There are 5 tie-lines (looping
branches) in the system and sectionalizing switches on
every branch of the system. The total system loads for the
base con®guration are 3802.19 kW and 2694.60 kVAr. The
system real power loss is about 5.92% of the total load
which is 225.05 kW. The proposed technique has been
implemented by using Borland C11.
The proposed geometrical method is tested on the 69-bus
test system and test results are summarized in Tables 1 and
2. Table 1 shows the ®rst search-level at which radii of
modi®ed zero-loss change circles for all loops are
calculated, and the loop that gives the largest value of radius
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304300
Fig. 4. Schematic diagram of a 69-bus distribution system
Table 1
Selection of branch-exchange in the ®rst search-level of the proposed method (radius value is in per unit)
Selection of loss-reduction loop Con®rmation of loss reduction
in selected loop
Identi®cation of branch-exchange
Loop no. Radius of modi®ed zero-
loss change loop circle
Selected
loop
Radius of nominal
loop circle
Radius of zero-loss
change loop circle
Radius of
smallest circle
Corresponding branch-
exchange (in±out)
Loop 1 0.051 Loop 4 0.005 (smaller) 0.115 (larger) 0.004 73±59
Loop 2 0.015
Loop 3 0.050
Loop 4 0.105 (largest)
Loop 5 0.040
is selected. In the next step, a comparison is made between
the nominal loop circle and the zero-loss change loop circle
to make sure that the selected loop gives loss reduction. The
nominal circle has to be smaller to achieve loss reduction in
the system. Finally, the branch-exchange in that loop is
selected by determining and comparing the radii of the
loop circles starting from the nominal branch and searching
the branches backward in the lv-side of the selected loop
until the smallest circle is found which gives the maximum
loss-reduction. As shown in Table 1, the ®rst iteration of the
proposed method has found loop 4 as the maximum loss-
reduction loop, and the branch exchange 73±59 to be
performed in that loop to achieve maximum loss reduction.
The above procedure is continued until all the loops have
the nominal circles larger compared to their respective zero-
loss change circles.
Table 2 shows the summary of the selection of branch-
exchanges in all the search-levels of the proposed method.
The optimal network con®guration for loss reduction is
achieved after ®ve search-levels of the proposed method,
in which, at each search level (or iteration) a load ¯ow
solution is obtained, the maximum loss-reduction loop is
selected and a branch-exchange is determined. In the ®fth
search-level, all the nominal circles become larger in size
compared to their respective zero-loss change circles and
are shown in Table 2.
The performance of the proposed method and Baran and
Wu's method [2] are tested on the 69-bus test system. The
results are summarized and compared in Table 3. The test
results of Table 3 indicate that the ®rst branch exchange
(73±59) contributes most of the loss-reduction. The degree
of loss reductions at different search levels are shown in Fig.
5, in which 72.56% of the total loss reduction is obtained by
the ®rst branch exchange (or at ®rst search level). The opti-
mal con®guration for loss reduction is shown in Fig. 6,
which is the same as the con®guration obtained by Baran
and Wu's method as indicated in Table 3. The percentage of
real power loss for the optimal network con®guration is
2.62% which shows a reduction of 3.30% in the system
real power loss (or equivalently 55.72% of improvement
in reducing the total system loss).
From Table 3, it is seen that the search method of Baran
and Wu's algorithm involves m power ¯ow solutions, where
m is the number of open-switches. A power ¯ow solution is
also required to determine the operating point in Baran and
Wu's method [2]. In the test system, there are ®ve open
switches which are SW70, SW71, SW72, SW73 and
SW74. Baran and Wu's method requires ®ve search-levels
and hence 26 load ¯ow solutions are required to get the
optimal network con®guration. To reduce this large compu-
tational time, Baran and Wu proposed the use of simpli®ed
dist-¯ow method to calculate the load ¯ow solutions.
However, the proposed method requires only one load
¯ow solution at each search-level and 5 load ¯ow solutions
to achieve the optimal con®guration. Although the switch-
ing options for optimal con®guration and total loss-reduc-
tions are found to be the same for both methods, the
proposed method is found to be better since it identi®es
the switches to be opened for loss reduction with less
computational effort and time. This is due to the fact that
at each search level, the maximum loss reduction loop is
®rst determined and then followed by the branch to be
exchanged in that loop.
However, Baran and Wu's method takes longer time to
identify the branch to be exchanged because it considers the
switching exchanges of all the loops at each search-level
and calculates the loss reduction for each selected switch-
ing-option by using load ¯ow solution. A branch-exchange
of Baran and Wu's method is then chosen based on the
ordering of the loss reduction ®gures obtained in that search
level. On the other hand, the proposed method determines
the loop that gives maximum loss reduction and considers
the branches in that loop only, to choose a branch-exchange
in a search-level. It is seen that the proposed method has
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304 301
Table 2
Selection of branch-exchanges by the proposed geometrical method (radius value is in per unit)
Search-level Loop selection Con®rmation of loss reduction in selected
loop
Identi®cation of branch-exchange
Radius of
modi®ed zero-loss
change loop circle
Selected
loop
Radius of nominal
loop circle
Radius of zero-loss
change loop circle
Radius of
smallest circle
Corresponding
branch-exchange (in±out)
1 0.105 Loop 4 0.005 0.115 0.004 73±59
2 0.085 Loop 3 0.018 0.058 0.012 72±13
3 0.158 Loop 5 0.060 0.100 0.065 74±62
4 0.095 Loop 3 0.015 0.065 0.005 13±15
5 0.298 Loop 1 0.050 0.015 (smaller) No branch-exchange is identi®ed as no loop is
found to give loss reduction.
0.293 Loop 2 0.165 0.004 (smaller)
0.050 Loop 3 0.063 0.043 (smaller)
0.020 Loop 4 0.085 0.060 (smaller)
0.003 Loop 5 0.080 0.065 (smaller)
greatly reduced the computational time compared to Baran
and Wu's method due to the less number of load ¯ow execu-
tions. It is experimentally proven that the methods involved
with a large number of load ¯ow solutions, some times,
seem exhaustive and unrealistic especially for larger
systems, due to excessive computational time.
6. Conclusion
A geometrical method for loss-reduction has been
presented in this paper. In the ®rst stage of the proposed
method, the sizes of the modi®ed zero-loss change circles
are compared, and the largest one is selected as the maxi-
mum loss-reduction loop. To ensure the loss-reduction for a
branch-exchange in the selected loop, the size of nominal
loop circle is compared with that of the zero-loss change
circle. If the nominal loop circle-size is reduced, then the
corresponding loop gives the maximum loss reduction.
Otherwise, the next largest circle is considered. In the
next stage, the sizes of the loop circles for various branch-
exchanges in the selected loop are compared to identify the
smallest one for the best solution. The corresponding
branch-exchange of the smallest circle gives the maximum
loss-reduction in the system. To show the ef®ciency and
performance of the proposed method for the solution of
computationally complex and large dimensionality
problems, a system with 69-bus and seven laterals has
been considered. Test results indicate that the proposed
method can identify the most effective branch-exchange
operations for loss-reduction with less computational effort
and time. A new approach for network recon®guration
based loss reduction is presented in this paper by
introducing a geometrical technique. The method can be
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304302
Table 3
Results obtained by the proposed geometrical method and Baran and Wu's Method [2] (`(in±out)' indicates branch into the system and branch out from the
system, respectively)
Search level Proposed geometrical method Baran and Wu's branch±exchange method
Maximum loss
reduction loopa
Branch exchange
(in±out)
Loss reduction
(kW)
Branch exchange
(in±out)
Loss reduction
(kW)
Chosen
branch-exchange
1 Loop 4 73±59 90.98 70±10 29.94 73±59
71±18 2.96
72±12 28.84
73±59 90.98
74±62 24.21
2 Loop 3 72±13 11.08 70±11 2.70 72±13
71±18 2.76
72±13 11.08
59±73 290.98
74±62 4.32
3 Loop 5 74±62 23.13 70±11 22.19 74±62
71±21 20.18
13±15 20.07
59±73 277.70
74±62 23.13
4 Loop 3 13±15 0.20 70±43 221.93 13±15
71±21 22.31
13±15 0.20
59±73 249.89
62±61 2224.33
5 No loop is selected
for loss reductionb
± ± 70±43 221.79 No branch-
exchange
is selectedc
71±21 26.68
15±72 230.09
59±73 250.34
62±61 2222.73
Selection of ®nal
branch-exchange
Selection of ®nal branch-exchange
73±59, 72±15, 74±62 73±59, 72±15, 74±62
a Loop1 is associated with tie-line 70, loop2 with tie-line 71, loop3 with tie-line 72, loop4 with tie-line 73 and loop5 with tie-line 74.b No loop is selected in the search for loss reduction due to all nominal circles becoming bigger in size compared to their respective zero-loss change circles.c No branch exchange is selected because of negative loss reduction for all branch-exchanges.
implemented in two distinct ways: one is by measuring and
comparing the radii of the circles as presented in this paper,
and the other is by drawing, superimposing and comparing
the circles graphically. The proposed method can be used as
an ef®cient tool for network recon®guration based loss-
reduction in distribution systems.
Acknowledgements
Some of the preliminary results of this paper have been
reported in International Power Engineering Conference
(IPEC '99), Singapore, 24±26 May 1999.
Appendix A. Network data of the 69-bus distributionsystem
Substation voltage (kV)� 12.66, base MVA� 10.00,
base voltage (kV)� 12.66, total load: P(kW)� 3802.19,
Q(kVAr)� 2694.60.
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304 303
Fig. 5. Loss reduction at different search levels
Fig. 6. The optimal con®guration for loss minimization
Branch
no.
Send
bus
Recv
bus
Branch data Receiving end load
r (ohm) x (ohm) P (kW) Q (kW)
1 0 1 0.0005 0.0012 0.0000 0.0000
2 1 2 0.0005 0.0012 0.0000 0.0000
3 2 2e 0.0000 0.0000 0.0000 0.0000
4 2e 3 0.0015 0.0036 0.0000 0.0000
5 3 4 0.0251 0.0294 0.0000 0.0000
6 4 5 0.3660 0.1864 2.6000 2.2000
7 5 6 0.3811 0.1941 40.400 30.000
8 6 7 0.0922 0.0470 75.000 54.000
9 7 8 0.0493 0.0251 30.000 22.000
10 8 9 0.8190 0.2707 28.000 19.000
11 9 10 0.1872 0.0691 145.00 104.00
12 10 11 0.7114 0.2351 145.00 104.00
13 11 12 1.0300 0.3400 8.0000 5.5000
14 12 13 1.0440 0.3450 8.0000 5.5000
15 13 14 1.0580 0.3496 0.0000 0.0000
16 14 15 0.1966 0.0650 45.500 30.000
17 15 16 0.3744 0.1238 60.000 35.000
18 16 17 0.0047 0.0016 60.000 35.000
19 17 18 0.3276 0.1083 0.0000 0.0000
20 18 19 0.2106 0.0696 1.0000 0.6000
21 19 20 0.3416 0.1129 114.00 81.000
22 20 21 0.0140 0.0046 5.3000 3.5000
23 21 22 0.1591 0.0526 0.0000 0.0000
24 22 23 0.3463 0.1145 28.000 20.000
25 23 24 0.7488 0.2745 0.0000 0.0000
26 24 25 0.3089 0.1021 14.000 10.000
27 25 26 0.1732 0.0572 14.000 10.000
28 2 27 0.0044 0.0108 26.000 18.600
29 27 28 0.0640 0.1565 26.000 18.600
30 28 29 0.3978 0.1315 0.0000 0.0000
31 29 30 0.0702 0.0232 0.0000 0.0000
32 30 31 0.3510 0.1160 0.0000 0.0000
33 31 32 0.8390 0.2816 14.000 10.000
34 32 33 1.7080 0.5646 19.500 14.000
35 33 34 1.4740 0.4673 6.0000 4.0000
36 2e 27e 0.0044 0.0108 26.000 18.550
37 27e 28e 0.0640 0.1565 26.000 18.550
38 28e 65 0.1053 0.1230 0.0000 0.0000
39 65 66 0.0304 0.0355 24.000 17.000
40 66 67 0.0018 0.0021 24.000 17.000
41 67 68 0.7283 0.8509 1.2000 1.0000
42 68 69 0.3100 0.3623 0.0000 0.0000
43 69 70 0.0410 0.0478 6.0000 4.3000
44 70 88 0.0092 0.0116 0.0000 0.0000
45 88 89 0.1089 0.1373 39.220 26.300
46 89 90 0.0009 0.0012 39.220 26.300
References
[1] Civanlar S, Grainger JJ, Yin H, Lee SSH. Distribution feeder recon-
®guration for loss reduction. IEEE Transactions on Power Delivery
1988;3(3):1217±23.
[2] Baran ME, Wu FF. Network recon®guration in distribution systems
for loss reduction and load balancing. IEEE Transactions on Power
Delivery 1989;4(2):1401±7.
[3] Merlin A, Back H. Search for a minimal-loss operating spanning tree
con®guration for an urban power distribution system. Proceedings of
the Fifth Power System Conference (PSCC). Cambridge, 1975. p. 1±
18.
[4] Shirmohammadi D, Hong HW. Recon®guration of electric distribu-
tion networks for resistive line losses reduction. IEEE Transactions on
Power Delivery 1989;4(2):1492±8.
[5] Goswami SK, Basu SK. A new algorithm for the recon®guration of
distribution feeders for loss minimization. IEEE Transactions on
Power Delivery 1992;7(3):1484±91.
[6] Broadwater RP, Khan AH, Shaalan HE, Lee RE. Time varying load
analysis to reduce distribution losses through recon®guration. IEEE
Transactions on Power Delivery 1993;8(1):294±300.
[7] Huddleston CT, Broadwater RP, Chandrasekaran A. Recon®guration
algorithm for minimizing losses in radial electric distribution systems.
Electric Power System Research 1990;18(1):57±67.
[8] Peponis GP, Papadopoulos MP, Hatziargyriou ND. Distribution
network recon®guration to minimize resistive line losses. IEEE
Transactions on Power Delivery 1995;10(3):1338±42.
[9] Taleski R, Rajicic D. Distribution network recon®guration for energy
loss reduction. IEEE Transactions on Power Systems 1997;12(1):
398±406.
[10] Kashem MA, Moghavvemi M, Mohamed A, Jasmon GB. Loss reduc-
tion in distribution networks using new network recon®guration algo-
rithm. Electric Machines and Power Systems 1998;26(8):815±29.
[11] Shin BCG. Development of the loss minimization function for real
time power system operations: a new tool. IEEE Transactions on
Power Systems 1994;9(4):2028±34.
[12] Borozan V, Rajakovic N. Minimum loss distribution network con®g-
uration: analyses and management. Proceedings of IEE Conference,
2±5 June 1997. p. 6.18.1±6.18.5.
[13] Baran ME, Wu FF. Optimal capacitor placement on radial distribution
systems. IEEE Transactions on Power Delivery 1989;4(1):725±34.
M.A. Kashem et al. / Electrical Power and Energy Systems 23 (2001) 295±304304
(continued)
Branch
no.
Send
bus
Recv
bus
Branch data Receiving end load
r (ohm) x (ohm) P (kW) Q (kW)
47 3 35 0.0034 0.0084 0.0000 0.0000
48 35 36 0.0851 0.2083 79.000 56.400
49 36 37 0.2898 0.7091 384.70 274.50
50 37 38 0.0822 0.2011 384.70 274.50
51 7 40 0.0928 0.0473 40.500 28.300
52 40 41 0.3319 0.1114 3.6000 2.7000
53 8 42 0.1740 0.0886 4.3500 3.5000
54 42 43 0.2030 0.1034 26.400 19.000
55 43 44 0.2842 0.1447 24.000 17.200
56 44 45 0.2813 0.1433 0.0000 0.0000
57 45 46 1.5900 0.5337 0.0000 0.0000
58 46 47 0.7837 0.2630 0.0000 0.0000
59 47 48 0.3042 0.1006 100.00 72.000
60 48 49 0.3861 0.1172 0.0000 0.0000
61 49 50 0.5075 0.2585 1244.0 888.00
62 50 51 0.0974 0.0496 32.000 23.000
63 51 52 0.1450 0.0738 0.0000 0.0000
64 52 53 0.7105 0.3619 227.00 162.00
65 53 54 1.0410 0.5302 59.000 42.000
66 10 55 0.2012 0.0611 18.000 13.000
67 55 56 0.0047 0.0014 18.000 13.000
68 11 57 0.7394 0.2444 28.000 20.000
69 57 58 0.0047 0.0016 28.000 20.000
Tie-line
70 10 70 0.5000 0.5000
71 12 20 0.5000 0.5000
72 14 90 1.0000 1.0000
73 38 48 2.0000 2.0000
74 26 54 1.0000 1.0000