Document No. FTEX 10 20 21 Building TechnologiesRevision 10-2008 Activity FIS
EQUIPPED CYLINDER HFC227ea*AND FK5-1-12**
Code: See tableReference: BOUT32-RED/BOUT67-RED/BOUT80-RED
Cylinder fitted with its PROCAP-Nmetallic protection cap shown in half cross section.
Code A6E60200516 A6E60200459 A6E60200460
Reference BOUT32-RED BOUT67-RED BOUT80-RED
Minimum capacity 32 l 67 l 80 l
Length of cylinder I 997 15 mm 1 517 15 mm 1 717 15 mm
Total heightL 1 200 15 mm 1 720 15 mm 1 920 15 mm
Output height H 1 068 15 mm 1 588 15 mm 1 788 15 mm
External diameter D 229 mm 267 mm
Collar diameter d 150 mm
Tag E 380 mm 670 mm 870 mm
Empty weight 3% 53 kg 88 kg 93 kg
Maximum full weight 88.8 kg* - 91.4 kg** 163 kg* - 168.4 kg** 182.6 kg* - 189 kg**
Maximum load 35.8 kg* - 38.4 kg** 75 kg* - 80.4 kg** 89.6 kg* - 96g**
Minimum / maximum filling rate HFC227ea 0.4 kg/l / 1.12 kg/l (Vds : 1 kg/l)
Minimum / maximum filling rate FK5-1-12 0.4 kg/l / 1.2 kg/l
Test pressure 300 bar
Transport temperature range 30 C
+ 65 C
Storage temperature 20 C
+ 50 C
Normal pressure at 20 C 42 bar
Valve VSB33
Valve outletRight
Left
Visual and electric pressure indicator Detachable equipment not included
Shoulder colour (+ reference) Red
(RAL3000)Cylinder colour (+ reference)
Approval (cylinder + valve)
(1999/36/CE)
-
7/25/2019 Ht Botellas
2/2
Siemens SAS
Building Technologies
ZI BP 20 617, rue Fourny78531 BUC Cedex FRANCE
Tel. +33 1 - 30 84 66 00
Fax +33 1 - 39 56 42 08
www.siemens.fr/buildingtechnologies
2008 Copyright by Siemens SAS
Subject to change and availability without notice
Document No. FTEX 10 20 21Revision 10-2008
Description and use
Equipped cylinder HFC227eaand FK5-1-12
The fitted cylinders (cylinder + valve) are made in accordance with the Transportable Pressure Equipment Directive (DESPT 99/36/CE). Valves and
cylinders are stamped .
The cylinders are of seamless forged steel. They are coated with a corrosion-inhibiting primer and an enamel finishing coat, the colour of which is indicated
in the table overleaf.
A cap protects the valves during transport and storage.
Tag
Refer to the FTEX 10 21 10and FTEX 10 21 11data sheets.The label plates FR2:LB000459126008(for HFC227 eagas) and FR2:LB000459136008(for FK5-1-12gas) are delivered in the cylinder cap. During the
installation, stick the label version required.
Maintenance
Every 6months, check the general condition of the cylinder. For the maintenance of the other elements, refer to the corresponding technical sheets. The
cylinder must be secured before any dismantling. Apply the instructions of the INS AX02document for the supply of securing accessories and handling
the cylinders.
Precautions
This product is exclusively intended for use by specialised installers with experience in the design, installation and maintenance of automatic extinguishing
systems. They must ensure that this product is correctly used according to the specified conditions, that there is no danger for themselves or others, andthat the SIEMENSinstructions are followed (assembly instructions, technical instructions, commissioning instructions, installation manuals). Checks shall