Taking the Guesswork out of Mixed-Use Building Analysis
Photo credit: Eckert & Eckert Photography; GBD Architects
Marc Rivard, PE, SERegional Director - MA, CT, ME, NH, RI, VT
Momo Sun, PERegional Director – NY, NJ, PA
Terry Pattillo, AIARegional Director – DC, DE, WV, VA, MD
“The Wood Products Council” is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES), Provider #G516.
Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request.
This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product.______________________________
Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
Course DescriptionWhile mixed-use buildings—which combine multiple occupancy types and/or functions in a single structure—are common, determining how to apply their unique mix of code requirements can be a daunting task. To simplify code analysis associated with these buildings, this presentation covers logical, code-compliant steps for a number of topics, including determining allowable building size, separation needs, detailing requirements, and the application of special provisions. With an emphasis on the use of wood framing in Construction Types III, IV and V, examples, calculations, and details will be presented to demonstrate how to navigate the various code requirements associated with mixed-use buildings while maximizing building size and meeting fire and life safety needs.
Learning Objectives
1. Review the basic fire and life safety requirements associated with mixed-use, wood-frame structures.
2. Become familiar with the differences between Construction Types III, IV and V as defined by the International Building Code.
3. Highlight options for determining allowable building size of mixed-use facilities, including separated and non-separated occupancies, incidental uses and podiums.
4. Demonstrate how to achieve separation of occupancies with fire barriers, fire walls and horizontal assemblies.
Fire and life safetyibc
The building code:• Controls building size• Regulates type of materials used• Stipulates fire resistance
Fire and life safetyibc
In early years of building code development, main purpose was to provide a reasonable level of protection to propertyfrom fire.Concept was that if property was adequately protected fromfire, occupants would also be protected.
Historical limitations
Many of the current building size limits are based on historical fire department access limitations
Sources:E.M. Shaw, Fire surveys 1872: E. WilsonGreat Britain. Parliament. House of Commons, Reportsfrom Committees. 1874.
60 ft
60 ft
60 ft
Fire and life safetyibc
From this outlook on property fire safety, concept of equivalent risk evolved in the code.
Equivalent risk associates an acceptable level of risk against the damages of fire respective to a particular occupancy group by limiting building size according to construction type
Fire and life safetyibc
As a result of extensive research and advancements in fire technology, today’s building codes are more comprehensive and complex
While the principle of equivalent risk remains an important component in the codes for protecting the building, perspectives have changed and life safety is now the paramount fire issue.
But…The code still allows flexibility in building design, configuration, construction type, materials and other choices
Don’tgetboxedin
building optionsNational market data indicates that many commercial occupancies including hotels, multi-family, office, retail and restaurants can be framed with wood, including in mixed-use applications, when considering building size
Market data analysis
Hotels and motels: average building size
Project SF: <50K 50-100 100-150 150-200 200-250 250-300 300-350 350-400
Source: 2015 dodge market data
• 90% of hotel buildings are less than 150k sf in total building area
Market data analysisapartments: average building sizeSource: 2015 dodge market data
Project SF: <50K 50-100 100-150 150-200 200-250 250-300 300-350 350-400 400-450 >450
• 77% of apartment buildings are less than 150k sf in total building area
Market data analysisRetail & restaurants: average building sizeSource: 2015 dodge market data
Project SF: <50K 50-100 100-150 150-200 200-250
• 90% of retail and restaurant buildings are less than 50k sf in total building area
Market data analysisWhat does all of this mean?
Wood is being underutilized in many commercial occupancy buildings
These can be framed with wood, type v construction, why is it important to recognize that?
Of those bldgs: % Wood
hotels 90% < 150 K SF 49% are Wood
apartments 77% < 150K SF 48% are Wood
Retail/restaurant 90% < 50K SF 22% are Wood
offices 76% < 50K SF 25% are Wood
Source: 2015 dodge market data
In low- to mid-rise building types, Many designers accustomed to steel & concrete default to type ii construction
However, nearly identical building size can be achieved with wood framing in Type IIIA or IIIB
Why is the construction type selection so important?
building options
$ia
$134
$ib
$128
$$123
iia
$$117
iib
$$107
iiia$
iiib
$104
$$93
va$
$89
vbConstruction Type
ICC building valuation data, m occupancy buildings, February 2017
Cost per SF
$ia
$186
$ib
$179
$$174
iia$
$167
iib$
$154
iiia$
iiib
$150
$$138
va$$134
vbConstruction Type
Cost per SFICC building valuation data, r-1 occupancy buildings, February 2017
building options
Many buildings utilize a higher construction type than necessary due to traditional practice. This can have an impact on fire ratings, materials and ultimately cost.
Mixed-use development is a type of urban development that blends residential, commercial, cultural, institutional, or
industrial uses, where those functions are physically and functionally integrated, and
that provides pedestrian connections.
Or, simplistically:
Source: thrall
building options
There are multiple ways to classify a building. Challenge tradition and Consider all options in an effort to achieve the most cost-effective solution
building optionsStart with the lowest common denominator option & work up. Don’t assume that a certain construction type, occupancy separation, etc. will be required simply based on use of certain materials or presence of certain occupancies
Image credit: neo studio
Mixed occupancy buildingsIBC 508
Example: urban infill project: 3 story buildingBelow grade: 12,000 sf parking
1st floor: 9,500 sf parking1,200 sf insurance agency1,300 sf print shop
2nd floor: 2,400 sf martial arts studio9,600 sf apartments
3rd floor: 12,000 sf apartments
NFPA 13 sprinkler system throughout buildingenclosed parking garage
grade to mean roof height = 38 ft
Parking (s-2)
Insurance agency (b)
Print Shop (b) Martial Arts Studio (b)
Apartments (r-2)
3rd floor - - - - 12,000 sf
2nd floor - - - 2,400 sf 9,600 sf
1st floor 9,500 sf 1,200 sf 1,300 sf - -
basement 12,000 sf - - - -
Per ibc 503 & 506, basement does not need to be included in area and story calculations
Mixed occupancy buildingsIBC 508
S-2 b r-2 Actual Building
Allow. # stories 3 3 3 3
Allow. height 60 ft 60 ft 60 ft 38 ft
Allow. area/floor 40,500 sf 27,000 sf 21,000 sf 12,000 sf
Allow. Total area 121,500 sf 81,000 sf 63,000 sf 36,000 sf
try type vb construction:
Most restrictive occupancy group, r-2 works for total building.
Use non-separated, type vb construction
Mixed occupancy buildingsIBC 508
This 3 story, type vb mixed-use building can be fully framed with wood and can have non-separated occupancies
• No podium is necessary• No fire resistance rated separation
between occupancies is necessary (unless required by other code provisions)
• Even if other materials are used in parts of the building, can still be type VB construction
Mixed occupancy buildingsIBC 508
Mixed occupancy buildingsIBC 508What are the special provisions and/or other special design allowances we
can use?
• Incidental Uses (509)• Accessory occupancies (508.2)• Unique occupancy combinations (303)• Roof top occupancies (Chpt. 5)• Special provisions (510)• Non-Separated occupancies (508.3)• Separated Occupancies (508.4)• Separate Buildings – firewalls (503.1 & 706)• Covered and Open Malls (402)
Outside scope of presentation
Credit: boye architecture
Mixed occupancy buildingsIBC 508
Incidental usesIBC 509
• Ancillary function associated with an Occupancy• Pose GREATER risk than the Occupancy• Examples:
• Laundry room over 100 sf• Refrigerant machinery room• Incinerator room• Furnace room• Boiler room• Vocational shop in a school
Incidental usesIBC 509
Limitations:• Each incidental use not more than 10% of area of story• Have fire resistance rated separation (fire barrier or
horizontal assembly), smoke separation and/or sprinkler systems per Table 509 and Section 509.4• Many permit use of sprinklers in lieu of rated separation
• NOT classified as a different occupancy.• Allowable Building Area and Height per main Occupancy
Photo Sean Hackbarth/Flickr
Occupancy 1
Incidental Use
Separation per Table 509
Incidental usesIBC 509
Incidental uses example:• NFPA 13 sprinklered, 4 story, type VA building• Upper 3 floors: 18,000 sf apartments (r-2)• 1st floor: 16,400 sf apartments plus 800 sf laundry room & 800 sf
boiler room• Total building area = 72,000 sf
• Table 503: allowable building area w/sprinkler increase = 108,000 sf; no floor greater than 36,000 sf: ok
• Allowable incidental use area = 18,000*0.10 = 1,800 sf > 800 sf: ok can classify laundry room & boiler room as r-2
• Table 509: walls and floor separating laundry room & boiler room from r-2: no hourly rating required since bldg is sprinklered but smoke resistance is required in conjunction with sprinklers per Section 509.4.2
R-2 apartments16,400 sf
800 sf Laundry room
800 sf boiler room
Accessory occupanciesIBC 508.2
• Ancillary to the main occupancy• Aggregate accessory area not greater than:
• 10% of the main Occupancy on same floor• Table 503 non-increased Allowable Area limit of accessory
occupancy• No separation between occupancies required*• Allowable building area and height per main occupancy
*Hazardous occupancies require separation*Residential separations per Section 420 still apply
Occupancy 1
Accessory Occupancy
No Separation Required*
Accessory Occupancy
Accessory occupanciesIBC 508.2
Accessory occupancies Example:• Unsprinklered, 1 story, type VA building• Factory (f-1) 9,600 sf• Two office (b) spaces: 400 sf and 800 sf
• Table 503: allowable area = 14,000 sf• Total floor area = 10,800 sf < 14,000 sf ok
• Aggregate Accessory use areas = 1,200 sf• Max. allowable aggregate accessory use area =
10,800*0.10 = 1,080 sf
• Does not work as accessory occupancies• Solution: reduce office area, increase factory area or
use mixed-use occupancies
Factory: 9,600 sf
Accessory OccupancyOffice: 800 sf
Office: 400 sf
small assembly spacesIBC 303.1.1 & 303.1.2
Small assembly spaces:• A building or tenant space used for assembly purposes with an occupant load of less than
50 persons shall be classified as a Group B occupancy.Example: small cafe
Small assembly spaces accessory to other occupancies:• Occupant load less than 50 persons or less
than 750 sf in area - can be classified as a Group B occupancy or as part of main occupancy
Examples: • Conference room in office building• Fitness center in hotel
Assembly spaces in educational facilitiesIBC 303.1.3
Educational facilities:• A room or space used for assembly purposes that is associated with a Group E
occupancy is not considered a separate occupancy.Examples: gymnasium used for school sports; cafeteria used for school meals
Educational spaces in places of worshipIBC 303.1.4
Places of religious worship:• Accessory religious educational rooms and religious auditoriums with occupant loads of
less than 100 per room or space are not considered separate occupancies. Example: classrooms
St. Martha Catholic Church – Porter, TXDesign Team : Turner Duran Architects, Pinnacle Structural EngineersPhoto Credit: G. Lyon Photography, Inc.
Multiple functionsIBC 302.1
Buildings used for multiple functions:• A room or space that is intended to be occupied at different times for different
purposes shall comply with all of the requirements that are applicable to each of the purposes for which the room or space will be occupied.
Example: church hall also used as a daycare center and for wedding receptions
Rooftop decksIBC 503.1
Many mixed-use buildings, especially apartment buildings, are implementing occupiable roof top decks, either for individual use or as a gathering space
No current code sections clearly discuss this except for basic exit provisions but several design routes have been used:
Typically these spaces do not have a roof and therefore aren’t classified as stories per the definition of a story (IBC 202)
Rooftop decksIBC 503.1
Occupied roofs Code development 2012 IBC section 1021 contains exit provisions for occupied roofs
2015 IBC clarified egress requirements for occupied roofs (IBC 1006.3)
2018 IBC further recognizes occupied roofs. 2018 IBC provisions:
302.1: Occupied roof classified as occupancy it most closely resembles503.1.4: Permitted to be used as an occupied roof if the occupancy of the roof is an occupancy that is permitted by code for the story immediately below the roof. Area of the occupied roofs is not required to be included in the building area. Further exceptions for sprinklered buildings exist
Special provisionsIBC 510.2
Horizontal building separationoften called podium provision:• Considered separate buildings above and below for
purposes of area calculations if:
• Overall height in feet is still limited to min of either building
• 3hr rated horizontal assembly
• Building below is Type 1A with sprinklers
• Occupancy restrictions above and below
Special provisionsIBC 510.2
Increases allowable stories… not allowable building height
5 story Type III Building 5 story Type III BuildingOn Top of a Type IA Podium
Type
IA
3Hr
Horizontal building separation
Special provisionsIBC 510.5Group r-1 & r-2, type iiia buildings
• Height limitation increased to 6 stories & 75 ft
• First floor assembly above the basement has a fire-resistance rating of not less than 3 hours
• Floor area is subdivided by 2-hour fire- resistance-rated fire walls into areas of not more than 3,000 square feet
Image Credit: ibc code commentary
Allowable building sizeIBC 508
Non-separated occupancies
Occupancy 1
Occupancy 2
Most restrictive requirements of all occupancies apply for:
• Fire Protection Systems (Chapter 9)• Allowable Height and Area
Other requirements for each portion based upon occupancy of that portion (i.e. egress, others)No fire separation between occupancies required*
*Hazardous occupancies require separation.
Non-separated occupanciesIBC 508.3
Occupancy 1 Occupancy 1 Occupancy 2 Occupancy 2
Occupancy 1 Occupancy 2
Acceptable Height & Area?
Acceptable Height & Area?
No Separation Required*
Yes
Yes
Allowable building sizeIBC 508
Non-separated occupancies example
Regional dispatch Office (b)30,000 sf
Warehouse Storage (s-1)41,200 sf
• 1 story building• Total building area = 71,200 sf• IBC section 903 does not require an
automatic sprinkler in group B buildings but it does for S-1 buildings with fire area > 12,000 sf (903.2.9)
• NFPA 13 sprinkler required throughout building
Allowable building sizeIBC 508
Non-separated occupancies example cont’d
Regional dispatch Office (b)30,000 sf
Warehouse Storage (s-1)41,200 sf
Construction type options• VB: inadequate for both• VA: ok for b, inadequate for s-1• IIIB: ok for b, inadequate for s-1• IIIA: works for both, use type IIIA
Allowable 1 Story Building Area
VB VA IIIB IIIA
Group B 36,000 sf 72,000 sf 76,000 sf 114,000 sf
Group S-1 36,000 sf 56,000 sf 70,000 sf 104,000 sfAssumptions:
Nfpa 13 sprinkler throughout. no frontage increase.
No Separation Required
Allowable building sizeIBC 508
Multi-story non-separated occupancy buildings
Image credit: ware malcomb
Allowable building sizeIBC 508
Image credit: ware malcomb
Multi-story Non-separated occupancies example• 3 story building on college campus• Total building area = 61,200 sf:
Floor 3• 16,400 sf classrooms• 4,000 offices
Floor 2• 14,000 sf classrooms• 5,600 sf offices• 800 sf coffee/ snack area
Floor 1• 13,700 sf classrooms• 4,200 offices• 1,700 sf administration• 800 sf coffee/ snack area
• Nfpa 13 sprinkler required throughout building
Allowable building sizeIBC 508
Image credit: ware malcomb
Multi-story Non-separated occupancies example
• Offices: group b occupancy
• Classrooms for higher than 12th grade: group b occupancy
• Admin & offices: group b occupancy
• Coffee/snack bar: group a-2 occupancy• May be able to Use small assembly provision
(ibc 303.1.1) – group b
Allowable building sizeIBC 508
Image credit: ware malcomb
Multi-story Non-separated occupancies exampleOPTIONS:
• If coffee/snack areas meet provisions for small assembly spaces: classify as group b. entire building is group B and can use type VB construction: allowed 3 stories, 60 ft, 27,000 sf per floor, 81,000 sf total area
• If coffee/snack areas don’t meet provisions for small assembly spaces: classify them as group A-2. use non-separated occupancies, type VA construction: group B ok per above, group A-2 allowed 3 stories, 70 ft, 34,500 sf per floor, 103,500 sf total area
• Could also use separated occupancies, type VB construction
Allowable building sizeIBC 508
separated occupancies
Requirements of code for each portion based upon occupancy of that portion
Allowable Height of each occupancy based upon construction type and occupancy
Allowable Area of each storySum of actual area over allowable area of each occupancy ≤ 1.0
Occupancy 1
Occupancy 2
Separated occupanciesIBC 508.4
Actual Area for Occupancy 1Allowable Area for Occupancy 1
Separation PerTable 508.4
+ Actual Area for Occupancy 2Allowable Area for Occupancy 2
≤ 1.0
Check Performed for each Story.Separation by Fire Barriers and Horizontal Assemblies
Occupancy 1
Occupancy 2
Separated occupanciesIBC table 508.4
NP = Not Permitted, N = No Separation Required
Separation accomplished with:Walls: fire barriers (ibc 707)Floors: horizontal assemblies (ibc 711)
Separated occupanciesIBC 508.4
separated occupancies example
Regional dispatch Office (b)30,000 sf
Warehouse Storage (s-1)41,200 sf
• 1 story building• Total building area = 71,200 sf• IBC section 903 does not require an
automatic sprinkler in group B buildings but it does for S-1 buildings with fire area > 12,000 sf (903.2.9)
• NFPA 13 sprinkler required throughout building
Allowable building sizeIBC 508
separated occupancies example cont’d
Regional dispatch Office (b)30,000 sf
Warehouse Storage (s-1)41,200 sf
Construction type options• VB: 30,000/36,000 + 41,200/36,000 = 1.98 > 1.0
inadequate• VA: 30,000/72,000 + 41,200/56,000 = 1.15 > 1.0
inadequate• IIIB: 30,000/76,000 + 41,200/70,000 = 0.98 < 1.0 ok. Use
type IIIb
Allowable 1 Story Building Area
VB VA IIIB IIIA
Group B 36,000 sf 72,000 sf 76,000 sf 114,000 sf
Group S-1 36,000 sf 56,000 sf 70,000 sf 104,000 sf
Assumptions:Nfpa 13 sprinkler throughout. no
frontage increase.
Separation per 508.4
Separated occupanciesIBC table 508.4
NP = Not Permitted, N = No Separation Required
Separation accomplished with:Walls: fire barriers (ibc 707)Floors: horizontal assemblies (ibc 711)
For this example, no separation required
Separated occupanciesIBC table 508.4
Multi-story separated occupancy buildings
Image credit: CUBE 3 Studio LLC & Rixon Photography
Separated occupanciesIBC 2012 506.5 & 508.4 / IBC 2015 506.2.4 & 508.4
Multi-story separated occupancy buildings
Separation PerTable 508.4
sum of ratios of actual area/allowable area for all occupancies per floor:
≤ 1.0 for 1 story building≤ 2.0 for 2 story building≤ 3.0 for 3 or more story buildingNo floor can have a ratio > 1.0
Occupancy 1 Occupancy 2
Occupancy 1Occ. 3
Occupancy 1Occ. 3
Occupancy 1 Occupancy 4
Level 1
Level 2
Level 3
Level 4
Also btwn occ. 1 & occ. 3
Elevation view
Separated occupanciesIBC 508.4
• 4 story building• Total building area = 120,000 SF• Occupancy 1 = apartments (R-2)• Occupancy 2 = retail (M)• Occupancy 3 = restaurant (A-2)• Occupancy 4 = professional offices (B)• IBC section 903.2.8 requires buildings
containing group R fire areas to be sprinklered throughout the building
• Provide NFPA 13 sprinkler throughout building
Occupancy 1 Occupancy 2
Occupancy 1Occ. 3
Occupancy 1Occ. 3
Occupancy 1 Occupancy 4
Level 1
Level 2
Level 3
Level 4
Multi-story separated occupancy example
Occ. 4
Elevation view
Separated occupanciesIBC 508.4
Apartments (r-2)21,000 sf
Retail (m)9,000 sf
Level 1 floor plan
Multi-story separated occupancy example
Apartments (r-2)17,400 sf
Restaurant (a-2)12,600 sf
Level 2 floor plan
Separated occupanciesIBC 508.4
Apartments (r-2)15,200 sf
Level 3 floor plan
Multi-story separated occupancy example
Apartments (r-2)24,400 sf
Restaurant (a-2)12,600 sf
Level 4 floor plan
Office (b)2,200 sf Office (b)
5,600 sf
Separated occupanciesIBC 503
Multi-story separated occupancy example
Allowable floor Area / # of stories
VB VA IIIB IIIA
Group a-2 18,000 sf / 2 34,500 sf / 3 28,500 sf / 3 42,000 sf / 4
Group B 27,000 sf / 3 54,000 sf / 4 57,000 sf / 4 85,500 sf / 6
Group m 27,000 sf / 2 42,000 sf / 4 37,500 sf / 3 55,500 sf / 5
Group r-2 21,000 sf / 3 36,000 sf / 4 48,000 sf / 5 72,000 sf / 5
With full nfpa 13 sprinkler increases but no frontage increase
Separated occupanciesIBC 508.4
Level 1 floor plan
Multi-story separated occupancy example
Try construction type va:va: 21,000/36,000 + 9,000/42,000 = 0.80
Allowable height & stories:R-2: 70 ft, 4 stories - okM: 70 ft, 4 stories - ok
Apartments (r-2)21,000 sf
Retail (m)9,000 sf
Separated occupanciesIBC 508.4
Multi-story separated occupancy example
Level 2 floor plan
Try construction type va:va: 17,400/36,000 + 12,600/34,500 = 0.85
Allowable height & stories:R-2: 70 ft, 4 stories - okA-2: 70 ft, 3 stories - ok
Apartments (r-2)17,400 sf
Restaurant (a-2)12,600 sf
Separated occupanciesIBC 508.4
Level 3 floor plan
Multi-story separated occupancy example
Try construction type va:va: 15,200/36,000 + 12,600/34,500 + 2,200/54,000 = 0.83
Allowable height & stories:R-2: 70 ft, 4 stories - okA-2: 70 ft, 3 stories - ok B: 70 ft, 4 stories - ok
Apartments (r-2)15,200 sf
Restaurant (a-2)12,600 sf
Office (b)2,200 sf
Separated occupanciesIBC 508.4
Multi-story separated occupancy example
Level 4 floor plan
Try construction type va:va: 24,400/36,000 + 5,600/54,000 = 0.78
Allowable height & stories:R-2: 70 ft, 4 stories - okB: 70 ft, 4 stories - ok
Apartments (r-2)24,400 sf
Office (b)5,600 sf
Separated occupanciesIBC 508.4
Occupancy 1 Occupancy 2
Occupancy 1Occ. 3
Occupancy 1Occ. 3
Occupancy 1 Occupancy 4
Level 1
Level 2
Level 3
Level 4
Multi-story separated occupancy example
Occ. 4
sum of ratios of actual area/allowable area for all occupancies per floor:
0.78 + 0.83 + 0.85 + 0.80 = 3.26 > 3.0 inadequate; type va can’t be usedUse type iiib
0.78
0.83
0.85
0.80
Elevation view
building configuration options
example: 5 story hotel
1st floor: lobby, restaurantfitness centerconference roomsResidential
2nd-5th floors residential
Option 1:4-story, type VA over 1 story type IA (podium provision – IBC 510.2)Mixed-use on 1st floor handled with separated/non-separated occupancies considering that floor only
building configuration options
example: 5 story hotel
1st floor: lobby, restaurantfitness centerconference roomsResidential
2nd-5th floors residential
Option 2:5-story, type III (with or without firewalls for area limitations)Mixed-use on 1st floor handled with separated/non-separated occupancies considering all floors
building configuration options
example:T- and l-shaped buildings – common in hotels, often with large floor areas
building configuration options
These building configurations may lend themselves well to use of firewalls at building intersections. Minimize length/impact of firewall while maximizing allowable building areamay allow lower construction type (i.e. type IIIB instead of IIIA)
firewall
Building 1Bu
ildin
g 2
Building 3
Fire wallsIBC 706
separate buildings – fire wallsEach portion of a building separated by one or more fire walls shall be considered to be a separate building
Building 1 Building 2
Fire Wall perIBC 706
Fire wallsIBC 706
• Materials: noncombustible except type V• Hourly ratings per table 706.4• Protected openings• Continuous from foundation to/through roof• Structural stability
If fire wall is separating 2 occupancies, use most restrictive fire rating from
table
building configuration options
There are multiple ways to classify a building. Challenge tradition and Consider all options in an effort to achieve the most cost effective solution
Mixed-use building analysis flow chart Do sub-occupancies classify
as incidental or accessory?
Does bldg size work w/non-separated
occ?
Use non-separated occ
no
yes
yes
Does bldg size work w/incidental or accessory
occ?yes
Use incidental or accessory occ
no
no
Does bldg size work w/separated occ?
Use separated occ
yes
no
Options:Change construction typeUse Special Provisions (eg. podium)Use Fire wall(s)
Also check IBC 303 provisions (small
assembly spaces, etc.)