Panduan Servis

307
Seri - E / F / G / K [Model yang Digunakan] Pasangan Inverter Pendingin Saja Pasangan Inverter Pompa Kalor SiBE121135_A Panduan Servis

Transcript of Panduan Servis

Seri - E / F / G / K

[Model yang Digunakan]

● Pasangan Inverter Pendingin Saja

● Pasangan Inverter Pompa Kalor

SiBE121135_A

Panduan

Servis

SiBE121135_A Pendahuluan

vi

SUPER MULTI NX

Seri - E / F / G / K

Pendingin Saja

Unit Outdoor 3MKS50E3V1B 4MKS58E3V1B 4MKS75F2V1B 5MKS90E2V3B

Unit Indoor FTXS25J2V1B FFQ25B9V1B FHQ35BWV1B FDBQ25B8V1 FTXS35J2V1B FFQ35B9V1B FHQ50BWV1B FBQ35C8VEB FTXS42J2V1B FFQ50B9V1B FHQ60BWV1B FBQ50C8VEB FTXS50J2V1B FFQ60B9V1B FBQ60C8VEB FTXS60GV1B FTXS71GV1B

Pompa Kalor

Unit Outdoor 3MXS40K2V1B 3MXS68G2V1B 4MXS80E2V3B 3AMX52E3V1B 3MXS40K3V1B 3MXS68G3V1B 4MXS80E3V3B 3AMX52E4V1B 3MXS52E3V1B 4MXS68F2V1B 5MXS90E2V3B 3MXS52E4V1B 4MXS68F3V1B 5MXS90E3V3B

Unit Indoor FTXG25JV1BW FVXG25K2V1B FCQG35FVEB ATXS20G2V1B FTXG25JV1BA FVXG35K2V1B FCQG50FVEB ATXS25G2V1B FTXG35JV1BW FVXG50K2V1B FCQG60FVEB ATXS35G2V1B FTXG35JV1BA FVXS25FV1B FFQ25B9V1B ATXS42G2V1B FTXG50JV1BW FVXS35FV1B FFQ35B9V1B ATXS50G2V1B FTXG50JV1BA FVXS50FV1B FFQ50B9V1B CTXS15K2V1B FLXS25BAVMB FFQ60B9V1B FTXS20K2V1B FLXS35BAVMB FHQ35BWV1B FTXS25K2V1B FLXS50BAVMB FHQ50BWV1B CTXS35K2V1B FLXS60BAVMB FHQ60BWV1B FTXS35K2V1B FDXS25E7VMB FDBQ25B8V1 FTXS42K2V1B FDXS35E7VMB FBQ35C8VEB FTXS50K2V1B FDXS50C7VMB FBQ50C8VEB FTXS25J2V1B FDXS60C7VMB FBQ60C8VEB FTXS35J2V1B FTXS42J2V1B FTXS50J2V1B FTXS60GV1B FTXS71GV1B

Pendahuluan

SiBE121135_A

vii

1. Pendahuluan .............................................................................................. vi Peringatan Keselamatan

Ikon yang digunakan ..........................................................................x

Bagian 1 Daftar Fungsi ................................................................................................................ 1

1. Pendingin Saja ........................................................................................... 2

Unit Outdoor ...................................................................................... 2

Unit Indoor ......................................................................................... 3

2. Pompa Kalor............................................................................................... 6 Unit Outdoor ...................................................................................... 6

Unit Indoor ......................................................................................... 8

Bagian 2 Spesifikasi .................................................................................................................. 16

1. Pendingin Saja ......................................................................................... 17

Unit Outdoor .................................................................................... 17

Unit Indoor ....................................................................................... 19

2. Pompa Kalor............................................................................................. 24

Unit Outdoor .................................................................................... 24

Unit Indoor ....................................................................................... 28

Bagian 3 Diagram Pengkabelan Konektor Papan Sirkuit Cetak ........................................ 43

1. Unit Outdoor ............................................................................................. 44

2. Unit Indoor ................................................................................................ 47

2.1 FTXG25/35/50JV1BW(A) ............................................................... 47

2.2 CTXS15/35K2V1B, FTXS20/25K2V1B.......................................... 49

2.3 FTXS35/42/50K2V1B, FTXS25/35/42/50J2V1B,

ATXS20/25/35/42/50G2V1B .......................................................... 51

2.4 FTXS60/71GV1B ............................................................................ 53

2.5 FVXG25/35/50K2V1B ..................................................................... 55

2.6 FVXS25/35/50FV1B ........................................................................ 57

2.7 FLXS25/35/50/60BAVMB ............................................................... 59

2.8 FDXS25/35E7VMB, FDXS50/60C7VMB ....................................... 61

2.9 FCQG35/50/60FVEB ...................................................................... 63

2.10 FFQ25/35/50/60B9V1B .................................................................. 65

2.11 FHQ35/50/60BWV1B ..................................................................... 66

2.12 FDBQ25B8V1 ................................................................................. 67

2.13 FBQ35/50/60C8VEB ...................................................................... 68

3. Remote Kontrol Kabel.............................................................................. 70 3.1 BRC1D528 ...................................................................................... 70

3.2 BRC1E52A7, BRC1E52B7 ............................................................. 71 Bagian 4 Fungsi dan Kendali ................................................................................................... 72

1. Fungsi Unit Indoor RA ............................................................................. 73 Kendali Suhu ................................................................................... 73 Prinsip Frekuensi ............................................................................ 73 Kendali Awal Operasi ..................................................................... 75 Kendali Arah Aliran Udara .............................................................. 76

Kendali Kecepatan Kipas untuk Unit Indoor .................................. 80

Operasi RADIANT ........................................................................... 81

Program Operasi Kering ................................................................. 83

SiBE121135_A Pendahuluan

viii

Operasi Otomatis ............................................................................ 84

Kendali Termostat ........................................................................... 85

Mode NIGHT SET ........................................................................... 86

Operasi ECONO ............................................................................. 87

Operasi HOME LEAVE ................................................................... 88

Operasi INTELLIGENT EYE ......................................................... 90

Operasi INTELLIGENT EYE 2-Area ............................................. 91

Operasi Inverter POWERFUL ....................................................... 93

Lampu Indikator Banyak Warna / Lampu TIMER ......................... 94

Pengaturan Kecerahan pada Layar Unit Indoor............................ 95

Pengaturan Jam .............................................................................. 96

Operasi WEEKLY TIMER ............................................................... 97

Fungsi-fungsi Lainnya................................................................... 103

2. Fungsi Unit Indoor SA............................................................................ 104 Kendali Pompa Pengurasan......................................................... 104

Sensor Termostat pada Remote Kontrol ..................................... 106

Kendali Pencegahan Kebekuan ................................................... 108

Kendali Hot Start (Pada Operasi Pemanasan Saja) ................... 109

3. Fungsi Termistor .................................................................................... 110

4. Spesifikasi Kendali ................................................................................. 112

Mode Hirarki .................................................................................. 112

Kendali Frekuensi ......................................................................... 113

Kendali Pengubahan Mode / Start-Up ......................................... 116

Kendali Suhu Pipa Buang............................................................. 117

Kendali Arus input ......................................................................... 118

Kendali Perlindungan Kebekuan .................................................. 118

Kendali pemutusan Puncak Pemanasan..................................... 119

Kendali Kipas Outdoor .................................................................. 120

Fungsi Perlindungan Kompresi Cairan ........................................ 120

Kendali Pencairan ......................................................................... 121

Batas Tekanan Tinggi Hz Rendah ............................................... 122

Kendali Katup Ekspansi Elektronik Outdoor................................ 122

Malfungsi ....................................................................................... 126

Bagian 5 Remote Kontrol ........................................................................................................ 128

1. Unit Indoor RA........................................................................................ 129 1.1 FTXG25/35/50JV1BW(A), CTXS15/35K2V1B, FTXS20/25K2V1B 129

1.2 FTXS35/42/50K2V1B ................................................................... 131

1.3 FTXS25/35/42/50J2V1B, FTXS60/71GV1B ................................ 133

1.4 ATXS20/25/35/42/50G2V1B ........................................................ 135

1.5 FVXG25/35/50K2V1B ................................................................... 137

1.6 FVXS25/35/50FV1B ...................................................................... 139

1.7 FLXS25/35/50/60BAVMB ............................................................. 141

1.8 FDXS25/35E7VMB, FDXS50/60C7VMB ..................................... 143

2. Unit Indoor SA ........................................................................................ 145 2.1 BRC1D528 .................................................................................... 145

Bagian 6 Diagnosis Servis ...................................................................................................... 148 1. Pemecahan Masalah dengan LED ....................................................... 150

Pendahuluan

SiBE121135_A

ix

Unit Indoor ..................................................................................... 150 Unit Outdoor .................................................................................. 152

2. Gejala Masalah dan Tindakan .............................................................. 153 3. Fungsi Pemeriksaan Servis................................................................... 154

Unit Indoor RA ............................................................................... 154 Unit Indoor SA ............................................................................... 163

4. Indikasi Kode pada Remote Kontrol ..................................................... 167 Unit Indoor RA ............................................................................... 167 Unit Indoor SA ............................................................................... 167 Sub Kode untuk Unit Indoor SA ................................................... 168 Unit Outdoor .................................................................................. 169

5. Pemecahan Masalah untuk Unit Indoor RA ......................................... 170 Kelainan PCB Unit Indoor ............................................................. 170 Kendali Perlindungan Kebekuan atau Kendali pemutusan Puncak

Pemanasan ................................................................................... 172 Kipas Motor atau Kelainan terkait ............................................... 173 Kelainan Kenaikan Suhu Panel Radiant, Katup Ekspansi

Elektronik Indoor (Katup yang Dioperasikan Motor), Kendali

Perlindungan Kebekuan (Seri FVXG Saja) ................................. 178

Termistor atau Kelainan terkait (Unit Indoor RA) ........................ 180 Kegagalan Membuka/Menutup Bagian Depan (Seri FTXG Saja)181 Kesalahan transmisi sinyal (Antara Unit Indoor dan Unit Outdoor)

....................................................................................................... 182 Tegangan yang Tidak Menentu (Antara Unit Indoor dan Unit

Outdoor)......................................................................................... 183 6. Pemecahan Masalah untuk Unit Indoor SA ......................................... 184

Kelainan PCB Unit Indoor ............................................................. 184 Kelainan Sistem Kendali Tingkat Pengurasan ............................ 185 Kipas Motor atau Kelainan terkait ............................................... 187 Motor ayun terkunci (Seri FHQ Saja) ........................................... 193 Kelainan Sistem Pengurasan ....................................................... 194 Termistor atau Kelainan terkait (Unit Indoor SA) ........................ 195 Kelainan Termistor Remote Kontrol ............................................. 196 Kesalahan transmisi sinyal

(Antara Unit Indoor dan Remote Kontrol) ................................... 197 Kesalahan transmisi sinyal

(antara Remote Kontrol UTAMA dan SUB Remote Kontrol) ...... 198 Kelainan Pengaturan bidang ........................................................ 199

7. Pemecahan Masalah untuk Unit Outdoor ............................................ 200 Kekurangan Refrigeran................................................................. 200 Deteksi Tegangan Rendah atau Terlalu Tinggi .......................... 202 Kesalahan transmisi sinyal (pada PCB Unit Outdoor) ................ 204 Tegangan yang Tidak Menentu (Antara Unit Indoor dan Unit

Outdoor) / Fungsi Anti Pembentukan Es (Anti-icing) di Ruangan Lainnya.. 205

Kendali Anti Pembentukan Es (Anti-icing) untuk Unit Indoor ..... 206 Kelainan PCB Unit Outdoor .......................................................... 208 Aktivasi OL (Kompresor kelebihan beban) .................................. 209 Kompresor Terkunci...................................................................... 211 Kipas DC Terkunci ........................................................................ 212 Deteksi arus input berlebih ........................................................... 213 Kendali Suhu Pipa Buang............................................................. 214 Kendali Tekanan Tinggi dalam Pendinginan ............................... 215 Kelainan Sistem Sensor Kompresor ............................................ 216 Kelainan Sensor Posisi ................................................................. 218

SiBE121135_A Pendahuluan

x

CT atau Kelainan terkait .............................................................. 220 Termistor atau Kelainan terkait (Unit Outdoor) ........................... 222 Kenaikan Suhu Panel Listrik ........................................................ 224 Kenaikan Suhu Fin Radiasi .......................................................... 226 Deteksi Kelebihan Arus Output .................................................... 228

8. Pemeriksaan .......................................................................................... 230 Pemeriksaan Tahanan Termistor ................................................. 230 Pemeriksaan Konektor Motor Kipas ............................................ 231 Pemeriksaan Hall IC ..................................................................... 232 Pemeriksaan Kumpaan Katup Ekspansi Elektronik Indoor ........ 232 Pemeriksaan Bentuk Gelombang Catu Daya ............................. 233 Pemeriksaan Katup Ekspansi Elektronik Outdoor ...................... 234 Pemeriksaan Kinerja Katup Empat Arah ..................................... 235 Pemeriksaan Sistem Refrigeran Unit Inverter ............................. 235 Pemeriksaan Penganalisa Inverter .............................................. 236 Pemeriksaan Dorongan rotasi pada PCB Unit Outdoor ............ 237 Pemeriksaan Kondisi Pemasangan ............................................. 238 Pemeriksaan Tekanan Buang ..................................................... 238 Pemeriksaan Sistem Kipas Outdoor ............................................ 239 Pemeriksaan Tegangan Kapasitor............................................... 239 Pemeriksaan Modul Daya ............................................................ 240

Bagian 7 Operasi Uji Coba dan Pengaturan Bidang. ........................................................ 241 1. Operasi Pump Down (Penampungan) .................................................. 242 2. Operasi Paksa........................................................................................ 243 3. Fungsi Pemeriksaan Kesalahan Pengkabelan .................................... 244 4. Operasi Uji coba .................................................................................... 246

Unit Indoor RA ............................................................................... 246 Unit Indoor SA ............................................................................... 248

5. Pengaturan bidang ................................................................................ 250 Unit Outdoor .................................................................................. 250 Unit Indoor RA ............................................................................... 253 Unit Indoor SA ............................................................................... 258

6. Pelumas Silikon pada Transistor Daya / Jembatan Dioda .................. 262 Bagian 8 Lampiran ................................................................................................................... 263

1. Diagram Perpipaan ................................................................................ 264 Unit Outdoor .................................................................................. 264 Unit Indoor ..................................................................................... 269

2. Diagram Pemasangan Kabel ................................................................ 276 Unit Outdoor .................................................................................. 276 Unit Indoor ..................................................................................... 281

3. Prosedur penghapusan (Buku Kecil No.) ............................................. 289

Pendahuluan

SiBE121135_A

xi

1. Pendahuluan

Peringatan Keamanan

Perhatian

dan

Peringatan

Pastikan membaca petunjuk keselamatan berikut sebelum melakukan pekerjaan perbaikan.

Item-item perhatian digolongkan ke dalam “ Peringatan" dan" Perhatian". Item

"Peringatan" sangat penting karena mereka dapat menyebabkan kematian atau cedera

serius jika item diikuti dengan benar. Item "Perhatian" juga dapat menyebabkan

kecelakaan serius dalam beberapa kondisi jika item tersebut tidak diikuti. Oleh karena itu,

pastikan untuk mematuhi semua item perhatian keselamatan yang dijelaskan di bawah ini.

Tentang Piktogram

Simbol ini mengindikasikan item yang harus dilaksanakan dengan hati-hati. Piktogram menunjukkan item yang harus diperhatikan.

Simbol ini mengindikasikan tindakan yang dilarang. Item atau tindakan yang dilarang ditunjukkan dalam ilustrasi atau di dekat simbol.

Simbol ini mengindikasikan tindakan atau petunjuk yang harus dilakukan. Petunjuk tersebut ditunjukkan dalam ilustrasi atau di dekat

simbol.

Setelah pekerjaan perbaikan selesai, pastikan melakukan operasi pengujian untuk

memastikan bahwa peralatan beroperasi secara normal, dan menjelaskan kepada

pelanggan tentang perhatian pengoperasian produk.

Kehati-hatian tentang Keselamatan Pekerja

Peringatan

Peringatan Pastikan mencabut steker kabel listrik dari stopkontak sebelum membongkar peralatan untuk perbaikan. Bekerja pada peralatan yang tersambung ke catu daya dapat menyebabkan sengatan listrik. Jika perlu memasok listrik ke peralatan untuk melakukan perbaikan atau memeriksa sirkuit, jangan menyentuh bagian peralatan yang bermuatan listrik.

Jika refrigeran dibuang selama pekerjaan perbaikan, jangan menyentuh gas refrigeran yang dibuang. Gas refrigeran dapat menyebabkan radang dingin.

Saat melepas pipa hisap atau pembuangan dari kompresor di bagian yang dilas, terlebih dahulu memindahkan gas refrigeran ke tempat yang berventilasi baik. Jika ada gas yang tersisa di dalam kompresor, gas refrigeran atau mesin refrigerasi akan mengeluarkan minyak saat pipa dilepas, dan dapat menyebabkan cedera.

Jika gas refrigeran bocor selama pekerjaan perbaikan, beri ventilasi di area tersebut. Gas refrigeran dapat menghasilkan gas beracun saat melakukan kontak dengan nyala api.

Kapasitor step-up (penaik tegangan) memasok listrik bertegangan tinggi ke komponen listrik unit outdoor. Pastikan untuk mengosongkan kapasitor sepenuhnya sebelum melakukan pekerjaan perbaikan. Kapasitor yang bermuatan dapat menyebabkan sengatan listrik.

Jangan memulai atau menghentikan operasi AC dengan mencolokkan atau mencabut steker kabel listrik. Mencolokkan atau mencabut steker kabel listrik untuk mengoperasikan peralatan tersebut dapat menyebabkan sengatan listrik atau kebakaran.

SiBE121135_A Pendahuluan

viii

Peringatan

Peringatan Pastikan untuk menggunakan helm pengaman, sarung tangan dan sabuk keselamatan saat bekerja di tempat yang tinggi (lebih dari 2 meter) Tindakan keselamatan yang kurang memadai dapat menyebabkan kecelakaan terjatuh.

Untuk model refrigeran R-410A, pastikan menggunakan pipa, mur penyambung dan alat khusus yang digunakan untuk refrigeran R-410A. Penggunaan material untuk model refrigeran R-22 dapat menimbulkan kecelakaan serius, seperti kerusakan siklus refrigeran dan kerusakan peralatan.

Perhatian

Perhatian Jangan memperbaiki komponen listrik dengan tangan basah. Bekerja pada peralatan dengan tangan basah dapat menyebabkan sengatan listrik.

Jangan membersihkan AC dengan cara memercikkan air. Mencuci unit menggunakan air dapat menyebabkan sengatan listrik.

Pastikan melakukan pembumian ketika memperbaiki peralatan di tempat lembab atau basah, untuk menghindari sengatan listrik.

Pastikan mematikan saklar daya dan mencabut kabel listrik saat membersihkan peralatan. Kipas internal berputar dengan kecepatan tinggi, dan menyebabkan cedera.

Pastikan melakukan pekerjaan perbaikan dengan alat yang tepat. Penggunaan alat yang tidak tepat dapat menyebabkan cedera.

Pastikan untuk memeriksa bahwa bagian siklus refrigerasi telah didinginkan dengan cukup sebelum melakukan pekerjaan perbaikan. Bekerja pada unit saat bagian siklus refrigerasi panas dapat menyebabkan luka bakar.

Gunakan las di tempat yang berventilasi baik. Penggunaan las di ruang tertutup dapat menyebabkan kekurangan oksigen.

Pendahuluan

SiBE121135_A

ix

Kehati-hatian tentang Keselamatan Pengguna

Peringatan

Peringatan Pastikan menggunakan komponen yang tercantum dalam daftar komponen servis dari model yang berlaku dan alat yang tepat untuk melakukan pekerjaan perbaikan. Jangan pernah mencoba memodifikasi peralatan. Penggunaan komponen atau alat yang tidak sesuai dapat menyebabkan sengatan listrik, menimbulkan panas berlebih atau kebakaran.

Jika kabel listrik dan kawat timah memiliki goresan atau berubah bentuk, pastikan untuk menggantinya. Kabel dan kawat yang rusak dapat menyebabkan sengatan listrik, menimbulkan panas berlebih atau kebakaran.

Jangan gunakan kabel listrik sambungan atau kabel perpanjangan, atau berbagi stopkontak yang sama dengan peralatan listrik lainnya, karena dapat menyebabkan sengatan listrik, menimbulkan panas berlebih atau kebakaran.

Pastikan menggunakan rangkaian listrik khusus untuk peralatan, dan mengikuti standar teknis setempat terkait dengan peralatan listrik tersebut, peraturan pengkabelan internal, dan panduan petunjuk pemasangan ketika melakukan pekerjaan listrik. Kapasitas rangkaian listrik yang tidak memadai dan pekerjaan listrik yang tidak tepat dapat menyebabkan sengatan listrik atau kebakaran.

Pastikan menggunakan kabel yang ditetapkan untuk pengkabelan antara unit indoor dan outdoor. Membuat sambungan dengan aman dan mengatur jalur kabel dengan benar sehingga tidak ada gaya yang menarik kabel di terminal sambungan. Sambungan yang tidak benar dapat menimbulkan panas berlebih atau kebakaran.

Ketika melakukan pengkabelan antara unit indoor dan outdoor, pastikan penutup terminal tidak terangkat atau turun akibat kabel. Jika penutup tidak terpasang dengan benar, bagian terminal sambungan dapat menyebabkan sengatan listrik, menimbulkan panas berlebih atau kebakaran.

Jangan merusak atau memodifikasi kabel listrik. kabel listrik yang rusak atau dimodifikasi dapat menyebabkan sengatan listrik atau kebakaran. Menempatkan benda berat pada kabel listrik, dan memanasi atau menarik kabel listrik dapat merusak kabel.

Jangan mencampur udara atau gas selain dari refrigeran yang ditentukan (R-410A/R-22) dalam sistem refrigeran. Jika udara memasuki sistem refrigerasi, maka akan menimbulkan tekanan tinggi yang berlebihan, yang menyebabkan kerusakan peralatan dan cedera.

Jika gas refrigeran bocor, pastikan menemukan titik kebocoran dan memperbaikinya sebelum pengisian refrigeran. Setelah pengisian refrigeran, pastikan tidak ada refrigeran yang bocor. Jika titik kebocoran tidak dapat ditemukan dan pekerjaan perbaikan harus dihentikan, pastikan untuk melakukan pump down dan menutup katup servis, untuk mencegah gas refrigeran bocor ke dalam ruangan. Gas refrigeran tidak berbahaya, tetapi dapat menghasilkan gas beracun ketika melakukan kontak dengan nyala api, seperti kipas dan pemanas lainnya, tungku dan kompor.

Saat memindah peralatan, pastikan bahwa tempat instalasi baru memiliki kekuatan yang cukup untuk menahan berat peralatan. Jika tempat instalasi tidak memiliki kekuatan yang cukup dan jika pekerjaan instalasi tidak dilakukan dengan aman, peralatan bisa jatuh dan menyebabkan cedera.

SiBE121135_A Pendahuluan

x

Peringatan

Peringatan Periksa untuk memastikan bahwa steker kabel listrik tidak kotor atau longgar, kemudian masukkan steker ke stopkontak dengan aman. Jika steker berdebu atau sambungannya longgar, dapat menyebabkan sengatan listrik atau kebakaran.

Pastikan memasang produk dengan benar dengan menggunakan kerangka kerja instalasi standar yang diberikan. Penggunaan yang tidak tepat kerangka kerja instalasi dan instatlasi yang tidak tepat dapat menyebabkan peralatan jatuh, yang mengakibatkan cedera.

Untuk tipe kesatuan saja

Pastikan memasang produk secara aman dalam kerangka yang dipasang pada kerangka jendela. Jika unit tidak dipasang secara aman, maka unit bisa jatuh dan menyebabkan cedera.

Untuk tipe kesatuan saja

Ketika mengganti baterai koin di remote kontrol, pastikan membuang baterai lama untuk mencegah agar anak kecil tidak menelannya. Jika anak kecil menelan baterai koin tersebut, segera periksakan ke dokter.

Perhatian

Perhatian Instalasi pemutus kebocoran diperlukan dalam beberapa kasus tergantung pada kondisi tempat instalasi, untuk mencegah sengatan listrik.

Jangan memasang peralatan di tempat yang ada kemungkinan kebocoran gas yang mudah terbakar. Jika gas yang mudah terbakar bocor dan tetap di sekitar unit, hal itu dapat menyebabkan kebakaran.

Periksa untuk melihat apakah komponen dan kabel telah terpasang dan tersambung dengan benar, dan apakah sambungan di terminal telah disolder atau dirapatkan dengan aman. Pemasangan dan sambungan yang tidak tepat dapat menyebabkan timbulnya panas berlebihan, kebakaran atau sengatan listrik.

Jika platform atau rangka pemasangan telah berkarat, maka harus diganti. Platform atau kerangka pemasangan yang berkarat dapat menyebabkan unit jatuh, yang mengakibatkan cedera.

Memeriksa pembumian, dan memperbaikinya jika peralatan tidak dibumikan dengan benar. Pembumian yang tidak tepat dapat menyebabkan sengatan listrik.

Pendahuluan

SiBE121135_A

xi Daftar Fungsi-Fungsi

Perhatian

Perhatian Pastikan mengukur tahanan isolasi setelah perbaikan, dan pastikan bahwa hambatannya sebesar 1 M atau lebih besar. Isolasi yang rusak dapat menyebabkan sengatan listrik.

Pastikan memeriksa drainase unit indoor setelah perbaikan. Drainase yang rusak dapat menyebabkan air memasuki ruangan dan membasahi furnitur dan lantai.

Jangan memiringkan unit saat melepasnya. Air di dalam unit dapat tumpah dan membasahi furnitur dan lantai.

Pastikan untuk memasang kemasan dan segel pada kerangka instalasi dengan benar. Jika kemasan dan segel tidak terpasang dengan benar, air dapat memasuki ruangan dan membasahi furnitur dan lantai.

Untuk tipe kesatuan saja

Ikon yang digunakan Ikon digunakan untuk menarik perhatian pembaca pada informasi khusus. Arti dari masing-

masing ikon dijelaskan dalam tabel di bawah ini:

Ikon Jenis

Informasi Keterangan

Catatan:

Catatan “Catatan” memberikan informasi yang tidak terlalu diperlukan, tetapi mungkin tetap berharga bagi pembaca, seperti tips dan trik.

Perhatian

Perhatian “Perhatian” digunakan ketika ada bahaya bahwa pembaca, melalui manipulasi yang salah, dapat merusak peralatan, hilangnya data, memperoleh hasil yang tak terduga atau harus memulai ulang (sebagian dari) prosedur.

Peringatan

Peringatan "Peringatan" digunakan bila ada bahaya cedera diri.

Referensi “Referensi” memandu pembaca ke tempat-tempat lain di map atau dalam panduan ini, di mana pembaca akan menemukan informasi tambahan tentang suatu topik tertentu.

SiBE121135_A Pendahuluan

Daftar Fungsi-Fungsi

2

Bagian 1

Daftar Fungsi 1. Pendingin Saja ........................................................................................... 2

Unit Outdoor ..................................................................................................2 Unit Indoor ....................................................................................................3

2. Pompa Kalor............................................................................................... 6 Unit Outdoor ..................................................................................................6 Unit Indoor ....................................................................................................8

Pendahuluan

SiBE121135_A

3 Daftar Fungsi-Fungsi

1. Pendingin Saja

Unit Outdoor

Kategori

Fungsi-fungsi

3M

KS

50

E3

V1

B,

4M

KS

58

E3

V1

B

4M

KS

75

F2

V1

B

5M

KS

90

E2

V3

B

Kategori

Fungsi-fungsi

3M

KS

50

E3

V1

B,

4M

KS

58

E3

V1

B

4M

KS

75

F2

V1

B

5M

KS

90

E2

V3

B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) -10 ~46

10 ~46

Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— — Kendali PAM

Penghematan listrik siaga — — Filter pemurni udara fotokatalitik apatit Titanium

— — Kompresor Kompresor gulir oval — —

Kompresor ayun Filter udara (pra filter) — —

Kompresor putar — — Panel datar pembersih — —

Motor DC reluktansi Grille yang dapat dicuci — —

Aliran Udara nyaman

Sirip aliran udara kuat — — Operasi TAHAN JAMUR — —

Sirip ganda aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

Penyebar aliran udara kuat — — Timer Operasi WEEKLY TIMER — —

sirip bersudut lebar — — TIMER ON/OFF 24 jam — —

Ayunan otomatis Vertikal (naik dan turun)

— — Mode NIGHT SET — —

Ayunan otomatis horisontal (kanan dan kiri)

— — Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

— —

Aliran udara 3-D — — Layar (digital, LED) diagnosis sendiri

Operasi ALIRAN UDARA NYAMAN — — Fungsi pemeriksaan kesalahan pengkabelan

Kendali Kenyamanan

Kecepatan kipas otomatis — — Perawatan anti korosi penukar panas outdoor

Operasi senyap unit indoor — — Fleksibilitas Unit indoor kompatibel tipe multi-split

/split — —

Mode senyap MALAM (otomatis) Unit indoor kompatibel H/P, C/O — —

Operasi senyap UNIT OUTDOOR (manual)

Keterhubungan catu daya yang fleksibel — —

Operasi INTELLIGENT EYE 2-area — — Penerapan pada plafon yang tinggi — —

Operasi INTELLIGENT EYE — — Tidak berisi 65 m

Fungsi penghangatan cepat (operasi pra-pemanasan) — — Pipa buang samping (kanan atau

kiri) — —

Fungsi hot-start — — Pemilihan daya — —

Pencairan otomatis — — Remote kontrol

Pengontrol terpusat 5-ruangan

— Operasi Operasi otomatis — —

Operasi kering program — — Adaptor remote kontrol (kontak pulse terbuka normal)

— — Kipas saja — —

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— — Adaptor remote kontrol (kontak terbuka normal) (pilihan)

— —

Operasi Inverter yang KUAT — — DIII-NET yang kompatibel (adaptor) (pilihan)

— —

Pengaturan ruang-Prioritas Pengendali Remote

Nirkabel (pilihan) — —

Kunci Mode SEJUK / PANAS — — Berkabel — —

Operasi MENINGGALKAN RUMAH — — Operasi ECONO — — Tombol [ON/OFF] unit indoor — — Tanda penerimaan sinyal — — R/C dengan cahaya belakang — — Tampilan suhu — —

Catatan: : Ada

— : Tidak ada

Daftar Fungsi-Fungsi

4

Pendingin saja

SiBE121135_A

Unit Indoor

Kategori

Fungsi-fungsi

FT

XS

25

/35

/42

/50

J2

V1

B

FT

XS

60

/71

GV

1B

Kategori

Fungsi-fungsi

FT

XS

25

/35

/42

/50

J2

V1

B

FT

XS

60

/71

GV

1B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) — — Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— — Kendali PAM — —

Penghematan listrik siaga — — Filter pemurni udara fotokatalitik apatit Titanium

Kompresor Kompresor gulir oval — —

Kompresor ayun — — Filter udara (pra filter)

Kompresor putar — — Panel datar pembersih

Motor DC reluktansi — — Grille yang dapat dicuci — —

Aliran Udara nyaman

Sirip aliran udara kuat — — Operasi TAHAN JAMUR — —

Sirip ganda aliran udara kuat Operasi pendinginan tidur nyenyak — —

Penyebar aliran udara kuat — — Timer Operasi WEEKLY TIMER

sirip bersudut lebar TIMER ON/OFF 24 jam

Ayunan otomatis Vertikal (naik dan turun)

Mode NIGHT SET

Ayunan otomatis horisontal (kanan dan kiri)

Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Aliran udara 3-D Layar (digital, LED) diagnosis sendiri

Operasi ALIRAN UDARA NYAMAN Fungsi pemeriksaan kesalahan pengkabelan

— —

Kendali Kenyamanan

Kecepatan kipas otomatis Perawatan anti korosi penukar panas outdoor — —

Operasi senyap unit indoor Fleksibilitas Unit indoor kompatibel tipe multi-split

/split

Mode senyap MALAM (otomatis) — — Unit indoor kompatibel H/P, C/O

Operasi senyap UNIT OUTDOOR (manual)

Keterhubungan catu daya yang fleksibel — —

Operasi INTELLIGENT EYE 2-area — Penerapan pada plafon yang tinggi — —

Operasi INTELLIGENT EYE — Tidak berisi — —

Fungsi penghangatan cepat (operasi pra-pemanasan) — — Pipa buang samping (kanan atau

kiri)

Fungsi hot-start — — Pemilihan daya — —

Pencairan otomatis — — Remote kontrol

Pengontrol terpusat 5-ruangan

Operasi Operasi otomatis — — Adaptor remote kontrol (kontak pulse terbuka normal)

Operasi kering program

Kipas saja Adaptor remote kontrol (kontak terbuka normal) (pilihan)

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— — DIII-NET yang kompatibel (adaptor) (pilihan)

Operasi Inverter yang KUAT Pengendali Remote

Nirkabel

Pengaturan ruang-Prioritas — — Berkabel (pilihan)

Kunci Mode SEJUK / PANAS — — Operasi MENINGGALKAN RUMAH — — Operasi ECONO Tombol [ON/OFF] unit indoor Tanda penerimaan sinyal R/C dengan cahaya belakang — — Tampilan suhu — —

Catatan: : Ada

— : Tidak ada

5 Daftar Fungsi-Fungsi

SiBE121135_A Pendingin saja

Kategori

Fungsi-fungsi

FF

Q2

5/3

5/5

0/6

0B

9V

1B

Kategori

Fungsi-fungsi

FF

Q2

5/3

5/5

0/6

0B

9V

1B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara —

Batas Operasi pendinginan (°CDB) — Filter penghilang bau Fotokatalitik —

Batas Operasi pemanasan (°CWB) — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— Kendali PAM —

Penghematan listrik siaga — Filter pemurni udara fotokatalitik apatit Titanium

— Kompresor Kompresor gulir oval —

Kompresor ayun — Filter tahan lama

Kompresor putar — Panel datar pembersih —

Motor DC reluktansi — Grille yang dapat dicuci

Aliran Udara nyaman

Sirip aliran udara kuat — Indikator pembersih filter

Sirip ganda aliran udara kuat — Panel dekorasi pembersih sendiri (pilihan) —

Penyebar aliran udara kuat — Operasi TAHAN JAMUR —

sirip bersudut lebar — Operasi pendinginan tidur nyenyak —

Ayunan otomatis Vertikal (naik dan turun) Timer

Operasi timer terjadwal

★2

Ayunan otomatis horisontal (kanan dan kiri) — TIMER ON/OFF 72 jam

★1

Aliran udara 3-D — Mode NIGHT SET —

Operasi ALIRAN UDARA NYAMAN — Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Kendali Kenyamanan

Kecepatan kipas otomatis — Layar (digital, LED) diagnosis sendiri

Operasi senyap unit indoor — Fungsi pemeriksaan kesalahan pengkabelan

Mode senyap MALAM (otomatis) — Perawatan anti korosi penukar panas outdoor

Operasi senyap UNIT OUTDOOR (manual) — Fleksibilitas Unit indoor kompatibel tipe multi-split /split

Operasi INTELLIGENT EYE 2-area — Unit indoor kompatibel H/P, C/O

Operasi INTELLIGENT EYE — Keterhubungan catu daya yang fleksibel —

Fungsi penghangatan cepat (operasi pra-pemanasan)

— Penerapan pada plafon yang tinggi —

Fungsi hot-start — Tidak berisi —

Pencairan otomatis — Pipa buang samping (kanan atau kiri)

Operasi Operasi otomatis — Pemilihan daya —

Operasi kering program Remote kontrol

Pengontrol terpusat 5-ruangan —

Kipas saja Adaptor remote kontrol (kontak pulse terbuka normal)

— Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

Operasi Inverter yang KUAT — Adaptor remote kontrol (kontak terbuka normal) (pilihan) —

Pengaturan ruang-Prioritas — DIII-NET yang kompatibel (adaptor) (pilihan)

Kunci Mode SEJUK / PANAS — Pengendali Remote

Nirkabel (pilihan)

Operasi MENINGGALKAN RUMAH — Berkabel (pilihan)

Operasi ECONO —

Tombol [ON/OFF] unit indoor

★1

Tanda penerimaan sinyal

★1

Tampilan suhu — Catatan: : Ada

— : Tidak ada

★1:

★2:

dengan remote kontrol nirkabel

dengan remote kontrol kabel

Daftar Fungsi-Fungsi

6

Pendingin saja

SiBE121135_A

Kategori

Fungsi-fungsi

FH

Q3

5/5

0/6

0B

WV

1B

FD

BQ

25

B8

V1

F

BQ

35

/50

/60

C8

VE

B

Kategori

Fungsi-fungsi

FH

Q3

5/5

0/6

0B

WV

1B

FD

BQ

25

B8

V1

F

BQ

35

/50

/60

C8

VE

B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) — — Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— — Kendali PAM — —

Penghematan listrik siaga — — Filter pemurni udara fotokatalitik apatit Titanium

— Kompresor Kompresor gulir oval — —

Kompresor ayun — — Filter tahan lama

Kompresor putar — — Panel datar pembersih — —

Motor DC reluktansi — — Grille yang dapat dicuci —

Aliran Udara nyaman

Sirip aliran udara kuat — — Indikator pembersih filter

Sirip ganda aliran udara kuat — — Panel dekorasi pembersih sendiri (pilihan)

— —

Penyebar aliran udara kuat — — Operasi TAHAN JAMUR — —

sirip bersudut lebar — — Operasi pendinginan tidur nyenyak — —

Ayunan otomatis Vertikal (naik dan turun)

— Timer

Operasi timer terjadwal

★2

★2

Ayunan otomatis horisontal (kanan dan kiri)

— — TIMER ON/OFF 72 jam

★1 —

Aliran udara 3-D — — Mode NIGHT SET — —

Operasi ALIRAN UDARA NYAMAN — — Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Kendali Kenyamanan

Kecepatan kipas otomatis — — Layar (digital, LED) diagnosis sendiri

Operasi senyap unit indoor — — Fungsi pemeriksaan kesalahan pengkabelan

— —

Mode senyap MALAM (otomatis) — — Perawatan anti korosi penukar panas outdoor — —

Operasi senyap UNIT OUTDOOR (manual) — —

Fleksibilitas Unit indoor kompatibel tipe multi-split /split

Operasi INTELLIGENT EYE 2-area — — Unit indoor kompatibel H/P, C/O

Operasi INTELLIGENT EYE — — Keterhubungan catu daya yang fleksibel — —

Fungsi penghangatan cepat (operasi pra-pemanasan)

— — Penerapan pada plafon yang tinggi —

Fungsi hot-start — — Tidak berisi — —

Pencairan otomatis — — Pipa buang samping (kanan atau kiri)

— —

Operasi Operasi otomatis — — Pemilihan daya — —

Operasi kering program Remote kontrol

Pengontrol terpusat 5-ruangan — —

Kipas saja Adaptor remote kontrol (kontak pulse terbuka normal)

— Kenyamanan

Gaya Hidup Operasi KUAT (POWERFUL) yang baru (non-inverter)

— —

Operasi Inverter yang KUAT — — Adaptor remote kontrol (kontak terbuka normal) (pilihan)

— —

Pengaturan ruang-Prioritas — — DIII-NET yang kompatibel (adaptor) (pilihan)

Kunci Mode SEJUK / PANAS — — Pengendali Remote

Nirkabel (pilihan) —

Operasi MENINGGALKAN RUMAH — — Berkabel (pilihan)

Operasi ECONO — —

Tombol [ON/OFF] unit indoor

★1 —

Tanda penerimaan sinyal

★1 —

Tampilan suhu — — Catatan: : Ada

— : Tidak ada

★1:

★2:

dengan remote kontrol nirkabel

dengan remote kontrol kabel

7 Daftar Fungsi-Fungsi

SiBE121135_A Pompa panas

2. Pompa Kalor

Unit Outdoor

Kategori

Fungsi-fungsi

3M

XS

40

K2

V1

B,

3M

XS

40

K3

V1

B

3M

XS

52

E3

V1

B,

3M

XS

52

E4

V1

B

3M

XS

68

G2

V1

B,

3M

XS

68

G3

V1

B

4M

XS

68

F2

V1

B,

4M

XS

68

F3

V1

B

Kategori

Fungsi-fungsi

3M

XS

40

K2

V1

B,

3M

XS

40

K3

V1

B

3M

XS

52

E3

V1

B,

3M

XS

52

E4

V1

B

3M

XS

68

G2

V1

B,

3M

XS

68

G3

V1

B

4M

XS

68

F2

V1

B,

4M

XS

68

F3

V1

B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) –10 ~46

–10 ~46 Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) –15 ~15,5

–15 ~15,5

Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— —

Kendali PAM Filter pemurni udara fotokatalitik apatit Titanium — —

Penghematan listrik siaga — —

Kompresor Kompresor gulir oval — — Filter udara (pra filter) — —

Kompresor ayun Panel datar pembersih — —

Kompresor putar — — Grille yang dapat dicuci — —

Motor DC reluktansi Operasi TAHAN JAMUR — —

Aliran Udara nyaman

Sirip aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

Sirip ganda aliran udara kuat — — Timer Operasi WEEKLY TIMER — —

Penyebar aliran udara kuat — — TIMER ON/OFF 24 jam — —

sirip bersudut lebar — — Mode NIGHT SET — —

Ayunan otomatis Vertikal (naik dan turun)

— — Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

— —

Ayunan otomatis horisontal (kanan dan kiri)

— — Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D — — Fungsi pemeriksaan kesalahan pengkabelan

Operasi ALIRAN UDARA NYAMAN — — Perawatan anti korosi penukar panas outdoor

Kendali Kenyamanan

Kecepatan kipas otomatis — — Fleksibilitas Unit indoor kompatibel tipe multi-split

/split — —

Operasi senyap unit indoor — — Unit indoor kompatibel H/P, C/O — —

Mode senyap MALAM (otomatis) Keterhubungan catu daya yang fleksibel — —

Operasi senyap UNIT OUTDOOR (manual)

Penerapan pada plafon yang tinggi — —

Operasi INTELLIGENT EYE 2-area — — Tidak berisi 30 m 30 m

Operasi INTELLIGENT EYE — — Pipa buang samping (kanan atau kiri)

— —

Fungsi penghangatan cepat (operasi pra-pemanasan)

Pemilihan daya — —

Fungsi hot-start — — Remote kontrol

Pengontrol terpusat 5-ruangan

— Pencairan otomatis

Operasi Operasi otomatis — — Adaptor remote kontrol (kontak pulse terbuka normal)

— — Operasi kering program — —

Kipas saja — — Adaptor remote kontrol (kontak terbuka normal) (pilihan)

— Kenyamanan

Gaya Hidup Operasi KUAT (POWERFUL) yang baru (non-inverter) — —

Operasi Inverter yang KUAT — — DIII-NET yang kompatibel (adaptor) (pilihan)

— —

Pengaturan ruang-Prioritas Pengendali Remote

Nirkabel (pilihan) — —

Kunci Mode SEJUK / PANAS Berkabel — —

Operasi MENINGGALKAN RUMAH — — Operasi ECONO — — Tombol [ON/OFF] unit indoor — — Tanda penerimaan sinyal — — R/C dengan cahaya belakang — — Tampilan suhu — —

Catatan: : Ada

— : Tidak ada

Daftar Fungsi-Fungsi

8

Pompa panas

SiBE121135_A

Kategori

Fungsi-fungsi

4M

XS

80

E2

V3

B,

4M

XS

80

E3

V3

B

5M

XS

90

E2

V3

B,

5M

XS

90

E3

V3

B

3A

MX

52

E3

V1

B,

3A

MX

52

E4

V1

B

Kategori

Fungsi-fungsi

4M

XS

80

E2

V3

B,

4M

XS

80

E3

V3

B

5M

XS

90

E2

V3

B,

5M

XS

90

E3

V3

B

3A

MX

52

E3

V1

B,

3A

MX

52

E4

V1

B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) –10 ~46

–10 ~46

Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) –15 ~15,5

–15 ~15,5

Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— —

Kendali PAM Filter pemurni udara fotokatalitik apatit Titanium

— — Penghematan listrik siaga — —

Kompresor Kompresor gulir oval — — Filter udara (pra filter) — —

Kompresor ayun Panel datar pembersih — —

Kompresor putar — — Grille yang dapat dicuci — —

Motor DC reluktansi Operasi TAHAN JAMUR — —

Aliran Udara nyaman

Sirip aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

Sirip ganda aliran udara kuat — — Timer Operasi WEEKLY TIMER — —

Penyebar aliran udara kuat — — TIMER ON/OFF 24 jam — —

sirip bersudut lebar — — Mode NIGHT SET — —

Ayunan otomatis Vertikal (naik dan turun)

— — Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

— —

Ayunan otomatis horisontal (kanan dan kiri)

— — Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D — — Fungsi pemeriksaan kesalahan pengkabelan

Operasi ALIRAN UDARA NYAMAN — — Perawatan anti korosi penukar panas outdoor

Kendali Kenyamanan

Kecepatan kipas otomatis — — Fleksibilitas Unit indoor kompatibel tipe multi-split

/split — —

Operasi senyap unit indoor — — Unit indoor kompatibel H/P, C/O — —

Mode senyap MALAM (otomatis) Keterhubungan catu daya yang fleksibel — —

Operasi senyap UNIT OUTDOOR (manual) Penerapan pada plafon yang tinggi — —

Operasi INTELLIGENT EYE 2-area — — Tidak berisi 30 m 30 m

Operasi INTELLIGENT EYE — — Pipa buang samping (kanan atau kiri)

— —

Fungsi penghangatan cepat (operasi pra-pemanasan)

Pemilihan daya — —

Fungsi hot-start — — Remote kontrol

Pengontrol terpusat 5-ruangan

— Pencairan otomatis

Operasi Operasi otomatis — — Adaptor remote kontrol (kontak pulse terbuka normal)

— Operasi kering program — —

Kipas saja — — Adaptor remote kontrol (kontak terbuka normal) (pilihan)

— Kenyamanan

Gaya Hidup Operasi KUAT (POWERFUL) yang baru (non-inverter)

— —

Operasi Inverter yang KUAT — — DIII-NET yang kompatibel (adaptor) (pilihan)

— —

Pengaturan ruang-Prioritas Pengendali Remote

Nirkabel (pilihan) — —

Kunci Mode SEJUK / PANAS Berkabel — —

Operasi MENINGGALKAN RUMAH — — Operasi ECONO — — Tombol [ON/OFF] unit indoor — — Tanda penerimaan sinyal — — R/C dengan cahaya belakang — — Tampilan suhu — —

Catatan: : Ada

— : Tidak ada

9 Daftar Fungsi-Fungsi

SiBE121135_A Pompa panas

Unit Indoor

Kategori

Fungsi-fungsi

FT

XG

25

/35

/50

JV

1B

W(A

)

Kategori

Fungsi-fungsi

FT

XG

25

/35

/50

JV

1B

W(A

)

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara —

Batas Operasi pendinginan (°CDB) — Filter penghilang bau Fotokatalitik —

Batas Operasi pemanasan (°CWB) — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik —

Kendali PAM — Filter pemurni udara fotokatalitik apatit Titanium

Penghematan listrik siaga —

Kompresor Kompresor gulir oval — Filter udara (pra filter)

Kompresor ayun — Panel datar pembersih

Kompresor putar — Grille yang dapat dicuci —

Motor DC reluktansi — Operasi TAHAN JAMUR —

Aliran Udara nyaman

Sirip aliran udara kuat — Operasi pendinginan tidur nyenyak —

Sirip ganda aliran udara kuat Timer Operasi WEEKLY TIMER

Penyebar aliran udara kuat — TIMER ON/OFF 24 jam

sirip bersudut lebar Mode NIGHT SET

Ayunan otomatis Vertikal (naik dan turun) Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Ayunan otomatis horisontal (kanan dan kiri) — Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D — Fungsi pemeriksaan kesalahan pengkabelan

Operasi ALIRAN UDARA NYAMAN Perawatan anti korosi penukar panas outdoor

— Kendali Kenyamanan

Kecepatan kipas otomatis

Operasi senyap unit indoor Fleksibilitas Unit indoor kompatibel tipe multi-split /split

Mode senyap MALAM (otomatis) —

Operasi senyap UNIT OUTDOOR (manual) Unit indoor kompatibel H/P, C/O —

Operasi INTELLIGENT EYE Keterhubungan catu daya yang fleksibel —

Operasi INTELLIGENT EYE 2-area — Penerapan pada plafon yang tinggi —

Fungsi penghangatan cepat (operasi pra-pemanasan)

— Tidak berisi —

Fungsi hot-start Pipa buang samping (kanan atau kiri)

Pencairan otomatis — Pemilihan daya —

Operasi Operasi otomatis Remote kontrol Pengontrol terpusat 5-ruangan

Operasi kering program

Kipas saja Adaptor remote kontrol (kontak pulse terbuka normal)

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— Adaptor remote kontrol (kontak terbuka normal) (pilihan)

Operasi Inverter yang KUAT DIII-NET yang kompatibel (adaptor) (pilihan)

Pengaturan ruang-Prioritas — Pengendali Remote

Nirkabel

Kunci Mode SEJUK / PANAS — Berkabel (pilihan)

Operasi MENINGGALKAN RUMAH — Operasi ECONO Tombol [ON/OFF] unit indoor Tanda penerimaan sinyal Lampu indikator multi warna (lampu multi-monitor)

R/C dengan cahaya belakang Tampilan suhu —

Catatan: : Ada

— : Tidak ada

Daftar Fungsi-Fungsi

10

Pompa panas

SiBE121135_A

Kategori

Fungsi-fungsi

CT

XS

15

/35

K2

V1

B

FT

XS

20

/25

K2

V1

B

FT

XS

35

/42

/50

K2

V1

B

Kategori

Fungsi-fungsi

CT

XS

15

/35

K2

V1

B

FT

XS

20

/25

K2

V1

B

FT

XS

35

/42

/50

K2

V1

B

Fungsi Dasar Inverter (dengan kendali daya inverter)

Kesehatan & Kebersihan

Filter pemurni udara — — —

Batas Operasi pendinginan (°CDB)

— — — Filter penghilang bau Fotokatalitik — — —

Batas Operasi pemanasan (°CWB)

Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

Kendali PAM — — — Filter pemurni udara fotokatalitik apatit Titanium

Penghematan listrik siaga — — —

Kompresor Kompresor gulir oval — — — Filter udara (pra filter)

Kompresor ayun — — — Panel datar pembersih

Kompresor putar — — — Grille yang dapat dicuci — — —

Motor DC reluktansi — — — Operasi TAHAN JAMUR — — —

Aliran Udara nyaman

Sirip aliran udara kuat — Operasi pendinginan tidur nyenyak

— — —

Sirip ganda aliran udara kuat — — Timer Operasi WEEKLY TIMER

Penyebar aliran udara kuat — — — TIMER ON/OFF 24 jam

sirip bersudut lebar Mode NIGHT SET

Ayunan otomatis Vertikal (naik dan turun)

Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Ayunan otomatis horisontal (kanan dan kiri)

— — Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D — — Fungsi pemeriksaan kesalahan pengkabelan

— — —

Operasi ALIRAN UDARA NYAMAN

Perawatan anti korosi penukar panas outdoor

— Kendali Kenyamanan

Kecepatan kipas otomatis

Operasi senyap unit indoor Fleksibilitas Unit indoor kompatibel tipe multi-split /split

Mode senyap MALAM (otomatis) — —

Operasi senyap UNIT OUTDOOR (manual) Unit indoor kompatibel H/P, C/O — — —

Operasi INTELLIGENT EYE — Keterhubungan catu daya yang fleksibel — — —

Operasi INTELLIGENT EYE 2-area — — Penerapan pada plafon yang

tinggi — — —

Fungsi penghangatan cepat (operasi pra-pemanasan)

— — — Tidak berisi — — —

Fungsi hot-start Pipa buang samping (kanan atau kiri)

Pencairan otomatis — — — Pemilihan daya — — —

Operasi Operasi otomatis Remote kontrol

Pengontrol terpusat 5-ruangan

Operasi kering program

Kipas saja Adaptor remote kontrol (kontak pulse terbuka normal)

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— — — Adaptor remote kontrol (kontak terbuka normal) (pilihan)

Operasi Inverter yang KUAT DIII-NET yang kompatibel (adaptor) (pilihan)

Pengaturan ruang-Prioritas — — — Pengendali Remote

Nirkabel

Kunci Mode SEJUK / PANAS — — — Berkabel (pilihan)

Operasi MENINGGALKAN RUMAH

— — — Operasi ECONO Tombol [ON/OFF] unit indoor Tanda penerimaan sinyal Lampu indikator multi warna (lampu multi-monitor)

— — —

R/C dengan cahaya belakang Tampilan suhu — — —

Catatan: : Ada

— : Tidak ada

11

Daftar Fungsi-Fungsi

SiBE121135_A Pompa panas

Kategori

Fungsi-fungsi

FT

XS

25

/35

/42

/50

J2

V1

B

FT

XS

60

/71

GV

1B

Kategori

Fungsi-fungsi

FT

XS

25

/35

/42

/50

J2

V1

B

FT

XS

60

/71

GV

1B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) — — Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— —

Kendali PAM — — Filter pemurni udara fotokatalitik apatit Titanium

Penghematan listrik siaga — —

Kompresor Kompresor gulir oval — — Filter udara (pra filter)

Kompresor ayun — — Panel datar pembersih

Kompresor putar — — Grille yang dapat dicuci — —

Motor DC reluktansi — — Operasi TAHAN JAMUR — —

Aliran Udara nyaman

Sirip aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

Sirip ganda aliran udara kuat Timer Operasi WEEKLY TIMER

Penyebar aliran udara kuat — — TIMER ON/OFF 24 jam

sirip bersudut lebar Mode NIGHT SET

Ayunan otomatis Vertikal (naik dan turun)

Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Ayunan otomatis horisontal (kanan dan kiri)

Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D Fungsi pemeriksaan kesalahan pengkabelan

— —

Operasi ALIRAN UDARA NYAMAN Perawatan anti korosi penukar panas outdoor — —

Kendali Kenyamanan

Kecepatan kipas otomatis Fleksibilitas Unit indoor kompatibel tipe multi-split

/split

Operasi senyap unit indoor Unit indoor kompatibel H/P, C/O

Mode senyap MALAM (otomatis) — — Keterhubungan catu daya yang fleksibel — —

Operasi senyap UNIT OUTDOOR (manual)

Penerapan pada plafon yang tinggi — —

Operasi INTELLIGENT EYE 2-area — Tidak berisi — —

Operasi INTELLIGENT EYE — Pipa buang samping (kanan atau kiri)

Fungsi penghangatan cepat (operasi pra-pemanasan)

— — Pemilihan daya — —

Fungsi hot-start Remote kontrol

Pengontrol terpusat 5-ruangan

Pencairan otomatis — —

Operasi Operasi otomatis Adaptor remote kontrol (kontak pulse terbuka normal)

Operasi kering program

Kipas saja Adaptor remote kontrol (kontak terbuka normal) (pilihan)

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— — DIII-NET yang kompatibel (adaptor) (pilihan)

Operasi Inverter yang KUAT Pengendali Remote

Nirkabel

Pengaturan ruang-Prioritas — — Berkabel (pilihan)

Kunci Mode SEJUK / PANAS — — Operasi MENINGGALKAN RUMAH — — Operasi ECONO Tombol [ON/OFF] unit indoor Tanda penerimaan sinyal Lampu indikator multi warna (lampu multi-monitor) — —

R/C dengan cahaya belakang — — Tampilan suhu — —

Catatan: : Ada

— : Tidak ada

Daftar Fungsi-Fungsi

12

Pompa panas

SiBE121135_A

Kategori

Fungsi-fungsi

AT

XS

20

/25

/35

/42

/50

G2

V1

B

Kategori

Fungsi-fungsi

AT

XS

20

/25

/35

/42

/50

G2

V1

B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara —

Batas Operasi pendinginan (°CDB) — Filter penghilang bau Fotokatalitik —

Batas Operasi pemanasan (°CWB) — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

Kendali PAM — Filter pemurni udara fotokatalitik apatit Titanium

Penghematan listrik siaga —

Kompresor Kompresor gulir oval — Filter udara (pra filter)

Kompresor ayun — Panel datar pembersih

Kompresor putar — Grille yang dapat dicuci —

Motor DC reluktansi — Operasi TAHAN JAMUR —

Aliran Udara nyaman

Sirip aliran udara kuat — Operasi pendinginan tidur nyenyak —

Sirip ganda aliran udara kuat Timer Operasi WEEKLY TIMER —

Penyebar aliran udara kuat — TIMER ON/OFF 24 jam

sirip bersudut lebar Mode NIGHT SET

Ayunan otomatis Vertikal (naik dan turun) Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Ayunan otomatis horisontal (kanan dan kiri) Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D Fungsi pemeriksaan kesalahan pengkabelan

Operasi ALIRAN UDARA NYAMAN Perawatan anti korosi penukar panas outdoor —

Kendali Kenyamanan

Kecepatan kipas otomatis Fleksibilitas Unit indoor kompatibel tipe multi-split /split

Operasi senyap unit indoor Unit indoor kompatibel H/P, C/O —

Mode senyap MALAM (otomatis) — Keterhubungan catu daya yang fleksibel —

Operasi senyap UNIT OUTDOOR (manual) Penerapan pada plafon yang tinggi —

Operasi INTELLIGENT EYE 2-area — Tidak berisi —

Operasi INTELLIGENT EYE Pipa buang samping (kanan atau kiri)

Fungsi penghangatan cepat (operasi pra-pemanasan)

— Pemilihan daya —

Fungsi hot-start Remote kontrol

Pengontrol terpusat 5-ruangan

Pencairan otomatis —

Operasi Operasi otomatis Adaptor remote kontrol (kontak pulse terbuka normal)

Operasi kering program

Kipas saja Adaptor remote kontrol (kontak terbuka normal) (pilihan)

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— DIII-NET yang kompatibel (adaptor) (pilihan)

Operasi Inverter yang KUAT Pengendali Remote

Nirkabel

Pengaturan ruang-Prioritas — Berkabel (pilihan)

Kunci Mode SEJUK / PANAS — Operasi MENINGGALKAN RUMAH — Operasi ECONO Tombol [ON/OFF] unit indoor Tanda penerimaan sinyal Tampilan suhu —

Catatan: : Ada

— : Tidak ada

13

Daftar Fungsi-Fungsi

SiBE121135_A Pompa panas

Kategori

Fungsi-fungsi

FV

XG

25

/35

/50

K2

V1

B

FV

XS

25

/35

/50

FV

1B

Kategori

Fungsi-fungsi

FV

XG

25

/35

/50

K2

V1

B

FV

XS

25

/35

/50

FV

1B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) — — Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— —

Kendali PAM — — Filter pemurni udara fotokatalitik apatit Titanium

Penghematan listrik siaga — —

Kompresor Kompresor gulir oval — — Filter udara (pra filter)

Kompresor ayun — — Panel datar pembersih —

Kompresor putar — — Grille yang dapat dicuci — —

Motor DC reluktansi — — Operasi TAHAN JAMUR — —

Aliran Udara nyaman

Sirip aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

Sirip ganda aliran udara kuat — — Timer Operasi WEEKLY TIMER

Penyebar aliran udara kuat — — TIMER ON/OFF 24 jam

sirip bersudut lebar Mode NIGHT SET

Ayunan otomatis Vertikal (naik dan turun)

Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Ayunan otomatis horisontal (kanan dan kiri)

— — Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D — — Fungsi pemeriksaan kesalahan pengkabelan

— —

Operasi ALIRAN UDARA NYAMAN — — Perawatan anti korosi penukar panas outdoor — —

Kendali Kenyamanan

Kecepatan kipas otomatis Fleksibilitas Unit indoor kompatibel tipe multi-split

/split

Operasi senyap unit indoor Unit indoor kompatibel H/P, C/O —

Mode senyap MALAM (otomatis) — — Keterhubungan catu daya yang fleksibel — —

Operasi senyap UNIT OUTDOOR (manual)

Penerapan pada plafon yang tinggi — —

Operasi INTELLIGENT EYE 2-area — — Tidak berisi — —

Operasi INTELLIGENT EYE — — Pipa buang samping (kanan atau kiri)

— —

Fungsi penghangatan cepat (operasi pra-pemanasan)

— — Pemilihan daya — —

Fungsi hot-start Remote kontrol

Pengontrol terpusat 5-ruangan

Pencairan otomatis — — Adaptor Remote kontrol (kontak pulse terbuka normal) (pilihan)

Operasi Operasi otomatis

Adaptor remote kontrol (kontak terbuka normal) (pilihan)

Operasi RADIANT — DIII-NET yang kompatibel (adaptor) (pilihan)

Operasi kering program Pengendali Remote

Nirkabel

Kipas saja Berkabel (pilihan) —

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— —

Operasi Inverter yang KUAT Pengaturan ruang-Prioritas — — Kunci Mode SEJUK / PANAS — — Operasi MENINGGALKAN RUMAH — — Operasi ECONO Tombol [ON/OFF] unit indoor Tanda penerimaan sinyal Lampu indikator multi warna (lampu multi-monitor) — —

R/C dengan cahaya belakang Tampilan suhu — —

Catatan: : Ada

— : Tidak ada

Daftar Fungsi-Fungsi

14

Pompa panas

SiBE121135_A

Kategori

Fungsi-fungsi

FL

XS

25

/35

/50

/60

BA

VM

B

FD

XS

25

/35

E7

VM

B

FD

XS

50

/60

C7

VM

B

Kategori

Fungsi-fungsi

FL

XS

25

/35

/50

/60

BA

VM

B

FD

XS

25

/35

E7

VM

B

FD

XS

50

/60

C7

VM

B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara —

Batas Operasi pendinginan (°CDB) — — Filter penghilang bau Fotokatalitik —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— —

Kendali PAM — — Filter pemurni udara fotokatalitik apatit Titanium — —

Penghematan listrik siaga — —

Kompresor Kompresor gulir oval — — Filter udara (pra filter)

Kompresor ayun — — Panel datar pembersih — —

Kompresor putar — — Grille yang dapat dicuci — —

Motor DC reluktansi — — Operasi TAHAN JAMUR — —

Aliran Udara nyaman

Sirip aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

Sirip ganda aliran udara kuat — — Timer Operasi WEEKLY TIMER — —

Penyebar aliran udara kuat — — TIMER ON/OFF 24 jam

sirip bersudut lebar — — Mode NIGHT SET

Ayunan otomatis Vertikal (naik dan turun)

— Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Ayunan otomatis horisontal (kanan dan kiri)

— — Layar (digital, LED) diagnosis sendiri

Aliran udara 3-D — — Fungsi pemeriksaan kesalahan pengkabelan

— —

Operasi ALIRAN UDARA NYAMAN — — Perawatan anti korosi penukar panas outdoor

— —

Kendali Kenyamanan

Kecepatan kipas otomatis Fleksibilitas Unit indoor kompatibel tipe multi-split

/split

Operasi senyap unit indoor Unit indoor kompatibel H/P, C/O — —

Mode senyap MALAM (otomatis) — — Keterhubungan catu daya yang fleksibel

Operasi senyap UNIT OUTDOOR (manual) Penerapan pada plafon yang tinggi — —

Operasi INTELLIGENT EYE 2-area — — Tidak berisi — —

Operasi INTELLIGENT EYE — — Pipa buang samping (kanan atau kiri)

— —

Fungsi penghangatan cepat (operasi pra-pemanasan)

— — Pemilihan daya — —

Fungsi hot-start Remote kontrol

Pengontrol terpusat 5-ruangan

Pencairan otomatis — —

Operasi Operasi otomatis Adaptor remote kontrol (kontak pulse terbuka normal)

Operasi kering program

Kipas saja Adaptor remote kontrol (kontak terbuka normal) (pilihan)

Kenyamanan

Gaya Hidup Operasi KUAT (POWERFUL) yang baru (non-inverter)

— —

Operasi Inverter yang KUAT DIII-NET yang kompatibel (adaptor) (pilihan)

Pengaturan ruang-Prioritas — — Pengendali Remote

Nirkabel

Kunci Mode SEJUK / PANAS — — Berkabel (pilihan) —

Operasi MENINGGALKAN RUMAH Operasi ECONO — — Tombol [ON/OFF] unit indoor Tanda penerimaan sinyal Lampu indikator multi warna (lampu multi-monitor)

— —

R/C dengan cahaya belakang — — Tampilan suhu — —

Catatan: : Ada

— : Tidak ada

15

Daftar Fungsi-Fungsi

SiBE121135_A Pompa panas

Kategori

Fungsi-fungsi

FC

QG

35

/50

/60

FV

EB

FF

Q2

5/3

5/5

0/6

0B

9V

1B

Kategori

Fungsi-fungsi

FC

QG

35

/50

/60

FV

EB

FF

Q2

5/3

5/5

0/6

0B

9V

1B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) — — Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— —

Kendali PAM — — Filter pemurni udara fotokatalitik apatit Titanium

— Penghematan listrik siaga — —

Kompresor Kompresor gulir oval — — Filter tahan lama

Kompresor ayun — — Panel datar pembersih — —

Kompresor putar — — Grille yang dapat dicuci

Motor DC reluktansi — — Indikator pembersih filter

Aliran Udara nyaman

Sirip aliran udara kuat — — Panel dekorasi pembersih sendiri (pilihan)

Sirip ganda aliran udara kuat — — Operasi TAHAN JAMUR — —

Penyebar aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

sirip bersudut lebar — — Timer

Operasi timer terjadwal

★2

★2

Ayunan otomatis Vertikal (naik dan turun)

TIMER ON/OFF 72 jam

★1

★1

Ayunan otomatis horisontal (kanan dan kiri)

— — Mode NIGHT SET — —

Aliran udara 3-D — — Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Operasi ALIRAN UDARA NYAMAN — — Layar (digital, LED) diagnosis sendiri

Kendali Kenyamanan

Kecepatan kipas otomatis — — Fungsi pemeriksaan kesalahan pengkabelan

— —

Operasi senyap unit indoor — — Perawatan anti korosi penukar panas outdoor — —

Mode senyap MALAM (otomatis) — — Fleksibilitas Unit indoor kompatibel tipe multi-split

/split

Operasi senyap UNIT OUTDOOR (manual) — — Unit indoor kompatibel H/P, C/O

Operasi INTELLIGENT EYE 2-area — — Keterhubungan catu daya yang fleksibel — —

Operasi INTELLIGENT EYE — — Penerapan pada plafon yang tinggi — —

Fungsi penghangatan cepat (operasi pra-pemanasan)

— — Tidak berisi — —

Fungsi hot-start Pipa buang samping (kanan atau kiri)

— —

Pencairan otomatis — — Pemilihan daya — —

Operasi Operasi otomatis Remote kontrol

Pengontrol terpusat 5-ruangan — —

Operasi kering program Adaptor remote kontrol (kontak pulse terbuka normal)

— Kipas saja

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— — Adaptor remote kontrol (kontak terbuka normal) (pilihan)

— —

Operasi Inverter yang KUAT — — DIII-NET yang kompatibel (adaptor) (pilihan)

Pengaturan ruang-Prioritas — — Pengendali Remote

Nirkabel (pilihan)

Kunci Mode SEJUK / PANAS — — Berkabel (pilihan)

Operasi MENINGGALKAN RUMAH — — Operasi ECONO — —

Tombol [ON/OFF] unit indoor

★1

★1

Tanda penerimaan sinyal

★1

★1

Tampilan suhu — — Catatan: : Ada

— : Tidak ada

★1:

★2:

dengan remote kontrol nirkabel

dengan remote kontrol kabel

SiBE121135_A

Spesifikasi 16

Kategori

Fungsi-fungsi

FH

Q3

5/5

0/6

0B

WV

1B

FD

BQ

25

B8

V1

F

BQ

35

/50

/60

C8

VE

B

Kategori

Fungsi-fungsi

FH

Q3

5/5

0/6

0B

WV

1B

FD

BQ

25

B8

V1

F

BQ

35

/50

/60

C8

VE

B

Fungsi Dasar Inverter (dengan kendali daya inverter) Kesehatan & Kebersihan

Filter pemurni udara — —

Batas Operasi pendinginan (°CDB) — — Filter penghilang bau Fotokatalitik — —

Batas Operasi pemanasan (°CWB) — — Filter pemurni udara dengan fungsi penghilang bau fotokatalitik

— —

Kendali PAM — — Filter pemurni udara fotokatalitik apatit Titanium

— — Penghematan listrik siaga — —

Kompresor Kompresor gulir oval — — Filter tahan lama

Kompresor ayun — — Panel datar pembersih — —

Kompresor putar — — Grille yang dapat dicuci —

Motor DC reluktansi — — Indikator pembersih filter

Aliran Udara nyaman

Sirip aliran udara kuat — — Panel dekorasi pembersih sendiri (pilihan)

— —

Sirip ganda aliran udara kuat — — Operasi TAHAN JAMUR — —

Penyebar aliran udara kuat — — Operasi pendinginan tidur nyenyak — —

sirip bersudut lebar — — Timer

Operasi timer terjadwal

★2

Ayunan otomatis Vertikal (naik dan turun)

— TIMER ON/OFF 72 jam

★1 —

Ayunan otomatis horisontal (kanan dan kiri)

— — Mode NIGHT SET — —

Aliran udara 3-D — — Bebas khawatir (Keandalan & Daya tahan)

Memulai kembali otomatis (setelah listrik mati)

Operasi ALIRAN UDARA NYAMAN — — Layar (digital, LED) diagnosis sendiri

Kendali Kenyamanan

Kecepatan kipas otomatis — — Fungsi pemeriksaan kesalahan pengkabelan

— —

Operasi senyap unit indoor — — Perawatan anti korosi penukar panas outdoor

— —

Mode senyap MALAM (otomatis) — — Fleksibilitas Unit indoor kompatibel tipe multi-split

/split

Operasi senyap UNIT OUTDOOR (manual)

— — Unit indoor kompatibel H/P, C/O

Operasi INTELLIGENT EYE 2-area — — Keterhubungan catu daya yang fleksibel — —

Operasi INTELLIGENT EYE — — Penerapan pada plafon yang tinggi —

Fungsi penghangatan cepat (operasi pra-pemanasan) — — Tidak berisi — —

Fungsi hot-start Pipa buang samping (kanan atau kiri)

— —

Pencairan otomatis — — Pemilihan daya — —

Operasi Operasi otomatis Remote kontrol

Pengontrol terpusat 5-ruangan — —

Operasi kering program Adaptor remote kontrol (kontak pulse terbuka normal)

— — Kipas saja

Kenyamanan Gaya Hidup

Operasi KUAT (POWERFUL) yang baru (non-inverter)

— — Adaptor remote kontrol (kontak terbuka normal) (pilihan)

— —

Operasi Inverter yang KUAT — — DIII-NET yang kompatibel (adaptor) (pilihan)

Pengaturan ruang-Prioritas — — Pengendali Remote

Nirkabel (pilihan) —

Kunci Mode SEJUK / PANAS — — Berkabel (pilihan)

Operasi MENINGGALKAN RUMAH — — Operasi ECONO — —

Tombol [ON/OFF] unit indoor

★1 —

Tanda penerimaan sinyal

★1 —

Tampilan suhu — —

Catatan: : Ada ★1: dengan remote kontrol nirkabel

— : Tidak ada ★2:dengan remote kontrol kabel

Pendingin saja SiBE121135_A

17 Spesifikasi

Bagian 2 Spesifikasi

1. Pendingin Saja ......................................................................................... 17 Unit Outdoor ................................................................................................17 Unit Indoor ..................................................................................................19

2. Pompa Kalor............................................................................................. 24 Unit Outdoor ................................................................................................24 Unit Indoor ..................................................................................................28

SiBE121135_A

Spesifikasi 18

1. Pendingin Saja

Unit Outdoor 50 Hz, 230 V

Model 3MKS50E3V1B 4MKS58E3V1B

Warna Penutup Putih gading Putih gading

Kompresor

Tipe Tipe Ayun Tersegel Kedap Udara Tipe Ayun Tersegel Kedap Udara

Model 2YC36BXD 2YC36BXD

Output Motor W 1.100 1.100

Oli Refrigeran Model FVC50K FVC50K

Isi L 0,65 0,65

Refrigeran Tipe R-410A R-410A

Isi kg 2,0 2,0

Laju Aliran

Udara

H m³/min

45 45

L 45 45

H cfm

1.589 1.589

L 1.589 1.589

Kipas

Tipe Baling-baling Baling-baling

Output Motor W 53 53

Arus Berjalan A H: 0,33 / L: 0,33 H: 0,33 / L: 0,33

Konsumsi Daya W H: 43 / L: 43 H: 43 / L: 43

Arus Start A 5,3 6,7

Dimensi (H × W × D) mm 735 × 936 × 300 735 × 936 × 300

Dimensi Kemasan (H × W × D) mm 797 × 992 × 390 797 × 992 × 390

Berat (Massa) kg 49 49

Berat Bruto (Massa Bruto) kg 56 56

Tingkat Tekanan Suara dB(A) 46 46

Tingkat Daya Suara dB 59 59

Sambungan Perpipaan

Cairan mm 6,4 × 3 6,4 × 4

Gas mm 9,5 × 3 9,5 × 2, 12,7 × 2

Pembuangan mm 18,0 18,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Jumlah Sambungan Pengkabelan 3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

Panjang Perpipaan Antar unit Maks. m 50 (untuk Total Setiap Ruangan) 50 (untuk Total Setiap Ruangan)

m 25 (untuk Satu Ruangan) 25 (untuk Satu Ruangan)

Jumlah Isi Tambahan g/m Tidak berisi Tidak berisi

Selisih Tinggi Pemasangan Maks. m 15 (Antara Unit Indoor dan Unit Outdoor) 15 (Antara Unit Indoor dan Unit Outdoor)

m 15 (Antara Unit Indoor) 15 (Antara Unit Indoor)

No. Gambar 3D054330#1 3D054329#1

Catatan: Data berdasarkan kondisi yang ditunjukkan pada tabel di bawah ini.

Pendinginan Panjang

Perpipaan Indoor ; 27°CDB / 19°CWB

Outdoor ; 35°CDB 7,5 m

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

19 Spesifikasi

SiBE121135_A Pendingin saja

50 Hz, 230 V

Model 4MKS75F2V1B 5MKS90E2V3B

Warna Penutup Putih gading Putih gading

Kompresor

Tipe Tipe Ayun Tersegel Kedap Udara Tipe Ayun Tersegel Kedap Udara

Model 2YC45DXD 2YC63BXD

Output Motor W 1.380 1.920

Oli Refrigeran Model FVC50K FVC50K

Isi L 0,65 0,75

Refrigeran Tipe R-410A R-410A

Isi kg 2,3 2,95

Laju Aliran

Udara

H m³/min

52,7 54,5

M 49,4 —

L 43,5 46

H cfm

1.861 1.924

M 1.744 —

L 1.536 1.624

Kipas

Tipe Baling-baling Baling-baling

Output Motor W 53 66

Arus Berjalan A H: 0,20 / M: 0,16 / L: 0,10 H: 0,97 / L: 0,69

Konsumsi Daya W H: 70 / M: 58 / L: 36 H: 86 / L: 55

Arus Start A 6,2 11,4

Dimensi (H × W × D) mm 735 × 936 × 300 770 × 900 × 320

Dimensi Kemasan (H × W × D) mm 797 × 992 × 390 900 × 925 × 390

Berat (Massa) kg 57 69

Berat Bruto (Massa Bruto) kg 61 78

Tingkat Tekanan Suara dB(A) 48 48

Tingkat Daya Suara dB 61 62

Sambungan Perpipaan

Cairan mm 6,4 × 4 6,4 × 5

Gas mm 9.5 × 2, 12.7 × 1, 15.9 × 1 9.5 × 2, 12.7 × 1, 15.9 × 2

Pembuangan mm 18,0 25,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Jumlah Sambungan Pengkabelan 3 untuk Catu Daya, 4 untuk Pengkabelan

Antar unit

3 untuk Catu Daya, 4 untuk Pengkabelan

Antar unit Panjang Perpipaan Antar unit Maks.

m 60 (untuk Total Setiap Ruangan) 75 (untuk Total Setiap Ruangan)

m 25 (untuk Satu Ruangan) 25 (untuk Satu Ruangan)

Jumlah Isi Tambahan g/m Tidak berisi 20 (65 m atau lebih)

Selisih Tinggi Pemasangan Maks. m 15 (Antara Unit Indoor dan Unit Outdoor) 15 (Antara Unit Indoor dan Unit Outdoor)

m 15 (Antara Unit Indoor) 7,5 (Antara Unit Indoor)

No. Gambar 3D056453 3D063120

Catatan: Data berdasarkan kondisi yang ditunjukkan pada tabel di bawah ini.

Pendinginan Panjang Perpipaan

Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB

5 m (4MKS75F2V1B) 7.5 m (5MKS90E2V3B)

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 20

Pendingin saja

SiBE121135_A

Unit Indoor

Tipe Wall Mounted 50 Hz, 220 - 230 - 240 V

Model FTXS25J2V1B FTXS35J2V1B

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

10,8 (381) 11,4 (403)

M 7,9 (279) 8,7 (307)

L 5,2 (184) 5,8 (205)

SL 3,7 (131) 4,4 (155)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 23 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0,09 - 0,08 - 0,08 0,12 - 0,12 - 0,11

Komsumsi Daya (Terpasang) W 18 - 18 - 18 26 - 26 - 26

Faktor Daya (Terpasang) % 90.9 - 97.8 - 93.8 98.5 - 94.2 - 98.5

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 800 × 215 295 × 800 × 215

Dimensi Kemasan (H × W × D) mm 289 × 870 × 366 289 × 870 × 366

Berat (Massa) kg 9 10

Berat Bruto (Massa Bruto) kg 13 14

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

41 / 33 / 25 / 22

45 / 37 / 29 / 23

Tingkat Daya Suara dB 57 61

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D070570A 3D070571A

Model FTXS42J2V1B FTXS50J2V1B

Kapasitas Terpasang Kelas 4,2 kW Kelas 5,0 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

11,3 (399) 11,6 (410)

M 9,0 (318) 9,2 (325)

L 6,8 (240) 7,0 (247)

SL 5,9 (208) 6,0 (212)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 23 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0,11 - 0,11 - 0,11 0.12 - 0.12 - 0.11

Komsumsi Daya (Terpasang) W 24 - 24 - 24 26 - 26 - 26

Faktor Daya (Terpasang) % 99,2 - 94,9 - 90,9 98.5 - 94.2 - 98.5

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 800 × 215 295 × 800 × 215

Dimensi Kemasan (H × W × D) mm 289 × 870 × 366 289 × 870 × 366

Berat (Massa) kg 10 10

Berat Bruto (Massa Bruto) kg 14 14

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

45 / 39 / 33 / 30

46 / 40 / 34 / 31

Tingkat Daya Suara dB 61 62

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 12,7

Pembuangan mm 18,0 18,0

No. Gambar 3D070572A 3D070573A

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

21 Spesifikasi

SiBE121135_A Pendingin saja

50 Hz, 220 - 230 - 240 V

Model FTXS60GV1B FTXS71GV1B

Kapasitas Terpasang Kelas 6,0 kW Kelas 7,1 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

16,0 (565) 17,2 (607)

M 13,5 (477) 14,5 (512)

L 11,3 (399) 11,5 (406)

SL 10,1 (357) 10,5 (371)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 43 43

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.19 - 0.18 - 0.17 0.21 - 0.20 - 0.19

Komsumsi Daya (Terpasang) W 40 - 40 - 40 45 - 45 - 45

Faktor Daya (Terpasang) % 95.7 - 96.6 - 98.0 97.4 - 97.8 - 98.7

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 290 × 1.050 × 250 290 × 1.050 × 250

Dimensi Kemasan (H × W × D) mm 361 × 1.145 × 364 361 × 1.145 × 364

Berat (Massa) kg 12 12

Berat Bruto (Massa Bruto) kg 18 18

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

45 / 41 / 36 / 33

46 / 42 / 37 / 34

Tingkat Daya Suara dB 61 62

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 12,7 15,9

Pembuangan mm 18,0 18,0

No. Gambar 3D065735A 3D065737A

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 22

Pendingin saja

SiBE121135_A

Tipe Ceiling Mounted Cassette 50 Hz, 230 V

Model FFQ25B9V1B FFQ35B9V1B

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Panel Dekorasi

Model BYFQ60B8W1 BYFQ60B8W1

Warna Putih Putih

Dimensi (H × W × D) mm 55 × 700 × 700 55 × 700 × 700

Berat (Massa) kg 2,7 2,7

Laju Aliran

Udara

H m³/min (cfm)

9,0 (318) 10,0 (353)

L 6,5 (230) 6,5 (230)

Kipas

Tipe Kipas Turbo Kipas Turbo

Output Motor W 55 55

Kecepatan Langkah

2 Langkah 2 Langkah

Kendali Arah Udara Mendatar, Kebawah Mendatar, Kebawah

Arus Berjalan (Terpasang) A 0,37 0,40

Komsumsi Daya (Terpasang) W 73 84

Faktor Daya (Terpasang) % 85,8 91,3

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) ★ mm 260 (286) × 575 × 575 260 (286) × 575 × 575

Dimensi Kemasan (H × W × D) mm 370 × 687 × 674 370 × 687 × 674

Berat (Massa) kg 17,5 17,5

Berat Bruto (Massa Bruto) kg 21 21

Tingkat Tekanan Suara

H / L

dB(A)

29,5/24,5

32,0/25,0

Tingkat Daya Suara dB 46,5 49,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm VP20 (O.D. 26 / I.D. 20) VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D060406 3D060408

Model FFQ50B9V1B FFQ60B9V1B

Kapasitas Terpasang Kelas 5,0 kW Kelas 6,0 kW

Panel Dekorasi

Model BYFQ60B8W1 BYFQ60B8W1

Warna Putih Putih

Dimensi (H × W × D) mm 55 × 700 × 700 55 × 700 × 700

Berat (Massa) kg 2,7 2,7

Laju Aliran Udara

H m³/min (cfm)

12,0 (424) 15,5 (530)

L 8,0 (283) 10,0 (353)

Kipas

Tipe Kipas Turbo Kipas Turbo

Output Motor W 55 55

Kecepatan Langkah

2 Langkah 2 Langkah

Kendali Arah Udara Mendatar, Kebawah Mendatar, Kebawah

Arus Berjalan (Terpasang) A 0,49 0,61

Komsumsi Daya (Terpasang) W 97 120

Faktor Daya (Terpasang) % 86,1 85,5

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) ★ mm 260 (286) × 575 × 575 260 (286) × 575 × 575

Dimensi Kemasan (H × W × D) mm 370 × 687 × 674 370 × 687 × 674

Berat (Massa) kg 17,5 17,5

Berat Bruto (Massa Bruto) kg 21 21

Tingkat Tekanan Suara

H / L

dB(A)

36,0/27,0

41,0/32,0

Tingkat Daya Suara dB 53,0 58,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 12,7 12,7

Pembuangan mm VP20 (O.D. 26 / I.D. 20) VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D060410 3D040431

★ ( ) : dimensi termasuk kotak kendali

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

23 Spesifikasi

SiBE121135_A Pendingin saja

Tipe Ceiling Suspended

50 Hz, 220 - 230 - 240 V

Model FHQ35BWV1B FHQ50BWV1B

Kapasitas Terpasang Kelas 3,5 kW Kelas 5,0 kW

Warna Panel Putih Putih

Laju Aliran Udara

H m³/min

13,0 (459) 13,0 (459)

L 10,0 (353) 10,0 (353)

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 62 62

Kecepatan Langkah

2 Langkah 2 Langkah

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 195 × 960 × 680 195 × 960 × 680

Dimensi Kemasan (H × W × D) mm 279 × 1.046 × 818 279 × 1.046 × 818

Berat (Massa) kg 24 25

Berat Bruto (Massa Bruto) kg 31 32

Tingkat Tekanan Suara

H / L

dB(A)

37/32

38/33

Tingkat Daya Suara dB 53 54

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 12,7

Pembuangan mm VP20 (O.D. 26 / I.D. 20) VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D075708 3D075709

Model FHQ60BWV1B

Kapasitas Terpasang Kelas 6,0 kW

Warna Panel Putih

Laju Aliran Udara

H m³/min

17,0 (600)

L 13,0 (459)

Kipas

Tipe Kipas Siroko

Output Motor W 62

Kecepatan Langkah

2 Langkah

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur

Pengendalian suhu Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 195 × 1.160 × 680

Dimensi Kemasan (H × W × D) mm 279 × 1.246 × 818

Berat (Massa) kg 27

Berat Bruto (Massa Bruto) kg 35

Tingkat Tekanan Suara

H / L

dB(A)

39/33

Tingkat Daya Suara dB 55

Isolasi Panas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4

Gas mm 12,7

Pembuangan mm VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D075710

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 24

Pendingin saja

SiBE121135_A

Tipe Ceiling Mounted Built-in 50 Hz, 220 - 230 - 240 V /

50 Hz, 230 V 60 Hz, 220 V

Model FDBQ25B8V1 FBQ35C8VEB

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Panel Dekorasi

Model — BYBS45DJW1

Warna — Putih

Dimensi (H × W × D) — 55 × 800 × 500

Berat (Massa) kg — 3,5

Laju Aliran

Udara

H m³/min

6,5 16,0

L 5,2 11,0

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 10 140

Kecepatan Langkah

2 Langkah 2 Langkah

Filter udara Jaring resin tahan jamur Jaring resin tahan jamur

Dimensi (H × W × D) mm 230 × 652 × 502 300 × 700 × 700

Dimensi Kemasan (H × W × D) mm 301 × 753 × 584 325 × 920 × 900

Berat (Massa) kg 17 25

Berat Bruto (Massa Bruto) kg 18 28

Tingkat Tekanan Suara

H / L

dB(A)

35/28

37/29

Tingkat Daya Suara

H / L dB 55/49 63 / —

Isolasi Panas — Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,35 6,35 (Flare / Penyambung)

Gas mm 9,52 9,52 (Flare / Penyambung)

Pembuangan mm O.D. 27,2 VP25 (O.D. 32 / I.D. 25)

Model FBQ50C8VEB FBQ60C8VEB

Kapasitas Terpasang Kelas 5,0 kW Kelas 6,0 kW

Panel Dekorasi

Model BYBS45DJW1 BYBS71DJW1

Warna Putih Putih

Dimensi (H × W × D) 55 × 800 × 500 55 × 1.100 × 500

Berat (Massa) kg 3,5 4,5

Laju Aliran Udara

H m³/min

16,0 18,0

L 11,0 15,0

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 140 350

Kecepatan Langkah

2 Langkah 2 Langkah

Filter udara Jaring resin tahan jamur Jaring resin tahan jamur

Dimensi (H × W × D) mm 300 × 700 × 700 300 × 1.000 × 700

Dimensi Kemasan (H × W × D) mm 355 × 920 × 900 355 × 1.220 × 900

Berat (Massa) kg 25 34

Berat Bruto (Massa Bruto) kg 28 41

Tingkat Tekanan Suara

H / L

dB(A)

37/29

37/29

Tingkat Daya Suara

H / L dB 63 / — 57 / —

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,35 (Flare / Penyambung) 6,35 (Flare / Penyambung)

Gas mm 12,7 (Flare / Penyambung) 12,7 (Flare / Penyambung)

Pembuangan mm VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

25 Spesifikasi

SiBE121135_A Pompa panas

2. Pompa Kalor

Unit Outdoor 50 Hz, 230 V

Model 3MXS40K2V1B, 3MXS40K3V1B 3MXS52E3V1B, 3MXS52E4V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Warna Penutup Putih gading Putih gading

Kompresor

Tipe Tipe Ayun Tersegel Kedap Udara Tipe Ayun Tersegel Kedap Udara

Model 2YC36BXD 2YC36BXD

Output Motor W 1.100 1.100

Oli Refrigeran Model FVC50K FVC50K

Isi L 0,65 0,65

Refrigeran Tipe R-410A R-410A

Isi kg 2,0 2,0

Laju Aliran Udara

H m³/min

45,0 45,0 45,0 45,0

L 41,0 41,0 45,0 41,0

H cfm

1.589 1.589 1.589 1.589

L 1.448 1.448 1.589 1.448

Kipas

Tipe Baling-baling Baling-baling

Output Motor W 53 53

Arus Berjalan A H: 0,33 / L: 0,29 H: 0,33 / L: 0,29

Konsumsi Daya W H: 43 / L: 34 H: 43 / L: 34

Arus Start A 4,0 6,2

Dimensi (H × W × D) mm 735 × 936 × 300 735 × 936 × 300

Dimensi Kemasan (H × W × D) mm 797 × 992 × 390 797 × 992 × 390

Berat (Massa) kg 49 49

Berat Bruto (Massa Bruto) kg 56 56

Tingkat Tekanan Suara dB(A) 46 47 46 47

Tingkat Daya Suara dB 59 60 59 60

Sambungan Perpipaan

Cairan mm 6,4 × 3 6,4 × 3

Gas mm 9,5 × 3 9,5 × 2 12,7 × 1

Pembuangan mm 16,0 16,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Jumlah Sambungan Pengkabelan 3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

Panjang Perpipaan Antar unit Maks. m 50 (untuk Total Setiap Ruangan) 50 (untuk Total Setiap Ruangan)

m 25 (untuk Satu Ruangan) 25 (untuk Satu Ruangan)

Jumlah Isi Tambahan g/m 20 (30 m atau lebih) 20 (30 m atau lebih)

Selisih Tinggi Pemasangan Maks. m 15 (Antara Unit Indoor dan Unit Outdoor) 15 (Antara Unit Indoor dan Unit Outdoor)

m 7,5 (Antara Unit Indoor) 7,5 (Antara Unit Indoor)

No. Gambar 3D074741A 3D054327#1A

Catatan: Data berdasarkan kondisi yang ditunjukkan pada tabel di bawah ini.

Pendinginan Pemanasan Panjang Perpipaan

Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB

Indoor ; 20°CDB Outdoor ; 7°CDB / 6°CWB

5 m (3MXS40K2V1B) 7,5 m (3MXS52E3V1B)

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 26

Pompa panas SiBE121135_A

50 Hz, 230 V

Model 3MXS68G2V1B, 3MXS68G3V1B 4MXS68F2V1B, 4MXS68F3V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Warna Penutup Putih gading Putih gading

Kompresor

Tipe Tipe Ayun Tersegel Kedap Udara Tipe Ayun Tersegel Kedap Udara

Model 2YC45DXD 2YC45DXD

Output Motor W 1.380 1.380

Oli Refrigeran Model FVC50K FVC50K

Isi L 0,65 0,65

Refrigeran Tipe R-410A R-410A

Isi kg 2,59 2,6

Laju Aliran

Udara

H m³/min

52,7 46,4 52,7 46,4

M 49,4 44,5 49,4 44,5

L 43,5 16,3 43,5 16,3

H cfm

1.861 1.638 1.861 1.638

M 1.744 1.571 1.744 1.571

L 1.536 576 1.536 576

Kipas

Tipe Baling-baling Baling-baling

Output Motor W 53 53

Arus Berjalan A H: 0,20 / M: 0,16 / L: 0,10 H: 0,16 / M: 0,14 / L: 0,03 H: 0,20 / M: 0,16 / L: 0,10 H: 0,16 / M: 0,14 / L: 0,03

Konsumsi Daya W H: 70 / M: 58 / L: 36 H: 55 / M: 48 / L: 10 H: 70 / M: 58 / L: 36 H: 55 / M: 48 / L: 10

Arus Start A 9,1 8,3

Dimensi (H × W × D) mm 735 × 936 × 300 735 × 936 × 300

Dimensi Kemasan (H × W × D) mm 797 × 992 × 390 797 × 992 × 390

Berat (Massa) kg 58 58

Berat Bruto (Massa Bruto) kg 63 63

Tingkat Tekanan Suara dB(A) 48 49 48 49

Tingkat Daya Suara dB 61 — 61 —

Sambungan Perpipaan

Cairan mm 6,4 × 3 6,4 × 4

Gas mm 9,5 × 1, 12,7 × 2 9,5 × 2, 12,7 × 2

Pembuangan mm 16,0 16,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Jumlah Sambungan Pengkabelan 3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

Panjang Perpipaan Antar unit Maks. m 50 (untuk Total Setiap Ruangan) 60 (untuk Total Setiap Ruangan)

m 25 (untuk Satu Ruangan) 25 (untuk Satu Ruangan)

Jumlah Isi Tambahan g/m 20 (30 m atau lebih) 20 (30 m atau lebih)

Selisih Tinggi Pemasangan Maks. m 15 (Antara Unit Indoor dan Unit Outdoor) 15 (Antara Unit Indoor dan Unit Outdoor)

m 7,5 (Antara Unit Indoor) 7,5 (Antara Unit Indoor)

No. Gambar 3D058720B 3D056404A

Catatan: Data berdasarkan kondisi yang ditunjukkan pada tabel di bawah ini.

Pendinginan Pemanasan Panjang

Perpipaan Indoor ; 27°CDB / 19°CWB

Outdoor ; 35°CDB Indoor ; 20°CDB

Outdoor ; 7°CDB / 6°CWB 5 m

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

27 Spesifikasi

SiBE121135_A Pompa panas

50 Hz, 230 V

Model 4MXS80E2V3B, 4MXS80E3V3B 5MXS90E2V3B, 5MXS90E3V3B

Pendinginan Pemanasan Pendinginan Pemanasan

Warna Penutup Putih gading Putih gading

Kompresor

Tipe Tipe Ayun Tersegel Kedap Udara Tipe Ayun Tersegel Kedap Udara

Model 2YC63BXD 2YC63BXD

Output Motor W 1.920 1.920

Oli Refrigeran Model FVC50K FVC50K

Isi L 0,75 0,75

Refrigeran Tipe R-410A R-410A

Isi kg 2,99 2,99

Laju Aliran

Udara

H m³/min

54,5 46,0 57,1 52,5

M — — 54,5 —

L 46,0 14,7 46,0 14,7

H cfm

1.924 1.624 2.016 1.854

M — — 1.924 —

L 1.624 519 1.624 519

Kipas

Tipe Baling-baling Baling-baling

Output Motor W 66 66

Arus Berjalan A H: 0,97 / L: 0,69 H: 0,69 / L: 0,05 H: 1,02 / M: 0,97 / L: 0,69 H: 0,90 / L: 0,05

Konsumsi Daya W H: 86 / L: 55 H: 55 / L: 9 H: 95 / M: 86 / L: 55 H: 78 / L: 9

Arus Start A 9,7 11,8

Dimensi (H × W × D) mm 770 × 900 × 320 770 × 900 × 320

Dimensi Kemasan (H × W × D) mm 900 × 925 × 390 900 × 925 × 390

Berat (Massa) kg 72 73

Berat Bruto (Massa Bruto) kg 80 80

Tingkat Tekanan Suara dB(A) 48 49 52 52

Tingkat Daya Suara dB 62 — 66 —

Sambungan Perpipaan

Cairan mm 6,4 × 4 6,4 × 5

Gas mm 9.5 × 1, 12.7 × 1, 15.9 × 2 9.5 × 2, 12.7 × 1, 15.9 × 2

Pembuangan mm 25,0 25,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Jumlah Sambungan Pengkabelan 3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

Panjang Perpipaan Antar unit Maks. m 70 (untuk Total Setiap Ruangan) 75 (untuk Total Setiap Ruangan)

m 25 (untuk Satu Ruangan) 25 (untuk Satu Ruangan)

Jumlah Isi Tambahan g/m 20 (30 m atau lebih) 20 (30 m atau lebih)

Selisih Tinggi Pemasangan Maks. m 15 (Antara Unit Indoor dan Unit Outdoor) 15 (Antara Unit Indoor dan Unit Outdoor)

m 7,5 (Antara Unit Indoor) 7,5 (Antara Unit Indoor)

No. Gambar 3D063118A 3D063119A

Catatan: Data berdasarkan kondisi yang ditunjukkan pada tabel di bawah ini.

Pendinginan Pemanasan Panjang

Perpipaan Indoor ; 27°CDB / 19°CWB

Outdoor ; 35°CDB Indoor ; 20°CDB

Outdoor ; 7°CDB / 6°CWB 7,5 m

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 28

Pompa panas SiBE121135_A

50 Hz, 230 V

Model 3AMX52E3V1B, 3AMX52E4V1B

Pendinginan Pemanasan

Warna Penutup Putih gading

Kompresor

Tipe Tipe Ayun Tersegel Kedap Udara

Model 2YC36BXD

Output Motor W 1.100

Oli Refrigeran Model FVC50K

Isi L 0,65

Refrigeran Tipe R-410A

Isi kg 2,0

Laju Aliran

Udara

H m³/min

45,0 45,0

M — —

L 45,0 41,0

H cfm

1.589 1.589

M — —

L 1.589 1.448

Kipas

Tipe Baling-baling

Output Motor W 53

Arus Berjalan A H: 0,33 / L: 0,29 H: 0,33 / L: 0,29

Konsumsi Daya W H: 43 / L: 34 H: 43 / L: 34

Arus Start A 6,2

Dimensi (H × W × D) mm 735 × 936 × 300

Dimensi Kemasan (H × W × D) mm 797 × 992 × 390

Berat (Massa) kg 49

Berat Bruto (Massa Bruto) kg 56

Tingkat Tekanan Suara dB(A) 46 47

Tingkat Daya Suara dB 59 60

Sambungan Perpipaan

Cairan mm 6,4 × 3

Gas mm 9,5 × 2, 12,7 × 1

Pembuangan mm 16,0

Isolasi Panas Kedua Pipa Cair dan Gas

Jumlah Sambungan Pengkabelan 3 untuk Catu Daya, 4 untuk Pengkabelan Antar unit

Panjang Perpipaan Antar unit Maks. m 50 (untuk Total Setiap Ruangan)

m 25 (untuk Satu Ruangan)

Jumlah Isi Tambahan g/m 20 (30 m atau lebih)

Selisih Tinggi Pemasangan Maks. m 15 (Antara Unit Indoor dan Unit Outdoor)

m 7,5 (Antara Unit Indoor)

No. Gambar 3D054331#1A

Catatan: Data berdasarkan kondisi yang ditunjukkan pada tabel di bawah ini.

Pendinginan Pemanasan Panjang

Perpipaan Indoor ; 27°CDB / 19°CWB

Outdoor ; 35°CDB Indoor ; 20°CDB

Outdoor ; 7°CDB / 6°CWB 7,5 m

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

29 Spesifikasi

SiBE121135_A Pompa panas

Unit Indoor

Tipe Wall Mounted 50 Hz, 220 - 230 - 240 V

Model FTXG25JV1BW FTXG25JV1BA

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 2,5 kW

Warna Panel Depan Putih Panel Sentuhan Alumunium

Laju Aliran

Udara

H

m³/min (cfm)

8,8 (311) 9,6 (339) 8,8 (311) 9,6 (339)

M 6,8 (240) 7,9 (279) 6,8 (240) 7,9 (279)

L 4,7 (166) 6,2 (219) 4,7 (166) 6,2 (219)

SL 3,8 (134) 5,4 (191) 3,8 (134) 5,4 (191)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 29 29

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0,09 - 0,08 - 0,08 0.12 - 0.11 - 0.11 0.09 - 0.08 - 0.08 0.12 - 0.11 - 0.11

Komsumsi Daya (Terpasang) W 18 - 18 - 18 24 - 24 - 24 18 - 18 - 18 24 - 24 - 24

Faktor Daya (Terpasang) % 90.9 - 97.8 - 93.8 90.9 - 94.9 - 90.9 90.9 - 97.8 - 93.8 90.9 - 94.9 - 90.9

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 915 × 155 295 × 915 × 155

Dimensi Kemasan (H × W × D) mm 285 × 1.003 × 377 285 × 1.003 × 377

Berat (Massa) kg 11 11

Berat Bruto (Massa Bruto) kg 15 16

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

38 / 32 / 25 / 22

39 / 34 / 28 / 25

38 / 32 / 25 / 22

39 / 34 / 28 / 25

Tingkat Daya Suara dB 56 57 56 57

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 16,0 atau 18,0 16,0 atau 18,0

No. Gambar 3D080182 3D080183

Model FTXG35JV1BW FTXG35JV1BA

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 3,5 kW Kelas 3,5 kW

Warna Panel Depan Putih Panel Sentuhan Alumunium

Laju Aliran Udara

H

m³/min (cfm)

10,1 (357) 10,8 (381) 10,1 (357) 10,8 (381)

M 7,3 (258) 8,6 (304) 7,3 (258) 8,6 (304)

L 4,6 (162) 6,4 (226) 4,6 (162) 6,4 (226)

SL 3,9 (138) 5,6 (198) 3,9 (138) 5,6 (198)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 29 29

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.13 - 0.12 - 0.12 0.16 - 0.15 - 0.14 0.13 - 0.12 - 0.12 0.16 - 0.15 - 0.14

Komsumsi Daya (Terpasang) W 26 - 26 - 26 32 - 32 - 32 26 - 26 - 26 32 - 32 - 32

Faktor Daya (Terpasang) % 90.9 - 94.2 - 90.3 90.9 - 92.8 - 95.2 90.9 - 94.2 - 90.3 90.9 - 92.8 - 95.2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 915 × 155 295 × 915 × 155

Dimensi Kemasan (H × W × D) mm 285 × 1.003 × 377 285 × 1.003 × 377

Berat (Massa) kg 11 11

Berat Bruto (Massa Bruto) kg 15 16

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

42 / 34 / 26 / 23

42 / 36 / 29 / 26

42 / 34 / 26 / 23

42 / 36 / 29 / 26

Tingkat Daya Suara dB 60 60 60 60

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 16,0 atau 18,0 16,0 atau 18,0

No. Gambar 3D080185 3D080186

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 30

Pompa panas SiBE121135_A

50 Hz, 220 - 230 - 240 V

Model FTXG50JV1BW FTXG50JV1BA

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW Kelas 5,0 kW

Warna Panel Depan Putih Panel Sentuhan Alumunium

Laju Aliran

Udara

H

m³/min (cfm)

10,3 (364) 11,4 (402) 10,3 (364) 11,4 (402)

M 8,5 (300) 9,8 (346) 8,5 (300) 9,8 (346)

L 6,7 (237) 8,1 (286) 6,7 (237) 8,1 (286)

SL 5,7 (201) 7,1 (251) 5,7 (201) 7,1 (251)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 40 40

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.16 - 0.15 - 0.14 0.19 - 0.18 - 0.17 0.16 - 0.15 - 0.14 0.19 - 0.18 - 0.17

Komsumsi Daya (Terpasang) W 32 - 32 - 32 38 - 38 - 38 32 - 32 - 32 38 - 38 - 38

Faktor Daya (Terpasang) % 90.9 - 92.8 - 95.2 90.9 - 91.8 - 93.1 90.9 - 92.8 - 95.2 90.9 - 91.8 - 93.1

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 915 × 155 295 × 915 × 155

Dimensi Kemasan (H × W × D) mm 285 × 1.003 × 377 285 × 1.003 × 377

Berat (Massa) kg 11 11

Berat Bruto (Massa Bruto) kg 15 16

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

44 / 40 / 35 / 32

44 / 40 / 35 / 32

44 / 40 / 35 / 32

44 / 40 / 35 / 32

Tingkat Daya Suara dB 60 60 60 60

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 12,7 12,7

Pembuangan mm 18,0 18,0

No. Gambar 3D080642 3D080643

Model CTXS15K2V1B FTXS20K2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 1,5 kW Kelas 2,0 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

7,9 (279) 9,0 (318) 8,8 (311) 9,5 (335)

M 6,3 (222) 7,5 (265) 6,7 (237) 7,8 (275)

L 4,7 (166) 6,0 (212) 4,7 (166) 6,0 (212)

SL 3,9 (138) 4,3 (152) 3,9 (138) 4,3 (152)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 16 16

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.19 - 0.18 - 0.17 0.19 - 0.18 - 0.17 0.19 - 0.18 - 0.17 0.19 - 0.18 - 0.17

Komsumsi Daya (Terpasang) W 40 - 40 - 40 40 - 40 - 40 40 - 40 - 40 40 - 40 - 40

Faktor Daya (Terpasang) % 95.7 - 96.6 - 98.0 95.7 - 96.6 - 98.0 95.7 - 96.6 - 98.0 95.7 - 96.6 - 98.0

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 289 × 780 × 215 289 × 780 × 215

Dimensi Kemasan (H × W × D) mm 274 × 850 × 346 274 × 850 × 346

Berat (Massa) kg 8 8

Berat Bruto (Massa Bruto) kg 12 12

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

37 / 31 / 25 / 21

38 / 33 / 28 / 21

40 / 32 / 24 / 19

40 / 34 / 27 / 19

Tingkat Daya Suara dB 55 56 58 58

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D074531A 3D080188

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

31 Spesifikasi

SiBE121135_A Pompa panas

50 Hz, 220 - 230 - 240 V

Model FTXS25K2V1B CTXS35K2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

9,1 (321) 10,0 (353) 9,2 (325) 10,1 (357)

M 7,0 (247) 8,0 (282) 7,2 (254) 8,1 (286)

L 5,0 (177) 6,0 (212) 5,2 (184) 6,3 (222)

SL 3,9 (138) 4,3 (152) 3,9 (138) 4,3 (152)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 16 16

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.19 - 0.18 - 0.17 0.19 - 0.18 - 0.17 0.19 - 0.18 - 0.17 0.19 - 0.18 - 0.17

Komsumsi Daya (Terpasang) W 40 - 40 - 40 40 - 40 - 40 40 - 40 - 40 40 - 40 - 40

Faktor Daya (Terpasang) % 95.7 - 96.6 - 98.0 95.7 - 96.6 - 98.0 95.7 - 96.6 - 98.0 95.7 - 96.6 - 98.0

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 289 × 780 × 215 289 × 780 × 215

Dimensi Kemasan (H × W × D) mm 274 × 850 × 346 274 × 850 × 346

Berat (Massa) kg 8 8

Berat Bruto (Massa Bruto) kg 12 12

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

41 / 33 / 25 / 19

41 / 34 / 27 / 19

42 / 35 / 28 / 21

41 / 36 / 30 / 21

Tingkat Daya Suara dB 58 58 59 58

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D080189 3D074535A

Model FTXS35K2V1B FTXS42K2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 3,5 kW Kelas 4,2 kW

Warna Panel Depan Putih Putih

Laju Aliran Udara

H

m³/min (cfm)

11,2 (395) 12,1 (427) 11,2 (395) 12,4 (438)

M 8,5 (300) 9,3 (328) 9,1 (321) 10,0 (353)

L 5,8 (205) 6,5 (230) 7,0 (247) 7,8 (275)

SL 4,1 (145) 4,2 (148) 4,1 (145) 5,2 (184)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 23 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.12 - 0.12 - 0.11 0.13 - 0.13 - 0.12 0.11 - 0.11 - 0.11 0.14 - 0.14 - 0.13

Komsumsi Daya (Terpasang) W 26 - 26 - 26 28 - 28 - 28 24 - 24 - 24 30 - 30 - 30

Faktor Daya (Terpasang) % 98.5 - 94.2 - 98.5 97.9 - 93.6 - 97.2 99.2 - 94.9 - 90.9 97.4 - 93.2 - 96.2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 298 × 900 × 215 298 × 900 × 215

Dimensi Kemasan (H × W × D) mm 290 × 977 × 371 290 × 977 × 371

Berat (Massa) kg 11 11

Berat Bruto (Massa Bruto) kg 15 15

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

45 / 37 / 29 / 19

45 / 39 / 29 / 19

45 / 39 / 33 / 21

45 / 39 / 33 / 22

Tingkat Daya Suara dB 59 59 59 59

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D080619 3D080620

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 32

Pompa panas SiBE121135_A

50 Hz, 220 - 230 - 240 V

Model FTXS50K2V1B

Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW

Warna Panel Depan Putih

Laju Aliran

Udara

H

m³/min (cfm)

11,9 (420) 13,3 (470)

M 9,6 (339) 10,8 (381)

L 7,4 (261) 8,4 (297)

SL 4,5 (159) 5,5 (194)

Kipas

Tipe Kipas Aliran Silang

Output Motor W 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.12 - 0.12 - 0.11 0.15 - 0.14 - 0.14

Komsumsi Daya (Terpasang) W 26 - 26 - 26 32 - 32 - 32

Faktor Daya (Terpasang) % 98.5 - 94.2 - 98.5 97.0 - 99.4 - 95.2

Pengendalian suhu Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 298 × 900 × 215

Dimensi Kemasan (H × W × D) mm 290 × 977 × 371

Berat (Massa) kg 11

Berat Bruto (Massa Bruto) kg 15

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

46 / 40 / 34 / 23

47 / 40 / 34 / 24

Tingkat Daya Suara dB 60 60

Isolasi Panas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4

Gas mm 12,7

Pembuangan mm 18,0

No. Gambar 3D080621

Model FTXS25J2V1B FTXS35J2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Warna Panel Depan Putih Putih

Laju Aliran Udara

H

m³/min (cfm)

10,8 (381) 11,9 (420) 11,4 (403) 12,4 (438)

M 7,9 (279) 9,1 (321) 8,7 (307) 9,5 (335)

L 5,2 (184) 6,4 (226) 5,8 (205) 6,8 (240)

SL 3,7 (131) 5,9 (208) 4,4 (155) 6,0 (212)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 23 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.09 - 0.08 - 0.08 0.10 - 0.10 - 0.09 0.12 - 0.12 - 0.11 0.13 - 0.13 - 0.12

Komsumsi Daya (Terpasang) W 18 - 18 - 18 21 - 21 - 21 26 - 26 - 26 28 - 28 - 28

Faktor Daya (Terpasang) % 90.9 - 97.8 - 93.8 95.5 - 91.3 - 97.2 98.5 - 94.2 - 98.5 97.9 - 93.6 - 97.2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 800 × 215 295 × 800 × 215

Dimensi Kemasan (H × W × D) mm 289 × 870 × 366 289 × 870 × 366

Berat (Massa) kg 9 10

Berat Bruto (Massa Bruto) kg 13 14

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

41 / 33 / 25 / 22

42 / 35 / 28 / 25

45 / 37 / 29 / 23

45 / 39 / 29 / 26

Tingkat Daya Suara dB 57 58 61 61

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D070565A 3D070566A

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

33 Spesifikasi

SiBE121135_A Pompa panas

50 Hz, 220 - 230 - 240 V

Model FTXS42J2V1B FTXS50J2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 4,2 kW Kelas 5,0 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

11,3 (399) 12,2 (431) 11,6 (410) 12,1 (427)

M 9,0 (318) 9,7 (343) 9,2 (325) 9,8 (346)

L 6,8 (240) 7,3 (258) 7,0 (247) 7,6 (268)

SL 5,9 (208) 6,4 (228) 6,0 (212) 6,7 (237)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 23 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.11 - 0.11 - 0.11 0.14 - 0.14 - 0.13 0.12 - 0.12 - 0.11 0.15 - 0.14 - 0.14

Komsumsi Daya (Terpasang) W 24 - 24 - 24 30 - 30 - 30 26 - 26 - 26 32 - 32 - 32

Faktor Daya (Terpasang) % 99.2 - 94.9 - 90.9 97.4 - 93.2 - 96.2 98.5 - 94.2 - 98.5 97.0 - 99.4 - 95.2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 800 × 215 295 × 800 × 215

Dimensi Kemasan (H × W × D) mm 289 × 870 × 366 289 × 870 × 366

Berat (Massa) kg 10 10

Berat Bruto (Massa Bruto) kg 14 14

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

45 / 39 / 33 / 30

45 / 39 / 33 / 30

46 / 40 / 34 / 31

47 / 41 / 34 / 31

Tingkat Daya Suara dB 61 61 62 63

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 12,7

Pembuangan mm 18,0 18,0

No. Gambar 3D070567A 3D070568A

Model FTXS60GV1B FTXS71GV1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 6,0 kW Kelas 7,1 kW

Warna Panel Depan Putih Putih

Laju Aliran Udara

H

m³/min (cfm)

16,0 (565) 17,2 (607) 17,2 (607) 19,5 (689)

M 13,5 (477) 14,9 (526) 14,5 (512) 16,7 (590)

L 11,3 (399) 12,6 (445) 11,5 (406) 14,2 (501)

SL 10,1 (357) 11,3 (399) 10,5 (371) 12,6 (445)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 43 43

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.19 - 0.18 - 0.17 0.21 - 0.20 - 0.19 0.21 - 0.20 - 0.19 0.28 - 0.27 - 0.26

Komsumsi Daya (Terpasang) W 40 - 40 - 40 45 - 45 - 45 45 - 45 - 45 60 - 60 - 60

Faktor Daya (Terpasang) % 95.7 - 96.6 - 98.0 97.4 - 97.8 - 98.7 97.4 - 97.8 - 98.7 97.4 - 96.6 - 96.2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 290 × 1.050 × 250 290 × 1.050 × 250

Dimensi Kemasan (H × W × D) mm 361 × 1.145 × 364 361 × 1.145 × 364

Berat (Massa) kg 12 12

Berat Bruto (Massa Bruto) kg 18 18

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

45 / 41 / 36 / 33

44 / 40 / 35 / 32

46 / 42 / 37 / 34

46 / 42 / 37 / 34

Tingkat Daya Suara dB 60 59 63 62

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 12,7 15,9

Pembuangan mm 18,0 18,0

No. Gambar 3D080641 3D080176A

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 34

Pompa panas SiBE121135_A

50 Hz, 220 - 230 - 240 V

Model ATXS20G2V1B ATXS25G2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,0 kW Kelas 2,5 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

9,4 (332) 9,9 (350) 9,1 (321) 9,8 (346)

M 7,4 (261) 8,2 (290) 7,1 (252) 7,9 (280)

L 5,5 (194) 6,5 (230) 5,2 (182) 6,2 (217)

SL 4,0 (141) 5,5 (194) 3,7 (130) 5,2 (183)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 23 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.09 - 0.08 - 0.08 0.10 - 0.10 - 0.09 0.09 - 0.08 - 0.08 0.10 - 0.10 - 0.09

Komsumsi Daya (Terpasang) W 18 - 18 - 18 21 - 21 - 21 18 - 18 - 18 21 - 21 - 21

Faktor Daya (Terpasang) % 90.9 - 97.8 - 93.8 95.5 - 91.3 - 97.2 90.9 - 97.8 - 93.8 95.5 - 91.3 - 97.2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 800 × 215 295 × 800 × 215

Dimensi Kemasan (H × W × D) mm 289 × 870 × 366 289 × 870 × 366

Berat (Massa) kg 9 9

Berat Bruto (Massa Bruto) kg 13 13

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

38 / 32 / 25 / 22

38 / 33 / 28 / 25

38 / 32 / 25 / 22

39 / 34 / 28 / 25

Tingkat Daya Suara dB 54 54 54 55

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D080178 3D080179

Model ATXS35G2V1B ATXS42G2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 3,5 kW Kelas 4,2 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

10,4 (367) 10,6 (374) 9,1 (321) 11,2 (395)

M 7,7 (270) 8,5 (302) 7,7 (273) 9,4 (333)

L 4,8 (170) 6,4 (226) 6,3 (221) 7,7 (271)

SL 3,5 (125) 5,4 (191) 5,4 (190) 6,8 (240)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 23 23

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.12 - 0.12 - 0.11 0.13 - 0.13 - 0.12 0.11 - 0.11 - 0.10 0.14 - 0.14 - 0.13

Komsumsi Daya (Terpasang) W 26 - 26 - 26 28 - 28 - 28 24 - 24 - 24 30 - 30 - 30

Faktor Daya (Terpasang) % 98.5 - 94.2 - 98.5 97.9 - 93.6 - 97.2 99.2 - 94.9 - 100.0 97.4 - 93.2 - 96.2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 800 × 215 295 × 800 × 215

Dimensi Kemasan (H × W × D) mm 289 × 870 × 366 289 × 870 × 366

Berat (Massa) kg 10 10

Berat Bruto (Massa Bruto) kg 14 14

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

42 / 34 / 26 / 23

42 / 36 / 29 / 26

42 / 38 / 33 / 30

42 / 38 / 33 / 30

Tingkat Daya Suara dB 59 59 59 59

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D080180 3D080181

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

35 Spesifikasi

SiBE121135_A Pompa panas

50 Hz, 220 - 230 - 240 V

Model ATXS50G2V1B

Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW

Warna Panel Depan Putih

Laju Aliran

Udara

H

m³/min (cfm)

10,2 (360) 11,0 (388)

M 8,6 (305) 9,3 (330)

L 7,0 (246) 7,6 (267)

SL 6,0 (212) 6,7 (236)

Kipas

Tipe Kipas Aliran Silang

Output Motor W 23

Kecepatan Langk

ah

5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.12 - 0.12 - 0.11 0.15 - 0.14 - 0.14

Komsumsi Daya (Terpasang) W 26 - 26 - 26 32 - 32 - 32

Faktor Daya (Terpasang) % 98.5 - 94.2 - 98.5 97.0 - 99.4 - 95.2

Pengendalian suhu Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 295 × 800 × 215

Dimensi Kemasan (H × W × D) mm 289 × 870 × 366

Berat (Massa) kg 10

Berat Bruto (Massa Bruto) kg 14

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

43 / 39 / 34 / 31

44 / 39 / 34 / 31

Tingkat Daya Suara dB 60 61

Isolasi Panas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4

Gas mm 12,7

Pembuangan mm 18,0

No. Gambar 3D081101

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 36

Pompa panas SiBE121135_A

Tipe Floor Standing 50 Hz, 220 - 230 - 240 V

Model FVXG25K2V1B FVXG35K2V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

8,9 (314) 9,9 (350) 9,1 (321) 10,2 (360)

M 7,0 (247) 7,8 (275) 7,2 (254) 8,0 (282)

L 5,3 (187) 5,7 (201) 5,3 (187) 5,8 (205)

SL 4,5 (159) 4,7 (166) 4,5 (159) 5,0 (177)

Kipas

Tipe Kipas Aliran Silang Kipas Aliran Silang

Output Motor W 32 32

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara ke Kanan, Kiri, Atas ke Kanan, Kiri, Atas

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.10 - 0.09 - 0.09 0.11 - 0.11 - 0.10 0.11 - 0.10 - 0.10 0.12 - 0.12 - 0.11

Komsumsi Daya (Terpasang) W 19 - 19 - 19 22 - 22 - 22 21 - 21 - 21 24 - 24 - 24

Faktor Daya (Terpasang) % 86.4 - 91.8 - 88.0 90.9 - 87.0 - 91.7 86.8 - 91.3 - 87.5 90.9 - 87.0 - 90.9

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 600 × 950 × 215 600 × 950 × 215

Dimensi Kemasan (H × W × D) mm 761 × 1.030 × 314 761 × 1.030 × 314

Berat (Massa) kg 22 22

Berat Bruto (Massa Bruto) kg 28 28

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

38 / 32 / 26 / 23

39 / 32 / 26 / 22

39 / 33 / 27 / 24

40 / 33 / 27 / 23

Tingkat Daya Suara dB 52 53 52 53

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D080184 3D080187

Model FVXG50K2V1B

Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW

Warna Panel Depan Putih

Laju Aliran

Udara

H

m³/min (cfm)

10,6 (374) 12,2 (431)

M 8,9 (314) 10,0 (353)

L 7,3 (258) 7,8 (275)

SL 6,0 (212) 6,8 (240)

Kipas

Tipe Kipas Aliran Silang

Output Motor W 32

Kecepatan Langkah

5 Langkah, senyap, Otomatis

Kendali Arah Udara ke Kanan, Kiri, Atas

Filter udara Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.17 - 0.16 - 0.15 0.18 - 0.17 - 0.17

Komsumsi Daya (Terpasang) W 32 - 32 - 32 35 - 35 - 35

Faktor Daya (Terpasang) % 85.6 - 87.0 - 88.9 88.4 - 89.5 - 85.8

Pengendalian suhu Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 600 × 950 × 215

Dimensi Kemasan (H × W × D) mm 761 × 1.030 × 314

Berat (Massa) kg 22

Berat Bruto (Massa Bruto) kg 28

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

44 / 40 / 36 / 32

46 / 40 / 34 / 30

Tingkat Daya Suara dB 58 60

Isolasi Panas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4

Gas mm 12,7

Pembuangan mm 18,0

No. Gambar 3D080644

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

37 Spesifikasi

SiBE121135_A Pompa panas

50 Hz, 220 - 230 - 240 V

Model FVXS25FV1B FVXS35FV1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Warna Panel Depan Putih Putih

Laju Aliran

Udara

H

m³/min (cfm)

8,2 (290) 8,8 (311) 8,5 (300) 9,4 (332)

M 6,5 (230) 6,9 (244) 6,7 (237) 7,3 (258)

L 4,8 (169) 5,0 (177) 4,9 (173) 5,2 (184)

SL 4,1 (145) 4,4 (155) 4,5 (159) 4,7 (166)

Kipas

Tipe Kipas Turbo Kipas Turbo

Output Motor W 48 48

Kecepatan Langk

ah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.14 - 0.13 - 0.12 0.15 - 0.14 - 0.13 0.14 - 0.13 - 0.12 0.15 - 0.14 - 0.13

Komsumsi Daya (Terpasang) W 15 - 15 - 15 17 - 17 - 17 15 - 15 - 15 17 - 17 - 17

Faktor Daya (Terpasang) % 48.7 - 50.2 - 52.1 51.5 - 52.8 - 54.5 48.7 - 50.2 - 52.1 51.5 - 52.8 - 54.5

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 600 × 700 × 210 600 × 700 × 210

Dimensi Kemasan (H × W × D) mm 696 × 786 × 280 696 × 786 × 280

Berat (Massa) kg 14 14

Berat Bruto (Massa Bruto) kg 18 18

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

38 / 32 / 26 / 23

38 / 32 / 26 / 23

39 / 33 / 27 / 24

39 / 33 / 27 / 24

Tingkat Daya Suara dB 52 52 52 52

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 20,0 20,0

No. Gambar 3D080190 3D080877

Model FVXS50FV1B

Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW

Warna Panel Depan Putih

Laju Aliran Udara

H

m³/min (cfm)

10,7 (378) 11,8 (417)

M 9,2 (325) 10,1 (357)

L 7,8 (275) 8,5 (300)

SL 6,6 (233) 7,1 (251)

Kipas

Tipe Kipas Turbo

Output Motor W 48

Kecepatan Langk

ah

5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.18 - 0.17 - 0.16 0.17 - 0.17 - 0.16

Komsumsi Daya (Terpasang) W 27 - 27 - 27 34 - 34 - 34

Faktor Daya (Terpasang) % 68.2 - 69.1 - 70.3 90.9 - 82.0 - 88.5

Pengendalian suhu Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 600 × 700 × 210

Dimensi Kemasan (H × W × D) mm 696 × 786 × 280

Berat (Massa) kg 14

Berat Bruto (Massa Bruto) kg 18

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

44 / 40 / 36 / 32

45 / 40 / 36 / 32

Tingkat Daya Suara dB 60 61

Isolasi Panas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4

Gas mm 12,7

Pembuangan mm 20,0

No. Gambar 3D080878

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 38

Pompa panas SiBE121135_A

Tipe Floor / Ceiling Suspended Dual 50 Hz, 220 - 230 - 240 V

50 Hz, 220 - 230 - 240 V 50 Hz, 230 V

Model FLXS50BAVMB FLXS60BAVMB

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW Kelas 6,0 kW

Warna Panel Depan Putih Almon Putih Almon

Laju Aliran Udara

H

m³/min (cfm)

11,4 (403) 12,1 (427) 12,0 (424) 12,8 (452)

M 10,0 (353) 9,8 (346) 10,7 (378) 10,6 (374)

L 8,5 (300) 7,5 (265) 9,3 (328) 8,4 (297)

SL 7,5 (265) 6,8 (240) 8,3 (293) 7,5 (265)

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 34 34

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.48 - 0.45 - 0.43 0.47 - 0.45 - 0.44 0,47 0,45

Komsumsi Daya (Terpasang) W 96 - 96 - 96 96 - 96 - 96 98 96

Faktor Daya (Terpasang) % 90.9 - 92.8 - 93.0 92.8 - 92.8 - 90.9 90,7 92,8

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 490 × 1.050 × 200 490 × 1.050 × 200

Dimensi Kemasan (H × W × D) mm 280 × 1.100 × 566 280 × 1.100 × 566

Berat (Massa) kg 17 17

Berat Bruto (Massa Bruto) kg 24 24

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

47 / 43 / 39 / 36

46 / 41 / 35 / 33

48 / 45 / 41 / 39

47 / 42 / 37 / 34

Tingkat Daya Suara dB 60 59 60 59

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 12,7 12,7

Pembuangan mm 18,0 18,0

No. Gambar 3D081092 3D050882A

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Model FLXS25BAVMB FLXS35BAVMB

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Warna Panel Depan Putih Almon Putih Almon

Laju Aliran

Udara

H

m³/min (cfm)

7,6 (268) 9,2 (325) 8,6 (304) 9,8 (346)

M 6,8 (240) 8,3 (293) 7,6 (268) 8,9 (314)

L 6,0 (212) 7,4 (261) 6,6 (233) 8,0 (282)

SL 5,2 (184) 6,6 (233) 5,6 (198) 7,2 (254)

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 34 34

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0.33 - 0.32 - 0.31 0.36 - 0.34 - 0.33 0.38 - 0.36 - 0.35 0.38 - 0.36 - 0.35

Komsumsi Daya (Terpasang) W 70 - 70 - 70 74 - 74 - 74 78 - 78 - 78 78 - 78 - 78

Faktor Daya (Terpasang) % 96.4 - 95.1 - 94.1 93.4 - 94.6 - 93.4 93.3 - 94.2 - 92.9 93.3 - 94.2 - 92.9

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 490 × 1.050 × 200 490 × 1.050 × 200

Dimensi Kemasan (H × W × D) mm 280 × 1.100 × 566 280 × 1.100 × 566

Berat (Massa) kg 16 16

Berat Bruto (Massa Bruto) kg 22 22

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

37 / 34 / 31 / 28

37 / 34 / 31 / 29

38 / 35 / 32 / 29

39 / 36 / 33 / 30

Tingkat Daya Suara dB 51 51 53 54

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm 18,0 18,0

No. Gambar 3D081090 3D081091

39 Spesifikasi

SiBE121135_A Pompa panas

Tipe Duct Connected 50 Hz, 230 V

Model FDXS25E7VMB FDXS35E7VMB

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Laju Aliran Udara

H

m³/min (cfm)

8,7 (307) 8,7 (307) 8,7 (307) 8,7 (307)

M 8,0 (282) 8,0 (282) 8,0 (282) 8,0 (282)

L 7,3 (258) 7,3 (258) 7,3 (258) 7,3 (258)

SL 6,2 (219) 6,2 (219) 6,2 (219) 6,2 (219)

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 62 62

Kecepatan Langk

ah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0,48 0,48 0,48 0,48

Komsumsi Daya (Terpasang) W 71 71 71 71

Faktor Daya (Terpasang) % 64,3 64,3 64,3 64,3

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 200 × 700 × 620 200 × 700 × 620

Dimensi Kemasan (H × W × D) mm 274 × 906 × 751 274 × 906 × 751

Berat (Massa) kg 21 21

Berat Bruto (Massa Bruto) kg 29 29

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

35 / 33 / 31 / 29

35 / 33 / 31 / 29

35 / 33 / 31 / 29

35 / 33 / 31 / 29

Tingkat Daya Suara dB 53 53 53 53

Tekanan statis eksternal PA 30 30

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm VP20 (O.D. 26 / I.D. 20) VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D060029 3D060030

Model FDXS50C7VMB FDXS60C7VMB

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW Kelas 6,0 kW

Laju Aliran Udara

H

m³/min (cfm)

12,0 (424) 12,0 (424) 16,0 (565) 16,0 (565)

M 11,0 (388) 11,0 (388) 14,8 (523) 14,8 (523)

L 10,0 (353) 10,0 (353) 13,5 (477) 13,5 (477)

SL 8,4 (297) 8,4 (297) 11,2 (395) 11,2 (395)

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 130 130

Kecepatan Langkah

5 Langkah, senyap, Otomatis 5 Langkah, senyap, Otomatis

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Arus Berjalan (Terpasang) A 0,64 0,64 0,74 0,74

Komsumsi Daya (Terpasang) W 140 140 160 160

Faktor Daya (Terpasang) % 95,1 95,1 94,0 94,0

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 200 × 900 × 620 200 × 1.100 × 620

Dimensi Kemasan (H × W × D) mm 266 × 1.106 × 751 266 × 1.306 × 751

Berat (Massa) kg 27 30

Berat Bruto (Massa Bruto) kg 34 37

Tingkat Tekanan Suara

H / M / L / SL

dB(A)

37 / 35 / 33 / 31

37 / 35 / 33 / 31

38 / 36 / 34 / 32

38 / 36 / 34 / 32

Tingkat Daya Suara dB 55 55 56 56

Tekanan statis eksternal Pa 40 40

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 12,7 12,7

Pembuangan mm VP20 (O.D. 26 / I.D. 20) VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D060033 3D065477

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 40

Pompa panas SiBE121135_A

Tipe Ceiling Mounted Cassette

50 Hz, 220 - 230 - 240 V

Model FCQG35FVEB FCQG50FVEB

Pendinginan

Pemanasan

Pendinginan

Pemanasan Kapasitas Terpasang Kelas 3,5 kW Kelas 5,0 kW

Panel Dekorasi

Model BYCQ140D7W1 / BYCQ140D7W1W / BYCQ140D7GW1 BYCQ140D7W1 / BYCQ140D7W1W / BYCQ140D7GW1

Warna Putih Segar Putih Segar

Dimensi (H × W × D) mm 60 × 950 × 950 / 60 × 950 × 950 / 145 × 950 × 950 60 × 950 × 950 / 60 × 950 × 950 / 145 × 950 × 950

Berat (Massa) kg 5.4 / 5.4 / 10.3 5.4 / 5.4 / 10.3

Filter udara Jaring resin tahan jamur Jaring resin tahan jamur

Laju Aliran Udara

H m³/min

12,5 12,5 12,6 12,6

M 10,6 10,6 10,7 10,7

L 8,7 8,7 8,7 8,7

Kipas

Tipe Kipas Turbo Kipas Turbo

Output Motor W 48 48

Kecepatan Langkah

3 Langkah 3 Langkah

Dimensi (H × W × D) mm 204 × 840 × 840 204 × 840 × 840

Dimensi Kemasan (H × W × D) mm 220 × 880 × 880 220 × 880 × 880

Berat (Massa) kg 18 19

Berat Bruto (Massa Bruto) kg 22 23

Tingkat Tekanan Suara

H / M / L

dB(A)

31 / 29 / 27

31 / 29 / 27

Tingkat Daya Suara

H dB 49 49

Isolasi Panas Polistiren Berbusa / Polietilen Berbusa Polistiren Berbusa / Polietilen Berbusa

Sambungan Perpipaan

Cairan mm 6,35 (Flare /

Penyambung)

6,35 (Flare /

Penyambung) Gas mm 9.52 (Flare /

Penyambung)

12.7 (Flare /

Penyambung) Pembuangan mm VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)

No. Gambar 3D076994 3D076994

Model FCQG60FVEB

Pendinginan Pemanasan

Kapasitas Terpasang Kelas 6,0 kW

Panel Dekorasi

Model BYCQ140D7W1 / BYCQ140D7W1W / BYCQ140D7GW1

Warna Putih Segar

Dimensi (H × W × D) mm 60 × 950 × 950 / 60 × 950 × 950 / 145 × 950 × 950

Berat (Massa) kg 5.4 / 5.4 / 10.3

Filter udara Jaring resin tahan jamur

Laju Aliran

Udara

H m³/min

13,6 13,6

M 11,2 11,2

L 8,7 8,7

Kipas

Tipe Kipas Turbo

Output Motor W 48

Kecepatan Langkah

3 Langkah

Dimensi (H × W × D) mm 204 × 840 × 840

Dimensi Kemasan (H × W × D) mm 220 × 880 × 880

Berat (Massa) kg 19

Berat Bruto (Massa Bruto) kg 23

Tingkat Tekanan Suara

H / M / L

dB(A)

33 / 31 / 28

Tingkat Daya Suara

H dB 51

Isolasi Panas Polistiren Berbusa / Polietilen Berbusa

Sambungan Perpipaan

Cairan mm 6.35 (Flare / Penyambung)

Gas mm 12.7 (Flare / Penyambung)

Pembuangan mm VP25 (O.D. 32 / I.D. 25)

No. Gambar 3D076994

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

41 Spesifikasi

SiBE121135_A Pompa panas

50 Hz, 230 V

Model FFQ25B9V1B FFQ35B9V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Panel Dekorasi

Model BYFQ60B8W1 BYFQ60B8W1

Warna Putih Putih

Dimensi (H × W × D) mm 55 × 700 × 700 55 × 700 × 700

Berat (Massa) kg 2,7 2,7

Laju Aliran Udara

H m³/min (cfm)

9,0 (318) 9,0 (318) 10,0 (353) 10,0 (353)

L 6,5 (230) 6,5 (230) 6,5 (230) 6,5 (230)

Kipas

Tipe Kipas Turbo Kipas Turbo

Output Motor W 55 55

Kecepatan Langkah

2 Langkah 2 Langkah

Kendali Arah Udara Mendatar, Kebawah Mendatar, Kebawah

Arus Berjalan (Terpasang) A 0,37 0,32 0,40 0,36

Komsumsi Daya (Terpasang) W 73 64 84 76

Faktor Daya (Terpasang) % 85,8 87,0 91,3 91,8

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) ★ mm 260 (286) × 575 × 575 260 (286) × 575 × 575

Dimensi Kemasan (H × W × D) mm 370 × 687 × 674 370 × 687 × 674

Berat (Massa) kg 17,5 17,5

Berat Bruto (Massa Bruto) kg 21 21

Tingkat Tekanan Suara

H / L

dB(A)

29.5/24.5

32.0/25.0

Tingkat Daya Suara dB 46,5 49,0

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 9,5

Pembuangan mm VP20 (O.D 26 / I.D 20) VP20 (O.D 26 / I.D 20)

No. Gambar 3D060405 3D060407

Model FFQ50B9V1B FFQ60B9V1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW Kelas 6,0 kW

Panel Dekorasi

Model BYFQ60B8W1 BYFQ60B8W1

Warna Putih Putih

Dimensi (H × W × D) mm 55 × 700 × 700 55 × 700 × 700

Berat (Massa) kg 2,7 2,7

Laju Aliran

Udara

H m³/min (cfm)

12,0 (424) 12,0 (424) 15,0 (530) 15,0 (530)

L 8,0 (283) 8,0 (283) 10,0 (353) 10,0 (353)

Kipas

Tipe Kipas Turbo Kipas Turbo

Output Motor W 55 55

Kecepatan Langkah

2 Langkah 2 Langkah

Kendali Arah Udara Mendatar, Kebawah Mendatar, Kebawah

Arus Berjalan (Terpasang) A 0,49 0,45 0,61 0,56

Komsumsi Daya (Terpasang) W 97 89 120 111

Faktor Daya (Terpasang) % 86,1 86,0 85,5 86,2

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) ★ mm 260 (286) × 575 × 575 260 (286) × 575 × 575

Dimensi Kemasan (H × W × D) mm 370 × 687 × 674 370 × 687 × 674

Berat (Massa) kg 17,5 17,5

Berat Bruto (Massa Bruto) kg 21 21

Tingkat Tekanan Suara

H / L

dB(A)

36.0/27.0

41.0/32.0

41,0/32,0

Tingkat Daya Suara dB 53,0 — 58,0 —

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 12,7 12,7

Pembuangan mm VP20 (O.D 26 / I.D 20) VP20 (O.D 26 / I.D 20)

No. Gambar 3D060409 3D040436

Catatan: ★ ( ) : dimensi termasuk kotak kendali Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

Spesifikasi 42

Pompa panas SiBE121135_A

Tipe Ceiling Suspended

50 Hz, 220 - 230 - 240 V

Model FHQ35BWV1B FHQ50BWV1B

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 3,5 kW Kelas 5,0 kW

Warna Panel Putih Putih

Laju Aliran Udara

H m³/min

13,0 (459) 13,0 (459) 13,0 (459) 13,0 (459)

L 10,0 (353) 10,0 (353) 10,0 (353) 10,0 (353)

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 62 62

Kecepatan Langkah

2 Langkah 2 Langkah

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur Dapat dilepas/dapat dicuci/Anti jamur

Pengendalian suhu Pengendalian Mikrokomputer Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 195 × 960 × 680 195 × 960 × 680

Dimensi Kemasan (H × W × D) mm 279 × 1.046 × 818 279 × 1.046 × 818

Berat (Massa) kg 24 25

Berat Bruto (Massa Bruto) kg 31 32

Tekanan Suara

H / L

dB(A)

37/32

38/33

Tingkat Daya Suara dB 53 54

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4 6,4

Gas mm 9,5 12,7

Pembuangan mm VP20 (O.D. 26 / I.D. 20) VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D075705 3D075706

Model

FHQ60BWV1B

Pendinginan Pemanasan

Kapasitas Terpasang Kelas 6,0 kW

Warna Panel Putih

Laju Aliran Udara

H m³/min

17,0 (600) 16,0 (565)

L 13,0 (459) 13,0 (459)

Kipas

Tipe Kipas Siroko

Output Motor W 62

Kecepatan Langkah

2 Langkah

Kendali Arah Udara Kanan, Kiri, Mendatar, Kebawah

Filter udara Dapat dilepas/dapat dicuci/Anti jamur

Pengendalian suhu Pengendalian Mikrokomputer

Dimensi (H × W × D) mm 195 × 1.160 × 680

Dimensi Kemasan (H × W × D) mm 279 × 1.246 × 818

Berat (Massa) kg 27

Berat Bruto (Massa Bruto) kg 35

Tekanan Suara

H / L

dB(A)

39/33

Tingkat Daya Suara dB 55

Isolasi Panas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,4

Gas mm 12,7

Pembuangan mm VP20 (O.D. 26 / I.D. 20)

No. Gambar 3D075707

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

43 Spesifikasi

SiBE121135_A Pompa panas

Tipe Ceiling Mounted Built-in 50 Hz, 220 - 230 - 240 V /

50 Hz, 230 V 60 Hz, 220 V

Model FDBQ25B8V1 FBQ35C8VEB

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 2,5 kW Kelas 3,5 kW

Panel Dekorasi

Model — BYBS45DJW1

Warna — Putih

Dimensi (H × W × D) — 55 × 800 × 500

Berat (Massa) kg — 3,5

Laju Aliran Udara

H m³/min

6,5 6,95 16,0

L 5,2 5,2 11,0

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 10 140

Kecepatan Langkah

2 Langkah 2 Langkah

Filter udara Jaring resin tahan jamur Jaring resin tahan jamur

Dimensi (H × W × D) mm 230 × 652 × 502 300 × 700 × 700

Dimensi Kemasan (H × W × D) mm 301 × 753 × 584 325 × 920 × 900

Berat (Massa) kg 17 25

Berat Bruto (Massa Bruto) kg 18 28

Tekanan Suara

H / L

dB(A)

35/28

35/29

37/29

Tingkat Daya Suara

H / L dB 55/49 63 / —

Isolasi Panas — Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6,35 6,35 (Flare / Penyambung)

Gas mm 9,52 9,52 (Flare / Penyambung)

Pembuangan mm O.D. 27,2 VP25 (O.D. 32 / I.D. 25)

Model FBQ50C8VEB FBQ60C8VEB

Pendinginan Pemanasan Pendinginan Pemanasan

Kapasitas Terpasang Kelas 5,0 kW Kelas 6,0 kW

Panel Dekorasi

Model BYBS45DJW1 BYBS71DJW1

Warna Putih Putih

Dimensi (H × W × D) 55 × 800 × 500 55 × 1.100 × 500

Berat (Massa) kg 3,5 4,5

Laju Aliran

Udara

H m³/min

16,0 18,0

L 11,0 15,0

Kipas

Tipe Kipas Siroko Kipas Siroko

Output Motor W 140 350

Kecepatan Langkah

2 Langkah 2 Langkah

Filter udara Jaring resin tahan jamur Jaring resin tahan jamur

Dimensi (H × W × D) mm 300 × 700 × 700 300 × 1.000 × 700

Dimensi Kemasan (H × W × D) mm 355 × 920 × 920 355 × 1.220 × 900

Berat (Massa) kg 25 34

Berat Bruto (Massa Bruto) kg 28 41

Tekanan Suara

H / L

dB(A)

37/29

37/29

Tingkat Daya Suara

H / L dB 63 / — 57 / —

Isolasi Panas Kedua Pipa Cair dan Gas Kedua Pipa Cair dan Gas

Sambungan Perpipaan

Cairan mm 6.35 (Flare / Penyambung) 6.35 (Flare / Penyambung)

Gas mm 12,7 (Flare / Penyambung) 12,7 (Flare / Penyambung)

Pembuangan mm VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)

a

Rumus Konversi

kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35,3

SiBE121135_A Unit Outdoor

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

44

Bagian 3

Diagram Pengkabelan

Konektor Papan Sirkuit

Cetak

1. Unit Outdoor ............................................................................................. 44

2. Unit Indoor ................................................................................................ 47 2.1 FTXG25/35/50JV1BW(A) ....................................................................47

2.2 CTXS15/35K2V1B, FTXS20/25K2V1B ................................................49

2.3 FTXS35/42/50K2V1B, FTXS25/35/42/50J2V1B,

ATXS20/25/35/42/50G2V1B ...............................................................51

2.4 FTXS60/71GV1B ................................................................................53

2.5 FVXG25/35/50K2V1B .........................................................................55

2.6 FVXS25/35/50FV1B ...........................................................................57

2.7 FLXS25/35/50/60BAVMB ....................................................................59

2.8 FDXS25/35E7VMB, FDXS50/60C7VMB .............................................61

2.9 FCQG35/50/60FVEB ..........................................................................63

2.10 FFQ25/35/50/60B9V1B .......................................................................65

2.11 FHQ35/50/60BWV1B ..........................................................................66

2.12 FDBQ25B8V1 .....................................................................................67

2.13 FBQ35/50/60C8VEB ...........................................................................68

3. Remote Kontrol Kabel.............................................................................. 70 3.1 BRC1D528 .........................................................................................70

3.2 BRC1E52A7, BRC1E52B7..................................................................71

SiBE121135_A

45 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

1. Unit Outdoor

PCB Utama

1) S10 Konektor untuk papan terminal (transmisi indoor - outdoor)

2) S15 Konektor untuk kunci Mode COOL / HEAT

Lihat hal 251 untuk penjelasan rinci.

3) S20 (putih) Konektor untuk port A kumparan katup ekspansi elektronik

4) S21 (merah) Konektor untuk port B kumparan katup ekspansi elektronik

5) S22 (biru) Konektor untuk port C kumparan katup ekspansi elektronik

6) S23 (kuning) Konektor untuk port D kumparan katup ekspansi elektronik (untuk model

ruangan 4 dan 5)

7) S24 (hijau) Konektor untuk port E kumparan katup ekspansi elektronik (untuk model

ruangan 5 saja)

8) S40 Konektor untuk pengaman beban lebih

9) S51, S101 Konektor untuk PCB monitor servis

10)S70 Konektor untuk motor kipas outdoor

11) S80 Konektor untuk kumparan katup empat arah

12) S90 Konektor untuk Termistor

(Suhu outdoor, penukar panas outdoor, suhu pipa buang)

13) S92 Konektor untuk Termistor pipa gas

14) S93 Konektor untuk Termistor pipa cair 15)AC1,

AC2 Konektor untuk papan terminal (catu daya)

16)HR1, HR2 Konektor untuk reaktor

17)E1, E2 Konektor untuk kabel bumi

18)U, V, W Konektor untuk kompresor

19) FU1 Sekring (30 A, 250 V)

20)FU2, FU3 Sekring (3.15 A, 250

V) 21)V2, V3, V5 Varistor

V6, V11 (untuk kelas 40 - 58 )

V9, V100 (untuk kelas 68 - 90 )

Kelas 40/50/52/58

AC1 E1 E2 FU2 V3 V11

FU1

V2

V6

AC2

HR1

HR2

S15

S10

S101

V5

S80

S93 S92 S90 S40 2P165232-2

S23 S22 S21 S20 S70 S51 FU3 W V U 2P165232-4 2P165232-7

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

46

Unit Outdoor SiBE121135_A

Kelas 68/75

AC1 E1 E2 FU2 V3

FU1

V2

V9

AC2

V100

HR1

HR2

S10

S15

S101

V5

S80

S93 S92 S90 S70 S40 S51 FU3 W V U

S23 S22 S21 S20 3P194316-1

3P194316-2 3P194316-4

3P194316-5

Kelas 80/90

AC1 E1 E2 FU2 V3

FU1

V2

V9

AC2

V100

HR1

(putih)

HR2

(biru)

S10

S15

S101

V5

S80

S24

S93

S23 S22

S92

S21

S90

S20

S40 S51 FU3

S70

W V U

2P171491-1

2P171491-2 2P171491-8

2P171491-9

47 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Outdoor

Monitor Servis

PCB

1) S52, S102 Konektor untuk PCB utama

2) LED A LED untuk monitor servis (hijau)

3) LED1 - LED4 LED untuk monitor servis (merah)

4) LED 5 LED untuk monitor servis (merah) (untuk model 5 ruangan saja)

5) SW1 Saklar [ON/OFF] operasi paksa

Lihat hal 243 untuk penjelasan rinci.

6) SW2 Saklar mode operasi

Lihat hal 243 untuk penjelasan rinci.

7) SW3 Saklar pemeriksaan kesalahan pengkabelan

Lihat hal 244 untuk penjelasan rinci.

8) SW4 Saklar pengaturan ruangan prioritas

Lihat hal 250 untuk penjelasan rinci.

9) SW5 Saklar pengaturan mode senyap MALAM (NIGHT QUIET)

Lihat hal 252 untuk penjelasan rinci.

Untuk model 3 atau 4 ruangan

LED3 LED1

S52 LED4 LED2 LED A

SW2

SW5

SW1 SW3 SW4 S102

3P165332-1

Untuk model 3 atau 5 ruangan

LED5 LED3 LED1

S52 LED4 LED2 LED A

SW2

SW5

SW1 SW3 SW4 S102

3P173588-1

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

48

Unit Indoor SiBE121135_A

F1U V1 S32

S200

S41

S

JB

JC

2. Unit Indoor

2.1 FTXG25/35/50JV1BW(A)

PCB Kendali

1) S21 Konektor untuk kendali terpusat (HA)

2) S25 Connector for INTELLIGENT EYE sensor PCB

3) S32 Termistor penukar panas indoor

4) S41 Konektor untuk motor ayun

5) S42 Konektor untuk motor reduksi (mekanisme panel depan) dan sakelar pembatas

6) S46 Konektor untuk PCB tampilan/penerima sinyal

7) S200 Konektor untuk motor kipas

8) H1, H2, H3,

FG

Konektor untuk papan terminal

9) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati (menyala kembali otomatis)

Lihat hal 257 untuk penjelasan rinci.

10) LED A LED untuk memantau servis (hijau)

11) F1U Sekring (3,15 A, 250 V)

12) V1 Varistor

H1 FG H2 H3

42

S21 LED A S25 S46

2P254830-1

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JB dan JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

49 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

Penerima Sinyal/

PCB Tampilan

1) S51 Konektor untuk PCB kendali

2) S52 Konektor untuk Termistor suhu ruangan

3) S1W Tombol [ON/OFF] operasi pendinginan paksa

4) H1P LED untuk operasi (beberapa warna)

5) H2P LED untuk INTELLIGENT EYE (hijau)

6) JA Jumper pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

H2P

H1P

S51

JA

S1W

S52

3P254832-1

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JA.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda memotong

salah satu darinya.

PCB Sensor

INTELLIGENT EYE 1) S36 Konektor untuk PCB kendali

3P255914-1

S36

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

50

Unit Indoor SiBE121135_A

2.2 CTXS15/35K2V1B, FTXS20/25K2V1B

PCB Kendali

1) S6 Konektor untuk motor ayun (bilah mendatar)

2) S25 Connector for INTELLIGENT EYE sensor PCB

3) S26 Konektor untuk PCB tampilan

4) S32 Konektor untuk Termistor penukar panas indoor

5) S200 Konektor untuk motor kipas

6) S403 Konektor untuk PCB adaptor (pilihan)

7) FG1, FG2 Konektor untuk papan terminal (pembumian kerangka)

8) H1, H2, H3 Konektor untuk papan terminal (transmisi indoor - outdoor)

9) V1 Varistor

10) JA Jumper pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

11) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati (menyala kembali otomatis)

Lihat hal 257 untuk penjelasan rinci.

12) LED A LED untuk memantau servis (hijau)

13) FU1 Sekring (3,15 A, 250 V)

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JA, JB dan

JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

S32 S26 S6

JA JC JB

LED A

S25 S200

S403

FU1

V1

FG1, FG2 H1 H3 H2

2P297453-1

51 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

PCB Tampilan

1) S27 Konektor untuk PCB kendali

2) SWI (S1W) Tombol [ON/OFF] operasi pendinginan paksa

3) LED1 (H1P) LED untuk operasi (hijau)

4) LED2 (H2P) LED untuk timer (kuning)

5) LED3 (H3P) LED untuk INTELLIGENT EYE (hijau)

6) RTH1 (R1T) Termistor suhu ruangan

S27

SW1 LED3 LED2 LED1

(Sisi solder)

RTH1

3P185701-3

PCB Sensor

INTELLIGENT EYE

1) S36 Konektor untuk PCB kendali

S36

3P296737-1

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

52

Unit Indoor SiBE121135_A

S32 FG

H3 H2 H1 LED A FU1

JCJAJB S21

S47

2.3 FTXS35/42/50K2V1B, FTXS25/35/42/50J2V1B,

ATXS20/25/35/42/50G2V1B

PCB Kendali

1) S1 Konektor untuk motor kipas dc

2) S21 Konektor untuk kendali terpusat (HA)

3) S25 Connector for INTELLIGENT EYE sensor PCB

4) S32 Termistor penukar panas indoor

5) S41 Konektor untuk motor ayun

6) S46 Konektor untuk PCB tampilan

7) S47 Konektor untuk PCB penerima sinyal

8) H1, H2, H3,

FG

Konektor untuk papan terminal

9) JA Jumper pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

10) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati (menyala kembali otomatis)

Lihat hal 257 untuk penjelasan rinci.

11) LED A LED untuk memantau servis (hijau)

12) FU1 Sekring (3,15 A, 250 V)

13) V1 Varistor

S41 S1

S46

S25 V1

2P206687-1

2P206687-5

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JA, JB

dan JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

53 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

Penerima Sinyal

PCB 1) S48 Konektor untuk PCB kendali

3P210728-1

PCB Tampilan

1) S49 Konektor untuk PCB kendali

2) SW1 Tombol [ON/OFF] operasi pendinginan paksa

3) LED1 (H1P) LED untuk operasi (hijau)

4) LED2 (H2P) LED untuk timer (kuning)

5) LED3 (H3P) LED untuk INTELLIGENT EYE (hijau)

6) RTH1 (R1T) Termistor suhu ruangan

RTH1 SW1

3P210728-1

PCB Sensor

INTELLIGENT EYE 1) S26 Konektor untuk PCB kendali

S26

3EB86013-1

LED3 LED2 LED1

S48

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

54

Unit Indoor SiBE121135_A

S32

H3 FG H2 FU1 H1

LED A (3,15A)

S46

S25

S21

S47JCJA JB

2.4 FTXS60/71GV1B

PCB Kendali

1) S1 Konektor untuk motor kipas DC

2) S21 Konektor untuk kendali terpusat (HA)

3) S25 Connector for INTELLIGENT EYE sensor PCB

4) S32 Konektor untuk Termistor penukar panas indoor

5) S41 Konektor untuk motor ayun

6) S46 Konektor untuk PCB tampilan

7) S47 Konektor untuk PCB penerima sinyal

8) H1, H2, H3,

FG

Konektor untuk papan terminal

9) V1 Varistor

10) JA Jumper pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

11) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati (menyala kembali otomatis)

Lihat hal 257 untuk penjelasan rinci.

12) LED A LED untuk memantau servis (hijau)

13) FU1 Sekring (3,15 A, 250 V)

S41 S1

V1

2P227881-2

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JA, JB dan

JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

55 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

Penerima Sinyal

PCB 1) S48 Konektor untuk PCB kendali

3P247309-1

PCB Tampilan

1) S49 Konektor untuk PCB kendali

2) SW1 Tombol [ON/OFF] operasi pendinginan paksa

3) LED1 (H1P) LED untuk operasi (hijau)

4) LED2 (H2P) LED untuk timer (kuning)

5) LED3 (H3P) LED untuk INTELLIGENT EYE (hijau)

6) RTH1 (R1T) Termistor suhu ruangan

RTH1

LED3 LED2 LED1

S49

SW1

3P247309-1

PCB Sensor

INTELLIGENT EYE

1) S36 Konektor untuk PCB kendali

S36

3P227885-1

S48

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

56

Unit Indoor SiBE121135_A

2.5 FVXG25/35/50K2V1B

PCB Utama

1) S1 Konektor untuk motor kipas

2) S2 Konektor untuk papan terminal

3) S6 Konektor untuk motor ayun

4) S21 Konektor untuk kendali terpusat (HA)

5) S26 Konektor untuk PCB servis

6) S30 Konektor untuk kumparan katup ekspansi elektronik (katup yang

dioperasikan motor)

7) S32 Konektor untuk Termistor penukar panas indoor

8) S33 Konektor untuk Termistor suhu ruangan

9) S34 Konektor untuk Termistor panel radiant

10) S46 Konektor untuk PCB tampilan

11) FG Konektor untuk pembumian

12) V1 Varistor

13) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati

Lihat hal 257 untuk penjelasan rinci.

14) F1U Sekring (3,15A, 250V)

15) LED A LED untuk monitor servis (hijau)

JC JB LED A S1 V1 F1U S2

S21

S30

S6 S32 S33 S34 S26 S46 FG

2P273247-1

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JB dan JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda memotong

salah satu darinya.

57 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

PCB Tampilan

1) S56 Konektor untuk PCB utama

2) S1W Tombol [ON/OFF] operasi pendinginan paksa

3) H1P LED untuk operasi (hijau)

4) H2P LED untuk timer (kuning)

5) H3P LED untuk operasi RADIANT (merah)

S56

S1W

H3P H1P H2P

3P273252-1

PCB Servis

1) S27 Konektor untuk PCB utama

2) S2W-1 Saklar pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

Pertahankan saklar lain sebagaimana pengaturan pabrik (OFF).

S27

S2W-1

3P273254-1

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

58

Unit Indoor SiBE121135_A

E1

H1

V2

V1

JB

JA

JC

S

H2 S48

FU1

H3 S46

2.6 FVXS25/35/50FV1B

PCB Kendali

1) S1 Konektor untuk motor kipas

2) S21 Konektor untuk kendali terpusat (HA)

3) S26 Konektor untuk PCB servis

4) S32 Termistor penukar panas indoor

5) S41 Konektor untuk motor outlet udara rendah

6) S42 Konektor untuk motor ayun

7) S46 Konektor untuk PCB tampilan

8) S48 Konektor untuk PCB sensor

9) H1, H2, H3 Konektor untuk papan

terminal 10)E1 Terminal untuk kabel

pembumian

11) V1, V2 Varistor

12) JA Jumper pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

13) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati

Lihat hal 257 untuk penjelasan rinci.

14) FU1 (F1U) Sekring (3,15A, 250V)

15) LED A LED untuk monitor servis (hijau)

32

S1 LED A S21 S41 S42 S26

2P191446-1

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JA, JB dan

JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

59 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

PCB Sensor

1) S49 Konektor untuk PCB kendali

2) RTH2 (R1T) Termistor suhu ruangan

RTH2

S49

3P191450-1

PCB Servis

1) S27 Konektor untuk PCB kendali

2) SW2-4 Saklar untuk pengaturan batas aliran udara ke atas

Lihat hal 257 untuk penjelasan rinci.

Pertahankan saklar lain sebagaimana pengaturan pabrik.

3) SW4 (S4W) Saklar untuk pemilihan aliran udara

Lihat hal 79 untuk penjelasan rinci.

SW4

S27

SW2-4

3P191448-1

PCB Tampilan

1) S47 Konektor untuk PCB kendali

2) SWI (S1W) Tombol [ON/OFF] operasi pendinginan paksa

3) LED1 (H1P) LED untuk operasi (hijau)

4) LED2 (H2P) LED untuk timer (kuning)

LED1

LED2 SW1 S47

3P191447-1

★ LED3 tidak berfungsi.

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

60

Unit Indoor SiBE121135_A

2.7 FLXS25/35/50/60BAVMB

PCB Kendali

1) S6 Konektor untuk motor ayun (ayunan mendatar)

2) S7 Konektor untuk motor kipas AC

3) S21 Konektor untuk kendali terpusat (HA)

4) S24 Konektor untuk PCB tampilan

5) S26 Konektor untuk PCB penerima sinyal

6) S32 Konektor untuk Termistor penukar panas indoor

7) S37 Konektor untuk PCB catu daya

8) JA Jumper pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

9) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati

Lihat hal 257 untuk penjelasan rinci.

10) SW2 Saklar pemilihan untuk instalasi (plafon atau lantai)

Lihat hal 257 untuk penjelasan rinci.

11) LED A LED untuk monitor servis (hijau)

S21 LED A

SW2

S7

S26

S6

S32

S24 JC JB JA S37

2P084352-3

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JA, JB dan

JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

61 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

PbF C1

SW1 C2

EX511 REV 12

S27

RTH I PHOTO

2P084377- W LU C3

PCB Catu

Daya

1) S36 Konektor untuk PCB kendali

2) H1, H2, H3 Konektor untuk papan terminal

3) H4, H5, H6 Konektor untuk motor kipas AC

4) V1 Varistor

5) FU1 Sekring (3,15A, 250V)

2P084361-1

PCB Tampilan

1) S25 Konektor untuk PCB kendali

2) LED1 (H1P) LED untuk operasi (hijau)

3) LED2 (H2P) LED untuk timer (kuning)

4) LED3 (H3P) LED untuk operasi HOME LEAVE (merah)

LED3 LED2 LED1

S25

2P084377-5

PCB Penerima

Sinyal

1) S27 Konektor untuk PCB kendali

2) S31 (RTH) Termistor suhu ruangan

3) SWI (S1W) Tombol [ON/OFF] operasi pendinginan paksa

SW1

S27

S31 (RTH) 2P084377-5

H4

S36 H5

H6

H1

FU1

H3 V1 H2

3

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

62

Unit Indoor SiBE121135_A

FU1

S1 H

H

H

V1

G

S7

S21

FDXS25/35E7VMB, FDXS50/60C7VMB

PCB Kendali

1) S1 Konektor untuk motor kipas AC

2) S7 Konektor untuk motor kipas AC (Hall IC)

3) S21 Konektor untuk kendali terpusat (HA)

4) S26 Konektor untuk PCB tampilan

5) S32 Konektor untuk Termistor penukar panas indoor

6) H1, H2, H3 Konektor untuk papan terminal

7) GND Konektor untuk papan terminal (pembumian)

8) JA Jumper pengaturan alamat

Lihat hal 253 untuk penjelasan rinci.

9) JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF

JC Fungsi pemulihan listrik mati (menyala kembali otomatis)

Lihat hal 257 untuk penjelasan rinci.

10) LED A LED untuk memantau servis (hijau)

11) FU1 Sekring (3,15A, 250V)

12) V1 (V1TR) Varistor

2

1

3

ND

LED A JA JB JC S32 S26

2P131149-1

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper selain daripada JA, JB dan

JC.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

63 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

PCB Tampilan

1) S1 Konektor untuk PCB kendali

2) SWI (S1W) Tombol [ON/OFF] operasi pendinginan paksa

3) LED1 (H1P) LED untuk operasi HOME LEAVE (merah)

4) LED2 (H2P) LED untuk timer (kuning)

5) LED3 (H3P) LED untuk operasi (hijau)

6) RTH1 (R1T) Termistor suhu ruangan

S1

LED3

LED2

RTH1

LED1 SW1

2P084375-1

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

64

Unit Indoor SiBE121135_A

FCQG35/50/60FVEB

[A1P]

1) X15A Konektor untuk saklar apung

2) X16A Konektor untuk Termistor suhu ruangan

3) X17A, X18A Konektor untuk Termistor penukar panas indoor

4) X20A Konektor untuk motor kipas

5) X24A Konektor untuk PCB penerima sinyal

(apabila remote kontrol nirkabel digunakan)

6) X27A Konektor untuk papan terminal (untuk pengkabelan antar unit)

7) X30A Konektor untuk papan terminal (untuk remote kontrol kabel)

8) X33A Konektor untuk PCB adaptor pengkabelan (pilihan)

9) X35A Konektor untuk adaptor kendali kelompok (pilihan)

10) X36A Konektor untuk panel dekorasi pembersihan sendiri (pilihan)

11) X65A, X70A Konektor untuk [A2P]

12) HAP LED untuk monitor servis (hijau)

13) SS1 Saklar pemilih untuk keadaan darurat

X24A

X15A

X18A

X16A X27A

X36A

X17A HAP X33A X35A

2P263068-4

X65A X20A SS1 X70A X30A

65 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

[A2P]

1) X1A, X7A Konektor untuk [A1P]

2) X2A Konektor untuk kotak sensor (pilihan)

3) X4A Konektor untuk PCB sensor kelembaban [A3P]

4) X8A Konektor untuk panel dekorasi pembersihan sendiri (pilihan)

5) X9A Konektor untuk motor ayun

6) X10A Konektor untuk motor pompa pengurasan

7) HAP LED untuk monitor servis (hijau)

X9A X2A X4A X10A X8A X7A

X1A

HAP

2P263045-1

[A3P]: PCB Sensor

Kelembaban 1) CN1 Konektor untuk [A2P]

Sensor kelembaban

CN1

4EB86011-3

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

66

Unit Indoor SiBE121135_A

2.10 FFQ25/35/50/60B9V1B

PCB Kendali

1) X5A Konektor untuk papan terminal (untuk remote kontrol kabel)

2) X10A, X11A Konektor untuk trafo

3) X15A Konektor untuk saklar apung

4) X17A, X18A Konektor untuk Termistor penukar panas indoor

5) X19A Konektor untuk Termistor suhu ruangan

6) X20A Konektor untuk motor kipas

7) X24A Konektor untuk PCB penerima sinyal

(apabila remote kontrol nirkabel digunakan)

8) X25A Konektor untuk motor pompa pengurasan

9) X27A Konektor untuk papan terminal (untuk pengkabelan antar unit)

10) X33A Konektor untuk PCB adaptor pengkabelan (pilihan)

11) X35A Konektor untuk adaptor kendali kelompok (pilihan)

12) X36A Konektor untuk motor ayun

13) X40A Konektor untuk input ON/OFF dari luar (pilihan)

14) X60A, X61A Konektor untuk adaptor antarmuka (pilihan)

15) HAP LED untuk monitor servis (hijau)

16) SS1 Saklar pemilih untuk keadaan darurat

X27A X11A

X10A

X33A

X19A X60A X61A

X5A

X35A

X20A

X24A

HAP

X25A

X18A X36A X40A

SS1 X17A X15A

2P197080-6

67 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

2.11 FHQ35/50/60BWV1B

PCB Kendali

1) X5A Konektor untuk papan terminal (untuk remote kontrol kabel)

2) X10A, X11A Konektor untuk trafo

3) X14A Konektor untuk saklar batas (untuk sirip ayun)

4) X15A Konektor untuk saklar apung (pilihan)

5) X17A, X18A Konektor untuk Termistor penukar panas indoor

6) X19A Konektor untuk Termistor suhu ruangan

7) X20A, X26A Konektor untuk motor kipas

8) X24A Konektor untuk PCB penerima sinyal

(apabila remote kontrol nirkabel digunakan)

9) X25A Konektor untuk motor pompa pengurasan (pilihan)

10) X27A Konektor untuk papan terminal (untuk pengkabelan antar unit)

11) X29A Konektor untuk motor ayun

12) X33A Konektor untuk PCB adaptor pengkabelan (pilihan)

13) X35A Konektor untuk adaptor kendali kelompok (pilihan)

14) X40A Konektor untuk input ON/OFF dari luar (pilihan)

15) X60A, X61A Konektor untuk adaptor antarmuka (pilihan)

16) HAP LED untuk monitor servis (hijau)

17) SS1 Saklar pemilih untuk keadaan darurat

X14A X61A X33A X11A X27A

X15A

X40A

X20A

X18A X29A

X19A

X17A SS1 X35A X60A

X10A X5A

HAP X24A X26A X25A

2P197075-6

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

68

Unit Indoor SiBE121135_A

2.12 FDBQ25B8V1

PCB Kendali

1) X5A Konektor untuk papan terminal (untuk remote kontrol kabel)

2) X10A, X11A Konektor untuk trafo

3) X17A Konektor untuk Termistor penukar panas indoor

4) X18A Konektor untuk termistor pipa cair

5) X19A Konektor untuk Termistor suhu ruangan

6) X21A Konektor untuk motor kipas

7) X27A Konektor untuk papan terminal (untuk pengkabelan antar unit)

8) X33A Konektor untuk PCB adaptor pengkabelan (pilihan)

9) X35A Konektor untuk adaptor kendali kelompok (pilihan)

10) X40A Konektor untuk input ON/OFF dari luar (pilihan)

11) X60A, X61A Konektor untuk adaptor antarmuka (pilihan)

12) HAP LED untuk monitor servis (hijau)

13) SS1 Saklar pemilih untuk keadaan darurat

X61A X33A X11A X27A

X18A

X19A

X17A

SS1 X60A HAP X35A X10A X5A X40A X21A

2P095008-8

69 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Unit Indoor

2.13 FBQ35/50/60C8VEB

PCB Kendali

1) X15A Konektor untuk saklar apung

2) X16A Konektor untuk Termistor suhu ruangan

3) X17A Konektor untuk Termistor penukar panas indoor

4) X18A Konektor untuk termistor pipa cair

5) X25A Konektor untuk motor pompa pengurasan

6) X27A Konektor untuk papan terminal (untuk pengkabelan antar unit)

7) X28A Konektor untuk pengkabelan catu daya (pilihan)

8) X30A Konektor untuk papan terminal (untuk remote kontrol kabel)

9) X33A Konektor untuk PCB adaptor pengkabelan (pilihan)

10) X35A Konektor untuk adaptor kendali kelompok (pilihan)

11) X70A Konektor untuk PCB kipas

12) X85A Konektor untuk beberapa zona (pilihan)

13) HAP LED untuk monitor servis (hijau)

14) SS1 Saklar pemilih untuk keadaan darurat

X35A X33A X85A SS1X70A

X27A

X28A

X25A

X17A

X18A

X15A

X30A

HAP X16A

2P202878-7

PCB Kipas

(untuk

FBQ35/50C8VEB

)

1) X3A Konektor untuk PCB kendali

2) X6A Konektor untuk reaktor

3) X8A Konektor untuk motor kipas

4) X10A Konektor untuk papan terminal (catu daya)

5) F2U Sekring (5 A, 250 V)

6) F4U Sekring (6,3 A, 250 V)

7) HAP LED untuk monitor servis (hijau)

F4U X6A

X10A

F2U

X3A HAP X8A

2P207230-1

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

70

Unit Indoor SiBE121135_A

PCB Kipas

(untuk

FBQ60C8VEB)

1) X1A, X2A Konektor untuk motor kipas

2) X3A Konektor untuk PCB kendali

3) X6A Konektor untuk reaktor

4) X9A Konektor untuk PCB kapasitor

5) X10A Konektor untuk papan terminal (catu daya)

6) F3U Sekring (6,3 A, 250 V)

7) HAP LED untuk monitor servis (hijau)

F3U X6A

X10A

X9A

X1A

X3A HAP

X2A

2P210642-2

PCB Kapasitor

(FBQ60C8VEB

saja)

Konektor untuk X9A pada PCB kipas

3P217472-1

71 Diagram Pengkabelan Konektor Papan Sirkuit Cetak

SiBE121135_A Remote Kontrol Kabel

3. Remote Kontrol Kabel

BRC1D528

Konektor dan

komponen lain

Rincian PCB

1) P1, P2 Terminal unit indoor

2) R1T Termistor suhu ruangan

3) SS1 Saklar pengaturan MAIN / SUB

Lihat hal 261 untuk penjelasan rinci.

SS1

2P113638-2

R1T

P2 P1

Diagram Pengkabelan Konektor Papan Sirkuit Cetak

72

Remote Kontrol Kabel SiBE121135_A

P2

P1

2P2980

2P2980

BRC1E52A7, BRC1E52B7

Konektor dan

komponen lain

Rincian PCB

1) P1, P2 Terminal unit indoor

2) R1T Termistor suhu ruangan

R1T

37-1 37-2

SiBE121135_A

Fungsi dan Pengendalian

72

Bagian 4

Fungsi dan Kendali 1. Fungsi Unit Indoor RA ............................................................................. 73

Kendali Suhu ...............................................................................................73 Prinsip Frekuensi .........................................................................................73 Kendali Awal Operasi ..................................................................................75 Kendali Arah Aliran Udara ...........................................................................76 Kendali Kecepatan Kipas untuk Unit Indoor ..................................................80 Operasi RADIANT .......................................................................................81 Program Operasi Kering ..............................................................................83 Operasi Otomatis ........................................................................................84 Kendali Termostat .......................................................................................85 Mode NIGHT SET .......................................................................................86 Operasi ECONO..........................................................................................87 Operasi HOME LEAVE ................................................................................88 Operasi INTELLIGENT EYE .......................................................................90 Operasi INTELLIGENT EYE 2-Area ............................................................91 Operasi Inverter POWERFUL .....................................................................93 Lampu Indikator Banyak Warna / Lampu TIMER ..........................................94 Pengaturan Kecerahan pada Layar Unit Indoor ............................................95 Pengaturan Jam ..........................................................................................96 Operasi WEEKLY TIMER ............................................................................97 Fungsi-fungsi Lainnya................................................................................ 103

2. Fungsi Unit Indoor SA............................................................................ 104 Kendali Pompa Pengurasan ...................................................................... 104 Sensor Termostat pada Remote Kontrol .................................................... 106 Kendali Pencegahan Kebekuan ................................................................. 108 Kendali Hot Start (Pada Operasi Pemanasan Saja) .................................... 109

3. Fungsi Termistor .................................................................................... 110 4. Spesifikasi Kendali ................................................................................. 112

Mode Hirarki .............................................................................................. 112 Kendali Frekuensi ...................................................................................... 113 Kendali Pengubahan Mode / Start-Up ........................................................ 116 Kendali Suhu Pipa Buang .......................................................................... 117 Kendali Arus input ..................................................................................... 118 Kendali Perlindungan Kebekuan ................................................................ 118 Kendali pemutusan Puncak Pemanasan .................................................... 119 Kendali Kipas Outdoor ............................................................................... 120 Fungsi Perlindungan Kompresi Cairan ....................................................... 120 Kendali Pencairan ..................................................................................... 121 Batas Tekanan Tinggi Hz Rendah.............................................................. 122 Kendali Katup Ekspansi Elektronik Outdoor ............................................... 122 Malfungsi .................................................................................................. 126

Fungsi Unit Indoor RA SiBE121135_A

73 Fungsi dan Pengendalian

1. Fungsi Unit Indoor RA

Pengendalian suhu

Definisi Suhu

Definisi suhu diklasifikasikan sebagai berikut:

Suhu ruangan : suhu bagian bawah ruangan

Suhu yang diatur: suhu yang diatur oleh remote kontrol

Suhu termistor ruangan : suhu yang dideteksi oleh termistor suhu ruangan

Suhu target : suhu yang ditentukan oleh mikrokomputer

★ Ilustrasi adalah untuk tipe wall mounted sebagai perwakilan.

Pengendalia

n suhu

Suhu ruangan dideteksi oleh termistor suhu ruangan. Namun, ada perbedaan antara "suhu

yang dideteksi oleh termistor suhu ruangan" dan "suhu bagian bawah ruangan", bergantung

pada jenis unit indoor atau kondisi pemasangannya. Sebetulnya, kontrol suhu dilakukan

dengan "suhu target yang disesuaikan dengan tepat untuk unit indoor" dan "suhu yang

terdeteksi oleh termistor suhu ruangan".

Prinsip Frekuensi

Parameter

Kendali

Utama

Frekuensi kompresor dikendalikan oleh 2 parameter berikut ini:

Kondisi beban operasi unit indoor

Perbedaan antara suhu termistor ruangan dan suhu target

Parameter

Kendali

Tambahan

Frekuensi target disesuaikan dengan parameter tambahan dalam kasus berikut:

Pembatasan frekuensi

Pengaturan Awal

Operasi pendinginan paksa

Prinsip Inverter Untuk mengatur kapasitas, diperlukan kontrol frekuensi. Inverter memungkinkan untuk

mengendalikan kecepatan putar kompresor. Tabel berikut menjelaskan prinsip inverter:

Fase Deskripsi

1 Sumber listrik AC yang disuplai diubah menjadi sumber listrik DC untuk saat ini.

2 Sumber listrik DC diubah menjadi sumber listrik AC tiga-fasa dengan frekuensi bervariasi. Ketika frekuensi meningkat, kecepatan putar kompresor meningkat yang

mengakibatkan peningkatan sirkulasi refrigeran. Hal ini menyebabkan jumlah pertukaran panas yang lebih besar per unit.

Ketika frekuensi menurun, kecepatan putar kompresor menurun mengakibatkan penurunan sirkulasi refrigeran. Hal ini menyebabkan jumlah pertukaran panas yang lebih kecil per unit.

Suhu target

Suhu termistor ruangan

Suhu yang diatur Suhu ruangan

(R12321)

Fungsi dan Pengendalian

74

Fungsi Unit Indoor RA SiBE121135_A

Gambar

Inverter

Gambar berikut ini menunjukkan gambaran skematik prinsip inverter:

Laju sirkulasi refrigeran (tinggi)

Jumlah udara penukar panas (besar)

Jumlah udara penukar panas (kecil)

50 Hz

60 Hz

tinggi f

rendah f

kecepatan tinggi

kecepatan rendah

Jumlah udara penukar panas (besar)

Jumlah udara penukar panas (kecil)

Laju sirkulasi refrigeran (rendah) (R2812)

Fitur Inverter Inverter menyediakan fitur berikut: Kapasitas pengaturan dapat diubah sesuai dengan perubahan suhu outdoor

dan beban pendinginan/pemanasan.

Pendinginan dan pemanasan cepat

Kecepatan putar kompresor meningkat ketika memulai pemanasan (atau pendinginan). Hal

ini memungkinkan untuk mencapai suhu yang diatur dengan cepat.

Bahkan selama cuaca sangat dingin, kapasitas tinggi dicapai. Hal ini dipertahankan

bahkan ketika suhu outdoor sebesar 2°C.

Pendinginan udara yang nyaman

Terintegrasi dengan pengaturan yang bagus untuk menjaga suhu kamar tetap konstan.

Pendinginan dan pemanasan hemat energi

Setelah suhu yang diatur tercapai, operasi hemat energi memungkinkan untuk

mempertahankan suhu kamar pada daya rendah.

Batas Frekuensi Fungsi berikut mengatur frekuensi minimal dan maksimal :

Frekuensi Fungsi

Rendah Kompensasi operasi katup empat arah Lihat hal 116.

Tinggi Fungsi pelindung kompresor. Lihat hal 117. Kendali Suhu Pipa Buang. Lihat hal 117. Kendali Arus input. Lihat hal 118. Kendali perlindungan kebekuan Lihat hal 118. Kendali pemutusan puncak pemanasan. Lihat hal 119. Kendali Pencairan. Lihat hal 121.

Operasi Paksa Lihat hal 243 untuk penjelasan rinci.

Da

ya

AC

frek= konstan frek=variabel

kapasitas= variabel

Da

ya

DC

75 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Start

(1) Membuka panel depan sepenuhnya (2) Output Sinyal D setelah

panel depan mulai bergerak

(3)Membuka sirip sepenuhnya (4) Menyebabkan kipas

berputar saat sirip melewati area terlarang bagi kipas

Berjalan

Kendali Awal Operasi

Uraian Tipe Wall Mounted: Seri FTXG

Sistem menjalankan kendali berikut di awal untuk melakukan setiap fungsi bagian dengan baik.

1. Membuka panel depan sepenuhnya

2. Output Sinyal D setelah panel depan mulai bergerak

3. Membuka sirip sepenuhnya setelah panel depan terbuka sepenuhnya

4. Menyebabkan kipas berputar saat sirip melewati area terlarang bagi kipas

Arus Kendali

(R14049)

Grafik Waktu

OFF

Start

Kendali awal operasi

ON

Tertutup penuh

Terbuka penuh

Terbuka penuh

: Posis i aktual panel atau

sirip

: Kendali tambahan motor

Area larangan

bagi kipas Tertutup

penuh

ON

OFF

Output

0

Dengan kendali berjalan

Dengan kendali mode operasi

Dengan kendali mode operasi

ON

OFF

Daya dipasok saat unit outdoor menerima sinyal D.

(R11910)

D

Kipas

Panel Depan

Sirip

Catu Daya (dari unit outdoor)

Fungsi dan Pengendalian

76

Fungsi Unit Indoor RA SiBE121135_A

Kendali Arah Aliran Udara

Sirip Ganda

Aliran Udara

Kuat

sirip

Bersudut

Lebar

Sirip yang besar mengirimkan udara bervolume besar ke bawah sampai lantai. Sirip

memberikan kendali optimal dalam operasi pendinginan, kering dan pemanasan.

<Cooling/Dry> (Pendinginan/Kering)

Selama operasi pendinginan atau kering sirip ditarik ke dalam unit indoor. Kemudian, udara

sejuk dapat dihembuskan jauh dan disebarkan ke seluruh ruangan.

<Pemanasan>

Selama operasi pemanasan, sirip besar mengarahkan aliran udara ke bawah untuk

menyebarkan udara hangat ke seluruh ruangan.

sirip, yang terbuat dari resin sintetis elastis, menyediakan banyak aliran udara yang menjamin

penyebaran udara nyaman.

Ayun-Otomatis Tabel berikut menjelaskan proses ayunan otomatis untuk pendinginan, kering, dan kipas:

Tipe Wall Mounted

Seri Ayunan Vertikal

(atas dan bawah) Ayunan horisontal

(kanan dan kiri)

Pendinginan

Kering

Pemanasan Kipas

FTXG

10˚ 15˚

60˚ 65˚

20˚ 25˚

75˚

70˚

10˚

80˚

75˚

(R11662) (R11664) (R11663)

CTXS

FTXS20/

15˚

— 25K

45˚ 45˚ 45˚

(R11256) (R11257) (R11256)

10˚

10˚

10˚

FTXS35/42/ 50K

10˚ 60˚

30˚ 10˚

60˚ 65˚ 60˚

(R18422) (R18423) (R18422) (R11404)

FTXS-J

15˚

30˚

50˚ 55˚

30˚

30˚

70˚ 65˚

30˚ 65˚

80˚

(R14208)

(R12182) (R11402) (R11404)

FTXS-G

10˚

40˚ 10˚

40˚

35˚ 5˚ 35˚

15˚ 15˚

55˚ 55˚

55˚ 55˚

(R2814) (R2815) (R2813) (R2816) (R2817)

ATXS

15˚ 30˚

50˚ 55˚

30˚

30˚

70˚ 65˚

30˚ 65˚

80˚

(R11403)

(R12182) (R11402) (R11404)

77 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Tipe Floor Standing Seri FVXG

Kisaran ayunan sirip adalah sama di setiap mode operasi.

(R14634)

Tipe Floor Standing: Seri FVXS

Ayunan Vertikal (naik dan turun)

Pendinginan/Kering

Pemanasan

Batas aliran

udara ke atas OFF

(R6831)

(R6829)

Batas aliran

udara ke atas ON

(R6832)

(R6830)

Tipe Floor / Ceiling Suspended Dual

Ayunan Vertikal (naik dan turun)

Pendinginan/Kering/Kipas

Pemanasan

Langit-langit

(R2964)

(R2963)

Lantai

(R2967)

(R2966)

Fungsi dan Pengendalian

78

Fungsi Unit Indoor RA SiBE121135_A

Aliran Udara 3-D Tipe Wall Mounted: Seri FTXS-J/G, ATXS

Gerakan ayunan tegak dan mendatar yang berulang-ulang alternatif memungkinkan

pendinginan udara merata ke seluruh ruangan. Fungsi ini efektif untuk penyalaan AC.

Saat ayunan mendatar dan tegak diatur untuk beroperasi otomatis, aliran udara menjadi aliran

udara 3-D. Gerakan ayunan mendatar dan tegak saling bergantian dan arah aliran udara

berubah dalam urutan yang ditunjukkan oleh diagram berikut.

(1): Bilah (sirip) tegak bergerak dari kanan ke kiri. (2): Bilah (sirip)

bergerak ke arah bawah.

(3): Bilah (sirip) tegak bergerak dari kiri ke kanan. (4): Bilah (sirip)

bergerak ke arah atas.

(2) (1)

(3) (4)

(R13554)

Operasi

ALIRAN

UDARA NYAMAN

Tipe Wall Mounted

Sirip horizontal dikendalikan agar tidak langsung menghembuskan udara secara langsung kepada orang di ruangan.

Pendinginan

/ Kering Pemanasan

A

(R11665)

B

(R12181)

A B

FTXG 5° 75°

CTXS, FTXS20/25K 0° 50°

FTXS35-50K 5° 70°

FTXS-J 8° 80°

FTXS-G 5° 55°

ATXS 5° 80°

79 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Pengaturan

Pemilihan Aliran

Udara

Tipe Floor Standing: Seri FVXS

Arah aliran udara dapat diatur dengan saklar pilihan aliran udara.

Membuka panel depan

PERHATIAN Sebelum membuka panel depan, pastikan untuk menghentikan operasi dan

mematikan pemutus arus. Jangan menyentuh sirip aluminium (penukar panas indoor)

di dalam unit indoor, karena dapat mengakibatkan cedera.

(R17866)

Saat mengatur saklar pilihan aliran udara pada . AC menetapkan secara otomatis pola hembusan yang tepat bergantung pada

mode/situasi pengoperasian.

Mode pengoperasian Situasi Pola hembusan

Operasi pendinginan

• Saat ruangan telah menjadi benar-benar dingin, atau saat 1 jam telah berlalu sejak menyalakan AC.

• Udara dihembuskan dari outlet udara atas, sehingga udara tidak bersentuhan langsung dengan orang, dan suhu ruangan diseimbangkan.

• Pada awal operasi atau saat ruangan tidak benar-benar didinginkan.

(R17867)

• Udara dihembuskan dari outlet udara atas dan bawah untuk pendinginan kecepatan tinggi selama operasi pendinginan, dan untuk mengisi ruangan dengan udara hangat selama operasi pemanasan.

Operasi pemanasan

• Waktu normal

• Pada awal atau saat suhu udara rendah.

• Udara dihembuskan dari outlet udara atas, sehingga udara tidak bersentuhan langsung dengan orang.

• Selama operasi kering, udara dihembuskan dari outlet udara atas, sehingga udara tidak

bersentuhan langsung dengan orang.

Saat mengatur saklar pilihan aliran udara pada .

Terlepas dari mode atau situasi pengoperasian, udara dihembuskan dari outlet udara atas.

Gunakan saklar ini saat Anda tidak ingin udara keluar dari outlet udara yang lebih

rendah. (Misalnya, saat tidur)

■ Udara dihembuskan dari outlet atas saja.

Pola hembusan secara otomatis ditetapkan bergantung pada mode dan kondisi (Direkomendasikan dan pengaturan

pabrik.)

Panel Depan

Fungsi dan Pengendalian

80

Fungsi Unit Indoor RA SiBE121135_A

kipas MH

M

ML

L

Kendali Kecepatan Kipas untuk Unit Indoor

Uraian Kendali fase dan kendali kecepatan kipas terdiri dari 9 langkah: LLL,, LL, SL, L, ML, M, MH, H, dan HH. Laju

Aliran Udara dapat dikendalikan secara otomatis bergantung pada perbedaan antara suhu termistor ruangan dan suhu target. Hal ini dilakukan melalui kendali fase dan kendali Hall IC.

Untuk informasi lebih lanjut tentang Hall IC, lihat pemecahan masalah untuk motor kipas pada halaman 173,

176.

Pengendalian

Kecepatan

Kipas

Otomatis

Pada operasi kecepatan kipas otomatis, tidak ada langkah "SL".

Tipe Wall Mounted Tipe Floor Standing

Tipe Floor / Ceiling Suspended Dual Tipe Duct Connected

Langkah Pendinginan Pemanasan Pendinginan Pemanasan

LLL

(R11681)

(R6834)

(R6833)

(R6834)

LL

L

ML

M

MH

H

HH (POWERFUL)

= Laju Aliran Udara dikendalikan secara otomatis dalam kisaran ini bila tombol pengaturan [FAN] diatur

ke automatic.

<Pendinginan>

Gambar berikut menjelaskan prinsip kendali kecepatan kipas untuk pendinginan.

Tipe Wall Mounted, Tipe Floor Standing

Kecepatan

+2,5°C

+1,5°C

+0.5°C

Termistor ruangan – suhu target

* +3°C

+2°C

+1°C

*Batas atas adalah M tap selama 30 menit dari operasi awal.

Tipe Floor / Ceiling Suspended, Dual Tipe Duct Connected

(R12317)

Kecepatan Kipas Suhu termistor ruangan – suhu target

+1,5˚C

+0,5˚C

+2˚C

+1˚C

(R12390)

<Pemanasan>

Dalam operasi pemanasan, kecepatan kipas diatur sesuai dengan suhu penukar panas indoor dan

perbedaan antara suhu ruangan termistor dan suhu target.

Catatan: 1. Selama operasi POWERFUL, kipas berputar pada H tap + 40 ~ 90 rpm.

2. Kipas berhenti selama operasi Pencairan.

Operasi

ALIRAN

UDARA

NYAMAN

Tipe Wall Mounted

Kecepatan kipas dikendalikan secara otomatis.

Perintah terbaru memiliki prioritas antara POWERFUL (KUAT) dan COMFORT AIRFLOW (ALIRAN UDARA NYAMAN).

M

ML L

81 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Operasi RADIANT

Uraian Tipe Floor Standing: Seri FVXG

Operasi RADIANT memiliki 2 mode operasi.

RADIANT 1: Operasi RADIANT dengan pemanasan

RADIANT 2: Operasi RADIANT saja

Kendali (Katup yang Dioperasikan Motor) Katup Ekspansi Elektronik Indoor

Memulai

dengan Daya

ON

Katup ekspansi elektronik indoor dimulai saat menyalakan daya

Kendali Batas

Pembukaan

Kendali batas pembukaan membatasi pembukaan katup ekspansi indoor untuk menjaga

kisaran tertentu selama operasi RADIANT.

Kendali

Operasi

Awal

Kendali operasi awal membuka katup ekspansi elektronik indoor untuk tingkat tertentu ketika

operasi RADIANT penyalaan. Katup ekspansi elektronik indoor tetap terbuka untuk jangka

waktu tertentu.

Kendali

Suhu Panel

Target

Saat kendali operasi awal selesai, kendali suhu panel target memulai dan menyesuaikan

pembukaan katup ekspansi elektronik indoor untuk mencapai suhu panel target. Suhu panel

dikategorikan ke dalam zona berhenti, turun, tetap, naik, dan kembali.

(Suhu panel target adalah maksimum 55°C tetapi mungkin lebih rendah tergantung pada

kondisi.)

Suhu panel Radiant

70˚C

Zona berhenti

55˚C

53˚C

51˚C

Zona turn

Zona tetap

Zona naik

45˚C

Zona naik / zona turun dari berhenti

(R14636)

Zona berhenti Operasi berhenti, kendali suhu panel radiant dilakukan.

Zona turun Pembukaan katup ekspansi elektronik indoor menurun.

Zona tetap Pembukaan katup ekspansi elektronik indoor terjaga.

Zona naik Pembukaan katup ekspansi elektronik indoor meningkat.

Zona Kembali Kendali operasi awal dilakukan.

Kendali

Berhenti

Operasi

Jika operasi berhenti selama operasi RADIANT (termasuk termostat off)

Jika kejadian berikut terjadi sementara katup ekspansi elektronik indoor terbuka, kendali

berhenti operasi menyebabkan katup ekspansi elektronik indoor menutup sepenuhnya.

ON OFF operasi

RADIANT 1 atau RADIANT 2 dibatalkan.

Termostat OFF

Kendali Pencairan

Fungsi dan Pengendalian

82

Fungsi Unit Indoor RA SiBE121135_A

Kendali Kipas Unit Indoor Pergerakan kipas unit indoor berbeda baik dalam RADIANT 1 atau RADIANT 2.

RADIANT 1 memulai.

Operasi RADIANT dan Fungsi Pilihan

(R14637)

Beberapa fungsi pilihan tidak dapat digunakan pada RADIANT 1 atau RADIANT 2 pada saat bersamaan.

Fungsi RADIANT 1 RADIANT 2

Operasi POWERFUL ada tidak ada

Operasi ECONO tidak ada tidak ada

Operasi senyap UNIT OUTDOOR

tidak ada tidak ada

Suhu ruangan

Suhu yang diatur

Suhu ruangan

Catatan: Satu-satunya perbedaan antara RADIANT 1 dan RADIANT

2 adalah pergerakan kipas unit indoor.

Pada RADIANT 1, kecepatan putaran

kipas unit indoor dikendalikan bergantung pada perbedaan antara suhu

yang diatur dan suhu ruangan. Pada

RADIANT 2, kecepatan putaran unit kipas indoor konstan.

Kecepatan putaran

kipas unit indoor

83 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

X

Zona C = Termostat ON Z

B Zona B

+

~

~

Operasi Kering Program

Uraian Operasi kering program menghilangkan kelembaban sambil mencegah penurunan suhu ruangan.

Karena mikrokomputer mengendalikan suhu dan laju aliran udara, penyesuaian suhu dan

tombol pengaturan [FAN] tidak bisa dioperasikan.

Rincian Mikrokomputer secara otomatis mengatur suhu dan laju aliran udara. Perbedaan antara suhu

termistor ruang pada saat start-up dan suhu target dibagi menjadi dua zona. Jadi, unit

beroperasi dalam kapasitas yang tepat untuk setiap zona guna mempertahankan suhu dan

kelembaban pada tingkat yang nyaman.

Suhu termistor ruang pada saat start-up

Suhu target X Titik OFF Termostat Y Titik ON Termostat Z

24°C atau

lebih

Suhu termistor ruang pada saat start-up

X – 2,5°C

X – 0,5°C atau

Y + 0,5°C (zona B) Berlangsung selama

10 menit

23,5°C X – 0,5°C

X – 2.0°C atau Y + 0,5°C (zona B)

18°C Berlangsung selama 10 menit

17.5°C 18°C

X – 2.0°C

X – 0,5°C = 17,5°C atau

Y + 0,5°C (zona B) Berlangsung selama

10 menit

Zona

Y

Zona A = Termostat OFF

0,5˚C

(R11581)

Fungsi dan Pengendalian

84

Fungsi Unit Indoor RA SiBE121135_A

Operasi Otomatis

Uraian Fungsi Otomatis / Pemanasan Pendingin Saat operasi otomatis dipilih dengan remote kontrol, mikrokomputer yang secara otomatis

menentukan mode operasi sebagai pendinginan atau pemanasas sesuai dengan suhu ruangan dan

suhu yang diatur pada saat start-up.

Unit secara otomatis mengalihkan saklar mode operasi untuk menjaga suhu ruangan pada suhu

yang diatur.

Rincian Ts: suhu yang diatur (diatur oleh remote kontrol) Tt: suhu target (ditentukan oleh mikrokomputer) Tr: suhu termistor ruangan (dideteksi oleh termistor suhu ruangan) C: nilai

perbaikan

1. Suhu yang diatur (Ts) menentukan suhu target (Tt). (Ts = 18 ~

30°C).

2. Suhu target (Tt) dihitung sebagai berikut; Tt = Ts + C

di mana C adalah nilai perbaikan. C = 0 ° C

3. Titik ON/OFF termostat dan titik peralihan saklar mode operasi adalah sebagai

berikut. Tr berarti suhu ruangan termistor.

(1) Titik peralihan saklar Pemanasan Pendinginan:

Tr Tt + 3,0°C (seri FTXG, FTXS35/42/50K, FTXS-G, FVXG)

Tr Tt + 2,5°C (model lain)

(2) Titik peralihan saklar Pendinginan Pemanasan: Tr < Tt – 2,5°C

(3) Titik ON/OFF termostat adalah sama dengan titik ON/OFF operasi pendinginan atau

pemanasan.

4. Selama operasi awal

Tr Ts: Operasi

pendinginan Tr < Ts:

Operasi pemanasan

FTXG, FTXS35/42/50K, FTXS-G, FVXG series

Suhu target – 2,0˚C = Termostat OFF

Operasi pendinginan

Suhu target + 3,0˚C Suhu

target + 2,0˚C = Termostat OFF

Suhu target – 2,5˚C

Operasi Pemanasan

Misal: Saat suhu target adalah 25°C

(R11892)

Pendinginan 23°C: Termostat OFF 22°C: Beralih ke

pemanasan Pemanasan 27°C: Termostat OFF 28°C:

Beralih ke pendinginan

Model Lainnya

Suhu target – 2,0˚C = Termostat OFF

Operasi pendinginan

Suhu target + 2,5˚C Suhu

target + 1,5˚C = Termostat OFF

Suhu target – 2,5˚C

Operasi Pemanasan

Misal: Saat suhu target adalah 25°C

(R118

93)

Pendinginan 23°C: Termostat OFF 22°C: Beralih ke

pemanasan Pemanasan 26,5°C: Termostat OFF 27,5°C:

Beralih ke pendinginan

85 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Kendali Termostat

Uraian Kendali termostat didasarkan pada perbedaan antara suhu termistor ruangan dan suhu target.

Rincian Kondisi Termostat OFF (mati)

Perbedaan suhu ada di zona A.

Kondisi Termostat ON (Nyala)

Perbedaan suhu kembali ke zona C setelah berada di zona A.

sistem berlanjut dari kendali Pencairan di setiap zona kecuali A.

Operasi berlangsung di setiap zona, kecuali zona A.

Waktu pemantauan telah berlalu saat perbedaan suhu ada di zona B.

(Pendinginan/Kering: 10 menit, Pemanasan / Radiant) 10 detik)

<Cooling/Dry> (Pendinginan/Kering)

ON

Suhu termistor ruangan – suhu target

-1,5˚C

Pendinginan: –

0,5˚C Kering : -

0,5˚C

OFF

Cooling : -2,0˚C

Kering : –2,5 ~ –

2,0˚C

(R12319)

<Pemanasan / Radiant>

FTXG, FTXS35/42/50K, FTXS-G, FVXG series

OFF

Suhu termistor ruangan – suhu target

2,0˚C

1,5˚C

0,5˚C

ON (R11894)

Model Lainnya

OFF

Suhu termistor ruangan – suhu target

1,5˚C

1,0˚C

0˚C

ON (R12320)

Lihat ke “Kendali Suhu” pada hal 73 untuk penjelasan rinci.

C

B

A

A

B

C

A

B

C

Fungsi dan Pengendalian

86

Fungsi Unit Indoor RA SiBE121135_A

0,5˚C target

Operasi berhenti 30 menit pada pengaturan sejam

Operasi TIMER +0,5˚C

Mode NIGHT SET ON (Nyala) peralihan suhu

Mode NIGHT SET (Pengaturan Mode Malam)

Uraian Ketika TIMER OFF (mati) diatur, Mode NIGHT SET secara otomatis diaktifkan. Mode NIGHT

SET menjaga pengaturan Laju Aliran Udara.

Rincian Mode NIGHT SET terus beroperasi pada suhu target selama satu jam pertama, kemudian

secara otomatis perlahan-lahan sedikit meningkatkan suhu target dalam hal pendinginan, atau

sedikit menurunkannya dalam hal pemanasan. Ini mencegah pendinginan berlebihan pada

musim panas pemanasan berlebihan pada musim dingin guna menjamin kenyamanan untuk

tidur, dan juga penghematan listrik.

<Pendinginan>

Suhu

(R18034)

<Pemanasan / Radiant>

Suhu target

2˚C

Operasi TIMER Mode NIGHT SET ON (Nyala)

1 jam kemudian

(R10871)

87 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Operasi ECONO

Uraian Tipe Wall Mounted , Tipe Floor Standing

"Operasi ECONO" mengurangi penggunaan maksimal arus dan konsumsi daya. Operasi ini

sangat nyaman untuk penghematan energi. Selain itu, juga sangat bagus ketika kapasitas

pemutus tidak memungkinkan penggunaan beberapa perangkat listrik dan AC.

Operasi ini mudah diaktifkan dengan menekan tombol [ECONO] pada remote control nirkabel.

Rincian Ketika fungsi ini diaktifkan, kapasitas maksimum juga menurun.

Operasi ECONO hanya dapat dijalankan saat unit sedang bekerja. Tekan tombol

[ON/OFF] pada remote kontrol untuk membatalkan fungsi tersebut.

Operasi ECONO tersedia saat unit dalam operasi pendinginan, pemanasan,

kering, atau otomatis dan tidak tersedia pada saat operasi RADIANT atau FAN.

Operasi ECONO dan operasi POWERFUL (KUAT) tidak dapat digunakan pada saat

bersamaan. Perintah terbaru akan diprioritaskan.

Konsumsi daya dan

arus

Normal

Maksimal selama operasi normal

Maksimal selama operasi ECONO

Operasi ECONO

Waktu

(R9288)

Fungsi dan Pengendalian

88

Fungsi Unit Indoor RA SiBE121135_A

Operasi MENINGGALKAN RUMAH [HOME LEAVE]

Uraian Tipe Floor / Ceiling Suspended Dual, Tipe Duct Connected

Operasi HOME LEAVE adalah fungsi yang memungkinkan Anda untuk merekam laju suhu dan

aliran udara favorit Anda. Anda dapat memulai mode operasi favorit Anda hanya dengan

menekan tombol [HOME LEAVE] tombol pada remote kontrol.

Rincian 1. Penyalaan Fungsi

Fungsi dimulai ketika tombol [HOME LEAVE] ditekan dalam operasi pendinginan, operasi

pemanasan (termasuk operasi KUAT), atau saat operasi dihentikan. Jika tombol ini ditekan

dalam operasi KUAT, operasi KUAT dibatalkan dan fungsi ini menjadi efektif.

tombol [HOME LEAVE] tidak efektif dalam operasi kering dan operasi kipas.

2. Rincian Fungsi

Tanda yang menunjukkan HOME LEAVE ditunjukkan pada layar remote kontrol. Unit indoor

dioperasikan sesuai dengan suhu dan laju aliran udara yang diatur untuk HOME LEAVE yang

diatur sebelumnya dalam memori remote kontrol.

LED (merah) unit indoor menunjukkan lampu HOME LEAVE menyala. (Lampu ini padam ketika

operasi dihentikan.)

3. Akhir Fungsi

Fungsi berakhir saat tombol [HOME LEAVE] ditekan lagi selama operasi HOME LEAVE atau

saat tombol [POWERFUL] ditekan.

<Pendinginan>

Pengaturan suhu “operasi HOME LEAVE ” .

Pengaturan suhu

Operasi normal

Operasi HOME LEAVE

Operasi normal

<Pemanasan>

Waktu

Start Stop (R1366)

Pengaturan suhu

Pengaturan suhu “operasi

HOME LEAVE ” .

Operasi HOME LEAVE

Operasi normal Operasi normal

Start Stop

Waktu

(R1367)

89 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Cara mengatur Suhu dan Laju Aliran Udara

Saat menggunakan operasi HOME LEAVE untuk pertama kalinya, atur suhu dan laju aliran

udara untuk operasi HOME LEAVE. Rekam suhu dan laju aliran udara pilihan Anda.

Pengaturan Awal kisaran yang

dapat dipilih Suhu Laju Aliran Udara

Suhu Laju Aliran Udara

Pendinginan 25°C

18 ~ 32°C 5 langkah, ,

Pemanasan 25°C

10 ~ 30°C 5 langkah, ,

1. Tekan tombol [HOME LEAVE].

Pastikan [ ] ditampilkan pada layar remote kontrol.

2. Sesuaikan suhu dengan atau yang Anda suka.

3. Sesuaikan laju aliran udara dengan tombol pengaturan [FAN] yang Anda suka.

Operasi HOME LEAVE akan bekerja dengan pengaturan ini pada saat Anda memulai operasi

HOME LEAVE. Untuk mengubah informasi yang direkam, ulangi langkah 1 - 3.

Lainnya Suhu dan laju aliran udara yang diatur diingat di remote kontrol. Ketika remote kontrol

diatur ulang karena penggantian baterai, maka perlu untuk mengatur suhu dan laju

aliran udara lagi untuk operasi HOME LEAVE.

Mode operasi tidak dapat diubah saat operasi HOME LEAVE sedang dijalankan.

Fungsi dan Pengendalian

90

Fungsi Unit Indoor RA SiBE121135_A

Operasi INTELLIGENT EYE

Uraian Tipe Wall Mounted: Seri FTXG, CTXS, FTXS20/25K, FTXS-G, ATXS

Fungsi ini mendeteksi keberadaan orang di dalam ruangan dengan sensor gerak orang

(INTELLIGENT EYE) dan mengurangi kapasitas ketika tidak ada seorang pun di dalam

ruangan untuk menghemat listrik.

Rincian 1. Metode deteksi dari INTELLIGENT EYE

contoh (20 mdetik)

1 detik

Jika sensor mendeteksi output 10 kali/detik atau lebih, sensor menilai ada orang dalam ruangan.

Output sensor

Ting

gi

Ren

dah

(Gerakan orang)

Sinyal deteksi ON orang OFF

(R2821)

Sensor mendeteksi gerakan orang dengan menerima sinar infra merah dan

menampilkan output gelombang pulse.

Mikro komputer dalam unit indoor melakukan pengambilan sampel setiap 20 m detik dan

jika mendeteksi total 10 siklus gelombang dalam 1 detik (sesuai dengan 20 m detik × 10

= 200 m detik), mikrokomputer menilai bahwa orang ada ruangan sehigga sinyal gerak

menjadi ON.

2. Gerakan (misalnya: dalam pendinginan)

dalam 20 mnt. 20 mnt. 20 mnt.

Sinyal deteksi orang

ON

OFF

RESET.

Suhu target

Tombol Remote kontrol [INTELLIGENT EYE]

Operasi

Kecepatan kipas (★)

ON

OFF

ON

OFF

OFF

Kecepatan yang diatur Kecepatan yang diatur

(R15346)

Ketika mikro komputer tidak menangkap sinyal dari sensor selama 20 menit, maka mikro

komputer menilai tidak ada orang dalam ruangan dan mengoperasikan unit dengan suhu

yang diubah dari suhu target. (pendinginan/pengeringan: 1 ~ 2°C lebih tinggi, pemanasan:

2 ° C lebih rendah, otomatis: Sesuai dengan mode operasi pada waktu tersebut)

★ Dalam operasi FAN, kecepatan kipas berkurang sebesar 60 rpm.

Lainnya Untuk operasi kering, Anda tidak dapat mengatur suhu dengan remote kontrol, tetapi

suhu target dialihkan secara internal.

91 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

(Kondisi output 10 kali atau lebih )

(Berlangsung 3 detik) Jika sinyal deteksi (ON) selam 3 detik atau lebih,

sensor menilai ada orang dalam ruangan.

Operasi INTELLIGENT EYE 2-area

Uraian Tipe Wall Mounted: Seri FTXS35/42/50K, FTXS-J

Fungsi berikut ini dapat dilakukan oleh sensor gerak (INTELLIGENT EYE).

1. Pengurangan kapasitas ketika tidak ada orang dalam ruangan guna menghemat

listrik (operasi penghemtan listrik).

2. Membagi ruangan ke dalam beberada area dan mendeteksi keberadaan orang di setiap

area. Secara otomatis memindahkan arah aliran udara ke area yang tidak ada orangnya

untuk menghindari aliran udara langsung ke tubuh manusia.

Rincian 1. Metode deteksi INTELLIGENT EYE

contoh (20 mdetik)

1 detik

Jika sensor mendeteksi output 10 kali/detik atau lebih, sensor menilai ada orang dalam ruangan.

Output sensor

Tinggi

Rendah

Sinyal deteksi dari sensor

ON

OFF

(Gerakan orang)

Sinyal deteksi ON orang OFF

(R12757)

Sensor ini mendeteksi gerakan orang dengan menerima sinar infra merah dan

menampilkan output gelombang pulse.

Mikro komputer dalam unit indoor melakukan pengambilan sampel setiap 20 m detik dan

jika mendeteksi total 10 siklus gelombang dalam 1 detik (sesuai dengan 20 m detik × 10 =

200 m detik) dan jika sinyal ON (NYALA) berlangsung selama 3 detik, mikrokomputer

menilai ada orang dalam ruangan karena sinyal gerakan menyala ON.

Sensor INTELLIGENT EYE 2-area terbagi dalam 2 area dan mendeteksi orang di setiap area.

Gambar INTELLIGENT EYE 2-area

· Mikrokomputer menilai keberadaan orang

dengan sinyal sensor dari masing-masing area A dan B.

(R12276)

Dinding

Tampilan atas

Area B Area A

Unit Indoor

Fungsi dan Pengendalian

92

Fungsi Unit Indoor RA SiBE121135_A

2. Gerakan (misalnya: dalam pendinginan)

dalam 20 mnt 20 mnt. 20 mnt.

Sinyal deteksi orang

(Dari area A atau B)

ON

OFF RESET.

Suhu target

Lampu INTELLIGENT ON EYE

Tombol Remote kontrol [INTELLIGENT EYE]

Operasi

OFF

ON

OFF

ON

OFF

Kecepatan yang diatur Kecepatan yang diatur

Kecepatan kipas (★)

OFF

(R15308)

Ketika mikro komputer tidak menangkap sinyal dari sensor selama 20 menit, maka

mikro komputer menilai tidak ada orang dalam ruangan dan mengoperasikan unit

dengan suhu yang diubah dari suhu target. (Pendinginan/Kering : 2°C lebih tinggi,

Pemanasan: 2 ° C lebih rendah, otomatis: Sesuai dengan mode operasi pada waktu

tersebut)

★ Dalam operasi FAN, kecepatan kipas berkurang sebesar 60 rpm.

3. Arah Aliran Udara pada Operasi INTELLIGENT EYE 2-area

Metode deteksi: Area berlawanan dari area yang dideteksi diatur sebagai arah target.

Area B Area A

(R3853)

1. Sinyal deteksi ON di area A dan B: Pindah arah aliran udara ke area B (sebelah kiri)

2. Sinyal deteksi ON di area A: Pindah arah aliran udara ke area B (sebelah kiri)

3. Sinyal deteksi ON di area B: Pindah arah aliran udara ke area A (sebelah kanan)

4. Sinyal deteksi OFF di kedua area A dan B: Tidak ada perubahan

*Jika sinyal deteksi OFF selama 20 menit baik di area A dan B, unit mulai melakukan

penghematan energi.

Lainnya Untuk operasi kering, Anda tidak dapat mengatur suhu dengan remote kontrol, tetapi

suhu target dialihkan secara internal.

Dinding

Unit Indoor

Tampilan atas

Kiri Kanan

Orang

93 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

Suhu target Harus batas bawah suhu pendinginan.

18˚C

POWERFUL ON POWERFUL OFF

Kipas

H tap

Atur

tap

Pada remote control juga memerlukan 20 menit

A rpm

20 menit

Kondisi akhir: "atau" pada 1 hingga 3 1. Setelah jeda 20 menit. 2. Operasi OFF (Berhenti) 3. Operasi POWERFUL Berhenti

Operasi Inverter POWERFUL (KUAT)

Uraian Untuk memanfaatkan kapasitas pendinginan secara maksimal, AC dapat dioperasikan

dengan meningkatkan kecepatan putar kipas indoor dan frekuensi kompresor.

Rincian Ketika tombol POWERFUL ditekan, kecepatan kipas dan suhu target dikonversi ke keadaan

berikut selama 20 menit.

Mode Operasi Kecepatan kipas Suhu target

COOL (DINGIN) H tap + A rpm 18°C

DRY (KERING) Kecepatan putar kering + A rpm

Diturunkan 2 ~ 2,5°C

HEAT (PANAS) / RADIANT 1

H tap + A rpm 30 ~ 32°C

FAN H tap + A rpm —

AUTO Sama seperti pendinginan / pemanasan dalam operasi POWERFUL

Suhu target dijaga tidak berubah.

A = 40 ~ 90 rpm (tergantung model) Misal:

Operasi POWERFUL dalam pendinginan

(R13571)

Catatan: Untuk Tipe Floor Standing: Seri FVXG Operasi POWERFUL hanya tersedia pada RADIANT 1 (operasi RADIANT dengan pemanasan),

operasi ini tidak tersedia di RADIANT 2 (operasi RADIANT saja).

Fungsi dan Pengendalian

94

Fungsi Unit Indoor RA SiBE121135_A

Lampu Indikator Banyak Warna / Lampu TIMER

Fitur Tipe Wall Mounted: Seri FTXG

Mode operasi berjalan ditampilkan dalam warna lampu unit indoor. Status pengoperasian dapat dipantau bahkan dalam operasi otomatis sesuai dengan mode operasi aktual.

Lampu indikator banyak warna /

Lampu TIMER

(R15294)

Warna lampu berubah sesuai dengan operasi yang berlangsung. AUTO ........................................................ Merah / Biru KERING ..................................................... Hijau DINGIN ...................................................... Biru PANAS ..................................................... Merah KIPAS .......................................................... Putih TIMER....................................................... Oranye

Pengaturan

Kecerahan Tingkat kecerahan lampu indikator banyak warna dapat disesuaikan L (rendah), H (tinggi), atau OFF.

1. Tekan bagian tengah Tombol [Temp] dan tombol [Mode] pada saat bersamaan.

5C ditampilkan pada LCD.

2. Pilih L (lampu) dengan tombol ▲atau ▼ [Temp].

(R11669)

(R11911)

(R11912)

3. Tekan tombol [Mode] untuk masuk ke mode pengaturan kecerahan.

95 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

4. Tekan tombol ▲atau ▼ [Temp] untuk mengatur kecerahan lampu indikator banyak warna.

L (rendah)

H (tinggi)

OFF

(R11913)

5. Tekan tombol [Mode] selama 5 detik untuk keluar dari mode pengaturan kecerahan.

(Ketika remote kontrol dibiarkan selama 60 detik, maka kembali ke mode normal juga.)

Pengaturan Kecerahan pada Layar Unit Indoor Tipe Wall Mounted: FTXS35/42/50K2V1B

Tipe Floor Standing: Seri FVXG

Setiap kali Anda menekan tombol [Brightness] pada remote kontrol, kecerahan layar unit

indoor berubah menjadi "tinggi", "rendah", atau "off (mati)".

Fungsi dan Pengendalian

96

Fungsi Unit Indoor RA SiBE121135_A

Pengaturan Jam

Seri ARC466

Seri ARC452

Jam dapat diatur dengan langkah berikut:

1. Tekan tombol [CLOCK].

muncul dan MON dan berkedip.

2. Tekan tombol ▲atau ▼ [SELECT] untuk mengatur jam hari ini dalam seminggu.

3. Tekan tombol [CLOCK].

berkedip.

4. Tekan tombol ▲atau ▼ [SELECT] untuk mengatur jam saat ini. Tahan tombol ▲atau ▼ [SELECT] untuk menambah atau mengurangi waktu yang ditampilkan dengan cepat.

5. Tekan tombol [CLOCK]. (Arahkan remote kontrol di unit indoor ketika menekan tombol

tersebut).

kedip dan pengaturan jam selesai.

Seri ARC466 Seri ARC452

Tombol SELECT

(R18250)

Tombol CLOCK

Tombol CLOCK

Tombol CLOCK

(R18281)

Seri ARC433 Series Jam dapat diatur dengan langkah berikut:

1. Tekan tombol [CLOCK].

muncul dan berkedip.

2. Tekan tombol ▲atau ▼ [TIMER] untuk mengatur jam saat ini. Tahan tombol ▲atau ▼ [TIMER] untuk menambah atau mengurangi waktu yang ditampilkan dengan cepat.

3. Tekan tombol [CLOCK] lagi.

kedip dan pengaturan jam selesai.

Tombol TIMER Tombol CLOCK

(R18286)

97 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

■ Contoh Pengaturan WEEKLY TIMER

Contoh: Pengaturan waktu yang sama dibuat untuk sepekan mulai Senin sampai Jum’at, sementara pengaturan

waktu yang berbeda dibuat untuk akhir pekan.

[Senin] Melakukan pengaturan waktu sampai 1-4 program.

ON OFF ON OFF

[Selasa] sampai [Jum’at

]

Gunakan mode salinan untuk melakukan pengaturan untuk hari Selasa sampai Jum’at karena pengaturannya sama dengan yang untuk hari Senin.

[Sabtu] [Minggu]

Tidak ada pengaturan waktu

Melakukan pengaturan waktu sampai 1-4 program.

Program 1 Program 2 ON OFF

Program 3

OFF 25˚C 27˚C

8:00 10:00 19:00

Program 4

ON

27˚C

21:00

ON OFF OFF ON

• Sampai dengan 4 pesanan per hari dan 28 pesanan per minggu dapat diatur dalam WEEKLY TIMER. Penggunaan mode salinan

yang efektif mempermudah pembuatan pesanan.

• Contohnya, penggunaan pengaturan ON-ON-ON-ON, memungkinkan untuk menjadwal mode operasi dan mengatur

perubahan suhu. Selanjutnya, dengan menggunakan pengaturan OFF-OFF-OFF-OFF, hanya waktu mematikan tiap

harinya yang dapat diatur. Hal ini akan membuat AC mati secara otomatis jika pengguna lupa mematikannya.

Operasi WEEKLY TIMER (PENGATUR WAKTU MINGGUAN)

Uraian Seri FTXG, CTXS, FTXS, FVXG, FVXS

Sampai dengan 4 pengaturan waktu dapat disimpan setiap harinya selama seminggu

(total hingga 28 pengaturan). 3 item, yaitu: "ON/OFF", "suhu", dan "waktu"dapat diatur.

Rincin ★ Perwakilan Ilustrasi ini adalah untuk seri FTXG.

Program 1 Program 2 Program 3 Program 4

ON 25˚C

OFF ON 27˚C

OFF

6:00 8:30 17:30 22:00

Program 1 Program 2 Program 3 Program 4

ON 25˚C

OFF ON 27˚C

OFF

6:00 8:30 17:30 22:00

Fungsi dan Pengendalian

98

Fungsi Unit Indoor RA SiBE121135_A

■ Cara menggunakan operasi WEEKLY TIMER

Mode pengaturan

• Pastikan mengatur harinya. Jika tidak, atur hari dan waktu.

Program 1

ON

Program 2

OFF

Program 3

ON

Program 4

OFF

[Senin] 25˚C 27˚C

6:00 8:30 17:30 22:00

Tampilan Pengaturan

Hari dan nomor ON/OFF Waktu Suhu

1. Tekan

• Hari-hari dalam seminggu dan nomor pesanan hari itu akan ditampilkan.

• Tiap harinya dapat membuat 1 sampai 4 pengaturan.

2. Tekan untuk memilih hari yang diinginkan dan nomor

pesanan.

• Tekan untuk mengubah nomor pesanan dan hari.

3. Tekan .

• Hari-hari dalam seminggu dan nomor pesanan akan diatur.

• “ ” dan “ ” berkedip.

4. Tekan untuk memilih mode yang diinginkan.

• Tekan untuk mengubah pengaturan “ON” atau “OFF” secara berurutan.

Tekan akan mengganti item-item berikut yang muncul

pada LCD dengan urutan berputar.

ON TIMER OFF TIMER kosong

• Jika pesanan telah diatur, pilih “blank” untuk menghapus

pesanan tersebut.

• Lanjutkan ke langkah 9 jika “blank (kosong)” dipilih.

• Untuk kembali ke pengaturan hari dan nomor pesanan ,tekan .

5. Tekan .

• Mode ON/OFF TIMER akan diatur.

• “ ” dan waktu akan berkedip.

99 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor RA

6. Tekan untuk memilih waktu yang diinginkan.

• Waktu dapat diatur antara 0:00 dan 23:50 dalam jarak 10 menit.

• Untuk kembali ke mode pengaturan ON/OFF TIMER, tekan .

• Masuk ke langkah 9 jika akan mengatur OFF TIMER.

7. Tekan .

• Waktu akan diatur.

• “ ” dan suhu akan berkedip.

8. Tekan untuk memilih suhu yang diinginkan.

• Suhu dapat diatur antara 18˚C dan 32˚C.

DINGIN atau AUTO: Unit beroperasi pada suhu 18˚C bahkan jika

unit diatur pada 10-17˚C.

PANAS atau AUTO Unit beroperasi pada suhu 30˚C bahkan jika

unit diatur pada 31-32˚C.

• Untuk kembali ke pengaturan,tekan .

• Suhu yang diatur hanya ditampilkan ketika mode pengaturan sedang menyala.

9. Tekan .

• Pastikan untuk mengarahkan remote kontrol ke unit indoor dan periksa

suara penerimaan dan apakah Lampu Multi-Monitor berkedip.

• Suhu dan waktu diatur saat berada dalam operasi ON TIMER dan waktu

diatur saat dalam operasi OFF TIMER.

• Layar pesanan berikutnya akan muncul.

• Untuk melanjutkan pengaturan, ulangi prosedur mulai langkah 4.

• Lampu Multi-Monitor berkedip dua kali.

• Lampu TIMER secara berkala menyala oranye.

• Lampu Multi-Monitor tidak akan berkedip oranye jika semua pengaturan pesanan dihapus.

Tampilan

10. Tekan untuk menyelesaikan pengaturan.

• “ ” muncul di LCD dan operasi WEEKLY TIMER diaktifkan.

• Pesanan yang sudah dibuat dapat disalin dengan mudah dan pengaturan

yang sama digunakan untuk hari yang lain dalam minggu tersebut. Lihat

copy mode.

CATATAN

■ Catatan mengenai operasi WEEKLY TIMER

• Jangan lupa untuk mengatur jam pada remote kontrol terlebih dahulu.

• Hari-hari dalam sepekan, mode ON/OFF TIMER, waktu dan suhu (hanya untuk mode ON TIMER) dapat diatur dengan WEEKLY TIMER.

Pengaturan lain untuk ON TIMER didasarkan pada pengaturan sebelum operasi.

• Operasi WEEKLY TIMER dan ON/OFF TIMER tidak dapat digunakan bersamaan. Operasi ON/OFF TIMER mendapatkan prioritas jika diatur saat

WEEKLY TIMER masih aktif. WEEKLY TIMER akan berada dalam kondisi siaga, dan “ ” akan hilang dari LCD. Saat ON/OFF

TIMER muncul, WEEKLY TIMER akan otomatis menjadi aktif.

• Mematikan pemutus sirkuit, mati listrik dan kejadian sejenis lainnya akan menyebabkan pengoperasian jam internal unit indoor tidak akurat. Atur

ulang jamnya.

Fungsi Unit Indoor RA SiBE121135_A

Fungsi dan Pengendalian

100

Copy mode / Mode Salinan

• Pesanan yang sudah dibuat dapat disalin untuk hari yang lain. Keseluruhan pesanan dari

hari yang dipilih akan disalin.

Program 1 ON

Program 2 OFF

Program 3 ON

Program 4 OFF

[Senin] 25˚C 27˚C

SALIN 6:00 8:30 17:30 22:00

[Selasa]

Program 1 ON

Program 2 OFF

Program 3 ON

Program 4 OFF

hingga 25˚C 27˚C

[Jum’at] 6:00 8:30 17:30 22:00

Tampilan Pengaturan

CATATAN

■ Catatan mengenai mode salinan

Konfirmasi Copy Paste Normal

1. Tekan .

2. Tekan untuk konfirmasi hari yang akan disalin.

3. Tekan .

• Keseluruhan pesanan dari hari yang dipilih akan disalin.

4. Tekan untuk memilih hari yang dituju.

5. Tekan .

• Pastikan untuk mengarahkan remote kontrol ke unit indoor dan periksa suara

penerimaan dan apakah Lampu Multi-Monitor berkedip.

• Pesanan akan disalin ke hari yang dipilih. Seluruh pesanan hari tersebut akan disalin.

• • Unttuk melanjutkan menyalin pengaturan ke hari yag lain, ulangi langkah 4 dan langkah 5.

• Lampu Multi-Monitor berkedip dua kali. Lampu TIMER secara berkala menyala oranye.

6. Tekan untuk menyelesaikan pengaturan.

• “ ” muncul di LCD dan operasi WEEKLY TIMER diaktifkan.

• Seluruh pesanan dari hari sumber disalin dalam mode salinan.

Jika ingin mengubah pesanan masing-masing hari setelah menyalin isi pesanan mingguan, tekan dan ubah pengaturan

pada langkah “setting mode”.

SiBE121135_A Fungsi Unit Indoor RA

101 Fungsi dan Pengendalian

■ Mengkonfirmasi Pesanan

• Pesanan dapat dikonfirmasi.

Tampilan Pengaturan

Normal Konfirmasi

1. Tekan .

• Hari-hari dalam seminggu dan nomor pesanan hari itu akan ditampilkan.

2. Tekan untuk memilih hari dan nomor pesanan yang akan

dikonfirmasi.

• Tekan untuk menampilkan rincian pesanan.

• Untuk mengubah pengaturan pesanan yang sudah dikonfirmasi, pilih nomor pesanan dan tekan

.

Mode berubah menjadi mode pengaturan. Lanjutkan ke mode pengaturan langkah 2.

3. Tekan untuk keluar dari mode konfirmasi.

menonaktifkan operasi WEEKLY TIMER

Tekan saat “ ” muncul pada LCD.

• “ ” akan hilang dari LCD.

• Lampu TIMER mati.

Untuk mengaktifkan kembali operasi WEEKLY TIMER,

tekan lagi.

• Jika pesanan dinonaktifkan saat diaktifkan sekali lagi, maka mode

pesanan terakhir akan digunakan.

PERHATIAN

• Jika tidak semua pengaturan pesanan digambarkan, nonaktifkan operasi WEEKLY TIMER. Tekan kembali

untuk mengaktifkan ulang operasi WEEKLY TIMER.

Fungsi Unit Indoor RA SiBE121135_A

Fungsi dan Pengendalian

102

■ Cara menghapus pesanan

Pesanan individual

1. Tekan .

• Hari-hari dalam seminggu dan nomor pesanan akan muncul.

2. Tekan untuk memilih hari dan nomor pesanan yang akan

dihapus.

3.

Tekan .

• “ ” dan “ ” atau “ ” berkedip.

4. Tekan dan pilih “ blank (kosong) ”.

• Tekan untuk mengubah mode ON/OFF TIMER.

Tekan akan mengganti item-item berikut yang muncul pada LCD dengan urutan berputar.

• Pilih “blank” untuk membatalkan semua pesanan yang Anda miliki.

ON TIMER OFF TIMER kosong

5. Tekan .

• Pesanan yang dipilih akan dihapus.

6. Tekan .

• Jika masih ada pesanan yang lain, operasi WEEKLY TIMER akan diaktifkan.

Pesanan untuk masing-masing hari dalam seminggu

• Fungsi ini dapat digunakan untuk menghapus pesanan masing-masing hari dalam seminggu.

• Ini dapat digunakan saat mengonfirmasi atau mengatur pesanan.

1. Tekan untuk memilih hari yang akan dihapus.

2. Tahan sekitar 5 detik.

• Pesanan hari yang dipilih akan dihapus.

Seluruh pesanan

Tahan sekitar 5 detik saat dalam tampilan normal.

• Pastikan untuk mengarahkan remote kontrol ke arah unit indoor dan periksa suara penerimaan.

• Operasi ini tidak efektif saat WEEKLY TIMER sedang diatur.

• Seluruh pesanan akan dihapus.

SiBE121135_A Fungsi Unit Indoor RA

103 Fungsi dan Pengendalian

Fungsi-fungsi Lainnya Fungsi Hot-Start

Untuk mencegah hembusan udara dingin yang biasanya muncul saat operasi pemanasan

dimulai, suhu penukar panas indoor terdeteksi, dan aliran udara yang dihentikan atau dibuat

sangat lemah sehingga melakukan pemanasan ruangan yang nyaman.

Hembusan udara dingin juga dicegah dengan menggunakan kendali yang sama ketika

operasi pembersihan pembekuan dimulai atau saat termostat dinyalakan (ON).

Tanda Penerimaan Sinyal Ketika unit indoor menerima sinyal dari remote kontrol, unit akan mengeluarkan suara

penerimaan sinyal

Tombol [ON/OFF] Unit Indoor Tombol [ON/OFF] terdapat pada tampilan unit. Tekan tombol [ON / OFF] sekali untuk memulai operasi. Tekan sekali lagi untuk

menghentikannya. Tombol [ON / OFF] berguna ketika remote kontrol hilang atau baterai sudah mati.

Untuk mode operasi lihat tabel berikut.

Mode Operasi Pengaturan Suhu Laju Aliran Udara

Pendingin Saja

COOL (DINGIN) 22°C Otomatis

Pompa Kalor AUTO 25°C Otomatis

Dalam hal operasi multi-sistem, ada kalanya unit tidak mengaktifkan dengan tombol [ON

/ OFF].

Misal: Tpe Wall mounted Seri FTXS-J

Tombol [ON/OFF]

(R8302)

Filter Pemurni Udara Fotokatalitik Apatit Titanium Tipe Wall Mounted, Tipe Floor Standing Filter ini menggabungkan Filter Pemurni Udara dan Filter Penghilang Bau Fotokatalitik Apatit

Titanium sebagai filter tunggal yang sangat efektif. Filter menangkap partikel mikroskopis, bau

busuk dan bahkan mematikan bakteri dan virus. Filter ini bertahan selama 3 tahun tanpa

penggantian jika dicuci sekitar sekali setiap 6 bulan.

Filter Penghilang Bau Fotokatalitik Tipe Floor / Ceiling Suspended Dual Filter penghilang bau fotokatalitik sangat kuat menghilangkan bau busuk rokok, binatang, dll

Kekuatan penghilang bau dihasilkan kembali hanya dengan terkena sinar matahari. Kami

menganjurkan untuk mengeringkan filter di bawah sinar matahari selama sekitar 6 jam (setelah

pembersihan filter) setiap 6 bulan.

Filter Pemurni Udara Tipe Floor / Ceiling Suspended Dual Filter pemurni udara mengumpulkan asap rokok, serbuk, dll dengan zat elektrostatik. Filter ini termasuk filter karbon aktif penghilang bau yang menghilangkan partikel kecil bau.

Ganti filter pemurni udara setiap 3 bulan.

Fungsi Auto-Restart (Memulai Kembali Otomatis) Jika listrik mati selama operasi (termasuk listrik mati meski sebentar), operasi akan hidup

kembali secara otomatis jika listrik telah nyala dalam kondisi yang sama seperti sebelum listrik

mati.

Catatan: Diperlukan waktu selama 3 menit untuk menghidupkan kembali AC karena fungsi Siaga-3 menit diaktifkan.

Fungsi dan Pengendalian

104

Fungsi Unit Indoor SA SiBE121135_A

2. Fungsi Unit Indoor SA

Kendali Pompa Pengurasan Saat Saklar Apung Tertahan sedangkann Termostat Pendinginan ON:

Termostat

(berfungsi)

Saklar apung

ON

OFF

OFF

ON

Remote kontrol menampilkan A3

dan unit indoor berhenti.

Pompa penguras

ON

OFF

5 mnt.

1) Operasi normal

5 mnt. 5 det.

2) Sisa kerusakan

(R16092)

1. (Operasi normal):

Tujuan dari operasi sisa adalah untuk menguras sepenuhnya setiap kelembaban yang

menempel pada sirip penukar panas indoor ketika termostat mati selama operasi pendinginan.

2. (Sisa kerusakan):

Remote kontrol menampilkan A3 dan AC segera berhenti tidak normal dalam 5 menit

jika saklar apung dialihkan OFF sementara termostat pendinginan sedang ON.

Saat Saklar Apung Tertahan sedangkan Termostat Pendinginan OFF:

Termostat ON

(berfungsi)

OFF

OFF

Saklar apung

ON

Unit indoor masuk ke perawatan kerusakan jika saklar apung tidak diatur ulang dalam waktu 5 menit.

Remote kontrol menampilkan A3 dan unit indoor berhenti.

Pompa penguras ON

OFF

5 mnt.

5 det.

3

5 mnt.

5 det.

(R16093)

3. (Sisa kerusakan):

Remote kontrol menampilkan A3 dan AC segera berhenti tidak normal jika saklar apung

dialihkan OFF dan tidak dialihkan ON lagi dalam 5 menit sementara termostat pendinginan

sedang OFF.

105 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor SA

Remote kontrol menampilkan A3 dan unit indoor berhenti.

Reset

1 kali 2 kali 3 kali 4 kali 5 kali

Saat Saklar Apung Tertahan Selama Operasi Pemanasan:

Termostat (berfungsi

)

Humidifier

Saklar apung

Pompa penguras

ON

OFF

ON

OFF

ON

OFF

ON

OFF

5 mnt. 5 det. 5 mnt. (R16094)

Selama operasi pemanasan, jika saklar apung tidak diatur ulang bahkan setelah operasi 5

menit, berhenti 5 detik, siklus operasi 5 menit berakhir, operasi berlanjut sampai saklar diatur

ulang.

Saat Saklar Apung Tertahan dan AF Ditampilkan pada Remote Kontrol:

Tampilan Remote kontrol

Saklar apung

ON

OFF

OFF

ON

Tampilan AF

(berfungsi)

Unit indoor masuk ke perawatan kerusakan jika saklar apung tidak diatur ulang dalam waktu 5 menit.

Remote kontrol menampilkan A3 dan unit indoor berhenti.

Pompa penguras

1: 5mnt

ON

OFF

1 1 1 1 1 1 1

4 5

5 det.

(R15615)

4. (Sisa kerusakan):

Jika saklar apung tertahan 5 kali berturut-turut, dipastikan terjadi kerusakan pembuangan. AF

kemudian ditampilkan sebagai operasi kelanjutan.

5. (Sisa kerusakan):

Remote kontrol menampilkan A3 dan AC segera berhenti tidak normal jika saklar apung OFF

selama lebih dari 5 menit dalam kasus 4.

Fungsi dan Pengendalian

106

Fungsi Unit Indoor SA SiBE121135_A

Sensor Termostat pada Remote Kontrol Suhu dikendalikan oleh sensor termostat di remote kontrol dan termostat hisap udara di unit

indoor. (Hal ini bagaimanapun terbatas pada saat Pengaturan bidang untuk sensor termostat di

remote kontrol diatur pada "Use (Gunakan)." )

Pendinginan Jika ada perbedaan yang signifikan pada suhu yang diatur dan suhu hisap, kendali

penyesuaian halus dilakukan dengan menggunakan sensor termostat tubuh, atau

menggunakan sensor pada remote kontrol dekat posisi pengguna saat suhu hisap dekat

suhu yang diatur.

˚C 32

Suhu yang diatur (Ts)

TH1 = Ts - 1

30

28

26

TH1 = Ts - 3

TH1 = Ts + 1

TH1 = Ts + 3

A B C D E F 24

22

20

18

16 ˚C

12 14 16 18 20 22 24 26 28 30 32 34

Suhu hisap (TH1)

kisaran di mana sensor termostat pada remote kontrol dapat digunakan

kisaran di mana sensor termostat tubuh dapat digunakan

Perbedaan

(R17288)

Dengan asumsi bahwa suhu yang diatur pada gambar di atas

adalah 24°C, dan suhu hisap telah diubah dari 18°C hingga

30°C (A F):

(Contoh ini juga mengasumsikan ada beberapa AC lainnya, dan suhu hisap berubah bahkan

saat sensor termostat dimatikan.)

Sensor termostat tubuh digunakan untuk suhu dari 18°C hingga 23°C (A C).

Sensor termostat remote kontrol digunakan untuk suhu dari 23°C hingga 27°C (C E).

sensor termostat tubuh digunakan untuk suhu dari 27°C hingga 30°C (E F).

Dengan asumsi bahwa suhu hisap telah diubah dari 30°C hingga 18°C (F

A):

Sensor termostat tubuh digunakan untuk suhu dari 30°C menjadi 25°C (F D).

Sensor termostat remote kontrol digunakan untuk suhu dari 25°C hingga 21°C (D B).

Sensor tubuh termostat digunakan untuk suhu dari 21°C hingga 18°C (B A).

107 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor SA

Pemanasan Ketika pemanasan, udara panas naik ke atas ruangan, yang mengakibatkan terjadi suhu

lebih rendah di dekat lantai tempat penghuninya. Ketika mengendalikan dengan sensor

termostat tubuh saja, unit indoor mungkin dapat dimatikan oleh termostat sebelum bagian

bawah ruangan mencapai suhu yang diatur. Suhu dapat dikendalikan sehingga bagian

bawah ruangan tempat penghuni tidak menjadi dingin dengan memperluas jangkauan di

mana sensor termostat pada remote kontrol dapat digunakan sehingga suhu hisap lebih

tinggi daripada suhu yang diatur.

˚C 32

Suhu yang diatur (Ts)

30

28

26

24

22

20

18

16

TH1 = Ts - 1

A B C D

TH1 = Ts + 1 31˚C

TH1 = Ts + 12 33˚C

TH1 = Ts + 10 31˚C

˚C

12 14 16 18 20 22 24 26 28 30 32 34

Suhu hisap (TH1)

kisaran di mana sensor termostat pada remote kontrol dapat digunakan

kisaran di mana sensor termostat tubuh dapat digunakan

(R17289)

Dengan asumsi bahwa suhu yang diatur pada gambar di atas

adalah 24°C, dan suhu hisap telah diubah dari 18°C hingga

28°C (A D):

(Contoh ini juga mengasumsikan ada beberapa AC lainnya, dan suhu hisap berubah bahkan

saat sensor termostat dimatikan.)

Sensor tubuh termostat digunakan untuk suhu dari 18°C menjadi 25°C (A C).

Sensor termostat remote kontrol digunakan untuk suhu dari 25°C hingga 28°C (C D).

Dengan asumsi bahwa suhu hisap telah diubah dari 30°C hingga 18°C (D

A):

Sensor termostat remote kontrol digunakan untuk suhu dari 28°C hingga 23°C (D B).

Sensor tubuh termostat digunakan untuk suhu dari 23°C hingga 18°C (B A).

Perbedaan

Fungsi dan Pengendalian

108

Fungsi Unit Indoor SA SiBE121135_A

Kendali pencegahan kebekuan

Kendali Pencegahan Kebekuan Ketika suhu dideteksi oleh termistor pipa cairan (R2T) dari penukar panas indoor menurun

terlalu rendah, unit memasuki kendali pencegahan kebekuan sesuai dengan kondisi sebagai

berikut, dan juga diatur sesuai dengan kondisi yang diberikan di bawah ini.

Kondisi untuk awal: Suhu sebesar -1°C atau kurang untuk total 40 menit., Atau suhu sebesar -

5°C atau kurang untuk total 10 menit.

Kondisi untuk pembatalan: Suhu sebesar + 7°C atau lebih selama 10 menit.

berkelanjutan Misal: Kasus di mana suhu sebesar -5°C atau kurang untuk total 10

menit.

10 mnt.

+ 7˚C

+ 0˚C

– 5˚C

10 mnt.

OFF paksa oleh termostat

Operasi normal

(R12940)

109 Fungsi dan Pengendalian

SiBE121135_A Fungsi Unit Indoor SA

Kendali Hot Start (Pada Operasi Pemanasan Saja)

Uraian Saat penyalaan dengan termostat ON atau setelah selesainya pembersihan pembekuan

dalam operasi pemanasan, kipas unit indoor dikendalikan untuk mencegah udara dingin

berhembus keluar dan memastikan kapasitas penyalaan.

Rincian

Akhir pembersihan pembekuan

atau akhir pengembalian minyak

atau Termostat ON

Kondisi akhir hot start

· jeda 3 menit OR · [TH2] > 34˚C

· Tc > 52˚C

Kendali hot start

Hot start berlangsung

Kip

as

Pengaturan remote kontrol

H/L

LL

OFF

Operasi normal

Kipas tidak OFF sebelum memulai hot start: LL Kipas OFF sebelum memulai hot start: OFF

Sir

ip

Pengaturan remote kontrol

Posisi tingkat

Operasi normal

(R15421)

TH2: Suhu (°C) dideteksi dengan termistor gas TC:

Tekanan tinggi setara dengan suhu jenuh

SiBE121135_A Fungsi Termistor

Fungsi dan Pengendalian

110

EVB

EVC

EVD

EVA

D C B A

(2)

Kompresor

EVB

EVC

EVD

(6) 6

EVA

C B

Katup ekspansi

elektronik indoor

(Katup yang

dioperasikan motor)

(6) 4

D

Panel radiant (4)

Katup empat arah

(2)

Kompresor (4)

3. Fungsi Termistor ★ Perwakilan ilustrasi adalah model 4-ruangan dan memiliki 4 jalur sistem unit indoor (A ~ D).

Model 3-ruangan memiliki 3 jalur (A ~ C) dan model 5-ruangan memiliki 5 jalur (A ~ E).

Model Pendinginan Saja

Katup ekspansi elektronik outdoor

(1)

(4)

(3) (R17248)

Model Pompa Kalor

Katup ekspansi elektronik outdoor

(5)

A: Dalam kasus model FVXG

(1)

(3)

(R17159)

(1) Termistor

Penukar Panas

Outdoor

1. Termistor penukar panas outdoor digunakan untuk mengendalikan suhu target pipa

buang. Sistem ini menetapkan suhu target pipa buang sesuai dengan suhu penukar

panas outdoor dan indoor, dan mengendalikan pembukaan katup ekspansi elektronik

sehingga suhu target pipa buang dapat dicapai.

2. Dalam operasi pendinginan, termistor penukar panas outdoor digunakan untuk mendeteksi

pemutusan termistor pipa buang. Ketika suhu pipa buang turun di bawah suhu penukar

panas outdoor sebesar lebih dari satu nilai tertentu, maka termistor pipa buang dianggap

terputus.

3. Pada operasi pendinginan, termistor penukar panas outdoor digunakan untuk

perlindungan tekanan tinggi.

Fungsi Termistor SiBE121135_A

111 Fungsi dan Pengendalian

(2) Termistor

Pipa Buang

1. Termistor pipa buang digunakan untuk mengendalikan suhu pipa buang. Jika suhu pipa

buang (digunakan di tempat suhu bagian dalam kompresor) meningkat secara tidak

normal, frekuensi operasi menjadi lebih rendah atau operasi terhenti.

2. Termistor pipa buang digunakan untuk mendeteksi pemutusan termistor pipa buang.

(3) Termistor

Pipa Gas

Pada operasi pendinginan, termistor pipa gas digunakan untuk kendali isotermal pipa gas.

Sistem mengendalikan pembukaan katup ekspansi elektronik outdoor sehingga suhu pipa gas

di setiap ruangan menjadi sama.

(4) Termistor

Penukar

Panas indoor

1. Termistor penukar panas indoor digunakan untuk mengendalikan suhu target pipa

buang. Sistem ini menetapkan suhu target pipa buang sesuai dengan suhu penukar

panas outdoor dan indoor, dan mengendalikan pembukaan katup ekspansi elektronik

sehingga suhu target pipa buang dapat dicapai.

2. Pada operasi pendinginan, termistor penukar panas indoor digunakan untuk kendali

perlindungan kebekuan. Jika suhu penukar panas turun secara tidak normal, frekuensi

operasi menjadi lebih rendah atau operasi berhenti.

3. Pada operasi pendinginan, termistor penukar panas indoor digunakan untuk fungsi anti

pembentukan es (anti-icing). Jika salah satu kondisi berikut terpenuhi di dalam ruangan

tempat operasi berhenti, maka diasumsikan sebagai pembentukan es (icing).

Kondisi adalah Tc

– 1° C

Ta – Tc 10° C

di mana Ta adalah suhu ruangan dan Tc adalah suhu penukar panas indoor.

4. Pada operasi pendinginan, termistor penukar panas indoor digunakan untuk kendali

pemutusan puncak pemanasan. Jika suhu penukar panas naik secara tidak normal,

frekuensi operasi menjadi lebih rendah atau operasi berhenti.

5. Dalam operasi pemanasan, termistor penukar panas indoor digunakan untuk mendeteksi

pemutusan termistor pipa buang. Ketika suhu pipa buang turun di bawah suhu penukar

panas indoor terbesar lebih dari satu nilai tertentu, maka termistor pipa buang dianggap

terputus.

6. Ketika hanya satu unit indoor beroperasi, termistor penukar panas indoor digunakan untuk

kendali sub-pendinginan. Sub-pendinginan aktual dihitung dengan suhu pipa cair dan suhu

penukar panas indoor. Sistem kendali bukaan katup ekspansi elektronik outdoor untuk

mencapai target sub-pendinginan.

7. Termistor penukar panas indoor digunakan untuk fungsi pemeriksaan kesalahan

pengkabelan. Aliran refrigeran secara berurutan dari port A untuk mendeteksi suhu

penukar panas indoor satu per satu, dan kemudian pengkabelan dan perpipaan dapat

diperiksa.

(5) Termistor

Pipa Cair

1. Ketika hanya satu unit indoor dalam pemanasan, termistor pipa cair digunakan untuk

kendali sub-pendinginan. Sub-pendinginan aktual dihitung dengan suhu pipa cair dan

suhu penukar panas indoor maksimal. Sistem kendali bukaan katup ekspansi elektronik

outdoor untuk mencapai target sub-pendinginan.

2. Pada operasi pemanasan, termistor pipa cair digunakan untuk kendali isotermal pipa cair.

Sistem mengendalikan pembukaan katup ekspansi elektronik outdoor sehingga suhu pipa

cair di setiap ruangan menjadi sama.

(6) Termistor

Panel Radiant

1. Termistor panel radiant digunakan untuk menghitung suhu permukaan panel radiant.

Karena pembatasan struktural dan manufaktur, suhu permukaan panel radiant tidak dapat

dikendalikan secara langsung dengan termistor. Termistor dipasang pada perpipaan panel

radiant untuk menghitung suhu permukaan panel radiant.

Katup ekspansi elektronik indoor dikendalikan sesuai dengan suhu permukaan panel

radiant.

2. Termistor panel radiant digunakan untuk mendeteksi kerusakan pada katup ekspansi

elektronik indoor

Fungsi dan Pengendalian

112

Spesifikasi Pengendalian

SiBE121135_A

Mode operasi paksa

Mode uji transistor daya

Mode operasi normal

Mode kendali AC

Operasi pendinginan paksa

Operasi pemeriksaan kesalahan pengkabelan

Kipas

Pendinginan (termasuk pengeringan)

4. Spesifikasi Pengendalian

Hirarki Mode

Uraian Kendali AC memiliki mode operasi normal, mode operasi paksa, dan mode uji transistor daya

untuk pemasangan dan servis

Rincian Model Pendinginan Saja

(untuk Operasi Pump Down)

Model Pompa Kalor

Penghentian (unit indoor: OFF)

Operasi pra pemanasan

Pengosongan kapasitor

Penghentian

(R17811)

(untuk Operasi pump down)

paksa

pengkabelan

Kipas

Pendinginan (termasuk

pengeringan) Pemanasan

Pemanasan

Pembersihan

Pembekuan

Penghentian (unit indoor: OFF)

Operasi pra pemanasan

Pengosongan kapasitor

Penghentian

(R17361)

Catatan: Kecuali ditentukan lain, perintah operasi pengeringan dianggap sebagai operasi

pendinginan dan perintah operasi radiant dianggap sebagai operasi pemanasan

Operasi kipas indoor tidak dapat dibuat dalam beberapa unit indoor. (Perintah kipas

paksa dibuat selama operasi pendinginan paksa.)

Menentukan Mode Operasi

Sistem ini menilai perintah mode operasi yang diatur oleh masing-masing ruangan sesuai

dengan prosedur, dan menentukan mode operasi sistem.

Prosedur berikut diambil ketika mode bertentangan satu sama lain.

1. Sistem ini mengikuti mode yang pertama diatur. (Pertama-tekan, pertama-diatur)

2. Untuk ruangan tempat mode yang berbeda diatur, mode siaga diaktifkan. (Lampu operasi

berkedip.)

Mode kendali AC

Mode operasi paksa Operasi pendinginan paksa

Operasi pemanasan

Operasi pemeriksaan

kesalahan

Mode uji transistor daya Mode operasi normal

113 Fungsi dan Pengendalian

SiBE121135_A Spesifikasi Pengendalian

Fungsi penurunan

kendali arus input, dll.

Frekuensi target

Frekuesi batas atas

FMAX

Fungsi batas atas

Fungsi perlindungan

kompresor

Frekuensi perintah

Kendali Frekuensi

Uraian Frekuensi yang sesuai dengan kapasitas masing-masing ruangan ditentukan berdasarkan

perbedaan antara suhu target dan suhu masing-masing ruangan.

Fungsi ini dijelaskan sebagai berikut.

1. Bagaimana cara menentukan frekuensi

2. Perintah frekuensi dari unit indoor (Perbedaan antara suhu termistor ruangan

dan suhu target)

3. Perintah frekuensi dari unit indoor (Kapasitas berperingkat dari ruang operasi)

4. Pengaturan awal frekuensi

5. Kendali PI

Ketika perubahan frekuensi oleh kendali PI kurang dari nol

(F<0),frekuensi target digunakan sebagai frekuensi perintah.

Frekuensi batas Kendali Skip

Fungsi batas bawah

Kompensasi operasi katup empat arah (), dll.

(): hanya untuk model pompa kalor (R17847)

Rincian Cara Menentukan Frekuensi Frekuensi kompresor ditentukan dengan melakukan langkah-langkah berikut.

Untuk Model Pendinginan Saja

1. Menentukan frekuensi perintah

Frekuensi perintah ditentukan berdasarkan urutan prioritas berikut.

1. Pendinginan paksa

2. Perintah frekuensi indoor

2. Menentukan fekuensi batas atas

Nilai minimal ditetapkan sebagai frekuensi batas atas di antara batas atas frekuensi dari

fungsi-fungsi berikut:

Perlindungan kompresor, arus input, suhu pipa buang, batas tekanan tinggi hz bawah,

perlindungan kebekuan.

3. Menentukan fekuensi batas bawah

Nilai maksimal ditetapkan sebagai frekuensi batas bawah di antara batas bawah frekuensi

fungsi-fungsi berikut :

Pencegahan aliran udara, pemeliharaan perbedaan tekanan.

4. Menentukan frekuensi terlarang

Terdapat frekuensi terlarang tertentu seperti frekuensi catu daya.

Frekuensi awal

kendali PI

Kendali Pencairan ()

Frekuesi batas bawah

FMIN

Fungsi dan Pengendalian

114

Spesifikasi Pengendalian

SiBE121135_A

Untuk Model Pompa Kalor

1. Menentukan frekuensi perintah

Frekuensi perintah ditentukan berdasarkan urutan prioritas berikut.

1. Membatasi waktu kendali pencairan

2. Pendinginan/pemanasan paksa

3. Perintah frekuensi indoor

2. Menentukan fekuensi batas atas

Nilai minimal ditetapkan sebagai frekuensi batas atas di antara batas atas frekuensi dari

fungsi-fungsi berikut:

Perlindungan kompresor, arus input, suhu pipa buang, batas tekanan tinggi hz

bawah,pemutusan puncak pemanasan, perlindungan kebekuan, penghilang kebekuan.

3. Menentukan fekuensi batas bawah

Nilai maksimal ditetapkan sebagai frekuensi batas bawah di antara batas bawah frekuensi

fungsi-fungsi berikut :

Kompensasi operasi katup empat arah, pencegahan aliran udara, pemeliharaan perbedaan tekanan.

4. Menentukan frekuensi terlarang

Terdapat frekuensi terlarang tertentu seperti frekuensi catu daya.

Perintah Frekuensi Indoor (SinyalD)

Perbedaan antara suhu termistor ruangan dan suhu target diambil sebagai "sinyalD” dan

digunakan untuk perintah frekuensi.

Perbedaan suhu (°C)

SinyalD

Perbedaan suhu (°C)

SinyalD

Perbedaan suhu (°C)

SinyalD

Perbedaan suhu (°C)

SinyalD

-2,0 Th OFF

0 4 2,0 8 4,0 C

-1,5 1 0,5 5 2,5 9 4,5 D

-1,0 2 1,0 6 3,0 A 5,0 E

-0,5 3 1,5 7 3,5 B 5,5 F

Nilai-nilai tergantung pada tipe unit indoor.

Th OFF = Termostat OFF

Kapasitas Unit Indoor (nilai S)

Kapasitas unit indoor adalah nilai "S" dan digunakan untuk perintah frekuensi.

Misal:

Pengaturan Awal Frekuensi

<Uraian>

Saat memulai kompresor, atau saat kondisi beragam karena perubahan ruang operasi,

frekuensi harus diawali sesuai dengan total nilai D maksimal dari setiap ruangan dan total nilai

Q (Q) dari ruang operasi (ruang tempat termos diatur ke ON).

Nilai Q: Output unit indoor ditentukan dari volume unit indoor, laju aliran udara dan faktor lainnya.

Kapasitas

Nilai S Kapasitas

Nilai S

2,5 kW 25 5,0 kW 50

3,5 kW 35 6,0 kW 60

115 Fungsi dan Pengendalian

SiBE121135_A Spesifikasi Pengendalian

Kendali PI (Menentukan Kenaikan/ Penurunan Frekuensi oleh Sinyal D)

1. Kendali P

Total nilai D dihitung pada masing-masing waktu sampling (20 detik), dan frekuensinya

diatur menurut perbedaannya dari frekuensi yang dihitung sebelumnya.

2. Kendali I

Jika frekuensi operasi tidak berubah untuk waktu tetap tertentu, frekuensi diatur menurut nilai

D.

Bila nilai D rendah, frekuensinya menurun. Bila nilai D

tinggi, frekuensinya meningkat.

3. Batas kisaran peningkatan frekuensi

Ketika perbedaan antara arus input dan arus input nilainya menurun kurang dari 1,5 A,

kisaran peningkatan frekuensi harus dibatasi.

4. Manajemen frekuensi saat kendali lain berfungsi

Ketika masing-masing frekuensi menurun;

Manajemen frekuensi dilakukan hanya saat frekuensi turun.

Untuk membatasi batas bawah

Manajemen frekuensi dilakukan hanya saat frekuensi meningkat.

5. Batas atas dan bawah frekuensi oleh kendali PI

Batas atas dan bawah frekuensi diatur sesuai dengan total nilai S. Ketika perintah operasi

senyap unit indoor berasal dari lebih dari satu ruangan atau ketika perintah operasi senyap

unit outdoor berasal dari semua ruang, frekuensi batas atas lebih rendah daripada

pengaturan biasanya.

Fungsi dan Pengendalian

116

Spesifikasi Pengendalian

SiBE121135_A

Kendali Pengubahan Mode / Start-Up Kendali Pra Pemanasan

Uraian Pengoperasian inverter pada fase terbuka dimulai dengan kondisi suhu outdoor.

Kendali ini tidak bekerja pada model 3MXS68G3V1B dan 4MXS68F3V1B.

Rincian Kondisi ON

Saat suhu outdoor lebih rendah dari 10,5ºC, pengoperasian inverter pada fase terbuka akan dimulai.

Kondisi OFF

Saat suhu outdoor lebih tinggi dari 12ºC, pengoperasian inverter pada fase terbuka

akan berhenti.

Pensaklaran Katup Empat Arah

Uraian Pada operasi pemanasan, arus dijalankan, dan pada pendinginan dan pencairan, arus tidak

dijalankan. Untuk menghilangkan suara pensaklaran, karena kumparan empat arah beralih

dari ON ke OFF ketika pemanasan dihentikan, saklar penunda OFF dari katup empat arah

dilakukan.

Rincian Saklar tunda OFF dari katup empat arah:

Kumparan katup empat arah diberi aliran listrik selama 150 detik setelah operasi dihentikan.

Kompensasi Operasi Katup Empat Arah

Rincian Pada awal operasi saat katup empat arah diaktifkan, perbedaan tekanan untuk mengaktifkan

katup empat arah diperoleh dengan memiliki frekuensi output yang lebih dari frekuensi tetap

tertentu, untuk waktu tetap tertentu.

Rincian Kondisi Penyalaan (Start)

1. Ketika kompresor memulai dan katup empat arah beralih dari OFF ke ON

2. Ketika katup empat arah beralih dari ON ke OFF selama operasi

3. Ketika kompresor memulai setelah penyetelan ulang

4. Ketika kompresor memulai setelah kesalahan pensaklaran katup empat arah

Batas bawah frekuensi bertahan A Hz selama 70 detik dengan kondisi 1 sampai 4 di atas.

A (Hz)

Kelas 40/50/52/58 48

Kelas 68/75 40

Kelas 80/90 28

Siaga 3 Menit Jangan menyalakan kompresor selama 3 menit setelah mematikannya.

(Kecuali saat pencairan)

117 Fungsi dan Pengendalian

SiBE121135_A Spesifikasi Pengendalian

D E F

Fungsi Perlindungan Kompresor Ketika menyalakan kompresor dari OFF ke ON, batas atas frekuensi diatur sebagai berikut.

(Fungsi tidak digunakan saat pencairan)

(Hz) Frekuensi

C

B

A

(det.) Wakt

u (R13528)

Kelas 40/50/52/58 Kelas 68/75/80/90

A (Hz) 55 55

B (Hz) 70 65

C (Hz) 85 80

D (detik) 150 ~ 240 120

E (detik) 180 200

F (detik) 300 470

Kendali Suhu Pipa Buang

Uraian Suhu pipa buang digunakan sebagai suhu internal kompresor. Jika suhu pipa buang naik

melebihi tingkat tertentu, batas atas frekuensi diatur untuk menjaga suhu pipa buang agar

tidak naik lagi.

Rincian

Zona berhenti

A

Zona

B turun

Suhu pipa

buang

C Zona tetap

D

Zona atur ulang E

(R14266)

Kelas 40/50/52/58 Kelas 68/75/80/90

A (˚C) 110 120

B (˚C) 103 111

C (˚C) 102 109

D (˚C) 100 107 ★

E (˚C) 95 107 ★

★ Suhu D dan E adalah sama

Zona Kendali

Zona berhenti Ketika suhu mencapai zona berhenti, kompresor berhenti.

Zona turun Batas atas frekuensi menurun.

Zona tetap Batas atas frekuensi tetap.

Zona atur ulang Batas atas frekuensi dibatalkan.

Fungsi dan Pengendalian

118

Spesifikasi Pengendalian

SiBE121135_A

Kendali Arus input

Uraian Arus input dideteksi oleh CT saat kompresor berjalan, dan batas atas frekuensi diatur dari

arus input.

Pada kasus model pompa kalor, kendali ini yang merupakan kendali batas atas frekuensi

mengambil prioritas atas kendali batas bawah dari kompensasi operasi katup empat arah.

Rincian

Kompresor Berhenti

Zona berhenti

Zona turun

Zona tetap

Arus input

Kendali Frekuensi di setiap

zona Zona berhenti

Zona atur ulang

(R14912)

Setelah 2,5 detik berada di zona ini, kompresor berhenti.

Zona turun

Batas atas frekuensi kompresor ditetapkan sebagai frekuensi operasi– 2 Hz.

Selanjutnya, frekuensi output turun 2 Hz setiap detiknya sampai mencapai zona tetap.

Zona tetap

Frekuensi maksimum saat ini tetap berlangsung.

Zona atur ulang

Batas frekuensi dibatalkan.

Pembatasan nilai turun dan berhenti arus sesuai dengan suhu outdoor

Arus menurun ketika suhu outdoor menjadi lebih tinggi dari tingkat tertentu

(tergantung pada model).

Kendali perlindungan kebekuan

Uraian Selama operasi pendinginan, sinyal yang dikirim dari unit indoor menentukan batas atas

frekuensi dan mencegah pembekuan penukar panas indoor. (Sinyal dari unit indoor dibagi ke

dalam zona-zona.)

Rincian Pembatasan frekuensi operasi dinilai dengan suhu penukar panas indoor selama 2 detik

setelah operasi dimulai dan 30 detik setelah jumlah ruang operasi diubah.

(Referensi) Suhu termistor penukar panas indoor

13˚C

11˚C

9˚C

7˚C

0˚C

(R14913)

Zona atur ulang

Zona naik

Zona tetap

Zona turun

Zona berhenti

119 Fungsi dan Pengendalian

SiBE121135_A Spesifikasi Pengendalian

Kendali pemutusan Puncak Pemanasan

Uraian Selama operasi pemanasan, suhu penukar panas indoor menentukan batas atas frekuensi

untuk mencegah tekanan tinggi tidak normal.

Rincian Frekuensi operasi dinilai dengan suhu penukar panas indoor selama 2 menit setelah

operasi dimulai dan F detik setelah jumlah ruang operasi diubah.

Nilai maksimum kendali suhu penukar panas indor adalah sebagai berikut (tidak

termasuk ruang yang dihentikan).

Zona Kendali

Zona berhenti Ketika suhu mencapai zona berhenti, kompresor berhenti.

Zona turun Batas atas frekuensi menurun.

Zona tetap Batas atas frekuensi tetap.

Zona naik Batas atas frekuensi meningkat.

Zona atur ulang Batas atas frekuensi dibatalkan.

A (°C) 65

B (°C) 55

C (°C) 54

D (°C) 52

E (°C) 50

F (detik)

Saat meningkat 30

Saat menurun 2

Zona berhenti A˚C

B˚C

C˚C Zona turun

D˚C Zona tetap

Suhu termistor penukar panas indoor

Zona naik

Zona atur ulang

E˚C

(R14645)

Spesifikasi Pengendalian

SiBE121135_A

Fungsi dan Pengendalian

120

Kendali Kipas Outdoor 1. Kendali kipas ON untuk mendinginkan kotak listrik

Kipas outdoor dinyalakan (ON) ketika suhu kotak listrik tinggi saat kompresor mati (OFF).

2. Kipas OFF selama pencairan

Kipas outdoor dimatikan (OFF) saat pencairan

3. Kipas mati ketika berhenti

Kipas outdoor akan mati 60 detik setelah kompresor berhenti.

4. Kendali kecepatan kipas untuk pemeliharaan perbedaan tekanan

Kecepatan putar kipas outdoor dikendalikan untuk menjaga perbedaan tekanan selama operasi

pendinginan dengan suhu outdoor rendah.

Ketika perbedaan tekanan rendah, kecepatan putar kipas outdoor berkurang.

Ketika perbedaan tekanan tinggi, kecepatan putar kipas outdoor dikendalikan seperti

operasi normal.

5. Kendali kecepatan ketika jumlah ruangan pemananasan menurun

Ketika suhu outdoor lebih dari 10°C, kipas dimatikan selama 30 detik.

6. Kendali kecepatan kipas selama operasi paksa

Kipas outdoor dikendalikan seperti operasi normal selama operasi paksa.

7. Kendali kecepatan kipas selama operasi POWERFUL

Kecepatan putar kipas outdoor meningkat selama operasi POWERFUL.

8. Kendali kecepatan kipas selama operasi senyap unit indoor / outdoor

Kecepatan putar kipas outdoor berkurang oleh perintah operasi senyap unit indoor / outdoor.

9. Kendali kipas ON/OFF ketika operasi dimulai / berhenti

Kipas outdoor dinyalakan ketika operasi dimulai. Kipas outdoor dimatikan ketika operasi

berhenti.

Fungsi Perlindungan Kompresi Cairan

Uraian Untuk meningkatkan keandalan kompresor, kompresor dihentikan sesuai dengan suhu

outdoor dan suhu penukar panas outdoor.

Rincian Operasi berhenti bergantung pada suhu outdoor.

Kompresor mati jika sistem dalam operasi pendinginan dan suhu outdoor di bawah -12°C.

SiBE121135_A Spesifikasi Pengendalian

121 Fungsi dan Pengendalian

350 pulse 400 pulse

0 pulse

Kendali Pencairan

Uraian Pencairan dilakukan oleh siklus pendinginan (siklus terbalik). Waktu pencairan atau suhu

penukar panas outdoor harus lebih dari nilai tertentu sampai akhir.

Rincian Kondisi untuk Memulai Pencairan

Kondisi mulai ditentukan dengan suhu outdoor dan suhu penukar panas outdoor.

Sistem ada dalam operasi pemanasan.

Kompresor beroperasi selama 6 menit.

Lebih dari 38 menit jumlah waktu berlalu setelah dimulainya operasi, atau akhir

pencairan sebelumnya.

Kondisi untuk Membatalkan Pencairan

Suhu penukar panas target dipilih sebagai kondisi pembatalan dalam kisaran

4 ~ 12°C sesuai dengan suhu outdoor.

Frekuensi

A Hz

B Hz

Kendali PI

0 Hz 0 Hz

60 det. 120 det. 60 det.

530 det.

Kompresor

Katup empat arah

ON

OFF

ON

OFF

Kipas

ON

OFF

5 det. 5 det.

Bukaan katup ekspansi elektronik outdoor

(ruangan operasi)

Bukaan katup ekspansi elektronik

outdoor (ruangan berhenti)

450 pulse

160 pulse

bukaan awal

bukaan awal

(R18381)

Kelas 40/50/52/58 Kelas 68/75 Kelas 80/90

A (Hz)

62 54 39

B (Hz) 80 82 62

Spesifikasi Pengendalian

SiBE121135_A

Fungsi dan Pengendalian

122

Batas Tekanan Tinggi Hz Rendah

Uraian Batas atas tekanan tinggi di zona Hz rendah akan diatur. Batas atas suhu penukar panas

indoor juga diatur oleh frekuensi operasi. Zona dibagi menjadi tiga, zona atur ulang, zona

tetap, dan zona turun, dan kendali frekuensi dilakukan menurut masing-masing zona.

Rincian

A

Suhu penukar

Zona atur ulang

Zona turun

Zona B

tetap C

panas indoor tertinggi antara ruangan operasi

(R14587)

Kelas 40/50/52/58/68/75 Kelas 80/90

A (°C) 60 57

B (°C) 59 56

C (°C) 56 53

Catatan: Penurunan: Sistem berhenti 2 menit setelah tinggal di zona turun.

Kendali Katup Ekspansi Elektronik Outdoor

Uraian Hal-hal berikut termasuk dalam kendali katup ekspansi elektronik.

Katup ekspansi elektronik tertutup rapat

1. Katup ekspansi elektronik outdoor tertutup rapat saat menyalakan daya.

2. Kendali penyeimbangan tekanan

Kendali Distribusi Ruangan

1. Kendali isotermal pipa gas

2. Kendali SC (Subpendinginan)

3. Kendali suhu pipa cair (dengan semua port terhubung dan semua ruang diberi

AC)

4. Kendali suhu pipa cair untuk ruang berhenti

5. Kendali pencegahan pengembunan untuk rotor indoor

Kendali Buka

1. Kendali katup ekspansi elektronik ketika memulai operasi

2. Kendali katup ekspansi elektronik ketika frekuensi berubah

3. Kendali katup ekspansi elektronik outdoor untuk pencairan

4. Kendali katup ekspansi elektronik outdoor untuk pemulihan oli

5. Kendali katup ekspansi elektronik ketika suhu pipa buang tidak normal yaitu

sangat tinggi

6. Kendali katup ekspansi elektronik ketika termistor pipa buang terputus

7. Kendali katup ekspansi elektronik outdoor untuk kendali anti pembentukan es (anti-icing) untuk unit indoor

Kendali Umpan Balik (Feedback Control)

1. Kendali suhu target pipa buang

SiBE121135_A Spesifikasi Pengendalian

123 Fungsi dan Pengendalian

Rincian Berikut ini adalah contoh kendali katup ekspansi elektronik yang berfungsi dalam setiap

mode operasi.

Ke

nd

ali i

so

term

al

pip

a g

as

Ke

nd

ali S

C (

Su

bp

en

din

gin

an

)

Ken

da

li k

eti

ka

fre

ku

en

si b

eru

bah

Ke

nd

ali s

uh

u p

ipa

bu

an

g t

ing

gi

tid

ak

no

rma

l

ke

nd

ali p

em

ulih

an

oli

Ke

nd

ali p

erl

ind

un

ga

n k

eb

ek

ua

n

ind

oo

r

Ke

nd

ali s

uh

u p

ipa

ca

ir

Ke

nd

ali s

uh

u p

ipa

ca

ir u

ntu

k u

nit

ya

ng

tid

ak b

ero

pe

rasi

Ke

nd

ali p

en

ce

ga

ha

n p

en

ge

mb

un

an

un

tuk r

oto

r in

do

or

Pola operasi

• : Ada — : Tidak ada

Ketika daya dinyalakan

Pendinginan, operasi 1 ruangan

Pendinginan, operasi 2 ruangan untuk

Pendinginan, operasi 4 ruangan

Berhenti

Pemanasan, operasi 1 ruangan

Pemanasan, operasi 2 ruangan

Berhenti

Operasi pemanasan

Kendali pemutusan termistor pipa buang

Berhenti

Tertutup sepenuhnya ketika dinyalakan

Kendali buka ketika mulai

(Kendali suhu target pipa buang)

Kendali ketika ruang operasi berubah

(Kendali suhu target pipa buang) •

Kendali penyeimbangan tekanan

Kendali buka ketika mulai

(Kendali suhu target pipa buang)

— •

★2

★1

★3

Kendali ketika ruang operasi berubah

(Kendali suhu target pipa buang)

— •

★2

★1

★3

(Kendali pencairan)

Kendali penyeimbangan tekanan

— Kendali buka ketika mulai

Lanjut

— •

★2

★1

★3

Kendali penyeimbangan tekanan

★1: Ketika semua unit indoor beroperasi, "kendali suhu pipa cair" dilakukan.

(R16007)

★2 : "Kendali SC (Subpendinginan)" dilakukan untuk mengoperasikan unit indoor, ketika beberapa unit tidak beroperasi.

★3 : "Kendali suhu pipa cair untuk ruangan berhenti" dilakukan untuk unit indoor yang tidak beroperasi.

Spesifikasi Pengendalian

SiBE121135_A

Fungsi dan Pengendalian

124

Tertutup Penuh dengan Daya ON Katup ekspansi elektronik outdoor diaktifkan ketika daya listrik dinyalakan. Posisi pembukaan

diatur dan tekanan disamakan.

Kendali Penyeimbangan Tekanan Ketika kompresor dihentikan, kendali penyeimbangan tekanan diaktifkan. Katup ekspansi

elektronik outdoor terbuka dan tekanannya disamakan.

Kendali Batas Pembukaan

Uraian Pembukaan maksimum dan minimum katup ekspansi elektronik outdoor dibatasi.

Rincian Pembukaan maksimum katup ekspansi elektronik outdoor di ruang operasi: 450 pulse

Pembukaan manimum katup ekspansi elektronik outdoor di ruang operasi: 75 pulse Katup

ekspansi elektronik outdoor ditutup sepenuhnya di ruangan tempat pendinginan berhenti dan

dibuka pada tingkat tetap selama pencairan.

Kendali Operasi Awal / Ruang Operasi Perubahan Pembukaan katup ekspansi elektronik dikendalikan saat operasi dimulai, dan mencegah

pemanasan berlebih atau Kompresi Cairan.

Kendali ketika Frekuensi Berubah Ketika kendali suhu target pipa buang aktif, jika frekuensi target berubah ke nilai tertentu dalam

periode waktu tertentu, kendali suhu target pipa buang dibatalkan dan target pembukaan katup

ekspansi elektronik outdoor berubah.

Fungsi Pemulihan Oli

Uraian Pembukaan katup ekspansi elektronik outdoor di ruang penghentian pendinginan diatur

untuk membuka selama waktu tertentu pada interval tertentu sehingga oli pada ruang

penghentian pendinginan tidak dapat menumpuk.

Rincian Selama operasi pendinginan, setiap 1 jam terus beroperasi, katup ekspansi elektronik

outdoor pada ruang penghentian operasi dibuka oleh 80 pulse untuk waktu tertentu.

Kendali Suhu Tinggi Pipa Buang Ketika kompresor beroperasi, jika suhu pipa buang melebihi nilai tertentu, katup ekspansi

elektronik outdoor terbuka dan refrigeran bekerja ke sisi tekanan rendah. Prosedur ini

menurunkan suhu pipa buang.

SiBE121135_A Spesifikasi Pengendalian

125 Fungsi dan Pengendalian

Kendali Pemutusan Termistor Pipa buang

Uraian Pemutusan termistor pipa buang dideteksi dengan membandingkan suhu pipa buang dengan

suhu kondensasi. Jika termistor pipa buang terputus, katup ekspansi elektronik terbuka sesuai

dengan suhu outdoor dan frekuensi operasi, beroperasi untuk waktu tertentu, lalu berhenti.

Setelah 3 menit, operasi berlangsung kembali dan periksa apakah termistor pipa buang

terputus. Jika termistor pipa buang terputus, sistem berhenti setelah beroperasi untuk waktu

tertentu.

Jika pemutusan terdeteksi berulang kali, sistem dimatikan. Ketika kompresor bekerja selama 60

menit tanpa kesalahan, penghitung kesalahan diatur kembali.

Rincian Mendeteksi Terputusnya Termsitor

Ketika kendali penyalaan (660 ~ 810 detik, tergantung pada model) selesai, dilakukan

penyesuaian berikut.

1. Ketika mode operasi adalah pendinginan

Ketika kondisi berikut terpenuhi, terputusnya termistor pipa buang diketahui.

Suhu pipa buang + 6°C < suhu penukar panas outdoor

2. Ketika mode operasi adalah pemanasan

Ketika kondisi berikut terpenuhi, terputusnya termistor pipa buang dipastikan.

Suhu pipa buang + 6°C < suhu penukar panas indoor tertinggi

Penilaian saat termistor terputus

Jika terputusnya termistor diketahui, kompresor terus beroperasi selama 9 menit, lalu berhenti.

Jika kompresor berhenti secara beruang-ulang, sistem akan mati.

Kendali isotermal Pipa Gas Selama Pendinginan Ketika unit beroperasi di beberapa ruang, suhu pipa gas dideteksi dan pembukaan katup

ekspansi elektronik outdoor disesuaikan sehingga suhu pipa gas di setiap ruang menjadi

sama.

Ketika suhu pipa gas > rata-rata suhu pipa gas,

tingkat pembukaan katup ekspansi elektronik di ruangan yang sesuai meningkat.

Ketika suhu pipa gas < rata-rata suhu pipa gas,

tingkat pembukaan katup ekspansi elektronik di ruangan yang sesuai menurun.

Suhu dipantau setiap 40 detik.

Kendali SC (Subpendinginan)

Uraian Suhu pipa cair dan suhu penukar panas dideteksi dan pembukaan katup ekspansi elektronik

outdoor dikompensasi sehingga SC dari setiap ruangan menjadi SC target.

Ketika SC aktual adalah > SC target, buka katup ekspansi elektronik outdoor dari ruangan.

Ketika SC aktual adalah < SC target, tutup katup ekspansi elektronik outdoor dari

ruangan.

Rincian Kondisi Penyalaan (Start) Setelah menyelesaikan kendali penyalaan (660 ~ 810 detik, tergantung pada model), (semua)

katup ekspansi elektronik outdoor untuk ruang operasi dikendalikan.

Menentukan Kendali Katup Ekspansi Elektronik Outdoor

Pembukaan katup ekspansi elektronik outdoor disesuaikan sehingga perbedaan suhu antara

suhu penukar panas maksimum dari ruangan terhubung dan termistor suhu pipa cair menjadi

konstan.

Spesifikasi Pengendalian

SiBE121135_A

Fungsi dan Pengendalian

126

Kendali Suhu Target Pipa Buang Suhu target pipa buang diperoleh dari suhu penukar panas indoor dan outdoor, dan

pembukaan katup ekspansi elektronik disesuaikan sehingga suhu pipa buang aktual mendekati

suhu target pipa buang. (Kendali SH (pemanasan berlebih) tidak langsung menggunakan suhu

pipa buang)

Pembukaan katup ekspansi elektronik dan suhu target pipa buang diperiksa setiap 20 detik.

Suhu target pipa buang dikendalikan oleh suhu penukar panas indoor dan suhu penukar panas

outdoor. Tingkat pembukaan katup ekspansi elektronik outdoor disesuaikan dengan hal-hal

berikut.

Suhu target pipa buang

Suhu pipa buang aktual

Suhu pipa buang sebelumnya

Malfungsi Deteksi Malfungsi Sensor

Sensor malfungsi dapat terjadi baik di sistem termistor atau trafo arus (CT).

Keterkaitan Malfungsi Termistor

1. Termistor penukar panas outdoor

2. Termistor pipa buang

3. Termistor sirip radiasi

4. Termistor pipa gas

5. Termistor suhu outdoor

6. Termistor pipa cair

Keterkaitan Malfungsi CT

Lihat pada “CT atau Kelainan terkait ” pada hal 220 untuk penjelasan rinci.

Deteksi Arus dan Beban Berlebih

Uraian Untuk melindungi inverter, arus output yang berlebihan dideteksi dan suhu OL diamati untuk

melindungi kompresor.

Rincian Jika arus inverter melebihi 14 ~ 20 A (tergantung pada model), sistem akan mematikan

kompresor.

Jika suhu OL (kepala kompresor) melebihi 120° ~ 130°C, kompresor berhenti.

SC (Subpend

inginan)

Suhu target pipa buang diatur untuk menjadi tujuan SH.

Kemiringan tidak berubah, tergantung pada kondisi operasi.

SH (Pemanasan berlebih) (R14213)

SiBE121135_A Spesifikasi Pengendalian

127 Fungsi dan Pengendalian

Kendali Kekurangan Refrigeran

Uraian I : Deteksi dengan konsumsi daya

Jika konsumsi daya di bawah nilai yang ditentukan dan frekuensinya lebih tinggi dari frekuensi

yang ditentukan, ini dianggap sebagai kekurangan refrigeran.

Konsumsi dayanya rendah jika dibandingkan dengan konsumsi daya operasi normal saat

refrigeran tidak cukup. Kekurangan refrigeran dideteksi dengan memeriksa konsumsi daya.

Zona kekurangan

refrigeran

40 ~ 55 Hz (bergantung

pada model)

II : Deteksi dengan suhu pipa buang

Frekuensi

(R18382)

Jika suhu pipa buang lebih tinggi dari suhu pipa buang target, dan katup ekspansi elektronik

outdoor terbuka penuh selama lebih dari waktu yang ditentukan, maka dianggap sebagai

kekurangan refrigeran.

Suhu target pipa

buang

Zona kekurangan refrigeran

Lihat ke “Kekurangan refrigeran” pada hal 200 untuk penjelasan rinci.

(R1391)

Fungsi Anti Pembentukan Es (Anti-icing) Selama pendinginan, jika suhu penukar panas outdoor di dalam ruangan penghentikan operasi

menjadi di bawah suhu yang ditentukan untuk waktu tertentu, katup ekspansi elektronik outdoor

dibuka di dalam ruangan penghentikan operasi sebagaimana ditentukan, dan dilakukan operasi

tertutup sepenuhnya. Selanjutnya, jika kelainan pembekuan terjadi lebih dari waktu yang

ditentukan, sistem dimatikan karena kelainan sistem.

Ko

ns

um

si

da

ya

(I

np

ut

cu

rre

nt)

SiBE121135_A

Remote Kontrol 128

Bagian 5

Remote Kontrol

1. Unit Indoor RA........................................................................................ 129 1.1 FTXG25/35/50JV1BW(A), CTXS15/35K2V1B,

FTXS20/25K2V1B ............................................................................ 129

1.2 FTXS35/42/50K2V1B ....................................................................... 131

1.3 FTXS25/35/42/50J2V1B, FTXS60/71GV1B ....................................... 133

1.4 ATXS20/25/35/42/50G2V1B ............................................................. 135

1.5 FVXG25/35/50K2V1B ....................................................................... 137

1.6 FVXS25/35/50FV1B ......................................................................... 139

1.7 FLXS25/35/50/60BAVMB .................................................................. 141

1.8 FDXS25/35E7VMB, FDXS50/60C7VMB ........................................... 143

2. Unit Indoor SA ........................................................................................ 145 2.1 BRC1D528 ....................................................................................... 145

Unit Indoor RA SiBE121135_A

129 Remote Kontrol

Pemancar Sinyal

Penerima

• Untuk menggunakan remote kontrol, arahkan pemancar ke unit indoor. Jika ada

yang menghalangi sinyal antara unit

dan remote kontrol, seperti tirai, unit

tidak akan beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tampilan (LCD)

• Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua tampilannya

untuk tujuan penjelasan.)

Tombol pengaturan

SUHU • Ubah pengaturan suhu.

Tombol pengaturan KIPAS • Pilih pengaturan Laju Aliran

Udara.

Auto Senyap unit Indoor

Rendah

Agak Rendah

Tinggi

Agak menengah

Menengah • Pada operasi senyap unit indoor,

suara operasi menjadi lemah.

(Laju Aliran Udara juga menurun.)

• Pada Operasi KERING,

pengaturan laju aliran udara tidak

tersedia.

Tombol ON/OFF

• Tekan tombol ini sekali untuk

memulai operasi.

Tekan sekali lagi untuk mengakhirinya.

Tombol POWERFUL*1

• Operasi POWERFUL.

1. Unit Indoor RA

1.1 FTXG25/35/50JV1BW(A), CTXS15/35K2V1B,

FTXS20/25K2V1B

: AUTO 18 ~ 30 C

: DRY (KERING)

Tidak ada

: COOL

(DINGIN)

18 ~ 32 C

: HEAT

(PANAS)

10 ~ 30 C

: KIPAS Tidak ada

(R17860)

< ARC466A1, A6 >

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi POWERFUL Hal.93

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

SiBE121135_A Unit Indoor RA

Remote Kontrol 130

Buka Tutup Depan

Tombol MODE • Pilih mode operasi.

Tombol QUIET (SENYAP) • Operasi SENYAP UNIT

OUTDOOR.

• Operasi SENYAP tidak

tersedia pada operasi

KIPAS dan KERING.

• Operasi SENYAP dan operasi

POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada fungsi

yang ditekan terakhir.

Tombol COMFORT*2

(NYAMAN) • Arah aliran udara akan ke atas saat

dalam operasi COOL (DINGIN), ke

bawah saat dalam operasi HEAT (PANAS). Fungsi ini akan mencegah udara dingin atau hangat

berhembus langsung ke tubuh Anda.

Tombol ECONO*3 • Operasi ECONO.

Tombol SWING*4

• Menyesuaikan arah aliran udara.

• Ketika Anda menekan tombol

SWING (AYUN), Sirip bergerak

ke atas dan ke bawah.

Sirip berhenti ketika Anda

menekan tombol SWING lagi.

Tombol SENSOR

(Operasi INTELLIGENT

EYE*5) • Untuk memulai operasi

INTELLIGENT EYE, tekan tombol SENSOR.

" " yang ditampilkan pada LCD.

• Untuk membatalkan operasi INTELLIGENT EYE, tekan

tombol SENSOR lagi.

" " akan hilang dari LCD.

Tombol OFF TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol SELECT. Tekan kembali tombol ini untuk

menyelesaikan pengaturan TIMER.

Tombol PEMBATALAN

TIMER (TIMER CANCEL)

• Membatalkan pengaturan timer.

• Ini tidak dapat digunakan pada operasi WEEKLY TIMER.

Tombol SELECT (PILIH)

• Mengubah pengaturan

ON/OFF TIMER dan

WEEKLY TIMER.

Tombol CLOCK

(JAM)*7

: Tombol WEEKLY (MINGGUAN)

: Tombol PROGRAM

: Tombol COPY (SALIN)

: Tombol BACK (KEMBALI)

: Tombol NEXT

(SELANJUTNYA)

• Operasi WEEKLY TIMER*6.

Tombol ON TIMER

• Tekan tombol ini dan atur hari dan

waktu dengan tombol SELECT. Tekan kembali tombol ini untuk

menyelesaikan pengaturan

TIMER.

(R17861)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat

mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

★2 Operasi ALIRAN UDARA NYAMAN Hal.78, 80

★3 Operasi ECONO Hal.87 ★4 Pengaturan ayun otomatis Hal.76

★5 Operasi INTELLIGENT EYE Hal.90 ★6 Operasi WEEKLY TIMER Hal.97

★7 Pengaturan Jam Hal.96

Unit Indoor RA SiBE121135_A

131 Remote Kontrol

Pemancar Sinyal

Penerima

• Untuk menggunakan remote kontrol, arahkan pemancar ke unit indoor. Jika ada

yang menghalangi sinyal antara unit

dan remote kontrol, seperti tirai, unit

tidak akan beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tampilan (LCD)

• Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua tampilannya

untuk tujuan penjelasan.)

Tombol pengaturan

SUHU • Ubah pengaturan suhu.

Tombol pengaturan KIPAS • Pilih pengaturan Laju Aliran

Udara.

Auto Senyap unit Indoor

Rendah

Agak Rendah

Tinggi

Agak menengah

Menengah

• Pada operasi senyap unit indoor,

suara operasi menjadi lemah. (Laju

Aliran Udara juga menurun.)

• Pada Operasi KERING, pengaturan

laju aliran udara tidak tersedia.

Tombol ON/OFF • Tekan tombol ini sekali untuk

memulai operasi.

Tekan sekali lagi untuk mengakhirinya.

Tombol POWERFUL*1 • Operasi POWERFUL.

1.2 FTXS35/42/50K2V1B

: AUTO 18 ~ 30 C

: DRY

(KERING)

Tidak ada

: COOL

(DINGIN)

18 ~ 32 C

: HEAT

(PANAS)

10 ~ 30 C

: KIPAS Tidak ada

(R18413)

< ARC466A9 >

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi POWERFUL Hal.93

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

SiBE121135_A Unit Indoor RA

Remote Kontrol 132

Buka Tutup Depan

Tombol MODE • Pilih mode operasi.

Tombol pengaturan

Tombol UNIT QUIET

ECONO*5 / OUTDOOR

• Setiap kali Anda

men

ekan pilihan pengaturan

berbeda pada LCD.

kecerahan lampu*2

Tombol COMFORT

/SENSOR (Operasi COMFORT AIRFLOW*3/

ECONO

kosong

SENYAP UNIT OUTDOOR

Operasi INTELLIGENT EYE*4) • Setiap kali Anda menekan

tombol COMFORT/SENSOR,

pegaturan berubah ke urutan

berikut.

Tanpa pengaturan Kombinasi

• Operasi SENYAP tidak tersedia pada operasi

KIPAS dan KERING.

• Operasi SENYAP dan operasi POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada ALIRAN UDARA

NYAMAN

kosong

INTELLIGENT EYE

fungsi yang ditekan terakhir.

Tombol SWING*6

• Menyesuaikan arah aliran udara. • Ketika Anda menekan tombol

SWING (AYUN),

Tanpa pengaturan Kombinasi

Tombol OFF TIMER

• Tekan tombol ini dan atur hari dan waktu dengan tombol SELECT.

Tekan kembali tombol ini untuk menyelesaikan pengaturan

TIMER.

Tombol PEMBATALAN

TIMER

• Membatalkan pengaturan timer.

• Ini tidak dapat digunakan pada operasi WEEKLY TIMER.

Tombol SELECT (PILIH)

• Mengubah pengaturan

ON/OFF TIMER dan

WEEKLY TIMER.

Tombol CLOCK

(JAM)*8

Sirip bergerak ke atas dan ke

bawah, atau (dan) sirip bergerak

ke kanan dan ke kiri. Sirip (kisi

kisi) berhenti ketika Anda menekan tombol SWING lagi.

: Tombol WEEKLY (MINGGUAN)

: Tombol PROGRAM

: Tombol COPY (SALIN)

: Tombol BACK (KEMBALI)

: Tombol NEXT (SELANJUTNYA)

• Operasi WEEKLY TIMER*7.

Tombol ON TIMER

• Tekan tombol ini dan atur hari dan

waktu dengan tombol SELECT.

Tekan kembali tombol ini untuk

menyelesaikan pengaturan

TIMER.

(R17861)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan (URL:

http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

★2 Pengaturan kecerahan lampu Hal.95

★3 Operasi ALIRAN UDARA NYAMAN Hal.78

, 80

★4 Operasi INTELLIGENT

EYE 2-area Hal.91

★5 Operasi ECONO Hal.87

★6 Pengaturan ayun otomatis Hal.76

★7 Operasi WEEKLY TIMER Hal.97

★8 Pengaturan Jam Hal.96

Unit Indoor RA SiBE121135_A

133 Remote Kontrol

Pemancar Sinyal

Penerima

• Untuk menggunakan remote kontrol, arahkan pemancar ke unit indoor. Jika ada

yang menghalangi sinyal antara unit

dan remote kontrol, seperti tirai, unit

tidak akan beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tampilan (LCD)

• Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua tampilannya

untuk tujuan penjelasan.)

Tombol pengaturan

SUHU • Ubah pengaturan suhu.

Tombol pengaturan KIPAS • Pilih pengaturan laju aliran udara

setiap kali Anda menekan

tombol ini.

Auto Senyap unit Indoor

Rendah

Agak Rendah

Tinggi

Agak menengah

Menengah

• Pada operasi senyap unit indoor,

suara operasi menjadi lemah. (Laju

Aliran Udara juga menurun.)

• Pada Operasi KERING, pengaturan

laju aliran udara tidak tersedia.

Tombol ON/OFF • Tekan tombol ini sekali

untuk memulai operasi.

Tekan sekali lagi untuk mengakhirinya.

Tombol POWERFUL*1 • Operasi POWERFUL.

1.3 FTXS25/35/42/50J2V1B, FTXS60/71GV1B

: AUTO 18 ~ 30 C

: DRY

(KERING)

Tidak ada

: COOL

(DINGIN)

18 ~ 32 C

: HEAT

(PANAS)

10 ~ 30 C

: KIPAS Tidak ada

(R18208)

< ARC452A3 >

Remote kontrol ini cocok dengan model pendingin saja dan pompa kalor ★ 2.

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi POWERFUL Hal.93 ★2 Pengaturan Tipe Model Hal.253

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

SiBE121135_A Unit Indoor RA

Remote Kontrol 134

Buka Tutup Depan

Tombol MODE • Pilih mode operasi.

(pompa kalor saja) (pompa kalor saja)

Tombol QUIET

(SENYAP) • Operasi SENYAP UNIT

OUTDOOR.

• Operasi SENYAP tidak

tersedia pada operasi

KIPAS dan KERING.

• Operasi SENYAP dan operasi

POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada fungsi

yang ditekan terakhir.

Tombol COMFORT

/SENSOR

(Operasi COMFORT AIRFLOW*3

/ Operasi

INTELL IGENT EYE*4 *5

)

• Setiap kali Anda menekan

tombol COMFORT/SENSOR,

pegaturan berubah ke urutan

berikut.

Tombol ECONO*6

• Operasi ECONO.

Tombol SWING*7

• Menyesuaikan arah aliran udara.

• Ketika Anda menekan tombol SWING (AYUN), Sirip bergerak ke atas dan ke bawah, atau (dan) sirip bergerak ke kanan dan ke kiri. Sirip (kisi kisi) berhenti ketika Anda menekan tombol SWING lagi.

Tombol WEEKLY (MINGGUAN)

: Tombol WEEKLY (MINGGUAN)

: Tombol PROGRAM

: Tombol COPY (SALIN)

: Tombol BACK (KEMBALI)

: Tombol NEXT (SELANJUTNYA)

• Operasi WEEKLY TIMER*8.

Tombol ON TIMER

ALIRAN

UDARA

NYAMAN

kosong

INTELLIGENT

EYE

• Tekan tombol ini dan atur hari dan waktu dengan tombol SELECT.

Tekan kembali tombol ini untuk menyelesaikan pengaturan

TIMER.

Tanpa pengaturan Kombinasi

Tombol OFF TIMER

• Tekan tombol ini dan atur hari dan waktu dengan tombol SELECT.

Tekan kembali tombol ini untuk menyelesaikan pengaturan

TIMER.

Tombol PEMBATALAN

TIMER

• Membatalkan pengaturan timer.

• Ini tidak dapat digunakan pada

operasi WEEKLY TIMER.

Tombol CLOCK*9

Tombol

SELECT

• Mengubah pengaturan

ON/OFF TIMER dan

WEEKLY TIMER.

(R18209)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh

panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan (URL:

http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

★3 Operasi ALIRAN

UDARA NYAMAN

Hal.78, 80

★4 Operasi INTELLIGENT

EYE 2-area (kelas 20-50) Hal.91

★5 Operasi INTELLIGENT EYE (kelas 60/71)

Hal.90

★6 Operasi ECONO Hal.87

★7 Pengaturan ayun otomatis Hal.76

★8 Operasi WEEKLY TIMER Hal.97

★9 Pengaturan Jam Hal.96

Unit Indoor RA SiBE121135_A

135 Remote Kontrol

Tampilan (LCD) • Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua

tampilannya untuk tujuan penjelasan.)

Tombol ECONO*1 • Operasi ECONO Tombol ON/OFF

• Tekan tombol ini sekali untuk

memulai operasi.

Tekan sekali lagi untuk mengakhirinya.

Pemancar Sinyal

R

Penerima

• Untuk menggunakan remote kontrol,

arahkan pemancar ke unit indoor. Jika

ada yang menghalangi sinyal antara unit

dan remote kontrol, seperti tirai, unit tidak

akan beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tombol pengaturan SUHU • Ubah pengaturan suhu.

Tombol POWERFUL*2 • Operasi POWERFUL

(R18210)

1.4 ATXS20/25/35/42/50G2V1B

: AUTO 18 ~ 30 ˚C

: DRY

(KERING)

Tidak ada

: COOL (DINGIN)

18 ~ 32 ˚C

: HEAT

(PANAS)

10 ~ 30 ˚C

: KIPAS Tidak ada

< ARC433A85 >

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi ECONO Hal.87 ★2 Operasi POWERFUL Hal.93

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat

mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

SiBE121135_A Unit Indoor RA

Remote Kontrol 136

Buka Tutup Depan

Tombol MODE • Pilih mode operasi.

Tombol QUIET (SENYAP) • Operasi SENYAP UNIT

OUTDOOR.

Tombol pengaturan KIPAS

• Pilih pengaturan laju aliran udara setiap kali Anda menekan tombol

ini.

• Operasi SENYAP tidak tersedia pada operasi

KIPAS dan KERING.

• Operasi SENYAP dan operasi POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada

fungsi yang ditekan terakhir.

Auto Senyap unit Indoor

Rendah

Agak

Rendah

Tinggi Agak menengah

Menengah

Tombol ON TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol pengaturan TIMER.

Tekan kembali tombol ini untuk menyelesaikan pengaturan

TIMER.

Tombol OFF TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol pengaturan TIMER.

Tekan kembali tombol ini untuk menyelesaikan pengaturan

TIMER.

Tombol pengaturan TIMER

• Mengubah pengaturan

ON/OFF TIMER.

Tombol COMFORT/SENSOR

(Operasi COMFORT AIRFLOW*4

/

Operasi INTELLIGENT EYE*5

)

• Setiap kali Anda menekan

tombol COMFORT/SENSOR,

pegaturan berubah ke urutan berikut.

• Pada operasi senyap unit indoor, suara operasi menjadi lemah. (Laju Aliran Udara juga menurun.)

• Pada Operasi KERING, pengaturan laju aliran udara tidak tersedia.

ALIRAN UDARA

NYAMAN

kosong

INTELLIGENT EYE

Tombol CLOCK (JAM)*6

Tanpa pengaturan Kombinasi

(R18211)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat

mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

★3 Pengaturan ayun otomatis Hal.76

★4 Operasi ALIRAN UDARA NYAMAN

Hal.78, 80

★5 Operasi INTELLIGENT EYE Hal.90

★6 Pengaturan Jam Hal.96

Tombol

SWING*3

• Menyesuaikan arah aliran udara.

• Ketika Anda menekan tombol SWING (AYUN), Sirip bergerak ke atas dan ke bawah, atau (dan) sirip bergerak ke kanan dan ke kiri. Sirip (kisi kisi) berhenti ketika Anda menekan tombol SWING lagi.

Tombol PEMBATALAN TIMER • Membatalkan pengaturan timer. Tombol RESET

• Memulai ulang unit jika membeku.

• Menggunakan benda tipis untuk menekan.

Unit Indoor RA SiBE121135_A

137 Remote Kontrol

Pemancar Sinyal

Penerima

• Untuk menggunakan remote kontrol, arahkan pemancar ke unit indoor. Jika ada

yang menghalangi sinyal antara unit

dan remote kontrol, seperti tirai, unit

tidak akan beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tampilan (LCD)

• Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua tampilannya

untuk tujuan penjelasan.)

Tombol pengaturan

SUHU • Ubah pengaturan suhu.

Tombol pengaturan KIPAS • Pilih pengaturan Laju Aliran

Udara.

Auto Senyap unit Indoor

Rendah

Agak Rendah

Tinggi

Agak menengah

Menengah

• Pada operasi senyap unit indoor,

suara operasi menjadi lemah. (Laju

Aliran Udara juga menurun.)

• Pada Operasi KERING, pengaturan

laju aliran udara tidak tersedia.

Tombol ON/OFF • Tekan tombol ini sekali untuk

memulai operasi.

Tekan sekali lagi untuk mengakhirinya.

Tombol RADIANT*1

• Memilih operasi RADIANT.

• Tombol ini hanya dapat digunakan

dalam mode operasi HEAT.

HEAT (PANAS)

RADIANT1 RADIANT2

1.5 FVXG25/35/50K2V1B

: AUTO 18 ~ 30 C

: DRY

(KERING)

Tidak ada

: COOL (DINGIN)

18 ~ 32 C

: HEAT

(PANAS)

10 ~ 30 C

: KIPAS Tidak ada

(R18348)

< ARC466A2 >

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi RADIANT Hal.81

Catatan:Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat

mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

Remote Kontrol 138

SiBE121135_A Unit Indoor RA

Buka Tutup Depan

Tombol MODE • Pilih mode operasi.

Tombol QUIET (SENYAP) • Operasi SENYAP UNIT

OUTDOOR • Operasi SENYAP tidak

tersedia pada operasi

KIPAS dan KERING.

• Operasi SENYAP dan operasi

POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada fungsi

yang ditekan terakhir.

Tombol ECONO*3 • Operasi ECONO.

Tombol SWING*4 • Menyesuaikan arah aliran udara. • Ketika Anda menekan tombol

SWING (AYUN), Sirip

bergerak ke atas dan ke

bawah. Sirip berhenti ketika

Anda menekan tombol

SWING lagi.

Pengaturan kecerahan

lampu*5

Tombol POWERFUL*2 • Operasi POWERFUL.

Tombol OFF TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol SELECT. Tekan kembali tombol ini untuk

menyelesaikan pengaturan

TIMER.

Tombol PEMBATALAN TIMER • Membatalkan pengaturan

timer. • Ini tidak dapat digunakan

pada operasi WEEKLY

TIMER.

Tombol SELECT (PILIH) • Mengubah pengaturan

ON/OFF TIMER dan WEEKLY TIMER.

Tombol CLOCK

(JAM)*7

: Tombol WEEKLY (MINGGUAN)

: Tombol PROGRAM

: Tombol COPY (SALIN)

: Tombol BACK (KEMBALI)

: Tombol NEXT

(SELANJUTNYA)

• Operasi WEEKLY TIMER*6.

Tombol ON TIMER • Tekan tombol ini dan atur hari

dan waktu dengan tombol

SELECT.

Tekan kembali tombol ini

untuk menyelesaikan

pengaturan TIMER.

(R18349)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

Catatan:Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat

mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

★2

Operasi POWERFUL Hal.93 ★

3 Operasi ECONO Hal.

87 ★4

Pengaturan ayun otomatis Hal.76

★5

Pengaturan kecerahan lampu Hal.95 ★

6 Operasi WEEKLY TIMER Hal.9

7 ★7

Pengaturan Jam Hal.96

139 Remote Kontrol

SiBE121135_A Unit Indoor RA

Pemancar Sinyal

Penerima

• Untuk menggunakan remote kontrol, arahkan pemancar ke unit indoor. Jika ada

yang menghalangi sinyal antara unit

dan remote kontrol, seperti tirai, unit

tidak akan beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tampilan (LCD) • Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua tampilannya

untuk tujuan penjelasan.)

Tombol pengaturan

SUHU • Ubah pengaturan suhu.

Tombol pengaturan KIPAS • Pilih pengaturan laju aliran udara

setiap kali Anda menekan

tombol ini.

Auto Senyap unit Indoor

Rendah

Agak Rendah

Tinggi

Agak menengah

Menengah

• Pada operasi senyap unit indoor,

suara operasi menjadi lemah. (Laju

Aliran Udara juga menurun.)

• Pada Operasi KERING, pengaturan

laju aliran udara tidak tersedia.

Tombol ON/OFF • Tekan tombol ini sekali

untuk memulai operasi.

Tekan sekali lagi untuk mengakhirinya.

Tombol POWERFUL*1

• Operasi POWERFUL.

1.6 FVXS25/35/50FV1B

: AUTO 18 ~ 30 C

: DRY

(KERING)

Tidak ada

: COOL

(DINGIN)

18 ~ 32 C

: HEAT

(PANAS)

10 ~ 30 C

: KIPAS Tidak ada

(R17823)

< ARC452A1 >

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi POWERFUL Hal.93

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat

mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

Unit Indoor RA SiBE121135_A

Remote Kontrol 140

Buka Tutup Depan

Tombol MODE

• Pilih mode operasi.

Tombol QUIET (SENYAP)

• Operasi SENYAP UNIT

OUTDOOR

• Operasi SENYAP tidak

tersedia pada operasi

KIPAS dan KERING.

• Operasi SENYAP dan operasi

POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada fungsi

yang ditekan terakhir.

Tombol OFF TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol SELECT. Tekan kembali tombol ini untuk

menyelesaikan pengaturan TIMER.

Tombol ECONO*2 • Operasi ECONO.

Tombol SWING*3 • Menyesuaikan arah aliran udara. • Ketika Anda menekan tombol

SWING (AYUN), Sirip bergerak ke atas dan ke bawah. Sirip (kisi kisi) berhenti ketika Anda menekan tombol SWING lagi.

Tombol WEEKLY (MINGGUAN)

: Tombol WEEKLY (MINGGUAN) : Tombol PROGRAM

: Tombol COPY (SALIN) : Tombol BACK

(KEMBALI) : Tombol NEXT

(SELANJUTNYA) • Operasi WEEKLY TIMER*4.

Tombol PEMBATALAN

TIMER • Membatalkan pengaturan

timer.

• Ini tidak dapat digunakan pada operasi WEEKLY

TIMER.

Tombol SELECT (PILIH) • Mengubah pengaturan ON/OFF

TIMER dan WEEKLY TIMER.

Tombol ON TIMER • Tekan tombol ini dan atur

hari dan waktu dengan

tombol SELECT. Tekan kembali tombol ini untuk

menyelesaikan pengaturan TIMER.

Tombol CLOCK (JAM)*5

(R17824)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat

mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

★4 Operasi WEEKLY TIMER Hal.97 ★5 Pengaturan Jam Hal.96

★2 Operasi ECONO Hal.87 ★3 Pengaturan ayun otomatis Hal.76

SiBE121135_A Unit Indoor RA

141 Remote Kontrol

1.7 FLXS25/35/50/60BAVMB

Pemancar Sinyal Tampilan (LCD) • Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua tampilannya

untuk tujuan penjelasan.)

Penerima

• Untuk menggunakan remote kontrol, arahkan

pemancar ke unit indoor. Jika ada

yang menghalangi sinyal antara unit

dan remote kontrol, seperti tirai,

unit tidak akan beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tombol HOME LEAVE (MENINGGALKAN RUMAH)*1 • Tekan tombol ini untuk memulai

operasi HOME

LEAVE.

Lampu HOME

LEAVE menyala.

Lampu HOME

LEAV

• Tekan tombol lagi untuk membatalkan operasi HOME LEAVE.

Tombol pengaturan

SUHU • Ubah pengaturan suhu.

: AUTO 18 ~ 30 ˚C

: DRY (KERING)

Tidak ada

: COOL (DINGIN)

18 ~ 32 ˚C

: HEAT (PANAS)

10 ~ 30 ˚C

: KIPAS Tidak ada

Tombol ON/OFF • Tekan tombol ini sekali untuk memulai

operasi.

Tekan sekali lagi untuk mengakhirinya.

Tombol POWERFUL*2 • Operasi POWERFUL

(R17827)

< ARC433B67 >

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi HOME LEAVE Hal.88 ★2 Operasi POWERFUL Hal.93

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

Unit Indoor RA SiBE121135_A

Remote Kontrol 142

Buka Tutup Depan

Tombol MODE • Pilih mode operasi.

Tombol QUIET (SENYAP) • Operasi SENYAP UNIT

OUTDOOR.

Tombol pengaturan KIPAS • Pilih pengaturan laju aliran udara setiap kali

Anda menekan tombol ini.

• Operasi SENYAP tidak

tersedia pada operasi

KIPAS dan KERING. • Operasi SENYAP dan operasi

POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada

fungsi yang ditekan terakhir.

Auto Senyap unit Indoor

Rendah

Agak

Rendah

Tinggi

Agak menengah

Menen

gah

Tombol ON TIMER • Tekan tombol ini dan atur hari

dan waktu dengan tombol

pengaturan TIMER. Tekan

kembali tombol ini untuk

menyelesaikan pengaturan TIMER.

Tombol OFF TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol pengaturan TIMER. Tekan kembali tombol ini

untuk menyelesaikan pengaturan TIMER.

Tombol pengaturan TIMER • Mengubah pengaturan

ON/OFF TIMER.

Tombol CLOCK (JAM)*4

• Pada operasi senyap unit indoor,

suara operasi menjadi lemah. (Laju

Aliran Udara juga menurun.)

• Pada Operasi KERING, pengaturan

laju aliran udara tidak tersedia.

Tombol SWING*3 • Menyesuaikan arah aliran udara. • Ketika Anda menekan tombol SWING

(AYUN), Sirip bergerak ke atas dan ke

bawah. Sirip berhenti ketika Anda

menekan tombol SWING lagi.

Tombol PEMBATALAN TIMER • Membatalkan pengaturan timer.

Tombol RESET • Memulai ulang unit jika membeku.

• Menggunakan benda tipis untuk menekan.

(R18385)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★3 Pengaturan ayun otomatis Hal.76 ★4 Pengaturan Jam Hal.96

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

SiBE121135_A Unit Indoor RA

143 Remote Kontrol

Tombol pengaturan

SUHU

• Ubah pengaturan suhu. Tombol HOME LEAVE (MENINGGALKAN RUMAH)*1

• Tekan tombol ini untuk

memulai operasi HOME

LEAVE.

Lampu HOME LEAVE menyala.

Lampu HOME LEAVE

• Tekan tombol lagi untuk membatalkan

operasi HOME LEAVE.

Tombol ON/OFF • Tekan tombol ini sekali untuk

memulai operasi.

Tekan sekali lagi untuk mengakhirinya.

Tombol POWERFUL*2

• Operasi POWERFUL

Pemancar Sinyal • Untuk menggunakan remote kontrol,

arahkan pemancar ke unit indoor. Jika ada

yang menghalangi sinyal antara unit dan

remote kontrol, seperti tirai, unit tidak akan

beroperasi.

• Jarak maksimal komunikasi

adalah sekitar 7 meter.

Tampilan (LCD) • Menampilkan pengaturan saat ini.

(Dalam ilustrasi ini, tiap bagian

ditampilkan dengan semua

tampilannya untuk tujuan

penjelasan.)

(R17825)

FDXS25/35E7VMB, FDXS50/60C7VMB

: AUTO 18 ~ 30 ˚C

: DRY (KERING

)

Tidak ada

: COOL (DINGIN)

18 ~ 32 ˚C

: HEAT (PANAS)

10 ~ 30 ˚C

: KIPAS Tidak ada

< ARC433B69 >

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★1 Operasi HOME LEAVE Hal.88 ★2 Operasi POWERFUL Hal.93

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

Unit Indoor RA SiBE121135_A

Remote Kontrol 144

Buka Tutup Depan

Tombol MODE • Pilih mode operasi.

Tombol QUIET (SENYAP) • Operasi SENYAP UNIT

OUTDOOR.

Tombol pengaturan KIPAS • Pilih pengaturan laju aliran udara

setiap kali Anda menekan tombol

ini.

• Operasi SENYAP tidak tersedia pada operasi

KIPAS dan KERING.

• Operasi SENYAP dan operasi POWERFUL tidak dapat

digunakan bersamaan.

Prioritas diberikan pada fungsi yang ditekan terakhir.

Auto Senyap unit

Indoor

Rendah

Agak

Rendah

Tinggi

Agak menengah

Menen

gah

Tombol ON TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol pengaturan TIMER. Tekan kembali tombol ini untuk menyelesaikan pengaturan TIMER.

Tombol OFF TIMER • Tekan tombol ini dan atur hari dan

waktu dengan tombol pengaturan TIMER. Tekan kembali tombol ini untuk menyelesaikan pengaturan

TIMER.

• Pada operasi senyap unit indoor, suara operasi menjadi lemah. (Laju

Aliran Udara juga menurun.)

• Pada Operasi KERING, pengaturan laju aliran udara tidak tersedia.

Tombol PEMBATALAN TIMER • Membatalkan pengaturan timer.

Tombol RESET • Memulai ulang unit jika membeku.

• Menggunakan benda tipis untuk menekan.

Tombol CLOCK (JAM)*3

(R18386)

Referensi Lihat halaman berikut ini untuk penjelasan rinci.

★3 Pengaturan Jam Hal.96

Catatan: Lihat panduan pengoperasian model yang dipakai untuk penjelasan rinci. Anda dapat mengunduh panduan operasi dari: ‘DISTRIBUTOR’S PAGE’:

DISTRIBUTOR’S PAGE Informasi Produk Panduan Operasi/Pemasangan

(URL: http://global.daikin.com/Daikin/global/Distributors_admin/user_mng/login.php)

Tombol pengaturan TIMER • Mengubah pengaturan

ON/OFF TIMER.

SiBE121135_A Unit Indoor RA

145 Remote Kontrol

2. Unit Indoor SA

BRC1D528

3 6 23 7 8 9 2 1

10

4 11

12

14 22

17

25

16 13 15 18 19

29

20 21 5 24

33

26 35

27 36

37

28 30 31 32 34

Remote Kontrol 146

Unit Indoor SA SiBE121135_A

SiBE121135_A Unit Indoor SA

1 TOMBOL ON/OFF

Tekan tombol ON / OFF untuk memulai atau menghentikan sistem.

2 LAMPU OPERASI

Lampu operasi menyala selama operasi atau berkedip

jika kegagalan fungsi terjadi.

3 IKON MODE OPERASI

Ikon ini menunjukkan mode operasi saat ini (KIPAS, KERING, OTOMATIS, PENDINGINAN,

PEMANASAN).

4 IKON MODE VENTILASI

ikon ini menunjukkan mode ventilasi saat ini (HRV saja) (OTOMATIS, PERTUKARAN PANAS, PINTASAN (BYPASS)).

5 IKION VENTILASI

Ikon ventilasi muncul ketika ventilasi disesuaikan

dengan tombol jumlah ventilasi (HRV saja). Secara bersamaan, jumlah ventilasi ditunjukkan dengan ikon

kecepatan kipas (lihat 22).

6 IKON PEMBERSIH UDARA

Ikon ini menunjukkan bahwa unit pembersih udara

(pilihan) adalah operasional.

7 IKON MENINGGALKAN RUMAH

Ikon meninggalkan rumah menunjukkan status fungsi

meninggalkan rumah.

ON Meninggalkan rumah diaktifkan

BERKEDIP Meninggalkan rumah aktif

OFF Meninggalkan rumah dinonaktifkan

8 IKON KENDALI EKSTERNAL

Ikon ini menunjukkan bahwa pengendali lain dengan prioritas yang lebih tinggi mengendalikan atau

menonaktifkan instalasi Anda.

9 IKON KENDALI TERPUSAT BERDASARKAN

PERALIHAN

Ikon ini menunjukkan bahwa peralihan instalasi berdasrkan kendali terpusat ditetapkan untuk unit indoor

lain atau pemilih dingin/panas opsional yang terhubung

ke unit outdoor (= remote kontrol induk).

10 HARI INDIKATOR MINGGUAN

Hari indikator mingguan menunjukkan hari minggu saat ini (atau hari yang diatur ketika membaca atau

memprogram timer terjadwal).

11 TAMPILAN JAM

Tampilan jam menunjukkan waktu saat ini (atau waktu tindakan ketika membaca atau memprogram timer

terjadwal).

12 SUHU YANG DIATUR MAKSIMAL

Suhu yang diatur maksimal menunjukkan

suhu yang diatur maksimal saat dalam operasi batas.

13 SUHU YANG DIATUR MINIMAL

Suhu yang diatur minimal menunjukkan suhu yang diatur minimal saat dalam operasi batas.

14 IKON TIMER TERJADWAL

Ikon ini menunjukkan bahwa timer terjadwal diaktifkan.

15 IKON TINDAKAN

Ikon ini menunjukkan tindakan selama setiap hari dari timer terjadwal.

16 IKON OFF

Ikon ini menunjukkan bahwa tindakan OFF dipilih saat memprogram timer terjadwal.

17 PEMERIKSAAN YANG DIPERLUKAN dan

Ikon ini menunjukkan bahwa pemeriksaan diperlukan. Konsultasikan dengan tukang pemasang Anda.

18 TAMPILAN SUHU YANG DIATUR Ini

menunjukkan suhu yang diatur saat ini

ketika pemasangan (tidak ditampilkan dalam operasi BATAS atau mode KIPAS atau KERING).

19 PENGATURAN

Tidak digunakan, untuk keperluan servis saja.

20 IKON ARAH ALIRAN UDARA

Ikon ini menunjukkan arah aliran udara (hanya untuk

pemasangan dengan sirip aliran udara berpenggerak

motor).

21 TIDAK ADA

ditampilkan setiap kali pilihan yang dituju tidak

dapat dipasang atau fungsi tidak ada.

22 IKON KECEPATAN KIPAS

Ikon ini menunjukkan setelan

kecepatan kipas.

23 IKON MODE PENYALAAN PANAS/PENCAIRAN

Ikon ini menunjukkan mode penyalaan panas/pencairan aktif

24 IKON WAKTU PEMBERSIHAN FILTER UDARA

Ikon ini menunjukkan filter udara harus dibersihkan. Lihat panduan unit outdoor.

25 IKON WAKTU PEMBERSIHAN ELEMEN

Ikon ini menunjukkan elemen harus

dibersihkan ( saja

26 TOMBOL MODE VENTILASI

Tombol mode operasi mengoperasikan ; lihat

panduan untuk penjelasan rinci.

27 TOMBOL JUMLAH VENTILASI

Tombol mode mengatur jumlah ventilasi lihat

panduan untuk penjelasan rinci.

28 TOMBOL OPERASI UJI/PEMERIKSAAN Tidak

digunakan, untuk keperluan servis saja.

29 TOMBOL PEMROGRAMAN Tombol ini adalah tombol berbagai

fungsi.

Tergantung pada pengubahan sebelumnya dari

pengguna, tombol pemrograman dapat memiliki berbagai

fungsi.

Unit Indoor SA SiBE121135_A

147 Remote Kontrol

30 TOMBOL TIMER TERJADWAL

Tombol ini mengaktifkan atau menonaktifkan timer terjadwal.

31 TIME ADJUST BUTTON TOMBOL PENYESUAI WAKTU

Tombol ini digunakan untuk menyesuaikan jam atau, ketika dalam mode pemrograman, untuk menyesuaikan

waktu tindakan yang diprogram. Kedua tombol memiliki

fungsi auto-ulang.

32 TOMBOL PENYESUAI SUHU

Tombol ini digunakan untuk menyesuaikan titik pengaturan saat ini atau, untuk menyesuaikan suhu titik

pengaturan yang diprogram (langkah = 1C). Kedua tombol juga digunakan untuk mengatur hari dalam seminggu.

33 TOMBOL MIN-MIX/PERUBAHAN OPERASI

Tombol ini adalah tombol berbagai fungsi. Tergantung

pada pengubahan sebelumnya dari pengguna, tombol ini memiliki fungsi sebagai berikut:

1 memilih mode operasi pemasangan (KIPAS, KERING, OTOMATIS, PENDINGINAN, PEMANAS)

2 bergantian antara suhu minimum dan suhu

maksimum ketika dalam operasi batas

34 TOMBOL BATAS/TITIK PENGATURAN

Tombol ini bergantian antara titik pengaturan, operasi

batas atau (mode pemrograman saja).

35 FAN SPEED BUTTON TOMBOL KECEPATAN KIPAS

Tombol ini matikan antara L (Rendah), H (Tinggi), HH

(Sangat Tinggi), (Otomatis).

36 TOMBOL PENYESUAI ARAH ALIRAN

UDARA Tombol ini memungkinkan untuk

menyesuaikan arah aliran udara.

37 TOMBOL PENGATURAN ULANG IKON WAKTU PEMBERSIHAN

FILTER UDARA

Tombol ini digunakan untuk mengatur ulang ikion waktu

pembersihan filter udara.

SiBE121135_A

149 Diagnosis Servis

Bagian 6

Diagnosis Servis 1. Pemecahan Masalah dengan LED ....................................................... 150

Unit Indoor ................................................................................................ 150 Unit Outdoor .............................................................................................. 152

2. Gejala Masalah dan Tindakan .............................................................. 153 3. Fungsi Pemeriksaan Servis................................................................... 154

Unit Indoor RA ........................................................................................... 154 Unit Indoor SA ........................................................................................... 163

4. Indikasi Kode pada Remote Kontrol ..................................................... 167 Unit Indoor RA ........................................................................................... 167 Unit Indoor SA ........................................................................................... 167 Sub Kode untuk Unit Indoor SA ................................................................. 168 Unit Outdoor .............................................................................................. 169

5. Pemecahan Masalah untuk Unit Indoor RA ......................................... 170 Kelainan PCB Unit Indoor .......................................................................... 170 Kendali Perlindungan Kebekuan atau Kendali pemutusan Puncak Pemanasan172 Kipas Motor atau Kelainan terkait .............................................................. 173 Kelainan Kenaikan Suhu Panel Radiant, Katup Ekspansi Elektronik Indoor (Katup yang Dioperasikan Motor), Kendali Perlindungan Kebekuan (Seri FVXG Saja) ......................................................................................................... 178 Termistor atau Kelainan terkait (Unit Indoor RA)......................................... 180 Kegagalan Membuka/Menutup Bagian Depan (Seri FTXG Saja) ................ 181 Kesalahan transmisi sinyal (Antara Unit Indoor dan Unit Outdoor) ............. 182 Tegangan yang Tidak Menentu (Antara Unit Indoor dan Unit Outdoor) ...... 183

6. Pemecahan Masalah untuk Unit Indoor SA ......................................... 184 Kelainan PCB Unit Indoor .......................................................................... 184 Kelainan Sistem Kendali Tingkat Pengurasan ............................................ 185 Kipas Motor atau Kelainan terkait .............................................................. 187 Motor ayun terkunci (Seri FHQ Saja).......................................................... 193 Kelainan Sistem Pengurasan ..................................................................... 194 Termistor atau Kelainan terkait (Unit Indoor SA) ......................................... 195 Kelainan Termistor Remote Kontrol............................................................ 196 Kesalahan transmisi sinyal (Antara Unit Indoor dan Remote Kontrol) .......... 197 Kesalahan transmisi sinyal (antara Remote Kontrol UTAMA dan SUB Remote Kontrol) ..................................................................................................... 198 Kelainan Pengaturan bidang ...................................................................... 199

7. Pemecahan Masalah untuk Unit Outdoor ............................................ 200 Kekurangan Refrigeran .............................................................................. 200 Deteksi Tegangan Rendah atau Terlalu Tinggi .......................................... 202 Kesalahan transmisi sinyal (pada PCB Unit Outdoor) ................................. 204 Tegangan yang Tidak Menentu (Antara Unit Indoor dan Unit Outdoor) / Fungsi Anti Pembentukan Es (Anti-icing) di Ruangan Lainnya .................... 205 Kendali Anti Pembentukan Es (Anti-icing) untuk Unit Indoor ....................... 206 Kelainan PCB Unit Outdoor ....................................................................... 208

SiBE121135_A Pemecahan Masalah dengan LED

Diagnosis Servis 150

Aktivasi OL (Kompresor kelebihan beban).................................................. 209 Kompresor Terkunci .................................................................................. 211 Kipas DC Terkunci..................................................................................... 212 Deteksi arus input berlebih ........................................................................ 213 Kendali Suhu Pipa Buang .......................................................................... 214 Kendali Tekanan Tinggi dalam Pendinginan ............................................... 215 Kelainan Sistem Sensor Kompresor ........................................................... 216 Kelainan Sensor Posisi .............................................................................. 218 CT atau Kelainan terkait ........................................................................... 220 Termistor atau Kelainan terkait (Unit Outdoor) ............................................ 222 Kenaikan Suhu Panel Listrik ...................................................................... 224 Kenaikan Suhu Fin Radiasi ........................................................................ 226 Deteksi Kelebihan Arus Output .................................................................. 228

8. Pemeriksaan .......................................................................................... 230

Pemeriksaan Tahanan Termistor ............................................................... 230

Pemeriksaan Konektor Motor Kipas ........................................................... 231

Pemeriksaan Hall IC .................................................................................. 232

Pemeriksaan Kumpaan Katup Ekspansi Elektronik Indoor .......................... 232

Pemeriksaan Bentuk Gelombang Catu Daya ............................................. 233

Pemeriksaan Katup Ekspansi Elektronik Outdoor ....................................... 234

Pemeriksaan Kinerja Katup Empat Arah .................................................... 235

Pemeriksaan Sistem Refrigeran Unit Inverter ............................................. 235

Pemeriksaan Penganalisa Inverter ............................................................. 236

Pemeriksaan Dorongan rotasi pada PCB Unit Outdoor .............................. 237

Pemeriksaan Kondisi Pemasangan ............................................................ 238

Pemeriksaan Tekanan Buang ................................................................... 238

Pemeriksaan Sistem Kipas Outdoor ........................................................... 239

Pemeriksaan Tegangan Kapasitor ............................................................. 239

Pemeriksaan Modul Daya .......................................................................... 240

SiBE121135_A

151 Diagnosis Servis

Lampu operasi (hijau)

Lampu operasi (hijau)

1. Pemecahan Masalah dengan LED

1.1 Unit Indoor

Lampu Operasi Lampu operasi akan berkedip jika mendeteksi salah satu kesalahan berikut.

1. Ketika perangkat pelindung unit indoor atau outdoor diaktifkan, atau ketika termistor

mengalami malfungsi.

2. Ketika terjadi kesalahan transmisi sinyal antara unit indoor dan outdoor. Dalam

kasus ini, lakukan prosedur diagnostik yang dijelaskan di halaman selanjutnya.

Tipe Wall Mounted: Seri FTXG Series Tipe Wall Mounted: Seri CTXS, FTXS20/25K

(R17161)

(R12750)

Seri FTXS35/42/50K Tipe Wall Mounted: Seri FTXS-J, ATXS

(Desain panel depan beragam tergantung

pada model.)

(R18419)

Tipe Wall Mounted: Seri FTXS-G

(R12187)

(R16008)

Lampu operasi (hijau)

Lampu operasi

(hijau) Lampu operasi

(multi-warna)

Diagnosis Servis 152

Pemecahan Masalah dengan LED

SiBE121135_A

Tipe Floor Standing: Seri FVXG Tipe Floor Standing: Seri FVXS

(R14646) Lampu operasi (hijau)

(R11687)

Tipe Floor / Ceiling Suspended Dual Tipe Duct Connected

Lampu operasi (hijau) Lampu operasi (hijau)

(R11688)

(Q0340)

BRC1D528 BRC1E52A7, BRC1E52B7

Lampu operasi (merah) Lampu operasi (hijau)

(R12851)

★ Pesan kesalahan atau peringatan juga akan

berkedip pada layar utama. (R17162)

Perhatian: Ketika operasi berhenti tiba-tiba dan lampu operasi berkedip, berarti terjadi "masalah

mode operasi".

Periksa hal-hal berikut;

Apakah mode operasi semuanya sama untuk unit indoor yang terhubung dengan sistem multi

unit outdoor?

Jika tidak, atur semua unit indoor untuk mode operasi yang sama dan pastikan bahwa lampu

operasi tidak berkedip.

Selain itu, bila mode operasi otomatis, atur semua mode operasi unit indoor sebagai

"pendinginan" atau "pemanasan" dan periksa lagi apakah lampu operasi normal.

Jika lampu berhenti berkedip setelah langkah di atas, maka tidak ada malfungsi.

Operasi berhenti dan lampu operasi berkedip hanya untuk unit indoor saat mode operasi

berbeda diatur kemudian. (Mode operasi yang diatur pertama menjadi prioritas.)

Layar Servis Unit indoor memiliki satu LED hijau (LED A) pada PCB kendali. Ketika mikrokomputer

bekerja dengan benar, LED A berkedip.

Lampu operasi (hijau)

153 Diagnosis Servis

SiBE121135_A Pemecahan Masalah dengan LED

Unit Outdoor Unit outdoor memiliki LED hijau (LED A) dan LED merah (LED 1 ~ LED 5) pada PCB. Ketika

mikrokomputer bekerja dengan benar, LED A berkedip, dan ketika sistem dalam kondisi

normal, LED merah OFF.

Bahkan setelah kesalahan dibatalkan dan unit beroperasi dalam kondisi normal, indikasi LED

tetap.

Ilustrasi perwakilan adalah

untuk model 4-ruangan.

PCB Monitor Servis

LED A

LED 1

LED 2

LED 3

LED 4

LED A

LED 1

LED 2

LED 3

LED 4

LED 5

model 3 atau 4-ruangan model 5-ruangan

(R17270)

Diagnosis Servis 154

Gejala Masalah dan Tindakan SiBE121135_A

2. Gejala Masalah dan Tindakan

Gejala Masalah Item Pemeriksaan Rincian Tindakan Halaman Referensi

Unit tidak beroperasi. Periksa catu daya. Periksa apakah terdapat tegangan terpasang yang tepat.

Periksa tipe unit indoor. Periksa apakah tipe unit indoor sesuai dengan unit outdoor.

Periksa suhu outdoor. Operasi pemanasan tidak dapat digunakan saat suhu outdoor 18°CWB atau lebih tinggi. dan operasi pendinginan tidak dapat digunakan saat suhu outdoor di bawah -10 ~ 10°CDB (tergantung model).

Diagnosis dengan indikasi remote kontrol.

— 167

Periksa alamat remote kontrol. Periksa apakah pengaturan alamat untuk remote kontrol dan unit indoor sudah benar.

253

Operasi kadang-kadang berhenti.

Periksa catu daya. Mati listrik 2 sampai 10 siklus akan menghentikan operasi AC. (Operasi lampu OFF)

Periksa suhu outdoor. Operasi pemanasan tidak dapat digunakan saat suhu outdoor 18°CWB atau lebih tinggi. dan operasi pendinginan tidak dapat digunakan saat suhu outdoor di bawah -10 ~ 10°CDB (tergantung model).

Diagnosis dengan indikasi remote kontrol.

— 167

Beberapa unit indoor tidak beroperasi.

Periksa tipe unit indoor. Periksa apakah tipe unit indoor sesuai dengan unit outdoor.

Diagnosis dengan indikasi remote kontrol.

— 167

Operasi pemanasan tidak tersedia.

Periksa pengaturan tipe model remote kontrol.

Pastikan bahwa pengaturan adalah untuk tipe model pompa kalor.

253

Unit beroperasi tapi tidak dingin atau tidak panas.

Periksa kesalahan pengkabelan dan pemipaan dalam sambungan antara unit indoor dan unit outdoor.

Lakukan pemeriksaan kesalahan pengkabelan / perpipaan sebagaimana dijelaskan pada plat nama diagnosis produk.

Periksa kesalahan deteksi termistor. Periksa apakah termistor dipasang dengan aman.

Periksa kesalahan operasi katup ekspansi elektronik outdoor.

Atur unit ke operasi pendinginan dan periksa suhu pipa cairan untuk melihat apakah katup ekspansi elektronik bekerja.

Diagnosis dengan indikasi remote kontrol.

— 167

Diagnosis tekanan port servis dan arus operasi.

Periksa apakah kekurangan Refrigeran 200

Operasi menimbulkan suara berisik dan getaran kencang.

Periksa tegangan output dari modul daya.

— 240

Periksa modul daya. — —

Periksa kondisi pemasangan. Periksa apakah tersedia ruang yang diperlukan untuk pemasangan (disebutkan dalam panduan pemasangan).

155 Diagnosis Servis

SiBE121135_A Fungsi Pemeriksaan Servis

3. Fungsi Pemeriksaan Servis

Unit Indoor RA Remote Kontrol Seri ARC466

Metode Pemeriksaan 1 1. Ketika tombol pembatalan timer ditahan selama 5 detik, layar tampilan suhu

menampilkan 00.

Tombol pembatalan timer

< Seri ARC466 >

(R14220)

2. Tekan tombol pembatalan timer berulang-ulang sampai terdengar suara bip yang panjang.

Kode berikut menunjukkan perubahan secara berurutan di bawah ini.

<ARC466A1, A6, A9>

No. Kode No. Kode No. Kode

1 00 13 C7 25 UA

2 U4 14 A3 26 UH

3 L5 15 H8 27 P4

4 E6 16 H9 28 L3

5 H6 17 C9 29 L4

6 H0 18 C4 30 H7

7 A6 19 C5 31 U2

8 E7 20 J3 32 EA

9 U0 21 J6 33 AH

10 F3 22 E5 34 FA

11 A5 23 A1 35 H1

12 F6 24 E1 36 P9

<ARC466A2>

Catatan: 1. Satu atau dua suara bip pendek berturut-turut menunjukkan kode tidak sesuai. 2. Untuk kembali ke mode normal, tahan tombol timer cancel selama 5 detik. Ketika remote

kontrol dibiarkan selama 60 detik, maka kembali ke mode normal.

3. Tidak semua kode kesalahan ditampilkan. Bila Anda tidak dapat menemukan kode

kesalahan, coba periksa metode 2 ( Lihat hal 155.)

No. Kode No. Kode No. Kode

1 00 14 C7 27 UA

2 U4 15 A3 28 UH

3 L5 16 H8 29 P4

4 E6 17 H9 30 L3

5 H6 18 C9 31 L4

6 H0 19 C4 32 H7

7 A6 20 C5 33 U2

8 E7 21 CE 34 EA

9 U0 22 J3 35 AH

10 F3 23 J6 36 FA

11 A5 24 E5 37 H1

12 F6 25 A1 38 P9

13 A9 26 E1

Diagnosis Servis 156

Fungsi Pemeriksaan Servis

SiBE121135_A

Metode Pemeriksaan 2

1. Tekan bagian tengah Tombol [Temp] dan tombol [Mode] pada saat bersamaan.

(R11669)

5C ditampilkan pada LCD.

(R11821)

2. Pilih 5C (pemeriksaan servis) dengan tombol ▲atau ▼ [Temp].

3. Tekan tombol [Mode] untuk masuk ke mode pemeriksaan servis.

(R11672)

Angka di sisi kiri berkedip.

(R11670)

4. Tekan tombol ▲atau ▼ [Temp] dan ubah nomornya sampai terdengar suara dua bip berurutan

atau bip panjang.

(R11671)

157 Diagnosis Servis

SiBE121135_A Fungsi Pemeriksaan Servis

5. Diagnosis dengan suara.

★bip : Angka di sisi kiri tidak sesuai dengan kode kesalahan.

★dua bip berurutan : Angka di sisi kiri sesuai dengan kode kesalahan,

tapi angka di sisi kanan tidak sesuai.

★bip panjang : Angka di sisi kanan dan kiri sesuai dengan kode kesalahan. Angka

yang ditunjukkan saat Anda mendengar bip panjang adalah kode

kesalahan.

Kode kesalahan dan penjelasan Lihat hal 167.

6. Tekan tombol [Mode].

(R11672)

Angka di sisi kanan berkedip.

(R11673)

7. Tekan tombol ▲atau ▼ [Temp] dan ubah nomornya sampai terdengar suara bip panjang.

8. Diagnosis dengan suara.

(R11671)

★bip : Angka di sisi kiri tidak sesuai dengan kode kesalahan.

★dua bip berurutan : Angka di sisi kiri sesuai dengan kode kesalahan,

tapi angka di sisi kanan tidak sesuai.

★bip panjang : Angka di sisi kanan dan kiri sesuai dengan kode kesalahan.

9. Menentukan kode kesalahan.

Angka yang ditunjukkan saat Anda mendengar bip panjang adalah kode

kesalahan. Kode kesalahan dan penjelasan Lihat hal 167.

10. Tekan tombol [Mode] selama 5 detik untuk keluar dari mode pemeriksaan servis.

(Ketika remote kontrol dibiarkan selama 60 detik, maka kembali ke mode normal juga.)

(R11672)

Diagnosis Servis 158

Fungsi Pemeriksaan Servis

SiBE121135_A

Remote Kontrol Seri ARC452

Metode Pemeriksaan 1 1. Ketika tombol pembatalan timer ditahan selama 5 detik, layar tampilan suhu

menampilkan 00.

Tombol pembatalan timer

< Seri ARC452 >

(R14554)

2. Tekan tombol pembatalan timer berulang-ulang sampai terdengar suara bip yang panjang.

Kode berikut menunjukkan perubahan secara berurutan di bawah ini.

<ARC452A1, A3>

No. Kode No. Kode No. Kode

1 00 13 C7 25 UA

2 U4 14 A3 26 UH

3 L5 15 H8 27 P4

4 E6 16 H9 28 L3

5 H6 17 C9 29 L4

6 H0 18 C4 30 H7

7 A6 19 C5 31 U2

8 E7 20 J3 32 EA

9 U0 21 J6 33 AH

10 F3 22 E5 34 FA

11 A5 23 A1 12 F6 24 E1

Catatan: 1. Satu atau dua suara bip pendek berturut-turut menunjukkan kode tidak sesuai.

2. Untuk kembali ke mode normal, tahan tombol timer cancel selama 5 detik. Ketika remote

kontrol dibiarkan selama 60 detik, maka kembali ke mode normal.

3. Tidak semua kode kesalahan ditampilkan. Bila Anda tidak dapat menemukan kode

kesalahan, coba periksa metode 2 ( Lihat hal 158.)

159 Diagnosis Servis

SiBE121135_A Fungsi Pemeriksaan Servis

Metode Pemeriksaan 2

1. Tekan 3 tombol ([TEMP] ▲, [TEMP] ▲, [MODE]) pada saat bersamaan untuk masuk

ke mode diagnosis.

Angka di sisi kiri berkedip.

(R8381)

(R8382)

2. Tekan tombol ▲atau ▼ [Temp] dan ubah nomornya sampai terdengar suara dua bip

berurutan atau bip panjang.

3. Diagnosis dengan suara.

(R8383)

★bip : Angka di sisi kiri tidak sesuai dengan kode kesalahan.

★dua bip berurutan : Angka di sisi kiri sesuai dengan kode kesalahan,

tapi angka di sisi kanan tidak sesuai.

★bip panjang : Angka di sisi kanan dan kiri sesuai dengan kode kesalahan. Angka yang ditunjukkan saat Anda mendengar bip panjang adalah kode kesalahan.

Kode kesalahan dan penjelasan Lihat hal 167.

4. Tekan tombol [MODE].

Angka di sisi kanan berkedip.

(R8384)

(R8385)

Diagnosis Servis 160

Fungsi Pemeriksaan Servis

SiBE121135_A

5. Tekan tombol ▲atau ▼ [Temp] dan ubah nomornya sampai terdengar suara bip panjang.

(R8383)

6. Diagnosis dengan suara.

★bip : Angka di sisi kiri tidak sesuai dengan kode kesalahan.

★dua bip berurutan : Angka di sisi kiri sesuai dengan kode kesalahan,

tapi angka di sisi kanan tidak sesuai.

★bip panjang : Angka di sisi kanan dan kiri sesuai dengan kode kesalahan.

7. Menentukan kode kesalahan.

Angka yang ditunjukkan saat Anda mendengar bip panjang adalah kode

kesalahan. Kode kesalahan dan penjelasan Lihat hal 167.

8. Tekan tombol [MODE] untuk keluar dari mode diagnosis.

(R8384)

Tampilam 7 berarti mode operasi Uji coba.

Lihat hal 246 operasi Uji coba.

(R9659)

9. Tekan tombol [ON/OFF] dua kali untuk kembali ke mode normal.

(R9660)

Catatan: Ketika remote kontrol dibiarkan selama 60 detik, maka kembali ke mode normal.

Fungsi Pemeriksaan Servis

SiBE121135_A

Diagnosis Servis 160

Remote Kontrol Seri ARC433

Metode Pemeriksaan 1 1. Ketika tombol pembatalan timer ditahan selama 5 detik, layar tampilan suhu

menampilkan 00.

Tombol pembatalan timer

< Seri ARC433 > (R14555)

2. Tekan tombol pembatalan timer berulang-ulang sampai terdengar suara bip yang panjang.

Kode berikut menunjukkan perubahan secara berurutan di bawah ini.

<ARC433B67, B69>

No. Kode No. Kode No. Kode

1 00 12 C7 23 H0

2 U4 13 H8 24 E1

3 F3 14 J3 25 P4

4 E6 15 A3 26 L3

5 L5 16 A1 27 L4

6 A6 17 C4 28 H6

7 E5 18 C5 29 H7

8 F6 19 H9 30 U2

9 C9 20 J6 31 UH

10 U0 21 UA 32 EA

11 E7 22 A5 33 AH

<ARC433A85>

No. Kode No. Kode No. Kode

1 00 12 F6 23 A1

2 U4 13 C7 24 E1

3 L5 14 A3 25 UA

4 E6 15 H8 26 UH

5 H6 16 H9 27 P4

6 H0 17 C9 28 L3

7 A6 18 C4 29 L4

8 E7 19 C5 30 H7

9 U0 20 J3 31 U2

10 F3 21 J6 32 EA

11 A5 22 E5 33 AH

Catatan: 1. Satu atau dua suara bip pendek berturut-turut menunjukkan kode tidak sesuai. 2. Untuk kembali ke mode normal, tahan tombol timer cancel selama 5 detik. Ketika remote

kontrol dibiarkan selama 60 detik, maka kembali ke mode normal.

3. Tidak semua kode kesalahan ditampilkan. Bila Anda tidak dapat menemukan kode

kesalahan, coba periksa metode 2 ( Lihat hal 161.)

SiBE121135_A Fungsi Pemeriksaan Servis

161 Diagnosis Servis

Metode Pemeriksaan 2

1. Tekan bagian tengah Tombol [Temp] dan tombol [Mode] pada saat bersamaan untuk

masuk ke mode diagnosis

Angka di sisi kiri berkedip.

(R4272)

(R14967)

2. Tekan tombol ▲atau ▼ [Temp] dan ubah nomornya sampai terdengar suara dua bip

berurutan atau bip panjang.

3. Diagnosis dengan suara.

(R4274)

★bip : Angka di sisi kiri tidak sesuai dengan kode kesalahan.

★dua bip berurutan : Angka di sisi kiri sesuai dengan kode kesalahan,

tapi angka di sisi kanan tidak sesuai.

★bip panjang : Angka di sisi kanan dan kiri sesuai dengan kode kesalahan. Angka yang

ditunjukkan saat Anda mendengar bip panjang adalah kode kesalahan.

Kode kesalahan dan penjelasan Lihat hal 167.

4. Tekan tombol [MODE].

Angka di sisi kanan berkedip.

(R4275)

(R14968)

Fungsi Pemeriksaan Servis

SiBE121135_A

Diagnosis Servis 162

5. Tekan tombol ▲atau ▼ [Temp] dan ubah nomornya sampai terdengar suara bip panjang.

6. Diagnosis dengan

suara.

(R4277)

★bip : Angka di sisi kiri tidak sesuai dengan kode kesalahan.

★dua bip berurutan : Angka di sisi kiri sesuai dengan kode kesalahan,

tapi angka di sisi kanan tidak sesuai.

★bip panjang : Angka di sisi kanan dan kiri sesuai dengan kode kesalahan.

7. Menentukan kode kesalahan.

Angka yang ditunjukkan saat Anda mendengar bip panjang adalah kode

kesalahan. Kode kesalahan dan penjelasan Lihat hal 167.

8. Tekan tombol [MODE] untuk keluar dari mode diagnosis.

(R4278)

Tampilam 7 berarti mode operasi Uji coba.

Lihat hal 246 operasi Uji coba.

(R14969)

9. Tekan tombol [ON/OFF] dua kali untuk kembali ke mode normal.

(R9670)

Catatan: Ketika remote kontrol dibiarkan selama 60 detik, maka kembali ke mode normal.

SiBE121135_A Fungsi Pemeriksaan Servis

163 Diagnosis Servis

Unit Indoor SA Hubungan antara Mode

BRC1D528 Mode berikut dapat dipilih dengan menggunakan tombol [Inspection/Test] pada remote kontrol.

Pengaturan unit indoor dapat dibuat.

• Waktu tanda pembersihan filter

Tekan tombol [INSPECTION/TEST

OPERATION] selama lebih

dari 4 detik.

Data servis dapat diperoleh.

• Riwayat kode kesalahan

• Lainnya

Mode

Penga

turan

bidan

g

Mode

servis

• Data suhu berbagai bagian

Pengaturan servis dapat dibuat.

• ON kipas paksa

• Pengaturan laju aliran udara

Tekan tombol [INSPECTION/TEST

OPERATION] selama lebih

dari 4 detik.

Tekan tombol [INSPECTION/TEST

OPERATION] sekali.

Mode

norma

l

Tekan tombol [INSPECTION/TEST OPERATION] sekali.

Tekan tombol [INSPECTION/TEST OPERATION] sekali

atau biarkan remote kontrol tanpa menyentuhnya selama 30 menit.

Kode berikut dapat diperiksa.

Setelah 10 detik Mode

• Kode kesalahan

• Kode Model Indoor

Mode

Pemeriksaa

n

operasi

uji

Termostat dapat dihidupkan secara paksa.

Tekan tombol [INSPECTION/TEST OPERATION] sekali. (R15367)

Fungsi Pemeriksaan Servis

SiBE121135_A

Diagnosis Servis 164

<Layar utama> • Perubahan mode operasi

• Kendalian kecepatan kipas

• Tampilan menu

• Konfirmasi setiap pengaturan

• On • Off

• Batal

• Lampu operasi

• Perubahan bahasa

Tekan

Tekan tombol sekali. tombol

sekali.

Tekan

tombol selama 4 detik atau

lebih. Layar utama Tekan tombol sekali.

Tekan tombol sekali. Teka

n tombol selama 4 detik atau

lebih.

BRC1E52A7, BRC1E52B7

Layar Menu Utama

<Menu Utama> • Mengatur perubahan mode suhu

• Arah aliran udara

• On/Off Panas/Dingin Cepat • Ventilasi

• Pengaturan timer

• Kontak Servis/ Info Model

• Fungsi nyaman • Daftar status pengaturan

• Pengaturan Jam

Layar Pengaturan bidang Layar menu servis

<Menu Pengaturan bidang>

• ON/OFF operasi uji

• Kontrak Servis Pendaftaran

• Daftar Pengaturan bidang • Pengaturan No. Group

• Pengaturan No. AIRNET unit indoor

• Pengaturan No. AIRNET unit outdoor

• Rekaman kesalahan • Tampilan status indoor

• Tampilan status outdoor

• ON operasi paksa kipas

• Perubahan Sub/Main (Utama)

• OFF tanda elemen filter

<Menu Servis> • Tampilan nama model

• Tampilan jam operasi

• Tampilan status indoor • Tampilan status outdoor

• Pencairan paksa

• Pemilihan tampilan kesalahan

• Pemindahan No. unit • Tampilan data sensor/alamat

(R12855)

SiBE121135_A Fungsi Pemeriksaan Servis

165 Diagnosis Servis

BRC1D528 Jika operasi berhenti karena malfungsi, lampu operasi pada remote kontrol berkedip, dan

ditampilkan kode kesalahan. (Bahkan jika operasi berhenti terjadi, isi malfungsi ditampilkan

saat mode pemeriksaan dimasukkan.) Kode kesalahan memungkinkan Anda untuk

menjelaskan malfungsi apa yang menyebabkan operasi berhenti.

Lihat hal 167 untuk kode kesalahan dan isi malfungsi.

Lampu operasi

Tombol [ON/OFF]

Tampialn unit indoor

tempat malfungsi

terdeteksi

Tampilan pemeriksaan

Kode kesalahan

Tombol [INSPECTION/

TEST OPERATION]

(R14423)

Catatan: 1. Saat Anda menekan tombol [INSPECTION/TEST OPERATION], tampilan pemeriksaan berkedip.

2. Ketika dalam mode pemeriksaan, tekan tombol [ON/OFF] selama 5 detik atau lebih untuk

menghapus indikasi riwayat kesalahan. Dalam hal ini, kode kesalahan berkedip dua kali

dan kemudian berubah menjadi 00 (= Normal), No. UNIT berubah menjadi 0, dan mode

operasi secara otomatis beralih dari mode pemeriksaan ke mode normal (menampilkan

suhu yang diatur).

Fungsi Pemeriksaan Servis

SiBE121135_A

Diagnosis Servis 166

BRC1E52A7, BRC1E52B7 Tampilan berikut muncul di layar saat kesalahan (atau peringatan) terjadi selama operasi.

Periksa kode kesalahan dan lakukan tindakan perbaikan khusus untuk model tertentu.

Layar

Lampu operasi

Tombol [Menu/Masuk]

(R17163)

(1) Periksa apakah termasuk kesalahan/peringatan.

Status operasi Tampilan

Mati tidak normal

Sistem menghentikan operasi.

Lampu operas (hijau) mulai berkedip. Pesan "Kesalahan: Tekan Tombol Menu" yang mucul dan berkedip di bagian bawah layar.

(R12858)

Peringatan

Sistem terus beroperasi.

Lampu Operasi (hijau) tetap menyala. Pesan "Peringatan: Tekan Tombol Menu" yang mucul dan berkedip di bagian bawah layar.

(R12857)

(2) Melakukan tindakan perbaikan.

· Tekan tombol [Menu/Enter] untuk memeriksa kode kesalahan.

· Lakukan tindakan perbaikan sesuai dengan model.

Kode kesalahan

Nama model

yang berlaku

(R12859)

167 Diagnosis Servis

SiBE121135_A Indikasi Kode pada Remote Kontrol

4. Indikasi Kode pada Remote Kontrol

Unit Indoor RA

Kode Kesalahan

Deskripsi Halaman Referensi 00 Kondisi normal —

A1 Kelainan PCB Unit Indoor 170

A5 Kendali perlindungan kebekuan atau kendali pemutusan puncak pemanasan

172

A6 kipas motor atau Kelainan terkait

Motor DC (wall, floor standing) 173

Motor AC (floor / ceiling, duct) 176

A9 Kenaikan suhu panel radiant, katup ekspansi elektronik indoor (katup yang dioperasikan motor), kendali perlindungan kebekuan (Seri FVXG Saja)

178

C4 Termistor penukar panas indoor atau kelainan terkait 180

C7 Kegagalan membuka/menutup panel depan (Seri FTXG Saja) 181

C9 Termistor suhu ruangan atau kelainan terkait 180

CE Termistor panel radiant atau kelainan terkait (Seri FVXG saja) 180

U4 Kesalahan transmisi sinyal (antara unit indoor dan unit outdoor) 182

UA Tegangan yang tidak menentu (antara unit indoor dan unit outdoor)

183

Unit Indoor SA

Kode Kesalahan

Deskripsi Halaman Referensi 00 Kondisi normal —

A1 Kelainan PCB Unit Indoor 184

A3 Kelainan sistem kendali tingkat pengurasan 185

A6

Motor kipas atau kelainan terkait (Lihat Catatan di bawah.)

Motor AC (FFQ, FHQ, FDBQ) 187

Motor DC (FCQG, FBQ35/50C8VEB) 189

Motor DC (FBQ60C8VEB) 191

A7 Motor ayun terkunci (Seri FHQ Saja) 193

AF Kelainan sistem pengurasan 194

C4 Termistor penukar panas indoor 1 atau kelainan terkait 195

C5 Termistor penukar panas indoor 2 atau kelainan terkait 195

C9 Termistor suhu ruangan atau kelainan terkait 195

CJ Kelainan termistor remote kontrol 196

U5 Kesalahan transmisi sinyal (antara unit indoor dan remote kontrol)

197

U8 Kesalahan transmisi sinyal (antara remote kontrol UTAMA dan remote kontrol SUB)

198

UA Kelainan Pengaturan bidang 199

: Kode kesalahan muncul otomatis dan sistem

berhenti. Periksa dan selesaikan kesalahan.

: Jika kode kesalahan berarsir, "pemeriksaan" tidak ditampilkan. Sistem beroperasi,

tetapi pastikan untuk memeriksa dan menyelesaikan kesalahan.

Catatan: Ketika ada kemungkinan catu daya fase terbuka, periksa juga catu daya.

Diagnosis Servis 168

Indikasi Kode pada Remote Kontrol SiBE121135_A

Sub Kode untuk Unit Indoor SA Jika kode kesalahan seperti yang ditunjukkan di bawah ini ditampilkan saat remote kontrol

navigasi (BRC1E52A7, BRC1E52B7) sedang digunakan, lakukan diagnosis terperinci atau

diagnosis unit yang relevan yang mengacu pada daftar terlampir.

Kode

kesalahan Deskripsi Pemecahan masalah

A6 - 01

A6 - 10

A6 - 11

Motor kipas terkunci Arus motor kipas terkunci telah terdeteksi. Putar kipas dengan tangan untuk memeriksa sambungan konektor.

Kesalahan arus berlebih kipas Arus berlebih Motor kipas telah terdeteksi. Periksa sambungan konektor antara motor kipas dan PCB. Jika sambungan normal, ganti motor kipas. Jika tetap saja hal ini tidak dapat mengatasi kesalahan, ganti PCB.

Kesalahan deteksi posisi kipas Kesalahan dalam mendeteksi posisi motor kipas. Periksa sambungan konektor antara motor kipas dan PCB. Jika sambungan normal, ganti motor kipas. Jika tetap saja hal ini tidak dapat mengatasi kesalahan, ganti PCB.

AH - 03 Kesalahan transmisi (antara Pemeriksaan sendiri sambungan panel

dekorasi pembersihan harness dan konektor indoor antara PCB panel dan

unit) PCB unit indoor.

[Ketika panel dekorasi pembersihan sendiri

dipasang]

AH - 04 Kesalahan sensor deteksi debu [Ketika panel dekorasi pembersihan sendiri dipasang]

Periksa koneksi dari konektor X12A pada PCB panel dan konektor X18A dan X19A pada PCB sensor.

AH - 05 Kesalahan tanda pengumpulan debu [Ketika panel dekorasi pembersihan sendiri dipasang]

Periksa penyumbatan akibat debu pada port pengumpulan debu serta di unit sikat, pipa berbentuk S, dan kotak debu. Selanjutnya, periksa setiap noda dari penerima cahaya dan bagian pancaran dari unit inframerah.

AH - 06 Kesalahan putaran filter udara [Ketika panel dekorasi pembersihan sendiri dipasang]

Periksa apa pun yang didapat di jalur putar filter (misalnya filter terlepas atau gigi dorong tersumbat oleh benda asing).

AH - 07 Kesalahan putaran damper [Ketika panel dekorasi pembersihan sendiri dipasang]

Damper tidak berputar secara normal. Periksa setiap benda asing di sekitar damper dan untuk operasi gigi dan saklar batas.

AH - 08 Kesalahan operasi pembersihan filter Unit masih belum menyelesaikan operasi [Ketika panel dekorasi pembersihan

sendiri pembersihan sendiri filter bahkan

dipasang] setelah jeda waktu tertentu. Periksa

semua kebisingan luar, dll.

AH - 09 Kesalahan penonaktifan awal operasi pembersihan filter [Ketika panel dekorasi pembersihan sendiri dipasang]

Unit telah dimasukkan ke keadaan di mana operasi filter pembersihan sendiri dinonaktifkan. Periksa unit untuk kondisi operasi.

C6 - 01 kombinasi kegagalan PCB unit indoor dan PCB kipas

kombinasi PCB unit indoor dan PCB kipas bersifat merusak. Periksa apakah adaptor pengaturan kapasitas dan tipe PCB telah benar.

169 Diagnosis Servis

SiBE121135_A Indikasi Kode pada Remote Kontrol

Unit Outdoor i: ON, h: OFF, j: Berkedip

Hijau : Berkedip saat kondisi

normal Merah : OFF saat kondisi

normal

Indikasi LED Unit Outdoor Kode Kesalahan

Deskripsi Halaman Referensi

Hijau Merah

A 1 2 3 4 5 ★

j h h h h h 00 Kondisi normal —

UA Tegangan yang tidak menentu (antara unit indoor dan unit outdoor)

205

UH Fungsi anti pembentukan es (Anti-icing) di ruangan lainnya

205

j h h i i h (U0) Kekurangan refrigeran 200

j i h h i h U2 Deteksi tegangan rendah atau terlalu tinggi 202

j h i i i h U7 Kesalahan transmisi sinyal (pada PCB unit outdoor) 204

j i h i i h A5 Kendali anti pembentukan es (Anti-icing) untuk Unit

Indoor 206

j i i i h h E1 Kelainan PCB unit outdoor 208

j i h i h h (E5) Aktivasi OL (Kompresor kelebihan beban) 209

j h i i h h (E6) Kompresor terkunci 211

j i i i i h E7 Kipas DC terkunci 212

j h i h i h E8 Deteksi arus input berlebih 213

j i h i h h F3 Kendali suhu pipa buang 214

j i h i i h F6 Kendali tekanan tinggi dalam pendinginan 215

j i i h h h H0 Kelainan sistem sensor kompresor 216

H6 Kelainan sensor posisi 218

H8 CT atau kelainan terkait 220

H9 Termistor suhu Outdoor atau kelainan terkait 222

J3 Termistor pipa buang atau kelainan terkait 222

J6 Termistor penukar panas outdoor atau kelainan terkait

222

J8 Termistor pipa cair atau kelainan terkait 222

J9 Termistor pipa gas atau kelainan terkait 222

P4 Termistor sirip (fin) radiasi atau kelainan terkait 222

j i i h i h L3 Kenaikan suhu panel listrik 224

j h h h i h L4 Kenaikan suhu sirip (fin) radiasi 226

j h h i h h L5 Deteksi kelebihan arus output 228

Catatan: 1. Kode kesalahan dalam tanda kurun () akan ditampilkan hanya ketika sistem dimatikan.

2. Ketika terjadi kesalahan sensor, periksa tampilan remote kontrol untuk menentukan

apakah sensor rusak.

Jika remote kontrol tidak menunjukkan kode kesalahan, lakukan prosedur berikut.

Matikan saklar daya dan nyalakan kembali lagi. Jika indikasi LED yang sama muncul

lagi segera setelah daya dihidupkan, kesalahan ada pada termistor.

Jika kondisi di atas tidak terjadi, kesalahan ada pada CT.

3. Kode kesalahan unit indoor mungkin lebih condong pada tampilan remote kontrol.

4. ★ model 3-ruangan dan model 4-ruangan tidak memiliki LED5.

SiBE121135_A Pemecahan Masalah untuk Unit Indoor RA

Diagnosis Servis 170

5. Pemecahan Masalah untuk Unit Indoor RA

Kelainan PCB Unit Indoor

Kode kesalahan A1

Metode Deteksi

Kesalahan

Sistem memeriksa apakah sirkuit bekerja dengan benar di dalam mikrokomputer unit indoor.

Kondisi

Keputusan

Kesalahan

Sistem tidak dapat menetapkan pengaturan internal.

Dugaan

penyebab

Model yang saling tersambung salah

PCB Unit indoor rusak.

Konektor terputus

Penurunan tegangan catu daya.

Pemecahan Masalah untuk Unit Indoor RA

SiBE121135_A

171 Diagnosis Servis

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Sesuaikan dengan model yang cocok.

Perbaiki catu daya.

Ganti PCB unit indoor.

Selesai

Perbaiki catu daya.

Ganti PCB unit indoor.

Selesai

Catatan: Periksa konektor berikut.

Selesai

(R15310)

Tipe Model Konektor

Tipe wall mounted Papan terminal ~ Kendali PCB (H1, H2, H3)

Tipe floor standing Papan terminal ~ Kendali PCB (H1, H2, H3)

Tipe floor / ceiling suspended dual S36 ~ S37

Tipe duct connected Papan terminal ~ Kendali PCB (H1, H2, H3)

Perbaiki sambungan.

Periksa kombinasi unit indoor dan outdoor.

OK? TIDAK

YA

Periksa sambungan konektor (Lihat Catatan).

Untuk mengamankan sambungan, lepas konektor kemudian pasang lagi.

OK? YA Periksa tegangan catu

daya.

TIDAK Tegangan

sesuai?

TIDAK

YA

Mulai operasi

Kesalahan berulang?

YA

TIDAK

Kesalahan berulang?

YA Periksa tegangan catu daya.

TIDAK Tegangan

sesuai?

TIDAK

YA

Mulai operasi

Kesalahan berulang?

YA

TIDAK

SiBE121135_A Pemecahan Masalah untuk Unit Indoor RA

Diagnosis Servis 172

Pastikan untuk mematikan saklar listrik sebelum menyambung atau

memutuskan

Perhatian sambungan, atau kerusakan komponen dapat terjadi.

Periksa saluran udara.

YA Apakah ada Korsleting? Sediakan saluran udara yang

cukup.

TIDAK

Periksa filter udara.

Kotor? YA Bersihkan filter udara

TIDAK

Periksa penumpukan debu pada penukar panas indoor.

YA

Kotor? Bersihkan penukar panas indoor.

TIDAK

Periksa No. 06 Periksa termistor penukar panas indoor.

Apakah

sesuai dengan TIDAK bagan karakteristik Ganti termistor.

termistor?

YA

Ganti PCB unit indoor.

(R7131)

Kendali Perlindungan Kebekuan atau Kendali

Pemutusan Puncak Pemanasan

Kode kesalahan A5

Metode Deteksi

Kesalahan

Kendali perlindungan kebekuan

Selama operasi pendinginan, kendali perlindungan kebekuan (penghentian operasi)

diaktifkan sesuai dengan suhu yang dideteksi oleh penukar panas termistor indoor.

Kendali pemutusan puncak pemanasan.

Selama operasi pemanasan, suhu penukar panas indoor digunakan untuk kendali

pemutusan puncak pemanasan (penghentian operasi, penghentian kipas outdoor, dll)

Kondisi

Keputusan

Kesalahan

Kendali perlindungan kebekuan

Selama operasi pendinginan, suhu penukar panas indoor di bawah 0°C.

Kendali pemutusan puncak pemanasan.

Selama operasi pemanasan, suhu penukar panas indoor di atas 65°C.

Dugaan

penyebab

Udara hubungan pendek (korsleting)

Filter udara unit indoor tersumbat

Penumpukan debu pada penukar panas indoor

Termistor penukar panas indoor rusak

PCB Unit indoor rusak

Pemecahan masalah

Periksa

No.01 Lihat

Hal.230

Perhatian Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskansambungan, atau kerusakan komponen dapat terjadi.

Periksa saluran udara.

Apakah ada Korsleting? YA

Sediakan saluran udara yang cukup.

TIDAK

Periksa filter udara.

Kotor?

YA Bersihkan filter udara.

TIDAK

Periksa penumpukan debu pada penukar panas indoor.

Kotor?

YA Bersihkan penukar panas indoor.

TIDAK

Periksa No. 01 Periksa termistor penukar panas indoor.

Apakah sesuai dengan bagan karakterikstik

termistror?

TIDAK Ganti termistror.

YA Ganti PCB unit indoor.

(R15715)

Pemecahan Masalah untuk Unit Indoor RA

SiBE121135_A

173 Diagnosis Servis

Kipas motor atau kelainan terkait Motor DC (Tipe Wall Mounted, Tipe Floor Standing)

Kode kesalahan A6

Metode Deteksi

Kesalahan

Kecepatan putar yang terdeteksi oleh Hall IC selama operasi motor kipas digunakan untuk

menentukan kelainan operasi motor kipas.

Kondisi

Keputusan

Kesalahan

Kecepatan putar yang terdeteksi tidak mencapai kecepatan putar yang diminta dari tap target,

dan kurang dari 50% dari kecepatan maksimal motor kipas.

Dugaan

penyebab

Penurunan signifikan tegangan catu daya.

Korsleting (short) dalam lilitan motor kipas

Kabel di dalam motor kipas putus

Kabel timah motor kipas rusak

Kapasitor motor kipas rusak

PCB Unit indoor rusak

SiBE121135_A Pemecahan Masalah untuk Unit Indoor RA

Diagnosis Servis 174

Hentikan motor kipas.

Periksa No.02 Periksa output konektor motor kipas

Pemecahan masalah Seri FTXG, FTXS35/42/50K, FTXS-J, FTXS-G, ATXS, FVXG, FVXS

Periksa No.02

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Lihat hal.231, Periksa tegangan catu daya.

Apakah

fluktuasi tegangan TIDAK dalam ±10% dari

nilai terpasang?

Perbaiki catu daya.

YA

matikan catu daya dan putar kipas dengan tangan.

Apakah kipas

berputar lancar?

YA Nyalakan daya dan mulai operasi.

Apakah TIDAK kipas

berputar?

YA

TIDAK

Matikan catu daya dan lepas konektor motor kipas, kemudian nyalakan daya.

Periksa No.02 Periksa output konektor motor kipas

Ganti motor kipas indoor.

Catatan: Motor bisa rusak jika konektor motor dilepas saat catu daya nyala. (Pastikan mematikan catu daya sebelum menyambungkan kembali ke konektor.)

Apakah tegangan catu daya motor TIDAK

310 ~ 340 VDC dihasilkan?

Ganti PCB unit indoor.

YA

Apakah tegangan

TIDAK kendali motor 15 VDC

dihasilkan?

Ganti PCB unit indoor.

YA

Apakah

YA tegangan perintah

putar 1 ~ 5 VDC dihasilkan?

TIDAK Apak

ah

Ganti motor kipas indoor.

Apakah pulsa putar

TIDAK dihasilkan?

YA

pulsa putar dihasilkan?

YA

TIDAK Ganti motor kipas indoor dan PCB unit indoor. Ganti PCB unit indoor.

Ganti motor kipas indoor.

Ganti PCB unit indoor.

(R18469)

Pemecahan Masalah untuk Unit Indoor RA

SiBE121135_A

175 Diagnosis Servis

Periksa No. 03 Periksa kerusakan atau korsleting motor kipas.

Pemecahan masalah Seri CTXS, FTXS20/25K

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

Periksa No.03

Perhatian

sambungan, atau kerusakan komponen dapat terjadi.

Catatan: Motor bisa rusak jika konektor

Lihat hal.231, Matikan catu daya. (Cabut kabel daya atau matikan pemutus.)

Periksa konektor sambungan.

motor dilepas saat catu daya nyala. (Pastikan mematikan catu daya sebelum menyambungkan kembali ke konektor.)

Untuk mengamankan

sambungan, lepas konektor kemudian pasang lagi.

OK? TIDAK

Perbaiki sambungan.

YA

YA Benda asing di dalam

atau sekitar kipas?

TIDAK

Buang benda asing.

Putar kipas dengan tangan.

TIDAK Kipas berputar lancar?

YA

Kelainan TIDAK

suara terjadi?

YA

Bantalan karet

Tahanan OK?

Apakah bantalan karet terpasang dengan tepat?

TIDAK

TIDAK

Bantalan karet

poros

YES Ganti bantalan karet poros.

Perbaiki posisi bantalan

karet atau ganti bantalan

karet.

Ganti motor kipas indoor.

YA

Nyalakan kembali daya.

Periksa No. 03 Periksa tegangan kendai motor.

Apakah tegangan

motor 15 VDC dihasilkan?

YA

TIDAK Ganti PCB unit indoor (1).

Periksa No. 03 Periksa PCB unit indoor untuk pulsa putar.

Apakah pulsa putar TID AK dihasilkan?

YA

Ganti motor kipas indoor.

Ganti PCB unit indoor (1).

(R18153)

SiBE121135_A Pemecahan Masalah untuk Unit Indoor RA

Diagnosis Servis 176

Motor AC (Tipe Floor / Ceiling Suspended Dual, Tipe Duct Connected)

Kode Kesalahan A6

Metode Deteksi

Kesalahan

Kecepatan putar yang terdeteksi oleh Hall IC selama operasi motor kipas digunakan untuk

menentukan kelainan operasi motor kipas.

Kondisi

Keputusan

Kesalahan

Kecepatan putar yang terdeteksi tidak mencapai kecepatan putar yang diminta dari tap target,

dan kurang dari 50% dari kecepatan maksimal motor kipas.

Dugaan

penyebab

Penurunan signifikan tegangan catu daya.

Korsleting (short) dalam lilitan motor kipas

Kabel di dalam motor kipas putus

Kabel timah motor kipas rusak

Kapasitor motor kipas rusak

PCB Unit indoor rusak

Pemecahan Masalah untuk Unit Indoor RA

SiBE121135_A

177 Diagnosis Servis

Periksa No. 04 Periksa Hall IC

Matikan catu daya dan putar kipas dengan tangan.

Periksa tegangan motor kipas.

Nyalakan daya dan periksa tegangan motor kipas. (segera setelah penyalaan kembali)

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Periksa

No.04 Lihat

Hal.232

Periksa tegangan catu daya.

Apakah

fluktuasi tegangan TIDAK dalam ±10% dari

nilai terpasang?

Perbaiki catu daya.

YA

Mulai operasi

Apakah kipas berputar?

YA

TIDAK

Apakah ada output?

TIDAK YA

TIDAK Ganti motor kipas dan PCB unit indoor.

Apakah kipas berputar Ganti motor kipas. lancar?

YA

Tegangan sesuai?TIDAK

Ganti PCB unit indoor.

Tegangan sesuai?

YA

Mengukur tegangan antara kabel timah merah dan

hitam dari motor kipas, dan periksa apakah tegangan maksimum mencapai tegangan

TIDAK yang sesuai.

Ganti motor kipas.

Ganti PCB unit indoor.

YA

Periksa kelancaran kapasitor.

Apakah lancar? YA

Ganti PCB unit indoor.

TIDAK

Ganti motor kipas.

(R19123)

SiBE121135_A Pemecahan Masalah untuk Unit Indoor RA

Diagnosis Servis 178

Kenaikan Suhu Panel Radiant, Katup Ekspansi Elektronik

Indoor (Katup yang Dioperasikan Motor), Kendali Perlindungan Kebekuan (Seri FVXG Saja)

Kode kesalahan A9

Metode Deteksi

Kesalahan

Kenaikan suhu panel radiant

Selama operasi RADIANT, kendali suhu tinggi (misalnya, penghentian operasi, penutupan

katup ekspansi elektronik indoor) diaktifkan sesuai dengan suhu terdeteksi oleh termistor panel

radiant.

Kelainan katup ekspansi elektronik indoor

Katup ekspansi elektronik indoor diperlukan untuk menutup sepenuhnya selama operasi

pendinginan, kering atau pemanasan. Ketika katup ekspansi elektronik indoor terbuka

karena malfungsi, refrigeran mengalir ke panel radiant dan suhu panel radiant naik atau

turun.

Katup ekspansi elektronik indoor diperlukan untuk membuka selama operasi RADIANT.

Ketika katup ekspansi elektronik indoor tertutup karena malfungsi, refrigeran tidak

mengalir ke panel radiant dan suhu panel radiant tidak naik.

Untuk multi sistem

Katup ekspansi elektronik indoor harus ditutup sepenuhnya di ruangan apabila sistem tidak

berjalan. Ketika katup ekspansi elektronik indoor terbuka karena malfungsi dan operasi

RADIANT atau pemanasan dilakukan di ruangan lainnya, refrigeran mengalir ke panel

radiant dan suhu panel radiant naik.

Kendali perlindungan kebekuan

Suhu yang dideteksi oleh termistor panel radiant digunakan untuk mencegah pembekuan unit

indoor selama operasi pendinginan.

Kondisi

Keputusan

Kesalahan

Kenaikan suhu panel radiant

Suhu permukaan panel radiant dihitung oleh termistor panel radiant di atas 70°C.

Kelainan katup ekspansi elektronik indoor

Selama operasi pendinginan atau kering, suhu yang dideteksi oleh termistor panel

radiant ( 4) telah menurun.

Selama operasi pemanasan, suhu yang dideteksi oleh termistor panel radiant ( 4) telah

meningkat.

Selama operasi RADIANT, suhu yang dideteksi oleh termistor panel radiant ( 4) tidak

meningkat.

Untuk multi sistem

Saat sistem tidak berjalan dan operasi pemanasan atau RADIANT dilakukan di ruangan

lainnya, suhu yang dideteksi oleh termistor panel radiant ( 4) telah meningkat.

Kendali perlindungan kebekuan

Selama operasi pendinginan, operasi berhenti ketika suhu yang dideteksi oleh termistor panel

radiant ( 4) telah menurun.

Dugaan

penyebab

Filter udara unit indoor tersumbat

Penumpukan debu pada penukar panas indoor

Udara hubungan pendek (korsleting)

Termistor panel radiant rusak

Termistor penukar panas indoor rusak

Termistor suhu ruangan rusak

Katup (atau kumparan) ekspansi elektronik indoor rusak

Pemecahan Masalah untuk Unit Indoor RA

SiBE121135_A

179 Diagnosis Servis

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Periksa

No.01 Lihat

Hal.230

Periksa

No.06 Lihat

Hal.232

Periksa kondisi operasi.

Kondisi OK?

YA

Periksa No. 06 Periksa katup (atau kumparan) ekspansi elektronik indoor.

Ketika suhu outdoor di bawah batas rendah untuk operasi pendinginan (10˚C), kendali perlindungan kebekuan diaktifkan dan operasi pendinginan berhenti.

TIIDAK Memulai operasi suhu outdoor dalam kisaran tertentu.

Periksa No. 01

OK?

YA

TIDAK Ganti katup (atau kumparan) ekspansi elektronik indoor.

Termistor panel radiant

Termistor penukar panas indoor

Termistor suhu ruangan

Apakah

sesuai dengan TIDAK

bagan karakterikstik termistor?

YA

Periksa saluran udara.

Apakah ada YA

korsleting?

TIDAK

Ganti termistror. Termistor panel radiant Termistor penukar

panas indoor Termistor suhu

ruangan

Sediakan saluran udara yang cukup.

Periksa filter udara.

Sangat kotor?

YA

Bersihkan filter udara.

TIDAK

Periksa penukar panas indoor.

Sangat kotor?

TIDAK

Ganti refrigeran untuk menghilangkan kelembaban

dari perpipaan (setelah gambar vakum).

YA

Bersihkan penukar panas indoor.

Kesalahan berulang? TIDAK

Selesai.

YA

Ganti PCB unit indoor.

Kesalahan berulang?

YA

TIDAK

Selesai.

Ganti penukar panas indoor.

(R18364)

SiBE121135_A Pemecahan Masalah untuk Unit Indoor RA

Diagnosis Servis 180

Termistor atau Kelainan Terkait (Unit Indoor RA)

Kode Kesalahan C4, C9, CE

Metode Deteksi

Kesalahan

Suhu yang dideteksi oleh termistor menentukan kesalahan termistor

Kondisi

Keputusan

Kesalahan

Input termistor adalah lebih dari 4,96 V atau kurang dari 0,04 V selama operasi kompresor.

Dugaan

penyebab

Konektor terputus

Termistor yang sesuai dengan kode kesalahan rusak.

PCB Unit indoor rusak

Pemecahan masalah

Periksa

No.01 Lihat

Hal.230

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Perbaiki sambungan.

Ganti termistror. (Ganti PCB unit indoor.)

Ganti PCB unit indoor.

(R15717)

C4 : Termistor penukar panas indoor

C9 : Termistor suhu ruangan

CE : Termistor panel radiant (Seri FVXG saja)

Periksa sambungan konektor.

Normal? TIDAK

YA

Periksa No. 01 Periksa nilai tahanan termistor.

Normal? TIDAK

YA

Pemecahan Masalah untuk Unit Indoor RA

SiBE121135_A

181 Diagnosis Servis

Kegagalan Membuka/Menutup Panel Depan (Seri FTXG Saja)

Kode Kesalahan C7

Metode Deteksi

Kesalahan

Kondisi

Keputusan

Kesalahan

Jika kesalahan beruang, sistem akan mati.

Dugaan

penyebab

Motor reduksi rusak

Mekanisme panel depan rusak atau tidak berfungsi.

Saklar pembatas rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau

memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Ganti rakitan mekanisme panel depan.

Ganti harness dan motor reduksi.

Ganti rakitan mekanisme panel depan. ★Periksa gerakan kanan dan

kiri secara terpisah dengan tangan.

Diduga kerusakan bentuk panel atau debu menumpuk. Cari penyebabnya.

Ganti sakelar pembatas.

(R17249)

Catatan: Anda tidak dapat mengoperasikan AC dengan remote kontrol jika mekanisme panel depan

rusak.

<Untuk dealer: langkah sementara sebelum memperbaiki>

1. Matikan daya.

2. Lepas panel depan.

3. Nyalakan daya.

(Tunggu sampai proses awal selesai.)

4. Operasikan unit dengan tombol [ON/OFF] unit indoor.

Lepas panel depan dan periksa pergerakannya.

Nyalakan kembali dan periksa gerakannya.

Apakah panel depan bergerak?

TIDAK

YA

Apakah mekanisme panel depan bergerak?

YA

TIDAK

Apakah panel depan membuka/

menutup sepenuhnya?

YA

TIDAK

Nyalakan kembali. Apakah kode

kesalahan muncul kembali?

YA

TIDAK

SiBE121135_A Pemecahan Masalah untuk Unit Indoor RA

Diagnosis Servis 182

Kesalahan transmisi sinyal (antara Unit Indoor dan

Unit Outdoor)

Kode kesalahan U4

Metode Deteksi

Kesalahan

Data yang diterima dari unit outdoor dalam transmisi sinyal diperiksa apakah normal atau tidak.

Kondisi

Keputusan

Kesalahan

Data yang dikirim dari unit outdoor tidak dapat diterima secara normal, atau isi data tidak

normal.

Dugaan

penyebab

Kesalahan pengkabelan

Terputusnya kabel penyambung antara unit indoor dan unit outdoor (kabel No. 3)

PCB unit indoor rusak

Korsleting di dalam lilitan motor kipas

PCB Unit indoor rusak

Bentuk gelombang catu daya terganggu

Pemecahan masalah

Periksa

No.11 Lihat

Hal.233

Perhati

an

Pastikan untuk mematikan saklar listrik sebelum menyambung atau

memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Perbaiki kabel penyambung unit indoor - unit outdoor.

Ganti kabel penyambung antara unit indoor dan unit outdoor.

Diagnosis PCB unit outdoor.

Ganti motor kipas outdoor dan PCB unit outdoor.

Ganti PCB unit indoor.

Cari penyebab gangguan bentuk gelombang catu daya dan perbaikilah.

(R18383)

Periksa kabel penyambung unit indoor - unit outdoor.

Apakah ada kesalahan pengkabelan?

YA

TIDAK

Periksa tegangan kabel penyambung pada papan terminal indoor antara No. 1 dan No. 3, dan antara No. 2 dan No. 3.

Terisolasi dengan baik?

YA

TIDAK

Periksa LED A pada PCB unit outdoor.

Apakah LED A berkedip?

TIDAK

YA

Putar kipas

outdoor dengan tangan.

Apakah kipas outdoor berputar lancar?

TIDAK

YA

Periksa No.11 Periksa bentuk gelombang persediaan listrik.

Apakah ada gangguan? TIDAK

YA

Pemecahan Masalah untuk Unit Indoor RA

SiBE121135_A

183 Diagnosis Servis

Tegangan yang Tidak Menentu (Antara Unit Indoor dan

Unit Outdoor)

Kode kesalahan UA

Metode Deteksi

Kesalahan

Catu daya dideteksi persyaratannya (tipe pasangan berbeda dengan tipe multi) dengan sinyal

transmisi indoor/outdoor.

Kondisi

Keputusan

Kesalahan

Tipe pasangan/pair dan tipe multi saling berhubungan

Dugaan

penyebab

Model yang saling tersambung salah

Model-model yang tersambung salah

Kesalahan pemasangan PCB unit indoor atau PCB unit outdoor

PCB Unit indoor rusak

PCB unit outdoor rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Sesuaikan dengan model yang cocok.

Perbaiki sambungan.

Ganti dengan PCB yang benar.

Ganti PCB unit indoor (atau PCB unit outdoor).

(R11707)

Periksa kombinasi unit indoor dan outdoor.

OK? TIDAK

YA

Apakah kabel penyambung TIDAK tersambung

dengan baik?

YA

Periksa nomor kode (2P01234, misalnya) dari unit PCB indoor dan outdoor dengan Daftar Komponen.

Apakah cocok? TIDAK

YA

Diagnosis Servis 184

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

6. Pemecahan Masalah untuk Unit Indoor SA

Kelainan PCB Unit Indoor

Kode kesalahan A1

Metode Deteksi

Kesalahan

Sistem memeriksa data dari EEPROM.

Kondisi

Keputusan

Kesalahan

Data tidak dapat diterima dengan benar dari EEPROM.

EEPROM : Tipe memori nonvolatil (tidak mudah berubah) Mempertahankan isi memori bahkan

saat catu daya dimatikan.

Dugaan

penyebab

Faktor eksternal (kebisingan dll)

PCB Unit indoor rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Bisa jadi ada penyebab lain (kebisingan, dll) selain kegagalan fungsi.

Ganti PCB unit indoor. (R15319)

Matikan catu daya sekali dan kemudian nyalakan kembali.

Apakah kembali normal?

YA

TIDAK

185 Diagnosis Servis

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

Kelainan Sistem Kendali Tingkat Pengurasan

Kode kesalahan A3

Metode Deteksi

Kesalahan

Saklar apung mendeteksi kesalahan.

Kondisi

Keputusan

Kesalahan

Ketika permukaan air mencapai batas atas dan ketika saklar apung dimatikan (OFF)

Dugaan

penyebab

Pompa pengurasan rusak

Pekerjaan perpipaan pengurasan salah

Perpipaan pengurasan tersumbat

Saklar apung rusak

PCB Unit indoor rusak

Konektor X15A sirkuit pendek rusak pada PCB unit indoor

Diagnosis Servis 186

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Sambungkan konektor sirkuit pendek.

Sambungkan konektor sirkuit pendek.

Ganti PCB unit indoor.

Sambungkan pompa pengurasan.

Ganti PCB unit indoor.

Ganti pompa pengurasan.

Apakah ada sistem pengurasan yang tidak normal?

Sambungkan saklar apung.

Ganti saklar apung.

Ganti PCB unit indoor.

Ganti PCB unit indoor

Catatan: Jika A3 terdeteksi oleh PCB unit indoor yang tidak dipasang dengan X15A, maka PCB unit

indoor rusak.

Apakah unit merupakan tipe ceiling

suspended (FHQ

)

YA

TIDAK

YA Apakah mekanisme kenaikan pengurasan

tersambung?

TIDAK

Apakah

konektor sirkuit pendek

tersambung ke X150 pada PCB

unit indoor?

YA

TIDAK

Periksa kelancaran konektor arus

pendek. Apakah lancar?

TIDAK

YA

Apakah pompa pengurasan tersambung ke

PCB unit indoor?

TIDAK

YA

Apakah pompa pengurasan

bekerja setelah operasi penyalaan kembali?

TIDAK

Atur ke "darurat" dan

periksa tegangan X25A. 220 - 240 VAC?

TIDAK

YA YA

Apakah ketinggian permukaan air pengurasan tidak normal?

YA

TIDAK

Apakah saklar apung tersambung ke X15A?

TIDAK

YA

Lepas saklar apung X15A, sirkuit pendek X15A, dan nyalakan kembali operasi.

Apakah A3 mucul pada tampila

remote kontrol?

TIDAK

YA

187 Diagnosis Servis

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

Kipas motor atau kelainan terkait Motor AC (Seri FFQ, FHQ, FDBQ)

Kode kesalahan A6

Metode Deteksi

Kesalahan

Sinyal dari motor kipas mendeteksi kelainan kecepatan kipas.

Kondisi

Keputusan

Kesalahan

Putaran kipas tidak terdeteksi sedangkan tegangan output ke kipas dalam kondisi maksimum

Dugaan

penyebab

Pemutusan, sirkuit pendek atau pelepasan konektor kipas pada harness motor kipas

Motor kipas rusak (pemutusan, isolasi buruk)

Kelainan sinyal dari motor kipas (sirkuit rusak)

PCB Unit indoor rusak

Fluktuasi sesaat tegangan catu daya.

Motor kipas terkunci

(Disebabkan oleh motor atau faktor eksternal lainnya)

Kipas tidak berputar karena tersangkut benda asing.

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Buang benda asing.

Sambungkan konektor dengan benar. Seri FFQ: X20A Seri FHQ: Seri X20A, X26A FDBQ : X21A

Ganti motor kipas.

Ganti PCB unit indoor.

(R18391)

Matikan catu daya.

Periksa konektor motor

kipas. (Lihat Catatan)

Apakah ada benda asing disekitar

kipas?

YA

TIDAK

Apakah harness dari motor kipas tersambung secara benar dengan

PCB unit indoor?

TIDAK

YA

Apakah ada sirkuit pendek

antara terminal?

TIDAK

YA

Diagnosis Servis 188

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Catatan: 1. Periksa konektor motor kipas. (Kabel catu daya)

2. Matikan catu daya.

3. Mengukur tahanan antara terminal di konektor sisi motor untuk memeriksa bahwa tidak

ada korsleting, sedangkan konektor terputus.

Seri FFQ, FHQ

(1) Merah

(2) Putih

(3) Hitam

(R18060)

Model Titik pengukuran Nilai tahanan

Seri FFQ (1) - (3) 88,2 ± 10%

(2) - (3) 85,5 ± 10%

Seri FHQ (1) - (3) 71,0 ± 10%

(2) - (3) 73,5 ± 10%

Seri FDBQ

ORG

(R18426)

Nilai tahanan

RED - BLK BLK - BLU BLU - ORG ORG - WHT

315,5 ± 10% 74,7 ± 10% 50,4 ± 10% 83,6 ± 10%

BLU WHT

BLK M1F

RED YLW

189 Diagnosis Servis

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

Motor DC (Seri FCQG, FBQ35/50C8VEB)

Kode kesalahan A6

Metode Deteksi

Kesalahan

Sinyal dari motor kipas mendeteksi kelainan kecepatan kipas.

Kondisi

Keputusan

Kesalahan

Kecepatan putar kipas tidak meningkat.

Dugaan

penyebab

Kipas tersumbat benda asing.

Konektor terputus

Motor kipas rusak.

PCB Unit indoor rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Buang benda asing.

Sambungkan konektor dengan benar. FCQG: X20A, konektor relai FBQ35/50C8VEB: X8A

Ganti motor kipas indoor.

Ganti motor kipas indoor dan PCB unit indoor. FCQG: A1P FBQ35/50C8VEB: A2P

Ganti PCB unit indoor.

(R19168)

Matikan catu daya dan tunggu selama 10 menit.

Periksa konektor motor

kipas. (Lihat Catatan)

Apakah ada benda asing disekitar

kipas?

YA

TIDAK

Apakah konektor dari motor kipas tersambung secara benar dengan

PCB unit indoor?

TIDAK

YA

Lepas konektor

motor kipas. Dapatkah Anda memutar kipas dengan lancar menggunakan

tangan?

TIDAK

YA

Apakah tahanan

antara setiap pin lebih besar dari

1?

YA

TIDAK

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Diagnosis Servis 190

Catatan: Periksa tahanan antara masing-masing pin dua kali dengan konektor kipas yang dilepas.

Tukar kabel uji (merah/hitam) dari tester pada saat pemeriksaan kedua.

Nilai kriteria: Lebih tinggi dari 1 kedua kali.

Harap isi bagian yang

kosong dengan tahanan.

Seri FCQG FBQ35/50C8VEB

X20A X8A

1

Merah

Vdc

1

Putih

FG

2

----

2

Oranye

Vsp

3 ----

3

Coklat

Vcc

4 Biru GND 4 Biru GND 5 Coklat Vcc 5 ----

6

Oranye

Vsp

6

----

7

Putih

FG

7

Merah

Vdc

(R19165) (R19166)

Pemeriksaan ke-1 Tester

Tahanan Merah Hitam

FG GND

Vsp GND

Vcc GND

Vdc GND

Pemeriksaan ke-2 Tester

Tahanan Merah Hitam

GND FG

GND Vsp

GND Vcc

GND Vdc

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

191 Diagnosis Servis

Motor DC (FBQ60C8VEB)

Kode kesalahan A6

Metode Deteksi

Kesalahan

Sinyal dari motor kipas mendeteksi kelainan kecepatan kipas.

Kondisi

Keputusan

Kesalahan

Kecepatan putar kipas tidak meningkat.

Dugaan

penyebab

Kipas tersumbat benda asing.

Konektor terputus

Motor kipas rusak.

PCB kipas rusak.

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Buang benda asing.

Sambungkan konektor dengan benar. (X1A, X2A)

Sambungkan konektor dengan benar. (X3A, X70A)

Ganti PCB kipas (A2P).

Matikan catu daya dan tunggu selama 10 menit.

Ganti motor kipas indoor.

Ganti motor kipas indoor dan PCB kipas (A2P).

Ganti PCB kipas (A2P).

Ganti motor kipas indoor jika terjadi kesalahan A6.

Matikan catu daya dan tunggu selama 10 menit.

Nyalakan catu daya dengan konektor kipas

(X2A) dilepas.

Matikan catu daya dan tunggu selama 10 menit.

Periksa konektor motor kipas. (Lihat Catatan)

Apakah ada benda asing disekitar kipas?

TIDAK

YA

Apakah konektor dari motor kipas tersambung ke PCB

kipas?

YA

TIDAK

Apakah konektor antara PCB unit indoor

(A1P) dan PCB kipas (A2P) tersambung dengan

benar?

TIDAK

YA

Sekring (F3U) pada PCB kipas (A2P)

lancar.

YA

TIDAK

Lampu HAP pada PCB

unit indoor berkedip, dan lampu HAP pada PCB

kipas (A2P) tidak berkedip.

TIDAK

YA

Apakah

tahanan antara setiap pin lebih besar dari 1?

TIDAK

YA

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Diagnosis Servis 192

(R19169)

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

193 Diagnosis Servis

Catatan: Periksa tahanan antara masing-masing pin dengan konektor kipas yang dilepas.

Nilai kriteria: Lebih besar dari 1 atas dasar GND dan Vcc.

Harap isi bagian yang

kosong dengan

tahanan.

(R19167)

Tester

Tahanan Mera

h Hitam

GND Hu

GND Hv

GND Hw

GND Vcc

Vcc Hu

Vcc Hv

Vcc Hw

X2A

5

Abu-abu

GND

4

Merah muda

Vcc

3 Oranye

Hw

2

Biru

Hv

1 Kuning

Hu

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Diagnosis Servis 194

Lepas X14A, matikan catu daya sekali dan nyalakan kembali. Periksa apakah saklar batas lancar saat listrik dihidupkan kembali.

YA

Apakah kelancaran/tidak ada kontinuitas terbalik?

YA

TIDAK

220 ~ 240 VAC?

TIDAK

YA

Motor Ayun Terkunci (Seri FHQ Saja)

Kode kesalahan A7

Metode Deteksi

Kesalahan

Kesalahan terdeteksi oleh saklar batas saat motor berputar.

Kondisi

Keputusan

Kesalahan

Ketika saklar mikro ON/OFF untuk deteksi posisi tidak dapat dipulihkan meskipun motor ayun

dialiri listrik selama jumlah waktu tertentu (sekitar 30 detik).

Dugaan

penyebab

Motor ayun rusak.

Saklar mikro rusak

Konektor terputus

PCB Unit indoor rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Sambungkan konektor dengan benar.

Sambungkan konektor dengan benar.

YA

Matikan catu daya sekali dan nyalakan kembali. Periksa apakah motor ayun berayun saat listrik dihidupkan kembali.

Ganti PCB unit indoor.

Ganti PCB unit indoor.

Ganti motor ayun.

(R17251)

Apakah motor ayun berayun?

Apakah konektor

tersambung dengan benar ke X29A dan X14A pada

PCB?

TIDAK

YA

Apakah konektor relai saklar batas

tersambung dengan benar?

TIDAK

TIDAK

Matikan catu daya sekali dan nyalakan kembali. Mengukur tegangan output konektor X29A saat catu daya dihidupkan kembali.

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

195 Diagnosis Servis

Kelainan Sistem Pengurasan

Kode kesalahan AF

Metode Deteksi

Kesalahan

Kebocoran air dideteksi dengan adanya peralihan ON/OFF saklar apung sementara kompresor

tidak beroperasi.

Kondisi

Keputusan

Kesalahan

Ketika saklar apung beralih dari ON ke OFF sementara kompresor OFF

Dugaan

penyebab

Kesalahan dalam pemasangan pipa pengurasan

Saklar apung rusak

PCB Unit indoor rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Saklar apung mungkin rusak. Periksa apakah ketinggian pengurasan dan panjang pipa horisontal melebihi spesifikasi.

Sistem pengurasan air tersumbat, pompa pengurasan tersumbat, atau saklar apung rusak

Ganti PCB unit indoor. Periksa apakah ketinggian pengurasan dan panjang pipa horisontal melebihi spesifikasi.

(R16022)

Dalam FHQ, masalah juga dapat terjadi di pompa pengurasan opsional.

Periksa konektor jumper.

Periksa pompa pengurasan dan pipa pengurasan.

Periksa sistem pengurasan air. Periksa apakah ketinggian pengurasan dan panjang pipa horisontal melebihi spesifikasi.

Penampung rusak dalam sistem pengurasan air

Ganti PCB unit indoor.

(R13752)

Apakah saklar apung dan

pipa pengurasan

normal?

TIDAK

YA

Apakah sistem

pengurasan air normal?

YA

TIDAK

Apakah kotak alat pengurasan terpasang?

TIDAK

YA

Apakah pompa

pengurasan normal?

TIDAK

YA

Apakah jumlah air pengurasan

yang diedarkan berlebihan setelah

pompa menghentikan operasi?

YA

TIDAK

Apakah air pengurasan mengalir

terbalik sedangkan unit indoor tidak beroperasi?

YA

TIDAK

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Diagnosis Servis 196

Termistor atau Kelainan Terkait (Unit Indoor SA)

Kode Kesalahan C4, C5, C9

Metode Deteksi

Kesalahan

Suhu yang dideteksi oleh termistor menentukan kesalahan termistor

Kondisi

Keputusan

Kesalahan

Input termistor adalah lebih dari 4,96 V atau kurang dari 0,04 V selama operasi kompresor.

Dugaan

penyebab

Konektor terputus

Termistor yang sesuai dengan kode kesalahan rusak.

PCB Unit indoor rusak

Pemecahan masalah Jika penyebab masalah terkait dengan termistor, termistor harus diperiksa sebelum mengganti

PCB unit indoor.

Periksa

No.01 Lihat

Hal.230

Untuk memeriksa termistor, lakukan hal-hal berikut:

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Perbaiki sambungan.

Ganti termistror. (Ganti PCB unit indoor.)

Ganti PCB unit indoor.

(R14406)

C4 : Termistor penukar panas indoor 1 (pipa cair) (R2T)

C5 : Termistor penukar panas indoor 2 (R3T)

C9 : Termistor suhu ruangan (R1T)

Periksa sambungan konektor.

Apakah normal?

TIDAK

YA

Periksa No. 01 Periksa nilai tahanan termistor.

Apakah normal?

TIDAK

YA

Langkah

Tindakan

1 Lepas termistor dari PCB unit indoor.

2 Baca suhu dan nilai tahanan.

3 Periksa apakah nilai yang diukur sesuai dengan nilai dalam tabel pemeriksaan tahanan termistor.

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

197 Diagnosis Servis

Kelainan Termistor Remote Kontrol

Kode kesalahan CJ

Metode Deteksi

Kesalahan

Bahkan jika remote kontrol termistor rusak, sistem ini memungkinkan beroperasi dengan sistem

termistor. Deteksi malfungsi dilakukan oleh suhu yang dideteksi oleh remote kontrol termistor.

Kondisi

Keputusan

Kesalahan

Termistor remote kontrol terlepas atau korsleting saat unit sedang berjalan.

Dugaan

penyebab

Termistor rusak

Kabel rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Ganti remote kontrol.

Faktor eksternal selain malfungsi peralatan. (misalnya, kebisingan dll.)

(R18062)

Catatan: Untuk menghapus catatan kode kesalahan, tekan tombol [ON/OFF] selama 4 detik atau lebih saat kode kesalahan ditampilkan dalam mode pemeriksaan.

Hapus rekaman kode kesalahan. (Lihat Catatan.)

Apakah CJ mucul pada

tampilan remote kontrol?

TIDAK

YA

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Diagnosis Servis 198

Kesalahan Transmisi Sinyal (antara Unit Indoor dan

Remote Kontrol)

Kode kesalahan U5

Metode Deteksi

Kesalahan

Dalam kasus pengendalian dengan 2 remote kontrol, periksa sistem menggunakan

mikrokomputer jika transmisi sinyal antara unit indoor dan remote kontrol (utama dan sub)

adalah normal.

Kondisi

Keputusan

Kesalahan

Transmisi normal tidak lancar selama jangka waktu tertentu.

Dugaan

penyebab

Sambungan 2 remote kontrol utama (saat menggunakan 2 remote kontrol)

PCB Unit indoor rusak

Remote kontrol rusak

Kesalahan transmisi akibat kebisingan

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Setel satu remote kontrol ke "SUB"; matikan catu daya sekali dan kemudian nyalakan kembali.

Ganti PCB unit indoor.

Ada kemungkinan kegagalan fungsi yang disebabkan oleh kebisingan. Periksa area sekitar dan nyalakan lagi.

Normal

Normal

Ada kemungkinan kegagalan fungsi yang disebabkan oleh kebisingan. Periksa area sekitar dan nyalakan lagi.

(R13276)

Ganti remote kontrol.

Ganti PCB unit indoor.

Menggunakan 2 remote kontrol?

YA Apakah SS1 kedua remote kontrol

diatur ke "MAIN (UTAMA)"?

YA

TIDAK

TIDAK

Apakah semua monitor PCB mikrokomputer

indoor berkedip?

YA

TIDAK

Apakah operasi kembali

normal ketika daya dimatikan sebentar?

TIDAK

YA

Apakah kembali normal?

YA

TIDAK

Apakah kembali normal?

YA

TIDAK

SiBE121135_A Pemecahan Masalah untuk Unit Indoor SA

199 Diagnosis Servis

Kesalahan Transmisi Sinyal (antara remote kontrol

UTAMA dan remote kontrol SUB)

Kode kesalahan U8

Metode Deteksi

Kesalahan

Dalam kasus pengendalian dengan 2 remote kontrol, periksa sistem menggunakan

mikrokomputer jika transmisi sinyal antara unit indoor dan remote kontrol (utama dan sub)

adalah normal.

Kondisi

Keputusan

Kesalahan

Transmisi normal tidak lancar selama jangka waktu tertentu.

Dugaan

penyebab

Remote kontrol disetel ke "SUB" saat menggunakan 1 remote kontrol

Sambungan 2 remote kontrol sub (saat menggunakan 2 remote kontrol)

PCB remote kontrol rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Setel SS1 ke "MAIN"; matikan catu daya sekali kemudian nyalakan kembali.

Matikan catu daya sekali dan nyalakan kembali. Jika kegagalan fungsi terjadi, ganti PCB remote kontrol.

Setel satu remote kontrol ke "MAIN"; matikan catu daya sekali kemudian nyalakan kembali.

(R15321)

Menggunakan 2 remote kontrol?

TIDAK

Apakah SS1 PCB remote

kontrol disetel ke "SUB"?

TIDAK

YA YA

Apakah SS1 kedua remote

kontrol disetel ke "SUB"?

TIDAK

YA

Pemecahan Masalah untuk Unit Indoor SA

SiBE121135_A

Diagnosis Servis 200

Kelainan Pengaturan bidang

Kode kesalahan UA

Metode Deteksi

Kesalahan

Kondisi

Keputusan

Kesalahan

Pengaturan bidang tidak tepat

Dugaan

penyebab

PCB Unit indoor rusak

PCB unit outdoor rusak

PCB catu daya rusak

Pengkabelan transmisi unit indoor-outdoor, indoor-indoor

Pengkabelan remote kontrol rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Sambungkan remote kontrol dengan tepat

Lepas jumper.

Setel Pengaturan bidang dengan tepat

Sambungkan pengkabelan dengan tepat.

Periksa sistem catu daya di dalam unit indoor.

Bisa jadi pengkabelan tidak tepat. Periksa lagi.

Sambungkan pengkabelan dengan tepat.

Ganti PCB unit indoor.

Normal

(R17253)

Matikan catu daya sekali, dan nyalakan kembali.

Apakah remote kontrol tersambung ke satu

atau lebih unit indoor?

TIDAK

YA

Apakah pengkabelan remote kontrol melompat

antara unit indoor?

TIDAK

YA

Apakah Pengaturan bidang tepat?

YA

TIDAK

Apakah LED (HAP) monitor

servis pada semua PCB unit indoor

berkedip?

TIDAK

Apakah pengkabelan antara unit indoor dan unit

outdoor tersambung dengan tepat?

TIDAK

YA YA

Apakah 220 ~ 240 VAC antara No.1 dan 3 dari papan terminal untuk transmisi (unit

indoor)?

YA

TIDAK

Apakah sistem beroperasi normal?

TIDAK

Apakah pengkabelan antara unit indoor dan unit

outdoor tersambung dengan tepat?

TIDAK

YA YA

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 200

7. Pemecahan Masalah untuk Unit Outdoor

Kekurangan Refrigeran

Kode Kesalahan U0

Tampilan LED

Unit Outdoor

A j 1 h 2 h 3 i 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Deteksi kekurangan refrigeran I :

Kekurangan refrigeran dideteksi dengan memeriksa nilai arus input dan frekuensi kompresor

berjalan. Jika refrigeran kurang, arus input lebih rendah dari nilai normal.

Deteksi kekurangan refrigeran II :

Kekurangan refrigeran dideteksi dengan memeriksa suhu pipa buang dan pembukaan katup

ekspansi elektronik outdoor. Jika refrigeran kurang, suhu pipa buang cenderung naik.

Kondisi

Keputusan

Kesalahan

Deteksi kekurangan refrigeran I :

Kondisi berikut berlanjut selama 7 menit.

Arus DC A × Frekuensi output kompresor + B

Frekuensi output > C

A (–) B (A) C (Hz)

Kelas 40/50/52/58 0,01 0,3 54

Kelas 68/75 0,035 0,5 55

Kelas 80/90 0,027 2,0 40

Deteksi kekurangan refrigeran II :

Kondisi berikut berlanjut selama 80 detik.

Pembukaan katup ekspansi elektronik outdoor D

Suhu pipa buang > E × suhu pipa buang target + F

D (pulsa) E (–) F (°C)

Pendinginan 450 255/256

20

Pemanasan

40

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 60 menit tanpa kesalahan lainnya

Dugaan

penyebab

Putusnya termistor pipa buang, termistor penukar panas indoor atau outdoor, termistor

suhu ruangan atau outdoor

Katup penutup tertutup

Kekurangan Refrigeran (kebocoran refrigeran)

Kinerja kompresi kompresor yang buruk

Katup ekspansi elektronik outdoor rusak

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

201 Diagnosis Servis

Pemecahan masalah

Periksa No.01

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Lihat hal.230 Adakah termistor yang terlepas?

YA

Termistor pipa buang

Ganti termistor pada posisinya.

Periksa

No.11 Lihat

Hal.234

TIDAK

Katup penutup tertutup?

Termistor penukar panas indoor atau outdoor Termistor suhu ruangan Termistor suhu outdoor

YA Buka Katup penutup.

TIDAK

Periksa apakah kekurangan refrigeran.

Oli mengalir di sambungan pipa

relai?

YA Perbaiki pipe flare (penyambung pipa) atau ganti sambungan pipa (union)

TIDAK

Oli mengalir di pipa internal?

YA

TIDAK

Periksa No. 12 Apakah katup

ekspansi elektronik berfungsi?

Kompresor terlalu

banyak bergetar?

TIDAK

TIDAK

YA

Periksa harness apakah longgar. Perbaikilah. Serta ganti pipa yang retak. Periksa pipa apakah ada kontak yang tidak tepat. Perbaikilah. Serta ganti pipa yang retak.

Ganti katup ekspansi elektronik outdoor.

YA

Ganti refrigeran baru dalam jumlah tertentu.

Kesalahan kekurangan

refrigeran lagi?

TIDAK

YA

Periksa No. 01

Periksa termistor.

NG Ganti termistor yang rusak.

OK

Ganti PCB unit outdoor.

Terjadi kesalahan lagi?

TIDAK

YA Ganti kompresor

Selesai

Selesai

(R17254)

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 202

Deteksi Tegangan Rendah atau Terlalu Tinggi

Kode kesalahan U2

Tampilan LED

Unit Outdoor

A j 1 i 2 h 3 h 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

★ Unit Indoor

Deteksi lintas nol catu daya dievaluasi oleh PCB unit indoor.

★ Unit Outdoor

Deteksi tegangan rendah:

Penurunan tegangan secara tidak normal dideteksi dengan sirkuit deteksi tegangan DC.

Deteksi tegangan berlebih:

Kenaikan tegangan secara tidak normal dideteksi dengan sirkuit deteksi tegangan berlebih.

Kondisi

Keputusan

Kesalahan

★ Unit Indoor

Tidak ada deteksi lintas nol selama sekitar 10 detik.

★ Unit Outdoor

Deteksi tegangan rendah:

Tegangan yang dideteksi oleh sirkuit deteksi tegangan DC adalah di bawah 150 V selama 0,1 detik.

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 60 menit tanpa kesalahan lainnya

Deteksi tegangan berlebih:

Sinyal tegangan berlebih dikirimkan oleh sirkuit deteksi tegangan berlebih ke komputer mikro.

Kompresor mati jika terjadi kesalahan, dan hidup kembali secara otomatis setelah siaga 3 menit.

Dugaan

penyebab

Tegangan catu daya tidak sesuai spesiikasi.

Sirkuit deteksi tegangan DC rusak

Sirkuit deteksi tegangan berlebih rusak

Bagian kendali PAM rusak

Terlepasnya harness kompresor

Korsleting di dalam lilitan motor kipas

Kebisingan

Penurunan tegangan sesaat

Mati listrik sebentar

PCB unit outdoor rusak

PCB Unit indoor rusak

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

203 Diagnosis Servis

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Perbaiki catu daya.

Sambung kembali harness.

Ganti motor kipas outdoor dan PCB unit outdoor.

Periksa faktor-faktor tersebut dengan seksama. Coba nyalakan kembali

beberapa kali.

Ganti PCB unit outdoor.

Ganti PCB unit indoor.

(R18425)

Faktor-faktor gangguan Kebisingan Distorsi catu daya

Periksa tegangan catu daya.

Tegangan sesuai?

TIDAK

YA

Periksa sambungan harness kompresor.

Kendor atau terlepas?

YA

TIDAK

Putar kipas outdoor dengan tangan.

Apakah

kipas outdoor berputar

lancar?

TIDAK

YA

Nyalakan daya lagi. Apakah sistem

menyala kembali.

(Pencegahan sebelum menyalakan daya kembali) Pastikan daya sudah mati sedikitnya selama 30 detik.

YA

TIDAK

Ulangi beberapa kali.

Terjadi kesalahan kembali

dalam waktu 3 menit setelah menyalakan

daya?

TIDAK

YA

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 204

Kesalahan Transmisi Sinyal (pada PCB unit outdoor)

Kode kesalahan U7

Tampilan LED

Unit Outdoor

A j 1 h 2 i 3 i 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kesalahan komunikasi antara mikrokomputer yang dipasang pada PCB utama dan PM1.

Kondisi

Keputusan

Kesalahan

Kelainan ditentukan ketika data yang dikirim dari PM1 tidak dapat diterima selama 9

detik.

Kontra kesalahan diatur ulang ketika data dari PM1 dapat berhasil diterima.

Dugaan

penyebab

PCB unit indoor rusak

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Ganti PCB unit outdoor.

Penyebab bisa jadi faktor eksternal selain kegagalan fungsi.

Amati kondisi operasi dengan seksama.

(R7185)

Matikan daya dan nyalakan kembali.

YA Terjadi kesalahan lagi?

TIDAK

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

205 Diagnosis Servis

Tegangan Tidak Menentu (Antara Unit Indoor dan Unit

Outdoor) / Fungsi Anti Pembentukan Es (Anti-icing) di Ruangan Lainnya

Kode kesalahan UA, UH

Tampilan LED

Unit Outdoor

A j 1 h 2 h 3 h 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Sambungan yang salah dideteksi dengan memeriksa kombinasi unit indoor dan outdoor di

mikrokomputer.

Kondisi

Keputusan

Kesalahan

Fungsi anti pembentukan es (Anti-icing) di ruangan lainnya

Tegangan internal dan/atau eksternal tidak menentu

Ketidakcocokan unit indoor dan outdoor

Dugaan

penyebab

Fungsi anti pembentukan es (Anti-icing) di ruangan lainnya

Tegangan catu daya tidak sesuai spesiikasi.

Model yang saling tersambung salah

Kesalahan pemasangan PCB unit indoor atau PCB unit outdoor

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Fungsi anti-icing diaktifkan di ruangan lain. Lihat A5.

Perbaiki tegangan catu daya.

Sesuaikan dengan model yang cocok.

Catatan: Lihat "Kendali Anti-icing untuk unit indoor" 206 untuk penjelasan rinci.

(R18424)

Periksa kombinasi model.

Apakah kesalahan ditampilkan saat beroperasi?

TIDAK

YA

Apakah tegangan catu daya sesuai spesiikasi.

TIDAK

YA

Apakah cocok? TIDAK

YA

Periksa kombinasi semua model yang disambungkan.

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 206

Kendali Anti Pembentukan Es (Anti-icing) untuk Unit Indoor

Kode kesalahan A5

Tampilan LED

Unit Outdoor

A j 1 i 2 h 3 i 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Selama operasi pendinginan, pembentukan es unit indoor dideteksi dengan memeriksa suhu

yang dibaca oleh termistor penukar panas indoor dan termistor suhu ruangan yang terletak di

ruangan mematikan sistem (shut-down).

Kondisi

Keputusan

Kesalahan

Dalam operasi pendinginan, kondisi (A) dan (B) terpenuhi selama 5 menit.

(A) Suhu ruangan - Suhu penukar panas indoor 10°C

(B) Suhu penukar panas indoor –1°C

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Siaga 3 menit berakhir dan suhu penukar panas indoor di

atas 0°C

Dugaan

penyebab

Pengkabelan atau perpipaan salah

Katup ekspansi elektronik outdoor rusak

Udara hubungan pendek (korsleting)

Termistor penukar panas indoor rusak

Termistor suhu ruangan rusak

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

207 Diagnosis Servis

Pemecahan masalah

Periksa

No.01 Lihat

Hal.230

Periksa

No.11 Lihat

Hal.234

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Mengaktifkan fungsi pemeriksaan kesalahan pengkabelan.

Ganti katup ekspansi elektronik outdoor.

Ganti termistor penukar panas outdoor.

Ganti termistor suhu ruangan.

Ganti termistor suhu ruangan atau termistor penukar panas indoor. Lakukan pengeringan vakum.

Ganti PCB unit indoor kemudian nyalakan fungsi pemeriksaan kesalahan pengkabelan.

(R17255)

Periksa No. 12 Periksa katup ekspansi elektronik outdoor.

Periksa No. 01 Periksa termistor penukar panas outdoor.

Periksa No. 01 Periksa termistor suhu ruangan.

Periksa pengkabelan atau perpipaan.

Apakah pengkabelan atau perpipaan salah?

YA

TIDAK

TIDAK Berfungsi?

YA

Apakah sesuai dengan bagan karakterikstik termistror?

YA

TIDAK

Apakah sesuai dengan bagan karakterikstik termistror?

YA

Ganti refrigeran untuk menghilangkan kelembaban dari perpipaan (setelah gambar vakum).

TIDAK

YA Terjadi kesalahan lagi?

TIDAK

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 208

Kelainan PCB Unit Outdoor

Kode kesalahan E1

Tampilan LED

Unit Outdoor

A j 1 i 2 i 3 i 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Mendeteksi di dalam program mikrokomputer.

Kondisi

Keputusan

Kesalahan

Program mikrokomputer berjalan di luar kendali.

Dugaan

penyebab

PCB unit indoor rusak

Kebisingan

Penurunan tegangan sesaat

Mati listrik sebentar

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Ganti PCB unit outdoor.

Lakukan pekerjaan pembumian.

Penyebab bisa jadi faktor eksternal selain kegagalan fungsi. Selidiki penyebab kebisingan.

(R7183)

Nyalakan kembali daya

Terjadi kesalahan lagi?

YA

TIDAK Periksa apakah unit outdoor dibumikan.

Dibumikan?

TIDAK

YA

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

209 Diagnosis Servis

Aktivasi OL (Kompresor Kelebihan Beban)

Kode kesalahan E5

Tampilan LED

Unit Outdoor

A j 1 i 2 h 3 i 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kelebihan beban pada kompresor di deteksi dengan OL kompresor

Kondisi

Keputusan

Kesalahan

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 60 menit tanpa kesalahan lainnya

Dugaan

penyebab

Termistor pipa buang lepas

Termistor pipa buang rusak

Konektor [S40] lepas

2 terminal OL (Q1L) lepas

OL(Q1L) rusak

Harness OL putus

Katup atau kumparan ekspansi elektronik rusak

Katup atau kumparan empat arah rusak

PCB unit indoor rusak

Kekurangan refrigeran

Air tercampur di dalam refrigeran

Katup penutup rusak

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 210

Pemecahan masalah

Periksa

No.01 Lihat

Hal.230

Periksa

No.12 Lihat

Hal.234

Periksa

No.13 Lihat

Hal.235

Periksa

No.14 Lihat

Hal.235

Perhatia

n

Pastikan untuk mematikan saklar listrik sebelum menyambung atau

memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Masukkan termistor pada posisinya

Ganti termistor pipa buang.

Sambungkan konektor dengan benar.

Ganti OL (Q1L).

Ganti harness OL.

Ganti katup ekspansi elektronik outdoor atau kumparan.

Ganti katup empat arah atau kumparan. Ganti PCB unit outdoor.

LIhat prosedur pemeriksaan saluran refrigeran.

Ganti PCB unit outdoor. (R18333)

Catatan: Suhu pengaktifan OL (Q1L): Suhu

pemulihan 120°C OL (Q1L): 95°C

Apakah termistor pipa buang tidak tersambung?

YA

TIDAK

Periksa No. 01 Periksa termistor.

NG

Termistor pipa buang

OK

Apakah konektor tersambung dengan baik ?

TIDAK

Konektor [S40] 2 terminal OL (Q1L)

YA

Lepaskan konektor [S40] dari PCB.

Periksa tahanan

Tahanan

antara 2 terminal pada konektor

[S40].

Lepaskan 2 terminal OL (Q1L).

Hampir 0

Periksa Tahanan

tahanan antara 2 terminal dari OL (Q1L).

Hampir 0

Periksa No. 12 Periksa katup ekspansi

elektronik outdoor.

NG

OK

Periksa No. 13 Periksa katup empat arah.

OK

NG

Periksa No. 14 Periksa saluran

refrigeran.

OK

NG Kekurangan

refrigeran Air bercampur Katup penutup

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

211 Diagnosis Servis

Kompresor Terkunci

Kode kesalahan E6

Tampilan LED

Unit Outdoor

A j 1 h 2 i 3 i 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kompresor terkunci dideteksi dengan memeriksa kondisi kompresor yang sedang digunakan

melalui sirkuit deteksi posisi.

Kondisi

Keputusan

Kesalahan

Melihat dari bentuk gelombang arus yang dihasilkan ketika tegangan frekuensi tinggi

diterapkan ke kompresor.

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 5 menit tanpa kesalahan lainnya

Dugaan

penyebab

PCB unit indoor rusak

Kompresor rusak

Katup ekspansi elektronik outdoor rusak

Pemecahan masalah

Periksa

No.15 Lihat

Hal.236

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

(Pencegahan sebelum menyalakan daya kembali)

Pastikan daya sudah mati sedikitnya selama 30 detik.

Perbaiki catu daya atau ganti PCB unit outdoor

Ganti kompresor

Periksa kumparan katup ekspansi elektronik outdoor. Ganti sesuai yang diperlukan.

Ganti kompresor

(R18317)

Periksa No.15 Periksa dengan penganalisa inverter

Matikan daya. Lepas harness U, V, dan W.

Penganalisa inverter RSUK0917C

TIDAK Normal?

YA

Matikan daya dan sambungkan kembali harness. Nyalakan daya dan hidupkan kembali sistem.

Mati darurat dan kompresor tidak

berjalan?

YA

TIDAK

Sistem mati setelah kesalahan

berulang beberapa kali? TIDAK

YA

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 212

Kipas DC Terkunci

Kode kesalahan E7

Tampilan LED

Unit Outdoor

A j 1 i 2 i 3 i 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kesalahan ditentukan dengan kecepatan putar motor kipas tegangan tinggi yang dideteksi oleh Hall IC.

Kondisi

Keputusan

Kesalahan

Kipas tidak nyala dalam waktu sekitar 30 detik, meski motor kipas berjalan.

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 5 menit tanpa kesalahan lainnya

Dugaan

penyebab

Motor kipas terlepas

Benda asing terjebak di dalam kipas

Motor kipas rusak.

PCB unit indoor rusak

Pemecahan masalah

Periksa

No.16 Lihat

Hal.237

Perhatia

n

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Matikan daya dan sambungkan kembali ke konektor.

Buang benda asing.

Ganti motor kipas outdoor.

Ganti motor kipas outdoor.

Ganti PCB unit outdoor. (R15890)

Konektor motor kipas terlepas?

YA

TIDAK

Ada benda asing di dalam atau sekitar kipas?

YA

TIDAK

Nyalakan daya.

Putar kipas.

Kipas berputar lancar?

TIDAK

YA

Periksa No. 16 Periksa input pulsa putaran pada PCB unit outdoor.

Ada sinyal pulsa? TIDAK

YA

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

213 Diagnosis Servis

Deteksi Arus Input Berlebih

Kode kesalahan E8

Tampilan LED

Unit Outdoor

A j 1 h 2 i 3 h 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Dideteksi dengan memeriksa nilai arus input

Kondisi

Keputusan

Kesalahan

Arus input pada nilai tertentu (bergantung pada kondisi) selama 2,5 detik.

Kompresor mati jika terjadi kesalahan, dan hidup kembali secara otomatis setelah siaga 3 menit.

Dugaan

penyebab

Suhu outdoor di luar jangkauan operasi.

Kompresor rusak

Modul daya rusak

PCB unit indoor rusak

Korsleting

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Periksa

No.15 Lihat

Hal.236

Periksa

No.17 Lihat

Hal.238

Periksa

No.18 Lihat

Hal.238

Arus input berlebih bisa disebabkan oleh pengkabelan internal yang salah. Jika sistem terganggu oleh arus input berlebih setelah kabel diputus atau disambung kembali untuk penggantian komponen, periksa kabelnya lagi.

Ganti PCB unit outdoor.

Perbaiki catu daya atau ganti PCB unit outdoor

(R18318)

Periksa No. 17 Periksa kondisi pemasangan.

Mulai operasi dan ukur arus input.

Arus input mengalir di atas level berhentinya?

TIDAK

YA

Matikan daya dan lepas harness U, V, dan W.

Periksa No.15 Periksa dengan penganalisa inverter

Penganalisa inverter RSUK0917C

Adakah LED mati?

YA

TIDAK

Matikan daya, dan sambungkan kembali harness. Nyalakan daya kembali dan mulai operasi.

Periksa No. 18 Periksa tekanan buang

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 214

Kendali Suhu Pipa Buang

Kode kesalahan F3

Tampilan LED

Unit Outdoor

A j 1 i 2 h 3 i 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Dideteksi dengan termistor pipa buang.

Kondisi

Keputusan

Kesalahan

Jika suhu yang dideteksi oleh termistor pipa buang naik di atas A°C, kompresor

berhenti.

Kesalahan menjadi jelas ketika suhu pipa buang telah turun di bawah B°C

A (°C) B (°C)

Kelas 40/50/52/58 110 95

Kelas 68/75/80/90 120 107

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 60 menit tanpa kesalahan lainnya

Dugaan

penyebab

Termistor pipa buang rusak

(Termistor penukar panas outdoor rusak atau termistor suhu outdoor rusak)

Katup atau kumparan ekspansi elektronik rusak

Kekurangan refrigeran

Katup empat arah rusak

Air tercampur di dalam refrigeran

Katup penutup rusak

PCB unit indoor rusak

Pemecahan masalah

Periksa

No.01 Lihat

Hal.230

Periksa

No.12 Lihat

Hal.234

Periksa

No.14 Lihat

Hal.235

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Ganti termistor yang rusak.

Ganti katup ekspansi elektronik outdoor atau kumparan.

LIhat prosedur pemeriksaan saluran refrigeran.

Ganti PCB unit outdoor.

(R15286)

Periksa No. 01 Periksa termistor.

OK

NG

Termistor pipa buang Termistor penukar panas outdoor Termistor suhu outdoor

Periksa No. 12 Periksa katup ekspansi

elektronik outdoor. NG

OK

Periksa No. 14 Periksa saluran

refrigeran.

OK

NG

Kekurangan refrigeran

Katup empat arah Air bercampur Katup penutup

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

215 Diagnosis Servis

Kendali Tekanan Tinggi dalam Pendinginan

Kode kesalahan F6

Tampilan LED

Unit Outdoor

A j 1 i 2 h 3 i 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kendali tekanan tinggi (penghentian operasi, penurunan frekuensi, dll) diaktifkan dalam operasi

pendinginan jika suhu yang dirasakan oleh termistor penukar panas outdoor melebihi batas.

Kondisi

Keputusan

Kesalahan

Suhu yang dirasakan oleh termistor penukar panas outdoor meningkat di atas 65°C.

Kesalahan menjadi jelas ketika suhu turun di bawah 50°C.

Dugaan

penyebab

Ruang instalasi tidak cukup besar.

Penukar panas outdoor kotor

Motor kipas outdoor rusak.

Katup penutup rusak

Katup atau kumparan ekspansi elektronik rusak

Termistor penukar panas outdoor rusak

PCB unit indoor rusak

Pemecahan masalah

Periksa

No.01 Lihat

Hal.230

Periksa

No.12 Lihat

Hal.234

Periksa

No.17 Lihat

Hal.238

Periksa

No.18 Lihat

Hal.238

Periksa

No.19 Lihat

Hal.239

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Ganti lokasi atau arah pemasangan. Bersihkan penukar panas outdoor.

Ganti motor kipas. Sambungkan kembali konektor atau kabel utama motor kipas

Ganti katup penutup.

Ganti katup ekspansi elektronik outdoor atau kumparan. Ganti PCB unit outdoor.

Ganti termistor penukar panas outdoor.

Ganti PCB unit outdoor.

(R14413)

Periksa ruang pemasangan.

Periksa No. 17 Periksa kondisi pemasangan.

NG

OK

Periksa No. 19 Periksa kipas outdoor.

NG

OK

Periksa No. 18 Periksa tekanan

buang.

OK

NG

Periksa No. 12 Periksa kumparan katup

ekspansi elektronik outdoor.

OK

NG

Periksa No. 1 Periksa termistor penukar panas outdoor.

NG

OK

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 216

Kelainan Sistem Sensor Kompresor

Kode Kesalahan H0

Tampilan LED

Unit Outdoor

A j 1 i 2 i 3 h 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kondisi kesalahan diidentifikasi oleh tegangan catu daya dan tegangan DC yang

terdeteksi sebelum penyalaan kompresor.

Kondisi kesalahan diidentifikasi oleh arus kompresor yang terdeteksi tepat setelah

penyalaan kompresor.

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 5 menit tanpa kesalahan lainnya

Kondisi

Keputusan

Kesalahan

Nilai yang dideteksi dari tegangan catu daya dan tegangan DC adalah jelas rendah atau tingginya.

Arus kompresor tidak berjalan ketika kompresor dinyalakan.

Dugaan

penyebab

Terlepasnya reaktor

Terlepasnya harness kompresor

PCB unit indoor rusak

Kompresor rusak

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

217 Diagnosis Servis

Pemecahan masalah

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Sambungkan reaktor dengan benar.

Sambungkan kompresor dengan benar.

Ganti reaktor

Ganti kompresor atau harness relai kompresor.

Mulai operasi kembali dan jika kesalahan muncul kembali, Ganti PCB unit outdoor.

(R15891)

Matikan daya.

Pemeriksaan sambungan reaktor

Sambungan OK?

TIDAK

YA

Pemeriksaan sambungan kompresor

Sambungan OK?

TIDAK

YA

Pemeriksaan reaktor

Lepaskan reaktor dari PCB unit outdoor dan mengukur nilai tahanan antara terminal reaktor dengan tester.

10 atau kurang?

TIDAK

YA

Pemeriksaan kompresor

Lepaskan harness relai kompresor dari PCB unit outdoor dan mengukur nilai tahanan antara terminal dengan tester.

10 atau kurang antara

setiap terminal?

YA

TIDAK

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 218

Kelainan Sensor Posisi

Kode kesalahan H6

Tampilan LED

Unit Outdoor

A j 1 i 2 i 3 h 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kegagalan penyalaan kompresor dideteksi dengan memeriksa kondisi kompresor saat bekerja melalui sirkuit deteksi posisi.

Kondisi

Keputusan

Kesalahan

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 5 menit tanpa kesalahan lainnya

Dugaan

penyebab

Terputusnya kabel relai kompresor

Kompresor rusak

PCB unit indoor rusak

Kegagalan penyalaan yang disebabkan oleh katup peutup yang tertutup

Tegangan input berada di luar kisaran yang ditetapkan.

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

219 Diagnosis Servis

Pemecahan masalah

Periksa

No.15 Lihat

Hal.236

Periksa

No.18 Lihat

Hal.238

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Perbaiki catu daya.

Ganti katup penutup.

Sambungkan kembali komponen listrik atau harness kompresor sesuai ketentuan.

Ganti PCB unit outdoor.

Perbaiki catu daya atau ganti PCB unit outdoor

Ganti kompresor

(R18343)

Nyalakan daya. Periksa tegangan kapasitor elektrolitik.

Matikan daya.

Periksa tegangan catu daya.

TIDAK Tegangan

sesuai?

YA

Periksa No. 18 Periksa tekanan buang

OK? TIDAK

YA

Periksa sambungan.

Komponen listrik atau

harness kompresor tersambung sesuai

ketentuan?

TIDAK

YA

TIDAK 320 ± 50 VDC?

YA

Matikan daya. Lepas harness U, V, dan W.

Periksa No. 15 Periksa dengan penganalisa inverter

Penganalisa inverter RSUK0917C

Adakah LED mati?

YA

TIDAK

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 220

CT atau Kelainan Terkait

Kode kesalahan H8

Tampilan LED

Unit Outdoor

A j 1 i 2 i 3 h 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

CT atau kelainan terkait dideteksi dengan memeriksa frekuensi aliran kompresor dan arus input

yang dideteksi CT.

Kondisi

Keputusan

Kesalahan

Frekuensi aliran kompresor lebih dari A Hz dan arus input kurang dari B A.

A (Hz) B (A)

Kelas 40/50/52/58/68/75 55 0,5

Kelas 80/90 32 0,5

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 60 menit tanpa kesalahan lainnya

Dugaan

penyebab

Modul daya rusak

Pengkabelan rusak atau terputus

Reaktor rusak

PCB unit indoor rusak

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

221 Diagnosis Servis

Mulai operasi.

Periksa No. 21 Periksa tegangan kapasitor.

Mengukur tegangan input penyearah.

Pemecahan masalah

Periksa No.15

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Lihat hal.236

Periksa

No.21 Lihat

Hal.239

Matikan daya dan nyalakan kembali.

Arus berjalan seperti yang ditunjukkan di sebelah kanan dengan kabel relai 1

atau 2?

TIDAK

YA

Arus (pedoman)

Kapasitor diisi ketika relai

utama unit indoor atau outdoor dinyalakan

Naik karena frekuensi meningkat

Ganti PCB unit outdoor.

2 det Waktu

320 ± 50 VDC? YES Matikan daya. Lepas harness U, V, dan W.

TIDAK

Periksa No.15 Periksa dengan penganalisa inverter

Penganalisa

inverter RSUK0917C

Adakah LED mati?

TIDAK

YA

Perbaiki catu daya atau ganti PCB unit outdoor

Matikan daya dan sambungkan kembali harness. Nyalakan daya kembali dan mulai kembali operasi.

Kompresor berjalan? YA

Ganti PCB unit outdoor.

Tegangan

dalam kisaran yang diijinkan (Tegangan

catu daya ± 15%) ?

YA

TIDAK

Ganti kompresor

Ganti PCB unit outdoor.

TIDAK Periksa tegangan catu daya.

(R18335)

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 222

Termistor atau Kelainan Terkait (Unit Outdoor) 222

Kode Kesalahan H9, J3, J6, J8, J9, P4

Tampilan LED

Unit Outdoor

A j 1 i 2 i 3 h 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Tipe kesalahan ini dideteksi dengan memeriksa tegangan input termistor pada

mikrokomputer. Kesalahan termistor dideteksi dengan memeriksa suhu yang dirasakan oleh

setiap termistor.

Kondisi

Keputusan

Kesalahan

Input termistor di atas 4,96 V atau di bawah 0,04 V dengan daya nyala.

Kesalahan J3 dinilai jika suhu pipa pembuangan lebih rendah dari suhu penukar

panas.

Sistem mati jika semua unit dinilai sebagai kesalahan J8.

Dugaan

penyebab

Pemutusan konektor untuk termistor

Termistor yang sesuai dengan kode kesalahan rusak.

Termistor penukar panas rusak dalam kasus kesalahan J3 (termistor penukar panas

outdoor dalam operasi pendinginan, atau termistor penukar panas indoor dalam operasi

pemanasan)

PCB unit indoor rusak

Pemecahan Masalah Dalam kasus P4

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

sambungan, atau kerusakan komponen dapat terjadi.

Ganti PCB unit outdoor.

P4 : Termistor sirip radiasi

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

223 Diagnosis Servis

Periksa No. 01 Periksa nilai tahanan termistor.

Pemecahan Masalah Dalam kasus H9, J3, J6, J8, J9

Periksa No.01

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau

memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Lihat hal.230 Nyalakan daya lagi.

Kesalahan tampilan TIDAK lagi pada remote

kontrol?

Sambung kembali konektor atau termistor.

YA

Kesalahan J3: Suhu pipa buang lebih rendah dari suhu penukar panas.

TIDAK Normal?

YA

Ganti termistor yang rusak. Termistor suhu

outdoor Termistor pipa buang Penukar panas outdoor

Pendinginan: Termistor penukar panas outdoor Pemanasan: Termistor penukar panas indoor

Periksa No. 01

Periksa nilai tahanan termistor penukar

panas indoor dalam operasi pemanasan.

termistor Termistor pipa cair Termistor pipa gas

Termistor penukar TIDAK

panas indoor

berfungsi?

YA

Ganti termistor berikut. Termistor penukar

panas indoor

Ganti PCB unit outdoor.

(R17164)

H9 : Termistor suhu outdoor

J3 : Termistor pipa buang

J6 : Termistor penukar panas outdoor

J8 : Termistor pipa cair

J9 : Termistor pipa gas

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 224

Kenaikan Suhu Panel Listrik

Kode kesalahan L3

Tampilan LED

Unit Outdoor

A j 1 i 2 i 3 h 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kenaikan suhu panel listrik dideteksi dengan memeriksa termistor sirip radiasi dengan

kompresor mati.

Kondisi

Keputusan

Kesalahan

Dengan kompresor mati, suhu sirip radiasi adalah di atas A°C.

Kesalahan menjadi jelas ketika suhu sirip radiasi turun di bawah B°C.

Untuk mendinginkan komponen listrik, kipas outdoor menyala ketika suhu sirip radiasi naik di

atas C°C dan mati ketika suhu sirip radiasi turun di bawah B°C.

A (°C) B (°C) C (°C)

100 70 85

Dugaan

penyebab

Motor kipas outdoor rusak.

Korsleting

Termistor sirip radiasi rusak

Konektor terputus

PCB unit indoor rusak

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

225 Diagnosis Servis

Pemecahan masalah

Periksa

No.17 Lihat

Hal.238

Periksa

No.19 Lihat

Hal.239

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Ganti PCB unit outdoor.

Ganti motor kipas. Perbaiki konektor atau kabel utama motor kipas Ganti PCB unit outdoor.

Bersihkan sirip radiasi

(R14416)

A (°C) B (°C) C (°C)

100 70 85

PERINGATAN

Untuk mendinginkan komponen listrik, kipas outdoor menyala ketika suhu sirip radiasi naik di atas C°C dan mati ketika suhu sirip radiasi turun di bawah B°C. Matikan daya dan nyalakan

kembali.

Periksa suhu sirip radiasi.

Kesalahan lagi atau kipas outdoor diaktifkan?

YA

TIDAK

Di atas A ˚C?

TIDAK

YA

Periksa No. 19 Periksa kipas outdoor

atau yang terkait.

NG

OK

Sirip radiasi kotor? Terlalu kotor

Agak kotor Periksa No. 17 Periksa kondisi pemasangan.

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 226

Kenaikan suhu sirip (fin) radiasi

Kode kesalahan L4

Tampilan LED

Unit Outdoor

A j 1 h 2 h 3 h 4 i 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kenaikan suhu sirip radiasi dideteksi dengan memeriksa termistor sirip radiasi dengan

kompresor menyala

Kondisi

Keputusan

Kesalahan

Suhu sirip radiasi dengan kompresor menyala adalah di atas A°C.

Kesalahan menjadi jelas ketika suhu sirip radiasi turun di bawah B°C.

A (°C) B (°C)

Kelas 40/50/52/58/68/75 103 95

Kelas 80/90 105 97

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 60 menit tanpa kesalahan lainnya

Dugaan

penyebab

Motor kipas outdoor rusak.

Korsleting

Termistor sirip radiasi rusak

Konektor terputus

PCB unit indoor rusak

Pelumas silikon tidak digunakan dengan benar pada sirip radiasi setelah mengganti

PCB Unit outdoor.

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

227 Diagnosis Servis

Pemecahan masalah

Periksa

No.17 Lihat

Hal.238

Periksa

No.19 Lihat

Hal.239

Perhatian

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan sambungan, atau kerusakan komponen dapat terjadi.

Periksa apakah pelumas silikon digunakan dengan benar pada sirip radiasi. Jika tidak, gunakan pelumas silikon.

Ganti PCB unit outdoor.

Ganti motor kipas outdoor. Perbaiki konektor dan kabel timah motor kipas Ganti PCB unit outdoor.

Bersihkan sirip radiasi

(R18320)

A (°C)

Kelas 40/50/52/58/68/75 103

Kelas 80/90 105

Catatan: Lihat "Pelumas Silikon pada Transistor Daya / Jembatan Dioda" pada hal. 262 untuk penjelasan rinci.

Matikan listrik. Lalu, nyalakan lagi untuk memulai kembali sistem.

Periksa suhu sirip radiasi.

Kesalahan ditampilankan lagi?

YA Haruskah PCB diganti?

YA

TIDAK TIDAK

Di atas A ˚C?

TIDAK

YA

Periksa No. 19 Periksa kipas outdoor

atau yang terkait.

NG

OK

Sirip radiasi kotor? Terlalu kotor

Agak kotor

Periksa No. 17 Periksa kondisi pemasangan.

SiBE121135_A Pemecahan Masalah untuk Unit Outdoor

Diagnosis Servis 228

Deteksi Kelebihan Arus Output

Kode kesalahan L5

Tampilan LED

Unit Outdoor

A j 1 h 2 h 3 i 4 h 5 h LED5 hanya tersedia pada model 5-ruangan.

Metode Deteksi

Kesalahan

Kelebihan arus output dideteksi dengan memeriksa arus yang mengalir pada bagian DC inverter.

Kondisi

Keputusan

Kesalahan

Kesalahan sinyal posisi terjadi saat kompresor berjalan.

Kesalahan kecepatan putar terjadi saat kompresor berjalan.

Sinyal kelebihan arus output diumpankan dari sirkuit deteksi kelebihan arus output

ke mikrokomputer.

Jika kesalahan beruang, sistem akan mati.

Kondisi pengaturan ulang: Terus berlangsung selama sekitar 5 menit tanpa kesalahan lainnya

Dugaan

penyebab

Kondisi pemasangan yang buruk

Katup penutup tertutup

Modul daya rusak

Pengkabelan internal yang salah

Kelainan tegangan catu daya

PCB unit indoor rusak

Kompresor rusak

Pemecahan Masalah untuk Unit Outdoor

SiBE121135_A

229 Diagnosis Servis

Pemecahan masalah

Periksa

No.15 Lihat

Hal.236

Periksa

No.17 Lihat

Hal.238

Periksa

No.18 Lihat

Hal.238

Periksa

No.22 Lihat

Hal.240

Pastikan untuk mematikan saklar listrik sebelum menyambung atau memutuskan

Perhatian sambungan, atau kerusakan komponen dapat terjadi.

Arus output berlebih bisa disebabkan oleh pengkabelan internal yang salah. Jika sistem terganggu oleh arus output berlebih setelah kabel diputus atau disambung kembali untuk penggantian komponen, periksa kabelnya lagi.

Buka sepenuhnya katup penutup.

.

Perbaiki catu daya atau ganti PCB unit outdoor

Ganti PCB unit outdoor

Perbaiki catu daya.

Ganti kompresor.

(R18321)

Awasi tegangan catu daya, tekanan buang dan hisap, serta faktor lain dengan seksama.

Kemungkinan penyebab Tegangan catu daya turun

sementara Kelebihan kompresor Korsleting

Matikan daya dan lepas harness U, V, dan W.

Periksa No. 22 Periksa modul daya.

Periksa No. 17 Periksa kondisi pemasangan.

Katup penutup terbuka sepenuhnya?

TIDAK

YA

Matikan listrik dan nyalakan lagi untuk memulai kembali sistem. Perhatikan apakah terjadi kesalahan yang sama.

TIDAK Terjadi

kesalahan lagi?

YA

Periksa No.15 Periksa dengan penganalisa inverter

Penganalisa inverter RSUK0917C

YA Adakah LED mati?

TIDAK

TIDAK Normal?

YA

Matikan daya, dan sambungkan kembali harness. Nyalakan daya kembali dan mulai operasi.

Periksa tegangan catu daya.

TIDAK Tegangan

sesuai?

YA

Korsleting atau

kabel putus diantara fase kumparan

kompresor?

YA

TIDAK

Periksa No. 18 Periksa tekanan buang

Terus awasi Periksa konektor dan komponen lain.

SiBE121135_A Pemeriksaan

Diagnosis Servis 230

8. Pemeriksaan

Pemeriksaan Tahanan Termistor

Pemeriksaan No.01 Lepaskan konektor termistor dari PCB, dan ukur tahanan setiap termistor menggunakan

tester.

Hubungan antara suhu normal dan tahanan ditunjukkan dalam tabel dan grafik di bawah ini.

Data berikut hanya untuk tujuan referensi.

Suhu Termistor (°C)

Tahanan (k)

Termistor suhu ruangan untuk seri CTXS dan FTXS20/25K

Termistor lainnya

-20 73,4 197,8

-15 57,0 148,2

-10 44,7 112,1

-5 35,3 85,60

0 28,2 65,93

5 22,6 51,14

10 18,3 39,99

15 14,8 31,52

20 12,1 25,02

25 10,0 20,00

30 8,2 16,10

35 6,9 13,04

40 5,8 10,62

45 4,9 8,707

50 4,1 7,176

(R25°C = 10 k, B = 3435 K) (R25°C = 20 k, B = 3950 K)

(k)

50

25

Termistor suhu ruangan

untuk CTXS dan FTXS20/25K

(k)

150

100

50

Termistor lainnya

0

-15 0 15 30 45

(˚C)

-15 0 15 30 45

(˚C)

(11952)

Termistor suhu ruangan

(R17417)

(R18296)

Ketika termistor suhu ruangan dipasang langsung pada PCB, lepaskan PCB dari kendali

PCB untuk mengukur tahanan.

Ketika konektor termistor penukar panas indoor disolder pada PCB, lepaskan termistor

dan ukur tahanan.

Tester

Tester

Kisaran tahanan

Pemeriksaan

SiBE121135_A

231 Diagnosis Servis

Pin bebas

Pin bebas

Pin bebas

Pin bebas

Pin bebas

Pin bebas

Pemeriksaan Konektor Motor Kipas

Pemeriksaan No.02 Seri FTXG, FTXS35/42/50K, FTXS-J, FTXS-G, ATXS, FVXG, FVXS

1. Periksa sambungan konektor.

2. Periksa tegangan motor catu daya output (pin 4 - 7).

3. Periksa tegangan kendali motor (pin 4-3).

4. Periksa tegangan perintah rotasi (pin 4 - 2).

5. Periksa pulsa rotasi/putar (pin 4 - 1).

S1 atau

S200 7

6

5

4

3

2

1

Tegangan catu daya motor (310 ~ 340 VDC)

Tidak digunakan

Tidak

digunak

an

GND

Tegangan kendali motor (15 VDC)

Tegangan perintah rotasi (1~ 6.5 VDC)

Input pulsa rotasi

(R14225)

Pemeriksaan No.03 Seri CTXS, FTXS20/25K

Pemeriksaan kerusakan kabel motor kipas / korsleting

1. Periksa konektor sambungan.

2. Matikan daya.

3. Periksa apakah setiap tahanan di fase U - V dan V - W adalah 90 ~ 100 (antara pin 12 - 9, dan antara

9 - 6).

Pemeriksaan tegangan kendali motor

1. Periksa konektor sambungan.

2. Periksa tegangan kendali motor apakah ada (antara pin 3 - 3).

Pemeriksaan pulsa putar

1. Periksa konektor sambungan.

2. Nyalakan daya dan hentikan operasi.

3. Periksa apakah Hall IC menghasilkan pulsa putaran 4 kali saat motor kipas diputar sekali secara

manual (antara pin 1 - 3).

S200

12

11

10

9

8

7

6

5

4

3

2

Fase U

Fase V

Fase W

GND

Tegangan kendali motor (15 VDC)

1 Pulsa putaran (5 VDC)

(R11979)

SiBE121135_A Pemeriksaan

Diagnosis Servis 232

Pemeriksaan Hall IC

Pemeriksaan No.04 Seri FLXS, FDXS

1. Periksa konektor sambungan.

2. Dengan daya nyala, operasi mati, dan konektor tersambung, periksa hal berikut.

Tegangan output sekitar 5 V antara pin 1 dan 3.

Pembangkitan 3 pulsa antara pin 2 dan 3 saat motor kipas beroperasi.

Jika NG pada tahap 1 → PCB rusak → Ganti PCB.

Jika NG pada tahap 2 → Hall IC rusak → Ganti motor kipas.

Jika OK di kedua langkah 1 dan 2 → Ganti PCB.

S7

1 Abu-abu (catu daya)

2 Ungu (sinyal)

3 Biru (pembumian)

(R14211)

Pemeriksaan Kumpaan Katup Ekspansi Elektronik Indoor

Pemeriksaan No.06 Lakukan hal-hal berikut untuk memeriksa katup ekspansi elektronik indoor (EV).

1. Periksa apakah konektor EV tersambung dengan benar ke PCB.

2. Matikan dan nyalakan lagi dayanya, serta periksa apakah EV menimbulkan bunyi grendel.

3. Jika EV tidak menghasilkan bunyi grendel pada langkah 2 di atas, lepaskan konektor

dan periksa kelancaran menggunakan tester.

4. Periksa kelancaran antara pin 1 - 6, 2 – 6, 3 - 6, 4 – 6. Jika tidak ada kelancaran di

antara pin, berarti kumparan EV rusak.

5P Harness

S50 (konektor relai)

1 2 3 4 5 6

Pemeriksaan

6-1

6-2

6-3

6-4

(R15307)

5. Jika dipastikan lancar pada langkah 3, berarti PCB unit outdoor rusak.

Catatan: Harap dicatat bahwa suara gerendel bervariasi tergantung pada tipe katup.

(5)

Konektor 6P

Pemeriksaan

SiBE121135_A

233 Diagnosis Servis

Pemeriksaan Bentuk Gelombang Catu Daya

Pemeriksaan No.11 Mengukur bentuk gelombang catu daya antara No. 1 dan No. 2 di papan terminal dan periksa

gangguan bentuk gelombang.

Periksa apakah bentuk gelombang catu daya berupa gelombang sinus. (Gambar 1)

Periksa apakah gangguan bentuk gelombang dekat lintas nol. (Bagian

dilingkari di Gbr.2) [Gbr.1] [Gbr.2]

(R1736)

(R1444)

SiBE121135_A Pemeriksaan

Diagnosis Servis 234

Pemeriksaan Katup Ekspansi Elektronik Outdoor

Pemeriksaan No.12 Lakukan hal-hal berikut untuk memeriksa katup ekspansi elektronik outdoor (EV).

1. Periksa apakah konektor EV terpasang dengan benar ke PCB. Cocokkan nomor unit EV

dan nomor konektor.

2. Matikan dan nyalakan lagi dayanya, serta periksa apakah EV menimbulkan bunyi grendel.

3. Jika EV tidak menghasilkan bunyi grendel pada langkah 2 di atas, lepaskan konektor

dan periksa kelancaran menggunakan tester.

Periksa kelancaran antara pin 1 - 6, 3 - 6, 2 - 5, 4 - 5 (antara pin 1 - 5, 2 - 5, 3 - 5, 4 - 5

untuk model harness 5P). Jika tidak ada kelancaran di antara pin, berarti kumparan EV

rusak.

4. Jika EV tidak menghasilkan bunyi grendel pada langkah 2, berarti PCB unit outdoor rusak.

5. Jika dipastikan lancar pada langkah di atas 3, pasang kumparan yang baik (saat

menghasilkan suara grendel) di unit EV yang tidak menghasilkan suara grendel, dan

periksa apakah EV menghasilkan suara grendel.

Jika menghasilkan suara grendel, PCB unit outdoor rusak.

Jika tidak ada suara grendel, maka EV rusak.

Catatan: Harap dicatat bahwa suara gerendel bervariasi tergantung pada tipe katup.

Jika sistem terus beroperasi saat katup ekspansi elektronik outdoor rusak, masalah berikut

dapat terjadi.

Posisi bukaan katup

Kemungkinan masalah Metode pemeriksaan

Terbuka Pendinginan: Aliran kebisingan refrigeran di

unit yang tidak beroperasi kebocoran air di unit yang tidak

beroperasi Setengah operasi karena

fungsi anti-icing

Atur ulang catu daya dan lakukan pendinginan unit operasi dengan unit.

Periksa suhu pipa cair tanpa unit operasi.

Apakah hampir sama TIDAK dengan suhu EV tidak outdoor? rusak.

YA Ganti EV ruangan.

(R16019)

Pemanasan: Aliran kebisingan refrigeran di

unit yang tidak beroperasi Unit tidak memanaskan ruangan.

Tertutup Pendinginan: Unit bermasalah tidak

mendinginkan ruangan. Hanya unit bermasalah yang

dalam operasi, unit memulai pump down. (Tekanan rendah unit menjadi vakum.)

Suhu pipa buang tidak normal

Atur ulang catu daya dan lakukan pendinginan unit operasi dengan unit.

Periksa tekanan rendah.

Apakah tekanan TIDAK EV tidak menjadi zona

vakum? rusak.

YA Ganti EV

ruangan.

(R16020)

Pemanasan: kekurangan refrigeran karena

kebekuan refrigeran cair di dalam unit indoor rusak

Unit tidak memanaskan ruangan. Suhu pipa buang tidak

normal

Pemeriksaan

SiBE121135_A

235 Diagnosis Servis

Pemeriksaan Kinerja Katup Empat Arah

Pemeriksaan No.13

Ganti PCB unit outdoor.

Ganti kumparan katup empat arah.

Ganti katup empat arah.

(R11903)

(Gbr. 1)

Tegangan pada S80

220 - 240 VAC

Kompresor ON

Waktu

(R11904)

Pemeriksaan Sistem Refrigeran Unit Inverter

Pemeriksaan No.14

Sambungkan kembali termistor.

Ganti refrigeran.

(R15833)

Mulai operasi pemanasan

Matikan daya dan nyalakan kembali.

Kumparan katup empat arah Pendinginan/Kering : Tidak lancar Lancar

S80 tegangan sebesar 220 - 240 VAC dengan kompresor nyala? (Gbr.

1)

TIDAK

YA

Lepas kumparan katup empat arah dari konektor dan periksa kelancarannya.

Tahanan kumparan katup

empat arah sebesar 1000 ~

2000 ?

TIDAK

YA

Periksa kebocoran refrigeran. Lihat diagnosis servis pada kekurangan refrigeran.

Pemeriksaan sistem refrigeran

Apakah termistor pipa buang lepas dari pegangannya?

YA

TIDAK

SiBE121135_A Pemeriksaan

Diagnosis Servis 236

Kompresor

(1) Lepaskan terminal dari kompresor.

Pemeriksaan Penganalisa Inverter

Pemeriksaan No.15 Karakteristik

Penganalisa inverter RSUK0917C

Jika unit berhenti secara tidak normal karena kegagalan penyalaan kompresor atau output

arus berlebih saat menggunakan unit inverter, maka sulit untuk menilai apakah berhentinya itu

disebabkan oleh kegagalan kompresor atau kegagalan lainnya (PCB Utama, modul daya, dll).

Penganalisa inverter memungkinkan untuk menilai penyebab masalah dengan mudah dan

aman. (Sambungkan penganalisa inverter sebagai kompresor semu, bukannya kompresor,

dan periksa output dari inverter.)

Metode Operasi

Tahap 1

Pastikan untuk mematikan daya.

Tahap 2

Pasang penganalisa inverter, bukan kompresor.

Catatan:

Pastikan tegangan yang dibebankan dari kapasitor elektrolitik built-in smoothing turun

menjadi 10 VDC atau di bawahnya sebelum melaksanakan pekerjaan servis.

Penganalisa inverter

Referensi:

(R18322)

Jika terminal kompresor bukan terminal FASTON (sulit untuk melepas kawat pada terminal),

dimungkinkan untuk menghubungkan kabel yang ada di lokasi ke unit ourdoor dari sisi

output PCB. (Jangan menghubungkannya ke kompresor pada saat yang bersamaan, atau

akan menyebabkan deteksi yang salah.)

Tahap 3

Aktifkan operasi uji transistor daya dari unit indoor.

1) Tekan saklar [ON/OFF] operasi paksa selama 5 detik.

(Lihat hal 243 untuk penjelasan posisi.)

memulai operasi uji transistor daya.

Hati-hati jangan biarkan terminal (U,V,W) saling bersentuhan. Jika tidak akan terjadi tegangan tinggi.

(2) Sambungkan terminal keterminal penganalisa inverter.

Pemeriksaan

SiBE121135_A

237 Diagnosis Servis

Metode Diagnosis (Diagnosis berdasarkan status nyala 6 LED.)

(1) Jika semua LED menyala seragam, kompresor rusak.

(2) Jika LED tidak menyala seragam, periksa modul daya.

Pemeriksaan No.22.

(3) Jika NG pada Pemeriksaan No.22, ganti modul daya.

(Ganti PCB Utama. Modul daya menyatu dengan PCB Utama.) Jika OK

pada pemeriksaan No.22, periksa apakah ada solder retak pada PCB.

(4) Jika ditemukan solderan retak, ganti PCB atau perbaiki bagian yang disolder.

Jika tidak ada retakan solder, ganti PCB.

Perhatian

(1) Ketika frekuensi output rendah, LED berkedip perlahan. Saat frekuensi output meningkat,

LED berkedip lebih cepat. (LED terlihat seperti menyala)

(2) Setelah penyelesaian diagnosis penganalisa inverter, pastikan untuk men-crimp kembali

terminal FASTON. Jika tidak, terminal dapat terbakar karena pengenduran.

Arah crimp

Ukuran ini

dikencangkan dengan

alat crimp.

Terminal FASTON

(R15292)

Pemeriksaan Pulsa Rotasi pada PCB Unit Outdoor

Pemeriksaan No.16 <Motor kipas outdoor>

Pastikan memakai tegangan 320 ± 30 V.

1. Mengatur operasi off dan daya off. Lepaskan konektor S70.

2. Periksa tegangan antara pin 4 - 7 adalah 320 VDC.

3. Periksa bahwa tegangan kendali antara pin 3 - 4 adalah 15 VDC.

4. Periksa bahwa tegangan perintah putar antara pin 2 - 4 adalah 0 ~ 15 VDC.

5. Jaga operasi off dan daya off. Sambungkan konektor S70.

6. Periksa apakah 2 pulsa (0 ~ 15 VDC) adalah output pada pin 1 - 4 saat motor kipas

diputar 1 putaran dengan tangan.

Ketika Sekring meleleh, periksa motor kipas outdoor untuk fungsi yang tepat.

Jika NG pada tahap 2 PCB rusak Ganti PCB.

Jika NG pada tahap 4 Hall IC rusak Ganti motor kipas outdoor.

Jika OK di kedua langkah Ganti PCB.

Unit Outdoor

Output pulsa putaran aktual (0 ~ 15 VDC)

Input pulsa perintah putaran (0 ~ 15 VDC)

15 VDC

320 VDC

(R10811)

S70

1

2

3

4

5

6

7

SiBE121135_A Pemeriksaan

Diagnosis Servis 238

Pemeriksaan Kondisi Pemasangan

Pemeriksan No.17

Ganti lokasi atau arah pemasangan.

Ganti lokasi atau arah pemasangan.

Bersihkan penukar panas outdoor.

Ganti lokasi atau arah pemasangan.

Periksa suhu outdoor. (Suhu outdoor harus berada dalam kisaran operasi.)

(R17537)

Pemeriksaan Tekanan Buang

Pemeriksaan No.18

Ganti kompresor.

Buka Katup penutup.

Ganti pipa yang terpasang di lokasi.

Bersihkan filter udara atau penukar panas indoor/outdoor yang kotor.

Ganti kompresor.

(R15738)

Pemeriksaan kondisi pemasangan

Periksa dimensi yang dibolehkan untuk area hisap dan area buang

udara

NG

OK

Apakah ada hubungan singkat pada udara yang dibuang?

YA

TIDAK

Apakah penukar panas outdoor sangat kotor?

YA

TIDAK

Apakah aliran udara terhalang rintangan

atau angin yang bertiup dengan arah

berlawanan?

YA

TIDAK

Pemeriksaan tekanan buang

Tinggi?

TIDAK

YA

TIDAK Apakah katup penutup

terbuka?

YA

Apakah pipa penghubung rusak?

YA

TIDAK

Apakah filter udara atau penukar

panas indoor/outdoor kotor?

Tidak kotor

Kotor

Pemeriksaan

SiBE121135_A

239 Diagnosis Servis

tester

N(–) P(+) Lapisan

PCB

Periksa sistem kipas outdoor

TIDAK Apakah kipas outdoor

berjalan?

Konektor kabel timah motor kipas terlepas?

YA TIDAK

Sistem kipas outdoor berfungsi.

Harap Periksa No. 16

Pemeriksaan Sistem Kipas Outdoor

Pemeriksaan No.15

YA Sambung kembali konektro.

(R15128)

Pemeriksaan Tegangan Kapasitor

Pemeriksaan No.21 Sebelum pemeriksaan ini, pastikan untuk memeriksa sirkuit utama mengenai korsleting.

Dengan pemutus sirkuit masih nyala, ukur tegangan sesuai dengan gambar model yang

bersangkutan. Hati-hati jangan menyentuh komponen langsung.

Multimeter

(DC. kisaran tegangan)

Untuk mencegah sengatan listrik, gunakan tester untuk memeriksa bahwa tegangan

antara P (+) dan N (-) adalah 50 V atau kurang.

Permukaan titik uji (P, N) dapat ditutupi dengan lapisan. Pastikan untuk melakukan kontak

langsung antara ujung pengukur tester dan titik uji.

Ujung pengukur

g

.

(R12869)

SiBE121135_A Pemeriksaan

Diagnosis Servis 240

Pemeriksaan Modul Daya

Pemeriksaan No.22

Catatan: Periksa untuk memastikan bahwa tegangan antara (+) dan (-) pada modul daya (PM1) sekitar

0 V sebelum memeriksa.

Putus konektor harness kompresor dari PCB unit outdoor. Untuk melepaskan konektor,

tekan tonjolan pada konektor.

Ikuti prosedur di bawah ini untuk mengukur tahanan antara terminal pada modul daya

dan terminal kompresor dengan multi-tester. Evaluasi hasil pengukuran berdasarkan

tabel berikut.

Terminal negatif (-) tester (terminal positif (+) untuk digital tester)

Modul daya (+) UVW Modul daya (-) UVW

Terminal positif (+) tester (terminal negatif (-) untuk digital tester)

UVW Modul daya (+) UVW Modul daya (-)

Tahanan OK. beberapa k ~ beberapa M

Tahanan NG. 0 atau

Ilustrasi perwakilan adalah untuk kelas 40/50/52/58.

Modul daya (PM1)

(R16074)

241 Operasi Uji coba dan Pengaturan bidang

SiBE121135_A Operasi Pump Down (Penampungan)

Bagian 7

Operasi Uji Coba

dan Pengaturan

bidang

1. Operasi Pump Down (Penampungan) .................................................. 242

2. Operasi Paksa........................................................................................ 243

3. Fungsi Pemeriksaan Kesalahan Pengkabelan .................................... 244

4. Operasi Uji coba .................................................................................... 246

Unit Indoor RA ........................................................................................... 246

Unit Indoor SA ........................................................................................... 248

5. Pengaturan bidang ................................................................................ 250

Unit Outdoor .............................................................................................. 250

Unit Indoor RA ........................................................................................... 253

Unit Indoor SA ........................................................................................... 258

6. Pelumas Silikon pada Transistor Daya / Jembatan Dioda .................. 262

SiBE121135_A

Operasi Uji coba dan Pengaturan bidang

242

Tutup

1. Operasi Pump Down (Penampungan)

Uraian Untuk melindungi lingkungan, pastikan untuk melakukan operasi pump down ketika

memindahkan atau membuang unit.

Rincian 1) Lepaskan tutup katup dari katup penutup cairan dan katup penutup gas.

2) Lakukan operasi pendinginan paksa.

3) Setelah 5 sampai 10 menit, tutup katup penutup cairan dengan Kunci heksagonal (kuncil L) .

4) Setelah 2 sampai 3 menit, tutup katup penutup gas dan hentikan operasi pendinginan paksa.

Katup penutup gas Kunci heksagonal (kuncil L)

Katup penutup cairan Tutup katup

Lihat hal 243 untuk operasi paksa.

(R14566)

243 Operasi Uji coba dan Pengaturan bidang

SiBE121135_A Fungsi Pemeriksaan Kesalahan Pengkabelan

2. Operaksi Paksa

Uraian Mode operasi paksa meliputi pendinginan paksa dan pemanasan paksa. Mode operasi

dapat dipilih oleh saklar mode operasi (SW2) pada unit outdoor. Tekan saklar (SW1)

[ON/OFF] operasi paksa pada unit outdoor untuk memulai operasi.

Rincian

Item Pendinginan Paksa Pemanasan Paksa Kondisi 1) Unit indoor normal, tetapi unit indoor

yang tidak ada di zona larangan pembekuan berada lebih dari 1 ruangan.

1) Unit indoor normal. Unit indoor yang tidak ada pada zana larangan pemutusan puncak berada lebih dari 1 ruangan.

2) Unit outdoor tidak normal dan tidak dalam mode siaga 3 menit.

3) Mode operasi unit outdoor dalam mode berhenti.

4) Saklar (SW2) mode operasi pada unit outdoor diatur ke mode pendinginan.

4) Saklar (SW2) mode operasi pada unit outdoor diatur ke mode pemanasan.

Awal Tekan saklar (SW1) [ON/OFF] operasi paksa pada unit outdoor.

Ruangan operasi Semua ruangan: Perintah dikirim ke semua ruangan di mana transmisi adalah normal.

Hanya 1 ruangan: Perintah dikirim ke salah satu ruangan yang dapat beroperasi dan urutan prioritas adalah A> B> C> D> E. Ruangan operasi lainnya harus dihentikan.

Frekuensi perintah

• Kelas 40/50/52/58 : 52 Hz • Kelas 68/75 : 42 Hz • Kelas 80/90 : 31 Hz

(Suhu outdoor : 2°C) • Kelas 40/50/52/58 : 42 Hz • Kelas 68/75 : 35 Hz • Kelas 80/90 : 26 Hz

Akhir Tekan saklar (SW1) [ON/OFF] operasi paksa pada unit outdoor lagi.

2) Operasinya berakhir secara otomatis setelah 15 menit.

2) Operasinya berakhir secara otomatis setelah 60 menit.

Lainnya Fungsi perlindungan mendapatkan prioritas dibanding semua fungsi lainnya selama operasi pendinginan paksa

(R17811)

Ilustrasi perwakilan adalah untuk

model 4-ruangan. PCB Monitor Servis

Saklar (SW2) mode

operasi

Saklar (SW1) ON/OFF

Operaksi paksa

Operasi Uji coba dan Pengaturan bidang

244

Operaksi Paksa SiBE121135_A

3. Fungsi Pemeriksaan Kesalahan Pengkabelan

Uraian Fungsi pemeriksaan kesalahan pengkabelan yang baik dirancang untuk mikrokomputer untuk

memperbaiki kesalahan kabel itu sendiri.

Jika kesalahan pengkabelan setempat tidak jelas karena pipa terkubur, misalnya, cukup tekan

saklar pemeriksaan kesalahan pengkabelan yang ada di balik penutup katup penutup dari unit

outdoor. Bahkan jika sambungan untuk Ruang A dan Ruang B membingungkan, sistem dapat

berjalan tanpa mengalami kerumitan. Perhatikan bahwa fungsi pemeriksaan ini tidak bekerja

dalam kasus berikut.

Untuk periode siaga 3 menit setelah daya dihidupkan atau setelah kompresor telah

berhenti.

Ketika suhu outdoor di bawah 5°C. Jika unit indoor mengalami masalah (juga dalam kasus kegagalan

transmisi semua ruangan). Ketika perpipaan dan pengkabelan baik, maka

tidak perlu menggunakan fungsi ini.

Operasi 1. Lepaskan penutup katup penutup.

2. Tekan saklar (SW3) pemeriksaan kesalahan pengkabelan pada PCB monitor servis dari

unit outdoor, dan fungsi pemeriksaan kesalahan pengkabelan diaktifkan.

3. Selama sekitar 10 ~ 20 menit, pemeriksaan selesai secara otomatis. 4. Ketika pemeriksaan berakhir, indikator LED monitor servis mulai berkedip.

LED 1 2 3 4 5 Penilaian

Status Semua berkedip sekaligus Perbaikan sendiri tak mungkin Berkedip satu per satu Perbaikan sendiri selesai

Perbaikan sendiri selesai ... Indikator LED 1 ~ 3 (model 3 ruangan), 1 ~ 4 (model 4-

ruangan), atau 1 ~ 5 (model 5-ruangan) berkedip satu per satu.

Perbaikan sendiri tak mungkin ... indikator LED berkedip semua pada saat bersamaan. Kegagalan transmisi terjadi di salah satu unit indoor.

Termistor penukar panas unit indoor terputus.

Unit indoor bermasalah (jika gangguan terjadi selama pemeriksaan kesalahan pengkabelan).

Berhenti darurat ... Salah satu indikator LED tetap menyala.

Catatan: 1. Pipa cair dan gas yang tersambung salah tidak dapat melakukan perbaikan sendiri. Pastikan

untuk menjadikan pipa cairan

dan pipa gas berpasangan. 2. Untuk membatalkan prosedur pemeriksaan kesalahan pengkabelan di tengah jalan,

tekan saklar pemeriksaan kesalahan pengkabelan lagi.

Dalam hal ini, memori mikrokomputer akan kembali ke status awal (pengkabelan Ruang A

perpipaan Port A, pengkabelan Ruang B perpipaan Port B). 3. Saat mengganti PCB unit outdoor, pastikan untuk menggunakan fungsi ini. 4. Buat pengaturan ruang prioritas setelah pemeriksaan kesalahan pengkabelan. Jika

Anda mengatur ruang prioritas sebelum pemeriksaan kesalahan pengkabelan, ruang

yang diprioritaskan dapat berubah setelah perbaikan sendiri.

PCB Monitor Servis

Saklar

pemeriksaan

kesalahan

pengkabelan

(SW3)

(R12871)

245 Operasi Uji coba dan Pengaturan bidang

SiBE121135_A Operasi Uji coba

Pengetahuan Mendasar Refrigeran mengalir dari Port A dan menyala. Suhu termistor penukar panas indoor

dideteksi satu persatu untuk memeriksa kecocokan antara perpipaan dan pengkabelan.

Dengan fungsi ini, suara kebekuan (keretakan) dapat didengar dari unit indoor. Ini bukan

masalah. (Hal ini karena suhu penukar panas dibuat untuk turun di bawah 0°C guna

meningkatkan akurasi deteksi.)

Kipas indoor dinyalakan atau dimatikan pada saat bersamaan.

Memeriksa

data

pengaturan

saat ini pada

memori

mikrokomputer

Data tersebut dapat diperiksa dengan melihat indikator LED monitor servis, saat pemeriksaan

kesalahan pengkabelan berakhir, selama operasi paksa, di pemberhentian sistem.

Indikator LED berhenti berkedip ketika operasi dipaksa berakhir. LED1 ...

pengkabelan Ruang A, LED2 ... pengkabelan Ruang B

LED berkedip ke-1 ... perpipaan Port A, LED 2 berkedip ke-2 ... perpipaan Port B

LED berkedip ke-1 berarti ruangan terhubung dengan Port A. LED berkedip ke-2 berarti

satunya terhubung dengan Port B.

Contoh: Contoh: Misal indikator LED berkedip sebagai berikut.

(R8252)

Maksud di atas adalah Port A terhubung dengan Port B, Port B dengan Ruang A (atau

diperbaiki sendiri dengan cara ini.)

(R8253)

A

Pengkabelan

B

Perpipa

an A B

Pengkabelan

Perpipaan

L A 1 2 3 4

E

D Hijau Merah

L A 1 2 3 4

E

D Hijau Merah

L A 1 2 3 4

E

D Hijau Merah

Operasi Uji coba dan Pengaturan bidang

246

Fungsi Pemeriksaan Kesalahan Pengkabelan

SiBE121135_A

4. Operasi Uji coba

4.1 Unit Indoor RA

Uraian 1. Ukur tegangan catu daya dan pastikan bahwa tegangannya berada dalam kisaran yang ditentukan.

2. Operasi uji coba harus dilakukan baik operasi pendinginan atau pemanasan.

Dalam operasi pendinginan, pilih suhu pemrograman terendah; dalam operasi pemanasan,

pilih pemrograman suhu tertinggi.

Operasi uji coba mungkin tidak dapat dilakukan pada salah satu mode operasi

bergantung pada suhu ruangan.

Setelah operasi uji coba selesai, atur suhu ke tingkat normal. (26°C ~

28°C dalam pendingan, 20°C ~ 24°C dalam pemanasan)

Untuk perlindungan, sistem tidak menyala selama 3 menit setelah dimatikan.

3. Lakukan operasi uji coba sesuai dengan panduan operasi untuk memastikan bahwa

semua fungsi dan komponen, seperti gerakan sirip, bekerja dengan benar.

Catatan: AC memerlukan sedikit daya dalam mode siaganya. Jika sistem tidak digunakan untuk

beberapa waktu setelah pemasangan, matikan pemutus sirkuit untuk menghilangkan

konsumsi daya yang tidak perlu.

Jika pemutus sirkuit berlanjut mematikan daya pada AC, sistem mem-back up

(mencadangkan) mode operasi. Sistem kemudian memulai ulang operasi dengan mode

operasi sebelumnya ketika pemutus sirkuit dipulihkan.

Rincian Seri ARC466

(1) Tekan tombol [ON/OFF] untuk menyalakan sistem.

(2) Tekan bagian tengah Tombol [Temp] dan tombol [Mode] pada saat bersamaan.

(3) Pilih T (operasi uji coba) dengan tombol ▲atau ▼ [Temp].

(4) Tekan tombol [Mode] untuk memulai operasi uji coba.

(5) Tekan tombol [Mode] dan pilih mode operasi.

(6) Operasi uji coba berakhir sekitar 30 menit dan beralih ke mode normal. Untuk keluar dari

operasi uji coba, tekan tombol [On/Off].

(3)

(2) (3)

(2) (4) (5) (1) (6) (R11676)

247 Operasi Uji coba dan Pengaturan bidang

SiBE121135_A Operasi Uji coba

Seri ARC452

(1) Tekan tombol [ON/OFF] untuk menyalakan sistem.

(2) Tekan kedua Tombol [Temp] dan tombol [Mode] pada saat bersamaan.

(3) Tekan tombol [MODE] dua kali.

(T muncul di layar untuk menunjukkan bahwa operasi uji coba dipilih.)

(4) Tekan tombol [Mode] dan pilih mode operasi.

(5) Operasi uji coba berakhir sekitar 30 menit dan beralih ke mode normal. Untuk keluar dari

operasi uji coba, tekan tombol [On/Off].

(3)

(2)

(2)

(2) (3) (4) (1) (5) (R14594)

Seri ARC433

(1) Tekan tombol [ON/OFF] untuk menyalakan sistem.

(2) Tekan bagian tengah Tombol [Temp] dan tombol [Mode] pada saat bersamaan.

(3) Tekan tombol [MODE] dua kali.

(T muncul di layar untuk menunjukkan bahwa operasi uji coba dipilih.)

(4) Tekan tombol [Mode] dan pilih mode operasi.

(5) Operasi uji coba berakhir sekitar 30 menit dan beralih ke mode normal. Untuk keluar dari

operasi uji coba, tekan tombol [On/Off].

(3)

(2)

(1) (5)

(2) (3) (4) (R9663)

Operasi Uji coba dan Pengaturan bidang

248

Operasi Uji coba

SiBE121135_A

Unit Indoor SA Poin pemeriksaan

Untuk melakukan operasi uji, periksa hal berikut:

Periksa pengaturan suhu remote kontrol yang berada pada tingkat terendah dalam mode

pendinginan.

Lakukan melalui daftar berikut:

Poin pemeriksaan Perhatian dan peringatan

Apakah semua unit telah terpasang dengan kencang? Berbahaya mengencangkan selama angin topan Kemungkinan kerusakan pada

sambungan pipa Apakah kawat bumi terpasang sesuai dengan standar lokal yang berlaku?

Berbahaya jika kebocoran listrik terjadi.

Apakah semua inlet dan outlet udara dari unit indoor dan outdoor terhalang?

Pendinginan buruk Pemanasan buruk

Apakah pengurasan mengalir lancar? Kebocoran air

Apakah perpipaan terisolasi panas dengan memadai? Kebocoran air

Apakah sambungan sudah diperiksa mengenai kebocoran refrigeran?

Pendinginan buruk Pemanasan buruk Hentikan

Apakah tegangan catu daya sesuai dengan spesifikasi pada pelat nama?

Operasi salah

Apakah ukuran kabel sesuai spesifikasi dan sesuai dengan peraturan lokal?

Kerusakan kabel

Apakah sinyal remote kontrol diterima oleh unit? Tidak ada operasi

Operasi Uji

BRC1D528

Langkah

Tindakan

1 Hidupkan catu daya lebih dari 6 jam sebelum operasi uji.

2 Buka Katup penutup gas.

3 Buka Katup penutup cairan.

4 Atur ke operasi pendinginan dengan remote kontrol dan mulai operasi dengan menekan tombol [ON/OFF] ( ).

5 Tekan tombol [INSPECTION/TEST OPERATION] ( ) 4 kali (2 kali untuk

remote kontrol nirkabel) dan operasikan pada mode operasi uji selama 3 menit. 6 Tekan tombol [AIRFLOW DIRECTION ADJUST] ( ) untuk memastikan unit masih beroperasi.

7 Tekan tombol[INSPECTION/TEST OPERATION] ( ) dan beroperasi normal.

8 Pastikan semua fungsi unit sesuai dengan panduan operasi.

9 Jika panel dekorasi belum dipasang, matikan daya setelah operasi uji.

249 Operasi Uji coba dan Pengaturan bidang

SiBE121135_A Operasi Uji coba

BRC1E52A7,

BRC1E52B7

Langkah Tindakan Pengaturan remote

Sebelum operasi uji

1 Hidupkan catu daya lebih dari 6 jam sebelum operasi uji.

2 Buka Katup penutup gas.

3 Buka Katup penutup cairan.

Cara mengaktifkan operasi uji

4 Tekan dan tahan tombol [Cancel] ( ) selama 4 detik untuk masuk ke menu Pengaturan bidang.

5 Gunakan tombol ▼▲ untuk memilih Test operation ON/OFF dan tekan tombol [Menu/

Enter] ( ).

(R12872)

6 Test operation ditampilkan di bagian bawah layar dasar.

(R12873)

7 Tekan tombol [ON/OFF] ( ) dalam waktu 10 detik untuk memulai operasi uji.

Cara memeriksa arah aliran udara

8 Tekan tombol [Menu/Enter] ( ) untuk masuk ke Main Menu.

9 Gunakan tombol ▼▲ untuk memilih Airflow direction/Arah aliran udara dan tekan tombol

[Menu/ Enter] ( ).

(R12874)

10 Periksa arah aliran udara yang bergerak sesuai dengan pengaturan dan tekan tombol [Menu/ Enter] ( ).

(R12875)

Cara menonaktifkan operasi uji

11 Tekan dan tahan tombol [Cancel] ( ) selama 4 detik untuk masuk ke menu Pengaturan bidang.

12 Gunakan tombol ▼▲ untuk memilih ON/OFF Operasi Uji dan tekan tombol [Menu/ Enter] (

).

(R12876)

SiBE121135_A Pengaturan bidang

Operasi Uji coba dan Pengaturan bidang

250

5. Pengaturan bidang

Unit Outdoor Pengaturan Ruang Prioritas

Katup ekspansi elektronik outdoor dikendalikan untuk menyediakan lebih banyak kapasitas

untuk ruang yang diprioritaskan.

Metode pengaturan

Matikan pemutus sirkuit sebelum mengubah pengaturan.

Hanya satu ruangan yang dapat diatur sebagai ruang prioritas (Dengan mengaktifkan salah

satu SW4 pada PCB monitor servis unit outdoor).

Kendali dimulai ketika semua kondisi berikut ini terpenuhi.

Pengaturan ruang prioritas telah dibuat.

Sinyal "POWERFUL" dari unit ruang prioritas diterima.

Catatan: Mode operasi unit ruang prioritas didahulukan.

Pembatalan kendali

Fungsi Kendali dibatalkan ketika mode operasi "POWERFUL" dimatikan atau 20 menit jeda

setelah "Operasi POWERFUL" dimulai.

A Ruang

Ruang tamu

Ruang B

Ruang C

Ketika operasi kuat inverter dipilih di ruang prioritas

Ruang yang diprioritaskan akan dipanaskan/ didinginkan lebih cepat (R1396)

PCB monitor servis PCB monitor servis

Ruang prioritas

Saklar pengaturan (SW4)

Ruang prioritas Saklar pengaturan (SW4)

Model 3 atau 4 ruangan

(R17271) Model 5 ruangan (R17272)

Ruang A

Ruang tamu

Ruang B

Ruang C

Operasi normal

Pengaturan bidang

SiBE121135_A

251 Operasi Uji coba dan Pengaturan bidang

Kunci Mode SEJUK/PANAS

Uraian Gunakan konektor [S15] untuk mengatur unit ke pendinginan saja atau pemanasan saja.

Pengaturan ke pemanasan saja (H): Pin arus pendek 1 dan 3 dari konektor

[S15]. Pengaturan ke pendinginan saja (C): Pin arus pendek 3 dan 5 dari

konektor [S15]. Spesifikasi berikut berlaku untuk rumahan dan pin

konektor.

Produk JST:

Rumahan: VHR-

5N

Pin: SVH-21T-1, 1

Perhatikan bahwa operasi paksa juga memungkinkan dalam mode pendinginan/ pemanasan.

Rincian

Ilustrasi perwakilan adalah untuk

model 4-ruangan.

Mode

Mode DINGIN (C)

(R17814)

1 3 5

Tampilan tanda panah A

Kelas 40/50/52/58 A

PCB Utama

A Kelas 68/75/80/90

PCB Utama

A

PANAS (H)

SiBE121135_A Pengaturan bidang

Operasi Uji coba dan Pengaturan bidang

252

Mode NIGHT QUIET (Mode Senyap Malam)

Uraian Jika mode NIGHT QUIET digunakan, pengaturan awal harus dilakukan saat unit dipasang.

Menjelaskan fungsi mode QUIET NIGHT, seperti dijelaskan di bawah, ke pelanggan, dan

mengkonfirmasi apakah ia atau tidak pelanggan ingin menggunakan Mode QUIET NIGHT.

Fungsi mode NIGHT QUIET mengurangi kebisingan operasi unit outdoor di malam hari. Fungsi

ini berguna jika pelanggan khawatir tentang efek dari kebisingan operasi ke tetangga. Namun,

jika mode NIGHT QUIET berjalan, kapasitas pendinginan berkurang.

Rincian 1. Lepas saklar jumper SW5 pada PCB monitor servis dari unit outdoor.

Setelah pengaturan selesai, atur ulang daya.

PCB Monitor Servis

Mode NIGHT QUIET

Saklar pengaturan (SW5)

(R17815)

2. Pasang saklar jumper yang dilepas seperti yang dijelaskan di bawah ini. Saklar jumper

diperlukan nanti untuk menonaktifkan pengaturan ini.

Saklar Jumper Setelah melepas

(R10813)

Pengaturan anti mode ECONO

Uraian Anda dapat membuat mode ECONO tidak efektif pada unit outdoor.

Operasi Mode ECONO dapat dialihkan antara "efektif" dan "tidak efektif" dengan menekan saklar

(SW1) [ON/OFF] operasi paksa pada unit outdoor dan saklar pemeriksaan kesalahan

pengkabelan (SW3) pada unit outdoor pada saat yang sama dan menahannya selama 5

detik saat kompresor dihentikan. LED menyala secara bergantian selama 15 detik untuk

menunjukkan status mode ECONO.

Pengaturan pabrik adalah "efektif".

Urutan kedipan LED

efektif tidak efektif tidak efektif efektif

Model 3 atau 4 ruangan

4 3 2 1 1 2 3 4

Model 5 ruangan 5 4 3 2 1 1 2 3 4 5

Pengaturan bidang

SiBE121135_A

253 Operasi Uji coba dan Pengaturan bidang

Unit Indoor RA Pengaturan Tipe Model

ARC466A6, ARC466A9

Remote kontrol ini biasanya untuk model pompa kalor dan model pompa pendinginan saja.

Operasi pemanasan tidak akan tersedia ketika jumper di sisi kiri dipotong. Ganti remote kontrol

jika Anda memotong jumper di sisi kiri.

(R18451)

ARC452A1, ARC452A3

Remote kontrol ini biasanya untuk model pompa kalor dan model pompa pendinginan saja.

Pastikan saklar DIP diatur ke sisi yang benar. Operasi pemanasan tidak akan

tersedia ketika saklar DIP diatur ke sisi kanan.

Ketika 2 Unit dipasang dalam 1 Ruangan

Uraian Ketika 2 unit indoor dipasang di dalam 1 ruang, 1 dari 2 unit indoor dan remote kontrol

nirkabel yang sesuai dapat diatur untuk alamat yang berbeda.

PCB unit indoor dan remote kontrol nirkabel perlu diubah.

Metode pengaturan alamat bervariasi tergantung pada tipe unit indoor dan serangkaian remote

kontrol kabel. Merujuk pada halaman berikut untuk unit indoor dan remote kontrol nirkabel

yang tepat.

Tipe Wall

Mounted (1) Lepas grill depan.

(2) Lepas kotak listrik.

(3) Lepas pelat pelindung dari kotak listrik.

(4) Potong jumper pengaturan alamat JA pada PCB.

Jangan pernah memotong jumper ini.

Saklar DIP

H/P C/O (R12755)

SiBE121135_A Pengaturan bidang

Operasi Uji coba dan Pengaturan bidang

254

Seri FTXG CTXS, FTXS20/25K

JA ADDRESS EXIST 1 CUT 2

(Bagian bawah kotak listrik) (R16497)

(R12036)

Seri FTXS35/42/50K, FTXS-J, ATXS Seri FTXS-G

ADDRESS

JA

JB

JA

JC

JA

EXIST CUT

ADDRESS 1 2

(R11735)

(R12216)

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper yang salah. Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

Tipe Floor

Standing Seri FVXG

(1) Lepas panel depan, filter udara dan grill depan.

(2) Lepaskan sekrup, dan lepas penutup servis.

Penutup servis

(R14629)

ADDR

ESS

AD

DR

ES

S :

JA

EX

IST

: 1

CU

T :

2 JA

AD

DR

ES

S:J

A

EX

IST

1

CU

T

2

JA

JB

JC

Pengaturan bidang

SiBE121135_A

255 Operasi Uji coba dan Pengaturan bidang

JC JA JB

2)

Pelat pemasangan PCB sensor

Pelat pelindung depan

Pelat pelindung

(3)Nyalakan saklar DIP [S2W-1] pada PCB servis.

(R14630)

Pertahankan saklar lain sebagaimana pengaturan pabrik (OFF).

Seri FVXS

1) Lepas grill depan.

2) Angkat pelat pemasangan PCB sensor dan lepas pelat pelindung depan.

3) Lepas konektor [S1] [S41] [S42].

4) Lepas kotak listrik (1 sekrup).

5) Cabut termistor penukar panas indoor.

6) Lepas pelat pelindung (8 tab).

7) Potong jumper pengaturan alamat JA pada PCB unit indoor.

Konektor [S42]

5) Termistor penukar

panas indoor

Konektor [S41] 3)

Konektor [S1]

4) Lepas sekrup.

JA Alamat

EXIST 1

CUT 2

6)

(R17290)

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper yang salah. Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

PCB Servis

ON

1 2 3 4

OFF

SiBE121135_A Pengaturan bidang

Operasi Uji coba dan Pengaturan bidang

256

JB JC

Tipe Floor /

Ceiling

Suspended Dual

Potong jumperJA pada PCB.

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper yang salah.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

Tipe Duct

Connected Potong jumperJA pada PCB.

(R17876)

Perhatian Ganti PCB jika Anda secara tidak sengaja memotong jumper yang

salah.

Jumper diperlukan untuk sirkuit elektronik. Operasi yang tidak tepat dapat terjadi jika Anda

memotong salah satu darinya.

Remote Kontrol

Nirkabel (1) Lepas penutup dan keluarkan.

(2) Potong jumper pengaturan alamat.

Seri ARC466 series Seri ARC452

ADDRESS EXIST 1 CUT 2

Jangan memotong jumper kiri.

Seri ARC433

(R18416)

(R6573)

Jumper

(R11732)

A D D R E S S J A

1 2 3

ADDRESS : JA

EXIST 1 CUT 2

Jumper

(R12065)

Jumper

ADDRESS JA

EXIST 1

CUT 2

ADDRESS EXIST 1 CUT 2

ADDRESS EXIST 1 CUT 2

Pengaturan bidang

SiBE121135_A

257 Operasi Uji coba dan Pengaturan bidang

Pengaturan Jumper dan Saklar

Jumper (pada PCB unit indoor)

Fungsi Saat tersambung (pengaturan pabrik)

Saat dipotong

JB Pengaturan kecepatan kipas saat kompresor berhenti karena termostat OFF. (hanya efektif pada operasi pendinginan)

Pengaturan kecepatan kipas ; Pengaturan remote kontrol

Pengaturan kecepatan kipas ;"0" (kipas berhenti)

JC Fungsi pemulihan kegagalan daya

Auto-restart Unit tidak melanjutkan operasi setelah pulih dari kegagalan daya. Pengaturan Timer dihapus.

<Tipe Floor Standing: Seri FVXS>

Saklar (pada PCB unit indoor)

Fungsi OFF (pengaturan pabrik)

ON

SW2-4 Pengaturan batas aliran udara ke atas

Pemasanagn menempel atau setengah tertanam

Atur saklar ke posisi ON saat Anda memasang unit indoor yang tertanam di dinding untuk menghindari kondensasi.

<Tipe Floor / Ceiling Suspended Dual>

Saklar (pada PCB unit indoor)

Fungsi LANTAI (pengaturan

pabrik)

LANGIT-LANGIT

SW2 Perubahan gaya pemasangan

Ketika dipasang sebagai tipe floor mounted

Ketika dipasang sebagai tipe ceiling suspended

Untuk lokasi jumper dan saklar, lihat halaman berikut.

FTXG25/35/50JV1BW(A): hal 47 CTXS15/35/K2V1B,

FTXS20/25K2V1B: hal 49

FTXS35/42/50K2V1B, FTXS25/35/42/50J2V1B, ATXS20/25/35/42/50G2V1B: hal 51

FTXS60/71GV1B: hal 53

FVXG25/35/50K2V1B: hal 55

FVXS25/35/50FV1B: hal 57

FLXS25/35/50/60BAVMB: hal 59 FDXS25/35E7VMB,

FDXS50/60C7VMB: hal 61

SiBE121135_A Pengaturan bidang

Operasi Uji coba dan Pengaturan bidang

258

(4)

(3)

(1) (7)

Unit Indoor SA Cara Mengubah Pengaturan Bidang

Uraian Jika aksesori pilihan dipasang di unit indoor, pengaturan unit indoor mungkin harus diubah.

Lihat buku panduan untuk setiap aksesori pilihan.

Remote

Kontrol

Kabel

BRC1D528

No. Unit

No. kode kedua

No. kode pertama

No. Mode

Mode pengaturan bidang

(6) (5) (2)

(R14595)

Untuk menetapkan pengaturan bidang, Anda harus mengubah:

No. Mode

No. kode pertama

No. kode kedua

Langkah Tindakan

1 Tekan tombol [INSPECTION/TEST OPERATION] selama 4 detik selama mode

normal untuk masuk ke mode pengaturan bidang.

2 Tekan tombol [TEMPERATURE ADJUST] untuk memilih No. mode yang diinginkan 3 Jika unit indoor di bawah kendali kelompok, semua pengaturan untuk semua

unit indoor diatur pada saat bersamaan. Gunakan kode 10 sampai 15 untuk

menerapkan kendali kelompok ini dan lanjutkan ke langkah berikutnya.

Jika Anda ingin mengatur unit indoor satu kelompok secara individu atau jika

Anda ingin membaca pengaturan terakhir, gunakan kode 20 sampai 25 yang

ditampilkan dalam tanda kurung. Tekan tombol [PROGRAMMING] untuk

memilih No. unit indoor yang Anda ingin menyesuaikan pengaturan bidang.

4 Tekan bagian atas tombol [TIME ADJUST] untuk memilih No. kode pertama

5 Tekan bagian bawah tombol [TIME ADJUST] untuk memilih No. kode kedua

6 Tekan tombol [SCHEDULE TIMER] untuk mengkonfirmasi pengaturan.

7 Tekan tombol [INSPECTION/TEST OPERATION] untuk kembali ke mode normal.

Pengaturan bidang

SiBE121135_A

259 Operasi Uji coba dan Pengaturan bidang

BRC1E52A7, BRC1E52B7

d

b

c

A

(R12878)

a No. Unit

b No. kode pertama

c No. kode kedua

d Mode

Langkah

Tindakan Pengaturan remote

1 Tekan dan tahan tombol [Cancel] ( ) selama 4 detik untuk masuk ke menu Pengaturan bidang.

2 Gunakan tombol ▼▲ untuk memilih daftar pengaturan bidang dan tekan tombol [Menu/ Enter] ( ).

(R12879)

3 Gunakan tombol ▼▲ untuk memilih Mode yang diinginkan

4 Selama kendali kelompok, apabila pengaturan dari masing-masing unit indoor (mode 20, 21, 22 dan 23 telah dipilih), tekan tombol ◄ untuk menyorot dan tombol ▼▲ untuk memilih UNIT INDOOR NO. harus diatur. Operasi ini tidak perlu bila dilakukan pengaturan kelompok.

5 Sorot No. kode kedua untuk diubah menggunakan tombol ◄►, dan menggunakan tombol ▼▲ untuk memilih No. kode kedua yang diinginkan

Saat pengaturan kelompok, semua No. kode kedua yang mungkin diatur ditampilkan sebagai "*".

6 Tekan tombol [Menu/Enter] ( ) untuk menampilkan layar konfirmasi.

7 Gunakan tombol ▼▲ untuk memilih Yes dan tekan tombol [Menu/ Enter] ( ).

Ketika beberapa perubahan pengaturan diperlukan, ulangi langkah 3 sampai 7.

8 Tekan tombol [Cancel] ( ) untuk kembali ke layar utama.

SiBE121135_A Pengaturan bidang

Operasi Uji coba dan Pengaturan bidang

260

Peninjauan Pengaturan Bidang

No. Mode

No. kode pertama

Penjelasan pengaturan No. kode kedua

01 02 03 04

10 (20)

0

Interval tanda pembersihan filter

Filter dangat tahan lama

Rin

ga

n

Sekitar 10.000 jam.

Bera

t

Sekitar 5.000 jam.

Filter tahan lama

Sekitar 2.500 jam.

Sekitar 1.250 jam.

1 Tipe filter tahan lama Filter tahan lama

Filter dangat tahan lama

— —

2 Remote kontrol termistor Diaktifkan Dinonaktifkan

— —

3 Tanda pembersihan filter Tampilan Tidak ada tampilan

— —

11 (21)

0 jumlah unit indoor dari sistem operasi serempak

Sepasang Kembar Rangkap tiga Kembar ganda

1 Pengaturan individu sistem operasi serempak

Pengaturan seragam

Pengaturan individu

— —

2 Kipas OFF saat termostat OFF Standar Kipas OFF — —

7

Pengaturan tekanan statis eksternal Penyesuaian aliran udara

OFF

Penyelesaian penyesuaian aliran udara

Awal penyesuaian aliran udara

12

(22)

0 Pemilihan output aksesori pilihan (pemilihan bidang output untuk adaptor pengkabelan)

Kompresor

— Output operasi

Output kesalahan

1 Fungsi OFF paksa OFF paksa Operasi ON/OFF

— —

2 Perubahan perbedaan termostat (pengaturan ketika menggunakan sensor jarak jauh)

1°C 0.5°C — —

13 (23)

0 Kecepatan outlet udara tinggi (untuk aplikasi plafon tinggi)

2,7 m 2,7 ~ 3,0 m 3,0 ~ 3,5 m —

1 Pemilihan arah aliran udara (pengaturan ketika kotak bantalan penghambat telah dipasang)

Aliran 4-arah

Aliran 3-arah

Aliran 2-arah

3 Pemilihan fungsi aliran udara (pengaturan ketika menggunakan panel dekorasi untuk outlet)

Ada

Tidak ada

4 Pengaturan kisaran arah aliran udara Tinggi Normal Rendah —

6 Tekanan statis eksternal Lihat Catatan 2.

14 (24)

2 Interval tanda pengumpulan debu Sekitar 1.250 jam.

Sekitar 2.500 jam.

Sekitar 5.000 jam.

3 Tanda penggantian filter Tidak ada tampilan

Sekitar 32.000 jam.

Sekitar 48.000 jam.

Sekitar 72.000 jam.

4

Indikator panel (hijau) ON/OFF

Indikator menyala selama operasi AC dan pembersihan otomatis filter.

Indikator dapat menyala hanya selama pembersihan otomatis filter.

Indikator tidak menyala selama operasi AC dan pembersihan otomatis filter.

8 Pemilihan mode penguncian operasi kendali otomatis

ON OFF — —

9 Pengaturan jumlah debu Standar Berat — — 15

(25) 3 Operasi pompa pengurasan dengan

pelembaban Tidak ada Ada — —

: pengaturan pabrik Catatan: 1. Fungsi apapun yang tidak tersedia pada unit indoor tidak ditampilkan.

2.

: pengaturan pabrik

Tekanan statis eksternal (Pa) No.

Mode

No. kode pertama

No. kode kedua

FBQ

Kelas 35 Kelas 50 Kelas 60

13 (23)

6

03 30 30 30

04 35 35 40

05 40 40 50

06 45 45 60

07 50 50 70

08 60 60 80

09 70 70 90

10 80 80 100

11 90 90 —

12 100 100 —

Pengaturan bidang

SiBE121135_A

261 Operasi Uji coba dan Pengaturan bidang

Pengaturan MAIN/SUB saat Menggunakan 2 Remote Kontrol Kabel

Uraian Pengaturan MAIN/SUB diperlukan saat 1 unit indoor dikendalikan oleh 2 remote kontrol.

Ketika anda menggunakan 2 remote kontrol (panel kendali dan remote kontrol terpisah), atur

satu untuk MAIN dan satunya untuk SUB.

Rincian Remote kontrol diatur pabrik ke MAIN, sehingga Anda hanya perlu mengubah satu

remote kontrol dari MAIN ke SUB.

BRC1D528

Langkah

Tindakan

1 Masukkan obeng min ke dalam lekukan antara bagian atas dan bawah remote

kontrol, seperti yang ditunjukkan pada ilustrasi di bawah. Bongkar dengan pelan

bagian atas kontrol, kerjakan dari dua posisi kemungkinan.

Bagian atas remote

kontrol

Bagian bawah remote kontrol

(R11738)

2 Atur saklar [perubahan MAIN / SUB] pada PCB ke “S”.

Saklar diatur ke MAIN (pengaturan pabrik)

Atur saklar ke SUB.

(R11739)

BRC1E52A7, BRC1E52B7

Langkah

Tindakan Pengaturan remote

1 Nyalakan daya pada kedua remote kontrol 2 Tentukan mana yang merupakan remote

kontrol sub / main.

3 Apabila Error code: U5 - Connection under check Please wait for a moment (Sambungan sedang dalam pemeriksaan Tunggu sebentar ) ditampilkan pada kedua remote kontrol, tekan dan tahan tombol [Operation mode selector] dari remote kontrol sub selama 4 detik.

(R12880)

4 Remote kontrol sub sekarang menampilkan Sub remote contrl.

Catatan) Remote kontrol main masih

menampilkan Main remote

contrl.

(R12881)

5 Setelah beberapa detik, layar dasar ditampilkan.

Operasi Uji coba dan Pengaturan bidang

262

SiBE121135_A

6. Pelumas Silikon pada Transistor Daya /

Jembatan Dioda

Uraian Gunakan pelumas silikon yang telah ditentukan pada bagian radiasi panas transistor daya/

jembatan dioda ketika Anda mengganti PCB Unit outdoor. Pelumas silikon mendorong

radiasi panas transistor daya / jembatan dioda.

Rincian 1. Bersihkan pelumas silikon lama secara keseluruhan.

2. Oleskan pelumas silikon secara merata. Lihat ilustrasi di bawah untuk contoh penggunaan.

3. Kencangkan sekrup dari transistor daya / jembatan dioda.

4. Pastikan bahwa komponen-komponen radiasi panas tersambung kuat dengan sirip radiasi.

Catatan: Keluarnya asap mungkin ditimbulkan oleh radiasi panas yang buruk bila pelumas

silikon digunakan dengan tidak tepat.

OK: Dioleskan secara merata

Transistor daya

(atau jembatan

dioda)

PCB

Sirip

radiasi

Pelumas Silikon

(R18015)

NG: Tidak dioleskan secara merata

(R18016)

NG: Benda asing terjebak.

Benda asing (R18017)

SiBE121135_A Pelumas Silikon pada Transistor Daya / Jembatan Dioda

263 Lampiran

Bab 8

Lampiran 1. Diagram Perpipaan ................................................................................ 264

Unit Outdoor .............................................................................................. 264 Unit Indoor ................................................................................................ 269

2. Diagram Pemasangan Kabel ................................................................ 276 Unit Outdoor .............................................................................................. 276 Unit Indoor ................................................................................................ 281

3. Prosedur Penghapusan (Buku Kecil No.) ............................................. 289

Lampiran 264

Diagram Perpipaan

SiBE121135_A

H E AD E R

HEAT EXCHANGER OUTDOOR TEMPERATURE THERMISTOR (DOA) ELECTRONIC

EX PA NSIO N V A LVE LIQ UID P IP E THE RMISTOR (DLA)

9.5CuT HEADER 6.4CuT E VA

ELECTRONIC FILTER

EX PA NSIO N V A LVE LIQ UID

PIPE 6.4CuT EV B

ELECTRONIC

THE RMISTOR (DLB)

FILTER

HEAT EXC HAN G ER THERMI STO R (DE)

FILTER EX PA NSIO N V A LVE LIQ UID

PIPE DISTRIBUTOR 6.4CuT EVC

THE RMISTOR (DLC)

CAPILLARY TUBE

DC FAN MOTOR M

PROPELLER FAN

LIQUID LINE STOP VALVE

FILTER

7.9CuT 12.7CuT GAS PIPE THE RMIS TO R (DGA) HEADER 12.7CuT

GAS PIPE THE RMIS TO R (DGB)

MUFFLER 12.7CuT

MUFFLER

DISCHARGE PIPE THERMISTOR (DO)

GAS PIPE THE RMIS TO R (DG C)

MUFFLER 12.7CuT

REFRIGERANT FLOW

COOLING CO MP RESSO R ACCUMULATOR

GAS LINE STOP VALVE

HEAT EXCHANGER

H E AD E R

OUTDOOR TEMPERATURE THERMISTOR (DOA)

ELECTRONIC EXPANSIO N VA LVE LIQ UID

PIPE HEADER 6.4CuT E VA THE RMISTOR (DLA)

9.5CuT ELECTRONIC FILTER

EXPANSIO N VA LVE LIQ UID PIPE

6.4CuT E VB THE RMISTOR (DLB)

ELECTRONIC FILTER

HEAT EXC HAN G ER THERMI STO R (DE)

FILTER EXPANSION VALVE LIQUID PIPE EVC THE RMISTOR (DLC)

DISTRIBUTOR 6.4CuT

CAPILLARY TUBE ELECTRONIC FILTER

DC FAN MOTOR M EXPANSIO N VA LVE LIQ UID PIPE

PROPELLER FAN

LIQUID LINE STOP VALVE

THE RMISTOR (DLD) 6.4CuT

E V D

FILTER

7.9CuT 12.7CuT GAS PIPE THE RMIS TO R (DGA) HEADER 12.7CuT

GAS PIPE THE RMIS TO R (DGB)

MUFFLER 12.7CuT

MUFFLER

DISCHARGE PIPE THERMISTOR (DO)

GAS PIPE THE RMIS TO R (DG C)

MUFFLER 12.7CuT

REFRIGERANT FLOW

COOLING

GAS LINE STOP VALVE

12.7CuT GAS PIPE THE RMIS TO R (DG D)

CO MP RESSO R ACCUMULATOR

( )

( )

( )

( )

12

.7C

uT

1. Diagram Perpipaan

Unit Outdoor Pendingin Saja

3MKS50E3V1B

Operasi senyap

R O O M A (6. 4 Cu T)

R O O M B

(6. 4 Cu T)

R O O M C

(6. 4 Cu T)

R O O M A (9. 5 Cu T)

R O O M B

(9. 5 Cu T)

R O O M C (9. 5 Cu T)

FIELD PIPING LIQUID SIDE

FIELD PIPING GAS SIDE

3D052056C

4MKS58E3V1B

Operasi senyap

R O O M A (6. 4 Cu T)

R O O M B (6. 4 Cu T)

R O O M C

(6. 4 Cu T)

R O O M D

(6. 4 Cu T)

R O O M A (9. 5 Cu T)

R O O M B (9. 5 Cu T)

ROO M C

(12.7

CuT)

ROO M D

(12.7

CuT)

FIELD PIPING LIQUID SIDE

FIELD PIPING GAS SIDE

3D052057B

12

.7C

uT

265 Lampiran

SiBE121135_A Diagram Perpipaan

15

.9C

uT

4MKS75F2V1B

Operasi senyap

HEAT EXCHANGER

OUTDOOR TEMPERATURE THERMISTOR (DOA)

MOTOR OP ERATE D VA LV E

LI QUI D PI P E

9.5CuT HEADER 6.4CuT E VA THERMISTOR (DLA)

ROO M A

MOTOR OP ERATE D VA LV E LI QUI D PI P E FILTER (6.4 CuT)

6.4CuT E VB THERMISTOR (DLB)

FILTER

RO O M B

(6.4 CuT) MOTOR OP ERATE D VA LV E LI QUI D PI P E FIELD

HEAT EXC HAN G ER THERMI STO R (DE)

FILTER 6.4CuT

E V C THERMISTOR (DLC) ROO M C

PIPING LIQUID

DISTRIBUTOR MOTOR OP ERATE D VA LV E LI QUI D PI P E FILTER (6.4 CuT)

DC FAN MOTOR M

PROPELLER FAN

CAPILLARY TUBE LIQUID LINE STOP VALVE

6.4CuT E V D THERMISTOR (DLD)

FILTER

RO O M D

(6.4 CuT)

7.9CuT

DISCHARGE PIPE THERMISTOR (DO)

12.7CuT

12.7CuT

HEADER

GAS LINE

12.7CuT

12.7CuT

12.7CuT

GAS PIPE THE RMIS TO R (DGA)

GAS PIPE THE RMIS TO R (DGB)

GAS PIPE THE RMIS TO R (DG C)

GAS PIPE THE RMIS TO R (DG D)

RO O M A

(9.5 CuT)

RO O M B

(9.5 CuT)

RO O M C

(12.7

CuT)

FIELD PIPING GAS

REFRIGERANT FLOW STOP VALVE

12.7CuT ROO M D

ACCUMULATOR COOLING COMPRESSOR

(15.9 CuT)

3D034513H

5MKS90E2V3B

OUTDOOR UNIT

HEAT EXCHANGER

7.9CuT 7.9CuT

OUTDOOR TEMPERATURE THERMISTOR

HEADER

MOTOR OPERATED VALVE (A)

EVA

7.9CuT

LIQUID PIPE

THERMISTOR (ROOM-A)

ROOM A

HEADE R 7.9CuT

7.9CuT 7.9CuT

7.9CuT

7.9CuT

7.9CuT

HEAT EXCHANGER (CONDENSER)

THERMISTOR

7.9CuT

9.5CuT

MOTOR OPERATED VALVE (B)

EVB

7.9CuT

MOTOR OPERATED VALVE (C)

7.9CuT E VC

MOTOR OPERATED VALVE (D)

7.9CuT E VD

LIQUID PIPE THERMISTOR (ROOM-B)

LIQUID PIPE FILT ER

THERMISTOR (R O O M -C )

LIQUID PIPE THERMISTOR (ROOM-D)

(6.4 CuT)

ROOM B

(6.4 CuT)

ROOM C

(6.4 CuT)

ROOM D

FIELD

PIPING LIQUID

MOTOR OP ERATE D LIQUID PIP E FILTER (6.4 CuT) DC FAN MOTOR M DISTRIBUTOR LIQUID LINE VALVE (E) TH E RMI S T OR

PROPELLER FAN

CAPILLARY TUBE STOP

VALVE

7.9CuT E VE

(ROOM-E)

FILTE R

ROOM E

(6.4 CuT)

7.9CuT

DISCHARGE PIPE THERMISTOR

REFRIGE RA NT FLOW

15.9CuT

15.9CuT

9.5CuT FILTER

HEADER

GAS LINE

STOP VALVE

12.7CuT

12.7CuT

12.7CuT

12.7CuT

12.7CuT

GAS PIPE THERMISTOR

(ROOM-A)

GAS PIPE

THERMISTOR (ROOM-B)

GAS PIPE THERMISTOR

(ROOM-C)

GAS PIPE

THERMISTOR (ROOM-D)

GAS PIPE

THERMISTOR (ROOM-E)

ROOM A (9.5 CuT)

ROOM B (9.5 CuT)

ROOM C (12.7

CuT)

ROOM D

(15.9 CuT)

ROOM E

FIELD PIPING

GAS

COOLING COMPRESSOR ACCUMULATOR ACCUMULATOR 15.9CuT

(15.9 CuT)

3D051938

A CCUMULA TO R

FILTE R

FILTE R

9.5

Cu

T

12

.7C

uT

1

2.7

Cu

T

7.9

Cu

T

9.5

Cu

T

Lampiran 266

Diagram Perpipaan

SiBE121135_A

( )

( ) 7.9

Cu

T

7.9

Cu

T

12

.7C

uT

1

2.7

CuT

)

)

Pompa Kalor

3MXS40K2V1B, 3MXS40K3V1B

Operasi senyap

HEADER

HEAT EXCHANGER OUTDOOR TEMPERATURE

THERMISTOR (DOA)

ELECTRONIC EXPANSION VALVE LIQUID PIPE

9.5CuT HEADER 6.4CuT

EVA THERMISTOR (DLA) ROOM A

ELECTRONIC FILTER (6.4 CuT)

EXPANSION VALVE LIQUID PIPE

HEAT EXC HAN G ER

FILTER

6.4CuT EVB

ELECTRONIC

THERMISTOR (DLB)

FILTER

ROOM B (6.4 CuT)

FIELD

PIPING

TH E RMI S T OR (D E ) DISTRIBUTOR EXPANSION VALVE LIQUID PIPE

LIQUID SIDE

DC FAN MOTOR M

CAPILLARY TUBE LIQUID LINE STOP

VALVE

6.4CuT EVC THERMISTOR (DLC)

FILTER

ROOM C (6.4 CuT)

PROPELLER FAN

12.7CuT 12.7CuT

REVERSING SOLENOID VALVE

MUFFLER

HEADER

GAS PIPE THERMISTOR (DGA) 12.7CuT

GAS PIPE THERMISTOR (DGB)

ROOM A (9.5 CuT)

MUFFLER 12.7CuT

DISCHARGE PIPE

ROOM B (9.5 CuT)

FIELD PIPING

THERMISTOR (DO)

REFRIG E RA NT FLO W

MUFFLER

GAS LINE STOP

VALVE

GAS PIPE THERMISTOR (DGC) 12.7CuT

ROOM C (9.5 CuT)

GAS SIDE

COOLING COMPRESSOR HEATING

ACCUMULATOR

3D073394A

3MXS52E3V1B, 3MXS52E4V1B, 3AMX52E3V1B, 3AMX52E4V1B

Operasi senyap

HEADER

HEAT EXCHANGER OUTDOOR TEMPERATURE

THERMISTOR (DOA)

ELECTRONIC EXPANSION VALVE LIQUID PIPE

9.5CuT HEADER 6.4CuT

EVA THERMISTOR (DLA) ROOM A

ELECTRONIC FILTER (6.4 CuT)

EXPANSION VALVE LIQUID PIPE

HEAT EXC HAN G ER

FILTER

6.4CuT EVB

ELECTRONIC

THERMISTOR (DLB)

FILTER

ROOM B (6.4 CuT)

FIELD

PIPING

TH E RMI S T OR (D E ) DISTRIBUTOR EXPANSION VALVE LIQUID PIPE

LIQUID SIDE

DC FAN MOTOR M

CAPILLARY TUBE LIQUID LINE STOP

VALVE

6.4CuT EVC THERMISTOR (DLC)

FILTER

ROOM C (6.4 CuT)

PROPELLER FAN

12.7CuT 12.7CuT

REVERSING SOLENOID VALVE

MUFFLER

HEADER

GAS PIPE THERMISTOR (DGA) 12.7CuT

GAS PIPE THERMISTOR (DGB)

ROOM A (9.5 CuT)

MUFFLER 12.7CuT

DISCHARGE PIPE

ROOM B (9.5 CuT)

FIELD PIPING

THERMISTOR (DO)

REFRIG E RA NT FLO W

MUFFLER

GAS LINE STOP

VALVE

GAS PIPE THERMISTOR (DGC) 12.7CuT

ROOM C (12.7 CuT)

GAS SIDE

COOLING COMPRESSOR HEATING

ACCUMULATOR

3D052055F

(

(

267 Lampiran

SiBE121135_A Diagram Perpipaan

7.9

Cu

T

7.9

Cu

T

3MXS68G2V1B, 3MXS68G3V1B

Operasi senyap

HEA DE R

HEAT EXCHANGER OUTDOOR TEMPERATURE

THERMISTOR (DOA)

MOTOR OPERATED VALVE

LIQUID PIPE

9.5CuT HEADER 6.4CuT EVA THERMISTOR (DLA)

ROOM A

MOTOR OP ERATE D VA LV E LIQUID FILTER

PIPE (6.4 CuT)

6.4CuT EVB THERMISTOR (DLB)

ROOM B FIELD

PIPING MOTOR OP ERATE D VA LV E LIQUID

FILTER PIPE

(6.4 CuT) LIQUID

H E AT E XC H A N G ER TH E RMI S T OR (D E )

DC FAN MOTOR M

DISTRIBUTOR

CAPILLARY TUBE

FILTER

LIQUID LINE STOP

VALVE

6.4CuT EVC THERMISTOR (DLC)

FILTER

ROOM C

(6.4 CuT)

PROPELLER FAN

12.7CuT

12.7CuT 12.7CuT

REVERSING SOLENOID VALVE

MUFFLER

12.7CuT DISCHARGE PIPE THERMISTOR (DO)

REFRIG E RA NT FLO W

GAS PIPE THERMISTOR (DGA) HEADER 12.7CuT

GAS PIPE THERMISTOR (DGB) 12.7CuT

GAS PIPE THERMISTOR (DGC) 12.7CuT

GAS LINE

STOP VALVE

ROOM A (9.5 CuT)

ROOM B (12.7 CuT)

ROOM C (12.7 CuT)

FIELD

PIPING GAS

COOLING COMPRESSOR HEATING

ACCUMULATOR ACCUMULATOR

3D058888A

4MXS68F2V1B, 4MXS68F3V1B

Operasi senyap

HEA DE R

HEAT EXCHANGER OUTDOOR TEMPERATURE

THERMISTOR (DOA)

MOTOR OPERATED VALVE

LIQUID PIPE

9.5CuT HEADER 6.4CuT EVA THERMISTOR (DLA)

ROOM A

MOTOR OP ERATE D VA LV E LIQUID FILTER

PIPE (6.4 CuT)

6.4CuT EVB THERMISTOR (DLB)

ROOM B

MOTOR OP ERATE D VA LV E LIQUID FILTER

PIPE (6.4 CuT) FIELD

HEAT EXC HAN G ER TH E RMI S T OR (D E )

FILTER 6.4CuT

C THERMISTOR (DLC)

ROOM C

PIPING LIQUID

DISTRIBUTOR MOTOR OP ERATE D VA LV E LIQUID FILTER PIPE

(6.4 CuT)

DC FAN MOTOR M

PROPELLER FAN

CAPILLARY TUBE

12.7CuT

LIQUID LINE STOP

VALVE

6.4CuT EVD THERMISTOR (DLD)

FILTER

ROOM D

(6.4 CuT)

12.7CuT 12.7CuT

REVERSING SOLENOID VALVE

MUFFLER

12.7CuT DISCHARGE PIPE THERMISTOR (DO)

GAS PIPE THERMISTOR (DGA) HEADER 12.7CuT

GAS PIPE THERMISTOR (DGB) 12.7CuT

GAS PIPE THERMISTOR (DGC) 12.7CuT

ROOM A (9.5 CuT)

ROOM B (9.5 CuT)

ROOM C (12.7 CuT)

FIELD

PIPING GAS

REFRIG E RA NT FLO W

COOLING COMPRESSOR HEATING

GAS LINE

STOP

VALVE ACCUMULATOR

ACCUMULATOR

GAS PIPE THERMISTOR (DGD) 12.7CuT

ROOM D (12.7 CuT)

3D055041A

12

.7C

uT

1

2.7

CuT

Lampiran 268

Diagram Perpipaan

SiBE121135_A

7.9C

uT

7.9C

uT

15

.9C

uT

15

.9C

uT

15

.9C

uT

15

.9C

uT

4MXS80E2V3B, 4MXS80E3V3B

Operasi senyap

MOTOR OPERATED LIQUID PIPE HEAT EXCHANGER OUTDOOR TEMPERATURE VALVE (A) TH E RMI S T OR

7.9CuT THERMISTOR RECEIVER HEADER 7.9CuT EVA (R O O M -A)

HEA DE R 7.9CuT MOTOR OPERATED LIQUID PIPE ROOM A

7.9CuT 7.9CuT 9.5CuT 7.9CuT

VALVE (B)

7.9CuT EVB

THERMISTOR FILT ER (ROO M-B )

(6.4 CuT)

ROOM B 7.9CuT MOTOR OPERATED LIQUID PIPE FILTER (6.4 CuT) FIELD

7.9CuT 7.9CuT

HE A T EX C H A N G E R (C O N DE N SE R ) T HE R M IS T O R

VALVE (C)

7.9CuT EVC

THERMISTOR (ROOM-C)

ROOM C

PIPING LIQUID

MOTOR OPERATED LIQUID PIPE FILTER (6.4 CuT)

DC FAN MOTOR M

7 . 9 C u T

DISTRIBUTOR

LIQ UID LINE

VALVE (D)

7.9CuT EVD

THERMISTOR (ROOM-D)

FILTER

RO O M D (6.4 CuT)

PROPELLER FAN

CAPILLARY TUBE

4-WAY VALVE

STOP VA LVE

9.5CuT FILTER

GAS PIPE THERMISTOR

15.9CuT 15.9CuT HEADER

12.7CuT (ROOM-A)

GAS PIPE THERMISTOR

7.9CuT 12.7CuT (ROOM-B)

R O O M A

(9. 5 Cu T)

7.9CuT GAS PIPE THERMISTOR R O O M B

(1 2. 7 C u T)

MUFFLER 12.7CuT (ROOM-C)

R O O M C FIELD

DISCHARGE PIPE THERMISTOR

REFRIGE RA NT FLOW

15.9CuT

GAS LINE

STOP VALVE MUFFLER MUFFLER

GAS PIPE THERMISTOR (ROOM-D)

12.7CuT

(15.9 CuT)

R O O M D (1 5. 9 C u T)

PIPING GAS

COOLING COMPRESSOR AC C U M U LA T O R A C C UM U LA T O R

HE A TI N G

15.9CuT

12.7CuT

15.9CuT

3D051937G

5MXS90E2V3B, 5MXS90E3V3B

Operasi senyap

MOTOR OPERATED LIQUID PIPE HEAT EXCHANGER OUTDOOR TEMPERATURE VALVE (A) TH E RMI S T OR

7.9CuT THERMISTOR RECEIVER HEADER 7.9CuT EVA (R O O M -A)

HEA DE R 7.9CuT MOTOR OPERATED LIQUID PIPE ROOM A

7.9CuT 7.9CuT 9.5CuT 7.9CuT

VALVE (B)

7.9CuT EVB

THERMISTOR FILTER (ROOM-B)

(6.4 CuT)

ROOM B 7.9CuT MOTOR OPERATED LIQUID PIPE FILTER (6.4 CuT)

7.9CuT 7.9CuT

HE A T EX C H A N G E R (C O N DE N SE R ) T HE R M IS T O R

VALVE (C)

7.9CuT EVC

THERMISTOR (ROOM-C)

ROOM C

FIELD PIPING LIQUID

MOTOR OPERATED LIQUID PIPE FILTER (6.4 CuT)

7. 9 C u T

VALVE (D)

7.9CuT EVD

THERMISTOR (ROOM-D)

ROOM D MOTOR OP ERATE D LIQUID PIP E (6.4 CuT) DC FAN MOTOR M DISTRIBUTOR V A L V E (E ) T H ER MI ST O R FI LT E R

PROPELLER FAN

CAPILLARY TUBE

4-WAY

LIQ UID LINE

STOP VA LVE

9.5CuT FILTER

7.9CuT EVE

(ROOM-E)

FILTER

ROO M E (6.4 CuT)

VALVE 15.9CuT 15.9CuT

GAS PIPE THERMISTOR HEADER 12.7CuT (ROOM-A)

GAS PIPE THERMISTOR

R O O M A (9. 5 Cu T)

7.9CuT 12.7CuT (ROOM-B)

7.9CuT GAS PIPE THERMISTOR R O O M B

(9. 5 Cu T)

MUFFLER 12.7CuT (ROOM-C)

R O O M C FIELD

DISCHARGE PIPE THERMISTOR

REFRIGE RA NT FLOW

15.9CuT

GAS LINE

STOP VALVE MUFFLER MUFFLER

GAS PIPE THERMISTOR (ROOM-D)

12.7CuT GAS PIPE THERMISTOR

(ROOM-E) 12.7CuT

(12.7 CuT)

R O O M D (1 5. 9 C u T)

R O O M E

PIPING GAS

COOLING COMPRESSOR AC C U M U LA T O R A C C UM U LA T O R HE A TI N G

15.9CuT

12.7CuT

15.9CuT

(15.9 CuT)

3D051936B

12

.7C

uT

1

2.7

CuT

9.5

Cu

T

9.5

Cu

T

9.5

Cu

T

9.5

Cu

T

269 Lampiran

SiBE121135_A Diagram Perpipaan

Unit Indoor Tipe Wall Mounted

FTXG25/35JV1BW(A) FTXG50JV1BW(A)

INDOOR UNIT INDOOR UNIT

REFRIGERANT FLOW

COOLING HEATING

REFRIGERANT FLOW

COOLING HEATING

4D065855B 4D065856C

FTXS20/25K2V1B, CTXS15/35K2V1B FTXS35/42K2V1B, FTXS25/35/42J2V1B ATXS20/25/35/42G2V1B

INDOOR UNIT

INDOOR UNIT

REFRIGERANT FLOW

COOLING

HEATING

REFRIGERANT FLOW

COOLING

HEATING

4D058926Q

4D058897K

6.4CuT

HEAT EXCHANG ER

FIELD PIPING

6.4CuT

FIELD PIPING

12.7CuT

CRO SS FLO W FA N

M FAN MOTOR

9.5CuT

THERMISTOR ON HEAT EXCH.

6.4CuT

HEAT EXCHANG ER

FIELD PIPING

6.4CuT

FIELD PIPING

9.5CuT

CRO SS FLO W FA N

M FAN MOTOR

THERMISTOR ON HEAT EXCH.

9.5CuT

7.0CuT HEAT EX CHANGER

4.8CuT

THERMISTOR

ON HEAT EXCH. 7.0CuT

7.0CuT

FIELD PIPING

(6.4CuT)

CROSS FLOW FAN

M FAN MOTOR

FIELD PIPING 9.5CuT

(9.5CuT)

M FAN MOTOR

6.4CuT

HEAT EXCHANGER

FIELD PIPING

6.4CuT

CROSS FLO W FAN

TH E RMI S T OR ON HEAT E XCH.

FIELD PIPING

9.5CuT 9.5CuT

7.0

Cu

T

Diagram Perpipaan

SiBE121135_A

Lampiran 270

M

FTXS50K2V1B, FTXS50J2V1B ATXS50G2V1B

FTXS60GV1B

INDOOR UNIT

INDOOR UNIT

REFRIGERANT FLOW

COOLING

HEATING

REFRIGERANT FLOW

COOLING

HEATING

4D040081Y

4D058898G

FTXS71GV1B

INDOOR UNIT

REFRIGERANT FLOW

COOLING

HEATING

4D040082W

(7.9CuT)

HEAT EXCHANGER

THE RMISTOR

ON HEAT EXCH.

FIELD PIPING

(6.4CuT)

FIELD PIPING

(12.7CuT)

CRO SS FLO W FA N

M

FAN MOTOR

(12.7CuT)

(7.9CuT)

HEAT EXCHANGER

THERMISTOR ON HEAT EXCH.

FIELD PIPING

(6.4CuT)

CROSS FLO W FAN

FIELD PIPING

(15.9CuT)

FAN MOTOR

(12.7CuT)

M FAN MOTOR

6.4CuT

HEAT EXCHANGER

FIELD PIPING

6.4CuT

CROSS FLO W FAN

TH E RMI S T OR

ON HEAT E XCH.

FIELD PIPING

12.7CuT 9.5CuT

SiBE121135_A Diagram Perpipaan

271 Lampiran

Tipe Floor Standing

FVXG25/35K2V1B FVXG50K2V1B

INDOOR UNIT

MV THERMIST OR 6.4CuTR ADIANT P ANE L THE RMISTOR

HEAT EXCHANGER

INDOOR UNIT

MV THERMIST OR 6.4CuTR ADIANT P ANE L THERMISTOR

HEAT EXCHANGER

FIE L D PI PIN G

6. 4C uT

FIE L D PI PIN G

9. 5C uT

CROSS FLOW FAN

M FAN MOTOR

9.5CuT

THERMISTOR ON HEAT

EXCH.

FIE L D PI PIN G

6. 4C uT

FIE L D PI PIN G

1 2.7 C uT

CROSS FLOW FAN

M FAN MOTOR

9.5CuT

THERMISTOR ON HEAT EXCH.

REFRIGERANT FLOW

COOLING HEATING

REFRIGERANT FLOW COOLING

HEATING

4D071597 4D071598

FVXS25/35FV1B FVXS50FV1B

INDOOR UNIT

MUFFLER ASSY

7.0CuT

6.4CuT

6.4CuT

HEAT EX CHA NGER

INDOOR UNIT

MUFFLER ASSY 7.0CuT

6.4CuT

6.4CuT

6.4CuT

HEAT EXCHANGER

FIELD PIPING

(6.4CuT)

M

TURB O FA N FA N MO TO R

THER MIST O R ON HEAT EXCH.

6. 4C uT

6. 4C uT

FIELD PIPING

(6.4CuT)

TU R B O F A N

M

FAN M OTO R

THER MIST O R ON HEAT EXCH.

6. 4 Cu T 6. 4 Cu T

6. 4 Cu T

FIELD PIPING

(9.5CuT)

9.5CuT

FIELD PIPING

(12.7CuT)

9.5CuT

REFRIGERANT FLOW

COOLING

HEATING

REFRIGERANT FLOW

COOLING

HEATING

4D056137B 4D056138D

6.4

Cu

T

6.4

Cu

T

6.4

Cu

T

6.4

Cu

T

6.4

Cu

T

6.4

Cu

T

Diagram Perpipaan

SiBE121135_A

Lampiran 272

Tipe Floor/Ceiling Suspended Dual

FLXS25/35BAVMB FLXS50/60BAVMB

INDOOR UNIT

INDOOR UNIT

REFRIGERANT FLOW

COOLING HEATING

REFRIGERANT FLOW COOLING

HEATING

4D048722B 4D048724B

Tipe Duct Connected

FDXS25/35E7VMB, FDXS50/60C7VMB

INDOOR UNIT

(6.4CuT)

HEAT EXCHANGER

FIELD PIPING (6.4CuT) SIROCCO FAN

M

FAN MOTOR

TH E RMI S T OR

O N H E A T E X CH.

FIELD PIPING (A CuT)

(A CuT)

REFRIGERANT FLOW

COOLING HEATING

A A

FDXS25E7 VMB FDXS35E7 VMB

9,5 FDXS50C7VMB FDXS60C7VMB

12,7

C: 4D045449R

M

FAN MOTOR

(9.5CuT)

HEAT EX CHA NGER

FIELD PIPING (6.4CuT) SIROCCO FAN

THERMISTOR ON HEAT

EXCH.

FIELD PIPING (12.7CuT)

(12.7CuT)

M

FAN MOTOR

(6.4CuT)

HEAT EXCHANGER

FIELD PIPING (6.4CuT) SIROCCO FAN

THERMISTOR ON HEAT EXCH.

FIELD PIPING (9.5CuT)

(9.5CuT)

SiBE121135_A Diagram Perpipaan

273 Lampiran

Tipe Ceiling Mounted Cassette

FCQG35/50/60FVEB

FFQ25/35/50/60B9V1B

To Outdoor unit

Indoor unit

MODEL A Ruan

g

FFQ25/35B9V1B

6,4

9,5

FFQ50/60B9V1B

6,4

12,7

C: 4D039335B

REFRIGERANT FLOW

COOLING

HEATING

HEAT EXCHANGER

MODEL

FCQG35FVEB

FCQG50FVEB

FCQG60FVEB

A

6,35

Ruang

9,52

12,7

M

KIPAS

LIQUID PIPE

CONNECTION PORT

A

GAS PIPE CONNECTION PORT

Ruang

C: 4D076993

Indoor heat exchanger

Field piping A C1220T-

O

Field piping B C1220T-

O

Diagram Perpipaan

SiBE121135_A

Lampiran 274

Tipe Ceiling Suspended

FHQ35/50/60BWV1B

To Outdoor unit

Indoor unit

MODEL A Ruang

FHQ35BWV1B 6,4 9,5

FHQ50/60BWV1B 6,4 12,7

C: 4D037995P

Indoor heat exchanger

Field piping C1220T-O A

Field piping C1220T-O

Ruang

SiBE121135_A Diagram Perpipaan

275 Lampiran

Tipe Ceiling Mounted Built-in

FDBQ25B8V1

Refrigerant flow

Cooling

Heating

Refrigerant pipe connection port diameters

Model Gas Cairan

FDBQ25B8V1 9,52 6,35

C 3TW20815-1B

FBQ35/50/60C8VEB

Refrigerant flow

Cooling

Heating

Refrigerant pipe connection port diameters

Model Gas Cairan

FBQ35C 9,52 6,35

FBQ50C 12,70 6,35

FBQ60C 12,70 6,35

C: 3TW31275-1

Heat exchanger

Liquid pipe connection port

Gas pipe connection port

Heat exchanger

Liquid pipe connection port

Gas pipe connection port

Lampiran 276

Diagram Pengkabelan

SiBE121135_A

BLK

WH

T

2. Diagram Pengkabelan Outdoor Unit Pendingin Saja

3MKS50E3V1B

GRN YLW

GRN

Z1C

L1R

P O WE R S UP P L Y

X1M L

Z2C

AC1

SA2 FU1 30A

GRN

E1

E2 MRM20 MRM10

HR1 HR2 FU3 7

3,15A RE D

BLU

Z4C M1F M

L N

TO I ND O O R UNI T

N

Z3 C

BRN

AC2 V6 BLU

V11

1 9 8

2

6(P)

7(N)

+ + + S70 1

BRN OR G WH T

ROOM B PM1 U X11A M1C X2M 1 1 A 1

FU2

5 RE D V RE D U V M

2 2 RED 3, 15A 4 YLW W YLW

3~

3 3 YLW B

C

S10 V3 3 BLU BLU W

ROOM A

BLU

X3M 7 Q1L

1 2 3

ROOM C

1 2 3

X4M

1 3 S15 5

V5

S8

0

WHT A

RED B

BLU C

PCB1 S40

1 4

1 1 2 2 3 3

SHEET METAL

1 S51 12 1S1015 3 1 1 S20 6 1 S21 6 1 S22 6 1 S90 6 1 S92 8 1 S93 9

1 S52 12 1S102 5 M M M t˚ t˚ t˚ t˚ t˚ t˚ t˚ t˚ t ̊

indoor LED PCB2 R3T R2T R1T R8T R9T R10T R4T R5T R6T

4 3 2 1 A S2 Y1E Y2E Y3E (OU TD O O R) (D I S CHA R GE ) (R O OM -A ) (R O OM - C) (R O OM -A ) (RO O M -C)

SW2 SW5 SW1 SW3

SW4

outdoor

(CONDENSE R) (RO O M -B ) <GA S P I P E >

(ROOM-B) <L I QUI D P I P E >

Z1C~Z4C

X1M~X4

M

: FERRITE CORE

: TERMINAL

STRIP

MRM10, MRM20

MRC/W

L

: MA GNETIC RELAY N

: LIV E : NEUTRA L

M1C

M1F

: COMPRESSOR MOTOR

: FA N MOTOR

Y1E~Y3E : ELECTRONIC EX PA NSION VALV E COIL

R1T~R6T SW1 : FORCED OPERA TION ON/OFF SW (SW1) L1R : REA CTOR

V2, V3, V5, V6, V11 :

VARISTOR

R8T~R10T : THERMISTOR SW2 : SELECT SW (SW2) Q1L : OV ERLOA D PROTECTOR

SA2

FU1, FU2, FU3

: SURGE A RRESTER

: FUSE

S2~S102

LED1~LED

4

: CONNECTOR SW3 : WIRING ERROR CHECK SW (SW3)

SW4 : PRIORITY ROOM SETTING SW (SW4)

PM1

PCB1, 2

: POW ER MODULE

: PRINTED CIRCUIT BOA RD

AC1, A C2

U, V, W,

X11A E1, E2 HR1, HR2

: CONNECTOR

LEDA : PILOT LA MP SW5 : NIGHT QUIET MODE SETTING SW (SW5) SHEET META L : TERMINA L STRIP FIXED PLA TE

3D057135

4MKS58E3V1B

POW ER SUPPLY

GRN

YLW

X1M

L

GRN

FU1

SA2

Z1C GRN

E1

E2 MRM20

HR1

L1R

HR2

FU3

3,15A

7

RED

M1F

M L Z2C AC1 30A V2 M RM1 0 BLU

N N

Z3 C

BRN

AC2 V6

V11

1 9 8 6(P)

7(N)

+ + + S70 1

B R N ORG WHT

TO INDO OR UNIT

BLU 2 PM1

X11A M1C

ROO M B 1 2

X2M 1 RED

A 1 2

FU2 3. 15A

5 U

4 V

RE D

YL W

R ED U

YLW V M 3~

3

ROO M A 1

3

X3M

1

YLW B

BLU C

ORG D

S10 V3

7 1

3 W BLU BLU W

Q1L

2 3

ROO M C

2 3

X4M

3 S15 5

V5 WHT

A

RED B

BLU C

PCB1

YLW

D

S40 1 4

1 2 3

ROO M D

1

1 2 3

X5M 1

1 S51

1 S52

12 1 S101 5

12 1 S102 5

3 S80 1 1 S20

M

6 1 S21 6 1

M

S22

M

6 1 S23 6

M

1 S90 6

t t t

1 S92

t t

8

t t

1 S93 9

t t t t

2 2 PCB2 R3T R2T R1T R8T R9T R10T R11T R4T R5T R6T R7T

3 3 4 LED

3 2 1 A Y1E Y2E Y3E Y4E (OUTDOOR) (DISCHARGE ) (ROOM-A ) (ROOM -C) (ROOM-A) (ROOM-C)

indoor SHEET METAL SW 2 SW 5 SW 1 SW 3 SW 4 outdoor (CONDENSER) (ROOM-B) (ROOM-D) < GAS PIPE >

(ROOM-B) (ROOM-D) < LIQUID PIPE >

Z1C ~ Z3C

X1M ~ X5M

: FERRITE CORE : TERMINAL STRIP

MRM10, MRM20

MRC/W

L : MA GNETIC RELAY N

: LIV E : NEUTRA L

M1C

M1F

: COMPRESSOR MOTOR : FA N MOTOR

FIELD WIRING Y1E ~ Y4E : ELECTRONIC EX PA NSION VALV E

COIL

R1T ~ R11T : THERMISTOR SW1 : FORCED OPERA TION ON/OFF SW

(SW1)

L1R : REA CTOR

V2, V3, V5, V6, V11 :

VARISTOR

S2 ~ S102 : CONNECTOR SW2 : SEL ECT SW

(SW2)

Q1L : OV ERLOA D PROTECTOR

SA2

FU1, FU2, FU3

: SURGE A RRESTER

: FUSE LED1 ~ LED4

LEDA

: PILOT LA MP SW3 : WIRING ERROR CHECK SW (SW3)

SW4 : PRIORITY ROOM SETTING SW

(SW4)

PM1

PCB1, 2

: POW ER MODULE

: PRINTED CIRCUIT BOA RD

AC1, A C2

U, V, W,

X11A E1, E2

HR1, HR2

: CONNECTOR

SW5 : NIGHT QUIET MODE SETTING SW

(SW5)

SHEET META L : TERMINA L STRIP FIXED PLA TE

3D051014B

FIELD WIRING

V2

BLK

WH

T

BLK

WH

T

BLK

WH

T

BLK

WH

T

BLK

WH

T

BLK

WH

T

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

RED

BLK

W

HT G

RN

BLU

BLU

BLU

BLU

BLU

BLU

BLU

BLU

BLU

BLU

BLU

BLU

RED

BL

K W

HT

GRN

MR

C

W

MRC

/W

WH

T YL

W

OR

G BL

U BR

N

RED

WH

T YL

W

OR

G BL

U BR

N

RED

WH

T YL

W

OR

G BL

U BR

N

RED

WH

T YL

W

OR

G BL

U BR

N

RED

BLK

BLK

BLK

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T W

HT

WH

T W

HT

BLK

BLK

BLK

BLK

GR

Y

BRN

BLK

GRY

BRN

RED

BLK

GR

Y

YLW

BLK

GRY

YLW

BLU

BLK

BL

K

BLK

BL

K

S2

277 Lampiran

SiBE121135_A Diagram Pengkabelan

: PROTE

: TE

: TER

: RELA

: CON : CON

WH

T Y

LW

OR

G

BLU

B

RN

R

ED

WH

T Y

LW

OR

G

BLU

B

RN

R

ED

WH

T Y

LW

OR

G

BLU

B

RN

R

ED

WH

T Y

LW

OR

G

BLU

B

RN

R

ED B

LK

BLK

BLK

3~

4MKS75F2V1B

POW ER SUPPLY

GR N

YLW

X1M

L

GRN

SA2

GRN

E1

Z1C

E2

MRM20

HR1

L1R

HR2

FU3 7

3,15A

RED

Z5C

M1 F

FU1 V100 M L N

TO INDOOR UNIT

ROOM B

N

X2M

Z3C

Z2C BRN

BLU

AC1

AC2

30A V 2

V9

MRM10

1 9

2

PM1

8 6( P)

7(N)

+ + +

S70

1

U

BLU BRN ORG W HT

X11A

M1C

U

1 1 2 2

RED A 1

B

FU2 3.15A

5

4 V W

RED

YLW

R ED

YLW V M

3

ROOM A

1

3

X3M

1

YLW

BLU C

ORG D

S10

7

1

V3

MRC/W

3

PCB1

BLU Z4C

BLU W

Q1L

2

3

ROOM C 1

2

3

2

3

X4M

1

2

3

3 S15

5

1 S51

12 1 S101 5

V5

3 S80 1 1

Z6C

WHT

A

S20 6

RED

B

1 S21 6 1

BLU

C

S22 6

YLW

D

1 S23 6 1 S90 6 1 S92 8

S40

1

1 4

S93 9

ROOM D

1

X5M

1 1 S52 12 1 S102 5

t t t t t t t t t t t

2 2 LED PCB2 M M M M R3T R2T R1T R8T R9T R10T R11T

R4T R5T R6T R7T

3 3 4 3 2 1 A S2 (OU T D O OR ) (DI S C H A R GE ) (R OOM -A ) (R OOM -C ) (R OOM -A ) (R OOM -C )

Y1E Y2E Y3E Y4E (C ON D E N S E R ) (ROOM-B) (ROOM-D) (ROOM-B) (ROOM-D)

SHEET METAL

indoor outdoor

SW2 SW5 SW1 SW3 SW4 < GA S PI PE > < LI QU I D PI P E >

Z1C~Z6C X1M~X5

M

: FERRITE CORE

: TERMINA L STRIP

MRM10, MRM20 MRC/W

L

: MA GNETIC RELAY N

: LIV E

: NEUTRA L M1C M1F

: COMPRES SOR MOTOR

: FA N MOTOR

Y1E~Y 4E : ELECTRONIC EXPANSION VALVE COIL

R1T~R11T : THERMISTOR SW 1 : F ORC ED OPER ATI ON ON/ OFF SW

(SW 1)

L1R : REA CTOR

V2, V 3, V 5, V 9, V 100 :

VA RIS TOR

S2~S102 : CONNECTOR SW2 : SEL ECT SW (SW2) Q1L : OV ERLOA D PROTECTOR

SA2

FU1, FU2, FU3 : SURGE A RRESTER

: FUS E

LED1~LED4

LEDA : PILOT LA MP

SW3 : WIRING ERROR CHECK SW (SW3)

SW4 : PRIORITY ROOM SETTING SW (SW4)

PM1

PCB1, 2

: POW ER MODUL E : PRINTED CIRCUIT BOA RD

A C1, A C2

U, V, W,

X11A E1, E2

HR1, HR2

: CONNECTOR

SW5 : NIGHT QUIET MODE SETTING SW

(SW5)

SHEET META L : TERMINA L STRIP FIX ED PLA TE

3D055885

5MKS90E2V3B

WHT : WHITE

YLW : YELLOW

ORG :

ORANGE RED

: RED GRN :

GREEN BLU :

BLUE BRN :

BROWN BLK :

BLACK GRY :

GREY

1N ~50Hz 230V

TO INDOOR UNIT

ROOM B

ROOM A

ROOM C

ROOM D

ROOM E

SHEET

META L

indoor outdoor

: FIELD WIRING CTIVE EARTH (SCREW)

RMINAL STRIP

MINAL Y CONNECTOR

NECTOR NECTION

L : LIVE

N : NEUTRAL

2TW27596-1A

FIELD WIRING

BLK

WH

T

BLK

WH

T

BLK

WH

T

BLK

WH

T

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

RE

D

BLK

W

HT

GR

N

WH

T

WH

T

OU

TD

OO

R

CO

ND

EN

SE

R

DIS

CH

AR

GE

BLK

GR

Y

BR

N

RE

D

RO

OM

-A

RO

OM

-B

RO

OM

-C

RO

OM

-D

RO

OM

-E

RO

OM

-A

RO

OM

-B

RO

OM

-C

RO

OM

-D

RO

OM

-E

GA

S P

IPE

BLK

GR

Y

YL

W

BLU

LIQ

UID

PIP

E

BLK

B

LK

Z1C~Z6C FERRITE CORE R1T~R3T THERMISTOR

Q1L OVERLOA D PROTE CTO R X1M~X6M TERMINA L STRIP R4T~R8T PM1 POWER MO DULE

Y1E~Y5E ELECTRONIC EXPANSION VALVE COIL R9T~R13T PCB1, 2 PRINTED CIRCUIT BOARD V2, V3, V5

VARISTOR S2~S102 CONNECTOR SHEET METAL TERMIN A L STRI P FIX ED P LATE

V9, V100 LED1~LE D5 LIGHT EMITTING DIODE

F2U FIELD FUSE

SA2 SURGE A RRESTER LEDA Q1DI FIELD EARTH LEAKAGE

BREAKER (300mA) FU1, FU2, FU3 FUSE SW1 FORCED OPERATION SW (SW1) AC1, AC2

CONNECTOR

SW2 OPERATION MODE SW (SW2) U, V, W, X11A SW3 WIRING ERROR CHECK SW (SW3)

E1, E2 SW4 PRIO RITY ROO M SETTING SW (SW4) HR1, HR2 SW5 NIGHT QUIET MODE SETTING SW (SW5)

MRM10, MRM20 MAG NETIC RE LAY

M1C CO MPRESSO R MOTOR MRC/W M1F FAN MOTOR

L1R REACTOR

Lampiran 278

Diagram Pengkabelan

SiBE121135_A

Ruang

C V3

3 3

BL

K

WH

T

BLK

WH

T

MR

C

W

BLU

BLU

Pompa Kalor

3MXS40K2V1B, 3MXS40K3V1B, 3MXS52E3V1B, 3MXS52E4V1B, 3AMX52E3V1B, 3AMX52E4V1B

GRN

YLW X1M

GRN

Z1C GRN

HR1

L1R

HR2

FU3 7

Z4C

POWER SUPPLY L SA2

FU1 E1 E2 MRM20

3,15A RED M1F

M Z2C AC1 30A V2 MRM10 BLU

L N

TO INDO OR UNIT

N

Z3 C

BR N

AC2 V6 BLU

V11

1 6 (P) 9 8

7 (N) 2

+ + + S70

1

BRN ORG WHT

PM1 X11A M1C ROOM B 1

X2M 1 RED

A 1

FU2 3.15A

5 U

4 V RE D

YL W

R ED U

YLW

V M

2 2 YLW 3 W BLU 3~

3 3

S10 BLU

BLU W

Q1L ROOM A 1

X3M 7

1 1 PCB1 2 2 3 S15 3 3 S40

ROOM C X4M

5 V5 WHT

A

RED

Ruang

1 4 BLU

Ruang 1 1 2 2 3 3

1 S51 12 1S1015 3 S80

1

1 S20 6 1 S21 6 1 S22 6 1 S90 6 1 S92 8 1 S93 9

INDOOR

SHEET METAL

1 S52 12 1S1025

M M M

t˚ t˚ t˚

t˚ t˚ t˚

t˚ t˚ t˚

LED PCB2 Y1R Y1E Y2E Y3E R3T R2T R1T R8T R9T R10T R4T R5T R6T

4 3 2 1 A S2 (OUTDOOR) (DIS CHA RGE) (ROOM -A ) (ROOM -C) (ROOM -A) (ROOM -C) (CONDENSE R) (ROOM -B) (ROOM-B)

SW2 SW5 SW1 SW3 SW4 OUTDOO R

<GAS PIPE> <LIQUID PIPE>

Z1C~Z4C X1M~X4M

: FERRITE CORE : TERMINAL STRIP

MRM10, MRM20 MRC/W

L

: MAGNETIC RELAY N

: LIVE : NEUTRAL

M1C M1F

: COMPRESSOR MOTOR : FAN MOTO R

Y1E~Y3E : ELECTRONIC EXPANSION VALVE COIL R1T~R6T

SW1 : FORCED OPERATION ON/OFF SW (SW1)

L1R : REACTOR

V2, V3, V5, V6, V11 : VARISTOR

R8T~R10T : THERMISTOR SW2 : SELECT SW (SW2)

Q1L : OVERLOAD PROTECTOR

SA2 FU1, FU2, FU3 AC1, AC2

: SURGE ARRESTER : FUSE

S2~S102 LED1~LED4 LEDA

: CONNECTOR

: PILOT LAMP

SW3 : WIRING ERROR CHECK SW (SW3) SW4 : PRIORITY ROOM SETTING SW (SW4) SW5 : NIGHT QUIET MODE SETTING SW (SW5)

PM1 PCB1, 2 Y1R

: POWER MODULE : PRINTED CIRCUIT BOARD : REVERSING SORENOID VALVE COIL

U, V, W, X11A E1, E2 HR1, HR2

SHEET METAL : TERMI NAL STRIP FIXED PLATE

: CONNECTOR 3D057134B

3MXS68G2V1B, 3MXS68G3V1B

GRN

YLW

X1M

GRN

Z1C GRN

E1 E2

HR1

L1R

HR2

FU3 7

Z5C

POWER SUPPLY L SA2 MRM20 3.15A FU1 V100

RED M1F M

L Z2C AC1 30A V2 MRM10 BL U

N N BRN 1 9 8

6(P)

+ + + S70 BRN OR G

TO INDO OR

UNIT

ROO M B

X2M

Z3C

BL U

AC2 V9

2 PM1

7(N) 1 WHT

U

X11A

M1C

U

1 1 A FU2 5 RED V RED V M RED 1 2 2 3, 15A 4 YLW YLW 3~

3 3 YLW B 3 W BLU BLU

ROOM A X3M

BLU C S10 V3

7

Z4C W

Q1L

1 1 1 M RC/ W PCB1 2 2 3 S15 S40

5 V5 WHT RED BLU 1 4

ROOM C X4M A B C

1 1 2 2 3 3

SHEET METAL

1 S51 12 1S1015 3 S80 1

Z6C

1 S20 6 1 S21 6 1 S22 6 1 S90 6

t˚ t ˚ t ˚

1 S92 8

t˚ t ˚ t ˚

1 S93 9

t˚ t ˚ t ˚

1 S52 12 1S1025 LED PCB2

Y1R M M M

R3T R2T R1T

R8T R9TR10T

R4T R5T R6T

4 3 2 1 A S2 (OU TD O O R)(D I S CHA R GE ) (RO O M -A )(R O OM - C) (RO OM -A ) (R O O M -C) Y1E Y2E Y3E (CONDENSER) (ROOM-B) (ROOM-B)

INDOOR

OUTDOOR

SW2 SW5 SW1 SW3 SW4 <GAS PIPE> <LIQUID PIPE>

Z1C~Z6C FIELD WIRING X1M~X5M

: FERRI TE CORE : TERMI NAL STRI P

MRM10, MRM20 MRC/ W

L : MAGNETIC RELAY N

: LIVE : NEUTRAL

M1C M1F

: COMPRE SS OR MOTOR : FAN MOTOR

Y1E~ Y4E : ELECTRONIC EXPANSION VALVE COIL R1T~R11T : THERMI STOR SW1 : FORCED OPERATION ON/OFF SW (SW1) L1R : REACTOR V2, V3, V5, V9, V100 : VARISTOR

S2~S10 2 : CONNECTOR SW2 : SELECT SW (SW2)

Q1L : OVERLOAD PROTECTOR

SA2 FU1, FU2, FU3

: SURGE ARRESTER : FUSE

LED1~LED4 LEDA

: PILOT LAMP

SW3 : WIRING ERROR CHECK SW (SW3) SW4 : PRIORITY ROOM SETTING SW (SW4)

PM1 PCB1, 2

: POW ER MODULE : PRI NTED CI RCUI T BOARD

AC1, AC2 SW5 : NIGHT QUIET MODE SETTING SW (SW5) Y1R

: REVERSI NG SOREN OI D VALVE COI L

U, V, W, X11A E1, E2 HR1, HR2

: CONNECTOR

SHEET METAL : TERMINAL STRIP FIXED PLATE

3D058434B

FI ELD WI RI NG

BL

K

WH

T

BL

K

WH

T

BLK

WH

T

BLK

WH

T

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

RE

D

BLK

W

HT

GR

N

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

RE

D

BLK

W

HT

GR

N

BLU

BLU

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T Y

LW

OR

G

BLU

B

RN

R

ED

WH

T Y

LW

OR

G

BLU

B

RN

R

ED

WH

T Y

LW

OR

G

BLU

B

RN

R

ED

WH

T W

HT

WH

T W

HT

BLK

BLK

BLK

BLK

BLK

BLK

BLK

GR

Y

BR

N

BLK

GR

Y

BR

N

BLK

GR

Y

YLW

BLK

GR

Y

YLW

BLK

BL

K

BLK

BL

K

279 Lampiran

SiBE121135_A Diagram Pengkabelan

: PROTE

: TE

: TER

: RELA

: CON

: CON

3 3

BL

K

WH

T

BLU

BLU

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T YL

W

OR

G

BLU

BRN

RED

WH

T YL

W

OR

G

BLU

BRN

RED B

LK

BLK

BLK

4MXS68F2V1B, 4MXS68F3V1B

GRN

YLW

X1M

GRN

Z1C

GRN

E1 E2

HR1

L1R

HR2

FU3 7

Z5C

POWER SUPPLY L SA2 MRM20 3.15A FU1 V100

RED M1F M

L Z2C AC1 30A V2 MRM10 BL U

N N BRN 1 9 8

6(P)

+ + + S70 BRN OR G

TO INDO OR

UNIT

ROO M B

X2M

Z3C

BL U

AC2 V9

2 PM1

7(N) 1 WHT

U

X11A

M1C

U

1 1 A FU2 5 RED V RED V M RED 1 2 2 3, 15A 4 YLW YLW 3~

3 3 YLW B 3 W BLU BLU

ROOM A

1 X3M

1

BLU C

OR G D

S10

7

1

V3

M RC/ W PCB1

Z4C W

Q1L

2 2 3 S15 S40 5 V5 WHT RED BLU YLW 1 4

ROOM C X4M A B C D

1 1 2 2 3 3

1 S51 12 1S1015 3 S80 1

Z6C

1 S20 6 1 S21 6 1 S22 6 1 S23 6 1 S90 6 1 S92 8 1 S93 9

ROOM D

X5M t˚ t ˚ t ˚ t˚ t ˚ t˚ t ˚ t˚ t ˚ t˚ t ˚

1 1 2 2

1 S52 12 1S1025 LED PCB2

Y1R M M M

M R3T R2T R1T

R8 T R9 T R1 0 TR1 1 T

R4T R5T R6T R7T

3 3 4 3 2 1 A S2 (OU TD O O R)(D I S CHA R GE ) (RO O M -A )(R O OM - C) (R OO M -A ) (R O OM -C) Y1E Y2E Y3E Y4E (CONDENSER) (ROOM-B) (ROOM-D) (ROOM-B) (ROOM -D)

INDOOR

SHEET METAL OUTDOOR

SW2 SW5 SW1 SW3 SW4 <GAS PIPE> <LIQUID PIPE>

Z1C~Z6C X1M~X5 M

: FERRI TE CORE : TERMI NAL STRI P

MRM10, MRM20 MRC/ W

L : MAGNETIC RELAY N

: LIVE : NEUTRAL

M1C M1F

: COMPRE SS OR MOTOR : FAN MOTOR

Y1E~ Y4E : ELECTRONIC EXPANSION VALVE COIL R1T~R11T

: THERMI STOR SW1 : FORCED OPERATION ON/OFF SW (SW1) L1R

: REACTOR

V2, V3, V5, V9, V100 : VARISTOR

S2~S10 2 : CONNECTOR SW2 : SELECT SW (SW2)

Q1L : OVERLOAD PROTECTOR

SA2 FU1, FU2, FU3

: SURGE ARRESTER : FUSE

LED1~LED4 LEDA

: PILOT LAMP

SW3 : WIRING ERROR CHECK SW (SW3) SW4 : PRIORITY ROOM SETTING SW (SW4)

PM1 PCB1, 2

: POW ER MODULE : PRI NTED CI RCUI T BOARD

AC1, AC2 SW5 : NIGHT QUIET MODE SETTING SW (SW5) Y1R

: REVERSI NG SOREN OI D VALVE COI L

U, V, W, X11A E1, E2 HR1, HR2

: CONNECTOR

SHEET METAL : TERMINAL STRIP FIXED PLATE

3D055495A

4MXS80E2V3B, 4MXS80E3V3B

WHT : WHITE

YLW : YELLOW

ORG : ORANGE

RED : RED

GRN : GREEN

BLU : BLUE

BRN : BROWN

BLK : BLAC K

GRY : GREY

1N ~50Hz 230V

TO INDOOR UNIT

ROOM B

ROOM A

ROOM C

ROOM D

SHEET

METAL

indoor outdoor

: FIELD WIRING

CTIV E EA RTH (SCREW)

RMINA L STRIP

MINAL

Y CONNECTOR

NECTOR

NECTION

L : LIV E

N : NEUTRAL

2TW27576-1B

FI ELD WI RI NG

BL

K

WH

T

BL

K

WH

T

BL

K

WH

T

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

BLU

B

LU

RE

D

BLK

W

HT

GR

N

WH

T

WH

T

OU

TD

OO

R

CO

ND

EN

SE

R

DIS

CH

AR

GE

RO

OM

-A

RO

OM

-B

RO

OM

-C

RO

OM

-D

BLK

GR

Y

BR

N

RE

D

GA

S P

IPE

RO

OM

-A

RO

OM

-B

RO

OM

-C

RO

OM

-D

BLK

GR

Y

YL

W

BLU

LIQ

UID

PIP

E

BLK

BL

K

Z1C~Z6C FERRITE CORE R1T~ R3T THERMISTOR

Q1L OV ERLOA D PROTECTOR

X1M~X5 M TERMINA L STRIP R4T~ R7T PM1 POW ER MODUL E

Y1E~Y 4E ELECTRONIC EXPANSION VALVE COIL R8T~ R11T PCB1, 2 PRINTED CIRCUIT BOA RD

V2, V 3, V 5 VA RIS TOR

S2~S102 CONNECTOR Y1R FOUR WA Y V ALV E COIL

V9, V 100 LED1~L ED4 LIGHT EMITTING DIODE

SHEET META L TERMINAL STRIP FIXED PLATE

SA2 SURGE A RRES TER LEDA F2U FIEL D FUS E

FU1, FU2, FU3 FUS E SW1 FORCED OPERA TION SW (SW1) Q1DI FIEL D EA RTH L EA KA GE

BREA K ER (300 mA) A C1, A C2 CONNECTOR

SW2 OPERA TION MODE S W (SW2)

U, V, W, X11A SW3 WIRING ERROR CHECK SW (SW3)

E1, E2 SW4 PRIORITY ROOM SETTING SW (SW4) HR1, HR2 SW5 NI GHT QUI ET M OD E SETTI N G SW (SW 5)

MRM10, MRM20 MA GNETIC RELAY M1 C COMPRESSOR MOTOR

MRC/W M1 F FA N MOTOR

L1R REA CTOR

Diagram Pengkabelan

SiBE121135_A

Lampiran 280

: PROTE

: TE

: TER

: RELA

: CON

: CON

5MXS90E2V3B, 5MXS90E3V3B

WHT : WHITE

YLW : YELLOW

ORG : ORANGE

RED : RED

GRN : GREEN

BLU : BLUE

BRN : BROWN

BLK : BLAC K

GRY : GREY

1N ~50Hz

230V

TO INDOOR UNIT

ROOM B

ROOM A

ROOM C

ROOM D

ROOM E

SHEET

METAL

indoor outdoor

L : LIV E

: FIELD WIRING

CTIV E EA RTH (SCREW)

RMINA L STRIP

MINAL

Y CONNECTOR

NECTOR

NECTION

N : NEUTRAL

2TW27586-1A O

UT

DO

OR

CO

ND

EN

SE

R

DIS

CH

AR

GE

RO

OM

-A

RO

OM

-B

RO

OM

-C

RO

OM

-D

RO

OM

-E

RO

OM

-A

RO

OM

-B

RO

OM

-C

RO

OM

-D

RO

OM

-E

GA

S P

IPE

LIQ

UID

PIP

E

Z1C~Z6C FERRITE CORE R1T~ R3T THERMISTOR

Q1L OV ERLOA D PROTECTOR

X1M~X6 M TERMINA L STRIP R4T~ R8T PM1 POW ER MODUL E

Y1E~Y 5E ELECTRONIC EXPANSION VALVE COIL R9T~ R13T PCB1, 2 PRINTED CIRCUIT BOA RD

V2, V 3, V 5 VA RIS TOR

S2~S102 CONNECTOR

Y1R FOUR WA Y V ALV E COIL

V9, V 100 LED1~L ED5 SHEET META L T ER MI N AL STRI P FI XED PLAT E SA2 SURGE A RRES TER LEDA LIGHT EMITTING DIODE F2U FIEL D FUS E

FU1, FU2, FU3 FUS E SW1 FORCED OPERA TION SW (SW1) Q1DI

FIEL D EA RTH L EA KA GE

BREA K ER (300 mA) A C1, A C2

CONNECTOR

SW2 OPERA TION MODE S W (SW2)

U, V, W, X11A SW3 WIRING ERROR CHECK SW (SW3)

E1, E2 SW4 PRIORITY ROOM SETTING SW (SW4) HR1, HR2 SW5 NIGHT QUI ET M ODE SETTIN G SW (SW5)

MRM10, MRM20 MA GNETIC RELAY

M1 C COMPRESSOR MOTOR

MRC/W M1 F FA N MOTOR

L1R REA CTOR

SiBE121135_A Diagram Pengkabelan

281 Lampiran

S1W

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

RE

D

OR

G

YL

W

PN

K

BL

U

RE

D

OR

G

YL

W

PN

K

BL

U

Unit Indoor Tipe Wall Mounted

FTXG25/35/50JV1BW(A)

S21

A1P F1U H1 X1M 1 FG

F1U

: FRAME GROUND : FUSE

S25 ~ 3,15A BLK 1 2 H1P, H2P : PILOT LAMP A3P 1 BLK 1 C102 V1 WHT 2 3 M1F : FAN MOTOR

S36 BLK HA MR10 H2 GRN RED 3 OUTDO OR

M1S, M2S : SWING MOTOR 3 BLK 3 C101 TR A N SMI S SI O N

/YLW M1 : STEPPING MOTOR

t˚ A2P

S51 S46

CIRCUIT FG GRN/YLW FIELD WIRING.

A1P~A3P : PRINTED CIRCUIT BOARD

R1T, R2T : THERMISTOR S25~S200 : CONNECTOR

R1T 1

BLK BLK

1 7 S42 1 S32 S41

S200 7 RED

S1W S1C

: OPERATION SWITCH : LIMIT SWITCH

S52 BLK 1 2 1 2 3 4 5 10 6 7 8 9 M X1M : TERMINAL STRIP

1 3 H1P

BLK BLK 8 3 1 BZ 4 BLU M1F

: BUZZER : PROTECTIVE EARTH

BLK BRN H2P BLK ORG PERHATI

AN BLK 1 WHT NOTE THAT OPERATION WILL

S1W 9 BLK 9 t˚ RESTART AUTOMATICALLY IF

W IRE LES S RE MO TE

CO NTRO LLER

SIGNA L B Z RECE IVER

M R2T

M1 S1C

MSW

M1S (MAIN)

MSW

M2S (SUB)

INDOOR

THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN.

3D065507D

FTXS20/25K2V1B, CTXS15/35K2V1B

PCB 2

S27 1

BLK

S26 10

PCB 1

TRANSMISSION

FIELD WIRING.

BLK GRN/YLW LED1 H1P BLK

BLK CIRCUIT

FG2 GRN LED2 H2P B LK

BLK FG1 Z1C GRN

3

LED3 H3P B LK

BLK – RECTIFIER + H3 N=3

RED

2 3 OUTDOOR

t

R1T

SIGNAL RECEIVE

R

B LK 10 BLK 1

– +

IPM200

V1 MR10

F1U

3.15A

H2 WHT

H1 BLK

2

1

X1M

1

PERHATIAN

NOTE THAT OPERATION WILL

RESTART AUTOMATICALLY IF

THE MAIN POWER SUPPLY IS

TURNED OFF AND THEN BACK

ON AGAIN.

1 3 1 2 1 5 1 6 9 12 1 S403 10 S25 S32 S6 S200

Z2C N=2

INDOOR

WIRELESS REMOTE

CONTROLLER S36

INTE LLIGE NT E YE M

6

S602 M

1 4 1

S601

FG1, FG2

F1U

H1~H3

H1P~H3P

: FRAME GROUND

: FUSE

: HARNESS

: PILOT LAMP S E N S OR

t M1S M1F

M1F : FAN MOTOR

PCB 3 R2T M1S : SWING MOTOR

PCB1~PCB4 : PRINTED CIRCUIT BOARD

NOTE) S21

1. PCB4 SHOWS THE CASE OF

R1T, R2T

S6~S602

S1W

Z1C, Z2C

: THERMISTOR

: CONNECTOR

: OPERATION SWITCH

: FERRITE CORE

OPTIONAL CONNECTION. OPTION

PCB 4 X1M : TERMINAL STRIP

: PROTECTIVE EARTH

3D073474C

IN T EL LI G E N T EY E SE NS O R

BL

K BL

K

BL

K

BL

K

BL

K

BL

K BL

K

BL

K BL

K

BL

K

OR

G

YLW

B

LU

RE

D

BLK

WH

T BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

BL

K

H3

Diagram Pengkabelan

SiBE121135_A

Lampiran 282

FTXS35/42/50K2V1B, FTXS25/35/42/50J2V1B, ATXS20/25/35/42/50G2V1B

PCB3

S49

S46

PCB1

1

FU1 X1M 2 1

LED1 BLK 1 BLK

F1U H1 BLK 1 3

H1P BLK

BLK

~ C102 V1

3,15A WHT 2 OUTDOOR

LED2 H2P

LED3

- BLK

BLK

BLK

BLK

C101

MR10 H2 RED 3

GRN

GRN FIELD WIRING.

H3P 9 BLK 9 TRANSMISSION H3

CIRCUIT

/ YLW

PERHATIAN

SW1 S21

t ̊

FG

HA 7 S1

NOTE THAT OPERATION WILL RESTART

AUTOMATICALLY IF THE MAIN POWER

SUPPLY IS TURNED OFF AND THEN BACK ON

AGAIN.

BZ

PCB4

RTH1

R1T

1

S26

S25

BLK 1 BLK

RED

4 BLU

BRN MS

ORG 3~

BZ

C101, C102

FG

F1U

: BUZZER

: CAPACITOR

: FRAME GROUND

: FUSE

BLK 1 WHT H1P~H3P : PILOT LAMP 4 BLK 4 S47 S32 S41 M1F MR10 : MAGNETIC RELAY

INTELLIGENT EYE

SENSOR

WIRELESS

REMOTE

PCB2

1 3 1

S48

1 3

2 16 8 1012 14 2 5 3 4 6 15 13 11 9 7 1

t ̊

R2T MSW MSW MSW

INDOOR

M1F

M1S~M3S

PCB1~PCB4

R1T, R2T

S1~S49

SW1

V1

: FAN MOTOR

: SWING MOTOR

: PRINTED CIRCUIT BOARD

: THERMISTOR

: CONNECTOR

: OPERATION SWITCH

: VARISTOR

CONTROLLER

M1S

M2S M3S X1M : TERMINAL STRIP

: PROTECTIVE EARTH

3D058246G

FTXS60/71GV1B

PCB3

S49

S46

PCB1

1

FU1 X1M 2 1

LED1 BLK 1 BLK

F1U H1 BLK 1 3

H1P BLK

BLK

~ C102 V1

3,15A WHT 2 OUTDOOR

LED2 H2P

LED3 H3P

BLK

BLK

BLK

BLK

C101

MR10 H2

TRANSMISSION H3

RED 3

GRN

GRN/Y LW

9 BLK 9

SW1

S21

t ̊

CIRCUIT

FG

PERHATIAN

NOTE THAT OPERATION WILL RESTART

AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN.

BZ RTH1

R1T

HA 7 S1

RED

BZ

C101, C102

FG

: BUZZER

: CAPACITOR

: FRAME GROUND

PCB4

1 BLK S25

1

4 BLU

BRN

F1U

MS H1P~H3P

: FUSE

: PILOT LAMP

S36 BLK ORG 3~ MR10 M1F

: MAGNETIC RELAY : FAN MOTOR

3 BLK 1 WHT M1S, M2S : SWING MOTOR 4 S47 S32 S41 M1F PCB1~PCB4 : PRINTED CIRCUIT BOARD

PCB2

1 3 1

S48

2 16 8 10 12 14 15 13 11 9 7 R1T, R2T

S1~S49

SW1

V1

X1M

: THERMISTOR

: CONNECTOR

: OPERATION SWITCH

: VARISTOR

: TERMINAL STRIP : PROTECTIVE EARTH

WIRELESS REMOTE

CONTROLLER

1 3 t ̊

R2T

MSW

M1S

MSW

M2S

INDOOR

3D064800D

SIGNAL

RECEIVER

INTELLIGENT EYE SENSOR

SIGNAL RECEIVER

FIELD WIRING

BLK

BLK

BLK

BLK

BLK

BLK

BLK

BLK

BLK

R

ED

OR

G

YLW

PN

K

BLU

RE

D

OR

G

YLW

PN

K

BLU

BLK

R

ED

OR

G

YLW

PN

K

BLU

RE

D

OR

G

YLW

PN

K

BLU

RE

D

OR

G

YLW

PN

K

BLU

SiBE121135_A Diagram Pengkabelan

283 Lampiran

Tipe Floor Standing

FVXG25/35/50K2V1B

PCB3

S27

1

WHT

S26 PCB1 1 ~ ~

V1 F1U 1 S2

BLK

X1M 1

1 2 RECTIFIER

3 3 3,15A WHT 2 3 outdoor

PCB2 S56 S57 BLK BLK S46

MR10 3

RED 3 GRN GRN/YLW

1 1 C102 E3 FIELD WIRING.

H1P H2P H3P 9

TRANSMISSION CIRCUIT

9

5

FG

GRN

PERHATI

AN NOTE THAT OPERATION

WILL RESTART AUTOMATICALLY IF THE

MAIN POWER SUPPLY IS

W HT

M YLW

S50 N=1 S30

1 RED 1

C101 7 S1BRN S10

7 RED

TURNED OFF AND THEN BACK

ON AGAIN.

Y1E ORG 4 4 BLU

BLU B RN

M M1F

RED 6 S21 HA ORG

6 1 1 WHT S51 S6 t˚

RE D 1 BLU 1 S32 S35

M1S M ORG 2 YLW 1

BLK BLK R2T

BLK BLU 5

4 S34 1 3S331 t˚

5 Z1C BLK

YLW t˚ t˚ BRN R1T

indoor R4T R3T

WIRELESS

REMOTE

F1U

H1P~H3P

M1F M1S

: PROTECTIVE EARTH : FUSE

: PILOT LAMP

: FAN MOTOR : SWING MOTOR

S1~S57

S1W S2W(4)

X1M E3

: CONNECTOR : OPERATION SWITCH

: UPWARD AIR FLOW LIMIT SWITCH : TERMINAL STRIP : EARTH TERMINAL (HEAT EX.)

CONTROLLER PCB1~PCB3 : PRINTED CIRCUIT BOARD Y1E : ELECTRONIC EXPANSION VALVE COIL

R1T~R4T : THERMISTOR Z1C : FERRITE CORE 3D069838A

FVXS25/35/50FV1B

PCB3

S2W(4)

S4W

S27

PCB2

S26

~ ~ RECTIF IER

V1 F1U

3,15A

H1

H2 GRN

BLK WHT RED

X1M 1 2 3

1

2 3 outdoor

WIRE LESS RE MOTE

CO NTRO LLER

PCB4

S47

S46

TRANSMISSION

CIRCUIT

H3

V2

SA1 E1

E4

GRN

GRN/YLW

E3 PERHATIAN

NOTE THAT OPERATION

WILL RESTART

AUTOMATICALLY IF THE

MAIN POWER SUPPLY IS

LED1

LED2

7 S1 RED

TURNED OFF AND THEN BACK

ON AGAIN.

H1P H2P

RED

S42 1

S21 HA

4 BLU BRN ORG

1 WHT

M M1F

t

F1U H1P,H2P M1F

: PROTECTIVE EARTH : FUSE : PILOT LAMP

: FAN MOTOR

M1S M ORG YLW PNK

S48 S49 R1T

M1S M2S

: SWING MOTOR : LOWER AIR OUTLET MOTOR

BLU 6 PCB1 PCB1~PCB4 : PRINTED CIRCUIT BOARD

M2S M

RED

ORG YLW PNK

S41 1 t

S32

R1T,R2T S1~S49 S1W S2W(4)

: THERMISTOR : CONNECTOR : OPERATION SWITCH : UPWARD AIR FLOW LIMIT SWITCH

indoor

BLU 5 R2T S4W X1M E3 E4

: AIR OUTLET SELECTION SWITCH : TERMINAL STRIP : EARTH TERMINAL (HEAT EX.)

: EARTH TERMINAL (SHIELD PLATE)

3D055953A

FIE LD WIRING .

S2W(4)

SIGNAL RECEIVER S1W

SIGNAL RECEIVER

S1W

E3

Diagram Pengkabelan

SiBE121135_A

Lampiran 284

Outdoor

Perhatian

Terminal for Transmission Operation will restart automatically centralized control circuit if the main power supply is turned

off and then back on again.

Signal receiver

Signal receiver Switch box (indoor)

Indoor

Infrared remote control

Indoor unit PCB2 Signal receiver

C1 Capacitor O1TR Phase control circuit

F1M Thermal protector (M1F Embedded) R1T, R2T Thermistor

F1U Fuse (3.15, 250V) S1~S32, RTH1 Connector

H1P~H3P Light emitting diode S1W Operation switch

M1F Motor (fan) X1M Terminal strip

PCB1 Printed circuit board Z1C Noise filter (Ferrite core)

: Field wiring Colors: BLK: Black ORG: Orange WHT: Putih

: Protective earth (screw) BLU: Blue PNK: Pink YLW: Kuning

: Connector BRN: Brown PRP: Purple GRN: Hijau

: Wire clamp GRY: Grey RED: Merah

Tipe Floor/Ceiling Suspended Dual

FLXS25/35/50/60BAVMB

PCB3

LED LED LED

H1P H2P H3P

PCB4

S25 S24

PCB1 S37

S36

C70

PCB2 H1

Fu 3.15A

H2

TRANSMISSION H3

BLK

WHT

RED

GRN/YLW

X1M

1

2

3

FIELD WIRING.

1

2 3

outdoor

S1W

SIGNAL

RECEIVER

S27

S31

t

S26

S32

t

HA

S7 S21

S6

H4 H5

H6

X11A

CIRCUIT

indoor

PERHATIAN

NOTE THAT OPERATION WILL

RESTART AUTOMATICALLY IF

THE MAIN POWER SUPPLY IS

TURNED OFF AND THEN BACK

ON AGAIN.

R1T R2T X21A

M M

C70

: PROTECTIVE EARTH

: RUNNING

CAPACITOR

PCB1~PCB4

R1T~R2T

: PRINTED CIRCUIT BOARD

: THERMISTOR

1~ M1F FU : FUSE

S6~S37, X11A, X21A : CONNECTOR

WIRELESS M1S t H1P~H3 P : PILO T LAMP

S1W : OPERATION SWITCH (SW7)

REMOTE CONTROLLER 100C

M1F

M1S

: FAN MOTOR

: SWING MOTOR

X1M : TERMINAL STRIP

3D033909F

Tipe Duct Connected

FDXS25/35E7VMB, FDXS50/60C7VMB

2TW32966-1

SiBE121135_A Diagram Pengkabelan

285 Lampiran

TO O

UTD

OO

R U

NIT

Tipe Ceiling Mounted Cassette

FCQG35/50/60FVEB

INDOOR UNIT

GRN

R2T R3T S1L

A4P A5P X1M

PNK T2

INPUT FROM 35 ~60 CLA SS

t˚ t˚ SS1 H1P WHT T1 OUTSIDE (NOTE 9)

X2M A1P X2A H2P BS1 YLW F2 CENTRAL REMOTE

F1 U NE V1R+C105 SS2 H3P ORG F1 CONTROLLER (NOTE 2) TO OUTDOOR 1 BLK + X18A X17A X15A H4P BLU P2 P2 R1T UNIT (NOTE 8) Z1F BLK P1 P1

2 WHT - SS1 X24A X1A X1A

3 RED NOTE)3 RECEIVER/DI SPLAY

UNIT NORM. EMG.

WI RE D RE M OTE C O NT R OL L E R (OP TI ONA L A CCE S S O RY )

X27A X30A

(NO TE 5 ) H05VV-U4G2. 5 GRN/YLW

PS HAP (NOTE 7)

TERMI NAL FOR OPERATI ON DISPLAY

RC

TC

X33A

X65A

RED WHT

X1A

C21 + PS

A2P

MSW M4S

KI PAS OPERATION

CO M P RE S S OR OPERATION

(NOTE 3) X20A

Z1C

N=1

X70A

X7A Lampu

X9A

MSW M3S

X4 X3 X2

KFR

X1

KCR X 2 A WHTORGB RN BLU RED

WHT

X36A X8A X10A X4A (NOTE 3)

X2A (NOTE 3) MSW M2S

F1U KHuR Y2

ADAPTOR FOR WI RI NG

(OPTI ONAL ACCESS ORY)

M1F MS X16A

X35A

(NOTE 3) MS

MSW M1S

YC t ̊ (NOTE 3) M1P CN1 X1A F2U

NOTES

(NOTE 4) R1T A3P A6P A7P

SENSOR KIT 1. : TERMINAL BLOCK , : CONNECTOR : FIELD

WIRING 2. IN CASE USING CENTRAL REMOTE CONTROLLER, CONNECT IT TO

THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION

(OPTI ONAL ACCESSORY)

IN CASE OF SI MULTANEOUS OPERATI ON SYSTEM

MANUAL.

3. X2A, X8A, X33A, X35A, X36A ARE CONNECTED WHEN THE OPTIONAL ACCESSORIES ARE BEING USED. IN CASE OF USING

INDOOR UNIT (MASTER)

X2M

INDOOR UNIT (SLAVE)

X2M

X8A X36A

R1T A3P

X24A

AN AUTO CLEAN PANEL, SEE THE WIRING DIAGRAM OF IT.

1 1 X2A

4. CONNECT POWER OF ADAPTOR FOR WIRING TO TERMINAL 2 2

BLOCK (X2M) OF INDOOR UNIT DIRECTLY.

X1 M 3 3

A2P A1P X2M

5. IN CASE OF MAIN/SUB OVERCHANGE, SEE THE INSTALLATION MANUAL ATTACHED TO REMOTE CONTROLLER.

6. SYMBOLS SHOWS AS FOLLOWS : RED : RED BLK : BLACK WHT :

X33A

CONTROL BOX

X35A

WHITE YLW : YELLOW GRN : GREEN ORG : ORANGE BRN : BROWN PNK : PINK GRY : GRAY BLU : BLUE

7. SHOWS ONLY IN CASE OF PROTECTED PIPES. USE H07RN-F IN CASE OF NO PROTECTION.

8. FOR THE DETAIL, SEE WIRING DIAGRAM ATTACHED TO OUTDOOR UNIT.

9. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED OFF OR ON/OFF CONTROL OPERATION CAN BE SELECTED BY THE REMOTE CONTROLLER. SEE INSTALLATION MANUAL FOR MORE DETAILS.

REMOTE CONTROLLER

INDOOR UNIT RECEIVER/DISPLAY UNIT (ATTACHED TO WIRELESS REMOTE CONTROLLER)

CONNECTOR FOR OPTIONAL PARTS A1P PRINTED CIRCUIT BOARD X2A CONNECTOR

(SENSOR KIT) A2P PRINTED CIRCUIT BOARD

A3P PRINTED CIRCUIT BOARD PRINTED CIRCUIT BOARD X8A CONNECTOR

(AUTO CLEAN PANEL) (HUMIDITY SENSOR UNIT) A4P PRINTED CIRCUIT BOARD C21 CAPACITOR A5P PUSH BUTTON (ON/OFF) X24A CONNECTOR (WIRELESS

REMOTE CONTROLLER) C105 CAPACITOR BS1 H1P

LIGHT EMITTING DIODE (ON-RED) F1U FUSE (F, 5A, 250V) X33A CONNECTOR (ADAPTOR

FOR WIRING) Lampu LIGHT EMITTING DIODE (SERVICE MONITOR GREEN)

H2P

LIGHT EMITTING DIODE (TIMER-GREEN) X35A CONNECTOR (GROUP

CONTROL ADAPTOR)

H3P

LIGHT EMITTING DIODE (FILTER SIGN-RED) M1F MOTOR (INDOOR FAN) X36A CONNECTOR (AUTO

CLEAN PANEL) M1P MOTOR (DRAIN PUMP) H4P

LIGHT EMITTING DIODE (DEFROST-ORANGE) M1S-M4S MOTOR (SWING FLAP) R1T THERMISTOR (AIR)

SS1 SELECTOR SWITCH (MAIN/SUB) R2T·R3T THERMISTOR (COIL)

S1L FLOAT SWITCH SS2 SELECTOR SWITCH (WIRELESS ADDRESS SET)

SS1 SELECTOR SWITCH (EMERGENCY)

V1R DIODE BRIDGE ADAPTOR FOR WIRING X1M TERMINAL BLOCK F1U FUSE ( B , 5A, 250V) X2M TERMINAL BLOCK F2U Z1C FERRITE CORE

(NOISE FILTER) KCR MAGNETIC RELAY KFR MAGNETIC RELAY

Z1F NOISE FILTER KHuR MAGNETIC RELAY (Hu) PS POWER SUPPLY CIRCUIT RC SIGNAL RECEIVER

CIRCUIT

TC SIGNAL TRANSMISSION CIRCUIT

WIRED REMOTE CONTROLLER R1T THERMISTOR (AIR)

3D074344

Diagram Pengkabelan

SiBE121135_A

Lampiran 286

: COLOR OF WIRE. : (MAR KE D) C OLOR OF WIR E CONN ECT OR. : COLOR OF PCB CONNECTOR.

IN CASE OF SIMUL TANEOUS

OPERATION SYSTEM

TO OUTDOOR

UNIT INDOOR UNIT INDO OR UNIT

(MASTER) (SLAVE)

WIRED REMOTE CONTROLLER

SWITCH BOX

REMOTE (SEE NOTE 3)

CONTROLLER

NOTES:

1. IN CASE OF USING A REMOTE CONTROLLER, CONNECT IT TO THE UNIT IN ACCORDANCE TO THE ATTACHED INSTALLATION MANUAL.

2. X24A IS CONNECTED WHEN THE WIRELESS REMOTE CONTROLLER KIT IS BEING USED.

3. REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM. SEE TECHNICAL DATA AND CATALOGS, ETC. BEFORE CONNECTING.

4. GROUND THE SHIELD OF THE REMOTE CONTROLLER WIRE TO THE INDOOR UNIT. (IN CASE OF USING SHIELD WIRE)

: TERMINAL

: CONNECTOR

: WIRE CLAMP

: FIELD WIRING

RED: RE D

BLK: BLACK

WHT: WHITE

YLW:

YELLOW

GRN: GREEN

FFQ25/35/50/60B9V1B

A1P PRINTED CIRCUIT BOARD WIRED REMOTE CONTROLLER WIRELESS REMOTE CONTROLLER

(RECEIVER/DISPLAY UNIT) CONNECTOR FOR OPTIONAL PARTS

C1 CAPACITOR (M1F) R1T THERMISTOR (AIR) X33A CONNECTOR (ADAPTOR FOR WIRING)

F1U FUSE (F5A, 250V) SS1 SELECTOR SWITCH (MAIN/SUB) A3P PRINTED CIRCUIT BOARD

Lampu

LIGHT EMITTING DIODE (SERVICE MONITOR GREEN)

A4P PRINTED CIRCUIT BOARD X35A CONNECTOR

(GROUP CONTROL ADAPTOR) BS1 PUSH BUTTON (ON/OFF) KPR MAGNETIC RELAY (M1P)

H1P LIGHT EMITTING DIODE (ON-RED)

X40A CONNECTOR (ON/OFF INPUT FROM OUTSIDE) M1F MOTOR (INDOOR FAN)

M1P MOTOR (DRAIN PUMP) H2P LIGHT EMITTING DIODE

(TIMER-GREEN) X60A X61A

CONNECTOR (INTERF AC E A DA PT OR F OR S K Y-AIR SE RIE S)

M1S MOTOR (SWING FLAP)

Q1M THERMO SWITCH (M1F EMBEDDED)

H3P LIGHT EMITTING DIODE (FILTER SIGN-RED)

R1T THERMISTOR (AIR) H4P LIGHT EMITTING DIODE (DEFROST-ORANGE) R2T THERMISTOR (COIL-1)

R3T THERMISTOR (COIL-2) SS1 SELECTOR SWITCH (MAIN/SUB) S1L FLOAT SWITCH

T1R TRAN SF ORM ER (220-240V/22V ) SS2 SELECTOR SWITCH (WIRELESS ADDRESS SET) V1TR PHASE CO NTRO L CIRCUIT

X1M TERMINAL STRIP X2M TERMINAL STRIP

RC SIGNAL RECEIVER CIRCUIT TC SIGNAL TRANSMISSION CIRCUIT

3TW26476-1

TO O

UT

DO

OR

UN

IT

SiBE121135_A Diagram Pengkabelan

287 Lampiran

NOTE 1: SEPARATE POWER SUPP LY

1~50Hz 230V

YLW

WH

T

P1

Tipe Ceiling Suspended

FHQ35/50/60BWV1B

IN CASE OF SIMULTA NEOUS OPERATION SYSTEM (NOTE 6)

R1T

R3T

R2T :CONNE CTOR DIS CRI MI NA TI ON COL OUR FOR COM P ONE NTS. :CONNE CTOR COL OUR FOR COM P ONE NTS.

INDOOR UNIT INDOOR UNIT t ̊ :CONNE CTOR COL OUR FOR P RI NTE D C I RCUI T B OA RD. (MASTER) (SLAVE)

TO OUTDOOR X2M A1P

t˚ t ̊ YLW

WHT X1M

SS1 1 1 UNI T (NOTE 4) 2 2 3 3

F1U BLK

WHT

X61A X19A X18A YLW X17A

X10A T1R

X11A

X24A P2

SS1 X5A

P2 P1 R1T

WIRED REMOTE CONTROLLER (OPTIONAL ACCESSORY)

X2M

X2M (NOTE 10)

RED X27A X60A

t˚ NORM.

EM G.

GRY (NOTE 7) PRP BLU

REMOTE CONTROLLER

H05VV-U4G2.5 A1P A2P A3P KPR X26A C1

NOTES 1. : TE RM I NA L B L O CK

: CO NNE CT OR : SHORT CI RCUIT CONNECTOR

SS1

SS2

H1P H2PBS1 H3P X25A

V1TR X20A RED

BLK

M 1 ~ Q1M

X24A X2A H4P X29A M1F

: CO NNE CT OR X1A X1A RC TC KAR BLK MSW

2. : FI E L D WI R I N G 3. IN CASE OF

SIMUL TANE OUS OPE RATION INDOOR UNI T SYS TEM, SEE THE INDOOR UNI T WI RING ONLY.

WIRELESS REMOTE CONTROLLER (RECEIVER/DISPLAY UNIT) (OPTIONAL ACCESSORY)

X40A X33A

X35A HAP

X14A

BLK 1~ M1S

S1C

X15A X5 0A X 3 3A X2 5 A 4. FOR THE DE TA IL , S EE WI RI NG DIA GRA M A TTACHE D TO OUTDOOR UNI T.

5. IN CAS E USI NG CE NTRAL RE M OTE CONTROL LE R, CONNE CT I T TO THE UNI T

X15A (NOTE 8)

X40A A1P C1 T1R IN A CCORDA NCE WI TH THE A TTA CHE D I NS TAL LA TI ON MA NUAL .

8. IN CAS E I NS TAL LI NG THE DRAI N P UMP (M 1P ), RE M OVE THE JUM PE R CONNE CTOR OF X 15 A

X61A 6. IN CAS E OF CONNE CTI ON UNI TS V A RIE S A CCORDI NG TO THE COM BI NA TI ON S YS TE M, A ND E XE CUTE THE A DDI TI ONAL WI R I NG FOR FL OA T S WI TCH A ND DRAI N P UMP .

X60A X1M X2M X35A X24 A CONTROL BOX

CONFIRM TECHNICAL GUIDE A ND CA TAL OGS, ETC. BE FORE CONNECTING. 7. IN CAS E OF MA I N/S UB CHA NGE OV E R,

SEE THE I NS TAL L A TI ON M A NUA L A TTA CHE D TO RE M OTE CONTROL LE R.

9. SYMBOLS SHOW AS FOLL OWS : BLK : B LACK RED : RED BLU : BLUE WHT : WHITE P NK : PI NK YL W : YELL OW GRY : GRAY PRP : P URP LE. 10. SHO WS ONL Y I N CA SE OF P ROTE CTE D

PIP ES . US E H07 RN -F IN CA SE OF NO PROTE CTI ON.

3D074574A

Ceiling Mounted Built-in Type

FDBQ25B8V1

NOTES:

outdoor indoor

1. WHEN USING THE CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO THE UNIT.

2. THE REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM. SEE TECHNICAL MATERIALS AND CATALOGUES, ETC. BEFORE CONNECTING.

WIRED REMOTE CONTROLLER (OPTIONAL)

COLORS: BLK: BLACK ORG: ORANGE

WHT: WHITE BLU: BLUE RED: RED

FIELD WIRING

TERMINAL

: CONNECTOR

: WIRE CLAMP

: PROTECTIVE EARTH (SCREW)

ADAPTOR FOR WIRING

Power cable 220VAC/3A

110VDC/0.3A

A1P PRINTED CIRCUIT BOARD R1T THERMISTOR (AIR) ADAPTOR FOR WIRING FIELD SUPPLY

T1R POWER SUPPLY TRANSFORMER (TRANSFORMER 220-240V/218V)

R2T THERMISTOR (LIQUID) RyH MAGNETIC RELAY K1R MAGNETIC RELAY

R3T THERMISTOR (COIL) Q1L THERMAL PROTECTOR EH ELECTRICAL HEATER KIT

C1R CAPACITOR (FAN) RyF1-4 MAGNETIC RELAY (FAN) CONNECTOR FOR OPTIONAL PARTS F1U FUSE (5A, 250V) SS1 SELECTOR SWITCH (EMERGENCY) X60 A, X6 1A CONNECTOR (INTERFACE ADAPTOR FOR SKY AIR/US SERIES) F1T THERMAL FUSE (152˚C) (M1F

EMBEDDED) X1M TERMINAL STRIP X2M TERMINAL STRIP X33A CONNECTOR (ADAPTOR FOR WIRING)

Lampu

LIGHT EMITTING DIODE (SERVICE MONITOR-GREEN)

RC SIGNAL RECEIVER CIRCUIT X35A CONNECTOR (GROUP CONTROL ADAPTOR)

TC SIGNAL TRANSMISSION CIRCUIT X40A CONNECTOR (REMOTE ON/OFF FORCED OFF)

M1F MOTOR (FAN) 2TW25856-1B

(NOTE 8)

TO

OU

TD

OO

R U

NIT

A1P PRINTED CIRCUIT BOARD BS1 PUS H B UTTON S WI TCH (ON/ OFF) C1 CAPACITOR (M1F) H1P PILOT LAMP

(ON-RED) F1U FUSE (F5A 250V) Lampu

FLASHING LAMP (SERVICE MONITOR GREEN)

H2P PI LOT LAMP (TI MER -GREEN) KAR MAGNETIC RELAY (M1S) H3P PI LOT LAMP (FI LTER SI GN -RED)

KPR MAGNETIC RELAY (M1P) M1F MOTOR (INDOOR FAN) H4P PI LOT LAMP

(DEFROST -ORANG E)

M1S MOTOR (SWING FLAP) Q1M T HE RM A L P RO T E CT O R ( M1 F E M B E DDE D) SS1 SELECTOR SWITCH

(MAIN/SUB) R1T THERMISTOR (AIR) R2T THERMISTOR (COIL-1) SS2 SELECTOR SWI TCH

(WI RELESS ADDRES S SET)

R3T THERMISTOR (COIL-2) S1C LIMIT SWITCH (SWING FLAP) CO NNE CT O R FO R OP TI O NA L P A RTS SS1 SELECTOR S WI TCH (E MERGE NCY ) X15A CO NNE CT O R (FL OA T S WI TCH) T1R TRA NS FORM E R (22 0 -2 4 0V/ 2 2V ) X24A CO NNE CT O R

(WIREL ESS REM OTE CONTROLLE R) V1TR TRIA C (P HASE CONTROL CIRCUI T) X1M TERMINAL BLOCK X25A CONNECTOR (DRAIN PUMP) X2M TERMINAL BLOCK X33A CONNECTOR (ADAPTOR FOR WIRING)

RC SIGNAL RECEIVER CIRCUIT X35A CONNECTOR (GR O UP C ONT R OL A DA P T OR) TC SI GNAL TRA NS M IS SI ON CI RCUI T

WIRED REMOTE CONTROLLER X40A CONNECTOR (ON/ OFF I NP UT FROM OUTSI DE ) R1T THERMISTOR (AIR)

SS1 SE LE CTOR S WI TCH (M AI N/ S UB ) X60A X61A

CONNECTOR (INTERFACE ADAPTOR FOR SKY AIR SERIES) WI RE L E S S RE M O TE C ON TR OL L E R

(RE CE I V E R/ D I S P L A Y UNI T) A2P PRINTED CIRCUIT BOARD

A3P PRINTED CIRCUIT BOARD

1 2

3

Diagram Pengkabelan

SiBE121135_A

Lampiran 288

FBQ35/50C8VEB

1N~220-240V 50Hz 1N~220V 60Hz

COLORS: BLK : BLACK BLU : BLUE BRN : BROWN GRY : GREY ORG : ORANGE PNK : PINK RED : RED WHT : WHITE YLW : YELLOW GRN : GREEN

TRANSMISSION WIRING CENTRAL REMOTE CONTROLLER NOTE 2

WIRED REMOTE CONTROLLER (OPTIONAL ACCESSORY)

COMMON POWER

SUPPLY NOTE 4

NOTES

1. USE COPPER CONDUCTORS ONLY.

2. WHEN USING THE CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO THE UNIT.

: LIVE

FIELD WIRING

SWITCH BOX (INDOO R)

3. THE REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM. SEE TECHNICAL MATERIALS AND CATALOGUES, ETC. BEFORE CONNECTING.

4. REFER TO INSTALLATION MANUAL.

: NEUTRAL : CONNECTOR

: WIRE CLAMP : PROTECTIVE EARTH (SCREW)

2TW31276-1A

FBQ60C8VEB

1N~220-240V 50Hz 1N~220V 60Hz

COMMON POWER SUPPLY NOTE 4

ONLY FOR 60 CLASS

indoor

COLORS: BLK : BLACK BLU : BLUE BRN : BROWN GRY : GREY ORG : ORANGE PNK : PINK RED : RED WHT : WHITE YLW : YELLOW GRN : GREEN

TRANSMISSION WIRING CENTRAL REMOTE CONTROLLER NOTE 2

WIRED REMOTE CONTROLLER (OPTIONAL ACCESSORY)

NOTES: 1. USE COPPER CONDUCTORS ONLY. 2. WHEN USING THE CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO THE

UNIT. 3. THE REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM.

SEE TECHNICAL MATERIALS AND CATALOGUES, ETC. BEFORE CONNECTING.

4. REFER TO INSTALLATION MANUAL

FIELD WIRING

: LIVE : NEUTRAL : CONNECTOR

SWITCH BOX (INDOOR)

: WIRE CLAMP : PROTECTIVE EARTH (SCREW)

2TW31296-3

INDOOR UNIT C O N NE C T O R O PTI O N AL A CC ESS O R Y WIRED REMOTE CONTROLLER

A1P PRINTED CIRCUIT BOARD X28A CONNECTOR (POWER SUPPLY FOR WIRING)

R1T THERMISTOR (AIR)

A2P PRINTED CIRCUIT BOARD (FAN) SS1 SELECTOR SWITCH (MAIN/SUB)

C1 CAPACITOR X33A CONNECTOR (FOR WIRING)

F1 U, F2 U FUSE (T, 5A, 250V) X35A CONNECTOR (ADAPTER)

F4U FUSE (T, 6.3A, 250V) X85A CONNECTOR (FOR MULTI ZONING)

Lampu LIGHT EMITTING DIODE (SERVICE MONITOR-GREEN)

KPR, K1R MAGNETIC RELAY L1R REACTOR M1F MOTOR (FAN)

M1P MOTOR (DRAIN PUMP) PS SWITCHING POWER SUPPLY Q1DI EARTH LEAK DETECTOR R1 RESISTOR (CURRENT LIMITING)

R2 CURRENT SENSING DEVICE R1T THERMISTOR (SUCTION AIR) R2T THERMISTOR (LIQUID) R3T THERMISTOR (COIL)

SS1 SELECTOR SWITCH (EMERGENCY) S1L FLOAT SWITCH V1R DIODE BRIDGE V2R POWER MODULE

X1M TERMINAL STRIP (POWER SUPPLY) X2M TERMINAL STRIP (CONTROL) Z1C NOISE FILTER (FERRITE CORE) Z1F NOISE FILTER

RC SIGNAL RECEIVER CIRCUIT TC SIGNAL TRANSMISSION CIRCUIT

INDOOR UNIT CONNECTOR OPTIONAL ACCESSORY WIRED REMOTE CONTROLLER

[A1P] PRINTED CIRCUIT BOARD X28A CONNECTOR (POWER SUPPLY FOR WIRING) R1T THERMISTOR (AIR)

A2P PRINTED CIRCUIT BOARD (FAN) X33A CONNECTOR (FOR WIRING) SS1 SELECTOR SWITCH (MAIN/SUB) A3P PRINTED CIRCUIT BOARD (CAPACITOR) X35A CONNECTOR (ADAPTER)

C1, C2, C3 CAPACITOR X85A CONNECTOR (FOR MULTI ZONING)

F1U FUSE (T,5A,250V)

F3U FUSE (T,6.3A,250V)

Lampu LIGHT EMITTING DIODE (SERVICE MONITOR-GREEN)

KPR, K1R MAGNETIC RELAY

L1R REACTOR

M1F MOTOR (FAN)

M1P MOTOR (DRAIN PUMP)

PS SWITCHING POWER SUPPLY

Q1DI EARTH LEAK DETECTOR

R2 CURRENT SENSING DEVICE

R3, R4 RESISTOR (ELECTRIC DISCHARGE)

R1T THERMISTOR (SUCTION AIR)

R2T THERMISTOR (LIQUID) R3T THERMISTOR (COIL) R5T THERMISTOR NTC (CURRENT LIMITING) SS1 SELECTOR SWITCH (EMERGENCY)

S1L FLOAT SWITCH V1R DIODE BRIDGE V2R POWER MODULE X1M TERMINAL STRIP (POWER SUPPLY)

X2M TERMINAL STRIP (CONTROL) Z1C, Z2C NOISE FILTER (FERRITE CORE) Z1F NOISE FILTER RC SIGNAL RECEIVER CIRCUIT

TC SIGNAL TRANSMISSION CIRCUIT

SiBE121135_A Diagram Pengkabelan

289 Lampiran

3. Prosedur Penghapusan (Buku Kecil No.)

Lihat buku kecil berikut untuk prosedur penghapusan.

3MKS50E3V1B, 4MKS58E3V1B, 4MKS75F2V1B, 3MXS40K2V1B, 3MXS52E3V1B, 3MXS68G2V1B, 4MXS68F2V1B

Lihat Si121174.

3AMX52E3V1B Lihat SiBE121021_C.

5MKS90E2V3B, 4MXS80E2V3B, 5MXS90E2V3B Lihat Si121176.

3MXS40K3V1B, 3MXS52E4V1B, 3MXS68G3V1B,

3AMX52E4V1B, 4MXS68F3V1B Lihat Si121291_A.

4MXS80E3V3B, 5MXS90E3V3B Lihat Si121292_A.

FTXG25/35/50JV1BW(A) Lihat Si041256.

CTXS15/35K2V1B FTXS20/25K2V1B Lihat Si041258.

FTXS35/42/50K2V1B Lihat Si041259.

FTXS25/35/42/50J2V1B Lihat Si041049.

FTXS60/71GV1B Lihat Si041255_A.

FVXG25/35/50K2V1B Lihat Si061263.

FVXS25/35/50FV1B Lihat Si061262_A.

FLXS25/35/50/60BAVMB Lihat Si051261_A.

ATXS20/25/35/42/50G2V1B Lihat Si041252_A.

Seri FDXS, Seri FCQG, Seri FFQ, Seri FHQ, Seri FDBQ, Seri FBQ

N/A

Lampiran 290

Prosedur penghapusan (Buku Kecil No.)

SiBE121135_A

Riwayat Revisi

Bulan/Tahun Versi Isi yang Direvisi

03 / 2012 SiBE121135 Edisi pertama

01 / 2013

SiBE121135_A

Penambahan model: 3MXS40K3V1B, 3MXS52E4V1B, 3MXS68G3V1B, 4MXS68F3V1B, 4MXS80E3V3B, 5MXS90E3V3B, 3AMX52E3V1B, 3AMX52E4V1B, FTXS35/42/50K2V1B ATXS20/25/35/42/50G2V1B

Peringatan Produk Daikin diproduksi untuk ekspor ke berbagai negara di seluruh dunia. Oleh karena itu, sebelum membeli,

konfirmasikan dengan importir resmi, distributor dan / atau pengecer lokal apakah produk ini sesuai dengan

standar yang berlaku, dan cocok untuk digunakan, di area produk tersebut akan digunakan. Pernyataan ini tidak

dimaksudkan untuk mengecualikan, membatasi atau memodifikasi penerapan dari setiap peraturan setempat.

Mintalah instalatur (pemasang) atau kontraktor yang memenuhi syarat untuk memasang produk ini. Jangan

mencoba memasang produk ini sendiri. Pemasangan yang tidak tepat dapat mengakibatkan kebocoran air atau

refrigeran, sengatan listrik, kebakaran atau ledakan

Gunakan hanya komponen-komponen dan aksesori yang telah disediakan atau ditentukan Daikin. Mintalah

instalatur (pemasang) atau kontraktor yang memenuhi syarat untuk memasang komponen-komponen dan

aksesori. Penggunaan komponen dan aksesori yang tidak resmi atau pemasangan komponen dan aksesori

yang salah dapat mengakibatkan kebocoran air atau refrigeran, sengatan listrik, kebakaran atau ledakan.

Bacalah buku panduan pengguna dengan seksama sebelum menggunakan produk ini. Buku panduan

pengguna memberikan peringatan dan petunjuk keselamatan yang penting. Pastikan mengikuti peringatan dan

petunjuk ini.

Jika Anda memiliki pertanyaan, hubungi importir, distributor dan/atau pengecer lokal Anda.

Spesifikasi, desain dan isi lainnya yang ada dalam brosur ini adalah terbitan Januari 2013, tetapi dapat berubah tanpa pemberitahuan. SiBE121135_A

01/2013 AK.B

Dealer Kantor Pusat:

Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,

Kita-ku, Osaka, 530-8323 Japan

Kantor Tokyo:

JR Shinagawa East Bldg., 2-18-1, Konan,

Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global_ac/

Semua hak dilindungi .

Perhatian terhadap korosi produk

1. AC tidak boleh dipasang di area yang menghasilkan gas korosif, seperti gas asam atau gas bersifat basa.

2. Jika unit outdoor akan dipasang dekat pantai, tidak boleh terpapar langsung angin laut. Jika Anda perlu memasang unit

outdoor dekat pantai, hubungi distributor lokal Anda.