OKONITE CABLES
-
Upload
khangminh22 -
Category
Documents
-
view
0 -
download
0
Transcript of OKONITE CABLES
Bulletin OSC
OKONITE CABLES
102 Hilltop Road, Ramsey, New Jersey 07446 Phone 201.825.0300 www.okonite.com• •
THEOKONITECOMPANY
STOCK CATALOGIn Stock for Immediate Delivery
▲“ ”
INDEX
Data SheetSection:Sheet
GLOSSARY OF TERMS AND DEFINITIONS
MEDIUM VOLTAGE POWER CABLES 2.4kV AND ABOVESingle Conductor CableOkoguard Non-Shielded Okolon TS-CPE Type MV-90 (CT USE) 2.4kV ......................2:2
Okoguard Shielded Okoseal Type MV-105 (CT USE) 5/8kV ........................................2:3
Okoguard Shielded Okoseal Type MV-105 5/8 kV.........................................................2:4
Okoguard Shielded Okoseal Type MV-105 (CT USE) 15kV .........................................2:8
Okoguard Shielded Okoseal Type MV-105 15kV ..........................................................2:9
Okoguard Shielded Okolon TS-CPE Type MV-105 (CT USE) 15kV .............................2:11
Okoguard Shielded Okoseal Type MV-105 35kV...........................................................2:16
Okoguard Shielded Okoseal 69kV ................................................................................2:18
Multi-Conductor CableOkoguard Shielded Okoseal Type MV-105 (CT USE) 3/C 5/8kV ..................................2:19
Okoguard Shielded Okoseal Type MV-105 (CT USE) 3/C 15kV ...................................2:20
Okoguard Non-Shielded C-L-X Type MV-90 or MC-HL (CT USE) 2.4kV ......................2:21
Okoguard Shielded C-L-X Type MV-105 or MC-HL (CT USE) 5/8kV ...........................2:22
Okoguard Shielded C-L-X Type MV-105 or MC-HL (CT USE) 15kV ............................2:24
Solid Type PILC 3/C 15kV..............................................................................................2:31
UNDERGROUND RESIDENTIAL DISTRIBUTION CABLEOkoguard URO-J 15kV Aluminum Conductor ................................................................2:35
Okoguard URO-J 15kV Filled Strand Aluminum Conductor ...........................................2:36
Okoguard URO-J 25kV Aluminum Conductor ................................................................2:39
Okoguard URO-J 35kV Aluminum Conductor ................................................................2:40
Okoguard URO-J 15kV to 35kV Copper Conductor .......................................................2:42
LOW VOLTAGE CABLES TO 2kVSingle Conductor CableOkoguard Okolon TS-CPE Type RHH or RHW-2 or USE-2, VW-1 600V RW-90 .........3:1
Okoguard Okolon TS-CPE Type RHH or RHW-2, 2000V .............................................3:10
Multi-Conductor CableC-L-X Type MC-HL for CT USE (XHHW-2) 600V .........................................................4:1
C-L-X Type MC (XHHW-2) 600V....................................................................................4:2
Okonite-FMR Okoseal Type TC 600V............................................................................4:5
X-Olene - Okoseal Type TC-ER Control Cable (XHHW-2) 600V ...................................4:8
C-L-X Type MC for CT USE (XHHW-2) 600V Control Cable ........................................4:14
C-L-X Type MC-HL for CT USE (XHHW-2) 600V Control Cable ..................................4:15
INDEX
Data SheetSection:Sheet
INSTRUMENTATION CABLESOkoseal Type P-OS 300V .............................................................................................5:2
Okoseal Type P-OS C-L-X 300V ...................................................................................5:3
Type SP-OS Instrumentation Cable ...............................................................................5:13
Okoseal Type SP-OS C-L-X 300V ................................................................................5:14
Okoseal Type P-OS Thermocouple 300V .....................................................................5:18
C-L-X Okoseal Type P-OS Thermocouple 300V............................................................5:19
Okoseal-N Type P-OS 600V .........................................................................................5:29
Okoseal-N Type SP-OS 600V .......................................................................................5:31
Okoseal-N Type P-OS C-L-X Type MC-HL 600V .........................................................5:40
Okoseal-N Type SP-OS C-L-X Type MC-HL 600V ......................................................5:42
Okobus Type PLTC & Type ITC-ER Fieldbus CableSingle Pair Type P-OS — Multi Pair Type SP-OS..........................................................5:47
Okobus C-L-X.................................................................................................................5:48
C-L-X X-Olene P-OS, SP-OS .........................................................................................5:49
X-Olene Okoseal UL Type TC-ER/ITC-ER & cUL Type CIC-TC-ER..............................5:50
SPECIAL PURPOSE CABLESX-Ray Low Noise 65-250kV DC .....................................................................................6:1
X-Ray 65-1000kV DC .....................................................................................................6:2
Okoguard Aerial Jumper Cable 15kV ............................................................................6:4
Okoguard-Okolon TS-CPE 5kV Airport Lighting Cable ..................................................6:6
RAILROAD AND TRANSIT SYSTEM CABLESArmored Signal Cable ....................................................................................................7:1
Track Wire .....................................................................................................................7:6
Tower and Case Wire ....................................................................................................7:10
Case Wire ......................................................................................................................7:11
Nylon Braid Case Wire ..................................................................................................7:12
Type DEL........................................................................................................................7:17
SPLICING AND TERMINATING PRODUCTSC-L-X Terminating Tool Kit ............................................................................................ 6:5
Color Code Tables ......................................................................................................... OSL
Miscellaneous Information ............................................................................................. OSL
OSC Index 10/2021
INDUSTRY ASSOCIATIONS
ABS American Bureau of Shipping.
AEIC Association of Edison
Illuminating Companies.
ANSI American National Standards
Institute.
AREMA American Railway Engineering
and Maintenance of Way Association
ASTM American Society for Testing and
Materials.
ICEA Insulated Cable Engineers
Association (formerly IPCEA).
IEC International Electrotechnical
Commission
IEEE Institute of Electrical and
Electronics Engineers.
NEC National Electrical Code.
NEMA National Electrical
Manufacturers Association.
NFPA National Fire Protection
Association.
GOVERNMENT AGENCIES
OSHA Occupational Safety and Health
Act administered by U.S. Dept. of
Labor which establishes employee safety
standards in all industrial and commercial
establishments.
RUS Rural Utility Systems of the U.S.
Department of Agriculture, formerly REA.
FAA Federal Aviation Administration
EPA Environmental Protection Agency
DOE Department of Energy
FERC Federal Energy Regulatory
Commission
OKONITE REGISTERED TRADE
NAMES
C-L-X® Continuous-Lightweight-Exterior.
Welded and corrugated, impervious
metallic sheathed cables.
LOXARMOR® An interlocked “S” shaped
armor cable covering, normally galvanized
steel or aluminum.
OKOBON® A moisture resistant cable
finish consisting of an aluminum/
copolymer tape fused to itself and to an
overall jacket.
OKOBUS® Fieldbus instrumentation
cable.
OKOCLEAR TP® (TPPO) Thermoplastic
Polyolefin low smoke/zero halogen jacket
compound.
OKOCLEAR TS® Thermosetting Polyolefin low
smoke/zero halogen jacket compound.
OKOGUARD® Okonite's exclusive ethylene-pro-
pylene rubber (EPR) based, thermosetting
insulation, with an optimum balance of electrical
and physical properties unequaled in other solid
dielectrics, used on power cables rated 600 V
and above. (50th Anniversary - 2017)
OKOLENE® Thermoplastic polyethylene or
polypropylene based insulation or jacket
compound.
OKONITE® Okonite's exclusive ethylene
propylene rubber (EPR) based, thermo-
setting insulation used up to 2000V.
OKONITE-FMR® Okonite’s exclusive flame and
moisture resistant ethylene propylene rubber
(EPR) insulation used up to 2000V.
OKOGUARD-OKOLON® Composite insulation
system consisting of a layer of EPR and covered
with a chlorinated thermoset compound.
OKOPACT® Okonite’s unique compact round
conductor shape and design.
OKOSEAL® A PVC insulation or jacketing
compound with excellent resistance to flame and
most chemicals.
OKOSEAL-N® PVC insulated and nylon
jacketed low voltage conductors, Type THHN,
THWN-2 and TFN.
OKOLON TP-CPE® Thermoplastic moisture
resistant CPE compound serving as an outer
jacket.
OKOLON TS-CPE® Thermoset moisture
resistant flame retardant CPE outer jacket.
OKOTEMP® - Thermoplastic rubber jacketing
compound with excellent abrasion resistance
combined with flexibility.
OKOTHERM® Heat resistant silicone rubber
based insulation for use in high temperature
locations.
OKOZEL® Okonite's name for its ETFE based
flame and radiation resistant
insulating and jacketing compound.
P-30® Okolene-Okoseal insulated 600V
multiple and single conductor control
cable.
P-45® Okolene-Okoseal Insulated 1000V
Multiple Conductor Control Cable.
X-OLENE® Okonite's name for its XLPE
insulation and jacket.
STANDARD TERMS
AWG American Wire Gauge, based on the
circular mil system where 1 mil equals 0.001
inch.
CIC Cable in Conduit for buried distribution
systems.
CIC Circuit Integrity flame retardant cables
C-L-X-M C-L-X Marine Shipboard Cable
CPE Chlorinated Polyethylene jacketing
material.
CSA Canadian Standards Association. An
independent organization which implements
and monitors the commercial and consumer
electrical product standards. The CSA
assures compliance to the various Canadian
Electrical Code requirements.
CT Designation given to cables meeting UL
requirements for cable tray use.
CTC Designation for Centralized Traffic
Control Code Line cable.
CWCMC UL’s designation for 600 volt
C-L-X marine shipboard cable - “continu-
ously welded corrugated MC” cable.
DEL Diesel Electric Locomotive and car
wiring with Okonite insulation and Okolon
jacket.
EPR Ethylene Propylene Rubber insulating
compound ingredient.
ER Exposed Run, UL term designating
cables approved for open wire applications.
ETFE Modified Ethylene Tetrofluoroethylene
compound (Okozel) used for insulation and
jackets.
FIELDBUS CABLE - High Speed digital
signal transmission instrumentation cable
having specific electrical characteristics.
FPL Power limited Fire Protective Signal
Cable (NEC Art. 760). 300V rated
FMR Flame and Moisture Retardant.
HL Designation given to MC and ITC cables
meeting NEC and UL requirements for use
in Division 1 hazardous locations.
INSULATION LEVEL-100% Cable for use
on grounded systems or where the system is
provided with relay protection such that
grounds faults will be cleared as rapidly as
possible but in any case within one minute.
INSULATION LEVEL-133% Cable for use
on ungrounded or grounded systems or
where the faulted section will be de-ener-
gized in a time not exceeding one hour.
ITC Instrumentation Tray Cable for
instrumentation & control circuits operating
�150V and �5 amps., per NEC Article 727.
GLOSSARY
5
kcmil A unit of conductor area in thou-
sands of circular mils. (Formerly MCM).
LOCA Loss of Coolant Accident, IEEE
383 defines test requirements.
LCS Longitudinal Corrugated Shield.
MC Metal-Clad cable. NEC type designa-
tion for power and control cables enclosed
in a welded and corrugated metallic
sheath (C-L-X), or an interlocking tape
armor (Loxarmor). (Article 330)
MC-HL Metal-Clad cable listed for
hazardous locations
mil 0.001 inch.
MV Medium Voltage cable. NEC designa-
tion for single & multiple conductor
insulated cable rated 2001 to 35,000 volts.
(NEC Article 328)
NPLF Non-Power Limited Fire Protective
Signal Cable (NEC Art. 760). 600V rated
OKO-MARINE UL designation for
non-armored Marine Shipboard Cable.
PLTC Type designation for Power-
Limited Tray Cable for use in Class 2 or 3
power-limited circuits; instrumentation,
supervisory control, and thermocouple
extension.
P-NS Single pair or triad, Non Shielded,
instrumentation or thermocouple extension
cable.
P-OS Single or multi Pairs or Triads with
Overall Shield, instrumentation or thermo-
couple extension cable.
POWER-LIMITED CIRCUIT Circuit either
inherently limited requiring no overcurrent
protection or limited by a combination of a
power source and overcurrent protection.
PVC Polyvinyl Chloride insulating and
jacketing material which is usually flame
retardant and resistant to many
chemicals.
P-104 Okonite’s identification number
issued by the Pennsylvania Department of
Environmental Resources.
RHH NEC conductor type designation for
conductors with Heat resistant rubber or
XLPE insulation, for use in dry locations.
RHW-2 NEC conductor type designation
for conductors with Heat and Moisture
resistant rubber or XLPE insulation, for
use in 90°C wet or dry locations.
RTA Thermoplastic insulated, aluminum
shielded, polyethylene jacketed communi-
cation cable.
SCREEN A semiconducting nonmetallic layer
used under and over the insulation of
power cables rated over 2kV to reduce
electrical stresses and corona
SEMICONDUCTING An extruded layer or tape
of such resistance that when applied between
two elements of a cable the adjacent surfaces of
the two elements will maintain substantially the
same potential.
SHIELD A nonmagnetic, metallic material
applied over an insulated conductor(s) to confine
the electric field to the insulation.
SP-OS Multiple Shielded Pairs or Triads with
Overall Shield, instrumentation or thermocouple
extension cable.
SR Sunlight Resistant
TC NEC type designation for power and
control tray cable. (Article 336)
TFN NEC conductor type designation for PVC
insulated nylon jacketed conductors in sizes #18
and 16 AWG for use in dry locations.
THERMOCOUPLE CABLE - A cable consisting
of two dissimilar metals or alloys that, when
electrically joined at one end can be used to
measure temperature. These cables have no
voltage rating.
THHN NEC conductor type designation for PVC
insulated nylon jacketed conductors for use in
dry locations.
THWN-2 NEC conductor type designation for
PVC insulated nylon jacketed conductors for use
in 90°C wet or dry locations.
TPPO Thermoplastic Polyolefin, a thermoplastic
jacket material with low smoke characteristics
and is free of halogens.
UL Underwriters Laboratories. An independent
organization which examines, tests, lists and
periodically inspects
equipment to appropriate standards.
URO-J Underground Residential distribution-
Okoguard (EPR) insulation-Okolene Jacket em-
ploying a concentric neutral.
USE Underground Service Entrance
cable. (NEC Article 338)
VERTICAL TRAY FLAME TEST
Conducted per UL, IEEE or ICEA procedures to
demonstrate that a single conductor (1/0 AWG
and larger) or multi-conductor cable will not
propagate a fire in the defined test.
VOLTAGE LEVELS
Power-Limited - 0-300 Volts
Low Voltage - 600-2000 Volts
Medium Voltage - 2400-46000 Volts
High Voltage - >46 to 345kV
VOLTAGE RATING V or kV, industry
convention to identify voltage levels, phase
to phase voltage.
VW-1 Basic flammability test for single
conductors; employs a tirrill burner applied
intermittently to a Vertical Wire.
XHHW-2 NEC conductor type designation
for conductors with Heat and Moisture resis-
tant thermoset insulation for use in 90°C wet
or dry locations.
XLPE Cross-Linked Polyethylene insulating
compound.
XLPO Cross Linked Polyolefin, a thermoset
jacket material with low smoke characteris-
tics and is free of halogens.
Z NEC conductor type designation for
conductors with ETFE insulation for use in
dry locations.
ZW NEC conductor type designation for
conductors with ETFE insulation for use in
wet or dry locations.
CONDUCTOR IDENTIFICATION
INFORMATION
E-1 Color sequences for utility conductor
identification, see Appendix E, Table E-1,
ICEA Standard S-73-532, includes green
and white.
E-2 Color sequence for industrial conductor
identification, see Appendix E, Table E-2,
ICEA Standard S-73-532, excludes green
and white.
METHOD-1 Conductor identification, colored
compounds with tracers in accordance with
the ICEA standard.
METHOD-2 Conductor identification, neutral
compounds with tracers in accordance with
the ICEA Standard.
METHOD-3 Conductor identification, neutral
or single colored compounds with surface
printing of numbers and color designations in
accordance with the ICEA Standard.
METHOD-4 Conductor identification, neutral
or single colored compounds with surface
printing of numbers in accordance with the
ICEA Standard.
METHOD-5 Conductor identification, individ-
ual color coding with braids in accordance
with the ICEA Standard.
GLOSSARY (continued)
6
Okoguard -Okolon TS-CPE Type MV-90® ®
2.4 kV Nonshielded Power CableOne Okopact (Compact Stranded)
®
Copper Conductor/90°C Rating Wet or DryFor Cable Tray Use-Sunlight Resistant
A Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCJacket-Okolon TS-CPED
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 2
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequalled in other soliddielectrics. Okoguard insulation, with thedistinctive red color and a totally integratedEPR system, provides the optimum balancefor long, problem free service.
JacketThe Okolon TS-CPE jacket on this cable is avulcanized chloronated polyethylene basedcompound which is mechanically rugged,flame, radiation and oil resistant.
ApplicationsOkoguard-Okolon TS-CPE 2 .4 kV cables areheavy duty nonshielded cables designed foruse at up to 2.4 kV phase-to-phase in wet ordry locations in accordance with NEC.
Okoguard-Okolon TS-CPE nonshieldedcables are recommended for power distribu-tion and motor circuits in generating plantsand substations; in industrial and commercialbuildings.
Single conductors may be installed inindustrial or commercial occupancies intriplexed or random lay in any raceway or ductin wet or dry locations, or in open runs aspermitted by the NEC.
Sizes 1/0 AWG and larger, may be installed incable trays where permitted by NEC Section311.32(2).
SpecificationsConductor: Annealed uncoated coppercompact stranded per ASTM B-496.
Strand Screen: Extruded semiconductingEPR strand screen. Meets or exceedselectrical and physical requirements of ICEAS-96-659/NEMA WC71 and UL 1072.
Insulation: Meets or exceeds electrical andphysical requirements of ICEA S-96-659/NEMA WC71 and UL 1072.
Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-96-659/NEMA WC71 for chlorinated polyethylenejackets.UL listed as Type MV-90, sunlight resistant, -40°C and for use in cable tray in accordance
with UL 1072. CSA listed as RW90 as 5kVnon-shielded (FT4 1/0 and larger) -40°C inaccordance with CSA C22.2 No 38.
1/C non-shielded cables can surfacedischarge in service when in a randomphase spacing or when in contact withgrounded surfaces.
Product Features• Okoguard cables meet or exceed allrecognized industry standards (UL, CSA,NEMA/ICEA, IEEE).
• 90°C continuous operating temperature.
• 130°C emergency rating.
• 250°C short circuit rating.
• Passes UL and IEEE 383 and 1202/FT4(1/0 and larger) Vertical Tray Flame Test.
• Sizes 500 kcmil and larger pass ICEA
T-29-520 (210,000 BTU/hr) Vertical TrayFlame Test.
• Sizes 1/0 and larger pass CSA FT4Vertical Tray Flame Test.
• Sizes #1 and smaller pass CSA FT1.
• Excellent corona resistance.
• Radiation resistant.
• Exceptional resistance to "treeing".
• Stress cones not required.
• Moisture resistant.
• Resistant to most oils, acids, and alkalies.
• Sunlight Resistant.
• Sizes #6 and #8 AWG are identified asFAA-L-824, Type B 5kV rated.
ULR
Okoguard-Okolon TS-CPE Type MV-902.4 kV Nonshielded Power CableOne Okopact (Compact Stranded)
°C Rating Wet or DryCopper Conductor/90For Cable Tray Use-Sunlight Resistant
Product DataSection 2: Sheet 2
*▲114-24-2213*▲114-24-2217▲114-24-2219▲114-24-2221
8 8.46 13.34 21.22 33.6
125 3.18125 3.18125 3.18125 3.18
80 2.0380 2.0380 2.0380 2.03
0.60 15.10.63 16.00.67 17.10.73 18.6
215 250260 295328 368427 492
55 64 -75 85 -97 110 -
130 145 -
2222
114-24-2223▲114-24-2225▲114-24-2227
114-24-2229
1 42.41/0 53.52/0 67.43/0 85.0
125 3.18125 3.18125 3.18125 3.18
80 2.0380 2.0380 2.0395 2.41
0.76 19.40.80 20.30.88 22.40.96 24.5
493 558580 645682 742838 908
155 170 -180 195 260205 220 300240 250 345
2½2½2½3
▲114-24-2231114-24-2233
▲114-24-2237
4/0 107.0250 127.0350 177.0
125 3.18140 3.56140 3.56
95 2.41110 2.79110 2.79
0.97 24.61.08 27.41.18 29.9
991 10861198 12931555 1660
280 290 400315 320 445385 385 550
333½
▲114-24-2243▲114-24-2249
114-24-2251
500 253.0750 380.0
1000 507.0
140 3.56155 3.94155 3.94
110 2.79125 3.18125 3.18
1.29 32.91.54 39.01.70 43.0
2075 22053034 32243891 4141
475 470 695600 585 900690 670 1075
3½55
Okonite’s web site, www.okonite.com contains the most up to date information.
▲ Available from our Customer Service Center.Authorized stock item.
Aluminum Okopact Conductors(1) Aluminum conductors are available on special order.Ampacities(2) Ampacities are in accordance with Table 311.60(C)(73) of the NEC for three singleType MV-90 conductors, or single conductors twisted together (triplexed) andinstalled in an isolated conduit in air at an ambient temperature of 40°C and aconductor temperature of 90°C.
(3) Ampacities are in accordance with Table 311.60(C)(77) of the NEC for three singleconductors or triplexed cable in one underground raceway, three feet deep witha conductor temperature of 90°C, 100% Load Factor, an ambient earth temperatureof 20°C, and thermal resistance (RHO) of 90.
(4) Ampacities for cable in cable tray are in accordance with the NEC, Section 392.80(B)(2)(2),Table 311.60(C)(69) (copper), for single conductor cables installed in a single layer, in uncoveredtray, with a maintained spacing of 1 cable OD or more at 90°C conductor temperature and 40°Cambient temperature and multi-point grounding.
O/21010202
THE OKONITE COMPANYRamsey, New Jersey 07446
Catalo
g Num
ber (1)
Conductor s
ize
AWG
or k
cmil
Conductor S
ize -m
m²
Insula
tion
Thickness -
mils
Insula
tion
Thickness -
mm
Jacket Thic
kness - m
ils
Jacket Thic
kness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. N
et Weig
ht
lbs./1
000’
Approx. S
hip W
eight
lbs./1
000’
Am
paciti
es (2
)
Conduit
inAir
Am
paciti
es (3
)
Under
ground D
uct
Conduit Siz
e
Inches
(5)*
* Marked “FAA L-824 5kV Type B”.
Am
paciti
es (4
)
Cab
le T
ray
Refer to the NEC, IEEE/ICEA-S-135 Power Cable Ampacities, or the OkoniteEngineering Data Bulletin for other ambient temperatures, circuit configurationsor installation requirements.
(5) Recommended size of rigid or nonmetallic conduit for three conductorsbased on 40% maximum fill.
* The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possiblejamming.
ULR
Okoguard -Okoseal Type MV-105® ®
5/8kV Shielded Power CableOne Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
5kV-133% or 8kV-100% Insulation LevelFor Cable Tray Use-Sunlight Resistant
A Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCInsulation Screen-Extruded Semi-Dconducting EPRShielding-Copper TapeEJacket-OkosealF
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 3
InsulationOkoguard is Okonite's registered tradename for its exclusive ethylene-propylenerubber (EPR) based, thermosettingcompound, whose optimum balance ofelectrical and physical properties isunequaled in other solid dielectrics.Okoguard insulation, with the distinctivered color and a totally integrated EPRsystem, provides the optimum balance ofelectrical and physical properties for long ,problem free service.
The triple tandem extrusion of the screenswith the insulation provides optimumelectrical characteristics.
JacketThe Okoseal (PVC) jacket supplied withthis cable is mechanically rugged and hasexcellent resistance to oil, acids and mostchemicals.
ApplicationsOkoguard shielded Okoseal Type MV-105power cables are recommended for useas feeder circuits, in electric utilitygenerating stations, for distributioncircuits, and for feeders or branch circuitsin industrial and commercial installations.
Type MV cables may be installed in wet ordry locations, indoors or outdoors(exposed to sunlight), in any raceway orunderground duct, directly buried ifinstalled in a system with a groundingconductor in close proximity that conformswith NEC Section 311.36 and 250.4(A)(5),or messenger supported in industrialestablishments and electric utilities. Sizes1/0 AWG and larger may also be installedin cable tray.
SpecificationsConductor: Annealed uncoated coppercompact stranded per ASTM B-496.
Strand Screen: Extruded semiconductingEPR strand screen. Meets or exceedselectrical and physical requirements ofICEA S-93-639/NEMA WC74 & S-97-682,AEIC CS8, CSA C68.10 and UL 1072.
Insulation: Meets or exceeds electricaland physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA C68.10 and UL 1072.
Insulation Screen: Extruded semiconductingEPR insulation screen applied directly overthe insulation. Meets or exceeds electricaland physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA C68.10 and UL 1072.
Shield: 5 mil bare copper tape helicallyapplied with 25% minimum overlap.
Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.10and UL 1072 for polyvinyl chloride jackets.
UL listed as Type MV-105 and sunlightresistant, in accordance with UL 1072.
CSA C68.10 listed as FT4, SR, LTGG
(-40°C), TC (< 500 kcmil) and TC-ER (≥ 500kcmil).
Product Features•Triple tandem extruded, all EPRsystem.
• Okoguard cables meet or exceed allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).
• 105°C continuous operating temperature.
• 140°C emergency rating.
• 250°C short circuit rating.
• Passes UL and IEEE 383 and 1202
(1/0 AWG and larger) Vertical Tray FlameTest.
• Excellent corona resistance.
• Screens are clean stripping.
• Exceptional resistance to "treeing".
• Exceptional resistance to moisture.
• Resistant to most oils, acids, andalkalies.
• Sunlight resistant.
• For Cable Tray Use.
• Improved Temperature Rating.
ULR
Okoguard-Okoseal Type MV-1055/8kV Shielded Power CableOne Okopact (Compact Stranded)
105°C Rating WetCopper Conductor/5kV-133% or 8kV-100% Insulation LevelFor Cable Tray Use-Sunlight Resistant
Okoguard Insulation: 115 mils (2.92mm), 5kV-133% or 8kV-100% Insulation Level
Product DataSection 2: Sheet 3
▲114-23-3824▲114-23-3826
114-23-3865▲114-23-3832
1/0 53.52/0 67.43/0 85.04/0 107.0
0.61 0.670.65 0.710.70 0.760.75 0.81
60 1.5260 1.5280 2.0380 2.03
0.81 20.60.85 21.60.95 24.10.99 25.2
615 655720 775895 950
1030 1090
200 210 290225 235 335270 270 385305 310 445
2½2½33
▲114-23-3834▲114-23-3838▲114-23-3846▲114-23-3873
114-23-3855
250 127.0350 177.0500 253.0750 380.0
1000 507.0
0.80 0.860.89 0.951.01 1.071.19 1.261.34 1.40
80 2.0380 2.0380 2.0380 2.0380 2.03
1.05 26.71.14 29.01.26 32.01.45 36.91.59 40.4
1185 12501540 16252055 21552940 31203781 3960
355 345 495430 415 610530 505 765665 630 990770 720 1185
33½3½44
Okonite’s web site, www.okonite.com contains the most up to date information.
K/21010203
THE OKONITE COMPANYRamsey, New Jersey 07446
Catalo
gNum
ber (1)
Conduct
or si
ze
AW
G o
r kc
mil
Conducto
r Size
-mm
²
Appro
x. D
ia. o
ver
Insu
latio
n (in.)
Appro
x. D
ia. o
ver
Scree
n (in.)
Jacket Thic
kness- m
ils
Jacket Thic
kness- m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Am
paciti
es C
onduit in
Air
(2)
Am
paciti
esUnder
ground
Duct
(3)
Conduit
Size
Inch
es(5
)*
Am
paciti
es C
able
Tra
y (4
)
▲ Available from our Customer Service Center.Authorized stock item.Aluminum Conductors(1) Aluminum conductors are available on special order.Ampacities(2) Ampacities are in accordance with Table 311.60(C)(73) of the NEC for three singleType MV-105 5kV conductors, or single conductors twisted together (triplexed) andinstalled in an isolated conduit in air at an ambient temperature of 40°C and aconductor temperature of 105°C. Refer to Table 311.60(C)(73) for 8kV ampacities.(3) Ampacities are in accordance with Table 311.60(C)(77) of the NEC for three single5kV conductors or triplexed cable in one underground raceway, three feet deep witha conductor temperature of 105°C, 100% Load Factor, an ambient earth temperatureof 20°C, and thermal resistance (RHO) of 90. Refer to Table 311.60(C)(77) for 8kV ampacities.
(4) Ampacities for cable in cable tray are in accordance with the NEC,Section 392.80(B)(2)(2), Table 311.60(C)(69) (copper),for single conductor cables installed in a single layer, in uncovered tray,with a maintained spacing of 1 cable OD or more at 105°C conductortemperature and 40°C ambient temperature and multi-point grounding.
Refer to NEC, IEEE/ICEA-S-135 Power Cable Ampacities, or the OkoniteEngineering Data Bulletin for installation in duct banks, multiple point groundedshields, other ambient temperatures, circuit configurations or installationrequirements.
(5) Recommended size of rigid or nonmetallic conduit for three conductorsbased on 40% maximum fill.
* The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possiblejamming.
ULR
Okoguard -Okoseal Type MV-105® ®
5/8kV Shielded Power CableOne Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
5kV-133% or 8kV-100% Insulation Level
A Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCInsulation Screen-Extruded Semi-Dconducting EPRShielding-Copper TapeEJacket-OkosealF
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 4
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in othersolid dielectrics. Okoguard insulation, withthe distinctive red color and a totallyintegrated EPR system, provides theoptimum balance of electrical and physicalproperties for long , problem free service.
The triple tandem extrusion of the screenswith the insulation provides optimumelectrical characteristics.
JacketThe Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to oil, acids and mostchemicals.
ApplicationsOkoguard shielded Okoseal Type MV-105power cables are recommended fordistribution circuits, and for feeders or branchcircuits.
Type MV cables may be installed in wet ordry locations, indoors or outdoors (exposedto sunlight), in any raceway or undergroundduct, directly buried if installed in a systemwith a grounding conductor in close proximitythat conforms with NEC Section 311.36 and250.4(A)(5), or messenger supported inindustrial establishments and electric utilities.
SpecificationsConductor: Annealed uncoated coppercompact stranded per ASTM B-496.
Strand Screen: Extruded semiconductingEPR strand screen. Meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC74 & S-97-682, AEICCS8, CSA C68.10 and UL 1072.
Insulation: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA C68.10 and UL 1072.
Insulation Screen: Extruded semiconductingEPR insulation screen applied directly overthe insulation. Meets or exceeds electricaland physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA C68.10 and UL 1072.
Shield: 5 mil bare copper tape helicallyapplied with 12.5% nominal overlap.
Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSAC68.10 and UL 1072 for polyvinyl chloridejackets.
UL Listed as Type MV-105 and sunlightresistant, in accordance with UL 1072.
CSA C68.10 listed as FT1, SR, and
LTDD (-25°C).
Product Features• Triple tandem extruded, all EPR system.
• Okoguard cables meet or exceed allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).
• 105°C continuous operating temperature.
• 140°C emergency rating.
• 250°C short circuit rating.
• Excellent corona resistance.
• Screens are clean stripping.
• Exceptional resistance to "treeing".
• Exceptional resistance to moisture.
• Resistant to most oils, acids, and alkalies.
• Sunlight resistant.
• Improved Temperature Rating.
ULR
Okoguard-Okoseal Type MV-1055/8kV Shielded Power CableOne Okopact (Compact Stranded)
105°C RatingCopper Conductor/5kV-133% or 8kV-100% Insulation Level
Product DataSection 2: Sheet 4
▲114-23-3817▲114-23-3819▲114-23-3821
6 13.34 21.22 33.6
0.44 0.500.48 0.540.54 0.60
60 1.5260 1.5260 1.52
0.64 16.30.69 17.50.74 18.8
285 320355 385455 495
84 92110 120145 155
222
114-23-3823114-23-3825114-23-3827114-23-3829
1 42.41/0 53.52/0 67.43/0 85.0
0.58 0.630.61 0.670.65 0.710.70 0.75
60 1.5260 1.5260 1.5280 2.03
0.77 19.50.81 20.60.85 12.60.93 23.6
530 570610 645710 765880 935
175 180200 210225 235270 270
2½2½2½3
114-23-3831114-23-3833114-23-3837
4/0 107.0250 127.0350 177.0
0.75 0.810.80 0.860.89 0.95
80 2.0380 2.0380 2.03
0.99 25.11.04 26.41.14 29.0
1035 11001180 12451535 1625
305 310355 345430 415
333½
114-23-3843114-23-3849114-23-3851
500 253.0750 380.0
1000 507.0
1.01 1.071.19 1.251.33 1.39
80 2.0380 2.0380 2.03
1.25 31.81.43 36.81.57 39.9
2050 21502935 31103650 3825
530 505665 630770 720
3½45
Minimum Manufacturing Quantity for non-stock items is 5000’.Aluminum Conductors(1) Aluminum conductors are available on special order.Ampacities(2) Ampacities are in accordance with Table 311.60(C)(73) of the NEC for three singleType MV-105 5kV conductors or single conductors twisted together (triplexed) andinstalled in an isolated conduit in air at an ambient temperature of 40°C and aconductor temperature of 105°C. Refer to Table 311.60(C)(73) for 8kV ampacities.(3) Ampacities are in accordance with Table 310.60(C)(77) of the NEC for three single5kV conductors or triplexed cable in one underground raceway, three feet deep witha conductor temperature of 105°C, 100% Load Factor, an ambient earth temperatureof 20°C, and thermal resistance (RHO) of 90. Refer to Table 311.60(C)(77) for 8kVampacities.
Q/21060204
THE OKONITE COMPANYRamsey, New Jersey 07446
Cata
log
Num
ber (1)
Conducto
r size
AWG
or kcmil
Conducto
r Size
-mm
²
Appro
x. Dia
over
Insula
tion
(in.)
Appro
x. Dia
. Over
Screen
(in.)
Jacket Thickness
- mils
Jacket Thickness
- mm
Appro
x. O.D
. -In
ches
Appro
x. O.D
. -m
m
Appro
x. Net W
eight
lbs./1
000’
Appro
x. Ship
Weig
ht
lbs./1
000’
Am
pacities
Conduit
inAir
(2)
Am
pacities
Underg
round
Duct (3
)
Conduit
Size
Inches
(4)*
Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the OkoniteEngineering Data Bulletin for installation in duct banks, multiple point groundedshields, other ambient temperatures, circuit configurations or installationrequirements.(4) Recommended size of rigid or nonmetallic conduit for three conductors basedon 40% maximum fill.*The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possiblejamming.
Okoguard Insulation: 115 mils (2.92mm), 5kV-133% or 8kV -100% Insulation
Okonite’s web site, www.okonite.com contains the most up to date information.
ULR
▲ Available from our Customer Service Centers.Authorized stock item.
Okoguard -Okoseal Type MV-105® ®
15kV Shielded Power CableOne Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
100% and 133% Insulation LevelFor Cable Tray Use-Sunlight Resistant
A Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCInsulation Screen-ExtrudedDSemiconducting EPRShield-Copper TapeEJacket-OkosealF
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 8
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in othersolid dielectrics. Okoguard insulation, withthe distinctive red color and a totallyintegrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free service.The triple tandem extrusion of the screenswith the insulation provides optimumelectrical characteristics.
JacketThe Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to flame, oil, acids andmost chemicals.
ApplicationsOkoguard shielded Okoseal Type MV-105power cables are recommended for use asfeeder circuits, in electric utility generatingstations, for distribution circuits, and forfeeders or branch circuits in industrial andcommercial installations.Type MV cables may be installed in wet ordry locations, indoors or outdoors (exposedto sunlight), in any raceway or undergroundduct, directly buried if installed in a systemwith a grounding conductor in close proximitythat conforms with NEC Section 311.36 and250.4(A)(5), or messenger supported inindustrial establishments and electric utilities.Sizes 1/0 AWG and larger may also beinstalled in cable tray as permitted by NECSection 311.32(2).
SpecificationsConductor: Annealed uncoated coppercompact stranded per ASTM B-496.Strand Screen: Extruded EPRsemiconducting strand screen. Meets orexceeds electrical and physical requirementsof ICEA S-93-639/NEMA WC74 & S-97-682,AEIC CS8, CSA C68.10 and UL 1072.Insulation: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA C68.10 and UL 1072.Insulation Screen: Extruded EPRsemiconducting insulation screen applieddirectly over the insulation. Meets or exceedselectrical and physical requirements of ICEA
S-93-639/NEMA WC74 & S-97-682,AEIC CS8, CSA C68.10 and UL 1072.Shield: 5 mil bare copper tape helicallyapplied with 25% minimum overlap.Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.10and UL 1072 for polyvinyl chloride jackets.
UL listed as Type MV-105, sunlightresistant, and for use in cable tray inaccordance with UL 1072.
CSA C68.10 listed as FT4, SR, LTGG(-40°C), TC (< 500 kcmil) and TC-ER (≥ 500kcmil).
Product Features• Triple tandem extruded, all EPR system.
• Okoguard cables meet or exceed allrecognized industry standards (UL, CSA,AEIC, NEMA/ICEA, IEEE).• 105°C continuous operating temperature.• 140°C emergency rating.• 250°C short circuit rating.• Passes the Vertical Tray Flame Testrequirements of UL 1072 and IEEE 383 and1202.• Excellent corona resistance.• Screens are clean stripping.• Exceptional resistance to "treeing".• Exceptional resistance to moisture.• Resistant to most oils, acids, and alkalies.• Sunlight resistant.• For Cable Tray Use.• Improved Temperature Rating.
ULR
Okoguard-Okoseal Type MV-10515kV Shielded Power CableOne Okopact (Compact Stranded)
105°C RatingCopper Conductor/100% and 133% Insulation LevelFor Cable Tray Use - Sunlight Resistant
Product DataSection 2: Sheet 8
115-23-3064115-23-3066115-23-3067
1/0 53.52/0 67.43/0 85.0
0.74 0.800.78 0.840.83 0.89
80 2.0380 2.0380 2.03
0.98 24.81.02 25.81.07 27.1
760 825870 935
1005 1070
215 215 290255 245 335290 275 385
333
115-23-3069115-23-3074115-23-3076
4/0 107.0250 127.0350 177.0
0.88 0.940.93 0.981.03 1.07
80 2.0380 2.0380 2.03
1.12 28.41.17 29.71.26 32.0
1160 12401330 14151700 1800
330 315 445365 345 495440 415 610
33½3½
115-23-3090115-23-3091115-23-3092
500 253.0750 380.0
1000 507.0
1.14 1.191.32 1.371.47 1.52
80 2.0380 2.0380 2.03
1.38 35.11.55 39.41.71 43.4
2230 22753105 33403960 4215
535 500 765655 610 990755 690 1185
455
Okoguard Insulation: 220 mils (5.59mm), 133% Insulation Level
U/21050208 THE OKONITE COMPANYRamsey, New Jersey 07446
Catalo
gNum
ber (1)
Conduct
or si
ze
AW
G o
r kc
mil
Conduct
or Size
-mm
²
Appro
x. D
ia. o
ver
Insu
latio
n (in.)
Appro
x. D
ia. o
ver
Scree
n (in.)
Jacket Thic
kness- m
ils
Jacket Thic
kness- m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Am
paciti
es (2
) Conduit
inAir
Am
paciti
es(3
) Under
ground
Duct
Conduit
Size
Inch
es(5
)*
Am
paciti
es (4
) Cab
le T
ray
▲115-23-3479**▲115-23-3230▲115-23-3232
115-23-3234
2 33.61/0 53.52/0 67.43/0 85.0
0.76 0.810.83 0.880.87 0.920.92 0.98
80 2.0380 2.0380 2.0380 2.03
0.99 25.21.10 28.01.11 28.21.16 29.4
682 742905 975970 1030
1170 1185
165 165 ̶215 215 290255 245 335290 275 385
3333½
▲115-23-3236▲115-23-3238▲115-23-3240
4/0 107.0250 127.0350 177.0
0.96 1.021.01 1.071.11 1.17
80 2.0380 2.0380 2.03
1.21 30.71.26 32.01.35 34.3
1280 13701435 15201810 1940
330 315 445365 345 495440 415 610
3½3½4
▲115-23-3242▲115-23-3243▲115-23-3244
500 253.0750 380.0
1000 507.0
1.22 1.281.40 1.461.55 1.60
80 2.0380 2.03
110 2.79
1.47 37.31.65 41.91.86 47.1
2350 25353240 34804220 4490
535 500 765655 610 990755 690 1185
456
Okoguard Insulation: 175 mils (4.45mm), 100% Insulation Level
▲ Available from our Customer Service Centers.Authorized Stock Item.Minimum Manufacturing Quantity for non-stock items is 5000’.Aluminum Conductors(1) Aluminum conductors are available on special order. To order aluminumconductors, change the first three digits of the catalog number from 115 to 135.Ampacities(2) Ampacities are in accordance with Table 311.60(C)(73) of the NEC for three singleType MV-105 conductors, or single conductors twisted together (triplexed) andinstalled in an isolated conduit in air at an ambient temperature of 40°C and aconductor temperature of 105°C.(3) Ampacities are in accordance with Table 311.60(C)(77) of the NEC for three singleconductors or triplexed cable in one underground raceway, three feet deep witha conductor temperature of 105°C, 100% Load Factor, an ambient earth temperatureof 20°C, and thermal resistance (RHO) of 90.Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite EngineeringData Bulletin EHB for installation in duct banks, multiple point ground shields, otherambient temperatures, circuit configurations or installation requirements.
(5) Recommended size of rigid or nonmetallic conduit for three conductorsbased on 40% maximum fill.* The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possiblejamming.
**This cable is not recognized by UL for Cable Tray-Use
(4) Ampacities for cable in cable tray are in accordance with the NEC,Section 392.80(B)(2)(2), Table 311.60(C)(69) (copper), for single conductorcables installed in a single layer, in uncovered tray, with a maintained spacingof 1 cable OD or more at 105°C conductor temperature and 40°C ambienttemperature and multi-point grounding.
Okonite’s web site, www.okonite.com contains the most up to date information.
ULR
Okoguard -Okoseal Type MV-105® ®
15kV Shielded Power CableOne Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
100% and 133% Insulation Level
A Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCInsulation Screen-ExtrudedDSemiconducting EPRShield-Copper TapeEJacket OkosealF
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 9
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in othersolid dielectrics. Okoguard insulation, withthe distinctive red color and a totallyintegrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free service.The triple tandem extrusion of the screenswith the insulation provides optimumelectrical characteristics.
JacketThe Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to oil, acids and mostchemicals.
ApplicationsOkoguard shielded Okoseal Type MV-105power cables are recommended fordistribution circuits, and for feeders orbranch circuits.Type MV cables may be installed in wet ordry locations, indoors or outdoors (exposedto sunlight), in any raceway or undergroundduct, directly buried if installed in a systemwith a grounding conductor in close proximitythat conforms with NEC Section 311.36 and250.4(A)(5), or messenger supported inindustrial establishments and electric utilities.
SpecificationsConductor: Annealed uncoated coppercompact stranded per ASTM B-496.Strand Screen: Extruded semiconductingEPR strand screen. Meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC74, AEIC CS8, CSAC68.10 and UL 1072.Insulation: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA C68.10 and UL 1072.Insulation Screen: Extrudedsemiconducting EPR insulation screen .Meets or exceeds electrical and physicalrequirements of ICEA S-93-639/NEMAWC74 & S-97-682, AEIC CS8, CSA C68.10and UL 1072.Shield: 5 mil bare copper tape helicallyapplied with 12.5% nominal overlap.
Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSAC68.10 and UL 1072 for polyvinyl chloridejackets.UL Listed as Type MV-105 and sunlightresistant in accordance with UL 1072 .CSA C68.10 listed as FT1, SR, andLTDD (-25°C).
Product Features• Triple tandem extruded, all EPR system.• Okoguard cables meet or exceed allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).• 105°C continuous operatingtemperature.• 140°C emergency rating.• 250°C short circuit rating.• Excellent corona resistance.• Screens are clean stripping.• Exceptional resistance to "treeing".• Moisture resistant.• Resistant to most oils, acids, andalkalies.• Sunlight resistant.• Improved Temperature Rating.
ULR
Okoguard-Okoseal Type MV-10515kV Shielded Power CableOne Okopact (Compact Stranded)
105°C RatingCopper Conductor/
Product DataSection 2: Sheet 9
115-23-3011115-23-3013
2 33.61 42.4
0.67 0.730.70 0.76
60 1.5280 2.03
0.87 22.10.94 23.9
555 610665 720
165 225 165190 260 185
33
115-23-3015115-23-3017115-23-3019
1/0 53.52/0 67.43/0 85.0
0.74 0.800.78 0.840.83 0.89
80 2.0380 2.0380 2.03
0.98 24.81.02 25.81.07 27.2
755 820865 930
1000 1070
215 295 215255 335 245290 380 275
333
115-23-3021115-23-3023115-23-3027
4/0 107.0250 127.0350 177.0
0.88 0.940.93 0.991.03 1.07
80 2.0380 2.0380 2.03
1.12 28.31.18 30.01.26 32.0
1170 12501325 14051700 1800
330 435 315365 475 345440 575 415
33½3½
115-23-3031115-23-3035115-23-3037
500 253.0750 380.0
1000 507.0
1.14 1.191.32 1.371.47 1.52
80 2.0380 2.0380 2.03
1.38 35.11.55 39.41.71 43.4
2240 23853105 33403950 4185
535 700 500655 865 610755 1005 690
455
Okoguard Insulation: 220 mils (5.59mm), 133% Insulation Level
O/21050209
THE OKONITE COMPANYRamsey, New Jersey 07446
Catalo
gNum
ber (1)
Conduct
or si
ze
AW
G o
r kc
mil
Conduct
or Size
-mm
²
Appro
x. D
ia. o
ver
Insu
latio
n (in.)
Appro
x. D
ia. o
ver
Scree
n (in.)
Jacket Thic
kness- m
ils
Jacket Thic
kness- m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Am
paciti
es (2
) Conduit
inAir
Am
paciti
es(3
) Dire
ct B
urial
Conduit
Size
Inch
es(5
)*
Am
paciti
es (4
) Under
ground D
uct
115-23-3111115-23-3113
2 33.61 42.4
0.76 0.810.79 0.85
80 2.0380 2.03
1.00 25.41.04 26.4
670 720755 820
165 225 165190 260 185
33
115-23-3115115-23-3117115-23-3119
1/0 53.52/0 67.43/0 85.0
0.83 0.890.87 0.920.92 0.98
80 2.0380 2.0380 2.03
1.07 27.11.11 28.21.16 29.3
845 915950 1020
1000 1180
215 295 215255 335 245290 380 275
333½
115-23-3121115-23-3123115-23-3127
4/0 107.0250 127.0350 177.0
0.96 1.021.01 1.071.11 1.16
80 2.0380 2.0380 2.03
1.20 30.51.26 32.01.35 34.3
1260 13601415 15001790 1920
330 435 315365 475 345440 575 415
3½3½4
115-23-3131115-23-3135115-23-3139
500 253.0750 380.0
1000 507.0
1.22 1.281.40 1.461.54 1.60
80 2.0380 2.03
110 2.79
1.47 37.31.64 41.71.84 46.7
2325 25103220 34554075 4340
535 700 500655 865 610755 1005 690
456
Okoguard Insulation: 175 mils (4.45mm), 100% Insulation Level
Aluminum Conductors(1) Aluminum conductors are available on special order.Ampacities(2) Ampacities are in accordance with Table 311.60(C)(73) of the NEC for three singleType MV-105 conductors, or single conductors twisted together (triplexed) andinstalled in an isolated conduit in air at an ambient temperature of 40°C and aconductor temperature of 105°C.(3) Ampacities are in accordance with Table 311.60(C)(81) of the NEC for an insulatedsingle conductor directly buried with a conductor temperature rating of 105°C, ambientearth temperature of 20°C, 100% Load Factor, thermal resistance (RHO) of 90, 7 1/2 inchspacing between conductor center lines, and 24 inch spacing between circuits.
Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the OkoniteEngineering Data Bulletin for installation in duct banks, multiple point groundedshields, other ambient temperatures, circuit configurations or installationrequirements.(5) Recommended size of rigid or nonmetallic conduit for three conductorsbased on 40% maximum fill.* The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possiblejamming.
(4) Ampacities are in accordance with Table 311.60(C)(77) of the NEC for three singleconductors or triplexed cable in one underground raceway, three feet deep with aconductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of20°C, and thermal resistance (RHO) of 90.
Okonite’s web site, www.okonite.com contains the most up to date information.
ULR
Okoguard -Okolon TS-CPE Type MV-105® ®
15kV Shielded Power CableOne Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
100% and 133% Insulation Level
For Cable Tray Use-Sunlight Resistant
A Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCInsulation Screen-ExtrudedDSemiconducting EPRShield Copper TapeEJacket-Okolon TS-CPEF
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 11
A
B
C
D
E
F
OK
ON
ITE
4 4
/0A
WG
CO
MP
AC
TC
U O
KO
GU
AR
DE
PT
S-C
PE
15kV
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene (EPR)based, thermosetting compound, whoseoptimum balance of electrical and physicalproperties is unequaled in other soliddielectrics. Okoguard insulation, with thedistinctive red color and a totally integratedEPR system, provides the optimum balanceof electrical and physical properties for long,problem free service.The triple tandem extrusion of the screenswith the insulation provides optimum electricalcharacteristics.
JacketThe Okolon TS-CPE jacket on this cable is avulcanized chloronated polyethylene basecompound which is mechanically rugged,flame, radiation, and oil resistant.
ApplicationsOkoguard shielded Okolon TS-CPE Type MV-105 power cables are recommended for useas feeder circuits in electric utility generatingstations, for distribution circuits, and forfeeders or branch circuits in industrial andcommercial installations. Type MV cablesmay be installed in wet or dry locations,indoors or outdoors (exposed to sunlight), inany raceway or underground duct, directlyburied if installed in a system with agrounding conductor in close proximity thatconforms with NEC Section 311.36 and250.4(A)(5), or messenger supported inindustrial establishments and electric utilities.Sizes 1/0 AWG and larger may also beinstalled in cable tray.
SpecificationsConductor: Annealed uncoated coppercompact stranded per ASTM B-496.Strand Screen: Extruded semiconductingEPR strand screen. Meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC74 & S-97-682, AEICCS8, CSA C68.10 and UL 1072.Insulation: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8,CSA C68.10 and UL 1072.Insulation Screen: Extruded semiconductingEPR insulation screen. Meets or exceeds
electrical and physical requirements of ICEAS-93-639/NEMA WC74 & S-97-682, AEICCS8, CSA C68.10 and UL 1072.Shield: 5 mil bare copper tape helicallyapplied, with 25% minimum overlap.Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA CS68.10and UL 1072 for chloronated polyethylenejackets.UL listed as Type MV-105, sunlight resistantand for use in cable tray in accordance withUL 1072.CSA C68.10 listed as FT4, SR, LTDD(-25°C), and TC (1/0 AWG & larger).
Product Features• Triple tandem extruded, all EPR system.
• Okoguard cables meet or exceed allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).
• 105°C continuous operating temperature.
• 140°C emergency rating.
• 250°C short circuit rating.
• Passes UL and IEEE 383 and 1202 (1/0AWG & larger) Vertical Tray Flame Tests.
• Excellent corona resistance.
• Screens are clean stripping.
• Exceptional resistance to “treeing."
• Moisture resistant.
• Resistant to most oils, acids, andalkalies.• Sunlight resistant.• UL listed For Cable Tray Use; 1/0 AWG &larger.• Improved Temperature Rating.
ULR
Okoguard-Okolon TS-CPE Type MV-10515kV Shielded Power CableOne Okopact (Compact Stranded)Copper Conductor/ 105°C Rating100% and 133% Insulation LevelFor Cable Tray Use-Sunlight Resistant
Okoguard Insulation: 175 mils (4.45mm), 100% Insulation Level
115-23-2011115-23-2013
21
33.642.4
0.670.70
0.730.76
6080
1.522.03
0.890.96
22.524.4
585700
640765
165190
165185
——
33
115-23-2015115-23-2017115-23-2019
1/02/03/0
53.567.485.0
0.730.770.82
0.790.830.88
808080
2.032.032.03
1.001.041.09
25.326.427.6
790905
1040
855965
1110
215255290
215245275
290335385
333
115-23-2021115-23-2023115-23-2027
4/0250350
107.0127.0177.0
0.870.931.01
0.930.991.07
808080
2.032.032.03
1.131.191.28
28.730.332.4
120013701725
128014501825
330365440
315345415
445495610
312
312
4
115-23-2031115-23-2035115-23-2038
500750
1000
253.0380.0507.0
1.131.311.46
1.191.371.52
808080
2.032.032.03
1.391.571.73
35.439.943.9
225531404020
237033204255
535655755
500610690
765990
1185
455
Okoguard Insulation: 220 mils (5.59mm), 133% Insulation Level
115-23-2111115-23-2113
21
33.642.4
0.750.79
0.810.85
8080
2.032.03
1.011.05
25.826.7
710790
775860
165190
165185
——
33
115-23-2115115-23-2117115-23-2119
1/02/03/0
53.567.485.0
0.820.860.91
0.880.920.97
808080
2.032.032.03
1.081.121.18
27.528.529.9
880995
1145
94510751225
215255290
215245275
290335385
312
312
312
115-23-2121115-23-2123115-23-2127
4/0250350
107.0127.0177.0
0.961.011.10
1.021.071.16
808080
2.032.032.03
1.221.281.37
31.132.434.7
131014651840
140015651940
330365440
315345415
445495610
312
44
� 115-23-2131� 115-23-2135
115-23-2138
500750
1000
253.0380.0507.0
1.221.401.54
1.281.461.60
8080
110
2.032.032.79
1.491.661.87
37.742.247.5
238532854275
257035404540
535655755
500610690
765990
1185
556
115-23-2144115-23-2145
12501500
633.5760.2
1.751.88
1.811.94
110110
4.334.33
2.082.20
52.756.0
52556140
56456540
845925
770845
13501500
68
Okonite's web site, www.okonite.com contains the most up to date information.
� Authorized Stock Item. Available from our Customer Service Centers.
Aluminum Conductors
(1) Aluminum conductors are available on special order.
Ampacities
(2) Ampacities are in accordance with Table 311.60(C)(73) of the NEC for threesingle Type MV-105 conductors, or single conductors twisted together (tri-plexed) and installed in an isolated conduit in air at an ambient temperature of40°C and a conductor temperature of 105°C.
(3) Ampacities are in accordance with Table 311.60(C)(77) of the NEC for threesingle conductors or triplexed cable in one underground raceway, three feetdeep with a conductor temperature of 105°C, 100% Load Factor, an ambientearth temperature of 20°C and thermal resistance (RHO) of 90.
(4) Ampacities for cable in cable tray are in accordance witht he NEC, Section392.80(B)(2)(2), Table 311.60(C)(69) (copper), for single conductor cables in-stalled in a single layer, in uncovered tray, with a maintained spacing of 1 cable
OD or more at 105°C conductor temperature and 40°C ambient temperatureand multi-point grounding.
Refer to the NEC, IEEE/ICEA-S-135 Power Cable Ampacities, or the OkoniteEngineering Data Bulletin for installation in duct banks, multiple point groundedshields, other ambient temperatures, circuit configurations or installation re-quirements.
(5) Recommended size of rigid or nonmetallic conduit for three conductorsbased on 40% maximum fill.
*The jam ratio conduit l.D. to cable O.D. should be checked to avoid possiblejamming.
P/21010211
Product DataSection 2: Sheet 11
Catalo
gNum
ber(1
)
Approx.
NetW
eight
(lbs./
1000
’)
Conductor Size
- mm
2
Approx.
O.D. -
mm
Conductor Size
AWG
or kcm
il
Jack
et
Thicknes
s - mm
Approx.
Dia.
over In
sulat
ion
(in.)
Jack
et
Thicknes
s - mils
Approx.
O.D. -
Inch
es
Approx.
Dia.
over Scr
een
(in.)
Approx.
ShipW
eight
(lbs./
1000
’)
Ampac
ities
(3)
Undergro
und
Conduit(5
)
SizeIn
ches
*
Ampac
ities
(2)
Conduitin
Air
Ampac
ities
(4)
Cable
Tray
THE OKONITE COMPANYRamsey, New Jersey 07446
ULR
Okoguard -Okoseal Type MV-105® ®
35kV Shielded Power CableOne Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
100% and 133% Insulation Level
A Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCInsulation Screen-ExtrudedDSemiconducting EPRShield-Copper TapeEJacket-OkosealF
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 16
InsulationOkoguard Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in othersolid dielectrics. Okoguard insulation, withthe distinctive red color and a totallyintegrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free service. Thetriple tandem extrusion of the screens withthe insulation provides optimum electricalcharacteristics.
JacketThe Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to oil and mostchemicals.
ApplicationsOkoguard shielded Okoseal Type MV-105power cables are recommended fordistribution circuits, and for feeders orbranch circuits in industrial and commercialinstallations.Type MV cables may be installed in wet ordry locations, indoors or outdoors (exposedto sunlight), in any raceway or undergroundduct, directly buried if installed in a systemwith a grounding conductor in close proximitythat conforms with NEC Section 311.36 and250.4(A)(5), or messenger supported inindustrial establishments and electric utilities.
SpecificationsConductor: Annealed uncoated coppercompact stranded per ASTM B-496.Strand Screen: Extruded semiconductingEPR strand screen. Meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC7 & S-97-682, AEICCS8, CSA C68.10 and UL 1072.Insulation: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74, & S-97-682 AEIC CS8,CSA C68.10 and UL 1072.Insulation Screen: Extrudedsemiconducting EPR insulation screen.Meets or exceeds electrical and physicalrequirements of ICEA S-93-639/NEMAWC74 & S-97-682, AEIC CS8, CSA C68.10and UL 1072.Shield: 5 mil bare copper tape helicallyapplied with 12.5% nominal overlap.
Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMAWC74 & S-97-682, CSA C68.10 and UL 1072for polyvinyl chloride jackets.
UL Listed as Type MV-105 and sunlightresistant, in accordance with UL 1072.
CSA C68.10 listed as FT1, SR, and LTDD(-25°C).
Product Features• Triple tandem extruded all EPR system.
• Okoguard cables meet or exceed allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).
• 105°C continuous operating temperature.
• 140°C emergency rating.
• 250°C short circuit rating.
• Excellent corona resistance.
• Screens are clean stripping.
• Exceptional resistance to "treeing."
• Moisture resistant.
• Resistant to most oils, acids, and alkalies.
• Sunlight resistant.
• Improved Temperature Rating.
UL®
Okoguard-Okoseal Type MV-10535kV Shielded Power CableOne Okopact (Compact Stranded)Copper Conductor/105°C Rating100% and 133% Insulation Level
Product DataSection 2: Sheet 16
115-23-3516115-23-3517115-23-3519
1/0 53.52/0 67.43/0 85.0
1.09 1.151.12 1.191.17 1.23
80 2.0380 2.0380 2.03
1.33 34.01.37 35.01.42 36.1
1140 12751270 13801420 1605
215 295 215255 335 245290 380 275
444
115-23-3521115-23-3523115-23-3527
4/0 107.0250 127.0350 177.0
1.23 1.291.27 1.331.36 1.43
80 2.0380 2.0380 2.03
1.47 37.41.52 38.71.61 41.2
1595 18001790 19502150 2420
330 435 315365 475 345440 575 415
455
115-23-3531115-23-3535115-23-3537
500 253.0750 380.0
1000 507.0
1.48 1.541.66 1.721.81 1.86
80 2.03110 2.79110 2.79
1.73 43.91.97 50.12.12 53.9
2720 30143765 42404671 5300
535 700 500655 865 610755 1005 690
566
Okoguard Insulation: 420 mils (10.7mm), 133% Insulation Level
S/21050216
THE OKONITE COMPANYRamsey, New Jersey 07446
Catalo
g Num
ber (1)
Conductor s
ize
AWG
or k
cmil
Conductor S
ize -m
m²
Approx. D
ia. o
ver
Insula
tion (i
n.)
Approx. D
ia. o
ver
Screen (i
n.)
Jacket Thic
kness - m
ils
Jacket Thic
kness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. N
et Weig
ht
lbs./1
000’
Approx. S
hip W
eight
lbs./1
000’
Ampaciti
es (2) C
onduit in
Air
Ampaciti
es (3) D
irect B
urial
Conduit Siz
e
Inches (5
)*
Ampaciti
es (4) U
ndergro
und Duct
115-23-3656115-23-3657115-23-3659
1/0 53.52/0 67.43/0 85.0
1.24 1.301.28 1.341.32 1.39
80 2.0380 2.0380 2.03
1.49 37.91.53 39.01.57 40.0
1350 15351470 16651630 1825
215 295 215255 335 245290 380 275
555
115-23-3661115-23-3663115-23-3667
4/0 107.0250 127.0350 177.0
1.39 1.451.42 1.481.52 1.58
80 2.0380 2.03
110 2.79
1.64 41.91.69 42.91.83 46.5
1840 20851985 22502495 2770
330 435 315365 475 345440 575 415
555
115-23-3671115-23-3675115-23-3677
500 253.0750 380.0
1000 507.0
1.63 1.691.81 1.871.97 2.02
110 2.79110 2.79110 2.79
1.94 49.32.12 53.92.27 57.6
3085 35554055 46805980 5630
535 700 500655 865 610755 1005 690
668
Okoguard Insulation: 345 mils (8.76mm), 100% Insulation Level
Aluminum Conductors(1) Aluminum conductors are available on special order.Ampacities(2) Ampacities are in accordance with Table 311.60(C)(73) of the NEC for threesingle Type MV-105 conductors, or single conductors twisted together (triplexed)and installed in an isolated conduit in air at an ambient temperature of 40°C and aconductor temperature of 105°C.(3) Ampacities are in accordance with Table 311.60(C)(81) of the NEC for aninsulated single conductor directly buried with a conductor temperature ratingof 105°C, ambient earth temperature of 20°C, 100% Load Factor, thermalresistance (RHO) of 90, 7 1/2 inch spacing between conductor center lines, and24 inch spacing between circuits.
Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the OkoniteEngineering Data Bulletin for installation in duct banks, multiple point groundedshields, other ambient temperatures, circuit configurations or installationrequirements.(5) Recommended size of rigid or nonmetallic conduit for three conductorsbased on 40% maximum fill.* The jam ratio conduit I.D. to cable O.D. should be checked to avoid possiblejamming.
(4) Ampacities are in accordance with Table 311.60(C)(77) of the NEC for threesingle conductors or triplexed cable in one underground raceway, three feet deepwith a conductor temperature of 105°C, 100% Load Factor, an ambient earthtemperature of 20°C, and thermal resistance (RHO) of 90.
Okonite’s web site, www.okonite.com contains the most up to date information.
UL®
Okoguard -Okoseal® ®
69kV Shielded Power CableConductor/105°C Rating - 100% Insulation Level
A Uncoated, Okopact (Compact)or Compress Stranded Copperor Aluminum ConductorStrand Screen-ExtrudedBSemiconducting EPRInsulation-Okoguard EPRCInsulation Screen-ExtrudedDSemiconducting EPRShield-5 Mil Uncoated CopperETapeJacket-OkosealF
Product DataSection 2: Sheet 18
InsulationOkoguard is Okonite's registered tradename for its exclusive ethylene-propylenerubber (EPR) based, thermosettingcompound, whose optimum balance ofelectrical and physical properties isunequaled in other solid dielectrics.Okoguard insulation, with the distinctivered color and a totally integrated EPRsystem, provides the optimum balance ofelectrical and physical properties for long,problem free service.The triple tandem extrusion of the screenswith the insulation provides optimumelectrical characteristics.
JacketThe Okoseal (PVC) jacket supplied withthis cable is mechanically rugged and hasexcellent resistance to oil and mostchemicals.
ApplicationsOkoguard-Shielded-Okoseal 69kV Cablesare designed for use as primary circuits inelectrical utility and industry applicationswhere they provide maximum circuitsecurity and economical installation.Rated 105°C for continuous operatingtemperature, Okoguard 69kV cables maybe installed in wet or dry locations indoorsor outdoors (exposed to sunlight) inunderground ducts, conduits or directburial.
SpecificationsConductors: Uncoated copper sizes 350through 1000 kcmil compact roundstranding per ASTM B-496. Uncoatedcopper sizes larger than 1000 kcmilcompress round stranding per ASTM B-8.EC Aluminum per ASTM B609, Class Bstranded per B-231.Strand Screen: Extruded semiconductingEPR strand screen. Meets or exceedselectrical and physical requirements ofICEA S-108-720, AEIC CS9.
Insulation: Meets or exceeds electricaland physical requirements of ICEAS-108-720 and AEIC Cs9.Insulation Screen: Extrudedsemiconducting EPR insulation screen.Meets or exceeds electrical andphysical requirements of ICEA S-108-720 and AEIC Cs9.Shield: 5 mil bare copper tape helicallyapplied with 25% nominal overlap.Jacket: Meets or exceeds electricaland physical requirements of ICEA S-108-720 for polyvinyl chloride jackets.Optional jackets include Okolene,Okolon TS-CPE, Okoclear and, whenspecified, a semi-conducting outerlayer.Optional shields include neutral wires,LCS and a combination of copper tapeand wires. A CLX armor covering isalso available.
Product Features• Triple tandem extruded, all EPRsystem.
• Okoguard cables meet or exceedrecognized industry standards (AEIC,NEMA/ ICEA).
• 105°C continuous operatingtemperature.
• 140°C emergency rating.
• 250°C short circuit rating.
• Excellent corona resistance.
• Exceptional resistance to “treeing."
• Low shield resistance.
• Moisture resistant.
• Resistant to most oils, acids, andalkalies.
• Sunlight resistant.
• Improved Temperature Rating.
• Screens are clean stripping.• Production testing and associatedfrequency to be performed inaccordance with ICEA S-108-720,latest edition.
Okoguard-Okoseal69kV Shielded Power CableConductor/105°C Rating100% Insulation Level
Okoguard Insulation: 650 mils(16.5mm)
Product DataSection 2: Sheet 18
Copper Conductor - Compact Round
115-22-3765115-22-3767
▲115-22-3771115-22-3775
250 127350 177500 253750 380
1.91 2.012.01 2.112.12 2.222.30 2.40
110 2.79110 2.79110 2.79110 2.79
2.26 57.42.36 59.92.47 62.72.64 67.1
3086 34593538 38734179 45145213 5805
444 398550 495667 599825 742
3½3½3½4
▲115-22-3777 1000 507 2.44 2.54 140 3.56 2.85 72.4 6389 7151 957 861 4
Copper Conductor - Compress Round
115-22-3778 1250 633 2.68 2.78 140 3.56 3.09 78.5 7582 8344 1066 959 5
115-22-3779 1500 761 2.78 2.88 140 3.56 3.19 81.0 8527 9447 1157 1042 5
G/20080218THE OKONITE COMPANY
Ramsey, New Jersey 07446
Catalo
g Num
ber
Conductor s
ize
AWG
or kcm
il
Conductor S
ize
-mm
²
Approx. D
ia. o
ver
Insula
tion (i
n.)
Approx. D
ia. o
ver
Screen (i
n.)
Jacket Thic
kness- m
ils
Jacket Thic
kness- m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. N
et Weig
ht
lbs./1
000’
Approx. S
hip W
eight
lbs./1
000’
Ampaciti
es(1
) Dire
ct Buria
l
Ampaciti
es(1
)
Undergro
und Duct
Conduit Siz
e
Inches
(2)*
▲ Available from our Customer Service Centers.Authorized Stock Item.
Additional conductor sizes are available.
Ampacities
(1) Ampacities are in accordance with ICEA P-53-426 for threesingle 69kV conductors directly buried or in individual ducts underground, 36"deep with 7 1/2" spacing between conductors, at 105°C maximum conductortemperature, 25°C earth temperature, soil resistivity of 90 Rho, 100% loadfactor, and open circuit shields.
(2) Recommended size of rigid nonmagnetic or nonmetallic conduit for a singleconductor based on 53% maximum fill.
Aluminum Conductor - Compress Round
135-22-3765135-22-3767135-22-3771135-22-3775
250 127350 177500 252750 380
1.94 2.042.06 2.162.19 2.292.37 2.47
110 2.79110 2.79110 2.79110 2.79
2.29 58.22.41 61.22.54 64.52.72 69.1
2614 32002888 32233244 35793778 4175
348 312429 386523 469650 584
3½3½3½4
135-22-3777135-22-3778
1000 5071250 633
2.52 2.622.68 2.78
140 3.56140 3.56
2.93 74.43.09 78.5
4433 49044954 5716
759 683853 768
45
135-22-3779 1500 761 2.80 2.90 140 3.56 3.21 81.5 5381 6034 936 842 5
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard -Okoseal Type MV-105® ®
5/8kV Okoguard Shielded Power Cable3 Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
5kV-133% or 8kV-100% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
A Uncoated Okopact (CompactStranded) Copper ConductorExtruded Semiconducting EPRBStrand Screen
C Okoguard Insulation (EPR)D Extruded Semiconducting EPR
Insulation ScreenE Phase Identification TapeF Okopact Compact Copper
Grounding ConductorG Uncoated Copper ShieldH Fillers and Binder TapeJ Jacket-Black Okoseal
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 19
Grounding Conductor: Uncoated coppercompact stranded per ASTM B-496 andsized in accordance with UL 1072.Assembly: Cabled with fillers and groundwire in the interstices, binder tape overall.Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74, CSA C68.10 and UL1072 for polyvinyl chloride jackets.
UL Listed as Type MV-105, sunlightresistant for use in cable tray, and fordirect burial in accordance with UL 1072.
Cables listed to CSA C68.10
Product Features• Triple tandem extruded, all EPRsystem.
• Complete prepackaged, color coded,factory tested wiring system.• Passes the UL 1072, IEEE 383 andIEEE 1202/FT4 Vertical Tray Flame Tests.• Complies with NEC Section 336.36 andis suitable for direct buried when installedin accordance with NEC Sections250.4(A)(5).• Minimum installation temperature of-40°C.• Excellent corona resistance.• Screens and clean stripping.• Exceptional resistance to “treeing”.• Improved Temperature Rating.• Sizes 4/0 AWG and larger are CSAlisted as FT4, SR, LTGG (-40°C), and TC-ER.• Sizes smaller than 4/0 AWG are CSAlisted as FT4, SR, and LTDD (-25°C).
InsulationOkoguard Is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) base, thermosetting compound, whoseoptimum balance of electrical and physicalproperties is unequaled in other soliddielectrics. Okoguard insulation, with thedistinctive red color and a totally integratedEPR system, provides the optimum balance ofelectrical and physical properties for long,problem free service.
AssemblyThe Type MV-105 conductors are assembledwith fillers and a binder tape overall. One barestranded copper ground conductor is placedin one of the outer interstices.
JacketThe Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to oil and mostchemicals.
ApplicationsOkoguard shielded three conductor Type MV-105 power cables are recommended fordistribution circuits, and for feeders or branchcircuits in industrial & utility power distributionsystems. Type MV cables may be installed inwet or dry locations, indoors or outdoors(exposed to sunlight), in any raceway orunderground duct, directly buried, cable tray,or messenger supported in industrialestablishments and electric utilities.
SpecificationsConductors: Uncoated copper compactstranded per ASTM B-496.Strand Screen: Extruded semiconductingEPR strand screen meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC74, CSA C68.10 and UL1072.Insulation: Okoguard meets or exceeds theelectrical and physical requirements of ICEAS-93-639/NEMA WC74, CSA C68.10 and UL1072. The insulated conductors are tested inaccordance with AEIC CS8.Insulation Screen: Extruded semiconductingEPR insulation screen per ICEA S-93-639/NEMA WC74, AEIC CS8, CSA C68.10and UL 1072.Shield: 5 mil uncoated copper tape helicallyapplied with 12.5% nominal overlap.Phase Identification: Color coded (black,red, blue) polyester ribbon laid longitudinallyunder the copper shield.
UL®
Product DataSection 2: Sheet 19
N/21060219
THE OKONITE COMPANYRamsey, New Jersey 07446
Cat
alog N
umber
(1)
Conduct
or siz
e
(AW
G o
r kcm
il)
Conduct
or Siz
e -m
m²
Appro
x. D
iam
eter
ove
r
Insu
latio
n (in.)
Gro
unding
Conduct
or Size
(AW
G/k
cmil)
Jack
et T
hickn
ess
- mm
Appro
x. C
ore O
.D. -
Inch
es
Appro
x. Net W
eight
lbs./1
000’
Appro
x. Ship
Weig
ht
lbs./1
000’
Am
pacities
inCable
Tray
(2)
Am
pacities
Dire
ct Buria
l (3)
▲ Available from our Customer Service Centers.Authorized stock item.Aluminum Conductors
Aluminum conductors are available on special order.(1)Ampacities(2) Ampacities are in accordance with Table 311.60(C)(71) of the NEC for aninsulated three conductor cable, isolated in air, with a conductor operating tem-perature of 105°C and an ambient air temperature of 40°C.
Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the OkoniteEngineering Data Bulletin for installation in duct banks, other ambient tempera-tures, circuit configurations or installation requirements.
(3) Ampacities are in accordance with Table 311.60(C)(83) of the NEC for aninsulated three conductor cable directly buried in the earth with a conductor op-erating temperature of 105°C, ambient earth temperature of 20°C, 100% loadfactor and thermal resistance (RHO) of 90.
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard -Okoseal Type MV-105® ®
5/8kV Okoguard Shielded Power Cable3 Okopact (Compact Stranded) Copper Conductor/105°C Rating
®
5kV-133% or 8kV-100% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
Okoguard Insulation: 115 mils (2.92mm), 5kV-133% or 8kV-100% Insulation Level
▲114-23-3630114-23-3633
6 13.34 21.2
0.440.48
6 13.36 13.3
1.10 27.91.19 30.2
80 2.0380 2.03
1.29 32.81.38 35.1
1015 11151235 1390
88 115115 150
▲114-23-3640114-23-3642
2 33.61/0 53.5
0.540.61
6 13.34 21.2
1.32 33.51.46 37.0
80 2.0380 2.03
1.51 38.31.65 41.9
1560 17152090 2250
155 190205 245
▲114-23-3648▲114-23-3736
114-23-3770
2/0 67.44/0 107.0
250 127.0
0.650.750.80
4 21.23 26.72 26.7
1.55 39.41.77 45.01.88 47.8
110 2.79110 2.79110 2.79
1.80 45.72.02 51.32.13 54.1
2513 26953455 37803961 4245
240 280320 360355 395
▲114-23-3772▲114-23-3782
350 177.0500 253.0
0.891.01
2 33.61 42.4
2.08 52.82.33 59.2
110 2.79110 2.79
2.33 59.22.59 65.8
5116 56656799 7430
440 475545 570
Jack
et T
hickn
ess
- mils
Gro
unding
Conduct
or
Size
- mm
²
Appro
x. C
ore O
.D. -
mm
Appro
x. O.D
. -In
ches
Appro
x. O.D
. -m
m
For 8kV ampacities refer to the NEC tables referenced below in the columns listed 5001-35,000 Volts
UL®
Okoguard Okoseal Type MV-105® ®
15kV Okoguard Shielded Power Cable3 Okopact (Compact Stranded) Copper Conductors/105°C Rating
®
100% & 133% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
A Uncoated Okopact (CompactStranded) Copper ConductorsExtruded Semiconducting EPRBStrand Screen
C Okoguard Insulation (EPR)D Extruded Semiconducting EPR
Insulation ScreenE Phase Identification TapeF Okopact Copper Grounding
ConductorG Uncoated Copper ShieldH Fillers and Binder TapeJ Jacket-Black Okoseal
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 20
InsulationOkoguard Is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) base, thermosetting compound, whoseoptimum balance of electrical and physicalproperties is unequaled in other soliddielectrics. Okoguard insulation, with thedistinctive red color and a totally integratedEPR system, provides the optimum balanceof electrical and physical properties for long,problem free service.
AssemblyThe Type MV-105 conductors areassembled with fillers and a binder tapeoverall. One bare stranded copper groundconductor is placed in one of the outerinterstices.
JacketThe Okoseal (PVC) jacket supplied with thiscable is mechanically rugged and hasexcellent resistance to oil and mostchemicals.
ApplicationsOkoguard shielded three conductor OkosealType MV-105 power cables arerecommended for distribution circuits, andfor feeders or branch circuits in industrialand utility power distribution systems. TypeMV cables may be installed in wet or drylocations, indoors or outdoors (exposed tosunlight), in any raceway or undergroundduct, directly buried, cable tray, ormessenger supported in industrialestablishments and electric utilities.
SpecificationsConductors: Uncoated copper compactstranded per ASTM B-496.Strand Screen: Extruded semiconductingEPR strand screen meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC74, CSA C68.10 andUL 1072.Insulation: Okoguard meets or exceeds theelectrical and physical requirements of ICEAS-93-639/NEMA WC74, CSA C68.10 andUL 1072. The insulated conductors aretested in accordance with AEIC CS8.Insulation Screen: Extrudedsemiconducting EPR insulation screen perICEA S-93-639/NEMA WC74, AEIC CS8,CSA C68.10 and UL 1072.Shield: 5 mil uncoated copper tape helicallyapplied with 12.5% nominal overlap.
Phase Identification: Color coded (black,red, blue) polyester ribbon laidlongitudinally under the copper tapeshield.Grounding Conductor: Uncoated coppercompact stranded per ASTMB-496 and sized in accordance with UL1072.Assembly: Cabled with fillers and groundwire in the interstices, binder tape overall.Jacket: Meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMA WC74, CSA C68.10 and UL1072 for polyvinyl chloride jackets.
UL Listed as Type MV-105, sunlightresistant for use in cable tray, and fordirect burial in accordance with UL 1072.
Cables listed to CSA C68.10Product Features
• Triple tandem extruded, all EPR system.
• Complete prepackaged, color coded,factory tested wiring system.
• Passes the UL 1072, IEEE 383 andIEEE 1202/FT4 Vertical Tray Flame Tests.
• Complies with NEC Section 336.6 and issuitable for direct buried when installed inaccordance with NEC Sections250.4(A)(5).
• Minimum installation temperature of
-40°C.
• Excellent corona resistance.• Screens are clean stripping.• Exceptional resistance to “treeing”.• Improved Temperature Rating.• Sizes 4/0 AWG and larger are CSA listedas FT4, SR, LTGG (-40°C), and TC-ER.• Sizes smaller than 4/0 AWG are CSAlisted as FT4, SR, and LTDD (-25°C).
UL®
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard Okoseal Type MV-10515kV Okoguard Shielded Power Cable3 Okopact (Compact Stranded) Copper Conductors/105°C Rating
®
100% & 133% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
Product DataSection 2: Sheet 20
Cata
log
Num
ber(1
)
Conducto
r size
AWG
or kcmil
Conducto
r Size
-mm
²
Appro
x. D
ia. o
ver
Insu
latio
n (in.)
Jacket Thic
kness- m
ils
Jacket Thic
kness- m
m
Appro
x. O
.D. -
Inch
es
Appro
x. O
.D. -
mm
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Am
paciti
es in
Cab
le T
ray
(2)
Okoguard Insulation: 175 mils (4.45mm), 100% Insulation Level
115-23-3766115-23-3768
2 33.61/0 53.5
0.670.74
6 13.34 21.2
1.59 40.41.74 44.2
110 2.79110 2.79
1.83 46.51.97 50.0
1985 21302560 2770
185 200240 255
115-23-3770115-23-3772115-23-3774
2/0 67.44/0 107.0
250 127.0
0.780.880.93
4 21.23 26.73 26.7
1.82 42.22.04 51.82.15 54.6
110 2.79110 2.79110 2.79
2.06 52.32.28 57.92.39 60.7
2890 31503905 41904390 4930
275 290360 375400 410
115-23-3776115-23-3778115-23-3780
350 177.0500 253.0750 380.0
1.031.141.32
2 33.61 42.4
1/0 53.5
2.36 59.92.61 66.32.99 75.9
110 2.79140 3.56140 3.56
2.59 65.82.91 73.93.29 83.6
5608 62107480 8255
10320 11330
490 495600 590745 720
Okoguard Insulation: 220 mils (5.59mm), 133% Insulation Level
▲115-23-3802115-23-3804
2 33.61/0 53.5
0.760.83
6 13.34 21.2
1.79 45.51.93 49.0
110 2.79110 2.79
2.02 51.32.17 55.1
2280 25752857 3145
185 200240 255
▲115-23-3806▲115-23-3808
115-23-3810
2/0 67.44/0 107.0
250 127.0
0.870.971.03
4 21.23 26.73 26.7
2.02 51.32.24 56.92.36 60.0
110 2.79110 2.79110 2.79
2.26 57.42.48 63.02.59 65.8
3260 35704285 46404795 5295
275 290360 375400 410
▲115-23-3812▲115-23-3814
115-23-3816
350 177.0500 253.0750 380.0
1.121.241.41
2 33.61 42.4
1/0 53.5
2.56 65.02.81 71.43.19 81.0
140 3.56140 3.56140 3.56
2.85 72.43.10 78.73.49 88.7
6168 70007895 8945
10805 11800
490 495600 590745 720
Gro
unding
Conduct
or
Sizes
- Aw
g/kcm
il
Gro
unding C
onductor
Sizes
- m
m²
Appro
x. C
ore O
.D. -
Inch
es
Approx. C
oreO
.D. -
mm
Am
paciti
es
Dire
ct B
urial (
3)
(3) Ampacities are in accordance with Table 311.60(C)(83) of the NEC for aninsulated three conductor cable directly buried in the earth with a conductoroperating temperature of 105°C, ambient earth temperature of 20°C, 100%load factor, thermal resistance (RHO) of 90.
Refer to the NEC, lEEE/lCEA S-135 Power Cable Ampacities or the OkoniteEngineering Data Bulletin for installation in duct banks, other ambienttemperatures, circuit configurations or installation requirements.
▲ Available from our Customer Service Centers.Authorized stock item.
Aluminum Conductors
(1) Aluminum conductors available on special orders.
Ampacities
(2) Ampacities are in accordance with Table 311.60(C)(71) of the NEC for an insulated threeconductor cable, isolated in air, with a conductor operating temperature of 105°C and an ambient airtemperature of 40°C.
L/21060220
THE OKONITE COMPANYRamsey, New Jersey 07446
UL®
C-L-X VFD Type MV-90 or MC-HL®
2.4kV Okoguard Nonshielded Power Cable-Aluminum Sheath5000V CSA RA90
3 Okopact (Compact Stranded) Copper Conductors/90°C Rating®
100% & 133% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
A Uncoated Okopact (CompactStranded) Copper ConductorExtruded Semiconducting EPRBStrand Screen
C Okoguard (EPR) InsulationD Three Copper Grounding
ConductorsE Phase IdentificationF Fillers and Binder TapeG Impervious, Continuous,
Corrugated Aluminum C-L-XSheath
H Jacket-Low Temperature YellowOkoseal
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 21
®
3X
8A
WG
CU
GR
D C
LX
VF
D (
UL
) M
V-9
0 M
C-H
L
physical requirements of ICEA S-96-659/NEMA WC71 and UL 1072.Insulation: Okoguard meets or exceeds theelectrical and physical requirements ofICEA S-96-659/NEMA WC71 and UL 1072.Phase Identification: Print color code (black,red and blue).Grounding Conductors: Three uncoatedcopper Class B in accordance with UL1072.Assembly: Cabled with fillers and groundwires, in the interstices, binder tape overall.Sheath: Close fitting, impervious,continuous, corrugated aluminum C-L-X perUL 1072. C-L-X is recognized as agrounding conductor by NEC.Jacket: A low temperature sunlightresistant, yellow PVC jacket in accordancewith UL 1072. Other color jackets areavailable.UL Listed as type MV-90 or MC-HL,sunlight resistant, for use in cable tray, andfor direct burial in accordance with UL 1072and 2225.
Product Features• Tandem extruded, all EPR system.• Complete prepackaged, color coded,factory tested wiring system.• Okoguard C-L-X cables meet or exceedelectrical and physical requirements of allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).
• Passes the vertical tray flame test
requirements of IEEE 383 and 1202, UL
1072, ICEA T-29-520(210,000 BTU/hr.)• Complies with NEC Section 336.36 and issuitable for direct buried when installed inaccordance with NEC Sections 250.4(A)(5).• Complies with NEC Articles 501, 502, 503and 505 for hazardous locations.• Continuous sheath provides groundingsafety.• Excellent corona resistance.• Exceptional resistance to "treeing."• Stress cones not required.• Minimum installation temperature of -40°C.• Three symmetrical grounding conductorswith the CLX sheath provide a superior lowresistance return path for VFD and othermodern ac drive/motor applications.• ABS listed as CWCMC Type MC-HL.• CSA listed as RA90, FT4, SR, HL, -40°Cand 5000V.
InsulationOkoguard is Okonite's registered trade name forits exclusive ethylene-propylene rubber (EPR)base, thermosetting compound, whose optimumbalance of electrical and physical properties isunequaled in other solid dielectrics. Okoguardinsulation, with the distinctive red color and atotally integrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free service.
AssemblyThe Type MV-90 conductors are assembled withfillers and a binder tape into a round core. Threebare stranded copper grounding conductors,located in the outer interstices, is provided forgrounding. A continuously corrugated weldedaluminum sheath C-L-X encases the cable core.The C-L-X sheath is protected with a lowtemperature yellow Okoseal (PVC) jacket. The®
impervious, continuous, corrugated aluminum C-L-X sheath provides complete protection againstmoisture, liquids and gases in addition to itsexcellent mechanical strength. In addition, thealuminum CLX sheath exceeds the equipmentgrounding requirements of NEC Section 250.118and 250.122, and can be used as the equipmentgrounding conductor in non-HL areas. Theoverall Okoseal (PVC) jacket allows the cable tobe direct buried in the ground, embedded inconcrete or areas subjected to a corrosiveatmosphere.
ApplicationsC-L-X power cables are recommended as aneconomical alternate to a wire in conduit system.They are designed specifically for use onfeeders and branch circuits in industrial powerdistribution systems. C-L-X power cables maybe installed in both exposed and concealedwork, wet and dry locations, direct burial in theearth, or embedded in concrete. They may beinstalled on metal racks, troughs, in cable traysor secured to supports not greater than 6 feetapart. C-L-X power cables are also approved forClasses I, II and III. Divisions 1 and 2 and ClassI, Zones 1 and 2 hazardous locations - NECArticles 501, 502, 503 and 505.Medium voltage Non-Shielded cables dischargenormally in service when spacing betweenphases is non-uniform or when phases are inclose proximity to a grounded surface.
SpecificationsConductors: Annealed uncoated coppercompact stranded per ASTM B-496.Strand Screen: Extruded semiconducting EPRstrand screen meets or exceeds electrical and
UL®
C-L-X VFD Type MV-90 or MC-HL2.4kV Okoguard Nonshielded Power Cable-Aluminum Sheath5000V CSA RA90
3 Okopact (Compact Stranded) Copper Conductors/90°C Rating®
100% & 133% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
Product DataSection 2: Sheet 21
Okoguard Insulation: 90 mils (2.29mm)
Catalo
g Num
ber (1
)
Conductor s
ize
(AW
G o
r kcm
il)
Conductor S
ize -m
m²
Approx. D
iam
eter o
ver
Insula
tion (i
n.)
Jacket Thic
kness mils
Jacket Thic
kness mm
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. N
et Weig
ht
lbs./1
000’
Approx. S
hip W
eight
lbs./1
000’
Ampaciti
es in
Cable T
ray (2
)
With Yellow Okoseal Jacket
571-21-3193571-21-3196
▲571-21-3200
8 8.46 13.34 21.2
0.360.390.44
3x123x103x10
0.77 19.60.85 21.60.97 24.6
0.971.061.19
50 1.2750 1.2750 1.27
1.08 27.41.17 29.71.30 33.0
565 630740 820960 1050
59 8579 105
105 135
▲571-21-3204571-21-3208571-21-3212
2 33.61 42.4
1/0 53.5
0.500.520.56
3x103x83x8
1.10 27.91.16 29.41.23 31.2
1.341.421.51
50 1.2750 1.2760 1.52
1.45 36.81.53 38.91.65 41.9
1270 14701520 16601835 1980
140 180160 200185 230
▲571-21-3217▲571-21-3224
571-21-3228
2/0 67.44/0 107.0
250 127.0
0.600.700.75
3x83x73x6
1.33 33.81.53 38.91.64 41.7
1.601.831.96
60 1.5260 1.5260 1.52
1.73 43.91.96 49.82.09 53.1
2160 23253075 33403470 3725
215 260285 335320 365
▲571-21-3236▲571-21-3244
571-21-3248571-21-3252
350 177.0500 253.0750 380.0
1000 507.0
0.850.961.141.29
3x63x53x43x4
1.86 47.22.10 53.32.51 63.82.90 73.7
2.192.452.933.41
60 1.5275 1.9175 1.9185 2.16
2.32 58.92.61 66.33.10 78.73.59 91.2
4705 52656405 69659220 980
12075 13155
395 440485 530615 650705 730
Gro
unding C
onductors
No. x S
ize (A
WG
/kcm
il)
Approx. C
ore O
.D. -
Inches
Approx. C
ore O
.D. -
mm
Ampaciti
es
Direct B
urial (
3)
Okonite’s web site, www.okonite.com contains the most up to date information.
▲ Available from our Customer Service Centers.Authorized stock item.
Copper or bronze and non-jacketed C-L-X is available on special order.
JacketsOptional jacket types available - consult local sales office.
Aluminum Conductors
(1) Aluminum conductors are available on special order.
AmpacitiesAmpacities are in accordance with Table 311.60(C)71 of the NEC for an(2)
insulated three conductor cable, isolated in air, with a conductor operatingtemperature of 90°C and an ambient air temperature of 40°C.
(3) Ampacities are in accordance with Table 311.60(C)83 of the NEC for aninsulated three conductor cable directly buried in the earth with a conductoroperating temperature of 90°C, ambient earth temperature of 20°C, 100% loadfactor and thermal resistance (RHO) of 90.
Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacity Tables, or theOkonite Engineering Data Bulletin for installation in duct banks, other ambienttemperatures, circuit configurations or installation requirements.
C-L-X The Okonite Company
Q/21060221
THE OKONITE COMPANYRamsey, New Jersey 07446
C-L-X
O.D
- In
ches
®
UL®
C-L-X VFD Type MV-105 or MC-HL®
5/8kV Okoguard Shielded Power Cable-Aluminum Sheath5000V CSA RA903 Okopact (Compact Stranded) Copper Conductors/105°C Rating5kV - 133% or 8kV - 100% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
A Uncoated (Compact Stranded)Copper ConductorsExtruded Semiconducting EPRBStrand Screen
C Okoguard Insulation (EPR)D Extruded Semiconducting EPR
Insulation ScreenE Phase Identification TapeF Three Copper Grounding
ConductorsG Uncoated Copper ShieldH Fillers and Binder TapeJ Impervious, continuous,
Corrugated Aluminum C-L-X SheathJacket-Yellow OkosealK
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 22
®
InsulationOkoguard Is Okonite's registered trade name forits exclusive ethylene-propylene rubber (EPR)base, thermosetting compound, whose optimumbalance of electrical and physical properties isunequaled in other solid dielectrics. Okoguardinsulation, with the distinctive red color and atotally integrated EPR system, provides theoptimum balance of electrical and physicalproperties for long, problem free service.
AssemblyType MV-105 conductors are assembled withfillers, three bare stranded grounding conductorsand a binder tape into a round core. Acontinuously corrugated welded aluminum sheath(C-L-X) encases the cable core. The C-L-Xsheath is protected with a low temperatureyellow Okoseal jacket. The impervious,
®
continuous, corrugated aluminum C-L-X sheathprovides complete protection against moisture,liquids and gases in addition to its excellentmechanical strength. In addition, the aluminumCLX sheath exceeds the equipment groundingrequirements of NEC Section 250.118 and250.122, and can be used as the equipmentgrounding conductor in non-HL areas. TheOkoseal jacket allows the cable to be directburied in the ground, embedded in concrete orareas subjected to corrosive atmospheres.
ApplicationsC-L-Xpower cables are recommended as aneconomical alternate to a wire in conduit system.They are designed specifically for use as feedersor branch circuits in industrial and utility powerdistribution systems. C-L-Xpower cables may beinstalled in both exposed and concealed work,wet and dry locations, directly buried in the earth,or embedded in concrete. They may be installedon metal racks, troughs, in cable trays or securedto supports not greater than 6 feet apart.C-L-X Type MC-HL cables are also approved forClasses I, II, and III, Division 1 and 2 and Class I,Zones 1 and 2 hazardous locations - NECArticles 501, 502, 503 and 505.
SpecificationsConductors: Uncoated copper compactstranded per ASTM B-496.Strand Screen: Extruded semiconducting EPRstrand screen meets or exceeds electrical andphysical requirements of ICEA S-93-639/NEMAWC74 and UL 1072.Insulation: Okoguard meets or exceeds theelectrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072. The insul-
lated conductors are tested in accordancewith AEIC CS8.Insulation Screen: Extruded semiconductingEPR insulation screen per ICEA S-93-639/NEMA WC74, AEIC CS8 and UL 1072.Shield: 5 mil uncoated copper tape helicallyapplied with 12.5% nominal overlap.Phase Identification: Color coded (black, red,blue) polyester ribbon laid longitudinallyunder the copper shield tape.Grounding Conductors: Three uncoatedcopper in accordance with UL 1072.Assembly: Cabled with fillers and groundwires in the interstices, binder tape overall.Sheath: Close fitting, impervious, continuous,corrugated aluminum C-L-Xper UL 1072; C-L-Xis recognized as a grounding conductorby NEC.Jacket: A low temperature, sunlight resistant,yellow PVC jacket in accordance with UL1072. Other color jackets are available.UL Listed as type MV-105 or MC-HL, sunlightresistant for use in cable tray, and for directburial in accordance with UL 1072 & 2225.CSA Listed to C68.10.
Product Features• Triple tandem extruded, all EPR system.• Complete prepackaged, color coded,factory tested wiring system.• Okoguard C-L-X cables meet or exceed allrecognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).• Passes the vertical tray flame testrequirements of IEEE 383 and 1202, UL1072, ICEA T-29-520 (210,000 BTU/hr.).• Complies with NEC Section 336.36 and issuitable for direct buried when installed inaccordance with NEC Sections 250.4(A)(5).• Complies with NEC Articles 501, 502, 503and 505 for hazardous locations.• Continuous sheath provides groundingsafety.• Excellent corona resistance.• Screens are clean stripping.• Exceptional resistance to "treeing".• Minimum installation temperature of -40°C.• Improved Temperature Rating.• Three symmetrical grounding conductorswith the CLX sheath provide a superior lowresistance return path for VFD and othermodern ac drive/motor applications.• ABS listed as CWCMC Type MC-HL.• CSA listed as FT4, SR, HL and LTGG(-40°C).
ULR
C-L-X VFD Type MV-105 or MC-HL5/8kV Okoguard Shielded Power Cable-Aluminum Sheath3 Okopact (Compact Stranded) Copper Conductors/105°C Rating100% & 133% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
Product DataSection 2: Sheet 22
Okoguard Insulation: 115 mils (2.92mm), 5kV-133% or 8kV-100% Insulation Level
Catalo
g Num
ber (1
)
Conduct
or si
ze
(AW
G o
r kc
mil)
Conduct
or Siz
e -m
m²
Appro
x. D
iam
eter
ove
r
Insu
latio
n (in.)
Jack
et T
hickn
ess
mils
Jack
et T
hickn
ess
mm
Appro
x. O
.D. -
Inch
es
Appro
x. O
.D. -
mm
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Am
paciti
es in
Cab
le T
ray
(2)
With Yellow Okoseal Jacket
* 571-22-3694571-22-3696
▲571-22-3698
8 8.46 13.34 21.2
0.400.440.48
3x123x103x10
1.04 26.41.12 28.41.21 30.7
1.291.371.51
50 1.2750 1.2760 1.52
1.40 35.61.48 37.61.65 41.9
907 10561090 12591398 1556
66 9088 115
115 150
▲571-22-3706571-22-3708571-22-3710
2 33.61 42.4
1/0 53.5
0.540.580.61
3x103x83x8
1.34 34.01.40 35.61.48 37.6
1.641.691.78
60 1.5260 1.5260 1.52
1.78 45.21.82 46.21.91 48.5
1732 18901992 21372273 3012
154 190180 215205 245
▲571-22-3717▲571-22-3725
571-22-3727
2/0 67.44/0 107.0
250 127.0
0.650.750.80
3x83x73x6
1.57 39.91.78 45.21.90 48.3
1.922.152.28
60 1.5260 1.5260 1.52
2.00 50.82.29 58.22.44 62.0
2616 41713613 39804175 4390
240 280320 360355 395
▲571-22-3838▲571-22-3846
571-22-3748571-22-3751
350 177.0500 253.0750 380.0
1000 507.0
0.891.011.191.34
3x63x53x43x3
2.10 53.32.35 57.62.73 69.33.11 79.1
2.452.753.243.67
75 1.9175 1.9185 2.1685 2.16
2.61 66.32.91 73.93.42 86.93.85 97.8
5328 54357095 7603
10134 1102113164 14794
440 475545 570685 700790 785
Gro
unding C
onductors
No. x
Siz
e (A
WG
/kcm
il)
Appro
x. C
ore O
.D. -
Inch
es
Appro
x. C
ore O
.D. -
mm
Am
paciti
es
Dire
ct B
urial (
3)
Okonite’s web site, www.okonite.com contains the most up to date information.
Q/21070222
THE OKONITE COMPANYRamsey, New Jersey 07446
C-L
-X O
.D -
Inch
es
▲ Available from our Customer Service Centers.Authorized stock item.
Copper or bronze C-L-X and non-jacketed C-L-X are available on special order.
JacketsOptional jacket types available - consult local sales office.
Aluminum Conductors
(1) Aluminum conductors are available on special order.
AmpacitiesAmpacities are in accordance with Table 311.60(C)(71) of the NEC for an(2)
insulated three conductor cable, isolated in air, with a conductor operatingtemperature of 105°C and an ambient air temperature of 40°C.
(3) Ampacities are in accordance with Table 311.60(C)(83) of the NEC for aninsulated three conductor cable directly buried in the earth with a conductoroperating temperature of 105°C, ambient earth temperature of 20°C, 100%load factor and thermal resistance (RHO) of 90.
Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacity Tables, or theOkonite Engineering Data Bulletin for installation in duct banks, other ambienttemperatures, circuit configurations or installation requirements.
C-L-X The Okonite Company®
For 8kV ampacities refer to the NEC tables referenced below in the columns listed 5001-35,000 Volts
* This cable is only rated 5kV (133%), due to UL limitations, it cannot be rated 8kV.
ULR
C-L-X Type MV-105 or MC-HL®
15kV Okoguard Shielded Power Cable-Aluminum Sheath3 Okopact (Compact Stranded) Copper Conductors/105°C Rating133% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct Burial
A Uncoated Okopact (CompactStranded) Copper ConductorsExtruded Semiconducting EPRBStrand Screen
C Okoguard Insulation (EPR)D Extruded Semiconducting EPR
Insulation ScreenE Phase Identification TapeF Copper Grounding ConductorG Uncoated Copper ShieldH Fillers and Binder TapeJ Impervious, Continuous,
Corrugated Aluminum C-L-X SheathJacket-Red Low TemperatureKOkoseal
COMPACT STRAND
CONSTRUCTION Product DataSection 2: Sheet 24
®
®C
OM
PA
CT
CU
OK
OG
UA
RD
EP
PV
C 1
5kV
sulated conductors are tested in accordancewith AEIC CS8.Insulation Screen: Extrudedsemiconducting EPR insulation screenmeets or exceeds electrical and physicalrequirements of ICEA S-93-639/NEMAWC74 and UL 1072.Shield: 5 mil uncoated copper tape helicallyapplied with 12.5% nominal overlap.Phase Identification: Color coded (black,red, blue) polyester ribbon laid longitudinallyunder the copper shield tape.Grounding Conductor: Uncoated copper inaccordance with UL 1072.Assembly: Cabled with fillers and groundwire in the interstices, binder tape overall.Sheath: Close fitting, impervious,continuous, corrugated aluminum C-L-XperUL 1072; C-L-X is recognized as agrounding conductor by NEC.Jacket: A low temperature, sunlightresistant, red PVC jacket in accordance withUL 1072. Other color jackets are available.UL Listed as type MV-105 or MC-HL,sunlight resistant, for use in cable tray, andfor direct burial in accordance with UL 1072and 2225. UL certified to IEEE 1580. CSAListed to C68.10.
Product Features• Triple tandem extruded, all EPR system.• Complete prepackaged, color coded,factory tested wiring system.• Okoguard C-L-X cables meet or exceedall recognized industry standards (UL, AEIC,NEMA/ICEA, IEEE).• Passes the vertical tray flame testrequirements of IEEE 383 and 1202, UL1072, ICEA T-29-520 (210,000 BTU/hr.)• Complies with NEC Section 336.36 and issuitable for direct buried when installed inaccordance with NEC Sections 250.4(A)(5).• Complies with NEC Articles 501, 502, 503and 505 for hazardous locations.• Continuous sheath provides groundingsafety.• Excellent corona resistance.• Screens are clean stripping.• Exceptional resistance to "treeing".• Minimum installation temperature of -40°C.• Improved Temperature Rating.• ABS listed as CWCMC Type MC-HL.• CSA listed as FT4, SR, HL and LTGG(-40°C).
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) base, thermosetting compound, whoseoptimum balance of electrical and physicalproperties is unequaled in other soliddielectrics. Okoguard insulation, with thedistinctive red color and a totally integratedEPR system, provides the optimum balanceof electrical and physical properties for long,problem free service.
AssemblyThe Type MV-105 conductors are assembledwith fillers, one bare stranded groundingconductor and a binder tape into a roundcore. A continuously corrugated weldedaluminum sheath (C-L-X) encases the cablecore. The C-L-X sheath is protected with alow temperature red Okoseal jacket. The®
impervious, continuous, corrugated aluminumC-L-X sheath provides complete protectionagainst moisture, liquids and gases inaddition to its excellent mechanical strength.In addition, the aluminum CLX sheathexceeds the equipment groundingrequirements of NEC Section 250.118 and250.122, and can be used as the equipmentgrounding conductor in non-HL areas. TheOkoseal jacket allows the cable to be directburied in the ground, embedded in concreteor areas subjected to corrosive atmospheres.
ApplicationsC-L-X power cables are recommended as aneconomical alternate to a wire in conduitsystem. They are designed specifically foruse as feeders or branch circuits in industrialand utility power distribution systems. C-L-Xpower cables may be installed in bothexposed and concealed work, wet and drylocations, direct burial in the earth, orembedded in concrete. They may be installedon metal racks, troughs, in cable trays orsecured to supports not greater than 6 feetapart.C-L-X Type MC-HL cables are also approvedfor Classes , , and , Divisions 1 and 2I II III
and Class Zones 1 and 2 hazardousI ,
locations - NEC Articles 501, 502, 503 and505.
SpecificationsConductors: Uncoated copper compactstranded per ASTM B-496.Strand Screen: Extruded semiconductingEPR strand screen meets or exceedselectrical and physical requirements of ICEAS-93-639/NEMA WC74 and UL 1072.Insulation: Okoguard meets or exceeds theelectrical and physical requirements of ICEAS-93-639/NEMA WC74 and UL 1072. The in-
UL®
C-L-X Type MV-105 or MC-HL15kV Okoguard Shielded Power Cable-Aluminum Sheath3 Okopact (Compact Stranded) Copper Conductors/105°C Rating133% Insulation LevelFor Cable Tray Use-Sunlight Resistant-For Direct BurialOkoguard Insulation: 220 mils (5.59mm)
Product DataSection 2: Sheet 24
Catalo
g Num
ber (1
)
Conductor s
ize
(AW
G o
r kcm
il)
Conductor S
ize -m
m²
Approx. D
iam
eter o
ver
Insula
tion (i
n.)
Jacket Thic
kness (m
ils)
Jacket Thic
kness mm
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. N
et Weig
ht
lbs./1
000’
Approx. S
hip W
eight
lbs./1
000’
Ampaciti
es in
Cable T
ray (2
)
With Red Okoseal Jacket
▲571-23-3504571-23-3508571-23-3512
2 33.61 42.4
1/0 53.5
0.760.790.83
644
1.79 45.51.86 47.31.94 49.3
2.152.232.32
60 1.5260 1.5275 1.91
2.28 57.92.36 60.02.48 63.0
2420 31472706 34043076 3674
185 200210 225240 255
▲571-23-3516▲571-23-3524
571-23-3528
2/0 67.44/0 107.0
250 127.0
0.870.971.03
432
2.03 51.62.24 57.02.36 60.0
2.412.632.76
75 1.9175 1.9175 1.91
2.57 65.32.79 70.92.92 74.2
3434 42194460 53855078 5845
275 290360 345400 410
▲571-23-3536▲571-23-3544▲571-23-3548
350 177.0500 253.0750 380.0
1.121.241.41
21
1/0
2.56 65.02.81 71.43.19 81.0
2.983.283.76
75 1.9175 1.9185 2.16
3.14 79.83.46 89.23.94 100.0
6264 73058221 9653
11317 13087
490 495600 590745 720
Gro
unding C
onductor
Size (A
WG
/kcm
il)
Approx. C
ore O
.D. -
Inches
Approx. C
ore O
.D. -
mm
Ampaciti
es
Direct B
urial (
3)
Okonite’s web site, www.okonite.com contains the most up to date information.
R/21060224
THE OKONITE COMPANYRamsey, New Jersey 07446
C-L-X
O.D
- In
ches
▲ Available from our Customer Service Centers.Authorized stock item.
JacketsOptional jacket types available - consult local sales office.
Copper or bronze C-L-X and non-jacketed C-L-X are available on special order.
Aluminum Conductors
(1) Aluminum conductors are available on special order.
Ampacities
(2) Ampacities are in accordance with Table 311.60(C)(71) of the NEC for aninsulated three conductor cable, isolated in air, with a conductor operatingtemperature of 105°C and an ambient air temperature of 40°C.
(3) Ampacities are in accordance with Table 311.60(C)(83) of the NEC for an
insulated three conductor cable directly buried in the earth with a conductor
operating temperature of 105°C, ambient earth temperature of 20°C, 100%
load factor, thermal resistance (RHO) of 90.
Refer to the NEC, IEEE 835 Power Cable Ampacity Tables, or theOkonite Engineering Data Bulletin for installation in duct banks, other ambienttemperatures, circuit configurations or installation requirements.
C-L-X The Okonite Company®
UL®
Solid Type PILC15kV Paper Insulated Lead Covered Power CableThree Copper Conductors/90°C Rating100% Insulation Level
A Conductor-StrandedCompact Sector, Pre-twisted
B Strand Screen-CarbonBlack Paper Tapes
C Insulation-ImpregnatedPaper Tapes
D Insulation Screen-CarbonBlack Paper Tape
E Shield Copper TapeF Fillers-Impregnated
PaperG Binder Copper TapeH Sheath-Copper Bearing LeadJ Jacket
Product DataSection 2: Sheet 31
ConductorOkonite's multiconductor PILC cables are available
with three different style conductors depending on
the application. The three conductor styles are
compressed round, compact round and compact
(120°) sector.
InsulationOkonite's impregnated paper insulation consists of
the finest electrical grade paper made from the
highest quality coniferous wood pulp and the
purest polybutene dielectric fluid. The paper is
manufactured to meet Okonite specifications to
produce the necessary mechanical and physical
properties to resist tearing and wrinkling during
manufacture and subsequent handling during field
operations; and in addition to assure properties of
low dielectric loss with high dielectric strength. To
maintain a smooth, wrinkle-free precisely gapped
tape insulation, Okonite carefully slits it own paper
tapes into widths tailored for each conductor size
and wall thickness. Most importantly, Okonite has
the most precise tape tensions available.
The impregnating fluid used is a medium viscosity
polybutene type with an optional high viscosity
fluid for warm installations, risers installations or
installations with severe elevation changes.
Polybutene fluids are superior in that they resist
aging, have lower and more stable power factor
values and possess an inherent tackiness which
resists draining. Okonite treats the dielectric fluid
with clay-filtering and then de-gases it prior to
impregnating the cable to provide the lowest power
factor and ionization levels.
Sheath & JacketOkonite's copper bearing lead sheath provides an
impervious barrier from the environment; in
addition, it provides mechanical protection for the
insulation and encapsulation of the impregnant. All
lead sheaths have the inherent capacity for
substantial electrical conductivity, even under short
circuit conditions without requiring a separate
ground. Okonite's lead sheaths are applied with a
continuous lead extruder under the control of a
thickness gauge for uniform wall thickness and
concentricity of extrusion.
The Okolene jacket provides mechanical and
corrosion protection for the lead sheath and is
used in most installations. (Indoor and aerial
installations may not require a jacket). Okolene is a
thermoplastic polyethylene material that resists
most chemicals and moisture; it is unaffected by
oils below 60°C and has a low coefficient of friction
which aids pulling through ducts and conduits.
ApplicationsOkonite Paper Insulated Lead Covered 3/C cable
is recommended for use in underground ducts,
direct buried, and aerially when lashed to a
messenger.
PILC cables are used in any circuit that requires
the highest reliability, the longest uninterrupted
service life, and where the greatest surge,
impulse and AC dielectric strength is desired. An
added advantage is that a 3/C PILC cable permits
the largest amount of power to be transmitted in
the smallest diameter space because of its unique
triangle shaped and nested design.
Although not shown as an insulation above 600
Volts in the National Electrical Code, it is readily
approved for use by local inspectors because of
its extensive safe use by utilities. Therefore, PlLC
cables can be used in industrial or commercial
applications with prior notification and approval by
the local inspector.
Also available in other voltage ratings.
SpecificationsOkonite PILC cables are available in accordance
with AEIC CS1-90 or AEIC CS1-12.
° Cables made per AEIC CS1-90 have
traditional nominal wall thicknesses
for the lead sheath and overall
jacket.
° Cables made per AEIC CS1-12 have
"minimum point" wall thicknesses for
the lead sheath and overall jacket.
Specifications• Copper conductors available as:
° Concentric Round
° Compact Round
° Compact Sector (Pre-twisted)
• 90°C continuous operation.
• 110°C emergency rating.
• 200°C short circuit rating.
• Polybutene impregnating fluid.
• Type H (shielded) cable.
• High impulse strength.
• Proven service life of over 80 years.
• Impervious to environment.
• Copper bearing lead sheath.
Options• Available in other voltage ranges from 0.6
though 69 kV.
• Available with 133 and 173% insulation levels.
• Available as 3 and 4 conductor cables.
• Available with high viscosity dielectric fluid for
risers and installations with severe elevation
differences.
• Available with a reinforced lead sheath (ROC-
Reinforced Okonite Covering).
• Available with LS/ZH Okoclear TP (TPPO) and
Okoseal (PVC) jackets.
• Belted PILC cables are also available.
Solid Type PILC15kV Paper Insulated Lead Covered Power CableThree Copper Conductor/90°C Rating100% Insulation Level
AEIC CS1-90 11th Edition(A)
Product DataSection 2: Sheet 31
THE OKONITE COMPANYRamsey, New Jersey 07446
A-Lead sheath and jacket thicknesses per AEIC CS1-90 version using traditional nominal thicknesses.
AEIC CS1-12 12th Edition(B)
Authorized Stock Item. Stock items use
high viscosity polybutene impregnating fluid.
Available from our Customer Service Centers.
(1) Ampacity for one circuit, one conduit in
ductbank, 90°C conductor temperature, 90
RHO soil 20°C earth temperature, 100% Load
Factor, multi point grounded sheaths. Per Okonite Bulletin 205,
page 53.
(2) Ampacity for one circuit, one conduit in
ductbank, 90°C conductor temperature, 90
RHO soil 20°C earth temperature, 75% Load
Factor, multi point grounded sheaths. Per Okonite Bulletin 205,
page 53.
B- Lead sheath and jacket thicknesses per AEIC CS1-12 version using minimum point thicknesses.
Catalo
gNum
ber
Conduct
or size
AWG
/kcm
il
Conduct
or Size
-mm
²
Insu
latio
nThic
knes
s
Nom
inal
-mils
Cab
leDia
met
er-in
ches
Am
paciti
es D
uct (1
)
(100
%LF)
Am
paciti
esin
Duct
(2)
(75%
LF)
Lead
Thickn
ess
Nom
inal
-mils
Jack
et T
hickn
ess
Nom
inal
-mils
New
Wei
ght - Ib
s./ft
.
Concentric Round
101-63-4120101-63-4175
2 33.61 42.4
180165
9090
9090
1.921.94
4.344.53
146 154167 176
Compact Round
101-63-4243 1/0 53.5 165 90 90 1.97 4.83 191 202
Compact Sector
101-63-4277101-63-4335101-63-4373101-63-4436
▲101-63-4544▲101-63-4665
101-63-4904
2/0 67.43/0 85.04/0 107.0250 127.0350 177.0500 253.0750 380.0
165165165165165165165
9090909090
110110
9090909090
110110
1.922.002.122.192.372.642.94
4.805.326.136.678.19
10.3713.71
215 228245 260280 297307 327371 397450 483555 599
Catalo
g Num
ber
Conduct
or siz
e
AWG
/kcm
il
Conduct
or Siz
e -m
m²
Insu
latio
n Thic
knes
s
Nom
inal
-mils
Cab
le D
iam
eter
-inch
es
Am
paciti
es D
uct (1
)
(100
% L
F)
Am
paciti
es in
Duct
(2)
(75%
LF)
Lead T
hickn
ess
Nom
inal
-mils
Jack
et T
hickn
ess
Nom
inal
-mils
New
Wei
ght - Ib
s./ft
.
Concentric Round
101-61-4120101-61-4175
2 33.61 42.4
180165
8585
7070
1.931.95
4.464.65
146 154167 176
Compact Round
101-61-4243 1/0 53.5 165 85 70 1.98 4.96 191 202
Compact Sector
101-61-4277101-61-4335101-61-4373101-61-4436101-61-4544101-61-4665101-61-4904101-61-4986
2/0 67.43/0 85.04/0 107.0250 127.0350 177.0500 253.0750 380.0
1000 507.0
165165165165165165165165
8585858585
100100100
70707070708585
100
1.932.022.122.202.372.652.953.29
4.925.456.116.658.00
10.6113.7316.95
215 228245 260280 297307 327371 397450 483555 599636 689
G/21060231
Okoguard URO-J®
15kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating100% and 133% Insulation Levels
A Conductor-Stranded AluminumStrand Screen-BExtruded Semiconducting EPR
C Insulation-Okoguard-EPRD Insulation Screen-
Extruded Semiconducting EPRE Concentric Conductor-Bare
Copper WiresEncapsulating Jacket-OkoleneFwith 3 extruded red ID stripesand NESC lightning bolt
Product DataSection 2: Sheet 35
1/0
AW
G O
KO
GU
AR
D E
PR
100%
IN
SU
L
� ◄
InsulationOkoguard is Okonite's registered tradename for its exclusive ethylene-propylenerubber (EPR) based, thermosettingcompound, whose optimum balance ofelectrical and physical properties isunequaled in other solid dielectrics.Okoguard insulation, with the distinctive redcolor and a totally integrated EPR system,provides the optimum balance of electricaland physical properties for long, problemfree service.The triple tandem extrusion of the screenswith the insulation provides optimumelectrical characteristics.An insulation screen of ethylene-propylenerubber is extruded over the insulation. Thebare copper concentric wires are uniformlyspaced around the insulation screen. Theoverall polyethylene jacket providesprotection against mechanical damage andcorrosion.Product identification is provided throughthe use of three red stripes placed 120°apart in the black jacket with an NESClightning bolt.
ApplicationsOkoguard URO-J cables provide maximumcircuit longevity in underground residentialdistribution systems. They can be burieddirectly or installed in underground ducts orconduits.
SpecificationsCentral Conductor: Aluminum per ASTMB-609, Class B stranded per B-231.Conductor Screen: Extrudedsemiconducting ethylene-propylene rubbermeets or exceeds the requirements of ICEAS-94-649, AEIC CS8, and CSA C68.5.Insulation: Extruded Okoguard meets orexceeds the requirements of ICEA S-94-649, AEIC CS8, and CSA C68.5.Insulation Screen: Extrudedsemiconducting ethylene-propylene rubbermeets or exceeds the requirements of ICEAS-94-649, AEIC CS8, and C68.5.Concentric Conductor: Bare copper wires.
Jacket: Black Okolene with redextruded stripes meets or exceeds therequirements of ICEA S-94-649, AEICCS8, and CSA C68.5 for polyethylenejackets.
Product Features• Triple tandem extruded, all EPRsystem• Okoguard cables meet or exceedICEA standards.• Meets RUS 1728.204 for cables withfilled strand or solid conductor and133% insulation level.• 105°C continuous operatingtemperature.
140°C emergency rating.•250°C short circuit rating.•
• Excellent corona resistance.• Low dielectric constant and powerfactor.• Screens are clean stripping.• Exceptional resistance to "treeing".• Moisture resistant.• Overall jacket provides extended life.• Red extruded stripes.• Excellent resistance to mostchemicals.• Can be listed by UL as Type MV-90on Special Orders.• CSA C68.5 listed, LTGG (-40 C), SR.�
• Design Options:Additional conductor sizesFilled strandCopper central conductorCopper flat strap concentric neutralProduct identification via coloredjackets.Semiconducting jacket
• Improved Temperature Rating.Okoguard insulation system has beentested and qualified for operation at105°C continuous and 140°Cemergency operating temperature.• Minimum installation temperature of-40°C.
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard URO-J15kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating100% Insulation Level
Okoguard Insulation: 175 mils 100% Insulation Level
Product DataSection 2: Sheet 35
Catalo
gNum
ber
Conduct
or si
ze
(AW
G o
r kc
mil)
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
THE OKONITE COMPANYRamsey, New Jersey 07446
Nom
inal
Dia
. ove
r Insu
latio
n (in.)
Nom
inal
Dia
. ove
r Insu
latio
n
Scree
n (in.)
Copper
Neu
tral
, No. x
AWG
(1)
Nom
inal
O.D
. (in
.)
90C
Am
pacity
Dire
ct B
urial (
2)
°90
CAm
pacity
Duct
(2)
°10
5C
Am
pacity
Dire
ct B
urial (
2)
°10
5C
Am
pacity
Duct
(2)
°
(1) Individual wire size and count may vary. The resulting combination meets the 1/3 or full neutral,size requirement.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEA P-117-734for 90°C or 105°C conductor temperature, 25°C ambient temperature,100% load factor, and earth thermal resistivity of RHO 90.One third neutral ampacities are based on triplexed or triangularconfiguration for the same conditions stated above.
Insu
latio
n Scr
een
Thickn
ess
(mils
)
FULL NEUTRAL
161-23-2057161-23-2060161-23-2066161-23-2069
2(1X)2(7X)
1(19X)1/0(1X)
0.66 30 0.730.67 30 0.750.72 30 0.790.72 30 0.80
10X1410X1413X1416X14
0.970.981.031.03
499 603512 568587 698642 747
170 125170 125195 145220 160
185 135185 135210 155235 175
161-23-2072161-23-2075161-23-2078
1/0(19X)2/0(19X)3/0(19X)
0.75 30 0.830.80 30 0.870.85 30 0.92
16X1414X1216X12
1.061.141.19
662 725791 910
908 1029
220 160250 185285 210
235 175270 205310 230
161-23-2081161-23-2084161-23-2090
4/0(19X)250(37X)350(37X)
0.90 30 0.980.97 30 1.041.07 40 1.17
14X1016X10
18X.1078
1.291.361.50
1129 12381268 14181598 1793
320 240350 270425 310
350 260380 295460 340
1/3 NEUTRAL
160-23-2057160-23-2060160-23-2066160-23-2069
2(1X)2(7X)
1(19X)1/0(1X)
0.66 30 0.730.67 30 0.750.72 30 0.790.72 30 0.80
6X146X146X146X14
0.970.981.031.03
452 528465 579505 617525 663
150 120150 120175 140195 155
165 135165 135185 150215 170
160-23-2072160-23-2075160-23-2078160-23-2081
1/0(19X)2/0(19X)3/0(19X)4/0(19X)
0.74 30 0.830.80 30 0.870.85 30 0.920.90 30 0.98
6X147X149X1411X14
1.061.111.161.21
545 662611 726695 889792 922
195 155225 180255 200285 235
215 170240 195275 220310 255
160-23-2084160-23-2090160-23-2093
250(37X)350(37X)500(37X)
0.97 30 1.041.07 40 1.171.20 40 1.30
13X1418X1416X12
1.281.411.57
892 10181135 13151470 1691
305 250375 310450 370
330 275405 335490 405
160-23-2096160-23-2099
750(61X)1000(61X)
1.39 40 1.491.54 40 1.64
16X.096618X.1052
1.862.03
2062 24022580 2877
545 460620 520
595 505675 570
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard URO-J15kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating133% Insulation Levels
Okoguard Insulation: 220 mils 133% Insulation Level
Product DataSection 2: Sheet 35
O/20110235
THE OKONITE COMPANYRamsey, New Jersey 07446
▲Authorized stock item. Available from our Customer ServiceCenters.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEAP-117-734 for 90°C or 105°C conductor temperature, 25°C ambienttemperature, 100% load factor, and earth thermal resistivity of RHO90.One third neutral ampacities are based on triplexed or triangularconfiguration for the same conditions stated above.
Catalo
gNum
ber
Conduct
or si
ze
(AW
G o
r kc
mil)
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Nom
inal
Dia
. ove
r Insu
latio
n (in.)
Nom
inal
Dia
. ove
r Insu
latio
n
Scree
n (in.)
Copper
Neu
tral
, No. x
AWG
(1)
Nom
inal
O.D
. (in
.)
90C
Am
pacity
Dire
ct B
urial (
2)
°90
CAm
pacity
Duct
(2)
°10
5C
Am
pacity
Dire
ct B
urial (
2)
°10
5C
Am
pacity
Duct
(2)
°In
sula
tion S
cree
n
Thickn
ess
(mils
)
FULL NEUTRAL
▲161-23-3057161-23-3060161-23-3066
▲161-23-3069
2(1X)2(7X)
1(19X)1/0(1X)
0.74 30 0.820.77 30 0.840.81 30 0.880.80 30 0.89
10X1410X1413X1416X14
1.061.081.121.12
572 635590 662669 781721 792
170 125170 125195 145220 160
185 135185 135210 155235 175
▲161-23-9525161-23-3072161-23-3075161-23-3078
1/0(1X)1/0(19X)2/0(19X)3/0(19X)
0.80 30 0.890.84 30 0.920.89 30 0.920.94 30 1.01
10X14*16X1414X1216X12
1.121.151.231.28
651 718746 818900 1012998 1136
230 170220 160250 185285 210
245 185235 175270 205310 230
161-23-3081161-23-3084161-23-3090
4/0(19X)250(37X)350(37X)
0.98 30 1.061.06 40 1.161.16 40 1.26
14X1016X10
18X.1078
1.381.471.59
1226 13571405 16191716 1912
320 240350 270425 310
350 260380 295460 340
1/3 NEUTRAL
160-23-3057160-23-3060160-23-3066160-23-3069
2(1X)2(7X)
1(19X)1/0(1X)
0.74 30 0.820.76 30 0.840.81 30 0.880.80 30 0.89
6X146X146X146X14
1.061.081.121.12
525 621543 659586 700604 715
150 120150 120175 140195 155
165 135165 135185 150215 170
160-23-3072160-23-3075160-23-3078160-23-3081
1/0(19X)2/0(19X)3/0(19X)4/0(19X)
0.84 30 0.920.89 30 0.960.94 30 1.010.99 30 1.06
6X147X149X1411X14
1.151.201.251.30
629 748699 826787 916884 1002
195 155225 180255 200285 235
215 170240 195275 220310 255
160-23-3084160-23-3090160-23-3093
250(37X)350(37X)500(37X)
1.06 40 1.161.16 40 1.261.29 40 1.39
13X1418X1416X12
1.401.501.72
1024 11681243 14581650 1959
305 250375 310450 370
330 275405 335490 405
160-23-3096160-23-3099
**▲160-23-9590
750(61X)1000(61X)1100(61X)
1.47 40 1.581.64 55 1.771.61 55 1.74
16X.096618X.105218X12**
1.952.162.01
2201 25182802 32232470 2833
545 460620 520675 575
595 505675 570730 620
* - Special design 64% neutral** - Special design 1/6 neutral, compact conductor(1) Individual wire size and count may vary. The resulting combination meets the 1/3 or full neutral,size requirement.
Okoguard URO-J®
15kV Underground Primary Distribution Cable-JacketedRed Identification StripesFilled Strand Aluminum Conductor/105°C Rating100% and 133% Insulation Levels
A Conductor-Stranded Aluminumwith Filled StrandStrand Screen - ExtrudedBSemiconducting EPR
C Insulation-Okoguard EPRD Insulation Screen - Extruded
Semiconducting EPRE Concentric Conductor-Bare
Copper WiresEncapsulating Jacket-OkoleneFwith Extruded ID Stripes & NESClightning bolt
Product DataSection 2: Sheet 36
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound, whoseoptimum balance of electrical and physicalproperties is unequaled in other soliddielectrics. Okoguard insulation, with thedistinctive red color and a totally integratedEPR system, provides the optimum balance ofelectrical and physical properties for long,problem free service.
The triple tandem extrusion of the screens withthe insulation provides optimum electricalcharacteristics.
The compressed conductors are filled with awater swellable agent. This construction slowsthe migration of water through the strands inthe event of a mechanical dig-in followed byexternal exposure to water.
An insulation screen of ethylene-propylenerubber is extruded over the insulation. Thecopper concentric wires are uniformly spacedaround the insulation screen. The overallpolyethylene jacket provides protection againstmechanical damage and corrosion.
Product identification is provided through theuse of three red stripes placed 120° apart in theblack jacket, with an NESC lightning bolt.
ApplicationsOkoguard URO-J cables provide maximumcircuit longevity in underground residentialdistribution systems. They can be burieddirectly or installed in underground ducts orconduits.
SpecificationsCentral Conductor: Aluminum per ASTM
B-609, Class B stranded per B-231.
Filled Strand: Water swellable agent meets orexceeds ICEA T-31-610 water penetrationresistance and ANSI/NEMA class Aconnectorability requirements.
Conductor Screen: Extruded semiconuctingethylene-propylene rubber meets or exceedsthe requirements of ICEA S-94-649, AEIC CS8,and CSA C68.5.
Insulation: Extruded Okoguard meets orexceeds the requirements of ICEA S-94-649,AEIC CS8, and C68.5.
Insulation Screen: Extruded semiconductingethylene-propylene rubber meets or exceedsthe requirements of ICEA S-94-649, AEIC CS8,and CSA C68.5.
Concentric Conductor: Bare copper wires.
Jacket: Black Okolene with red extrudedstripes meets or exceeds the requirementsof ICEA S-94-649, AEIC CS8, and CSAC68.5 for polyethylene jackets.
Product Features• Triple tandem extruded, all EPR system.
• Okoguard cables meet or exceed ICEA
standards.
• Meets RUS 1728.204 for cables with filledstrand or solid conductor and 133%insulation level.
• 105°C continuous operating temperature.140°C emergency rating.•250°C short circuit rating.•
• Excellent corona resistance.
• Low dielectric constant and power factor.
• Screens are clean stripping.
• Exceptional resistance to "treeing".
• Filled strand conductor.
• Moisture resistant.• Overall jacket provides extended life.
• Excellent resistance to most chemicals.
• Can be listed by UL as Type MV-90 onSpecial Orders.
• CSA C68.5 listed, LTGG (-40°C), SR.
• Design Options:
Additional conductor sizes
Copper central conductor
Copper flat strap concentric neutral
Product identification via colored jackets.
Semiconducting jackets.
• Improved Temperature Rating.
Okoguard insulation system has beentested and qualified for operation at 105°Ccontinuous and 140°C emergency operatingtemperature.
• Minimum installation temperature of
-40°C.1/0
AW
G O
KO
GU
AR
D E
PR
100%
IN
SU
L
� ◄
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard URO-J15kV Underground Primary Distribution Cable-JacketedRed Identification StripesFilled Strand Aluminum Conductor/105°C Rating100% Insulation Level
Okoguard Insulation: 175 mils 100% Insulation Level
Product DataSection 2: Sheet 36
THE OKONITE COMPANYRamsey, New Jersey 07446
(1) Individual wire size and count may vary. The resulting combination meets the 1/3 or full neutral,size requirement.
▲ . Available from our Customer ServiceAuthorized stock itemCenters.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEAP-117-734 for 90°C or 105°C conductor temperature, 25°Cambient temperature, 100% load factor, and earth thermal resistivityof RHO 90.One third neutral ampacities are based on triplexed or triangularconfiguration for the same conditions stated above.
Catalo
gNum
ber
Conduct
or si
ze
(AW
G o
r kc
mil)
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Nom
inal
Dia
. ove
r Insu
latio
n (in.)
Nom
inal
Dia
. ove
r Insu
latio
n
Scree
n (in.)
Copper
Neu
tral
, No. x
AWG
(1)
Nom
inal
O.D
. (in
.)
90C
Am
pacity
Dire
ct B
urial (
2)
°90
CAm
pacity
Duct
(2)
°10
5C
Am
pacity
Dire
ct B
urial (
2)
°10
5C
Am
pacity
Duct
(2)
°In
sula
tion S
cree
n
Thickn
ess
(mils
)
FULL NEUTRAL
▲163-23-2060163-23-2066
▲163-23-2072163-23-2075
2(7X)1(19X)
1/0(19X)2/0(19X)
0.68 30 0.750.72 30 0.790.76 30 0.830.80 30 0.87
10X1413X1416X1414X12
0.991.031.071.14
517 626588 698667 778793 910
170 125195 145220 160250 185
185 135210 155235 175270 205
163-23-2078163-23-2081163-23-2084163-23-2090
3/0(19X)4/0(19X)
250(37X)350(37X)
0.85 30 0.920.90 30 0.980.97 30 1.041.07 40 1.17
16X1214X1016X10
18X.1078
1.191.291.351.50
910 10291131 12381270 14181603 1793
285 210320 240350 270425 310
310 230350 260380 295460 340
1/3 NEUTRAL
162-23-2060162-23-2066162-23-2072
2(7X)1(19X)
1/0(19X)
0.69 30 0.760.72 30 0.790.76 30 0.83
6X146X146X14
1.001.031.07
475 579506 617550 662
150 120175 140195 155
165 135185 150215 170
162-23-2075162-23-2078162-23-2081162-23-2084
2/0(19X)3/0(19X)4/0(19X)
250(37X)
0.80 30 0.870.85 30 0.920.90 30 0.980.97 30 1.04
7X149X1411X1413X14
1.111.161.211.28
612 726697 889794 922895 1018
225 180255 200285 235305 250
240 195275 220310 255330 275
162-23-2090162-23-2093162-23-2096162-23-2099
350(37X)500(37X)750(37X)
1000(61X)
1.07 40 1.171.20 40 1.301.39 40 1.491.54 40 1.68
18X1416X12
16X.096618X.1052
1.411.571.862.06
1138 13151476 16912066 24022645 3059
375 310450 370545 460620 520
405 335490 405595 505675 570
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard URO-J15kV Underground Primary Distribution Cable-JacketedRed Identification StripesFilled Strand Aluminum Conductor/105°C Rating133% Insulation Levels
Okoguard Insulation: 220 mils 133% Insulation Level
Product DataSection 2: Sheet 36
P/21010236
THE OKONITE COMPANYRamsey, New Jersey 07446
(1) Individual wire size and count may vary. The resulting combination meets the 1/3 or full neutral, size requirement.
▲ - Available from Customer ServiceAuthorized Stock Itemcenters.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEA P-117-734 for 90°C or 105°C conductor temperature, 25°Cambient temperature, 100% load factor, and earth thermalresistivity of RHO 90.One third neutral ampacities are based on triplexed ortriangular configuration for the same conditions stated above.
Catalo
gNum
ber
Conduct
or si
ze
(AW
G o
r kc
mil)
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Nom
inal
Dia
. ove
r Insu
latio
n (in.)
Nom
inal
Dia
. ove
r Insu
latio
n
Scree
n (in.)
Copper
Neu
tral
, No. x
AWG
(1)
Nom
inal
O.D
. (in
.)
90C
Am
pacity
Dire
ct B
urial (
2)
°90
CAm
pacity
Duct
(2)
°10
5C
Am
pacity
Dire
ct B
urial (
2)
°10
5C
Am
pacity
Duct
(2)
°In
sula
tion S
cree
n
Thickn
ess
(mils
)
FULL NEUTRAL
▲163-23-3060163-23-3066
▲163-23-3072163-23-3075
2(7X)1(19X)
1/0(19X)2/0(19X)
0.77 30 0.840.81 30 0.880.84 30 0.920.89 30 0.96
10X1413X1416X1414X12
1.081.121.151.23
591 669670 766748 820902 996
170 125195 145220 160250 185
185 135210 155235 175270 205
163-23-3078163-23-3081163-23-3084163-23-3090
3/0(19X)4/0(19X)
250(37X)350(37X)
0.94 30 1.010.98 30 1.061.06 40 1.161.16 40 1.26
16X1214X1016X10
18X.1078
1.281.381.471.59
1004 11251228 13471410 16061721 1912
285 210320 240350 270425 310
310 230350 260380 295460 340
1/3 NEUTRAL
162-23-3060162-23-3066162-23-3072162-23-3075
2(7X)1(19X)
1/0(19X)2/0(19X)
0.77 30 0.840.81 30 0.880.84 30 0.920.89 30 0.96
6X146X146X147X14
1.081.121.151.20
544 627588 684631 733701 810
150 120175 140195 155225 180
165 135185 150215 170240 195
162-23-3078▲162-23-3081
162-23-3084▲162-23-3090
3/0(19X)4/0(19X)
250(37X)350(37X)
0.94 30 1.010.98 30 1.061.06 40 1.161.16 40 1.26
9X1411X1413X1418X14
1.251.301.401.50
789 905887 1005
1029 11641246 1425
255 200285 235305 250375 310
275 220310 255330 275405 335
▲162-23-3093▲162-23-3096▲162-23-3099
500(37X)750(61X)
1000(37X)
1.29 40 1.391.47 40 1.581.64 55 1.77
16X1216X.096618X.1052
1.721.952.16
1653 18532209 24682807 3093
450 370545 460620 520
490 405595 505675 570
Okoguard URO-J®
25kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating100% and 133% Insulation Levels
A Conductor-Stranded AluminumStrand Screen - ExtrudedBSemiconducting EPR
C Insulation-Okoguard EPRD Insulation Screen - Extruded
Semiconducting EPRE Concentric Conductor-Bare
Copper WiresEncapsulating Jacket-OkoleneFwith three extruded red ID Stripes, andNESC lightning bolt
Product DataSection 2: Sheet 39
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in other soliddielectrics. Okoguard insulation, with thedistinctive red color and a totally integratedEPR system, provides the optimum balance ofelectrical and physical properties for long,problem free service.
The triple tandem extrusion of the screens withthe insulation provides optimum electricalcharacteristics.
An insulation screen of ethylene-propylenerubber is extruded over the insulation. Thebare copper concentric wires are uniformlyspaced around the insulation screen. Theoverall polyethylene jacket provides protectionagainst mechanical damage and corrosion.
Product identification is provided through theuse of three red stripes placed 120° apart inthe black jacket with an NESC lightning bolt.
ApplicationsOkoguard URO-J cables provide maximumcircuit longevity in underground residentialdistribution systems. They can be burieddirectly or installed in underground ducts orconduits.
SpecificationsCentral Conductor: Aluminum per ASTM B-609, Class B stranded per B-231.
Conductor Screen: Extruded semiconductingethylene-propylene rubber meets or exceedsthe requirements of ICEA S-94-649, AEICCS8, and CSA C68.5.
Insulation: Extruded Okoguard meets orexceeds the requirements of ICEA S-94-649,AEIC CS8, and CSA C68.5.
Insulation Screen: Extruded semiconductingethylene-propylene rubber meets or exceedsthe requirements of ICEA S-94-649, AEICCS8, and CSA C68.5.
Concentric Conductor: Bare copper wires.
Jacket: Black Okolene with red extrudedstripes meets or exceeds the requirements ofICEA S-94-649, AEIC CS8, and CSA C68.5 forpolyethylene jackets.
Product Features• Triple tandem extruded, all EPR system.
• Okoguard cables meet or exceed ICEAstandards.
• Meets RUS 1728.204 for cables withfilled strand or solid conductor and 100%insulation level.
• 105°C continuous operating temperature.140°C emergency rating.•250°C short circuit rating.•
• Excellent corona resistance.
• Low dielectric constant and powerfactor.
• Screens are clean stripping.
• Exceptional resistance to "treeing".
• Moisture resistant.
• Overall jacket provides extended life.
• Red extruded stripes.
• Excellent resistance to most chemicals.
• Can be listed by UL as Type MV-90 onSpecial Orders.
• CSAC68.5 listed, LTGG (-40°C), SR.
• Design Options:
Additional conductor sizes
Filled strand
Copper central conductor
Copper flat strap concentric neutral
Product identification via colored jackets
Semiconducting jackets
• Improved Temperature Rating.
Okoguard insulation system has beentested and qualified for operation at 105°Ccontinuous and 140°C emergencyoperating temperature.
• Minimum installation temperature of
-40°C.
1/0
AW
G O
KO
GU
AR
D E
PR
100%
IN
SU
L
� ◄
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard URO-J25kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating100% Insulation Levels
Okoguard Insulation: 260 mils 100% Insulation Level
Product DataSection 2: Sheet 39
* These items include filled strand
(1) Individual wire size and count may vary. The resulting combination meets the 1/3 or full neutral, size requirement.
▲ - Available from Customer ServiceAuthorized Stock ItemCenters.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEA P-117-734for 90°C or 105°C conductor temperature, 25°C ambient temperature,100% load factor, and earth thermal resistivity of RHO 90.One third neutral ampacities are based on triplexed or triangularconfiguration for the same conditions stated above.
Catalo
gNum
ber
Conduct
or size
(AW
Gor kc
mil)
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Nom
inal
Dia
. ove
r Insu
latio
n (in.)
Nom
inal
Dia
. ove
r
Insu
latio
n Scr
een (i
n.)
Copper
Neu
tral
No. x
AWG
(1)
Nom
inal
O.D
. (in
.)
90C
Am
pacity
Dire
ct B
urial (
2)
°90
CAm
pacity
Duct
(2)
°In
sula
tion S
cree
n
Thickn
ess
(mils
)
FULL NEUTRAL
161-23-4066▲161-23-4069
161-23-4072▲163-23-4072*
161-23-4075
1(19X)1/0(1X)
1/0(19X)1/0(19X)2/0(19X)
0.89 30 0.960.89 30 0.970.93 30 1.000.92 30 1.000.97 30 1.05
13X1416X1416X1416X1414X12
1.201.201.241.231.32
747 872798 870832 898827 899986 1117
195 145220 160220 160220 160250 185
210 155235 175235 175235 175270 205
161-23-4078161-23-4081161-23-4084161-23-4090
3/0(19X)4/0(19X)
250(37X)350(37X)
1.02 30 1.011.08 40 1.181.14 40 1.241.25 40 1.35
16X1214X1016X10
18X.1078
1.371.491.551.74
1092 12101357 15501507 17241887 2166
285 210320 240350 270425 310
310 230350 260380 295460 340
1/3 NEUTRAL
160-23-4066160-23-4072160-23-4075160-23-4078
1(19X)1/0(19X)2/0(19X)3/0(19X)
0.88 30 0.960.93 30 1.000.97 30 1.051.02 30 1.01
6X146X147X149X14
1.191.241.281.33
659 791715 841784 912875 994
175 140195 155225 180255 200
185 150215 170240 195275 220
160-23-4081▲162-23-4081*
160-23-4084160-23-4090
4/0(19X)4/0(19X)
250(37X)350(37X)
1.08 40 1.181.07 40 1.171.14 40 1.241.24 40 1.34
11X1411X1413X1418X14
1.411.411.471.58
1011 11281006 11291115 13301347 1566
285 235285 235305 250375 310
310 255310 255330 275405 335
160-23-4093▲162-23-4093*
160-23-4096▲162-23-4096*
160-23-4099▲162-23-4099*
500(37X)500(37X)750(61X)750(61X)
1000(61X)1000(61X)
1.38 40 1.481.37 40 1.471.57 40 1.671.57 40 1.671.72 55 1.851.70 55 1.85
16X1216X12
16X.096616X.096618X.105218X.1052
1.811.802.032.032.242.23
1777 19861771 19882396 31562365 32152952 35332951 3535
450 370450 370545 460545 460620 520620 520
490 405490 405595 505595 505675 570675 570
105
CAm
pacity
Dire
ct B
urial (
2)
°
105
CAm
pacity
Duct
(2)
°
Okonite’s web site, www.okonite.com contains the most up to date information.
Okoguard URO-J25kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating133% Insulation Levels
Okoguard Insulation: 320 mils 133% Insulation Level
Product DataSection 2: Sheet 39
(1) Individual wire size and count may vary. The resulting combination meets the 1/3 or full neutral,size requirement.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEA P-117-734 for 90°C or 105°C conductor temperature, 25°Cambient temperature, 100% load factor, and earth thermalresistivity of RHO 90.One third neutral ampacities are based on triplexed ortriangular configuration for the same conditions stated above.
THE OKONITE COMPANYRamsey, New Jersey 07446L/20110239
Catalo
gNum
ber
Conduct
or size
(AW
Gor kc
mil)
Appro
x. N
et W
eight
lbs.
/100
0’
Appro
x. S
hip W
eight
lbs.
/100
0’
Nom
inal
Dia
. ove
r Insu
latio
n (in.)
Nom
inal
Dia
. ove
r
Insu
latio
n Scr
een (i
n.)
Copper
Full
Neu
tral
No. x
AWG
(1)
Nom
inal
O.D
. (in
.)
90C
Am
pacity
Dire
ct B
urial (
2)
°90
CAm
pacity
Duct
(2)
°In
sula
tion S
cree
n
Thickn
ess
(mils
)
FULL NEUTRAL
161-23-5066161-23-5072161-23-5075
1(19X)1/0(19X)2/0(19X)
1.01 40 1.091.05 40 1.151.09 40 1.19
13X1416X1414X12
1.321.391.46
876 1047994 1138
1157 1353
195 145220 160250 185
210 155235 175270 205
161-23-5078161-23-5081161-23-5084161-23-5090
3/0(19X)4/0(19X)
250(37X)350(37X)
1.14 40 1.241.20 40 1.301.26 40 1.361.37 40 1.47
16X1214X1016X10
18X.1074
1.511.611.741.86
1269 25031514 18191733 20322068 2349
285 210320 240350 270425 310
310 230350 260380 295460 340
1/3 NEUTRAL
160-23-5066160-23-5072160-23-5075160-23-5078
1(19X)1/0(19X)2/0(19X)3/0(19X)
1.01 40 1.091.05 40 1.151.09 40 1.191.14 40 1.24
6X146X147X149X14
1.321.391.431.48
793 966877 1022952 1099
1049 1261
175 140195 155225 180255 200
185 150215 170240 195275 220
160-23-5081160-23-5084160-23-5090
4/0(19X)250(37X)350(37X)
1.20 40 1.301.26 40 1.361.37 40 1.47
11X1413X1418X14
1.541.601.77
1162 13781281 14901588 1881
285 235305 250375 310
310 255330 275405 335
160-23-5093160-23-5096160-23-5099
500(37X)750(61X)
1000(61X)
1.50 40 1.601.68 55 1.821.84 55 1.98
16X1216X.096618X.1052
1.932.202.36
1968 22752647 31223189 3771
450 370545 460620 520
490 405595 505675 570
Num
berof S
tran
ds
105
CAm
pacity
Dire
ct B
urial (
2)
°
105
CAm
pacity
Duct
(2)
°
InsulationOkoguard is Okonite's registered trade namefor its exclusive ethylene-propylene rubber(EPR) based, thermosetting compound,whose optimum balance of electrical andphysical properties is unequaled in othersolid dielectrics. Okoguard insulation, withthe distinctive red color and a totally inte-grated EPR system, provides the optimumbalance of electrical and physical propertiesfor long, problem free service.The triple tandem extrusion of the screenswith the insulation provides optimum electri-cal characteristics.An insulation screen of ethylene-propylenerubber is extruded over the insulation. Thebare copper concentric wires are uniformlyspaced around the insulation screen. Theoverall polyethylene jacket provides protec-tion against mechanical damage andcorrosion.Product identification is provided through theuse of three red stripes placed 120° apart inthe black jacket, with an NESC lightning bolt.
ApplicationsOkoguard URO-J cables provide maximumcircuit longevity in underground residentialdistribution systems. They can be buried di-rectly or installed in underground ducts orconduits.
SpecificationsCentral Conductor: Aluminum per ASTMB-609, Class B stranded per B-231.Conductor Screen: Extruded semiconduct-ing ethylene-propylene rubber meets orexceeds the requirements of ICEA S-94-649,AEIC CS8, and CSA C68.5.Insulation: Extruded Okoguard meets or ex-ceeds the requirements of ICEA S-94-649,AEIC CS8, and CSA C68.5.Insulation Screen: Extruded semiconduct-ing ethylene-propylene rubber meets orexceeds the requirements of ICEA S-94-649,AEIC CS8, and CSA C68.5.Concentric Conductor: Bare copper wires.Jacket: Black Okolene with red extrudedstripes meets or exceeds the requirements ofICEA S-94-649, AEIC CS8, and CSA C68.5for polyethylene jackets.
Product Features• Triple tandem extruded, all EPR system.
• Okoguard cables meet or exceed ICEAstandards.
• Meets RUS 1728.204 for cables withfilled strand or solid conductor and 100%insulation level.
• 105°C continuous operating temperature• 140°C emergency rating• 250°C short circuit rating
• Excellent corona resistance.
• Low dielectric constant and powerfactor.
• Screens are clean stripping.
• Exceptional resistance to “treeing”.
• Moisture resistant.
• Overall jacket provides extended life.
• Excellent resistance to most chemicals.
• Can be listed by UL as Type MV-90 onSpecial Orders.
• CSA C68.5 listed, LTGG (-40°C), SR.
• Design Options:Additional conductor sizesFilled strandCopper central conductorCopper flat strap concentric neutralProduct identification via coloredjacketsSemiconducting jackets
• Improved Temperature Rating.Okoguard insulation system has beentested and qualified for operation at105°C continuous and 140°C emergencyoperating temperature. Appropriate jacketshould be selected when cable is to beoperated at these higher temperatures.
• Minimum installation temperature of-40°C.
Okoguard® URO-J35kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating100% and 133% Insulation Levels
Product DataSection 2: Sheet 40
A Conductor-Stranded AluminumB Strand Screen- Extruded
Semiconducting EPRC Insulation-Okoguard EPRD Insulation Screen- Extruded
Semiconducting EPRE Concentric Conductor-Bare Copper
WiresF Encapsulating Jacket-Okolene with
three extruded red ID stripes andNESC lightning bolt
Okoguard URO-J35kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating100% Insulation Level
Okoguard Insulation: 345 mils 100% Insulation Level
Product DataSection 2: Sheet 40
FULL NEUTRAL
161-23-6072� 163-23-6072*
161-23-6075161-23-6078
1/0 (19x)1/0 (19x)2/0 (19x)3/0 (19x)
1.10 401.10 401.15 401.20 40
1.201.201.251.30
16x1416x1414x1216x12
1.441.441.521.57
1055105712311336
1179118114161552
205205240270
165165190215
225225260295
180180205230
161-23-6081161-23-6084161-23-6090
4/0 (19x)250 (37x)350 (37x)
1.26 401.31 401.42 40
1.361.411.52
14x1016x10
18x.1078
1.741.791.91
165718052146
192121062525
310340410
240265320
335370445
265290350
1/3 NEUTRAL
160-23-6072160-23-6075160-23-6078
1/0 (19x)2/0 (19x)3/0 (19x)
1.10 401.15 401.20 40
1.201.251.30
6x147x149x14
1.441.481.54
93810151125
108212231326
195220250
160185210
210240270
175200230
160-23-6081160-23-6084160-23-6090
4/0 (19x)250 (37x)350 (37x)
1.26 401.31 401.42 40
1.361.411.52
11x1413x1418x14
1.601.721.82
124114111663
144517011957
285305370
235255315
310330405
260280345
160-23-6093160-23-6096160-23-6099
500 (37x)750 (61x)
1000 (61x)
1.55 401.74 551.89 55
1.651.882.03
16x1216x.096618x.1052
1.982.242.41
205827273289
251533233872
450545620
380470530
485595675
415515585
* These items include filled strand.
Okonite's web site, www.okonite.com contains the most up to date information.
CopperNeu
tral
Number
x AWG
(1)
Nomin
alDia.
Over
Insu
latio
n
Nomin
alDia.
Over
Insu
latio
nScr
een
Approx.
ShipW
eight
lbs./
1000
’
Conductor Size
AWG/kc
mil
105°
CAm
pacity
(2)
Direct
Burial
Catalo
gNum
ber
Nomin
alO.D
. (In
.)
Approx.
NetW
eight
lbs./
1000
’
105°
CAm
pacity
(2)
Duct90
°CAm
pacity
(2)
Direct
Burial
90°C
Ampac
ityDuct
(2)
� Authorized Stock Item - Available from Customer Servicecenters.
(1) Individual wire size and count may vary. The resulting combinationmeets the 1/3 or full neutral, size requirement.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEA P-117-734for 90°C or 105°C conductor temperature, 25°C ambient temperature,100% load factor, and earth thermal resistivity of RHO 90.One third neutral ampacities are based on triplexed or triangular con-figuration for the same conditions stated above.
Insu
latio
nScr
een
Thicknes
s (mils
)
Okoguard URO-J35kV Underground Primary Distribution Cable-JacketedRed Identification StripesAluminum Conductor/105°C Rating133% Insulation Level
Okoguard Insulation: 420 mils 133% Insulation Level
Product DataSection 2: Sheet 40
FULL NEUTRAL
161-23-7072161-23-7075161-23-7078
1/0 (19x)2/0 (19x)3/0 (19x)
1.26 401.31 401.35 40
1.361.411.45
16x1414x1216x12
1.591.741.78
125015031608
146317701916
205240270
165190215
225260295
180205230
161-23-7081161-23-7084161-23-7090
4/0 (19x)250 (37x)350 (37x)
1.41 401.47 401.57 55
1.511.571.71
14x1016x10
18x.1078
1.891.952.10
189120482479
215923522846
310340410
240265320
335370445
265290350
1/3 NEUTRAL
160-23-7072160-23-7075160-23-7078
1/0 (19x)2/0 (19x)3/0 (19x)
1.26 401.31 401.36 40
1.361.411.46
6x147x149x14
1.591.711.76
113312921401
134715731684
195220250
160185210
210240270
175200230
160-23-7081160-23-7084160-23-7090
4/0 (19x)250 (37x)350 (37x)
1.40 401.47 401.56 55
1.501.571.70
11x1413x1418x14
1.801.872.00
150916461956
181419392367
285305370
235255315
310330405
260280345
160-23-7093160-23-7096160-23-7099
500 (37x)750 (61x)
1000 (61x)
1.69 551.90 552.05 55
1.832.032.18
16x1216x.096618x.1052
2.162.402.57
237030323617
284636324202
450545620
380470530
485595675
415515585
Okonite's web site, www.okonite.com contains the most up to date information.
CopperNeu
tral
Number
x AWG
(1)
Nomin
alDia.
Over
Insu
latio
n
Nomin
alDia.
Over
Insu
latio
nScr
een
Approx.
ShipW
eight
lbs./
1000
’
Conductor Size
AWG/kc
mil
105°
CAm
pacity
(2)
Direct
Burial
Catalo
gNum
ber
Number
of Strands
Approx.
NetW
eight
lbs./
1000
’
105°
CAm
pacity
Duct(2
)
Nomin
alO.D
. (In
.)
(1) Individual wire size and count may vary. The resulting combinationmeets the 1/3 or full neutral, size requirement.
Ampacities
(2) Full neutral, single phase ampacities are based on ICEA P-117-734for 90°C or 105°C conductor temperature, 25°C ambient temperature,100% load factor, and earth thermal resistivity of RHO 90.One third neutral ampacities are based on triplexed or triangular con-figuration for the same conditions stated above.
90°C
Ampac
ity(2
)
Direct
Burial
90°C
Ampac
ityDuct
(2)
J/19070240
THE OKONITE COMPANYRamsey, New Jersey 07446
Insu
latio
nScr
een
Thicknes
s (mils
)
Okoguard URO-J®
15kV to 35kV Underground Primary Distribution CableJacketed-Red Identification StripesCopper Conductor/105°C Rating100% and 133% Insulation Levels
A Conductor-Compressed or CompactRound CopperStrand Screen -BExtruded Semiconducting EPR
C Insulation-Okoguard-EPRD Insulation Screen -
Extruded Semiconducting EPRE Concentric Conductor-Bare Copper
WiresEncapsulating Jacket-Okolene withF3 extruded red ID stripes, and NESCLightning bolt
Product DataSection 2: Sheet 42
1/0
AW
G O
KO
GU
AR
D E
PR
100%
IN
SU
L
� ◄
InsulationOkoguard is Okonite's registered trade name
for its exclusive ethylene-propylene rubber
(EPR) based, thermosetting compound,
whose optimum balance of electrical and
physical properties is unequaled in other
solid dielectrics. Okoguard insulation, with
the distinctive red color and a totally
integrated EPR system, provides the
optimum balance of electrical and physical
properties for long, problem-free service.
The triple tandem extrusion of the screens
with the insulation provides optimum
electrical characteristics.
An insulation screen of ethylene-propylene
rubber is extruded over the insulation. The
bare concentric copper wires are uniformly
spaced around the insulation screen. The
overall polyethylene jacket provides
protection against mechanical damage and
corrosion.
Product identification is provided through the
use of three red stripes placed 120° apart in
the black jacket with an NESC Lightning bolt.
ApplicationsOkoguard URO-J cables provide maximum
circuit longevity in underground residential
distribution systems. They can be buried
direct or installed in underground ducts or
conduits.
SpecificationsCentral Conductor: Uncoated soft copper.
Compressed round conductors per ASTM
B-3 and ASTM B-8. Compact round
conductors per ASTM B-496.
Conductor Screen: Extruded
semiconducting ethylene-propylene rubber
meets or exceeds the requirements of ICEA
S-94-649, AEIC CS8, and CSA C68.5.
Insulation: Extruded Okoguard meets or®
exceeds the requirements of ICEA S-94-649,
AEIC CS8, and CSA C68.5.
Insulation Screen: Two insulation screen
thicknesses are available:
Cables with Compressed Round Copper
Conductor: Have extruded semiconducting
ethylene-propylene rubber insulation
screens that meet the requirements of ICEA
S-94-649, AEIC CS8, and CSA C68.5.
Select cables with Compact Round
Copper Conductor: Have extruded
semiconducting ethylene-propylene rubber
insulation screens that meet the
requirements of ICEA S-93-639/NEMA
WC74 & S-97-682, and AEIC CS8.
Concentric Conductor: Bare copper wires.
Jacket: Black Okolene with red extruded
stripes meets or exceeds the requirements
of ICEA S-94-649, AEIC CS8, and CSA
C68.5 for polyethylene jackets.
Product Features• Triple tandem extruded, all EPR
system
• Okoguard cables meet or exceed ICEA
standards.
• 105°C continuous operating
temperatures
140°C emergency rating•250°C short circuit rating•
• Excellent corona resistance.
• Low dielectric constant and power
factor.
• Screens are clean stripping.
• Exceptional resistance to "treeing".
• Moisture resistant.
• Excellent resistance to most
chemicals.
• Can be listed by UL as Type MV-90 on
Special Orders.
• CSA C68.5 listed, LTGG (-40°C), SR.
• Design Options:- Additional conductor sizes- Filled strand- Copper flat strap concentric
neutral- Product identification via colored
jackets.- Semiconducting jacket.
• Improved Temperature Rating.
Okoguard insulation system has been
tested and qualified for operation at 105°C
continuous and 140°C emergency
operating temperature.
Product DataSection 2: Sheet 42
Okoguard URO-J®
Copper Compressed Round Conductor/105ºC Rating(with ICEA S-94-649 Insulation Screen Thickness)
15kV - 175 mils (4.45mm), 100% Insulation LevelFull Neutral
141-23-2060141-23-2066141-23-2072
2(7x)1(19x)
1/0(19x)
0.68 30 0.750.72 30 0.790.76 30 0.83
16x14 0.9914x12 1.0616x12 1.10
725 775890 959
1017 1086
210 160235 180270 205
230 175260 200290 225
141-23-2075141-23-2078141-23-2081
2/0(19x)3/0(19x)4/0(19x)
0.80 30 0.870.85 30 0.920.90 30 0.98
14x10 1.1916x10 1.24
18x.1073 1.30
1273 13801468 16171763 1912
310 235350 265405 305
335 255380 290440 330
1/3 Neutral
140-23-2060140-23-2066140-23-2072
2(7x)1(19x)
1/0(19x)
0.68 30 0.750.72 30 0.790.76 30 0.83
6x14 0.997x14 1.039x14 1.07
608 658693 743805 874
195 160220 180250 200
210 175240 195275 220
140-23-2075140-23-2078140-23-2081
2/0(19x)3/0(19x)4/0(19x)
0.80 30 0.870.85 30 0.920.90 30 0.98
11x14 1.1114x14 1.1618x14 1.21
937 10061106 11831318 1413
285 230325 260365 300
310 250350 285395 325
140-23-2084140-23-2090140-23-2093
250(37x)350(37x)500(37x)
0.97 30 1.041.07 40 1.171.20 40 1.30
14x12 1.3118x12 1.44
18x.0953 1.60
1549 16832021 22072721 2959
395 325475 390555 455
430 355515 425610 500
140-23-2096140-23-2099
750(61x)1000(61x)
1.39 40 1.491.54 40 1.64
24x.1010 1.8724x.1167 2.05
3925 48625083 5502
650 545815 685
710 600885 750
15kV - 220 mils (5.59mm), 133% Insulation LevelFull Neutral
141-23-3060141-23-3066141-23-3072
2(7x)1(19x)
1/0(19x)
0.77 30 0.840.81 30 0.880.85 30 0.92
16x14 1.0814x12 1.1516x12 1.19
803 871973 1055
1103 1185
210 160235 180270 205
230 175260 200290 225
141-23-3075141-23-3078141-23-3081
2/0(19x)3/0(19x)4/0(19x)
0.89 30 0.960.94 30 1.010.99 30 1.07
14x10 1.2816x10 1.33
18x.1073 1.39
1362 14541561 16631864 1953
310 235350 265405 305
335 255380 290440 330
1/3 Neutral
140-23-3060140-23-3066140-23-3072
2(7x)1(19x)
1/0(19x)
0.77 30 0.840.81 30 0.880.85 30 0.92
6x14 1.087x14 1.129x14 1.16
686 755774 858890 972
195 160220 180250 200
210 175240 195275 220
140-23-3075140-23-3078140-23-3081
2/0(19x)3/0(19x)4/0(19x)
0.89 30 0.960.94 30 1.010.99 30 1.07
11x14 1.2014x14 1.2518x14 1.31
1025 11051198 12901414 1506
285 230325 260365 300
310 250350 285395 325
140-23-3084140-23-3090140-23-3093
250(37x)350(37x)500(37x)
1.06 40 1.161.16 40 1.261.29 40 1.39
14x12 1.4318x12 1.53
18x.0953 1.77
1683 17982130 22762953 3146
395 325475 390555 455
430 355515 425610 500
140-23-3096140-23-3099
750(61x)1000(61x)
1.49 40 1.591.64 55 1.77
24x.1010 1.9624x.1167 2.18
4071 43535306 5667
650 545815 685
710 600885 750
Catalo
gNum
ber
Approx. N
et Weig
ht
(lbs./1
000’)
Approx. S
hipW
eight
(lbs./1
000’)
Catalo
gNum
ber
Conductor S
ize
AWG
/kcm
il
Nomin
al Dia
. over
Insula
tion
(in.)
Insula
tion
Screen
Thickness
(mils
)
Nomin
al Dia
. over
Insula
tion
Screen
(in.)
Copper Neutra
l
No. xAW
G(1
)
Nomin
al O.D
. (in
.)
90ºCAm
pacity
Direct B
urial (
2)
90ºCAm
pacity
Duct (2)
105ºCAm
pacity
Direct B
urial (
2)
105ºCAm
pacity
Duct (2)
Okonite’s web site, www.okonite.com contains the most up to date information.
(1) individual wire size and count may vary. The resulting combination meets 1/3 or full neutral, size requirement.
Product DataSection 2: Sheet 42
Okoguard URO-J®
Copper Compressed Round Conductor/105ºC Rating(with ICEA S-94-649 Insulation Screen Thickness)
25kV - 260 mils (6.60mm), 100% Insulation LevelFull Neutral
141-23-4066141-23-4072141-23-4075141-23-4078141-23-4081
1(19x)1/0(19x)2/0(19x)3/0(19x)4/0(19x)
0.89 30 0.960.93 30 1.000.97 30 1.041.02 40 1.121.08 40 1.18
14x12 1.2316x12 1.2714x10 1.3616x10 1.43
18x.1073 1.50
1053 11651187 13051451 15691683 18351992 2139
235 180270 205310 235350 265405 305
260 200290 225335 255380 290440 330
1/3 Neutral
140-23-4066140-23-4072140-23-4075140-23-4078140-23-4081
1(19x)1/0(19x)2/0(19x)3/0(19x)4/0(19x)
0.89 30 0.960.93 30 1.000.97 30 1.051.02 30 1.101.08 40 1.18
7x14 1.209x14 1.24
11x14 1.2814x14 1.3318x14 1.41
853 921972 1083
1110 12261287 14331537 1654
220 180250 200285 230325 260365 300
240 195275 220310 250350 285395 325
140-23-4084140-23-4090140-23-4093140-23-4096140-23-4099
250(37x)350(37x)500(37x)750(61x)
1000(61x)
1.14 40 1.241.24 40 1.341.38 40 1.481.57 40 1.701.72 55 1.85
14x12 1.5118x12 1.61
18x.0953 1.8424x.1010 2.0824x.1167 2.26
1783 19652235 24233032 34084285 46225458 5817
395 325475 390555 455650 545815 685
430 355515 425610 500710 600885 750
35kV - 345 mils (8.76mm), 100% Insulation LevelFull Neutral
141-23-6072141-23-6075141-23-6078141-23-6081
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
1.11 40 1.211.13 40 1.231.20 40 1.301.26 40 1.36
16x12 1.4814x10 1.5516x10 1.61
18x.1073 1.75
1424 15641678 18401909 20522293 2439
265 210305 235345 270395 305
285 230330 255375 295430 330
1/3 Neutral
140-23-6072140-23-6075140-23-6078140-23-6081
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
1.11 40 1.211.15 40 1.251.20 40 1.301.26 40 1.36
9x14 1.4511x14 1.4914x14 1.5418x14 1.60
1205 13441351 14891537 16761767 1906
250 210280 235320 265360 300
270 230305 260345 290395 330
140-23-6084140-23-6090140-23-6093140-23-6096140-23-6099
250(37x)350(37x)500(37x)750(61x)
1000(61x)
1.31 40 1.411.42 40 1.521.55 40 1.651.74 55 1.881.89 55 2.03
14x12 1.7518x12 1.85
18x.0953 2.0124x.1010 2.2524x.1167 2.43
2076 22352556 27363320 37894598 51635797 6323
390 330470 400555 470650 560815 700
425 365510 435605 515710 620885 770
35kV - 420 mils (10.67mm), 133% Insulation LevelFull Neutral
141-23-7022141-23-7025141-23-7028141-23-7031
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
1.27 40 1.371.31 40 1.411.36 40 1.461.41 40 1.51
16x12 1.6414x10 1.7916x10 1.84
18x.1073 1.90
1628 18321980 22262201 24472528 2778
265 210305 235345 270395 305
285 230330 260375 290430 330
1/3 Neutral
140-23-9923140-23-9931140-23-9932140-23-9940140-23-9941140-23-9942140-23-9943140-23-9944140-23-9946
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
250(37x)350(37x)500(37x)750(61x)
1000(61x)
1.27 40 1.371.31 40 1.411.36 40 1.461.41 40 1.511.47 40 1.571.57 40 1.671.70 55 1.841.90 55 2.032.02 55 2.18
9x14 1.6011x14 1.7114x14 1.7618x14 1.8214x12 1.9018x12 2.00
18x.0953 2.2024x.1010 2.4124x.1167 2.59
1406 15941619 18231813 20172053 22582314 28772818 31823658 40274905 54646128 6699
250 210280 235320 265360 300390 330470 400555 470650 560815 700
270 230305 255345 295395 330425 365510 435605 515710 620885 770
Catalo
gNum
ber
Approx. N
et Weig
ht
(lbs./1
000’)
Approx. S
hipW
eight
(lbs./1
000’)
Catalo
gNum
ber
Conductor S
ize
AWG
/kcm
il
Nomin
al Dia
. over
Insula
tion
(in.)
Insula
tion
Screen
Thickness
(mils
)
Nomin
al Dia
. over
Insula
tion
Screen
(in.)
Copper Neutra
l
No. xAW
G(1
)
Nomin
al O.D
. (in
.)
90ºCAm
pacity
Direct B
urial (
2)
90ºCAm
pacity
Duct (2)
105ºCAm
pacity
Direct B
urial (
2)
105ºCAm
pacity
Duct (2)
Okonite’s web site, www.okonite.com contains the most up to date information.
(1) individual wire size and count may vary. The resulting combination meets 1/3 or full neutral, size requirement.
Product DataSection 2: Sheet 42
Okoguard URO-J®
Copper Compact Round Conductor/105ºC Rating(with ICEA S-94-649 Insulation Screen Thickness)**
15kV - 175 mils (4.45mm), 100% Insulation LevelFull Neutral
141-23-2010141-23-2012141-23-2014141-23-2018141-23-2020
●141-23-2024
2(7x)1(19x)
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
0.67 30 0.740.70 30 0.770.74 30 0.810.78 30 0.850.83 30 0.900.86 24 0.93
16x14 0.9814x12 1.0416x12 1.0814x10 1.1716x10 1.21
18x.1073 1.26
718 762879 950
1004 10751256 13611449 15991723 1823
210 160235 180270 205310 235350 265405 305
230 175260 200290 225335 255380 290440 330
1/3 Neutral
140-23-2010140-23-2012140-23-2014140-23-2018140-23-2020
●140-23-2024140-23-2026
●140-23-2030●140-23-2032●140-23-2036
140-23-2038
2(7x)1(19x)
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
250(37x)350(37x)500(37x)750(61x)
1000(61x)
0.67 30 0.740.70 30 0.770.74 30 0.810.78 30 0.850.83 30 0.900.86 24 0.930.93 30 1.011.01 24 1.081.12 24 1.191.30 24 1.371.47 40 1.57
6x14 0.987x14 1.019x14 1.05
11x14 1.0914x14 1.1418x14 1.1714x12 1.2818x12 1.35
18x.0953 1.4924x.1010 1.7424x.1167 1.98
601 645682 732792 864922 990
1089 11571280 13611522 16391928 20282603 27463775 40104979 5398
195 160220 180250 200285 230325 260365 300395 325475 390555 455650 545815 685
210 175240 195275 220310 250350 285395 325430 355515 425610 500710 600885 750
15kV - 220 mils (5.59mm), 133% Insulation LevelFull Neutral
▲141-23-9460*●141-23-9060
141-23-9066●141-23-9517
2(7x)2(7x)
1(19x)1/0(19x)
0.76 30 0.830.74 24 0.810.79 30 0.870.81 24 0.88
16x14 1.0716x14 1.0514x12 1.1416x12 1.15
792 862774 841960 1022
1065 1145
210 160210 160235 180270 205
230 175230 175260 200290 225
●141-23-9075141-23-9533
●141-23-9535
2/0(19x)3/0(19x)4/0(19x)
0.85 24 0.920.92 30 0.990.95 24 1.02
14x10 1.2316x10 1.30
18x.1073 1.34
1320 14051541 16411813 1901
310 235350 265405 305
335 255380 290440 330
1/3 Neutral
●140-23-9512140-23-9514
●140-23-9523
2(7x)1(19x)
1/0(19x)
0.74 24 0.810.79 30 0.870.81 24 0.88
6x14 1.057x14 1.109x14 1.12
657 724761 829852 933
195 160220 180250 200
210 175240 195275 220
●140-23-9025●140-23-9068●140-23-9046
2/0(19x)3/0(19x)4/0(19x)
0.85 24 0.920.92 30 0.990.95 24 1.02
11x14 1.1614x14 1.2318x14 1.26
985 10651179 12701367 1445
285 230325 260365 300
310 250350 285395 325
●140-23-9231140-23-9234
●140-23-9087
250(37x)350(37x)500(37x)
1.00 24 1.071.10 24 1.161.21 24 1.28
14x12 1.3418x12 1.43
18x.0953 1.58
1592 16742030 21732720 2906
395 325475 390555 455
430 355515 425610 500
●140-23-9096●140-23-9048
750(61x)1000(61x)
1.39 24 1.461.54 24 1.60
24x.1010 1.8324x.1167 2.01
3913 41975065 5387
650 545815 685
710 600885 750
Catalo
gNum
ber
Approx. N
et Weig
ht
(lbs./1
000’)
Approx. S
hipW
eight
(lbs./1
000’)
Catalo
gNum
ber
Conductor S
ize
AWG
/kcm
il
Nomin
al Dia
. over
Insula
tion
(in.)
Insula
tion
Screen
Thickness
(mils
)
Nomin
al Dia
. over
Insula
tion
Screen
(in.)
Copper Neutra
l
No. xAW
G(1
)
Nomin
al O.D
. (in
.)
90ºCAm
pacity
Direct B
urial (
2)
90ºCAm
pacity
Duct (2)
105ºCAm
pacity
Direct B
urial (
2)
105ºCAm
pacity
Duct (2)
Okonite’s web site, www.okonite.com contains the most up to date information.
▲Authorized stock item - Available from Customer Service Centers. ● Items use component core for quicker delivery*141-23-9460 is listed and shipped UL’s MV-90 rating on jacket. All other cables shown are available with same listing on special order.(1) Individual wire size and count may vary. The resulting combination meets 1/3 or full neutral, size requirements.** When component core is used, insulation screen thickness per ICEA S-93-639 and S-97-682.
Product DataSection 2: Sheet 42
Okoguard URO-J®
Copper Compact Round Conductor/105ºC Rating(with ICEA S-94-649 Insulation Screen Thickness)**
25kV - 260 mils (6.60mm), 100% Insulation LevelFull Neutral
141-23-4166141-23-4172141-23-4175141-23-4178141-23-4181
1(19x)1/0(19x)2/0(19x)3/0(19x)4/0(19x)
0.87 30 0.950.91 30 0.990.95 30 1.031.00 30 1.071.05 40 1.15
14x12 1.2216x12 1.2614x10 1.3416x10 1.39
18x.1073 1.48
1040 11291170 12851434 15531634 17871966 2128
235 180270 205310 235350 265405 305
260 200290 225335 255380 290440 330
1/3 Neutral
140-23-4166140-23-4172140-23-4175140-23-4178140-23-4181140-23-4184140-23-4190140-23-4193140-23-4197140-23-4199
1(19x)1/0(19x)2/0(19x)3/0(19x)4/0(19x)
250(37x)350(37x)500(37x)750(61x)
1000(61x)
0.87 30 0.950.91 30 0.990.95 30 1.031.00 30 1.071.05 40 1.151.11 40 1.211.20 40 1.301.32 40 1.421.50 40 1.601.64 55 1.78
7x14 1.199x14 1.22
11x14 1.2614x14 1.3118x14 1.3914x12 1.4818x12 1.57
18x.0953 1.7824x.1010 1.9724x.1167 2.19
839 952956 1070
1092 12061266 13811513 16651750 19122199 23842969 31974128 44345364 5765
220 180250 200285 230325 260365 300395 325475 390555 455650 545815 685
240 195275 220310 250350 285395 325430 355515 425610 500710 600885 750
35kV - 345 mils (8.76mm), 100% Insulation LevelFull Neutral
141-23-9822141-23-9825141-23-9828141-23-9831
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
1.09 40 1.191.13 40 1.231.18 40 1.281.23 40 1.33
16x12 1.4614x10 1.5516x10 1.59
18x.1073 1.72
1404 15441677 17911886 20302263 2327
270 205310 235350 265405 305
290 225335 255380 290440 330
1/3 Neutral
140-23-9822140-23-9825140-23-9828140-23-9831
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
1.09 40 1.191.13 40 1.231.18 40 1.281.23 40 1.33
9x14 1.4311x14 1.4614x14 1.5218x14 1.57
1185 13251319 14731512 16551739 1867
250 200285 230325 260365 300
275 220310 250350 285395 325
140-23-9834140-23-9839
●140-23-9841140-23-9846140-23-9848
250(37x)350(37x)500(37x)750(61x)
1000(61x)
1.28 40 1.381.37 40 1.471.47 24 1.541.67 55 1.801.81 55 1.95
14x12 1.6518x12 1.81
18x.0953 1.9124x.1010 2.1824x.1167 2.36
1976 21002502 26673160 34964505 49245691 6219
395 325475 390555 455650 545815 685
430 355515 425610 500710 600885 750
35kV - 420 mils (10.67mm), 133% Insulation LevelFull Neutral
141-23-9922141-23-9925141-23-9928141-23-9931
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
1.25 40 1.351.29 40 1.391.34 40 1.441.39 40 1.49
16x12 1.6214x10 1.7716x10 1.81
18x.1073 1.88
1606 17451950 20852168 23322494 2662
265 210305 235345 270395 305
285 230330 255375 295430 330
1/3 Neutral
140-23-9922140-23-9924140-23-9927140-23-9928
1/0(19x)2/0(19x)3/0(19x)4/0(19x)
1.25 40 1.351.28 40 1.381.34 40 1.441.39 40 1.49
9x14 1.5911x14 1.6814x14 1.7418x14 1.79
1384 15231576 16771784 19482021 2169
250 210280 235320 265360 300
270 230305 260345 290395 330
140-23-9930140-23-9939
●140-23-9947140-23-9948140-23-9949
250(37x)350(37x)500(37x)750(61x)
1000(61x)
1.44 40 1.541.53 40 1.631.62 24 1.691.82 55 1.961.97 55 2.11
14x12 1.8718x12 1.96
18x.0953 2.0624x.1010 2.3424x.1167 2.51
2269 24382757 30143424 37564801 53806011 6547
390 330470 400555 470650 560815 700
425 365510 435605 515710 620885 770
Catalo
gNum
ber
Approx. N
et Weig
ht
(lbs./1
000’)
Approx. S
hipW
eight
(lbs./1
000’)
Catalo
gNum
ber
Conductor S
ize
AWG
/kcm
il
Nomin
al Dia
. over
Insula
tion
(in.)
Insula
tion
Screen
Thickness
(mils
)
Nomin
al Dia
. over
Insula
tion
Screen
(in.)
Copper Neutra
l
No. xAW
G(1
)
Nomin
al O.D
. (in
.)
90ºCAm
pacity
Direct B
urial (
2)
90ºCAm
pacity
Duct (2)
105ºCAm
pacity
Direct B
urial (
2)
105ºCAm
pacity
Duct (2)
Okonite’s web site, www.okonite.com contains the most up to date information.
●Items use component core for quicker delivery.*141-23-9460 is listed and shipped UL’s MV-90 rating on jacket. All other cables shown are available with same listing on special order.**When component core is used, insulation screen thickness per ICEA S-93-639 and S-97-682.
Product DataSection 2: Sheet 42
Okoguard URO-J®
15kV to 35kV Underground Primary Distribution CableJacketed - Red Identification StripesCopper Conductor/105ºC Rating 100% and 133% Insulation Level
Okonite’s web site, www.okonite.com contains the most up to date information.
Table CNInsulation Screen Thickness*
per ICEA S-94-649(for Traditional Concentric Neutral Shield)
Calculated MinimumDiameter overInsulation (In.)
Minimum Point(mils)
0 - 1.000 30
1.001 - 1.500 40
1.5001 - 2.000 55
2.001 - larger 55
Table CTInsulation Screen Thickness*
per ICEA S-93-639(for Traditional Copper Tape Shield)
Calculated MinimumDiameter overInsulation (In.)
Minimum Point(mils)
ALL 24
*Insulation Screens: Two insulation screen thicknesses are available:Cables with Compressed Round Copper Conductor (Table CN):Have extruded semiconducting ethylene-propylene rubber insulation screens that meet therequirements of ICEA S-94-649 and AEIC CS8.Cables with Compact Round Copper Conductor (Table CT):Have extruded semiconducting ethylene-propylene rubber insulation screens that meet therequirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072, when component core is used.
Ampacities(2)Full neutral, single phase ampacities are based on ICEA
P-117-734 for 90ºC or 105ºC conductor temperature, 25ºCambient temperature, 100% load factor, and earth thermal resistivityof RHO 90.One third neutral ampacities are based on triplexed or triangularconfiguration for the same conditions stated above.
P/21030242 THE OKONITE COMPANYRamsey, New Jersey 07446
Composite InsulationOkoguard-Okolon TS-CPE is Okonite’s tradename for its composite insulation systemconsisting of a layer of EPR and covered witha chlorinated polyethylene (CPE) thermosetcompound.
The advantages of Okoguard EPR, with aproven track record of over 50 years as a me-dium voltage insulation, are now offered in lowvoltage cables. Okolon TS-CPE is Okonite'strade name for its chlorinated polyethylene(CPE) thermoset compound.
ApplicationsOkoguard-Okolon TS-CPE 600 Volt Powerand Control Cables are recommended for usein all low voltage circuits where continuity ofservice is the prime consideration. These ca-bles may be installed in wet or dry locations,indoors or outdoors, in raceways, undergroundducts, directly buried in the earth, or lashed toa messenger for aerial installation. These ca-bles may also be installed in cable tray (size1/0 AWG and larger per NEC 392.10(B)(1)).
SpecificationsConductor: Uncoated soft copper per ASTMB-3. Solid per ASTM B-3. Sizes smaller than#8 are compress stranded per ASTM B-8.Sizes #8 and larger are compact stranded perASTM B-496.
Insulation: Meets or exceeds all requirementsof ICEA S-95-658, NEMA WC-70 and ULStandards 44 and 854.
Listed by Underwriters Laboratories, Inc. asType RHH or RHW-2 or USE-2, VW-1. Sizes1/0 AWG and larger are also marked sunlightresistant, for use in cable tray.
Listed by CSA as RW-90, -40C, FT1 (1/0 andlarger: FT4), sunlight resistant.
** Sizes 12 AWG and larger, with exception to 6 AWG
Product Features• Sizes 1/0 AWG and larger pass the Verti-cal Tray Flame Test requirements of UL1581 for use in cable tray.
• Passes the IEEE 383-1974 Vertical TrayFlame Test. (sizes #6 AWG and larger)
• Passes the IEEE 1202 Vertical TrayFlame Test. (sizes 1/0 AWG & larger)
• Extreme heat resistance;90°C continuous rating, wet or dry130°C emergency overload rating250°C short circuit rating
• Exceptional resistance to deformation athigh temperature.
• Stable electrical properties.
• Low SIC and power factor.
• Low moisture absorption.
• Mechanically rugged.
• Resistant to weather, most oils, acids andalkalies.
• More flexible, easier to install and termi-nate than XLPE insulation.
• UL and CSA Listed.
• Multiple Conductor ConstructionsAvailable.
Okoguard-Okolon® TS-CPE Type RHHor RHW-2 or USE-2**, VW-1, FT-4, CSA RW-90600V Power and ControlCopper Conductor/90°C Wet or DryFor Cable Tray Use-Sunlight Resistant-For Direct Burial
Product DataSection 3: Sheet 1
A Uncoated, Copper ConductorB Composite Okoguard/Okolon
TS-CPE Insulation
Composite InsulationThickness (mils)
Conductor(AWG/kcmil) Okoguard
OkolonTS-CPE
14-9 30 15
8 45 15
6-2 45 30
1-4/0 55 45
250-500 65 65
750-1000 80 65
ULR
B
A
OK
ON
ITE
51/
0A
WG
CU
OK
OG
UA
RD
EP
TS
-CP
E(U
L)C
SA
112-24-2061� 112-24-2071
112-24-2091
141412
171
454545
1.141.141.14
0.160.170.18
4.064.574.57
232532
283037
151520
151520
242430
� 112-24-2101112-24-2121
� 112-24-2131
121010
717
454545
1.141.141.14
0.190.200.21
4.835.085.33
344649
395154
203030
203030
304242
112-24-2171� 112-24-2191� 112-24-2221
986
1977
456075
1.141.521.91
0.230.270.33
5.846.868.38
5875
119
6382
130
305575
305065
485575
� 112-24-2251� 112-24-2311
112-24-2331
421
77
19
7575
100
1.911.912.54
0.380.430.52
9.7511.0013.16
173257340
184280372
95130150
85115130
97130156
� 112-24-2351� 112-24-2371
112-24-2391
1/02/03/0
191919
100100100
2.542.542.54
0.560.600.64
14.1015.1416.33
414507622
446539654
170195225
150175200
179204242
� 112-24-2411� 112-24-2431� 112-24-2471
4/0250350
193737
100130130
2.543.303.30
0.700.800.89
17.6820.3222.61
766938
1265
805993
1320
260290350
230255310
278317384
� 112-24-2531� 112-24-2591� 112-24-2651
500750
1000
376161
130145145
3.303.683.68
1.011.211.36
25.6530.7334.54
175025903391
182726903568
430535615
380475545
477598689
Okonite's web site, www.okonite.com contains the most up to date information.
� Authorized stock item. Available from our Customer Service Centers. (1) Ampacities are based on Table 310.16 of the National Electrical Code forthese 90°C rated conductors at an ambient temperature of 30°C. The 75°Cwet column is provided for additional information.
The ampacities shown apply to open runs of cable, installation in any approvedraceway, direct burial in the earth, or as aerial cable on a messenger. Deratingfor more than three current carrying conductors within a raceway is in accor-dance with NEC 310.15(C)(1).
(2) Based on three (3) conductors in a single enclosed or exposed conduit. Ca-pacities based on 40°C air ambient using ICEA methods. For 30°C ambientmultiply values by 1.10; for 50°C multiply by .90. For other ambients or installa-tion conditions refer to Engineering Data Book EHB.
For ampacities in cable tray, see NEC Section 392.80.
F/21060301
Okoguard-Okolon TS-CPE Type RHHor RHW-2 or USE-2**, VW-1, FT-4, CSA RW-90600V Power and ControlCopper Conductor/90°C Wet or DryFor Cable Tray Use - Sunlight Resistant - For Direct Burial
Product DataSection 3: Sheet 1
To order a color other than black, change the last digit of thecatalog number as follows:
White 2 Orange 5
Red 3 Blue 6
Green 4 Yellow 7
Example: To order #14/Sol - Red, the catalog number would be112-24-2063.
ULR
Catalo
gNum
ber
Composit
e Insu
latio
n
Thicknes
s - mils
Number
of Strands
Conductor Size
AWG
kcm
il
Composit
e Insu
latio
n
Thicknes
s - mm
Approx.
ShipW
eight
lbs./
1000
’
ICEA
Ampac
ity(2
)
Approx.
O.D. -
mm
90°C
Wet
(1)*
NECAm
pacity
75°C
Wet
(1)*
NECAm
pacity
Approx.
O.D. -
Inch
es
Approx.
NetW
eight
lbs./
1000
’
Ramsey, New Jersey 07446THE OKONITE COMPANY
*Current limited to 15, 20 and 30 amps per Section 240.4(D)(3) of the NEC for #14, #12 and #10 AWG, respectively.**Sizes 12 AWG and larger, with exception to 6 AWG.
Composite InsulationOkoguard-Okolon® TS-CPE is Okonite’strade name for its composite insulationsystem consisting of a layer of EPR andcovered with a chlorinated polyethylene(CPE) thermoset compound. The combi-nation of the two materials provides adielectric which has excellent resistanceto heat, mechanical abuse, flame,weathering, most oils, acids and al-kalies.The advantages of Okoguard EPR, witha proven track record of over 50 yearsas a medium voltage insulation, are nowoffered in low voltage cables. OkolonTS-CPE is Okonite's trade name for itschlorinated polyethylene (CPE)thermoset compound.
ApplicationsOkoguard-Okolon TS-CPE 2000 voltpower cables are recommended for usein all low voltage circuits where continu-ity of service is the prime consideration.They can be installed in wet or dry loca-tions, indoors or outdoors in conduit,underground ducts, approved raceways.These cables may also be installed incable tray (size 1/0 AWG kcmil andlarger per NEC 392.10(B)(1)).
SpecificationsConductors: Uncoated soft copper perASTM B-3. Solid per ASTM B-3. Sizessmaller than #8 are compress strandedper ASTM B-8. Sizes #8 and larger arecompact stranded per ASTM B-496.Composite Insulation: Meets or ex-ceeds all requirements of ICEAS-95-658, NEMA WC-70 and UL Stan-dard 44.Listed by Underwriters Laboratories, Inc.as Type RHH or RHW-2, VW-1. Sizes1/0 AWG and larger are also markedsunlight resistant, for use in cable tray.All sizes meet FT-1. Sizes 1/0 andlarger meet FT-4.Listed by CSA as RW-90, -40�C, FT1(1/0 and larger: FT4), sunlight resistant.
Product Features• Sizes 1/0 AWG and larger pass theVertical Tray Flame Test require-ments of UL 1581 for use in cabletray.• Passes the IEEE 383-1974 VerticalTray Flame Test (size #8 AWG andlarger).• Passes the IEEE 1202 Vertical TrayFlame Test (sizes 1/0 AWG andlarger).• Passes the ICEA T-29-520(210,000 BTU/hr.) Vertical TrayFlame Test (sizes 2/0 AWG andlarger).• Extreme heat resistance90°C continuous rating, wet or dry130°C emergency overload rating250°C short circuit rating• Exceptional resistance to deforma-tion at high temperature.• Stable electrical properties.• Low SIC and power factor.• Low moisture absorption.• Mechanically rugged.• Resistant to weather, most oils, ac-ids and alkalies.• Smaller diameter than RHW jack-eted cables.• More flexible, easier to install, ter-minate or splice than XLPEinsulation.• OSHA acceptable.• UL and CSA Listed.
Okoguard-Okolon® TS-CPE Type RHHor RHW-2, VW-1, FT-4, CSA RW-902kV Power CableCopper Conductors/90°C Wet or DryFor Cable Tray Use - Sunlight Resistant
Product DataSection 3: Sheet 10
A Uncoated Copper ConductorB Composite Okoguard—Okolon
TS-CPE Insulation
Composite InsulationThickness (mils)
Conductor(AWG/kcmil) Okoguard Okolon
TS-CPE
14-109
8-21-4/0
250-500750-1000
455555657590
151530456565
B
A
OK
OG
UA
RD
EP
TS
-CP
E(U
L)
RH
HO
RR
HW
-2V
W-1
ULR
113-24-2061� 113-24-2071
113-24-2091
141412
171
606060
1.521.521.52
0.190.200.21
4.835.085.33
283038
333543
151520
151520
242430
� 113-24-2101113-24-2121
� 113-24-2131
121010
717
606060
1.521.521.52
0.220.230.24
5.595.846.10
405255
455760
203030
203030
304242
113-24-2171� 113-24-2191� 113-24-2221
986
1977
708585
1.792.162.16
0.280.320.35
7.118.138.89
7090
126
75101137
305575
305065
485575
� 113-24-2251� 113-24-2311
113-24-2331
421
77
19
8585
110
2.162.162.79
0.400.450.54
10.2611.4313.72
180265348
191278367
95130150
85115130
97130156
� 113-24-2351� 113-24-2371
113-24-2391
1/02/03/0
191919
110110110
2.792.792.79
0.570.610.66
14.4815.4916.76
424517633
442537657
170195225
150175200
179204242
� 113-24-2411� 113-24-2431� 113-24-2471
4/0250350
193737
110140140
2.793.563.56
0.710.830.92
18.0321.0823.37
777957
1286
81310041355
260290350
230255310
278317384
� 113-24-2531� 113-24-2591
113-24-2651
500750
1000
376161
140155155
3.563.943.94
1.041.241.38
26.4231.5035.05
177326183423
191528053674
430535615
380475545
477598689
Okonite's web site, www.okonite.com contains the most up to date information.
� Authorized stock item. Available from our Customer Service Centers. Ampacities
(1) Ampacities are based on Table 310.16 of the National Electrical Code forthese 90°C rated conductors at an ambient temperature of 30°C. The 75°C wetcolumn is provided for additional information.
The ampacities shown apply to open runs of cable, installation in any approvedraceway, direct burial in the earth, or as aerial cable on a messenger. Deratingfor more than three current carrying conductors within a raceway is in accor-dance with NEC 310.15(C)(1).
(2) Based on three (3) conductors in a single enclosed or exposed conduit. Ca-pacities based on 40°C air ambient using ICEA method. For 30°C ambientmultiply values by 1.10; for 50°C multiply by 0.89. For other ambients or instal-lation conditions refer to Okonite’s Engineering Data Book EHB.
For ampacities in cable tray see NEC Section 392.80.
I/21010310
Okoguard-Okolon TS-CPEType RHH or RHW-2, VW-1, FT-42kV Power CableCopper Conductor/90°C Wet or DryFor Cable Tray Use - Sunlight Resistant
Product DataSection 3: Sheet 10
To order a color other than black, change the last digit of thecatalog number as follows:
White 2 Orange 5
Red 3 Blue 6
Green 4 Yellow 7
Example: To order #14 - Red, the catalog number would be113-24-2073.
Catalo
gNum
ber
Approx.
ShipW
eight
lbs./
1000
’
ICEA
Ampac
ity(2
)
Number
of Strands
Approx.
O.D. -
mm
Composit
e Insu
latio
n
Thicknes
s - mm
75°C
Wet
(1)*
NECAm
pacity
Composit
e Insu
latio
n
Thicknes
s - mils
Approx.
O.D. -
Inch
es
Approx.
NetW
eight
lbs./
1000
’
Conductor Size
AWG
or kcm
il
90°C
Wet
(1)*
NECAm
pacity
Ramsey, New Jersey 07446THE OKONITE COMPANY
ULR
*Current limited to 15, 20 and 30 amps per Section 240.4(D)(3) of the NEC for #14, #12 and #10 AWG, respectively.
C-L-X Type MC-HL (XHHW-2)®
600/1000V Power MC-HL Cable - Aluminum Sheath3/C VFD & 4/C Copper Conductors/90°C Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
A Bare, Stranded Copper ConductorsX-Olene Insulation-Color Coded forBIdentificationBare, Stranded Copper GroundingCConductor(s)
D Non-Hygroscopic Fillers, as necessaryBinder TapeEImpervious, Continuous, WeldedFCorrugated, Aluminum C-L-X Sheath
G Black Okoseal Jacket
Product DataSection 4: Sheet 1
OK
ON
ITE
SP
-OS
12
PR
16
AW
G C
U X
-OL
EN
E (
XL
PE
)
OK
ON
ITE
6 P
-OS
1 P
R 1
6A
WG
CU
X-O
LE
NE
(X
LP
E)
A
B
E
F
C
D
G
UL®
Conductor Identification: Control Sizes, #9AWG and smaller, color coded insulation. PowerSizes, #8 AWG and larger, black with printedwords of number and color.Grounding Conductor(s): One or three baresoft copper per ASTM B-3. Stranded inaccordance with UL 1581. Meets or exceedsrequirements of NEC Table 250.122.Sheath: Close fitting, impervious, continuous,welded, corrugated aluminum C-L-X per UL1569. Exceeds grounding conductorrequirements of NEC Table 250.122.Jacket: Black Okoseal (PVC) per UL1569.MeetsASTM D746 brittle point at -40°C.
Product Features• ULListed as Type MC-HLcable per UL2225(E38916).• UL Listed for cable tray use, direct burial andsunlight resistant.• UL1309 (CWCMC) listed & ULclassified inaccord with IEEE 1580 as Marine ShipboardCable rated 600/1000 volts.• Passes the IEEE 383-1974 and IEEE 1202Vertical Tray Flame Test.
• Passes the 210,000 BTU ICEAT-29-520Vertical Tray Flame Test.
• Complete pre-packaged, factory-tested wiringsystem; color coded.• C-L-X cables are quality control inspected tomeet or exceed applicable ULstandards.• 90°C continuous operating temperature in alltypes of installations.• 130°C emergency rating.• 250°C short circuit rating.• Good EMI shielding characteristics.• Impervious, continuous metallic sheath ex-cludes moisture, gases and liquids.
• Lower installed system cost than conduit orEMT systems.
• Provides excellent grounding safety.• Excellent compression and impact resistance.• Continuous long lengths.• Installation temperature of -40°C or °F.• Complies with NEC Articles 501, 502 and 503for hazardous locations.• American Bureau of Shipping Type approvedas CWCMC Type MC-HL.• Three symmetrical grounding conductors withthe CLX sheath provide a superior lowresistance return path for VFD and other modernac drive/motor applications.• CSAC22.2 No. 123 Type RA90.
• CSAC22.2 No. 174 Type HL.• CSAlisted as FT4 and LTGG (-40°C).• CSAType RA90 HLcomplies with CEC Zone 1,Zone 2, Class II Div 2, Class III Div 1 and Class IIIDiv 2 Hazardous Locations.
InsulationX-Olene is Okonite's trade name for its
®
chemically cross-linked polyethylene, withhigh dielectric strength.
Assembly and CoveringsThe individual conductors are cabled togetherwith non-hygroscopic fillers and a binder tapeoverall. The C-L-X sheath exceeds thegrounding conductor requirements of Table250.122 of the NEC and UL 1569. A barestranded copper grounding conductor(s),located in the outer interstices, is provided forgrounding. The impervious, continuous,welded, corrugated aluminum C-L-X sheathprovides complete protect ion againstmoisture, liquids and gases and has excellentmechanical strength. For direct burial in theground, embedment in concrete, or for areassubjected to corrosive atmospheres, the C-L-Xsheath is protected with a low temperatureblack Okoseal (PVC) jacket.
®
ApplicationsC-L-X Type MC-HL cables with the impervious,continuous, corrugated aluminum sheath arerecommended as an economical alternate to awire in conduit system. In addition, thealuminum CLX sheath exceeds the equipmentgrounding requirements of NEC Section250.118 and 250.122, and can be used as theequipment grounding conductor in non-HLareas.They are authorized for use on services,feeders and branch circuits for power, lighting,control and signaling circuits in accordancewithArticle 330 and 725 of the NEC.C-L-X Type MC-HL cables may be installedindoors or outdoors, in wet or dry locations, asopen runs of cable secured to supports spacednot more than six feet apart, in cable tray, asaerial cable on a messenger, in any approvedraceway, direct burial, or encased in concrete.C-L-X type MC-HL cables are also approvedfor Classes I, II and III, Division 1 and 2 andClass I, Zones 1 and 2 hazardous locations perNEC Articles 501, 502, 503 and 505; in Zone 1,Zone 2, Class II Div 2, Class III Div 1 and ClassIII Div 2 per CEC.
SpecificationsConductors: Uncoated soft copper per ASTMB-3. Sizes smaller than #8 are compressstranded per ASTM B-8. Sizes #8 and largerare compact stranded perASTM B-496.Insulation: X-Olene per ICEA S-95-658/NEMA WC70 and UL 44, Listed UL TypeXHHW-2. Meets MIL-DTL-1377H, section4.8.4.1.2 cold bend at -66°C and ASTM D746brittle point at -76°C.
3/C
1/0
AW
G C
OM
PA
CT
CU
600/1
000V
3X
10A
WG
CU
GR
D C
LX
VF
D(U
L)
MC
-HL
XH
HW
-2
Product DataSection 4: Sheet 1
UL®
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
▲546-31-3403▲546-31-3404
14(7X)(2.08mm²)
34
30 3#183#18
0.33 8.40.37 9.3
0.53 13.50.58 14.7
50 1.2750 1.27
0.64 16.30.69 17.5
0.320.37
160 190222 261
15 1515 15
▲546-31-3453▲546-31-3454
12(7X)(3.31mm²)
34
30 3#163#16
0.37 9.30.45 11.4
0.58 14.70.67 16.9
50 1.2750 1.27
0.69 17.50.78 19.7
0.370.47
239 278286 320
20 2020 20
▲546-31-3503▲546-31-3504
10(7X)(5.26mm²)
34
30 3#143#14
0.41 10.40.45 11.4
0.62 15.80.67 16.9
50 1.2750 1.27
0.73 18.60.78 19.7
0.420.47
300 380348 428
30 3030 28
▲571-31-3190▲571-31-3263
8(7X)(8.36mm²)
34
45 3#1410
0.50 12.70.58 14.7
0.71 18.00.80 20.3
50 1.2750 1.27
0.81 20.60.90 22.9
0.520.64
385 420465 495
55 5044 40
▲571-31-3191▲571-31-3270
6(7X)(13.3mm²)
34
45 3#128
0.58 14.70.66 16.8
0.80 20.30.89 22.5
50 1.2750 1.27
0.90 22.90.99 25.1
0.640.77
525 595630 685
75 6560 52
▲571-31-3200▲571-31-3272
4(7X)(21.2mm²)
34
45 3#128
0.68 17.30.77 19.6
0.89 22.50.97 24.7
50 1.2750 1.27
0.99 25.11.08 27.5
0.770.92
704 820845 930
95 8576 68
▲571-31-3204▲571-31-3276
2(7X)(33.6mm²)
34
45 3#106
0.80 20.30.92 23.4
1.02 25.91.15 29.2
50 1.2750 1.27
1.13 28.71.26 32.0
1.001.25
995 10501245 1370
130 115104 92
571-31-3208571-31-3280
1(19X)(42.4mm²)
34
55 3#106
0.92 23.41.04 26.4
1.15 29.21.29 32.8
50 1.2750 1.27
1.26 32.01.40 35.6
1.251.54
1100 11811500 1620
145 130116 104
▲571-31-3213571-31-3285
1/0(19X)(53.5mm²)
34
55 3#106
1.00 25.51.12 28.4
1.24 31.41.37 34.9
50 1.2750 1.27
1.34 34.01.48 37.6
1.411.72
1470 15601830 1975
170 150136 120
▲571-31-3216▲571-31-3289
2/0(19X)(67.4mm²)
34
55 3#106
1.09 27.71.23 31.2
1.34 34.01.51 38.5
50 1.2760 1.52
1.44 36.61.64 41.7
1.632.11
1770 20202310 2545
195 175156 140
▲571-31-3218571-31-3291
3/0(19X)(85.1mm²)
34
55 3#86
1.19 30.21.35 34.3
1.47 37.31.64 41.7
50 1.2760 1.52
1.58 40.11.78 45.2
1.962.49
2180 24042752 2939
225 200180 160
▲571-31-3224▲571-31-3296
4/0(19X)(107mm²)
34
55 3#84
1.33 33.81.49 37.8
1.60 40.61.78 45.2
60 1.5260 1.52
1.73 44.01.91 48.6
______
2675 28803430 3710
260 230208 184
▲571-31-3228571-31-3300
250(37X)(127mm²)
34
65 3#84
1.48 37.61.64 41.6
1.74 44.21.96 49.7
60 1.5260 1.52
1.87 47.52.09 53.0
______
3140 34204070 4330
290 255232 204
▲571-31-3236▲571-31-3308
350(37X)(177mm²)
34
65 3#73
1.66 42.21.89 48.0
1.96 49.72.19 55.6
60 1.5275 1.90
2.09 53.02.35 59.8
______
4210 43005440 6000
350 310280 248
▲571-31-3244▲571-31-3316
500(37X)(253mm²)
34
65 3#62
1.94 59.32.14 54.4
2.28 57.92.49 63.2
75 1.9075 1.90
2.44 62.02.65 67.4
______
5930 64207570 8120
430 380344 304
▲571-31-3248571-31-3320
750(61X)(380mm²)
34
80 3#51
2.37 60.22.61 66.2
2.75 69.83.03 76.9
75 1.9085 2.16
2.92 74.13.21 81.6
______
8700 940011250 12190
535 475428 380
571-31-3252571-31-3324
1000(61X)(507mm²)
34
80 1/01/0
2.67 67.73.07 78.0
3.11 79.03.63 92.1
85 2.1685 2.16
3.30 83.83.81 96.8
______
11410 1243015110 17510
615 545492 436
Catalog Number
Conductor SizeAWG
Number of Conductors
Insulation Thickness - m
ils
Grounding Conductor(s
) AWG
CableO.D
. - mm
CableO.D
. - Inches
90ºCW
et or Dry
NECAm
pacity*
C-L-X Type MC-HL (XHHW-2)®
600/1000V Power MC-HL Cable - Aluminum Sheath3/C VFD & 4/C Copper Conductors/90°C Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
C-L-XO.D
. - Inches
C-L-XO.D
. - mm
Jacket Thickness - m
ils
Jacket Thickness - m
m
Cross-S
ectional
Area (sq. In.)†
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
75ºCW
et
NECAm
pacity*
Okonite’s web site, www.okonite.com contains the most up to date information.
Product DataSection 4: Sheet 1
UL®
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
▲546-31-3984▲571-31-3657▲571-31-3667▲571-31-3677
3X103X83X63X4
30454545
4X124X124X124X12
30303030
101088
0.75 19.00.89 22.60.93 23.60.97 24.7
0.86 21.90.99 25.11.03 26.21.08 27.5
0.580.770.830.92
425 460530 585655 720810 895
30 3055 5075 6595 85
Catalog Number
Power Conductors
Number X Size
Insulation Thickness - m
ils
Insulating Thickness - m
ils
CableO.D
. - mm
CableO.D
. - Inches
90ºCW
et or Dry
NECAm
pacity(1
)*
C-L-X Type MC-HL (XHHW-2)®
600/1000V Power MC-HL Cable - Aluminum Sheath3/C VFD & 4/C Copper Conductors/90°C Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
C-L-XO.D
. - Inches
C-L-XO.D
. - mm
Cross-S
ectional
Area (sq. In.)†
75ºCW
et
NECAm
pacity*
600/1000V Composite Power and Control Cable - Aluminum SheathOkoseal Jacket: 50 mils (1.27mm)
Control C
onductors
Number X Size
Grounding Conductor AWG
Okonite’s web site, www.okonite.com contains the most up to date information.
▲ Available from our Customer Service Centers.Authorized Stock Item.is available on special order.Copper or Bronze C-L-X
JacketsOptional jacket types available - consult local sales office.† area for calculation of cable tray fill in accordance withCross-sectionalNEC Section 392.22.
(1) AmpacitiesAmpacities are based on Table 310.16 of the National Electrical Code forXHHW-2 conductors rated 90ºC, in a multi-conductor cable, at an ambient tem-perature of 30ºC (86ºF). The 75ºC column is provided for additional information .
The ampacities shown apply to open runs of cable, installation in any approvedraceway, direct burial in the earth, or as aerial cable on a messenger.Derating for more than three current carrying conductors within the cables is inaccordance with NEC Section 310.15(C)(1).
The ampacities shown also apply to cable installed in cable tray in accordancewith NEC Section 392.80
*Current limited to 15, 20 and 30 amps per Section 240.4(D)(3) of the NEC for #14, #12 and #10 AWG, respectively.
Product DataSection 4: Sheet 1
UL®
C-L-X Type MC-HL (XHHW-2)®
600/1000V Power MC-HL Cable - Aluminum Sheath3/C VFD & 4/C Copper Conductors/90°C Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
ConductorNumber
Base Color
1234
BlackRedBlue
Orange
Purpose Base Color Tracer Color
Equipment Grounding UninsulatedGreenGreen 1 or more continuous yellow stripes
Grounded WhiteWhiteWhiteWhiteWhiteWhiteWhite
Black continuous stripeRed continuous stripeBlue continuous stripeOrange continuous stripeBrown continuous stripeNumeric Printing
Sizes 14, 12 & 10 AWG:Color Coding per ICEA Method 1, E-2 color sequence.Sizes 8 AWG and larger:Surface Printing of Numbers and colordesciptions per ICEA Method 3, E-2 color sequence.
THE OKONITE COMPANYRamsey, New Jersey 07446O/21010401
A Bare, Stranded Copper PowerConductorsX-Olene Insulation-Color Coded forBIdentificationStranded Control ConductorsC
D Non-Hygroscopic Fillers, as necessaryBinder TapeEImpervious, Continuous, WeldedFCorrugated, Aluminum Sheath
G Black Okoseal Jacket
Product DataSection 4: Sheet 2
OK
ON
ITE
SP
-OS
12
PR
16
AW
G C
U X
-OL
EN
E (
XL
PE
)
OK
ON
ITE
6 P
-OS
1 P
R 1
6A
WG
CU
X-O
LE
NE
(X
LP
E)
Control conductors are color coded black, red,
blue, yellow. When the control conductors are
within one standard AWG size of the power
conductors, the control conductors have an
additional tracer to facilitate identification.Grounding Conductor: Where indicated, baresoft copper per ASTM B-3. Stranded inaccordance with UL 1581. Meets or exceedsrequirements of NEC Table 250.122.Sheath: Close fitting, impervious, continuous,welded, corrugated aluminumC-L-X per UL 1569. In addition, the aluminumCLX sheath exceeds the equipment groundingrequirements of NEC Section 250.118 and250.122, and can be used as the equipmentgrounding conductor.Jacket: Black Okoseal (PVC) per UL 1569.Meets ASTM D746 brittle point at -40°C.
Product Features• UL Listed as Type MC cable per E38916.• UL 1309 (CWCMC) listed & UL classified inaccord with IEEE 1580 as Marine ShipboardCable rated 600/1000 volts.• UL Listed for cable tray use, direct burial andsunlight resistant.• Passes the IEEE 383-1974 and IEEE 1202vertical tray flame tests.• Passes the 210,000 BTU ICEA T-29-520Vertical Tray Flame Test.• Complete pre-packaged, factory-tested wiringsystem — color coded.• C-L-X cables are quality control inspected tomeet or exceed applicable UL standards.• 90°C continuous operating temperature in alltypes of installations.• 130°C emergency rating.• 250°C short circuit rating.• Good EMI shielding characteristics.• Impervious, continuous metallic sheathexcludes moisture, gases and liquids.• Lower installed system cost than conduit orEMT systems.• Provides excellent grounding safety.• Excellent compression and impact resistance.• Continuous long lengths.• Installation temperature of -40°C or °F.• American Bureau of Shipping Type approvedas CWCMC Type MC.• CSA C22.2 No. 123 listed as RA90, FT4 andLTGG (-40°C).• CSA Type RA90 complies with CEC Zone 2,Class II Div 2, Class III Div 1 and Class III Div 2Hazardous Locations.
InsulationX-Olene is Okonite's trade name for its
®
chemically cross-linked polyethylene, with highdielectric strength.
Assembly and CoveringsThe individual conductors are cabled togetherwith non-hygroscopic fillers, bare copperequipment grounding conductor, whereindicated, and a binder tape overall. The C-L-X sheath exceeds the grounding conductorrequirements of Table 250.122 of the NEC andUL 1569. The impervious, continuous, welded,corrugated aluminumC-L-X sheath provides complete protectionagainst moisture, liquids and gases and hasexcellent mechanical strength. For directburial in the ground, embedment in concrete,or for areas subjected to corrosiveatmospheres, the C-L-X sheath is protectedwith a low temperature black Okoseal (PVC)®
jacket.
ApplicationsC-L-X Type MC cables with the impervious,continuous, corrugated aluminum sheath arerecommended as an economical alternate to awire in conduit system.They are authorized for use on feeders andbranch circuits for power, lighting, control andsignaling circuits in accordance with Article 330and 725 of the NEC.C-L-X Type MC cables may be installedindoors or outdoors, in wet or dry locations, asopen runs of cable secured to supports spacednot more than six feet apart, in cable tray, asaerial cable on a messenger, in any approvedraceway, direct burial, or encased in concrete.C-L-X type MC cables are also approved foruse in Class I & II, Division 2, Class III,Divisions 1 and 2 and Class I, Zone 2hazardous locations per NEC Articles 501,502, 503 and 505; in Zone 2, Class II Div 2,Class III Div 1 and Class III Div 2 per CEC.
SpecificationsConductors: Uncoated soft copper per ASTMB-3. Sizes smaller than #8 are compressedstranded per ASTM B-8. Sizes #8 and largerare compact stranded per ASTM B-496.Insulation: X-Olene per ICEA S-95-658/NEMA WC-70, ICEA S-73-532/NEMA WC57,and UL 44, Listed UL Type XHHW-2. MeetsMIL-DTL-1377H, section 4.8.4.1.2 cold bond at-66°C and ASTM D746-04 brittle point at -76°C.Conductor Identification: Conductors 9 AWGand smaller are color coded black, red, blue,orange. Power conductors #8 AWG and largerare black with printed number/color coded.
C-L-X Type MC (XHHW-2)600/1000V Composite Power and Control MC Cable-Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
®UL®
MC
XH
HW
-2 6
00/1
000V
3/C
8A
WG
4/C
12
AW
G
A
B
E
F
C
D
G
Product DataSection 4: Sheet 2
L/20120402
THE OKONITE COMPANYRamsey, New Jersey 07446
C-L-X Type MC (XHHW-2)600/1000V Composite Power and Control MC Cable-Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct BurialX-Olene Insulation: #14 Through #10 AWG, 30 mils (0.76mm); #8 Through #2 AWG, 45 mils (1.14mm)Okoseal Jacket: 50 mils (1.27mm)
®
UL®
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
546-31-3983546-31-3927546-31-3950546-31-3925
3X123X124X124X12
3X144X143X144X14
―———
0.71 18.00.71 18.00.71 19.10.75 19.1
0.82 20.80.82 20.80.82 20.80.86 21.8
0.530.530.530.58
304 374320 390328 309281 351
20 2020 2020 2020 20
546-31-3758546-31-3992546-31-3990
▲ 546-31-3984
3X103X103X103X10
3X144X143X124X12
———10
0.75 19.10.80 20.30.75 19.10.75 19.1
0.86 21.80.91 23.10.86 21.80.86 21.8
0.580.650.580.58
358 428388 453296 366430 465
30 2030 3030 3030 30
546-31-3956546-31-3987546-31-3988546-31-3958
4X104X104X104X10
3X144X143X124X12
————
0.80 20.30.80 20.30.80 20.30.80 20.3
091 23.10.91 23.10.91 23.10.91 23.1
0.650.650.650.65
408 473424 489432 497455 520
30 2830 2830 2830 28
571-31-3192571-31-3661571-31-3664571-31-3665
3X83X83X83X8
3X144X143X124X12
————
0.80 20.30.84 21.30.80 20.30.84 21.3
0.91 23.10.95 24.10.91 23.10.95 24.1
0.650.710.650.71
420 500450 530450 530490 570
55 5055 5055 5055 50
▲ 571-31-3657571-31-3682571-31-3960571-31-3683
3X84X84X84X8
4X123X144X143X12
10———
0.89 22.60.84 21.30.89 22.60.89 22.6
0.99 25.10.95 24.11.00 25.41.00 25.4
0.770.710.790.79
530 585500 580525 605530 615
55 5044 4044 4044 40
571-31-3680571-31-3686571-31-3666571-31-3673
4X83X63X63X6
4X123X144X143X12
————
0.93 23.60.84 21.30.84 21.30.84 21.3
1.04 26.40.95 24.10.95 24.10.95 24.1
0.850.710.710.71
570 650520 600540 620550 630
44 4075 6575 6575 65
571-31-3668▲ 571-31-3667
571-31-3968571-31-3684
3X63X64X64X6
4X124X123X144X14
—8——
0.93 23.60.93 23.60.93 23.60.93 23.6
1.03 26.21.03 26.21.04 26.41.04 26.4
0.830.830.850.85
600 680655 720650 730660 740
75 6575 6560 5260 52
571-31-3685571-31-3965571-31-3655571-31-3970
4X64X63X43X4
3X124X123X144X14
————
0.97 24.60.97 24.60.93 23.60.93 23.6
1.08 27.41.08 27.41.04 26.41.04 26.4
0.920.920.850.85
680 760710 790700 780720 800
60 5260 5295 8595 85
571-31-3671571-31-3974
▲ 571-31-3677571-31-3688
3X43X43X44X4
3X124X124X123X14
——8—
0.93 23.60.97 24.60.97 24.71.06 26.9
1.04 26.41.08 27.41.08 27.51.17 29.7
0.850.920.921.08
720 800760 840810 895890 970
95 8595 8595 8576 68
571-31-3669571-31-3670571-31-3672571-31-3203
4X44X44X43X2
4X143X124X123X14
————
1.06 26.91.06 26.91.06 26.91.06 26.9
1.17 29.71.17 29.71.17 29.71.17 29.7
1.081.081.081.08
920 1000920 1000950 1030985 1065
76 6876 6876 68
130 115
571-31-3674571-31-3675571-31-3505571-31-3506
3X23X23X24X2
4X143X124X123X14
————
1.06 26.91.06 26.91.06 26.91.15 29.2
1.17 29.71.17 29.71.17 29.71.26 32.0
1.081.081.081.25
1000 10801010 10901040 11151230 1320
130 115130 115130 115104 92
571-31-3507571-31-3508571-31-3509
4X24X24X2
4X143X124X12
———
1.15 29.21.15 29.21.15 29.2
1.26 32.01.26 32.01.26 32.0
1.251.251.25
1250 13401260 13501280 1370
104 92104 92104 92
Catalog Number
Power Conductors
Number X Size
Control C
onductors
Number X Size
Grounding Conductor
AWGC-L-X
O.D. -
mm
C-L-XO.D
. - Inches
CableO.D
. - mm
CableO.D
. - Inches
Cross-S
ectional
Area (sq. in.)†
90ºCW
et or Dry
NECAm
pacity(1
)*
75ºCW
et
NECAm
pacity*
Okonite’s web site, www.okonite.com contains the most up to date information.
▲ Available fromAuthorized Stock Item.our Customer Service Centers.These stock items are listed as MC-HLCopper or Bronze C-L-X is availableon special order.JacketsOptional jacket types - consult local sales office.† area for calculation of cableCross-sectionaltray fill in accordance with NEC Section 392.22.
(1) AmpacitiesAmpacities are based on Table 310.16 of theNational Electrical Code for XHHW-2 conductorsrated 90ºC, in a multi-conductor cable, at anambient temperature of 30ºC (86ºF). The 75ºCcolumn is provided for additional information .
The ampacities shown apply to open runs ofcable, installation in any approved raceway,direct burial in the earth, or as aerial cable on amessenger.Derating for more than three current carryingconductors within the cables is in accordancewith NEC Section 310.15(C)(1).
The ampacities shown also apply to cableinstalled in cable tray in accordance withNEC Section 392.80
*Current limited to 15, 20 and 30 amps per Section 240.4(D) of the NEC for #14, #12 and #10 AWG, respectively.
A
B
E
D
C
InsulationOkonite-FMR is Okonite’s trade name for itsheat, moisture, flame and chemical resistant,mechanically rugged ethylene-propylene in-sulating compound.The properties of Okonite-FMR insulationsubstantially enhance the well known fea-tures of ethylene-propylene rubber insula-tions.
Overall JacketThe Okoseal (PVC) jacket is mechanicallyrugged and has excellent resistance to mostchemicals.
ApplicationsOkonite-FMR Okoseal Type TC-ER tray ca-ble is permitted for use on power, lighting,control, and signal circuits; indoors or out-doors; in cable trays, raceways, direct burialin the ground, or where supported in outdoorlocations by a messenger wire; for Class 1circuits as permitted in Article 725 of theNEC; and in cable trays in Class I, Division 2hazardous locations in industrial establish-ments where the conditions of maintenanceand supervision assure that only qualifiedpersons will service the installation. Cablesmarked TC-ER may also be used between acable tray and the utilization equipment ordevice, when installed in accordance withNEC 336.10(7).As Type Oko-Marine cable, it is suitable foruse in marine shipboard and off-shore plat-form applications in accordance with API andABS requirements.
SpecificationsConductors: Uncoated soft copper perASTM B-3. Sizes smaller than #8 are com-press stranded per ASTM B-8. Sizes #8 andlarger are compact stranded per ASTMB-496.Insulation: Okonite-FMR meets or exceedsrequirements of UL 1581, ICEA S-73-532(NEMA WC57) and ICEA S-95-658 NEMAWC70 Type II insulation.Color Coding: Base colors and tracers asshown on reverse of Data Sheet and forsizes #8 AWG and larger black conductorswith surface printing of numbers per ICEAS-73-532 NEMA/WC57 Method 4.Grounding Conductor: Where indicated,bare stranded copper per ASTM B-8, orcompact round per ASTM B-496, Class B &NEC Table 250.122.
Assembly: Conductors cabled in accor-dance with UL 1277 and 1309 using fill-ers, as necessary, with a cable tapeoverall.Overall Jacket: Complies with UL 1277and 1309. The Okoseal compound meetsor exceeds the requirements of UL 1581.UL Listed as Type TC or TC-ER cablewith a sunlight resistant low temperaturejacket and for direct burial and TypeOko-Marine cable.Sizes 4 AWG and larger without agrounding conductor are Type TC only(not ER).
Product FeaturesInsulated conductors are UL ratedXHH/XHHW-2, cUL rated RW75/RW90,VW-1, PR I, and -40�C.90°C continuous rating in wet or drylocations130°C emergency overload rating250°C short circuit rating.Okonite-FMR Okoseal Type TC-ER andOko-Marine cables are quality control in-spected to meet or exceed applicable in-dustry standards.Resistant to moisture and most chemicalatmospheres.Thermal stability at elevated tempera-tures.Flexible, easy to install and terminate.High dielectric strength.Installation Temperature -40°C.
Applicable Standards• UL listed for cable tray use, directburial, in ducts, and sunlight resistant.• Vertical Tray Flame Tests;IEEE 383-1974, FT4/IEEE 1202, UL1277, Sizes 250 kcmil and larger meetICEA T-29-520 (210,000 BTU/hr).• OSHA Acceptable• UL 1309-Oko-Marine• UL certified to IEEE 1580 - MarineShipboard Cable rated 600/1000V.• ABS Type approved; API-RP-14F,IEEE 1202, 46 CFR 111.60.• CSA C22.2 No. 239 Type CIC for sizes4/0 AWG and smaller.• CSA C22.2 No. 230 Type TC-ER forsizes 14 through 4/0 AWG.• 1000V CSA Type CIC available forsizes 4/0 AWG and smaller.
Okonite-FMR® Okoseal®UL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC-ER600V Power & ControlTray Cable or Oko-Marine Cable 600/1000VMultiple Copper Conductors With or WithoutGrounding Conductor/90°C Wet or DryFor Cable Tray Use - Sunlight Resistant - For Direct Burial
Product DataSection 4: Sheet 5
A Stranded Copper ConductorsB Okonite-FMR InsulationC Fillers, as necessaryD Binder TapeE Okoseal Jacket — Black
ULR
AW
GC
UO
KO
NIT
E-F
MR
PV
C60
0V
c ULR
UL TYPE: TC-ER
�202-10-3203�202-10-3204
14(7X)
34
30
——
4545
1.141.14
0.400.44
10.211.2
0.130.16
104126
127149
1515
1515
�202-10-3205�202-10-3207
202-10-3209
579
———
454560
1.141.141.52
0.480.520.63
12.213.216.0
0.180.220.32
151195260
174218292
151515
151414
�202-10-3212�202-10-3219�202-10-3237
121937
———
606080
1.521.522.03
0.710.821.14
18.020.829.0
0.400.541.03
332480925
364519
1005
121210
10108
�202-10-3403�202-10-3443
12(7X)
33
30
—12*
4545
1.141.14
0.440.48
11.212.2
0.160.18
134162
157185
2020
2020
�202-10-3404�202-10-3405�202-10-3407
457
———
454560
1.141.141.52
0.480.520.60
12.213.215.2
0.190.220.29
167202281
190225305
202020
202017
�202-10-3409�202-10-3412�202-10-3419
202-10-3437
9121937
————
60608080
1.521.522.032.03
0.700.780.951.26
17.819.824.132.0
0.390.490.731.27
363446697
1266
395485752
1266
20151512
17121210
�202-10-3503�202-10-3543�202-10-3504
202-10-4505202-10-3505* 10(7X)
33455 30
—10*———
4545606060
1.141.141.521.521.52
0.490.530.570.620.62
12.413.514.515.715.7
0.200.230.260.310.31
183223243294294
206247267318318
3030303030
3030282828
202-10-3507202-10-3509202-10-3512
7912
———
606080
1.521.522.03
0.670.780.92
17.019.823.4
0.370.490.68
384494669
416533724
282820
242417
Okonite's web site, www.okonite.com contains the most up to date information.
ULR
Okonite-FMR Okoseal®UL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC-ER600V Power & ControlTray Cable or Oko-Marine Cable 600/1000VMultiple Copper Conductors With or WithoutGrounding Conductor/90°C Wet or DryFor Cable Tray Use - Sunlight Resistant - for Direct Burial
Product DataSection 4: Sheet 5
� Authorized stock item —Available from our Service Centers.
Equipment Grounding Conductor: Any conductor in these cables may be per-manently re-identified during installation as the equipment grounding conductorin accordance with Section 250.119(B) of the NEC.
† Cross-sectional area for calculation of cable tray fill in accordance with Sec-tion 392.22 of the NEC.
* Method 4 Color Code
(1) Ampacities
Ampacities are based on Table 310.16 of the National Electrical Code for con-ductors rated 90°C, in a multi-conductor cable, at an ambient temperature of30°C (86°F). The 75°C column is provided for additional information.
The ampacities shown apply to open runs of cable, installation in any approvedraceway, direct burial in the earth, or as aerial cable on a messenger. Deratingfor more than three current carrying conductors within the cable is in accor-dance with NEC Section 310.15(C)(1).
The ampacities shown also apply to cables installed in cable tray in accordancewith NEC Section 392.80.
Conductor Size
AWG/kc
mil
Number
of Conductors
Groundin
gConduct
or AWG
Catalo
gNum
ber
Jack
etThick
ness (m
ils)
90°C
Wet
or Dry
NECAm
pacity
(1)*
Jack
etThick
ness (m
m)
Cross
-Sec
tional
Area (s
q. In.)
�
Approx.
O.D. (
In.)
Approx.
NetW
eight
lbs./
1000
’
Approx.
ShipW
eight
lbs./
1000
’
Approx.
O.D. (
mm
)
Insu
latio
nThick
ness (m
ils)
c ULR
75°C
Wet
NECAm
pacity
(1)*
*Current limited to 15, 20 and 30 amps per Section 240.4(D) of the NEC for #14, #12 and #10 AWG, respectively.
112-10-3842� 112-10-3844
112-10-3845112-10-3847
8(7X) TC-ER
3344
45
—10*—10*
60606060
1.521.521.521.52
0.640.700.700.73
16.317.817.818.5
0.320.380.380.42
273349352412
305388391451
55554545
50504040
112-10-3852� 112-10-3854
112-10-3855112-10-3857
6(7X) TC-ER
3344
45
—8*—8*
60606060
1.521.521.521.52
0.720.760.790.83
18.319.320.121.1
0.410.450.490.54
382437493582
421469532637
75756060
65655252
112-10-3862� 112-10-3864
112-10-3865112-10-3867
4(7X)
TCTC-ER
TCTC-ER
3344
45
—8*—8*
60808080
1.522.032.032.03
0.810.840.941.00
20.621.323.925.4
0.520.550.690.79
549696750891
588751805955
95957676
85856868
112-10-3872� 112-10-3874
112-10-3875112-10-3877
2(7X)
TCTC-ER
TCTC-ER
3344
45
—6—6
80808080
2.032.032.032.03
0.990.991.091.12
25.125.127.728.4
0.770.770.930.99
888941
11331242
952100512001322
130130104104
115115
9292
112-10-3882112-10-3884112-10-3885112-10-3887
1(19X)
TCTC-ER
TCTC-ER
3344
55
—6—6
80808080
2.032.032.032.03
1.101.101.211.21
27.927.930.730.7
0.950.951.151.15
1103118014341505
1170124715341605
145145116116
130130104104
112-10-3892� 112-10-3894
112-10-3895112-10-3897
1/0(19X)
TCTC-ER
TCTC-ER
3344
55
—6—6
80808080
2.032.032.032.03
1.181.181.301.23
30.030.033.031.2
1.091.091.331.19
1330141017411812
1410149018411912
170170136136
150150120120
112-10-3902� 112-10-3904
112-10-3905112-10-3907
2/0(19X)
TCTC-ER
TCTC-ER
3344
55
—6—6
80808080
2.032.032.032.03
1.271.271.401.40
32.332.335.635.6
1.271.271.541.54
1632171121142186
1732181122302302
195195156156
175175140140
112-10-3922� 112-10-3924
112-10-3925112-10-3927
4/0(19X)
TCTC-ER
TCTC-ER
3344
55
—4—4
80808080
2.032.032.032.03
1.481.481.641.64
39.439.450.050.0
————
2462257632063320
2605271933833497
260260208208
230230184184
112-10-3928112-10-3929112-10-3930112-10-3931
250(37X)
TCTC-ER
TCTC-ER
3344
65
—4—4
8080
110110
2.032.032.792.79
1.621.621.861.86
44.744.749.349.3
————
2904302938934000
3047320641594265
290290232232
255255204204
112-10-3932� 112-10-3933
112-10-3934112-10-3935
350(37X)
TCTC-ER
TCTC-ER
3344
65
—3—3
110110110110
2.792.792.792.79
1.891.892.082.08
50.350.355.655.6
————
3995416452435394
4261443055905741
350350280280
310310248248
112-10-3936� 112-10-3937
112-10-3938112-10-3939
500(37X)
TCTC-ER
TCTC-ER
3344
65
—2—2
110110110110
2.792.792.792.79
2.142.142.372.37
57.457.463.563.5
————
5549574372377425
5939613377967984
430430344344
380380304304
112-10-3940112-10-3941112-10-3942112-10-3943
750(61X)
TCTC-ER
TCTC-ER
3344
80
—1—1
110110140140
2.792.793.563.56
2.582.582.922.92
68.668.676.576.5
————
82778515
1094211157
89049142
1170411919
535535428428
475475380380
112-10-3944112-10-3945112-10-3946112-10-3947
1000(61X)
TCTC-ER
TCTC-ER
3344
80
—1/0—1/0
140140140140
3.563.563.563.56
2.962.963.283.28
77.277.285.685.6
————
10953112371433714632
11715120001527015565
615615492492
545545436436
Note: Sizes 4 AWG & larger without a grounding conductor are type TC only (not ER rated).*Ground size marked with asterisk are green insulated. **Grounds may be split.Okonite's web site, www.okonite.com contains the most up to date information.
Product DataSection 4: Sheet 5
Approx.
NetW
eight
lbs./
1000
’
75°C
Wet
NEC
Ampac
ity(1
)
90°C
Wet
or Dry
NECAm
pacity
(1)
Approx.
ShipW
eight
lbs./
1000
’
Conductor Size
AWG/kc
mil
Number
of Conductors
Groundin
gConduct
or AWG**
ULTC
TYPE
Jack
etThick
ness (m
ils)
Jack
etThick
ness (m
m)
Insu
latio
nThick
ness (m
ils)
Cross
-Sec
tional
Area (s
q. In.)
�
Approx.
O.D. (
In.)
Approx.
O.D. (
mm
)
Catalo
gNum
ber
Okonite-FMR OkosealUL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC-ER600V Power & ControlTray Cable or Oko-Marine Cable 600/1000VMultiple Copper Conductors With or WithoutGrounding Conductor/ 90°C Wet or DryFor Cable Tray Use - Sunlight Resistant - For Direct Burial
Conductor Color Coding SequenceSizes 14, 12 & 10 AWG
Conductor Color Coding per ICEA Method 1,Number Base Color Tracer Color E-2 (except 202-10-3505 - Method 4)
1 Black Sizes 8 AWG and larger:2 Red Surface Printing of Numbers per3 Blue ICEA Method 44 Orange5 Yellow6 Brown7 Red Black8 Blue Black9 Orange Black
10 Yellow Black11 Brown Black12 Black Red13 Blue Red14 Orange Red15 Yellow Red16 Brown Red17 Black Blue18 Red Blue19 Orange Blue20 Yellow Blue21 Brown Blue22 Black Orange23 Red Orange24 Blue Orange25 Yellow Orange26 Brown Orange27 Black Yellow28 Red Yellow29 Blue Yellow30 Orange Yellow31 Brown Yellow32 Black Brown33 Red Brown34 Blue Brown35 Orange Brown36 Yellow Brown37 Black
Special Order: Any or all of the following conductors may be added when specifi-cally requested by the customer to meet their specific application requirements.These conductor codings comply with UL and NEC requirements.
Purpose Base Color Tracer Color
Equipment Grounding UninsulatedGreenGreen 1 or more continuous yellow stripes
Grounded WhiteWhiteWhiteWhiteWhiteWhiteWhite
Black continuous stripeRed continuous stripeBlue continuous stripeOrange continuous stripeBrown continuous stripeNumeric Printing
T/21070405
Product DataSection 4: Sheet 5
ULR
THE OKONITE COMPANYRamsey, New Jersey 07446
c ULR
A Uncoated Copper ConductorsX-Olene InsulationBFillers, as requiredCBlack Okoseal JacketD
Product DataSection 4: Sheet 8
OK
ON
ITE
6 P
-OS
1 P
R 1
6A
WG
CU
X-O
LE
NE
(X
LP
E)
Cable passes the Vertical Tray Flame Test
requirements of UL 1277 for Type TC Power
and Control Tray Cable.
UL Listed as Type TC or TC-ER cable with a
sunlight resistant jacket and for direct burial.
Product FeaturesInsulated conductors are UL Listed Type
XHH / XHHW-2.
90°C continuous rating in wet or dry
locations.
130°C emergency overload rating.
250°C short circuit rating.
X-Olene Okoseal Type TC or TC-ER cables
are quality control inspected to meet or
exceed applicable industry standards.
Resistant to moisture and most chemical
atmospheres.
Thermal stability at elevated temperatures.
Easy to install and terminate.
Mechanically rugged.
High dielectric strength.
Small diameter, lightweight.
Minimum installation temperature of -40°C.
Applicable Standards• UL listed for cable tray use, direct burial, in
ducts, and sunlight resistant.
• Vertical Tray Flame Tests: IEEE 383-1974,
Sizes 4/0 AWG and larger meet FT4/IEEE
1202.
• CSA C22.2 No. 239 Type CIC for sizes 4/0
AWG and smaller.
• CSA C22.2 No. 230 Type TC-ER for sizes
1-4/0 AWG.
• CSA C22.2 No. 230 Type TC for sizes
smaller than 1 AWG.
• 1000V CSA Type CIC available for sizes
4/0 AWG and smaller.
InsulationX-Olene is Okonite's trade name for its cross-®
linked polyethylene, with high dielectric strength
insulation.
JacketThe Okoseal (PVC) jacket supplied with this
cable is mechanically rugged and has excellent
resistance to acids and most chemicals and is
rated for low temperature installations.
ApplicationsOkonite X-Olene Okoseal tray cable is
permitted for use on power, lighting, control,
and signal circuits; indoors or outdoors; in cable
trays, raceways, direct burial in the ground, or
where supported in outdoor locations by a
messenger wire; for Class 1 circuits as
permitted in Article 725 of the NEC; and in
cable trays in Class I, Division 2 hazardous
locations in industrial establishments where the
conditions of maintenance and supervision
assure that only qualified persons will service
the installation. Cables marked TC-ER may
also be used between a cable tray and the
utilization equipment or device, when installed
in accordance with NEC 336.10(7).
SpecificationsConductors: Uncoated soft copper per ASTM
B-3. Sizes smaller than #8 are compress
stranded per ASTM B-8. Sizes #8 and larger
are compact stranded per ASTM B-496.
Insulation: X-Olene insulation per UL 1581,
listed as XHHW-2.
Color Coding: Base colors and tracers as
shown on reverse of Data Sheet and, for sizes
#8 AWG and larger, black conductors with
surface printing of numbers and colors per
ICEA S-73-532 NEMA/WC57 Method 3.
Assembly: Conductors cabled in accordance
with UL 1277 using fillers and tape, as needed.
Grounding Conductor: Where indicated, bare
or insulated stranded copper in accordance
with NEC Table 250.122.
Overall Jacket: Complies with UL 1277. The
Okoseal compound meets or exceeds the
requirements of UL 1581.
7/C
14
AW
G C
U X
-OL
EN
E X
LP
60
0/1
00
0V
(U
L)
TC
-ER
XH
HW
-2
X-Olene -OkosealUL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC*600/1000 Volt Power and Control Tray CableMultiple Copper Conductors, 90°C Wet or DryWith or Without Grounding ConductorFor Cable Tray Use - Sunlight Resistant - For Direct Burial*cUL CIC-TC-ER sizes 1-4/0 AWG
® ® UL® ®
Product DataSection 4: Sheet 8
Catalog Number
Conductor Size
AWG/kcmil
Number of Conductors
UL TYPE
Insulation Thickeness - m
ils
Jacket Thickness - m
ils
Jacket Thickness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. C
ross-S
ectional
Area (sq. in.)†
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
90ºCW
et or Dry
NECAm
pacity(1
)*
75ºC W
et NEC
Ampacity
(1)*
▲202-31-3502▲202-31-3503▲202-31-3504
14(17X)(2.08mm²)
TCTC-ERTC-ER
234
30(0.76mm)
454545
1.141.141.14
0.37 9.40.41 10.40.43 10.9
0.110.130.15
70 85105 120120 135
15 1515 1515 15
▲202-31-3505▲202-31-3507▲202-31-3509
TC-ERTC-ERTC-ER
579
454560
1.141.141.52
0.47 11.90.50 12.70.62 15.7
0.170.200.30
132 148182 205254 278
15 1515 1415 14
▲202-31-3512202-31-3519202-31-3537
TC-ERTC-ERTC-ER
121937
606080
1.521.522.03
0.69 17.60.80 20.31.11 28.2
0.380.500.97
306 338446 485856 936
12 1012 1010 8
▲202-31-3602▲202-31-3603▲202-31-3604
12(7X)(3.31mm²)
TCTC-ERTC-ER
234
30(0.76mm)
454545
1.141.141.14
0.40 10.20.44 11.20.47 11.9
0.130.150.17
92 107139 152171 187
20 2020 2020 20
▲202-31-3605▲202-31-3607▲202-31-3609
TC-ERTC-ERTC-ER
579
456060
1.141.521.52
0.52 13.10.59 15.00.68 17.3
0.210.270.36
179 195269 293344 376
20 2020 1720 17
▲202-31-3612202-31-3619202-31-3637
TC-ERTC-ERTC-ER
121937
608080
1.522.032.03
0.77 19.60.95 24.11.24 31.5
0.470.711.21
425 464640 704
1200 1290
15 1215 1212 10
▲202-31-3702▲202-31-3703▲202-31-3704▲202-31-3705 10(7X)
(5.26mm²)
TCTC-ERTC-ERTC-ER
2345 30
(0.76mm)
45456060
1.141.141.521.52
0.45 11.40.48 12.20.56 14.20.61 15.5
0.160.180.250.29
122 138183 199242 258294 318
30 3030 3030 2830 28
▲202-31-3707202-31-3709202-31-3712
TC-ERTC-ERTC-ER
79
12
606080
1.521.522.03
0.66 16.80.77 19.60.91 23.1
0.340.470.65
378 410485 524643 698
28 2428 2420 17
X-Olene-OkosealUL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC*600/1000 Volt Power and Control Tray CableMultiple Copper Conductors, 90°C Wet or DryWith or Without Grounding ConductorFor Cable Tray Use - Sunlight Resistant - For Direct Burial*cUL CIC-TC-ER sizes 1-4/0 AWG
UL® ®
UL TYPE: TC-ER
202-31-3813▲202-31-3823▲202-31-3833
14(7X)12(7X)10(7X)
3 303 303 30
1#141#121#10
45 1.1445 1.1460 1.52
.43 10.9
.47 11.9
.56 14.2
0.150.170.25
120 135171 187242 248
15 1520 2030 30
Conductor Size
AWG/kcmil
Number of
Conductors
Catalog Number
Insulation Thickness
milsGreen Insulated
Grounding Conductor AWG
Jacket Thickness - m
ils
Jacket Thickness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. C
ross-S
ectional
Area (sq. in.)†
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
90ºCW
et or Dry
NECAm
pacity(1
)*
75ºC W
et NEC
Ampacity
(1)*
Conductor Size
AWG/kcmil
Number of
Conductors
Catalog Number
Insulation Thickness
milsBare
Grounding Conductor AWG
Jacket Thickness - m
ils
Jacket Thickness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. C
ross-S
ectional
Area (sq. in.)†
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
90ºCW
et or Dry
NECAm
pacity(1
)*
75ºC W
et NEC
Ampacity
(1)*
UL TYPE: TC
▲202-31-3653▲202-31-3753
12(7X)10(7X)
3 303 30
1#121#10
45 1.1460 1.52
.47 11.9
.56 14.20.170.25
141 157214 230
20 2030 30
▲ Available from our Service Centers.Authorized Stock Item.
Equipment Grounding Conductor: Any conductor in TC rated cables may be permanentlyre-identified during Installation as the equipment grounding conductor in accordancewith Section 250.119(B) of the NEC.
† Cross-sectional area for calculation of cable tray fill in accordance with NEC Section 392.22.
(1) AmpacitiesAmpacities are based on Table 310.16 of the National Electrical Code forXHHW-2 conductors rated 90ºC, in a multi-conductor cable, at an ambienttemperature of 30ºC (86ºF). Derating for more than three current carryingconductors within the cable is in accordance with NEC Section 310.15(C)(1).The ampacities shown also apply to cables installed in cable tray inaccordance with NEC Section 392.80
Product DataSection 4: Sheet 8
Catalog Number
Conductor Size
AWG/kcmil
Number of Conductors
UL TYPE
Insulation Thickeness - m
ils
Jacket Thickness - m
ils
Jacket Thickness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Approx. C
ross-S
ectional
Area (sq. in.)†
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
90ºCW
et or Dry
NECAm
pacity(1
)
75ºC W
et (1)
NECAm
pacity
112-31-3734▲112-31-3735
112-31-3736112-31-3737
8(7X)(8.36mm²)
TC-ERTC-ERTC-ERTC-ER
3344
45
─10─10
60 1.5260 1.5260 1.5260 1.52
0.64 16.30.66 16.70.70 17.80.72 18.3
0.320.340.390.41
259 298313 352331 370385 424
55 5055 5044 4044 40
112-31-3746▲112-31-3747
112-31-3748112-31-3749
6(7X)(13.3mm²)
TC-ERTC-ERTC-ERTC-ER
3344
45
─8─8
60 1.5260 1.5260 1.5260 1.52
0.71 18.00.74 18.80.78 19.80.82 20.8
0.400.430.480.53
365 404440 479471 510552 616
75 6575 6560 5260 52
112-31-3758▲112-31-3759
112-31-3760112-31-3761
4(7X)(21.2mm²)
TCTC-ER
TCTC-ER
3344
45
─8─8
60 1.5260 1.5280 2.0380 2.03
0.81 20.60.81 20.60.93 23.60.96 24.4
0.520.520.680.72
527 566662 715720 784808 872
95 8595 8576 6876 68
112-31-3764▲112-31-3765
112-31-3766112-31-3767
2(7X)(33.6mm²)
TCTC-ER
TCTC-ER
3344
45
─6─6
80 2.0380 2.0380 2.0380 2.03
0.97 24.60.97 24.61.07 27.21.11 28.2
0.740.740.900.97
816 8801018 10981060 11401196 1276
130 115130 115104 92104 92
112-31-3770112-31-3771112-31-3772112-31-3773
1(19X)(42.4mm²)
TCTC-ER
TCTC-ER
3344
55
─6─6
80 2.0380 2.0380 2.0380 2.03
1.09 27.71.09 27.71.20 30.51.20 30.5
0.930.931.131.13
1051 11181127 11941355 14351431 1511
145 130145 130116 104116 104
112-31-3776▲112-31-3777
112-31-3778112-31-3779
1/0(19X)(53.5mm²)
TCTC-ER
TCTC-ER
3344
55
─6─6
80 2.0380 2.0380 2.0380 2.03
1.17 29.71.17 20.71.29 32.81.29 32.8
1.081.081.311.31
1274 13541350 14301652 17521729 1829
170 150170 150136 120136 120
112-31-3780▲112-31-3781
112-31-3782112-31-3783
2/0(19X)(67.4mm²)
TCTC-ER
TCTC-ER
3344
55
─6─6
80 2.0380 2.0380 2.0380 2.03
1.26 32.01.26 32.01.39 35.31.39 35.3
1.251.251.521.52
1561 16611639 17392033 21492109 2225
195 175195 175156 140156 140
112-31-3784▲112-31-3785
112-31-3786112-31-3787
4/0(19X)(107mm²)
TCTC-ER
TCTC-ER
3344
55
─4─4
80 2.0380 2.0380 2.0380 2.03
1.47 37.31.47 37.31.63 41.41.63 41.4
────
2361 25042488 26313101 32783222 3399
260 230260 230208 184208 184
112-31-3788112-31-3789112-31-3790112-31-3791
250(37X)(127mm²)
TCTC-ER
TCTC-ER
3344
65
─4─4
80 2.0380 2.03110 2.79110 2.79
1.62 41.21.62 41.21.85 47.01.85 47.0
────
2796 29392917 30603778 40443899 4165
290 255290 255232 204232 204
112-31-3792▲112-31-3793
112-31-3794112-31-3795
350(37X)(177mm²)
TCTC-ER
TC-TC-ER
3344
65
─3─3
110 2.79110 2.79110 2.79110 2.79
1.88 47.81.88 47.82.08 52.82.08 52.8
────
3889 41554044 43105091 54385245 5592
350 310350 310280 248280 248
112-31-3796▲112-31-3797
112-31-3798112-31-3799
500(37X)(253mm²)
TCTC-ER
TCTC-ER
3344
65
─2─2
110 2.79110 2.79110 2.79110 2.79
2.13 54.12.13 54.12.36 59.92.36 59.9
────
5386 57335581 59287082 76417276 7835
430 380430 380344 304344 304
112-31-3800▲112-31-3801
112-31-3802112-31-3803
750(61X)(380mm²)
TCTC-ER
TCTC-ER
3344
80
─1─1
110 2.79110 2.79140 3.56140 3.56
2.56 65.02.56 65.02.90 73.72.90 73.7
────
7961 85208206 8833
10632 1139410879 11641
535 475535 475428 380428 380
112-31-3804112-31-3805112-31-3806112-31-3807
1000(61X)(507mm²)
TCTC-ER
TCTC-ER
3344
80
─1/0─
1/0
140 3.56140 3.56140 3.56140 3.56
2.93 74.42.93 74.43.25 82.63.25 82.6
────
10584 1134610894 1165613925 1485814235 15168
615 545615 545492 436492 436
Okonite’s web site, www.okonite.com contains the most up to date information.
Grounding Conductor AWG
NOTE: Sizes 4 AWG & larger without a grounding conductor are Type TC only (Not ER rated).
Product DataSection 4: Sheet 8
UngroundedConductor
NumberBase Color Tracer Color
123456789
10111213141516171819202122232425262728293031323334353637
BlackRedBlue
OrangeYellowBrownRedBlue
OrangeYellowBrownBlackBlue
OrangeYellowBrownBlackRed
OrangeYellowBrownBlackRedBlue
YellowBrownBlackRedBlue
OrangeBrownBlackRedBlue
OrangeYellowBlack
BlackBlackBlackBlackBlackRedRedRedRedRedBlueBlueBlueBlueBlue
OrangeOrangeOrangeOrangeOrangeYellowYellowYellowYellowYellowBrownBrownBrownBrownBrown
Conductor Color Coding Sequence
Color CodingSizes 14,12 & 10 AWG:per ICEA Method 1, E-2 color sequence
Sizes 8 AWG and larger:Surface Printing of Numbers and colordesignation per ICEA Method 3, E-3color sequence
Special Order: Any or all of the following conductors may be added whenspecifically requested by the customer to meet their specific applicationrequirements. These conductor codings comply with UL and NEC require-ments.
THE OKONITE COMPANYRamsey, New Jersey 07446O/20120408
X-Olene-OkosealUL Type TC/TC-ER (XHH/XHHW-2) and cUL CIC-TC*600/1000 Volt Power and Control Tray CableMultiple Copper Conductors, 90°C Wet or DryWith or Without Grounding ConductorFor Cable Tray Use - Sunlight Resistant - For Direct Burial*cUL CIC-TC-ER sizes 1-4/0 AWG
UL® ®
Purpose Base Color Tracer Color
Equipment Grounding UninsulatedGreenGreen 1 or more continuous yellow stripes
Grounded WhiteWhiteWhiteWhiteWhiteWhiteWhite
Black continuous stripeRed continuous stripeBlue continuous stripeOrange continuous stripeBrown continuous stripeNumeric Printing
A Bare, Stranded Copper ConductorsX-Olene Insulation-Color Coded forBIdentificationMarker TapeC
D Non-Hygroscopic Fillers, as necessaryBinder TapeEImpervious, Continuous, Corrugated,FAluminum C-L-X Sheath
G Black Okoseal Jacket
Product DataSection 4: Sheet 14
OK
ON
ITE
6 P
-OS
1 P
R 1
6A
WG
CU
X-O
LE
NE
(X
LP
E)
C-L-X Type MC (XHHW-2)600/1000V Control Cable - Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
®UL®
Sheath: Close fitting, impervious, continuous,corrugated aluminum C-L-X per UL 1569.In addition, the aluminum CLX sheathexceeds the equipment groundingrequirements of NEC Section 250.118 and250.122, and can be used as the equipmentgrounding conductor.Jacket: Black Okoseal (PVC) per ULrequirements for Type MC Cables. MeetsASTM D746-04 brittle point at -40°C.
Product Features• UL Listed as Type MC cable and MarineShipboard Cable, E38916 (UL 1569) andE137931 (UL 1309).• UL Listed for cable tray use, direct burial andsunlight resistant.• UL 1309 (CWCMC) listed & UL classified inaccord with IEEE 1580 as Marine ShipboardCable rated 600/1000 volts.• Passes the IEEE 383-1974 and IEEE1202/FT4 vertical tray flame tests.• Passes the 210,000 BTU/hr ICEAT-29-520 Vertical Tray Flame Test.• Complete pre-packaged, factory-testedwiring system — color coded.• C-L-X cables are quality control inspected tomeet or exceed applicable UL standards.• 90°C continuous operating temperature in alltypes of installations• 130°C emergency rating• 250°C short circuit rating.• Good EMI shielding characteristics.• Impervious, continuous metallic sheathexcludes moisture, gases and liquids.• Lower installed system cost than conduit orEMT systems.• Provides excellent grounding safety• Excellent compression and impactresistance.• Continuous long lengths.• Installation temperature of -40°C or °F.• UL and American Bureau of Shipping Typeapproved as CWCMC Type MC.• CSA C22.2 No. 123 listed as RA90, FT4 andLTGG (-40°C).• CSA Type RA90 complies with CEC Zone 2,Class II Div 2, Class III Div 1, Class III Div 2Hazardous Locations.
InsulationX-Olene is Okonite's trade name for its
®
chemically cross-linked polyethylene, with highdielectric strength.
Color CodingConductors are color coded using base colorsand tracers in accordance with the ConductorIdentification Table on the back of this DataSheet.
Assembly and CoveringsThe individual conductors are cabled togetherwith non-hygroscopic fillers and a binder tapeoverall. The C-L-X sheath exceeds thegrounding conductor requirements of Table250.122 of the NEC and UL 1569.The impervious, continuous, corrugatedaluminum C-L-X sheath provides completeprotection against moisture, liquids and gasesand has excellent mechanical strength. Fordirect burial in the ground, embedment inconcrete, or for areas subjected to corrosiveatmospheres, the C-L-X sheath is protectedwith a low temperature black Okoseal (PVC)
®
jacket.
ApplicationsC-L-X Type MC cables with the impervious,continuous, corrugated aluminum sheath arerecommended as an economical alternate to awire in conduit system.They are authorized for use on services,feeders and branch circuits for power, lighting,control and signaling circuits in accordancewith Articles 330 and 725 of the NEC.C-L-X Type MC cables may be installedindoors or outdoors, in wet or dry locations, asopen runs of cable secured to supports spacednot more than six feet apart, in cable tray, asaerial cable on a messenger, in any approvedraceway, direct burial, or encased in concrete.C-L-X Type MC cables are also approved foruse in Class I & II, Division 2, Class III,Divisions 1 and 2, and Class I, Zone 2hazardous locations per NEC articles 501,502, 503 and 505; in Zone 2, Class II Div 2,Class III Div 1 and Class III Div 2 per CEC.
SpecificationsConductors: Bare soft annealed copper,Class B stranding per ASTM B-8.Insulation: X-Olene per ICEA S-73-532/NEMA WC57 and UL 44, Listed UL TypeXHHW-2. Meets MIL-DTL-1377H, section4.8.4.1.2 cold bend at -66°C and ASTM D746-04 brittle point at -76°C.Conductor Identification: Base Colors andtracers.Assembly: Per UL 1569 with binder tapeoverall.
A
B
E
F
D
G
C
600/1
000V
7/C
12
AW
G C
U
Product DataSection 4: Sheet 14
UL®
▲ 546-31-3002▲ 546-31-3003▲ 546-31-3004
14(7X)(2.08mm²)
234
30(0.76mm)
0.280.300.33
7.17.68.4
0.490.490.53
12.312.413.5
50 1.27
0.600.600.64
15.115.216.3
0.280.320.36
142153181
174185214
151515
151515
▲546-31-3005▲546-31-3007▲546-31-3009
579
0.370.410.50
9.410.412.7
0.580.620.71
14.715.718.0
0.690.730.82
17.518.520.8
0.410.460.57
210254308
242309363
151515
151414
▲546-31-3012▲546-31-3019▲546-31-3037
121937
0.570.690.96
14.417.524.4
0.800.931.24
20.323.631.5
0.911.041.35
23.126.434.3
0.710.841.43
381537946
448604
1036
121210
10108
546-31-3082▲546-31-3083▲546-31-3084
12(7X)(3.31mm²)
234
30(0.76mm)
0.310.340.38
7.88.69.6
0.530.530.58
13.513.514.7
50 1.27
0.640.640.69
16.316.317.5
0.320.320.38
164189226
196221258
202020
202020
▲546-31-3085▲546-31-3087▲546-31-3089
579
0.420.470.56
10.611.914.2
0.620.670.80
15.717.020.3
0.730.780.91
18.519.823.1
0.420.480.65
262324405
317379472
202020
201717
▲546-31-3092▲546-31-3099▲546-31-3117
121937
0.650.781.08
16.519.827.4
0.891.021.37
22.625.934.8
0.991.131.48
25.428.737.6
0.791.001.72
503721
1301
570801
1444
151512
121210
▲546-31-3162▲546-31-3163▲546-31-3164
10(7X)(5.26mm²)
234
30(0.76mm)
0.360.390.44
9.19.9
11.1
0.580.580.67
14.714.717.0
50 1.27
0.690.690.78
17.517.519.8
0.380.380.48
202238297
234270352
303030
303028
0.820.861.001.08
20.821.825.427.4
0.530.580.790.85
348436544684
403491611751
30282820
28242417
546-31-3165▲546-31-3167
546-31-3169546-31-3172
579
12
0.480.540.650.74
12.213.716.518.8
0.710.750.890.97
18.019.122.624.6
Catalog Number
Conduct Size
AWG
Insulation
Thickness - mils
Okonite’s web site, www.okonite.com contains the most up to date information.
*Current limited to 15, 20 and 30 amps per Section 240.4(D) of the NEC for #14, #12 and #10 AWG, respectively.
C-L-X Type MC (XHHW-2)600/1000V Control Cable - Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
®
Number of Conductors
CoreO.D
. - Inches
CoreO.D
. - mm
C-L-XO.D
. - Inches
C-L-XO.D
. - mm
Jacket Thickness - m
ils
Jacket Thickness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Cross-S
ectional
Area (sq. in.)†
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
90ºCW
et or Dry
(1)
NECAm
pacity
75ºCW
et
NECAm
pacity*
▲ Available from our Customer Service Centers.Authorized Stock Item.
- is available on special order.Copper or Bronze C-L-X
† area for calculation of cable tray fill in accordance with NEC Section 392.22.Cross-sectional
Optional jacket types available - consult local sales office.Jackets -
(1) AmpacitiesAmpacities are based on Table 310.16 of the National Electrical Code forXHHW-2 conductors rated 90ºC, in a multi-conductor cable, at an ambienttemperature of 30ºC (86ºF). The 75ºC column is provided for additionalinformation .
The ampacities shown apply to open runs of cable, installation in anyapproved raceway, direct burial in the earth, or as aerial cable on amessenger. Derating for more than three current carrying conductorswithin the cable is in accordance with NEC Section 310.15(C)(1).
The ampacities shown also apply to cables installed in cable tray inaccordance with NEC Section 392.80
C-L-X Type MC (XHHW-2)600/1000V Control Cable - Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
®
UL®
Product DataSection 4: Sheet 14
ConductorNumber Base Color Tracer Color
123456789
10111213141516171819202122232425262728293031323334353637
BlackRedBlue
OrangeYellowBrownRedBlue
OrangeYellowBrownBlackBlue
OrangeYellowBrownBlackRed
OrangeYellowBrownBlackRedBlue
YellowBrownBlackRedBlue
OrangeBrownBlackRedBlue
OrangeYellowBlack
BlackBlackBlackBlackBlackRedRedRedRedRedBlueBlueBlueBlueBlue
OrangeOrangeOrangeOrangeOrangeYellowYellowYellowYellowYellowBrownBrownBrownBrownBrown
Conductor Color Coding Sequence
Color Coding per ICEAMethod 1, E-2
Special Order: Any or all of the following conductors may be added whenspecifically requested by the customer to meet their specific applicationrequirements. These conductor codings comply with UL and NEC require-ments.
Purpose Base Color Tracer Color
Equipment Grounding UninsulatedGreenGreen 1 or more continuous
yellow stripes
Grounded WhiteWhiteWhiteWhiteWhite
WhiteWhite
Black continuous stripeRed continuous stripeBlue continuous stripeOrange continuousstripeBrown continuousstripeNumeric printing
THE OKONITE COMPANYRamsey, New Jersey 07446N/21010414
A Bare, Stranded Copper ConductorsX-Olene Insulation-Color Coded forBIdentificationStranded copper, green insulatedCgrounding conductorMarker TapeD
E Non-Hygroscopic Fillers, as necessaryBinder TapeFImpervious, Continuous, Corrugated,GAluminum C-L-X Sheath
H Black Okoseal Jacket
Product DataSection 4: Sheet 15
OK
ON
ITE
SP
-OS
12
PR
16
AW
G C
U X
-OL
EN
E (
XL
PE
)
OK
ON
ITE
6 P
-OS
1 P
R 1
6A
WG
CU
X-O
LE
NE
(X
LP
E)
C-L-X Type MC-HL (XHHW-2)600/1000V Control Cable - Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
®UL®
MC
XH
HW
-2 6
00V
3/C
8A
WG
4/C
12
AW
G
InsulationX-Olene is Okonite's trade name for its chemically
®
cross-linked polyethylene, with high dielectric
strength.
Color CodingConductors are color coded using base colors and
tracers in accordance with the Conductor
Identification Table on the back of this Data Sheet.
Assembly and CoveringsThe individual conductors are cabled together with
non-hygroscopic fillers and a binder tape overall. The
C-L-X sheath exceeds the grounding conductor
requirements of Table 250.122 of the NEC and
UL1569.
The impervious, continuous, corrugated aluminum
C-L-X sheath provides complete protection against
moisture, liquids and gases and has excellent
mechanical strength. For direct burial in the ground,
embedment in concrete, or for areas subjected to
corrosive atmospheres, the C-L-X sheath is
protected with a low temperature black Okoseal®
(PVC) jacket.
ApplicationsC-L-X Type MC cables with the impervious,
continuous, corrugated aluminum sheath are
recommended as an economical alternate to a wire
in conduit system. In addition, the aluminum CLX
sheath exceeds the equipment grounding
requirements of NEC Section 250.118 and 250.122,
and can be used as the equipment grounding
conductor in non-HL areas.
They are authorized for use on services, feeders and
branch circuits for power, lighting, control and
signaling circuits in accordance with Articles 330 and
725 of the NEC.
C-L-X Type MC-HL cables may be installed indoors
or outdoors, in wet or dry locations, as open runs of
cable secured to supports spaced not more than six
feet apart, in cable tray, as aerial cable on a
messenger, in any approved raceway, direct burial,
or encased in concrete. C-L-X Type MC-HL cables
are also approved for Classes I, II , and III Division 1
and 2 and Class I, Zones 1 and 2 hazardous
locations per NEC Articles 501, 502, and 503 and UL
2225; in Zone Class II Div 2, Class III Div 1 and
Class III Div 2 per CEC.
SpecificationsConductors: Bare soft annealed copper, Class B
stranding per ASTM B-8.
Insulation: X-Olene per ICEA S-73-532 and UL 44,
Listed UL Type XHHW-2. Meets MIL-DTL-1377H,
section 4.8.4.1.2, cold bend at -66°C and ASTM
D746-04 brittle point at -40°C.
Conductor Identification: Base Colors and tracers.
Grounding Conductor: Green insulated stranded
copper per ASTM B-8, Class B. Meets or exceeds
requirements of NEC Table 250.122.
Assembly: Per UL 1569 with binder tape overall.
Sheath: Close fitting, impervious, continuous,
corrugated aluminum C-L-X per UL 1569.
Exceeds grounding conductor requirements of
NEC Table 250.122.
Jacket: Black Okoseal (PVC) per UL
requirements for Type MC-HL Cables. Meets
ASTM D746-04 brittle point at -40°C.
Product Features• UL Listed as Type MC-HL cable and Marine
Shipboard Cable, E38916 (UL 1569) and
E137931 (Ul1309).
• UL Listed for cable tray use, direct burial
and sunlight resistant.• UL 1309 listed (CWCMC) & UL classified inaccord with IEEE 1580 as Marine ShipboardCable rated 600/1000V.• Passes the IEEE 383-1974 and IEEE1202/FT4 vertical tray flame tests.• Passes the 210,000 BTU/hr ICEAT-29-520 Vertical Tray Flame Test.
• Complete pre-packaged, factory-tested
wiring system — color coded.• C-L-X cables are quality control inspected tomeet or exceed applicable UL standards.• 90°C continuous operating temperature inall types of installations.• 130°C emergency rating.• 250°C short circuit rating.• Good EMI shielding characteristics.• Impervious, continuous metallic sheathexcludes moisture, gasses and liquids.• Lower installed system cost than conduit orEMT systems.• Provides excellent grounding safety.• Excellent compression and impactresistance.• Continuous long lengths.• Installation temperature of -40°C or °F.• Complies with NEC Articles 501, 502 and503 for hazardous locations.• UL and American Bureau of Shipping listedas CWCMC Type MC-HL.
• CSA C22.2 No. 123 Type RA90.
• CSA C22.2 No. 174 Type HL.
• CSA listed as FT4 and LTGG (-40ºC).• CSA Type RA 90-HL complies with CECZone 1, Zone 2, Class II Div 2, Class III Div 1and Class III Div 2 Hazardous Locations.
D
E
F
G
H
C-H
L6
00
/10
00
V 7
/C 1
2A
WG
Product DataSection 4: Sheet 15
UL®
Catalog Number
Conductor SizeAWG
Green Insulated Grounding
Conductor AWG
Okonite’s web site, www.okonite.com contains the most up to date information.
*Current limited to 15, 20 and 30 amps per Section 240.4(D) of the NEC for #14, #12 and #10 AWG, respectively.
C-L-X Type MC-HL (XHHW-2)600/1000V Control Cable - Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
®
Number of Ungro
unded
CoreO.D
. - Inches
CoreO.D
. - mm
C-L-XO.D
. - Inches
C-L-XO.D
. - mm
Jacket Thickness - m
ils
Jacket Thickness - m
m
Approx. O
.D. -
Inches
Approx. O
.D. -
mm
Cross-S
ectional
Area (sq. in.)†
Approx. N
et Weight
lbs./1000'
Approx. S
hipWeight
lbs./1000'
90ºCW
et or Dry
(1)
NECAm
pacity
75ºCW
et NEC
Ampacity
*
▲ Available from our Customer Service Centers.Authorized Stock Item.
- is available on special order.Copper or Bronze C-L-X
† area for calculation of cable tray fill in accordance with NEC Section 392.22.Cross-sectional
Optional jacket types available - consult local sales office.Jackets -
(1) Ampacities are based on Table 310.16 of the National Electrical Code forXHHW-2 conductors rated 90ºC, in a multi-conductor cable, at an ambienttemperature of 30ºC (86ºF). The 75ºC column is provided for additionalinformation .
The ampacities shown apply to open runs of cable, installation in anyapproved raceway, direct burial in the earth, or as aerial cable on amessenger. Derating for more than three current carrying conductorswithin the cable is in accordance with NEC Section 310.15(B)(1).
The ampacities shown also apply to cables installed in cable tray inaccordance with NEC Section 392.80
▲546-31-3402▲546-31-3406▲546-31-3408
14(17X)(2.08mm²)
268
#14(7X)
0.300.410.49
7.610.412.4
0.490.620.71
12.415.818.0
50 1.27
0.600.730.82
15.218.520.8
0.280.420.53
163267321
202347401
151515
151414
▲546-31-3411▲546-31-3418▲546-31-3436
111836
0.570.690.97
14.517.524.6
0.800.931.24
20.323.631.5
0.911.041.35
23.126.434.3
0.650.851.43
395554948
475634
1038
121210
10108
▲546-31-3452▲546-31-3456▲546-31-3458
12(7X)(3.31mm²)
268
#12(7X)
0.340.470.56
8.611.914.2
0.530.670.80
13.517.020.3
50 1.27
0.640.780.91
16.319.723.1
0.320.480.65
200338426
239418506
202020
201717
▲546-31-3461▲546-31-3468▲546-31-3486
111836
0.650.781.10
16.519.827.9
0.891.021.37
22.625.934.8
1.001.131.48
25.428.737.6
0.791.001.72
519739
1302
599819
1445
151512
121210
546-31-3502▲546-31-3506
10(7X)(5.26mm²)
26
#10(7X)
0.390.54
9.913.7
0.580.75
14.719.1
50 1.27
0.690.86
17.521.8
0.370.58
253451
292531
3028
3024
▲546-31-3508▲546-31-3511
811
0.650.75
16.519.1
0.890.97
22.624.6
1.001.08
25.427.4
0.790.92
568704
648784
2820
2417
C-L-X Type MC-HL (XHHW-2)600/1000V Control Cable - Aluminum SheathMultiple Copper Conductors/90ºC Wet or Dry RatingFor Cable Tray Use - Sunlight Resistant - For Direct Burial
®
UL®
Product DataSection 4: Sheet 15
UngroundedConductor
NumberBase Color Tracer Color
123456789
10111213141516171819202122232425262728293031323334353637
BlackRedBlue
OrangeYellowBrownRedBlue
OrangeYellowBrownBlackBlue
OrangeYellowBrownBlackRed
OrangeYellowBrownBlackRedBlue
YellowBrownBlackRedBlue
OrangeBrownBlackRedBlue
OrangeYellowBlack
BlackBlackBlackBlackBlackRedRedRedRedRedBlueBlueBlueBlueBlue
OrangeOrangeOrangeOrangeOrangeYellowYellowYellowYellowYellowBrownBrownBrownBrownBrown
Conductor Color Coding Sequence
Color Coding per ICEAMethod 1, E-2
Special Order: Any or all of the following conductors may be added whenspecifically requested by the customer to meet their specific applicationrequirements. These conductor codings comply with UL and NEC require-ments.
Purpose Base Color Tracer Color
Equipment Grounding UninsulatedGreenGreen 1 or more continuous
yellow stripes
Grounded WhiteWhiteWhiteWhiteWhite
WhiteWhite
Black continuous stripeRed continuous stripeBlue continuous stripeOrange continuousstripeBrown continuousstripeNumeric printing
THE OKONITE COMPANYRamsey, New Jersey 07446M/21010415
SpecificationsConductors: Bare soft annealed copper,Class B, 7-strand concentric per ASTM B-8.
Insulation: Flame-retardant Okoseal®
(PVC) per UL 13 and UL 2250, 15 milsnominal thickness, 105°C temperaturerating.
Conductor Identification: Pigmentedblack and white in pairs, black, red andwhite in triads.
Assembly: Pair or triad assembled with left-hand lay.
Cable Shield: Aluminum/synthetic polymertape overlapped to provide 100% coverage,and a 7-strand tinned copper drain wire.
Jacket: Black, flame-retardant, lowtemperature Okoseal per UL 13 and UL2250. A rip cord is laid longitudinally underthe jacket to facilitate removal.
ClassificationsUL Listed as ITC/PLTC — Instrument TrayCable/Power Limited Tray Cable for use inaccordance with Article 727 and Article 725of the National Electrical Code.
These cables comply with UL 2250 and UL13 for PLTC, CL2, and CL3.
ApplicationsOkonite type P-OS (Pair/Triad - OverallShield) instrumentation cables are de-signed for use as instrumentation,process control, and computer cables inITC non-classified or labeled circuits upto 150 volts and 5 amps (750VA) and inClass 2 or 3 Power-Limited circuitswhere shielding against external inter-ference is required, but shieldingagainst interference among groups isnot required; indoors or outdoors; in wetor dry locations with conductor operat-ing temperatures up to 105°C; in cabletrays; in raceways; supported by a mes-senger wire. Suitable Class I, Division2, Class II, Division 2, or Class III, Divi-sion 2 hazardous locations. Also for useas Power-Limited fire protective signal-ing cable (FPL) per NEC Code 760.
The overall shield eliminates most ofthe static interference from the elec-tric field radiated by power cablesand other electrical equipment.
For dc service in wet locations, X-Olene®
insulation is recommended.
Product Features• Passes the UL 1581 & IEEE 383-1974 vertical tray flame tests.
• Sunlight resistant and oil resistant.
• Individual pairs or triads are colorcoded for simplified hook-up.
• Good noise rejection.
• Excellent weathering characteristics.
• OSHA Acceptable.
• Flexible, easy to handle and terminate.
• Twisted with 100% shield coverage toreduce electromagnetic noise pick-up.
• Suitable for low temperature installa-tion of -40°C.
Type P-OSType ITC/PLTC Instrumentation CableSingle Pair or Triad - Overall Shield300 Volts - 105°C RatingFor Cable Tray Use
A Bare Stranded CopperConductor
B Okoseal InsulationC Twisted Pair/TriadD Tinned Stranded Copper Drain WireE Aluminum/Polyester TapeF Rip CordG Black Okoseal Jacket
Product DataSection 5: Sheet 2
ULR
(UL
)T
YP
EIT
C/P
LT
C10
5°c
G
A
B
C
D
E
F
Okoseal Insulation 15 mils
264-10-1101264-15-1101 22
11 12
35
0.200.21
0.030.03
2226
2731
264-10-2201264-15-2201 20
11 12
0.220.23
0.040.04
2733
3238
� 264-10-3301� 264-15-3301 18
11 15
0.230.24
0.050.05
3543
4048
� 264-10-4401264-10-4901*
� 264-15-440116
11
115
0.250.250.26
0.050.050.06
474758
525259
* Tinned Copper Conductor
� Authorized Stock Item: Available from our Customer Service Center.
� Cross-sectional area for calculation of cable tray fill in accordancewith NEC Section 392-22
Length Tolerance: Cut lengths of 1000 feet or longer are subject to atolerance of � 10%; less than 1000 feet � 15%.
G/17100502
ULR
Type P-OSType ITC/PLTC Instrumentation CableSingle Pair or Triad - Overall Shield 300V - 105°C RatingFor Cable Tray Use
Product DataSection 5: Sheet 2
ELECTRICAL SPECIFICATIONSPer UL Standard 13 & 2250
Conductor Resistance, nominal .............ohms/1000 ft. @20°C
22 AWG ............................................................... 16.520 AWG................................................................. 10.318 AWG................................................................... 6.516 AWG................................................................... 4.1
Insulation Test Voltage (spark test) ..............5000 Volts ac
Dielectric Test Voltage.........................1500 Volts ac for 15 sec.
Insulation Resistance Constant @60°F minimum(natural material typical value)..............2000 Megohms-1000 ft.
Loop Resistance, nominal (2 conductor) ohms-1000 ft @20°C
22 AWG................................................................ 33.020 AWG................................................................ 20.818 AWG................................................................ 13.016 AWG................................................................. 8.2
Mutual Capacitance (PF/ft.)*
#22 ......................................................................... 34#20 ......................................................................... 37#18 ......................................................................... 41#16 ......................................................................... 44
*Typical Value
Cross
-Sec
tional
Area �
(sq
in)
Number
of Triads
Conductor Size
(AW
G)
Jack
etThick
ness-
(mils
)
Catalo
gNum
ber
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Nomin
alCab
le
O.D. -
(In.)
Insu
latio
nThick
ness-
(mils
)
THE OKONITE COMPANYRamsey, New Jersey 07446
E
AB
C
D
FG
H
J
SpecificationsConductors: Bare soft annealed copper, ClassB, 7-strand concentric per ASTM B-8.
Insulation: Flame-retardant Okoseal® (PVC)per UL Standard 13 and UL 2250, 15 milsnominal thickness, 105°C temperature rating.
Conductor Identification: Pigmented black andwhite in pairs, black, red and white in triads.
Assembly: Pair or triad assembled with left-handlay.
Cable Shield: Aluminum/Polyester tape over-lapped to provide 100% coverage, and a #18AWG, 7-strand tinned copper drain wire.
Inner Jacket: Black, flame-retardant Okosealper UL 13 and UL Standard 2250. A rip cord islaid longitudinally under the jacket to facilitate re-moval.
C-L-X Sheath: A close-fitting, impervious, con-tinuously welded and corrugated aluminumsheath provides complete protection againstmoisture, liquids, and gases, has excellent me-chanical strength and provides equipmentgrounding through the sheath.
Outer Jacket: Black, flame-retardant Okosealper UL 13 and UL Standard 2250.
ClassificationsUL Listed as ITC/PLTC — Instrument Tray Ca-ble/Power Limited Tray Cable for use inaccordance with Article 727 and Article 725 ofthe National Electrical Code.
These cables comply with UL 2250 and UL 13for PLTC, CL2 and CL3.
ApplicationsOkonite Type C-L-X P-OS (Pair/Triad - OverallShield) instrumentation cables are designed foruse as instrumentation, process control, andcomputer cables in ITC non-classified or labeledcircuits up to 150 volts and 5 amps (750VA) andin Class 2 or 3 Power-Limited circuits whereshielding against external interference is re-quired, but shielding against interference amonggroups is not required; indoors or outdoors; inwet or dry locations with conductor operatingtemperatures up to 105°C; in cable trays; inraceways; supported by a messenger wire; un-der raised floors; for direct burial. Suitable ClassI, Division 2, and Class I, Zone 2 Class II, Divi-sion 2, or Class III, Division 2 and Class I, Zone2 hazardous locations. Also for use asPower-Limited fire protective signaling cable(FPL) per NEC Code 760. The C-L-X sheath
provides physical protection against mechan-ical damage. It may be installed in bothexposed and concealed work, secured tosupports not greater than 6 feet apart.
The overall shield eliminates most of thestatic interference from the electric field radi-ated by power cables and other electricalequipment.
For dc service in wet locations, X-Olene® in-sulation is recommended.
Product Features• Passes the UL 1581, IEEE 383-1974, andIEEE 1202 vertical tray flame tests.
• Passes the 210,000 BTU/hr vertical trayflame test per ICEA T-29-520.
• UL listed as sunlight resistant.
• UL listed for direct burial.
• Complete pre-packaged, factory-testedwiring system-color coded.
• C-L-X enclosure permits installation in ca-ble tray containing light and power cableswithout a barrier separator.
• Individual pairs or triads are color codedfor simplified hook-up.
• Maximum noise rejection.
• Impervious, continuous sheath excludesmoisture, gases and liquids.
• In addition, the aluminum CLX sheath ex-ceeds the equipment groundingrequirements of NEC Section 250.118 and250.122, and can be used as the equipmentgrounding conductor.
• Excellent compression and impact resis-tance.
• Lower installed system cost than conduitor EMT systems.
• OSHA Acceptable.
• Meets API Standards 14F and 14FZ.
• Suitable for low temperature installation of-40°C.
C-L-X® Type P-OSType ITC/PLTC Armored Instrumentation CableSingle Pair or Triad - Overall Shield300 Volts - 105°C RatingFor Cable Tray Use
A Bare Stranded Copper ConductorB Okoseal InsulationC Twisted Pair/TriadD Tinned Stranded Copper Drain WireE Aluminum/Polyester TapeF Rip CordG Inner Black Okoseal JacketH Impervious, Continuous Corrugated
Aluminum C-L-X SheathJ Outer Black Okoseal Jacket
Product DataSection 5: Sheet 3
ULR
(UL
)T
YP
EIT
C/P
LT
C10
5°c
Conductors: 16 AWGOkoseal Insulation: 15 mils
� 564-10-3401� 564-15-3401
11
3535
.26
.285050
.43
.43.54.54
.25
.25134155
173194
� Authorized Stock Item: Available from our Customer Service Center
� Cross-sectional area for calculation of cable tray fill in accordancewith NEC Section 392.22.
Jackets- Optional jacket types available - consult local sales office.
Copper or bronze C-L-X available on special order.
To order C-L-X Type P-OS without the outer Okoseal jacket, change thesixth digit of the catalog number from 3 to 1, for example to order 1 pr.16 AWG with a bare aluminum C-L-X, the catalog number would be564-10-1401.
Length Tolerance: Cut lengths of 1000 feet or longer are subject to atolerance of � 10%; less than 1000 feet � 15%.
L/20020503
ULR
C-L-X Type P-OSType ITC/PLTC Armored Instrumentation CableSingle Pair or Triad - Overall Shield 300V - 105°C RatingFor Cable Tray Use
Product DataSection 5: Sheet 3
ELECTRICAL SPECIFICATIONSPer UL Standard 13 & 2250
Conductor Resistance, nominal .............ohms/1000 ft. @20°C
16 AWG................................................................... 4.1
Insulation Test Voltage (spark test) ..............5000 Volts ac
Dielectric Test Voltage....................................1500 Volts
Insulation Resistance Constant @60°F minimum(natural material typical value)..............2000 Megohms-1000 ft.
Loop Resistance, nominal (2 conductor) ohms-1000 ft @20°C
16 AWG................................................................. 8.2
Mutual Capacitance, typical .............................76 PF/ft.
Cross
-Sec
tional
Area �
(sq
in)
Number
of Triads
Inner
Jack
et
Thicknes
s-m
ils
Catalo
gNum
ber
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
C-L-X
O.D. -
Inch
es
Inner
Jack
et
Nomin
alO.D
. -In
ches
Outer Ja
cket
-
(mils
)
Nomin
alCab
le
O.D. -
Inch
es
THE OKONITE COMPANYRamsey, New Jersey 07446
D
A
B
G
HC
E
F
J
K
SpecificationsConductors: Bare soft annealed copper,Class B, 7-strand concentric per ASTM B-8.
Insulation: Flame-retardant Okoseal®
(PVC) per UL 13 and 2250, 15 mils nomi-nal thickness, 105°C temperature rating.
Conductor Identification: Pigmented blackand white in pairs, black, red and white in tri-ads; white conductor numerically printed forgroup identification.
Group Shield: Aluminum/Polyester tapeoverlapped to provide 100% coverage, anda 7-strand tinned copper drain wire, twosizes smaller than the conductor. All groupshields are completely isolated from eachother.
Communications Wire: 22 AWG, solid, barecopper conductor, 12 mils nominal flame-retardant Okoseal insulation, 105°C rating.
Assembly: Pairs or triads assembled with aleft-hand lay. Flame-retardant, non-wicking fillersincluded where required to provide a round ca-ble.
Cable Shield: Aluminum/Polyester tape over-lapped to provide 100% coverage, and a7-strand tinned copper drain wire, same sizeas conductor.
Jacket: Black, flame-retardant, lowtemperature Okoseal per UL Subject 13 and2250. A rip cord is laid longitudinally under thejacket to facilitate removal.
Classifications: UL Listed as ITC/PLTC - In-strument Tray Cable/Power Limited TrayCable for use in accordance with Article 727and Article 725 of the National ElectricalCode.
Cables comply with UL 2250 and UL 13 forPLTC, CL2 and CL3.
ApplicationsOkonite® Type SP-OS (Pair/triad - Individualand Overall Shield) instrumentation cables aredesigned for use as instrumentation, processcontrol, in ITC non-classified or labeled circuitsup to 150 volts and 5 amps (750VA) and inClass 2 or 3 Power-Limited circuits wheremaximum shielding against external interfer-ence is required, as well as shielding amonggroups, particularly where the cable may be
subject to abnormally high current or volt-age interference; indoors or outdoors; inwet or dry locations with conductor operat-ing temperatures up to 105°C; in cabletrays; in raceways; supported by a messen-ger wire; under raised floors. Suitable ClassI, Division 2, Class II, Division 2, or Class III,Division 2 hazardous locations. Also for useas Power-Limited fire protective signalingcable (FPL) per NEC Code 760.
The isolated individual shields overeach pair, when properly grounded,prevent crosstalk or capacitive cou-pling between adjacent pairs whichoccurs with ac signals, particularly thepulse type.
The overall shield eliminates most of thestatic interference from the electrical fieldradiated by power cables and other electri-cal equipment.
For dc service in wet locations, X-Olene®
insulation is recommended.
Product Features• Passes the UL 13 and IEEE 383-1974 ver-tical tray flame tests.
• Sunlight & oil resistant.
• Individual pairs or triads are completelyisolated.
• 100% shield coverage for reduced elec-tromagnetic noise pick-up.
• Good external noise rejection.
• Excellent weathering characteristics.
• OSHA Acceptable.
• Flexible, easy to handle and terminate.
• Communication wire included in each ca-ble for voice communication duringinstallation or instrument calibration.
• Suitable for low temperature installation of-40°C.
Type SP-OSType ITC/PLTC Instrumentation CableMultiple Shielded Pairs or Triads - Overall Shield300 Volts - 105°C RatingFor Cable Tray Use
A Bare Stranded CopperConductor
B Okoseal InsulationC Tinned Stranded Copper Group
Drain WireD Aluminum/PolyesterTapeE Twisted, Shielded Pairs/TriadsF Tinned Stranded Copper Drain WireG Aluminum/Polyester TapeH Communication WireJ Rip CordK Black Okoseal Jacket
Product DataSection 5: Sheet 13
ULR
(UL
)T
YP
EIT
C/P
LT
C10
5°c
Okoseal Insulation: 15 mils
261-10-2202261-10-2204261-10-2206
20(7X) 15
246
405050
0.350.420.51
0.100.150.20
63103138
74126161
261-10-2208261-10-2210261-10-2212
81012
506060
0.530.660.66
0.250.340.37
169219248
193258287
261-10-2216261-10-2220261-10-2224
162024
606070
0.760.820.90
0.450.530.69
311374457
350413521
261-10-2236261-10-2250
3650
7070
1.061.23
0.881.19
632845
696951
261-15-2204261-15-2208261-15-2212
48
12
505060
0.480.620.77
0.180.300.47
126212314
149236353
261-15-2216261-15-2224261-15-2236
162436
607070
0.790.991.11
0.490.770.97
397587825
436651905
261-10-3302� 261-10-3304
261-10-3306
18(7X) 15
246
505050
0.380.470.57
0.110.190.25
89133181
112156205
� 261-10-3308261-10-3310
� 261-10-3312
81012
506060
0.560.730.69
0.290.420.44
223289330
247328369
261-10-3316261-10-3320
� 261-10-3324
162024
607070
0.830.940.98
0.540.690.85
417523614
456587678
� 261-10-3336261-10-3350
3650
7080
1.141.42
1.111.58
8611188
9411294
261-15-3304261-15-3308261-15-3312
48
12
506060
0.520.680.83
0.230.410.57
165301425
188340464
261-15-3316261-15-3324261-15-3336
162436
607070
0.891.101.24
0.620.951.21
543804
1143
607884
1249
� 261-10-4402� 261-10-4404
261-10-4406
16(7X) 15
246
505060
0.430.510.66
0.170.230.34
116179260
130203299
� 261-10-4408261-10-4410
� 261-10-4412
81012
606060
0.680.820.81
0.400.530.57
323397456
362436520
261-10-4416261-10-4420
� 261-10-4424
162024
707070
0.941.061.10
0.750.881.07
600729860
664809940
261-10-4436261-10-4450
3650
8080
1.371.57
1.471.93
12501687
13561830
261-15-4404� 261-15-4408� 261-15-4412
48
12
506070
0.550.740.93
0.260.480.74
227418615
251457679
261-15-4416261-15-4424261-15-4436
162436
708080
1.021.271.43
0.821.271.61
78811671668
85212731784
� Authorized Stock Item: Available from ourCustomer Service Center.
� Cross-sectional area for calculation of cabletray fill in accordance with NEC Section 392.22
Length Tolerance: Cut lengths of 1000 feet orlonger are subject to a tolerance of � 10%; lessthan 1000 feet � 15%.
I/19100513
ULR
Type SP-OSType ITC/PLTC Instrumentation CableMultiple Shielded Pairs or Triads - Overall Shield 300V - 105°C RatingFor Cable Tray Use
Product DataSection 5: Sheet 13
ELECTRICAL SPECIFICATIONSPer UL Subject 13 & 2250
Conductor Resistance, nominal .............ohms/1000 ft. @20°C
20 AWG ............................................................... 10.418 AWG ................................................................. 6.516 AWG................................................................... 4.1
Insulation Test Voltage (spark test) ..............5000 Volts ac
Dielectric Test Voltage.........................1500 Volts ac for 15 sec.
Insulation Resistance Constant @60°F, minimum(natural material typical value)............. 2,000 Megohms-1000 ft.
Loop Resistance, nominal (2 conductor) ohms-1000 ft @20°C
20 AWG ............................................................... 20.818 AWG ............................................................... 13.016 AWG................................................................. 8.2
Mutual Capacitance (PF/ft.)*
20 AWG .................................................................. 5918 AWG................................................................... 6816 AWG................................................................... 76
*Typical Value
Cross
-Sec
tional
Area �
(sq
in)
Number
of Triads
Jack
et
Thicknes
s-m
ils
Catalo
gNum
ber
Insu
latio
nThick
ness
(mils
)
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Nomin
alCab
le
O.D. -
Inch
es
Number
of Pairs
Strand
Size(A
WG)
THE OKONITE COMPANYRamsey, New Jersey 07446
SpecificationsConductors: Bare soft annealed copper, Class B,7-strand concentric per ASTM B-8.Insulation: Flame-retardant Okoseal® (PVC) perUL 13 and 2250, 15 mils nominal thickness,105°C temperature rating.Conductor Identification: Pigmented black andwhite in pairs, black, red and white in triads;white conductor numerically printed for groupidentification.Group Shield: Aluminum/Polyester tape over-lapped to provide 100% coverage, and a 7-strandtinned copper drain wire, two sizes smaller than theconductor. All group shields are completely isolatedfrom each other.Communications Wire: 22 AWG, solid, bare cop-per conductor, 12 mils nominal flame-retardantOkoseal insulation, 105°C temperature rating.Assembly: Pairs or triads assembled with left-hand lay. Flame-retardant, non-wicking fillers in-cluded where required to provide a round cable.Cable Shield: Aluminum/Polyester tape over-lapped to provide 100% coverage, and a 7-strandtinned copper drain wire, same size as conductor.Inner Jacket: Black, flame-retardant, lowtemperature Okoseal per UL 13 and 2250. A ripcord is laid longitudinally under the jacket to facili-tate removal.C-L-X Sheath: A close-fitting, impervious, continu-ously welded and corrugated, aluminum sheathprovides complete protection against moisture, liq-uids, and gases, has excellent mechanical strength,and provides equipment grounding through thesheath.Outer Jacket: Black, flame-retardant, lowtemperature Okoseal per UL 13 and 2250.Classifications: UL Listed as ITC/PLTC - Instru-ment Tray Cable/Power Limited Tray Cable for usein accordance with Article 727 and Article 725 ofthe National Electrical Code.Cables comply with UL 2250 and UL 13 for PLTC,CL2 and CL3.
ApplicationsC-L-X Type SP-OS (Pair/triad - Individual andOverall Shield) instrumentation cables are de-signed for use as instrumentation, processcontrol, in ITC non-classified or labeled circuitsup to 150 volts and 5 amps (750VA) and inClass 2 or 3 Power-Limited circuits where max-imum shielding against external interference isrequired, as well as shielding among groups,particularly where the cable may be subject toabnormally high current or voltage interference;indoors or outdoors; in wet or dry locations withconductor operating temperatures up to 105°C;in cable trays; in raceways; supported by a
messenger wire; under raised floors or di-rect burial. Suitable in Class I & II, Division2 or Class III, Division 2 and Class I, Zone2 hazardous locations. Also for use asPower-Limited fire protective signaling ca-ble (FPL) per NEC Code 760. It may beinstalled in both exposed and concealedwork, secured to supports not greater than6 feet apart.The isolated individual shields over each pair,when properly grounded, prevent crosstalk orcapacitive coupling between adjacent pairswhich occurs with ac signals, particularly thepulse type.The overall shield eliminates most of the staticinterference from the electric field radiated bypower cables and other electrical equipment.The C-L-X sheath provides physical protectionagainst mechanical damage as well as com-plete protection against moisture or gasesentering the cable.For dc service in wet locations X-Olene® insula-tion is recommended.
Product Features• Passes the UL 13, IEEE 383-1974 vertical trayflame tests.• Passes the IEEE 1202 vertical tray flame test (2pr #18 AWG and larger).• Passes the 210,000 BTU/hr vertical tray flametest per ICEA T-29-520.• UL listed for direct burial (2 PR #20 AWG andlarger)• Complete pre-packaged, factory-tested wiringsystem-color coded.• C-L-X enclosure permits installation in cable traycontaining light and power cables without a barrierseparator.• Individual pairs or triads are completely iso-lated.• Impervious, continuous sheathexcludes moisture,gases and liquids.• In addition, the aluminum CLX sheath exceedsthe equipment grounding requirements of NECSection 250.118 and 250.122, and can be used asthe equipment grounding conductor.• Lower installed system cost than conduit orEMT systems.• Meets API Standards 14F & 14FZ.• Suitable for low temperature installation to -40°C.
C-L-X® Type SP-OSType ITC/PLTC Armored Instrumentation CableMultiple Shielded Pairs or Triads - Overall Shield300 Volts - 105°C RatingFor Cable Tray Use
A Bare Stranded Copper ConductorB Okoseal InsulationC Tinned Stranded Copper Group
Drain WireD Aluminum/PolyesterE Twisted, Shielded Pairs/TriadsF Communication WireG Aluminum/PolyesterH Tinned Stranded Copper Drain WireJ Rip CordK Inner Black Okoseal JacketL Impervious, Continuous, Corru-
gated Aluminum C-L-X SheathM Outer Black Okoseal Jacket
Product DataSection 5: Sheet 14
ULR
D
A
B
G
HC
E
F
J
K
L
M
(UL
)T
YP
EIT
C/P
LT
C10
5°c
Okoseal Insulation: 15 mils
561-10-3202561-10-3204561-10-3206
20(7X)
246
405050
0.360.430.48
0.580.620.71
505050
0.690.730.82
.37
.42
.53
198234286
217314366
561-10-3208561-10-3210561-10-3212
81012
505060
0.530.570.63
0.750.800.84
505050
0.860.911.95
.58
.65
.71
317393430
397473510
561-10-3216561-10-3220561-10-3224
162024
606070
0.720.810.90
0.971.061.15
505050
1.081.171.26
.921.081.25
501581704
581661794
561-10-3236561-10-3250
3650
7070
1.041.19
1.341.51
5060
1.451.65
1.652.14
9071230
10131373
561-15-3204561-15-3208561-15-3212
48
12
505060
0.450.560.67
0.670.800.89
505050
0.780.911.00
.48
.65
.79
258369504
338439584
561-15-3216561-15-3224561-15-3236
162436
607070
0.770.961.11
1.021.241.42
505050
1.131.351.53
1.001.431.84
604852
1117
684958
1260
� 561-10-3302� 561-10-3304
561-10-3306
18(7X)
246
405050
0.380.490.55
0.580.710.75
505050
0.690.820.86
0.370.530.58
212273338
292353418
� 561-10-3308561-10-3310
� 561-10-3312
81012
506060
0.600.670.71
0.800.890.93
505050
0.921.001.04
0.650.790.85
389479529
469559609
561-10-3316561-10-3320
� 561-10-3324
162024
606070
0.790.880.98
1.061.151.24
505050
1.171.261.35
1.081.251.43
632778889
738868995
561-10-3336561-10-3350
3650
7080
1.151.36
1.471.69
5060
1.581.82
1.962.60
12031629
13461812
561-15-3304561-15-3308561-15-3312
48
12
506060
0.540.690.79
0.750.931.06
505050
0.861.041.17
.58
.851.08
314475632
394555712
561-15-3316561-15-3324561-15-3336
162436
707080
0.901.061.29
1.151.341.60
505060
1.261.451.73
1.251.652.35
78110971539
86112401682
� 561-10-3402� 561-10-3404
561-10-3406
16(7X)
246
505050
0.440.520.59
0.670.710.84
505050
0.780.820.95
0.480.530.71
255327434
336407514
� 561-10-3408561-10-3410
� 561-10-3412
81012
606060
0.690.750.81
0.931.021.06
505050
1.041.131.17
0.851.001.08
505604671
585684777
561-10-3416561-10-3420
� 561-10-3424
162024
707070
0.951.031.10
1.241.341.37
505050
1.351.451.48
1.431.651.72
85510041245
94511011388
561-10-3436561-10-3450
3650
8080
1.291.53
1.601.87
6060
1.732.00
2.353.14
16782172
18422428
� 561-15-3404� 561-15-3408� 561-15-3412
48
12
506070
0.580.790.95
0.801.021.19
505050
0.911.131.30
0.651.001.33
384609862
464689952
561-15-3416561-15-3424561-15-3436
162436
708080
1.041.271.49
1.341.601.83
506060
1.451.731.96
1.652.353.02
105315742119
115917382306
� Authorized Stock Item: Available from our Cus-tomer Service Center.Jackets - Optional jacket types available - consultlocal sales office.� Cross-sectional area for calculation of cabletray fill in accordance with NEC Section 392.22.Copper or bronze C-L-X available on special order.To order C-L-X Type SP-OS without the outerOkoseal jacket, change the sixth digit of the cata-log number from 3 to 1. For example, to order 12 pr.20 AWG with a bare aluminum C-L-X, the catalognumber would be 561-10-1212.Length Tolerance: Cut lengths of 1000 feet orlonger are subject to a tolerance of � 10%; lessthan 1000 feet � 15%.
J/20020514
ULRC-L-X Type SP-OSType ITC/PLTC Armored Instrumentation CableMultiple Shielded Pairs or Triads - Overall Shield 300V - 105°C RatingFor Cable Tray Use
Product DataSection 5: Sheet 14
ELECTRICAL SPECIFICATIONSConductor Resistance, nominal .............ohms/1000 ft. @20°C
20 AWG....................................................................... 10.418 AWG......................................................................... 6.516 AWG......................................................................... 4.1
Insulation Test Voltage (spark test) ..............5000 Volts acDielectric Test Voltage.........................1500 Volts ac for 15 sec.Insulation Resistance Constant @60°F minimum
(natural material typical value) ......2000 Megohms-1000 ft.Loop Resistance, nominal (2 conductor) ohms-1000 ft @20°C
20 AWG....................................................................... 20.818 AWG....................................................................... 13.016 AWG......................................................................... 8.2
Mutual Capacitance (PF/ft.)*#20 ................................................................................. 59#18 ................................................................................. 68#16 ................................................................................. 76
*Typical Value
Cross
-Sec
tional
Area �
(sq
in)
Number
of Triads
Strand
Size(A
WG)
Inner
Jack
et
Thicknes
s - mils
Nomin
alCore
O.D. (
In.)
Outer Ja
cket
mils
C-L-X
O.D. (
In.)
Catalo
gNum
ber
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Nomin
alCab
le
O.D. -
(In.)
THE OKONITE COMPANYRamsey, New Jersey 07446
SpecificationsConductors: Solid alloys per ANSI MC96.1Insulation: Flame-retardant Okoseal®
(PVC) per UL Standard 13 and 2250,15 mils nominal thickness, 105°C tem-perature rating.Conductor Identification: Pigmented in-sulation on individual conductors.Assembly: Pair assembled with left-hadlay.Cable Shield: Auminum/Polyester tapeoverlapped to provide 100% coverage,and a 7-strand tinned copper drain wire,same size as conductor.Jacket: Flame-retardant, low temperatureOkoseal per UL Standard 13 and 2250. Arip cord is laid longitudinally under thejacket to facilitate removal.Classifications: UL Listed as TypeITC/PLTC - Instrumentation Tray Ca-ble/Power Limited Tray Cable, for use inaccordance with Article 727 and 725 ofthe National Electrical Code.Cables comply with UL 2250 and ULSubject 13 for PLTC, CL2 and CL3.
ApplicationsOkonite Type P-OS (Pair/triad -Overall Shield) thermocoupleextension cables are designed for useas instrumentation and process con-trol cables in ITC non-classified orlabeled circuits up to 150 volts and 5amps (750VA) and in Class 2 of 3Power-Limited circuits where shieldingagainst external interference is re-quired, but shielding againstinterference among groups is not re-quired; indoors or outdoors; in wet ordry locations with conductor operatingtemperatures up to 105°C; in cabletrays; in raceways; supported by a
messenger wire; under raised floors;for direct burial. Suitable Class I, Divi-sion 2, Class II, Division 2, orClass III, Division 2 hazardous lo-cations.
Product Features• Passes the UL 1581 & IEEE 383-1974vertical tray flame tests.• Sunlight resistant & oil resistant..• UL listed for direct burial.• Individual pairs or triads are colorcoded for simplified hook-up.• Good noise rejection.• Excellent weathering characteristics.• OSHA Acceptable.• Flexible, easy to handle terminate.• Twisted with 100% shield coverage toreduce electromagnetic noise.• Suitable for lowtemperature installationof-40°C.
Type P-OSType ITC/PLTC Thermocouple Extension CableSingle Pair - Overall Shield - 105°C RatingFor Cable Tray Use
A Solid Thermocouple AlloyConductor
B Okoseal InsulationC Twisted Pair/TriadD Tinned Stranded Copper Drain WireE Aluminum/Polyester TapeF Rip CordG Okoseal Jacket
Product DataSection 5: Sheet 18
ULR
G
B
A
C
D
E
F
(UL
)T
YP
EIT
C/P
LT
C10
5°c
Conductors: 16 AWGOkoseal Insulation: 15 mils
EXJXKXTX
� 284-20-1401� 284-20-2401� 284-20-3401
284-20-4401
1111
35353535
.24
.24
.24
.24
.05
.05
.05
.05
44444444
49494949
� Authorized Stock Item: Available from our Cus-tomer Service Center.
SX available upon request.
(1) Special grade alloy conductors for JX and TXare available on special order.
� Cross-sectional area for calculation of cable trayfill in accordance with NEC Section 392.22
E/15040518
ULR
Type P-OSType ITC/PLTC Thermocouple Extension CableSingle Pair - Overall Shield - 105°C RatingFor Cable Tray Use
Product DataSection 5: Sheet 18
ELECTRICAL SPECIFICATIONSPer UL Standard 13 and 2250
Insulation Test Voltage (spark test) ..............5000 Volts ac
Dielectric Test Voltage.........................1500 Volts ac for 15 sec.
Shield Isolation TestPair to Cable Shield..........................exceeds 100M ohms/1000 ft.
Insulation Resistance Constant @60°F minimum(natural material typical value)..............2000 Megohms-1000 ft.
Cross
-Sec
tional
Area �
(sq
in)
Catalo
gNum
ber
Jack
etThick
ness-
(mils
)
ASA/ISA
Type
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
ASA/ISA COLOR CODE AND LIMITS OF ERROR
ASA/ISAType
Positive Wire Negative Wire OuterJacketColor
TemperatureRange°C
Limits of Error Nom. LoopResistance
Per 100’ @ 20°CAlloy Color Alloy Color Standard Special (1)
EX Chromel Purple Constantan Red Purple 0 to 200°C � 1.7°C 27.8 ohms
JX Iron White Constantan Red Black 0 to 200°C � 2.2°C � 1.1°C 13.9 ohms
KX Chromel Yellow Alumel Red Yellow 0 to 200°C � 2.2°C 23.6 ohms
TX Copper Blue Constantan Red Blue -60 to 100°C � 1.0°C � 0.5°C 12.0 ohms
Nomin
alCab
le
O.D. -
(In.)
THE OKONITE COMPANYRamsey, New Jersey 07446
D
A
B
G
H
C
EF
J
SpecificationsConductors: Solid alloys per ANSI MC96.1.
Insulation: Flame-retardant Okoseal®
(PVC) per UL Standard 13 and 2250,15 mils nominal thickness, 105°C tem-perature rating.
Conductor Identification: Pigmented in-sulating on individual conductors.
Assembly: Pairs assembled with left-hand lay
Cable Shield: Aluminum/Polyesterbacked tape overlapped to provide 100%coverage, and a 7-strand tinned copperdrain wire, same size as the conductor.
Inner Jacket: Black, flame-retardant, lowtemperature Okoseal per UL Standard 13and 2250. A rip cord is laid longitudinallyunder the jacket to facilitate removal.
C-L-X Sheath: Close fitting, impervious,continuously welded and corrugated alu-minum sheath provides completeprotection against moisture, liquids, andgases, has excellent mechanical strengthand provides equipment groundingthrough the sheath.
Outer Jacket: Flame-retardant, lowtemperature Okoseal per UL Standard 13and 2250.
Classifications: UL Listed as TypeITC/PLTC - Instrumentation Tray Ca-ble/Power Limited Tray Cable, for use inaccordance with Article 727 and 725 ofthe National Electrical Code.
Cables comply with UL 2250 and UL Sub-ject 13 for PLTC, CL2 and CL3.
ApplicationsOkonite Type C-L-X P-OS (Pair/triad -Overall Shield) Thermocouple Extensioncables are designed for use as instrumen-tation and process control cables in ITCnon-classified or labeled circuits up to 150volts and 5 amps (750VA) and in Class 2or 3 Power-Limited circuits where shield-ing against external interference isrequired, but shielding against interfer-
ence among groups is not required;indoors or outdoors; in wet or dry loca-tion with conductor operatingtemperatures up to 105°C; in cabletrays; in raceways; supported by amessenger wire; under raised floors;for direct burial. Suitable Class I, Divi-sion 2, Class II, Division 2, or Class III,Division 2 and Class I, Zone 2 hazard-ous locations. The C-L-X sheathprovides physical protection againstmechanical damage. It may be in-stalled in both exposed and concealedwork, secured to supports not greaterthan 6 feet apart.
Product Features• Passes the UL 1581, IEEE 383-1974,& IEEE 1202 vertical tray flame tests.• Passes the 210,000 BTU/hr verticaltray flame test per ICEA T-29-520.• Complete pre-packaged, factory-testedwiring system-color coded.• C-L-X cables are quality control in-spected to meet or exceed applicable ULStandards.• C-L-X enclosure permits installation incable tray containing light and power ca-bles without a barrier separator.• Individual pairs or triads are colorcoded for simplified hook-up.• Impervious, continuous sheath ex-cludes moisture, gases and liquids.• In addition, the aluminum CLX sheathexceeds the equipment grounding re-quirements of NEC Section 250.118 and250.122, and can be used as the equip-ment grounding conductor.• Lower installed system cost than conduit orEMT systems.• Meets API Standards 14F and 14FZ.• UL listed for direct burial• Suitable for low temperature installa-tion of -40°C
C-L-X® Type P-OSType ITC/PLTC Armored ThermocoupleExtension CableSingle Pair - Overall Shield - 105°C RatingFor Cable Tray Use
A Solid Thermocouple AlloyConductor
B Okoseal InsulationC Twisted PairD Tinned Stranded Copper Drain WireE Aluminum/Polyester TapeF Rip CordG Inner Okoseal JacketH Impervious, Continuous, Corru-
gated Aluminum C-L-X SheathJ Outer Okoseal Jacket
Product DataSection 5: Sheet 19
ULR
(UL
)T
YP
EIT
C/P
LT
C10
5°c
Conductors: 16 AWGOkoseal Insulation: 15 mils
EXJXKXTX
584-20-1401584-20-2401
� 584-20-3401584-20-4401
1111
35353535
.24
.24
.25
.24
.43
.43
.43
.43
50505050
.54
.54
.54
.54
.23
.23
.23
.23
128128128128
167167167167
� Authorized Stock Item: Available from our CustomerService Centers.
SX available upon request.
(1) Special grade alloy conductors for JX and TX areavailable on special order.
� Cross-sectional area for calculation of cable tray fillin accordance with NEC Section 392.22.
Jackets - Optional jacket types available - consult lo-cal sales office.
Copper or bronze C-L-X available on special order.
To order C-L-X Type P-OS without the outer Okosealjacket, change the sixth digit of the catalog numberfrom 1 to 5 for EX, 2 to 6 for JX, 3 to 7 for KX, and 4 to8 for TX. For example to order 12 pr. 20 AWG TypeKX with a bare aluminum C-L-X, the catalog numberwould be 584-20-7212.
Length Tolerance: Cut lengths of 1000 feet or longerare subject to a tolerance of � 10%; less than 1000feet � 15%.
L/20020519
ULR
C-L-X Type P-OSType ITC/PLTC Armored ThermocoupleExtension CableSingle Pair - Overall Shield - 105°C RatingFor Cable Tray Use
Product DataSection 5: Sheet 19
ELECTRICAL SPECIFICATIONSPer UL Standard 2250
Insulation Test Voltage (spark test) .......................5000 Volts ac
Dielectric Test Voltage .........................1500 Volts ac for 15 sec.
Shield Isolation TestPair to Cable Shield.......................exceeds 100M ohms/1000 ft.
Insulation Resistance Constant @60°F, minimum(natural material typical value)...............2000 Megohms-1000 ft.
Cross
-Sec
tional
Area (s
qin
) �
C-L-X
O.D. -
Inch
es
Inner
Jack
et
Thicknes
s - mils
ASA/ISA
Type
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Inner
Jack
et
Nomin
alO.D
. -In
ches
ASA/ISA COLOR CODE AND LIMITS OF ERROR
ASA/ISAType
Positive Wire Negative Wire OuterJacketColor
TemperatureRange°C
Limits of Error Nom. LoopResistance
Per 100’ @ 20°CAlloy Color Alloy Color Standard Special (1)
EX Chromel Purple Constantan Red Purple 0 to 200°C � 1.7°C 27.8 ohms
JX Iron White Constantan Red Black 0 to 200°C � 2.2°C � 1.1°C 13.9 ohms
KX Chromel Yellow Alumel Red Yellow 0 to 200°C � 2.2°C 23.6 ohms
TX Copper Blue Constantan Red Blue -60 to 100°C � 1.0°C � 0.5°C 12.0 ohms
Outer Ja
cket
- mils
Catalo
gNum
ber
Nomin
alCab
le
O.D. -
(In.)
THE OKONITE COMPANYRamsey, New Jersey 07446
SpecificationsConductors: Bare soft annealed copper,Class B, 7-strand concentric per ASTMB-8.
Insulation & Jacket: Flame-retardantOkoseal® (PVC), 15 mils nominal thick-ness, nylon jacket, 4 mil nominalthickness, 90°C temperature rating, perUL Standard 1277.
Conductor Identification: Pigmentedblack and white in pairs, black, whiteand red in triads.
Assembly: Pair or triad assembled withleft-hand lay.
Cable Shield: Aluminum/Polyester tapeoverlapped to provide 100% coverage,and a 7-strand tinned copper drain wire,same size as conductor.
Jacket: Black, flame-retardant, lowtemperature Okoseal per UL Standard1277, 90°C temperature rating. A rip cordis laid longitudinally under the jacket to fa-cilitate removal.
Classification: UL Listed as Type TC Ar-ticle 336 of the National Electrical Code.
ApplicationsOkonite’s single pair or triad Type P-OSinstrumentation cables are designed foruse on Class 1 Remote-Control Signalingcircuits or where a 600V cable is desired,as instrumentation, process control, orcomputer cable transmitting signals atlevels above 100 milli-volts in circuitswhere shielding against external interfer-ence is required, but shielding againstinterference among groups is not re-quired. For use indoors or outdoors; wetor dry locations; in cable trays; in race-ways; supported by a messenger wire; inClass I, Division 2, Class II, Division 2 orClass III, Division 2 hazardous locations.Also for use as non power limited fire pro-tective signaling cable (NPLF) per NECCode 760. Type TC cables can be labeledOkomarine to be used in ABS and CoastGuard approved marine applications.
Type TC is authorized for use inClass I & II, Division 2 hazardouslocations.
Product Features• UL listed for cable tray use (all sizes).
• Flame Retardant - passes the verticaltray flame test requirements of IEEE383-1974 & 1202/FT4 and UL 1277.
• May be combined with 600V powerand control cables in the same tray.
• Sunlight resistant & oil resistant
• Individual pairs or triads are colorcoded for simplified hook-up.
• Good noise rejection.
• Excellent weathering characteristics.
• May be used in approved marine ap-plications.
• Flexible, easy to handle and termi-nate.
• Twisted with 100% shield coverage toreduce electromagnetic pick-up.
• OSHA Acceptable.
• Suitable for installation in low tem-perature installations to -40°C.
• CSA C22.2 No. 239 Type CIC.
Okoseal-N® Type P-OSUL Type TC and cUL Type CIC Instrumentation CableSingle Pair or Triad - Overall Shield600 Volts - 90°C Rating Wet or Dry
A Stranded Bare Copper ConductorB Okoseal Insulation with Nylon
JacketC Twisted Pair/TriadD Stranded Tinned Copper Drain WireE Aluminum/Synthetic Polymer TapeF Rip CordG Black Okoseal Jacket
Product DataSection 5: Sheet 29
E
ABC
D
FG
(UL
)T
YP
ET
CO
RC
(UL
)T
YP
EC
IC
ULR c ULR
Okoseal Insulation: 15 milsNylon Jacket: 4 mils
� 264-60-3301264-65-3301
1818
11
45
0.270.29
0.060.07
4854
5359
� 264-60-4401� 264-65-4401
1616
11
0.290.31
0.070.08
5669
6180
� 264-60-5501264-65-5501
1414
11
0.320.34
0.090.10
7594
86105
� Cross-sectional area for calculation of cable tray fill inaccordance with NEC Section 392-22
Length Tolerance: Cut lengths of 1000 feet or longer aresubject to a tolerance of � 10%; less than 1000 feet � 15%.
� Authorized Stock Item: Available from our CustomerService Centers.
L/19110529
Okoseal-N Type P-OSUL Type TC and cUL Type CIC Instrumentation CableSingle Pair or Triad - Overall Shield600V - 90°C Rating Wet or Dry
Product DataSection 5: Sheet 29
ELECTRICAL SPECIFICATIONSPer UL Standard 1277
Conductor Resistance, maximumohms/1000 ft.. . . . . . . . . . . . . . . . . . . . . . . . . . . . @20°C ..........@25°C
18 AWG . . . . . . . . . . . . . . . . . . . . 6.09···············7.0416 AWG . . . . . . . . . . . . . . . . . . . . 4.34···············4.4314 AWG . . . . . . . . . . . . . . . . . . . . . 2.72···············2.78
Insulation Test Voltage (spark test)
18 - 16 AWG . . . . . . . . . . . . . . 6000 volts ac14 AWG . . . . . . . . . . . . . . . . . . 7500 volts ac
Dielectric Test Voltage
18-16 AWG . . . . . . . . . . . . . . . 1500 volts ac for 1 minute14 AWG . . . . . . . . . . . . . . . . . . 2000 volts ac for 1 minute
Shield Isolation Test
Pair to Cable Shield . . . exceeds 100 Megohms/1000 ft.
Insulation Resistance Constant @60°F minimum(natural material typical value) ..........2000 Ohms-1000 ft.
Loop Resistance, nominal (2 conductor)ohms-1000 ft. . . . . . . . . . . . . . . . . . . . . . . . . . . . @20°C ..........@25°C
18 AWG . . . . . . . . . . . . . . . . . . . 12.18·············14.0816 AWG . . . . . . . . . . . . . . . . . . . . 8.68···············8.8614 AWG . . . . . . . . . . . . . . . . . . . . 5.44···············5.56
Cross
-Sec
tional
Area �
(sq
in)
Number
of Triads
SizeAW
G
Catalo
gNum
ber
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Nomin
alCab
le
O.D. -
(In.)
Jack
etThick
ness-
(mils
)
Mutual Capacitance 18 AWG ......................49 pF/ft16 AWG ......................56 pF/ft14 AWG ......................64 pF/ft
L/R ratio 18 AWG ......................14 micro Henry/ohm16 AWG ......................21 micro Henry/ohm14 AWG ......................31 micro Henry/ohm
Inductance 18 AWG ......................0.19 micro Henry/ft16 AWG ......................0.18 micro Henry/ft14 AWG ......................0.17 micro Henry/ft
THE OKONITE COMPANYRamsey, New Jersey 07446
ULR c ULR
SpecificationsConductors: Bare soft annealed copper,Class B, 7-strand concentric per ASTM B-8.Insulation: Flame-retardant Okoseal®
(PVC), 15 mils nominal thickness, nylonjacket, 4 mil nominal thickness, 90°C tem-perature rating, per UL Standard 1277.Conductor Identification: Pigmented blackand white in pairs; black, white and redin triads.Group Shield: Aluminum/Polyester tape over-lapped to provide 100% coverage, and a7-strand tinned copper drain wire, two sizessmaller than the conductor. All group shieldsare completely isolated from each other.Assembly: Pairs or triads assembled with1 left-hand lay. Flame-retardant, non-wickingfillers included where required to provide around cable.Cable Shield: Aluminum/Polyester tape over-lapped to provide 100% coverage, and a7-strand tinned copper drain wire, same sizeas conductor.Jacket: Black, flame-retardant, lowtemperature Okoseal per UL Standard 1277,90°C temperature rating. A rip cord is laid lon-gitudinally under the jacket to facilitateremoval.Classification: UL Listed as Type TC Article336 of the National Electrical Code.
ApplicationsOkonite’s Type SP-OS (Shielded pairs or tri-ads - Overall Shield) instrumentation cablesare designed for use on Class 1 Remote-Control Signaling circuits or where a 600V ca-ble is desired, as instrumentation, processcontrol, or computer cable transmitting signalsat levels above 100 mili-volts in circuits wheremaximum noise protection is required. Protec-tion from interference among groups as well asexternal sources is provided by individualgroup shields as well as an overall cableshield. For use indoors or outdoors; wet or drylocations; in raceways; supported by a mes-senger wire; for direct burial; in Class I,Division 2, Class II, Division 2 or Class III, Di-vision 2 hazardous locations. Also for use asnon power limited fired protective signaling ca-ble (NPLF) per NEC Code 760. As an option,type TC cables can be labeled Okomarine tobe used in ABS and Coast Guard approvedmarine applications, on special order.
Product Features• UL listed for cable tray use (all sizes).
• Passes the UL 1277 and IEEE 383-1974vertical tray flame tests.
• Passes IEEE 1202/FT4 vertical trayflame test.
• May be combined with 600 volt powerand control cables in the same tray.
• Sunlight resistant and oil resistant.
• UL listed for direct burial (8/pr #16 AWGand larger)
• Individual pairs or triads are numberedand color-coded for simplified hook-up.
• Individual pairs or triads are completelyisolated.
• 100% shield coverage for reduced elec-tromagnetic noise pick-up.
• Good external noise rejection.
• Excellent weathering characteristics.
• OSHA Acceptable.
• Flexible, easy to handle and termi-nate.
• Suitable for installation at low tem-peratures to -40°C.
• CSA C22.2 No. 239 Type CIC.
Okoseal-N® Type SP-OSUL Type TC and cUL Type CIC Instrumentation CableMultiple Shielded Pairs or Triads - Overall Shield600 Volts - 90°C Rating Wet or Dry
Product DataSection 5: Sheet 31
A Stranded Bare Copper ConductorB Okoseal Insulation with Nylon
JacketC Tinned Stranded Copper Group
Drain WireD Double Faced Aluminum/Synthetic
Polymer Backed TapeE Twisted, Shielded Pairs/TriadsF Double Faced Aluminum/Synthetic
Polymer Backed TapeG Stranded Tinned Copper Drain WireH Rip CordJ Black Okoseal Jacket
(UL
)T
YP
ET
CO
RC
(UL
)T
YP
EC
ICULR c ULR
Okoseal Insulation - 15 mils; Nylon Jacket - 4 mils
261-60-3302261-60-3304261-60-3308
18 (7x)
248
454560
0.420.500.67
0.140.200.35
83138254
96161297
261-60-3310261-60-3312261-60-3316
101216
608080
0.770.810.93
0.460.510.67
316395496
355459559
261-60-3320261-60-3324261-60-3336261-60-3350
20243650
80808080
1.071.091.281.55
0.900.931.291.89
597699974
1307
677779
10801450
261-65-3304261-65-3308261-65-3312
48
12
606080
0.610.750.95
0.290.440.71
196317516
220356580
261-65-3316261-65-3324261-65-3336
162436
808080
1.091.341.53
0.931.411.84
652940
1319
73210461462
� 261-60-4402� 261-60-4404� 261-60-4408
16 (7x)
248
456060
0.440.580.72
0.150.260.47
114198337
137222376
261-60-4410� 261-60-4412� 261-60-4416
101216
808080
0.940.911.04
0.690.650.85
452515639
516579692
261-60-4420� 261-60-4424
261-60-4436261-60-4450
20243650
808080
110
1.191.181.401.79
1.111.091.542.52
787925
13041866
867103114102053
261-65-4404� 261-65-4408� 261-65-4412
48
12
608080
0.610.791.00
0.290.490.79
252478674
291542754
261-65-4416261-65-4424261-65-4436
162436
808080
1.121.501.71
0.991.772.30
85812451761
96413881948
261-60-5502261-60-5504261-60-5508
14 (7x)
248
456080
0.510.680.91
0.210.360.65
147272511
163311575
261-60-5510261-60-5512261-60-5516 •
101216
808080
1.061.091.20
0.880.931.13
627721919
707801
1025
261-60-5520 •261-60-5524 •261-60-5536 •261-60-5550 •
20243650
808080
110
1.341.481.672.02
1.411.722.193.20
1120132218862681
1226142820292973
261-65-5504261-65-5512
412
6080
0.751.23
0.441.19
351954
3901060
261-65-5516 •261-65-5524 •261-65-5536 •
162436
8080
110
1.361.692.00
1.452.243.14
122517942683
133119872975
• Contains 41-strand tinned copper overall drain wire, same size as conductor.
� Cross-sectional area for calculation of cable tray fill inaccordance with NEC Section 392.22
Length Tolerance: Cut lengths of 1000 feet or longer aresubject to a tolerance of � 10%; less than 1000 feet � 15%.
� Authorized Stock Item: Available from our Customer Service Centers.
M/21020531
Okoseal-N Type SP-OSUL Type TC and cUL Type CIC Instrumentation CableSingle Pairs or Triads - Individual and Overall Shield600V - 90°C Rating Wet or Dry
Product DataSection 5: Sheet 31
ELECTRICAL SPECIFICATIONSPer UL Standard 1277
Conductor Resistance, maximum ........ohms/1000 ft................................................................... @20°C @25°C
18 AWG ................................................ 6.09 7.0416 AWG ................................................ 4.34 4.4314 AWG ................................................ 2.72 2.78
Insulation Test Voltage (spark test)18 - 16 AWG .................... 6000 VOLTS AC14 AWG ........................... 7500 VOLTS AC
Dielectric Test Voltage ...............2000 Volts ac for 1 minuteInsulation Resistance Constant @ 60F, minimum
(natural material typical value) ............ 2000 ohms/1000 ft.Loop Resistance, maximum (2 conductor)ohms-1000 ft.................................................................. @20°C @25°C
18 AWG............................................... 12.18 14.0816 AWG ............................................... 8.68 8.8614 AWG .............................................. 5.44 5.56
Cross
-Sec
tional
Area �
(sq
in)
Number
of Triads
SizeAW
GStra
nds
Catalo
gNum
ber
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Nomin
alCab
le
O.D. -
(In.)
Jack
etThick
ness-
(mils
)
THE OKONITE COMPANYRamsey, New Jersey 07446
ULR c ULR
C-L-X Okoseal-N P-OS® ®
UL Type MC-HL and cUL Type ACIC-TC Instrumentation CableSingle Pair or Triad-Overall Shield600 Volts 90°C Rating 600/1000V Marine CableFor Cable Tray Use - Sunlight Resistant - For Direct Burial
A Bare Stranded Copper ConductorOkoseal Insulation/Nylon JacketBTwisted, Shielded Pairs/TriadsCTinned Stranded Copper Drain WireDAluminum/Synthetic Polymer TapeERip CordF
G Inner Black Okoseal JacketImpervious, Continuous, CorrugatedHAluminum C-L-X SheathOuter Black Okoseal JacketJ
Product DataSection 5: Sheet 40
OK
ON
ITE
SP
-OS
12
PR
16
AW
G C
U X
-OL
EN
E (
XL
PE
)
SpecificationsConductors: Bare soft annealed copper,
Class B, 7-strand concentric per ASTM B-8.
Insulation: Flame-retardant Okoseal (PVC)
per UL 83, 15 mils nominal thickness, 90°C
temperature rating.
Jacket: Nylon per UL 83, 8 mils nominal
thickness.
Conductor Identification: Pigmented black
and white in pairs; black, white and red in
triads.
Assembly: Pairs or triads assembled with
left-hand lay. Non-wicking fillers included
where required to provide a round cable.
Cable Shield: Aluminum/Polyester tape
overlapped to provide 100% coverage, and a
#16 AWG stranded tinned copper drain wire.
Inner Jacket: Black, flame-retardant Okoseal
per UL Standard 1569. A rip cord is laid
longitudinally under the jacket to facilitate
removal.
C-L-X Sheath: A close-fitting, impervious,
continuously welded and corrugated,
aluminum sheath meeting UL 1569 provides
complete protection against moisture, liquids,
and gases, has excellent mechanical
strength, and provides equipment grounding
through the sheath.
Outer Jacket: Black, flame-retardant
Okoseal per UL Standard 1569.
ApplicationsOkonite C-L-X Single pair or triad type P-OS
instrumentation cables are designed for use
on Class 1 Remote-Control Signaling circuits
or where a 600V cable is desired, as
instrumentation, process control, or computer
cable transmitting signals at levels above 100
milli-volts in circuits where shielding against
external interference is required, but
shielding against interference among groups
is not required. For use indoors or outdoors;
wet or dry locations; in cable trays; in
raceways; supported by a messenger wire;
for direct burial; in Classes I, II, and III,
Divisions 1 and 2 hazardous locations per
NEC Articles 501, 502, 503, 504 and 505; in
Zone 2, Class II Div 2, Class III Div 1 and
Class III Div 2 per CEC.
The overall shield eliminates most of the
static interference from the electric field
radiated by power cables and other electrical
equipment.
The C-L-X sheath provides the physical
protection against mechanical damage as
required in NEC Section 725-8 as well as
complete protection against moisture or
gases entering the cable.
UL® c UL®
OK
ON
ITE
6 P
-OS
1 P
R 1
6A
WG
CU
X-O
LE
NE
(X
LP
E)
E
AB
C
D
FG
H
J
P-O
S 1
PR
16
AW
G C
U P
VC
-N P
VC
(U
L)
For dc service in wet locations, X-Olene
insulation is recommended.
These cables also comply with UL requirements
for Types CL2 and CL3.
Product FeaturesComplete pre-packaged, factory-tested wiring
system—color coded.
C-L-X enclosure permits installation in cable
tray containing light and power cables without a
barrier separator.
Impervious, continuous sheath excludes
moisture, gases and liquids.
Excellent compression and impact resistance.
Lower installed system cost than conduit or
EMT systems.
Suitable for low temperature installation to
-40°C.
Applicable Standards• UL listed for cable tray use, direct burial andsunlight resistant.
• Vertical Tray Flame Tests.IEEE 383-1974, FT4/IEEE 1202,ICEA T-29-520 (210,000 BTU)
• American Bureau of Shipping Type approvedas CWCMC Type MC-HL.
• API Standards 14F and 14FZ.
• ASTM B-8.
• OSHA Acceptable
• UL 2225 Type MC-HL
• UL 83
• UL 1309 (CWCMC) Marine Shipboard
• UL 1569
• UL certified as Marine Shipboard in accordwith IEEE 1580, Marine Shipboard Cable rated600/1000 volts.
• NEC Articles 501, 502, 503, 504 and 505 forClasses I, II and III, Divisions 1 and 2Hazardous Locations.
• NPLF per NEC Code Article 760.
• CSA C22.2 No. 230 Type TC
• CSA C22.2 No. 239 Type ACIC
• cUL Type ACIC-TC complies with CEC Zone2, Class II Div 2, Class III Div 1 and Class III Div2 Hazardous Locations.
Product DataSection 5: Sheet 40
O/20090540
THE OKONITE COMPANYRamsey, New Jersey 07446
Inner J
acket
Thickness-m
ils
Catalo
gNum
ber
Number of P
airs
Cross-S
ectional
Area* S
q. in.
Net Weig
ht
Lbs./1000’
ShipW
eight
Lbs./1000’
Number o
f Tria
ds
#16 AWG - Single Pair & Triad (P-OS) Type MC-HL
▲ Available from our Customer Service Centers.Authorized Stock Item.area for calculation of cable tray fill in accordance with* Cross-sectional
NEC Section 392.22.Optional jacket types available - consult local sales office.Jackets:
C-L-X available on special order.Copper or bronzeC-L-X Type P-OS without the outer Okoseal jacket (not “HL” listed),To Order
change the sixth digit of the catalog number from 3 to 1, for example to order1 pr. 20 AWG with a bare aluminum C-L-X, the catalog number would be 564-10-1212.
Cut lengths of 1000 ft. or longer are subject to a tolerance of + \ -10%;Length Tolerance:less than 1000 feet + \ -15%.
ELECTRICAL SPECIFICATIONS
Conductor Resistance, maximum..............................ohms/1000 ft....................................................................................@20°C @25°C16 AWG ....................................................................4.34............4.43
Insulation Test Voltage (spark test)....................................6000 Volts acDielectric Test Voltage .......................................................2000 Volts acShield Isolation Test
Pair to Cable Shield............................exceeds 100 Megohms-1000 ft.Insulation Resistance Constant @60°F minimum
(natural material typical value................2000 Ohms-1000 ft.Loop Resistance, nominal (2 conductors).............ohms/1000 ft...............................................................................@20°C.............@25°C16 AWG ...............................................................8.68..................8.86
Mutual Capacitance (PF/ft.)*#16.......................................................................60
*Typical Value
UL® c UL®
C-L-X Okoseal-N P-OSUL Type MC-HL and cUL Type ACIC-TC Instrumentation CableSingle Pair or Triad-Overall Shield600 Volts 90°C Rating 600/1000V Marine CableFor Cable Tray Use - Sunlight Resistant - For Direct BurialConductors: #16 AWG; Okoseal Insulation: 15 mils: Nylon Jacket: 8 mils
▲564-60-3401▲564-65-3401
564-60-3403
11
3
66 .3558 .3540 .45
.53 50 .64
.53 50 .64
.67 50 .78
0.320.320.48
182 221190 229247 640
Inner J
acket
Nomin
al O.D
. - in
ches
C-L-X
O.D
. - in
ches
Outte
r Jacket
Thickness-m
ils
Nomin
al Jacket
O.D
. - in
ches
SpecificationsConductors: Bare soft annealed copper, Class B,7-strand concentric per ASTM B-8.Insulation: Flame-retardant Okoseal (PVC) perUL 83, 15 mils nominal thickness, 90°C tem-perature rating.Insulation Jacket: Nylon per UL 83, 4 mils nominalthickness.Conductor Identification: Pigmented black andwhite in pairs, black, white and red in triads.Group Shield: Aluminum polyester tape over-lapped to provide 100% coverage, and a 7-strandtinned copper drain wire, two sizes smaller thanthe conductor. All group shields are completelyisolated from each other.Assembly: Pairs or triads assembled with left-handlay. Non-wicking fillers included where required toprovide a round cable.Cable Shield: Aluminum/polyester tape over-lapped to provide 100% coverage, and a 7-strandtinned copper drain wire, same size as conductor.Inner Jacket: Black, flame-retardant Okoseal perUL Standard 1569. A rip cord is laid longitudinallyunder the jacket to facilitate removal.C-L-X Sheath: A close-fitting, impervious, contin-uously welded and corrugated, aluminum sheathprovides physical protection against mechanicaldamage as required in NEC Section 725-8.Additionaly, C-L-X meets UL 1569 provides com-plete protection against moisture, liquids, andgases, has excellent mechanical strength, andprovides equipment grounding through the sheath.Outer Jacket: Black, flame-retardant Okoseal perUL Standard 1569.Classifications: UL Listed as Type MC-HL Arti-cles 501, 502, and 503 of the National ElectricalCode.
ApplicationsOkonite C-L-X type SP-OS (shielded pairs or tri-ads - overall shield) instrumentation cables aredesigned for use on Class 1 Remote-Control Sig-naling circuits or where a 600V cable is desired,as instrumentation, process control, or computercable transmitting signals at levels above 100mili-volts in circuits where maximum noise protec-tion is required. Protection from interferenceamong groups as well as external sources is pro-vided by individual group shields as well as anoverall cable shield. For use indoors or outdoors;wet or dry locations; in cable trays’ in raceways;supported by a messenger wire; for direct burial;in Classes I, II, and III, Divisions 1 and 2 andClass I, Zones 1 and 2 hazardous locations perNEC Articles 501, 502, 503 and 505; in Zone 2,
Class II Div 2, Class III Div 1 and Class III Div2 per CEC.The isolated individual shields over eachpair, when properly grounded, preventcrosstalk or capacitive coupling betweenadjacent pairs which occurs with ac signals,particularly the pulse type.The overall shield eliminates most of the staticinterference from the electric field radiated bypower cables and other electrical equipment.The C-L-X sheath provides physical protectionagainst mechanical damage as required inNEC Section 725-8 as well as complete pro-tection against moisture or gases entering thecable.For dc service in wet locations, X-Olene insu-lation is recommended.
Product FeaturesIndividual units are completely isolated formaximum noise rejection.C-L-X enclosure permits installation in cabletray containing light and power cables withouta barrier separator.Lower installed system cost than conduit orEMT systems.Suitable for low temperature installation to-40°C.
Applicable Standards• UL listed for cable tray use, direct burial, inducts, and sunlight resistant.• Vertical Tray Flame Tests;IEEE 383-1974, FT4/ IEEE 1202, ICEAT-29-520 (210,000 BTU).• American Bureau of Shipping Type approvedas CWCMC Type MC-HL.• API Standards 14F and 14FZ.• ASTM B-8• OSHA Acceptable• UL 2225 Type MC-HL, UL 83, UL 1309(CWCMC) Marine Shipboard, UL 1569• UL certified to IEEE 1580 - Marine Ship-board Cable rated 600/1000V.• NEC Articles 501, 502, 503, 504 and 505 forClasses I, II, and III, Divisions 1 and 2 Hazard-ous Locations.• NPLF pr NEC Code Article 760.• CSA C22.2 No. 230 Type TC• CSA C22.2 No. 239 Type ACIC• cUL Type ACIC-TC Complies with CECZone 2, Class II Div 2, Class III Div 1, Class IIIDiv 2 Hazardous Locations.
C-L-X® Okoseal-N® SP-OSUL Type MC-HL and cUL Type ACIC-TC Instrumentation CableMultiple Shielded Pairs or Triads - Individual and Overall Shield600 Volts 90°C Rating MC-HL — 600/1000V Marine CableFor Cable Tray Use - Sunlight Resistant - For Direct Burial
Product DataSection 5: Sheet 42
A Bare Stranded CopperConductor
B Okoseal Insulation/Nylon JacketC Tinned Stranded Copper Group
Drain WireD Aluminum/Polyster TapeE Twisted, Shielded Pairs/TriadsF Tinned Stranded Copper Drain WireG Aluminum/Polyester TapeH Rip CordJ Inner Black Okoseal JacketK Impervious, Continuous, Corrugated
Aluminum C-L-X SheathL Outer Black Okoseal Jacket
SP
-OS
24P
R16
AW
GC
UP
VC
-NP
ULR c ULR
� 561-60-3402561-60-3403
� 561-60-3404561-60-3406
2346
40405050
0.450.490.560.66
0.670.700.800.89
50505050
0.760.820.911.00
0.450.530.650.79
234278335421
314369415501
� 561-60-3408561-60-3410
� 561-60-3412
81012
505050
0.700.790.85
0.931.061.11
505050
1.041.171.22
0 .851.081.17
492601674
572681780
561-60-3416561-60-3420
�561-60-3424
162024
505050
0.981.061.12
1.291.341.42
505050
1.401.451.53
1.541.651.84
842977
1118
94811201261
� 561-60-3436561-60-3450
3650
5050
1.371.57
1.691.92
6060
1.822.05
2.603.30
15862124
17732416
561-65-3402� 561-65-3404� 561-65-3408� 561-65-3412
24812
40505050
0.490.610.820.98
0.710.841.061.29
50505050
0.820.951.171.40
0.530.711.081.54
272395637863
439475717969
561-65-3416561-65-3424561-65-3436
162436
505050
1.101.331.58
1.371.641.96
506060
1.481.782.09
1.722.493.43
105814852141
120116722426
� Authorized Stock Item: Available from our Customer Service Centers.
*Cross-sectional area for calculation of cable tray fill in accordance withNEC Section 392.22.
Jackets - Optional jacket types available - consult local sales office.
Copper or bronze C-L-X available on special order.
To order C-L-X Type SP-OS without the outer Okoseal jacket (not “HL”listed), change the sixth digit of the catalog number from 3 to 1, for exam-ple to order 1 pr. 20 AWG with a bare aluminum C-L-X, the catalog numberwould be 564-10-1212.
Length Tolerance: Cut lengths of 1000 ft. or longer are subject to a toler-ance of � �\ 10%; less than 1000 ft. � �\ 15%
O/20050542
C-L-X Okoseal-N SP-OSUL Type MC-HL and cUL Type ACIC-TC Instrumentation CableMultiple Shielded Pairs or Triads - Individual and Overall Shield600V 90°C Rating MC-HL — 600/1000V Marine CableFor Cable Tray Use - Sunlight Resistant - For Direct BurialConductors: #16 AWG; Okoseal Insulation: 15 mils: Nylon Jacket: 4 mils
Product DataSection 5: Sheet 42
ELECTRICAL SPECIFICATIONSConductor Resistance, nominal ........................ohms/1000 ft. @20°C
16 AWG......................................................................4.1Insulation Test Voltage (spark test) ...............................6000 Volts acDielectric Test Voltage .................................2000 Volts ac for 60 sec.Insulation Resistance Constant @60°F minimum
(natural material typical value) ..2000 Megohms-1000 ft.Loop Resistance, nominal (2 conductor)............ohms-1000 ft @20°C
16 AWG......................................................................8.2Mutual Capacitance (PF/ft.)*
#16 ..............................................................................60*Typical Value
Nomin
alCab
le
O.D. -
Inch
es
Number
of Triads
Number
of Pairs
Inner
Jack
et
Thicknes
s - mils
Nomin
alCore
O.D. -
Inch
es
Outer Ja
cket
mils
C-L-X
O.D. -
Inch
es
ShipW
eight
Lbs./10
00’
Cross
-Sec
tional
Area*
Sq. In.
NetW
eight
Lbs./10
00’
Catalo
gNum
ber
THE OKONITE COMPANYRamsey, New Jersey 07446
ULRc ULR
#18 AWG tinned copper,Class M, stranded per ASTM B-174.
Okolene® (Polypropylene)per UL 13 and 2250, 32 mils nominalthickness, 75°C temperature rating.
Pigmented or-ange and blue in pairs, orange conductornumerically printed for group identification.
Aluminum/Polyester tapeoverlapped to provide 100% coverage,and a Class M tinned copper drain wire,two sizes smaller than the conductor. Allmulti-pair shields are isolated from eachother.
Pairs assembledwith a left-hand lay. Cable fillers includedwhere required to provide a round cable.
Alumi-num/Polyester tape overlapped to provide100% coverage, and a class M strandtinned copper drain wire, same size asconductor.
Orange, flame-retardant, Okosealper UL 13 and 2250. A rip cord is laid lon-gitudinally under the jacket to facilitateremoval.
UL Listed asPLTC-Power Limited Tray Cable and asITC-ER - Instrument Tray Cable/ExposedRun for use in accordance with Article 727and Article 725 of the National ElectricalCode.
Cables comply with ISA-S-50-02, UL 2250and UL 13 for Fieldbus circuits and CL2and CL3.
Okonite® OKOBUS® cables are designedfor use in rugged plant environments utiliz-ing networked discrete or processautomation and control. ITC-ER (Instru-ment Tray Cable - Exposed Run)eliminated the need for conduit when in-stalled in accordance with NEC Article727.4(6). Fully complies with ANSI/ISA50.02 part 2 for Fieldbus Cable.
The isolated individual shields overeach pair, when properly grounded,
prevent crosstalk or capacitive cou-pling between adjacent pairs whichoccurs with ac signals, particularlythe pulse type.
The overall shield or multi pair cableseliminates most of the static interferencefrom the electrical field radiated by powercables and other electrical equipment.
• Passes the UL 13 and IEEE 383 verticaltray flame tests.
• Single pair passes IEEE 1202 verticaltray flame test.
• Sunlight & oil resistant.
• UL listed for direct burial.
• Individual pairs are completely isolated.
• 100% shield coverage for reduced elec-tromagnetic noise pick-up.
• Excellent external noise rejection.
• Excellent weathering characteristics.
• OSHA Acceptable.
• Flexible, easy to handle and terminate.
Tinned Copper StrandedConductorPolypropylene InsulationTinned Stranded Copper GroupDrain WireAluminum/Polyester TapeTwisted, Shielded PairsAluminum/Polyester TapeTinned Stranded Copper DrainWireRip CordOrange Okoseal Jacket
Okobus
Single Pair or Multiple Shielded Pairs - Overall Shield300 Volts 75°C Rating
ULR
� 264-92-3901261-92-3302
12
4550
0.340.55
0.090.24
62148
73172
261-92-3304261-92-3063
46
6060
0.710.80
0.400.50
212264
251303
261-92-3308261-92-3312261-92-3316
81216
707070
0.911.041.17
0.650.851.08
340474580
404554660
261-92-3320261-92-3324
2024
8080
1.321.46
1.371.67
722880
8281023
� area for calculation of cabletray fill in accordance with NEC Section 392.22
Cut lengths of 1000 feet orlonger are subject to a tolerance of � 10%; lessthan 1000 feet � 15%.
� Available from ourCustomer Service Centers.
E/13110547
ULR
Okobus
Single Pair or Multiple Shielded Pairs - Overall Shield 300 V 75°C Rating
a) Characteristic Impedance, zo, at fr(31.25kHz), minimum ........................100 ohms
b) Maximum attenuation at1.25 fr (39 kHz)..................................3.0 dB/km
c) Maximum capacitive unbalanceto shield...............................................2 nF/km
d) Maximum DC resistance(per conductor) ................................24 ohms/km
e) Maximum propagation delaychange 0.25 fr to 1.25 fr.....................1.7 �s/km
f) conductor cross-sectional area nominal(wire size) ..................................0.8 mm2 (#18 AWG)
g) Minimum shield coverage.....................100%
�
THE OKONITE COMPANYRamsey, New Jersey 07446
SpecificationsConductors: #18 AWG tinned copper,Class M, stranded per ASTM B-174.
Insulation: Okolene® (Polypropylene)per UL 13 and 2250, 32 mils nominalthickness, 75°C temperature rating.
Conductor Identification: Pigmented or-ange and blue in pairs, orange conductornumerically printed for group identification.
Pair Shield: Aluminum/Polyester tapeoverlapped to provide 100% coverage,and a Class M tinned copper drain wire,two sizes smaller than the conductor. Allmulti-pair shields are isolated from eachother.
Multiple Pair Assembly: Pairs assembledwith a left-hand lay. Cable fillers includedwhere required to provide a round cable.
Multiple Pair Cable Shield: Alumi-num/Polyester tape overlapped to provide100% coverage, and a class M strandtinned copper drain wire, same size asconductor.
Inner Jacket: Orange, flame-retardant,Okoseal per UL 13 and 2250. A rip cord islaid longitudinally under the jacket to facili-tate removal.
C-L-X Sheath: A close-fitting, impervious,continuously welded and corrugated, alu-minum sheath provides completeprotection against moisture, liquids, andgases, has excellent mechanical strength,and provides equipment groundingthrough the sheath.
Outer Jacket: Orange, flame-retardant,Okoseal per UL 13 and 2250.
Classifications: UL Listed asPLTC-Power Limited Tray Cable and asITC-HL - Instrument Tray Cable/Hazard-ous Locations for use in accordance withArticle 727 and Article 725 of the NationalElectrical Code.
Cables comply with ISA-S-50-02, UL 2250and UL 13 for Fieldbus circuits and CL2and CL3.
ApplicationsC-L-X OKOBUS® cables are designed foruse in rugged plant and off-shore marine
environments utilizing networked discreteor process automation and control.ITC-HL (Instrument Tray Cable - Hazard-ous Locations) eliminates the need forconduit when installed in accordancewith NEC Article 501.10(A)(1)(4)"ITC-HL" installations. Fully complieswith ANS/ISA 50.02 Part 2 FieldbusCable.
The isolated individual shields overeach pair, in SP-OS cables, whenproperly grounded, prevent crosstalkor capacitive coupling between adja-cent pairs which occurs with acsignals, particularly the pulse type.
The overall shield eliminates most of thestatic interference from the electrical fieldradiated by power cables and other elec-trical equipment.
The C-L-X sheath provides additionalelectrical shielding and physical protec-tion against mechanical damage as wellas complete protection against moistureor gases entering the cable.
Product Features• Passes the UL 13 and IEEE 383 verticaltray flame tests.
• Passes IEEE 1202 vertical tray flametest.
• Sunlight & oil resistant.
• UL listed for direct burial.
• Complete pre-packaged, factory-testedwiring system-color coded.
• C-L-X enclosure permits installation incable tray containing lighting and power ca-bles without a barrier separator.
• Individual pairs are completely isolated.
• Impervious, continuous sheath excludesmoisture, gases and liquids.
• In addition, the aluminum CLX sheathexceeds the equipment grounding require-ments of NEC Section 250.118 and250.122, and can be used as the equip-ment grounding conductor in non-HLareas.
• Lower installed system cost than conduitor EMT systems.
A Tinned Copper StrandedConductor
B Polypropylene InsulationC Tinned Stranded Copper Group
Drain WireD Aluminum/Polyester TapeE Twisted, Shielded PairsF Aluminum/Polyester TapeG Tinned Stranded Copper Drain
WireH Rip CordJ Inner Orange Okoseal JacketK Impervious, Continuous, Corrugated
Aluminum C-L-X SheathL Outer Orange Okoseal Jacket
Product DataSection 5: Sheet 48
Okobus C-L-XSingle Pair: Type P-OS - Multi Pair: Type SP-OSType PLTC & Type ITC-HL Fieldbus CableSingle Pair or Multiple Shielded Pairs - Overall Shield300 Volts 75°C Rating
ULR
� 564-92-3301561-92-3302
12
4550
0.340.55
0.530.80
4050
0.620.91
0.300.65
155311
194391
561-92-3304561-92-3306
46
6060
0.710.81
0.931.06
5050
1.041.17
0.851.08
400493
480573
561-92-3308561-92-3312561-92-3316
81216
707070
0.911.041.17
1.151.341.47
505050
1.261.451.58
1.251.651.96
587759902
693902
1045
561-92-3320561-92-3324
2024
8080
1.331.46
1.641.78
5050
1.751.89
2.412.81
10721308
12361495
� Cross-sectional area for calculation of cable tray fillin accordance with NEC Section 392.22.Copper or bronze C-L-X available on special order.Length Tolerance: Cut lengths of 1000 feet or longerare subject to a tolerance of � 10%; less than 1000feet � 15%.� Authorized Stock Item: Available from our Cus-tomer Service Centers.
G/20020548
ULR
Okobus — C-L-XSingle Pair Type P-OS - Multi Pair Type SP-OSType PLTC & Type ITC-HL Fieldbus CableSingle Pair or Multiple Shielded Pairs - Overall Shield 300 V 75°C Rating#18 AWG
Product DataSection 5: Sheet 48
Cross
-Sec
tional
Area �
(sq
in)
Inner
Jack
et
Thicknes
s - mils
Nomin
alCore
O.D. In
ches
Outer Ja
cket
mils
C-L-X
O.D. In
ches
Catalo
gNum
ber
Number
of Pairs
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Nomin
alCab
le
O.D. -
Inch
es
CHARACTERISTICS
a) Characteristic Impedance, Zo, at fr(31.25kHz), minimum ............................100 ohms
b) Maximum attenuation at1.25 fr (39 kHz)......................................3.0 dB/km
c) Maximum capacitive unbalanceto shield...................................................2 nF/km
d) Maximum DC resistance(per conductor) ....................................24 ohms/km
e) Maximum propagation delaychange 0.25 fr to 1.25 fr.........................1.7 �s/km
f) conductor cross-sectional area nominal(wire size) ......................................0.8 mm2 (#18 AWG)
g) Minimum shield coverage .........................100%
THE OKONITE COMPANYRamsey, New Jersey 07446
SpecificationsConductors: Bare copper, Class B,stranded per ASTM B8.
Insulation: X-Olene� (XLPE), per UL 13,2250 & 1569, 30 mils nominal thickness,90°C temperature rating. MeetsMIL-DTL-1377H, section 4.8.4.1.2 ColdBend at -66°C and ASTM D746-04brittlepoint at -76°C.
Conductor Identification: Pigmentedblack and white in pairs, black, red andwhite in triads; white conductor numericallyprinted for group identification.
Pair Shield: Aluminum/Polyester tapeoverlapped to provide 100% coverage, anda Class B tin coated copper drain wire, twosizes smaller than the conductor. Allmulti-pair shields are isolated from eachother.
Multiple Pair Assembly: Pairs/triads as-sembled with a left-hand lay. Cable fillersincluded where required to provide a roundcable.
Multiple Pair Cable Shield: Alumi-num/Polyester tape overlapped to provide100% coverage, and a class B strand tincoated copper drain wire, same size asconductor.
Inner Jacket: Black, flame-retardant, lowtemperature Okoseal® (PVC) per UL 13and UL 2250. The inner jacket meets thethickness requirements of UL 1277. A ripcord is laid longitudinally under the jacketto facilitate removal.
C-L-X Sheath: A close-fitting, impervious,continuously welded and corrugated, alu-minum sheath provides completeprotection against moisture, liquids, andgases, has excellent mechanical strength,and provides equipment grounding throughthe sheath.
Outer Jacket: Black, flame-retardant, lowtemperature Okoseal per UL 13 and UL2250.
ApplicationsITC-HL and MC-HL cables eliminate theneed for conduit when installed in accor-dance with NEC Article 501.10(A)(1)(4)"ITC-HL" or 501.10(A)(1)(3) "MC-HL" in-stallations. UL listed as PLTC-PowerLimited Tray Cable and as ITC-HL - Instru-ment Tray Cable/Hazardous Locations foruse in accordance with Article 725 (Class1, 2 & 3) and Article 727 of the NationalElectrical Code.
UL listed as MC-HL for use in Class I, II, andIII, Divisions 1 and 2 hazardous location in ac-cordance with NEC Articles 501, 502, 503, 504& 505; in Zone 2, Class II Div 2, Class III Div 1and Class III Div 2 per CEC.
The isolated individual shields over each pair, inSP-OS cables, when properly grounded, pre-vent crosstalk or capacitive coupling betweenadjacent pairs while the overall shield elimi-nates most of the static interference from theelectrical field radiated by power cables andother electrical equipment.
Product FeaturesComplete pre-packaged, factory-tested wiringsystem-color coded.C-L-X enclosure permits installation in cabletray containing lighting and power cables with-out a barrier separator.Lower installed system cost than conduit orEMT systems.
Applicable Standards• UL listed for cable tray use, direct burial, inducts, and sunlight resistant.
• Vertical Tray Flame Tests;IEEE 383-1974 & FT4/IEEE 1202.
• UL listed at -50°C. Also, meets the CSA 22.2No.3 Cold Impact Test at -45°C.
• API Standards 14F and 14FZ.
• ASTM B8.
• OSHA Acceptable
• UL 2225 Type MC-HL & UL 1569
• NEC Articles 501, 502, 503, 504 and 505 forClasses I, II, and III, Divisions 1 and 2 HazardousLocations.
• UL listed as PLTC-Power Limited Tray Cableand as ITC-HL - Instrument Tray Cable/Hazard-ous Locations for use in accordance with Article725 (Class 1, 2 & 3) and Article 727 of the Na-tional Electrical Code.
• NPLF per NEC Code Article 760.
• CSA C22.2 No. 230 Type TC
• CSA C22.2 No. 239 type ACIC
• cUL listed as Type ACIC-TC complies with CECZone 2, Class II Div 2, Class III Div 1, Class III Div2 Hazardous Locations.
Product DataSection 5: Sheet 49
C-L-X� X-Olene� SP-OSUL Type MC-HL, PLTC, ITC-HL and cUL ACIC-TC Instrumentation CableMultiple Shielded Pairs/Triads - Overall Shield600 Volts 90°C Rating: UL MC-HL and cUL ACIC-TC300 Volts 90°C Rating: UL PLTC & ITC-HLFor Cable Tray Use Sunlight Resistant For Direct Burial -50°C
A Copper Stranded ConductorB X-Olene InsulationC Tin Coated Copper Group
Drain WireD Aluminum/Polyester TapeE Twisted, Shielded PairsF Aluminum/Polyester TapeG Tin Coated Copper Drain
WireH Rip CordJ Inner Okoseal JacketK Impervious, Continuous, Corrugated
Aluminum C-L-X SheathL Outer Okoseal Jacket
ULR c ULR
567-70-3302567-70-3304567-70-3308567-70-3312567-70-3324567-70-3336
248
122436
45 0.5060 0.6760 0.8380 1.0080 1.3480 1.55
0.71 50 0.820.89 50 1.001.06 50 1.171.29 50 1.401.64 60 1.781.92 60 2.05
0.530.791.081.542.483.29
253365503693
11251545
333445583799
12901835
567-71-3302567-71-3304567-71-3308567-71-3312567-71-3324
248
1224
60 0.6260 0.7380 0.9880 1.1580 1.58
0.84 50 0.950.97 50 1.081.24 50 1.351.47 50 1.581.96 60 2.09
0.710.921.431.963.42
326428658860
1505
406508764
10031760
� Cross-sectional area for calculation of cable tray fill inaccordance with NEC Section 392.22.Jackets - Optional jacket types available - consult localsales office.Copper or bronze C-L-X available on special order.To order without the outer Okoseal jacket (not "HL" listed),change the sixth digit of the catalog number from 3 to 1, forexample to order 2 pr. 16 AWG with a bare aluminum C-L-X,the catalog number would be 567-70-1402.Length Tolerance: Cut lengths of 1000 feet or longer aresubject to a tolerance of � 10%; less than 1000 feet � 15%.
K/21050549
C-L-X� X-Olene� SP-OSUL Type MC-HL, PLTC, ITC-HL and cUL ACIC-TC Instrumentation CableMultiple Shielded Pairs/Triads - Overall Shield600 Volts 90°C Rating: UL MC-HL and cUL ACIC-TC300 Volts 90°C Rating: UL PLTC & ITC-HLFor Cable Tray Use Sunlight Resistant For Direct Burial -50°C
Product DataSection 5: Sheet 49
Cross
-Sec
tional
Area �
(sq
in)
Inner
Jack
et
Thicknes
s - mils
Nomin
alCore
O.D. In
ches
Outer Ja
cket
mils
C-L-X
O.D. In
ches
Catalo
gNum
ber
Number
of Triads
Approx Net
Weig
ht
(lbs/1
000’)
Approx Ship
Weig
ht
(lbs/1
000’)
Nomin
alCab
le
O.D. -
Inch
es
ELECTRICAL SPECIFICATIONS
Conductor Resistance, nominal - ohms/1000 ft......@20°C ..........@25°C16 AWG ................................................................4.34 .................4.4318 AWG ................................................................6.93 .................7.07
Insulation Test Voltage (spark test) ....................................7500 Volts ac
Dielectric Test Voltage .......................................................3000 Volts ac
Insulation Resistance Constant @60°F minimum ...10,000 ohms-1000 ft.
Loop Resistance, nominal (2 cdr.) - ohms/1000 ft .@20°C ..........@25°C16 AWG .................................................................8.68 .................8.8618 AWG .................................................................13.9 .................14.2
Mutual Capacitance (PF/ft.)*#16 ....................................................................................................23#18 ....................................................................................................21
*Typical Value
THE OKONITE COMPANYRamsey, New Jersey 07446
#16 AWG567-70-3402567-70-3404567-70-3408567-70-3412567-70-3424567-70-3436
248
122436
60 0.5860 0.7080 0.9280 1.1080 1.44
110 1.82
0.80 50 0.910.93 50 1.041.19 50 1.301.37 50 1.481.78 60 1.912.19 60 2.32
0.650.851.331.732.874.23
325 405424 504650 752842 985
1450 16402145 2480
567-71-3402567-71-3404567-71-3408567-71-3412567-71-3424
248
1224
60 0.6460 0.7580 1.0680 1.2680 1.65
0.89 50 1.001.02 50 1.131.34 50 1.451.56 60 1.692.01 60 2.14
0.791.001.642.243.61
376 456500 580800 945
1090 12351914 2199
#18 AWG
Number
of Pairs
ULRc ULR
X-Olene Okoseal® ®
UL Type TC-ER/ITC -ER and cUL Type CIC-TC*or Oko-Marine Cable600 Volt Instrumentation/Signal Cable600/1000V Marine Shipboard CableSingle Pair/Triads or Multiple Pairs/Triads Type P-OSFor Cable Tray Use - Sunlight Resistant - For Direct Burial*cUL CIC-TC-ER sizes 14 AWG & larger
A Copper Strand ConductorX-Olene InsulationB
C Tinned Stranded Copper Drain WireD Aluminum/Polyester TapeE Twisted PairsF Rip CordG Okoseal Jacket
Product DataSection 5: Sheet 50
triads; white conductor numerically printed
for group identification.
Cable Shield: Aluminum/Polyester tape
overlapped to provide 100% coverage, and
a tinned copper. Class M drain wire same
size as conductor. All multi-unit shields are
isolated from each other.
Multiple Unit Assembly: Pairs/Triads
assembled with a left-hand lay. Cable
fillers, included where required, providing a
round cable.
Jacket: Black Okoseal jacket. Complies
with UL 1277, UL 1309 & IEEE 1580 PVC,
Type T, thermoplastic polyvinyl chloride
jacket.
UL Listed as Type TC-ER cable with a
sunlight resistant jacket and for direct
burial.
UL Listed as Type OKO-MARINE signal
cable to the requirements of UL 1309. Also,
UL certified as meeting the requirements of
IEEE 1580 — Marine Cable.
Product Features• For cable tray use and direct burial.• Sunlight resistant.• Insulated conductors are UL rated 90°Ccontinuous rating in wet or dry locations.• Flame Retardant - passes the vertical trayflame test requirements of IEEE 383-1974& 1202-2010 and UL 1277.
• X-Olene Okoseal Type TC-ER/ITC-ER
cables are quality control inspected to meet
or exceed applicable industry standards.
• Resistant to moisture and most chemical
atmospheres.
• Thermal stability at elevated
temperatures.
• CSA C22.2 No. 239 & 230 Type
CIC-TC-ER*.
• CSA C22.2 No. 245 Type Marine
Shipboard.
• Passes -40°C cold bend test.
InsulationX-Olene is Okonite's trade name for
®
its cross-linked polyethylene
insulation, with high dielectric strength.
Cable JacketThe Okoseal (PVC) jacket supplied
with this cable is mechanically rugged
and has excellent resistance to acids
and most chemicals and is rated for
low temperature installations.
ApplicationsX-Olene Okoseal 600 volt shielded
instrumentation cables are designed
for use in rugged plant environments,
such as Offshore Rig Projects, on
Class 1 Remote-Control Signaling
circuits or where a 600V
instrumentation or control cable is
desired.They are designed for use
indoors or outdoors; wet or dry
locations; in cable trays; in raceways;
supported by a messenger wire; and
for direct burial. Can be installed as
Type TC/ITC in Class I, Division 2;
Class II, Division 2; Class III, Division
1; and Zone 2 hazardous locations in
accordance with NEC Articles 501.10,
502.10, 503.10, and 505.15.
TC-ER (Tray Cable - Exposed Run)
eliminates the need for conduit when
installed in accordance with NEC
Article 336.10(7). These cables are
also UL labeled Okomarine and are
listed for marine applications.
SpecificationsInsulated Conductors: Bare soft
annealed copper, Class B stranded
per ASTM B8.
Insulation: X-Olene (XLPE), per®
UL 13, 30 mils nominal thickness,
90°C temperature rating. Meets or
exceeds requirements of UL 1277,
UL 1309 Type X90 and IEEE 1580
Type X cross-linked polyethylene
insulation.
Color Coding: Pigmented black and
white in pairs, black, red and white in
UL® c UL®
OK
ON
ITE
6 P
-OS
12
PR
16
AW
G C
U X
-OL
EN
E (
XL
PE
)
OK
ON
ITE
6 P
-OS
1 P
R 1
6A
WG
CU
X-O
LE
NE
(X
LP
E)
C
A
B
D
E
F
G
Product DataSection 5: Sheet 50
N/21060550
THE OKONITE COMPANYRamsey, New Jersey 07446
Jacket Thic
kness-mils
#16 AWG
▲267-40-3401▲267-41-3401
11
4545
0.350.37
0.100.11
7789
8597
267-40-3402267-40-3404267-40-3408267-40-3412
248
12
45608080
0.520.680.900.99
0.220.360.570.77
173244415521
178278430606
267-40-3416267-40-3420267-40-3424267-40-3436
16202436
80808080
1.181.311.401.60
1.101.351.542.01
684816937
1299
756915
10941433
268-38-4402268-38-4404268-38-4408268-38-4412
24812
60608080
0.650.781.021.21
0.330.470.811.14
240307559742
261366617809
268-38-4416268-38-4420268-38-4424
162024
808080
1.361.501.63
1.461.772.09
93111181296
108312461430
#14 AWG
Catalo
gNum
ber
Number of P
airs
Nomin
al Cable
O.D
. - In
ches
Cross-S
ectional
Area
†(s
q. in.)
Approx. N
et Weig
ht
(lbs./1
000’)
Approx. S
hipW
eight
(lbs./1
000’)
Number o
f Tria
ds
267-40-3501267-41-3501
11
4545
0.370.40
0.110.13
99103
115131
267-40-3502267-40-3504267-40-3508267-40-3512
248
12
60608080
0.590.720.971.15
0.270.410.741.03
237337570732
258366620799
16202436
808080110
1.291.421.571.57
1.311.591.932.92
914108812641189
1066124713982198
267-40-3516267-40-3520267-40-3524267-40-3536
267-38-3502267-38-3504267-38-3508267-38-3512
248
12
60608080
0.630.771.031.22
0.310.460.841.18
291430731978
3144597891103
267-38-3516267-38-3520267-38-3524
162024
808080
1.381.521.68
1.491.822.22
123814961748
139016301972
UL® c UL®
ELECTRICAL SPECIFICATIONS
Conductor Resistance, nominal-ohms/1000 f..........@20°C..........@25°C16 AWG ....................................................................4.34................4.4314 AWG ....................................................................2.68................2.73Insulation Test Voltage (spark test)....................................8000 Volts ac
Dielectric Test Voltage ........................................................1500 Volts acInsulation Resistance Constant @60°F minimum...10,000 ohms-1000 ft.Loop Resistance, nominal (2 cdr.) - ohms/1000 ft @20°C............@25°C16 AWG ..................................................................8.68...................8.8614 AWG...................................................................5.36...................5.46Mutual Capacitance (PF/ft.)*#16......................................................................................................23#14......................................................................................................25
*Typical Value
▲ Available from our CustomerAuthorized Stock Item.Service Centers.† area for calculation of cable tray fill inCross-sectionalaccordance with NEC Section 392.22.
Cut lengths of 1000 feet or longer areLength Tolerance:subject to a tolerance of ± 10%; less than 1000 feet ± 15%.
X-Olene Okoseal® ®
UL Type TC-ER/ITC -ER and cUL Type CIC-TC*or Oko-Marine Cable600 Volt Instrumentation/Signal Cable600/1000V Marine Shipboard CableSingle Pair/Triads or Multiple Pairs/Triads Type P-OSFor Cable Tray Use - Sunlight Resistant - For Direct Burial*cUL CIC-TC-ER sizes 14 AWG & larger
ApplicationsOkonite X-Ray cables are suitable for use onX-Ray apparatus for medical, industrial, re-search and control applications. They givetrouble-free performance where pulse typehigh voltages are required. Although primar-ily used with medical diagnostic imagingequipment, Okonite X-Ray cables are alsoused with equipment in industrial applica-tions as well as in research projects wherehigh voltages, low power are required.Okonite LOW NOISE X-Ray cables havespecifically been designed for use wheresensitive measurements are required. TheseLOW NOISE cables are manufactured andassurance tested to meet less than 10 pico-coulumb discharge thereby reducing noise toa minimum.Okonite LOW NOISE X-Ray cables are of-fered at 65kV, 75kV, 100kV, 230kV and250kV dc ratings.Typically, Okonite X-Ray cables are used tosupply the anode and cathode voltages tothe X-Ray tube. Since one terminal operatesat a negative potential and the other at apositive potential, the voltage across the X-Ray tube is twice (2X) the rated voltage ofthe cable.The two usual constructions are (1) threeconductor (3/C) used on typical cathode ca-ble installations, and (2) four conductor (4/C)utilized on installations with a grid controlledlead. Upon request, designs and construc-tions can be developed for specialapplications.
Product Features• Low Noise - < 10 pC @ 200 Vac/mil of in-sulation to 42 kV max.• Performance tested for long trouble-freeservice.• Small diameter.• Flexible construction.• Excellent flexing endurance.• Mechanically rugged.• Easy to strip and terminate.• Resistant to most oils and chemicals.• Complies with NEMA Standard XR-7where applicable.
InstallationThe minimum bending radius for permanentinstallation or flexing in service is four timesthe cable diameter.
SpecificationsCable Core: Each Low Noise cable corecontains two insulated filament conduc-tor. In 65, 75, and 100kV cable filamentconductors are #15 AWG (19x)[1.65mm2] tinned copper insulated withheat sealed color coded polyester tape.In 230kV cables, the filament wires are#16 AWG (19x) [1.31mm2] tinned copper.The 250 kV cable filaments are #14 AWG(19x) [2.08mm2] tinned copper. Both the230 and 250kV filament wires are insu-lated with an extrusion of ETFE. Fourconductor cables include one #20 AWG(7x) [0.52mm2] copperweld conductor perASTM B-45 insulated with heat sealedpolyester and shielded with metalized redpolyester.The tinned copper uninsulated conductorin 3/C 65, 75, 100 and 230kV cables issegmented into two #18 AWG [0.83mm2]flex stranded wires. The 4/C uninsulatedconductor is segmented into three #18AWG wires. A single #12 AWG (19x) wireis used in the 250kV cable.Core Shield: An extruded layer of semi-conducting compound encapsulates thecomposite core assembly.High Voltage Insulation: Okonite’s pre-mium EPR (ethylene-propylene rubber)insulation. This ozone resistant high volt-age dielectric is extruded in tandem withthe semiconducting layers which insuresan intimate and contaminant free inter-face between the layers.Insulation Shield: A strippable extrudedlayer of semiconducting EPR compoundis applied directly over the insulation.Shield: A braid of tinned copper wires isapplied directly over the insulation shield.Minimum coverage indicated in table.Jacket: A flexible Okoseal (speciallycompounded PVC) jacket is extrudedover the shield to provide additional me-chanical strength and resistance to mostoils and chemicals.
Okonite X-Ray/Hi-Voltage CableLow Noise65kV, 75kV, 100kV, 230kV and 250kV dc RatingThree Conductor or Four Conductor
Product DataSection 6: Sheet 1
A Coated Stranded CopperConductors
B Polyester InsulationC Extruded Semiconducting LayerD Primary Insulation – OkoguardE Extruded Insulation ShieldF Coated Copper BraidG Jacket – Okoseal
A
B
C
E
F
G
D
65kV
3 Conductors2-#15 AWG insulated1-(2-#18 AWG)uninsulated
504-22-6436 80 yes Gray 0.465 11.81 0.605 15.36 219 33 243 36
75kV
3 Conductors2-#15 AWG insulated1-(2-#18 AWG)uninsulated
504-22-3437504-22-3495
8095
no Gray 0.510 12.95 0.650 16.50247258
3738
279297
4244
4 Conductors2-#15 AWG 1-#20AWG Copperweld,insulated1-(3-#18 AWG)uninsulated
504-22-4464 80 no Gray 0.570 14.48 0.715 18.20 296 44 335 50
75kVExtraSmall
Diameter
3 Conductors2-#15 AWG insulated1-(2-#18 AWG)uninsulated
504-22-3415 80 no Gray 0.490 12.45 0.620 15.75 228 34 267 40
100kV
3 Conductors2-#15 AWG insulated1-(2-#18 AWG)uninsulated
� 504-22-3436� 504-22-4437
80noyes
Gray 0.620 15.75 0.785 19.94 341 51 380 57
4 Conductors2-#15 AWG 1-#20AWG Copperweld,insulated 1-(3#18AWG) uninsulated
504-22-4436504-22-4437
80noyes
Gray 0.660 16.75 0.845 21.46 391 58 446 66
230kV
3 Conductors2-#16 AWG insulated1-(2-#18 AWG)uninsulated
� 504-22-741080 no Black
0.980� .020
24.89� .51
1.250� .025
31.75� .64
759 113 849 126
250kV
3 Conductors2-#14 AWG insulated1-(#12 AWG)uninsulated
504-22-9430 80 no Black1.280� .020
32.51� .51
1.505� .025
38.23� .64
1119 167 1250 186
Electrical Characteristics
Rated VoltageRectified dc kV (2)
Number ofConductors
Core to ShieldCapacitance ± 10%
4/C only: Copperweld grid lead capacitance = 70 pF/ft. (230 pF/m).
pF/ft. pF/m Conductor resistance @ 25°C:
6575 (ESD)7575
100100230250
33343433
5249.5475740493531
170162154187131159115101
#16 AWG (1.31 mm2) tinned copper = 4.18 ohms/1000 ft (1.37 ohms/100 m)#15 AWG (1.65 mm2) tinned copper = 3.51 ohms/1000 ft (1.15 ohms/100 m)#18 AWG (0.83 mm2) tinned copper = 7.16 ohms/1000 ft (2.34 ohms/100 m)
2 X #18 AWG (0.83 mm2) tinned copper = 3.58 ohms/1000 ft (1.17 ohms/100 m)3 X #18 AWG (0.83 mm2) tinned copper = 2.39 ohms/1000 ft (0.78 ohms/100 m)
#20 AWG (0.52 mm2) copperweld = 24.12 ohms/1000 ft (7.91 ohms/100 m)#14 AWG (2.08 mm2) tinned copper = 2.73 ohms/1000 ft (0.895 ohms/100 m)#12 AWG (3.31 mm2) tinned copper = 1.72 ohms/1000 ft (0.564 ohms/100 m)
(2) Voltage rating is between the conductor and the shielding braid.
C/06010601
Product DataSection 6: Sheet 1
� Authorized stock Item. Available from our Customer Service Centers.
(1) Cable is helically wrapped with a cellophane tape to maintain cleanliness during installation and includes a pull cord for ease of removal.
- Designs for special applications upon request.- Refer to Product Data Section 6 Sheet 1 for X-Ray Cable - Low Noise constructions.
Catalo
gNum
ber
Net. W
t.(k
g/100m
)
Jack
etColo
r
Insu
latio
nO.D
.
mm
±0.2
5
Insu
latio
nO.D
.
Inch
es±
0.010
Jack
etO.D
.
Inch
es±
0.015
Jack
etO.D
.
mm
±0.3
8
Tinned
CopperBra
id
Covera
ge (%)
Descr
iptio
n
Net. W
t.(lb
s/100
0 ft.)
Approx.
ShipW
eight
(kg./1
00m
)
Approx.
ShipW
eight
(lbs./
1000
’)
Okonite X-Ray/Hi-Voltage CableLow Noise65kV, 75kV, 100kV, 230kV and 250kV dc RatingThree Conductor or Four Conductor
Cellophan
e Wra
p(1
)
THE OKONITE COMPANYRamsey, New Jersey 07446
ApplicationsOkonite X-Ray cables are suitable for use onX-Ray apparatus for medical, industrial, re-search and control applications. They givetrouble-free performance where pulse typehigh voltages are required. Although primar-ily used with medical diagnostic imagingequipment, Okonite X-Ray cables are alsoused with equipment in industrial applica-tions as well as in research projects wherehigh voltages, low power are required.
Typically, Okonite X-Ray cables are used tosupply the anode and cathode voltages tothe X-Ray tube. Since one terminal operatesat a negative potential and the other at apositive potential, the voltage across the X-Ray tube is twice (2X) the rated voltage ofthe cable.
The two usual constructions are (1) threeconductor (3/C) used on typical cathode ca-ble installations, and (2) four conductor (4/C)utilized on installations with a grid controlledlead. Upon request, designs and construc-tions can be developed for specialapplications.
Product Features• Performance tested for long trouble-freeservice.• Small diameter.• Flexible construction.• Excellent flexing endurance.• Mechanically rugged.• Easy to strip and terminate.• Resistant to most oils and chemicals.• Complies with NEMA Standard XR-7where applicable.
InstallationThe minimum bending radius for permanentinstallation or flexing in service is four timesthe cable diameter.
SpecificationsCable Core: Each cable contains two #15AWG (19x) [1.65mm2] tinned copper filamentwires insulated with heat sealed color codedpolyester tape. Three conductor cores in-clude two uninsulated #18 AWG [0.83mm2]flex stranded tinned copper wires. Four con-ductor cables include one #20 AWG (7x)
[0.52mm2] copperweld conductor perASTM - 45 insulated with heat sealedpolyester and shielded with metalized redpolyester. The four conductor core in-cludes three uninsulated #18 AWG flexstranded tinned copper wires.
All conductors are twisted together into acomposite assembly.
Core Shield: An extruded layer of semi-conducting compound encapsulates thecomposite core assembly.
Insulation: Okonite’s premium high volt-age EPR (ethylene propylene rubber)insulation is extruded in tandem with thesemiconducting compound ensuring anintimate contaminant free bond betweenthe layers
Shield: A semiconducting tape is appliedover the insulation with a tinned copperwire braid. Minimum coverage indicatedin table.
Jacket: A light gray flexible Okoseal(specially compounded PVC) jacket isextruded over the shield to provide addi-tional mechanical strength and resistanceto most oils and chemicals.
Okonite X-Ray/Hi-Voltage Cable65kV, 75kV and 100kV dc RatingThree Conductor or Four Conductor
Product DataSection 6: Sheet 2
A Coated Stranded CopperConductors
B Polyester InsulationC Extruded Semiconducting LayerD Insulation – OkoguardE Semiconducting TapeF Coated Copper BraidG Jacket – Okoseal
A
B
C
E
F
G
D
65kV
3 Conductors2-#15 AWG insulated1-(2-#18 AWG)uninsulated
504-22-6040504-22-6041
80yesno
Gray 0.465 11.81 0.605 15.40 219 33 252 38
75kV
3 Conductors2-#15 AWG insulated1-(2-#18 AWG)uninsulated
� 504-22-3165504-22-3164504-22-3836
808095
yesnoyes
Gray 0.510 12.95 0.650 16.50236236248
353537
273273278
414142
4 Conductors2-#15 AWG insulated1-#20 AWGCopperweld, insulated1-(3-#18 AWG)uninsulated
504-22-2164 80 no Gray 0.570 14.48 0.715 18.20 289 43 333 50
75kVExtraSmall
Diameter
3 Conductors2-#15 AWG insulated1-(2-#18 AWG)uninsulated
� 504-22-3015 80 no Gray 0.490 12.45 0.600 15.25 224 34 248 37
100kV
3 Conductors2-#15 AWG insulated1-(2-#18 AWG) uninsu-lated
504-22-1033504-22-1035
80noyes
Gray 0.620 15.75 0.785 19.90 332 49 371 55
4 Conductors2-#15 AWG insulated1-(#20 AWG) Copper-weld, insulated1-(3#18 AWG)uninsulated
504-22-2041 80 no Gray 0.660 16.75 0.845 21.50 380 57 441 66
Electrical Characteristics
Rated VoltageRectified dc kV (2)
Number ofConductors
Core to ShieldCapacitance ± 10%
4/C only: Copperweld grid lead capacitance = 70 pF/ft. (230 pF/m).
pF/ft. pF/m Conductor resistance @ 25°C:
6575 (ESD)7575
100100160250
33343433
5249.5475740493531
170162154187131159115101
#16 AWG (1.31 mm2) tinned copper = 4.18 ohms/1000 ft (1.37 ohms/100 m)#15 AWG (1.65 mm2) tinned copper = 3.51 ohms/1000 ft (1.15 ohms/100 m)#18 AWG (0.83 mm2) tinned copper = 7.16 ohms/1000 ft (2.34 ohms/100 m)
2 X #18 AWG (0.83 mm2) tinned copper = 3.58 ohms/1000 ft (1.17 ohms/100 m)3 X #18 AWG (0.83 mm2) tinned copper = 2.39 ohms/1000 ft (0.78 ohms/100 m)
#20 AWG (0.52 mm2) copperweld = 24.12 ohms/1000 ft (7.91 ohms/100 m)
(2) Voltage rating is between the conductor and the shielding braid.
B/03040602
Product DataSection 6: Sheet 2
� Authorized stock Item. Available from our Customer Service Centers.
(1) Cable is helically wrapped with a cellophane tape to maintain cleanliness during installation and includes a pull cord for ease of removal.
- Designs for special applications upon request.- Refer to Product Data Section 6 Sheet 1 for X-Ray Cable - Low Noise constructions.
Catalo
gNum
ber
Net. W
t.(k
g/100m
)
Jack
etColo
r
Insu
latio
nO.D
.
mm
±0.2
5
Insu
latio
nO.D
.
Inch
es±
0.010
Jack
etO.D
.
Inch
es±
0.015
Jack
etO.D
.
mm
±0.3
8
#34 AW
GT.C
. Bra
id
Covera
ge (%)
Descr
iptio
n
Net. W
t.(lb
s/100
0 ft.)
Approx.
ShipW
eight
(kg./1
00m
)
Approx.
ShipW
eight
(lbs./
1000
’)
Okonite X-Ray/Hi-Voltage Cable65kV, 75kV, 100kV dc RatingThree Conductor or Four Conductor
Cellophan
e Wra
p(1
)
THE OKONITE COMPANYRamsey, New Jersey 07446
Insulation/JacketOkoguard is Okonite’s registered tradename for its exclusive ethylene-propyl-ene base, thermosetting compound,whose optimum balance of electricaland physical properties is unequaled inother solid dielectrics.
This durable Okoguard insulation servesas a jacket as well. It is permanentlyembossed with a legend and has anatural, highly visible, red color.
ApplicationsOkoguard Portable Jumper cables aredesigned as flexible power leads for usewith tap-off or jumper clamps which per-mit temporary connections or “by-pass”of energized aerial lines operating atvoltages up to and including 15000V(phase to phase).
SpecificationsExtra-flexible rope
tin coated copper per ASTM B-33, flexi-ble rope stranded.
: A taped conductivescreen, whose purpose is to improveservice life, dielectric strength and elimi-nate internal corona, meets andexceeds ICEA Standard S-96-639.
Okoguard meets and ex-ceeds ICEA Standard S-93-639.
Product FeaturesExtra-flexible conductors for ease
of handling under adverse condi-tions.
Conductor screen for improvedvoltage stress control.
• Heat, moisture and ozone resistant90°C Okoguard Insulation/Jacket.
• Okoguard is red for visual attentionand it has good color stability evenwhen exposed to strong sunlight.
• Excellent low temperatureproperties.
Okoguard® Aerial Jumper Cable
Coated, Stranded CopperConductorStrand ScreenInsulation/Jacket-Okoguard
Okoguard Aerial Jumper Cable
� 303-21-1934� 303-21-1938� 303-21-1940� 303-21-1944
21/02/04/0
259259259437
0.3190.4080.4500.592
0.7800.8630.9101.052
19.822.023.327.2
425583687997
480638752
1092
192258298400
� Available from our Customer Service Centers
is 150 ft.—1000' N.R. Reel. Standard package will be
furnished where orders do not specify otherwise.
C/12040604THE OKONITE COMPANY
Ramsey, New Jersey 07446
Ampacity based on 90°C conductor temperature, 40°C ambient temperature.For ampacity correction factors covering various ambient temperatures:
AmbientTemperature
DegreesCorrection
Factor
C F
1020304050
506886
104122
1.261.181.101.000.90
Okoguard is Okonite’s registered trade namefor its exclusive medium voltage grade ethyl-ene-propylene rubber (EPR) based,thermosetting compound, whose optimumbalance of electrical and physical propertiesis unequaled in other solid dielectrics.Okoguard insulation, with the distinctive redcolor and a totally integrated EPR system,provides the optimum balance for long, prob-lem free service.
The Okolon TS-CPE jacket on this cable is avulcanized chlorinated polyethylene basedcompound which is mechanically rugged,flame, and oil resistant.
Okoguard-Okolon TS-CPE cables are heavyduty nonshielded cables designed for use atup to 5kV in wet or dry airport lighting appli-cations.Okoguard-Okolon TS-CPE nonshielded air-port lighting cables are recommended foruse in series lighting circuits for runways andcontrol systems. Cables can be installed inmetallic or non-metallic conduit, directly bur-ied or aerial application.
Meets or exceeds the requirements of FAAAdvisory Circular AC 150/5345-7F.
Annealed uncoated coppercompact Class B stranded per ASTM B-496.
Extruded semiconduct-ing EPR strand screen. Meets or exceedselectrical and physical requirements ofICEA S-96-659/NEMA WC71.
Meets or exceeds electricaland physical requirements of ICEAS-96-659/NEMA WC71. Insulation thick-ness per Table 4-3 for wet or dryapplications.
Meets or exceeds electrical andphysical requirements of ICEAS-96-659/NEMA WC71 for chlorinatedpolyethylene jackets.
• Resistant to runway and wing de-icers• 90°C Continuous Rating,130°C Emergency Overload Rating,250°C Short Circuit Rating• Exceptional resistance to surfacetracking• Superior Flexibility• Constructed for “wet” locationapplications• Excellent corona resistance• Stress cones not required• Resistant to most oils, acids, andalkalies
*Applications governed by the NationalElectrical Code limit non-shielded cableto 2.4kV
Okoguard®-Okolon® TS-CPE5kV Airport Lighting Cable*
One Okopact (Compact Stranded) Copper Conductor/90°C Rating Wet or Dry
Uncoated, Okopact (CompactStranded) Copper ConductorStrand Screen-ExtrudedSemiconducting EPRInsulation-Okoguard EPRJacket-Okolon TS-CPE
� 114-24-2213� 114-24-2217
8 8.46 13.3
125 3.18125 3.18
80 2.0380 2.03
0.60 15.10.63 16.0
215260
250295
� Available from our Customer Service Centers.
are available.
E/14080606 THE OKONITE COMPANYRamsey, New Jersey 07446
A
B
C
D
InsulationOkonite EPR insulation is a heat, mois-ture and chemical resistant,mechanically rugged compound. The in-sulation thickness for size #14 AWGthrough #9 AWG is 5/64" and for #6AWG through #2 AWG is 6/64". Oneconductor in each layer is identified as"Tracer". In addition, each conductor isnumber coded for ease of identification.
Assembly and FinishIndividual conductors are assembledwith suitable fillers, where necessary,and a cable cushioning tape. A 7 mil flatcopper alloy tape is then helically ap-plied, giving outstanding mechanicalprotection. The black Okolene® (poly-ethylene) jacket is then applied overall.
ApplicationsOkonite Armored Underground SignalCables are designed for use in all vitalrailroad signal circuits where security ofservice and long life are required in allvital circuit and safety related applica-tions. These cables are recommendedfor use where crush resistance, termiteand rodent protection are considera-tions and in all wet and dry locations.
SpecificationsAREMA Signal Manual Part 10.3.17Conductors: Solid uncoated copperper ASTM B-3, stranded uncoated com-pact round copper per ASTM B-496.
Insulation: Meets or exceeds electri-cal and physical requirements ofICEA S-95-658 (NEMA WC70) andAREMA Manual Part 10.3.19, thick-ness per table 10317-4.Armor Tape: Copper alloy C19400per ASTM B-465.Jacket: Meets or exceeds electricaland physical requirements of ICEAS-95-658, Part 4.1.5.
Product Features• Mechanically rugged.• Resistant to aging.• Easy to install and splice.• Resistant to environmental haz-ards.• Superior moisture resistance.• Outstanding termite and rodent pro-tection.• Excellent electrical properties...high dielectric strength, low SIC andpower factor and high insulation re-sistance.• The Pull Cord feature affords easyand quick accessibility to conductorsfor splicing and terminating.• Sequential footage markings onsurface of outer jacket.
Okonite® ArmoredUnderground Signal CablesWith P.C.F. (Pull Cord Feature)Heavy Duty Direct Burial Railroad Signal Cable— AREMA Type 1 EPR Insulation — 600VMultiple Copper Conductors/90°C Rating
Product DataSection 7: Sheet 1
COMPOSITE CONSTRUCTIONS
Okonite Insulation: #14 AWG through #9 AWG 5/64”, #6 AWG 6/64”
CatalogNumber
CompositeMake-Up
ConductorsNo. x Size No. x Size(# Strands) (# Strands)
OuterJacket
Thickness64th
ApproxCable
O.D. (In.)
ApproxNet Wt.Lbs./M’
ApproxShipWt.
Lbs./M
206-11-8974� 206-11-8255� 206-11-6283
7/C15/C19/C
2 x 9 (1X)3 x 6 (1X)6 x 6 (1X)
5 x 14 (1X)12 x 14 (1X)13 x 14 (1X)
566
0.991.481.69
52311451674
57412731877
� Authorized Stock Item - Available from Customer Service Centers.
Composite Cable Constructions are also available with stranded conductors.Consult your Okonite Representative.
B
A
C
E
D
F
TH
EO
KO
NIT
EC
O.5
/C14
AW
GC
U
A Solid or Stranded Uncoated CopperConductors
B Insulation—Okonite #14 AWG-#9AWG 5/64", #6 - #2 AWG 6/64" withprinted number code and tracer
C Cushion Tape LayerD Flat Copper Alloy Armor TapeE Pull CordF Jacket—Okolene with sequential
footage marking
Okonite ArmoredUnderground Signal CablesOkonite Insulation: #14 AWG Through #9 AWG, 5/64", #6 through #2 AWG, 6/64"
CatalogNumber
Size AWGNo. of
Strands (1)No.
Condrs.Outer Jacket
Thickness-64thApprox. Cable
O.D. InchesNet Wt.Lbs./M'
Approx. ShipWt. Lbs./M'
� 206-11-6882206-11-6883206-11-6884
141414
Sol.Sol.Sol.
234
444
.63
.67
.73
184220267
241286338
� 206-11-6885� 206-11-6887
206-11-6889
141414
Sol.Sol.Sol.
579
455
.79
.891.03
314409526
408510671
206-11-6890� 206-11-6892
206-11-6895
141414
Sol.Sol.Sol.
101215
556
1.101.161.31
583649804
790792994
206-11-6896� 206-11-6899
206-11-6901
141414
Sol.Sol.Sol.
161921
666
1.311.381.45
928959
1050
102911511250
� 206-11-6907� 206-11-6910
206-11-6692
141412
Sol.Sol.Sol.
2737
2
674
1.651.87
.66
13081735
206
16382076
273
206-11-6693206-11-6694206-11-6695
121212
Sol.Sol.Sol.
345
444
.70
.76
.83
256313368
330392471
206-11-6697206-11-6699206-11-6700
121212
Sol.Sol.Sol.
79
10
555
.941.091.16
487625699
594781866
206-11-6702206-11-6812206-11-6813
121010
Sol.Sol.Sol.
1223
544
1.26.70.75
804244311
952317384
206-11-6814206-11-6815206-11-6817
101010
Sol.Sol.Sol.
457
455
.82
.921.00
383479611
483577746
206-11-6819206-11-6820206-11-6822
101010
Sol.Sol.Sol.
91012
566
1.171.251.35
772872
1007
93410781199
206-11-6922� 206-11-6923
206-11-6924
999
Sol.Sol.Sol.
234
445
.73
.77
.88
283351452
350443554
� 206-11-6925� 206-11-6927
206-11-6928206-11-6929
9999
Sol.Sol.Sol.Sol.
5789
5555
.961.041.131.23
549686775901
640829935
1057
� 206-11-6930206-11-6931
� 206-11-6242
996
Sol.Sol.Sol.
1012
2
665
1.331.400.93
10521161
457
12211338
564
� 206-11-6243206-11-6244
� 206-11-6245
666
Sol.Sol.Sol.
345
555
0.971.081.18
591730913
724881
1044
� 206-11-6247206-11-6248
� 206-11-6249
666
Sol.Sol.Sol.
789
666
1.321.431.54
119313511532
136815521820
� 206-11-6070*� 206-11-6374� 206-11-6042� 206-11-6373� 206-11-6045� 206-11-6130**
664442
777777
3*4*2353**
565566
1.041.131.031.101.181.25
671829606801911
1191
753896674894
13561346
Minimum Manufacturing Quantity is 1000 ft. Standard Package—1000' N.R. Reel.
� Authorized Stock Item - Available from Customer Service Centers.
(1) This construction is also available with stranded conductors. Consult yourOkonite Representative.* Includes 1 #8 AWG Class B Ground** Includes 1 #6 AWG Class B Ground
J/20020701
THE OKONITE COMPANYRamsey, New Jersey 07446
Product DataSection 7: Sheet 1
Okonite EPR is Okonite's tradename for its heat resistant, mechani-cally rugged ethylene-propylenebased insulating compound. The in-sulation thickness for wire sizes #9AWG is 5/64" and for #6 AWG is6/64".
The Okolene (PE) jacket suppliedwith this cable provides excellent re-sistance to mechanical abuse,weathering and most acids, oils andalkalies. Color Coded; 1-Black,1-Red.
Okonite-Okolene 600V Duplex TrackWire is recommended for use intrack circuits, signal operations, carretarder and switch machine appli-cations. Can be installed in eitherwet or dry locations, in conduit traysor trough or buried direct.
Solid uncoated cop-per per ASTM B-3.
Per ICEA S-95-658,and AREMA Signal Manual Part10.3.19.
Meets or exceeds thephysical and electrical require-ments of ICEA S-95-658, andAREMA Signal Manual Part10.3.21
• Exceptional heat resistance.• 90°C Continuous Rating130°C Emergency Overload Rat-ing.250°C Short Circuit Rating.• Mechanically rugged.• Flexible, easy to handle andsplice.• Resistant to most oils, acids, al-kalies and effects of weather.• Stable electrical and physicalproperties.• Excellent moisture resistance.
Okonite®-Okolene® Duplex Track Wire
One Copper Conductor/90°C Rating
Solid Uncoated Copper ConductorsInsulation - Okonite-Sizes #9 AWGand #8 AWG-5/64", #6 AWG-6/64"Jacket-Okolene, Color Coded;1-Black, 1-Red
150-12-3931� 150-12-3933
96
SolidSolid
44
0.83"1.00"
199329
243404
� Authorized Stock Item: Available from our Customer Service Center-1000' Non-Returnable Reel
THE OKONITE COMPANYRamsey, New Jersey 07446E/11100706
B
A
InsulationOkonite EPR is Okonite's trade name for itsheat resistant, mechanically ruggedethylene-propylene based insulating com-pound. The insulation thickness for wiresizes are listed below.
Jackets and FinishesThe Blue Okoseal® (PVC) jacket suppliedwith this cable provides excellent resistanceto mechanical abuse, flame, weathering, andmost acids, oils, and alkalies.
ApplicationsOkonite Tower and Case Wire is recom-mended for use as relay and associatedsignal apparatus wiring and for connectorwire use where a flexible, small diameterwire is required.
SpecificationsConductor: Uncoated stranded copperstranded per ASTM B-8.Insulation: Per ICEA S-95-658. Meets orexceeds all requirements for EPR insulation.Jacket: Per ICEA S-95-658. Meets or ex-ceeds all requirements.Okonite Tower and Case Wire meets or ex-ceeds the requirements of AREMA ManualPart 10.3.15.
Product Features• Exceptional heat resistance.• 90°C Continuous Rating130°C Emergency Overload Rating.250°C Short Circuit Rating.• Mechanically rugged.• Flexible, easy to handle and splice.• Flame resistant—meets U.L. horizontalflame test.• Resistant to most oils acids, alkaliesand effects of weather.• Stable electrical and physical proper-ties.
Okonite® TC BlueTower and Case Wire600 VoltOne Copper Conductor/90°C Rating
Product DataSection 7: Sheet 10
A Uncoated, Stranded CopperConductor
B Insulation—OkoniteC Jacket—Blue Okoseal
CatalogNumber
SizeAWG
No. ofStrands
InsulationThickness
Mils
JacketThickness
Mils
Approx.O.D.(In.)
Approx.Net Wt.Lbs./m'
Approx.Ship Wt.Lbs./m'
� 152-11-3002� 152-11-3024
152-11-3026
161412
191919
303045
202020
.17
.20
.23
202642
242846
� 152-11-3038152-11-3108152-11-3010
� 152-11-3015
1010
96
19371919
30454560
20202530
.23
.26
.29
.37
565871130
606275143
� Authorized Stock Item - Available from our Customer Service Centers.Note: The construction described has a Blue Jacket. Consult your local Okonite Representa-tive for details about alternate colors.Standard Package - #16 AWG and #14 AWG, 1,000 spool; #12 AWG, #10 AWG,and #9 AWG, 500' spool.
F/21010710
TH
EO
KO
NIT
EC
O.1
/C9
AW
GC
UT
OW
ER
AN
DC
AS
EW
IRE
B
A
C
THE OKONITE COMPANYRamsey, New Jersey 07446
Okonite EPR is Okonite’s trade namefor its heat resistant, mechanically rug-ged ethylene-propylene based insulatingcompound. The insulation thickness forwire size #16 AWG and #14 AWG is2/64" and for #12 AWG and #10 AWG itis 3/64".
The Okolon (TS-CP) jacket suppliedwith this cable provides excellent resis-tance to mechanical abuse, flame,weathering and most acids, oils and al-kalies.
Okonite Okolon (TS-CP) 600V CaseWire is recommended for use as relayand associated signal apparatus wiringand for connector wire use where a flex-ible, small diameter wire is required.
Uncoated stranded copperper ASTM B-8.
Per ICEA S-95-658.Per ICEA S-95-658, Part 4.1.13
and 4.1.3.
• Exceptional heat resistance.• 90°C Continuous Rating130°C Emergency Overload Rating.250°C Short Circuit Rating.• Mechanically rugged.• Flexible, easy to handle and splice.• Flame resistant — meets U.L. hori-zontal flame test.• Resistant to most oils, acids, al-kalies and effects of weather.• Stable electrical and physical prop-erties.
Okonite® Okolon® - (TS-CPE) Case Wire
One Copper Conductor/90°C Rating
Uncoated, Stranded CopperConductorInsulation—Okonite—#16 AWG and#14 AWG - 2/64"; #12 AWG thru #6AWG - 3/64"Jacket - Okolon TS-CPE
151-12-1051�151-12-1081
151-12-1101
161412
191919
111
.16
.18
.23
202642
243046
151-12-1140151-12-1171
�151-12-1201
1096
191919
111
.25
.26
.31
5867
112
6275
122� Authorized Stock Item - Available from Customer Service Centers.
— #16 AWG and #14 AWG, 1000’ spool; #12 AWG thru #6 AWG, 500’ spool.
THE OKONITE COMPANYRamsey, New Jersey 07446
G/11100711
B
A
TH
EO
KO
NIT
EC
O.O
KO
LON
TS
-CP
EC
AS
EW
IRE
InsulationOkonite EPR is Okonite's tradename for its heat resistant, mechani-cally rugged ethylene-propylenebased insulating compound. The in-sulation thickness for wire sizes #16AWG and #14 AWG is 2/64" and for#12 AWG through #9 AWG it is3/64".
FinishThe nylon braid and lacquer finishsupplied with this cable provides ex-cellent resistance to mechanicalabuse, weathering and most oils, ac-ids and alkalies.
ApplicationsOkonite-Nylon Braid 600V CaseWire is recommended for use as re-lay and associated signal apparatuswiring, and for connector wire usewhere a flexible, small diameter wireis required.
SpecificationsConductor: Uncoated, strandedcopper conductor per ASTM B-8.Insulation: Per ICEA S-95-658.Finish: Black nylon braid (100%coverage) with clean lacquer fin-ish.
Product Features• Mechanically rugged.• 90°C Continuous Rating130°C Emergency Overload Rat-ing.250°C Short Circuit Rating.• Mechanically rugged.• Flexible, easy to handle andsplice.• Resists most oils, acids, alkaliesand effects of weather.• Stable electrical and physicalproperties.
Okonite®-Nylon Braid Case Wire600VOne Copper Conductor/90°C Rating
Product DataSection 7: Sheet 12
A Uncoated, Stranded CopperConductor
B Insulation—Okonite #16 and #14AWG 2/64"; #12 AWG through #9AWG 3/64"
C Finish—Nylon Braid with LacquerOverall
Nominal Finish Thickness: 5 mils
CatalogNumber Size AWG No. of
Strands
InsulationThickness
64 th's
Approx.O.D. (In.)
Approx.Net Wt.Lbs./M'
Approx.Ship Wt.Lbs./M'
�151-12-9051151-12-9081
�151-12-9111
161412
191919
223
.14
.15
.20
162238
202642
151-12-9145�151-12-9161
151-12-9181
10109
193719
333
.22
.23
.24
505162
545566
� Authorized Stock Item — Available from our Customer Service CentersStandard Package — #16 AWG and #14 AWG, 1000' spool;#12 AWG, #10 AWG, and #9 AWG, 500' spool.
F/20020712
B
A
C
THE OKONITE COMPANYRamsey, New Jersey 07446
InsulationOkonite EPR® is Okonite’s trade namefor its heat resistant, mechanically rug-ged ethylene-propylene based insulatingcompound. The insulation thickness forDEL numbers 002 and 004 is 2/64”, for008 through 016 is 3/64”, 018 through026 is 4/64”, 030 through 040 is 5/64”,044 and 048 is 6/64”, 050 through 056 is7/64” and for 058 it is 8/64”.
Jackets and FinishesThe Okolon® TS-CPE jacket suppliedwith this cable provides excellent resis-tance to mechanical abuse, flame,weathering, most oils, acids and alka-lies.
ApplicationsOkonite Type DEL, Diesel-Electric Loco-motive Traction and Car Wires isdesigned for use in locomotives and carequipment circuits where reliability is forprime consideration. DEL can also beused in other low voltage applicationswhere flexibility is important. It is suit-able for use in wet or dry locations, inconduits, ducts, cable troughs or trays.
SpecificationsConductor: Coated copper strandedper AREMA Recommended Practice,Section M, RP-588, as applicable andICEA S-95-658.Insulation: Per AREMA RecommendedPractice, Section M, RP-588, as applica-ble and ICEA S-95-658.Jacket: Per AREMA Recommended Prac-tice, Section M, RP-588, as applicable andICEA S-95-658.
Product Features• Extreme heat resistance.• Extra flexible conductor.• 90°C Continuous Rating,110°C Hot Spot Rating,130°C emergency Overload Rating,300°C Short Circuit Rating.• Mechanically rugged.• Exceptional resistance to deforma-tion and cut through at hightemperature.• Excellent flame resistance. Meetsboth UL vertical and horizontal flametest requirements.• Resistant to oils, weather and mostchemicals and alkalies.• Stable electrical properties at hightemperatures.• Meets the RHH/RHW requirementsof NEC/UL and can be labeled assuch on special orders.
Type DEL600-2000V Diesel-Electric Locomotive,Motor Traction and Car WireOne Copper Conductor/90°C — 110°C Hot Spot Rating
Product DataSection 7: Sheet 17
A Coated Stranded Copper ConductorB Separator (sizes 36,700 CM and
larger)C Insulation - OkoniteD Jacket - Okolon TS-CPE
B
A
C
D
TH
EO
KO
NIT
EC
O.D
EL
016
8A
WG
Type DEL600-2000V Diesel - Electric Locomotive,Motor Traction and Car WireOne Copper Conductor/90°C - 110°C Hot Spot Rating
CatalogNumber
DELNumber
SizeAWG
or MCM
No. ofStrands
Thickness64ths
Ins. Jkt.
VoltageRating
Approx.O.D. In.
Approx.Wt. Lbs./M’Net Ship
Ampacity AC or DC1/C 3-1/C
in Air1 in Duct²
ConduitSize
Inches3
DC Resis@ 25°C
ohms/1000’
� 112-11-1702112-11-1704112-11-1708
002004008
161414
19 X .011719 X .014219 X .0147
223
111
600600
2000
.16
.17
.21
192531
232835
243333
182424
1/2”1/2”1/2”
4.4902.7902.790
112-11-1710� 112-11-1714
112-11-1716
010014016
1210
8
19 X .017927 X .020137 X .0201
333
111
200020002000
.23
.26
.28
436179
446078
395774
294151
1/2”3/4”3/4”
1.7201.1000.690
112-11-1718112-11-1720112-11-1722
018020022
654
61 X .020191 X .0201
105 X .0201
444
222
200020002000
.41
.44
.46
144182204
141200222
101129142
728995
1”1 1/4”1 1/4”
0.4400.3500.280
112-11-1724112-11-1726112-11-1730
024026030
321
125 X .0201150 X .0201225 X .0201
445
223
200020002000
.49
.55
.69
242285445
241298497
160180233
111124153
1 1/4”1 1/2”2”
0.2200.1800.140
112-11-1732112-11-1734112-11-1738
032034038
1/02/03/0
275 X .0201325 X .0201450 X .0201
555
333
200020002000
.72
.76
.86
492594786
550633842
268297367
175193236
2”2”2 1/2”
0.1100.0900.070
112-11-1740112-11-1744112-11-1748
040044048
4/0313.1444.4
550 X .0201775 X .0201
1100 X .0201
566
333
200020002000
.891.061.20
92612891707
98513711830
419518653
268328402
2 1/2”3”3 1/2”
0.0600.0400.030
112-11-1750112-11-1752112-11-1754
050052054
535.3646.4777.7
1325 X .02011600 X .02011925 X .0201
777
444
200020002000
1.351.441.53
214125452842
226327003148
728813904
446496546
4”4”5”
0.0200.0180.016
112-11-1756112-11-1758
056058
929.21111.1
2300 X .02012750 X .0201
78
44
20002000
1.621.79
35164208
35604072
10021119
594637
5”5”
0.0130.011
� Authorized Stock Item - Available from CustomerService Centers.
Standard Package - 1000’ Non-Returnable Reel; #16 #8- 1000’ coil in carton; # 6 - 500’ coil in carton; #5 - #4/0 -2000’ N.R. Reel; #313.1 MCM and Larger - 1000’ N.R.Reel1 Ampacities based on single insulated conductor in freeair, 90°C conductor temperature, 30°C ambient air tem-perature per NEC Table 310.17.
2 Ampacities based on three (3) insulated conductors in asingle enclosed or exposed conduit with 90°C conductortemperature and 30°C ambient air temperature per NECTable 310.16. For other ambient temperatures refer toNEC Table 310.15(B)(1).3 Based on three (3) conductors in conduit with a fill of40% or less.
G/21080717
Product DataSection 7: Sheet 17
THE OKONITE COMPANYRamsey, New Jersey 07446
Applications
The C-L-X Terminating Tool Kit contains allthe tools required to remove the overalljacket and aluminum sheath from C-L-Xpower, control, and instrumentation ca-bles. The Cable Slitting Saw may also beused on interlocked armor and leadsheathed cables. The Cable Slitting Sawprovides a simple and efficient means ofremoving the aluminum C-L-X sheath. It isavailable in either an electric or a pneu-matic model. Both models have aretractable blade guard to protect the user.The electric model is powered by a 2500rpm, 120 Volt ac double insulated motor.The lightweight pneumatic model is pow-ered by a 2200 rpm motor which requires90 psi of air pressure for maximum effi-ciency. The Small Cable Guide keeps thesaw centered on the cable when slitting ca-bles of 1” diameter or less.The High Speed Steel Saw Blades providea smooth cut in the aluminum sheath andhave a cutting depth of 3/8” without the ca-ble guide.
Removing the C-L-X Armor
This procedure applies to all types of C-L-Xarmor - aluminum, copper, bronze andstainless steel. Safe working practices areto be observed, e.g., safety glasses andwork gloves. Practice sessions are recom-mended to familiarize all concerned withthe procedures and equipment.
1. Remove the jacket to expose the desiredlength of un-armored cable within the en-closure.
2. Refer to the C-L-X fitting instructions forthe length of C-L-X armor to be exposedbeyond the end of the jacket and markthe C-L-X armor at the top of the crownnearest to that point.
• For C-L-X Diameters 1 5/8” andSmaller, Go To Steps 10 through 12.
• For C-L-X Diameters greater than 15/8” Follow Steps 3. Through 9.
C-L-X Terminating Tool Kit
Product DataSection 6: Sheet 5
C-L-X TERMINATING TOOL KIT CONTENTS1 Cable Slitting Saw1 Small Cable Guide
12 2” dia. High Speed Steel Saw Blades1 Tubing Cutter1 Channel Lock Pliers1 10' Retractable Tape
1 5/16” x 11” Screwdriver1 Cable Knife, 4” blade1 Hacksaw Blade Holder3 10” Hacksaw Blades1 Tool Case1 Padlock with 2 keys
PACKAGING
Catalog Number Description Net Weight(lbs.)
Shipping Weight(lbs.)
C-L-X Terminating Tool Kit
� 606-01-1026� 606-01-1526
Electric - 120 Volt acPneumatic - 90psi
2020
2121
Cable Slitting Saw, Small Cable Guideand 12 High Speed steel saw Blades
� 606-01-0026� 606-01-0526
Electric - 120 Volt acPneumatic - 90psi
1919
2020
12 High Speed Steel Saw Blades
� 606-01-5754 2” diameter, 7 teethper inch, packaged ina round tin container
1 1
� Authorized Stock Item
C-L-X Terminating Tool Kit
3. First the C-L-X armor will be circumferentially cut using a hack-saw blade, (note the C-L-X saw tool kit is supplied with ahacksaw blade and blade holder) cut through the crown (highpoint) of the C-L-X at an angle so as to connect (or bridge) thevalleys (low points) on both sides of the crown.
4. Again using a hacksaw blade, make a circumferential score inthe valleys adjacent to the cut crown connecting both sides ofthe crown cut to the valleys. Do not cut through armor in valleys.
5. Holding the score area rigid, flex the cable by moving the freeend so as to break the score around the circumference of thecable.
6. Next the C-L-X will be longitudinally cut by performing thefollowing:Note on the C-L-X Saw - The longitudinal cut is made with theC-L-X saw, which has an adjustable positive depth stop that canbe set so the saw blade cuts through the crowns and partiallycuts through the valleys. A proper saw depth is achieved when80 to 95 % of the metal in the valley is removed. Use an extrapiece of the cable being terminated to adjust the blade depth and
practice.
Set blade to remove 80 to 95% of the metal thick-ness in the valley.
7. With cable secured, start at the free end of the cable andadvance the Kett saw, making sure to use slight downwardpressure to maintain the depth of cut along the cable, to the ringcut. When advancing the saw, be sure maintain a straight line bycutting along the high point of the cable; this affects the cut depthalso. See following:
Proper Saw Position
If it is necessary to stop cutting or if a portion of the cut is to be re-peated, use caution when reinserting the blade as kickback mayoccur.
8. At the completion of the longitudinal cut, starting at the free end,insert a wide blade screwdriver into the cut and twist. Repeat un-til the ring cut is reached. This will cause the remaining metal inthe valleys to break open and the armor to loosen on the cable.Do not drive the screwdriver into the cut with excessive force asthis may damage the underlying conductors.
9. Slide the armor off the cable. In the event that the armor is tightaround the cable, pliers may be used to grab the armor at thesplit and pull it away from the cable. For large diameter cables,where long lengths of armor are to be removed, two cuts spaced180° apart are recommended so that the armor may be removedin two pieces.
• For C-L-X Diameters 1 5/8” and Smaller Follow Steps 10.
Through 13.
10. Using a hacksaw blade or tubing cutter, circumferentially scorethe C-L-X armor. Grip the cable in both hands with the scorecentered between hands, and flex the cable at the score line untilit opens. Slide the sheath off the cable.
11. For C-L-X cables with an inner jacket or cable constructionswhere the C-L-X armor is tight fitting around the insulatedconductors, the C-L-X saw should be used with the optional redcolored cable guide. This guide assists in centering the saw onsmall diameter cable. The procedures and precautions of steps3 to 9 apply here also.
12. Remove the cable fillers and marker tape and install the C-L-Xfitting as per the manufacturer’s instructions. The cable is nowready to be terminated into the enclosure.
Product DataSection 6: Sheet 5
THE OKONITE COMPANYRamsey, New Jersey 07446G/17040605
Correct Incorrect
CONDUCTOR
COLOR CODING SEQUENCE
ICEA S-73-532 TABLE E-2
Color Sequence (No Green or White Conductors)
Conductor
Number
Base
Color
Tracer
Color
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Black
Red
Blue
Orange
Yellow
Brown
Red
Blue
Orange
Yellow
Brown
Black
Blue
Orange
Yellow
Brown
Black
Red
Orange
Yellow
Brown
Black
Red
Blue
Yellow
Brown
Black
Red
Blue
Orange
Brown
Black
Red
Blue
Orange
Yellow
Black
—
—
—
—
—
—
Black
Black
Black
Black
Black
Red
Red
Red
Red
Red
Blue
Blue
Blue
Blue
Blue
Orange
Orange
Orange
Orange
Orange
Yellow
Yellow
Yellow
Yellow
Yellow
Brown
Brown
Brown
Brown
Brown
Special Order: Any or all of the following conductors may be added whenspecifically requested by the customer to meet his specific applicationrequirements. These conductor codings comply with UL and NEC requirements
Purpose Base Color Tracer Color
Equipment Grounding UninsulatedGreenGreen 1 or more continuous yellow stripes
Grounded WhiteWhiteWhiteWhiteWhiteWhiteWhite
Black continuous stripeRed continuous stripeBlue continuous stripeOrange continuous stripeBrown continuous stripeNumeric Printing
Oko
nite
3/2
021
Houston, TX
Servic
e C
enters
Ramsey, NJ
Kansas City, KS
Pittsburgh, PAPortland, ORNew Orleans, LA
Corporate H
DQ
Cumberland, RI - Manufacturing Plant
Orangeburg, SC - Compound Facility Orangeburg, SC - Manufacturing Plant
Richmond, KY - Manufacturing Plant Santa Maria, CA - Manufacturing Plant
Facilities OverviewM
anufa
cturin
g P
lants
Okonite CablesDistrict Offices, Manufacturing Plants & Service Centers
Paterson, NJ - Manufacturing Plant
New Orleans District Officeand Service Center(504) 467-1920
FAX: (504) 467-1926
E-Mail: [email protected]
New York District Office
NJ (973) 742-8040
NY (212) 239-0660
FAX: (973) 742-2156
E-Mail: [email protected]
Philadelphia District Office
(302) 318-2054
FAX: (302) 368-4163
E-Mail: [email protected]
Phoenix District Office
(480) 838-8596
FAX: (480) 897-8924
E-Mail: [email protected]
Pittsburgh Service Center
(724) 899-4300
FAX: (724) 899-4320
E-Mail: [email protected]
Portland District Office
& Service Center
(503) 598-0598
FAX: (503) 620-7447
E-Mail: [email protected]
Salt Lake District Office(801) 262-1993
FAX: (801) 262-3167
E-Mail: [email protected]
San Francisco District Office(925) 830-0801
FAX: (925) 830-0954
E-Mail: [email protected]
St Louis District Office(314) 770-9070
FAX: (314) 770-9140
E-Mail: [email protected]
Tampa District Office(813) 627-9400
FAX: (813) 246-4705
E-Mail: [email protected]
Washington District Office(302) 318-2054
FAX: (302) 368-4163
E-Mail: [email protected]
International Sales(281) 821-5500
FAX: (281) 821-7855
E-Mail: [email protected]
Atlanta District Office(770) 928-9778
FAX: (770) 928-0913
E-Mail: [email protected]
Birmingham District Office(205) 655-0390
FAX: (205) 655-0393
E-Mail: [email protected]
Boston District Office(603) 625-1900
(781) 749-3374
FAX: (603) 624-2252
E-Mail: [email protected]
Charlotte District Office(704) 542-1572
FAX: (704) 541-6183
E-Mail: [email protected]
Chicago District Office(630) 961-3100
FAX: (630) 961-3273
E-Mail: [email protected]
Houston District Office& Service Center(281) 821-5500
FAX: (281) 821-7855
E-Mail: [email protected]
Kansas City District Office& Service Center(913) 422-6958
FAX: (913) 422-1647
E-Mail: [email protected]
Los Angeles District Office(562) 590-3070
Fax: (562) 590-3139
E-Mail: [email protected]
Cleveland District Office(330) 926-9181
FAX: (330) 926-9183
E-Mail: [email protected]
Dallas District Office(940) 383-1967
FAX: (469) 630-0048
E-Mail: [email protected]
Denver District Office(303) 772-3517
FAX: (303) 772-3513
E-Mail: [email protected]
Minneapolis District Office(763) 432-3818
FAX: (763) 432-3811
E-Mail: [email protected]
Baton Rouge District Office(504) 467-1920
FAX: (504) 305-4773
E-Mail: [email protected]
05673102 Hilltop Road, Ramsey, NJ 07446 201.825.0300 Fax: 201.825.9026 www.okonite.com• •Printed on post consumer paper
THEOKONITECOMPANY