MEG PLUS STANDALONE MONITOR FOR TOXIC AND COMBUSTIBLE GASES
FEATURES
• SUPPORTS THREE INPUT CHANNELS
• ACCEPTS PRE-CALIBRATED PLUG-IN SENSORS
• INTUITIVE TOUCH SCREEN USER INTERFACE WITH
PASSWORD PROTECTION
• AUTOMATIC FAIL-SAFE
• 3-STAGE 10A SPDT RELAY OUTPUTS WITH FIELD
PROGRAMMABLE SET-POINTS, WARNING, HIGH &
ALARM
• TIME DELAY FOR ALARM
• BUILT-IN VISUAL/AUDIBLE ALARM WITH KILL SWITCH
• 4 ANALOG 4-20MA OUTPUTS
• RS485/MODBUS RTU SERIAL COMMUNICATION
• FAN OVERRIDE TIMER (OPTIONAL)
• DATA LOGGING (OPTIONAL)
APPLICATIONS
• PARKING GARAGES, LOADING DOCKS
• VEHICLE MAINTENANCE FACILITIES
• CAR DEALERSHIPS
• INDOOR SPORTS COMPLEXES/ARENAS
• HOSPITALS, AMBULANCE BAYS
• AIRPORTS, FIRE STATIONS
• WAREHOUSES
• BOILER ROOMS, BATTERY ROOMS
• GREENHOUSES, WINERIES
• LABORATORIES
• COMMERCIAL KITCHENS
1
MissionTo ensure occupant safety in enclosed areas from any sudden release or build-up of hazardous gases.
To maintain indoor air quality at acceptable levels.
To help reduce building energy costs by operating the mechanical ventilation system intermittently based on demand.
DescriptionThe KADA MEG Plus is a compact standalone multi-gas monitor with up to 3 sensors. The MEG Plus will monitor a combination of gases from different sensors, display the acquired readings on a touchscreen LCD and, based on conditions, provide a set of outputs to control the ventilation system of the monitored area and activate alarms.
Standard models of the MEG Plus are offered with 1 integral sensor and 2 remote sensors; alternatively, Meg Plus can be ordered with all its 3 sensors remote.
MEG Plus has a set of 3 SPDT relay outputs reserved for WARNING, HIGH and ALARM levels with separately programmable set points for each sensor. The relay outputs of the MEG Plus are typically used to turn on supply/exhaust fans, open motorized dampers and activate remote strobe/horns.
MEG PLUS FLEXIBLE AND PRACTICAL, EFFICIENT AND COST-EFFECTIVE
MEG Plus also has 4 analog
4-20mA outputs (one for
each sensor and one more
for peak or average reading).
The analog outputs of the
MEG Plus can be used to
control variable frequency
drive (VFD) fans, remote
actuators or simply to feed
data to the BAS (Building
Automation System).
Although shipped as a “Plug
and Play” device, Meg Plus
also allows the user to make
field-modifications easily thanks
to a user-friendly touch screen
interface.
Meg Plus is housed in a robust
NEMA 1 metal enclosure with
a hinged door and tamper
proof screws; optionally
MEG Plus can be ordered
with splash-proof cover or a
protective guard.
2
Variable Frequency Drives (VFD’s),
Air Handling Units (AHU’s),
Building Automation System (BAS)
Network Connectivity,IoT(cloud)
Exhaust/Supply fans,Motorized Dampers,
Strobe/Horn units
Relay Outputs Analog Outputs
RS485/MODBUS
24V/60HZ120V/60HZ
4-20mA 4-20mA
3
MEG PLUS GENERAL SPECIFICATIONSUses Wall-mounted standalone gas monitor for toxic and combustible gases and oxygen
deficiency -single, double and triple-sensor platforms
Aluminum powder-painted finish 203 x 140 x 76 mm (8 ½ x 5½ x 3 in) 2kg (4.4lbs)
Polycarbonate 108 x 83 x 45 mm (4¼ x 3¼ x 1¾ in) less than 0.5kg (1.1lbs)
Power Requirement 120V 50/60HZ 500mA, 12VA also available 24V 50/60Hz 750mA
Input Type (3) 4-20mA, 2- or 3-wire
Relay Outputs (3) SPDT (Form C) 10A @ 250VAC
Analog Outputs (4) 4-20mA into 500 ohms max
Operating Temperature -20 to 50°C (4-122°F)
Humidity 5 to 95% RH non-condensing
Enclosure (monitor)
Sensor enclosure
Sensing Method Diffusion
Gases Detected CO, CO2 ,H2S, NH3 ,NO2 ,O2 ,CH4 ,C3H8 ,C 4 H10 ,H22CLSensor Technology Electrochemical cell (CO,CL2 2S,NH 3 ,NO2 ,O2 ), Catalytic bead(CH4,C3H8 ,C4 H10, H2 ),, H
Response Time T90 < 30 sec
Sensor Accuracy ± 3% Full Scale @ 25°C
Hysteresis 0-20% Full Scale programmable
Display 5” color LCD touchscreen. Graphic user interface
Audible Alarm 85 dBA @ 3 meters (10ft)
OPTIONAL FEATURESBattery Backup 22.2 V lithium ion battery 2600mAh
Onboard Data logging Logged events and sensor readings
Communication RS485/MODBUS RTU serial communication
,
Infrared CO2
MEG PLUS AT KADA, WE VALUE QUALITY ASSURANCE AS OUR TOP PRIORITY
TOXIC GASES
AMMONIA
CARBON DIOXIDE
CARBON MONOXIDE
CHLORINE
HYDROGEN SULFIDE
NITROGEN DIOXIDE
COMBUSTIBLES:
BUTANE
HYDROGEN
METHANE
PROPANE
OXYGEN DEFICIENCY:
OXYGEN
KADA GS SERIES GAS SENSORS 4-20MA OUTPUT
Gas
Model no. Connect
Sensor technology
Range Coverage radius
Mounting height Sensor Life
I: integraltype
R: remote
Ammonia NH3
GS2-NH 3-I2-wire Electrochemical 0-100PPM 6m (20ft)
0.5m (20in) below ceiling >2 years
GS2-NH3-R
Butane C4H10
GS3-C4H10-I3-wire Catalytic bead 100% L.E.L. 6m (20ft) 0.3m (12in) a.f.f.** >3 years
GS3-C4H10-R
Carbon dioxide CO2
GS3-CO2-I3-wire Infrared 0-5000PPM* 15m (50ft)
1.21-1.83m (4-6ft) a.f.f.
>10 yearsGS3-CO2-R
Carbon monoxide COGS2-CO-I
2-wire Electrochemical 0-200PPM 15m (50ft)1.21-1.83m (4-6ft)
a.f.f. 10 yearsGS2-CO-R
Hydrogen H2
GS3-H2-I3-wire Catalytic bead 100% L.E.L 6m (20ft) 0.5m (20in) below
ceiling >3 yearsGS3-H2-R
Hydrogen sulfide H2SGS2-H2S-I
2-wire Electrochemical 0-20PPM 6m (20ft) 0.3m (12in) a.f.f. >3 yearsGS2-H2S-R
Methane CH4
GS3-CH4-I3-wire Catalytic bead 100% L.E.L. 6m (20ft) 0.5m (20in below
ceiling >3 yearsGS3-CH4-R
Nitrogen dioxide NO2
GS2-NO2-I2-wire Electrochemical 0-10PPM 15m (50ft) 0.5m (20in) below
ceiling >2 yearsGS2-NO2-R
Oxygen O2
GS2-O2-I2-wire Electrochemical 0-25% 6m (20ft) 1.21-1.83m (4-6ft)
a.f.f. 5 yearsGS2-O2-R
Propane C3H8
GS3-C3H8-I3-wire 100% L.E.L. 6m (20ft) 0.3m (12in) a.f.f. >3 years
GS3-C3H8-RCatalytic bead
Chlorine CL2GS2-CL2-I GS2-CL2-R 2-wire Electrochemical 0-10PPM 6m (20ft)
1.21-1.83m (4-6ft) a.f.f. >2 years
MEG Plus employs electrochemical, catalytic
bead and infrared sensors to detect various
gases. KADA’s GS-Series 4-20mA sensor modules
are furnished pre-calibrated from the factory and
can either be integral or remote to the MEG Plus.
Remote types are field-connected to the input
channels of the MEG Plus via dedicated 2 or 3
wires. Please refer to the table below for more
information on the KADA GS-series gas sensors.
MEG PLUS KADA GS-SERIES GAS SENSORS ARE RELIABLE AND LONG LASTING WITH A 2 YEAR LIMITED WARRANTY
4
²
A typical application where MEG Plus is monitoring 3 different gases in a parking garage: CO (for gasoline-fuelled engines), NO (for diesel-fuelled engines) and C H (for flammable vapors).
³ 8
MEG Plus combines time proven concepts in gas detection withmodern technology offering sound solutions for personal safety and protection of property
in a building environment.
CONTACT US:Kada Industries50 Steeles Ave E, Unit 10Milton, ON L9T 4W9, CANADA438.883.9693Email: [email protected]: www.kadaindustries.com (under construction)
REPRESENTED BY:
Although we strive to ensure accuracy in this data sheet, we are not responsible for any errors or omissions that may be encountered therein. This data sheet may not be used as a source for regulations, standards or guidelines. The contents of this data sheet are subject to change without notice.
5
MEG Plus makes dual and triple-sensor gas detection possible in any of the following combinations: toxic-toxic, toxic-combustible, combustible-com-bustible, toxic-oxygen, combustible-oxygen or even toxic-combustible-oxygen.
Although designed primarily as a standalone monitor, MEG Plus can also be configured to operate as an addressable device (node) within an integrated network via its RS485/MODBUS communication port.
MEG Plus is a fail-safe device, whereby upon a fault condition, it will force all (or pre-selected) outputs to switch to their HIGH state, thus allowing alarm(s)to be activated and ventilation equipment to run at maximum design rate. The fail-safe mode will last until faults are rectified.
MEG PLUS INTUITIVE, WALK THROUGH MENUS ON A TOUCHSCREEN LCD HELP USERS SET UP THEIR MACHINE IN NO TIME
N0 SENSOR (REMOTE)
CO SENSOR (INTEGRAL)
2
8C H (PROPANE) SENSOR (REMOTE)3