CITY OF LAREDO TEXAS
-
Upload
khangminh22 -
Category
Documents
-
view
0 -
download
0
Transcript of CITY OF LAREDO TEXAS
Revisions:
The record of this drawing is on file at the office of Slay Architecture, 123 Altgelt Avenue, San Antonio, Texas 78201 & 9901 McPherson Avenue, Suite 104, Laredo, Texas 78045. This document is released for the purpose of reference, coordination, and/of facility management under the authority of the named professional, registration number and date on the seal affixed above. COPYRIGHT 2000 - , Slay Architecture. This document was prepared using computer assited design and drafting equipment and saved on magnetic media. Neither the printed document nor the magnetic media may be altered or amended by
any party other than Slay Architecture.
123 Altgelt Avenue
San Antonio, Texas 78201
T: 210.736.3009
9901 McPherson Avenue, #104
Laredo, Texas 78045
T: 956.791.0405
SAN ANTONIO
LAREDO
PROJECT NO.:
CDBG DE LLANO PARK
IMPROVEMENTS PROJECT
19005
09/12/2019
CITY OF LAREDO TEXAS
2019
HMG & ASSOCIATES INCCONTACT: MIKE GARZA, PE
8000 W. INTERSTATE 10, STE 1004
SAN ANTONIO, TEXAS 78230
(210) 349-0800
MEP ENGINEER
IESCONTACT: AGUSTING TELLEZ, JR.
10001 REUNION PLACE, SUITE 200
SAN ANTONIO, TEXAS 78216
(210) 349-0800
STRUCTURAL ENGINEER
SLAY ENGINEERINGCONTACT: RAMIRO IBARRA
9901 MCPHERSON AVENUE, #104
LAREDO, TEXAS 78045
(956) 791-0405
CIVIL ENGINEER
ROSARIO C. CABELLO CO-INTERIM CITY MANAGER
ROBERT A. EADS CO-INTERIM CITY MANAGER
RAMON CHAVEZ, P.E. CITY ENGINEER
DATE
DATE
DATE
APPROVED: CITY OF LAREDO
CITY COUNCIL
HONORABLE PETE SAENZ, MAYOR
ROBERTO BALLI
RUDY GONZALEZ, JR.
VIDAL RODRIGUEZ
MERCURIO MARTINEZ, III
ALBERTO TORRES, JR.
NELLY VIELMA
MARTE A. MARTINEZ
GEORGE J. ALTGELT
MAYOR PRO-TEMPORE
COUNCIL MEMBER
COUNCIL MEMBER
COUNCIL MEMBER
COUNCIL MEMBER
COUNCIL MEMBER
COUNCIL MEMBER
COUNCIL MEMBER
CONSTRUCTION DOCUMENTS
9/12/19
This set of CONSTRUCTION DOCUMENTS is presented in two parts :a set of technical SPECIFICATIONS and a set of DRAWINGS.
CONSTRUCTION DOCUMENT ORGANIZATION
1. SPECIFICATIONS
2. DRAWINGS
DRAWINGS are organized according to disciplines, with each discipline describing a general aspect of the construction. Disciplines are arranged in the order of typical construction sequence as follows:
A-ARCHITECTURAL:Work required to produce the basic building envelope, including: Floor plan(s), roof plan(s), exterior elevations, building sections, wall sections, stair details, exterior enclosure details, interior floor plan(s), enlarged plans, interior elevations, interior partition sections, interior details,cabinets, millwork,equipment details, ceilings and floor finishes.
M-MECHANICAL:Work related to heating, ventilating and cooling systems.
P-PLUMBING:Work related to plumbing systems.
E-ELECTRICAL:Work related to the electrical system.
3. DRAWING NUMBERING
Each drawing is numbered preceding the drawing title. In this example, drawing 16 represents the sixteenth drawing on a sheet of the architectural discipline, a JAMB DETAIL.
16 JAMB DETAILDESCRIPTIONSCALE
4. SYMBOLS
This symbol (with solid black arrow) represents the direction of true north for this set ofdrawings. This symbol (with outlined arrow) represents the direction of "project" north for this set of drawings.
PLAN NORTH
TRUENORTH
This symbol is a key to a building section drawing taken along the straight line of thesymbol. The arrow points in the direction of the view for the section. The number is areference to the section drawing, in this example, drawing 2, sheet A5.
This symbol is a key to a section drawing taken along the straight line of the symbol.The arrow points in the direction of the view for the section. The number is a referenceto the section drawing, in this example, drawing 2, sheet A6.
D1
03A
W1
6/A2.2
This symbol is a key to a detail drawn of the area within the dashed line. The number is a reference to the detail drawing, in this example, drawing 6, sheet A2.2
This symbol is a key to an elevation drawing. The arrow points in the direction of view for the elevation. The number is a reference to the elevation drawing, in this example, drawing 5, sheet A3.0
This symbol is a key to a partition type, if included. The number is a reference to the partition
This symbol is a key to the door schedule. All doors are keyed with a letter "D" and the room number. If more than one door, "A", "B", etc. is added. See door "D103A" in the Door Schedule.
This symbol is a key to the window schedule if included. Windows are keyed with a pre-fix "W". In this example, see "W1" in the Window Schedule.
5. DIMENSIONS
6. TYPICAL DOOR PLACEMENT
All doors are to be installed with the clearances indicated below unless otherwisenoted. If there is a conflict with the drawings, notify the Architect prior to performing work on that area.
All plan dimensions are to the face of finish or face of masonry unless otherwise noted.
6"min.1'-0"
min.
1'-6"min.
line of wallor
_______________________2A5
_______________________2A6
5/ A3.0
___________A4
SPECIFICATIONS are organized according to the divisions of theUNIFORM CONSTRUCTION INDEX as follows:
DIVISION 1 GENERAL REQUIREMENTSDIVISION 2 EXISTING CONDITIONSDIVISION 3 CONCRETEDIVISION 4 MASONRYDIVISION 5 METALSDIVISION 6 WOOD, PLASTICS, AND COMPONENTSDIVISION 7 THERMAL AND MOISTURE PROTECTIONDIVISION 8 OPENINGSDIVISION 9 FINISHESDIVISION 10 SPECIALTIESDIVISION 11 EQUIPMENTDIVISION 12 FURNISHINGSDIVISION 13 SPECIAL CONSTRUCTIONDIVISION 14 CONVEYING EQUIPMENTDIVISION 21 FIRE SUPPRESSIONDIVISION 22 PLUMBINGDIVISION 23 HEATING, VENTILATION AND AIR-CONDITIONINGDIVISION 25 INTEGRATED AUTOMATIONDIVISION 26 ELECTRICALDIVISION 27 COMMUNICATIONSDIVISION 28 ELECTRONIC SAFETY AND SECURITYDIVISION 31 EARTHWORKDIVISION 32 EXTERIOR IMPROVEMENTSDIVISION 33 UTILITIESDIVISION 34 TRANSPORTATIONDIVISION 35 WATERWAY AND MARINE CONSTRUCTIONDIVISION 40 PROCESS INTEGRATIONDIVISION 41 MATERIAL PROCESSING AND HANDLING EQUIPMENTDIVISION 42 PROCESS HEATING, COOLING AND DRYING EQUIPMENTDIVISION 43 PROCESS GAS AND LIQUID HANDLING, PURIFICATION
AND STORAGEDIVISION 44 POLLUTION CONTROL EQUIPMENTDIVISION 45 INDUSTRY-SPECIFIC MANUFACTURING EQUIPMENTDIVISION 48 ELECTRICAL POWER GENERATION
Indicates dimension to edge of slab
Indicates dimension to face of wall
LOCATION MAPLAREDO, TX
GENERAL NOTES1. GENERAL CONTRACTOR: ALL SUBCONTRACTORS AND
CONSTRUCTION WORKERS MUST READ THE WRITTEN SPECIFICATIONS CONTAINED IN THE PROJECT MANUAL. THE SPECIFICATIONS CONTAIN ADDITIONAL SURFACE PREPARATION OR INSTALLATION REQUIREMENTS FOR THE BUILDING MATERIALS, PRODUCTS OR COMPONENTS THAT ARE BEING PLACED OR INSTALLED.
2. THE INSTALLATION / APPLICATION INFORMATION SHOWN ON THE DRAWINGS IS NOT COMPLETE WITHOUT THE WRITTEN SPECIFICATIONS. IF THE SPECIFICATIONS / PROJECT MANUAL IS NOT WITH THESE DRAWINGS, AS THE GENERAL CONTRACTOR FOR A COPY TO REVIEW BEFORE BEGINNING YOUR WORK.
3. THE INFORMATION REFERENCING THE EXISTING FACILITIES ON THESE DOCUMENTS HAS BEEN PROVIDED BY OTHERS. THE CONSULTANT HAS NOT VERIFIED THE ACCURACY AND / OR COMPLETENESS INCORPORATED AS A RESULT OF ERRONEOUS INFORMATION PROVIDED BY OTHERS. GENERAL CONTRACTOR MUST VERIFY ALL EXISTING CONDITIONS.
FLOOR
SURFACE-PLAN
SIDEELEVATION
4'-0
"
2'-6"
1'-6"
1'-6"
8"MIN.
6" MAX.
9"
MIN
.
2'-3
" M
IN.
3'-0
" M
AX
.
EQUIPMENT ALLOWED
IN SHADED AREA
IF MOUNTED MORE THAN 27" AFF, THE LEADING EDGE OF THE DRINKING FOUNTAIN CAN PROTRUDE A MAXIMUM OF 4 INCHES IN WALKS, CORRIDORS, PASSAGEWAYS, HALLS, OR AISLES.
IF MOUNTED AT 27" AFF OR BELOW THE LEADING EDGE OF THE DRINKING FOUNTAIN CAN PROTRUDE ANY AMOUNT.
FRONT OF TOILET PLAN SIDEELEVATION
1-1/4" TO 1-1/2"
GRAB BAR DETAIL
44"
MA
X.
2'-1
0"
3'-0" MIN.
6" MAX.
FLUSH VALVE HANDLE MUST POINT TOWARD THE WIDE SIDE OF TOILET STALLS IN ALL CASES.
COORDINATE WITH M.E.P. ALL PIPES ARE TO BE PROPERLY INSULATED OR LOCATED TO PREVENT CONTACT.
1'-8
" M
AX
.
2'-6" 2'-6"
KNEE SPACE CLEARANCE8" MIN.
LAV.
3'-4
" M
AX
.
2'-1
0"
MA
X.
2'-3
" M
IN.
9"
MIN
.
11" MIN. 1-'5" MIN.
HAND DRYER / PAPER TOWEL DISPENSOR
MIRROR & SINK
SOAP DISPENSOR
FLOOR MOUNTED TOILET
URINAL (FRONT)
URINAL (SIDE)
URINAL (PLAN)
3'-8
"
U.N
.O.
6'-8
" M
IN.
2'-3
" M
IN.
2'-1
0"
MA
X.
3'-4
" M
AX
.
1'-5
" M
IN.
1'-3" MIN.
3'-8
"
3'-8
" M
AX
. T
O F
LU
SH
CO
NT
RO
L
1'-6
" T
OP
OF
SE
AT
7-9" MAX.
2'-0"
2'-1
0"
1'-1
0"
NAPKIN DISPOSAL UNIT (WHERE SHOWN)
TOILET TISSUE DISPENSOR
2'-6" MIN.
3'-8
" M
AX
.
17
"M
AX
.
3'-8
" M
AX
.
17"
MA
X.
DIMENSION LESS THAN URINAL RIM DEPTH 24" MAX.
13-1/2" MIN. TO FRONT OF URINAL RIM
X
Y
IF X | 24", Y = 2'-6"IF X > 24",Y = 3'-0"
MOUNTING LOCATION REQUIRED AT STRIKE SIDE OF DOOR; SIDELITE SIGNS TO BE DOUBLE, BLANK SIGN ON BACK SIDE OF GLASS
48"
MIN
. T
O
LO
WE
ST
TA
CT
ILE
CH
AR
AC
TE
RRESTROOMS RESTROOMS
LINE OF NEAREST DOOR SWING OR
PROTRUDING OBJECT
ALTERNATE MOUNTING LOCATION WHERE STRIKE SIDE MOUNTING NOT POSSIBLE. (NEAREST ADJACENT WALL)
5'-0
" C
EN
TE
R O
F
SIG
N
MAXIMUM SIDE REACH OVER AN OBSTRUCTION
FORWARD REACH
MAXIMUM FRONT REACH OVER AN OBSTRUCTION
HIGH AND LOW SIDE REACH
2'-1
0"
MA
X.
46"
MA
X.
2'-6" MIN.
2'-0" MAX.
4'-0
" M
AX
.
1'-3
" M
IN.
4'-0"
44"
MA
X.
4'-0
" F
OR
H
OR
IZO
NT
AL
RE
AC
H <
20
"
25" MAX.
15"
MIN
.
48"
MA
X.
10" MAX.
SPACE REQUIREMENTS TURNING SPACE
CLEAR FLOOR
WHEELCHAIR
4'-0
"
5'-0" MIN.2'-6"
60"
MIN
. T
O
HIG
HE
ST
TA
CT
ILE
CH
AR
AC
TE
R
18
" M
IN.
18" MIN.
LCCENTERED ON
TACTILE CHARACTERS
38" MIN. & 43" MAX FOR STANDING PERSONS
CENTER LINE OF SPOUT
LC
15" MIN5" MIN
ACCESSIBILITY STANDARDS NOTE:1. ALL MOUNTING HEIGHTS ARE GIVEN FOR FRONTAL APPROACH UNLESS NOTED OTHERWISE.2. ALL MOUNTING HEIGHTS ARE GIVEN TO THE HIGHEST OPERABLE CONTROL UNLESS NOTED OTHERWISE.
18" MIN.6
0"
MIN
.
DOORS - MANEUVERING CLEARANCES
FRONT APPROACH, PULL SIDE
48"
MIN
.
HINGE APPROACH, PUSH SIDE, DOOR PROVIDED WITH BOTH CLOSER AND LATCH
22" MIN.
24" MIN.
48"
MIN
.
LATCH APPROACH, PUSH SIDE, DOOR PROVIDED WITH CLOSER
NOTE: ALL ASPECTS OF THE PROJECT SHALL COMPLY WITH TEXAS ACCESSIBILITY STANDARDS (TAS) 2012 EDITION, THE ELIMINATION OF ARCHITECTURAL BARRIERS - TEXAS GOVERNMENT CODE, CHAPTER 469; EFFECTIVE MARCH 15TH, 2012. INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING DRAWINGS FOR MINIMUM DIMENSIONS AND CLEARANCES ONLY.
Project NO.:
Date:
Th
e r
eco
rd o
f th
is d
raw
ing
is
on
file
at
the o
ffic
es
of S
lay A
rch
itectu
re,
123 A
ltg
elt A
ven
ue,
San
An
ton
io,
Texa
s 7820
1 &
99
01 M
cP
he
rso
n A
ven
ue,
Su
ite
10
4,
Lare
do
, T
exa
s 7
8045
. T
his
do
cu
men
t is
re
lease
d f
or
the p
urp
ose
of
refe
ren
ce,
co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the a
uth
ori
ty o
f th
e n
am
ed
pro
fess
ion
al, r
eg
istr
atio
n n
um
be
r an
d d
ate
on
th
e s
ea
l affix
ed
ab
ove
. C
OP
YR
IGH
T 2
000 -
, S
lay A
rch
ite
ctu
re.
Th
is d
ocu
me
nt
wa
s p
rep
are
d u
sin
g c
om
pu
ter
ass
iste
d d
esi
gn
an
d d
raftin
g e
qu
ipm
en
t an
d s
ave
d o
n m
ag
netic m
ed
ia.
Neith
er
the p
rin
ted
do
cu
me
nt
no
r th
e m
ag
netic m
ed
ia m
ay b
e a
ltere
d o
r am
en
ded
by a
ny p
art
y o
ther
than
Sla
y A
rch
ite
ctu
re.
Revisions:
123 Altgelt Avenue
San Antonio, Texas
78201
9901 McPherson Avenue, #
104
Laredo, Texas 78045
SAN ANTONIO
LAREDO
A0.0PROJECT INFORMATION
19005
CD
BG
DE
LLA
NO
PA
RK
IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/2019
FIN
AL S
ET
2019
INDEX OF DRAWINGS
SHEETNUMBER SHEET NAME
COVER COVER SHEET
A0.0 PROJECT INFORMATION
ARCHITECTURAL DRAWINGS
A1.0 DEMOLITION SITE PLAN
A1.1 SITE PLAN
A2.0 TOILET ROOM DETAILS
A2.1 TOILET ROOM DETAILS
CIVIL DRAWINGS
C1 SITE PLAN AND DETAILS
C2 GRADING, UTILITIES, AND SWPP PLAN
STRUCTURAL DRAWINGS
S0.1 STRUCTURAL NOTES
S0.2 STRUCTURAL NOTES
S0.3 SPECIAL INSPECTIONS
S1.1 FOUNDATION AND ROOF FRAMING PLANS
S2.1 TYPICAL CONCRETE FRAMING DETAILS
S2.2 CONCRETE FRAMING DETAILS
S3.1 TYPICAL CMU WALL FRAMING DETAILS
MEP DRAWINGS
EP1 ELECTRICAL AND PLUMBING SCHEDULE
EP2 ELECTRICAL AND PLUMBING PLAN
EP3 ELECTRICAL AND DETAILS
E 1 ELECTRICAL SITE PLAN
CD
BG
D
E LLA
NO
P
AR
K IM
P
CIT
Y O
F LA
RE
DO
TE
XA
S
Fost
er A
venu
e an
d S
andm
an S
tree
t
09/12/19
6"
#3 BARS @
12" O.C.E.W.
KEYWAY FORMED BY
FASTENING KEY TO FORM
1"
FILL WITH FLEXIBLE
JOINT SEALER
3
4
"
2"
CONSTRUCTION/KEY JOINT
1"
OF JOINT.
TOOL BOTH SIDES
SEALANT-SELF LEVELING TYPE.
3/4" FILL WITH POLY-URETHANE
CONTRACTION / DUMMY JOINT
EXPANSION JOINT
17" SMOOTH SLEEVE
14
1
4
"
9"
EXPANSION JOINT
3/4" PREMOLDED
DOWELL SET 9"
24" #3 SMOOTH
INTO CONCRETE IN
CENTER OF SLAB @ 18" O.C.
SEALANT-SELF LEVELING TYPE.
3/4" FILL WITH POLY-URETHANE
TOOL BOTH
SIDES OF JOINT
NOTES:
1. CONTRACTION JOINTS
EVERY 10' AND EXPANSION
JOINTS AT 40.0' MAXIMUM ON
CENTER. UNLESS
OTHERWISE SHOWN ON
PLANS.
2. SAW CUT JOINTS
BETWEEN 18 AND 24 HOURS
AFTER CONCRETE POUR
CLASS "A" (3000 PSI)
CONCRETE w/6"x6"
No. 6 WWF
1
1
2"
3
1
4"
4
3
4"
As Shown
SLOPE 2% MAX
90% PROCTOR
DENSITY IS
REQUIRED ON
EMBANKMENT AREA
SPACE
9" DOWELS
@ 24" O.C.
4"
#3 BARS
@ 12" O.C.E.W.
#3 BARS
@ 12" O.C.E.W.
6"
As Shown
NOTES
- TO BE CONSTRUCTED
MONOLITHICALLY
6"
6" (3000 PSI)
CONCRETE
PAVEMENT
@ 28 DAYS
6"
As S
how
n
CONTRACTION
JOINT
LANDING
SIDEWALK
1/2" BARS ON 12" O.C., "
LONG EMBEDDED A MIN.
OF 6" INTO LANDING
HANDICAP RAMP
6x6 No. 6 W.W.F.
1"/
FT
MA
X.
EXPANSION JOINT
SE
E P
LA
NS
1:12 SLOPE
5'6' 6'
1:12 SLOPE
DEPRESSED CURB DEPRESSED CURB
CONCRETE
SIDEWALK
CONCRETE
SIDEWALK
DETAIL "C"
CURB
NOTES (HANDICAP ACCESSIBLE RAMP)
- FULL DEPTH COLORED CONCRETE SHALL BE USED AT ALL RAMPS. THE
CONCRETE SHALL BE MIXED INTO THE PAINT PRIOR TO POURING. THE COLOR
SHALL BE AS DIRECTED BY THE CITY OF LAREDO ENGINEERING DEPARTMENT.
A FINISHED TEXTURE IN COMPLIANCE WITH TDLR REQUIREMENTS SHALL BE
USED AT ALL RAMPS.
- THE FINISH SURFACE OF THE CONCRETE ACCESS RAMP IS TO BE GROOVED
AS SHOWN ON THE DETAIL WITH A 3/4" WIDE BY 1/4" DEEP GROOVE SPACED AT
2" ON CENTER. THE SURFACE SHALL BE ROUGHENED WITH NO LESS THAN A
BROOM FINISH TO PREVENT SLIPPING AND TO DIFFERENTIATE ITS TEXTURE
FROM THAT OF THE STANDARD SIDEWALK.
- DURING CONSTRUCTION, THE LOCATION OF THE CONCRETE ACCESS RAMP
MAY BE SHIFTED FROM THE PROPOSED LOCATION DUE TO UNFORESEEN
EXISTING CONDITIONS WITH ENGINEER APPROVAL.
- CONTRACTOR SHALL BLOCK AND POUR RAMP SEPARATE FROM SIDEWALK
AND RAMP WINGS.
CURB
WITH ARCHITECT.
WHITE EMBLEM. VERIFY
2. BLUE SQUARE AROUND
2
1
"
R
2
5
"
R
1'-3"
NOTE:
1. PROVIDE ONE
SYMBOL FOR
EACH HANDICAP
PARKING SPACE.
6 1/2" R
5'-0"
2
"
#3 BARS
@ 12" O.C.E.W.
6"
See Plans
NOTES
1. CONTRACTION
JOINTS SHALL BE
PLACED AT A MAXIMUM
OF 15'.
2. EXPANSION JOINT
SHALL BE PLACED AT
MIDCOURT.
6" (3000 PSI)
CONCRETE
PAVEMENT
@ 28 DAYS
6"
#3 BARS
@ 12" O.C.E.W.
1'1'
6"
CONCRETE
PAVEMENT
1
1
8"
CALL BEFORE YOU DIG!
TEXAS ONE CALL PARTICIPANTS REQUEST
48 HOURS NOTICE BEFORE YOU DIG, DRILL,
OR BLAST-STOP, CALL!
TEXAS ONE CALL SYSTEM
1-800-245-4545
AT&T
AT 1-800-828-5127
THE LONE STAR NOTIFICATION CENTER
1-800-669-8344
TEXAS EXCAVATION SAFETY SYSTEM
1-800-344-8377
Plan - SiteScale: 1" = 20' Scale
Sheet
C1
1" = 20'
01 02
OF
0 1 2 3
0 10 20 30
LEGEND
EXISTING SANITARY SEWER
EXISTING GAS LINE
EXISTING AT&T LINE
EXISTING WATER LINE
EXISTING OVERHEAD LINE
EXISTING STORM DRAIN LINE
EXISTING WATER LINE
EXISTING UNDERGROUND CABLE
EXISTING FENCE
EXISTING CURB AND GUTTER
EXISTING IRRIGATION VALVE
PROPOSED CONCRETE
EXISTING ELECTRICAL BOX
Project NO.:
Date:
Revisions:
123 Altgelt Avenue
San Antonio, Texas 78201
T: 210.736.3009
9901 McPherson Avenue, #104
Laredo, Texas 78045
T: 956.791.0405
SAN ANTONIO
LAREDO
19009
09/12/2019
CO
NS
TRU
CTI
ON
DO
CU
ME
NTS
EST.
198
2
9901
McP
hers
on A
venu
e, S
uite
104
Lare
do, T
exas
780
45(9
56) 7
91-0
405
- Tel
.(9
56) 7
91-1
703
- fax
.
SLA
Y E
NG
INEE
RIN
GC
ompa
ny, I
nc.
REG
ISTR
ATI
ON
NU
MB
ER F
-190
1C
DB
G D
E LLA
NO
P
AR
K
IM
PR
OV
EM
EN
TS
P
RO
JE
CT
A
RAMIRO IBARRA
G
X
E
S
P
R
O
F
E
N
109982
C
L
S
I
I
O
N
S
E
D
L
E
N
A
S
T
T
E
OF
T
E
N
E
E
I
R
S
A
The
reco
rd o
f thi
s dr
awin
g is
on
file
at th
e of
fices
of S
lay
Arc
hite
ctur
e, 1
23 A
ltgel
t Ave
nue,
San
Ant
onio
, Tex
as 7
8201
& 9
901
McP
hers
on R
oad,
Sui
te 1
04, L
ared
o, T
exas
780
45. T
his
docu
men
t is
rele
ased
for
the
purp
ose
of r
efer
ence
, coo
rdin
atio
n, a
nd/o
f fac
ility
man
agem
ent u
nder
the
auth
ority
of t
he n
amed
pro
fess
iona
l, re
gist
ratio
n nu
mbe
r an
d da
te o
n th
e se
al a
ffixe
d ab
ove.
CO
PY
RIG
HT
2000
- 20
19, S
lay
Arc
hite
ctur
e. T
his
docu
men
t was
pre
pare
d us
ing
com
pute
r as
sist
ed d
esig
n an
d dr
aftin
g eq
uipm
ent a
nd s
aved
on
mag
netic
med
ia.
Nei
ther
the
prin
ted
docu
men
t nor
the
mag
netic
med
ia m
ay b
e al
tere
d or
am
ende
d by
any
par
ty o
ther
than
Sla
y A
rchi
tect
ure.
Fost
er A
venu
e an
d S
andm
an S
tree
tC
ITY
OF
LAR
ED
O T
EX
AS
Plan - Basketball CourtScale: 1" = 10'
SIT
E P
LA
N
AN
D
DE
TA
ILS
TYPICAL ACCESS RAMP SCALE: N.T.S.
PAINTED ACCESSIBLE PARKING SYMBOLSCALE: N.T.S.
TYPICAL ACCESS RAMP SCALE: N.T.S.
Deduct Alternate
Package #1
(Refer to Architecture
Plans for Deduct
Alternate items)
EXISTING BENCH
GENERAL NOTES
1. ALL DIMENSIONS ARE TO THE EDGE OF CONCRETE UNLESS
NOTED OTHERWISE ON THE PLANS.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
COORDINATE ALL CONSTRUCTION ACTIVITIES UNDER THE
REQUIREMENTS OF THE CITY OF LAREDO. THIS INCLUDES ALL
NECESSARY PERMITS, NOTIFICATIONS, PUBLICATIONS,
SPECIFICATIONS AND SHOP DRAWINGS SUBMITTALS FOR
CONSTRUCTION. NO CONSTRUCTION ACTIVITIES SHALL
COMMENCE UNTIL PROPER CLEARANCE IS PROVIDED BY THE
APPROPRIATE CITY OF LAREDO DEPARTMENTS. CONTRACTOR
SHALL CONTACT CITY OF LAREDO ROW MANAGER BEFORE
COMMENCING ANY WORK ON THE ROW.
3. RIGHT-OF-WAY AND PROPERTY BOUNDARIES ARE FOR
ILLUSTRATION PURPOSES ONLY, AND DO NOT REPRESENT AN
ATTEMPT BY THE ENGINEER TO CONFIRM THE ACTUAL
PROPERTY BOUNDARIES.
4. THE CONTRACTOR SHALL PROVIDE CONSTRUCTION
STAKING FOR THE PROJECT, AS MAY BE REQUIRED.
5. ALL MATERIALS AND CONSTRUCTION PROCEDURES WITHIN
THE SCOPE OF THIS PROJECT SHALL CONFORM TO ALL
APPLICABLE CITY OF LAREDO STANDARD TECHNICAL
SPECIFICATION MANUAL.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE
DEMOLITION AND THE PROPER REMOVAL/DISPOSAL OF THE
ITEMS SHOWN ON THESE PLANS TO BE REMOVED, INCLUDING
BUT NOT LIMITED TO IRRIGATION PIPES, IRRIGATION
HARDWARE, TREES, TRASH, BOULDERS AND MISCELLANEOUS
DEBRIS.
7. WHERE TREES OR LANDSCAPING ARE TO BE REMOVED OR
RELOCATED AND/OR AFFECTED BY THE PROPOSED
IMPROVEMENTS, THE CONTRACTOR SHALL COORDINATE THE
SAFE REMOVAL AND RELOCATION OF THESE ITEMS AS
DIRECTED BY THE CITY OF LAREDO PARKS DEPARTMENT.
8. CONTRACTOR SHALL INCLUDE IN HIS BID THE REQUIRED
ADJUSTMENTS OF ALL VALVES, VALVE COVERS, MANHOLES
LIDS, FIRE HYDRANTS, CLEANOUTS, TELEPHONE PEDESTALS,
AND ANY OTHER MISC. UTILITY ITEM WHETHER SHOWN ON
THESE PLANS OR NOT.
9. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING
EXISTING FACILITIES FROM DAMAGE AND COST OF REPAIR TO
EXISTING FACILITIES AND IMPROVEMENTS AS A RESULT OF
THE CONTRACTOR'S WORK. ANY EXISTING PAVEMENT, CURBS,
SIGNS, IRRIGATION LINES, ELECTRICAL LINES, SIDEWALKS,
WALLS, FENCES, UTILITY INFRASTRUCTURE, TREES, ETC.
DAMAGED OR REMOVED WILL BE REPAIRED BY THE
CONTRACTOR AT HIS EXPENSE.
10. THE LOCATIONS OF ALL EXISTING UTILITIES SHOWN ON
THESE PLANS HAVE BEEN BASED UPON RECORD
INFORMATION ONLY AND MAY NOT MATCH LOCATIONS AND/OR
DEPTHS AS CONSTRUCTED. THE CONTRACTOR SHALL
CONTACT EACH OF THE INDIVIDUAL UTILITY COMPANIES, FOR
ASSISTANCE IN DETERMINING EXISTING UTILITY LOCATIONS
AND DEPTHS PRIOR TO BEGINNING ANY CONSTRUCTION.
CONTRACTOR SHALL FIELD VERIFY LOCATIONS AND DEPTHS
PRIOR TO BEGINNING ANY CONSTRUCTION. CONTRACTOR
SHALL FIELD VERIFY LOCATIONS OF ALL UTILITY CROSSINGS
(BOTH VERTICALLY AND HORIZONTALLY) PRIOR TO BEGINNING
ANY CONSTRUCTION.
FG FINISH GRADE
FL FLOW LINE
FLOW ARROW
EXISTING
CONTOURS
FLOW LINE
GRADE BREAK
PROPOSED REINFORCED
SILT FENCE
Plan - Grading, Utilities, and SWPPScale: 1" = 20'
TRENCH EXCAVATION
PROTECTION
CONTRACTOR AND/OR
CONTRACTORS INDEPENDENTLY
RETAINED EMPLOYEE OR
STRUCTURAL
DESIGN/GEOTECHNICAL/
SAFETY/EQUIPMENT CONSULTANT,
IF ANY, SHALL REVIEW THESE
PLANS AND ANY AVAILABLE
GEOTECHNICAL INFORMATION
AND THE ANTICIPATED
INSTALLATION SITE(S) WITHIN THE
PROJECT WORK AREA IN ORDER
TO DEVELOP THE CONTRACTOR'S
PLANS TO IMPLEMENT THE
PROJECT DESCRIBED IN THE
CONTRACT DOCUMENTS. THE
CONTRACTOR'S PLANS SHALL
PROVIDE FOR ADEQUATE TRENCH
SAFETY SYSTEMS THAT COMPLY
WITH MINIMUM OSHA STANDARDS
FOR TRENCH EXCAVATIONS.
SPECIFICALLY, CONTRACTOR OF
CONTRACTOR'S INDEPENDENTLY
RETAINED EMPLOYEE OR SAFETY
CONSULTANT SHALL DEVELOP
AND IMPLEMENT A TRENCH
SAFETY PROGRAM IN
ACCORDANCE WITH OSHA
STANDARDS GOVERNING THE
PRESENCE AND ACTIVITIES OF
INDIVIDUALS WORKING IN AND
AROUND TRENCH EXCAVATION.
Permit Filing
Contractor must complete and file TCEQ forms as required by the General
Permit No. TXR150000 associated with construction activity coverage under the
TPDES General Permit for storm water discharges associated with construction
activity in compliance with EPA requirements.
Sequence of Construction
The general order of activities will be as follows:
1. Clear and grub for perimeter control (silt fences)
2. Install all perimeter controls, downstream of any construction activity.
3. Install construction entrances and exits to be used while working in the area at
the locations shown on the plan, or as approved by the Engineer.
4. General site grading; stabilize disturbed areas and stockpiles within seven (7)
days.
5. General project construction; site grading, excavation, and filling construction
of amentities.
6. When all construction is complete and is stabilized and approved by the
Project Engineer, remove temporary structural controls and regrade any areas
disturbed by their removal.
Storm Water Management
Storm water drainage will be through curb and gutter flow, into an underground
storm drainage system, that connects to the City Drainage System.
General Notes
1. Contractor shall follow the requirements for temporary and permanent erosion
control as outlined on the plans and specifications.
2. A copy of the storm water pollution prevention plan (SWPPP) shall be kept on
the construction site at all times.
3. Silt fence and gravel entrances must be installed prior to proceeding with any
construction.
4. Gravel entrance as shown may be relocated if approved by the Engineer.
461
CALL BEFORE YOU DIG!
TEXAS ONE CALL PARTICIPANTS REQUEST
48 HOURS NOTICE BEFORE YOU DIG, DRILL,
OR BLAST-STOP, CALL!
TEXAS ONE CALL SYSTEM
1-800-245-4545
AT&T
AT 1-800-828-5127
THE LONE STAR NOTIFICATION CENTER
1-800-669-8344
TEXAS EXCAVATION SAFETY SYSTEM
1-800-344-8377
Scale
Sheet
C2
1" = 20'
02 02
OF
0 1 2 3
0 10 20 30
UTILITIES, GENERAL
1. THE CONTRACTOR IS SPECIFICALLY CAUTIONED THAT
THE LOCATION AND/OR ELEVATION OF EXISTING
UTILITIES AND STRUCTURES AS SHOWN ON THESE
PLANS IS BASED ON RECORDS FROM VARIOUS UTILITY
COMPANIES AND WHERE POSSIBLE, MEASUREMENTS
TAKEN ON THE FIELD. THIS INFORMATION IS NOT TO BE
RELIED ON AS BEING EXACT OR COMPLETE. THE
LOCATION OF ALL UNDERGROUND UTILITIES AND
STRUCTURES SHALL BE VERIFIED IN THE FIELD BY THE
CONTRACTOR PRIOR TO THE START OF CONSTRUCTION.
THE CONTRACTOR MUST CONTACT THE APPROPRIATE
UTILITY COMPANY, ANY GOVERNING PERMITTING
AUTHORITY, AND "DIG TEST" AT LEAST 72 HOURS PRIOR
TO ANY EXCAVATION WORK TO REQUEST EXACT FIELD
LOCATION OF UTILITIES INTERFERING WITH THE
PROPOSED CONSTRUCTION AND APPROPRIATE
REMEDIAL ACTION TAKEN BEFORE PROCEEDING WITH
THE WORK. IT SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO RELOCATE ALL EXISTING UTILITIES
WHICH CONFLICT WITH THE PROPOSED IMPROVEMENTS
SHOWN ON THE PLAN PER THE APPROPRIATE REMEDIAL
ACTION AGREED UPON BY THE ENGINEER.
2. THE CONTRACTOR SHALL REQUEST ALL UTILITIES
LINE LOCATION BEFORE PERFORMING ANY EXCAVATION,
AND SECURE A R.O.W. PERMIT FOR ALL PROPOSED
PROJECT IMPROVEMENTS.
3. ALL EXISTING VALVES, FIRE HYDRANTS, WATER
SERVICES, METER BOXES, MANHOLES, CLEAN OUTS,
SHALL BE ADJUSTED TO NEW FINISH GRADE.
4. CONTRACTOR SHALL CONTACT ENGINEER IF INVERT
OF EXISTING SANITARY SEWER LINE IS HIGHER THAN
SHOWN BEFORE PROCEEDING.
5. CONTRACTOR SHALL CONTACT THE CITY OF LAREDO
UTILITIES DEPARTMENT BEFORE EXCAVATING AND TIE-IN
ON THE EXISTING SANITARY SEWER LINE.
6. ALL WATER AND SEWER MAIN APPURTENANCES,
MATERIALS, METHODS OF INSTALLATION AND TESTING
REQUIREMENTS, SHALL MEET OR EXCEED THE CITY OF
LAREDO STANDARD TECHNICAL SPECIFICATION MANUAL.
7. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING
AND PAYING FOR ANY PERMITS AND/OR CONNECTION
FEES REQUIRED TO CARRY OUT THE WORK SHOWN ON
THESE PLANS.
CONTACTS
1. AEP CONTACT: LINO VILLARREAL OFFICE 956-721-3029
2. AT&T CONTACT: LILY FARIAS, OFFICE: 956-727-6748.
3. CENTERPOINT ENERGY CONTACT: ROEL PENA,
OFFICE: 956-723-6352.
4. TIME WARNER CABLE CONTACT: JAVIER ESQUIVEL,
OFFICE: (956)235-6318.
5. LAREDO WATER UTILITIES DEPARTMENT CONTACT:
ROLAND LOZANO, OFFICE: 956-794-1625.
6. CITY OF LAREDO BUILDING DEVELOPMENT SERVICES
CONTACT: (956)794-1625.
LEGEND
EXISTING OVERHEAD LINE
EXISTING GAS LINE
EXISTING AT&T LINE
EXISTING SANITARY SEWER
EXISTING MANHOLE
EXISTING POWER POLE
EXISTING BOUNDARY
EXISTING WATER LINE
EXISTING WATER SERVICE
Project NO.:
Date:
Revisions:
123 Altgelt Avenue
San Antonio, Texas 78201
T: 210.736.3009
9901 McPherson Avenue, #104
Laredo, Texas 78045
T: 956.791.0405
SAN ANTONIO
LAREDO
19009
09/12/2019
CO
NS
TRU
CTI
ON
DO
CU
ME
NTS
EST.
198
2
9901
McP
hers
on A
venu
e, S
uite
104
Lare
do, T
exas
780
45(9
56) 7
91-0
405
- Tel
.(9
56) 7
91-1
703
- fax
.
SLA
Y E
NG
INEE
RIN
GC
ompa
ny, I
nc.
REG
ISTR
ATI
ON
NU
MB
ER F
-190
1C
DB
G D
E LLA
NO
P
AR
K
IM
PR
OV
EM
EN
TS
P
RO
JE
CT
A
RAMIRO IBARRA
G
X
E
S
P
R
O
F
E
N
109982
C
L
S
I
I
O
N
S
E
D
L
E
N
A
S
T
T
E
OF
T
E
N
E
E
I
R
S
A
The
reco
rd o
f thi
s dr
awin
g is
on
file
at th
e of
fices
of S
lay
Arc
hite
ctur
e, 1
23 A
ltgel
t Ave
nue,
San
Ant
onio
, Tex
as 7
8201
& 9
901
McP
hers
on R
oad,
Sui
te 1
04, L
ared
o, T
exas
780
45. T
his
docu
men
t is
rele
ased
for
the
purp
ose
of r
efer
ence
, coo
rdin
atio
n, a
nd/o
f fac
ility
man
agem
ent u
nder
the
auth
ority
of t
he n
amed
pro
fess
iona
l, re
gist
ratio
n nu
mbe
r an
d da
te o
n th
e se
al a
ffixe
d ab
ove.
CO
PY
RIG
HT
2000
- 20
19, S
lay
Arc
hite
ctur
e. T
his
docu
men
t was
pre
pare
d us
ing
com
pute
r as
sist
ed d
esig
n an
d dr
aftin
g eq
uipm
ent a
nd s
aved
on
mag
netic
med
ia.
Nei
ther
the
prin
ted
docu
men
t nor
the
mag
netic
med
ia m
ay b
e al
tere
d or
am
ende
d by
any
par
ty o
ther
than
Sla
y A
rchi
tect
ure.
Fost
er A
venu
e an
d S
andm
an S
tree
tC
ITY
OF
LAR
ED
O T
EX
AS
GR
AD
IN
G,
UT
ILIT
IE
S,
AN
D S
WP
P
PLA
N
INSET AScale: 1" = 10'
SEE INSET A
Deduct Alternate
Package #1
(Refer to Architecture
Plans for Deduct
Alternate items)
LEGEND
EXISTING TREE
EXISTING STONE
EXISTING BENCH
EXISTING SIGNAGE
EXISTING TRASH RECEPTACLE
EXISTING LIGHT POLE
exist. playgroundarea with PIPsurfacing
exis
ting
trac
k
ex. conc. sidewalk
conc. pad
exist.drink. ftn.
ex. roof over
ex. c
onc.
sid
ewal
k
exis
ting
trac
k
RELOCATE BENCH,TRASH BIN, & SIGNAGE
RELOCATE TREEAND STONE
RELOCATESIGNAGE
REMOVE CURB RAMP& PORTION OF SIDEWALK
RE: CIVIL
existing stormdrain inlet
EXISTING ELECTRICALSVC. PANEL
DEMO EXISTING PORTION OF CURB AS REQUIREDFOR NEW WORK
Project NO.:
Date:
The
reco
rd o
f thi
s dr
awin
g is
on
file
at th
e of
fices
of S
lay
Arc
hite
ctur
e, 1
23 A
ltgel
t Ave
nue,
San
Ant
onio
, Tex
as 7
8201
& 9
901
McP
hers
on R
oad,
Sui
te 1
04, L
ared
o, T
exas
780
45. T
his
docu
men
t is
rele
ased
for
the
purp
ose
of r
efer
ence
, coo
rdin
atio
n, a
nd/o
f fac
ility
man
agem
ent u
nder
the
auth
ority
of t
he n
amed
pro
fess
iona
l, re
gist
ratio
n nu
mbe
r an
d da
te o
n th
e se
al a
ffixe
d ab
ove.
CO
PY
RIG
HT
2000
- 20
19, S
lay
Arc
hite
ctur
e. T
his
docu
men
t was
pre
pare
d us
ing
com
pute
r as
sist
ed d
esig
n an
d dr
aftin
g eq
uipm
ent a
nd s
aved
on
mag
netic
med
ia.
Nei
ther
the
prin
ted
docu
men
t nor
the
mag
netic
med
ia m
ay b
e al
tere
d or
am
ende
d by
any
par
ty o
ther
than
Sla
y A
rchi
tect
ure.
Revisions:
123 Altgelt Avenue
San Antonio, Texas 78201
T: 210.736.3009
9901 McPherson Avenue, #104
Laredo, Texas 78045
T: 956.791.0405
SAN ANTONIO
LAREDO
19005
CD
BG
D
E LLA
NO
P
AR
K IM
PR
OV
EM
EN
TS
P
RO
JE
CT
09/12/19
CIT
Y O
F LA
RE
DO
TE
XA
S
CO
NS
TRU
CTI
ON
DO
CU
ME
NTS
Fost
er A
venu
e an
d S
andm
an S
tree
t
GENERAL DEMOLITION NOTES:
1. LOCATION OF EXISTING UTILITIES AND DRAINAGE SHOWN AREAPPROXIMATE ONLY. ACTUAL LOCATION AND DEPTHS MUST BE VERIFIEDBY THE CONTRACTOR PRIOR TO BEGINNING CONSTRUCTION.
2. CONTRACTOR IS RESPONSIBLE FOR CLEARING THE SITE OF ALLOBSTRUCTIONS THAT EXIST PRIOR TO THE START OF CONSTRUCTION SOAS NOT TO IMPEDE CONSTRUCTION PROGRESS.
3. CONTRACTOR SHALL COORDINATE WITH THE OWNER TO IDENTIFYANY MATERIAL OR EQUIPMENT SCHEDULED FOR REMOVAL, AND ORRELOCATION TO BE SALVAGED AND RE-USED. CONTRACTOR SHALLREPLACE ANY DESTROYED MATERIAL OR EQUIPMENT THAT WAS MARKEDFOR SALVAGE OR RELOCATION.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR ACQUIRING ALLNECESSARY PERMITS/ APPROVALS BEFORE BEGINNING DEMOLITIONAND/OR CONSTRUCTION.
5. CONTRACTOR SHALL COORDINATE WITH OWNER FOR ANY TREEREMOVAL AND REMOVAL AND /OR REPLACEMENT OF EXISTING IRRIGATIONPIPING PRIOR TO CONSTRUCTION.
6. COVER AND PROTECT TREES, EQUIPMENT AND FIXTURES TOREMAIN DURING DEMOLITION AND CONSTRUCTION OPERATIONS.
7. COORDINATE DISCONNECTION AND DOWNTIME OF UTILITIES WITHOWNER AT LEAST 48 HOURS PRIOR TO STARTING WORK.
DE LLANO PARK
DEMOLITION SITE PLANSURVEY / EXISTING CONDITIONS1
0 10' 20' 40' 80'
A1.0
09/12/19
LEGEND
EXISTING TREE
NEW POURED IN PLACE RUBBER
NEW CONCRETE PAVING
INS
TALL
PLAYGROUND SURFACING
EXISTING STONE
EXISTING BENCH
EXISTING SIGNAGE
EXISTING TRASH RECEPTACLE
EXISTING LIGHT POLE
exist. playgroundarea with PIPsurfacing
PR
OP
ER
TY L
INE
- A
PP
RO
X. L
OC
ATI
ON
EXIST. LIGHT POLE
35'X80'
TOILET ROOMS
exis
ting
trac
k
ex. conc. sidewalk
exis
ting
chai
n lin
k fe
nce
conc. pad
CONCRETEBASKETBALL
COURT 60' X 104'
exist.drink. ftn.
ex. roof over
existing chain link fence
ex. c
onc.
sid
ewal
k
8' HIGH CHAIN LINK FENCE
NEW SIDEWALK
P2
P1
P4
P3
P3
P3 P3
F2
F2
F2
NEW
30'-0
"
NEW PIP PLAYGROUNDSURFACING SYSTEM
34'-10"
NEW CURB RAMPRE: CIVIL
NEW STRIPINGFOR ACCESSIBLEPARKING SPACES
RELOCATED BENCH & TRASH BIN
NEW FABRIC SHADE STRUCTURE
VERIFY LOCATION W/ ARCHITECT
RE: CIVIL
6' BENCH WITH BACK - SURFACE MOUNTED
PARK EQUIPMENT
F1
TRASH CONTAINERF2
OTH
ER
SIN
STA
LL
GC
INS
TALL
P1
P2
P3
P4AQUA GATHER STATION By Aquatix by landscape structures
#120458 SANDBOX
ADJUSTABLE BASKETBALL GOAL
#221292A 5" ARCH SWING FRAME 8' BEAM HEIGHT ONLY#221293A 5" ARCH SWING FRAME ADD'L BAY 8' BEAM HT. ONLY(2) #174018A BELT SEAT W/ PROGUARD CHAiNS FOR 8' HT.(1) #177350A MOLDED BUCKET SEAT (5-12 YRS) W/ CHAINS/
PROGUARD CHAINS FOR 8' BEAM HT.(1) #218671C MOLDED BUCKET SEAT (2-5 YRS) W. HARNESS &
CHAINS PROGUARD CHAINS FOR 8' BEAM HT.
FOR PLAYGROUND EQUIPMENT CONTACT:RAY VERNON AT (956)566-2888, [email protected] EXERPLAY, INC.
CONTACT: Gregory Neal at (505)577-7004, [email protected]
CONCRETE SIDEWALK (RE: C1)
DEDUCT ALTERNATE PKG #1
TRASH CONTAINER F2
P1AQUA GATHER STATION By Aquatix
CONCRETE PAD (RE: C1)
CIVIL QTY.
930 SF
465 SF
WATER SUPPLY LINE (RE: C2) 250 LF
ARCHITECTURAL (RE: A1)
6' SURFACE MTD. BENCH WITH BACK F1
W/ ACTIVATION BOLLARD By Aquatix
MEP
FLOOR DRAIN AND DRAIN PIPE (RE: EP1)
1
1
1
RE-CIRCULATION AND PUMP SYSTEM By Aquatix(RE: EP1, EP2)
1
1-#6 G IN 1" CONDUIT FROM EQUIP. GROUNDINGLUG TO GROUND BUS IN PANEL (RE: EP1, E3)
360 LF
1
1
2
3
4
5
6
7
8
9
THESE ITEMS SHOULD BE PART OF THE BASE BID.PROVIDE A COST FOR THE ALTERNATE PACKAGE DESCRIBED ABOVESHOULD THE OWNER DECIDE TO DEDUCT IT FROM THE BASE BID.
ART MURAL OVER TOILET ROOM WEST FACING WALL
DEDUCT ALTERNATE PKG #2
STANDARD CMU IN LIEU OF SPLIT FACE ON
QTY.
1
64 SF
PROVIDE CLEAR ANTI-GRAFFITI SEAL OVER ART WORK 64 SF
1
2
3
(REFER TO SPEC SECTION 01 2100 ALLOWANCES)
EXTERIOR WALL IN 10'-8" X 6'-0" MURAL AREA
GENERAL NOTES:
1. REFER TO CIVIL FOR GRADING, DIMENSIONS AND DETAILS.
2. ALL EQUIPMENT SHALL BE PROVIDED AND INSTALLED BYEQUIPMENT SUPPLIER. ALL AREAS SHALL BE PREPARED ASRECOMMENDED BY EQUIPMENT SUPPLIER.
3. MARKINGS FOR BASKETBALL COURTS ER OFFICIAL GAMESTANDARDS AND REGULATIONS.
4. ALL NEW CONC. WALKS ARE TO HAVE A 5% MAX. SLOPE ANDA 2% MAX. CROSS SLOPE.
5. CURB RAMPS 8.3% MAX. SLOPE, 2% MAX. CROSS SLOPE,WITH 1/2" WIDE BY 1/8" DEEP GROOVES AT 2" O.C. EXTENDING THEFULL WIDTH OF THE RAMP AT AN ANGLE THAT WILL ALLOW WATERTO DRAIN FROM GROOVES. THE RAMP MUST ALSO BE OFCONTRASTING COLOR TO BE SELECTED BY THE ARCHITECT. FIELDVERIFY RISE TO SET RAMP DEPTH.
6. ALL JOINTS SHOWN ON WALKS ARE CONTROL JOINTS &EXPANSION JOINTS. CONTROL JOINTS AT 5'-0" O.C., AND EXPANSIONJOINTS @ 20'-0" O.C. UNLESS SHOWN OTHERWISE.
7. REFER TO CIVIL DRAWINGS FOR EXPANSION JOINTS,CONTROL JOINTS AND CONCRETE CURB CONSTRUCTION.
8. REFER TO CIVIL FOR ALL UTILITY LOCATIONS & EASEMENTS,AND GRADING.
9. REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF NEWLIGHTING FIXTURES AND CONDUITS.
10. LANDSCAPE ELEMENTS SHOWN ON PLAN INDICATEGENERAL LOCATION OF EXISTING TREE AND SHRUB PLANTINGS.
SITE PLANDE LLANO PARK
10 10' 20' 40' 80'
A1.1
Project NO.:
Date:
The
reco
rd o
f thi
s dr
awin
g is
on
file
at th
e of
fices
of S
lay
Arc
hite
ctur
e, 1
23 A
ltgel
t Ave
nue,
San
Ant
onio
, Tex
as 7
8201
& 9
901
McP
hers
on R
oad,
Sui
te 1
04, L
ared
o, T
exas
780
45. T
his
docu
men
t is
rele
ased
for
the
purp
ose
of r
efer
ence
, coo
rdin
atio
n, a
nd/o
f fac
ility
man
agem
ent u
nder
the
auth
ority
of t
he n
amed
pro
fess
iona
l, re
gist
ratio
n nu
mbe
r an
d da
te o
n th
e se
al a
ffixe
d ab
ove.
CO
PY
RIG
HT
2000
- 20
19, S
lay
Arc
hite
ctur
e. T
his
docu
men
t was
pre
pare
d us
ing
com
pute
r as
sist
ed d
esig
n an
d dr
aftin
g eq
uipm
ent a
nd s
aved
on
mag
netic
med
ia.
Nei
ther
the
prin
ted
docu
men
t nor
the
mag
netic
med
ia m
ay b
e al
tere
d or
am
ende
d by
any
par
ty o
ther
than
Sla
y A
rchi
tect
ure.
Revisions:
123 Altgelt Avenue
San Antonio, Texas 78201
T: 210.736.3009
9901 McPherson Avenue, #104
Laredo, Texas 78045
T: 956.791.0405
SAN ANTONIO
LAREDO
19005
CD
BG
D
E LLA
NO
P
AR
K IM
PR
OV
EM
EN
TS
P
RO
JE
CT
09/12/19
CIT
Y O
F LA
RE
DO
TE
XA
S
CO
NS
TRU
CTI
ON
DO
CU
ME
NTS
Fost
er A
venu
e an
d S
andm
an S
tree
t
DEDUCTALTERNATE #1REFER TO SCHEDULE
DEDUCTALTERNATE #2REF. TO 2/A1.2 &ALTERNATESCHEDULE
1/4" = 1'-0"
5 @ TOILET ROOMS SIDE WALL
EXTERIOR ELEVATION2DEDUCT ALTERNATE #2
0" F.F. 0" F.F.
ROOF11' - 4" A.F.F.
PL HT.8' - 0" A.F.F.
PL HT.8' - 0" A.F.F.
SCREEN WALL HT.6' - 0" A.F.F.
METAL ROOF OVER WOOD FRAME ROOF STRUCTURE
8X8X6 CMU SOLAR SCREEN DEC. BLK. W/
VENT SCREEN
8X8X16 REINFORCED SPLIT FACE CMU
8X2X16 CMU CAP
7' -
2"
DEDUCT ALTERNATE PKG #2. PROVIDE MURAL OVER STANDARDCMU WALL SURFACE
FRAME AROUND MURAL
SEAL ART WORK WITH ANTI-GRAFFITICLEAR COATING
8"8"
6' -
0"
7' -
4"
16" 10' - 8"
1
9/12/19
LEGEND
EXISTING TREE
NEW POURED IN PLACE RUBBER
NEW CONCRETE PAVING
INS
TALL
PLAYGROUND SURFACING
EXISTING STONE
EXISTING BENCH
EXISTING SIGNAGE
EXISTING TRASH RECEPTACLE
EXISTING LIGHT POLE
exist. playgroundarea with PIPsurfacing
PR
OP
ER
TY L
INE
- A
PP
RO
X. L
OC
ATI
ON
EXIST. LIGHT POLE
35'X80'
TOILET ROOMS
exis
ting
trac
k
ex. conc. sidewalk
exis
ting
chai
n lin
k fe
nce
conc. pad
CONCRETEBASKETBALL
COURT 60' X 104'
exist.drink. ftn.
ex. roof over
existing chain link fence
ex. c
onc.
sid
ewal
k
8' HIGH CHAIN LINK FENCE
NEW SIDEWALK
P2
P1
P4
P3
P3
P3 P3
F2
F2
F2
NEW
30'-0
"
NEW PIP PLAYGROUNDSURFACING SYSTEM
34'-10"
NEW CURB RAMPRE: CIVIL
NEW STRIPINGFOR ACCESSIBLEPARKING SPACES
RELOCATED BENCH & TRASH BIN
NEW FABRIC SHADE STRUCTURE
VERIFY LOCATION W/ ARCHITECT
RE: CIVIL
6' BENCH WITH BACK - SURFACE MOUNTED
PARK EQUIPMENT
F1
TRASH CONTAINERF2
OTH
ER
SIN
STA
LL
GC
INS
TALL
P1
P2
P3
P4AQUA GATHER STATION By Aquatix by landscape structures
#120458 SANDBOX
ADJUSTABLE BASKETBALL GOAL
#221292A 5" ARCH SWING FRAME 8' BEAM HEIGHT ONLY#221293A 5" ARCH SWING FRAME ADD'L BAY 8' BEAM HT. ONLY(2) #174018A BELT SEAT W/ PROGUARD CHAiNS FOR 8' HT.(1) #177350A MOLDED BUCKET SEAT (5-12 YRS) W/ CHAINS/
PROGUARD CHAINS FOR 8' BEAM HT.(1) #218671C MOLDED BUCKET SEAT (2-5 YRS) W. HARNESS &
CHAINS PROGUARD CHAINS FOR 8' BEAM HT.
FOR PLAYGROUND EQUIPMENT CONTACT:RAY VERNON AT (956)566-2888, [email protected] EXERPLAY, INC.
CONTACT: Gregory Neal at (505)577-7004, [email protected]
CONCRETE SIDEWALK (RE: C1)
DEDUCT ALTERNATE PKG #1
TRASH CONTAINER F2
P1AQUA GATHER STATION By Aquatix
CONCRETE PAD (RE: C1)
CIVIL QTY.
930 SF
465 SF
WATER SUPPLY LINE (RE: C2) 250 LF
ARCHITECTURAL (RE: A1)
6' SURFACE MTD. BENCH WITH BACK F1
W/ ACTIVATION BOLLARD By Aquatix
MEP
FLOOR DRAIN
1
1
1
RE-CIRCULATION AND PUMP SYSTEM (RE: EP1, EP2)
1
1-#6 G IN 1" CONDUIT FROM EQUIP. GROUNDINGLUG TO GROUND BUS IN PANEL (RE: EP1, E3)
360 LF
1
1
2
3
4
5
6
7
8
9
THESE ITEMS SHOULD BE PART OF THE BASE BID.PROVIDE A COST FOR THE ALTERNATE PACKAGE DESCRIBED ABOVESHOULD THE OWNER DECIDE TO DEDUCT IT FROM THE BASE BID.
GENERAL NOTES:
1. REFER TO CIVIL FOR GRADING, DIMENSIONS AND DETAILS.
2. ALL EQUIPMENT SHALL BE PROVIDED AND INSTALLED BYEQUIPMENT SUPPLIER. ALL AREAS SHALL BE PREPARED ASRECOMMENDED BY EQUIPMENT SUPPLIER.
3. MARKINGS FOR BASKETBALL COURTS ER OFFICIAL GAMESTANDARDS AND REGULATIONS.
4. ALL NEW CONC. WALKS ARE TO HAVE A 5% MAX. SLOPE ANDA 2% MAX. CROSS SLOPE.
5. CURB RAMPS 8.3% MAX. SLOPE, 2% MAX. CROSS SLOPE,WITH 1/2" WIDE BY 1/8" DEEP GROOVES AT 2" O.C. EXTENDING THEFULL WIDTH OF THE RAMP AT AN ANGLE THAT WILL ALLOW WATERTO DRAIN FROM GROOVES. THE RAMP MUST ALSO BE OFCONTRASTING COLOR TO BE SELECTED BY THE ARCHITECT. FIELDVERIFY RISE TO SET RAMP DEPTH.
6. ALL JOINTS SHOWN ON WALKS ARE CONTROL JOINTS &EXPANSION JOINTS. CONTROL JOINTS AT 5'-0" O.C., AND EXPANSIONJOINTS @ 20'-0" O.C. UNLESS SHOWN OTHERWISE.
7. REFER TO CIVIL DRAWINGS FOR EXPANSION JOINTS,CONTROL JOINTS AND CONCRETE CURB CONSTRUCTION.
8. REFER TO CIVIL FOR ALL UTILITY LOCATIONS & EASEMENTS,AND GRADING.
9. REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF NEWLIGHTING FIXTURES AND CONDUITS.
10. LANDSCAPE ELEMENTS SHOWN ON PLAN INDICATEGENERAL LOCATION OF EXISTING TREE AND SHRUB PLANTINGS.
SITE PLANDE LLANO PARK
10 10' 20' 40' 80'
A1.1
Project NO.:
Date:
The
reco
rd o
f thi
s dr
awin
g is
on
file
at th
e of
fices
of S
lay
Arc
hite
ctur
e, 1
23 A
ltgel
t Ave
nue,
San
Ant
onio
, Tex
as 7
8201
& 9
901
McP
hers
on R
oad,
Sui
te 1
04, L
ared
o, T
exas
780
45. T
his
docu
men
t is
rele
ased
for
the
purp
ose
of r
efer
ence
, coo
rdin
atio
n, a
nd/o
f fac
ility
man
agem
ent u
nder
the
auth
ority
of t
he n
amed
pro
fess
iona
l, re
gist
ratio
n nu
mbe
r an
d da
te o
n th
e se
al a
ffixe
d ab
ove.
CO
PY
RIG
HT
2000
- 20
19, S
lay
Arc
hite
ctur
e. T
his
docu
men
t was
pre
pare
d us
ing
com
pute
r as
sist
ed d
esig
n an
d dr
aftin
g eq
uipm
ent a
nd s
aved
on
mag
netic
med
ia.
Nei
ther
the
prin
ted
docu
men
t nor
the
mag
netic
med
ia m
ay b
e al
tere
d or
am
ende
d by
any
par
ty o
ther
than
Sla
y A
rchi
tect
ure.
Revisions:
123 Altgelt Avenue
San Antonio, Texas 78201
T: 210.736.3009
9901 McPherson Avenue, #104
Laredo, Texas 78045
T: 956.791.0405
SAN ANTONIO
LAREDO
19005
CD
BG
D
E LLA
NO
P
AR
K IM
PR
OV
EM
EN
TS
P
RO
JE
CT
09/12/19
CIT
Y O
F LA
RE
DO
TE
XA
S
CO
NS
TRU
CTI
ON
DO
CU
ME
NTS
Fost
er A
venu
e an
d S
andm
an S
tree
t
09/12/19
EXTERIOR DOOR HEAD8
5/ A
2.0
4/ A2.0
3/ A2.0
2/ A2.0
6' - 8" 4' - 8" 6' - 8"
0"1' - 4" 3' - 4"
2' - 4" 4' - 0" 2' - 4"
3' - 4"
1' - 4"
19
' - 0
"
18' - 0"18' - 0"
SCREEN WALL SCREEN WALL
DRINKING FOUNTAIN
ROOF ABOVE
D102D101
6A2.0
4A2.1
6/ A
2.1
7/ A2.1
5/ A
2.1
18' - 0"
TOILET ROOM 1
TOILET ROOM 2
19
' - 0
"
CONCRETE SLAB RE: STRUCTURAL
123 1 2 3
6
4
7
8
9
10
11
6
4
7
8
10
11
1' - 3"
FD FD
0" F.F. 0" F.F.
ROOF11' - 4" A.F.F.
PL HT.8' - 0" A.F.F.
PL HT.8' - 0" A.F.F.
SCREEN WALL HT.6' - 0" A.F.F.
METAL ROOF OVER WOOD FRAME ROOF STRUCTURE
8X8X6 CMU SOLAR SCREEN DEC. BLK. W/
VENT SCREEN
8X8X16 REINFORCED SPLIT FACE CMU RE: STRUCT.
8X2X16 CMU CAP
7' -
2"
0" F.F.
PL HT.8' - 0" A.F.F.
METAL ROOF OVER WOOD FRAME ROOF STRUCTURE
8X8X6 CMU SOLAR SCREEN DECORATIVE BLOCK
8X8X16 REINFORCED SPLIT FACE CMU RE: STRUCT.
SCREEN WALL HT.6' - 0" A.F.F.
DRINKING FTN 8X2X16 CMU CAP
0" F.F.
PL HT.8' - 0" A.F.F.
METAL ROOF OVER WOOD FRAME ROOF STRUCTURE
CEMENT BOARD FASCIA & SOFFIT
DOOR RE: DOOR SCHED.
DRINKING FOUNTAINS
8X8X16 REINFORCED SPLIT FACE CMU RE: STRUCT.
0" F.F.
ROOF11' - 4" A.F.F.
METAL ROOF OVER WOOD FRAME ROOF STRUCTURE
8X8X6 CMU SOLAR SCREEN DEC. BLK. W/ VENT SCREEN
8X8X16 REINFORCED SPLIT FACE CMU RE: STRUCT.
7' -
2"
8X2X16 CMU CAP
VENTED CEMENT FIBER BRD SOFFIT
4'X8' FIBER CEMENT BEADED CEILING PANEL BUTT JOINT
0" F.F.
ROOF11' - 4" A.F.F.
PL HT.8' - 0" A.F.F.
SCREEN WALL HT.6' - 0" A.F.F.
A2.11
A2.12
METAL ROOF
REINFORCED SPLIT FACE CMU RE: STRUCTURAL8x8x6 CMU
SOLAR SCREEN DECORATIVE
BLOCK
RE: STRUCTURAL CONC. FOUNDATION
SMOKE DETECTOR
WALL MOUNTED LIGHT
WALL MOUNTED EXIT LIGHT
CEILING MOUNTED EXIT LIGHT
EMERGENCY LIGHT
FLUORESCENT LIGHT 2' X 4'
CEMENT FIBER CEILING PANEL
110 V GFI DUPLEX
SD
REFLECTED CEILING PLAN
GFI
TOILET ROOM ACCESSORIES
36" GRAB BARS
42" GRAB BARS
TOILET TISSUE DISPENSER
ELECTRIC HAND DRYER
NOT USED
SOAP DISPENSER
TODDLER RESTRAING CHAIR
ADULT CHANGING STATION
DRINKING FOUNTAIN
RE: SPECS
RE: SPECS
RE: SPECS
RE: SPECS
N/A
RE: SPECS
RE: SPECS
RE: SPECS
1
2
3
4
5
6
7
8
9
10
11
RE: SPECS
SIGNAGE RE: SPECS
COAT HOOK RE: SPECS
DOOR SCHEDULE
D101
3'-0" X 7'-0"H.M.H.M.H.M.PAINTNONE9/A2.012/A2.08/A2.02/A2.0RE: SPECS
NO.
SIZE:DOOR:FINISH:FRAME:FINISH:GLASS:HEAD:JAMB:SILL:ELEV:HARDWARE:REMARKS:
D102
3'-0" X 7'-0"H.M.H.M.H.M.PAINTNONE9/A2.012/A2.08/A2.02/A2.0RE: SPECS
NO.
SIZE:DOOR:FINISH:FRAME:FINISH:GLASS:HEAD:JAMB:SILL:ELEV:HARDWARE:REMARKS:
_______________________3A2.1
_______________________
1A
2.1
_____________
__________
2A
2.1
8'-0"
TOP OF CMU
11'-4"
TOP OF CMU
CMU WALL BELOW
METAL ROOF
OVERHANG TYP.1' - 0"
DOOR AS SCHED.
FRAME AS SCHED.
EXTRUDED ALUM. THRESHOLD SET IN A FULL BED OF MASTIC
FLOORING AS SCHED.
INTEXT
2% SLOPE
PARTITION AS SCHEDULED OR MATCH EXISTING
REINFORCED LINTEL
VOID FILLED WITH GROUT
CONT. SEALANT, BOTH SIDES
HOLLOW METAL FRAME, PAINT
DOOR AS SCHEDULED
DRIP CAP
DOOR AS SCHED.
FRAME ANCHOR
SEALANT & BACKER ROD, BOTH SIDES
HOLLOW METAL FRAME - PAINT FILL WITH GROUT
HORIZ. JOINT REINF.
PARTITION AS SCHEDULED OR
MATCH EXISTING
REINFORCED CELL RE: STRUCTURAL
FOUR POST HIP SHADE STRUCTURE AND PIER FOOTINGS BY VENDOR
10
' - 0
"
40' - 0"40' - 0"
Project NO.:
Date:
Th
e r
eco
rd o
f th
is d
raw
ing
is
on
file
at
the o
ffic
es
of S
lay A
rch
itectu
re,
123 A
ltg
elt A
ven
ue,
San
An
ton
io,
Texa
s 7820
1 &
99
01 M
cP
he
rso
n A
ven
ue,
Su
ite
10
4,
Lare
do
, T
exa
s 7
8045
. T
his
do
cu
men
t is
re
leased
fo
r th
e p
urp
ose
of
refe
ren
ce,
co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the a
uth
ori
ty o
f th
e n
am
ed
pro
fess
ion
al, r
eg
istr
atio
n n
um
be
r an
d d
ate
on
th
e s
ea
l affix
ed
ab
ove
. C
OP
YR
IGH
T 2
000 -
, S
lay A
rch
ite
ctu
re.
Th
is d
ocu
me
nt
wa
s p
rep
are
d u
sin
g c
om
pu
ter
ass
iste
d d
esi
gn
an
d d
raftin
g e
qu
ipm
en
t an
d s
ave
d o
n m
ag
netic m
ed
ia.
Neith
er
the p
rin
ted
do
cu
me
nt
no
r th
e m
ag
netic m
ed
ia m
ay b
e a
ltere
d o
r am
en
ded
by a
ny p
art
y o
ther
than
Sla
y A
rch
ite
ctu
re.
Revisions:
123 Altgelt Avenue
San Antonio, Texas
78201
9901 McPherson Avenue, #
104
Laredo, Texas 78045
SAN ANTONIO
LAREDO
A2.0TOILET ROOM DETAILS
19005
CD
BG
DE
LLA
NO
PA
RK
IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/2019
FIN
AL S
ET
2019
1/4" = 1'-0"1 TOILET ROOMS
FLOOR PLAN
1/4" = 1'-0"
5 @ TOILET ROOMS SIDE WALL
EXTERIOR ELEVATION
1/4" = 1'-0"
3 @ TOILET ROOMS FRONTWALL
EXTERIOR ELEVATION
1/4" = 1'-0"2 @ TOILET ROOM ENTRY
EXTERIOR ELEVATION
1/4" = 1'-0"
4 @ TOILET ROOMS REAR WALL
EXTERIOR ELEVATION
1/4" = 1'-0"10REFLECTED CEILING PLAN
1/4" = 1'-0"6BUILDING SECTION
1/4" = 1'-0"7ROOF PLAN
8 N.T.S.
THRESHOLD @ DOORS
1 1/2" = 1'-0"9DOOR HEAD
1 1/2" = 1'-0"12DOOR JAMB
1/8" = 1'-0"11SHADE STRUCTURE
CD
BG
D
E LLA
NO
P
AR
K IM
P
CIT
Y O
F LA
RE
DO
TE
XA
S
Fost
er A
venu
e an
d S
andm
an S
tree
t
09/12/19
FOIL FACED ROOF DECK
ROOF UNDERLAYMENT
METAL ROOF
METAL ROOF FLASHING
10" FIBER CEMENT FASCIA BRD
VENTED FIBER CEMENT BRD SOFFIT PANEL
3" FIBER CEMENT TRIM
REINF. SPLIT FACE CMU RE: STRUCT.
BATT INSULATION
FIBER CEMENT BEADED CEILING PANELS
3" FIBER CEMENT TRIM
CMU BOND BEAM W/REINFORCED RE: STRUCTURAL
RE: STRUCTURAL
O.H.
1' - 0"
2X10
1" NAILER
FOIL FACED ROOF DECK RE: STRUCTURAL
ROOF UNDERLAYMENT METAL ROOF
METAL ROOF FLASHING
BATT INSULATION
CEMENT FIBER BRD BEADED CLG
PANELS
3" CEMENT FIBER BRD TRIM
8X8X6 CMU SOLAR SCREEN DECORATIVE BLOCK
CMU REINFORCED BOND BEAM RE: STRUCTURAL
VENTED CEMENT FIBER BRD SOFFIT
10" CEMENT FIBER BRD FASCIA
3" FIBER CEMENT TRIM
METAL SCREEN
RE: STRUCTURAL
O.H.
1' - 0"
2X10
1" NAILER
FOIL FACED ROOF DECK
ROOF UNDERLAYMENT
METAL ROOF
CEMENT FIBER BRD FASCIA
VENTED CEMENT FIBER BRD SOFFIT
3" CEMENT FIBER BRD TRIM
8X8X6 CMU SOLAR SCREEN DECORATIVE BLOCK
3" CEMENT FIBER TRIM
BATT INSULATION
METAL ROOF FLASHING
SCRENN MESH METAL FRAME
2X10
2x10 PLATE
8X2X16 CMU CAP
8X2X16 CMU CAP
O.H.
1' - 0"
SCREEN MESH METAL. FRAME
1" NAIILER
FIBER CEMENT BEADED CEILING PANELS
0" F.F.
2' -
10
"
3' -
0"
CMU SEAL AND PAINT
TILE 4"X8"
6"X6" COVE BASEWA
INS
CO
T
6' -
8"
TILE 4"X8" BULLNOSE
8X8X6 CMU SOLAR SCREEN DEC. BLK W/ VENT SCREEN
8X2X16 CMU CAP
7' -
2"
0" F.F.
2' -
2"
MAX
MAX
MIN
3' -
0"
CMU SEAL & PAINT
TILE 4"X8"
6"X6" COVE BASE
WA
INS
CO
T
6' -
8"
TILE 4"X8" BULLNOSE
8X8X6 CMU SOLAR SCREEN DEC. BLK. W/ VENT SCREEN
7' -
2"
8x2x16 CMU CAP
0" F.F.
3' - 0" 6"
2' -
9"
2' -
3"
CMU SEAL & PAINT
TILE 4"X8"
6"X6" COVE BASE
WA
INS
CO
T
6' -
8"
TILE 4"X8" BULLNOSE
8X8X6 CMU SOLAR SCREEN DEC. BLK. W/ VENT SCREEN
8X2X16 CMU CAP
7' -
2"
0" F.F.
A2.13
WA
INS
CO
T F
INIS
H
6' -
8"REINF. SPLIT FACED
CMU RE: STRUCTURAL
STRUCTURAL FOUNDATION
WALL & FLOOR TILE RE: FINISH SCHEDULE
Project NO.:
Date:
Th
e r
eco
rd o
f th
is d
raw
ing
is
on
file
at
the o
ffic
es
of S
lay A
rch
itectu
re,
123 A
ltg
elt A
ven
ue,
San
An
ton
io,
Texa
s 7820
1 &
99
01 M
cP
he
rso
n A
ven
ue,
Su
ite
10
4,
Lare
do
, T
exa
s 7
8045
. T
his
do
cu
men
t is
re
leased
fo
r th
e p
urp
ose
of
refe
ren
ce,
co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the a
uth
ori
ty o
f th
e n
am
ed
pro
fess
ion
al, r
eg
istr
atio
n n
um
be
r an
d d
ate
on
th
e s
ea
l affix
ed
ab
ove
. C
OP
YR
IGH
T 2
000 -
, S
lay A
rch
ite
ctu
re.
Th
is d
ocu
me
nt
wa
s p
rep
are
d u
sin
g c
om
pu
ter
ass
iste
d d
esi
gn
an
d d
raftin
g e
qu
ipm
en
t an
d s
ave
d o
n m
ag
netic m
ed
ia.
Neith
er
the p
rin
ted
do
cu
me
nt
no
r th
e m
ag
netic m
ed
ia m
ay b
e a
ltere
d o
r am
en
ded
by a
ny p
art
y o
ther
than
Sla
y A
rch
ite
ctu
re.
Revisions:
123 Altgelt Avenue
San Antonio, Texas
78201
9901 McPherson Avenue, #
104
Laredo, Texas 78045
SAN ANTONIO
LAREDO
A2.1TOILET ROOM DETAILS
19005
CD
BG
DE
LLA
NO
PA
RK
IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/2019
FIN
AL S
ET
2019
ROOM FINISH SCHEDULE
NO.
ROOMNAME FLOOR BASE
WALL FINISH
CEILING REMARKSNORTH SOUTH EAST WEST
1 TOILET ROOM 1 TILE TILE TILE / PAINT TILE / PAINT TILE / PAINT TILE / PAINT PAINT CEMENT FIBERBRD
TILE WAINSCOT HT @ 6'-8"
2 TOILET ROOM 2 TILE TILE TILE / PAINT TILE / PAINT TILE / PAINT TILE / PAINT PAINT CEMENT FIBERBRD
TILE WAINSCOT HT @ 6'-8"
1 1/2" =1'-0"
1 @ EAVE
ROOF DETAIL
1 1/2" =1'-0"
2 @ RIDGE
ROOF DETAIL
1 1/2" =1'-0"
3 @ RAKE
TYPICAL ROOF DETAL 1/4" = 1'-0"5Elevation 3 - a
1/4" = 1'-0"7Elevation 2 - a
1/4" = 1'-0"6Elevation 1 - a
3/4" = 1'-0"4WALL SECTION
CD
BG
D
E LLA
NO
P
AR
K IM
P
CIT
Y O
F LA
RE
DO
TE
XA
S
Fost
er A
venu
e an
d S
andm
an S
tree
t
09/12/19
1000 COORDINATION
A. The Contractor shall compare the Architectural, Structural, Mechanical, Electrical, Plumbing, and other series drawings and report any discrepancies between each set of drawings and within each set of drawings prior to fabrication and installation of any structural members.
B. Only larger sleeve openings and framed openings in structural framing component members are indicated on the Structural Drawings. However, all sleeves, inserts and openings, including frames and/or sleeves shall be provided for passage, provision and/or incorporation of the work of the contract, including but not limited to Mechanical, Electrical and Plumbing work. This work shall include the coordination of sizes, alignment, dimensions, position, locations, elevations and grades as required to serve the intended purpose. Openings not indicated on the Structural Drawings, but required as noted above, shall be submitted to the Engineer for review.
C. Refer to Architectural, Mechanical, Electrical and Plumbing drawings for floor elevations, slopes, drains and location of depressed and elevated floor areas.
D. Compatibility of the structure and provisions for building equipment supported on or from structural components shall be verified as to size, dimensions, clearances, accessibility, weights and reaction with the equipment for which the structure has been designed prior to submission of shop drawings and data for each piece of equipment and for structural components. Differences shall be noted on the submittals.
E. Shop drawings shall be prepared for all structural items and submitted for review by the Engineer. Structural Drawings shall not be reproduced and used as shop drawings. All items deviating from the Structural Drawings or from previously submitted shop drawings shall be clouded.
F. The details designated as "Typical Details" apply generally to the Structural Drawings in all areas where conditions are similar to those described in the details.
G. All dimensions and conditions of existing construction shall be verified at the job site prior to the preparation of shop drawings. Differences between existing construction and that shown on the Structural Drawings shall be referred to the Architect. Differences shall also be clouded on the shop drawings.
H. All structural elements of the project have been designed by the Engineer to resist the required Code vertical and lateral forces that could occur in the final completed structure only. It is the responsibility of the Contractor to provide all required bracing during construction to maintain the stability and safety of all structural elements during the construction process until the lateral-load resisting or stability-providing system is completely installed and the structure is completely tied together. Temporary supports shall not result in the overstress or damage of the elements to be braced nor any elements used as brace supports.
I. The Contract Structural Drawings and Specifications represent the finished structure, and except where specifically shown do not indicate the means or methods of construction. The Contractor and their Sub-Contractors shall supervise and direct the Work and shall be solely responsible for all construction means, methods, procedures, techniques, sequences and safety measures including, but not limited to, adherences to all OSHA guidelines. The Engineer shall not have control of, and shall not be responsible for, construction means, methods, techniques, sequences or procedures, for safety precautions and programs in connection with the Work, for the acts or omissions of the Contractor, Subcontractors, or any other person performing any of the Work, or for the failure of any of these persons to carry out the Work in accordance with the Structural Contract Documents.
J. Where conflict exists among the various parts of the Structural Contract Documents, Structural Drawings, General Notes, and Specifications, the strictest requirements, as indicated by the Engineer, shall govern.
K. Periodic site observation by field representatives of Intelligent Engineering Services, LLP (IES) is solely for the purpose of determining if the Work is proceeding in accordance with the Structural Contract Documents. This limited site observation is not intended to be a check of the quality or quantity of the Work, but rather a periodic check in an effort to inform the Owner against defects and deficiencies in the work of the Contractor.
1010 SUBSTITUTIONS
A. All requests for substitutions of materials or details shown in the Structural Contract Documents shall be submitted for approval during the bidding period.
B. Once bids are accepted, proposed substitutions will be considered only when they are officially submitted with an identified savings or duration to be deducted from the contract and/or schedule impact. Submittals not satisfying the above criteria will not be reviewed.
1020 CODES
A. The General Building Code used as the basis for the structural design is as follows:
2012 International Building Code as adipted by the City of Laredo
1030 IBC 2012 DESIGN LOADS
A. Live Loads
OCCUPANCY OR USE UNIFORM CONCENTRATED (psf) (lbs.)
Restrooms 60 2000Roof - See Section Design Loads Note B
B. Roof Live LoadsROOF USE ROOF LIVE LOAD
UNIFORM CONCENTRATEDOrdinary Flat, Pitched, and Curved Roofs 20 psf N/AAll Other Construction 20 psf N/A
Notes:
1. Concentrated load applied to skeleton structure.2. Concentrated load applied to supporting roof frame members only.3. Roof live load has been reduced according to the General Building Code using the formula:
Lr = Lo x R1 x R2
Where Lr = Reduced live load per square foot of horizontal projection supported by the member.
LO = Unreduced design of roof live load per square foot of horizontal projection supported by the member.
R1 = Reduction factor based on Tributary AreaR2 = Reduction factor based in Roof Slope
C. Wind Loads
1. Wind lateral load on structural frame is based on ASCE 7 using the following:
Ultimate Design Wind Speed (Vult) 115 mphNominal Design Wind Speed (Vasd) 90 mphExposure Category CInternal Pressure Coefficient, GCpi +/-0.18Risk Category II
D. Load Combinations
1. Strength Design a. 1.4(D+F)b. 1.2(D+F) + 1.6(L+H) + 0.5(Lr or S or R)c. 1.2(D+F) + 1.6(Lr or S or R) + 1.6H + (f1L or 0.5W)d. 1.2(D+F) + 1.0W + f1L + 1.6H + 0.5(Lr or S or R)e. 1.2(D+F) + 1.0E + f1L + 1.6H + f2Sf. 0.9D + 1.0W + 1.6Hg. 0.9(D+F) + 1.0E + 1.6H
f1 = 1.0 for places of public assembly live loads in excess of 100 pounds per square foot and parking garages; and 0.5 for other live loads.f2 = 0.7 for roof configurations (such as saw tooth) that do not shed snow off the structure; and 0.2 for other roof configurations.
2. Allowable Stress Design:a. D + Fb. D + H + F + Lc. D + H + F + (Lr or S or R)d. D + H + F + 0.75L + 0.75(Lr or S or R)e. D + H + F + (0.6W or 0.7E)f. D + H + F +0.75(0.6W) + 0.75L + 0.75(Lr or S or R)g. D + H + F +0.75(0.7E) + 0.75L + 0.75Sh. 0.6D + 0.6W + Hi. 0.6(D+F) + 0.7E + H
1100 SUBMITTALS
A. Shop drawings shall be prepared for all structural items and submitted for review by the Engineer. Structural Drawings shall not be reproduced and used as shop drawings. All items deviating from the Structural Drawings or from previously submitted shop drawings shall be clouded.
B. Contractor shall review shop drawings for compliance with the Structural Drawings and shall certify that they have done so by a stamp noting that the drawings have been "Approved" and which bears the signature (or initials) of an authorized representative of the Contractor and the date. Submittals which do not reflect the Contractor's approval, signature and date will be returned without review.
C. Contractor shall be responsible for delays caused by rejection of inadequate shop drawings.
D. where review and return of shop drawings is required or requested, the Engineer will review each submittal and, where possible, return within two weeks of receipt.
E. Corrections or comments on shop drawings or manufacturer's data sheets do not relieve the Contractor from compliance with requirements of the plans and specifications. Engineer's review is for general conformance with the requirements of the Structural Drawings. Contractor is responsible for confirming and correcting all quantities and dimensions, selecting fabrication processes and techniques of construction, and coordinating the work with that of all other contractors.
F. Refer to individual sections for specific submittal requirements.
G. Contractor shall submit electronically in pdf format. Submittals shall be generated electronically and will be commented upon electronically as to maintain clarity of the image file. Scans of hard copy submittals shall be legible, full size scans. All illegible scans or scans of contractor comments on reduced size prints will be rejected. Contractor will be responsible for providing and distributing Engineer’s comments to their subcontractors.
2315 BUILDING PAD PREPARATION:
A. The building area should be stripped of all organic topsoil and/or vegetation up to a minimum of 3 feet laterally beyond the limits of the proposed building and pavement areas.
B. The area of construciton should be initially graded to provide a relatively level surface to receive fill and to provide for a relatively uniform thickness of fill beneath the building structure. Areas requiring fill where existing slopes are steeper than 5:1 (horizontal to vertical) shall be benched to reduce the potential for slippage between existing slopes and fills. Benches should be wide enough to accomodate compaction and earth moving equipment and to allow placement of horizontal lifts of fill.
C. Exposed grades should be thoroughly proofrolled in an effort to solidify any potentially compressible areas that may be isolated. Compresible areas encountered during proof-rolling should be overexcavated and backfilled with materials placed in accordance with the recommendations outlined in the Geotechnical Report. A heavily loaded piece of construction equipment should be used for the proofrolling procedures. A representative of the Geotechnical Engineer shall be retained to observe the proofrolling procedures carried out in the field for documentation and quality control of the subgrade.
D. Following the proofrolling activities, the exposed subgrade shall be scarified rto a minimum depth of 6 inches (mositure conditioning) and re-compacted. The mositure content of the subgrade should be maintained wihtin the range of optimum to plus 3 percentage points of optimum until permanently covered.
E. Structural fill shall be used in alla reas requiring raising above the balanced site elevation. Structural fill material shall consist of material conforming to TxDOT 2014 Standard Specifications for Cosntruction of Highways, Streets and Bridges, Item 247, Flexible Base, Tyoes A, B, or C, Grades 1-2 through 5.
F. Structural fill shall be placed in loose horizontal lifts of approximatley 6 inches but not exceeding 8 inches in thickness. The water content of the fill should be maintained within the range of optimum to 2 percentage points above the optimum water content until the fill is permanently covered. Compaction criteria for engineered fill is as follows:
G. Provide a vapor retarder that conforms to ASTM E1745, Class A or better with a maximum water vapor permeance of 0.03 (0.01) perms per ASTM E154. Vapor retarder shall be no less than 10 mils thick.
H. Building pad preparation information is based on a geotechnical report provided by O'Connor Engineering & Science, Inc. dated July 2, 2019, OES Project No. OES-G776003-01.
3000 CAST-IN-PLACE CONCRETE
A. Structural Concrete Code: Building Code Requirements for Structural Concrete, American Concrete Institute, ACI 318, as referenced by the General Building Code.
B. Classes of Concrete
1. All concrete shall conform to the requirements as specified in the table below, unless noted otherwise on the Structural Drawings:
2. Concrete Mix Schedule:
Conc Strength Agg Max Agg Slump MaxClass psi Type Size Inches w/c Notes A 2500 NWT 1/2" 2-4 --- PP Fibers B 3000 NWT 1-1/2" 5-7 0.55 C 3000 NWT 1" 3-5 0.55 D 3000 NWT 3/4" 3-5 ---
a. NWT" refers to normal concrete having an dry unit weight of approximately 145 pcf (ASTM c33 AGGREGATE)
b. "LWC" refers to sand lightweight concrete having an airdry unit weight not to exceed 120 PCF (ASTM C330 aggregate)
c. Where the w/c ratio is not indicated in the Concrete Mix Schedule, it shall be as necessary to meet strength requirements.
d. Where the w/c ratio is shown, it shall be adhered to regardless of thestrength requirements.
e. Strength" is required compressive cylinder strength at an age of 28 days.f. "Maximum aggregate size" is defined as first sieve with greater than 15 cumulative
percent retained.
3. Mix Usage Schedule:
Concrete AirDescription of Use Class Content
Grade Beams C 3 - 6%Interior Slab-on-Grade C 3 - 6%
C. Provide 4 1/2 percent plus or minus 1 1/2 percent of entrained air in concrete permanently exposed to the weather and elsewhere at the contractor’s option.
D. Horizontal construction joints in concrete placements shall be permitted only where indicated on the Structural Drawings. All vertical construction joints shall be made in the center of spans in accordance with the typical details. Contractor shall submit proposed locations for construction joints not shown on the Structural Drawings for review by the Architect and Engineer. Additional construction joints may require additional reinforcing as specified by the Engineer which shall be provided by the contractor at no additional cost to the owner.
E. Embedded conduits, pipes, and sleeves shall meet the requirements of ACI 318, and the following:
1. Conduits and pipes running within a slab, beam, or wall shall not be larger in outside dimension than 1/3 the overall thickness of the slab, wall or beam and shall be located within the middle third of that thickness.
2. Conduits, pipes, and sleeves passing horizontally through a beam shall not be larger in outside dimension than 1/3 the overall depth of the beam and shall be located within the middle third of that depth.
3. Conduits, pipes, and sleeves passing vertically through a beam shall utilize a sleeve not larger in outside dimension than 1/3 the overall width of the beam or 6 inches (whichever is less). The sleeve shall be made of hot dip galvanized schedule 40 steel.
4. Conduits, pipes and sleeves shall not be spaced closer than three diameters or widths on center.
F. Concrete placements shall not exceed 10,000 square feet or 100 linear feet on each side without prior approval by the Engineer for each placement.
G. Concrete sampling for quality assurance: Concrete that is pumped shall be sampled at the point of discharge from the truck for information, including slump; and shall be sampled at the point of placement for acceptance of slump and air content.
H. Submittal: Submit proposed mix designs in accordance with ACI 301, chapter 4.2.3. Each proposed mix design shall be accompanied by a record of past performance or by three laboratory trial mixtures with confirmation tests.
AGUSTIN TELLEZ, JR.
79341
10001 REUNION PLACE, SUITE 200
210.349.9098
SAN ANTONIO, TEXAS 78216
TBPE FIRM F-432IES JOB NO:
ENGINEERING COMMUNITIES FROM THE GROUND UP
ie-services.com
Th
e r
eco
rd o
f th
is d
raw
ing
is o
n file
at
the
offic
es o
f S
lay A
rch
itectu
re,
12
3 A
ltg
elt A
ve
nu
e,
San
An
ton
io, T
exa
s 7
82
01
& 9
90
1 M
cP
he
rso
n R
oa
d,
Su
ite 1
04,
La
red
o,
Te
xas 7
80
45.
Th
is d
ocu
me
nt
is r
ele
ased
fo
r th
e p
urp
ose
of re
fere
nce
, co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the
au
tho
rity
of th
e n
am
ed
pro
fessio
na
l, r
eg
istr
atio
n n
um
be
r a
nd
date
on
th
e s
ea
l a
ffix
ed
ab
ove
.C
OP
YR
IGH
T 2
00
0 -
20
19
, S
lay A
rch
ite
ctu
re. T
his
do
cu
men
t w
as p
rep
are
d u
sin
g c
om
pu
ter
assis
ted
desig
n a
nd
dra
ftin
g e
qu
ipm
en
t a
nd
sa
ved
on
mag
netic m
ed
ia.
Ne
ith
er
the
prin
ted
do
cu
men
t n
or
the
ma
gn
etic m
ed
ia m
ay b
e a
ltere
d o
r am
en
de
d b
y a
ny p
art
y o
the
r th
an
Sla
y A
rch
ite
ctu
re.
123 Altgelt AvenueSan Antonio, Texas 78201T: 210.736.3009
9901 McPherson Avenue, #104Laredo, Texas 78045T: 956.791.0405
SAN ANTONIO
LAREDO
Project NO.:
Date:
Revisions:
19005
CD
BG
DE
LL
AN
O P
AR
K IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/19
CIT
Y O
F L
AR
ED
O T
EX
AS
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1192756
September 12, 2019
Fo
ste
r A
ven
ue a
nd
San
ma
n S
tre
et
9/1
0/2
019
5:3
4:4
0 A
M
S0.1
STRUCTURAL NOTES
S T R U C T U R A L N O T E S
3200 CONCRETE REINFORCING
A. Concrete reinforcement for the project shall conform to the following:
1. All reinforcing steel shall be new billet steel in accordance ASTM A615, Grade 60, unless noted otherwise in the Structural Drawings or these notes.
2. Deformed Bar Anchors. ASTM A1064 minimum yield strength 70,000 psi as noted on the Structural Drawings. Reinforcing bars shall not be substituted for deformed bar anchors.
3. Welded wire reinforcement. Welded smooth wire reinforcement, ASTM A1064, yield strength 65,000 psi where noted on the Structural Drawings. Welded deformed wire reinforcement, ASTM A497, yield strength 70,000 psi where noted on the Structural Drawings. Welded wire reinforcement to be provided in flat sheets.
B. Detailing of reinforcing steel shall conform to the American Concrete Institute 315 Detailing Manual and all hooks and bends in reinforcing bars shall conform to ACI detailing standards, unless noted otherwise on the Structural Drawings.
C. Welded Wire Reinforcement shall be continuous across the entire concrete surface and not interrupted by beams or girders and properly lapped one cross wire spacing plus 2”.
D. In unscheduled grade beams, walls, and slabs, detail reinforcing as follows:
1. Class A lap beam top reinforcing bars at mid span.
2. Class A lap beam bottom reinforcing bars at the supports.
3. Provide Class B lap at other location pending Engineer’s approval.
4. Provide standard hooks in top bars at cantilever and discontinuous ends of beams, walls and slabs.
5. Provide corner bars for all horizontal bars at the inside and outside faces of intersecting beams or walls. Corner bars are not required if horizontal bars are hooked.
6. Provide 2-#4 diagonal bars at all slab re-entrant corners placed under the top mat of steel.
E. Welding of reinforcing steel will not be permitted unless specifically shown on the Structural Drawings.
F. Heat shall not be used in the fabrication or installation of reinforcement.
G. Reinforcing steel clear cover shall be as follows:
1. Earth-formed Grade Beams 1-1/2" top, 3" sides, 3" bottom2. Formed Grade Beams 1-1/2" top, 2" sides, 3" bottom 3. Slab-on-grade 2" top
Exterior Exposure refers to concrete exposed to earth or weather
H. Submittal: Submit shop drawings for fabrication, bending, and placement of concrete reinforcement. Comply with ACI 315 "Details and Detailing of Concrete Reinforcement". Do not reproduce the Structural Drawings for use as shop drawings.
4800 STRUCTURAL MASONRY
A. Concrete Masonry: Building Code Requirements for Masonry Structures, American Concrete Institute, ACI 530 & 530.1, as referenced by the General Building Code.
B. Minimum compressive strength of the masonry (f'm) shall be 1,500 pounds per square inch.
C. Mortar shall conform to ASTM C270, Type S. Masonry cement shall not be used.
D. Concrete masonry units shall be hollow load bearing units which conform to ASTM C90, with a minimum net compressive strength as follows:f'm Net area Compressive Strength
(psi) of CMU Block (psi)1500 19002000 28002500 37503000 4800
E. Chases shall be built in and not cut in. Chases shall be plumb and shall be minimum one-unit length from jambs of openings. Anchors, wall plugs, accessories and other items to be built in shall be installed as the masonry work progresses. All cutting and fitting of masonry, including that required to accommodate the work of other sections shall be done by masons with masonry saws.
F. Coarse grout shall conform to ASTM C476, with a maximum aggregate size of 1/2" and a minimum compressive strength equal to the specified minimum compressive strength, f’m, but not less than 2000 psi. Course grout shall be placed in accordance with ACI 530.1 Section 3.5.
G. Reinforce concrete masonry unit joints with ladder type hot dip galvanized cold-drawn steel conforming to ANSI/ASTM A82, with [W1.7 or W2.8] side rods with W1.7 cross rods.
1. Space joint reinforcing at 16 inches o.c. unless noted otherwise.
2. Lap joint reinforcing 14 inches at splices.
3. Provide prefabricated joint reinforcing corner pieces at all wall corners and intersections.
4. Joint reinforcing shall be discontinuous at control and expansion joints.
H. Lap reinforcing bars in grouted masonry as noted below. Splices in reinforcing shall be staggered so that not more than 1/2 of all bars are spliced at the same location.
I. Z-ties shall be provided in all masonry surfaces used as a form for grout at 16 inches on center each way in vertical masonry surfaces and at 8 inches on center each way in horizontal masonry surfaces. The leg embedded in the masonry joint shall have its hook placed 3/4 inch from the outside face of the masonry.
J. Z-ties shall be manufactured from 3/16 inch diameter cold drawn wire. Ties shall be hot dip galvanized, 6 inches long with a 2 inches hook at each end, unless noted otherwise on the Structural Drawings.
K. Provide 1 inch clear cover between ties or longitudinal reinforcing and the inside face of masonry used as forms in grouted beams, pilasters and columns.
5050 POST-INSTALLED ANCHORS AND DOWELS
A. Expansion Anchors shall be one of the following:
1. Concrete:
a. Kwik Bolt TZ, Hilti Inc.b. Strong Bolt, Simpson Strong-Tiec. Power-Stud+ SD1, DeWalt (Powers)
2. Grouted Masonry
a. Kwik Bolt 3, Hilti Inc.b. Wedge-All, Simpson Strong-Tiec. Power-Stud+ SD1, DeWalt (Powers)
B. Screw Anchors shall be one of the following:
1. Concrete:
a. Kwik HUS-EZ, Hilti Inc.b. Titen HD, Simpson Strong-Tiec. Wedge-Bolt+, DeWalt (Powers)
2. Grouted Masonry
a. Kwik HUS-EZ, Hilti Inc.b. Titen HD, Simpson Strong-Tiec. Wedge-Bolt+, DeWalt (Powers)
C. Adhesive Anchors shall be one of the following:
1. Concrete:
a. HIT-RE 500-V3, Hilti Inc.b. HIT-HY 200, Hilti inc.c. Pure 110+, DeWalt (Powers)d. AC200+, DeWalt (Powers)e. SET 3G, Simpson Strong-Tie.
2. Grouted Masonry
a. HIT-HY 270, Hilti Inc.b. SET, Simpson Strong-Tie.c. AC100+ Gold, DeWalt (Powers)
D. Adhesive Doweling
1. Adhesive doweling system shall be one of the following products:
a. HIT RE 500-V3, Hilti Inc.b. Pure 110+, DeWalt (Powers)c. AC200+, DeWalt (Powers)d. SET 3G, Simpson Strong-Tie.
E. Install dowels in strict accordance with the adhesive manufacturer's instructions.
F. Clean out holes with compressed air after drilling per manufacturer's printed installation instructions or use manufacturer's alternate hole cleaning procedures.
G. Unless noted otherwise on the structural drawings, embedment depth shall be as required to develop full yield strength of the embedded dowels.
H. Prior to drilling holes for dowels, locate existing reinforcing steel with a Pachometer (R-Meter) or by drilling 1/4 inch diameter pilot holes. Relocate bolt holes as required to avoid existing reinforcement.
I. Anchors and dowels of the size and embedment shown on the Drawings shall be installed in accordance with the Contract Documents, the manufacturer's recommendations, and the manufacturer's current ICC ES report for the anchor. If conflicts exist between these referenced documents, the most stringent requirements shall govern.
J. The Contractor shall locate all existing reinforcing steel and other embedded items contained in the concrete using non-destructive methods and shall position anchor locations to avoid conflicts with existing embedded items. Anchor locations can be adjusted by a maximum of 1 1/2 inch from detailed locations to avoid conflicts, unless noted otherwise. Submit an as-built of anchor locations to engineer.
K. Based on field verified locations of reinforcing steel and embedded items, the Contractor shall create templates for each anchor group. Submit template dimensions for review prior to fabrication of connection plates.
L. Holes for anchors and dowels shall be drilled in a continuous operation using the bit type and size recommended by the anchor manufacturer. Diamond cored holes shall not be used unless noted otherwise on the structural drawings. Holes shall be drilled perpendicular to the concrete surface and shall not be enlarged or redirected at any point along its length. All debris shall be blown out of the holes with compressed air after drilling.
M. All abandoned holes shall be filled with non-shrink grout.
N. Holes in connection plates shall be no more than 1/16 inch larger than the anchor diameter. If larger holes are required for erection purposes, Contractor shall notify Engineer such that a plate washer size can be provided.
O. Installation of anchors and dowels shall be continuously inspected by the testing agency to ensure that holes are of specified size, and that bolts are properly installed including application of minimum installation torques.
6100 TIMBER FRAMING
A. Structural Wood Framing and Sheathing: National Design Specifications for Wood Construction with Supplement, American Forest and Paper Association, AF&PA NDS as referenced by the General Building Code.
B. Unless noted otherwise on the Structural Drawings, all structural framing lumber shall be clearly marked No. 2 Southern yellow pine or Douglas fir.
C. Wood Preservative Treated Lumber (Pressure Treated):
1. Preservative Treated Lumber shall be Southern Yellow Pine and shall be treated as described below.
2. Preservative Treatment by Pressure Process should be performed according to the AWPA methods described below. The preservative chemicals shall be waterborne and can include Alkaline Copper Quat (ACQ-C, ACQ-D) and Copper Azole (CBA-C & CA-B) for interior or exterior uses and Inorganic Boron (SBX) for interior use only. Preservative shall not contain arsenic or chromium and shall not contain ammonia carriers.
3. Wood Installed for above ground use shall be preservative treated using water-borne preservatives in accordance with AWPA U2, use category UC3B. The locations to be treated are as follows:
a. Wood joists or wood floor without joists are closer than 18 inches or wood girders are closer than 12 inches to the exposed ground in crawl space.
b. Wood Framing members including wood sheathing which rest on exterior foundation walls and are less than 8inches from the exposed earth.
c. Wood framing members or furring strips attached directly to the interior of exterior or concrete walls below grade.
d. Wood sleepers and sill plates on concrete or masonry slab that is in direct contact with earth.
e. Wood Girder ends supported by exterior masonry or concrete walls unless 1/2 inch airspace is provided on top, sides, and end.
f. Wood Siding closer than 6 inches to earth.g. Posts or columns supported directly on a footing unless separated by
an impervious moisture barrier and a minimum 6 inches above grade and 1 inch above slab where a slab exists or 8 inches above earth on a concrete pier where no slab exists.
h. Portions of Glued-laminated timbers exposed to weather.
4. Wood in contact with Ground (exposed earth) or fresh water shall be preservative treated using water-borne preservatives in accordance with AWPA U1, with use category UC4C.
5. Wood member that form supports of buildings, balconies, porches, or similar permanent building appurtenances where such members are exposed to the weather without adequate protection from the roof, eave, overhang, etc. to prevent water accumulation on the surface or between joints shall be preservative treated using water-borne preservatives in accordance with AWPA U1 with use category UC3A.
6. Other wood members noted in the drawings shall be preservative treated using water-borne preservatives in accordance with AWPA U1 with use category UC3A.
D. All wood headers, beams, and top plates shall be no. 2 Southern Yellow Pine or Douglas Fir.
E. Roof sheathing: 1/2" APA rated sheathing with an exposure 1 rating (or) 1/2" grade C-D plywood with exterior glue. Panels shall be continuous over two or more spans with the long dimension oriented perpendicular to the framing members. Nail with 8d common nails at 6" on center at supported edges and 12" on center at intermediate supports. Stagger joints in sheathing.
F. Solid 2x blocking or bandboard shall be provided at supports and cantilever
ends of all wood joists, and between supports in rows not exceeding 4'-0" apart.
G. All framing members framing into the side of a header shall be attached using metal joist hangers of type “LU” as manufactured by the Simpson Company or equal. The hanger shall be sized and installed in accordance with the manufacturer’s recommendations for the size of joist supported.
H. Nailing and attachment of all framing members and sheathing shall be as specified in the International Building Code Fastening Schedule unless noted otherwise on the Structural Drawings. Common wire nails or spikes, or galvanized box nails shall be used for all framing unless noted otherwise on the Structural Drawings.
I. Sill plates shall be bolted with 1/2" diameter ASTM F1554 anchor rods with a minimum embedment of 6" spaced at 2'-0" on center with a minimum of two bolts per plate segment.
J. Simpson Strong Tie steel connectors in contact with Pressure Treated Lumber shall the following composition/ finish:
Type of Preservative/Usage Retention Level Simpson FinishInterior SBX/DOT G90
Interior/Exterior ACQ(All)/0.40 pcf (max) HDG/ZMAXInterior/Exterior CBA-A/0.41 pcf (max) HDG/ZMAXInterior/Exterior CA-B/0.21 pcf (max) HDG/ZMAX
K. All bolts and lag screws shall have standard washers. All anchor and expansion bolts used shall be hot dip galvanized or stainless steel.
L. Refer to the Architectural Drawings for additional wood framing members. Provide additional wood framing members shown on the Architectural Drawings even though they may not be shown on the Structural Drawings.
PIER TYPE, T.O.PIER ELT.O.PIER DETAIL
WXXxXX (X) C=X"
BEAM SIZE
REACTION(ULTIMATE LOAD)
NUMBER OF HEADED STUDS
R=XXK
CAMBER
SYMBOLS LEGEND
SYMBOL DESCRIPTION
COMPOSITE STEEL BEAM
CONCRETE PIER
MOMENT CONNECTION
WXXxXX STEEL BEAM MOMENT CONNECTION
SLAB OR DECK SPAN DIRECTION
DROP IN SLAB OR DECK
DROP AND SLOPE IN SLAB OR DECK
SLOPE IN SLAB OR DECK
HEAVY STEEL CONNECTION
EXISTING CONSTRUCTION
LOAD-BEARINGMASONRY WALL
ROOF TOP UNIT (RTU)
WELDED METAL BAR GRATING
COLUMN SIZEBASE PLATE TYPE
STEEL COLUMN
C1CONCRETE COLUMN
STEEL BEAM SPLICE
EXISTING COLUMN GRID
NEW COLUMN GRID#
#
MISCELLANEOUS, SEE PLAN
WINDOW IN LOAD-BEARING MASONRY WALL
DOOR IN LOAD-BEARING MASONRY WALL
NONLOAD-BEARING WALL
BRACE-xVERTICAL STEEL BRACE
STUDRAIL
STANDARD PAN WIDTH
SKIP PAN, xx WIDTH
10P, 15P, 20P, 30P, 40P, 53P, 66P
xxSP
WOOD LOAD-BEARING WALL, SEE SCHEDULE
SHEARWALL, SEE SCHEDULE
SW-x
CONCRETE SHEAR WALL, SEE SCHEDULE
SW-x
BEAM SIZE
R=XXK
NONLOAD-BEARING / BACKUPMASONRY WALL
WINDOW IN NONLOAD-BEARING / BACKUP MASONRY WALL
DOOR IN NONLOAD-BEARING / BACKUP MASONRY WALL
NONLOAD-BEARING MASONRY WALL BELOW
LOAD-BEARING MASONRY WALL BELOW
MASONRY SHEARWALL
AGUSTIN TELLEZ, JR.
79341
10001 REUNION PLACE, SUITE 200
210.349.9098
SAN ANTONIO, TEXAS 78216
TBPE FIRM F-432IES JOB NO:
ENGINEERING COMMUNITIES FROM THE GROUND UP
ie-services.com
Th
e r
eco
rd o
f th
is d
raw
ing
is o
n file
at
the
offic
es o
f S
lay A
rch
itectu
re,
12
3 A
ltg
elt A
ve
nu
e,
San
An
ton
io, T
exa
s 7
82
01
& 9
90
1 M
cP
he
rso
n R
oa
d,
Su
ite 1
04,
La
red
o,
Te
xas 7
80
45.
Th
is d
ocu
me
nt
is r
ele
ased
fo
r th
e p
urp
ose
of re
fere
nce
, co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the
au
tho
rity
of th
e n
am
ed
pro
fessio
na
l, r
eg
istr
atio
n n
um
be
r a
nd
date
on
th
e s
ea
l a
ffix
ed
ab
ove
.C
OP
YR
IGH
T 2
00
0 -
20
19
, S
lay A
rch
ite
ctu
re. T
his
do
cu
men
t w
as p
rep
are
d u
sin
g c
om
pu
ter
assis
ted
desig
n a
nd
dra
ftin
g e
qu
ipm
en
t a
nd
sa
ved
on
mag
netic m
ed
ia.
Ne
ith
er
the
prin
ted
do
cu
men
t n
or
the
ma
gn
etic m
ed
ia m
ay b
e a
ltere
d o
r am
en
de
d b
y a
ny p
art
y o
the
r th
an
Sla
y A
rch
ite
ctu
re.
123 Altgelt AvenueSan Antonio, Texas 78201T: 210.736.3009
9901 McPherson Avenue, #104Laredo, Texas 78045T: 956.791.0405
SAN ANTONIO
LAREDO
Project NO.:
Date:
Revisions:
19005
CD
BG
DE
LL
AN
O P
AR
K IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/19
CIT
Y O
F L
AR
ED
O T
EX
AS
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1192756
September 12, 2019
Fo
ste
r A
ven
ue a
nd
San
ma
n S
tre
et
9/1
0/2
019
5:3
4:4
1 A
M
S0.2
STRUCTURAL NOTES
S T R U C T U R A L N O T E S
SPECIAL INSPECTIONS TABLES FOR STRUCTURAL ELEMENTS - 2012
MINIMUM TESTS
INSPECTION FREQUENCY
LEVEL B VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION (ACI 530 Table 1.19.2)
VERIFICATION, INSPECTION AND TESTINGCONTINUOUS PERIODIC
Verification of Slump flow and Visual Stability Index (VSI) as delivered to the project site in accordance with Specification Article 1.5 B.1.b.3 for self-consolidating grout
Verification of f' and f' in accordance with Specification Article 1.4B prior to construction, except where specifically exempted by this Code
--
-- --
--AACm
INSPECTION TASKS
ACI 318: 6.1.1X13. Inspect formwork for shape, location and dimensions of the concrete members being formed.
ACI 318: 6.2X
12. Verification of in-situ concrete strength, prior to stressing of tendons in post-tensioned concreteand prior to removal of shores and forms from beams and structural slabs.
ACI 318: Ch. 16
X11. Erection of precast concrete members.
X
X ACI 318: 18.20
b. Grouting of bonded prestressing tendons in theseismic-force-resisting system:
a. Application of prestressing forces:
10. Inspection of prestressed concrete:
X 1910.99. Inspection for maintenance of specified curing
temperature and techniques.ACI 318: 5.11-5.13
1910.6,1910.7,1910.8
ACI 318: 5.9, 5.10
8. Inspection of concrete and shotcrete placement for proper application techniques. X
1910.10
ASTM C 172ASTM C 31
ACI 318: 5.6, 5.8
X
7. At the time fresh concrete is sampled to fabricate specimens for strength tests, perform slump andair content tests, and determine the temperature of the concrete.
1904.2,1910.2,1910.3
ACI 318: Ch. 4,5.2-5.4
X
1908.5,1909.1
--3. Inspection of anchors cast in concrete where allowable
loads have been increased or where strength design is used.
AWS D1.4ACI 318: 3.5.2
1910.4ACI 318: 3.5,7.1-7.7
X
VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION (IBC TABLE 1705.3)
1. Inspection of reinforcing steel, including prestressing tendons, and placement.
2. Inspection of reinforcing steel welding in accordance with Table 1705.2.2, Item 2b.
6. Verifying use of required design mix.
VERIFICATION, INSPECTION AND TESTING
X5. Prior to placement of compacted fill, observe subgrade and verify that site has been
prepared properly.
X4. Verify use of proper materials, densities and lift thicknesses during placement and compaction of
controlled fill.
X3. Perform classification and testing of controlled fill materials.
X2. Verify excavations are extended to proper depth and have reached proper material.
X
PERIODICCONTINUOUS
INSPECTION FREQUENCY
1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity.
VERIFICATION AND INSPECTION OF SOILS (IBC TABLE 1705.6)
VERIFICATION AND INSPECTIONCONTINUOUS
INSPECTION FREQUENCY
PERIODIC
--
--
--
X
--
--
--
--
--
--
--
--
--
--
----
--
--
--
--
--
--
--
ACI 318: Appendix D
--
4. Inspection of adhesive anchors installed in hardenedconcrete. Special Inspector must be certified by ACI/CRSI "Adhesive Anchor Installer. A report must be submitted to the licensed design professional and building official documenting, stating how anchor was installed and the Manufacturer's Printed Installation Instructions per ACI 318-11 (D.9.2.2 and D.9.2.4)
X
ACI 318: 8.1.3,21.2.8
1909.1
1. Verify compliance with the approved submittals X--
2. As masonry construction begins, verify that the following are in compliance:
a. Proportions of site-prepared mortar X--
b. Construction of mortar joints X--
c. Grade and size of prestressing tendons and anchorages X--
d. Location of reinforcement, connectors, and prestressing tendons and anchorages X--
e. Prestressing technique X--
3. Prior to grouting, verify that the following are in compliance:
a. Grout space X--
b. Grade, type and size of reinforcement and anchor bolts, and prestressingtendons and anchorages X--
c. Placement of reinforcement, connectors and prestressing tendons and anchorages
d. Proportions of site-prepared grout and prestressing grout for bonded tendons X--
e. Construction of mortar joints X--
X--
4. Verify during construction:
a. Size and location of structural elements X--
b. Type, size and location of anchors, including other details of anchorage of
X--
c. Welding of reinforcement --X
d. Preparation, construction and protection of masonry during cold weather (temperature below 40°F (4.4°C)) or hot weather (temperature above 90°F (32.2°C))
X--
e. Application and measurement of prestressing force
f. Placement of grout and prestressing grout for bonded tendons is in compliance --X
5. Observe preparation of grout specimens, mortar specimens and/or prisms
--X
X--
SPECIAL INSPECTIONS
1. Special Inspections shall be performed in accordance with Chapter 17 of the 2012 International Building Code (IBC) by a SpecialInspector hired by the Owner to perform the Special Inspections listed below. The Special Inspector shall be qualified by anapproved agency according to the City's building official to perform the special inspections for which they will be undertaking. The Contractor shall coordinate with and notify the Special Inspector of all tests. The Special Inspector shall be responsible to verify that the items detailed in the Construction Documents were built accordingly and shall prepare, sign, and furnish inspectionreports to the building official and the Architect for all time spent at the site. The Inspector shall bring discrepancies to the immediate attention of the General Contractor for correction. If the discrepancies are not corrected, the discrepancies shall be brought to the attention of the building official and to the Architect prior to the completion of that phase of the work. These special inspections are in addition to the other inspections listed in these Structural Notes or Project Specifications.
2. Where structural members and assemblies are shop fabricated, the Special Inspector shall verify that the fabricatormaintains detailed fabrication and quality control procedures that provide a basis for inspection control of the workmanship and the fabricator's ability to conform to the Construction Documents and Referenced Standards, unless the fabricator is registeredand approved to perform such work without special inspection.
REFERENCEDSTANDARD
IBCREFERENCE
VERIFICATION, INSPECTION AND TESTING
2. Inspect wood structural panel sheathing construction for the following:
X
PERIODICCONTINUOUS
INSPECTION FREQUENCY
1. Fabrication process of prefabricated wood structural elements and assemblies shall bein accordance with IBC 1704.2.5 and local amendments
VERIFICATION AND INSPECTION OF WOOD (IBC 1705.5)
--
a. Grade and thickness shown on approved building plans.
b. Nominal size of framing members at adjoining panel edges, per approved building plans.
c. Nail or staple diameter and length, per approved building plans.
d. Number of fastener lines and the spacing between fasteners in each line and at edge margins, per approved building plans.
X--
X--
X--
X--
3. Trusses over 60'-0", inspector shall verify the following:
a. Temporary installation restraint/bracing per approved truss submittal. X--
X--b. Permanent individual truss member restraint/bracing are installed per approved
truss submittal.
ACI 318: 3.8.6, 8.1.3, 21.2.8
X5. Inspection of mechanical anchors installed in hardened
concrete.-- 1909.1
--
f. Properties of thin-bed mortar for AAC masonry XX
g. Placement of AAC masonry units and construction of thin-bed mortar joints XX
1. Required for the first 5000 square feet (465 square meters) of AAC masonry.2. Required after the first 5000 square feet (465 square meters) of AAC masonry.
masonry to structural members, frames or other construction
ACI 318: 18.18.4
21
21
AGUSTIN TELLEZ, JR.
79341
10001 REUNION PLACE, SUITE 200
210.349.9098
SAN ANTONIO, TEXAS 78216
TBPE FIRM F-432IES JOB NO:
ENGINEERING COMMUNITIES FROM THE GROUND UP
ie-services.com
Th
e r
eco
rd o
f th
is d
raw
ing
is o
n file
at
the
offic
es o
f S
lay A
rch
itectu
re,
12
3 A
ltg
elt A
ve
nu
e,
San
An
ton
io, T
exa
s 7
82
01
& 9
90
1 M
cP
he
rso
n R
oa
d,
Su
ite 1
04,
La
red
o,
Te
xas 7
80
45.
Th
is d
ocu
me
nt
is r
ele
ased
fo
r th
e p
urp
ose
of re
fere
nce
, co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the
au
tho
rity
of th
e n
am
ed
pro
fessio
na
l, r
eg
istr
atio
n n
um
be
r a
nd
date
on
th
e s
ea
l a
ffix
ed
ab
ove
.C
OP
YR
IGH
T 2
00
0 -
20
19
, S
lay A
rch
ite
ctu
re. T
his
do
cu
men
t w
as p
rep
are
d u
sin
g c
om
pu
ter
assis
ted
desig
n a
nd
dra
ftin
g e
qu
ipm
en
t a
nd
sa
ved
on
mag
netic m
ed
ia.
Ne
ith
er
the
prin
ted
do
cu
men
t n
or
the
ma
gn
etic m
ed
ia m
ay b
e a
ltere
d o
r am
en
de
d b
y a
ny p
art
y o
the
r th
an
Sla
y A
rch
ite
ctu
re.
123 Altgelt AvenueSan Antonio, Texas 78201T: 210.736.3009
9901 McPherson Avenue, #104Laredo, Texas 78045T: 956.791.0405
SAN ANTONIO
LAREDO
Project NO.:
Date:
Revisions:
19005
CD
BG
DE
LL
AN
O P
AR
K IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/19
CIT
Y O
F L
AR
ED
O T
EX
AS
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1192756
September 12, 2019
Fo
ste
r A
ven
ue a
nd
San
ma
n S
tre
et
9/1
0/2
019
5:3
4:4
3 A
M
S0.3
SPECIAL INSPECTIONS
PL - PLATE
PLF - POUNDS PER LINEAR FOOT
PLYWD - PLYWOOD
PREFAB - PREFABRICATED
PRELIM - PRELIMINARY
PROJ - PROJECTION
PSF - POUNDS PER SQUAREFOOT
PSI - POUNDS PER SQUARE INCH
PT - POINT (OR) PRESSURETREATED
P-T - POST-TENSION(ED)
P/E - PRE-ENGINEERED
PAF - POWDER ACTUATEDFASTENER
QTY - QUANTITY
R - RADIUS (OR) REACTION(OR) REMAINDER
RCP - REINFORCED CONCRETEPIPE
RD - ROOF DRAIN
REINF - REINFORCE(ING)(ED)(MENT)
REQ - REQUIRE(MENT)
REQD - REQUIRED
RET - RETAINING
RET SYS - RETENTION SYSTEM
RF - ROOF
RIS - RISER
RM - ROOM
RND - ROUND
RO - ROUGH OPENING
RTU - ROOF TOP UNIT
SCHED - SCHEDULE(D)
SECT - SECTION
SF - SQUARE FOOT
SHT - SHEET
SHTG - SHEATHING
SIM - SIMILAR
SJI - STEEL JOIST INSTITUTE
SL - SLOPE
SOG - SLAB ON GRADE
SP - SOUTHERN PINE
SPA - SPACE
SPECD - SPECIFIED
SPEC(S) - SPECIFICATION(S)
SQ - SQUARE
SS - STAINLESS STEEL
SSL - SHORT SLOTTED HOLE
STAGG - STAGGERED
STD - STANDARD
STIFF - STIFFENER
STIRR - STIRRUPS
STL - STEEL
STR - STRAIGHT
STRUCT - STRUCTURE (OR)STRUCTURAL
SUBCONTR - SUBCONTRACTOR
SUPT(S) - SUPPORT(S)
SW - SHEARWALL (OR)SIDEWALK
T - TENSION
T.O. - TOP OF
T&B - TOP AND BOTTOM
T&G - TONGUE AND GROOVE
TEMP - TEMPERATURE
TERR - TERRAZZO
THK - THICK
THRD - THREAD(ED)
TIL - TOP INSIDE LAYER
TOB - TOP OF BEAM
TOC - TOP OF CONCRETE
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOL - TOP OUTSIDE LAYER
TOP - TOP OF PIER
TOPC - TOP OF PIER (PILE) CAP
TOS - TOP OF STEEL
TOW - TOP OF WALL
TR - TREAD
TRANSV - TRANSVERSE
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
V - SHEAR
VB - VERTICAL BRACE
VERT - VERTICAL
W - WIDTH
W/ - WITH
W/O - WITHOUT
WD - WOOD
WDW - WINDOW
WL - WIND LOAD
WP - WORK POINT
WPFG - WATERPROOFING
WS - WATERSTOP
WT - WEIGHT
WWM - WELDED WIRE MESH
X-STR - EXTRA STRONG
XX-STR - DOUBLE EXTRA STRONG
HDR - HEADER
HI - HIGH
HK - HOOK
HL - HOLE
HORIZ - HORIZONTAL
HP - HIGH POINT
HS - HEADED STUD
HSS - HOLLOW STRUCTURALSECTION
HT - HEIGHT
ID - INSIDE DIAMETER
IF - INSIDE FACE
IN - INCH
INFO - INFORMATION
INT - INTERIOR
INTERM - INTERMEDIATE
JG - JOIST GIRDER
JST(S) JOIST(S)
JT - JOINT
K - KIPS (1000 LBS)
KLF - KIP PER LINEAR FOOT
KSF - KIP PER SQUARE FOOT
KSI - KIP PER SQUARE INCH
L - LENGTH
LBS - POUNDS
LL - LIVE LOAD
LLH - LONG LEG HORIZONTAL
LLV - LONG LEG VERTICAL
LO - LOW
LOC - LOCATION
LONG - LONGITUDINAL
LP - LOW POINT
LSH - LONG SIDE HORIZONTAL
LSL - LONG SLOTTED HOLES
LSV - LONG SIDE VERTICAL
LW - LIGHTWEIGHT
LWC - LIGHTWEIGHT CONCRETE
M - MOMENT
MAS - MASONRY
MATL - MATERIAL
MAX - MAXIMUM
MC - MOMENT CONNECTION(S)
MECH - MECHANICAL
MEP - MECHANICAL, ELECTRICAL,PLUMBING
MEZZ - MEZZANINE
MFR - MANUFACTURER
MID - MIDDLE
MIN - MINIMUM
MISC - MISCELLANEOUS
MTL - METAL
NF - NEAR FACE
NIC - NOT IN CONTRACT
NOM - NOMINAL
NS - NON-SHRINK
NTS - NOT TO SCALE
OC - ON CENTER
OCEW - ON CENTER EACH WAY
OD - OUTSIDE DIAMETER (OR)OVERFLOW DRAIN
OF - OUTSIDE FACE
OH - OPPOSITE HAND
OPNG(S) - OPENING(S)
OPP - OPPOSITE
OVS - OVER-SIZED HOLE
P - PAN
P/C - PRECAST CONCRETE
PAR - PARALLEL
PC - PIECE
PCF - POUNDS PER CUBIC FOOT
PEMB - PRE-ENGINEERED METALBUILDING
PERP - PERPENDICULAR
PI - PLASTICITY INDEX
PJ - PANEL JOINT
PJP - PARTIAL JOINTPENETRATION
A/C - AIR CONDITIONER
AB - ANCHOR BOLT
ABV - ABOVE
ACI - AMERICAN CONCRETEINSTITUTE
ADDL - ADDITIONAL
ADH - ADHESIVE
ADJ - ADJACENT
AEC - ARCHITECTURALLYEXPOSED CONCRETE
AESS - ARCHITECTURALLYEXPOSED STRUCTURALSTEEL
AFF - ABOVE FINISHED FLOOR
AGGR - AGGREGATE
AHU - AIR HANDLING UNIT
AISC - AMERICAN INSTITUTE OFSTEEL CONSTRUCTION
ALT - ALTERNATE
APPD - APPROVED
APPROX - APPROXIMATE
ARCH - ARCHITECT (OR)ARCHITECTURAL
BD - BOARD
B.O. - BOTTOM OF
BF - BACK FACE
BFF - BELOW FINISH FLOOR
BIL - BOTTOM INSIDE LAYER
BL - BUILDING LINE
BLDG - BUILDING
BLK - BLOCK
BLKG - BLOCKING
BM - BEAM
BOL - BOTTOM OUTSIDE LAYER
BOS - BOTTOM OF STEEL
BOTT - BOTTOM
BP - BASE PLATE
BRDG - BRIDGING
BRG - BEARING
BRKT - BRACKET
BRL - BRICKLEDGE
BSMT - BASEMENT
B TO B - BACK TO BACK
BTWN - BETWEEN
C - CAMBER (OR)COMPRESSION
CANT - CANTILEVER
CFS - COLD FORMED STEEL
CG - CENTER OF GRAVITY
CGS - CENTER OF GRAVITY OFSTRAND
CIP - CAST-IN-PLACE
CJ - CONTROL JOINT
CJP - COMPLETE JOINTPENETRATION
CL - CENTER LINE
CLG - CEILING
CLR - CLEAR (OR) CLEARANCE
CMU - CONCRETE MASONRY UNIT
COL - COLUMN
C OR COMP - COMPRESSION
CONC - CONCRETE
CONN(S) - CONNECTION(S)
CONST - CONSTRUCTION
CONST JT - CONSTRUCTION JOINT
CONT - CONTINOUS
CONTR - CONTRACTOR
COORD - COORDINATE
CTSK - COUNTER SUNK
CVR - COVER
DBA - DEFORMED BAR ANCHORS
DBL - DOUBLE
DEV - DEVELOPMENT
DFL - DOUGLAS FIR LARCH
DIA - DIAMETER
DIAG - DIAGONAL
DIM(S) - DIMENSION(S)
DKG - DECKING
DL - DEAD LOAD
DN - DOWN
DS - DOWNSPOUT
DTL - DETAIL
DVTL - DOVETAIL
DWG(S) - DRAWING(S)
DWL(S) - DOWELS
DE - DECK EDGE
EA - EACH
EF - EACH FACE (OR) EXHAUSTFAN
EJ - EXPANSION JOINT
EL - ELEVATION
ELEC - ELECTRICAL
ELEV - ELEVATOR
EMBED - EMBEDMENT
ENGR - ENGINEER
EOR - ENGINEER OF RECORD
EQ - EQUAL (OR) EQUIVALENT
EQUIP - EQUIPMENT
EW - EACH WAY
EXIST - EXISTING
EXP - EXPANSION
EXT - EXTERIOR
EXTN - EXTENSION
F TO F - FACE TO FACE
FABR - FABRICATOR
FD - FLOOR DRAIN
FDN - FOUNDATION
FFE - FINISHED FLOORELEVATION
FIN - FINSH (OR) FINISHED
FIN FL - FINISHED FLOOR
FL - FLOOR
FLG - FLANGE
FP - FIREPROOF(ING)
FRMG - FRAMING
FS - FAR SIDE
FT - FOOT (OR) FEET
FTG - FOOTING
FV - FIELD VERIFY
GA - GAGE (OR) GAUGE
GALV - GALVANIZED
GC - GENERAL CONTRATOR
GR - GRADE
GR BM - GRADE BEAM
HB - HORIZONTAL BRACE
HCA - HEADED CONCRETEANCHOR
HDG - HOT DIPPED GALVANIZED
SL
SL
SLSL SL SL
SL
SL
19'-4"
1'-4" 5'-0" 1'-4" 4'-0" 1'-4" 5'-0" 1'-4"
8'-8" 2'-0" 8'-8"
19'-4"
8" 18'-0" 8"
8'-0" 2'-0" 8'-0"
19'-0
"
13'-4"
5'-8"
19'-0
"
13'-4"
5'-8"
" CONCRETE SLAB-ON-GRADE REINFORCED W/ @ " OC EA WAY, REFER STRUCTURAL NOTES FOR VAPOR RETARDER & FILL REQUIREMENTS.
5
#4 12
1
S2.2
1
S2.2
1
S2.2
2
S2.2
3
S2.2
3
S2.2
4
S2.2
2x10 @ 2'-0" OC
3
S1.1
CMU PILASTER BLW, TYP
4
S1.1
4
S1.1
5
S1.1
5
S1.1
HDR ABV OPNG, TYP
2x10 OUTRIGGERS, TYP
TOW ELEV = +8'-0" AFF
TOW ELEV = +11'-4" AFF BEYOND
ROOF DECK, SEE STRUCT NOTES, TYP
2x10 CONT FASCIA, TYP
TO OPNG ELEV = + 8'-0" AFF
8" BOND BM CONT REINF W/2-#5, SOLID GROUTED, TYP
2x8 PT SILL PLATE CONT W/5/8" DIA SS EXP ANCHORS @ 2'-0" O.C., TYP
SIMPSON H2.5 (OR APP'D EQ) HURRICANE TIE, TYP
2x8 BLOCKING BETWEEN RAFTERS
2x10 & 2x8 HDR ABV OPNG
SEE ARCH'L
2x10 BLOCKING BETWEEN JOISTS @ 1/3 POINTS, TYP
2x10 OUTRIGGERS @ OPNG, TYP
ELEV VARIES
TOW ELEV VARIES
ROOF DECK, SEE STRUCT NOTES, TYP
ROOF JOISTS, SEE PLAN, TYP
2x8 SILL PLATE, SEE 3/S1.1, TYP
SIMPSON H2.5 (OR APP'D EQ) TIE EA FACE OF 2x10 BLOCKING, TYP
8" BOND BM CONT, SEE 3/S1.1, TYP
ARCH'L
SEE
2x10 BLOCKING BETWEEN JOISTS, TYP
ELEV VARIES
BOND BM ELEV, SEE ARCH'L
ROOF DECK, SEE STRUCT NOTES, TYP
ROOF JOISTS, SEE PLAN, TYP
2x8 SILL PLATE, SEE 3/S1.1, TYP
SIMPSON H2.5 (OR APP'D EQ) TIE EA FACE OF 2x10 BLOCKING, TYP
8" BOND BM CONT, SEE 3/S1.1, TYP
ARCH'L
SEE
2x10 BLOCKING BETWEEN JOISTS, TYP
DECORATIVE WALL UNITS, SEE ARCH'L, TYP
AGUSTIN TELLEZ, JR.
79341
10001 REUNION PLACE, SUITE 200
210.349.9098
SAN ANTONIO, TEXAS 78216
TBPE FIRM F-432IES JOB NO:
ENGINEERING COMMUNITIES FROM THE GROUND UP
ie-services.com
Th
e r
eco
rd o
f th
is d
raw
ing
is o
n file
at
the
offic
es o
f S
lay A
rch
itectu
re,
12
3 A
ltg
elt A
ve
nu
e,
San
An
ton
io, T
exa
s 7
82
01
& 9
90
1 M
cP
he
rso
n R
oa
d,
Su
ite 1
04,
La
red
o,
Te
xas 7
80
45.
Th
is d
ocu
me
nt
is r
ele
ased
fo
r th
e p
urp
ose
of re
fere
nce
, co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the
au
tho
rity
of th
e n
am
ed
pro
fessio
na
l, r
eg
istr
atio
n n
um
be
r a
nd
date
on
th
e s
ea
l a
ffix
ed
ab
ove
.C
OP
YR
IGH
T 2
00
0 -
20
19
, S
lay A
rch
ite
ctu
re. T
his
do
cu
men
t w
as p
rep
are
d u
sin
g c
om
pu
ter
assis
ted
desig
n a
nd
dra
ftin
g e
qu
ipm
en
t a
nd
sa
ved
on
mag
netic m
ed
ia.
Ne
ith
er
the
prin
ted
do
cu
men
t n
or
the
ma
gn
etic m
ed
ia m
ay b
e a
ltere
d o
r am
en
de
d b
y a
ny p
art
y o
the
r th
an
Sla
y A
rch
ite
ctu
re.
123 Altgelt AvenueSan Antonio, Texas 78201T: 210.736.3009
9901 McPherson Avenue, #104Laredo, Texas 78045T: 956.791.0405
SAN ANTONIO
LAREDO
Project NO.:
Date:
Revisions:
19005
CD
BG
DE
LL
AN
O P
AR
K IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/19
CIT
Y O
F L
AR
ED
O T
EX
AS
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1192756
September 12, 2019
Fo
ste
r A
ven
ue a
nd
San
ma
n S
tre
et
9/1
0/2
019
5:3
4:4
3 A
M
S1.1
FOUNDATION AND
ROOF FRAMING PLANS
north
SCALE: 1/4" = 1'-0"1 FOUNDATION PLAN
north
SCALE: 1/4" = 1'-0"2 FRAMING PLAN
SCALE: 3/4" = 1'-0"3 TYPICAL ROOF FRAMING ELEVATION
SCALE: 3/4" = 1'-0"4 TYPICAL PERIMETER FRAMING DETAIL
SCALE: 3/4" = 1'-0"5 TYPICAL PERIMETER FRAMING DETAIL
CORNER BARS EACH FACETO MATCH TOP, BOTTOMAND INTERMEDIATE BARSIN DISCONTINUOUS MEMBER
NOTES:
1. MATCH SIZE, LOCATION AND NUMBER OF HORIZONTALBEAM AND WALL BARS, EXCEPT THAT WHERE THERE AREMORE THAN 2 TOP OR BOTTOM BARS, ONLY THE INSIDEAND OUTSIDE BARS MUST BE MATCHED.
2. WHERE 90 DEGREE HOOKS ARE PROVIDED FOR TOP BARS CORNER BARS MAY BE OMITTED AT TOP. WHERE 90 DEGREE HOOKS ARE PROVIDED FOR BOTTOM BARS, CORNER BARS MAY BE OMITTED AT BOTTOM.
STOP DETAILEDREINF 2" SHORT OF FORM TYPICAL
CORNER BARS
PLAN
CORNER BARS EACH FACE TO MATCHLARGER BAR AT INTERSECTION.PROVIDE CORNER BARS SHOWN ATTOP, BOTTOM AND INTERMEDIATEHORIZONTAL BARS
EACH LEG TYPICAL
48 BAR DIAMETERS
EAC
H L
EG
TYPIC
AL
48 B
AR
DIA
METER
S
CONSTRUCTION JOINT WITHIN MIDDLE THIRD OF SPAN
ELEVATION
BEAM REINFORCINGCONTINUOUS THROUGHCONSTRUCTION JOINT 2 ADDL STIRRUPS
EACH SIDE OF JOINT
NOTE:THIS DETAIL APPLIES TO BEAMS < 4'-0" DEPTH.
11 1/4"
9 1/4"
24" TO 30"
20" TO 24"
7 1/4"
5 1/2"
3 1/2"
16" TO 20"
< 12"
12" TO 16"
KEY WIDTH
BEAMWIDTH
W
ADDL (4)-#6 x 5'-0" AT JOINT
6" 6" 6" 6"
1/3 "D
"1/
3 "D
"1/
3 "D
"
"D" D
EPTH O
F B
EAM
1 1/2" DEEP SHEAR KEY
3 ADDL STIRRUPS @4" OC (TYP EACH SIDEOF PIPE SLEEVE)
PIPE SLEEVE - SEE MEP SERIESDRAWINGS FOR EXACT SIZEAND LOCATION (Ø NOT TOEXCEED 6" NOR 1/3 BEAMDEPTH; SUBMIT DRAWING TOARCHITECT/ENGINEER SHOWINGLOCATION AND SIZE OF ALLPENETRATIONS LARGER THAN 3"PRIOR TO PLACEMENT)
(2)-#5 x 2'-6" ABOVE& BELOW SLEEVE
D/3
CLR
(MIN
)
D/3
CLR
(MIN
)BEAM
DEPTH "D
"
1'-
0 3
/128"
1'-
0 3
/128"
(TYP)1" CLR MIN
ELEVATION
CONTINUOUS 3/4"x1 1/2" KEY. IF METAL FORM IS USED, REMOVE IT BEFORE POURING ADJACENT SLAB
1/2"x2'-0" SMOOTH BARS @ 18" OC
VAPOR RETARDER
6" 6"
WHIC
HEV
ER
IS G
REATER
8" O
R S
LAB
THIC
KNESS,
#4 x 1'-0" @ 18"WITH (1)-#4 CONTINUOUSOPTIONAL
CONSTRUCTION JOINTDRAPE REINFORCING
1'-0"
VAPOR RETARDER
VAPOR RETARDER
THIC
KNESS
< SLAB
1'-0"
1'-0"
THIC
KNESS
> SLAB
NOTE:MAINTAIN TYPICAL SLAB THICKNESS EACH SIDE OF DROP UNLESS NOTED OTHERWISE.
-# CONT
#3 @ 18" OC
8"
EQUAL
-
EQUAL
1'-0
"
CENTERLINE OF WALLSEE ARCHITECTURAL DRAWINGS FOR LOCATION
VAPOR RETARDER,SEE STRUCTURAL NOTES
RECTANGULAR, SQUAREOR ROUND BLOCKOUT INSLAB-ON-GRADE
#4x2'-6" EA SIDE OFBLOCKOUT AT MID DEPTHOF SLAB (NOT REQD ATROUND BLOCKOUTS LESSTHAN 4" DIAMETER)
PLAN
2" CLR
PLAN
CONCRETE SLAB
(2)-#4 x 3'-0" @ ALL RE-ENTRANTCORNERS ((NOT ALIGNED WITHCONTROL JOINT)). PLACE IN TOPOF SLAB WITH 1" MIN CLEAR
2" C
LR
AGUSTIN TELLEZ, JR.
79341
10001 REUNION PLACE, SUITE 200
210.349.9098
SAN ANTONIO, TEXAS 78216
TBPE FIRM F-432IES JOB NO:
ENGINEERING COMMUNITIES FROM THE GROUND UP
ie-services.com
Th
e r
eco
rd o
f th
is d
raw
ing
is o
n file
at
the
offic
es o
f S
lay A
rch
itectu
re,
12
3 A
ltg
elt A
ve
nu
e,
San
An
ton
io, T
exa
s 7
82
01
& 9
90
1 M
cP
he
rso
n R
oa
d,
Su
ite 1
04,
La
red
o,
Te
xas 7
80
45.
Th
is d
ocu
me
nt
is r
ele
ased
fo
r th
e p
urp
ose
of re
fere
nce
, co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the
au
tho
rity
of th
e n
am
ed
pro
fessio
na
l, r
eg
istr
atio
n n
um
be
r a
nd
date
on
th
e s
ea
l a
ffix
ed
ab
ove
.C
OP
YR
IGH
T 2
00
0 -
20
19
, S
lay A
rch
ite
ctu
re. T
his
do
cu
men
t w
as p
rep
are
d u
sin
g c
om
pu
ter
assis
ted
desig
n a
nd
dra
ftin
g e
qu
ipm
en
t a
nd
sa
ved
on
mag
netic m
ed
ia.
Ne
ith
er
the
prin
ted
do
cu
men
t n
or
the
ma
gn
etic m
ed
ia m
ay b
e a
ltere
d o
r am
en
de
d b
y a
ny p
art
y o
the
r th
an
Sla
y A
rch
ite
ctu
re.
123 Altgelt AvenueSan Antonio, Texas 78201T: 210.736.3009
9901 McPherson Avenue, #104Laredo, Texas 78045T: 956.791.0405
SAN ANTONIO
LAREDO
Project NO.:
Date:
Revisions:
19005
CD
BG
DE
LL
AN
O P
AR
K IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/19
CIT
Y O
F L
AR
ED
O T
EX
AS
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1192756
September 12, 2019
Fo
ste
r A
ven
ue a
nd
San
ma
n S
tre
et
9/1
0/2
019
5:3
4:4
4 A
M
S2.1
TYPICAL CONCRETE
FRAMING DETAILS
SCALE: 3/4" = 1'-0"1 TYPICAL CORNER BARS AT GRADE BEAM INTERSECTION DETAIL
SCALE: 3/4" = 1'-0"2 TYPICAL CONCRETE BEAM CONSTRUCTION JOINT DETAIL
SCALE: 3/4" = 1'-0"3 TYPICAL HORIZONTAL GRADE BEAM PENETRATION DETAIL
SCALE: 3/4" = 1'-0"4 TYPICAL SLAB-ON-GRADE CONSTRUCTION JOINT DETAIL
SCALE: 3/4" = 1'-0"5 TYPICAL DROP IN SLAB-ON-GRADE DETAIL
SCALE: 3/4" = 1'-0"6 TYPICAL SLAB-ON-GRADE STIFFENER BEAM DETAIL
SCALE: 3/4" = 1'-0"7
TYPICAL ADDITIONAL REINFORCING ATBLOCKOUT IN SLAB-ON-GRADE < 3'-0" DETAIL
SCALE: 3/4" = 1'-0"8
TYPICAL SLAB RE-ENTRANTCORNER REINFORCING DETAIL
TOC ELEV
CVR, TYP3" CLR
1'-0"
PLAN
SEE
2'-6" M
IN
8" CMU WALL REINF W/#5 VERT @ 2'-8" OC IN SOLID GROUTED CELLS, TYP
#5 HOOKED DOWELS @ 2'-8" OC, EXTEND 2'-0" MIN INTO CMU WALL, TYP
2-#6 CONT TOP & BOTT W/#3 CLOSED TIES @ 12" OC, TYP
SEE PLAN FOR SLAB REINF. DOWEL OR HOOK INTO PERIMETER BM, TYP
VAPOR RETARDER, SEE STRUCT NOTES, TYP
COMPACTED FILL MAT'L, SEE STRUCT NOTES, TYP
3"
TOC ELEV
1'-0"
8" CMU WALL REINF W/#5 VERT @ 2'-8" OC IN SOLID GROUTED CELLS, TYP
#5 HOOKED DOWELS @ 2'-8" OC, EXTEND 2'-0" MIN INTO CMU WALL, TYP
2-#6 CONT TOP & BOTT W/#3 CLOSED TIES @ 12" OC, TYP
SEE PLAN FOR SLAB REINF. DOWEL OR HOOK INTO PERIMETER BM, TYP
VAPOR RETARDER, SEE STRUCT NOTES, TYP
COMPACTED FILL MAT'L, SEE STRUCT NOTES, TYP
1'-0" 1'-0"
CVR, TYP3" CLR
PLAN
SEE
2'-6"
TOC ELEV
CVR, TYP3" CLR
1'-0"
PLAN
SEE
2'-6" M
IN
LINE OF CONC BM BEYOND
2-#6 CONT TOP & BOTT W/#3 CLOSED TIES @ 12" OC, TYP
SEE PLAN FOR SLAB REINF. DOWEL OR HOOK INTO PERIMETER BM, TYP
VAPOR RETARDER, SEE STRUCT NOTES, TYP
COMPACTED FILL MAT'L, SEE STRUCT NOTES, TYP
1-#5 CONT TOP & BOTT W/#3 OPEN TIES @ 12" OC, TYP
TOC ELEV
CVR, TYP3" CLR
1'-0"
PLAN
SEE
2'-6" M
IN
2-#6 CONT TOP & BOTT W/#3 CLOSED TIES @ 12" OC, TYP
SEE PLAN FOR SLAB REINF. DOWEL OR HOOK INTO PERIMETER BM, TYP
VAPOR RETARDER, SEE STRUCT NOTES, TYP
COMPACTED FILL MAT'L, SEE STRUCT NOTES, TYP
3"
AGUSTIN TELLEZ, JR.
79341
10001 REUNION PLACE, SUITE 200
210.349.9098
SAN ANTONIO, TEXAS 78216
TBPE FIRM F-432IES JOB NO:
ENGINEERING COMMUNITIES FROM THE GROUND UP
ie-services.com
Th
e r
eco
rd o
f th
is d
raw
ing
is o
n file
at
the
offic
es o
f S
lay A
rch
itectu
re,
12
3 A
ltg
elt A
ve
nu
e,
San
An
ton
io, T
exa
s 7
82
01
& 9
90
1 M
cP
he
rso
n R
oa
d,
Su
ite 1
04,
La
red
o,
Te
xas 7
80
45.
Th
is d
ocu
me
nt
is r
ele
ased
fo
r th
e p
urp
ose
of re
fere
nce
, co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the
au
tho
rity
of th
e n
am
ed
pro
fessio
na
l, r
eg
istr
atio
n n
um
be
r a
nd
date
on
th
e s
ea
l a
ffix
ed
ab
ove
.C
OP
YR
IGH
T 2
00
0 -
20
19
, S
lay A
rch
ite
ctu
re. T
his
do
cu
men
t w
as p
rep
are
d u
sin
g c
om
pu
ter
assis
ted
desig
n a
nd
dra
ftin
g e
qu
ipm
en
t a
nd
sa
ved
on
mag
netic m
ed
ia.
Ne
ith
er
the
prin
ted
do
cu
men
t n
or
the
ma
gn
etic m
ed
ia m
ay b
e a
ltere
d o
r am
en
de
d b
y a
ny p
art
y o
the
r th
an
Sla
y A
rch
ite
ctu
re.
123 Altgelt AvenueSan Antonio, Texas 78201T: 210.736.3009
9901 McPherson Avenue, #104Laredo, Texas 78045T: 956.791.0405
SAN ANTONIO
LAREDO
Project NO.:
Date:
Revisions:
19005
CD
BG
DE
LL
AN
O P
AR
K IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/19
CIT
Y O
F L
AR
ED
O T
EX
AS
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1192756
September 12, 2019
Fo
ste
r A
ven
ue a
nd
San
ma
n S
tre
et
9/1
0/2
019
5:3
4:4
4 A
M
S2.2
CONCRETE FRAMING
DETAILS
SCALE: 3/4" = 1'-0"1 TYPICAL PERIMETER BEAM DETAIL
SCALE: 3/4" = 1'-0"2 TYPICAL INTERIOR BEAM AT CHASE DETAIL
SCALE: 3/4" = 1'-0"3 WIDENED BEAM DETAIL
SCALE: 3/4" = 1'-0"4 S2.2/4
#5 VERT IN GROUTED CELLFULL HEIGHT OF WALL @2'-8" OC MAX - TYP UNO
SEE 2/S3.1 FORDOWEL INFO
JAMB REINFORCING, TYP
ELEVATION
T.O. FOUNDATION
1 '-0" EXTEND HORIZONTAL REINFORCING16" FOR OPENINGS < 6'-0";24" MIN OR MATCH REINFORCEDJAMB WIDTH AT OPENINGS > 6'-0" -TYP
> 6'-0"< 6'-0"
NOTES:1. SEE ARCH DRAWINGS FOR LOCATION AND DIMENSIONS OF WALL OPENINGS.
2. SEE THE STRUCTURAL MASONRY NOTES ON S0.2 FOR LAP SPLICE LENGTHS. 3. SEE STRUCTURAL NOTES FOR ADDITIONAL CMU REQUIREMENTS.
4. ELECTRICAL JUNCTION BOXES SHALL NOT INTERRUPT WALL REINFORCEMENT.
SEE NOTE 4
3S3.1
4S3.1
3S3.1
3S3.1
4S3.1
2S3.1
"A" "B" "C"
CAST-IN-PLACE (STRAIGHT BAR)
PROVIDE DOWELS TOMATCH SIZE & SPACINGOF REINFORCING BARSIN WALL, TYP - SEE NOTE 1
1'-6" 2'-0" 5 1/2"
1'-6" 2'-6" 7"
2'-0" 3'-6" 8 1/2"
2'-6" 4'-10" 10"
#4
#5
#6
#7
CAST-IN-PLACE (HOOKED BAR)
#4 CONT
STD HOOKDRILL & ADHERE DOWELINTO CONCRETE, SEESTRUCTURAL NOTES FOR ADHESIVE DOWEL INFO
DRILLED-IN ALTERNATE(@ INTERIOR PARTITIONS ONLY)
SEE 1/S3.1 FORWALL REINF, TYPUNO
"A"
"B"
"B"
6"
"C"
"B"
SEE S
EC
TIO
NS
SLAB CONT AT INTERIOR CONDITION, TYP
NOTES:
1. AT WALLS WITH DOUBLE REINFORCING, PROVIDE SINGLE DOWEL AT SIZE AND SPACING OF SCHEDULED WALL REINFORCING. CENTER DOWEL ON WALL, UNO
2. MASONRY DOWELS SHALL BE TIED IN OR DRILLED AND ADHERED. MASONRY DOWELS SHALL NOT BE "STABBED" IN.
3. HOLES FOR MASONRY DOWELS MUST BE CLEANED WITH A WIRE BRUSH AND COMPRESSED AIR. SEE STRUCTURAL NOTES AND SPECIFICATIONS FOR ADDITIONAL INFORMATION. FOLLOW MANUFACTURER'S INSTALLATION INSTRUCTIONS.
DOWEL SIZE
DIMENSIONS
OPENINGS < 6'-0" 6'-0" < OPENINGS < 12'-0"
TROUGH BLOCKS
(2)-#4 CONT
GROUT AND VERT REINF SPACING, SEE CM-1, CM-1A
NOTES:
1. LINTELS SHALL REMAIN SHORED UNTIL MASONRY CONSTRUCTION ABOVE HAS CURED FOR A MINIMUM OF 14 DAYS.
2. SEE ARCHITECTURAL DRAWINGS FOR OPENING SIZE AND LOCATION.
3. EXTEND LINTELS PAST EDGES OF OPENINGS PER 1/S3.1, TYP.
4. VERTICAL CONTROL JOINTS SHALL NOT CROSS LINTEL REINFORCING.
(2)-#5 CONT
CO
URSE
GR
OUT
1
CO
URSE
GR
OUT
1
KNOCK-OUT WEB BOND BEAM
EXTEND VERTICAL REINFBEYOND THROUGH BONDBEAM
(2)-#4 CONT
WALL IS CONTINUOUSWHERE SHOWN
1" M
AX
TYP1 1/2" CLR
HORIZONTAL JOINTREINFORCING AT16" OC, UNO SEE 1/S3.1 FOR CMU WALL
VERT REINF
PRE-FABRICATEDJOINT REINFORCING SECTIONS @ CORNERS AND TEES (NOT SHOWN):
PLAN
TYPICAL VERT REINFAT CORNERS
(1)-#5 CORNERBAR 2'-6"
2'-6"
2'-6"
(1)-#5 CORNERBAR 2'-6"
SEE 3/S3.1 FORBOND BEAM REINFORCING, TYP
AGUSTIN TELLEZ, JR.
79341
10001 REUNION PLACE, SUITE 200
210.349.9098
SAN ANTONIO, TEXAS 78216
TBPE FIRM F-432IES JOB NO:
ENGINEERING COMMUNITIES FROM THE GROUND UP
ie-services.com
Th
e r
eco
rd o
f th
is d
raw
ing
is o
n file
at
the
offic
es o
f S
lay A
rch
itectu
re,
12
3 A
ltg
elt A
ve
nu
e,
San
An
ton
io, T
exa
s 7
82
01
& 9
90
1 M
cP
he
rso
n R
oa
d,
Su
ite 1
04,
La
red
o,
Te
xas 7
80
45.
Th
is d
ocu
me
nt
is r
ele
ased
fo
r th
e p
urp
ose
of re
fere
nce
, co
ord
inatio
n,
an
d/o
f fa
cili
ty m
an
ag
em
en
t u
nd
er
the
au
tho
rity
of th
e n
am
ed
pro
fessio
na
l, r
eg
istr
atio
n n
um
be
r a
nd
date
on
th
e s
ea
l a
ffix
ed
ab
ove
.C
OP
YR
IGH
T 2
00
0 -
20
19
, S
lay A
rch
ite
ctu
re. T
his
do
cu
men
t w
as p
rep
are
d u
sin
g c
om
pu
ter
assis
ted
desig
n a
nd
dra
ftin
g e
qu
ipm
en
t a
nd
sa
ved
on
mag
netic m
ed
ia.
Ne
ith
er
the
prin
ted
do
cu
men
t n
or
the
ma
gn
etic m
ed
ia m
ay b
e a
ltere
d o
r am
en
de
d b
y a
ny p
art
y o
the
r th
an
Sla
y A
rch
ite
ctu
re.
123 Altgelt AvenueSan Antonio, Texas 78201T: 210.736.3009
9901 McPherson Avenue, #104Laredo, Texas 78045T: 956.791.0405
SAN ANTONIO
LAREDO
Project NO.:
Date:
Revisions:
19005
CD
BG
DE
LL
AN
O P
AR
K IM
PR
OV
EM
EN
TS
PR
OJE
CT
09/12/19
CIT
Y O
F L
AR
ED
O T
EX
AS
CO
NS
TR
UC
TIO
N D
OC
UM
EN
TS
1192756
September 12, 2019
Fo
ste
r A
ven
ue a
nd
San
ma
n S
tre
et
9/1
0/2
019
5:3
4:4
4 A
M
S3.1
TYPICAL CMU WALL
FRAMING DETAILS
SCALE: 3/4" = 1'-0"1 TYPICAL INTERIOR CMU PARTITION WALL REINFORCING DETAIL
SCALE: 3/4" = 1'-0"2 TYPICAL MASONRY WALL DOWEL DETAIL
SCALE: 3/4" = 1'-0"3 TYPICAL CMU LINTEL DETAIL
SCALE: 3/4" = 1'-0"4 TYPICAL CMU BOND BEAM DETAIL
SCALE: 3/4" = 1'-0"5 TYPICAL CMU BAR PLACEMENT DETAIL
SCALE: 3/4" = 1'-0"6 TYPICAL CORNER BARS AT BOND BEAMS DETAIL