Bristol Warren totals 551,283 square feet and consists of the school type(s) detailed below. School(s) were visited three times during the Statewide Facilities Assessment by teams of specialists from April-July 2016. This report provides LEA summary findings for the statewide assessment program.
School Type SqFtElementary School 223,636Middle School 149,915High School 177,732Total: 551,283
DemographicsEnrollment is projected to decrease by 12.6% over the next 10 years in Bristol Warren. The total LEA enrollment at 6 school(s) is 3,288 students with a total capacity of 4,098 as reported by the LEA. Utilization is calculated by dividing enrollment by capacity, resulting in 80.2% utilization at Bristol Warren.
Educational Program Space AnalysisIn Bristol Warren there are 272 instructional spaces; of these spaces 25.7% meet or exceed the space size standards. Of the total current deficiencies identified, $4,742,060 are related to the educational program space assessment. Addressing these identified deficiencies will improve the learning environment and bring the school(s) in the district closer to 21st century learning facilities.
Five Year Need SummaryThe current deficiencies total $49,471,548, with 43.3% categorized as Priority 3 and another 24.4% as Priority 4. The building systems with the highest current deficiency costs are Interior and Technology.
The projected life cycle need in Years 1 through 5 is $10,060,814. It is anticipated that the majority of the need will occur in Year 5. School(s) with the greatest need are represented in the adjacent table and make up 77.0% of the combined 5-Year need at Bristol Warren.
Five Year Facility Condition Index (FCI)For master planning purposes, the total current deficiencies, less new construction, and the first 5 years of projected life cycle needs were combined. This provides an understanding of the current needs of a facility as well as the projected needs in the near future. A 5-Year FCI was calculated by dividing the 5-Year need by the total replacement cost. The 5-Year need is $59,532,362 with a district replacement value of $192,019,672. The resulting 5-Year FCI is 31.0%.
School(s) with Greatest Need Combined 5-Year Need
Mt. Hope High School $22,406,303
Kickemuit Middle School $16,193,355
Hugh Cole School $7,256,649
80.2 % Utilization
LEA Summary Data
Gross SqFt Avg Year BuiltCurrent Deficiencies
(Less New Construction)Life Cycle Year 1-5
TotalTotal 5-Year Need
(Year 1-5 + Current Defs) 5-Year FCI551,283 1946 $49,471,548 $10,060,814 $59,532,362 31.0%
M▪A▪P▪P▪S ©, Jacobs 2017
LEA SummaryBristol Warren
570-574 Hope Street, Bristol, RI 02809
Facility Condition AssessmentBristol Warren - Colt Andrews School June 2017
1M▪A▪P▪P▪S ©, Jacobs 2017
Colt Andrews School, located at 570-574 Hope Street in Bristol, Rhode Island, was built in 1906. It comprises 71,300 gross square feet. Each school across the district was visited three times during the Facility Condition Assessments by three teams of specialists in the spring/summer of 2016.
For master planning purposes a 5-year need was developed to provide an understanding of the current need as well as the projected needs in the near future. For Colt Andrews School the 5-year need is $3,620,454. The findings contained within this report resulted from an assessment of building systems performed by building professionals experienced in disciplines including: architecture, mechanical, plumbing, electrical, acoustics, hazardous materials, and technology infrastructure.
Figure 1: Aerial view of Colt Andrews School
Introduction
Colt Andrews School serves grades KG - 5, has 32 instructional spaces, and has an enrollment of 368. Instructional spaces are defined as rooms in which a student receives education. The LEA reported capacity for Colt Andrews School is 432 with a resulting utilization of 85%.
2M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Approach and MethodologyA facility condition assessment evaluates each building’s overall condition. Two components of the facility condition assessment are combined to total the cost for facility need. The two components of the facility condition assessment are current deficiencies and life cycle forecast.
Current Deficiencies: Deficiencies are items in need of repair or replacement as a result of being broken, obsolete, or beyond useful life. The existing deficiencies that currently require correction are identified and assigned a priority. An example of a current deficiency might include a broken lighting fixture or an inoperable roof top air conditioning unit.
Life Cycle Forecast: Life cycle analysis evaluates ages of a building's systems to forecast system replacement as they reach the end of serviceable life. An example of a life cycle system replacement is a roof with a 20-year life that has been in place for 15 years and may require replacement in five years.
Discipline Specialists
All assessment teams produced current deficiencies associated with each school. The assessment for the school facilities at the Rhode Island Department of Education included several specialties:
Facility Condition Assessment: Architectural, mechanical, and electrical engineering professionals observed conditions via a visual observation that did not include intrusive measures, destructive investigations, or testing. Additionally, the assessment incorporated input provided by district facilities and maintenance staff where applicable. The assessment team recorded existing conditions, identified problems and deficiencies, documented corrective action and quantities, and identified the priority of the repair in accordance with parameters defined during the planning phase. The team took digital photos at each school to better identify significant deficiencies.
Technology: Technology specialists visited RIDE facilities and met with technology directors to observe and assess each facility's technology infrastructure. The assessment included network architecture, major infrastructure components, classroom instructional systems, necessary building space and support for technology. The technology assessment took into account the desired technology outcome and best practices and processes to ensure results can be attained effectively.
Hazardous Materials: Schools constructed prior to 1990 were assessed by specialists to identify the presence of hazardous materials. The team focused on identifying asbestos containing building materials (ACBMs), lead-based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. If sampling and analysis was required, these activities were recommended but not included in the scope of work.
Traffic: A traffic specialist performed an in-office review of aerial imagery of the traffic infrastructure around the facilities in accordance with section 1.05-7 in the Rhode Island School Construction Regulations and reviewed data collected on site during the facility condition assessment. Based on this information, deficiencies and corrective actions were identified. High problem areas were identified for consideration of more detailed site-specific study and analysis in the future.
Acoustics: Specialists assessed each school's acoustics, including architectural acoustics, mechanical system noise and vibration, and environmental noise. The assessment team evaluated room acoustics with particular attention to the intelligibility of speech in learning spaces, interior and exterior sound isolation, and mechanical system noise and vibration control.
Educational Program Space Assessment: Teams evaluated schools to ensure that that all spaces adequately support the districts educational program. Standards are established for each classroom type or instructional space. Each space is evaluated to determine if it meets those standards and a listing of alterations that should be made to make the space a better environment for teaching and learning was created.
3M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
System Summaries
Building Envelope
The exterior systems for the building(s) at this campus includes:01 - Colt School: Fiber Cement Exterior Wall
Wood Exterior WindowsSteel Exterior Entrance Doors
02 - Andrews School: Brick Exterior Wall Vinyl on Wood Frame Exterior WindowsStorefront Entrance Doors
The roofing for the building(s) at this campus consists of:01 - Colt School: Clay Tile Roofing02 - Andrews School: Composition Shingle Roofing
Site
The site level systems for this campus include:Site Asphalt Parking Lot Pavement
Concrete Pedestrian Pavement
Interior
The interior systems for the building(s) at this campus include:01 - Colt School: Wood Interior Doors
Steel Interior DoorsInterior Door Hardware Suspended Acoustical Grid SystemSuspended Acoustical Ceiling TilePainted CeilingsCeramic Tile WallBrick/Stone Veneer Interior Wall PaintingConcrete FlooringCeramic Tile FlooringWood FlooringVinyl Composition Tile FlooringCarpet
02 - Andrews School: Wood Interior DoorsOverhead Interior Coiling DoorsInterior Door Hardware
The following tables summarize major building systems at the Colt Andrews School campus, identified by discipline and building.
4M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
02 - Andrews School: Suspended Acoustical Grid SystemPainted CeilingsCeramic Tile WallAcoustical Wall PanelingBrick/Stone Veneer Interior Wall PaintingConcrete FlooringCeramic Tile FlooringVinyl Composition Tile FlooringEpoxy Coated FlooringCarpetAthletic/Sport Flooring
Mechanical
The mechanical systems for the building(s) at this campus include:
01 - Colt School: 1,275 MBH Cast Iron Water Boiler 3,264 MBH Cast Iron Water Boiler Steam/Hot Water Heating Unit VentDDC Heating System Controls1 Ton Ductless Split System5 HP VFD 5 HP Pump 2-Pipe Hot Water Hydronic Distribution System 15,000 CFM Interior AHU 15,000 CFM Outdoor AHUDuctworkKitchen Exhaust HoodsRoof Exhaust FanFire Sprinkler System
02 - Andrews School: 1,275 MBH Cast Iron Water Boiler Finned Wall Radiator Steam/Hot Water Heating Unit VentElectronic Heating System Controls1 Ton Ductless Split System3 Ton Outside Air Cooled Condenser2-Pipe Hot Water Hydronic Distribution System 5 HP Pump Ductwork15,000 CFM Interior AHU 15,000 CFM Outdoor AHURoof Exhaust FanSupply Fan
5M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
02 - Andrews School: Fire Sprinkler System
Electrical
The electrical systems for the building(s) at this campus include:01 - Colt School: 208/120v Switch
1,200 Amp SwitchgearPanelboard - 120/208 125APanelboard - 120/208 225ABuilding Mounted Lighting Fixtures Light Fixtures
02 - Andrews School: 208/120v Switch 1,600 Amp SwitchgearPanelboard - 120/208 125APanelboard - 120/208 225APanelboard - 120/208 400ABuilding Mounted Lighting Fixtures
Plumbing
The plumbing systems for the building(s) at this campus include:01 - Colt School: 2" Backflow Preventers
Gas Piping System100 Gallon Gas Water Heater
02 - Andrews School: 2" Backflow PreventersGas Piping System100 Gallon Gas Water Heater
01 - Colt School: Domestic Water Piping System 02 - Andrews School: Domestic Water Piping System 01 - Colt School: Classroom Lavatories
Mop/Service SinksRefrigerated Drinking FountainRestroom LavatoriesToiletsUrinals
02 - Andrews School: Classroom LavatoriesMop/Service SinksRefrigerated Drinking FountainRestroom LavatoriesToiletsUrinals
01 - Colt School: Sump Pump02 - Andrews School: Sump Pump01 - Colt School: Air Compressor (5 hp)
6M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
02 - Andrews School: Light Fixtures
7M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Facility Deficiency Priority Levels
Deficiencies were ranked according to five priority levels, with Priority 1 items being the most critical to address:
Priority 1 – Mission Critical Concerns: Deficiencies or conditions that may directly affect the school’s ability to remain open or deliver the educational curriculum. These deficiencies typically relate to building safety, code compliance, severely damaged or failing building components, and other items that require near-term correction. An example of a Priority 1 deficiency is a fire alarm system replacement.
Priority 2 – Indirect Impact to Educational Mission: Items that may progress to a Priority 1 item if not addressed in the near term. Examples of Priority 2 deficiencies include inadequate roofing that could cause deterioration of integral building systems, and conditions affecting building envelopes, such as roof and window replacements.
Priority 3 – Short-Term Conditions: Deficiencies that are necessary to the school's mission but may not require immediate attention. These items should be considered necessary improvements required to maximize facility efficiency and usefulness. Examples of Priority 3 items include site improvements and plumbing deficiencies.
Priority 4 – Long-Term Requirements: Items or systems that may be considered improvements to the instructional environment. The improvements may be aesthetic or provide greater functionality. Examples include cabinets, finishes, paving, removal of abandoned equipment, and educational accommodations associated with special programs.
Priority 5 – Enhancements: Deficiencies aesthetic in nature or considered enhancements. Typical deficiencies in this priority include repainting, replacing carpet, improved signage, or other improvements to the facility environment.
8M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Table 1: System by Priority
Priority
System 1 2 3 4 5 Total % of Total
Site - - $151,087 $175,819 $69,827 $396,734 12.93 %
Roofing - - - - - $0 0.00 %
Structural - - - - - $0 0.00 %
Exterior - $350 - - - $350 0.01 %
Interior - - $421,535 $146,708 $97,620 $665,864 21.70 %
Mechanical - $259,702 - - - $259,702 8.46 %
Electrical - - - - $57,567 $57,567 1.88 %
Plumbing - - $271,079 - $17,375 $288,454 9.40 %
Fire and Life Safety - - - - - $0 0.00 %
Technology - - $1,390,561 - - $1,390,561 45.32 %
Conveyances - - - - - $0 0.00 %
Specialties - - $9,127 - - $9,127 0.30 %
Total $0 $260,052 $2,243,389 $322,528 $242,389 $3,068,358
*Displayed totals may not sum exactly due to mathematical rounding
The following chart summarizes this site's current deficiencies by building system and priority. The listing details current deficiencies including deferred maintenance, functional deficiencies, code compliance, capital renewal, hazardous materials and technology categories.
The building systems with the most need include:Technology - $1,390,561Interior - $665,864Site - $396,734
The chart below represents the building systems and associated deficiency costs.
Figure 2: System Deficiencies
9M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Current Deficiencies by Category
Deficiencies have been further grouped according to the observed category.
• Acoustics deficiencies relate to room acoustics, sound insolation, and mechanical systems and vibration control modeled after ANSI/ASA Standard S12.60-2010 and ASHRAE Handbook, Chapter 47 on Sound and Vibration Control.
• Barrier to Accessibility deficiencies relate to the Americans with Disabilities Act and the Rhode Island Governors Commission on Disability. Additional items related to accessibility may be included other categories.
• Capital Renewal items have reached or exceeded serviceable life and require replacement. These are current and do not include life cycle capital renewal forecasts. Also included are deficiencies correcting planned work postponed beyond its regular life expectancy.
• Code Compliance deficiencies related to current codes. Many may fall under grandfather clauses, which allow buildings to continue operating under codes effective at the time of construction. However, there are instances where the level of renovation requires full compliance which are reflected in the master plan.
• Educational Adequacy deficiencies identify where facilities do not align with the Basic Education Program and the RIDE School Construction Regulations. • Functional Deficiencies are deficiencies for components or systems that have failed before the end of expected life or are not the right application, size, or design.
• Hazardous Materials include deficiencies for building systems or components containing potentially hazardous material. The team focused on identifying asbestos containing building materials (ACBMs), lead based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. With other scopes of work there may be other costs associated with hazardous materials.
• Technology deficiencies relate to network architecture, technology infrastructure, classroom systems, and support. Examples of technology deficiencies include: security cameras, secure electronic access, telephone handsets, and dedicated air conditioning for telecommunication rooms.
• Traffic deficiencies relate to vehicle or pedestrian traffic, such as bus loops, crosswalks, and pavement markings.
10M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Table 2: Deficiency Category by PriorityPriority
Category 1 2 3 4 5 Total
Acoustics - - - $3,708 - $3,708
Barrier to Accessibility - - - - - $0
Capital Renewal - $260,052 $687,619 $238,542 $88,379 $1,274,593
Code Compliance - - - - - $0
Educational Adequacy - - $31,943 $28,329 $154,010 $214,282
Functional Deficiency - - $4,995 - - $4,995
Hazardous Material - - - $51,949 - $51,949
Technology - - $1,367,744 - - $1,367,744
Traffic - - $151,087 - - $151,087
Total $0 $260,052 $2,243,389 $322,528 $242,389 $3,068,358
*Displayed totals may not sum exactly due to mathematical rounding
The following chart and table represent the deficiency category by priority. This listing includes current deficiencies for all building systems.
11M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Life Cycle Capital Renewal Projections
System Current DeficienciesYear 12017
Year 22018
Year 32019
Year 42020
Year 52021 LC Yr. 1-5 Total Total 5-Year Need
Site $396,734 $0 $0 $0 $0 $74,154 $74,154 $470,888
Roofing $0 $0 $0 $0 $0 $0 $0 $0
Structural $0 $0 $0 $0 $0 $0 $0 $0
Exterior $350 $0 $0 $0 $0 $0 $0 $350
Interior $665,864 $0 $43,730 $0 $0 $211,978 $255,708 $921,572
Mechanical $259,702 $0 $0 $0 $0 $0 $0 $259,702
Electrical $57,567 $0 $0 $0 $0 $0 $0 $57,567
Plumbing $288,454 $0 $0 $5,322 $0 $5,322 $10,644 $299,098
Fire and Life Safety $0 $0 $0 $0 $208,980 $0 $208,980 $208,980
Technology $1,390,561 $0 $0 $0 $0 $0 $0 $1,390,561
Conveyances $0 $0 $0 $0 $0 $0 $0 $0
Specialties $9,127 $0 $0 $0 $0 $0 $0 $9,127
Total $3,068,358 $0 $43,730 $5,322 $208,980 $291,454 $549,486 $3,617,844
*Displayed totals may not sum exactly due to mathematical rounding
Life Cycle Capital Renewal ForecastDuring the facility condition assessment, assessors inspected all major building systems. If a need for immediate replacement was identified, a deficiency was created with the estimated repair costs. The identified deficiency contributes to the facility's total current repair costs.
Capital planning scenarios span multiple years, as opposed to being constrained to immediate repairs. Construction projects may begin several years after the initial facility condition assessment. Therefore, in addition to the current year repair costs, it is necessary to forecast the facility's future costs using a 5-year life cycle renewal forecast model.
Life cycle renewal is the projection of future building system costs based upon each individual system’s expected serviceable life. Building systems and components age over time, eventually break down, reach the end of their useful lives, and may require replacement. While an item may be in good condition now, it might reach the end of its life before a planned construction project occurs.
The following chart shows all current deficiencies and the subsequent 5-year life cycle capital renewal projections. The projections outline costs for major building systems in which a component is expected to reach the end of its useful life and require capital funding for replacement.
Table 3: Capital Renewal Forecast
12M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Facility Condition Index (FCI)The Facility Condition Index (FCI) is used throughout the facility condition assessment industry as a general indicator of a building’s health. Since 1991, the facility management industry has used an index called the FCI to benchmark the relative condition of a group of schools. The FCI is derived by dividing the total repair cost, including educational adequacy and site-related repairs, by the total replacement cost. A facility with a higher FCI percentage has more need, or higher priority, than a facility with a lower FCI. It should be noted that costs in the New Construction category are not included in the FCI calculation.
For master planning purposes, the total current deficiencies and the first five years of projected life cycle needs were combined. This provides an understanding of the current needs of a facility as well as the projected needs in the near future. A 5-year FCI was calculated by dividing the 5-year need by the total replacement cost. Costs associated with new construction are not included in the FCI calculation.
Figure 5: 5-Year FCI
Financial modeling has shown that over a 30-year period, it is more cost effective to replace than repair schools with a FCI of 65 percent or greater. This is due to efficiency gains with facilities that are more modern and the value of the building at the end of the analysis period. It is important to note that the FCI at which a facility should be considered for replacement is typically debated and adjusted based on property owners and facility managers approach to facility management. Of course, FCI is not the only factor used to identify buildings that need renovation, replacement, or even closure. Historical significance, enrollment trends, community sentiment, and the availability of capital are additional factors that are analyzed when making school facility decisions.
The replacement value represents the estimated cost of replacing the current building with another building of like size, based on today’s estimated cost of construction in the Providence, Rhode Island area. The estimated replacement cost for this facility is $24,955,000. For planning purposes, the total 5-year need at the Colt Andrews School is $3,620,454 (Life Cycle Years 1-5 plus the FCI deficiency cost). The Colt Andrews School facility has a 5-year FCI of 14.50%.
It is important to reiterate that this FCI replacement threshold is not conclusive, but is intended to initiate planning discussion in which other relevant issues with regard to a facility’s disposition must be incorporated. This merely suggests where conversations regarding replacement might occur.
13M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
The capacity of a school reflects how many students the school’s physical facility can effectively serve. There are various methodologies that exist to calculate capacity. It is not uncommon to review an existing building only to find that the capacity that had once been assigned is greater than what can be reasonably accommodated today. This is primarily because of a change in how programs are delivered.
The Rhode Island Aspirational Capacity is based on the Rhode Island School Construction Regulations (SCRs) and is an aspirational goal of space use. The capacity for each individual public school in the state of Rhode Island was designed to conform to Section 1.06-2 Space Allowance Guidelines of the Rhode Island Department of Education (RIDE) SCRs. These regulations outline the allowed gross square feet (GSF) per student at each school type (ES, MS, HS) by utilizing a sliding scale based on projected enrollment. The resulting capacities reflect how school capacities align to the SCRs for new construction. The existing enrollment was multiplied by the GSF per student for the appropriate bracket. For the purposes of this analysis, Pre-K centers were rolled into the elementary totals, and K-8 facilities were counted as middle schools.
The most consistent and equitable way a state can determine school capacities across a variety of districts and educational program offerings is to use square-foot-per-student standards. In contrast, in the 2013 Public Schoolhouse Assessment Report, LEAs self-reported capacities for their elementary, middle and high schools. Districts typically report “functional capacity,” which is defined as the number of students each classroom can accommodate. Functional capacity counts how many students can occupy a space, not how much room students and teachers have within that space. For example, a 650-square-foot classroom and a 950-square-foot classroom can both have a reported capacity of 25 students, but the actual teaching and learning space per student varies greatly.
The variation in square feet per student impacts the kinds of teaching practices possible in each space. The lowest allocation of space per student restricts group and project-based learning strategies and requires teachers to teach in more traditional, lecture-style formats, due to a lack of space. Furthermore, the number of students that can be accommodated in a classroom does not account for access to sufficient common spaces such as libraries, cafeterias, and gymnasiums. When cafeterias are undersized relative to the population, schools must host four or more lunch periods a day, resulting in some students eating lunch mid-morning and some mid-afternoon. Similarly, undersized libraries and gymnasiums create scheduling headaches for schools and restrict student access. Finally, a classroom count-only approach to school capacity does not consider the inherent scheduling challenges schools face.
Rhode Island Aspirational Capacity
Applying the Rhode Island Aspirational Capacity, a facility of this size could ideally support an enrollment of approximately 430 students.
As part of the Educational Program Space Assessment, select core spaces were compared to the RI School Construction Regulations. If it was determined that a facility was in need of square footage related to a cafeteria or library/media center, a cost for additional space was estimated. This cost is not included in the total 5-year need or the 5-year FCI calculation.
Facility New Construction
The New Construction cost to bring the Colt Andrews School cafeteria and/or library/media center to the size prescribed by the SCRs is estimated to be $353,430.
14M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Table 4: Facility Condition by Building
Gross Sq Ft Year BuiltCurrent
Deficiencies LC Yr. 1-5 TotalTotal 5 Yr Need
(Yr 1-5 + Current Defs) 5-Year FCI
Colt Andrews School Totals 71,300 1906 $3,070,968 $549,486 $3,620,454 14.50%
*Displayed totals may not sum exactly due to mathematical rounding
The following pages provide a listing of all current deficiencies and 5-year life cycle need and the associated costs, followed by photos taken during the assessment.
The Colt Andrews School comprises 71,300 square feet and was constructed in 1906. Current deficiencies at this school total $3,070,968. Five year capital renewal costs total $549,486. The total identified need for the Colt Andrews School (current deficiencies and 5-year capital renewal costs) is $3,620,454. The 5-year FCI is 14.50%.
Summary of Findings
Cost estimates are derived from local cost estimating expertise and enhanced by industry best practices, historical cost data, and relevance to the Rhode Island region. Costs have been developed from current market rates as of the 2nd quarter in 2016. All costs are based on a replace-in-kind approach, unless the item was not in compliance with national or state regulations or standards. For planning and budgeting purposes, facility assessments customarily add a soft cost multiplier onto deficiency repair cost estimates. This soft cost multiplier accounts for costs that are typically incurred when contracting for renovation and construction services. Soft costs typically include construction cost factors, such as contractor overhead and profit, as well as labor and material inflation, professional fees, and administrative costs. Based on the Rhode Island School Construction Regulations, a soft cost multiplier of 20% is included on all cost estimates. Other project allowances are included in the cost estimates based on school attributes such as age, location, and historic designation. All stated costs in the assessment report will include soft costs for planning and budgeting purposes. These are estimates, and costs will vary at the time of construction.
Cost Estimating
15M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Site Level DeficienciesSiteDeficiency Category Qty UoM Priority Repair Cost ID
Traffic Signage Is Required Traffic 4 Ea. 3 $151,087 9292
Note: Add school zone signs on adjacent roadways (2 on Hope St, 2 on Bradford St)
Asphalt Paving Requires Replacement Capital Renewal 30 CAR 4 $98,587 11431
Backstops Require Replacement Educational Adequacy
1 Ea. 4 $28,329 28405
Note: Backstops Require Replacement
Fencing Requires Replacement (4' Chain Link Fence) Capital Renewal 750 LF 4 $48,159 11430
Exterior Basketball Goals are Required Educational Adequacy
1 Ea. 5 $5,807 28687
Note: Exterior Basketball Goals are Required
PE / Recess Playfield is Missing and is Needed Educational Adequacy
1 Ea. 5 $64,020 54859
Note: PE / Recess Playfield is Missing and is Needed
Sub Total for System 6 items $395,990
Sub Total for School and Site Level 6 items $395,990
Building: 01 - Colt SchoolExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Glass Pane In The Storefront Window Requires Replacement Capital Renewal 10 SF 2 $350 9669
Note: First floor office interior window is cracked and should be replaced.
Sub Total for System 1 items $350
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Interior Doors Require Replacement Functional Deficiency 1 Door 3 $4,995 9663
Note: Lower level boy's restroom door is swelling and delaminating.
The Vinyl Composition Tile Requires Replacement Capital Renewal 4,300 SF 3 $53,439 9664
Note: There are cracks in the VCT floor at the 1st floor lobby, 2nd floor corridor, and north stairwell 2nd landing.
Interior Gypsum Board Walls Require Repair Capital Renewal 2,000 SF Wall
4 $15,835 9666
Location: Girl's restroom, VP office, Room C117
Classroom Door Requires Vision Panel Educational Adequacy
1 Ea. 5 $2,282 Rollup
Room lacks appropriate sound control. Educational Adequacy
200 SF 5 $6,959 Rollup
The Gypsum Board Ceilings Require Repainting Capital Renewal 5,449 SF 5 $24,693 Rollup
Sub Total for System 6 items $108,203
MechanicalDeficiency Category Qty UoM Priority Repair Cost ID
The Mechanical / HVAC Piping / System Is Beyond Its Useful Life Capital Renewal 31,100 SF 2 $259,702 9668
Sub Total for System 1 items $259,702
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
Room Has Insufficient Electrical Outlets Educational Adequacy
36 Ea. 5 $17,866 Rollup
Sub Total for System 1 items $17,866
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Capital Renewal 31,100 SF 3 $271,079 9667
Note: Replace pipes and insulation.
The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed Educational Adequacy
1 Ea. 5 $1,512 Rollup
Sub Total for System 2 items $272,591
16M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks Interactive White Board Educational Adequacy
1 Ea. 3 $5,704 Rollup
Sub Total for System 1 items $5,704
SpecialtiesDeficiency Category Qty UoM Priority Repair Cost ID
Room has insufficient writing area. Educational Adequacy
1 Ea. 3 $4,563 Rollup
Sub Total for System 1 items $4,563
Sub Total for Building 01 - Colt School 13 items $668,979
Building: 02 - Andrews SchoolSiteDeficiency Category Qty UoM Priority Repair Cost ID
Bleachers Require Repainting Capital Renewal 165 Seat 4 $744 9659
Sub Total for System 1 items $744
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Vinyl Composition Tile Requires Replacement Capital Renewal 29,217 SF 3 $363,101 9661
Note: VCT is aged and chipped with cracks and stains.
Interior Gypsum Board Walls Require Repair Capital Renewal 9,500 SF Wall
4 $75,216 9658
Note: There are cracks in the gypboard wall in the stairwells, damage to corners, and various chips in walls.
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - each)
Hazardous Material 12 Ea. 4 $3,708 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - linear feet)
Hazardous Material 460 LF 4 $11,370 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - square feet)
Hazardous Material 3,580 SF 4 $36,871 Rollup
Partitions Provide Insufficient Sound Isolation Acoustics 120 SF 4 $3,708 19686
Note: Principal Office
The Exposed Ceilings Require Repainting Capital Renewal 5,153 SF 5 $63,686 9660
Note: Gym ceiling shows flaking paint.
Sub Total for System 7 items $557,660
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
Room Has Insufficient Electrical Outlets Educational Adequacy
80 Ea. 5 $39,701 Rollup
Sub Total for System 1 items $39,701
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks a drinking fountain. Educational Adequacy
7 Ea. 5 $7,720 Rollup
The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed Educational Adequacy
8 Ea. 5 $8,143 Rollup
Sub Total for System 2 items $15,863
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks Interactive White Board Educational Adequacy
3 Ea. 3 $17,113 Rollup
Technology: Campus network switching electronics are antiquated and/or do not meet standards.
Technology 288 Ea. 3 $148,309 18346
Technology: Campus wireless infrastructure inadequate. Technology 46 Ea. 3 $66,327 18345
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 1 Ea. 3 $21,628 18352
Technology: Instructional spaces do not have local sound reinforcement. Technology 40 Ea. 3 $205,984 18355
17M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Technology: Intermediate Telecommunications Room grounding system is inadequate or non-existent.
Technology 4 Ea. 3 $23,070 18343
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $40,785 18340
Technology: Intermediate Telecommunications Room needs M/E improvements. Technology 3 Ea. 3 $79,098 18341
Technology: Intermediate Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 4 Ea. 3 $20,598 18342
Technology: Main Telecommunications Room ground system is inadequate or non-existent. Technology 2 Ea. 3 $14,419 18338
Technology: Main Telecommunications Room needs M/E improvements. Technology 1 Ea. 3 $31,722 18336
Technology: Main Telecommunications Room needs minor improvements. Technology 1 Ea. 3 $23,482 18335
Technology: Main Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 2 Ea. 3 $19,569 18337
Technology: Network cabling infrastructure is outdated (Cat 5 or less) and/or does not meet standards.
Technology 103 Ea. 3 $47,737 18347
Technology: Network cabling infrastructure is partially outdated and/or needs expansion. Technology 144 Ea. 3 $66,739 18351
Technology: Network system inadequate and/or near end of useful life Technology 48 Ea. 3 $247,181 18354
Technology: PA/Bell/Clock system is inadequate and/or near end of useful life. Technology 71,032 SF 3 $131,683 18353
Technology: Special Space AV/Multimedia system is inadequate. Technology 1 Ea. 3 $58,706 18348
Technology: Telecommunications Room (large size room) needs dedicated cooling system improvements.
Technology 2 Ea. 3 $16,479 18339
Technology: Telecommunications Room (small size room) needs dedicated cooling system improvements.
Technology 4 Ea. 3 $20,598 18344
Technology: Telephone handsets are inadequate and sparsely deployed throughout the campus.
Technology 46 Ea. 3 $75,802 18349
Technology: Telephone system is inadequate and/or non-existent. Technology 1 Ea. 3 $7,827 18350
Sub Total for System 22 items $1,384,856
SpecialtiesDeficiency Category Qty UoM Priority Repair Cost ID
Room has insufficient writing area. Educational Adequacy
1 Ea. 3 $4,563 Rollup
Sub Total for System 1 items $4,563
Sub Total for Building 02 - Andrews School 34 items $2,003,389
Total for Campus 53 items $3,068,358
18M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Colt Andrews School - Life Cycle Summary Yrs 1-5Site Level Life Cycle Items
SiteUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Fences and Gates Wood 300 LF $74,154 5
Note: Andrews School
Sub Total for System 1 items $74,154
Sub Total for Building - 1 items $74,154
Building: 01 - Colt School
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Suspended Plaster and Painted ceilings 10,898 SF $45,587 5
Wall Painting and Coating Painting/Staining (Bldg SF) 12,440 SF $82,195 5
Carpeting Carpet 3,870 SF $84,196 5
Sub Total for System 3 items $211,979
PlumbingUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Domestic Water Equipment Water Heater - Gas - 100 Gallon 1 Ea. $5,322 5
Note: 120 gallons
Sub Total for System 1 items $5,322
Fire and Life SafetyUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Fire Detection and Alarm Fire Alarm 31,100 SF $91,154 4
Sub Total for System 1 items $91,154
Sub Total for Building 01 - Colt School 5 items $308,455
Building: 02 - Andrews School
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Carpeting Carpet 2,010 SF $43,730 2
Sub Total for System 1 items $43,730
PlumbingUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Domestic Water Equipment Water Heater - Gas - 100 Gallon 1 Ea. $5,322 3
Note: 120 gallon
Sub Total for System 1 items $5,322
Fire and Life SafetyUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Fire Detection and Alarm Fire Alarm 40,200 SF $117,826 4
Sub Total for System 1 items $117,826
Sub Total for Building 02 - Andrews School 3 items $166,878
Total for: Colt Andrews School 9 items $549,487
19M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Supporting Photos
Typical Damage to Walls
Main Entry
Computer Lab
Gypsum Board Wall Damage
20M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Typical Lockers
Site Aerial
Cracked VCT
Typical Classroom
Stained VCT
Faded Paint At Bleachers
21M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Damage To Wall Corner
Lobby Plaque
Lockers
Kitchen
Restroom Finishes
Entrance
22M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Andrews School Sign
Gym/Cafeteria
Play Area
Corridor Finishes
Theater
Cracked Window
23M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Aged Piping
Ceiling Paint Flaking
Delaminating Door
Chipped Gypsum Board Wall
Cracked VCT
Peeling Ceiling Paint
24M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
Library
Colt School Plaque
Colt School Sign
Cracked Gypboard Wall
25M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Colt Andrews School
35 Washington Street, Bristol, RI 02809
Facility Condition AssessmentBristol Warren - Guiteras School June 2017
1M▪A▪P▪P▪S ©, Jacobs 2017
Guiteras School, located at 35 Washington Street in Bristol, Rhode Island, was built in 1929. It comprises 38,600 gross square feet. Each school across the district was visited three times during the Facility Condition Assessments by three teams of specialists in the spring/summer of 2016.
For master planning purposes a 5-year need was developed to provide an understanding of the current need as well as the projected needs in the near future. For Guiteras School the 5-year need is $6,012,645. The findings contained within this report resulted from an assessment of building systems performed by building professionals experienced in disciplines including: architecture, mechanical, plumbing, electrical, acoustics, hazardous materials, and technology infrastructure.
Figure 1: Aerial view of Guiteras School
Introduction
Guiteras School serves grades KG - 5, has 23 instructional spaces, and has an enrollment of 303. Instructional spaces are defined as rooms in which a student receives education. The LEA reported capacity for Guiteras School is 288 with a resulting utilization of 105%.
2M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Approach and MethodologyA facility condition assessment evaluates each building’s overall condition. Two components of the facility condition assessment are combined to total the cost for facility need. The two components of the facility condition assessment are current deficiencies and life cycle forecast.
Current Deficiencies: Deficiencies are items in need of repair or replacement as a result of being broken, obsolete, or beyond useful life. The existing deficiencies that currently require correction are identified and assigned a priority. An example of a current deficiency might include a broken lighting fixture or an inoperable roof top air conditioning unit.
Life Cycle Forecast: Life cycle analysis evaluates ages of a building's systems to forecast system replacement as they reach the end of serviceable life. An example of a life cycle system replacement is a roof with a 20-year life that has been in place for 15 years and may require replacement in five years.
Discipline Specialists
All assessment teams produced current deficiencies associated with each school. The assessment for the school facilities at the Rhode Island Department of Education included several specialties:
Facility Condition Assessment: Architectural, mechanical, and electrical engineering professionals observed conditions via a visual observation that did not include intrusive measures, destructive investigations, or testing. Additionally, the assessment incorporated input provided by district facilities and maintenance staff where applicable. The assessment team recorded existing conditions, identified problems and deficiencies, documented corrective action and quantities, and identified the priority of the repair in accordance with parameters defined during the planning phase. The team took digital photos at each school to better identify significant deficiencies.
Technology: Technology specialists visited RIDE facilities and met with technology directors to observe and assess each facility's technology infrastructure. The assessment included network architecture, major infrastructure components, classroom instructional systems, necessary building space and support for technology. The technology assessment took into account the desired technology outcome and best practices and processes to ensure results can be attained effectively.
Hazardous Materials: Schools constructed prior to 1990 were assessed by specialists to identify the presence of hazardous materials. The team focused on identifying asbestos containing building materials (ACBMs), lead-based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. If sampling and analysis was required, these activities were recommended but not included in the scope of work.
Traffic: A traffic specialist performed an in-office review of aerial imagery of the traffic infrastructure around the facilities in accordance with section 1.05-7 in the Rhode Island School Construction Regulations and reviewed data collected on site during the facility condition assessment. Based on this information, deficiencies and corrective actions were identified. High problem areas were identified for consideration of more detailed site-specific study and analysis in the future.
Acoustics: Specialists assessed each school's acoustics, including architectural acoustics, mechanical system noise and vibration, and environmental noise. The assessment team evaluated room acoustics with particular attention to the intelligibility of speech in learning spaces, interior and exterior sound isolation, and mechanical system noise and vibration control.
Educational Program Space Assessment: Teams evaluated schools to ensure that that all spaces adequately support the districts educational program. Standards are established for each classroom type or instructional space. Each space is evaluated to determine if it meets those standards and a listing of alterations that should be made to make the space a better environment for teaching and learning was created.
3M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
System Summaries
Building Envelope
The exterior systems for the building(s) at this campus includes:01 - Main Building: Brick Exterior Wall
CMU Exterior Wall Vinyl on Wood Frame Exterior WindowsSteel Exterior Entrance DoorsStorefront Entrance Doors
The roofing for the building(s) at this campus consists of:01 - Main Building: Single Ply Roofing
Site
The site level systems for this campus include:Site Asphalt Parking Lot Pavement
Asphalt Roadway PavementConcrete Pedestrian Pavement
Interior
The interior systems for the building(s) at this campus include:01 - Main Building: Steel Interior Doors
Wood Interior DoorsInterior Door Hardware Suspended Acoustical Grid SystemSuspended Acoustical Ceiling TilePainted CeilingsCeramic Tile WallInterior Wall PaintingConcrete FlooringCeramic Tile FlooringWood FlooringVinyl Composition Tile FlooringCarpetAthletic/Sport Flooring
Mechanical
The mechanical systems for the building(s) at this campus include:
01 - Main Building: 3,264 MBH Cast Iron Water Boiler
The following tables summarize major building systems at the Guiteras School campus, identified by discipline and building.
4M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
01 - Main Building: Finned Wall Radiator Steam/Hot Water Heating Unit VentDDC Heating System Controls2-Pipe Hot Water Hydronic Distribution System 5 HP Pump 5 Ton DX Gas Roof Top Unit10,000 CFM Outdoor AHUDuctworkKitchen Exhaust HoodsRoof Exhaust FanFire Sprinkler System
Electrical
The electrical systems for the building(s) at this campus include:01 - Main Building: 800 Amp Distribution Panel
Panelboard - 120/208 100APanelboard - 120/208 225ALight Fixtures Building Mounted Lighting Fixtures
Plumbing
The plumbing systems for the building(s) at this campus include:01 - Main Building: 2" Backflow Preventers
Gas Piping System80 Gallon Electric Water HeaterDomestic Water Piping System Classroom LavatoriesMop/Service SinksRefrigerated Drinking FountainRestroom LavatoriesToiletsUrinalsSump Pump275 Gallon Above Ground Fuel Oil Storage Tank
5M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Facility Deficiency Priority Levels
Deficiencies were ranked according to five priority levels, with Priority 1 items being the most critical to address:
Priority 1 – Mission Critical Concerns: Deficiencies or conditions that may directly affect the school’s ability to remain open or deliver the educational curriculum. These deficiencies typically relate to building safety, code compliance, severely damaged or failing building components, and other items that require near-term correction. An example of a Priority 1 deficiency is a fire alarm system replacement.
Priority 2 – Indirect Impact to Educational Mission: Items that may progress to a Priority 1 item if not addressed in the near term. Examples of Priority 2 deficiencies include inadequate roofing that could cause deterioration of integral building systems, and conditions affecting building envelopes, such as roof and window replacements.
Priority 3 – Short-Term Conditions: Deficiencies that are necessary to the school's mission but may not require immediate attention. These items should be considered necessary improvements required to maximize facility efficiency and usefulness. Examples of Priority 3 items include site improvements and plumbing deficiencies.
Priority 4 – Long-Term Requirements: Items or systems that may be considered improvements to the instructional environment. The improvements may be aesthetic or provide greater functionality. Examples include cabinets, finishes, paving, removal of abandoned equipment, and educational accommodations associated with special programs.
Priority 5 – Enhancements: Deficiencies aesthetic in nature or considered enhancements. Typical deficiencies in this priority include repainting, replacing carpet, improved signage, or other improvements to the facility environment.
6M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Table 1: System by Priority
Priority
System 1 2 3 4 5 Total % of Total
Site - - $78,825 $28,329 $8,414 $115,568 2.83 %
Roofing - - - - - $0 0.00 %
Structural - - - - - $0 0.00 %
Exterior - - $69,322 - - $69,322 1.70 %
Interior - - $172,139 $972,867 $298,669 $1,443,675 35.32 %
Mechanical - $687,035 - $19,854 $3,260 $710,149 17.38 %
Electrical - - $94,302 - $43,671 $137,973 3.38 %
Plumbing - - $364,577 $46,109 $18,647 $429,333 10.50 %
Fire and Life Safety - - - - - $0 0.00 %
Technology - - $1,171,805 - - $1,171,805 28.67 %
Conveyances - - - - - $0 0.00 %
Specialties - - $9,127 - - $9,127 0.22 %
Total $0 $687,035 $1,960,096 $1,067,159 $372,661 $4,086,951
*Displayed totals may not sum exactly due to mathematical rounding
The following chart summarizes this site's current deficiencies by building system and priority. The listing details current deficiencies including deferred maintenance, functional deficiencies, code compliance, capital renewal, hazardous materials and technology categories.
The building systems with the most need include:Interior - $1,443,675Technology - $1,171,805Mechanical - $710,149
The chart below represents the building systems and associated deficiency costs.
Figure 2: System Deficiencies
7M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Current Deficiencies by Category
Deficiencies have been further grouped according to the observed category.
• Acoustics deficiencies relate to room acoustics, sound insolation, and mechanical systems and vibration control modeled after ANSI/ASA Standard S12.60-2010 and ASHRAE Handbook, Chapter 47 on Sound and Vibration Control.
• Barrier to Accessibility deficiencies relate to the Americans with Disabilities Act and the Rhode Island Governors Commission on Disability. Additional items related to accessibility may be included other categories.
• Capital Renewal items have reached or exceeded serviceable life and require replacement. These are current and do not include life cycle capital renewal forecasts. Also included are deficiencies correcting planned work postponed beyond its regular life expectancy.
• Code Compliance deficiencies related to current codes. Many may fall under grandfather clauses, which allow buildings to continue operating under codes effective at the time of construction. However, there are instances where the level of renovation requires full compliance which are reflected in the master plan.
• Educational Adequacy deficiencies identify where facilities do not align with the Basic Education Program and the RIDE School Construction Regulations. • Functional Deficiencies are deficiencies for components or systems that have failed before the end of expected life or are not the right application, size, or design.
• Hazardous Materials include deficiencies for building systems or components containing potentially hazardous material. The team focused on identifying asbestos containing building materials (ACBMs), lead based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. With other scopes of work there may be other costs associated with hazardous materials.
• Technology deficiencies relate to network architecture, technology infrastructure, classroom systems, and support. Examples of technology deficiencies include: security cameras, secure electronic access, telephone handsets, and dedicated air conditioning for telecommunication rooms.
• Traffic deficiencies relate to vehicle or pedestrian traffic, such as bus loops, crosswalks, and pavement markings.
8M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Table 2: Deficiency Category by PriorityPriority
Category 1 2 3 4 5 Total
Acoustics - - - $523,626 - $523,626
Barrier to Accessibility - - $41,065 - - $41,065
Capital Renewal - $687,035 $581,535 $66,200 $299,647 $1,634,418
Code Compliance - - - - - $0
Educational Adequacy - - $14,831 $385,972 $70,408 $471,211
Functional Deficiency - - $78,754 - - $78,754
Hazardous Material - - - $91,360 - $91,360
Technology - - $1,166,101 - - $1,166,101
Traffic - - $77,810 - $2,606 $80,416
Total $0 $687,035 $1,960,096 $1,067,159 $372,661 $4,086,951
*Displayed totals may not sum exactly due to mathematical rounding
The following chart and table represent the deficiency category by priority. This listing includes current deficiencies for all building systems.
9M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Life Cycle Capital Renewal Projections
System Current DeficienciesYear 12017
Year 22018
Year 32019
Year 42020
Year 52021 LC Yr. 1-5 Total Total 5-Year Need
Site $115,568 $0 $0 $0 $0 $0 $0 $115,568
Roofing $0 $0 $0 $0 $0 $0 $0 $0
Structural $0 $0 $0 $0 $0 $0 $0 $0
Exterior $69,322 $0 $0 $0 $0 $0 $0 $69,322
Interior $1,443,675 $0 $0 $213,213 $0 $0 $213,213 $1,656,888
Mechanical $710,149 $0 $0 $500,803 $19,398 $0 $520,201 $1,230,350
Electrical $137,973 $0 $0 $229,356 $0 $0 $229,356 $367,329
Plumbing $429,333 $0 $0 $1,449 $0 $836,217 $837,666 $1,266,999
Fire and Life Safety $0 $0 $0 $113,137 $0 $0 $113,137 $113,137
Technology $1,171,805 $0 $0 $0 $0 $0 $0 $1,171,805
Conveyances $0 $0 $0 $0 $0 $0 $0 $0
Specialties $9,127 $0 $0 $0 $0 $0 $0 $9,127
Total $4,086,951 $0 $0 $1,057,958 $19,398 $836,217 $1,913,573 $6,000,524
*Displayed totals may not sum exactly due to mathematical rounding
Life Cycle Capital Renewal ForecastDuring the facility condition assessment, assessors inspected all major building systems. If a need for immediate replacement was identified, a deficiency was created with the estimated repair costs. The identified deficiency contributes to the facility's total current repair costs.
Capital planning scenarios span multiple years, as opposed to being constrained to immediate repairs. Construction projects may begin several years after the initial facility condition assessment. Therefore, in addition to the current year repair costs, it is necessary to forecast the facility's future costs using a 5-year life cycle renewal forecast model.
Life cycle renewal is the projection of future building system costs based upon each individual system’s expected serviceable life. Building systems and components age over time, eventually break down, reach the end of their useful lives, and may require replacement. While an item may be in good condition now, it might reach the end of its life before a planned construction project occurs.
The following chart shows all current deficiencies and the subsequent 5-year life cycle capital renewal projections. The projections outline costs for major building systems in which a component is expected to reach the end of its useful life and require capital funding for replacement.
Table 3: Capital Renewal Forecast
10M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Facility Condition Index (FCI)The Facility Condition Index (FCI) is used throughout the facility condition assessment industry as a general indicator of a building’s health. Since 1991, the facility management industry has used an index called the FCI to benchmark the relative condition of a group of schools. The FCI is derived by dividing the total repair cost, including educational adequacy and site-related repairs, by the total replacement cost. A facility with a higher FCI percentage has more need, or higher priority, than a facility with a lower FCI. It should be noted that costs in the New Construction category are not included in the FCI calculation.
For master planning purposes, the total current deficiencies and the first five years of projected life cycle needs were combined. This provides an understanding of the current needs of a facility as well as the projected needs in the near future. A 5-year FCI was calculated by dividing the 5-year need by the total replacement cost. Costs associated with new construction are not included in the FCI calculation.
Figure 5: 5-Year FCI
Financial modeling has shown that over a 30-year period, it is more cost effective to replace than repair schools with a FCI of 65 percent or greater. This is due to efficiency gains with facilities that are more modern and the value of the building at the end of the analysis period. It is important to note that the FCI at which a facility should be considered for replacement is typically debated and adjusted based on property owners and facility managers approach to facility management. Of course, FCI is not the only factor used to identify buildings that need renovation, replacement, or even closure. Historical significance, enrollment trends, community sentiment, and the availability of capital are additional factors that are analyzed when making school facility decisions.
The replacement value represents the estimated cost of replacing the current building with another building of like size, based on today’s estimated cost of construction in the Providence, Rhode Island area. The estimated replacement cost for this facility is $13,510,000. For planning purposes, the total 5-year need at the Guiteras School is $6,012,645 (Life Cycle Years 1-5 plus the FCI deficiency cost). The Guiteras School facility has a 5-year FCI of 44.42%.
It is important to reiterate that this FCI replacement threshold is not conclusive, but is intended to initiate planning discussion in which other relevant issues with regard to a facility’s disposition must be incorporated. This merely suggests where conversations regarding replacement might occur.
11M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
The capacity of a school reflects how many students the school’s physical facility can effectively serve. There are various methodologies that exist to calculate capacity. It is not uncommon to review an existing building only to find that the capacity that had once been assigned is greater than what can be reasonably accommodated today. This is primarily because of a change in how programs are delivered.
The Rhode Island Aspirational Capacity is based on the Rhode Island School Construction Regulations (SCRs) and is an aspirational goal of space use. The capacity for each individual public school in the state of Rhode Island was designed to conform to Section 1.06-2 Space Allowance Guidelines of the Rhode Island Department of Education (RIDE) SCRs. These regulations outline the allowed gross square feet (GSF) per student at each school type (ES, MS, HS) by utilizing a sliding scale based on projected enrollment. The resulting capacities reflect how school capacities align to the SCRs for new construction. The existing enrollment was multiplied by the GSF per student for the appropriate bracket. For the purposes of this analysis, Pre-K centers were rolled into the elementary totals, and K-8 facilities were counted as middle schools.
The most consistent and equitable way a state can determine school capacities across a variety of districts and educational program offerings is to use square-foot-per-student standards. In contrast, in the 2013 Public Schoolhouse Assessment Report, LEAs self-reported capacities for their elementary, middle and high schools. Districts typically report “functional capacity,” which is defined as the number of students each classroom can accommodate. Functional capacity counts how many students can occupy a space, not how much room students and teachers have within that space. For example, a 650-square-foot classroom and a 950-square-foot classroom can both have a reported capacity of 25 students, but the actual teaching and learning space per student varies greatly.
The variation in square feet per student impacts the kinds of teaching practices possible in each space. The lowest allocation of space per student restricts group and project-based learning strategies and requires teachers to teach in more traditional, lecture-style formats, due to a lack of space. Furthermore, the number of students that can be accommodated in a classroom does not account for access to sufficient common spaces such as libraries, cafeterias, and gymnasiums. When cafeterias are undersized relative to the population, schools must host four or more lunch periods a day, resulting in some students eating lunch mid-morning and some mid-afternoon. Similarly, undersized libraries and gymnasiums create scheduling headaches for schools and restrict student access. Finally, a classroom count-only approach to school capacity does not consider the inherent scheduling challenges schools face.
Rhode Island Aspirational Capacity
Applying the Rhode Island Aspirational Capacity, a facility of this size could ideally support an enrollment of approximately 214 students.
As part of the Educational Program Space Assessment, select core spaces were compared to the RI School Construction Regulations. If it was determined that a facility was in need of square footage related to a cafeteria or library/media center, a cost for additional space was estimated. This cost is not included in the total 5-year need or the 5-year FCI calculation.
Facility New Construction
The New Construction cost to bring the Guiteras School cafeteria and/or library/media center to the size prescribed by the SCRs is estimated to be $554,904.
12M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Table 4: Facility Condition by Building
Gross Sq Ft Year BuiltCurrent
Deficiencies LC Yr. 1-5 TotalTotal 5 Yr Need
(Yr 1-5 + Current Defs) 5-Year FCI
Guiteras School Totals 38,600 1929 $4,099,072 $1,913,573 $6,012,645 44.42%
*Displayed totals may not sum exactly due to mathematical rounding
The following pages provide a listing of all current deficiencies and 5-year life cycle need and the associated costs, followed by photos taken during the assessment.
The Guiteras School comprises 38,600 square feet and was constructed in 1929. Current deficiencies at this school total $4,099,072. Five year capital renewal costs total $1,913,573. The total identified need for the Guiteras School (current deficiencies and 5-year capital renewal costs) is $6,012,645. The 5-year FCI is 44.42%.
Summary of Findings
Cost estimates are derived from local cost estimating expertise and enhanced by industry best practices, historical cost data, and relevance to the Rhode Island region. Costs have been developed from current market rates as of the 2nd quarter in 2016. All costs are based on a replace-in-kind approach, unless the item was not in compliance with national or state regulations or standards. For planning and budgeting purposes, facility assessments customarily add a soft cost multiplier onto deficiency repair cost estimates. This soft cost multiplier accounts for costs that are typically incurred when contracting for renovation and construction services. Soft costs typically include construction cost factors, such as contractor overhead and profit, as well as labor and material inflation, professional fees, and administrative costs. Based on the Rhode Island School Construction Regulations, a soft cost multiplier of 20% is included on all cost estimates. Other project allowances are included in the cost estimates based on school attributes such as age, location, and historic designation. All stated costs in the assessment report will include soft costs for planning and budgeting purposes. These are estimates, and costs will vary at the time of construction.
Cost Estimating
13M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Site Level DeficienciesSiteDeficiency Category Qty UoM Priority Repair Cost ID
Concrete Walks Require Replacement Capital Renewal 50 SF 3 $1,015 8766
Note: Concrete is spalling at the west side of the building.
Crosswalk Requires Repainting Traffic 3 Ea. 3 $2,266 9325
Note: Repaint crosswalks at front of school
Traffic Signage Is Required Traffic 2 Ea. 3 $75,544 9327
Note: Add flashing beacon to school zone signs on adjacent roadway
Backstops Require Replacement Educational Adequacy
1 Ea. 4 $28,329 28406
Note: Backstops Require Replacement
Exterior Basketball Goals are Required Educational Adequacy
1 Ea. 5 $5,807 28688
Note: Exterior Basketball Goals are Required
Paving Requires Restriping Traffic 46 CAR 5 $2,606 9326
Note: Paint parking spots in lots around school
Sub Total for System 6 items $115,568
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
The Pole Lighting Is Missing And Needed Functional Deficiency 4 Ea. 3 $78,754 8767
Note: School does not have any pole lighting. School has four building mounted fixtures that partially illuminate the parking lot. Light poles should be installed to provide sufficient illumination.
Sub Total for System 1 items $78,754
Sub Total for School and Site Level 7 items $194,322
Building: 01 - Main BuildingExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Brick Exterior Requires Repair Capital Renewal 1,000 SF Wall
3 $69,322 9281
Sub Total for System 1 items $69,322
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Interior CMU Walls Require Repair Capital Renewal 750 SF 3 $28,372 8787
Note: Cracked walls should be repaired.
Location: Rooms 209, 107, B2 restroom, 3rd boy's restroom, 2nd corridor
The Acoustical Ceiling Tiles Require Replacement Capital Renewal 250 SF 3 $2,352 8768
Note: There are several stained or broken acoustical tiles.
Location: Rooms: 205, 207, 105, 3rd floor resource office, social worker, cafe, 1st floor custodial closet, all 3 floor corridors
The Carpet Flooring Requires Replacement Capital Renewal 2,528 SF 3 $57,291 8769
Location: Stairwell entries and library
The Ceramic Tile Flooring Requires Replacement Capital Renewal 40 SF 3 $1,119 8772
Location: 3rd floor boy's restroom
The Vinyl Composition Tile Requires Replacement Capital Renewal 5,500 SF 3 $65,724 8770
Location: All corridors, Rooms 205, 206, 207, 202, 204, 107, 108, 101, 102, 104, principal, nurse, cafe, custodial closet
The Wood Flooring Requires Replacement Capital Renewal 500 SF 3 $17,281 8771
Location: Stairwell and gym
Paint (probable pre-1978 in base (layers(s)) - large areas (> 10 sq. ft.) of peeling/damage & area in active use - children (measurement unit - each)
Hazardous Material 165 Ea. 4 $49,020 Rollup
Paint (probable pre-1978 in base layer(s)) - large areas (> 10 sq. ft.) of peeling/damage & area in active use - children (measurement unit - linear feet)
Hazardous Material 1,576 LF 4 $37,457 Rollup
Paint (probable pre-1978 in base layer(s)) - large areas (> 10 sq. ft.) of peeling/damage & area in active use - children (measurement unit - square feet)
Hazardous Material 460 SF 4 $4,555 Rollup
Room Is Excessively Reverberant Acoustics 18,000 SF 4 $418,901 27981
Location: Classrooms
Room Is Excessively Reverberant Acoustics 4,500 SF 4 $104,725 27982
Location: Gym
14M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Room Lighting Is Inadequate Or In Poor Condition. Educational Adequacy
9,386 SF 4 $357,644 Rollup
The Gypsum Board Ceilings Require Replacement Capital Renewal 20 SF 4 $238 9235
Wall/ceiling materials - area < 9 sq. ft. AND in children-accessible area Hazardous Material 33 SF 4 $327 Rollup
Classroom Door Requires Vision Panel Educational Adequacy
1 Ea. 5 $2,282 Rollup
Interior Walls Require Repainting (Bldg SF) Capital Renewal 36,732 SF 5 $252,814 Rollup
The Gypsum Board Ceilings Require Repainting Capital Renewal 10,000 SF 5 $43,574 Rollup
Sub Total for System 17 items $1,443,675
MechanicalDeficiency Category Qty UoM Priority Repair Cost ID
The Cast Iron Water Boiler Requires Replacement Capital Renewal 2 Ea. 2 $377,102 8782
The Mechanical / HVAC Piping / System Is Beyond Its Useful Life Capital Renewal 38,600 SF 2 $309,934 8783
Small HVAC Circulating Pump Requires Replacement Capital Renewal 2 Ea. 4 $19,854 8781
Remove Abandoned Equipment Capital Renewal 1 Ea. 5 $3,260 9236
Note: 100 gallon water heater
Sub Total for System 4 items $710,149
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
The Mounted Building Lighting Requires Replacement Capital Renewal 10 Ea. 3 $15,548 8774
Room Has Insufficient Electrical Outlets Educational Adequacy
88 Ea. 5 $43,671 Rollup
Sub Total for System 2 items $59,219
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Existing Lavatory/Sink Pipes Are Not Insulated Correctly Barrier to Accessibility
8 LF 3 $396 8776
Location: Lower level boy's restroom
The Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Capital Renewal 38,600 SF 3 $323,512 8780
The Restroom Is Not ADA Compliant Barrier to Accessibility
140 SF 3 $40,669 8775
Location: 2nd floor office restroom
The Refrigerated Water Cooler Requires Replacement Capital Renewal 6 Ea. 4 $46,109 8779
Room lacks a drinking fountain. Educational Adequacy
10 Ea. 5 $11,028 Rollup
The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed Educational Adequacy
7 Ea. 5 $7,619 Rollup
Sub Total for System 6 items $429,333
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks Interactive White Board Educational Adequacy
1 Ea. 3 $5,704 Rollup
Technology: Campus network switching electronics are antiquated and/or do not meet standards.
Technology 234 Ea. 3 $115,866 18404
Technology: Campus wireless infrastructure inadequate. Technology 25 Ea. 3 $34,661 18406
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 20 Ea. 3 $415,930 18410
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 1 Ea. 3 $20,797 18412
Technology: Instructional spaces do not have local sound reinforcement. Technology 21 Ea. 3 $103,982 18415
Technology: Main Telecommunications Room ground system is inadequate or non-existent. Technology 1 Ea. 3 $6,932 18402
Technology: Main Telecommunications Room is not dedicated and/or inadequate. Technology 1 Ea. 3 $52,288 18400
15M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Technology: Main Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 1 Ea. 3 $9,408 18401
Technology: Network cabling infrastructure is outdated (Cat 5 or less) and/or does not meet standards.
Technology 164 Ea. 3 $73,085 18405
Technology: Network cabling infrastructure is partially outdated and/or needs expansion. Technology 72 Ea. 3 $32,086 18411
Technology: Network system inadequate and/or near end of useful life Technology 25 Ea. 3 $123,789 18414
Technology: PA/Bell/Clock system is inadequate and/or near end of useful life. Technology 38,673 SF 3 $68,937 18413
Technology: Special Space AV/Multimedia system is inadequate. Technology 1 Ea. 3 $56,448 18407
Technology: Telecommunications Room (large size room) needs dedicated cooling system improvements.
Technology 1 Ea. 3 $7,922 18403
Technology: Telephone handsets are inadequate and sparsely deployed throughout the campus.
Technology 23 Ea. 3 $36,443 18408
Technology: Telephone system is inadequate and/or non-existent. Technology 1 Ea. 3 $7,526 18409
Sub Total for System 17 items $1,171,805
SpecialtiesDeficiency Category Qty UoM Priority Repair Cost ID
Room has insufficient writing area. Educational Adequacy
2 Ea. 3 $9,127 Rollup
Sub Total for System 1 items $9,127
Sub Total for Building 01 - Main Building 48 items $3,892,629
Total for Campus 55 items $4,086,951
16M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Guiteras School - Life Cycle Summary Yrs 1-5Building: 01 - Main Building
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Acoustical Suspended Ceilings Ceilings - Acoustical Tiles 19,300 SF $174,310 3
Suspended Plaster and Painted ceilings 9,300 SF $38,903 3
Sub Total for System 2 items $213,213
MechanicalUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Decentralized Heating Equipment Heating Unit Vent - Steam/Hot water 14 Ea. $236,807 3
Exhaust Air Kitchen Exhaust Hoods 1 Ea. $15,964 3
Exhaust Air Roof Exhaust Fan 3 Ea. $15,612 3
Heating System Supplementary Components
Controls - DDC (Bldg.SF) 38,600 SF $232,420 3
HVAC Air Distribution Roof Top Unit - DX Gas (5 Ton) 1 Ea. $19,398 4
Sub Total for System 5 items $520,202
ElectricalUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Lighting Fixtures Light Fixtures (Bldg SF) 38,600 SF $229,356 3
Sub Total for System 1 items $229,356
PlumbingUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Building Support Plumbing System Supplementary Components
Sump Pump 1 Ea. $1,449 3
Fuel Storage Tanks Above Ground Fuel Oil StorageTank ( 275 Gal) 1 Ea. $475 5
Note: 80 gallon
Domestic Water Equipment Gas Piping System (BldgSF) 38,600 SF $835,742 5
Sub Total for System 3 items $837,667
Fire and Life SafetyUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Fire Detection and Alarm Fire Alarm 38,600 SF $113,137 3
Sub Total for System 1 items $113,137
Sub Total for Building 01 - Main Building 12 items $1,913,573
Total for: Guiteras School 12 items $1,913,573
17M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Supporting Photos
Site Aerial
Aged Piping
Gymnasium
Library
18M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Play Area
Art Classroom
Worn Carpet
Stained Ceiling Tile
Circulating Pump
Elevation
19M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Cracked And Chipped VCT Flooring
Boilers
Restroom Fixtures And Finishes
Cracked And Separating VCT
Cafeteria
Building Mounted Lighting
20M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Main Entrance
Site Signage
Peeling Wall Paint
Cracked Interior Wall
Classroom
Stage In Gymnasium
21M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Roof Condition
Asphalt Parking
Non-Compliant Restroom
Computer Lab
Missing Lavatory Pipe Insulation
Concrete Spalling
22M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
Paint Bubbled On Ceiling
Hallway Finishes
Refrigerated Water Fountain
Cracks In Exterior Brick
23M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Guiteras School
50 Asylum Road, Bristol, RI 02809
Facility Condition AssessmentBristol Warren - Hugh Cole School June 2017
1M▪A▪P▪P▪S ©, Jacobs 2017
Hugh Cole School, located at 50 Asylum Road in Bristol, Rhode Island, was built in 1968. It comprises 84,536 gross square feet. Each school across the district was visited three times during the Facility Condition Assessments by three teams of specialists in the spring/summer of 2016.
For master planning purposes a 5-year need was developed to provide an understanding of the current need as well as the projected needs in the near future. For Hugh Cole School the 5-year need is $7,256,649. The findings contained within this report resulted from an assessment of building systems performed by building professionals experienced in disciplines including: architecture, mechanical, plumbing, electrical, acoustics, hazardous materials, and technology infrastructure.
Figure 1: Aerial view of Hugh Cole School
Introduction
Hugh Cole School serves grades PK - 5, has 47 instructional spaces, and has an enrollment of 674. Instructional spaces are defined as rooms in which a student receives education. The LEA reported capacity for Hugh Cole School is 780 with a resulting utilization of 86%.
2M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Approach and MethodologyA facility condition assessment evaluates each building’s overall condition. Two components of the facility condition assessment are combined to total the cost for facility need. The two components of the facility condition assessment are current deficiencies and life cycle forecast.
Current Deficiencies: Deficiencies are items in need of repair or replacement as a result of being broken, obsolete, or beyond useful life. The existing deficiencies that currently require correction are identified and assigned a priority. An example of a current deficiency might include a broken lighting fixture or an inoperable roof top air conditioning unit.
Life Cycle Forecast: Life cycle analysis evaluates ages of a building's systems to forecast system replacement as they reach the end of serviceable life. An example of a life cycle system replacement is a roof with a 20-year life that has been in place for 15 years and may require replacement in five years.
Discipline Specialists
All assessment teams produced current deficiencies associated with each school. The assessment for the school facilities at the Rhode Island Department of Education included several specialties:
Facility Condition Assessment: Architectural, mechanical, and electrical engineering professionals observed conditions via a visual observation that did not include intrusive measures, destructive investigations, or testing. Additionally, the assessment incorporated input provided by district facilities and maintenance staff where applicable. The assessment team recorded existing conditions, identified problems and deficiencies, documented corrective action and quantities, and identified the priority of the repair in accordance with parameters defined during the planning phase. The team took digital photos at each school to better identify significant deficiencies.
Technology: Technology specialists visited RIDE facilities and met with technology directors to observe and assess each facility's technology infrastructure. The assessment included network architecture, major infrastructure components, classroom instructional systems, necessary building space and support for technology. The technology assessment took into account the desired technology outcome and best practices and processes to ensure results can be attained effectively.
Hazardous Materials: Schools constructed prior to 1990 were assessed by specialists to identify the presence of hazardous materials. The team focused on identifying asbestos containing building materials (ACBMs), lead-based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. If sampling and analysis was required, these activities were recommended but not included in the scope of work.
Traffic: A traffic specialist performed an in-office review of aerial imagery of the traffic infrastructure around the facilities in accordance with section 1.05-7 in the Rhode Island School Construction Regulations and reviewed data collected on site during the facility condition assessment. Based on this information, deficiencies and corrective actions were identified. High problem areas were identified for consideration of more detailed site-specific study and analysis in the future.
Acoustics: Specialists assessed each school's acoustics, including architectural acoustics, mechanical system noise and vibration, and environmental noise. The assessment team evaluated room acoustics with particular attention to the intelligibility of speech in learning spaces, interior and exterior sound isolation, and mechanical system noise and vibration control.
Educational Program Space Assessment: Teams evaluated schools to ensure that that all spaces adequately support the districts educational program. Standards are established for each classroom type or instructional space. Each space is evaluated to determine if it meets those standards and a listing of alterations that should be made to make the space a better environment for teaching and learning was created.
3M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
System Summaries
Building Envelope
The exterior systems for the building(s) at this campus includes:01 - Main Building: Brick Exterior Wall
CMU Exterior Wall Metal Panel Exterior Wall Steel Exterior WindowsStorefront / Curtain WallSteel Exterior Entrance DoorsOverhead Exterior Utility Doors
The roofing for the building(s) at this campus consists of:01 - Main Building: Composition Shingle Roofing
EPDM Roofing
Site
The site level systems for this campus include:Site Asphalt Parking Lot Pavement
Asphalt Roadway PavementConcrete Pedestrian Pavement
Interior
The interior systems for the building(s) at this campus include:01 - Main Building: Foldable Interior Partition
Steel Interior DoorsAluminum/Glass Storefront Interior DoorsWood Interior DoorsInterior Door Hardware Suspended Acoustical Grid SystemSuspended Acoustical Ceiling TileCeramic Tile WallCMU WallInterior Wall PaintingConcrete FlooringCeramic Tile FlooringVinyl Composition Tile FlooringTerrazzo FlooringCarpet
The following tables summarize major building systems at the Hugh Cole School campus, identified by discipline and building.
4M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Mechanical
The mechanical systems for the building(s) at this campus include:
01 - Main Building: 1,275 MBH Cast Iron Water Boiler Finned Wall Radiator Steam/Hot Water Heating Unit VentDDC Heating System ControlsPneumatic Heating System Controls20 Ton Outdoor Air Cooled Chiller3 Ton Outside Air Cooled Condenser3 Ton D/X Fan Coil25 HP VFD 2-Pipe Hot Water Hydronic Distribution System 1 HP or Smaller Pump5 HP Pump Roof Exhaust FanKitchen Exhaust HoodsFire Sprinkler System
Electrical
The electrical systems for the building(s) at this campus include:01 - Main Building: 1,600 Amp Switchgear
Panelboard - 120/208 100APanelboard - 120/208 225A600 Amp Distribution PanelLight Fixtures Building Mounted Lighting Fixtures Canopy Mounted Lighting Fixtures
Plumbing
The plumbing systems for the building(s) at this campus include:01 - Main Building: 60 Gallon Gas Water Heater
Domestic Water Piping System Classroom LavatoriesMop/Service SinksRefrigerated Drinking FountainRestroom LavatoriesToiletsUrinalsAir Compressor (5 hp)
5M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Facility Deficiency Priority Levels
Deficiencies were ranked according to five priority levels, with Priority 1 items being the most critical to address:
Priority 1 – Mission Critical Concerns: Deficiencies or conditions that may directly affect the school’s ability to remain open or deliver the educational curriculum. These deficiencies typically relate to building safety, code compliance, severely damaged or failing building components, and other items that require near-term correction. An example of a Priority 1 deficiency is a fire alarm system replacement.
Priority 2 – Indirect Impact to Educational Mission: Items that may progress to a Priority 1 item if not addressed in the near term. Examples of Priority 2 deficiencies include inadequate roofing that could cause deterioration of integral building systems, and conditions affecting building envelopes, such as roof and window replacements.
Priority 3 – Short-Term Conditions: Deficiencies that are necessary to the school's mission but may not require immediate attention. These items should be considered necessary improvements required to maximize facility efficiency and usefulness. Examples of Priority 3 items include site improvements and plumbing deficiencies.
Priority 4 – Long-Term Requirements: Items or systems that may be considered improvements to the instructional environment. The improvements may be aesthetic or provide greater functionality. Examples include cabinets, finishes, paving, removal of abandoned equipment, and educational accommodations associated with special programs.
Priority 5 – Enhancements: Deficiencies aesthetic in nature or considered enhancements. Typical deficiencies in this priority include repainting, replacing carpet, improved signage, or other improvements to the facility environment.
6M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Table 1: System by Priority
Priority
System 1 2 3 4 5 Total % of Total
Site - - $23,872 $609,994 $5,807 $639,673 9.92 %
Roofing - - - - - $0 0.00 %
Structural - - - - - $0 0.00 %
Exterior - $12,748 - - - $12,748 0.20 %
Interior - - $507,853 $1,404,562 $6,738 $1,919,152 29.77 %
Mechanical - $878,045 - $536,737 - $1,414,783 21.94 %
Electrical - $315,881 - - $88,726 $404,607 6.28 %
Plumbing - - $348,498 $106,661 $32,744 $487,903 7.57 %
Fire and Life Safety - - - - - $0 0.00 %
Technology - - $1,466,315 - - $1,466,315 22.74 %
Conveyances - - - - - $0 0.00 %
Specialties - - $4,533 $88,900 $8,499 $101,931 1.58 %
Total $0 $1,206,674 $2,351,071 $2,746,853 $142,514 $6,447,112
*Displayed totals may not sum exactly due to mathematical rounding
The following chart summarizes this site's current deficiencies by building system and priority. The listing details current deficiencies including deferred maintenance, functional deficiencies, code compliance, capital renewal, hazardous materials and technology categories.
The building systems with the most need include:Interior - $1,919,152Technology - $1,466,315Mechanical - $1,414,783
The chart below represents the building systems and associated deficiency costs.
Figure 2: System Deficiencies
7M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Current Deficiencies by Category
Deficiencies have been further grouped according to the observed category.
• Acoustics deficiencies relate to room acoustics, sound insolation, and mechanical systems and vibration control modeled after ANSI/ASA Standard S12.60-2010 and ASHRAE Handbook, Chapter 47 on Sound and Vibration Control.
• Barrier to Accessibility deficiencies relate to the Americans with Disabilities Act and the Rhode Island Governors Commission on Disability. Additional items related to accessibility may be included other categories.
• Capital Renewal items have reached or exceeded serviceable life and require replacement. These are current and do not include life cycle capital renewal forecasts. Also included are deficiencies correcting planned work postponed beyond its regular life expectancy.
• Code Compliance deficiencies related to current codes. Many may fall under grandfather clauses, which allow buildings to continue operating under codes effective at the time of construction. However, there are instances where the level of renovation requires full compliance which are reflected in the master plan.
• Educational Adequacy deficiencies identify where facilities do not align with the Basic Education Program and the RIDE School Construction Regulations. • Functional Deficiencies are deficiencies for components or systems that have failed before the end of expected life or are not the right application, size, or design.
• Hazardous Materials include deficiencies for building systems or components containing potentially hazardous material. The team focused on identifying asbestos containing building materials (ACBMs), lead based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. With other scopes of work there may be other costs associated with hazardous materials.
• Technology deficiencies relate to network architecture, technology infrastructure, classroom systems, and support. Examples of technology deficiencies include: security cameras, secure electronic access, telephone handsets, and dedicated air conditioning for telecommunication rooms.
• Traffic deficiencies relate to vehicle or pedestrian traffic, such as bus loops, crosswalks, and pavement markings.
8M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Table 2: Deficiency Category by PriorityPriority
Category 1 2 3 4 5 Total
Acoustics - - - - - $0
Barrier to Accessibility - - - - - $0
Capital Renewal - $1,206,674 $856,351 $1,837,853 $3,281 $3,904,160
Code Compliance - - - - - $0
Educational Adequacy - - $10,198 $846,477 $139,232 $995,908
Functional Deficiency - - - - - $0
Hazardous Material - - - $62,524 - $62,524
Technology - - $1,460,650 - - $1,460,650
Traffic - - $23,872 - - $23,872
Total $0 $1,206,674 $2,351,071 $2,746,853 $142,514 $6,447,112
*Displayed totals may not sum exactly due to mathematical rounding
The following chart and table represent the deficiency category by priority. This listing includes current deficiencies for all building systems.
9M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Life Cycle Capital Renewal Projections
System Current DeficienciesYear 12017
Year 22018
Year 32019
Year 42020
Year 52021 LC Yr. 1-5 Total Total 5-Year Need
Site $639,673 $0 $0 $0 $59,553 $0 $59,553 $699,226
Roofing $0 $0 $0 $0 $0 $0 $0 $0
Structural $0 $0 $0 $0 $0 $0 $0 $0
Exterior $12,748 $0 $0 $0 $0 $121,974 $121,974 $134,722
Interior $1,919,152 $0 $84,639 $10,878 $0 $272,584 $368,101 $2,287,253
Mechanical $1,414,783 $0 $0 $0 $0 $0 $0 $1,414,783
Electrical $404,607 $0 $0 $0 $0 $0 $0 $404,607
Plumbing $487,903 $0 $0 $0 $0 $0 $0 $487,904
Fire and Life Safety $0 $0 $0 $247,775 $0 $0 $247,775 $247,775
Technology $1,466,315 $0 $0 $0 $0 $0 $0 $1,466,315
Conveyances $0 $0 $0 $0 $0 $0 $0 $0
Specialties $101,931 $0 $0 $0 $0 $0 $0 $101,931
Total $6,447,112 $0 $84,639 $258,653 $59,553 $394,558 $797,403 $7,244,515
*Displayed totals may not sum exactly due to mathematical rounding
Life Cycle Capital Renewal ForecastDuring the facility condition assessment, assessors inspected all major building systems. If a need for immediate replacement was identified, a deficiency was created with the estimated repair costs. The identified deficiency contributes to the facility's total current repair costs.
Capital planning scenarios span multiple years, as opposed to being constrained to immediate repairs. Construction projects may begin several years after the initial facility condition assessment. Therefore, in addition to the current year repair costs, it is necessary to forecast the facility's future costs using a 5-year life cycle renewal forecast model.
Life cycle renewal is the projection of future building system costs based upon each individual system’s expected serviceable life. Building systems and components age over time, eventually break down, reach the end of their useful lives, and may require replacement. While an item may be in good condition now, it might reach the end of its life before a planned construction project occurs.
The following chart shows all current deficiencies and the subsequent 5-year life cycle capital renewal projections. The projections outline costs for major building systems in which a component is expected to reach the end of its useful life and require capital funding for replacement.
Table 3: Capital Renewal Forecast
10M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Facility Condition Index (FCI)The Facility Condition Index (FCI) is used throughout the facility condition assessment industry as a general indicator of a building’s health. Since 1991, the facility management industry has used an index called the FCI to benchmark the relative condition of a group of schools. The FCI is derived by dividing the total repair cost, including educational adequacy and site-related repairs, by the total replacement cost. A facility with a higher FCI percentage has more need, or higher priority, than a facility with a lower FCI. It should be noted that costs in the New Construction category are not included in the FCI calculation.
For master planning purposes, the total current deficiencies and the first five years of projected life cycle needs were combined. This provides an understanding of the current needs of a facility as well as the projected needs in the near future. A 5-year FCI was calculated by dividing the 5-year need by the total replacement cost. Costs associated with new construction are not included in the FCI calculation.
Figure 5: 5-Year FCI
Financial modeling has shown that over a 30-year period, it is more cost effective to replace than repair schools with a FCI of 65 percent or greater. This is due to efficiency gains with facilities that are more modern and the value of the building at the end of the analysis period. It is important to note that the FCI at which a facility should be considered for replacement is typically debated and adjusted based on property owners and facility managers approach to facility management. Of course, FCI is not the only factor used to identify buildings that need renovation, replacement, or even closure. Historical significance, enrollment trends, community sentiment, and the availability of capital are additional factors that are analyzed when making school facility decisions.
The replacement value represents the estimated cost of replacing the current building with another building of like size, based on today’s estimated cost of construction in the Providence, Rhode Island area. The estimated replacement cost for this facility is $29,587,600. For planning purposes, the total 5-year need at the Hugh Cole School is $7,256,649 (Life Cycle Years 1-5 plus the FCI deficiency cost). The Hugh Cole School facility has a 5-year FCI of 24.48%.
It is important to reiterate that this FCI replacement threshold is not conclusive, but is intended to initiate planning discussion in which other relevant issues with regard to a facility’s disposition must be incorporated. This merely suggests where conversations regarding replacement might occur.
11M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
The capacity of a school reflects how many students the school’s physical facility can effectively serve. There are various methodologies that exist to calculate capacity. It is not uncommon to review an existing building only to find that the capacity that had once been assigned is greater than what can be reasonably accommodated today. This is primarily because of a change in how programs are delivered.
The Rhode Island Aspirational Capacity is based on the Rhode Island School Construction Regulations (SCRs) and is an aspirational goal of space use. The capacity for each individual public school in the state of Rhode Island was designed to conform to Section 1.06-2 Space Allowance Guidelines of the Rhode Island Department of Education (RIDE) SCRs. These regulations outline the allowed gross square feet (GSF) per student at each school type (ES, MS, HS) by utilizing a sliding scale based on projected enrollment. The resulting capacities reflect how school capacities align to the SCRs for new construction. The existing enrollment was multiplied by the GSF per student for the appropriate bracket. For the purposes of this analysis, Pre-K centers were rolled into the elementary totals, and K-8 facilities were counted as middle schools.
The most consistent and equitable way a state can determine school capacities across a variety of districts and educational program offerings is to use square-foot-per-student standards. In contrast, in the 2013 Public Schoolhouse Assessment Report, LEAs self-reported capacities for their elementary, middle and high schools. Districts typically report “functional capacity,” which is defined as the number of students each classroom can accommodate. Functional capacity counts how many students can occupy a space, not how much room students and teachers have within that space. For example, a 650-square-foot classroom and a 950-square-foot classroom can both have a reported capacity of 25 students, but the actual teaching and learning space per student varies greatly.
The variation in square feet per student impacts the kinds of teaching practices possible in each space. The lowest allocation of space per student restricts group and project-based learning strategies and requires teachers to teach in more traditional, lecture-style formats, due to a lack of space. Furthermore, the number of students that can be accommodated in a classroom does not account for access to sufficient common spaces such as libraries, cafeterias, and gymnasiums. When cafeterias are undersized relative to the population, schools must host four or more lunch periods a day, resulting in some students eating lunch mid-morning and some mid-afternoon. Similarly, undersized libraries and gymnasiums create scheduling headaches for schools and restrict student access. Finally, a classroom count-only approach to school capacity does not consider the inherent scheduling challenges schools face.
Rhode Island Aspirational Capacity
Applying the Rhode Island Aspirational Capacity, a facility of this size could ideally support an enrollment of approximately 567 students.
As part of the Educational Program Space Assessment, select core spaces were compared to the RI School Construction Regulations. If it was determined that a facility was in need of square footage related to a cafeteria or library/media center, a cost for additional space was estimated. This cost is not included in the total 5-year need or the 5-year FCI calculation.
Facility New Construction
The New Construction cost to bring the Hugh Cole School cafeteria and/or library/media center to the size prescribed by the SCRs is estimated to be $424,116.
12M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Table 4: Facility Condition by Building
Gross Sq Ft Year BuiltCurrent
Deficiencies LC Yr. 1-5 TotalTotal 5 Yr Need
(Yr 1-5 + Current Defs) 5-Year FCI
Hugh Cole School Totals 84,536 1968 $6,459,246 $797,403 $7,256,649 24.48%
*Displayed totals may not sum exactly due to mathematical rounding
The following pages provide a listing of all current deficiencies and 5-year life cycle need and the associated costs, followed by photos taken during the assessment.
The Hugh Cole School comprises 84,536 square feet and was constructed in 1968. Current deficiencies at this school total $6,459,246. Five year capital renewal costs total $797,403. The total identified need for the Hugh Cole School (current deficiencies and 5-year capital renewal costs) is $7,256,649. The 5-year FCI is 24.48%.
Summary of Findings
Cost estimates are derived from local cost estimating expertise and enhanced by industry best practices, historical cost data, and relevance to the Rhode Island region. Costs have been developed from current market rates as of the 2nd quarter in 2016. All costs are based on a replace-in-kind approach, unless the item was not in compliance with national or state regulations or standards. For planning and budgeting purposes, facility assessments customarily add a soft cost multiplier onto deficiency repair cost estimates. This soft cost multiplier accounts for costs that are typically incurred when contracting for renovation and construction services. Soft costs typically include construction cost factors, such as contractor overhead and profit, as well as labor and material inflation, professional fees, and administrative costs. Based on the Rhode Island School Construction Regulations, a soft cost multiplier of 20% is included on all cost estimates. Other project allowances are included in the cost estimates based on school attributes such as age, location, and historic designation. All stated costs in the assessment report will include soft costs for planning and budgeting purposes. These are estimates, and costs will vary at the time of construction.
Cost Estimating
13M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Site Level DeficienciesSiteDeficiency Category Qty UoM Priority Repair Cost ID
Crosswalk: Needs to be added Traffic 1 Ea. 3 $755 9302
Note: Install crosswalk across parking lot to proposed sidewalk location
New Sidewalk Is Required Traffic 1,020 SF 3 $23,116 9301
Note: Install sidewalk from north edge of parking lot to existing neighborhood sidewalk (6' wide)
Asphalt Paving Requires Replacement Capital Renewal 177 CAR 4 $581,665 8421
Note: North East rear lot by paly area has large damaged area. West lot has several cracks, and alligatoring.
Backstops Require Replacement Educational Adequacy
1 Ea. 4 $28,329 28410
Note: Backstops Require Replacement
Exterior Basketball Goals are Required Educational Adequacy
1 Ea. 5 $5,807 28691
Note: Exterior Basketball Goals are Required
Sub Total for System 5 items $639,673
Sub Total for School and Site Level 5 items $639,673
Building: 01 - Main BuildingExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Metal Exterior Door Requires Replacement Capital Renewal 2 Door 2 $12,748 8423
Note: Door by room 01 and door by room 02
Sub Total for System 1 items $12,748
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Acoustical Ceiling Tiles Require Replacement Capital Renewal 42,268 SF 3 $379,178 8424
Note: Replace in older portion of building.
The Acoustical Ceiling Tiles Require Replacement Capital Renewal 900 SF 3 $8,074 8425
Note: New wing of school, several stained tiles: cafeteria, room 71, 75, 61, 57, 54, 52, 53, 51, 48, west corridor, 47, and nurse room.
The Ceramic Tile Flooring Requires Replacement Capital Renewal 2,500 SF 3 $66,682 8428
Note: Mary wing restroom floors are in need of repair.
The Terrazzo Flooring Requires Replacement Capital Renewal 500 SF 3 $36,828 8432
Note: Cracks in terrazzo flooring by gym.
The Vinyl Composition Tile Requires Replacement Capital Renewal 500 SF 3 $5,697 8426
Note: Cracked tiles in south corridor.
The Vinyl Composition Tile Requires Replacement Capital Renewal 1,000 SF 3 $11,394 8427
Note: Damaged VCT in north and east entry vestibule, cracked VCT north corridor, room 67
Ceiling Grid Requires Replacement Capital Renewal 42,268 SF 4 $497,944 8716
Interior Ceramic Walls Require Repair Or Replacement Capital Renewal 1,200 SF 4 $26,516 8444
Note: Damaged in both boys and girls restrooms.
Paint (probable pre-1978 in base (layers(s)) - large areas (> 10 sq. ft.) of peeling/damage & area in active use - children (measurement unit - each)
Hazardous Material 173 Ea. 4 $49,009 Rollup
Paint (probable pre-1978 in base layer(s)) - large areas (> 10 sq. ft.) of peeling/damage & area in active use - children (measurement unit - linear feet)
Hazardous Material 102 LF 4 $2,312 Rollup
Paint (probable pre-1978 in base layer(s)) - large areas (> 10 sq. ft.) of peeling/damage & area in active use - children (measurement unit - square feet)
Hazardous Material 121 SF 4 $1,143 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. AND NOT in children-accessible area (measurement unit - each)
Hazardous Material 1 Ea. 4 $283 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. AND NOT in children-accessible area (measurement unit - linear feet)
Hazardous Material 36 LF 4 $816 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. AND NOT in children-accessible area (measurement unit - square feet)
Hazardous Material 875 SF 4 $8,263 Rollup
Room Lighting Is Inadequate Or In Poor Condition. Educational Adequacy
21,602 SF 4 $817,578 Rollup
Wall/ceiling materials - area < 9 sq. ft. AND in children-accessible area Hazardous Material 74 SF 4 $699 Rollup
Interior Walls Require Repainting (Bldg SF) Capital Renewal 500 SF 5 $3,281 Rollup
14M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks appropriate sound control. Educational Adequacy
100 SF 5 $3,456 Rollup
Sub Total for System 18 items $1,919,152
MechanicalDeficiency Category Qty UoM Priority Repair Cost ID
Replace Unit Vent Capital Renewal 33 Ea. 2 $554,430 8443
Note: Original.
The Mechanical / HVAC Piping / System Is Beyond Its Useful Life Capital Renewal 42,268 SF 2 $323,616 8438
Note: Half of the piping in the school needs to be replaced.
Existing Controls Are Inadequate And Should Be Replaced With DDC Controls Capital Renewal 80,000 SF 4 $536,737 8441
Note: Part of the original 1968 section. Needs to be upgraded.
Sub Total for System 3 items $1,414,783
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
The Distribution Panel Requires Replacement Capital Renewal 1 Ea. 2 $28,933 8439
Note: FPE panel, Past life expectancy, needs replacement.
The Lighting Fixtures Require Replacement Capital Renewal 42,268 SF 2 $249,459 8440
Note: Replace lighting in the older half of school.
The Panelboard Requires Replacement Capital Renewal 3 Ea. 2 $14,448 8436
Note: In the old part of building
The Panelboard Requires Replacement Capital Renewal 4 Ea. 2 $23,041 8437
Note: In the old part of building, replace.
Room Has Insufficient Electrical Outlets Educational Adequacy
180 Ea. 5 $88,726 Rollup
Sub Total for System 5 items $404,607
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Capital Renewal 42,286 SF 3 $337,937 8435
Note: Half of the school has not been renovated. Replace piping in old half.
The Urinal Plumbing Fixtures Require Replacement Capital Renewal 8 Ea. 3 $10,561 8433
Note: Replace in original part of school.
Floor Drains Are Required Educational Adequacy
1 Ea. 4 $570 Rollup
The Custodial Mop Or Service Sink Requires Replacement Capital Renewal 2 Ea. 4 $5,118 8431
Note: Replace in original part of the building
The Refrigerated Water Cooler Requires Replacement Capital Renewal 3 Ea. 4 $21,983 8434
Note: Replace in older portion of building.
The Restroom Lavatories Plumbing Fixtures Require Replacement Capital Renewal 25 Ea. 4 $78,990 8429
Note: Replace in older portion of the building.
Room lacks a drinking fountain. Educational Adequacy
16 Ea. 5 $17,526 Rollup
The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed Educational Adequacy
14 Ea. 5 $15,218 Rollup
Sub Total for System 8 items $487,903
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks Interactive White Board Educational Adequacy
1 Ea. 3 $5,666 Rollup
Technology: Auditorium AV/Multimedia system is in need of minor improvements. Technology 1 Room 3 $94,430 18364
Technology: Campus network switching electronics are antiquated and/or do not meet standards.
Technology 336 Ea. 3 $158,642 18361
Technology: Campus wireless infrastructure inadequate. Technology 25 Ea. 3 $33,050 18362
15M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 22 Ea. 3 $436,264 18367
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 1 Ea. 3 $19,830 18369
Technology: Instructional spaces do not have local sound reinforcement. Technology 23 Ea. 3 $108,594 18373
Technology: Intermediate Telecommunications Room needs M/E improvements. Technology 1 Ea. 3 $24,174 18360
Technology: Main Telecommunications Room ground system is inadequate or non-existent. Technology 1 Ea. 3 $6,610 18358
Technology: Main Telecommunications Room needs M/E improvements. Technology 1 Ea. 3 $29,084 18356
Technology: Main Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 1 Ea. 3 $8,971 18357
Technology: Network cabling infrastructure is outdated (Cat 5 or less) and/or does not meet standards.
Technology 431 Ea. 3 $183,146 18363
Technology: Network cabling infrastructure is partially outdated and/or needs expansion. Technology 96 Ea. 3 $40,794 18368
Technology: Network system inadequate and/or near end of useful life Technology 24 Ea. 3 $113,315 18371
Technology: Network system inadequate and/or near end of useful life Technology 1 Ea. 3 $7,554 18372
Technology: PA/Bell/Clock system is inadequate and/or near end of useful life. Technology 84,536 SF 3 $143,688 18370
Technology: Telecommunications Room (large size room) needs dedicated cooling system improvements.
Technology 1 Ea. 3 $7,554 18359
Technology: Telephone handsets are inadequate and sparsely deployed throughout the campus.
Technology 25 Ea. 3 $37,772 18365
Technology: Telephone system is inadequate and/or non-existent. Technology 1 Ea. 3 $7,177 18366
Sub Total for System 19 items $1,466,315
SpecialtiesDeficiency Category Qty UoM Priority Repair Cost ID
Room has insufficient writing area. Educational Adequacy
1 Ea. 3 $4,533 Rollup
Replace Cabinetry In Classes/Labs Capital Renewal 8 Room 4 $88,900 9263
Room lacks an appropriate refrigerator. Educational Adequacy
1 Ea. 5 $8,499 Rollup
Sub Total for System 3 items $101,931
Sub Total for Building 01 - Main Building 57 items $5,807,440
Total for Campus 62 items $6,447,112
16M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Hugh Cole School - Life Cycle Summary Yrs 1-5Site Level Life Cycle Items
SiteUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Roadway Pavement Asphalt 18 CAR $59,553 4
Sub Total for System 1 items $59,553
Sub Total for Building - 1 items $59,553
Building: 01 - Main Building
ExteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Exterior Wall Veneer Metal Panel - Bldg SF basis 1,283 SF $121,974 5
Note: Original school
Sub Total for System 1 items $121,974
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Wall Painting and Coating Painting/Staining (Bldg SF) 4,270 SF $28,213 2
Note: New wing of school
Wall Painting and Coating Painting/Staining (Bldg SF) 4,270 SF $28,213 2
Note: Original wing of school
Wall Painting and Coating Painting/Staining (Bldg SF) 4,270 SF $28,213 2
Note: Original wing of school
Carpeting Carpet 500 SF $10,878 3
Interior Operable Partitions Foldable partition (Bldg SF) 2,280 SF Wall $263,362 5
Interior Swinging Doors Wood 2 Door $9,222 5
Note: Library has 2 6'x8' sliding glass door, wood frame.
Sub Total for System 6 items $368,102
Fire and Life SafetyUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Fire Detection and Alarm Fire Alarm 84,536 SF $247,775 3
Sub Total for System 1 items $247,775
Sub Total for Building 01 - Main Building 8 items $737,851
Total for: Hugh Cole School 9 items $797,405
17M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Supporting Photos
North Parking Alligator Cracking
Corridor
Stained Ceiling Tile
225 Amp Panel
18M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
100 Amp Panel
Piping
Lighting
Electric Panel
Cabinet Unit Ventilator
Damaged VCT
19M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Stained Tile
Cracked VCT
Door Damage
VCT
Lobby
East Parking Cracking
20M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Ceramic Tile Damage
VCT
Restroom Floor
East Parking Cracking
Classroom
Piping
21M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Service Sink
Water Fountain
Lockers
Damage Tile Wall
VCT
Restroom Sink
22M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Play Area
Computer Lab
Site Aerial
Urinals
Corridor
Music
23M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
Cafeteria
Gym
Plaque
Entry
Restroom
Library
24M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Hugh Cole School
525 Child Street, Warren, RI 02885
Facility Condition AssessmentBristol Warren - Kickemuit Middle School June 2017
1M▪A▪P▪P▪S ©, Jacobs 2017
Kickemuit Middle School, located at 525 Child Street in Warren, Rhode Island, was built in 1958. It comprises 149,915 gross square feet. Each school across the district was visited three times during the Facility Condition Assessments by three teams of specialists in the spring/summer of 2016.
For master planning purposes a 5-year need was developed to provide an understanding of the current need as well as the projected needs in the near future. For Kickemuit Middle School the 5-year need is $16,193,355. The findings contained within this report resulted from an assessment of building systems performed by building professionals experienced in disciplines including: architecture, mechanical, plumbing, electrical, acoustics, hazardous materials, and technology infrastructure.
Figure 1: Aerial view of Kickemuit Middle School
Introduction
Kickemuit Middle School serves grades 6 - 8, has 74 instructional spaces, and has an enrollment of 753. Instructional spaces are defined as rooms in which a student receives education. The LEA reported capacity for Kickemuit Middle School is 879 with a resulting utilization of 86%.
2M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Approach and MethodologyA facility condition assessment evaluates each building’s overall condition. Two components of the facility condition assessment are combined to total the cost for facility need. The two components of the facility condition assessment are current deficiencies and life cycle forecast.
Current Deficiencies: Deficiencies are items in need of repair or replacement as a result of being broken, obsolete, or beyond useful life. The existing deficiencies that currently require correction are identified and assigned a priority. An example of a current deficiency might include a broken lighting fixture or an inoperable roof top air conditioning unit.
Life Cycle Forecast: Life cycle analysis evaluates ages of a building's systems to forecast system replacement as they reach the end of serviceable life. An example of a life cycle system replacement is a roof with a 20-year life that has been in place for 15 years and may require replacement in five years.
Discipline Specialists
All assessment teams produced current deficiencies associated with each school. The assessment for the school facilities at the Rhode Island Department of Education included several specialties:
Facility Condition Assessment: Architectural, mechanical, and electrical engineering professionals observed conditions via a visual observation that did not include intrusive measures, destructive investigations, or testing. Additionally, the assessment incorporated input provided by district facilities and maintenance staff where applicable. The assessment team recorded existing conditions, identified problems and deficiencies, documented corrective action and quantities, and identified the priority of the repair in accordance with parameters defined during the planning phase. The team took digital photos at each school to better identify significant deficiencies.
Technology: Technology specialists visited RIDE facilities and met with technology directors to observe and assess each facility's technology infrastructure. The assessment included network architecture, major infrastructure components, classroom instructional systems, necessary building space and support for technology. The technology assessment took into account the desired technology outcome and best practices and processes to ensure results can be attained effectively.
Hazardous Materials: Schools constructed prior to 1990 were assessed by specialists to identify the presence of hazardous materials. The team focused on identifying asbestos containing building materials (ACBMs), lead-based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. If sampling and analysis was required, these activities were recommended but not included in the scope of work.
Traffic: A traffic specialist performed an in-office review of aerial imagery of the traffic infrastructure around the facilities in accordance with section 1.05-7 in the Rhode Island School Construction Regulations and reviewed data collected on site during the facility condition assessment. Based on this information, deficiencies and corrective actions were identified. High problem areas were identified for consideration of more detailed site-specific study and analysis in the future.
Acoustics: Specialists assessed each school's acoustics, including architectural acoustics, mechanical system noise and vibration, and environmental noise. The assessment team evaluated room acoustics with particular attention to the intelligibility of speech in learning spaces, interior and exterior sound isolation, and mechanical system noise and vibration control.
Educational Program Space Assessment: Teams evaluated schools to ensure that that all spaces adequately support the districts educational program. Standards are established for each classroom type or instructional space. Each space is evaluated to determine if it meets those standards and a listing of alterations that should be made to make the space a better environment for teaching and learning was created.
3M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
System Summaries
Building Envelope
The exterior systems for the building(s) at this campus includes:01 - Main Building: Brick Exterior Wall
CMU Exterior Wall Glass Block Exterior Wall Steel Exterior WindowsStorefront / Curtain WallSteel Exterior Entrance Doors
02 - Maintenance Shop: Metal Panel Exterior Wall Steel Exterior Entrance DoorsOverhead Exterior Utility Doors
03 - Shed: Wood Siding Exterior Wall Wood Exterior Doors
The roofing for the building(s) at this campus consists of:01 - Main Building: Composition Shingle Roofing
EPDM RoofingBuilt-Up Roofing With Ballast
02 - Maintenance Shop: Metal Low-Slope Roofing03 - Shed: Composition Shingle Roofing
Site
The site level systems for this campus include:Site Asphalt Parking Lot Pavement
Asphalt Roadway PavementAsphalt Pedestrian PavementConcrete Pedestrian Pavement
Interior
The interior systems for the building(s) at this campus include:01 - Main Building: Steel Interior Doors
Wood Interior DoorsInterior Door Hardware Suspended Acoustical Grid SystemSuspended Acoustical Ceiling TilePainted CeilingsWood Ceilings
The following tables summarize major building systems at the Kickemuit Middle School campus, identified by discipline and building.
4M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
01 - Main Building: Ceramic Tile WallInterior Wall PaintingConcrete FlooringCeramic Tile FlooringWood FlooringRubber Tile FlooringVinyl Composition Tile FlooringTerrazzo FlooringCarpetAthletic/Sport Flooring
02 - Maintenance Shop: Steel Interior DoorsWood Interior DoorsInterior Door Hardware Exposed Metal Structure CeilingInterior Wall PaintingConcrete Flooring
03 - Shed: Wood CeilingsInterior Wall PaintingWood Flooring
Mechanical
The mechanical systems for the building(s) at this campus include:
01 - Main Building: 4,200 MBH Cast Iron Steam Boiler Finned Wall Radiator Steam/Hot Water Heating Unit Vent3 kW Electric Unit HeaterDDC Heating System Controls1 Ton Ductless Split System2-Pipe Steam Hydronic Distribution System 5,000 CFM Outdoor AHU10,000 CFM Outdoor AHU8,000 CFM Energy Recovery Unit Roof Exhaust FanFire Sprinkler System
02 - Maintenance Shop: 5 kW Electric Unit Heater
Plumbing
The plumbing systems for the building(s) at this campus include:01 - Main Building: 2" Backflow Preventers
Gas Piping System80 Gallon Electric Water Heater
5M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Electrical
The electrical systems for the building(s) at this campus include:01 - Main Building: 1200 kW Emergency Generator
1,200 Amp Switchgear1,600 Amp SwitchgearPanelboard - 120/208 100APanelboard - 120/208 225APanelboard - 120/208 400A600 Amp Distribution PanelLight Fixtures Building Mounted Lighting Fixtures Canopy Mounted Lighting Fixtures
02 - Maintenance Shop: Panelboard - 120/208 225ABuilding Mounted Lighting Fixtures Light Fixtures
01 - Main Building: Domestic Water Piping System Classroom LavatoriesMop/Service SinksRefrigerated Drinking FountainRestroom LavatoriesShowersToiletsUrinalsSump Pump
6M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Facility Deficiency Priority Levels
Deficiencies were ranked according to five priority levels, with Priority 1 items being the most critical to address:
Priority 1 – Mission Critical Concerns: Deficiencies or conditions that may directly affect the school’s ability to remain open or deliver the educational curriculum. These deficiencies typically relate to building safety, code compliance, severely damaged or failing building components, and other items that require near-term correction. An example of a Priority 1 deficiency is a fire alarm system replacement.
Priority 2 – Indirect Impact to Educational Mission: Items that may progress to a Priority 1 item if not addressed in the near term. Examples of Priority 2 deficiencies include inadequate roofing that could cause deterioration of integral building systems, and conditions affecting building envelopes, such as roof and window replacements.
Priority 3 – Short-Term Conditions: Deficiencies that are necessary to the school's mission but may not require immediate attention. These items should be considered necessary improvements required to maximize facility efficiency and usefulness. Examples of Priority 3 items include site improvements and plumbing deficiencies.
Priority 4 – Long-Term Requirements: Items or systems that may be considered improvements to the instructional environment. The improvements may be aesthetic or provide greater functionality. Examples include cabinets, finishes, paving, removal of abandoned equipment, and educational accommodations associated with special programs.
Priority 5 – Enhancements: Deficiencies aesthetic in nature or considered enhancements. Typical deficiencies in this priority include repainting, replacing carpet, improved signage, or other improvements to the facility environment.
7M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Table 1: System by Priority
Priority
System 1 2 3 4 5 Total % of Total
Site - - $44,815 $598,057 $5,807 $648,680 4.40 %
Roofing - $543,914 $198 - - $544,112 3.69 %
Structural - - - - - $0 0.00 %
Exterior - $82,841 $62,746 - - $145,587 0.99 %
Interior - - $2,344,945 $2,751,171 $940,813 $6,036,930 40.91 %
Mechanical - $1,575,847 $488,561 - - $2,064,409 13.99 %
Electrical - $69,059 $59,066 - $132,999 $261,123 1.77 %
Plumbing - - $1,165,358 $88,529 $18,710 $1,272,597 8.62 %
Fire and Life Safety $470,156 - - - - $470,156 3.19 %
Technology - - $2,473,391 - - $2,473,391 16.76 %
Conveyances - - - - - $0 0.00 %
Specialties - - $9,127 $821,402 $8,556 $839,085 5.69 %
Total $470,156 $2,271,661 $6,648,207 $4,259,160 $1,106,886 $14,756,069
*Displayed totals may not sum exactly due to mathematical rounding
The following chart summarizes this site's current deficiencies by building system and priority. The listing details current deficiencies including deferred maintenance, functional deficiencies, code compliance, capital renewal, hazardous materials and technology categories.
The building systems with the most need include:Interior - $6,036,930Technology - $2,473,391Mechanical - $2,064,409
The chart below represents the building systems and associated deficiency costs.
Figure 2: System Deficiencies
8M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Current Deficiencies by Category
Deficiencies have been further grouped according to the observed category.
• Acoustics deficiencies relate to room acoustics, sound insolation, and mechanical systems and vibration control modeled after ANSI/ASA Standard S12.60-2010 and ASHRAE Handbook, Chapter 47 on Sound and Vibration Control.
• Barrier to Accessibility deficiencies relate to the Americans with Disabilities Act and the Rhode Island Governors Commission on Disability. Additional items related to accessibility may be included other categories.
• Capital Renewal items have reached or exceeded serviceable life and require replacement. These are current and do not include life cycle capital renewal forecasts. Also included are deficiencies correcting planned work postponed beyond its regular life expectancy.
• Code Compliance deficiencies related to current codes. Many may fall under grandfather clauses, which allow buildings to continue operating under codes effective at the time of construction. However, there are instances where the level of renovation requires full compliance which are reflected in the master plan.
• Educational Adequacy deficiencies identify where facilities do not align with the Basic Education Program and the RIDE School Construction Regulations. • Functional Deficiencies are deficiencies for components or systems that have failed before the end of expected life or are not the right application, size, or design.
• Hazardous Materials include deficiencies for building systems or components containing potentially hazardous material. The team focused on identifying asbestos containing building materials (ACBMs), lead based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. With other scopes of work there may be other costs associated with hazardous materials.
• Technology deficiencies relate to network architecture, technology infrastructure, classroom systems, and support. Examples of technology deficiencies include: security cameras, secure electronic access, telephone handsets, and dedicated air conditioning for telecommunication rooms.
• Traffic deficiencies relate to vehicle or pedestrian traffic, such as bus loops, crosswalks, and pavement markings.
9M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Table 2: Deficiency Category by PriorityPriority
Category 1 2 3 4 5 Total
Acoustics - - $488,561 $191,019 - $679,580
Barrier to Accessibility - - - - - $0
Capital Renewal - $2,271,661 $3,618,062 $3,916,359 $940,813 $10,746,895
Code Compliance $424,523 - - - - $424,523
Educational Adequacy $45,633 - $14,831 $119,626 $166,072 $346,163
Functional Deficiency - - $59,066 - - $59,066
Hazardous Material - - - $32,156 - $32,156
Technology - - $2,467,686 - - $2,467,686
Traffic - - - - - $0
Total $470,156 $2,271,661 $6,648,207 $4,259,160 $1,106,886 $14,756,069
*Displayed totals may not sum exactly due to mathematical rounding
The following chart and table represent the deficiency category by priority. This listing includes current deficiencies for all building systems.
10M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Life Cycle Capital Renewal Projections
System Current DeficienciesYear 12017
Year 22018
Year 32019
Year 42020
Year 52021 LC Yr. 1-5 Total Total 5-Year Need
Site $648,680 $0 $0 $0 $0 $0 $0 $648,680
Roofing $544,112 $0 $0 $0 $0 $0 $0 $544,112
Structural $0 $0 $0 $0 $0 $0 $0 $0
Exterior $145,587 $0 $0 $0 $0 $0 $0 $145,587
Interior $6,036,930 $34,000 $0 $0 $0 $37,372 $71,372 $6,108,302
Mechanical $2,064,409 $0 $0 $1,228,517 $0 $0 $1,228,517 $3,292,926
Electrical $261,123 $0 $0 $117,796 $0 $0 $117,796 $378,919
Plumbing $1,272,597 $0 $0 $5,655 $0 $1,449 $7,104 $1,279,701
Fire and Life Safety $470,156 $0 $0 $0 $0 $0 $0 $470,156
Technology $2,473,391 $0 $0 $0 $0 $0 $0 $2,473,391
Conveyances $0 $0 $0 $0 $0 $0 $0 $0
Specialties $839,085 $0 $0 $0 $0 $0 $0 $839,085
Total $14,756,069 $34,000 $0 $1,351,968 $0 $38,821 $1,424,789 $16,180,858
*Displayed totals may not sum exactly due to mathematical rounding
Life Cycle Capital Renewal ForecastDuring the facility condition assessment, assessors inspected all major building systems. If a need for immediate replacement was identified, a deficiency was created with the estimated repair costs. The identified deficiency contributes to the facility's total current repair costs.
Capital planning scenarios span multiple years, as opposed to being constrained to immediate repairs. Construction projects may begin several years after the initial facility condition assessment. Therefore, in addition to the current year repair costs, it is necessary to forecast the facility's future costs using a 5-year life cycle renewal forecast model.
Life cycle renewal is the projection of future building system costs based upon each individual system’s expected serviceable life. Building systems and components age over time, eventually break down, reach the end of their useful lives, and may require replacement. While an item may be in good condition now, it might reach the end of its life before a planned construction project occurs.
The following chart shows all current deficiencies and the subsequent 5-year life cycle capital renewal projections. The projections outline costs for major building systems in which a component is expected to reach the end of its useful life and require capital funding for replacement.
Table 3: Capital Renewal Forecast
11M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Facility Condition Index (FCI)The Facility Condition Index (FCI) is used throughout the facility condition assessment industry as a general indicator of a building’s health. Since 1991, the facility management industry has used an index called the FCI to benchmark the relative condition of a group of schools. The FCI is derived by dividing the total repair cost, including educational adequacy and site-related repairs, by the total replacement cost. A facility with a higher FCI percentage has more need, or higher priority, than a facility with a lower FCI. It should be noted that costs in the New Construction category are not included in the FCI calculation.
For master planning purposes, the total current deficiencies and the first five years of projected life cycle needs were combined. This provides an understanding of the current needs of a facility as well as the projected needs in the near future. A 5-year FCI was calculated by dividing the 5-year need by the total replacement cost. Costs associated with new construction are not included in the FCI calculation.
Figure 5: 5-Year FCI
Financial modeling has shown that over a 30-year period, it is more cost effective to replace than repair schools with a FCI of 65 percent or greater. This is due to efficiency gains with facilities that are more modern and the value of the building at the end of the analysis period. It is important to note that the FCI at which a facility should be considered for replacement is typically debated and adjusted based on property owners and facility managers approach to facility management. Of course, FCI is not the only factor used to identify buildings that need renovation, replacement, or even closure. Historical significance, enrollment trends, community sentiment, and the availability of capital are additional factors that are analyzed when making school facility decisions.
The replacement value represents the estimated cost of replacing the current building with another building of like size, based on today’s estimated cost of construction in the Providence, Rhode Island area. The estimated replacement cost for this facility is $49,471,952. For planning purposes, the total 5-year need at the Kickemuit Middle School is $16,193,355 (Life Cycle Years 1-5 plus the FCI deficiency cost). The Kickemuit Middle School facility has a 5-year FCI of 32.71%.
It is important to reiterate that this FCI replacement threshold is not conclusive, but is intended to initiate planning discussion in which other relevant issues with regard to a facility’s disposition must be incorporated. This merely suggests where conversations regarding replacement might occur.
12M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
The capacity of a school reflects how many students the school’s physical facility can effectively serve. There are various methodologies that exist to calculate capacity. It is not uncommon to review an existing building only to find that the capacity that had once been assigned is greater than what can be reasonably accommodated today. This is primarily because of a change in how programs are delivered.
The Rhode Island Aspirational Capacity is based on the Rhode Island School Construction Regulations (SCRs) and is an aspirational goal of space use. The capacity for each individual public school in the state of Rhode Island was designed to conform to Section 1.06-2 Space Allowance Guidelines of the Rhode Island Department of Education (RIDE) SCRs. These regulations outline the allowed gross square feet (GSF) per student at each school type (ES, MS, HS) by utilizing a sliding scale based on projected enrollment. The resulting capacities reflect how school capacities align to the SCRs for new construction. The existing enrollment was multiplied by the GSF per student for the appropriate bracket. For the purposes of this analysis, Pre-K centers were rolled into the elementary totals, and K-8 facilities were counted as middle schools.
The most consistent and equitable way a state can determine school capacities across a variety of districts and educational program offerings is to use square-foot-per-student standards. In contrast, in the 2013 Public Schoolhouse Assessment Report, LEAs self-reported capacities for their elementary, middle and high schools. Districts typically report “functional capacity,” which is defined as the number of students each classroom can accommodate. Functional capacity counts how many students can occupy a space, not how much room students and teachers have within that space. For example, a 650-square-foot classroom and a 950-square-foot classroom can both have a reported capacity of 25 students, but the actual teaching and learning space per student varies greatly.
The variation in square feet per student impacts the kinds of teaching practices possible in each space. The lowest allocation of space per student restricts group and project-based learning strategies and requires teachers to teach in more traditional, lecture-style formats, due to a lack of space. Furthermore, the number of students that can be accommodated in a classroom does not account for access to sufficient common spaces such as libraries, cafeterias, and gymnasiums. When cafeterias are undersized relative to the population, schools must host four or more lunch periods a day, resulting in some students eating lunch mid-morning and some mid-afternoon. Similarly, undersized libraries and gymnasiums create scheduling headaches for schools and restrict student access. Finally, a classroom count-only approach to school capacity does not consider the inherent scheduling challenges schools face.
Rhode Island Aspirational Capacity
Applying the Rhode Island Aspirational Capacity, a facility of this size could ideally support an enrollment of approximately 824 students.
As part of the Educational Program Space Assessment, select core spaces were compared to the RI School Construction Regulations. If it was determined that a facility was in need of square footage related to a cafeteria or library/media center, a cost for additional space was estimated. This cost is not included in the total 5-year need or the 5-year FCI calculation.
Facility New Construction
The New Construction cost to bring the Kickemuit Middle School cafeteria and/or library/media center to the size prescribed by the SCRs is estimated to be $761,627.
13M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Table 4: Facility Condition by Building
Gross Sq Ft Year BuiltCurrent
Deficiencies LC Yr. 1-5 TotalTotal 5 Yr Need
(Yr 1-5 + Current Defs) 5-Year FCI
Kickemuit Middle School Totals 149,915 1958 $14,768,566 $1,424,789 $16,193,355 32.71%
*Displayed totals may not sum exactly due to mathematical rounding
The following pages provide a listing of all current deficiencies and 5-year life cycle need and the associated costs, followed by photos taken during the assessment.
The Kickemuit Middle School comprises 149,915 square feet and was constructed in 1958. Current deficiencies at this school total $14,768,566. Five year capital renewal costs total $1,424,789. The total identified need for the Kickemuit Middle School (current deficiencies and 5-year capital renewal costs) is $16,193,355. The 5-year FCI is 32.71%.
Summary of Findings
As part of the assessment process, LEAs were given several opportunities to provide feedback on the data. Jacobs performed a thorough review of the comments provided relating to the Facilities Condition Assessment. Based on information provided, some adjustments were made to improve or refine the dataset. In other situations, enough information was not provided, item was out of scope, or evidence provided by assessment team did not align with the feedback and no adjustment was made. Finally, deficiency priorities, costs, and educational space/technology standards are consistent throughout the state.
Cost estimates are derived from local cost estimating expertise and enhanced by industry best practices, historical cost data, and relevance to the Rhode Island region. Costs have been developed from current market rates as of the 2nd quarter in 2016. All costs are based on a replace-in-kind approach, unless the item was not in compliance with national or state regulations or standards. For planning and budgeting purposes, facility assessments customarily add a soft cost multiplier onto deficiency repair cost estimates. This soft cost multiplier accounts for costs that are typically incurred when contracting for renovation and construction services. Soft costs typically include construction cost factors, such as contractor overhead and profit, as well as labor and material inflation, professional fees, and administrative costs. Based on the Rhode Island School Construction Regulations, a soft cost multiplier of 20% is included on all cost estimates. Other project allowances are included in the cost estimates based on school attributes such as age, location, and historic designation. All stated costs in the assessment report will include soft costs for planning and budgeting purposes. These are estimates, and costs will vary at the time of construction.
Cost Estimating
LEA Feedback
14M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Site Level DeficienciesSiteDeficiency Category Qty UoM Priority Repair Cost ID
Asphalt Walks Require Replacement Capital Renewal 5,280 SF 3 $44,815 8901
Note: Beyond useful life. Several large cracks, these cracks are a trip hazard.
Asphalt Paving Requires Replacement Capital Renewal 147 CAR 4 $483,077 8899
Note: Beyond useful life. Several large cracks, several areas of alligatoring, potholes. Several trip hazards. Asphalt also requires sealcoating.
Asphalt Paving Requires Replacement Capital Renewal 25 CAR 4 $82,156 8900
Note: Beyond useful life.
Backstops Require Replacement Educational Adequacy
1 Ea. 4 $28,329 28408
Note: Backstops Require Replacement
Fencing Requires Replacement (4' Chain Link Fence) Capital Renewal 70 LF 4 $4,495 8898
Note: Over life cycle
Exterior Basketball Goals are Required Educational Adequacy
1 Ea. 5 $5,807 28690
Note: Exterior Basketball Goals are Required
Sub Total for System 6 items $648,680
RoofingDeficiency Category Qty UoM Priority Repair Cost ID
The Asphalt Shingle Roof Covering Requires Replacement Capital Renewal 24,000 SF 2 $543,914 8902
Note: Several leaks in rooms under low sloping asphalt. Rooms with leaks: 111, 111C, 113, 115, 119, 141, 144, 146, 148, 149, 151,155, Book storage. 1st floor corridor outside room 114
Sub Total for System 1 items $543,914
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
The Pole Lighting Is Missing And Needed Functional Deficiency 3 Ea. 3 $59,066 8903
Note: Need more lights in parking lot.
Sub Total for System 1 items $59,066
Sub Total for School and Site Level 8 items $1,251,660
Building: 01 - Main BuildingRoofingDeficiency Category Qty UoM Priority Repair Cost ID
The Roof Drains Require Cleaning Capital Renewal 5 Ea. 3 $198 8907
Sub Total for System 1 items $198
ExteriorDeficiency Category Qty UoM Priority Repair Cost ID
Glass Wall Requires Replacement (Bldg SF) Capital Renewal 250 SF 2 $42,781 8928
Note: Glass wall in gym has broken glass blocks
The Glass Pane In The Steel Exterior Window Requires Replacement Capital Renewal 48 SF 2 $22,794 8906
Note: 2 4'x6' glass panes are damaged. 1 in assistant principals office, 1 in main office
The Brick Exterior Requires Repointing Capital Renewal 1,500 SF Wall
3 $62,746 8914
Note: Several areas require Repointing, possibly could be the cause of leaks.
Sub Total for System 3 items $128,321
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Interior CMU Walls Require Repair Capital Renewal 3,000 SF 3 $108,950 8922
Note: Cracks in CMU located in rooms: 114, 212, work room, 246, in corridor walls by rooms, 124, 221, 224, 255. Holes in mechanical room.
The Acoustical Ceiling Tiles Require Replacement Capital Renewal 128,839 SF 3 $1,163,625 8908
Note: Several damaged and stained ceiling tiles throughout school. Whole system should be replaced.
The Carpet Flooring Requires Replacement Capital Renewal 3,357 SF 3 $73,036 8909
Note: Carpet installed in 1997
The Ceramic Tile Flooring Requires Replacement Capital Renewal 250 SF 3 $6,713 8911
Note: Restroom floors.
15M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Interior Door Hardware Requires Replacement Capital Renewal 1 Door 3 $3,137 8916
Note: Missing hardware in main office
The Vinyl Composition Tile Requires Replacement Capital Renewal 86,254 SF 3 $989,484 8910
Note: Several areas of damage, replace whole system.
Interior Ceramic Walls Require Repair Or Replacement Capital Renewal 800 SF Wall
4 $21,296 8913
Note: Most Restrooms have damage to ceramic tile walls.
Interior Gypsum Board Walls Require Repair Capital Renewal 500 SF Wall
4 $3,654 8904
Note: Cracks in gypboard above lockers 327, 173, 123, 111, 97, 81, 767, 705, 651, 639, 621, 607.
Moveable Partitions Require Replacement Capital Renewal 3,840 SF Wall
4 $443,557 8905
Note: Partition has a tear in fabric, room 117. Additional partitions old and obsolete.
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - each)
Hazardous Material 4 Ea. 4 $1,141 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - linear feet)
Hazardous Material 276 LF 4 $6,297 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - square feet)
Hazardous Material 2,600 SF 4 $24,718 Rollup
Room Is Excessively Reverberant Acoustics 8,550 SF 4 $191,019 27950
Location: Gym
Room Lighting Is Inadequate Or In Poor Condition. Educational Adequacy
2,396 SF 4 $91,297 Rollup
The Terrazzo Flooring Requires Repair Capital Renewal 36,966 SF 4 $1,968,192 8915
Note: Several large cracks in terrazzo floor. All corridors have cracks, cracks in rooms.
Interior Walls Require Repainting (Bldg SF) Capital Renewal 142,389 SF 5 $940,813 Rollup
Sub Total for System 16 items $6,036,930
MechanicalDeficiency Category Qty UoM Priority Repair Cost ID
The Boiler HVAC Component Requires Replacement Capital Renewal 2 Ea. 2 $455,325 8912
Note: Replace
The Mechanical / HVAC Piping / System Is Beyond Its Useful Life Capital Renewal 144,839 SF 2 $1,116,447 8923
Unit Ventilators Are Excessively Noisy Acoustics 77 Ea. 3 $488,561 27949
Location: Classrooms
Sub Total for System 3 items $2,060,333
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
Switchgear Is Needed Or Requires Replacement Capital Renewal 1 Ea. 2 $69,059 8924
Room Has Insufficient Electrical Outlets Educational Adequacy
268 Ea. 5 $132,999 Rollup
Sub Total for System 2 items $202,058
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Capital Renewal 144,839 SF 3 $1,165,358 8921
The Refrigerated Water Cooler Requires Replacement Capital Renewal 12 Ea. 4 $88,529 8920
Room lacks a drinking fountain. Educational Adequacy
6 Ea. 5 $6,617 Rollup
The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed Educational Adequacy
8 Ea. 5 $12,093 Rollup
Sub Total for System 4 items $1,272,597
Fire and Life SafetyDeficiency Category Qty UoM Priority Repair Cost ID
Fire Alarm Is Missing Or Inadequate (NFPA 72 and NFPA 101, Section 9.6) Code Compliance 144,839 SF 1 $424,523 8918
Room lacks shut-off valves for utilities. (International Fuel Gas Code, Section 409.6) Educational Adequacy
4 Ea. 1 $45,633 Rollup
Sub Total for System 2 items $470,156
16M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks Interactive White Board Educational Adequacy
1 Ea. 3 $5,704 Rollup
Technology: Campus network switching electronics are antiquated and/or do not meet standards.
Technology 24 Ea. 3 $11,408 18441
Technology: Campus wireless infrastructure inadequate. Technology 55 Ea. 3 $73,204 18439
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 50 Ea. 3 $998,232 18446
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 1 Ea. 3 $19,965 18447
Technology: Gymnasium sound system is nonexistent, inadequate, or near end of useful life.
Technology 1 Ea. 3 $9,127 18443
Technology: Instructional spaces do not have local sound reinforcement. Technology 51 Ea. 3 $242,428 18451
Technology: Intermediate Telecommunications Room grounding system is inadequate or non-existent.
Technology 5 Ea. 3 $26,620 18437
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $37,648 18435
Technology: Intermediate Telecommunications Room needs minor improvements. Technology 4 Ea. 3 $66,929 18434
Technology: Intermediate Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 5 Ea. 3 $23,767 18436
Technology: Main Telecommunications Room ground system is inadequate or non-existent. Technology 1 Ea. 3 $6,655 18433
Technology: Main Telecommunications Room needs M/E improvements. Technology 1 Ea. 3 $29,281 18432
Technology: Network cabling infrastructure is outdated (Cat 5 or less) and/or does not meet standards.
Technology 615 Ea. 3 $263,105 18442
Technology: Network system inadequate and/or near end of useful life Technology 55 Ea. 3 $261,442 18449
Technology: Network system inadequate and/or near end of useful life Technology 3 Ea. 3 $22,817 18450
Technology: PA/Bell/Clock system is inadequate and/or near end of useful life. Technology 144,839 SF 3 $247,856 18448
Technology: Telecommunications Room (small size room) needs dedicated cooling system improvements.
Technology 5 Ea. 3 $23,767 18438
Technology: Telecommunications Room fiber connectivity infrastructure is outdated and/or inadequate.
Technology 2 Ea. 3 $12,549 18440
Technology: Telephone handsets are inadequate and sparsely deployed throughout the campus.
Technology 55 Ea. 3 $83,661 18444
Technology: Telephone system is inadequate and/or non-existent. Technology 1 Ea. 3 $7,225 18445
Sub Total for System 21 items $2,473,391
SpecialtiesDeficiency Category Qty UoM Priority Repair Cost ID
Room has insufficient writing area. Educational Adequacy
2 Ea. 3 $9,127 Rollup
The Retractable Bleachers Require Replacement Capital Renewal 720 Seat 4 $821,402 8917
Room lacks an appropriate refrigerator. Educational Adequacy
1 Ea. 5 $8,556 Rollup
Sub Total for System 3 items $839,085
Sub Total for Building 01 - Main Building 55 items $13,483,068
17M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Building: 02 - Maintenance ShopMechanicalDeficiency Category Qty UoM Priority Repair Cost ID
Electric Unit Heater Requires Replacement Capital Renewal 3 Ea. 2 $4,076 8929
Note: Past life expectancy, needs replacement.
Sub Total for System 1 items $4,076
Sub Total for Building 02 - Maintenance Shop 1 items $4,076
Building: 03 - ShedExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Exterior Wood Requires Replacement (Bldg SF) Capital Renewal 576 SF 2 $17,266 8930
Note: over life
Sub Total for System 1 items $17,266
Sub Total for Building 03 - Shed 1 items $17,266
Total for Campus 65 items $14,756,069
18M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Kickemuit Middle School - Life Cycle Summary Yrs 1-5Building: 01 - Main Building
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Resilient Flooring Rubber Tile Flooring 1,820 SF $34,000 1
Sub Total for System 1 items $34,000
MechanicalUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Exhaust Air Roof Exhaust Fan 68 Ea. $353,880 3
Heating System Supplementary Components
Controls - DDC (Bldg.SF) 144,839 SF $872,110 3
Decentralized Heating Equipment Unit Heater Electric (3 KW) 2 Ea. $2,527 3
Sub Total for System 3 items $1,228,517
ElectricalUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Electrical Service Switchgear - Main Dist Panel (1600 Amps) 1 Ea. $82,102 3
Sub Total for System 1 items $82,102
PlumbingUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Domestic Water Equipment Water Heater - Electric - 80 gallon 1 Ea. $5,655 3
Note: 75 Gallon
Building Support Plumbing System Supplementary Components
Sump Pump 1 Ea. $1,449 5
Sub Total for System 2 items $7,104
Sub Total for Building 01 - Main Building 7 items $1,351,723
Building: 02 - Maintenance Shop
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Wall Painting and Coating Painting/Staining (Bldg SF) 4,500 SF $29,733 5
Sub Total for System 1 items $29,733
ElectricalUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Lighting Fixtures Building Mounted Fixtures (Ea.) 6 Ea. $8,956 3
Lighting Fixtures Light Fixtures (Bldg SF) 4,500 SF $26,738 3
Sub Total for System 2 items $35,694
Sub Total for Building 02 - Maintenance Shop 3 items $65,427
Building: 03 - Shed
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Wall Painting and Coating Painting/Staining (Bldg SF) 576 SF $3,806 5
Specialty Suspended Ceilings Ceiling - Wood 576 SF $3,833 5
Note: Exposed Wood
Sub Total for System 2 items $7,639
Sub Total for Building 03 - Shed 2 items $7,639
Total for: Kickemuit Middle School 12 items $1,424,789
19M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Supporting Photos
Piping
Elevation
CMU Crack
Crack in CMU
20M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
CMU Holes
Piping
Unit Ventilator
Switchboard
Alligatoring In Parking Lot Asphalt
Trip Hazard
21M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Large Trip Hazard
Parking Lot Cracks
Asphalt Sidewalk Trip Hazard
Cracks In Asphalt Sidewalk
Roof
Damaged Roof Covering
22M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Active Leak Outside Room 232
Damaged Roof Covering
Tear In Partition #1
Broken Glass (Gym)
Corridor
Classroom
23M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Site Aerial
Science lab
Auditorium
Kitchen
Gymnasium
Roof
24M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Gymnasium
Cafe
Fintess Center
Restroom
Restroom 2
Marquee
25M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Music
Boys locker room
Art
Auditorium
Library
Cracks In Gypsum Board
26M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Computer lab
Roof
Damaged Glass Pane
Glass Pane
Stained Tiles
Damaged VCT
27M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Roof Drain
Stained Tiles
Cracked VCT
Restroom Flooring
Boilers
Damaged Wall
28M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Restroom Flooring
Damaged Wall
Repoint Brick
Repoint
Cracked Terrazo
Water Fountain
29M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
Terrazzo Floor Damage
Missing Hardware
Shop Interior
Maintenance Shop
Shed
30M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Kickemuit Middle School
199 Chestnut Street, Bristol, RI 02809
Facility Condition AssessmentBristol Warren - Mt. Hope High School June 2017
1M▪A▪P▪P▪S ©, Jacobs 2017
Mt. Hope High School, located at 199 Chestnut Street in Bristol, Rhode Island, was built in 1965. It comprises 177,732 gross square feet. Each school across the district was visited three times during the Facility Condition Assessments by three teams of specialists in the spring/summer of 2016.
For master planning purposes a 5-year need was developed to provide an understanding of the current need as well as the projected needs in the near future. For Mt. Hope High School the 5-year need is $22,406,303. The findings contained within this report resulted from an assessment of building systems performed by building professionals experienced in disciplines including: architecture, mechanical, plumbing, electrical, acoustics, hazardous materials, and technology infrastructure.
Figure 1: Aerial view of Mt. Hope High School
Introduction
Mt. Hope High School serves grades 9 - 12, has 78 instructional spaces, and has an enrollment of 912. Instructional spaces are defined as rooms in which a student receives education. The LEA reported capacity for Mt. Hope High School is 1,407 with a resulting utilization of 65%.
2M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Approach and MethodologyA facility condition assessment evaluates each building’s overall condition. Two components of the facility condition assessment are combined to total the cost for facility need. The two components of the facility condition assessment are current deficiencies and life cycle forecast.
Current Deficiencies: Deficiencies are items in need of repair or replacement as a result of being broken, obsolete, or beyond useful life. The existing deficiencies that currently require correction are identified and assigned a priority. An example of a current deficiency might include a broken lighting fixture or an inoperable roof top air conditioning unit.
Life Cycle Forecast: Life cycle analysis evaluates ages of a building's systems to forecast system replacement as they reach the end of serviceable life. An example of a life cycle system replacement is a roof with a 20-year life that has been in place for 15 years and may require replacement in five years.
Discipline Specialists
All assessment teams produced current deficiencies associated with each school. The assessment for the school facilities at the Rhode Island Department of Education included several specialties:
Facility Condition Assessment: Architectural, mechanical, and electrical engineering professionals observed conditions via a visual observation that did not include intrusive measures, destructive investigations, or testing. Additionally, the assessment incorporated input provided by district facilities and maintenance staff where applicable. The assessment team recorded existing conditions, identified problems and deficiencies, documented corrective action and quantities, and identified the priority of the repair in accordance with parameters defined during the planning phase. The team took digital photos at each school to better identify significant deficiencies.
Technology: Technology specialists visited RIDE facilities and met with technology directors to observe and assess each facility's technology infrastructure. The assessment included network architecture, major infrastructure components, classroom instructional systems, necessary building space and support for technology. The technology assessment took into account the desired technology outcome and best practices and processes to ensure results can be attained effectively.
Hazardous Materials: Schools constructed prior to 1990 were assessed by specialists to identify the presence of hazardous materials. The team focused on identifying asbestos containing building materials (ACBMs), lead-based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. If sampling and analysis was required, these activities were recommended but not included in the scope of work.
Traffic: A traffic specialist performed an in-office review of aerial imagery of the traffic infrastructure around the facilities in accordance with section 1.05-7 in the Rhode Island School Construction Regulations and reviewed data collected on site during the facility condition assessment. Based on this information, deficiencies and corrective actions were identified. High problem areas were identified for consideration of more detailed site-specific study and analysis in the future.
Acoustics: Specialists assessed each school's acoustics, including architectural acoustics, mechanical system noise and vibration, and environmental noise. The assessment team evaluated room acoustics with particular attention to the intelligibility of speech in learning spaces, interior and exterior sound isolation, and mechanical system noise and vibration control.
Educational Program Space Assessment: Teams evaluated schools to ensure that that all spaces adequately support the districts educational program. Standards are established for each classroom type or instructional space. Each space is evaluated to determine if it meets those standards and a listing of alterations that should be made to make the space a better environment for teaching and learning was created.
3M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
System Summaries
Building Envelope
The exterior systems for the building(s) at this campus includes:01 - Main Building: CMU Exterior Wall
Metal Panel Exterior Wall Aluminum Exterior WindowsStorefront / Curtain WallStorefront Entrance DoorsSteel Exterior Entrance Doors
02 - Storage: Wood Siding Exterior Wall Steel Exterior Entrance Doors
03 - Maintenance: CMU Exterior Wall Steel Exterior Entrance DoorsOverhead Exterior Utility Doors
04 - Storage: Wood Siding Exterior Wall Steel Exterior Entrance Doors
05 - Storage: Wood Siding Exterior Wall Overhead Exterior Utility Doors
06 - Concessions: Wood Siding Exterior Wall Steel Exterior WindowsSteel Exterior Entrance Doors
07 - Ticket Building: Wood Siding Exterior Wall Vinyl on Wood Frame Exterior WindowsSteel Exterior Entrance DoorsOverhead Exterior Utility Doors
08 - Field Electrical Room: Wood Siding Exterior Wall Steel Exterior Entrance Doors
09 - Portable A: Wood Siding Exterior Wall Vinyl on Wood Frame Exterior WindowsSteel Exterior Entrance Doors
10 - Building 10: Wood Siding Exterior Wall Vinyl on Wood Frame Exterior Windows
Site
The site level systems for this campus include:Site Asphalt Parking Lot Pavement
Asphalt Roadway PavementAsphalt Pedestrian PavementConcrete Pedestrian Pavement
The following tables summarize major building systems at the Mt. Hope High School campus, identified by discipline and building.
4M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
10 - Building 10: Storefront Entrance Doors11 - Pump House: CMU Exterior Wall
Steel Exterior Entrance Doors
The roofing for the building(s) at this campus consists of:01 - Main Building: Composition Shingle Roofing
EPDM RoofingSteel Canopy Roofing
02 - Storage: Composition Shingle Roofing03 - Maintenance: Metal Steep Slope Roofing04 - Storage: Composition Shingle Roofing05 - Storage: Composition Shingle Roofing06 - Concessions: Composition Shingle Roofing07 - Ticket Building: Composition Shingle Roofing08 - Field Electrical Room: Composition Shingle Roofing09 - Portable A: Composition Shingle Roofing10 - Building 10: Clear Polycarbonate Roofing11 - Pump House: Composition Shingle Roofing
Interior
The interior systems for the building(s) at this campus include:01 - Main Building: Moveable Interior Partition
Steel Interior DoorsWood Interior DoorsInterior Door Hardware Suspended Acoustical Grid SystemSuspended Acoustical Ceiling TilePainted CeilingsCeramic Tile WallCMU WallInterior Wall PaintingConcrete FlooringCeramic Tile FlooringWood FlooringVinyl Composition Tile FlooringTerrazzo FlooringCarpetAthletic/Sport Flooring
02 - Storage: Wood CeilingsInterior Wall PaintingWood Flooring
03 - Maintenance: Wood Interior Doors
5M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
03 - Maintenance: Overhead Interior Coiling DoorsInterior Door Hardware Exposed Metal Structure CeilingWood Wall PanelingConcrete Flooring
04 - Storage: Wood CeilingsInterior Wall PaintingWood Flooring
05 - Storage: Wood CeilingsInterior Wall PaintingWood Flooring
06 - Concessions: Wood Interior DoorsInterior Door Hardware Wood CeilingsInterior Wall PaintingConcrete Flooring
07 - Ticket Building: Wood CeilingsWood Wall PanelingWood Flooring
08 - Field Electrical Room: Wood CeilingsWood Wall PanelingWood Flooring
09 - Portable A: Wood Interior DoorsInterior Door Hardware Suspended Acoustical Grid SystemSuspended Acoustical Ceiling TileWood Wall PanelingCarpet
10 - Building 10: Wood Flooring11 - Pump House: Wood Ceilings
Concrete Flooring
Mechanical
The mechanical systems for the building(s) at this campus include:
01 - Main Building: 1,275 MBH Cast Iron Steam Boiler 4,200 MBH Cast Iron Steam Boiler Finned Wall Radiator Steam/Hot Water Heating Unit Vent5 kW Electric Unit HeaterDDC Heating System ControlsPneumatic Heating System Controls1 Ton Ductless Split System
6M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
01 - Main Building: 3 Ton D/X Fan Coil2-Pipe Hot Water Hydronic Distribution System 1 HP or Smaller Pump5 HP Pump 10 HP Pump 5,000 CFM Outdoor AHUDuctworkDehumidifierRoof Exhaust FanKitchen Exhaust HoodsFire Sprinkler System
03 - Maintenance: 3 kW Electric Unit Heater
Electrical
The electrical systems for the building(s) at this campus include:01 - Main Building: 1200 kW Emergency Generator
Plumbing
The plumbing systems for the building(s) at this campus include:01 - Main Building: 2" Backflow Preventers
Gas Piping System40 Gallon Gas Water Heater50 Gallon Gas Water Heater75 Gallon Gas Water HeaterDomestic Water Piping System
03 - Maintenance: Domestic Water Piping System 09 - Portable A: Domestic Water Piping System 01 - Main Building: Classroom Lavatories
Mop/Service SinksNon-Refrigerated Drinking FountainRefrigerated Drinking FountainRestroom LavatoriesShowersToiletsUrinals
03 - Maintenance: Restroom LavatoriesToilets
09 - Portable A: Restroom LavatoriesToilets
01 - Main Building: Sump PumpAir Compressor (2 hp)1,000 Gallon Underground Fuel Oil Storage Tank
7M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
01 - Main Building: 1,600 Amp SwitchgearPanelboard - 120/208 100APanelboard - 120/208 225APanelboard - 120/208 400AElectrical DisconnectLight Fixtures Building Mounted Lighting Fixtures Canopy Mounted Lighting Fixtures
03 - Maintenance: Panelboard - 120/208 100ALight Fixtures
07 - Ticket Building: Panelboard - 120/208 100ALight Fixtures
08 - Field Electrical Room: 45 KVA TransformerPanelboard - 120/208 100APanelboard - 120/208 225A
09 - Portable A: Panelboard - 120/208 100ALight Fixtures
8M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Facility Deficiency Priority Levels
Deficiencies were ranked according to five priority levels, with Priority 1 items being the most critical to address:
Priority 1 – Mission Critical Concerns: Deficiencies or conditions that may directly affect the school’s ability to remain open or deliver the educational curriculum. These deficiencies typically relate to building safety, code compliance, severely damaged or failing building components, and other items that require near-term correction. An example of a Priority 1 deficiency is a fire alarm system replacement.
Priority 2 – Indirect Impact to Educational Mission: Items that may progress to a Priority 1 item if not addressed in the near term. Examples of Priority 2 deficiencies include inadequate roofing that could cause deterioration of integral building systems, and conditions affecting building envelopes, such as roof and window replacements.
Priority 3 – Short-Term Conditions: Deficiencies that are necessary to the school's mission but may not require immediate attention. These items should be considered necessary improvements required to maximize facility efficiency and usefulness. Examples of Priority 3 items include site improvements and plumbing deficiencies.
Priority 4 – Long-Term Requirements: Items or systems that may be considered improvements to the instructional environment. The improvements may be aesthetic or provide greater functionality. Examples include cabinets, finishes, paving, removal of abandoned equipment, and educational accommodations associated with special programs.
Priority 5 – Enhancements: Deficiencies aesthetic in nature or considered enhancements. Typical deficiencies in this priority include repainting, replacing carpet, improved signage, or other improvements to the facility environment.
9M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Table 1: System by Priority
Priority
System 1 2 3 4 5 Total % of Total
Site - - $12,452 $521,265 $453,262 $986,978 5.45 %
Roofing - $102,675 - - - $102,675 0.57 %
Structural - - - - - $0 0.00 %
Exterior - $2,403,767 - - - $2,403,767 13.27 %
Interior - - $2,245,366 $1,594,643 $731,371 $4,571,380 25.23 %
Mechanical - $3,571,287 $42,991 $482,926 - $4,097,204 22.61 %
Electrical - $319,206 $88,918 $5,514 $113,148 $526,786 2.91 %
Plumbing - - $1,414,290 $226,224 $85,840 $1,726,355 9.53 %
Fire and Life Safety $503,830 - - - - $503,830 2.78 %
Technology - - $2,988,024 - - $2,988,024 16.49 %
Conveyances - - - - - $0 0.00 %
Specialties - - $13,690 $139,879 $59,894 $213,463 1.18 %
Total $503,830 $6,396,936 $6,805,730 $2,970,451 $1,443,515 $18,120,462
*Displayed totals may not sum exactly due to mathematical rounding
The following chart summarizes this site's current deficiencies by building system and priority. The listing details current deficiencies including deferred maintenance, functional deficiencies, code compliance, capital renewal, hazardous materials and technology categories.
The building systems with the most need include:Interior - $4,571,380Mechanical - $4,097,204Technology - $2,988,024
The chart below represents the building systems and associated deficiency costs.
Figure 2: System Deficiencies
10M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Current Deficiencies by Category
Deficiencies have been further grouped according to the observed category.
• Acoustics deficiencies relate to room acoustics, sound insolation, and mechanical systems and vibration control modeled after ANSI/ASA Standard S12.60-2010 and ASHRAE Handbook, Chapter 47 on Sound and Vibration Control.
• Barrier to Accessibility deficiencies relate to the Americans with Disabilities Act and the Rhode Island Governors Commission on Disability. Additional items related to accessibility may be included other categories.
• Capital Renewal items have reached or exceeded serviceable life and require replacement. These are current and do not include life cycle capital renewal forecasts. Also included are deficiencies correcting planned work postponed beyond its regular life expectancy.
• Code Compliance deficiencies related to current codes. Many may fall under grandfather clauses, which allow buildings to continue operating under codes effective at the time of construction. However, there are instances where the level of renovation requires full compliance which are reflected in the master plan.
• Educational Adequacy deficiencies identify where facilities do not align with the Basic Education Program and the RIDE School Construction Regulations. • Functional Deficiencies are deficiencies for components or systems that have failed before the end of expected life or are not the right application, size, or design.
• Hazardous Materials include deficiencies for building systems or components containing potentially hazardous material. The team focused on identifying asbestos containing building materials (ACBMs), lead based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. With other scopes of work there may be other costs associated with hazardous materials.
• Technology deficiencies relate to network architecture, technology infrastructure, classroom systems, and support. Examples of technology deficiencies include: security cameras, secure electronic access, telephone handsets, and dedicated air conditioning for telecommunication rooms.
• Traffic deficiencies relate to vehicle or pedestrian traffic, such as bus loops, crosswalks, and pavement markings.
11M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Table 2: Deficiency Category by PriorityPriority
Category 1 2 3 4 5 Total
Acoustics - - - $178,731 - $178,731
Barrier to Accessibility - - $160,097 - - $160,097
Capital Renewal - $6,396,936 $3,582,587 $1,270,107 $750,651 $12,000,281
Code Compliance $503,830 - - - - $503,830
Educational Adequacy - - $65,028 $1,469,477 $692,864 $2,227,369
Functional Deficiency - - $59,066 - - $59,066
Hazardous Material - - - $52,136 - $52,136
Technology - - $2,936,686 - - $2,936,686
Traffic - - $2,266 - - $2,266
Total $503,830 $6,396,936 $6,805,730 $2,970,451 $1,443,515 $18,120,462
*Displayed totals may not sum exactly due to mathematical rounding
The following chart and table represent the deficiency category by priority. This listing includes current deficiencies for all building systems.
12M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Life Cycle Capital Renewal Projections
System Current DeficienciesYear 12017
Year 22018
Year 32019
Year 42020
Year 52021 LC Yr. 1-5 Total Total 5-Year Need
Site $986,978 $0 $0 $0 $0 $0 $0 $986,978
Roofing $102,675 $0 $0 $0 $0 $0 $0 $102,675
Structural $0 $0 $0 $0 $0 $0 $0 $0
Exterior $2,403,767 $0 $0 $0 $466,440 $250,271 $716,711 $3,120,478
Interior $4,571,380 $0 $0 $917,509 $154,150 $5,947 $1,077,606 $5,648,986
Mechanical $4,097,204 $0 $0 $70,869 $0 $871,591 $942,460 $5,039,664
Electrical $526,786 $0 $0 $0 $0 $0 $0 $526,786
Plumbing $1,726,355 $0 $0 $235,035 $0 $0 $235,035 $1,961,390
Fire and Life Safety $503,830 $0 $0 $0 $0 $0 $0 $503,830
Technology $2,988,024 $0 $0 $0 $0 $0 $0 $2,988,024
Conveyances $0 $0 $0 $285,209 $0 $0 $285,209 $285,209
Specialties $213,463 $0 $0 $0 $0 $1,001,683 $1,001,683 $1,215,146
Total $18,120,462 $0 $0 $1,508,622 $620,590 $2,129,492 $4,258,704 $22,379,166
*Displayed totals may not sum exactly due to mathematical rounding
Life Cycle Capital Renewal ForecastDuring the facility condition assessment, assessors inspected all major building systems. If a need for immediate replacement was identified, a deficiency was created with the estimated repair costs. The identified deficiency contributes to the facility's total current repair costs.
Capital planning scenarios span multiple years, as opposed to being constrained to immediate repairs. Construction projects may begin several years after the initial facility condition assessment. Therefore, in addition to the current year repair costs, it is necessary to forecast the facility's future costs using a 5-year life cycle renewal forecast model.
Life cycle renewal is the projection of future building system costs based upon each individual system’s expected serviceable life. Building systems and components age over time, eventually break down, reach the end of their useful lives, and may require replacement. While an item may be in good condition now, it might reach the end of its life before a planned construction project occurs.
The following chart shows all current deficiencies and the subsequent 5-year life cycle capital renewal projections. The projections outline costs for major building systems in which a component is expected to reach the end of its useful life and require capital funding for replacement.
Table 3: Capital Renewal Forecast
13M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Facility Condition Index (FCI)The Facility Condition Index (FCI) is used throughout the facility condition assessment industry as a general indicator of a building’s health. Since 1991, the facility management industry has used an index called the FCI to benchmark the relative condition of a group of schools. The FCI is derived by dividing the total repair cost, including educational adequacy and site-related repairs, by the total replacement cost. A facility with a higher FCI percentage has more need, or higher priority, than a facility with a lower FCI. It should be noted that costs in the New Construction category are not included in the FCI calculation.
For master planning purposes, the total current deficiencies and the first five years of projected life cycle needs were combined. This provides an understanding of the current needs of a facility as well as the projected needs in the near future. A 5-year FCI was calculated by dividing the 5-year need by the total replacement cost. Costs associated with new construction are not included in the FCI calculation.
Figure 5: 5-Year FCI
Financial modeling has shown that over a 30-year period, it is more cost effective to replace than repair schools with a FCI of 65 percent or greater. This is due to efficiency gains with facilities that are more modern and the value of the building at the end of the analysis period. It is important to note that the FCI at which a facility should be considered for replacement is typically debated and adjusted based on property owners and facility managers approach to facility management. Of course, FCI is not the only factor used to identify buildings that need renovation, replacement, or even closure. Historical significance, enrollment trends, community sentiment, and the availability of capital are additional factors that are analyzed when making school facility decisions.
The replacement value represents the estimated cost of replacing the current building with another building of like size, based on today’s estimated cost of construction in the Providence, Rhode Island area. The estimated replacement cost for this facility is $64,275,120. For planning purposes, the total 5-year need at the Mt. Hope High School is $22,406,303 (Life Cycle Years 1-5 plus the FCI deficiency cost). The Mt. Hope High School facility has a 5-year FCI of 34.82%.
It is important to reiterate that this FCI replacement threshold is not conclusive, but is intended to initiate planning discussion in which other relevant issues with regard to a facility’s disposition must be incorporated. This merely suggests where conversations regarding replacement might occur.
14M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
The capacity of a school reflects how many students the school’s physical facility can effectively serve. There are various methodologies that exist to calculate capacity. It is not uncommon to review an existing building only to find that the capacity that had once been assigned is greater than what can be reasonably accommodated today. This is primarily because of a change in how programs are delivered.
The Rhode Island Aspirational Capacity is based on the Rhode Island School Construction Regulations (SCRs) and is an aspirational goal of space use. The capacity for each individual public school in the state of Rhode Island was designed to conform to Section 1.06-2 Space Allowance Guidelines of the Rhode Island Department of Education (RIDE) SCRs. These regulations outline the allowed gross square feet (GSF) per student at each school type (ES, MS, HS) by utilizing a sliding scale based on projected enrollment. The resulting capacities reflect how school capacities align to the SCRs for new construction. The existing enrollment was multiplied by the GSF per student for the appropriate bracket. For the purposes of this analysis, Pre-K centers were rolled into the elementary totals, and K-8 facilities were counted as middle schools.
The most consistent and equitable way a state can determine school capacities across a variety of districts and educational program offerings is to use square-foot-per-student standards. In contrast, in the 2013 Public Schoolhouse Assessment Report, LEAs self-reported capacities for their elementary, middle and high schools. Districts typically report “functional capacity,” which is defined as the number of students each classroom can accommodate. Functional capacity counts how many students can occupy a space, not how much room students and teachers have within that space. For example, a 650-square-foot classroom and a 950-square-foot classroom can both have a reported capacity of 25 students, but the actual teaching and learning space per student varies greatly.
The variation in square feet per student impacts the kinds of teaching practices possible in each space. The lowest allocation of space per student restricts group and project-based learning strategies and requires teachers to teach in more traditional, lecture-style formats, due to a lack of space. Furthermore, the number of students that can be accommodated in a classroom does not account for access to sufficient common spaces such as libraries, cafeterias, and gymnasiums. When cafeterias are undersized relative to the population, schools must host four or more lunch periods a day, resulting in some students eating lunch mid-morning and some mid-afternoon. Similarly, undersized libraries and gymnasiums create scheduling headaches for schools and restrict student access. Finally, a classroom count-only approach to school capacity does not consider the inherent scheduling challenges schools face.
Rhode Island Aspirational Capacity
Applying the Rhode Island Aspirational Capacity, a facility of this size could ideally support an enrollment of approximately 950 students.
As part of the Educational Program Space Assessment, select core spaces were compared to the RI School Construction Regulations. If it was determined that a facility was in need of square footage related to a cafeteria or library/media center, a cost for additional space was estimated. This cost is not included in the total 5-year need or the 5-year FCI calculation.
Facility New Construction
The New Construction cost to bring the Mt. Hope High School cafeteria and/or library/media center to the size prescribed by the SCRs is estimated to be $0.
15M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Table 4: Facility Condition by Building
Gross Sq Ft Year BuiltCurrent
Deficiencies LC Yr. 1-5 TotalTotal 5 Yr Need
(Yr 1-5 + Current Defs) 5-Year FCI
Mt. Hope High School Totals 177,732 1965 $18,147,599 $4,258,704 $22,406,303 34.82%
*Displayed totals may not sum exactly due to mathematical rounding
The following pages provide a listing of all current deficiencies and 5-year life cycle need and the associated costs, followed by photos taken during the assessment.
The Mt. Hope High School comprises 177,732 square feet and was constructed in 1965. Current deficiencies at this school total $18,147,599. Five year capital renewal costs total $4,258,704. The total identified need for the Mt. Hope High School (current deficiencies and 5-year capital renewal costs) is $22,406,303. The 5-year FCI is 34.82%.
Summary of Findings
As part of the assessment process, LEAs were given several opportunities to provide feedback on the data. Jacobs performed a thorough review of the comments provided relating to the Facilities Condition Assessment. Based on information provided, some adjustments were made to improve or refine the dataset. In other situations, enough information was not provided, item was out of scope, or evidence provided by assessment team did not align with the feedback and no adjustment was made. Finally, deficiency priorities, costs, and educational space/technology standards are consistent throughout the state.
Cost estimates are derived from local cost estimating expertise and enhanced by industry best practices, historical cost data, and relevance to the Rhode Island region. Costs have been developed from current market rates as of the 2nd quarter in 2016. All costs are based on a replace-in-kind approach, unless the item was not in compliance with national or state regulations or standards. For planning and budgeting purposes, facility assessments customarily add a soft cost multiplier onto deficiency repair cost estimates. This soft cost multiplier accounts for costs that are typically incurred when contracting for renovation and construction services. Soft costs typically include construction cost factors, such as contractor overhead and profit, as well as labor and material inflation, professional fees, and administrative costs. Based on the Rhode Island School Construction Regulations, a soft cost multiplier of 20% is included on all cost estimates. Other project allowances are included in the cost estimates based on school attributes such as age, location, and historic designation. All stated costs in the assessment report will include soft costs for planning and budgeting purposes. These are estimates, and costs will vary at the time of construction.
Cost Estimating
LEA Feedback
16M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Site Level DeficienciesSiteDeficiency Category Qty UoM Priority Repair Cost ID
Asphalt Walks Require Replacement Capital Renewal 1,200 SF 3 $10,185 8583
Note: Asphalt walks have several large pot holes and cracks.
Location: Courtyard and front sidewalk
Pavement Markings: Words/Symbols Are Required Traffic 6 Ea. 3 $2,266 9314
Note: Add arrow pavement markings on campus to control parent drop off/pick up flow
Asphalt Paving Requires Replacement Capital Renewal 150 CAR 4 $492,936 8582
Note: Asphalt pavement has several large pot holes and cracks.
Backstops Require Replacement Educational Adequacy
1 Ea. 4 $28,329 28409
Note: Backstops Require Replacement
School has insufficient baseball fields. Educational Adequacy
1 Ea. 5 $207,745 28313
Note: School has insufficient baseball fields.
School has insufficient football/soccer fields. Educational Adequacy
1 Ea. 5 $94,430 28184
Note: School has insufficient football/soccer fields.
School has insufficient softball fields. Educational Adequacy
1 Ea. 5 $151,087 28356
Note: School has insufficient softball fields.
Sub Total for System 7 items $986,978
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
The Pole Lighting Is Missing And Needed Functional Deficiency 3 Ea. 3 $59,066 8585
Note: Additional pole lighting is needed.
Sub Total for System 1 items $59,066
Sub Total for School and Site Level 8 items $1,046,044
Building: 01 - Main BuildingExteriorDeficiency Category Qty UoM Priority Repair Cost ID
Metal Edge Termination At Wall Requires Repair Capital Renewal 1 Ea. 2 $61 8602
The Aluminum Window Requires Replacement Capital Renewal 10,061 SF 2 $1,702,563 8587
The Metal Exterior Door Requires Replacement Capital Renewal 2 Door 2 $12,834 8586
Note: Doors rusted at bottom.
The Metal Panel Exterior Requires Replacement (Bldg SF) Capital Renewal 3,290 SF 2 $500,447 8624
Note: Original to the building.
Sub Total for System 4 items $2,215,906
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Interior CMU Walls Require Repair Capital Renewal 1,800 SF 3 $65,370 8626
Location: Corridor M, D205, D201, E101, A138, B101, B102, B106, B207
Interior Doors Require Replacement Capital Renewal 262 Door 3 $1,208,051 8590
Note: Interior wood doors are original, scratched, worn and need to be replaced.
The Acoustical Ceiling Tiles Require Replacement Capital Renewal 1,800 SF 3 $16,257 8588
Note: There are various stained, broken, and cracked acoustical ceiling tiles throughout the building in classrooms and corridors.
The Carpet Flooring Requires Replacement Capital Renewal 5,800 SF 3 $126,186 8591
Note: Carpet is frayed and worn.
The Ceramic Tile Flooring Requires Replacement Capital Renewal 15,000 SF 3 $402,806 8593
Note: Several areas have broken ceramic flooring and base.
The Existing Toilet Stall Does Not Meet Minimum ADA Requirements Barrier to Accessibility
10 Ea. 3 $29,472 8584
The Existing Toilet Stall Does Not Meet Minimum ADA Requirements Barrier to Accessibility
6 Ea. 3 $17,683 8599
Location: 2nd floor D wing, 1st floor D110, G wing, E101, 2nd floor B wing
17M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Interior Door Hardware Requires Replacement Barrier to Accessibility
36 Door 3 $112,943 9223
Note: Original to the building.
The Vinyl Composition Tile Requires Replacement Capital Renewal 20,000 SF 3 $229,435 8592
Location: Corridors D, M, C; 1st floor faculty room, mechanical room, E105, Dean's office, B208, C205, C210, C203, C201, C206
Light Deterioration or Damage of 9x9 Asbestos Floor Tile is Present Hazardous Material 6 SF 4 $171 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - each)
Hazardous Material 6 Ea. 4 $1,711 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - linear feet)
Hazardous Material 1,340 LF 4 $30,574 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - square feet)
Hazardous Material 2,070 SF 4 $19,679 Rollup
Room Is Excessively Reverberant Acoustics 8,000 SF 4 $178,731 19713
Note: Gym
Room Lighting Is Inadequate Or In Poor Condition. Educational Adequacy
35,135 SF 4 $1,338,782 Rollup
Vinyl Wall Covering Requires Replacement Capital Renewal 70 SF 4 $1,464 8612
Note: Wall laminate in elevator cab is chipped.
Classroom Door Requires Vision Panel Educational Adequacy
1 Ea. 5 $2,282 Rollup
Interior Ceramic Walls Require Repainting Capital Renewal 1,200 SF Wall
5 $9,127 8633
Note: Tile wall has paint peeling.
Interior Doors Require Repainting Capital Renewal 255 Door 5 $17,212 8589
Interior Walls Require Repainting (Bldg SF) Capital Renewal 23,974 SF 5 $158,404 Rollup
Room lacks appropriate sound control. Educational Adequacy
200 SF 5 $6,959 Rollup
The Concrete Flooring Requires Repair Or Repainting Capital Renewal 8,500 SF 5 $64,647 8594
Note: Floor in auditorium is chipped and worn and should be repainted.
The Gypsum Board Ceilings Require Repainting Capital Renewal 111,591 SF 5 $466,793 Rollup
Sub Total for System 23 items $4,504,739
MechanicalDeficiency Category Qty UoM Priority Repair Cost ID
Ductwork Requires Replacement (SF Basis) Capital Renewal 30,000 SF 2 $441,035 10952
Note: Original to the building.
Electric Unit Heater Requires Replacement Capital Renewal 9 Ea. 2 $12,227 8618
Replace Unit Vent Capital Renewal 70 Ea. 2 $1,184,036 8630
The Boiler HVAC Component Requires Replacement Capital Renewal 2 Ea. 2 $455,325 8595
Note: Original installation.
The Fan Coil HVAC Component Requires Replacement Capital Renewal 3 Ea. 2 $17,113 8627
The Fin Tube Water Radiant Heater Requires Replacement Capital Renewal 80 Ea. 2 $134,010 8619
The Mechanical / HVAC Piping / System Is Beyond Its Useful Life Capital Renewal 171,897 SF 2 $1,325,015 8620
Air Compressor Is Inoperable And Requires Replacement Capital Renewal 2 Ea. 3 $12,766 8613
Large HVAC Circulating Pump Requires Replacement Capital Renewal 2 Ea. 3 $30,225 8614
Existing Controls Are Inadequate And Should Be Replaced With DDC Controls Capital Renewal 42,974 SF 4 $290,277 8623
Note: Approximately 25% of the school has pneumatic controls that should be updated to DDC.
Lab lacks an appropriate fume hood. Educational Adequacy
4 Ea. 4 $87,943 Rollup
Small HVAC Circulating Pump Requires Replacement Capital Renewal 4 Ea. 4 $38,119 8608
Small HVAC Circulating Pump Requires Replacement Capital Renewal 6 Ea. 4 $45,770 8632
The Exhaust Hood Requires Replacement Capital Renewal 4 Ea. 4 $20,816 10953
Sub Total for System 14 items $4,094,677
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
Switchgear Is Needed Or Requires Replacement Capital Renewal 1 Ea. 2 $82,102 8609
The Panelboard Requires Replacement Capital Renewal 20 Ea. 2 $96,971 8615
The Panelboard Requires Replacement Capital Renewal 19 Ea. 2 $110,186 8616
The Panelboard Requires Replacement Capital Renewal 4 Ea. 2 $25,098 8617
18M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
The Mounted Building Lighting Requires Replacement Capital Renewal 20 Ea. 3 $29,852 10954
The Canopy Lighting Requires Replacement Capital Renewal 4 Ea. 4 $5,514 10955
Room Has Insufficient Electrical Outlets Educational Adequacy
228 Ea. 5 $113,148 Rollup
Sub Total for System 7 items $462,872
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Gas Water Heater Requires Replacement Capital Renewal 2 Ea. 3 $6,320 8610
The Gas Water Heater Requires Replacement Capital Renewal 1 Ea. 3 $3,113 8611
The Gas Water Heater Requires Replacement Capital Renewal 1 Ea. 3 $5,845 8629
The Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Capital Renewal 171,897 SF 3 $1,383,064 8607
Note: Water piping is old and deteriorating.
The Urinal Plumbing Fixtures Require Replacement Capital Renewal 12 Ea. 3 $15,949 8605
Non-Refrigerated Drinking Fountain Requires Replacement Capital Renewal 1 Ea. 4 $10,220 8598
The Custodial Mop Or Service Sink Requires Replacement Capital Renewal 7 Ea. 4 $18,035 8601
The Refrigerated Water Cooler Requires Replacement Capital Renewal 7 Ea. 4 $51,642 8606
The Restroom Lavatories Plumbing Fixtures Require Replacement Capital Renewal 45 Ea. 4 $143,146 8596
Room lacks a drinking fountain. Educational Adequacy
6 Ea. 5 $6,617 Rollup
Room lacks a private shower area. Educational Adequacy
2 Ea. 5 $20,470 Rollup
The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed Educational Adequacy
20 Ea. 5 $30,232 Rollup
Underground Fuel/Oil Storage Tank Requires Replacement Capital Renewal 1 Ea. 5 $28,521 8622
Sub Total for System 13 items $1,723,174
Fire and Life SafetyDeficiency Category Qty UoM Priority Repair Cost ID
Fire Alarm Is Missing Or Inadequate (NFPA 72 and NFPA 101, Section 9.6) Code Compliance 171,897 SF 1 $503,830 8603
Sub Total for System 1 items $503,830
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Room lacks Interactive White Board Educational Adequacy
9 Ea. 3 $51,338 Rollup
Technology: Auditorium AV/Multimedia system is in need of minor improvements. Technology 1 Room 3 $95,070 18391
Technology: Campus network switching electronics are antiquated and/or do not meet standards.
Technology 196 Ea. 3 $93,168 18389
Technology: Campus wireless infrastructure inadequate. Technology 65 Ea. 3 $86,513 18388
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 55 Ea. 3 $1,098,055 18394
Technology: Instructional spaces do not have local sound reinforcement. Technology 56 Ea. 3 $266,195 18399
Technology: Intermediate Telecommunications Room grounding system is inadequate or non-existent.
Technology 5 Ea. 3 $26,620 18385
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $37,648 18377
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $37,648 18378
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $37,648 18379
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $37,648 18380
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $37,648 18381
19M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Technology: Intermediate Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $37,648 18383
Technology: Intermediate Telecommunications Room needs minor improvements. Technology 1 Ea. 3 $16,732 18382
Technology: Intermediate Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 5 Ea. 3 $23,767 18384
Technology: Main Telecommunications Room ground system is inadequate or non-existent. Technology 1 Ea. 3 $6,655 18376
Technology: Main Telecommunications Room is not dedicated and/or inadequate. Technology 1 Ea. 3 $50,197 18374
Technology: Main Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 1 Ea. 3 $9,032 18375
Technology: Network cabling infrastructure is outdated (Cat 5 or less) and/or does not meet standards.
Technology 598 Ea. 3 $255,833 18390
Technology: Network cabling infrastructure is partially outdated and/or needs expansion. Technology 196 Ea. 3 $83,851 18395
Technology: Network system inadequate and/or near end of useful life Technology 32 Ea. 3 $152,112 18397
Technology: Network system inadequate and/or near end of useful life Technology 3 Ea. 3 $22,817 18398
Technology: PA/Bell/Clock system is inadequate and/or near end of useful life. Technology 171,879 SF 3 $294,129 18396
Technology: Telecommunications Room (small size room) needs dedicated cooling system improvements.
Technology 4 Ea. 3 $19,014 18387
Technology: Telecommunications Room fiber connectivity infrastructure is outdated and/or inadequate.
Technology 2 Ea. 3 $12,549 18386
Technology: Telephone handsets are inadequate and sparsely deployed throughout the campus.
Technology 60 Ea. 3 $91,267 18392
Technology: Telephone system is inadequate and/or non-existent. Technology 1 Ea. 3 $7,225 18393
Sub Total for System 27 items $2,988,024
SpecialtiesDeficiency Category Qty UoM Priority Repair Cost ID
Room has insufficient writing area. Educational Adequacy
3 Ea. 3 $13,690 Rollup
The Metal Student Lockers Require Replacement Capital Renewal 255 Ea. 4 $125,456 8625
Location: Boy's locker room
Welding Bays Are Required Educational Adequacy
2 Ea. 4 $10,838 Rollup
Work Tables Are Required Educational Adequacy
1 Ea. 4 $3,585 Rollup
Room lacks an appropriate refrigerator. Educational Adequacy
7 Ea. 5 $59,894 Rollup
Sub Total for System 5 items $213,463
Sub Total for Building 01 - Main Building 94 items $16,706,684
Building: 02 - StorageExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Exterior Wood Requires Replacement (Bldg SF) Capital Renewal 900 SF 2 $26,978 8635
The Metal Exterior Door Requires Replacement Capital Renewal 1 Door 2 $6,417 8634
Sub Total for System 2 items $33,395
Sub Total for Building 02 - Storage 2 items $33,395
20M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Building: 03 - MaintenanceRoofingDeficiency Category Qty UoM Priority Repair Cost ID
The Metal Roof Architectural Roof Covering Requires Replacement Capital Renewal 2,250 SF 2 $77,006 8639
Sub Total for System 1 items $77,006
ExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Metal Exterior Door Requires Replacement Capital Renewal 1 Door 2 $6,417 8636
The Overhead Door Requires Replacement Capital Renewal 1 Door 2 $36,792 8637
The Overhead Door Requires Replacement Capital Renewal 1 Door 2 $36,792 8638
Sub Total for System 3 items $80,001
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Interior Doors Require Replacement Capital Renewal 1 Door 3 $4,611 8640
Interior Wood Walls Require Replacement Capital Renewal 2,250 SF 4 $20,535 8646
Sub Total for System 2 items $25,146
MechanicalDeficiency Category Qty UoM Priority Repair Cost ID
Electric Unit Heater Requires Replacement Capital Renewal 2 Ea. 2 $2,527 8645
Sub Total for System 1 items $2,527
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
The Panelboard Requires Replacement Capital Renewal 1 Ea. 2 $4,849 8644
Sub Total for System 1 items $4,849
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Restroom Lavatories Plumbing Fixtures Require Replacement Capital Renewal 1 Ea. 4 $3,181 8641
Sub Total for System 1 items $3,181
Sub Total for Building 03 - Maintenance 9 items $192,710
Building: 04 - StorageRoofingDeficiency Category Qty UoM Priority Repair Cost ID
Shingle Roof Requires Replacement Capital Renewal 450 SF 2 $12,834 8647
Sub Total for System 1 items $12,834
ExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Exterior Wood Requires Replacement (Bldg SF) Capital Renewal 450 SF 2 $13,489 8649
The Metal Exterior Door Requires Replacement Capital Renewal 1 Door 2 $6,417 8648
Sub Total for System 2 items $19,906
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Wood Flooring Requires Replacement Capital Renewal 450 SF 3 $14,931 9225
The Wood Ceiling Tiles Require Replacement Capital Renewal 450 SF 4 $2,995 9224
Interior Walls Require Repainting (Bldg SF) Capital Renewal 450 SF 5 $2,973 Rollup
Sub Total for System 3 items $20,899
Sub Total for Building 04 - Storage 6 items $53,639
Building: 05 - StorageRoofingDeficiency Category Qty UoM Priority Repair Cost ID
Shingle Roof Requires Replacement Capital Renewal 450 SF 2 $12,834 8650
Sub Total for System 1 items $12,834
21M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Buildings with no reported deficiencies07 - Ticket Building
08 - Field Electrical Room
10 - Building 10
11 - Pump House
ExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Exterior Wood Requires Replacement (Bldg SF) Capital Renewal 450 SF 2 $13,489 8652
The Overhead Door Requires Replacement Capital Renewal 1 Door 2 $36,792 8651
Sub Total for System 2 items $50,281
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
Interior Walls Require Repainting (Bldg SF) Capital Renewal 450 SF 5 $2,973 Rollup
Sub Total for System 1 items $2,973
Sub Total for Building 05 - Storage 4 items $66,089
Building: 06 - ConcessionsExteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Steel Window Requires Replacement Capital Renewal 20 SF 2 $4,278 8653
Note: Window is cracked.
Sub Total for System 1 items $4,278
Sub Total for Building 06 - Concessions 1 items $4,278
Building: 09 - Portable AInteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Carpet Flooring Requires Replacement Capital Renewal 810 SF 3 $17,623 8712
Sub Total for System 1 items $17,623
Sub Total for Building 09 - Portable A 1 items $17,623
Total for Campus 125 items $18,120,462
22M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Mt. Hope High School - Life Cycle Summary Yrs 1-5Building: 01 - Main Building
ExteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Exterior Window Wall Storefront / Curtain Wall (Bldg SF) 3,240 SF $261,206 4
Exterior Entrance Doors Storefront Doors - Glass/Aluminum 25 Door $178,256 4
Exterior Entrance Doors Steel - Insulated and Painted 38 Door $243,854 5
Sub Total for System 3 items $683,315
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Interior Operable Partitions Moveable Partitions (Major) 3,060 SF Wall $353,460 3
Wood Flooring Wood Flooring - All Types 17,000 SF $564,049 3
Note: Gym
Interior Swinging Doors Steel 36 Door $154,150 4
Sub Total for System 3 items $1,071,658
MechanicalUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Decentralized Cooling Ductless Split System (1 Ton) 3 Ea. $42,348 3
Facility Distribution Systems Supplementary Components
Dehumidifier 1 Ea. $28,521 3
Exhaust Air Kitchen Exhaust Hoods 1 Ea. $15,964 5
HVAC Air Distribution AHU 5,000 CFM Outdoor 6 Ea. $855,627 5
Sub Total for System 4 items $942,460
PlumbingUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Plumbing Fixtures Classroom Lavatories 85 Ea. $231,114 3
Domestic Water Equipment Backflow Preventers - 2 in. (Ea.) 1 Ea. $3,921 3
Sub Total for System 2 items $235,035
ConveyancesUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Elevators Hydraulic (Passenger Elev) 1 Ea. $285,209 3
Sub Total for System 1 items $285,209
SpecialtiesUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Casework Lockers 2,036 Ea. $1,001,683 5
Sub Total for System 1 items $1,001,683
Sub Total for Building 01 - Main Building 14 items $4,219,361
Building: 02 - Storage
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Wall Painting and Coating Painting/Staining (Bldg SF) 900 SF $5,947 5
Sub Total for System 1 items $5,947
Sub Total for Building 02 - Storage 1 items $5,947
Building: 10 - Building 10
ExteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Exterior Wall Veneer Wood Siding - Bldg SF basis 900 SF $26,978 4
Sub Total for System 1 items $26,978
Sub Total for Building 10 - Building 10 1 items $26,978
23M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Building: 11 - Pump House
ExteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Exterior Entrance Doors Steel - Insulated and Painted 1 Door $6,417 5
Sub Total for System 1 items $6,417
Sub Total for Building 11 - Pump House 1 items $6,417
Total for: Mt. Hope High School 17 items $4,258,702
24M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Supporting Photos
Site Aerial
Gymnasium
Lockers
Auditorium
25M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Hallway Finishes
Wood Shop
Library
Press Box
Robotics Classroom
Art Room
26M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Pump House
Retractable Bleachers
Kitchen
Weight Room
Science Lab
Music Classroom
27M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Home Economics Classroom
Classroom
Computer Lab
Main Entrance
Site Signage
Greenhouse
28M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Exterior Door Rusted At Bottom
Poor Seals At Window
Stained Ceiling Tiles
Broken Window
Broken Ceiling Tile
Worn Wood Door
29M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Vandalized Interior Door
Worn Carpet
Cracked Parking Lot Pavement
Frayed Carpet In Office
Alligatoring Parking Lot Pavement
Pot Hole In Parking Lot
30M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Pot Hole In Asphalt Walkway
Cafeteria
Kitchen
Unlevel Walkway
Science Lab
Peeling Wall Paint
31M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Aged Pump
Weathered Wood Siding
Aged Panelboard
Rusted Exterior Door
Unit Heater
Weathered And Vandalized Wood Siding
32M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Maintenance Building Exterior
Storage Building 5 Exterior
Cabinet Unit Ventilator
Cracked Window At Concessions Building
Damaged Cabinet Unit Ventilator
Damaged Wall
33M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Chipped Paint
Worn CMU Wall
Damaged Locker Room Lockers
Aged Fan Coil Unit
Cracked CMU Wall
Finned Tube Radiator
34M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Aged Unit Heater
Aged Panelboard
Aged Air Compressors
Aged Panelboard
10 HP Circulating Pump
Switchboard
35M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Aged Pump
Damaged Drinking Fountain
Corroded Metal At Termination Wall
Aged Piping
Typical Urinal Fixtures
Aged Service Sink
36M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Non-Compliant Toilet Stalls
Worn Bathroom Sink
Chipped Paint On Auditorium Floor
Non-Refrigerated Drinking Fountain
Original Boilers
Cracked And Missing Ceramic Tile
37M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
Cracked VCT Flooring Stained And Broken VCT
38M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Mt. Hope High School
1225 Hope Street, Bristol, RI 02809
Facility Condition AssessmentBristol Warren - Rockwell School June 2017
1M▪A▪P▪P▪S ©, Jacobs 2017
Rockwell School, located at 1225 Hope Street in Bristol, Rhode Island, was built in 1951. It comprises 29,200 gross square feet. Each school across the district was visited three times during the Facility Condition Assessments by three teams of specialists in the spring/summer of 2016.
For master planning purposes a 5-year need was developed to provide an understanding of the current need as well as the projected needs in the near future. For Rockwell School the 5-year need is $4,042,956. The findings contained within this report resulted from an assessment of building systems performed by building professionals experienced in disciplines including: architecture, mechanical, plumbing, electrical, acoustics, hazardous materials, and technology infrastructure.
Figure 1: Aerial view of Rockwell School
Introduction
Rockwell School serves grades KG - 5, has 18 instructional spaces, and has an enrollment of 278. Instructional spaces are defined as rooms in which a student receives education. The LEA reported capacity for Rockwell School is 312 with a resulting utilization of 89%.
2M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Approach and MethodologyA facility condition assessment evaluates each building’s overall condition. Two components of the facility condition assessment are combined to total the cost for facility need. The two components of the facility condition assessment are current deficiencies and life cycle forecast.
Current Deficiencies: Deficiencies are items in need of repair or replacement as a result of being broken, obsolete, or beyond useful life. The existing deficiencies that currently require correction are identified and assigned a priority. An example of a current deficiency might include a broken lighting fixture or an inoperable roof top air conditioning unit.
Life Cycle Forecast: Life cycle analysis evaluates ages of a building's systems to forecast system replacement as they reach the end of serviceable life. An example of a life cycle system replacement is a roof with a 20-year life that has been in place for 15 years and may require replacement in five years.
Discipline Specialists
All assessment teams produced current deficiencies associated with each school. The assessment for the school facilities at the Rhode Island Department of Education included several specialties:
Facility Condition Assessment: Architectural, mechanical, and electrical engineering professionals observed conditions via a visual observation that did not include intrusive measures, destructive investigations, or testing. Additionally, the assessment incorporated input provided by district facilities and maintenance staff where applicable. The assessment team recorded existing conditions, identified problems and deficiencies, documented corrective action and quantities, and identified the priority of the repair in accordance with parameters defined during the planning phase. The team took digital photos at each school to better identify significant deficiencies.
Technology: Technology specialists visited RIDE facilities and met with technology directors to observe and assess each facility's technology infrastructure. The assessment included network architecture, major infrastructure components, classroom instructional systems, necessary building space and support for technology. The technology assessment took into account the desired technology outcome and best practices and processes to ensure results can be attained effectively.
Hazardous Materials: Schools constructed prior to 1990 were assessed by specialists to identify the presence of hazardous materials. The team focused on identifying asbestos containing building materials (ACBMs), lead-based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. If sampling and analysis was required, these activities were recommended but not included in the scope of work.
Traffic: A traffic specialist performed an in-office review of aerial imagery of the traffic infrastructure around the facilities in accordance with section 1.05-7 in the Rhode Island School Construction Regulations and reviewed data collected on site during the facility condition assessment. Based on this information, deficiencies and corrective actions were identified. High problem areas were identified for consideration of more detailed site-specific study and analysis in the future.
Acoustics: Specialists assessed each school's acoustics, including architectural acoustics, mechanical system noise and vibration, and environmental noise. The assessment team evaluated room acoustics with particular attention to the intelligibility of speech in learning spaces, interior and exterior sound isolation, and mechanical system noise and vibration control.
Educational Program Space Assessment: Teams evaluated schools to ensure that that all spaces adequately support the districts educational program. Standards are established for each classroom type or instructional space. Each space is evaluated to determine if it meets those standards and a listing of alterations that should be made to make the space a better environment for teaching and learning was created.
3M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
System Summaries
Building Envelope
The exterior systems for the building(s) at this campus includes:01 - Main Building: Brick Exterior Wall
Vinyl on Wood Frame Exterior WindowsSteel Exterior Entrance DoorsStorefront Entrance Doors
The roofing for the building(s) at this campus consists of:01 - Main Building: Composition Shingle Roofing
EPDM RoofingCanopy Roofing
Site
The site level systems for this campus include:Site Asphalt Parking Lot Pavement
Asphalt Roadway PavementAsphalt Pedestrian Pavement
Interior
The interior systems for the building(s) at this campus include:01 - Main Building: Wood Interior Doors
Overhead Interior Coiling DoorsInterior Door Hardware Suspended Acoustical Grid SystemSuspended Acoustical Ceiling TileCeramic Tile WallAcoustical Wall PanelingInterior Wall PaintingConcrete FlooringCeramic Tile FlooringVinyl Composition Tile FlooringCarpet
Mechanical
The mechanical systems for the building(s) at this campus include:
01 - Main Building: 1,275 MBH Cast Iron Water Boiler Steam/Hot Water Heating Unit Vent
The following tables summarize major building systems at the Rockwell School campus, identified by discipline and building.
4M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
01 - Main Building: Pneumatic Heating System ControlsWindow Units5 HP VFD 2-Pipe Hot Water Hydronic Distribution System 5 HP Pump Fire Sprinkler System
Electrical
The electrical systems for the building(s) at this campus include:01 - Main Building: 800 Amp Distribution Panel
Panelboard - 120/208 125APanelboard - 120/208 225ALight Fixtures Building Mounted Lighting Fixtures Canopy Mounted Lighting Fixtures
Plumbing
The plumbing systems for the building(s) at this campus include:01 - Main Building: 400 Gallon Electric Water Heater
Domestic Water Piping System Classroom LavatoriesMop/Service SinksRefrigerated Drinking FountainRestroom LavatoriesToiletsUrinalsAir Compressor (1 hp)
5M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Facility Deficiency Priority Levels
Deficiencies were ranked according to five priority levels, with Priority 1 items being the most critical to address:
Priority 1 – Mission Critical Concerns: Deficiencies or conditions that may directly affect the school’s ability to remain open or deliver the educational curriculum. These deficiencies typically relate to building safety, code compliance, severely damaged or failing building components, and other items that require near-term correction. An example of a Priority 1 deficiency is a fire alarm system replacement.
Priority 2 – Indirect Impact to Educational Mission: Items that may progress to a Priority 1 item if not addressed in the near term. Examples of Priority 2 deficiencies include inadequate roofing that could cause deterioration of integral building systems, and conditions affecting building envelopes, such as roof and window replacements.
Priority 3 – Short-Term Conditions: Deficiencies that are necessary to the school's mission but may not require immediate attention. These items should be considered necessary improvements required to maximize facility efficiency and usefulness. Examples of Priority 3 items include site improvements and plumbing deficiencies.
Priority 4 – Long-Term Requirements: Items or systems that may be considered improvements to the instructional environment. The improvements may be aesthetic or provide greater functionality. Examples include cabinets, finishes, paving, removal of abandoned equipment, and educational accommodations associated with special programs.
Priority 5 – Enhancements: Deficiencies aesthetic in nature or considered enhancements. Typical deficiencies in this priority include repainting, replacing carpet, improved signage, or other improvements to the facility environment.
6M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Table 1: System by Priority
Priority
System 1 2 3 4 5 Total % of Total
Site - - - $136,775 $69,827 $206,602 7.08 %
Roofing - $184,594 - - - $184,594 6.32 %
Structural - - - - - $0 0.00 %
Exterior - - - - - $0 0.00 %
Interior - - $26,156 $300,374 $172,894 $499,424 17.11 %
Mechanical - $225,079 $101,519 $197,237 - $523,836 17.94 %
Electrical - - - - $35,731 $35,731 1.22 %
Plumbing - $61,118 $234,940 $44,264 $16,527 $356,849 12.22 %
Fire and Life Safety $85,585 - - - - $85,585 2.93 %
Technology - - $1,022,437 - - $1,022,437 35.02 %
Conveyances - - - - - $0 0.00 %
Specialties - - $4,563 - - $4,563 0.16 %
Total $85,585 $470,791 $1,389,615 $678,650 $294,979 $2,919,621
*Displayed totals may not sum exactly due to mathematical rounding
The following chart summarizes this site's current deficiencies by building system and priority. The listing details current deficiencies including deferred maintenance, functional deficiencies, code compliance, capital renewal, hazardous materials and technology categories.
The building systems with the most need include:Technology - $1,022,437Mechanical - $523,836Interior - $499,424
The chart below represents the building systems and associated deficiency costs.
Figure 2: System Deficiencies
7M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Current Deficiencies by Category
Deficiencies have been further grouped according to the observed category.
• Acoustics deficiencies relate to room acoustics, sound insolation, and mechanical systems and vibration control modeled after ANSI/ASA Standard S12.60-2010 and ASHRAE Handbook, Chapter 47 on Sound and Vibration Control.
• Barrier to Accessibility deficiencies relate to the Americans with Disabilities Act and the Rhode Island Governors Commission on Disability. Additional items related to accessibility may be included other categories.
• Capital Renewal items have reached or exceeded serviceable life and require replacement. These are current and do not include life cycle capital renewal forecasts. Also included are deficiencies correcting planned work postponed beyond its regular life expectancy.
• Code Compliance deficiencies related to current codes. Many may fall under grandfather clauses, which allow buildings to continue operating under codes effective at the time of construction. However, there are instances where the level of renovation requires full compliance which are reflected in the master plan.
• Educational Adequacy deficiencies identify where facilities do not align with the Basic Education Program and the RIDE School Construction Regulations. • Functional Deficiencies are deficiencies for components or systems that have failed before the end of expected life or are not the right application, size, or design.
• Hazardous Materials include deficiencies for building systems or components containing potentially hazardous material. The team focused on identifying asbestos containing building materials (ACBMs), lead based painted (LBP) areas, polychlorinated biphenyls (PCBs), and chlorofluorocarbons (CFCs). As part of an indoor air and exterior air quality assessment, the team noted evidence of mold, water intrusion, mercury, and oil and hazardous materials (OHMs) exposure. With other scopes of work there may be other costs associated with hazardous materials.
• Technology deficiencies relate to network architecture, technology infrastructure, classroom systems, and support. Examples of technology deficiencies include: security cameras, secure electronic access, telephone handsets, and dedicated air conditioning for telecommunication rooms.
• Traffic deficiencies relate to vehicle or pedestrian traffic, such as bus loops, crosswalks, and pavement markings.
8M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Table 2: Deficiency Category by PriorityPriority
Category 1 2 3 4 5 Total
Acoustics - - $101,519 - - $101,519
Barrier to Accessibility - - - - - $0
Capital Renewal - $470,791 $261,095 $355,878 $172,894 $1,260,659
Code Compliance $85,585 - - - - $85,585
Educational Adequacy - - $4,563 $303,401 $122,085 $430,050
Functional Deficiency - - - $11,861 - $11,861
Hazardous Material - - - $7,511 - $7,511
Technology - - $1,022,437 - - $1,022,437
Traffic - - - - - $0
Total $85,585 $470,791 $1,389,615 $678,650 $294,979 $2,919,621
*Displayed totals may not sum exactly due to mathematical rounding
The following chart and table represent the deficiency category by priority. This listing includes current deficiencies for all building systems.
9M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Life Cycle Capital Renewal Projections
System Current DeficienciesYear 12017
Year 22018
Year 32019
Year 42020
Year 52021 LC Yr. 1-5 Total Total 5-Year Need
Site $206,602 $0 $0 $0 $0 $0 $0 $206,602
Roofing $184,594 $0 $0 $0 $0 $0 $0 $184,594
Structural $0 $0 $0 $0 $0 $0 $0 $0
Exterior $0 $0 $0 $0 $0 $0 $0 $0
Interior $499,424 $0 $0 $0 $219,087 $637,884 $856,971 $1,356,395
Mechanical $523,836 $0 $0 $0 $19,060 $12,024 $31,084 $554,920
Electrical $35,731 $0 $0 $0 $0 $0 $0 $35,731
Plumbing $356,849 $0 $162,645 $5,153 $0 $0 $167,798 $524,647
Fire and Life Safety $85,585 $0 $0 $0 $0 $0 $0 $85,585
Technology $1,022,437 $0 $0 $0 $0 $0 $0 $1,022,437
Conveyances $0 $0 $0 $0 $0 $0 $0 $0
Specialties $4,563 $0 $0 $0 $0 $61,006 $61,006 $65,569
Total $2,919,621 $0 $162,645 $5,153 $238,147 $710,914 $1,116,859 $4,036,480
*Displayed totals may not sum exactly due to mathematical rounding
Life Cycle Capital Renewal ForecastDuring the facility condition assessment, assessors inspected all major building systems. If a need for immediate replacement was identified, a deficiency was created with the estimated repair costs. The identified deficiency contributes to the facility's total current repair costs.
Capital planning scenarios span multiple years, as opposed to being constrained to immediate repairs. Construction projects may begin several years after the initial facility condition assessment. Therefore, in addition to the current year repair costs, it is necessary to forecast the facility's future costs using a 5-year life cycle renewal forecast model.
Life cycle renewal is the projection of future building system costs based upon each individual system’s expected serviceable life. Building systems and components age over time, eventually break down, reach the end of their useful lives, and may require replacement. While an item may be in good condition now, it might reach the end of its life before a planned construction project occurs.
The following chart shows all current deficiencies and the subsequent 5-year life cycle capital renewal projections. The projections outline costs for major building systems in which a component is expected to reach the end of its useful life and require capital funding for replacement.
Table 3: Capital Renewal Forecast
10M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Facility Condition Index (FCI)The Facility Condition Index (FCI) is used throughout the facility condition assessment industry as a general indicator of a building’s health. Since 1991, the facility management industry has used an index called the FCI to benchmark the relative condition of a group of schools. The FCI is derived by dividing the total repair cost, including educational adequacy and site-related repairs, by the total replacement cost. A facility with a higher FCI percentage has more need, or higher priority, than a facility with a lower FCI. It should be noted that costs in the New Construction category are not included in the FCI calculation.
For master planning purposes, the total current deficiencies and the first five years of projected life cycle needs were combined. This provides an understanding of the current needs of a facility as well as the projected needs in the near future. A 5-year FCI was calculated by dividing the 5-year need by the total replacement cost. Costs associated with new construction are not included in the FCI calculation.
Figure 5: 5-Year FCI
Financial modeling has shown that over a 30-year period, it is more cost effective to replace than repair schools with a FCI of 65 percent or greater. This is due to efficiency gains with facilities that are more modern and the value of the building at the end of the analysis period. It is important to note that the FCI at which a facility should be considered for replacement is typically debated and adjusted based on property owners and facility managers approach to facility management. Of course, FCI is not the only factor used to identify buildings that need renovation, replacement, or even closure. Historical significance, enrollment trends, community sentiment, and the availability of capital are additional factors that are analyzed when making school facility decisions.
The replacement value represents the estimated cost of replacing the current building with another building of like size, based on today’s estimated cost of construction in the Providence, Rhode Island area. The estimated replacement cost for this facility is $10,220,000. For planning purposes, the total 5-year need at the Rockwell School is $4,042,956 (Life Cycle Years 1-5 plus the FCI deficiency cost). The Rockwell School facility has a 5-year FCI of 39.50%.
It is important to reiterate that this FCI replacement threshold is not conclusive, but is intended to initiate planning discussion in which other relevant issues with regard to a facility’s disposition must be incorporated. This merely suggests where conversations regarding replacement might occur.
11M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
The capacity of a school reflects how many students the school’s physical facility can effectively serve. There are various methodologies that exist to calculate capacity. It is not uncommon to review an existing building only to find that the capacity that had once been assigned is greater than what can be reasonably accommodated today. This is primarily because of a change in how programs are delivered.
The Rhode Island Aspirational Capacity is based on the Rhode Island School Construction Regulations (SCRs) and is an aspirational goal of space use. The capacity for each individual public school in the state of Rhode Island was designed to conform to Section 1.06-2 Space Allowance Guidelines of the Rhode Island Department of Education (RIDE) SCRs. These regulations outline the allowed gross square feet (GSF) per student at each school type (ES, MS, HS) by utilizing a sliding scale based on projected enrollment. The resulting capacities reflect how school capacities align to the SCRs for new construction. The existing enrollment was multiplied by the GSF per student for the appropriate bracket. For the purposes of this analysis, Pre-K centers were rolled into the elementary totals, and K-8 facilities were counted as middle schools.
The most consistent and equitable way a state can determine school capacities across a variety of districts and educational program offerings is to use square-foot-per-student standards. In contrast, in the 2013 Public Schoolhouse Assessment Report, LEAs self-reported capacities for their elementary, middle and high schools. Districts typically report “functional capacity,” which is defined as the number of students each classroom can accommodate. Functional capacity counts how many students can occupy a space, not how much room students and teachers have within that space. For example, a 650-square-foot classroom and a 950-square-foot classroom can both have a reported capacity of 25 students, but the actual teaching and learning space per student varies greatly.
The variation in square feet per student impacts the kinds of teaching practices possible in each space. The lowest allocation of space per student restricts group and project-based learning strategies and requires teachers to teach in more traditional, lecture-style formats, due to a lack of space. Furthermore, the number of students that can be accommodated in a classroom does not account for access to sufficient common spaces such as libraries, cafeterias, and gymnasiums. When cafeterias are undersized relative to the population, schools must host four or more lunch periods a day, resulting in some students eating lunch mid-morning and some mid-afternoon. Similarly, undersized libraries and gymnasiums create scheduling headaches for schools and restrict student access. Finally, a classroom count-only approach to school capacity does not consider the inherent scheduling challenges schools face.
Rhode Island Aspirational Capacity
Applying the Rhode Island Aspirational Capacity, a facility of this size could ideally support an enrollment of approximately 162 students.
As part of the Educational Program Space Assessment, select core spaces were compared to the RI School Construction Regulations. If it was determined that a facility was in need of square footage related to a cafeteria or library/media center, a cost for additional space was estimated. This cost is not included in the total 5-year need or the 5-year FCI calculation.
Facility New Construction
The New Construction cost to bring the Rockwell School cafeteria and/or library/media center to the size prescribed by the SCRs is estimated to be $0.
12M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Table 4: Facility Condition by Building
Gross Sq Ft Year BuiltCurrent
Deficiencies LC Yr. 1-5 TotalTotal 5 Yr Need
(Yr 1-5 + Current Defs) 5-Year FCI
Rockwell School Totals 29,200 1951 $2,926,097 $1,116,859 $4,042,956 39.50%
*Displayed totals may not sum exactly due to mathematical rounding
The following pages provide a listing of all current deficiencies and 5-year life cycle need and the associated costs, followed by photos taken during the assessment.
The Rockwell School comprises 29,200 square feet and was constructed in 1951. Current deficiencies at this school total $2,926,097. Five year capital renewal costs total $1,116,859. The total identified need for the Rockwell School (current deficiencies and 5-year capital renewal costs) is $4,042,956. The 5-year FCI is 39.50%.
Summary of Findings
Cost estimates are derived from local cost estimating expertise and enhanced by industry best practices, historical cost data, and relevance to the Rhode Island region. Costs have been developed from current market rates as of the 2nd quarter in 2016. All costs are based on a replace-in-kind approach, unless the item was not in compliance with national or state regulations or standards. For planning and budgeting purposes, facility assessments customarily add a soft cost multiplier onto deficiency repair cost estimates. This soft cost multiplier accounts for costs that are typically incurred when contracting for renovation and construction services. Soft costs typically include construction cost factors, such as contractor overhead and profit, as well as labor and material inflation, professional fees, and administrative costs. Based on the Rhode Island School Construction Regulations, a soft cost multiplier of 20% is included on all cost estimates. Other project allowances are included in the cost estimates based on school attributes such as age, location, and historic designation. All stated costs in the assessment report will include soft costs for planning and budgeting purposes. These are estimates, and costs will vary at the time of construction.
Cost Estimating
13M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Site Level DeficienciesSiteDeficiency Category Qty UoM Priority Repair Cost ID
Asphalt Paving Requires Replacement Capital Renewal 33 CAR 4 $108,446 8789
Note: cracks and alligatoring
Backstops Require Replacement Educational Adequacy
1 Ea. 4 $28,329 28407
Note: Backstops Require Replacement
Exterior Basketball Goals are Required Educational Adequacy
1 Ea. 5 $5,807 28689
Note: Exterior Basketball Goals are Required
PE / Recess Playfield is Missing and is Needed Educational Adequacy
1 Ea. 5 $64,020 54860
Note: PE / Recess Playfield is Missing and is Needed
Sub Total for System 4 items $206,602
Sub Total for School and Site Level 4 items $206,602
Building: 01 - Main BuildingRoofingDeficiency Category Qty UoM Priority Repair Cost ID
EPDM Roofing Requires Replacement (Bldg SF) Capital Renewal 14,599 SF 2 $184,594 9226
Note: Inaccessible due to snow. Evidence of leaks present inside the building.
Sub Total for System 1 items $184,594
InteriorDeficiency Category Qty UoM Priority Repair Cost ID
The Vinyl Composition Tile Requires Replacement Capital Renewal 2,280 SF 3 $26,156 8790
Note: Lounge has chipped VCT, north corridor has curled and loose tiles, cracked VCT outside room 4
Ceiling Grid Requires Replacement Capital Renewal 500 SF 4 $5,930 8800
Note: Stained tiles in library, room 5, room 8, office, several corridors.
Ceiling Grid Requires Replacement Functional Deficiency 1,000 SF 4 $11,861 8801
Note: Water leak in girls restroom next to room 17 damaging tile.
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - each)
Hazardous Material 8 Ea. 4 $2,282 Rollup
Paint (probable pre-1978 in base layer(s)) - damaged area < 9 sq. ft. OR overall worn AND in children-accessible area (measurement unit - square feet)
Hazardous Material 550 SF 4 $5,229 Rollup
Room Lighting Is Inadequate Or In Poor Condition. Educational Adequacy
7,219 SF 4 $275,072 Rollup
Interior Walls Require Repainting (Bldg SF) Capital Renewal 26,167 SF 5 $172,894 Rollup
Sub Total for System 7 items $499,424
MechanicalDeficiency Category Qty UoM Priority Repair Cost ID
The Mechanical / HVAC Piping / System Is Beyond Its Useful Life Capital Renewal 29,200 SF 2 $225,079 8795
Unit Ventilators Are Excessively Noisy Acoustics 16 Ea. 3 $101,519 27968
Location: Classrooms
Existing Controls Are Inadequate And Should Be Replaced With DDC Controls Capital Renewal 29,200 SF 4 $197,237 8798
Note: Need to be upgraded to digital, past life expectancy
Sub Total for System 3 items $523,836
ElectricalDeficiency Category Qty UoM Priority Repair Cost ID
Room Has Insufficient Electrical Outlets Educational Adequacy
72 Ea. 5 $35,731 Rollup
Sub Total for System 1 items $35,731
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Electric Water Heater Requires Replacement Capital Renewal 1 Ea. 2 $61,118 8803
Note: Replace 530 gallon storage water heater
The Plumbing / Domestic Water Piping System Is Beyond Its Useful Life Capital Renewal 29,200 SF 3 $234,940 8794
14M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
PlumbingDeficiency Category Qty UoM Priority Repair Cost ID
The Refrigerated Water Cooler Requires Replacement Capital Renewal 6 Ea. 4 $44,264 8793
Room lacks a drinking fountain. Educational Adequacy
9 Ea. 5 $9,925 Rollup
The Class Room Lavatories Plumbing Fixtures Are Missing And Should Be Installed Educational Adequacy
6 Ea. 5 $6,601 Rollup
Sub Total for System 5 items $356,849
Fire and Life SafetyDeficiency Category Qty UoM Priority Repair Cost ID
Fire Alarm Is Missing Or Inadequate (NFPA 72 and NFPA 101, Section 9.6) Code Compliance 29,200 SF 1 $85,585 8791
Sub Total for System 1 items $85,585
TechnologyDeficiency Category Qty UoM Priority Repair Cost ID
Technology: Campus network switching electronics are antiquated and/or do not meet standards.
Technology 120 Ea. 3 $57,042 18420
Technology: Campus wireless infrastructure inadequate. Technology 26 Ea. 3 $34,605 18421
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 21 Ea. 3 $419,257 18426
Technology: Classroom AV/Multimedia systems are inadequate and/or near end of useful life.
Technology 1 Ea. 3 $19,965 18428
Technology: Instructional spaces do not have local sound reinforcement. Technology 22 Ea. 3 $104,577 18431
Technology: Main Telecommunications Room ground system is inadequate or non-existent. Technology 1 Ea. 3 $6,655 18418
Technology: Main Telecommunications Room is not dedicated. Room requires partial walls and/or major improvements.
Technology 1 Ea. 3 $42,591 18416
Technology: Main Telecommunications Room UPS does not meet standards, is inadequate, or non-existent.
Technology 1 Ea. 3 $9,032 18417
Technology: Network cabling infrastructure is outdated (Cat 5 or less) and/or does not meet standards.
Technology 48 Ea. 3 $20,535 18422
Technology: Network cabling infrastructure is partially outdated and/or needs expansion. Technology 72 Ea. 3 $30,803 18427
Technology: Network system inadequate and/or near end of useful life Technology 25 Ea. 3 $118,837 18430
Technology: PA/Bell/Clock system is inadequate and/or near end of useful life. Technology 29,200 SF 3 $49,969 18429
Technology: Special Space AV/Multimedia system is inadequate. Technology 1 Ea. 3 $54,190 18423
Technology: Telecommunications Room (large size room) needs dedicated cooling system improvements.
Technology 1 Ea. 3 $7,606 18419
Technology: Telephone handsets are inadequate and sparsely deployed throughout the campus.
Technology 26 Ea. 3 $39,549 18424
Technology: Telephone system is inadequate and/or non-existent. Technology 1 Ea. 3 $7,225 18425
Sub Total for System 16 items $1,022,437
SpecialtiesDeficiency Category Qty UoM Priority Repair Cost ID
Room has insufficient writing area. Educational Adequacy
1 Ea. 3 $4,563 Rollup
Sub Total for System 1 items $4,563
Sub Total for Building 01 - Main Building 35 items $2,713,018
Total for Campus 39 items $2,919,621
15M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Rockwell School - Life Cycle Summary Yrs 1-5Building: 01 - Main Building
InteriorUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Resilient Flooring Vinyl Composition Tile Flooring 19,098 SF $219,087 4
Resilient Flooring Vinyl Composition Tile Flooring 2,335 SF $26,787 5
Note: Sheet
Acoustical Suspended Ceilings Ceilings - Acoustical Grid System 29,200 SF $346,327 5
Acoustical Suspended Ceilings Ceilings - Acoustical Tiles 29,200 SF $263,723 5
Wall Paneling Acoustical Panel Wall 114 SF $1,047 5
Sub Total for System 5 items $856,971
MechanicalUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Facility Hydronic Distribution Pump - 5HP 2 Ea. $19,060 4
Other HVAC Distribution Systems VFD (5 HP) 2 Ea. $12,024 5
Sub Total for System 2 items $31,084
PlumbingUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Plumbing Fixtures Classroom Lavatories 17 Ea. $46,223 2
Plumbing Fixtures Restroom Lavatories 21 Ea. $66,802 2
Plumbing Fixtures Toilets 16 Ea. $45,633 2
Plumbing Fixtures Urinals 3 Ea. $3,987 2
Plumbing Fixtures Mop/Service Sinks 2 Ea. $5,153 3
Sub Total for System 5 items $167,798
SpecialtiesUniformat Description LC Type Description Qty UoM Repair Cost Remaining Life
Casework Lockers 124 Ea. $61,006 5
Sub Total for System 1 items $61,006
Sub Total for Building 01 - Main Building 13 items $1,116,859
Total for: Rockwell School 13 items $1,116,859
16M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Supporting Photos
Site Aerial
Restroom Paint
530 Gallon Water Heater
Playground
17M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Gym
Typical Classroom
Lockers
Front Elevation
Library
Sidewalk
18M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Main Entry
VCT North Corridor
VCT Outside Room 4
Kitchen
Cracks
Typical Restroom
19M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School
Piping
Stained Tile
Cracks
VCT In Lounge
Piping
Typical Corridor Paint
20M▪A▪P▪P▪S ©, Jacobs 2017
Facility Condition AssessmentBristol Warren - Rockwell School