Armor Shield Tank Lining & Tank Repair an AmTech Coatings, LLC company TANK REPAIR & LINING REPORT by Armor Shield Tank Lining & Tank Repair 74-4 Main Street, Suite 300 Plymouth, NH 03264 888.839.0373 FAX: 603.947.9500 www.armorshieldlining.com Report Reviewed and Approved by Robert Pearlman NLPA Special Inspector Sanbornton Store 666 Rte 127 Sanbornton, NH 03269 IQRA LLC 202 Victory DR Client: Franklin, NH 03235

Transcript of Armor Shield

Armor ShieldTank Lining & Tank Repair

an AmTech Coatings, LLC company

TANK REPAIR & LINING REPORT

by

Armor ShieldTank Lining & Tank Repair74-4 Main Street, Suite 300

Plymouth, NH 03264888.839.0373 FAX: 603.947.9500

www.armorshieldlining.com

Report Reviewed and Approvedby

Robert PearlmanNLPA Special Inspector

Sanbornton Store666 Rte 127

Sanbornton, NH 03269

IQRA LLC202 Victory DR

Client:

Franklin, NH 03235

Sanbornton Store666 Rte 127Sanbornton, NH 03269 ,

Armor Shield

75-4 Main Street, Suite 300Plymouth, NH 03264

888.839.0373 FAX: 603.947.9500

Tank Lining & Repair

LOCATION:

DATE OF SERVICE:

CLIENT:

TANK DESCRIPTION:

IQRA LLC

ENTRANCE:

202 Victory DR

PREPARATION:

INSPECTION:

Friday, September 16, 2011

REPAIR PROCESS:

One 15,000 gallon, two compartment, double walled UST (11k/4k). Steel Inner shell and FRP outer shell. Permeations(s) reported from the primary containment 11k section.

CLOSING:

The tank(s) was purged and vented. LEL was monitored. When LEL reached entrancelevels, the AS crew cut & entered the tank(s), using OSHA approved Confined Space Protocols.

OVERSIGHT:

The tank(s) was de-sludged and abrasively blasted. All sludge and spent blast media was removedto DOT approved 55 gallon drums (Drums were left onsite for disposal by client).

Inspection of the tank's interior was performed in accordance with API 1631 and NLPA 631 protocols.Heavy pitting was present at the bottom of the 11k tank in an area of approximately two square feet. One large permeation (approximately 1/4 inch diameter) were near the striker plate. Light tomoderate Pitting was present near bulkhead striker plate.

Welded patches were used to seal the permeation and then both the patch and tank pitting were covered using fiberglass/resin composite (11k).The tank(s) was then spray-coated with a product compatible, immersion resistant material:ArmorShield TL-300M, applied in accordance with NLPA 631 standard.

NLPA INSPECTOR: R. McQuillian, ForemanCertification #: NLPA Special Inspector: SNT-TC-1A NY-0033-04-1C Level C PA: 3761 PA DEP Certified NJ: 15665 DEP Install-Entire

The tank coating(s) was allowed to cure, and inspected for workmanship and material integrity. The tank was then sealed. The tank was then recommissioned and returned to control of the client's location personnel.

Sanbornton Store 666 Rte 127 Sanbornton, NH 03269

Franklin, NH 03235,

,

,

,

2

Sanbornton Store666 Rte 127Sanbornton, NH 03269 ,

Armor Shield

75-4 Main Street, Suite 300Plymouth, NH 03264

888.839.0373 FAX: 603.947.9500

Tank Lining & Repair

Tank opened, installation of 18" man way

Permeation near striker plate had been located (11k)

3

Sanbornton Store666 Rte 127Sanbornton, NH 03269 ,

Armor Shield

75-4 Main Street, Suite 300Plymouth, NH 03264

888.839.0373 FAX: 603.947.9500

Tank Lining & Repair

Permeation near striker plate (11k)

Fiberglass applied over welded patches and pitting (11k)

4

Sanbornton Store666 Rte 127Sanbornton, NH 03269 ,

Armor Shield

75-4 Main Street, Suite 300Plymouth, NH 03264

888.839.0373 FAX: 603.947.9500

Tank Lining & Repair

Tank lined with ArmorShield TL-300M (11k)

Tank lined with ArmorShield TL-300M (11k)

5

Sanbornton Store666 Rte 127Sanbornton, NH 03269 ,

Armor Shield

75-4 Main Street, Suite 300Plymouth, NH 03264

888.839.0373 FAX: 603.947.9500

Tank Lining & Repair

Man way installed and sealed

6