Draft Pemeliharaan Transmisi

196
STANDAR PT PLN (PERSERO) SPLN S5.002: 2008 Lampiran Surat Keputusan Direksi PT PLN (PERSERO) No. .K/DIR/2008 Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik PT PLN (PERSERO) JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU JAKARTA SELATAN 12160 DRAF STANDAR BIDANG

Transcript of Draft Pemeliharaan Transmisi

Page 1: Draft Pemeliharaan Transmisi

STANDAR PT PLN (PERSERO)

SPLN S5.002: 2008 Lampiran Surat Keputusan Direksi

PT PLN (PERSERO) No. .K/DIR/2008

Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga

Listrik

PT PLN (PERSERO)

JALAN TRUNOJOYO BLOK M-I/135 KEBAYORAN BARU

JAKARTA SELATAN 12160

DRAF STANDAR BIDANG

Page 2: Draft Pemeliharaan Transmisi

Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga

Listrik

Disusun oleh:

Kelompok Bidang SCADA dengan Surat Keputusan Direksi

PT PLN (Persero) No.094.K/DIR/2006

Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik

dengan Surat Keputusan General Manager PT PLN (Persero) Penelitian dan Pengembangan Ketenagalistrikan

No. 006.K/LITBANG/2007

Diterbitkan oleh:

PT PLN (PERSERO) Jalan Trunojoyo Blok M-I /135, Kebayoran Baru

Jakarta Selatan

Page 3: Draft Pemeliharaan Transmisi

Susunan Kelompok Bidang SCADA Standardisasi

Surat Keputusan Direksi PT PLN (Persero) No: 094.K/DIR/2006

1. Ir. Nur Pamudji, M.Eng, MPM : Sebagai Ketua merangkap Anggota

2. Ir. Harry Hartoyo, MM, MPM : Sebagai Wakil Ketua merangkap Anggota

3. Ir. Hernadi Buhron : Sebagai Sekretaris merangkap Anggota

4. Novrizal Erdiansyah, ST : Sebagai Wakil Sekretaris merangkap Anggota

5. Ir. Solida : Sebagai Anggota

6. Ir. Sudibyo : Sebagai Anggota

7. Agus H Maulana, ST : Sebagai Anggota

8. Ir. Joko Pramono : Sebagai Anggota

9. Ir. A. Sugeng Sugarjito : Sebagai Anggota

10. Ir. Yarid Pabisa : Sebagai Anggota

11. Ir. Ruly Chaerul : Sebagai Anggota

12. Ir. Herry Santoso : Sebagai Anggota

13. Ir. Yanuar I. Prakoso : Sebagai Anggota

14. Ir. Hesti Sayoga : Sebagai Anggota

15. Ir. Deany EA Rumengan : Sebagai Anggota

Susunan Kelompok Kerja Teleinformasi Data Untuk Pemeliharaan Instalasi

Sistem Tenaga Listrik Surat Keputusan General Manager PT PLN (Persero) Litbang Ketenagalistrikan

No: 004.K/LITBANG/2007

1. Ir. Solida : Sebagai Ketua merangkap Anggota

2. Novrizal Erdiansyah, ST : Sebagai Sekretaris merangkap Anggota

3. Ir. A. Sugeng Sugarjito : Sebagai Anggota

4. Ir. Ruly Chaerul : Sebagai Anggota

5. Tri Hardimasyar, ST : Sebagai Anggota

6. Ir. Yarid Pabisa : Sebagai Anggota

7. Ir. Joko Pramono : Sebagai Anggota

8. Ir. Denden Ruhdani : Sebagai Anggota

Page 4: Draft Pemeliharaan Transmisi
Page 5: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

i

Daftar Isi

Daftar Isi .................................................................................................................................i

Daftar Tabel .........................................................................................................................iii

Daftar Gambar.....................................................................................................................iv

Daftar Gambar.....................................................................................................................iv

Daftar Lampiran ...................................................................................................................v

Prakata ................................................................................................................................vii

1. Ruang Lingkup ............................................................................................. 1

2. Tujuan........................................................................................................... 1

3. Acuan Normatif............................................................................................. 1

4. Istilah dan Definisi ........................................................................................ 1 4.1 Alarm ................................................................................................................................. 1 4.2 Control center .................................................................................................................... 2 4.3 Distribution control center (DCC) ....................................................................................... 2 4.4 Feeder colouring ................................................................................................................ 2 4.5 Gardu hubung .................................................................................................................... 2 4.6 Gardu induk ....................................................................................................................... 2 4.7 Gardu tengah ..................................................................................................................... 2 4.8 Inter distribution control center (IDCC) ............................................................................... 2 4.9 Inter regional control center (IRCC) ................................................................................... 2 4.10 Keypoint ............................................................................................................................. 2 4.11 Maintenance center............................................................................................................ 2 4.12 National control center (NCC) ............................................................................................ 3 4.13 Operator............................................................................................................................. 3 4.14 Regional control center (RCC) ........................................................................................... 3 4.15 Regu pemeliharaan............................................................................................................ 3 4.16 Supervisory control and data acquisition (SCADA) ............................................................ 3 4.17 Telecontrol ......................................................................................................................... 3 4.18 Telesignal........................................................................................................................... 3 4.19 Telemetering ...................................................................................................................... 3

5. Umum........................................................................................................... 3 5.1 Fasilitas SCADA ................................................................................................................ 3 5.2 Teleinformasi data.............................................................................................................. 4

Page 6: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

ii

5.3 Struktur informasi ............................................................................................................... 4 5.4 Simbol dan warna .............................................................................................................. 4

6. Perbatasan Kebutuhan Teleinformasi Data ................................................. 4 6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC...................................... 5 6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC....................................... 6

Lampiran A – Daftar Teleinformasi (Transmisi)............................................................. 7

Lampiran B – Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk)................................................................................................................................... 17

Lampiran C – Daftar Teleinformasi (Distribusi) ......................................................... 131

Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) .......................................................................................................................... 139

Lampiran E – Struktur Informasi .................................................................................. 172

Lampiran F – Simbol dan Warna ................................................................................. 180

Page 7: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

iii

Daftar Tabel Tabel 1. Struktur informasi ............................................................................................ 173 Tabel 2. Level tegangan ................................................................................................ 175 Tabel 3. Nama bay atau feeder .................................................................................... 176 Tabel 4. Kode tegangan dari primer dan sekunder trafo.......................................... 176 Tabel 5. Kode nama peralatan/alarm/elemen ............................................................ 177 Tabel 6. Warna tampilan................................................................................................ 183

Page 8: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

iv

Daftar Gambar Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a).............................. 5 Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b).............................. 5 Gambar 3. Batas wewenang antara RCC dengan DCC .............................................. 6 Gambar 4. Struktur informasi khusus (bay diameter) ............................................... 178 Gambar 5. Struktur informasi khusus (gardu induk 1½ breaker)............................ 179 Gambar 6. Simbol gambar ............................................................................................ 181 Gambar 7. Tampilan status........................................................................................... 182

Page 9: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

v

Daftar Lampiran

Lampiran A – Daftar Teleinformasi (Transmisi) .............................................................7 A-1: Telesignal ................................................................................................................................. 8 A-2: Telemeasurement................................................................................................................... 14 A-3: Tap Changer Position............................................................................................................. 15 A-4: Remote Control Digital ........................................................................................................... 16

Lampiran B – Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk) ...................................................................................................................................17 TA-01: Konfigurasi Umum Pada 1½ Breaker ................................................................................. 18 TA-02: Konfigurasi Umum Pada Double Busbar ............................................................................ 28 TA-03: Konfigurasi Umum Pada Single Busbar ............................................................................. 39 TB-01: Generator Combined Cycle Pada Konfigurasi 1½ Breaker................................................. 50 TB-02: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1½ Breaker .......................... 52 TB-03: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar ..................... 54 TB-04: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar ...................... 56 TB-05: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker .......................... 58 TB-06: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar ..................... 60 TB-07: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar ...................... 62 TB-08: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker .......................... 64 TB-09: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar ..................... 66 TB-10: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar ...................... 68 TB-11: Interbus Transformer (Secondary Side Connected to 1½ Breaker).................................................................................. 70 TB-12: Interbus Transformer73 (Secondary Side Connected to Double Busbar)............................................................................. 73 TB-13: Interbus Transformer (Secondary Side Connected to Single Busbar) .............................................................................. 76 TB-14: Interbus Transformer (Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier) .. 79 TB-15: Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan

Tersier)............................................................................................................................... 82 TB-16: Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan

Tersier)............................................................................................................................... 85 TB-17: Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker ............................................................... 88 TB-18: Bay Trafo Tenaga Pada Konfigurasi Double Busbar .......................................................... 91 TB-19: Bay Trafo Tenaga Pada Konfigurasi Single Busbar ........................................................... 94 TB-20: Bay Reaktor Pada Konfigurasi 1 ½ Breaker ....................................................................... 97 TB-21: Bay Reaktor Pada Konfigurasi Double Busbar ................................................................... 98 TB-22: Bay Reaktor Pada Konfigurasi Single Busbar .................................................................. 100 TB-23: Bay Capasitor Pada Konfigurasi Double Busbar .............................................................. 102 TB-24: Bay Capasitor Pada Konfigurasi Single Busbar................................................................ 104 TB-25: Bay Penghantar Pada Konfigurasi 1 ½ Breaker ............................................................... 106 TB-26: Bay Penghantar Pada Konfigurasi Double Busbar ........................................................... 109 TB-27: Bay Penghantar Pada Konfigurasi Single Busbar ............................................................ 112 TB-28: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi Double Busbar .................... 115 TB-29: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½ Breaker ...................... 118 TB-30: Bay Penghantar Paralel Dengan 2 Reaktor Seri Pada Konfigurasi 1½ Breaker ............... 121 TB-31: Bay Kopel Pada Konfigurasi Double Busbar .................................................................... 124 TB-32: Bus Section ...................................................................................................................... 126 TB-33: Bay Diameter Pada Konfigurasi 1½ Breaker .................................................................... 128 TB-34: Bus Bar ............................................................................................................................ 130

Page 10: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

vi

Lampiran C – Daftar Teleinformasi (Distribusi) ......................................................... 131 C-1: Telesignal............................................................................................................................. 132 C-2: Telemeasurement ................................................................................................................ 136 C-3: Tap Changer Position........................................................................................................... 137 C-4: Remote Control Digital ......................................................................................................... 138

Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi) .......................................................................................................................... 139 DA-01: Konfigurasi Umum Pada Double Busbar.......................................................................... 140 DA-02: Konfigurasi Umum Pada Single Busbar ........................................................................... 143 DB-01: Trafo 150/20 kV dan 70/20 kV Tipe 1............................................................................... 146 DB-02: Trafo 150/20 kV dan 70/20 kV Tipe 2............................................................................... 148 DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3............................................................................... 150 DB-04: Generator Pada Konfigurasi Double Busbar .................................................................... 152 DB-05: Generator Pada Konfigurasi Single Busbar...................................................................... 154 DB-06: Feeder 20 kV Tipe 1 ........................................................................................................ 156 DB-07: Feeder 20 kV Tipe 2 ........................................................................................................ 158 DB-08: Feeder 20 kV Tipe 3 ........................................................................................................ 160 DB-09: Bus Section 20 kV Tipe 1................................................................................................. 162 DB-10: Bus section 20 kV Tipe 2 ................................................................................................. 163 DB-11: Kopel................................................................................................................................ 164 DB-12: Capacitor Bay .................................................................................................................. 165 DB-13: SUTM radial dengan keypoint dan PBO .......................................................................... 166 DB-14: SUTM radial dengan keypoint tanpa PBO........................................................................ 168 DB-15: SUTM loop dengan beberapa keypoint ............................................................................ 169 DB-16: Spindle 20 kV................................................................................................................... 170

Lampiran E – Struktur Informasi .................................................................................. 172 A. Nomor ID ................................................................................................................................. 173 B. Time stamp.............................................................................................................................. 175 C. Nama GI/GH/GT...................................................................................................................... 175 D. Level Tegangan....................................................................................................................... 175 E. Nama Bay / Feeder.................................................................................................................. 176 F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen.................................................. 177 G. Status Peralatan atau Status Alarm ........................................................................................ 177 H. Nama user yang melakukan aksi............................................................................................. 177 I. Prioritas Alarm .......................................................................................................................... 178 Struktur Informasi Khusus............................................................................................................ 178

Lampiran F – Simbol dan Warna ................................................................................. 180

Page 11: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

vii

Prakata Standar SCADA ini merupakan pengganti dari Pola SCADA SPLN No. 109 Tahun 1996, dalam rangka mengikuti perkembangan teknologi SCADA. Standar ini menjelaskan mengenai master station, komunikasi dan remote station yang terdiri dari enam bagian, yaitu: 1. S3.001 Peralatan SCADA sistem tenaga listrik 2. S5.001 Teleinformasi data untuk operasi jaringan tenaga listrik 3. S5.002 Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik 4. S4.001 Pengujian sistem SCADA 5. S6.001 Perencanaan dan pembangunan sistem SCADA 6. S7.001 Operasi dan pemeliharaan sistem SCADA Keenam standar di atas adalah yang telah diselesaikan dalam tahun 2007 dan direncanakan akan ditambah dengan beberapa standar lainnya mengenai SCADA. Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasi data, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi dan pemeliharaan yang memiliki hubungan dengan sistem SCADA. Standar ini dapat menjadi acuan dalam setiap perencanaan, pembangunan, operasi dan pemeliharaan sistem SCADA di PT PLN (Persero) secara nasional.

Page 12: Draft Pemeliharaan Transmisi
Page 13: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

1

Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik

1. Ruang Lingkup

Teleinformasi data terdiri dari telecontrol, telesignal dan telemetering. Sesuai dengan penggunaannya, teleinformasi data dibedakan untuk kepentingan operasi dan kebutuhan pemeliharaan. Standar ini dimaksudkan untuk menetapkan standar teleinformasi data yang diaplikasikan untuk kebutuhan pemeliharaan sistem tenaga listrik dan mencakup sistem transmisi dan sistem distribusi.

Standar ini, berlaku untuk sistem SCADA: a. National Control Center, disingkat NCC; b. Inter Regional Control Center, disingkat IRCC; c. Regional Control Center, disingkat RCC; d. Inter Distribution Control Center, disingkat IDCC; e. Distribution Control Center, disingkat DCC.

2. Tujuan

Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalam penerapan teleinformasi data bagi kebutuhan pemeliharaan sistem transmisi dan sistem distribusi tenaga listrik yang mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakan acuan dalam pembangunan sistem SCADA baru dan pengembangan sistem SCADA yang telah ada.

3. Acuan Normatif

Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam pembuatan standar SCADA: Teleinformasi Data Untuk Pemeliharaan Instalasi Sistem Tenaga Listrik.

a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol – Bagian 1: Pertimbangan Umum – Seksi 1: Prinsip Umum;

b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali;

4. Istilah dan Definisi

4.1 Alarm

Perubahan kondisi dari peralatan atau sistem yang telah terdeteksi sebelumnya karena fungsi yang tidak dilakukan oleh operator/dispatcher, atau kegagalan peralatan untuk merespon secara benar. Indikasi alarm berupa audible atau visual, atau keduanya.

Page 14: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

2

4.2 Control center

Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan.

4.3 Distribution control center (DCC)

Pusat kendali jaringan distribusi.

4.4 Feeder colouring

Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi bertegangan.

4.5 Gardu hubung

Gardu yang mempunyai fungsi utama melakukan manuver antar feeder.

4.6 Gardu induk

Gardu yang mempunyai fungsi sebagai pusat pembagi beban.

4.7 Gardu tengah

Gardu yang merupakan titik tengah beban atau titik tengah feeder.

4.8 Inter distribution control center (IDCC)

Pusat kendali yang terhubung dengan beberapa distribution control center.

4.9 Inter regional control center (IRCC)

Pusat kendali yang terhubung dengan beberapa regional control center.

4.10 Keypoint

Peralatan switching dimana bisa dilakukan manuver antara dua feeder atau lebih.

4.11 Maintenance center

Workstation di luar control center yang digunakan untuk keperluan pemeliharaan.

Page 15: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

3

4.12 National control center (NCC)

Pusat kendali yang terhubung dengan beberapa inter regional control center.

4.13 Operator

Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk.

4.14 Regional control center (RCC)

Pusat kendali jaringan transmisi tegangan tinggi.

4.15 Regu pemeliharaan

Petugas yang melakukan pemeliharaan pada instalasi sistem tenaga listrik.

4.16 Supervisory control and data acquisition (SCADA)

Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara geografis. [ IEC 870-1-3 ]

4.17 Telecontrol

Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik telekomunikasi. [IEV 371-01-01] Catatan – Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran, proteksi dan fasilitas tripping, tidak menggunakan pesan suara.

4.18 Telesignal

Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-04]

4.19 Telemetering

Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV 371-01-03]

5. Umum

5.1 Fasilitas SCADA

Setiap pembangunan pembangkit, gardu induk, gardu hubung, gardu tengah, key point dan fasilitas sistem tenaga listrik yang baru harus dapat dipantau dari control center dan

Page 16: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

4

dilakukan pengujian sebelum diintegrasikan ke sistem transmisi atau sistem distribusi tenaga listrik.

5.2 Teleinformasi data

Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik dapat dilihat pada pada Lampiran A – Daftar Teleinformasi (Transmisi) sampai dengan Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi). Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi maka master station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasi yang digunakan mengacu pada teleinformasi data transmisi dan distribusi.

Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik ditampilkan pada Maintenance Center dan Local HMI (Human Machine Interface). Konfigurasi workstation di luar control center yang difungsikan untuk Maintenance Center, menampilkan kebutuhan teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik, dapat dilihat pada SPLN S3.001 Butir 5.2 dan untuk Local HMI (Human Machine Interface) dapat dilihat pada SPLN S3.001 Butir 7.2.

Setiap pembangunan SCADA untuk fasilitas sistem tenaga listrik, kebutuhan teleinformasi datanya harus mengacu pada SPLN S5.001 (Teleinformasi data untuk operasi jaringan tenaga listrik) dan SPLN S5.002 (Teleinformasi data untuk pemeliharaan instalasi sistem tenaga listrik).

5.3 Struktur informasi

Event dan alarm pemeliharaan merupakan informasi kepada regu pemeliharaan dan operator tentang kejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di data historikal. Struktur informasi event dan alarm SCADA dapat dilihat pada Lampiran E – Struktur Informasi.

5.4 Simbol dan warna

Simbol dan warna diperlukan untuk penyajian diagram sistem tenaga listrik pada monitor dan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat informatif dan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenali oleh regu pemeliharaan dan operator. Simbol dan warna dapat dilihat pada Lampiran F – Simbol dan Warna.

6. Perbatasan Kebutuhan Teleinformasi Data

Teleinformasi data yang dikirim ke/dari suatu control center ditentukan oleh kewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelas antara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskan perbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC dan DCC.

Page 17: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

5

6.1 Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC

Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanan tegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 1 dan Gambar 2 berikut:

a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar

IRCC

RCC

BUSBAR TT

BUSBAR TET/TT

Gambar 1. Batas wewenang antara IRCC dengan RCC (Tipe-a)

b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1½ Breaker

IRCC

RCC

BUSBAR TT

BUSBAR TT

BUSBAR TET/TT

Gambar 2. Batas wewenang antara IRCC dengan RCC (Tipe-b)

Page 18: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

6

6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC

Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan pada Gambar 3.

B U S B A R T T

B U S B A R T M

L /R

PQVI

R C C

D C C

Gambar 3. Batas wewenang antara RCC dengan DCC

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belum dipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi data dapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOP yang berlaku di daerah tersebut.

Page 19: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

7

Lampiran A – Daftar Teleinformasi (Transmisi)

Page 20: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

8

A-1: Telesignal

No Kode Fungsi Implementasi Single (S) or Double (D) Indication

Alarm (A) or Event/

Indication (I)

1 BI Bus isolator switch closed/opened Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

2 CAM Capasitor Auto/Manual Capasitor D I

3 CB Circuit breaker closed/opened Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

4 CD Control disable switch RTU D I

5 CSO Check synchronizing override Gardu induk, Kopel, Feeder, Diameter

D I

6 DCBC Dummy breaker closed/opened Gardu induk D I

7 ES Earth Switch Closed/Opened Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

8 GUC Generator unit run/stop Generator D I 9 LFA Load frequency available/not available Generator D I 10 LFC Load frequency control on/off switch Generator D I 11 LFR Load frequency request on/off Generator D I 12 LI Line isolator switch closed/opened Feeder, Trafo D I

13 LR Local remote

Gardu induk, Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

D I

14 LRT Local remote switch for tapchanger Trafo D I 15 PSO Power station operated Generator D I

16 RACK Circuit Breaker Rack-In/Rack-Out Distribution Transformer D I

17 RMT Reset Master Trip Gardu induk D I

18 SAM Synchronization Auto/Manual Gardu induk, Kopel, Feeder, Trafo, Diameter

D I

19 TC Tap changer raise/lower Trafo D I 20 TCC Tap changer auto/manual Trafo D I 21 TFAM Transformer Fan Auto/Manual Transformer D I 22 110RF 110 VDC Rectifier failure Gardu Induk S A 23 110SF 110 VDC Supply failure Gardu Induk S A 24 220F 220 VAC Failure Gardu Induk S A 25 220RF 220 VDC Rectifier failure Gardu Induk S A 26 220SF 220 VDC Supply failure Gardu Induk S A 27 24RF 24 VDC Rectifier failure Gardu Induk S A 28 24SF 24 VDC Supply failure Gardu Induk S A 29 380F 380 VAC Failure Gardu Induk S A 30 48RF 48 VDC Rectifier failure Gardu Induk S A 31 48SF 48 VDC Supply failure Gardu Induk S A 32 AIRCF Air conditioning failure Gardu Induk S A 33 AQR Automatic power factor regulator Generator S I

Page 21: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

9

No Kode Fungsi Implementasi Single (S) or Double (D) Indication

Alarm (A) or Event/

Indication (I) active

34 AR Circuit breaker auto reclose Feeder S I 35 ARO Auto reclose off Feeder S I 36 AVR Automatic voltage regulator on/off Generator S I 37 BPA Busbar protection (a) Busbar S A 38 BPAF Busbar protection (a) failure Busbar S A 39 BPB Busbar protection (b) Busbar S A 40 BPBF Busbar protection (b) failure Busbar S A

41 CBDF Circuit breaker drive failure Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

S A

42 CBFA Circuit breaker failure (a) operate Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

S A

43 CBFB Circuit breaker failure (b) operate Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

S A

44 CBM Circuit breaker maintenance Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor

S I

45 CBTR Circuit breaker trip

Kopel, Feeder, Trafo, Diameter, Capasitor, Reaktor, Generator

S A

46 CCPA Circulating current protection (a) operate Diameter S A

47 CCPB Circulating current protection (b) operate Diameter S A

48 CCPF Circulating current protection failure Diameter S A 49 CDAF Current differential relay (a) failure Feeder S A 50 CDAR Current differential (a) phase R Feeder S A 51 CDAS Current differential (a) phase S Feeder S A 52 CDAT Current differential (a) phase T Feeder S A 53 CDBF Current differential relay (b) failure Feeder S A 54 CDBR Current differential (b) phase R Feeder S A 55 CDBS Current differential (b) phase S Feeder S A 56 CDBT Current differential (b) phase T Feeder S A 57 CF Carrier faulty Feeder S A 58 CSP Check synchronizing in progress Gardu induk S I 59 CTE Cabinet temperatur Remote station S I

60 DCF DC supply failure Kopel, Feeder, Trafo, Capasitor, Reaktor

S A

61 DCG DC ground Gardu Induk S A 62 DEARX Directional earth fault (a) relay receive Feeder S A 63 DEATX Directional earth fault (a) relay

transmit Feeder S A 64 DEBRX Directional earth fault (b) relay receive Feeder S A 65 DEBTX Directional earth fault (b) relay

transmit Feeder S A 66 DEFAF Directional earth fault (a) failure Feeder S A 67 DEFAR Directional earth fault (a) phase r Feeder S A 68 DEFAS Directional earth fault (a) phase s Feeder S A 69 DEFAT Directional earth fault (a) phase t Feeder S A

Page 22: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

10

No Kode Fungsi Implementasi Single (S) or Double (D) Indication

Alarm (A) or Event/

Indication (I) 70 DEFBF Directional earth fault (b) failure Feeder S A 71 DEFBR Directional earth fault (b) phase r Feeder S A 72 DEFBS Directional earth fault (b) phase s Feeder S A 73 DEFBT Directional earth fault (b) phase t Feeder S A 74 DFRF Disturbance fault recorder faulty Gardu Induk S A 75 DIFF Differential failure Trafo S A 76 DOOR Door activated Gardu Induk S I

77 DSDF Disconnecting switch driving fault Busbar, Kopel, Feeder, Trafo, Capasitor

S A

78 DTARX Direct transfer trip (a) receive Feeder S I 79 DTATX Direct transfer trip (a) transmit Feeder S I 80 DTBRX Direct transfer trip (b) receive Feeder S I 81 DTBTX Direct transfer trip (b) transmit Feeder S I 82 DZ1AR Distance (a) phase R zone 1 Feeder S A 83 DZ1AS Distance (a) phase S zone 1 Feeder S A 84 DZ1AT Distance (a) phase T zone 1 Feeder S A 85 DZ1BR Distance (b) phase R zone 1 Feeder S A 86 DZ1BS Distance (b) phase S zone 1 Feeder S A 87 DZ1BT Distance (b) phase T zone 1 Feeder S A 88 DZ2AR Distance (a) phase R zone 2 Feeder S A 89 DZ2AS Distance (a) phase S zone 2 Feeder S A 90 DZ2AT Distance (a) phase T zone 2 Feeder S A 91 DZ2BR Distance (b) phase R zone 2 Feeder S A 92 DZ2BS Distance (b) phase S zone 2 Feeder S A 93 DZ2BT Distance (b) phase T zone 2 Feeder S A 94 DZ3AR Distance (a) phase R zone 3 Feeder S A 95 DZ3AS Distance (a) phase S zone 3 Feeder S A 96 DZ3AT Distance (a) phase T zone 3 Feeder S A 97 DZ3BR Distance (b) phase R zone 3 Feeder S A 98 DZ3BS Distance (b) phase S zone 3 Feeder S A 99 DZ3BT Distance (b) phase T zone 3 Feeder S A 100 DZAF Distance relay (a) failure Feeder S A 101 DZARX Distance (a) relay receive Feeder S I 102 DZATX Distance (a) relay transmit Feeder S I 103 DZBF Distance relay (b) failure Feeder S A 104 DZBRX Distance (b) relay receive Feeder S I 105 DZBTX Distance (b) relay transmit Feeder S I

106 ERF Event recorder failure

Busbar, Kopel, Bus Section, Feeder, Trafo, Reaktor, Diameter

S A

107 FOTF FO terminal faulty Gardu Induk S A 108 FPO Fire protection operated Trafo S I 109 FRA Fire alarm Gardu Induk S A 110 FRSF Fire alarm system failure Gardu Induk S A

111 GFRF Ground fault relay failure

Gardu Induk, Kopel, Bus Section, Feeder, Trafo, Capasitor

S A

112 GOV Free acting governor active Generator S I

Page 23: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

11

No Kode Fungsi Implementasi Single (S) or Double (D) Indication

Alarm (A) or Event/

Indication (I) 113 GRE Genset ready Gardu Induk S I 114 GTT Generator transformer trip Trafo Generator S A 115 IR Internal remote station Remote Station S A 116 LFF Load frequency control unit failure Generator S A 117 LOWCT Low oil pressure cable trip Cable Feeder S A

118 LPA Low pressure alarm

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator

S A

119 LPB Low pressure block

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator

S A

120 LPT Low pressure trip

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter, Generator

S A

121 MTO Master trip operate Gardu Induk S A 122 OCPA Oil cable pressure alarm Cable Feeder S A

123 OCRF Over current relay failure Kopel, Bus Section, Feeder, Trafo, Capasitor

S A

124 OTA Oil temperature alarm Trafo S A 125 OTT Oil temperatur trip Trafo S A

126 OVR Over voltage relay operate Busbar, Feeder, Trafo, Capasitor S A

127 OVRF Over voltage relay failure Busbar, Feeder, Trafo, Capasitor S A

128 P1DIF Differential Trafo, Capasitor, Reaktor S A

129 P1REF Restricted earth fault Trafo S A

130 P2GFR Ground fault relay Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor

S A

131 P2OCR Over current relay Kopel, Feeder, Bus Section, Trafo, Reaktor, Capasitor

S A

132 PBXF PABX faulty Gardu Induk S A

133 PD Pole discrepancy

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

134 PHR Trip phase R

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

135 PHS Trip phase S

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

136 PHT Trip phase T

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

137 PLCF PLC terminal faulty Gardu Induk S A

Page 24: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

12

No Kode Fungsi Implementasi Single (S) or Double (D) Indication

Alarm (A) or Event/

Indication (I)

138 POT Protection on test

Busbar, Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S I

139 PRDT Pressure relay device trip Trafo, Reaktor 140 PTF Protection faulty Gardu induk S A 141 PWF Pilot wire failure Feeder S A 142 RADF Radio link faulty Gardu Induk S A 143 RBUC2 Reaktor bucholz trip Reaktor S A 144 RBUCA Reaktor bucholz alarm Reaktor S A

145 RCBF Relay circuit breaker fail failure

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

146 RCFF Reaktor cooling fan failure Reaktor S A 147 REFF Restrcited earth fault failure Trafo S A 148 RF Reactor failure Reaktor S A 149 RFDP Reaktor fire detection & protection Reaktor S A 150 ROLA Reaktor oil level alarm Reaktor S A 151 RSPA Reaktor sudden pressure alarm Reaktor S A 152 RSPT Reaktor sudden pressure trip Reaktor S A 153 RSTA Reset alarm Gardu Induk S I 154 RTN Relay tegangan nol Gardu Induk S I 155 RTUA Remote Station Alarm Gardu Induk S A 156 SIA Station intruder alarm Gardu Induk S A 157 SYNF Synchronizing failure Gardu induk S A

158 SZPA Short zone protection (a) operate

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

159 SZPB Short zone protection (b) operate

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

160 SZPF Short zone protection failure

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

161 TAF Tranformer AVR failure Trafo S A 162 TBUC2 Transformer Bucholz trip Trafo S A 163 TBUCA Transformer Bucholz alarm Trafo S A 164 TCA Tap changer alarm Trafo S A 165 TCFF Transformer cooling fan failure Trafo S A 166 TCH Tap changer high limit Trafo S A 167 TCL Tap changer low limit Trafo S A 168 TCPF Transformer cooling pump failure Trafo S A

169 TCS1 Trip coil supervisory 1

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

170 TCS2 Trip coil supervisory 2

Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor, Diameter

S A

Page 25: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

13

No Kode Fungsi Implementasi Single (S) or Double (D) Indication

Alarm (A) or Event/

Indication (I) 171 TFDP Transformer fire detection & protection Trafo S A 172 TJANT Transformer jansen trip Trafo S I 173 TOLA Transformer oil level alarm Trafo S I 174 TOOS Transformer out of step alarm Trafo 175 TPAF Teleprotection (a) failure Feeder 176 TPBF Teleprotection (b) failure Feeder S A 177 TPIF Tap position indication failure Trafo S A 178 TSPA Transformer sudden pressure alarm Trafo S A 179 TSPT Transformer sudden pressure trip Trafo S A 180 UFR Under frequency relay operate Feeder, Trafo S A 181 UT Unit trip Generator S A 182 UVR Under voltage relay Busbar S A

183 UVRF Under voltage relay failure Busbar, Feeder, Trafo S A

184 VS Voltage status Busbar S I

185 VTF Voltage transformer failure Busbar, Feeder, Trafo, Capasitor S A

186 WTHVA HV winding temperatur alarm Trafo S A 187 WTHVT HV winding temperatur trip Trafo S A 188 WTLVA LV winding temperatur alarm Trafo S A 189 WTLVT LV winding temperatur trip Trafo S A

Keterangan: A = Announciation of abnormal condition (audible alarm, flashing display, etc) I = Event/Indication (normal condition)

Page 26: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

14

A-2: Telemeasurement

No Kode Fungsi Implementasi

1 AMF Amperes fault ( per phase ) Feeder, Trafo, Capasitor Reaktor

2 CCB Counter of circuit breaker Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor

3 CNTA Counter arester Feeder, Trafo

4 CTPI Counter tap position indication Trafo

5 F Frekuensi Gardu induk

6 I Arus Feeder, Trafo, Kopel

7 KVARH Kilovar hour Feeder, Trafo

8 KWH Kilowatt hour Feeder, Trafo

9 P Daya Aktif Feeder, Trafo, Generator

10 POAQ Real power setting Generator

11 PRAQ Maksimum power variation setting Generator

12 PRES Pressure Kopel, Bus Section, Feeder, Trafo, Capasitor, Reaktor

13 Q Daya Reaktif Feeder, Trafo, Generator, Capasitor, Reaktor

14 RH Relative humidity Gardu Induk

15 TEMP Temperature Trafo, Reaktor

16 V Tegangan Feeder, Trafo, Generator, Busbar

Page 27: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

15

A-3: Tap Changer Position

No Kode Fungsi Implementasi

1 TPI Tap position indication Transformer

Page 28: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

16

A-4: Remote Control Digital

No Kode Fungsi Implementasi

1 BI Bus isolator switch closed/opened Kopel, Feeder, Transformer, Capasitor, Reaktor, Diameter

2 CB Circuit breaker closed/opened Kopel, Feeder, Transformer, Capasitor, Reaktor, Diameter

3 CD Control disable switch Remote Station

4 CSO Check synchronizing override Gardu induk

5 DCBC Dummy circuit breaker closed/opened Remote Station

6 LI Line isolator switch closed/opened Feeder, Transformer, Capasitor, Reaktor

7 LR Local remote Gardu Induk, Kopel, Bus Section, Feeder, Transformer, Capasitor, Reaktor, Diameter

8 LRT Local/remote switch for tapchanger Trafo

9 RMT Reset master trip Gardu Induk

10 SAM Synchronization auto/manual Gardu Induk, Kopel, Bus Section, Feeder, Transformer, Diameter

11 TC Tap changer raise/lower Trafo

12 TCC Tap changer auto/manual Trafo

13 TFAM Transformer fan auto/manual Trafo

Page 29: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

17

Lampiran B – Bidang Transmisi (Teleinformasi pada Berbagai Konfigurasi Gardu Induk)

Page 30: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

18

TA-01: Konfigurasi Umum Pada 1½ Breaker

KONFIGURASI UMUM PADA 1½ BREAKER

BUSBAR -A

TA-01

BUSBAR -B

Q

L/R

PQV

PQ

I

PQV

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBT BAY TRAFO TENAGA

VI

PQ

L/R

L/R

L/R

L/R

L/R

L/R

L/R

L/R

L/R

V

V

I

PQ

IV

Page 31: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

19

Teleinformasi Data Untuk Konfigurasi Umum Pada 1½ Breaker Group Bay Data No Kode Fungsi Tipe Jmh

1 F Frekuensi 1 TM 14 RH Relative humidity 1 22 110RF 110 VDC rectifier failure A 1 23 110SF 110 VDC supply failure A 1 24 220F 220 VAC failure A 1 25 220RF 220 VDC rectifier failure A 1 26 220SF 220 VDC supply failure A 1 27 24RF 24 VDC rectifier failure A 1 28 24SF 24 VDC supply failure A 1 29 380F 380 VAC failure A 1 30 48RF 48 VDC rectifier failure A 1 31 48SF 48 VDC supply failure A 1 32 AIRCF Air conditioning failure A 1 61 DCG DC ground A 1 76 DOOR Door activated A 1 107 FOTF FO terminal faulty A 1 109 FRA Fire alarm A 1 110 FRSF Fire alarm system failure A 1 111 GFRF Ground fault relay failure A 1 113 GRE Genset ready I 1 121 MTO Master trip operate A 1 132 PBXF Pabx faulty A 1 137 PLCF PLC terminal faulty A 1 142 RADF Radio link faulty A 1 153 RSTA Reset alarm A 1 154 RTN Relay tegangan nol A 1 155 RTUA Remote station alarm A 1

TSS

157 SIA Station intruder alarm A 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1 17 RMT Reset master trip I 1

TSD

18 SAM Synchronization auto/manual I 1 3 CSO Check synchronizing override 1 7 LR Local remote 1 9 RMT Reset master trip 1

GARDU INDUK

RCD

10 SAM Synchronization auto/manual 1 TM 7 V Tegangan 2

37 BPA Busbar protection (a) A 2 38 BPAF Busbar protection (a) failure A 2 39 BPB Busbar protection (b) A 2 40 BPBF Busbar protection (b) failure A 2 77 DSDF Disconnecting switch driving fault A 2 106 ERF Event recorder failure A 2 126 OVR Over voltage relay operate A 2 127 OVRF Over voltage relay failure A 2 138 POT Protection on test I 2 182 UVR Under voltage relay operate A 2 183 UVRF Under voltage relay failure A 2

BUSBAR

TSS

184 VS Voltage status I 2

Page 32: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

20

Group Bay Data No Kode Fungsi Tipe Jmh

TSD 7 ES Earth switch closed/opened I 2 59 CTE Cabinet temperatur A 1 TSS 115 IR Internal remote station A 1

TSD 4 CD Control disable switch I 1 3 CD Control disable switch 1

REMOTE STATION

RCD 5 DCBC Dummy circuit breaker

closed/opened 1

2 CCB Counter of circuit breaker 3 TM 12 PRES Pressure 3 41 CBDF Circuit breaker drive failure A 3 42 CBFA Circuit breaker failure (a) operate A 3 43 CBFB Circuit breaker failure (b) operate A 3 44 CBM Circuit breaker maintenance I 3

46 CCPA Circulating current protection (a) operate

A 1

47 CCPB Circulating current protection (b) operate

A 1

48 CCPF Circulating current protection failure

A 3

58 CSP Check synchronizing in progress I 3 106 ERF Event recorder failure A 3 118 LPA Low pressure alarm A 3 119 LPB Low pressure block A 3 120 LPT Low pressure trip A 3 133 PD Pole discrepancy A 3 134 PHR Trip phase R A 3 135 PHS Trip phase S A 3 136 PHT Trip phase T A 3 138 POT Protection on test I 1 145 RCBF Relay circuit breaker fail failure A 3 157 SYNF Synchronizing failure A 3 158 SZPA Short zone protection (a) operate A 3 159 SZPB Short zone protection (b) operate A 3 160 SZPF Short zone protection failure A 3 169 TCS1 Trip coil supervisory 1 A 3

TSS

170 TCS2 Trip coil supervisory 2 A 3

1 BI Bus isolator switch closed/opened I 6

3 CB Circuit breaker closed/opened I 3 5 CSO Check synchronizing override I 3 13 LR Local remote I 3

TSD

18 SAM Synchronization auto/manual I 3

1 BI Bus isolator switch closed/opened 6

2 CB Circuit breaker closed/opened 3 4 CSO Check synchronizing override 3 7 LR Local remote 3

DIAMETER

RCD

10 SAM Synchronization auto/manual 3 1 AMF Amperes fault ( per phase ) 1 3 CNTA *) Counter arester 1

BAY TRANSMISI

TM

6 I Arus 1

Page 33: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

21

Group Bay Data No Kode Fungsi Tipe Jmh

7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 16 V Tegangan 1

49 CDAF Current differential relay (a) failure

A 1

50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1

53 CDBF Current differential relay (b) failure

A 1

54 CDBR Current differential (b) phase R A 1 55 CDBS Current differential (b) phase S A 1 56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1

62 DEARX *) Directional earth fault (a) relay receive

A 1

63 DEATX *) Directional earth fault (a) relay transmit

A 1

64 DEBRX *) Directional earth fault (b) relay receive

A 1

65 DEBTX *) Directional earth fault (b) relay transmit

A 1

66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1

TSS

91 DZ2BR *) Distance (b) phase R zone 2 A 1

Page 34: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

22

Group Bay Data No Kode Fungsi Tipe Jmh

92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1 122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 7 ES Earth switch closed/opened I 1

TSD 12 LI Line isolator switch

closed/opened I 1

RCD 6 LI Line isolator switch closed/opened 1 TC 1 TPI Tap position indication I 1

1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1

BAY IBT TM

13 Q Daya reaktif 1

Page 35: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

23

Group Bay Data No Kode Fungsi Tipe Jmh

15 TEMP Temperature 1 16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1

171 TFDP Transformer fire detection & protection A 1

172 TJANT Transformer jansen trip A 1

TSS

173 TOLA Transformer oil level alarm A 1

Page 36: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

24

Group Bay Data No Kode Fungsi Tipe Jmh

174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1

178 TSPA Transformer sudden pressure alarm A 1

179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 2

12 LI Line isolator switch closed/opened I 1

13 LR Local remote I 1

14 LRT Local/remote switch for tapchanger I 1

18 SAM Synchronization auto/manual I 1 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1

6 LI Line isolator switch closed/opened 1

7 LR Local remote 1

8 LRT Local/remote switch for tapchanger 1

10 SAM Synchronization auto/manual 1 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 TC 1 TPI Tap position indication I 1

1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1

BAY TRAFO TENAGA

TSS

108 FPO Fire protection operated A 1

Page 37: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

25

Group Bay Data No Kode Fungsi Tipe Jmh

111 GFRF Ground fault relay failure A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer avr failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1

171 TFDP Transformer fire detection & protection A 1

172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1

178 TSPA Transformer sudden pressure alarm A 1

179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1

14 LRT Local/remote switch for tapchanger I 1

20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1

RCD 6 LI Line isolator switch closed/opened 1

Page 38: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

26

Group Bay Data No Kode Fungsi Tipe Jmh

8 LRT Local/remote switch for tapchanger 1

11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1 13 TFAM Transformer fan auto/manual 1 1 AMF Amperes fault ( per phase ) 1 12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1

TSS

160 SZPF Short zone protection failure A 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 TSD

21 TFAM Transformer fan auto/manual I 1

6 LI Line isolator switch closed/opened 1

BAY REAKTOR

RCD 13 TFAM Transformer fan auto/manual 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1

TSS

147 REFF Restricted earth fault failure A 1 7 ES Earth switch closed/opened I 1

TSD 12 LI Line isolator switch

closed/opened I 1

BAY GENERATOR

RCD 6 LI Line isolator switch closed/opened 1

KETERANGAN:

Page 39: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

27

*) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay

Page 40: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

28

TA-02: Konfigurasi Umum Pada Double Busbar

KONFIGURASI UMUM PADA DOUBLE BUSBAR

BUSBAR - A

TA-02

BUSBAR - B

Q P

PQ

I

PQV

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBTBAY TRAFO TENAGA

L/R

Q

BAY KOPEL

VI

L/R L/R

V

V

I

QP

V

L/R

L/R L/R L/R

PQ

IV

I

Page 41: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

29

Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Bay Data No Kode Fungsi Tipe Jmh

1 F Frekuensi 1 TM 14 RH Relative humidity 1 22 110RF 110 VDC rectifier failure A 1 23 110SF 110 VDC supply failure A 1 24 220F 220 VAC failure A 1 25 220RF 220 VDC rectifier failure A 1 26 220SF 220 VDC supply failure A 1 27 24RF 24 VDC rectifier failure A 1 28 24SF 24 VDC supply failure A 1 29 380F 380 VAC failure A 1 30 48RF 48 VDC rectifier failure A 1 31 48SF 48 VDC supply failure A 1 32 AIRCF Air conditioning failure A 1 61 DCG DC ground A 1 76 DOOR Door activated A 1 107 FOTF FO terminal faulty A 1 109 FRA Fire alarm A 1 110 FRSF Fire alarm system failure A 1 111 GFRF Ground fault relay failure A 1 113 GRE Genset ready I 1 121 MTO Master trip operate A 1 132 PBXF Pabx faulty A 1 137 PLCF PLC terminal faulty A 1 142 RADF Radio link faulty A 1 153 RSTA Reset alarm A 1 154 RTN Relay tegangan nol A 1 155 RTUA Remote station alarm A 1

TSS

157 SIA Station intruder alarm A 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1 17 RMT Reset master trip I 1

TSD

18 SAM Synchronization auto/manual I 1 3 CSO Check synchronizing override 1 7 LR Local remote 1 9 RMT Reset master trip 1

GARDU INDUK

RCD

10 SAM Synchronization auto/manual 1 TM 7 V Tegangan 2

37 BPA Busbar protection (a) A 2 38 BPAF Busbar protection (a) failure A 2 39 BPB Busbar protection (b) A 2 40 BPBF Busbar protection (b) failure A 2 77 DSDF Disconnecting switch driving fault A 2 106 ERF Event recorder failure A 2 126 OVR Over voltage relay operate A 2 127 OVRF Over voltage relay failure A 2 138 POT Protection on test I 2 182 UVR Under voltage relay operate A 2 183 UVRF Under voltage relay failure A 2

BUSBAR

TSS

184 VS Voltage status I 2

Page 42: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

30

Group Bay Data No Kode Fungsi Tipe Jmh

TSD 7 ES Earth switch closed/opened I 2 59 CTE Cabinet temperatur A 1 TSS 115 IR Internal remote station A 1

TSD 4 CD Control disable switch I 1 3 CD Control disable switch 1

REMOTE STATION

RCD 5 DCBC Dummy circuit breaker closed/opened 1 2 CCB Counter of circuit breaker 1 6 I Arus 1 TM 12 PRES Pressure 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1

TSS

170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1

TSD

18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 7 LR Local remote 1

KOPEL

RCD

10 SAM Synchronization auto/manual 1 1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1

BAY TRANSMISI

TM

3 CNTA *) Counter arester 1

Page 43: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

31

Group Bay Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 16 V Tegangan 1 34 AR *) Circuit breaker auto reclose I 1 35 ARO *) Auto reclose off I 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 49 CDAF Current differential relay (a) failure A 1 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) failure A 1 54 CDBR Current differential (b) phase R A 1 55 CDBS Current differential (b) phase S A 1 56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1

62 DEARX *) Directional earth fault (a) relay receive

A 1

63 DEATX *) Directional earth fault (a) relay transmit

A 1

64 DEBRX *) Directional earth fault (b) relay receive

A 1

65 DEBTX *) Directional earth fault (b) relay transmit

A 1

66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1

TSS

85 DZ1BR *) Distance (b) phase R zone 1 A 1

Page 44: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

32

Group Bay Data No Kode Fungsi Tipe Jmh

86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1

Page 45: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

33

Group Bay Data No Kode Fungsi Tipe Jmh

183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 1 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

10 SAM Synchronization auto/manual 1 TC 1 TPI Tap position indication I 1

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1

BAY IBT

TSS

130 P2GFR Ground fault relay A 1

Page 46: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

34

Group Bay Data No Kode Fungsi Tipe Jmh

131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1

171 TFDP Transformer fire detection & protection A 1

172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 2 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 18 SAM Synchronization auto/manual I 1 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1

RCD

7 LR Local remote 1

Page 47: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

35

Group Bay Data No Kode Fungsi Tipe Jmh

8 LRT Local/remote switch for tapchanger 1 10 SAM Synchronization auto/manual 1 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1 13 TFAM Transformer fan auto/manual 1

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1

BAY TRAFO TENAGA

TSS

147 REFF Restricted earth fault failure A 1

Page 48: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

36

Group Bay Data No Kode Fungsi Tipe Jmh

158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer avr failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1

171 TFDP Transformer fire detection & protection A 1

172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1 13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 16 RACK Circuit breaker rackin/rackout I 1 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 7 LR Local remote 1 8 LRT Local/remote switch for tapchanger 1 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1

BAY REAKTOR

TSS 41 CBDF Circuit breaker drive failure A 1

Page 49: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

37

Group Bay Data No Kode Fungsi Tipe Jmh

42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance A 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1 12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

13 TFAM Transformer fan auto/manual 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 106 ERF Event recorder failure A 1

BAY GENERATOR

TSS

114 GTT Generator transformer trip A 1

Page 50: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

38

Group Bay Data No Kode Fungsi Tipe Jmh

118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1 12 LI Line isolator switch closed/opened I 1

TSD

13 LR Local remote I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 6 LI Line isolator switch closed/opened 1

RCD

7 LR Local remote 1 KETERANGAN: *) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay

Page 51: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

39

TA-03: Konfigurasi Umum Pada Single Busbar

KONFIGURASI UMUM PADA SINGLE BUSBAR

BUSBAR

TA-03

QP

V

PQ

I

PQV

PQ

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBTBAY TRAFO TENAGA

Q

VI

V

I

PQ

L/R L/R L/R

L/R

L/R L/R

IV

Page 52: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

40

Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar

Group Bay Data No Kode Fungsi Tipe Jmh

1 F Frekuensi 1 TM 14 RH Relative humidity 1 22 110RF 110 VDC rectifier failure A 1 23 110SF 110 VDC supply failure A 1 24 220F 220 VAC failure A 1 25 220RF 220 VDC rectifier failure A 1 26 220SF 220 VDC supply failure A 1 27 24RF 24 VDC rectifier failure A 1 28 24SF 24 VDC supply failure A 1 29 380F 380 VAC failure A 1 30 48RF 48 VDC rectifier failure A 1 31 48SF 48 VDC supply failure A 1 32 AIRCF Air conditioning failure A 1 61 DCG DC ground A 1 76 DOOR Door activated A 1 107 FOTF FO terminal faulty A 1 109 FRA Fire alarm A 1 110 FRSF Fire alarm system failure A 1 111 GFRF Ground fault relay failure A 1 113 GRE Genset ready I 1 121 MTO Master trip operate A 1 132 PBXF Pabx faulty A 1 137 PLCF PLC terminal faulty A 1 142 RADF Radio link faulty A 1 153 RSTA Reset alarm A 1 154 RTN Relay tegangan nol A 1 155 RTUA Remote station alarm A 1

TSS

157 SIA Station intruder alarm A 1 5 CSO Check synchronizing override I 1 13 LR Local remote I 1 17 RMT Reset master trip I 1

TSD

18 SAM Synchronization auto/manual I 1 3 CSO Check synchronizing override 1 7 LR Local remote 1 9 RMT Reset master trip 1

GARDU INDUK

RCD

10 SAM Synchronization auto/manual 1 TM 7 V Tegangan 1

37 BPA Busbar protection (a) A 1 38 BPAF Busbar protection (a) failure A 1 39 BPB Busbar protection (b) A 1 40 BPBF Busbar protection (b) failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 138 POT Protection on test I 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1

BUSBAR

TSS

184 VS Voltage status I 1

Page 53: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

41

Group Bay Data No Kode Fungsi Tipe Jmh

TSD 7 ES Earth switch closed/opened I 1 59 CTE Cabinet temperatur A 1 TSS 115 IR Internal remote station A 1

TSD 4 CD Control disable switch I 1 3 CD Control disable switch 1

REMOTE STATION

RCD 5 DCBC Dummy circuit breaker

closed/opened 1

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1

TM

16 V Tegangan 1 34 AR *) Circuit breaker auto reclose I 1 35 ARO *) Auto reclose off I 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1

49 CDAF Current differential relay (a) failure

A 1

50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1

53 CDBF Current differential relay (b) failure

A 1

54 CDBR Current differential (b) phase R A 1 55 CDBS Current differential (b) phase S A 1 56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1

62 DEARX *) Directional earth fault (a) relay receive

A 1

63 DEATX *) Directional earth fault (a) relay transmit

A 1

64 DEBRX *) Directional earth fault (b) relay receive

A 1

65 DEBTX *) Directional earth fault (b) relay transmit

A 1

66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1

BAY TRANSMISI

TSS

72 DEFBS Directional earth fault (b) phase S A 1

Page 54: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

42

Group Bay Data No Kode Fungsi Tipe Jmh

73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1

Page 55: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

43

Group Bay Data No Kode Fungsi Tipe Jmh

145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1

1 BI Bus isolator switch closed/opened I 1

3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1

13 LR Local remote I 1

TSD

18 SAM Synchronization auto/manual I 1

1 BI Bus isolator switch closed/opened 1

2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

10 SAM Synchronization auto/manual 1 TC 1 TPI Tap position indication I 1

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1

BAY IBT

TSS

75 DIFF Differential failure A 1

Page 56: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

44

Group Bay Data No Kode Fungsi Tipe Jmh

77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1

171 TFDP Transformer fire detection & protection A 1

172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1

178 TSPA Transformer sudden pressure alarm A 1

179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1

Page 57: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

45

Group Bay Data No Kode Fungsi Tipe Jmh

189 WTLVT LV winding temperatur trip A 1

1 BI Bus isolator switch closed/opened I 1

3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 2 13 LR Local remote I 1

14 LRT Local/remote switch for tapchanger I 1

18 SAM Synchronization auto/manual I 1 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1

1 BI Bus isolator switch closed/opened 1

2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 7 LR Local remote 1

8 LRT Local/remote switch for tapchanger 1

10 SAM Synchronization auto/manual 1 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 TC 1 TPI Tap position indication I 1

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1 12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1

BAY TRAFO TENAGA

TSS

120 LPT Low pressure trip A 1

Page 58: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

46

Group Bay Data No Kode Fungsi Tipe Jmh

123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer avr failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1

171 TFDP Transformer fire detection & protection A 1

172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1

178 TSPA Transformer sudden pressure alarm A 1

179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1

1 BI Bus isolator switch closed/opened I 1 TSD

3 CB Circuit breaker closed/opened I 1

Page 59: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

47

Group Bay Data No Kode Fungsi Tipe Jmh

7 ES Earth switch closed/opened I 1 13 LR Local remote I 1

14 LRT Local/remote switch for tapchanger I 1

16 RACK Circuit breaker rackin/rackout I 1 20 TCC Tap changer auto/manual I 1 21 TFAM Transformer fan auto/manual I 1

1 BI Bus isolator switch closed/opened 1

2 CB Circuit breaker closed/opened 1 7 LR Local remote 1

8 LRT Local/remote switch for tapchanger 1

11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance A 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1

TSS

170 TCS2 Trip coil supervisory 2 A 1

1 BI Bus isolator switch closed/opened I 1

BAY REAKTOR

TSD

3 CB Circuit breaker closed/opened I 1

Page 60: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

48

Group Bay Data No Kode Fungsi Tipe Jmh

7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1

13 LR Local remote I 1 21 TFAM Transformer fan auto/manual I 1

1 BI Bus isolator switch closed/opened 1

2 CB Circuit breaker closed/opened 1

6 LI Line isolator switch closed/opened 1

7 LR Local remote 1

RCD

13 TFAM Transformer fan auto/manual 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1

TSS

170 TCS2 Trip coil supervisory 2 A 1

1 BI Bus isolator switch closed/opened I 1

3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1

TSD

13 LR Local remote I 1

1 BI Bus isolator switch closed/opened 1

2 CB Circuit breaker closed/opened 1

BAY GENERATOR

RCD

6 LI Line isolator switch 1

Page 61: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

49

Group Bay Data No Kode Fungsi Tipe Jmh

closed/opened 7 LR Local remote 1

KETERANGAN: *) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder A = Alarm I = Indikasi Rincian Teleinformasi diatas adalah rincian per bay

Page 62: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

50

TB-01: Generator Combined Cycle Pada Konfigurasi 1½ Breaker

GENERATOR COMBINED CYCLEPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-01

BUSBAR - B

PQ

V

Joint Control

I

PQ

PQI

PQI

V

PQ

V

PQ

V

PQ

Teleinformasi Data Untuk Generator Combined Cycle Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

6 I Arus 3 7 KVARH Kilovar hour 4 8 KWH Kilowatt hour 4 9 P Daya aktif 7 13 Q Daya reaktif 7

TM

16 V Tegangan 4 74 DFRF Disturbance fault recorder faulty A 3 75 DIFF Differential failure A 3

106 ERF Event recorder failure A 3 114 GTT Generator transformer trip A 3

TSS

129 P1REF Restricted earth fault A 3

Page 63: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

51

Data No Kode Fungsi Tipe Jmh

130 P2GFR Ground fault relay A 3 131 P2OCR Over current relay A 3 138 POT Protection on test A 3 147 REFF Restricted earth fault failure A 3 3 CB Circuit breaker closed/opened I 2 TSD 12 LI Line isolator switch closed/opened I 3

RCD 6 LI Line isolator switch closed/opened 3

Page 64: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

52

TB-02: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1½ Breaker

2 GENERATOR TERHUBUNG KE MTR 3-BELITANPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-02

BUSBAR - B

PQI

PQV

PQV

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 2 8 KWH Kilowatt hour 2 9 P Daya aktif 3 13 Q Daya reaktif 3

TM

16 V Tegangan 2 TSS 74 DFRF Disturbance fault recorder faulty A 1

Page 65: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

53

Data No Kode Fungsi Tipe Jmh

75 DIFF Differential failure A 1 106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 3 CB Circuit breaker closed/opened I 2 TSD 12 LI Line isolator switch closed/opened I 1

RCD 6 LI Line isolator switch closed/opened 1

Page 66: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

54

TB-03: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar

2 GENERATOR TERHUBUNG KE MTR 3-BELITANPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-03

BUSBAR - B

PQI

PQV

PQV

L/R

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 2 8 KWH Kilowatt hour 2 9 P Daya aktif 3 13 Q Daya reaktif 3

TM

16 V Tegangan 2 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1

TSS

129 P1REF Restricted earth fault A 1

Page 67: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

55

Data No Kode Fungsi Tipe Jmh

130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 3 7 ES Earth switch closed/opened I 1

TSD

13 LR Local remote I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 RCD 7 LR Local remote 1

Page 68: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

56

TB-04: 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar

2 GENERATOR TERHUBUNG KE MTR 3-BELITANPADA KONFIGURASI SINGLE BUSBAR

BUSBAR

TB-04

PQI

PQV

PQV

L/R

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 3-Belitan Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 2 8 KWH Kilowatt hour 2 9 P Daya aktif 3 13 Q Daya reaktif 3

TM

16 V Tegangan 2 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1

TSS

133 PD Pole discrepancy A 1

Page 69: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

57

Data No Kode Fungsi Tipe Jmh

134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 1 3 CB Circuit breaker closed/opened I 3 7 ES Earth switch closed/opened I 1

TSD

13 LR Local remote I 1 1 BI Bus isolator switch closed/opened 1 2 CB Circuit breaker closed/opened 1 RCD 7 LR Local remote 1

Page 70: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

58

TB-05: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker

1 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-05

BUSBAR - B

PQ

V

I

PQ

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1

TSS

129 P1REF Restricted earth fault A 1

Page 71: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

59

Data No Kode Fungsi Tipe Jmh

130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 7 ES Earth switch closed/opened I 1 TSD 12 LI Line isolator switch closed/opened I 1

RCD 6 LI Line isolator switch closed/opened 1

Page 72: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

60

TB-06: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar

1 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-06

BUSBAR - B

P

V

QI

PQ

L/R

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1

TSS

131 P2OCR Over current relay A 1

Page 73: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

61

Data No Kode Fungsi Tipe Jmh

133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

TSD

13 LR Local remote I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 RCD 7 LR Local remote 1

Page 74: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

62

TB-07: 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar

1 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI SINGLE BUSBAR

BUSBAR

TB-07

P

V

QI

PQ

L/R

Teleinformasi Data Untuk 1 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1

TSS

136 PHT Trip phase T A 1

Page 75: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

63

Data No Kode Fungsi Tipe Jmh

138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 1 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

TSD

13 LR Local remote I 1 1 BI Bus isolator switch closed/opened 1 2 CB Circuit breaker closed/opened 1 RCD 7 LR Local remote 1

Page 76: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

64

TB-08: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker

2 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-08

BUSBAR - B

PQI

PQV

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

TSS

106 ERF Event recorder failure A 1

Page 77: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

65

Data No Kode Fungsi Tipe Jmh

114 GTT Generator transformer trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 3 CB Circuit breaker closed/opened I 2 TSD 12 LI Line isolator switch closed/opened I 1

RCD 6 LI Line isolator switch closed/opened 1

Page 78: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

66

TB-09: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar

2 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-09

BUSBAR - B

PQI

PQV

L/R

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1

TSS

129 P1REF Restricted earth fault A 1

Page 79: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

67

Data No Kode Fungsi Tipe Jmh

130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 3 7 ES Earth switch closed/opened I 1

TSD

13 LR Local remote I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 RCD 7 LR Local remote 1

Page 80: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

68

TB-10: 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar

2 GENERATOR TERHUBUNG KE MTR 2-BELITANPADA KONFIGURASI SINGLE BUSBAR

BUSBAR

TB-10

PQI

PQV

L/R

Teleinformasi Data Untuk 2 Generator Terhubung ke MTR 2-Belitan Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 2 13 Q Daya reaktif 2

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 44 CBM Circuit breaker maintenance A 1 58 CSP Check synchronizing in progress A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1

106 ERF Event recorder failure A 1 114 GTT Generator transformer trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1

TSS

133 PD Pole discrepancy A 1

Page 81: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

69

Data No Kode Fungsi Tipe Jmh

134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 1 3 CB Circuit breaker closed/opened I 3 7 ES Earth switch closed/opened I 1

TSD

13 LR Local remote I 1 1 BI Bus isolator switch closed/opened 1 2 CB Circuit breaker closed/opened 1 RCD 7 LR Local remote 1

Page 82: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

70

TB-11: Interbus Transformer

(Secondary Side Connected to 1½ Breaker)

INTERBUS TRANSFORMERSecondary Side Connected to 1½ Breaker

BUSBAR - A

TB-11

BUSBAR - B

PQ

I

Dioperasikan dari IRCC

Dioperasikan dari RCC Download to RCC

BUSBAR (IRCC)

V

L/R

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1½ Breaker)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

TM

13 Q Daya reaktif 1

Page 83: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

71

Data No Kode Fungsi Tipe Jmh

15 TEMP Temperature 1 16 V Tegangan 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1

106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1

TSS

189 WTLVT LV winding temperatur trip A 1 7 ES Earth switch closed/opened I 2 12 LI Line isolator switch closed/opened I 2

TSD

14 LRT Local/remote switch for tapchanger I 1

Page 84: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

72

Data No Kode Fungsi Tipe Jmh

20 TCC Tap changer auto/manual I 1 21 TFAM Transformer fan auto/manual I 1 6 LI Line isolator switch closed/opened 2 8 LRT Local/remote switch for tapchanger 1 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 85: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

73

TB-12: Interbus Transformer

(Secondary Side Connected to Double Busbar)

INTERBUS TRANSFORMERSecondary Side Connected to Double Busbar

BUSBAR - A

TB-12

BUSBAR - B

BUSBAR (IRCC or RCC)

PQ

IV

Operation Responsibility by IRCC or RCC

Operation Responsibility by RCC

Download to RCC

L/R

L/R

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1-2 *) 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1

Page 86: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

74

Data No Kode Fungsi Tipe Jmh

41 CBDF Circuit breaker drive failure A 1-2 *) 42 CBFA Circuit breaker failure (a) operate A 1-2 *) 43 CBFB Circuit breaker failure (b) operate A 1-2 *) 44 CBM Circuit breaker maintenance I 1-2 *) 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1-2 *) 134 PHR Trip phase R A 1-2 *) 135 PHS Trip phase S A 1-2 *) 136 PHT Trip phase T A 1-2 *) 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1-2 *) 170 TCS2 Trip coil supervisory 2 A 1-2 *) 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1

TSS

177 TPIF Tap position indication failure A 1

Page 87: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

75

Data No Kode Fungsi Tipe Jmh

178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 2-4 *) 3 CB Circuit breaker closed/opened I 1-2 *) 5 CSO Check synchronizing override I 1-2 *) 7 ES Earth switch closed/opened I 2

12 LI Line isolator switch closed/opened I 1-0 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 18 SAM Synchronization auto/manual I 1-2 *) 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2-4 *) 2 CB Circuit breaker closed/opened 1-2 *) 4 CSO Check synchronizing override 1-2 *) 6 LI Line isolator switch closed/opened 1-0 *) 7 LR Local remote 1-2 *) 8 LRT Local/remote switch for tapchanger 1

10 SAM Synchronization auto/manual 1-2 *) 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 88: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

76

TB-13: Interbus Transformer

(Secondary Side Connected to Single Busbar)

INTERBUS TRANSFORMERSecondary Side Connected to Single Busbar

BUSBAR

TB-13

BUSBAR (IRCC or RCC)

PQ

IV

Operation Responsibility by IRCC or RCC

Operation Responsibility by RCC

Download to RCC

L/R

L/R

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1-2 *) 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1-2 *) 42 CBFA Circuit breaker failure (a) operate A 1-2 *) 43 CBFB Circuit breaker failure (b) operate A 1-2 *)

TSS

44 CBM Circuit breaker maintenance I 1-2 *)

Page 89: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

77

Data No Kode Fungsi Tipe Jmh

58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1-2 *) 134 PHR Trip phase R A 1-2 *) 135 PHS Trip phase S A 1-2 *) 136 PHT Trip phase T A 1-2 *) 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1-2 *) 170 TCS2 Trip coil supervisory 2 A 1-2 *) 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1

Page 90: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

78

Data No Kode Fungsi Tipe Jmh

186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 3 CB Circuit breaker closed/opened I 1-2 *) 5 CSO Check synchronizing override I 1-2 *) 7 ES Earth switch closed/opened I 2

12 LI Line isolator switch closed/opened I 1-0 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 18 SAM Synchronization auto/manual I 1-2 *) 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 1-3 *) 2 CB Circuit breaker closed/opened 1-2 *) 4 CSO Check synchronizing override 1-2 *) 6 LI Line isolator switch closed/opened 1-0 *) 7 LR Local remote 1-2 *) 8 LRT Local/remote switch for tapchanger 1

10 SAM Synchronization auto/manual 1-2 *) 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 91: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

79

TB-14: Interbus Transformer

(Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

INTERBUS TRANSFORMERSecondary Side Connected to 1½ Breaker

Dilengkapi Shunt Reaktor Pada Kumparan Tersier

BUSBAR - A

TB-14

BUSBAR - B

PQ

IV

Operation Responsibility by IRCC

Operation Responsibility by RCC

Download to RCC

BUSBAR (IRCC)

QL/R

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1

TM

9 P Daya aktif 1

Page 92: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

80

Data No Kode Fungsi Tipe Jmh

13 Q Daya reaktif 2 15 TEMP Temperature 1 16 V Tegangan 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1

106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1

TSS

189 WTLVT LV winding temperatur trip A 1 7 ES Earth switch closed/opened I 2 12 LI Line isolator switch closed/opened I 3

TSD

14 LRT Local/remote switch for tapchanger I 1

Page 93: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

81

Data No Kode Fungsi Tipe Jmh

20 TCC Tap changer auto/manual I 1 21 TFAM Transformer fan auto/manual I 1 6 LI Line isolator switch closed/opened 3 8 LRT Local/remote switch for tapchanger 1 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 94: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

82

TB-15: Interbus Transformer

(Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Double Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

TM

12 PRES Pressure 1-2 *)

Page 95: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

83

Data No Kode Fungsi Tipe Jmh

13 Q Daya reaktif 2 15 TEMP Temperature 1 16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1-2 *) 42 CBFA Circuit breaker failure (a) operate A 1-2 *) 43 CBFB Circuit breaker failure (b) operate A 1-2 *) 44 CBM Circuit breaker maintenance I 1-2 *) 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1-2 *) 134 PHR Trip phase R A 1-2 *) 135 PHS Trip phase S A 1-2 *) 136 PHT Trip phase T A 1-2 *) 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1-2 *) 170 TCS2 Trip coil supervisory 2 A 1-2 *) 171 TFDP Transformer fire detection & protection A 1

TSS

172 TJANT Transformer jansen trip A 1

Page 96: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

84

Data No Kode Fungsi Tipe Jmh

173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 2-4 *) 3 CB Circuit breaker closed/opened I 1-2 *) 5 CSO Check synchronizing override I 1-2 *) 7 ES Earth switch closed/opened I 2

12 LI Line isolator switch closed/opened I 2-1 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 18 SAM Synchronization auto/manual I 1-2 *) 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2-4 *) 2 CB Circuit breaker closed/opened 1-2 *) 4 CSO Check synchronizing override 1-2 *) 6 LI Line isolator switch closed/opened 2-1 *) 7 LR Local remote 1-2 *) 8 LRT Local/remote switch for tapchanger 1

10 SAM Synchronization auto/manual 1-2 *) 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 97: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

85

TB-16: Interbus Transformer

(Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

INTERBUS TRANSFORMERSecondary Side Connected to Single Busbar

Dilengkapi Shunt Reaktor Pada Kumparan Tersier

BUSBAR

TB-16

BUSBAR (IRCC or RCC)

PQ

IV

Operation Responsibility by IRCC or RCC

Operation Responsibility by RCC

Download to RCC

Q

L/R

L/R

Teleinformasi Data Untuk Interbus Transformer (Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor Pada Kumparan Tersier)

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1-2 *) 13 Q Daya reaktif 2 15 TEMP Temperature 1

TM

16 V Tegangan 1

Page 98: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

86

Data No Kode Fungsi Tipe Jmh

41 CBDF Circuit breaker drive failure A 1-2 *) 42 CBFA Circuit breaker failure (a) operate A 1-2 *) 43 CBFB Circuit breaker failure (b) operate A 1-2 *) 44 CBM Circuit breaker maintenance I 1-2 *) 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1-2 *) 134 PHR Trip phase R A 1-2 *) 135 PHS Trip phase S A 1-2 *) 136 PHT Trip phase T A 1-2 *) 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer AVR failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1-2 *) 170 TCS2 Trip coil supervisory 2 A 1-2 *) 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1

TSS

177 TPIF Tap position indication failure A 1

Page 99: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

87

Data No Kode Fungsi Tipe Jmh

178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 3 CB Circuit breaker closed/opened I 1-2 *) 5 CSO Check synchronizing override I 1-2 *) 7 ES Earth switch closed/opened I 2

12 LI Line isolator switch closed/opened I 2-1 *) 13 LR Local remote I 1-2 *) 14 LRT Local/remote switch for tapchanger I 1 18 SAM Synchronization auto/manual I 1-2 *) 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 1-3 *) 2 CB Circuit breaker closed/opened 1-2 *) 4 CSO Check synchronizing override 1-2 *) 6 LI Line isolator switch closed/opened 2-1 *) 7 LR Local remote 1-2 *) 8 LRT Local/remote switch for tapchanger 1

10 SAM Synchronization auto/manual 1-2 *) 11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1 KETERANGAN: *) = (Primary Side Connected to 1½ Breaker)–(Primary Side Connected to Double Busbar)

Page 100: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

88

TB-17: Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1

TM

13 Q Daya reaktif 1

Page 101: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

89

Data No Kode Fungsi Tipe Jmh

15 TEMP Temperature 1 16 V Tegangan 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer avr failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1

TSS

189 WTLVT LV winding temperatur trip A 1 TSD 7 ES Earth switch closed/opened I 1

Page 102: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

90

Data No Kode Fungsi Tipe Jmh

12 LI Line isolator switch closed/opened I 1 14 LRT Local/remote switch for tapchanger I 1 20 TCC Tap changer auto/manual I 1 21 TFAM Transformer fan auto/manual I 1 6 LI Line isolator switch closed/opened 1 8 LRT Local/remote switch for tapchanger 1

11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 103: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

91

TB-18: Bay Trafo Tenaga Pada Konfigurasi Double Busbar

BAY TRAFO TENAGAPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-18

BUSBAR - B

PQ

TEGANGAN TINGGI

TEGANGAN MENENGAH

DOUBLE BUSBAR

Batas wewenang

L/R

VI

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1

TSS

44 CBM Circuit breaker maintenance I 1

Page 104: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

92

Data No Kode Fungsi Tipe Jmh

60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer avr failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 182 UVR Under voltage relay operate A 1

Page 105: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

93

Data No Kode Fungsi Tipe Jmh

183 UVRF Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 16 RACK Circuit breaker rackin/rackout I 1 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 7 LR Local remote 1 8 LRT Local/remote switch for tapchanger 1

11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 106: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

94

TB-19: Bay Trafo Tenaga Pada Konfigurasi Single Busbar

BAY TRAFO TENAGAPADA KONFIGURASI SINGLE BUSBAR

TB-19

BUSBAR

PQTEGANGAN TINGGI

TEGANGAN MENENGAH

DOUBLE BUSBAR

Batas wewenang

L/R

VI

Teleinformasi Data Untuk Bay Trafo Tenaga Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1 1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA Counter arester 1 4 CTPI Counter tap position indication 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1 13 Q Daya reaktif 1 15 TEMP Temperature 1

TM

16 V Tegangan 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 60 DCF DC supply failure A 1

TSS

74 DFRF Disturbance fault recorder faulty A 1

Page 107: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

95

Data No Kode Fungsi Tipe Jmh

75 DIFF Differential failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 108 FPO Fire protection operated A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 124 OTA Oil temperature alarm A 1 125 OTT Oil temperatur trip A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 128 P1DIF Differential A 1 129 P1REF Restricted earth fault A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 147 REFF Restricted earth fault failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 161 TAF Tranformer avr failure A 1 162 TBUC2 Transformer bucholz trip A 1 163 TBUCA Transformer bucholz alarm A 1 164 TCA Tap changer alarm A 1 165 TCFF Transformer cooling fan failure A 1 166 TCH Tap changer high limit A 1 167 TCL Tap changer low limit A 1 168 TCPF Transformer cooling pump failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 171 TFDP Transformer fire detection & protection A 1 172 TJANT Transformer jansen trip A 1 173 TOLA Transformer oil level alarm A 1 174 TOOS Transformer out of step alarm A 1 177 TPIF Tap position indication failure A 1 178 TSPA Transformer sudden pressure alarm A 1 179 TSPT Transformer sudden pressure trip A 1 180 UFR Under frequency relay operate A 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1

Page 108: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

96

Data No Kode Fungsi Tipe Jmh

186 WTHVA HV winding temperatur alarm A 1 187 WTHVT HV winding temperatur trip A 1 188 WTLVA LV winding temperatur alarm A 1 189 WTLVT LV winding temperatur trip A 1 1 BI Bus isolator switch closed/opened I 1 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

13 LR Local remote I 1 14 LRT Local/remote switch for tapchanger I 1 16 RACK Circuit breaker rackin/rackout I 1 20 TCC Tap changer auto/manual I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 1 2 CB Circuit breaker closed/opened 1 7 LR Local remote 1 8 LRT Local/remote switch for tapchanger 1

11 TC Tap changer raise/lower 1 12 TCC Tap changer auto/manual 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 109: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

97

TB-20: Bay Reaktor Pada Konfigurasi 1 ½ Breaker

BAY REAKTORPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-20

BUSBAR - B

Q

Reaktor

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi 1 ½ Breaker Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1

TSS

160 SZPF Short zone protection failure A 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 TSD 21 TFAM Transformer fan auto/manual I 1 6 LI Line isolator switch closed/opened 1 RCD

13 TFAM Transformer fan auto/manual 1

Page 110: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

98

TB-21: Bay Reaktor Pada Konfigurasi Double Busbar

BAY REAKTORPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-21

BUSBAR - B

Q

Reaktor

L/R

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1

12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance A 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1

TSS

138 POT Protection on test A 1

Page 111: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

99

Data No Kode Fungsi Tipe Jmh

139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 112: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

100

TB-22: Bay Reaktor Pada Konfigurasi Single Busbar

BAY REAKTORPADA KONFIGURASI SINGLE BUSBAR

TB-22

BUSBAR

Q

Reaktor

L/R

Teleinformasi Data Untuk Bay Reaktor Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1

12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance A 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1

TSS

158 SZPA Short zone protection (a) operate A 1

Page 113: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

101

Data No Kode Fungsi Tipe Jmh

159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 1 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 1 2 CB Circuit breaker closed/opened 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 114: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

102

TB-23: Bay Capasitor Pada Konfigurasi Double Busbar

BAY KAPASITORPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-23

BUSBAR - B

Q

Capasitor

L/R

Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1

12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance A 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1

TSS

135 PHS Trip phase S A 1

Page 115: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

103

Data No Kode Fungsi Tipe Jmh

136 PHT Trip phase T A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 116: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

104

TB-24: Bay Capasitor Pada Konfigurasi Single Busbar

BAY KAPASITORPADA KONFIGURASI SINGLE BUSBAR

TB-24

BUSBAR

Q

L/R

Capasitor

Teleinformasi Data Untuk Bay Capasitor Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1

12 PRES Pressure 1 13 Q Daya reaktif 1

TM

15 TEMP Temperature 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance A 1 60 DCF DC supply failure A 1 74 DFRF Disturbance fault recorder faulty A 1 106 ERF Event recorder failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 128 P1DIF Differential A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test A 1 139 PRDT Pressure relay device trip A 1 145 RCBF Relay circuit breaker fail failure A 1 148 RF Reaktor failure A 1

TSS

158 SZPA Short zone protection (a) operate A 1

Page 117: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

105

Data No Kode Fungsi Tipe Jmh

159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 1 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

21 TFAM Transformer fan auto/manual I 1 1 BI Bus isolator switch closed/opened 1 2 CB Circuit breaker closed/opened 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

13 TFAM Transformer fan auto/manual 1

Page 118: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

106

TB-25: Bay Penghantar Pada Konfigurasi 1 ½ Breaker

BAY PENGHANTARPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-25

BUSBAR - B

PQVI

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi 1 ½ Breaker

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

13 Q Daya reaktif 1

TM

16 V Tegangan 1 49 CDAF Current differential relay (a) failure A 1 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) failure A 1 54 CDBR Current differential (b) phase R A 1 55 CDBS Current differential (b) phase S A 1

TSS

56 CDBT Current differential (b) phase T A 1

Page 119: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

107

Data No Kode Fungsi Tipe Jmh

57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 62 DEARX *) Directional earth fault (a) relay receive A 1 63 DEATX *) Directional earth fault (a) relay transmit A 1 64 DEBRX *) Directional earth fault (b) relay receive A 1 65 DEBTX *) Directional earth fault (b) relay transmit A 1 66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1 122 OCPA**) Oil cable pressure alarm A 1

Page 120: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

108

Data No Kode Fungsi Tipe Jmh

123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 7 ES Earth switch closed/opened I 1 TSD

12 LI Line isolator switch closed/opened I 1 RCD 6 LI Line isolator switch closed/opened 1

KETERANGAN:

*) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder

Page 121: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

109

TB-26: Bay Penghantar Pada Konfigurasi Double Busbar

BAY PENGHANTARPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-26

BUSBAR - B

L/R

QVI

P

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1 13 Q Daya reaktif 1

TM

16 V Tegangan 1 34 AR *) Circuit breaker auto reclose I 1 35 ARO *) Auto reclose off I 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 49 CDAF Current differential relay (a) failure A 1 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) failure A 1 54 CDBR Current differential (b) phase R A 1

TSS

55 CDBS Current differential (b) phase S A 1

Page 122: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

110

Data No Kode Fungsi Tipe Jmh

56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 62 DEARX *) Directional earth fault (a) relay receive A 1 63 DEATX *) Directional earth fault (a) relay transmit A 1 64 DEBRX *) Directional earth fault (b) relay receive A 1 65 DEBTX *) Directional earth fault (b) relay transmit A 1 66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1

Page 123: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

111

Data No Kode Fungsi Tipe Jmh

118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

10 SAM Synchronization auto/manual 1 KETERANGAN:

*) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder

Page 124: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

112

TB-27: Bay Penghantar Pada Konfigurasi Single Busbar

Teleinformasi Data Untuk Bay Penghantar Pada Konfigurasi Single Busbar

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1 13 Q Daya reaktif 1

TM

16 V Tegangan 1 34 AR *) Circuit breaker auto reclose I 1 35 ARO *) Auto reclose off I 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 49 CDAF Current differential relay (a) failure A 1 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) failure A 1 54 CDBR Current differential (b) phase R A 1 55 CDBS Current differential (b) phase S A 1 56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1

TSS

60 DCF DC supply failure A 1

Page 125: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

113

Data No Kode Fungsi Tipe Jmh

62 DEARX *) Directional earth fault (a) relay receive A 1 63 DEATX *) Directional earth fault (a) relay transmit A 1 64 DEBRX *) Directional earth fault (b) relay receive A 1 65 DEBTX *) Directional earth fault (b) relay transmit A 1 66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 122 OCPA**) Oil cable pressure alarm A 1

Page 126: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

114

Data No Kode Fungsi Tipe Jmh

123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 1 BI Bus isolator switch closed/opened I 1 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 1

12 LI Line isolator switch closed/opened I 1 13 LR Local remote I 1

TSD

18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 1 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 6 LI Line isolator switch closed/opened 1 7 LR Local remote 1

RCD

10 SAM Synchronization auto/manual 1 KETERANGAN:

*) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder

Page 127: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

115

TB-28: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi Double Busbar

BAY PENGHANTARPARALEL DENGAN REAKTOR

PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-28

BUSBAR - B

PQV

Q

I

L/R

Teleinformasi Data Untuk Bay Penghantar Serial Dengan Reaktor Pada Konfigurasi Double Busbar Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 2 CCB Counter of circuit breaker 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

12 PRES Pressure 1 13 Q Daya reaktif 2

TM

16 V Tegangan 1 34 AR *) Circuit breaker auto reclose I 1 35 ARO *) Auto reclose off I 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1

TSS

49 CDAF Current differential relay (a) failure A 1

Page 128: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

116

Data No Kode Fungsi Tipe Jmh 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) failure A 1 54 CDBR Current differential (b) phase R A 1 55 CDBS Current differential (b) phase S A 1 56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 62 DEARX *) Directional earth fault (a) relay receive A 1 63 DEATX *) Directional earth fault (a) relay transmit A 1 64 DEBRX *) Directional earth fault (b) relay receive A 1 65 DEBTX *) Directional earth fault (b) relay transmit A 1 66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1

Page 129: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

117

Data No Kode Fungsi Tipe Jmh 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1 7 ES Earth switch closed/opened I 2

12 LI Line isolator switch closed/opened I 2 13 LR Local remote I 1

TSD

18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 6 LI Line isolator switch closed/opened 2 7 LR Local remote 1

RCD

10 SAM Synchronization auto/manual 1 KETERANGAN:

*) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder

Page 130: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

118

TB-29: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½ Breaker

BAY PENGHANTAR PARALEL DENGAN 1 REAKTOR

PADA KONFIGURASI 1½ BREAKERBUSBAR - A

TB-29

BUSBAR - B

PQVQI

L/R

Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

13 Q Daya reaktif 2

TM

16 V Tegangan 1 49 CDAF Current differential relay (a) failure A 1 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) failure A 1 54 CDBR Current differential (b) phase R A 1

TSS

55 CDBS Current differential (b) phase S A 1

Page 131: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

119

Data No Kode Fungsi Tipe Jmh

56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 62 DEARX *) Directional earth fault (a) relay receive A 1 63 DEATX *) Directional earth fault (a) relay transmit A 1 64 DEBRX *) Directional earth fault (b) relay receive A 1 65 DEBTX *) Directional earth fault (b) relay transmit A 1 66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 117 LOWCT**) Low oil pressure cable trip A 1

Page 132: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

120

Data No Kode Fungsi Tipe Jmh

122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 3 CB Circuit breaker closed/opened I 1 7 ES Earth switch closed/opened I 2 TSD

12 LI Line isolator switch closed/opened I 2 2 CB Circuit breaker closed/opened 1 RCD 6 LI Line isolator switch closed/opened 2

KETERANGAN:

*) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder

Page 133: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

121

TB-30: Bay Penghantar Paralel Dengan 2 Reaktor Seri Pada Konfigurasi 1½ Breaker

BAY PENGHANTAR PARALEL DENGAN 2 REAKTOR SERIPADA KONFIGURASI 1 ½ BREAKER

BUSBAR - A

TB-30

BUSBAR - B

PQV

Q

Q I

Teleinformasi Data Untuk Bay Penghantar Paralel Dengan 2 Reaktor seri Pada Konfigurasi 1½ Breaker

Data No Kode Fungsi Tipe Jmh

1 AMF Amperes fault ( per phase ) 1 3 CNTA *) Counter arester 1 6 I Arus 1 7 KVARH Kilovar hour 1 8 KWH Kilowatt hour 1 9 P Daya aktif 1

13 Q Daya reaktif 3

TM

16 V Tegangan 1 49 CDAF Current differential relay (a) failure A 1 50 CDAR Current differential (a) phase R A 1 51 CDAS Current differential (a) phase S A 1 52 CDAT Current differential (a) phase T A 1 53 CDBF Current differential relay (b) failure A 1

TSS

54 CDBR Current differential (b) phase R A 1

Page 134: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

122

Data No Kode Fungsi Tipe Jmh

55 CDBS Current differential (b) phase S A 1 56 CDBT Current differential (b) phase T A 1 57 CF *) Carrier faulty A 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 62 DEARX *) Directional earth fault (a) relay receive A 1 63 DEATX *) Directional earth fault (a) relay transmit A 1 64 DEBRX *) Directional earth fault (b) relay receive A 1 65 DEBTX *) Directional earth fault (b) relay transmit A 1 66 DEFAF *) Directional earth fault (a) failure A 1 67 DEFAR Directional earth fault (a) phase R A 1 68 DEFAS Directional earth fault (a) phase S A 1 69 DEFAT Directional earth fault (a) phase T A 1 70 DEFBF *) Directional earth fault (b) failure A 1 71 DEFBR Directional earth fault (b) phase R A 1 72 DEFBS Directional earth fault (b) phase S A 1 73 DEFBT Directional earth fault (b) phase T A 1 74 DFRF Disturbance fault recorder faulty A 1 77 DSDF Disconnecting switch driving fault A 1 78 DTARX *) Direct transfer trip (a) receive I 1 79 DTATX *) Direct transfer trip (a) transmit I 1 80 DTBRX *) Direct transfer trip (b) receive I 1 81 DTBTX *) Direct transfer trip (b) transmit I 1 82 DZ1AR *) Distance (a) phase R zone 1 A 1 83 DZ1AS *) Distance (a) phase S zone 1 A 1 84 DZ1AT *) Distance (a) phase T zone 1 A 1 85 DZ1BR *) Distance (b) phase R zone 1 A 1 86 DZ1BS *) Distance (b) phase S zone 1 A 1 87 DZ1BT *) Distance (b) phase T zone 1 A 1 88 DZ2AR *) Distance (a) phase R zone 2 A 1 89 DZ2AS *) Distance (a) phase S zone 2 A 1 90 DZ2AT *) Distance (a) phase T zone 2 A 1 91 DZ2BR *) Distance (b) phase R zone 2 A 1 92 DZ2BS *) Distance (b) phase S zone 2 A 1 93 DZ2BT *) Distance (b) phase T zone 2 A 1 94 DZ3AR *) Distance (a) phase R zone 3 A 1 95 DZ3AS *) Distance (a) phase S zone 3 A 1 96 DZ3AT *) Distance (a) phase T zone 3 A 1 97 DZ3BR *) Distance (b) phase R zone 3 A 1 98 DZ3BS *) Distance (b) phase S zone 3 A 1 99 DZ3BT *) Distance (b) phase T zone 3 A 1 100 DZAF *) Distance relay (a) failure A 1 101 DZARX *) Distance (a) relay receive I 1 102 DZATX *) Distance (a) relay transmit I 1 103 DZBF *) Distance relay (b) failure A 1 104 DZBRX *) Distance (b) relay receive I 1 105 DZBTX *) Distance (b) relay transmit I 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1

Page 135: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

123

Data No Kode Fungsi Tipe Jmh

117 LOWCT**) Low oil pressure cable trip A 1 122 OCPA**) Oil cable pressure alarm A 1 123 OCRF Over current relay failure A 1 126 OVR *) Over voltage relay operate A 1 127 OVRF *) Over voltage relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 138 POT Protection on test I 1 141 PWF Pilot wire failure A 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1 159 SZPB Short zone protection (b) operate A 1 160 SZPF Short zone protection failure A 1 175 TPAF *) Teleprotection (a) failure A 1 176 TPBF *) Teleprotection (b) failure A 1 180 UFR Under frequency relay operate A 1 182 UVR *) Under voltage relay operate A 1 183 UVRF *) Under voltage relay failure A 1 185 VTF Voltage transformer failure A 1 7 ES Earth switch closed/opened I 2 TSD

12 LI Line isolator switch closed/opened I 3 RCD 6 LI Line isolator switch closed/opened 2

KETERANGAN:

*) = Khusus untuk OHL Feeder **) = Khusus untuk Cable Feeder

Page 136: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

124

TB-31: Bay Kopel Pada Konfigurasi Double Busbar

BAY KOPELPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-31

BUSBAR - B

L/R

I

Teleinformasi Data Untuk Bay Kopel Pada Konfigurasi Double Busbar

Data No Kode Fungsi Tipe Jmh

2 CCB Counter of circuit breaker 1 6 I Arus 1 TM 12 PRES Pressure 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 60 DCF DC supply failure A 1 77 DSDF Disconnecting switch driving fault A 1 106 ERF Event recorder failure A 1 111 GFRF Ground fault relay failure A 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 130 P2GFR Ground fault relay A 1 131 P2OCR Over current relay A 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 145 RCBF Relay circuit breaker fail failure A 1 157 SYNF Synchronizing failure A 1 158 SZPA Short zone protection (a) operate A 1

TSS

159 SZPB Short zone protection (b) operate A 1

Page 137: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

125

Data No Kode Fungsi Tipe Jmh

160 SZPF Short zone protection failure A 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1

13 LR Local remote I 1 TSD

18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 2 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 7 LR Local remote 1

RCD

10 SAM Synchronization auto/manual 1

Page 138: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

126

TB-32: Bus Section

BUS SECTIONTB-32

Tipe-1

L/RTipe-2

L/R

Teleinformasi Data Untuk Bus Section

Jmh Data No Kode Fungsi Tipe Tipe-1 Tipe-2 2 CCB Counter of circuit breaker 1 TM 12 PRES Pressure 1 41 CBDF Circuit breaker drive failure A 1 42 CBFA Circuit breaker failure (a) operate A 1 43 CBFB Circuit breaker failure (b) operate A 1 44 CBM Circuit breaker maintenance I 1 58 CSP Check synchronizing in progress I 1 106 ERF Event recorder failure A 1 1 111 GFRF Ground fault relay failure A 1 1 118 LPA Low pressure alarm A 1 119 LPB Low pressure block A 1 120 LPT Low pressure trip A 1 123 OCRF Over current relay failure A 1 1 130 P2GFR Ground fault relay A 1 1 131 P2OCR Over current relay A 1 1 133 PD Pole discrepancy A 1 134 PHR Trip phase R A 1 135 PHS Trip phase S A 1 136 PHT Trip phase T A 1 138 POT Protection on test I 1 1 145 RCBF Relay circuit breaker fail failure A 1 1 157 SYNF Synchronizing failure A 1 1 158 SZPA Short zone protection (a) operate A 1 1

TSS

159 SZPB Short zone protection (b) operate A 1 1

Page 139: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

127

Jmh 160 SZPF Short zone protection failure A 1 1 169 TCS1 Trip coil supervisory 1 A 1 170 TCS2 Trip coil supervisory 2 A 1 1 BI Bus isolator switch closed/opened I 2 1 3 CB Circuit breaker closed/opened I 1 5 CSO Check synchronizing override I 1

13 LR Local remote I 1 TSD

18 SAM Synchronization auto/manual I 1 1 BI Bus isolator switch closed/opened 2 1 2 CB Circuit breaker closed/opened 1 4 CSO Check synchronizing override 1 7 LR Local remote 1

RCD

10 SAM Synchronization auto/manual 1

Page 140: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

128

TB-33: Bay Diameter Pada Konfigurasi 1½ Breaker

BAY DIAMETERPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-33

BUSBAR - B

L/R

L/R

L/R

Teleinformasi Data Untuk Diameter

Data No Kode Fungsi Tipe Jmh

2 CCB Counter of circuit breaker 3 TM 12 PRES Pressure 3 41 CBDF Circuit breaker drive failure A 3 42 CBFA Circuit breaker failure (a) operate A 3 43 CBFB Circuit breaker failure (b) operate A 3 44 CBM Circuit breaker maintenance I 3 46 CCPA Circulating current protection (a) operate A 1 47 CCPB Circulating current protection (b) operate A 1 48 CCPF Circulating current protection failure A 3 58 CSP Check synchronizing in progress I 3 106 ERF Event recorder failure A 3 118 LPA Low pressure alarm A 3 119 LPB Low pressure block A 3 120 LPT Low pressure trip A 3 133 PD Pole discrepancy A 3 134 PHR Trip phase R A 3 135 PHS Trip phase S A 3 136 PHT Trip phase T A 3 138 POT Protection on test I 1 145 RCBF Relay circuit breaker fail failure A 3 157 SYNF Synchronizing failure A 3

TSS

158 SZPA Short zone protection (a) operate A 3

Page 141: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

129

Data No Kode Fungsi Tipe Jmh

159 SZPB Short zone protection (b) operate A 3 160 SZPF Short zone protection failure A 3 169 TCS1 Trip coil supervisory 1 A 3 170 TCS2 Trip coil supervisory 2 A 3 1 BI Bus isolator switch closed/opened I 6 3 CB Circuit breaker closed/opened I 3 5 CSO Check synchronizing override I 3

13 LR Local remote I 3 TSD

18 SAM Synchronization auto/manual I 3 1 BI Bus isolator switch closed/opened 6 2 CB Circuit breaker closed/opened 3 4 CSO Check synchronizing override 3 7 LR Local remote 3

RCD

10 SAM Synchronization auto/manual 3

Page 142: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

130

TB-34: Bus Bar

Teleinformasi Data Untuk Bus Bar

Data No Kode Fungsi Tipe Jumlah

TM 7 V Tegangan 1 37 BPA Busbar protection (a) A 1 38 BPAF Busbar protection (a) failure A 1 39 BPB Busbar protection (b) A 1 40 BPBF Busbar protection (b) failure A 1 77 DSDF Disconnecting switch driving fault A 1

106 ERF Event recorder failure A 1 126 OVR Over voltage relay operate A 1 127 OVRF Over voltage relay failure A 1 138 POT Protection on test I 1 182 UVR Under voltage relay operate A 1 183 UVRF Under voltage relay failure A 1

TSS

184 VS Voltage status I 1 TSD 7 ES Earth switch closed/opened I 1

Page 143: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

131

Lampiran C – Daftar Teleinformasi (Distribusi)

Page 144: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

132

C-1: Telesignal

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

1 ARU Auto Recloser Use/Unuse Feeder PBO D I

2 BI Bus Isolator Switch Closed/Opened

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf

D I

3 CAM Capacitor Auto/Manual Capacitor D I

4 CB Circuit Breaker Closed/Opened

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Generator PBO

D I

5 CD Control Disable Switch RTU D I

6 DCBC Dummy Breaker Closed/Opened RTU D I

7 ES Earth Switch Closed/Opened

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Keypoint Gardu Tengah Gardu Hubung

8 GUC Generator Unit Run/Stop Generator D I

9 LBS Load Break Switch Key Point Gardu Tengah Gardu Hubung

D I

10 LR Local Remote

Bus Coupler Bus Section Feeder Capacitor Reactor Gen Transf Generator Keypoint PBO Gardu Tengah Gardu Hubung

D I

11 RACK Circuit Breaker Rackin/Rackout

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf

D I

Page 145: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

133

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

Generator

12 RR Recloser Reset Feeder PBO D I

13 110RF 110VDC Rectifier Failure Gardu Induk S A

14 110SF 110VDC Supply Failure Gardu Induk S A

15 220F 220 VAC Failure

Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung

S A

16 380F 380 VAC Failure Gardu Induk S A

17 48RF 48VDC Rectifier Failure

Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung

S A

18 48SF 48VDC Supply Failure

Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung k

S A

19 AIRCF Air Conditioning Failure RTU S A

20 AR Circuit Breaker Auto Reclose Feeder PBO S A

21 ARO Auto Reclose Off Feeder PBO S A

22 CBDF Circuit Breaker Drive Failure

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO

S A

23 CBTR CB Trip

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor PBO

S A

24 CTE Cabinet Temperatur RTU IED S A

25 DCG DC Ground

Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung

S A

26 DOOR Door Activated

Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung

S A

Page 146: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

134

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

27 FOTF FO Terminal Faulty

Gardu Induk IED PBO Gardu Tengah Gardu Hubung

S A

28 FPO Fire Protection Operated Gardu Induk S A

29 FRA Fire Alarm Gardu Induk S A

30 FRSF Fire Alarm System Failure Gardu Induk S A

31 GFRF Ground Fault Relay Failure PBO S A

32 GTT Generator Transformer Trip Gen Transf S A

33 HFD Homopolar Fault Detector Keypoint Gardu Hubung Gardu Tengah

S A

34 iR Internal Remote Station RTU IED S A

35 LPA Low Pressure Alarm

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO

S A

36 OCRF Over Current Relay Failure PBO S A

37 P1DEF Directional Earth Fault Feeder S A

38 P2GFR Ground Fault Relay

Bus Coupler Bus Section Feeder Capacitor Reactor

S A

39 P2OCR Over Current Relay

Bus Coupler Bus Section Feeder Capacitor Reactor

S A

40 PBXF PABX Faulty Gardu Induk S A

41 PTF Protection Faulty

Bus Coupler Bus Section Feeder Capacitor Reactor

S A

42 RADF Radio Link Faulty

Gardu Induk Keypoint PBO Gardu Tengah Gardu Hubung

S A

43 RBUCA Reaktor Bucholz Alarm Gen Transf S A

44 RBUCZ Reaktor Bucholz Trip Gen Transf S A

Page 147: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

135

No Kode Fungsi Implementasi Single (S) or Double

(D) Indication

Suggested Alarm (A) or

Event/Indication (I)

45 RFDP Reaktor Fire Detection & Protection Gen Transf S A

46 ROLA Reaktor Oil Level Alarm Gen Transf S A

47 RSPA Reaktor Sudden Pressure Alarm Gen Transf S A

48 RSPT Reaktor Bucholz Sudden Pressure Trip Gen Transf S A

49 RSTA Reset Alarm Gardu Induk S A

50 SIA Station Intruder Alarm Gardu Induk S A

51 TCH Tap Changer High Limit Incoming S A

52 TCL Tap Changer Low Limit Incoming S A

53 TCS1 Trip Coil Supervisory 1

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO

S A

54 TPIF Tap Position Indication Failure Incoming S A

55 UFR Under Frequency Relay Operate Feeder S A

56 UT Unit Trip Generator S A

Page 148: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

136

C-2: Telemeasurement

No Kode Fungsi Implementasi

1 AMF Amperes Fault (Per Phase)

Feeder Incoming Gen Transf PBO

2 CCB Counter of Circuit Breaker

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf PBO

3 F Frekuensi Busbar

4 I Arus

Feeder Incoming Capacitor Reactor Generator Keypoint PBO

5 KVARH Kilovar Hour

Feeder Incoming Capacitor Reactor Gen Transf

6 KWH Kilowatt Hour

Feeder Incoming Capacitor Reactor Gen Transf

7 P Daya Aktif

Feeder Incoming Capacitor Reactor Generator Keypoint

8 PF Power Factor Incoming

9 Q Daya Reaktif

Incoming Capacitor Reactor Generator

10 V Tegangan

Busbar Generator Keypoint PBO

Page 149: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

137

C-3: Tap Changer Position

No Kode Fungsi Implementasi

1 TPI Tap Position Indication Incoming

Page 150: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

138

C-4: Remote Control Digital

No Kode Fungsi Implementasi

1 ARU Auto Recloser use/unuse Feeder PBO

2 CB Circuit Breaker Closed/Opened

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf

3 CD Control Disable Switch RTU

4 DCBC Dummy Circuit Breaker Closed/Opened RTU

5 LBS Load Break Switch Close/Open Keypoint Gardu Tengah Gardu Hubung

6 LR Local Remote

Bus Coupler Bus Section Feeder Incoming Capacitor Reactor Gen Transf Keypoint PBO Gardu Tengah Gardu Hubung

7 RMT Reset Master Trip Gardu Induk

8 RR Recloser Reset Feeder PBO

Page 151: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

139

Lampiran D - Bidang Distribusi (Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi)

Page 152: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

140

DA-01: Konfigurasi Umum Pada Double Busbar

KONFIGURASI UMUM PADA DOUBLE BUSBAR

BUSBAR - A

DA- 01

BUSBAR - B

Q P

GENERATOR

FEEDER

CAPASITOR

INCOMING 20KV

L/R

Q

PQ

L/R

I

QP

V

L/R L/R L/R

I

PF

V (R)V (S)V (T)

V (R)V (S)V (T)

P

KOPEL

I (R)I (S)I (T)

Page 153: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

141

Teleinformasi Data Untuk Konfigurasi Umum Pada Double Busbar Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 6 1 AMF Ampere Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1

TM

7 P Daya Aktif 1 20 AR Circuit Breaker Auto Reclose A 1 21 ARO Auto Reclose Off A 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 53 TCS1 Trip Coil Supervisory 1 A 1

TSS

55 UFR Under Frequency Relay Operate A 1 1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1

10 LR Local Remote I 1

TSD

12 RR Recloser Reset I 1 1 ARU Auto Recloser Use/Unuse 1 2 CB Circuit Breaker Closed/Opened 1 6 LR Local Remote 1

Feeder

RCD

8 RR Recloser Reset 1 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1 8 PF Power Factor 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 51 TCH Tap Changer High Limit A 1 52 TCL Tap Changer Low Limit A 1 53 TCS1 Trip Coil Supervisory A 1

TSS

54 TPIF Tap Position Indication Failure A 1

Incoming 20 kV

TSD 2 BI Bus Isolator Switch Closed/Opened I 2

Page 154: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

142

Group Bay Data No Kode Fungsi Tipe Jmh

4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1 2 CB Circuit Breaker Closed/Opened I 1

RCD 6 LR Local Remote I 1 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1

TSS

53 TCS1 Trip Coil Supervisory 1 A 1 2 BI Bus Isolator Switch Closed/Opened I 2 3 CAM Capacitor Auto/Manual I 1 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1

TSD

10 LR Local Remote I 1 2 CB Circuit Breaker Closed/Opened 1

Capasitor

RCD 6 LR Local Remote 1 4 I Arus 3 7 P Daya aktif 1 9 Q Daya reaktif 1

TM

10 V Tegangan 1 TSS 56 UT Unit Trip A 1

4 CB Circuit breaker closed/opened I 1

Generator

TSD 8 GUC Generator unit run/stop I 1

TM 2 CCB Counter of Circuit Breaker 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1

TSS

53 TCS1 Trip Coil Supervisory 1 A 1 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1

TSD

10 LR Local Remote I 1 2 CB Circuit Breaker Closed/Opened 1

Kopel

RCD 6 LR Local Remote 1

Page 155: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

143

DA-02: Konfigurasi Umum Pada Single Busbar

KONFIGURASI UMUM PADA SINGLE BUSBAR

BUSBAR - A

DA- 02

Q P

GENERATOR

FEEDER

CAPASITOR

INCOMING 20 KV

L/R

Q

PQ

L/R

I

QP

V

L/R L/R

I

PF

V (R)V (S)V (T)

P

I (R)I (S)I (T)

Page 156: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

144

Teleinformasi Data Untuk Konfigurasi Umum Pada Single Busbar Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 3 1 AMF Ampere Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1

TM

7 P Daya Aktif 1 20 AR Circuit Breaker Auto Reclose A 1 21 ARO Auto Reclose Off A 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 53 TCS1 Trip Coil Supervisory 1 A 1

TSS

55 UFR Under Frequency Relay Operate A 1 1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 1 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1 10 LR Local Remote I 1

TSD

12 RR Recloser Reset I 1 1 ARU Auto Recloser Use/Unuse 1 2 CB Circuit Breaker Closed/Opened 1 6 LR Local Remote 1

Feeder

RCD

8 RR Recloser Reset 1 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1 8 PF Power Factor 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 51 TCH Tap Changer High Limit A 1 52 TCL Tap Changer Low Limit A 1 53 TCS1 Trip Coil Supervisory A 1

TSS

54 TPIF Tap Position Indication Failure A 1

Incoming 20 kV

TSD 2 BI Bus Isolator Switch Closed/Opened I 1

Page 157: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

145

Group Bay Data No Kode Fungsi Tipe Jmh

4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1 2 CB Circuit Breaker Closed/Opened I 1

RCD 6 LR Local Remote I 1 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1

TSS

53 TCS1 Trip Coil Supervisory 1 A 1 2 BI Bus Isolator Switch Closed/Opened I 1 3 CAM Capacitor Auto/Manual I 1 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1

TSD

10 LR Local Remote I 1 2 CB Circuit Breaker Closed/Opened 1

Capasitor

RCD 6 LR Local Remote 1 4 I Arus 3 7 P Daya aktif 1 9 Q Daya reaktif 1

TM

10 V Tegangan 1 TSS 56 UT Unit Trip A 1

4 CB Circuit breaker closed/opened I 1

Generator

TSD 8 GUC Generator unit run/stop I 1

Page 158: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

146

DB-01: Trafo 150/20 kV dan 70/20 kV Tipe 1

TRAFO 150/20 KV DAN 70/20 KV DB- 01

TYPE 1

RCC

DCCL/RP

Q

I

PF

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 1

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 6 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1 8 PF Power Factor 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 51 TCH Tap Changer High Limit A 1 52 TCL Tap Changer Low Limit A 1 53 TCS1 Trip Coil Supervisory A 1

TSS

54 TPIF Tap Position Indication Failure A 1

Incoming 20 kV

TSD 2 BI Bus Isolator Switch Closed/Opened I 2

Page 159: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

147

Group Bay Data No Kode Fungsi Tipe Jmh

4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1 2 CB Circuit Breaker Closed/Opened I 1

RCD 6 LR Local Remote I 1

Page 160: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

148

DB-02: Trafo 150/20 kV dan 70/20 kV Tipe 2

TRAFO 150/20 KV DAN 70/20 KV DB -02

TYPE 2

RCC

DCC

PQ

I

PF

L/R

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 2

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 6 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1 8 PF Power Factor 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 51 TCH Tap Changer High Limit A 1 52 TCL Tap Changer Low Limit A 1 53 TCS1 Trip Coil Supervisory A 1

TSS

54 TPIF Tap Position Indication Failure A 1

Incoming 20 kV

TSD 4 CB Circuit Breaker Closed/Opened I 1

Page 161: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

149

Group Bay Data No Kode Fungsi Tipe Jmh

7 ES Earth Switch Closed/Opened I 1 11 RACK Circuit Breaker Rackin/Rackout I 1 2 CB Circuit Breaker Closed/Opened I 1

RCD 6 LR Local Remote I 1

Page 162: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

150

DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3

TRAFO 150/20 KV DAN 70/20 KV DB -03

TYPE 3

RCC

DCC

PQ

I

PF

L/R

Teleinformasi Data Untuk Trafo 150/20 kV dan 70/20 kV Tipe 3

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 3 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1 8 PF Power Factor 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 51 TCH Tap Changer High Limit A 1 52 TCL Tap Changer Low Limit A 1 53 TCS1 Trip Coil Supervisory A 1

TSS

54 TPIF Tap Position Indication Failure A 1 2 BI Bus Isolator Switch Closed/Opened I 1

Incoming 20 kV

TSD 4 CB Circuit Breaker Closed/Opened I 1

Page 163: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

151

Group Bay Data No Kode Fungsi Tipe Jmh

7 ES Earth Switch Closed/Opened I 1 2 CB Circuit Breaker Closed/Opened I 1

RCD 6 LR Local Remote I 1

Page 164: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

152

DB-04: Generator Pada Konfigurasi Double Busbar

GENERATOR PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

DB-04

BUSBAR - B

P

V

QI

PQ

L/R

Teleinformasi Data Untuk Generator Pada Konfigurasi Double Busbar

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 6 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1 8 PF Power Factor 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 51 TCH Tap Changer High Limit A 1 52 TCL Tap Changer Low Limit A 1 53 TCS1 Trip Coil Supervisory A 1

Incoming 20 kV

TSS

54 TPIF Tap Position Indication Failure A 1

Page 165: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

153

Group Bay Data No Kode Fungsi Tipe Jmh

2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 TSD 7 ES Earth Switch Closed/Opened I 1 2 CB Circuit Breaker Closed/Opened I 1

RCD 6 LR Local Remote I 1 4 I Arus 3 7 P Daya aktif 1 9 Q Daya reaktif 1

TM

10 V Tegangan 1 TSS 56 UT Unit Trip A 1

4 CB Circuit breaker closed/opened I 1

Generator

TSD 8 GUC Generator unit run/stop I 1

Page 166: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

154

DB-05: Generator Pada Konfigurasi Single Busbar

GENERATOR PADA KONFIGURASI SINGLE BUSBAR

BUSBAR

DB-05

P

V

QI

PQ

L/R

Teleinformasi Data Untuk Generator Pada Konfigurasi Single Busbar

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 3 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1 8 PF Power Factor 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 51 TCH Tap Changer High Limit A 1 52 TCL Tap Changer Low Limit A 1 53 TCS1 Trip Coil Supervisory A 1

TSS

54 TPIF Tap Position Indication Failure A 1 2 BI Bus Isolator Switch Closed/Opened I 1 4 CB Circuit Breaker Closed/Opened I 1 TSD 7 ES Earth Switch Closed/Opened I 1

Incoming 20 kV

2 CB Circuit Breaker Closed/Opened I 1

Page 167: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

155

Group Bay Data No Kode Fungsi Tipe Jmh

6 LR Local Remote I 1 RCD 6 LR Local Remote 1 4 I Arus 3 7 P Daya aktif 1 9 Q Daya reaktif 1

TM

10 V Tegangan 1 TSS 56 UT Unit Trip A 1

4 CB Circuit breaker closed/opened I 1

Generator

TSD 8 GUC Generator unit run/stop I 1

Page 168: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

156

DB-06: Feeder 20 kV Tipe 1

FEEDER 20 KVDB - 06

TYPE 1

L/R

P

I ( R )I ( S )I ( T )

Teleinformasi Data Untuk Feeder 20 kV Tipe 1

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 6 1 AMF Ampere Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1

TM

7 P Daya Aktif 1 20 AR Circuit Breaker Auto Reclose A 1 21 ARO Auto Reclose Off A 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 53 TCS1 Trip Coil Supervisory 1 A 1

TSS

55 UFR Under Frequency Relay Operate A 1 1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 2

Feeder

TSD

4 CB Circuit Breaker Closed/Opened I 1

Page 169: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

157

Group Bay Data No Kode Fungsi Tipe Jmh

7 ES Earth Switch Closed/Opened I 1 10 LR Local Remote I 1 12 RR Recloser Reset I 1 1 ARU Auto Recloser Use/Unuse 1 2 CB Circuit Breaker Closed/Opened 1 6 LR Local Remote 1

RCD

8 RR Recloser Reset 1

Page 170: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

158

DB-07: Feeder 20 kV Tipe 2

FEEDER 20 KVDB - 07

TYPE 2

L/R

P

I ( R)I ( S )I ( T )

Teleinformasi Data Untuk Feeder 20 kV Tipe 2

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 3 1 AMF Ampere Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1

TM

7 P Daya Aktif 1 20 AR Circuit Breaker Auto Reclose A 1 21 ARO Auto Reclose Off A 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 53 TCS1 Trip Coil Supervisory 1 A 1

TSS

55 UFR Under Frequency Relay Operate A 1 1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 2

Feeder

TSD

4 CB Circuit Breaker Closed/Opened I 1

Page 171: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

159

Group Bay Data No Kode Fungsi Tipe Jmh

7 ES Earth Switch Closed/Opened I 1 10 LR Local Remote I 1 11 RACK Circuit Breaker Rackin/Rackout I 1 12 RR Recloser Reset I 1 1 ARU Auto Recloser Use/Unuse 1 2 CB Circuit Breaker Closed/Opened 1 6 LR Local Remote 1

RCD

8 RR Recloser Reset 1

Page 172: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

160

DB-08: Feeder 20 kV Tipe 3

FEEDER 20 KVDB - 08

TYPE 3

L/R

P

I ( R )I ( S)I ( T )

Teleinformasi Data Untuk Feeder 20 kV Tipe 3

Group Bay Data No Kode Fungsi Tipe Jmh

3 F Frekuensi 1 Busbar TM 10 V Tegangan 3 1 AMF Ampere Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1

TM

7 P Daya Aktif 1 20 AR Circuit Breaker Auto Reclose A 1 21 ARO Auto Reclose Off A 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1 53 TCS1 Trip Coil Supervisory 1 A 1

TSS

55 UFR Under Frequency Relay Operate A 1 1 ARU Auto Reclose Use/Unuse I 1 2 BI Bus Isolator Switch Closed/Opened I 1

Feeder

TSD

4 CB Circuit Breaker Closed/Opened I 1

Page 173: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

161

Group Bay Data No Kode Fungsi Tipe Jmh

7 ES Earth Switch Closed/Opened I 1 10 LR Local Remote I 1 12 RR Recloser Reset I 1 1 ARU Auto Recloser Use/Unuse 1 2 CB Circuit Breaker Closed/Opened 1 6 LR Local Remote 1

RCD

8 RR Recloser Reset 1

Page 174: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

162

DB-09: Bus Section 20 kV Tipe 1

BUS SECTION 20 KVTYPE 1

DB- 09

L/R

Teleinformasi Data Untuk Bus Section 20 kV Tipe 1 Group Bay Data No Kode Fungsi Tipe Jmh

TM 2 CCB Counter of Circuit Breaker 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1

TSS

53 TCS1 Trip Coil Supervisory 1 A 1 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1

TSD

10 LR Local Remote I 1 2 CB Circuit Breaker Closed/Opened 1

Bus Section

RCD 6 LR Local Remote 1

Page 175: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

163

DB-10: Bus section 20 kV Tipe 2

BUS SECTION 20 KVTYPE 2

DB -10

L/R

Teleinformasi Data Untuk Bus Section 20 kV Tipe 2

Group Bay Data No Kode Fungsi Tipe Jmh

TM 2 CCB Counter of Circuit Breaker 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1

TSS

53 TCS1 Trip Coil Supervisory 1 A 1 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1 10 LR Local Remote I 1

TSD

11 RACK Circuit Breaker Rackin/Rackout I 1 2 CB Circuit Breaker Closed/Opened 1

Bus Section

RCD 6 LR Local Remote 1

Page 176: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

164

DB-11: Kopel

KOPELDB -11

L/R

Teleinformasi Data Untuk Kopel Group Bay Data No Kode Fungsi Tipe Jmh

TM 2 CCB Counter of Circuit Breaker 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1

TSS

53 TCS1 Trip Coil Supervisory 1 A 1 2 BI Bus Isolator Switch Closed/Opened I 2 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1

10 LR Local Remote I 1 TSD

11 RACK Circuit Breaker Rackin/Rackout I 1 2 CB Circuit Breaker Closed/Opened 1

Bus Section

RCD 6 LR Local Remote 1

Page 177: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

165

DB-12: Capacitor Bay

CAPACITOR BAYDB -12

Q L/R

Teleinformasi Data Untuk Capasitor Bay

Group Bay Data No Kode Fungsi Tipe Jmh

2 CCB Counter of Circuit Breaker 1 4 I Arus 3 5 KVARH Kilovar Hour 1 6 KWH Kilowatt Hour 1 7 P Daya Aktif 1

TM

9 Q Daya Reaktif 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 35 LPA Low Pressure Alarm A 1 37 P1DEF Directional Earth Fault A 1 38 P2GFR Ground Fault Relay A 1 39 P2OCR Over Current Relay A 1 41 PTF Protection Faulty A 1

TSS

53 TCS1 Trip Coil Supervisory 1 A 1 2 BI Bus Isolator Switch Closed/Opened I 2 3 CAM Capacitor Auto/Manual I 1 4 CB Circuit Breaker Closed/Opened I 1 7 ES Earth Switch Closed/Opened I 1

TSD

10 LR Local Remote I 1 2 CB Circuit Breaker Closed/Opened 1

Capasitor

RCD 6 LR Local Remote 1

Page 178: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

166

DB-13: SUTM radial dengan keypoint dan PBO

SUTM RADIALDENGAN KEYPOINT DAN PBO

DB -13

PBO

IV

KP

I

I I

L/R V (R)V (S)V (T)

L/R

L/R

Teleinformasi Data Untuk SUTM radial dengan keypoint dan PBO

Group Bay Data No Kode Fungsi Tipe Jmh

4 I Arus 3 TM 10 V Tegangan 3 15 220F 220 VAC Failure A 1 17 48RF 48 VDC Rectifier Failure A 1 18 48SF 48 VDC Supply Failure A 1 25 DCG DC Ground A 1 26 DOOR Door Activated A 1 27 FOTF FO Terminal Faulty A 1 33 HFD Homopolar Fault Detector A 3

TSS

42 RADF Radio Link Faulty A 1 7 ES Earth Switch Closed/Opened I 1 9 LBS Load Break Switch Closed/Opened I 1 TSD 10 LR Local Remote I 1 5 LBS Load Break Switch Closed/Opened 1

Keypoint

RCD 6 LR Local Remote 1 1 AMF Amperes Fault 3 2 CCB Counter of Circuit Breaker 1 4 I Arus 1

TM

10 V Tegangan 3 15 220F 220VAC Failure A 1 17 48RF 48VDC Rectifier Failure A 1

PBO

TSS

20 AR Circuit Breaker Auto Reclose A 1

Page 179: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

167

Group Bay Data No Kode Fungsi Tipe Jmh

21 ARO Auto Reclose Off A 1 22 CBDF Circuit Breaker Drive Failure A 1 23 CBTR CB Trip A 1 25 DCG DC Ground A 1 26 DOOR Door Activated A 1 27 FOTF FO Terminal Faulty A 1 31 GFRF Ground Fault Relay Failure A 1 35 LPA Low Pressure Alarm A 1 36 OCRF Over Current Relay Failure A 1 42 RADF Radio Link Faulty A 1 53 TCS1 Trip Coil Supervisory 1 A 1 1 ARU Auto Recloser Use/Unuse I 1 4 CB Circuit Breaker Closed/Opened I 1 10 LR Local Remote I 1

TSD

12 RR Recloser Reset I 1 1 ARU Auto Recloser Use/Unuse 1 2 CB Circuit Breaker Closed/Opened 1 6 LR Local Remote 1

RCD

8 RR Recloser Reset 1

Page 180: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

168

DB-14: SUTM radial dengan keypoint tanpa PBO

SUTM RADIALDENGAN KEYPOINT TANPA PBO

DB -14

KP

I

I I

L/R V (R)V (S)V (T)

L/R

L/R

Teleinformasi Data Untuk SUTM radial dengan keypoint tanpa PBO

Group Bay Data No Kode Fungsi Tipe Jmh

4 I Arus 3 TM 10 V Tegangan 3 15 220F 220 VAC Failure A 1 17 48RF 48 VDC Rectifier Failure A 1 18 48SF 48 VDC Supply Failure A 1 25 DCG DC Ground A 1 26 DOOR Door Activated A 1 27 FOTF FO Terminal Faulty A 1 33 HFD Homopolar Fault Detector A 3

TSS

42 RADF Radio Link Faulty A 1 7 ES Earth Switch Closed/Opened I 1 9 LBS Load Break Switch Closed/Opened I 1 TSD 10 LR Local Remote I 1 5 LBS Load Break Switch Closed/Opened 1

Keypoint

RCD 6 LR Local Remote 1

Page 181: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

169

DB-15: SUTM loop dengan beberapa keypoint

SUTM LOOPDENGAN BEBERAPA KP

DB -15

I

V

I

VI

L/R

L/R

L/R

V

Teleinformasi Data Untuk SUTM loop dengan beberapa keypoint Group Bay Data No Kode Fungsi Tipe Jmh

4 I Arus 3 TM 10 V Tegangan 3 15 220F 220 VAC Failure A 1 17 48RF 48 VDC Rectifier Failure A 1 18 48SF 48 VDC Supply Failure A 1 25 DCG DC Ground A 1 26 DOOR Door Activated A 1 27 FOTF FO Terminal Faulty A 1 33 HFD Homopolar Fault Detector A 3

TSS

42 RADF Radio Link Faulty A 1 7 ES Earth Switch Closed/Opened I 1 9 LBS Load Break Switch Closed/Opened I 1 TSD 10 LR Local Remote I 1 5 LBS Load Break Switch Closed/Opened 1

Keypoint

RCD 6 LR Local Remote 1

Page 182: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

170

DB-16: Spindle 20 kV

SPINDLE 20 kVDB -16

20 kVBusbar

GI

GT

GH

GD

GD

L/R

L/R

Teleinformasi Data Untuk Spindle 20 kV

Group Bay Data No Kode Fungsi Tipe Jmh

15 220F 220 VAC Failure A 1 17 48RF 48 VDC Rectifier Failure A 1 18 48SF 48 VDC Supply Failure A 1 25 DCG DC Ground A 1 26 DOOR Door Activated A 1 27 FOTF FO Terminal Faulty A 1 33 HFD Homopolar Fault Detector A 3

TSS

42 RADF Radio Link Faulty A 1 7 ES Earth Switch Closed/Opened I 1 9 LBS Load Break Switch Closed/Opened I 1 TSD 10 LR Local Remote I 1 5 LBS Load Break Switch Closed/Opened 1

Gardu Hubung

RCD 6 LR Local Remote 1 15 220F 220 VAC Failure A 1 17 48RF 48 VDC Rectifier Failure A 1 18 48SF 48 VDC Supply Failure A 1 25 DCG DC Ground A 1 26 DOOR Door Activated A 1 27 FOTF FO Terminal Faulty A 1 33 HFD Homopolar Fault Detector A 3

TSS

42 RADF Radio Link Faulty A 1 7 ES Earth Switch Closed/Opened I 1

Gardu Tengah

TSD 9 LBS Load Break Switch Closed/Opened I 1

Page 183: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

171

Group Bay Data No Kode Fungsi Tipe Jmh

10 LR Local Remote I 1

5 LBS Load Break Switch Closed/Opened 1 RCD 6 LR Local Remote 1

Page 184: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

172

Lampiran E – Struktur Informasi

Page 185: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

173

STRUKTUR INFORMASI Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilan bagian, yaitu:

A B C D E F G H I Bagian A: Nomor ID, terdiri dari 6 digit (sebagai primary key) Bagian B: Time stamp, sebanyak karakter 23 karakter Bagian C: Nama GI/GH/GT/KP, sebanyak 20 karakter Bagian D: Level tegangan, sebanyak 5 karakter Bagian E: Nama bay / feeder, sebanyak 20 karakter Bagian F: Kode nama peralatan atau nama alarm atau nama elemen, sebanyak 5 karakter Bagian G: Status peralatan atau status alarm, sebanyak 15 karakter Bagian H: Nama user yang melakukan aksi (seperti remote control, dan sebagainya),

sebanyak 10 karakter Bagian I: Prioritas alarm, sebanyak 8 karakter Struktur di atas ditentukan dalam field yang berbeda. Contohnya dapat dilihat pada Tabel 1 berikut:

Tabel 1. Struktur informasi

A B C D E F G H I RCC Cawang 110007 02/03/2007 11:10:05.320 Cawang 150 Gandul-1 BI1 Close Class-3 110009 05/03/2007 07:00:55.115 Gandul 150 Cawang-1 ARO Appear Class-2 RCC Waru 140104 11/04/2007 17:44:21.220 Rungkut 150 Waru-1 LT Disappear Class-1 140085 12/04/2007 20:11:51.312 Waru 150 Bangil-1 CB Invalid Class-4 DCC Pasuruan 430011 25/04/2007 00:30:35.000 Gondang Wetan 20 Bromo CB Open Adi Class-1 430012 19/11/2007 10:00:05.520 Gondang Wetan 20 Semeru CBTR Appear Class-1

A. Nomor ID Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yang menyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTU bersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut

A1 A2 Bagian A1: Kode area Bagian A2: Nomor RTU

Page 186: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

174

Kode area Kode area yang terdiri dari 3 karakter adalah sebagai berikut: NCC : 900 IRCC : x00 IRCC Jawa-Bali : 100 IRCC Sumatera : 200 IRCC Kalimantan : 300 IRCC Sulawesi : 400 IRCC di Indonesia Timur : 500 RCC di Jawa-Bali : 1xx RCC Cawang : 110 RCC Cigereleng : 120 RCC Ungaran : 130 RCC Waru : 140 RCC di Sumatera : 2xx RCC Medan : 210 RCC Padang : 220 RCC Palembang : 230 RCC di Kalimantan : 3xx RCC Banjarbaru : 310 RCC Balikpapan : 320 RCC di Sulawesi : 4xx RCC Makassar : 410 RCC Manado : 420 RCC di Indonesia Timur : 5xx IDCC : x00 IDCC Jawa-Bali : 100, 200, 300, 400 IDCC Sumatera : 500, 600 IDCC Kalimantan : 700 IDCC Sulawesi : 800 IDCC di Indonesia Timur : 900 DCC di Jakarta : 0xx – 1xx DCC daerah Jawa bagian Barat : 2xx DCC daerah Jawa bagian Tengah : 3xx DCC daerah Jawa bagian Timur dan Bali : 4xx DCC daerah Sumatera : 5xx – 6xx DCC daerah Kalimantan : 7xx DCC daerah Sulawesi : 8xx DCC daerah Indonesia Timur : 9xx

Nomor RTU Nomor RTU terdiri dari 3 digit (001 – 999)

Page 187: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

175

B. Time stamp Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari 23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2 karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakter atau sampai dengan orde milidetik). Contohnya:

25/04/2007 00:30:35.000

19/11/2007 10:00:05.520

C. Nama GI/GH/GT Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter). Contohnya adalah sebagai berikut:

Cawang Gandul Gondang Wetan Rungkut Waru

Cawang : menyatakan GI Cawang (dikontrol oleh RCC Cawang). Gandul : menyatakan GI Gandul (dikontrol oleh RCC Cawang). Waru : menyatakan GI Waru (dikontrol oleh RCC Waru). Rungkut : menyatakan GI Rungkut (dikontrol oleh RCC Waru). Gondang Wetan : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC Pasuruan).

D. Level Tegangan Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada Tabel 2 berikut:

Tabel 2. Level tegangan

Tegangan Level Tegangan 500 kV 500 275 kV 275 150 kV 150 70 kV 70 66 kV 66 30 kV 30 25 kV 25

23.5 kV 23 20 kV 20

16.75 kV 16.75 16.5 kV 16.5 13 kV 13 11 kV 11 6 kV 6

Page 188: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

176

E. Nama Bay / Feeder Nama Bay/Feeder terdiri dari 20 karakter. Contohnya dapat dilihat pada Tabel 3 berikut:

Tabel 3. Nama bay atau feeder

Nama Bay / Feeder Kode Pusat Listrik Pusat Listrik Tenaga Air PLTA Pusat Listrik Tenaga Diesel PLTD Pusat Listrik Tenaga Gas PLTG Pusat Listrik Tenaga Panas Bumi PLTP Pusat Listrik Tenaga Nuklir PLTN Pusat Listrik Tenaga Uap PLTU Pusat Listrik Gas/Uap (Combine Cycle) PLTGU Pusat Listrik Tenaga Mikrohidro PLTMH Pusat Listrik Tenaga Angin/Bayu PLTB Peralatan di Gardu Induk Line Bay (Feeder Bay) Format penulisan:

IRCC/RCC: Nama GI lawan + ”-” + nomor penghantar. Contohnya: o Gandul-1 o Cawang-1

DCC: Nama Feeder. Contohnya: o Bromo o Semeru

Bay ke Unit Generator UNIT Busbar BUSBAR Kopel (Bus Tie) KOPEL Bus Section BUSSECT Trafo TRAFOx (X adalah Kode Tegangan

dari primer dan sekunder trafo) Diameter DAMTR Shunt Reactor SHTXL Shunt Capacitor SHTXC Cadangan SPARE Nama Bay Bay 500 kV diameter 1 busbar A 7A1 Bay 500 kV diameter 3 antara busbar A dan B

7AB3

Bay 500 kV diameter 5 busbar B 7B5

Kode tegangan dari primer dan sekunder trafo dapat dilihat pada Tabel 4 berikut: Tabel 4. Kode tegangan dari primer dan sekunder trafo

Tegangan Range Kode Tegangan Rendah (TR) sampai 1000 V 0 Tegangan Menengah (TM) 1 sampai 10 kV 1 Tegangan Menengah (TM) 10 sampai 30 kV 2

Page 189: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

177

Tegangan Range Kode Tegangan Menengah (TM) 30 sampai 60 kV 3 Tegangan Tinggi (TT) 60 sampai 90 kV 4 Tegangan Tinggi (TT) 90 sampai 200 kV 5 Tegangan Tinggi (TT) 200 sampai 400 kV 6 Tegangan Ekstra Tinggi (TET) 400 sampai 600 kV 7 Tegangan Ekstra Tinggi (TET) 600 sampai 1000 kV 8 Tegangan Ekstra Tinggi (TET) 1000 kV ke atas 9

F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen Kode nama peralatan atau nama alarm atau nama elemen terdiri dari 5 karakter. Contohnya dapat dilihat pada Tabel 5 sebagai berikut:

Tabel 5. Kode nama peralatan/alarm/elemen Nama Kode Circuit Breaker CB Bus Isolator #1 BI1 Bus Isolator #2 BI2 Line Isolator LI Ground Fault GF Over Current OC Line Trip LT Breaker Fault BRF Power Supply Faulty PSF Daya MW P Daya MVAr Q Arus I Load Break Switch LBS Recloser REC

Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal, telemeasurement atau remote kontrol seperti ditunjukan pada Lampiran A-D).

G. Status Peralatan atau Status Alarm Status peralatan atau status alarm terdiri dari 15 karakter, menunjukkan status dari peralatan atau alarm pada bagian E. Contohnya adalah sebagai berikut:

Close Open Invalid Appear Disappear On Off

H. Nama user yang melakukan aksi Nama user terdiri dari 10 karakter, menunjukkan nama user yang login pada saat melakukan aksi tertentu seperti Remote Control, Overall Check, start dan stop perangkat keras, out of service RTU dan Inter Center Link, dan sebagainya. Contohnya adalah sebagai berikut:

Page 190: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

178

Adi Lukman Jufri Joko Syafnir Kuncoro

I. Prioritas Alarm Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1 merupakan kelas alarm yang menempati prioritas paling tinggi. Contohnya sebagai berikut:

Class-1 Class-2 Class-3 Class-4

Struktur Informasi Khusus Penamaan Pemutus Tenaga Pada Gardu Induk 1 ½ Breaker. Struktur informasi khusus untuk pemutus tenaga pada gardu induk 1 ½ breaker dipakai untuk tujuan komunikasi verbal diantara operator. Kode tersebut hanya ditampilkan di VDU (Video Display Unit), dan dipergunakan di dalam database. Struktur informasi dinyatakan dengan susunan sebagai berikut:

X Y Z

Bagian X: kode referensi tegangan Bagian Y: kode nama CB Bagian Z: nomor diameter

Contoh: A untuk breaker yang terhubung langsung ke busbar A B untuk breaker yang terhubung langsung ke busbar B AB untuk breaker yang terhubung ke breaker A dan breaker B

Contohnya dapat dilihat pada Gambar 4 dan Gambar 5 berikut: Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4

Gambar 4. Struktur informasi khusus (bay diameter)

Page 191: Draft Pemeliharaan Transmisi

SPLN S5.001: 2008

179

Contoh :

GITET 500 kVSAGULING

UNIT 2 UNIT 3 UNIT 4UNIT 1

CIRATA 1 CIRATA 2

BANDUNG SELATAN 2

BUSBAR A

BUSBAR B

CIBINONG 1

7A1

7AB1

7B1

~ ~

7A3

7AB3

7B3

7AB4

7B4

7AB5

7B5

BANDUNG SELATAN 1

~ ~

CIBINONG 2

7A2

7AB2

7B2

Gambar 5. Struktur informasi khusus (gardu induk 1½ breaker)

Page 192: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

180

Lampiran F – Simbol dan Warna

Page 193: Draft Pemeliharaan Transmisi

SPLN S5.002: 2008

181

Simbol-simbol gambar yang digunakan mengacu pada Gambar 6 berikut:

Gambar 6. Simbol gambar

Page 194: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

182

Tampilan-tampilan status yang digunakan mengacu pada Gambar 7 berikut: Tampilan Status

GENERATOR

ITEMS SYMBOL R E M A R K

CB CLOSED

CB OPENED

DS CLOSED

DS OPENED

ES CLOSED

ES OPENED

RACKED IN CB CLOSED

Busbar' s color, filled

Busbar' s color, blank

RACKED IN CB OPENED

TRANSF. 2 WINDINGS

TRANSF. 3 WINDINGS

REACTOR

CAPACITOR

LBS CLOSED

LBS OPENED

GARDU PORTALTIANG

GARDU TEMBOK BESI

CUT OUT FUSE

PBO CLOSED

PBO OPENED

Feeder’s color, filledPBO

PBO

RACKED OUT CB CLOSED

RACKED OUT CB OPENED

Feeder’s color, blank

Feeder’s color

Feeder’s color

Feeder’s color, filled

Feeder’s color, blank

Feeder’s color

Feeder’s color

Feeder’s color, filled

Feeder’s color, blank

Feeder’s color, filled

Feeder’s color, blank

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

Feeder’s color

VOLTAGE STATUS : LIVE

DEAD

/

Gambar 7. Tampilan status

Page 195: Draft Pemeliharaan Transmisi

SPLN S5.002: 2008

183

WARNA TAMPILAN Tabel 6 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitor dan layar tayang.

Tabel 6. Warna tampilan URAIAN WARNA Single line diagram 500 kV Biru Single line diagram 275 kV Biru-muda Single line diagram 150 kV Merah Single line diagram 70 kV Kuning Single line diagram 30 kV Hijau Single line diagram 20 kV Coklat Single line diagram 12 kV Abu-abu Single line diagram 6 kV Merah muda Single line diagram 0.4 kV Hijau-muda All devices Warna Busbar Invalid device Ungu dan perubahan simbol Device saat loss connection (RTU out of poll) Oranye Background color Hitam Ground color Biru-tua Kondisi tidak bertegangan Putih Perubahan status karena gangguan Frame CB warna merah, blinking Perubahan status karena local dari gardu induk Warna Busbar, blinking + karakter ”L” Perubahan status karena remote dari dispatcher Warna Busbar, blinking Telemetering Putih Invalid telemetering Ungu Telesignal Alarm Warna kuning, blinking

Keterangan: • Untuk change of state gangguan, setelah acknowledge blinking hilang, warna merah

pada frame CB mengikuti warna busbar. • Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan

warna pada single line diagram level tegangan terdekat. • Warna jaringan sesuai dengan feeder colouring. • Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol dan

warna.

Page 196: Draft Pemeliharaan Transmisi

SPLN S3.001: 2008

184

Pengelola Standardisasi:

PT PLN (Persero) Litbang Ketenagalistrikan Jalan Durentiga Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762,

www. pln-litbang.co.id.