Market Trend
General needs in the past New-normal needs
Apparatus by 1000Vdc, 690Vac
Manual type, low cost
Apparatus by 1000Vdc Less interest on Short-circuit
level
LVRT and HVRT for wind turbine control and power converter
1500Vdc, 900Vac for high altitude
Compact UL Listed device
Breakers for 1500Vdc, 690Vac Bigger battery, higher kA Bi-directional
Breakers up to 1150Vac Still important : LVRT/HVRT
Now markets want to have more compatible, compact and certified solution.
Note)LVRT : Low Voltage Ride-Through, HVRT : High Voltage Ride-Through
AC
DC
Frame C Frame D Frame E
NEW
NEW
NEW NEWUe : ~690Vac In : 800~1600AUp to 50kA Compact size
Ue : 690Vac In : 630~2000AUp to 85kA 900/1000/1150Vac
Ue : 690Vac In : ~3200AUp to 100kA 900/1000/1150Vac
TBD in 2021 Ue : ~635Vac In : 800~1600AUp to 85kA
Ue : ~635Vac In : ~3200AUp to 100kA
Ue : 1500VdcIn : 800~1600AIcw=50kA/1sCompact size
Ue : 1500Vdc In : ~2000AIcw=65kA/1s Medium size
1500Vdc breaker (world first)
Ue : 1500Vdc In : ~1200, 1600Icw=50kA/1s Compact size
TBD
Ue : 1500VdcIn : ~4000AIcw=100kA/1s UL489B/489F
LS ELECTRIC AC/DC series overview
UDA Compact 1500Vdc Switch
Now markets want to have more compatible, compact and certified solution.
UL489B for PV, UL489F for Battery System
1500Vdc 1200A with motorized
UL 1600A for vertical connection
Rated Short-time : 50kA/1sec, 80kA/50ms
Operation 12500 times in No-load switching
ForSusol UL Compact DC switch-disconnector
High-voltage AC Circuit Breaker
Smaller than E-frame but covering by 2000A 1500Vdc, which C-frame could not do
Idea solution for medium-sized BCP/ESS panel
Maximum 2000A 1500Vdc
388mm width (21% narrower than Frame E)
Rated Short-time : 65kA/1sec, 100kA/0.5ms
Operation 20000 times in No-load switching
ForD-frame 1500Vdc 2000A Switch
493mm 283mm
High-voltage AC Circuit Breaker
Smaller than E-frame but covering by 2000A 1500Vdc, which C-frame could not do
ForD-frame 1500Vdc 2000A Switch
General
Standard IEC 60947-3
Utilization categoryDC-22ADC-23A
Type Fixed type
Poles 3P, 4P
Characteristics
InsulationUimp 12kV
Ui 1500V
Rated Voltage Ue1500V DC (4P)
1000V DC (3P)
Rated Current In 2000 A
Rated Short-time... Icw 65kA/1s
Lifetime Electrical 500 times
Mechanical 20000 times
▣ General specification ▣ Ordering code
High-voltage AC Circuit Breaker
Various rating : 800/900/1000/1150Vac according to specific needs and application
800/900Vac for Solar, 1000/1150Vac for Wind
Ideal solution for high altitude LV project
New OCR installed : enhanced performance
Easy maintenance : Same as previous AC ACB
ForAV-type Air Circuit Breaker
Based on delivery record for wind industry
Altitude 2000m 3000m 4000mWithstand voltage [V] 3500 3150 2800
Average insulating voltage [V] 1250 1125 1000Max. using voltage [V] 1150 1035 920
Current compensation constant 1xIn 0.98xIn 0.96xIn
High-voltage AC Circuit Breaker
Various rating : 800/900/1000/1150Vac according to specific needs and application
ForAV-type Air Circuit Breaker Characteristics
(P)(Vac)(V)(kV)
VersionSuitability for isolationDegree of pollution IEC60661-1Certification
Brand nameAV-16D□ AV-32E□
1600AF 3200AFRated current (In)at 40℃
400 / 630 / 800 / 1000 / 1250 / 1600 400 / 630 / 800 / 1000 / 1250 / 1600/ 2000 / 2500 / 3200
1150V 30 501000V 42 65
900V 50 75800V 50 75
Rated serivce breakingcapacity (Ics)
1s 30 503s 30 50
Rated making capacity
< Icw (ms) ≥ Icw
Closing time
Mechanical and Electrical Life cycle
Endurance (times) Mechanical(Without maintenance) Electrical
Dimension and Weight
Weight (3P/4P) Drawout Without cradle 37/45 44/49With cradle 70/85 88/104
Fixed 34/44 45/56External Dimensions Drawout 3P(4P) 430×334(419)×375 430×412(527)×375(H×W×D) Fixed 3P(4P) 300×300(385)×295 300×378(493)×295
CB certification according to IEC 60947-2
Number of poles 3 / 4Rated operational voltage (Ue) 1150Rated insulation voltage (Ui) 1250Rated impulse withstand voltage (Uimp) 12kV
Fixed / Withdrawable
3
% 100
SUSOL
Ampere Frame
(A)
Rated ultimate breakingcapacity (Icu) (kA)
% 100
Rated short-timewithstand current (Icw)
(kA)
12,5001,000
(kg)
(mm)
Utilization category (according to IEC 60947-2) B
Operation timeTotal Breaking time
max. 70max. 30max. 80
50kA at 1150Vac
65kA at 1000Vac
75kA at 900Vac
75kA at 800Vac
High-voltage AC Circuit Breaker
Various rating : 800/900/1000/1150Vac according to specific needs and application
ForAV-type Air Circuit Breaker
▣ Temperature derating (800/900/1000/1150Vac ACB)
Type
Connection type
Ambient temperature(°C) 40 45 50 55 60 65 70 40 45 50 55 60 65 70
AV-08D (800A) 800 800
AV-10D (1000A) 1000 1000
AV-13D (1250A) 1250 1230 1180 1120 1250 1240 1180
AV-16D (1600A) 1600 1580 1520 1450 1390 1600 1530 1460
Type
Connection type
Ambient temperature(°C) 40 45 50 55 60 65 70 40 45 50 55 60 65 70
AV-20E (2000A) 2000 1960 1890 1810 1720 2000 1900 1810
AV-25E (2500A) 2500 2390 2300 2200 2100 2500 2420 2320 2210
AV-32E (3200A) 3200 3100 2990 2870 2750 2620 3200 3150 3020 2900 2760
* Ambient temperature is greater than 60˚C, consult us.
Fixed type
Horizontal or Frontal Vertical
Fixed type
Horizontal or Frontal Vertical
BCP for containerized solution
Battery Connection Panel?
Main protection panel, between Power Conversion System and Battery Container
AC
DC
●●●
●●●
●●●
●●●
●●●
BANK 2
AC
DC
BatteryRack
●●●
●●●
●●●
●●●
●●●
BANK 1
BCP (Battery Connection Panel)
: Protection Device(CB, Relay, Fuse)
Grid Connected LV Switchgear
Air Circuit Breaker
LV SWGR
Transformer
Air Circuit Breaker
DC Switch-disconnector
LS ELECTRIC PCS for BESS
PCS (Battery Inverter)
LS ELECTRIC BCP for BESS
BPU for BESS DC MCBDC Relay
DC Switch-disconnector
SPD
CP
BPU (Battery Protection Unit)
BESS System Diagram
DC MCCB
[DC Air Circuit Breaker]• Ue : DC1200V/1500V• In : 3200A• ICW : 100kA/1s• Control Voltage : AC 220V
[AC Air Circuit Breaker]• Ue : 690Vac• In : 1600A• Control Voltage : AC 220V
[DC MCCB]• DC 1000V, ~800A, 40kA• DC 1150V, 1000,1250,1600A• DC 1500V, ~250A, 50kA
[DC Switch-Disconnector]• Ue : DC1200V/1500V• In : 4000A• ICW : 100kA/1s• Control Voltage : AC220V
Hall Sensor(Option)
DC Shunt
[Volt Meter]
[Ampere Meter]
Circuit Protectorof control power
Outline Front Back
BCP Structure
BESS Container
CASE (I)Disconnect Switch
CASE (II)Disconnect Switch + Fuse
Category Contents
Specification 1) Ue : DC 1000V / 1200V / 1500V2) In : 160~4000A3) Icw : 100kA/1s
Usage 1) Connection between PCS and Battery Rack2) Backup Protection of BPU & PCS
ConnectionMethod
1) Connecting to PCS : Cable(300~400 mm2) or Busduct
- from Top or Bottom 2) Connecting to Battery Rack : Cable(25~70mm2)
- from Top or Bottom
ComponentSelection
1) Max Voltage of Ve ≥ ESS/PV system2) Max Current of Ie ≥ ESS/PV system3) Max Icu of Icu or Icw ≥ ESS/PV system
Related Test Insulation / Temperature / Short circuit performance / Operation performance check
Technical datasheet BCP Customized design
BCP consist of DC Main Circuit (Blue box) and Control Power Circuit of Battery Rack (BPU*, BMS* - Red box).* There is no Control Operation in BCP itself.
Switch or LBS
CB or Fuse
Communication
Control power
DC main line
Index
* BCP: Battery Connection Panel
* BPU: Battery Protection Unit
* BMS: Battery Management System
* RBMS: Rack BMS
* MBMS: Module BMS
* SBMS: System BMS
Single-Iine Diagram & Control Circuit
~=
DC Switch
EMS/PMS
RBM
S
MBM
S
MBM
S
MBM
S
MBM
S
SBMSRBM
S
MBM
S
MBM
S
MBM
S
MBM
S
…GRID PCS
Low
Voltag
e (A
C 1
10~
220V
)
SMPS
BPU
BPU
BATTERY RACK
BATTERY RACK
TR
(DC 24V)
BCP Battery RackPCSAC Panel
PCS Controller
Fuse
Circuit Breaker/Switch-
disconnector
BCP installation with Battery Racks
<DC Panel>
DDH + Fuse combinated type (Upper & Lower side component changeable)
<Ratings>(1) Un (Rated Voltage) : DC 1200V/1500V(2) In (Rated Current) : 800~4000A (Typical
1600A)(3) Icw (Rated short-time withstand
current) : 100kA/1s
Actual Panel Image
3D model
CASE Study : DC Switch-disconnector + Fuse type
Single-Line Diagram 3D model
CASE Study : DC Panel only type (External Control voltage supply)=> Circuit Breakers are applied for each DC circuit