Three-Phase Three-Level Flying Capacitor PV Generation ...
-
Upload
khangminh22 -
Category
Documents
-
view
0 -
download
0
Transcript of Three-Phase Three-Level Flying Capacitor PV Generation ...
Electronics 2019, 8, 118; doi:10.3390/electronics8020118 www.mdpi.com/journal/electronics
Article
Three-Phase Three-Level Flying Capacitor PV Generation System with an Embedded Ripple Correlation Control MPPT Algorithm
Manel Hammami 1, Mattia Ricco 1, Alex Ruderman 2 and Gabriele Grandi 1,*
1 Department of Electrical, Electronic, and Information Engineering, University of Bologna,
Viale Risorgimento 2, 40136 Bologna, Italy; [email protected] (M.H.); [email protected] (M.R.) 2 Department of Electrical and Computer Engineering, Nazarbayev University, 53 Kabanbay Batyr Ave,
Astana 010000, Kazakhstan; [email protected]
* Correspondence: [email protected], Tel.: +39-051-20-93571
Received: 19 December 2018; Accepted: 21 January 2019; Published: 22 January 2019
Abstract: This paper presents the implementation of a maximum power point tracking (MPPT)
algorithm in a multilevel three-phase photovoltaic (PV) system using the ripple correlation control
(RCC) method. Basically, RCC adopts the inherent oscillations of PV current and voltage as
perturbation, and it has been predominantly used for single-phase configurations, where the
oscillations correspond to the 2nd order harmonics. The implementation of an RCC-MPPT
algorithm in a three-phase system has not been presented yet in the literature. In this paper, the
considered three-phase three-level converter is a three-level flying capacitor (FC) inverter. The
proffered RCC method uses the 3rd harmonic components of PV current and voltage for the
estimation of the voltage derivative of the power dPpv/dVpv (or current, dIpv/dVpv), compelling the PV
array to operate at or very close to the maximum power point. The analysis and calculation of the
low-frequency PV current and voltage ripple harmonic components in the three-phase flying
capacitor inverter is presented first, with reference to centered carrier-based three-level PWM. The
whole grid-connected PV generation scheme has been implemented by MATLAB/Simulink, and
detailed numerical simulations verified the effectiveness of the control method in both steady-state
and dynamic conditions, emulating different sun irradiance transients.
Keywords: Photovoltaic; three-level flying capacitor inverter; three-phase inverter; maximum
power point (MPP); ripple correlation control (RCC); low-frequency harmonics
1. Introduction
To fulfill the constantly increasing worldwide energy demand, renewable energy sources such
as photovoltaic (PV), wind, geothermal, and biomass, are being explored. Currently, PV energy is
becoming one of the most widely used renewable energy sources, due to its indubitable known
advantages and the decreasing installation costs.
In order to improve the PV conversion efficiency, maximum power point tracking (MPPT)
algorithms are widely adopted in both grid-connected and stand-alone PV systems. Among the
different methods known in the literature, the most popular and effective are perturb and observe
(P&O) [1] and incremental conductance [2]. Typical problems for these methods are the
identification of a suitable perturbation step size, and the limited maximum power point (MPP)
tracking dynamic capability during sudden variations in solar irradiance. In this class of P&O
algorithms, either fixed or variable step size are adopted to improve the settling time in transient
conditions and the MPP resolution in the steady-state operating points [3].
Similar to P&O techniques, the extremum seeking (ES) algorithm employs “ad hoc” perturba-
tions [4]. A multi-variable extremum seeking algorithm based on a single control loop for cascaded
Electronics 2019, 8, 118 2 of 15
dc/dc photovoltaic micro-converters has been proposed in [5]. A Newton-based ES algorithm has
been adopted to improve the dynamic performances of gradient-based ES in [6]. All aforementioned
algorithms implemented the ES control by injecting an external perturbation signal into the duty
cycle. On the contrary, ripple correlation control (RCC) algorithms exploit the inherent PV voltage
and current oscillations to track the MPP. In particular, for single-phase PV systems the 2nd
harmonics are exploited [4,7–13]. The RCC algorithm has good dynamic performance comparing
with the P&O algorithms and it does not require additional perturbations in tracking the MPP. A
comprehensive analysis and comparison between RCC and ES methods has been carried out in
reference [9] in case MPPT algorithms for PV systems.
The basic RCC-MPPT method has been investigated in references [9,12,14] where two low-pass
filters and two high-pass filters are used for ripple extraction and implementation. In reference [10],
a modified RCC method has been proposed by using the moving average concept instead of
high/low-pass filtering to improve the dynamic response, without the need to tune the time constant
of the low/high pass filters. Moreover, the scheme has been simplified by using only the sign of the
product of power and voltage ripple to drive the PV operating point toward the MPP. In reference
[13], a hybrid RCC-MPPT algorithm has been proposed to improve stability during sudden solar
irradiance transients. In case of three-phase two-level (2L) inverters, the RCC algorithm cannot be
applied due to the inexistence of inherent (natural) low-order harmonic oscillations on the PV side of
the inverter. In this case, the ES algorithm can be successfully applied by means of additional
perturbations, as reported in reference [15].
In recent years, multilevel inverters have become more attractive for single- and three-phase
systems thanks to their advantages over the conventional inverters [7,15–19]. They offer improved
output waveforms, lower total harmonic distortion (THD) and smaller grid filter size [20–22]. The
most common multilevel converter configurations, presented in literature, are the cascaded
H-bridge (CHB), neutral-point-clamped (NPC) and flying capacitor (FC). These types of converters
are also adopted in PV applications due to the aforementioned advantages. Multilevel flying
capacitor inverters have some specific distinct advantages over the other two topologies such as: no
need for many isolated dc sources when compared to CHB inverters, no need for clamping diodes in
contrast to NPC inverters, but still preserving the ability to self-balance the capacitor voltages.
With reference to the FC inverter, several analyses have been presented in the literature. A
mathematical model for the dynamic behavior of a simple FC inverter using a sampled-data
modeling approach has been derived in reference [23], with useful information on the power circuit
characteristics and its natural balancing property. In reference [24], a modified pulse with
modulation (PWM) strategy is introduced to improve the balancing rate of capacitor voltages,
mainly for small output voltages, by optimizing the use of redundancy of switching states. A new
PWM scheme has been proposed and analyzed in reference [25], which results in better balancing
properties than the normal phase-shifted (PS) PWM. In particular, a five-level configuration has
been considered and a modified PS-PWM scheme has been studied, solving the slow-balancing
problems of the normal PS-PWM method for odd-level of FC converters.
In general, adopting a multilevel inverter introduces different low-order voltage and current
harmonics on the dc-link side compared to the case of a single-phase H-bridge inverter where only
the 2nd order harmonics are present. The application of the RCC algorithm in case of a single-phase
inverter with level doubling network (LDN) has been introduced and examined in reference [10].
Due to the multiple harmonics, the basic implementation of the RCC-MPPT scheme becomes
deficient, leading to a misestimating of the voltage derivative of the power (dPpv/dVpv). For this
reason, a modified RCC scheme extracting the amplitude of a definite harmonic form PV voltage
and current (dc-link) waveforms has been proposed. In order to maximize the resolution, the
proposed solution makes reference to the highest amplitude harmonic, leading to a more effective
estimation of dPpv/dVpv.
Though numerous RCC-MPPT algorithms for single-phase grid-connected PV systems have
been developed, no analysis of RCC-MPPT in case of three-phase multilevel inverters has been
reported. This paper presents an RCC-MPPT algorithm for a grid-connected three-phase three-level
Electronics 2019, 8, 118 3 of 15
FC inverter (Figure 1) with reference to centered level-shifted (LS) carrier-based PWM modulation.
Moreover, a complete analysis of PV voltage and PV current harmonic components is accomplished,
being the foundation of the ripple correlation control. In this case, dc-link voltage and current
harmonics are introduced by the instantaneous power oscillations between the three flying
capacitors and the dc bus, consisting mainly of 3rd harmonic components. These voltage and current
harmonics are exploited as embedded perturbations to determine the MPP of the PV array. The
considered grid-connected three-phase PV generation system is presented in the block diagram of
Figure 1.
fL
pvi
pvV
Figure 1. Three-phase grid-connected PV generation system based on three-level FC inverter.
2. Modulation Principle for the Three-Level FC Inverter
With reference to linear and balanced sinusoidal modulation, the modulating signals (uA, uB,
and uC) correspond to the inverter output voltages (vA, vB, and vC) normalized by Vpv and averaged
over the switching period (Tsw =1/fsw):
mm
mm
mm
CuCmu
CuCmu
CuCmu
*C3
4C
*B3
2B
*AA
)(sin
)(sin
)(sin
, (1)
where ϑ = ωt is the phase angle, ω is the fundamental (angular) frequency, m is the modulation
index, *iu are the reference (normalized) output voltages (i = A, B or C), and Cm is the
common-mode signal to maximize the linear modulation range.
The voltages across the flying capacitors CA, CB and CC are spontaneously regulated to the half
of the DC-link voltage if a proper modulation technique with self-balancing capability is adopted
[19]. Introducing for the upper switch of each phase i (i = A, B, C) the switching function )1(
iS
(averaging is denoted in the following by overline) results in:
1)1( iii uuS . (2)
With reference to phase A, considering Equations (1) and (2), it becomes:
1)(sin)(sin)1(
A mm CmCmS . (3)
The switching functions for the other phases B and C are readily obtained by exploiting the
modulation symmetry among the three phases, according to Equation (1).
In order to improve the so-called sinusoidal PWM (SPWM), in which there is no common-mode
signal injection, Cm = 0, one of the most popular ways to maximize the modulation index is the so
called “centered” PWM (CPWM), consisting of the injection of a common-mode signal able to center
the modulating signals:
Electronics 2019, 8, 118 4 of 15
),,min(),,max(2
1 *C
*B
*A
*C
*B
*A uuuuuuCm . (4)
In case of sinusoidal reference voltages, Equation (1), Cm can be rewritten as:
6
11
2
3,
6
5
2,
3
2sin
2
3
6
7,
26,
3
2sin
6
7
6
5,
66,sin
2
1mCm . (5)
Figure 2 shows an example of the considered carrier-based CPWM strategy for three different
modulation indices.
Si(2), Si
(3)
Si(1), Si
(4)
ui
Figure 2. Carrier-based CPWM modulation logic for each leg (i) of three-level FC inverter in case of m
= 0.577/2 (red trace), m = 0.43 (green trace) and m = 0.577 (blue trace). Underline denotes
complementary.
3. Evaluation of PV Current and Voltage Harmonics
In the studied single-stage PV generation system (Figure 1), the PV array is directly connected
to the dc-link bus of the three-phase FC inverter. In this way, PV voltage harmonics correspond to
the inverter dc-link voltage harmonics, whereas PV current harmonics can be calculated on the basis
of the inverter dc-link current harmonics by the following procedure.
3.1. Inverter Input Current Harmonics
The instantaneous inverter input current i(t) consists of the averaged component over the
switching period i , and the instantaneous switching ripple component i . Similarly, the current
averaged over the switching period consists of its averaged component over the fundamental
period Idc (dc component) and the alternating low-frequency harmonic component i~
. These
compositions are summarized as:
iiIiiti dc ~
)( . (6)
Neglecting the switching ripple, the output currents can be considered a sinusoidal balanced
system with the amplitude Iac and the general output phase angle comparing to grid voltages:
)(sin
)(sin
(sin
34
c
32
b
a
ac
ac
ac
Ii
Ii
Ii
. (7)
For each inverter leg, the averaged input current (over the switching period) can be determined
by multiplying the switching function of upper switch by the corresponding output current. With
reference to leg A, it leads to:
aAA)1( iSi . (8)
Electronics 2019, 8, 118 5 of 15
By introducing Equations (3) and (7) in Equation (8), the averaged current of the leg A becomes:
]1)(sin)(sin[(sinA mmac CmCmIi . (9)
The resulting averaged total input current i is the sum of the three leg currents:
cba iSiSiSi )1()1()1(
CBA . (10)
In the following, the analysis is restricted to the phase angle span 2/3 since the inverter input
current has a periodicity of T/3. In particular, with reference to the phase angle range 2/3 ≤ ≤ 4/3,
the inverter input current can be expressed in the following two sub-ranges /3:
3
4 ,
3
2 ,)1(
cCbaA
cC
)1()1(
)1(
iSiiS
iS
i . (11)
Introducing Equations (1), (2), and (7) in Equation (11) leads to:
3
4
6
7,cos5
3cos
2
32cos3
6
7 ,cos
2
33
2cos
2
1
6
72cos3
6
5,
6cos
62cos3
6
5
3
2 ,
6cos
2
32cos3
2acmI
i . (12)
By examining Equation (12), the average and the low-frequency input current components can
be determined in case of centered PWM as:
cos2
3acdc ImI , (13)
3
4
6
7,cos2
3cos
2
32cos3
6
7 ,cos
2
3
2cos
2
1
6
72cos3
6
5,)cos(3
6cos
62cos3
6
5
3
2 ,)cos(3
6cos
2
32cos3
2
~ acmIi . (14)
Although the above developments are carried out for centered PWM, the input inverter current
analysis can be similarly extended to other PWM techniques. As an example, the simpler case of
sinusoidal PWM has been presented in reference [21].
In order to prove the validity of Equations (12)–(14), some simulation tests concerning the input
inverter currents, with specific reference to unity power factor ( = 0°) and unity sinusoidal output
currents (Iac = 1A), are presented in Figure 3.
In particular, top traces in Figure 3 show the simulation results comparing the instantaneous
input current of leg A iA (blue trace) with its averaged value over the switching period Ai (red
trace), and the corresponding low-frequency current component calculated by replacing Equation
(5) in Equation (9) (green trace). Two cases of modulation index m = 0.577/2 (Figure 3, left) and m =
0.577 (Figure 3, right) are considered.
Electronics 2019, 8, 118 6 of 15
The bottom traces in Figure 3 show the total instantaneous inverter input current i(t) (blue
trace) and its averaged value over the switching period i (red trace). The averaged current
component (green trace) is determined analytically in case of centered PWM by Equation (12).
Figure 3 shows a perfect matching between theoretical and simulated results. The slight delay (Tsw/2)
between numerically averaged values and the corresponding theoretical averaged values is due to
the numerical averaging itself.
Figure 3. One leg input current (top) and total inverter input current (bottom): instantaneous value
(blue trace), its numerically averaged value over the switching period (red), and theoretical value
(green) in case of for m = 0.577/2 and m = 0.577 (from right to left), Iac = 1 A and
3.2. PV Voltage Harmonics
Similarly to the input dc-link current, dc-link voltage components can also be pointed out. The
instantaneous dc-link voltage vpv, corresponding to the PV voltage, consists of its averaged value
over the switching period pvv and the instantaneous switching ripple vpv. Also, the averaged
component over the fundamental period Vpv (dc component) and the low-frequency harmonic
component pvv~ can be introduced, leading to:
pv pv pv pv pv pv pv pvv v v V v v V v . (15)
The switching ripple component vpv is practically insignificant for switching frequencies
starting from few kHz, being completely smoothed by the dc-link capacitor. For this reason, it is
assumed here to be vpv ≈ 0. The alternating low-frequency voltage component can be evaluated
based on the low-frequency input current component i~
taking into account the whole dc-link
impedance, given by the parallel of the capacitor reactance and the equivalent resistance of the PV
array at maximum power point (Rpv ≈Vmpp/Impp).
Taking into consideration the expected parameters for PV arrays and dc-link capacitors, the
assumption Rpv >> 1/(kC) is usually true, with k being the harmonic order. In this case, the whole
alternating input current component is circulating through the dc-link capacitor, and the alternating
dc-link (PV) voltage component can be calculated by integrating Equation (14). The resulting four
contributions can be adopted in order to calculate the amplitude (peak value) of the alternating
low-frequency voltage component:
Electronics 2019, 8, 118 7 of 15
24,
13,
2,
,1
V~
V~
V~
V~
cos8
32sin
38V~
cos8
32sin
38V~
pv
pv
acpv
acpv
C
Im
C
Im
. (16)
As most of the grid-connected PV systems operate under unity power factor conditions, the
case = 0° is considered in the following developments. In this case, the peak of the alternating
low-frequency voltage ripple is calculated taking into account either the first or the second
contribution, leading to:
2 3V 0.04
8ac ac
pv
I Im m
C C
. (17)
Equation (17) presents the peak value of the alternating voltage ripple in case of CPWM with
reference to = 0. However, the peak value of the same quantity has been determined in case of
SPWM in reference [21] as:
V 0.167 acpv
Im
C . (18)
Comparing Equations (17) and (18), it should be noted that practically the peak value of the
alternating low-frequency voltage ripple in case of CPWM is almost four times less than the voltage
ripple in the case of SPWM.
As an example, the instantaneous PV voltage is shown in Figure 4 (green trace) together with its
averaged value over the switching period (pink trace) in case of Iac/C = 1 for two cases of
modulation indices m = 0.577/2 and m = 0.577. A small delay between averaged and instantaneous
values (Tsw/2) can be noticed, due to the averaging itself. The peak value of the alternating PV
voltage component corresponds to the result obtained by Equation (17). In particular, pvv~ is equal
to 0.011 V and 0.023 V for m = 0.577/2 and m = 0.577, respectively.
As expected, there is a very good matching between simulation and analytical results.
11 mV
0.22 Time (s)
23 mV
0.22 Time (s)
Figure 4. Alternating PV voltage ripple (green trace) and its averaged value over the switching
period (pink trace), for m = 0.577/2 (left) and m = 0.577 (right), Iac/wC = 1.
3.3. PV Current Harmonics
With regard to the PV voltage vpv (Equation 15) and neglecting the switching frequency
component, the instantaneous PV current ipv can be written as:
pvpvpv iIi~
, (19)
Electronics 2019, 8, 118 8 of 15
being Ipv the average over the fundamental period (Ipv = Idc, due to the dc-link capacitor) and pvi~
the
alternating low-frequency harmonic component, calculated as:
pvpvpv Rvi /~~ . (20)
The amplitude of the alternating low-frequency PV current ripple is calculated based on
Equations (17) and (20) as:
2 30.04
8ac ac
pv
pv pv
I II m m
R C R C
. (21)
As an example, Figure 5 shows the instantaneous PV current (red trace) together with its
averaged value over the switching period (blue trace) in case of Iac/C = 1 and for two cases of
modulation index, considering a PV series equivalent resistance Rpv = 7.13 , representing the scale
factor with Figure 4.
1.5 mA
Time (s)
3.2 mA
Time (s)
Figure 5. Alternating PV current ripple (red trace) and its averaged value over the switching period
(blue trace), for m = 0.577/2 (left) and m = 0.577 (right), Iac/wC = 1 and Rpv = 7.13 .
4. Proposed RCC-MPPT Algorithm
Figure 6 presents the block diagram of the adopted control scheme, including MPPT and
dc-link (PV) voltage regulation. In particular, the proposed RCC algorithm estimates the voltage
derivative of the power, dPpv/dVpv, used to drive the working point to the maximum power point.
Integrating dPpv/dVpv, the reference dc-link voltage vpv* is simply obtained and a proportional-integral
(PI) voltage regulator can be used to determine the reference grid current amplitude Iac*. In order to
inject a sinusoidal current into the grid with unity power factor, a traditional dq current controller
has been used.
PW
M
*acI
*ABCv
abcv abci
controllervoltage
PV
pvipvv
pvv
*pvv
pv
pv
dV
dPpvv
Figure 6. Control scheme of the PV generation system.
An example of PV voltage and current ripple in case of a three-phase FC inverter configuration
is given in the following. Figure 7 shows the results considering the PV conversion scheme for a
Electronics 2019, 8, 118 9 of 15
given operating point. As expected, the inverter voltage has nine levels for a higher modulation
index. Also, it is noticeably clear that PV voltage and current contain a huge 3rd harmonic component
(150 Hz) and are in phase opposition.
(a)
(b)
(c)
vA
ia
ipv
vpv
Time (s)
Figure 7. Simulation example of: (a) grid current and inverter output voltage, (b) PV voltage, and (c)
PV current, in case of three-phase flying capacitor inverter.
In case of three-phase PV systems, with the inverter being directly connected to the PV array,
the FC inherent 3rd (and odd multiple) order harmonic appears in PV current and PV voltage (as
shown in Figure 7). As is known, ripple correlation control algorithm is able to exploit the amplitude
of these oscillations to provide information about the operating point of the PV array. Considering
the working point Q, the voltage derivative of the PV power dPpv/dVpv can be s written as:
pv
Qpv
pvpv
Qpv
pvV
dV
dII
dV
dP , (22)
where dIpv/dVpv is defining the voltage derivative of the current as:
pv
Qpv
pvpv v
dV
dIi ~~
. (23)
A conventional RCC-MPPT algorithm is implemented by multiplying the voltage oscillation by
the current oscillation, and integrating over the harmonic period [10]. As an alternative
implementation, the estimation of dIpv/dVpv (and then dPpv/dVpv) can be carried out by considering a
specific harmonic order, which is the 3rd in the case of the FC inverter. Equation (23) can be then
rewritten as:
3,3,~~
pv
Qpv
pvpv v
dV
dIi . (24)
By following the approach of the conventional RCC-MPPT implemented in [10], the estimation
of the voltage derivative of the current dIpv/dVpv can be calculated, considering the third harmonic
component as:
Electronics 2019, 8, 118 10 of 15
3,
3,
23,
3,3,
23,
3,3,3
~
~~
pv
pv
pv
pvpv
t
Tt
pv
t
Tt
pvpv
Qpv
pv
V
I
V
VI
dtv
dtvi
dV
dI
. (25)
It should be noted that dIpv/dVpv derived by Equation (25) is calculated by integrating the
product of the PV voltage and current over the fundamental period T, as defined by Fourier series
(FS) to calculate the 3rd harmonic. The block diagram of Figure 8 shows a possible implementation of
Equation (25), with the estimation of dPpv/dVpv considering only the 3rd harmonic component.
LPF
3,pvI
3,pvV
harmonic
FS
rd3
harmonic
FS
rd3
pvi
pvv
pvi~
pv
pv
dV
dP
pv
pv
dV
dI
pvV
pvI
pvV
pvI
pvv~
Hz
MAvg
150
Hz
MAvg
150
Figure 8. Block diagram of proposed RCC, estimating dPpv/dVpv by the 3rd harmonic component.
5. Simulation Results
In order to validate the proposed analysis, the three-phase grid-connected PV generation
system shown in Figure 1 was simulated in Matlab-Simulink. The circuit parameters are
summarized in Table 1. A string of series/parallel connected PV modules has been adopted as PV
source, according to the data given in Table 2 in standard test conditions (STC). In particular, the
considered PV modules are SP-305 type (96 cells, monocrystalline).
Table 1. Simulation circuit parameters.
Label Description Parameters
Vac Grid voltage (rms) 230 V
Lf, Rf Ac-link inductor 1 mH, 3 m
C DC-link capacitor 2 mF
CA, CB, CC Flying capacitors 5 mF
f, fsw Fundamental and switching frequencies 50 Hz, 3kHz
Table 2. PV module specifications (STC) and modules arrangement.
Label Description Parameters
VOC Open circuit voltage 64.2 V
ISC Short circuit current 5.96 A
Vmpp Maximum photovoltaic voltage 54.7 V
Impp Maximum photovoltaic current 5.58 A
NS Number of series-connected modules per string 16
NP Number of parallel strings 22
The first simulation test is carried out in order to verify the input/output steady-state
waveforms of the PV generation system with considered three-phase three-level FC inverter.
Electronics 2019, 8, 118 11 of 15
In particular, Figure 9 shows grid voltage and current (top traces), PV voltage (medium trace)
and PV current (bottom trace). It can be noticed that the grid current is almost sinusoidal, with unity
power factor. As expected, the PV voltage and PV current have 3rd harmonic component oscillations
(150 Hz), in phase opposition. The proposed RCC-MPPT algorithm can well track the maximum
power point at sun irradiance E = 1000 W/m2 (in this case Vmpp = 875 V and Impp = 123 A).
Figure 9. Input/output steady-state waveforms of the FC in case of sun irradiance E = 1000 W/m2:
grid voltage and current (top traces), PV voltage (middle trace) and PV current (bottom trace).
The following simulation tests are carried out to verify the dynamic performance of the
proposed RCC-MPPT algorithm in case of fast solar irradiance transients. In particular, two
scenarios have been considered:
1. Sun irradiance (ramp) increase,
2. Sun irradiance (ramp) decrease.
The cell temperature has been considered constant (25°C) during simulations for both
scenarios.
The simulation results depicted in Figures 10 and 11 show the behavior of the considered
system during the first scenario. A linear ramp increase of solar irradiance from 500 W/m2 to 1000
W/m2 is applied in a transient period of 200 ms, between 1.3 s and 1.5 s. The results clearly indicate
that as soon as the transient occurs, the estimation of dPpv/dVpv is oscillating. However, it is almost
acceptable during the steady-state (Figure 10b), which means that the PV current and the PV voltage
perfectly follow the MPP under this kind of smooth irradiance change (Figure 10c and d). Figure 10e
presents the waveform of the injected grid current. The injected grid current is perfectly sinusoidal
and well controlled thanks to the dynamic performance of the dq current controller.
Figure 11 shows the Ppv(Vpv) and Ipv(Vpv) diagrams corresponding to the transient depicted in
Figure 10. The operating point moves from the first MPP, before the solar irradiance transient, to the
new MPP, in the steady-state condition after the transient.
Electronics 2019, 8, 118 12 of 15
Figure 10. Irradiance ramp increase: (a) irradiance, (b) power derivative, (c) photovoltaic current. (d)
photovoltaic voltage, and (e) grid current, in case of proposed RCC-MPPT algorithm.
Figure 11. Effects of a 50% irradiance transient of PV power vs. PV voltage in case of irradiance ramp
decrease.
Simulation results for ramp decrease in solar irradiance are presented in Figure 12 and 13. In
this case, the initial value of solar irradiance is 1000 W/m2, decreasing linearly to 500 W/m2 in a
period of 200 ms. As can be seen, the estimation of dPpv/dVpv is correct during the steady state (Figure
12b). At the end of the transient, the estimation of dPpv/dVpv becomes correct again, and the operating
point is correctly driven toward the MPP. The current injected into the grid is perfectly sinusoidal
and follows the sun irradiance profile (Figure 12e). The path of the operating points is displayed on
the Ppv(Vpv) and Ipv(Vpv) diagrams and presented in Figure 13.
Electronics 2019, 8, 118 13 of 15
Figure 12. Irradiance ramp decrease: (a) irradiance, (b) power derivative, (c) photovoltaic current, (d)
photovoltaic voltage, and (e) grid current, in case of proposed RCC-MPPT algorithm.
Figure 13. Effects of a 50% irradiance transient of PV power vs. PV voltage in case of irradiance ramp
decrease.
6. Conclusion
In this paper, an original RCC-MPPT algorithm suitable for three-phase three-level flying
capacitor photovoltaic systems has been proposed and analyzed in detail. The three-phase FC
inverter introduces voltage and current harmonics on the input (i.e., PV) side. In particular, a
significant 3rd order harmonic is clearly noticeable, whereas higher harmonic components have
much lower amplitudes. Both PV voltage and current harmonic amplitudes are analytically
Electronics 2019, 8, 118 14 of 15
calculated in the whole modulation range in case of centered PWM, offering the possibility of a
precise and effective design of the DC-link capacitor in order to obtain the desired ripple amplitude.
Because of the presence of different harmonics, a ripple correlation control scheme extracting
the amplitude of a specific harmonic from PV voltage and current waveforms has been proposed in
order to track the maximum power point of the PV arrays. Specifically, the estimation of dIpv/dVpv
(and then dPpv/dVpv) is carried out by considering the 3rd order harmonic of PV voltage and current
oscillations.
Numerical tests have been performed to prove the effectiveness of the whole PV generation
scheme, including three-phase three-level FC inverter and the proposed RCC-MPPT algorithm.
Tests have been carried out considering both steady-state conditions and fast solar irradiance
transients in order to verify the dynamic performance of the proposed RCC algorithm, resulting in
an effective and original MPPT method in the case of three-phase PV systems.
Author Contributions: M.H. and G.G. developed the theoretical analysis; M.H. performed the simulation
results, also providing for the manuscript arrangement in cooperation with M.R.; A.R. and G.G. generally
supervised and finalized the work.
Funding: This research received no external funding.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Elgendy, M.A.; Zahawi, B.; Atkinson, D.J. Assessment of Perturb and Observe MPPPT Algorithm
Implementaion Techniques for PV Pumping Applications. IEEE Trans. Sustain. Energy 2012, 3, 21–33.
2. Kumar, N.; Hussain, I.; Singh, B.; Panigrahi, B.K. Self-Adaptive Incremental Conductance Algorithm for
Swift and Ripple-Free Maximum Power Harvesting from PV Array. IEEE Trans. Ind. Inform. 2018, 14,
2031–2041.
3. Thangavelu, A.; Vairakannu, S.; Parvathyshankar, D. Linear Open Circuit Voltage-Variable
Step-Size-Incremental Conductance Strategy-Based Hybrid MPPT Controller for Remote Power
Applications. IET Power Electron. 2017, 10, 1363–1376.
4. Ariyur, K.; Krstic, M. Real-Time Optimization by Extremum-Seeking Control; Wiley: Howard, NY, USA, 2003.
5. Ghaffari, A.; Seshagiri, S.; Krstic, M. Control Engineering Practice Multivariable Maximum Power Point
Tracking for Photovoltaic Micro-Converters Using Extremum Seeking. Control Eng. Pract. 2015, 35, 83–91.
6. Ghaffari, A.; Krstic, M.; Seshagiri, S. Power Optimization for Photovoltaic Microconverters Using
Multivariable Newton-Based Extremum Seeking. IEEE Trans. Control Syst. Technol. 2014, 22, 2141–2149.
7. Barth, C.; Pilawa-Podgurski, R.C.N. Dithering Digital Ripple Correlation Control for Photovoltaic
Maximum Power Point Tracking. IEEE Trans. Power Electron. 2015, 30, 4548–4559.
8. Kimball, J.W.; Krein, P.T. Discrete-Time Ripple Correlation Control for Maximum Power Point Tracking.
IEEE Trans. Power Electron. 2008, 23, 2353–2362.
9. Bazzi, A.M.; Krein, P.T. Ripple Correlation Control: An Extremum Seeking Control Perspective for
Real-Time Optimization. IEEE Trans. Power Electron. 2014, 29, 988–995.
10. Hammami, M.; Grandi, G. A Single-Phase Multilevel PV Generation System with an Improved Ripple
Correlation Control. Energies 2017, 10, 2037.
11. Hammami, M.; Grandi, G.; Rudan, M. RCC-MPPT Algorithms for Single-Phase PV Systems in Case of
Multiple DC Harmonics. In Procedding of the 6th International Conference on Clean Electrical Power
(ICCEP), Santa Margherita Ligure, Italy, 27–29 June 2017.
12. Casadei, D.; Grandi, G.; Rossi, C. Single-Phase Single-Stage Photovoltaic Generation System Based on a
Ripple Correlation Control Maximum Power Point Tracking. IEEE Trans. Energy Convers. 2006, 21,
562–568.
13. Hammami, M.; Grandi, G.; Rudan, M. An Improved MPPT Algorithm Based on Hybrid RCC Scheme for
Single-Phase PV Systems. In Proceedings of the 42nd Annual Conference of the IEEE Industrial Electronics
Society (IECON), Florence, Italy, 23–26 October 2016.
14. Esram, T.; Kimball, J.W.; Krein, P.T.; Chapman, P.L.; Midya, P. Dynamic Maximum Power Point Tracking
of Photovoltaic Arrays Using Ripple Correlation Control. IEEE Trans. Power Electron. 2006, 21, 1282–1290.
15. Elnosh, A.; Khadkikar, V.; Xiao, W.; James, L. An Improved Extremum—Seeking Based MPPT for
Electronics 2019, 8, 118 15 of 15
Grid—Connected PV Systems with Partial Shading. In Proceeding of the 2014 IEEE 23rd International
Symposium on Industrial Electronics (ISIE), Istanbul, Turkey, 1–4 June 2014.
16. Yuan, X.; Stemmler, H.; Barbi, I. Self-Balancing of the Clamping-Capacitor-Voltages in the Multilevel
Capacitor-Clamping-Inverter under Sub-Harmonic PWM Modulation. IEEE Trans. Power Electron. 2001,
16, 256–263.
17. Babaei, E.; Laali, S.; Bayat, Z. A Single-Phase Cascaded Multilevel Inverter Based on a New Basic Unit with
Reduced Number of Power Switches. IEEE Trans. Ind. Electron. 2015, 62, 922–929.
18. Buticchi, G.; Barater, D.; Lorenzani, E.; Concari, C.; Franceschini, G. A Nine-Level Grid-Connected
Converter Topology for Single-Phase Transformerless PV Systems. IEEE Trans. Ind. Electron. 2014, 61,
3951–3960.
19. Rahim, N.A.; Selvaraj, J. Multistring Five-Level Inverter with Novel PWM Control Scheme for PV
Application. IEEE Trans. Ind. Electron. 2010, 57, 2111–2123.
20. Hammami, M.; Rizzoli, G.; Mandrioli, R.; Grandi, G. Capacitors Voltage Switching Ripple in Three-Phase
Three-Level Neutral Point Clamped Inverters With. Energies 2018, 11, 3244.
21. Hammami, M.; Vujacic, M.; Grandi, G. Dc-Link Current and Voltage Ripple Harmonics in Three-Phase
Three-Level Flying Capacitor Inverters with Sinusoidal Carrier-Based PWM. In Proceedings of the 19th
International Conference on Imdustrial Technology (ICIT), Lyon, France, 20–22 February 2018.
22. Nabae, A.; Takahashi, I.; Akagi, H. A New Neutral-Point-Clamped PWM Inverter. IEEE Trans. Ind. Appl.
1981, IA-17, 518–523.
23. Margaliot, M.; Ruderman, A.; Reznikov, B. Mathematical Analysis of a Flying Capacitor Converter : A
Sampled- Data Modeling Approach. Int. J. Circuit Therory Appl. 2013, 41, 682–700.
24. Ibrayeva, A.; Ten, V.; Familiant, Y.L.; Ruderman, A. PWM Strategy for Improved Natural Balancing of a
Four-Level H-Bridge Flying Capacitor Converter. In Proceedings of the Aegean Conference on Electrical
Machines and Power Electroonics (ACEMP), Side, Turkey, 2–4 September 2015.
25. Thielemans, S.; Ruderman, A.; Reznikov, B. Improved Natural Balancing With Modified Phase-Shifted
PWM for Single-Leg Five-Level Flying-Capacitor Converters. IEEE Trans. Power Electron. 2012, 27,
1658–1667.
© 2019 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access
article distributed under the terms and conditions of the Creative Commons Attribution
(CC BY) license (http://creativecommons.org/licenses/by/4.0/).