Strategies in Architecture: Radiant Cooling Systems
Transcript of Strategies in Architecture: Radiant Cooling Systems
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 1
Radiant Cooling Systems: Comfort Distribution Strategies in Architecture
By William A. Womeldorf, Department of Building
Construction Technology at Umass Amherst
Introduction
Mechanical distribution systems for heating and cooling are always evolving and reiterating to achieve a greater efficiency
and a superior form of comfort. The history of cooling in buildings is a relatively new attainment when compared to that of
heating. This paper will discuss in more detail on the current methods used and will tackle the question of radiant cooling
panels in buildings. These systems pose many caveats, especially in residential uses, but do the advantages of this
innovative system out way the disadvantages? More detail will be discussed on the main types of radiant cooling and
which situations where these should and should not be used as a cooling distribution system.
The Fundamentals of Cooling
To effectively understand cooling in a building, one must
comprehend the fundamentals of heat. Foremost, there
are two main forms of heat flow: Sensible heat and latent
heat. Sensible heat is form of energy that can be
measured with a thermometer. It is associated with a
change in temperature of a substance, material or space. [2]
Latent heat results from a release or storage of heat
associated with a change in the phase of the substance
(i.e. Gas to a liquid). Total heat flow is the sum of
sensible and latent flows. The moisture in humid air
holds energy as latent heat so that is why it may feel
hotter than the expressed temperature. Human comfort in
buildings requires careful attention to both of these heat
flows. The study of the psychometric chart explains the
relationship between temperature and humidity and
where maximum comfort is achieved. This is paramount
when designing a comfort distribution system in a
building.
The transfer of sensible heat has three cardinal methods:
Conduction, Convection and Radiation.
Conduction is the transfer of heat between substances
(solids mostly) when they are in direct relationship with
each other. [1]
Some materials conduct heat better, while
others like insulation slow the conduction of heat.
Conduction in a building typically occurs in a building’s
envelope. Heated conditioned air in the winter is
conducting through a wall assembly to the outside, while
in the summer conduction is moving heat into the
building from the outside by the same process.
Convection is the natural movement of heat through a gas
Figure 1 – A psychometric chart can be used to show humidity and
temperature and where ideal comfort can be found. Note that the
comfort zone is a range as humans experience comfort differently. [3]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 2
or liquid by changes in density. As a gas or liquid is
heated, it warms, expands and rises because it is less
dense. [2]
Convection takes place in architecture as a
result of wind or pressure-driven air movement.
Radiation, the last of the three main methods of heat
transfer, occurs when electromagnetic waves travel
through space. This mostly occurs in a building by the
sun in which a space can be heated by direct radiation,
diffuse radiation or by reflected radiation. When these
electromagnetic waves hit an object, they transfer their
heat to that object by the form of radiation. [2]
These three
transfer methods, when understood, give the designer of
the building greater insights when designing a cooling
system in a building.
Air, water or both are the most common mediums used
as methods of transferring heat in a building. It is
important to understand the thermal properties of these
substances to best grasp which comfort delivery systems
are right for the building’s usage. Specific heat is the
amount of heat per unit of mass to raise the temperature
by one degree Celsius. [5]
Water has much higher specific
heat
content than air so less water is needed to store or
transfer heat. This is because water is much denser than
air allowing it to hold and channel more energy per unit
volume. The relationship is a big difference in which it
requires far greater amounts of air to transfer the same
amount of heat as water. That being said, there are some
obvious benefits of using air, like for ventilation and the
quick rapidity of comfort to a space.
“Is supplying chilled water to a room causing
the room to cool by delivering a process akin
to heating but with a “cooling” property?”
An understanding of the concepts of heat flow in a space
and heat sinks are needed to understand how certain
cooling distribution systems are better than others in
certain situations. Heat flows from a higher temperature
but not necessarily from an area of more heat to less heat.
Temperature, not heat content, determines heat flow in a
building. [4]
When studying how a room is heated it is
easy to take note on why water or air with higher heat
content is moved into the conditioned space to raise the
room’s temperature. However, it is much less intuitive to
understand the cooling process in a space. Is supplying
chilled water to a room causing the room to cool by
delivering a process akin to heating but with a “cooling”
property? The answer is no, because instead the chilled
water is absorbing the heat in the space by acting as a
heat sink. A heat sink is a term used to describe a
material or space used to store the heat exited from a
conditioned space. Sometimes the heat sink is in the form
of a cooling tower. Generally, when cooling is occurring
in a building, what is actually happening is the warm air
is being removed by an air conditioning mechanical
system and is being exited from the building in the form
of a heat sink process. In areas where it gets much cooler
Figure 2 – The three main ways heat transfers in a building is by conduction, convection and radiation (respectfully shown, left to right). [3]
Figure 3 – One cubic foot of water can store or
transfer the same amount of heat as over 3000
ft3of air. [4]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 3
at night, the outside air can be used instead as a heat sink
to relieve some of the hot indoor air. A cooling delivery
system utilizes heat sinks to condition the air and provide
comfort for the building’s users.
Mean radiant temperature (or MRT) describes the
radiant environment for a point in space. [4]
It is an
important metric when comparing a radiant dominated
distribution system to other more direct systems. To
determine how much radiant heat or cooling a human in a
building will experience from a specific point the
designer should be aware of both the temperature and the
exposure angle of all objects in question. [4]
A toe-kick
heater produces a high amount of heat but because it has
a lower angle of exposure the body experiences a lower
MRT. Walking towards the toe-kick heater will result in
an increased MRT because the exposure angle would
increase. A different example is that of a window on a
cold winter day, in which the window produces a lower
mean radiant temperature causing the human to
experience what would feel like a cold draft, especially
once the human approaches it. This is important because
in regards towards radiant ceiling panels, the temperature
of the conditioned water can be lower (for warming) or
higher (for cooling) than that of a more direct source
because its large covering on the ceiling will result in a
higher exposure angle, resulting in an adjusted MRT.
Traditional Cooling Systems
There are many ways to remove heat from a room. These
cooling systems all use a refrigeration machine, heat
rejection equipment and a heat sink to move heat from a
building. The big difference between the cooling systems
is how heat is transferred from the conditioned space to
the refrigeration machine. There are all-air systems that
pumps the room’s heat into a refrigeration machine and
then rejects the waste heat to a heat sink (either a
evaporative condenser or a cooling tower. The main
advantages of air cooling systems are that they can vent,
filter and dehumidify the air in a room. However, their
disadvantages include the large fan power needed in the
air handler unit and the massive space allocated to ducts
for the distribution on the supply air and return air in a
building. Another method of cooling a space is that of the
all-water systems in which water is chilled by mechanical
equipment like an evaporator coil and then delivered to
fan-coil units in each space. An advantage with this
system is that the pump requires much less energy than
the fans. However, the drawback of this system is that
venting and filtering of the air is often tough especially if
a room does not have any windows. A compromise can
be obtained when combination air-water systems are
used. A radiant cooling panel with supplementary air is
one of these systems. It uses water as the primary heat
convector and then utilizes a supplementary air system
(like a heat recovery ventilator) to control the ventilation
and humidity in the air.
“The big difference between all the cooling
systems is the process on how heat is
transferred from the conditioned space to the
refrigeration machine.”
Radiant vs Conventional Cooling
With climate change becoming a larger issue in the built
environment, the efficiency and effectiveness of HVAC
systems are being held to increased scrutiny. At peak
demand (during hot summer days when cooling in
building is almost unanimously needed) the conventional
HVAC system uses about 37.5% of its power on tasks
like the fan and motor for air distribution.[6]
The reminder
of the loads is accounted for by the chiller and
compressor units. The Department of Energy has stated
that, at peak load, a building uses about 10% to 20% of
the supply air as outside air. [6]
It is important to note that
only a fraction of this supply air is needed to properly
ventilate a building and maintain excellent air quality
levels. This realization is causing a lot of research in
developing new innovative technology involving
hydronic radiant systems which require less circulated air
and less wasted energy from fans and motors. The
radiation system provides it’s cooling by using water as
Figure 4 – The mean radiant temperature (MRT) is a metric used
in determining observed comfort. It is a relationship between the
surface temperature and the angle of exposure. [4]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 4
the transport medium for removing heat from the
conditioned space. As discussed earlier, water has a
much higher heat carrying capacity allowing for
increased efficiency over all-air systems. A study done
by the Lawrence Berkeley National Laboratory has
shown a 42.3% increase in efficiency over a conventional
HVAC system during peak power times. Also noted in
the article is that the separation of cooling and ventilation
tasks not only improves comfort conditions, it also
improves indoor air quality as well as control and zoning
of the system. [6]
“This realization is causing a lot of new
research in developing innovative technology
involving hydronic radiant systems which
require less circulated air and less wasted
energy from fans.”
Additional benefits can occur when the area of the panels
is large enough for the mean radiation temperature to
decrease enough to where moderately cool panels (about
65 degrees) will suffice. [5]
This saves additional energy
by allowing less energy-intensive cooling to occur to
achieve the same level of comfort in the conditioned
spaces. When combined with sustainable primary
systems like geo-exchange heat pumps the total
efficiency of the cooling system can skyrocket from the
use of semi-cooled ground water (around 58-60 degrees)
in a closed or open loop exchange system. In addition,
using heat pumps with high coefficient-of-performance
(COP) values, night cooling, economizers or some
variation of these will allow for even further diminishing
energy costs.
A possible disadvantage can occur by condensation and
even indoor rain from the ceiling. This occurs from the
temperature falling below the dew point. A way to
prevent this problem is by having indoor humidity
controls and monitoring devices to make sure the
humidity is above the dew-point temperature of the air.
This is why it is critical to use a supplementary air
system for ventilation and humidity controls for when
they are needed. A second noteworthy disadvantage
occurs when there are too many occupants in the space
than it was designed for. The sizing of the system is
critical because the more people that are in a space the
more heat that will be given off. If this is a rather sudden
event then the heat removal of the radiant cooling will be
not enough to properly condition a space. A solution to
this problem is to avoid using this cooling system for
auditoriums or gathering spaces and focus on utilizing it
for more predictable usage spaces like offices.
Hydronic radiant cooling has an additional benefit of
requiring less space for HVAC than conventional all-air
duct based systems. This saves in additional space for the
building’s main use which could be substantial when
considering ductwork consists of about 6% to 9% of the
building in a typical conventional HVAC system. [4]
In
addition, money can be saved from not investing in
costly duct and air handling systems. Radiant cooling
systems save energy when compared to the amount of
leakage that occurs with typical all-air systems.
Radiant cooling systems are not all the same. There are
three main types of radiant cooling panels: concrete core
system, suspended ceiling panel system and the capillary
tube system. [4]
Cost, retrofitting conditions, location,
climate and building usage should be considered when
selecting the ideal system.
Concrete Core Systems
This system consists of a series of hydronic tubes
(usually oxygen barrier PEX) inside of a concrete slab.
The concrete core system is the cooling version of the
radiant slab heating method. However, it is often used in
ceiling scenarios because of the natural direction of heat
flow. In this layout, the concrete slab can be useful for its
thermal storage capabilities in consonance with the water
flowing in the tubes. The time lag effect can provide
great benefits in both summer and winter if used
correctly. The total building costs with a radiant concrete
core system have been proven to be around equal to that
Figure 5 – A comparison done by Lawrence Berkeley National
Laboratory on conventional HVAC vs Radiant cooling HVAC
systems during electrical peak power demand. [6]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 5
of a conventional building approach with a conventional
all-air HVAC system. Some of the other advantages with
using a concrete core system include [7]
:
- High energy efficiency
- Integrated into building structure (not visible)
- Low maintenance
- Can install large areas at low capital costs
- Silent operation
- Very long operational life
- Provides stable space comfort conditions
Disadvantages of a concrete core system include [7]
:
- Harder to model temperatures in design phase
- Requires detailed coordination between architect,
mechanical engineer and structural engineer.
(Requires an integrated design team)
- Severe fire or seismic event will render the
system inoperable, with extensive repairs needed
- Aesthetical issues of having exposed slab finish
It is important to note that this concrete core system
among other radiant cooling systems requires that the
cooling system be kept at the ceiling. There is a great
decrease in effectiveness when it is used for floor
applications. [7]
Suspended Ceiling Panel System
This method is the most common and is built primarily
by a suspended ceiling consisting of a highly conductive
material like aluminum, however, other materials are
increasing in popularity. Above the panels lay the metal
tubes connected to the rear of the panel. The highly
conductive material allows for a fast response time to
changes in the room usage loads. This system is used in
tandem with many others to produce a highly efficient
cooling load in the space. It is perhaps more aesthetically
pleasing than having a concrete slab as a ceiling finish.
Also, if there ever is a problem with one of the panels, it
is far easier to remove one of them and make
replacements as necessary. Costs are also around the
same as the typical VAV (variable-air-volume) systems
but with additional lifelong energy savings. [8]
The users
of the building also get the pleasure of enjoying the
increased comfort with the minimal noise compared to
that of an all-air system. The most valid reason to use this
system as opposed to the concrete core system is its
ability to retrofit into an existing space. This allows for
many more applications of this method for the
marketplace.
Capillary Tube System
The final system discussed involves using cooling grids
made of capillary tubes placed close to each other. This
system is done by embedding the tubes in plaster or
gypsum board. [4]
Usually the system is done with a
backer board (or rigid insulation) on the underside of a
ceiling joist. This is different than the concrete core
system because there is no thermal mass involved and the
Figure 6 – The Concrete Core System is a type of radiant cooling
that can double as a structural support while providing cooling to a
space. [6]
Figure 7 – A Suspended Ceiling Panel radiant cooling system
being used in an office setting [8]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 6
tube system is closer to the interior finish side. This
system provides temperature distribution to be evenly
spread around the ceiling of a space. An advantage of
this over other all-air systems is that there is less of a
need to ensure that there is not blockage in the
convection loop because with an increased surface area
virtually all areas of the space will experience an equal
level of cooling throughout. In addition, due to the tube’s
flexibility, the cooling grids can be effective decision in
retrofit scenarios where ceiling height may not allow for
a suspended ceiling panel system. While some
applications of this system have been used to cover the
walls, it is not needed as most of the cooling effect will
occur on the ceiling. Another consideration when using
capillary tubes in lower areas like on the wall or floor is
that the cooling effect is often less desirable on the lower
side of the body than it is at the head. This logic is
opposite of the conventional wisdom used when radiant
floor heating is used (in which, heating from the floor
makes greater sense). Location for the radiant cooling
system increased effectiveness when it is not obstructed
by furniture items and can also cool from convection. [4]
Due to the massive surface area of the system,
conditioned water can be kept at a much higher
temperature than it would be for a direct all-water system
like that of a fan-coil. This utilizes less energy, allowing
for more sustainable, yet effective buildings.
Dedicated Outdoor Air System
As mentioned earlier, all radiant cooling systems operate
best when they are combined with outside air for
ventilation and humidity controls. These ventilation
systems are also required by international building code
to meet a requirement for supply quantities for
introduced outdoor air. When combined with a heat
recovery ventilator, conditioned temperature can be
preserved at a much high efficiency while still
maintaining ventilation to the space. A dedicated outdoor
air system (DOAS) consists of two parallel systems: A
dedicated outdoor air ventilation system that handles
latent loads (fresh air) and a parallel system that handles
sensible loads (dehumidifying). [11]
A dedicated outdoor
air system uses minimum energy because it is often not
conditioning the air nor is there a lot of duct work
associated with it. However, in applications on internally
dominated buildings it can be comparable to a VAV
system with ducts reaching into the inner spaces.
A heat recovery ventilator is used to preserve the
temperature of the room while still allowing for new
outdoor air to enter the space. This system can reserve in
the summer and winter months and is used when code
requires a space to be mechanically vented. This system
should be used with radiant cooling systems to provide
fresh air in the building.
Figure 8 – A Capillary Tube System being installed before the
finishing of the plaster. Notice how close the tubes are placed to
each other. [8]
Figure 9 – A Dedicated Outdoor Air System (DOAS) is often used
with a radiant cooling system for ventilation and improved air
quality. Pictured above is a heat recovery ventilator (HRV) which is
used to conserve the temperature of the building while allowing for
supply air to enter [12]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 7
A Side-by-Side Comparison
Infosys in Hyderabad, India is the first commercial
radiant cooled building in the country. The building is
among others on larger campus and is known for being
50% more efficient than any other building at Infosys. [13]
The reason this is such a fascinating case study is the
building is split into two symmetric halves. While one
half is cooled by a conventional VAV all-air conditioning
system the other half utilizes a concrete core radiant
cooling system. The area, location, envelope design,
orientation, lighting and number of occupants remain
constant for each side of the building allowing for an
ideal demonstration of the efficiency of radiant cooling
over VAV air conditioning. The building was awarded
LEED India “Platinum” rating by the Indian Green
Building Council. [13]
The building is world renowned for
being a high performance green building.
ASHRAE Journal in 2014 published in a feature on VAV
vs Radiant how the radiant cooling system allowed
architects and engineers to achieve such a high efficiency
with the method they used. Radiant cooling data showed
after two years a 34% reduction in operational costs
when compared to the VAV building. Along with other
remarkable advantages of a better comfort delivery
system and the best part, it was actually less expensive to
build then the underperforming VAV system. [14]
The
building was outfitted with many measuring devices
allowing building scientists a field day of data to study.
The building also utilizes a DOAS (Dedicated outdoor air
system) on the side of the building with radiant cooling.
This was to ensure that fresh air and humidity were
controlled in the space to facilitate a better indoor
environment and prevent indoor rain from occurring on
the radiant system. The designers combined this with a
energy recovery wheel to prevent the conditioned
temperature from being lost from the space. Another
aspect to the interior design was ceiling fans were used to
facilitate the cooling effects from the radiant panels
which can create a convection loop.
Infosys decided to divide the building’s HVAC systems
in half because at the time in India a large scale radiant
cooling system was not used before and they wanted to
compare the results with that of a typical system. [14]
They
also wanted to hedge their decision in case it backfired in
a negative result.
This case study in Hyderabad, India has some
astonishing conclusions. Radiant cooling may not only
costs less to maintain, but more importantly it also
provides a greater level of comfort to the people in the
building. A potential downside could be if some disaster
inhibited the use of the radiant cooling in the slab
maintenance could reverse all pervious savings, but for
the location of the building that may prove unlikely. It is
vital that architects and engineers realize that the boiler
plate all-air systems are not the only option for providing
cooling to a space.
Discussion
This article is not for the promotion of radiant cooling. It
is an encouragement to designers of buildings to think
outside the box when it comes to decision on the HVAC
comfort delivery method. New innovative solutions can
elevate the efficiency and comfort of the building if the
option is on the table. Relying solely on traditional
methods when more advanced and effective methods
Figure 10 – The Infosys building featured above is split in two
halves. Left side uses a VAV all-air system while the right side uses
a radiant cooling system. [13]
Figure 11 – Annual electricity consumption of the VAV system and
the radiant cooling system. Note the 35% decrease in energy used. [14]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 8
exist is not moving in the right direction of progress. It is
paramount that designers focus on the advancement of
mankind and the idea that humans can reverse the causes
of climate change. The major player in this reversal
remains in the efficiency of the HVAC systems being
used in architecture.
The following list depicts the advantages of radiant
cooling over the conventional HVAC systems.
- Increased heat transfer when switching from
an air to water based system because of the stark
differences in thermal properties
- Decreased energy demands from removing the
fans, motors and air handlers of an all-air system
and switching to a more efficient hydronic heat
pump
- Moderately cool water will suffice because a
cool surface will achieve thermal comfort when
lowering the MRT. This benefit becomes
amplified when used on the ceiling and large
unobstructed coverings. Often chilled water can
be around 65 degrees as opposed to a much
lower temperature with fan-coil systems. This
allows for the use of geo-exchange heat pumps
and other systems to run more effectively with
not much additional energy required.
- Increased comfort when using a radiant cooling
system because typical all-air systems will
provide a dry, less comforting air than that of
radiant. While all-water systems often provide
more effective cooling comfort.
- Decreased heat loss from using hydronic lines
as opposed to using ducts and air handlers that
are more prone to leakage.
- Decreased capital costs when compared with
all-air systems because of the decreased need for
ductwork, expensive HVAC handlers and other
gadgets that go along with having a full scale air
system in a building. In addition maintenance of
these systems is less than that of other systems.
With that being said, there still are disadvantages when
using any all-water system. Radiant cooling is not alone
for many of those restrictions. The following are some
disadvantages when using radiant cooling systems and
some instances where they would not be recommended.
The following list depicts the disadvantages of radiant
cooling over the conventional HVAC systems.
- Not recommended in hot, humid climates because of the high humidity in the air, these
systems will not perform well at removing the
massive latently stored heat.
- A supplementary air system is often required
especially in internally dominated buildings with
no operable windows the dangers of stale
unventilated air will not be solved by using a
water-based system. Supplementary air will need
to be provided; however, often these systems like
the DOAS can provide clean air for a fraction of
the energy of a VAV or all-air system.
- Humidity concerns and indoor rain can occur
if the temperature reaches the dew point in which
condensation can occur on the bottom of panel
radiant systems. For this reason it is appropriate
that the space have a humidity control and
monitoring system to ensure the occupants don’t
need a rain coat indoors.
- Coordination required between architects,
mechanical and structural engineers to ensure
that the system is properly built. This is
especially true when using a concrete core
system because the HVAC equipment doubles as
the structural floor system of the building as
well. An integrated design strategy will be
required in these applications.
- Loss of effectiveness when occupants load rapidly increase because of the gradual cooling
of the space when there is a sudden change in
loads the cooling system will need to take more
time to remove the heat of additional unplanned
occupants. This makes this system less useful for
unpredictable changes in room use.
In conculsion, the use of innovated radiant cooling
systems can provide an asset to the building when used in
accordance with its depicted advanatges and for the
betterment of comfort delivery in architecture.
Figure 12 – Radiant
cooling on the ceiling can
provide a decreased MRT
allowing for more energy
efficiency. [4]
UMass BCT 597SD (2015) - “Solar Energy Systems and Building Design” - Page 9
References
1: Sadik Kakaç, and Yaman Yener. Convective Heat
Transfer. 3rd ed. Vol. 1. Boca Raton, FL: CRC, 2014.
Print.
2: "Heat Energy Flows in Buildings | Sustainability
Workshop." Sustainability Workshop. Autodesk, n.d.
Web. 04 Oct. 2015.
3: "Psychrometric Charts | Sustainability Workshop."
Sustainability Workshop. Autodesk, n.d. Web. 04 Oct.
2015.
4: Lechner, Norbert. Heating, Cooling, Lighting.
Sustainable Design Methods for Architects. 3rd ed.
Hoboken, NJ: John Wiley & Sons, 2009. Print.
5: "Specific Heat." Hyperphysics.phy-astr.gsu.edu. N.p.,
n.d. Web. 04 Oct. 2015.
6: Feustel, Helmut. "Re: Hydronic Radiant Cooling
Systems." Weblog comment. CBS Newsletter. Indoor
Environment Program, 1994. Web. 04 Oct. 2015.
7: McDonell, Geoff, LEED AP. "Selecting Radiant
Ceiling Cooling and Heating Systems." Plant
Engineering. N.p., 2007. Web. 04 Oct. 2015.
8: Drake, Lawrence. "Radiant Cooling." Energy Design
Resources. Radiant Panel Association, n.d. Web. 4 Oct.
2015.
9: "Energy Design: Thermal Comfort in the Home." The
Challenge Series. N.p., n.d. Web. 04 Oct. 2015.
10: "Radiant Cooling." Energy.gov. United States
Goverment, n.d. Web. 04 Oct. 2015.
11: "Dedicated Outdoor Air Systems." Wikipedia. N.p.,
n.d. Web. 04 Oct. 2015.
12: "Radiant Cooling Systems." Energy Efficiency
Emerging Technologies Database. Washington State
University: Extension Energy Program, n.d. Web. 4 Oct.
2015.
13: "News." Hyderabad Radiant Cooling Building.
Infosys, n.d. Web. 04 Oct. 2015.
14: Sastry, Guruprakash, and Peter Rumsey. "VAV vs
Radiant Side-by-Side Comparison." ASHRAE Journal.
ASHRAE, May 2014. Web. 04 Oct. 2015.