High Voltage Experiments
-
Upload
independent -
Category
Documents
-
view
0 -
download
0
Transcript of High Voltage Experiments
Lab ReportHigh Voltage Engineering
WAPDA Engineering Academy Faisalabad
Submitted To : Sir Rizwan-ul-Hasan
Submitted By : Muhammad Gulraiz Ahmed
Roll No : 10-EL-15
NFC Institute Of Engineering & Fertilizer
Lab Assignment No : 01 Objective:
“Determination of an ac flash over of a 11kv pin type
insulator under dry conditions.”
Apparatus:
11kv pin type insulator,
connecting cup,
current limiting resisitor,
coaxial cable,
measuring capacitor
Theory:
It is one of the earliest designs used for supporting lineconductor. The pin insulator is supported on the forged steelpins and bolds, whichare skewed to the crosssection of thissupporting structure.The conductor is lied toinsulator on thegrooves. In order toincrease the leakagepath, one, two or three rain shades are so designed when theseinsulators are wet even then sufficient dry space is providedby the inner shades.For higher voltages the thickness of the material required forthe purpose of the insulation. But the practical way is to usemore than one insulator unit instead of increasing thethickness.
Flashover distances when the insulators are dry and wet aredifferent. The flash over voltage when the insulator is wet isless. The rain shades should not disturb the voltagedistribution. They are so designed that their surface is rightangle to electrostatic lines of forces or they must try to liein the equipotential.The pin type insulator is reliable for voltage level upto 50KVmax. and They are never used for voltage beyond 80 KV. Sincethe suspension insulator is more reliable and cheaper. Themodern practice is “not to used” the pin type insulator beyond33KV.
There are three types of loads that may be occur on insulator.1- Mechanical loading2- Thermal loading3- Electrical loading
Mechanical loading contains conducting weight, wind storms,snow fall (ice) and birds etc.Thermal loading is due to atmospheric tensionWhile electrical loading is caused by normal operating voltageI.e. 11 KV, 33KV ------(H.T dist) and 400V, 230V---- ( L.TDist ). It also contains overvoltage for short duration, and transientdue to lightening, switching, steady state overvoltage (due tophase to ground fault).
Connection diagram:
220/100kv
10 m ohm resistance
100 pf capacitor
Procedure:
Connected the circuit as shown in the circuit diagram.
Starting from the 50% of the ac test voltage, required
according to the wapda specification.
The voltage is raised to the test voltage within
approximately 10 seconds.ac test voltage is applied for
one minute, the voltage is raised until the flashover
occurs.
The flash over value shall be determined as the mean
value of 3 individual measurements.
Observations:
Serial # Flashover voltage (v)1 902 903 89
Mean flashover voltage=89.6 v
Precautions :
Insulator under test must be cleaned carefully.
All parts which are grounded under normal service
conditions must be grounded for the test also.
Equivalent linear conductor is to be attached to the
insulator.
Conclusion:
When a disruptive charge take place between two electrodes in
a gas or liquid or over a surface of solid insulation it is
called a flashover. insulation flashover is the discharge
through the air taking the form of an arc or a spark or of
several arcs or sparks between conducting part of an insulator
under the application of high voltage which normally having
the operating voltage between them.
What is the objective of performing ac flashover voltage
test under dry conditions?
In order to check the maximum operating voltage which an
insulator can bear and if that voltage is below or above the
standard voltage which are specified by the wapda.so that when
they operate in dry environment they can bear the voltage for
a specific limit.
Compare your reading with the wapda standard readings?
We uses pin type insulator for this test and standard voltage
set by the wapda for pin type insulator under dry condition is
70kv.our mean value of flashover voltages comes out to be 89.6
so as the value is greater than that set by wapda so insulator
we uses met the standard set by the wapda.if the means value
comes out to be less than 70kv then that insulator does not
met wapda standard specification and thus can not be use in
the field.
______________________________________________________________
_____________
Lab Assignment No : 02
Objective:
“To determine the AC flashover voltage of 11 KV Pin type
insulation under Wet condition.”
Apparatus:
HV control disk
Test Transformer
Current limiting resistor
Flexible conductor cable
Measuring capacitor
Connecting cup
Coaxial cable
11 KV pin type Insulator
Theory: It is one of the earliest designs used for supporting line
conductor. The pin
insulator is
supported on the
forged steel pins and
bolds, which are
skewed to the cross
section of this
supporting structure.
The conductor is lied to insulator on the grooves. In order to
increase the leakage path, one, two or three rain shades are
so designed when these insulators are wet even then sufficient
dry space is provided by the inner shades.
For higher voltages the thickness of the material required for
the purpose of the insulation. But the practical way is to use
more than one insulator unit instead of increasing the
thickness.
Flashover distances when the insulators are dry and wet are
different. The flash over voltage when the insulator is wet is
less. The rain shades should not disturb the voltage
distribution. They are so designed that their surface is right
angle to electrostatic lines of forces or they must try to lie
in the equipotential.
The pin type insulator is reliable for voltage level upto 50KV
max. and They are never used for voltage beyond 80 KV. Since
the suspension insulator is more reliable and cheaper. The
modern practice is “not to used” the pin type insulator beyond
33KV.
There are three types of loads that may be occur on insulator.
4- Mechanical loading
5- Thermal loading
6- Electrical loading
Mechanical loading contains conducting weight, wind storms,
snow fall (ice) and birds etc.
Thermal loading is due to atmospheric tension
While electrical loading is caused by normal operating voltage
I.e. 11 KV, 33KV ------(H.T dist) and 400V, 230V---- ( L.T
Dist ).
It also contains overvoltage for short duration, and transient
due to lightening, switching, steady state overvoltage (due to
phase to ground fault).
Circuit connection:
Procedure: Connect the components as shown in the diagram.
Insulator is objected to artificial raining condition .
It is subjected to a spray of water with the help of
nozzle which are so arranged that the water drops fall
approximately at the inclination of 45 degree with the
vertical. The spray of water on the insulator should
begin atleast one min before the voltage application and
should be continue all throughout the test.
Starting from 50% points of the AC test voltage required
according to WAPDA specification.
The voltage is raised to test voltage within 10 sec approx,
the AC test voltage is applied atleast for 1 minute. The
voltage is quickly raised until a flashover occur. The
flashover value shall be determine as the mean value of three
individual measurement.
Observations:
S.NO FLASHOVER VOLTAGE (wet
condition) PIN type
1 40 KV
2 42 KV
3 46 KV
Mean 42.66 KV
Wapda specification:
S.NO TYPE OF
INSULATOR
FLASHOVER VOLTAGE (WET)
1 PIN 40 KV --- H.T Running
2 DISC 50 KV --- H.T Dead line, angle
position
3 SPOOL (D-SHACKLE 15 KV --- L.T Running
4 STRAIN 18 KV --- L.T Guying wire
Precautions:
The insulator under test must be cleaned carefully.
All the parts which are grounded under normal service
condition must be grounded for test also.
Equivalent line conductor is to be attached to the
insulator.
Conclusions:
Why insulator flashes over at lower voltage under wet
conditions?
Since the flash over occurs when air breakdown take place
and also ionization becomes occur between connecting
parts of an insulator so it totally depends on dielectric
strength . At normal condition the dry air dielectric
strength is 2.1kv/cm but in wet conditions the dielectric
strength becomes low and ionization take place at low
voltage. Also air breakdown take place at low voltage so
insulator flash over at low voltage.
Compare your result with WAPDA’S standard specifications
under wet conditions?
Wapda standard specification:
And results taken during the lab
S.NO FLASHOVER VOLTAGE (wet condition) PINtype
1 40 KV
S.NO Type Wet condition
1. Pin type 40kv
2. Disc type 50kv
3. Spool type 15kv
4. Strain type 18kv
2 42 KV
3 46 KV
Mean 42.66 KV
Pin type insulator flashover at 40 KV under wet conditions while from observations it is clear that flashover occurs at 40 KV,42 KV,46 KV and their mean is 40.66 KV. So it is far good and meet the WAPDA standard specifications.
___________________________________________________________________________
Lab Assignment No : 03 Objective:
“ One minute power frequency withstand voltage
test.”
Apparatus:
11kv pin type insulator,
connecting cup,
current limiting resisitor,
coaxial cable,
measuring capacitor
Circuit diagram:
Procedure:
Connect the component as shown in the figure.
starting from 50 percent ac test voltage required
according to wapda specification, the voltage is raised
to the test voltage within approximately 10 seconds, the
ac test voltage is applied at least for one minute
Observation: Wapda specifications:
Pin type 65kv
Disc type 75kv
Spool type 23kv
Strain type 32kv
Resulst in the lab:
Pin type Voltage kv
1 64
2 62
3 64
Mean value=63.33kv
Precautions: The insulator under test must be cleaned carefully.
All the parts which are grounded under normal service
condition must be grounded for test also.
Equivalent line conductor is to be attached to the
insulator.
Conclusion: Q: What is the object of performing this test?
The main objective of this test is to measure the
dielectric strength of insulator.
Q: What do you under stand by one minute power frequency test?
At power frequency of 50 hertz this test is perform to
check the dielectric strength of the insulating material
under the specific condition.
Q: Define following?
Time lag for break down:
This is the time difference between the application of a
voltage sufficient to cause and occurrence of a breakdown
itself.
Statistical time lag:
The time which elapses between the application of voltage
sufficient to cause breakdown and the appearance of
initiating electron
Formative time lag:
After the appearance of initiating electrons a time is
required for ionization processes to develop fully to
cause the breakdown of the gap and this time is called
formative time lag
Total time lag:
The breakdown of the gap will take place after a time
(ts+tf) from the instant of application of breakdown
voltage.
Crona discharge:
Partially ionized air around the conductor accompanied by
hising noise and bluish glow.
______________________________________________________________
_____________
Lab Assignment No : 04 Objective:
“One minute power frequency withstand voltage
test of pin type insulator under wet conditions.”
Apparatus:
11kv pin type insulator,
connecting cup,
current limiting resisitor,
coaxial cable,
measuring capacitor
Circuit diagram:
Procedure: Connect the component as shown in the figure.
The insulator shall be exposed for 5 minutes before the
application of voltage throughout test to artificial rain
with following characteristics. rainfall intensity 3mm
per min, tolerance plus minus 10 percent, direction above
45 degree to vertical, water resistivity 10000 ohm
centimeter, water temperature not differing more than 10
percent from that insulator.
Observation: Wapda specifications:
Pin type 35kv
Disc type 45kv
Spool type 13kv
Strain type 10kv
Resulst in the lab:
Pin type Voltage kv
1 36
2 37
3 35
Mean value=36kv
Precautions: The insulator under test must be cleaned carefully.
All the parts which are grounded under normal service
condition must be grounded for test also.
Equivalent line conductor is to be attached to the
insulator.
Conclusion: Q: What is the object of performing this test?
The main objective of this test is to measure the
dielectric strength of insulator under wet conditions.
Q: Define townsends first and second ionization coefficients?
Average no of ionizing collisions made by an electron per cm
travel in the direction of field is the townsends first
ionization coefficient. Townsends second ionization
coefficient can be define as the net yields of electrons due
to secondary process
Q: Secondary ionization processes?
Are those processes by which secondary electrons are produced,
which sustain a charge after it is established due to
ionization by collision and photo ionization following are the
secondary ionization process,
1) Electron emission due to positive ion impact
2) Electron emission due to photon
3) Electron emission due to metastables and neutral atoms
Q: is crona discharge take place during one minute power
factor with stand voltage test. Differentiate between crona
discharge and flash over (arc discharge)?
Yes crona crona discharge take place during one minute power
factor with stand voltage test.
Crona discharge:
Partially ionized air around the conductor accompanied by
hising noise and bluish glow
Flashover:
Electric discharge between two electrodes separated by
insulator.
______________________________________________________________
_____________
Lab Assignment No : 05 Objective:
“Voltage measurement through capacitor
divider.”
Apparatus:
Test transformer
Insulator
Resistance
Capacitor
Circuit diagram:
Procedure:
Connect the component as shown in the figure.
Observation: Wapda specifications:
Pin type 35kv
Disc type 45kv
Spool type 13kv
Strain type 10kv
Resulst in the lab:
Pin type Voltage kv
1 36
2 37
3 35
Mean value=36kv
Precautions:
The insulator under test must be cleaned carefully.
All the parts which are grounded under normal service
condition must be grounded for test also.
Equivalent line conductor is to be attached to the
insulator.
Conclusion: Q: What is the object of performing this test?
The main objective of this test is to measure the
dielectric strength of insulator under wet conditions.
Q: Define townsends first and second ionization coefficients?
Average no of ionizing collisions made by an electron per cm
travel in the direction of field is the townsends first
ionization coefficient. Townsends second ionization
coefficient can be define as the net yields of electrons due
to secondary process
Q: Secondary ionization processes?
Are those processes by which secondary electrons are produced,
which sustain a charge after it is established due to
ionization by collision and photo ionization following are the
secondary ionization process,
4) Electron emission due to positive ion impact
5) Electron emission due to photon
6) Electron emission due to metastables and neutral atoms
Q: is crona discharge take place during one minute power
factor with stand voltage test. Differentiate between crona
discharge and flash over (arc discharge)?
Yes crona crona discharge take place during one minute power
factor with stand voltage test.
Crona discharge:
Partially ionized air around the conductor accompanied by
hising noise and bluish glow
Flashover: