Grounding Transformers
-
Upload
khangminh22 -
Category
Documents
-
view
4 -
download
0
Transcript of Grounding Transformers
• It is used to provide a ground path on either an ungrounded Wye or a Delta connected system• The relatively low impedance path to ground maintains the system
neutral at ground potential
•Plot of transient over-voltage for an arcing ground fault
Arcing Ground FaultsIntermittent or Re-strike
Arcing Ground FaultsIntermittent or Re-strike
•Intermittent ground fault: A re-striking ground fault can create a high frequency oscillator (RLC circuit), independent of L and C values, causing high transient over-voltages.
– i.e. re-striking due to ac voltage waveform or loose wire caused by vibration
V V
480V Delta Source
3Ø Load
Cb bC
Rfe
faS
• It supports the voltage on a faulted phase– If a single line-to-ground fault occurs on an ungrounded or
isolated system, no return path exists and no current flows
– The system will continue to operate but the other two un-faulted lines will rise in in voltage by the square root of 3, possibly overstressing the transformer insulation, and other components, by 173%
A typical example is a Wind Farm. They utilize grounding transformers for fault protection on ungrounded lines
When a ground fault occurs on a collector cable causes the substation
circuit breaker to open, the wind turbine string becomes isolated
Turbines do not always detect the fault and the generators continue to energize the cable.
Voltages between the un-faulted cable and the ground rise by the 173%
The transformer, placed on the turbine string, provides the ground path
A typical example is a Wind Farm.
When the feeder breaker
Opens, the collector bus and
the step up transformer delta
connected MV windings
rely on the Grounding
Transformer for their ground
path and voltage support.
•What if no neutral exists (i.e. delta systems)?– A grounding transformer is installed (either a zig-zag or a wye-delta)
from all three phases to create an artificial neutral for grounding purposes only.
HRG
Broken Delta
Grounding
Transformers
Wye-Delta
Grounding
Transformers
HRGHRG
Zig-Zag
Grounding
Transformer
CØBØAØ AØ BØ CØAØ BØ CØ
• The zigzag transformer contains six coils on three cores. The first coil on each core is connected contrariwise to the second coil on the next core.
• The second coils are then all tied together to form the neutral and the phases are connected to the primary coils.
• Each phase, therefore, couples with each other phase and the voltages cancel out
Typical Wye connection with
Neutral end of windings connected
Together
A B C
Symmetrical three phase source
A B C
Vector diagram of
balanced system
A
B
C
C
B
A
b
c
aEach leg of the Zig-Zag
Connection is connected
to a winding from another which
is out of phase
B
C
A
c
b
a
Cz
Az
Bz
The resulting Zig-Zag connection
Is phase shifted with respect to the
incoming three phase source
• Limits circulation of triplen harmonics
( 3 rd, 6th, 9th, etc)
• Can be used without a Delta connected or 5-legged core
• Elimination of secondary winding results in smaller footprint, lower cost (25-30%)
• Includes a Delta or Wye connected secondary
• Utilizes 4 or 5 legged core when Wye connected secondary is specified
• Multi-functional, provides benefit of auxiliary power
• Primary Voltage
• Phase to Phase continuous primary current (or Rated kVA)
• Continuous Neutral current
• Available Fault Current and Duration
• Impedance as a % or as an ohms/phase value
• Primary Winding connection
• Secondary connection
• Basic overall construction
Know the basic parameters
• This is the system voltage to which the grounded winding is to be connected.
• Don’t forget to specify the BIL also.
• In some cases the BIL will be dictated by equipment considerations, such as 150 kV BIL on 34.5 kV wind farms because of the limitation of dead front connectors
• The Transformer must be sized to carry the rated continuous, phase-to-phase current without exceeding its temperature limit
• The higher the current, the larger and more costly the transformer
• Typical values can be as low as 5 amps to as high as a few hundred
• Include any auxiliary loading requirements
• Is defined as 3X the Phase-to-Phase current (Zero Sequence Current)
• It is the value that is expected to flow in the neutral circuit without tripping protective circuits
• Used to design for thermal capacity of the transformer
• Used to determine the short time heating resulting from a fault on the system which returns through the transformer
• Typical ranges run from a few hundred to a few thousand amps
• Duration is expressed in seconds (i.e. 400 amps for 10 seconds)
• Can be expressed as either a percentage or as an ohmic value
• Either should be chosen such that the un-faulted phase voltages are within the temporary over-voltage capability of:
• The Transformer
• Associated equipment (i.e. arresters, terminal connectors, etc.)
• Typical values can be as low as 8% and as much as 100%
• Must be determined by the system designer
• Specify the secondary voltage and connection for primary Wye connected transformers
• Specify size of auxiliary loading to be connected
• If two winding with no secondary load, advise if the delta winding can be “buried” (not brought out) or if only one bushing is to be brought out for grounding to the tank or testing
• Compartmental pad mount or unit substation design
• Indoor or outdoor
• Fluid type (Mineral Oil, Silicone, or Envirotemp FR3)
• Site Elevation or Environmental conditions
• Connectivity• Dead Front or Live Front
• Spade terminals
• Cover-mounted or sidewall
• Exposed or enclosed
• Temperature Rise• 65 degrees C
• 55 degrees C
• 55/65 deg. C
• Special Coating requirements
The following transformers are for reference only to let you be aware of
different type transformers for different applications.
• A Scott – T Transformer is a transformer that is designed for converting 2 phase current to 3 phase current or vice-versa.
• An autotransformer is a transformer that only have one winding with taps. No isolation is provided between the primary and secondary.
• A Buck-Boost transformer is one that is designed to lower (buck) or raise (boost) the voltage in the range of 5% to 25%. This is a great (low cost) way to get between 208 and 240 Volts, or between 480 and 575 Volts. Used on 1 and 3 Phase applications.
• A drive isolation transformer is one that is typically used on AC or DC Drive systems. It typically has the same primary and secondary voltages and is used for isolation. In addition you typically have a shield to attenuate line to ground noise.
• A constant voltage transformer is one in which the secondary stays constant with large swings on the primary voltage. This is accomplished by operating the primary in a saturated mode so even when the primary voltage dips you can still maintain a constant output. Typical input may be 80% to 110% with the output maintaining 1% voltage regulation.
For more information and specification sheets
Contact:
Levine Lectronics and Lectric, Inc.770 [email protected]