DESIGN AND FAULT ANALYSIS OF A 345KV 220 MILE ...

196
DESIGN AND FAULT ANALYSIS OF A 345KV 220 MILE OVERHEAD TRANSMISSION LINE A Project Presented to the faculty of the Department of Electrical and Electronic Engineering California State University, Sacramento Submitted in partial satisfaction of the requirements for the degree of MASTER OF SCIENCE in Electrical and Electronic Engineering and MASTER OF SCIENCE in Electrical and Electronic Engineering by Greg Clawson Mira Lopez SPRING 2012

Transcript of DESIGN AND FAULT ANALYSIS OF A 345KV 220 MILE ...

DESIGN AND FAULT ANALYSIS OF

A 345KV 220 MILE OVERHEAD TRANSMISSION LINE

A Project

Presented to the faculty of the Department of Electrical and Electronic Engineering

California State University, Sacramento

Submitted in partial satisfaction of

the requirements for the degree of

MASTER OF SCIENCE

in

Electrical and Electronic Engineering

and

MASTER OF SCIENCE

in

Electrical and Electronic Engineering

by

Greg Clawson

Mira Lopez

SPRING

2012

ii

© 2012

Greg Clawson

Mira Lopez

ALL RIGHTS RESERVED

iii

DESIGN AND FAULT ANALYSIS OF

A 345KV 220 MILE OVERHEAD TRANSMISSION LINE

A Project

by

Greg Clawson

Mira Lopez

Approved by:

_____________________________________, Committee Chair

Turan Gönen, Ph.D.

_____________________________________, Second Reader

Salah Yousif, Ph.D.

____________________

Date

iv

Student: Greg Clawson

Mira Lopez

I certify that these students have met the requirements for the format contained in the

University format manual and that this project is suitable for shelving in the Library and

that credit is to be awarded for the project.

_____________________________, Graduate Coordinator _________________

B. Preetham. Kumar, Ph.D. Date

Department of Electrical and Electronic Engineering

v

Abstract

of

DESIGN AND FAULT ANALYSIS OF

A 345KV 220 MILE OVERHEAD TRANSMISSION LINE

by

Greg Clawson

Mira Lopez

Efficient and reliable transmission of bulk power economically benefits both the power

company and consumer. This report gives clarification to concept and procedure in

design of an overhead 345 kV long transmission line. The project will find an optimum

design alternative which meets certain criteria including transmission efficiency, voltage

regulation, power loss, line sag and tension. A MATLAB script will be developed to

assess which alternative solutions can fulfill the criteria.

Integration of protective devices is a fundamental part of achieving power system

reliability. To determine the sizing and setting of protective devices, analysis of potential

fault conditions provide the necessary current and voltage data. A fault analysis for the

final transmission line design will be simulated two ways: 1) by using a MATLAB script

that was developed for this project and 2) by using an available Aspen One Liner

program.

_____________________________________, Committee Chair

Turan Gönen, Ph.D.

_____________________

Date

vi

DEDICATION

I dedicate my work to my sister, Mandica Konjevod for inspiring me.

vii

TABLE OF CONTENTS

Page

Dedication……………………………………………………………………………...…vi

List of Tables…………………………………………………………………………….xii

List of Figures…………………………………………………………………………...xiii

Chapter

1. INTRODUCTION……………………………………………………………..…..…...1

2. LITERATURE SURVEY…………………………………………………………..…..3

2.1. Introduction……………………………………………………………….……...3

2.2. Support Structure……………………………………………………….………...3

2.3. Line Spacing and Transposition……………………………………….…………5

2.3.1. Symmetrical Spacing……………………………………………….……....6

2.3.2. Asymmetrical Spacing………………………………………………..….....7

2.3.3. Transposed Line………………………………………………………..….10

2.4. Line Constants…………………………………………………………………..11

2.5. Conductor Type and Size…………………………………………………….….12

2.6. Extra-High Voltage Limiting Factors……………………………..…………….16

2.6.1. Corona…………………………………………………………………..…16

2.6.2. Line Design Based on Corona………………………………………..…...19

2.6.3. Advantages of Corona………………………………………………….…19

2.6.4. Disadvantages of Corona……………………………………………..…...20

viii

2.6.5. Prevention of Corona……………………………………………………...20

2.6.6. Radio Noise………………………………………………………………..20

2.6.7. Audible Noise…………………………………………………………..…21

2.7. Line Modeling…………………………….……………………………….…….21

2.8. Line Loadability…………………………………………………………………24

2.9. Fault Events……………………………………………..………………………25

2.10. Fault Analysis………………………………………………………….………26

2.11. Single Line-to-Ground (SLG) Fault………...…………………………………27

2.12. Line-to-Line (L-L) Fault…………………………….…………..……………..27

2.13. Double Line-to-Ground (DLG) Fault………………………….………………28

2.14. Three-Phase Fault…………………………………….……….……………….29

2.15. The Per-Unit System…………………………………..………………….……30

3. MATHEMATICAL MODEL……………………………..……….………………….31

3.1. Introduction…………………………………………………………………...…31

3.2. Geometric Mean Distance (GMD)…………………………………………...…31

3.3. Geometric Mean Radius (GMR)………………………………………………..33

3.4. Inductance and Inductive Reactance……………………………………...……..34

3.5. Capacitance and Capacitive Reactance…………………………………….……35

3.6. Long Transmission Line Model………………………………………...….……35

3.7. Sending-End Voltage and Current……………………………………………....40

3.8. Power Loss…………………………………………………………..……….….42

ix

3.9. Transmission Line Efficiency……………………………………..…………….44

3.10. Percent Voltage Regulation…………………………………….…...…………44

3.11. Surge Impedance Loading (SIL)………………………………………………45

3.12. Sag and Tension……………………………………………………………….46

3.12.1. Catenary Method……………….………...………………………… …46

3.12.2. Parabolic Method…………………..…………………………………….50

3.13. Corona Power Loss………………………….…………………………………51

3.13.1. Critical Corona Disruptive Voltage……………………………………...51

3.13.2. Visual Corona Disruptive Voltage……………………………………….53

3.13.3. Corona Power Loss at AC Voltage………………………………………54

3.14. Method of Symmetrical Components……………………………………….....55

3.14.1. Sequence Impedance of Transposed Lines………………………………59

3.15. Fault Analysis………………………………………………………...………..61

3.16. Per Unit………………………………………………………..………….……62

3.17. Single Line-to-Ground (SLG) Fault………………………..…………….……63

3.18. Line-to-Line (L-L) Fault………………………….……...……………………66

3.19. Double Line-to-Ground (DLG) Fault…………………...……………….…….69

3.20. Three-Phase Fault……………………………………………………….……..72

4. APPLICATION OF MATHEMATICAL MODEL…………….…………….……..76

4.1. Introduction……………………………………………………..………………76

4.2. Design Criteria…………………………………………………………..……....77

x

4.3. Geometric Mean Distance (GMD)……………..……………...………………..77

4.4. Geometric Mean Radius (GMR)………………………………………….….....78

4.5. Inductance and Inductive Reactance.………………...…………………………78

4.6. Capacitance and Capacitive Reactance…………………...……...…..…………79

4.7. Long Line Characteristics……………………...……………………………......80

4.8. ABCD Constants………………………….………………………..…………...81

4.9. Sending-End Voltage and Current…………………………………..…………..83

4.10. Power Loss…………………………………….……………..…………….…..84

4.11. Percent Voltage Regulation…………………………………………................86

4.12. Transmission Line Efficiency………………………..………………………...86

4.13. Surge Impedance Loading (SIL)………………………………………………86

4.14. Sag and Tension…………………………………………………………...…...87

4.14.1. Catenary Method…………………………………………………………87

4.14.2. Parabolic Method………………………………………………...………89

4.15. Corona Power Loss ……………………………………………………….…...89

4.15.1. Critical Corona Disruptive Voltage………………………………….......89

4.15.2. Visual Corona Disruptive Voltage…………………………………...…..91

4.15.3. Corona Power Loss at AC Voltage………………………………..……..92

4.15.4. Corona Power Loss for Foul Weather Conditions.………………………94

4.16. Per Unit……………………………………………………………...….……...97

4.17. Fault Analysis Outline…………………………………………….…………...98

xi

4.18. Procedure Using Symmetrical Components……………………..…..………...99

4.19. Fault Analysis at the End of Transmission Line……………....…………..….100

4.19.1. Single Line-to-Ground (SLG) Fault………………………...……....….101

4.19.2. Line-to-Line (L-L) Fault……………….……………………………….104

4.19.3. Double Line-to-Ground (DLG) Fault……….………………………….109

4.19.4. Three Line-to-Ground (3LG) Fault…………………………….....…….113

5. CONCLUSIONS………………………..……………………………………..…….117

Appendix A. Conductor and Tower Characteristics……………….………………......119

Appendix B. Aspen Simulation Model and Analysis……….……….…………...……120

Appendix C. Aspen Fault Analysis Summary…………………..….….………………123

Appendix D. MATLAB–Aspen Fault Analysis Results..……………….……….….....131

Appendix E. MATLAB Code……………………...……………………………...…...137

Bibliography……………………………………………………………………………182

xii

LIST OF TABLES

Tables Page

1. Table 2.1 Typical conductor separation…………………………………….…………5

2. Table 2.2 Aluminum vs. copper conductor type…………………………….…….…13

3. Table 3.1 Corona Factor………………………………………………………..……55

4. Table 3.2 Power and functions of operator a………………………………………...56

5. Table 4.1 Design parameters…………………………………………………………77

6. Table 4.2 System data for power system model.…………………………...………..99

7. Table 4.3 Fault analysis of SLG fault at receiving end of line.……………….……104

8. Table 4.4 Fault analysis of L-L fault at receiving end of line.………….…….……108

9. Table 4.5 Fault analysis of DLG fault at receiving end of line……………………112

10. Table 4.6 Fault analysis of 3LG fault at receiving end of line……………………..116

xiii

LIST OF FIGURES

Figures Page

1. Figure 2.1 Three-phase line with symmetrical spacing…………………………..…...6

2. Figure 2.2 Cross section of three-phase line with horizontal tower configuration…....6

3. Figure 2.3 Three-phase line with asymmetrical spacing………………………………8

4. Figure 2.4 A transposed three-phase line…………………………………………….10

5. Figure 2.5 Equivalent circuit of short transmission line…………………….…….…22

6. Figure 2.6 Nominal-T circuit of medium transmission line……………………...….22

7. Figure 2.7 Nominal-π circuit of medium transmission line……………………….…23

8. Figure 2.8 Segment of 1-phase and neutral connection for long transmission line.…23

9. Figure 2.9 Practical Loadability for Line Length……………………………………25

10. Figure 2.10 General representation for single line-to-ground fault………………….27

11. Figure 2.11 General representation for line-to-line fault…………………………….28

12. Figure 2.12 General representation of double line-to-ground fault………………….29

13. Figure 2.13 General representation for three-phase fault………………………...….30

14. Figure 3.1 Bundled conductors configurations………………...…………………….32

15. Figure 3.2 Cross section of three-phase horizontal bundled-conductor……………..32

16. Figure 3.3 Segment of 1-phase and neutral connection for long transmission line….36

17. Figure 3.4 Parameters of catenary…………………………………...………………48

18. Figure 3.5 Parameters of parabola…………………………………………………...50

19. Figure 3.6 Sequence components……………………………..……………………..56

xiv

20. Figure 3.7 Single line-to-ground fault sequence network connection……………….64

21. Figure 3.8 Line-to-line fault sequence network connection………...……………….66

22. Figure 3.9 Double line-to-ground fault sequence network connection………………70

23. Figure 3.10 Three-phase fault sequence network connection………………………..72

24. Figure 4.1 3H1 wood H-frame type structure.…………………………………...…..76

25. Figure 4.2 One line diagram of power system model.…………………………...…..98

26. Figure 4.3 Power system model with fault at end of line.……………………….....100

27. Figure 4.4 Equivalent sequence networks.…………………………………………101

28. Figure 4.5 Sequence network connection for SLG fault…………………………...101

29. Figure 4.6 Sequence network connection for L-L fault.……………………………105

30. Figure 4.7 Sequence network connection for DLG fault.……………………..……109

31. Figure 4.8 Sequence network connection for 3LG fault ……………………..…….113

1

Chapter 1

INTRODUCTION

The purpose of this project is to design an overhead long transmission line that operates

at an extra-high voltage (EHV), and effectively supplies power to a specified load. The

line will have a length of 220 miles, and operate at 345 kV. The receiving end of the line

will be connected to a load of 100 MVA with a lagging power factor of 0.9.

Design of an overhead transmission line is an intricate process that essentially involves a

complete study of conductors, structure, and equipment [1]. The study determines the

potential effectiveness of a proposed system of components in satisfying design criteria.

The design criteria for this project are primarily focused on electrical performance

requirements. The criteria include transmission line efficiency, power loss, voltage

regulation, line sag and tension. To simplify the design process for this project, the same

support structure will be used for all design options, and for the final solution. The

options in conductor size with the predetermined structure will provide alternative

solutions. A MATLAB program will be used to determine the performance of all

alternative solutions with respect to each design criteria. Amongst the options, the ones

that meet all design criteria will be considered and compared for selecting the optimal

final solution.

A fault analysis will be completed for the final solution in order to demonstrate the

electrical behavior and performance of the transmission line system, when subjected to

fault conditions. The system model will interconnect the transmission line to a typical

2

generator source, via a step-up transformer, in order to supply power to the line. On the

receiving end of the line, the load will be connected. This fault study will be completed

twice, one time via a MATLAB program, and another time via the ASPEN One-Liner

software. Current and voltage conditions will be found during the different fault events.

The study will cover fault events occurring at the following three locations: 1) beginning

of the transmission line, 2) midpoint on the transmission line and 3) end of the

transmission line. At each location, the four classical fault types will be considered.

The last analysis for this project will use the ASPEN One-Liner software to simulate the

load flow for the final line design using the same system model as described for the fault

study. The results will indicate performance of the final line design under normal

operating conditions.

Equation Chapter (Next) Section 1

Equation Chapter (Next) Section 1

Equation Section (Next)

3

Chapter 2

LITERATURE SURVEY

2.1 INTRODUCTION

This chapter succinctly introduces and explains important fundamental concepts and

terminology involved with transmission line design and fault analysis. Some basic theory

is provided as circumstantial information that leads to general questions and issues that

must be addressed during the design and analysis processes.

2.2 SUPPORT STRUCTURE

A line design usually has structure support requirements that are very similar to

requirements of some existing lines [1]. Thus, an existing structure design can likely be

found and leveraged to accommodate the support requirements. For this reason, most of

the work associated with the structure involves defining the configuration and mechanical

load requirements that the structure must support in order to select the appropriate

existing structure design.

Many factors must be considered when defining the configuration and mechanical load of

an overhead transmission line. First, data about the environmental conditions and climate

must be gathered and reviewed. Parameters such as air temperature, wind velocity,

rainfall, snow, ice, relative humidity and solar radiation must be studied [9].

Subsequently, other factors are assessed, including conductor weight, ground shielding

needs, clearance to ground, right of way, equipment mounting needs, material

4

availability, terrain to be crossed, cost of procurement, and lifetime upgrading and

maintenance [1].

Conductor load is found by calculating sag/tension on the conductor. The amount of

tension depends on the conductor's weight, sag, and span. In addition, wind and ice

loading increases the tension and must be included in the load specifications [9]. For safe

operation of conductors, the structure must have a margin of strength under all expected

load/tension conditions. For all conditions, the structure must also provide adequate

clearance between conductors.

The three main types of structures are pole, lattice, and H-frame. The lattice and H-frame

types are stronger than the pole type, and provide more clearance between conductors.

Common materials used for structure fabrication are wood, steel, aluminum and concrete

[1]. For an extra-high or ultra-high voltage line, conductors are larger and heavier, so the

structure must be stronger than ones that are used for lower voltage lines. Steel lattice

type structures are the most reliable, having advantages in strength of structure type and

material and in additional clearance between conductors. In comparison, wood and

concrete pole type structures are suited more for lower load stresses. Wood has

advantages of less procurement cost and natural insulating qualities [1].

Since the scope of this project is primarily focused on the electrical design criteria of

transmission lines, a structure for this design will be selected from a group of existing

345kV support structures without defining specific load support requirements.

5

2.3 LINE SPACING AND TRANSPOSITION

When designing a transmission line the spacing between conductors should be taken into

consideration. There are two aspects of spacing analysis: mechanical and electrical.

Mechanical Aspect: Wing conductors usually swing synchronously. However, in cases

of small size conductors and long spans there is the likelihood that conductors might

swing non-synchronously. In order to determine correct conductor spacing the following

factors should be included into analysis: the material, the diameter and the size of the

conductor, in addition to maximum sag at the center of the span. A conductor with

smaller cross-section will swing out further than a conductor of large cross-section. There

are several formulas in use to determine right spacing [8].This is NESC, USA formula

3.6812

LD A S (2.1)

D = horizontal spacing in cm

A = 0.762 cm per kV line voltage

S = sag in cm

L = length of insulator string in cm

Voltage between

conductors

Minimum horizontal

spacing

Minimum vertical

spacing

Up to 8700V 12in 16in

8701 to 50,000V 12in, plus 0.4in for each

1000 V above 8700V* 40in

Above 50,000V 12in, plus 0.4in for each

1000 V above 8700V

40in, plus 0.4in for each

1000 V above 50,000V

*This is approximate.

Table 2.1 Typical conductor separation [11].

6

Electrical Aspect: When increasing spacing (GMDΦ = geometric mean distance between

the phase conductors in ft) Z1 (positive-sequence impedance) increases and Z0 (zero-

sequence impedance) decreases. If the neutral is placed closer to the phase conductors it

will reduce Z0 but may increase the resistive component of Z0. A small neutral with high

resistance increases the resistance part of Z0 [8].

2.3.1 SYMMETRICAL SPACING

Three-phase line with symmetrical spacing forms an equilateral triangle with a distance D

between conductors. Assuming that the currents are balanced:

0a b cI I I (2.2)

(a) (b)

Figure 2.1 Three-phase line with symmetrical spacing: a) geometry; b) phase inductance [8].

b ca

D12 D23

D31

Figure 2.2 Cross section of three-phase line with horizontal tower configuration.

La

neutral

D

D

D

Ia

IbIcr

7

The total flux linkage of phase conductor is:

7

'

1 1 12 10 ( )a a b cI ln I ln I ln

Dr D (2.3)

b c aI I I (2.4)

7

'

1 12 10 a a aI ln l

rI n

D

(2.5)

72 10'

a a lnr

DI (2.6)

Because of symmetry:

a b c (2.7)

and the three inductances are identical.

The inductance per phase per kilometer length:

0.2s

D mHL ln

D km (2.8)

r′= the geometric mean radius, GMR, and is shown by Ds

For a solid round conductor:

1

4sD r e

(2.9)

Inductance per phase for a three-phase circuit with equilateral spacing is the same as for

one conductor of a single-phase circuit.

2.3.2 ASYMMETRICAL SPACING

While constructing a transmission line it is necessary to take into account the practical

problem of how to maintain symmetrical spacing. With asymmetrical spacing between

8

the phases, the voltage drop due to line inductance will be unbalanced even when the line

currents are balanced. The distances between the phases are denoted by D12, D32 and D13.

The following flux linkages for the three phases are obtained:

D13

D23

D12

a

b

c

Figure 2.3 Three-phase line with asymmetrical spacing [8].

7

12 13

1 1 12 10 ( )

'a a b cI ln I ln I ln

r D D (2.10)

7

12 23

1 1 12 10 ( )

'b a b cI ln I ln I ln

D r D (2.11)

7

13 23

1 1 12 10 (

' )c a b cI ln I ln I ln

D D r (2.12)

In matrix form:

L I (2.13)

9

The symmetrical inductance matrix:

12 13

7

12 23

13 23

1 1 1

'

'

'

1 1 12 10

1 1 1

ln ln lnr D D

L ln ln lnD

r

r D

ln ln lnD D

(2.14)

With Ia as a reference for balanced three-phase currents:

2240b a aI I a I (2.15)

120c a aI I a I (2.16)

The operator a:

120aa I (2.17)

2 240aa I (2.18)

The phase inductances are not equal and they contain an imaginary term due to the

mutual inductance:

7

12 13

1 1 1 2 10 ( )

'

aa a b c

a

L I ln I ln I lnI r D D

(2.19)

7

12 23

1 1 1 2 10 (

')

bb a b c

b

L I ln I ln I lnI D r D

(2.20)

7

13 23

1 1 1 2 1

'0

cc a b c

c

L I ln I ln I lnI D D r

(2.21)

10

2.3.3 TRANSPOSED LINE

In most power system analysis a per-phase model of the transmission line is required.

The previously above stated inductances are unwanted because they result in an

unbalanced circuit configuration. The balanced nature of the circuit can be restored by

exchanging the positions of the conductors at consistent intervals. This is known as

transposition of line and is shown in Figure 2.4. In this example each segment of the line

is divided into three equal sub-segments. Transposition involves interchanging of the

phase configuration every one-third the length so that each conductor is moved to occupy

the next physical position in a regular sequence.

aa

aa

aa

bb

bb

bb

cc

cc

cc

1

2

3

D23D23

D12D12

S/3

Length of line, S

S/3 S/3

1

2

3

1

2

3

Section IISection I Section III

Figure 2.4 A Transposed three-phase line [7].

In a transposed line, each phase takes all the three positions. The inductance per phase

can be found as the average value of the three inductances (La, Lb and Lc) previously

calculated in (2.19) to (2.21). Consequently,

3

a b cL L LL

(2.22)

11

Since, 2 1 120 1 240 1o oa a (2.23)

The average of a b cL L L come to be

7

'

12 23 13

2 10 1 1 1 1 3

3L ln ln ln ln

r D D D

(2.24)

1

37 12 23 31( )

2 10'

D D DL ln

r

(2.25)

The inductance per phase per kilometer length:

0.2s

GMD mHL ln

D km (2.26)

Ds is the geometric mean radius, (GMR). For stranded conductor Ds is obtained from the

manufacture‟s data. However, for solid conductor:

1

4'sD r r e

(2.27)

GMD (geometric mean distance) is the equivalent conductor spacing:

312 23 31GMD D D D (2.28)

For the modeling purposes it is convenient to treat the circuit as transposed.

2.4 LINE CONSTANTS

Transmission lines have four basic constants: series resistance, series inductance, shunt

capacitance, and shunt conductance [8].

Series resistance is the most important cause of power loss in a transmission line. The ac

resistance or effective resistance of a conductor is

12

2

ΩLac

PR

I (2.29)

where the real power loss (PL) in the conductor is in watts, and the conductor's rms

current (I) is in amperes [8]. The amount of resistance in the line depends mostly upon

conductor material resistivity, conductor length, and conductor cross-sectional area.

The inductance of a transmission line is calculated as flux linkages per ampere. An

accurate measure of inductance in the line must include both flux internal to each

conductor and the external flux that is produced by the current in each conductor [5].

Both series resistance and series inductance, i.e. series impedance, bring about series

voltage drops along the line.

Shunt capacitance produces line-charging currents. Shunt capacitance in a transmission

line is due to the potential difference between conductors [1].

Shunt conductance causes, to a much lesser degree, real power losses as a result of

leakage currents between conductors or between conductors and ground. The current

leaks at insulators or to corona [8]. Shunt conductance of overhead lines is usually

ignored.

2.5 CONDUCTOR TYPE AND SIZE

A conductor consists of one or more wires appropriate for carrying electric current. Most

conductors are made of either aluminum or copper.

13

Aluminum (Al) Copper (Cu) Observation

Melting Point 660C 1083C

Annealing

starts

Most rapidly

above 100C

100C

200C and 325C

Both soften and lose

tensile strength.

Resistance to

corrosion Good Very Good

Al corrodes quickly

through electrical

contact with Cu or

steel. This galvanic

corrosion

accelerates in the

presence of salt.

Oxidation When exposed to the

atmosphere

Al thin invisible

oxidation film

protects against

most chemicals,

weather and even

acids.

Resistivity Very low

Cu conductor has

equivalent

ampacity of an

aluminum

conductor that is

two AWG sizes

larger. A larger Al

cross-sectional area

is required to obtain

the same loss as in a

Cu conductor

Usage

Al is lighter, less

expensive and so it has

been used for almost all

new overhead

installations

Cu is widely used as a

power conductor, but

rarely as an overhead

conductor. Cu is

heavier and more

expensive than Al

The supply of Al is

abundant, whereas

that of Cu is limited.

Table 2.2 Aluminum vs. copper conductor type.

Since aluminum is lighter and less expensive for a given current-carrying capability it has

been used by utilities for almost all new overhead installations. Aluminum for power

14

conductors is alloy 1350, which is 99.5% pure and has a minimum conductivity of 61.0%

IACS [10].

Different types of aluminum conductors are available:

AAC — all-aluminum conductor

Aluminum grade 1350-H19 AAC has the highest conductivity-to-weight ratio of all

overhead conductors [10].

ACSR — aluminum conductor, steel reinforced

Because of its high mechanical strength-to-weight ratio, ACSR has equivalent or higher

ampacity for the same size conductor. The steel adds extra weight, normally 11 to 18% of

the weight of the conductor. Several different strandings are available to provide different

strength levels. Common distribution sizes of ACSR have twice the breaking strength of

AAC. High strength means the conductor can withstand higher ice and wind loads.

Also, trees are less likely to break this conductor [10]. Stranded conductors are easier to

manufacture, since larger conductor sizes can be obtained by simply adding successive

layers of strands. Stranded conductors are also easier to handle and more flexible than

solid conductors, especially in larger sizes. The use of steel strands gives ACSR

conductors a high strength-to-weight ratio. For purposes of heat dissipation, overhead

transmission-line conductors are bare (no insulating cover) [8].

AAAC — all-aluminum alloy conductor

This alloy of aluminum, the 6201-T81 alloy, has high strength and equivalent ampacities

of AAC or ACSR. AAAC finds good use in coastal areas where use of ACSR is

prohibited because of excessive corrosion [10].

15

ACAR — aluminum conductor, alloy reinforced

Strands of aluminum 6201-T81 alloy are used along with standard 1350 aluminum. The

alloy strands increase the strength of the conductor. The strands of both are the same

diameter, so they can be arranged in a variety of configurations. For most urban and

suburban applications, AAC has sufficient strength and has good thermal characteristics

for a given weight. In rural areas, utilities can use smaller conductors and longer pole

spans, so ACSR or another of the higher-strength conductors is more appropriate [10].

Conductor Sizes

The American Wire Gauge (AWG) is the standard generally employed in this country

and where American practices prevail. The circular mil (cmil) is usually used as the unit

of measurement for conductors. It is the area of a circle having a diameter of 0.001 in,

which works out to be 0.7854 × 10–6 in2. In the metric system, these figures are a

diameter of 0.0254 mm and an area of 506.71 × 10–6 mm2 [11]. Wire sizes are given in

gauge numbers, which, for distribution system purposes, range from a minimum of no. 12

to a maximum of no.0000 (or 4/0) for solid type conductors. Solid wire is not usually

made in sizes larger than 4/0, and stranded wire for sizes larger than no. 2 is generally

used. Above the 4/0 size, conductors are generally given in circular mils (cmil) or in

thousands of circular mils (cmil × 103); stranded conductors for distribution purposes

usually range from a minimum of no. 6 to a maximum of 1,000,000 cmil (or 1000 cmil ×

103) and may consist of two classes of strandings. Gauge numbers may be determined

from the formula:

0.3249

1.123n

Diameter in (2.30)

16

105,500

Cross sectional area 1,261n

cmil (2.31)

where n is the gauge number (no. 0 = 0; no. 00 = – 1; no. 000 = – 2; no.0000 = – 3) [11].

2.6 EXTRA HIGH VOLTAGE LIMITING FACTORS

Limiting factors for extra high voltage are:

a) Corona

b) Radio noise (RN)

c) Audible Noise (AN)

2.6.1 CORONA

Air surrounding conductors act as an insulator between them. Under certain conditions

air gets ionized and its partial breakdown occurs. Disruption of air dielectrics when the

electrical field reaches the critical surface gradient is known as corona. Corona effect

causes significant power loss and a high frequency current. Corona comes in different

forms: visual corona as violet or blue glows, audible corona as high pitched sound and

gaseous corona as ozone gas which can be identified by its specific odor. In addition

high conductor surface gradient causes the emission of radio and television interference

(RI and TVI) to the surrounding antennas known as radio corona. In order to design

corona free lines it is necessary to take into consideration following factors:

1) Electrical

2) Atmospheric

17

3) Conductor

1) Electrical Factors:

a) Frequency and waveform of the supply: Corona loss is a function of frequency.

For that reason the higher the frequency of the supply voltage the higher is corona

loss. This means that corona loss at 60 Hz is greater than at 50 Hz. As a result

direct current (DC) corona loss is less than the alternate current (AC).

b) Line Voltage: Line voltage factor is significant for voltages higher than disruptive

voltage. Corona and line voltage are directly proportional.

c) Conductor electrical field: Conductor electrical field depends on the voltage and

conductor configuration i.e., vertical, horizontal, delta etc. In horizontal

configuration the middle conductor has a larger electrical field than the outsides

ones. This means that the critical disruptive voltage is lower for the middle

conductor and therefore corona loss is larger.

2) Atmospheric Factors: Air density, humidity, wind, temperature and pressure have an

effect on the corona loss. In addition rain, snow, hail and dust can reduce the critical

disruptive voltage and hence increase the corona loss. Rain has more effect on the

corona loss than any other weather conditions. The most influential are temperature

and pressure. Atmospheric condition such as air density is directly proportional to the

air strength breakdown.

3) Conductor Factors: Several different conductor factors affect the corona loss:

18

a) Radius or size of the conductor: The larger the size of the conductor (radius) the

larger the power lower loss. For a certain voltages the larger the conductor size,

the larger the critical disruptive voltage and therefore the smaller the power loss.

2( )loss ln cP V V (2.32)

Vln = line-to-neutral (phase) operating voltage in kV

Vc = disruptive (inception) critical voltage kV (rms)

b) Spacing between conductors: The larger the spacing between conductors the

smaller the power loss. This can be observed from power loss approximation:

loss

rP

D (2.33)

r = conductor radius

D = distance (spacing) between conductors

c) Number of conductors / Phases: In case of a single conductor per phase for higher

voltages there is a significant corona loss. In order to reduce corona loss two or

more conductors are bundled together. By bundling conductors the self-

geometric mean distance (GMD) and the critical disruptive voltage are greater

than in case of a single conductor per phase which leads to reducing corona loss.

d) Profile or shape of the conductor: Conductors can have different shapes or

profiles. The profile of the conductor (cylindrical, oval, flat, etc.,) affects the

corona loss. Cylindrical shape has better field uniformity than any other shape and

hence less corona loss.

19

e) Surface conditions of the conductors: The disruptive voltage is higher for smooth

cylindrical conductors. Conductors with uneven surface have more deposit (dust,

dirt, grease, etc.,) which lowers the disruptive voltage and increases corona.

f) Clearance from ground: Electrical field is affected by the height of the conductor

from the ground. Corona loss is greater for smaller clearances.

g) Heating of the conductor by load current: Load current causes heating of the

conductor which accelerates the drying of the conductor surface after rain. This

helps to minimize the time of the wet conductor and indirectly reduces the corona

loss [12].

2.6.2 LINE DESIGN BASED ON CORONA

When designing a long transmission line (TL) it is desirable to have corona-free lines for

fair weather conditions and to minimize corona loss under wet weather conditions. The

average corona value is calculated by finding out corona loss per kilometer at various

points at long transmission line and averaging them out. For typical transmission line in

fair weather condition corona loss of 1kW per three-phase mile and foul weather loss of

20 kW per three-phase mile is acceptable [7].

2.6.3 ADVANTAGES OF CORONA

Corona reduces the magnitude of high voltage waves due to lightning by partially

dissipating as a corona loss. In this case it has a purpose of a safety valve.

20

2.6.4 DISADVANTAGES OF CORONA

a) Loss of power

b) The effective capacitance of the conductor is increased which increases the

flow of charging current.

c) Due to electromagnetic and electrostatic induction field corona interferes with

the communication lines which usually run along the same route as the power

lines [7].

2.6.5 PREVENTION OF CORONA

Corona loss can be prevented by:

a) increasing the radius of conductor

b) increasing spacing of the conductors

c) selecting proper type of the conductor

d) using bundled conductors [7].

2.6.6 RADIO NOISE

Radio noise (RN) happens due to corona and gap discharges (sparking). It is unwanted

interference within radio frequency band. RN includes radio interference (RI) and

television interference (TVI).

Radio interference (RI): It affects amplitude modulated (AM) radio waves within the

standard broadcast band (0.5 to 1.6 MHz). Frequency modulated (FM) waves are less

affected.

21

Television interference (TVI): In general TVI is caused by sparking within VHF (30-

300MHz) and UHF (300-3000MHz) bands. Two types of TVI are recognized due to

weather conditions: fair and foul [1].

2.6.7 AUDIBLE NOISE

Audible noise (AN) takes place predominantly during foul weather conditions due to

corona. AN sounds like a hiss or sizzle. In addition corona produces low-frequency

humming tones (120 - 240Hz) [1].

2.7 LINE MODELING

To understand the electrical performance of a transmission line, electrical parameters at

both ends of a line must be evaluated. When voltage and current is given at one end of a

line, an accurate calculation of voltage and current at the other end, or at some point

along the line, requires a sufficiently accurate model of a line. How a transmission line is

modeled depends on the line length. There are three classes of line lengths. For line

lengths that are classified as short, up to 50 miles, the model is simplified because shunt

capacitance and shunt admittance can be omitted because they have little effect on the

accuracy of the model. Because the line impedance is constant throughout the line, the

current will be the same from the sending end to the receiving end, so the model can be a

simple, lumped impedance value, as shown in Figure 2.5 [1].

22

Figure 2.5 Equivalent circuit of short transmission line [1].

For line lengths that are classified as medium, between 50 and 150 miles, there is enough

current leaking through the shunt capacitance that shunt admittance must be included in

order for the model to be an acceptable representation. However, a medium line is still

short enough that lumping the shunt admittance at some points along the line is a

sufficiently accurate model [1]. Typically, a medium line is modeled either as a T or π

network, as shown in Figures 2.6 and 2.7.

Figure 2.6 Nominal-T circuit of medium transmission line [1].

I S Z = R + jX LI R

+

V S

-

+

V R

-

a a ’

N ’N

S e n d in g

e n d

( s o u r c e )

R e c e iv in g

e n d

( s o u r c e )

l

I S R / 2 + j( X L / 2 ) R / 2 + j( X L / 2 ) I R

+

V S

-

+

V R

-

C G

I Y

a a ’

N ’N

V Y

23

Figure 2.7 Nominal-π circuit of medium transmission line [1].

For line lengths that are classified as long, above 150 miles, the needed accuracy from the

model requires that the series impedance and shunt admittance be represented by a

uniform distribution of the line parameters [1]. Each differential length is infinitely small

and defined as a unit length. The series impedance and shunt admittance is represented

for each unit length of line, as shown in Figure 2.8.

Figure 2.8 Segment of one phase and neutral connection for long transmission line [5].

I S R + jX LI R

+

V S

-

+

V R

-

C / 2 G / 2

I C 1

a a ’

N ’N

C / 2 G / 2

I C 2

I I

24

This model accounts for the changes in voltage and current throughout the line exactly as

the series impedance and shunt admittance affect them. In this way, the difference

between voltage and current at the sending end and receiving end can be analyzed

accurately [5]. The scope of this project will only cover the mathematical model used for

designing long line lengths. For details of the long transmission line mathematical model,

see Chapter 3.

2.8 LINE LOADABILITY

The characteristic impedance of a line, also known as surge impedance, is a function of

line inductance and capacitance. Surge impedance loading (SIL) is a measure of the

amount of power the line delivers to a purely resistive load equal to its surge impedance.

SIL provides a comparison of the capabilities of lines to carry load, and permissible

loading of a line can be expressed as a fraction of SIL.

The theoretical maximum power that can be transmitted over a line is when the angular

displacement across the line is δ = 90⁰, for the terminal voltages. However, for reasons

of system stability, the angular displacement across the line is typically between 30⁰ and

45⁰ [8]. Figure 2.9 illustrates the differences in curve plots for the theoretical steady-

state stability limit and a practical line loadability. The practical line loadability is

derived from a typical voltage-drop limit of and a maximum angular

displacement of 30⁰ to 35⁰ across the line [8]. The loadability curve is generally

applicable to overhead 60-Hz lines with no compensation.

25

Figure 2.9 Practical Loadability for Line Length [8].

As indicated by the chart, for lines classified as short, the power transfer capability is

determined by the thermal loading limit. For medium and long lines, maximum power

transfer is determined by the stability limit.

2.9 FAULT EVENTS

A fault event in an electric power transmission system is any abnormal change in the

physical state of a transmission system that impairs normal current flow. Typically, a

fault in a transmission line occurs when an external object or force causes a short circuit.

Examples of external objects that intrude upon an overhead transmission line are

lightning strikes, tree limbs, animals, high winds, earthquakes, and local structures.

Other faults occur when components or devices in a transmission system fail. During a

fault, the network can experience either an open circuit or a short circuit. Short-circuit

26

faults impose the most risk of damaging elements in a power system. Open circuit faults

are typically not a threat for causing damage to other network elements.

2.10 FAULT ANALYSIS

Important part of TL designing includes fault analysis. In order to have well protected

network typically faults are simulated at different points throughout the transmission

system. It is crucial to have precise analysis of the designed system to prevent fault‟s

interruption. In general the three phase faults can be classified as:

1. Shunt faults (short circuits)

1.1. Unsymmetrical faults (Unbalanced)

1.1.1. Single line-to-ground (SLG) fault

1.1.2. Line-to-line (L-L) fault

1.1.3. Double line-to-ground (DLG) fault

1.2. Symmetrical fault (Balanced)

1.2.1. Three-phase-fault

2. Series Faults (open conductor)

2.1. Unbalanced faults

2.1.1. One line open (OLO)

2.1.2. Two lines open (TLO)

3. Simultaneous faults

27

2.11 SINGLE LINE-TO-GROUND (SLG) FAULT

Seventy percent of all transmission line faults are attributable to when a single conductor

is physically damaged and either lands a connection to the ground or makes contact with

the neutral wire [1]. This fault type makes the system unbalanced and is called a single

line-to-ground (SLG) fault. The failed phase conductor, generally defined as phase a, is

connected to ground by an impedance value Zf. Figure 2.10 shows the general

representation of an SLG fault.

Zf

a

b

c

n

F

+Vaf

-

Ibf = 0Iaf Icf = 0

Figure 2.10 General representation for single line-to-ground fault [1].

2.12 LINE-TO-LINE (L-L) FAULT

A line-to-line fault is unsymmetrical (unbalanced) fault and it takes place when two

conductors are short-circuited. This can happen for various reasons i.e., ionization of air,

28

flashover, or bad insulation. Figure 2.11 shows the general representation of an LL fault

[1].

a

b

c

F

Ibf Iaf=0 Icf = -Ibf

Zf

Figure 2.11 General representation for line-to-line fault [1].

2.13 DOUBLE LINE-TO-GROUND (DLG) FAULT

Ten percent of all transmission line faults are attributable to when two conductors are

physically damaged and both of them land a connection through the ground or both

contact the neutral wire [1]. This fault type makes the system unbalanced and is called a

double line-to-ground (DLG) fault. The failed phase conductors, generally defined as

phases b and c, are each connected to ground by their own separate fault impedance value

Zf and a common ground impedance value Zg.

29

Figure 2.12 shows the general representation of a DLG fault.

Zf

a

b

c

n

F

Ibf Iaf = 0 Icf

Zf

Zg

N

Ibf + Icf

Figure 2.12 General representation of double line-to-ground fault [1].

2.14 THREE-PHASE FAULT

A three-phase (3Φ) fault occurs when all three phases of a TL are short-circuited to each

other or earthed. It is a symmetrical (balanced) fault and the most severe one. Since 3Φ

fault is balanced it is sufficient to identify the positive sequence network. As all three

phases carry 120 displaced equal currents the single line diagram can be used for the

analysis. Three-phase faults make 5% of the initial faults in a power system [1].

30

Figure 2.13 shows the general representation of a 3Φ fault.

Zf

a

b

c

n

F

Ibf Iaf Icf

Zf

Zg

N

Iaf +Ibf + Icf = 3Ia0

Zf

Figure 2.13 General representation for three-phase (3Φ) fault [1].

2.15 THE PER-UNIT SYSTEM

In power system analysis it is beneficial to normalize or scale quantities because of

different ratings of the equipment used. Usually the impedances of machines and

transformers are specified in per-unit or percent of nameplate rating. Using per-unit

system has more than a few advantages such as simplifying hand calculations,

elimination of ideal transformers as circuit component, bringing voltage from beginning

to end of the system close to unity, and simplifies analysis of the system overall.

Particular disadvantages are that sometimes phase shifts are eliminated and equivalent

circuits look more abstract. In spite of this per-unit system is widely used in industry.

31

Chapter 3

MATHEMATICAL MODEL

Equation Chapter (Next) Section 1

3.1 INTRODUCTION

This chapter steps through the mathematical approach which is used for design and

analysis of an overhead extra-high voltage long transmission line. Some information

about the physical solution is included to relate the mathematical model and physical

solution.

After design requirements are established, the first step in preliminary design is to choose

a standardized support structure that can be adapted to provide the best solution for the

given job. The selection should be taken from a group of structures that have been

categorized as standard designs for the transmission voltage level that matches the design

requirement. A selected structure will define the spacing between conductor phases and

the limits on conductor size that can be supported.

The next step in preliminary design is to choose a conductor type and size that has

adequate capacity to handle the load current. With a preliminary selection of support

structure and conductor type and size, a detailed design analysis can be undertaken, as

shown in the mathematical approach from the following sections.

3.2 GEOMETRIC MEAN DISTANCE (GMD)

Bundling of conductors is used for extra-high voltage (EHV) lines instead of one large

32

conductor per phase. The bundles used at the EHV range usually have two, three, or four

subconductors [1].

(a) (b) (c)

d

d

d d

d

d d

d

Figure 3.1 Bundled conductors configurations: (a) two-conductor bundle; (b) three-conductor

bundle; (c) four-conductor bundle [1].

b'b

d

c'c

d

a'a

d

D12 D23

D31

Figure 3.2 Cross section of bundled-conductor three-phase line with horizontal tower

configuration [1].

The three-conductor bundle has its conductors on the vertices of an equilateral triangle,

and the four-conductor bundle has its conductors on the corners of a square.

For balanced three-phase operation of a completely transposed three-phase line only one

phase needs to be considered. Deq, the cube root of the product of the three-phase

spacings, is the geometric mean distance (GMD) between phases:

312 23 31 eq mD D D D D ft (3.1)

33

3.3 GEOMETRIC MEAN RADIUS (GMR)

Geometric Mean Radius (GMR) of bundled conductors for

Two-conductor bundle:

b

S SD D d ft (3.2)

Three-conductor bundle:

23 b

S SD D d ft (3.3)

Four-conductor bundle:

34 b

S SD D d ft (3.4)

where:

= GMR of subconductors

distance between two subconductors

If the phase spacings are large compared to the bundle spacing, then sufficient accuracy

for Deq is obtained by using the distances between bundle centers. If the conductors are

stranded and the bundle spacing d is large compared to the conductor outside radius, each

stranded conductor is replaced by an equivalent solid cylindrical conductor with

GMR= .

The modified GMR of bundled conductors used in capacitance calculations for

Two-conductor bundle:

b

SCD r d ft (3.5)

Three-conductor bundle:

3 2 b

SCD r d ft (3.6)

34

Four-conductor bundle:

341.09 b

SCD r d ft (3.7)

where:

= outside radius of subconductors

= distance between two subconductors.

3.4 INDUCTANCE AND INDUCTIVE REACTANCE

For three-phase transmission lines that are completely transposed, Equation (3.1) can be

used to find the equivalent equilateral spacing for the line. Thus, the average inductance

per phase is

72 10 ln

eq

a

s

D HL

D m

(3.8)

or

100.7411 log eq

a

s

D mHL

D mi

(3.9)

and the inductive reactance is found by

2L aX f L per phase (3.10)

or

0.1213 ln eq

L

s

DX

D mi

per phase (3.11)

35

3.5 CAPACITANCE AND CAPACITIVE REACTANCE

The average line-to-neutral capacitance per phase is

10

0.0388 μF to neutral

log

N

eq

CD mi

r

(3.12)

where

1

3 eq m ab bc caD D D D D ft (3.13)

radius of cylindrical conductor in feet.

The capacitive reactance is calculated by

1

2C

N

Xf C

(3.14)

or

100.06836 log .eq

C

DX M mi

r

(3.15)

3.6 LONG TRANSMISSION LINE MODEL

For lines 150 miles and longer, i.e. long lines, modeling with lumped parameters is not

sufficiently accurate for representing the effects of the parameters‟ uniform distribution

throughout the length of the line. An acceptable model provides mathematical

expressions for voltage and current at any point along the line [1]. Figure 3.3 depicts a

segment of one phase of a three-phase transmission line of length l.

36

Figure 3.3 Segment of one phase and neutral connection for long transmission line. [5]

The following derivation is given by Saadat [5]. The series impedance per unit length is

z, and the shunt admittance per phase is y, where z = r + jωL and y = g + jωC. Consider

one small segment of line Δx at a distance x from the receiving end of the line. The

phasor voltages and currents on both sides of this segment are shown as a function of

distance. From Kirchhoff‟s voltage law

( )V x x V x z xI x (3.16)

or

( )

( )V x x V x

zI xx

(3.17)

37

Taking the limit as , we have

( )

( )dV x

zI xdx

(3.18)

Also, from Kirchhoff‟s current law

I x x I x y xV x x (3.19)

or

( )

( )I x x I x

yV x xx

(3.20)

Taking the limit as , we have

( )

( )dI x

yV xdx

(3.21)

Differentiating (3.18) and substituting from (3.21), we get

2

2

( ) ( )( )

d x dI xz z x

dx

VyV

dx (3.22)

Let

2 zy (3.23)

The following second-order differential equation will result.

2

2

2

( )0

d V xV x

dx (3.24)

The solution of the above equation is

1 2

x xV x Ae A e (3.25)

where γ, known as the propagation constant, is a complex expression given by (3.23) or

( ) ( )j zy r j L g j C (3.26)

38

The real part α is known as the attenuation constant, and the imaginary component β is

known as the phase constant. β is measured in radian per unit length. From (3.18), the

current is

1 2 1 2

1 ( ) x x x xdV x yI x Ae A e Ae A e

z dx z z

(3.27)

or

1 2

1 x x

C

I x Ae A eZ

(3.28)

where Zc is known as the characteristic impedance, given by

C

zZ

y (3.29)

To find the constants and , we note that when , ( ) , and ( ) .

From (3.25) and (3.28) these constants are found to be

12

R C RV Z IA

(3.30)

22

R C RV Z IA

(3.31)

Upon substitution in (3.25) and (3.28), the general expressions for voltage and current

along a long transmission line become

2 2

x xR C R R C RV Z I V Z IV x e e

(3.32)

2 2

R RR R

x xC C

V VI I

Z ZI x e e

(3.33)

39

The equations for voltage and currents can be rearranged as follows:

2 2

x x x x

R C R

e e e eV x V Z I

(3.34)

1

2 2

x x x x

R R

C

e e e eI x V I

Z

(3.35)

Recognizing the hyperbolic functions sinh, and cosh, the above equations are written as

follows:

cosh sinhR C RV x x V Z x I (3.36)

1

sinh coshR R

C

I x x V x IZ

(3.37)

We are particularly interested in the relation between the sending-end and the receiving-

end on the line. Setting , ( ) and ( ) , the result is

cosh sinhS R C RV l V Z l I (3.38)

1

sinh coshS R R

C

I l V l IZ

(3.39)

Rewriting the above equations in terms of ABCD constants, we have

S R

S R

V VA B

I IC D

(3.40)

where

cosh cosh coshA l YZ (3.41)

sinh sinh sinhC C

ZB Z l YZ Z

Y (3.42)

40

sinh sinh sinhC C

YC Y l YZ Y

Z (3.43)

cosh cosh coshD A l YZ (3.44)

where

LZ r jx l (3.45)

is total line series impedance per phase

S Y g jb l (3.46)

is total line shunt admittance per phase.

Note that A D (3.47)

and 1AD BC . (3.48)

For a long transmission line, conductance is very small compared to susceptance, and can

be omitted for simplicity. Thus, can be reduced to the following equation:

1

C

Y jb l j lX

(3.49)

3.7 SENDING-END VOLTAGE AND CURRENT

One step in line design is analyzing what power input, i.e. voltage and current, is needed

at the sending-end in order to deliver the load power requirements. If the resulting power

input needs are within parameters that are acceptable to the overall power system, the

design is viable. However, the line design may still be adjusted to match preferred input

parameters. After the ABCD constants are determined, as shown in the previous section,

the following steps can be used to find the sending-end voltage and current.

41

Using the receiving-end design requirements for load power, voltage, and power factor,

the receiving-end line-to-neutral voltage and current magnitude are determined by the

following equations:

( )

3

R L L

R L N

VV (3.50)

and

( )3

R

R L L

S

IV

(3.51)

where:

( ) receiving-end line-to-neutral voltage (kV),

magnitude of receiving-end line current (A).

The receiving-end current phasor can be found by

(cos sin )R R R Rj I I (3.52)

where:

angle difference between ( ) and

and can be found by taking the inverse cosine of the power factor.

Using the calculated values for ABCD constants and receiving-end voltage and current,

we can use Equation (3.40) to determine the corresponding sending-end voltage and

current.

The sending-end voltage and current can be equated by

( ) ( ) ( )S L N RR L N V A V B I (3.53)

42

and

( ) ( )S RR L N I C V D I (3.54)

where:

sending-end line current (A),

( ) sending-end line-to-neutral voltage (kV).

The sending-end line-to-line voltage is

( ) 3 1 30S L L S L N V V (3.55)

where:

( ) sending-end line-to-line voltage (kV).

Note that an additional is added to the angle since the line-to-line voltage is

ahead of its line-to-neutral voltage.

3.8 POWER LOSS

Typically, referring to power loss in a transmission line means the difference in real

power between the sending- and receiving- ends. To calculate the power loss, the first

step is to determine the power factor at each end. For the receiving-end, the power factor

is normally specified per design criteria. For the sending-end, the power factor is found

by determining the angle θS between the sending-end current and voltage phasors. The

expression for sending-end power factor is

cos( os) cSS

S IV L N spf

(3.56)

43

where:

sending-end power factor,

( ) = angle of sending-end line-to-neutral voltage phasor,

angle of sending-end current phasor,

angle difference between ( ) and .

Then, using the value of , the equation for calculating real power at the sending-end is

( )33 cosS L L S SS

P V I (3.57)

where:

( ) sending-end real power in the line (MW).

A similar equation for calculating the receiving-end real power is

( )33 cosR L L R RR

P V I (3.58)

where:

( ) receiving-end real power in the line (MW).

Using the calculated values from the above equations, real power loss in the line is found

by

(3 ) (3 ) (3 )L S RP P P (3.59)

where:

( ) total real power loss in the line (MW).

The majority of power loss in a transmission line is a result of real power loss due to the

resistance of the line. A good design will minimize the total real power loss in the line.

44

3.9 TRANSMISSION LINE EFFICIENCY

Performance of transmission lines is determined by efficiency and regulation of lines.

Transmission line efficiency is:

100R

S

P

P (3.60)

where:

= transmission line efficiency

= receiving-end power

= sending end power

% 100

Power deliverd at receiving endtransmissionlineefficiency

Power sent fromthesending end (3.61)

% 100R

S

Ptransmissionlineefficiency

P (3.62)

The end of the line where source of supply is connected is called the sending end and

where load is connected is called the receiving end [1].

3.10 PERCENT VOLTAGE REGULATION

Voltage regulation of the line is a measure of the decrease in receiving-end voltage as

line current increases. In mathematical terms, percent voltage regulation is defined as the

percent change in receiving-end voltage from the no-load to the full-load condition at a

specified power factor with sending-end voltage VS held constant, that is,

, ,

,

- | |

| |

R NL R FL

R FL

V VPercentVR 100

V (3.63)

45

where:

|VR,NL|=magnitude of receiving-end voltage at no-load,

|VR,FL|=magnitude of receiving-end voltage at full-load with constant |Vs|,

|VS|=magnitude of sending-end phase (line-to-neutral) voltage at no load.

3.11 SURGE IMPEDANCE LOADING (SIL)

In power system analysis of high frequencies or surges caused by lightning, losses are

typically ignored and surge impedance becomes important. A line is lossless when its

series resistance and shunt conductance are zero [6]. The surge impedance of a lossless

line, also known as characteristic impedance, is a function of line inductance and

capacitance, and can be expressed as

C

LZ

C (3.64)

or

C C LZ X X (3.65)

where:

shunt capacitive reactance ( ),

series inductive reactance ( ),

characteristic impedance (Ω).

Surge impedance loading (SIL), a measure of the amount of power the line delivers to a

purely resistive load equal to its surge impedance [6], is found for a three-phase line by

the following equation:

46

2

( )| |Lr L

c

kVSIL MW

Z

(3.66)

where: SIL = surge impedance loading (MW).

SIL provides a comparison of the capabilities of lines to carry load, and permissible

loading of a line can be expressed as a fraction of SIL. SIL, or natural loading, is a

function of the line-to-line voltage, line inductance and line capacitance. Since the

characteristic impedance is based on the ratio of inductance and capacitance, SIL is

independent of line length. The relationship between SIL and voltage explains why an

extra-high voltage line has more power transfer capability than lower voltage lines.

3.12 SAG AND TENSION

3.12.1 CATENARY METHOD

Sag-tension calculations predict the behavior of conductors based on recommended

tension limits under varying loading conditions. These tension limits specify certain

percentages of the conductor‟s rated breaking strength that are not to be exceeded upon

installation or during the life of the line. These conditions, along with the elastic and

permanent elongation properties of the conductor, provide the basis for defining the

amount of resulting sag during installation and long-term operation of the line.

Accurately determined initial sag limits are essential in the line design process. Final sags

and tensions depend on initial installed sags and tensions and on proper handling during

installation. The final sag shape of conductors is used to select support point heights and

span lengths so that the minimum clearances will be maintained over the life of the line.

47

If the conductor is damaged or the initial sags are incorrect, the line clearances may be

violated or the conductor may break during heavy ice or wind loadings [1].

( )maxT w c d (3.67)

( )maxT w c d (3.68)

minT w c (3.69)

H w c (3.70)

H

cw

(3.71)

minT H (3.72)

T = the tension of the conductor at any point P in the direction of the curve

w = the weight of the conductor per unit length

H = the tension at origin 0

c = catenary constant

s = the length of the curve between points 0 and P

v = that the weight of the portion s is ws

L = horizontal distance.

48

d

y

AB

L

0H

2

ls

2

ls

Hc

w

θ

θ

V ws

0' (Directrix) x

y

T=wyTy=ws

Tx=wc

Figure 3.4 Parameters of catenary [1].

An increase in the catenary constant, having the units of length, causes the catenary curve

to become shallower and the sag to decrease. Although it varies with conductor

49

temperature, ice and wind loading, and time, the catenary constant typically has a value

in the range of several thousand feet for most transmission-line catenaries.

For equilibrium

xT H (3.73)

yT w s (3.74)

Tx = the horizontal component

Ty = the vertical component.

The total tension in the conductor at any point x:

w x

T H cosH

(3.75)

The total tension in the conductor at the support:

2

w LT H cos

H

(3.76)

The sag or deflection of the conductor for a span of length L between supports on the

same level:

cosh 12

H w Ld

w H

(3.77)

50

3.12.2 PARABOLIC METHOD

The conductor curve can be observed as a parabola for short spans with small sags.

x

y

A B

L

0 Hwx

d

Ty

H

θ

T Ty

Tx

P

Figure 3.5 Parameters of parabola [1].

The following assumptions can be taken into consideration when using parabolic method:

1. The tension is considered uniform throughout the span.

2. The change in length of the conductor due to stretch or temperature is the same as

the change of the length due to the horizontal distance between the towers [1].

Approximate value of tension by using parabolic method can be calculated as

2

8

w LT

d

(3.78)

51

or

2

8

w Ld

T

(3.79)

when

1

2x L (3.80)

y d . (3.81)

3.13 CORONA POWER LOSS

3.13.1 CRITICAL CORONA DISRUPTIVE VOLTAGE

The maximum stress on the surface of the conductor is given by:

ln

LNmax

V kVE

D cmm r

r

(3.82)

VLN = the phase or line-to-neutral voltage in kV

D = is equivalent spacing in cm

r = radius of the conductor in cm

mc = surface irregularity factor ( )

mc = 1 for smooth, solid, polished round conductor

mc = 0.93 – 0.98 for roughened or weathered conductor

mc = 0.80 – 0.87 for up to seven strands conductor

mc = approx. 0.90 for large conductor with more than seven strands [12]

Mean voltage gradient can be calculated from:

52

ln 3

LNmean

V kVE

D cmm r

r

(3.83)

The air density correction factor is defined as:

3.9211

273

p

t

(3.84)

where:

p = the barometric pressure in cm Hg

t = temperature in C

The critical disruptive voltage (corona inception voltage) Vc is voltage at which complete

disruption of dielectric occurs. The dielectric stress is 30δ kV/cm peak or 21.1δ rms at

NTP i.e., 25C and 76 mmHg. Vc is minimum conductor voltage with respect to earth at

which the corona is expected to start. At Vc corona is not visible [7].

30 c c

DV m r ln kV peak

r

(3.85)

21.1 c c

DV m r ln kV rms

r

(3.86)

Vc = the critical disruptive voltage in kV

The critical disruptive voltage Vc line-to-line is

( ) ( )3 c L L c rmsV V kV (3.87)

53

3.13.2 VISUAL CORONA DISRUPTIVE VOLTAGE

In order to observe corona visually the inception voltage has to exceed the critical

disruptive voltage Vc. The visual critical voltage Vv is given by:

0.301

30 1 v

DV m r ln kV peak

rr

(3.88)

0.301

21.1 1 v

DV m r ln kV rms

rr

(3.89)

Vv = the visual critical voltage in kV

D = equivalent spacing of conductors in cm

r = radius of the conductor in cm [7]

mv = surface irregularity factor ( )

m = 1 for smooth, solid, polished round conductor

For local and general visual corona:

m = 0.93 – 0.98 for roughened or weathered conductor

For local visual corona:

m = 0.70 – 0.75 for weathered stranded conductor

For general visual corona:

m = 0.80 – 0.85 for weathered stranded conductor

54

3.13.3 CORONA POWER LOSS AT AC VOLTAGE

For AC transmission lines empirical equations are used to determine corona loss.

According to Peek corona power loss can be determined from:

2 5241

25 10 / LN c

r kWP f V V phase peak

D km

(3.90)

P = corona loss in kW/km/phase

δ = density correction factor

VLN = the phase or line-to-neutral voltage in kV

Vc = the critical disruptive voltage in kV

f = frequency

r = radius of the conductor in cm

D = equivalent spacing of conductors in cm.

It is desirable to design transmission line with corona loss between 0.10 and 0.21

kW/km/phase for fair weather conditions. For lower loss range i.e., when

V

1 .8 LN

cV (3.91)

Peek‟s formula is not accurate [7].

According to Peterson‟s corona power loss formula:

2

5

10

2.1 10 /cV kWP f F phase

D kmlog

r

(3.92)

F = corona loss function

55

VLN / Vc 1.0 1.2 1.4 1.5 1.6 1.8 2.0

F 0.037 0.082 0.3 0.9 2.2 4.95 7.0

Table 3.1 Corona factor [7].

Above stated formulas are used for fair weather conditions. For wet weather conditions

critical disruptive voltage is approximately 0.80 of the fair weather calculated value. The

calculated disruptive critical voltage for three-phase horizontal conductor configuration

can be determined as:

3 0.96

c c fairV V

(3.93)

for the middle conductor and

3 1.06

c c fairV V

(3.94)

for the two outer conductors [1].

3.14 METHOD OF SYMMETRICAL COMPONENTS

According to Charles Fortescue, a set of three-phase voltages are resolved into the

following three sets of sequence components:

1. Zero-sequence components: consisting of three phasors with equal magnitudes and

with zero phase displacement

2. Positive-sequence components, consisting of three phasors with equal magnitudes,

±120 phase displacement

3. Negative-sequence components, consisting of three phasors with equal magnitudes,

±120 phase displacement[1].

56

Vb0 Vc0 = V0Va0

Vc2

Vb2 Va2 = V2

Va1 = V1

Vb1

Vc1

(a) (b) (c)

Figure 3.6 Sequence components: ( a) zero ( b) positive ( c) negative [8 ]

0 1 2 a a a a V V V V (3.95)

0 1 2 b b b b V V V V (3.96)

0 1 2 c c c c V V V V (3.97)

Operator a is a complex number with unit magnitude and a 120 phase angle. When any

phasor is multiplied by a, that phasor rotates by 120 (counterclockwise).

A list of some common powers, functions and identities involving a:

Power or Function In Polar Form In Rectangular Form

a 1120 -0.5+j0.866

a2 1240=1-120 -0.5-j0.866

a3 1360=10 1.0+j0.0

a4 1120 -0.5+j0.866

1+a = -a2 160 0.5+j0.866

1- a √ -30 1.5-j0.866

1+ a2= -a 1-60 0.5-j0.866

1- a2 √ 30 1.5+j0.866

a -1 √ 150 -1.5+j0.866

a + a2 1180 -1.0+j0.0

a - a2 √ 90 0.0+j1.732

a2- a √ -90 0.0-j1.732

a2- 1 √ -150 -1.5-j0.866

1 + a + a2 0 0.0+j0.0

ja 1210 -0.884+j0.468

Table 3.2 Power and functions of operator a [1].

57

1 120 a (3.98)

1 3

1 1202 2

j

a (3.99)

Similarly, when any phasor is multiplied by

2 1 120 1 240 a (3.100)

the phasor rotates by 240.

The phase voltages in terms of the sequence voltages i.e. synthesis equations:

0 1 2 0a a a a V V V V (3.101)

2

0 1 2 0b a a a V a V aV V (3.102)

2

0 1 2 0c a a a V aV a V V (3.103)

The sequence voltages in terms of phase voltages i.e. analysis equations:

0

1

3a a b c V V V V (3.104)

2

1

1

3a a b c V V aV a V (3.105)

2

2

1

3a a b c V V a V aV (3.106)

In matrix form the phase voltages can be expressed as

0

2

1

2

2

1 1 1

1

1

a a

b a

c a

V V

V a a V

V a a V

(3.107)

58

and the sequence voltages can be expressed as

0

2

1

2

2

1 1 11

13

1

a a

a b

a c

V V

V a a V

V a a V

(3.108)

or

012abc V A V (3.109)

1

012 abc

V A V (3.110)

where

2

2

1 1 1

1

1

A a a

a a

(3.111)

1 2

2

1 1 11

13

1

A a a

a a

(3.112)

Similarly, the phase currents in matrix form can be expressed as

0

2

1

2

2

1 1 1

1

1

a a

b a

c a

I I

I a a I

I a a I

(3.113)

and the sequence currents can be expressed as

0

2

1

2

2

1 1 11

13

1

a a

a b

a c

I I

I a a I

I a a I

(3.114)

59

or

012abc I A I (3.115)

1

012 abc

I A I (3.116)

3.14.1 SEQUENCE IMPEDANCES OF TRANSPOSED LINES

In order to attain equal mutual impedances the line should be transposed or conductors

should have equilateral spacings.

Hence, for the equal mutual impedances

ab bc ca m Z Z Z Z (3.117)

In case when the self-impedances of conductors are equal to each other

aa bb cc s Z Z Z Z . (3.118)

Therefore,

s m m

abc m s m

m m s

Z Z Z

Z Z Z Z

Z Z Z

(3.119)

where,

0.1213ln es a e

s

Dr r j l

D

Z Ω (3.120)

and

0.1213ln em e

eq

Dr j l

D

Z Ω. (3.121)

ra = resistance of a single conductor a

60

re = resistance of Carson‟s equivalent earth return conductor which is a function of

frequency

31.588 10er f

. (3.122)

At 60 Hz,

0.09528er

(3.123)

At 60 Hz frequency and for 100

average earth resistivity

2788.55eD ft. (3.124)

The equilateral spacings of the conductors can be calculated as

3eq m ab bc caD D D D D (3.125)

The Ds is geometric mean radius (GMR) of the phase conductor.

The sequence impedance matrix of a transposed transmission line can be expressed as

012

2 0 0

0 0

0 0

s m

s m

s m

Z Z

Z Z Z

Z Z

(3.126)

where, by definition,

Z0 is zero-sequence impedance at 60Hz

0 00 2s mZ Z = Z Z (3.127)

3

0 23 0.1213ln e

a e

s eq

Dr r j l

D D

Z Ω, (3.128)

61

Z1 is positive-sequence impedance at 60Hz

1 11 s m-Z Z = Z Z (3.129)

1 0.1213lneq

a

s

Dr j l

D

Z Ω, (3.130)

Z2 is negative-sequence impedance at 60Hz

2 22 s m-Z Z = Z Z (3.131)

2 0.1213lneq

a

s

Dr j l

D

Z Ω. (3.132)

Therefore, the sequence impedance matrix of a transposed transmission line can be

expressed as

0

012 1

2

0 0

0

0 0

Z

Z Z

Z

(3.133)

3.15 FAULT ANALYSIS

Three-phase faults can be balanced (i.e., symmetrical) or unbalanced (i.e.,

unsymmetrical). The unbalanced faults are more common. In order to resolve an

unbalanced system the method of symmetrical components can be applied by converting

the system into positive, negative and the zero-sequence fictitious networks. After

defining positive, negative and zero-sequence currents for specific fault phase currents,

sequence and phase voltages can calculated.

62

3.16 PER UNIT

Power, current, voltage, and impedance are often expressed in per-unit or percent of

specified base values.

The per-unit values are calculated as:

-

actual quantity

per unit quantitybasevalueof quantity

(3.134)

where actual quantity is the value of the quantity in the actual units and the base value

has the same units as the actual quantity, forcing the per-unit quantity to be

dimensionless. The actual value may be complex but the base value is always a real

number. Consequently, the angle of the per-unit value is the same as the angle of the

actual value [8] .

In a given power system two independent base values can be arbitrarily selected at one

point. Typically the base complex power Sbase1Φ and the base voltage VbaseLN are chosen

for either a single-phase circuit or for one phase of a three-phase circuit. In order to

preserve electrical laws in the per-unit system, the following equations must be used for

other base values:

1 1 1 base base baseP Q S (3.135)

11

basebase

baseLN

SI

V

(3.136)

2

1

baseLN baseLNbase base base

base base

V VR X

I SZ

(3.137)

1

base base base

base

Y G BZ

(3.138)

63

2

basebase

base

kVZ

MVA (3.139)

( )

3

basebase

base LL

MVAI

kV (3.140)

The subscripts LN and 1Φ represent “line-to-neutral” and “per-phase” respectively, for

three-phase circuits. Equations (2.35) and (2.36) are also effective for single-phase

circuits by omitting the subscripts.

By agreement, the following two rules for base quantities are assumed:

1) The value of Sbase1Φ is the same for the entire power system

2) The ratio of the voltage bases on either side of a transformer is selected to be the

same as the ratio of the transformer voltage ratings.

As a result per-unit impedance remains unchanged when referred from one side of a

transformer to the other [8].

3.17 SINGLE LINE-TO-GROUND (SLG) FAULT

An SLG fault generally occurs when one phase conductor either falls to the ground or

makes contact with the neutral wire. Figure 3.7 depicts the typical representation of an

SLG fault at a fault point F with a fault impedance Zf. It is customary to show the fault

occurring on phase a. If the fault actually takes place on another phase, the phases of the

system can simply be relabeled in the appropriate sequence.

64

(a)

(b)

Figure 3.7 Single line-to-ground fault: (a) general representation; (b) sequence network

connection [1]

From inspection of Figure 3.7a, the currents for phases b and c are

0bf cf I I (3.141)

Zf

a

b

c

n

F

+Vaf

-

Ibf = 0Iaf Icf = 0

F0Z0 N0

+ VA0 -

F1Z1 N1

+ VA1 -

F2Z2 N2

+ VA2 -

1.0 + -

0o

3ZfIa1

Ia1Ia0 Ia2

Zero-sequencenetwork

Positive-sequencenetwork

Negative-sequencenetwork

65

Substituting values into Equation (3.114), the symmetrical components for

the currents are given as

0

2

1

2

2

1 1 11

1 03

1 0

a af

a

a

a a

a a

I I

I

I

(3.142)

Using the above equation, the sequence currents for phase a are

0 1 2

1

3a a a af I I I I (3.143)

and can be rewritten as

0 1 23 3 3 af a a a I I I I (3.144)

By inspection of Figure 3.7b, the zero-, positive-, and negative-sequence currents are

equal and can be determined by

0 1 2

0 1 2

1.0 0

3a a a

f

I I I

Z Z Z Z (3.145)

Substituting (3.145) into Equation (3.144) gives

0 1 2

1.0 03

3af

f

IZ Z Z Z

(3.146)

With the sequence current values, Equation (3.155) can be used to find the sequence

voltages, and then Equation (3.107) can be used to find the phase voltages.

66

3.18 LINE-TO-LINE (L-L) FAULT

A line-to-line (L-L) fault occurs when two conductors are short-circuited. Figure 3.8a

represents the characteristic representation of a L-L fault at a fault point F with a fault

impedance Zf. Figure 3.8b indicates the interconnection of resulting sequence networks.

It is presumed that L-L fault is between phases b and c.

(a)

(b)

Figure 3.8 Line-to-line fault: (a) general representation; (b) sequence network connection [1].

a

b

c

F

Ibf Iaf=0 Icf = -Ibf

Zf

F0

Z0

N0

+VA0 = 0

-

F1

Z1

N1

+VA1

-

F2

Z2

N2

+VA2

-+

1.0-

0o

Ia1Ia0=0 Ia2

Zf

67

It can be seen from Figure 3.8a that

0af I (3.147)

bf cf I I (3.148)

bc b c f bf V V V Z I (3.149)

In the same way from Figure 3.8b

0 0a I (3.150)

1 2

1 2

1.0 0a a

f

I I

Z Z Z

(3.151)

If Zf=0

1 2

1 2

1.0 0a aI I

Z Z (3.152)

0

2

1

2

2

1 1 1

1

1

af a

b a

a

f

cf

a a

a a

I I

I I

I I

(3.153)

The faults currents for phases a and b can be found as

13 90bf cf a I I I (3.154)

The sequence voltages can be found as

0 0 0

1 1 1

2 2 2

0 0 0

1 0 0 0

0 0 0

a a

a a

a a

V Z I

V Z I

V Z I

(3.155)

0 0a V (3.156)

68

1 1 11 0a a V Z I (3.157)

2 2 2 2 1a a a V Z I Z I (3.158)

0

2

1

2

2

1 1 1

1

1

af a

bf a

cf a

V V

V a a V

V a a V

(3.159)

1 2af a a V V V (3.160)

2 2 11.0af a V I Z Z (3.161)

2

1 2bf a a V a V aV (3.162)

2 2

1 2 1bf a V a I aZ a Z (3.163)

2

1 2cf a a V aV a V (3.164)

2

1 2 1cf a V a I a Z aZ (3.165)

Thus, the L-L voltages can be specified as

ab af bf-V V V (3.166)

1 23 30 30ab a a V V V (3.167)

bc bf cf-V V V (3.168)

1 23 90 90bc a a V V V (3.169)

ca cf af-V V V (3.170)

1 23 150 150ca a a V V V (3.171)

69

3.19 DOUBLE LINE-TO-GROUND (DLG) FAULT

This fault is similar to an SLG fault, but involves two phase conductors. A double line-

to-ground fault takes place when two phase conductors either fall to the ground or make

contact with the neutral wire. The fault is represented as being on phases b and c. Figure

3.9 depicts the typical DLG fault at a fault point F with a fault impedance Zf and the

impedance from line to ground Zg.

From inspection of the circuit in Figure 3.9a, current and voltage equations can be written

as

0a I (3.172)

bf f g bf g cfV Z Z I Z I (3.173)

cf f g cf g bf V Z Z I Z I (3.174)

70

(a)

(b)

Figure 3.9 Double line-to-ground fault: (a) general representation; (b) sequence network

connection [1].

Zf

a

b

c

n

F

Ibf Iaf = 0 Icf

Zf

Zg

N

Ibf + Icf

F0

Z0

N0

+VA0

-

F1

Z1

N1

+VA1

-

F2

Z2

N2

+VA2

-+

1.0-

0o

Zf

Ia1Ia0Ia2

Zf +3Zg Zf

71

From Figure 3.9b, the positive-sequence current is found first by

1

2 0

1

2 0

2 0

1

0 2

1.0 0

3

3

1.0 0

3

2 3

a

f f g

f

f f g

f f g

f

f gZ

IZ Z Z Z Z

Z ZZ Z Z Z Z

Z Z Z Z ZZ Z

Z Z Z

(3.175)

Multiplying the positive-sequence current by the appropriate impedance ratios is the

direct method for dividing current between the two current paths. Thus, the zero- and

negative-sequence currents are given by

2

0 1

2 0 3

f

a a

f f g

I I

Z Z

Z Z Z Z Z (3.176)

and

0

2 1

2 0

3

3

f g

a a

f f g

I I

Z Z Z

Z Z Z Z Z (3.177)

With the sequence current values, Equation (3.113) can be used to find and phase

currents, Equation (3.155) can be used to find the sequence voltages, and then Equation

(3.107) can be used to find the phase voltages.

72

3.20 THREE-PHASE FAULT

The three-phase fault is a balanced fault that can be analyzed using symmetrical

components. The sequence networks are short-circuited and isolated from each other.

Only the positive-sequence network is considered to have internal voltage source. Figure

3.10b shows that resulting sequence networks are disconnected.

(a)

(b)

Figure 3.10 Three-phase fault: (a) general representation; (b) sequence network [1].

Zf

a

b

c

n

F

Ibf Iaf Icf

Zf

Zg

N

Iaf +Ibf + Icf = 3Ia0

Zf

F0

Z0

N0

F1

Z1

N1

+VA1

-

F2

Z2

N2

+VA2

-+

1.0-

0o

Zf

Ia1Ia0Ia2

Zf +3Zg Zf

73

The positive-, negative-, and zero-sequence currents can be specified as

0 0a I (3.178)

2 0a I (3.179)

1

1

1.0 0a

f

I

Z Z (3.180)

If the fault impedance Zf =0

1

1

1.0 0a

I

Z (3.181)

2

1

2

1 1 1

1

1

0

0

af

a

c

b

f

f

I

I a a I

I a a

(3.182)

1

1

1.0 0af a

f

I = I

Z Z (3.183)

2

1

1

1.0 240bf a

f

I = a I

Z Z (3.184)

1

1

1.0 120cf a

f

I = aI

Z Z (3.185)

Since the sequence networks are short-circuited over their own fault impedances,

0 0a V (3.186)

1 1a f aV Z I (3.187)

2 0a V (3.188)

74

2

1

2

1 1 1

1

0

1 0

bf

af

a

cf

a a

a

V

a

V

V

V

(3.189)

1 1af a f a V V Z I (3.190)

2

1 1 240bf a f a V a V Z I (3.191)

1 1 120cf a f a V aV Z I (3.192)

Hence, the L-L voltages become

2

1 11 3 30ab af bf a f a V V V =V a Z I (3.193)

2

1 13 90bc bf cf a f a V V V =V a a Z I (3.194)

1 11 3 150ca cf af a f a V V V =V a Z I (3.195)

If Zf=0

1

1.0 0af

I =

Z (3.196)

1

1.0 240bf

I =

Z (3.197)

1

1.0 120cf

I =

Z (3.198)

0af V (3.199)

0bf V (3.200)

0cf V (3.201)

75

0 0a V (3.202)

1 0a V (3.203)

2 0a V (3.204)

76

Chapter 4

APPLICATION OF THE MATHEMATICAL MODEL

Equation Chapter (Next) Section 1

4.1 INTRODUCTION

This chapter uses the mathematical model from Chapter 3 to step through important

design calculations which validate a solution meets prescribed design criteria and enables

the selection of an optimal solution from a group of varying solutions. As mentioned in

Chapter 1, the scope of this project is to find an optimal solution from varying conductor

sizes that are configured and supported by a 3H1 wood H-frame-type structure. Figure

4.1 shows a 3H1 structure with important dimensions noted.

Figure 4.1 3H1 wood H-frame type structure [1].

Prior to writing this chapter, the optimal solution was selected by using the E.1

MATLAB program in Appendix E to expeditiously repeat the process of calculation for

3 H 1

2 6 '

2 4 ' 6 "

13

'6

0 '

77

each variation of solution. The intent of this chapter is to show one example of the

process of calculation for a solution. The given example is for the optimal solution that

was selected from the MATLAB results as the final design. The calculated results for this

example were done by calculator using the equations from Chapter 3. Due to calculator

rounding and precision, the results are not exactly the same as the MATLAB results, but

are close enough for practical purposes.

4.2 DESIGN CRITERIA

Design Parameters

Parameters Specifications Description

VLL 345 kV Line-to-line voltage

l 220 mi Transmission line length

f 60 Hz Frequency

S 100 MVA Load

p.f. 0.9 lagging Power factor

3H1 horizontal Tower

VD ≤ 5% Voltage drop

VReg ≤ 5% Voltage regulation

η ≥ 95% Efficiency

PL ≤ 5% Power loss

s ≥8.5m Vertical clearance

Table 4.1 Design parameters.

4.3 GEOMETRIC MEAN DISTANCE (GMD)

The equivalent spacing between the conductors or GMD is calculated by using Equation

(3.1) as:

312 23 31 eq mD D D D D ft Equation Section (Next)

78

3 26 26 52 eq mD D ft (4.1)

32.7579 eq mD D ft

4.4 GEOMETRIC MEAN RADIUS (GMR)

Bundled conductors were not used in the design.

4.5 INDUCTANCE AND INDUCTIVE REACTANCE

Using Equation (3.9), the average inductance per phase is

100.7411 logeq

a

s

D mHL

D mi

10

32.75790.7411 log

0.0304

(4.2)

2.2473mH

mi

Equation (3.11) is used to find the inductive reactance, as follows,

0.1213 lneq

L

s

DX

D

32.7579

0.1213 ln0.0304

(4.3)

0.8470 perphasemi

79

Using the inductive reactance value, the line impedance per mile is found by

Lz r jx

0.216 0.847 0j perphasemi

(4.4)

Therefore, the total impedance of the line per phase is calculated as

0.216 0.8470 (220 )zl j mimi

Z

47.52 186.34 j (4.5)

o=192.3038 75.69

4.6 CAPACITANCE AND CAPACITIVE REACTANCE

Given Equation (3.12), the average line-to-neutral capacitance per phase is found as

10

0.0388

log

N

eq

CD

r

10

0.0388

32.7579log

0.883

2 1

2

(4.6)

0.0132 F

mi

to neutral.

The capacitive reactance is found by applying Equation (3.15), as follows,

100.06836 logeq

C

DX

r

80

10

32.7579 0.06836 log

0.883

2 12

(4.7)

0.2016 M mi (4.8)

Using the capacitive reactance, the line admittance is determined as

1

C

C

y jb jx

6

1

0.2016 10j

(4.9)

64.9603 10S

mij

Multiplying by the 220 mile line length gives the total line impedance as

64.9603 10 (220 )S

Y j mimi

0.0010927j S (4.10)

0.0010927 90 S

4.7 LONG LINE CHARACTERISTICS

Per Equation (3.29), the characteristic impedance of the line is

C

zZ

y

6

0.216 0.8470

4.9603 10

j

j

(4.11)

81

416.52 52.27j

419.79 7.15

The characteristic admittance is

C

yY

z

64.9603 10

0.216 0.8470

j

j

(4.12)

0.0023636 0.0002966j

0.0023636 7.15

Using Equation (3.26), the propagation constant is found by

zy

60.216 0.8470 4.9603 10 j j (4.13)

0.00025929 0.0020 606 6j per mile

4.8 ABCD CONSTANTS

Multiplying γ by the line length gives

0.00025929 0.00206606 220l j (4.14)

0.057044 0.454533j

From Equations (3.41) through (3.44), the ABCD constants are determined by

coshA l

82

cosh 0.057044 0.454533j (4.15)

0.8999 0.0251j

0.9003 1.60

sinhCB Z l

(416.52 52.27) sinh 0.057044 0.454533j j (4.16)

44.3453 180.4874j

185.8554 76.20

sinhCC Y l

(0.00236 0.000297) sinh 0.057044 0.454533j j (4.17)

6 9.2266 10 0.0011j

0.00105466 90.50

and

coshD A l

0.8999 0.0251j (4.18)

0.9003 1.60

83

4.9 SENDING-END VOLTAGE AND CURRENT

To find the sending-end voltage and current, Equation (3.40) can be used once the

receiving end line-to-neutral voltage and current is determined. From Equation (3.50),

the receiving end line-to-neutral voltage is calculated by

( )

3

R L L

R L N

VV

3345 10 0

3

(4.19)

199.186 0 kV

Using Equation (3.51), the receiving end current is

( )3

R

R L L

S

IV

6

3

100 10

3(345 10 )

(4.20)

167 9 .347 A

Since the design criteria defines the receiving end power factor as 0.9, and the magnitude

of receiving end current was just found, Equation (3.52) gives the receiving end current

phasor as

(cos sin )R R R Rj I I

167.3479(cos25.84 sin 25.84 )j (4.21)

150.6132 72. 4 9 02j A

167.346 25.84 A

84

The sending end voltage is found from Equation (3.53) as

( ) ( ) ( )S L N RR L N V A V B I

(0.9003 1.60 199186 0 ) (185.8554 76.20 167.346 25.84 ) (4.22)

201.194 8.28 kV

The sending end current is found from Equation (3.54) as

( ) ( )S RR L N I C V D I

(0.00105466 90.50 199186 0 ) (0.9003 1.60 167.346 25.84 ) (4.23)

200.845 47.56

From Equation (3.55), the conversion to sending end line-to-line voltage is

( ) 3 1 30S L L S L N V V

3(201.194 8.28 ) 1 30 (4.24)

348.487 38.28 kV (4.25)

Given the calculated voltages at both the sending and receiving ends, the voltage drop

satisfies the requirement of 5% or less.

4.10 POWER LOSS

For the sending-end, the power factor is determined from Equation (3.56) as

cos( ) cos SS

S I SV L Npf

cos(8.28 47.56 ) cos( 39.28 ) (4.26)

0.7741 lagging.

85

Then, using the value of , equation (3.57) gives the real power at the sending-end as

( )33 cosS L L S SS

P V I

33(348.487 10 )(200.845)(0.7741) (4.27)

93.83904 MW

Similarly, Equation (3.58) gives the receiving-end real power as

( )33 cosR L L R RR

P V I

33(345 10 )(167.346)(0.9) (4.28)

89.99898 MW

Using the calculated values from the above equations, and Equation (3.59), real power

loss in the line is found by

(3 ) (3 ) (3 )L S RP P P

93.83904 89. 8 9989 (4.29)

3.84006 MW (4.30)

The percent power loss can be found by

(3 )

(3 )

(3 )

% 100L

L

S

PP

P

3.84006

10093.83904

(4.31)

4.09%

Calculated power loss satisfies the requirement of 5% or less.

86

4.11 PERCENT VOLTAGE REGULATION

Using Equation (3.63), the voltage regulation of the line is

R,NL R,FL

R,FL

| |Percent VR 1 00

| |

V V

V

3 3

3

201.194 10 199.186 10 1 00

199.186 10

(4.32)

1.008%

Calculated percent voltage regulation satisfies the requirement of 5% or less.

4.12 TRANSMISSION LINE EFFICIENCY

Transmission line efficiency is calculated by using Equation (3.60):

100 %R

S

P

P

7

7

9.0000 10100

9.3818 10

(4.33)

95.9309%

95.93% 95.00%calc req (4.34)

Calculated transmission line efficiency satisfies the requirement of 95% and above.

87

4.13 SURGE IMPEDANCE LOADING (SIL)

Using the calculated values for and in Equation (3.65), the characteristic

impedance is

C C LZ X X

60.2016 10 0.8470 (4.35)

413.23 Ω

Using the characteristic impedance value above with Equation (3.66), the surge

impedance loading (SIL) is

2

r(L L)

c

| kV |SIL

Z

2(345)

413.23

(4.36)

288.04 MW

4.14 SAG AND TENSION

4.14.1 CATENARY METHOD

Due to diverse ground relief of the TL the value of the approximate span between two

towers at the maximum sagging point is assumed to be:

700 spanL ft

Similarly, the minimum tension at the maximum sag point is assumed as:

3000 H lb

88

The weight of the ACSR 477 000 kcmil 30 strand conductor from Appendix A.1 is:

3933 0.74489lb lb

wmi ft

The catenary constant is calculated from Equation. (3.71)

H

cw

3000 3000

4027.5

3933 0.74489

lb lbc ft

lb lb

mi ft

(4.37)

cosh 12

spLd c

c

700

4027.5 cosh 12 4027.5

ftd ft

ft

(4.38)

15.218 d ft

Since a 3H1 wood H-frame-type structure has been used the distance from the ground to

the insulator is approximated as 60 ft. The phase to ground clearance can be calculated as

follows:

PhasetoGround Clearance Tower hight sag (4.39)

60 15.218 PhasetoGround Clearance ft ft

44.782 ft

Conductor tension by using catenary method from Equation (3.67) is:

( )maxT w c d

0.74489 (4027.5 0.74489 )max

lb lbT ft

ft ft (4.40)

89

3011.3 lb

From Equation (3.69):

minT w c

0.74489 4027.5 min

lbT ft

ft (4.41)

3000.0 lb

4.14.2 PARABOLIC METHOD

Approximate value of tension by using parabolic method:

2

8

sp

app

w LT lb

d

2 0.74489 700

8 15.218 app

lbft

ftT

ft

(4.42)

2998.1 lb

4.15 CORONA POWER LOSS

4.15.1 CRITICAL CORONA DISRUPTIVE VOLTAGE

The maximum stress on the surface of the conductor is given by Equation (3.78)

ln

LNmax

V kVE

D cmm r

r

90

3199.1858 10

998.462

0.9 1.1214 ln1.1214

2max

kVE

c

V

cm

cm

mcm

(4.43)

29.0590maxE kV

cm (4.44)

Mean voltage gradient can be calculated from Equation 3.79:

ln 3

LNmean

V kVE

D cmm r

r

3199.1858 10

998.4622

0.9 1.1214 ln 31.1214

mean

V

cm

cm

kVE

cmcm

(4.45)

16. 77 7 2mean

kVE

cm

The air density correction factor is calculated from Equation (3.80) as

3.9211

273

p

t

3.9211 76

273 25

cmHg

C

(4.46)

1.00

The critical disruptive voltage (corona inception voltage) Vc is calculated from Equations

(3.81) and (3.82) as

30 c c

DV m r ln kV peak

r

998.4622

0.91.121

30 1.00 1.1214 4

cV ln kV peak

(4.47)

91

205.6359 cV kV peak

21.1 c c

DV m r ln kV rms

r

998.4622

0.91.1214

21.1 1.00 1.1214 cV ln kV rms

(4.48)

14 4.63 06cV kV rms

The critical disruptive voltage Vc line-to-line is found from Equation (3.83) as

( ) ( )3 c L L c rmsV V kV

( ) 3 1 44.6306 c L LV kV (4.49)

( ) 250.5075 c L LV kV

4.15.2 VISUAL CORONA DISRUPTIVE VOLTAGE

The visual critical voltage Vv can be calculated from Equations (3.83) and (3.84)

0.301

30 1 v

DV m r ln kV peak

rr

0.9

998.4

0.30130 1.

622

1.1214

00 11.00 1.1214

1.1214

vV

ln kV peak

(4.50)

264.0859 vV kV peak

0.301

21.1 1 v

DV m r ln kV rms

rr

92

0.30121.1 1.00 1

1.00 1.1214

1.1214

0.9

998.4622

1.1 14

2

vV

ln kV rms

(4.51)

185.7404 vV kV rms

4.15.3 CORONA POWER LOSS AT AC VOLTAGE

According to Peek corona power loss can be determined from Equation (3.85)

2 5241

25 10 / LN c

r kWP f V V phase peak

D km

2 5

24160 25

199.1858 144.6306 10 /

1.1214

1.00 998.4622P

kWphase peak

km

(4.52)

20.4330 / kW

P phase peakkm

Corona power loss for 3-phase is

3 3P P (4.53)

3 3 20.4330P

kWpeak

km (4.54)

3 61.2990P

kWpeak

km

Total loss for 220 mi or 354.0557 km long TL is

3 3totalP l P kW peak (4.55)

93

3 354.0557 61.2990totalP kW peak (4.56)

3

3 21.703 10totalP kW peak

According to Peterson‟s corona power loss can be found from Equation (3.87) as

2

5

10

2.1 10 /cV kWP f F phase

D kmlog

r

2

5

10

144

998.4622

1.121

.63062.1 60 0.4566 10

4

/kW

P phasekm

log

(4.57)

1.3833 /kW

P phasekm

From Equation (4.53) corona power loss for 3-phase is

3 3P P

3 1.3833 3km

PkW

(4.58)

3 4.1498 PkW

km

According to Peterson‟s total loss for 220 mi or 354.0557 km long TL using Equation

(4.55) is

3 3totalP l P kW peak

3 354.0557 4.1498totalP kW peak (4.59)

3

3 1.4693 10totalP kW peak

94

4.15.4 CORONA POWER LOSS FOR FOUL WEATHER CONDITIONS

On the occasion of foul weather conditions for three-phase horizontal line a middle

conductor disruptive critical voltage value should be multiplied by 90% of fair weather

disruptive critical voltage and two outside conductors by 106%.

14 4.63 06cV kV rms

( ) 0.96 c cmiddle VV kV rms (4.60)

( ) 0.96 144. 630 6c middleV kV rms

( ) 138.850 0 c middleV kV rms

( ) 1. 06 cc outerV kV msV r (4.61)

( ) 1.06 144.6 306 c outerV kV rms

( ) 153.310 0 c outerV kV rms

Using Peeks‟ formula Equation (3.85)

2 5

24160 25

199.1858 138.8500 10 /

1.1214

1.00 998.4622middleP

kWphase peak

km

(4.62)

24.9960 / middle

kWP phase peak

km

2 5

24160 25

199.1858 153.3100 10 /

1

.1214

1.00 998.4622outerP

kWphase peak

km

(4.63)

95

14.4490 / outer

kWP phase peak

km

3 2 middle outer

kWP P P peak

km (4.64)

3 24.9960 2 14.4490 kW

P peakkm

(4.65)

3 53.8950 kW

P peakkm

3 ( ) 3 line

kWP l P peak

km (4.66)

3 ( ) 354.0557 53.8950 line

kWP peak

km (4.67)

3

3 ( ) 1 9.0820 10 line

kWP peak

km

It can be confirmed from the above obtained results that Peek‟s formula provides

inaccurate results. For that reason it is not valid for lower loss range when

1.8ph

c

V

V (4.68)

For wet weather conditions using Peterson‟s formula Equation (3.87)

critical disruptive voltage is taken as approximately 80% of the fair weather value.

0.8 0 ccV kV sV rm (4.69)

0.80 144.6306 cV kV rms (4.70)

11 5.70 00cV kV rms

96

199.1858

1.7215115.7000

LN

c

V

V (4.71)

For this ratio using Table 3.1 by interpolation F is found to be 4.7107. Hence,

2

5

10

998.4622

1.121

144.59282.1 60 4.7107 10 /

4

kWP phase

kmlog

(4.72)

14.2640 /kW

P phasekm

From Equation (4.53) corona power loss for 3-phase is

3 3P P

3 14.2640 3km

PkW

(4.73)

3 42.7910 PkW

km

According to Peterson‟s total loss for 220 mi or 354.0557 km long TL using Equation

(4.55) is

3 3totalP l P kW peak

3 354.0557 42.7910totalP kW peak (4.74)

3

3 15.1500 10totalP kW peak

97

4.16 PER UNIT

In this case per-unit system will be used for TL fault analysis.

Voltage base is nominated as

345baseV kV (4.75)

Apparent power base is selected to be

100baseS MVA (4.76)

Using Equation (3.134)

2

basebase

base

kVZ

MVA

2345

00 1

baseZ (4.77)

31 .1903 10baseZ Ω

The total impedance of the line per phase is from Equation (4.5) is

47.52 186.34 j Z

Applying Equation (3.129) impedance of the TL in per-unit can be found as

( )

( ) 3

( )

47.52 186.34

1.1903 10

TL actual

TL pu

TL base

j

ZZ

Z (4.78)

3 3

( ) 39.924 10 156.56 10TL pu j Z pu

98

4.17 FAULT ANALYSIS OUTLINE

An analysis of fault scenarios will be performed for three different locations on the line.

The three selected locations are the beginning of the line, the midpoint on the line, and

the end of the line. At each location, the four classical shunt fault scenarios will be

studied. In this chapter, as an explicit example, the fault analysis for the four fault type

scenarios occurring at the end of line location are calculated using the equations from

Chapter 3 and a calculator.

As part of this project, a MATLAB program was written for performing the fault studies.

In addition, ASPEN One-Liner was learned and used to simulate and verify the same

fault studies. In Appendix D, results from MATLAB and ASPEN One-Liner programs

for all fault scenarios at all three locations are provided.

Figure 4.2 shows the model which is used for the fault studies. All three fault locations

are marked with an „X‟.

Figure 4.2 One line diagram of power system model.

For the generator and transformer, typical values for their parameters were selected. The

synchronous generator was chosen to be a two pole turbine type. The transmission line

F F F

G 1

T 1

G e n B u s

(2 2 k V )

S e n d B u s

(3 4 5 k V )

L o a d B u s

(3 4 5 k V )

T L 1

99

parameters are the values from the final design of the transmission line, which uses a 477

kcmil conductor for each phase of the line. Table 4.2 lists the system data for the

model‟s network components.

Network

Component

MVA

Rating

Voltage

Rating

(kV)

Z 1 (pu) Z 2 (pu) Z 0 (pu) X d' Xd

G1 100 22 j0.09 j0.09 j0.03 0.15 1.2

T1 100 22/345 j0.07 j0.07 j0.07

TL1 100 345 0.0399 +

j0.1566

0.0399 +

j0.1566

0.1198 +

j0.4699

Table 4.2 System data for power system model.

Refer to the following sections for the explicit example of all fault scenarios occurring at

the end of the designed transmission line.

4.18 PROCEDURE USING SYMMETRICAL COMPONENTS

Symmetrical component method is generally used for analysis of the unbalanced systems.

Three-phase unbalanced systems can be separated into three balanced phasor systems:

1) Positive –sequence system

2) Negative – sequence system

3) Zero–sequence system

When applying symmetrical component concise procedure can be itemized as follows

1) Phase a is chosen to be the reference phase

2) Using synthesis (3.102) and analysis (3.103) equations find phase and sequence

voltages

100

3) Likewise, the phase and sequence currents can be found from Equations (3.108)

and (3.109) in matrix form.

4.19 FAULT ANALYSIS AT THE END OF TRANSMISSION LINE

This section will step through the calculations which provide an analysis of fault

scenarios occurring at the end of the transmission line. Figure 4.3 shows the one liner

system model with the fault location.

Figure 4.3 Power system model with fault at end of line.

A fault study on the system is started by resolving the system of network components

into three equivalent sequence impedances. It should be noted that only the portion of

line impedance involved with the fault is added as part of the equivalent sequence

impedances. In this case, since the fault is located at the end of the transmission line, the

impedance of the entire line is involved with the fault. Figure 4.4 below gives the

simplified sequence networks using the equivalent sequence impedances for the system

model when the fault is located at the end of the line.

F

G 1

T 1

G e n B u s

(2 2 k V )

S e n d B u s

(3 4 5 k V )

L o a d B u s

(3 4 5 k V )

T L 1

101

Figure 4.4 Equivalent sequence networks: (a) positive; (b) negative; (c) zero.

4.19.1 SINGLE LINE-TO-GROUND (SLG) FAULT

For a single line-to-ground fault at the receiving end of the line, the sequence network for

the fault occurring on phase a is shown in Figure 4.5 below.

F0Z0 N0

+ VA0 -

F1Z1 N1

+ VA1 -

F2Z2 N2

+ VA2 -

1.0 + -

0o

Ia1

Ia1Ia0 Ia2

0.1198 + j0.5399 pu 0.0399 + j0.3166 pu 0.0399 + j0.3166 pu

Figure 4.5 Sequence network connection for SLG fault at receiving end of line [1].

Note that and is not included in the circuit above.

0 .0 3 9 9

+ j0 .3 1 6 6 p u

F 1

N 1

+

1 .0 0 °

a ) F 2

N 2

b ) F 0

N 0

c )

Z 1 Z 2 Z 00 .0 3 9 9

+ j0 .3 1 6 6 p u

0 .1 1 9 8

+ j0 .5 3 9 9 p u

102

From Equation (3.145), the positive, negative, and zero sequence currents are equal and

found by

0 1 2

0 1 2

1.0 0

3a a a

f

I I I

Z Z Z Z

1.0 0

0.1198 0.5399 0.0399 0.3166 0.0399 0.3166 (3 0)j j j

(4.79)

0.840 80.3 pu A

From Equation (3.144), the fault current on phase a is equal to three times the positive

sequence current, and is equated by

13af aI I

3 0.840 80.3 (4.80)

2.521 80.3 pu A

Since phases b and c are not involved with the fault, as shown in figure 3.7a,

and .

With the sequence current values, Equation (3.155) can be used to find the sequence

voltages as

0 0 0

1 1 1

2 2 2

0 0 0

0 0

0 0 0

a a

a f a

a a

V Z I

V V Z I

V Z I

103

0 0.1198 0.5399 0 0

1.0 0 0 0.0399 0.3166 0

0 0 0 0.0399 0.3166

0.840 80.3

0.840 80.3

0.840 80.3

j

j

j

(4.81)

0.4645 177.19

0.7323 0.92

0.2680 177.48

pu V

With the sequence voltage values, Equation (3.107) can be used to find the phase

voltages as

0

2

1

2

2

1 1 1

1

1

af a

bf a

cf a

V V

V a a V

V a a V

1 1 1 0.4645 177.19

1 1 240 1 120 0.7323 0.92

1 1 120 1 240 0.2680 177.48

(4.82)

0.000 60.36

1.0845 129.94

1.1383 127.71

pu V

The SLG results above were verified using both MATLAB and Aspen programs to

calculate values for the same variables.

104

Table 4.3 below lists the results from both programs

SLG Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.840 -80.3 0.840 -80.3

Ia1 (pu) 0.840 -80.3 0.840 -80.3

Ia2 (pu) 0.840 -80.3 0.840 -80.3

Iaf (pu) 2.521 -80.3 2.520 -80.3

Ibf (pu) 0.000 0.000

Icf (pu) 0.000 0.000

Va0 (pu) 0.465 177.1 0.465 177.1

Va1 (pu) 0.732 -0.9 0.732 -0.9

Va2 (pu) 0.268 177.5 0.268 -177.5

Vaf (pu) 0.000 0.000

Vbf (pu) 1.084 -129.9 1.084 -130.0

Vcf (pu) 1.138 127.7 1.139 127.7

Table 4.3 Fault Analysis of SLG fault at receiving end of line.

4.19.2 LINE-TO-LINE (L-L) FAULT

Typically line-to-line (L-L) fault occurs when two conductors are short circuited. It is

assumed for the symmetric perseverance that L-L fault occurs between phases b and c.

105

Since the fault impedance is not shown in the circuit Figure 4.6 below.

F0

Z0

N0

+VA0 = 0

-

F1

Z1

N1

+VA1

-

F2

Z2

N2

+VA2

-+

1.0-

0o

Ia1Ia0=0 Ia2

Zf

0.1198+j0.5399 pu

0.0399+j0.3166 pu

0.0399+j0.3166 pu

Figure 4.6 Sequence network connection for L-L fault at receiving end of line [1]

From Equations (3.146) and (3.147) the sequence currents at the receiving end of the line

are

0 0a I

1 2

1 2

1.0 0a a

f

I I

Z Z Z

0 0a I pu (4.83)

10.0399 0.3166 0.03

1.0 0

99 0.3166 (3 0)a

j j

I (4.84)

1 1.5669 82.8171a I

106

2 1.5669 97.1829a I (4.85)

Using above calculated values and Equation (3.149) the phase currents are

0

2

1

2

2

1 1 1

1

1

af a

b a

a

f

cf

a a

a a

I I

I I

I I

01 1 1

1 1 240 1 120

1 1 120 1 240

0

1.5669 82.8171

1.5669 97.1829

af

f

bf

c

I

I

I

(4.86)

0

2.7139 172.8171

2.7139 7.1 9

0

82

bf

af

cf

I

I

I

pu A (4.87)

Furthermore using the sequence currents and impedance values the sequence voltages can

be found from Equation (3.151) as

0 0 0

1 1 1

2 2 2

0 0 0

1 0 0 0

0 0 0

a a

a a

a a

V Z I

V Z I

V Z I

0

1

2

0 0.1198 0.5399 0 0

1 0 0 0

0 0 0

0.0399 0.3166

0.0399 0.3166

0 0

1.5669 82.8171

1.5669 97.1829

a

a

a

j

j

j

V

V

V

(4.88)

107

0

1

2

0 0

0.5 0

0.5 0

a

a

a

V

V

V

pu V

The phase voltage can be obtained by using above calculated values and Equation (3.155)

0

2

1

2

2

1 1 1

1

1

af a

bf a

cf a

V V

V a a V

V a a V

01 1 1

1 1 240 1 120

1 1 120 1 2

0

0.5 0

0.540 0

af

bf

cf

V

V

V

(4.89)

0

0.5 180

0.

0

5 180

af

bf

cf

V

V

V

pu V

The L-L results were confirmed using MATLAB and Aspen programs to calculate values

for the same variables.

108

Table 4.4 below lists the results obtained by these programs

L-L Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 1.567 -82.8 1.566 -82.8

Ia2 (pu) 1.567 97.2 1.566 97.2

Iaf (pu) 0.000 0.000

Ibf (pu) 2.714 -172.8 2.713 -172.8

Icf (pu) 2.714 7.2 2.713 7.2

Va0 (pu) 0.000 0.000

Va1 (pu) 0.500 0.0 0.500 0.0

Va2 (pu) 0.500 0.0 0.500 0.0

Vaf (pu) 1.000 0.0 1.000 0.0

Vbf (pu) 0.500 180.0 0.500 180.0

Vcf (pu) 0.500 180.0 0.500 180.0

Table 4.4 Fault Analysis of L-L fault at receiving end of line.

109

4.19.3 DOUBLE LINE-TO-GROUND (DLG) FAULT

For a double line-to-ground fault at the receiving end of the line, the sequence network

for the fault occurring on phases b and c is shown in Figure 4.7 below.

F0

Z0

N0

F1

Z1

N1

+VA1

-

F2

Z2

N2

+VA2

-+

1.0-

0o

Ia1Ia0Ia2

0.1198+j0.5399 pu

0.0399+j0.3166 pu

0.0399+j0.3166 pu

Figure 4.7 Sequence network connection for DLG fault at receiving end of line [1]

Because the fault impedance , and the impedance from line to ground ,

neither is shown in the circuit above.

From Equation (3.175), the positive sequence current is found by

1

2 0

1

0 2

1.0 0

3

2 3

a

f f g

f

f gZ

IZ Z Z Z Z

Z ZZ Z Z

1

1.0 0

(0.0399 0.3166) 0 (0.1198 0.5399) 0 (3 0)(0.0399 0.3166) 0

(0.1198 0.5399) (0.0399 0.3166) (2 0) (3 0)

aj j

jj j

I

1 1.9172 82.06a I pu A (4.90)

110

Using Equations (3.176) and (3.177) to multiply the positive-sequence current by the

appropriate impedance ratios is the direct method for dividing current between the two

current paths. Thus, the zero- and negative-sequence currents are given by

2

0 1

2 0 3

f

a a

f f g

Z ZI I

Z Z Z Z Z

0

(0.0399 0.3166) 0

(0.0399 0.3166) 0 (0.1198 0.5399) 0 (3 0)

(1.9172 82.06 )

a

j

j j

I

(4.91)

0 0.7022 101 .32a I pu A

and

0

2 1

2 0

3

3

f g

a a

f f g

Z Z ZI I

Z Z Z Z Z

2

(0.1198 0.5399) 0 (3 0)

(0.0399 0.3166) 0 (0.1198 0.5399) 0 (3 0)

(1.9172 82.06 )

a

j

j j

I (4.92)

2 1.2170 95 9 .9a I pu A

From Equation (3.113), the fault currents are equated by

0

2

1

2

2

1 1 1

1

1

af a

bf a

cf a

I I

I a a I

I a a I

1 1 1 0.7022 101.32

1 1 240 1 120 1.9172 82.06

1 1 120 1 240 1.2170 95.99

af

bf

cf

I

I

I

(4.93)

111

0.000 89.43

2.9811 166.55

2.8394 28.90

af

bf

cf

I

I

I

pu A

With the sequence current values, Equation (3.155) can be used to find the sequence

voltages as

0 0 0

1 1 1

2 2 2

0 0 0

0 0

0 0 0

a a

a f a

a a

V Z I

V V Z I

V Z I

0

1

2

0 0.1198 0.5399 0 0

1.0 0 0 0.0399 0.3166 0

0 0 0 0.0399 0.3166

0.7022 101.32

1.9172 82.06

1.2170 95.99

a

a

a

j

j

j

V

V

V(4.94)

0

1

2

0.3883 1.19

0.3884 1.19

0.3883 1.19

a

a

a

V

V

V

pu V

With the sequence voltage values, Equation (3.107) can be used to find the phase

voltages as

0

2

1

2

2

1 1 1

1

1

af a

bf a

cf a

V V

V a a V

V a a V

1 1 1 0.3883 1.19

1 1 240 1 120 0.3884 1.19

1 1 120 1 240 0.3883 1.19

af

bf

cf

V

V

V

(4.95)

112

1.1650 1.19

0.0000 127.58

0.0000 130.72

af

bf

cf

V

V

V

pu V

The DLG results above were verified using both MATLAB and Aspen programs to

calculate values for the same variables. Table 4.5 below lists the results from both

programs.

DLG Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.702 101.3 0.702 101.3

Ia1 (pu) 1.917 -82.1 1.916 -82.1

Ia2 (pu) 1.217 96.0 1.216 96.0

Iaf (pu) 0.000 0.000

Ibf (pu) 2.981 166.5 2.980 166.6

Icf (pu) 2.839 28.9 2.838 28.9

Va0 (pu) 0.388 -1.2 0.388 -1.2

Va1 (pu) 0.388 -1.2 0.388 -1.2

Va2 (pu) 0.388 -1.2 0.388 -1.2

Vaf (pu) 1.165 -1.2 1.165 -1.2

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

Table 4.5 Fault Analysis of DLG fault at receiving end of line.

113

4.19.4 THREE LINE-TO-GROUND (3LG) FAULT

Three-phase fault is a balanced fault. The sequence networks are isolated from each other

because they are short-circuited through their individual fault impedances.

F0

Z0

N0

+VA0

-

F1

Z1

N1

+VA1

-

F2

Z2

N2

+VA2

-+

1.0-

0o

Zf

Ia1Ia0Ia2

Zf +3Zg Zf

0.1198+j0.5399 pu

0.0399+j0.3166 pu

0.0399+j0.3166 pu

Figure 4.8 Sequence network connection for 3LG fault at receiving end of line [1].

The negative - and zero-sequence networks do not have internal voltage sources therefore

they do not generate any currents. Hence, Equations (3.174)-(3.177) can be applied

0 0a I

0 0a I pu A (4.96)

2 0a I

2 0a I pu A (4.97)

1

1

1.0 0a

f

I

Z Z

Since the fault impedance Zf =0 the 3LG fault current is calculated from

114

1

1

1.0 0a

I

Z.

1

1.0 0

0.399 0.3166a

j

I (4.98)

1 3.1338 82.8171a I pu A

Using above calculated values and Equation (3.149) the phase currents are

0

2

1

2

2

1 1 1

1

1

af a

b a

a

f

cf

a a

a a

I I

I I

I I

01 1 1

1 1 240 1 120

1 1 120 1 240 0

0

3.1338 82.8171

0

af

c

bf

f

I

I

I

(4.99)

3.1338 82.8171

3.1338 157.1829

3.1338 37.1829

af

f

bf

c

I

I

I

pu A

Additionally using the above calculated results for sequence currents and impedance the

sequence voltages can be found from Equation (3.151) as

0 0 0

1 1 1

2 2 2

0 0 0

1 0 0 0

0 0 0

a a

a a

a a

V Z I

V Z I

V Z I

115

0

1

2

0.0399 0.3166

0.03

0 0.1198 0.5399 0 0

1 0 0

99 0

0

0 0 0

0

3.1338 82.8

.31

0

1 1

0

6

7

6

0

a

a

a

j

j

j

V

V

V

(4.100)

0

1

2

0

0 0

0 0

0a

a

a

V

V

V

pu V

The phase voltage can be found by using above calculated outcomes and Equation

(3.155)

0

2

1

2

2

1 1 1

1

1

af a

bf a

cf a

V V

V a a V

V a a V

01 1 1

1 1 240 1 120

1 1 120 1 24

0

0 0

00 0

af

bf

cf

V

V

V

(4.101)

0

0 0

0

0

0

af

bf

cf

V

V

V

pu V

The 3LG results were confirmed by using MATLAB and Aspen programs for the same

variables.

116

Table 4.6 below lists the results obtained by these programs.

3LG Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 3.134 -82.8 3.132 -82.8

Ia2 (pu) 0.000 0.000

Iaf (pu) 3.134 -82.8 3.132 -82.8

Ibf (pu) 3.134 157.2 3.132 157.2

Icf (pu) 3.134 37.2 3.132 37.2

Va0 (pu) 0.000 0.000

Va1 (pu) 0.000 0.000

Va2 (pu) 0.000 0.000

Vaf (pu) 0.000 0.000

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

Table 4.6 Fault Analysis of 3LG fault at receiving end of line.

117

Chapter 5

CONCLUSIONS

The goal of this project was to design an overhead transmission line that fulfills the

prescribed design criteria. To simplify the exercise, a line configuration for spacing

between phase conductors was predefined by selecting a standard support structure that

would be used throughout the design process, and for the final solution. A 3H1 wood H-

frame-type structure was selected. Only ACSR conductors were considered for the

design. ACSR conductors are one of the most commonly used types, providing good

strength for a 220-mile long transmission line. The design options included different

ACSR conductor sizes supported by the 3H1 structure. The process of design analysis

was developed to determine and compare the performance of each design option. The

design calculations are based on the requirement of the transmission line being

completely transposed. A MATLAB program was written to efficiently and accurately

perform the many calculations for analysis of all options considered. Fourteen different

design options were analyzed. The results from the analysis of each design option are

given in Appendix E.2. From the group of design options that met the design criteria, a

final design was selected based primarily on tradeoffs between the following factors: cost

of conductor size, capacity for future load growth, and margin to maintain performance

criteria if the load decreases slightly due to load fluctuations. The final design used the

predefined 3H1 wood H-frame-type structure with ACSR 477 kcmil conductors. The

electrical performance of this solution met the design requirements for transmission line

118

efficiency, power loss, and voltage regulation. The mechanical performance of this

solution met the design requirements for sag and tension. Per the calculated SIL, the

design can easily handle the load criteria of 90 MW, which is significantly less than the

practical loadability limit of the line. Power loss due to corona at fair and foul weather

conditions is satisfactory. A fault study was done for the final solution to show the

system exposure to voltage and current during typical fault events. A MATLAB program

was written to efficiently and accurately perform the many calculations required for fault

analysis. In addition, ASPEN One-Liner software was used to simulate the same fault

conditions. Twelve combinations of fault conditions, between four fault types and three

fault locations, were evaluated. The results from the fault study are given in Chapter 4

and Appendices C and D.

119

APPENDIX A

Conductor and Tower Characteristics

A.1 ACSR CHARACTERISTICS

Circular

Mills

Aluminum Steel

Frequency

[Hz]

Outside

Diameter

[in]

Weight

[lb/mi] Strands Layers

Strand

Diameter

[in]

Strands

Strand

Diameter

[in]

477000 30 2 0.1261 7 0.1261 60 0.883 3933

Geometric

Mean

Radius Ds

[ft]

Resistance

r

[Ω/mi]

at 50C

Inductive

Reactance xa

at 1ft spacings

[Ω/cond./mi]

Shunt Capacitive

Reactance

at 1ft spacings

[MΩmi/cond.]

Inductive

Reactance

Spacing Factor

Xd

[Ω/cond./mi]

Shunt

Capacitive

Reactance

Spacing Factor

[MΩ/cond.

mi]

0.0304 0.216 0.424 0.0980 0.42337 0.1035

A.2 STRUCTURE CHARACTERISTICS

Material Type

Average

Number

per mile

Average

Weight per

structure

[lb]

Height

[ft]

Base

Width

[ft]

Conductor

Spacing

Style

Conductor

Spacing

[ft]

Steel 3H1 8 16000 73 36 Horizontal

D12=26

D23=26

D31=52

120

APPENDIX B

Aspen Simulation Model and Analysis

B.1.1 SYSTEM MODEL ONE LINE DIAGRAM

B.1.2 GENERATOR DATA

121

B.1.3 TRANSFORMER DATA

B.1.4 TRANSMISSION LINE DATA FOR FAULT ANALYSIS

122

B.1.5 TRANSMISSION LINE DATA FOR POWER FLOW ANALYSIS

B.1.6 LOAD DATA

B.2 POWER FLOW BY NEWTON-RAPHSON METHOD

123

Appendix C

Aspen Fault Analysis Summary

C.1 477kcmil SE FAULTS

===================================================================================================================================

5. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 3LG 0.50%( 0.01%)

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

6.216@ -89.9 0.000@ 0.0 0.000@ 0.0 6.216@ -89.9 6.216@ 150.1 6.216@ 30.1

THEVENIN IMPEDANCE (PU)

0.0002+j0.16084 0.0002+j0.16084 0.0006+j0.07236

SHORT CIRCUIT MVA= 621.6 X/R RATIO= 805.617 R0/X1= 0.00373 X0/X1= 0.44989

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

CURRENT TO FAULT (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 6.218@ 90.1 0.000@ 0.0 0.000@ 0.0 6.218@ 90.1 6.218@ -29.9 [email protected]

-3 #Load Bus 345. 1L 0.002@ -90.0 0.000@ 0.0 0.000@ 0.0 0.002@ -90.0 0.002@ 150.0 0.002@ 30.0

CURRENT TO FAULT (PU) > 6.216@ -89.9 0.000@ 0.0 0.000@ 0.0 6.216@ -89.9 6.216@ 150.1 6.216@ 30.1

THEVENIN IMPEDANCE (PU) > 0.16084@ 89.9 0.16084@ 89.9 0.07236@ 89.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.005@ -14.2 0.000@ 0.0 0.000@ 0.0 0.005@ -14.2 [email protected] 0.005@ 105.8

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 6.218@ -89.9 0.000@ 0.0 0.000@ 0.0 6.218@ -89.9 6.218@ 150.1 6.218@ 30.1

1 Gen Bus 22. T1T 6.220@ 90.1 0.000@ 0.0 0.000@ 0.0 6.220@ 90.1 6.220@ -29.9 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 6.218@ -89.9 0.000@ 0.0 0.000@ 0.0 6.218@ -89.9 6.218@ 150.1 6.218@ 30.1

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.005@ -14.2 0.000@ 0.0 0.000@ 0.0 0.005@ -14.2 [email protected] 0.005@ 105.8

-2 Send$1 $#Loa 345.kV 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

3Io= 0.0@ 12.2 A Va/Ia= 0.962@ 75.7 Ohm (Va-Vb)/(Ia-Ib)= 0.962@ 75.7 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

6. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 2LG 0.50%( 0.01%) Type=B-C

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

4.744@ -89.9 1.472@ 89.9 3.272@ 90.3 0.000@ 0.0 7.297@ 137.8 7.273@ 42.5

THEVENIN IMPEDANCE (PU)

0.0002+j0.16084 0.0002+j0.16084 0.0006+j0.07236

SHORT CIRCUIT MVA= 729.7 X/R RATIO= 418.232 R0/X1= 0.00373 X0/X1= 0.44989

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.237@ -0.2 0.237@ -0.2 0.237@ -0.2 0.710@ -0.2 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

124

-2 Send$1 $#Loa 345. 1L 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

CURRENT TO FAULT (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.237@ -0.2 0.237@ -0.2 0.237@ -0.2 0.710@ -0.2 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 4.746@ 90.1 1.473@ -90.1 3.272@ -89.7 0.001@ 90.5 7.299@ -42.2 [email protected]

-3 #Load Bus 345. 1L 0.002@ -89.9 0.001@ 89.8 0.001@ 89.8 0.001@ -89.5 0.002@ 150.0 0.002@ 30.0

CURRENT TO FAULT (PU) > 4.744@ -89.9 1.472@ 89.9 3.272@ 90.3 0.000@ 0.0 7.297@ 137.8 7.273@ 42.5

THEVENIN IMPEDANCE (PU) > 0.16084@ 89.9 0.16084@ 89.9 0.07236@ 89.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.240@ -0.4 0.236@ -0.1 0.229@ 0.3 0.705@ -0.1 [email protected] 0.010@ 140.8

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 4.746@ -89.9 1.473@ 89.9 3.272@ 90.3 0.001@ -89.5 7.299@ 137.8 7.275@ 42.5

1 Gen Bus 22. T1T 4.747@ 90.1 1.473@ -90.1 3.272@ -89.7 0.002@ 90.2 7.300@ -42.2 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 4.746@ -89.9 1.473@ 89.9 3.272@ 90.3 0.001@ -89.5 7.299@ 137.8 7.275@ 42.5

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.240@ -0.4 0.236@ -0.1 0.229@ 0.3 0.705@ -0.1 [email protected] 0.010@ 140.8

-2 Send$1 $#Loa 345.kV 0.237@ -0.2 0.237@ -0.2 0.237@ -0.2 0.710@ -0.2 0.000@ 0.0 0.000@ 0.0

3Io= 1642.9@ 90.3 A Va/Ia= 1.21e+006@ 89.4 Ohm (Va-Vb)/(Ia-Ib)= 117@ 42.2 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

7. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 1LG 0.50%( 0.01%) Type=A

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

2.537@ -89.9 2.537@ -89.9 2.537@ -89.9 7.612@ -89.9 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU)

0.0002+j0.16084 0.0002+j0.16084 0.0006+j0.07236

SHORT CIRCUIT MVA= 761.2 X/R RATIO= 394.638 R0/X1= 0.00373 X0/X1= 0.44989

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.592@ -0.0 [email protected] 0.184@ 179.7 0.000@ 0.0 [email protected] 0.910@ 107.6

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

CURRENT TO FAULT (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.592@ -0.1 [email protected] 0.184@ 179.7 0.000@ 0.0 [email protected] 0.910@ 107.6

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 2.538@ 90.1 2.538@ 90.1 2.538@ 90.1 7.614@ 90.1 0.001@ -89.0 0.001@ -90.2

-3 #Load Bus 345. 1L 0.001@ -89.9 0.001@ -89.9 0.000@ 0.0 0.002@ -90.0 0.001@ 91.0 0.001@ 89.8

CURRENT TO FAULT (PU) > 2.537@ -89.9 2.537@ -89.9 2.537@ -89.9 7.612@ -89.9 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU) > 0.16084@ 89.9 0.16084@ 89.9 0.07236@ 89.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.594@ -0.1 [email protected] [email protected] 0.010@ -14.2 [email protected] 0.908@ 107.4

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 2.538@ -89.9 2.538@ -89.9 2.538@ -89.9 7.614@ -89.9 0.001@ 91.0 0.001@ 89.8

1 Gen Bus 22. T1T 2.539@ 90.1 2.538@ 90.1 2.538@ 90.1 7.615@ 90.1 0.002@ -47.6 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 2.538@ -89.9 2.538@ -89.9 2.538@ -89.9 7.614@ -89.9 0.001@ 91.0 0.001@ 89.8

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.594@ -0.1 [email protected] [email protected] 0.010@ -14.2 [email protected] 0.908@ 107.4

-2 Send$1 $#Loa 345.kV 0.592@ -0.1 [email protected] 0.184@ 179.7 0.000@ 0.0 [email protected] 0.910@ 107.6

3Io= 1274.0@ -89.9 A Va/Ia= 1.6@ 75.7 Ohm (Va-Vb)/(Ia-Ib)= 142@ 161.8 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

8. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L LL 0.50%( 0.01%) Type=B-C

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

3.108@ -89.9 3.108@ 90.1 0.000@ 0.0 0.000@ 0.0 [email protected] 5.383@ 0.1

THEVENIN IMPEDANCE (PU)

0.0002+j0.16084 0.0002+j0.16084 0.0006+j0.07236

SHORT CIRCUIT MVA= 538.3 X/R RATIO= 805.617 R0/X1= 0.00373 X0/X1= 0.44989

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

125

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.500@ 0.0 0.500@ -0.0 0.000@ 0.0 1.000@ 0.0 0.500@ 180.0 [email protected]

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

CURRENT TO FAULT (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.500@ 0.0 0.500@ 0.0 0.000@ 0.0 1.000@ 0.0 [email protected] [email protected]

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 3.109@ 90.1 3.109@ -89.9 0.000@ 0.0 0.000@ 0.0 5.385@ 0.1 [email protected]

-3 #Load Bus 345. 1L 0.001@ -90.0 0.001@ 90.0 0.000@ 0.0 0.000@ 0.0 0.002@ 179.9 0.002@ 0.1

CURRENT TO FAULT (PU) > 3.108@ -89.9 3.108@ 90.1 0.000@ 0.0 0.000@ 0.0 [email protected] 5.383@ 0.1

THEVENIN IMPEDANCE (PU) > 0.16084@ 89.9 0.16084@ 89.9 0.07236@ 89.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.502@ -0.1 0.497@ 0.1 0.000@ 0.0 1.000@ 0.0 [email protected] 0.499@ 179.5

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 3.109@ -89.9 3.109@ 90.1 0.000@ 0.0 0.000@ 0.0 [email protected] 5.385@ 0.1

1 Gen Bus 22. T1T 3.110@ 90.1 3.109@ -89.9 0.000@ 0.0 0.001@ 90.0 5.386@ 0.1 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 3.109@ -89.9 3.109@ 90.1 0.000@ 0.0 0.000@ 0.0 [email protected] 5.385@ 0.1

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.502@ -0.1 0.497@ 0.1 0.000@ 0.0 1.000@ 0.0 [email protected] 0.499@ 179.5

-2 Send$1 $#Loa 345.kV 0.500@ 0.0 0.500@ 0.0 0.000@ 0.0 1.000@ 0.0 [email protected] [email protected]

3Io= 0.0@ 0.5 A Va/Ia= 1.86e+008@ 90.0 Ohm (Va-Vb)/(Ia-Ib)= 332@ 0.1 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

126

C.2 477kcmil MID FAULTS

===================================================================================================================================

5. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 3LG 50.00%

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

4.179@ -85.2 0.000@ 0.0 0.000@ 0.0 4.179@ -85.2 4.179@ 154.8 4.179@ 34.8

THEVENIN IMPEDANCE (PU)

0.01997+j0.23842 0.01997+j0.23842 0.05997+j0.30511

SHORT CIRCUIT MVA= 417.9 X/R RATIO= 11.9388 R0/X1= 0.25152 X0/X1= 1.27975

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 0.001@ 90.0 0.000@ 0.0 0.000@ 0.0 0.001@ 90.0 0.001@ -30.0 [email protected]

CURRENT TO FAULT (PU) > 0.001@ -90.0 0.000@ 0.0 0.000@ 0.0 0.001@ -90.0 0.001@ 150.0 0.001@ 30.0

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55333@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 4.181@ 94.8 0.000@ 0.0 0.000@ 0.0 4.181@ 94.8 4.181@ -25.2 [email protected]

-3 #Load Bus 345. 1L 0.002@ -90.0 0.000@ 0.0 0.000@ 0.0 0.002@ -90.0 0.002@ 150.0 0.002@ 30.0

CURRENT TO FAULT (PU) > 4.179@ -85.2 0.000@ 0.0 0.000@ 0.0 4.179@ -85.2 4.179@ 154.8 4.179@ 34.8

THEVENIN IMPEDANCE (PU) > 0.23925@ 85.2 0.23925@ 85.2 0.31095@ 78.9

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.338@ -9.5 0.000@ 0.0 0.000@ 0.0 0.338@ -9.5 [email protected] 0.338@ 110.5

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 4.181@ -85.2 0.000@ 0.0 0.000@ 0.0 4.181@ -85.2 4.181@ 154.8 4.181@ 34.8

1 Gen Bus 22. T1T 4.182@ 94.8 0.000@ 0.0 0.000@ 0.0 4.182@ 94.8 4.182@ -25.2 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 4.181@ -85.2 0.000@ 0.0 0.000@ 0.0 4.181@ -85.2 4.181@ 154.8 4.181@ 34.8

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.338@ -9.5 0.000@ 0.0 0.000@ 0.0 0.338@ -9.5 [email protected] 0.338@ 110.5

-2 Send$1 $#Loa 345.kV 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

3Io= 0.0@ 0.0 A Va/Ia= 96.2@ 75.7 Ohm (Va-Vb)/(Ia-Ib)= 96.2@ 75.7 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

6. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 2LG 50.00% Type=B-C

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

2.669@ -84.2 1.511@ 93.0 1.162@ 99.4 0.000@ 0.0 4.140@ 160.0 3.890@ 31.3

THEVENIN IMPEDANCE (PU)

0.01997+j0.23842 0.01997+j0.23842 0.05997+j0.30511

SHORT CIRCUIT MVA= 414.0 X/R RATIO= 9.87422 R0/X1= 0.25152 X0/X1= 1.27975

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.361@ -1.8 0.361@ -1.8 0.361@ -1.8 1.084@ -1.8 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 0.001@ 90.0 0.000@ 0.0 0.000@ 0.0 0.001@ 90.0 0.001@ -30.0 [email protected]

CURRENT TO FAULT (PU) > 0.001@ -90.0 0.000@ 0.0 0.000@ 0.0 0.001@ -90.0 0.001@ 150.0 0.001@ 30.0

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55333@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.361@ -1.8 0.361@ -1.8 0.361@ -1.8 1.084@ -1.8 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 2.670@ 95.8 1.511@ -87.0 1.163@ -80.6 0.000@ 0.0 4.142@ -20.0 [email protected]

-3 #Load Bus 345. 1L 0.001@ -89.4 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.002@ 150.0 0.002@ 30.0

CURRENT TO FAULT (PU) > 2.669@ -84.2 1.511@ 93.0 1.162@ 99.4 0.000@ 0.0 4.140@ 160.0 3.890@ 31.3

THEVENIN IMPEDANCE (PU) > 0.23925@ 85.2 0.23925@ 85.2 0.31095@ 78.9

-----------------------------------------------------------------------------------------------------------------------------------

127

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.576@ -4.3 0.242@ 3.0 0.081@ 9.4 0.897@ -1.1 [email protected] 0.423@ 131.4

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 2.671@ -84.2 1.512@ 93.0 1.163@ 99.4 0.001@ -82.2 4.143@ 160.0 3.892@ 31.3

1 Gen Bus 22. T1T 2.672@ 95.8 1.512@ -87.0 1.163@ -80.6 0.001@ 93.6 4.144@ -20.0 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 2.671@ -84.2 1.512@ 93.0 1.163@ 99.4 0.001@ -82.2 4.143@ 160.0 3.892@ 31.3

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.576@ -4.3 0.242@ 3.0 0.081@ 9.4 0.897@ -1.1 [email protected] 0.423@ 131.4

-2 Send$1 $#Loa 345.kV 0.361@ -1.8 0.361@ -1.8 0.361@ -1.8 1.084@ -1.8 0.000@ 0.0 0.000@ 0.0

3Io= 583.9@ 99.4 A Va/Ia= 2.09e+006@ 81.1 Ohm (Va-Vb)/(Ia-Ib)= 372@ 30.9 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

7. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 1LG 50.00% Type=A

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

1.268@ -82.7 1.268@ -82.7 1.268@ -82.7 3.805@ -82.7 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU)

0.01997+j0.23842 0.01997+j0.23842 0.05997+j0.30511

SHORT CIRCUIT MVA= 380.5 X/R RATIO= 7.8266 R0/X1= 0.25152 X0/X1= 1.27975

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.697@ -1.1 [email protected] 0.394@ 176.2 0.000@ 0.0 [email protected] 1.081@ 123.1

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 0.001@ 90.0 0.000@ 0.0 0.000@ 0.0 0.001@ 90.0 0.001@ -30.0 [email protected]

CURRENT TO FAULT (PU) > 0.001@ -90.0 0.000@ 0.0 0.000@ 0.0 0.001@ -90.0 0.001@ 150.0 0.001@ 30.0

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55333@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.697@ -1.1 [email protected] 0.394@ 176.2 0.000@ 0.0 [email protected] 1.081@ 123.1

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 1.269@ 97.3 1.269@ 97.3 1.269@ 97.3 3.807@ 97.3 0.001@ -18.7 [email protected]

-3 #Load Bus 345. 1L 0.001@ -89.1 0.000@ 0.0 0.000@ 0.0 0.002@ -90.0 0.001@ 161.3 0.001@ 22.1

CURRENT TO FAULT (PU) > 1.268@ -82.7 1.268@ -82.7 1.268@ -82.7 3.805@ -82.7 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU) > 0.23925@ 85.2 0.23925@ 85.2 0.31095@ 78.9

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.799@ -1.8 [email protected] [email protected] 0.513@ -7.0 [email protected] 0.961@ 113.7

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 1.270@ -82.7 1.269@ -82.7 1.269@ -82.7 3.807@ -82.7 0.001@ 161.1 0.000@ 0.0

1 Gen Bus 22. T1T 1.270@ 97.3 1.269@ 97.3 1.269@ 97.3 3.808@ 97.3 0.001@ -24.4 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 1.270@ -82.7 1.269@ -82.7 1.269@ -82.7 3.807@ -82.7 0.001@ 161.1 0.000@ 0.0

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.799@ -1.8 [email protected] [email protected] 0.513@ -7.0 [email protected] 0.961@ 113.7

-2 Send$1 $#Loa 345.kV 0.697@ -1.1 [email protected] 0.394@ 176.2 0.000@ 0.0 [email protected] 1.081@ 123.1

3Io= 637.1@ -82.7 A Va/Ia= 160@ 75.7 Ohm (Va-Vb)/(Ia-Ib)= 373@ 124.1 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

8. Interm. Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L LL 50.00% Type=B-C

with end opened

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

2.089@ -85.2 2.089@ 94.8 0.000@ 0.0 0.000@ 0.0 [email protected] 3.619@ 4.8

THEVENIN IMPEDANCE (PU)

0.01997+j0.23842 0.01997+j0.23842 0.05997+j0.30511

SHORT CIRCUIT MVA= 361.9 X/R RATIO= 11.9388 R0/X1= 0.25152 X0/X1= 1.27975

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

CURRENT TO FAULT (PU) > 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

THEVENIN IMPEDANCE (PU) > 1.@ 25.8 1.@ 25.8 1.@ 25.8

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.500@ 0.0 0.500@ 0.0 0.000@ 0.0 1.000@ 0.0 0.500@ 180.0 [email protected]

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 0.001@ 90.0 0.000@ 0.0 0.000@ 0.0 0.001@ 90.0 0.001@ -30.0 [email protected]

CURRENT TO FAULT (PU) > 0.001@ -90.0 0.000@ 0.0 0.000@ 0.0 0.001@ -90.0 0.001@ 150.0 0.001@ 30.0

128

THEVENIN IMPEDANCE (PU) > 0.31925@ 82.8 0.31925@ 82.8 0.55333@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS -2 Send$1 $#Loa 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.500@ 0.0 0.500@ 0.0 0.000@ 0.0 1.000@ 0.0 [email protected] [email protected]

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 2.091@ 94.8 2.090@ -85.2 0.000@ 0.0 0.001@ 90.0 3.620@ 4.8 [email protected]

-3 #Load Bus 345. 1L 0.001@ -90.0 0.001@ 90.0 0.000@ 0.0 0.001@ -90.0 0.002@ 169.1 0.002@ 10.9

CURRENT TO FAULT (PU) > 2.089@ -85.2 2.089@ 94.8 0.000@ 0.0 0.000@ 0.0 [email protected] 3.619@ 4.8

THEVENIN IMPEDANCE (PU) > 0.23925@ 85.2 0.23925@ 85.2 0.31095@ 78.9

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.667@ -2.4 0.334@ 4.8 0.000@ 0.0 1.000@ 0.0 [email protected] 0.536@ 147.4

BRANCH CURRENT (PU) TO >

-2 Send$1 $#Loa 345. 1L 2.091@ -85.2 2.090@ 94.8 0.000@ 0.0 0.001@ -90.0 [email protected] 3.621@ 4.8

1 Gen Bus 22. T1T 2.092@ 94.8 2.090@ -85.2 0.000@ 0.0 0.001@ 90.0 3.622@ 4.8 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -2 Send$1 $#Loa 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 2.091@ -85.2 2.090@ 94.8 0.000@ 0.0 0.001@ -90.0 [email protected] 3.621@ 4.8

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.667@ -2.4 0.334@ 4.8 0.000@ 0.0 1.000@ 0.0 [email protected] 0.536@ 147.4

-2 Send$1 $#Loa 345.kV 0.500@ 0.0 0.500@ 0.0 0.000@ 0.0 1.000@ 0.0 [email protected] [email protected]

3Io= 0.0@ 80.6 A Va/Ia= 2e+006@ 90.0 Ohm (Va-Vb)/(Ia-Ib)= 518@ 5.8 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

129

C.3 477kcmil RE FAULTS

===================================================================================================================================

1. Line-End Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 3LG

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

3.132@ -82.8 0.000@ 0.0 0.000@ 0.0 3.132@ -82.8 3.132@ 157.2 3.132@ 37.2

THEVENIN IMPEDANCE (PU)

0.03993+j0.31675 0.03993+j0.31675 0.11995+j0.54024

SHORT CIRCUIT MVA= 313.2 X/R RATIO= 7.93257 R0/X1= 0.37871 X0/X1= 1.70557

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 3.132@ 97.2 0.000@ 0.0 0.000@ 0.0 3.132@ 97.2 3.132@ -22.8 [email protected]

CURRENT TO FAULT (PU) > 3.132@ -82.8 0.000@ 0.0 0.000@ 0.0 3.132@ -82.8 3.132@ 157.2 3.132@ 37.2

THEVENIN IMPEDANCE (PU) > 0.31926@ 82.8 0.31926@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.506@ -7.1 0.000@ 0.0 0.000@ 0.0 0.506@ -7.1 [email protected] 0.506@ 112.9

BRANCH CURRENT (PU) TO >

-3 #Load Bus 345. 1L 3.134@ -82.8 0.000@ 0.0 0.000@ 0.0 3.134@ -82.8 3.134@ 157.2 3.134@ 37.2

1 Gen Bus 22. T1T 3.134@ 97.2 0.000@ 0.0 0.000@ 0.0 3.134@ 97.2 3.134@ -22.8 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -3 #Load Bus 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 3.134@ -82.8 0.000@ 0.0 0.000@ 0.0 3.134@ -82.8 3.134@ 157.2 3.134@ 37.2

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.506@ -7.1 0.000@ 0.0 0.000@ 0.0 0.506@ -7.1 [email protected] 0.506@ 112.9

-3 #Load Bus 345.kV 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

3Io= 0.0@ 0.0 A Va/Ia= 192@ 75.7 Ohm (Va-Vb)/(Ia-Ib)= 192@ 75.7 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

2. Line-End Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 2LG Type=B-C

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

1.916@ -82.1 1.216@ 96.0 0.702@ 101.3 0.000@ 0.0 2.980@ 166.6 2.838@ 28.9

THEVENIN IMPEDANCE (PU)

0.03993+j0.31675 0.03993+j0.31675 0.11995+j0.54024

SHORT CIRCUIT MVA= 298.0 X/R RATIO= 7.16758 R0/X1= 0.37871 X0/X1= 1.70557

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.388@ -1.2 0.388@ -1.2 0.388@ -1.2 1.165@ -1.2 0.000@ 0.0 0.000@ 0.0

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 1.916@ 97.9 1.216@ -84.0 0.702@ -78.7 0.000@ 0.0 2.980@ -13.4 [email protected]

CURRENT TO FAULT (PU) > 1.916@ -82.1 1.216@ 96.0 0.702@ 101.3 0.000@ 0.0 2.980@ 166.6 2.838@ 28.9

THEVENIN IMPEDANCE (PU) > 0.31926@ 82.8 0.31926@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.697@ -3.5 0.195@ 6.0 0.049@ 11.3 0.938@ -0.8 [email protected] 0.570@ 126.9

BRANCH CURRENT (PU) TO >

-3 #Load Bus 345. 1L 1.917@ -82.1 1.217@ 96.0 0.702@ 101.3 0.000@ 0.0 2.981@ 166.5 2.840@ 28.9

1 Gen Bus 22. T1T 1.917@ 97.9 1.217@ -84.0 0.702@ -78.7 0.000@ 0.0 2.981@ -13.5 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -3 #Load Bus 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 1.917@ -82.1 1.217@ 96.0 0.702@ 101.3 0.000@ 0.0 2.981@ 166.5 2.840@ 28.9

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.697@ -3.5 0.195@ 6.0 0.049@ 11.3 0.938@ -0.8 [email protected] 0.570@ 126.9

-3 #Load Bus 345.kV 0.388@ -1.2 0.388@ -1.2 0.388@ -1.2 1.165@ -1.2 0.000@ 0.0 0.000@ 0.0

3Io= 352.6@ 101.3 A Va/Ia= 8.59e+006@ -71.1 Ohm (Va-Vb)/(Ia-Ib)= 577@ 29.6 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

3. Line-End Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L 1LG Type=A

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

0.840@ -80.3 0.840@ -80.3 0.840@ -80.3 2.520@ -80.3 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU)

0.03993+j0.31675 0.03993+j0.31675 0.11995+j0.54024

130

SHORT CIRCUIT MVA= 252.0 X/R RATIO= 5.87412 R0/X1= 0.37871 X0/X1= 1.70557

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.732@ -0.9 [email protected] 0.465@ 177.1 0.000@ 0.0 [email protected] 1.139@ 127.7

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 0.840@ 99.7 0.840@ 99.7 0.840@ 99.7 2.520@ 99.7 0.000@ 0.0 0.000@ 0.0

CURRENT TO FAULT (PU) > 0.840@ -80.3 0.840@ -80.3 0.840@ -80.3 2.520@ -80.3 0.000@ 0.0 0.000@ 0.0

THEVENIN IMPEDANCE (PU) > 0.31926@ 82.8 0.31926@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.868@ -1.5 [email protected] [email protected] 0.679@ -4.6 [email protected] 0.976@ 115.8

BRANCH CURRENT (PU) TO >

-3 #Load Bus 345. 1L 0.840@ -80.3 0.840@ -80.3 0.841@ -80.3 2.521@ -80.3 0.000@ 0.0 0.000@ 0.0

1 Gen Bus 22. T1T 0.840@ 99.7 0.840@ 99.7 0.841@ 99.7 2.521@ 99.7 0.000@ 0.0 0.000@ 0.0

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -3 #Load Bus 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 0.840@ -80.3 0.840@ -80.3 0.841@ -80.3 2.521@ -80.3 0.000@ 0.0 0.000@ 0.0

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.868@ -1.5 [email protected] [email protected] 0.679@ -4.6 [email protected] 0.976@ 115.8

-3 #Load Bus 345.kV 0.732@ -0.9 [email protected] 0.465@ 177.1 0.000@ 0.0 [email protected] 1.139@ 127.7

3Io= 422.0@ -80.3 A Va/Ia= 321@ 75.7 Ohm (Va-Vb)/(Ia-Ib)= 643@ 116.3 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

===================================================================================================================================

4. Line-End Fault on: 2 Send Bus 345.kV - 3 Load Bus 345.kV 1L LL Type=B-C

FAULT CURRENT (PU @ DEG)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

1.566@ -82.8 1.566@ 97.2 0.000@ 0.0 0.000@ 0.0 [email protected] 2.713@ 7.2

THEVENIN IMPEDANCE (PU)

0.03993+j0.31675 0.03993+j0.31675 0.11995+j0.54024

SHORT CIRCUIT MVA= 271.3 X/R RATIO= 7.93257 R0/X1= 0.37871 X0/X1= 1.70557

-----------------------------------------------------------------------------------------------------------------------------------

BUS -3 #Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.500@ -0.0 0.500@ -0.0 0.000@ 0.0 1.000@ -0.0 0.500@ 180.0 0.500@ 180.0

BRANCH CURRENT (PU) TO >

2 Send Bus 345. 1L 1.566@ 97.2 1.566@ -82.8 0.000@ 0.0 0.000@ 0.0 2.713@ 7.2 [email protected]

CURRENT TO FAULT (PU) > 1.566@ -82.8 1.566@ 97.2 0.000@ 0.0 0.000@ 0.0 [email protected] 2.713@ 7.2

THEVENIN IMPEDANCE (PU) > 0.31926@ 82.8 0.31926@ 82.8 0.55339@ 77.5

-----------------------------------------------------------------------------------------------------------------------------------

BUS 3 Load Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

SHUNT CURRENTS (PU) >

TO LOAD 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0 0.000@ 0.0

FROM FICT. CURR. SOURCE 1.000@ -25.8 0.000@ 0.0 0.000@ 0.0 1.000@ -25.8 [email protected] 1.000@ 94.2

-----------------------------------------------------------------------------------------------------------------------------------

BUS 2 Send Bus 345.KV AREA 1 ZONE 1 TIER 0 (PREFAULT V=1.000@ 0.0 PU)

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

VOLTAGE (PU) > 0.752@ -2.4 0.251@ 7.2 0.000@ 0.0 1.000@ -0.0 [email protected] 0.623@ 135.7

BRANCH CURRENT (PU) TO >

-3 #Load Bus 345. 1L 1.567@ -82.8 1.567@ 97.2 0.000@ 0.0 0.000@ 0.0 [email protected] 2.714@ 7.2

1 Gen Bus 22. T1T 1.567@ 97.2 1.567@ -82.8 0.000@ 0.0 0.000@ 0.0 2.714@ 7.2 [email protected]

-----------------------------------------------------------------------------------------------------------------------------------

MONITORED BRANCH: 2 Send Bus 345.KV -> -3 #Load Bus 345.KV 1L

+ SEQ - SEQ 0 SEQ A PHASE B PHASE C PHASE

RELAY CURRENT (PU) 1.567@ -82.8 1.567@ 97.2 0.000@ 0.0 0.000@ 0.0 [email protected] 2.714@ 7.2

BUS VOLTAGES (PU)

2 Send Bus 345.kV 0.752@ -2.4 0.251@ 7.2 0.000@ 0.0 1.000@ -0.0 [email protected] 0.623@ 135.7

-3 #Load Bus 345.kV 0.500@ -0.0 0.500@ -0.0 0.000@ 0.0 1.000@ -0.0 0.500@ 180.0 0.500@ 180.0

3Io= 0.0@ -45.5 A Va/Ia= 1.02e+018@ 39.3 Ohm (Va-Vb)/(Ia-Ib)= 708@ 8.5 Ohm

(Zo-Z1)/3Z1 = 0.6669 @ -0.0

-----------------------------------------------------------------------------------------------------------------------------------

131

Appendix D

MATLAB – Aspen Fault Analysis Results

D.1 SLG FAULT AT LOAD BUS

SLG Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.840 -80.3 0.840 -80.3

Ia1 (pu) 0.840 -80.3 0.840 -80.3

Ia2 (pu) 0.840 -80.3 0.840 -80.3

Iaf (pu) 2.521 -80.3 2.520 -80.3

Ibf (pu) 0.000 0.000

Icf (pu) 0.000 0.000

Va0 (pu) 0.465 177.1 0.465 177.1

Va1 (pu) 0.732 -0.9 0.732 -0.9

Va2 (pu) 0.268 177.5 0.268 -177.5

Vaf (pu) 0.000 0.000

Vbf (pu) 1.084 -129.9 1.084 -130.0

Vcf (pu) 1.138 127.7 1.139 127.7

D.2 DLG FAULT AT LOAD BUS

DLG Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.702 101.3 0.702 101.3

Ia1 (pu) 1.917 -82.1 1.916 -82.1

Ia2 (pu) 1.217 96.0 1.216 96.0

Iaf (pu) 0.000 0.000

Ibf (pu) 2.981 166.5 2.980 166.6

Icf (pu) 2.839 28.9 2.838 28.9

Va0 (pu) 0.388 -1.2 0.388 -1.2

Va1 (pu) 0.388 -1.2 0.388 -1.2

Va2 (pu) 0.388 -1.2 0.388 -1.2

Vaf (pu) 1.165 -1.2 1.165 -1.2

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

132

D.3 L-L FAULT AT LOAD BUS

D.4 3LG FAULT AT LOAD BUS

3LG Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 3.134 -82.8 3.132 -82.8

Ia2 (pu) 0.000 0.000

Iaf (pu) 3.134 -82.8 3.132 -82.8

Ibf (pu) 3.134 157.2 3.132 157.2

Icf (pu) 3.134 37.2 3.132 37.2

Va0 (pu) 0.000 0.000

Va1 (pu) 0.000 0.000

Va2 (pu) 0.000 0.000

Vaf (pu) 0.000 0.000

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

L-L Fault at Load Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 1.567 -82.8 1.566 -82.8

Ia2 (pu) 1.567 97.2 1.566 97.2

Iaf (pu) 0.000 0.000

Ibf (pu) 2.714 -172.8 2.713 -172.8

Icf (pu) 2.714 7.2 2.713 7.2

Va0 (pu) 0.000 0.000

Va1 (pu) 0.500 0.0 0.500 0.0

Va2 (pu) 0.500 0.0 0.500 0.0

Vaf (pu) 1.000 0.0 1.000 0.0

Vbf (pu) 0.500 180.0 0.500 180.0

Vcf (pu) 0.500 180.0 0.500 180.0

133

D.5 SLG FAULT AT MIDPOINT OF LINE

SLG Fault at Midpoint of Line

Variable Value

Matlab Aspen

Ia0 (pu) 1.269 -82.7 1.268 -82.7

Ia1 (pu) 1.269 -82.7 1.268 -82.7

Ia2 (pu) 1.269 -82.7 1.268 -82.7

Iaf (pu) 3.808 -82.7 3.805 -82.7

Ibf (pu) 0.000 0.000

Icf (pu) 0.000 0.000

Va0 (pu) 0.394 176.2 0.394 176.2

Va1 (pu) 0.697 -1.1 0.697 -1.1

Va2 (pu) 0.304 -177.5 0.303 -177.5

Vaf (pu) 0.000 0.000

Vbf (pu) 1.016 -125.5 1.015 -125.5

Vcf (pu) 1.081 123.1 1.081 123.1

D.6 DLG FAULT AT MIDPOINT OF LINE

DLG Fault at Midpoint of Line

Variable Value

Matlab Aspen

Ia0 (pu) 1.163 99.4 1.162 99.4

Ia1 (pu) 2.671 -84.2 2.669 -84.2

Ia2 (pu) 1.512 93.0 1.511 93.0

Iaf (pu) 0.000 0.000

Ibf (pu) 4.143 160.0 4.140 160.0

Icf (pu) 3.893 31.3 3.890 31.3

Va0 (pu) 0.362 -1.8 0.361 -1.8

Va1 (pu) 0.362 -1.8 0.361 -1.8

Va2 (pu) 0.362 -1.8 0.361 -1.8

Vaf (pu) 1.085 -1.8 1.084 -1.8

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

134

D.7 L-L FAULT AT MIDPOINT OF LINE

D.8 3LG FAULT AT MIDPOINT OF LINE

3LG Fault at Midpoint of Line

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 4.182 -85.2 4.179 -85.2

Ia2 (pu) 0.000 0.000

Iaf (pu) 4.182 -85.2 4.179 -85.2

Ibf (pu) 4.182 154.8 4.179 154.8

Icf (pu) 4.182 34.8 4.179 34.8

Va0 (pu) 0.000 0.000

Va1 (pu) 0.000 0.000

Va2 (pu) 0.000 0.000

Vaf (pu) 0.000 0.000

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

L-L Fault at Midpoint of Line

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 2.091 -85.2 2.089 -85.2

Ia2 (pu) 2.091 94.8 2.089 94.8

Iaf (pu) 0.000 0.000

Ibf (pu) 3.621 -175.2 3.619 -175.2

Icf (pu) 3.621 4.8 3.619 4.8

Va0 (pu) 0.000 0.000

Va1 (pu) 0.500 0.0 0.500 0.0

Va2 (pu) 0.500 0.0 0.500 0.0

Vaf (pu) 1.000 0.0 1.000 0.0

Vbf (pu) 0.500 180.0 0.500 180.0

Vcf (pu) 0.500 180.0 0.500 -180.0

135

D.9 SLG FAULT AT SEND BUS

D.10 DLG FAULT AT SEND BUS

SLG Fault at Send Bus

Variable Value

Matlab Aspen

Ia0 (pu) 2.564 -90.0 2.537 -89.9

Ia1 (pu) 2.564 -90.0 2.537 -89.9

Ia2 (pu) 2.564 -90.0 2.537 -89.9

Iaf (pu) 7.692 -90.0 7.612 -89.9

Ibf (pu) 0.000 0.000

Icf (pu) 0.000 0.000

Va0 (pu) 0.180 180.0 0.184 179.7

Va1 (pu) 0.590 0.0 0.592 0.0

Va2 (pu) 0.410 180.0 0.408 -179.9

Vaf (pu) 0.000 0.000

Vbf (pu) 0.907 -107.3 0.907 -107.7

Vcf (pu) 0.907 107.3 0.910 107.6

DLG Fault at Send Bus

Variable Value

Matlab Aspen

Ia0 (pu) 3.333 90.0 3.272 90.3

Ia1 (pu) 4.792 -90.0 4.744 -89.9

Ia2 (pu) 1.458 90.0 1.472 89.9

Iaf (pu) 0.000 0.000

Ibf (pu) 7.369 137.3 7.297 137.8

Icf (pu) 7.369 42.7 7.273 42.5

Va0 (pu) 0.233 0.0 0.237 -0.2

Va1 (pu) 0.233 0.0 0.237 -0.2

Va2 (pu) 0.233 0.0 0.237 -0.2

Vaf (pu) 0.700 0.0 0.710 -0.2

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

136

D.11 L-L FAULT AT SEND BUS

D.12 3LG FAULT AT SEND BUS

L-L Fault at Send Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 3.125 -90.0 3.108 -89.9

Ia2 (pu) 3.125 90.0 3.108 90.1

Iaf (pu) 0.000 0.000

Ibf (pu) 5.413 180.0 5.383 -179.9

Icf (pu) 5.413 0.0 5.383 0.1

Va0 (pu) 0.000 0.000

Va1 (pu) 0.500 0.0 0.500 0.0

Va2 (pu) 0.500 0.0 0.500 0.0

Vaf (pu) 1.000 0.0 1.000 0.0

Vbf (pu) 0.500 180.0 0.500 180.0

Vcf (pu) 0.500 180.0 0.500 -180.0

3LG Fault at Send Bus

Variable Value

Matlab Aspen

Ia0 (pu) 0.000 0.000

Ia1 (pu) 6.250 -90.0 6.216 -89.9

Ia2 (pu) 0.000 0.000

Iaf (pu) 6.250 -90.0 6.216 -89.9

Ibf (pu) 6.250 150.0 6.216 150.1

Icf (pu) 6.250 30.0 6.216 30.1

Va0 (pu) 0.000 0.000

Va1 (pu) 0.000 0.000

Va2 (pu) 0.000 0.000

Vaf (pu) 0.000 0.000

Vbf (pu) 0.000 0.000

Vcf (pu) 0.000 0.000

137

Appendix E

MATLAB Code

E.1. LONG TRANSMISSION LINE DESIGN PROGRAM

%Parameters %Power in MVA %l=220mi %VLL=345kV=345*10^3 V %pf=0.90 lagging % %Cable Characteristics %ACSR %f=60Hz cycles %t=50 C Temperature % %Cable Parameters %ra ohm/mi Resistance %xa ohm/mi Inductive Reactance %xa' Mohm*mi/cond or (*10^6 ohm/mi) % %Tower Parameters %Using 3H1 tower type %Spacings 26ft 26ft 52ft %Deq=nthroot(26*26*52,3)=32.7579ft %From Table 8 for 32.7579ft: %xd=0.42333737 ohm/mi by interpolation % %From Table 9 for 32.7579ft: %xd'= 0.1035*10^6 Mohm*mi/cond=0.1035*10^6 ohm/mi %Note: all necessary data for the code are from the book reference [1] % % clc clear all format short

%Data Input disp('<a href="">Results for Optimum Conductor </a>')

%Distance between conductors in ft Dab=26; Dbc=Dab; Dca=Dab*2; Deq=(Dab*Dbc *Dca)^(1/3); %Equivalent spacing (GMD) %The Line Length in [mi] l=220; %The Line Voltage in [V] VLL=345e3; %P=input('Enter Power in [MVA]:'

138

Power=[40;50;60;70;80;90;100]; for n=1:7 P=(Power(n,1))*10^6;

% pf power factor pf=0.9; % %Cable Parameters From Table 3

%ra in [ohm/mi]

%xa in [ohm/mi]

%xa_prime in [Mohm*mi/cond] %xap=xap*10^6;

%Cable Parameters From Table 3 % Size(CMIL) Strands ra(ohm/cond) xa(ohm/mi)

xap(Mohm*mi/cond)) Cond_param= [266800 26 0.385 0.465 0.1074; 300000 30 0.342 0.452 0.1049; 397500 26 0.259 0.441 0.1015; 397500 30 0.259 0.435 0.1006; 477000 30 0.216 0.424 0.0980; 500000 30 0.206 0.421 0.0973; 556500 30 0.1859 0.415 0.0957; 605000 26 0.1720 0.415 0.0953; 636000 30 0.1618 0.406 0.0937; 636000 54 0.1688 0.414 0.0950; 666600 54 0.1601 0.412 0.0943; 715500 30 0.1442 0.399 0.0920; 715500 54 0.1482 0.407 0.0932; 900000 54 0.1185 0.393 0.0898; 1192500 54 0.0906 0.376 0.0857; 1590000 54 0.0684 0.359 0.0814];

for k=1:16 Cond_Size_cmil=Cond_param(k,1); Strands=Cond_param(k,2); ra=Cond_param(k,3); xa=Cond_param(k,4); xap=10^6*Cond_param(k,5);

%Cable Parameters From Table 8 % xd(ohm/mi) xdp(Mohm*mi/cond) %From Table A.8 for xd y1=0.4232; %Lower value y2=0.4235; %Upper value x=32.7579; %Value x1=32.7; %Lower Value x2=32.8; %Upper value

139

y=y1+((x-x1)/(x2-x1))*(y2-y1);

xd=y; %From table A.8 by linear interpolation

%From Table 9 for 32.8ft xdp=0.1035

%xd_prime in [Mohm*mi/cond] %xdp=xdp*10^6; xdp=0.1035*10^6;

%Series Impedance z=ra+1i*(xa+xd); real1=abs(z); angle1=angle(z); Zpolar=real1,angle1*(180/pi);

%Shunt Admittance xc=xap+xdp; y=(1i/xc); real2=abs(y); angle2=angle(y); Ypolar=real2,angle2*(180/pi);

%gamma - Propagation Constant per Unit Length gamma=sqrt(z*y); gammapolar=abs(gamma),angle(gamma)*(180/pi);

%gamma*length of the line: for l=200mi yl=gamma*l; ylpolar=abs(yl),angle(yl)*(180/pi);

%Characteristic Impedance of the Line Per Unit Length zc=sqrt(z/y); zcpolar=abs(zc),angle(zc)*(180/pi);

%Characteristic Admittance of the Line Per Unit Length yc=1/zc; ycpolar=abs(yc),angle(yc)*(180/pi);

%The Receiving-end Line to Neutral Voltage Vrln=VLL/(sqrt(3)); Vrlnrad=Vrln + 1i*0; Vrlnpolar=abs(Vrln),angle(Vrln)*(180/pi);

%Using the Receiving-end Voltage as the Reference The Receiving-end

Current angle3=-acos(pf); real3=(P/((sqrt(3)*VLL)))*(cos(angle3)+1i*sin(angle3)); Ir=[real3 angle3]; Ir=real3; angle3deg=angle3*(180/pi);

140

%Irpolar = real3 angle3deg Ir_abs=abs(Ir); Irpolar = Ir_abs angle3deg;

%ABCD Constants %A Constant A=cosh(yl); Apolar=abs(A),angle(A)*(180/pi);

%B Constant B=zc*sinh(yl); Bpolar=abs(B),angle(B)*(180/pi);

%C Constant C=yc*sinh(yl); Cpolar=abs(C),angle(C)*(180/pi);

%D Constant D=A; Dpolar=Apolar; % %Constant Matrix format short g ConstMatrx = [A B;C D]; %ConstMatrx = [[Apolar] [Bpolar];[Cpolar] [Dpolar]];

%Sending-end Voltage and Current %Irrad=real3+i*angle3 VrlnIr = [Vrlnrad; Ir]; %Receving-end Voltage and Current Matrix %VrlnIr = Vrlnpolar Irpolar VslnIs = ConstMatrx*VrlnIr; %Sending-end Voltage and Current Matrix

Vsln=VslnIs(1,1); % Gives 1st row of the VslnIs Matrix % Is = VslnIs(2,1); % Gives 2nd row of the VslnIs Matrix

Vslnreal=real(Vsln); %Real part Vslnimag=imag(Vsln); %Imaginary Part

Isreal=real(Is); %Real part Isimag=imag(Is); %Imaginary Part

Vslnpolar=[abs(Vsln),angle(Vsln)*(180/pi)]; %Sending-end Line-to-

Neutral Voltage in Polar Form

Ispolar=[abs(Is),angle(Is)*(180/pi)]; %Sending-end Current in

Polar Form

Vsll=sqrt(3)* Vsln; %Sending-end Line-to-Line

Voltage %Note: An additional 30deg is added to the angle since a line-to-line

141

%voltage is 30deg ahead of its line-to neutral voltage Vsllnpolar=abs(Vsll),angle(Vsll)*(180/pi)+30; %Sending-end Line-to-

Line Voltage in Polar Form

%The Sending End PF thetas=Vslnpolar-Ispolar; %Theta angle sending (subtracts Is angle

from Vs line-to-neutral angle) thetas_=thetas(1,2);

pf_=cos(thetas_/180*pi); % The Sending-end Power Factor

%The Sending End Power ps=sqrt(3)*abs(Vsll)*abs(Is)*pf_;

%The Receiving End Power Pr=sqrt(3)*VLL*abs(Ir)*pf; % %The Power Loss in the Line Pl=ps-Pr;

%The TL Efficiency format short eng %disp('<a href="">Outputs</a>') %fprintf(2,'Optimal TL >= 95% ') etha=(Pr/ps)*100; TL_efficiency_percent=etha; TLeff=TL_efficiency_percent;

%The % of Voltage Regulation %fprintf(2,'Optimal Voltage Drop <= 5% ') VoltReg_percent=((abs(Vsln)-abs(Vrln))/(Vrln))*100; Vreg=VoltReg_percent;

%Power Loss Percentage %fprintf(2,'Optimal Power Loss <= 5% ') Power_loss_percent=(Pl/ps)*100; PL=Power_loss_percent;

%disp('Optimal TL >= 95%___________Optimal Voltage Drop <=

5%__________Optimal Power Loss <= 5') %disp('................................................................

.......................') %Results within the specs: %if TL_efficiency_percent>95 && 0<VoltReg_percent && VoltReg_percent<5

&& Power_loss_percent<5

%Loose results just for comparison and check: if TL_efficiency_percent>95 && VoltReg_percent<5 &&

Power_loss_percent<5 disp([' Power: Cond_cmil: Strands_#: TL_eff_%:

VoltReg_%: Power_loss_%:'])

142

disp([P, Cond_Size_cmil, Strands, TLeff, Vreg, PL])

k=k+1; n=n+1; end end end disp('_____________________________________________________________')

143

E.2. LONG TRANSMISSION LINE DESIGN OUTPUT

Results for Optimum Conductor

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 500.0000e+003 30.0000e+000 95.1183e+000 -5.8234e+000 4.8817e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 556.5000e+003 30.0000e+000 95.5148e+000 -5.9893e+000 4.4852e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 605.0000e+003 26.0000e+000 95.8240e+000 -6.1037e+000 4.1760e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 636.0000e+003 30.0000e+000 96.0066e+000 -6.1770e+000 3.9934e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 636.0000e+003 54.0000e+000 95.8881e+000 -6.1320e+000 4.1119e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 666.6000e+003 54.0000e+000 96.0688e+000 -6.2093e+000 3.9312e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 715.5000e+003 30.0000e+000 96.3726e+000 -6.3224e+000 3.6274e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 715.5000e+003 54.0000e+000 96.3158e+000 -6.3030e+000 3.6842e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 900.0000e+003 54.0000e+000 96.9417e+000 -6.5569e+000 3.0583e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 1.1925e+006 54.0000e+000 97.5541e+000 -6.8083e+000 2.4459e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

40.0000e+006 1.5900e+006 54.0000e+000 98.0640e+000 -7.0319e+000 1.9360e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 477.0000e+003 30.0000e+000 95.6339e+000 -4.6521e+000 4.3661e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 500.0000e+003 30.0000e+000 95.8070e+000 -4.7486e+000 4.1930e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 556.5000e+003 30.0000e+000 96.1565e+000 -4.9523e+000 3.8435e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 605.0000e+003 26.0000e+000 96.4249e+000 -5.0889e+000 3.5751e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 636.0000e+003 30.0000e+000 96.5879e+000 -5.1871e+000 3.4121e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 636.0000e+003 54.0000e+000 96.4813e+000 -5.1233e+000 3.5187e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 666.6000e+003 54.0000e+000 96.6394e+000 -5.2164e+000 3.3606e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 715.5000e+003 30.0000e+000 96.9080e+000 -5.3673e+000 3.0920e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 715.5000e+003 54.0000e+000 96.8554e+000 -5.3339e+000 3.1446e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 900.0000e+003 54.0000e+000 97.4016e+000 -5.6487e+000 2.5984e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 1.1925e+006 54.0000e+000 97.9327e+000 -5.9612e+000 2.0673e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

50.0000e+006 1.5900e+006 54.0000e+000 98.3721e+000 -6.2368e+000 1.6279e+000

144

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 397.5000e+003 26.0000e+000 95.3225e+000 -3.0521e+000 4.6775e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 397.5000e+003 30.0000e+000 95.2954e+000 -3.0587e+000 4.7046e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 477.0000e+003 30.0000e+000 95.9868e+000 -3.5457e+000 4.0132e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 500.0000e+003 30.0000e+000 96.1496e+000 -3.6608e+000 3.8504e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 556.5000e+003 30.0000e+000 96.4783e+000 -3.9020e+000 3.5217e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 605.0000e+003 26.0000e+000 96.7266e+000 -4.0605e+000 3.2734e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 636.0000e+003 30.0000e+000 96.8820e+000 -4.1836e+000 3.1180e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 636.0000e+003 54.0000e+000 96.7795e+000 -4.1009e+000 3.2205e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 666.6000e+003 54.0000e+000 96.9272e+000 -4.2096e+000 3.0728e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 715.5000e+003 30.0000e+000 97.1810e+000 -4.3984e+000 2.8190e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 715.5000e+003 54.0000e+000 97.1290e+000 -4.3509e+000 2.8710e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 900.0000e+003 54.0000e+000 97.6382e+000 -4.7265e+000 2.3618e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 1.1925e+006 54.0000e+000 98.1309e+000 -5.1000e+000 1.8691e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

60.0000e+006 1.5900e+006 54.0000e+000 98.5361e+000 -5.4277e+000 1.4639e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 397.5000e+003 26.0000e+000 95.4717e+000 -1.8495e+000 4.5283e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 397.5000e+003 30.0000e+000 95.4499e+000 -1.8622e+000 4.5501e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 477.0000e+003 30.0000e+000 96.1308e+000 -2.4268e+000 3.8692e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 500.0000e+003 30.0000e+000 96.2909e+000 -2.5604e+000 3.7091e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 556.5000e+003 30.0000e+000 96.6141e+000 -2.8388e+000 3.3859e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 605.0000e+003 26.0000e+000 96.8547e+000 -3.0188e+000 3.1453e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 636.0000e+003 30.0000e+000 97.0097e+000 -3.1670e+000 2.9903e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 636.0000e+003 54.0000e+000 96.9067e+000 -3.0652e+000 3.0933e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 666.6000e+003 54.0000e+000 97.0511e+000 -3.1895e+000 2.9489e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 715.5000e+003 30.0000e+000 97.3020e+000 -3.4163e+000 2.6980e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 715.5000e+003 54.0000e+000 97.2485e+000 -3.3544e+000 2.7515e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 900.0000e+003 54.0000e+000 97.7459e+000 -3.7904e+000 2.2541e+000

145

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 1.1925e+006 54.0000e+000 98.2250e+000 -4.2249e+000 1.7750e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

70.0000e+006 1.5900e+006 54.0000e+000 98.6171e+000 -4.6048e+000 1.3829e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 397.5000e+003 26.0000e+000 95.4705e+000 -635.4097e-003 4.5295e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 397.5000e+003 30.0000e+000 95.4527e+000 -654.3706e-003 4.5473e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 477.0000e+003 30.0000e+000 96.1432e+000 -1.2958e+000 3.8568e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 500.0000e+003 30.0000e+000 96.3054e+000 -1.4479e+000 3.6946e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 556.5000e+003 30.0000e+000 96.6329e+000 -1.7632e+000 3.3671e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 605.0000e+003 26.0000e+000 96.8735e+000 -1.9645e+000 3.1265e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 636.0000e+003 30.0000e+000 97.0324e+000 -2.1376e+000 2.9676e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 636.0000e+003 54.0000e+000 96.9261e+000 -2.0168e+000 3.0739e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 666.6000e+003 54.0000e+000 97.0718e+000 -2.1565e+000 2.9282e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 715.5000e+003 30.0000e+000 97.3273e+000 -2.4212e+000 2.6727e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 715.5000e+003 54.0000e+000 97.2709e+000 -2.3448e+000 2.7291e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 900.0000e+003 54.0000e+000 97.7724e+000 -2.8411e+000 2.2276e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 1.1925e+006 54.0000e+000 98.2537e+000 -3.3364e+000 1.7463e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

80.0000e+006 1.5900e+006 54.0000e+000 98.6460e+000 -3.7685e+000 1.3540e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 397.5000e+003 26.0000e+000 95.3690e+000 589.8914e-003 4.6310e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 397.5000e+003 30.0000e+000 95.3542e+000 564.5055e-003 4.6458e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 477.0000e+003 30.0000e+000 96.0676e+000 -153.2770e-003 3.9324e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 500.0000e+003 30.0000e+000 96.2352e+000 -323.5469e-003 3.7648e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 556.5000e+003 30.0000e+000 96.5734e+000 -675.5677e-003 3.4266e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 605.0000e+003 26.0000e+000 96.8192e+000 -897.7055e-003 3.1808e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 636.0000e+003 30.0000e+000 96.9851e+000 -1.0960e+000 3.0149e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 636.0000e+003 54.0000e+000 96.8736e+000 -955.9301e-003 3.1264e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 666.6000e+003 54.0000e+000 97.0235e+000 -1.1109e+000 2.9765e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

146

90.0000e+006 715.5000e+003 30.0000e+000 97.2888e+000 -1.4137e+000 2.7112e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 715.5000e+003 54.0000e+000 97.2286e+000 -1.3225e+000 2.7714e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 900.0000e+003 54.0000e+000 97.7447e+000 -1.8788e+000 2.2553e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 1.1925e+006 54.0000e+000 98.2388e+000 -2.4348e+000 1.7612e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

90.0000e+006 1.5900e+006 54.0000e+000 98.6401e+000 -2.9191e+000 1.3599e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 397.5000e+003 26.0000e+000 95.1977e+000 1.8260e+000 4.8023e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 397.5000e+003 30.0000e+000 95.1854e+000 1.7940e+000 4.8146e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 477.0000e+003 30.0000e+000 95.9309e+000 1.0005e+000 4.0691e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 500.0000e+003 30.0000e+000 96.1060e+000 812.1515e-003 3.8940e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 556.5000e+003 30.0000e+000 96.4595e+000 423.7291e-003 3.5405e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 605.0000e+003 26.0000e+000 96.7141e+000 181.0093e-003 3.2859e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 636.0000e+003 30.0000e+000 96.8890e+000 -42.3493e-003 3.1110e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 636.0000e+003 54.0000e+000 96.7709e+000 116.9316e-003 3.2291e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 666.6000e+003 54.0000e+000 96.9272e+000 -53.1645e-003 3.0728e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 715.5000e+003 30.0000e+000 97.2056e+000 -393.9519e-003 2.7944e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 715.5000e+003 54.0000e+000 97.1410e+000 -287.9565e-003 2.8590e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 900.0000e+003 54.0000e+000 97.6791e+000 -904.0125e-003 2.3209e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 1.1925e+006 54.0000e+000 98.1932e+000 -1.5205e+000 1.8068e+000

Power: Cond_cmil: Strands_#: TL_eff_%: VoltReg_%: Power_loss_%:

100.0000e+006 1.5900e+006 54.0000e+000 98.6098e+000 -2.0570e+000 1.3902e+000

_________________________________________________________________________________________

147

E.3. CONDUCTOR'S SAG AND TENSION USING CATENARY AND PARABOLIC

METHOD PROGRAM

%Calculation of conductor's tension using catenary and parabolic method

%

%Assumptions:

% - A transmission line conductor has been suspended freely from two

% towers in catenary shape.

% - The span between two towers is 700ft.

% - Horizontal tension is 3000lb.

clc

clear all

format short g

% Cable Parameters

Lspan=900; %Assuming the span between two towers is 700ft

w_lb_mi=3933; %Weight of the conductor 477000 30 strand is

3933lb/mi

mi=5280; %1mi=5280ft

w_lb_ft=w_lb_mi/mi; %lb/mi to lb/ft conversion

w=w_lb_ft; %Weight of the conductor

H=3000; %Assuming horizontal tension is 3000lb.

%Length of the conductor:

l=((2*H)/w)*sinh((w*Lspan)/(2*H));

%or

c=H/w;

l=2*c*(sinh(Lspan/(2*c)));

%Sag

d_sag=c*(cosh((Lspan)/(2*c))-1);

% Conductor tension using catenary method:

Tmax=w*(c+d_sag); %Maximum value of conductor tension [lb]

Tmin=w*c; %Minimum values of conductor tension [lb]

%Approximate value of tension by using parabolic method:

Tapp=(w*Lspan^2)/(8*d_sag);

%Phase to Ground Clearance :

Thight=60; %Tower hight [ft]

Clr=Thight-d_sag; %Phase to Ground Clearence

%Results Display

disp('<a href="">Results for Sag and Tension </a>')

disp('Sag Value [ft]')

disp([d_sag])

disp('..............................................')

disp('Conductor tension using catenary method:')

disp('Maximum value of the conductor tension [lb]:')

148

disp([Tmax])

disp('Minimum value of the conductor tension [lb]:')

disp([Tmin])

disp('..............................................')

disp('Conductor tension using parabolic method:')

disp('Minimum value of the conductor tension [lb]:')

disp([Tapp])

disp('_______________________________________________')

disp('<a href="">Results for Phase to Ground Clearance </a>')

disp('Phase to Ground Clearance [ft]:')

disp([Clr])

149

E.4. CONDUCTOR'S SAG AND TENSION USING CATENARY AND PARABOLIC

METHOD OUTPUT

Results for Sag and Tension

Sag Value [ft]

15.21

..............................................

Conductor tension using catenary method:

Maximum value of the conductor tension [lb]:

3011.3

Minimum value of the conductor tension [lb]:

3000

..............................................

Conductor tension using parabolic method:

Minimum value of the conductor tension [lb]:

2998.1

_______________________________________________

Results for Phase to Ground Clearance

Phase to Ground Clearance [ft]:

44.782

150

E.5. CORONA POWER LOSS PROGRAM

clc

clear all

format short eng

%Line Parameters

VLL=345e3; % line voltage in [V]

Vln=VLL/sqrt(3); % line-to-neutral operating voltage in [kV]

Vln=Vln/10^3; % adjusted for formula usage

f=60; % frequency in [Hz]

%Distance between conductors in [ft]

Dab=26;

Dbc=Dab;

Dca=Dab*2;

Deq=(Dab*Dbc *Dca)^(1/3); %Equivalent spacing (GMD)

%Conductor Parameters

l=220; % line length in [mi]

km=1.6093; % [mi] to [km] conversion factor

l_km=l*km; % line length in [km]

D=Deq; % distance between conductors in [ft]

ft=30.48; % [ft] to [cm] conversion factor

D=Deq*ft; % equivalent spacing between conductors [ft] to

[cm]

d=0.883; % conductor diameter - Outside diameter [in]

in=2.54; % [in] to [cm] conversion factor

d=in*d; % [in] to [cm] conversion

r=d/2; % radius of the conductor [cm]

%*******************************************************************

%For fair weather conditions

%*******************************************************************

%

%Maximum electric stress on the surface of the conductor:

m=0.9; %Surface irregularity factor (0<m=<1,0.87-0.90

for

%weathered conductors with more than seven

strands)

Emax=Vln/(m*r*log(D/r)); % max voltage gradient

[kV/cm]

Emean=Vln/(m*r*log(D/r)*(sqrt(3))); % mean voltage

gradient[kV/cm]

%For fair weather conditions 25C and 760 mmHg:

%The breakdown field strength of air is 30kV/cm

%For any other temperature in [C] and pressure p in [mmHg]

t=25;

p=760;

delta=(0.392*p)/(273+t); %The air-density factor

151

%The disruptive (inception)critical voltage

Vc_peak=30*delta*m*r*log(D/r); %kV (peak)

Vc_rms=21.1*delta*m*r*log(D/r); %kV (rms)/phase

Vc_LL=sqrt(3)*Vc_rms; %kV

%Visual corona inception voltage

Vv_peak=30*delta*(1+0.301/(sqrt(delta*r)))*m*r*log(D/r); %kV (peak)

Vv_rms=21.1*delta*(1+0.301/(sqrt(delta*r)))*m*r*log(D/r); %kV (rms)

%Peek's Formula:

P_Peek_phase=(241/(delta))*(f+25)*sqrt(r/D)*(Vln-Vc_rms)^2*10^-5;

%[kW/km/phase]

P_Peek_3_phase=3*P_Peek_phase; %[kW/km]

P_Peek_Line=l_km*P_Peek_3_phase; %Total loss for all three lines [kW]

%Peterson's Formula:

Vln_per_Vc_rms=Vln/Vc_rms;

%By Linear Interpolation

x=Vln_per_Vc_rms;

y1=0.3; %Lower value

y2=0.9; %Upper value

x=1.4261; %Value of Vln_per_Vc_rms

x1=1.4; %Lower Value

x2=1.5; %Upper value

y=y1+((x-x1)/(x2-x1))*(y2-y1);

F=y; %Corona factor: ratio of Vln/Vc

P_Peterson_phase=2.1*f*F*(Vc_rms/log10(D/r))^2*10^-5;

%[kW/km/phase]

P_Peterson_3_phase=3*P_Peterson_phase; %[kW/km]

P_Peterson_Line=l_km*P_Peterson_3_phase; %Total loss for all three

%lines [kW]

%*******************************************************************

%For foul weather conditions

%*******************************************************************

%

%Peek's Formula:

Vc_rms_foul_middle=0.96*Vc_rms; %Disruptive voltage is taken as

%0.9*fair weather value for a middle conductor

Vc_rms_foul_outer=1.06*Vc_rms; %Disruptive voltage is taken as

%1.06*fair weather value for a outer conductor

%Vc_rms_foul_outer=2*Vc_rms_foul_outer %Disruptive voltage for two

%outside conductors

P_Peek_phase_foul_middle=(241/(delta))*(f+25)*sqrt(r/D)*(Vln-

Vc_rms_foul_middle)^2*10^-5; Power loss for middle

%conductor[kW/km/phase]

P_Peek_phase_foul_outer=(241/(delta))*(f+25)*sqrt(r/D)*(Vln-

Vc_rms_foul_outer)^2*10^-5; %[kW/km/phase]

P_Peek_phase_foul_two_outer=2*P_Peek_phase_foul_outer; %Power loss

%for two outside conductors

152

P_Peek_3_phase_foul_total=P_Peek_phase_foul_middle+P_Peek_phase_foul_tw

o_outer; %Total power loss for all three conductors[kW/km]

P_Peek_3_phase_foul_total_TL=l_km*P_Peek_3_phase_foul_total; %Total

%loss for all three lines [kW]

%Peterson's Formula:

%For rain Vc is approx. 80% of the fair weather calculated value

Vln_per_Vc_rms_foul=Vln/(0.8*Vc_rms);

%By Linear Interpolation

x_f=Vln_per_Vc_rms_foul;

y1_f=2.2; %Lower value

y2_f=4.95; %Upper value

x_f=1.7826; %Value of Vln_per_Vc_rms_foul

x1_f=1.6; %Lower Value

x2_f=1.8; %Upper value

y_f=y1_f+((x_f-x1_f)/(x2_f-x1_f))*(y2_f-y1_f);

F_f=y_f; %Corona factor: ratio of Vln/Vc

P_Peterson_phase_foul=2.1*f*F_f*(Vc_rms/log10(D/r))^2*10^-5;

%[kW/km/phase]

P_Peterson_3_phase_foul=3*P_Peterson_phase_foul; %[kW/km]

P_Peterson_Line_foul=l_km*P_Peterson_3_phase_foul; %Total loss

%for all three lines [kW]

disp('<a href=""> Voltage Gradient</a>')

disp(' Emax[kV/cm] Emean[kV/cm] ')

disp([Emax Emean ])

disp('<a href=""> Corona Loss for Fair Weather Conditions</a>')

disp('According to Peek`s Formula:')

disp('P_Peek_phase[kW/km/phase]=')

disp([P_Peek_phase ])

disp('P_Peek_3_phase[kW/km]=')

disp([P_Peek_3_phase ])

disp('P_Peek_Line[kW]=')

disp([P_Peek_Line ])

disp('________________________________________________________')

disp('According to Peterson`s Formula:')

disp('P_Peterson_phase [kW/km/phase]=')

disp([P_Peterson_phase ])

disp(' P_Peterson_3_phase [kW/km]= ')

disp([ P_Peterson_3_phase ])

disp(' P_Peterson_Line[kW]]=')

disp([ P_Peterson_Line ])

disp('________________________________________________________')

disp('<a href=""> Corona Loss for Foul Weather Conditions</a>')

disp('According to Peek`s Formula:')

disp('P_Peek_3_phase_foul[kW/km]=')

disp([P_Peek_3_phase_foul_total ])

disp('P_Peek_Line_foul[kW]=')

disp([P_Peek_3_phase_foul_total_TL ])

disp('________________________________________________________')

disp('According to Peterson`s Formula:')

disp('P_Peterson_phase_foul [kW/km/phase]=')

153

disp([P_Peterson_phase_foul ])

disp(' P_Peterson_3_phase_foul [kW/km]= ')

disp([ P_Peterson_3_phase_foul ])

disp(' P_Peterson_Line_foul[kW]]=')

disp([ P_Peterson_Line_foul ])

154

E.6. CORONA POWER LOSS OUTPUT

Voltage Gradient

Emax[kV/cm] Emean[kV/cm]

29.0588e+000 16.7771e+000

Corona Loss for Fair Weather Conditions

According to Peek`s Formula:

P_Peek_phase[kW/km/phase]=

20.4665e+000

P_Peek_3_phase[kW/km]=

61.3994e+000

P_Peek_Line[kW]=

21.7382e+003

________________________________________________________

According to Peterson`s Formula:

P_Peterson_phase [kW/km/phase]=

1.3826e+000

P_Peterson_3_phase [kW/km]=

4.1477e+000

P_Peterson_Line[kW]]=

1.4685e+003

________________________________________________________

Corona Loss for Foul Weather Conditions

According to Peek`s Formula:

P_Peek_3_phase_foul[kW/km]=

53.9898e+000

P_Peek_Line_foul[kW]=

19.1149e+003

________________________________________________________

According to Peterson`s Formula:

P_Peterson_phase_foul [kW/km/phase]=

14.2639e+000

P_Peterson_3_phase_foul [kW/km]=

42.7916e+000

P_Peterson_Line_foul[kW]]=

15.1502e+003

155

E.7 CALCULATIONS OF THE FOUR SHUNT FAULT TYPES

% Matlab program for calculations of the 4 shunt fault types.

% Model: 22kV generator, 22/345-kV transformer connected delta-Y

grounded,

% and 345kV overhead transmission line.

% Pre-set parameters: Sbase, Gen_Xd_subtran, Z0gen, Z2gen, Z0trf,

ZL_ohms, Zf, Zg

%

clear all

clc

format short

%Setting 'a' operator value to use as element in A matrix

j=sqrt(-1);

a=cosd(120)+j*sind(120);

%System base parameter

Sbase=100e6;

%Generator assigned values

SBgen=100e6;

VBgen=22e3;

Gen_Xd_subtran=j*0.09; %Average subtransient reactance for two-pole

turbine generator

Z0gen=j*0.03; %Average zero sequence impedance for two-pole turbine

generator

Z1gen=Gen_Xd_subtran; %Average pos-sequence impedance for two-pole

turbine generator

Z2gen=j*0.09; %Average neg-sequence impedance for two-pole turbine

generator

%Transformer assigned values; common practice to set Z0=Z1=Z2 for a

transformer

Z0trf=j*0.07;

Z1trf=Z0trf;

Z2trf=Z0trf;

%Transmission line assigned values

SBL=100e6;

VBL=345e3;

ZBL=VBL^2/SBL

ZL_ohms = 47.52+j*186.4280;

%Sequence impedances of line in per-unit

Z1L=ZL_ohms/ZBL;

Z2L=Z1L;

Z0L=3*Z1L;

%Choosing shunt fault type for calculations

Fault_type = input('\nEnter fault type(1=SLG,2=DLG,3=LL,4=3LG): \n');

%Getting fault location on line to calculate actual portion of line

impedance involved with fault

fpoint = input('\nEnter percentage of line from sending-end that is

involved with fault(e.g.0,50,100): \n');

fpoint = fpoint/100;

%System equivalent sequence impedance values

Z0=Z0trf+fpoint*Z0L;

Z1=Z1gen+Z1trf+fpoint*Z1L;

156

Z2=Z2gen+Z2trf+fpoint*Z2L;

Zseq=[Z0;Z1;Z2]

%Setting fault impedance values;

Zf=0;

Zg=0;

%Base values for per-unit fault calculations

Sbase=100e6;

Vbase=345e3;

Ibase=Sbase/(sqrt(3)*Vbase);

%Calculating sequence currents in p.u.

if Fault_type == 1 %Case for calculating SLG fault sequence currents

Ia0=(1+j*0)/(Z0+Z1+Z2+3*Zf);

Ia1=Ia0;

Ia2=Ia0;

disp('+++++++++++++SLG Fault Analysis+++++++++++++');

elseif Fault_type == 2 %Case for calculating DLG fault sequence

currents

Ia1=(1+j*0)/[(Z1+Zf)+((Z2+Zf)*(Z0+Zf+3*Zg))/((Z2+Zf)+(Z0+Zf+3*Zg))];

Ia2=-[(Z0+Zf+3*Zg)/((Z2+Zf)+(Z0+Zf+3*Zg))]*Ia1;

Ia0=-[(Z2+Zf)/((Z2+Zf)+(Z0+Zf+3*Zg))]*Ia1;

disp('+++++++++++++DLG Fault Analysis+++++++++++++');

elseif Fault_type == 3 %Case for calculating LL fault sequence

currents

Ia0=0+j*0;

Ia1=(1.0+j*0)/(Z1+Z2+Zf);

Ia2=-Ia1;

disp('+++++++++++++LL Fault Analysis+++++++++++++');

else %Case for calculating 3LG fault sequence currents

Ia0=0+j*0;

Ia1=(1.0+j*0)/(Z1+Zf);

Ia2=0+j*0;

disp('+++++++++++++3-Phase Fault Analysis+++++++++++++');

end

disp('Sequence Currents in Per-Unit:');

Iaseq_pu_rect=[Ia0;Ia1;Ia2]; %Array of p.u. current values in

rectangular form

Iaseq_pu_polar=polar(Iaseq_pu_rect) %Converting to polar form

for i=1:3 %Setting sequence current angle to zero if sequence current

magnitude is zero

if abs(Iaseq_pu_polar(i)) == 0

Iaseq_pu_rect(i)=0;

end

end

disp('Sequence Currents in Amps:');

Iaseq_amps_rect=Iaseq_pu_rect*Ibase; %Converting sequence currents

from p.u. to amps

Iaseq_amps_polar=polar(Iaseq_amps_rect) %Converting to polar form

Amatrix=[1 1 1;1 a^2 a;1 a a^2]; %Defining A matrix for calculations

disp('Phase Currents in Per-Unit:');

Iabcf_pu_rect=Amatrix*Iaseq_pu_rect; %Calculating phase currents in

p.u.

Iabcf_pu_polar=polar(Iabcf_pu_rect) %Converting to polar form

disp('Phase Currents in Amps');

157

Iabcf_amps_rect=Iabcf_pu_rect*Ibase; %Converting phase currents from

p.u. to amps

Iabcf_amps_polar=polar(Iabcf_amps_rect) %Converting to polar form

disp('Sequence Voltages in Per-Unit(L-N):');

Eseq=[0;1+j*0;0];

Zmatrix=[Z0 0 0;0 Z1 0;0 0 Z2];

Vaseq_pu_rect=Eseq-Zmatrix*Iaseq_pu_rect; %Calculating sequence

voltages in p.u.

Vaseq_pu_polar=polar(Vaseq_pu_rect) %Converting to polar form

disp('Sequence Voltages in Volts(L-N)');

Vaseq_volts_rect=Vaseq_pu_rect*Vbase; %Converting sequence voltages

from p.u. to volts

Vaseq_volts_polar=polar(Vaseq_volts_rect) %Converting to polar form

for i=1:3 %Setting sequence voltage angle to zero if sequence voltage

magnitude is zero

if abs(Vaseq_pu_polar(i)) == 0

Vaseq_pu_rect(i)=0;

end

end

disp('Phase Voltages in Per-Unit(L-N):');

Vabcf_pu_rect=Amatrix*Vaseq_pu_rect; %Calculating phase voltages(L-N)

in p.u.

Vabcf_pu_polar=polar(Vabcf_pu_rect) %Converting to polar form

disp('Phase Voltages in Volts(L-N):');

Vabcf_volts_rect=Vabcf_pu_rect*Vbase; %Converting phase voltages from

p.u. to volts

Vabcf_volts_polar=polar(Vabcf_volts_rect) %Converting to polar form

disp('Phase Voltages in Per-Unit(L-L):');

%Calculating phase voltages(L-L) in p.u.

Vabf_pu_rect=Vabcf_pu_rect(1)-Vabcf_pu_rect(2);

Vbcf_pu_rect=Vabcf_pu_rect(2)-Vabcf_pu_rect(3);

Vcaf_pu_rect=Vabcf_pu_rect(3)-Vabcf_pu_rect(1);

%Converting to polar form

Vabf_pu_polar=polar(Vabf_pu_rect)

Vbcf_pu_polar=polar(Vbcf_pu_rect)

Vcaf_pu_polar=polar(Vcaf_pu_rect)

disp('Phase Voltages in Volts(L-L)');

%Converting phase voltages from p.u. to volts

Vabf_volts_rect=Vabf_pu_rect*Vbase;

Vbcf_volts_rect=Vbcf_pu_rect*Vbase;

Vcaf_volts_rect=Vcaf_pu_rect*Vbase;

%Converting to polar form

Vabf_volts_polar=polar(Vabf_volts_rect)

Vbcf_volts_polar=polar(Vbcf_volts_rect)

Vcaf_volts_polar=polar(Vcaf_volts_rect)

158

E.8 OUTPUTS OF THE FOUR SHUNT FAULT TYPES

E8.1 477kcmil SLG SE

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

1

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

0

Zseq =

0 + 0.0700i

0 + 0.1600i

0 + 0.1600i

+++++++++++++SLG Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

2.5641 -90.0000

2.5641 -90.0000

2.5641 -90.0000

Sequence Currents in Amps:

Iaseq_amps_polar =

429.0972 -90.0000

429.0972 -90.0000

429.0972 -90.0000

Phase Currents in Per-Unit:

Iabcf_pu_polar =

7.6923 -90.0000

0.0000 45.0000

0.0000 45.0000

Phase Currents in Amps

Iabcf_amps_polar =

1.0e+003 *

1.2873 -0.0900

0.0000 0.0450

0.0000 0.0450

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0.1795 180.0000

0.5897 0

0.4103 180.0000

159

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+005 *

0.6192 0.0018

2.0346 0

1.4154 0.0018

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

0 0

0.9069 -107.2695

0.9069 107.2695

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

1.0e+005 *

0 0

3.1288 -0.0011

3.1288 0.0011

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

0.9069 72.7305

Vbcf_pu_polar =

1.7321 -90.0000

Vcaf_pu_polar =

0.9069 107.2695

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

1.0e+005 *

3.1288 0.0007

Vbcf_volts_polar =

1.0e+005 *

5.9756 -0.0009

Vcaf_volts_polar =

1.0e+005 *

3.1288 0.0011

160

E8.2 477kcmil SLG MID

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

1

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

50

Zseq =

0.0599 + 0.3049i

0.0200 + 0.2383i

0.0200 + 0.2383i

+++++++++++++SLG Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

1.2692 -82.7224

1.2692 -82.7224

1.2692 -82.7224

Sequence Currents in Amps:

Iaseq_amps_polar =

212.3918 -82.7224

212.3918 -82.7224

212.3918 -82.7224

Phase Currents in Per-Unit:

Iabcf_pu_polar =

3.8075 -82.7224

0.0000 48.3665

0.0000 48.3665

Phase Currents in Amps

Iabcf_amps_polar =

637.1755 -82.7224

0.0000 48.3665

0.0000 48.3665

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0.3944 176.1669

0.6969 -1.0840

0.3035 -177.5106

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+005 *

1.3607 0.0018

2.4043 -0.0000

1.0471 -0.0018

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

161

0.0000 1.7899

1.0156 -125.5359

1.0810 123.0984

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

1.0e+005 *

0.0000 0.0000

3.5039 -0.0013

3.7294 0.0012

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

1.0156 54.4641

Vbcf_pu_polar =

1.7321 -90.0000

Vcaf_pu_polar =

1.0810 123.0984

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

1.0e+005 *

3.5039 0.0005

Vbcf_volts_polar =

1.0e+005 *

5.9756 -0.0009

Vcaf_volts_polar =

1.0e+005 *

3.7294 0.0012

162

E8.3 477kcmil SLG RE

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

1

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

100

Zseq =

0.1198 + 0.5399i

0.0399 + 0.3166i

0.0399 + 0.3166i

+++++++++++++SLG Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0.8403 -80.3431

0.8403 -80.3431

0.8403 -80.3431

Sequence Currents in Amps:

Iaseq_amps_polar =

140.6274 -80.3431

140.6274 -80.3431

140.6274 -80.3431

Phase Currents in Per-Unit:

Iabcf_pu_polar =

2.5210 -80.3431

0.0000 90.0000

0.0000 90.0000

Phase Currents in Amps

Iabcf_amps_polar =

421.8823 -80.3431

0.0000 90.0000

0.0000 90.0000

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0.4647 177.1485

0.7322 -0.9046

0.2682 -177.5297

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+005 *

1.6033 0.0018

2.5260 -0.0000

0.9252 -0.0018

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

0.0000 -165.9638

1.0844 -129.9443

1.1384 127.7026

163

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

1.0e+005 *

0.0000 -0.0017

3.7411 -0.0013

3.9275 0.0013

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

1.0844 50.0557

Vbcf_pu_polar =

1.7321 -90.0000

Vcaf_pu_polar =

1.1384 127.7026

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

1.0e+005 *

3.7411 0.0005

Vbcf_volts_polar =

1.0e+005 *

5.9756 -0.0009

Vcaf_volts_polar =

1.0e+005 *

3.9275 0.0013

164

E8.4 477kcmil LL SE

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

3

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

0

Zseq =

0 + 0.0700i

0 + 0.1600i

0 + 0.1600i

+++++++++++++LL Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0 0

3.1250 -90.0000

3.1250 90.0000

Sequence Currents in Amps:

Iaseq_amps_polar =

0 0

522.9622 -90.0000

522.9622 90.0000

Phase Currents in Per-Unit:

Iabcf_pu_polar =

0 0

5.4127 180.0000

5.4127 -0.0000

Phase Currents in Amps

Iabcf_amps_polar =

0 0

905.7971 180.0000

905.7971 -0.0000

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0 0

0.5000 0

0.5000 0

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

0 0

172500 0

172500 0

165

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

1.0000 0

0.5000 180.0000

0.5000 180.0000

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

1.0e+005 *

3.4500 0

1.7250 0.0018

1.7250 0.0018

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

1.5000 -0.0000

Vbcf_pu_polar =

0 0

Vcaf_pu_polar =

1.5000 180.0000

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

1.0e+005 *

5.1750 -0.0000

Vbcf_volts_polar =

0 0

Vcaf_volts_polar =

517500 180

166

E8.5 477kcmil LL MID

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

3

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

50

Zseq =

0.0599 + 0.3049i

0.0200 + 0.2383i

0.0200 + 0.2383i

+++++++++++++LL Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0 0

2.0907 -85.2119

2.0907 94.7881

Sequence Currents in Amps:

Iaseq_amps_polar =

0 0

349.8817 -85.2119

349.8817 94.7881

Phase Currents in Per-Unit:

Iabcf_pu_polar =

0 0

3.6213 -175.2119

3.6213 4.7881

Phase Currents in Amps

Iabcf_amps_polar =

0 0

606.0130 -175.2119

606.0130 4.7881

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0 0

0.5000 0

0.5000 0

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+005 *

0 0

1.7250 0

1.7250 0

167

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

1.0000 0

0.5000 180.0000

0.5000 180.0000

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

345000 0

172500 180

172500 180

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

1.5000 0

Vbcf_pu_polar =

0.0000 -90.0000

Vcaf_pu_polar =

1.5000 180.0000

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

517500 0

Vbcf_volts_polar =

0.0000 -90.0000

Vcaf_volts_polar =

517500 180

168

E8.6 477kcmil LL RE

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

3

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

100

Zseq =

0.1198 + 0.5399i

0.0399 + 0.3166i

0.0399 + 0.3166i

+++++++++++++LL Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0 0

1.5667 -82.8134

1.5667 97.1866

Sequence Currents in Amps:

Iaseq_amps_polar =

0 0

262.1887 -82.8134

262.1887 97.1866

Phase Currents in Per-Unit:

Iabcf_pu_polar =

0 0

2.7137 -172.8134

2.7137 7.1866

Phase Currents in Amps

Iabcf_amps_polar =

0 0

454.1241 -172.8134

454.1241 7.1866

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0 0

0.5000 -0.0000

0.5000 0.0000

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+005 *

0 0

1.7250 -0.0000

1.7250 0.0000

169

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

1.0000 0

0.5000 180.0000

0.5000 180.0000

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

345000 0

172500 180

172500 180

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

1.5000 0

Vbcf_pu_polar =

0.0000 -90.0000

Vcaf_pu_polar =

1.5000 180.0000

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

517500 0

Vbcf_volts_polar =

0.0000 -90.0000

Vcaf_volts_polar =

517500 180

170

E8.7 477kcmil DLG SE

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

2

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

0

Zseq =

0 + 0.0700i

0 + 0.1600i

0 + 0.1600i

+++++++++++++DLG Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

3.3333 90.0000

4.7917 -90.0000

1.4583 90.0000

Sequence Currents in Amps:

Iaseq_amps_polar =

557.8263 90.0000

801.8754 -90.0000

244.0490 90.0000

Phase Currents in Per-Unit:

Iabcf_pu_polar =

0.0000 90.0000

7.3686 137.2695

7.3686 42.7305

Phase Currents in Amps

Iabcf_amps_polar =

1.0e+003 *

0.0000 0.0900

1.2331 0.1373

1.2331 0.0427

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0.2333 0

0.2333 0

0.2333 0

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+004 *

8.0500 0

8.0500 0

8.0500 0

171

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

0.7000 0

0.0000 -158.1986

0.0000 129.8056

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

1.0e+005 *

2.4150 0

0.0000 -0.0016

0.0000 0.0013

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

0.7000 0.0000

Vbcf_pu_polar =

0.0000 -90.0000

Vcaf_pu_polar =

0.7000 180.0000

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

1.0e+005 *

2.4150 0.0000

Vbcf_volts_polar =

0.0000 -90.0000

Vcaf_volts_polar =

1.0e+005 *

2.4150 0.0018

172

E8.8 477kcmil DLG MID

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

2

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

50

Zseq =

0.0599 + 0.3049i

0.0200 + 0.2383i

0.0200 + 0.2383i

+++++++++++++DLG Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

1.1633 99.3550

2.6709 -84.2183

1.5117 93.0325

Sequence Currents in Amps:

Iaseq_amps_polar =

194.6731 99.3550

446.9764 -84.2183

252.9730 93.0325

Phase Currents in Per-Unit:

Iabcf_pu_polar =

0.0000 -90.0000

4.1430 159.9640

3.8926 31.3297

Phase Currents in Amps

Iabcf_amps_polar =

0.0000 -90.0000

693.3266 159.9640

651.4145 31.3297

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0.3615 -1.7556

0.3615 -1.7556

0.3615 -1.7556

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+005 *

1.2472 -0.0000

1.2472 -0.0000

1.2472 -0.0000

173

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

1.0845 -1.7556

0.0000 180.0000

0.0000 131.1859

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

1.0e+005 *

3.7417 -0.0000

0.0000 0.0018

0.0000 0.0013

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

1.0845 -1.7556

Vbcf_pu_polar =

0.0000 -74.2914

Vcaf_pu_polar =

1.0845 178.2444

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

1.0e+005 *

3.7417 -0.0000

Vbcf_volts_polar =

0.0000 -74.2914

Vcaf_volts_polar =

1.0e+005 *

3.7417 0.0018

174

E8.9 477kcmil DLG RE

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

2

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

100

Zseq =

0.1198 + 0.5399i

0.0399 + 0.3166i

0.0399 + 0.3166i

+++++++++++++DLG Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0.7022 101.3174

1.9171 -82.0575

1.2168 95.9956

Sequence Currents in Amps:

Iaseq_amps_polar =

117.5116 101.3174

320.8198 -82.0575

203.6295 95.9956

Phase Currents in Per-Unit:

Iabcf_pu_polar =

0.0000 110.5560

2.9808 166.5497

2.8393 28.9028

Phase Currents in Amps

Iabcf_amps_polar =

0.0000 110.5560

498.8298 166.5497

475.1491 28.9028

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0.3883 -1.1910

0.3883 -1.1910

0.3883 -1.1910

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e+005 *

1.3397 -0.0000

1.3397 -0.0000

1.3397 -0.0000

Phase Voltages in Per-Unit(L-N):

175

Vabcf_pu_polar =

1.1650 -1.1910

0.0000 180.0000

0.0000 134.7753

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

1.0e+005 *

4.0192 -0.0000

0.0000 0.0018

0.0000 0.0013

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

1.1650 -1.1910

Vbcf_pu_polar =

0.0000 -90.0000

Vcaf_pu_polar =

1.1650 178.8090

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

1.0e+005 *

4.0192 -0.0000

Vbcf_volts_polar =

0.0000 -90.0000

Vcaf_volts_polar =

1.0e+005 *

4.0192 0.0018

176

E8.10 477kcmil 3LG SE

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

4

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

0

Zseq =

0 + 0.0700i

0 + 0.1600i

0 + 0.1600i

+++++++++++++3-Phase Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0 0

6.2500 -90.0000

0 0

Sequence Currents in Amps:

Iaseq_amps_polar =

1.0e+003 *

0 0

1.0459 -0.0900

0 0

Phase Currents in Per-Unit:

Iabcf_pu_polar =

6.2500 -90.0000

6.2500 150.0000

6.2500 30.0000

Phase Currents in Amps

Iabcf_amps_polar =

1.0e+003 *

1.0459 -0.0900

1.0459 0.1500

1.0459 0.0300

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0 0

0 0

0 0

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

0 0

0 0

0 0

177

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

0 0

0 0

0 0

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

0 0

0 0

0 0

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

0 0

Vbcf_pu_polar =

0 0

Vcaf_pu_polar =

0 0

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

0 0

Vbcf_volts_polar =

0 0

Vcaf_volts_polar =

0 0

178

E8.11 477kcmil 3LG MID

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

4

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

50

Zseq =

0.0599 + 0.3049i

0.0200 + 0.2383i

0.0200 + 0.2383i

+++++++++++++3-Phase Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0 0

4.1815 -85.2119

0 0

Sequence Currents in Amps:

Iaseq_amps_polar =

0 0

699.7635 -85.2119

0 0

Phase Currents in Per-Unit:

Iabcf_pu_polar =

4.1815 -85.2119

4.1815 154.7881

4.1815 34.7881

Phase Currents in Amps

Iabcf_amps_polar =

699.7635 -85.2119

699.7635 154.7881

699.7635 34.7881

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

1.0e-015 *

0 0

0.1110 0

0 0

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

1.0e-010 *

0 0

0.3830 0

0 0

Phase Voltages in Per-Unit(L-N):

179

Vabcf_pu_polar =

0.0000 0

0.0000 -120.0000

0.0000 120.0000

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

0.0000 0

0.0000 -120.0000

0.0000 120.0000

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

0.0000 30.0000

Vbcf_pu_polar =

0.0000 -90.0000

Vcaf_pu_polar =

0.0000 150.0000

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

0.0000 30.0000

Vbcf_volts_polar =

0.0000 -90.0000

Vcaf_volts_polar =

0.0000 150.0000

180

E8.12 477kcmil 3LG RE

SBgen =

100000000

VBgen =

22000

ZBL =

1.1903e+003

Enter fault type(1=SLG,2=DLG,3=LL,4=3LG):

4

Enter percentage of line from sending-end that is involved with

fault(e.g.0,50,100):

100

Zseq =

0.1198 + 0.5399i

0.0399 + 0.3166i

0.0399 + 0.3166i

+++++++++++++3-Phase Fault Analysis+++++++++++++

Sequence Currents in Per-Unit:

Iaseq_pu_polar =

0 0

3.1335 -82.8134

0 0

Sequence Currents in Amps:

Iaseq_amps_polar =

0 0

524.3773 -82.8134

0 0

Phase Currents in Per-Unit:

Iabcf_pu_polar =

3.1335 -82.8134

3.1335 157.1866

3.1335 37.1866

Phase Currents in Amps

Iabcf_amps_polar =

524.3773 -82.8134

524.3773 157.1866

524.3773 37.1866

Sequence Voltages in Per-Unit(L-N):

Vaseq_pu_polar =

0 0

0.0000 -7.1250

0 0

Sequence Voltages in Volts(L-N)

Vaseq_volts_polar =

0 0

0.0000 -7.1250

0 0

181

Phase Voltages in Per-Unit(L-N):

Vabcf_pu_polar =

0.0000 -7.1250

0.0000 -127.1250

0.0000 112.8750

Phase Voltages in Volts(L-N):

Vabcf_volts_polar =

0.0000 -7.1250

0.0000 -127.1250

0.0000 112.8750

Phase Voltages in Per-Unit(L-L):

Vabf_pu_polar =

0.0000 22.8750

Vbcf_pu_polar =

0.0000 -97.1250

Vcaf_pu_polar =

0.0000 142.8750

Phase Voltages in Volts(L-L)

Vabf_volts_polar =

0.0000 22.8750

Vbcf_volts_polar =

0.0000 -97.1250

Vcaf_volts_polar =

0.0000 142.8750

182

BIBLIOGRAPHY

[1] Gonen, T. 2009. Electrical power transmission system engineering analysis and

design, 2nd

ed. Florida: CRC Press.

[2] Electrical Power Research Institute. 1979. Transmission line reference book 345

kV and above. Palo Alto, CA: EPRI.

[3] Kiessling, F., Nefzger, P., Nolasco, J.F., and Kaintzyk, U. 2003. Overhead power

lines. New York: Springer.

[4] Gonen, T. 2008. Electrical power distribution system engineering, 2nd

ed. Florida:

CRC Press.

[5] Sadaat, H. 2002. Power system analysis. New York: McGraw-Hill.

[6] Granger, J. J. and W. D. Stevenson. 1994. Power system analysis. New York:

McGraw-Hill.

[7] Ray, S. 2012. Electrical power systems: concepts, theory and practice, 4th

ed. New

Delhi: PHI Learning Private Limited.

[8] Glover, J. D., Sarma M. S., Overbye T. J. 2010. Power system analysis and design,

5th

ed. Stamford, CT: Cengage Learning

[9] Bayliss, C., Hardy, B. 2007. Transmission and distribution electrical engineering,

3rd

ed. Burlington, MA: Elsevier Ltd.

[10] Short, T.A. 2004. Electric power distribution handbook. New York: CRC Press.

[11] Pansini, A.J. 2006. Electrical distribution engineering, 3rd

ed. Florida: CRC Press.

[12] Wadhwa, C.L. 2009. Electric power systems, 2nd

ed. Tunbridge Wells: New

Academic Science Ltd.