ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
50-Point Addressable Fire Alarm Control Panel Model FC901
Answers for infrastructure
CerberusTM PRO Fire Safety & Security Products
Cerberus PRO Fire Safety
9813
FACP for simple-size buildings
Product Overview Model FC901 is an addressable FACP that provides a cost-effective solution for simple fire-alarm system applications.
Small and compact in design, Model FC901 is ideal for small fire-protection applications using less than 50 addressable devices: retail outlets / strip malls doctors’ offices dry cleaner shops restaurants, etc.
With its built-in DACT and two (2) NACs, Model FC901 is powerful enough to economically meet the needs of these applications. Each 50-point FACP is FM, CSFM (Listing No.: 7165-0067:0259) and FDNY (Certificate of Approval: #6104) Approved.
Specifications The Model FC901 FACP consists of a main board (Model FCM901-U3); a 170-Watt power supply (Model FP2011-U1), and a Model FH901-U3 / R3 system enclosure. The programming software for Model FC901 is held in flash electrically erasable programmable read-only memory (EEPROM).
Main Board The Model FCM901-U3 main board provides system display and control, as well as connections for system field wiring, via removable terminal blocks.
The 3.5-inch (8.9 centimeters) by 1.5” (3.8 centimeters) liquid-crystal display (LCD) screen shows all system messages and event status. Each event may have a custom message up to 28 characters that describes the event’s location.
The backlit LCD screen illuminates on any system event or manual key press. New, ‘unacknowledged’ events are indicated by a flashing exclamation point ('!'). Once ‘acknowledged,’ the exclamation point changes to a check mark ( ‘√ ’). A system-status line shows the quantity of events presently active.
The main board supports system-status light-emitting diodes (LEDs), based upon the following conditions of Model FC901:
Power Alarm Trouble Supervisory Ground Fault
An addressable fire alarm control panel (FACP) comprised of the following three (3) system components: Main board (Model FCM901-U3) 170-Watt power supply (Model FP2011-U1) System enclosure (Model FH901-U3 / R3)
System features: Supports 50 addressable devices on one (1) ‘Class A’,
or one (1) ─ two (2) ‘Class B’ circuits Includes one (1) ‘Class A’, or two (2) ‘Class B’
notification appliance circuits (NACs) Built-in digital alarm communication transmitter
(DACT) Built-in RS─485 connection for remote annunciators Resettable and non-resettable 24VDC auxiliary
power Optional connectivity to a leased-line / city-tie
module Off-normal warning message prior to reset Fast and easy set-up with custom-configuration tool
Alphanumeric keypad for manual configuration
UL 864 9th Edition Listed; FM, CSFM & NYC Fire Department Approved
s Industry, Inc. Building Technologies Division
CerberusTM PRO
Specifications ─ (continued) There are also LEDs to indicate when audible circuits are ‘active’ or ‘silenced.’ The main board supports four (4) system-control buttons, including: Acknowledge; Alarm Silence; Unsilence, and Reset.
The system offers an off-normal warning feature, alerting users when active devices are not ready for reset. These active devices may include manual stations that have not been reset; smoke detectors with smoke remaining in the optical chamber, etc.
Additionally, the main board supports an alphanumeric keypad, as well as navigation keys, which are used for scrolling maintenance functions and system configuration.
The main board supports connection for up to 50 addressable devices, via one (1) ‘Class A’, or one (1) to two (2) ‘Class B’ circuits. The loop supports all C-NET devices, including the Cerberus PRO Fire Safety and Model ‘H’-series devices. The main board also supports one (1) ‘Class A’ or two (2) ‘Class B’ NACs.
Each NAC supports a maximum 2.5 Amps ─ with 2.5 Amps, max. allowed between the NACs. Each NAC can be set to a synchronized strobe, for horn-strobe devices, or for audible devices. Audible devices can be set for: ‘STEADY’ ‘ANSI Temporal 3’ ‘March Time 30 / 60 / 120 Codes’
The main board supports four (4) ‘Form C’ relays for Alarm, Trouble, Supervisory and user-programmable events. Each relay is rated at 2 Amps at 30VDC maximum, resistive. The main board supports two (2) auxiliary 24VDC connections. Upon system reset, one (1) connection interrupts the power for five seconds for use with (4) four-wire conventional detectors. Each auxiliary-power output is 24VDC, nominal ─ rated at 0.75 Amps.
The main board contains a built-in DACT (Model FCA2015-A1), which provides communication between Model FC901 and with the central or remote monitoring station. The built-in DACT supports two (2) separate programmable accounts, as well as two (2) connections to the public-switched telephone network.
The connections support RJ31X male connectors.
The main board contains a battery-charging circuit, providing connection to lead-acid batteries rated at 24VDC, nominal. The main board can charge up to 18 AH batteries.
The main board contains a universal serial bus (USB) connector that supports connection for system configuration and module firmware upload, via the custom-configuration tool.
Model FC901 can be configured using the configuration tool or manually from the alphanumeric keypad on the main board. An auto-configuration feature creates a basic system configuration of all connected devices to accelerate initial system commissioning.
170-Watt Power Supply The Model FCM901-U3 main board also supports connection to the system power supply. The 170-Watt power supply (Model FP2011-U1) incorporates a 4.0A, non-resettable slow-blow fuse on the primary input, and includes a built-in AC-line filter for surge and noise suppression. Model FP2011-U1 mounts in a standard Siemens ─ Fire Safety enclosure, and there are no serviceable Siemens ─ Fire Safety parts to be maintained.
50-Point Addressable System Enclosure The Model FH901-U3 / R3 enclosure for the 50-point addressable fire system, Model FC901, supports all system modules. The enclosure also supports 12AH batteries. Note: For systems requiring larger than 12AH batteries,
use a UL Listed battery box.
The Model FH901-U3 / R3 enclosure for the 50-point panel is comprised of a dual-mounting setup that allows the main board to be partially mounted in a lower-to-upper position. When temporarily installed in the lower position, technicians are allowed more space to install field wiring at the time of system set-up. When field-wiring installation is complete, the main board shall be moved to the upper position for standard mounting prior to applying power to the system.
Additionally, the enclosure supports an optional battery bracket (Model FHA901-U1) that can be used to secure batteries up to 12AH. Model FHA901-U1 is required to comply with seismic certification, pursuant to ASC / SEI 7-05, Section 13.2.2.
A flush-mount trim kit (Model FHA902-U1 / R1) is also available for use when flush mounting Model FH901-U3 / R3.
Optional Accessories
The Model FC901 FACP has the capability of operating an optional leased-line, city-tie module (Model FCI2020-U1) that provides a local-energy output for municipal call-box connection. The leased-line, city-tie module is installed on the back of the main board of the Model FC901 FACP, and all field wiring is connected to the main board.
s Industry, Inc. Building Technologies Division
CerberusTM PRO
Specifications ─ (continued) Model FC901 contains a built-in RS─485 connection on the main board, thus eliminating the need for an additional communication module. The fire-system displays (FSD901-U3 / R3) are remote LED / LCD units that show the existing status of the Model FC901 FACP.
The Model FSD901-U3 / R3 optional display supports the following LEDs for system-status conditions: Power Alarm Trouble Supervisory Ground-Fault
There are also LEDs to indicate when audible circuits are ‘active’ or ‘silenced.’ The main board supports four (4) system-control buttons, including: Acknowledge; Alarm Silence; Unsilence, and Reset.
For Model FSD901-U3 / R3, a LED will illuminate for any given Alarm, Supervisory and Trouble Cerberus PRO-system event. A 3.5-inch (8.9 centimeters) by 1.5” (3.8 centimeters) LCD screen will give details of the event in alphanumeric form. The display screen can be scrolled to reveal additional events. Optional remote-system-control capabilities are also available.
The dimensions (based upon connection to a one-height-unit enclosure) for Model FC901 are as follows:
Approximate size: 16.25” (41.3 cm.) [H]; 18” (46 cm.) [W]; 5” (41.3 cm.) [D]
The weight (without operating unit or batteries) is approximately 9 Lbs [4082 g].
Temperature and Humidity Range Model FC901 is UL 864 9th Edition Listed for indoor dry locations within a temperature range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).
Related Documentation Product Data Sheet Number
170-Watt power supply 9806
Leased-Line / city-tie module 9810
Details for Ordering Model
Number Part
Number Description
FCM901-U3 S54433-B101-A1 Cerberus PRO Main Board {for 50-point FACP}
FP2011-U1 S54400-Z59-A1 170-Watt Power Supply
FH901-U3 S54433-B103-A3 System Enclosure, Black {for 50-point FACP}
FH901-R3 S54433-B103-A4 System Enclosure, Red {for 50-point FACP}
Optional Accessories
Model Number
Part Number
Description
FHA901-U1 S54433-B107-A1 Battery Bracket
FHA902-U1 S54433-B106-A1 Flush-Mount Trim Kit, Black
FHA902-R1 S54433-B106-A2 Flush-Mount Trim Kit, Red
FCI2020-U1 S54400-A57-A1 Leased-Line / City-Tie Module
FSD901-U3 S54433-C102-A1 System Display, Black {for 50-point system}
FSD901-R3 S54433-C102-A2 System Display, Red {for 50-point system}
s CerberusTM PRO
Siemens Industry, Inc. ─ Building Technologies Div. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO
NOTICE ─ The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information.
Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer.
Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer.
Building Technologies Division SII ─ Fire Safety
[Printed in U.S.A ]
August 2012 ─ Supersedes sheet dated 5/12 (Rev. 4)
MH20845
®
Sealed Rechargeable
MODEL PS-1290 F212 Volt 9.0 Amp. Hr.
Battery
www.power-sonic.com BAT
T ERY
MUSTB ERECYC
LED
PbNONSPILLABLE
L
HT H
W
7.95
6.35
3.4
0.8
Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice.
Physical Dimensions: in (mm)
Features
Absorbent Glass Mat (AGM) technology for superior performance
Valve regulated, spill proof construction allows safe operation in any position
Power/volume ratio yielding unrivaled energy density
Rugged impact resistant ABS case and cover (UL94-HB)
Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certifi ed
U.L. recognized under fi le number MH 20845
•
•
•
•
•
•
Performance Specifi cations
Nominal Voltage ........................................................................ 12 volts (6 cells)
Nominal Capacity
20-hr. (450mA to 10.50 volts) ....................................................... 9.00 AH
10-hr. (810mA to 10.50 volts) ......................................................... 8.10 AH
5-hr. (1.44A to 10.20 volts) ........................................................... 7.20 AH
1-hr. (5.4A to 9.00 volts) .............................................................. 5.40 AH
15-min. (14.4A to 9.00 volts) .............................................................. 3.60 AH
Approximate Weight ........................................................... 6.00 lbs. (2.72 kg)
Energy Density (20-hr. rate) .............................. 1.92 W-h/in3 (116.94 W-h/l)
Specifi c Energy (20-hr. rate) ............................. 18.00 W-h/lb (39.68 W-h/kg)
Internal Resistance (approx.) ...................................................... 13 milliohms
Max Discharge Current (7 Min.) ................................................ 27.0 amperes
Max Short-Duration Discharge Current (10 Sec.) .................. 90.0 amperes
Shelf Life (% of nominal capacity at 68°F (20°C))
1 Month ...................................................................................................... 97%
3 Months ..................................................................................................... 91%
6 Months .................................................................................................... 83%
Operating Temperature Range
Charge .. ........................................................... -4°F (-20°C) to 122°F (50°C)
Discharge ....................................................... -40°F (-40°C) to 140°F (60°C)
Case ...................................................................................................... ABS Plastic
Power-Sonic Chargers ................................................ PSC-12800A, 12800A-C
PS-1290
www.power-sonic.comTo ensure safe and effi cient operation always refer to the latest edition of our Technical Manual, as published on our website.All data subject to change without notice.
Terminals (mm)
F2 - Quick disconnect tabs, 0.250” x 0.032” - Mate with AMP. INC FASTON “250” series
•
12 Volt 9.0 AH
L: 5.95 (151) W: 2.56 (65) H: 3.70 (94) HT: 3.86 (98)
CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650
ChargingCycle Applications: Limit initial current to 2.7A. Charge until battery voltage (under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7 volts until current drops to under 90mA. Battery is fully charged under these conditions, and charger should be disconnected or switched to “float” voltage.
“Float” or “Stand-By” Service: Hold battery across constant voltage source of 13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition.
Note: Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged within 6 months of storage, otherwise permanent loss of capacity might occur as a result of sulfation.
ChargersPower-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to the Charger Selection Guide in our specification sheets for “C-Series Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our Technical department for advice if you have difficulty in locating suitable models.
Cap
acity
Ret
entio
nR
atio
(%)
Standing Period (Months)
100
80
60
40
00 2 4 6 8 10 12 14 16 18 20
40oC(104oF)
30oC(86oF)
20oC(68oF)
5oC(41oF)
Charging is notnecessary unless 100% of capacity is required.
Charging beforeuse is necessaryto help recoverfull capacity.
Charge may failto restore fullcapacity. Do notlet batteries reachthis state.
100
80
60
40
20
00 1 2 3 4
Ambient Temperature 20˚C (68˚F)
Float Charging Voltage2.25 - 2.30 V/Cell
Ret
entio
nC
apac
ity(%
)
Years
120
100
80
60
40
20
00 200 400 600 800 1000 1200
Number of Cycles
1. Discharge Current 0.2C (Final Voltage 1.7V/Cell)2. Charge Current: 0.1C3. Ambient Temperature: 20oC to 25oC (68oF to 77oF)R
eten
tion
Cap
acity
(%)
DischargeDepth 30%
DischargeDepth 100%
DischargeDepth 50%
Discharge Characteristics
Discharge Time vs. Discharge Current
Shelf Life & Storage
Life Characteristics in Stand-By Use
Life Characteristics in Cyclic Use
PS-1290 12 Volt 9.0 AH
CUSTOMER SERVICETel: +1-619-661-2030 Fax: [email protected]
INTERNATIONAL SALESTel: +1-650-364-5001 Fax: [email protected]
DOMESTIC SALESTel: +1-619-661-2020Fax: [email protected]
TECHNICAL SUPPORTTel: +1-619-661-2020 Fax: [email protected]
Contact Information www.power-sonic.com
Further InformationPlease refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), ISO certification, etc..
408 1M
13.0
12.0
11.0
10.0
9.0
8.0
14.0
Term
inal
Vol
tage
(V)
Ambient Temperature 20oC (68oF)
1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0
Discharge Time
FinalVoltage
min h
0.450.901.8
4.5
9.0
18
0.45 0.90 1.8 4.5 9.0 18Discharge Current (A)
201510
5
2
1
30
10
5
Dis
char
ge T
ime
40oC (104oF)20oC (68oF) 0oC (32oF)
min
h
10.2V
9.6V
9.0V
8.1V
FinalVoltage10.5V
ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
Remote Annunciator for the 50-Point Addressable System Models FSD901-U3, FSD901-R3
Answers for infrastructure
CerberusTM PRO Fire Safety & Security Products
Cerberus PRO Fire Safety
9817 Remote Annunciator for the 50-Point Fire Alarm Control Panel
Product Overview
Model FSD901-U3 / R3 are separate LED / LCD remote annunciators that show the existing status of the 50-point addressable FACP (Model FC901). Each remote annunciator connects to the 50-point FACP through a built-in RS─485 connection on the main board.
A 3.5-inch (8.9 centimeters) by 1.5” (3.8 centimeters) LCD screen will give details of the event in alphanumeric form. The display screen can be scrolled to reveal additional events.
Optional remote-system-control capabilities are also available. A keyswitch is also provided to prevent unauthorized access to the control operations.
Additionally, Model FSD901-U3 / R3 contains navigation keys that are used for scrolling through the list of FACP events.
The remote annunciators are CSFM (Listing Number: 7165-0067:0259) and FDNY (Certificate of Approval: #6104) Approved.
Each Model FSD901-U3 / R3 Remote Annunciator supports the following LEDs for system-status conditions: Power, Alarm, Trouble, Supervisory and Ground-Fault. Note: Each remote annunciator can have its own ‘Normal’
system message. Further, Model FSD901-U3 / R3 can be configured to display any aforesaid system command, or any combination of FACP events.
There are also LEDs to indicate when audible circuits are ‘active’ or ‘silenced.’ Each remote annunciator supports four (4) system-control buttons, including: ‘Acknowledge’; ‘Alarm Silence’; ‘Unsilence’, and ‘Reset’. The dimensions for each Model FSD901-U3 / R3 remote annunciator are as follows:
Approximate size: 8.5” (21.6 cm.) [H]; 11.25” (28.8 cm.) [W]; 2.5” (6.4 cm.) [D]
Note: Up to eight (8) remote annunciators are supported for each 50-point addressable FACP.
The weight of each remote annunciator is approximately 4 Lbs [1814 g].
• Displays the existing status of the 50-point addressable fire alarm control panel (FACP)
• Liquid-crystal display (LCD) screen shows the same event message display as the main FACP display
• Includes light-emitting diodes (LEDs) for system status
• Supports ‘Acknowledge’; ‘Alarm Silence’; ‘Unsilence,’ and ‘Reset’ controls
• Keyswitch prevents unauthorized access • UL 864 9th Edition Listed;
CSFM & NYC Fire Department Approved
s CerberusTM PRO
Siemens Industry, Inc. ─ Building Technologies Div. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO
NOTICE ─ The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information.
Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer.
Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer.
Building Technologies Division SII ─ Fire Safety
[Printed in U.S.A ]
March 2012 ─ New Issue (Rev. 0)
Temperature and Humidity Range Each Model FSD901-U3 / R3 Remote Annunciator is
UL 864 9th Edition Listed for indoor dry locations within a temperature range of 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).
Related Documentation Product Data Sheet Number
50-point Addressable System 9813
Details for Ordering Model
Number Part
Number Description
FSD901-U3 S54433-C102-A1 Remote Annunciator, Black {for the 50-point addressable system}
FSD901-R3 S54433-C102-A2 Remote Annunciator, Red {for the 50-point addressable system}
aes-corp.com
7707 Fire Subscribers
www.aes-corp.com
Feature Highlights• Leverages state of the art technology• Applies advanced security protection• Offers flexible power and configuration options• Engineered for backward compatibility with legacy systems• Enables future ready capabilities• Provides instant subscriber status through front panel with Power and Trouble LEDs,
a backlit LCD display, and Menu/Silence button • Includes robust Multiple Communication Technologies (MCT) feature• Emulates virtual keypad• Improves functionality with an adaptive Graphic User Interface (GUI) for programming
via smartphones, tablets and PCs• Plus many more…
Key Benefits • Built upon the solid foundation of AES-IntelliNet patented mesh radio technology for use in private
licensed wireless networks• Protects subscriber units against unauthorized access and rogue activity with a password-protected
Dealer Code• Makes programming and streamlined troubleshooting easy with user friendly interface• Adds integrated supervision of AES-IntelliPro full data module• Provides versatile power options:
(1) Direct from the Fire Alarm Control Panel (FACP) without requiring an electrician onsite and without Subscriber backup battery; (2) Directly from the FACP with Subscriber backup battery; or (3) Traditional installation with plug in Class 2 low power transformer
• Allows for enhancement upgrades and an expanded number of new features to be added easily with highly flexible and scalable alarm communications infrastructure
• Rigorously tested to the highest industry standards and future ready to meet emerging NFPA code and UL standards
A Newer, Smarter Alarm Communications Platform
Enhanced Wireless Fire Alarm MonitoringPowered by AES enhanced mesh radio technology, IntelliNet 2.0 7707 Fire Subscribers are next generation universal wireless communicators that provide advanced security protection for any new or existing alarm monitoring network. The AES Model 7707 is ideal for commercial fire applications. With the AES-IntelliPro full data module option, they are the ideal drop-in replacement for Plain Old Telephone Service (POTS) lines.
The red metal enclosure comes with a key lock and front panel LCD backlit display with intuitive view that provides an instant visual of the subscriber status. The user friendly GUI makes it easy to program AES subscriber units via a smartphone, laptop, tablet, or integrated Universal Serial Bus (USB)—without the need for special cables or having to use a handheld programmer. Additional knockouts make it easier to mount for faster installation.
IntelliNet 2.0 Private Wireless Mesh Radio Network
The IntelliNet 2.0 Fire Subscriber has an 8 Zone modular design for expansion with normal and reverse polarity, POTS and DACT interfaces with an option for the 7794A AES-IntelliPro full data module add-on accessory board. AES subscribers’ intelligent software automatically detects new hardware and devices to reduce installation time.
An AES certified WiFi accessory allows seamless wireless connectivity for configuration and programming. A laptop, Ethernet cable, or a Wi-Fi USB dongle is required for IntelliNet 2.0 programming, handheld programmers will not work with 2.0 units. A FACP Power Supply Adapter is required for certain configurations when using flexible power options. The forward compatible design allows for feature add-ons, engineered to adapt seamlessly with future software upgrades as technology advances. IntelliNet 2.0 allows configuration cloning for fasterinstallation time.
The AES 7707 was designed with quick configuration and installation in mind to make it easier for field technicians to get in, out, and on to the next install.
Visit our Fire Marshal Resources web page for official NFPA and UL Listings: aes-corp.com/products/fire/fire-marshal-resources
www.aes-corp.com
How to Order 7707 Fire
www.aes-corp.com
IntelliNet 2.0 Fire Subscribers
2.0 PREMIUM (UL & ULC Listed)
7707P-88-M IntelliNet 2.0 Fire Subscriber, 8 Zone with Multiple Communication Technologies (MCT), Red Enclosure
7707P-88-ULP-M IntelliNet 2.0 Fire Subscriber, 8 Zone with 7794A AES-IntelliPro, and integrated onboard Local Annunciator plus MCT, Red Enclosure
7707P-44-M IntelliNet 2.0 Fire Subscriber, 4x4 Zone (4 Reversing Polarity, 4 Supervised) with Multiple Communication Technologies (MCT), Red Enclosure
7707P-44-ULP-MIntelliNet 2.0 Fire Subscriber, 4x4 Zone (4 Reversing Polarity, 4 Supervised) with 7794A AES-IntelliPro, and integrated onboard Local Annunciator plus MCT, Red Enclosure
2.0 ACCESSORIES
7794A Standalone AES-IntelliPro Fire full data module add-on accessory board with firmware for new IntelliNet 2.0 units only, cannot be used in legacy units
77-WiFi AES certified WiFi adapter
77-FACPA FACP Power Supply Adapter for internal mount
77-FACPA-KIT External installation hardware for 2-way Junction Box
Legacy Fire Subscribers
7706-ULF Integrated Fire Monitoring System, Red Enclosure
7788F-ULP-P Legacy Fire Subscriber, 8 Zone with 7795 AES-IntelliPro (7794 full data module, 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure
7788F-ULP Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones with 7794 AES-IntelliPro, Red Enclosure
7788F Legacy Fire Subscriber, 8 Zone, 8 Supervised Zones, Red Enclosure
7744F-ULP-P Legacy Fire Subscriber, 4 Zone with 7795 AES-IntelliPro (7794 full data module, 7762 hardware supervisory module, and 7740 Local Annunciator), Red Enclosure
7744F-ULP Legacy Fire Subscriber, 4x4 Zone, 4 Supervised Zones with 7794 AES-IntelliPro, Red Enclosure
7744F Legacy Fire Subscriber, 4x4 Zone, 4 Reversing Polarity, 4 Supervised Zones, Red Enclosure
LEGACY ACCESSORIES
7794 Standalone AES-IntelliPro Fire full data module add-on accessory board for legacy units only, please see 7794A above for IntelliNet 2.0 version
www.aes-corp.comAES Corporation | 285 Newbury Street | Peabody, MA 01960 United States
© Copyright 2018 AES Corporation and AES-IntelliNet® are registered trademarks of AES Corporation
7707_03222018_F
D I M E N S I O N S13”H x 8.5”W x 4.5”D(33cmH x 21.5cmW x 11.4cmD)
W E I G H T5.8 lbs (2.6 kilograms)excluding battery13 lbs (5.9 kilograms) with10 Ah battery
R A D I O F R E Q U E N C YStandard Frequency Range:450-470 MHzContact AES for other UHFand VHF frequencies
A N T E N N A2.5 dB tamper resistant antenna included, mounts on enclosure Optional remote mountingantenna available
P O W E R I N P U TAC SOURCESTransformer: Class 216.5V AC nominal output1.9 A max current (40 VA MIN)ELK ELK-TRG1640,MG ELECTRONIC SALES MGT1640,or AES 1640 (not included)DC SOURCES (includes FACP)24V DC Regulated Power Supplywith Subscriber Rechargeable Battery1.9 A max current
B A C K U P B AT T E R Y10-12 Ah, UL recognized lead acid gel cell, size based on subscriber configuration
P O R T SEthernet for configurationand message communicationUSB access for software upgrade
R E M O T E A N N U N C I AT O RAES Model 7740 Remote Annunciator, supervised
C O M PAT I B L E R E C E I V E R S7705i AES-MultiNet Receiver
C O N F I G U R AT I O N I N T E R F A C EWeb browser capable device accessible via smartphone, tablet, laptop, or PC
C U R R E N T C O N S U M P T I O NStandby w/ charged backup battery: 200 mA (1.2 A Transmitting)Standby + charging backup battery: 900 mA (1.9 A Transmitting - MAX)
P O W E R O U T P U T2 or 5 WattsFactory set
E N C L O S U R E M AT E R I A LSteel with paint finish
F I N I S H C O L O RRed
V I S U A L I N D I C AT O R SFront panel LCD (2 x 20 alphanumeric characterbacklit display)Power and Trouble LEDs (ALM, Trouble, Tx, Rx, WA)
A L A R M S I G N A L I N P U T S / Z O N E S· 8 individually programmable E.O.L. type zone inputs· 4+4: 4 reverse polarity input and 4 individually programmable E.O.L. type zone inputs· Optional 7794A AES-IntelliPro for full data via Contact ID, Pulse, Modem IIe and Modem IIIa2
U L L I S T I N G SUL 864 10th EditionStandard for Control Units and Accessories for Fire Alarm SystemsULC S559-04 1st EditionEquipment for Fire Signal Receiving Centres and Systems
T R O U B L E O U T P U T— A C K D E L AY/A N T E N N A C U TForm C relay, fail secure, rated 24VDC 1A resistive, unsupervised
R E S E T B U T T O NLocated on main circuit board
O P E R AT I N G T E M P E R AT U R E32 to 120°F (0 to 49°C)
S T O R A G E T E M P E R AT U R E14 to 140°F (-10 to 60°C)
R E L AT I V E H U M I D I T Y0 to 93%, non-condensing
R E C H A R G E C A PA B I L I T YWill charge 12V battery size from 10-12 Ah
Technical Specifications 7707 Fire
Contact UsFor pricing and availability or to learn more about IntelliNet 2.0, please call your local AES Sales Representative at (800) 237-6387 or email [email protected].
Sealed Rechargeable
MODEL PS-12120 F212 Volt 12.0 Amp. Hr.
Battery
www.power-sonic.com
BATT
ERY
MUST BE RECYC
LED
PbNONSPILLABLE
MH20845
®
L
HT
W
H
Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice.
Physical Dimensions: in (mm)
Features
Absorbent Glass Mat (AGM) technology for superior performance
Valve regulated, spill proof construction allows safe operation in any position
Power/volume ratio yielding unrivaled energy density
Rugged impact resistant ABS case and cover (UL94-HB)
Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certifi ed
U.L. recognized under fi le number MH 20845
•
•
•
•
•
•
Performance Specifi cations
Nominal Voltage ........................................................................ 12 volts (6 cells)
Nominal Capacity
20-hr. (600mA to 10.50 volts) ....................................................... 12.0 AH
10-hr. (1.1A to 10.50 volts) ............................................................ 11.0 AH
5-hr. (2.1A to 10.20 volts) ............................................................ 10.5 AH
1-hr. (7.25A to 9.00 volts) ............................................................. 7.25 AH
15-min. (21.5A to 9.00 volts) .............................................................. 5.38 AH
Approximate Weight ........................................................... 7.92 lbs. (3.59 kg)
Energy Density (20-hr. rate) ............................... 1.69 W-h/in3 (103.41 W-h/l)
Specifi c Energy (20-hr. rate) .............................. 18.18 W-h/lb (40.08 W-h/kg)
Internal Resistance (approx.) ...................................................... 20 milliohms
Max Discharge Current (7 Min.) ............................................... 36.0 amperes
Max Short-Duration Discharge Current (10 Sec.) ................ 120.0 amperes
Shelf Life (% of nominal capacity at 68°F (20°C))
1 Month ...................................................................................................... 97%
3 Months ..................................................................................................... 91%
6 Months .................................................................................................... 83%
Operating Temperature Range
Charge .. ........................................................... -4°F (-20°C) to 122°F (50°C)
Discharge ....................................................... -40°F (-40°C) to 140°F (60°C)
Case ...................................................................................................... ABS Plastic
Power-Sonic Chargers ........................................... PSC-122000A, 122000A-C
PS-12120
www.power-sonic.comTo ensure safe and effi cient operation always refer to the latest edition of our Technical Manual, as published on our website.All data subject to change without notice.
Terminals (mm)
12 Volt 12.0 AH
L: 5.95 (151) W: 3.86 (98) H: 3.70 (94) HT: 3.94 (100)
7.95
6.35
3.4
0.8
F2 - Quick disconnect tabs, 0.250” x 0.032” - Mate with AMP. INC FASTON “250” series
• F2 - Quick disconnect tabs, 0.250” x 0.032” - Mate with AMP. INC FASTON “250” series
•
CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650
ChargingCycle Applications: Limit initial current to 3.6A. Charge until battery voltage (under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7 volts until current drops to under 120mA. Battery is fully charged under these conditions, and charger should be disconnected or switched to “float” voltage.
“Float” or “Stand-By” Service: Hold battery across constant voltage source of 13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition.
Note: Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged within 6 months of storage, otherwise permanent loss of capacity might occur as a result of sulfation.
ChargersPower-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to the Charger Selection Guide in our specification sheets for “C-Series Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our Technical department for advice if you have difficulty in locating suitable models.
Cap
acity
Ret
entio
nR
atio
(%)
Standing Period (Months)
100
80
60
40
00 2 4 6 8 10 12 14 16 18 20
40oC(104oF)
30oC(86oF)
20oC(68oF)
5oC(41oF)
Charging is notnecessary unless 100% of capacity is required.
Charging beforeuse is necessaryto help recoverfull capacity.
Charge may failto restore fullcapacity. Do notlet batteries reachthis state.
100
80
60
40
20
00 1 2 3 4
Ambient Temperature 20˚C (68˚F)
Float Charging Voltage2.25 - 2.30 V/Cell
Ret
entio
nC
apac
ity(%
)
Years
120
100
80
60
40
20
00 200 400 600 800 1000 1200
Number of Cycles
1. Discharge Current 0.2C (Final Voltage 1.7V/Cell)2. Charge Current: 0.1C3. Ambient Temperature: 20oC to 25oC (68oF to 77oF)R
eten
tion
Cap
acity
(%)
DischargeDepth 30%
DischargeDepth 100%
DischargeDepth 50%
Discharge Characteristics
Discharge Time vs. Discharge Current
Shelf Life & Storage
Life Characteristics in Stand-By Use
Life Characteristics in Cyclic Use
PS-12120 12 Volt 12.0 AH
CUSTOMER SERVICETel: +1-619-661-2030 Fax: [email protected]
INTERNATIONAL SALESTel: +1-650-364-5001 Fax: [email protected]
DOMESTIC SALESTel: +1-619-661-2020Fax: [email protected]
TECHNICAL SUPPORTTel: +1-619-661-2020 Fax: [email protected]
®
Contact Information www.power-sonic.com
Further InformationPlease refer to our website www.power-sonic.com for a complete range of useful downloads, such as product catalogs, material safety data sheets (MSDS), ISO certification, etc..
0309 1M
13.0
12.0
11.0
10.0
9.0
8.0
14.0
Term
inal
Vol
tage
(V)
Ambient Temperature 20oC (68oF)
1.2 2.4 6 12 24 36 48 1 2 4 6 8 10 20 4 0
Discharge Time
FinalVoltage
min h
0.601.22.4
6.0
12
24
0.60 1.2 2.4 6.0 12 24Discharge Current (A)
201510
5
2
1
30
10
5
Dis
char
ge T
ime
40oC (104oF)20oC (68oF) 0oC (32oF)
min
h
10.2V
9.6V
9.0V
8.1V
FinalVoltage10.5V
Advanced multi-criteria fire detector that has dual-optical and thermal sensors Differentiates between deceptive phenomena and an actual fire (nuisance-alarm avoidance) Compatible with Siemens Model ‘H’-series devices on the same loop (with Cerberus PRO
fire-alarm control panels [FACPs] or FireFinder® XLS FACPs) Provides enhanced detection via forward-and-backward light-scattering technology Complies with NFPA 76 (Telco standard) as ‘VEWFD’ high-sensitivity detector UL Listed and FM Approved as a multi-criteria and ‘VEWFD’ fire detector
UL 268A Listed for direct air-duct (4,000 FPM) use
Supervisory temperature-monitoring feature
Remote sensitivity-measurement capability
Automatic environment compensation
Up to 22 application profiles
Tri-color detector status LED with 360° viewing
Environmental alternative to ionization detectors
Polarity insensitive utilizing SureWireTM technology
Low-temperature warning for sprinkler systems, per NFPA 25
Meets UL, NFPA 72 requirements for sensitivity self-monitoring
Compatible with: Legacy Model DB-11─series mounting bases Model 8720 / DPU (device programmer / loop tester)
Restriction of Hazardous Substances (RoHS) compliant
Responds to both flaming and smoldering-fire signatures
ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
Multi-Criteria Fire Detector [with ASAtechnologyTM] Model OOH941
Answers for infrastructure
CerberusTM PRO Fire Safety & Security Products
Intelligent Detection Devices
9904 Multi-Criteria Fire Detector [with ASAtechnologyTM]
Product Overview Model OOH941 is an advanced, multi-criteria fire detector that incorporates a redundant, optical / thermal sensor. Model OOH941 uses a distinctive forward / backward, light-scattering technology that provides state-of-the-art, unparalleled fire detection to the widest range of fire types.
Model OOH941 is programmable as a high-sensitivity detector, meeting the requirements of NFPA 76 Standard (for the Fire Protection of Telecommunications Facilities) as a Very Early Warning Fire Detector (VEWFD).
The Model OOH941 detector is a flexible, multi-purpose detector that provides a complete solution to meet detection needs. This type of detector can be field programmed for simultaneous and / or independent functionality, depending upon the exact customer and application requirements.
For example, the detector can simultaneously utilize the optical and heat sensors for enhanced fire detection (multi-criteria), as well as provide together independent outputs for heat detection. Any combination of the sensors is possible. The detector is extremely versatile and meets the following standards:
UL 268 compliant
UL Listed and ULC Listed; FM and CSFM Approved
s Industry, Inc. Building Technologies Division
CerberusTM PRO
Product Overview ─ (continued) • Multi-criteria fire detector ( UL 268) • Heat detector ( UL 521) with five (5) possible
field-selectable temperatures; combined with four (4) rate-of-rise options
• Direct, in-duct (plenum) detector ( UL 268A) • Supervisory monitoring for temperature ranges • NFPA 76 (Telco Standard) as VEWFD • Low-temperature warning signal at 40°F (4.4°C) ─ for sprinkler systems, per NFPA 25 / NFPA 72
Model OOH941 ─ which provides extremely accurate and reliable fire detection with built-in redundancy ─ utilizes advanced, multi-criteria detection technology known as ASA (Advanced Signal Analysis) that allows the detector to distinguish non-threatening deceptive phenomena.
For instance, the signals from the detector’s sensors are monitored and processed via the ASA-patented algorithm technology, which combines the signals into a neural network to create an intelligent, multi-criteria detector.
The encompassing result is a detector that provides enhanced detection to a wide range of products of combustion ─ while offering unsurpassed rejection to nuisance-alarm sources, such as: dust, steam, aerosols and other deceptive phenomena that could cause false alarms.
Since Model OOH941 is a (2) two-wire, addressable device, it is able to function as a multi-purpose detector ─ satisfying smoke and heat detection in a singular, aesthetically pleasing package. Further, Model OOH941 serves as an extremely cost-effective, viable solution that saves product, installation and maintenance costs (compared to other multiple-detector alternatives). Each detector fits into one (1) wall-or-ceiling footprint, and only occupies one (1) address on the signal-line circuit (SLC).
A patented forward-and-backward, light-scattering technology ─ which is able to distinguish both small and large products of combustion ─ operates at the core of each Model OOH941 detector.
Additionally, each Model OOH941 provides an environmental-friendly solution to ionization detectors, eliminating the need for a radioactive source and eventual disposal requirements. Thus, each detector is capable of detecting both smoldering and flaming fire ─ all in ecologically efficient manner ─ and is a valid, RoHS-compliant (Restriction of Hazardous Substances) detection alternative to ionization detectors.
Two (2) thermal sensors make each Model OOH941 detector a robust, reliable device suitable for the most challenging applications.
Operation
Forward-and-Backward Light-Scattering Technology
1. Heat sensors 4. Forward scatterer 2. Receiver 5. Labyrinth 3. Backward scatterer
The high-quality, optical-electronic measuring chamber for each Model OOH941 houses the following components:
Two (2) optical transmitters One (1) optical receiver Two (2) thermal sensors
The transmitters illuminate the smoke particles from different angles: one sensor acts as forward scatterer, the other sensor as a backward scatterer. The scattered light then hits the receiver (photodiode) and generates a measurable electric signal. The combination of a forward-and-backward scatterer facilitates optimum detection, as well as differentiates between light-and-dark particles / particle size.
This type of detection creates standardized, responsive behavior, thus optimizing the differentiation between wanted signals and deceptive phenomena. In addition, the heat sensors make it possible to detect fires without smoke generation.
This scenario generates the following advantages: Early detection of all fire types of fire ─ whether they
generate light-or-dark smoke, or no smoke The fire detector can be operated at a lower sensitivity
level, thus achieving a higher immunity against false alarms that may otherwise be caused by cold aerosols (e.g. ─ by smoking, electrical welding, etc.).
In the case of an open fire, the smoke sensitivity is heightened by a temperature increase ─ which means that a detection-reliability level that is comparable to a wide-spectrum smoke detector ─ can be achieved and maintained.
Note: For Model OOH941 compatibility to FireFinder® XLS, the XLS FACP requires Model PMI-2 (no firmware upgrade required), or Model PMI (firmware Rev. 9 or higher is required). The detector’s compatibility also requires both of following: - Rev. 9 (or higher) ZEUS custom-configuration software - Rev. 6 (or higher) Device Loop Card (DLC) firmware
s Industry, Inc. Building Technologies Division
CerberusTM PRO
Operation ─ (continued)
Field-Device Programmer / Test Unit Model OOH941 is compatible with the Device Program / Test Unit accessory, which is used to program and verify the address of the detector. The technician selects the accessory’s program mode, and enters the desired address. Model 8720 / DPU automatically sets and verifies the address and tests the detector.
Model 8720 / DPU eliminates the need for cumbersome, unreliable mechanical programming methods ─ such as dials or switches ─ and reduces installation and service costs by electronically programming and testing the detector prior to installation.
Model 8720 / DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programmer and testing equipment from practically any location.
When in ‘test’ mode, Model 8720 / DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly.
Field-selectable application profiles Model OOH941 provides 22 user-friendly, field-selectable application profiles, indentified with universally known names (e.g. ─ Hotel, Telco, Office, Parking Garage, Dormitory, and Data Center etc.) Refer to installation manual: P/N ─ A6V10324655 for a complete list and description of application profiles.
Due to generic-name classification, no cross-reference tables are required as the application name resides in the panel’s configuration tool. This user-friendly feature ─ along with the algorithms provided by ASAtechnology ─ provides a reliable, field-configurable detector suitable for an array of applications.
Field-selectable temperature settings Model OOH941 provides five (5) field-selectable temperature thresholds, ranging from 135°F to 175°F (57°C to 79°C), with fixed and rate-of-rise options. These ranges provide maximum flexibility to program and to easily adjust the temperature settings that suit multi-application needs within a building or changing environmental conditions. Additionally, Model OOH941 can be configured to provide a low-temperature warning signal at 40°F (4.4°C).
This configuration (along with connection to a compatible fire alarm control panel {FACP}) meets NFPA 72 requirements for sprinkler-temperature monitoring, and serves as prevention of water freezing in pipes for water-based suppression systems.
Ambient supervisory feature for temperature-threshold ranges
Another highlight for Model OOH941 is supervision of ambient temperatures, allowing the end user to set an unique, specified warning point at a customized temperature threshold ranging from -4°F to 120°F (-20°C to 49 °C). This feature is practical for monitoring of machinery; special processes, or for environments where maintaining a temperature is critical as an early-warning supervisory signal.
Self-monitoring for smoke-sensor sensitivity Model OOH941 provides an automatic self-monitoring sensitivity check that complies with the NFPA 72 sensitivity requirements. When connected with a compatible FACP, it provides automatic and dynamic sensitivity verification within the agency-listed-and-approved limits. Besides checking for sensor integrity and automatic environmental compensation, Model OOH941 provides a display and report of sensitivity in percent-per-foot (or percent-per-meter) at the FACP.
Profile Overview The Model OOH941 detector contains a tri-color LED indicator, capable of flashing any one (1) of three (3) distinct colors: green, yellow, or red. During each flash interval, the microprocessor-based detector monitors the following: • Smoke in its sensing chamber • Smoke sensitivity is within the range indicated
on the nameplate label • Internal sensors and electronics
Based on the results of the monitoring, the LED indicator flashes the following:
Flash Color
Condition Flash
Interval (in seconds)
Green*: Normal supervisory operation. Smoke sensitivity is within rated limits.
10
Yellow: Detector is in trouble and needs replacement.
4
Red: Alarm condition. 1
No Flash: Detector is not powered. ─ ─
* LED can be turned OFF. Please follow the corresponding description of the panel used.
A quick, visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from each Cerberus PRO FACP, indicating the status and settings assigned to each individual detector.
s Industry, Inc. Building Technologies Division
CerberusTM PRO
Installation
All Model OOH941 detectors use a surface-mounting base (Model DB-11 or Model DB-11E), which mounts on a 4-inch octagonal, square or single-gang electrical box. The base utilizes screw-clamp contacts for electrical connections and self-wiping contacts for increased reliability.
The Model DB-11 base can be used with the optional Model LK-11 detector locking kit, which contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has decorative plugs to cover the outer mounting screw holes.
Model OOH941 may be installed on the same initiating circuit with the Siemens Model ‘H’-series detectors [when used with Cerberus PRO FACPs] ─ • Models HFP-11, HFPT-11 • Model ‘HMS’-series manual stations • Model ‘HTRI’-series interfaces • Model HCP output-control devices • Model ‘HZM’-series of addressable,
conventional zone modules
Each detector consists of the following: Dust-resistant photoelectric chamber Solid state, non-mechanical thermal sensor Microprocessor-based electronics with a low-profile
plastic housing
Each Model OOH941 fire detector is shipped with a protective dust cover:
All Model OOH941 detectors are approved for operation within the UL-specified temperature range of 32° to 120°F (0° to 49°C) ─ depending on heat-detector configuration (see to installation manual: P/N A6V10324655) for details.
Application Data Installation of Model OOH941 detectors requires a two-wire circuit. In many retrofit cases, existing wiring may be used. ’T-tapping’ is permitted only for Style 4 (Class B) wiring. Model OOH941 is polarity insensitive, which can greatly reduce installation and debugging time.
Model OOH941 fire detectors can be applied within the maximum 30-feet center spacing (900 sq. ft. areas,) as referenced in NFPA 72. This application guideline is based on ideal conditions ─ specifically, smooth ceiling surfaces; minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire-protection-system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens ─ Fire Safety distributor or sales office whenever you need assistance applying Model OOH941 in unusual applications. Be sure to follow NFPA guidelines and UL Listed / ULC Listed installation instructions ─ included with every Siemens − Fire Safety detector ─ and local codes as for all fire protection equipment.
Technical Data Operating Temperatures: +32°F (0°C) to 120°F (49°C) depending upon heat-detector configurations (see to installation manual: P/N A6V10324655) for details
Heat-Detector Range: +135°F (57°C) to 175°F (79°C)
Thermal Rating:
s Industry, Inc. Building Technologies Division
CerberusTM PRO
Technical Data ─ (continued)
Detector Sensitivity Range: UL: 0.77% to 3.82% / ft. NFPA 76 (Telco) VEWFD: 0.2% / ft. Pre-alarm, 1.0% / ft. Alarm
Application Profiles: 22 (field configurable)
Programmable Supervisory Temperature Warning available with compatible FACPs: -4°F (-20°C) to 120°F (49°C)
Relative Humidity: 0-95%; non-condensing
Air Velocity ─ (Open Area): 0 − 4,000 feet-per-minute (fpm) Direct-in-Duct: 0 − 4,000 (fpm)
Air Pressure: No effect
Maximum Spacing: 30-foot centers (900 sq. ft.), per NFPA 72 and ULC-S524 Listed
Input Voltage Range: 13VDC − 32VDC
Alarm Current: 650μA, max.
Quiescent (Standby) Current: 280μA − 360μA
Detector Weight: 0.281 lbs. (0.128 kg.)
Approvals / Standards: FM 3210, 3220 CSFM 7272-0067:0260 UL 268 NFPA 25 UL 268A NFPA 72 UL 521 NFPA 76 ULC-S524 Listed
Mounting Diagrams Dimensions
Model OOH941
Model OOH941
with Model DB-11 base
Model OOH941
with Model DB-11E base
Detector Compatibility Table
Model Number
Data Sheet
NumberDescription
— 6300 FireFinder® XLS (system overview)
DLC 6312 Device Loop Card
FC901 9813 50-point panel
FC922 9815 252-point system (networkable)
FC924 9815 504-point system (networkable)
s CerberusTM PRO Siemens Industry, Inc. ─ Building Technologies Div. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO
NOTICE ─ The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitation and liability information.
Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer.
Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer.
Building Technologies Division SII ─ Fire Safety
[Printed in U.S.A ]
March 2013 ─ Supersedes sheet dated 2/2013 (Rev. 2)
Details for Ordering Model
Number Part
Number Description
OOH941 S54320-F7-A2 Multi-Criteria Fire Detector with ASAtechnology DB-11 500-094151 Detector Mounting Base
DB-11E 500-094151E Detector Base {small} DB2-HR S54320-F12-A1 Detector Mounting Base with Relay
RL-HC 500-033230 Remote Alarm Indicator: 4” octagon-box mount, red
RL-HW 500-033310 Remote Alarm Indicator: single-gang box mount, red
LK-11 500-695350 Base Locking Kit
In Canada, order: Model
Number Part
Number Description
DB-11C 500-095687 Detector Mounting Base for ULC (Listed)
ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
Cerberus® PRO Fire Safety Products
Thermal (Heat) Detector Model HI921
Answers for infrastructure
Intelligent Detection Devices
9901
Thermal (Heat) Detector Fire Detector
Product Overview The Intelligent Thermal (Heat) Detector (Model HI921) provides an advanced method of detection, address programming and supervision combined with sophisticated FACP communication. Model HI921 uses a state-of-the-art thermistor, microprocessor and advanced signal analysis, providing high reliability and accuracy.
Further, Model HI921 is a cost-effective, two-wire / addressable thermal detector that provides a distinctive, advanced feature: field-selectable temperature settings specially tailored for application-specific detection needs.
Model HI921 provides seven (7) field-selectable temperature-range settings: 135°F (57°C) 174°F (79°C) with fixed and rate-of-rise programmability. This variance provides the customer with maximum flexibility to program the temperature settings to suit multiple application needs and changing environmental conditions.
Additionally, Model HI921 can be configured to provide a low-temperature warning signal at 40°F (4.4°C). This feature along with a compatible FACP (FireFinder® XLS, or with either Model FC922 or Model FC924) serves as prevention of water freezing in pipes for sprinkler systems, meeting NFPA 72.
Model DPU Model HI921 is compatible with the Siemens field-device programmer / test unit (Model DPU), which is a compact, portable, menu-driven accessory for electronically programming and testing detectors easily and reliably.
Model DPU eliminates the need for cumbersome, unreliable mechanical programming methods, such as dials or switches, and reduces installation and service costs by electronically programming and testing the detector prior to installation.
Each detector consists of a solid state, non-mechanical thermal sensor, and microprocessor-based electronics with a low-profile plastic housing.
Model HI921 is Underwriters’ Laboratories ( UL521) Listed as a thermal (heat) detector.
Provides seven (7) field-selectable settings in the 135° 174°F (57.2° 78.9°F) temperature range
Tri-color detector-status light-emitting diode (LED) with 360° viewing
Compatible with Model DPU (device programmer / loop tester)
Utilizes advanced microprocessor-based signal processing
Provides a low-temperature warning at 40°F (4.4°C)
Each detector is self-testing: complete diagnostics performed every 10 seconds
Polarity insensitive utilizing SureWireTM technology
Compatible with Model DB-11 series mounting bases
Field programmable as rate-of-rise or fixed temperature
Compatible with Siemens Model ‘H’-series devices on the same loop (with Model FC9 series fire-alarm control panels)
Superior EMI / RFI immunity
RoHS compliant
UL521 Listed and ULC Listed; FM (#3230, 3210), CSFM (#72720067:0258) Approved
s Industry, Inc. Building Technologies Division Cerberus® PRO
Product Overview (continued) Each Model HI921 detector base also contains a provision for an optional, concealed locking mechanism to prevent unauthorized removal of the detector head (Model LK-11).
For proper operation of Model DPU, the technician selects the accessory’s program mode, and enters the desired address. In turn, Model DPU automatically sets and verifies the address, as well as tests the detector. When in the ‘test’ mode, Model DPU will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly.
Model DPU operates on AC power or rechargeable batteries, providing flexibility and convenience in programming and testing equipment from practically any location.
Operation Model HI921 also utilizes a modern, accurate and shock-resistant thermistor to sense temperature changes:
Each Model HI921 detector provides seven (7) pre-programmed parameter sets that can be selected by the FACP.
Detector Supervision and Testing Model HI921, which is listed as a self-testing device, contains a tri-color light emitting diode (LED) indicator, capable of flashing any one (1) of three (3) distinct colors: Green, Yellow, or Red. During each flash interval, the microprocessor-based detector monitors the following: • Temperatures reaching programmed thresholds • Internal sensors and electronics are functional
Based on the monitoring results, the LED indicator flashes the following colors based on the following conditions:
Flash Color
Condition Flash
Interval (in seconds)
Green*:
Normal supervisory operation. Temperature has not reached programmed alarm thresholds or set points.
10
Yellow: Detector is in trouble and needs replacement.
4
Red: Alarm condition. 1
No Flash: Detector is not powered.
* LED can be turned OFF. Please follow the corresponding description of the panel used.
A quick, visual inspection is sufficient to indicate the condition of the detector at any time. If more detailed information is required, a printed report can be provided from the Model FC9-series FACPs indicating the status and settings assigned to each individual detector.
Installation
All Model HI921 detectors use a surface-mounting base, Model DB-11 or Model DB-11E, which mounts on a 4-inch octagonal, square or single-gang electrical box. The base utilizes screw-clamp contacts for electrical connections and self-wiping contacts for increased reliability.
The Model DB-11 base can be used with the optional Model LK-11 detector locking kit, which contains 50 detector locks and an installation tool to prevent unauthorized removal of the detector head. Model DB-11 has decorative plugs to cover the outer mounting screw holes.
Model HI921 may be installed on the same initiating circuit with the Siemens Model ‘H’-series detectors [when used with the Model FC9-series of FACPs] • Model HFP-11 • Model ‘HMS’-series manual stations • Model ‘HTRI’-series interfaces • Model HCP output-control devices • Model ‘HZM’-series of addressable,
conventional zone modules
Application Data Installation of Model HI921 detectors requires a two-wire circuit. In many retrofit cases, existing wiring may be used. ’T-tapping’ is permitted only for Style 4 (Class B) wiring. Model HI921 is polarity insensitive, which can greatly reduce installation and debugging time.
Model HI921 can be applied within the maximum 50-feet center spacing (2,500 sq. ft. areas), per UL. This application guideline is based on ideal conditions, specifically, smooth ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire-protection system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens Fire Safety distributor or sales office whenever you need assistance applying Model HI921 in unusual applications. Be sure to follow NFPA guidelines and UL Listed / ULC Listed installation instructions included with every Siemens Fire Safety detector and local codes as for all fire-protection equipment.
s Industry, Inc. Building Technologies Division Cerberus® PRO
Specifications Model HI921 is a plug-in, (2) two-wire thermal (heat) detector, compatible with FireFinder XLS and Model FC9-series FACPs. Each Model HI921 detector has microcomputer-chip technology and highly stable, solid-state electronic circuitry.
The Model HI921 detector utilizes a modern, accurate and shock-resistant thermistor to sense temperature changes.
This electronic-sensing method virtually eliminates thermal lag associated with mechanical temperature-sensing devices, and provides almost instantaneous temperature status to the FACP.
Model HI921 provides seven (7) field-selectable, pre-programmed temperature settings: • Fixed 135°F (57°C) • Fixed 145°F (63°C) • Fixed 155°F (68°C) • Fixed 165°F (74°C) • Fixed 174°F (79°C)
• Rate-of-Rise: 15°F / min. (8.3°C) at fixed 135°F (57°C) • Rate-of-Rise: 15°F / min. (8.3°C) at fixed 174°F (79°C)
Additionally, the Model HI921 detector has the following optional feature: • Model HI921 provides indication of potential water
freezing for sprinkler systems, via configuration for reporting a low-temperature warning of 40°F (4.4°C).
This feature is compatible with FireFinder XLS panels, as well as with Models FC922 and FC924.
Technical Data Operating Temperature +32°F (0°C) to 100°F (38°C) Range: [with 135°F (57°C) alarm- threshold setting]
Relative Humidity: 0-95%; non-condensing
Air Pressure: No effect
Input Voltage Range: 16VDC 30VDC
Alarm Current (max.): 410 A
Standby Current (max.): 250 A, max. (average)
Maximum Spacing: 50-foot centers (2,500 sq. ft.), per NFPA 72 and ULC-S524
Thermal Rating: Model HI921 provides up to seven (7) field-selectable, pre-programmed temperature settings:
Fixed 135°F (57°C) Fixed 145°F (63°C) Fixed 155°F (68°C) Fixed 165°F (74°C) Fixed 174°F (79°C)
Rate-of-Rise: 15°F / min. (8.3°C / min) at fixed 135°F (57°C)
Rate-of-Rise: 15°F / min. (8.3°C / min) at fixed 174°F (79°C)
Detector Weight: 0.317 lbs.
(0.144 kg.)
s Cerberus® PRO NOTICE The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice. The devices described here have specific instruction sheets that cover various technical, limitat ion and liability information.
Copies of these instruction sheets and the General Product Warning and Limitations document, which also contains important information, are provided with the product and, are available from the Manufacturer.
Information contained in these documents should be consulted before specifying or using the product. For further information or assistance concerning particular problems contact the Manufacturer.
Siemens Industry, Inc. Building Technologies Div. 8 Fernwood Road • Florham Park, NJ 07932 Tel: (973) 593-2600 • Fax: (908) 547-6877 Web: www.USA.Siemens.com/Cerberus-PRO
Building Technologies Division SII Fire Safety
[Printed in U.S.A ]
April 2014 Supersedes sheet dated 6/2013 (Rev. 3)
Mounting Diagram Dimensions
Compatibility Chart Model
Number
Data Sheet
Number Description
— 6300 FireFinder® XLS (system overview)
FC901 9813 50-point panel
FC922 9815 252-point system (networkable)
FC924 9815 504-point system (networkable)
Details for Ordering
Model Part
Number Description
HI921 S54320-F5-A2 Thermal (Heat) Detector
DB-11 500-094151 Detector Mounting Base
DB-11E 500-094151E Detector Base {small}
RL-HC 500-033230 Remote Alarm Indicator: 4” octagon-box mount, red
RL-HW 500-033310 Remote Alarm Indicator: single-gang box mount, red
LK-11 500-695350 Base Locking Kit
STI-9604 STI Mechanical Protection Guard
See: www.STI-USA.com for further details on ordering Model STI-9604.
In Canada, order:
Model Part
Number Description
DB-11C 500-095687 Detector Mounting Base ( ULC Listed)
Agency Listings
5600 Series Mechanical Heat Detectors
System Sensor’s 5600 series mechanical heat detectors
offer a low-cost means for property protection against fire,
and for non-life-safety installations where smoke detectors
are inappropriate.
Features
• Multipleconfigurationsforinstallations: –Single-anddual-circuitmodels –Fixedtempandcombinationfixed-temp/rate-of-rise
135°For194°Fratings.
• Plainhousingforresidentialinstallations(Model5601P)
• Easy-to-useterminalscrews
• Abroadrangeofbackboxmountingoptions: –Singlegang –3.5˝and4˝Octagonal –4˝squarewithsquaretoroundplasterring
• Reversiblemountingbracket
Multiple configurations.The5600seriesoffersafull-lineofconfigurationstoaccommodateabroadrangeofapplications.Bothsingle-anddual-circuitmodelsareavailableforlow-andhigh-temperatureratingswitheitherfixedtemperatureorcombinationfixedtemperature/rate-of-rise(ROR)activation.TheRORelementofthefixed/RORmodelsisrestorabletoaccommodatefield-testing.
Installation flexibility.Tosatisfyavarietyofinstallationneeds,the5600serieseasilymountstosingle-gangandoctagonalbackboxes.Andthesemodelsaccommodatefour-squarebackboxes,whenusedwithasquaretoroundplasterring.Thereversiblemountingbracketpermitsbothflush-andsurface-mountbackboxinstallations.
Visual identification.The5600seriesprovidesclearmarkingsontheexterioroftheunittoensurethattheproperdetectorisbeingused.Alphanumericcharactersidentifytheactivationmethod,aswellasthetemperaturerating,inFahrenheitandCelsiusdegrees.FixedtemperaturemodelsareidentifiedFX,whilecombinationfixed/rate-of-riseunitsaremarkedFX/ROR.The5600seriesalsoprovidesapost-activationindicatorintheformofacollector.Whenthedetectorisactivated,thecollectordropsfromtheunit,makingiteasytoidentifytheunitinalarm.
S2101 3016008 CS630 7270-1653:0167
5601P
5621
3825OhioAvenue•St.Charles,IL60174Phone:800-SENSOR2•Fax:630-377-6495
www.systemsensor.com
©2013SystemSensor.Productspecificationssubjecttochangewithoutnotice.Visitsystemsensor.comforcurrentproductinformation,includingthelatestversionofthisdatasheet.
SPDS30001•7/13
SpecificationsArchitectural/Engineering Specifications
MechanicalheatdetectorshallbeaSystemSensor5600seriesmodelnumber_________,listedtoUnderwritersLaboratoriesUL521forHeatDetectorsforFireProtectiveSignalingSystems.Thedetectorshallbeeitherasingle-circuitoradual-circuittype,normallyopen.Thedetectorshallberatedforactivationateither135°F(57°C)or194°F(90°C),andshallactivatebymeansofafixedtemperaturethermalsensor,oracombinationfixedtemperature/rate-of-risethermalsensor.Therate-of-riseelementshallbeactivatedbyarapidriseintemperature,approximately15°F(8.3°C)perminute.Thedetectorshallincludeareversiblemountingbracketformountingto3½-inchand4-inchoctagonal,singlegang,and4-inchsquarebackboxeswithasquaretoroundplasterring.WiringconnectionsshallbemadebymeansofSEMSscrewsthatshallaccommodate14–22AWGwire.Thedetectorshallcontainalphanumericmarkingsontheexteriorofthehousingtoidentifyitstemperatureratingandactivationmethod.Therate-of-riseelementofcombinationfixedtemperature/rate-of-risemodelsshallberestorable,toallowforfield-testing.Thedetectorsshallincludeanexternalcollectorthatshalldropuponactivationtoidentifytheunitinalarm.Physical/Operating Specifications
Maximum Installation Temperature 5601P,5603,5621,and5623:100°F(38°C)5602,5604,5622,and5624:150°F(65.6°C)
Operating Humidity Range 5to95%RHnon-condensingDimensions with mounting bracket Diameter:4.57inches(11.6cm)
Height:1.69inches(4.3cm)Alarm Temperature 5601P,5603,5621,and5623:135°F(57°C)
5602,5604,5622,and5624:194°F(90°C)Weight 6oz.(170grams)Rate-of-Rise Threshold 15°F(8.3°C)riseperminute(models5601P,5602,5621,and5622only)Mounting 3½-inchoctagonalbackbox
4-inchoctagonalbackboxSinglegangbackbox4-inchsquarebackboxwithasquaretoroundplasterring
Electrical Specifications
Operating Voltage / Contact Ratings
6–125VAC/3A6–28VDC/1A125VDC/0.3A250VDC/0.1A
Input Terminals 14–22AWG
Ordering Information
Model Circuit
Identification Methodon Exterior
TemperatureRating Activation
UL Protected Spacing – 10 Foot Ceiling*
5601P Single None 135°F(57°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5602 Single Lettering 194°F(90°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5603 Single Lettering 135°F(57°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
5604 Single Lettering 194°F(90°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
5621 Dual Lettering 135°F(57°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5622 Dual Lettering 194°F(90°C) FixedTemperature/Rate-of-Rise 50feet×50feet(15.24m×15.2m)
5623 Dual Lettering 135°F(57°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
5624 Dual Lettering 194°F(90°C) FixedTemperature 25feet×25feet(7.62m×7.62m)
*NOTE:RefertoNFPA72guidelinesforspacingreductionswhenceilingheightsexceed10feet.
5601P
FX/ROR
1 9 4 ° F / 9 0 ° C5602, 5622
FX
1 3 5 ° F / 5 7 ° C5603, 5623
FX
1 9 4 ° F / 9 0 ° C5604, 5624
FX/ROR
1 3 5 ° F / 5 7 ° C5621
HMS-S and HMS-D Intelligent Manual Fire Alarm Boxes for FireFinder XLSControl Panels� Durable Design
� Shock and Vibration Resistant
� Pull Down Lever Remains Down Until Reset
� Custom Microcomputer Chip Technology
� Dynamic Supervision
� Polarity Insensitive with SureWire� Technology
� Reset with Allen Key
� No Break Rods Necessary
� Two Wire Operation
� Surface or Semiflush Installation
� DPU Programs and Verifies Device�sAddress and Tests Device�s Functionality
� Electronic Address Programming is Easierand More Dependable
� Single and Double Action Models Available
� , Listed, CSFM, FM and NYMEA Submitted
IntroductionHMS-S and HMS-D intelligent manual fire alarm boxesprovide the markets� most advanced method ofaddress programming and supervision, combined withsophisticated control panel communication. Each HMSmanual fire alarm box incorporates custom microcom-puter chip. The microcomputer chip technology, and itssophisticated bi-directional communication capabilitieswith the control panel, achieves the state of an �Intelli-gent Initiating Device.�
DescriptionThe HMS-S and HMS-D are constructed of durablemolded polycarbonate material which is matte finishedin red with raised white lettering. The housing accom-modates a �pull-down� lever which, when operated,locks in position indicating the manual fire alarm boxhas been activated. The pull down lever remains downand locked until the manual fire alarm box is reset.The manual fire alarm box is reset only by opening thehinged housing cover with an allen key and thenclosing and locking the cover.
HMS Series Intelligent Initiating Devices
6306CATALOG NUMBER
HMS-SSingle-Action Station
HMS-DDual-Action Station
The HMS-S and HMS-D manual fire alarm boxes operatewith FireFinder XLS Series control panels.
The manual fire alarm box�s microcomputer chip has thecapacity of storing, in memory, identification informationas well as important operating status information.
Siemens Building Technologies Inc., Fire SafetyDivision innovative technology also allows all HMSSeries Intelligent manual fire alarm boxes to be pro-grammed by using the Model DPU Programmer/Tester. The Programmer/Tester is a compact, portable,menu driven accessory which makes programming andtesting a manual fire alarm box device faster, easierand more dependable than previous methods. TheDPU eliminates the need for the device�s mechanicaladdressing mechanisms, such as program jumpers,dipswitches or rotary dials because the DPU electroni-cally sets the manual fire alarm box�s address intoits microcomputer chip, nonvolatile memory. Vibration,corrosion and other conditions which deteriorate mechani-cal addressing mechanisms are no longer a causefor concern.
Manual Fire Alarm Boxes
The HMS-S and HMS-D are fitted with screw terminalsfor connection to an addressable circuit. They can beeither surface or semiflush mounted.
The HMS Series manual fire alarm boxes derivetheir power, communicate information and receivecommands over a single pair of wires.
The HMS Series is compatible on the same circuitwith all H Series detectors, interfaces or addressableconventional zone modules.
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment willbe considered a misapplication of Fire Safety equipment and as such void all warranties eitherexpressed or implied with regard to loss, damage, liabilities and/or service problems.
Ordering Information
Mounting Data
Electrical RatingsCurrent Draw (Active or Standby): 1.5mA
August 2005Supersedes sheet dated 1/03
Siemens Building TechnologiesFire Safety
Fire Safety8 Fernwood RoadFlorham Park, NJ 07932Tel: (973) 593-2600FAX: (973) 593-6670Website: www.sbt.siemens.com/fis
8/055M
SFS-IGPrinted in U.S.A.
Fire Safety2 Kenview BoulevardBrampton, OntarioCanada L6T 5E4Tel: (905) 799-9937FAX: (905) 799-9858
Intelligent Interface Modules for FireFinder XLS and FS-250 SeriesFire Alarm Control Panels HTRI-S, HTRI-D, HTRI-R� Interfaces and Supervises Normally Open or Normally
Closed Contacts
� Integral SPDT Relay (up to 4 amps) on HTRI-R Model
� Dual Input on HTRI-D Model using a single address
� Polarity Insensitive with SureWire� Technology
� Multi-color L.E.D. indicates status (green, amber, red)
� Easy front access to programming port andwiring terminals
� Mounts 4 inch square 2 ¼ deep box, or double gang box
� Dynamic Supervision
� Comes with 5x5 inch faceplate
� Two wire operation
� DPU Device Program/Test Unit programs and VerifiesDevice�s Address and Tests Devices functionality
� Electronic Address Programming is Easy and Dependable
� ULC ListedCFSM, FM, NYMEA Approved
IntroductionThe HTRI Series Intelligent interface modules are de-signed to provide the means of interfacing direct shortingdevices to the FireFinder XLS and FS-250 Fire AlarmControl Panel loop circuit.
The HTRI Series Intelligent interface modules provide themarket�s most advanced method of address programmingand supervision, combined with sophisticated control panelcommunication. Each HTRI Series interface moduleincorporates a microcomputer chip. The HTRI Seriesmicrocomputer chip technology and its sophisticatedbi-directional communication capabilities with the controlpanel, achieve the state of an �Intelligence Device.�
DescriptionThe HTRI Series intelligent interface modules areavailable in three models. The HTRI-S and HTRI-R aredesigned to monitor a normally open or closed drycontact. The interface module reports the contact�sstatus to the control panel. The HTRI-S model can only
HTRI SeriesFireFinder XLS and FS-250 Intelligent Initiating DevicesInterface Modules
6304CATALOG NUMBER
monitor and report the status of the contact, while theHTRI-R incorporates an addressable Form C relay. TheHTRI-R relay and contact device input are controlled at thesame address. For the control panel system, the relayand input contact can be controlled as a separate function.The relay is typically used where control or shunting ofexternal equipment is required.
The HTRI-D is a dual input module and is designed tosupervise and monitor two sets of dry contacts. TheDual Input Module only requires one address but re-sponds independently to each input. The HTRI-D is idealfor monitoring a water flow switch and its respectivevalve tamper switch.
The HTRI has a multi-color Light Emitting Diode thatflashes green when operating normally, amber if unitis in trouble condition, and red to indicate a change ofstate. The HTRI-D flashes twice, once for each ad-dress, the HTRI-R red L.E.D. indicates a change ofstate in the relay.
Ordering Information
The device�s microcomputer chip has the capacity ofstoring, in memory, identification information as well asimportant operating status information.
Siemens Building Technologies, Inc., Fire Safety Divisioninnovative technology allows all HTRI Series intelligentinterface modules to be programmed by using the DPUDevice Programming/Test Unit. The DPU is a compact,portable, menu driven accessory that makes program-ming and testing an interface device faster, easier andmore dependable than previous methods. The DPUeliminates the need for mechanical addressing mecha-nisms, such as program jumpers, DIP switches or rotarydials, because the DPU electronically sets the HTRIinterface�s address into the interface�s microcomputerchip nonvolatile memory. Vibration, corrosion and otherconditions that deteriorate mechanical addressing mecha-nisms are no longer a cause for concern.
The HTRI Series is fitted with screw terminals forconnection to an addressable circuit.
The HTRI Series is fully compatible on the sameFireFinder XLS and FS-250 circuits with all intelligent HSeries detectors, HMS Series addressable manualstations or any other addressable intelligent modules,such as the HZM or HCP.
All HTRI Series intelligent interface modules areUL listed.
Environmental operating conditions for all HTRI Seriesmodules are 32ºF (ºC) to 120ºF (49ºC) with a relativehumidity of not greater than 93% non-condensating.
Mounting DataAddressable Interface Model HTRI-S, HTRI-D, HTRI-Rmounts directly into a 4 inch square 2 ¼ deep box ora double gang box (user supplied). A 5 inch squareoff-white faceplate is included with each HTRI.
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment willbe considered a misapplication of Fire Safety equipment and as such void all warranties eitherexpressed or implied with regard to loss, damage, liabilities and/or service problems.
Electrical RatingsCurrent Draw (Active or Standby): 1mA
HTRI-R Relay RatingsResistive: 4A, 125 VAC
4A, 30 VDC
Inductive: 3.5A, 120 VAC (0.6P.F.)3.0A, 30 VDC (0.6P.F.)2.0A, 120 VAC (0.4P.F.)2.0A, 120 VAC (0.35P.F.)2.0A, 30 VDC (0.35P.F.)
December 2004Supersedes sheet dated 1/03
Siemens Building TechnologiesFire Safety
Fire Safety8 Fernwood RoadFlorham Park, NJ 07932Tel: (973) 593-2600FAX: (973) 593-6670Website: www.sbt.siemens.com/fis
12/045M
SFS-IGPrinted in U.S.A.
Fire Safety2 Kenview BoulevardBrampton, OntarioCanada L6T 5E4Tel: (905) 799-9937FAX: (905) 799-9858
HLIM Line Isolator Module
� Short Circuit Isolation
� Used on FireFinder XLS Intelligent Device Circuits
� Increased Fault Tolerance
� Style 4 or Style 6
� Up to 15 Per DLC Circuit Max.
� Requires no Programming
� Does Not Occupy a Device Address
� Mounts in Either 4" Square, 2 1/8" Deepor a 3 1/2" Deep Double Gang Electrical Box
� Local LED Indicator
� Cover Plate Included
� Listed, ULC Listed, NYMEA and CSFMApproved
6310CATALOG NUMBER
For Use With the FireFinder XLS Control Panel
DescriptionThe HLIM loop isolator module provides short circuitprotection on FireFinder XLS intelligent device circuits(DLC). When a short is detected by the HLIM, it isolatesthe affected segment of the circuit, allowing the remainingdevices to continue operation. The HLIM is self-restoring,automatically reconnecting to circuit segment when thefault is removed.
The HLIM also includes a yellow LED which illuminatesto indicate that the device has been activated. The HLIMmounts in either a 4" square, 2 1/8" deep or a 3 1/2" deepdouble gang electrical box and is supplied with a coverplate with an opening for the LED.
It can be wired in either a Style 4 or Style 6 configuration.
The HLIM does not occupy a device address on the DLCcircuit and requires no programming. Up to twelve HLIMsmay be installed on each DLC loop.
Ordering Information
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safetyequipment will be considered a misapplication of Fire Safety equipment and assuch void all warranties either expressed or implied with regard to loss, damage,liabilities and/or service problems.
August 2005Supersedes sheet dated 1/03
Siemens Building TechnologiesFire Safety
Fire Safety8 Fernwood RoadFlorham Park, NJ 07932Tel: (973) 593-2600FAX: (973) 593-6670Website: www.sbt.siemens.com/fis
8/055M
SFS-IGPrinted in U.S.A.
Fire Safety2 Kenview BoulevardBrampton, OntarioCanada L6T 5E4Tel: (905) 799-9937FAX: (905) 799-9858
HTRI-M Intelligent Device Interface Module
Intelligent Interface Modules ForFireFinder™ XLS and FS-250Control Panels• Interfaces and Supervises Normally Open (Fire Detection)
or Normally Closed Contacts (Security Detection)
• Compact Size Allows Mounting in Single Gang BoxBehind Equipment
• Polarity Insensitive with SureWire™ Technology
• Operates with FireFinder XLS DLC Circuit
• Innovative Technology Supports ComprehensiveSystem and Interface Communication
• Dynamic Supervision
• Two Wire Operation
• DPU Device Program/Test Unit ElectronicallyPrograms and Verifies Device’s Address and TestsDevice’s Functionality
• ULC ListedCSFM, FM and NYMEA Pending
6308CATALOG NUMBER
IntroductionThe HTRI-M Intelligent interface module is designedto provide the means of interfacing direct shortingdevices to the FireFinder XLS or FS-250 system’s DLCloop circuit.
The HTRI-M Intelligent interface module provides themarket’s most advanced method of address program-ming and supervision, combined with sophisticatedcontrol panel communication. Each HTRI-M interfacemodule incorporates microcomputer chip technologyand its sophisticated bi-directional communicationcapabilities with the control panel.
DescriptionThe HTRI-M is designed to monitor a normally open orclosed dry contact and reports the contact’s status tothe control panel.
The device’s microcomputer chip has the capacity ofstoring, in memory, identification information as wellas important operating status information.
Siemens Building Technologies, Inc. innovative technol-ogy allows all HTRI-M intelligent interface modules to beprogrammed by using the DPU Device Program/TestUnit. The DPU is a compact, portable, menu drivenaccessory that makes programming and testing aninterface device faster, easier and more dependable thanprevious methods. The DPU eliminates the need formechanical addressing mechanisms, such as programjumpers, DIP switches or rotary dials, because it elec-tronically sets the HTRI-M interface’s address into theinterface’s microcomputer chip non-volatile memory.Vibration, corrosion and other conditions that deterioratemechanical addressing mechanisms are no longer acause for concern. This HTRI-M is connected to theprogram/tester with the programming cable provided withthe tester. This cable (P/N 110-694927) utilizes two (2)alligator clip connectors, to attach to the HTRI-M.
The HTRI-M Series has five leads, one for grounding,which are wired to the system with user suppliedwire nuts.
For Use With the FireFinder-XLS and FS-250 Control Panel
The HTRI-M is fully compatible on the same DLCcircuit with all intelligent H Series detectors, HMS Seriesaddressable manual stations or any other H Seriesaddressable intelligent modules, such as the HZM orHCP.
All HTRI-M intelligent interface modules have beenUL and ULC submitted.
Environmental operating conditions for all HTRI-Mmodules are 32oF (oC) to 120oF (49oC) with a relativehumidity of not greater than 93% non-condensating.
Ordering Information
NOTICE: The use of other than Fire Safety detectors and bases with Fire Safety equipment willbe considered a misapplication of Fire Safety equipment and as such void all warranties eitherexpressed or implied with regard to loss, damage, liabilities and/or service problems.
Electrical RatingsCurrent Draw (Active or Standby): 1.5mA
June 2006Supersedes sheet dated 5/06
Siemens Building TechnologiesFire Safety
Fire Safety8 Fernwood RoadFlorham Park, NJ 07932Tel: (973) 593-2600FAX: (973) 593-6670Website: www.sbt.siemens.com/fis
6/065M
SFS-IGPrinted in U.S.A.
Fire Safety2 Kenview BoulevardBrampton, OntarioCanada L6T 5E4Tel: (905) 799-9937FAX: (905) 799-9858
Siemens Data Sheet 2594 Building Technologies Division usa.siemens.com/fire
Product Overview
Formed as the `SL’-series, Siemens is now offering horns, strobes, and horn-strobes to its notification-appliances portfolio. With the `SL’-series, Siemens now offers an additional range of products with low and high candela settings that makes these sophisticated notification appliances ideal for new installs and retrofit applications.
Innovative light-emitting diode (LED) strobe technology provides an energy-efficient means for a significantly reduced current draw.
The strobe portion of these appliances meets the 20 millisecond light-pulse-duration requirements of the 2016 edition of NFPA 72. This feature allows existing Xenon and the new LED devices to be used in the same field-of-view.
In a single device, the `SL’-series can provide alarm-signaling tones for dual applications. All strobe models in the series feature multi-candela settings (15 | 30 | 75 | 95cd) on a single appliance.
Additionally, there are two (2) modes of operation for the audible portion of these notification appliances:
• T3 (coded) • Continuous
The `SL’-series of horns, strobes and horn-strobes devices are produced in a sleek, modern design. Its structure and design provide high-quality energy efficiency in an aesthetically pleasing, low-profile design that is consistent to the look of the interior composition of the building application.
This `SL’-series is exclusive to indoor ceiling-mount applications. The Model `SLHC’-series horn appliances work in either 12V or 24VDC, whereas the Series `SLSC’ and `SLHSC’ strobe and horn-strobe devices are specifically for 24V operation.
Notification Appliances `SL’ Series – Horns | Strobe
| Horn-Strobes
Applications : Indoor, Ceiling-Only
Model SLHSCR-F+ Horn-strobe
Architect & Engineer Specifications
Sophisticated series of notification appliances that meets fire-industry codes and regulations for commercial-building applications
Compatible with the Siemens 50-point, 252-point and 504-point addressable fire alarm control panels (FACPs), and with:
- Siemens Modular FACPs
- Siemens PAD-series of NAC extenders
- FireFinder® XLS / XLSV FACPs - Siemens dual-sync control (DSC) modules
Innovative LED strobe technology provides an energy-efficient means for a significantly reduced current draw
- Capability to have existing Xenon and new LED strobes in the same field-of-view
- Fewer power supplies required, smaller wire gage, reduced wire runs
Straightforward installation coupled with compact, modern design
- No visible mounting screws
- Manual (index finger) slide-setting adjustor
- Four (4) field-selectable settings in one (1) device: 15cd | 30cd | 75cd | 95cd
Faceplates ship in four (4) distinctive types:
- ``FIRE’’ | ``ALERT’’ | ``AGENT’’ | (blank)
Two (2) audible settings in each notification appliance
- Temporal or steady horn output
- High or Low setting
UL (2034 | 1971 | 464) and ULC Listed (ULC-S525 | - S526); CSFM Approved
- ADA | NFPA | FCC | ANSI | OSHA compliant
Model SLSCW-AL+ Strobe
Model SLHCR-N + Horn
Siemens Building Technologies Division
–2– usa.siemens.com/fire
Specifications
In terms of composition and functionality, Models `SLHC ’-series, `SLSC ’-series, and `SLHSC ’-series provide added value to the installer for the types of applications for operation:
• Compact | sleek | low-profile design
• Comprehensive feature list • Convenient mounting options • Easy-to-adjust selection-slider switch for candela settings
− No tools required for setting changes − Multi-level settings: 15cd | 30cd | 75cd | 95cd
• High and Low audible outputs
• Reduced current draw, via cutting-edge LED technology
The LED portions of the Siemens `SL’-series of strobes and horn-strobes meet the 20 millisecond light-pulse-duration requirements of the 2016 edition of NFPA 72. By meeting this latest requirement, existing Xenon as well as the new LED-technology devices can now be in the same field-of-view.
The horn, strobe and horn-strobes in this Siemens `SL’-series of notification appliances have received UL / ULC Listed status by attaining compatible testing standards with all of the Siemens fire-alarm control panels (FACPs) and accessories that have been determined to be aligned with existing Siemens strobe-based appliances.
This would include the following existing model-types: `CH’ | `HS’ | `MTH’ | `S-HQ’ | `AS’ | `SE’ | `SEF’ | `SET’ | `ST’ | `STH’ | `ZR’ and `ZH’ Series notification appliances. The regulatory listing also includes the capability for installing the Siemens `SL’-series sounder-strobes in the same notification zone and field-of-view with any existing Siemens Notification Appliance Xenon-based strobes.
All these horns, strobes and horn-strobes models are UL Listed (for indoor use under Standard 1971 and 464), as well as ULC-S525 | ULC-S526 Listed. The Siemens `SL’-series sounder-strobes also have ADA | RoHS and ICES approval.
`SLHC’ Serieso Ceiling Horn
`SLSHC’ Serieso Ceiling Horn-Strobe
Flathead screw indentation
6.26” (2.84 cm.) Diameter
1.5” (3.81 cm.) Depth
Siemens Building Technologies Division
–3– usa.siemens.com/fire
Electrical RatingsCeiling-Mount | Horn-Strobes Output Current Draw
UL Current Ratings (HIGH dB | in Amps)
16.0 - 33.0 VDC
MODEL
S̀LHSC’
SERIES:^
Setting 15cd 30cd 75cd 95cd
Code 3 0.044 0.065 0.182 0.268
Continuous 0.049 0.067 0.187 0.274
UL Current Ratings (LOW dB | in Amps)
16.0 - 33.0 VDC
MODEL
S̀LHSC’
SERIES:
Setting 15cd 30cd 75cd 95cd
Code 3 0.042 0.064 0.181 0.256
Continuous 0.045 0.066 0.183 0.271
Ceiling-Mount | Horn-Only Output Current Draw
Current Ratings (Code 3 | in Amps)
RMS Current @ 24 Volts DC
MODEL
S̀LHC’
SERIES:^
Regulated Voltage Range, VDC
High Low
8.0 – 17.5 VDC 0.024 0.018
16.0 – 33.0 VDC 0.030 0.022
Ceiling-Mount | Strobe-Only Output Current Draw
Current Ratings (in Amps) RMS Current @ 24 Volts DC
MODEL
S̀LSC’
SERIES:^
Regulated Voltage Range
15cd 30cd 75cd 95cd
16.0 – 33.0 Volts DC 0.040 0.058 0.171 0.256
GENERAL NOTES:
1. Strobes are designed to flash at 1-flash-per-second minimum over their ``Regulated Voltage Range.”
2. NFPA-72 specifies a flash rate of 1-to-2 flashes-per-second, and guidelines for the Americans with Disabilities Act (ADA) specify a flash rate of 1-to-3 flashes-per-second.
3. All candela ratings represent minimum
effective Strobe intensity based on UL 1971.
UL | Ceiling-Mount | Horn-Only | Output Current Draw
UL Sound Output Ratings (dBA) Reverberant per UL464 @ 10 feet
Volume
SLHC @ 12VDC
SLHC -and- SLHSC @ 24VDC
8.0V 12.0V 17.5V 16.0V 24.0V 33.0V
MODEL
S̀LHW’–
and –
S̀LHSW’
SERIES:^
Code 3 |
High dBA 75 80 83 76 79 81
Code 3 |
Low dBA 73 77 80 75 77 77
Continuous |
High dBA 80 84 87 80 83 86
Continuous |
Low dBA 78 79 84 78 81 81
ULC | Ceiling-Mount | Horn-Only | Output Current Draw
ULC Sound Output Ratings (dBA) Anechoic per ULCS525-16 @ 3.05 meters
Volume
SLHW @ 12VDC
SLHW -and- SLHSW @ 24VDC
8.0V 12.0V 17.5V 16.0V 24.0V 33.0V
MODEL
S̀LHW’–
and –
S̀LHSW’
SERIES:^
Code 3 |
High dBA 85 89 92 91 95 96
Code 3 |
Low dBA 79 84 87 86 90 91
Continuous |
High dBA 85 89 92 91 94 97
Continuous |
Low dBA 79 84 87 86 90 92
^RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16 - 33V for 24V units)
^ For audible appliances, the max current is usually at the maximum listed voltage (16 - 33V for 24V units)
^ For unfiltered FWR ratings, see installation instruction
Technical Data General Properties
MODEL `SL’-series
OPERATING
TEMPERATURE: 32F (0C) to 122F (50C) for indoor-applications’ use only
RELATIVE HUMIDITY: 93%, maximum
OPERATING
VOLTAGE RANGES:
12 VDC / VFWR → 8 - 17.5 VDC / VFWR; 24 VDC / VFWR → 16 - 33 VDC/VFWR
(12 VDC for Model SLHC only)
STROBE
OUTPUT RATING:
UL 1971, ULC-S526
Field-selectable 15cd | 30cd | 75cd | 95cd
candela outputs
STROBE FLASH RATE: Strobes are designed to flash at one-flash-per-second
STROBE
SYNCRONIZATION:
all Siemens addressable panels Siemens PAD-series NAC extenders Siemens dual-sync (DSC) modules,
which provide the unique Siemens proprietary synchronization protocol
TEMPORAL
PATTERN:
Continuous
Code 3 (1/2 second on, 1/2 second off; then 1/2 second on, 1/2 second off; followed
by 1/2 second on, 1-1/2 second off and repeat)
NOTES: The Code 3 pattern is specified by
ANSI and NFPA 72 for Standard Emergency Evacuation Signaling.
Physical Properties
MODEL `SL’-series
MATERIAL:
White-or-red textured, ultraviolet (UV) stabilized, colored impregnated engineered plastic
Exceeds 94V-0 UL flammability rating
WEIGHT: 0.55 Lbs. (0.25 Kg.)
LENS TYPE: LED strobe situated in a rugged Lexan lens
DIMENSIONS: 3.13’’ (7.95 cm.) { H }; 3.13’’ (7.95 cm.) { W }; 1.5’’ (3.81 cm.) { D }
Mounting and Wiring Properties
MODEL `SL’-series
INDOOR
MOUNTING:
Ceiling-mount applications
Model SLSBBC backboxes or to 4” (10.2 cm.) square
1.5” (cm.) -or- 2.125” (cm.) octagonal 1.5” (cm.) -or- 2.125” (cm.) deep
WIRING TYPE: #12 – #18, American Wire Gauge (AWG)
NOTICE – The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s) that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product Warning and Limitations document, which also contains important data, are provided with the product. All are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted with a fire-safety professional before specifying or using the product.
Any further questions or assistance concerning particular problems that might arise, relative to the proper functioning of the equipment, please contact the Manufacturer.
Details for Ordering
MODEL PART NUMBER APPLIANCE
TYPE UL ULC
MOUNTING TYPE
STROBE TYPE
FACEPLATE COLOR
FACEPLATE LETTERING
SLHCR-N S54329-F12-A1 Horn
✓ ✓ C e i l i n g
– None – RED – None –
SLHCW-N S54329-F12-A2 ✓ ✓ – None – WHITE – None –
SLHSCW-F S54329-F13-A1 Horn-Strobe
✓ ⎯ C e i l i n g
Clear WHITE FIRE
SLHSCR-F S54329-F13-A2 ✓ ⎯ Clear RED FIRE
SLHSCR-FB S54329-F14-A1 Horn-Strobe
⎯ ✓ C e i l i n g
Clear RED – Pictogram –
SLHSCW-FB S54329-F14-A2 ⎯ ✓ Clear WHITE – Pictogram –
SLSCW-F S54329-F15-A1 Strobe
✓ ⎯ C e i l i n g
Clear WHITE FIRE
SLSCR-F S54329-F15-A2 ✓ ⎯ Clear RED FIRE
SLSCW-FB S54329-F16-A1 Strobe
⎯ ✓ C e i l i n g
Clear RED – Pictogram –
SLSCR-FB S54329-F16-A2 ⎯ ✓ Clear WHITE – Pictogram –
SLSCW-AL S54329-F17-A1 Strobe
✓ ✓ C e i l i n g
Clear WHITE ALERT
SLSCR-AL S54329-F17-A2 ✓ ✓ Clear RED ALERT
SLSCW-ALA S54329-F18-A1 Strobe
✓ ✓ C e i l i n g
Amber WHITE ALERT
SLSCR-ALA S54329-F18-A2 ✓ ✓ Amber RED ALERT
SLSCW-NA S54329-F19-A1 Strobe
✓ ✓ C e i l i n g
Amber WHITE – None –
SLSCR-NA S54329-F19-A2 ✓ ✓ Amber RED – None –
SLSCW-N S54329-F20-A1 Strobe
✓ ⎯ C e i l i n g
Clear WHITE – None –
SLSCR-N S54329-F20-A2 ✓ ⎯ Clear RED – None –
SLHSCR-A S54329-F32-A2 Horn-Strobe
✓ ✓ C e i l i n g
Clear RED AGENT
SLHSCW-A S54329-F35-A2 ✓ ✓ Clear WHITE AGENT
SLHSCR-AL S54329-F33-A1 Horn-Strobe
✓ ✓ C e i l i n g
Clear RED ALERT
SLHSCW-AL S54329-F36-A1 ✓ ✓ Clear WHITE ALERT
SLHSCR-N S54329-F33-A2 Horn-Strobe
✓ ⎯ C e i l i n g
Clear RED – None –
SLHSCW-N S54329-F36-A2 ✓ ⎯ Clear WHITE – None –
SLSCW-A S54329-F65-A1 Strobe
✓ ✓ C e i l i n g
Clear WHITE AGENT
SLSCR-A S54329-F37-A2 ✓ ✓ Clear RED AGENT
SLSBBCR S54329-F55-A1 Backbox
✓ ✓ C e i l i n g
– None – RED – None –
SLSBBCW S54329-F55-A2 ✓ ✓ – None – WHITE – None –
Siemens Industry, Inc.
Building Technologies Division 8 Fernwood Road • Florham Park, NJ 07932
Tel: (973) 593-2600
October 2018 ─ Supersedes sheet dated 4/2018 (Rev. 2)
Siemens Data Sheet 2593 Building Technologies Division usa.siemens.com/fire
Product Overview Formed as the `SL’-series, Siemens is now offering horns, strobes, and horn-strobes to its notification-appliances portfolio. With the `SL’-series, Siemens offers a full range of products with low and high candela settings that makes these sophisticated notification appliances ideal for new installs and retrofit applications.
Innovative light-emitting diode (LED) strobe technology provides an energy-efficient means for a significantly reduced current draw.
The strobe portion of these appliances meets the 20 millisecond light-pulse-duration requirements of the 2016 edition of NFPA 72. This feature allows existing Xenon and the new LED devices to be used in the same field-of-view.
In a single device, the `SL’-series can provide alarm-signaling tones for dual applications. All strobe models in the series feature multi-Candela settings (15 | 30 | 75 | 110cd) on a single appliance.
Additionally, there are two (2) modes of operation for the audible portion of these notification appliances:
• T3 (coded) • Continuous
The `SL’-series of horns, strobes and horn-strobes devices are produced in a sleek, modern design. Its single-gang form factor provides high-quality energy efficiency in an aesthetically pleasing, low-profile design that is consistent to the look of the interior composition of the building application.
The `SL’-series is apt for indoor wall-mount applications. The Model `SLH’-series horn appliances work in either 12V or 24VDC, whereas the Series `SLSW’ and `SLHSW’ strobe and horn-strobe devices are specifically for 24V operation.
Notification Appliances `SL’ Series – Horns | Strobes
Horn-Strobes
Applications : Indoor, Wall-Only
Model SLHSWR-F+ Horn-strobe
Architect & Engineer Specifications Sophisticated series of notification
appliances that meets fire-industry codes and regulations for commercial-building applications
Compatible with the Siemens 50-point, 252-point and 504-point addressable fire alarm control panels (FACPs), and with: - Siemens Modular FACPs - Siemens PAD-series of NAC extenders - FireFinder® XLS / XLSV FACPs - Siemens dual-sync control (DSC) modules
Innovative LED strobe technology provides an energy-efficient means for a significantly reduced current draw
- Capability to have existing Xenon and new LED strobes in the same field-of-view
- Fewer power supplies required, smaller wire gage, reduced wire runs
Straightforward installation coupled with compact, modern design - No visible mounting screws - Manual (index finger)
slide-setting adjustor - Four (4) field-selectable
settings in one (1) device: 15cd | 30cd | 75cd | 110cd
Faceplates ship in four (4) distinctive types: - ``FIRE’’ | ``ALERT’ ’ | ``AGENT’’ | (blank)
Two (2) audible settings in each notification appliance - Temporal or steady horn output - High or Low setting
UL (2034 | 1971 | 464) and ULC Listed (ULC-S525 | - S526); CSFM Approved - ADA | NFPA | FCC | ANSI | OSHA compliant
Model SLSWW-ALA+ Strobe
Model SLHR-N + Horn
Siemens Building Technologies Division
–2– usa.siemens.com/fire
Specifications In terms of composition and functionality, Models `SLHW’-series, `SLSW’-series, and `SLHSW’-series provide added value to the installer for the types of applications for operation:
• Compact | sleek | low-profile design • Comprehensive feature list • Convenient mounting options • Easy-to-adjust selection-slider switch for Candela settings
− No tools required for setting changes − Multi-level settings: 15cd | 30cd | 75cd | 110cd
• High and Low audible outputs • Reduced current draw, via cutting-edge LED technology
The LED portions of the Siemens `SL’-series of strobes and horn-strobes meet the 20 millisecond light-pulse-duration requirements of the 2016 edition of NFPA 72. By meeting this latest requirement, existing Xenon as well as the new LED-technology devices can now be in the same field-of-view.
The horn, strobe and horn-strobes in this Siemens `SL’-series of notification appliances have received UL / ULC Listed status by attaining compatible testing standards with all of the Siemens fire-alarm control panels (FACPs) and accessories that have been determined to be aligned with existing Siemens strobe-based appliances.
This would include the following existing model-types: `CH’ | `HS’ | `MTH’ | `S-HQ’ | `SA’ | `SE’ | `SEF’ | `SET’ | `ST’ | `STH’ | `ZR’ and `ZH’ Series notification appliances. The regulatory listing also includes the capability for installing the Siemens `SL’-series LED-based strobes in the same notification zone and field-of-view with any existing Siemens Notification Appliance Xenon-based strobes.
All types of these horns, strobes and horn-strobes are UL Listed (for indoor use under Standard 1971 and 464), as well as ULC-S525 | ULC-S526 Listed. The Siemens `SL’-series sounder-strobes also have ADA | RoHS and ICES approval.
`SLHW’ Serieso Horn
TRIMPLATE DIMENSIONS: 5.25 inches (13.34 cm.) {H}; 4.58 inches (11.6 cm.) {W}; 0.32 inches (0.81 cm.) {D}
`SLSW’ Serieso Strobe
`SLSHW’ Serieso Horn-Strobe
Candela Setting
Adjustor
Candela Setting
Adjustor
MOUNTING OPTIONS INCLUDE:
Model SLSBB to any single-gang backbox
4” (10.2 cm.) square backboxes with the Model SLSGP adapter kit
Siemens Building Technologies Division
–3– usa.siemens.com/fire
Electrical RatingsWall-Mount | Horn-Strobes | Output Current Draw
Current Ratings (HIGH dB | in Amps) 16.0 – 33.0VDC
MODEL S̀LHSW’
SERIES:^
Setting 15cd 30cd 75cd 110cd
Code 3 0.034 0.046 0.105 0.214
Continuous 0.042 0.052 0.110 0.217
Wall-Mount | Horn-Strobes | Output Current Draw
Current Ratings (LOW dB | in Amps) 16.0 – 33.0VDC
MODEL S̀LHSW’ SERIES:
Setting 15cd 30cd 75cd 110cd
Code 3 0.032 0.042 0.102 0.213
Continuous 0.036 0.044 0.104 0.216
Wall-Mount | Horn-Only | Output Current Draw
Current Ratings (Code 3 | in Amps) RMS Current @ 24VDC
MODEL S̀LHW’
SERIES:^
Regulated Voltage Range High Low
8.0 – 17.50 VDC 0.024 0.018 16.0 – 33.0 VDC 0.030 0.022
Wall-Mount | Strobe-Only | Output Current Draw
Current Ratings (Code 3 | in Amps) RMS Current @ 24VDC
MODEL S̀LSW’
SERIES:^
Regulated Voltage Range 15cd 30cd 75cd 110cd
16.0 – 33.0 VDC 0.030 0.040 0.102 0.201
UL | Wall-Mount | Horn-Only | Output Current Draw
UL Sound Output Ratings (dBA) Reverberant per UL464 @ 10 feet
Volume SLHW @ 12VDC
SLHW -and- SLHSW @ 24VDC
8.0V 12.0V 17.5V 16.0V 24.0V 33.0V
MODEL S̀LHW’– and –
S̀LHSW’ SERIES:^
Code 3 | High dBA
75 80 83 76 79 81
Code 3 | Low dBA
73 77 80 75 77 77
Continuous | High dBA
80 84 87 80 83 86
Continuous | Low dBA
78 79 84 78 81 81
ULC | Wall-Mount | Horn-Only | Output Current Draw
ULC Sound Output Ratings (dBA) Anechoic per ULCS525-16 @ 3.05 meters
Volume SLHW @ 12VDC
SLHW -and- SLHSW @ 24VDC
8.0V 12.0V 17.5V 16.0V 24.0V 33.0V
MODEL S̀LHW’– and –
S̀LHSW’ SERIES:^
Code 3 | High dBA
85 89 92 91 95 96
Code 3 | Low dBA
79 84 87 86 90 91
Continuous | High dBA
85 89 92 91 94 97
Continuous | Low dBA
79 84 87 86 90 92
^RMS current ratings are per UL maximum RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16 - 33V for 24V units)
^ For audible appliances, the max current is usually at the maximum listed voltage (16 - 33V for 24V units)
^ For unfiltered FWR ratings, see installation instructions
GENERAL NOTES: 1. Strobes are designed to flash at 1-flash-per-second minimum over their ``Regulated Voltage Range.”
2. NFPA-72 specifies a flash rate of 1-to-2 flashes-per-second, and guidelines for the Americans with Disabilities Act (ADA) specify a flash rate of 1-to-3 flashes-per-second.
3. All Candela ratings represent minimum effective Strobe intensity based on UL 1971.
Technical Data General Properties
MODEL `SL’-series
OPERATING TEMPERATURE:
32F (0C) to 122F (50C) for indoor-applications’ use only
RELATIVE HUMIDITY: 93%, maximum
OPERATING VOLTAGE RANGES:
12 VDC / VFWR → 8 - 17.5 VDC / VFWR; 24 VDC / VFWR → 16 - 33 VDC/VFWR
(12 VDC for Model SLHW only)
STROBE OUTPUT RATING:
UL 1971, ULC-S526 Field-selectable 15cd | 30cd | 75cd | 110cd
Candela outputs
STROBE FLASH RATE: Strobes are designed to flash at one-flash-per-second
STROBE SYNCRONIZATION:
all Siemens addressable panels Siemens PAD-series NAC extenders Siemens dual-sync (DSC) modules,
which provide the unique Siemens proprietary synchronization protocol
TEMPORAL PATTERN:
Continuous Code 3 (1/2 second on, 1/2 second off; then
1/2 second on, 1/2 second off; followed by 1/2 second on, 1-1/2 second off and repeat)
NOTES: The Code 3 pattern is specified by ANSI and NFPA 72 for Standard Emergency Evacuation Signaling.
Physical Properties
MODEL `SL’-series
MATERIAL: White-or-red textured, ultraviolet (UV) stabilized,
colored impregnated engineered plastic
Exceeds 94V-0 UL flammability rating
WEIGHT: 0.35 Lbs. (0.16 Kg.)
LENS TYPE: LED strobe situated in a rugged Lexan lens
DIMENSIONS:
Actual Appliance: 4.53’’ (11.5 cm.) { H }; 2.76’’ (7.0 cm.) { W }; 1.27’’ (3.23 cm.) { D }
Single-Gang Trim Plate: 5.25’’ (13.3 cm.) { H }; 4.58’’ (11.6 cm.) { W }; 0.32’’ (0.81 cm.) { D }
Mounting and Wiring Properties
MODEL `SL’-series
INDOOR MOUNTING:
Wall-mount applications
Single-gang (Model SLSBB) backboxes or to 4” (10.2 cm.) square with Model SLSGP adapter ki t
WIRING TYPE: #12 – #18, American Wire Gauge (AWG)
NOTICE – The information contained in this data-sheet document is intended only as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s) that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product Warning and Limitations document, which also contains important data, are provided with the product. All are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted with a fire-safety professional before specifying or using the product.
Any further questions or assistance concerning particular problems that might arise, relative to the proper functioning of the equipment, please contact the Manufacturer.
Details for Ordering
MODEL PART NUMBER APPLIANCE TYPE
UL ULC MOUNTING TYPE
STROBE TYPE
FACEPLATE COLOR
FACEPLATE LETTERING
SLHWR-N S54329-F23-A1 Horn
✓ ✓ WALL – None – RED – None – SLHWW-N S54329-F23-A2 ✓ ✓ WALL Clear WHITE – None –
SLHSWR-F S54329-F22-A1 Horn-Strobe
✓ ⎯ WALL Clear RED FIRE SLHSWW-F S54329-F22-A2 ✓ ⎯ WALL Clear WHITE FIRE
SLHSWR-FB S54329-F24-A1 Horn-Strobe
⎯ ✓ WALL Clear RED – Pictogram – SLHSWW-FB S54329-F24-A2 ⎯ ✓ WALL Clear WHITE – Pictogram –
SLHSWR-A S54329-F31-A2 Horn-Strobe
✓ ✓ WALL Clear RED AGENT SLHSWW-A S54329-F34-A2 ✓ ✓ WALL Clear WHITE AGENT
SLHSWR-N S54329-F34-A1 Horn-Strobe
✓ ⎯ WALL Clear RED – None – SLHSWW-N S54329-F37-A1 ✓ ⎯ WALL Clear WHITE – None –
SLHSWW-AL S54329-F35-A1 Horn-Strobe
✓ ✓ WALL Clear WHITE ALERT SLHSWR-AL S54329-F32-A1 ✓ ✓ WALL Clear RED ALERT
SLSWR-F S54329-F25-A1 Strobe
✓ ⎯ WALL Clear RED FIRE SLSWW-F S54329-F25-A2 ✓ ⎯ WALL Clear WHITE FIRE
SLSWW-FB S54329-F26-A1 Strobe
⎯ ✓ WALL Clear WHITE – Pictogram – SLSWR-FB S54329-F26-A2 ⎯ ✓ WALL Clear RED – Pictogram –
SLSWR-A S54329-F27-A1 Strobe ✓ ⎯ WALL Clear RED AGENT
SLSWW-AL S54329-F27-A2 Strobe
✓ ✓ WALL Clear WHITE ALERT SLSWR-AL S54329-F28-A1 ✓ ✓ WALL Clear RED ALERT
SLSWW-ALA S54329-F28-A2 Strobe
✓ ✓ WALL Amber WHITE ALERT SLSWR-ALA S54329-F29-A1 ✓ ✓ WALL Amber RED ALERT
SLSWR-NA S54329-F29-A2 Strobe
✓ ✓ WALL Amber RED – None – SLSWW-NA S54329-F30-A1 ✓ ✓ WALL Amber WHITE – None –
SLSWW-N S54329-F30-A2 Strobe
✓ ⎯ WALL Clear WHITE – None – SLSWR-N S54329-F31-A1 ✓ ⎯ WALL Clear RED – None –
SLSBBR S54329-F21-A1 Backbox
✓ ✓ WALL – None – RED – None – SLSBBW S54329-F21-A2 ✓ ✓ WALL – None – WHITE – None –
SLSGP-R S54329-F64-A1 Optional Single-Gang
Trim Plate
✓ ✓ WALL – None – RED – None –
SLSGP-W S54329-F64-A2 ✓ ✓ WALL – None – WHITE – None –
Siemens Industry, Inc.
Building Technologies Division 8 Fernwood Road • Florham Park, NJ 07932
Tel: (973) 593-2600
October 2018 ─ Supersedes sheet dated 4/2018 (Rev. 2)
‘08 Series Notification Appliances 2578
s Industry, Inc. Building Technologies Division
s Data Sheet
Fire Safety & Security Products
‘08 Series Notification Appliances AS / AH & AS – Audible Strobe Appliances and AH Audibles Application: Indoor / Outdoor
Product Overview – Fast installation with In / Out screw terminals using #12 to #18 AWG wires – Synchronization can be accomplished using the Siemens DSC sync modules, FS-250 panel,
XLS panel, MXL panel, or PAD-3 power supply with built-in sync protocol – 3 Selectable dBA settings of 90/95/99 dBA Anechoic in both tones – Selectable Continuous Horn or Temporal (Code 3) – Wall mounts are available with field-selectable Candela settings: 15/30/75/110cd or 135/185cd – Ceiling-mount models are available with field-selectable Candela settings: 15/30/75/95cd or
115/177cd (multi-Candela ceiling models) – Weatherproof models are available for outdoor use – UL Listed & ULC Listed;
FM, CSFM & NYMEA Approved – ADA / NFPA / UFC / ANSI compliant
Specifications – Notification appliances shall be Siemens Series AS Audible Strobe appliances and Series AH Audible
appliances or approved equals – Series AS Audible be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired for
Indoor Fire Protection Service) – Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling) – All inputs shall be compatible with standard reverse polarity supervision of circuit wiring
by the Fire Alarm Control Panel (FACP) – The audible portion of the appliance shall have a minimum of three (3) field-selectable settings for
dBA Anechoic levels, and shall have a choice of continuous or temporal (Code 3) audible outputs – Strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the
Regulated Input Voltage Range, and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens
AS-MC-CW AS-MC-R AH-W AH-R
s Industry, Inc. Building Technologies Division
Specifications – (continued)
– Series AS shall be of low-current design – Strobe intensity, where Multi-Candela appliances are specified, shall have field-selectable settings,
and shall be rated per UL Standard 1971 for: 15/30/75/110cd 135/185cd
– The appliance, when synchronization is required, shall be compatible with Siemens’ DSC Sync Modules or Siemens PAD-3 Power Supplies with built-in Siemens Proprietary Sync Protocol
– The strobes shall not drift out of synchronization at any time during operation – The strobes shall revert to a non-synchronized flash-rate, if the sync module or Power Supply
should fail to operate (i.e. – contacts remain closed) – The appliance shall also be designed so that the audible signal may be silenced while maintaining
strobe activation when used with Siemens synchronization – The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal
Mounting Plate that shall allow mounting to a single-gang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBBS Surface Backbox
– All notification appliances shall listed for Special Applications: Strobes are designed to flash at 1-flash-per-second minimum over their “Regulated Input Voltage Range”
Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second, and ADA Guidelines specify a flash rate of 1-to-3 flashes per second
All Candela ratings represent minimum-effective Strobe intensity, based on UL Standard 1971
Mounting Diagram
Mounting Options
(Shown In Inches) (Shown In Inches)
s Industry, Inc. Building Technologies Division
Technical Data
Notes: 1. Strobe will produce 1 flash per second over the Input Voltage range.
2. This strobe/horn model meets the required light distribution patterns defined in UL 1971 3. This model is UL Listed for indoor use with a temperature range of +32ºF to +120ºF (0ºC to +49ºC) and maximum
humidity of 93% + 2% RH. The effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and not subjected to misuse or abuse.
Note: All models are UL / ULC Listed for indoor use with a temperature range of +0°C to +49°C (+32°F to +120°F) and
maximum humidity of 93%.
s Industry, Inc. Building Technologies Division
Technical Data – (continued)
Note: These notification appliances are UL Listed as “Special Application”. They are intended to be used only with Siemens notification appliance circuits.
Notes: 1. Strobe will produce 1 flash per second over the Input Voltage range. 2. This strobe/horn model meets the required light distribution patterns defined in UL 1971 3. This model is UL Listed for indoor use with a temperature range of +32ºF to +120ºF (0ºC to +49ºC) and
maximum humidity of 93% + 2% RH. The effect of shipping and storage temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and not subjected to misuse or abuse.
s Industry, Inc. Building Technologies Division
Technical Data – (continued)
Details for Ordering ─ (Including Mounting Options & Agency Approvals)
Agency Approvals
Model Number
Part Number
Wall Mount
Ceiling Mount
Description Mounting Options*
UL ULC FM CSFM
AS-MC-R 500-636010 X ─ AS Horn: Multi-Candela, Red A,B,D,E,F,G,J,N,R,X X X X X AS-MC-W 500-636011 X ─ AS Horn: Multi-Candela, White A,B,D,E,F,G,J,N,R,X X X X X AS-HMC-R 500-636012 X ─ AS Horn: Hi Multi-Candela, Red A,B,D,E,F,G,J,N,R,X X X X X AS-HMC-W 500-636013 X ─ AS Horn: Hi Multi-Candela, White A,B,D,E,F,G,J,N,R,X X X X X AS-MC-CR 500-636006 ─ X AS Horn: Multi-Candela Ceiling, Red A,B,D,E,F,G,J,N,R,X X X X X AS-MC-CW 500-636007 ─ X AS Horn: Multi-Candela Ceiling, White A,B,D,E,F,G,J,N,R,X X X X X AS-HMC-CR 500-636008 ─ X AS Horn: Hi Multi-Candela Ceiling, Red A,B,D,E,F,G,J,N,R,X X X X X AS-HMC-CW 500-636009 ─ X AS Horn: Hi Multi-Candela Ceiling, White A,B,D,E,F,G,J,N,R,X X X X X
AS-HMC-CR-WP 500-636181 ─ X AS Horn: Hi Multi-Candela Ceiling Weatherproof, Red
I X X X X
AS-HMC-CW-WP 500-636182 ─ X AS Horn: Hi Multi-Candela Ceiling Weatherproof, White
I X X X X
AS-HMC-R-WP 500-636183 X ─ AS Horn: Hi Multi-Candela Wall
Weatherproof, Red I X X X X
AS-HMC-W-WP 500-636184 X ─ AS Horn: Hi Multi-Candela Wall
Weatherproof, White I X X X X
AS-75-R-WP 500-636016 X ─ AS Horn: 75CD Weatherproof, Red I X X X X
AS-75-CR-WP 500-636015 ─ X AS Horn: 75CD Ceiling Weatherproof, Red
I X X X X
AH-R 500-636003 X X AH Horn, Red A,B,D,E,F,G,J,N,R,X X X X X AH-W 500-636004 X X AH Horn, White A,B,D,E,F,G,J,N,R,X X X X X
AH-R-WP 500-636005 X X AH Horn: Weatherproof, Red K X X X X
X = listed / approved *= Refer to data sheet #: 2585 for detailed mounting options
s Industry, Inc. Building Technologies Division
Fire Safety 8 Fernwood Road Florham Park, NJ 07932 Tel: (973) 593-2600 FAX: (908) 547-6877 URL: www.SBT.Siemens.com/FIS
(SII) Printed in U.S.A.
Fire Safety 2 Kenview Boulevard Brampton, Ontario L6T 5E4 / Canada Tel: (905) 799-9937 FAX: (905) 799-9858
March 2010
Supersedes sheet dated 12/09 (Rev. 2)
Notice: This marketing data sheet is not intended to be used for system design or installation purposes. For the most up-to-date information, refer to each product’s installation instructions.