Aura I nter ior IR Sett ings M anual(BACnet)

Table O f Contents

Preparation .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Setting the Sensor Address for the First Time .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Changing the Sensor Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Verifying the Sensor Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Changing the baud rate (Default = 38400) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Using the Factory Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Changing the Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Changing the Light Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Changing the Motion Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

Changing the Threshold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

Changing the Vacancy Delay / Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

Appendix I - Virtual Buttons Mode 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

Appendix II - Virtual Buttons Mode 1 (Default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

Appendix III - Motion Detection Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

4822 Projects Dr l Fort Wayne, Indiana 46825 l 1 .260.426.1565 l www.touchplate .com

Page 2w w w.touchplate.com

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

PreparationUnpack the Aura I nter ior and inspec t the contents for damaged or miss ing produc ts. I f any problems ar ise, p lease contac t Touch-Plate at 260.426.1565 for ass istance.

Prec autionsThe Aura I nter ior hardware is des igned to be in environments that have a temperature range of 0-60°C (non- condensing atmosphere) . I nsta l l ing in an environment outs ide of these parameterswi l l shor ten the l i fe span of the hardware.

Touch-Plate recommends the use of 18 to 22 AWG wire for low voltage wir ing of contac t c losure produc ts, 18 AWG wire for a l l 24v power connec t ions, and 16 AWG wire for Smar t Switch Stat ions.

Al l 120VAC wir ing must use wire as speci f ied by Nat ional E lec tr ic Code for load s ize and wire length.

Compatible HardwareThe Aura is a smar t sensor that can be a par t of a net worked, intel l igent system.

Warrant yTouch-Plate warrants this produc t against defec ts in mater ia ls or work manship, under normal use, for a per iod of ONE (1) year f rom date of shipment. I f a defec t ar ises and a val id c la im is received within the Warrant y Per iod, Touch-Plate wi l l repair or replace the produc t at no charge.

This warrant y does not apply to :

a . Damage to unit (s ) caused by accident , ac ts of God, inappropr iate insta l lat ion, fault yinsta l lat ion, or any negl igent use ;

b. Unit (s ) which have been subjec t to being taken apar t or other wise modif ied;c. Unit not used in accordance with instruc t ions ;d. The f in ish on any por t ion of the produc t , such as sur face and/or weather ing, as this

is considered normal wear and tear ;e. Non-Touch-Plate hardware insta l led by the user ;f. Damage caused by Non-Touch-Plate produc ts ;g. Damage caused by operat ing the produc t outs ide the permitted or intended uses

descr ibed by Touch-Plate ;h . - or- Speci f ic p lans or Speci f ic appl icat ion requirements, unless the plans and

speci f icat ions have been for warded to Touch-Plate and Touch-Plate has approvedand accepted the plans in wr i t ing.

EXCEPT AS PROVIDED IN THIS WARR ANT Y, TOUCH-PL ATE IS NOT RESPONSIBLE FOR DIREC T, SPECIAL,

INCIDENTAL, OR CONSEQUENTIAL DAMAGES RESULTING FROM ANY BREACH OF WARR ANT Y OR CONDITION,

INCLUDING BUT NOT LIMITED TO, INSTALL ATION OR REPL ACEMENT L ABOR COSTS.

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Page 3w w w.touchplate.com

S etting the S ensor Address for the First TimeTypical ly the Aura sensor comes f rom the fac tor y pre -addressed. The fol lowing steps are only appl icable i f the address was not set at the fac tor y. Only attempt to address one unaddressed sensor at a t ime, per room. The fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Power up the Aura sensor. A white l ight wi l l turn on.

2 . Press ‘POWER ’. A blue l ight wi l l f lash.

3 . Enter the desi red address and press ‘ENTER ’. A red l ight wi l l b l ink and then bl ink each t ime mo -t ion is detec ted.

a . I f the desi red address is 10 , press the 1 and 0 .

Changing the S ensor AddressThe fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Enter the current address and press ‘ENTER ’. Another blue l ight wi l l f lash.

4 . Enter the numbers 101 to change this parameter and press ‘ENTER ’. An yel low l ight wi l l b l ink .

5 . Enter the new, des i red address and press ‘ENTER ’. A yel low l ight wi l l b l ink and the unit wi l l re -boot . Once restar ted, a red l ight wi l l b l ink and then bl ink each t ime motion is detec ted.

a . I f i t i s to be addressed 94, press the 9 and 4 .

b. I f the new address is entered incorrec t ly, press ‘STOP ’ and star t at step 1 .

Verifying the S ensor AddressThe fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Press ‘PLAY ’. The sensor wi l l f lash a colored coded sequence of l ights to indicate i ts address. See the table below for the f lash color value and add up the number of f lashes by value.

4 . Press ‘STOP ’ to exi t . A blue l ight wi l l b l ink , then a red l ight wi l l b l ink and then bl ink each t ime motion is detec ted.

Address Value Flash Color

1 Blue Flashes10 Red Flashes

100 Green Flashes1000 Purple Flashes

10000 Yel low FlashesExample: 2 Red Flashes and 3 Blue Flashes = Address 23

Page 4w w w.touchplate.com

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Changing the baud rate (Default = 38400)1. Point the IR remote at the sensor.

2 . Press Stop. The sensor wi l l f lash a blue l ight .

3 . Press Power. The sensor wi l l f lash a blue l ight .

4 . Use the number buttons on the remote to enter the current address. ( I f i t ’s address 1 , press 1 . I f i t ’s address 94, press 9 and then 4 . ) I f there are mult iple sensors in the room, this step a l lows you to selec t which sensor you want to conf igure.

5 . Press Enter. The sensor wi l l f lash a blue l ight .

6 . Press the numbers 102.

7 . Press Enter. The sensor wi l l b l ink yel low.

8 . Use the number buttons on the remote to enter the new baud rate.

9 . Press ing Play wi l l f lash the current baud rate sett ing. Ex : 3 blue f lashes = 38400

1 = 9600

2 = 19200

3 = 38400

4 = 76800

TIP: I f you enter the new baud rate incorrec t ly, press Stop and star t over at step 1 .

10. Enter number 1-4 for des i red baud rate.

11 . Press Enter. The sensor wi l l b l ink yel low and resume normal operat ion at se lec ted baud rate.

Using the Fac tor y ResetUse the fac tor y reset to restore sensor parameters to fac tor y defaults and to reset the address to 0 . The fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Enter the current address and press ‘ENTER ’. A blue l ight wi l l b l ink .

a . I f the current address is 94 , press the 9 and 4 .

4 . Enter the numbers 1094 to change this parameter and press ‘ENTER ’. A pink l ight wi l l b l ink .

5 . Press ‘PAUSE’. A pink l ight wi l l b l ink . Power c ycle the unit . Af ter star t ing a white l ight wi l l turn on sol id. Use the ‘Sett ing the Sensor Address for the Fi rst Time’ sec t ion to set a new address.

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Page 5w w w.touchplate.com

Changing the HysteresisThe hysteres is i s a percentage of the threshold. The hysteres is i s used to create a range of acceptable l ight levels above and below the threshold. This i s so that l ights do not turn on and off with ever y smal l var iat ion in l ight level above and below the threshold.

Example: A large hysteres is (greater than 10%) would make the sensor less sensit ive. A smal l hysteres is ( less than 10%) would make the sensor more sensit ive. A threshold of 100 with a hysteres is of 10% would give you an On value of 90 lux and an O ff value of 110 lux . I f the hysteres is was set too low at say 1% the On/O ff values would be 99 & 101 lux which may cause the l ight to turn On/O ff several t imes before staying On/O ff due to c louds, people pass ing by, exc. . .

The hysteres is might need to be changed depending on local fac tors such as : normal outdoor l ight levels , how sunny or c loudy the sk y tends to be, the t ype of windows in the bui lding, whether the sensor is indoors or outdoors, etc.

I f l ights are too sensit ive to changes in the l ight level , ra is ing the hysteres is might help. I f l ights are not responsive enough to changes in the l ight level , lower ing the hysteres is might help.

Selec t ing the opt imal hysteres is wi l l l ike ly require on-s i te t r ia l and error.

The fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Enter the current address and press ‘ENTER ’. A blue l ight wi l l b l ink .

a . I f the current address is 94 , press the 9 and 4 .

4 . Enter the numbers 202 to change this parameter and press ‘ENTER ’. A white l ight wi l l b l ink .

5 . Enter the new, des i red H ysteres is value and press ‘ENTER ’. Another white l ight wi l l b l ink .

6 . Press ‘PLAY ’ to review the current hysteres is value. The sensor wi l l f lash a colored coded sequence of l ights to indicate i ts value. See the table below for the f lash color value and add up the number of f lashes by value.

7 . Press ‘STOP ’ to exi t . A blue l ight wi l l b l ink , then a red l ight wi l l b l ink and then bl ink each t ime motion is detec ted.

H ysteres is Value R ange Default

1 - 100% 10%

H ysteres is Value Flash Color

1 Blue Flashes10 Red Flashes

100 Green Flashes1000 Purple Flashes

10000 Yel low FlashesExample: 2 Red Flashes and 3 Blue Flashes = 23%

Page 6w w w.touchplate.com

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Changing the Light DelayThe l ight delay is the number of seconds the ac t ion is delayed before being tr iggered.

Example: When the l ight level drops below the hysteres is range, the system waits a set amount of seconds before the l ights come on or of f. Used so l ights aren’t unintent ional ly t r iggered by ref lec t ions, c loud cover, exc. . .

The l ight delay feature helps to ensure that l ights do not f l icker on and off with ever y pass ing c loud or other br ief and temporar y changes in l ight level .

The fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Enter the current address and press ‘ENTER ’. A blue l ight wi l l b l ink .

a . I f the current address is 94 , press the 9 and 4 .

4 . Enter the numbers 203 to change this parameter and press ‘ENTER ’. A yel low l ight wi l l b l ink .

5 . Enter the new, des i red value and press ‘ENTER ’. A white l ight wi l l b l ink .

6 . Press ‘PLAY ’ to review the current seconds value. The sensor wi l l f lash a colored coded sequenceof l ights to indicate i ts value. See the table below for the f lash color value and add up thenumber of f lashes by value.

7 . Press ‘STOP ’ to exi t . A blue l ight wi l l b l ink , then a red l ight wi l l b l ink and then bl ink each t imemotion is detec ted.

L ight Delay Value R ange Default

1 - 3600 seconds 1 second

Light Delay Value Flash Color

1 Blue Flashes10 Red Flashes

100 Green Flashes1000 Purple Flashes

10000 Yel low FlashesExample: 2 Red Flashes and 3 Blue Flashes = 23 Seconds

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Page 7w w w.touchplate.com

Changing the M otion S ensit ivit yThe motion sensit iv i t y i s the sensit iv i t y of the motion detec tor. The higher the number, the more motion that wi l l be needed for the sensor to detec t motion. The lower the number, then less motion wi l l be needed for the sensor to detec t motion.

The fac tor y default works under most condit ions. The motion sensit iv i t y might need to be lowered i f there is a motion sensor in an of f ice that would be repeatedly t r ipped by people walk ing past the of f ice door. The motion sensit iv i t y might need to be ra ised i f there is a motion sensor that does not seem to detec t motion when there are occupants in the room.

Selec t ing the opt imal motion sensit iv i t y wi l l l ike ly require on-s i te t r ia l and error.

The fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Enter the current address and press ‘ENTER ’. A blue l ight wi l l b l ink .

a . I f the current address is 94 , press the 9 and 4 .

4 . Enter the numbers 301 to change this parameter and press ‘ENTER ’. A green l ight wi l l b l ink .

5 . Enter the new, des i red motion sensit iv i t y and press ‘ENTER ’. Another green l ight wi l l b l ink .

6 . Press ‘PLAY ’ to review the current sensit iv i t y value. The sensor wi l l f lash a colored coded sequence of l ights to indicate i ts value. See the table below for the f lash color value and add up the number of f lashes by value.

7 . Press ‘STOP ’ to exi t . A blue l ight wi l l b l ink , then a red l ight wi l l b l ink and then bl ink each t ime motion is detec ted.

M otion Sensit iv i t y Value R ange Default

2 - 254 25

Motion Sensit iv y Value Flash Color

1 Blue Flashes10 Red Flashes

100 Green Flashes1000 Purple Flashes

10000 Yel low FlashesExample: 2 Red Flashes and 3 Blue Flashes = Sensit iv i t y Value of 23

Page 8w w w.touchplate.com

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Changing the ThresholdThe threshold is the l ight level in lux at which the ac t ion is t r iggered.

When the l ight level i s below the threshold, i t wi l l turn the l ights on. When the l ight level i s above the threshold, i t wi l l turn the l ights of f.

The sensor a l lows the threshold to be set for 4 v i r tual button pairs .

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Enter the current address and press ‘ENTER ’. An blue l ight wi l l b l ink .

a . I f the current address is 94 , press the 9 and 4 .

4 . Enter the IR code to change the desi red parameter and press ‘ENTER ’. A white l ight wi l l b l ink .

a . See the table below for the avai lable IR Codes.

5 . Enter the new threshold value and press ‘ENTER ’. A white l ight wi l l b l ink .

a . To set the value to the current l ight sensor reading press ‘REC ’.

6 . Press ‘PLAY ’ to review the current lux value. The sensor wi l l f lash a colored coded sequence of l ights to indicate i ts value. See the table below for the f lash color value and add up the number of f lashes by value.

7 . Press ‘STOP ’. A blue l ight wi l l b l ink , then a red l ight wi l l b l ink and then bl ink each t ime motion is detec ted.

Descr ipt ion IR Code Value R ange Default

Lux Threshold Buttons 1/2 201 0 - 65535 lux 50Lux Threshold Buttons 3/4 204 0 - 65535 lux 100Lux Threshold Buttons 5/6 205 0 - 65535 lux 200Lux Threshold Buttons 7/8 206 0 - 65535 lux 500

Threshold Value Flash Color

1 Blue Flashes10 Red Flashes

100 Green Flashes1000 Purple Flashes

10000 Yel low FlashesExample: 2 Red Flashes and 3 Blue Flashes = Value of 23 lux

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Page 9w w w.touchplate.com

Changing the Vac anc y Delay / Test M o deThe vacanc y delay is the number of minutes that the l ights stay on af ter motion stops.

Vacanc y delay helps prevent l ights f rom turning of f whi le people are in the room.

The fac tor y recommends that the vacanc y delay is not set for less than 15 minutes, unless i t i s a c loset , supply room, or a room where people are a lways moving i f they are in there.

Test Mode can be used to test the sensit iv i t y of the sensor. Us ing Test Mode sets the vacanc y delay to 2 seconds.

Note : When you set the vacanc y delay to ‘0 ’ i t s t i l l shows up as a value of ‘1 ’ when you press the play button to review the value s ince there is no color value for ‘0 ’. Be sure to set a proper value for the vacanc y delay af ter us ing the Test M ode.

The fol lowing steps are only appl icable us ing a Universal IR Remote.

1 . Point the Universal IR Remote towards the sensor and press ‘STOP ’. A blue l ight wi l l f lash.

2 . Press ‘POWER ’. Another blue l ight wi l l f lash.

3 . Enter the current address and press ‘ENTER ’. A blue l ight wi l l b l ink .

a . I f the current address is 94 , press the 9 and 4 .

4 . Enter the numbers 302 to change this parameter and press ‘ENTER ’. A green l ight wi l l b l ink .

a . Proceed to step 5 to set the desi red motion sensit iv i t y.

b. Proceed to step 8 to enter test mode.

5 . Enter the new, des i red vacanc y delay and press ‘ENTER ’. Another green l ight wi l l b l ink .

6 . Press ‘PLAY ’ to review the current minutes value. The sensor wi l l f lash a colored coded sequence of l ights to indicate i ts value. See the table below for the f lash color value and add up the number of f lashes by value.

7 . Press ‘STOP ’. A blue l ight wi l l b l ink , then a red l ight wi l l b l ink and then bl ink each t ime motion is detec ted. (Sk ip steps 8 - 9) .

8 . Enter the number 0 and press ‘ENTER ’. Another green l ight wi l l b l ink .

9 . Press ‘STOP ’. A blue l ight wi l l b l ink , then a red l ight wi l l b l ink and then bl ink each t ime motion is detec ted.

Vacanc y Delay Value R ange Def init ion Default

0 2 Second Test Mode N/A1 - 120 Number of M inutes 1 minute

Threshold Value Flash Color

1 Blue Flashes10 Red Flashes

100 Green Flashes1000 Purple Flashes

10000 Yel low FlashesExample: 2 Red Flashes and 3 Blue Flashes = Value of 23 minutes

Page 10w w w.touchplate.com

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

App endix I - Vir tual Buttons M o de 0To Touch-Plate control lers , a sensor is an input device, just l ike a control stat ion. Touch-Plate control lers “sees” that each sensor has e ight (8) buttons.

The sensor communicates with the control lers v ia v i r tual button presses. These v i r tual button presses re lease input information to the control ler based on set Thresholds. When the l ight level crosses a set threshold, the control ler ac ts as i f a button was pressed to t r igger the conf igured ac t ion. To disable motion detec t ion the sensor mode must be set to 0 us ing Analog Value AV10 v ia a BACnet f rontend.

Sensor Used as a L ight Sensor (Mode 0 = Motion Disabled)

Vir tual Button Condit ions that Tr igger a Button Press Descr ipt ion

1Button 1 turns on and button 2 turns of f i f the l ight level i s less than threshold 1/2 minus the hysteres is .

Ambient l ight less than Threshold_1/2 - H ysteres is

2Button 2 turns on and button 1 turns of f i f the l ight level i s more than threshold 1/2 plus the hysteres is .

Ambient l ight more than Threshold_1/2 + H ysteres is

3Button 3 turns on and button 4 turns of f i f the l ight level i s less than threshold 3/4 minus the hysteres is .

Ambient l ight less than Threshold_3/4 - H ysteres is

4Button 4 turns on and button 3 turns of f i f the l ight level i s more than threshold 3/4 plus the hysteres is .

Ambient l ight more than Threshold_3/4 + H ysteres is

5Button 5 turns on and button 6 turns of f i f the l ight level i s less than threshold 5/6 minus the hysteres is .

Ambient l ight less than Threshold_5/6 - H ysteres is

6Button 6 turns on and button 5 turns of f i f the l ight level i s more than threshold 5/6 plus the hysteres is .

Ambient l ight more than Threshold_5/6 + H ysteres is

7Button 7 turns on and button 8 turns of f i f the l ight level i s less than threshold 7/8 minus the hysteres is .

Ambient l ight less than Threshold_7/8 - H ysteres is

8Button 8 turns on and button 7 turns of f i f the l ight level i s more than threshold 7/8 plus the hysteres is .

Ambient l ight more than Threshold_7/8 + H ysteres is

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Page 11w w w.touchplate.com

App endix I I - Vir tual Buttons M o de 1 (Default)To Touch-Plate control lers , a sensor is an input device, just l ike a control stat ion. Touch-Plate control lers “sees” that each sensor has e ight (8) buttons.

The sensor communicates with the control lers v ia v i r tual button presses. These v i r tual button presses re lease information to the control ler based on set Thresholds. When the l ight level crosses a set threshold, the control ler ac ts as i f a button was pressed to t r igger the conf igured ac t ion.

Sensor Used as a L ight Sensor (Mode 1 = Motion Enabled)

Vir tual Button Condit ions that Tr igger a Button Press Descr ipt ion

1Button 1 turns on and button 2 turns of f i f the l ight level i s less than threshold 1/2 and the hysteres is .

Ambient l ight less than Threshold_1/2 - H ysteres is

2Button 2 turns on and button 1 turns of f i f the l ight level i s more than threshold 1/2 plus the hysteres is .

Ambient l ight more than Threshold_1/2 + H ysteres is

3

Button 3 is used for Maintain ac t ions. When the sensor senses motion, the l ight stays on. When the sensor does not sense motion, the l ight turns of f.

Occupied MaintainOCC Sensor On- Send button press- Send button press 1 sec laterOCC Sensor O ff- Send button re lease- Send button re lease 1 sec later

4

Button 4 is used for Auto O ff ac t ions, especia l ly when there are mult iple sensors in one room. When motion is sensed, the Auto O ff t imer star ts over. This process is repeated unt i l no motion is sensed.

Occupied Pulsed RepeatOCC Sensor On- Send button press- Send button re lease 1 sec later-Repeat pulse ever y 2 minutesOCC Sensor O ff- Send button re lease

5

Button 5 is used for On/O ff ac t ions. When motion is detec ted, the l ights turn on. I t can work with Cycle ac t ion, but the e f fec t i s less re l iable.

Occupied Pulsed OnceOCC Sensor On- Send button press- Send button re lease 1 sec later

6

Button 6 is used for On/O ff ac t ions.When no motion is detec ted, the l ights turn of f. I t can work with Cycle ac t ion, but the ef fec t i s less re l iable.

Vacant Pulsed OnceOCC Sensor O ff- Send button press- Send button re lease 1 sec later

7

Button 7 is used for dayl ight har vest ing.I f a room is unoccupied or the l ight level i s adequate, the l ight wi l l s tay of f.I f a room is occupied or the l ight level i s below the threshold and hysteres is , the l ight wi l l turn on.

I f dark and room occupied

8Button 8 is used to send a button press when l ight levels are within the hysteres is range.

L ight goodLight level i s with the hysteres is

Page 12w w w.touchplate.com

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

App endix I I I - M otion Detec tion R angeThe fol lowing diagram is the motion detec t ion range for the Aura I nter ior sensor.

This representat ion is the minimum detec t ion range poss ible. This representat ion is based on the t ypical sett ing at 25 .

Touch-Plate® L ight ing ControlsAura BACnet I nter ior Manual

Page 13w w w.touchplate.com

Frequently Asked Q uestions

1. How does the sensor get mounted?

a . The sensor comes with a mounting post , washer, and nut . To insta l l the sensor, make a hole in the cei l ing.

b. Place the washer on top of the cei l ing t i le or other mater ia l .c . Screw the nut onto the mounting post unt i l the sensor is secured t ight ly

against the cei l ing.

2 . How does the sensor get uninsta l led?

a. Unscrew the nut f rom the mounting post .b. Remove the washer.c . Pul l the sensor out of i ts mounted locat ion.

3 . Can I open the sensor?

a . The fac tor y does not recommend that you open the sensor. There are no DIP switches to set ins ide the sensor.

b. The l id and the f resnel lens should remain attached to the base of the sensor.

Touch-Plate Aura Inter ior BACnet IR Manual Revis ion: 2.0a