4100ES Fire Control Panels - Haseen Habib Trading Pvt Ltd

10
Features Master Controller (top) bay standard equipment: 32-Bit Master Controller with color-coded operator interface and raised switches for high confidence feedback Dual configuration program CPU, convenient service port access, and capacity for up to 2500 addressable points CPU assembly includes 2 GB dedicated compact flash memory for on-site system programming and information storage An Enhanced Power Supply (EPS+) and battery charger (9 A total) with on-board IDNAC SLCs (signaling line circuit) for addressable appliance control, IDNet 1+ isolated addressable device control channel, and programmable function auxiliary output Also available with InfoAlarm Command Center expanded content user interface (see data sheet S4100-0045) Standard addressable device interfaces include: IDNet 1+ 250 point addressable device SLC supports TrueAlarm analog sensors and IDNet communications monitoring and control devices, and operates with isolated output for use with either shielded or unshielded, twisted or untwisted single pair wiring MINIPLEX Transponder and remote LCD and LED annunciator support via RUI+ (remote unit interface) communications port with isolated output for use with either shielded or unshielded, twisted or untwisted single pair wiring Standard EPS+ power supplies provide enhanced power delivery IDNAC SLCs to addressable notification appliances: With IDNAC SLCs, a constant 29 VRMS source voltage is maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby Efficiencies include lower strobe currents, wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, ability to use smaller gauge wiring, all providing installation and maintenance savings with high assurance appliances that operate during normal system testing will operate during worst case alarm conditions IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther Optional modules and connections include: Fire Alarm Network Interfaces, city connections, and up to five (5) RS-232 ports for printers and terminals Building Network Interface Module (BNIC) for Ethernet connectivity options (see data sheet S4100-0061) Side mounted DACT assembly requiring minimal panel space; DACT is compatible with IP Communicators Emergency communications systems (ECS) equipment; 8 channel digital audio or 2 channel analog audio 4100ES Cabinets are Available with One, Two or Three Bays Option Modules (Continued) Additional IDNet 1+ addressable device communications modules and IDNet+ quad output isolator modules; additional power supplies, alarm relays, and auxiliary relays LED/switch modules and panel mount printers; VESDA Air Aspiration Systems interface, ASHRAE BACnet Interface, TCP/IP Bridges Battery brackets for seismic area protection (see page 2) 4100ES compatible legacy interface modules, including control of conventional (non-addressable) NACS (see data sheet reference list on page 8) 4100ES Listings reference: UL Std. 864, Fire Detection and Control (UOJZ), and Smoke Control Service (UUKL) UL Std. 2017, Process Management Equipment (QVAX) UL Std. 1076, Proprietary Alarm Units-Burglar (APOU) UL Std. 1730, Smoke Detector Monitor (UULH) ULC Std. S527 Control Units for Fire Alarm Systems Software Feature Summary CPU provides dual configuration programs: Two programs allow for optimal system protection and commissioning efficiency with one active program and one reserve; downtime is reduced because the system stays running during download PC based programmer features: Convenient front panel accessed Ethernet port for quick and easy download of site-specific programming Modifications can be uploaded as well as downloaded for greater service flexibility; AND, firmware enhancements are made via software downloads to the on-board flash memory * See pages 7 and 8 for product that is UL or ULC listed and additional listing information. This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products. 4100ES Fire Control Panels UL, ULC, CSFM Listed; Addressable Fire Detection and Control FM Approved* Basic Panel Modules and Accessories S4100-0100 5/2013

Transcript of 4100ES Fire Control Panels - Haseen Habib Trading Pvt Ltd

Features

Master Controller (top) bay standard equipment: 32-Bit Master Controller with color-coded operator

interface and raised switches for high confidence feedback Dual configuration program CPU, convenient service port

access, and capacity for up to 2500 addressable points CPU assembly includes 2 GB dedicated compact flash

memory for on-site system programming and information storage

An Enhanced Power Supply (EPS+) and battery charger (9 A total) with on-board IDNAC SLCs (signaling line circuit) for addressable appliance control, IDNet 1+ isolated addressable device control channel, and programmable function auxiliary output

Also available with InfoAlarm Command Center expanded content user interface (see data sheet S4100-0045)

Standard addressable device interfaces include: IDNet 1+ 250 point addressable device SLC supports

TrueAlarm analog sensors and IDNet communications monitoring and control devices, and operates with isolated output for use with either shielded or unshielded, twisted or untwisted single pair wiring

MINIPLEX Transponder and remote LCD and LED annunciator support via RUI+ (remote unit interface) communications port with isolated output for use with either shielded or unshielded, twisted or untwisted single pair wiring

Standard EPS+ power supplies provide enhanced power delivery IDNAC SLCs to addressable notification appliances: With IDNAC SLCs, a constant 29 VRMS source voltage is

maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby

Efficiencies include lower strobe currents, wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, ability to use smaller gauge wiring, all providing installation and maintenance savings with high assurance appliances that operate during normal system testing will operate during worst case alarm conditions

IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther

Optional modules and connections include: Fire Alarm Network Interfaces, city connections, and up

to five (5) RS-232 ports for printers and terminals Building Network Interface Module (BNIC) for Ethernet

connectivity options (see data sheet S4100-0061) Side mounted DACT assembly requiring minimal panel

space; DACT is compatible with IP Communicators Emergency communications systems (ECS) equipment;

8 channel digital audio or 2 channel analog audio

Press ACK l ocated under fl ashin g indicator.Repeat operation unti l al l events are acknowledged.Local tone wil l silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP ' ( ) , 0 :

S T U V W X Y Z /

ALARMSFire Alarm Priority 2 Alarm

SYSTEM WARNINGSSupervisory Trouble Ala rm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem ind icator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to si lence tone device.

ZONE

1SI G

2A UX

3

FB

4IO

5I DNet

6

P

7A

8L

9

N ET ADDR

0 DE L

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

Enable On Arm

Disable OffDisarm Auto Lamp

Test

MoreInfo

Menu

Previous

Next

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

On

Off

Auto

Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Lo cal to ne will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /

ALARMSFire Alarm Priority 2 Ala rm

SYSTEM WARNINGSSupervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to si lence tone device.

ZONE

1SI G

2A UX

3

FB

4IO

5I DNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

Enable On Arm

Disable OffDisarm Auto Lamp

Test

MoreInfo

Menu

Previous

Next

4100ES Cabinets are Available with One, Two or Three Bays

Option Modules (Continued) Additional IDNet 1+ addressable device communications

modules and IDNet+ quad output isolator modules; additional power supplies, alarm relays, and auxiliary relays

LED/switch modules and panel mount printers; VESDA Air Aspiration Systems interface, ASHRAE BACnet Interface, TCP/IP Bridges

Battery brackets for seismic area protection (see page 2) 4100ES compatible legacy interface modules,

including control of conventional (non-addressable) NACS (see data sheet reference list on page 8)

4100ES Listings reference: UL Std. 864, Fire Detection and Control (UOJZ), and

Smoke Control Service (UUKL) UL Std. 2017, Process Management Equipment (QVAX) UL Std. 1076, Proprietary Alarm Units-Burglar (APOU) UL Std. 1730, Smoke Detector Monitor (UULH) ULC Std. S527 Control Units for Fire Alarm Systems

Software Feature Summary

CPU provides dual configuration programs: Two programs allow for optimal system protection and

commissioning efficiency with one active program and one reserve; downtime is reduced because the system stays running during download

PC based programmer features: Convenient front panel accessed Ethernet port for quick

and easy download of site-specific programming Modifications can be uploaded as well as downloaded for

greater service flexibility; AND, firmware enhancements are made via software downloads to the on-board flash memory

* See pages 7 and 8 for product that is UL or ULC listed and additional listing information. This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.

4100ES Fire Control Panels UL, ULC, CSFM Listed; Addressable Fire Detection and Control FM Approved* Basic Panel Modules and Accessories

S4100-0100 5/2013

Introduction

4100ES Series Fire Detection and Control Panels provide extensive installation, operator, and service features with point and module capacities suitable for a wide range of system applications. An on-board Ethernet port provides fast external system communications to expedite installation and service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files to meet NFPA 72 (National Fire Alarm and Signaling Code) requirements.

Modular design. A wide variety of functional modules are available to meet specific system requirements. Selections allow panels to be configured for either Stand-Alone or Networked fire control operation.

Module Bay Description

The Master Controller Bay (top) includes a standard multi-featured enhanced power supply (EPS+), the master controller board, two vertical expansion blocks, and operator interface equipment.

The Expansion Bays include a Power Distribution Interface (PDI) for connection of single or multiple block modules, and/or slot style (motherboard/daughter card) modules.

The Battery Compartment (bottom) accepts two batteries, up to 50 Ah, to be mounted within the cabinet without interfering with module space.

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

41

00 O

ptio

n

41

00 O

ptio

n

41

00 O

ptio

n

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

PDI

Ma

ster

Con

trol

ler

Bo

ard

Slot 1 Slot 2 Slot 3 Slot 4

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

41

00 O

ptio

n

41

00 O

ptio

n

41

00 O

ptio

n

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

Master Controller Bay

Expansion Bay 1

Battery Compartment

EPS+ Power Supply with IDNet 1+ Module

Master controller with dual slot motherboard

Expansion Bay 2

Typical bays with mixed module sizes

PDI board with two connectors available

4100-6080 DACT mounting location

Optional 4190-6104 TrueInsight Module mounting location

4100ES Module Placement Reference in 3-Bay Cabinet

Mechanical Description

Boxes can be close-nippled; each box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting

Smooth box surfaces are provided for locally cutting conduit entrance holes exactly where required

Cabinet assembly design has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7-05 category D, requires battery brackets as detailed on data sheet S2081-0019

The latching front panel assembly easily lifts off for internal access

Modules are power-limited (except as noted, such as relay modules)

The NEMA 1 box is ordered separately and available for early installation

Doors are available with tempered glass inserts or solid; boxes and doors are available in platinum or red

Boxes and door/retainer assemblies are ordered separately per system requirements; refer to data sheet S4100-0037

Operator Interface Detail Reference

The following illustration identifies the primary functions of the operator interface.

Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Local tone will silence.

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /

ALARMSFire Alarm Priority 2 Alarm

SYSTEM WARNINGSSupervisory Trouble Alarm Silenced

Emergency Operating Instructions

Alarm or Warning Condition

How to Acknowledge / View Events

How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.

How to Reset SystemPress System Reset.Press Ack to silence tone device.

ZONE

1SIG

2AUX

3

FB

4IO

5IDNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

EnableOnArm

DisableOff

DisarmAuto

LampTest

MoreInfo

Menu

Previous

Next

Upload/Download Ethernet port access (under sliding cover)

Basic operator instructions are printed on the interface

mounting plate

Panel sounder

Operator interface panel is directly viewable and accessible (no access door)

Software Feature Summary

“Install Mode” allows grouping of multiple troubles for uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas

Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring

“Recurring Trouble Filtering” allows the panel to recognize, process, and log recurring intermittent troubles (such as external wiring ground faults), but only sends a single outbound system trouble to avoid nuisance communications

WALKTEST silent or audible system test performs an automatic self-resetting test cycle

Support for TrueAlarm individual analog sensing and IDNAC addressable notification with front panel information and selection access

2 S4100-0100 5/2013

Operator Interface

Convenient Status Information. With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in the illustration below.

LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control switches and allows further inquiry by scrolling the display for additional detail.

Operator Interface Features

Convenient and extensive operator information is provided using a logical, menu-driven display

Multiple automatic and manual diagnostics for maintenance reduction

Alarm and Trouble History Logs (up to 1250 entries for each, 2500 total events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer

Convenient PC programmer label editing Password access control

A B C

AC Power

D E F G H I

J K L M N O P Q R

'SP' ( ) , 0 :

S T U V W X Y Z /

ALARMSFire Alarm Priority 2 Alarm

SYSTEM WARNINGSSupervisory Trouble Alarm Silenced

ZONE

1SIG

2AUX

3

FB

4IO

5IDNet

6

P

7A

8L

9

NET ADDR

0 DEL

Enter C/Exit

Fire AlarmAck

Priority 2Ack

SupvAck

TroubleAck

AlarmSilence

SystemReset

EventTime

EnableOn

Arm

DisableOff

DisarmAuto

LampTest

MoreInfo

Menu

Previous

Next

SIX SYSTEM STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset :Fire Alarm & Priority 2 Alarm, red LEDSupervisory & Trouble, yellow LEDAlarm Silenced, yellow LEDAC Power, green LED (on for normal)

FIVE PROGRAMMABLE FUNCTION SWITCHES, each with a yellow LED indicator

POINT STATUS CONTROL KEYS:Point Enable and DisableForce On or ArmForce Off or DisarmReturn On/Off or Arm/Disarm to Auto Mode

NUMERIC KEYPAD for point category and point selection (alphabet characters are not used at this time)

ADDITIONAL FUNCTION KEYS:Event Time RequestMore Information RequestLamp Test

Elevator Recall

City Disconnect

Manual Evac

Ground Fault

Waterflow-West

Waterflow-East

Custom label insert

LCD NAVIGATION CONTROL:Menu selectionVertical and Horizontal position selection buttons

FIRE ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

PRIORITY 2 ACK acknowledges a Priority 2 Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

TROUBLE ACK acknowledges system troubles, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts

ALARM SILENCE causes audible notification appliances to be silenced (depending on panel programming) typically after evacuation is complete and while alarm source is being investigated; may allow visible notification to continue (strobes still flashing)

SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal

2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 40 characters for custom label information

FIRST ALARM DISPLAY: Operation can be selected for maintained display of first alarm until acknowledged

THREE PROGRAMMABLE LEDs provide custom labeling, the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow

ULC SYSTEMS require designating a Ground Fault indicator

Almost Dirty

Ground Fault Latch

3 S4100-0100 5/2013

Overview. The 4100ES with EPS+ power supplies provides IDNet 1+ addressable initiating device and IDNAC addressable notification appliance Signaling Line Circuits (SLCs) that supervise wiring connections and the individual device/appliance communications status on their SLC. With these 2-wire SLCs, initiation, monitoring, and control devices such as manual fire alarm stations, TrueAlarm sensors, control relays, and sprinkler waterflow switches; and notification appliances such as strobes and horns can communicate their identity and status and receive fire alarm system control. Additional interface modules include circuit isolators, conventional IDC zone adapters, and interface to other system circuits such as fans, dampers, and elevator controls.

IDNet Addressable Device Operation

Each addressable device on the IDNet 1+ communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation is available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuits for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel. With addressable devices, the location and status of the connected device is monitored and logged, and displayed on the operator interface LCD and on remote system annunciators with each device having its own 40 character custom label for precise identification.

TrueAlarm Addressable Sensor Operation

Addressable initiating device communications include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.

TrueAlarm Addressable Sensor Reference

TrueAlarm Photo Sensor with Base

TrueAlarm Photo/Heat

Sensor in CO Base

Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read (or downloaded as a report) and compared to the alarm threshold directly in percent.

CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, used in LED/Switch modes and custom control, and can be made public for communication across a fire alarm Network. (refer to data sheet S4098-0041 for details)

TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius. TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4100ES IDNet address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet S4098-0024.

Diagnostics and Default Device Type

Sensor Status. TrueAlarm operation allows the control panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 5 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and end of life.

Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.

IDNet Addressable Device Wiring Reference

IDNet 1+ Addressable Channel Capacity. The CPU bay system power supply (EPS+) provides an IDNet 1+ signaling line circuit (SLC) that supports up to 250 addressable monitor and control points intermixed on the same pair of wires. Additional 250 address IDNet 1+ circuit modules are available.

IDNet 1+ SLC Wiring Specifications

Maximum Distance from Control Panel per Device Load

0 to 125 4000 ft (1219 m); 50 ohms

126-250 2500 feet (762 m); 35 ohms

Total Wire Length Allowed With “T” Taps for Class B Wiring

Up to 12,500 ft (3.8 km); 0.60 µF

Maximum Capacitance Between IDNet+ Channels

1 µF

Wire Type and Connections Shielded or unshielded, twisted or untwisted wire*

Connections Terminal blocks for 18 to 12 AWG

Installation Instructions (see for more information) 579-1014

* Some applications may require shielded wiring. Review your system with your local Simplex product supplier.

4 S4100-0100 5/2013

IDNet Addressable Device and IDNAC Addressable Notification Appliance Control

Addressable notification appliance communications include operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible (S/V) notification appliances. (S/V appliances require separate speaker wiring.) IDNAC SLC addressable communications allow each horn and strobe to be individually controlled using a single two-wire circuit, confirms the wiring connections to the individual notification appliance’s electronic circuit, and confirms communications between each appliance and the fire alarm control panel. Addressable communications increases supervision integrity versus conventional notification systems by providing supervision beyond the circuit wiring to each individual appliance and by constantly verifying the ability of each appliance to communicate with the control panel.

Individual Appliance Status and Settings. Each addressable notification appliance is polled by the control panel to verify its ability to communicate. The fire alarm control panel monitors each addressable notification appliances for its status, condition, type of appliance, and configured appliance settings. A fault in any individual appliance automatically reports a trouble condition to the control panel.

TrueAlert ES Addressable Appliance Reference

A/O (horn) V/O (strobe) A/V (horn/strobe)

Location Information, Diagnostics, and Troubleshooting. Each addressable notification appliance has its own 40 character custom label to identify the location of the appliance and to aid in troubleshooting fault conditions. In conventional notification systems, conventional appliances are not capable of communicating with the control panel. Fault reporting on a conventional system is limited to the circuit wiring and the entire area (zone) covered by appliances on the notification appliance circuit (NAC) making it much more difficult and costly to locate and correct the source of a problem.

Tracking Appliance Details. The 4100ES with IDNAC SLCs provides intelligent addressable communications that allow detailed information associated with each addressable notification appliance to be reported to the fire alarm control panel for diagnostics and troubleshooting. Detailed information available includes; the appliance location, status, condition, type of appliance, and configured appliance settings.

New Installation, Retrofit, and Life-Cycle Cost Benefits. With each addressable appliance capable of being controlled separately on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T-tapped”, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency.

Panel Control Convenience. Applicable operation settings for each appliance can be programmed without having to replace appliances or remove them from the wall or ceiling. An appliance’s notification zone can be easily changed through programming without having to add additional circuits, conduit, and wiring. Audible and visible appliances for non-Fire Emergency Communications notification can be programmed to operate separately on the same pair of wires as the fire alarm notification appliances. The result is lower installation, retrofit, and overall life-cycle cost of ownership compared with traditional conventional notification systems.

IDNAC SLC Hardware Reference

EPS+ and EPS Power Supplies provide three, 3 A IDNAC SLCs for control and power to TrueAlert ES and TrueAlert addressable notification appliances. Both power supplies incorporate an efficient switching design that provides a regulated output of 29 VRMS, even during battery operation. With 29 VRMS minimum output at the panel, addressable notification SLCs can support wiring distances 2 to 3 times farther than available with conventional notification, or support more appliances per SLC, or work with smaller gauge wiring, or combinations of these benefits, all resulting in installation and maintenance savings with high assurance appliances that operate during normal system testing will operate during worst case alarm conditions.

Virtual NACs Provide Control Convenience. For control convenience, IDNAC notification appliances can be grouped into Virtual NACS for group control, grouping that can be made across SLCs, not defined by their wiring connection.

IDNAC SLC Appliance Wiring Reference

Recommended wire type UTP, unshielded twisted pair

IDNAC SLC Capacity

Up to 63 addresses and up to 75 unit loads (appliances are typically one unit load, devices such as Isolators may require more than one load, refer to individual device data sheet for specific information)

Maximum wire length allowed with “T-Taps” for Class B wiring, per SLC

10,000 ft (3048 m)

Maximum wire length per SLC to any appliance

4000 ft (1219 m)

Maximum wiring resistance between appliances

26 Ω

Wiring connections Terminal blocks for 18 to 12 AWG

Installation Instructions (see for more information) 579-1015

5 S4100-0100 5/2013

IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification

Master Controller and Motherboard: Mounts in Slot 2 of a two slot motherboard and provides

one Style 4 or Style 7, RUI+, isolated communications channel with earth fault detection

RUI+ isolated communications controls up to 31 devices per master controller at up to 2500 ft (762 m) for single run, or 10,000 ft (3048 m) total if wiring is Class B and T-tapped; if more distance is required, up to four total RUI channels are supported; add up to three 4100-1291 RUI expansion modules (4100-1291 provides unisolated RUI communications)

RUI remote equipment includes: MINIPLEX transponders, 4603-9101 LCD Annunciators, 4602-9101 Status Command Units (SCU), 4602-9102 Remote Command Units (RCU), 4602 Series LED Annunciator Panels, 4100 Series 24 I/O and LED/Switch modules

Open slot space on the left of the CPU motherboard is available for either another dual slot motherboard, or for one or two block modules (refer to diagram on page 2)

Slot 1 of the motherboard is primarily for the 4100-6078 Network Interface Board with media modules

EPS+ Power Supply: (see page 9 for more detail) Rating is 9 A total with “Special Application” appliances Outputs are power-limited, except for the battery charger Provides system power, battery charging, auxiliary

power, auxiliary relay, earth detection, on-board IDNet 1+ communications channel for 250 points, three on-board 3 A IDNAC SLCs, and provisions for either an optional City Connect Module or an optional Alarm Relay Module

IDNet 1+ SLC Output provides Class B or Class A communications for up to 250 addressable devices (as described on page 4)

DCAI (Dual Class A IDNAC Isolator) module creates two Class A outputs from one IDNAC SLC Class B Input; up to two can be connected to one IDNAC SLC, with up to 6 total per EPS; total Class A output loop current is limited to the 3 A rating of the IDNAC SLC

EPS+ Power Supply (Continued): Battery Charger is dual rate, temperature

compensated, and charges up to 50 Ah sealed lead-acid batteries mounted in the battery compartment (33 Ah for single bay cabinets); also is UL listed for charging up to 115 Ah batteries mounted in an external cabinet (see data sheet S2081-0012 for details)

Battery and Charger Monitoring includes battery charger status and low or depleted battery conditions; status information provided to the master controller includes analog values for: battery voltage, charger voltage and current, actual system voltage and current, and individual IDNAC SLC currents

Low Battery Cutout is selectable for each EPS+ (and EPS) power supply, Canadian models are shipped selected, other models are shipped unselected

2 A Programmable Output: Select for conventional non-synchronous NAC

operation to provide supervised reverse polarity for sounder base power, Suppression Release Peripheral (SRP) power, or other coded NAC operation requirements

Select for Auxiliary (AUX) operation for sounder base power, 4-wire detector power, or door holder; supervised AUX operation does not require an end-of-line relay to provide Power-Limited operation

EPS+ Power Supply Mounted Optional Modules (select one): City Connect Module (4100-6031, with disconnect

switches, or 4100-6032, without disconnect switches) can be selected for conventional dual circuit city connections

Alarm Relay Module (4100-6033) provides three Form C relays that are used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC

Master Controller and Expansion Bay Selection

Model Model Type and Listing Description Current

4100-9311 120 VAC, 50/60 Hz Input UL 4100ES Master Controller Assembly with LCD and operator interface, 9 A EPS+ Enhanced Power Supply/battery charger with 250 point IDNet 1+ interface, 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and one output configurable for Auxiliary or simple NAC operation

Without IDNet devices: Supervisory = 217 mA Alarm = 480 mA With 200 IDNet devices and 20 device LEDs in alarm: Supervisory = 417 mA Alarm = 770 mA

4100-9312 English 120 VAC, 50/60 Hz Canadian

ULC 4100-9313 French

4100-9511 220-240 VAC, 50/60 Hz Input

UL

4100-9331 120 VAC, 50/60 Hz input UL 4100ES Master Controller Assembly, No Display, No Operator Interface, 9 A EPS+ Enhanced Power Supply/battery charger with 250 point IDNet 1+ interface, 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and one output configurable for Auxiliary or simple NAC operation

4100-9332 120 VAC, 50/60 Hz input, Canadian, English

ULC

4100-2300 Expansion Bay Assembly; order for each required expansion bay

4100-2303 Slot Module Stabilizer Bracket, used when expansion bays have style modules

(Continued on next page)

6 S4100-0100 5/2013

Master Controller Selection Information

CPU Bay Module Details

7 S4100-0100 5/2013

Communication Modules Model Description Size Supv. Alarm

4100-6078 For Master Controller; mounts in Slot 3 Modular Network Interface; each requires two media modules (below)

1 Slot 46 mA 46 mA 4100-6061 For Redundant Master Controller 1 Slot 46 mA 46 mA

4100-6056 Wired Media Module Select two media cards as required; mounts on 4100-6078 or 4100-6061

N.A. 55 mA 55 mA 4100-6057 Fiber Optic Media Module N.A. 25 mA 25 mA

4100-6047 Building Network Interface Card (BNIC), refer to data sheet S4100-0061 for details 2 Blocks 291 mA 291 mA

4100-6055 Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network Interface Card, requires telephone line connection N.A. 60 mA 60 mA

4100-1291 Remote Unit Interface Module (RUI, unisolated); up to 3 maximum per control panel 1 Slot 85 mA 85 mA

4100-6031 Select one per EPS+ or EPS

City Circuit, with disconnect switches N.A. 20 mA 36 mA 4100-6032 City Circuit, w/o disconnect switches N.A. 20 mA 36 mA 4100-6033 Alarm Relay, 3 Form C relays, 2 A @ 32 VDC N.A. 15 mA 37 mA

4100-6046 Dual Port RS-232 standard interface (single block) 3 maximum RS-232 modules per panel

1 Block 60 mA 60 mA 4100-6038 Dual Port RS-232 with 2120 interface (slot module) 1 Slot 132 mA 132 mA

4100-6079 SafeLINC Internet Interface (refer to data sheet S4100-0062 for details) 2 Blocks 145 mA 145 mA 4190-6104 TrueInsight Remote Monitoring Module (refer to data sheet S4100-0063 for details) Side Mt. 62 mA 73 mA 4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1 Slot 210 mA 210 mA 4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2 Slots 300 mA 300 mA 4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA

4100-6080 DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected; 2 max. per system; includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs Side Mt. 30 mA 40 mA

Additional Enhanced Power Supplies, Expansion and Remote Power Supplies, and Accessories Model Voltage/Listing Description Size Supv. Alarm

4100-5311 120 VAC UL & ULC

Additional Enhanced Power Supply (EPS+); 9 A Enhanced Power Supply/battery charger with 250 point IDNet 1+ interface, 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and auxiliary relay; 120 VAC model has selectable low battery cutout

4 Blocks Right Side

217 mA 480 mA

4100-5313 220-240 VAC UL with 200 IDNet devices and 20

device LEDs in alarm

4100-5325 120 VAC UL & ULC

Enhanced Power Supply (EPS); 9 A Enhanced Power Supply/battery charger with 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and auxiliary relay; 120 VAC model has selectable low battery cutout

4 Blocks Right Side

125 mA 220 mA 4100-5327 220-240 VAC UL

4100-6103

Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to two Class A or two Class B SLC outputs; provides short circuit isolation between each Class A or B output circuit; connect up to two DCAI modules per IDNAC SLC input up to a maximum of 6 DCAI modules per EPS; each isolated output SLC used requires one IDNAC address; the total current remains controlled by the Class B input source SLC at 3 A maximum

1 Block 6.5 mA 6.5 mA

4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum 4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block included w/loads

4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet 4100-0638 4100 Slot Module Additional 24 VDC Harness; need when 4100 Slot module requirements exceed 2 A from EPS

Module Selection is continued on next page

Subject Data Sheet Subject Data Sheet

Introducing the 4100ES S4100-0060 Fire Alarm Network Overview S4100-0055

4100ES Enclosures S4100-0037 Network Communications S4100-0056

4100ES Audio and Firefighter Phone Modules S4100-0034 Network Display Unit (NDU) S4100-0102

LED/Switch Modules & Printer S4100-0032 Addressable Device Compatibility S4090-0011

Remote Annunciators S4100-0038 4009 IDNAC Repeater S4009-0004

MINIPLEX Transponders S4100-0103 IDNet+ Module w/Quad Isolator S4100-0046

Building Network Interface (BNIC) S4100-0061 Remote Battery Charger S4081-0002

InfoAlarm Command Center S4100-0101 TFX Interface Module S4100-0042

Graphic I/O Modules S4100-0005 SafeLINC Internet Interface S4100-0062

TrueInsight Remote Service S4100-0063 4100ES Panels for Conventional Notification S4100-0031

Agent Release Applications S4100-0040 TrueAlarm Sensors S4098-0019

TrueAlert ES Audible Only Appliances S49AO-0001 TrueAlert ES Audible/Visible Appliances S49AV-0001

TrueAlert ES Visible Only Appliances S49VO-0001 TrueAlert ES Weatherproof Appliances, UL Listed S49WP-0001

TrueAlert Appliance/IDNAC SLC Isolator S4905-0001 TrueAlert ES Weatherproof Appliances, ULC Listed S49WP-0002

Module Selection Information

Additional 4100ES Data Sheet and Related Product Reference

8 S4100-0100 5/2013

Addressable Interface Modules (refer to location reference on pages 9 and 10) Model Description Supv. Alarm

4100-3108 IDNet 1+ Module, 250 point capacity with isolated output, 1 block

With 250 IDNet devices, and 20 device LEDs in alarm 292 mA 510 mA

Module without devices 92 mA 115 mA

Loading per IDNet device (no LEDs on) 0.8 mA 1 mA

4100-3107

Quad IDNet Isolator Module; converts a single connected SLC into four isolated outputs selectable as Class A or Class B, provides advanced diagnostics for use with retrofit wiring; dual horizontal block module; (see data sheet S4100-0046 for additional details) NOTE: This module is compatible with IDNet Remote Isolators

75 mA 115 mA

Relay Modules; Nonpower-limited (for mounting in expansion bay only, refer to location reference on pages 9 and 10) Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm

4100-3202 4 DPDT w/feedback 10 A @ 250 VAC 10 A @ 250 VAC 2 Slots 15 mA 175 mA

4100-3204 4 DPDT w/feedback 2 A @ 30 VDC/VAC 1/2 A @ 30 VDC/120 VAC 1 Block 15 mA 60 mA

4100-3206 8 SPDT 3 A @ 30 VDC/120 VAC 1-1/2 A @ 30 VDC/120 VAC 1 Block 15 mA 190 mA

Current Calculation Notes: 1. To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered

by panel power supplies. 2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel SLC and

NAC loads and all external loads powered from panel power supplies.

Miscellaneous Accessories Model Description

4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay

4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules

4100-6029 Smoke Management Application Guide; required for UUKL listing

4100-6034 Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM

2081-9031 Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 Ω, 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)

Input Power

Enhanced Power Supplies, EPS/EPS+

120 VAC Models 4.6 A maximum @ 102 to 132 VAC, 50/60 Hz

220-240 VAC Models 2.3 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC

Power Supply Output Ratings for EPS/EPS+

Total Power Supply Output Rating

Including module currents and auxiliary power outputs; 9 A total for “Special Application” appliances

Output switches to battery backup during mains AC failure or brownout conditions

IDNAC SLC Ratings 3 A, regulated 29 VRMS, 63 addresses, 75 unit loads

Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)

Compatible Special Application Appliances Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances

Battery Charger Ratings for EPS/EPS+ (sealed lead-acid batteries)

Battery capacity range UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries

Charger characteristics and performance

Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527

Environmental Operating Temperature 32° to 120°F (0° to 49° C)

Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum

Additional Technical Reference

Description Document

ES Installation Instructions 574-848

ES Operating Instructions 579-197

IDNet 1+ Module Installation Instructions 579-1014

EPS/EPS+ Installation Instructions 579-1015

DCAI Module Installation Instructions 579-1029

Module Selection Information (Continued)

General Specifications

Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2

Expansion Bay Chassis

Block A

Block B

Block C

Block D

Block E

Block F

Block G

Block H

Size Definitions: 1 Block = 4” W x 5.65” H (102 mm x 144 mm); (often called

x 5 modules) 1 Slot = 2” W x 11.3” H (51 mm x 287 mm), typically a

motherboard with daughter card

PDI

Ma

ste

r C

on

tro

ller

Bo

ard

PDI

4x5 Module

Expansion PowerSupply

(XPS)

4x5 Module

I/O Wiring

I/O Wiring

I/O Wiring

41

00

Op

tion

41

00

Op

tion

41

00

Op

tion

Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8

(Block E)

(Block F)

(Blocks G & H)

*EPS+ power supply with IDNet 1+ module

Optional semi-flush trim kit

4100-6031 or 4100-6032 City Circuit or 4100-6033Alarm Relay mounts on bottom of EPS

4100-6030 Service Modem mounts only on master controller board

One 2" card: either 4100-6078 Network Module with media cards or 4100-6038 RS-232/2120 Interface

Cabinet height:(2 bay shown for reference)

1 Bay = 22"(559 mm)

2 Bay = 40"(1016 mm)

3 Bay = 56"(1427 mm)

Stud alignment markers, each side

Knockout screw/nail holes (for semi-flush mounting)

4" stud

6" stud

Master Controller Bay

Typical Expansion Bay(showing mixed module sizes)

Battery Compartment(50 Ah maximum)

Door can be hunghinged left or right

Wall board reference for semi-flush mounting, 6" stud

Two bay cabinet shown without dress panel

11-11/16"(296 mm)

6-29/32"(175 mm)

Door thickness4-3/4"(121 mm)

Exposed cabinet forsemi-flush mounting

1-3/8" (35 mm)minimum

Exposed door and cabinet for semi-

flush mounting 6-1/8" (156 mm)

minimum

24" (610 mm)

Door 4-3/4"(121 mm)

4100-6080 DACT mounting location

*Master controller with motherboard

Space for two 2" slot modules, or one 4" slot modules, or two single block modules, or one double block (vertical mount) module

Optional 4100-6049 TrueInsight Module mounting location

NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made

to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

9 S4100-0100 5/2013

Expansion Bay Module Loading Reference

Mounting and CPU Bay Module Reference (* indicates supplied modules)

Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4100-0100 5/2013

www.simplexgrinnell.com © 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA). ASHRAE and BACnet are trademarks of ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.