Features
Master Controller (top) bay standard equipment: 32-Bit Master Controller with color-coded operator
interface and raised switches for high confidence feedback Dual configuration program CPU, convenient service port
access, and capacity for up to 2500 addressable points CPU assembly includes 2 GB dedicated compact flash
memory for on-site system programming and information storage
An Enhanced Power Supply (EPS+) and battery charger (9 A total) with on-board IDNAC SLCs (signaling line circuit) for addressable appliance control, IDNet 1+ isolated addressable device control channel, and programmable function auxiliary output
Also available with InfoAlarm Command Center expanded content user interface (see data sheet S4100-0045)
Standard addressable device interfaces include: IDNet 1+ 250 point addressable device SLC supports
TrueAlarm analog sensors and IDNet communications monitoring and control devices, and operates with isolated output for use with either shielded or unshielded, twisted or untwisted single pair wiring
MINIPLEX Transponder and remote LCD and LED annunciator support via RUI+ (remote unit interface) communications port with isolated output for use with either shielded or unshielded, twisted or untwisted single pair wiring
Standard EPS+ power supplies provide enhanced power delivery IDNAC SLCs to addressable notification appliances: With IDNAC SLCs, a constant 29 VRMS source voltage is
maintained, even during battery standby, allowing strobes to operate at higher voltage with lower current and ensuring a consistent current draw and voltage drop margin under both primary power and secondary battery standby
Efficiencies include lower strobe currents, wiring distances up to 2 to 3 times farther than with conventional notification, support for more appliances per IDNAC SLC, ability to use smaller gauge wiring, all providing installation and maintenance savings with high assurance appliances that operate during normal system testing will operate during worst case alarm conditions
IDNAC SLCs are compatible with both TrueAlert ES and TrueAlert addressable notification appliances, and remote 4009 IDNAC Repeaters to extend power and wiring distance even farther
Optional modules and connections include: Fire Alarm Network Interfaces, city connections, and up
to five (5) RS-232 ports for printers and terminals Building Network Interface Module (BNIC) for Ethernet
connectivity options (see data sheet S4100-0061) Side mounted DACT assembly requiring minimal panel
space; DACT is compatible with IP Communicators Emergency communications systems (ECS) equipment;
8 channel digital audio or 2 channel analog audio
Press ACK l ocated under fl ashin g indicator.Repeat operation unti l al l events are acknowledged.Local tone wil l silence.
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP ' ( ) , 0 :
S T U V W X Y Z /
ALARMSFire Alarm Priority 2 Alarm
SYSTEM WARNINGSSupervisory Trouble Ala rm Silenced
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building SignalsSystem ind icator flashing. Tone On. Press Alarm Silence.
How to Reset SystemPress System Reset.Press Ack to si lence tone device.
ZONE
1SI G
2A UX
3
FB
4IO
5I DNet
6
P
7A
8L
9
N ET ADDR
0 DE L
Enter C/Exit
Fire AlarmAck
Priority 2Ack
SupvAck
TroubleAck
AlarmSilence
SystemReset
EventTime
Enable On Arm
Disable OffDisarm Auto Lamp
Test
MoreInfo
Menu
Previous
Next
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Lo cal to ne will silence.
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP' ( ) , 0 :
S T U V W X Y Z /
ALARMSFire Alarm Priority 2 Ala rm
SYSTEM WARNINGSSupervisory Trouble Alarm Silenced
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.
How to Reset SystemPress System Reset.Press Ack to si lence tone device.
ZONE
1SI G
2A UX
3
FB
4IO
5I DNet
6
P
7A
8L
9
NET ADDR
0 DEL
Enter C/Exit
Fire AlarmAck
Priority 2Ack
SupvAck
TroubleAck
AlarmSilence
SystemReset
EventTime
Enable On Arm
Disable OffDisarm Auto Lamp
Test
MoreInfo
Menu
Previous
Next
4100ES Cabinets are Available with One, Two or Three Bays
Option Modules (Continued) Additional IDNet 1+ addressable device communications
modules and IDNet+ quad output isolator modules; additional power supplies, alarm relays, and auxiliary relays
LED/switch modules and panel mount printers; VESDA Air Aspiration Systems interface, ASHRAE BACnet Interface, TCP/IP Bridges
Battery brackets for seismic area protection (see page 2) 4100ES compatible legacy interface modules,
including control of conventional (non-addressable) NACS (see data sheet reference list on page 8)
4100ES Listings reference: UL Std. 864, Fire Detection and Control (UOJZ), and
Smoke Control Service (UUKL) UL Std. 2017, Process Management Equipment (QVAX) UL Std. 1076, Proprietary Alarm Units-Burglar (APOU) UL Std. 1730, Smoke Detector Monitor (UULH) ULC Std. S527 Control Units for Fire Alarm Systems
Software Feature Summary
CPU provides dual configuration programs: Two programs allow for optimal system protection and
commissioning efficiency with one active program and one reserve; downtime is reduced because the system stays running during download
PC based programmer features: Convenient front panel accessed Ethernet port for quick
and easy download of site-specific programming Modifications can be uploaded as well as downloaded for
greater service flexibility; AND, firmware enhancements are made via software downloads to the on-board flash memory
* See pages 7 and 8 for product that is UL or ULC listed and additional listing information. This product has been listed by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:0251 for allowable values and/or conditions concerning material presented in this document. Additional listings may be applicable; contact your local Simplex product supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
4100ES Fire Control Panels UL, ULC, CSFM Listed; Addressable Fire Detection and Control FM Approved* Basic Panel Modules and Accessories
S4100-0100 5/2013
Introduction
4100ES Series Fire Detection and Control Panels provide extensive installation, operator, and service features with point and module capacities suitable for a wide range of system applications. An on-board Ethernet port provides fast external system communications to expedite installation and service activity. Dedicated compact flash memory archiving provides secure on-site system information storage of electronic job configuration files to meet NFPA 72 (National Fire Alarm and Signaling Code) requirements.
Modular design. A wide variety of functional modules are available to meet specific system requirements. Selections allow panels to be configured for either Stand-Alone or Networked fire control operation.
Module Bay Description
The Master Controller Bay (top) includes a standard multi-featured enhanced power supply (EPS+), the master controller board, two vertical expansion blocks, and operator interface equipment.
The Expansion Bays include a Power Distribution Interface (PDI) for connection of single or multiple block modules, and/or slot style (motherboard/daughter card) modules.
The Battery Compartment (bottom) accepts two batteries, up to 50 Ah, to be mounted within the cabinet without interfering with module space.
PDI
4x5 Module
Expansion PowerSupply
(XPS)
4x5 Module
I/O Wiring
I/O Wiring
I/O Wiring
41
00 O
ptio
n
41
00 O
ptio
n
41
00 O
ptio
n
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
(Block E)
(Block F)
(Blocks G & H)
PDI
Ma
ster
Con
trol
ler
Bo
ard
Slot 1 Slot 2 Slot 3 Slot 4
PDI
4x5 Module
Expansion PowerSupply
(XPS)
4x5 Module
I/O Wiring
I/O Wiring
I/O Wiring
41
00 O
ptio
n
41
00 O
ptio
n
41
00 O
ptio
n
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
(Block E)
(Block F)
(Blocks G & H)
Master Controller Bay
Expansion Bay 1
Battery Compartment
EPS+ Power Supply with IDNet 1+ Module
Master controller with dual slot motherboard
Expansion Bay 2
Typical bays with mixed module sizes
PDI board with two connectors available
4100-6080 DACT mounting location
Optional 4190-6104 TrueInsight Module mounting location
4100ES Module Placement Reference in 3-Bay Cabinet
Mechanical Description
Boxes can be close-nippled; each box provides convenient stud markers for drywall thickness and nail-hole knockouts for quicker mounting
Smooth box surfaces are provided for locally cutting conduit entrance holes exactly where required
Cabinet assembly design has been seismic tested and is certified to IBC and CBC standards as well as to ASCE 7-05 category D, requires battery brackets as detailed on data sheet S2081-0019
The latching front panel assembly easily lifts off for internal access
Modules are power-limited (except as noted, such as relay modules)
The NEMA 1 box is ordered separately and available for early installation
Doors are available with tempered glass inserts or solid; boxes and doors are available in platinum or red
Boxes and door/retainer assemblies are ordered separately per system requirements; refer to data sheet S4100-0037
Operator Interface Detail Reference
The following illustration identifies the primary functions of the operator interface.
Press ACK located under flashing indicator.Repeat operation until all events are acknowledged.Local tone will silence.
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP' ( ) , 0 :
S T U V W X Y Z /
ALARMSFire Alarm Priority 2 Alarm
SYSTEM WARNINGSSupervisory Trouble Alarm Silenced
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building SignalsSystem indicator flashing. Tone On. Press Alarm Silence.
How to Reset SystemPress System Reset.Press Ack to silence tone device.
ZONE
1SIG
2AUX
3
FB
4IO
5IDNet
6
P
7A
8L
9
NET ADDR
0 DEL
Enter C/Exit
Fire AlarmAck
Priority 2Ack
SupvAck
TroubleAck
AlarmSilence
SystemReset
EventTime
EnableOnArm
DisableOff
DisarmAuto
LampTest
MoreInfo
Menu
Previous
Next
Upload/Download Ethernet port access (under sliding cover)
Basic operator instructions are printed on the interface
mounting plate
Panel sounder
Operator interface panel is directly viewable and accessible (no access door)
Software Feature Summary
“Install Mode” allows grouping of multiple troubles for uninstalled modules and devices into a single trouble condition (typical with future phased expansion); with future equipment and devices grouped into a single trouble, operators can more clearly identify events from the commissioned and occupied areas
Module level ground fault searching assists installation and service by locating and isolating modules with grounded wiring
“Recurring Trouble Filtering” allows the panel to recognize, process, and log recurring intermittent troubles (such as external wiring ground faults), but only sends a single outbound system trouble to avoid nuisance communications
WALKTEST silent or audible system test performs an automatic self-resetting test cycle
Support for TrueAlarm individual analog sensing and IDNAC addressable notification with front panel information and selection access
2 S4100-0100 5/2013
Operator Interface
Convenient Status Information. With the locking door closed, the glass window allows viewing of the display, status LEDs, and available operator switches. Features include a two-line by 40-character, wide viewing angle (super-twist) LCD with status LEDs and switches as shown in the illustration below.
LED indicators describe the general category of activity being displayed with the LCD providing more detail. For the authorized user, unlocking the door provides access to the control switches and allows further inquiry by scrolling the display for additional detail.
Operator Interface Features
Convenient and extensive operator information is provided using a logical, menu-driven display
Multiple automatic and manual diagnostics for maintenance reduction
Alarm and Trouble History Logs (up to 1250 entries for each, 2500 total events) are available for viewing from the LCD, or capable of being printed to a connected printer, or downloaded to a service computer
Convenient PC programmer label editing Password access control
A B C
AC Power
D E F G H I
J K L M N O P Q R
'SP' ( ) , 0 :
S T U V W X Y Z /
ALARMSFire Alarm Priority 2 Alarm
SYSTEM WARNINGSSupervisory Trouble Alarm Silenced
ZONE
1SIG
2AUX
3
FB
4IO
5IDNet
6
P
7A
8L
9
NET ADDR
0 DEL
Enter C/Exit
Fire AlarmAck
Priority 2Ack
SupvAck
TroubleAck
AlarmSilence
SystemReset
EventTime
EnableOn
Arm
DisableOff
DisarmAuto
LampTest
MoreInfo
Menu
Previous
Next
SIX SYSTEM STATUS INDICATOR LEDs provide system status indications in addition to LCD information, LEDs flash to indicate the condition and then when acknowledged, remain on until reset :Fire Alarm & Priority 2 Alarm, red LEDSupervisory & Trouble, yellow LEDAlarm Silenced, yellow LEDAC Power, green LED (on for normal)
FIVE PROGRAMMABLE FUNCTION SWITCHES, each with a yellow LED indicator
POINT STATUS CONTROL KEYS:Point Enable and DisableForce On or ArmForce Off or DisarmReturn On/Off or Arm/Disarm to Auto Mode
NUMERIC KEYPAD for point category and point selection (alphabet characters are not used at this time)
ADDITIONAL FUNCTION KEYS:Event Time RequestMore Information RequestLamp Test
Elevator Recall
City Disconnect
Manual Evac
Ground Fault
Waterflow-West
Waterflow-East
Custom label insert
LCD NAVIGATION CONTROL:Menu selectionVertical and Horizontal position selection buttons
FIRE ALARM ACK acknowledges a Fire Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
PRIORITY 2 ACK acknowledges a Priority 2 Alarm condition, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
SUPV ACK acknowledges system supervisory conditions, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
TROUBLE ACK acknowledges system troubles, logs the acknowledge, and silences the operator panel and all annunciator tone-alerts
ALARM SILENCE causes audible notification appliances to be silenced (depending on panel programming) typically after evacuation is complete and while alarm source is being investigated; may allow visible notification to continue (strobes still flashing)
SYSTEM RESET restores control panel to normal when all alarmed inputs are returned to normal
2 X 40 LCD READOUT, LED backlighted during normal conditions and abnormal operating conditions, provides up to 40 characters for custom label information
FIRST ALARM DISPLAY: Operation can be selected for maintained display of first alarm until acknowledged
THREE PROGRAMMABLE LEDs provide custom labeling, the top two LEDs are selectable as red or yellow, the bottom LED is selectable as green or yellow
ULC SYSTEMS require designating a Ground Fault indicator
Almost Dirty
Ground Fault Latch
3 S4100-0100 5/2013
Overview. The 4100ES with EPS+ power supplies provides IDNet 1+ addressable initiating device and IDNAC addressable notification appliance Signaling Line Circuits (SLCs) that supervise wiring connections and the individual device/appliance communications status on their SLC. With these 2-wire SLCs, initiation, monitoring, and control devices such as manual fire alarm stations, TrueAlarm sensors, control relays, and sprinkler waterflow switches; and notification appliances such as strobes and horns can communicate their identity and status and receive fire alarm system control. Additional interface modules include circuit isolators, conventional IDC zone adapters, and interface to other system circuits such as fans, dampers, and elevator controls.
IDNet Addressable Device Operation
Each addressable device on the IDNet 1+ communication channel is continuously interrogated for status condition such as: normal, off-normal, alarm, supervisory, or trouble. Both Class B and Class A operation is available. Sophisticated poll and response communication techniques ensure supervision integrity and allow for "T-tapping" of the circuits for Class B operation. Devices with LEDs pulse the LED to indicate receipt of a communications poll and can be turned on steady from the panel. With addressable devices, the location and status of the connected device is monitored and logged, and displayed on the operator interface LCD and on remote system annunciators with each device having its own 40 character custom label for precise identification.
TrueAlarm Addressable Sensor Operation
Addressable initiating device communications include operation of TrueAlarm smoke and temperature sensors. Smoke sensors transmit an output value based on their smoke chamber condition and the CPU maintains a current value, peak value, and an average value for each sensor. Status is determined by comparing the current sensor value to its average value. Tracking this average value as a continuously shifting reference point filters out environmental factors that cause shifts in sensitivity.
TrueAlarm Addressable Sensor Reference
TrueAlarm Photo Sensor with Base
TrueAlarm Photo/Heat
Sensor in CO Base
Programmable sensitivity of each sensor can be selected at the control panel for different levels of smoke obscuration (shown directly in percent) or for specific heat detection levels. To evaluate whether the sensitivity should be revised, the peak value is stored in memory and can be easily read (or downloaded as a report) and compared to the alarm threshold directly in percent.
CO sensor bases combine an electrolytic CO sensing module with a TrueAlarm analog sensor to provide a single multiple sensing assembly using one system address. The CO sensor can be enabled/disabled, used in LED/Switch modes and custom control, and can be made public for communication across a fire alarm Network. (refer to data sheet S4098-0041 for details)
TrueAlarm heat sensors can be selected for fixed temperature detection, with or without rate-of-rise detection. Utility temperature sensing is also available, typically to provide freeze warnings or alert to HVAC system problems. Readings can selected as either Fahrenheit or Celsius. TrueSense Early Fire Detection. Multi-sensor 4098-9754 provides photoelectric and heat sensor data using a single 4100ES IDNet address. The panel evaluates smoke activity, heat activity, and their combination, to provide TrueSense early detection. For more details on this operation, refer to data sheet S4098-0024.
Diagnostics and Default Device Type
Sensor Status. TrueAlarm operation allows the control panel to automatically indicate when a sensor is almost dirty, dirty, and excessively dirty. The NFPA 72 requirement for a test of the sensitivity range of the sensors is fulfilled by the ability of TrueAlarm operation to maintain the sensitivity level of each sensor. CO Sensors track their 5 year active life status providing indicators to assist with service planning. Indicators occur at: 1 year, 6 months, and end of life.
Modular TrueAlarm sensors use the same base and different sensor types (smoke or heat sensor) and can be easily interchanged to meet specific location requirements. This allows intentional sensor substitution during building construction when conditions are temporarily dusty. Instead of covering smoke sensors (causing them to be disabled), heat sensors may be installed without reprogramming the control panel. The control panel will indicate an incorrect sensor type, but the heat sensor will operate at a default sensitivity to provide heat detection for building protection at that location.
IDNet Addressable Device Wiring Reference
IDNet 1+ Addressable Channel Capacity. The CPU bay system power supply (EPS+) provides an IDNet 1+ signaling line circuit (SLC) that supports up to 250 addressable monitor and control points intermixed on the same pair of wires. Additional 250 address IDNet 1+ circuit modules are available.
IDNet 1+ SLC Wiring Specifications
Maximum Distance from Control Panel per Device Load
0 to 125 4000 ft (1219 m); 50 ohms
126-250 2500 feet (762 m); 35 ohms
Total Wire Length Allowed With “T” Taps for Class B Wiring
Up to 12,500 ft (3.8 km); 0.60 µF
Maximum Capacitance Between IDNet+ Channels
1 µF
Wire Type and Connections Shielded or unshielded, twisted or untwisted wire*
Connections Terminal blocks for 18 to 12 AWG
Installation Instructions (see for more information) 579-1014
* Some applications may require shielded wiring. Review your system with your local Simplex product supplier.
4 S4100-0100 5/2013
IDNet Addressable Device and IDNAC Addressable Notification Appliance Control
Addressable notification appliance communications include operation of TrueAlert and TrueAlert ES Visible only (V/O, strobe), Audible only (A/O, horn), Audible/Visible (A/V, horn/strobe), and strobes of Speaker/Visible (S/V) notification appliances. (S/V appliances require separate speaker wiring.) IDNAC SLC addressable communications allow each horn and strobe to be individually controlled using a single two-wire circuit, confirms the wiring connections to the individual notification appliance’s electronic circuit, and confirms communications between each appliance and the fire alarm control panel. Addressable communications increases supervision integrity versus conventional notification systems by providing supervision beyond the circuit wiring to each individual appliance and by constantly verifying the ability of each appliance to communicate with the control panel.
Individual Appliance Status and Settings. Each addressable notification appliance is polled by the control panel to verify its ability to communicate. The fire alarm control panel monitors each addressable notification appliances for its status, condition, type of appliance, and configured appliance settings. A fault in any individual appliance automatically reports a trouble condition to the control panel.
TrueAlert ES Addressable Appliance Reference
A/O (horn) V/O (strobe) A/V (horn/strobe)
Location Information, Diagnostics, and Troubleshooting. Each addressable notification appliance has its own 40 character custom label to identify the location of the appliance and to aid in troubleshooting fault conditions. In conventional notification systems, conventional appliances are not capable of communicating with the control panel. Fault reporting on a conventional system is limited to the circuit wiring and the entire area (zone) covered by appliances on the notification appliance circuit (NAC) making it much more difficult and costly to locate and correct the source of a problem.
Tracking Appliance Details. The 4100ES with IDNAC SLCs provides intelligent addressable communications that allow detailed information associated with each addressable notification appliance to be reported to the fire alarm control panel for diagnostics and troubleshooting. Detailed information available includes; the appliance location, status, condition, type of appliance, and configured appliance settings.
New Installation, Retrofit, and Life-Cycle Cost Benefits. With each addressable appliance capable of being controlled separately on the same two-wire SLC, installation time and expense for both retrofit and new construction can be significantly reduced. When Class B wiring is used, wiring can be “T-tapped”, allowing more savings in distance, wire, conduit (size and utilization), and overall installation efficiency.
Panel Control Convenience. Applicable operation settings for each appliance can be programmed without having to replace appliances or remove them from the wall or ceiling. An appliance’s notification zone can be easily changed through programming without having to add additional circuits, conduit, and wiring. Audible and visible appliances for non-Fire Emergency Communications notification can be programmed to operate separately on the same pair of wires as the fire alarm notification appliances. The result is lower installation, retrofit, and overall life-cycle cost of ownership compared with traditional conventional notification systems.
IDNAC SLC Hardware Reference
EPS+ and EPS Power Supplies provide three, 3 A IDNAC SLCs for control and power to TrueAlert ES and TrueAlert addressable notification appliances. Both power supplies incorporate an efficient switching design that provides a regulated output of 29 VRMS, even during battery operation. With 29 VRMS minimum output at the panel, addressable notification SLCs can support wiring distances 2 to 3 times farther than available with conventional notification, or support more appliances per SLC, or work with smaller gauge wiring, or combinations of these benefits, all resulting in installation and maintenance savings with high assurance appliances that operate during normal system testing will operate during worst case alarm conditions.
Virtual NACs Provide Control Convenience. For control convenience, IDNAC notification appliances can be grouped into Virtual NACS for group control, grouping that can be made across SLCs, not defined by their wiring connection.
IDNAC SLC Appliance Wiring Reference
Recommended wire type UTP, unshielded twisted pair
IDNAC SLC Capacity
Up to 63 addresses and up to 75 unit loads (appliances are typically one unit load, devices such as Isolators may require more than one load, refer to individual device data sheet for specific information)
Maximum wire length allowed with “T-Taps” for Class B wiring, per SLC
10,000 ft (3048 m)
Maximum wire length per SLC to any appliance
4000 ft (1219 m)
Maximum wiring resistance between appliances
26 Ω
Wiring connections Terminal blocks for 18 to 12 AWG
Installation Instructions (see for more information) 579-1015
5 S4100-0100 5/2013
IDNAC SLC Control of TrueAlert and TrueAlert ES Addressable Notification
Master Controller and Motherboard: Mounts in Slot 2 of a two slot motherboard and provides
one Style 4 or Style 7, RUI+, isolated communications channel with earth fault detection
RUI+ isolated communications controls up to 31 devices per master controller at up to 2500 ft (762 m) for single run, or 10,000 ft (3048 m) total if wiring is Class B and T-tapped; if more distance is required, up to four total RUI channels are supported; add up to three 4100-1291 RUI expansion modules (4100-1291 provides unisolated RUI communications)
RUI remote equipment includes: MINIPLEX transponders, 4603-9101 LCD Annunciators, 4602-9101 Status Command Units (SCU), 4602-9102 Remote Command Units (RCU), 4602 Series LED Annunciator Panels, 4100 Series 24 I/O and LED/Switch modules
Open slot space on the left of the CPU motherboard is available for either another dual slot motherboard, or for one or two block modules (refer to diagram on page 2)
Slot 1 of the motherboard is primarily for the 4100-6078 Network Interface Board with media modules
EPS+ Power Supply: (see page 9 for more detail) Rating is 9 A total with “Special Application” appliances Outputs are power-limited, except for the battery charger Provides system power, battery charging, auxiliary
power, auxiliary relay, earth detection, on-board IDNet 1+ communications channel for 250 points, three on-board 3 A IDNAC SLCs, and provisions for either an optional City Connect Module or an optional Alarm Relay Module
IDNet 1+ SLC Output provides Class B or Class A communications for up to 250 addressable devices (as described on page 4)
DCAI (Dual Class A IDNAC Isolator) module creates two Class A outputs from one IDNAC SLC Class B Input; up to two can be connected to one IDNAC SLC, with up to 6 total per EPS; total Class A output loop current is limited to the 3 A rating of the IDNAC SLC
EPS+ Power Supply (Continued): Battery Charger is dual rate, temperature
compensated, and charges up to 50 Ah sealed lead-acid batteries mounted in the battery compartment (33 Ah for single bay cabinets); also is UL listed for charging up to 115 Ah batteries mounted in an external cabinet (see data sheet S2081-0012 for details)
Battery and Charger Monitoring includes battery charger status and low or depleted battery conditions; status information provided to the master controller includes analog values for: battery voltage, charger voltage and current, actual system voltage and current, and individual IDNAC SLC currents
Low Battery Cutout is selectable for each EPS+ (and EPS) power supply, Canadian models are shipped selected, other models are shipped unselected
2 A Programmable Output: Select for conventional non-synchronous NAC
operation to provide supervised reverse polarity for sounder base power, Suppression Release Peripheral (SRP) power, or other coded NAC operation requirements
Select for Auxiliary (AUX) operation for sounder base power, 4-wire detector power, or door holder; supervised AUX operation does not require an end-of-line relay to provide Power-Limited operation
EPS+ Power Supply Mounted Optional Modules (select one): City Connect Module (4100-6031, with disconnect
switches, or 4100-6032, without disconnect switches) can be selected for conventional dual circuit city connections
Alarm Relay Module (4100-6033) provides three Form C relays that are used for Alarm, Trouble, and Supervisory, rated 2 A resistive @ 32 VDC
Master Controller and Expansion Bay Selection
Model Model Type and Listing Description Current
4100-9311 120 VAC, 50/60 Hz Input UL 4100ES Master Controller Assembly with LCD and operator interface, 9 A EPS+ Enhanced Power Supply/battery charger with 250 point IDNet 1+ interface, 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and one output configurable for Auxiliary or simple NAC operation
Without IDNet devices: Supervisory = 217 mA Alarm = 480 mA With 200 IDNet devices and 20 device LEDs in alarm: Supervisory = 417 mA Alarm = 770 mA
4100-9312 English 120 VAC, 50/60 Hz Canadian
ULC 4100-9313 French
4100-9511 220-240 VAC, 50/60 Hz Input
UL
4100-9331 120 VAC, 50/60 Hz input UL 4100ES Master Controller Assembly, No Display, No Operator Interface, 9 A EPS+ Enhanced Power Supply/battery charger with 250 point IDNet 1+ interface, 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and one output configurable for Auxiliary or simple NAC operation
4100-9332 120 VAC, 50/60 Hz input, Canadian, English
ULC
4100-2300 Expansion Bay Assembly; order for each required expansion bay
4100-2303 Slot Module Stabilizer Bracket, used when expansion bays have style modules
(Continued on next page)
6 S4100-0100 5/2013
Master Controller Selection Information
CPU Bay Module Details
7 S4100-0100 5/2013
Communication Modules Model Description Size Supv. Alarm
4100-6078 For Master Controller; mounts in Slot 3 Modular Network Interface; each requires two media modules (below)
1 Slot 46 mA 46 mA 4100-6061 For Redundant Master Controller 1 Slot 46 mA 46 mA
4100-6056 Wired Media Module Select two media cards as required; mounts on 4100-6078 or 4100-6061
N.A. 55 mA 55 mA 4100-6057 Fiber Optic Media Module N.A. 25 mA 25 mA
4100-6047 Building Network Interface Card (BNIC), refer to data sheet S4100-0061 for details 2 Blocks 291 mA 291 mA
4100-6055 Network Access Dial-in Service Modem, mounts to 4100-6078 or 4100-6061 Network Interface Card, requires telephone line connection N.A. 60 mA 60 mA
4100-1291 Remote Unit Interface Module (RUI, unisolated); up to 3 maximum per control panel 1 Slot 85 mA 85 mA
4100-6031 Select one per EPS+ or EPS
City Circuit, with disconnect switches N.A. 20 mA 36 mA 4100-6032 City Circuit, w/o disconnect switches N.A. 20 mA 36 mA 4100-6033 Alarm Relay, 3 Form C relays, 2 A @ 32 VDC N.A. 15 mA 37 mA
4100-6046 Dual Port RS-232 standard interface (single block) 3 maximum RS-232 modules per panel
1 Block 60 mA 60 mA 4100-6038 Dual Port RS-232 with 2120 interface (slot module) 1 Slot 132 mA 132 mA
4100-6079 SafeLINC Internet Interface (refer to data sheet S4100-0062 for details) 2 Blocks 145 mA 145 mA 4190-6104 TrueInsight Remote Monitoring Module (refer to data sheet S4100-0063 for details) Side Mt. 62 mA 73 mA 4100-6101 Physical Bridge, Class B, includes 1 modem module and 2 wired modules 1 Slot 210 mA 210 mA 4100-6102 Physical Bridge, Class X, includes 2 modem and 2 wired modules 2 Slots 300 mA 300 mA 4100-6048 VESDA Aspiration System Interface 1 Slot 132 mA 132 mA
4100-6080 DACT, Point or Event Reporting; 1 shipped unless 4100-7908 is selected; 2 max. per system; includes 2, 2080-9047 cables, 14 ft (4.3 m) long, RJ45 plug and spade lugs Side Mt. 30 mA 40 mA
Additional Enhanced Power Supplies, Expansion and Remote Power Supplies, and Accessories Model Voltage/Listing Description Size Supv. Alarm
4100-5311 120 VAC UL & ULC
Additional Enhanced Power Supply (EPS+); 9 A Enhanced Power Supply/battery charger with 250 point IDNet 1+ interface, 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and auxiliary relay; 120 VAC model has selectable low battery cutout
4 Blocks Right Side
217 mA 480 mA
4100-5313 220-240 VAC UL with 200 IDNet devices and 20
device LEDs in alarm
4100-5325 120 VAC UL & ULC
Enhanced Power Supply (EPS); 9 A Enhanced Power Supply/battery charger with 3 Class B IDNAC SLCs, RUI+ isolated output communications interface, and auxiliary relay; 120 VAC model has selectable low battery cutout
4 Blocks Right Side
125 mA 220 mA 4100-5327 220-240 VAC UL
4100-6103
Dual Class A IDNAC Isolator (DCAI), converts a single Class B IDNAC SLC input to two Class A or two Class B SLC outputs; provides short circuit isolation between each Class A or B output circuit; connect up to two DCAI modules per IDNAC SLC input up to a maximum of 6 DCAI modules per EPS; each isolated output SLC used requires one IDNAC address; the total current remains controlled by the Class B input source SLC at 3 A maximum
1 Block 6.5 mA 6.5 mA
4100-5152 12 VDC Power Option, 2 A maximum 1 Block 1.5 A maximum 4100-0156 8 VDC Converter, required for multiple Physical Bridge Modules, 3 A maximum 1 Block included w/loads
4100-0636 Box Interconnection Harness Kit (non-audio); order one for each close-nippled cabinet 4100-0638 4100 Slot Module Additional 24 VDC Harness; need when 4100 Slot module requirements exceed 2 A from EPS
Module Selection is continued on next page
Subject Data Sheet Subject Data Sheet
Introducing the 4100ES S4100-0060 Fire Alarm Network Overview S4100-0055
4100ES Enclosures S4100-0037 Network Communications S4100-0056
4100ES Audio and Firefighter Phone Modules S4100-0034 Network Display Unit (NDU) S4100-0102
LED/Switch Modules & Printer S4100-0032 Addressable Device Compatibility S4090-0011
Remote Annunciators S4100-0038 4009 IDNAC Repeater S4009-0004
MINIPLEX Transponders S4100-0103 IDNet+ Module w/Quad Isolator S4100-0046
Building Network Interface (BNIC) S4100-0061 Remote Battery Charger S4081-0002
InfoAlarm Command Center S4100-0101 TFX Interface Module S4100-0042
Graphic I/O Modules S4100-0005 SafeLINC Internet Interface S4100-0062
TrueInsight Remote Service S4100-0063 4100ES Panels for Conventional Notification S4100-0031
Agent Release Applications S4100-0040 TrueAlarm Sensors S4098-0019
TrueAlert ES Audible Only Appliances S49AO-0001 TrueAlert ES Audible/Visible Appliances S49AV-0001
TrueAlert ES Visible Only Appliances S49VO-0001 TrueAlert ES Weatherproof Appliances, UL Listed S49WP-0001
TrueAlert Appliance/IDNAC SLC Isolator S4905-0001 TrueAlert ES Weatherproof Appliances, ULC Listed S49WP-0002
Module Selection Information
Additional 4100ES Data Sheet and Related Product Reference
8 S4100-0100 5/2013
Addressable Interface Modules (refer to location reference on pages 9 and 10) Model Description Supv. Alarm
4100-3108 IDNet 1+ Module, 250 point capacity with isolated output, 1 block
With 250 IDNet devices, and 20 device LEDs in alarm 292 mA 510 mA
Module without devices 92 mA 115 mA
Loading per IDNet device (no LEDs on) 0.8 mA 1 mA
4100-3107
Quad IDNet Isolator Module; converts a single connected SLC into four isolated outputs selectable as Class A or Class B, provides advanced diagnostics for use with retrofit wiring; dual horizontal block module; (see data sheet S4100-0046 for additional details) NOTE: This module is compatible with IDNet Remote Isolators
75 mA 115 mA
Relay Modules; Nonpower-limited (for mounting in expansion bay only, refer to location reference on pages 9 and 10) Model Description Resistive Ratings Inductive Ratings Size Supv. Alarm
4100-3202 4 DPDT w/feedback 10 A @ 250 VAC 10 A @ 250 VAC 2 Slots 15 mA 175 mA
4100-3204 4 DPDT w/feedback 2 A @ 30 VDC/VAC 1/2 A @ 30 VDC/120 VAC 1 Block 15 mA 60 mA
4100-3206 8 SPDT 3 A @ 30 VDC/120 VAC 1-1/2 A @ 30 VDC/120 VAC 1 Block 15 mA 190 mA
Current Calculation Notes: 1. To determine total supervisory current, add currents of modules in panel to base system value and all external loads powered
by panel power supplies. 2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel SLC and
NAC loads and all external loads powered from panel power supplies.
Miscellaneous Accessories Model Description
4100-1279 Single blank 2” display cover; 4100-2302 provides a single plate for a full bay
4100-9835 Termination and Address Label Kit (for module marking); provides additional labels for field installed modules
4100-6029 Smoke Management Application Guide; required for UUKL listing
4100-6034 Tamper Switch, one per cabinet assembly if required; monitors solid door for panels with solid door; monitors the internal retainer panel for panels with glass door (not the glass door); has a built-in addressable IDNet IAM
2081-9031 Series resistor for WSO, IDCs (N.O. water flow and tamper on same circuit, wires after water flow and before tamper) 470 Ω, 1 W, encapsulated, two 18 AWG leads (0.82 mm2 ), 2-1/2” L x 1-3/8” W x 1” H (64 mm x 35 mm x 25 mm)
Input Power
Enhanced Power Supplies, EPS/EPS+
120 VAC Models 4.6 A maximum @ 102 to 132 VAC, 50/60 Hz
220-240 VAC Models 2.3 A maximum @ 204 to 264 VAC, 50/60 Hz; separate taps for 220/230/240 VAC
Power Supply Output Ratings for EPS/EPS+
Total Power Supply Output Rating
Including module currents and auxiliary power outputs; 9 A total for “Special Application” appliances
Output switches to battery backup during mains AC failure or brownout conditions
IDNAC SLC Ratings 3 A, regulated 29 VRMS, 63 addresses, 75 unit loads
Auxiliary Power Tap 2 A maximum, 24 VDC nominal (19.5 to 31.1 VDC)
Compatible Special Application Appliances Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your Simplex product representative for compatible appliances
Battery Charger Ratings for EPS/EPS+ (sealed lead-acid batteries)
Battery capacity range UL listed for battery charging of 6.2 Ah up to 115 Ah (batteries larger than 50 Ah require a remote battery cabinet); ULC listed for charging up to 50 Ah batteries
Charger characteristics and performance
Temperature compensated, dual rate, recharges depleted batteries within 48 hours per UL Standard 864; to 70% capacity in 12 hours per ULC Standard S527
Environmental Operating Temperature 32° to 120°F (0° to 49° C)
Operating Humidity Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Additional Technical Reference
Description Document
ES Installation Instructions 574-848
ES Operating Instructions 579-197
IDNet 1+ Module Installation Instructions 579-1014
EPS/EPS+ Installation Instructions 579-1015
DCAI Module Installation Instructions 579-1029
Module Selection Information (Continued)
General Specifications
Slot 1 Slot 8Slot 7Slot 6Slot 5Slot 4Slot 3Slot 2
Expansion Bay Chassis
Block A
Block B
Block C
Block D
Block E
Block F
Block G
Block H
Size Definitions: 1 Block = 4” W x 5.65” H (102 mm x 144 mm); (often called
x 5 modules) 1 Slot = 2” W x 11.3” H (51 mm x 287 mm), typically a
motherboard with daughter card
PDI
Ma
ste
r C
on
tro
ller
Bo
ard
PDI
4x5 Module
Expansion PowerSupply
(XPS)
4x5 Module
I/O Wiring
I/O Wiring
I/O Wiring
41
00
Op
tion
41
00
Op
tion
41
00
Op
tion
Slot 1 Slot 2 Slot 3 Slot 4 Slot 5 Slot 6 Slot 7 Slot 8
(Block E)
(Block F)
(Blocks G & H)
*EPS+ power supply with IDNet 1+ module
Optional semi-flush trim kit
4100-6031 or 4100-6032 City Circuit or 4100-6033Alarm Relay mounts on bottom of EPS
4100-6030 Service Modem mounts only on master controller board
One 2" card: either 4100-6078 Network Module with media cards or 4100-6038 RS-232/2120 Interface
Cabinet height:(2 bay shown for reference)
1 Bay = 22"(559 mm)
2 Bay = 40"(1016 mm)
3 Bay = 56"(1427 mm)
Stud alignment markers, each side
Knockout screw/nail holes (for semi-flush mounting)
4" stud
6" stud
Master Controller Bay
Typical Expansion Bay(showing mixed module sizes)
Battery Compartment(50 Ah maximum)
Door can be hunghinged left or right
Wall board reference for semi-flush mounting, 6" stud
Two bay cabinet shown without dress panel
11-11/16"(296 mm)
6-29/32"(175 mm)
Door thickness4-3/4"(121 mm)
Exposed cabinet forsemi-flush mounting
1-3/8" (35 mm)minimum
Exposed door and cabinet for semi-
flush mounting 6-1/8" (156 mm)
minimum
24" (610 mm)
Door 4-3/4"(121 mm)
4100-6080 DACT mounting location
*Master controller with motherboard
Space for two 2" slot modules, or one 4" slot modules, or two single block modules, or one double block (vertical mount) module
Optional 4100-6049 TrueInsight Module mounting location
NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection shall be made
to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.
9 S4100-0100 5/2013
Expansion Bay Module Loading Reference
Mounting and CPU Bay Module Reference (* indicates supplied modules)
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4100-0100 5/2013
www.simplexgrinnell.com © 2013 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. VESDA is a trademark of Xtralis Pty Ltd. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (NFPA). ASHRAE and BACnet are trademarks of ASHRAE, American Society of Heating, Refrigeration, and Air Conditioning Engineers.