Tata Udara Hitungan

download Tata Udara Hitungan

of 14

description

-

Transcript of Tata Udara Hitungan

  • Tata Udara SATUAN (UNIT)TR = Ton Refrigeration.

    1 TR = 200 BTU / minute = 12000 BTU/h = 3.517 kJ/s = 3.517 kilowatts

    1 ton of refrigeration = 12,000Btu/hour. 100 Watts = 341 Btu/hour Conversion factor = Watts x 3.41 = Btu/hour. Therefore 12,000 Btu/hr = 12,000 3.41 = 3.5 kW

    1 HP =0.7457 kW

    *

  • Jenis bangunan: Kampus dengan bentuk dan ukuran seperti berikut:*

  • Menggunakan lampu sebanyak 6 buah, masing-masing 200Watt.Okupansi = tingkat penghunian bangunan Okupansi = (LBruto ) / (Lper orang) Lper orang = Luas per orang = 15-20 m2 /orang Misal diambil = Lper orang = 15 m2 /orang LBruto = Luas lantai = 30 m x 15 m = 450 m2 Okupansi = (LBruto ) / (Lper orang) = 450/15 = 30*

  • Beban Pendingin (BP): BP = BSB + BSO +BLO + BSL + CFM1 + CFM2BSB = Beban Sensibel BangunanBSO = Beban Sensibel OrangBLO = Beban Laten OrangBSL = Beban Sensibel LampuCFM1 = Beban Infiltrasi udaraCFM2 = Beban Ventilasi udara*

  • Beban Sensibel Bangunan (BSB = Lbidang x Beban kalorBeban kalor dihitung dengan bantuan Tabel 6.3:

    *

  • Beban Sensibel Bangunan (BSB = Lbidang x Beban kalorBeban kalor kaca utara = 800 (BTU/jam/m2) x (luas kaca utara) = 800 (BTU/jam/m2) x (2 m x 8 m) = 12800 BTU/jam) Beban kalor kaca selatan = 400 (BTU/jam/m2) x (luas kaca utara) = 400 (BTU/jam/m2) x (4 m x 6 m) = 9600 BTU/jam)Beban kalor kaca barat = 0 (BTU/jam/m2) Beban kalor kaca timur = 0 (BTU/jam/m2)

    *

  • t0 = temperatur ruangan luar t1 = temperatur ruangan dalam Di Indonesia (t0 t1) = 5oC (pendekatan)Beban kalor dinding arah utara = 2,15(t0 t1) (BTU/jam/m2)x(luas dinding arah utara) = 2,15 x (5) (BTU/jam/m2) x (10 m x 30 m) = 3225 BTU/jamBeban kalor dinding arah selatan = 2,15(t0 t1)(BTU/jam/m2)x(luas dinding arah selatan) = 2,15 x (5) (BTU/jam/m2) x (10 m x 30 m) = 3225 BTU/jam

    *

  • Beban kalor dinding arah timur = 2,15(t0 t1)(BTU/jam/m2)x(luas dinding arah timur) = 2,15 x (5) (BTU/jam/m2) x (10 m x 15 m) = 1612,5 BTU/jamBeban kalor dinding arah barat = 2,16(t0 t1)(BTU/jam/m2)x(luas dinding arah barat) = 2,16 x (5) (BTU/jam/m2) x (10 m x 15 m) = 1620 BTU/jam

    *

  • BSB total = Beban sensibel bangunan total = (Beban kalor kaca utara) + (Beban kalor kaca selatan) + (Beban kalor kaca barat) + (Beban kalor kaca timur) + (Beban kalor dinding arah utara) + (Beban kalor dinding arah selatan) + ( Beban kalor dinding arah timur) + (Beban kalor dinding arah barat)

    BSB total = (12800+ 9600+0+0+3225+3225 +1612,5 +1620) BTU/jam = 32082,5 BTU/jam*

  • Okupansi = tingkat penghunian bangunan Okupansi = (LBruto ) / (Lper orang) Lper orang = Luas per orang = 15-20 m2 /orang Misal diambil = Lper orang = 15 m2 /orang LBruto = Luas lantai = 30 m x 15 m = 450 m2 Okupansi = (LBruto ) / (Lper orang) = 450/15 = 30 Beban Sensibel Orang (BSO): BSO = (okupansi).200 BTU/jam

    *

  • BSO = (okupansi).200 BTU/jam BSO = (30).(200) = 6000 BTU/jamBeban Laten Orang (BLO): BLO = (okupansi).250 BTU/jam BLO = (okupansi).250 BTU/jam BLO = (30).(250) = 7500 BTU/jam Menggunakan lampu sebanyak 6 buah, masing-masing 200Watt. Beban Sensibel Lampu (BSL): BSL = (Jumlah Watt lampu)(1,25).(3,4) BTU/jam BSL = (6 x 200)(1,25).(3,4) BTU/jam BSL = 5100 BTU/jam *

  • Beban Infiltrasi Udara = CFM1 CFM1 = (Volume ruangan)(jumlah pertukaran udara /jam)(35,31) / 60 BTU/jam Jumlah pertukaran udara/jam, dengan menggunakan Tabel 6.1, diambil 6 (misal kampus didekati dengan tipe ruang Hall Pertemuan) CFM1 = (30m x 15m x 10m)(6)(35,31) / 60 BTU/jam CFM1 = 15889,5 BTU/jamBeban Ventilasi Udara = CFM2 CFM2 = [(t0 t1)(1,08) + (RH0 RH1).(0,67)] BTU/jam CFM2 = [(5)(1,08) + (0,9 0,6).(0,67)] BTU/jam CFM2 = 5,601 BTU/jam*

  • *

  • Beban Pendingin (BP): BP = BSB + BSO +BLO + BSL + CFM1 + CFM2 BP = (32082,5 + 6000 + 7500 + 5100 + 15889,5 + 5,601) BTU/jam BP = 66577,601 BTU/jam

    Kapasitas Tata Udara = (BP/12.000) TR Kapasitas Tata Udara = (65777,601 /12.000) TR = 5,481 TR = 5,481 x 3,517 kilowatts = 19,512 kW = 19,512/ 0.7457 = 26,167 HP*