PT PLN (PERSERO) P3B JAWA BALI
Standard Addressing Teleinformation
Plan P3B Jawa Bali untuk Protokol IEC 870-5-101 dan 870-5-104
PT PLN (PERSERO) P3B JAWA BALI
KRUKUT LIMO, DEPOK
JAKARTA SELATAN 16512
-
Daftar Isi Daftar Isi .............................................................................................................1
Prakata ...............................................................................................................2
1. Ruang lingkup..............................................................................................3
2. Tujuan..........................................................................................................3
3. Acuan normatif.............................................................................................3
4. Konfigurasi IEC 870-5-101 dan IEC 870-5-104 ...........................................3
5. Standar Addressing Remote Station............................................................4
6. Standar Addressing Teleinformasi...............................................................5
Lampiran A: Contoh Standar Addressing..........................................................19
1 dari 71
-
Prakata Standar addressing teleinformation plan ini memberikan acuan untuk penetapan address RTU dan teleinformasi dengan menggunakan protokol IEC 870-5-101 dan IEC 870-5-104 untuk mengakomodir SPLN S5.001 2008 tentang teleinformasi data untuk operasi jaringan dan SPLN S5.001 2008 tentang teleinformasi data untuk pemeliharaan instalasi sistem Standar ini mencakup konfigurasi protokol IEC 870-5-101 dan IEC 870-5-104, standar addressing Remote Station dan Standar addressing teleinformasi yang digunakan dalam sistem SCADA untuk operasi maupun pemeliharaan. Standar ini dapat menjadi acuan dalam implementasi Sistem Otomasi Gardu Induk (SOGI) di lingkungan PT PLN (Persero) P3B Jawa Bali.
2 dari 71
-
Standard Addressing Teleinformation Plan P3B Jawa Bali untuk Protokol IEC 870-5-101 dan 870-5-104
1. Ruang lingkup
Standar ini dimaksudkan untuk menetapkan standar addressing teleinformation plan PLN P3B Jawa Bali. Standar ini, berlaku untuk sistem SCADA: a. Inter Regional Control Center, disingkat IRCC; b. Regional Control Center, disingkat RCC;
2. Tujuan Standar ini memberikan pedoman addressing teleinformasi untuk implementasi SOGI. Standar ini diimplementasikan pada Gardu Induk baru, pengembangan bay baru dan rehabilitasi Gardu Induk.
3. Acuan normatif Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalam pembuatan standar addressing teleinformation plan untuk protokol IEC 870-5-101 dan IEC 870-5-104. Pada saat publikasi standar ini, dokumen normatif yang tersebut dibawah ini masih berlaku. Semua dokumen normatif ini, mungkin untuk dilakukan revisi sehingga pihak-pihak yang menggunakan standar ini diharapkan untuk mencari kemungkinan menggunakan edisi terbaru dokumen normatif yang bersangkutan. a. Edaran Direksi PT PLN (PERSERO) nomor 00546/140/DITTND/2004 tanggal 23
Juni 2004 tentang Investasi Sistem SCADA; b. Edaran Direksi PT PLN (PERSERO) nomor 01020/140/DITTND/2004 tanggal 17
Desember 2004 tentang Acuan Di Dalam Proses Investasi Pembangunan Sistem SCADA;
c. Edaran Direksi PT PLN (PERSERO) no. 004.E/DIR/2006 tentang Pedoman Proses Pencapaian Sasaran melalui Penetepan Enterprise Risk Manajemen di PT PLN (PERSERO);
d. SPLN S5.001 2008 tentang Teleinformasi Data untuk Operasi Jaringan Tenaga Listrik
e. SPLN S5.001 2008 tentang Teleinformasi Data untuk Pemeliharaan Instalasi Sistem Tenaga Listrik
4. Istilah dan Definisi
4.1 ASDU Application Spesific Data Unit. Paket data pada application layer protokol IEC 870-5-101 dan IEC 870-5-104
4.2 Control center Pusat kendali pengoperasian sistem tenaga listrik dimana master station ditempatkan.
4.3 Inter regional control center (IRCC) Pusat kendali yang terhubung dengan beberapa regional control center.
3 dari 71
-
4.4 Intelligent electronic device (IED) Peralatan elektronik berbasis mikroprosesor yang memiliki fungsi tertentu untuk melakukan telekontrol, telemetering, telesignal, proteksi, dan meter energi.
4.5 Regional control center (RCC) Pusat kendali jaringan transmisi tegangan tinggi.
4.6 Remote station Stasiun yang dipantau, atau diperintah dan dipantau oleh master station, yang terdiri dari gateway, IED, local HMI, RTU, dan meter energi.
4.7 Remote terminal unit (RTU) Peralatan yang dipantau, atau diperintah dan dipantau oleh master station. [IEV 371-06-04]
4.8 Supervisory control and data acquisition (SCADA) Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara geografis. [ IEC 60870-1-3 ]
4.9 Telecontrol Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan teknik telekomunikasi. [IEV 371-01-01] CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering/pengukuran, proteksi dan fasilitas tripping, tidak menggunakan pesan suara.
4.10 Telesignal Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakan teknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-04]
4.11 Telemetering Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV 371-01-03]
5. Penentuan CAASDU dan IO Address IEC 870-5-101 dan IEC 870-5-104 Untuk kompatibilitas addressing antara IEC 870-5-101 dan IEC 870-5-104, maka digunakan pola sebagai berikut: Panjang Common Address of ASDU = 2 byte Panjang IO Address = 3 byte
6. Standar Addressing Remote Station Untuk menghindari overlapping addressing remote station di sistem Jawa Bali, maka alokasi addressing remote station di sistem Jawa Bali diatur sebagai berikut:
CAASDU RTU 500kV = 0 9999 CAASDU RTU RJKB = 10000 19999 CAASDU RTU RJBR = 20000 29999
4 dari 71
-
CAASDU RTU RJTD = 30000 39999 CAASDU RTU RJTB = 40000 49999 CAASDU RTU SRB = 50000 59999
7. Standar Addressing Teleinformasi IO Address untuk addressing teleinformasi mempunyai pola sebagai berikut:
a b / c / d e
dimana variabel:
a adalah tipe bay b adalah tipe teleinformasi c adalah nomor urut teleinformasi d adalah nomor urut bay e adalah nomor urut elemen
7.1 Tipe Bay (Nilai variabel a) Mengacu pada SPLN S5.001:2008 dan SPLN S5.002:2008 Lampiran-B, opsi untuk tipe bay adalah sebagai berikut:
Nilai 'a' Bay 500 kV 1 Remote Station 2 Gardu Induk 3 Busbar 4 Bus Coupler 5 Bus Section 6 OHL Feeder 7 IBT 500/150 Sisi 500 8 IBT 500/150 Sisi 150 9 Reactor 10 Diameter 11 Gen Transf 12 Generator 13 Blok
Nilai 'a' Bay 150 kV
1 Remote Station 2 Gardu Induk 3 Busbar 4 Bus Coupler 5 Bus Section 6 OHL Feeder 7 Cable Feeder 8 IBT 500/150 Sisi 150 9 Tranf 150/70 Sisi 150
5 dari 71
-
10 Tranf 150/70 Sisi 70 11 Distribution Transf 12 Capacitor 13 Reactor 14 Diameter 15 Gen Transf 16 Generator 17 Blok
7.2 Tipe Teleinformasi (Nilai variabel b) Opsi untuk tipe teleinformasi adalah sebagai berikut:
Nilai 'b' Tipe Teleinformasi
0 Tap Changer ( TC ) 1 Tele Measurement ( TM ) 2 Remote Control Digital ( RCD ) 3 Remote Control Analog ( RCA ) 4 Tele Signal Double ( TSD ) 5 Tele Signal Single ( TSS ) 6 Accumulator ( ACC )
7.3 Nomor urut teleinformasi (Nilai variabel c) SPLN S5.001:2008 dan SPLN S5.002:2008 Lampiran B, opsi untuk nomer urut teleinformasi adalah sebagai berikut: Nomor urut Teleinformasi untuk RTU 500 kV
TAP CHANGER ( TC ) Nilai c MNEMO DESIGNATION
1 TPI TAP POSITION INDICATION
TELE MEASUREMENT ( TM ) Nilai c MNEMO DESIGNATION
1 F FREKUENSI
2 V TEGANGAN
3 I ARUS
4 P DAYA AKTIF
5 Q DAYA REAKTIF
6 PF POWER FACTOR
7 CCB COUNTER OF CIRCUIT BREAKER
8 TEMP TEMPERATURE (OIL, PRIMARY-SECONDARY-TERTIARY WINDING)
9 PRES PRESSURE
10 POAQ REAL POWER SETTING
11 PRAQ MAX POWER VARIATION SETTING
12 AMF AMPERES FAULT ( PER PHASE )
13 KWH KILOWATT HOUR
6 dari 71
-
14 KVARH KILOVAR HOUR
15 RH RELATIVE HUMIDITY
16 CNTA COUNTER ARESTER
17 CTPI COUNTER TAP POSITION INDICATION
REMOTE CONTROL DIGITAL ( RCD ) Nilai c MNEMO DESIGNATION
1 DCBC DUMMY CIRCUIT BREAKER CLOSED/OPENED
2 CB CIRCUIT BREAKER CLOSED/OPENED
3 BI BUS ISOLATOR SWITCH CLOSED/OPENED
4 LI LINE ISOLATOR SWITCH CLOSED/OPENED
5 LR LOCAL REMOTE
6 LRT LOCAL/REMOTE SWITCH FOR TAPCHANGER
7 TCC TAP CHANGER AUTO/MANUAL
8 TC TAP CHANGER RAISE/LOWER
9 CSO CHECK SYNCHRONIZING OVERRIDE
10 ES EARTH SWITCH CLOSED/OPENED
11 RACK CIRCUIT BREAKER RACKIN/RACKOUT
12 TFAM TRANSFORMER FAN AUTO/MANUAL
13 SAM SYNCHRONIZATION AUTO/MANUAL
14 RMT RESET MASTER TRIP
15 GUC GENERATOR UNIT RUN/STOP
16 LFR LOAD FREQ REQUEST ON/OFF
17 CD CONTROL DISABLE SWITCH
18 CAM CAPASITOR AUTO/MANUAL
REMOTE CONTROL ANALOG ( RCA ) Nilai c MNEMO DESIGNATION POOP REAL POWER SET POINT
PROP MAX POWER VARIATION SET POINT
N LOAD FREQ CONTROL N_LEVEL
TELESIGNAL DOUBLE ( TSD ) Nilai c MNEMO DESIGNATION
1 DCBC DUMMY BREAKER CLOSED/OPENED
2 CB CIRCUIT BREAKER CLOSED/OPENED
3 BI BUS ISOLATOR SWITCH CLOSED/OPENED
4 LI LINE ISOLATOR SWITCH CLOSED/OPENED
5 LR LOCAL REMOTE
6 LRT LOCAL/REMOTE SWITCH FOR TAPCHANGER
7 TCC TAP CHANGER AUTO/MANUAL
8 TC TAP CHANGER RAISE/LOWER
9 CSO CHECK SYNCHRONIZING OVERRIDE
10 ES EARTH SWITCH CLOSED/OPENED **)
7 dari 71
-
11 RACK CIRCUIT BREAKER RACKIN/RACKOUT
12 TFAM TRANSFORMER FAN AUTO/MANUAL
13 SAM SYNCHRONIZATION AUTO/MANUAL
14 RMT RESET MASTER TRIP
15 GUC GENERATOR UNIT RUN/STOP
16 LFR LOAD FREQ REQUEST ON/OFF
17 CD CONTROL DISABLE SWITCH
18 CAM CAPASITOR AUTO/MANUAL
19 LFC LOAD FREQ CONTROL ON/OFF SWITCH
20 LFA LOAD FREQ AVAILABLE/NOT AVAILABLE
21 PSO POWER STATION OPERATED
TELESIGNAL SINGLE (TSS)
Nilai c MNEMO OP MNEMO
HAR DESIGNATION
1 VACF VAC FAILURE
2 220F 220 VAC FAILURE
3 380F 380 VAC FAILURE
4 VDCF VDC FAILURE
5 220RF 220VDC RECTIFIER FAILURE
6 220SF 220VDC SUPPLY FAILURE
7 110RF 110VDC RECTIFIER FAILURE
8 110SF 110VDC SUPPLY FAILURE
9 24RF 24VDC RECTIFIER FAILURE
10 24SF 24VDC SUPPLY FAILURE
11 48RF 48VDC RECTIFIER FAILURE
12 48SF 48VDC SUPPLY FAILURE
13 DCG DC GROUND
14 PHA PERIPHERAL ALARM
15 DFRF DISTURBANCE FAULT RECORDER FAULTY
16 ERF EVENT RECORDER FAILURE
17 FDC FAULT DATA CAPTURED
18 GRE GENSET READY
19 AIRCF AIR CONDITIONING FAILURE
20 AR CIRCUIT BREAKER AUTO RECLOSE
21 ARO AUTO RECLOSE OFF
22 BF BAY FAULT
23 VTF VOLTAGE TRANSFORMER FAILURE
24 DSDF DISCONNECTING SWITCH DRIVING FAULT
25 DCF DC SUPPLY FAILURE
26 BRF BREAKER FAULT
27 LPA LOW PRESSURE ALARM
28 LPB LOW PRESSURE BLOCK
29 LPT LOW PRESSURE TRIP
30 PD POLE DISCREPANCY
31 CBDF CIRCUIT BREAKER DRIVE FAILURE
32 TCS1 TRIP COIL SUPERVISORY 1
8 dari 71
-
33 TCS2 TRIP COIL SUPERVISORY 2
34 CBM CIRCUIT BREAKER MAINTENANCE
35 RTUA REMOTE STATION ALARM
36 IR INTERNAL REMOTE STATION
37 CTE CABINET TEMPERATUR
38 COM COMMUNICATION FAULTY
39 CF CARRIER FAULTY
40 FOTF FO TERMINAL FAULTY
41 PLCF PLC TERMINAL FAULTY
42 RADF RADIO LINK FAULTY
43 PBXF PABX FAULTY
44 DOOR DOOR ACTIVATED
45 SIA STATION INTRUDER ALARM
46 RSTA RESET ALARM
47 CSP CHECK SYNCHRONIZING IN PROGRESS
48 OCPA OIL CABLE PRESSURE ALARM
49 PWF PILOT WIRE FAILURE
50 RTN RELAY TEGANGAN NOL
51 SYNF SYNCHRONIZING FAILURE
52 FPO FIRE PROTECTION OPERATED
53 TEA TEMPERATURE ALARM
54 WTHVA HV WINDING TEMPERATUR ALARM
55 WTLVA LV WINDING TEMPERATUR ALARM
56 OTA OIL TEMPERATURE ALARM
57 TET TEMPERATURE TRIP
58 WTHVT HV WINDING TEMPERATUR TRIP
59 WTLVT LV WINDING TEMPERATUR TRIP
60 OTT OIL TEMPERATUR TRIP
61 TRA TRANSFORMER ALARM
62 TBUCA TRANSFORMER BUCHOLZ ALARM
63 TSPA TRANSFORMER SUDDEN PRESSURE ALARM
64 TOLA TRANSFORMER OIL LEVEL ALARM
65 TOOS TRANSFORMER OUT OF STEP ALARM
66 TRT TRANSFORMER TRIP
67 TBUC2 TRANSFORMER BUCHOLZ TRIP
68 TSPT TRANSFORMER SUDDEN PRESSURE TRIP
69 TFDP TRANSFORMER FIRE DETECTION & PROTECTION
70 TJANT TRANSFORMER JANSEN TRIP
71 RCFF REAKTOR COOLING FAN FAILURE
72 RF REACTOR FAILURE
73 RA REAKTOR ALARM
74 RBUCA REAKTOR BUCHOLZ ALARM
75 RSPA REAKTOR SUDDEN PRESSURE ALARM
76 ROLA REAKTOR OIL LEVEL ALARM
77 RT REAKTOR TRIP
78 RBUC2 REAKTOR BUCHOLZ TRIP
79 RSPT REAKTOR SUDDEN PRESSURE TRIP
80 RFDP REAKTOR FIRE DETECTION & PROTECTION
9 dari 71
-
81 TAF TRANFORMER AVR FAILURE
82 TCA TAP CHANGER ALARM
83 TCT TAP CHANGER TRIP
84 TPIF TAP POSITION INDICATION FAILURE
85 TCH TAP CHANGER HIGH LIMIT
86 TCL TAP CHANGER LOW LIMIT
87 TCFF TRANSFORMER COOLING FAN FAILURE
88 TCPF TRANSFORMER COOLING PUMP FAILURE
89 VS VOLTAGE STATUS
90 FRA FIRE ALARM
91 FRSF FIRE ALARM SYSTEM FAILURE
92 POT PROTECTION ON TEST
93 GOV FREE ACTING GOVERNOR ACTIVE
94 AVR AUTOMATIC VOLTAGE REGULATOR ON/OFF
95 AQR AUTOMATIC POWER FACTOR ACTIVE
96 LFF LOAD FREQ CONTROL UNIT FAILURE
97 UT UNIT TRIP
98 GTT GENERATOR TRANSFORMER TRIP
99 LOWCT LOW OIL PRESSURE CABLE TRIP
100 PRDT PRESSURE RELAY DEVICE TRIP
101 MTO MASTER TRIP OPERATE
102 UFR UNDER FREQUENCY RELAY OPERATE
103 UVR UNDER VOLTAGE RELAY OPERATE
104 OVR OVER VOLTAGE RELAY OPERATE
105 PTF PROTECTION FAULTY
106 OCRF OVER CURRENT RELAY FAILURE
107 OVRF OVER VOLTAGE RELAY FAILURE
108 UVRF UNDER VOLTAGE RELAY FAILURE
109 GFRF GROUND FAULT RELAY FAILURE
110 DZAF DISTANCE RELAY (a) FAILURE
111 DZBF DISTANCE RELAY (b) FAILURE
112 DEFAF DIRECTIONAL EARTH FAULT (a) FAILURE
113 DEFBF DIRECTIONAL EARTH FAULT (b) FAILURE
114 CDAF CURRENT DIFFERENTIAL RELAY (a) FAILURE
115 CDBF CURRENT DIFFERENTIAL RELAY (b) FAILURE
116 TPAF TELEPROTECTION (a) FAILURE
117 TPBF TELEPROTECTION (b) FAILURE
118 DIFF DIFFERENTIAL FAILURE
119 REFF RESTRICTED EARTH FAULT FAILURE
120 BPAF BUSBAR PROTECTION (a) FAILURE
121 BPBF BUSBAR PROTECTION (b) FAILURE
122 CCPF CIRCULATING CURRENT PROTECTION FAILURE
123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE
124 SZPF SHORT ZONE PROTECTION FAILURE
125 TTR TELEPROTECTION TRIP RECEIVE
126 DZARX DISTANCE (a) RELAY RECEIVE
127 DZBRX DISTANCE (b) RELAY RECEIVE
128 DEARX DIRECTIONAL EARTH FAULT (a) RELAY RECEIVE
10 dari 71
-
129 DEBRX DIRECTIONAL EARTH FAULT (b) RELAY RECEIVE
130 DTARX DIRECT TRANSFER TRIP (a) RECEIVE
131 DTBRX DIRECT TRANSFER TRIP (b) RECEIVE
132 TTT TELEPROTECTION TRIP TRANSMIT
133 DZATX DISTANCE (a) RELAY TRANSMIT
134 DZBTX DISTANCE (b) RELAY TRANSMIT
135 DEATX DIRECTIONAL EARTH FAULT (a) RELAY TRANSMIT
136 DEBTX DIRECTIONAL EARTH FAULT (b) RELAY TRANSMIT
137 DTATX DIRECT TRANSFER TRIP (a) TRANSMIT
138 DTBTX DIRECT TRANSFER TRIP (b) TRANSMIT
139 P1BP BUSBAR PROTECTION
140 BPA BUSBAR PROTECTION (a)
141 BPB BUSBAR PROTECTION (b)
142 P1CD CURRENT DEFFERENTIAL
143 CDAR CURRENT DIFFERENTIAL (a) PHASE R
144 CDAS CURRENT DIFFERENTIAL (a) PHASE S
145 CDAT CURRENT DIFFERENTIAL (a) PHASE T
146 CDBR CURRENT DIFFERENTIAL (b) PHASE R
147 CDBS CURRENT DIFFERENTIAL (b) PHASE S
148 CDBT CURRENT DIFFERENTIAL (b) PHASE T
149 P1DEF DIRECTIONAL EARTH FAULT
150 DEFAR DIRECTIONAL EARTH FAULT (a) PHASE R
151 DEFAS DIRECTIONAL EARTH FAULT (a) PHASE S
152 DEFAT DIRECTIONAL EARTH FAULT (a) PHASE T
153 DEFBR DIRECTIONAL EARTH FAULT (b) PHASE R
154 DEFBS DIRECTIONAL EARTH FAULT (b) PHASE S
155 DEFBT DIRECTIONAL EARTH FAULT (b) PHASE T
156 P1DIF DIFFERENTIAL
157 P1REF RESTRICTED EARTH FAULT
158 P1Z1 DISTANCE PROTECTION ZONE 1
159 DZ1AR DISTANCE (a) PHASE R ZONE 1
160 DZ1AS DISTANCE (a) PHASE S ZONE 1
161 DZ1AT DISTANCE (a) PHASE T ZONE 1
162 DZ1BR DISTANCE (b) PHASE R ZONE 1
163 DZ1BS DISTANCE (b) PHASE S ZONE 1
164 DZ1BT DISTANCE (b) PHASE T ZONE 1
165 P1Z2 DISTANCE PROTECTION ZONE 2
166 DZ2AR DISTANCE (a) PHASE R ZONE 2
167 DZ2AS DISTANCE (a) PHASE S ZONE 2
168 DZ2AT DISTANCE (a) PHASE T ZONE 2
169 DZ2BR DISTANCE (b) PHASE R ZONE 2
170 DZ2BS DISTANCE (b) PHASE S ZONE 2
171 DZ2BT DISTANCE (b) PHASE T ZONE 2
172 P1Z3 DISTANCE PROTECTION ZONE 3
173 DZ3AR DISTANCE (a) PHASE R ZONE 3
174 DZ3AS DISTANCE (a) PHASE S ZONE 3
175 DZ3AT DISTANCE (a) PHASE T ZONE 3
176 DZ3BR DISTANCE (b) PHASE R ZONE 3
11 dari 71
-
177 DZ3BS DISTANCE (b) PHASE S ZONE 3
178 DZ3BT DISTANCE (b) PHASE T ZONE 3
179 P2GFR GROUND FAULT RELAY
180 P2OCR OVER CURRENT RELAY
181 P3DTT DIRECT TRANSFER TRIP
182 CCPA CIRCULATING CURRENT PROTECTION (a) OPERATE
183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE
184 SZPA SHORT ZONE PROTECTION (a) OPERATE
185 CCPB CIRCULATING CURRENT PROTECTION (b) OPERATE
186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE
187 SZPB SHORT ZONE PROTECTION (b) OPERATE
188 CBTR CB TRIP
189 PHR TRIP PHASE R
190 PHS TRIP PHASE S
191 PHT TRIP PHASE T
192 HFD HOMOPOLAR FAULT DETECTOR
193 SIB SOFTWARE INTERLOCKING BYPASS
194 IEDF IED FAULTY
195 SOTF SWITCH ON TO FAULT
196 PD PARTIAL DISCHARGE (PRIMARY-SECONDARY-TERSIER)
197 OFO ONLINE FILTERING OLTC
198 DGA DISSOLVE GAS ANALYSIS
199 NVD NEUTRAL VOLTAGE DISPLACEMENT (TERSIER)
Nomor Teleinformasi untuk RTU 150/70 kV:
TAP CHANGER ( TC ) Nilai c MNEMO DESIGNATION
1 TPI TAP POSITION INDICATION
TELE MEASUREMENT ( TM )
Nilai c MNEMO DESIGNATION 1 F FREKUENSI
2 V TEGANGAN
3 I ARUS
4 P DAYA AKTIF
5 Q DAYA REAKTIF
6 PF POWER FACTOR
7 CCB COUNTER OF CIRCUIT BREAKER
8 TEMP TEMPERATURE (OIL, PRIMARY-SECONDARY WINDING)
9 PRES PRESSURE
10 POAQ REAL POWER SETTING
11 PRAQ MAX POWER VARIATION SETTING
12 AMF AMPERES FAULT ( PER PHASE )
13 KWH KILOWATT HOUR
14 KVARH KILOVAR HOUR
12 dari 71
-
15 RH RELATIVE HUMIDITY
16 CNTA COUNTER ARESTER
17 CTPI COUNTER TAP POSITION INDICATION
REMOTE CONTROL DIGITAL ( RCD )
Nilai c MNEMO DESIGNATION 1 DCBC DUMMY CIRCUIT BREAKER CLOSED/OPENED
2 CB CIRCUIT BREAKER CLOSED/OPENED
3 BI BUS ISOLATOR SWITCH CLOSED/OPENED
4 LI LINE ISOLATOR SWITCH CLOSED/OPENED
5 LR LOCAL REMOTE
6 LRT LOCAL/REMOTE SWITCH FOR TAPCHANGER
7 TCC TAP CHANGER AUTO/MANUAL
8 TC TAP CHANGER RAISE/LOWER
9 CSO CHECK SYNCHRONIZING OVERRIDE
10 ES EARTH SWITCH CLOSED/OPENED
11 RACK CIRCUIT BREAKER RACKIN/RACKOUT
12 TFAM TRANSFORMER FAN AUTO/MANUAL
13 SAM SYNCHRONIZATION AUTO/MANUAL
14 RMT RESET MASTER TRIP
15 GUC GENERATOR UNIT RUN/STOP
16 LFR LOAD FREQ REQUEST ON/OFF
17 CD CONTROL DISABLE SWITCH
18 CAM CAPASITOR AUTO/MANUAL
TELESIGNAL DOUBLE ( TSD )
Nilai c MNEMO DESIGNATION 1 DCBC DUMMY BREAKER CLOSED/OPENED
2 CB CIRCUIT BREAKER CLOSED/OPENED
3 BI BUS ISOLATOR SWITCH CLOSED/OPENED
4 LI LINE ISOLATOR SWITCH CLOSED/OPENED
5 LR LOCAL REMOTE
6 LRT LOCAL/REMOTE SWITCH FOR TAPCHANGER
7 TCC TAP CHANGER AUTO/MANUAL
8 TC TAP CHANGER RAISE/LOWER
9 CSO CHECK SYNCHRONIZING OVERRIDE
10 ES EARTH SWITCH CLOSED/OPENED **)
11 RACK CIRCUIT BREAKER RACKIN/RACKOUT
12 TFAM TRANSFORMER FAN AUTO/MANUAL
13 SAM SYNCHRONIZATION AUTO/MANUAL
14 RMT RESET MASTER TRIP
15 GUC GENERATOR UNIT RUN/STOP
16 LFR LOAD FREQ REQUEST ON/OFF
17 CD CONTROL DISABLE SWITCH
18 CAM CAPASITOR AUTO/MANUAL
19 LFC LOAD FREQ CONTROL ON/OFF SWITCH
20 LFA LOAD FREQ AVAILABLE/NOT AVAILABLE
21 PSO POWER STATION OPERATED
13 dari 71
-
REMOTE CONTROL ANALOG ( RCA )
Nilai c MNEMO DESIGNATION 1 POOP REAL POWER SET POINT
2 PROP MAX POWER VARIATION SET POINT
3 N LOAD FREQ CONTROL N_LEVEL
TELESIGNAL SINGLE (TSS)
Nilai c MNEMO OP MNEMO
HAR DESIGNATION
1 VACF VAC FAILURE
2 220F 220 VAC FAILURE
3 380F 380 VAC FAILURE
4 VDCF VDC FAILURE
5 220RF 220VDC RECTIFIER FAILURE
6 220SF 220VDC SUPPLY FAILURE
7 110RF 110VDC RECTIFIER FAILURE
8 110SF 110VDC SUPPLY FAILURE
9 24RF 24VDC RECTIFIER FAILURE
10 24SF 24VDC SUPPLY FAILURE
11 48RF 48VDC RECTIFIER FAILURE
12 48SF 48VDC SUPPLY FAILURE
13 DCG DC GROUND
14 PHA PERIPHERAL ALARM
15 DFRF DISTURBANCE FAULT RECORDER FAULTY
16 ERF EVENT RECORDER FAILURE
17 FDC FAULT DATA CAPTURED
18 GRE GENSET READY
19 AIRCF AIR CONDITIONING FAILURE
20 AR CIRCUIT BREAKER AUTO RECLOSE
21 ARO AUTO RECLOSE OFF
22 BF BAY FAULT
23 VTF VOLTAGE TRANSFORMER FAILURE
24 DSDF DISCONNECTING SWITCH DRIVING FAULT
25 DCF DC SUPPLY FAILURE
26 BRF BREAKER FAULT
27 LPA LOW PRESSURE ALARM
28 LPB LOW PRESSURE BLOCK
29 LPT LOW PRESSURE TRIP
30 PD POLE DISCREPANCY
31 CBDF CIRCUIT BREAKER DRIVE FAILURE
32 TCS1 TRIP COIL SUPERVISORY 1
33 TCS2 TRIP COIL SUPERVISORY 2
34 CBM CIRCUIT BREAKER MAINTENANCE
35 RTUA REMOTE STATION ALARM
36 IR INTERNAL REMOTE STATION
37 CTE CABINET TEMPERATUR
14 dari 71
-
38 COM COMMUNICATION FAULTY
39 CF CARRIER FAULTY
40 FOTF FO TERMINAL FAULTY
41 PLCF PLC TERMINAL FAULTY
42 RADF RADIO LINK FAULTY
43 PBXF PABX FAULTY
44 DOOR DOOR ACTIVATED
45 SIA STATION INTRUDER ALARM
46 RSTA RESET ALARM
47 CSP CHECK SYNCHRONIZING IN PROGRESS
48 OCPA OIL CABLE PRESSURE ALARM
49 PWF PILOT WIRE FAILURE
50 RTN RELAY TEGANGAN NOL
51 SYNF SYNCHRONIZING FAILURE
52 FPO FIRE PROTECTION OPERATED
53 TEA TEMPERATURE ALARM
54 WTHVA HV WINDING TEMPERATUR ALARM
55 WTLVA LV WINDING TEMPERATUR ALARM
56 OTA OIL TEMPERATURE ALARM
57 TET TEMPERATURE TRIP
58 WTHVT HV WINDING TEMPERATUR TRIP
59 WTLVT LV WINDING TEMPERATUR TRIP
60 OTT OIL TEMPERATUR TRIP
61 TRA TRANSFORMER ALARM
62 TBUCA TRANSFORMER BUCHOLZ ALARM
63 TSPA TRANSFORMER SUDDEN PRESSURE ALARM
64 TOLA TRANSFORMER OIL LEVEL ALARM
65 TOOS TRANSFORMER OUT OF STEP ALARM
66 TRT TRANSFORMER TRIP
67 TBUC2 TRANSFORMER BUCHOLZ TRIP
68 TSPT TRANSFORMER SUDDEN PRESSURE TRIP
69 TFDP TRANSFORMER FIRE DETECTION & PROTECTION
70 TJANT TRANSFORMER JANSEN TRIP
71 RCFF REAKTOR COOLING FAN FAILURE
72 RF REAKTOR FAILURE
73 RA REAKTOR ALARM
74 RBUCA REAKTOR BUCHOLZ ALARM
75 RSPA REAKTOR SUDDEN PRESSURE ALARM
76 ROLA REAKTOR OIL LEVEL ALARM
77 RT REAKTOR TRIP
78 RBUC2 REAKTOR BUCHOLZ TRIP
79 RSPT REAKTOR SUDDEN PRESSURE TRIP
80 RFDP REAKTOR FIRE DETECTION & PROTECTION
81 TAF TRANFORMER AVR FAILURE
82 TCA TAP CHANGER ALARM
83 TCT TAP CHANGER TRIP
84 TPIF TAP POSITION INDICATION FAILURE
85 TCH TAP CHANGER HIGH LIMIT
86 TCL TAP CHANGER LOW LIMIT
87 TCFF TRANSFORMER COOLING FAN FAILURE
15 dari 71
-
88 TCPF TRANSFORMER COOLING PUMP FAILURE
89 VS VOLTAGE STATUS
90 FRA FIRE ALARM
91 FRSF FIRE ALARM SYSTEM FAILURE
92 POT PROTECTION ON TEST
93 GOV FREE ACTING GOVERNOR ACTIVE
94 AVR AUTOMATIC VOLTAGE REGULATOR ON/OFF
95 AQR AUTOMATIC POWER FACTOR REGULATOR ACTIVE
96 LFF LOAD FREQ CONTROL UNIT FAILURE
97 UT UNIT TRIP
98 GTT GENERATOR TRANSFORMER TRIP
99 LOWCT LOW OIL PRESSURE CABLE TRIP
100 PRDT PRESSURE RELAY DEVICE TRIP
101 MTO MASTER TRIP OPERATE
102 UFR UNDER FREQUENCY RELAY OPERATE
103 UVR UNDER VOLTAGE RELAY OPERATE
104 OVR OVER VOLTAGE RELAY OPERATE
105 PTF PROTECTION FAULTY
106 OCRF OVER CURRENT RELAY FAILURE
107 OVRF OVER VOLTAGE RELAY FAILURE
108 UVRF UNDER VOLTAGE RELAY FAILURE
109 GFRF GROUND FAULT RELAY FAILURE
110 DZAF DISTANCE RELAY (a) FAILURE
111 DZBF DISTANCE RELAY (b) FAILURE
112 DEFAF DIRECTIONAL EARTH FAULT (a) FAILURE
113 DEFBF DIRECTIONAL EARTH FAULT (b) FAILURE
114 CDAF CURRENT DIFFERENTIAL RELAY (a) FAILURE
115 CDBF CURRENT DIFFERENTIAL RELAY (b) FAILURE
116 TPAF TELEPROTECTION (a) FAILURE
117 TPBF TELEPROTECTION (b) FAILURE
118 DIFF DIFFERENTIAL FAILURE
119 REFF RESTRICTED EARTH FAULT FAILURE
120 BPAF BUSBAR PROTECTION (a) FAILURE
121 BPBF BUSBAR PROTECTION (b) FAILURE
122 CCPF CIRCULATING CURRENT PROTECTION FAILURE
123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE
124 SZPF SHORT ZONE PROTECTION FAILURE
125 TTR TELEPROTECTION TRIP RECEIVE
126 DZARX DISTANCE (a) RELAY RECEIVE
127 DZBRX DISTANCE (b) RELAY RECEIVE
128 DEARX DIRECTIONAL EARTH FAULT (a) RELAY RECEIVE
129 DEBRX DIRECTIONAL EARTH FAULT (b) RELAY RECEIVE
130 DTARX DIRECT TRANSFER TRIP (a) RECEIVE
131 DTBRX DIRECT TRANSFER TRIP (b) RECEIVE
132 TTT TELEPROTECTION TRIP TRANSMIT
133 DZATX DISTANCE (a) RELAY TRANSMIT
134 DZBTX DISTANCE (b) RELAY TRANSMIT
135 DEATX DIRECTIONAL EARTH FAULT (a) RELAY TRANSMIT
16 dari 71
-
136 DEBTX DIRECTIONAL EARTH FAULT (b) RELAY TRANSMIT
137 DTATX DIRECT TRANSFER TRIP (a) TRANSMIT
138 DTBTX DIRECT TRANSFER TRIP (b) TRANSMIT
139 P1BP BUSBAR PROTECTION
140 BPA BUSBAR PROTECTION (a)
141 BPB BUSBAR PROTECTION (b)
142 P1CD CURRENT DEFFERENTIAL
143 CDAR CURRENT DIFFERENTIAL (a) PHASE R
144 CDAS CURRENT DIFFERENTIAL (a) PHASE S
145 CDAT CURRENT DIFFERENTIAL (a) PHASE T
146 CDBR CURRENT DIFFERENTIAL (b) PHASE R
147 CDBS CURRENT DIFFERENTIAL (b) PHASE S
148 CDBT CURRENT DIFFERENTIAL (b) PHASE T
149 P1DEF DIRECTIONAL EARTH FAULT
150 DEFAR DIRECTIONAL EARTH FAULT (a) PHASE R
151 DEFAS DIRECTIONAL EARTH FAULT (a) PHASE S
152 DEFAT DIRECTIONAL EARTH FAULT (a) PHASE T
153 DEFBR DIRECTIONAL EARTH FAULT (b) PHASE R
154 DEFBS DIRECTIONAL EARTH FAULT (b) PHASE S
155 DEFBT DIRECTIONAL EARTH FAULT (b) PHASE T
156 P1DIF DIFFERENTIAL
157 P1REF RESTRICTED EARTH FAULT
158 P1Z1 DISTANCE PROTECTION ZONE 1
159 DZ1AR DISTANCE (a) PHASE R ZONE 1
160 DZ1AS DISTANCE (a) PHASE S ZONE 1
161 DZ1AT DISTANCE (a) PHASE T ZONE 1
162 DZ1BR DISTANCE (b) PHASE R ZONE 1
163 DZ1BS DISTANCE (b) PHASE S ZONE 1
164 DZ1BT DISTANCE (b) PHASE T ZONE 1
165 P1Z2 DISTANCE PROTECTION ZONE 2
166 DZ2AR DISTANCE (a) PHASE R ZONE 2
167 DZ2AS DISTANCE (a) PHASE S ZONE 2
168 DZ2AT DISTANCE (a) PHASE T ZONE 2
169 DZ2BR DISTANCE (b) PHASE R ZONE 2
170 DZ2BS DISTANCE (b) PHASE S ZONE 2
171 DZ2BT DISTANCE (b) PHASE T ZONE 2
172 P1Z3 DISTANCE PROTECTION ZONE 3
173 DZ3AR DISTANCE (a) PHASE R ZONE 3
174 DZ3AS DISTANCE (a) PHASE S ZONE 3
175 DZ3AT DISTANCE (a) PHASE T ZONE 3
176 DZ3BR DISTANCE (b) PHASE R ZONE 3
177 DZ3BS DISTANCE (b) PHASE S ZONE 3
178 DZ3BT DISTANCE (b) PHASE T ZONE 3
179 P2GFR GROUND FAULT RELAY
180 P2OCR OVER CURRENT RELAY
181 P3DTT DIRECT TRANSFER TRIP
182 CCPA CIRCULATING CURRENT PROTECTION (a) OPERATE
183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE
17 dari 71
-
184 SZPA SHORT ZONE PROTECTION (a) OPERATE
185 CCPB CIRCULATING CURRENT PROTECTION (b) OPERATE
186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE
187 SZPB SHORT ZONE PROTECTION (b) OPERATE
188 CBTR CB TRIP
189 PHR TRIP PHASE R
190 PHS TRIP PHASE S
191 PHT TRIP PHASE T
192 HFD HOMOPOLAR FAULT DETECTOR
193 SIB SOFTWARE INTERLOCKING BYPASS
194 IEDF IED FAULTY
195 SOTF SWITCH ON TO FAULT
196 PD PARTIAL DISCHARGE (PRIMARY-SECONDARY-TERSIER)
197 OFO ONLINE FILTERING OLTC
198 DGA DISSOLVE GAS ANALYSIS
199 NVD NEUTRAL VOLTAGE DISPLACEMENT (TERSIER)
7.4 Nomer Urut Bay (Nilai variabel d) Berisi nomer urut untuk masing-masing tipe bay tertentu. Contoh: jika suatu gardu induk memiliki 4 diameter maka field ini akan memiliki nilai sebagai berikut:
Bay Nilai d Diameter 1 1 Diameter 2 2 Diameter 3 3 Diameter 4 4
Jika suatu gardu induk memiliki bay dengan urutan yang tidak dimulai dari satu, maka field ini akan disesuaikan dengan urutan bay tersebut. Contoh jika suatu gardu induk memiliki 2 transformer dengan urutan trafo-2 dan trafo-3 maka field ini akan memiliki nilai sebagai berikut:
Bay Nilai d Trafo 2 2 Trafo 3 3
Untuk Bay Substation field ini akan bernilai 1, karena hanya ada satu bay substation di satu gardu induk. Contohnya:
Bay Nilai d Gardu Induk 1
7.5 Nomor Urut Elemen (Nilai variabel e) Berisi nomor urut jika dalam satu bay ada elemen yang sama.
18 dari 71
-
19 dari 71
Contoh: Pada bay kopel terdapat dua Pemisah maka field ini akan memiliki nilai sebagai berikut:
Elemen Nilai e BI1 1 BI2 2
Contoh lain: pada beberapa bay penghantar terdapat empat pemisah tanah, maka field ini akan memiliki nilai sebagai berikut:
Elemen Nilai e ES1 1 ES2 2 ES3 3 ES4 4
Jika elemen tersebut adalah unik (tunggal) pada bay tersebut, maka field ini akan bernilai nol (0). Contoh: Pada bay yang hanya memiliki satu CB maka field ini akan bernilai nol (0).
Elemen Nilai e CB 0
Untuk diameter yang memiliki tiga CB, maka addressing elemen-elemen pada diameter tersebut sebagai berikut:
Elemen Nilai e CB_A 1 CB_AB 2 CB_B 3 BI1_A 1 BI2_A 2 BI1_AB 3 BI2_AB 4 BI1_B 5 BI2_B 6
Contohnya, address untuk indikasi elemen CB B pada diameter ke 24 (7B24) adalah:
104 / 2 / 243
dimana: 10 menginidikasikan tipe bay diameter 4 menginidikasikan telesignal double
2 mengindikasikan elemen CB 24 mengindikasikan diameter ke-24 3 mengin dikasikan CB ke-3 (CB B)
-
8. Lampiran A: Contoh Standard Addressing Teleinformation Plan
20 dari 71
-
BAY TYPE TYPE NO MNEMO DESIGNATION OP HAR IEC 60870-5-101 / 104
IOA1 IOA2 IOA3
REMOTE STATION RCD 1 DCBC DUMMY CIRCUIT BREAKER CLOSED/OPENED X X 12 1 10 REMOTE STATION RCD 17 CD CONTROL DISABLE SWITCH X 12 17 10 REMOTE STATION TSD 1 DCBC DUMMY BREAKER CLOSED/OPENED X 14 1 10 REMOTE STATION TSD 17 CD CONTROL DISABLE SWITCH X X 14 17 10 REMOTE STATION TSS 35 RTUA REMOTE STATION ALARM X 15 35 10 REMOTE STATION TSS 36 IR INTERNAL REMOTE STATION X 15 36 10 REMOTE STATION TSS 37 CTE CABINET TEMPERATUR X 15 37 10 REMOTE STATION 7
GARDU INDUK TM 1 F FREKUENSI (BUS 1) X X 21 1 11
GARDU INDUK TM 1 F FREKUENSI (BUS 2) X X 21 1 12
GARDU INDUK TM 15 RH RELATIVE HUMIDITY X 21 15 10
GARDU INDUK RCD 5 LR LOCAL REMOTE X 22 5 10
GARDU INDUK RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 22 9 10
GARDU INDUK RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 22 13 10
GARDU INDUK RCD 14 RMT RESET MASTER TRIP X 22 14 10
GARDU INDUK TSD 5 LR LOCAL REMOTE X X 24 5 10
GARDU INDUK TSD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 24 9 10
GARDU INDUK TSD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 24 13 10
GARDU INDUK TSD 14 RMT RESET MASTER TRIP X 24 14 10
GARDU INDUK TSS 1 VACF VAC FAILURE X 25 1 10
GARDU INDUK TSS 2 220F 220 VAC FAILURE X 25 2 10
GARDU INDUK TSS 3 380F 380 VAC FAILURE X 25 3 10
21 dari 71
-
GARDU INDUK TSS 4 VDCF VDC FAILURE X 25 4 10
GARDU INDUK TSS 5 220RF 220VDC RECTIFIER FAILURE X 25 5 10
GARDU INDUK TSS 6 220SF 220VDC SUPPLY FAILURE X 25 6 10
GARDU INDUK TSS 7 110RF 110VDC RECTIFIER FAILURE X 25 7 10
GARDU INDUK TSS 8 110SF 110VDC SUPPLY FAILURE X 25 8 10
GARDU INDUK TSS 9 24RF 24VDC RECTIFIER FAILURE X 25 9 10
GARDU INDUK TSS 10 24SF 24VDC SUPPLY FAILURE X 25 10 10
GARDU INDUK TSS 11 48RF 48VDC RECTIFIER FAILURE X 25 11 10
GARDU INDUK TSS 12 48SF 48VDC SUPPLY FAILURE X 25 12 10
GARDU INDUK TSS 13 DCG DC GROUND X 25 13 10
GARDU INDUK TSS 14 PHA PERIPHERAL ALARM X 25 14 10
GARDU INDUK TSS 18 GRE GENSET READY X 25 18 10
GARDU INDUK TSS 19 AIRCF AIR CONDITIONING FAILURE X 25 19 10
GARDU INDUK TSS 38 COM COMMUNICATION FAULTY X 25 38 10
GARDU INDUK TSS 40 FOTF FO TERMINAL FAULTY X 25 40 10
GARDU INDUK TSS 41 PLCF PLC TERMINAL FAULTY X 25 41 10
GARDU INDUK TSS 42 RADF RADIO LINK FAULTY X 25 42 10
GARDU INDUK TSS 43 PBXF PABX FAULTY X 25 43 10
GARDU INDUK TSS 44 DOOR DOOR ACTIVATED X 25 44 10
GARDU INDUK TSS 45 SIA STATION INTRUDER ALARM X 25 45 10
GARDU INDUK TSS 46 RSTA RESET ALARM X 25 46 10
GARDU INDUK TSS 50 RTN RELAY TEGANGAN NOL X 25 50 10
GARDU INDUK TSS 51 SYNF SYNCHRONIZING FAILURE X 25 51 10
GARDU INDUK TSS 90 FRA FIRE ALARM X 25 90 10
GARDU INDUK TSS 91 FRSF FIRE ALARM SYSTEM FAILURE X 25 91 10
GARDU INDUK TSS 101 MTO MASTER TRIP OPERATE X 25 101 10
GARDU INDUK TSS 105 PTF PROTECTION FAULTY X 25 105 10
22 dari 71
-
GARDU INDUK TSS 109 GFRF GROUND FAULT RELAY FAILURE X 25 109 10
GARDU INDUK TSS 193 SIB SOFTWARE INTERLOCKING BYPASS X 25 193 10
GARDU INDUK TSS 194 IEDF IED FAULTY X 25 194 10
GARDU INDUK TSS 195 SOTF SWITCH ON TO FAULT X 25 195 10
GARDU INDUK 45
BUSBAR 1 TM 2 V TEGANGAN X X 31 2 10
BUSBAR 1 TSS 22 BF BAY FAULT X 35 22 10
BUSBAR 1 TSS 23 VTF VOLTAGE TRANSFORMER FAILURE X 35 23 10
BUSBAR 1 TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 35 24 10
BUSBAR 1 TSS 89 VS VOLTAGE STATUS X X 35 89 10
BUSBAR 1 TSS 92 POT PROTECTION ON TEST X 35 92 10
BUSBAR 1 TSS 103 UVR UNDER VOLTAGE RELAY OPERATE X X 35 103 10
BUSBAR 1 TSS 104 OVR OVER VOLTAGE RELAY OPERATE X X 35 104 10
BUSBAR 1 TSS 107 OVRF OVER VOLTAGE RELAY FAILURE X 35 107 10
BUSBAR 1 TSS 108 UVRF UNDER VOLTAGE RELAY FAILURE X 35 108 10
BUSBAR 1 TSS 120 BPAF BUSBAR PROTECTION (a) FAILURE X 35 120 10
BUSBAR 1 TSS 121 BPBF BUSBAR PROTECTION (b) FAILURE X 35 121 10
BUSBAR 1 TSS 139 P1BP BUSBAR PROTECTION X 35 139 10
BUSBAR 1 TSS 140 BPA BUSBAR PROTECTION (a) X 35 140 10
BUSBAR 1 TSS 141 BPB BUSBAR PROTECTION (b) X 35 141 10
BUSBAR 1 TSS 194 IEDF IED FAULTY X 35 194 10
BUSBAR 1 16
BUSBAR 2 TM 2 V TEGANGAN X X 31 2 20
BUSBAR 2 TSS 22 BF BAY FAULT X 35 22 20
BUSBAR 2 TSS 23 VTF VOLTAGE TRANSFORMER FAILURE X 35 23 20
BUSBAR 2 TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 35 24 20
BUSBAR 2 TSS 89 VS VOLTAGE STATUS X X 35 89 20
23 dari 71
-
BUSBAR 2 TSS 92 POT PROTECTION ON TEST X 35 92 20
BUSBAR 2 TSS 103 UVR UNDER VOLTAGE RELAY OPERATE X X 35 103 20
BUSBAR 2 TSS 104 OVR OVER VOLTAGE RELAY OPERATE X X 35 104 20
BUSBAR 2 TSS 107 OVRF OVER VOLTAGE RELAY FAILURE X 35 107 20
BUSBAR 2 TSS 108 UVRF UNDER VOLTAGE RELAY FAILURE X 35 108 20
BUSBAR 2 TSS 120 BPAF BUSBAR PROTECTION (a) FAILURE X 35 120 20
BUSBAR 2 TSS 121 BPBF BUSBAR PROTECTION (b) FAILURE X 35 121 20
BUSBAR 2 TSS 139 P1BP BUSBAR PROTECTION X 35 139 20
BUSBAR 2 TSS 140 BPA BUSBAR PROTECTION (a) X 35 140 20
BUSBAR 2 TSS 141 BPB BUSBAR PROTECTION (b) X 35 141 20
BUSBAR 2 TSS 194 IEDF IED FAULTY X 35 194 20
BUSBAR 2 16
KOPEL TM 3 I ARUS (BUS 1) X X 41 31 11
KOPEL TM 3 I ARUS (BUS 2) X X 41 32 12
KOPEL TM 7 CCB COUNTER OF CIRCUIT BREAKER X 41 7 10
KOPEL TM 9 PRES PRESSURE X 41 9 10
KOPEL RCD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 42 2 10
KOPEL RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 42 3 11
KOPEL RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 42 3 12
KOPEL RCD 5 LR LOCAL REMOTE X 42 5 10
KOPEL RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X 42 9 10
KOPEL RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 42 13 10
KOPEL TSD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 44 2 10
KOPEL TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 44 3 11
KOPEL TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 44 3 12
KOPEL TSD 5 LR LOCAL REMOTE X X 44 5 10
KOPEL TSD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 44 9 10
24 dari 71
-
KOPEL TSD 10 ES EARTH SWITCH CLOSED/OPENED **) X 44 10 10
KOPEL TSD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 44 13 10
KOPEL TSS 16 ERF EVENT RECORDER FAILURE X 45 16 10
KOPEL TSS 22 BF BAY FAULT X 45 22 10
KOPEL TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 45 24 10
KOPEL TSS 25 DCF DC SUPPLY FAILURE X 45 25 10
KOPEL TSS 26 BRF BREAKER FAULT X 45 26 10
KOPEL TSS 27 LPA LOW PRESSURE ALARM X 45 27 10
KOPEL TSS 28 LPB LOW PRESSURE BLOCK X 45 28 10
KOPEL TSS 29 LPT LOW PRESSURE TRIP X 45 29 10
KOPEL TSS 30 PD POLE DISCREPANCY X 45 30 10
KOPEL TSS 31 CBDF CIRCUIT BREAKER DRIVE FAILURE X 45 31 10
KOPEL TSS 32 TCS1 TRIP COIL SUPERVISORY 1 X 45 32 10
KOPEL TSS 33 TCS2 TRIP COIL SUPERVISORY 2 X 45 33 10
KOPEL TSS 34 CBM CIRCUIT BREAKER MAINTENANCE X 45 34 10
KOPEL TSS 47 CSP CHECK SYNCHRONIZING IN PROGRESS X X 45 47 10
KOPEL TSS 92 POT PROTECTION ON TEST X 45 92 10
KOPEL TSS 101 MTO MASTER TRIP OPERATE X 45 101 10
KOPEL TSS 106 OCRF OVER CURRENT RELAY FAILURE X 45 106 10
KOPEL TSS 109 GFRF GROUND FAULT RELAY FAILURE X 45 109 10
KOPEL TSS 123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE X 45 123 10
KOPEL TSS 124 SZPF SHORT ZONE PROTECTION FAILURE X 45 124 10
KOPEL TSS 179 P2GFR GROUND FAULT RELAY X X 45 179 10
KOPEL TSS 180 P2OCR OVER CURRENT RELAY X X 45 180 10
KOPEL TSS 183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE X 45 183 10
KOPEL TSS 184 SZPA SHORT ZONE PROTECTION (a) OPERATE X 45 184 10
KOPEL TSS 186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE X 45 186 10
KOPEL TSS 187 SZPB SHORT ZONE PROTECTION (b) OPERATE X 45 187 10
KOPEL TSS 188 CBTR CB TRIP X 45 188 10
KOPEL TSS 189 PHR TRIP PHASE R X 45 189 10
25 dari 71
-
KOPEL TSS 190 PHS TRIP PHASE S X 45 190 10
KOPEL TSS 191 PHT TRIP PHASE T X 45 191 10
KOPEL TSS 193 SIB SOFTWARE INTERLOCKING BYPASS X 45 193 10
KOPEL TSS 194 IEDF IED FAULTY X 45 194 10
KOPEL TSS 195 SOTF SWITCH ON TO FAULT X 45 195 10 KOPEL 50
PURWODADI 1 TM 2 V TEGANGAN X X 61 2 10
PURWODADI 1 TM 2 V TEGANGAN X X 61 2 11
PURWODADI 1 TM 2 V TEGANGAN X X 61 2 12
PURWODADI 1 TM 2 V TEGANGAN X X 61 2 13
PURWODADI 1 TM 3 I ARUS X X 61 3 10
PURWODADI 1 TM 3 I ARUS X X 61 3 11
PURWODADI 1 TM 3 I ARUS X X 61 3 12
PURWODADI 1 TM 3 I ARUS X X 61 3 13
PURWODADI 1 TM 4 P DAYA AKTIF X X 61 4 10
PURWODADI 1 TM 5 Q DAYA REAKTIF X X 61 5 10
PURWODADI 1 TM 7 CCB COUNTER OF CIRCUIT BREAKER X 61 7 10
PURWODADI 1 TM 9 PRES PRESSURE X 61 9 10
PURWODADI 1 TM 12 AMF AMPERES FAULT ( PER PHASE ) X 61 12 10
PURWODADI 1 TM 13 KWH KILOWATT HOUR X 61 13 10
PURWODADI 1 TM 14 KVARH KILOVAR HOUR X 61 14 10
PURWODADI 1 TM 16 CNTA COUNTER ARESTER X 61 16 10
PURWODADI 1 RCD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 62 2 10
PURWODADI 1 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 62 3 11
PURWODADI 1 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 62 3 12
PURWODADI 1 RCD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X 62 4 10
PURWODADI 1 RCD 5 LR LOCAL REMOTE X 62 5 10
PURWODADI 1 RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X 62 9 10
PURWODADI 1 RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 62 13 10
26 dari 71
-
PURWODADI 1 TSD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 64 2 10
PURWODADI 1 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 64 3 11
PURWODADI 1 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 64 3 12
PURWODADI 1 TSD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X X 64 4 10
PURWODADI 1 TSD 5 LR LOCAL REMOTE X X 64 5 10
PURWODADI 1 TSD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 64 9 10
PURWODADI 1 TSD 10 ES EARTH SWITCH CLOSED/OPENED **) X 64 10 10
PURWODADI 1 TSD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 64 13 10
PURWODADI 1 TSS 15 DFRF DISTURBANCE FAULT RECORDER FAULTY X 65 15 10
PURWODADI 1 TSS 16 ERF EVENT RECORDER FAILURE X 65 16 10
PURWODADI 1 TSS 20 AR CIRCUIT BREAKER AUTO RECLOSE X X 65 20 10
PURWODADI 1 TSS 21 ARO AUTO RECLOSE OFF X X 65 21 10
PURWODADI 1 TSS 22 BF BAY FAULT X 65 22 10
PURWODADI 1 TSS 23 VTF VOLTAGE TRANSFORMER FAILURE X 65 23 10
PURWODADI 1 TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 65 24 10
PURWODADI 1 TSS 25 DCF DC SUPPLY FAILURE X 65 25 10
PURWODADI 1 TSS 26 BRF BREAKER FAULT X 65 26 10
PURWODADI 1 TSS 27 LPA LOW PRESSURE ALARM X 65 27 10
PURWODADI 1 TSS 28 LPB LOW PRESSURE BLOCK X 65 28 10
PURWODADI 1 TSS 29 LPT LOW PRESSURE TRIP X 65 29 10
PURWODADI 1 TSS 30 PD POLE DISCREPANCY X 65 30 10
PURWODADI 1 TSS 31 CBDF CIRCUIT BREAKER DRIVE FAILURE X 65 31 10
PURWODADI 1 TSS 32 TCS1 TRIP COIL SUPERVISORY 1 X 65 32 10
PURWODADI 1 TSS 33 TCS2 TRIP COIL SUPERVISORY 2 X 65 33 10
PURWODADI 1 TSS 34 CBM CIRCUIT BREAKER MAINTENANCE X 65 34 10
PURWODADI 1 TSS 39 CF CARRIER FAULTY X 65 39 10
PURWODADI 1 TSS 47 CSP CHECK SYNCHRONIZING IN PROGRESS X X 65 47 10
PURWODADI 1 TSS 49 PWF PILOT WIRE FAILURE X 65 49 10
PURWODADI 1 TSS 51 SYNF SYNCHRONIZING FAILURE X 65 51 10
27 dari 71
-
PURWODADI 1 TSS 92 POT PROTECTION ON TEST X 65 92 10
PURWODADI 1 TSS 101 MTO MASTER TRIP OPERATE X 65 101 10
PURWODADI 1 TSS 102 UFR UNDER FREQUENCY RELAY OPERATE X 65 102 10
PURWODADI 1 TSS 103 UVR UNDER VOLTAGE RELAY OPERATE X 65 103 10
PURWODADI 1 TSS 104 OVR OVER VOLTAGE RELAY OPERATE X 65 104 10
PURWODADI 1 TSS 106 OCRF OVER CURRENT RELAY FAILURE X 65 106 10
PURWODADI 1 TSS 107 OVRF OVER VOLTAGE RELAY FAILURE X 65 107 10
PURWODADI 1 TSS 108 UVRF UNDER VOLTAGE RELAY FAILURE X 65 108 10
PURWODADI 1 TSS 109 GFRF GROUND FAULT RELAY FAILURE X 65 109 10
PURWODADI 1 TSS 110 DZAF DISTANCE RELAY (a) FAILURE X 65 110 10
PURWODADI 1 TSS 111 DZBF DISTANCE RELAY (b) FAILURE X 65 111 10
PURWODADI 1 TSS 112 DEFAF DIRECTIONAL EARTH FAULT (a) FAILURE X 65 112 10
PURWODADI 1 TSS 113 DEFBF DIRECTIONAL EARTH FAULT (b) FAILURE X 65 113 10
PURWODADI 1 TSS 114 CDAF CURRENT DIFFERENTIAL RELAY (a) FAILURE X 65 114 10
PURWODADI 1 TSS 115 CDBF CURRENT DIFFERENTIAL RELAY (b) FAILURE X 65 115 10
PURWODADI 1 TSS 116 TPAF TELEPROTECTION (a) FAILURE X 65 116 10
PURWODADI 1 TSS 117 TPBF TELEPROTECTION (b) FAILURE X 65 117 10
PURWODADI 1 TSS 123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE X 65 123 10
PURWODADI 1 TSS 124 SZPF SHORT ZONE PROTECTION FAILURE X 65 124 10
PURWODADI 1 TSS 125 TTR TELEPROTECTION TRIP RECEIVE X 65 125 10
PURWODADI 1 TSS 126 DZARX DISTANCE (a) RELAY RECEIVE X 65 126 10
PURWODADI 1 TSS 127 DZBRX DISTANCE (b) RELAY RECEIVE X 65 127 10
PURWODADI 1 TSS 128 DEARX DIRECTIONAL EARTH FAULT (a) RELAY RECEIVE X 65 128 10
PURWODADI 1 TSS 129 DEBRX DIRECTIONAL EARTH FAULT (b) RELAY RECEIVE X 65 129 10
PURWODADI 1 TSS 130 DTARX DIRECT TRANSFER TRIP (a) RECEIVE X 65 130 10
PURWODADI 1 TSS 131 DTBRX DIRECT TRANSFER TRIP (b) RECEIVE X 65 131 10
PURWODADI 1 TSS 132 TTT TELEPROTECTION TRIP TRANSMIT X 65 132 10
PURWODADI 1 TSS 133 DZATX DISTANCE (a) RELAY TRANSMIT X 65 133 10
PURWODADI 1 TSS 134 DZBTX DISTANCE (b) RELAY TRANSMIT X 65 134 10
28 dari 71
-
PURWODADI 1 TSS 135 DEATX DIRECTIONAL EARTH FAULT (a) RELAY TRANSMIT X 65 135 10
PURWODADI 1 TSS 136 DEBTX DIRECTIONAL EARTH FAULT (b) RELAY TRANSMIT X 65 136 10
PURWODADI 1 TSS 137 DTATX DIRECT TRANSFER TRIP (a) TRANSMIT X 65 137 10
PURWODADI 1 TSS 138 DTBTX DIRECT TRANSFER TRIP (b) TRANSMIT X 65 138 10
PURWODADI 1 TSS 142 P1CD CURRENT DEFFERENTIAL X 65 142 10
PURWODADI 1 TSS 143 CDAR CURRENT DIFFERENTIAL (a) PHASE R X 65 143 10
PURWODADI 1 TSS 144 CDAS CURRENT DIFFERENTIAL (a) PHASE S X 65 144 10
PURWODADI 1 TSS 145 CDAT CURRENT DIFFERENTIAL (a) PHASE T X 65 145 10
PURWODADI 1 TSS 146 CDBR CURRENT DIFFERENTIAL (b) PHASE R X 65 146 10
PURWODADI 1 TSS 147 CDBS CURRENT DIFFERENTIAL (b) PHASE S X 65 147 10
PURWODADI 1 TSS 148 CDBT CURRENT DIFFERENTIAL (b) PHASE T X 65 148 10
PURWODADI 1 TSS 149 P1DEF DIRECTIONAL EARTH FAULT X 65 149 10
PURWODADI 1 TSS 150 DEFAR DIRECTIONAL EARTH FAULT (a) PHASE R X 65 150 10
PURWODADI 1 TSS 151 DEFAS DIRECTIONAL EARTH FAULT (a) PHASE S X 65 151 10
PURWODADI 1 TSS 152 DEFAT DIRECTIONAL EARTH FAULT (a) PHASE T X 65 152 10
PURWODADI 1 TSS 153 DEFBR DIRECTIONAL EARTH FAULT (b) PHASE R X 65 153 10
PURWODADI 1 TSS 154 DEFBS DIRECTIONAL EARTH FAULT (b) PHASE S X 65 154 10
PURWODADI 1 TSS 155 DEFBT DIRECTIONAL EARTH FAULT (b) PHASE T X 65 155 10
PURWODADI 1 TSS 158 P1Z1 DISTANCE PROTECTION ZONE 1 X 65 158 10
PURWODADI 1 TSS 159 DZ1AR DISTANCE (a) PHASE R ZONE 1 X 65 159 10
PURWODADI 1 TSS 160 DZ1AS DISTANCE (a) PHASE S ZONE 1 X 65 160 10
PURWODADI 1 TSS 161 DZ1AT DISTANCE (a) PHASE T ZONE 1 X 65 161 10
PURWODADI 1 TSS 162 DZ1BR DISTANCE (b) PHASE R ZONE 1 X 65 162 10
PURWODADI 1 TSS 163 DZ1BS DISTANCE (b) PHASE S ZONE 1 X 65 163 10
PURWODADI 1 TSS 164 DZ1BT DISTANCE (b) PHASE T ZONE 1 X 65 164 10
PURWODADI 1 TSS 165 P1Z2 DISTANCE PROTECTION ZONE 2 X 65 165 10
PURWODADI 1 TSS 166 DZ2AR DISTANCE (a) PHASE R ZONE 2 X 65 166 10
PURWODADI 1 TSS 167 DZ2AS DISTANCE (a) PHASE S ZONE 2 X 65 167 10
PURWODADI 1 TSS 168 DZ2AT DISTANCE (a) PHASE T ZONE 2 X 65 168 10
29 dari 71
-
PURWODADI 1 TSS 169 DZ2BR DISTANCE (b) PHASE R ZONE 2 X 65 169 10
PURWODADI 1 TSS 170 DZ2BS DISTANCE (b) PHASE S ZONE 2 X 65 170 10
PURWODADI 1 TSS 171 DZ2BT DISTANCE (b) PHASE T ZONE 2 X 65 171 10
PURWODADI 1 TSS 172 P1Z3 DISTANCE PROTECTION ZONE 3 X 65 172 10
PURWODADI 1 TSS 173 DZ3AR DISTANCE (a) PHASE R ZONE 3 X 65 173 10
PURWODADI 1 TSS 174 DZ3AS DISTANCE (a) PHASE S ZONE 3 X 65 174 10
PURWODADI 1 TSS 175 DZ3AT DISTANCE (a) PHASE T ZONE 3 X 65 175 10
PURWODADI 1 TSS 176 DZ3BR DISTANCE (b) PHASE R ZONE 3 X 65 176 10
PURWODADI 1 TSS 177 DZ3BS DISTANCE (b) PHASE S ZONE 3 X 65 177 10
PURWODADI 1 TSS 178 DZ3BT DISTANCE (b) PHASE T ZONE 3 X 65 178 10
PURWODADI 1 TSS 179 P2GFR GROUND FAULT RELAY X X 65 179 10
PURWODADI 1 TSS 180 P2OCR OVER CURRENT RELAY X X 65 180 10
PURWODADI 1 TSS 181 P3DTT DIRECT TRANSFER TRIP X 65 181 10
PURWODADI 1 TSS 183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE X 65 183 10
PURWODADI 1 TSS 184 SZPA SHORT ZONE PROTECTION (a) OPERATE X 65 184 10
PURWODADI 1 TSS 186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE X 65 186 10
PURWODADI 1 TSS 187 SZPB SHORT ZONE PROTECTION (b) OPERATE X 65 187 10
PURWODADI 1 TSS 188 CBTR CB TRIP X 65 188 10
PURWODADI 1 TSS 189 PHR TRIP PHASE R X 65 189 10
PURWODADI 1 TSS 190 PHS TRIP PHASE S X 65 190 10
PURWODADI 1 TSS 191 PHT TRIP PHASE T X 65 191 10
PURWODADI 1 TSS 193 SIB SOFTWARE INTERLOCKING BYPASS X 65 193 10
PURWODADI 1 TSS 194 IEDF IED FAULTY X 65 194 10
PURWODADI 1 TSS 195 SOTF SWITCH ON TO FAULT X 65 195 10
PURWODADI 1 134
PURWODADI 2 TM 2 V TEGANGAN X X 61 2 20
PURWODADI 2 TM 2 V TEGANGAN X X 61 2 21
PURWODADI 2 TM 2 V TEGANGAN X X 61 2 22
PURWODADI 2 TM 2 V TEGANGAN X X 61 2 23
PURWODADI 2 TM 3 I ARUS X X 61 3 20
30 dari 71
-
PURWODADI 2 TM 3 I ARUS X X 61 3 21
PURWODADI 2 TM 3 I ARUS X X 61 3 22
PURWODADI 2 TM 3 I ARUS X X 61 3 23
PURWODADI 2 TM 4 P DAYA AKTIF X X 61 4 20
PURWODADI 2 TM 5 Q DAYA REAKTIF X X 61 5 20
PURWODADI 2 TM 7 CCB COUNTER OF CIRCUIT BREAKER X 61 7 20
PURWODADI 2 TM 9 PRES PRESSURE X 61 9 20
PURWODADI 2 TM 12 AMF AMPERES FAULT ( PER PHASE ) X 61 12 20
PURWODADI 2 TM 13 KWH KILOWATT HOUR X 61 13 20
PURWODADI 2 TM 14 KVARH KILOVAR HOUR X 61 14 20
PURWODADI 2 TM 16 CNTA COUNTER ARESTER X 61 16 20
PURWODADI 2 RCD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 62 2 20
PURWODADI 2 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 62 3 21
PURWODADI 2 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 62 3 22
PURWODADI 2 RCD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X 62 4 20
PURWODADI 2 RCD 5 LR LOCAL REMOTE X 62 5 20
PURWODADI 2 RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X 62 9 20
PURWODADI 2 RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 62 13 20
PURWODADI 2 TSD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 64 2 20
PURWODADI 2 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 64 3 21
PURWODADI 2 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 64 3 22
PURWODADI 2 TSD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X X 64 4 20
PURWODADI 2 TSD 5 LR LOCAL REMOTE X X 64 5 20
PURWODADI 2 TSD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 64 9 20
PURWODADI 2 TSD 10 ES EARTH SWITCH CLOSED/OPENED **) X 64 10 20
PURWODADI 2 TSD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 64 13 20
PURWODADI 2 TSS 15 DFRF DISTURBANCE FAULT RECORDER FAULTY X 65 15 20
PURWODADI 2 TSS 16 ERF EVENT RECORDER FAILURE X 65 16 20
31 dari 71
-
PURWODADI 2 TSS 20 AR CIRCUIT BREAKER AUTO RECLOSE X X 65 20 20
PURWODADI 2 TSS 21 ARO AUTO RECLOSE OFF X X 65 21 20
PURWODADI 2 TSS 22 BF BAY FAULT X 65 22 20
PURWODADI 2 TSS 23 VTF VOLTAGE TRANSFORMER FAILURE X 65 23 20
PURWODADI 2 TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 65 24 20
PURWODADI 2 TSS 25 DCF DC SUPPLY FAILURE X 65 25 20
PURWODADI 2 TSS 26 BRF BREAKER FAULT X 65 26 20
PURWODADI 2 TSS 27 LPA LOW PRESSURE ALARM X 65 27 20
PURWODADI 2 TSS 28 LPB LOW PRESSURE BLOCK X 65 28 20
PURWODADI 2 TSS 29 LPT LOW PRESSURE TRIP X 65 29 20
PURWODADI 2 TSS 30 PD POLE DISCREPANCY X 65 30 20
PURWODADI 2 TSS 31 CBDF CIRCUIT BREAKER DRIVE FAILURE X 65 31 20
PURWODADI 2 TSS 32 TCS1 TRIP COIL SUPERVISORY 1 X 65 32 20
PURWODADI 2 TSS 33 TCS2 TRIP COIL SUPERVISORY 2 X 65 33 20
PURWODADI 2 TSS 34 CBM CIRCUIT BREAKER MAINTENANCE X 65 34 20
PURWODADI 2 TSS 39 CF CARRIER FAULTY X 65 39 20
PURWODADI 2 TSS 47 CSP CHECK SYNCHRONIZING IN PROGRESS X X 65 47 20
PURWODADI 2 TSS 49 PWF PILOT WIRE FAILURE X 65 49 20
PURWODADI 2 TSS 51 SYNF SYNCHRONIZING FAILURE X 65 51 20
PURWODADI 2 TSS 92 POT PROTECTION ON TEST X 65 92 20
PURWODADI 2 TSS 101 MTO MASTER TRIP OPERATE X 65 101 20
PURWODADI 2 TSS 102 UFR UNDER FREQUENCY RELAY OPERATE X 65 102 20
PURWODADI 2 TSS 103 UVR UNDER VOLTAGE RELAY OPERATE X 65 103 20
PURWODADI 2 TSS 104 OVR OVER VOLTAGE RELAY OPERATE X 65 104 20
PURWODADI 2 TSS 106 OCRF OVER CURRENT RELAY FAILURE X 65 106 20
PURWODADI 2 TSS 107 OVRF OVER VOLTAGE RELAY FAILURE X 65 107 20
PURWODADI 2 TSS 108 UVRF UNDER VOLTAGE RELAY FAILURE X 65 108 20
PURWODADI 2 TSS 109 GFRF GROUND FAULT RELAY FAILURE X 65 109 20
PURWODADI 2 TSS 110 DZAF DISTANCE RELAY (a) FAILURE X 65 110 20
PURWODADI 2 TSS 111 DZBF DISTANCE RELAY (b) FAILURE X 65 111 20
32 dari 71
-
PURWODADI 2 TSS 112 DEFAF DIRECTIONAL EARTH FAULT (a) FAILURE X 65 112 20
PURWODADI 2 TSS 113 DEFBF DIRECTIONAL EARTH FAULT (b) FAILURE X 65 113 20
PURWODADI 2 TSS 114 CDAF CURRENT DIFFERENTIAL RELAY (a) FAILURE X 65 114 20
PURWODADI 2 TSS 115 CDBF CURRENT DIFFERENTIAL RELAY (b) FAILURE X 65 115 20
PURWODADI 2 TSS 116 TPAF TELEPROTECTION (a) FAILURE X 65 116 20
PURWODADI 2 TSS 117 TPBF TELEPROTECTION (b) FAILURE X 65 117 20
PURWODADI 2 TSS 123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE X 65 123 20
PURWODADI 2 TSS 124 SZPF SHORT ZONE PROTECTION FAILURE X 65 124 20
PURWODADI 2 TSS 125 TTR TELEPROTECTION TRIP RECEIVE X 65 125 20
PURWODADI 2 TSS 126 DZARX DISTANCE (a) RELAY RECEIVE X 65 126 20
PURWODADI 2 TSS 127 DZBRX DISTANCE (b) RELAY RECEIVE X 65 127 20
PURWODADI 2 TSS 128 DEARX DIRECTIONAL EARTH FAULT (a) RELAY RECEIVE X 65 128 20
PURWODADI 2 TSS 129 DEBRX DIRECTIONAL EARTH FAULT (b) RELAY RECEIVE X 65 129 20
PURWODADI 2 TSS 130 DTARX DIRECT TRANSFER TRIP (a) RECEIVE X 65 130 20
PURWODADI 2 TSS 131 DTBRX DIRECT TRANSFER TRIP (b) RECEIVE X 65 131 20
PURWODADI 2 TSS 132 TTT TELEPROTECTION TRIP TRANSMIT X 65 132 20
PURWODADI 2 TSS 133 DZATX DISTANCE (a) RELAY TRANSMIT X 65 133 20
PURWODADI 2 TSS 134 DZBTX DISTANCE (b) RELAY TRANSMIT X 65 134 20
PURWODADI 2 TSS 135 DEATX DIRECTIONAL EARTH FAULT (a) RELAY TRANSMIT X 65 135 20
PURWODADI 2 TSS 136 DEBTX DIRECTIONAL EARTH FAULT (b) RELAY TRANSMIT X 65 136 20
PURWODADI 2 TSS 137 DTATX DIRECT TRANSFER TRIP (a) TRANSMIT X 65 137 20
PURWODADI 2 TSS 138 DTBTX DIRECT TRANSFER TRIP (b) TRANSMIT X 65 138 20
PURWODADI 2 TSS 142 P1CD CURRENT DEFFERENTIAL X 65 142 20
PURWODADI 2 TSS 143 CDAR CURRENT DIFFERENTIAL (a) PHASE R X 65 143 20
PURWODADI 2 TSS 144 CDAS CURRENT DIFFERENTIAL (a) PHASE S X 65 144 20
PURWODADI 2 TSS 145 CDAT CURRENT DIFFERENTIAL (a) PHASE T X 65 145 20
PURWODADI 2 TSS 146 CDBR CURRENT DIFFERENTIAL (b) PHASE R X 65 146 20
PURWODADI 2 TSS 147 CDBS CURRENT DIFFERENTIAL (b) PHASE S X 65 147 20
33 dari 71
-
PURWODADI 2 TSS 148 CDBT CURRENT DIFFERENTIAL (b) PHASE T X 65 148 20
PURWODADI 2 TSS 149 P1DEF DIRECTIONAL EARTH FAULT X 65 149 20
PURWODADI 2 TSS 150 DEFAR DIRECTIONAL EARTH FAULT (a) PHASE R X 65 150 20
PURWODADI 2 TSS 151 DEFAS DIRECTIONAL EARTH FAULT (a) PHASE S X 65 151 20
PURWODADI 2 TSS 152 DEFAT DIRECTIONAL EARTH FAULT (a) PHASE T X 65 152 20
PURWODADI 2 TSS 153 DEFBR DIRECTIONAL EARTH FAULT (b) PHASE R X 65 153 20
PURWODADI 2 TSS 154 DEFBS DIRECTIONAL EARTH FAULT (b) PHASE S X 65 154 20
PURWODADI 2 TSS 155 DEFBT DIRECTIONAL EARTH FAULT (b) PHASE T X 65 155 20
PURWODADI 2 TSS 158 P1Z1 DISTANCE PROTECTION ZONE 1 X 65 158 20
PURWODADI 2 TSS 159 DZ1AR DISTANCE (a) PHASE R ZONE 1 X 65 159 20
PURWODADI 2 TSS 160 DZ1AS DISTANCE (a) PHASE S ZONE 1 X 65 160 20
PURWODADI 2 TSS 161 DZ1AT DISTANCE (a) PHASE T ZONE 1 X 65 161 20
PURWODADI 2 TSS 162 DZ1BR DISTANCE (b) PHASE R ZONE 1 X 65 162 20
PURWODADI 2 TSS 163 DZ1BS DISTANCE (b) PHASE S ZONE 1 X 65 163 20
PURWODADI 2 TSS 164 DZ1BT DISTANCE (b) PHASE T ZONE 1 X 65 164 20
PURWODADI 2 TSS 165 P1Z2 DISTANCE PROTECTION ZONE 2 X 65 165 20
PURWODADI 2 TSS 166 DZ2AR DISTANCE (a) PHASE R ZONE 2 X 65 166 20
PURWODADI 2 TSS 167 DZ2AS DISTANCE (a) PHASE S ZONE 2 X 65 167 20
PURWODADI 2 TSS 168 DZ2AT DISTANCE (a) PHASE T ZONE 2 X 65 168 20
PURWODADI 2 TSS 169 DZ2BR DISTANCE (b) PHASE R ZONE 2 X 65 169 20
PURWODADI 2 TSS 170 DZ2BS DISTANCE (b) PHASE S ZONE 2 X 65 170 20
PURWODADI 2 TSS 171 DZ2BT DISTANCE (b) PHASE T ZONE 2 X 65 171 20
PURWODADI 2 TSS 172 P1Z3 DISTANCE PROTECTION ZONE 3 X 65 172 20
PURWODADI 2 TSS 173 DZ3AR DISTANCE (a) PHASE R ZONE 3 X 65 173 20
PURWODADI 2 TSS 174 DZ3AS DISTANCE (a) PHASE S ZONE 3 X 65 174 20
PURWODADI 2 TSS 175 DZ3AT DISTANCE (a) PHASE T ZONE 3 X 65 175 20
PURWODADI 2 TSS 176 DZ3BR DISTANCE (b) PHASE R ZONE 3 X 65 176 20
PURWODADI 2 TSS 177 DZ3BS DISTANCE (b) PHASE S ZONE 3 X 65 177 20
PURWODADI 2 TSS 178 DZ3BT DISTANCE (b) PHASE T ZONE 3 X 65 178 20
PURWODADI 2 TSS 179 P2GFR GROUND FAULT RELAY X X 65 179 20
34 dari 71
-
PURWODADI 2 TSS 180 P2OCR OVER CURRENT RELAY X X 65 180 20
PURWODADI 2 TSS 181 P3DTT DIRECT TRANSFER TRIP X 65 181 20
PURWODADI 2 TSS 183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE X 65 183 20
PURWODADI 2 TSS 184 SZPA SHORT ZONE PROTECTION (a) OPERATE X 65 184 20
PURWODADI 2 TSS 186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE X 65 186 20
PURWODADI 2 TSS 187 SZPB SHORT ZONE PROTECTION (b) OPERATE X 65 187 20
PURWODADI 2 TSS 188 CBTR CB TRIP X 65 188 20
PURWODADI 2 TSS 189 PHR TRIP PHASE R X 65 189 20
PURWODADI 2 TSS 190 PHS TRIP PHASE S X 65 190 20
PURWODADI 2 TSS 191 PHT TRIP PHASE T X 65 191 20
PURWODADI 2 TSS 193 SIB SOFTWARE INTERLOCKING BYPASS X 65 193 20
PURWODADI 2 TSS 194 IEDF IED FAULTY X 65 194 20
PURWODADI 2 TSS 195 SOTF SWITCH ON TO FAULT X 65 195 20
PURWODADI 2 134
SAYUNG 1 TM 2 V TEGANGAN X X 61 2 30
SAYUNG 1 TM 2 V TEGANGAN X X 61 2 31
SAYUNG 1 TM 2 V TEGANGAN X X 61 2 32
SAYUNG 1 TM 2 V TEGANGAN X X 61 2 33
SAYUNG 1 TM 3 I ARUS X X 61 3 30
SAYUNG 1 TM 3 I ARUS X X 61 3 31
SAYUNG 1 TM 3 I ARUS X X 61 3 32
SAYUNG 1 TM 3 I ARUS X X 61 3 33
SAYUNG 1 TM 4 P DAYA AKTIF X X 61 4 30
SAYUNG 1 TM 5 Q DAYA REAKTIF X X 61 5 30
SAYUNG 1 TM 7 CCB COUNTER OF CIRCUIT BREAKER X 61 7 30
SAYUNG 1 TM 9 PRES PRESSURE X 61 9 30
SAYUNG 1 TM 12 AMF AMPERES FAULT ( PER PHASE ) X 61 12 30
SAYUNG 1 TM 13 KWH KILOWATT HOUR X 61 13 30
SAYUNG 1 TM 14 KVARH KILOVAR HOUR X 61 14 30
SAYUNG 1 TM 16 CNTA COUNTER ARESTER X 61 16 30
35 dari 71
-
SAYUNG 1 RCD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 62 2 30
SAYUNG 1 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 62 3 31
SAYUNG 1 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 62 3 32
SAYUNG 1 RCD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X 62 4 30
SAYUNG 1 RCD 5 LR LOCAL REMOTE X 62 5 30
SAYUNG 1 RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X 62 9 30
SAYUNG 1 RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 62 13 30
SAYUNG 1 TSD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 64 2 30
SAYUNG 1 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 64 3 31
SAYUNG 1 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 64 3 32
SAYUNG 1 TSD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X X 64 4 30
SAYUNG 1 TSD 5 LR LOCAL REMOTE X X 64 5 30
SAYUNG 1 TSD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 64 9 30
SAYUNG 1 TSD 10 ES EARTH SWITCH CLOSED/OPENED **) X 64 10 30
SAYUNG 1 TSD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 64 13 30
SAYUNG 1 TSS 15 DFRF DISTURBANCE FAULT RECORDER FAULTY X 65 15 30
SAYUNG 1 TSS 16 ERF EVENT RECORDER FAILURE X 65 16 30
SAYUNG 1 TSS 20 AR CIRCUIT BREAKER AUTO RECLOSE X X 65 20 30
SAYUNG 1 TSS 21 ARO AUTO RECLOSE OFF X X 65 21 30
SAYUNG 1 TSS 22 BF BAY FAULT X 65 22 30
SAYUNG 1 TSS 23 VTF VOLTAGE TRANSFORMER FAILURE X 65 23 30
SAYUNG 1 TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 65 24 30
SAYUNG 1 TSS 25 DCF DC SUPPLY FAILURE X 65 25 30
SAYUNG 1 TSS 26 BRF BREAKER FAULT X 65 26 30
SAYUNG 1 TSS 27 LPA LOW PRESSURE ALARM X 65 27 30
SAYUNG 1 TSS 28 LPB LOW PRESSURE BLOCK X 65 28 30
SAYUNG 1 TSS 29 LPT LOW PRESSURE TRIP X 65 29 30
SAYUNG 1 TSS 30 PD POLE DISCREPANCY X 65 30 30
36 dari 71
-
SAYUNG 1 TSS 31 CBDF CIRCUIT BREAKER DRIVE FAILURE X 65 31 30
SAYUNG 1 TSS 32 TCS1 TRIP COIL SUPERVISORY 1 X 65 32 30
SAYUNG 1 TSS 33 TCS2 TRIP COIL SUPERVISORY 2 X 65 33 30
SAYUNG 1 TSS 34 CBM CIRCUIT BREAKER MAINTENANCE X 65 34 30
SAYUNG 1 TSS 39 CF CARRIER FAULTY X 65 39 30
SAYUNG 1 TSS 47 CSP CHECK SYNCHRONIZING IN PROGRESS X X 65 47 30
SAYUNG 1 TSS 49 PWF PILOT WIRE FAILURE X 65 49 30
SAYUNG 1 TSS 51 SYNF SYNCHRONIZING FAILURE X 65 51 30
SAYUNG 1 TSS 92 POT PROTECTION ON TEST X 65 92 30
SAYUNG 1 TSS 101 MTO MASTER TRIP OPERATE X 65 101 30
SAYUNG 1 TSS 102 UFR UNDER FREQUENCY RELAY OPERATE X 65 102 30
SAYUNG 1 TSS 103 UVR UNDER VOLTAGE RELAY OPERATE X 65 103 30
SAYUNG 1 TSS 104 OVR OVER VOLTAGE RELAY OPERATE X 65 104 30
SAYUNG 1 TSS 106 OCRF OVER CURRENT RELAY FAILURE X 65 106 30
SAYUNG 1 TSS 107 OVRF OVER VOLTAGE RELAY FAILURE X 65 107 30
SAYUNG 1 TSS 108 UVRF UNDER VOLTAGE RELAY FAILURE X 65 108 30
SAYUNG 1 TSS 109 GFRF GROUND FAULT RELAY FAILURE X 65 109 30
SAYUNG 1 TSS 110 DZAF DISTANCE RELAY (a) FAILURE X 65 110 30
SAYUNG 1 TSS 111 DZBF DISTANCE RELAY (b) FAILURE X 65 111 30
SAYUNG 1 TSS 112 DEFAF DIRECTIONAL EARTH FAULT (a) FAILURE X 65 112 30
SAYUNG 1 TSS 113 DEFBF DIRECTIONAL EARTH FAULT (b) FAILURE X 65 113 30
SAYUNG 1 TSS 114 CDAF CURRENT DIFFERENTIAL RELAY (a) FAILURE X 65 114 30
SAYUNG 1 TSS 115 CDBF CURRENT DIFFERENTIAL RELAY (b) FAILURE X 65 115 30
SAYUNG 1 TSS 116 TPAF TELEPROTECTION (a) FAILURE X 65 116 30
SAYUNG 1 TSS 117 TPBF TELEPROTECTION (b) FAILURE X 65 117 30
SAYUNG 1 TSS 123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE X 65 123 30
SAYUNG 1 TSS 124 SZPF SHORT ZONE PROTECTION FAILURE X 65 124 30
SAYUNG 1 TSS 125 TTR TELEPROTECTION TRIP RECEIVE X 65 125 30
SAYUNG 1 TSS 126 DZARX DISTANCE (a) RELAY RECEIVE X 65 126 30
SAYUNG 1 TSS 127 DZBRX DISTANCE (b) RELAY RECEIVE X 65 127 30
37 dari 71
-
SAYUNG 1 TSS 128 DEARX DIRECTIONAL EARTH FAULT (a) RELAY RECEIVE X 65 128 30
SAYUNG 1 TSS 129 DEBRX DIRECTIONAL EARTH FAULT (b) RELAY RECEIVE X 65 129 30
SAYUNG 1 TSS 130 DTARX DIRECT TRANSFER TRIP (a) RECEIVE X 65 130 30
SAYUNG 1 TSS 131 DTBRX DIRECT TRANSFER TRIP (b) RECEIVE X 65 131 30
SAYUNG 1 TSS 132 TTT TELEPROTECTION TRIP TRANSMIT X 65 132 30
SAYUNG 1 TSS 133 DZATX DISTANCE (a) RELAY TRANSMIT X 65 133 30
SAYUNG 1 TSS 134 DZBTX DISTANCE (b) RELAY TRANSMIT X 65 134 30
SAYUNG 1 TSS 135 DEATX DIRECTIONAL EARTH FAULT (a) RELAY TRANSMIT X 65 135 30
SAYUNG 1 TSS 136 DEBTX DIRECTIONAL EARTH FAULT (b) RELAY TRANSMIT X 65 136 30
SAYUNG 1 TSS 137 DTATX DIRECT TRANSFER TRIP (a) TRANSMIT X 65 137 30
SAYUNG 1 TSS 138 DTBTX DIRECT TRANSFER TRIP (b) TRANSMIT X 65 138 30
SAYUNG 1 TSS 142 P1CD CURRENT DEFFERENTIAL X 65 142 30
SAYUNG 1 TSS 143 CDAR CURRENT DIFFERENTIAL (a) PHASE R X 65 143 30
SAYUNG 1 TSS 144 CDAS CURRENT DIFFERENTIAL (a) PHASE S X 65 144 30
SAYUNG 1 TSS 145 CDAT CURRENT DIFFERENTIAL (a) PHASE T X 65 145 30
SAYUNG 1 TSS 146 CDBR CURRENT DIFFERENTIAL (b) PHASE R X 65 146 30
SAYUNG 1 TSS 147 CDBS CURRENT DIFFERENTIAL (b) PHASE S X 65 147 30
SAYUNG 1 TSS 148 CDBT CURRENT DIFFERENTIAL (b) PHASE T X 65 148 30
SAYUNG 1 TSS 149 P1DEF DIRECTIONAL EARTH FAULT X 65 149 30
SAYUNG 1 TSS 150 DEFAR DIRECTIONAL EARTH FAULT (a) PHASE R X 65 150 30
SAYUNG 1 TSS 151 DEFAS DIRECTIONAL EARTH FAULT (a) PHASE S X 65 151 30
SAYUNG 1 TSS 152 DEFAT DIRECTIONAL EARTH FAULT (a) PHASE T X 65 152 30
SAYUNG 1 TSS 153 DEFBR DIRECTIONAL EARTH FAULT (b) PHASE R X 65 153 30
SAYUNG 1 TSS 154 DEFBS DIRECTIONAL EARTH FAULT (b) PHASE S X 65 154 30
SAYUNG 1 TSS 155 DEFBT DIRECTIONAL EARTH FAULT (b) PHASE T X 65 155 30
SAYUNG 1 TSS 158 P1Z1 DISTANCE PROTECTION ZONE 1 X 65 158 30
SAYUNG 1 TSS 159 DZ1AR DISTANCE (a) PHASE R ZONE 1 X 65 159 30
SAYUNG 1 TSS 160 DZ1AS DISTANCE (a) PHASE S ZONE 1 X 65 160 30
38 dari 71
-
SAYUNG 1 TSS 161 DZ1AT DISTANCE (a) PHASE T ZONE 1 X 65 161 30
SAYUNG 1 TSS 162 DZ1BR DISTANCE (b) PHASE R ZONE 1 X 65 162 30
SAYUNG 1 TSS 163 DZ1BS DISTANCE (b) PHASE S ZONE 1 X 65 163 30
SAYUNG 1 TSS 164 DZ1BT DISTANCE (b) PHASE T ZONE 1 X 65 164 30
SAYUNG 1 TSS 165 P1Z2 DISTANCE PROTECTION ZONE 2 X 65 165 30
SAYUNG 1 TSS 166 DZ2AR DISTANCE (a) PHASE R ZONE 2 X 65 166 30
SAYUNG 1 TSS 167 DZ2AS DISTANCE (a) PHASE S ZONE 2 X 65 167 30
SAYUNG 1 TSS 168 DZ2AT DISTANCE (a) PHASE T ZONE 2 X 65 168 30
SAYUNG 1 TSS 169 DZ2BR DISTANCE (b) PHASE R ZONE 2 X 65 169 30
SAYUNG 1 TSS 170 DZ2BS DISTANCE (b) PHASE S ZONE 2 X 65 170 30
SAYUNG 1 TSS 171 DZ2BT DISTANCE (b) PHASE T ZONE 2 X 65 171 30
SAYUNG 1 TSS 172 P1Z3 DISTANCE PROTECTION ZONE 3 X 65 172 30
SAYUNG 1 TSS 173 DZ3AR DISTANCE (a) PHASE R ZONE 3 X 65 173 30
SAYUNG 1 TSS 174 DZ3AS DISTANCE (a) PHASE S ZONE 3 X 65 174 30
SAYUNG 1 TSS 175 DZ3AT DISTANCE (a) PHASE T ZONE 3 X 65 175 30
SAYUNG 1 TSS 176 DZ3BR DISTANCE (b) PHASE R ZONE 3 X 65 176 30
SAYUNG 1 TSS 177 DZ3BS DISTANCE (b) PHASE S ZONE 3 X 65 177 30
SAYUNG 1 TSS 178 DZ3BT DISTANCE (b) PHASE T ZONE 3 X 65 178 30
SAYUNG 1 TSS 179 P2GFR GROUND FAULT RELAY X X 65 179 30
SAYUNG 1 TSS 180 P2OCR OVER CURRENT RELAY X X 65 180 30
SAYUNG 1 TSS 181 P3DTT DIRECT TRANSFER TRIP X 65 181 30
SAYUNG 1 TSS 183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE X 65 183 30
SAYUNG 1 TSS 184 SZPA SHORT ZONE PROTECTION (a) OPERATE X 65 184 30
SAYUNG 1 TSS 186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE X 65 186 30
SAYUNG 1 TSS 187 SZPB SHORT ZONE PROTECTION (b) OPERATE X 65 187 30
SAYUNG 1 TSS 188 CBTR CB TRIP X 65 188 30
SAYUNG 1 TSS 189 PHR TRIP PHASE R X 65 189 30
SAYUNG 1 TSS 190 PHS TRIP PHASE S X 65 190 30
SAYUNG 1 TSS 191 PHT TRIP PHASE T X 65 191 30
SAYUNG 1 TSS 193 SIB SOFTWARE INTERLOCKING BYPASS X 65 193 30
39 dari 71
-
SAYUNG 1 TSS 194 IEDF IED FAULTY X 65 194 30
SAYUNG 1 TSS 195 SOTF SWITCH ON TO FAULT X 65 195 30
SAYUNG 1 134
SAYUNG 2 TM 2 V TEGANGAN X X 61 2 40
SAYUNG 2 TM 2 V TEGANGAN X X 61 2 41
SAYUNG 2 TM 2 V TEGANGAN X X 61 2 42
SAYUNG 2 TM 2 V TEGANGAN X X 61 2 43
SAYUNG 2 TM 3 I ARUS X X 61 3 40
SAYUNG 2 TM 3 I ARUS X X 61 3 41
SAYUNG 2 TM 3 I ARUS X X 61 3 42
SAYUNG 2 TM 3 I ARUS X X 61 3 43
SAYUNG 2 TM 4 P DAYA AKTIF X X 61 4 40
SAYUNG 2 TM 5 Q DAYA REAKTIF X X 61 5 40
SAYUNG 2 TM 7 CCB COUNTER OF CIRCUIT BREAKER X 61 7 40
SAYUNG 2 TM 9 PRES PRESSURE X 61 9 40
SAYUNG 2 TM 12 AMF AMPERES FAULT ( PER PHASE ) X 61 12 40
SAYUNG 2 TM 13 KWH KILOWATT HOUR X 61 13 40
SAYUNG 2 TM 14 KVARH KILOVAR HOUR X 61 14 40
SAYUNG 2 TM 16 CNTA COUNTER ARESTER X 61 16 40
SAYUNG 2 RCD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 62 2 40
SAYUNG 2 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 62 3 41
SAYUNG 2 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 62 3 42
SAYUNG 2 RCD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X 62 4 40
SAYUNG 2 RCD 5 LR LOCAL REMOTE X 62 5 40
SAYUNG 2 RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X 62 9 40
SAYUNG 2 RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 62 13 40
SAYUNG 2 TSD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 64 2 40
SAYUNG 2 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 64 3 41
SAYUNG 2 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED X X 64 3 42
40 dari 71
-
(BUS 2)
SAYUNG 2 TSD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X X 64 4 40
SAYUNG 2 TSD 5 LR LOCAL REMOTE X X 64 5 40
SAYUNG 2 TSD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 64 9 40
SAYUNG 2 TSD 10 ES EARTH SWITCH CLOSED/OPENED **) X 64 10 40
SAYUNG 2 TSD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 64 13 40
SAYUNG 2 TSS 15 DFRF DISTURBANCE FAULT RECORDER FAULTY X 65 15 40
SAYUNG 2 TSS 16 ERF EVENT RECORDER FAILURE X 65 16 40
SAYUNG 2 TSS 20 AR CIRCUIT BREAKER AUTO RECLOSE X X 65 20 40
SAYUNG 2 TSS 21 ARO AUTO RECLOSE OFF X X 65 21 40
SAYUNG 2 TSS 22 BF BAY FAULT X 65 22 40
SAYUNG 2 TSS 23 VTF VOLTAGE TRANSFORMER FAILURE X 65 23 40
SAYUNG 2 TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 65 24 40
SAYUNG 2 TSS 25 DCF DC SUPPLY FAILURE X 65 25 40
SAYUNG 2 TSS 26 BRF BREAKER FAULT X 65 26 40
SAYUNG 2 TSS 27 LPA LOW PRESSURE ALARM X 65 27 40
SAYUNG 2 TSS 28 LPB LOW PRESSURE BLOCK X 65 28 40
SAYUNG 2 TSS 29 LPT LOW PRESSURE TRIP X 65 29 40
SAYUNG 2 TSS 30 PD POLE DISCREPANCY X 65 30 40
SAYUNG 2 TSS 31 CBDF CIRCUIT BREAKER DRIVE FAILURE X 65 31 40
SAYUNG 2 TSS 32 TCS1 TRIP COIL SUPERVISORY 1 X 65 32 40
SAYUNG 2 TSS 33 TCS2 TRIP COIL SUPERVISORY 2 X 65 33 40
SAYUNG 2 TSS 34 CBM CIRCUIT BREAKER MAINTENANCE X 65 34 40
SAYUNG 2 TSS 39 CF CARRIER FAULTY X 65 39 40
SAYUNG 2 TSS 47 CSP CHECK SYNCHRONIZING IN PROGRESS X X 65 47 40
SAYUNG 2 TSS 49 PWF PILOT WIRE FAILURE X 65 49 40
SAYUNG 2 TSS 51 SYNF SYNCHRONIZING FAILURE X 65 51 40
SAYUNG 2 TSS 92 POT PROTECTION ON TEST X 65 92 40
SAYUNG 2 TSS 101 MTO MASTER TRIP OPERATE X 65 101 40
SAYUNG 2 TSS 102 UFR UNDER FREQUENCY RELAY OPERATE X 65 102 40
41 dari 71
-
SAYUNG 2 TSS 103 UVR UNDER VOLTAGE RELAY OPERATE X 65 103 40
SAYUNG 2 TSS 104 OVR OVER VOLTAGE RELAY OPERATE X 65 104 40
SAYUNG 2 TSS 106 OCRF OVER CURRENT RELAY FAILURE X 65 106 40
SAYUNG 2 TSS 107 OVRF OVER VOLTAGE RELAY FAILURE X 65 107 40
SAYUNG 2 TSS 108 UVRF UNDER VOLTAGE RELAY FAILURE X 65 108 40
SAYUNG 2 TSS 109 GFRF GROUND FAULT RELAY FAILURE X 65 109 40
SAYUNG 2 TSS 110 DZAF DISTANCE RELAY (a) FAILURE X 65 110 40
SAYUNG 2 TSS 111 DZBF DISTANCE RELAY (b) FAILURE X 65 111 40
SAYUNG 2 TSS 112 DEFAF DIRECTIONAL EARTH FAULT (a) FAILURE X 65 112 40
SAYUNG 2 TSS 113 DEFBF DIRECTIONAL EARTH FAULT (b) FAILURE X 65 113 40
SAYUNG 2 TSS 114 CDAF CURRENT DIFFERENTIAL RELAY (a) FAILURE X 65 114 40
SAYUNG 2 TSS 115 CDBF CURRENT DIFFERENTIAL RELAY (b) FAILURE X 65 115 40
SAYUNG 2 TSS 116 TPAF TELEPROTECTION (a) FAILURE X 65 116 40
SAYUNG 2 TSS 117 TPBF TELEPROTECTION (b) FAILURE X 65 117 40
SAYUNG 2 TSS 123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE X 65 123 40
SAYUNG 2 TSS 124 SZPF SHORT ZONE PROTECTION FAILURE X 65 124 40
SAYUNG 2 TSS 125 TTR TELEPROTECTION TRIP RECEIVE X 65 125 40
SAYUNG 2 TSS 126 DZARX DISTANCE (a) RELAY RECEIVE X 65 126 40
SAYUNG 2 TSS 127 DZBRX DISTANCE (b) RELAY RECEIVE X 65 127 40
SAYUNG 2 TSS 128 DEARX DIRECTIONAL EARTH FAULT (a) RELAY RECEIVE X 65 128 40
SAYUNG 2 TSS 129 DEBRX DIRECTIONAL EARTH FAULT (b) RELAY RECEIVE X 65 129 40
SAYUNG 2 TSS 130 DTARX DIRECT TRANSFER TRIP (a) RECEIVE X 65 130 40
SAYUNG 2 TSS 131 DTBRX DIRECT TRANSFER TRIP (b) RECEIVE X 65 131 40
SAYUNG 2 TSS 132 TTT TELEPROTECTION TRIP TRANSMIT X 65 132 40
SAYUNG 2 TSS 133 DZATX DISTANCE (a) RELAY TRANSMIT X 65 133 40
SAYUNG 2 TSS 134 DZBTX DISTANCE (b) RELAY TRANSMIT X 65 134 40
SAYUNG 2 TSS 135 DEATX DIRECTIONAL EARTH FAULT (a) RELAY TRANSMIT X 65 135 40
SAYUNG 2 TSS 136 DEBTX DIRECTIONAL EARTH FAULT (b) RELAY TRANSMIT X 65 136 40
42 dari 71
-
SAYUNG 2 TSS 137 DTATX DIRECT TRANSFER TRIP (a) TRANSMIT X 65 137 40
SAYUNG 2 TSS 138 DTBTX DIRECT TRANSFER TRIP (b) TRANSMIT X 65 138 40
SAYUNG 2 TSS 142 P1CD CURRENT DEFFERENTIAL X 65 142 40
SAYUNG 2 TSS 143 CDAR CURRENT DIFFERENTIAL (a) PHASE R X 65 143 40
SAYUNG 2 TSS 144 CDAS CURRENT DIFFERENTIAL (a) PHASE S X 65 144 40
SAYUNG 2 TSS 145 CDAT CURRENT DIFFERENTIAL (a) PHASE T X 65 145 40
SAYUNG 2 TSS 146 CDBR CURRENT DIFFERENTIAL (b) PHASE R X 65 146 40
SAYUNG 2 TSS 147 CDBS CURRENT DIFFERENTIAL (b) PHASE S X 65 147 40
SAYUNG 2 TSS 148 CDBT CURRENT DIFFERENTIAL (b) PHASE T X 65 148 40
SAYUNG 2 TSS 149 P1DEF DIRECTIONAL EARTH FAULT X 65 149 40
SAYUNG 2 TSS 150 DEFAR DIRECTIONAL EARTH FAULT (a) PHASE R X 65 150 40
SAYUNG 2 TSS 151 DEFAS DIRECTIONAL EARTH FAULT (a) PHASE S X 65 151 40
SAYUNG 2 TSS 152 DEFAT DIRECTIONAL EARTH FAULT (a) PHASE T X 65 152 40
SAYUNG 2 TSS 153 DEFBR DIRECTIONAL EARTH FAULT (b) PHASE R X 65 153 40
SAYUNG 2 TSS 154 DEFBS DIRECTIONAL EARTH FAULT (b) PHASE S X 65 154 40
SAYUNG 2 TSS 155 DEFBT DIRECTIONAL EARTH FAULT (b) PHASE T X 65 155 40
SAYUNG 2 TSS 158 P1Z1 DISTANCE PROTECTION ZONE 1 X 65 158 40
SAYUNG 2 TSS 159 DZ1AR DISTANCE (a) PHASE R ZONE 1 X 65 159 40
SAYUNG 2 TSS 160 DZ1AS DISTANCE (a) PHASE S ZONE 1 X 65 160 40
SAYUNG 2 TSS 161 DZ1AT DISTANCE (a) PHASE T ZONE 1 X 65 161 40
SAYUNG 2 TSS 162 DZ1BR DISTANCE (b) PHASE R ZONE 1 X 65 162 40
SAYUNG 2 TSS 163 DZ1BS DISTANCE (b) PHASE S ZONE 1 X 65 163 40
SAYUNG 2 TSS 164 DZ1BT DISTANCE (b) PHASE T ZONE 1 X 65 164 40
SAYUNG 2 TSS 165 P1Z2 DISTANCE PROTECTION ZONE 2 X 65 165 40
SAYUNG 2 TSS 166 DZ2AR DISTANCE (a) PHASE R ZONE 2 X 65 166 40
SAYUNG 2 TSS 167 DZ2AS DISTANCE (a) PHASE S ZONE 2 X 65 167 40
SAYUNG 2 TSS 168 DZ2AT DISTANCE (a) PHASE T ZONE 2 X 65 168 40
SAYUNG 2 TSS 169 DZ2BR DISTANCE (b) PHASE R ZONE 2 X 65 169 40
SAYUNG 2 TSS 170 DZ2BS DISTANCE (b) PHASE S ZONE 2 X 65 170 40
SAYUNG 2 TSS 171 DZ2BT DISTANCE (b) PHASE T ZONE 2 X 65 171 40
43 dari 71
-
SAYUNG 2 TSS 172 P1Z3 DISTANCE PROTECTION ZONE 3 X 65 172 40
SAYUNG 2 TSS 173 DZ3AR DISTANCE (a) PHASE R ZONE 3 X 65 173 40
SAYUNG 2 TSS 174 DZ3AS DISTANCE (a) PHASE S ZONE 3 X 65 174 40
SAYUNG 2 TSS 175 DZ3AT DISTANCE (a) PHASE T ZONE 3 X 65 175 40
SAYUNG 2 TSS 176 DZ3BR DISTANCE (b) PHASE R ZONE 3 X 65 176 40
SAYUNG 2 TSS 177 DZ3BS DISTANCE (b) PHASE S ZONE 3 X 65 177 40
SAYUNG 2 TSS 178 DZ3BT DISTANCE (b) PHASE T ZONE 3 X 65 178 40
SAYUNG 2 TSS 179 P2GFR GROUND FAULT RELAY X X 65 179 40
SAYUNG 2 TSS 180 P2OCR OVER CURRENT RELAY X X 65 180 40
SAYUNG 2 TSS 181 P3DTT DIRECT TRANSFER TRIP X 65 181 40
SAYUNG 2 TSS 183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE X 65 183 40
SAYUNG 2 TSS 184 SZPA SHORT ZONE PROTECTION (a) OPERATE X 65 184 40
SAYUNG 2 TSS 186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE X 65 186 40
SAYUNG 2 TSS 187 SZPB SHORT ZONE PROTECTION (b) OPERATE X 65 187 40
SAYUNG 2 TSS 188 CBTR CB TRIP X 65 188 40
SAYUNG 2 TSS 189 PHR TRIP PHASE R X 65 189 40
SAYUNG 2 TSS 190 PHS TRIP PHASE S X 65 190 40
SAYUNG 2 TSS 191 PHT TRIP PHASE T X 65 191 40
SAYUNG 2 TSS 193 SIB SOFTWARE INTERLOCKING BYPASS X 65 193 40
SAYUNG 2 TSS 194 IEDF IED FAULTY X 65 194 40
SAYUNG 2 TSS 195 SOTF SWITCH ON TO FAULT X 65 195 40
SAYUNG 2 134
JEPARA 1 TM 2 V TEGANGAN X X 61 2 50
JEPARA 1 TM 2 V TEGANGAN X X 61 2 51
JEPARA 1 TM 2 V TEGANGAN X X 61 2 52
JEPARA 1 TM 2 V TEGANGAN X X 61 2 53
JEPARA 1 TM 3 I ARUS X X 61 3 50
JEPARA 1 TM 3 I ARUS X X 61 3 51
JEPARA 1 TM 3 I ARUS X X 61 3 52
JEPARA 1 TM 3 I ARUS X X 61 3 53
44 dari 71
-
JEPARA 1 TM 4 P DAYA AKTIF X X 61 4 50
JEPARA 1 TM 5 Q DAYA REAKTIF X X 61 5 50
JEPARA 1 TM 7 CCB COUNTER OF CIRCUIT BREAKER X 61 7 50
JEPARA 1 TM 9 PRES PRESSURE X 61 9 50
JEPARA 1 TM 12 AMF AMPERES FAULT ( PER PHASE ) X 61 12 50
JEPARA 1 TM 13 KWH KILOWATT HOUR X 61 13 50
JEPARA 1 TM 14 KVARH KILOVAR HOUR X 61 14 50
JEPARA 1 TM 16 CNTA COUNTER ARESTER X 61 16 50
JEPARA 1 RCD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 62 2 50
JEPARA 1 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 62 3 51
JEPARA 1 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 62 3 52
JEPARA 1 RCD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X 62 4 50
JEPARA 1 RCD 5 LR LOCAL REMOTE X 62 5 50
JEPARA 1 RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X 62 9 50
JEPARA 1 RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 62 13 50
JEPARA 1 TSD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 64 2 50
JEPARA 1 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 64 3 51
JEPARA 1 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 64 3 52
JEPARA 1 TSD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X X 64 4 50
JEPARA 1 TSD 5 LR LOCAL REMOTE X X 64 5 50
JEPARA 1 TSD 9 CSO CHECK SYNCHRONIZING OVERRIDE X X 64 9 50
JEPARA 1 TSD 10 ES EARTH SWITCH CLOSED/OPENED **) X 64 10 50
JEPARA 1 TSD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 64 13 50
JEPARA 1 TSS 15 DFRF DISTURBANCE FAULT RECORDER FAULTY X 65 15 50
JEPARA 1 TSS 16 ERF EVENT RECORDER FAILURE X 65 16 50
JEPARA 1 TSS 20 AR CIRCUIT BREAKER AUTO RECLOSE X X 65 20 50
JEPARA 1 TSS 21 ARO AUTO RECLOSE OFF X X 65 21 50
JEPARA 1 TSS 22 BF BAY FAULT X 65 22 50
45 dari 71
-
JEPARA 1 TSS 23 VTF VOLTAGE TRANSFORMER FAILURE X 65 23 50
JEPARA 1 TSS 24 DSDF DISCONNECTING SWITCH DRIVING FAULT X 65 24 50
JEPARA 1 TSS 25 DCF DC SUPPLY FAILURE X 65 25 50
JEPARA 1 TSS 26 BRF BREAKER FAULT X 65 26 50
JEPARA 1 TSS 27 LPA LOW PRESSURE ALARM X 65 27 50
JEPARA 1 TSS 28 LPB LOW PRESSURE BLOCK X 65 28 50
JEPARA 1 TSS 29 LPT LOW PRESSURE TRIP X 65 29 50
JEPARA 1 TSS 30 PD POLE DISCREPANCY X 65 30 50
JEPARA 1 TSS 31 CBDF CIRCUIT BREAKER DRIVE FAILURE X 65 31 50
JEPARA 1 TSS 32 TCS1 TRIP COIL SUPERVISORY 1 X 65 32 50
JEPARA 1 TSS 33 TCS2 TRIP COIL SUPERVISORY 2 X 65 33 50
JEPARA 1 TSS 34 CBM CIRCUIT BREAKER MAINTENANCE X 65 34 50
JEPARA 1 TSS 39 CF CARRIER FAULTY X 65 39 50
JEPARA 1 TSS 47 CSP CHECK SYNCHRONIZING IN PROGRESS X X 65 47 50
JEPARA 1 TSS 49 PWF PILOT WIRE FAILURE X 65 49 50
JEPARA 1 TSS 51 SYNF SYNCHRONIZING FAILURE X 65 51 50
JEPARA 1 TSS 92 POT PROTECTION ON TEST X 65 92 50
JEPARA 1 TSS 101 MTO MASTER TRIP OPERATE X 65 101 50
JEPARA 1 TSS 102 UFR UNDER FREQUENCY RELAY OPERATE X 65 102 50
JEPARA 1 TSS 103 UVR UNDER VOLTAGE RELAY OPERATE X 65 103 50
JEPARA 1 TSS 104 OVR OVER VOLTAGE RELAY OPERATE X 65 104 50
JEPARA 1 TSS 106 OCRF OVER CURRENT RELAY FAILURE X 65 106 50
JEPARA 1 TSS 107 OVRF OVER VOLTAGE RELAY FAILURE X 65 107 50
JEPARA 1 TSS 108 UVRF UNDER VOLTAGE RELAY FAILURE X 65 108 50
JEPARA 1 TSS 109 GFRF GROUND FAULT RELAY FAILURE X 65 109 50
JEPARA 1 TSS 110 DZAF DISTANCE RELAY (a) FAILURE X 65 110 50
JEPARA 1 TSS 111 DZBF DISTANCE RELAY (b) FAILURE X 65 111 50
JEPARA 1 TSS 112 DEFAF DIRECTIONAL EARTH FAULT (a) FAILURE X 65 112 50
JEPARA 1 TSS 113 DEFBF DIRECTIONAL EARTH FAULT (b) FAILURE X 65 113 50
JEPARA 1 TSS 114 CDAF CURRENT DIFFERENTIAL RELAY (a) FAILURE X 65 114 50
46 dari 71
-
JEPARA 1 TSS 115 CDBF CURRENT DIFFERENTIAL RELAY (b) FAILURE X 65 115 50
JEPARA 1 TSS 116 TPAF TELEPROTECTION (a) FAILURE X 65 116 50
JEPARA 1 TSS 117 TPBF TELEPROTECTION (b) FAILURE X 65 117 50
JEPARA 1 TSS 123 RCBF RELAY CIRCUIT BREAKER FAIL FAILURE X 65 123 50
JEPARA 1 TSS 124 SZPF SHORT ZONE PROTECTION FAILURE X 65 124 50
JEPARA 1 TSS 125 TTR TELEPROTECTION TRIP RECEIVE X 65 125 50
JEPARA 1 TSS 126 DZARX DISTANCE (a) RELAY RECEIVE X 65 126 50
JEPARA 1 TSS 127 DZBRX DISTANCE (b) RELAY RECEIVE X 65 127 50
JEPARA 1 TSS 128 DEARX DIRECTIONAL EARTH FAULT (a) RELAY RECEIVE X 65 128 50
JEPARA 1 TSS 129 DEBRX DIRECTIONAL EARTH FAULT (b) RELAY RECEIVE X 65 129 50
JEPARA 1 TSS 130 DTARX DIRECT TRANSFER TRIP (a) RECEIVE X 65 130 50
JEPARA 1 TSS 131 DTBRX DIRECT TRANSFER TRIP (b) RECEIVE X 65 131 50
JEPARA 1 TSS 132 TTT TELEPROTECTION TRIP TRANSMIT X 65 132 50
JEPARA 1 TSS 133 DZATX DISTANCE (a) RELAY TRANSMIT X 65 133 50
JEPARA 1 TSS 134 DZBTX DISTANCE (b) RELAY TRANSMIT X 65 134 50
JEPARA 1 TSS 135 DEATX DIRECTIONAL EARTH FAULT (a) RELAY TRANSMIT X 65 135 50
JEPARA 1 TSS 136 DEBTX DIRECTIONAL EARTH FAULT (b) RELAY TRANSMIT X 65 136 50
JEPARA 1 TSS 137 DTATX DIRECT TRANSFER TRIP (a) TRANSMIT X 65 137 50
JEPARA 1 TSS 138 DTBTX DIRECT TRANSFER TRIP (b) TRANSMIT X 65 138 50
JEPARA 1 TSS 142 P1CD CURRENT DEFFERENTIAL X 65 142 50
JEPARA 1 TSS 143 CDAR CURRENT DIFFERENTIAL (a) PHASE R X 65 143 50
JEPARA 1 TSS 144 CDAS CURRENT DIFFERENTIAL (a) PHASE S X 65 144 50
JEPARA 1 TSS 145 CDAT CURRENT DIFFERENTIAL (a) PHASE T X 65 145 50
JEPARA 1 TSS 146 CDBR CURRENT DIFFERENTIAL (b) PHASE R X 65 146 50
JEPARA 1 TSS 147 CDBS CURRENT DIFFERENTIAL (b) PHASE S X 65 147 50
JEPARA 1 TSS 148 CDBT CURRENT DIFFERENTIAL (b) PHASE T X 65 148 50
JEPARA 1 TSS 149 P1DEF DIRECTIONAL EARTH FAULT X 65 149 50
JEPARA 1 TSS 150 DEFAR DIRECTIONAL EARTH FAULT (a) PHASE R X 65 150 50
47 dari 71
-
JEPARA 1 TSS 151 DEFAS DIRECTIONAL EARTH FAULT (a) PHASE S X 65 151 50
JEPARA 1 TSS 152 DEFAT DIRECTIONAL EARTH FAULT (a) PHASE T X 65 152 50
JEPARA 1 TSS 153 DEFBR DIRECTIONAL EARTH FAULT (b) PHASE R X 65 153 50
JEPARA 1 TSS 154 DEFBS DIRECTIONAL EARTH FAULT (b) PHASE S X 65 154 50
JEPARA 1 TSS 155 DEFBT DIRECTIONAL EARTH FAULT (b) PHASE T X 65 155 50
JEPARA 1 TSS 158 P1Z1 DISTANCE PROTECTION ZONE 1 X 65 158 50
JEPARA 1 TSS 159 DZ1AR DISTANCE (a) PHASE R ZONE 1 X 65 159 50
JEPARA 1 TSS 160 DZ1AS DISTANCE (a) PHASE S ZONE 1 X 65 160 50
JEPARA 1 TSS 161 DZ1AT DISTANCE (a) PHASE T ZONE 1 X 65 161 50
JEPARA 1 TSS 162 DZ1BR DISTANCE (b) PHASE R ZONE 1 X 65 162 50
JEPARA 1 TSS 163 DZ1BS DISTANCE (b) PHASE S ZONE 1 X 65 163 50
JEPARA 1 TSS 164 DZ1BT DISTANCE (b) PHASE T ZONE 1 X 65 164 50
JEPARA 1 TSS 165 P1Z2 DISTANCE PROTECTION ZONE 2 X 65 165 50
JEPARA 1 TSS 166 DZ2AR DISTANCE (a) PHASE R ZONE 2 X 65 166 50
JEPARA 1 TSS 167 DZ2AS DISTANCE (a) PHASE S ZONE 2 X 65 167 50
JEPARA 1 TSS 168 DZ2AT DISTANCE (a) PHASE T ZONE 2 X 65 168 50
JEPARA 1 TSS 169 DZ2BR DISTANCE (b) PHASE R ZONE 2 X 65 169 50
JEPARA 1 TSS 170 DZ2BS DISTANCE (b) PHASE S ZONE 2 X 65 170 50
JEPARA 1 TSS 171 DZ2BT DISTANCE (b) PHASE T ZONE 2 X 65 171 50
JEPARA 1 TSS 172 P1Z3 DISTANCE PROTECTION ZONE 3 X 65 172 50
JEPARA 1 TSS 173 DZ3AR DISTANCE (a) PHASE R ZONE 3 X 65 173 50
JEPARA 1 TSS 174 DZ3AS DISTANCE (a) PHASE S ZONE 3 X 65 174 50
JEPARA 1 TSS 175 DZ3AT DISTANCE (a) PHASE T ZONE 3 X 65 175 50
JEPARA 1 TSS 176 DZ3BR DISTANCE (b) PHASE R ZONE 3 X 65 176 50
JEPARA 1 TSS 177 DZ3BS DISTANCE (b) PHASE S ZONE 3 X 65 177 50
JEPARA 1 TSS 178 DZ3BT DISTANCE (b) PHASE T ZONE 3 X 65 178 50
JEPARA 1 TSS 179 P2GFR GROUND FAULT RELAY X X 65 179 50
JEPARA 1 TSS 180 P2OCR OVER CURRENT RELAY X X 65 180 50
JEPARA 1 TSS 181 P3DTT DIRECT TRANSFER TRIP X 65 181 50
JEPARA 1 TSS 183 CBFA CIRCUIT BREAKER FAILURE (a) OPERATE X 65 183 50
48 dari 71
-
JEPARA 1 TSS 184 SZPA SHORT ZONE PROTECTION (a) OPERATE X 65 184 50
JEPARA 1 TSS 186 CBFB CIRCUIT BREAKER FAILURE (b) OPERATE X 65 186 50
JEPARA 1 TSS 187 SZPB SHORT ZONE PROTECTION (b) OPERATE X 65 187 50
JEPARA 1 TSS 188 CBTR CB TRIP X 65 188 50
JEPARA 1 TSS 189 PHR TRIP PHASE R X 65 189 50
JEPARA 1 TSS 190 PHS TRIP PHASE S X 65 190 50
JEPARA 1 TSS 191 PHT TRIP PHASE T X 65 191 50
JEPARA 1 TSS 193 SIB SOFTWARE INTERLOCKING BYPASS X 65 193 50
JEPARA 1 TSS 194 IEDF IED FAULTY X 65 194 50
JEPARA 1 TSS 195 SOTF SWITCH ON TO FAULT X 65 195 50
JEPARA 1 134
JEPARA 2 TM 2 V TEGANGAN X X 61 2 60
JEPARA 2 TM 2 V TEGANGAN X X 61 2 61
JEPARA 2 TM 2 V TEGANGAN X X 61 2 62
JEPARA 2 TM 2 V TEGANGAN X X 61 2 63
JEPARA 2 TM 3 I ARUS X X 61 3 60
JEPARA 2 TM 3 I ARUS X X 61 3 61
JEPARA 2 TM 3 I ARUS X X 61 3 62
JEPARA 2 TM 3 I ARUS X X 61 3 63
JEPARA 2 TM 4 P DAYA AKTIF X X 61 4 60
JEPARA 2 TM 5 Q DAYA REAKTIF X X 61 5 60
JEPARA 2 TM 7 CCB COUNTER OF CIRCUIT BREAKER X 61 7 60
JEPARA 2 TM 9 PRES PRESSURE X 61 9 60
JEPARA 2 TM 12 AMF AMPERES FAULT ( PER PHASE ) X 61 12 60
JEPARA 2 TM 13 KWH KILOWATT HOUR X 61 13 60
JEPARA 2 TM 14 KVARH KILOVAR HOUR X 61 14 60
JEPARA 2 TM 16 CNTA COUNTER ARESTER X 61 16 60
JEPARA 2 RCD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 62 2 60
JEPARA 2 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 62 3 61
49 dari 71
-
JEPARA 2 RCD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 2) X X 62 3 62
JEPARA 2 RCD 4 LI LINE ISOLATOR SWITCH CLOSED/OPENED X 62 4 60
JEPARA 2 RCD 5 LR LOCAL REMOTE X 62 5 60
JEPARA 2 RCD 9 CSO CHECK SYNCHRONIZING OVERRIDE X 62 9 60
JEPARA 2 RCD 13 SAM SYNCHRONIZATION AUTO/MANUAL X 62 13 60
JEPARA 2 TSD 2 CB CIRCUIT BREAKER CLOSED/OPENED X X 64 2 60
JEPARA 2 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (BUS 1) X X 64 3 61
JEPARA 2 TSD 3 BI BUS ISOLATOR SWITCH CLOSED/OPENED (