Post on 26-Apr-2023
APPLICATION FOR HCAI SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)
OFFICE USE ONLY
APPLICATION #: OSP-0297
HCAI Special Seismic Certification Preapproval (OSP)
Type: New X Renewal
Manufacturer Information
Manufacturer: Daikin North America, LLC
Manufacturer's Technical Representative: Caglar Oburoglu
Mailing Address: Daikin Texas Technology Park, 19001 Kerm, Waller, TX 77484
Telephone: (713) 861-2500 Email: caglar.oburoglu@daikincomfort.com
Product Information
Product Name:
Product Type:
Product Model Number:
General Description:
Mounting Description:
Air Conditioning Units
Air Conditioning Units - Split
Varies, see attachment.
Indoor and outdoor heating and cooling units steel enclosures.
Rigid base mounted, rigid wall mounted, and ceiling suspended.
Applicant Information
Applicant Company Name: Structural Integrity Associates, Inc. dba TRU Compliance
Contact Person: Katie Braman
Mailing Address: 5215 Hellyer Ave., Suite 210, San Jose, CA 95138
kbraman@structint.comEmail:(844) 878-0200Telephone:
Title: Program Manager, TRU Compliance
Tested Seismic Enhancements: Seismic enhancements made to the test units and/or modifications required to address anomalies during the tests shall be incorporated into the production units.
DEPARTMENT OF HEALTH CARE ACCESS AND INFORMATIONFACILITIES DEVELOPMENT DIVISION
05/17/2022
OSP-0297
Page 1 of 99
OSP-0297
Mohammad Karim
05/17/2022
Company Name: STRUCTURAL INTEGRITY ASSOCIATES, INC.
Name: Andrew Coughlin
Mailing Address: 5215 Hellyer Ave, Suite 101, San Jose, CA 95138-1025
acoughlin@structint.comEmail:(415) 635-8461Telephone:
California Licensed Structural Engineer Responsible for the Engineering and Test Report(s)
S6082California License Number:
Certification Method
GR-63-Core
Other (Please Specify):
ICC-ES AC156X IEEE 344 IEEE 693 NEBS 3
Testing Laboratory
Company Name: CLARK TESTING LABORATORY, INC.
Contact Person: Devon Lohr
Mailing Address: 1801 Route 51, Jefferson Hills PA 15025
dlohr@clarktesting.comEmail:(412) 387-1004Telephone:
Company Name: ENVIRONMENTAL TESTING LABORATORIES, INC. (ETL)
Contact Person: Jeremy Lange
Mailing Address: 11034 Indian Trail, Dallas TX 75229-3513
Jeremy@etldallas.comEmail:(972) 247-9657Telephone:
Company Name: QUALTECH/CURTISS WRIGHT/TRENTEC
Contact Person: Jerry Newberry
Mailing Address: 4600 East Tech Drive, Cincinnati OH 45245
jnewberry@curtisswright.comEmail:(513) 528-7900Telephone:
DEPARTMENT OF HEALTH CARE ACCESS AND INFORMATIONFACILITIES DEVELOPMENT DIVISION
05/17/2022
OSP-0297
Page 2 of 99
OSP-0297
Mohammad Karim
05/17/2022
HCAI Approval (For Office Use Only) - Approval Expires on 05/17/2028
Date: 5/17/2022
Name: Mohammad Karim Title: Supervisor, Health Facilities Review
Special Seismic Certification Valid Up to: SDS (g) = See Above
Condition of Approval (if applicable):
z/h = See Above
1.50 (SDS = 2.00, z/h = 1); 1.13 (SDS = 2.50, z/h = 0)
Seismic Parameters
Design Basis of Equipment or Components (Fp/Wp) =
SDS (Design spectral response acceleration at short period, g) =
ap (Amplification factor) =
Rp (Response modification factor) =
Ω0 (System overstrength factor) =
Ip (Importance factor) =
z/h (Height ratio factor) =
Natural frequencies (Hz) =
Overall dimensions and weight =
2.00 (z/h = 1); 2.50 (z/h = 0)
2.5
6.0
2.0
1.5
1 and 0
See Attachment
See Attachment
DEPARTMENT OF HEALTH CARE ACCESS AND INFORMATIONFACILITIES DEVELOPMENT DIVISION
05/17/2022
OSP-0297
Page 3 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
11.3 30.1 21.6 75 1
11.2 31.3 22.4 99 Interp.
11.3 30.1 21.6 75 Interp.
11.2 31.3 22.4 99 Interp.
11.8 32.5 28.9 104 Interp.
11.2 31.3 22.4 99 Interp.
11.8 32.5 28.9 104 Interp.
12.6 35.4 30.3 159 2
12.6 37.0 38.9 179 Interp.
12.6 37.0 38.9 179 Interp.
12.6 37.0 38.9 179 Interp.
12.6 37.0 38.9 179 3
2Requires mounting w/ (4) 1/16”x1-1/2” angled aluminum straps approximately 30˚relative to vertical surface of the unit with (2)
#10 SMS to top of unit & 1/4ӯ bolt to floor
1Requires seismic enhancements: (4) ties from grille to unit frame, ties made of stainless steel 15" length by 3/16" width.
RKS36_VJU1,2
RXS36_VJU1,2
Outdoor Heat Pump
(Split System,
Quaternity, SkyAir)
9,000 to 36,000
BTU/hr; Qualified
design categories: L
RKS30_VJU1,2
RXS30_VJU1,2
RXS18_VJU1
RXS24_VJU1
RXS15_VJU1
RXG15_VJU1
RXS12_VJU1
RXG12_VJU1
RXS09_VJU1
RXG09_VJU1
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 4 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
30.2 36.7 66.7 435 27
30.2 36.7 66.7 451 Interp.
30.2 48.9 66.7 525 Interp.
30.2 48.9 66.7 553 Interp.
30.2 48.9 66.7 528 Interp.
30.2 48.9 66.7 556 Interp.
30.2 48.9 66.7 695 Interp.
30.2 48.9 66.7 709 Interp.
30.2 48.9 66.7 695 Interp.
30.2 48.9 66.7 709 28
30.2 85.6 66.7 963 Interp.
30.2 85.6 66.7 1007 Interp.
30.2 97.8 66.7 1053 Interp.
30.2 60.4 66.7 133 Interp.
30.2 97.8 66.7 1056 Interp.
30.2 97.8 66.7 1112 Interp.
30.2 97.8 66.7 1223 Interp.
30.2 97.8 66.7 1265 Interp.
30.2 97.8 66.7 1390 Interp.
30.2 97.8 66.7 1418 Interp.
30.2 97.8 66.7 1390 Interp.
30.2 97.8 66.7 1418 Interp.
RXYQ288_TJ_1 2 x RXYQ144
RXYQ288_YD_1 2 x RXYQ144
RXYQ264_TJ_1 RXYQ144 + RXYQ120
RXYQ264_YD_1 RXYQ144 + RXYQ120
RXYQ312_TJ_1 RXYQ168 + RXYQ144
RXYQ312_YD_1 RXYQ168 + RXYQ144
2 x RXYQ120RXYQ240_YD_1
RXYQ120_TJ_1
RXYQ120_YD_1
RXYQ96_TJ_1
RXYQ96_YD_1
RXYQ216_TJ_1 RXYQ120 + RXYQ96
RXYQ72_TJ_
RXYQ72_YD_
RXYQ144_TJ_1
RXYQ144_YD_1
RXYQ240_TJ_1 2 x RXYQ120
RXYQ216_YD_1 RXYQ120 + RXYQ96
Outdoor Heat Pump
(VRV) 72,000 to
408,000 BTU/hr
(cooling capacity);
Qualified design
categories: T, TA, XA2
RXYQ192_TJ_1 RXYQ120 + RXYQ72
RXYQ192_YD_1 RXYQ120 + RXYQ72
RXYQ168_TJ_1
RXYQ168_YD_1
1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)2Qualified design category X, TA , and XA differ only in coil color.
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 5 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
30.2 97.8 67 1418 Interp.
30.2 171.1 67 1926 Interp.
30.2 146.6 67 1668 Interp.
30.2 146.6 67 2085 Interp.
30.2 146.6 67 1818 Interp.
30.2 183.3 67 2186 Interp.
30.2 146.6 67 1971 Interp.
30.2 183.3 67 2186 Interp.
30.2 36.7 66.7 507 29
30.2 36.7 66.7 527 Interp.
30.2 48.9 66.7 703 Interp.
30.2 48.9 66.7 717 Interp.
30.2 48.9 66.7 703 Interp.
30.2 48.9 66.7 717 Interp.
30.2 48.9 66.7 780 Interp.
30.2 48.9 66.7 794 Interp.
30.2 48.9 66.7 780 Interp.
30.2 48.9 66.7 794 30
30.2 85.6 66.7 1210 Interp.
30.2 85.6 66.7 1244 Interp.
30.2 97.8 66.7 1406 Interp.
30.2 97.8 66.7 1406 Interp.
REYQ216_ATJ_1
2 x RXYQ168
RXYQ408_TJ_1 RXYQ168 + RXYQ144 + RXYQ96
RXYQ408_YD_1 RXYQ168 + RXYQ144 + RXYQ96
REYQ72_ATJ_
RXYQ336_YD_1 2 x RXYQ168
RXYQ360_TJ_1 3 x RXYQ120
RXYQ168 + RXYQ120 + RXYQ96
RXYQ384_YD_1 RXYQ168 + RXYQ120 + RXYQ96
REYQ120 + REYQ96
REYQ216_AYD_1 REYQ120 + REYQ96
REYQ72_AYD_
REYQ96_ATJ_1
REYQ96_AYD_1
REYQ120_ATJ_1
3 x RXYQ120
RXYQ384_TJ_1
RXYQ336_TJ_1
REYQ120 + REYQ72
REYQ120_AYD_1
REYQ144_ATJ_1
REYQ144_AYD_1
REYQ168_ATJ_1
REYQ168_AYD_1
REYQ192_ATJ_1 REYQ120 + REYQ72
REYQ192_AYD_1
RXYQ360_YD_1
1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)2Qualified design category X, TA , and XA differ only in coil color.
Outdoor Heat
Recovery Units (VRV
IV) 72,000 to 456,000
BTU/hr (cooling
capacity);
Qualified design
categories: T
Outdoor Heat Pump
(VRV) 72,000 to
408,000 BTU/hr
(cooling capacity);
Qualified design
categories: T, TA, XA2
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 6 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
30.2 97.8 66.7 1483 Interp.
30.2 97.8 66.7 1511 Interp.
30.2 97.8 66.7 1483 Interp.
30.2 97.8 66.7 1511 Interp.
30.2 97.8 66.7 1560 Interp.
30.2 97.8 66.7 1588 Interp.
30.2 97.8 66.7 1560 Interp.
30.2 97.8 66.7 1588 Interp.
30.2 97.8 66.7 1560 Interp.
30.2 97.8 66.7 1588 Interp.
30.2 149.7 66.7 2109 Interp.
30.2 149.7 66.7 2151 Interp.
30.2 149.7 66.7 2186 Interp.
30.2 149.7 66.7 2228 Interp.
30.2 149.7 66.7 2340 Interp.
30.2 149.7 66.7 2305 Interp.
30.2 149.7 66.7 2340 Interp.
30.2 149.7 66.7 2382 Interp.
30.2 149.7 66.7 2340 Interp.
30.2 149.7 66.7 2382 Interp.
REYQ240_AYD_1 REYQ144 + REYQ96
REYQ336_ATJ_1 2 x REYQ168
2 x REYQ168
REYQ360_ATJ_1 3 x REYQ120
REYQ240_ATJ_1 REYQ144 + REYQ96
REYQ384_ATJ_1 REYQ168 + REYQ120 + REYQ96
REYQ432_ATJ_1 3 x REYQ144
REYQ408_AYD_1
1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)
REYQ336_AYD_1
REYQ360_AYD_1 3 x REYQ120
REYQ168 + REYQ120 + REYQ96
REYQ408_ATJ_1 REYQ168 + REYQ144 + REYQ96
REYQ384_AYD_1
3 x REYQ144
REYQ456_ATJ_1 REYQ168 + 2 x REYQ144
REYQ456_AYD_1 REYQ168 + 2 x REYQ144
REYQ432_AYD_1
REYQ312_ATJ_1 REYQ168 + REYQ144
REYQ312_AYD_1 REYQ168 + REYQ144
REYQ288_ATJ_1 2 x REYQ144
REYQ288_AYD_1 2 x REYQ144
REYQ264_ATJ_1 REYQ144 + REYQ120
REYQ264_AYD_1 REYQ144 + REYQ120
Outdoor Heat
Recovery Units (VRV
IV) 72,000 to 456,000
BTU/hr (cooling
capacity);
Qualified design
categories: T
REYQ168 + REYQ144 + REYQ96
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 7 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
30.2 48.9 66.7 714 50
30.2 48.9 66.7 727 Interp.
30.2 48.9 66.7 727 Interp.
30.2 48.9 66.7 727 Interp.
30.2 48.9 66.7 727 Interp.
30.2 48.9 66.7 727 Interp.
30.2 48.9 66.7 785 Interp.
30.2 48.9 66.7 785 Interp.
30.2 48.9 66.7 785 Interp.
30.2 48.9 66.7 785 51
30.2 97.8 66.7 1428 Interp.
30.2 97.8 66.7 1428 Interp.
30.2 97.8 66.7 1441 Interp.
30.2 97.8 66.7 1441 Interp.
30.2 97.8 66.7 1454 Interp.
30.2 97.8 66.7 1454 Interp.
30.2 97.8 66.7 1512 Interp.
30.2 97.8 66.7 1512 Interp.
30.2 97.8 66.7 1512 Interp.
30.2 97.8 66.7 1512 Interp.
30.2 97.8 66.7 1570 Interp.
30.2 97.8 66.7 1570 Interp.
30.2 97.5 66.7 1570 Interp.
REYQ192_ATJ_1 2 x REYQ96
REYQ192_AYD_1
REYQ264_ATJ_1 REYQ120 + REYQ144
REYQ168_AYD_1
REYQ72_ATJ_1
REYQ72_AYD_1
REYQ168_ATJ_1
REYQ96_ATJ_1
REYQ312_AYD_1
REYQ96 + REYQ120
REYQ216_AYD_1 REYQ96 + REYQ120
REYQ240_ATJ_1
2 x REYQ96
REYQ264_AYD_1
REYQ216_ATJ_1
REYQ336_ATJ_1 2 x REYQ168
REYQ288_AYD_1 2 x REYQ144
REYQ312_ATJ_1
REYQ240_AYD_1 2 x REYQ120
REYQ120 + REYQ144
REYQ288_ATJ_1 2 x REYQ144
REYQ144 + REYQ168
REYQ144 + REYQ168
2 x REYQ120
Outdoor Heat
Recovery Units (VRV)
72,000 to 513,000
BTU/hr (cooling
capacity);
Qualified design
categories: X
1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)
REYQ96_AYD_1
REYQ120_ATJ_1
REYQ120_AYD_1
REYQ144_ATJ_1
REYQ144_AYD_1
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 8 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
30.2 97.8 66.7 1570 Interp.
30.2 146.7 66.7 2297 Interp.
30.2 146.7 66.7 2297 Interp.
30.2 146.7 66.7 2355 Interp.
30.2 146.7 66.7 2355 Interp.
30.2 146.7 66.7 2355 Interp.
30.2 146.7 66.7 2355 Interp.
30.5 36.6 65.4 554 53
30.5 36.6 65.4 554 Interp.
30.5 48.8 65.4 710 Interp.
30.5 48.8 65.4 726 Interp.
30.5 48.8 65.4 713 Interp.
30.5 48.8 65.4 728 Interp.
30.5 48.8 65.4 785 Interp.
30.5 48.8 65.4 801 Interp.
30.5 48.8 65.4 788 Interp.
30.5 48.4 65.4 803 Interp.
30.5 68.8 65.4 957 Interp.
30.5 68.8 65.4 973 Interp.
30.5 68.8 65.4 957 Interp.
30.5 68.8 65.4 973 Interp.
REYQ408_AYD_1 2 x REYQ144 + REYQ120
REYQ432_ATJ_1
REYQ168AATJA2
REYQ168AAYDA2
REYQ144AATJA2
REYQ72AATJA
REYQ72AAYDA
REYQ96AATJA2
REYQ96AAYDA2
REYQ192AATJA2
3 x REYQ144
2 x REYQ144 + REYQ120
REYQ192AAYDA2
REYQ408_ATJ_1
REYQ216AATJA2
REYQ432_AYD_1 3 x REYQ144
REYQ456_ATJ_1
Outdoor Heat
Recovery (VRV) 72,000
to 513,000 BTU/hr
(cooling capacity);
Qualified design
categories: X
1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)2Requires seismic enhancements: Six (6) 1/2" mounting bolts per base unit rather than standard four (4) 1/2" mounting bolts. See
UUT 52 for details.
REYQ216AAYDA2
Outdoor Heat
Recovery (VRV) 69,000
to 456,000 BTU/hr
(cooling capacity);
Qualified design
categories: A
2 x REYQ144 + REYQ168
REYQ456_AYD_1 2 x REYQ144 + REYQ168
REYQ120AATJA2
REYQ120AAYDA2
REYQ336_AYD_1 2 x REYQ168
REYQ144AAYDA2
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 9 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
30.5 68.8 65.4 1002 Interp.
30.5 68.8 65.4 1002 52
30.5 97.6 65.4 1441 Interp.
30.5 97.6 65.4 1514 Interp.
30.5 97.6 65.4 1570 Interp.
30.5 97.6 65.4 1602 Interp.
30.5 97.6 65.4 1573 Interp.
30.5 97.6 65.4 1602 Interp.
30.5 97.6 65.4 1573 Interp.
30.5 97.6 65.4 1606 Interp.
30.5 116.6 65.4 1573 Interp.
30.5 116.6 65.4 1776 Interp.
30.5 137.6 65.4 1914 Interp.
30.5 137.6 65.4 1946 Interp.
30.5 137.6 65.4 1914 Interp.
30.5 137.6 65.4 1946 Interp.
30.5 137.6 65.4 1914 Interp.
30.5 137.6 65.4 1946 Interp.
30.5 137.6 65.4 1959 Interp.
30.5 137.6 65.4 1975 Interp.
30.5 137.6 65.4 2004 Interp.
30.5 137.6 65.4 2004 Interp.REYQ480AAYDA2
2 x REYQ216
2 x REYQ216
REYQ216 + REYQ240
REYQ216 + REYQ240
REYQ192+REYQ168
2 x REYQ168
REYQ360AATJA2 REYQ192+REYQ168
REYQ360AAYDA2
2 x REYQ144
REYQ312AATJA2 REYQ144+REYQ168
REYQ288AAYDA2
2 x REYQ240
2 x REYQ240
REYQ240AATJA2
REYQ240AAYDA2
REYQ264AATJA2 REYQ120+REYQ144
REYQ264AAYDA2
2 x REYQ144
REYQ120+REYQ144
REYQ408AATJA2 REYQ192 + REYQ216
REYQ408AAYDA2 REYQ192 + REYQ216
REYQ312AAYDA2 REYQ144+REYQ168
REYQ336AATJA2 2 x REYQ168
REYQ336AAYDA2
REYQ432AATJA2
REYQ432AAYDA2
REYQ456AATJA2
REYQ456AAYDA2
REYQ480AATJA2
2 x REYQ192
REYQ384AAYDA2 2 x REYQ192
Outdoor Heat
Recovery (VRV) 69,000
to 456,000 BTU/hr
(cooling capacity);
Qualified design
categories: A
2Requires seismic enhancements: Six (6) 1/2" mounting bolts per base unit rather than standard four (4) 1/2" mounting bolts. See
UUT 52 for details.
REYQ288AATJA2
REYQ384AATJA2
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 10 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
12.6 35.4 52.9 221.5 Interp.
12.6 37.0 39.0 172 Interp.
12.6 37.0 39.0 172 Interp.
12.6 35.4 52.9 221.5 Interp.
12.6 35.4 52.9 221.5 Interp.
12.6 35.4 52.9 221.5 Interp.
RZ_36_VJ_1,2,3
39 172
RXTQ48_VJ_1,2
RXTQ60_VJ_1,2 221.5
12.6 37 39 176
RZ_30_VJ_1,2,3
12.6
37
Interp.
38
Interp.
12.6 37
3 Construction of RXSQ, RZR, RZQ is identical to RXTQ, units differ in software only.
2Requires seismic enhancements: (4)ties from grille to unit frame, ties made of stainless steel 15" length by 3/16" width.
Interp.
39
Outdoor Heat Pump
(VRV-IV S) 34,200 to
57,000 BTU/hr;
Qualified design
categories: T
RXSQ60_VJ_1,2,3
Outdoor Heat Pump
(VRV LIFE) 23,00 to
57,000 BTU/hr;
Qualified design
categories: T
RXSQ36_VJ_1,2,3 12.6 37 39 172
RXSQ24_VJ_1,2,3 12.6 37 39 172
RZ_18_VJ_1,2,3
RZ_24_VJ_1,2,3
35.4 52.9
RXTQ36_VJ_1,2
1Required seismic enhancements: Two (2) stainless steel straps ( ¾” wide and 0.02” thick), running perpendicular to the units
width, approximately 30˚relative to vertical surface of the unit, attached with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish
Screws. Two (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws used to attach each end of the strap to the mounting fixture.
RZ_48_VJ_1,2,3
Outdoor Cooling/
Heat Pump (SkyAir)
18,000 to 48,000
BTU/hr;
Qualified design
categories: T
176 Interp.RXSQ48_VJ_1,2,3 12.6 37
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 11 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
22.2 30.1 38.6 423 39
22.2 30.1 38.6 423 Interp.
22.2 30.1 38.6 423 Interp.
22.2 30.1 38.6 426 Interp.
22.2 30.1 38.6 430 Interp.
22.2 30.1 38.6 450.5 45
22.2 30.1 38.6 846 Interp.
22.2 60.2 38.6 852 Interp.
22.2 60.2 38.6 846 Interp.
22.2 60.2 38.6 856 Interp.
22.2 60.2 38.6 846 Interp.
22.2 60.2 38.6 860 Interp.
22.2 60.2 38.6 846 Interp.
22.2 60.2 38.6 880.5 Interp.
131.5 58
131.5
RWEQ192_ATJ_ /ATJ_-HR 2 x RWEQ96
RWEQ192_AYD_ /AYD_-HR 2 x RWEQ96
RWEQ144_ATJ_ /ATJ_-HR
RWEQ144_AYD_ /AYD_-HR
Outdoor Water Cooled
Heat Pump and Heat
Recovery Unit
(VRV-W)
208/230V and 460V
96,000 to 144,000
BTU/hr (cooling
capacity);
Qualified design
categories: T
1Construction RX36NMVJUA is identical to RX30NMVJUA, units differ in software only.2Constructcion RK36NMVJUA is identical to RK30NMVJUA, units differ in software only.
Outdoor Heat Pump
24,000 to 36,000
BTU/hr: Qualified
design categories: N
RWEQ96_ATJ_ /ATJ_-HR
RWEQ120_AYD_ /AYD_-HR
RWEQ120_ATJ_ /ATJ_-HR
RWEQ96_AYD_ /AYD_-HR
34.1 28.9 131.5 57
RX30NMVJUA1 12.5 34.1
RK30NMVJUA2 12.5 34.1 28.9 131.5 Interp.
RK36NMVJUA2
RWEQ264_AYD_ /AYD_-HR RWEQ120 + RWEQ144
RWEQ240_AYD_ /AYD_-HR 2 x RWEQ120
RWEQ264_ATJ_ /ATJ_-HR RWEQ120 + RWEQ144
RWEQ216_AYD_ /AYD_-HR RWEQ96 + RWEQ120
RWEQ240_ATJ_ /ATJ_-HR 2 x RWEQ120
RWEQ216_ATJ_ /ATJ_-HR RWEQ96 + RWEQ120
12.5
28.9 Interp.
RX36NMVJUA1 12.5 34.1 28.9
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 12 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
22.2 60.2 38.6 846 Interp.
22.2 60.2 38.6 901 Interp.
22.2 90.3 38.6 1269 Interp.
22.2 90.3 38.6 1282 Interp.
22.2 90.3 38.6 1269 Interp.
22.2 90.3 38.6 1286 Interp.
22.2 90.3 38.6 1269 Interp.
22.2 90.3 38.6 1290 Interp.
22.2 90.3 38.6 1269 Interp.
22.2 90.3 38.6 1310.5 Interp.
RWEQ360_AYD_ /AYD_-HR 3 x RWEQ120
RWEQ384_AYD_ /AYD_-HR 2 x RWEQ120 + RWEQ144
Outdoor Water Cooled
Heat Pump and Heat
Recovery Unit
(VRV-W)
208/230V and 460V
96,000 to 144,000
BTU/hr (cooling
capacity);
Qualified design
categories: T
3 x RWEQ144 Interp.
38.6 1269 RWEQ120 + 2 x RWEQ144
RWEQ336_AYD_ /AYD_-HR RWEQ96 + 2 x RWEQ120
RWEQ360_ATJ_ /ATJ_-HR 3 x RWEQ120
RWEQ312_AYD_ /AYD_-HR 2 x RWEQ96 + RWEQ120
RWEQ336_ATJ_ /ATJ_-HR RWEQ96 + 2 x RWEQ120
2 x RWEQ144
RWEQ288_ATJ_ /ATJ_-HR 2 x RWEQ144
Interp.
RWEQ288_AYD_ /AYD_-HR
Outdoor Water Cooled
Heat Pump and Heat
Recovery Unit
(VRV-W)
208/230V and 460V
96,000 to 144,000
BTU/hr (cooling
capacity);
Qualified design
categories: TRWEQ432_AYD_ /AYD_-HR 22.2 90.3 38.6 1351.5
RWEQ120 + 2 x RWEQ144 Interp.
RWEQ432_ATJ_ /ATJ_-HR 22.2 90.3 38.6 1269 3 x RWEQ144 Interp.
RWEQ408_AYD_ /AYD_-HR 22.2 90.3
RWEQ408_ATJ_ /ATJ_-HR 22.2 90.3
38.6 1331
RWEQ312_ATJ_ /ATJ_-HR 2 x RWEQ96 + RWEQ120
RWEQ384_ATJ_ /ATJ_-HR 2 x RWEQ120 + RWEQ144
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 13 of 99
OSP-0297
Mohammad Karim
05/17/2022
Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 14 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 15 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 16 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 17 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 18 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 19 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
9.3 31.3 11.4 26.0 Extrap.
14.4 34.3 10.8 20.0 Extrap.
8.2 35.0 12.0 31.0 11
9.3 31.3 11.4 26.0 12
14.4 34.3 10.8 22.0 Interp.
8.2 35.0 12.0 31.0 Interp.
9.3 31.3 11.4 26.0 Interp.
9.4 41.3 11.4 26.5 Interp.
16.9 45.7 13.0 31.0 Interp.
8.2 35.0 12.0 31.0 Interp.
9.0 41.4 11.4 31.0 14
9.4 41.3 11.4 26.5 Interp.
16.9 45.7 13.0 31.0 Interp.
9.3 41.4 11.4 31.0 Interp.
9.4 41.3 11.4 26.5 Interp.
16.9 45.7 13.0 31.0 13
9.0 41.4 11.4 31.0 Interp.
9.3 41.4 11.4 31.0 Interp.
10.3 47 13.4 37 Interp.
9.4 47.3 13.4 38.0 Interp.
10.3 47 13.4 37 56
9.4 47.3 13.4 38.0 15
2.5 g z/h=0.0
FTXS36_VJU
FTX36_VJU
FTXS30_VJU
FAQ24_VJU
FXAQ24_VJU
FTXN24_VJU
FTXS24_VJU
FTXS18_VJU
FXAQ18_VJU
FAQ18_VJU
FTXN18_VJU
FTXS15_VJU
FTXG15_VJU
FXAQ12_VJU
FTXN15_VJU
FTXS12_VJU
FTX30_VJU1
Indoor Fan Coil (Split
System, Quaternity,
SkyAir)
7,500 to 36,000
BTU/hr;
Qualified design
categories: H (FTXG), P
(FXAQ), L (FTXS), P
(FAQ), N (FTX)
1Construction of the FTX30_VJU is identical to FTX36_VJU (UUT 56), units differ in software only.
Certified Product Construction Summary:
Plastic enclosure
Certified Options Summary:
Mounting Configuration:
Rigid - wall mounted
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 2Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
FTXG12_VJU
FTXG09_VJU
FXAQ09_VJU
FXAQ07_VJU
FTXS09_VJU
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.5
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 20 of 99
OSP-0297
Mohammad Karim
05/17/2022
FOR REFERENCE ONLY
Nomenclature: Split System, Quaternity, SkyAir Indoor Units
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 2Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 21 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
26.8 37.8 7.7 55 16
26.8 62.6 7.7 90 Interp.
26.8 62.6 7.7 90 Interp.
26.8 55.1 7.7 80 Interp.
26.8 62.6 7.7 90 Interp.
26.8 62.6 7.7 90 Interp.
26.8 62.6 7.7 90 Interp.
26.8 62.6 7.7 90 17
37.4 37.4 7.8 58 33
37.4 37.4 7.8 58 Interp.
37.4 37.4 7.8 60 Interp.
37.4 37.4 7.8 60 42
1Requires seismic enhancements: Heavy duty square washers (1.6" x 1.3 x 0.2”) were used at top and bottow of mounting
bracket. S-Shape hooks on four (4) internal wires, used to secure outer cover attachment to unit, were crimped closed to secure
cover to unit.
FXUQ30_VJU1
FXUQ36_VJU1
Indoor Fan Coil (VRV)
18,000 to 36,000 BTU/hr;
Qualified design
categories: P
FXUQ18_VJU1
FXUQ24_VJU1
FXHQ36_VJU
FHQ42_VJU
Indoor Fan Coil
(SkyAir, VRV-S, VRV)
12,000 to 40,500
BTU/hr;
Qualified design
categories: M
FHQ30_VJU
FHQ36_VJU
FHQ24_VJU
FXHQ24_VJU
FXHQ12_VJU
FHQ18_VJU
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Plastic cabinet. Seismic enhancements as indicated.
Certified Options Summary:
Mounting Configuration:
Ceiling suspended
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 22 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Plastic cabinet. Seismic enhancements as indicated.
Certified Options Summary:
Mounting Configuration:
Ceiling suspended
27.6 21.7 11.8 55 Extrap.
27.6 21.7 11.8 55 Extrap.
27.6 27.6 11.8 55 20
27.6 39.4 11.8 80 Interp.
27.6 39.4 11.8 80 Interp.
27.6 39.4 11.8 80 21
27.6 39.4 11.8 80 Interp.
27.6 39.4 11.8 80 Interp.
27.6 39.4 11.8 80 Interp.
27.6 55.1 11.8 80 Interp.
27.6 55.1 11.8 102 Interp.
27.6 55.1 11.8 101 Interp.
27.6 55.1 11.8 102 Interp.
27.6 55.1 11.8 101 22
27.6 55.1 11.8 101 Interp.
43.3 29.3 18.5 190 23
43.3 54.4 18.5 271 Interp.
43.3 54.4 18.1 302 Interp.
43.3 54.4 18.5 271 Interp.
43.3 54.4 18.1 302 24
2Requires seismic enhancements: One (1) #10 SMS at each mounting ear (4 total)3Construction of FXMQ54_VJU is identical to FMXQ48_VJU (UUT 22), units differ in software only.
1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch
FXMQ96MVJU2
Indoor Fan Coil (VRV-
S, VRV)
7,500 to 96,000
BTU/hr;
Qualified design
categories: P
FXMQ72MVJU2
FXMQ96MFVJU2
FXMQ48MFVJU2
FXMQ72MFVJU2
FXMQ48_VJU1
FXMQ54_VJU1,3
FXMQ36_VJU1
FBQ42_VJU1
FXMQ30_VJU1
FBQ36_VJU1
FXMQ24_VJU1
FBQ30_VJU1
FXMQ18_VJU1
FBQ24_VJU1
FXMQ12_VJU1
FBQ18_VJU1
FXMQ07_VJU1
FXMQ09_VJU1
FXMQ15_VJU1
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 23 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Plastic cabinet. Seismic enhancements as indicated.
Certified Options Summary:
Mounting Configuration:
Ceiling suspended
33.1 33.1 9.7 43 35
33.1 33.1 9.7 43 18
33.1 33.1 9.7 43 Interp.
33.1 33.1 9.7 43 Interp.
33.1 33.1 9.7 43 Interp.
33.1 33.1 9.7 49 Interp.
33.1 33.1 9.7 49 Interp.
33.1 33.1 9.7 49 Interp.
33.1 33.1 9.7 58 Interp.
33.1 33.1 11.3 58 Interp.
33.1 33.1 11.3 55 Interp.
33.1 33.1 11.3 55 Interp.
33.1 33.1 11.3 58 19
2Requires seismic enhancements: Eight (8) #10 SMS in each mounting ear. Four (4) cable tie (shipped with unit) chains, each with
two links, between decoration panel cover latches and through mounting ear. Two (2) strips of heavy duty Velcro® tape 1” x 2” at
each corner cover (eight total).
1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch
FXFQ48_VJU2
Indoor Fan Coil
(SkyAir, VRV III-S, VRV)
9,500 to 48,000
BTU/hr;
Qualified design
categories: P, T
FCQ36_VJU1
FCQ42_VJU1
FXFQ30_VJU2
FXFQ36_VJU2
FXFQ24_VJU2
FCQ30_VJU2
FXFQ18_VJU2
FCQ24_VJU1
FXFQ12_VJU2
FCQ18_VJU1
FXFQ07_VJU2
FXFQ09_VJU2
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 24 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Plastic cabinet. Seismic enhancements as indicated.
Certified Options Summary:
Mounting Configuration:
Ceiling suspended
22.6 22.6 10.3 41.5 Extrap.
22.6 22.6 10.3 41.5 Extrap.
22.6 22.6 10.3 41.5 48
22.6 22.6 10.3 46 Interp.
22.6 22.6 10.3 46 Interp.
22.6 22.6 10.3 46 49
31.5 21.7 9.7 51 Extrap.
31.5 21.7 9.7 51 46
31.5 21.7 9.7 55 Interp.
31.5 21.7 9.7 55 Interp.
31.5 21.7 9.7 60 Interp.
31.5 27.6 9.7 77 Interp.
31.5 39.4 9.7 82 Interp.
31.5 39.4 9.7 82 Interp.
31.5 55.1 9.7 101 Interp.
31.5 55.1 9.7 104 Interp.
31.5 61 9.7 110.5 47
Indoor Fan Coil (VRV
Vista) 5,800 to 18,000
BTU/hr (kW); Qualified
design categories: T
Indoor Fan Coil (VRV)
5,800 to 54,000 BTU/hr
(kW); Qualified design
categories: T
FXSQ54TAVJU1
FXSQ36TAVJU1
FXSQ48TAVJU1
FXSQ24TAVJU1
FXSQ30TAVJU1
FXSQ15TAVJU1
FXSQ18TAVJU1
FXSQ09TAVJU1
FXSQ12TAVJU1
FXSQ05TAVJU1
FXSQ07TAVJU1
FXZQ15TAVJU1,2
FXZQ18TAVJU1,2
FXZQ09TAVJU1,2
FXZQ12TAVJU1,2
FXZQ05TAVJU1,2
FXZQ07TAVJU1,2
1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch2 Requires seismic enchancements: Filter secured with two (2) stripes of 3M velcor. Panel cover hinges secured with 50 lb wire
and metal ferrule. See UUT summary for more details.
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 25 of 99
OSP-0297
Mohammad Karim
05/17/2022
Nomenclature: VRV Indoor Units
FOR REFERENCE ONLY
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 26 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: VRV Indoor Units
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 27 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
FOR REFERENCE ONLY
Nomenclature: VRV Indoor Units
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 28 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
12.2 15.3 8.1 26 25
12.2 15.3 8.1 26 Interp.
12.2 15.3 8.1 33 Interp.
25.0 41.5 8.3 132 Interp.
25.0 62.1 8.3 196 26
18.9 14.6 11.8 49 31
18.9 22.8 11.8 68 Interp.
18.9 22.8 11.8 73 Interp.
18.9 32.3 11.8 101 Interp.
18.9 32.3 11.8 106 32
9.5 83.5
23.4 9.5 50
1Seismic enhancements: 1/8" steel backer plate behind each mouting ear with (2) machine screws through each mounting ear.
54
Indoor Multi Port Branch
Selector (VRV IV)
144 to 290 total capacity
index;
Qualified design
categories: T
BS6Q54_VJ1
BS8Q54_VJ1
BSV6Q36_VJU
BS4Q54_VJ1
Indoor Single Port
Branch Selector (VRV III)
36 to 96 capacity index;
Qualified design
categories: P, T
BSVQ96_VJU
BSV4Q36_VJU
BSVQ36_VJU
BSVQ60_VJU
Indoor Multi Branch
Selectors (VRV)
Flex Series
Qualified design
categories: T
BSF4Q54TVJ
BSF6Q54TVJ
BSF8Q54TVJ
13.8
23.8 23.4 9.5 73
23.8 23.4
Interp.
55
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 4Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements as indicated.
Certified Options Summary:
Mounting Configuration:
Ceiling suspended
BS10Q54_VJ1
BS12Q54_VJ1
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 29 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 4Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: VRV III Indoor Branch Selector Units
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 30 of 99
OSP-0297
Mohammad Karim
05/17/2022
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 4Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Nomenclature: VRV III Indoor Branch Selector UnitsNomenclature: VRV III Indoor Branch Selector Units
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 31 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS=
S DS=
Depth Width Height
21 17.5 45 115 40
21 17.5 45 115 Interp.
21 17.5 45 115 Interp.
21 17.5 45 115 Interp.
21 17.5 45 115 Interp.
21 17.5 45 140 Interp.
21 21 54.43 150 Interp.
21 21 54.43 150 Interp.
22 24.5 58 167 Interp.
21 24.5 58 167 41
FXTQ54_VJU
FXTQ60_VJU
Air Handling Unit
9,500-60,000 BTU/hr
(cooling capacity)FXTQ42_VJU
FXTQ48_VJU
FXTQ30_VJU
FXTQ36_VJU
FXTQ18_VJU
FXTQ24_VJU
FXTQ09_VJU
FXTQ12_VJU
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 5Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Line ModelDimensions (in) Weight
(lb)Notes UUT
Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.
Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0
I P= 1.52.5 g z/h=0.0
Certified Product Construction Summary:
Carbon steel cabinet. Seismic enhancements as indicated.
Certified Options Summary:
Mounting Configuration:
Rigid - base mounted
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 32 of 99
OSP-0297
Mohammad Karim
05/17/2022
Nomenclature: VRV III Indoor Branch Selector Units
SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLCTABLE 5Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
FOR REFERENCE ONLY
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 33 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
2
3
1
27
28
29
30
37
Interp.
38
39,45
57,58
53Fins coated w/ anti-corrosion
hydrophilic blue coating
65-3/8" x 36-5/8" x 30-1/8"
Al fin, Cu tube2P626353-1
Interp. Fins coated w/ anti-corrosion
hydrophilic blue coating
65-3/8" x 48-13/16" x 30-1/8"
Al fin, Cu tube2P631073-1
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
3P138067-2 7mm x 0.27 mm coil, Al fin, Cu tube
2P170976-3 8mm x 0.3 mm coil, Al fin, Cu tube
3P287611-2
Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code:
Heat Exchanger Daikin
3P379239-1 7mm x 0.24mm, 2 row, 32 stage, Cu tube Aluminum parts
7500099 7mm x 0.3mm coil, Al fin, Cu tube
6019568
7mm x 0.3mm coil, Al fin, Cu tube
7mm x 0.3mm coil, Al fin, Cu tube
6019584
CBC 2019 Seismic Certification Limits: I P = 1.5
7009510 7mm x 0.3mm coil, Al fin, Cu tube
5018937 18-3/4" x 4-1/2" Stainless Steel Braze Plate
7mm x 0.3mm coil, Al fin, Cu tube
7009559 7mm x 0.3mm coil, Al fin, Cu tube
7500019 7mm x 0.3mm coil, Al fin, Cu tube
51
UUTComponent Type Manufacturer Model Description Notes
8mm x 0.3 mm coil, Al fin, Cu tube
3P341763-2 7mm x 0.3mm coil, Al fin, Cu tubeused for all REYQ_XATJU and
REYQ_XAYDU models
3P412977-1 Plate HX for vapor injectionREYQ72/96/120XATJU,
REYQ72/96/120XAYDU
39412975-1 Plate HX for vapor injectionREYQ151/168XATJU,
REYQ151/168XAYDU
50,51
50
6021509
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 34 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description: Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
UUTComponent Type Manufacturer Model Description Notes
1
2
3
37
38
57, 58
39
45
27
28,30
29
30
Extrap.
53
Interp.
Interp.
50
Interp.
Interp.
Vapor Injection
Scroll Compressor
Daikin
Heat Exchanger
7009548 96,000 BTU/hr, 460V, Carbon Steel
JT250KADWTJ@S 230 V, 3-phase, 50.6 lbs.
JP057AEAXMV#T 230 V, 3-phase, 72.8 lbs.
52Fins coated w/ anti-corrosion
hydrophilic blue coating
65-3/8" x 68-7/8" x 30-1/8"
Al fin, Cu tube2P623585-1
Interp.Fins coated w/ anti-corrosion
hydrophilic blue coating
65-3/8" x 48-13/16" x 30-1/8"
Al fin, Cu tube2P627736-1
230 V, 3-phase, 63.9 lbs.
JT16KADWYDN@S 144,000 BTU/hr, 460V, Carbon Steel
151,000 BTU/hr, 208-230V Carbon Steel5018933
2YC63FXD#D 36,000 BTU/hr, 208-230V
1873054 72,000 BTU/hr, 208-230V, Carbon Steel
7009494 72,000 BTU/hr, 208-230V, Carbon Steel
7009487 96,000 BTU/hr, 460V, Carbon Steel
JP035AEAXSV#T
1YC23AEXD 12,000 BTU/hr, 208-230V
2YC63BXD#A 21,500 BTU/hr, 208-230V
JP057AEAYSV#T 460 V, 3-phase, 71.4 lbs.
JT160KADWTJ@T 230 V, 3-phase, 39 lbs.
6025911
6025930 57, 000 BTU/hr, 208-230V
2YC63AAXD 220VDC, 18A, Insulation Class E
JP057AEAXSV#T 230 V, 3-phase, 71.9 lbs.
JP035AEAYSV#T 460 V, 3-phase, 63.7 lbs.
Scroll Compressor in UUT 53 is a
depopulated version of Vapor Injection
Scroll Compressor in UUT 52.
Scroll Compressor
Scroll Compressor
36,000 BTU/hr, 208-230V
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 35 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description: Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
UUTComponent Type Manufacturer Model Description Notes
Interp.
51
52
3
27
28,30
29
28,30
29
57,58
1
2
37
38
39
50
51
Interp.
53
Interp.
52
Vapor Injection
Scroll CompressorDaikin
Fan Motor
Fan Motor Panasonic
Panasonic2219507 Propellor Fan 400 Watts UUT: Polyester resin tested
4012512 Propellor Fan 650 Watts UUT: Polyester resin tested
D90B-37 DC375V, 128 Watts, Class E UUT: Polyester resin tested
NIDEC
Propellor Fan 500 Watts
Propellor Fan 650 Watts
1713309 UUT: Polyester resin tested
4012512 UUT: Polyester resin tested
2P557547-1
3SB40622-3 60W, 208-230V UUT: Polyester resin tested
2219507 Propellor Fan 400 Watts UUT: Polyester resin tested
UUT: Polyester resin tested23W, 208-230V3SB40632-6
460 V, 3-phase, 50.6 lbs.
JP057AEAYMV#T 460 V, 3-phase, 72.3 lbs.
3SB40675-1 200W, 208-230V UUT: Polyester resin tested
650W, 460V UUT: Acrylonitrile Resin Plastic
2P618618-2 950W, 460V UUT: Acrylonitrile Resin Plastic
2P618618-1 950W, 208/230V UUT: Acrylonitrile Resin Plastic
2P519551-2 650W, 208/230V UUT: Acrylonitrile Resin Plastic
2P360713-3 800W, 208/230V
2P343735-1 800W, 460V
JT15JBVDWYR@S 460 V, 3-phase, 34.2 lbs.
JT25KADWYDN@S
1,2Low Ambient Wind
BaffleKPW937A4
Daikin
Plastic
6016145 Propeller Fan, 200 Watts, 208-230 V UUT: Polyester resin tested
2025036 Propeller Fan, 70 Watts, 208-230 V UUT: Polyester resin tested
5019722 23 Watts, 208-230 V UTT: Polyester resin tested
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 36 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description: Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
UUTComponent Type Manufacturer Model Description Notes
1,2
3
Daikin BRP2A81Plastic, Requires BRP2A81 ABC Terminal
KitCool/Heat Selector
27,28,29,
30
Saginomiya
FujikokiExpansion Valve
CAM-B30YGDM Copper, SS, Resin
UKV-25D Copper, SS, Resin
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 37 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
11
13
12
14
15
56
11
12
15
14
13
56
12
14
11
11
12
13
14
15
11
11
13,15
Deodorizing Filter Daikin
Photocatalytic Filter Daikin
1288416 Plastic Mesh
4009476 Plastic Mesh
1700125 Plastic Mesh
1685846 Plastic Mesh
2SA50075-1-KU Copper, SS, Resin
Cross Flow Fan 48W, 208-230V UUT: Polyester resin tested
KFD-325-64-8A 64W, DC325V UUT: Unsaturated Polyester Resin
3SB40672-1 Cross Flow Fan 64W, 208-230V UUT: Polyester resin tested
1380242 Plastic Mesh
4000835 Plastic Mesh
NIDEC
Fan Motor
Photocatalytic1840489
1843039
Filter Daikin
Expansion Valve Fujikoki
Daikin
Panasonic
2SA50075-1-SI Copper, SS, Resin
3SB40720-1
1843053 Plastic Mesh
Photocatalytic
3SB40591-1 Cross Flow Fan 43W, 208-230V UUT: Polyester resin tested
3SB40647-3 Cross Flow Fan 23W, 208-230V UUT: Polyester resin tested
3SB40565-1 Cross Flow Fan 40W, 208-230V UUT: Polyester resin tested
UUT
Fan Coil -Wall SubcomponentsTABLE 7
2P222543-1 7mm x 0.3 mm coil, Al fin, Cu tube
1P222779-1 7mm, 2 row, 18 stage, Al fin, Cu tube
2P168924-4 7mm x 0.3 mm coil, Al fin, Cu tube
2P171400-2 7mm x 0.3 mm coil, Al fin, Cu tube
1P287200-1 6.35mm x 0.3 mm coil, Al fin, Cu tube
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
3P204553-2 6.35mm x 0.3 mm coil, Al fin, Cu tube
Component Type Manufacturer Model Description
Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
Heat Exchanger Daikin
Notes
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 38 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
UUT
Fan Coil -Wall SubcomponentsTABLE 7
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
Component Type Manufacturer Model Description
Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
Notes
12, 14Individual Zone
ControllerDaikin BRC7E818 Plastic
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 39 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
16
17
18
19
20
21
22
23
24
33
Interp.
Interp.
Interp.
Interp.
Interp.
Interp.
35
42
48
Interp.
49
46
Interp.2397801 3/8" x 1/8", Cu Tube, Al fin FXSQ12TAVJU
5011003 3/8" x 1/8", Cu Tube, Al fin FXZQ18TAVJU
2397793 3/8" x 1/8", Cu Tube, Al fin FXSQ05/07/09TAVJU
5011000 3/8" x 1/8", Cu Tube, Al fin FXZQ05/07/09TAVJU
5011004 3/8" x 1/8", Cu Tube, Al fin FXZQ12/15TAVJU
1993028 7mm x 0.3 mm coil, Al fin, Cu tube
2110756 7mm x 0.3 mm coil, Al fin, Cu tube
1993059 7mm x 0.3 mm coil, Al fin, Cu tube
2110763 7mm x 0.3 mm coil, Al fin, Cu tube
1993042 7mm x 0.3 mm coil, Al fin, Cu tube
2110770 7mm x 0.3 mm coil, Al fin, Cu tube
1993035 7mm x 0.3 mm coil, Al fin, Cu tube
3P290389-1 7mm x 0.3 mm coil, Al fin, Cu tube
3P288941-1 7mm x 0.3 mm coil, Al fin, Cu tube
2218100 7mm x 0.3 mm coil, Al fin, Cu tube
CRB-FXYMP280M 8mm x 0.3 mm coil, Al fin, Cu tube
2273936 7mm x 0.3 mm coil, Al fin, Cu tube
3P288942-1 7mm x 0.3 mm coil, Al fin, Cu tube
CRB-FXYMP224M 8mm x 0.3 mm coil, Al fin, Cu tube
2P231854-1 7mm x 0.3 mm coil, Al fin, Cu tube
2P231856-1
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
AFREX 2PN05185-3 7mm x 0.3 mm coil, Al fin, Cu tube
2PN05189-3 7mm x 0.3 mm coil, Al fin, Cu tube
Component Type Manufacturer Model Description Notes
7mm x 0.3 mm coil, Al fin, Cu tube
UUT
Fan Coil -Ceiling SubcomponentsTABLE 8Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
DaikinHeat Exchanger
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 40 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
Component Type Manufacturer Model Description Notes UUT
Fan Coil -Ceiling SubcomponentsTABLE 8Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
Interp.
Interp.
Interp.
Interp.
Interp.
Interp.
47
48
Interp.
49
46
Interp.
Interp.
Interp.
Interp.
47
46
Interp.
Interp.
Interp.
47
48,49
48,49
Expansion Valve Daikin Pulse motor electronic expansion valve FXSQ12/15TAVJU
2214021 Pulse motor electronic expansion valve FXSQ18/24TAVJU
2110073
2371955 Pulse motor electronic expansion valve FXSQ54TAVJU
4018537 Pulse motor electronic expansion valve FXSQ30TAVJU
4018534 Pulse motor electronic expansion valve FXSQ36/48TAVJU
4015739
5011010 Molded polymer, 12" Ø
5011038 50W
2P383154-2 Galvanized Steel FXSQ36/48TAVJU
2P394978-1 Galvanized Steel FXSQ54TAVJU
2P383156-2 Galvanized Steel FXSQ15TAVJU
2P383155-2 Galvanized Steel FXSQ18/24/30TAVJU
2397818 Galvanized Steel FXSQ05/07/09/12TAVJU
Pulse motor electronic expansion valve FXZQ18TAVJU
4015738 Pulse motor electronic expansion valve FXSQ05/07/09TAVJU
2108342 Pulse motor electronic expansion valve FXZQ05/07/09TAVJU
2108359 Pulse motor electronic expansion valve FXZQ12/15TAVJU
2397902 3/8" x 1/8", Cu Tube, Al fin FXSQ48TAVJU
2397933 3/8" x 1/8", Cu Tube, Al fin FXSQ54TAVJU
2397863 3/8" x 1/8", Cu Tube, Al fin FXSQ30TAVJU
2397919 3/8" x 1/8", Cu Tube, Al fin FXSQ36TAVJU
2397870 3/8" x 1/8", Cu Tube, Al fin FXSQ18TAVJU
2397887 3/8" x 1/8", Cu Tube, Al fin FXSQ24TAVJU
2397856 3/8" x 1/8", Cu Tube, Al fin FXSQ15TAVJU
DaikinHeat Exchanger
Fan Assembly Sirocco
Turbo Fan Rotor Sirocco
Fan Motor Panasonic
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 41 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
Component Type Manufacturer Model Description Notes UUT
Fan Coil -Ceiling SubcomponentsTABLE 8Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
46
Interp.
Interp.
Interp.
474016361 350W FXSQ54TAVJU
2258153 230W FXSQ18/24/30TAVJU
2258160 300W FXSQ36/48TAVJU
4015745 78W FXSQ05/07/09/12TAVJU
2258146 130W FXSQ15TAVJU
Fan Motor Panasonic
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 42 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
25
25
25
25
25
25
25
25
31,32
31,32
31,32
31,32
31,32
Body/Motor Operated Valve, Copper
Coil/Motor Operated Valve, Copper
Coil/Motor Operated Valve, Copper
Coil/Motor Operated Valve, Copper
Coil/Motor Operated Valve, Copper
Coil/Motor Operated Valve, Copper
Body/Motor Operated Valve, Copper
Body/Motor Operated Valve, Copper
Coil/Motor Operated Valve (Sub Suction), Copper
Coil/Motor Operated Valve (Sub Discharge), Copper
Coil/Motor Operated Valve (Sub Cool), Copper
Coil/Motor Operated Valve (Main Suction), Copper
Coil/Motor Operated Valve (Main Discharge), Copper 26
1939745 26
2227469
2271202
2271194
2227476
Coil/Electronic Exp. Valve, Copper
Coil/Electronic Exp. Valve Assy., Copper
Coil/Electronic Exp. Valve Assy., Copper
Coil/Electronic Exp. Valve, Copper
Coil/Electronic Exp. Valve Assy., Copper
DaikinValve
1801299
1801408
1801390
UUTNotesDescription
2227515
1801268
1801251
1801282
1801275
1801415
1939776 26
1939752 26
1939769 26
1939738
Branch SubcomponentsTABLE 9Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
Component Type Manufacturer Model
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 43 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
UUTNotesDescription
Branch SubcomponentsTABLE 9Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
Component Type Manufacturer Model
31,32
31,32
31,32
31,32
31,32
31,32
31,32
54
Interp.
55
54
Interp.
Interp.
Interp.
Interp.
55
Daikin
Fujikoki
Valve
EEV Coil
EEV Coil
EEV Coil
EEV Body
EEV Body
EEV Body
Coil/Electronic Exp. Valve Assy., Copper
Coil/Electronic Exp. Valve Assy., Copper
Coil/Electronic Exp. Valve, Copper
Coil/Electronic Exp. Valve Assy., Copper
Coil/Electronic Exp. Valve Assy., Copper
Coil/Electronic Exp. Valve, Copper
Coil/Electronic Exp. Valve Assy., Copper
3P389855-4 EEV Coil
3P389855-2
3P389855-3
3P389855-1
3S500040-1
3P363865-1
3S500039-1
2227445
2227483
3S500038-1
3P363865-2
EEV Coil
EEV Coil
2271226
2271219
2227452
2227490
2227508
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 44 of 99
OSP-0297
Mohammad Karim
05/17/2022
S DS = 2.0 g z/h = 1.0
S DS = 2.5 g z/h = 0.0
40
Interp.
Interp.
Interp.
Interp.
Interp.
Interp.
Interp.
41
40
Interp.
Interp.
41
40
Interp.
41
40
Interp.
Interp.
Interp.
Interp.
Interp.
41
Blower Assembly Daikin
Heat Exchanger Daikin
Fan Motor Daikin
0131M00272 1 Hp, Serial ECM
3S500052-1
0271A00029 10 x 8" , Galvanized Steel
0270A01206 3/8" x 1/8", Al Tube, Al fin
0270A01161 3/8" x 1/8", Al Tube, Al fin
0270A01156 3/8" x 1/8", Al Tube, Al fin
3S500054-1 FXTQ54, 60 - tested in FXTQ60
Expansion Valve Daikin
FXTQ42,48
0271A00206 10 x 8" , Galvanized Steel FXTQ54,60 - tested in FXTQ60
FXTQ60
0271A00299 9 x 6", Galvanized Steel FXTQ09-36, tested in FXTQ09
Pulse motor electronic expansion valve
FXTQ30
3S500053-1 FXTQ36, 42
3S500050-1 FXTQ18
3S500051-1 FXTQ24
3S500048-1 FXTQ09
3S500049-1 FXTQ12
0131M00271 3/4 Hp, Serial ECM FXTQ42-48
FXTQ54
FXTQ54, 60 - tested in FXTQ60
0131M00270 1/2 Hp, Serial ECM FXTQ09-36
0270A01196 3/8" x 1/8", Al Tube, Al fin FXTQ42
0270A01197 3/8" x 1/8", Al Tube, Al fin FXTQ48
FXTQ30
0270A01162 3/8" x 1/8", Al Tube, Al fin FXTQ36
0270A01159 3/8" x 1/8", Al Tube, Al fin FXTQ18
0270A01160 3/8" x 1/8", Al Tube, Al fin FXTQ24
FXTQ09
0270A01157 3/8" x 1/8", Al Tube, Al fin FXTQ12
Component Type Manufacturer Model Description Notes
SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX
2100103-CR-001-R1
Manufacturer: Daikin North America, LLC Table Description:
UUT
Multi Position AHU SubcomponentsTABLE 10Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 45 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
2.98 1.0 1.5
Notes:
22FXMQ48PVJU
Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No
21FXMQ18PVJU
Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.90 1.0 1.5
20FXMQ12PVJU
Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.92 1.0 1.5
2.92 1.0 1.5
19FXFQ48PVJU
Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.95
18FXFQ09PVJU
Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No
1.0 1.5
1.5
NOT USED
12
13
15
14
16
17FHQ42MVJU
Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 3.05 1.0 1.5
FXAQ09PVJU
Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.92 1.0 1.5
11FTXG09HVJU
Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.95
4-10
1.0
3RXS36LVJU
Base Mounted - RigidQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5
1.0 1.5
2RXS24LVJU
Base Mounted - RigidQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5
1RXS09LVJU
Base Mounted - RigidQ1222.0, Rev 0 QualTech NP 2012 No 2.87
UUT Unit Description Report Number Testing LabYear
Tested
ISO 17025
Accredited?
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
SDS z/h IP
FTXS24LVJU
Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.90 1.0 1.5
FAQ18PVJU
Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5
FTXS36LVJU
Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.92 1.0 1.5
FXHQ12MVJU
Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 46 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
UUT Unit Description Report Number Testing LabYear
Tested
ISO 17025
Accredited?
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
SDS z/h IP
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
Clark Testing
Environment Testing
Laboratory, Inc.
NOT USED
2017 Yes
2017 Yes
2016 Yes
2016 Yes
1.5
1.5
1.5
36
FXFQ07TVJU
Ceiling - Suspended35 2016 Yes
1.5
14662, Rev. 3
QualTech NP
QualTech NP
QualTech NP
QualTech NP
Clark Testing
Clark Testing
Clark Testing
Clark Testing
Clark Testing
JID 15-1054
Rev 0
JID 15-1054
Rev 0
JID 15-1054
Rev 0
14662, Rev. 3
Environment Testing
Laboratory, Inc.
Clark Testing
Clark Testing
FXMQ48MFVJU Ceiling -
Suspended
FXMQ96MVJU
Ceiling - Suspended
BSVQ36PVJU
Ceiling - Suspended
BSV6Q36PVJU
Ceiling - Suspended
RXYQ72TTJU
Base Mounted - Rigid
RXYQ168TYDN
Base Mounted - Rigid
REYQ72TTJU
Base Mounted - Rigid
REYQ168TYDN
Base Mounted - Rigid
BS4Q54TVJ
Ceiling - Suspended
34
FXUQ18PVJU
Ceiling - Suspended33
1.5
32 1.5BS12Q54TVJ
Ceiling - Suspended
JID 15-1054
Rev 031 2016 Yes
NOT USED
1.5
30 1.5
JID 15-1054
Rev 0
JID 15-1054
Rev 0
29 2.50 1.02016 Yes
2016 Yes
1.5
28 1.5
JID 15-1054
Rev 0
JID 15-1054
Rev 0
27 2.50 1.0Yes
2016 Yes
2016
1.5
26 2.95 1.0 1.5
Q1222.0, Rev 0
Q1222.0, Rev 0
25 2.98 1.02012 No
2012 No
1.5
24 2.92 1.0 1.5
Q1222.0, Rev 0
Q1222.0, Rev 0
23 2.98 1.02012 No
2012 No
Notes:
38
RXTQ36TAVJU,
Base Mounted - Rigid
RXTQ60TAVJU,
Base Mounted - Rigid
37
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 47 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
UUT Unit Description Report Number Testing LabYear
Tested
ISO 17025
Accredited?
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
SDS z/h IP
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
2.00 1.0
2.50 0.0
56FTX36NVJU
Wall - Rigid Mount2100103-TR-001-R1
Environment Testing
Laboratory, Inc. 2022 Yes
55BSF8Q54TVJ
Ceiling-Suspended2100103-TR-001-R1
Environment Testing
Laboratory, Inc. 2022 Yes
57RK36NMVJUA
Base Mounted - Rigid2100103-TR-001-R1
Environment Testing
Laboratory, Inc. 2022 Yes
58RX36NMVJUA
Base Mounted - Rigid2100103-TR-001-R1
Environment Testing
Laboratory, Inc. 2022
BSF4Q54TVJ
Ceiling-Suspended2100103-TR-001-R1
Environment Testing
Laboratory, Inc. 2022 Yes
53REYQ72AATJA
Base Mounted - Rigid2100103-TR-001-R1
Environment Testing
Laboratory, Inc. 2022 Yes
54
52REQ240AAYDA
Base Mounted - Rigid2100103-TR-001-R1
Environment Testing
Laboratory, Inc. 2022 Yes
51 REYQ144XATJU
Base Mounted - Rigid15215, Rev.1
Environment Testing
Laboratory, Inc. 2019 Yes
50
49FXZQ18TAVJU
Ceiling-Suspended15215, Rev.1
Environment Testing
Laboratory, Inc. 2019 Yes
48FXZQ09TAVJU
Ceiling-Suspended15215, Rev.1
Environment Testing
Laboratory, Inc. 2019 Yes
REYQ72XATJU
Base Mounted - Rigid15215, Rev.1
Environment Testing
Laboratory, Inc. 2019 Yes
47FXSQ54TAVJU
Ceiling-Suspended15215, Rev.1
Environment Testing
Laboratory, Inc. 2019 Yes
46FXSQ07TAVJU
Ceiling-Suspended15215, Rev.1
Environment Testing
Laboratory, Inc. 2019 Yes
Yes
45RWQE144TAYDU
Base Rigid Mount15215, Rev.1
Environment Testing
Laboratory, Inc. 2019 Yes
43, 44 NOT USED
Yes
42
41FXTQ60TAVJU,
Base Mounted - Rigid14662, Rev. 3
Environment Testing
Laboratory, Inc. 2017
Environment Testing
Laboratory, Inc. 2017 Yes
FXTQ09TAVJU,
Base Mounted - Rigid14662, Rev. 3
Environment Testing
Laboratory, Inc. 2017 Yes
FXUQ36PVJU
Ceiling - Suspended14662, Rev. 3
Environment Testing
Laboratory, Inc. 2017
Notes:
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Yes
40
39RWEQ96TATJU,
Base Mounted - Rigid14662, Rev. 3
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 48 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
75
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Rigid base mounted with (4) 3/8ӯ A307 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.87 1.0 1.5 4.59 3.44 1.91 0.77
Test Mounting Details:
14.6
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
11.8 33.5 21.5 29.5 >33.3
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.27 mm coil DAIKIN 3P138067-2
Compressor: 12,000 Btu/h DAIKIN 1YC23AEXD
Fan: Propeller 23W NIDEC 3SB40632-6
Printed Circuit Boards: Main DAIKIN 4009626, Filter DAIKIN 4009359
Expansion Valve: FUJIKOKI CAM-B30YGDM
Other: DAIKIN Carbon Steel cabinet, DAIKIN KPW937A4 Low ambient wind baffle
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RXS09LVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 49 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
158
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Rigid base mounted with (4) 1/2ӯ A307 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.98 1.0 1.5 4.77 3.58 1.99 0.79
Test Mounting Details:
14.6
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
11.5 29.5 14.3 12.2 6.6
Options/Subcomponent Summary:
Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN 2P170976-3
Compressor: 21,500 Btu/h DAIKIN 2YC63BXD#A
Fan: Propeller 60W NIDEC 3SB40622-3
Printed Circuit Boards: Main DAIKIN 4009630, Filter DAIKIN 1688256
Expansion Valve: FUJIKOKI CAM-B30YGDM, Other: DAIKIN Carbon steel cabinet, DAIKIN KPW945A4 Low ambient wind baffle
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Heat Pump: carbon steel enclousre with (4) cable ties grille to unit frame
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 2Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RXS24LVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 50 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
181
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Rigid base mounted with (4) 1/2”Ø A307 bolts & (4) 1/16”x1-1/2” aluminum straps were secured approximately 30˚relative to
vertical surface of the unit with (2) #10 SMS to unit & 1/4ӯ bolt to table
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.98 1.0 1.5 4.77 3.58 1.99 0.79
Test Mounting Details:
14.6
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
14.0 37.0 39.3 11.5 6.6
Options/Subcomponent Summary:
Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN 3P287611-2
Compressor: 36,000 Btu/h DAIKIN 2YC63FXD#D
Fan: Propeller 200W Panasonic 3SB40675-1
Printed Circuit Board: Main DAIKIN 4009635
Expansion Valve : Saginomiya UKV-25D, Other: DAIKIN Carbon steel cabinet
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RXS36LVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 51 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
29
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Wall mounted with (4) 3/8ӯ A307 bolts & (1) #6-32 screw & (1) #10-32 screw
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.95 1.0 1.5 4.72 3.54 1.97 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
8.5 35.0 12.0 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 6.35 mm x 0.3 mm coil DAIKIN 3P204553-2
Fan: Cross Flow Fan 23W NIDEC 3SB40647-3
Printed Circuit Boards: Printed Circuit Assy(Photo/Display) DAIKIN 1840054; Pyroelectric Passive Infrared Sensor DAIKIN 1840061;
Main DAIKIN 4009433
Other: DAIKIN 1843053 Deodorizing filters; DAIKIN 1700125 Filter; DAIKIN 1685846 Filter; DAIKIN 1843039 Photocatalytic filter
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (wall mounted) enclosure constructed of plastic
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 11Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FTXG09HVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 52 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
25
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Wall mounted with (4) 3/8ӯ A307 bolts & (5) #10 self-tapping screws
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.92 1.0 1.5 4.67 3.50 1.95 0.78
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
9.3 31.0 11.5 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P168924-4
Fan: Cross Flow Fan 40W NIDEC 3SB40565-1
Printed Circuit Boards: Main DAIKIN 4008765; Main DAIKIN 4005831
Expansion Valve: Fujikoki 2SA50075-1-KU
Other: DAIKIN BRC7E818 Individual Zone Controller; DAIKIN 1288416 Filter
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (wall mounted) enclosure constructed of plastic
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 12Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXAQ09PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 53 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
32
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Wall mounted with (4) 3/8ӯ A307 bolts & (1) #10-32 screw
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.90 1.0 1.5 4.64 3.48 1.93 0.77
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
9.8 40.8 13.4 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 6.35 mm x 0.3 mm coil DAIKIN 1P287200-1
Fan: Cross Flow Fan 48W Panasonic 3SB40720-1
Printed Circuit Boards: Printed Circuit Assy(Photo/Display) DAIKIN 4000843; Printed Circuit Assy(Infrared Sensor) DAIKIN
4000844; Main DAIKIN 4009491
Other: DAIKIN 4009476 Filter; DAIKIN 1840489 Photocatalytic filter
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (wall mounted) enclosure constructed of plastic
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 13Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FTXS24LVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 54 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
31
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Wall mounted with (4) 3/8ӯ A307 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.98 1.0 1.5 4.77 3.58 1.99 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
8.5 41.1 11.5 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P171400-2
Fan: Cross Flow Fan 43W Panasonic 3SB40591-1
Printed Circuit Board: Main DAIKIN 1884472
Expansion Valve: Valve Fujikoki 2SA50075-1-SI
Other: DAIKIN BRC7E818 Individual Zone Controller; DAIKIN Plastic Mesh 1380242 Filter
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (wall mounted) enclosure constructed of plastic
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 14Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FAQ18PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 55 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
36
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
Wall mounted with (4) 3/8ӯ A307 bolts & (1) #6-32 screw
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.92 1.0 1.5 4.67 3.50 1.95 0.78
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
9.5 46.9 13.4 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P222543-1
Fan: Cross Flow Fan 64W NIDEC 3SB40672-1
Printed Circuit Boards: Printed Circuit Assy.(Photo/Display) DAIKIN 4000843; Printed Circuit Assy. (Infrared Sensor) DAIKIN
4000844; Main DAIKIN 4009500
Other: DAIKIN 4000835 Plastic Mesh Filter; DAIKIN 1840489 Photocatalytic filter
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (wall mounted) enclosure constructed of plastic
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 15Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FTXS36LVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 56 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
59
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.98 1.0 1.5 4.77 3.58 1.99 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
8.0 37.5 27.0 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil AFREX 2PN05185-3
Fan: Sirocco Fan 60W Panasonic 3PN04213-1
Printed Circuit Boards: Main DAIKIN 1621626; Main DAIKIN 1621633; Main DAIKIN 162163J
Expansion Valve: Valve Fujikoki 2SA50046-2-KE
Other: DAIKIN 1245349 Filter
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 16Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXHQ12MVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 57 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
93
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
3.05 1.0 1.5 4.88 3.66 2.03 0.81
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
8.0 62.0 27.0 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil AFREX 2PN05189-3
Fan: Sirocco Fan 130W Panasonic 3PN04404-1
Printed Circuit Board: Main DAIKIN 1621626; Main DAIKIN 1621633; Main DAIKIN 162163J
Expansion Valve: Valve Fujikoki 2SA50046-2-KA
Other: DAIKIN BRC7E83 Individual Zone Controller; DAIKIN 1245363 Filter
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 17Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FHQ24MVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 58 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
70
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with ½” washers & nuts above and below mounting ears & (8)
1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.92 1.0 1.5 4.67 3.50 1.95 0.78
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
33.0 33.0 9.5 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P231854-1, Fan: 3P173872-1 Turbo Fan 56W Panasonic 3P173872-1
Printed Circuit Board: Main DAIKIN 2034193; Group Control Adaptor DAIKIN KRP4A74 , Expansion Valve: Valve Saginomiya
3SA50093-1
Other: Installation Box for Adapter PCB DAIKIN KRP1H98; DAIKIN KRP1C75 Wiring Adapter PCB (requires KRP1H98 for
FXFQ_PVJU); DAIKIN KDDP55B160K Fresh Air Intake Kit with T Pipe; DAIKIN DACA-FQP13-1K MERV 13 Filter & Kit
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic. Plastic enclosure with 6-#10 SMS at each mounting ear (24
total) & #10 SMS in grille latch
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 18Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXFQ09PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 59 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
82
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with ½” washers and nuts above and below mounting ears & (8)
1/8” diagonal cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.95 1.0 1.5 4.72 3.54 1.97 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
33.0 33.0 11.4 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7mm coil DAIKIN 2P231856-1, Fan: 3P173873-1 Turbo Fan 120W Panasonic 3P173873-1, Printed Circuit Boards:
Main DAIKIN 2034193; Group Control Adaptor DAIKIN KRP4A74
Expansion Valve: Valve Saginomiya 3SA50095-1, Other: DAIKIN KRP1H98 Installation Box for Adapter PCB; DAIKIN KRP1C75
Wiring Adapter PCB (requires KRP1H98
for FXFQ_PVJU); DAIKIN KDDP55B160K Fresh Air Intake Kit with T Pipe; DAIKIN DACA-FQP13-1K MERV 13 Filter & Kit
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic. Plastic enclosure with 6-#10 SMS at each mounting ear (24
total) & #10 SMS in grille latch
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 19Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXFQ48PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 60 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
67
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted w/ A14(4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each
end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.92 1.0 1.5 4.67 3.50 1.95 0.78
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
25.0 30.0 12.0 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P290389-1, Fan: Sirocco Fan 90W NIDEC 3P229859-1
Printed Circuit Boards: Main DAIKIN 4006121; Printed Circuit Assy. (Fan) DAIKIN 4006122
Expansion Valve: Valve Fujikoki 2SA50046-1-KE
Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71
Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 20Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXMQ12PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 61 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
99
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.90 1.0 1.5 4.64 3.48 1.93 0.77
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
30.0 42.5 12.0 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P288941-1, Fan: Sirocco Fan 350W Panasonic 3P259061-2
Printed Circuit Board: Printed Circuit Assy. DAIKIN 1863862; Printed Circuit Assy. (Inverter) DAIKIN 2007595; Main DAIKIN 4006121,
Expansion Valve: Valve Fujikoki 2SA50046-1-SU
Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71
Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 21Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXMQ18PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 62 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
128
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end .
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.98 1.0 1.5 4.77 3.58 1.99 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
30.0 58.5 12.0 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P288942-1, Fan: Sirocco Fan 350W Panasonic 3P204674-2
Printed Circuit Boards: Inverter Assy. DAIKIN 2007588; DAIKIN 1863862; Main DAIKIN 4006121, Expansion Valve: Valve Fujikoki
2SA50046-2-KA
Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71
Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 22Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXMQ48PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 63 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
212
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.98 1.0 1.5 4.77 3.58 1.99 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
33.5 44.5 18.5 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger 8 mm x 0.3 mm coil DAIKIN CRB-FXYMP224M
Fan: Sirocco Fan 380W TOP 3P028033-1, Printed Circuit Board: Main DAIKIN 1962257
Expansion Valve: Valve Fujikoki 2SA50046-2-KA
Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71
Group Control Adaptor PCB
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 23Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXMQ48MFVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 64 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
376
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with 1/2” washers and nuts above and below mounting ears &
(8) 1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.92 1.0 1.5 4.67 3.50 1.95 0.78
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
44.5 58.5 19.5 N/A N/A
Options/Subcomponent Summary:
Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CRB-FXYMP280M
Fan: Sirocco Fan (380W x 2) TOP 3P028033-1, Printed Circuit Boards: Main DAIKIN 1962257; Main DAIKIN 1962219
Expansion Valve: Valve Fujikoki 2SA50046-2-KE
Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71
Group Control Adaptor PCB
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel. Plastic enclosure with #10 SMS at each mounting ear (4
total)
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 24Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXMQ96MVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 65 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
25
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted with (4) 3/8”Ø A36 hanger rods & (8) 1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end. Unit
maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.98 1.0 1.5 4.77 3.58 1.99 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
13.0 12.5 8.1 N/A N/A
Options/Subcomponent Summary:
Printed Circuit Board: Main DAIKIN 1893591
Valves: BODY/ MOTOR OPERATED VALVE DAIKIN 1801408; COIL/ MOTOR OPERATED VALVE DAIKIN 1801299; BODY/ MOTOR
OPERATED VALVE DAIKIN 1801390; COIL/ MOTOR OPERATED VALVE DAIKIN 1801282; BODY/ MOTOR OPERATED VALVE DAIKIN
1801390; COIL/ MOTOR OPERATED VALVE DAIKIN 1801275; BODY/ MOTOR OPERATED VALVE DAIKIN 1801415; COIL/ MOTOR
OPERATED VALVE DAIKIN 1801268; BODY/ MOTOR OPERATED VALVE DAIKIN 1801415; COIL/ MOTOR OPERATED VALVE DAIKIN
1801251UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Branch Selector: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 25Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: BSVQ36PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 66 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
203
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.95 1.0 1.5 4.72 3.54 1.97 0.79
Test Mounting Details:
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
25.0 62.1 8.1 N/A N/A
Options/Subcomponent Summary:
Printed Circuit Board: Main DAIKIN 2058618
Valves: COIL/ MOTOR OPERATED VALVE (MAIN SUCTION)DAIKIN 1939738; COIL/ MOTOR OPERATED VALVE (MAIN DISCHARGE)
DAIKIN 1939745; COIL/ MOTOR OPERATED VALVE (SUB SUCTION) DAIKIN 1939752; COIL/ MOTOR OPERATED VALVE (SUB
DISCHARGE)
DAIKIN 1939769; COIL/ MOTOR OPERATED VALVE (SUB COOL) DAIKIN 1939776
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Branch Selector: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 26Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: BSV6Q36PVJU Serial Number: N/A
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 67 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
444
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Rigid base mounted with (4) 3/8ӯ A307 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.5 1.0 1.5 4.00 3.00 1.67 0.67
Test Mounting Details:
>33.3
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
30.2 36.7 66.7 5.4 21.2
Options/Subcomponent Summary:
Heat Exchanger: 7mm x 0.3mm coil, Daikin 7009440
Compressor: 72,000 BTU/hr, 208-230V, Carbon Steel, Daikin 1873054
Fan Motor: Propellor Fan 500 Watts, 208-230V, Panasonic, 1713309
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Heat Pump: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 27Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RXYQ72TTJU Serial Number: 1510195615
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 68 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
702
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
30.2 48.9 66.7 4.5 6.8
Rigid base mounted with (4) 3/8ӯ A307 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
>33.3
Options/Subcomponent Summary:
Heat Pump: carbon steel enclosure with seismic enhancements: (3) #10 self tapping screws in each foot (12 total)
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 28Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RXYQ168TYDN Serial Number: 1510119528
Product Construction Summary:
Heat Exchanger: 7mm x 0.3mm coil, Daikin 7009559
Compressor: 96,000 BTU/hr, 460V, Carbon Steel, Daikin 7009494
Fan Motor: Propellor Fan 650 Watts, 460V, Panasonic, 4012442
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 69 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
518
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
Rigid base mounted with (4) 3/8ӯ A307 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
2.5 1.0 1.5 4.00 3.00 1.67 0.67
Test Mounting Details:
>33.3
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
30.2 36.7 66.7 4.9 7.5
Options/Subcomponent Summary:
Heat Exchanger: 7mm x 0.3mm coil, Daikin 7500019
Compressor: 72,000 BTU/hr, 208-230V, Carbon Steel, Daikin 7009487
Fan Motor: Propellor Fan 400 Watts, 208-230V, Panasonic, 2219437
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Heat Pump: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 29Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: REYQ72TTJU Serial Number: 1510085242
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 70 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
798
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
30.2 48.9 66.7 4.2 5.4
Rigid base mounted with (4) 3/8ӯ A307 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
>33.3
Options/Subcomponent Summary:
Heat Pump: carbon steel enclosure with seismic enhancements: (3) #10 self tapping screws in each foot (12 total)
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 30Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: REYQ168TYDN Serial Number: 1506206866
Product Construction Summary:
Heat Exchanger: 7mm x 0.3mm coil, Daikin 7500099
Compressors: 96,000 BTU/hr, 460V, Carbon Steel, Daikin 7009494 and 7009548
Fan Motor: Propellor Fan 650 Watts, 460V, Panasonic, 4012442
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 71 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
48
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
18.9 14.6 11.8 N/A N/A
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A
Options/Subcomponent Summary:
Branch Selector: carbon steel enclosure with seismic enhancements: Additional (4) #10 self tapping screws in each mounting ear
connection
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 31Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: BS4Q54TVJ Serial Number: A001008
Product Construction Summary:
Valves: COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271194; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227476; COIL/ ELECTRONIC EXP.
VALVE ASSY., DAIKIN 2227515; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271202; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227469;
COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227508; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271219; COIL/ ELECTRONIC EXP. VALVE
ASSY., DAIKIN 2227452; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227490; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271226; COIL/
ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227445; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227483
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 72 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
104
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
18.9 32.3 11.8 N/A N/A
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A
Options/Subcomponent Summary:
Branch Selector: carbon steel enclosure with seismic enhancements: 1/8" steel backer plate behind each mouting ear with (2)
machine screws through each mounting ear.
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 32Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: BS12Q54TVJ Serial Number: A000140
Product Construction Summary:
Valves: COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271194; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227476; COIL/ ELECTRONIC EXP. VALVE
ASSY., DAIKIN 2227515; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271202; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227469; COIL/
ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227508; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271219; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN
2227452; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227490; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271226; COIL/ ELECTRONIC EXP.
VALVE ASSY., DAIKIN 2227445; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227483
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 73 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
56
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
37.4 37.4 7.8 N/A N/A
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A
Options/Subcomponent Summary:
Indoor Fan Coil (ceiling mounted): plastic and carbon steel cabinet with seismic upgrades: Four (4) 15/32” x 4-1/2” x 0.041”
extension springs between grille cover and unit corner, fastened to existing screws and retightened. Springs extended
approximately 2”. Heavy duty square washer (1.5”x1.5”) top and bottom of mounting bracket with (2) ½” flat washers as spacers
on top only.
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 33Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXUQ18PVJU Serial Number: C000176
Product Construction Summary:
Heat Exchanger: 7mm x 0.3mm coil, Daikin 2273936
Fan Motor: QTS48D11M Turbo Fan 46W, 208-230V, Panasonic 2110749
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 74 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
54
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
33.1 33.1 9.7 N/A N/A
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A
Options/Subcomponent Summary:
Indoor Fan Coil (ceiling mounted): plastic and carbon steel enclosure with seismic upgrades: Eight (8) #10 SMS in each mounting
ear. Four (4) cable tie (shipped with unit) chains, each with two links, between decoration panel cover latches and through
mounting ear. Two (2) strips of heavy duty Velcro® tape 1” x 2” at each corner cover (eight total).
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 35Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXFQ07TVJU Serial Number: C000406
Product Construction Summary:
Heat Exchanger: 7mm x 0.3mm coil, Daikin 1993028
Fan Motor: QTS48C15M Turbo Fan 48W, 208-230V, Panasonic 1993105
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 75 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
175.5
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
12.6 37.0 39.0 13.21 12.1
In addition to (4) 1/2” Grade 5 bolts used at the mounting feet, UUT #37 was also secured to the shake table with stainless-steel
strapping. Two (2) stainless steel straps ( ¾” wide and 0.02” thick) were secured approximately 30˚relative to vertical surface of
the unit to the shake table with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws at each end of the strapping. The strapping
was affixed to the top of the test unit with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
> 33.3
Options/Subcomponent Summary:
Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 37Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RXTQ36TAVJU Serial Number: F000419
Product Construction Summary:
Daikin Heat Exchanger 6021439
Daikin Swing Compressor 15.3A 6025911
Fan Motor 200W Daikin 6016145
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 76 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
221.5
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
12.6 35.4 52.9 >33.3 10.97
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
In addition to (4) 1/2” Grade 5 bolts used at the mounting feet, UUT #38 was also secured to the shake table with stainless-steel
strapping. Two (2) stainless steel straps ( ¾” wide and 0.02” thick) were secured approximately 30˚relative to vertical surface of
the unit to the shake table with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws at each end of the strapping. The strapping
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
> 33.3
Options/Subcomponent Summary:
Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 38Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RXTQ60TAVJU Serial Number: F001523
Product Construction Summary:
Daikin Heat Exchanger 6019584
Swing Compressor 23.2A Daikin 2025911
Fan Motor (2) 70W Daikin 2024336
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 77 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
439
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
22.2 30.2 38.6 10.25 8.80
Rigid base mounted with (4) 5/8”Grade 5 bolts
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.671.5
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
20.52
Options/Subcomponent Summary:
Outdoor Water Cooled Heat Recovery: carbon steel cabinet
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 39Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RWEQ96TATJU Serial Number: 1700004
Product Construction Summary:
Daikin Heat Exchanger 5018937, Scroll Compressor Daikin 5018933, Daikin Fan Motor 5019722
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 78 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
94.5
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
17.5 45.0 10.68 10.65
3.2 2.41.5
UUT#40 was mounted on plenum boxes. The plenum box was constructed of 10-gauge carbon steel. UUT#40’s plenum box
dimensions are as follows: 21.25” x 18.5” x 25.12” with a weight 80.5 lbs. UUT #40 was secured to the plenum box with (5) #10 -16
x 1-1/2” screws on both the right and left side at the junction of the AHU and plenum box. The AHU/plenum box was secured to
the shake table with steel angles. Two L2.5x2x3/16 LLV, each side w/ (2) #10-16 x 1-1/2” screws w/ integral washer through
slotted hole to unit and 3/8” Grade 5 bolt w/ washer and lock washer to table.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
1.67 0.67
1/2 Hp Fan Motor, electric expansion valve-Daikin 3S500048-1, Daikin Heat Exchanger 0270A01156
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
11.121.0
Air Handling Unit: carbon steel enclosure mounted to plenum box.
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 40Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXTQ09TAVJU Serial Number: 1702209059
Product Construction Summary:
Options/Subcomponent Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 79 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
147
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
24.5 58.0 8.83 12.45
3.2 2.41.5
UUT #41 was mounted on plenum boxes. The plenum box was constructed of 10-gauge carbon steel. UUT#41’s plenum box
dimensions are as follows: 21.25” x 25.5” x 25.12” with a weight 98.0 lbs. UUT #41 was secured to their respective plenum boxes
with (5) #10 -16 x 1-1/2” screws on both the right and left side at the junction of the AHU and plenum box. The AHU/plenum box
was secured to the shake table with steel angles. Two L2.5x2x3/16 LLV, each side w/ (2) #10-16 x 1-1/2” screws w/ integral washer
through slotted hole to unit and 3/8” Grade 5 bolt w/ washer and lock washer to table.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
1.67 0.67
1 Hp Fan Motor, electric expansion valve-Daikin 3S500054-1, Daikin Heat Exchanger 0270A01206
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
27.6321.0
Air Handling Unit: carbon steel enclosure mounted to plenum box.
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 41Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXTQ60TAVJU Serial Number: 1710220821
Product Construction Summary:
Options/Subcomponent Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 80 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
60.5
SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
2.0 1.0
2.5 0.0
37.4 7.8 N/A N/A
3.2 2.41.5
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-0 clips at
each end.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
1.67 0.67
Heat Exchanger: 7mm x 0.3mm coil, Daikin 2110756
Fan Motor: QTS48D11M Turbo Fan 106W, 208-230V, Panasonic
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A37.4
Indoor Fan Coil (ceiling mounted): plastic and carbon steel enclosure with seismic upgrades: Heavy duty square washers (1.6" x
1.3 x 0.2”) were used at top and bottow of mounting bracket. S-Shape hooks on four (4) internal wires, used to secure outer cover
attachment to uni t, were crimped closed to secure cover to unit.
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 42Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXUQ36PVJU
Serial Number: C000618
Product Construction Summary:
Options/Subcomponent Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 81 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
450.5
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0
2.5 0.0
27.37
Base mounted with four (4) 5/8" Grade 8 bolts with lock and flat washer.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
22.1 30.1 38.6 7.36 9.40
1.5
Options/Subcomponent Summary:
3.2 2.4
Scroll Compressor (Daikin) PN: JT16KADWYDN@S, Heat Exchanger (Daikin) PN: 5018937
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
1.67 0.67
Outdoor Water Cooled Heat Recovery: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 45Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RWQEQ144TAYDU Serial Number: 1800331
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 82 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
51
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0
2.5 0.0
31.5 21.7 9.7 N/A N/A
Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-0 clips at
each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. See next page for details.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
2.4 1.67 0.673.21.5
Options/Subcomponent Summary:
Heat Exchanger (Daikin) PN: 2397793, Expansion Valve (Daikin) PN: 4015738, Fan Assembly (Sirocco) PN: 2397818, Fan Motor
(Panasonic) PN: 4015745
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/a
Indoor Fan Coil (ceiling mounted): carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 46Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXSQ07TAVJU Serial Number: E000654
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 83 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 46Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXSQ07TAVJU Serial Number: E000654
Modification Details:
Six (6) #12 -3/4" self tapping screws added to the four (4) mounting ears on the unit.
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 84 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
110.5
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0
2.5 0.0
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.2 2.4
31.5 61.0 9.7 N/A N/A
1.671.5
Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-
0 clips at each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. One additional #12- 3/4" self tapping
screw was added to the ebox. See next page for details.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
0.67
Test Mounting Details:
Indoor Fan Coil (ceiling mounted): carbon steel enclosure
Options/Subcomponent Summary:
Heat Exchanger (Daikin) PN: 2397933, Expansion Valve (Daikin) PN: 2371955, Fan Assembly (Sirocco) PN: 2P394978-1, Fan Motor
(Panasonic) PN: 4016361
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 47Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXSQ54TAVJU Serial Number: E000181
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 85 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 47Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXSQ54TAVJU Serial Number: E000181
Modification Details:
Single #12-3/4" self tapping screw added to Ebox.
Six (6) #12 -3/4" self tapping screws added to the four (4) mounting ears on the unit.
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 86 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
41.5
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0
2.5 0.01.5
Test Mounting Details:
21.6 21.6 10.3 N/A N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 2.4 1.67 0.67
N/A
Options/Subcomponent Summary:
Heat Exchanger (Daikin) PN: 5011000, Expansion Valve (Daikin) PN: 2108342, Turbo Fan Rotor (Sirocco) PN: 5011010, Fan Motor
(Panasonic) PN: 5011038
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-
0 clips at each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. One additional #12- 3/4" self tapping
screw was added to the Ebox. See next page for details.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
Indoor Fan Coil (ceiling mounted): carbon steel enclosure and plastic decorative panel
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 48Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXZW09TAVJU Serial Number: J002344
Product Construction Summary:
3.2
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 87 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 48Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXZW09TAVJU Serial Number: J002344
Modification Details:
Single #12-3/4" self tapping screw added to Ebox
1
2
1. 3M Dual Lock Velcro used to secure filter.2. Stainless steel hanging wire, 50lb, and 1/16" ferrule used to secure each hinge.
#18-1" sheet metal screw added to outside of filter door
1
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 88 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
46
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0
2.5 0.0
N/A
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.2 2.4
21.6 21.6 10.3 N/A N/A
1.671.5
Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-
0 clips at each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. One additional #12- 3/4" self tapping
screw was added to the ebox. See next page for details.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
0.67
Test Mounting Details:
Indoor Fan Coil (ceiling mounted): carbon steel enclosure and plastic decorative panel
Options/Subcomponent Summary:
Heat Exchanger (Daikin) PN: 5011003, Expansion Valve (Daikin) PN: 2110073, Turbo Fan Rotor (Sirocco) PN: 5011010, Fan Motor
(Panasonic) PN: 5011038
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 49Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXAQ18TAVJU Serial Number: J002138
Product Construction Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 89 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 49Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FXAQ18TAVJU Serial Number: J002138
Modification Details:
t
Single #12-3/4" self tapping screw added to Ebox
1
1
2
1. 3M Dual Lock Velcro used to secure filter.2. Stainless steel hanging wire, 50lb, and 1/16" ferrule used to secure each hinge.
#18-1" sheet metal screw added to outside of filter door
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 90 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
714
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0
2.5 0.01.5
14.1030.2
Outdoor Heat Recovery: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 50Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: REYQ72XATJU Serial Number: 999999999-2
Product Construction Summary:
Options/Subcomponent Summary:
Vapor Injection Scroll Compressor (Daikin) PN: JT160KADWTJ@T, Heat Exchanger (Daikin) PN: 3P341763-2, Heat Exchanger Plate
HX (Daikin) PN: 3P412977-1, Fan Motor (Daikin) PN: 2P360713-3
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
48.9 66.7
Base mounted with four (4) 1/2-13 Grade 8 bolts with lock and flat washer. Three (3) #12 3/4" self tapping screws were added at
each foot.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.67
3.43 7.22
Three #12 3/4" Self Tapping Screws
1/2" -13 Grade 8 Bolt
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 91 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001-R1
785
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0
2.5 0.01.5
>33.330.2
Outdoor Heat Recovery: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 51Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: REYQ168XATDU Serial Number: 999999999-2
Product Construction Summary:
Options/Subcomponent Summary:
Vapor Injection Scroll Compressor (Daikin) PN: JT25KADWYDN@S, Heat Exchanger (Daikin) PN: 3P341763-2, Heat Exchanger
Plate HX (Daikin) PN: 39412975-1, Fan Motor (Daikin) PN: 2P343735-1
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
48.9 66.7
Base mounted with four (4) 1/2-13 Grade 8 bolts with lock and flat washer. Three (3) #12 3/4" self tapping screws were added at
each foot.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.2 2.4 1.67 0.67
3.48 5.71
Three #12 3/4" Self Tapping Screws
1/2" -13 Grade 8 Bolt
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 92 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001 R1
1002
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0 1.5
2.5 0.0 1.5
12.8330.5
Outdoor Heat Recovery: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 52Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: REYQ240AAYDA Serial Number: MT20007
Product Construction Summary:
Options/Subcomponent Summary:
Vapor Injected Scroll Compressor: Daikin - 240,000 BTU/HR
Fan Motor: Daikin (2P618618-1) - 950W x 2
Heat Exchanger: Daikin (2P623585-1)
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
67.0 65.4
Base mounted - rigid with (6) 1/2" - 8 Grade hex-head bolts, washers, and lock washers
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156
Test Mounting Details:
3.20 2.40 1.67 0.67
4.16 30.36
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 93 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001 R1
554
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0 1.5
2.5 0.0 1.5
36.6 65.4
Test Mounting Details:
Base mounted - rigid with (6) 1/2" - 8 Grade hex-head bolts, washers, and lock washers. Used center wind slots.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67
5.17 8.54
Scroll Compressor: Daikin - 72,000 BTU/HR
Fan Motor: Daikin (2P618618-1)
Heat Exchanger: Daikin (2P626353-1)
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
>33.330.5
Outdoor Heat Recovery: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 53Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: REYQ72AATJA Serial Number: N/A
Product Construction Summary:
Options/Subcomponent Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 94 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001 R1
50
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0 1.5
2.5 0.0 1.5
Test Mounting Details:
Ceiling mounted - rigid with w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & four (4) 3/32” Ø diag. cable braces w/ Mason
SCB-0/SCBH-0 clips at each end. Washers at mounting were square plate washers.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67
N/A N/A
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A13.8 23.4 9.5
Branch Selector: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 54Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: BSF4Q54TVJ Serial Number: A00026
Product Construction Summary:
Options/Subcomponent Summary:
EEV Body: Fujikoki (3S500038-1)
EEV Coil: Fujikoki (3P363865-1)
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 95 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001 R1
83.5
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0 1.5
2.5 0.0 1.5
24.0 9.5
Test Mounting Details:
Ceiling suspended/mounted - rigid Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag.
cable braces w/ Mason SCB-0/SCBH-0 clips at each end. Washers used for mounting were square plate washers
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67
N/A N/A
EEV Body: Fujikoki (3S500040-1)
EEV Coil: Fujikoki (3P389855-1)
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A23.8
Branch Selector: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 55Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: BSF8Q54TVJ Serial Number: A001054
Product Construction Summary:
Options/Subcomponent Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 96 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001 R1
37
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0 1.5
2.5 0.0 1.5
47.0 13.4
Test Mounting Details:
Wall mounted - rigid with (9) 8-32 wood screws used to mount the mounting plate (see Image 2) . Additional (3) M4 x 1/2" screws
and used at base of unit (See Image 3).
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67
N/A N/A
Fan Motor: Daikin (KFD-325-64-84)
Heat Exchanger: Daikin (1P222779-1)
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
N/A10.3
Indoor Fan Coil (wall mounted):plastic enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 56Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: FTX36NVJU Serial Number: E035579
Product Construction Summary:
Options/Subcomponent Summary:
Image 1
Image 2
Image 3
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 97 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001 R1
131.5
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0 1.5
2.5 0.0 1.5
34.3 28.9
Test Mounting Details:
Base mounted - rigid with (4) 3/8" - 8 Grade hex-head bolts, washers, and lock washers.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67
5.97 13.96
Compressor: Daikin (2YC63AAXD)
Fan Motor: Panasonic (D901B-37)
Heat Exchanger: Daikin (3P379239-1)
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
>33.312.5
Heat Pump: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 57Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RK36NMVJUA Serial Number: E004712
Product Construction Summary:
Options/Subcomponent Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 98 of 99
OSP-0297
Mohammad Karim
05/17/2022
2100103-CR-001 R1
132
SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)
2.0 1.0 1.5
2.5 0.0 1.5
34.3 28.9
Test Mounting Details:
Base mounted - rigid with (4) 3/8" - 8 Grade hex-head bolts, washers, and lock washers.
Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.
Contents were included in testing per operating conditions.
UUT Highest Passed Seismic Run Information
Building Code Test Criteria
CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67
6.42 14.89
Compressor: Daikin (2YC63AAXD)
Fan Motor: Panasonic (D901B-37)
Heat Exchanger: Daikin (3P379239-1)
UUT Properties
Weight
(lb)
Dimension (in) Lowest Natural Frequency (Hz)
Depth Width Height Front-Back Side-Side Vertical
>33.312.5
Heat Pump: carbon steel enclosure
UNIT UNDER TEST (UUT)SUMMARY SHEET
Manufacturer: Daikin North America, LLC
UUT 58Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV
Model Number: RX36NMVJUA Serial Number: E008172
Product Construction Summary:
Options/Subcomponent Summary:
TRU Compliance, by Structural Integrity Associates, Inc.
844-TRU-0200 | info@trucompliance.com 05/17/2022
OSP-0297
Page 99 of 99
OSP-0297
Mohammad Karim
05/17/2022