OSP-0297 | HCAI

99
APPLICATION FOR HCAI SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP) OFFICE USE ONLY APPLICATION #: OSP-0297 HCAI Special Seismic Certification Preapproval (OSP) Type: New X Renewal Manufacturer Information Manufacturer: Daikin North America, LLC Manufacturer's Technical Representative: Caglar Oburoglu Mailing Address: Daikin Texas Technology Park, 19001 Kerm, Waller, TX 77484 Telephone: (713) 861-2500 Email: [email protected] Product Information Product Name: Product Type: Product Model Number: General Description: Mounting Description: Air Conditioning Units Air Conditioning Units - Split Varies, see attachment. Indoor and outdoor heating and cooling units steel enclosures. Rigid base mounted, rigid wall mounted, and ceiling suspended. Applicant Information Applicant Company Name: Structural Integrity Associates, Inc. dba TRU Compliance Contact Person: Katie Braman Mailing Address: 5215 Hellyer Ave., Suite 210, San Jose, CA 95138 [email protected] Email: (844) 878-0200 Telephone: Title: Program Manager, TRU Compliance Tested Seismic Enhancements: Seismic enhancements made to the test units and/or modifications required to address anomalies during the tests shall be incorporated into the production units. DEPARTMENT OF HEALTH CARE ACCESS AND INFORMATION FACILITIES DEVELOPMENT DIVISION 05/17/2022 OSP-0297 Page 1 of 99 OSP-0297 Mohammad Karim 05/17/2022

Transcript of OSP-0297 | HCAI

APPLICATION FOR HCAI SPECIAL SEISMIC CERTIFICATION PREAPPROVAL (OSP)

OFFICE USE ONLY

APPLICATION #: OSP-0297

HCAI Special Seismic Certification Preapproval (OSP)

Type: New X Renewal

Manufacturer Information

Manufacturer: Daikin North America, LLC

Manufacturer's Technical Representative: Caglar Oburoglu

Mailing Address: Daikin Texas Technology Park, 19001 Kerm, Waller, TX 77484

Telephone: (713) 861-2500 Email: [email protected]

Product Information

Product Name:

Product Type:

Product Model Number:

General Description:

Mounting Description:

Air Conditioning Units

Air Conditioning Units - Split

Varies, see attachment.

Indoor and outdoor heating and cooling units steel enclosures.

Rigid base mounted, rigid wall mounted, and ceiling suspended.

Applicant Information

Applicant Company Name: Structural Integrity Associates, Inc. dba TRU Compliance

Contact Person: Katie Braman

Mailing Address: 5215 Hellyer Ave., Suite 210, San Jose, CA 95138

[email protected]:(844) 878-0200Telephone:

Title: Program Manager, TRU Compliance

Tested Seismic Enhancements: Seismic enhancements made to the test units and/or modifications required to address anomalies during the tests shall be incorporated into the production units.

DEPARTMENT OF HEALTH CARE ACCESS AND INFORMATIONFACILITIES DEVELOPMENT DIVISION

05/17/2022

OSP-0297

Page 1 of 99

OSP-0297

Mohammad Karim

05/17/2022

Company Name: STRUCTURAL INTEGRITY ASSOCIATES, INC.

Name: Andrew Coughlin

Mailing Address: 5215 Hellyer Ave, Suite 101, San Jose, CA 95138-1025

[email protected]:(415) 635-8461Telephone:

California Licensed Structural Engineer Responsible for the Engineering and Test Report(s)

S6082California License Number:

Certification Method

GR-63-Core

Other (Please Specify):

ICC-ES AC156X IEEE 344 IEEE 693 NEBS 3

Testing Laboratory

Company Name: CLARK TESTING LABORATORY, INC.

Contact Person: Devon Lohr

Mailing Address: 1801 Route 51, Jefferson Hills PA 15025

[email protected]:(412) 387-1004Telephone:

Company Name: ENVIRONMENTAL TESTING LABORATORIES, INC. (ETL)

Contact Person: Jeremy Lange

Mailing Address: 11034 Indian Trail, Dallas TX 75229-3513

[email protected]:(972) 247-9657Telephone:

Company Name: QUALTECH/CURTISS WRIGHT/TRENTEC

Contact Person: Jerry Newberry

Mailing Address: 4600 East Tech Drive, Cincinnati OH 45245

[email protected]:(513) 528-7900Telephone:

DEPARTMENT OF HEALTH CARE ACCESS AND INFORMATIONFACILITIES DEVELOPMENT DIVISION

05/17/2022

OSP-0297

Page 2 of 99

OSP-0297

Mohammad Karim

05/17/2022

HCAI Approval (For Office Use Only) - Approval Expires on 05/17/2028

Date: 5/17/2022

Name: Mohammad Karim Title: Supervisor, Health Facilities Review

Special Seismic Certification Valid Up to: SDS (g) = See Above

Condition of Approval (if applicable):

z/h = See Above

1.50 (SDS = 2.00, z/h = 1); 1.13 (SDS = 2.50, z/h = 0)

Seismic Parameters

Design Basis of Equipment or Components (Fp/Wp) =

SDS (Design spectral response acceleration at short period, g) =

ap (Amplification factor) =

Rp (Response modification factor) =

Ω0 (System overstrength factor) =

Ip (Importance factor) =

z/h (Height ratio factor) =

Natural frequencies (Hz) =

Overall dimensions and weight =

2.00 (z/h = 1); 2.50 (z/h = 0)

2.5

6.0

2.0

1.5

1 and 0

See Attachment

See Attachment

DEPARTMENT OF HEALTH CARE ACCESS AND INFORMATIONFACILITIES DEVELOPMENT DIVISION

05/17/2022

OSP-0297

Page 3 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

11.3 30.1 21.6 75 1

11.2 31.3 22.4 99 Interp.

11.3 30.1 21.6 75 Interp.

11.2 31.3 22.4 99 Interp.

11.8 32.5 28.9 104 Interp.

11.2 31.3 22.4 99 Interp.

11.8 32.5 28.9 104 Interp.

12.6 35.4 30.3 159 2

12.6 37.0 38.9 179 Interp.

12.6 37.0 38.9 179 Interp.

12.6 37.0 38.9 179 Interp.

12.6 37.0 38.9 179 3

2Requires mounting w/ (4) 1/16”x1-1/2” angled aluminum straps approximately 30˚relative to vertical surface of the unit with (2)

#10 SMS to top of unit & 1/4ӯ bolt to floor

1Requires seismic enhancements: (4) ties from grille to unit frame, ties made of stainless steel 15" length by 3/16" width.

RKS36_VJU1,2

RXS36_VJU1,2

Outdoor Heat Pump

(Split System,

Quaternity, SkyAir)

9,000 to 36,000

BTU/hr; Qualified

design categories: L

RKS30_VJU1,2

RXS30_VJU1,2

RXS18_VJU1

RXS24_VJU1

RXS15_VJU1

RXG15_VJU1

RXS12_VJU1

RXG12_VJU1

RXS09_VJU1

RXG09_VJU1

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 4 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

30.2 36.7 66.7 435 27

30.2 36.7 66.7 451 Interp.

30.2 48.9 66.7 525 Interp.

30.2 48.9 66.7 553 Interp.

30.2 48.9 66.7 528 Interp.

30.2 48.9 66.7 556 Interp.

30.2 48.9 66.7 695 Interp.

30.2 48.9 66.7 709 Interp.

30.2 48.9 66.7 695 Interp.

30.2 48.9 66.7 709 28

30.2 85.6 66.7 963 Interp.

30.2 85.6 66.7 1007 Interp.

30.2 97.8 66.7 1053 Interp.

30.2 60.4 66.7 133 Interp.

30.2 97.8 66.7 1056 Interp.

30.2 97.8 66.7 1112 Interp.

30.2 97.8 66.7 1223 Interp.

30.2 97.8 66.7 1265 Interp.

30.2 97.8 66.7 1390 Interp.

30.2 97.8 66.7 1418 Interp.

30.2 97.8 66.7 1390 Interp.

30.2 97.8 66.7 1418 Interp.

RXYQ288_TJ_1 2 x RXYQ144

RXYQ288_YD_1 2 x RXYQ144

RXYQ264_TJ_1 RXYQ144 + RXYQ120

RXYQ264_YD_1 RXYQ144 + RXYQ120

RXYQ312_TJ_1 RXYQ168 + RXYQ144

RXYQ312_YD_1 RXYQ168 + RXYQ144

2 x RXYQ120RXYQ240_YD_1

RXYQ120_TJ_1

RXYQ120_YD_1

RXYQ96_TJ_1

RXYQ96_YD_1

RXYQ216_TJ_1 RXYQ120 + RXYQ96

RXYQ72_TJ_

RXYQ72_YD_

RXYQ144_TJ_1

RXYQ144_YD_1

RXYQ240_TJ_1 2 x RXYQ120

RXYQ216_YD_1 RXYQ120 + RXYQ96

Outdoor Heat Pump

(VRV) 72,000 to

408,000 BTU/hr

(cooling capacity);

Qualified design

categories: T, TA, XA2

RXYQ192_TJ_1 RXYQ120 + RXYQ72

RXYQ192_YD_1 RXYQ120 + RXYQ72

RXYQ168_TJ_1

RXYQ168_YD_1

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)2Qualified design category X, TA , and XA differ only in coil color.

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 5 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

30.2 97.8 67 1418 Interp.

30.2 171.1 67 1926 Interp.

30.2 146.6 67 1668 Interp.

30.2 146.6 67 2085 Interp.

30.2 146.6 67 1818 Interp.

30.2 183.3 67 2186 Interp.

30.2 146.6 67 1971 Interp.

30.2 183.3 67 2186 Interp.

30.2 36.7 66.7 507 29

30.2 36.7 66.7 527 Interp.

30.2 48.9 66.7 703 Interp.

30.2 48.9 66.7 717 Interp.

30.2 48.9 66.7 703 Interp.

30.2 48.9 66.7 717 Interp.

30.2 48.9 66.7 780 Interp.

30.2 48.9 66.7 794 Interp.

30.2 48.9 66.7 780 Interp.

30.2 48.9 66.7 794 30

30.2 85.6 66.7 1210 Interp.

30.2 85.6 66.7 1244 Interp.

30.2 97.8 66.7 1406 Interp.

30.2 97.8 66.7 1406 Interp.

REYQ216_ATJ_1

2 x RXYQ168

RXYQ408_TJ_1 RXYQ168 + RXYQ144 + RXYQ96

RXYQ408_YD_1 RXYQ168 + RXYQ144 + RXYQ96

REYQ72_ATJ_

RXYQ336_YD_1 2 x RXYQ168

RXYQ360_TJ_1 3 x RXYQ120

RXYQ168 + RXYQ120 + RXYQ96

RXYQ384_YD_1 RXYQ168 + RXYQ120 + RXYQ96

REYQ120 + REYQ96

REYQ216_AYD_1 REYQ120 + REYQ96

REYQ72_AYD_

REYQ96_ATJ_1

REYQ96_AYD_1

REYQ120_ATJ_1

3 x RXYQ120

RXYQ384_TJ_1

RXYQ336_TJ_1

REYQ120 + REYQ72

REYQ120_AYD_1

REYQ144_ATJ_1

REYQ144_AYD_1

REYQ168_ATJ_1

REYQ168_AYD_1

REYQ192_ATJ_1 REYQ120 + REYQ72

REYQ192_AYD_1

RXYQ360_YD_1

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)2Qualified design category X, TA , and XA differ only in coil color.

Outdoor Heat

Recovery Units (VRV

IV) 72,000 to 456,000

BTU/hr (cooling

capacity);

Qualified design

categories: T

Outdoor Heat Pump

(VRV) 72,000 to

408,000 BTU/hr

(cooling capacity);

Qualified design

categories: T, TA, XA2

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 6 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

30.2 97.8 66.7 1483 Interp.

30.2 97.8 66.7 1511 Interp.

30.2 97.8 66.7 1483 Interp.

30.2 97.8 66.7 1511 Interp.

30.2 97.8 66.7 1560 Interp.

30.2 97.8 66.7 1588 Interp.

30.2 97.8 66.7 1560 Interp.

30.2 97.8 66.7 1588 Interp.

30.2 97.8 66.7 1560 Interp.

30.2 97.8 66.7 1588 Interp.

30.2 149.7 66.7 2109 Interp.

30.2 149.7 66.7 2151 Interp.

30.2 149.7 66.7 2186 Interp.

30.2 149.7 66.7 2228 Interp.

30.2 149.7 66.7 2340 Interp.

30.2 149.7 66.7 2305 Interp.

30.2 149.7 66.7 2340 Interp.

30.2 149.7 66.7 2382 Interp.

30.2 149.7 66.7 2340 Interp.

30.2 149.7 66.7 2382 Interp.

REYQ240_AYD_1 REYQ144 + REYQ96

REYQ336_ATJ_1 2 x REYQ168

2 x REYQ168

REYQ360_ATJ_1 3 x REYQ120

REYQ240_ATJ_1 REYQ144 + REYQ96

REYQ384_ATJ_1 REYQ168 + REYQ120 + REYQ96

REYQ432_ATJ_1 3 x REYQ144

REYQ408_AYD_1

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

REYQ336_AYD_1

REYQ360_AYD_1 3 x REYQ120

REYQ168 + REYQ120 + REYQ96

REYQ408_ATJ_1 REYQ168 + REYQ144 + REYQ96

REYQ384_AYD_1

3 x REYQ144

REYQ456_ATJ_1 REYQ168 + 2 x REYQ144

REYQ456_AYD_1 REYQ168 + 2 x REYQ144

REYQ432_AYD_1

REYQ312_ATJ_1 REYQ168 + REYQ144

REYQ312_AYD_1 REYQ168 + REYQ144

REYQ288_ATJ_1 2 x REYQ144

REYQ288_AYD_1 2 x REYQ144

REYQ264_ATJ_1 REYQ144 + REYQ120

REYQ264_AYD_1 REYQ144 + REYQ120

Outdoor Heat

Recovery Units (VRV

IV) 72,000 to 456,000

BTU/hr (cooling

capacity);

Qualified design

categories: T

REYQ168 + REYQ144 + REYQ96

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 7 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

30.2 48.9 66.7 714 50

30.2 48.9 66.7 727 Interp.

30.2 48.9 66.7 727 Interp.

30.2 48.9 66.7 727 Interp.

30.2 48.9 66.7 727 Interp.

30.2 48.9 66.7 727 Interp.

30.2 48.9 66.7 785 Interp.

30.2 48.9 66.7 785 Interp.

30.2 48.9 66.7 785 Interp.

30.2 48.9 66.7 785 51

30.2 97.8 66.7 1428 Interp.

30.2 97.8 66.7 1428 Interp.

30.2 97.8 66.7 1441 Interp.

30.2 97.8 66.7 1441 Interp.

30.2 97.8 66.7 1454 Interp.

30.2 97.8 66.7 1454 Interp.

30.2 97.8 66.7 1512 Interp.

30.2 97.8 66.7 1512 Interp.

30.2 97.8 66.7 1512 Interp.

30.2 97.8 66.7 1512 Interp.

30.2 97.8 66.7 1570 Interp.

30.2 97.8 66.7 1570 Interp.

30.2 97.5 66.7 1570 Interp.

REYQ192_ATJ_1 2 x REYQ96

REYQ192_AYD_1

REYQ264_ATJ_1 REYQ120 + REYQ144

REYQ168_AYD_1

REYQ72_ATJ_1

REYQ72_AYD_1

REYQ168_ATJ_1

REYQ96_ATJ_1

REYQ312_AYD_1

REYQ96 + REYQ120

REYQ216_AYD_1 REYQ96 + REYQ120

REYQ240_ATJ_1

2 x REYQ96

REYQ264_AYD_1

REYQ216_ATJ_1

REYQ336_ATJ_1 2 x REYQ168

REYQ288_AYD_1 2 x REYQ144

REYQ312_ATJ_1

REYQ240_AYD_1 2 x REYQ120

REYQ120 + REYQ144

REYQ288_ATJ_1 2 x REYQ144

REYQ144 + REYQ168

REYQ144 + REYQ168

2 x REYQ120

Outdoor Heat

Recovery Units (VRV)

72,000 to 513,000

BTU/hr (cooling

capacity);

Qualified design

categories: X

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

REYQ96_AYD_1

REYQ120_ATJ_1

REYQ120_AYD_1

REYQ144_ATJ_1

REYQ144_AYD_1

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 8 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

30.2 97.8 66.7 1570 Interp.

30.2 146.7 66.7 2297 Interp.

30.2 146.7 66.7 2297 Interp.

30.2 146.7 66.7 2355 Interp.

30.2 146.7 66.7 2355 Interp.

30.2 146.7 66.7 2355 Interp.

30.2 146.7 66.7 2355 Interp.

30.5 36.6 65.4 554 53

30.5 36.6 65.4 554 Interp.

30.5 48.8 65.4 710 Interp.

30.5 48.8 65.4 726 Interp.

30.5 48.8 65.4 713 Interp.

30.5 48.8 65.4 728 Interp.

30.5 48.8 65.4 785 Interp.

30.5 48.8 65.4 801 Interp.

30.5 48.8 65.4 788 Interp.

30.5 48.4 65.4 803 Interp.

30.5 68.8 65.4 957 Interp.

30.5 68.8 65.4 973 Interp.

30.5 68.8 65.4 957 Interp.

30.5 68.8 65.4 973 Interp.

REYQ408_AYD_1 2 x REYQ144 + REYQ120

REYQ432_ATJ_1

REYQ168AATJA2

REYQ168AAYDA2

REYQ144AATJA2

REYQ72AATJA

REYQ72AAYDA

REYQ96AATJA2

REYQ96AAYDA2

REYQ192AATJA2

3 x REYQ144

2 x REYQ144 + REYQ120

REYQ192AAYDA2

REYQ408_ATJ_1

REYQ216AATJA2

REYQ432_AYD_1 3 x REYQ144

REYQ456_ATJ_1

Outdoor Heat

Recovery (VRV) 72,000

to 513,000 BTU/hr

(cooling capacity);

Qualified design

categories: X

1Requires seismic enhancements: (3) #10 self tapping screws in each foot (12 total)2Requires seismic enhancements: Six (6) 1/2" mounting bolts per base unit rather than standard four (4) 1/2" mounting bolts. See

UUT 52 for details.

REYQ216AAYDA2

Outdoor Heat

Recovery (VRV) 69,000

to 456,000 BTU/hr

(cooling capacity);

Qualified design

categories: A

2 x REYQ144 + REYQ168

REYQ456_AYD_1 2 x REYQ144 + REYQ168

REYQ120AATJA2

REYQ120AAYDA2

REYQ336_AYD_1 2 x REYQ168

REYQ144AAYDA2

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 9 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

30.5 68.8 65.4 1002 Interp.

30.5 68.8 65.4 1002 52

30.5 97.6 65.4 1441 Interp.

30.5 97.6 65.4 1514 Interp.

30.5 97.6 65.4 1570 Interp.

30.5 97.6 65.4 1602 Interp.

30.5 97.6 65.4 1573 Interp.

30.5 97.6 65.4 1602 Interp.

30.5 97.6 65.4 1573 Interp.

30.5 97.6 65.4 1606 Interp.

30.5 116.6 65.4 1573 Interp.

30.5 116.6 65.4 1776 Interp.

30.5 137.6 65.4 1914 Interp.

30.5 137.6 65.4 1946 Interp.

30.5 137.6 65.4 1914 Interp.

30.5 137.6 65.4 1946 Interp.

30.5 137.6 65.4 1914 Interp.

30.5 137.6 65.4 1946 Interp.

30.5 137.6 65.4 1959 Interp.

30.5 137.6 65.4 1975 Interp.

30.5 137.6 65.4 2004 Interp.

30.5 137.6 65.4 2004 Interp.REYQ480AAYDA2

2 x REYQ216

2 x REYQ216

REYQ216 + REYQ240

REYQ216 + REYQ240

REYQ192+REYQ168

2 x REYQ168

REYQ360AATJA2 REYQ192+REYQ168

REYQ360AAYDA2

2 x REYQ144

REYQ312AATJA2 REYQ144+REYQ168

REYQ288AAYDA2

2 x REYQ240

2 x REYQ240

REYQ240AATJA2

REYQ240AAYDA2

REYQ264AATJA2 REYQ120+REYQ144

REYQ264AAYDA2

2 x REYQ144

REYQ120+REYQ144

REYQ408AATJA2 REYQ192 + REYQ216

REYQ408AAYDA2 REYQ192 + REYQ216

REYQ312AAYDA2 REYQ144+REYQ168

REYQ336AATJA2 2 x REYQ168

REYQ336AAYDA2

REYQ432AATJA2

REYQ432AAYDA2

REYQ456AATJA2

REYQ456AAYDA2

REYQ480AATJA2

2 x REYQ192

REYQ384AAYDA2 2 x REYQ192

Outdoor Heat

Recovery (VRV) 69,000

to 456,000 BTU/hr

(cooling capacity);

Qualified design

categories: A

2Requires seismic enhancements: Six (6) 1/2" mounting bolts per base unit rather than standard four (4) 1/2" mounting bolts. See

UUT 52 for details.

REYQ288AATJA2

REYQ384AATJA2

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 10 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

12.6 35.4 52.9 221.5 Interp.

12.6 37.0 39.0 172 Interp.

12.6 37.0 39.0 172 Interp.

12.6 35.4 52.9 221.5 Interp.

12.6 35.4 52.9 221.5 Interp.

12.6 35.4 52.9 221.5 Interp.

RZ_36_VJ_1,2,3

39 172

RXTQ48_VJ_1,2

RXTQ60_VJ_1,2 221.5

12.6 37 39 176

RZ_30_VJ_1,2,3

12.6

37

Interp.

38

Interp.

12.6 37

3 Construction of RXSQ, RZR, RZQ is identical to RXTQ, units differ in software only.

2Requires seismic enhancements: (4)ties from grille to unit frame, ties made of stainless steel 15" length by 3/16" width.

Interp.

39

Outdoor Heat Pump

(VRV-IV S) 34,200 to

57,000 BTU/hr;

Qualified design

categories: T

RXSQ60_VJ_1,2,3

Outdoor Heat Pump

(VRV LIFE) 23,00 to

57,000 BTU/hr;

Qualified design

categories: T

RXSQ36_VJ_1,2,3 12.6 37 39 172

RXSQ24_VJ_1,2,3 12.6 37 39 172

RZ_18_VJ_1,2,3

RZ_24_VJ_1,2,3

35.4 52.9

RXTQ36_VJ_1,2

1Required seismic enhancements: Two (2) stainless steel straps ( ¾” wide and 0.02” thick), running perpendicular to the units

width, approximately 30˚relative to vertical surface of the unit, attached with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish

Screws. Two (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws used to attach each end of the strap to the mounting fixture.

RZ_48_VJ_1,2,3

Outdoor Cooling/

Heat Pump (SkyAir)

18,000 to 48,000

BTU/hr;

Qualified design

categories: T

176 Interp.RXSQ48_VJ_1,2,3 12.6 37

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 11 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

22.2 30.1 38.6 423 39

22.2 30.1 38.6 423 Interp.

22.2 30.1 38.6 423 Interp.

22.2 30.1 38.6 426 Interp.

22.2 30.1 38.6 430 Interp.

22.2 30.1 38.6 450.5 45

22.2 30.1 38.6 846 Interp.

22.2 60.2 38.6 852 Interp.

22.2 60.2 38.6 846 Interp.

22.2 60.2 38.6 856 Interp.

22.2 60.2 38.6 846 Interp.

22.2 60.2 38.6 860 Interp.

22.2 60.2 38.6 846 Interp.

22.2 60.2 38.6 880.5 Interp.

131.5 58

131.5

RWEQ192_ATJ_ /ATJ_-HR 2 x RWEQ96

RWEQ192_AYD_ /AYD_-HR 2 x RWEQ96

RWEQ144_ATJ_ /ATJ_-HR

RWEQ144_AYD_ /AYD_-HR

Outdoor Water Cooled

Heat Pump and Heat

Recovery Unit

(VRV-W)

208/230V and 460V

96,000 to 144,000

BTU/hr (cooling

capacity);

Qualified design

categories: T

1Construction RX36NMVJUA is identical to RX30NMVJUA, units differ in software only.2Constructcion RK36NMVJUA is identical to RK30NMVJUA, units differ in software only.

Outdoor Heat Pump

24,000 to 36,000

BTU/hr: Qualified

design categories: N

RWEQ96_ATJ_ /ATJ_-HR

RWEQ120_AYD_ /AYD_-HR

RWEQ120_ATJ_ /ATJ_-HR

RWEQ96_AYD_ /AYD_-HR

34.1 28.9 131.5 57

RX30NMVJUA1 12.5 34.1

RK30NMVJUA2 12.5 34.1 28.9 131.5 Interp.

RK36NMVJUA2

RWEQ264_AYD_ /AYD_-HR RWEQ120 + RWEQ144

RWEQ240_AYD_ /AYD_-HR 2 x RWEQ120

RWEQ264_ATJ_ /ATJ_-HR RWEQ120 + RWEQ144

RWEQ216_AYD_ /AYD_-HR RWEQ96 + RWEQ120

RWEQ240_ATJ_ /ATJ_-HR 2 x RWEQ120

RWEQ216_ATJ_ /ATJ_-HR RWEQ96 + RWEQ120

12.5

28.9 Interp.

RX36NMVJUA1 12.5 34.1 28.9

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 12 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements and enhanced mounting as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

22.2 60.2 38.6 846 Interp.

22.2 60.2 38.6 901 Interp.

22.2 90.3 38.6 1269 Interp.

22.2 90.3 38.6 1282 Interp.

22.2 90.3 38.6 1269 Interp.

22.2 90.3 38.6 1286 Interp.

22.2 90.3 38.6 1269 Interp.

22.2 90.3 38.6 1290 Interp.

22.2 90.3 38.6 1269 Interp.

22.2 90.3 38.6 1310.5 Interp.

RWEQ360_AYD_ /AYD_-HR 3 x RWEQ120

RWEQ384_AYD_ /AYD_-HR 2 x RWEQ120 + RWEQ144

Outdoor Water Cooled

Heat Pump and Heat

Recovery Unit

(VRV-W)

208/230V and 460V

96,000 to 144,000

BTU/hr (cooling

capacity);

Qualified design

categories: T

3 x RWEQ144 Interp.

38.6 1269 RWEQ120 + 2 x RWEQ144

RWEQ336_AYD_ /AYD_-HR RWEQ96 + 2 x RWEQ120

RWEQ360_ATJ_ /ATJ_-HR 3 x RWEQ120

RWEQ312_AYD_ /AYD_-HR 2 x RWEQ96 + RWEQ120

RWEQ336_ATJ_ /ATJ_-HR RWEQ96 + 2 x RWEQ120

2 x RWEQ144

RWEQ288_ATJ_ /ATJ_-HR 2 x RWEQ144

Interp.

RWEQ288_AYD_ /AYD_-HR

Outdoor Water Cooled

Heat Pump and Heat

Recovery Unit

(VRV-W)

208/230V and 460V

96,000 to 144,000

BTU/hr (cooling

capacity);

Qualified design

categories: TRWEQ432_AYD_ /AYD_-HR 22.2 90.3 38.6 1351.5

RWEQ120 + 2 x RWEQ144 Interp.

RWEQ432_ATJ_ /ATJ_-HR 22.2 90.3 38.6 1269 3 x RWEQ144 Interp.

RWEQ408_AYD_ /AYD_-HR 22.2 90.3

RWEQ408_ATJ_ /ATJ_-HR 22.2 90.3

38.6 1331

RWEQ312_ATJ_ /ATJ_-HR 2 x RWEQ96 + RWEQ120

RWEQ384_ATJ_ /ATJ_-HR 2 x RWEQ120 + RWEQ144

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 13 of 99

OSP-0297

Mohammad Karim

05/17/2022

Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 14 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 15 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 16 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 17 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 18 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: Split System, Quaternity, SkyAir Outdoor Heat Pumps

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 19 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

9.3 31.3 11.4 26.0 Extrap.

14.4 34.3 10.8 20.0 Extrap.

8.2 35.0 12.0 31.0 11

9.3 31.3 11.4 26.0 12

14.4 34.3 10.8 22.0 Interp.

8.2 35.0 12.0 31.0 Interp.

9.3 31.3 11.4 26.0 Interp.

9.4 41.3 11.4 26.5 Interp.

16.9 45.7 13.0 31.0 Interp.

8.2 35.0 12.0 31.0 Interp.

9.0 41.4 11.4 31.0 14

9.4 41.3 11.4 26.5 Interp.

16.9 45.7 13.0 31.0 Interp.

9.3 41.4 11.4 31.0 Interp.

9.4 41.3 11.4 26.5 Interp.

16.9 45.7 13.0 31.0 13

9.0 41.4 11.4 31.0 Interp.

9.3 41.4 11.4 31.0 Interp.

10.3 47 13.4 37 Interp.

9.4 47.3 13.4 38.0 Interp.

10.3 47 13.4 37 56

9.4 47.3 13.4 38.0 15

2.5 g z/h=0.0

FTXS36_VJU

FTX36_VJU

FTXS30_VJU

FAQ24_VJU

FXAQ24_VJU

FTXN24_VJU

FTXS24_VJU

FTXS18_VJU

FXAQ18_VJU

FAQ18_VJU

FTXN18_VJU

FTXS15_VJU

FTXG15_VJU

FXAQ12_VJU

FTXN15_VJU

FTXS12_VJU

FTX30_VJU1

Indoor Fan Coil (Split

System, Quaternity,

SkyAir)

7,500 to 36,000

BTU/hr;

Qualified design

categories: H (FTXG), P

(FXAQ), L (FTXS), P

(FAQ), N (FTX)

1Construction of the FTX30_VJU is identical to FTX36_VJU (UUT 56), units differ in software only.

Certified Product Construction Summary:

Plastic enclosure

Certified Options Summary:

Mounting Configuration:

Rigid - wall mounted

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 2Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

FTXG12_VJU

FTXG09_VJU

FXAQ09_VJU

FXAQ07_VJU

FTXS09_VJU

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.5

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 20 of 99

OSP-0297

Mohammad Karim

05/17/2022

FOR REFERENCE ONLY

Nomenclature: Split System, Quaternity, SkyAir Indoor Units

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 2Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 21 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

26.8 37.8 7.7 55 16

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 Interp.

26.8 55.1 7.7 80 Interp.

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 Interp.

26.8 62.6 7.7 90 17

37.4 37.4 7.8 58 33

37.4 37.4 7.8 58 Interp.

37.4 37.4 7.8 60 Interp.

37.4 37.4 7.8 60 42

1Requires seismic enhancements: Heavy duty square washers (1.6" x 1.3 x 0.2”) were used at top and bottow of mounting

bracket. S-Shape hooks on four (4) internal wires, used to secure outer cover attachment to unit, were crimped closed to secure

cover to unit.

FXUQ30_VJU1

FXUQ36_VJU1

Indoor Fan Coil (VRV)

18,000 to 36,000 BTU/hr;

Qualified design

categories: P

FXUQ18_VJU1

FXUQ24_VJU1

FXHQ36_VJU

FHQ42_VJU

Indoor Fan Coil

(SkyAir, VRV-S, VRV)

12,000 to 40,500

BTU/hr;

Qualified design

categories: M

FHQ30_VJU

FHQ36_VJU

FHQ24_VJU

FXHQ24_VJU

FXHQ12_VJU

FHQ18_VJU

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 22 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

27.6 21.7 11.8 55 Extrap.

27.6 21.7 11.8 55 Extrap.

27.6 27.6 11.8 55 20

27.6 39.4 11.8 80 Interp.

27.6 39.4 11.8 80 Interp.

27.6 39.4 11.8 80 21

27.6 39.4 11.8 80 Interp.

27.6 39.4 11.8 80 Interp.

27.6 39.4 11.8 80 Interp.

27.6 55.1 11.8 80 Interp.

27.6 55.1 11.8 102 Interp.

27.6 55.1 11.8 101 Interp.

27.6 55.1 11.8 102 Interp.

27.6 55.1 11.8 101 22

27.6 55.1 11.8 101 Interp.

43.3 29.3 18.5 190 23

43.3 54.4 18.5 271 Interp.

43.3 54.4 18.1 302 Interp.

43.3 54.4 18.5 271 Interp.

43.3 54.4 18.1 302 24

2Requires seismic enhancements: One (1) #10 SMS at each mounting ear (4 total)3Construction of FXMQ54_VJU is identical to FMXQ48_VJU (UUT 22), units differ in software only.

1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch

FXMQ96MVJU2

Indoor Fan Coil (VRV-

S, VRV)

7,500 to 96,000

BTU/hr;

Qualified design

categories: P

FXMQ72MVJU2

FXMQ96MFVJU2

FXMQ48MFVJU2

FXMQ72MFVJU2

FXMQ48_VJU1

FXMQ54_VJU1,3

FXMQ36_VJU1

FBQ42_VJU1

FXMQ30_VJU1

FBQ36_VJU1

FXMQ24_VJU1

FBQ30_VJU1

FXMQ18_VJU1

FBQ24_VJU1

FXMQ12_VJU1

FBQ18_VJU1

FXMQ07_VJU1

FXMQ09_VJU1

FXMQ15_VJU1

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 23 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

33.1 33.1 9.7 43 35

33.1 33.1 9.7 43 18

33.1 33.1 9.7 43 Interp.

33.1 33.1 9.7 43 Interp.

33.1 33.1 9.7 43 Interp.

33.1 33.1 9.7 49 Interp.

33.1 33.1 9.7 49 Interp.

33.1 33.1 9.7 49 Interp.

33.1 33.1 9.7 58 Interp.

33.1 33.1 11.3 58 Interp.

33.1 33.1 11.3 55 Interp.

33.1 33.1 11.3 55 Interp.

33.1 33.1 11.3 58 19

2Requires seismic enhancements: Eight (8) #10 SMS in each mounting ear. Four (4) cable tie (shipped with unit) chains, each with

two links, between decoration panel cover latches and through mounting ear. Two (2) strips of heavy duty Velcro® tape 1” x 2” at

each corner cover (eight total).

1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch

FXFQ48_VJU2

Indoor Fan Coil

(SkyAir, VRV III-S, VRV)

9,500 to 48,000

BTU/hr;

Qualified design

categories: P, T

FCQ36_VJU1

FCQ42_VJU1

FXFQ30_VJU2

FXFQ36_VJU2

FXFQ24_VJU2

FCQ30_VJU2

FXFQ18_VJU2

FCQ24_VJU1

FXFQ12_VJU2

FCQ18_VJU1

FXFQ07_VJU2

FXFQ09_VJU2

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 24 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Plastic cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

22.6 22.6 10.3 41.5 Extrap.

22.6 22.6 10.3 41.5 Extrap.

22.6 22.6 10.3 41.5 48

22.6 22.6 10.3 46 Interp.

22.6 22.6 10.3 46 Interp.

22.6 22.6 10.3 46 49

31.5 21.7 9.7 51 Extrap.

31.5 21.7 9.7 51 46

31.5 21.7 9.7 55 Interp.

31.5 21.7 9.7 55 Interp.

31.5 21.7 9.7 60 Interp.

31.5 27.6 9.7 77 Interp.

31.5 39.4 9.7 82 Interp.

31.5 39.4 9.7 82 Interp.

31.5 55.1 9.7 101 Interp.

31.5 55.1 9.7 104 Interp.

31.5 61 9.7 110.5 47

Indoor Fan Coil (VRV

Vista) 5,800 to 18,000

BTU/hr (kW); Qualified

design categories: T

Indoor Fan Coil (VRV)

5,800 to 54,000 BTU/hr

(kW); Qualified design

categories: T

FXSQ54TAVJU1

FXSQ36TAVJU1

FXSQ48TAVJU1

FXSQ24TAVJU1

FXSQ30TAVJU1

FXSQ15TAVJU1

FXSQ18TAVJU1

FXSQ09TAVJU1

FXSQ12TAVJU1

FXSQ05TAVJU1

FXSQ07TAVJU1

FXZQ15TAVJU1,2

FXZQ18TAVJU1,2

FXZQ09TAVJU1,2

FXZQ12TAVJU1,2

FXZQ05TAVJU1,2

FXZQ07TAVJU1,2

1Requires seismic enhancements: Six (6) #10 SMS at each mounting ear (24 total) & #10 SMS in grille latch2 Requires seismic enchancements: Filter secured with two (2) stripes of 3M velcor. Panel cover hinges secured with 50 lb wire

and metal ferrule. See UUT summary for more details.

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 25 of 99

OSP-0297

Mohammad Karim

05/17/2022

Nomenclature: VRV Indoor Units

FOR REFERENCE ONLY

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 26 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: VRV Indoor Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 27 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

FOR REFERENCE ONLY

Nomenclature: VRV Indoor Units

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 28 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

12.2 15.3 8.1 26 25

12.2 15.3 8.1 26 Interp.

12.2 15.3 8.1 33 Interp.

25.0 41.5 8.3 132 Interp.

25.0 62.1 8.3 196 26

18.9 14.6 11.8 49 31

18.9 22.8 11.8 68 Interp.

18.9 22.8 11.8 73 Interp.

18.9 32.3 11.8 101 Interp.

18.9 32.3 11.8 106 32

9.5 83.5

23.4 9.5 50

1Seismic enhancements: 1/8" steel backer plate behind each mouting ear with (2) machine screws through each mounting ear.

54

Indoor Multi Port Branch

Selector (VRV IV)

144 to 290 total capacity

index;

Qualified design

categories: T

BS6Q54_VJ1

BS8Q54_VJ1

BSV6Q36_VJU

BS4Q54_VJ1

Indoor Single Port

Branch Selector (VRV III)

36 to 96 capacity index;

Qualified design

categories: P, T

BSVQ96_VJU

BSV4Q36_VJU

BSVQ36_VJU

BSVQ60_VJU

Indoor Multi Branch

Selectors (VRV)

Flex Series

Qualified design

categories: T

BSF4Q54TVJ

BSF6Q54TVJ

BSF8Q54TVJ

13.8

23.8 23.4 9.5 73

23.8 23.4

Interp.

55

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 4Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Ceiling suspended

BS10Q54_VJ1

BS12Q54_VJ1

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 29 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 4Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: VRV III Indoor Branch Selector Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 30 of 99

OSP-0297

Mohammad Karim

05/17/2022

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 4Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Nomenclature: VRV III Indoor Branch Selector UnitsNomenclature: VRV III Indoor Branch Selector Units

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 31 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS=

S DS=

Depth Width Height

21 17.5 45 115 40

21 17.5 45 115 Interp.

21 17.5 45 115 Interp.

21 17.5 45 115 Interp.

21 17.5 45 115 Interp.

21 17.5 45 140 Interp.

21 21 54.43 150 Interp.

21 21 54.43 150 Interp.

22 24.5 58 167 Interp.

21 24.5 58 167 41

FXTQ54_VJU

FXTQ60_VJU

Air Handling Unit

9,500-60,000 BTU/hr

(cooling capacity)FXTQ42_VJU

FXTQ48_VJU

FXTQ30_VJU

FXTQ36_VJU

FXTQ18_VJU

FXTQ24_VJU

FXTQ09_VJU

FXTQ12_VJU

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 5Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Line ModelDimensions (in) Weight

(lb)Notes UUT

Note: Installed mounting configuration must be of similar configuration and equivalent strength and stiffness to those tested.

Building Code: CBC 2019 Seismic Certification Limits:2.0 g z/h=1.0

I P= 1.52.5 g z/h=0.0

Certified Product Construction Summary:

Carbon steel cabinet. Seismic enhancements as indicated.

Certified Options Summary:

Mounting Configuration:

Rigid - base mounted

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 32 of 99

OSP-0297

Mohammad Karim

05/17/2022

Nomenclature: VRV III Indoor Branch Selector Units

SPECIAL SEISMIC CERTIFICATIONCERTIFIED COMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLCTABLE 5Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

FOR REFERENCE ONLY

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 33 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

2

3

1

27

28

29

30

37

Interp.

38

39,45

57,58

53Fins coated w/ anti-corrosion

hydrophilic blue coating

65-3/8" x 36-5/8" x 30-1/8"

Al fin, Cu tube2P626353-1

Interp. Fins coated w/ anti-corrosion

hydrophilic blue coating

65-3/8" x 48-13/16" x 30-1/8"

Al fin, Cu tube2P631073-1

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

3P138067-2 7mm x 0.27 mm coil, Al fin, Cu tube

2P170976-3 8mm x 0.3 mm coil, Al fin, Cu tube

3P287611-2

Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code:

Heat Exchanger Daikin

3P379239-1 7mm x 0.24mm, 2 row, 32 stage, Cu tube Aluminum parts

7500099 7mm x 0.3mm coil, Al fin, Cu tube

6019568

7mm x 0.3mm coil, Al fin, Cu tube

7mm x 0.3mm coil, Al fin, Cu tube

6019584

CBC 2019 Seismic Certification Limits: I P = 1.5

7009510 7mm x 0.3mm coil, Al fin, Cu tube

5018937 18-3/4" x 4-1/2" Stainless Steel Braze Plate

7mm x 0.3mm coil, Al fin, Cu tube

7009559 7mm x 0.3mm coil, Al fin, Cu tube

7500019 7mm x 0.3mm coil, Al fin, Cu tube

51

UUTComponent Type Manufacturer Model Description Notes

8mm x 0.3 mm coil, Al fin, Cu tube

3P341763-2 7mm x 0.3mm coil, Al fin, Cu tubeused for all REYQ_XATJU and

REYQ_XAYDU models

3P412977-1 Plate HX for vapor injectionREYQ72/96/120XATJU,

REYQ72/96/120XAYDU

39412975-1 Plate HX for vapor injectionREYQ151/168XATJU,

REYQ151/168XAYDU

50,51

50

6021509

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 34 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description: Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

UUTComponent Type Manufacturer Model Description Notes

1

2

3

37

38

57, 58

39

45

27

28,30

29

30

Extrap.

53

Interp.

Interp.

50

Interp.

Interp.

Vapor Injection

Scroll Compressor

Daikin

Heat Exchanger

7009548 96,000 BTU/hr, 460V, Carbon Steel

JT250KADWTJ@S 230 V, 3-phase, 50.6 lbs.

JP057AEAXMV#T 230 V, 3-phase, 72.8 lbs.

52Fins coated w/ anti-corrosion

hydrophilic blue coating

65-3/8" x 68-7/8" x 30-1/8"

Al fin, Cu tube2P623585-1

Interp.Fins coated w/ anti-corrosion

hydrophilic blue coating

65-3/8" x 48-13/16" x 30-1/8"

Al fin, Cu tube2P627736-1

230 V, 3-phase, 63.9 lbs.

JT16KADWYDN@S 144,000 BTU/hr, 460V, Carbon Steel

151,000 BTU/hr, 208-230V Carbon Steel5018933

2YC63FXD#D 36,000 BTU/hr, 208-230V

1873054 72,000 BTU/hr, 208-230V, Carbon Steel

7009494 72,000 BTU/hr, 208-230V, Carbon Steel

7009487 96,000 BTU/hr, 460V, Carbon Steel

JP035AEAXSV#T

1YC23AEXD 12,000 BTU/hr, 208-230V

2YC63BXD#A 21,500 BTU/hr, 208-230V

JP057AEAYSV#T 460 V, 3-phase, 71.4 lbs.

JT160KADWTJ@T 230 V, 3-phase, 39 lbs.

6025911

6025930 57, 000 BTU/hr, 208-230V

2YC63AAXD 220VDC, 18A, Insulation Class E

JP057AEAXSV#T 230 V, 3-phase, 71.9 lbs.

JP035AEAYSV#T 460 V, 3-phase, 63.7 lbs.

Scroll Compressor in UUT 53 is a

depopulated version of Vapor Injection

Scroll Compressor in UUT 52.

Scroll Compressor

Scroll Compressor

36,000 BTU/hr, 208-230V

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 35 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description: Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

UUTComponent Type Manufacturer Model Description Notes

Interp.

51

52

3

27

28,30

29

28,30

29

57,58

1

2

37

38

39

50

51

Interp.

53

Interp.

52

Vapor Injection

Scroll CompressorDaikin

Fan Motor

Fan Motor Panasonic

Panasonic2219507 Propellor Fan 400 Watts UUT: Polyester resin tested

4012512 Propellor Fan 650 Watts UUT: Polyester resin tested

D90B-37 DC375V, 128 Watts, Class E UUT: Polyester resin tested

NIDEC

Propellor Fan 500 Watts

Propellor Fan 650 Watts

1713309 UUT: Polyester resin tested

4012512 UUT: Polyester resin tested

2P557547-1

3SB40622-3 60W, 208-230V UUT: Polyester resin tested

2219507 Propellor Fan 400 Watts UUT: Polyester resin tested

UUT: Polyester resin tested23W, 208-230V3SB40632-6

460 V, 3-phase, 50.6 lbs.

JP057AEAYMV#T 460 V, 3-phase, 72.3 lbs.

3SB40675-1 200W, 208-230V UUT: Polyester resin tested

650W, 460V UUT: Acrylonitrile Resin Plastic

2P618618-2 950W, 460V UUT: Acrylonitrile Resin Plastic

2P618618-1 950W, 208/230V UUT: Acrylonitrile Resin Plastic

2P519551-2 650W, 208/230V UUT: Acrylonitrile Resin Plastic

2P360713-3 800W, 208/230V

2P343735-1 800W, 460V

JT15JBVDWYR@S 460 V, 3-phase, 34.2 lbs.

JT25KADWYDN@S

1,2Low Ambient Wind

BaffleKPW937A4

Daikin

Plastic

6016145 Propeller Fan, 200 Watts, 208-230 V UUT: Polyester resin tested

2025036 Propeller Fan, 70 Watts, 208-230 V UUT: Polyester resin tested

5019722 23 Watts, 208-230 V UTT: Polyester resin tested

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 36 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description: Heat Pump Subcomponents TABLE 6Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

UUTComponent Type Manufacturer Model Description Notes

1,2

3

Daikin BRP2A81Plastic, Requires BRP2A81 ABC Terminal

KitCool/Heat Selector

27,28,29,

30

Saginomiya

FujikokiExpansion Valve

CAM-B30YGDM Copper, SS, Resin

UKV-25D Copper, SS, Resin

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 37 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

11

13

12

14

15

56

11

12

15

14

13

56

12

14

11

11

12

13

14

15

11

11

13,15

Deodorizing Filter Daikin

Photocatalytic Filter Daikin

1288416 Plastic Mesh

4009476 Plastic Mesh

1700125 Plastic Mesh

1685846 Plastic Mesh

2SA50075-1-KU Copper, SS, Resin

Cross Flow Fan 48W, 208-230V UUT: Polyester resin tested

KFD-325-64-8A 64W, DC325V UUT: Unsaturated Polyester Resin

3SB40672-1 Cross Flow Fan 64W, 208-230V UUT: Polyester resin tested

1380242 Plastic Mesh

4000835 Plastic Mesh

NIDEC

Fan Motor

Photocatalytic1840489

1843039

Filter Daikin

Expansion Valve Fujikoki

Daikin

Panasonic

2SA50075-1-SI Copper, SS, Resin

3SB40720-1

1843053 Plastic Mesh

Photocatalytic

3SB40591-1 Cross Flow Fan 43W, 208-230V UUT: Polyester resin tested

3SB40647-3 Cross Flow Fan 23W, 208-230V UUT: Polyester resin tested

3SB40565-1 Cross Flow Fan 40W, 208-230V UUT: Polyester resin tested

UUT

Fan Coil -Wall SubcomponentsTABLE 7

2P222543-1 7mm x 0.3 mm coil, Al fin, Cu tube

1P222779-1 7mm, 2 row, 18 stage, Al fin, Cu tube

2P168924-4 7mm x 0.3 mm coil, Al fin, Cu tube

2P171400-2 7mm x 0.3 mm coil, Al fin, Cu tube

1P287200-1 6.35mm x 0.3 mm coil, Al fin, Cu tube

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

3P204553-2 6.35mm x 0.3 mm coil, Al fin, Cu tube

Component Type Manufacturer Model Description

Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

Heat Exchanger Daikin

Notes

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 38 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

UUT

Fan Coil -Wall SubcomponentsTABLE 7

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

Component Type Manufacturer Model Description

Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

Notes

12, 14Individual Zone

ControllerDaikin BRC7E818 Plastic

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 39 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

16

17

18

19

20

21

22

23

24

33

Interp.

Interp.

Interp.

Interp.

Interp.

Interp.

35

42

48

Interp.

49

46

Interp.2397801 3/8" x 1/8", Cu Tube, Al fin FXSQ12TAVJU

5011003 3/8" x 1/8", Cu Tube, Al fin FXZQ18TAVJU

2397793 3/8" x 1/8", Cu Tube, Al fin FXSQ05/07/09TAVJU

5011000 3/8" x 1/8", Cu Tube, Al fin FXZQ05/07/09TAVJU

5011004 3/8" x 1/8", Cu Tube, Al fin FXZQ12/15TAVJU

1993028 7mm x 0.3 mm coil, Al fin, Cu tube

2110756 7mm x 0.3 mm coil, Al fin, Cu tube

1993059 7mm x 0.3 mm coil, Al fin, Cu tube

2110763 7mm x 0.3 mm coil, Al fin, Cu tube

1993042 7mm x 0.3 mm coil, Al fin, Cu tube

2110770 7mm x 0.3 mm coil, Al fin, Cu tube

1993035 7mm x 0.3 mm coil, Al fin, Cu tube

3P290389-1 7mm x 0.3 mm coil, Al fin, Cu tube

3P288941-1 7mm x 0.3 mm coil, Al fin, Cu tube

2218100 7mm x 0.3 mm coil, Al fin, Cu tube

CRB-FXYMP280M 8mm x 0.3 mm coil, Al fin, Cu tube

2273936 7mm x 0.3 mm coil, Al fin, Cu tube

3P288942-1 7mm x 0.3 mm coil, Al fin, Cu tube

CRB-FXYMP224M 8mm x 0.3 mm coil, Al fin, Cu tube

2P231854-1 7mm x 0.3 mm coil, Al fin, Cu tube

2P231856-1

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

AFREX 2PN05185-3 7mm x 0.3 mm coil, Al fin, Cu tube

2PN05189-3 7mm x 0.3 mm coil, Al fin, Cu tube

Component Type Manufacturer Model Description Notes

7mm x 0.3 mm coil, Al fin, Cu tube

UUT

Fan Coil -Ceiling SubcomponentsTABLE 8Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

DaikinHeat Exchanger

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 40 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

Component Type Manufacturer Model Description Notes UUT

Fan Coil -Ceiling SubcomponentsTABLE 8Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

Interp.

Interp.

Interp.

Interp.

Interp.

Interp.

47

48

Interp.

49

46

Interp.

Interp.

Interp.

Interp.

47

46

Interp.

Interp.

Interp.

47

48,49

48,49

Expansion Valve Daikin Pulse motor electronic expansion valve FXSQ12/15TAVJU

2214021 Pulse motor electronic expansion valve FXSQ18/24TAVJU

2110073

2371955 Pulse motor electronic expansion valve FXSQ54TAVJU

4018537 Pulse motor electronic expansion valve FXSQ30TAVJU

4018534 Pulse motor electronic expansion valve FXSQ36/48TAVJU

4015739

5011010 Molded polymer, 12" Ø

5011038 50W

2P383154-2 Galvanized Steel FXSQ36/48TAVJU

2P394978-1 Galvanized Steel FXSQ54TAVJU

2P383156-2 Galvanized Steel FXSQ15TAVJU

2P383155-2 Galvanized Steel FXSQ18/24/30TAVJU

2397818 Galvanized Steel FXSQ05/07/09/12TAVJU

Pulse motor electronic expansion valve FXZQ18TAVJU

4015738 Pulse motor electronic expansion valve FXSQ05/07/09TAVJU

2108342 Pulse motor electronic expansion valve FXZQ05/07/09TAVJU

2108359 Pulse motor electronic expansion valve FXZQ12/15TAVJU

2397902 3/8" x 1/8", Cu Tube, Al fin FXSQ48TAVJU

2397933 3/8" x 1/8", Cu Tube, Al fin FXSQ54TAVJU

2397863 3/8" x 1/8", Cu Tube, Al fin FXSQ30TAVJU

2397919 3/8" x 1/8", Cu Tube, Al fin FXSQ36TAVJU

2397870 3/8" x 1/8", Cu Tube, Al fin FXSQ18TAVJU

2397887 3/8" x 1/8", Cu Tube, Al fin FXSQ24TAVJU

2397856 3/8" x 1/8", Cu Tube, Al fin FXSQ15TAVJU

DaikinHeat Exchanger

Fan Assembly Sirocco

Turbo Fan Rotor Sirocco

Fan Motor Panasonic

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 41 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

Component Type Manufacturer Model Description Notes UUT

Fan Coil -Ceiling SubcomponentsTABLE 8Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

46

Interp.

Interp.

Interp.

474016361 350W FXSQ54TAVJU

2258153 230W FXSQ18/24/30TAVJU

2258160 300W FXSQ36/48TAVJU

4015745 78W FXSQ05/07/09/12TAVJU

2258146 130W FXSQ15TAVJU

Fan Motor Panasonic

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 42 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

25

25

25

25

25

25

25

25

31,32

31,32

31,32

31,32

31,32

Body/Motor Operated Valve, Copper

Coil/Motor Operated Valve, Copper

Coil/Motor Operated Valve, Copper

Coil/Motor Operated Valve, Copper

Coil/Motor Operated Valve, Copper

Coil/Motor Operated Valve, Copper

Body/Motor Operated Valve, Copper

Body/Motor Operated Valve, Copper

Coil/Motor Operated Valve (Sub Suction), Copper

Coil/Motor Operated Valve (Sub Discharge), Copper

Coil/Motor Operated Valve (Sub Cool), Copper

Coil/Motor Operated Valve (Main Suction), Copper

Coil/Motor Operated Valve (Main Discharge), Copper 26

1939745 26

2227469

2271202

2271194

2227476

Coil/Electronic Exp. Valve, Copper

Coil/Electronic Exp. Valve Assy., Copper

Coil/Electronic Exp. Valve Assy., Copper

Coil/Electronic Exp. Valve, Copper

Coil/Electronic Exp. Valve Assy., Copper

DaikinValve

1801299

1801408

1801390

UUTNotesDescription

2227515

1801268

1801251

1801282

1801275

1801415

1939776 26

1939752 26

1939769 26

1939738

Branch SubcomponentsTABLE 9Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

Component Type Manufacturer Model

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 43 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

UUTNotesDescription

Branch SubcomponentsTABLE 9Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

Component Type Manufacturer Model

31,32

31,32

31,32

31,32

31,32

31,32

31,32

54

Interp.

55

54

Interp.

Interp.

Interp.

Interp.

55

Daikin

Fujikoki

Valve

EEV Coil

EEV Coil

EEV Coil

EEV Body

EEV Body

EEV Body

Coil/Electronic Exp. Valve Assy., Copper

Coil/Electronic Exp. Valve Assy., Copper

Coil/Electronic Exp. Valve, Copper

Coil/Electronic Exp. Valve Assy., Copper

Coil/Electronic Exp. Valve Assy., Copper

Coil/Electronic Exp. Valve, Copper

Coil/Electronic Exp. Valve Assy., Copper

3P389855-4 EEV Coil

3P389855-2

3P389855-3

3P389855-1

3S500040-1

3P363865-1

3S500039-1

2227445

2227483

3S500038-1

3P363865-2

EEV Coil

EEV Coil

2271226

2271219

2227452

2227490

2227508

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 44 of 99

OSP-0297

Mohammad Karim

05/17/2022

S DS = 2.0 g z/h = 1.0

S DS = 2.5 g z/h = 0.0

40

Interp.

Interp.

Interp.

Interp.

Interp.

Interp.

Interp.

41

40

Interp.

Interp.

41

40

Interp.

41

40

Interp.

Interp.

Interp.

Interp.

Interp.

41

Blower Assembly Daikin

Heat Exchanger Daikin

Fan Motor Daikin

0131M00272 1 Hp, Serial ECM

3S500052-1

0271A00029 10 x 8" , Galvanized Steel

0270A01206 3/8" x 1/8", Al Tube, Al fin

0270A01161 3/8" x 1/8", Al Tube, Al fin

0270A01156 3/8" x 1/8", Al Tube, Al fin

3S500054-1 FXTQ54, 60 - tested in FXTQ60

Expansion Valve Daikin

FXTQ42,48

0271A00206 10 x 8" , Galvanized Steel FXTQ54,60 - tested in FXTQ60

FXTQ60

0271A00299 9 x 6", Galvanized Steel FXTQ09-36, tested in FXTQ09

Pulse motor electronic expansion valve

FXTQ30

3S500053-1 FXTQ36, 42

3S500050-1 FXTQ18

3S500051-1 FXTQ24

3S500048-1 FXTQ09

3S500049-1 FXTQ12

0131M00271 3/4 Hp, Serial ECM FXTQ42-48

FXTQ54

FXTQ54, 60 - tested in FXTQ60

0131M00270 1/2 Hp, Serial ECM FXTQ09-36

0270A01196 3/8" x 1/8", Al Tube, Al fin FXTQ42

0270A01197 3/8" x 1/8", Al Tube, Al fin FXTQ48

FXTQ30

0270A01162 3/8" x 1/8", Al Tube, Al fin FXTQ36

0270A01159 3/8" x 1/8", Al Tube, Al fin FXTQ18

0270A01160 3/8" x 1/8", Al Tube, Al fin FXTQ24

FXTQ09

0270A01157 3/8" x 1/8", Al Tube, Al fin FXTQ12

Component Type Manufacturer Model Description Notes

SPECIAL SEISMIC CERTIFICATIONCERTIFIED SUBCOMPONENT MATRIX

2100103-CR-001-R1

Manufacturer: Daikin North America, LLC Table Description:

UUT

Multi Position AHU SubcomponentsTABLE 10Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Building Code: CBC 2019 Seismic Certification Limits: I P = 1.5

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 45 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

2.98 1.0 1.5

Notes:

22FXMQ48PVJU

Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No

21FXMQ18PVJU

Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.90 1.0 1.5

20FXMQ12PVJU

Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.92 1.0 1.5

2.92 1.0 1.5

19FXFQ48PVJU

Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.95

18FXFQ09PVJU

Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No

1.0 1.5

1.5

NOT USED

12

13

15

14

16

17FHQ42MVJU

Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 3.05 1.0 1.5

FXAQ09PVJU

Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.92 1.0 1.5

11FTXG09HVJU

Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.95

4-10

1.0

3RXS36LVJU

Base Mounted - RigidQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5

1.0 1.5

2RXS24LVJU

Base Mounted - RigidQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5

1RXS09LVJU

Base Mounted - RigidQ1222.0, Rev 0 QualTech NP 2012 No 2.87

UUT Unit Description Report Number Testing LabYear

Tested

ISO 17025

Accredited?

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

SDS z/h IP

FTXS24LVJU

Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.90 1.0 1.5

FAQ18PVJU

Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5

FTXS36LVJU

Wall - Rigid MountQ1222.0, Rev 0 QualTech NP 2012 No 2.92 1.0 1.5

FXHQ12MVJU

Ceiling - SuspendedQ1222.0, Rev 0 QualTech NP 2012 No 2.98 1.0 1.5

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 46 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

UUT Unit Description Report Number Testing LabYear

Tested

ISO 17025

Accredited?

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

SDS z/h IP

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

Clark Testing

Environment Testing

Laboratory, Inc.

NOT USED

2017 Yes

2017 Yes

2016 Yes

2016 Yes

1.5

1.5

1.5

36

FXFQ07TVJU

Ceiling - Suspended35 2016 Yes

1.5

14662, Rev. 3

QualTech NP

QualTech NP

QualTech NP

QualTech NP

Clark Testing

Clark Testing

Clark Testing

Clark Testing

Clark Testing

JID 15-1054

Rev 0

JID 15-1054

Rev 0

JID 15-1054

Rev 0

14662, Rev. 3

Environment Testing

Laboratory, Inc.

Clark Testing

Clark Testing

FXMQ48MFVJU Ceiling -

Suspended

FXMQ96MVJU

Ceiling - Suspended

BSVQ36PVJU

Ceiling - Suspended

BSV6Q36PVJU

Ceiling - Suspended

RXYQ72TTJU

Base Mounted - Rigid

RXYQ168TYDN

Base Mounted - Rigid

REYQ72TTJU

Base Mounted - Rigid

REYQ168TYDN

Base Mounted - Rigid

BS4Q54TVJ

Ceiling - Suspended

34

FXUQ18PVJU

Ceiling - Suspended33

1.5

32 1.5BS12Q54TVJ

Ceiling - Suspended

JID 15-1054

Rev 031 2016 Yes

NOT USED

1.5

30 1.5

JID 15-1054

Rev 0

JID 15-1054

Rev 0

29 2.50 1.02016 Yes

2016 Yes

1.5

28 1.5

JID 15-1054

Rev 0

JID 15-1054

Rev 0

27 2.50 1.0Yes

2016 Yes

2016

1.5

26 2.95 1.0 1.5

Q1222.0, Rev 0

Q1222.0, Rev 0

25 2.98 1.02012 No

2012 No

1.5

24 2.92 1.0 1.5

Q1222.0, Rev 0

Q1222.0, Rev 0

23 2.98 1.02012 No

2012 No

Notes:

38

RXTQ36TAVJU,

Base Mounted - Rigid

RXTQ60TAVJU,

Base Mounted - Rigid

37

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 47 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

UUT Unit Description Report Number Testing LabYear

Tested

ISO 17025

Accredited?

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

SDS z/h IP

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

2.00 1.0

2.50 0.0

56FTX36NVJU

Wall - Rigid Mount2100103-TR-001-R1

Environment Testing

Laboratory, Inc. 2022 Yes

55BSF8Q54TVJ

Ceiling-Suspended2100103-TR-001-R1

Environment Testing

Laboratory, Inc. 2022 Yes

57RK36NMVJUA

Base Mounted - Rigid2100103-TR-001-R1

Environment Testing

Laboratory, Inc. 2022 Yes

58RX36NMVJUA

Base Mounted - Rigid2100103-TR-001-R1

Environment Testing

Laboratory, Inc. 2022

BSF4Q54TVJ

Ceiling-Suspended2100103-TR-001-R1

Environment Testing

Laboratory, Inc. 2022 Yes

53REYQ72AATJA

Base Mounted - Rigid2100103-TR-001-R1

Environment Testing

Laboratory, Inc. 2022 Yes

54

52REQ240AAYDA

Base Mounted - Rigid2100103-TR-001-R1

Environment Testing

Laboratory, Inc. 2022 Yes

51 REYQ144XATJU

Base Mounted - Rigid15215, Rev.1

Environment Testing

Laboratory, Inc. 2019 Yes

50

49FXZQ18TAVJU

Ceiling-Suspended15215, Rev.1

Environment Testing

Laboratory, Inc. 2019 Yes

48FXZQ09TAVJU

Ceiling-Suspended15215, Rev.1

Environment Testing

Laboratory, Inc. 2019 Yes

REYQ72XATJU

Base Mounted - Rigid15215, Rev.1

Environment Testing

Laboratory, Inc. 2019 Yes

47FXSQ54TAVJU

Ceiling-Suspended15215, Rev.1

Environment Testing

Laboratory, Inc. 2019 Yes

46FXSQ07TAVJU

Ceiling-Suspended15215, Rev.1

Environment Testing

Laboratory, Inc. 2019 Yes

Yes

45RWQE144TAYDU

Base Rigid Mount15215, Rev.1

Environment Testing

Laboratory, Inc. 2019 Yes

43, 44 NOT USED

Yes

42

41FXTQ60TAVJU,

Base Mounted - Rigid14662, Rev. 3

Environment Testing

Laboratory, Inc. 2017

Environment Testing

Laboratory, Inc. 2017 Yes

FXTQ09TAVJU,

Base Mounted - Rigid14662, Rev. 3

Environment Testing

Laboratory, Inc. 2017 Yes

FXUQ36PVJU

Ceiling - Suspended14662, Rev. 3

Environment Testing

Laboratory, Inc. 2017

Notes:

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

Yes

40

39RWEQ96TATJU,

Base Mounted - Rigid14662, Rev. 3

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 48 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

75

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.87 1.0 1.5 4.59 3.44 1.91 0.77

Test Mounting Details:

14.6

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

11.8 33.5 21.5 29.5 >33.3

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.27 mm coil DAIKIN 3P138067-2

Compressor: 12,000 Btu/h DAIKIN 1YC23AEXD

Fan: Propeller 23W NIDEC 3SB40632-6

Printed Circuit Boards: Main DAIKIN 4009626, Filter DAIKIN 4009359

Expansion Valve: FUJIKOKI CAM-B30YGDM

Other: DAIKIN Carbon Steel cabinet, DAIKIN KPW937A4 Low ambient wind baffle

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 1Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RXS09LVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 49 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

158

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Rigid base mounted with (4) 1/2ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.98 1.0 1.5 4.77 3.58 1.99 0.79

Test Mounting Details:

14.6

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

11.5 29.5 14.3 12.2 6.6

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN 2P170976-3

Compressor: 21,500 Btu/h DAIKIN 2YC63BXD#A

Fan: Propeller 60W NIDEC 3SB40622-3

Printed Circuit Boards: Main DAIKIN 4009630, Filter DAIKIN 1688256

Expansion Valve: FUJIKOKI CAM-B30YGDM, Other: DAIKIN Carbon steel cabinet, DAIKIN KPW945A4 Low ambient wind baffle

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Heat Pump: carbon steel enclousre with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 2Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RXS24LVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 50 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

181

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Rigid base mounted with (4) 1/2”Ø A307 bolts & (4) 1/16”x1-1/2” aluminum straps were secured approximately 30˚relative to

vertical surface of the unit with (2) #10 SMS to unit & 1/4ӯ bolt to table

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.98 1.0 1.5 4.77 3.58 1.99 0.79

Test Mounting Details:

14.6

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

14.0 37.0 39.3 11.5 6.6

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN 3P287611-2

Compressor: 36,000 Btu/h DAIKIN 2YC63FXD#D

Fan: Propeller 200W Panasonic 3SB40675-1

Printed Circuit Board: Main DAIKIN 4009635

Expansion Valve : Saginomiya UKV-25D, Other: DAIKIN Carbon steel cabinet

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 3Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RXS36LVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 51 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

29

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Wall mounted with (4) 3/8ӯ A307 bolts & (1) #6-32 screw & (1) #10-32 screw

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.95 1.0 1.5 4.72 3.54 1.97 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

8.5 35.0 12.0 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 6.35 mm x 0.3 mm coil DAIKIN 3P204553-2

Fan: Cross Flow Fan 23W NIDEC 3SB40647-3

Printed Circuit Boards: Printed Circuit Assy(Photo/Display) DAIKIN 1840054; Pyroelectric Passive Infrared Sensor DAIKIN 1840061;

Main DAIKIN 4009433

Other: DAIKIN 1843053 Deodorizing filters; DAIKIN 1700125 Filter; DAIKIN 1685846 Filter; DAIKIN 1843039 Photocatalytic filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (wall mounted) enclosure constructed of plastic

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 11Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FTXG09HVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 52 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

25

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Wall mounted with (4) 3/8ӯ A307 bolts & (5) #10 self-tapping screws

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.92 1.0 1.5 4.67 3.50 1.95 0.78

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

9.3 31.0 11.5 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P168924-4

Fan: Cross Flow Fan 40W NIDEC 3SB40565-1

Printed Circuit Boards: Main DAIKIN 4008765; Main DAIKIN 4005831

Expansion Valve: Fujikoki 2SA50075-1-KU

Other: DAIKIN BRC7E818 Individual Zone Controller; DAIKIN 1288416 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (wall mounted) enclosure constructed of plastic

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 12Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXAQ09PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 53 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

32

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Wall mounted with (4) 3/8ӯ A307 bolts & (1) #10-32 screw

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.90 1.0 1.5 4.64 3.48 1.93 0.77

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

9.8 40.8 13.4 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 6.35 mm x 0.3 mm coil DAIKIN 1P287200-1

Fan: Cross Flow Fan 48W Panasonic 3SB40720-1

Printed Circuit Boards: Printed Circuit Assy(Photo/Display) DAIKIN 4000843; Printed Circuit Assy(Infrared Sensor) DAIKIN

4000844; Main DAIKIN 4009491

Other: DAIKIN 4009476 Filter; DAIKIN 1840489 Photocatalytic filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (wall mounted) enclosure constructed of plastic

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 13Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FTXS24LVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 54 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

31

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Wall mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.98 1.0 1.5 4.77 3.58 1.99 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

8.5 41.1 11.5 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P171400-2

Fan: Cross Flow Fan 43W Panasonic 3SB40591-1

Printed Circuit Board: Main DAIKIN 1884472

Expansion Valve: Valve Fujikoki 2SA50075-1-SI

Other: DAIKIN BRC7E818 Individual Zone Controller; DAIKIN Plastic Mesh 1380242 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (wall mounted) enclosure constructed of plastic

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 14Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FAQ18PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 55 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

36

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

Wall mounted with (4) 3/8ӯ A307 bolts & (1) #6-32 screw

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.92 1.0 1.5 4.67 3.50 1.95 0.78

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

9.5 46.9 13.4 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P222543-1

Fan: Cross Flow Fan 64W NIDEC 3SB40672-1

Printed Circuit Boards: Printed Circuit Assy.(Photo/Display) DAIKIN 4000843; Printed Circuit Assy. (Infrared Sensor) DAIKIN

4000844; Main DAIKIN 4009500

Other: DAIKIN 4000835 Plastic Mesh Filter; DAIKIN 1840489 Photocatalytic filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (wall mounted) enclosure constructed of plastic

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 15Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FTXS36LVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 56 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

59

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.98 1.0 1.5 4.77 3.58 1.99 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

8.0 37.5 27.0 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil AFREX 2PN05185-3

Fan: Sirocco Fan 60W Panasonic 3PN04213-1

Printed Circuit Boards: Main DAIKIN 1621626; Main DAIKIN 1621633; Main DAIKIN 162163J

Expansion Valve: Valve Fujikoki 2SA50046-2-KE

Other: DAIKIN 1245349 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 16Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXHQ12MVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 57 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

93

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

3.05 1.0 1.5 4.88 3.66 2.03 0.81

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

8.0 62.0 27.0 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil AFREX 2PN05189-3

Fan: Sirocco Fan 130W Panasonic 3PN04404-1

Printed Circuit Board: Main DAIKIN 1621626; Main DAIKIN 1621633; Main DAIKIN 162163J

Expansion Valve: Valve Fujikoki 2SA50046-2-KA

Other: DAIKIN BRC7E83 Individual Zone Controller; DAIKIN 1245363 Filter

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 17Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FHQ24MVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 58 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

70

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with ½” washers & nuts above and below mounting ears & (8)

1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.92 1.0 1.5 4.67 3.50 1.95 0.78

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

33.0 33.0 9.5 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 2P231854-1, Fan: 3P173872-1 Turbo Fan 56W Panasonic 3P173872-1

Printed Circuit Board: Main DAIKIN 2034193; Group Control Adaptor DAIKIN KRP4A74 , Expansion Valve: Valve Saginomiya

3SA50093-1

Other: Installation Box for Adapter PCB DAIKIN KRP1H98; DAIKIN KRP1C75 Wiring Adapter PCB (requires KRP1H98 for

FXFQ_PVJU); DAIKIN KDDP55B160K Fresh Air Intake Kit with T Pipe; DAIKIN DACA-FQP13-1K MERV 13 Filter & Kit

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic. Plastic enclosure with 6-#10 SMS at each mounting ear (24

total) & #10 SMS in grille latch

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 18Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXFQ09PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 59 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

82

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with ½” washers and nuts above and below mounting ears & (8)

1/8” diagonal cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.95 1.0 1.5 4.72 3.54 1.97 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

33.0 33.0 11.4 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7mm coil DAIKIN 2P231856-1, Fan: 3P173873-1 Turbo Fan 120W Panasonic 3P173873-1, Printed Circuit Boards:

Main DAIKIN 2034193; Group Control Adaptor DAIKIN KRP4A74

Expansion Valve: Valve Saginomiya 3SA50095-1, Other: DAIKIN KRP1H98 Installation Box for Adapter PCB; DAIKIN KRP1C75

Wiring Adapter PCB (requires KRP1H98

for FXFQ_PVJU); DAIKIN KDDP55B160K Fresh Air Intake Kit with T Pipe; DAIKIN DACA-FQP13-1K MERV 13 Filter & Kit

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of plastic. Plastic enclosure with 6-#10 SMS at each mounting ear (24

total) & #10 SMS in grille latch

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 19Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXFQ48PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 60 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

67

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted w/ A14(4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each

end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.92 1.0 1.5 4.67 3.50 1.95 0.78

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

25.0 30.0 12.0 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P290389-1, Fan: Sirocco Fan 90W NIDEC 3P229859-1

Printed Circuit Boards: Main DAIKIN 4006121; Printed Circuit Assy. (Fan) DAIKIN 4006122

Expansion Valve: Valve Fujikoki 2SA50046-1-KE

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 20Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXMQ12PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 61 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

99

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.90 1.0 1.5 4.64 3.48 1.93 0.77

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

30.0 42.5 12.0 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P288941-1, Fan: Sirocco Fan 350W Panasonic 3P259061-2

Printed Circuit Board: Printed Circuit Assy. DAIKIN 1863862; Printed Circuit Assy. (Inverter) DAIKIN 2007595; Main DAIKIN 4006121,

Expansion Valve: Valve Fujikoki 2SA50046-1-SU

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 21Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXMQ18PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 62 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

128

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end .

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.98 1.0 1.5 4.77 3.58 1.99 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

30.0 58.5 12.0 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 7 mm x 0.3 mm coil DAIKIN 3P288942-1, Fan: Sirocco Fan 350W Panasonic 3P204674-2

Printed Circuit Boards: Inverter Assy. DAIKIN 2007588; DAIKIN 1863862; Main DAIKIN 4006121, Expansion Valve: Valve Fujikoki

2SA50046-2-KA

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB; DAIKIN KRP4A96 Mounting Plate for Accessory PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 22Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXMQ48PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 63 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

212

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.98 1.0 1.5 4.77 3.58 1.99 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

33.5 44.5 18.5 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger 8 mm x 0.3 mm coil DAIKIN CRB-FXYMP224M

Fan: Sirocco Fan 380W TOP 3P028033-1, Printed Circuit Board: Main DAIKIN 1962257

Expansion Valve: Valve Fujikoki 2SA50046-2-KA

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 23Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXMQ48MFVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 64 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

376

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted with (4) 3/8”Ø A36 hanger rods w/ rod stiffeners with 1/2” washers and nuts above and below mounting ears &

(8) 1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.92 1.0 1.5 4.67 3.50 1.95 0.78

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

44.5 58.5 19.5 N/A N/A

Options/Subcomponent Summary:

Heat Exchanger: 8 mm x 0.3 mm coil DAIKIN CRB-FXYMP280M

Fan: Sirocco Fan (380W x 2) TOP 3P028033-1, Printed Circuit Boards: Main DAIKIN 1962257; Main DAIKIN 1962219

Expansion Valve: Valve Fujikoki 2SA50046-2-KE

Other: DAIKIN DACA-FXMQ12-13-1K MERV 13 Filter Kit (Throwaway Type); DAIKIN KRP1C74 Wiring Adapter PCB; DAIKIN KRP4A71

Group Control Adaptor PCB

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Indoor Fan Coil (ceiling mounted) enclosure constructed of carbon steel. Plastic enclosure with #10 SMS at each mounting ear (4

total)

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 24Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXMQ96MVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 65 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

25

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted with (4) 3/8”Ø A36 hanger rods & (8) 1/8” Ø diagonal cable braces w/ Mason SCB-1 clips at each end. Unit

maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.98 1.0 1.5 4.77 3.58 1.99 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

13.0 12.5 8.1 N/A N/A

Options/Subcomponent Summary:

Printed Circuit Board: Main DAIKIN 1893591

Valves: BODY/ MOTOR OPERATED VALVE DAIKIN 1801408; COIL/ MOTOR OPERATED VALVE DAIKIN 1801299; BODY/ MOTOR

OPERATED VALVE DAIKIN 1801390; COIL/ MOTOR OPERATED VALVE DAIKIN 1801282; BODY/ MOTOR OPERATED VALVE DAIKIN

1801390; COIL/ MOTOR OPERATED VALVE DAIKIN 1801275; BODY/ MOTOR OPERATED VALVE DAIKIN 1801415; COIL/ MOTOR

OPERATED VALVE DAIKIN 1801268; BODY/ MOTOR OPERATED VALVE DAIKIN 1801415; COIL/ MOTOR OPERATED VALVE DAIKIN

1801251UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Branch Selector: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 25Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: BSVQ36PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 66 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

203

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.95 1.0 1.5 4.72 3.54 1.97 0.79

Test Mounting Details:

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

25.0 62.1 8.1 N/A N/A

Options/Subcomponent Summary:

Printed Circuit Board: Main DAIKIN 2058618

Valves: COIL/ MOTOR OPERATED VALVE (MAIN SUCTION)DAIKIN 1939738; COIL/ MOTOR OPERATED VALVE (MAIN DISCHARGE)

DAIKIN 1939745; COIL/ MOTOR OPERATED VALVE (SUB SUCTION) DAIKIN 1939752; COIL/ MOTOR OPERATED VALVE (SUB

DISCHARGE)

DAIKIN 1939769; COIL/ MOTOR OPERATED VALVE (SUB COOL) DAIKIN 1939776

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Branch Selector: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 26Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: BSV6Q36PVJU Serial Number: N/A

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 67 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

444

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.5 1.0 1.5 4.00 3.00 1.67 0.67

Test Mounting Details:

>33.3

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

30.2 36.7 66.7 5.4 21.2

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7009440

Compressor: 72,000 BTU/hr, 208-230V, Carbon Steel, Daikin 1873054

Fan Motor: Propellor Fan 500 Watts, 208-230V, Panasonic, 1713309

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Heat Pump: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 27Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RXYQ72TTJU Serial Number: 1510195615

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 68 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

702

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

30.2 48.9 66.7 4.5 6.8

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

>33.3

Options/Subcomponent Summary:

Heat Pump: carbon steel enclosure with seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 28Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RXYQ168TYDN Serial Number: 1510119528

Product Construction Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7009559

Compressor: 96,000 BTU/hr, 460V, Carbon Steel, Daikin 7009494

Fan Motor: Propellor Fan 650 Watts, 460V, Panasonic, 4012442

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 69 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

518

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

2.5 1.0 1.5 4.00 3.00 1.67 0.67

Test Mounting Details:

>33.3

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

30.2 36.7 66.7 4.9 7.5

Options/Subcomponent Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7500019

Compressor: 72,000 BTU/hr, 208-230V, Carbon Steel, Daikin 7009487

Fan Motor: Propellor Fan 400 Watts, 208-230V, Panasonic, 2219437

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Heat Pump: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 29Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: REYQ72TTJU Serial Number: 1510085242

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 70 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

798

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

30.2 48.9 66.7 4.2 5.4

Rigid base mounted with (4) 3/8ӯ A307 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

>33.3

Options/Subcomponent Summary:

Heat Pump: carbon steel enclosure with seismic enhancements: (3) #10 self tapping screws in each foot (12 total)

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 30Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: REYQ168TYDN Serial Number: 1506206866

Product Construction Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 7500099

Compressors: 96,000 BTU/hr, 460V, Carbon Steel, Daikin 7009494 and 7009548

Fan Motor: Propellor Fan 650 Watts, 460V, Panasonic, 4012442

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 71 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

48

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

18.9 14.6 11.8 N/A N/A

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A

Options/Subcomponent Summary:

Branch Selector: carbon steel enclosure with seismic enhancements: Additional (4) #10 self tapping screws in each mounting ear

connection

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 31Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: BS4Q54TVJ Serial Number: A001008

Product Construction Summary:

Valves: COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271194; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227476; COIL/ ELECTRONIC EXP.

VALVE ASSY., DAIKIN 2227515; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271202; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227469;

COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227508; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271219; COIL/ ELECTRONIC EXP. VALVE

ASSY., DAIKIN 2227452; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227490; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271226; COIL/

ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227445; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227483

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 72 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

104

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

18.9 32.3 11.8 N/A N/A

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A

Options/Subcomponent Summary:

Branch Selector: carbon steel enclosure with seismic enhancements: 1/8" steel backer plate behind each mouting ear with (2)

machine screws through each mounting ear.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 32Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: BS12Q54TVJ Serial Number: A000140

Product Construction Summary:

Valves: COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271194; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227476; COIL/ ELECTRONIC EXP. VALVE

ASSY., DAIKIN 2227515; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271202; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227469; COIL/

ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227508; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271219; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN

2227452; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227490; COIL/ ELECTRONIC EXP. VALVE, DAIKIN 2271226; COIL/ ELECTRONIC EXP.

VALVE ASSY., DAIKIN 2227445; COIL/ ELECTRONIC EXP. VALVE ASSY., DAIKIN 2227483

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 73 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

56

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

37.4 37.4 7.8 N/A N/A

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A

Options/Subcomponent Summary:

Indoor Fan Coil (ceiling mounted): plastic and carbon steel cabinet with seismic upgrades: Four (4) 15/32” x 4-1/2” x 0.041”

extension springs between grille cover and unit corner, fastened to existing screws and retightened. Springs extended

approximately 2”. Heavy duty square washer (1.5”x1.5”) top and bottom of mounting bracket with (2) ½” flat washers as spacers

on top only.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 33Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXUQ18PVJU Serial Number: C000176

Product Construction Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 2273936

Fan Motor: QTS48D11M Turbo Fan 46W, 208-230V, Panasonic 2110749

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 74 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

54

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

33.1 33.1 9.7 N/A N/A

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (4) 1/8” Ø diag. cable braces w/ Mason SCB-1 clips at each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A

Options/Subcomponent Summary:

Indoor Fan Coil (ceiling mounted): plastic and carbon steel enclosure with seismic upgrades: Eight (8) #10 SMS in each mounting

ear. Four (4) cable tie (shipped with unit) chains, each with two links, between decoration panel cover latches and through

mounting ear. Two (2) strips of heavy duty Velcro® tape 1” x 2” at each corner cover (eight total).

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 35Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXFQ07TVJU Serial Number: C000406

Product Construction Summary:

Heat Exchanger: 7mm x 0.3mm coil, Daikin 1993028

Fan Motor: QTS48C15M Turbo Fan 48W, 208-230V, Panasonic 1993105

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 75 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

175.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

12.6 37.0 39.0 13.21 12.1

In addition to (4) 1/2” Grade 5 bolts used at the mounting feet, UUT #37 was also secured to the shake table with stainless-steel

strapping. Two (2) stainless steel straps ( ¾” wide and 0.02” thick) were secured approximately 30˚relative to vertical surface of

the unit to the shake table with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws at each end of the strapping. The strapping

was affixed to the top of the test unit with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

> 33.3

Options/Subcomponent Summary:

Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 37Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RXTQ36TAVJU Serial Number: F000419

Product Construction Summary:

Daikin Heat Exchanger 6021439

Daikin Swing Compressor 15.3A 6025911

Fan Motor 200W Daikin 6016145

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 76 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

221.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

12.6 35.4 52.9 >33.3 10.97

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

In addition to (4) 1/2” Grade 5 bolts used at the mounting feet, UUT #38 was also secured to the shake table with stainless-steel

strapping. Two (2) stainless steel straps ( ¾” wide and 0.02” thick) were secured approximately 30˚relative to vertical surface of

the unit to the shake table with (2) #10-16 X1/2” Phillips Pan Head Zinc Finish Screws at each end of the strapping. The strapping

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

> 33.3

Options/Subcomponent Summary:

Heat Pump: carbon steel enclosure with (4) cable ties grille to unit frame

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 38Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RXTQ60TAVJU Serial Number: F001523

Product Construction Summary:

Daikin Heat Exchanger 6019584

Swing Compressor 23.2A Daikin 2025911

Fan Motor (2) 70W Daikin 2024336

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 77 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

439

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

22.2 30.2 38.6 10.25 8.80

Rigid base mounted with (4) 5/8”Grade 5 bolts

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.671.5

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

20.52

Options/Subcomponent Summary:

Outdoor Water Cooled Heat Recovery: carbon steel cabinet

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 39Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RWEQ96TATJU Serial Number: 1700004

Product Construction Summary:

Daikin Heat Exchanger 5018937, Scroll Compressor Daikin 5018933, Daikin Fan Motor 5019722

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 78 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

94.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

17.5 45.0 10.68 10.65

3.2 2.41.5

UUT#40 was mounted on plenum boxes. The plenum box was constructed of 10-gauge carbon steel. UUT#40’s plenum box

dimensions are as follows: 21.25” x 18.5” x 25.12” with a weight 80.5 lbs. UUT #40 was secured to the plenum box with (5) #10 -16

x 1-1/2” screws on both the right and left side at the junction of the AHU and plenum box. The AHU/plenum box was secured to

the shake table with steel angles. Two L2.5x2x3/16 LLV, each side w/ (2) #10-16 x 1-1/2” screws w/ integral washer through

slotted hole to unit and 3/8” Grade 5 bolt w/ washer and lock washer to table.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

1.67 0.67

1/2 Hp Fan Motor, electric expansion valve-Daikin 3S500048-1, Daikin Heat Exchanger 0270A01156

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

11.121.0

Air Handling Unit: carbon steel enclosure mounted to plenum box.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 40Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXTQ09TAVJU Serial Number: 1702209059

Product Construction Summary:

Options/Subcomponent Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 79 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

147

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

24.5 58.0 8.83 12.45

3.2 2.41.5

UUT #41 was mounted on plenum boxes. The plenum box was constructed of 10-gauge carbon steel. UUT#41’s plenum box

dimensions are as follows: 21.25” x 25.5” x 25.12” with a weight 98.0 lbs. UUT #41 was secured to their respective plenum boxes

with (5) #10 -16 x 1-1/2” screws on both the right and left side at the junction of the AHU and plenum box. The AHU/plenum box

was secured to the shake table with steel angles. Two L2.5x2x3/16 LLV, each side w/ (2) #10-16 x 1-1/2” screws w/ integral washer

through slotted hole to unit and 3/8” Grade 5 bolt w/ washer and lock washer to table.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

1.67 0.67

1 Hp Fan Motor, electric expansion valve-Daikin 3S500054-1, Daikin Heat Exchanger 0270A01206

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

27.6321.0

Air Handling Unit: carbon steel enclosure mounted to plenum box.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 41Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXTQ60TAVJU Serial Number: 1710220821

Product Construction Summary:

Options/Subcomponent Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 80 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

60.5

SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

2.0 1.0

2.5 0.0

37.4 7.8 N/A N/A

3.2 2.41.5

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-0 clips at

each end.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

1.67 0.67

Heat Exchanger: 7mm x 0.3mm coil, Daikin 2110756

Fan Motor: QTS48D11M Turbo Fan 106W, 208-230V, Panasonic

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A37.4

Indoor Fan Coil (ceiling mounted): plastic and carbon steel enclosure with seismic upgrades: Heavy duty square washers (1.6" x

1.3 x 0.2”) were used at top and bottow of mounting bracket. S-Shape hooks on four (4) internal wires, used to secure outer cover

attachment to uni t, were crimped closed to secure cover to unit.

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 42Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXUQ36PVJU

Serial Number: C000618

Product Construction Summary:

Options/Subcomponent Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 81 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

450.5

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0

2.5 0.0

27.37

Base mounted with four (4) 5/8" Grade 8 bolts with lock and flat washer.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

22.1 30.1 38.6 7.36 9.40

1.5

Options/Subcomponent Summary:

3.2 2.4

Scroll Compressor (Daikin) PN: JT16KADWYDN@S, Heat Exchanger (Daikin) PN: 5018937

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

1.67 0.67

Outdoor Water Cooled Heat Recovery: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 45Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RWQEQ144TAYDU Serial Number: 1800331

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 82 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

51

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0

2.5 0.0

31.5 21.7 9.7 N/A N/A

Ceiling mounted w/ (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-0 clips at

each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. See next page for details.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

2.4 1.67 0.673.21.5

Options/Subcomponent Summary:

Heat Exchanger (Daikin) PN: 2397793, Expansion Valve (Daikin) PN: 4015738, Fan Assembly (Sirocco) PN: 2397818, Fan Motor

(Panasonic) PN: 4015745

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/a

Indoor Fan Coil (ceiling mounted): carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 46Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXSQ07TAVJU Serial Number: E000654

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 83 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 46Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXSQ07TAVJU Serial Number: E000654

Modification Details:

Six (6) #12 -3/4" self tapping screws added to the four (4) mounting ears on the unit.

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 84 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

110.5

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0

2.5 0.0

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.2 2.4

31.5 61.0 9.7 N/A N/A

1.671.5

Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-

0 clips at each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. One additional #12- 3/4" self tapping

screw was added to the ebox. See next page for details.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

0.67

Test Mounting Details:

Indoor Fan Coil (ceiling mounted): carbon steel enclosure

Options/Subcomponent Summary:

Heat Exchanger (Daikin) PN: 2397933, Expansion Valve (Daikin) PN: 2371955, Fan Assembly (Sirocco) PN: 2P394978-1, Fan Motor

(Panasonic) PN: 4016361

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 47Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXSQ54TAVJU Serial Number: E000181

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 85 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 47Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXSQ54TAVJU Serial Number: E000181

Modification Details:

Single #12-3/4" self tapping screw added to Ebox.

Six (6) #12 -3/4" self tapping screws added to the four (4) mounting ears on the unit.

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 86 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

41.5

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0

2.5 0.01.5

Test Mounting Details:

21.6 21.6 10.3 N/A N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 2.4 1.67 0.67

N/A

Options/Subcomponent Summary:

Heat Exchanger (Daikin) PN: 5011000, Expansion Valve (Daikin) PN: 2108342, Turbo Fan Rotor (Sirocco) PN: 5011010, Fan Motor

(Panasonic) PN: 5011038

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-

0 clips at each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. One additional #12- 3/4" self tapping

screw was added to the Ebox. See next page for details.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

Indoor Fan Coil (ceiling mounted): carbon steel enclosure and plastic decorative panel

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 48Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXZW09TAVJU Serial Number: J002344

Product Construction Summary:

3.2

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 87 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 48Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXZW09TAVJU Serial Number: J002344

Modification Details:

Single #12-3/4" self tapping screw added to Ebox

1

2

1. 3M Dual Lock Velcro used to secure filter.2. Stainless steel hanging wire, 50lb, and 1/16" ferrule used to secure each hinge.

#18-1" sheet metal screw added to outside of filter door

1

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 88 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

46

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0

2.5 0.0

N/A

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.2 2.4

21.6 21.6 10.3 N/A N/A

1.671.5

Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag. cable braces w/ Mason SCB-0/SCBH-

0 clips at each end. Six (6) #12 - 3/4" self tapping screw were added to each mounting ear. One additional #12- 3/4" self tapping

screw was added to the ebox. See next page for details.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

0.67

Test Mounting Details:

Indoor Fan Coil (ceiling mounted): carbon steel enclosure and plastic decorative panel

Options/Subcomponent Summary:

Heat Exchanger (Daikin) PN: 5011003, Expansion Valve (Daikin) PN: 2110073, Turbo Fan Rotor (Sirocco) PN: 5011010, Fan Motor

(Panasonic) PN: 5011038

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 49Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXAQ18TAVJU Serial Number: J002138

Product Construction Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 89 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 49Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FXAQ18TAVJU Serial Number: J002138

Modification Details:

t

Single #12-3/4" self tapping screw added to Ebox

1

1

2

1. 3M Dual Lock Velcro used to secure filter.2. Stainless steel hanging wire, 50lb, and 1/16" ferrule used to secure each hinge.

#18-1" sheet metal screw added to outside of filter door

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 90 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

714

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0

2.5 0.01.5

14.1030.2

Outdoor Heat Recovery: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 50Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: REYQ72XATJU Serial Number: 999999999-2

Product Construction Summary:

Options/Subcomponent Summary:

Vapor Injection Scroll Compressor (Daikin) PN: JT160KADWTJ@T, Heat Exchanger (Daikin) PN: 3P341763-2, Heat Exchanger Plate

HX (Daikin) PN: 3P412977-1, Fan Motor (Daikin) PN: 2P360713-3

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

48.9 66.7

Base mounted with four (4) 1/2-13 Grade 8 bolts with lock and flat washer. Three (3) #12 3/4" self tapping screws were added at

each foot.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.67

3.43 7.22

Three #12 3/4" Self Tapping Screws

1/2" -13 Grade 8 Bolt

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 91 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001-R1

785

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0

2.5 0.01.5

>33.330.2

Outdoor Heat Recovery: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 51Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: REYQ168XATDU Serial Number: 999999999-2

Product Construction Summary:

Options/Subcomponent Summary:

Vapor Injection Scroll Compressor (Daikin) PN: JT25KADWYDN@S, Heat Exchanger (Daikin) PN: 3P341763-2, Heat Exchanger

Plate HX (Daikin) PN: 39412975-1, Fan Motor (Daikin) PN: 2P343735-1

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

48.9 66.7

Base mounted with four (4) 1/2-13 Grade 8 bolts with lock and flat washer. Three (3) #12 3/4" self tapping screws were added at

each foot.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.2 2.4 1.67 0.67

3.48 5.71

Three #12 3/4" Self Tapping Screws

1/2" -13 Grade 8 Bolt

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 92 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001 R1

1002

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0 1.5

2.5 0.0 1.5

12.8330.5

Outdoor Heat Recovery: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 52Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: REYQ240AAYDA Serial Number: MT20007

Product Construction Summary:

Options/Subcomponent Summary:

Vapor Injected Scroll Compressor: Daikin - 240,000 BTU/HR

Fan Motor: Daikin (2P618618-1) - 950W x 2

Heat Exchanger: Daikin (2P623585-1)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

67.0 65.4

Base mounted - rigid with (6) 1/2" - 8 Grade hex-head bolts, washers, and lock washers

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156

Test Mounting Details:

3.20 2.40 1.67 0.67

4.16 30.36

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 93 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001 R1

554

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0 1.5

2.5 0.0 1.5

36.6 65.4

Test Mounting Details:

Base mounted - rigid with (6) 1/2" - 8 Grade hex-head bolts, washers, and lock washers. Used center wind slots.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67

5.17 8.54

Scroll Compressor: Daikin - 72,000 BTU/HR

Fan Motor: Daikin (2P618618-1)

Heat Exchanger: Daikin (2P626353-1)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

>33.330.5

Outdoor Heat Recovery: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 53Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: REYQ72AATJA Serial Number: N/A

Product Construction Summary:

Options/Subcomponent Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 94 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001 R1

50

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0 1.5

2.5 0.0 1.5

Test Mounting Details:

Ceiling mounted - rigid with w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & four (4) 3/32” Ø diag. cable braces w/ Mason

SCB-0/SCBH-0 clips at each end. Washers at mounting were square plate washers.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67

N/A N/A

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A13.8 23.4 9.5

Branch Selector: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 54Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: BSF4Q54TVJ Serial Number: A00026

Product Construction Summary:

Options/Subcomponent Summary:

EEV Body: Fujikoki (3S500038-1)

EEV Coil: Fujikoki (3P363865-1)

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 95 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001 R1

83.5

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0 1.5

2.5 0.0 1.5

24.0 9.5

Test Mounting Details:

Ceiling suspended/mounted - rigid Ceiling mounted w/ four (4) 3/8”Ø A36 hanger rods w/ rod stiffeners & eight (8) 3/32” Ø diag.

cable braces w/ Mason SCB-0/SCBH-0 clips at each end. Washers used for mounting were square plate washers

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67

N/A N/A

EEV Body: Fujikoki (3S500040-1)

EEV Coil: Fujikoki (3P389855-1)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A23.8

Branch Selector: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 55Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: BSF8Q54TVJ Serial Number: A001054

Product Construction Summary:

Options/Subcomponent Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 96 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001 R1

37

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0 1.5

2.5 0.0 1.5

47.0 13.4

Test Mounting Details:

Wall mounted - rigid with (9) 8-32 wood screws used to mount the mounting plate (see Image 2) . Additional (3) M4 x 1/2" screws

and used at base of unit (See Image 3).

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67

N/A N/A

Fan Motor: Daikin (KFD-325-64-84)

Heat Exchanger: Daikin (1P222779-1)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

N/A10.3

Indoor Fan Coil (wall mounted):plastic enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 56Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: FTX36NVJU Serial Number: E035579

Product Construction Summary:

Options/Subcomponent Summary:

Image 1

Image 2

Image 3

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 97 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001 R1

131.5

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0 1.5

2.5 0.0 1.5

34.3 28.9

Test Mounting Details:

Base mounted - rigid with (4) 3/8" - 8 Grade hex-head bolts, washers, and lock washers.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67

5.97 13.96

Compressor: Daikin (2YC63AAXD)

Fan Motor: Panasonic (D901B-37)

Heat Exchanger: Daikin (3P379239-1)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

>33.312.5

Heat Pump: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 57Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RK36NMVJUA Serial Number: E004712

Product Construction Summary:

Options/Subcomponent Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 98 of 99

OSP-0297

Mohammad Karim

05/17/2022

2100103-CR-001 R1

132

SDS (g) z/h IP AFLX-H (g) ARIG-H (g) AFLX-V (g) ARIG-V (g)

2.0 1.0 1.5

2.5 0.0 1.5

34.3 28.9

Test Mounting Details:

Base mounted - rigid with (4) 3/8" - 8 Grade hex-head bolts, washers, and lock washers.

Unit maintained structural integrity and remained functional per manufacturer requirement after shake table test.

Contents were included in testing per operating conditions.

UUT Highest Passed Seismic Run Information

Building Code Test Criteria

CBC 2019 ICC-ES AC156 3.20 2.40 1.67 0.67

6.42 14.89

Compressor: Daikin (2YC63AAXD)

Fan Motor: Panasonic (D901B-37)

Heat Exchanger: Daikin (3P379239-1)

UUT Properties

Weight

(lb)

Dimension (in) Lowest Natural Frequency (Hz)

Depth Width Height Front-Back Side-Side Vertical

>33.312.5

Heat Pump: carbon steel enclosure

UNIT UNDER TEST (UUT)SUMMARY SHEET

Manufacturer: Daikin North America, LLC

UUT 58Model Line: Split System, Quaternity, SkyAir, VRV-S, VRV

Model Number: RX36NMVJUA Serial Number: E008172

Product Construction Summary:

Options/Subcomponent Summary:

TRU Compliance, by Structural Integrity Associates, Inc.

844-TRU-0200 | [email protected] 05/17/2022

OSP-0297

Page 99 of 99

OSP-0297

Mohammad Karim