SCOPE OF WORK PROCUREMENT OF PRESSURE TRANSMITTER, DIFFERENTIAL PRESSURE TRANSMITTER & TEMPERATURE TRANSMITTER The specification of the materials are provided below and materials provided by the vendor should be accordingly suitable for our use. DIFFERENTIAL PRESSURE TRANSMITTER (0 to 2 Kg/cm2) GENERAL Function: Transmitter, indicating TYPE: MICROPORCESSOR BASED SMART, HART Case: Manufacturer standard Mounting: YOKE -2 inch pipe mounting Mounting accessories: Required Mounting bracket: U bolt & nuts suitable for 2 inch pipe required Electrical area classification: IEC zone-1 GR IIA/IIB, T3 Enclosure: weather proof IP-66 Class Intrinsically safe: YES, Ex ia IIA/IIB, T3 Cable entry: 1/2" NPTF (2 nos) Accuracy: "+/- 0.1% of calibrated span (including linearity hysteresis & repeatability Statutory Certification: CCOE certification required SIL Rating: SIL 2 Calibration Report: Required. TRANSMITTER Output: 4-20 mA HART Trans. Power supply: 24 V DC loop powered Zero and span adjustments: Both these adjustments shall be accessible locally at the transmitter as well as from the Hand Held Communicator (HHC). Both Zero & Span adjustments shall be non-interactive. Local mechanism of adjustment shall be clearly explained. This mechanism shall have tamper proof features. Rangeability (turndown ratio): 150:1 Response Time: 100 ms Long Term Stability: +/- 0.2% of URL for 10 years or better Temperature effect: Should be less than 0.005 % of range per Deg C Ambient temperature & Humidity: 5 Deg C to 65 Deg C & upto 95% RH non-condensing Process temperature: 0 to 70 Deg C Reverse polarity protection: To be provided Local indicator: Integral LCD digital display should be provided with each transmitter. Local indicator should be 3- 1/2 digit or better. This unit shall have 2 line alpha numeric displays. It shall have the feature of rotation by

Transcript of scope of work - Bharat Petroleum

SCOPE OF WORK

PROCUREMENT OF PRESSURE TRANSMITTER, DIFFERENTIAL PRESSURE TRANSMITTER &

TEMPERATURE TRANSMITTER

The specification of the materials are provided below and materials provided by the vendor should

be accordingly suitable for our use.

DIFFERENTIAL PRESSURE TRANSMITTER (0 to 2 Kg/cm2)

GENERAL

Function: Transmitter, indicating

TYPE: MICROPORCESSOR BASED SMART, HART

Case: Manufacturer standard

Mounting: YOKE -2 inch pipe mounting

Mounting accessories: Required

Mounting bracket: U bolt & nuts suitable for 2 inch pipe required

Electrical area classification: IEC zone-1 GR IIA/IIB, T3

Enclosure: weather proof IP-66 Class

Intrinsically safe: YES, Ex ia IIA/IIB, T3

Cable entry: 1/2" NPTF (2 nos)

Accuracy: "+/- 0.1% of calibrated span (including linearity hysteresis &

repeatability

Statutory Certification: CCOE certification required

SIL Rating: SIL 2

Calibration Report: Required.

TRANSMITTER

Output: 4-20 mA HART

Trans. Power supply: 24 V DC loop powered

Zero and span adjustments: Both these adjustments shall be accessible locally at the transmitter

as well as from the Hand Held Communicator (HHC). Both Zero &

Span adjustments shall be non-interactive. Local mechanism of

adjustment shall be clearly explained. This mechanism shall have

tamper proof features.

Rangeability (turndown ratio): 150:1

Response Time: 100 ms

Long Term Stability: +/- 0.2% of URL for 10 years or better

Temperature effect: Should be less than 0.005 % of range per Deg C

Ambient temperature

& Humidity: 5 Deg C to 65 Deg C & upto 95% RH non-condensing

Process temperature: 0 to 70 Deg C

Reverse polarity protection: To be provided

Local indicator: Integral LCD digital display should be provided with each

transmitter.

Local indicator should be 3- 1/2 digit or better. This unit shall have 2

line alpha numeric displays. It shall have the feature of rotation by

900 throughout 3600. Clearly mention the no. of digits of this

display.

Accuracy of display unit should be +/- 0.1% of input signal.

Electronics housing: It shall have the provision for rotation through 180 Deg C

Electronics: Electronics should be plug in cards type with high degree of

interchangeability among the transmitters of different ranges.

MEASURING UNIT

Service: Differential Pressure measurement of MS/HSD/SKO

Element: Diaphragm

Body material: Carbon steel

Element material: SS316

Process connection: 1/2" NPTF

Measuring Range: 0 to 2 Kg/cm2

Static pressure limit: 250 Kg/cm2

Static pressure effect on

Zero & span: Effect of static pressure should be clearly specified. Drift/error due

to static pressure in zero shall not be more than +/-0.1% of upper

range limit per 100 kg/cm2 change in static pressure. Span error

shall not be more than +/- 0.1% of upper range limit per 100 kg/cm2

change in static pressure. It should be possible to correct this error

through zero/span adjustment.

Over pressure limit: The design of the transmitter shall permit one side of the element to

be pressurized to maximum Design Static pressure of 250 Kg/cm2

with the other side vented to atmosphere, with no permanent

damage.

Vent / Drain Connection: To be provided on the side of the pressure chamber with 1/4 inch

NPT(F) thread & plug.

Warranty: 2 years warranty shall be provided from date of supply

PRESSURE TRANSMITTER (0 to 130 Kg/cm2)

GENERAL

Function: Transmitter, indicating

TYPE: MICROPORCESSOR BASED SMART, HART

Case: Manufacturer standard

Mounting: YOKE -2 inch pipe mounting

Mounting accessories: Required

Mounting bracket: U bolt & nuts suitable for 2 inch pipe required

Electrical area classification: IEC zone-1 GR IIA/IIB, T3

Enclosure: weather proof IP-66 Class

Intrinsically safe: YES, Ex ia IIA/IIB, T3

Cable entry: 1/2" NPTF (2 nos)

Accuracy: "+/- 0.075% of calibrated span (including linearity hysteresis &

repeatability

Statutory Certification: CCOE certification required

SIL Rating: SIL 2

Calibration Report: Required.

TRANSMITTER

Output: 4-20 mA HART

Trans. Power supply: 24 V DC loop powered

Zero and span adjustments: Both these adjustments shall be accessible locally at the transmitter

as well as from the Hand Held Communicator (HHC). Both Zero &

Span adjustments shall be non-interactive. Local mechanism of

adjustment shall be clearly explained. This mechanism shall have

tamper proof features.

Rangeability (turndown ratio): 150:1

Response Time: 100 ms

Long term Stability: +/- 0.2% of URL for 10 years or better

Temperature effect: Should be less than 0.005 % of range per Deg C

Ambient temperature

& Humidity: 5 Deg C to 65 Deg C & upto 95% RH non-condensing

Process temperature: 0 to 70 Deg C

Reverse polarity protection: To be provided

Local indicator: Integral LCD digital display should be provided with each

transmitter.

Local indicator should be 3-1/2 digit or better. This unit shall have 2

line alpha numeric displays. It shall have the feature of rotation by

900 throughout 3600. Clearly mention the no. of digits of this

display.

Accuracy of display unit should be +/- 0.1% of input signal.

Electronics housing: It shall have the provision for rotation through 180 Deg C

Electronics: Electronics should be plug in cards type with high degree of

interchangeability among the transmitters of different ranges.

MEASURING UNIT

Service: Pressure measurement of MS/HSD/SKO

Element: Diaphragm

Body material: Carbon steel

Element material: SS316

Process connection: 1/2" NPTF

Measuring Range: 0 to 130 Kg/cm2

Static pressure limit: 250 Kg/cm2

Static pressure effect on

Zero & span: Effect of static pressure should be clearly specified. Drift/error due

to static pressure in zero shall not be more than +/-0.1% of upper

range limit per 100 kg/cm2 change in static pressure. Span error

shall not be more than +/- 0.1% of upper range limit per 100 kg/cm2

change in static pressure. It should be possible to correct this error

through zero/span adjustment.

Over pressure limit: The design of the transmitter shall permit the element to

be pressurized to maximum Design Static pressure of 250 Kg/cm2

with no permanent damage.

Warranty: 2 years warranty shall be provided from date of supply

PRESSURE TRANSMITTER (0 to 20 Kg/cm2)

GENERAL

Function: Transmitter, indicating

TYPE: MICROPORCESSOR BASED SMART, HART

Case: Manufacturer standard

Mounting: YOKE -2 inch pipe mounting

Mounting accessories: Required

Mounting bracket: U bolt & nuts suitable for 2 inch pipe required

Electrical area classification: IEC zone-1 GR IIA/IIB, T3

Enclosure: weather proof IP-66 Class

Intrinsically safe: YES, Ex ia IIA/IIB, T3

Cable entry: 1/2" NPTF (2 nos)

Accuracy: "+/- 0.075% of calibrated span (including linearity hysteresis &

repeatability

Statutory Certification: CCOE certification required

SIL Rating: SIL 2

Calibration Report: Required.

TRANSMITTER

Output: 4-20 mA HART

Trans. Power supply: 24 V DC loop powered

Zero and span adjustments: Both these adjustments shall be accessible locally at the transmitter

as well as from the Hand Held Communicator (HHC). Both Zero &

Span adjustments shall be non-interactive. Local mechanism of

adjustment shall be clearly explained. This mechanism shall have

tamper proof features.

Rangeability (turndown ratio): 150:1

Response Time: 100 ms

Long term Stability: +/- 0.2% of URL for 10 years or better

Temperature effect: Should be less than 0.005 % of range per Deg C

Ambient temperature

& Humidity: 5 Deg C to 65 Deg C & upto 95% RH non-condensing

Process temperature: 0 to 70 Deg C

Reverse polarity protection: To be provided

Local indicator: Integral LCD digital display should be provided with each

transmitter.

Local indicator should be 3-1/2 digit or better. This unit shall have 2

line alpha numeric displays. It shall have the feature of rotation by

900 throughout 3600. Clearly mention the no. of digits of this

display.

Accuracy of display unit should be +/- 0.1% of input signal.

Electronics housing: It shall have the provision for rotation through 180 Deg C

Electronics: Electronics should be plug in cards type with high degree of

interchangeability among the transmitters of different ranges.

MEASURING UNIT

Service: Pressure measurement of MS/HSD/SKO

Element: Diaphragm

Body material: Carbon steel

Element material: SS316

Process connection: 1/2" NPTF

Measuring Range: 0 to 20 Kg/cm2

Static pressure limit: 250 Kg/cm2

Static pressure effect on

Zero & span: Effect of static pressure should be clearly specified. Drift/error due

to static pressure in zero shall not be more than +/-0.1% of upper

range limit per 100 kg/cm2 change in static pressure. Span error

shall not be more than +/- 0.1% of upper range limit per 100 kg/cm2

change in static pressure. It should be possible to correct this error

through zero/span adjustment.

Over pressure limit: The design of the transmitter shall permit the element to

be pressurized to maximum Design Static pressure of 250 Kg/cm2

with no permanent damage.

Warranty: 2 years warranty shall be provided from date of supply

PRESSURE TRANSMITTER (-1 to 4 Kg/cm2)

GENERAL

Function: Transmitter, indicating

TYPE: MICROPORCESSOR BASED SMART, HART

Case: Manufacturer standard

Mounting: YOKE -2 inch pipe mounting

Mounting accessories: Required

Mounting bracket: U bolt & nuts suitable for 2 inch pipe required

Electrical area classification: IEC zone-1 GR IIA/IIB, T3

Enclosure: weather proof IP-66 Class

Intrinsically safe: YES, Ex ia IIA/IIB, T3

Cable entry: 1/2" NPTF (2 nos)

Accuracy: "+/- 0.035% of calibrated span (including linearity hysteresis &

repeatability

Statutory Certification: CCOE certification required

SIL Rating: SIL 2

Calibration Report: Required.

TRANSMITTER

Output: 4-20 mA HART

Trans. Power supply: 24 V DC loop powered

Zero and span adjustments: Both these adjustments shall be accessible locally at the transmitter

as well as from the Hand Held Communicator (HHC). Both Zero &

Span adjustments shall be non-interactive. Local mechanism of

adjustment shall be clearly explained. This mechanism shall have

tamper proof features.

Rangeability (turndown ratio): 150:1

Response Time: 100 ms

Long term Stability: +/- 0.2% of URL for 10 years or better

Temperature effect: Should be less than 0.005 % of range per Deg C

Ambient temperature

& Humidity: 5 Deg C to 65 Deg C & upto 95% RH non-condensing

Process temperature: 0 to 70 Deg C

Reverse polarity protection: To be provided

Local indicator: Integral LCD digital display should be provided with each

transmitter.

Local indicator should be 3-1/2 digit or better. This unit shall have 2

line alpha numeric displays. It shall have the feature of rotation by

900 throughout 3600. Clearly mention the no. of digits of this

display.

Accuracy of display unit should be +/- 0.1% of input signal.

Electronics housing: It shall have the provision for rotation through 180 Deg C

Electronics: Electronics should be plug in cards type with high degree of

interchangeability among the transmitters of different ranges.

MEASURING UNIT

Service: Pressure measurement of MS/HSD/SKO

Element: Diaphragm

Body material: Carbon steel

Element material: SS316

Process connection: 1/2" NPTF

Measuring Range: -1 to 4 Kg/cm2

Static pressure limit: 250 Kg/cm2

Static pressure effect on

Zero & span: Effect of static pressure should be clearly specified. Drift/error due

to static pressure in zero shall not be more than +/-0.1% of upper

range limit per 100 kg/cm2 change in static pressure. Span error

shall not be more than +/- 0.1% of upper range limit per 100 kg/cm2

change in static pressure. It should be possible to correct this error

through zero/span adjustment.

Over pressure limit: The design of the transmitter shall permit the element to

be pressurized to maximum Design Static pressure of 250 Kg/cm2

with no permanent damage.

Warranty: 2 years warranty shall be provided from date of supply

TEMPERATURE TRANSMITTER (0 to 100 Deg C)

GENERAL

Function: Transmitter, indicating

TYPE: MICROPORCESSOR BASED SMART, HART

Case: Manufacturer standard

Mounting: YOKE – 2 inch pipe mounting

Mounting accessories: Required

Mounting bracket: U bolt & nuts suitable for 2" pipe required

Electrical area classification: IEC zone-1 GR IIA/IIB, T3

Enclosure: weather proof IP-66 Class

Intrinsically safe: YES, Ex ia IIA/IIB, T3

Cable entry: 1/2" NPTF (2 nos)

Accuracy: "+/- 0.2 % of calibrated span (including linearity hysteresis &

repeatability

Statutory Certification: CCOE certification required

SIL Rating: SIL 2

Calibration Report: Required.

TRANSMITTER

Output: 4-20 mA HART

Trans. Power supply: 24 V DC loop powered

Zero and span adjustments: Both these adjustments shall be accessible locally at the transmitter

as well as from the Hand Held Communicator (HHC). Both Zero &

Span adjustments shall be non-interactive. Local mechanism of

adjustment shall be clearly explained. This mechanism shall have

tamper proof features.

Long term Stability: +/- 0.2% of URL for 10 years

Temperature effect: Should be less than 0.005 % of range per Deg C

Ambient temperature

& Humidity: 5 Deg C to 65 Deg C & upto 95% RH non-condensing

Process temperature: 0 to 70 Deg C

Reverse polarity protection: To be provided

Local indicator: Integral LCD digital display should be provided with each

transmitter.

Local indicator should be 3-1/2 digit or better. This unit shall have 2

line alpha numeric displays. It shall have the feature of rotation by

900 throughout 3600. Clearly mention the no. of digits of this

display.

Accuracy of display unit should be +/- 0.1% of input signal.

Electronics housing: It shall have the provision for rotation through 180 Deg C

Electronics: Electronics should be plug in cards type with high degree of

interchangeability among the transmitters of different ranges.

MEASURING UNIT

Service: Temperature measurement of MS/HSD/SKO

Type: Pt-100, Simplex, 3 wire RTD

Body material: Carbon steel

Element material: SS316

Measuring Range: 0 to 100 Deg C

Warranty: 2 years warranty shall be provided from date of supply

The materials should be delivered to given addresss according to the list

given below:

ADDRESS 1:

MUMBAI REFINERY,

BHARAT PETROLEUM CORPORATION LIMITED

MAHUL GAON, CHEMBUR

MUMBAI,400074

ITEM QTY UNT

Pressure Transmitter -1 to 4 Kg/cm2 for Mumbai 2 No.

Pressure Transmitter 0 to 20 Kg/cm2 for Mumbai 8 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Mumbai 5 No.

Differential Pressure Transmitter 0 to 2 Kg/cm2 for Mumbai 4 No.

Temperature Transmitter 0 to 100 deg C for Mumbai 6 No.

ADDRESS 2:

WASHALA PUMPING STATION – MMBPL BHARAT PETROLEUM CORP. LTD VILLAGE-WASHALA, 7 KM from KASARA RAILWAY STATION TALUKA – SHAHPUR DISTRICT – THANE, MAHARASTRA – 421604 MOBILE: 9823060209

ITEM QTY UNT

Pressure Transmitter 0 to 20 Kg/cm2 for Washala 5 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Washala & SV-1 to 14 28 No.

Differential Pressure Transmitter 0 to 2 Kg/cm2 for Washala 2 No.

ADDRESS 3:

MOBILE: 9422271487

ITEM QTY UNT

Pressure Transmitter -1 to 4 Kg/cm2 for Manmad 2 No.

Pressure Transmitter 0 to 20 Kg/cm2 for Manmad & Sanghvi 13 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Manmad & Sanghvi 6 No.

MANMAD TERMINAL - MMBPL BHARAT PETROLEUM CORP. LTD MANMAD – NANDGAON ROAD PANEWADI, MANMAD MAHARASTRA -- 423104

ADDRESS 4:

MANGALYA TERMINAL MMBPL CONTROL ROOM BHARAT PETROLEUM CORP.LTD MANGALYA – SANVER ROAD INDORE- 453771 MOBILE: 9425065623

ITEM QTY UNT

Pressure Transmitter 0 to 20 Kg/cm2 for Manglya & Gujri 7 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Manglya & Gujri 6 No.

ADDRESS 5:

IPS KOTA – MMBPL BHARAT PETROLEUM CORP. LTD VILLAGE- BRIJESHPURA TAHSIL – TATHED DISTRICT – KOTA RAJASTHAN – 325201 MOBILE: 9928035386

ITEM QTY UNT

Pressure Transmitter 0 to 20 Kg/cm2 for Kota 4 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Kota, Sherpur, Malarna, Bharatpur, Karwadi 16 No.

ADDRESS 6: IPS MATHURA – MMBPL BHARAT PETROLEUM CORP. LTD ROAD NO 26, UPSIDC IND AREA, OPPOSITE IOCL REFINERY, MATHURA – 281005, MOBILE: 9412777828

ADDRESS 7:

PIYALA INSTALLATION – MMBPL BHARAT PETROLEUM CORP. LTDVILLAGE – PIYALA, POST – ASAOTI TEHSIL – BALLABGARH , DIST - FARIDABAD HARYANA – 121102 MOBILE : 9999102660

ITEM QTY UNT

Pressure Transmitter 0 to 20 Kg/cm2 for Piyala 4 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Piyala 4 No.

ADDRESS 8:

BIJWASAN INSTALLATION – MMBPL BHARAT PETROLEUM CORP. LTD POST – BIJWASAN NEW DELHI – 110061,MOBILE: 9910072573

ITEM QTY UNT

Pressure Transmitter 0 to 130 Kg/cm2 for Bijwasan 1 No.

ITEM QTY UNT

Pressure Transmitter 0 to 20 Kg/cm2 for Mathura 2 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Mathura 2 No.

Differential Pressure Transmitter 0 to 2 Kg/cm2 for Mathura 2 No.

ADDRESS 9:

ITEM QTY UNT

Pressure Transmitter 0 to 20 Kg/cm2 for Bina 2 No.

Pressure Transmitter 0 to 130 Kg/cm2 for Bina & Guna 3 No.

Temperature Transmitter 0 to 100 deg C for Bina 4 No.

BORL REFINERY, GATE NO – 3 BINA DESPATCH TERMINAL BHARAT PETROLEUM CORP.LTD BINA – MUNGAWALI ROAD VILLAGE – DEHRI, TEHSIL – BINA, DISTT.- SAGAR(M.P.) - 470113, MOBILE – 09575304063