ALL FOUNDATION SLAB SHALL BE 30" CONCRETE WITH #6 @ 8" ON CENTER, EACH WAY AND EACH FACE, (TOP AND BOTTOM), U.N.O.
FOR REINFORCEMENT GRADE AND TYPE, REFER TO GENERAL NOTES OR SPECIFICATIONS.
TOP SLAB ELEVATIONS REFER TO STRUCTURAL PLANS.
FOUNDATION PLAN, NOTES AND SPECIFICATION SHALL READ IN CONJUNCTION WITH ALL RELATED DISCIPLINES DOCUMENTS.
REFER TO CIVIL DOCUMENTS FOR SLAB LOCATION AND ORIENTATION.
REFER TO GEOTECHNICAL REPORT FOR SOIL BEARING CAPACITY AND FOUNDATION RECOMMENDATIONS.
FOUNDATION SLAB SHALL BE RESTED ON A 3'-0" DEEP LAYER OF TREMIE GROUT SLAB. REFER TO GEOTECHNICAL REPORT, FOR DEWATERING.
ANY DISCREPANCY SHALL BE REPORTED IN WRITING TO ENGINEER OF RECORD, PRIOR COMMENCING ANY WORK.
ALL REINFORCEMENT STEEL SHALL BE PLACED IN ACCORDANCE OF ACI318, AND ANY APPLICABLE CODE.
PROVIDE REQUIRED DEWATERING DURING ENTIRE PERIOD OF FOUNDATION SLAB AND PUMP STATION STRUCTURE CONSTRUCTION; PIPE INSTALLATION AND TEMPORARY SHEET PILING ACROSS THE CANAL AS PER LOCAL GOVERNING AUTHORITY REQUIREMENTS.
PROVIDE PROPOSE METHOD OF CONSTRUCTION WITH TEMPORARY SHORING FOR E.O.R. REVIEW AND APPROVAL PRIOR TO PROCEEDING WITH ANYWORK.
ID / SYMBOL DESCRIPTION
. INDICATES TARGET ELEVATION
STEEL INDICATES REINFORCEMENT SIZE AND DIRECTION
INDICATES DIRECTION OF SLAB SPAN
A INDICATES GRID LINE ID.
ID / SYMBOL DESCRIPTION WALL TYPE DESCRIPTION
1 8" CONCRETE WALL W/ #6 @ 8" O.C. E.W.
FOUNDATION REINFORCEMENTSIZE
LEGEND NOTES WALL TYPES SCHEDULE FOUNDATION SCHEDULE
1 INDICATES WALL TYPE
2 12" CONCRETE WALL W/ #6 @ 8" O.C. E.W. AND E.F.
12'-10" x 21'-6" X 30" DEEP F1 #6 CONT. BAR @ 8"O.C.
TOP AND BOTTOM, E.W.
BEAM TYPES SCHEDULE
BEAM TYPE DESCRIPTION
F2 2'-0" x 4'-6" T.E. SEE PLANS
F3 12'-6" x 21'-0" SEE PLANS
B-1 12"x1'-6" x 21'-0" LONG
B-2 12"x1'-6" x 17'-6" LONG
COLUMN SCHEDULE
COLUMN REINFORCEMENTSIZE
C-1 8x12 (4) #6 VERT. BARS
REINF.
RB-1
RB-3
TB-1
8"x12"
8"x12"
8"x12"
TOP EL.
0'-0"
0'-0"
11'-0"
VARIES
15'-0"
SEE DETAIL
SEE DETAIL
SEE DETAIL
SEE DETAIL
SEE DETAIL
3 8" MASONRY WALL W/ #5 @ 32" O.C.
#3 TIES @ 12" O.C.
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-0
AS NOTED
12-01-17
LN
DEF
LN
172603
PUMP STATION 3D VIEWS AND LEGEND AND SCHEDULES
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
PUMP HOUSE
PUMP STATION STRUCTURE
FOR BIDDING PURPOSES ONLY
A
B
1S-3
1S-4
C
D
12" THICK CONCRETE SLABON GRADE
3" MIN. COVER (TYP.)
A.1
6' -
5"3'
- 10
"10
' - 2
"
12" CONCRETE WALL
7' -
6"1'
- 4"
#5 @ 12" O.C. (TOP AND BOTTOM)
#5 @
12"
O.C
. (TO
P AN
D B
OTT
OM
)
#5 @ 10" O.C. E.W., E.F. (TYP.)
3S-4
15" THICKCONC. WALL
#6 HORIZONTAL E.F. @ 10" O.C.(TYP.)
#7 VERTICAL E.F. @ 6" O.C.(TYP.)
2S-4
7' -
0"
2S-3
1' - 3"
2' -
9"
OPE
NIN
G
4' -
0"
DIA
MET
ER3'
- 5"
1' -
4"
2' -
9"
OPE
NIN
G
4' -
0"
DIA
MET
ER3'
- 5"
TYP.1' - 0"
12" CONCRETE WALL
TRENCH (SEE SECTION FOR DETAIL)
48" THICKENED EDGE
(TYP)
1' - 8"
SLAB EDGE 1'-8" FROM WALL ALL AROUND (TYP)
8"2'
- 0"
1' -
0"4"
15' - 8"
EL. -10'-6"
EL. -10'-6"
EL. -11'-0"
S-5.01
TYP.
S-5.04
TYP.
#5 BENT HORIZONTALBARS @ 10"O.C. E.W., E.F. (TYP.)
1 1.1
1' - 3"
#6 - 90° BENT HORIZONTAL BARS @ 8" O.C. VERTICALLY (TYP.)
(TYP.)
1' - 8"
1' - 8 1/2"
2' -
6"
5/8" DIAMETER S.S. EYE BOLT 5" EMB. W/ EPOXY.
5/8" DIAMETER S.S. EYE BOLT 5" EMB. W/ EPOXY.
8" THICKCONC. WALL BELOW
18' - 2"
T.O SLAB -11' - 6"
CHAMFER AREA. SEE SHEET S-3
EDGE OF CONC. WALL BELOW SLAB
A
1.1
15" THICK CAST-IN-PLACE CONC. WALL
A.1
30" THICK CONCRETE SLABEL. -18'-0" TOP OF SLAB3" COVER MIN. (TYP.)ON 3'-0" DEEP TREMMI CONCRETE BED
1
18' - 2"
#6 -
90° S
TD H
OO
K @
8" O
.C.
(T &
B)
#6 - 90° STD HOOK @ 8" O.C. E.W. (T & B)
1' - 3" 7' - 6" 8"
#7 VERTICAL DOWELSE.F. @ 6" O.C., 90° STD HOOK(TYP)
1' - 8" 1' - 8"
1' -
8"10
' - 2
"
21' - 6"
1' -
8"
1S-3
2S-3
2S-4
#6 @ 8" O.C. (TYP)
#6 HORIZONTAL DOWELS E.F. @ 8" O.C., 90° STD HOOK (TYP)
8" THICK CONC. WALL
21' - 6"
13' -
6"
1' -
4"7'
- 6"
1' -
4"
7' - 6" 1' - 3"
8S-5.11' - 1"
1' -
1"
1' - 1"1' - 1"
1' - 1"
1' -
1"
1' -
1"
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
INTAKE LEVEL PLAN (EL -11'-0")
SCALE: 1/2" = 1'-0"
2
S-1
S-1
AS NOTED
12-01-17
LN
DEF
LN
172603
PUMP STATION INTAKE LEVEL AND LOWER LEVEL PLAN
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
PUMP HOUSE
LOWER LEVEL PLAN (EL -18'-0")
SCALE: 1/2" = 1'-0"
1
S-1
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
FOR BIDDING PURPOSES ONLY
UP
A
B
C
A.1
1S-3
2
S-4
4' - 0" 4' - 6" 4' - 0"
3' - 8" 11' - 0" 3' - 8"
C1C1
C1C1
ALUMINUM HAND RAIL & STAIR PROVIDE SIGN AND SEAL CALCULATIONS AND DRAWINGS FOR E.O.R. APPROVAL(SHOWN IN DASH LINE)
PROVIDE (3) #5 T&BAT EACH EDGE OF THE OPENING AS SHOWN (TYP.)
#6 @ 8" O.C. TOP & BOTT SEE DETAIL 1/S-3
8" THICK CMU WALL WITH#5 @ 32" O.C. FILL CELLSWITH 3000 PSI GROUT (TYP)
12" THICK CONCRETE SLAB WITH #5 @ 8" O.C. T&B E.W.
5' -
10"
3S-4
5' -
6 1/
2"
#6 @ 8" O.C.
T & B
#6 @ 8"O.C. T &B
(2) #5 x 30" LONGDIAGONAL BARS T & B (TYP)
#6 @ 8" O.C. TOP & BOTT SEE DETAIL 1/S-3
DOOR OPENING
3' - 4"
2'-0
" FR
OM
ED
GE
OF
OPE
NIN
G
SLO
PE
12" THICK LANDING SLAB EL. 0'-0"TOP OF SLAB
12" THICK SLABEL. 0'-0"TOP OF SLAB
7' - 4"
4' -
0"
B-1
B-2
WAL
L BE
LOW
S-5.17
TYP.
#6 @ 8" O.C. T & B
#6 @ 8" O.C.T & B
12" THICK CONCRETE SLABEL. VARIES T.O.S.
1 1.1 2
1' - 8" 1' - 0"
21' - 0"
1
S-4
OPENING(SEE CIVIL PLAN)
OPENING(SEE CIVIL PLAN)
2S-3
6' -
5"3'
- 10
"10
' - 2
"
1'-8"x1'-4" DEEP STRING JOIST W/ (3)-#5 T&B ON WELL COMPACTED GROUND (2000 PSI BEARING CAPACITY)
(6)-5/8"∅ EPOXY BOLTS STAGGERED 6"
3
WAL
L BE
LOW
3' -
0"
3' - 0"
OPENING(SEE CIVIL
PLAN)
(2) #5 x 30" LONGDIAGONAL BARS T & B (TYP)
PROVIDE (3) #5 T&BAT EACH EDGE OF THE OPENING AS SHOWN (TYP.)
14' -
0"
21' - 0"
#6 @
8" O
.C.
T &
B
36"x36" FLOOR/ HATCH ACCESS. REFER TO ARCH. DWGS.
2' -
11"
5' -
6 1/
2"
GLASS BLOCK WINDOW. RE: ARCH. DWGS.
5' -
6 1/
2"2'
- 11
"5'
- 6
1/2"
GLASS BLOCK WINDOW. RE: ARCH. DWGS.
2' - 2" 5' - 0"
11"
10' - 4"
6" 3' - 0"1' - 0"
1' -
0"W
ALL
BELO
W
12"x12" OPENING. COORDINATE WITH ELECTRICAL PLANS
PROVIDE (3) #5 T&BAT EACH EDGE OF THE OPENING AS SHOWN (TYP.)
#4 HOOK BAR 24" @ 6" O.C. MID DEPTH TYP. ALL AROUND
EL. 15'-0" T.O.P.ALL AROUND
TB-1
(EL.
15'
-0")
RB-
3(EL
. VAI
RES
)
TB-1
(EL.
15'
-0")
RB-
3( E
L. V
ARIE
S)
TB-1 (EL. 15'-0")RB-2 (EL. 11'-3")
TB-1 (EL. 15'-0")RB-1 (EL. 12'-0")
#5 @12"
MID DEPTH
(2) #5 x 30" LONGDIAGONAL BAR MID DEPTH (TYP.) S-5.0
8TYP.
S-5.17
TYP.
#5 @ 12" O.C.MID DEPTH
#5 @ 12" O.C.MID DEPTH
6" SLAB THICKNESSEL. VARIES
A
B
1 2
C-1 C-1
C-1 C-1
8" THICK CMU WALL
3-#5 @ EACH EDGE OF THE OPENINGS (TYP)
3
S-4
2
S-4
#5 DOWEL @ 12" O.C. (TYP.)
#5 @ 12" (TYP.)
#5-90° STANDARD HOOK @ OPENING @ 6" O.C.
#5-90° STANDARD HOOK @ OPENING @ 6" O.C.
1' - 9 1/2" 4' - 9" 3' - 9" 4' - 9" 4' - 7 1/2"
*SLO
PE
8" THK CMU WALL
A
B
1 2
C-1 C-1
C-1 C-1
TB-1
(EL.
15'
-0")
RB-
1(EL
. VAI
RES
)
TB-1
(EL.
15'
-0")
RB-
1( E
L. V
ARIE
S)
TB-1 (EL. 15'-0")RB-1 (EL. 11'-3")
TB-1 (EL. 15'-0")RB-1 (EL. 12'-0")
3
S-4
2
S-4
* REFER TO ARCHITECTURAL FOR BUILT-UP ROOF SYSTEM
*HATCH OPENINGAS PER
ARCHITECTURALPLANS (TYP)
21' - 0"
14' -
0"
14' -
0"
1' - 9 1/2" 4' - 9" 3' - 9" 4' - 9"
5' -
11"
5' -
10"
11"
5' -
11"
5' -
10"
11"
4' - 7 1/2"
REFER TO CIVIL PLAN FOR ROOF HATCH OPENING LOCATION
*HATCH OPENINGAS PER
ARCHITECTURALPLANS (TYP)
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
PLAN @ (EL 0'-0")
SCALE: 1/2" = 1'-0"
1
S-2
S-2
AS NOTED
12-01-17
LN
DEF
LN
172603
PUMP STATION GROUND LEVEL,ROOF LEVEL PLANS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
PUMP HOUSE
ROOF REINFORCEMENT LAY OUT PLAN
SCALE: 1/2" = 1'-0"
2
S-20' 1' 2'
* COORDINATE W/ ARCH TO DETERMINE THE TOP ELEVATION OF THE ROOF BEAM SO THAT IT SUPPORTS THE PRE-ENGINEERED LIGHT GAUGE TRUSSES OF THE ROOF CANOPY.
ROOF LEVEL PLAN
SCALE: 1/2" = 1'-0"
3
S-2
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
FOR BIDDING PURPOSES ONLY
GROUND LEVEL(FINISH FLOOR)
0' - 0"
8" CMU WALL W/ #5 @ 32" O.C. FULLY GROUTED FILL CELLS
12" DEEP CONCRETE DECK W/ #6 @ 8"O.C. E.W. AND T&B W/ 2.65% SLOPE
1' -
0"
LOWER SLAB-20' - 6"
INTAKE LEVEL-11' - 6"
TOP OF PARAPET13' - 0"
#5-90° VERTICAL DOWELS ,3'-0" LAP @ 32" O.C. TYP.
#5 @ 12"O.C. T & B , E.W. 3" COVER (TYP.)
#6-90° HOOKED BAR @ 8" O.C. E.W. T & B
12" CONC. SLAB
#6 HORIZONTAL BARS@ 10" O.C. E.F. , 3" COVER MIN.
#7 VERTICAL BARS @ 6" O.C. , E.F.
16" THICK CONC. WALL
30" DEEP CONC. PAD
TB-1 TB-1
RB-1 RB-1
4' - 0"
B-1B-2
1' -
0"6"
1' -
6"6"
1' - 0" 2' - 0" 8"
S-5.11
S-5.12
S-5.13
S-5.14
6' - 1" 1' - 0" 11' - 0" 1' - 0"
6" THICK CONCRETE ROOF DECK AS PER
PLAN
1' - 8"1' - 8"
13' - 6"
S-5.15
PRE- ENGINEERED LIGHT GAUGE METAL TRUSSES BY SPECIALTY ENGINEER (TYP.) SUBMIT SHOP DRAWINGS
#7 VERTICAL DOWEL@ 6" O.C.(TYP)
** NOTE: COORDINATE W/ ARCHITECT DWGS TO LOCATE ELEVATION OF ROOF BEAM SO THEY SUPPORT BOTH ROOF SLAB AND CANOPY.
A A-1 B C
10' - 2" 3' - 10" 6' - 5"
A-1
ROOF LEVEL11' - 0"
3/16"x6" WATERSTOP AS REQUIRED (TYP.)
#6 HORIZONTAL BARS @ 10" O.C. E.F. , 3" COVER MIN.
16" THICK CONC. WALL
2' -
6"
CO
NC
RET
E
3' -
0" T
REM
IE
ALL AROUND
3' - 0"
COVER3"
EXISTING GRADE(V.I.F.)-3' - 6"
EL. (±) -6.52'TOP ELEVATION OF PIPE(VERIFY W/ CIVIL PLANS)
8" CONCRETE CURTAIN WALL W/ #5 @ 10" O.C. E.W. CENTERED. SEE DETAIL 8/S-5.1
36" DIAMETER PIPE
#5 @ 12" O.C. E.W.MID DEPTH (TYP.)
(REBAR FOR OPENING NOT SHOWN FOR CLARITY)
STAIR LANDING (SEE 2/S-2 FOR REBAR LAYOUT)
20' - 5"
3' - 6"
7' - 6"1' - 4" 1' - 4"
1' - 0"12' - 10"
3/16"x6" WATERSTOP AS REQUIRED (TYP.)
7' -
6"8"
8" 14' - 10"
1' -
0"
11' -
6"
9' -
0"
ALUMINUM HAND RAIL . PROVIDE SIGN & SEAL DWGS FOR APPROVAL PRIOR TO CONSTRUCTION
10"
#6 BENT BAR @ 12" O.C.
3#6 CONT.
#6-90° STD. HOOK@ 6" O.C.
10' - 2"
1' -
1"
1' - 1" 5' - 4" 1' - 1"
CORNER CAST-IN-PLACE CONCRETE FILLET. SEE SHEET S-5.1 (TYP)
12"x12" WALL OPENING (BEYOND). REFER TO SHEET 8/S-11 OPENING REINFORCEMENT (TYP). COORDINATE WITH ELECT. PLANS
6"1'
- 0"
1' - 0"
EXHAUST FAN OPENING TO BE BELOW THE STRUCTURAL BEAM (BEYOND). CONTRACTOR TO FIELD VERIFY/ COORDINATE THE FINAL LOCATION NOT TO CONFLICT W/ THE CABINET HEIGHTS. SEE MECH. DWGS.
GROUND LEVEL(FINISH FLOOR)
0' - 0"
LOWER SLAB-20' - 6"
INTAKE LEVEL-11' - 6"
TOP OF PARAPET13' - 0"
RB-1RB-1
8" THICK CMU WALLW/ #5 @ 32" O.C. FULLY FILL CELLS
STAIR LANDING (SEE 2/S-2 FOR REBAR LAYOUT)
OPENING (SEE GROUND LEVEL PLAN)
#5 VERTICAL DOWELS ,3'-0" LAP @ 32" O.C. TYP.
#5 @ 12"O.C. T & B , E.W.
#6-90° HOOKED BAR @ 8" O.C. E.W. T & B
12" CONC. SLAB #6 HORIZONTAL BARS @ 10" O.C., E.F. 3" COVER MIN.
#7 VERTICAL BARS
@ 6" O.C. , E.F.
16" THICKCONC. WALL
#6 HORIZONTAL BARS @ 10" O.C. E.F. , 3" COVER MIN.
8" CONCRETE CURTAIN WALL W/ #6 @ 8" O.C. E.W. CENTERED. SEE DETAIL 8/S-5.1
16" THICK CONC. WALL
30" DEEP CONC. PAD
19' -
6"
1' -
6"
B-1
B-2
1' - 0" 2' - 0" 8"
1' -
6"6"
1' - 0" 4' - 0"
3" 5' - 10" 1' - 0" 11' - 0" 1' - 0"
6' - 5 3/8"
7' -
6"10
"8"
7' - 6" 14' - 10"
#6 VERT DOWEL @ 6" O.C.
S-5.12
SimS-5.1
5Sim
S-5.15
Sim
S-5.14
Sim
S-5.16
TYP.
A A-1 B C
10' - 2" 3' - 10" 6' - 5"
A-1
ROOF LEVEL11' - 0"
3/16"x6" WATERSTOP AS REQUIRED (TYP.)
3/16"x6" WATERSTOP AS REQUIRED (TYP.)
6" THICK CONCRETE ROOF DECK AS PER
PLAN
EXISTING GRADE(V.I.F.)-3' - 6"
ALUMINUM HAND RAIL . PROVIDE SIGN & SEAL DWGS FOR APPROVAL PRIOR TO CONSTRUCTION
HATCH ACCESS
3' - 0"
EL. (±) -6.52'TOP ELEVATION OF PIPE(VERIFY W/CIVIL PLANS)
36" DIAMETER PIPE
#5 @ 12" O.C. E.W.MID DEPTH (TYP.)
(REBAR FOR OPENING NOT SHOWN FOR CLARITY)
12' - 10"
11' -
6"
2' -
6"
9' -
0"
1' -
0"
ALUMINUM HAND RAIL . PROVIDE SIGN & SEAL DWGS FOR APPROVAL PRIOR TO CONSTRUCTION
3' - 6"
8"
3' -
6"
#6 BENT BAR @ 12" O.C.
#6-90° STD. HOOK@ 6" O.C.
3#6 CONT.
1' - 0" 6"
PRE- ENGINEERED LIGHT GAUGE METAL TRUSSES BY SPECIALTY ENGINEER (TYP.) SUBMIT SHOP DRAWINGS
1' -
1"
1' - 1" 5' - 4" 1' - 1"
3' - 6"
1' - 4"
7' - 6"
1' - 4"CORNER CAST-IN-PLACE CONCRETE FILLET. SEE SHEET S-5.1 (TYP)
12"x12" WALL OPENING (BEYOND). REFER TO SHEET 8/S-11 OPENING REINFORCEMENT (TYP). COORDINATE WITH ELECT. PLANS
6"1'
- 0"
EXHAUST FAN OPENING TO BE BELOW THE STRUCTURAL BEAM (BEYOND). CONTRACTOR TO FIELD VERIFY/ COORDINATE THE FINAL LOCATION NOT TO CONFLICT W/ THE CABINET HEIGHTS. SEE MECH. DWGS.
#3 REBAR STIRRUPS @ 12" O.C.
1' - 0"
8"
(3) #5 CONT., TOP & BOTTOM
(2) #5 CONT., MID B-1 & B-2
RB-1
(2) #5 CONT., TOP & BOTTOM
#5-90° STD. HOOK@ 12" O.C.
1' -
0"
12" CONCRETE SLAB W/ #6 @ 8" O.C. E.W. T&B
#3 REBAR STIRRUPS @ 12" O.C.
6" THICK CONCRETE ROOF DECK AS PER PLAN
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-3
AS NOTED
12-01-17
LN
DEF
LN
SECTION @ OPENING
SCALE: 3/8" = 1'=0"
2
S-3
PUMP STATION SECTIONS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
PUMP HOUSE
172603SECTION SCALE: 3/8" = 1'=0"
1
S-3
DETAIL
SCALE: 1-1/2" = 1'=0"
3
S-3
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
FOR BIDDING PURPOSES ONLY
12" CONCRETE WALL (TYP.)
#5 HORIZONTAL BARS@ 12" O.C. E.F. , 3" COVER MIN. (TYP.)
#5 VERTICAL BARS @ 12" O.C. , E.F. (TYP.)
12" DEEP CONCRETE SLAB SEE DETAIL 2/S-1 FOR REINFORCEMENT
10' -
6"
1' -
0"
21' - 6"
1' - 0" 16' - 2" 1' - 0"1' - 8" 1' - 8"
3/16"x6" WATERSTOP AS REQUIRED (TYP.)
EL. -11'-6"INTAKELEVEL
1.11 2
30" DEEP CONCRETE SLAB SEE PLAN FOR REINFORCEMENT
2' -
6"
21' - 6"
B-2
8" CMU WALL W/ #5 @ 32" O.C.FULLY GROUTED FILL CELL (TYP.)
12" DEEP CONCRETE PAD W/ #6 @ 8"O.C. E.W. AND T.B. W/ 2" SLOPE
1' - 8" 1' - 8"
2' - 10"
12" CONCRETE WALL
#5 HORIZONTAL BARS@ 12" O.C. E.F. , 3" COVER MIN.
#5 VERTICAL BARS @ 12" O.C. , E.F.
12" DEEP CONCRETE SLAB SEE DETAIL 2/S-1 FOR REINFORCEMENT
15" CONCRETE WALL(BEYOND)
RB-1 RB-1
15" CONCRETE WALL BEYOND
3/16"x6" WATERSTOP AS REQUIRED (TYP.)
4S-4
3S.5.1
EL. 0'-0"
GROUND LEVEL(FINISH FLOOR)
EL. -3'-6"
EXISTING GRADE(V.I.F.)
INTAKE LEVEL
HATCH ACCESS
3' - 0"
8" CONCRETE CURTAIN WALL W/ #5 @ 10" O.C. E.W. CENTERED. SEE DETAIL 8/S-5.1
6" THICK CONCRETE ROOF DECK AS PER
PLAN
(3)-#5 @ EACH EDGE OF THE OPENINGS (TYP)
#5 @ 12" O.C. E.W.MID DEPTH (TYP.)
8S.5.1
11' -
6"
EL. -11'-6"
1' - 8" 1' - 3" 7' - 6" 8" 7' - 6" 1' - 3" 1' - 8"
LOWER SLAB
EL. -20'-6"
9' -
0"
8S.5.1
PRE- ENGINEERED LIGHT GAUGE METAL TRUSSES BY SPECIALTY ENGINEER (TYP.) SUBMIT SHOP DRAWINGS
CORNER CAST-IN-PLACE CONCRETE FILLET. SEE SHEET S-5.1 (TYP)
6"
12"x12" SLAB OPENING. COORDINATE WITH ELECT. PLANS
1' - 0"
6"
12"x12" WALL OPENING. REFER TO SHEET 8/S-11 OPENING REINFORCEMENT (TYP). COORDINATE WITH ELECT. PLANS
3' - 2"
EXHAUST FAN OPENING TO BE BELOW THE STRUCTURAL BEAM. CONTRACTOR TO FIELD VERIFY/ COORDINATE THE FINAL LOCATION NOT TO CONFLICT W/ THE CABINET HEIGHTS. SEE MECH. DWGS.
1.11 2
15" CONCRETE WALL(TYP.)
#6 HORIZONTAL BARS @ 10" O.C. E.F. , 3" COVER MIN.(TYP.)
#7 VERTICAL BARS @ 6" O.C. , E.F. (TYP.)
30" DEEP CONCRETE SLABSEE PLAN FOR REINFORCEMENT
8" CMU WALL W/ #5 @ 32" O.C.FULLY GROUTED FILL CELL (TYP.) 12" DEEP CONCRETE PAD W/
#6 @ 8"O.C. E.W. AND T.B. W/ 2" SLOPE
4"x6" OPENINGS SEE MECHANICAL
DRAWINGS FOR SPECIFICATIONS
3'ø OPENINGS SEE CIVIL DRAWINGS
FOR LOCATION & ELEVATIONS PRIOR TO CONSTRUCTION(SEE TYPICAL OPENING DETAIL FOR ADDITIONAL REINFORCEMENT 7/S-5)
2' -
6"
21' - 6"
RB-1
RB-1
(3) #5 T&B @ EACH EDGE OF OPENING(TYP.)
4' - 0" 4' - 0"
3/16"x6" WATERSTOP AS REQUIRED (TYP.)
7S.5
6" THICK CONCRETE ROOF DECK AS PER PLAN
3S-5.1
EL. 0'-0"
GROUND LEVEL(FINISH FLOOR)
EL. -3'-6"
EXISTING GRADE(V.I.F.)
(3)-#5 @ EACH EDGE OF THE OPENINGS (TYP)
#5 @ 12" O.C. E.W.MID DEPTH (TYP.)
2' -
10"
4' -
4"3'
- 10
"
11' -
0"
8" CONCRETE CAP W/ 1#5 CONT.
8" PRE-CAST LINTEL
WALL OPENING. SEE ARCH. DWGS.
8" CMU WALL W/ #5 @ 32" O.C.FULLY GROUTED FILL CELL (TYP.)
8" CONCRETE CAP W/ 1#5 CONT.
2' -
10"
4' -
4"3'
- 10
"
8" CONCRETE CAP W/ 1#5 CONT.
8" PRE-CAST LINTEL
WALL OPENING. SEE ARCH. DWGS.
8" CONCRETE CAP W/ 1#5 CONT.
4' - 6"
1' - 9 1/2" 4' - 9" 3' - 9" 4' - 9" 4' - 8 3/8"
PRE-ENGINEERED LIGHT GAUGE METAL TRUSSES BY SPECIALTY ENGINEER (TYP.) SUBMIT SHOP DRAWINGS
8" CONCRETE CURTAIN WALL W/ #5 @ 10" O.C. E.W. CENTERED. SEE DETAIL 8/S-5.1
1' - 3"7' - 6" 8" 7' - 6"
1' - 3"
CORNER CAST-IN-PLACE CONCRETE FILLET. SEE SHEET S-5.1 (TYP)
1/4"∅-2" LONG TAPCON SCREW PER TRUSS
ROOF FINISH AS PER ARCHITECTURAL PLANS
8" CMU PARAPET WALL
6" THICK CONCRETE ROOF DECK AS PER PLAN
ROOF BEAM AS PER PLAN(RB-1)
EL. 13'-0"TOP OF PARAPET
8" LINTEL BLOCK W/ CONT. # 5
EL. 11'-0"TOP OF SLAB
#5-90° STD. HOOK@ 12" O.C.
PRE- ENGINEERED LIGHT GAUGE METAL TRUSSES BY SPECIALTY ENGINEER (TYP.) SUBMIT SHOP DRAWINGS
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
SECTION
SCALE: 3/8" = 1'=0"
2
S-4
SECTION
SCALE: 3/8" = 1'=0"
1
S-4
SECTION
SCALE: 3/8" = 1'=0"
3
S-4
S-4
AS NOTED
12-01-17
LN
DEF
LN
PUMP STATTION SECTIONS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
PUMP HOUSE
172603
DETAIL (SEE SHEET A-3 FOR DIMENSIONS)
SCALE: 1-1/2" = 1'=0"
4
S-4
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D. LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.
LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = 3.5' N.A.V.D.LYE GROUND LEVEL ELAVATION 0.0' = 7.0' N.A.V.D.
FOR BIDDING PURPOSES ONLY
16' THICK CONCRETE WALL
30" DEEP CONCRETE PAD W/ #6-90° HOOKED BAR @ 8"O.C., E.W., T&B
#7-90° STD. HOOK VERTICAL DOWEL @ 6" O.C. , E.F. (TYP)
#7 VERTICAL @ 6" E.F.
#6 HORIZ. @ 10" O.C. E.F.
(TYP
.)
36" L
AP M
IN.
3/16"x6" WATERSTOP AS REQUIRED
COVER3"
1' - 0"1"
1' -
1"
1' - 1"
1' -
0"1"
(2) # 5 CONT.
# 3 BENT BAR @ 12" O.C. 10" LONG EPOXY DOWEL 3" EMBEDMENT INTO CONCRETE WALL/ FOOTING (TYP)
CORNER CAST-IN-PLACE 4000 PSI MIN. EPOXY CONCRETE FILLET
CORNER CAST-IN-PLACE 4000 PSI MIN. EPOXY CONCRETE FILLET
#5 VERTICAL BAR @ 32" O.C. (TYP)
12" CONCRET SLABW/ #6 @ 8" O.C., E.F.,T & B (TYP)
8" CMU WALL
30" L
AP T
YP.
#5-90° STD. HOOKDOWEL @ 32" O.C.
8" CMU WALL
#5 VERTICAL DOWEL @ 32" O.C. (TYP)
12" CONCRETE SLAB w/ #6 @ 8" O.C., E.F.,T & B (TYP)
#5 VERTICAL BAR @ 32" O.C. (TYP)
16" THICK CONCRETE WALL (BELOW)
#7-90° STD. HOOK@ 6" O.C.
1' - 0" 2' - 0" 8"
1' -
6"6"
6" 4' - 0" #6 90° STD. HOOKED BAR @ 12" O.C. BOTTOM
#5 HORIZONTAL BAR@ 8" O.C. BOTT.
2'-0" x 4'-6" THICKNED EDGE
12" CONCRETE SLAB W/ #5 @ 12" O.C. E.W T&B
#6 BENT BAR @ 12" O.C.
1' -
0"6"
12" DEEP CONCRETE PAD #6 @ 8" O.C. E.W. AND T&B W/ 2" SLOPE 12"x18" CONCRETE BEAM (B-1 OR B-2)
1' - 0"
(3) #5 BOTTOM
#3 TIES @ 12" O.C.
(3) #5 TOP(2) #5 MID
#5-90° STD. HOOK@ 12" O.C.
#5-90° STD. HOOK@ 6" O.C.
6" THICK ROOF SLAB AS PER PLAN
LINTEL BLOCK
#5 HORIZONTAL BAR
#5 VERTICAL BAR @ 32" O.C.
GROUT FILLED
8" CMU WALL
11"(3) #5
#5 @ 12" O.C.
TOP OF ROOF SLAB
EL. 13'-0"TOP OF PARAPET
EL. 11'-0"TOP OF SLAB
8" CMU WALL
C-1
(4) # 5 VERTICAL BARS
#3 TIES @ 12"O.C.
8"
12"
REFER TO MASONRY NOTES FOR DUROWALL
#5-90° STD. HOOK@ 12" O.C.
1S-4
8" THICK CONCRETE WALL
30" DEEP CONCRETE PAD W/ #6-90° HOOKED BAR @ 8"O.C., E.W., T&B
#6-90° STD. HOOK VERTICAL DOWEL @ 8" O.C. , E.F. (TYP)
#6 @ 8" O.C. (TYP)
3/16"x6" WATERSTOP AS REQUIRED
#6 HORIZONTAL DOWELS E.F @ 8" O.C. 90° STD. HOOK (TYP) SEE SHEET S-1
2' -
5"
1"
11"
# 3 BENT BAR @ 12" O.C. 10" LONG EPOXY DOWEL 3" EMBEDMENT INTO CONCRETE WALL/ FOOTING (TYP)
(2) # 5 CONT. TYP
CORNER CAST-IN-PLACE 4000 PSI MIN. EPOXY CONCRETE FILLET
1' - 0" 1" 8" 1" 1' - 0"
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-5.1
PUMP STATION DETAILS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
PUMP HOUSE
DETAIL
SCALE: 3/4" = 1'=0"
1
S-5.1DETAIL
SCALE: 3/4" = 1'=0"
2
S-5.1
DETAIL
SCALE: 3/4" = 1'=0"
3
S-5.1
DETAIL
SCALE: 3/4" = 1'=0"
4
S-5.1
DETAIL- EDGE BEAM
SCALE: 1-1/2" = 1'=0"
5
S-5.1
FILL-IN CONCRETE CURB DETAIL
SCALE: 1-1/2" = 1'=0"
6
S-5.1
DETAIL - TYPICAL CMU WALL & COLUMN CONNECTION (PLAN VIEW SECTION)
SCALE: 3/4" = 1'=0"
7
S-5.1
AS NOTED
12-01-17
LN
DEF
LN
172603
DETAIL
SCALE: 3/4" = 1'=0"
8
S-5.1
FOR BIDDING PURPOSES ONLY
1' -
4"
1' - 3"
16" THICK CONC. WALL AS PER PLAN
#6 - 90° BENT BARS @ 8" O.C. VERTICALLY (TYP.)
#6 HORIZ. BAR, CONT. @ 8" O.C. E.F. (TYP.)
#8 VERT. BAR, CONT. @ 6" O.C. E.F. (TYP.)
#5-90° STD. HOOK@ 12" O.C.
LAP
12" MIN.
CLA
SS "B
" TEN
SIO
N L
AP
SHO
WN
ON
DW
GS
DO
WEL
PR
OJE
CTI
ON
AS
6" x 1/4" STEEL WATERSTOP
ROUGHNED SURFACE 1/4" FULL AMPLITUDE
12" MIN.
1' -
3"
#5 x4'-0" LONG @ 12"O.C.
1' -
0"
T/3
T/3
T/3
T
6" x 3/16" STEEL WATERSTOP BONDTO INTERSECTING, WATERSTOP.TERMINATE WATER AND KEYWAY 8" BELOW TOP OF WALL CONTINUOUS REINF
OR LAP AS SHOWN
WHERE SHOWN1 5/8" KEYWAY
TENSION LAPCLASS "B"
3" CLEAR TYP.
INTIAL CAST
TENSION LAP TYP.
CLASS "B"AREA EQUAL TO 50% OF INTERRUPTED BARS EACH SIDE W/ MATCHINGDOWELS
INTERRUPTED BARS
AREA EQUAL TO 50% OF INTERRUPTED HORIZ. BARS
INTERUPTED BARS
TENSION LAP TYP.
CLASS "B"
TYP.+/- 12
"
AREA EQUAL TO 50% OF INTERRUPTED BARS EACH SIDE
INTERRUPTED BARS
2#4 AT 4"EF TYP
CONTRACTOR TO COORDINATE WITH LINK-SEAL MANUFACTURER FOR THE SLEVE/ CASING / WALL HOLE I.D.
NOTE:WHERE OPENING IS WITHIN 4'-0" OF BASE SLAB PROVIDEMATCHING DOWELS FOR ADD BARS
TENSION LAP TYP.
CLASS "B"
AREA EQUAL TO 50% OF INTERRUPTED BARS EACH SIDE
2#4 x 4'-0" AT 4"EF TYP
INTERRUPTED BARS
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-5.0
AS NOTED
12-01-17
LN
DEF
LN
PUMP STATION STANDARD DETAILS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
WALL CORNER REINFORCING
SCALE: 3/4" = 1'=0"
1
S-5
WALL INTERSECTION REINFORCING
SCALE: 3/4" = 1'=0"
2
S-5
WALL BASE CONC. JOINT
SCALE: 3/4" = 1'=0"
3
S-5
WALL CONTROL JOINT
SCALE: 1-1/2" = 1'=0"
4
S-5 WALL CONSTRUCTION JOINT SCALE: 1-1/2" = 1'=0"
5
S-5
SLIDE GATE FLUSH BOTTOM
SCALE: 1-1/2" = 1'=0"
6
S-5
REINFORCING AT CIRCULAR OPENINGS
SCALE: 1-1/2" = 1'=0"
7
S-5REINFORCING AT RECTANGULAR OPENINGS SCALE: 1-1/2" = 1'=0"
8
S-5
172603
FOR BIDDING PURPOSES ONLY
ALL WORK TO BE PERFORMED UNDER THIS CONTRACT SHALLCOMPLY WITH THE MOST RECENT EDITION OF THE FLORIDABUILDING CODE (2014), CITY LABOR LAWS, CITY ORDINANCES, CITY/COUNTY ZONING CODES, RULES AND REGULATIONS, ANDANY APPLICABLE CODES. THE CONTRACTOR SHALL BERESPONSIBLE FOR OBTAINING ALL REQ'D PERMITS TO CARRYOUT THE WORK DESCRIBED IN THE CONSTRUCTIONDOCUMENTS.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTIONWITH PROJECT SPECIFICATIONS, ARCHITECTURAL,MECHANICAL, ELECTRICAL, PLUMBING, CIVIL AND SITEDRAWINGS. CONSULT THESE DOCUMENTS FOR SLEEVES,DEPRESSIONS AND ANY OTHER DETAIL NOT SHOWN ON THESTRUCTURAL DOCUMENTS.
ALL DIMENSIONS AND CONDITIONS MUST BE VERIFY IN THEFIELD. ANY DISCREPANCIES SHALL BE BROUGHT TO THEATTENTION OF THE ENGINEER OF RECORD BEFOREPROCEEDING WITH THE AFFECTED PART OF THE WORK.CONTRACTOR(S) SHALL FAMILIARIZE HERSELF/ HIMSELFWITH ALL THE EXISTING CONDITIONS
AT THE SITE RELATIVE TO SCOPE OF WORK RELATING TOTHIS PROJECT, MATERIALS HANDLING, STORAGE ANDDELIVERY, WORKING SPACE AVAILABLE, SAFETYPRECAUTIONS REQUIRED, AND ALL OTHER CONDITIONSNECESSARY TO THE MAKING OF AN ACCURATE ANDCOMPLETE PROJECT BID, NO INCREASE IN PROJECT COSTWILL BE ALLOWED FOR FAILURE OF THE CONTRACTOR TOKNOW EXISTING SITE CONDITIONS.
THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING ANDSTABLE AFTER THE BUILDING IS COMPLETED. IT IS THECONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTIONPROCEDURES AND SEQUENCING TO ENSURE SAFETY OF THEBUILDING AND ITS COMPONENTS DURING ERECTION. THISINCLUDES THE ADDITION OF NECESSARY SHORING,SHEETING, TEMPORARY BRACING, GUYS OR TIEDOWNS.
DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS. ANYDIMENSIONS NOT INDICATED ON DRAWINGS SHALL BECONFIRMED WITH ENGINEER PRIOR TO CONSTRUCTION.
NO WORK SHALL BE PERFORMED OUTSIDE THE PROJECTLIMITS WITHOUT PRIOR WRITTEN APPROVAL FROM THEBUILDING OWNER AND OR ENGINEER.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATINGTHE WORK OF ALL TRADES AS REQUIRED FOR COMPLETIONOF WORK.
MATERIALS SHALL BE NEW, OF QUALITY SPECIFIED,DELIVERED IN A TIMELY FASHION AND AMPLE QUANTITY TOPREVENT DELAY OF WORK. SUBSTITUTIONS REQUIRE PRIORAPPROVAL FROM ENGINEER.
THERE ARE NO SUBSTITUTIONS ALLOWED UNLESSAPPROVED BY THE ENGINEER. THE G. C. SHALL SUBMIT INWRITING ALL REQUESTS FOR SUBSTITUTIONS.THE GENERAL CONTRACTOR SHALL SUBMIT IN WRITING TO THE ENGINEERPRIOR INSTALLATION, IF ANY UNFORESEEN CONDITIONS AFFECTING INSTALLATION ACCORDING TO
ALL PLAN DETAILS AND WALL SECTIONS ARE ASSUMED TO BETYPICAL CONDITIONS UNLESS DETAILED OR NOTEDOTHERWISE.
CODES AND STANDARDS
THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THEFOLLOWING CODES:
A FLORIDA BUILDING CODE / 2014 EDITION & SUPPLEMENT
B BUILDING CODE REQUIREMENTS FORREINFORCED CONCRETE (ACI 318-11).
C MANUAL OF STANDARD PRACTICE FOR DETAILINGREINFORCED CONCRETE STRUCTURES (ACI 315 /LATEST EDITION)
D MANUAL FOR STANDARD PRACTICE FOR WELDINGREINFORCED STEEL INSERTS & CONNECTIONS INREINFORCED CONCRETE CONSTRUCTION AWS. D1.4 /LATEST EDITION.
E SPECIFICATION FOR THE DESIGN. FABRICATION &ERECTION OF STRUCTURAL STEEL FOR BUILDINGS.(AMERICAN INSTITUTE OF STEEL CONSTRUCTION) ASICASD / 9TH EDITION.
ALL CHANGES AND ADDITIONS MADE ON RE-SUBMITTAL MUSTBE CLEARLY FLAGGED AND NOTED THE PURPOSE OF THERE-SUBMITTAL MUST BE CLEARLY NOTED ON THE LETTER OFTRANSMITTAL. ENGINEER REVIEW WILL BELIMITED TO THOSE ITEMS CAUSING THE RE-SUBMITTAL.
SHOP DRAWINGS REQUIRED ENGINEERING INPUT BYSPECIALTY ENGINEER
SUBMITTAL SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECTAND APPLICABLE CODES, LIST DESIGN CRITERIA, AND SHOWALL DETAILS AND PLANS NECESSARY FOR PROPERFABRICATION AND INSTALLATION CALCULATIONS AND SHOPDRAWINGS SHALL IDENTIFY SPECIFIC PRODUCT UTILIZED.GENERIC PRODUCT WILL NOT BE ACCEPTED.
SHOP DRAWING AND CALCULATIONS MUST BE PREPAREDUNDER THE DIRECT SUPERVISION AND CONTROL OF THESPECIALTY ENGINEER.
SHOP DRAWINGS AND CALCULATIONS REQUIRE THEIMPRESSED SEAL, DATE AND SIGNATURE OF THE SPECIALTYENGINEER. COMPUTER PRINTOUTS ARE AN ACCEPTABLESUBSTITUTE FOR MANUAL COMPUTATIONS PROVIDED THEYARE ACCOMPANIED BY SUFFICIENT DESCRIPTIVEINFORMATION TO PERMIT THEIR PROPER EVALUATION, SUCHDESCRIPTIVE INFORMATION SHALL BEAR THE IMPRESSEDSEAL AND SIGNATURE OF THE SPECIALTY ENGINEER AS ANINDICATION THAT HE/SHE HAS ACCEPTED RESPONSIBILITYFOR THE RESULT.
DRAWINGS PREPARED SOLELY TO SERVE AS A GUIDE FORFABRICATION AND INSTALLATION, (SUCH AS REINFORCINGSTEEL SHOP DRAWINGS OR STRUCTURAL STEEL ERECTIONDRAWINGS), AND REQUIRING NO ENGINEERING INPUT DONOT REQUIRE THE SEAL OF A SPECIALTY ENGINEER.
REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OFSUBMITTAL IS LIMITED TO VERIFY THE FOLLOWING:
THAT THE SPECIFIED STRUCTURAL SUBMITTALHAVE BEEN FURNISHED.
THAT THE STRUCTURAL SUBMITTAL HAVE BEENSIGNED AND SEALED BY THE SPECIALTY ENGINEER.
THAT THE SPECIALTY ENGINEER HASUNDERSTOOD THE DESIGN INTENT AS HAS USEDTHE SPECIFIED STRUCTURAL CRITERIA. (NO DETAILCHECK OF DIMENSIONS OR QUANTITIES WILL BEMADE.)
THAT THE CONFIGURATION SET FORTH IN THESTRUCTURAL SUBMITTAL IS CONSISTENT WITH THECONTRACT DOCUMENTS. (NO DETAIL CHECK OFDIMENSIONS OR QUANTITIES WILL BE MADE).
SUBMITTAL NOT MEETING THE ABOVE REFERENCEDCRITERIA WILL NOT BE REVIEWED
FORMWORK AND SHORING (CONCRETE SLABS AND BEAMS)
NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HASREACHED AT LEAST TWO THIRDS OF THE 28 DAY DESIGNSTRENGTH. A MINIMUM OF 3 STORIES OF SHORING AND (/OR)RE-SHORING SHALL BE USED WHICH SHALL CONSIST OF ONECOMPLETE SET OF VERTICAL SHORES AND TWO SETS OFVERTICALS SHORES THAT COMPROMISE AT LEAST 50% OF ACOMPLETE SET.DESIGN, ERECTION AND REMOVAL OF ALL FORMWORK,SHORES AND RE-SHORES SHALL MEET REQUIREMENTS SETFORTH IN ACI STANDARDS 347 AND 301.DRAWINGS FOR SHORING AND RE-SHORING SHALL BEPREPARED BY A FLORIDA REGISTERED PROFESSIONALENGINEER.
PLUMBING SLEEVES
MINIMUM SLEEVE SPACING SHALL BE THREE DIAMETERSCENTER TO CENTER OF LARGER SLEEVE OR 6" CLEARBETWEEN SLEEVES, WHICHEVER IS GREATER. PRIOR TOCONSTRUCTION, SLEEVE LOCATIONS AND SIZES SHALL BEAPPROVED BY THE ENGINEER OF RECORD.
REINFORCING STEEL
SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREEFROM OIL, SCALE AND RUST AND PLACED IN ACCORDANCEWITH THE TYPICAL BENDING DIAGRAM AND PLACING DETAILSOF ACI STANDARDS AND SPECIFICATIONS. SECUREAPPROVAL OF SHOP DRAWINGS PRIOR COMMENCING ANYFABRICATION.
F SPECIFICATION FOR STRUCTURAL CONCRETE FORBUILDINGS. ACI 301 / LATEST EDITION.
G BUILDING CODE REQUIREMENTS AND SPECIFICATIONSFOR MASONRY STRUCTURES (ACI 530-05 & ACI 530.1-05).
DESIGN CRITERIA
ALL WORK SHALL CONFORM WITH THE MINIMUM STANDARDSAS SPECIFIED IN THE FLORIDA BUILDING CODE LATESTEDITION AND ASCE 7-10.
LOAD COMBINATION AS PER ASCE 7-10
ASD1 D + (L OR LR)2 D + 0.75L + 0.75LR3 D + 0.6(WP OR WS)4 D + 0.75L + 0.75LR + 0.75(0.6WP OR 0.6WS)LRFD1 1.2D + 1.6L + 0.5LR2 1.2D + 1.6LR + 1.0L3 1.2D + 1.6 LR + 0.5(WP OR WS)4 1.2D + (WP OR WS) + L = 0.5LR5 0.9D + 1.0(WP OR WS)
MISC. STRUCTURAL STEEL 36,000 PSIREINFORCEMENT - STEEL 60,000 PSI
CONCRETEMINIMUM 28 STRENGTH 4,000 PSIEXCEPT AS FOLLOWS U.N.O.ROOF DECK 4,000 PSIBEAM 4,000 PSICOLUMN 4,000 PSIWALL 4,000 PSIFOUNDATION 4,000 PSI
SOIL BEARING AS PER GEOTECHNICAL REPORT DATED MARCH 2017. BY NUTTTING ENGINEERING
SPECIAL INSPECTION
THE OWNER SHALL EMPLOY A QUALIFIED SPECIALINSPECTOR TO PERFORM INSPECTIONS IN ACCORDANCEWITH THE "THRESHOLD INSPECTION GUIDELINES", ISSUEDSEPARATELY BY THE ENGINEER OF RECORD.THE SPECIAL INSPECTOR SHALL CERTIFY WITH HIS SEAL ANDSIGNATURE AT THE END OF CONSTRUCTION, THAT THECONSTRUCTION OF THIS STRUCTURE HAS BEEN COMPLETEDACCORDING TO THE PROJECT PLANS AND SPECIFICATIONS.
SPECIAL INSPECTIONS SHALL BE PERFORMED BY AREGISTERED PROFESSIONAL ENGINEER LICENSED TOPERFORM INSPECTIONS UNDER FLORIDA THRESHOLD LAWOR HIS QUALIFIED FULL TIME EMPLOYEE.
SHOP DRAWING REVIEW
SHOP DRAWINGS WILL BE REVIEWED FOR GENERALCOMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACTDOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THECONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACTDOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS,DIMENSIONS, ETC.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THECONTRACTOR PRIOR TO SUBMITTAL TO THEARCHITECT/ENGINEER. DRAWINGS SUBMITTED WITHOUTREVIEW WILL BE RETURNED UNCHECKED.
IN ALL INSTANCES THE CONTRACT DOCUMENTS WILLGOVERN OVER THE SHOP DRAWINGS UNLESS OTHERWISESPECIFIED IN WRITING BY THE ENGINEER OF RECORD.
REPRODUCTION OF STRUCTURAL DRAWINGS FOR USE ASSHOP DRAWINGS IS NOT PERMITTED.
WELDED WIRE FABRIC
TO CONFORM TO ASTM A-185, FREE FROM OIL, SCALE ANDRUST AND PLACE IN ACCORDANCE WITH THE TYPICALPLACING DETAILS OF ACI STANDARDS AND SPECIFICATIONS.MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES.
EMBEDDED ITEMS IN CONCRETE
EMBEDDED ITEMS INCLUDING BUT NOT LIMITED TO STEELPLATES FOR CONNECTIONS, WATER STOPS, DOVETAIL SLOTSFOR MASONRY ANCHORS, INSERTS FOR GLASS DOOR ANDRAILS, DOWNSPOUT PIPES IN COLUMNS SHALL BECOORDINATED BY THE CONTRACTOR IN A TIMELY MANNER.ALL EMBEDDED STEEL PLATES FOR THE CONNECTION OFWALL FRAMING, ROOF FRAMING AND MISCELLANEOUS STEELSHALL BE COORDINATED WITH WALL PANEL JOINTS ANDOPENINGS. SUBMIT SHOP DRAWINGS AND OBTAIN ENGINEERAPPROVAL PRIOR CONCRETE PLACEMENT.
CONCRETE
SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TOACHIEVE A STRENGTH AT 28 DAYS AS LISTED BELOW WITH APLASTIC AND WORKABLE MIX:4,000 PSI FOR COLUMN: WATER TO CEMENT RATIO BYWEIGHT SHALL NOT EXCEED 0.504,000 PSI FOR FOUNDATION AND SLABS ON GRADE; WATERTO CEMENT RATIO BY WEIGHT SHALL NOT EXCEED 0.60.
4,000 PSI FOR BEAM: WATER TO CEMENT RATIO BY WEIGHTSHALL NOT EXCEED 0.504,000 PSI FOR ALL STRUCTURAL CONCRETE; WATERTO CEMENT RATIO BY WEIGHT SHALL NOT EXCEED 0.50
CONCRETE SHALL BE PLACED AND CURED ACCORDING TOACI STANDARDS AND SPECIFICATIONS.
SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELDCYLINDERS OR LAB TEST FOR REVIEW PRIOR TO USE. MIXSHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR OTHERPOSITIVE IDENTIFICATION. MIX SHALL MEET THEREQUIREMENTS OF ASTM C33 FOR COARSE AGGREGATE.CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OFASTM STANDARDS C94 FOR MEASURING, MIXING,TRANSPORTING, ETC.
CONCRETE TICKETS SHALL BE TIME STAMPED WITHCONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROMTHE TIME THE MIXING WATER IS ADDED UNTIL IT ISDEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED ONAND ONE HALF, (1 1/2), HOURS. IF FOR ANY REASON THERE ISA LONGER DELAY THAN THAT STATED ABOVE, THECONCRETE3 SHALL BE DISCARDED, IT SHALL BE THERESPONSIBILITY OF THE TESTING LAB TO NOTIFY THEOWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANYNONCOMPLIANCE THE ABOVE.
ALL SLABS SHALL BE CURED USING A DISSIPATING CURINGCOMPOUND MEETING ASTM STANDARD C309 TYPE 1 ANDSHALL HAVE A FUGITIVE DYE. THE COMPOUND SHALL BEPLACED AS SOON AS THE FINISHING IS COMPLETED OR ASSOON AS THE WATER HAS LEFT THE UNFINISHED CONCRETEALL SCUFFED OR BROKEN AREAS IN THE CURING MEMBRANESHALL BE RECOATED DAILY.
ALL CONCRETE SHALL HAVE MID-RANGE WATER REDUCINGADMIXTURE CONFORMING TO ASTM C494 TYPE A.ADMIXTURES CONTAINING CHLORIDE IONS MORE THAN 0.05PERCENT BY WEIGHT IN THE ADMIXTURE SHALL NOT BEUSED. OTHERS ADMIXTURES SHALL BE APPROVED BY THEENGINEER OF RECORD. AIR-ENTRAINING ADMIXTURES SHALLNOT BE USED IN STRUCTURAL CONCRETE.
ALL CONCRETE MIX DESIGN DESIGNS SHALL INCLUDE AWRITTEN DESCRIPTION INDICATING WHERE EACHPARTICULAR MIX IS TO BE PLACED WITHIN THE STRUCTURE.
ALL CONCRETE DESIGN MIX SUBMITTAL SHALL INCLUDETESTED, STATISTICAL BACK-UP DATA AS PER CHAPTER 5 OFACI 318.
CONCRETE TESTING
AN INDEPENDENT TESTING LABORATORY SHALL PERFORMTHE FOLLOWING TEST ON CAST IN PLACE CONCRETE;ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OFPORTLAND CEMENT CONCRETE". MAXIMUM SLUMP SHALL BE4" INCHES. CONCRETE CONTAINING MID-RANGE WATERREDUCED SHALL HAVE A MAXIMUM SLUMP OF 7.5 INCHES.
ASTM C39 - " STANDARD TEST METHOD FOR COMPRESSIVESTRENGTH OF CYLINDRICAL CONCRETE SPECIMENS." ASEPARATE TEST SHALL BE CONDUCTED FOR EACH CLASS,FOR EVERY 50 CUBIC YARDS, OR FRACTION THEREOF,PLACED PER DAY. REQUIRED CYLINDERS QUANTITIES ANDTEST AGE AS FOLLOWS:
1 AT 7 DAYS 2 AT 28 DAYS
ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDERTHE DIRECTION OF THE ENGINEER, IF REQUIRED, IF 28 DAYSTRENGTH IS ACHEIVED, THE CYLINDER MAY BE DISCARDED.PENETRATION
NO PENETRATING SHALL BE MADE IN ANY STRUCTURALMEMBERS OTHER THAN THOSE LOCATED ON THESEDRAWINGS WITHOUT PREVIOUS APPROVAL OF THEENGINEER.
CHEMICAL ANCHORS.
SHALL BE TWO PART EPOXY POLYMER INJECTION SYSTEM,SUCH AS RAMSET 'EPCON", RAWL "FOIL-FAST" CARTRIDGESYSTEM, DUR-O-WALL, "DUR-O-PAIR" EPOXY ANCHOR, ORHILTI HSE2411 EPOXY DOWELING SYSTEM, OR APPROVEDEQUAL. INSTALL IN ACCORDANCE WITH MANUFACTURERSINSTRUCTIONS. INSTALLERS SHALL BE TRAINED BY THEMANUFACTURER'S REPRESENTATIVE.
WELDING
WELDING SHALL BE DONE BY A CERTIFIED WELDERS USINGASTM E70XX SERIES FOR SHOP WELDING A36 STEEL, ANDE70XX SERIES LOW HYDROGEN ELECTRODES FOR ALLWELDING OF HIGH STRENGTH STEELS AND FOR ALL FIELDWELDING.
WELDS SHOWN ON STRUCTURAL DRAWINGS ARE MINIMUMDESIGN REQUIREMENTS. THE FABRICATOR'S SHOP SHALLREFLECT WELDS IN ACCORDANCE WITH AWS REQUIREMENTS.
FULL PENETRATION GROOVE WELDS SHALL BE INSPECTED BYULTRASONIC TESTING. TWENTY-FIVE PERCENT OF THEWELDS SHALL BE INSPECTED AT RANDOM UNLESS NOTEDOTHERWISE, SEE SPECIFICATIONS FOR ADDITIONALREQUIREMENTS. IF NON- COMPLIANCE IS FOUND, ADDITIONALTEST MAY BE ORDERED BY THE ENGINEER AT THE EXPENSEOF THE CONTRACTOR.
WHEN WELDS ARE NOT CALLED OUT ON DRAWINGS, THEYARE MINIMUM SIZE CONTINUOUS FILLET WELDS INACCORDANCE WITH AWS D1.1. FILLET WELDS NOT SPECIFIEDAS TO LENGTH SHALL BE CONTINUOUS.
UNLESS NOTED OTHERWISE ON THE DRAWINGS ALL GROOVEWELDS SHALL BE FULL PENETRATION.PROVIDE FILLET WELDS AT ALL CONTACT JOINT BETWEENSTEEL MEMBERS SUFFICIENT TO DEVELOP THE ALLOWABLETENSILE STRENGTH OF THE SMALLER MEMBER AT THE JOINT UNLESS DETAILED OTHERWISE.
GENERAL NOTES
SPECIFICATIONS.
Q= REFER TO SOIL REPORT FOR SOIL BEARING CAPACITYSOIL UNIT WEIGHT= 115 PCFFRICTION ANGLE= 30°
LOADING PUMP STATION ROOF
LIVE LOAD= 30 PSFSUPER IMPOSE= +25 PSFTOTAL 55 PSF
FLOOR SLAB:LIVE LOAD= 150 PSFSUPER IMPOSE= +25 PSFDEAD LOAD= +25PSFTOTAL 200 PSF
WIND LOAD:WIND SPEED= 180 MPHEXPOSURE= DCATEGORY= III
DEWATERING AS PER GEOTECHNICAL REPORT
DEWATERING
PROVIDE REQUIRED DEWATERING DURING ENTIRE PERIOD OF FOUNDATION SLAB AND PUMP STATION STRUCTURE CONSTRUCTION; PIPE INSTALLATION AND TEMPORARY SHEET PILING ACROSS THE CANAL AS PER LOCAL GOVERNING AUTHORITY REQUIREMENTS.
PROVIDE PROPOSE METHOD OF CONSTRUCTION WITH TEMPORARY SHORING FOR E.O.R. REVIEW AND APPROVAL PRIOR TO PROCEEDING WITH ANYWORK.
WIND LOAD:WIND SPEED= 180 MPHEXPOSURE= DCATEGORY= III
MASONRY NOTES:
AS REQ'D. MINIMUM LOAD CARRYING CAPACITY 1500 LB/FT NOT TO EXCEED 6'-0" WIDE OPENING.
ACI 531, LATEST EDITION.
12. ALL CONSTRUCTION SHALL BE DONE IN ACCORDANCE WITH THE "BUILDING CODE REQUIREMENTS FOR CONCRETE MASONRY STRUCTURES",
11. PRECAST CONCRETE LINTELS SHALL BE PROVIDED IN ALL MASONRY OPENINGS
9. ALL MASONRY SHALL BE LAID UP IN RUNNING BOND, UNLESS STIPULATED
10. PROVIDE 8" OF BEARING EACH END FOR BLOCK LINTELS, TYPICAL UNLESS
OF CORES TO BE FILLED (UNLESS NOTED OTHERWISE).
NOTED OTHERWISE. FILL BLOCK CORES SOLID FOR 2 COURSES BELOW BEARING, UNLESS OTHERWISE NOTED. NOTE DOOR DIM. ARE NOMINAL.
OTHERWISE BY THE ENGINEER.
B. PLACE GROUT IN MAXIMUM 8'-0" LIFTS AND CONSOLIDATE. ALLOW GROUT TO SET FOR MINIMUM OF 24-HOURS BETWEEN EACH SUCCEEDING 8'-0" LIFT. PROVIDE CLEANOUTS AT BOTTOM
SUCCEEDING 4'-0" LIFT (UNLESS NOTED OTHERWISE).
8. GROUTING OF WALLS SHALL BE ACCOMPLISHED BY ONE OF THE FOLLOWING METHODS:
A. PLACE GROUT IN MAXIMUM 4'-0" LIFTS AND CONSOLIDATE. ALLOW GROUT TO SET FOR MINIMUM OF 15 MINUTES BETWEEN EACH
7. GROUT FOR BOND BEAMS, PILASTERS, AND CORE FILL SHALL HAVE A
WITH ASTM C-476 AND A MAXIMUM SIZE OF AGGREGATE OF 3/8".
REINFORCING BARS SHALL BE ACCURATELY POSITIONED ACCORDING TO THE DRAWINGS AND SHALL BE SECURED TO PREVENT DISPLACEMENT DURING GROUTING.
MINIMUM f'c = 3000 PSI @ 28 DAYS AND SHALL BE IN ACCORDANCE
CALCIUM CHLORIDE SHALL NOT BE USED IN GROUT.
PLANS FOR VARIATIONS.
6. CONTACT LAP SPLICES FOR VERTICAL REINFORCING (UNLESS NOTED OTHER-WISE:
SPLICES. PROVIDE SPECIAL PREFABRICATED TEES AND CORNER UNITS AT INTERSECTING WALLS FOR WALLS LAID UP IN STACK BOND. SEE
COMPRESSION SPLICES: 30 DIAMETERS TENSION SPLICES: 48" DIAMETER FOR 3, & #4;30" FOR #5; 36" FOR #6; 45" FOR #7
5. PROVIDE MASONRY HORIZONTAL REINFORCING AT 16" O.C.
HAVE "LADDER" TYPE REINFORCING. PROVIDE A MINIMUM 6" LAP AT
THE FACE OF THE UNIT OR WALL, NOT LESS THAT THE THICKNESS OF THE LONGITUDINAL FACE SHELLS. MORTAR JOINTS SHALL BE MAIN- TAINED AT 3/8" THICKNESS FOR BOTH THE HORIZONTAL AND VERTICAL
HAVE "TRUSS" TYPE REINFORCING AT 16" O.C. EXCEPT THE TOP 3 COURSES SHALL BE 8" O.C. WALLS LAID UP IN RUNNING BOND MAY
IN ALL MASONRY WALLS. WALLS LAID UP IN STACK BOND SHALL
JOINTS, UNLESS NOTED OTHERWISE.
BE USED IN MORTAR.
3. MORTAR: THE MORTAR USED FOR MASONRY CONSTRUCTION SHALL BE
4. CONSTRUCTION: THE FIRST COURSE OF ALL HOLLOW MASONRY SHALL
SHALL BE FILLED SOLIDLY WITH MORTAR FOR A DISTANCE IN FROM
TYPE "M" BELOW GRADE AND TYPE "S" ABOVE GRADE AND SHALL CONFORM TO ALL THE REQUIREMENTS OF THE APPLICABLE BUILDING CODE, LATEST EDITION. CALCIUM CHLORIDE SHALL NOT
BE LAID IN A FULL BED OF MORTAR. ALL UNITS SHALL BE LAID WITH FULL FACE SHELL MORTAR BEDS. ALL HEAD AND END JOINTS
1. USE CODE FOR MASONRY ACI 530-93 AND CONSTRUCTION NATIONAL
2. CONCRETE MASONRY UNITS: THE QUALITY STANDARDS FOR THE UNITS SHALL CONFORM TO THE AMERICAN STANDARD SPECIFICATIONS FOR HOLLOW LOAD BEARING MASONRY UNITS (ASTM C90-70). MINIMUM f'm SHALL BE 1500 PSI BASED ON THE SHELL FACE MORTAR BEDDING.
CONCRETE MASONRY ASSOCIATION.
13. 9 GAUGE GALVANIZED DUROWALL HORIZONTAL REINFORCEMENT @ EVERY OTHER COURSE EXTEND 3" INTO TIE COLUMN
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-6
AS NOTED
12-01-17
LN
DEF
LN
PUMP STATION NOTES
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
172603
FOR BIDDING PURPOSES ONLY
DESIGN WIND PRESSURE PSF (ULTIMATE)
ZONE POSITIVE NEGATIVE
1 60 - 64.6
2 60 - 91.2
3 60 - 118
3 2 3
2 1 2
3 2 3
a = 3 ft (TYP)
WIND PRESSURE PSF (ULTIMATE)
POSITIVE
DOOR 61.9 67.3
POSITIVE
WINDOW 61.9 66.7
2S.10
14'-0" x 36'-0" x 2'-6" , CONCRETE SLABON 3'-0" DEEP TREMIE CONCRETE BED
MAT
FO
OTI
NG
ED
GE
MAT
FO
OTI
NG
ED
GE
MAT FOOTING EDGE
MAT FOOTING EDGE
1S.10
12" CONRETE WALL W/ #6 @ 8" O.C. E.W. AND E.F.(TYP.)
EL. 0'-0" TOP OF SLAB
4S.10
F-1
F-1
F-1
4' - 0" DIAMETER 2' - 0" 4' - 0" 4' - 0" DIAMETER6' - 0" 2' - 0"
1' - 0" 36' - 0" 1' - 0"
7"12
' - 2
"1'
- 0"
120.00°
BATTERED PILE12" x 12" (TYP)
10' - 0"
DIAMETER WALL OPENINGSEE ELEVATION
3' - 0" 3' - 0"4' - 0" DIAMETER 2' - 0"
8" THICKPRECAST CONCRETE WALL PANEL (TYP)
KING PILE12" x 12" (TYP)
BATTERED PILE12" x 12" (TYP)
KING PILE12" x 12" (TYP)
W1
W3
W6
W4
#6-90° STD. HOOKED REBARS@ 8" E.W., T&B
KING PILE12" x 12" (TYP)
BATTERED PILE12" x 12" (TYP)
2' -
0"7'
- 0"
2' -
0"7'
- 0"
2' -
6"
3' -
2"
6' - 1"
2' -
6"7'
- 6"
2' -
0"7'
- 6"
2' -
0"
1' -
0"
1' -
0"
12' -
0"
9' -
6"9' -
0"11
' - 6
"
1 2 3
14' - 1" 7' - 10"
4
14' - 1"
A
B
1' -
7"
4' - 1"5' - 9"
W5W2
10S-11
5/8" DIAMETER S.S. EYE BOLT 5" EMB. W/ EPOXY.
5/8" DIAMETER S.S. EYE BOLT 5" EMB. W/ EPOXY.
NEW PIPE VERIFY W/ CIVIL PLAN FOR LOCATION AND ELEVATION
10' -
2"
6" 6"
1' - 8"
1' - 8"
6' - 8"4' - 8
"
13' - 0" 13' - 0"
MAT FOOTING EDGE
WALL OPENING. SEE ELEVATION
2' - 0"
6'-0" x 9" CONCRETE SLAB OPENING TO HOUSE SLIDE GATE
FOOTING
FOOTING
FOOTING
FOOTING
FOO
TIN
G
FOO
TIN
G
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
FOUNDATION PLAN (EL 0'-0")
SCALE: 1/2" = 1'=0"
1
S-70' 1' 2'
S-7
AS NOTED
12-01-17
LN
DEF
LN
CONTROL STATIONFOUNDATION & SEA WALL LAYOUT PLAN
HALLANDALEPUMP STATION AND CONTROL STRUCTURE-
CONTROL STRUCTURE
172603
FOR BIDDING PURPOSES ONLY
1
1
2
2
3
3
4
4
AA
B B
2S.10
1S.10
4S.10
14' - 0" 7' - 10" 14' - 2"
B-1B-2B-2
L-1: 6" x 4" x 1/4" CONT. STAINLESS STEEL ANGLE W/ 3/8" DIA. ANCHOR INTO CONCRETE WALL @ 24" O.C.
L-2: 6" x 4" x 1/4" CONT. STAINLESS STEEL ANGLE W/ 1/2" DIA. ANCHOR BOLT EPOXY INTO CONCRETE WALL @ 24" O.C.
ALUMINUM GRATING / ANGLE BRACKET SUPPORT AND CONNECTIONS
BY SPECIALTY ENGINEER. SUBMIT SIGNED AND SEALED SHOP DRAWING AND
CALCULATION TO E.O.R. FOR APROVAL PRIOR TO CONSTRUCTION (TYP)
12" CONCRETEWALL (TYP)
B-1
#6 @ 8" O/CE.W./ E.F.(TYP.)
L-2
L-2
9
S.11
L-2 L-1L-1
L-1 L-2 L-1
4
S.11
6' - 10" 6' - 10"
BEAM SCHEDULES
Nº TYPE TOP EL SIZE REINF.
B-1 CONCRETE 12" x 18"
B-2 ALUMINUM W 10 x 22 N.A.
SEE DETAIL9'-6"
9'-6"
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
UPPER LEVEL PLAN (EL. 12'-0")
SCALE: 1/2" = 1'=0"
1
S-80' 1' 2'
S-8
AS NOTED
12-01-17
LN
DEF
LN
CONTROL STATION UPPER LEVEL PLAN
HALLANDALE PUMP STATION AND CONTROL STRUCTURE -
CONTROL STRUCTURE
172603
FOR BIDDING PURPOSES ONLY
FOUNDATION0' - 0"
1234
F.F.ELV.11' - 4"
2' -
6"2' - 0" 2' - 0"4' - 0" 4' - 0"6' - 0"3' - 0"
7S.11
2#4 ADDITIONAL REBAR AROUND THE OPENING SEE DETAIL 8/S-11#3 U BAR STIRRUPS AT 8"
O.C. BETWEEN VERTICAL BAR
#6 @ 8" O.C. E.W. E.F.
2#4 ADDITIONAL REBAR AROUND THE OPENING SEE DETAIL 7/S-11 (TYP)
TYP.
4' - 0" 2' - 0" 4' - 0" 2' - 0"
7' -
6"
3' - 0"
1' - 0" 1' - 0"
SEE CIVIL DWGS FOR ELEVATIONS
36' - 0"
SEE CIVIL PLANS
SLIDE GATE HOUSING. SEE SECTION DETAIL 4/S-10
FOUNDATION0' - 0"
1 2 3 4
F.F.ELV.11' - 4"
38' - 0"
#6 ADDITIONAL REBAR AROUND THE OPENING SEE DETAIL 8/S-11
#3 U BAR STIRRUPS AT 8" O.C. BETWEEN VERTICAL BAR
1' - 0"1' - 0"
36' - 0"
13' - 0"10' - 0"13' - 0"
SEE CIVIL PLAN
FOUNDATION0' - 0"
AB
F.F.ELV.11' - 4"
2' -
6"
#6 @ 8" O.C. E.W. E.F.
12' - 0"
1' - 0"7"
SEE CIVIL PLANS
FOUNDATION0' - 0"
A B
F.F.ELV.11' - 4"
7"1' - 0"
#8 @ 0' - 8" (E)#5 @ 0' - 8" (E)#8 @ 0' - 8" (I)#5 @ 0' - 8" (I)
#6 @ 8" O.C. E.W. E.F.
12' - 0"
SEE CIVIL PLANS
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-9
AS NOTED
12-01-17
LN
DEF
LN
SOUTH ELEVATION WALL
SCALE: 3/8" = 1'=0"
1
S-9
NORTH ELEVATION WALL
SCALE: 3/8" = 1'=0"
3
S-9
CONTROL STATION ELEVATIONS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE -
CONTROL STRUCTURE
WEST ELEVATION WALL
SCALE: 3/8" = 1'=0"
2
S-9
EAST ELEVATION WALL SCALE: 3/8" = 1'=0"
4
S-9
172603
14'-0" x 38'-0" x 2'-6"CONCRETE SLABPER PLAN
10'-0" DIA. WALL OPENINGPER CIVIL PLAN #6 @ 8" O/C
E.W. E.F.12" THICKCONCRETE WALL
2 #4 EACH SIDESEE DETAIL 7/S-11(TYP)
SEE CIVIL DWGS FOR ELEVATIONS
FOR BIDDING PURPOSES ONLY
1 2 3 4
12" CONCRETE WALL
#6 VERTICAL BAR 3'-0" LONG
18" DEEP CONCRETE PAD W/ #6 90 DEG. HOOK BARS8" O.C. E.W. AND T.B.
12" CONCRETE WALL
#6 VERITCAL BAR @ 8" O.C. E.F. / E.W. (TYP)
#6 90 DEG. HOOK BAR @ 3'-0" LONG LAP @8"O.C.
30" DEEP CONCRETE PAD W/ #6 @ 8"O.C. E.W. AND T.B.
14' - 2"7' - 10"14' - 0"
36' - 0"
34' - 0"
S.103
S.105
S.105
Sim
S.106
S.107
14' - 2"7' - 10"6' - 10"7' - 2"
B-2 B-1 B-1 B-2
A B
12" CONCRETE WALL (SOUTH WALL) W/ #6 @ 8" O.C., E.W. & E.F.
30" DEEP CONCRETE PAD W/ #6-90° STD. HOOKED BARS@ 8" O.C., E.W., T&B
ALUMINUM HAND RAILTO COMPLY WITH FLORIDA BUILDING CODE PROVIDE SIGN AND SEAL CALCULATIONS AND SHOP DRAWINGS FOR E.O.R. REVIEW AND APPROVAL (TYP.)
3/8" ALUMINUM GRATING SEE DETAILS
12' - 0"
1' - 0" 7"
2' -
6"
#6 VERT. BAR @ 8" O.C., E.F.
#6 HOR. BAR @ 8" O.C., E.F.
12' - 2"
#6 - 90º HOOKED DOWEL @ 8" O.C., E.F.
12" CONCRETE WALL (NORTH WALL)
VERT. #6 @ 8" O.C., E.F.
HOR. #6 @ 8" O.C., E.F.
3" C
OVE
R (T
YP)
LAP
36" M
IN. (
TYP)
3S.10
SIMILAR
1' - 0"
#6 VERT BARS @ 8" O.C., E.F.
#5 HOR. BARS @ 8" O.C., E.F.
#6 BENT BAR @ 8" O.C., E.F. 36" LAP
12" CONC. WALL
#6 - 90º HOOKED BAR@ 8" O.C., T&B
1' - 0"
A B
11' -
4"
1' - 0"
ALUMINUM HAND RAILTO COMPLY WITH FLORIDA BUILDING CODE PROVIDE SIGN AND SEAL CALCULATIONS AND SHOP DRAWINGS FOR E.O.R. REVIEW (TYP)
2' -
6"
ADDITIONAL(3)#6 HOR. BARSAROUND OPENING
B-1 B-3
2 1/2" ALUMINUM GRATING
6S.10
TYP.
1' - 0" 9"
SLIDE GATE HOUSING. COORDINATE WITH SPECIALTY CONTRACTOR
8#6 W/ # 3 REBAR STIRRUPS @ 12" O.C.
30" DEEP CONCRETE PAD W/ #6-90° STD. HOOKED BARS 8" O.C., E.W., T&B
12"x18" CONCRETE BEAM W/ 10#5 AS SHOWN W/ #3 TIES @ 8" O.C.
1' - 6"
1' -
0"
CO
OR
DIN
ATE
W/ M
ANU
FAC
TUR
ER
2 1/2" x 3/16 ALUMINUM GRATING
L-2 ANGLE (SEE SCHEDULES)
WITH 5/8" ANCHOR BOLTS STAGGERED EPOXY
INTOCONCRETE WALL
12" CONC. WALL
1" CHAMFER
2 1/2" x 3/8" ALUMINUM GRATING(REFER TO MANUFACTURER)
ALUMINUM W BEAM. SEE BEAM SCHEDULE ON SHEET S-8
CONNECTIONAS PER MANUFACTURERSPECIFICATION
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-10
AS NOTED
12-01-17
LN
DEF
LN
SECTION
SCALE: 3/8" = 1'=0"
1
S-10
SECTION (TYPICAL) SCALE: 3/8" = 1'=0"
2
S-10DETAILSCALE: 3/4" = 1'=0"
3
S-10
SECTION W/ OPENINGS SCALE: 3/8" = 1'=0"
4
S-10
TYPICAL
SCALE: 1-1/2" = 1'=0"
5
S-10
TYPICAL SCALE: 1-1/2" = 1'=0"
6
S-10
CONTROL STATION SECTIONS AND DETAILS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
CONTROL STRUCTURE
TYPICAL
SCALE: 1-1/2" = 1'=0"
7
S-10
172603
2 1/2 x 2 1/2 x 1/8 S. S. ANGLE W/ T, /2" DIA x 4" LONG.S.S. STUDS AT 2' -0" O/C
2 1/2" x 3/16 ALUMINUM GRATING
FOR BIDDING PURPOSES ONLY
LAP
12" MIN.
CLA
SS "B
" TEN
SIO
N L
AP
LAP
12" MIN.
CLA
SS "B
" TEN
SIO
N L
AP
SHO
WN
ON
DW
GS
DO
WEL
PR
OJE
CTI
ON
AS
6" x 1/4" STEEL WATERSTOP
ROUGHNED SURFACE 1/4" FULL AMPLITUDE
12" MIN.
T/3
T/3
T/3
T
6" x 3/16" STEEL WATERSTOP BONDTO INTERSECTING, WATERSTOP.TERMINATE WATER AND KEYWAY 8" BELOW TOP OF WALL CONTINUOUS REINF
OR LAP AS SHOWN
WHERE SHOWN1 5/8" KEYWAY
TENSION LAPCLASS "B"
3" CLEAR TYP.
INTIAL CAST
TENSION LAP TYP.
CLASS "B"AREA EQUAL TO 50% OF INTERRUPTED BARS EACH SIDE W/ MATCHINGDOWELS
INTERRUPTED BARS
AREA EQUAL TO 50% OF INTERRUPTED HORIZ. BARS
INTERUPTED BARS
NOTE:WHERE OPENING IS WITHIN 4'-0" OF BASE SLAB PROVIDEMATCHING DOWELS FOR ADD BARS
TENSION LAP TYP.
CLASS "B"
TYP.+/- 12
"
AREA EQUAL TO 50% OF INTERRUPTED BARS EACH SIDE
INTERRUPTED BARS
2#4 AT 4"EF TYP
2 #4 EACH SIDE
NOTE:WHERE OPENING IS WITHIN 4'-0" OF BASE SLAB PROVIDEMATCHING DOWELS FOR ADD BARS
TENSION LAP TYP.
CLASS "B"
AREA EQUAL TO 50% OF INTERRUPTED BARS EACH SIDE
2#4 x 4'-0" AT 4"EF TYP
INTERRUPTED BARS
2#4 ADDITIONAL BAR AROUND THE OPENING
1' - 0"
2-1/2" ALUMINUM GRATING AS PER PLAN
ALUMINUM I-BEAM AS PER DETAIL 1/S-8
6"x4"x1/4" CONT. STAINLESS STEEL ANGLE W/ 3/8" DIA. ANCHOR INTO CONCRETE WALL @ 24" O.C.
1/2" THICK STIFFENER PLATE FULLY WELDED TO SUPPORT ANGLE
(4)-5/8"∅ EPOXY S.S. BOLTS INTO CONCRETE WALL
12" CONCRETE WALLAS PER PLAN
PROVIDE 1/4" THICK NEOPRENE PAD BETWEEN CONCRETE & STEEL ANGLE
1" CHAMGER
#5 @ 8" O.C
CONCRETE BEAM AS PER PLAN (12 x 18)
6"
1' - 0"
1' -
0"
6"
1' -
0"
12" REINFORCED CONCRETE WALL
2'-6"8" 10" 1'-4"
16" CONCRETE CAP
1'-4
"
(4) #6 x CONT., TOP
#4 @ 10" O.C.
#6 x CONT. MID.
#4 @ 10" O.C.
(4) #6 x CONT., BOTTOM
12" BATTER PILE SEE SHEET S-7 FOR SPACING 12" KING PILE SEE SHEET S-7 FOR SPACING
8" THICK PRECAST SEAWALL W/ #5 @8" O.C. EA. WAY
EL. SEE CIVIL PLANS
3'-0
" MIN
.
EL. V.I.F.WATER LINE
T.O. CAP
EL. -6.49' SEE CIVIL DRAWINGTOP OF CONCRETE MAT
12
2.5
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-11
AS NOTED
12-01-17
LN
DEF
LN
CONTROL STATION STANDARD DETAILS
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
CONTROL STRUCTURE
WALL CORNER REINFORCING SCALE: 3/4" = 1'=0"
1
S-11
WALL INTERSECTION REINFORCING SCALE: 3/4" = 1'=0"
2
S-11
WALL BASE CONC. JOINT SCALE: 3/4" = 1'=0"
3
S-11
BEAM TO WALL CONNECTION
SCALE: 1-1/2" = 1'=0"
4
S-11
WALL CONSTRUCTION JOINT
SCALE: 3/4" = 1'=0"
5
S-11
SLIDE GATE FLUSH BOTTOM SCALE: 1 1/2" = 1'=0"
6
S-11
REINFORCING AT CIRCULAR OPENINGS SCALE: 1 1/2" = 1'=0"
7
S-11 REINFORCING AT RECTANGULAR OPENINGS SCALE: 1 1/2" = 1'=0"
8
S-11
172603
BEAM TO WALL CONNECTION
SCALE: NTS
9
S-11
SEAWALL SECTION DETAILSCALE: NTS
10
S-11
FOR BIDDING PURPOSES ONLY
ALL WORK TO BE PERFORMED UNDER THIS CONTRACT SHALLCOMPLY WITH THE MOST RECENT EDITION OF THE FLORIDABUILDING CODE (2014), CITY LABOR LAWS, CITY ORDINANCES, CITY/COUNTY ZONING CODES, RULES AND REGULATIONS, ANDANY APPLICABLE CODES. THE CONTRACTOR SHALL BERESPONSIBLE FOR OBTAINING ALL REQ'D PERMITS TO CARRYOUT THE WORK DESCRIBED IN THE CONSTRUCTIONDOCUMENTS.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTIONWITH PROJECT SPECIFICATIONS, ARCHITECTURAL,MECHANICAL, ELECTRICAL, PLUMBING, CIVIL AND SITEDRAWINGS. CONSULT THESE DOCUMENTS FOR SLEEVES,DEPRESSIONS AND ANY OTHER DETAIL NOT SHOWN ON THESTRUCTURAL DOCUMENTS.
ALL DIMENSIONS AND CONDITIONS MUST BE VERIFY IN THEFIELD. ANY DISCREPANCIES SHALL BE BROUGHT TO THEATTENTION OF THE ENGINEER OF RECORD BEFOREPROCEEDING WITH THE AFFECTED PART OF THE WORK.CONTRACTOR(S) SHALL FAMILIARIZE HERSELF/ HIMSELFWITH ALL THE EXISTING CONDITIONS
AT THE SITE RELATIVE TO SCOPE OF WORK RELATING TOTHIS PROJECT, MATERIALS HANDLING, STORAGE ANDDELIVERY, WORKING SPACE AVAILABLE, SAFETYPRECAUTIONS REQUIRED, AND ALL OTHER CONDITIONSNECESSARY TO THE MAKING OF AN ACCURATE ANDCOMPLETE PROJECT BID, NO INCREASE IN PROJECT COSTWILL BE ALLOWED FOR FAILURE OF THE CONTRACTOR TOKNOW EXISTING SITE CONDITIONS.
THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING ANDSTABLE AFTER THE BUILDING IS COMPLETED. IT IS THECONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTIONPROCEDURES AND SEQUENCING TO ENSURE SAFETY OF THEBUILDING AND ITS COMPONENTS DURING ERECTION. THISINCLUDES THE ADDITION OF NECESSARY SHORING,SHEETING, TEMPORARY BRACING, GUYS OR TIEDOWNS.
DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS. ANYDIMENSIONS NOT INDICATED ON DRAWINGS SHALL BECONFIRMED WITH ENGINEER PRIOR TO CONSTRUCTION.
NO WORK SHALL BE PERFORMED OUTSIDE THE PROJECTLIMITS WITHOUT PRIOR WRITTEN APPROVAL FROM THEBUILDING OWNER AND OR ENGINEER.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATINGTHE WORK OF ALL TRADES AS REQUIRED FOR COMPLETIONOF WORK.
MATERIALS SHALL BE NEW, OF QUALITY SPECIFIED,DELIVERED IN A TIMELY FASHION AND AMPLE QUANTITY TOPREVENT DELAY OF WORK. SUBSTITUTIONS REQUIRE PRIORAPPROVAL FROM ENGINEER.
THERE ARE NO SUBSTITUTIONS ALLOWED UNLESSAPPROVED BY THE ENGINEER. THE G. C. SHALL SUBMIT INWRITING ALL REQUESTS FOR SUBSTITUTIONS.THE GENERAL CONTRACTOR SHALL SUBMIT IN WRITING TO THE ENGINEERPRIOR INSTALLATION, IF ANY UNFORESEEN CONDITIONS AFFECTING INSTALLATION ACCORDING TO
ALL PLAN DETAILS AND WALL SECTIONS ARE ASSUMED TO BETYPICAL CONDITIONS UNLESS DETAILED OR NOTEDOTHERWISE.
CODES AND STANDARDS
THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THEFOLLOWING CODES:
A FLORIDA BUILDING CODE / 2014 EDITION & SUPPLEMENT
B BUILDING CODE REQUIREMENTS FORREINFORCED CONCRETE (ACI 318-11).
C MANUAL OF STANDARD PRACTICE FOR DETAILINGREINFORCED CONCRETE STRUCTURES (ACI 315 /LATEST EDITION)
D MANUAL FOR STANDARD PRACTICE FOR WELDINGREINFORCED STEEL INSERTS & CONNECTIONS INREINFORCED CONCRETE CONSTRUCTION AWS. D1.4 /LATEST EDITION.
E SPECIFICATION FOR THE DESIGN. FABRICATION &ERECTION OF STRUCTURAL STEEL FOR BUILDINGS.(AMERICAN INSTITUTE OF STEEL CONSTRUCTION) ASICASD / 9TH EDITION.
ALL CHANGES AND ADDITIONS MADE ON RE-SUBMITTAL MUSTBE CLEARLY FLAGGED AND NOTED THE PURPOSE OF THERE-SUBMITTAL MUST BE CLEARLY NOTED ON THE LETTER OFTRANSMITTAL. ENGINEER REVIEW WILL BELIMITED TO THOSE ITEMS CAUSING THE RE-SUBMITTAL.
SHOP DRAWINGS REQUIRED ENGINEERING INPUT BYSPECIALTY ENGINEER
SUBMITTAL SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECTAND APPLICABLE CODES, LIST DESIGN CRITERIA, AND SHOWALL DETAILS AND PLANS NECESSARY FOR PROPERFABRICATION AND INSTALLATION CALCULATIONS AND SHOPDRAWINGS SHALL IDENTIFY SPECIFIC PRODUCT UTILIZED.GENERIC PRODUCT WILL NOT BE ACCEPTED.
SHOP DRAWING AND CALCULATIONS MUST BE PREPAREDUNDER THE DIRECT SUPERVISION AND CONTROL OF THESPECIALTY ENGINEER.
SHOP DRAWINGS AND CALCULATIONS REQUIRE THEIMPRESSED SEAL, DATE AND SIGNATURE OF THE SPECIALTYENGINEER. COMPUTER PRINTOUTS ARE AN ACCEPTABLESUBSTITUTE FOR MANUAL COMPUTATIONS PROVIDED THEYARE ACCOMPANIED BY SUFFICIENT DESCRIPTIVEINFORMATION TO PERMIT THEIR PROPER EVALUATION, SUCHDESCRIPTIVE INFORMATION SHALL BEAR THE IMPRESSEDSEAL AND SIGNATURE OF THE SPECIALTY ENGINEER AS ANINDICATION THAT HE/SHE HAS ACCEPTED RESPONSIBILITYFOR THE RESULT.
DRAWINGS PREPARED SOLELY TO SERVE AS A GUIDE FORFABRICATION AND INSTALLATION, (SUCH AS REINFORCINGSTEEL SHOP DRAWINGS OR STRUCTURAL STEEL ERECTIONDRAWINGS), AND REQUIRING NO ENGINEERING INPUT DONOT REQUIRE THE SEAL OF A SPECIALTY ENGINEER.
REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OFSUBMITTAL IS LIMITED TO VERIFY THE FOLLOWING:
THAT THE SPECIFIED STRUCTURAL SUBMITTALHAVE BEEN FURNISHED.
THAT THE STRUCTURAL SUBMITTAL HAVE BEENSIGNED AND SEALED BY THE SPECIALTY ENGINEER.
THAT THE SPECIALTY ENGINEER HASUNDERSTOOD THE DESIGN INTENT AS HAS USEDTHE SPECIFIED STRUCTURAL CRITERIA. (NO DETAILCHECK OF DIMENSIONS OR QUANTITIES WILL BEMADE.)
THAT THE CONFIGURATION SET FORTH IN THESTRUCTURAL SUBMITTAL IS CONSISTENT WITH THECONTRACT DOCUMENTS. (NO DETAIL CHECK OFDIMENSIONS OR QUANTITIES WILL BE MADE).
SUBMITTAL NOT MEETING THE ABOVE REFERENCEDCRITERIA WILL NOT BE REVIEWED
FORMWORK AND SHORING (CONCRETE SLABS AND BEAMS)
NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HASREACHED AT LEAST TWO THIRDS OF THE 28 DAY DESIGNSTRENGTH. A MINIMUM OF 3 STORIES OF SHORING AND (/OR)RE-SHORING SHALL BE USED WHICH SHALL CONSIST OF ONECOMPLETE SET OF VERTICAL SHORES AND TWO SETS OFVERTICALS SHORES THAT COMPROMISE AT LEAST 50% OF ACOMPLETE SET.DESIGN, ERECTION AND REMOVAL OF ALL FORMWORK,SHORES AND RE-SHORES SHALL MEET REQUIREMENTS SETFORTH IN ACI STANDARDS 347 AND 301.DRAWINGS FOR SHORING AND RE-SHORING SHALL BEPREPARED BY A FLORIDA REGISTERED PROFESSIONALENGINEER.
PLUMBING SLEEVES
MINIMUM SLEEVE SPACING SHALL BE THREE DIAMETERSCENTER TO CENTER OF LARGER SLEEVE OR 6" CLEARBETWEEN SLEEVES, WHICHEVER IS GREATER. PRIOR TOCONSTRUCTION, SLEEVE LOCATIONS AND SIZES SHALL BEAPPROVED BY THE ENGINEER OF RECORD.
REINFORCING STEEL
SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREEFROM OIL, SCALE AND RUST AND PLACED IN ACCORDANCEWITH THE TYPICAL BENDING DIAGRAM AND PLACING DETAILSOF ACI STANDARDS AND SPECIFICATIONS. SECUREAPPROVAL OF SHOP DRAWINGS PRIOR COMMENCING ANY
F SPECIFICATION FOR STRUCTURAL CONCRETE FORBUILDINGS. ACI 301 / LATEST EDITION.
G BUILDING CODE REQUIREMENTS AND SPECIFICATIONSFOR MASONRY STRUCTURES (ACI 530-05 & ACI 530.1-05).
DESIGN CRITERIA
ALL WORK SHALL CONFORM WITH THE MINIMUM STANDARDSAS SPECIFIED IN THE FLORIDA BUILDING CODE LATESTEDITION AND ASCE 7-10.
LOAD COMBINATION AS PER ASCE 7-10
ASD1 D + (L OR LR)2 D + 0.75L + 0.75LR3 D + 0.6(WP OR WS)4 D + 0.75L + 0.75LR + 0.75(0.6WP OR 0.6WS)LRFD1 1.2D + 1.6L + 0.5LR2 1.2D + 1.6LR + 1.0L3 1.2D + 1.6 LR + 0.5(WP OR WS)4 1.2D + (WP OR WS) + L = 0.5LR5 0.9D + 1.0(WP OR WS)
MISC. STRUCTURAL STEEL 36,000 PSIREINFORCEMENT - STEEL 60,000 PSI
CONCRETEMINIMUM 28 STRENGTH 4,000 PSIEXCEPT AS FOLLOWS U.N.O.ROOF DECK 4,000 PSIBEAM 4,000 PSICOLUMN 4,000 PSIWALL 4,000 PSIFOUNDATION 4,000 PSI
SOIL BEARING AS PER GEOTECHNICAL REPORT DATED MARCH 2017. BY NUTTTING ENGINEERING
SPECIAL INSPECTION
THE OWNER SHALL EMPLOY A QUALIFIED SPECIALINSPECTOR TO PERFORM INSPECTIONS IN ACCORDANCEWITH THE "THRESHOLD INSPECTION GUIDELINES", ISSUEDSEPARATELY BY THE ENGINEER OF RECORD.THE SPECIAL INSPECTOR SHALL CERTIFY WITH HIS SEAL ANDSIGNATURE AT THE END OF CONSTRUCTION, THAT THECONSTRUCTION OF THIS STRUCTURE HAS BEEN COMPLETEDACCORDING TO THE PROJECT PLANS AND SPECIFICATIONS.
SPECIAL INSPECTIONS SHALL BE PERFORMED BY AREGISTERED PROFESSIONAL ENGINEER LICENSED TOPERFORM INSPECTIONS UNDER FLORIDA THRESHOLD LAWOR HIS QUALIFIED FULL TIME EMPLOYEE.
SHOP DRAWING REVIEW
SHOP DRAWINGS WILL BE REVIEWED FOR GENERALCOMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACTDOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THECONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACTDOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS,DIMENSIONS, ETC.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THECONTRACTOR PRIOR TO SUBMITTAL TO THEARCHITECT/ENGINEER. DRAWINGS SUBMITTED WITHOUTREVIEW WILL BE RETURNED UNCHECKED.
IN ALL INSTANCES THE CONTRACT DOCUMENTS WILLGOVERN OVER THE SHOP DRAWINGS UNLESS OTHERWISESPECIFIED IN WRITING BY THE ENGINEER OF RECORD.
REPRODUCTION OF STRUCTURAL DRAWINGS FOR USE ASSHOP DRAWINGS IS NOT PERMITTED.
WELDED WIRE FABRIC
TO CONFORM TO ASTM A-185, FREE FROM OIL, SCALE ANDRUST AND PLACE IN ACCORDANCE WITH THE TYPICALPLACING DETAILS OF ACI STANDARDS AND SPECIFICATIONS.MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES.
EMBEDDED ITEMS IN CONCRETE
EMBEDDED ITEMS INCLUDING BUT NOT LIMITED TO STEELPLATES FOR CONNECTIONS, WATER STOPS, DOVETAIL SLOTSFOR MASONRY ANCHORS, INSERTS FOR GLASS DOOR ANDRAILS, DOWNSPOUT PIPES IN COLUMNS SHALL BECOORDINATED BY THE CONTRACTOR IN A TIMELY MANNER.ALL EMBEDDED STEEL PLATES FOR THE CONNECTION OFWALL FRAMING, ROOF FRAMING AND MISCELLANEOUS STEELSHALL BE COORDINATED WITH WALL PANEL JOINTS ANDOPENINGS. SUBMIT SHOP DRAWINGS AND OBTAIN ENGINEERAPPROVAL PRIOR CONCRETE PLACEMENT.
CONCRETE
SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TOACHIEVE A STRENGTH AT 28 DAYS AS LISTED BELOW WITH APLASTIC AND WORKABLE MIX:4,000 PSI FOR COLUMN: WATER TO CEMENT RATIO BYWEIGHT SHALL NOT EXCEED 0.504,000 PSI FOR FOUNDATION AND SLABS ON GRADE; WATERTO CEMENT RATIO BY WEIGHT SHALL NOT EXCEED
0.60.
4,000 PSI FOR BEAM: WATER TO CEMENT RATIO BY WEIGHTSHALL NOT EXCEED 0.504,000 PSI FOR ALL STRUCTURAL CONCRETE; WATERTO CEMENT RATIO BY WEIGHT SHALL NOT EXCEED 0.50
CONCRETE SHALL BE PLACED AND CURED ACCORDING TOACI STANDARDS AND SPECIFICATIONS.
SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELDCYLINDERS OR LAB TEST FOR REVIEW PRIOR TO USE. MIXSHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR OTHERPOSITIVE IDENTIFICATION. MIX SHALL MEET THEREQUIREMENTS OF ASTM C33 FOR COARSE AGGREGATE.CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OFASTM STANDARDS C94 FOR MEASURING, MIXING,TRANSPORTING, ETC.
CONCRETE TICKETS SHALL BE TIME STAMPED WITHCONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROMTHE TIME THE MIXING WATER IS ADDED UNTIL IT ISDEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED ONAND ONE HALF, (1 1/2), HOURS. IF FOR ANY REASON THERE ISA LONGER DELAY THAN THAT STATED ABOVE, THECONCRETE3 SHALL BE DISCARDED, IT SHALL BE THERESPONSIBILITY OF THE TESTING LAB TO NOTIFY THEOWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANYNONCOMPLIANCE THE ABOVE.
ALL SLABS SHALL BE CURED USING A DISSIPATING CURINGCOMPOUND MEETING ASTM STANDARD C309 TYPE 1 ANDSHALL HAVE A FUGITIVE DYE. THE COMPOUND SHALL BEPLACED AS SOON AS THE FINISHING IS COMPLETED OR ASSOON AS THE WATER HAS LEFT THE UNFINISHED CONCRETEALL SCUFFED OR BROKEN AREAS IN THE CURING MEMBRANESHALL BE RECOATED DAILY.
ALL CONCRETE SHALL HAVE MID-RANGE WATER REDUCINGADMIXTURE CONFORMING TO ASTM C494 TYPE A.ADMIXTURES CONTAINING CHLORIDE IONS MORE THAN 0.05PERCENT BY WEIGHT IN THE ADMIXTURE SHALL NOT BEUSED. OTHERS ADMIXTURES SHALL BE APPROVED BY THEENGINEER OF RECORD. AIR-ENTRAINING ADMIXTURES SHALLNOT BE USED IN STRUCTURAL CONCRETE.
ALL CONCRETE MIX DESIGN DESIGNS SHALL INCLUDE AWRITTEN DESCRIPTION INDICATING WHERE EACHPARTICULAR MIX IS TO BE PLACED WITHIN THE STRUCTURE.
ALL CONCRETE DESIGN MIX SUBMITTAL SHALL INCLUDETESTED, STATISTICAL BACK-UP DATA AS PER CHAPTER 5 OFACI 318.
CONCRETE TESTING
AN INDEPENDENT TESTING LABORATORY SHALL PERFORMTHE FOLLOWING TEST ON CAST IN PLACE CONCRETE;ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OFPORTLAND CEMENT CONCRETE". MAXIMUM SLUMP SHALL BE4" INCHES. CONCRETE CONTAINING MID-RANGE WATERREDUCED SHALL HAVE A MAXIMUM SLUMP OF 7.5 INCHES.
ASTM C39 - " STANDARD TEST METHOD FOR COMPRESSIVESTRENGTH OF CYLINDRICAL CONCRETE SPECIMENS." ASEPARATE TEST SHALL BE CONDUCTED FOR EACH CLASS,FOR EVERY 50 CUBIC YARDS, OR FRACTION THEREOF,PLACED PER DAY. REQUIRED CYLINDERS QUANTITIES ANDTEST AGE AS FOLLOWS:
1 AT 7 DAYS 2 AT 28 DAYS
ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDERTHE DIRECTION OF THE ENGINEER, IF REQUIRED, IF 28 DAYSTRENGTH IS ACHEIVED, THE CYLINDER MAY BE DISCARDED.PENETRATION
NO PENETRATING SHALL BE MADE IN ANY STRUCTURALMEMBERS OTHER THAN THOSE LOCATED ON THESEDRAWINGS WITHOUT PREVIOUS APPROVAL OF THEENGINEER.
CHEMICAL ANCHORS.
SHALL BE TWO PART EPOXY POLYMER INJECTION SYSTEM,SUCH AS RAMSET 'EPCON", RAWL "FOIL-FAST" CARTRIDGESYSTEM, DUR-O-WALL, "DUR-O-PAIR" EPOXY ANCHOR, ORHILTI HSE2411 EPOXY DOWELING SYSTEM, OR APPROVEDEQUAL. INSTALL IN ACCORDANCE WITH MANUFACTURERSINSTRUCTIONS. INSTALLERS SHALL BE TRAINED BY THEMANUFACTURER'S REPRESENTATIVE.
GENERAL NOTES
SPECIFICATIONS.
LOADING PUMP STATION ROOF
LIVE LOAD= 30 PSFSUPER IMPOSE= +25 PSFTOTAL 55 PSF
FLOOR SLAB:LIVE LOAD= 150 PSFSUPER IMPOSE= +25 PSFDEAD LOAD= +25PSFTOTAL 200 PSF
WIND LOAD:WIND SPEED= 180 MPHEXPOSURE= DCATEGORY= III
Q= REFER TO SOIL REPORT FOR SOIL BEARING CAPACITYSOIL UNIT WEIGHT= 115 PCFFRICTION ANGLE= 30°DEWATERING AS PER GEOTECHNICAL REPORT
CONTROL LOAD:DL= 15PSFLL= 1 DOPS
PRECAST CONCRETE GENERAL NOTES:
1. SPLICES IN REINFORCING BARS SHALL NOT BE LESS 48 BAR DIAMETERS AND REINFORCING SHALL BE CONTINUOUS AROUND CORNERS AND CHANGES IN DIRECTION . CONTINUITY SHALL BE PROVIDED @ CORNERS OR CHANGES IN DIRECTION BY BENDING THE LONGITUDINAL STEELAROUND THE CORNER 48 BAR DIAMETERS.
2. APPROVED CONTRACTOR TO VERIFY ALL DIMENSIONS. THE APPROVED CONTRACTOR IS RESPONSIBLE FOR ALL METHODS, MEANS, SEQUENCES AND PROCEDURES OF WORK.
3. ANY DEVIATION & / OR SUBSTATION FROM THE APPROVED PLANS HEREIN SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF WORK.
4. ELEVATIONS SHOWN ARE BASED ON THE NATIONAL GEODETIC VERTICAL DATUM OF 1929.
5. DESIGN IN ACCORDANCE WITH 2012 FLORIDA BUILDING CODE , 2012 AMENDMENTS.
6 PILES TO BE CUT OFF SQUARE AT PROPER ELEVATIONS ALLOWING A MINIMUM OF 18" OF PILE STEEL TO PROJECT INTO CAP
PRECAST CONCRETE PILES
1. ALL PILE WORKS TO BE DONE IN ACCORDANCE OF THE ACI SPECIFICATIONS WITH THE RECOMMENDATION FOR DESIGN, CERTIFIED MANUFACTURES AND INSTALLATION CONCRETE PILE.
2. PILE TO BE CUT OFF SQUARE AT PROPER ELEVATIONS ALLOWING A MINIMUM OF 18" OF PILE REBAR TO PROJECT INTO PILE CAPS OR CONCRETE BEAM.
3. PRECAST CONCRETE PILES TO BE POURED WITH A MIX CONCRETE DESIGNED BY A RECOGNIZED TESTING LABORATORY TO ATTAIN A STRENGTH OF 6000 PSI IN 28 DAYS
4. ALL PILES SHOULD HAVE A MINIMUM LOAD BEARING CAPACITY OF 70 KIPS FOR VERTICAL PILE AND 110 KIPS FOR BATTERED PILE (2.5 : 12)
5. ALL REINFORCING STEEL TO BE GRADE 60. ALL STEEL TO BE EPOXY COATED.
PRE-CAST CONCRETE PANEL SCHEDULE
TYPE EXCAVATION DEPTH
W3
W4
W5
W6
HEIGHT (FT) THICK (IN)DIMENSION
W2
W1 EL. - 9'-6" (V.I.F.)
±9'-6"
±9'-6" 8"
8"
8"
8"
8"
8"
±9'-6"
±11'-0"
±11'-0"
±9'-6"
EL. - 9'-6" (V.I.F.)
EL. - 11'-0" (V.I.F.)
EL. - 11'-0" (V.I.F.)
EL. - 9'-6" (V.I.F.)
EL. - 9'-6" (V.I.F.)
DEWATERING
PROVIDE REQUIRED DEWATERING DURING ENTIRE PERIOD OF FOUNDATION SLAB AND CONTROL STATION STRUCTURE CONSTRUCTION; PIPE INSTALLATION AND TEMPORARY SHEET PILING ACROSS THE CANAL AS PER LOCAL GOVERNING AUTHORITY REQUIREMENTS.
PROVIDE PROPOSE METHOD OF CONSTRUCTION WITH TEMPORARY SHORING FOR E.O.R. REVIEW AND APPROVAL PRIOR TO PROCEEDING WITH ANYWORK.
SEE SCHEDULEFOR REBAR
SEE SCHEDULEFOR REBAR
LIFTING EYESMIN.5 " CABLE
1'-0
"
3" 3"
2"
EL. - 4.5GRADE / MUD LINE
1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CALCULATIONS SIGNED AND SEALED BY A FLORIDAREGISTERED ENGINEER, PRIOR COMMENCING ANY WORK.
2. PANEL WIDTH SHALL BE VERIFIED PRIOR COMMENCING ANY WORK.
3. PANEL HEIGHT SHALL BE COORDINATED WITH SITE CONDITIONS AND CIVIL DOCUMENTS.
4. REINFORCEMENT COVER SHALL BE 3" MIN. ON ALL SURFACES IN CONTACT WITH WATER OR SOIL. U.N.O.
5. REFER TO SPECS AND GENERAL NOTES FOR CONCRETE SPECIFICATIONS.
6. REFER TO SPECS AND GENERAL NOTES ROR REINFORCEMENT TYPE AND GRADE.
7. CONCRETE P[ANEL FINISH AT WATER SIDE SHALL BE LIGHT BROOM FINISH. U.M.O.
SEE PRE-CAST CONCRETE PANEL SCHEDULE
8"
SEE PRE-CAST CONCRETE PANEL SCHEDULE
3" COVER (TYP.)
4.' -
0"
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTENMATERIAL HEREIN, ASINSTRUMENTS OF SERVICE,SHALL REMAIN THE PROPERTYOF LAKDAS/YOHALEMENGINEERING, INC. (LYE) ANDSHALL NOT BE REPRODUCEDOR COPIED, IN WHOLE OR INPART, WITHOUT THEEXPRESSED WRITTEN CONSENTOF "LYE" AND MAY NOT BEUSED OR REFERENCED FORANY OTHER PROJECT.INFORMATION CONTAINEDHEREIN REPRESENTSPROPRIETARY INFORMATION OFLAKDAS/YOHALEM ENGINEERINGINC. AND / OR ITS CLIENTAND SHALL NOT BE DISCLOSEDTO OTHERS.LAKDAS/YOHALEM ENGINEERING,INC. SHALL BE AFFORDED THEOPPORTUNITY TO PROVIDECONSTRUCTION OBSERVATIONSERVICES DURING THE FRAMEERECTION OF THIS PROJECT. INTHE EVENT LAKDAS/YOHALEMENGINEERING, INC. IS NOTRETAINED IN THIS CAPACITY,LAKDAS/YOHALEM ENGINEERING,INC. CAN ASSUME NORESPONSIBILITY FOR THECONSTRUCTION DEFECTS FORTHE RECOMMENDATIONSPROVIDED IN THESE DOCUMENTS.
e-mail: [email protected]
P.E. # 037590
S-12
AS NOTED
12-01-17
LN
DEF
LN
CONTROL STATION GENERAL NOTES
HALLANDALE PUMP STATION AND CONTROL STRUCTURE-
CONTROL STRUCTURE
172603
FOR BIDDING PURPOSES ONLY
38'-8"
12'-8"
#5 R
EB
AR
@
12" O
.C
, T
&B
#5 REBAR @ 12" O.C, T&B
SLO
PE
1%
38'-8"
1" CHAMFER
#5-90° STD. HOOKED REBAR
@ 12" O.C., E.W., T&B
EL. -4'-0"
EL. 0'-0"
5'-0"
4'-0"
1'-0" M
IN
.
3"
CO
VE
R (T
YP
.)
FINISH GRADE
SEE CIVIL PLAN
CONCRETE
1 CONCRETE ELEMENTS TO HAVE THE FOLLOWING STRENGTHS:
A. SLAB-ON-GRADE 4000 PSI
ALL OTHER CONCRETE TO BE 3000 PSI UNLESS NOTED OTHERWISE.
2 ALL CONCRETE SHALL BE READY MIX, HAVE A MINIMUM COMPRESSIVE
STRENGTH OF :
A. 4000 PSI @28 DAYS AND HAVE A MINIMUM OF 517 LBS. OF CEMENT
PER CUBIC YARD.
B. SLUMPS SHALL BE 3 MINIMUM AND 5 MAXIMUM.
C. CONCRETE SHALL HAVE 3 +/- 1.5 PERCENT AIR ENTRAINMENT.
D. ALL CONCRETE TO HAVE MAXIMUM WATER/CEMENT RATIO OF 0.51.
E. JOB SITE WATER SHALL NOT BE ADDED.
3 ALL CONCRETE WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE
ACI BUILDING CODE (ACI 318 / LATEST EDITION), THE ACI DETAILING
MANUAL (ACI 315 / LATEST EDITION), AND THE SPECIFICATIONS FOR
STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301 / LATEST EDITION).
4 SUBMIT ALL REINFORCING STEEL SHOP DRAWINGS FOR APPROVAL
PRIOR TO ANY FABRICATION.
5 CONCRETE COVER FOR REINFORCING STEEL SHALL BE 3" MIN.
6NOT USED
7 REQUIREMENTS:
A. ALL REINFORCING STEEL SHALL BE MANUFACTURE FROM HIGH
STRENGTH BILLET STEEL CONFORMING TO ASTM DESIGNATION A 615
GRADE 60.
8 LAP ALL BARS MINIMUM 48 DIAMETERS UNLESS OTHERWISE NOTED ON
DRAWINGS.
FOUNDATION
· FOUNDATION ARE DESIGN WITH MINIMUM SAFE BEARING CAPACITY OF
2500 PSF
· REFER TO GEOTECHNICAL ENGINEER'S REPORT BY NUTTING
ENGINEERS OF FLORDA INC, DATED MARCH 2017, FOR GROUND
IMPROVEMENT RECOMMENDATION
DESIGN LOADS: REFER TO MANUFACTURER SPECIFICATION OF
GENERATOR & TRANSFORMER FOR UNIT WEIGHT
GENERAL NOTES:
CODES AND STANDARDS
1. THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THE FOLLOWING
CODES:
A. FLORIDA BUILDING CODE 2014
B. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE ACI
318-05.
C. MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED
CONCRETE STRUCTURES
(ACI 315-05).
D. MANUAL FOR STANDARD PRACTICE FOR WELDING REINFORCED
STEEL INSERTS & CONNECTIONS
IN REINFORCED CONCRETE CONSTRUCTION AWS. D1.4 / LATEST
EDITION.
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
AS NOTED
172603
ALL DRAWINGS AND WRITTEN
MATERIAL HEREIN, AS INSTRUMENTS
OF SERVICE, SHALL REMAIN THE
PROPERTY OF LAKDAS/YOHALEM
ENGINEERING, INC. (LYE) AND SHALL
NOT BE REPRODUCED OR COPIED, IN
WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
"LYE" AND MAY NOT BE USED OR
REFERENCED FOR ANY OTHER
PROJECT. INFORMATION CONTAINED
HEREIN REPRESENTS PROPRIETARY
INFORMATION OF LAKDAS/YOHALEM
ENGINEERING INC. AND / OR ITS
CLIENT AND SHALL NOT BE
DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC.
SHALL BE AFFORDED THE
OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION
SERVICES DURING THE FRAME
ERECTION OF THIS PROJECT. IN THE
EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED
IN THIS CAPACITY, LAKDAS/YOHALEM
ENGINEERING, INC. CAN ASSUME NO
RESPONSIBILITY FOR THE
CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN
THESE DOCUMENTS.
e-mail: [email protected]
12-01-17
IG
GENERATOR &
TRANSFORMER
PAD PLANS &
DETAILS
HALLANDALE
PUMP STATION
HALLANDALE BEACH,
FLORIDA
LN
LN
MS-1
P.E. # 037590
DE
C 0
4, 2
01
7 3
:5
4 P
M S
ER
GIO
L:\L
YE
P
RO
JE
CT
S\2
01
7\1
72
60
3 - H
AL
LA
ND
AL
E S
W P
UM
P S
TA
TIO
N\E
NG
IN
\C
AD
\C
ON
CR
ET
E P
AD
\C
ON
CR
ET
E P
AD
M
IS
C.D
WG
GENERATOR PAD PLAN VIEW
SCALE :1/2"=1'-0"
1
MS-1
GENERAL NOTES
NOT TO SCALE
5
MS-1
2
MS-1
GENERATOR PAD SECTION VIEW
SCALE :1/2"=1'-0"
3
MS-1
4
MS-1
3
MS-1
NOTE:
FINAL SLAB DIMENSIONS TO BE
DETERMINED AFTER GENERATOR FUEL
TANK SHOP DRAWING APPROVAL
FOR BIDDING PURPOSES ONLY
LYE ELEVATION 0' = +3' NA.V.D.
NOT USED
SCALE :NTS
NOT USED
SCALE :NTS
B
A
3'-9"4'-9"
4'-7
1
2
"
4'-9"
14'-0"
14'-0"
11"
5'-11"
5'-10"
21'-0"
3
A-2
1
A-2
1
A-3
1'-9
1
2
"
T.O. ROOF SLAB
+11'-0"
RO
OF
S
LO
PE
MIN
.
14
"/F
T.
RO
OF
S
LO
PE
MIN
.
14
"/F
T.
SLO
PE
SLOPESLOPE
2'-0"
2'-0"
18'-0"
2'-0" 2'-0"
25'-0"
9'-10"9'-10"
PER
MFG.
PER
MFG.
EQ
UA
L
RO
OF
S
LO
PE
MIN
.
14
"/F
T.
ROOF DRAIN PIPE AND
LEADER AT UNDERSIDE
ROOF SLAB.
CONTRACTOR TO
COORDINATE/ ROUTE
DRAIN PIPE TO OUTSIDE
OF NORTH WALL
COMBINATION ROOF AND
OVERFLOW DRAIN UNIT -
SIZE AND SPACING PER
MANUF. SPECIFICATIONS
MODEL: "ZURN"
(OR APPROVED EQUAL)
8"
8"
8" 8"
DIMENSIONAL "SHINGLE" STYLE ASPHALT ROOF TILE OVER
MULTIPLE LAYER ROOFING MEMBVRANE OVER
3
4
" EXTERIOR
GRADE PLYWOOD OVER METAL STUD SUB-FRAMING SEE
DETAIL 3/A-3 & STRUCT. DWGS.
MFG.: OWENS CORNING
"DURATION PREMIUM
COOL" SERIES SOLAR
REFLECTING SHINGLES
COLOR: "SUNRISE"
(OR APPROVED EQUAL)
6'x6' GALV. METAL
EQUIPMENT
ACCESS ROOF
HATCH WITH
INTEGRATED
INSULATED CURB &
PERIMETER
MOUNTING FLANGE
MFG.:JL INDUSTRIES
(OR APPROVED
EQUAL)
CONT. GALV. METAL CAP
FLASHING - SEE 3/A-3
SE
E
DE
TA
IL
4
A-2
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
TEL: (954) 771-0630 FAX: (954) 771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTEN MATERIAL
HEREIN, AS INSTRUMENTS OF SERVICE,
SHALL REMAIN THE PROPERTY OF
LAKDAS/YOHALEM ENGINEERING, INC. (LYE)
AND SHALL NOT BE REPRODUCED OR COPIED
IN WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF "LYE"
AND MAY NOT BE USED OR REFERENCED FOR
ANY OTHER PROJECT. INFORMATION
CONTAINED HEREIN REPRESENTS
PROPRIETARY INFORMATION OF LAKDAS/
YOHALEM ENGINEERING AND / OR ITS CLIENT
AND SHALL NOT BE DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC. SHALL
BE AFFORDED THE OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION SERVICES
DURING THE FRAME ERECTION OF THIS
PROJECT. IN THE EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED IN THIS
CAPACITY, LAKDAS/YOHALEM ENGINEERING,
INC. CAN ASSUME NO RESPONSIBILITY FOR
ANY CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN THESE
e-mail: [email protected]
A-1
AS NOTED
12-01-17
WWRA
IG
WWRA
172603
FLOOR PLAN
AND
ROOF PLAN
SEAL
walter wernecke architectfl license number ar91975
CITY OF HALLANDALE
PUMP STATION AND
CONTROL STRUCTURE
DOCUMENTS.
SCALE:
BUILDING FLOOR PLAN
1
A-1
1/2"=1'-0" SCALE:
BUILDING ROOF PLAN
2
A-1
1/2"=1'-0"
B
A
11"
5'-10"
5'-11"
3'-0"
2'-2" 4'-6"4'-0" 5'-0"4'-0"
7'-4"
5'-6
1 2
"
2'-11"
5'-6
1 2
"
14'-0"
6'-5"
5'-6
1 2
"
2'-11"
5'-6
1 2
"
14'-0"
6'-5"
3'-4" 10'-4"
11"
5'-10"
5'-11"
4'-0"
11'-0"11"11"11"11"1'-8" 4'-8"
21'-0"
8"
8"
8" 8"
3"
3"
3"
21.11
T.O. FLOOR SLAB
+O'-0"
8" GLASS BLOCK (TYP.)
WINDOW
SEE NORTH & SOUTH
ELEVATIONS
AND BUILDING
SECTION 1/A-3.
NOTE: FLUSH WITH
INTERIOR WALL
3
A-2
1
A-2
1
A-3
LINE OF ROOF
OPENING ABOVE
ROOF OVERHANG
T.O. FLOOR SLAB
+O'-0"
T.O. LANDING
+O'-0"
CONC. SLAB EDGE
NOTE:
CONTRACTOR TO
COORDINATE/ ROUTE
DRAIN PIPE TO
OUTSIDE OF NORTH
WALL
HOLLOW METAL DOOR,
FRAME, THRESHOLD
AND HARDWARE
AS SPECIFIED
ALUM. METAL STAIRS AND
RAILING, SEE ELEVATIONS,
DETAIL AND SPECIFICATIONS.
PROVIDE SIGNED AND SEALED
DWGS FOR APPROVAL PRIOR
TO CONSTRUCTION.
T.O. FLOOR SLAB
+O'-0"
OPENING
TO
BELOW
OPENING
TO
BELOW
NO WORK SHALL BE PERFORMED OUTSIDE THE PROJECT LIMITS
WITHOUT PRIOR WRITTEN APPROVAL FROM THE BUILDING OWNER
(CITY OF HALLANDALE), OR THE ENGINEER OF RECORD.
CONTRACTOR SHALL REMOVE ALL DEBRIS AT THE END OF EACH
WORKDAY. CONTRACTOR WILL FURNISH OWN DUMPSTER FOR
TRACH AND DEBRIS STORAGE UNTIL HE CAN REMOVE SUCH FROM
PREMISES. ALL AREAS SHALL BE CLEANED-UP AND PROTECTED.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE
WORK OF ALL TRADES AS REQUIRED FOR COMPLETION OF WORK.
MATERIALS SHALL BE NEW, OF QUALITY SPECIFIED, DELIVERED IN A
TIMELY FASHION AND AMPLE QUANTITY TO PREVENT DELAY OF WORK.
THERE ARE NO SUBSTITUTIONS ALLOWED UNLESS APPROVED BY THE
ENGINEER. THE G. C. SHALL SUBMIT IN WRITING ALL REQUESTS FOR
SUBSTITUTIONS.
THE G. C. SHALL SUBMIT IN WRITING TO THE ENGINEER PRIOR
INSTALLATION, IF ANY UNFORESEEN CONDITIONS AFFECTING
INSTALLATION ACCORDING TO SPECIFICATIONS.
ALL PLAN DETAILS AND WALL SECTIONS ARE ASSUMED TO BE
TYPICAL CONDITIONS UNLESS DETAILED OR NOTED OTHERWISE.
ALL WALLS ARE MIN.1 HR. FIRE RATED.
GROUP OCCUPANCY: F; DIVISION 2
OCCUPANT LOAD: UNOCCUPIED
CONSTRUCTION TYPE III, (NON-SPRINKLERED)
EFFECTIVE FLORIDA BUILDING CODE 2014 EDITION.
EFFECTIVE NFPA 101, LIFE SAFETY CODE, LATEST EDITION.
PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED AT ONE TO
EACH 2,500 SQUARE FEET OF FLOOR AREA, BUT NOT LESS THAN ONE
TO EACH PATH OF EGRESS WITHIN A TRAVEL DISTANCE OF 75 FEET
FOR BUILDINGS NOT EXCEEDING 50 FEET IN HEIGHT (N/A = 1 AT DOOR).
FIRE EXTINGUISHERS SHALL BE TYPE 2A10BC.
CITY OF HALLANDALE PUMP STATION AND CONTROL STRUCTURE - BUILDING DATA - APPLICABLE CODES - GENERAL NOTES
FLAMMABLE OR COMBUSTIBLE LIQUIDS SHALL BE STORED, HANDLED
OR USED ON THE CONSTRUCTION SITE TO COMPLY WITH NFPA 1141
SECTION 3-9.5.
ALL WORK TO BE PERFORMED UNDER THIS CONTRACT SHALL
COMPLY WITH THE MOST RECENT EDITION OF THE FLORIDA
BUILDING CODE, CITY LABOR LAWS, CITY ORDINANCES, CITY
AND COUNTY CODES, RULES AND REGULATIONS, AND ANY
APPLICABLE CODES. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR OBTAINING ALL REQUIRED PERMITS TO CARRY OUT THE
WORK DESCRIBED IN THE CONSTRUCTION DOCUMENTS.
REQUIRED NFPA 704 SIGNAGE SHALL BE INSTALLED ON THE OUTERMOST
EXTERIOR WALL, FACING THE ACCESS ROADWAY NEXT TO ALL DOORS.
INTERIOR FINISH FOR ALL WALLS AND CEILINGS AT EXITS SHALL
BE CLASS A OR B.
CONTRACTOR(S) SHALL FAMILIARIZE HIMSELF/ HERSELF WITH ALL THE
EXISTING CONDITIONS AT THE SITE RELATIVE TO SCOPE OF WORK
RELATED TO THIS PROJECT. ALL MATERIALS HANDLING, STORAGE AND
DELIVERY, WORKING SPACE AVAILABLE, SAFETY PRECAUTIONS REQUIRED,
AND ALL OTHER CONDITIONS NECESSARY TO THE MAKING OF AN
ACCURATE AND COMPLETE PROJECT ARE RESPONSIBILITY OF THE
CONTRACTOR. NO INCREASE IN PROJECT COST SHALL BE WARRANTED IN
THE EVENT THE CONTRACTOR FAILS TO ACKNOWLEDGE EXISTING
CONDITIONS.
ANY DISCREPANCIES WITH THE DRAWINGS, DIMENSIONS OR OTHERWISE
SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER OF RECORD
PRIOR TO CONSTRUCTION.
DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS. DIMENSIONS NOTED
SUPERCEDE SCALED DRAWING. DIMENSION DISCREPANCIES AND/OR
NOT INDICATED IN THE DRAWINGS SHALL BE CONFIRMED WITH THE
ENGINEER OF RECORD PRIOR TO CONSTRUCTION.
CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTAL MATERIALS
REQUIRED TO PROPERLY INSTALL, SUPPORT, (EFFECTIVE MEANS OR
SHORING THE SUPPORTING STRUCTURE DURING THE WORK ON THE
DECK), AND BRACE ALL ITEMS AND COMPONENTS WITHIN THE WORK.
THE WORK:
EXTENDED 12" CONCRETE
LANDING FOR A/C
COMPRESSOR - COORD.
WITH MECHANICAL DWGS.
2
A-2
2
A-3
6'x6' GALV. METAL
EQUIPMENT
ACCESS ROOF
HATCH WITH
INTEGRATED
INSULATED CURB &
PERIMETER
MOUNTING FLANGE
MFG.:JL INDUSTRIES
(OR APPROVED
EQUAL)
A-2
4
A-3
2
A-2
2
3'-0"
36"x36" FLOOR/HATCH
ACCESS. REFER TO CIVIL
PLANS
+ 61.9
- 79.5
+ 61.9
- 79.5
+ 61.9
- 67.3
FOR BIDDING
PURPOSES ONLY
EQ
UA
L
NOTES:
· ROOF SYSTEM IS DESIGNED TO PREVENT
THE ACCUMULATION OF MORE THAN 5" OF
WATER ON ANY PORTION OF THE ROOF AS
PER FBC1617.2.(RESERVED) FBC(PL)1102.6
1108/1108.1ASME A112.6.4 OR ASME A112.3.1
· USE OF ANY COMBUSTIBLE MATERIAL IN
TYPES I & II CONSTRUCTIONS TO COMPLY
WITH FBC603.1 (FIRE-RETARDTANT-TREATED
WOOD) AND 805.1 & 806.1) IF APPLICABLE
AC COMPRESSOR
AC COMPRESSOR
PRE- ENGINEERED LIGHT
GAUGE METAL TRUSSES BY
SPECIALTY ENGINEER
(TYP.). SUBMIT SHOP
DRAWINGS
EXHAUST FAN TO BE BELOW
THE STRUCTURAL BEAM.
CONTRACTOR TO FIELD
VERIFY/ COORDINATE THE
FINAL LOCATION NOT TO
CONFLICT W/ THE CABINET
HEIGHTS. SEE MECH. DWGS.
EXHAUST FAN TO BE BELOW
THE STRUCTURAL BEAM.
CONTRACTOR TO FIELD
VERIFY/ COORDINATE THE
FINAL LOCATION NOT TO
CONFLICT W/ THE CABINET
HEIGHTS. SEE MECH. DWGS.
6"
AHU UNIT HUNG
IN CEILING. SEE
MECH. DRWGS
12"x12" OPENING.
COORDINATE W/
ELECTRICAL PLANS
1'-0"
1'-0" 3'-2"
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
TEL: (954) 771-0630 FAX: (954) 771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTEN MATERIAL
HEREIN, AS INSTRUMENTS OF SERVICE,
SHALL REMAIN THE PROPERTY OF
LAKDAS/YOHALEM ENGINEERING, INC. (LYE)
AND SHALL NOT BE REPRODUCED OR COPIED
IN WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF "LYE"
AND MAY NOT BE USED OR REFERENCED FOR
ANY OTHER PROJECT. INFORMATION
CONTAINED HEREIN REPRESENTS
PROPRIETARY INFORMATION OF LAKDAS/
YOHALEM ENGINEERING AND / OR ITS CLIENT
AND SHALL NOT BE DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC. SHALL
BE AFFORDED THE OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION SERVICES
DURING THE FRAME ERECTION OF THIS
PROJECT. IN THE EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED IN THIS
CAPACITY, LAKDAS/YOHALEM ENGINEERING,
INC. CAN ASSUME NO RESPONSIBILITY FOR
ANY CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN THESE
e-mail: [email protected]
A-2
AS NOTED
12-01-17
WWRA
IG
WWRA
172603
BUILDING ELEVATIONS
SEAL
walter wernecke architectfl license number ar91975
CITY OF HALLANDALE
PUMP STATION AND
CONTROL STRUCTURE
DOCUMENTS.
SCALE:
SOUTH ELEVATION
1
A-2
1/2"=1'-0"
SCALE:
EAST ELEVATION
2
A-2
1/2"=1'-0"
T.O. ROOF SLAB
+11'-0"
T.O. FLOOR SLAB
+O'-0"
2
A-3
BA
SCALE:
WEST ELEVATION
4
A-2
1/2"=1'-0"
T.O. PARAPET
+13'-0"
SCALE:
NORTH ELEVATION
3
A-2
1/2"=1'-0"
21.11
3
A-3
T.O. FLOOR SLAB
+O'-0"
2
A-2
4
A-2
3
A-2
1
A-2
T.O. ROOF SLAB
+11'-0"
T.O. FLOOR SLAB
+O'-0"
2
A-3
B A
T.O. PARAPET
+13'-0"
4
A-2
2
A-2
3
A-2
3
A-3
1
A-2
2 1.1 1
T.O. ROOF SLAB
+11'-0"
T.O. FLOOR SLAB
+O'-0"
T.O. PARAPET
+13'-0"
T.O. ROOF SLAB
+11'-0"
T.O. PARAPET
+13'-0"
MIN.
1
2
"D x4"W SMOOTH
FINISH STUCCO REVEAL/
BAND AROUND DOOR AND
WINDOWS
MIN.
1
2
"D x4"W SMOOTH
FINISH STUCCO REVEAL/
BAND AROUND DOOR AND
WINDOWS
MIN.
1
2
"D x4"W SMOOTH
FINISH STUCCO REVEAL/
BAND AROUND DOOR AND
WINDOWS
DIMENSIONAL "SHINGLE"
ROOF TILE AS SPECIFIED
DIMENSIONAL "SHINGLE"
ROOF TILE AS SPECIFIED
DIMENSIONAL "SHINGLE"
ROOF TILE AS SPECIFIED
DIMENSIONAL "SHINGLE"
ROOF TILE AS SPECIFIED
CONT. METAL CAP
FLASHING AS SPEC.
CONT. METAL CAP
FLASHING AS SPEC.
CONT. METAL CAP
FLASHING AS SPEC.
CONT. METAL CAP
FLASHING AS SPEC.
PAINTED
STUCCO WALL
FINISH
PAINTED
STUCCO WALL
FINISH
PAINTED
STUCCO WALL
FINISH
PAINTED
STUCCO WALL
FINISH
EXTERIOR WALL-MOUNT
LIGHT FIXTURE AS SPEC.
1'-6"
6'-6
"
3'-6
"
3'-0
"
ALUM. STAIRS AND
RAILING. PROVIDE SIGN &
SEAL SHOP DWGS.
PRIOR TO MANUFACTURER
(SEE SHEET S-2)
PAINTED WOOD FASCIA (TYP)
PAINTED EXTERIOR
HOLLOW METAL DOOR
PAINTED WOOD FASCIA (TYP)
8" SQUARE GLASS
BLOCK - TYPICAL
8" SQUARE GLASS
BLOCK - TYPICAL
PAINTED WOOD FASCIA (TYP)PAINTED WOOD FASCIA (TYP)
ROOF RAINWATER LEADER
FROM INSIDE - SEE ROOF
PLAN AND DETAIL _/___
EXTERIOR WALL-MOUNT
LIGHT FIXTURE AS SPEC.
EXTENDED 12" THICK CONCRETE
LANDING FOR A/C COMPRESSOR
COORD. WITH MECHANICAL DWGS.
A/C
COMPRESSOR
STAIR BEYOND
12" CONCRETE SLAB
SEE STRUCTURAL FOR
CONNECTION
CONC. LANDING BEYOND
SEE STRUCTURAL DRAWINGS
FOR CONNECTION
+ 61.9
- 79.5
+ 61.9
- 67.3
+ 61.9
- 79.5
FOR BIDDING
PURPOSES ONLY
EXTENDED 12" THICK
CONCRETE LANDING FOR A/C
COMPRESSOR COORD. WITH
MECHANICAL DWGS.
PRE- ENGINEERED LIGHT
GAUGE METAL TRUSSES BY
SPECIALTY ENGINEER
(TYP.). SUBMIT SHOP
DRAWINGS
PRE- ENGINEERED LIGHT
GAUGE METAL TRUSSES BY
SPECIALTY ENGINEER
(TYP.). SUBMIT SHOP
DRAWINGS
PRE- ENGINEERED LIGHT
GAUGE METAL TRUSSES
BY SPECIALTY ENGINEER
(TYP.). SUBMIT SHOP
DRAWINGS
7'-7
1 2
"2
'-1
0
1 2
"
+/- 8
'-4
"
FIE
LD
V
ER
IF
Y
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
TEL: (954) 771-0630 FAX: (954) 771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
ALL DRAWINGS AND WRITTEN MATERIAL
HEREIN, AS INSTRUMENTS OF SERVICE,
SHALL REMAIN THE PROPERTY OF
LAKDAS/YOHALEM ENGINEERING, INC. (LYE)
AND SHALL NOT BE REPRODUCED OR COPIED
IN WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF "LYE"
AND MAY NOT BE USED OR REFERENCED FOR
ANY OTHER PROJECT. INFORMATION
CONTAINED HEREIN REPRESENTS
PROPRIETARY INFORMATION OF LAKDAS/
YOHALEM ENGINEERING AND / OR ITS CLIENT
AND SHALL NOT BE DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC. SHALL
BE AFFORDED THE OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION SERVICES
DURING THE FRAME ERECTION OF THIS
PROJECT. IN THE EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED IN THIS
CAPACITY, LAKDAS/YOHALEM ENGINEERING,
INC. CAN ASSUME NO RESPONSIBILITY FOR
ANY CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN THESE
e-mail: [email protected]
A-3
AS NOTED
12-01-17
WWRA
IG
WWRA
172603
BUILDING SECTIONS
AND ROOF DETAIL
SEAL
walter wernecke architectfl license number ar91975
CITY OF HALLANDALE
PUMP STATION AND
CONTROL STRUCTURE
DOCUMENTS.
SCALE:
BUILDING SECTION
1
A-3
1/2"=1'-0"
SCALE:
BUILDING SECTION
2
A-3
1/2"=1'-0"
T.O. CONC. PARAPET
+13'-0"
T.O. ROOF SLAB
+11'-0"
T.O. FLOOR SLAB
+O'-0"
2
A-3
ROOF
SLOPE
MIN.
1
4
"/FT.
3
A-3
4'-0" 3" 5'-10"
13
'-2
"
1'-0
"7
'-2
"1
'-4
"4
'-8
"
3'-6
"
2'-1
0"
3'-4
"4
'-4
"
10
'-6
"2
'-0
"
EQUALEQUAL5'-10"11"8" 8"
2'-0" 2'-0"
11" 5'-10" 5'-11"
2"
BA
SCALE:
MANSARD ROOF DETAIL
3
A-3
3"=1'-0"
21.11
8'-6
"4
'-6
"
13
'-2
"
1
A-3
2'-2" 4'-0" 4'-0"4'-6" 5'-0"
T.O. FLOOR SLAB
+O'-0"
3'-4
"2
'-0
"
4'-7
1
2
"
4'-9"3'-9"
1'-9
1
2
"
8" 8"
2'-0"
2"
4'-9"
4'-4
"2
'-1
0"
6"
6"
STUCCO WALL
FINISH OVER 8"
CMU (TYP.)
6
0
°
METAL DRIP FLASHING
FASTENED AS SHOWN
1x P.T. WOOD FASCIA
STUCCO OVER PAPER-BACKED GALV.
METAL LATH
8" GLASS BLOCK (TYP.)
WINDOW SEE NORTH &
SOUTH ELEVATIONS &
BLDG. SECTION 1/A-3
PRE-MANUF. DOUBLE-DOOR
EQUIPMENT ACCESS ROOF
HATCH - SEE SPECS.
CONC. HEADER - SEE
STRUCT. DWGS.
INSECT SCREENED PVC SOFFIT
VENT - TYPICAL
2'-0"
4'-8
"8
'-6
"
CAULK AT JOINT
EQUAL
CL
EQUAL
PRE- ENGINEERED LIGHT
GAUGE METAL TRUSSES BY
SPECIALTY ENGINEER (TYP.).
SUBMIT SHOP DRAWINGS
ROOF SLAB AND TIE BEAM
PER STRUCTURAL DWGS.
2x4 P.T. WOOD BLOCKING AT ROOF
OPENING PERIMETER
DIMENSIONAL "SHINGLE"
ROOF TILE AS SPECIFIED
MULTIPLE LAYER ROOFING
MEMBVRANE OVER
3
4
"
EXT. GRADE PLYWOOD
CONT. METAL CAP FLASHING FASTENED TO
METAL CLEAT AND KEEPER STRIP
(NOT SHOWN - BY ROOF SYSTEM MFG.)
EXTEND BASE ROOFING MEMBRANE
OVER PARAPET - TYPICAL
CONT. 2x10 P.T. WOOD NAILER
FLASHING MEMBRANE - TYPICAL
±6"
COUNTER FLASHING
SHINGLE TOP COVER
EXTEND ROOF MEMBRANE TO
TOP OF PARAPET - TYPICAL
4" (M
IN
.)
4" (M
IN
.)
INTERIOR FINISH AS SPECIFIED
TAPERED ROOF INSULATION
SEE ROOF PLAN AND SPECS.
INSULATED CURB AND PERIMETER
MOUNTING FLANGE (BY EQUIPMENT
ACCESS ROOF HATCH MFG.)
CONC. TIE - PER STRUCT.
CANT - TYP.
2'-0"
4" (M
IN
.)
CONCRETE LINTEL PER
STRUCTURAL DWGS.
HOLLOW METAL DOOR AND FRAME
AS SPECIFIED, TO INCLUDE
WEATHERSTRIPS AT ALL SIDES AND
AT THRESHOLD - SEE SCHEDULE
FOR HARDWARE
SMOOTHENED
AND PAINTED
EXPOSED CMU
WALL (INTERIOR)
T.O. CONC. ROOF SLAB
+11'-0"
T.O. PARAPET
+13'-0"
MIN.
1
2
"D x4"W SMOOTH
FINISH STUCCO REVEAL/
BAND AROUND DOOR AND
WINDOWS
STUCCO STOP AND
SEALANT AT DOOR
FRAME, ALL SIDES
SEAL DOOR FRAME ALL SIDES
EQ.
CL
EQ.
8"
6"
(P
ER
S
TR
UC
T.)
1.5"
MIN
. 12"
(P
ER
M
AN
UF
.)
±10"
2
A-2
4
A-2
3
A-2
1
A-2
NOTE:
ROOF DRAIN PIPE AND LEADER
AT UNDERSIDE ROOF SLAB.
CONTRACTOR TO COORDINATE/
ROUTE DRAIN PIPE TO OUTSIDE
OF NORTH WALL
EXTENDED BUILDING
CONCRETE FLOOR SLAB
STAIR LANDING SEE
STRUCT. DWGS.
+ 61.9
- 79.5
FOR BIDDING
PURPOSES ONLY
10
'-6
"
PRE- ENGINEERED LIGHT
GAUGE METAL TRUSSES BY
SPECIALTY ENGINEER
(TYP.). SUBMIT SHOP
DRAWINGS
PRE- ENGINEERED LIGHT
GAUGE METAL TRUSSES BY
SPECIALTY ENGINEER
(TYP.). SUBMIT SHOP
DRAWINGS
+/- 9
'-1
"
FIE
LD
V
ER
IF
Y
PROPOSED LOCATION OF EXHAUST
FAN TO BE BELOW THE STRUCTURAL
BEAM. CONTRACTOR TO FIELD
VERIFY/ COORDINATE THE FINAL
LOCATION. FINAL LOCATION NOT TO
CONFLICT W/ THE CABINET HEIGHTS.
CONTRACTOR TO COORDINATE/
ROUTE FAN TO OUTSIDE OF WALL
(TYP)
PROPOSED LOCATION OF AHU AS
PER A/C PLANS. CONTRACTOR TO
FIELD VERIFY/ COORDINATE THE
FINAL LOCATION. FINAL LOCATION
NOT TO CONFLICT W/ THE
CABINET HEIGHTS
B.O. BEAM
+10'-0"
CEILING/WALL
MOUNTED AHU
UNIT
AC-1
ME
CH
AN
IC
AL
F
LO
OR
P
LA
N
1
MECHANICAL FLOOR PLAN
1/2"=1'-0"
EXHAUST FANS SCHEDULE
AIR HANDLING UNIT AIR-COOLED CONDENSING UNIT SYSTEMAIR CONDITIONING SYSTEM SCHEDULE
NOTES:
2 DRYWELL DETAIL
AC-2 N.T.S.
12"
4" THICK CONCRETE
36"
2" A/C CONDENSATE
DRAIN PITCH @
1/8" PER FOOT
3/4" WASHED
CRUSHED ROCK
24" X 48" LONG
CONCRETE PIPE
ONE LENGTH OF
SEAL W/ PITCH
PLUG & COVER
12"
FINISH GRADE
VENT
DRYWELL MARKER
1/2" O ROD
1 REFRIGERANT LINE COVER DETAIL
AC-2 N.T.S.
4 AIR-COOLED CONDENSING UNIT SLAB MOUNTED
AC-2 N.T.S.
5 SIDEWALL EXHAST FAN DETAIL
AC-2 N.T.S.
6 AHU HANGING DETAIL
AC-2 N.T.S.
STEEL JOIST
CLEVIS HANGER SINGLE HORIZONTAL RUNS
WITH VAPOR BARRIER INSULATION NO VAPOR BARRIER INSULATION
SINGLE HORIZONTAL RUNS CLEVIS HANGER
STEEL BEAM
CONCRETE INSERT
(SPACING OF HANGERS TO BE IN ACCORDANCE WITH FLORIDA BUILDING CODE - PLUMBING 308.5)
7 PIPE SUPPORT DATAIL
AC-2 N.T.S.
3 CONDENSING UNIT TIE-DOWN DETAIL
AC-2 N.T.S.
AC-2
ME
CH
AN
IC
AL
S
CH
ED
UL
E &
D
ET
AIL
S
*5'-8" *8"
*6'-4"
8" CONCRETE WALL
#5 @ 10" O.C., E.W.
*1'-4"
*0"*0"
1'-0"
#5 - STD. 90°x2'-3"
DOWELS @ 10" O.C.
#4 - BENT @ 10"
O.C. (TYP.)
8" CONCRETE CONCRETE
SLAB W/ 16"x16"xCONT.
THICKENED EDGE
# 5 CON. AND #4
TRANSVERSE @
10" O.C. T&B
7"
11"
PAINT FINISH CONCRETE
EXPOSED SURFACED AS
REQUIRED
*3'-6"
*1'-4"
2'-3"
4 #5 CONT. (TYP.)
#4 @ 10" O.C.
(TYP.)
OUTLINE OF NEW PUMP
STRUCTURE, SEE STRUCTURAL
PLANS FOR MORE DETAILS
*4"
OUTLINE OF THE 2
CUBIC YARD DUMPSTER
3'-6"
FIXED 4" DIA. STEEL
PIPE BOLLARD
PAINT (2) COATS
TRAFFIC YELLOW
ROUNDED
CONCRETE CAP TO
DRAIN
45.0°
*1'-4"
*8"
*9'-4"
8" CONCRETE
WALL
#5 @ 10" O.C., E.W.
#5 - STD. 90°x2'-3"
DOWELS @ 10" O.C.
8" CONCRETE SLAB W/
16"x16"xCONT. THICKENED EDGE
# 5 CONT. AND #4 TRANSVERSE
@ 10" O.C. T&B
*3'-6"
*1'-4"
1% SLOPE
11"
7"
16" CONCRETE CAP
SEA WALL. REFER
TO SEA WALL DWGS.
STEEL SHEET PILE.
REFER TO SEA WALL
DWGS.
EXPANDABLE JOINT
1'-4"
8" 5'-4" 8" 1'-4"
7"
PVC COATED CHAIN-LINK
FENCE GATE WITH
3
4
"
WIDE PLASTIC STRIP
INSIDE BY OTHER
*3
'-6
"*1
'-4
"
OUTLINE OF NEW PUMP
STRUCTURE, SEE STRUCTURAL
PLANS FOR MORE DETAILS
6'-4"4"
PAINT FINISH
CONCRETE EXPOSED
SURFACED AS
REQUIRED
FINISH GRADE AS
CIVIL PLAN
8"5'-8"
*6'-4"
*5'-8"
*8"
*8'-8"
*8"
*9'-4"
OUTLINE OF NEW PUMP
STRUCTURE, SEE STRUCTURAL
PLANS FOR MORE DETAILS
OUTLINE OF NEW
SEAWALL, SEE SEAWALL
PLANS FOR MORE
DETAILS
OUTLINE OF NEW
DUMPSTER ENCLOSURE
8" CONCRETE
WALL
PVC COATED CHAIN-LINK
FENCE GATE WITH
3
4
"
WIDE PLASTIC STRIP
INSIDE BY OTHER
NEW 2 CUBIC
YARD DUMPSTER
*1'-0"
MIN
.
*1'-0"
MIN.
4"
4" DIA. STEEL
PIPE BOLLARD
DESIGN LOADS: HS-20 VEHICLE
GENERAL NOTES:
CODES AND STANDARDS
1. THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THE FOLLOWING
CODES:
A. FLORIDA BUILDING CODE 2014 SUPPL.
B. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE ACI
318-05.
C. MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED
CONCRETE STRUCTURES
(ACI 315-05).
D. MANUAL FOR STANDARD PRACTICE FOR WELDING REINFORCED
STEEL INSERTS & CONNECTIONS
IN REINFORCED CONCRETE CONSTRUCTION AWS. D1.4 / LATEST
EDITION.
CONCRETE
1 CONCRETE ELEMENTS TO HAVE THE FOLLOWING STRENGTHS:
A WALL 4000 PSI
B SLAB-ON-GRADE 4000 PSI
2 ALL CONCRETE SHALL BE READY MIX, HAVE A MINIMUM COMPRESSIVE
STRENGTH OF :
A. 4000 PSI @28 DAYS AND HAVE A MINIMUM OF 517 LBS. OF CEMENT
PER CUBIC YARD.
B. SLUMPS SHALL BE 3 MINIMUM AND 5 MAXIMUM.
C. CONCRETE SHALL HAVE 3 +/- 1.5 PERCENT AIR ENTRAINMENT.
D. ALL CONCRETE TO HAVE MAXIMUM WATER/CEMENT RATIO OF 0.55.
E. JOB SITE WATER SHALL NOT BE ADDED.
3 ALL CONCRETE WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE
ACI BUILDING CODE (ACI 318 / LATEST EDITION), THE ACI DETAILING
MANUAL (ACI 315 / LATEST EDITION), AND THE SPECIFICATIONS FOR
STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301 / LATEST EDITION).
4 SUBMIT ALL REINFORCING STEEL SHOP DRAWINGS FOR APPROVAL
PRIOR TO ANY FABRICATION.
5 CONCRETE COVER FOR REINFORCING STEEL SHALL BE 3" MIN.
6 NOT USED
7 REQUIREMENTS:
A ALL REINFORCING STEEL SHALL BE MANUFACTURE FROM HIGH
STRENGTH BILLET STEEL CONFORMING TO ASTM DESIGNATION A 615
GRADE 60.
B W.W.F. SHALL COMPLY WITH ASTM A 185.
8 LAP ALL BARS MINIMUM 48 DIAMETERS UNLESS OTHERWISE NOTED ON
DRAWINGS.
9 REINFORCING BARS:
A. AT CORNERS OF CONCRETE WALLS, BEAMS AND CONTINUOS WALL
FOOTINGS, PROVIDE (1)-#5 X 5'-0" BENT BAR FOR EACH HORIZONTAL
BAR SCHEDULED AT EACH FACE.
B. ALL HOOKS SHOWN IN REINFORCEMENT SHALL BE ACI
RECOMMENDED HOOKS UNLESS OTHERWISE NOTED.
FOUNDATION
· FOUNDATION ARE DESIGN WITH MINIMUM SAFE BEARING CAPACITY OF
2500 PSF
· REFER TO GEOTECHNICAL ENGINEER'S REPORT BY NUTTING
ENGINEERS OF FLORDA INC, DATED MARCH 2017, FOR GROUND
IMPROVEMENT RECOMMENDATION
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
AS NOTED
172603
ALL DRAWINGS AND WRITTEN
MATERIAL HEREIN, AS INSTRUMENTS
OF SERVICE, SHALL REMAIN THE
PROPERTY OF LAKDAS/YOHALEM
ENGINEERING, INC. (LYE) AND SHALL
NOT BE REPRODUCED OR COPIED, IN
WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
"LYE" AND MAY NOT BE USED OR
REFERENCED FOR ANY OTHER
PROJECT. INFORMATION CONTAINED
HEREIN REPRESENTS PROPRIETARY
INFORMATION OF LAKDAS/YOHALEM
ENGINEERING INC. AND / OR ITS
CLIENT AND SHALL NOT BE
DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC.
SHALL BE AFFORDED THE
OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION
SERVICES DURING THE FRAME
ERECTION OF THIS PROJECT. IN THE
EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED
IN THIS CAPACITY, LAKDAS/YOHALEM
ENGINEERING, INC. CAN ASSUME NO
RESPONSIBILITY FOR THE
CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN
THESE DOCUMENTS.
e-mail: [email protected]
12-01-17
IG
DUMPSTER
ENCLOSURE
PLAN & DETAILS
HALLANDALE
PUMP STATION
HALLANDALE BEACH,
FLORIDA
LN
LN
DE-1
P.E. # 037590
DE
C 0
4, 2
01
7 1
1:5
1 A
M S
ER
GIO
L:\L
YE
P
RO
JE
CT
S\2
01
7\1
72
60
3 - H
AL
LA
ND
AL
E S
W P
UM
P S
TA
TIO
N\E
NG
IN
\C
AD
\D
UM
PS
TE
R E
NC
LO
SU
RE
\P
UM
P S
TA
TIO
N D
UM
PS
TE
R E
NC
LO
SU
RE
.D
WG
DUMPSTER ENCLOSURE PLAN VIEW
SCALE :1/2"=1'-0"
N
2
DE-1
DUMPSTER - FRONT ELEVATION
SCALE :1/2"=1'-0"
3
DE-1
DUMPSTER ENCLOSURE - TYPICAL WALL SECTION 1
SCALE :1/2"=1'-0"
1
DE-1
4
DE-1
2
DE-1
3
DE-1
DUMPSTER ENCLOSURE - TYPICAL WALL SECTION 2
SCALE :1/2"=1'-0"
4
DE-1
GENERAL NOTES
NOT TO SCALE
5
DE-1
*VERIFY DIMENSIONS WITH
CIVIL DRAWINGS
*VERIFY DIMENSIONS WITH
CIVIL DRAWINGS
*VERIFY DIMENSIONS
WITH CIVIL DRAWINGS
*VERIFY DIMENSIONS WITH
CIVIL DRAWINGS
FOR BIDDING PURPOSES ONLY
C
L
C
L
C
L
C
L
C
L
C
L
C
L
C
L
C
L
C
L
C
L
S.W.
7th
STREET
PROPOSED STAY IN
PLACE
SEAWALL (*
)
PROPOSED TEMPORARY S
EAWALL
PROPOSED TEM
PORARY SEAW
ALL
Xref L:\LYE Projects\2017\172603 - Hallandale SW
Pump Station\AD
MIN
\Mail\Incom
ing\11-30-17\20171130 - To LYE\USF Fabrication\ASG
36x36.dwg
10'-0"
2'-0
"2
'-0
"
4'-0
" Ø
D
IP
(S
EE
C
IV
IL
F
OR
EL
EV
AT
IO
N)
3'-0" 3'-0"
8'-0
"
REFER TO CIVIL
PLANS FOR
ELEVATIONS.
4'-0" Ø DIP
(SEE CIVIL FOR
ELEVATION)
FLOW
FLO
W
3
SW-1
8'-0
"
MIN
. H
EIG
HT
10'-0"
FLOW
#5 @ 12" T&B, EW
#5 @ 12" EW, E.F
#5 BENT BAR @ 12"
O.C (TYP)
4'-0
" Ø
D
IP
(S
EE
C
IV
IL
F
OR
EL
EV
AT
IO
N)
1SW-1
PROPOSED SEAWALL LAYOUT PLANSCALE :3/16"=1'-0"
N
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
AS NOTED
172603
ALL DRAWINGS AND WRITTEN
MATERIAL HEREIN, AS INSTRUMENTS
OF SERVICE, SHALL REMAIN THE
PROPERTY OF LAKDAS/YOHALEM
ENGINEERING, INC. (LYE) AND SHALL
NOT BE REPRODUCED OR COPIED, IN
WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
"LYE" AND MAY NOT BE USED OR
REFERENCED FOR ANY OTHER
PROJECT. INFORMATION CONTAINED
HEREIN REPRESENTS PROPRIETARY
INFORMATION OF LAKDAS/YOHALEM
ENGINEERING INC. AND / OR ITS
CLIENT AND SHALL NOT BE
DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC.
SHALL BE AFFORDED THE
OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION
SERVICES DURING THE FRAME
ERECTION OF THIS PROJECT. IN THE
EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED
IN THIS CAPACITY, LAKDAS/YOHALEM
ENGINEERING, INC. CAN ASSUME NO
RESPONSIBILITY FOR THE
CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN
THESE DOCUMENTS.
e-mail: [email protected]
12-01-17
IG
PROPOSED
SEAWALL LAYOUT
PLAN
HALLANDALE
PUMP STATION
HALLANDALE BEACH,
FLORIDA
LN
LN
SW-1
P.E. # 037590
DE
C 0
4, 2
01
7 3
:4
9 P
M S
ER
GIO
L:\L
YE
P
RO
JE
CT
S\2
01
7\1
72
60
3 - H
AL
LA
ND
AL
E S
W P
UM
P S
TA
TIO
N\E
NG
IN
\C
AD
\S
EA
W
AL
L C
AD
\P
UM
P S
TA
TIO
N S
EA
W
AL
L 1
2-0
1-1
7.D
WG
PROPOSED
SEAWALL TYPE
1
PROPOSED
SEAWALL TYPE
2
PROPOSED SEAWALL
TYPE 3. (THIS SEAWALL
TO TERMINATE AT WET
WELL
1
SW-2
2
SW-2
EXISTING
ABUTMENT
SYSTEM
PROPOSED PUMP STATION
(REFER TO CIVIL &
STRUCTURAL PLAN)
NEW PIPE (TYP.)
(REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
EXISTING SEA WALL
(TYP.)
1
SW-3
EXISTING ABUTMENT
SYSTEM
NEW PIPE (TYP.)
(REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
NEW PIPE (TYP.)
(REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
EXISTING PANEL
SEA WALL (TYP.)
S
L
O
P
E
PROPOSED DRAINAGE PIPE
(TYP.)
(REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
(*) CUT OFF ELEVATION 2'-0"
BELOW THE CANAL MUDLINE
AFTER INSTALLATION OF THE PIPE
NEW DUMPSTER
ENCLOSURE. SEE SHEET
DE-1
SEE CIVIL DRAWINGS FOR
EXTENT OF RIP RAP
DIMENSION AND
SPECIFICATIONS
FOR DIMENSIONS AND SHEET PILE
LAYOUT SEE SHEET SW-2 & SW-3
EXISTING SEA WALL
TO BE REMOVED
EXISTING SEA WALL
TO BE REMOVED
EXISTING PILE OF
BRIDGES END BENT
EXISTING PILE OF
BRIDGES END BENT
EXISTING SEA WALL
(TYP.)
PROPOSED CONCRETE
GENERATOR PAD. SEE
SHEET MS-1
FOR BIDDING PURPOSES ONLY
NEW THRUST BLOCK #1
(TYP.) (REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
NEW THRUST BLOCK #2
(TYP.) (REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
NEW THRUST BLOCK #3
(TYP.) (REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
NEW THRUST BLOCK #4
(TYP.) (REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
2
SW-1
PLAN DETAIL
SCALE : 3/32 "=1'-0"
3
SW-1
SECTION DETAIL
SCALE : 3/32 "=1'-0"
13'-10"
7'-7"
21'-6"
3'-4" 2'-6"
3
2
1
1'-11"
9'-6"
3'-4"
10'-1"
EL. -9.25' (V.I.F.)
MUD LINE
EL. -13.65'
TOP OF PIPE
(REFER TO CIVIL
DRAWINGS)
21'-6"
1'-11" 9'-6" 10'-1"
EL. -3.0'
TOP OF WALL
2
1
1'-4
"
EL. -15.25'
BOTTOM OF
SHEET PILE
EL. -3.5'
EXISTING GRADE
48"Ø THRU PIPE
(REFER TO DETAIL 4/SW-4
FOR PIPE PENTRATION
DETAIL)
3
INV. EL. -9.10'
(V.I.F.)
DRAINAGE PIPE
EL.± -9.23' (V.I.F.)
MUD LINE
EL. -3.0'
TOP OF WALL
1
1'-4
"
3
EL. -15.25'
BOTTOM OF
SHEET PILE
EL. -3.5'
EXISTING GRADE
2
11'-8"
EL. -12.57'
TOP OF PIPE
(REFER TO CIVIL
DRAWINGS)
48"Ø THRU PIPE
(REFER TO DETAIL 4/SW-4
FOR PIPE PENTRATION
DETAIL)
1'-11"9'-10"
INV. EL. -8.99'
(V.I.F.)
DRAINAGE PIPE
6'-6"
2
4'-0"2'-6"
3
1
11'-8
"
9'-2
"2'-6"
1'-11
"9'-9"
3SW-2
PROPOSED WALL TYPE 1 EAST ELEVATIONSCALE :3/4"=1'-0"
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
AS NOTED
172603
ALL DRAWINGS AND WRITTEN
MATERIAL HEREIN, AS INSTRUMENTS
OF SERVICE, SHALL REMAIN THE
PROPERTY OF LAKDAS/YOHALEM
ENGINEERING, INC. (LYE) AND SHALL
NOT BE REPRODUCED OR COPIED, IN
WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
"LYE" AND MAY NOT BE USED OR
REFERENCED FOR ANY OTHER
PROJECT. INFORMATION CONTAINED
HEREIN REPRESENTS PROPRIETARY
INFORMATION OF LAKDAS/YOHALEM
ENGINEERING INC. AND / OR ITS
CLIENT AND SHALL NOT BE
DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC.
SHALL BE AFFORDED THE
OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION
SERVICES DURING THE FRAME
ERECTION OF THIS PROJECT. IN THE
EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED
IN THIS CAPACITY, LAKDAS/YOHALEM
ENGINEERING, INC. CAN ASSUME NO
RESPONSIBILITY FOR THE
CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN
THESE DOCUMENTS.
e-mail: [email protected]
12-01-17
IG
PROPOSED
SEAWALL PLANS
& PROFILES
HALLANDALE
PUMP STATION
HALLANDALE BEACH,
FLORIDA
LN
LN
SW-2
P.E. # 037590
DE
C 0
4, 2
01
7 3
:4
9 P
M S
ER
GIO
L:\L
YE
P
RO
JE
CT
S\2
01
7\1
72
60
3 - H
AL
LA
ND
AL
E S
W P
UM
P S
TA
TIO
N\E
NG
IN
\C
AD
\S
EA
W
AL
L C
AD
\P
UM
P S
TA
TIO
N S
EA
W
AL
L 1
2-0
1-1
7.D
WG
1SW-2
PROPOSED WALL TYPE 1 PLANSCALE :3/8"=1'-0"
NRev. Number:
4SW-2
PROPOSED WALL TYPE 2 WEST ELEVATIONSCALE :3/8"=1'-0"
N
LAND SIDE
CANAL SIDE
4
SW-3
2SW-2
PROPOSED WALL TYPE 2 PLANSCALE :3/8"=1'-0"
PROPOSED
PUMP STATION
WALL
LAND SIDE
CANAL SIDE
NEW PIPE (TYP.)
(REFER TO CIVIL FOR
LOCATION & ELEVATIONS)
NEW PIPE (TYP.)
(REFER TO CIVIL FOR
LOCATION &
ELEVATIONS)
3
SW-2
4
SW-2
3
SW-4
2
SW-4
4
SW-3
LEGEND
±CONCRETE CAP (NEW)1
STEEL SHEET PILE (PZ-35)2
BATTER PILE (14"x14")3
DISCRIPTION
NOTE:
1. CAPACITY OF ALL BATTER PILES = 34 TONS,
EMBEDMENT AS PER SIGNED & SEALED SOIL
REPORT BY NUTTING ENGINEERS
LEGEND
±CONCRETE CAP (NEW)1
STEEL SHEET PILE (PZ-35)2
BATTER PILE (14"x14")3
DISCRIPTION
NOTE:
1. CAPACITY OF ALL BATTER PILES = 34 TONS,
EMBEDMENT AS PER SIGNED & SEALED SOIL
REPORT BY NUTTING ENGINEERS
EL. -3'-0" (VERIFY)
TOP OF
WALL
EL. -3'-0" (VERIFY)
TOP OF WALL
3
SW-4
EXISTING SEA WALL
(SEE CIVIL PLAN FOR
PIPE INSTALLATION
THRU EXISTING )
EXISTING SEA
WALL
LYE EXISTING GRADE ELEVATION -3.5' = +3.5' NA.V.D.
LYE T.O.W. ELEVATION -3.0' = 4.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = +3.5' NA.V.D.
LYE T.O.W. ELEVATION -3.0' = 4.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = +3.5' NA.V.D.
LYE T.O.W. ELEVATION -3.0' = 4.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = +3.5' NA.V.D.
LYE T.O.W. ELEVATION -3.0' = 4.0' N.A.V.D.
PROPERTY LINE
PROPERTY LINE
REFER TO DETAIL
4/SW-4 FOR PILE
PENETRATION THRU
STEEL SHEET PILE
PROPOSED
DRAINAGE PIPE
PER CIVIL PLAN
NOTE:
WELD FULL LENGTH OF EACH SHEET PILE
1
4
"x4"
WELD PER EVERY FOOT. PRIOR TO DRIVE AND
CUT OPEN NEW PIPE OPENING. CUT NOT MORE
THAN 1" AROUND OUTSIDE OF DIAMETER OF
PIPE. INSTALL #3 REBAR 4" LONG AT 8" O.C.
AROUND CUT OPEING 2" CLEARANCE. SEAL
ALL AROUND THE PIPE BOTH SIDES WITH 4000
PSI NON SHRINK 6"x6"x6" GROUT AROUND THE
PIPE.
3
SW-4
EXISTING PILE OF
BRIDGES END BENT
NEW PIPE (TYP.)
(REFER TO CIVIL FOR
LOCATION &
ELEVATIONS)
NEW PIPE (TYP.)
(REFER TO CIVIL
FOR LOCATION &
ELEVATIONS)
EXISTING PILE OF
BRIDGES END BENT
FIELD ADJUSTMENT IF
CONFLICT WITH THRU
PROPOSED THRU PIPE
AS NECESSARY
PROPOSED
PUMP STATION
WALL
PROPOSED
DRAINAGE PILE
PER CIVIL PLAN
FOR BIDDING PURPOSES ONLY
1'-4
"
EL. REFER TO
CIVIL DRAWING
MUD LINE
EL. -14.67'
TOP OF PIPE
(REFER TO CIVIL
DRAWINGS)
EL. -3.0'
TOP OF
WALL
2
4
1
2'-6"
3
EL. -15.25'
BOTTOM OF SHEET PILE
EL. -3.5'
EXISTING
GRADE
EL. -3.5'
TOP OF WALL
(TO MATCH EXISTING
GRADE)
EL. -3.0'
TOP OF WALL
2
1
1'-4
"
4
19'-10"
4'-5" 10'-11" 4'-5"
2'-6"
3
EL. -15.25'
BOTTOM OF
SHEET PILE
EL. -3.5'
EXISTING GRADE
EL. -6.52'
TOP OF PIPE
(REFER TO CIVIL
DRAWINGS)
EL. REFER TO
CIVIL DRAWING
MUD LINE
2
1
4
19'-3"
8'-7
"
16'-9" 2'-6"
3'-7" 11'-3" 4'-5"
2'-6
"
3
INTER-LOCK CONNECTION AS PER
SHEET PILE MANUFACTURE
1'-4
"
8"
5" MIN.
2.75
12
REFER TO ELEVATION
FOR
NEW MUD LINE
5"
2'-6"(4) #6 x CONT., TOP
#4 @ 10" O.C.
EL. -3.0'
TOP OF WALL
16" CONCRETE CAP
REFER TO CIVIL
DWGS. FOR PROFILE.
#6 x CONT. MID.
#4 @ 10" O.C.
(4) #6 x CONT., BOTTOM
#4 - 30" LONG @ SHEET PILE MID
SECTION
6'-0
" M
IN
. E
MB
ED
ME
NT
14"x14" PRECAST BATTER PILE W/ EMBEDMENT
AS PER SIGNED AND SEALED SOIL REPORT
AND MIN. CAPACITY OF 34 TONS
STEEL SHEET PILE (PZ-35
OR EQUAL APPROVAL) AND
PROVIDE WEEP HOLES AS REQ'D
(SEE WEEP HOLE NOTE)
EXISTING GRADE
COMPACTED FINISH
GRADE AS REQUIRED
TOP VIEW (TYPICAL)
2'-6"
8" 1'-3"
5" MIN.
14"x14" PRECAST BATTER PILE
STEEL SHEET PILE PZ-35
16" CONCRETE CAP
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
AS NOTED
172603
ALL DRAWINGS AND WRITTEN
MATERIAL HEREIN, AS INSTRUMENTS
OF SERVICE, SHALL REMAIN THE
PROPERTY OF LAKDAS/YOHALEM
ENGINEERING, INC. (LYE) AND SHALL
NOT BE REPRODUCED OR COPIED, IN
WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
"LYE" AND MAY NOT BE USED OR
REFERENCED FOR ANY OTHER
PROJECT. INFORMATION CONTAINED
HEREIN REPRESENTS PROPRIETARY
INFORMATION OF LAKDAS/YOHALEM
ENGINEERING INC. AND / OR ITS
CLIENT AND SHALL NOT BE
DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC.
SHALL BE AFFORDED THE
OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION
SERVICES DURING THE FRAME
ERECTION OF THIS PROJECT. IN THE
EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED
IN THIS CAPACITY, LAKDAS/YOHALEM
ENGINEERING, INC. CAN ASSUME NO
RESPONSIBILITY FOR THE
CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN
THESE DOCUMENTS.
e-mail: [email protected]
12-01-17
IG
PROPOSED
SEAWALL PLANS,
PROFILES &
DETAIL
HALLANDALE
PUMP STATION
HALLANDALE BEACH,
FLORIDA
LN
LN
SW-3
N Rev. Number:
1SW-3
PROPOSED WALL TYPE 3 PLANSCALE :3/8"=1'-0"
LAND SIDE
CANAL SIDE
NEW PIPE
(BEYOND)
P.E. # 037590
SL
OP
E
4
SW-3
2
SW-3
4
SW-3
3
SW-3
PROPOSED PUMP STATION WALL
(SEE STRUCTURAL PLAN OF
PUMP STRUCTURE)
NEW PIPE
(BEYOND)
(TYP.)
LEGEND
±CONCRETE CAP (NEW)1
STEEL SHEET PILE (PZ-35)2
BATTER PILE (14"x14")3
DISCRIPTION
NOTE:
1. CAPACITY OF ALL BATTER PILES = 34 TONS,
EMBEDMENT AS PER SIGNED & SEALED SOIL
REPORT BY NUTTING ENGINEERS
4SW-3
TYPICAL SEAWALL SECTION DETAILSCALE :3/4"=1'-0"
PROPOSED
PUMP STATION
WALL
PROPOSED
PUMP STATION
WALL
TO
P O
F
CA
P
EL. REFER TO
CIVIL DRAWINGS
TOP OF WALL CAP
EL. 0''-0" (VERIFY)
TOP OF WALL
5
SW-3
LYE EXISTING GRADE ELEVATION -3.5' = +3.5' NA.V.D.
LYE T.O.W. ELEVATION -3.0' = 4.0' N.A.V.D.
LYE EXISTING GRADE ELEVATION -3.5' = +3.5' NA.V.D.
LYE T.O.W. ELEVATION -3.0' = 4.0' N.A.V.D.
2SW-3
PROPOSED WALL TYPE 3 EAST ELEVATIONSCALE :3/8"=1'-0"
3SW-3 SCALE :3/8"=1'-0"
PROPOSED WALL TYPE 3 NORTH ELEVATION
NEW PIPE AS
PER CIVIL
PLAN
KING PILE (14"x14")4
FOR BIDDING PURPOSES ONLY
9
0
.
0
°
DETAIL "AA"
PVC SEPARATOR
CONTINUOUS FULL
LENGTH
1
2
" Ø S.S. BOLT
STAGGERED
@ 18" VERTICALLY
ANCHORED INTO
EXISTING CONC. WALL
10"
3" 4" 3"
TYP
3/8
1
2
" THICK STEEL VERT. BENT
PLATE SAME HEIGHT AS
STEEL SHEET PILE
(VERIFY SITE CONDITION)
STEEL SHEET PILE
AS PER PLAN
8"
8"
PROPOSED PUMP STATION
CONCRETE WALL
DETAIL "BB"
TYP
3/8
4"
10
"
3"
4"
3"
STEEL SHEET PILE
AS PER PLAN
PVC SEPARATOR
CONTINUOUS FULL
LENGTH
1
2
" Ø S.S. BOLT
STAGGERED
@ 18" VERTICALLY
ANCHORED INTO
EXISTING CONC. WALL
PROPOSED PUMP STATION
CONCRETE WALL
1
2
" THICK STEEL VERT.
BENT PLATE SAME
HEIGHT AS STEEL SHEET
PILE (VERIFY SITE
CONDITION)
DETAIL "CC"
EXISTING SEAL
WALL
1
2
" Ø S.S. BOLT
STAGGERED
@ 18" VERTICALLY
ANCHORED INTO
EXISTING CONC. WALL
4"
10"
3"
4"
3"
TYP
3/8
PVC SEPARATOR
CONTINUOUS FULL
LENGTH
1
2
" THICK STEEL VERT.
BENT PLATE SAME HEIGHT
AS STEEL SHEET PILE
(VERIFY SITE CONDITION)
STEEL SHEET PILE
AS PER PLAN
EXISTING PILE OF
BRIDGES END BENT
6" MIN.
NEW CONCRETE PILE
CAP ABOVE AS PER
PLAN
NEW PZ-35 STEEL
SHEET PILING AS
PER PLAN
2'-6"
#3 HOR. BAR WELDED
TO THE SHEET PILE @
8" O.C.
48"Ø THRU PIPE
(REFER TO CIVIL PLAN FOR
LOCATION AND ELEVATION
FILLED GROUT
CONCRETE AROUND
THE OPENINGS
(TYP.)
DETAIL - TOP VIEW
DETAIL - TOP VIEW
1'-10" 1'-10" 1'-10"
PZ-35 PZ-35 PZ-35
DETAIL - ELEVATION
48"Ø THRU PIPE
(REFER TO CIVIL PLAN FOR
LOCATION AND ELEVATION
FILLED GROUT
CONCRETE AROUND
THE OPENINGS
(TYP.)
NEW PZ-35 STEEL
SHEET PILING AS
PER PLAN
WELD MIN. THREE (3)
SHEET PILES
TOGETHER PRIOR
TO DRIVE INTO
GROUND
#3 HOR. BAR WELDED TO THE
SHEET PILE @ 8" O.C.
6" M
IN
.
BOTTOM OF SHEET PILE
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
AS NOTED
172603
ALL DRAWINGS AND WRITTEN
MATERIAL HEREIN, AS INSTRUMENTS
OF SERVICE, SHALL REMAIN THE
PROPERTY OF LAKDAS/YOHALEM
ENGINEERING, INC. (LYE) AND SHALL
NOT BE REPRODUCED OR COPIED, IN
WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
"LYE" AND MAY NOT BE USED OR
REFERENCED FOR ANY OTHER
PROJECT. INFORMATION CONTAINED
HEREIN REPRESENTS PROPRIETARY
INFORMATION OF LAKDAS/YOHALEM
ENGINEERING INC. AND / OR ITS
CLIENT AND SHALL NOT BE
DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC.
SHALL BE AFFORDED THE
OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION
SERVICES DURING THE FRAME
ERECTION OF THIS PROJECT. IN THE
EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED
IN THIS CAPACITY, LAKDAS/YOHALEM
ENGINEERING, INC. CAN ASSUME NO
RESPONSIBILITY FOR THE
CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN
THESE DOCUMENTS.
e-mail: [email protected]
12-01-17
IG
PROPOSED
SEAWALL DETAILS
HALLANDALE
PUMP STATION
HALLANDALE BEACH,
FLORIDA
LN
LN
SW-4
Rev. Number:
P.E. # 037590
3SW-4
CONNECTION DETAIL CSCALE :1-1/2"=1'-0"
Checked:
1SW-4
CONNECTION DETAIL ASCALE :1-1/2"=1'-0"
2SW-4
CONNECTION DETAIL BSCALE :1-1/2"=1'-0"
PROPOSED PUMP
STATION CONCRETE
WALL
30" x 16" DP.
CONC SEAWALL CAP
SHEET PILING
AS PER PLAN
1
2
" THICK STEEL
BENT PLATE
DETAIL "AA"NOT TO SCALE
SHEET
PILING
AS PER PLAN
PROPOSED PUMP
STATION CONCRETE
WALL
DETAIL "BB"NOT TO SCALE
30" x 16" DP.
CONC SEAWALL CAP
EXISTING SEAWALL
1
2
" THICK STEEL
BENT PLATE
SHEET
PILING
AS PER PLAN
DETAIL "CC"NOT TO SCALE
4SW-4
PIPE PENETRATION TYPICAL DETAILSCALE : 1/2"=1'-0"
NOTE:
WELD FULL LENGTH OF EACH SHEET PILE
1
4
"x4"
WELD PER EVERY FOOT. PRIOR TO DRIVE AND
CUT OPEN NEW PIPE OPENING. CUT NOT MORE
THAN 1" AROUND OUTSIDE OF DIAMETER OF
PIPE. INSTALL #3 REBAR 4" LONG AT 8" O.C.
AROUND CUT OPEING 2" CLEARANCE. SEAL
ALL AROUND THE PIPE BOTH SIDES WITH 4000
PSI NON SHRINK 6"x6"x6" GROUT AROUND THE
PIPE.
1
2
" THICK STEEL
BENT PLATE
FOR BIDDING PURPOSES ONLY
14.9"
22.64"
PZ-35 STEEL SHEET PILE PROFILE
GENERAL NOTES
ALL WORK TO BE PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH THE MOSTRECENT EDITION OF THE FLORIDA BUILDING CODE, CITY LABOR LAWS, CITY ORDINANCES,CITY/ COUNTY ZONING CODES, RULES AND REGULATIONS, AND ANY APPLICABLE CODES.THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQ'D PERMITS TO CARRYOUT THE WORK DESCRIBED IN THE CONSTRUCTION DOCUMENTS.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH PROJECT SPECIFICATIONS, .CONSULT THESE DOCUMENTS FOR SLEEVES, DEPRESSIONS AND ANY OTHER DETAIL NOTSHOWN ON THE STRUCTURAL DOCUMENTS.
ALL DIMENSIONS AND CONDITIONS MUST BE VERIFY IN THE FIELD. ANY DISCREPANCIESSHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER OF RECORD BEFORE PROCEEDINGWITH THE AFFECTED PART OF THE WORK.
CONTRACTOR(S) SHALL FAMILIARIZE HERSELF/ HIMSELF WITH ALL THE EXISTING CONDITIONSAT THE SITE RELATIVE TO SCOPE OF WORK RELATING TO THIS PROJECT, MATERIALSHANDLING, STORAGE AND DELIVERY, WORKING SPACE AVAILABLE, SAFETY PRECAUTIONSREQUIRED, AND ALL OTHER CONDITIONS NECESSARY TO THE MAKING OF AN ACCURATE ANDCOMPLETE PROJECT BID, NO INCREASE IN PROJECT COST WILL BE ALLOWED FOR FAILUREOF THE CONTRACTOR TO KNOW EXISTING SITE CONDITIONS.
THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER IS COMPLETED.IT IS THE CONTRACTOR RESPONSIBILITY TO DETERMINE PROCEDURES AND SEQUENCING TOENSURE SAFETY OF THE DECK AND ITS COMPONENTS DURING ERECTION. THIS INCLUDESTHE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS ORTIEDOWNS.
DO NOT SCALE DRAWINGS TO OBTAIN DIMENSIONS. ANY DIMENSIONS NOT INDICATED ONDRAWINGS SHALL BE CONFIRMED WITH ENGINEER PRIOR TO CONSTRUCTION.
NO WORK SHALL BE PERFORMED OUTSIDE THE PROJECT LIMITS WITHOUT PRIOR WRITTENAPPROVAL FROM THE BUILDING OWNER AND OR ENGINEER.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES ASREQUIRED FOR COMPLETION OF WORK.
MATERIALS SHALL BE NEW, OF QUALITY SPECIFIED, DELIVERED IN A TIMELY FASHION ANDAMPLE QUANTITY TO PREVENT DELAY OF WORK. SUBSTITUTIONS REQUIRE PRIOR APPROVALFROM ENGINEER.
THERE ARE NO SUBSTITUTIONS ALLOWED UNLESS APPROVED BY THE ENGINEER. THE G. C.SHALL SUBMIT IN WRITING ALL REQUESTS FOR SUBSTITUTIONS.
THE G. C. SHALL SUBMIT IN WRITING TO THE ENGINEER PRIOR INSTALLATION, IF ANYUNFORESEEN CONDITIONS AFFECTING INSTALLATION ACCORDING TO SPECIFICATIONS.
ALL PLAN DETAILS AND WALL SECTIONS ARE ASSUMED TO BE TYPICAL CONDITIONS UNLESSDETAILED OR NOTED OTHERWISE.
CODES AND STANDARDSTHE PROJECT WAS DESIGNED IN ACCORDANCE WITH THE FOLLOWING CODES:
A FLORIDA BUILDING CODE / 2014 EDITION.B BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02).
C MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETESTRUCTURES (ACI 315 / LATEST EDITION)
D MANUAL FOR STANDARD PRACTICE FOR WELDING REINFORCED STEEL INSERTS &CONNECTIONS IN REINFORCED CONCRETE CONSTRUCTION AWS. D1.4 / LATESTEDITION.
E SPECIFICATION FOR STRUCTURAL CONCRETE FOR BUILDINGS. ACI 301 / LATESTEDITION.
G 2014 FDOT DESIGN STANDARD IF APPLICABLE DESIGN LOADS
THE STRUCTURAL SYSTEM HAS BEEN DESIGNED IN ACCORDANCE WITH THE FLORIDABUILDING CODE LATEST EDITION, (2014). THE FOLLOWING SUPERIMPOSED LOADING HAVEBEEN UTILIZED:
SEAWALLLIVE LOAD 250 PLFDEAD LOAD 500 PLFSURCHARGE 200 PSF
DESIGN CRITERIAALL WORK SHALL CONFORM WITH THE MINIMUM STANDARDS AS SPECIFIED IN THE FLORIDABUILDING CODE LATEST EDITION AND ASCE 7-10.
SPECIAL INSPECTIONTHE OWNER SHALL EMPLOY A QUALIFIED SPECIAL INSPECTOR TO PERFORM INSPECTIONS INACCORDANCE WITH THE "THRESHOLD INSPECTION GUIDELINES", ISSUED SEPARATELY BY THEARCHITECT OR ENGINEER OF RECORD. THE SPECIAL INSPECTOR SHALL CERTIFY WITH HISSEAL AND SIGNATURE AT THE END OF CONSTRUCTION, THAT THE CONSTRUCTION OF THISSTRUCTURE HAS BEEN COMPLETED ACCORDING TO THE PROJECT PLANS ANDSPECIFICATIONS.
SPECIAL INSPECTIONS SHALL BE PERFORMED BY A REGISTERED PROFESSIONAL ENGINEERLICENSED TO PERFORM INSPECTIONS UNDER FLORIDA THRESHOLD LAW OR HIS QUALIFIEDFULL TIME EMPLOYEE.
SHOP DRAWING REVIEWSHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENTOF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THECONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY,LENGTH, ELEVATIONS, DIMENSIONS, ETC.
LENGTH, ELEVATIONS, DIMENSIONS, ETC.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TOTHE ENGINEER. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED.
IN ALL INSTANCES THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGSUNLESS OTHERWISE SPECIFIED IN WRITING BY THE ENGINEER OF RECORD.
REPRODUCTION OF STRUCTURAL DRAWINGS FOR USE AS SHOP DRAWINGS IS NOTPERMITTED.
ALL CHANGES AND ADDITIONS MADE ON RE-SUBMITTAL MUST BE CLEARLY FLAGGED ANDNOTED THE PURPOSE OF THE RE-SUBMITTAL MUST BE CLEARLY NOTED ON THE LETTER OFTRANSMITTAL. ARCHITECT/ENGINEER REVIEW WILL BE LIMITED TO THOSE ITEMS CAUSINGTHE RE-SUBMITTAL.
SHOP DRAWINGS REQUIRED ENGINEERING INPUT BY SPECIALTY ENGINEER
THE FOLLOWING SYSTEM AND COMPONENTS AS A MINIMUM REQUIRE FABRICATION ANDERECTION DRAWINGS WITH INPUT BY A SPECIALTY ENGINEER:
· STRUCTURAL PRECAST PILES· STRUCTURAL PRECAST PANELS· STEEL SHEET PILES
SUBMITTAL SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECT AND APPLICABLE CODES, LISTDESIGN CRITERIA, AND SHOW ALL DETAILS AND PLANS NECESSARY FOR PROPERFABRICATION AND INSTALLATION CALCULATIONS AND SHOP DRAWINGS SHALL IDENTIFYSPECIFIC PRODUCT UTILIZED. GENERIC PRODUCT WILL NOT BE ACCEPTED.
SHOP DRAWING AND CALCULATIONS MUST BE PREPARED UNDER THE DIRECT SUPERVISIONAND CONTROL OF THE SPECIALTY ENGINEER.
SHOP DRAWINGS AND CALCULATIONS REQUIRE THE IMPRESSED SEAL, DATE ANDSIGNATURE OF THE SPECIALTY ENGINEER. COMPUTER PRINTOUTS ARE AN ACCEPTABLESUBSTITUTE FOR MANUAL COMPUTATIONS PROVIDED THEY ARE ACCOMPANIED BYSUFFICIENT DESCRIPTIVE INFORMATION TO PERMIT THEIR PROPER EVALUATION, SUCHDESCRIPTIVE INFORMATION SHALL BEAR THE IMPRESSED SEAL AND SIGNATURE OF THESPECIALTY ENGINEER AS AN INDICATION THAT HE/SHE HAS ACCEPTED RESPONSIBILITY FORTHE RESULT.
DRAWINGS PREPARED SOLELY TO SERVE AS A GUIDE FOR FABRICATION AND INSTALLATION,(SUCH AS REINFORCING STEEL SHOP DRAWINGS OR STRUCTURAL STEEL ERECTIONDRAWINGS), AND REQUIRING NO ENGINEERING INPUT DO NOT REQUIRE THE SEAL OF ASPECIALTY ENGINEER.
REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OF SUBMITTAL IS LIMITED TO VERIFYTHE FOLLOWING:
· THAT THE SPECIFIED STRUCTURAL SUBMITTAL HAVE BEEN FURNISHED.· THAT THE STRUCTURAL SUBMITTAL HAVE BEEN SIGNED AND SEALED BY THE
SPECIALTY ENGINEER.· THAT THE SPECIALTY ENGINEER HAS UNDERSTOOD THE DESIGN INTENT AS HAS
USED THE SPECIFIED STRUCTURAL CRITERIA. (NO DETAIL CHECK OFDIMENSIONS OR QUANTITIES WILL BE MADE.)
· THAT THE CONFIGURATION SET FORTH IN THE STRUCTURAL SUBMITTAL ISCONSISTENT WITH THE CONTRACT DOCUMENTS. (NO DETAIL CHECK OFDIMENSIONS OR QUANTITIES WILL BE MADE).
SUBMITTAL NOT MEETING THE ABOVE REFERENCED CRITERIA WILL NOT BE REVIEWED
REINFORCING STEEL
SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE AND RUST ANDPLACED IN ACCORDANCE WITH THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OFACI STANDARDS AND SPECIFICATIONS. SECURE APPROVAL OF SHOP DRAWINGS PRIORCOMMENCING ANY FABRICATION.
EMBEDDED ITEMS IN CONCRETE
EMBEDDED ITEMS INCLUDING BUT NOT LIMITED TO STEEL PLATES FOR CONNECTIONS,WATER STOPS, DOVETAIL SLOTS FOR MASONRY ANCHORS, INSERTS FOR GLASS DOORAND RAILS, DOWNSPOUT PIPES IN COLUMNS SHALL BE COORDINATED BY THE CONTRACTORIN A TIMELY MANNER. ALL EMBEDDED STEEL PLATES FOR THE CONNECTION OF WALLFRAMING, ROOF FRAMING AND MISCELLANEOUS STEEL SHALL BE COORDINATED WITH WALLPANEL JOINTS AND OPENINGS. SUBMIT SHOP DRAWINGS AND OBTAIN ENGINEER APPROVALPRIOR CONCRETE PLACEMENT.
CONCRETE
SHALL BE PER AN APPROVED MIX DESIGN PROPORTIONED TO ACHIEVE A STRENGTH AT 28DAYS AS LISTED BELOW WITH A PLASTIC AND WORKABLE MIX:
6,000 PSI FOR PILES WATER TO CEMENT RATIO BY WEIGHT SHALL NOT EXCEED0.50
4,000 PSI FOR WALL PANELS; WATER TO CEMENT RATIO BY WEIGHT SHALL NOTEXCEED 0.60.
4,000 PSI FOR ALL OTHER STRUCTURAL CONCRETE; WATER TO CEMENT RATIO BYWEIGHT SHALL NOT EXCEED 0.50
CONCRETE SHALL BE PLACED AND CURED ACCORDING TO ACI STANDARDS ANDSPECIFICATIONS.
SUBMIT PROPOSED MIX DESIGN WITH RECENT FIELD CYLINDERS OR LAB TEST FOR REVIEWPRIOR TO USE. MIX SHALL BE UNIQUELY IDENTIFIED BY MIX NUMBER OR OTHER POSITIVEIDENTIFICATION. MIX SHALL MEET THE REQUIREMENTS OF ASTM C33 FOR COARSEAGGREGATE. CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ASTMSTANDARDS C94 FOR MEASURING, MIXING, TRANSPORTING, ETC.
CONCRETE TICKETS SHALL BE TIME STAMPED WITH CONCRETE IS BATCHED. THE MAXIMUM
STANDARDS C94 FOR MEASURING, MIXING, TRANSPORTING, ETC.
CONCRETE TICKETS SHALL BE TIME STAMPED WITH CONCRETE IS BATCHED. THE MAXIMUMTIME ALLOWED FROM THE TIME THE MIXING WATER IS ADDED UNTIL IT IS DEPOSITED IN ITSFINAL POSITION SHALL NOT EXCEED ON AND ONE HALF, (1 1/2), HOURS. IF FOR ANYREASON THERE IS A LONGER DELAY THAN THAT STSTED ABOVE, THE CONCRETE3 SHALL BEDISCARDED, IT SHALL BE THE RESPONSIBILITY OF THE TESTING LAB TO NOTIFY THE OWNER'SREPRESENTATIVE AND THE CONTRACTOR OF ANY NONCOMPLIANCE THE THE ABOVE.
ALL SLABS SHALL BE CURED USING A DISSIPATING CURING COMPOUND MEETING ASTMSTANDARD C309 TYPE 1 AND SHALL HAVE A FUGITIVE DYE. THE COMPOUND SHALL BEPLACED AS SOON AS THE FINISHING IS COMPLETED OR AS SOON AS THE WATER HAS LEFTTHE UNFINISHED CONCRETE ALL SCUFFED OR BROKEN AREAS IN THE CURING MEMBRANESHALL BE RECOATED DAILY.
ALL CONCRETE SHALL HAVE MID-RANGE WATER REDUCING ADMIXTURE CONFORMING TOASTM C494 TYPE A. ADMIXTURES CONTAINING CHLORIDE IONS MORE THAN 0.05 PERCENTBY WEIGHT IN THE ADMIXTURE SHALL NOT BE USED. OTHERS ADMIXTURES SHALL BEAPPROVED BY THE ENGINEER OF RECORD. AIR-ENTRAINING ADMIXTURES SHALL NOT BEUSED IN STRUCTURAL CONCRETE.
ALL CONCRETE MIX DESIGN DESIGNS SHALL INCLUDE A WRITTEN DESCRIPTION INDICATINGWHERE EACH PARTICULAR MIX IS TO BE PLACED WITHIN THE STRUCTURE.
ALL CONCRETE DESIGN MIX SUBMITTAL SHALL INCLUDE TESTED, STATISTICAL BACK-UP DATAAS PER CHAPTER 5 OF ACI 318.
CONCRETE TESTING
AN INDEPENDENT TESTING LABORATORY SHALL PERFORM THE FOLLOWING TEST ON CAST INPLACE CONCRETE;ASTM C143 - "STANDARD TEST METHOD FOR SLUMP OF PORTLAND CEMENT CONCRETE".MAXIMUM SLUMP SHALL BE 4" INCHES. CONCRETE CONTAINING MID-RANGE WATERREDUCED SHALL HAVE A MAXIMUM SLUMP OF 7.5 INCHES.
ASTM C39 - " STANDARD TEST METHOD FOR COMPRESSIVE STRENGTH OF CYLINDRICALCONCRETE SPECIMENS." A SEPARATE TEST SHALL BE CONDUCTED FOR EACH CLASS, FOREVERY 50 CUBIC YARDS, OR FRACTION THEREOF, PLACED PER DAY. REQUIRED CYLINDERSQUANTITIES AND TEST AGE AS FOLLOWS:
· 1 AT 7 DAYS· 2 AT 28 DAYS
ONE ADDITIONAL RESERVE CYLINDER TO BE TESTED UNDEER THE DIRECTION OF THEENGINEER, IF REQUIRED, IF 28 DAY STRENGTH IS ARCHIVED, THE CYLINDER MAY BEDISCARDED.
PENETRATION
NO PENETRATING SHALL BE MADE IN ANY STRUCTURAL MEMBERS OTHER THAN THOSELOCATED ON THESE DRAWINGS WITHOUT PREVIOUS APPROVAL OF THE ENGINEER.
CHEMICAL ANCHORS.
SHALL BE TWO PART EPOXY POLYMER INJECTION SYSTEM, SUCH AS RAMSET 'EPCON", RAWL"FOIL-FAST" CARTRIDGE SYSTEM, DUR-O-WALL, "DUR-O-PAIR" EPOXY ANCHOR, OR HILTIHSE2411 EPOXY DOWELING SYSTEM, OR APPROVED EQUAL. INSTALL IN ACCORDANCE WITHMANUFACTURERS INSTRUCTIONS. INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'SREPRESENTATIVE.
SHEET PILES
1. ALL SHEET PILES AND PILE MISCELLANEOUS ALUMINUM WORK SHALL BE PERFORMED AS PER F.D.O.T. SPECIFICATION 455-9 AND SECTION 962.
2. SHOULD THE CONTRACTOR DECIDE TO USE A DIFFERENT SIZE OF ALUMINUMSHEET PILE SECTION, HE/ SHE SHALL MEET OR EXCEED THE FOLLOWING SHEETPILES REQUIREMENTS.
· SECTION TYPE PZ-35 OR SIMILAR APPROVALS· SECTION MODULUS 48.5 CU.IN./FT· MIN. EMBEDMENT AS SHOWN ON PLANS AND SECTION DETAILS
Design:
DescriptionNumber
Job Number:
Rev. Number:
Drawing Number:
Date:
Checked:
Drawn:
Scale:
Project Name:
Drawing Title
Revisions:
2211 NORTHEAST 54TH STREET
FORT LAUDERDALE, FLORIDA 33308
LAKDAS/YOHALEM ENGINEERING, INC.
(954)771-0630 FAX:(954)771-0519
FL. LIC.: CA-5458
CONSULTING ENGINEERS
AS NOTED
172603
ALL DRAWINGS AND WRITTEN
MATERIAL HEREIN, AS INSTRUMENTS
OF SERVICE, SHALL REMAIN THE
PROPERTY OF LAKDAS/YOHALEM
ENGINEERING, INC. (LYE) AND SHALL
NOT BE REPRODUCED OR COPIED, IN
WHOLE OR IN PART, WITHOUT THE
EXPRESSED WRITTEN CONSENT OF
"LYE" AND MAY NOT BE USED OR
REFERENCED FOR ANY OTHER
PROJECT. INFORMATION CONTAINED
HEREIN REPRESENTS PROPRIETARY
INFORMATION OF LAKDAS/YOHALEM
ENGINEERING INC. AND / OR ITS
CLIENT AND SHALL NOT BE
DISCLOSED TO OTHERS.
LAKDAS/YOHALEM ENGINEERING, INC.
SHALL BE AFFORDED THE
OPPORTUNITY TO PROVIDE
CONSTRUCTION OBSERVATION
SERVICES DURING THE FRAME
ERECTION OF THIS PROJECT. IN THE
EVENT LAKDAS/YOHALEM
ENGINEERING, INC. IS NOT RETAINED
IN THIS CAPACITY, LAKDAS/YOHALEM
ENGINEERING, INC. CAN ASSUME NO
RESPONSIBILITY FOR THE
CONSTRUCTION DEFECTS FOR THE
RECOMMENDATIONS PROVIDED IN
THESE DOCUMENTS.
e-mail: [email protected]
12-01-17
IG
PROPOSED
SEAWALL
GENERAL NOTES
HALLANDALE
PUMP STATION
HALLANDALE BEACH,
FLORIDA
LN
LN
SW-5
Rev. Number:
P.E. # 037590
1SW-5
GENERAL NOTESNOT TO SCALE
FOR BIDDING PURPOSES ONLY