Don't you think we're giving up enough already?’ Attitudes of patients and staff on an...

48
A Major Project Report on INTEGRATED APPROACH BASED FAULTY SECTION IDENTIFICATION USING SYNCHROPHASOR DATA Submitted as a partial fulfillment of the requirements for The Bachelor’s Degree in Electrical Engineering Submitted by: Suryakant Raycha (10117081) Syed Zeeshan Ahmad (10117082) Vinay Kumar Singh (10117084) Vivek Kumar (10117085) Vivek Kumar Verma (10117086) Vivek Kumar Singh (10117088) Approved by- Project Guided by- Dr. A S Thoke Dr. (Mrs.) Monalisa Biswal HOD Assistant Professor Department of Electrical Engg. Department of Electrical Engg. NIT RAIPUR NIT RAIPUR DEPARTMENT OF ELECTRICAL ENGINEERING NATIONAL INSTITUTE OF TECHNOLOGY, RAIPUR 2014

Transcript of Don't you think we're giving up enough already?’ Attitudes of patients and staff on an...

A

Major Project Report on

INTEGRATED APPROACH BASED

FAULTY SECTION IDENTIFICATION USING

SYNCHROPHASOR DATA

Submitted as a partial fulfillment of the requirements for

The Bachelor’s Degree

in

Electrical Engineering

Submitted by:

Suryakant Raycha (10117081)

Syed Zeeshan Ahmad (10117082)

Vinay Kumar Singh (10117084)

Vivek Kumar (10117085)

Vivek Kumar Verma (10117086)

Vivek Kumar Singh (10117088)

Approved by- Project Guided by-

Dr. A S Thoke Dr. (Mrs.) Monalisa Biswal

HOD Assistant Professor

Department of Electrical Engg. Department of Electrical Engg.

NIT RAIPUR NIT RAIPUR

DEPARTMENT OF ELECTRICAL ENGINEERING

NATIONAL INSTITUTE OF TECHNOLOGY, RAIPUR

2014

2

CERTIFICATE

This is to certify that the project work entitled “Integrated Approach Based Faulty

Section Identification using Synchrophasor Data” submitted by Suryakant Raycha,

Syed Zeeshan Ahmad, Vinay Kumar Singh, Vivek Kumar, Vivek Verma, Vivek

Kumar Singh students of B.Tech final year of ELECTRICAL ENGINEERING

during the academic year of 2013-2014 in a partial fulfillment of the requirements for

the award of Degree of Bachelor of Technology in Electrical Engineering by

National Institute of Technology, Raipur is a bonafide presentation of work done

by them. This certificate does not necessarily endorse or accept any statement made

opinion expressed or conclusion drawn as recorded in the report however it only

signifies the acceptance of the report for the purpose for which it is submitted.

Approved by: Under the guidance of:

Dr. A.S. Thoke Dr. (Mrs.) Monalisa Biswal

HOD Assistant Professor

Department of Electrical Engg. Department of Electrical Engg.

NIT RAIPUR NIT RAIPUR

3

ACKNOWLEDGEMENT

We are grateful to the Department of Electrical Engineering, for giving us the

opportunity to execute this project, which is an integral part of the curriculum in B.

Tech programme at the National Institute of Technology, Raipur.

We would also like to take this opportunity to express heartfelt gratitude for our

project guide Dr. (Mrs.) Monalisa Biswal who provided us with valuable inputs at the

critical stages of this project execution.

We would like to thank Dr. A. S. Thoke, H.O.D Electrical Dept. for his guidance,

support and direction without which project would not have taken shape.

We are also thankful to the staff of Electrical Engineering Department for

cooperating with us during the course of our project.

We would like to acknowledge the support of every individual who assisted using

making this project a success and

We are also very thankful to our parents for providing continuous guidance and

whole hearted support throughout the project.

4

ABSTRACT

Long transmission system is an effective and economical solution for handling

more power through a network. With the ever increasing load demand, stress on

power network increases day by day. In a large interconnected network localization

of fault and faulty section is a major challenge for many protection algorithms. In this

work a new algorithm is proposed for faulty section identification based on

synchrophasor data.

The major problem in power network is to diagnosis the fault quickly and

pinpointing the faulty section. Furthermore, communicating the information within

limited time period to other protective devices so as to avoid relay mal-operation in

that zone is a crucial task. With the inception of fault, the positive sequence voltage at

a particular bus is significantly varied. Again the cosine angle between positive

sequence voltage and current is a reliable parameter for fault direction discrimination.

A protection algorithm is developed using these two features for faulty section

identification. With the optimal placement of phasor measurement units the

information is further communicated to other protective devices using binary logic for

avoiding relay mal-operation. Such a technique is advantageous for different fault

cases. The method is tested for WSCC 3-Machine, 9 Bus System simulated using

EMTDC/PSCAD. Within 60 ms time period the information regarding faulty section

is easily communicated to other protective devices.

5

CONTENTS

1. INTRODUCTION 11

1.1 Literature Review…….…………………………..………………….. 12

1.2 Faults in Power System ……………………………………………. .… 13

1.2.1 Symmetrical fault …………………………………....…..… 13

1.2.2 Unsymmetrical fault………………………….....………….. 14

1.3 Sequence components………………………………..……………... 14

1.4 Fault Analysis using Sequence Components …………………..….…. 17

1.4.1 Three Phase fault……………………...…………………… 17

1.4.2 Line to Ground Fault………….…………………..…..…… 19

1.4.3 Line-to-Line Fault……………………………………………. 21

1.4.4 Double-Line-to-Ground Fault……………………………… 22

TITLE PAGE 1

CERTIFICATE 2

ACKNOWLEDGEMENT 3

ABSTRACT 4

CONTENTS 5

LIST OF FIGURES 8

LIST OF TABLES 10

6

2. WIDE AREA MEASUREMENT SYSTEM 24

2.1 Phasor Measurement Unit…………………………………………... 24

2.1.1 Fundamentals of PMU…………………………………….. 24

2.1.2 PMU Concept………………………………………………. 25

2.1.3 Techniques Used in PMU…………………………………… 28

3. INTEGRATED APPROACH BASED FAULTY SECTION

IDENTIFICATION………………………………………………………….

29

3.1 Fault Detection using Positive Sequence Voltage Change………… 29

3.2 Directional Estimation using Cosine Algorithm……………………... 31

3.3

Proposed Method…………………………………….……………….

3.3.1 3.3.1 Relay Binary Logic For Sectional Identification………………

32

34

4. SIMULATION RESULTS……………………….…………………….......

4.1 WSCC 3-Machine, 9-Bus System…………………………………….

37

37

4.2 Cosine Angle And Voltage Dip Plots For Three Phase Fault……

4.2.1 Cosine Angle Plots………………………………………

4.2.2 Voltage Dip Plots……………………………………………

39

39

40

4.3 Cosine Angle And Voltage Dips Plots For Double Line To Ground

Fault …………………………………………………………………….

4.3.1 Cosine Angle Plots…………………………………………

4.3.2 Voltage Dip Plots………………………………………………

41

41

42

7

4.4 Cosine Angle And Voltage Dip Plots For Phase To Phase

Fault……………………………………………………………………

4.4.1 Cosine Angle Plots………………………………………..

4.4.2 Voltage Dip Plots………………………………………………

43

43

44

4.5 Cosine Angle And Voltage Dip Plots For Single Phase To Ground

Fault..........................................................................................................

4.5.1 Cosine Angle Plots…………………………………………

4.5.2 Voltage Dip Plots………………………………………………..

45

45

46

5. CONCLUSION AND FUTURE SCOPE………………………………… 47

REFERENCES……………………………………………………………. 48

8

LIST OF FIGURES

1.1 Unbalance system (a), positive sequence (b), negative sequence(c), 15

zero sequence (d), phasors

1.2 General representation of balance three phase fault 17

1.3 Sequence network diagram of a balance three phase fault 17

1.4 Representation of a single line-to-ground fault 19

1.5 Sequence network diagram of single line-to-ground fault 19

1.6 Representation of line-to-line fault 21

1.7 Sequence network diagram of line-to-line fault 21

1.8 Representation of double line-to-ground fault 22

1.9 Sequence network diagram of double line-to-ground fault 22

2.1 Sinusoidal signal (a), phasor representation(b) 25

2.2 Communication using PMUS 25

2.3 The PMUs arrangement with phasor data concentration system 27

protection center

2.4 Block diagram of PMU 28

3.1 Positive sequence voltage during voltage dip 30

3.2 Flow chart is given for relay logic 33

Table

No.

Title of the Table Page

No.

9

3.3 Flow chart is given for sectional identification 35

4.1 Single line diagram of WSCC 3-machine 9-bus system 37

4.2 Cosine angle plot for relay at bus B2 39

4.3 Cosine angle plot for relay bus B5 39

4.4 Voltage dip plot for relay at bus B2 40

4.5 Voltage dip plot for relay at bus B5 40

4.6 Cosine angle plot for relay at bus B2 41

4.7 Cosine angle plot for relay at bus B5 41

4.8 Voltage dip plot for relay at B2 42

4.9 Voltage dip plot for relay at B5 42

4.10 Cosine angle plot for relay at bus B2 43

4.11 Cosine angle plot for relay at bus B5 43

4.12 Voltage dip plot for relay at B2 44

4.13 Voltage dip plot for relay at B5 44

4.14 Cosine angle plot for relay at bus B2 45

4.15 Cosine angle plot for relay at bus B5 45

4.16 Voltage dip plot for relay at B2 46

4.17 Voltage dip plot for relay at B5 46

10

LIST OF TABLES

3.1 Binary logic for relay at different buses 34

3.2 Binary logic for section identification 36

4.1 Generator’s parameters 38

4.2 Transmission line parameters 38

4.3 Parameters of transmission line between B8-B2, B3-B9 and B1-B7 38

Table

No.

Title of the Table Page

No.

11

CHAPTER-1

INTRODUCTION

An electrical power system consists of generators, transformers, transmission and

distribution lines, etc. Short circuits and other abnormal conditions often occur on a

power system. The heavy current associated with short circuits is likely to cause

damage to equipment if suitable protective relays and circuit breakers are not

provided for the protection of each section of the power system. If a fault occurs in an

element of a power system, an automatic protective device is needed to isolate the

faulty element as quickly as possible to keep the healthy sections of the system in

normal operation. Conventionally, faults are diagnosed through the status of

protective relays and circuit breakers which are activated following a fault. However,

hidden failures of the protection system has itself often been among the main suspects

of partial or widespread blackout. The fault must be cleared within a fraction of a

second.

A protective system includes circuit breakers, transducers (CTs and VTs), and

protective relays to isolate the faulty section of the power system from the healthy

sections. Until recently it was not able to measure the phase angle of the bus voltage

in real time due to technical difficulties in synchronizing measurements from

different locations. The advent of PMUs (Phasor measurement units) all obviated this

problem by synchronizing the voltage and current waveforms at widely dispersed

locations.

This project is based on power system protection using PMUs and its optimal no. of

placement at respective positions for sectional identification of faulty part and also

fault detection. The circuit model is simulated and analyzed by PSCAD, and values

are fetched to MATLAB for further processing using programming techniques. The

project is implemented on 9 bus system.

12

1.1 LITERATURE REVIEW

In recent years different protection algorithm are given by using PMU, wide area

protection, voltage dip[1-8] for fault detection and location calculation. Some

techniques uses synchrophasor measurement, other uses voltage sag technique to

differentiate between balanced and unbalanced condition.

Voltage dip occurs at the bus adjacent to faulty section. This technique is widely used

for fault detection in power system[6-8].another techniques like wide area protection

using PMU and MHO relays are used for power system protection.

MP Thakre[9] presented MHO characteristics and frequency dependent model type

transmission line and simulated using PSCAD/EMTDC software. To study the

performance of relay characteristics single line to ground fault with or without fault

resistance is considered. A fast fourier transform(FFT) block is used to determine

sequence components.

Phasor based voltage sag monitoring proposed by Bollen, Math H.J.[6] uses voltage

sag characteristics. It is drawn including sag magnitude phase angle jump and voltage

jump. A signal processing algorithm is given to obtain voltage sag characteristics of

phase voltages and positive sequence voltages. The proposed technique is applied to a

set of actual measurement obtained from power quality monitor (PQ) and a

synchrophasor measurement unit (PMU).

After reviewing the above techniques and their limitations an integrated technique

based on combination of voltage dip and cosine algorithm is proposed for a WSCC 9

bus system. The proposed approach effectively determines the faulty section with

optimum number of PMU and with minimum fault detecting time. The following

section deal with the objectives and outline of proposed technique.

13

1.2 Faults in Power System

FAULT: The operation of power system under normal operating condition is

balanced steady state three phase. This condition can be temporarily disturbed due to

sudden external or internal change in system a short circuit or fault occur when the

insulation of system fails at any location or conducting object comes in contact with

the lines. The occurrence of short circuit in power system is termed as fault at that

point.

Electrical power systems have a dynamic and complex behavior. Different types of

faults can interrupt the healthy operation of the power system. Some of the major

Electrical faults are phase faults include phase to phase faults and phase to ground

faults and three phase faults. Other Electrical faults are not of major significance but

still are considered, Open circuit faults occurs due to the parting of the overhead line

or failure operation of the circuit breaker, Interturn fault occurs due to the overvoltage

or insulation breakdown. Electrical Faults results in the overloads is due to the

passing the current through the conductor which is above the permissible value and

faults due to real power deficit occurs due to mismatch in the power generated and

consumed and results in the frequency deviation and collapse of grid.

Faults on power system are broadly classified into following two types:

1.2.1 Symmetrical Fault:

A fault involving all the three phases i.e. a three phase fault is called symmetrical

fault in this type of fault all the three phases are simultaneously short circuited. There

may be two situations:

All the three phases may be short circuited to the ground.

All the three phases are short circuited without involving the ground.

Since the network remains electrically balanced during this type of fault it is known

as balanced fault.

14

1.2.2 Unsymmetrical Fault:

An unsymmetrical fault is any fault other than a 3 phase symmetrical fault e.g.

Single line to ground fault(L-G faults),line to line faults(L-L),double line to ground

faults(2L-G).The path of the fault may or may not contain impedance.

Since any unsymmetrical fault causes unbalanced currents to flow in the system this

type of fault is also known as unbalanced faults.

1.3 Sequence Components:

An unbalanced three-phase system can be resolved into three balanced systems in the

sinusoidal steady state. This method of resolving an unbalanced system into three

balanced phasor system has been proposed by C. L. Fortescue. This method is called

resolving symmetrical components of the original phasors or simply symmetrical

components. In this chapter we shall discuss symmetrical components transformation

and then will present how unbalanced components like Y- or -connected loads,

transformers, generators and transmission lines can be resolved into symmetrical

components. We can then combine all these components together to form what are

called sequence networks.

A system of three unbalanced phasors can be resolved in the following three

symmetrical components:

Positive Sequence: A balanced three-phase system with the same phase

sequence as the original sequence.

Negative sequence: A balanced three-phase system with the opposite phase

sequence as the original sequence.

Zero Sequence: Three phasors that are equal in magnitude and phase.

15

Figure 1.2 depicts a set of three unbalanced phasors that are resolved into the three

sequence components mentioned above. In this the original set of three phasors are

denoted by Va, Vb and Vc, while their positive, negative and zero sequence

components are denoted by the subscripts 1, 2 and 0 respectively. This implies that

the positive, negative and zero sequence components of phase-a are denoted by Va1,

Va2 and Va0 respectively.

Figure 1.1 (a) An unbalanced network (b) Positive sequence, (c) Negative sequence

(d) Zero sequence

2

3

2

10120 jea j

on so and

1

2

3

2

1

22403606005

1203604804

3603

2402

000

000

0

0

aeeea

aeeea

ea

ajea

jjj

jjj

j

j

111

2

1 and acab aVVVaV

2

2

222 and acab VaVaVV 000 cba VVV (1.1)

16

The symmetrical component transformation matrix is then given by

c

b

a

a

a

a

V

V

V

aa

aa

V

V

V

2

2

2

1

0

1

1

111

3

1

(1.2)

C is the symmetrical component transformation matrix and is given by

aa

aaC2

2

1

1

111

3

1

(1.3)

2

1

0

1

2

1

0

2

2

1

1

111

a

a

a

a

a

a

c

b

a

V

V

V

C

V

V

V

aa

aa

V

V

V

(1.4)

210 aaaa VVVV (1.5)

21021

2

0 bbbaaab VVVaVVaVV (1.6)

2102

2

10 cccaaac VVVVaaVVV (1.7)

17

1.4 Fault Analysis using Sequence Components

1.4.1 Three-Phase Fault

By definition a three-phase fault is a symmetrical fault. Even though it is the

least frequent fault, it is the most dangerous. Some of the characteristics of a three-

phase fault are a very large fault current and usually a voltage level equals to zero at

the site where the fault takes place.

A general representation of a balanced three-phase fault is shown in Figure

where F is the fault point with impedances Zf and Zg . Below figure shows the

sequences networks interconnection diagram.

Figure 1.2 General representation of a balanced three-phase fault

Figure 1.3 Sequence network diagram of a balanced three-phase fault

18

The corresponding currents for each of the sequences can be expressed as

0

2

1

1

0

0

1.0 0

a

a

a

f

I

I

IZ Z

(1.8)

If the fault impedance Zf is zero,

1

1

1.0 0aI

Z

(1.9)

1

1

2

1

1

1

1

1.0 0,

1.0 240,

1.0 120

af a

f

bf a

f

cf a

f

I IZ Z

I a IZ Z

I aIZ Z

(1.10)

Since the sequence networks are short-circuited over their own fault impedance

0

1 1

2

0

0

a

a f a

a

V

V Z I

V

(1.11)

Therefore,

1 1

2

1 1

1 1

240

120

af a f a

bf a f a

cf a f a

V V Z I

V a V Z I

V aV Z I

(1.12)

19

The line-to-line voltages are

2

1 1

2

1 1

1 1

1 3 30

3 90

1 3 150

ab af bf a f a

bc bf cf a f a

ca cf af a f a

V V V V a Z I

V V V V a a Z I

V V V V a Z I

(1.13)

1.4.2 Single Line-To-Ground Fault

The single line-to-ground fault is usually referred as “short circuit” fault and

occurs when one conductor falls to ground or makes contact with the neutral wire.

The general representation of a single line-to-ground fault is shown in figure where F

is the fault point with impedances Zf. Figure shows the sequences network diagram.

Phase a is assumed to be the faulted phase, this is for simplicity in the fault analysis

calculations.

Figure 1.4 General representation of a single line-to-ground fault.

Figure 1.5 Sequence network diagram of a single line-to-ground fault.

20

Since the zero-, positive-, and negative-sequence currents are equals as it can

be observed in figure Therefore,

0 1 2

0 1 2

1.0 0

3a a a

f

I I IZ Z Z Z

(1.14)

0 1 2af a a aI I I I

0 1 23 3 3af a a aI I I I (1.15)

af f afV Z I

13af f aV Z I

0 1 2af a a aV V V V (1.17)

0 1 2 13a a a f aV V V Z I (1.18)

With the results obtained for sequence currents, the sequence voltages can be

obtained from

0 0

2

1 1

2

22

0 1 1 1

1.0 0 1

0 1

a a

b a

ac

V I

V a a I

a a IV

(1.19)

By solving Equation

0 0 0

1 1 1

2 2 2

1.0

a a

a a

a a

V Z I

V Z I

V Z I

(1.20)

21

1.4.3 Line-To-Line Fault

The general representation of a line-to-line fault is shown in Figure where F is the

fault point with impedances Zf. Figure shows the sequences network diagram. Phase

b and c are usually assumed to be the faulted phases; this is for simplicity in the fault

analysis calculations

Figure 1.6 Representation of line-to-line fault.

Figure 1.7 Sequence network diagram of a single line-to-ground fault.

0afI

(1.21)

bf cfI I (1.22)

bc f bfV Z I (1.23)

0 0aI (1.24)

1 2

1 2

1.0 0a a

f

I IZ Z Z

(1.25)

22

1.4.4 Double Line-To-Ground Fault

The general representation of a double line-to-ground fault is shown in figure

where F is the fault point with impedances Zf and the impedance from line to ground

Zg . figure shows the sequences network diagram. Phase b and c are assumed to be the

faulted phases, this is for simplicity in the fault analysis calculations.

Figure 1.8 Representation of a double line-to-ground fault.

Figure 1.9 Sequence network diagram of a double line-to-ground fault.

Iaf = 0 (1.26)

Vbf = (Zf+Zg)Ibf + ZgIcf

Vcf = (Zf + Zg)Icf + ZgIbf (1.27)

23

The sequence currents can be found as

12 0

1

2 0

1.0 0

( )( 3 )( )

( ) ( 3 )

af f g

f

f f g

IZ Z Z Z Z

Z ZZ Z Z Z Z

02 1

2 0

( 3 )[ ]( ) ( 3 )

f ga a

f f g

Z Z ZI I

Z Z Z Z Z

20 1

2 0

( )[ ]( ) ( 3 )

fa a

f f g

Z ZI I

Z Z Z Z Z

(1.28)

2

0 1 2

2

0 1 2

bf a a a

cf a a a

I I a I aI

I I aI a I

(1.29)

03n a bf cfI I I I (1.30)

0 0 0

1 1 1

2 2 2

1.0

a a

a a

a a

V Z I

V Z I

V Z I

(1.31)

24

CHAPTER 2

WIDE AREA MEASUREMENT SYSTEM

2.1 PHASOR MEASUREMENT UNIT:

Synchronized phasor measurements are becoming an important element of wide area

measurement systems used in advanced power system monitoring, protection, and

control applications. Phasor measurement units (PMUs) are power system devices

that provide synchronized measurements of real-time phasors of voltages and

currents. Synchronization is achieved by same-time sampling of voltage and current

waveforms using timing signals from the Global Positioning System Satellite (GPS).

2.1.1. FUNDAMENTALS OF PMU’S

PMUs technology provides phasor information (both magnitude and phase angle) in

real time. The advantage of referring phase angle to a global reference time is helpful

in capturing the wide area snap shot of the power system. With the advancement in

technology, the microprocessor based instrumentation such as protection Relays and

Disturbance Fault Recorders (DFRs) incorporate the PMU module along with other

existing functionalities as an extended feature. A pure sinusoidal waveform can be

represented by a unique complex number known as a phasor. Consider a sinusoidal

signal

......(2.1)

The phasor representation of this sinusoidal is given by

........ (2.2)

25

Fig.2.1 (a) Sinusoidal signal (b) Phasor representation.

2.1.2. PMU’s Concepts

Although a constant phasor implies a stationary sinusoidal waveform, in practice

it is necessary to deal with phasor measurements which consider the input signal over

a finite data window. The task of the PMU is to separate the fundamental frequency

component and find its phasor representation. The most common technique for

determining the phasor representation of an input signal is to use data samples, and

apply the Discrete Fourier Transform (DFT) to compute the phasor. Being able to

determine phasors across the power system at a fixed point in time has the potential to

solve these problems. One of the key components of future utility systems will

therefore be Phasor Measurement Units (PMUs). PMUs rely on a GPS time signal for

extremely accurate time-stamping of the power system information. A GPS provides

a precise timing

Figure 2.2 Communication using PMU’s

26

pulse, which is correlated with sampled voltage and current inputs - typically the

three phase voltages substation and the currents in lines, transformers, and loads

terminating at the substation. From these data samples, positive-sequence voltages

and currents are calculated and time-stamped so that the exact microsecond when the

phasor measurement is taking is permanently attached to it. The device assembles a

message from the timestamp and the phasor data in a format defined in IEEE standard

1344 which can then be transmitted to a remote site over any available

communication.

The Global Positioning Satellite (GPS) system consists of 24 satellites in six

orbits at an approximate altitude of 10,000 miles above the surface of the earth. It

should be mentioned that a time standard known as the IRIG-B standard is currently

being used by the power industry for time-tagging digital fault recorders and other

substation event monitoring systems. However, with standard IRIG-B receivers the

synchronization accuracy is of the order of 1 millisecond.

The technology of synchronized phasor measurements is well established. It

provides an ideal measurement system with which to protect, monitor and control a

power system, in particular during conditions of stress. The essential feature of the

technique is to measure positive sequence (negative and zero sequence quantities if

needed) voltages and currents of a power system in a real time with precise time

synchronization. This allows accurate comparison of measurements over widely

separated location as well as potential real-time measurement based control action.

Very fast recursive discrete Fourier transform (DFT) calculations are normally used

in phasor calculations. In the suggested technique, a positive sequence voltage and

phase angle of the positive sequence current is used.

The DFT technique is a short-time variation of the Fourier analysis. While the Fourier

transform is applied to signals in the continuous time domain, the DFT is applied to

time-domain signals represented by sequence of numbers. The basic phasor

measurement process is that of estimating a positive-sequence, fundamental

frequency phasor representation from voltage or current waveforms. Phasors of the

three phases are combined to produce the positive sequence measurement. The figure

includes a hardware low-pass filter (Hardware LPF) for antialiasing and an analog-to-

digital (A/D) converter for analog-to-digital conversion. The phase measuring unit is

represented by a discrete phase sequence analyzer block which converts 3 phase

27

signals (Vabc or Iabc) to a positive, negative and zero sequence component magnitude

and angle. Each phase signal (Va, Vb and Vc) is converted to real and imaginary

component using discrete fourier transform.

Figure 2.3 The PMUs arrangement with phasor data concentration and system

protection center.

Output of PMU:-

The output signal from the PMU is the positive sequence voltage and the positive

sequence currents |Vn| θn and |Inm|θnm respectively, where

|Vn| : Positive sequence voltage magnitude of bus.

θn : Positive sequence voltage angle of bus. |Inm| : Positive sequence current

magnitude for interconnected line between two bus.

SCADA

RECORD PDC SPC

PMU1

PMU2

PMU3

PMU4

PMU5

28

2.1.3. The Techniques Used In PMU

The primary purpose of these systems is to improve disturbance monitoring and

system event analysis. These measurements have been sited to monitor generating

sites, major transmission paths and significant control points. Synchronized phasor

measurements provide all significant state measurements including voltage

magnitude, voltage phase angle, and frequency. Most of this phasor measurement

system has been implemented as real-time system. With these systems phasor

measurement units (PMUs) installed at substations send data in real time over

dedicated communications channels to a data concentrators at a utility control centers.

This approach allows the data to be used in System Protection Centers (SPC) as well

as being recorded for system analysis &monitored via SCADA.PMUs measure the

bus voltage and all significant line currents. These measurements are sent to Phasor

Data Concentrator at the control centers. The PDC correlates the data by time tag to

create a system-wide measurement. The PDC exports these measurements as a data

stream as soon as they have been received and correlated. System Protection Center

receive data stream and make a wide area protection depending on wide area view.

WAPS schemes are designed to detect abnormal system conditions, take preplanned

corrective actions intended to minimize the risk of wide area disruption and isolate

the faulted segment from the overall power system.

figure 2.4 Block diagram of PMU

29

CHAPTER 3

INTEGRATED APPROACH BASED FAULTY SECTION

IDENTIFICATION

3.1. FAULT DETECTION USING POSITIVE SEQUENCE

VOLTAGE CHANGE

Voltage dips are the short-duration reductions in r.m.s. voltage caused by faults in the

electric supply system and the starting of large loads, such as motors. Voltage dips are

widely recognized as one of the most important aspects of power quality.

A voltage dip is normally characterized by a magnitude and a duration. In reality,

however, a specific dip can be far more complicated than this characterization can

show. First, besides the voltage drop during a dip, there is also a phase angle shift

associated with it, which is not included in the normal characterization. Second, this

characterization assumes a balanced voltage dip, whereas most voltage dips are due to

unbalanced faults. Both unbalance and phase angle shift are likely to have an

important influence on nuisance tripping of equipment

Voltage dips are regarded as one of the most relevant issues in power quality due

to their high-cost impact in sensitive industrial loads such as adjustable speed drives,

frequency converters, and contactors. A voltage event is considered as sag when the

r.m.s. voltage remains between 0.1 and 0.9 p.u. (per-unit) of nominal voltage and the

event duration does not exceed one minute. However, short interruptions where r.m.s.

voltage is below 0.1 p.u. of nominal voltage can also be considered as voltage dip

events.

Actual data, recorded by a synchrophasor measurement unit (PMU), are used to

evaluate the proposed methodology. PMU data is the positive sequence voltage,

estimated once each cycle. PMU data allows only positive voltage component

characterization through magnitude and phase angle estimated once per cycle.

Although, some drawbacks of PMU voltage dip assessment can be stated, it is a novel

application of this measurement device.

30

The PMU is connected to the substation voltage and current transformers. The

quantities recorded are positive sequence phasors (magnitude and phase angle) of the

measured voltages and currents, frequency and rate of change of frequency.

Positive sequence voltage estimated by a PMU needs to be analyzed. For

instance, phase-angle is measured using the GPS signal as time reference. As actual

frequency is not exactly nominal the phasor recorded seems to be rotating with a

relative frequency given by the difference between actual frequency and nominal one.

In order to obtain a static phasor the recorded phasor is decomposed in a new

coordinate system that is rotating at the pre-event relative frequency. Thus, a new

positive sequence voltage is obtained keeping the former phasor magnitude but with a

new angle which is zero for pre-event situation. So far, positive sequence voltage are

shown in Fig.1. where the star points show the estimated phasor values once per

cycle.

Figure 3.1 Positive sequence voltage during voltage dip

This can be achieved by comparing the measured values of the positive sequence

voltage magnitudes at the main bus for each area. This can result in the minimum

voltage value that indicates the nearest area to the fault.

The above two keys of operation can be mathematically described as follows:

Minimum {|V1|,|V2|,|V3|,|V4|,|V5|,|V6|,……|Vn|} (3.1)

31

Where |Vn| is the positive sequence voltage magnitude measured by PMU and located

at bus 1,2,…..n.

3.2. DIRECTIONAL ESTIMATION USING COSINE

ALGORITHM

By the voltage dip observed by the PMU the exact faulty section of power system

cannot be determined ,only the particular bus can be detected with whom the faulty

section is attached not the exact faulty section. Hence an integrated technique based

on combination of voltage dip measurement and cosine algorithm is used to

determine the faulty section of the system.

The cosine phase angle is used to determine the direction of fault. The ability to

differentiate between a fault in one direction or another is obtained by comparing the

phase angle of the operating voltage and current. The voltage is usually used as the

reference polarizing quantity. The fault current phasor lies within two distinct forward

and backward regions with respect to the reference phasor, depending on the power

system and fault conditions. The normal power flow in a given direction will result in

the phase angle between the voltage and the current varying around its power factor

angle ± Ø. When power flows in the opposite direction, this angle will become

180±Ø. For a fault in the reverse direction, the phase angle of the current with respect

to the voltage will be 180±Ø.

Hence the cosine of phase angle difference between the positive sequence

voltage and positive sequence current in transmission lines connecting to that bus,

also at the receiving end of all the lines where they are connected to another bus,

cosine of the phase angle difference between the positive sequence voltage of

receiving end bus and positive sequence component of current in the transmission

line is calculated via backup relay current transformer(CT).This operation is done for

all transmission lines connected to fault area.

Since for faulted transmission line, the receiving end will have opposite cosine as

observed by PMU of the faulted zone (forward fault and reverse fault). This line can

be identified by following logic-

Cos (α) = -Cos (180-α), α = phase angle (3.2)

32

If Cos (α) is positive then the output provided by relay is ‘0 ’

If Cos (α) is negative then the output provided by relay is ‘1’

3.3. PROPOSED TECHNIQUE

Due to stress on power system selectivity of relay algorithm is more essential

than ever before. In the proposed method for faulty section identification, the

information regarding faulty section is communicated to different relays under which

the faulty section is comes in zone-3 section. In a large integrated network the

application of PMU can be exploited for such a purpose. With optimal placement of

PMU the relay decision located near any bus can be enhanced. In Fig. 3.2 the flow

chart for proposed method is provided.

The voltage and current sample at every bus can be collected using current and

potential transformer. The DFT based phasor estimation technique is applied for

estimating the fundamental voltage and current signal. The WSCC, 9-bus 3- Machine

9-bus system as shown in Fig…..is considered for study. The prefault and fault

positive sequence voltage and fault positive sequence at every bus is calculated at

every bus. In this work three PMUs are placed at bus 1, 2 and 3. With such

placement of PMU the information of faulty section can be easily communicated to

other relays present in the 9-bus power network. Every bus is assigned with a binary

logic so as to differentiate the signal receiving by the PMU. If PMU located at any

bus receive the signal of faulty section will be transmitted to other PMUs to block

relay mal-operation. The proposed method is explained below.

Considering the WSCC, 9-bus 3- Machine 9-bus system as shown in Fig 4.1

suppose a fault occur between bus 5 and 3. From the prefault and fault voltage and

current signal positive sequence voltage and current phasor can be estimated at bus 5

and 3. In the integrated approach, according to first algorithm relay at bus 5 and

computes the value of Cos (α). At bus 3the value of Cos (α) will be negative whereas

at bus 5 it is positive. So relay output at bus 5 will be “0” and at bus 3 “1”. According

to second algorithm relay at bus 5 and 3 check the value of . As fault occurred in

section 5-3, the value of is negative at bus 5 and 3. The relay output at both the

buses will be “1”. So, the overall output for the fault in section 5-3 will be “01” for

relay at bus 5 and “11” for relay at bus 3.

33

Figure 3.2 Flow chart is given for relay logic

For any 01, 11 at relay bus indicate the fault indicates the fault in the reverse zone.

For exact section identification relay communicate the signal to both nearby reverse

Collect voltage and current

sample at bus 1 to 9

Prefault and fault voltage and fault

current phasor estimation at bus 1 to 9

Calculate Cos (α) and at

each bus

Is

Cos (α)

Negative

Yes

No

Is

Negative

No Yes

Relay output 11

Relay output 00

Relay output 01

Relay output 10

Communicated to PMU

34

and forward zone relays. Considering the communication delay the signal can be send

within 10 ms to the nearby relays. If at any bus relay receives any two signal from 01,

10, 11, it immediately transfer this signal to nearby PMU with its relay code for

further operation. The binary logic for all buses is shown in Table 3.1. The relay at

bus 5 has binary signal “01” due to its own measurement and “11” due to relay at bus

3 measurements. So it communicates its own binary signal “0101” to nearest PMU at

bus 2. Similarly the relay bus 3 sends its binary signal “0010” to PMU at the same

bus. In any network, two interconnected buses will exchange simultaneously binary

information then that section will declared as a faulty section. In a case, if any relay

receives “00” signal then it will be silent for that fault case. Further the relay at bus 2

and 3 communicate this signal to other PMU so as to circulate the decision among

other relays to avoid relay mal-operation.

3.3.1 RELAY BINARY LOGIC FOR SECTIONAL IDENTIFICATION

A binary code is developed for sectional identification for each relay bus as per the

following scheme-

1. First four digits shows relay bus position

2. Fifth digit shows cosine logic, 0 for positive cosine and 1 for negative cosine

3. Sixth digit shows the voltage dip logic, 1 if is negative otherwise 0

TABLE 3.1. Binary Logic for Relays at Different Buses

Bus No. Relay binary logic

1 0001

2 0010

3 0011

4 0100

5 0101

6 0110

7 0111

8 1000

9 1001

35

START

SELECT BINARY

CODE RELAY

BUS N

IF LAST TWO DIGITS

ARE 01 OR 10

CONVERT FIRST FOUR

DIGITS TO HEX

DECIMAL EQUIVALENT

N=N+1

COMBINE TWO HEX

DIGITS SO OBTAINED

(abH)

FAULT IS IN SECTION

BETWEEN BUS a AND

b

Among the nine binary codes for each relay bus, the two which has their last two digits as 01

or 11, will be selected from nine binary codes, after this the first four digits of both the relay

binary codes will be converted to their hexadecimal equivalent codes, then the pair of HEX

digits will be showing the faulty section.

For example-If fault occurs at section between B5 and B3, then binary code of relay at bus 5

will be 010101 and that of relay bus at 3 will be 001111; the other seven relay bus will not

have their last two digits as 01 or 11. After converting first four digits of binary codes of

relay bus 5 and relay bus 3, HEX digits will be 53H, which shows fault occurs between bus 5

and bus 3.

Figure 3.3 Flow chart is given for sectional identification

36

TABLE 3.2. Binary Logic for Section Identification

Relay binary logic Faulty Section

28H 2-8

25H 2-5

24H 2-4

53H 5-3

39H 3-9

36H 3-6

61H 6-1

17H 1-7

41H 4-1

37

CHAPTER 4

SIMULATION RESULT

4.1. WSCC 3-Machine, 9-Bus System

WSCC 3-Machine, 9-bus system as shown in Fig.1 is considered for the study. The

system data are provided in Table 4.1 and 4.2, 4.3. The system is simulated using

EMTDC/PSCAD software. The sampling frequency is maintained at 1KHz. Fault is

created at 0.3 sec and continues up to 0.8 sec in between B5 and B2. Type of fault is

varied for fault between B5 and B2.

100 MW, 35 MVAR

Bz B5 B3 B9

B4 B6

B1

B7

Figure 4.1. Single line diagram of WSCC 3-Machine, 9 Bus System.

S2 S3

S1

B8 B2

B5

B3

B9

B1

B4 B6

125 MW,50 MVAR 90 MW, 30 MVAR

B7

38

Table 4.3 Parameters of Transmission Line between B8-B2, B3-B9 and B1-B7

(+ ve) Sequence XC 302.151 [Mohm*m]

Zero Sequence XC 419.34[Mohm*m]

Table 4.2 Transmission Line Parameter

(+ ve) Sequence R 0.03293e-3

[ohm/m]

(+ ve) Sequence XL 0.3184e-3

[ohm/m]

(+ ve) Sequence XC 280.2023 [M ohm*m]

Zero Sequence R 0.2587e-3

[ohm/m]

Zero Sequence XC 414.46 [Mohm*m]

Zero Sequence XL 1.1740e-3

[ohm/m]

Table 4.1 Generator’s Parameter for 9 Bus System

GENERATOR

PARAMETERS

GENERATORS

S1 S2 S3

Base Voltage (L-L, RMS) 400 KV 400 KV 400KV

(+ve ) Seq. Impedance 20.0 [ohm] 20.0 [ohm] 20.0 [ohm]

(+ve ) Seq. Impedance phase angle 85.0 [deg.] 85.0 [deg.] 85.0 [deg.]

Zero Seq. Impedance 30.0 [ohm] 30.0 [ohm] 30.0 [ohm]

Zero Seq. Impedance phase angle 85.0 [deg.] 85.0 [deg.] 85.0 [deg.]

Phase 0 [deg.] 10 [deg.] 2 [deg.]

39

4.2 COSINE ANGLE AND VOLTAGE DIP PLOTS FOR

THREE PHASE FAULT

4.2.1 Cosine Angle Plot

figure 4.2 Cosine angle plot for relay at bus B2

figure 4.3 Cosine angle plot for relay bus B5

40

4.2.2 VOLTAGE DIP PLOTS

Figure 4.4 Voltage dip plot for relay at bus B2

Figure 4.5 Voltage dip plot for relay at bus B5

41

4.3 COSINE ANGLE AND VOLTAGE DIP PLOTS FOR

DOUBLE LINE TO GROUND FAULT

4.3.1 Cosine Angle plots

Figure 4.6 Cosine angle plot for relay at bus B2

Figure 4.7 Cosine angle plot for relay at bus B5

42

4.3.2 Voltage Dip Plots

Figure 4.8 Voltage dip plot for relay at B2

Figure 4.9 Voltage dip plot for relay at B5

43

4.4 COSINE ANGLE AND VOLTAGE DIP PLOTS FOR

PHASE TO PHASE FAULT

4.4.1 Cosine Angle plots

Figure 4.10 Cosine angle plot for relay at bus B2

Figure 4.11 Cosine angle plot for relay at bus B5

44

4.4.2 Voltage Dip Plots

Figure 4.12 Voltage dip plot for relay at B2

Figure 4.13 Voltage dip plot for relay at B5

45

4.5 COSINE ANGLE AND VOLTAGE DIP PLOTS FOR

SINGLE LINE TO GROUND FAULT

4.5.1 Cosine Angle plots

Figure 4.14 Cosine angle plot for relay at bus B2

Figure 4.15 Cosine angle plot for relay at bus B5

46

4.5.2 Voltage Dip Plots

Figure 4.16 Voltage dip plot for relay at B2

Figure 4.17 Voltage dip plot for relay at B5

47

CHAPTER 5

CONCLUSIONS AND SCOPE FOR WORK FUTURE

Large power demand and excess utilization of transmission system leads to stress

on power system. Localization of fault and faulty section is a major challenge for

protection algorithm. In this work a new integrated approach is proposed for faulty

section identification. Fault detection with the change in positive sequence voltage is

a reliable parameter. The cosine of angle between voltage and current is also a

reliable parameter for exact fault direction discrimination. These two features are

applied in the proposed algorithm for exact faulty section identification. With the

application of PMU device the information can be further transmitted to other related

zones to avoid relay mal-operation. The proposed technique has successfully

identified the faulted line and also types of fault in a large interconnected system. The

PMU descried in this paper represents a new state-of-art in the field of interconnected

grid protection for many reasons such as;

The PMU is based on sharing data from all areas.

One PMU is used instead of many standalone relays with different complexity

coordination.

The PMU has the feature of unit protection in identifying the faulted zone.

One and only one trip decision is issued from the protection Center.

The PMU has a very fast detection time for all fault cases. In the near future and

with a very fast communication links, the PMU can be considered as a main

protection unit on the interconnected grids. The proposed technique is a step forward

in achieving the full potential of a smart grid by using various measurements and data

across the grid. It is expected to be a new application of wide area measurement

system in the transmission grid with the development of communication

infrastructure in smart transmission grids. Exciting yet challenging times lie ahead.

The electrical power industry is undergoing rapid change. The rising cost of energy,

the mass electrification of everyday life, and climate change are the major drivers that

will determine the speed at which such transformations will occur.

48

References

1. Wide Area protection and Emergency control, 2002, IEEE members, Working

Group C-6.

2. Eissa ,M.M., Masoud ,M.E. Elenwar ,M.M.M. ‘A Novel back up wide area

protection technique for power transmission grid using phasor measurement unit’,

IEEE Trans, Power Deliv, 2010 , 25, (1), pp. 270-278

3. Dobakhshari , A.S, Ranjbar, A. M., ‘A circuit approach to fault diagnosis in power

system by wide area measurement system’, Accepted to be published in Eur. Trans.

Electr., power 2012

4. Phadke, A.G., Thorp, J.S., “Synchronized phasor measurements and their

application”, (Springer, 2008 1st Edition.)

5. Azizi ,S., Dobakhshari ,A.S., Sarmadi, S.A.N., Ranjbar, A.M., “Optimal PMU

Placement By An Equivalent Linear Formulation For Exhaustive search”, IEEE

Trans., Smart Grid ,2012.

6. Bollen, Math H.J. (1999). Solving power quality problems: voltage sags and

interruptions. New York: IEEE Press. p. 139.

7. Characteristic of voltage dips (sags) in power systems Lidong Zhan ; Bollen,

M.H.J. Page(s):827 – 832

8. A new definition of voltage sag duration considering the voltage tolerance

curve Seon-Ju Ahn ; Il-Yop Chung ; Joong-Moon Kim.

9. MATLAB-based fault analysis of Power Systems with Graphical User Interface

Jamahbozorg, A. ; Radman, G. Southeastcon, 2011

10. Detection of Symmetrical Faults by Distance Relays During Power Swings

Lotfifard, S. Faiz, J. ; Kezunovic, M.