EWAD~E- R3.7.0 Databook 16/07/2014
CSS - Rev. 9.1 Printing date: Code:
Air cooled screw chillers
EWAD~E- E-SS (Standard Efficiency - Standard Noise) - Cooling Capacity from 101 to 413 kW E-SL (Standard Efficiency - Low Noise) - Cooling Capacity from 98 to 398 kW
Performance according to EN14511.
www.eurovent-certification.com www.certiflash.com
FEATURES AND BENEFITS
Low operating cost and extended operating life This chiller range is the result of careful design, aimed to optimize the energy efficiency of the chillers, with the objective of bringing down operating costs and improving installation profitability, effectiveness and economical management. The chillers feature a high efficiency single screw compressor design, large condenser coil surface area for maximum heat transfer and low discharge pressure, advanced technology condenser fans and a ‘shell&tube’ evaporator with low refrigerant pressure drops.
Low operating sound levels Very low sound levels both at full load and part load conditions are achieved by the latest compressor design and by a unique new fan that moves large volume of air at exceptionally low sound levels and by the virtually vibration-free operation.
Infinite capacity control Cooling capacity control is infinitely variable by means of a single screw asymmetric compressor controlled by microprocessor system. Each unit has infinitely variable capacity control from 100% down to 25%. This modulation allows the compressor capacity to exactly match the building cooling load without any leaving evaporator water temperature fluctuation. This chilled water temperature fluctuation is avoided with a stepless control.
With a compressor load step control in fact, the compressor capacity, at partial loads, will be too high or too low compared to the building cooling load. The result is an increase in chiller energy costs, particularly at the part-load conditions at which the chiller operates most of the time.
Units with stepless regulation offer benefits that the units with step regulation are unable to match. The ability to follow the system energy demand at any time and the possibility to provide steady outlet water temperature without deviations from the set-point, are the two points that allow you to understand how the optimum operating conditions of a system can be met through the use of a unit with stepless regulation.
Superior control logic The new MicroTech III controller provides an easy to use control environmental. The control logic is designed to provide maximum efficiency, to continue operation in unusual operating conditions and to provide a history of unit operation. One of the greatest benefits is the easy interface with LonWorks, Bacnet, Ethernet TCP/IP or Modbus communications.
Code requirements – Safety and observant of laws/directives Units are designed and manufactured in accordance with applicable selections of the following:
Construction of pressure vessel Machinery Directive Low Voltage Electromagnetic Compatibility Electrical & Safety codes Manufacturing Quality Stds
97/23/EC (PED) 2006/42/EC 2006/95/EC 2004/108/EC EN 60204–1 / EN 60335-2-40 UNI – EN ISO 9001:2004
Certifications Units are CE marked, complying with European directives in force, concerning manufacturing and safety. On request units can be produced complying with laws in force in non European countries (ASME, GOST, etc.), and with other applications, such as naval (RINA, etc.).
Page 2 of 40
FEATURES AND BENEFITS
Versions This range is available as standard efficiency version: STANDARD EFFICIENCY 10 sizes to cover a range from 98 up to 413 kW with an EER up to 2.98 and an ESEER up to 3.34 (data refer to Standard Noise configuration). The EER (Energy Efficiency Ratio) is the ratio of the Cooling Capacity to the Power Input of the unit. The Power Input includes: the power input for operation of the compressor, the power input of all control and safety devices, the power input for fans. The ESEER (European Seasonal Energy Efficiency Ratio) is a weighed formula enabling to take into account the variation of EER with the load rate and the variation of air inlet condenser temperature. ESEER = A x EER100% + B x EER75% + C x EER50% + D x EER25%
K = Coefficient; T = Air inlet condenser temperature.
Sound configurations Standard and low sound configurations available as follows: STANDARD SOUND Condenser fan rotating at 900 rpm, rubber antivibration under compressor LOW SOUND Condenser fan rotating at 700 rpm, rubber antivibration under compressor, compressor sound enclosure.
Page 3 of 40
GENERAL CHARACTERISTICS
Cabinet and structure The cabinet is made of galvanized steel sheet and painted to provide a high resistance to corrosion. Colour Ivory White (Munsell code 5Y7.5/1) (±RAL7044).The base frame has an eye-hook to lift the unit with ropes for an easy installation. The weight is uniformly distributed along the profiles of the base and this facilitates the arrangement of the unit.
Compressor (Symmetric Single Screw) The compressor is semi-hermetic, single-screw type with gate-rotors made of carbon impregnated engineered composite material. The compressor has one slide managed by the unit microprocessor for infinitely modulating the capacity between 100% to 25%. An integrated high efficiency oil separator maximizes the oil separation and standard start is Wye-Delta (Y-Δ) type.
Compressor (Asymmetric Single Screw) The compressor is semi-hermetic, single-screw type with gate-rotor made with the latest high-strength fibre reinforced star material. The compressor has an asymmetric slide regulation managed by the unit controller for infinitely modulating capacity from 100% to 25%. An integrated high efficiency oil separator maximizes the oil separation and standard start is Wye-Delta (Y-Δ) type.
Refrigerant The compressors have been designed to operate with R-134a, ecological refrigerant with zero ODP (Ozone Depletion Potential) and very low GWP (Global Warming Potential), resulting in low TEWI (Total Equivalent Warming Impact).
Evaporator (Plate Heat Exchanger) The unit is equipped with a direct expansion plate to plate type evaporator. This heat exchanger is made of stainless steel brazed plates and is covered with a 20mm closed cell insulation material. The exchanger is equipped with an electric heater for protection against freezing down to –28°C and evaporator water connections are provided with victaulic kit (as standard). The evaporator has 1 circuit (one compressor) and is manufactured in accordance to PED approval. Flow switch on evaporator available as option and shipped loose(not available for Condensing unit version). Water filter is standard and shipped loose (not available for Condensing unit version).
Condenser The condenser is manufactured with internally enhanced seamless copper tubes arranged in a staggered row pattern and mechanically expanded into lanced and rippled aluminum condenser fins with full fin collars. An integral sub-cooler circuit provides sub-cooling to effectively eliminate liquid flashing and increase cooling capacity without increasing the power input.
Condenser fans (ø 800) The condenser fans are propeller type with high efficiency design blades to maximize performances. The material of the blades is glass reinforced resin and each fan is protected by a guard. Fan motors are internally protected from overtemperature and are IP54.
Electronic expansion valve The unit is equipped with the most advanced electronic expansion valves to achieve precise control of refrigerant mass flow. As today’s system requires improved energy efficiency, tighter temperature control, wider range of operating conditions and incorporate features like remote monitoring and diagnostics, the application of electronic expansion valves becomes mandatory. Electronic expansion valves possess unique features: short opening and closing time, high resolution, positive shut-off function to eliminate use of additional solenoid valve, continuous modulation of mass flow without stress in the refrigerant circuit and corrosion resistance stainless steel body. Electronic expansion valves are typically working with lower ΔP between high and low pressure side, than a thermostatic expansion valve. The electronic expansion valve allows the system to work with low condenser pressure (winter time) without any refrigerant flow problems and with a perfect chilled water leaving temperature control.
Refrigerant circuit Each unit has 1 independent refrigerant circuit and each one includes: • Compressor with integrated oil separator • Refrigerant • Evaporator • Air Cooled Condenser • Electronic expansion valve • Discharge line shut off valve • Liquid line shut off valve • Sight glass with moisture indicator • Filter drier • Charging valves • High pressure switch • High pressure transducers • Low pressure transducers • Oil pressure transducer • Suction temperature sensor
Electrical control panel Power and control are located in the main panel that is manufactured to ensure protection against all weather conditions. The electrical panel is IP54 and (when opening the doors) internally protected against possible accidental contact with live parts. The main panel is fitted with a main switch interlocked door that shuts off power supply when opening.
Power Section The power section includes compressors and fans protection devices, compressors and fans starters and control circuit power supply.
Page 4 of 40
GENERAL CHARACTERISTICS
MicroTech III controller MicroTech III controller is installed as standard; it can be used to modify unit set-points and check control parameters. A built-in display shows chiller operating status plus temperatures and pressures of water, refrigerant and air, programmable values, set-points. A sophisticated software with predictive logic, selects the most energy efficient combination of compressors, EEXV and condenser fans to keep stable operating conditions to maximise chiller energy efficiency and reliability. MicroTech III is able to protect critical components based on external signals from its system (such as motor temperatures, refrigerant gas and oil pressures, correct phase sequence, pressure switches and evaporator). The input coming from the high pressure switch cuts all digital output from the controller in less than 50ms, this is an additional security for the equipment. Fast program cycle (200ms) for a precise monitoring of the system. Floating point calculations supported for increased accuracy in Pressure / Temperature conversions.
Control section - main features Control Section has the following feature. • Management of the compressor stepless capacity and fans modulation. • Chiller enabled to work in partial failure condition. • Full routine operation at condition of: - high ambient temperature value - high thermal load - high evaporator entering water temperature (start-up) • Display of evaporator entering/leaving water temperature. • Display of Outdoor Ambient Temperature. • Display of condensing-evaporating temperature and pressure, suction and discharge superheat for each circuit. • Leaving water evaporator temperature regulation (temperature tolerance = 0,1°C). • Compressor and evaporator pumps hours counter. • Display of Status Safety Devices. • Number of starts and compressor working hours. • Optimized management of compressor load. • Fan management according to condensing pressure. • Re-start in case of power failure (automatic / manual). • Soft Load (optimized management of the compressor load during the start-up). • Start at high evaporator water temperature. • Return Reset (Set Point Reset based on return water temperature). • OAT (Outside Ambient temperature) Reset. • Set point Reset (optional). • Application and system upgrade with commercial SD cards. • Ethernet port for remote or local servicing using standard web browsers. • Two different sets of default parameters could be stored for easy restore.
Safety device / logic for each refrigerant circuit The following devices / logics are available. • High pressure (pressure switch). • High pressure (transducer). • Low pressure (transducer). • Fans circuit breaker. • High compressor discharge temperature. • High motor winding temperature. • Phase Monitor. • Low pressure ratio. • High oil pressure drop. • Low oil pressure. • No pressure change at start.
System security The following securities are available. • Phase monitor. • Low Ambient temperature lock-out. • Freeze protection.
Regulation type Proportional + integral + derivative regulation on the evaporator leaving water output probe.
Page 5 of 40
GENERAL CHARACTERISTICS
MicroTech III MicroTech III built-in terminal has the following features. • 164x44 dots liquid crystal display with white back lighting. Supports Unicode fonts for multi-lingual. • Key-pad consisting of 3 keys. • Push’n’Roll control for an increased usability. • Memory to protect the data. • General faults alarm relays. • Password access to modify the setting. • Application security to prevent application tampering or hardware usability with third party applications. • Service report displaying all running hours and general conditions. • Alarm history memory to allow an easy fault analysis.
Supervising systems (on request)
MicroTech III remote communication MicroTech III is able to communicate to BMS (Building Management System) based on the most common protocols as: • ModbusRTU • LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology. • BacNet BTP certifief over IP and MS/TP (class 4) (Native). • Ethernet TCP/IP.
Page 6 of 40
OPTIONS
Standard Options (supplied on basic unit) Wye-Delta compressor starter (Y-D) - For low inrush current and reduced starting torque
Double setpoint - Dual leaving water temperature setpoints.
Phase monitor - Device that monitors input voltage and stops the chiller in case of phase loss or wrong phase sequence.
Evaporator electric heater - Electric heater (controlled by a thermostat) to protect the evaporator from freezing down to -28°C ambient temperature, providing the power supply is on.
Electronic expansion valve
Discharge line shut-off valve - Installed on the discharge port of the compressor to facilitate maintenance operation.
Suction line shut-off valve - Installed on the suction port of the compressor to facilitate maintenance operation.
Ambient outside temperature sensor and setpoint reset
Hour run meter
General fault contactor
Setpoint reset, Demand limit and Alarm from external device - Setpoint Reset: The leaving water temperature set-point can be overwritten with an external 4-20mA, through the ambient temperature, or through the evaporator water temperature ΔT. Demand Limit: Chiller capacity can be limited through an external 4-20mA signal or via network. Alarm from external device: The unit controller is able to receive an external alarm signal. The user can decide whether this alarm signal will stop the unit or not.
Fans circuit breakers - Safety devices that, added to the standard protection devices, protect fan motors against overload and overcurrent.
Main switch interlock door
Options (on request) MECHANICAL
Total heat recovery - Plate to plate heat exchangers for hot water production.
Partial heat recovery - Plate to plate heat exchangers for hot water production.
Brine version - Allows the unit to operate down to -15°C leaving liquid temperature (antifreeze required). Reccomended below +4°C
20mm evaporator insulation - The external shell is covered with a 20mm closed cell insulation material.
Condenser coil guards
Cu-Cu condenser coil - To give better protection against corrosion by aggressive environments.
Cu-Cu-Sn condenser coil - To give better protection against corrosion in aggressive environments and by salty air.
Alucoat fins coil - Fins are protected by a special acrylic paint with a high resistance to corrosion.
High pressure side manometers
Low pressure side manometers
One centrifugal pump (low lift) - Hydronic kit consists of: single direct driven centrifugal pump, water filling system with pressure gauge, safety valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and wired to the control panel. The pipe and pump are protected from freezing with an additional electrical heater.
One centrifugal pump (high lift) Hydronic kit consists of: single direct driven centrifugal pump, water filling system with pressure gauge, safety valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and wired to the control panel. The pipe and pump are protected from freezing with an additional electrical heater.
Two centrifugal pump (low lift) - Hydronic kit consists of: twin direct driven centrifugal pumps, water filling system with pressure gauge, safety valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and wired to the control panel. The pipe and pumps are protected from freezing with an additional electrical heater.
Two centrifugal pump (high lift) Hydronic kit consists of: twin direct driven centrifugal pumps, water filling system with pressure gauge, safety valve, drain valve. The motor pump is protected by a circuit breaker installed in control panel. The kit is assembled and wired to the control panel. The pipe and pumps are protected from freezing with an additional electrical heater.
Double pressure relief valve with diverter
Page 7 of 40
OPTIONS
ELECTRICAL / CONTROL
Soft starter - Electronic starting device to reduce the mechanical stress during compressor start-up
Compressor thermal overload relays - Safety electronic devices that, added to the standard protection devices, protect compressor motors against overload and current unbalance.
Under / Over voltage control - Electronic device that monitors and displays input voltage, and stops the chiller in case of phase loss, wrong phase sequence, or voltage exceeding minimum and maximum allowed values.
Energy meter - Device installed inside the control box that displays all chiller electrical power parameters at line input such as line voltage and phase current, input active and reactive power, active and reactive energy. An integrated RS485 module allows a Modbus communication to an external BMS.
Capacitors for power factor correction - Devices that increase the power factor of the unit. The capacitors are “dry” self-regenerating type with over pressure disconnecting safety device insulated with a no toxic dielectric mix without PCB or PCT.
Current limit - To limit maximum absorbed current of the unit whenever is required
Speedtrol (fan speed control device - ON/OFF - up to -18°C) - Continuous fan speed regulation on the first fan (VFD driven) of each circuit. It allows unit operation down to -18ºC.
Evaporator flow switch - Supplied separately to be wired and installed on the evaporator water piping (by the customer).
Compressors circuit breakers Safety devices that include in a single device all safety functions otherwise provided by standard fuses and optional thermal relays, such as protection against overcurrent, overload, current unbalance.
Fans speed regulation (+ fan silent mode) - Continuous fan speed regulation of all fans (VFD driven) for improved sound level of the unit during low ambient temperature operation. At very low temperatures, all fans except the first are switched off thus allowing unit operation down to -18°C.
INSTALLATION
Rubber anti vibration mounts - Supplied separately, these are positioned under the base of the unit during installation. Ideal to reduce the vibrations when the unit is floor mounted.
Spring anti vibration mounts - Supplied separately, these are positioned under the base of the unit during installation. Ideal for dampening vibrations for installation on roofs and metallic structures.
External tank without cabinet (500 L)
External tank without cabinet (1000 L)
External tank with cabinet (500 L)
External tank with cabinet (1000 L)
OTHER
Container Kit
Witness test
Acoustic test
Transport kit
Page 8 of 40
NOMENCLATURE
E W A D 1 0 0 E - S S
= Air cooled chiller cool. only = Air cooled chiller heat pump = Air cooled condensing unit
EWA EWY ERA
Machine type
Refrigerant D P Q
= R-134a = R-407C = R-410A
Capacity class in kW (Cooling) Always 3-digit code
Model series A, B, …..
Inverter - = Non inverter
Efficiency level S = Standard Efficiency
Sound level
S L
= Standard sound = Low sound
Page 9 of 40
TECHNICAL SPECIFICATIONS
EWAD E-SS 120 140 160 180 210 310 260 100 MODEL
Capacity - Cooling (1) kW 306 255 213 183 163 121 101 138 Capacity control - Type --- Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Capacity control - Minimum capacity % 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 Unit power input - Cooling (1) kW 112 87,8 72,4 69,0 60,9 47,5 39,1 53,9 EER (1) --- 2,73 2,90 2,95 2,64 2,67 2,54 2,58 2,55 ESEER --- 2,96 3,08 2,93 2,73 2,84 2,83 2,84 2,66 IPLV --- 3,56 3,68 3,48 3,25 3,13 3,25 3,36 2,98
CASING Colour (2) --- IW IW IW IW IW IW IW IW Material (2) --- GPSS GPSS GPSS GPSS GPSS GPSS GPSS GPSS
DIMENSIONS Height mm 2223 2223 2273 2273 2273 2273 2273 2273 Width mm 2236 2236 1292 1292 1292 1292 1292 1292 Length mm 3070 3070 3965 3965 3065 2165 2165 3065
WEIGHT Unit Weight kg 2919 2919 2086 2086 1861 1684 1684 1861 Operating Weight kg 2963 2963 2116 2116 1881 1699 1699 1881
WATER HEAT EXCHANGER Type (3) --- PHE PHE PHE PHE PHE PHE PHE PHE Water Volume l 30 25 30 24 20 15 12 17 Nominal water flow rate - Cooling l/s 14,6 12,2 10,2 8,7 7,8 5,8 4,8 6,6 Nominal Water pressure drop - Cooling kPa 48 47 21 22 24 25 24 23 Insulation material (4) CC CC CC CC CC CC CC CC
AIR HEAT EXCHANGER Type (5) --- HFP HFP HFP HFP HFP HFP HFP HFP
FAN Type (6) --- DPT DPT DPT DPT DPT DPT DPT DPT Drive (7) --- DOL DOL DOL DOL DOL DOL DOL DOL Diameter mm 800 800 800 800 800 800 800 800 Nominal air flow l/s 32772 32772 21153 21848 15865 10576 10924 16386 Quantity No. 6 6 4 4 3 2 2 3 Speed rpm 900 900 900 900 900 900 900 900 Motor input kW 10,5 10,5 7,0 7,0 5,3 3,5 3,5 5,3
COMPRESSOR Type --- Asymm
Single Screw
Asymm Single Screw
Single Screw
Single Screw
Single Screw
Single Screw
Single Screw
Single Screw
Oil charge l 19 16 13 13 13 13 13 13 Quantity No. 1 1 1 1 1 1 1 1
SOUND LEVEL Sound Power - Cooling dB(A) 94 94 94 93 92 92 92 92 Sound Pressure - Cooling (8) dB(A) 75 75 75 74 74 74 74 74
REFRIGERANT CIRCUIT Refrigerant type --- R134a R134a R134a R134a R134a R134a R134a R134a Refrigerant charge kg 46 46 39 34 28 21 18 23 N. of circuits No. 1 1 1 1 1 1 1 1
PIPING CONNECTIONS Evaporator water inlet/outlet 3 " 3 " 3 " 3 " 3 " 3 " 3 " 3 "
Fluid: Water (1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12,0/7,0°C; ambient 35,0°C, unit at full load operation; (2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube (4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler (6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless (8) The values are according to ISO 3744 and are referred to: evaporator 12/7°C, ambient 35°C, full load operation.
Page 10 of 40
TECHNICAL SPECIFICATIONS
EWAD E-SS 410 360 MODEL
Capacity - Cooling (1) kW 411 359 Capacity control - Type --- Stepless Stepless Capacity control - Minimum capacity % 25,0 25,0 Unit power input - Cooling (1) kW 147 134 EER (1) --- 2,80 2,67 ESEER --- 3,24 3,13 IPLV --- 3,65 3,61
CASING Colour (2) --- IW IW Material (2) --- GPSS GPSS
DIMENSIONS Height mm 2223 2223 Width mm 2236 2236 Length mm 3070 3070
WEIGHT Unit Weight kg 2919 2919 Operating Weight kg 2963 2963
WATER HEAT EXCHANGER Type (3) --- PHE PHE Water Volume l 44 36 Nominal water flow rate - Cooling l/s 19,7 17,2 Nominal Water pressure drop - Cooling kPa 45 48 Insulation material (4) CC CC
AIR HEAT EXCHANGER Type (5) --- HFP HFP
FAN Type (6) --- DPT DPT Drive (7) --- DOL DOL Diameter mm 800 800 Nominal air flow l/s 31729 31729 Quantity No. 6 6 Speed rpm 900 900 Motor input kW 10,5 10,5
COMPRESSOR Type --- Asymm
Single Screw
Asymm Single Screw
Oil charge l 19 19 Quantity No. 1 1
SOUND LEVEL Sound Power - Cooling dB(A) 95 94 Sound Pressure - Cooling (8) dB(A) 76 75
REFRIGERANT CIRCUIT Refrigerant type --- R134a R134a Refrigerant charge kg 74 56 N. of circuits No. 1 1
PIPING CONNECTIONS Evaporator water inlet/outlet 3 " 3 "
Fluid: Water (1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12,0/7,0°C; ambient 35,0°C, unit at full load operation; (2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube (4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler (6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless (8) The values are according to ISO 3744 and are referred to: evaporator 12/7°C, ambient 35°C, full load operation.
Page 11 of 40
TECHNICAL SPECIFICATIONS
EWAD E-SL 120 130 160 180 210 300 250 100 MODEL
Capacity - Cooling (1) kW 295 248 208 177 157 116 97,6 134 Capacity control - Type --- Stepless Stepless Stepless Stepless Stepless Stepless Stepless Stepless Capacity control - Minimum capacity % 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 Unit power input - Cooling (1) kW 111 85,4 72,8 68,3 60,8 48,3 39,2 53,4 EER (1) --- 2,65 2,90 2,86 2,59 2,57 2,39 2,49 2,50 ESEER --- 3,31 3,44 3,22 2,98 2,91 2,88 2,92 2,76 IPLV --- 3,75 3,86 3,48 3,28 3,46 3,21 3,32 3,30
CASING Colour (2) --- IW IW IW IW IW IW IW IW Material (2) --- GPSS GPSS GPSS GPSS GPSS GPSS GPSS GPSS
DIMENSIONS Height mm 2223 2223 2273 2273 2273 2273 2273 2273 Width mm 2236 2236 1292 1292 1292 1292 1292 1292 Length mm 3070 3070 3965 3965 3065 2165 2165 3065
WEIGHT Unit Weight kg 3029 3029 2186 2186 1961 1784 1784 1961 Operating Weight kg 3073 3073 2216 2216 1981 1799 1799 1981
WATER HEAT EXCHANGER Type (3) --- PHE PHE PHE PHE PHE PHE PHE PHE Water Volume l 30 25 30 24 20 15 12 17 Nominal water flow rate - Cooling l/s 14,1 11,9 10,0 8,4 7,5 5,5 4,7 6,4 Nominal Water pressure drop - Cooling kPa 45 45 20 21 23 23 23 22 Insulation material (4) CC CC CC CC CC CC CC CC
AIR HEAT EXCHANGER Type (5) --- HFP HFP HFP HFP HFP HFP HFP HFP
FAN Type (6) --- DPT DPT DPT DPT DPT DPT DPT DPT Drive (7) --- DOL DOL DOL DOL DOL DOL DOL DOL Diameter mm 800 800 800 800 800 800 800 800 Nominal air flow l/s 25120 25120 16288 16747 12216 8144 8373 12560 Quantity No. 6 6 4 4 3 2 2 3 Speed rpm 700 700 700 700 700 700 700 700 Motor input kW 4,7 4,7 3,1 3,1 2,4 1,6 1,6 2,4
COMPRESSOR Type --- Asymm
Single Screw
Asymm Single Screw
Single Screw
Single Screw
Single Screw
Single Screw
Single Screw
Single Screw
Oil charge l 19 16 13 13 13 13 13 13 Quantity No. 1 1 1 1 1 1 1 1
SOUND LEVEL Sound Power - Cooling dB(A) 92 92 92 90 90 89 89 90 Sound Pressure - Cooling (8) dB(A) 73 73 73 71 71 71 71 71
REFRIGERANT CIRCUIT Refrigerant type --- R134a R134a R134a R134a R134a R134a R134a R134a Refrigerant charge kg 46 46 39 34 28 21 18 23 N. of circuits No. 1 1 1 1 1 1 1 1
PIPING CONNECTIONS Evaporator water inlet/outlet 3 " 3 " 3 " 3 " 3 " 3 " 3 " 3 "
Fluid: Water (1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12,0/7,0°C; ambient 35,0°C, unit at full load operation; (2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube (4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler (6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless (8) The values are according to ISO 3744 and are referred to: evaporator 12/7°C, ambient 35°C, full load operation.
Page 12 of 40
TECHNICAL SPECIFICATIONS
EWAD E-SL 400 350 MODEL
Capacity - Cooling (1) kW 397 344 Capacity control - Type --- Stepless Stepless Capacity control - Minimum capacity % 25,0 25,0 Unit power input - Cooling (1) kW 152 135 EER (1) --- 2,62 2,55 ESEER --- 3,35 3,24 IPLV --- 3,76 3,63
CASING Colour (2) --- IW IW Material (2) --- GPSS GPSS
DIMENSIONS Height mm 2223 2223 Width mm 2236 2236 Length mm 3070 3070
WEIGHT Unit Weight kg 3029 3029 Operating Weight kg 3073 3073
WATER HEAT EXCHANGER Type (3) --- PHE PHE Water Volume l 44 36 Nominal water flow rate - Cooling l/s 19,0 16,5 Nominal Water pressure drop - Cooling kPa 42 44 Insulation material (4) CC CC
AIR HEAT EXCHANGER Type (5) --- HFP HFP
FAN Type (6) --- DPT DPT Drive (7) --- DOL DOL Diameter mm 800 800 Nominal air flow l/s 24432 24432 Quantity No. 6 6 Speed rpm 700 700 Motor input kW 4,7 4,7
COMPRESSOR Type --- Asymm
Single Screw
Asymm Single Screw
Oil charge l 19 19 Quantity No. 1 1
SOUND LEVEL Sound Power - Cooling dB(A) 93 92 Sound Pressure - Cooling (8) dB(A) 74 73
REFRIGERANT CIRCUIT Refrigerant type --- R134a R134a Refrigerant charge kg 74 56 N. of circuits No. 1 1
PIPING CONNECTIONS Evaporator water inlet/outlet 3 " 3 "
Fluid: Water (1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12,0/7,0°C; ambient 35,0°C, unit at full load operation; (2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube (4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler (6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless (8) The values are according to ISO 3744 and are referred to: evaporator 12/7°C, ambient 35°C, full load operation.
Page 13 of 40
ELECTRICAL SPECIFICATIONS
EWAD E-SS 120 140 160 180 210 310 260 100 MODEL
POWER SUPPLY Phases Nr 3 3 3 3 3 3 3 3 Frequency Hz 50 50 50 50 50 50 50 50 Voltage V 400 400 400 400 400 400 400 400 Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10% -10% -10% Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10%
UNIT Maximum starting current A 151 151 195 195 288 288 330 410 Nominal running current cooling A 67 81 92 102 116 121 148 185 Maximum running current A 86 103 119 132 157 164 198 242 Maximum current for wires sizing A 94 112 130 144 171 179 215 264
FANS Nominal running current cooling A 8 8 12 12 16 16 24 24
COMPRESSORS Phases Nr 3 3 3 3 3 3 3 3 Voltage V 400 400 400 400 400 400 400 400 Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10% -10% -10% Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10% Maximum running current A 78 95 107 120 141 148 174 218 Starting method --- Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ
EWAD E-SS 410 360 MODEL
POWER SUPPLY Phases Nr 3 3 Frequency Hz 50 50 Voltage V 400 400 Voltage tolerance Minimum % -10% -10% Voltage tolerance Maximum % +10% +10%
UNIT Maximum starting current A 410 410 Nominal running current cooling A 220 241 Maximum running current A 284 298 Maximum current for wires sizing A 310 326
FANS Nominal running current cooling A 24 24
COMPRESSORS Phases Nr 3 3 Voltage V 400 400 Voltage tolerance Minimum % -10% -10% Voltage tolerance Maximum % +10% +10% Maximum running current A 260 274 Starting method --- Y-Δ Y-Δ
Fluid: Water Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for the circuit at 75%. Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current. Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current Maximum unit current for wires sizing is based on minimum allowed voltage Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
Page 14 of 40
ELECTRICAL SPECIFICATIONS
EWAD E-SL 120 130 160 180 210 300 250 100 MODEL
POWER SUPPLY Phases Nr 3 3 3 3 3 3 3 3 Frequency Hz 50 50 50 50 50 50 50 50 Voltage V 400 400 400 400 400 400 400 400 Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10% -10% -10% Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10%
UNIT Maximum starting current A 151 151 195 195 288 288 330 410 Nominal running current cooling A 67 83 92 103 116 122 144 184 Maximum running current A 83 100 115 128 151 158 189 234 Maximum current for wires sizing A 91 109 126 140 165 173 207 256
FANS Nominal running current cooling A 5 5 8 8 10 10 16 16
COMPRESSORS Phases Nr 3 3 3 3 3 3 3 3 Voltage V 400 400 400 400 400 400 400 400 Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10% -10% -10% Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10% Maximum running current A 78 95 107 120 141 148 174 218 Starting method --- Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ Y-Δ
EWAD E-SL 400 350 MODEL
POWER SUPPLY Phases Nr 3 3 Frequency Hz 50 50 Voltage V 400 400 Voltage tolerance Minimum % -10% -10% Voltage tolerance Maximum % +10% +10%
UNIT Maximum starting current A 410 410 Nominal running current cooling A 223 249 Maximum running current A 276 290 Maximum current for wires sizing A 302 317
FANS Nominal running current cooling A 16 16
COMPRESSORS Phases Nr 3 3 Voltage V 400 400 Voltage tolerance Minimum % -10% -10% Voltage tolerance Maximum % +10% +10% Maximum running current A 260 274 Starting method --- Y-Δ Y-Δ
Fluid: Water Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for the circuit at 75%. Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current. Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current Maximum unit current for wires sizing is based on minimum allowed voltage Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
Page 15 of 40
SOUND LEVELS
EWAD E-SL Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa) Power
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB(A) dB(A) MODEL
100 68,3 72,8 59,2 50,5 44,8 71,0 66,4 89,0 73,0 61,8 120 68,3 72,8 59,2 50,5 44,8 71,0 66,4 89,0 73,0 61,8 130 68,5 73,0 59,4 50,7 45,0 71,2 66,6 89,8 73,2 62,0 160 68,5 73,0 59,4 50,7 45,0 71,2 66,6 89,8 73,2 62,0 180 68,7 73,2 59,6 50,9 45,2 71,4 66,8 90,5 73,4 62,2 210 69,9 74,4 60,8 52,1 46,4 72,6 68,0 91,7 74,6 63,4 250 69,8 74,3 60,7 52,0 46,3 72,5 67,9 91,7 74,5 63,3 300 70,1 74,6 61,0 52,3 46,6 72,8 68,2 92,0 74,8 63,6 350 70,1 74,6 61,0 52,3 46,6 72,8 68,2 92,0 74,8 63,6 400 70,8 75,3 61,7 53,0 47,3 73,5 68,9 92,7 75,5 64,3
EWAD E-SS Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa) Power
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dB(A) dB(A) MODEL
100 70,8 75,3 61,7 53,0 47,3 73,5 68,9 91,5 75,5 64,3 120 70,8 75,3 61,7 53,0 47,3 73,5 68,9 91,5 75,5 64,3 140 71,0 75,5 61,9 53,2 47,5 73,7 69,1 92,3 75,7 64,5 160 71,0 75,5 61,9 53,2 47,5 73,7 69,1 92,3 75,7 64,5 180 71,2 75,7 62,1 53,4 47,7 73,9 69,3 93,0 75,9 64,7 210 72,4 76,9 63,3 54,6 48,9 75,1 70,5 94,2 77,1 65,9 260 72,3 76,8 63,2 54,5 48,8 75,0 70,4 94,2 77,0 65,8 310 72,6 77,1 63,5 54,8 49,1 75,3 70,7 94,5 77,3 66,1 360 72,6 77,1 63,5 54,8 49,1 75,3 70,7 94,5 77,3 66,1 410 73,3 77,8 64,2 55,5 49,8 76,0 71,4 95,2 78,0 66,8
Page 16 of 40
SOUND LEVEL AT DISTANCE
EWAD E-SL
SOUND PRESSURE LEVEL FOR DIFFERENT DISTANCES (dB(A))
50 m 25 m 20 m 15 m 10 m 5 m 1 m MODEL
100 54,0 49,8 57,1 51,6 62,2 71,0 44,0 120 54,0 49,8 57,1 51,6 62,2 71,0 44,0 130 54,6 50,5 57,8 52,3 62,8 71,2 44,8 160 54,6 50,5 57,8 52,3 62,8 71,2 44,8 180 55,3 51,2 58,4 53,0 63,3 71,4 45,4 210 56,5 52,4 59,6 54,2 64,5 72,6 46,6 250 56,4 52,4 59,6 54,2 64,4 72,5 46,6 300 56,7 52,7 59,9 54,5 64,7 72,8 46,9 350 56,7 52,7 59,9 54,5 64,7 72,8 46,9 400 57,4 53,4 60,6 55,2 65,4 73,5 47,6
EWAD E-SS
SOUND PRESSURE LEVEL FOR DIFFERENT DISTANCES (dB(A))
50 m 25 m 20 m 15 m 10 m 5 m 1 m MODEL
100 56,5 52,3 59,6 54,1 64,7 73,5 46,5 120 56,5 52,3 59,6 54,1 64,7 73,5 46,5 140 57,1 53,0 60,3 54,8 65,3 73,7 47,3 160 57,1 53,0 60,3 54,8 65,3 73,7 47,3 180 57,8 53,7 60,9 55,5 65,8 73,9 47,9 210 59,0 54,9 62,1 56,7 67,0 75,1 49,1 260 58,9 54,9 62,1 56,7 66,9 75,0 49,1 310 59,2 55,2 62,4 57,0 67,2 75,3 49,4 360 59,2 55,2 62,4 57,0 67,2 75,3 49,4 410 59,9 55,9 63,1 57,7 67,9 76,0 50,1
Fluid: Water Note: The values are according to ISO 3744 and are referred to: evaporator 12/7° C, air ambient 35°C, full load operation
Page 17 of 40
OPERATING LIMITS
Operating Limits
Note The above graphic represents a guidelines about the operating limits of the range. Please refer to Chiller Selection Software (CSS) for real operating limits working conditions for each size.
Legend: ELWT = Evaporator Leaving Water Temperature (°C) CIAT = Condenser Inlet Air Temperature (°C)
Ref.: A = Unit can only work in 'ICE mode' B = Operation with Glycol (below 4°C Evap LWT) C = Fan speed modulation required (below 18°C Condens. Air Temp. for less than 3 fans units) D = Fan speed modulation required (below 10°C Condens. Air Temp. for 3 or more fans units) E = Speedtroll required (below -10°C Condens. Air Temp.)
Table 1 - Water heat exchanger - Minimum and maximum water Δt
Legend: A = Max evaporator water Δt B = Min evaporator water Δt
Table 2 - Water heat exchanger - Fouling factors
Page 18 of 40
OPERATING LIMITS
Legend: A = Fouling factors (m2 °C / kW) B = Cooling capacity correction factor C = Power input correction factor D = EER correction factor
Table 3 - Air heat exchanger - Altitude correction factors
Legend: A = Elevation above sea level (m) B = Barometric pressure (mbar) C = Cooling capacity correction factor D = Power input correction factor - Maximum operating altitude is 2000 m above sea level - Contact factory in case the unit has to be installed at altitudes between 1000 and 2000 m above sea level
Table 4 - Minimum glycol percentage for low air ambient temperature
Legend: AAT = Air Ambient Temperature (°C) (2) A = Ethylene glycol (%) (1) B = Propylene glycol (%) (1) (1) Minimum glycol percentage to prevent freezing of water circuit at indicated air ambient temperature (2) Air ambient temperature do exceed the operating limits of the unit, a protection of water circuit may be needed in winter season at non-working conditions.
Table 5.1 - Available fan static pressure correction factors
The above data are referred to: - Fan 800 mm diameter - Fan speed 890 rpm or 900 rpm Legend: A = External Static Pressure (Pa) B = Cooling Capacity (kW) Correction factor C = Compressor Power Input (kW) Correction factor D = Reduction of Maximum Condenser Inlet Air Temperature (°C)
Table 5.2 - Available fan static pressure correction factors
Page 19 of 40
OPERATING LIMITS
The above data are referred to: - Fan 800 mm diameter - Fan speed 700 rpm or 705 rpm Legend: A = External Static Pressure (Pa) B = Cooling Capacity (kW) Correction factor C = Compressor Power Input (kW) Correction factor D = Reduction of Maximum Condenser Inlet Air Temperature (°C)
Water content in cooling circuits The cooled water distribution circuits should have minimum water content to avoid excessive compressors start and stop. In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressor sump and simultaneously there is a rise in the temperature of the compressor motor’s stator due to the inrush current during the start-up. To prevent damage to the compressors, have been envisaged the application of a device to limit frequent stops and restarts. During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore ensure that the overall water content allows a more constant functioning of the unit and consequently greater environmental comfort. The minimum water content per unit should be calculated with a certain approximation using this simplified formula:
For 1 compressor unit M (liters) = (0.94 x ΔT(°C) + 5.87) x P(kW)
where: M = minimum water content per unit expressed in litres P = cooling capacity of the unit expressed in kW ΔT = evaporator entering / leaving water temperature difference expressed in °C This formula is valid for standard microprocessor parameters. For more accurate determination of quantity of water, it is advisable to contact the designer of the plant.
Water charge, flow and quality
Page 20 of 40
COOLING PERFORMANCE
EWAD E-SS 100 120
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 104 99,7 94,9 89,8 84,3 80,7 125 120 114 107 101 93,1 PI kW 32,3 35,0 38,1 41,4 44,9 47,1 39,1 42,6 46,3 50,3 54,6 54,9 qw l/s 5,0 4,8 4,5 4,3 4,0 3,9 6,0 5,7 5,4 5,1 4,8 4,4 dpw kPa 26 24 22 20 18 16 26 24 22 20 18 15
CC kW 7 110 106 101 95,4 89,7 85,0 132 127 121 114 107 96,0 PI kW 33,2 36,0 39,1 42,4 45,9 47,4 40,2 43,7 47,5 51,6 55,9 53,6 qw l/s 5,3 5,1 4,8 4,6 4,3 4,1 6,3 6,1 5,8 5,5 5,1 4,6 dpw kPa 29 27 24 22 20 18 29 27 25 22 20 16
CC kW 9 116 111 106 101 95,3 86,9 139 134 127 121 114 97,7 PI kW 34,1 36,9 40,1 43,4 47,0 46,0 41,4 44,9 48,7 52,9 57,3 51,8 qw l/s 5,6 5,3 5,1 4,8 4,6 4,2 6,7 6,4 6,1 5,8 5,4 4,7 dpw kPa 32 29 27 25 22 19 32 30 27 25 22 17
CC kW 11 122 118 112 107 101 89,0 147 141 134 128 118 99,7 PI kW 35,1 38,0 41,1 44,5 48,1 44,8 42,6 46,2 50,0 54,2 57,2 50,4 qw l/s 5,9 5,6 5,4 5,1 4,8 4,3 7,0 6,8 6,4 6,1 5,7 4,8 dpw kPa 35 32 30 27 25 20 35 33 30 27 24 18
CC kW 13 129 124 118 113 107 90,7 154 148 141 135 121 102 PI kW 36,1 39,0 42,2 45,6 49,3 43,7 43,8 47,5 51,4 55,6 55,9 49,5 qw l/s 6,2 5,9 5,7 5,4 5,1 4,4 7,4 7,1 6,8 6,5 5,8 4,9 dpw kPa 38 36 33 30 27 20 39 36 33 30 25 18
CC kW 15 135 130 125 119 109 92,9 162 155 149 142 123 104 PI kW 37,1 40,1 43,3 46,7 48,3 42,9 45,1 48,8 52,8 57,1 54,6 48,5 qw l/s 6,5 6,3 6,0 5,7 5,2 4,5 7,8 7,5 7,1 6,8 5,9 5,0 dpw kPa 42 39 36 33 28 21 42 39 36 33 26 19
140 160
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 142 136 130 123 115 110 168 161 153 145 136 130 PI kW 44,8 48,5 52,6 57,2 62,2 65,6 50,2 54,6 59,4 64,5 70,1 73,6 qw l/s 6,8 6,5 6,2 5,9 5,5 5,3 8,0 7,7 7,3 6,9 6,5 6,2 dpw kPa 25 23 21 19 17 16 26 24 22 20 18 16
CC kW 7 150 144 138 130 123 118 177 170 163 154 145 139 PI kW 45,9 49,8 53,9 58,5 63,7 67,1 51,6 56,0 60,9 66,1 71,7 75,2 qw l/s 7,2 6,9 6,6 6,2 5,9 5,6 8,5 8,1 7,8 7,4 6,9 6,7 dpw kPa 27 25 23 21 19 18 28 26 24 22 20 18
CC kW 9 158 152 146 138 131 126 187 179 172 163 154 146 PI kW 47,1 51,0 55,2 59,9 65,2 68,6 52,9 57,5 62,4 67,7 73,3 75,7 qw l/s 7,6 7,3 7,0 6,6 6,3 6,0 9,0 8,6 8,2 7,8 7,4 7,0 dpw kPa 30 28 26 24 21 20 31 29 27 25 22 20
CC kW 11 167 161 154 146 138 131 197 189 181 172 163 149 PI kW 48,3 52,3 56,6 61,4 66,7 68,4 54,4 58,9 63,9 69,3 75,1 73,3 qw l/s 8,0 7,7 7,4 7,0 6,6 6,3 9,4 9,1 8,7 8,3 7,8 7,1 dpw kPa 33 31 28 26 24 21 34 32 30 27 25 21
CC kW 13 176 169 162 154 146 134 207 199 191 182 172 152 PI kW 49,6 53,6 58,0 62,8 68,3 66,9 55,9 60,5 65,5 70,9 76,8 71,6 qw l/s 8,4 8,1 7,8 7,4 7,0 6,4 9,9 9,5 9,1 8,7 8,3 7,3 dpw kPa 36 34 31 29 26 22 38 35 32 30 27 22
CC kW 15 184 178 170 163 154 137 217 209 200 191 182 155 PI kW 51,0 55,0 59,4 64,3 69,9 65,2 57,4 62,1 67,1 72,6 78,6 69,7 qw l/s 8,9 8,5 8,2 7,8 7,4 6,6 10,4 10,0 9,6 9,2 8,7 7,4 dpw kPa 40 37 34 32 29 23 41 38 36 33 30 22
Page 22 of 40
COOLING PERFORMANCE
EWAD E-SS 180 210
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 189 181 172 161 148 140 212 208 202 193 181 172 PI kW 57,2 62,0 67,4 73,5 80,5 85,1 58,7 64,5 70,8 77,9 86,1 91,5 qw l/s 9,0 8,6 8,2 7,7 7,1 6,7 10,1 9,9 9,7 9,2 8,7 8,2 dpw kPa 24 22 20 18 15 14 21 20 19 18 16 14
CC kW 7 200 192 183 171 158 149 223 220 213 204 192 182 PI kW 58,6 63,6 69,0 75,3 82,4 87,0 60,0 65,9 72,4 79,6 87,9 93,4 qw l/s 9,5 9,2 8,7 8,2 7,6 7,1 10,7 10,5 10,2 9,8 9,2 8,7 dpw kPa 26 25 22 20 17 16 23 22 21 20 18 16
CC kW 9 210 202 193 182 168 158 235 231 225 215 202 192 PI kW 60,1 65,1 70,7 77,1 84,3 89,1 61,4 67,4 74,0 81,4 89,8 95,4 qw l/s 10,1 9,7 9,2 8,7 8,0 7,6 11,2 11,1 10,8 10,3 9,7 9,2 dpw kPa 29 27 25 22 19 17 25 25 23 22 19 18
CC kW 11 221 213 203 192 177 167 247 243 236 226 213 200 PI kW 61,6 66,7 72,4 79,0 86,3 91,2 62,9 69,0 75,7 83,2 91,8 95,8 qw l/s 10,6 10,2 9,7 9,2 8,5 8,0 11,8 11,6 11,3 10,9 10,2 9,6 dpw kPa 32 30 27 25 21 19 28 27 26 24 21 19
CC kW 13 233 224 214 202 187 174 259 255 248 238 223 204 PI kW 63,2 68,4 74,2 80,9 88,5 91,0 64,4 70,6 77,4 85,1 93,8 93,2 qw l/s 11,2 10,7 10,3 9,7 9,0 8,3 12,4 12,2 11,9 11,4 10,7 9,8 dpw kPa 35 33 30 27 24 21 30 29 28 26 23 20
CC kW 15 244 235 224 212 197 178 271 267 259 249 234 207 PI kW 64,9 70,1 76,1 82,8 90,6 88,9 66,0 72,3 79,2 87,0 95,9 90,5 qw l/s 11,7 11,3 10,8 10,2 9,4 8,5 13,0 12,8 12,5 11,9 11,2 9,9 dpw kPa 38 36 33 30 26 22 33 32 30 28 25 20
260 310
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 262 252 240 226 211 200 317 304 289 271 251 237 PI kW 73,5 79,2 85,8 93,5 102 108 94,3 101 109 117 125 131 qw l/s 12,6 12,0 11,5 10,8 10,1 9,6 15,2 14,5 13,8 13,0 12,0 11,3 dpw kPa 50 46 42 38 33 30 51 47 43 38 33 30
CC kW 7 278 267 255 241 225 213 335 321 306 288 266 247 PI kW 75,5 81,3 87,8 95,4 104 110 97,2 104 112 120 129 133 qw l/s 13,3 12,8 12,2 11,5 10,8 10,2 16,1 15,4 14,6 13,8 12,7 11,8 dpw kPa 55 51 47 43 38 34 56 52 48 43 37 32
CC kW 9 294 282 270 256 239 227 354 339 323 304 282 253 PI kW 77,7 83,4 89,9 97,5 106 112 100 108 115 124 133 131 qw l/s 14,1 13,5 12,9 12,3 11,4 10,9 17,0 16,3 15,5 14,6 13,5 12,1 dpw kPa 61 57 52 48 42 38 62 57 53 47 41 34
CC kW 11 310 298 285 270 253 241 373 357 340 321 299 259 PI kW 79,9 85,6 92,1 99,7 108 114 103 111 119 128 137 129 qw l/s 14,9 14,3 13,7 13,0 12,2 11,6 17,9 17,2 16,3 15,4 14,3 12,4 dpw kPa 67 63 58 53 47 43 68 63 58 52 46 35
CC kW 13 327 314 301 285 268 256 392 376 358 338 312 264 PI kW 82,2 87,9 94,5 102 111 117 106 114 122 132 140 127 qw l/s 15,7 15,1 14,5 13,7 12,9 12,3 18,9 18,1 17,2 16,2 15,0 12,7 dpw kPa 74 69 64 58 52 48 75 69 64 57 49 37
CC kW 15 344 331 317 301 283 265 412 395 376 355 318 271 PI kW 84,7 90,4 96,9 104 113 117 110 118 126 135 138 125 qw l/s 16,6 15,9 15,2 14,5 13,6 12,8 19,8 19,0 18,1 17,1 15,3 13,0 dpw kPa 81 76 70 64 57 51 82 76 70 63 51 39
Page 23 of 40
COOLING PERFORMANCE
EWAD E-SS 360 410
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 373 357 339 317 293 267 416 405 391 372 338 281 PI kW 113 121 130 140 150 152 121 131 142 155 164 146 qw l/s 17,9 17,1 16,2 15,2 14,0 12,8 19,9 19,4 18,7 17,8 16,2 13,4 dpw kPa 52 48 43 38 33 28 46 43 41 37 31 22
CC kW 7 394 377 359 337 311 275 438 426 411 392 345 292 PI kW 116 125 134 144 155 151 125 136 147 159 162 147 qw l/s 18,9 18,1 17,2 16,1 14,9 13,2 21,0 20,4 19,7 18,8 16,5 14,0 dpw kPa 57 53 48 43 37 30 50 48 45 41 33 24
CC kW 9 416 398 378 356 329 282 460 448 432 412 353 298 PI kW 120 129 138 149 160 149 129 140 151 164 160 144 qw l/s 20,0 19,1 18,1 17,1 15,8 13,5 22,1 21,5 20,7 19,7 16,9 14,3 dpw kPa 63 58 53 47 41 31 55 52 49 45 34 25
CC kW 11 438 419 399 375 342 289 483 470 453 432 358 303 PI kW 124 133 143 153 162 146 133 144 156 169 157 140 qw l/s 21,0 20,1 19,1 18,0 16,4 13,9 23,2 22,6 21,8 20,7 17,2 14,5 dpw kPa 69 64 58 52 44 33 60 57 53 49 35 26
CC kW 13 460 441 419 395 348 294 506 492 475 452 365 309 PI kW 128 137 147 158 159 143 137 149 161 174 154 138 qw l/s 22,1 21,2 20,1 19,0 16,7 14,1 24,3 23,7 22,8 21,7 17,5 14,8 dpw kPa 76 70 64 57 46 34 65 62 58 53 36 27
CC kW 15 483 463 440 414 355 301 530 515 496 464 370 316 PI kW 132 141 152 163 157 140 142 153 166 176 151 135 qw l/s 23,3 22,3 21,2 19,9 17,1 14,5 25,5 24,8 23,9 22,3 17,8 15,2 dpw kPa 83 77 70 63 47 35 71 68 63 56 37 28
Fluid: Water Ta: Condenser inlet air temperature; Twout: Evaporator leaving water temperature (Δt 5°C) CC: Cooling capacity; PI: Power input; qw: Fluid flow rate; dpw: Fluid pressure drop * For working condition where dpw value is "Italic-Red Color" please contac factory
Page 24 of 40
COOLING PERFORMANCE
EWAD E-SL 100 120
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 102 97,0 92,1 86,8 81,0 70,2 121 115 109 103 91,9 77,1 PI kW 32,0 34,9 38,1 41,5 45,1 41,5 39,5 43,0 46,9 51,1 52,4 46,4 qw l/s 4,9 4,6 4,4 4,2 3,9 3,4 5,8 5,5 5,2 4,9 4,4 3,7 dpw kPa 25 23 21 19 16 13 25 23 21 19 15 11
CC kW 7 107 103 97,6 92,1 85,8 72,1 128 122 116 109 94,0 78,8 PI kW 33,0 36,0 39,2 42,6 45,9 40,4 40,7 44,4 48,3 52,6 50,7 45,0 qw l/s 5,1 4,9 4,7 4,4 4,1 3,4 6,1 5,8 5,5 5,2 4,5 3,8 dpw kPa 27 25 23 21 18 13 27 25 23 21 16 12
CC kW 9 113 108 103 97,5 87,7 73,6 135 129 122 115 96,4 80,8 PI kW 34,1 37,1 40,3 43,8 44,5 39,3 42,0 45,8 49,8 54,1 49,4 44,0 qw l/s 5,4 5,2 4,9 4,7 4,2 3,5 6,4 6,2 5,9 5,5 4,6 3,9 dpw kPa 30 28 26 23 19 14 30 28 25 23 17 12
CC kW 11 119 114 109 103 89,7 75,5 141 135 129 122 98,3 82,5 PI kW 35,2 38,2 41,5 45,0 43,4 38,5 43,4 47,2 51,3 55,6 48,0 43,0 qw l/s 5,7 5,5 5,2 4,9 4,3 3,6 6,8 6,5 6,2 5,8 4,7 4,0 dpw kPa 33 31 28 26 20 15 33 31 28 25 17 13
CC kW 13 125 120 115 109 91,5 77,1 149 142 135 126 101 83,9 PI kW 36,3 39,4 42,7 46,3 42,2 37,6 44,8 48,7 52,8 55,7 47,1 41,9 qw l/s 6,0 5,8 5,5 5,2 4,4 3,7 7,1 6,8 6,5 6,1 4,8 4,0 dpw kPa 36 34 31 28 21 15 36 33 31 27 18 13
CC kW 15 132 126 120 114 93,0 78,5 156 149 142 129 102 85,9 PI kW 37,5 40,6 43,9 47,6 41,0 36,7 46,3 50,2 54,4 54,4 45,5 41,3 qw l/s 6,3 6,1 5,8 5,5 4,5 3,8 7,5 7,2 6,8 6,2 4,9 4,1 dpw kPa 40 37 34 31 21 16 40 37 34 28 18 14
130 160
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 139 133 126 119 111 103 163 156 148 139 130 115 PI kW 43,8 47,7 51,9 56,7 62,0 63,1 49,7 54,3 59,2 64,5 70,2 66,5 qw l/s 6,6 6,3 6,0 5,7 5,3 4,9 7,8 7,4 7,1 6,7 6,2 5,5 dpw kPa 24 22 20 18 16 14 25 23 21 18 16 13
CC kW 7 147 140 134 126 118 106 172 165 157 148 139 118 PI kW 45,0 49,0 53,4 58,2 63,6 61,0 51,2 55,9 60,8 66,2 72,0 64,8 qw l/s 7,0 6,7 6,4 6,0 5,7 5,1 8,2 7,9 7,5 7,1 6,6 5,7 dpw kPa 26 24 22 20 18 15 27 25 23 21 18 14
CC kW 9 155 148 141 134 126 109 181 174 165 157 143 121 PI kW 46,3 50,4 54,9 59,8 65,3 59,5 52,8 57,5 62,6 68,0 71,2 63,0 qw l/s 7,4 7,1 6,8 6,4 6,0 5,2 8,7 8,3 7,9 7,5 6,9 5,8 dpw kPa 29 27 25 22 20 15 30 28 25 23 20 14
CC kW 11 163 156 149 142 132 111 190 183 174 165 147 125 PI kW 47,7 51,8 56,4 61,4 65,9 57,8 54,4 59,1 64,3 69,9 69,5 61,8 qw l/s 7,8 7,5 7,2 6,8 6,3 5,3 9,1 8,8 8,4 7,9 7,0 6,0 dpw kPa 32 29 27 25 22 16 33 30 28 25 20 15
CC kW 13 171 164 157 149 134 114 200 192 183 174 150 126 PI kW 49,1 53,3 57,9 63,1 63,7 56,7 56,0 60,9 66,1 71,8 67,8 59,9 qw l/s 8,2 7,9 7,5 7,2 6,4 5,5 9,6 9,2 8,8 8,4 7,2 6,1 dpw kPa 35 32 30 27 22 17 36 33 31 28 21 16
CC kW 15 180 173 165 157 137 115 210 201 193 183 153 129 PI kW 50,6 54,9 59,6 64,8 62,1 54,9 57,8 62,7 68,0 73,7 65,9 58,5 qw l/s 8,6 8,3 7,9 7,6 6,6 5,5 10,1 9,7 9,3 8,8 7,3 6,2 dpw kPa 38 35 33 30 23 17 39 36 33 31 22 16
Page 25 of 40
COOLING PERFORMANCE
EWAD E-SL 180 210
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 185 176 167 155 141 132 210 205 198 187 173 156 PI kW 55,7 60,7 66,4 72,9 80,2 85,0 58,1 64,2 71,0 78,6 87,3 87,6 qw l/s 8,8 8,4 8,0 7,4 6,7 6,3 10,0 9,8 9,4 8,9 8,2 7,5 dpw kPa 23 21 19 17 14 12 21 20 18 17 14 12
CC kW 7 195 187 177 164 150 137 222 216 208 197 182 160 PI kW 57,3 62,5 68,3 74,9 82,3 84,0 59,7 65,9 72,8 80,7 89,5 85,2 qw l/s 9,3 8,9 8,4 7,9 7,2 6,5 10,6 10,4 10,0 9,4 8,7 7,7 dpw kPa 25 23 21 19 16 13 23 22 20 18 16 13
CC kW 9 205 197 187 174 159 140 233 228 220 208 192 164 PI kW 59,0 64,3 70,3 76,9 84,5 81,1 61,3 67,7 74,8 82,7 91,7 82,6 qw l/s 9,8 9,4 8,9 8,3 7,6 6,7 11,2 10,9 10,5 9,9 9,2 7,8 dpw kPa 28 26 24 21 18 14 25 24 22 20 18 13
CC kW 11 216 207 196 184 168 144 245 239 230 218 197 167 PI kW 60,7 66,1 72,2 79,1 86,8 79,0 63,0 69,5 76,8 84,9 90,4 80,7 qw l/s 10,4 9,9 9,4 8,8 8,0 6,9 11,7 11,5 11,0 10,5 9,5 8,0 dpw kPa 31 28 26 23 19 15 27 26 24 22 19 14
CC kW 13 227 217 206 193 175 147 256 250 241 229 202 171 PI kW 62,4 67,9 74,2 81,3 87,6 76,8 64,8 71,4 78,8 87,1 88,7 78,8 qw l/s 10,9 10,4 9,9 9,3 8,4 7,0 12,3 12,0 11,6 11,0 9,7 8,2 dpw kPa 33 31 28 25 21 15 30 28 27 24 19 14
CC kW 15 238 228 216 202 178 151 269 262 252 239 205 173 PI kW 64,3 69,9 76,3 83,5 84,7 75,3 66,7 73,4 80,9 89,4 86,0 76,8 qw l/s 11,4 10,9 10,4 9,7 8,5 7,2 12,9 12,6 12,1 11,5 9,8 8,3 dpw kPa 37 34 31 27 22 16 32 31 29 26 20 15
250 300
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 257 246 233 219 203 191 309 295 278 260 238 203 PI kW 70,2 76,2 83,2 91,4 101 107 92,6 99,8 107 116 125 116 qw l/s 12,3 11,8 11,2 10,5 9,7 9,1 14,8 14,1 13,3 12,4 11,4 9,7 dpw kPa 48 44 40 36 31 28 49 45 40 35 30 23
CC kW 7 272 261 248 233 216 204 326 312 295 275 250 210 PI kW 72,4 78,4 85,4 93,5 103 109 95,8 103 111 120 127 115 qw l/s 13,0 12,5 11,9 11,2 10,3 9,8 15,6 14,9 14,1 13,2 11,9 10,0 dpw kPa 53 49 45 40 35 32 54 49 45 39 33 24
CC kW 9 287 276 263 247 229 212 344 328 311 291 255 216 PI kW 74,6 80,7 87,7 95,8 105 108 99,1 107 115 124 125 114 qw l/s 13,8 13,2 12,6 11,9 11,0 10,1 16,5 15,8 14,9 14,0 12,2 10,4 dpw kPa 59 55 50 45 39 34 59 54 49 44 34 26
CC kW 11 303 291 277 262 243 217 362 346 327 307 261 220 PI kW 77,0 83,1 90,1 98,1 107 105 103 110 119 128 124 111 qw l/s 14,6 14,0 13,3 12,6 11,7 10,4 17,4 16,6 15,7 14,7 12,5 10,6 dpw kPa 65 60 55 50 44 36 65 60 54 48 36 26
CC kW 13 319 306 292 276 257 223 380 363 344 322 267 226 PI kW 79,5 85,6 92,6 101 110 103 106 114 123 132 122 108 qw l/s 15,4 14,7 14,0 13,3 12,3 10,7 18,3 17,5 16,5 15,5 12,8 10,8 dpw kPa 71 66 61 55 48 37 71 65 59 53 37 28
CC kW 15 335 322 307 290 269 229 399 381 361 338 271 230 PI kW 82,2 88,2 95,2 103 112 101 110 118 127 137 119 106 qw l/s 16,2 15,5 14,8 14,0 12,9 11,0 19,2 18,3 17,4 16,3 13,0 11,1 dpw kPa 78 73 67 60 53 39 78 71 65 58 39 29
Page 26 of 40
COOLING PERFORMANCE
EWAD E-SL 350 400
45 40 35 30 25 48 45 40 35 30 25 48 Ta Twout
CC kW 5 362 345 325 302 267 221 408 395 377 354 281 234 PI kW 112 121 130 140 146 130 124 135 146 159 141 125 qw l/s 17,3 16,5 15,5 14,4 12,8 10,6 19,5 18,9 18,0 16,9 13,4 11,2 dpw kPa 49 45 40 35 28 20 44 41 38 34 22 16
CC kW 7 382 364 344 319 275 230 429 415 397 366 289 243 PI kW 116 125 135 145 145 129 128 139 152 161 140 125 qw l/s 18,3 17,4 16,5 15,3 13,1 11,0 20,5 19,9 19,0 17,5 13,8 11,6 dpw kPa 54 49 44 39 30 22 48 45 42 36 24 17
CC kW 9 402 383 362 337 280 237 450 435 416 372 295 248 PI kW 120 130 140 151 142 127 133 144 157 159 137 122 qw l/s 19,3 18,4 17,4 16,2 13,4 11,3 21,6 20,9 19,9 17,8 14,1 11,9 dpw kPa 59 54 49 43 31 23 53 50 46 37 25 18
CC kW 11 423 403 381 355 286 243 472 456 435 378 299 253 PI kW 125 134 145 156 139 124 137 149 162 157 133 119 qw l/s 20,3 19,4 18,3 17,0 13,7 11,6 22,7 21,9 20,9 18,1 14,3 12,1 dpw kPa 65 59 54 47 32 24 57 54 50 38 25 19
CC kW 13 444 423 399 369 293 248 494 476 455 385 306 257 PI kW 129 139 150 159 137 121 142 155 168 155 131 116 qw l/s 21,3 20,3 19,2 17,7 14,1 11,9 23,7 22,9 21,8 18,5 14,7 12,3 dpw kPa 71 65 59 51 34 25 62 59 54 40 26 19
CC kW 15 465 443 419 375 298 255 516 497 472 392 311 264 PI kW 134 144 155 156 132 119 148 160 173 152 128 114 qw l/s 22,4 21,3 20,1 18,0 14,3 12,2 24,8 23,9 22,7 18,8 15,0 12,7 dpw kPa 77 71 64 52 35 26 68 63 58 41 27 20
Fluid: Water Ta: Condenser inlet air temperature; Twout: Evaporator leaving water temperature (Δt 5°C) CC: Cooling capacity; PI: Power input; qw: Fluid flow rate; dpw: Fluid pressure drop * For working condition where dpw value is "Italic-Red Color" please contac factory
Page 27 of 40
OPTIONS (TECHNICAL DATA)
Water Pump Kit
Single Pump (2 poles) Low Discharge Head
Legend: ASP = Available Static Pressure (kPa); WF = Water Flow (l/s)
Note - the above curves are referred to the available static pressure - when selecting the pump you have to consider the installation pressure drops - when using mixture of water and glycol please contact the factory as above specification can change
Page 28 of 40
OPTIONS (TECHNICAL DATA)
Single Pump (2 poles) High Discharge Head
Legend: ASP = Available Static Pressure (kPa); WF = Water Flow (l/s)
Note - the above curves are referred to the available static pressure - when selecting the pump you have to consider the installation pressure drops - when using mixture of water and glycol please contact the factory as above specification can change
Twin Pump (2 poles) Low Discharge Head
Page 29 of 40
OPTIONS (TECHNICAL DATA)
Legend: ASP = Available Static Pressure (kPa); WF = Water Flow (l/s)
Note - the above curves are referred to the available static pressure - when selecting the pump you have to consider the installation pressure drops - when using mixture of water and glycol please contact the factory as above specification can change
Twin Pump (2 poles) High Discharge Head
Page 30 of 40
OPTIONS (TECHNICAL DATA)
Legend: ASP = Available Static Pressure (kPa); WF = Water Flow (l/s)
Note - the above curves are referred to the available static pressure - when selecting the pump you have to consider the installation pressure drops - when using mixture of water and glycol please contact the factory as above specification can change
Page 31 of 40
DIMENSIONAL DRAWING
1: 2: 3: 4: 5: 6: 7: 8:
Compressor Evaporator Condenser coil Electrical panel Fan Evaporator water inlet Evaporator water outlet Slot for power and control panel connection
LEGEND
A M L I H G B C F E D
2165 1175 172 2273 501 1292 EWAD100E-SS 2165 1175 172 2273 501 1292 EWAD120E-SS 3065 1175 172 2273 501 1292 EWAD140E-SS 3065 1175 172 2273 501 1292 EWAD160E-SS 3065 1175 172 2273 501 1292 EWAD180E-SS 3065 1175 172 2273 501 1292 EWAD210E-SS 2165 1175 172 2273 501 1292 EWAD100E-SL 2165 1175 172 2273 501 1292 EWAD120E-SL 3065 1175 172 2273 501 1292 EWAD130E-SL 3065 1175 172 2273 501 1292 EWAD160E-SL 3065 1175 172 2273 501 1292 EWAD180E-SL 3065 1175 172 2273 501 1292 EWAD210E-SL
Page 32 of 40
DIMENSIONAL DRAWING
1: 2: 3: 4: 5: 6: 7: 8:
Compressor Evaporator Condenser coil Electrical panel Fan Evaporator water inlet Evaporator water outlet Slot for power and control panel connection
LEGEND
A M L I H G B C F E D
3070 1612 172 2223 515 257 243 2236 EWAD260E-SS 3070 1612 172 2223 515 257 243 2236 EWAD310E-SS 3070 1612 172 2223 515 257 243 2236 EWAD360E-SS 3070 1612 172 2223 515 257 243 2236 EWAD410E-SS 3070 1612 172 2223 515 257 243 2236 EWAD250E-SL 3070 1612 172 2223 515 257 243 2236 EWAD300E-SL 3070 1612 172 2223 515 257 243 2236 EWAD350E-SL 3070 1612 172 2223 515 257 243 2236 EWAD400E-SL
Page 33 of 40
INSTALLATION NOTES
Warning Installation and maintenance of the unit must to be performed only by qualified personnel who have knowledge with local codes and regulations, and experience with this type of equipment. Must be avoided the unit installation in places that could be considered dangerous for all the maintenance operations.
Handling Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from anything other than the base frame. Never allow the unit to fall during unloading or moving as this may result in serious damage. To lift the unit, rings are provided in the base frame of the unit. Spreader bar and cables should be arranged to prevent damage to the condenser coil or unit cabinet.
Location The units are produced for outside installation on roofs, floors or below ground level on condition that the area is free from obstacles for the passage of the condenser air. The unit should be positioned on solid foundations and perfectly level; in the case of installation on roofs or floors, it may be advisable to arrange the use of suitable weight distribution beams. When the units are installed on the ground, a concrete base at least 250 mm wider and longer than the unit’s footprint should be laid. Furthermore, this base should withstand the unit weight mentioned in the technical data table.
Space requirements The units are air-cooled, then it is important to respect the minimum distances which guarantee the best ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions in cooling capacity and an increase in electricity consumption. To determinate unit placement, careful consideration must be given to assure a sufficient air flow across the condenser heat transfer surface. Two conditions must be avoided to achieve the best performance: warm air recirculation and coil starvation. Both these conditions cause an increase of condensing pressures that results in reductions in unit efficiency and capacity. Moreover the unique microprocessor has the ability to calculate the operating environment of the air cooled chiller and the capacity to optimize its performance staying on-line during abnormal conditions. Each side of the unit must be accessible after installation for periodic service. 'Fig.1 and Fig.2' shows you minimum recommended clearance requirements. Vertical condenser air discharge must be unobstructed because the unit would have its capacity and efficiency significantly reduced. If the units are positioned in places surrounded by walls or obstacles of the same height as the units, the units should follow the minimum recommended clearance requirements shown in 'Fig.3 and Fig.4'. In the event the obstacles are higher than the units, the minimum recommended clearance requirements are shown in 'Fig.5 and Fig.6'. Units installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, thus causing reduction in unit capacity and efficiency reductions. The microprocessor control is proactive in response “of design condition”. In the case of single or compounded influences restricting airflow to the unit, the microprocessor will act to keep the compressor(s) running (at reduced capacity) rather than allowing a shut-off on high discharge pressure. When two or more units are positioned side by side it is recommended that the condenser coils are at a minimum distance from one another as shown in 'Fig.7 and Fig.8'; strong wind could be the cause of air warm recirculation. For other installation solutions, consult our technicians. The above recommended information are representative of general installation. A specific evaluation should be done by contractor depending on the case.
Page 34 of 40
INSTALLATION NOTES
Acoustic protection When noise level must meet special requirements, it is necessary to pay the maximum attention to ensure the perfect insulation of the unit from the support base by applying appropriate vibration-dampening devices on the unit, on the water pipes and on the electrical connections.
Page 35 of 40
INSTALLATION NOTES
Storage The environment conditions have to be in the following limits:
Minimum ambient temperature: Maximum ambient temperature: Maximum R.H.:
-20°C +57°C 95% not condensing
Page 36 of 40
TECHNICAL SPECIFICATIONS
General The chiller will be designed and manufactured in accordance with the following European directives: • Construction of pressure vessel 97/23/EC (PED) • Machinery Directive 2006/42/EC • Low Voltage 2006/95/EC • Electromagnetic Compatibility 2004/108/EC • Electrical & Safety codes EN 60204–1 / EN 60335-2-40 • Manufacturing Quality Standards UNI – EN ISO 9001:2004 To avoid any losses, the unit will be tested at full load in the factory (at the nominal working conditions and water temperatures). The chiller will be delivered to the job site completely assembled and charged with refrigerant and oil. The installation of the chiller must comply with the manufacturer’s instructions for rigging and handling equipment. The unit will be able to start up and operate (as standard) at full load with: - outside air temperature from ............... °C to ............... °C - evaporator leaving fluid temperature between ............... °C and ............... °C
Refrigerant Only HFC 134a can be used.
Performance Chiller shall supply the following performances: • Number of chiller(s) : ............... unit(s) • Cooling capacity for single chiller : ............... kW • Power input for single chiller in cooling mode : ............... kW • Heat exchanger entering water temperature in cooling mode : ............... °C • Heat exchanger leaving water temperature in cooling mode : ............... °C • Heat exchanger water flow : ............... l/s • Nominal outside working ambient temperature in cooling mode : ............... °C Operating voltage range should be 400V ±10%, 3ph, 50Hz, voltage unbalance maximum 3%, without neutral conductor and shall only have one power connection point.
Unit description Chiller shall include as standard: one refrigerant circuit, semi-hermetic type rotary single screw compressor, electronic expansion device (EEXV), refrigerant direct expansion plate to plate heat exchanger, air-cooled condenser section, R134a refrigerant, lubrication system, motor starting components, discharge line shut-off valve, suction line shut-off valve, control system and all components necessary for safe and stable unit operation. Chiller will be factory assembled on a robust base-frame made of galvanized steel, protected by an epoxy paint.
Sound level and vibrations Sound pressure level at 1 meter distance in free field, semispheric conditions, shall not exceed ………dB(A). The sound pressure levels must be rated in accordance to ISO 3744 (other types of rating can not be used). Vibration on the base frame should not exceed 2 mm/s.
Dimensions Unit dimensions shall not exceed following indications: - Unit length ............... mm - Unit width ............... mm - Unit height ............... mm
Compressors (Symmetric) The unit shall be equipped with: • Semi-hermetic, single-screw type with one main helical rotor meshing with gaterotor. The gaterotor will be constructed of a carbon impregnated engineered composite material. The gaterotor supports will be constructed of cast iron.
Compressors (Asymmetric) The unit shall be equipped with: • Semi-hermetic, single-screw asymmetric type with one main helical rotor meshing with two diametrical opposed gaterotors. The gaterotors’ contact elements shall be constructed of composite material designed for extended life. Electrical motor shall be 2-pole, semi-hermetic, squirrel-cage induction type and cooled by suction gas. • The oil injection shall be used in order to get high EER (Energy Efficiency Ratio) also at high condensing pressure and low sound pressure levels in each load condition. • The compressor shall be provided with a built in, high efficiency, mesh type oil separator and oil filter. • Refrigerant system differential pressure shall provide oil injection on all moving compressor parts to correctly lubricate them. Electrical oil pump lubricating system is not allowed. • Compressor cooling must be done by refrigerant liquid injection. An external dedicated heat exchanger and additional piping to carry the oil from compressor to heat exchanger and viceversa is not allowed. • The compressor shall be direct electrical driven, without gear transmission between the screw and the electrical motor. • The compressor casing shall be provided with ports to realize economized refrigerant cycles. • The compressor must be protected by a temperature sensor for high discharge temperature and an electrical motor thermistor for high winding temperature. • The compressor shall be equipped with an electric oil heater. • The compressor shall be fully field serviceable. Compressor that must be removed and returned to the factory for service shall be unacceptable.
Page 37 of 40
TECHNICAL SPECIFICATIONS
Evaporator (PHE) The units shall be equipped with a direct expansion plate to plate type evaporator. • The evaporator will be made of of stainless steel brazed plates and shall be linked with an electrical heater to prevent freezing down to -28°C ambient temperature, controlled by a thermostat and shall be insulated with flexible, closed cell polyurethane insulation material (20-mm thick). • The evaporator will have 1 refrigerant circuit for each compressor. • The water connections shall be VICTAULIC type connections as standard to ensure quick mechanical disconnection between the unit and the hydronic network. • The evaporator will be manufactured in accordance to PED approval. • Flow switch on evaporator available as option and shipped loose(not available for Condensing unit version). • Water filter is standard and shipped loose (not available for Condensing unit version).
Condenser coil The unit shall be equipped with condenser coils constructed with internally finned seamless copper tubes and arranged in a staggered row pattern and mechanically expanded into lanced and rippled aluminum fins with full fin collars for higher efficiencies. The space between the fins is given by a collar that will increase the surface area in connection with the tubes, protecting them from ambient corrosion. • The condenser coils will have an integral subcooler circuit that provides sufficient subcooling to effectively eliminate the possibility of liquid flashing and increase the unit's efficiency with 5% to 7% without increasing in energy consumption. • The condenser coils shall be leak-tested and submitted to a pressure test with dry air.
Condenser fans The condenser fans used in conjunction with the condenser coils, shall be propeller type with glass reinforced resin blades for higher efficiencies and lower sound. Each fan shall be protected by a fan guard. • The air discharge shall be vertical and each fan must be coupled to the electrical motor, supplied as standard to IP54 and capable to work to ambient temperatures of - 20°C to + 65°C. • The condenser fans shall have as a standard a thermally protection by internal thermal motor protection and protected by circuit braker installed inside the electrical panel as a standard.
Refrigerant circuit The unit shall have one refrigerant circuit. • The circuit shall include as standard: electronic expansion device piloted by unit’s microprocessor control, compressor discharge shut-off valve, liquid line shut-off valve, sight glass with moisture indicator, replaceable filter drier, charging valves, high pressure switch, high and low pressure transducers, oil pressure transducer and insulated suction line.
Condensation control The units will be provided with an automatic control for condensing pressure which ensures the working at low external temperatures down to - …………… °C, to maintain condensing pressure. • The compressor automatically unloads when abnormal high condensing pressure is detected. This to prevent the shutdown of the refrigerant circuit (shutdown of the unit) due to a high-pressure fault.
Low sound unit configurations (on request) The unit compressor shall be connected with unit’s metal base frame by rubber antivibration supports to prevent the transmission of vibrations to all metal unit structure, in order to control the unit sound. • The chiller shall be provided with an acoustical compressor enclosure. This enclosure shall be realized with a light, corrosion resisting aluminum structure and metal panels. The compressor sound-proof enclosure shall be internally fitted with flexible, multi-layer, high density materials.
Hydronic kit options (on request) The hydronic module shall be integrated in the chiller chassis without increasing its dimensions and includes the following elements: centrifugal pump with motor protected by a circuit breaker installed in control panel, water filling system with pressure gauge, safety valve, drain valve. • The hydronic module shall be assembled and wired to the control panel. • The water piping shall be protected against corrosion and freezing and insulated to prevent condensation. • A choice of two pump types shall be available: - in-line single pump - in-line twin pumps.
Electrical control panel Power and control shall be located in the main panel that will be manufactured to ensure protection against all weather conditions. • The electrical panel shall be IP54 and (when opening the doors) internally protected against possible accidental contact with live parts. • The main panel shall be fitted with a main switch interlocked door that shuts off power supply when opening. • The power section will include compressors and funs protection devices, compressors and fans starters and control circuit power supply.
Page 38 of 40
TECHNICAL SPECIFICATIONS
Controller The controller will be installed as standard and it will be used to modify unit set-points and check control parameters. • A built-in display will shows chiller operating status plus temperatures and pressures of water, refrigerant and air, programmable values, set-points. • A sophisticated software with predictive logic, will select the most energy efficient combination of compressors, EEXV and condenser fans to keep stable operating conditions to maximize chiller energy efficiency and reliability. • The controller will be able to protect critical components based on external signals from its system (such as motor temperatures, refrigerant gas and oil pressures, correct phase sequence, pressure switches and evaporator). The input coming from the high pressure switch cuts all digital output from the controller in less than 50ms, this will be an additional security for the equipment. • Fast program cycle (200ms) for a precise monitoring of the system. • Floating point calculations supported for increased accuracy in P/T conversions.
Controller main features Controller shall be garantee following minimu functions: • Management of the compressor stepless capacity and fans modulation. • Chiller enabled to work in partial failure condition. • Full routine operation at condition of: - high ambient temperature value - high thermal load - high evaporator entering water temperature (start-up) • Display of evaporator entering/leaving water temperature. • Display of Outdoor Ambient Temperature. • Display of condensing-evaporating temperature and pressure, suction and discharge superheat for each circuit. • Leaving water evaporator temperature regulation (temperature tolerance = 0,1°C). • Compressor and evaporator pumps hours counter. • Display of Status Safety Devices. • Number of starts and compressor working hours. • Optimized management of compressor load. • Fan management according to condensing pressure. • Re-start in case of power failure (automatic / manual). • Soft Load (optimized management of the compressor load during the start-up). • Start at high evaporator water temperature. • Return Reset (Set Point Reset based on return water temperature). • OAT (Outside Ambient temperature) Reset. • Set point Reset (optional). • Application and system upgrade with commercial SD cards. • Ethernet port for remote or local servicing using standard web browsers. • Two different sets of default parameters could be stored for easy restore.
High Level Communications Interface (on request) The chiller shall be able to communicate to BMS (Building Management System) based on the most common protocols as: - ModbusRTU - LonWorks, now also based on the international 8040 Standard Chiller Profile and LonMark Technology - BacNet BTP certifief over IP and MS/TP (class 4) (Native) - Ethernet TCP/IP.
Page 39 of 40