Capacity Release in LV Distribution Networks with Power ...

174
Capacity Release in LV Distribution Networks with Power Electronics by Thomas Frost (CID: 782574) Control and Power Research Group Department of Electrical and Electronic Engineering Imperial College London London SW7 2AZ United Kingdom April, 2017 Thesis submitted as part of the requirements for the award of Doctor of Philosophy in Electrical Engineering, Imperial College London

Transcript of Capacity Release in LV Distribution Networks with Power ...

Capacity Release in LV Distribution Networks

with Power Electronics

by

Thomas Frost (CID: 782574)

Control and Power Research Group

Department of Electrical and Electronic Engineering

Imperial College London

London SW7 2AZ

United Kingdom

April, 2017

Thesis submitted as part of the requirements for the award of

Doctor of Philosophy in Electrical Engineering, Imperial College London

i

Abstract

Connection of low carbon technology to the LV distribution network stresses the network voltage

limits. In certain cases this is such that further low carbon technologies such as, distributed

generation sources, heat pumps, and electric vehicles, cannot be accommodated without costly

network reinforcement. One solution is use power electronics to regulate the voltage and so remove

these network voltage constraints. This can defer or even remove the need for network reinforcement

and so reduce investment costs for distribution network operators. This thesis examines how these

power electronics can be installed into distribution network for the purposes of voltage control and

capacity release in constrained networks. The efficacy of five power electronics solutions relative to

both reinforcement and de-regulation (or relaxing) of voltage limits is compared in technical and

economic aspects.

As de-regulation requires knowledge of how the network loads function in response to supply

voltage fluctuation an analysis of how de-regulation effects the loads connected to the grid was

undertaken. This revealed there is more reliable operation of these loads with voltages well below

the present UK limits, however their tolerance of over voltages is shown to be very limited. Fol-

lowing on from this, it was shown that, when coupled to changes to the nominal system voltages,

reinforcement could be deferred by de-regulation. Testing and simulation of both motor loads

and the magnetics in common power supply units was performed, were a method was outlined for

consideration of the losses in a flyback transformer and a boost inductor when subject to supply

voltages outside of their tolerance bands.

Detailed models of distribution networks are needed to accurately quantify the befits of de-

regulation and PEDs, so three detailed test networks where assessed in terms of their hosting

capacity for low carbon technologies. A load model was presented for load flow studies that enables

the model to be used in scenarios where the supply voltages are subject to wide voltage fluctuations.

Additionally, the effect of thermally controlled goods was also considered by implementing either

constant energy or dynamic thermal model into these goods. Finally to aid in assessment of the

huge variance in LV network topology, metrics were developed to indicate the relative constraints

a given network will likely face. These where seen in the cases test to be in good agreement with

the results of the substantially more time consuming load flow methods.

ii

Overall analysis revealed, all of the power electronic solutions which primarily control voltage

were effective in significantly reducing the occurrence of voltage violations, furthermore the control

they offer allows the distribution network operators significantly more flexibility in regards to no

load system voltages which are normally very close to the upper end of the tolerance band. This

flexibility afforded by PEDs enables a greatly increased percentage of distributed generation if this

practice is stopped, indeed this is the cause of over voltages that where seen with only amounts of

distributed generation connected to the LV networks.

iii

Acknowledgements

Firstly, many thanks go to my two supervisors Professor Paul Mitcheson and Professor Tim Green

for their guidance and advice thorough the 4 years of this work. Secondly, I thank all of my

friends and family, those in London, Imperial College, and further afield, for marking these years

so enjoyable, regardless of any ups and downs with study. In particular, Nelly, for putting up with

me during these last 2 years, in spite of my sometimes peculiar work schedules. Finally, and with

deepest gratitude, I thank my parents, Denise and Gerry, for supporting me throughout my (now

many) years of study, both at university and school.

iv

Declaration of Originality

I, Thomas Frost, confirm that all work presented in this thesis is my own and all work undertaken

by other authors is appropriately referenced within the text. All of my work is original and has

not been published before by a different author. All work that has been published by myself is

clearly indicated within the introduction of the relevant chapter.

v

Copyright Declaration

The copyright of this thesis rests with the author and is made available under a Creative Commons

Attribution Non-Commercial No Derivatives licence. Researchers are free to copy, distribute or

transmit the thesis on the condition that they attribute it, that they do not use it for commercial

purposes and that they do not alter, transform or build upon it. For any reuse or redistribution,

researchers must make clear to others the licence terms of this work.

vi

Contents

1 Introduction 1

1.1 GHG Emission Progress Thus Far . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.2 Future Predictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.3 Effects of Increased Load & Generation . . . . . . . . . . . . . . . . . . . . . . . . 8

1.4 Solutions to Networks Constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

1.4.1 Power Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

1.4.2 Other Approaches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

1.5 Problem Statement and Thesis Outline . . . . . . . . . . . . . . . . . . . . . . . . . 22

2 Background 24

2.1 Distribution Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

2.1.1 Network Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

2.1.2 Operation & Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

2.1.3 Distribution Network Components and Plant . . . . . . . . . . . . . . . . . 29

2.2 Power Electronic Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

2.2.1 Active Power Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

2.2.2 Soft Open Point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

2.2.3 Mid Feeder Compensator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

2.2.4 On-load Tap Changers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

2.2.5 Solid State Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

2.2.6 Overview of Power Electronic Devices . . . . . . . . . . . . . . . . . . . . . 53

2.3 Loads Profiles and Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

2.3.1 Loads without Thermal Control . . . . . . . . . . . . . . . . . . . . . . . . . 54

2.3.2 Loads with Thermal Control . . . . . . . . . . . . . . . . . . . . . . . . . . 57

2.3.3 Final Load Profiles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

3 Effect of Wider Voltage Tolerance on Domestic Loads 63

3.1 Domestic Energy Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

vii

3.2 Socialised Cost & Device Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

3.3 Voltage Tolerance - Experimental and Simulation . . . . . . . . . . . . . . . . . . . 70

3.3.1 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

3.3.2 Magnetics in Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . 73

3.4 Voltage Tolerance - Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

3.5 Summary of Voltage Tolerates of Domestic Loads . . . . . . . . . . . . . . . . . . . 90

4 Methods of Analysis in LV Networks 92

4.1 Load Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

4.2 Test Networks & Metrics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

4.3 Monte Carlo Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

4.4 Economic Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

5 Analysis of LV Networks with Wider Voltage Tolerances 105

5.1 Feeder Relief Strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

5.2 Considered Voltage Tolerance Bands . . . . . . . . . . . . . . . . . . . . . . . . . . 106

5.3 Feeder Relief with Voltage Deregulation . . . . . . . . . . . . . . . . . . . . . . . . 109

5.3.1 Generic LV Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

5.3.2 Real Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

5.3.3 Validation of the Real Network Model . . . . . . . . . . . . . . . . . . . . . 116

5.4 The Benefits of De-regulation in LV Networks . . . . . . . . . . . . . . . . . . . . . 119

6 Analysis of LV Networks with Power Electronic Devices 121

6.1 PED Device Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122

6.2 Feeder Relief with PEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

6.2.1 Generic LV Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

6.3 Analysis of Active Power Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127

6.4 Comparison of PED Regulation Approaches . . . . . . . . . . . . . . . . . . . . . . 129

6.5 The Benefits of PEDs in LV Networks . . . . . . . . . . . . . . . . . . . . . . . . . 130

7 Conclusions and Future Work 131

7.1 Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

7.2 Authors Contribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134

7.3 Future Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136

7.4 Published Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137

Appendices 150

A Load Goods Table 151

viii

B HV & LV Feeder Impedances 152

B.1 LV Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153

C Direct Load Flow Code 155

ix

List of Figures

1.1 GHG Emission in Million Tones of CO2 equivalent (MtCO2e) . . . . . . . . . . . . 2

1.2 Installed Electrical DG Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.3 GHG Emissions from the Domestic Sector . . . . . . . . . . . . . . . . . . . . . . . 4

1.4 GHG Emissions from the Transport Sector . . . . . . . . . . . . . . . . . . . . . . 5

1.5 Electrical Energy Demand by the Domestic Sector without EV . . . . . . . . . . . 6

1.6 Electrical Energy Demand in the whole domestic sector . . . . . . . . . . . . . . . 7

1.7 Installed Solar Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

1.8 Four network capacity constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.9 Two Node Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

1.10 Voltage Over the Network Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

1.11 Cable Life Expectancy Due to Thermal Ageing . . . . . . . . . . . . . . . . . . . . 11

1.12 Three Phase to Ground Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

1.13 Temperature Rise of Motor Due to Voltage Unbalance . . . . . . . . . . . . . . . . 14

1.14 Effect of Supply Voltage on Common Domestic Goods . . . . . . . . . . . . . . . . 17

1.15 Rating of Transformer Using Static and Dynamic Ratings . . . . . . . . . . . . . . 18

1.16 DSM and its effect on demand profiles . . . . . . . . . . . . . . . . . . . . . . . . . 19

1.17 Prospective fault current (red) and fault current with an FCL (green) . . . . . . . 21

2.1 Layout of Existing HV Distribution Network . . . . . . . . . . . . . . . . . . . . . 25

2.2 Structure of the HV Distribution Network . . . . . . . . . . . . . . . . . . . . . . . 26

2.3 Secondary Substation Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

2.4 Underground equipment used along LV feeder ways . . . . . . . . . . . . . . . . . . 27

2.5 Allocation of voltage drop among network components . . . . . . . . . . . . . . . . 28

2.6 Interconnected ring configuration of an 11kV network . . . . . . . . . . . . . . . . 28

2.7 Primary Substation with Two 15MVA 33/11kV transformers . . . . . . . . . . . . 29

2.8 Secondary Substation and LV Transformer . . . . . . . . . . . . . . . . . . . . . . . 31

2.9 Typical 3 Wire Overhead Distribution Lines . . . . . . . . . . . . . . . . . . . . . . 31

x

2.10 11kV Underground Triplex Cable Current Density with 1A in conductor A and

induced eddy currents in shields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

2.11 Earthing Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

2.12 ABC Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

2.13 Distribution Network with Power Electronics . . . . . . . . . . . . . . . . . . . . . 36

2.14 Configuration of a APF Control Scheme . . . . . . . . . . . . . . . . . . . . . . . . 37

2.15 Comparisons of APF Control Schemes . . . . . . . . . . . . . . . . . . . . . . . . . 41

2.16 Configuration of a APF Control Scheme . . . . . . . . . . . . . . . . . . . . . . . . 41

2.17 Configuration of a APF Control Scheme . . . . . . . . . . . . . . . . . . . . . . . . 43

2.18 Iterations of a SOP Regulating Phase Voltages . . . . . . . . . . . . . . . . . . . . 46

2.19 A SOP connected between two feeders facilitating power flow between them . . . . 46

2.20 Configuration of a UPQC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

2.21 MFC Power Load and Source Flows . . . . . . . . . . . . . . . . . . . . . . . . . . 49

2.22 Performance of an MFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

2.23 Automatic Voltage Control (AVC) of an OLTC Transformer . . . . . . . . . . . . . 52

2.24 Possible Configuration of a SST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

2.25 An example of “ZIP Profile” Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

2.26 Temperature of House air, mass of building, fridge (electrical load) . . . . . . . . . 59

2.27 Preprocessing Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

2.28 During Load Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

2.29 Nominal CWSH Demand Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

2.30 CWSH Demand with differing supply Voltages . . . . . . . . . . . . . . . . . . . . 62

2.31 Average Domestic 24 hour demand profile, the load is comprised of: Thermally

Controlled (White Goods & Restive Based), Static, EV and HP loads . . . . . . . 62

3.1 Domestic Energy Use by Fuel Type . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

3.2 Detailed domestic Electrical Energy Use by Sector . . . . . . . . . . . . . . . . . . 65

3.3 Ownership of Lighting Products by Type in the UK domestic Sector . . . . . . . . 68

3.4 Ownership of Class A rated cold goods . . . . . . . . . . . . . . . . . . . . . . . . . 69

3.5 Ownership of ICT Products by Type in the UK domestic Sector . . . . . . . . . . 69

3.6 Ownership of Consumer Electronic Products by Type in the UK domestic Sector . 69

3.7 Speed of SPIM in a fridge with different Supply Voltages . . . . . . . . . . . . . . . 71

3.8 Fridge Temperature with Differing Supply Voltages . . . . . . . . . . . . . . . . . . 71

3.9 PQ Demand for Fridge Simulated . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

3.10 PQ Demand for Fridge Measured . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

3.11 PQ Demand for Fridge Measured with Stalled & Normal Operation . . . . . . . . 73

3.12 Topology of Flyback Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

xi

3.13 Losses in Flyback Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

3.14 Peak Flux Density of Flyback Transformer . . . . . . . . . . . . . . . . . . . . . . . 80

3.15 Topology of Boost Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

3.16 Copper Losses & Peak Flux Density in the Inductor of a Boost Converter for PFC

with varied supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

3.17 Heating Element Power in Response to Step Voltage Change . . . . . . . . . . . . 83

3.18 Voltage Sag Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

3.19 Voltage Sag Results for specific types of Load . . . . . . . . . . . . . . . . . . . . . 88

4.1 Full Schematic of Original UK Generic Network . . . . . . . . . . . . . . . . . . . . 94

4.2 A typical Single Phase Nodal Voltage from a 24 load flow . . . . . . . . . . . . . . 95

4.3 Ratings per customer severed for branches in the Generic UK Network . . . . . . . 97

4.4 Layout of the original UK Generic Network . . . . . . . . . . . . . . . . . . . . . . 98

4.5 Layout of the detailed UK Generic Network . . . . . . . . . . . . . . . . . . . . . . 98

4.6 Layout of the real UK Network with street map overlay . . . . . . . . . . . . . . . 99

4.7 Ratings per customer severed for main branches in the Real UK Network . . . . . 99

4.8 Layout of the IEEE European Network . . . . . . . . . . . . . . . . . . . . . . . . . 100

4.9 Ratings per customer severed for main branches in the IEEE Network . . . . . . . 100

4.10 Histogram of Substation Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

4.11 EAC of Network Investment Options with uncertain project lifetimes. . . . . . . . 104

5.1 Methods to Increase Capacity for Voltage constrained Networks . . . . . . . . . . . 106

5.2 Application of PoL to Regulate Systems Voltages . . . . . . . . . . . . . . . . . . . 108

5.3 Generic Network Voltages with 60% PV . . . . . . . . . . . . . . . . . . . . . . . . 110

5.4 Generic Network Feeder Losses with 60% PV . . . . . . . . . . . . . . . . . . . . . 110

5.5 Generic Network Service Losses with 60% PV . . . . . . . . . . . . . . . . . . . . . 110

5.6 Generic Network Voltages with 80% HP . . . . . . . . . . . . . . . . . . . . . . . . 111

5.7 Generic Network Branch Thermal Limits with 80% HP . . . . . . . . . . . . . . . 111

5.8 Generic Network Voltages with 71% EV . . . . . . . . . . . . . . . . . . . . . . . . 112

5.9 Generic Network Branch Thermal Limits with 71% EV . . . . . . . . . . . . . . . 112

5.10 Real Network Voltages with 60% PV and -2.5% tap . . . . . . . . . . . . . . . . . 113

5.11 Real Network Voltages with 60% PV and -5% tap . . . . . . . . . . . . . . . . . . 113

5.12 Real Network VUF with 60% PV . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

5.13 Real Network VUF with 80% HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

5.14 Real Network Branch Thermal Limits with 80% HP . . . . . . . . . . . . . . . . . 115

5.15 Real Network VUF with 80% HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

5.16 Real Network VUF with 71% EV . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

xii

5.17 Real Network Branch Thermal Limits with 71% EV . . . . . . . . . . . . . . . . . 116

5.18 Efficiency and Annual Power Consumed of UK DNOs from 2000-2010 . . . . . . . 116

5.19 Expected LV Network Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

5.20 Simulated and Expected Network Losses . . . . . . . . . . . . . . . . . . . . . . . . 118

6.1 Distribution Network with Power Electronics . . . . . . . . . . . . . . . . . . . . . 123

6.2 Outlying Results with no LCTs Considered . . . . . . . . . . . . . . . . . . . . . . 124

6.3 Network with 30% proliferation of PV Installations . . . . . . . . . . . . . . . . . . 124

6.4 Network with 60% proliferation of PV Installations . . . . . . . . . . . . . . . . . . 125

6.5 Network with 30% proliferation of Heat Pumps . . . . . . . . . . . . . . . . . . . . 126

6.6 Network with 80% proliferation of Heat Pumps . . . . . . . . . . . . . . . . . . . . 126

6.7 Network with 33% proliferation of Electric Vehicles . . . . . . . . . . . . . . . . . . 127

6.8 Network with 71% proliferation of Electric Vehicles . . . . . . . . . . . . . . . . . . 128

6.9 Network with 60% proliferation of PV Installations . . . . . . . . . . . . . . . . . . 128

B.1 11kV Pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

B.2 11kV Triplex Single laid direct in ground . . . . . . . . . . . . . . . . . . . . . . . 154

B.3 Current Density in 185mm2 Waveform Cable at 50Hz (top) and 5kHz (bottom) . . 154

xiii

List of Tables

1.1 Renewable Generation and Load Factor in 2015 . . . . . . . . . . . . . . . . . . . . 3

1.2 GHG Emissions From Buildings in 2015 . . . . . . . . . . . . . . . . . . . . . . . . 4

1.3 Surface transport Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

1.4 Summary of Power Quality Statutory Limits . . . . . . . . . . . . . . . . . . . . . 13

1.5 Limits on Specific Harmonic Voltages (n � 25) as Percentage of Fundamental . . . 14

1.6 PED Solutions to Limitations in Network Capacity . . . . . . . . . . . . . . . . . . 16

1.7 DG Curtailment with additional DG installed at Nodes 5010 and 5018 . . . . . . . 19

1.8 Comparison of ESS Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

1.9 Other Solutions to Limitations in Network Capacity . . . . . . . . . . . . . . . . . 21

2.1 11kV/LV Transformer Impedances [1] . . . . . . . . . . . . . . . . . . . . . . . . . 30

2.2 New 11kV Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

2.3 New LV Conductors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

2.4 Performance Characterisation of Power Electronic Devices . . . . . . . . . . . . . . 53

2.5 PQ ZIP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

3.1 Overall UK Domestic Energy Use (ktoe=11.6 G Wh) . . . . . . . . . . . . . . . . . 64

3.2 Domestic Lighting Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3.3 Domestic Cooling Goods Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3.4 Domestic Washing Goods Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3.5 Domestic Electrical Goods Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3.6 Domestic ICT Goods Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3.7 Domestic Cooking Goods Energy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

3.8 Grouping of Loads IN CREST Profiler . . . . . . . . . . . . . . . . . . . . . . . . . 66

3.9 Domestic Ownership - Lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

3.10 Domestic Ownership - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

3.11 Domestic Ownership - Washing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

3.12 Domestic Ownership - Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

3.13 Domestic Ownership - ICT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

xiv

3.14 Domestic Ownership - Cooking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

3.15 Load Torque Speed Relationships . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70

3.16 Flyback Converter Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

3.17 Basic Values for Flyback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

3.18 Values for Magnetic Components in the Flyback . . . . . . . . . . . . . . . . . . . 75

3.19 Parameters of an EDF-25 core with 3C85 Material . . . . . . . . . . . . . . . . . . 75

3.20 Data for AWG #26 Copper Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

3.21 Parameters and Design Choices for Magnetic Components of a Flyback . . . . . . 77

3.22 Losses Incurred in the Magnetic Components of a Flyback . . . . . . . . . . . . . . 78

3.23 Values of Flyback Operating with Reduced Supply Voltage . . . . . . . . . . . . . 79

3.24 Sensitivity Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

3.25 Sensitivity Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

3.26 Sensitivity Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

3.27 Sensitivity Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

3.28 Sensitivity Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

3.29 Sensitivity Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

3.30 Sensitivity Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

3.31 Collected Results from Voltage Sag Results . . . . . . . . . . . . . . . . . . . . . . 89

3.32 Averaged PQ Sensitivity Results for Domestic Loads . . . . . . . . . . . . . . . . . 90

4.1 Generic UK Network Topology Metrics . . . . . . . . . . . . . . . . . . . . . . . . . 98

4.2 Real LV Network Topology Metrics . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

4.3 IEEE European Network Topology Metrics . . . . . . . . . . . . . . . . . . . . . . 100

4.4 Cost of UG Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

4.5 Cost of OH lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

4.6 Cost of Full Substations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

5.1 De-regulation LCT Proliferation Scenarios (%) . . . . . . . . . . . . . . . . . . . . 105

5.2 Network Loss Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

5.3 Substation Energy (kWh/day) and Network Efficiency . . . . . . . . . . . . . . . . 118

6.1 LCT Proliferation Scenarios (%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

6.2 Cable Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

6.3 APF Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129

6.4 Scenarios considered without Constraints . . . . . . . . . . . . . . . . . . . . . . . 130

A.1 Classification of Loads in CREST Simulator Worksheet . . . . . . . . . . . . . . . 151

xv

Glossary

APF Active Power Filter

CBA Cost Benefit analysis

CNE Combined Neutral Earth

CPL Customer Path Length

CPZ Customer Path Impedance

CT Constant Torque

CVR Conservative Voltage Reduction

CWSH Cooking, water heating, and space heating (Small)

DG Distributed Generation

D-LCRS Diversified Line rating per customer served

DNO Distribution network operator

DR Demand Response

EHP (Electric) Heat Pump

FCL Fault Current Limiter

FES Future Energy Scenarios

GHG Greenhouse gas

HV High Voltage

LCT Low carbon technologies

LRCS Line rating per customer served

LV Low Voltage

MFC Mid-feeder Compensator

OLTC On-load tap changer

PCC Point of Common Coupling

PED Power Electronic Device

PES Power Electronic Transformer

xvi

PEV (Plug-in) electric vehicle

PME Protective Multi Earth

PoL Point of Load

PQ Power quality

PSU Power Supply Unit

PV Photo voltaic

SH Space Heating (Large)

SOP Soft Open Point

SST Solid State Substation

TSO Transmission system operator

ZIP Coefficients of Impedance, Current, and Power

xvii

Chapter 1

Introduction

In order to provide a framework for the UK to reduce its greenhouse gas (GHG) emissions, the

UK parliament passed the climate change act of 2008 [2]. This act sets out goals and legislation

to facilitate an “economically credible emission reduction path”. The headline target is to reduce

CO2 (and other GHG) emissions by 80% come 2050, relative to levels in 1990. In order to achieve

this there must be a transmission from fossil fuels to low carbon equivalents across a range of

sectors, not just the power sector. Within the power sector there has already been a significant

shift from coal and gas to renewable sources such as large offshore wind farm projects [3] and

smaller distributed generation (DG). However, for upcoming carbon budgets, and the eventual

2050 target to be reached, the committee on climate change (CCC) state progress in other sectors

is required, in particular the domestic (residential) and transport sectors are key priorities [4].

Reducing GHG emissions in a cost effective way in the domestic sector can be achieved by

changes such as improvements to the thermal efficiency of buildings, and take up of electric heat

pumps (EHP) or district heating schemes. Whilst for transport, improved vehicle efficiency, real-

istic and independent vehicle testing, and an increasing share of plug-in electric vehicles (PEV),

are needed for the UK to meet climate change targets [4].

The take up of PEV and EHP represent increasing electrification of the transport and domestic

heating sectors respectively. Electrification, which is the process of moving from other energy

sources to electrical sources, when combined with use of renewable generation, nuclear power,

carbon capture and storage (CCS), and bioenergy, are the low carbon technologies (LCTs), that

along with more general energy efficiency schemes will enable the UK to meet 2050 targets.

However, the issue for the distribution networks operators (DNOs) is how they accommodate

these LCTs efficiently and economically, whilst still providing the quality of service (QoS) required

[5]. In particular it is know that the power quality (PQ), which measures the quality of the supply

voltage [6], is degraded by connection of LCTs [7]. The usual method to alleviate these issues is

reinforcement, but this is very costly and disruptive [8].

1

1.1. GHG Emission Progress Thus Far 2

1.1 GHG Emission Progress Thus Far

Since the climate change act [2] was passed, progress in reducing GHG emissions has been largely

the result of a transition from fossil fuel based generation to low carbon alternatives. GHG emission

figures from the department of Department of Energy & Climate Change (DECC) [9] are shown

in Figure 1.1, were the vertical red line indicates the year the climate change act was brought into

effect (2008). From the nine sectors of GHG sources which DECC uses, the transport sector is the

second largest source of GHG emissions with the domestic sector fourth.

1990 1995 2000 2005 2010 2015

Year

0

100

200

300

MtC

O2e

Energy supply

Business

Transport

Public

Residential

Figure 1.1: GHG Emission in Million Tones of CO2 equivalent (MtCO2e)

GHG emission reduction in the energy supply sector coupled with electrification of transport

and domestic heating can be effective in reducing three of the four biggest GHG emission sectors,

a necessary step in achieving later carbon budgets and the 2050 target [4].

Internationally the Paris Agreement was drafted in December 2015 and if ratified by at least

55 countries which produce over 55% of the world GHG gasses will come into force [10]. The

aims of the agreement are to limit the global rise in temperature to well below 2 �C pre-industrial

levels, and to pursue efforts to actually limit the temperature rise to 1.5 �C. Another aim of the

agreement is to reach zero net emission by 2060-2080.

Three of the sectors DECC uses in grouping GHG emission are particularly relevant when

considering their coupling to LV electrical distribution network, namely:

� Energy Supply

� Domestic

� Transport

1.1. GHG Emission Progress Thus Far 3

Energy Supply

The amount of electricity generated from, and the installed capacity of, renewable sources in the

UK has risen rapidly in recent years, this can be seen in Figure 1.2 were in 2015 the total electrical

generation capacity of renewables was over 30GW a significant portion (36%) of the UK’s total

generation capacity of 82GW [11].

1996 1998 2000 2002 2004 2006 2008 2010 2012 2014

Year

0

2

4

6

8

10

GW

Onshore Wind

Offshore Wind

Wave & Tidal

Solar photovoltaics

Hydro

Bioenergy

Figure 1.2: Installed Electrical DG Capacity

Particularly obvious is the recent growth in solar photovoltaics (PV) since 2010 which has been

supported by feed-in tariffs (FiT), resulting in over 24% of the PV generation capacity being small

scale installations (�4kW) connected to the LV distribution network [12].

Due to the intermittent nature of some renewables sources, the installed capacity needs to

be considered alongside the actual energy generated. In terms of electricity generated by these

sources, renewables accounted for 24.6% of all the electricity generated in the UK [11]. The load

factor relates capacity to annual generation, and is:

Load Factor � 100�Generation

Capacity � 365� 24(1.1)

The load factor of nuclear power stations is typically very high and was over 75% in 2015,

and for other fossil fuel power plants, typically ranges from 30% to 50%. In contrast renewables

typically feature much lower load factors as shown, along with the capacity, in Table 1.1.

Table 1.1: Renewable Generation and Load Factor in 2015

Tecnholgy Generation (GWh) Load Factors (%)

Onshore Wind 22887 28

Offshore Wind 17423 39

Wave & Tidal 2 3

Solar photovoltaics 7561 9

Hydro 6289 41

Bioenergy 29388 64

Total 83550 31

1.1. GHG Emission Progress Thus Far 4

Domestic

Emissions from all buildings, whereby all buildings encompasses, commercial, residential and public

buildings, are shown in Figure 1.3. As heating is a major component of building energy demand

Figure 1.3 also shows a temperature adjusted value of GHG emissions.

2004 2006 2008 2010 2012 2014

Year

80

90

100

110

120

MtC

O2e

Historic

Actual

Temp Adjusted

Figure 1.3: GHG Emissions from the Domestic Sector

Most clearly indicated in the temperature adjusted values, it is seen that GHG emissions

from buildings are generally reducing, this is in spite of small increases to the overall number of

buildings. The reasons for this are due to increases to building thermal efficiency, resulting for

better insulation, and improved device efficiency. Table 1.2 presents GHG emissions figures for the

domestic sector. In Table 1.2 the “electricity” emission come as a result of the generation required

for the loads used within the buildings.

Table 1.2: GHG Emissions From Buildings in 2015

Building TypeDirect Electricity Combined

Share MtCO2e Share MtCO2e Share MtCO2e

Residential 13 64.7 8 39.7 21 104.5

Public 2 10.0 1 29.8 3 39.9

Commercial 2 13.1 6 5.1 8 18.2

Total 17.6 87.9 15 74.6 32.6 162.5

In de-carbonising the power generation sector, the GHG emissions related to buildings elec-

tricity demand will also reduce, as the actual GHG emissions appointed to electrical energy use

within households are the GHG emissions from the part of power sector which supplies this energy

demand. This effect can be amplified if there is a transition from direct emissions within these

buildings to electricity emissions (ie. the process of electrification).

1.1. GHG Emission Progress Thus Far 5

Transport

Emission from the transport sector are now the largest single source of temperature adjusted GHG,

emissions accounting for 24% (118 MtCO2e) of overall GHG emissions [4]. Whilst demand for

travel has increased, the improvements to vehicle efficiency have offset this, resulting in somewhat

steady GHG emissions figures over recent year as is shown in Figure 1.4.

2004 2006 2008 2010 2012 2014

Year

80

100

120

140

MtC

O2e

Transport

Figure 1.4: GHG Emissions from the Transport Sector

Surface transport accounts for 95% of the overall transport emissions, with the remainder due to

sea and air travel. In surface transport, the use of cars remains the main source of GHG emissions

as shown in Table 1.3 which presents GHG contributions by surface transport vehicle type.

Table 1.3: Surface transport Emissions

Vehicle GHG (MtCO2e)

Cars 68

HGVs 19

Vans 17

Buses 3

Rail 2

Other 1

The CCC suggest that the main driver for reduced emissions will be improvement to the

efficiency of conventional internal combustion engine (ICE) based vehicles, whist beyond 2020 take

up of PEV and other ultra low emission vehicles (ULEV) will become increasingly important [4].

Uptake of PEV will require investment in development of a new charging infrastructure system,

reinforcement of the distribution network, and generation capacity to handle the increased load

from PEV charging demand. Indeed, the present lack of distributed vehicle charging infrastructure

is already cited as a key barrier to the uptake of PEVs [13].

1.2. Future Predictions 6

1.2 Future Predictions

The National Grid’s Future Energy Scenarios (FES) document [14], outlines how demand placed

upon the gas and electric transmission networks (which are both owned and operated by the

National Grid) will change up to the year 2050, under 4 possible scenarios:

� Gone Green

� Slow Progression

� No Progression

� Consumer Power

In the gone green scenario, within the residential sector, there is a large increase in electrical

energy consumption driven by uptake of EHP (also to a lesser extent air conditioning) and PEV

charging. Similar uptake of these LCTs is seen in the consumer power scenario but with less

emphasis placed on reducing GHG emissions. Both the slow, and no progression scenarios have

much lower LCT uptake, in large part due to the limited financial backing for LCT growth these

scenarios envision.

Electrical energy demand predictions is shown in Figure 1.6, where by 2040 annual electric

demand is up to 384 TWh/year a 15% increase from present levels in the gone green scenario.

This rise in demand increases to 62% when only the electrical demand from domestic and transport

sectors are considered; it is these two sectors that are severed primarily by the low voltage networks

(for transport when considering electric vehicles).

2005 2010 2015 2020 2025 2030 2035 2040Year

300

320

340

360

380

400

TW

h/Year

HistoricGone GreenSlow ProgressionNo ProgressionConsumer Power

Figure 1.5: Electrical Energy Demand by the Domestic Sector without EV

At the same time as these significant increases to potential loading, the increasing amount of

PV installed is predicted to continue growing for the foreseeable future as shown in Figure 1.7.

Worth noting is that the growth in PV capacity by 2040 is over 440% compared to the present

1.2. Future Predictions 7

2005 2010 2015 2020 2025 2030 2035 2040Year

300

320

340

360

380

400TW

h/Year

HistoricGone GreenSlow ProgressionNo ProgressionConsumer Power

Figure 1.6: Electrical Energy Demand in the whole domestic sector

installed capacity in the consumer power scenario, and significant in all but the no progression

scenario. Additionally, PV generation patterns do no coincide with the peaks in domestic demand

which would thus require large amounts of distributed energy storage where the PV generation

sources to reduce the peak demand in the LV network.

2015 2020 2025 2030 2035 2040

Year

0

10

20

30

40

50

GW

Gone Green

Slow Progression

No Progression

Consumer Power

Figure 1.7: Installed Solar Generation

The overall theme from the FES report when specifically considering the effect on the LV

distribution networks is, that for all but the no progression scenarios there are substantial increases

to low carbon generation (particularly solar PV), and substantially increased electrification of

transport and heating. In effect this means that the loading (demand) will increase, alongside the

generation within the LV network. Thus, the traditional peaks and troughs seen in the demand

profile of a substation be exacerbated by both, with sufficient generation at LV causing reverse

power flow upstream in the network, which is seen as negative troughs in the demand profile.

1.3. Effects of Increased Load & Generation 8

1.3 Effects of Increased Load & Generation

Given we can expect the loading and generation within LV distribution networks to increase due

to LCTs, variations in voltage profile across network would also be expected to widen [15]. Dur-

ing times of peak demand the network voltages are suppressed relative to the no-load condition,

particularly at points in the network most distant from the supply, that is at remote feeder ends.

DG, even with modest proliferations, is known to cause reverse power flows in the main feeder

and even the secondary substation thus increasing the voltage profile [16] such that the voltage at

the LV consumer point of common connection (PCC) can increase above the regulatory maximum

(+10%, -6% of nominal voltage [17]). Beyond a wider voltage profile, LCTs also cause a reduction

in other power quality measures [18, 19], potential increases to fault current levels [20], and ulti-

mately network thermal limits being breached in localised parts of the network [21]. These four

network issues will all ultimately limit the amount of LCTs that a given network can accommodate

without preventative measures being taken. These LCT hosting constraints are shown in Figure

1.8.

Voltage Thermal FaultCurrent

PowerQuality

NetworkConstraint

Figure 1.8: Four network capacity constraints

As indicated in Figure 1.8, it is ultimately the thermal limits of the network that represent the

final barrier to increasing LCT hosting capacity and so, eventually reinforcement will be required

to accommodate further LCT growth. However, by removing other network constraints if they

are encountered prior to thermal limits, or alternately, extending the thermal limits when they are

reached, increased network capacity can be released without costly and disruptive reinforcement

measures. Each of these four hosting constrains is next presented in further detail.

Voltage Regulation Limits

The cause of voltage change across any feeder can be seen by first considering of the simple two node

network shown in Figure 1.9 where the feeder is represented by a single phase lumped impedance,

which connects the sending and receiving ends of the network.

The phasor digram of the line is shown in Figure 1.10 where the voltage at the sending (Vs) and

1.3. Effects of Increased Load & Generation 9

R + jX

Vs Vr

I

Figure 1.9: Two Node Network

receiving (Vr) ends of the line are shown. From these two voltages, the voltage difference (ΔV )

between the two phasors is simply the phasor that connects both the sending and receiving end

voltages (as in Figure 1.10), which is the product of the current (I) and line impedance (Z).

Vq

VpI

Vr

IR

IX

Vs

Figure 1.10: Voltage Over the Network Line

The key difference between transmission and distribution networks when considering ΔV , is

the system X/R ratio. For transmission systems the X/R ratio might typically be around ten [22],

whilst in distribution networks the value is much lower, and often well below unity [16,23,24].

ΔVp � IR cos�θ� � IX sin�θ� (1.2)

ΔVq � IX cos�θ� � IR sin�θ� (1.3)

Given that P � V I cos�θ� and Q � V I sin�θ� we rewrite (1.2) and (1.3) as:

ΔVp �RPs �XQs

Vs(1.4)

ΔVq �XPs �RQs

Vs(1.5)

We then note that for all practical networks (both distribution and transmission), and even under

heavy loading, the direct axis voltage (ΔVp) will have a larger effect on the magnitude of the

received voltage (�Vr�) due to the load angle (δ) being small:

ΔVq � Vr �ΔVp (1.6)

1.3. Effects of Increased Load & Generation 10

Thus,

ΔV �RPs �XQs

Vs(1.7)

The sensitivity of ΔV is found by taking the partial derivatives of (1.7) w.r.t P and Q:

dΔV

dP�R (1.8)

dΔV

dQ�X (1.9)

What (1.8) and (1.9) show is that it is the active power flow (P ), not the reactive power (Q),

which has the greater effect upon voltage magnitude when the network feeders X�R ratio is low,

as is true in distribution networks. Equally, the converse is true in transmission systems or EHV

distribution networks where the X�R ratio is much greater [22]. Hence, it is due to the lower X�R

ratio of LV networks as compared to transmission systems, that the voltage drop along a LV feeder

is dominated by the resistive (R) rather than reactive (X) element of the feeder cable.

Thermal Limits

As the use of overhead cables in urban areas is not a preferable solution to the DNOs due visual

and social objections, thus the great majority of urban networks use predominantly underground

cable [25]. Compared to overhead lines, the thermal time constants in underground insulated

cables are very long and influenced not only by the ampere heating effect in the cable, but also

the proximity to other heat sources (cables), the ground temperature, and the heat stored in the

cable insulation layers. As such there are IEC and IEEE standards for calculation of the steady

state operation of underground cables [26] and for cyclic and emergency ratings of underground

cables [27], the latter of which are more appropriate for LV networks due to their cyclic loading

and high diversity factors.

Once a suitable rating has been deduced, either static, seasonal, or dynamic, the DNO will aim

to operate cables to within these limits, taking measures necessary to avoid frequently breaching

these limits. This is because as the cable is operated at higher loading the temperature increases

and the life expectancy of the cable is degraded [28]. This can be seen in Figure 1.11 where data

is for an XLPE insulated cable and lifetime is calculated based on the Arrhenius model (AM) [29],

which couples thermal and electrical stresses to expected cable lifetime.

The economic balance between cable outlay and power losses (I2R) along with cable ageing

from thermal and electrical stresses is addressed in part 3 of the IEC 60287 standard [26]. In

order to remove thermal constraints power flows can be routed to less utilised routes, voltage

optimisation can be employed, unbalance in the phases can be compensated, loads / generators

1.3. Effects of Increased Load & Generation 11

70 80 90 100 110 120Temp (°C)

0

20

40

60

80

100Lifetim

e(years)

Figure 1.11: Cable Life Expectancy Due to Thermal Ageing

can be disconnected, or a certain reduction in plant lifetime can be accepted. Ultimately if these

are not possible or ineffective then network reinforcement is required.

1.3. Effects of Increased Load & Generation 12

Fault Current Limits

When a short-circuit happens in the distribution network, the upstream network and electrical

machines, from rotating motors with inertia and distributed generators can all act to feed a large

current into the fault. As the assets in the distribution network can handle only a certain amount

of fault current, protection devices have to be chosen to ensure these limits are not breached.

Should the fault current contribution increase, due to network reinforcement or additional fault

contribution from new DG, either fault current limiting equipment such as reactors will be need

or the system will need to be designed with higher short circuit levels in mind [30].

The prospective short circuit current (Isc) is greatest during three phase symmetrical faults, and

although these faults are less common than unsymmetrical faults [31] the ratings of the protection

systems are specified for worst case scenarios and as such three phase fault calculations are used

when rating protection equipment. A symmetrical solid three phase to ground fault (LLL-G) is

shown in Figure 1.12.

A

B

C

F

Figure 1.12: Three Phase to Ground Fault

The fault current for the above illustrated fault is:

Isc �U0�3Zsc

(1.10)

where U0 is the open circuit secondary voltage of the upstream transformer, and Zsc is the

impedance from the source to the fault.

Clearly if the impedance is lowered the prospective short circuit current will increase and from

Figure 1.12 if we assume DG is present downstream (right of fault) then fault current may be feed

from both sizes of the fault, further increasing the fault current. In meshed networks the fault

levels are also increased due to the existence of parallel feeds to the fault, for example, in radial

LV networks in London the maximum design fault current is 25kA whist for the meshed networks

of central London it rises to 46kA [32].

1.3. Effects of Increased Load & Generation 13

Power Quality Limits

Power quality (PQ) is a measure of the voltage waveform quality supplied to customers on the

electrical network, and is as defined in standards such as EN50160 [6]. Voltage magnitude, as

mentioned in section 1.3, is also PQ measure but for the purposes of this thesis it has been

considered separately throughout.

Table 1.4 lists some of the PQ limits defined in the EN50160 standard, along with other

standards relevant to the UK.

Table 1.4: Summary of Power Quality Statutory Limits

Voltage Issue DefinitionPeriod of

AcceptanceMeasurement Monitoring

Frequency�0.5 Hz 10 sec 1 Week 95%

+2,-3 Hz 10 sec 1 Week 100%

Over 110% 10 min 1 Week 100%

Under 94% 10 min 1 Week 95%

Sag / Dip 85% 10 ms 1 Year �1000

THDv 8% 10 min 1 Week 95%

Unbalance1.3% NA 30 min �5 min

2.0% 10 min 1 Week 100%

The power system frequency must be tightly maintained (within 1%), but provision is made

for small islanded systems where frequency excursion are more pronounced due to smaller system

inertia.

Voltage unbalance factor (VUF) has multiple definitions from various institutions [33], but

throughout the following definition is used:

V UF �V�V�

(1.11)

where the sequence voltage components are:

�����

V�

V�

V0

����� �

�����

1 α α2

1 α2 α

1 1 1

�����

�����

Va

Vb

Vc

����� (1.12)

the complex α rotational 120� operator is:

α � e2iπ3 . (1.13)

It is worth noting that voltage balance is a 3 phase (or poly phase) system measurer and is

not measurable at single phase branches of an electricity network. The salient concern regarding

1.3. Effects of Increased Load & Generation 14

voltage unbalance is due to the heating effect it has on three phase motors. This is shown in Figure

1.13 where it can be seen that with 7% VUF the heating effects on motor are doubled relative to

the case with a balanced supply voltage [34].

0 1 2 3 4 5 6 7VUF (%)

0

20

40

60

80

100

Add

iona

l Tem

p R

ise

(%)

Figure 1.13: Temperature Rise of Motor Due to Voltage Unbalance

Total harmonic voltage distortion (THDv) is a measure of the overall potential heating effect

of the harmonic content in the supply voltage waveform [6]. It is calculated as:

THDv �

�40�

n�2V 2n

V1(1.14)

where Vn is the amplitude of particular harmonic voltage component. Further to a THDv limit,

limits for specific harmonics are presented in EN50160, these are given in Table 1.5 for all harmonics

up to the 25th.

Table 1.5: Limits on Specific Harmonic Voltages (n � 25) as Percentage of Fundamental

OddEven

Not Multiples of 3 Multiples of 3

Order (n) Magnitude (%) Order (n) Magnitude (%) Order (n) Magnitude (%)

5 6 3 5 2 2

7 5 9 1.5 4 1

11 3.5 15 0.5 6–24 0.5

13 3 21 0.5 - -

17 2 - - - -

19, 23, 25 1.5 - - - -

1.4. Solutions to Networks Constraints 15

1.4 Solutions to Networks Constraints

To remove any of the network constraints mentioned in section 1.3, a range of options are available

to the DNO. These approaches are grouped into power electronics based options, and other ap-

proaches, which encompass network operation schemes, novel grid technologies (potentially power

electronic based), and the traditional methods of reinforcement.

1.4.1 Power Electronics

Power electronics has been used for improvement of both the stability and capacity of the transmis-

sion network since the 1990’s with the flexible AC transmission systems (FACTS) family of power

electronic based devices [35]. Additionally large high voltage direct current (HVDC) transmission

links [36] utilising naturally commutated thyristors or forced commutation converters using GTOs

or IGBTs have been used since the 1970’s.

Within the distribution network however there is little power electronics used for the distribu-

tion of energy [37]. This is in-spite of the fact that the UK DNOs are aware traditional methods of

reinforcement cannot deliver increased network capacity in the short term and that large scale re-

inforcement, whist effective, is often initially under utilised and thus scope for smaller incremental

upgrades exists. This is the main premise of power electronics for investment “deferral”, that is to

release capacity in the short term allowing larger networks upgrades at a later time when power

electronics can no longer be used or is no longer able to remove increased capacity constraints.

Within this thesis 5 main power electronic based devices will be considered:

� Power Electronic Substation (PES) / Solid State Transformer (SST)

� Mid Feeder Compensator (MFC)

� Active Power Filter (APF)

� On-load Tap Changers (OLTC) for LV Transformers

� Soft Open Point (SOP)

Additionally, a power electronic point of load (PoL) regulator is considered in Chapter 5 for

removal of voltage limitations, thus allowing a fully de-regulated electrical network where the PoL

device is used to regulate the voltage for the end user’s connected loads and thus ensure operation

at rated voltage.

Each of the power electronic devices (PEDs) relative ability to remove the network constraints

mentioned in section 1.3 are listed in Table 1.6, were an “x” indicates the PED is able to remove the

particular network constraints whilst a “-” indicates that the PED not able to, or is very limited

in its ability, to remove the given network constraint.

1.4. Solutions to Networks Constraints 16

Table 1.6: PED Solutions to Limitations in Network Capacity

SolutionNetwork Constraint

Voltage Thermal Fault PQ

SST x - x x

MFC x - x x

SOP x x x x

APF - x - x

OLTC x - - -

Only the SOP is able to improve all of the networks constraints whilst, only the APF is unable

to significantly improve voltage regulation in the LV network, which is in urban arena networks is

the most frequently encountered hosting constraint stemming for LCT uptake [15].

1.4.2 Other Approaches

Beyond the use of PEDs there is considerable research and investment into a range of technologies

and network operation schemes that aim to defer network reinforcement. These include:

� De-regulation

� Dynamic asset rating

� Active network management

� Demand response

� Energy storage systems

� Fault current limiters

� Network Reinforcement

De-regulation

De-regulation involves relaxation of the tolerances on voltage magnitude [38] (and other PQ)

limits, thus allowing for greater proliferation of LCTs where voltage constrains exist, whist not

adversely effecting the loads connected to the network. As the existing voltage limits in the UK

are -6%/+10% from nominal voltage (230V) [39], if the supply voltage at the point of common

coupling (PCC) to the consumer is outside of these limits for more than 5% of the time (see Table

1.4) then the LV network voltage regulation need to be improved. However, if the only network

constraint is that of voltage magnitude by removing (or relaxing) the voltage tolerance, capacity

is released without need of any network upgrades or reinforcement.

1.4. Solutions to Networks Constraints 17

The key requirement of de-regulation is that connected loads must not be adversely effected by

any of these new voltage limits. This can be achieved by limiting the amount of de-regulation to

levels which do not adversely effect most goods [38] or by providing a “firewall” between the LV

networks and the loads, in the form of a PoL regulation device. Figure 1.14 shows how the supply

voltage magnitude effects common domestic loads along with existing and proposed regulatory

limits. In the figure the goods are sorted from left to right monotonically increasing with maxium

and minium supply voltages for the goods mentioned being indicated.

Figure 1.14: Effect of Supply Voltage on Common Domestic Goods from [40]

Deregulation can be considered “passive” solution to voltage regulation, were various levels of

de-regulation can be considered, such as:

� EU limits (�%10)

� Load operation limits [38] (+%10,-15%)

� No regulation

These levels of de-regulation are compared in Chapter 5 of this thesis, whilst the “load operation

limits” de-regulation scenario is justified in Chapter 3.

Dynamic asset rating

Dynamic asset rating (DAR) seeks to adjust the thermal limits placed on network equipment in

response to both environmental and operational conditions. It has been shown that DAR can

effectively increase the loading capacity of network assets, particularly during winter months [41].

When DAR is used across a network it is termed dynamic network rating (DNR). Figure 1.15

shows the monthly rating of a oil natural air natural (ONAN) cooled transformer over the course

of a year using both static and dynamic ratings.

1.4. Solutions to Networks Constraints 18

Figure 1.15: Rating of Transformer Using Static and Dynamic Ratings from [41]

Increases in transformer rating of up to 20% are possible during winter months which is when

peak loading of LV networks occurs due, primarily, to increased heating demand. Similar results

were presented for both underground cables and overhead lines [41].

Active network management

Active network management (ANM) utilises real time monitoring of the distribution network along-

side representative system models to optimise the system operating conditions. For example, volt-

age levels and power flows are controlled by means of coordinated OLTC operation and demand

shifting in [42]. Prospective fault level can also be limited in ANM schemes, such that network

switches are controlled to limit potential fault currents [43] to permissible values.

Table 1.7 shows DG curtailments using a last in first off (LIFO) rule and an AuRA-NMS based

(i.e an active network management control scheme) rule when additional DG is connected to two

nodes (5010 and 5018) in a test network [42].

The study incrementally added capacity to the HV test network and using the two mentioned

control schemes compared the energy curtailment the network required over the course of one year

to avoid breaching voltage or thermal constrains in the nodes and lines of the network. We see the

ANM strategy reduces DG curtailment at the expense of the remote monitoring and controllers

required to achieve the ANM control actions.

Demand side management

Demand side management (DSM) encompasses demand response (DR) which allows the loads to

take an active role in system operation by changing time of use patterns in response to network

signals or parameters. The ultimate aims of DR being to better allow the load to match generation

and reduce or smooth out peaks in demand. In particular, the present case whereby generation

1.4. Solutions to Networks Constraints 19

Table 1.7: DG Curtailment with additional DG installed at Nodes 5010 and 5018

New DGCapacity (MW)

LIFO rule (MWh) Proposed rule (MWh) Difference(MWh)# 5010 # 5018 # 5010 # 5018

20 0 0 0 0 0

22 21 0 1 0 20

24 128 0 6 0 122

26 756 0 32 0 726

28 2107 0 132 0 1975

30 3142 2 306 0.05 2838

40 6944 2438 1726 184 7472

changes in response to the demand becomes increasingly unsuitable (requiring backup generation

capacity) as the proliferation of intermittent DG sources grows [44].

The principle of DR is shown in Figure 1.16 along with an energy efficiency (marked EE) plot

showing how energy consumption can also be reduced by improving the efficiency of electrical loads

(e.g with low energy lighting). The two DR plots (with and without rebound) also show how DR

may or may not effect the total energy consumption indicated by the area under the respective

curve. In either case, both of the DR plots are seen to reduce the peak seen in the middle of the

graph.

Figure 1.16: DSM and its effect on demand profiles [45]

Energy storage systems

Energy storage systems (ESS), like DR, reduce the need for backup generation capacity by stor-

ing energy using a combination of flywheels, hydrogen fuel cells (FC), compressed air (CAES),

capacitors (EDLC), batteries and pumped hydro to help match generation to demand. For this

reason they are sometimes included as DSM technologies [45]. ESS increase the system demand

during periods of excess generation whist generating or supplying energy during periods of excess

demand. Furthermore, distributed energy storage systems (DESS) can have very rapid response

1.4. Solutions to Networks Constraints 20

times thus improving networks stability and frequency regulation [46] and being distributed reduce

transmission losses.

There are many forms of ESS each with certain advantages and disadvantages, some of the key

technologies uses are presented in Table 1.8.

Table 1.8: Comparison of ESS Types [47]

TypeEfficiency

(%)Energy Density

(Wh/kg)Power Density

(W/kg)Cycle Life

(cycles)Self

Discharge

Pb-acid* 70-80 20-35 25 200-2000 Low

Ni-Cd* 60-90 40-60 140-180 500-2000 Low

Ni-MH* 50-80 60-80 220 �3000 High

Li-ion* 70-85 100-200 360 500-2000 Mid

Li-polymer* 70 200 250-1000 �1200 Mid

NaS* 70 120 120 2000 -

VRB** 80 25 80-150 �16000 Negligible

EDLC 95 �50 4000 �50000 Very High

Hydro 65-80 0.3 - �20 years Negligible

CAES 40-50 10-130 - �20 years -

Flywheel 95 5-30 1000 �20000 Very High

* Denotes Type of Battery or ** Flow Battery

Fault current limiters

Fault current limiters (FCL), limit the fault current levels in the network, thus reducing the

fault ratings of the network protection equipment. As the planning requirements and costs of

circuit breakers are particularly high, FCL offer economic advantages compared to reinforcement

or replacement of the protection systems. In particular, increased fault levels stemming from DG

(where it contributes to faults levels) or network reinforcement can be controlled with FCL. The

ideal FCL features [48]:

� Instantaneous Fault Detection

� Rapid Reduction in Fault Current

� An ability to handle many types of faults

� Automatic Resets capacity without human maintenance

� A Compact and Lightweight package

An example of a FCL, limiting fault current is shown in Figure 1.17, where the FCL fault current

can be controlled so protection systems operate as expected, but are not subject to excessive fault

current.

1.4. Solutions to Networks Constraints 21

Figure 1.17: Prospective fault current (red) and fault current with an FCL (green)

Summary of the Other Solutions

To briefly summarise these technologies, Table 1.9 lists their relative ability to influence network

hosting constraints mentioned in section 1.3.

Table 1.9: Other Solutions to Limitations in Network Capacity

SolutionNetwork Constraint

Voltage Thermal Fault PQ

Reinforcement x x x x

De-regulation x - - x

DAR / DNR - x - -

Active Network Man. x x x x

Energy Storage x x - -

Demand Response x x - -

Fault Current Limiters - - x -

Only active network management, and network reinforcement are able to alleviate at of the

hosting constraints. Nonetheless a mixture of all the above technologies would be expected whereby

the application of a given technology is based on cost befit analysis (CBA) performed by the DNO.

1.5. Problem Statement and Thesis Outline 22

1.5 Problem Statement and Thesis Outline

Problem Statement

Distribution networks are presently subject to increased loading from electrification of transport

and heating, whilst at the same time distributed generation (typically PV) and use of co-generators

(μCHP) supply energy back to the networks and, in sufficient quantity, cause reverse power flow

(or back-feeding). The result is that PQ measures are often breached prior to thermal limitations,

and in particular the supply voltage magnitude can become a severe limitation to suitably hosting

further increases to the loading of, and generation present on, the network. The usual solution,

that is reinforcement, whilst effective, is very costly and time consuming, thus alternative measures

to reinforcement are sought.

Thesis Outline

This thesis explores two of these alternatives to network reinforcement, that is, de-regulation

of voltage tolerances, and the use of PEDs to improve voltage regulation. To asses how these

compare to network reinforcement, a review of distribution networks themselves is first presented.

Following this the specific PEDs considered in this work are presented, where an overview of

their topology, control, and performance is given. In the case of wider voltage tolerances, the

load models themselves become increasingly important as if the loads exhibit any form of voltage

dependency this needs to be captured within the model. Therefore load models are considered in

detail, alongside the commonly used methods to represent single phase LV domestic loads, and

how PQ voltage sensitivity can be implemented in these.

The issue of voltage de-regulation is presented in Chapters 2, 3 and 5. Background informa-

tion presented in Chapter 2 on load modelling is then used to asses how de-regulation will effect

connected loads subject to this de-regulation where the focus is entirely on domestic loads, as

in Chapter 3. From this a relationship between the supply voltage and correct load operation

is formed and by setting various permissible limits on the amount of loads for which their mal-

operation can be accepted we have corresponding ranges (or levels) of de-regulation. These levels

of de-regulation are then used to asses how LCT hosting capacity could be increased as a result of

their application to LV networks in Chapter 5.

The PEDs considered in this work are presented in Chapters 2 and 5. The control structure

and layout of each of the PEDs is presented (Chapter 2) and each device is then implemented

into LV test networks, then analysed, where the benefits brought about by this are presented in

Chapter 6.

This thesis is divided into 6 subsequent chapters, each organised as follows:

1.5. Problem Statement and Thesis Outline 23

� Chapter 2 presents the background material on the topics of: distribution networks, power

electronic devices, and loads modelling. The operation and control schemes of distribution

networks are discussed along with a presentation of the equipment that is used within the

network. The PEDs are discussed in terms of their control objectives, and how these are

applicable to removing hosting constraints in these networks. Load models used in the

literature are presented along with benefits and disadvantages of these models, particular

attention is given to how the load models are effected by changes in the supply voltage (i.e

their voltage sensitivity).

� Chapter 3 presents an assessment of the impact that changes to supply voltage tolerance will

have on domestic loads. In particular, the energy demanded by, and amount of, common

domestic loads are presented first. After grouping loads into classes based on their electrical

characteristics, experimental and simulation based work on: motor loads (found in white

good) and, power supply unit (PSU) magnetics (found in modern consumer electronics), are

presented. A review of the literature relating to experimental testing of domestic loads in

terms of their sensitivity to supply voltage magnitude is presented. Results from this are then

combined to give an indication of what voltage tolerances could potentially be implemented

without large scale malfunction of consumer loads.

� Chapter 4 presented the methodology used in assessing how either voltage regulation or PEDs

can be fairly compared to network reinforcement. Individual steps involved in this process

are then given in detail. Implementation of LV network load flow are first explored. Test

LV networks are then presented along with developed metrics to compare these networks.

The Monte Carlo simulation method is then presented and its use justified. Finally the

economic measures to asses the cost benefits of de-regulation and PEDs relative to network

reinforcement are given.

� Chapter 5 presents results regarding voltage de-regulation of the supply voltage. Varying

“levels” of de-regulation are consider and the benefits associated with each tolerance band,

in terms of their ability to realise additional hosting capacity for LCTs are compared.

� Chapter 6 presents results regarding the use of PEDs in LV distribution networks. The 5

different PEDs are compared initially to each other and then to network reinforcement. Eco-

nomic comparisons whereby the PEDs are used for asset replacement or investment deferral

are then presented.

� Chapter 7 gives conclusions from this work, with particular attention given to the results of

Chapters 5, and 6. Also given are the authors contributions and then recommendations for

further work.

Chapter 2

Background

The aim of this chapter is to provide the relevant technical background on areas that are built

upon in subsequent parts of the thesis. Namely, the specialised areas of:

� Distribution Networks

� Power Electronics for Electricity Distribution

� Domestic Load Profiling

are covered within.

The section on distribution networks is specific to UK networks, although these are largely

typical of European networks. The layout and operations schemes of the distribution networks are

first presented, then an overview of the individual plant (eg. underground cables) that together

form the distribution network is given. Relevant electrical parameters and modelling techniques

for this equipment are also presented.

The section on power electronics focuses upon power electronic topologies that are suited to

applications in low voltage networks rather than providing a general overview of power electronics

itself. For each of the devices the relevant literature is reviewed and, control schemas, physical

implementation, and performance characteristics are presented.

The section on load modelling focuses upon generation of high resolution single phase domestic

load profiles that are suitable for study with a wide supply voltage range. This builds upon the

CREST load profile generation tool [49]. As Chapter 5 considers how voltage tolerances effect LV

network hosting capacity, the ability of the load models to suitably respond to wide changes in

supply voltage is particularity important. Load profiles for new LCTs are also synthesised from

available data in the literature and this procedure is also outlined here.

24

2.1. Distribution Networks 25

2.1 Distribution Networks

In this section the typical plant operated by DNOs will be presented, the representative costs

and operating principles of this equipment is also given. The aim is to give a review of literature

specialised to distribution network plant in the UK along with an understanding of the network

itself and the problems it faces due to LCT uptake. In particular the network from the primary

substation downstream (that is 11kV and below) is presented. Information is taken largely from

available literature produced by the DNOs (long term development strategies) in mainland Britain

[25, 30,50], EON’s network design manual [1], and the distribution code [51].

2.1.1 Network Structure

The transmission system operators (TSO) in the UK own and operate their transmission networks

(400kV or 275kV) which transmit bulk quantities of power over long distances, and connect to

major generating facilities. The DNOs connect their distribution networks to this transmission

network at grid supply points (GSP) and then operate their own sub-transmission systems (132kV).

The sub-transmission system supplies bulk supply points (BSP) where the voltage is further stepped

down (typically to 33kV). The primary distribution network (33kV lines) then supplies the primary

substations (typically 33/11kV). Occasionally GSPs are connected directly to primary substations

(132/11kV) thus by-passing both the primary network, and the BSP stations.

NOP

LV Link Box

Primary Substation

Secondary Substation

Distribution Cabinet

11kV Ring Main Unit

Figure 2.1: Layout of Existing HV Distribution Network

The single line structure of a generic secondary (termed HV network herein) distribution net-

work is shown in Figure 2.1. The primary substation supplies the HV network which as mentioned

2.1. Distribution Networks 26

typically operates at 11kV. Also shown is how the HV network supplies numerous secondary sub-

stations which in turn reduce the voltage to LV levels, and ultimately connect to the loads via

LV feeders. As seen in Figure 2.1, on load tap changers are operated at the primary substa-

tions, whilst for each primary substation transformer in reality there may be up to 60 connected

secondary transformers [25] connected across all the outgoing 11kV feeders.

At each secondary substation the connection to the HV network is made typically via a ring

main unit (RMU) which enables the substation to be connected to a HV ring circuit, improving

security of supply in the case of HV network faults [30]. For this, the RMU has 2 ring switches

and a circuit breaker that connects to the primary side of the transformer. The ring circuit

itself may be connected between two 11kV bus bars at separate different primary substations

(interconnected) or two sections of a busbar within one primary substation (looped). In low

density areas occasionally the substation will be connected to radial HV networks. These three

possible HV network structures are shown in Figure 2.2.

N.O.N.C.

N.C.

N.O. N.C.

N.C.

Radial Interconnected Looped

Figure 2.2: Structure of the HV Distribution Network

From the secondary of the LV transformer, the individual feeders are connected to a LV distri-

bution cabinet that contains of an incoming isolation link, a LV busbar and finally fuses for each

of the feeders. A typical secondary substation RMU and distribution cabinet are shown in Figure

2.3. When coupled with the transformer, the RMU, distribution cabinet, and transformer itself,

form the main components of the secondary substation.

The LV feeders in urban and suburban areas are almost exclusively underground where each

of the main (3 phase) feeders is terminated at a link box or pot end. A link box (see Figure 2.4b)

serves a termination point for multiple feeders and via street level access manual changes to the

links which connect 2 feeder, can be made, so they offer some decree of reconfigurability in the case

of a long term fault. A pot end is simply a insulated termination for a feeder so that any bare end

conductors are suitably protected from the environment. Along the feeder single phase service (or

3 phase) cables branch off and connect to the individual customers. The branch from the main 3φ

feeder to the service cable is made at a cable joint (shown in Figure 2.4a) which much like a pot

2.1. Distribution Networks 27

(a) Ring Main Unit (RMU) (b) Four way LV Distribution Cabinet

Figure 2.3: Secondary Substation Equipment

end, protects any exposed conductors from the environment. The service cable terminates at the

customers breakout board which also serves as the end of the DNOs ownership of the network and

thus the PCC where PQ and QoS requirements must be meet by the DNO.

(a) Branch joint (b) Two way Link Box

Figure 2.4: Underground equipment used along LV feeder ways

2.1.2 Operation & Protection

The causes of and appointment of voltage drop from the primary substation to the LV consumers

PCC assumed by DNOs are given in Figure 2.5.

The OLTC at the primary substation has a resolution around 1.5% of the nominal voltage, this

is shown as the 2% band at the top of Figure 2.5. The HV feeders should be designed to stay

within 6% of the nominal voltage [30] and up to 6% provision is made for voltage drop on the

HV system. The remaining voltage drop under normal operation (i.e when no are faults present,

or maintenance needing special routeing is taking place) is shown across the transformer (2%) and

the LV feeder (4-6%) where the amount permissible in the LV system depends upon the length of

the 11KV feeder serving the secondary substation, where a figure of 15km is given as the break

point between “long” and “standard” feeders.

The 6% contingency for back-feeding (reverse power flow) is required for security of supply and

re-routing, which would potentially result in excessively high or low voltages if this 6% contingency

2.1. Distribution Networks 28

Figure 2.5: Allocation of voltage drop among network components [1]

margin is not used.

The network is operated in a radial or more commonly open ring structure with interconnection

used to provide reliability of service following network faults. Consider an example of the single

line system shown in Figure 2.6.

A

C

B

Fault

Figure 2.6: Interconnected ring configuration of an 11kV network

As seen the two feeders are can be normally operated as distinct radial networks from the two

primary substations by virtue of opening any one of the three sectionaliser switches indicated at

locations A, B or C. For example, if we assume prior to the long term fault indicated, that switch

A was open whilst B and C were closed, for restoration of the supply to all of the substations

switch A would close whilst B and C both open. Worth noting is that the switches at A, B and C

would typically not have fault current breaking capacity (i.e the RMU uses switch disconnecters)

and in such a case would only operate after a circuit breaker has temporarily disconnected the

faulted lines.

2.1. Distribution Networks 29

2.1.3 Distribution Network Components and Plant

This section will present the network owned plant that is most critical to the accuracy of flow

studies, these are the:

� Primary Transformers

� Secondary Transformers

� HV Feeders

� LV Feeders

Primary Transformers

Primary Substations are typically the last point at which voltage control is installed in the dis-

tribution network. The primary substation will have on load tap changer (OLTC) transformers

installed, where the primary voltage is typically 33kV although other voltages are used, and the sec-

ondary voltage is 11kV or 6.6kV. The most common vector group of transformers used at primary

substations is Dyn11.

Figure 2.7: Primary Substation with Two 15MVA 33/11kVtransformers (from [52])

Transformers are usually installed in pairs rated at 15/30MVA (corresponding to ONAN/OFAF-

CER ratings respectively), but scope exists for transformers from 3/6MVA up to 20/40MVA and

single transformers can be used if the load served is below 12MVA [30]. In high density load

areas provision is also made for up to four parallel transformers, with dual winding secondary

transformers also occasionally used [50]. The 11kV star point of the transformer is earthed via

solid or resistive grounding. If the secondary winding is delta connected (as in the case of some

132/11kV transformers) then earth is made via an earthing transformer.

2.1. Distribution Networks 30

Voltage control here is achieved via OTLC with a 1.25% to 1.5% bandwidth and a tap range of

-5% to +10% [30]. As with much of the distribution system, voltage control is designed assuming

power flow is uni-directional; hence voltage control settings are such that voltage drop along

standard 11kV feeders can use the full permissible voltage range (�6% at HV [30]). This means

the voltage at the secondary side busbars is kept towards upper limits at times of peak demand

with typical reference figures of 1.05pu at full load and 0.985pu at no load [25].

Secondary Transformers

Secondary substations connect to the HV distribution networks (11kV or 6.6kV) and step down

the voltage to LV (400V 3φ / 230V 1φ) for distribution to, predominately, single phase customers.

In some rural setting single phase pole mounted transformers (25kVA to 50kVA) are used to supply

distant and widely dispersed customers [1]. For urban and semi-urban distribution, transformers

ratings for those supplying multiple domestic or commercial customers are limited to 1000kVA so

as to limit the disruption caused by faults at the substation. This is because a 1000kVA can supply

only a limited number of individual customers (708 customers assuming an after diversity maximum

demand (ADMD) of 2kW [1]). Where a larger single customer connects to a secondary substation

the permissible rating will be increased, for example, with Northern Power Grid the maximum LV

transformer rating for a transformer supplying single customer is 1600kVA. The smallest ground

mounted transformers used are 200kVA [1] due to the deceasing efficiency of smaller transformer,

and the lower cost of alternative padmount, unit, and pole-mounted transformers.

New use size transformers and their typical impedances (referred to the secondary LV side)and

losses are shown in table 2.1.

Table 2.1: 11kV/LV Transformer Impedances [1]

Size (kVA) LocationImpedance (Ω) Losses (W )

R X Iron Copper

50 Pole 0.0266 0.0496 110 800

100 Pad 0.0271 0.0401 200 1500

200 Ground 0.0158 0.0406 275 3000

500 Ground 0.0051 0.0171 600 7000

Voltage control at secondary substations is limited to no load taps at the transformer. The taps

are located at the primary windings and allow a voltage range, from nominal, of �5% with a 2.5%

resolution. The nominal voltage ratio of many LV transformers is actually 11kV/0.433kV [1, 30].

This is due in part to the previous voltage regulations (prior to 1998) where the voltage tolerance

was 240V �6% and to allow for voltage drop along the feeder [25].

The secondary winding star point is grounded within the substation along with all perimeter

metalwork. If the connected LV network is operated with protective multi-earth (PME) earthing,

2.1. Distribution Networks 31

Figure 2.8: Secondary Substation and LV Transformer (from [53])

the grounding impedance of the substation earth electrode of should not exceed 40Ω [25].

HV Feeders

The 11kV network uses a mix of underground and overhead lines, both in 3 wire arrangements.

In urban areas the vast majority of the 11kV networks is underground whilst in rural areas there

is a greater percentage of overhead liens. The length of the HV network will dictate it general

operation regarding interconnection and voltage profile, with long HV feeders defined as extending

over 15 km [1] from the primary substation.

Overhead Lines The conductors used for overhead lines are, stranded aluminium, uncovered,

and either ACSR (steel reinforced) or AAAC (all aluminium). The conductors are supported on

wooden poles with a specified conductor height of greater than 5.2m [54].

Figure 2.9: Typical 3 Wire Overhead Distribution Lines (from [55])

2.1. Distribution Networks 32

Conductor impedance matrix are developed for the conductors in Table 2.2 using the MATLAB

function power lineparam. The ground resistivity is assumed as 100Ω.m which is a very typical

value [23], and the standard geometry on the conductors are shown in the Appendix B.

Regarding construction of the lines, the DNOs prefer the use all aluminium alloy conductors

(AAAC) or aluminium core steel reinforced (ACSR), with occasional use of general purpose jacked

cables (BXL/PAS). All of these conductors will be used in various sizes deemed appropriate by

the network engineer [1].

The preferred conductors used for underground cable are 11kV rated, solid aluminium core,

XLPE insulated triplex cable. In the E.ON design manual [1] the standard cables are listed as

triplex laid (see B.2) cables, of the sizing shown in Table 2.2.

Table 2.2: New 11kV Conductors [1]

Location Cable Type CSA (mm2)

OH AAAC 50, 100, 200

OH ACSR 50, 100, 150

OH HDA* 300

UG Al-XLPE 70, 95, 185, 300

UG Cu-XLPE* 300, 400

* Special Application

Figure 2.10: 11kV Underground Triplex Cable Current Density with 1A inconductor A and induced eddy currents in shields

For 11kV cable the MATLAB function power cableparam was used rather than finite element

analysis software (as in Figure 2.10), which was restricted in use for parametrisation of LV cables,

shown in section 2.1.3.

Taking the example of underground 185mm2 aluminium triplex cables buried 1 meter below

ground and spaced as can seen in Appendix B, where further details on HV cable impedances can

2.1. Distribution Networks 33

be found, we have the following phase impedance matrix:

Z �

�����

0.095+0.050i 0.002+0.000i 0.002+0.000i

0.002+0.000i 0.095+0.050i 0.002+0.000i

0.002+0.000i 0.002+0.000i 0.095+0.050i

������km (2.1)

C �

�����

211 0 0

0 211 0

0 0 211

�����nF �km (2.2)

All of the calculated phase impedance matrices are used in the load flow studies of chapters 5

and 6, where the cable section length and construction type are both know thus by calculating the

product of the cable length (in km) and the phase impedance matrices (in Ω/km) we have detailed

the branch impedances.

The standard range of cables and lines used in replacement or upgrade work, and for new 11kV

feeders are listed in Table 2.2 (some special application cables are omitted). All use either copper

or aluminium conductors and the CSA ranges from 50mm2 to 400mm2, where by the choice of

cable is dictated by, feeder length, loading, faults levels, and potential for new or increased loading.

LV Feeders

In urban areas the LV network is almost exclusively of underground construction, whilst in rural

areas a mix of overhead and underground cables are used. In both cases the final LV customer is

connected to the LV feeder via a service cable which is owned by the DNO. It is at this point that

the consumer should be supplies with a supply voltage that meets the requirements of EN50160,

and is also the PCC for all connected loads in the customers premises.

The grounding schemes used dictate the cable used, but 3 main schemes are employed for LV

grounding are used, these being TN-CS, TN-S and TT. In all, the final customers has a ground to

create the local equipotential zone. The preferred grounding practice is TN-CS, also called PME,

which use cables with combined neutral and earth conductors (CNE). The TN-CS grounding

scheme is shown in Figure 2.11a.

A

CB

PNE

Load(a) TN-CS (PME)

A

CB

NPE

Load(b) TN-S

Figure 2.11: Earthing Systems

2.1. Distribution Networks 34

An alternative to PME is to isolate the neutral of the LV feeder from the protective earth, with

the customers protective earth coming from a fifth conductor on the feeder, this practice is called

TC-S and is shown in Figure 2.11b. A third method of grounding (TT) uses only a local earth at

the customers site via their own earthing electrode, this is more common in mainland Europe than

the UK.

In urban areas where most of the LV network is underground the preferred conductor amongst

all of the DNOs in the UK is XLPE insulated “wavecon” cable. This has 3 or 4 solid aluminium

phase conductors and a stranded concentric copper, neutral conductors around the phase conduc-

tors.

With PME, as can be seen in Figure 2.11a the neutral conductor is earthed at multiple points

along the feeder length. As PME permits ground currents to flow, even without faults present,

due to the parallel return path formed by the earth and neutral, for accurate representation of

the cable impedance matrices, Carsons equations should be used [56]. Further details regarding

application of Carsons equations to distribution networks are found in [23,57]. The series “circuit”

impedance of a neutral grounded network with 185mm2 wavecon cable is given in (2.3), with the

capacitive suceptance given in (2.4).

Z �

��������

0.239+0.739i 0.047+0.674i 0.047+0.674i 0.048+0.664i

0.047+0.674i 0.239+0.738i 0.047+0.674i 0.048+0.664i

0.047+0.674i 0.047+0.674i 0.239+0.738i 0.048+0.664i

0.048+0.664i 0.048+0.664i 0.048+0.664i 0.220+0.663i

���������km (2.3)

C �

��������

250 �53 �53 �143

�53 250 �53 �143

�53 �53 250 �143

�143 �143 �143 129

��������nF �km (2.4)

The cable shows differing impedance depending on system frequency (due to proximity and

skin effects) for this reason 2d FE analysis is carried out in FEMM [58], where the results given in

(2.3) and (2.4) are from this work. This effect is shown in Appendix B.

For the reduction to an “abc” phase impedance matrix (3x3), via the Kron reduction [23], we

must first assume the neutral conductor is tied solidly to ground at both ends of the line, hence the

voltage to ground of the neutral at either end is zero. This allows the matrix size to be reduced,

but in the case of a resistive non-ideal ground impedance, or missing ground nodes, the accuracy

of this technique has been questioned [59].

Ciric [57] proposes use of a 5x5 impedance matrix (in the case of a 3 phase 4 wire system with

grounded neutral) as a means to “split up” the circuit equations and then accurately model both

the neutral and ground paths, whilst incorporating grounding impedances at specific locations,

2.1. Distribution Networks 35

Figure 2.12: ABC Conductors

Table 2.3: New LV Conductors [1]

Location Cable Type CSA (mm2)

OH-Service Al-ABC 2�25, 2�35

OH-Service* Al-ABC 4�25

OH-Feeder Al-ABC 4�95

UG-Service Al/Cu-CNE 25, 35

UG-Service* Cu-CE 35

UG-Feeder Al-CNE 95, 185, 300

* 3φ Service Cables

but again doubts are cast upon the validity of such a method [59], due to discrepancies between

the above method and that proposed by Anderson [60]. Herein, 4x4 circuit impedance matrices

will be used which are reduced to 3x3 phase impedance matrices if the ground is assumed solidly

tied to ground or the earthing scheme is TN-S.

Outside of urban areas parts of the LV network utilise overhead lines, especially in rural areas.

The preferred standard of these lines is to use insulated aerial bundled conductor (ABC), this is in

part because ABC is considered a less of an eyesore, and due to their improved reliability compared

to bare wire conductors.

ABC conductors with 4 distinct cores where the neutral conductor is regularly grounded (ie.

PME) are the preferred configuration of overhead LV feeders the UK DNOs. The construction of

an ABC conductors is illustrated in Figure 2.12.

All of the various LV cables and lines used for, new LV networks, and asset replacement are

listed in Table 2.3.

2.2. Power Electronic Devices 36

2.2 Power Electronic Devices

This section presents 5 PEDs aimed at increasing capacity in LV networks, particularly in the

presence of increasing LCT use, these are:

� Active Power Filter (APF)

� Soft Open Points (SOP)

� Mid Feeder Compensator (MFC)

� On-load Tap Changers (OLTC)

� Power Electronic Substation (PES)

In particular control schemes, applications, and design are considered in detail, along with the

practical implementation of these PEDs for AC power flow studies. For a more general introduction

to power electronics the reader is pointed to Reference [61] which covers power electronics from

the fundamental semiconductor physics through to the applications of specialised PEDs.

The location of these 5 PEDs installed in to a distribution network is shown in Figure 2.13, this

is the same network structure as shown earlier in Figure 2.1 but where PEDs have been installed

in place of, or in addition to, traditional network plant.

LVSOP

Primary Substation

OLTCSecondary Substation

LV DCNetwork

11kV SOP

MFC

LV AC Network

SST APF

Figure 2.13: Distribution Network with Power Electronics

2.2. Power Electronic Devices 37

2.2.1 Active Power Filter

Active power filters (APF), and in particular shunt active power filters which will be referred to

simply as APFs are particularity suited to use in distribution systems where single phase, non-

linear loads create both fundamental negative and zero sequence currents components (unbalance)

and harmonic current flows in the network [62]. Although power factor is typically high in LV

networks [1], the APF can also be used to increase power factor and improve other PQ issues such

as flicker. Furthermore it can act to improve the voltage quality by virtue of compensating the

current components that cause the harmonic, zero, and negative voltage components [63]. In [62]

the PQ issues that the APF should aim to address are given as:

� Harmonic distortion

� Fundamental reactive power

� Negative sequence components

� Zero sequence components

� Flicker

The basic topology of an APF comprises an inverter, energy storage element (DC link capacitor)

and coupling to the network (shown as an inductor). The inverter is then controlled in such a way

as to produce the compensation currents (Ic) such that the control objectives are reached. The

connection of such an APF to the network is shown in Figure 2.14.

DC

AC

Vs VlIc

Is Il

Figure 2.14: Configuration of a APF Control Scheme

As LV networks are comprised of single phase loads, feeder unbalance is inevitable, so the APF

must be able to compensate for zero sequence components (i.e eliminate neutral ground current).

This can be achieved in via two main topologies reported in the literature, the split capacitor 3 leg

inverter, the 4 leg inverter, or a combination thereof [64].

There exists a wide range of control strategies for the APF as summarised in [62] which mentions

the use of both time and frequency domain filtering methods along with more recently developed

pattern learning methods. A comparison between APF objectives with time domain filtering

2.2. Power Electronic Devices 38

methods was presented in [65]. This work considered APF operation in 4 wire systems and how

each control scheme performed in the most general case, that is in the presence of both distortion

and unbalance on both the supply voltages and the load currents. The control strategies compared

where:

� UPF

� p-q

� id-iq

� PHC

The conclusion was that the PHC strategy was the most resistant in terms of adhering to the

IEEE Standard 1459 [66] in the presence of distorted or unbalanced voltages at the APF PCC.

The PHC control strategy is so named as the control objective regardless of supply voltage is to

achieve balanced sinusoidal currents in phase with the fundamental positive sequence voltage.

These control strategies are herein formulated in αβ0 coordinates as it gives a more clear insight

to the control objectives than when it is presented in phase coordinates, as noted in [65].

The first step is thus transforming the phase voltage and current into the stationary αβ0

reference frame:

uαβ0 � C� uabc (2.5)

where the power invariant αβ0 transform (C) is:

C �

�2

3

�����

1 �12 �

12

0�32

�32

1�2

1�2

1�2

����� (2.6)

and the reverse transform (CT ) is:

CT� C�1 (2.7)

which allows the transformation from αβ0 coordinates back to phase coordinates:

uabc � CT� uαβ0 (2.8)

2.2. Power Electronic Devices 39

The instantaneous active load power (p) is comprised of three component powers (pα, pβ , p0),

which are:

p � Vαβ0 � Iαβ0 (2.9)

� VαIα � VβIβ � V0I0

� pα � pβ � p0

the instantaneous reactive load power (q) is comprised of three components powers (qα, qβ , q0):

q � Vαβ0 � Iαβ0 (2.10)

� VβI0 � V0Iβ � V0Iα � VαI0 � VαIβ � VβIα

� qα � qβ � q0

and both the load instantaneous real (p) and reactive (q) powers, in the general case, are comprised

of dc and ac components:

p � p� p (2.11)

q � q � q (2.12)

thus, the average load power that must be supplied from the source is the dc component of the

instantaneous active power (p):

p � pα � pβ � p0 (2.13)

From 2.13 the compensation schemes reference αβ0 source currents (I�αβ0) for the PHC control

strategy (Is in Figure 2.14) are in [65], given as:

�����

i�α,phc

i�β,phc

i�0,phc

����� �

pα � pβ � p0

v�2α1 � v�2

β1

�����

v�α1

v�β1

0

����� (2.14)

and for the UPF control strategy [65]:

�����

i�α,upf

i�β,upf

i�0,upf

����� �

pα � pβ � p0�v2α � v2β � v20�dc

�����

v0

����� (2.15)

2.2. Power Electronic Devices 40

where the dc subscript term represents an average over the fundamental frequency period. For the

modified p-q control strategy [67]:

�����

i�α,pq

i�β,pq

i�0,pq

����� �

pα � pβ � p0v2α � v

�����

0

����� (2.16)

A comparison of the three control strategies given by (2.14)-(2.16) is shown in Figure 2.15,

where it is seen that the UPF current waveforms match those of the supply voltage waveform

thus the control scheme achieves its goal of unity power factor (UPF). The PHC control scheme

draws balanced and sinusoidal currents that are in phase with the fundamental positive sequence

voltage waveforms (v�1 ). The modified pq strategy draws a constant active power (p) with no zero

sequence current (i�0 ), however as seen from Figure 2.15 and the “p-q current spectrum” subplot this

introduces current harmonics not originally present in the current or voltage waveforms. In Figure

2.15, all of the frequency domain plots are for the blue (phase a) current or voltage waveforms. It

should be noted that as the source is treated as an infinite source and the APF is shunt connected

neither the source voltage nor load currents can be changed, and the APF controls only the source

side current.

As indicated in Figure 2.15, for rejection of voltage distortion and adherence to the IEEE Stan-

dard 1459 the PHC scheme is the most suitable particularly for 4 wire LV distribution networks.

For the purpose of modelling an APF in a fundamental frequency AC load flow study the

compensation currents with the PHC compensation scheme (I�phc) are found by first calculating

the required conductance factor (kg):

kg �P

V �seq � V�seq

(2.17)

where V �seq are the positive sequence voltage vectors at the PCC, additionally V �seq is its conjugate

transpose, and P is the calculated power (a dc term for AC load flow). Given kg, we then multiply

by the positive sequence voltages to find the reference currents (I�s,phc):

I�s,phc � kgV�

seq (2.18)

As before these currents will be balanced and in phase with the positive sequence voltage

vectors. The implementation in signal flow diagrams are shown in Figure 2.16.

As only the fundamental component is considered in AC load flow studies, and the method

used to calculate reference currents is PHC, the APF can be considered as a phase balancer. Once

2.2. Power Electronic Devices 41

-400

0

400

Voltage(V

)

Source Voltage Waveform

0

200

400

Amplitude(V

) Source Voltage Spectrum

-20

0

20

Current(A

)

Load Current Waveform

0

5

10

15

Amplitude(A

) Current Spectrum

-20

0

20

Current(A

)

UPF Current Waveform

0

5

10

15

Amplitude(A

) UPF Current Spectrum

-20

0

20

Current(A

)

p-q Current Waveform

0

5

10

15

Amplitude(A

) p-q Current Spectrum

0 0.02 0.04 0.06 0.08 0.1Time (s)

-20

0

20

Current(A

)

PHC Current Waveform PHC Current Spectrum

0 50 100 150 200 250 300 350 400Frequency (Hz)

0

5

10

15

Amplitude(A

)

Figure 2.15: Comparison of APF control schemes, where the top two rows show the sourcevoltage and load current, whilst the lower 3 row show the source current with three different APF

control methods

Vseq

÷

PcalcVabc

I abc

x'x I *

Figure 2.16: Configuration of a APF Control Scheme

the reference currents are known the compensation current (Ic) is:

Ic � Il � I�

s,phc (2.19)

2.2. Power Electronic Devices 42

where Il is the load side current.

2.2. Power Electronic Devices 43

2.2.2 Soft Open Point

A limitation of all the other considered PEDs is their relative inability to relieve the loading on a

feeder or a transformer [18] where the problem is related to the feeder power flows rather than to

voltage regulation. This can be addressed by the use of SOPs, where the SOP is a back-to-back

pair of voltage source inverters each connected to a different feeder as shown in Figure 2.17.

DC

AC

AC

DCV1

I2I1

V2

Figure 2.17: Configuration of a APF Control Scheme

The connection of the SOP allows the power flow between the two feeders to be precisely con-

trolled by controlling the AC voltage of the two inverters independently, potentially alleviating both

thermal and voltage constraints [19]. Furthermore, even if neither feeder has redundant capacity

available for power exchange between them, the SOP can (similarly to an APF) exchange power

between the individual phases of each feeder to mitigate phase imbalance and release capacity.

A simplified implementation of this aforementioned, per phase control method is now shown.

From (1.7) if the SOP doesn’t exchange reactive power with the network, then any change in

voltage magnitude due to changing active power exchange from the SOP (P1,abc) is approximately

proportional to the grid resistance (R), as shown in (1.8). Hence considering one phase (a) of

feeder (#1) with an impedance of (Z1a), which directly connects the voltage source (Vs) to the

SOP, the voltage across the feeder (ΔV � Vs � V1a) is:

ΔV �R1aP1a

V1a�X1aQ1a

V1a� j

�X1aP1a

V1a�R1aQ1,a

V1a

�(2.20)

next considering only active power exchange from the SOP (Q1a � 0), and a line impedance that

is purely resistive (X1a � 0) the approximation of (1.7) is actually now equal to (2.20):

ΔV �R1a � P1a

V1a(2.21)

With these conditions, to find the sensitivity of the SOP voltage to any changes in SOP power we

perturb the SOP voltage (V1a � V1a,0 � v1a) in (2.21) and then linearise, namely ignore 2nd order

AC voltage terms.

Vs � V1a,0 � v1a �R1a � P1a

V1a,0 � v1a(2.22)

VsV1a,0 � Vsv1a � V21a,0 � 2V1a,0va1 � v

21a � R1a � P1a

2.2. Power Electronic Devices 44

equating the, constant voltage terms (V1a,0) and AC voltage terms (va1) after linearisation, to the

SOP power, which is itself comprised of the SOP operating point power (P1a,0) and SOP AC power

terms (p1a) results in:

P1a,0 �VsV1a,0 � V

21a,0

R1a(2.23)

p1a �Vsv1a � 2V1a,0v1a

R1a(2.24)

So the voltage sensitivity, defined as the incremental change in voltage, in response to a incremental

change in SOP power is:

dV1adP1a

�v1ap1a

�R1a

Vs � 2V1a,0(2.25)

Writing the voltage change at the SOP in terms of SOP power linearised around an operating

point V1a,0:

�dV1adP1a

dP1a � V1a � V1a,0 (2.26)

�v1a � V1a � V1a,0

where V �

1a is the new voltage at the SOP. If the three phase voltages of a connected feeder (here

feeder #1) are decoupled from each other the above expression in matrix from is:

���������

dV1adP1a

0 0

0dV1bdP1b

0

0 0dV1cdP1c

���������

���������

dP1a

dP1b

dP1c

����������

���������

V1a

V1b

V1c

����������

���������

V1a,0

V1b,0

V1c,0

���������

(2.27)

the above equation has n (� 3) control variables (dP1a, dP1b, dP1c) with n linearised equations.

We can remove one of these control variables by stating that:

P1a � P1b � P1c � PSOP (2.28)

dP1a � dP1b � dP1c � 0 (2.29)

we next introduce the unknown (V �

1x), and note that if the control scheme is to balance voltage

magnitudes at the SOP as effectively as possible (hence minimising losses [68]), where V �

x is the

2.2. Power Electronic Devices 45

voltage magnitude at the SOP we can write:

���������

�dV1adP1a

0 0

0 �dV1bdP1b

0

0 0 �dV1cdP1c

���������

���������

dP1a

dP1b

�dP1ab

����������

���������

V �

1x

V �

1x

V �

1x

����������

���������

V1a,0

V1b,0

V1c,0

���������

(2.30)

where dP1ab is equal to the sum of dP1a and dP1b. We see now that there exists 3 linear equations

with 3 unknowns (dP1a, dP1b, V�

1x), this equation can be rewritten as:

��������������

�dV1adP1a

0 0 1

0 �dV1bdP1b

0 1

0 0 �dV1cdP1c

1

1 1 1 0

��������������

��������������

dP1a

dP1b

dP1c

V �

1x

��������������

��������������

V1a,0

V1b,0

V1c,0

0

��������������

(2.31)

which has the form of:

Ax � B (2.32)

where x is comprised of the per phase changes in power flow in the SOP (dPa, dPb, dPc), and the

magnitude of the reference voltage (V �

x ), which form the unknown variables. Solving for x:

x � A�1B (2.33)

In B, PSOP is the power that the SOP passes from one connected feeder to the other feeder. The

expression above is valid for the other connected feeder (#2) whereby the subscripts are suitably

replaced and the sign of PSOP in (2.28) is switched (i.e �PSOP ).

This principle of SOP phase voltage regulation is demonstrated in Figure 2.18 where the net

SOP power (PSOP ) is specified as zero and an unbalanced load is connected to a feeder that also

connects to the SOP (as in Figure 2.19). Initially the voltages at the SOP are unbalanced (as

can be seen by the voltages at iteration #1 in the top graph of Figure 2.18). The SOP maintains

the requirement of zero net power flow but via adjustment of the per phase powers controls phase

power flows such that it results in balanced voltages at the SOP terminals after the solution is

found by iteration like in usual load flow studies. It is seen that after the first iteration changes to

the SOP power flows are small thus indicating the good convergence characteristics of the above

method.

2.2. Power Electronic Devices 46

1 2 3 4 5Itteration

0.8

0.85

0.9

0.95

1Phase Voltage at SOP (Vpu)

Va

Vb

Vc

-4

-2

0

2×104 SOP Phase Power (W)

Psop,a

Psop,b

Psop,c

Figure 2.18: Iterations of a SOP Regulating Phase Voltages

In the case where the line impedance (Z) has reactance (Z � R� jX) and / or mutual effects

between the SOP phases are considered the number of equations that need to be solved doubles,

as do the number of unknowns, the control objective then becomes to create a balanced voltage

set at the SOP, this necessitates that the SOP also control reactive power flow at its terminals for

independent angular control.

Regarding control of the main SOP power flow parameter, namely PSOP (see (2.28)), which is

the transfer of power from 1 connected feeder to another, a range of schemes are used [68] that

often have a control objective of minimising losses and regulating voltage when if falls outside of

permissible limits.

AC

AC

Feeder #1

Feeder #2SOP

Figure 2.19: A SOP connected between two feeders facilitating power flow between them

The 2 port SOP will be used herein to control voltage at each of its terminal to regulatory levels,

this is only achieved if capacity is available on the other feeder (ie. it does not suffer simultaneous

voltage constraints)

2.2. Power Electronic Devices 47

2.2.3 Mid Feeder Compensator

The MFC in topology is similar to that of a UPFC (or UPQC). It comprises shunt and series

inverters tied to a common DC link. A high level diagram of a MFC inserted between two network

buses is shown in Figure 2.20. The two converters are seen connected to one DC link but if we

were instead to consider two separate DC links (one for each converter), the MFC would actually

resemble a combination of both a shunt APF and series APF; something that can be taken into

account when considering control schemes for the MFC.

DC

AC

AC

DC

Vs VlIc

VcIs Il

Figure 2.20: Configuration of a UPQC

For optimal location of a single MFC it should maintain voltage profile as tightly as possible,

this will be achieved if it is located where the voltage across the feeder is half of total voltage across

the feeder. Conciser a single phase line of length L and impedance Z, with uniformly distributed

load and a total line current It, then at position x on the feeder the line current (ix) is:

ix � It �1� x� (2.34)

The gradient of the voltage at position x is:

dV

dx� Zix (2.35)

the voltage drop (ΔVx) at x is:

ΔVx �� x

0

dV

dx.dx (2.36)

�� x

0

Zix .dx

�� x

0

ZIt �1� x� .dx

The voltage drop is then half that of the remote feeder end voltage drop (ΔVL) when:

x � L2��2

2� ΔVx � ΔVL

2

2.2. Power Electronic Devices 48

The solution indicates the voltage drop is half the maximum value when x equals 0.29L, or 29%

of the total feeder length, which is where the MFC would, ideally, be located along the feeder.

Regarding control of the MFC, we initially consider both converters separately. Thus for the

shunt inverter it can be controlled exactly as the shunt APF shown previously in section 2.2.1 was.

Hence, the source side reference currents (Iαβ0,mfc) assuming PHC operation of the MFC’s shunt

converter are:

�����

i�α,mfc

i�β,mfc

i�0,mfc

����� �

pα � pβ � p0

v�2α1 � v�2

β1

�����

v�α1

v�β1

0

����� (2.37)

For the series connected converter, as a result of duality [69], equations (2.14)-(2.16) can be

applied for a series APF (or DVR) which injects a compensating voltage (Vcomp) to the source

voltage (Vs) such that the load voltage (Vl) is equal to the reference voltage (V �) and any control

objectives are meet. For example, the PHC control objective (2.14) applied to the series MFC

converter results in the MFC load side reference voltages (V�

αβ0,mfc) of:

�����

v�α,mfc

v�β,mfc

v�0,mfc

����� �

pα � pβ � p0

i�2α1 � i�2

β1

�����

i�α1

i�β1

0

����� (2.38)

we then note (2.38) is of the general form:

V�

αβ0,mfc � kr

��i�

αβ,1

0

�� (2.39)

we see the reference voltage components are proportional to the balanced positive sequence source

currents (i�αβ,1) via a resistive factor kr. Hence, by adjustment of kr we can control the load side

reference voltages (V�

αβ0,mfc).

Suppose now that we instead wish to control these load side reference voltages to some prede-

fined magnitude (�Vmfc�), then (2.39) can be reformed as:

V�

αβ0,mfc �

�32 � �Vmfc��i�2α1 � i�2

β1

��i�

αβ,1

0

�� (2.40)

Notice the factor of�

32 which is needed as the αβ0 transform (C) we defined previously (2.6) was

the power invariant transform.

Unlike with the voltages in (2.38) using the voltages of (2.40), the average load side power (Pl),

2.2. Power Electronic Devices 49

i.e the power at the load side of the MFC, which is the dc component of:

Pl � V�

αβ0,mfc � Iαβ0 (2.41)

is not necessarily equal to the average source side power (Ps), i.e the power on the source side of

MFC, which is the dc component of:

Ps � Vαβ0 � I�αβ0,mfc0 (2.42)

Thus there is need for an additional source of energy for the compensator to operate with energy

balance. The power demand of the compensator (Pmfc) is:

Pmfc � Ps � Pl (2.43)

The series compensator power (Pmfc) could be supplied by local energy storage (eg. from

batteries), from another circuit, or by the shunt connected converter. With the latter case it is

helpful to imagine the ideal MFC, as shown in Figure 2.21, connected between two network buses.

MFCImfc

Vmfc

Il

Vs

Pin Pout

Figure 2.21: MFC Power Load and Source Flows

The ideal MFC has no power losses such that the input (Ps) and output powers (Pl) are equal.

Furthermore the MFC controls the source side currents (I�mfc) and load side voltages (V �

mfc) to

the desired values. For the MFC shunt converter to supply the power of the series converter we

have that Ps � Pl, so the MFC reference currents (I�αβ0,mfc) will be such that:

I�αβ0,mfc �

�V�

αβ0,mfc � Iαβ0,l

�dc

V�

αβ0,s

(2.44)

this is due to the use PHC control such that:

P s � V�

αβ0,s � I�αβ0,mfc (2.45)

hence:

I�αβ0,mfc �

�V�

αβ0,mfc � Iαβ0,l

�dc

V�

αβ0,s

(2.46)

2.2. Power Electronic Devices 50

which, when put in the same general form of (2.37), becomes:

�����

i�α,mfc

i�β,mfc

i�0,mfc

����� �

�V�

αβ0,mfc � Iαβ0,l

�dc

v�2α1 � v

�2β1

�����

v�α1

v�β1

0

����� (2.47)

Equation (2.47) is actually identical to (2.37) but for the fact we had assumed (by virtue of

treating both the shunt and series MFC converters entirely separately) the numerator of (2.37)

was the load power without (or prior to) voltage regulation.

The effect of this change to the reference currents (I�αβ0,mfc) is that the shunt compensator

will now draw or supply the power drawn or supplied by the series compensator. Thus only small

energy storage components (i.e. a DC link capacitor) are needed for the MFC, which compared to

battery storage options, significantly reduces both costs and size at the expense of a higher rated

shunt MFC converter.

To demonstrate the operation of the MFC, Figure 2.22 shows the effect of an MFC when it

is used to connect a load comprised of a constant current source (same load current waveform as

in Figure 2.15) to a distorted and unbalanced infinite voltage source supply (same supply voltage

waveform in Figure 2.15). The MFC is set to regulate the peak load side phase voltage to the

maximum permissible UK voltage, namely 357.8V.

-400

0

400

Voltage(V

)

Source Voltage Waveform

-400

0

400

Voltage(V

)

Load Voltage

-20

0

20

Current(A

)

Source Current

-20

0

20

Current(A

)

Load Current

0 0.02 0.04 0.06 0.08 0.1Time (s)

0

2500

5000

7500

10000

Power

(W)

Source Power Load Power

0 0.02 0.04 0.06 0.08 0.1Time (s)

0

2500

5000

7500

10000

Power

(W)

Figure 2.22: Performance of an MFC

We also see that the mean source and load powers (as indicated by the red lines in the lowest

two plots) are equal, although a difference is seen in the instantaneous values, hence the need for

the DC link capacitor or some other form of local energy storage. These oscillations in the source

2.2. Power Electronic Devices 51

and load power are caused by the unbalance and distortion in the source voltage and load current,

respectively.

For the purposes of AC load flow studies operation of the PHC controlled MFC can be calculated

by first calculating the reference voltages (V �

mfc) via:

V �

mfc ��3 � �Vmfc��I�seq � I�seq

� I�seq (2.48)

the new load side apparent power (Sl) is then:

Sl � 0.5� V �mfc � i (2.49)

where the active load power (Pl) is the real component of Sl. The source side reference currents

(I�mfc) are then:

I�mfc �2� Pl

I�seq � I�seq� V �seq (2.50)

Due to the non linearity of load flow studies, ie. the dependencies of the load power flows upon

the supplied voltage itself, the load flow program would proceed iteratively find the actual solution

as usual.

2.2. Power Electronic Devices 52

2.2.4 On-load Tap Changers

The secondary substations in the UK are already fitted with no load taps on the primary winding,

these transformers have a nominal ratio of 11/0.433 kV [1,30], aligned with taps set at the nominal

value. This results in high substation voltages [70], limiting DG hosting capacity [71].

PT

CT

TimeDelay

TapSelection

LDC

AVC

Figure 2.23: Automatic Voltage Control (AVC) of an OLTC Transformer

Herein, we suppose, OLTC functionality is added to 11/0.433kV transformers, where tap selec-

tion is controlled as in Figure 2.23. As with the PES, LDC is used for generation of the reference

voltage. Taps are considered to have a range of �5% and a resolution of 2.5%; this corresponds to

the ratios of the no-load taps presently [30].

2.2.5 Solid State Transformers

Solid state transformers form the main part of power electronic substations for use in LV networks,

that are receiving greater attention [72]. A particular advantage offered is their ability to produce

a continually variable output voltage across each feeder. From Figure 2.24, a modular output con-

verter can be used to enable per feeder control and the possibility of LVDC distribution networks.

For the purposes of this work the SST will be used to offer a continually adjustable set of balanced

voltages on each connected LV feeder.

DC

AC

AC

DC

DC

AC

AC

DC

EnergyStorage

High FrequencyIsolation

DC

AC

AC

DC

ModularOutput

Figure 2.24: Possible Configuration of a SST

The SST control scheme can utilise LDC employed individually for each feeder to control

2.2. Power Electronic Devices 53

the magnitude of the PES voltage. Individual control of each feeder has clear advantages if the

substation had both commercial and residential feeders, which have different load and generation

profiles.

For both the OLTC and SST the voltage at the secondary side or head of the connected feeders

is controlled via line drop compensation, the reference voltage (Vref ) is:

Vref � Vnom � Vcomp �Smeas

Snom(2.51)

where Vnom is the no load reference voltage Vcomp is the compensation voltage that dictates the

change in reference voltage as the power flow though the transformer changes, finally Snom and

Smeas are the nominal and measured substation power, respectively. The difference between the

SST and OLTC comes from the fact that the FES is able to regulate individual feeders rather

than the secondary voltage and hence all the connected feeders, along with the fact the voltage

range is continuously adjustable rather than in discrete steps. Additionally, to avoid hunting and

mechanical wear tap changers have a slow response which will ignore transients in order to improve

the lifespan of the OLTC and improve stability, these requirements are not so with the SST and

so it can very quickly compensate for short transient events.

2.2.6 Overview of Power Electronic Devices

Despite the fact these devices have been proposed to mitigate a specific problems (power flow,

current imbalance, voltage), many of them share multiple features. Distribution networks across

the UK present different characteristics and are faced with different challenges due to a range

of factors including, historic network design choices, climate, population density, and regional

economic development. Therefore, the extent to which the constraints discussed earlier are a

concern to any DNOs will vary, and thus, so will the case for the devices presented. A table to

summarize the characteristics of the devices is presented (Table 2.4).

Table 2.4: Performance Characterisation of Power Electronic Devices

PEDControllability Offered

Voltage Power Balance Harmonics

SST x - limited x

MFC x - x x

SOP x x x x

APF - - x x

OLTC x - - -

2.3. Loads Profiles and Models 54

2.3 Loads Profiles and Models

Domestic loads for power systems studies including those related DSM, voltage optimisation, and

high resolution LV network analysis, should not be simply represented as a constant grouped PQ

demand, instead they should exhibit a representative voltage sensitivity. This sensitivity is the

relationship between the load apparent power and the magnitude of local supply voltage [73] and

its ability to function across a range of voltages. To achieve this models herein build upon work

from [49], an open access, Excel based load profile generator, that produces 24 hour domestic load

profiles with a 1 minute resolution using a bottom up (i.e device by device) approach. This tool

when coupled with previous work [38] which explored the voltage sensitivity (and limits) of all the

loads in the load profile generator, can be used to assign voltage sensitivity figures to each load,

after which a dwelling voltage sensitivity profile is output in the same way as the original load

profile (see Fig 2.25).

An extra complexity is introduced, as for much of the loads in domestic settings thermal

controls are present such that the energy consumed over a sufficient time period will be almost

constant regardless of the instantaneous power drawn. If the load has constant PQ characteristics

this is not an issue as the instantaneous power is independent of supply voltage, but for loads

with non constant PQ characteristics the instantaneous power will change and thus for constant

energy consumption the load duty (or on time) must change. For these loads thermal models are

developed which can be used in networks analysis so they consume constant energy over a sufficient

time period and will therefore more accurately follow temperature (energy) set-points.

2.3.1 Loads without Thermal Control

Many voltage sensitivity studies often characteristics the load as a function of a sum of constant:

� Impedance (Z)

� Current (I)

� Power (P)

type loads. For this reason these terms are called load ZIP parameters. The standard from of

these (ZIP) equations is:

Pm � Pnom �

�Zp

�VmVnom

�2

� IpVmVnom

� Pp

�(2.52)

Qm � Qnom �

�Zq

�VmVnom

�2

� IqVmVnom

� Pq

�(2.53)

2.3. Loads Profiles and Models 55

where, Pnom is the loads nominal power consumption which is specified at nominal voltage (Vnom)

magnitude. Pm is the actual power consumption at the actual supply voltage. Pp, Ip, and Pp are

the coefficients of the polynomial that relate Pm to Pnom. Equivalent expressions for the reactive

power demand are used in (2.53). Additionally, as Pm at nominal voltage must equal Pnom we

have that:

Zp � Ip � Pp � 1 (2.54)

Zq � Iq � Pq � 1 (2.55)

The ZIP model is the commonly used form to describe static load PQ characteristics found in

the literature. Alternatively PQ voltage sensitivity characteristics can be stated in the so called

“exponential” form:

Pm � Pnom �

�VmVnom

�np

(2.56)

Qm � Qnom �

�VmVnom

�nq

(2.57)

Where the np and nq values can be found [73] from the ZIP parameters using :

nx � 2Zx � Ix x � �p, q� (2.58)

The choice of (2.52) & (2.53) or (2.56) & (2.57) is not critical, providing the load PQ charac-

teristics are accurately described by these parameters. Table 2.5 following lists the sensitivity of

common domestic loads.

The loads that are not thermally controlled can be summed (with weighting) to give the overall

voltage sensitivity of the household loads. This will be dependent on the composition of the devices

being used at a given time in the load profile simulator, so will also be a function of time much

like the traditional demand profile.

To find the overall sensitivity of the loads used at a given time (t) we have the total power

consumed at nominal voltage (Pt), which is composted of n loads or devices each with a power

consumption at nominal voltages (Pnom) given as:

Pt,nom �n�

d�1

Pd,nom (2.59)

2.3. Loads Profiles and Models 56

Table 2.5: PQ ZIP Parameters [38]

Device Vmin�pu�

Active Reactive

Zp Ip Pp Zq Iq Pq

Incandescent - 0.53 0.51 -0.05 0.00 0.00 0.00

Halogen - 0.63 0.37 0.00 0.00 0.00 0.00

CFL 0.29 -0.11 1.1 0.00 -0.67 1.58 0.09

FL 0.39 -0.35 1.86 -0.51 1.86 -1.88 1.02

Heating - 1.00 0.00 0.00 0.00 0.00 0.00

Motor (CT) 0.59 0.58 -0.20 0.62 1.70 -1.19 0.49

Motor (FAN) 0.60 0.96 -0.89 0.94 1.20 -0.58 0.38

Motor (ASD) 0.77 1.81 -1.62 0.80 -0.06 1.65 -0.59

E Supply (PFC) 0.54 0.00 0.00 1.00 0.00 0.00 0.00

E Supply 0.54 -0.07 0.27 0.80 1.30 -1.85 1.54

For clarity power (p) and reactive power (q) subscripts are omitted in ZIP parameters giving a

voltage sensitivity of each device (ZIPd) defined as:

ZIPd �

�����

Zd

Id

Pd

����� (2.60)

Where:

d � �1, 2...n�

the total sensitivity (ZIPt) is then:

ZIPt �

�����

Zt

It

Pt

����� �

n�d�1

Pd,nom

Pt,nomZIPd (2.61)

Equation 2.61 is a weighted sum of the individual voltage sensitivities; where the weighting

factor is the device power consumption (Pd,nom) as a faction of the total domestic load (Pt,nom).

The same approach the can be repeated for the reactive power voltage sensitivities.

Extending the above approach for the duration of the load profiler will result in a time vary-

ing ZIP sensitivity profile ZIPt�t� comprised of Zt�t�, It�t� and Pt�t� which will show a strong

correlation to the related demand (Pt�t� and Qt�t�) .

In Figure 2.25 the total active power ZIP demand (ZIPp,t�t�) of a single domestic customer,

onwards from 6am and for 16 hours, is shown. We can notice that generally the curve stays

constant but, for example at 16:00, we see a large change in the voltage ZIP parameters, whereby

Pp,t falls and Zp,t rises. In reality this is likely due to a large resistive load being connected but

2.3. Loads Profiles and Models 57

could also be attributed to a large disconnection of a constant power type load, or a number of

other permutations. Regardless of the root cause, we can notice the coupling between each of the

ZIP parameters in the figure due to the constraint of (2.54).

Demand

0

500

1000

1500

2000

2500

Power

(W,Var) Active

Reactive

Voltage Senstivity

0 4 8 12 16 20 24Time (hours)

0

0.5

1

1.5

2

np,n

q

Active

Reactive

Figure 2.25: Example of “ZIP Profile” Data Synthesised from the CREST profiler and Table 2.5

The lower plot in Figure 2.25 is created by assigning (2.60) to each device modelled in the

CREST simulator, after which (2.61) is applied. This takes advantage of the bottom up modelling

approach taken in the CREST simulator, where the load profile (shown in the top plot of Figure

2.25) is actually comprised of the sum of all the active devices in one dwelling. Where the load

profile simply a total power demand of a dwelling the approach outlined above would not be

possible as the active loads would not be known. By comparing the top profile plot of Figure 2.25

with the top left plot of Figure 2.31 we can see how as the individual load profiles are aggregated

they tend to form the smooth load profiles often used to represent domestic loads in high voltage

power flows where domestic loads are grouped.

With reference to Figure 2.25 it can be seen above that when the reactive power demand is

high the nq tends towards 2 and for the active power the np value fluctuates between 1 and 2.

This is the basis for the often used assumptions of constant current type active power demand and

constant impedance type reactive power demand [74].

2.3.2 Loads with Thermal Control

To model the thermal properties of the loads two distinct approaches can be used, namely:

� Thermal Models

� Constant Energy Models

2.3. Loads Profiles and Models 58

The full thermal model may be more appropriate for domestic space heating, namely heat

pumps and storage heaters, and DR studies, whilst the constant energy consumption model is

sufficient for smaller goods, such as ovens or refrigerators or where decisions such as shifting of

thermal loads (DR) are not important. The effect of using the constant energy model is to decouple

these small loads from the ambient or house temperatures. If we assume the temperature inside a

house is fairly consistent or the range of these temperatures in small this is a valid simplification.

Thermal Model

From heat flow laws and the HVAC thermal system model presented in [75] we have the following

state model of a dwelling. The building heat flow equations, with ambient temperature (T0) set as

the reference is given as:

dTmdt

�Ta � TmRamCm

�Qa

Cm(2.62)

dTadt

�Tm � TaRamCa

�T0 � TaRaCa

�Qh

Ca(2.63)

where: Qh is the heat flow into the house, Ca is the heat capacity out of the house, Cm is the heat

capacity of the house mass, Ta is the temperature the house, Tm is the temperature of the house

mass, T0 is the ambient temperature, Ra is the thermal resistance of the house to the outside, and

Ram is the thermal resistance between the building mass and the house.

����dTadt

dTmdt

���� �

�����1

RaCa+

�1

RamCa

1

RmCa

1

RmCm

�1

RmCm

�������Ta

Tm

����

����

1

RiCa

1

Ca0

0 01

Cm

����

�����T0

Qa

Qm

����� (2.64)

For a coupled thermal model of loads inside a domestic building, consider a fridge which is

referenced to the ambient temperature (T0 � Ta), leading to:

dTfdt

�Qf

Cf�Ta � TfRfCf

(2.65)

The state equation for this first order system is:

dTfdt

��TfRfCf

�1

RfCf

1

Cf

���TaQf

�� (2.66)

2.3. Loads Profiles and Models 59

Combing the model of the dwelling and that of the fridge we have:

���������

dTadt

dTmdt

dTfdt

����������

���������

�1

Ca

�1

Ri+

1

Rm+

1

Rf

�1

RmCa

1

RfCa

1

RmCm

�1

RmCm0

1

RfCf0

�1

RfCf

���������

��������

Ta

Tm

Tf

���������

���������

1

RiCa

1

Ca0 0

0 01

Cm0

0 0 01

Cf

���������

��������

T0

Qa

Qm

Qf

��������

(2.67)

The above method could be applied to any internal loads that exchange heat within the building,

for example a cooker or hot water storage system. Figure 2.26 shows an example of a fridge with

initial conditions of 27�C, 20�C, 4�C for the house, mass and fridge, respectively, the ambient

temperature is 15�C. The long time constant of the house mass is evident, as is the coupling

between the house and the fridge, where the fridge temperature is dependant upon its heat flow

(Qf ).

0 0.5 1 1.5 2 2.5 3 3.5 4Time (hours)

0

5

10

15

20

25

30

Tem

prature

(◦C)

House

Mass

Fridge

Figure 2.26: Temperature of House air, mass of building, fridge (electrical load)

Constant Energy Consumption

Considering equation (2.67) if the load (eg. a fridge) is well insulated, the coupling between the air

temperature and load temperature will be low, meaning the fast temperature dynamics of the load

will be mostly sensitive to the heat flow (i.e. the first RHS term in (2.65)). Given an electrical use

profile for this and assuming: the COP (or efficiency) of the load does not change significantly, the

temperature of the house is constant, then the mean load temperature will be proportional to the

electrical energy use (i.e heat flow of load). Then as the voltage sensitivity of the load is known

(Table 2.5) the power consumption and hence instantaneous heat flow is also know. Being that

the load has a thermal controller which keeps the load temperature within a set tolerance the load

can be modelled as a constant energy load over a time scale longer than the loads thermal time

constant.

To calculate the energy needed the load profiles are first preprocessed as shown in Figure 2.27.

2.3. Loads Profiles and Models 60

Find SwitchOn/Off Events

Energy atswitch off

events (Eoff(t))

Times ofSwitch on

Event (Ton(t))

Energy Demand(Ed(t))

Create ZOHtimeseries withEoff(t) at Ton(t)

Load ProfileDemand(Pd(t))

Energy DemandEd(t) = Pd(t) / s

Figure 2.27: Preprocessing Data

Then during the load flow the models acts as shown in Figure 2.28, the model acts to maintain

constant energy use, where possible, given higher or lower supply voltages than nominal and

without incorrect or unrealistic switching of the device at supply voltages other than nominal. It

is noted this process takes advantages of the on/off nature of hysteresis type controllers and is not

suited to loads with ASD for example.

MeasuredConsumption

(Em(t-1))

MeasuredVoltage

(Vm(t-1))

EnergyDemand(Ed(t))

Load ProfileDemand (Pd(t))

Estimated Power (Pest(t))

Pest(t) = Pd(t) * ZIP * Vm(t-1)

Estimated Demand (Eest(t))

Eest(t) = Pest(t) + Em(t-1)

Ps=PdPs=Ps(t-1)

Ps=0

Power(Ps)

Figure 2.28: During Load Flow

An example of the above process is given in Figure 2.29 and Figure 2.30. In Figure 2.29 we

see the initial power demand at nominal voltage in the top plot with the energy consumed by

this load in the the middle. The pre-process operation shown in Figure 2.27 results in the energy

demand used for the load flow, where we can see the energy demand here is in discrete steps which

correspond to the energy when the load turns off (see middle plot) at the times when the load

turns on (see top plot).

In Figure 2.30 the results of a load flow using the load profile data for cooking, water heating

and small heating (CWSH) appliances, which are plotted in Figure 2.29, are shown for 3 different

supply voltages. In these results the load is assumed to be entirely resistive (i.e. ZIPd � �1 0 0�T)

in nature and thermally controlled, (eg. a kettle). Here Vnom is the the nominal supply voltages,

Vlow is a voltage 85% of Vnom, whist Vhigh is 110% of Vnom. The effect of the process described

2.3. Loads Profiles and Models 61

Nominal Power Demand

0

100

200

Power

(W)

Nominal Energy Consumption

0

0.5

1

1.5

Energy(kW

h)

Turn off Energy Consumed at Turn On Events

0 4 8 12 16 20 24Time (hours)

0

0.5

1

1.5

Energy(kW

h)

Figure 2.29: Nominal CWSH Demand Data

visually in Figure 2.28 can be seen in the top graph, whereby at the low supply voltage the device

demand (red plot) remains on after the original load profile (blue plot) has gone to zero until such

a time that the energy consumption (red plot, lower graph) is equal to that of the of the nominal

energy demand (blue plot, lower graph). A similar pattern is noticed for the high supply voltage

whereby the device turns off (yellow plot, upper graph) prior to the turn off times at nominal

voltage (blue plot, upper graph). It is important to notice that the load flow does not simply

compare the measured energy consumption to the energy consumption at nominal voltage, as if

this were to occur at higher than nominal voltages the device would actually just switch on and

off repeatedly, which is not what would occur in practice.

2.3.3 Final Load Profiles

Using the voltage sensitivity figures for the domestic loads given in Table 2.5, the amount of

capacity released from widened voltage levels can now be more accurately assessed. Using the

load profile generation worksheet [49] each device is given parameters to describe its operation

and voltage sensitivity. The thermally controlled loads are also specified and for each node are

separated from the non-thermally controlled loads in the load demand profile.

The advantage of the above scheme is that now a domestic load model, with a demand profile

built up from the distinct loads in a domestic setting, each of which with its own voltage sensitivity

2.3. Loads Profiles and Models 62

Nominal Power Demand

0

100

200

Power

(W) Vnom

Vlow

Vhigh

Nominal Energy Consumption

0 4 8 12 16 20 24Time (hours)

0

0.5

1

1.5

Energy(kW

h) Vnom

Vlow

Vhigh

Figure 2.30: Resultant Demand Profiles of CWSH goods with high, nominal, and low supplyvoltages, the effect of the supply voltage upon the load demand can be seen as shifting of both

the instantaneous power and time out use patters

figures has been produced.

Figure 2.31 shows the average profile from 1000 random individual domestic profiles, where the

load is split up into thermal load and non thermal load. It is noted that any single domestic load

is unlikely to resemble this profile, typically more resembling a square type wave as the customers

individual loads are turned on and off.

2.3. Loads Profiles and Models 63

0 4 8 12 16 20 240

200

400

600

800

1000Present Domestic Load

Powe

r

0 4 8 12 16 20 240

50

100

150

200

250

300Present Thermal Load

Powe

r

0 4 8 12 16 20 240

500

1000

1500

New Load from LCT

Powe

r

0 4 8 12 16 20 240

500

1000

1500

2000

2500Effect of LCT

Powe

rNon ThermalThermalTotal

White GoodsCWSH

EVHP

Domestic & LCTDomestic

Figure 2.31: Average Domestic 24 hour demand profile, the load is comprised of: ThermallyControlled (White Goods & Restive Based), Static, EV and HP loads. Non LCT profiles

from [49].

Chapter 3

Effect of Wider Voltage Tolerance

on Domestic Loads

Widened voltage tolerance is one way voltage constraints can be eased / removed from LV networks

where excess loading or DG has caused voltage profiles to stay outside or regulator standards, prior

to thermal or other network constraints being reached.

Prior to considering the benefits of de-regulation on the network, an assessment of the social

and technological effects a wider voltage band has upon the loads subject to these changes is

presented in this chapter. To aid in this goal, a list of consumer and domestic electrical devices is

first grouped so that the effect of voltage variations on each of these groups can be analysed, these

groups are:

� Lighting

� Heating

� Motors (e.g. motors, white goods)

� Electronic Equipment (e.g. TVs, PCs)

Within each of the above groups there is clearly much variation in the technologies used and

hence the effect wider voltage tolerances will have within each group. As such, the following

analysis aims only to give a broad overview of each groups characteristics.

Results from this chapter where published in the Top and Tail report “Impact of Wider Voltage

Tolerances on Consumer Electronics and Wider Socialised Costs” [38]. This report further served as

a foundation for The UK Energy Research Centre (UKERC) report “Consumer attitudes to changes

in electricity supply voltage” [40] which via customer surveys, addressed customers attitudes to

power quality, with the aim to inform policy development. Further reference to the effects of

de-regulation presented here was made in [76].

64

3.1. Domestic Energy Use 65

3.1 Domestic Energy Use

In 2000, 85% of energy use in the domestic sector was used for space and water heating [77]. This

comes from a range of energy sources as illustrated in Table 3.1, where in 2012, space and water

heating accounted for 82% of domestic energy usage [78].

Table 3.1: Overall UK Domestic Energy Use (ktoe=11.6 G Wh)

Fuel TypeThousand tonnes of oil equivalent (ktoe)

Space heating Water Cooking Lighting / Appliances Total

Solid fuel 666 42 - - 709

Gas 22,540 6,004 612 - 29,156

Electricity 2,098 650 503 6,611 9,862

Oil 2,281 425 - - 2,705

Heat sold 52 - - - 52

Bioenergy and Waste 669 - - - 669

Total 28,306 7,120 1,116 6,611 43,153

Total energy use by fuel type in the UK domestic sector in 2012 is shown in Figure 3.1:

Figure 3.1: Domestic Energy Use by Fuel Type

Electrical energy use constitutes less than a quarter of overall energy usage. However this is

known to increase as new electric based technologies become more popular, such as electric vehicles

and heat pumps which reduce domestic gas demand. Overall, whilst it is expected that electrical

energy use in the domestic sector will increase it is noted that overall energy use from centralised

sources (gas and electricity) will actually reduce, due to greater amounts of DG and the improved

efficiency of domestic appliances and particularly space heating (replacing gas heating with heat

pumps [79]).

To get a more accurate indication of the end use of domestic electrical energy figures shown

previously, the data in [78] is split up into more specific sectors, shown next in Tables 3.2-3.7, note

that 1 ktoe is approximately 11.6GWh.

3.1. Domestic Energy Use 66

Table 3.2: Domestic Lighting Energy

Device Energy Use (ktoe)

Standard Bulb 142

Halogen 594

Fluorescent Strip 105

Energy Saving 332

LED 9

Table 3.3: Domestic Cooling Goods Energy

Device Energy Use (ktoe)

Chest Freezer 108

Fridge-freezer 681

Refrigerator 166

Upright Freezer 214

Table 3.4: Domestic Washing Goods Energy

Device Energy Use (ktoe)

Washing Machine 394

Washer-dryer 209

Dishwasher 287

Tumble Dryer 406

Table 3.5: Domestic Electrical Goods Energy

Device Energy Use (ktoe)

TV 746

Set Top Box 364

DVD/VCR 155

Games Consoles 81

Power Supply Units 522

Table 3.6: Domestic ICT Goods Energy

Device Energy Use (ktoe)

Desktops 273

Laptops 128

Monitors 152

Printers 10

Multi-Function Device 24

Table 3.7: Domestic Cooking Goods Energy

Device Energy Use (ktoe)

Electric Oven 268

Electric Hob 270

Microwave 217

Kettle 386

From the data in Tables 3.2-3.7 we have the following split (see Figure 3.2) of electrical energy

consumption by usage sector.

Figure 3.2: Detailed domestic Electrical Energy Use by Sector [78]

The Centre for Renewable Energy Systems Technology (CREST) have used a list of common

domestic devices for generation of daily demand load profiles [49]. A report by Intertek [80] lists all

3.1. Domestic Energy Use 67

the electrical loads found in a monitoring scheme carried out across 251 houses, with an overview

of this report in [81]. Due to the great number distinct devices (115) in the Intertek report,

assessment of the effect of widened voltage tolerances will be limited to the groupings of the 31

devices in [49]. These is shown in Table 3.8 along with the grouping.

Table 3.8: Grouping of Loads IN CREST Profiler

Device Group Device Group

Standard Light Bulb L Set Top Box E

Halogen L DVD/VCR E

Fluorescent Strip Light L Games Consoles E

Energy Saving Bulb L Power Supply Units E

LED E HI-FI E

Chest Freezer* M, E Iron H

Fridge-Freezer* M, E Vacuum M

Refrigerator* M, E Telephone Cordless E

Upright Freezer* M, E Electric Oven** H

Washing Machine H/M, H/E Electric Hob** H

Washer-dryer ** H/M, H/E Microwave E

Dishwasher** H/M, H/E Kettle* H

Tumble Dryer H/M, H/E Water storage Heater* H

Desktops E Electric Water Heater H

Laptops E Electric Shower H

Monitors E Storage Heaters* H

Printers E Other Electric Heating* H

Multi-Function Devices E Heat Pumps* M, E

TV E

* Denotes thermal cycle loads

** Denotes possible thermal cycle loads

As stated, from an electrical perspective, working with devices by sector is not helpful; it is

of more use to class all of the loads in the home by their respective electrical characteristics. For

example, the electrical heating sector is comprised of either electrical storage heating devices, using

an electric element to heat up a large mass that maintains temperature thought out the day or

heat pumps that are like the cold products and comprise of a compressor and motor system.

With reference to the 4 electrical categories mentioned in the introduction, Appendix A groups

each product considered into one or more of these electrical categories of: Heating (H), Lighting

(L), Electronics (E), or Motors (M). In some cases classification is obvious, but for others it is

not so, for example, a washing machine could be listed as heating, motor, or an electronic supply

class of load. The actual classification in this case will ultimately depend upon how the motor is

connected to the supply. In older machines, and still many modern machines, the motor is a single

phase induction motor that is capacitor run. The speed control here is achieved by adjustment

3.2. Socialised Cost & Device Numbers 68

of pole number or mechanically. Alternatively, the machine may use a DC motor or AC motor

and a power electronic drive. Improved control and efficiency are advantages of this latter scheme

but they are costly and a relatively new development in this application. Still, both types should

be considered, especially as the average washing machine has a life expectancy of 16 years [77].

Continuing with the example of the washing machine, the water for the machine is usually heated

within the machine by an element so it can control water beyond limitations of the main hot water

supply. Hence, a washing machine can be electrically grouped as a heater and motor, heater and

electronic, or an electronic type load.

It is apparent that most of the devices listed in Appendix A, will have low voltage circuits

(control circuits). These, for reasons of practically, and use in LV simulations (ie. is their demand

relative to the whole good is small) will not be considered in detail.

3.2 Socialised Cost & Device Numbers

In 2012 there were 27.1 million houses in the UK and a population of 64.1 million; this means the

average house size is 2.36. To find out what types, and how many electrical products, are used in

the UK, figures from DECC [78] were assessed and are presented in this section.

This allows effects of de-regulation to be weighted with trends in the use of specific electrical

products. This is important for predicting the socialised costs of voltage deregulation, where simply

looking at device electrical characteristic does not give a wider picture of the social costs (i.e. if

certain classes of device would need replacement). Tables 3.9-3.14 presents the number of devices

owned in the domestic sector in the UK in 2012 [82].

Table 3.9: Domestic Ownership - Lighting

Device Amount (x1000)

Standard Bulb 78074

Halogen 262801

Fluorescent Strip 15603

Energy Saving 351786

LED 4574

Table 3.10: Domestic Ownership - Cooling

Device Amount (x1000)

Chest Freezer 4183

Fridge-freezer 18585

Refrigerator 10112

Upright Freezer 8382

Beyond the number of devices owned presently, future ownership trends must be taken into

account. As an example, filament lighting luminous output is known to be very sensitive to voltage

changes [83], so much so, that it could be considered a major barrier to voltage deregulation.

However the trend to change away from filament lighting (especially since 2008) to more efficient

fluorescent and LED alleviates this problem. The trend in ownership of lighting technologies since

1990 is illustrated in Figure 3.3.

If wider voltage tolerances were suddenly applied, given the effect on the luminosity of filament

3.2. Socialised Cost & Device Numbers 69

Table 3.11: Domestic Ownership - Washing

Device Amount (x1000)

Washing Machine 21577

Washer-dryer 4179

Dishwasher 10112

Tumble Dryer 12278

Table 3.12: Domestic Ownership - Electrical

Device Amount (x1000)

TV 63042

Set Top Box 34620

DVD/VCR 38070

Games Consoles 20963

Power Supply Units 199382

Table 3.13: Domestic Ownership - ICT

Device Amount (x1000)

Desktops 10547

Laptops 267224

Monitors 20414

Printers 8192

Multi-Function Device 17667

Table 3.14: Domestic Ownership - Cooking

Device Amount (x1000)

Electric Oven 17466

Electric Hob 12124

Microwave 23231

Kettle 26095

1990 1995 2000 2005 2010 2015Year

0

100

200

300

400

500

Number

Owned

(Millions)

Standard Light BulbHalogenFluorescent Strip LightingEnergy Saving Light BulbLED

Figure 3.3: Ownership of Lighting Products by Type in the UK domestic Sector

lighting is large, this would force an uptake of more efficient technologies that are less sensitive to

voltage change. However this obviously has a large social impact (i.e. effectively forcing people to

change lighting fixtures).

From Figure 3.4 we see there is a large trend towards more efficient (class A rated) cold devices

since 2004. In such devices, higher efficiency ratings are achieved by increasing the performance

of the insulation and /or replacing of single phase induction motors with adjustable speed drives

(ASD) and other types of AC or DC motors.

Sectors of recent growth in the domestic sector are those of ICT and consumer electronics.

These ownership patterns are shown in Figures 3.5 & 3.6 respectively.

Separate PSUs used for a variety of electronic devices now represent the most common electrical

load outside of lighting products in the house. Other electronic equipment and ICT products will

use a dedicated PSU. The advantage of separate PSU from a de-regulation point of view is that

3.2. Socialised Cost & Device Numbers 70

2004 2006 2008 2010 2012 2014Year

0

20

40

60

80

PercentageofGoods

RatedClass

AorHigher

Chest FreezerFridge freezerRefrigeratorUpright freezer

Figure 3.4: Ownership of Class A rated cold goods

1990 1995 2000 2005 2010 2015Year

0

10

20

30

Number

Owned

(Millions)

DesktopsLaptopsMonitorsPrintersMulti-Function Devices

Figure 3.5: Ownership of ICT Products by Type in the UK domestic Sector

1990 1995 2000 2005 2010 2015Year

0

50

100

150

200

250

Number

Owned

(Millions)

TVSet Top BoxDVD/VCRGames ConsolesPower Supply Units

Figure 3.6: Ownership of Consumer Electronic Products by Type in the UK domestic Sector

if performance were deemed unsatisfactory following voltage deregulation, it is cheap and easily

replaced by the end user. This is obviously not so true for the integrated PSUs common to the

majority of other products in the ICT and consumer electronics sectors.

3.3. Voltage Tolerance - Experimental and Simulation 71

3.3 Voltage Tolerance - Experimental and Simulation

To see how loads change with the supply voltage, and at what point malfunction or other key

changes to the device operation occur with wider supply voltages, simulation and lab testing were

carried out for some domestic loads.

� Motors

� PSU Magnetics

Although not exhaustive, these two load classes have somewhat more complex voltage sensitivity

characteristics than the two other load group class of heating and lighting.

3.3.1 Motors

The performance of any motor is tied to the load that it is driving. Broadly these mechanical

load types will have a torque - speed characteristic of either: constant power, constant torque, or

variable torque. These are presented for specific loads in Table 3.15.

Table 3.15: Load Torque Speed Relationships

Device Torque - Speed Loading

Conveyor Constant

Centrifugal pump Increases with speed squared

Fans Increases with speed squared

Screw Compressor Constant

Scroll Compressor Constant

Piston Compressor Constant

Winders Constant or decrease with speed

Mixers Increases with speed

Hoist Constant

Centrifuge Increases with speed squared

Relevant to the domestic environment are: mixers, centrifuges, hoists, fans, compressors. These

loads can be found when used in: food processors, washer dryers, lifts or stair lifts, air fans for

cooling/circulation, and fridge freezers / air conditioning, respectively.

Simulation of Motors

A single phase induction motor (SPIM) was simulated under steady state (SS) operation and

coupled to a model of a fridge that uses a constant torque type compressor and a temperature

control system using a hysteresis controller. This is shown in greater detail in Appendix D.

3.3. Voltage Tolerance - Experimental and Simulation 72

The speed of the motor when driving a constant torque load (here a fridge) with a varying

supply voltage is shown in Figure 3.7. Speed (and therefore power) is seen to remain almost

constant until the supply voltage falls to around 0.75 of nominal.

Start/Run Capcitor SPIM & Constant Toruqe Load

0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5Voltage (pu)

0

50

100

150

200

Speed(rad/s)

Figure 3.7: Speed of SPIM in a fridge with different Supply Voltages

The thermal control system for the fridge can be of varying complexity, in this model the control

system is a hysteresis controller. This control scheme turns the motor compressor on when a certain

air temperature is reached and turns it off once a new lower temperature has been reached.

0 0.2 0.4 0.6 0.8 1Time (hours)

0

2

4

6

8

10

Tem

p(◦C)

0.6pu

0.7pu

0.8pu

0.9pu

1.0pu

Figure 3.8: Fridge Temperature with Differing Supply Voltages

Figure 3.8 shows the temperature of the fridge when the supply voltage is reduced from 1.0pu to

0.6pu in steps of 0.1pu. At 0.6pu voltage (Figure 3.8) the motor is unable to produce the required

torque to start the compressor and the fridge will not work. At 0.7pu voltage the starting capacitor

remains permanently engaged as the motor never reaches cross over speed, here the cooling output

is insufficient to cool the fridge to desired temperatures.

3.3. Voltage Tolerance - Experimental and Simulation 73

Testing of Compressor Motor Systems

Single or quasi-dual phase motors are common in white goods (e.g. refrigeration and washing); the

load torque presented to the motor is the main difference between these goods from an electrical

perspective.

To verify simulation results (as in Figure 3.9 for a SPIM) and those in shown previously, lab

measurements on a fridge were taken.

0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2Voltage (pu)

0

100

200

300

Power

(W,VAr,Tω) Active

Reactive

Mechanical

Figure 3.9: PQ Demand for Fridge Simulated

The fridge was tested with a VARIAC supply and an AMTEK power quality meter. Voltage

range from the VARIAC was adjustable from 260V-0V. The motor was tested at various supply

voltages and given time to reach steady state. Over the voltage range of the VARIAC the power

and reactive power of the fridge was recorded and is shown in Figures 3.10 & 3.11:

0.4 0.5 0.6 0.7 0.8 0.9 1 1.1Voltage (pu)

0

50

100

150

200

Power

(W/Var)

Active

Reavtive

Figure 3.10: PQ Demand for Fridge Measured

Below 0.6 of nominal voltage the motor stalls, and the power drawn increases. However over

a wide voltage range (0.6-1.1) the motor operates largely as a constant power load. Once stalled,

if the voltage is restored (�0.6), the motor has a restart delay time where the power consumption

3.3. Voltage Tolerance - Experimental and Simulation 74

0.4 0.5 0.6 0.7 0.8 0.9 1 1.1Voltage (pu)

0

200

400

600

800

1000

Power

(W)

Active

Active (Stalled)

Figure 3.11: PQ Demand for Fridge Measured with Stalled & Normal Operation

rapidly increases. This is due to the back pressure in the compressor and time must pass before

the motor is able start again. This effect is shown in Figure 3.11 where the power drawn when the

motor has stalled and still unable to restart is clearly seen.

This type of effect is also seen with air conditioners that usually have a voltage stalling point

higher than the fridge tested. The effect can be that voltage recovery after a short voltage sag can

be delayed by these loads [84]. Wherever this type of stalled behaviour is possible, thermal relays

are included that trip if the current is too high following a stall condition for a given period, as

indeed was the case with the fridge tested.

3.3.2 Magnetics in Power Supplies

Design of a Flyback Transformer

Another class of common domestic appliances is electronics such as set top boxes and CD players,

which tend to use a flyback SMPS on the input following the rectification stage.

Figure 3.12: Topology of Flyback Converter

The flyback converter is an isolated dc-dc converter commonly used in domestic goods upto

3.3. Voltage Tolerance - Experimental and Simulation 75

100W the output can be higher or lower than the input and is:

VoutVin

� n�D

1�D(3.1)

where D is the duty ratio.

Here, a flyback converter is designed to produce a constant output voltage when supplied from

a 230V (-6, +10%) rectified AC source with negligible voltage ripple across the output capacitor in

the rectifier. Ideally this is equivalent to a 194.6V DC supply at the input of the flyback when the

supply voltage is at its minimum specified value. The flyback should produce 48V and operate at

the discontinuous current boundary (DCB) when supplying its rated power of 100W at its minimum

supply voltage 194.6V . The switching frequency of the flyback is set by the controller’s oscillator

to 100 kHz. A duty cycle of 50% at DCB is also specified and here the flyback is assumed 90%

efficient. These specification are summarised in 3.16 and enable design of the flyback’s transformer.

Table 3.16: Flyback Converter Specification

Parameter Value Parameter Value

�Vin 194.6 Vo 48 V

�Vin 205 Po 100W

fsw 100 kHz Io 2.083 A

η 90% Dmax 0.5

Results of the initial design stage of the flyback are shown in Table 3.17.

Table 3.17: Basic Values for Flyback

Parameter Value Parameter Value

�Iin 0.571 A Ip,rms 0.93 A

Pin 111.1 W L1 426H

Rin 340.81 L2 27 H

Ip 2.28 A N1:N2 (n) 3.97

Vdiode 1V

From the initial specification the magnetic design can now proceed; the design is based upon

the design principles laid out in Magnetics Design Handbook [85]. The energy storage (E) in the

primary inductor is:

E �I2pL1

2(3.2)

The electric constant (Ke) is given at a peak saturation flux density (Bm), which in the case

3.3. Voltage Tolerance - Experimental and Simulation 76

of ferrite cores is set to be 0.25T. Giving:

Ke � 0.145�10�4PoB2m (3.3)

Now the core geometry constant (Kg) is found with:

Kg �E2

Keα(3.4)

A window utilisation factor (Ku) of just 0.29 is appropriate for high frequency SMPS flyback

transformers as shown in the literature [85]. The magnetic core is defined with:

Ap �WaAc (3.5)

Where Ap is the area product which is defined as the product of the winding window area (Wa)

and the cross section area of the core (Ac). The magnetic design parameters are shown in Table

3.18.

Table 3.18: Values for Magnetic Components in the Flyback

Parameter Value

E 1.11 mJ

Ke 1.3� 10�4

Kg 1.27� 10�2

From this an EDF-25 type core with 3C85 grade ferrite is selected using the required value of

Kg calculated previously. This is the point in design where the magnetics would be chosen to be

overrated or not. In this example the core is chosen to be the smallest available standard size EDF

type core with a Kg greater than required. EDF type cores have a low profile that is popular

where space savings are given a high priority and where space saving is facilitated by using a core

with a low profile.

Table 3.19: Parameters of an EDF-25 core with 3C85 Material

Parameter Value Parameter Value

MLP 5.7 cm Area Product �Ap� 0.394 cm4

Core Weight �Wtfe� 16 g Core Geometry �Kg� 0.019 cm5

Copper Weight �Wtcu� 11.5 g Surface Area �At� 21.6 cm2

MLT 4.8 cm Core Permeability 2500

Iron Area �Ac� 0.58 cm2 Winding Length �Lw� 1.86 cm

Window Area �Wa� 0.679 cm2

3.3. Voltage Tolerance - Experimental and Simulation 77

Current density is:

J � 2� 104E

BmApKu(3.6)

The area of window for the primary windings is:

Apw � Ip,rms

J(3.7)

The correct wire is now chosen based on the skin depth of the conductor, for this example it

is # AWG 26 gauge wire to be used, this has an un-insulated area of 0.00128 cm2 shown in the

Table 3.20.

Table 3.20: Data for AWG #26 Copper Wires

Parameter Value

Gauge #26

Conductor Area (A#26) 0.00128 cm2

Total Area 0.001603 cm2

Resistivity (ρ#26) 0.1345 Ω/m

Table 3.20 allows the number of stands (Sp) and primary windings (Np) with half of the window

area allocated to the primary and half to the secondary winding to be chosen:

Sp � Apw

A�#26� (3.8)

Np�est� �Wa

2 �Ku

SpA#26(3.9)

The air gap length (lg) is:

lg �0.4πN2

pAc � 10�8

L1� MLP

μm(3.10)

Fringing effects (F) must next be taken into account then used to recalculate the number of

primary turns:

F � 1� lg�Ac

� ln

�2Lw

lg

�(3.11)

Np ��

lg � L

0.4πAcF � 10�8(3.12)

3.3. Voltage Tolerance - Experimental and Simulation 78

The peak flux (Bpk) density and AC flux (Bac) is:

Bpk �0.4πNpFIp � 10�4

lg �MPLm(3.13)

Bac �Bpk

2(3.14)

The secondary turns are calculated assuming DCB operation:

Ns �Np�Vo � Vd�Doff

VpD(3.15)

Choice of secondary winding values and window utilisation (Ku) are shown in Table 3.21.

Using the above design process the final design parameters are shown in Table 3.21.

Table 3.21: Parameters and Design Choices for Magnetic Components of a Flyback

Parameter Value Parameter Value

J 648.6 A/cm2 Bac 0.142

Apw 0.0014 cm2 Ns 15.9(16)

SP 1.123 (1) Is 8.332 A

Np�est� 76.9 (77) Is�rms� 3.402 A

lg 0.078 cm Asw 0.0052 cm2

F 1.5 Ss 4.1(4)

Np 62.7(63) Ku 0.239

Bpk 0.262

Winding losses (Pcu) and regulation (α) then calculated as given in Table 3.22. The core losses

(Pcore) and total losses (Pt) for 3C85 material, using 3 given constants are calculated:

Pcore�kg� � 4.85� f1.63sw �B2.62ac (3.16)

Pcore �Pcore�kg�Wtfe

1000(3.17)

Pt � Pcu � Pcore (3.18)

Finally, the loss density (φ) and resultant core temperature rise (Tr) are found:

ψ �Pt

At(3.19)

3.3. Voltage Tolerance - Experimental and Simulation 79

Tr � 450 ψ0.826 (3.20)

Table 3.22: Losses Incurred in the Magnetic Components of a Flyback

Parameter Value Parameter Value

ρp 0.135 Ω/m α 0.68%

ρs 0.034 Ω/m Pcore�kg� 33.5 W/kg

Rp 0.407 Ω Pcore 0.536 W

Rs 0.026 Ω Pt 1.214 W

Pp 0.379 W ψ 0.056 W/cm2

Ps 0.299 W Tr 41.7 �C

Pcu 0.678 W

To see the effect of wider voltage tolerances, the magnetic design is kept the same but the

regulatory minimum voltage is reduced from 0.94pu of the nominal voltage to 0.85pu of the nominal

voltage; or 176V DC at the input to the flyback. The duty ratio must also be adjusted to regulate

the output voltage that is proportional to the input voltage in continuous current mode (CCM),

here needing a new duty of 52.5%, the flyback will also have entered CCM.

The energy storage in the inductor that is released to the load must be kept constant as the

output voltage is regulated and the load had been represented by a resistance. Meaning the power

and consequently energy that is released by the inductor must remain the same each cycle. As the

voltage has fallen by 9.57% and the duty cycle has been raised by 5.02% the current build up in

the inductor during the on period is now 95% of its previous value. From:

E �1

2LI2 (3.21)

For the energy to remain constant the peak current (I) must increase to a higher value which

means the minimum current (I) must become greater than zero i.e. the flyback enters CCM.

E �1

2L�I2 � I2� (3.22)

The new value of ΔI (defined as: I � I )is found using the duty, and supply voltage. The

energy (E) must stay constant, so the new value of I is found by:

I2DCB�E (3.23)

I2 � I2 � I2DCB (3.24)

3.3. Voltage Tolerance - Experimental and Simulation 80

I � I � ΔI (3.25)

I2 � 2I I � I2 � ΔI2 (3.26)

With simultaneous equations:

I �ΔI2 � I2DCB

�2ΔI(3.27)

This allows the minimum current to be found analytically. For operation of the flyback at

reduced supply voltage (-15% of nominal) the operation parameters are shown in Table 3.23 fol-

lowing.

Table 3.23: Values of Flyback Operating with Reduced Supply Voltage

Parameter Value Parameter Value

�Vin 175.95 V ΔI 1.953 A

Dmax 0.525 I 2.056 A

Ton 5.25 s I 0.106 A

E 0.1 mJ Ip,rms 0.884 A

The winding losses have now increased, as has the peak flux and consequently peak energy

storage in the inductor (which is indicative of inductor size) but the AC losses in the core are

reduced (�ΔI).The overall losses in the transformer of this particular design with reduced voltage

are decreased; these losses are shown in Figure 3.13.

0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9Voltage (pu)

0

0.5

1

1.5

Losses

(W)

Core

Copper

Total

Figure 3.13: Losses in Flyback Transformer

From Figure 3.13, when the flyback is in CCM (i.e. below 0.94 pu), as the core losses are a

function of the AC flux component, at lower supply voltages this AC flux reduces, accordingly

the core losses also reduce. The winding losses increase as the RMS current flowing though each

3.3. Voltage Tolerance - Experimental and Simulation 81

winding increases. The peak energy storage and the peak flux density increase as the supply

voltage is lowered. If the specific flyback in section this had to be rated for worldwide operation

(110-240V) then the magnetic design would need to be changed.

0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9Voltage (pu)

0.23

0.24

0.25

0.26

0.27

0.28

PeakFluxDensity

(T)

Figure 3.14: Peak Flux Density of Flyback Transformer

The peak flux is shown in Figure 3.14 above. From comparison of Figures 3.13 & 3.14 it is seen

that the core in this particular design will be limited by saturation (peak flux above 0.25T) when

the supply voltage falls below 0.67pu of nominal. It will not be limited by temperature rise from

losses that are seen to remain reasonably constant over a wide input voltage range.

The previous magnetic design is valid for CCM (or DCB) flyback converters. Initially, this was

the case (0.94pu), after the magnetic design is completed; the design can then be applied to DCM

operation (higher voltage or lower load).

Design of Filter Inductor for PFC Boost Converter

A similar magnetic design approach to that outlined in previously is followed for a PFC boost

converter and relevant inductor. The PFC boost converter was originally specified to operate with

a voltage supply down to 0.94 of nominal.

Figure 3.15: Topology of Boost Converter

Unlike the flyback convert the output voltage is not isolated from the input and as the name

implies the boost converter is not able to step down the output voltage. The output voltage (Vout)

3.3. Voltage Tolerance - Experimental and Simulation 82

is:

VoutVin

� �

1

1�D(3.28)

where D is the duty ratio.

Losses in the inductor when the boost converter operates with a supply voltage of 0.94pu and

with an output ripple current of 20% of the peak current are dominated by the copper losses. This

is due to the AC flux swing being small and consequently the core losses are negligible compared to

the copper loss. The copper losses are shown against the supply voltage in Figure 3.16. As voltage

is reduced the peak flux again increases and the flux ripple consequently decreases yet further,

meaning the core losses reduce from what was already a negligible value compared to the copper

losses. As the peak flux has increased the peak current and therefore copper losses have increased.

This is visible in Figure 3.16 where only the copper losses are shown due to their dominance in the

total losses on the inductor.

0.45 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9Voltage (pu)

0

2.5

5

7.5

10

Losses

(W)

0

0.2

0.4

0.6

0.8

FluxDensity

(T)Losses

Flux

Figure 3.16: Copper Losses & Peak Flux Density in the Inductor of a Boost Converter for PFCwith varied supply voltage

The peak flux in the core is shown in Figure 3.16 where, due to the design procedure followed

here, a standard sized core almost exactly suited for operation at 0.94pu supply voltage was

available, and chosen, hence flux rises above the saturation value (0.25T) with only slightly reduced

supply voltages. This is indicative of a core that was very tightly designed to a specific voltage

supply band and with the core as small as possible, so to reduce manufacturing costs.

Losses from the windings and saturation of the magnetic core will be limiting factors in this

boost PFC inductor. There will be reduced losses and peak flux in the filter inductor when operated

with higher supply voltages.

3.4. Voltage Tolerance - Literature 83

3.4 Voltage Tolerance - Literature

As the results presented in section are based on the equations that are commonly used to describe

the voltage sensitivity of a load, namely the ZIP parameter based equations ((2.52) & (2.53)), and

the exponential form equations ((2.56) & (2.57)), are repeated here for clarity:

Pm � Pnom �

�Zp

�VmVnom

�2

� IpVmVnom

� Pp

Qm � Qnom �

�Zq

�VmVnom

�2

� IqVmVnom

� Pq

Pm � Pnom �

�VmVnom

�np

Qm � Qnom �

�VmVnom

�nq

The work literature review herein presents values for the ZIP parameters (Zp, Ip, Pp, Zq, Iq, Iq)

and the powers (np, nq) found in the literature, then curve fitted representative results for all the

works are given.

Static Voltage Sensitivity Studies

Reference [86] presented a general model for power system stability studies, as well as sensitivity

ratings for frequency dependence of loads. Exponential form values of voltage dependence are

shown in Table 3.24.

Table 3.24: Sensitivity Results from [86]

Device np nq

Incandescent lamp 1.6 0

Fluorescent lamp 1.2 3

Heating 2 0

Induction motor, half load 0.2 1.5

Induction motor, full load 0.1 2.8

Electric heating systems behave as a constant impedance, as would be expected, and the in-

duction motor is mostly sensitive in reactive power to voltage changes. The difference between

traditional filament lighting and florescent lighting is also shown, where florescent lighting has

considerable reactive power sensitivity.

Reference [87] was also a complete look at lighting, heating and motor systems. Results from lab

3.4. Voltage Tolerance - Literature 84

tests on different lighting technologies and on-site tests of street lighting were compared. Response

of thermally controlled heating systems to voltage change was investigated as were refrigerators.

Lighting results from this report are presented in Table 3.25 below. The turn off voltage of the

different lighting technologies was also recorded, and is shown.

Table 3.25: Sensitivity Results from [87]

Device Voff Poff np nq

Incandescent Light - - 1.5-1.6 -

Fluorescent lamp (72 W) 160 30 2.0-2.2 4.56.5

Mercury lamp (250 W) 180 165 2.2-2.4 4.0-6.0

High pressure sodium lamp (250 W) 180 180 2.1-2.5 -

Low pressure sodium lamp (91 W) 80 60 0.3-0.5 -

Low-energy lamp (11 W) 60 2.6 0.8-1.2 1.0-1.5

The lighting most applicable to domestic setting are: incandescent, florescent, and low energy

(CFL). Of these, the fluorescent light was the first to turn off when voltage was reduced below

0.7pu of the nominal supply voltage.

In Table 3.25, results are seen to differ for the two fluorescent lights, as the low energy light

used an electronic ballast whist the florescent light an inductive ballast.

In the temperature controlled heating system, the power after a 20% reduction in supply voltage

was recorded. The plots in Figure 3.17 show the load power after this supply voltage reduction

for both electronic, and bi-metallic thermostats, with the mean power recorded over a period

appropriate to the thermal cycle time for a house.

(a) Electronic Thermostat (b) Bi-metallic thermostat

Figure 3.17: Heating Element Power in Response to Step Voltage Change [87]

The bi-metallic switch thermostat system actually consumes more power after the reduction in

supply voltage. In both cases the peak measured power will be lower after the voltage reduction

3.4. Voltage Tolerance - Literature 85

as Table 3.24 had shown heating to have constant impedance voltage sensitivity; it is instead the

increased duty cycle that increased the longer term power drawn.

Tests were carried out on some common domestic loads, two fridges in [87] were tested for their

voltage sensitivity, with these results as shown in Table 3.26.

Table 3.26: Sensitivity Results from [87]

Device np nq

Refrigerator A 1.3-1.6 3.1-3.3

Refrigerator B 1.3-1.8 2.8-3.2

Both fridges were seen to stall at 0.6pu supply voltage, whereupon the current increased sub-

stantially. Like the induction motors measured in [86] from Table 3.26, it is seen there is a greater

voltage sensitivity of the reactive power than that of the active power. However, unlike before

there is substantial active power sensitivity; this may be due to the type of compressors used in

the fridges in these tests or the range of voltages used in the authors curve fitting process.

A report in 2010 [84] presents voltage sensitivity results for typical loads in domestic and

residential settings. Tests on electronic ballast florescent lighting (Lights A & B), and CFLs (now

the most common form of lighting in the UK [78]) and two PCs were conducted.

Power and minimum supply voltage results are shown in Table 3.27, as are voltage sensitivity

figures for the two lights in Table 3.28.

Table 3.27: Sensitivity Results from [84]

Device Power (W) Reactive (VAr) Power Factor Voff (pu) Von (pu)

Light A 56.3 -33 0.86 0.1 0.14

Light B 61.3 -23.8 0.93 0.1 0.39

CFL A 22.2 -12.4 0.87 0.2 0.25

CFL B 26.1 -13.7 0.88 0.2 0.25

PC w/ LCD 152 -14.4 0.99 04-0.5 0.53-0.65

PC w/ CRT 225 -17.4 0.99 0.4-0.5 0.54-0.67

Table 3.28: Sensitivity Results from [84]

S0 Vmin Power (P) Reactive Power (Q)

Device (VA) (pu) Z I P Z I P

Light A 56.3 0.1 0.27 0.79 -0.05 -0.37 1.37 0

Light B 61.3 0.1 -0.13 1.2 -0.07 -0.73 1.72 0

The lights are able to operate down to low voltages without extinguishing, and for the two

fluorescent lights tested present a load that is mostly constant current type (see Table 3.28), with

a greater voltage sensitivity in reactive power.

3.4. Voltage Tolerance - Literature 86

For the PCs both devices behaved as constant power loads until the minimum voltage, which

was at or below half of the nominal value. Turn on following these occurrences was notably higher,

with the CRT PC seen not to turn back on until voltage returned to 0.67 of nominal.

In [3] domestic loads were analysed for their static voltage sensitivity parameters, which were

then used in distribution networks models chosen to represent networks across the US; as was also

done in [88]. Results showed conservative voltage reduction (CVR) an effective method to reduce

the energy consumption and reduce peak demand in all but 2 of the 25 feeders tested.

A comprehensive report [89] on air conditioning units (ACU) was carried out in 2006 by South-

ern California Edison. Performance of the air conditioners was measured and the performance of

the motor in response to voltage change tested. Continuing this work [90] presented methods for

load modelling where large amounts of ACU are present, and its importance in system stability

studies. Delayed voltage recovery (DVR) was the finding from these works, and methods to accu-

rately model this issue were presented. The main cause of this delayed voltage recovery is stalled

single phase induction motors with constant torque loads that are prone to stalling (due to low

inertia). In [89] the final recommendation is that contactors be set to remove these motor systems

(i.e. ACUs) from the network when the voltage falls below the maximum stalling voltage of the

motors tested. A value of 0.78pu voltage is given in the paper. Though it might be thought this

work is of limited relevance to LV systems in the UK, if in the future more HP were installed in the

UK, due to the similarities of HP and ACU (high power constant torque compressor systems with

low inertias) this type of study would need to be considered, especially if wider voltage tolerances

were also introduced.

Reference [91] tested 13 types of load with a total of 55 distinct devices tested. For smaller

lighting loads multiples of the same device were connected to make a 15A load at nominal voltage.

Results were gathered for voltage sensitivity and using equations (2.52) and (2.53). The minimum

supply voltage prior to device failure was also recorded. These results are shown in Table 3.29.

The magnetic ballast fluorescent lighting and microwave are the two domestic products found

to be most sensitive to voltage (with regards to their correct functioning), with both failing at

0.83 of nominal voltage. All other devices tested continued to work down to, or below, 0.8 of the

nominal voltage.

Voltage sensitivity of common loads was also investigated in [92]. This testing was performed

with slow voltage magnitude ramps and with separate tests using voltage magnitude oscillation

and step changes. Results were not initially constrained with (2.54) and (2.55). Results from this

work are shown in Table 3.30.

3.4. Voltage Tolerance - Literature 87

Table 3.29: Sensitivity Results from [91]

Device Snom VminActive Reactive

Z I P Z I P

Dryer Heater 5400 0.5 0.96 0.05 -0.01 0 0 0

Dryer Motor 515 0.5 1.91 -2.23 1.32 2.51 -2.34 0.83

Washing Machine 654 0.5 0.05 0.31 0.64 -0.56 2.2 -0.64

AFD 1 1800 0.75 0.43 0.61 -0.04 -1.21 3.47 -1.26

AFD 2 1780 0.75 3.19 -3.84 1.65 1.09 -0.18 0.09

Heatpump 1 (capacitor) 1160 0.75 0.72 -0.98 1.26 14.78 -23.72 9.94

Heatpump 2 (blower) 575 0.87 5.46 -14.21 9.75 -14.85 31.59 -15.74

Heatpump 2 (compressor) 5700 0.87 0.84 -1.4 1.56 22.92 -40.39 18.47

Fridge Freezer 1030 0.76 1.19 -0.26 0.07 0.59 0.65 -0.24

Battery Charger 6430 0.61 3.51 -3.94 1.43 5.8 -7.26 2.46

CFL 1 (electronic) 60 0.5 0.14 0.77 0.09 -0.06 -0.34 -0.6

CFL 2 (electronic) 53 0.5 0.16 0.79 0.05 0.18 -0.83 -0.35

CFL (magnetic) 151 0.83 0.34 1.31 -0.65 3.03 -2.89 0.86

FL 1 (electronic) 1335 0.65 -2.48 5.46 -1.98 0 0 0

FL 2 (electronic) 1172 0.54 -1.6 3.58 -0.98 0.79 -0.16 0.37

Electronic Dimmer 62 0.63 -0.16 1.77 -0.61 0 0 0

FL Dimmer 157 0.78 -0.48 1.89 -0.41 12.21 -18.38 7.17

High Pressure Na Light 341 0.73 0.98 -0.03 0.05 29.84 -45.26 16.42

Office Equipment 1 1020 0.67 0.34 -0.32 0.98 0 0 0

Office Equipment 2 800 0.67 0.08 0.07 0.85 0 0 0

Microwave Oven 1361 0.83 -2.78 6.06 -2.28 0 0 0

Blower / Heater 1350 0.5 0.98 0.02 0 0.69 0.25 0.06

Baseboard Heater 1200 0 1 0 0 0 0 0

Voltage Sag Studies

Voltage sag is a short term dip in voltage, often caused by transient events such as the starting of

large motors. There is a large body of work that has investigated how domestic loads are affected

by these events. Although it is clearly different from permanent voltage tests, insight can still be

gained from these tests.

Work in the literature looking at the sensitivity of ASDs or variable frequency drives (VFDs)

to voltage sags was performed in [93]. Programmable three phase supplies were used to supply

an induction machine driving a constant torque type load at rated machine power. Results from

balanced 3 phase voltage sag tests are presented in Figure 3.18a.

Unlike the static voltage tests, voltage sag tests take account of both the duration of the applied

sag and the depth of sag. The above Figure (3.18a) shows the normal operational area, shown

above and to the left of the curves. There is a wide variation among the 5 ASDs tested with

a drop-out voltage range from 0.73 to 0.9 of the nominal voltage. For equating these to static

3.4. Voltage Tolerance - Literature 88

Table 3.30: Sensitivity Results from [92]

DeviceS0 Vmin Active Power (P) Reactive Power (Q)

(VA) (pu) Z I P Z I P

Dishwasher 600 0 0.99 0 0 0 0 0

Dryer 4900 0.56 1.02 0 0 0.1 0 0

Oven 3050 0 0.99 0 0 0 0 0

Range Cooker 4100 0 0.97 0 0 0 0 0

FAN 187 0 0.45 0.57 -0.04 -0.03 0.34 -0.02

Halogen 100 0 0.66 0.39 0 0 0 0

Incandescent 100 0 0.64 0.4 0 0 0 0

CFL 19 19 0.14 -0.42 1.5 -0.06 0.66 -1.16 0.06

CFL 23 23 0.23 -0.28 1.35 -0.05 0.58 -1.11 0.05

CFL 20 18 0.17 -0.3 1.36 -0.05 0.6 -1.08 0.04

Fluorescent 32W 56 0.12 0.35 0.72 -0.04 0.28 -0.9 0.03

Fluorescent 40W 50 0.1 0.34 0.71 -0.03 0.2 -0.76 0.02

CRT 120 0.6 0 0 1 0 0 0.15

LCD 120 0.6 0 0 1 0 0 0.15

Clothes Washer 120N.A

Refrigerator 120

(a) Sensitivity of ASD [93] (b) Sensitivity of PC’s [94]

Figure 3.18: Voltage Sag Results from [93] & [94]

performance characteristics in 5.1, the maximum length of time recorded should be considered the

most accurate, which in the above case is 500ms.

In [94] the effect of voltage sag upon personal computers was tested, where the PCs were also

monitored for hard disk read / write lock-up or OS lock-up as well as monitoring that the device

was still powered. None of the PC failed this testing with a supply voltage greater than 65% of

the nominal voltage, for sag durations up to 500ms.

3.4. Voltage Tolerance - Literature 89

Reference [95] tested PCs, lamps, and contactors with voltage sags. The PCs and lamps were

found to operate with voltage sags resulting in voltages of 0.3 nominal for up to 500ms. Both

computers tested only failed when the voltage fell below 0.5 of nominal voltage. The florescent

lights were seen to extinguish only when voltage fell below 0.3 of the nominal supply voltage.

Reference [96] tested a range of consumer products with sags up to 1000 cycles in length or 20

seconds with the 230V 50Hz nominal electrical supply as used in Australia. In total three TVs

(plasma, LCD, CRT), a PC, and LCD monitor, two DVD players, a clock radio, a microwave,

two printers (laser and ink-jet combo), a portable hard disk, a CFL, two air conditioners (inverter

driven and portable without inverter) and a refrigerator were tested. Devices were monitored for

functionality using a range of observational and recorded methods.

(a) Electronic Appliances (b) IT Equipment

(c) Constant Torque Motors (d) All Goods

Figure 3.19: Voltage Sag Results from [96] for specific types of Load

From the Figure 3.19 none of the devices failed when the supply voltage was above 0.6 of

nominal. With 0.6 of nominal supply voltage the test maximum length was 100 cycles. At 1000

cycles the test voltage recorded with a minimum supply voltage of 0.8. With a voltage of 0.6

nominal, only the microwave and both types of air conditioner failed, indicating they would have a

steady state drop off voltage between 0.6 and 0.8 of the nominal voltage. It is seen that the ACU

performance to sag was almost identical regardless of the connection of an inverter between it and

the supply or not.

3.4. Voltage Tolerance - Literature 90

Results from the minimum working voltage of the loads in these studies [93–96] and shown in

Table 3.31:

Table 3.31: Collected Results from Voltage Sag Results

Device Vmin (pu) Time (s) Device Vmin (pu) Time (s)

ASD 1 0.73 0.5 PC 6 0.58 0.5

ASD 2 0.78 0.5 Laser Printer 0.2 20

ASD 3 0.77 0.5 PC 0.4 20

ASD 4 0.9 0.5 Microwave � 0.80 20

ASD 5 0.91 0.5 All in one (MFD) 0.1 20

PC 1 0.47 0.5 External HDD � 0.1 20

PC 2 0.63 0.5 Inverter ACU � 0.80 20

PC 3 0.62 0.5 Portable ACU � 0.80 20

PC 4 0.59 0.5 Refrigerator 0.4 20

PC 5 0.6 0.5

The high drop out voltage Vmin of the ASD 4 & 5 is due to its industrial design and three

phase protection circuitry where contactors open, these devices are however not common (nor are

three phase supplies) in domestic use.

Overview of Findings from the Literature

Regarding the operational voltage range of devices, the literature [86–91] suggests there are few

devices that will malfunction with a voltage down to 80% of nominal (exceptions are two of the

3 phase ADS tested in [93] that tripped with 90% of nominal supply voltage, a microwave and a

magnetically ballasted CFL at tripped with 83% of the nominal supply voltage). All of the other

devices continued to function at 80% of the nominal supply voltage, with many operating down to

much lower than rated voltage. At the recommended minimum voltage (0.85pu) [38], 2 out of the 5

three-phase ASDs failed. However these loads are not common in domestic settings so the impact

on domestic customers of this proposed lower voltage band (0.85pu) can be concluded small.

Regarding the voltage sensitivity of devices, from the literature it has been show how the load

responds to a change in voltage; that is how its P and Q characteristics are described following

changes to the nominal supply voltage. Different methods for presenting these characteristics are

used, and as these results inevitably use a form of curve fitting, the processes of curve fitting

applied to the measured results will also affect the curve fitted results.

The IEEE documents on this subject are found in [97–99] from the IEEE transactions on power

systems released between 1993-1995. In [97] a bibliography referencing an additional 118 academic

papers with results and findings similar to those mentioned previously, are presented. Suggested

methods for representing different areas load composition in simulation studies for load flow and

3.5. Summary of Voltage Tolerates of Domestic Loads 91

stability studies are presented in [98]. Reference [99] lists the IEEE standards that should be used

when modelling loads in power systems simulations. These standards state that IM should usually

be modelled so to include transients; though a static representation can be used depending on

the type of network analysis being carried out. Results will be unsatisfactory if using a static

representation of the IM in transient network studies.

3.5 Summary of Voltage Tolerates of Domestic Loads

Using all of the relevant simulation, experimental and literature review based results, a list was

produced so it can be applied to the CREST load model simulator [49], as is further described in

2.3. The averaged results for the ZIP parameters is presented below in Table 3.32, using a least

squared fits for a range of equipment, in total 55 devices, are given in Table 3.32.

Table 3.32: Averaged PQ Sensitivity Results for Domestic Loads

DeviceVmin Power Reactive Power

(pu) Z I P Z I P

Incandescent - 0.53 0.51 -0.05 0 0 0

Halogen - 0.63 0.37 0 0 0 0

CFL 0.29 -0.11 1.1 0 -0.67 1.58 0.09

FL 0.39 -0.35 1.86 -0.51 1.86 -1.88 1.02

Heating - 1 0 0 0 0 0

Motor (CT) 0.59 0.58 -0.2 0.62 1.7 -1.19 0.49

Motor (FAN) 0.6 0.96 -0.89 0.94 1.2 -0.58 0.38

Motor (ASD) 0.77 1.81 -1.62 0.8 -0.06 1.65 -0.59

E Supply (PFC) 0.54 0 0 1 0 0 0

E Supply 0.54 -0.07 0.27 0.8 1.3 -1.85 1.54

Minimum voltages are taken as an average of all collected results. The surprising results come

from the ASD motors, where the voltage sensitivity was found to be a constant impedance type

load and with a relativity high minimum supply voltage (0.77pu). A constant volts per hertz (V/f)

ASD control scheme will lower the speed of a motor (ω) in order to maintain rated toque (T ) if

the DC bus voltage falls, hence without an active front end the supply voltage will be directly

proportional to the mechanical output power (Pmech � Tω). However even this does not fully

explain the PQ sensitivity, this may be due to undervotlage protections schemes implemented

within the controller itself.

Overall, assessing results from [86–95, 100, 101] shows of the 63 domestic devices tested, and

where the minimum operating voltage was recorded (neglecting the ASDs). Only three loads

(microwave, magnetic ballast CFL, and heat pump) failed to operate with a supply voltage of 0.8

nominal. With 0.85 nominal supply voltages only one heat pump didn’t operate. This gives a

3.5. Summary of Voltage Tolerates of Domestic Loads 92

good indication the vast majority (above 98%) of domestic loads in the UK will operate with the

recommended minimum voltage of 0.85pu nominal voltage.

As LV networks are often voltage constrained by voltage regulatory levels by simply to removing

or relaxing these tolerances capacity can be increased.

This voltage tolerance, and its ability to provide increased capacity to the LV network, is

also crucially dependant of the voltage at the secondary of the LV transformer. As such, this

voltage band needs be applied in conjunction with voltage settings on the secondary side of the

LV transformer. This still allows flexibility to the DNOs, given the range of these new voltage

tolerances is sufficiently wide to allow for a range of voltages on the transformer secondary. As

the maximum voltage is unchanged from current levels the existing practice commonly employed

by DNOs of boosting the secondary side to near its regulatory maximum should not be continued,

as this will limit the amount of DG that can be incorporated. The lowering of the minimum

permissible voltage on the system has in effect removed the need for the DNOs to do this anyhow.

The primary barrier to increased voltage tolerances is how the loads connected to the LV

network will respond to these new voltage levels. Looking at domestic loads it is shown in this

chapter, by using results from the literature and results presented within, that domestic products

exhibit a greater operational sensitivity to elevated voltage levels than they do with reduced voltage

levels. Within the voltage bounds recommended, the loads are shown to function without failure

or malfunction across this new voltage band in over 98% of the cases shown. The power demand

characteristics of each load type are also assessed and aggregated from a range of sources in the

literature. This allows load flow studies to genuinely show how much new load can be added to a

deregulated LV network.

Given all the above, it can be stated that widening of voltage tolerances along with careful

selection of secondary substation transformer tap setting has the ability to increase the capacity

for loading and generation within the LV network. The network capacity limitations now being

tied to thermal limits of the networks components (e.g. UG cables, transformers). If yet further

network capacity was required, then elevated AC distribution schemes might be considered. How-

ever, results presented show that even slightly elevated AC would be problematic and potentially

damaging to consumer products.Hence widespread proliferation of point of load regulation devices

would be needed to ensure the loads operate as normal.

Thus the final suggested voltage range, whereby the upper limit is maintained at 1.1 pu to avoid

damage to loads, and the lower voltage limit of 0.85 pu has been chosen to maintain the correct op-

eration of the great majority of domestic loads, has been justified via experimentation, simulation,

and a literature review. Crucially, these changed could be implemented without disruption to the

distribution network or significant expenditure, whist still increasing hosting capacity of LCTs.

Chapter 4

Methods of Analysis in LV

Networks

In this chapter the methods used for the analysis of LV networks are presented. The methodology

outlined is subsequently used in achieving the results presented in Chapters 5 and 6.

Initially, in section 4.1, types of load flow that are suited to LV simulation are presented and

briefly reviewed. Then in section 4.2, an overview of all the test networks for which results are

later presented is given, along with network topology metrics that are useful in aiding to predict

network performance characteristics, for example indicating most likely network constraints. Next

in section 4.3, a Monte Carlo procedure for statically assessing a given network topology under a

range of conditions is presented. The Monte Carlo based approach to analysis of LV networks is

popular in the literature [102–105] as the operating conditions of a LV network (eg. loading) at a

particular time are not deterministic. Finally some of the values and assumptions used in assessing

the financial benefits of increasing hosting capacity are presented.

4.1 Load Flow

The load flow studies are preformed in Matlab Simulink using the SimPowerSystems library, and

with load flow functions written with MATLAB. This software is built upon easily handling matrix

maths operations and is high level interpreted language which allows rapid deployment of code

without requiring extensive programming experience as is the case with other lower level languages.

This is not without drawbacks however as compared to well written code in an interpreted language,

MATLAB can be slower. Nonetheless, weighing up these and considering that it includes powerful

graphical and data analysis functionality in one software suite it was deemed most appropriate for

this work.

93

4.1. Load Flow 94

SimPowerSystems analysis for Distribution Networks

For small networks (�1000 nodes), networks can be readily constructed in Simulink software from

network topology data, be this in .csv, .xls, or another file format. Although a time domain envi-

ronment, AC steady state load flow can be performed within Simulink using the phasor simulation

method available. The advantage of the GUI based software is that the visual representation of

the network, is the block based, and this modelling environment facilitates rapid testing or modi-

fication of the network, PEDs, and controllers via simple reconfiguration of the model blocks and

parameters, added the large range of already available library blocks. Additionally, with only mi-

nor modification system fault, or stability analysis can be performed. The obvious disadvantages

are the compilation time involved in producing an executable file that describes the system and

the additional computational burden of the GUI itself, these becoming increasingly important as

the network size grows.

Load Flow Specialised for Distribution Networks

For large networks (�1000 nodes) the load flow approach outlined in [106] (termed the direct

approach) is used as it has robust convergence characteristics, is fast, and takes advances of the

radial structure of the LV networks. Compared to the Gauss Z-matrix method [107] the direct

approach is notably faster [106]. Traditional transmission based power flow solutions such as the

Newton-Raphson or Gauss-Seidel approaches are not suited for distribution networks due to the

largely radial structure, low X/R ratio of the system, and its unbalanced operation, which all result

in slow or non convergence of these algorithms [108].

In the “direct approach” the first step in the direct load flow process is to solve the nodal

current injections:

Iik �Pk � jQk

V ik

(4.1)

Then 2 matrices are required to solve the load flow problem, the bus injection, branch current

matrix (BIBC) and the branch current, bus voltage matrix (BCBV). The BIBC matrix relates the

nodal currents (I) to the branch currents (J):

�J��

�BIBC

� �I�

(4.2)

and is formed exclusively of ones and zeros, whereby a one at position �n, k� in the matrix means

that current in branch n is dependant upon the current injection at node k.

The BCBV matrix relates the change in nodal voltage relative to the source (ΔV ), to the

4.1. Load Flow 95

branch currents (J):

�ΔV

��

�BCBV

� �J�

(4.3)

The BCBV matrix is formed of the product of branch impedances (Z) in the network and a

connectivity matrix which contains ones and zeros, whereby a one is placed at position �k, n� if

node k is connected downstream of branch n.

By combining both the BCBI and BCBV matrices into the DLF matrix we can directly relate

the nodal current injections (I) to the change in voltage at a node (ΔV ) :

�ΔV

��

�BCBV

� �BCBI

� �I�

(4.4)

��DLF

� �I�

Thus to solve the load flow, the iterative process involved involves 3 steps:

� Find all nodal current injections Iik, using (4.1) and initial or calculated voltages V ik

� Find the change in voltage ΔV ik , using the current injections Iik and (4.4)

� Update the nodal voltages with, V ik�1 � V 0 �ΔV i

k�1

where k is the node number, i is the iteration count, V 0 is the swing bus voltage. The solution

has converged if:

�V i�1k � V i

k � � ε, �k

where ε is the acceptable tolerance value. Example code is included in Appendix C, where the load

flow algorithm is implemented in under 30 lines of MATLAB code. A simple example to illustrate

the direct load flow method is presented for the following network:

V1

V2

V3 V4

J1

J2

J3

I2

I2 I4

Figure 4.1: Full Schematic of Original UK Generic Network

The BCBI, BCBV and DLF matrices for this network are:

4.1. Load Flow 96

�BCBV

��

�����

1 0 0

0 1 1

0 0 1

����� ,

�BCBV

��

�����

z1 0 0

0 z2 0

0 z2 z3

����� ,

�DLF

��

�����

z1 0 0

0 z2 z2

0 z2 z2+z3

�����

As these matrices do not change, once formed, the iterative scheme outline above can be directly

implemented for any network operating point that does not change the layout of the network.

An example of the voltage on one phase and at one node in the network, is shown in Figure 4.2

over a 24 hour period. Following a load flow we typically generate many thousands of these plots

for the three phase line currents and nodal voltages typically generating many Gb of results when

combined with Monte Carlo methods.

To process the data into compact and presentable results each of the voltage and current plots

are analyses for breaches of relevant regulations, for example the voltage unbalance at each three

phase node is computed. Then results from the many Monte Carlo trails are presented typically in

the form of box plots (as shown frequently in chapters 5 and 6). Thus each of the box plots shown

is actually a snapshot into many thousands of the plots shown in 4.2.

The networks themselves are constructed from detailed net-list type information that at a min-

imum provides: the construction of the lines, that is the type of cable or transformer parameters,

the position of the nodes which is used to infer the length of line sections and the type of each

node, that being whether for example it is a load, junction, or other component of a network. Each

of these databases is thus analysed suitably with missing data inferred, then process and sorted

before then being used to construct either a Simulink model (programatically using MATLAB

commands) or construct the connectively matrices mentioned previously in this section.

4 8 12 16 20 240.99

1

1.01

1.02

1.03

1.04

1.05

1.06

Vol

tage

(pu)

Time

Transfromer Primary Votlage

Figure 4.2: A typical Single Phase Nodal Voltage from a 24 load flow

4.2. Test Networks & Metrics 97

4.2 Test Networks & Metrics

In this section new network metrics are developed that aim to give a compact indication of network

properties, then the topological information regarding the test networks that are used in subsequent

chapters are presented. For the plots and figures within this section that show the test network

metrics the x-axis which is termed branch number is a monotonously increasing tag for each branch

resulting from sorting the branches themselves by their metric.

Network Metrics

The metrics used to characterise the LV networks are:

� Total Feeder Length (service and main)

� Customer Path Length (CPL)

� Customer Path Impedance (CPZ)

� Diversified Line Ratings Per Customer Served (D-LRCS)

The total feeder length is simply a summation of the length of each of the n network branch

lengths (lk):

Length �n�

k�1

lk, N � �1, ..., n� (4.5)

where N is the set of all branches in the network.

The customer path length (CPL) is defined as the length of the m network branches that

connect the supply point to the customers PCC:

CPL ��

lk�M

lk, M � N (4.6)

Similarly for the customer path impedance (CPZ), each branch in the network has a know

impedance (zk), thus the CPZ is given by:

CPZ ��

zk�M

zk, M � N (4.7)

The non-diversified line rating per customer served (LRCS) is given by :

LRCS �1

Rk

xi�C

f�xi, Dk�, �k : Dk � C, C � �1, ..., c� (4.8)

where C is the set of all the customers (there being c customers in total) connected to the network,

and Dk is the set of customers connected downstream of branch k, where the rating of this branch

4.2. Test Networks & Metrics 98

is given by Rk. The second term (�

xi�Cf�xi, Dk�) in (4.8) is a simply the number of customers

connected downstream of branch k (ie. the cardinality of set Dk), where the function f�xi, Dk� is

described by:

f�xi, Dk� �

�����1, if xi � Dk

0, otherwise.

(4.9)

If we term the number of customers connected down stream of branch k as kc,k, the diversified

line rating per customer served (D-LRCS) is:

D-LRCS � DF�kc,k� �kc,kRk

(4.10)

Where DF�kc,k� is the diversity factor (DF) associated with kc,k individual customers. DF values

are presented in the literature [23] where the DF ranged from 1 to 3.2 as the amount of customers

increased from 1 to 70.

Given that we have a total of n branches and c customers, there exists one CPL/CPR for each

of the customers and one D-LRCS value for each network branch. The lowest D-LRCS values imply

the highest loading relative to the branch rating thus the D-LRCS typically increases further from

the substation but, the absolute minimum D-LRCS value need not necessarily occur at the start of

a feeder if the line is tapered. The D-LRCS is shown in Figure 4.3 for the main LV feeder segments

of the generic UK network [109].

0 5 10 15 20 25 30Branch Number

0

10

20

30

40

LRCS(A

)

DiversifiedNon-diversifed

Figure 4.3: Ratings per customer severed for branches in the Generic UK Network

As the D-LRCS is essentially a branch parameter much like its resistance or length, customer

path type metrics as previously shown for CPZ and CPL can also be calculated for the D-LRCS.

Generic UK Network

The generic UK test network was first presented in 2003 [109], since then it has been utilised in

numerous studies within the literature [110], this makes it a valuable network to include for com-

4.2. Test Networks & Metrics 99

parative purposes. Furthermore the network was approved by DNOs in the UK as representative

of a “typical” network.

The original network layout is shown in Figure 4.4, where the primary substation is comprised

of two parallel 7.5/15MVA transformers with a PU impedance of 18% on a 15MVA base, an X/R

ratio of 15, and taps with 1.67% resolution, which have range of � 20%.

Figure 4.4: Layout of the original UK Generic Network

As the focus of this work is on LV networks, the generic UK networks is modified as in [111],

such that each feeders supplies 96 single phase customers, each connected by 30m of service cable.

The loads are distributed in groups of 3 evenly along the length of the main 300m feeder (ie. 9.4m

intervals). Thus, there are 32 main feeder sections and, as in the original network, the first 150m

of the network is constructed of 150mm2 CSA cable which then tappers to 95mm2 CSA for the

final 150m. The layout of this modified section of the UK generic network is shown in Figure 4.5

26 Segments

Figure 4.5: Layout of the detailed UK Generic Network

The network topology metrics for the detailed LV section of this network are given in Table 4.1

Table 4.1: Generic UK Network Topology Metrics

Parameter Value Parameter Value

Total Length 3180 m Max CPL 330 m

Service Length 2880 m Mean CPL 185 m

Feeder Length 300 m Max CPR 141 mΩ

No. of Loads 96 Mean CPR 83 mΩ

This network is characterised by a very large proportion of single phase service cables, relatively

high mean CPL, and CPR, and a minimum D-LRCS of 10A.

4.2. Test Networks & Metrics 100

Real UK Network

The real test network here is a LV system based in London, for this geographic information system

(GIS) data is available for the nodes so they can be visually seen to correspond to maps, as in

Figure 4.6

NodesLoadsTransformerLV Feeder

Figure 4.6: Layout of the real UK Network with street map overlay

The network topology metrics for this network are given in Table 4.2

Table 4.2: Real LV Network Topology Metrics

Parameter Value Parameter Value

Total Length 3714 m Max CPL 351 m

Service Length 2665 m Mean CPL 175 m

Feeder Length 1049 m Max CPR 117 mΩ

No. of Loads 192 Mean CPR 69 mΩ

This network is characterised by a medium proportion of single phase service cables, a medium

mean CPL, and low CPR,with a minimum D-LRCS of 8A.

0 10 20 30 40 50 60 70 80 90Branch Number

0

20

40

60

80

100

LRCS(A

)

DiversifiedNon-diversifed

Figure 4.7: Ratings per customer severed for main branches in the Real UK Network

4.2. Test Networks & Metrics 101

IEEE European Network

The IEEE power and energy society (PES) recently published data for a “European Low Voltage

Test Feeder.” The other networks published by the IEEE PES such as the 13, 34 and 123 bus feeders

have become a de-facto standard for comparison of load flow methods [112], network integration of

novel grid technologies [113], state-estimation [114], optimal power flow [115] problems and many

more [116,117]. The European LV Network is shown in Figure 4.8.

NodesLoadsTransformerLV Feeder

Figure 4.8: Layout of the IEEE European Network

The network topology metrics for this network are given in Table 4.3

Table 4.3: IEEE European Network Topology Metrics

Parameter Value Parameter Value

Total Length 1431 m Max CPL 293.8 m

Service Length 224 m Mean CPL 171.3 m

Feeder Length 1208 m Max CPR 127 mΩ

No. of Loads 55 Mean CPR 77.1 mΩ

This network is characterised by a small proportion of service cables, normal mean CPL, and

CPR values with a minimum D-LRCS of 8A.

0 100 200 300 400 500 600Branch Number

0

50

100

150

LRCS(A

)

DiversifiedNon-diversifed

Figure 4.9: Ratings per customer severed for main branches in the IEEE Network

4.3. Monte Carlo Simulation 102

4.3 Monte Carlo Simulation

Within the LV distribution network the load profile cannot be given deterministically for any time

period. However at higher voltages, loads are aggregated and the network loading tends to more

closely follow a set of know load profile patterns. The same cannot be said when the aggregation

of loads remains low and large peaks in demand from single customers can be clearly seen at the

secondary substation. Further-more as the uptake of LCTs at particular nodes in the network is

not known in advance, but can be probabilistic determined for a given node from the known (or

herein considered) LCT penetration levels.

The secondary substation primary side voltage was measured in [70] for a range of substation

sites and timestamps. By fitting these results to a Weibull distribution with a scale value of 1.06

and a shape value of 61.3 we have the histogram for 10,000 samples as shown in Figure 4.10

Figure 4.10: Histogram of Substation Voltages

Additionally the phasing information of the particular customers, that is what phase the single

phase service cable branch connects to on the main feeder, is not always known by the DNOs [118].

Hence there cannot be any certainty for some data in the LV networks, specifically:

� Instantaneous demand

� Substation voltage

� Customer phasing

� Location of LCTs

To account for this Monte Carlo simulation methods are employed, such that a statistical

insight can be gained into network variables such as nodal voltages, branch currents and network

losses [119]. This is implemented by assigning, randomly, or with a defined probability, values

to the above variables. In the case of the instantaneous power demand, a random profile from a

database of 7,500 is assigned to each node. The secondary substation voltage is then defined along

with the phasing of each load and the associated LCT uses a Bernoulli distribution where the p

value is defined for various scenarios of LCT uptake.

4.4. Economic Assessment 103

4.4 Economic Assessment

As network reinforcement is the traditional solution to any network hosting constraints it needs

to be compared to in assessing the benefits of any alternative strategies. The cost of laying under-

ground (UG) cables in urban areas is particularly high largely due to excavation costs incurred,

the total costs for laying UG cable are given in Table 4.4 .

Table 4.4: Cost of UG Cable1 (�/m)

VoltageCSA Urban Rural

(mm2) Min Max Avg Min Max Avg

LV � 95 90 223 157 43 59 51

LV 95-185 100 360 230 55 73 64

LV � 185 105 380 243 58 82 70

HV - 111 414 262 70 101 86

These figures are for new customer connections [120] and checked against [121] where the cost

for laying 1km of UG cable across the DNO’s (excluding UKPN in the South East) ranges from

�55/m to �382/m, closely matching the minimum and maximum values of �43/m and �380/m in

Table 4.4. Other data [122] presented lists a maximum HV rural cable insulation cost at �48/m,

well below the minimum of �70/m in Table 4.4. Clearly, there can be much variation in the costs

associated with UG cable reinforcement, some of the potential reasons for this are given in [120]

as:

� the length of jointing spans (e.g. frequency of branching or service connections)

� the type of ground being excavated (e.g earth, roads, finished surfaces)

Due to the lack of excavation costs, OH line is substantially cheaper than cables, however it is

not common in urban and built up areas. Nonetheless, the cost of OH lines are listed in the Table

4.5.

Table 4.5: Cost of OH lines2 (�/m)

Voltage Min Max Avg

LV 23 66 45

HV 35 109 72

The final cost involved in the network reinforcement that is considered here is that incurred

from the substations, with figures given in the Table 4.6.

1Cost for laying 10m of cable with an additional 90m of extension.2Costs for 45m of LV OH line (60m for HV) with 2 poles and nine 45m spans with 1 extra pole (60m for HV)

4.4. Economic Assessment 104

Table 4.6: Cost of Full Substations (�1000s)

Voltage Type Rating (kVA) Min Max Avg

HV/LV Pole �100 8 20 14

HV/LV Pole 100-200 11 22 17

HV/LV Pad �200 21 34 27

HV/LV Ground 200-315 20 44 32

HV/LV Ground 315-500 23 50 36

HV/LV Ground 500-800 26 55 40

HV/LV Ground 800-1000 30 57 44

HV/LV Ground �1000 37 119 78

EHV/HV Indoor (x1) - 1208 1575 1391

EHV/HV Indoor (x2) - 1827 2730 2279

EHV/HV Outdoor (x1) - 1155 1470 1313

EHV/HV Outdoor (x2) - 1785 2415 2100

It must be noted the above table is for new substations and not upgrades to existing ones.

Thus the costs listed include the switch gear, fuses, RMU, breakers, and all other substation

equipment. Relative to installation of feeders and particularly UG cables the variance in the costs

for substations ae much reduced. This comes as a result of most DNOs in the UK purchasing a

limited range of distinct transformers in higher quantities

The uptake of power electronic devices by DNOs will only progress if a clear business case

for their use can be made. Typically this will involve a comparison of power electronics and the

alternative solutions relevant to the specific problem faced by the DNO (e.g. network reinforcement

with higher capacity cables or transformers or with additional substations). To facilitate this

comparison, particularly when the power electronics is considered for investment deferral or the

operational lifetime of power electronics and alternative solutions differ greatly, the Equivalent

Annual Costs (EAC) of a distribution asset is a useful measure in that it allows a direct comparison

of two investments with different life cycles:

CEA �Kf

ATl,r� �EeKe �Km� (4.11)

where:

CEA is the equivalent annual cost

Kf is the initial investment cost

Km is the cost of maintenance

Ke is the electrical losses

Ee is the cost of electrical losses

ATl,r is the annuity factor

4.4. Economic Assessment 105

the annuity factor, ATl,r, is a function of the device lifetime, Tl, and the cost of capital, r, given

by:

ATl,r �

1� 1�1�r�Tl

r(4.12)

As an example, suppose it is required to alleviate voltage problems resulting from DG. Given two

solutions, namely PEDs for voltage regulation which will defer network investment for a period

between 8 and 12 years, where the deferral period is assumed to be uniformly distributed, and

network reinforcement which consists of upgrading 200m of the line, which will have an operational

life between 40 and 50 years during which time further upgrades are not envisaged. If the rate of

capital is 5.6%, with initial project costs of �25,000 and �10,000 [120] for the reinforcement and

PED respectively, where the PED incurs further annual costs of �350, the EACs are as shown in

Figure 4.11.

Power Electronics Netwrok ReinfocementEqui

vale

nt A

nual

Cos

ts [£

]

1400

1500

1600

1700

1800

Figure 4.11: EAC of Network Investment Options with uncertain project lifetimes.

Despite similar median costs for both projects, the uncertainty over the deferral period (or

PED lifetime if considered as reinforcement avoidance) of the power electronics is evident when

compared to the network reinforcement solution, which is a low risk solution as is evident from

Figure 4.11. The challenge for PEDs in the distribution network are hence economically motivated

and are driven by: the operating (or deferral) time which will be directly related to its efficacy,

PED costs (both initially and during the assets operation), efficiency, and power density which is

indicative of PED size and thus related to installation costs. All of these can be directly related

to the factors included in equation (4.11).

Chapter 5

Analysis of LV Networks with

Wider Voltage Tolerances

Whilst the use power electronic devices, and other technologies or schemes such DSM, can im-

prove voltage regulation at LV, deregulation can also be considered a “passive” solution to voltage

constraints, varying levels of de-regulation are compared herein, namely:

� EU limits (�%10)

� Load operation limits [38] (+%10,-15%)

� No regulation

The first level of de-regulation “EU limits” represents the voltage tolerance across much of

Europe and is defined in [6]. The second limit was that which was justified in Chapter 3 of this

work, where-by voltage tolerance are increased to the maximum permissible range, prior to frequent

load malfunctions. The final level of deregulation, that is no regulation will clearly need some form

of local regulation to ensure the loads operate correctly. Therefore this will be considered in

conjunction with 100% proliferation of point of load regulation (PoL) devices.

The distinct LCT scenarios for which the befits of de-regulation upon network hosting con-

straints are considered are presented in Table 6.1.

Table 5.1: De-regulation LCT Proliferation Scenarios (%)

PV EV HP

Low - 13 -

Mid 30 33 30

High 60 71 80

106

5.1. Feeder Relief Strategies 107

Results from this chapter were published in the Top and Tail report “Assessment of Feeder

relief versus tolerance band” [123].

5.1 Feeder Relief Strategies

Figure 5.1 presents a tree diagram of the approaches taken to increase capacity within this chapter

along-side other solutions such as network reinforcement. Many further relief strategies can be

found in the literature covering, but not limited to, areas such as: power electronics [72, 124, 125],

reactive power control [126, 127], demand response [44], improved network operation [128, 129],

hybrid reinforcement [130] and dynamic rating methods [41]. All of these works offer alternatives

feeder relief strategies.

Increase NetworkCapacity

Relax Voltage Tolerances

Upgrade the Network

Regulation perDevice

Control Voltage Drop

Regualtion per Household

Reactive Power Control

Assess impact and range of voltage tolerance available

without extra regulation

Install more cables or no. of LV transformers

Control Power Flow

Figure 5.1: Methods to Increase Capacity for Voltage constrained Networks

5.2 Considered Voltage Tolerance Bands

It is known uptake of LCTs stresses voltage limits [130–132] and from [38] a hard limit on domestic

LV voltage tolerances is given as 230V +10,-15%, based on the requirement to maintaining the load

operation. As such voltage tolerances up to +10,-15% could be considered to alleviate network

voltage problems without any need of PoL regulation.

EU Regulations limit

Due to different nominal operating voltages across Europe before harmonisation to a nominal

operating voltage of 230V, where the UK used 240V and much of continental Europe used 220V

[133], the UK enforces a -6% lower bound and a +10% upper bound on voltage levels [39, 134].

It has been considered, but as yet not implemented, to change the voltage band to �10% [133].

5.2. Considered Voltage Tolerance Bands 108

This change would harmonise not only the nominal voltage but also the voltage tolerance band in

Europe, in-line with standard EN50160 [6].

As such the first considered (and smallest) change to the tolerance bands is a reduction in the

lower permissible voltage from -6% to -10%. As the upper limit remains unchanged at +10% the

range of voltage tolerance (VΔ) defined as Vmax - Vmin has been increased from 16% to 20%.

Load operation limit

In Chapter 3 an investigation into the effect of wider voltage tolerances on domestic goods was

presented. Salient results regarding voltage limits for load operation were:

� Domestic good are most sensitive to high voltages, with much equipment functional at very

low voltages (�0.7pu)

� A lower voltage range of -15% allows over 98% of goods to function correctly

� A higher voltage range (�10%) is not appropriate

For these reasons a voltage range of +10,-15% was recommend as the maximum un-disruptive

limit, so this limit will also be considered (VΔ=25%). This limit will be refereed to as “TT” herein.

Point of Load Regulation

It is feasible to remove the requirements upon voltage levels in LV networks if suitable point of

load regulation (PoL) is added (and with 100% proliferation). Two distinct locations within the

final consumers premises are possible:

� Bulk regulation at the PCC

� Regulation of each device

The difference between the two schemes will be the size of the converter required and the voltage

profile on the internal wiring. That is, with a deregulated supply and device by device regulation,

the internal wiring will also be subject to the deregulated network voltages. In the same scenario

but considering bulk regulation, the internal wiring will be subject to only the regulated output

voltage from the bulk PoL converter.

For the purpose of this work no distinction will be made between the two schemes. In modelling

PoL solutions (at either bulk or device locations) the load profiles will be considered to be entirely

constant power loads. This assumption is valid if the converter is able to regulate the output voltage

to the nominal system voltage. Thus the bracketed RHS terms in (2.52) and (2.53) become one and

the device consumes the nominal power as specified by the original load profile. Additionally, this

means thermally controlled loads will draw their specified power, regardless of their PQ voltage

5.2. Considered Voltage Tolerance Bands 109

ACAC

ACAC

ACAC

ACAC

ACAC

ACAC

Bulk Regulation at PCC

Regulation at Device

Figure 5.2: Application of PoL to Regulate Systems Voltages

sensitivity, at all times so the time of use for these device will not change, as it did with the

unregulated voltage.

A key point to note regarding PoL regulation, is that LV cables are rated for 0.6/1kV operation,

this means substantially higher voltages can, potentially, be used without the need to replace

existing cables. Additionally, PoL regulation will be a feasible solution to provide a flexible network

if coupled with LV OLTC or Power Electronic Substations (PES). In the latter case the possibility

of LVDC distribution also raised [135].

The preceding chapters within this report have outlined the problems caused by connection of

various LCTs for LV networks (chapter ??), then detailed how the results presented in this chapter

have been achieved. Namely, how the customers and LCTs are modelled (chapter ??) and well

as the network topology and standard plant and ratings from the UK DNOs (chapter 2.1). Here

we give first details of the LCT scenarios considered, and then metrics used to assess network

performance, before presenting results.

5.3. Feeder Relief with Voltage Deregulation 110

5.3 Feeder Relief with Voltage Deregulation

In this section the benefits of deregulation are explored, with results for the generic network given

first, after which results for the real UK network are given. It must be noted this chapter does not

explore the possibility of using elevated AC voltage alongside PoL or even hybrid DC distribution

networks alongside PoL as the cost of large scale PoL installation is prohibitive and its inclusion

is primarily to severe as a comparison to the de-regulation scenarios.

5.3.1 Generic LV Network

Zero LCT Scenario

Without consideration of any LCTs the network operates within all limits considered. This simply

serves to show without LCT connection to the network it operates without any of the problems or

constraints mentioned in section 1.3.

PV Generation Scenarios

In the case of PV installations it is over voltage and/or thermal problems we would expect to

encounter [131]. Hence, results presented in this section are shown for occurrences of over voltages

and breached thermal limits. Looking at Figure 5.3 it is seen that the introduction of PoL to the

network increases the occurrence of over voltage problems. This can be explained by the fact that

the PoL regulation device is modelled as a constant voltage source for all of the connected domestic

goods, hence they now act of constant power loads. Devices such as resistive based elements used

for space heating, hot water and cooking will no longer consume increased power as the voltage

rises. At the times of peak generation the load with PoL draws a reduced current from the source,

and the voltage rise from DG is consequently higher.

Its must be noted however that with full use of PoL regulation the voltage limits on the feeder

need only be such that insulation breakdown (typically 1kV line to line) and the permissible range

of input voltages for the PoL device itself are satisfied. Assuming the PoL regulation functions

with an input voltage within 25% of nominal no voltage breaches are encountered. This is true for

all of the following figures related to voltage magnitude.

In Figure 5.3 and similar PV scenarios only PoL and the no regulation scenarios are show as

non of the other regulation levels (UK, EU, T&T) propose any change to the upper voltage limit

thus with PV and considering only over voltage issues the results for these 3 would be the same.

The effect of PoL regulation upon networks cable losses is less pronounced, with PoL regulation

acting to reduce current demand at high voltages and increase demand at low voltages (both relative

to nominal). The effect of this can be seen in Figures 5.4 and 5.5 below, which display the cable

5.3. Feeder Relief with Voltage Deregulation 111

30

40

50

No Regulation PoLReg

ulat

ory

Bre

ache

s High PV Nodal Voltage Issues

Figure 5.3: Generic Network Voltages with 60% PV

losses in the main three phase feeder (Lfeed) and the single phase service connections (Lserv)

respectively.

3040506070

No Regulation PoL

Loss

es (k

Wh/

day)

High PV Feeder Losses

Figure 5.4: Generic Network Feeder Losses with 60% PV

5

5.5

6

No Regulation PoL

Loss

es (k

Wh/

day)

High PV Service Losses

Figure 5.5: Generic Network Service Losses with 60% PV

The network hosting capacity for PV (and other DG sources) with de-regulation is unchanged

due to the proposed limits on voltage tolerances all having the same upper limit (+10%). To

increase the hosting capacity of DG the network is instead operated with a lower nominal voltage.

This is easily achieved by reducing the tap position of the off-line tap to its lowest value (-5%).

This tap setting results in substation voltages below those typically measured in the UK [70], but

is requited to accommodate DG, as such, this setting will be maintained when considering the

increased loading with HP and EV that follows.

5.3. Feeder Relief with Voltage Deregulation 112

Heat Pump Scenarios

As the loading due to HP increases, and the business as usual case whereupon the DNOs operate

high system voltages has been changed to increase hosting capacity of DG (section 5.3.1), network

under voltages are encountered with existing voltage tolerance bands as can be seen in Figure 5.6.

In this case the alternative limits on voltage regulation are shown individually in the figure as the

lower regulatory limit and thus occurrence of under voltages, has been changed. Both the EU

limits and load operation (TT) limits remove all occurrences of nodal under voltage breaches. The

same is true when PoL regulation is considered with these two de-regulation strategies.

05

10

15

UK EU TT UK/PoL EU/PoL TT/PoLReg

ulat

ory

Bre

ache

s High HP Nodal Voltages

Figure 5.6: Generic Network Voltages with 80% HP

The effect of PoL regulation upon feeder losses is shown in Figure 5.7. It is noticed that there

is a small increase in network losses where PoL is implemented. The effect is the same in both the

feeder and service cables. As before, the reason for this is that at times of low network voltages, a

portion of the domestic load is resistive in nature and thus the power demanded by this load will

decrease when PoL regulation is not considered, leading to reduced network loading, losses, and

efficiency.

0

10

20

No Regulation PoL

Bra

nch

Ove

rcur

rent

High HP Feeder Thermal Limits

Figure 5.7: Generic Network Branch Thermal Limits with 80% HP

The settings used for the PoL in all of this work are such to regulate the voltage to its nominal

value (230V).

Electric Vehicle Scenarios

As the loading due to EVs increases and lower system voltages are once again used to accommodate

DG, network under voltages with EV use become problematic as can be seen in Figure 5.8.

5.3. Feeder Relief with Voltage Deregulation 113

In this case the alternative limits on voltage regulation are shown. As the lower voltage limit

and thus occurrence of under voltages, is seen to change. Both the EU limits and TT limits reduce

the occurrences of nodal under voltage breaches to permissible levels. From this we can say that

for the generic network, voltage limits are effectively reduced by de-regulation. Furthermore since

voltage limits are encountered prior to thermal limits the network hosting capacity is increased by

de-regulation. The cost of network reinforcer required to remove voltage and current limits for the

case of high EV usage is over �64000 per feeder, with de-regulation able to defer 15% of this cost.

0

10

20

UK EU TT UK/PoL EU/PoL TT/PoLReg

ulat

ory

Bre

ache

s High EV Nodal Voltages

Figure 5.8: Generic Network Voltages with 71% EV

In all high penetration scenarios thermal limits are breached, and like in the case of a high

penetration of heat pumps, the costly network upgrades mentioned above would need to be made

for this scenario to be a viable.

0

10

20

No Regulation PoL

High EV Feeder Thermal Limits

Bra

nch

Ove

rcur

rent

Figure 5.9: Generic Network Branch Thermal Limits with 71% EV

5.3. Feeder Relief with Voltage Deregulation 114

5.3.2 Real Network

Zero LCT Scenario

Without consideration of any LCTs the network operates without any limits being breached. Some

voltages outside tolerance are seen but the frequency of these is very low. This simply serves to

show that without LCT connection to the network it operates without any of the problems and

issues mentioned in section ??.

PV Generation Scenarios

0

20

40

No Regulation PoLReg

ulat

ory

Bre

ache

s High PV Nodal Voltages

Figure 5.10: Real Network Voltages with 60% PV and -2.5% tap

There are no voltage contained limitations with HP or EV but a large number due to PV, for

this reason the tap setting on the LV substation is reduced to its lowest value of -5%. Given a

nominal supply voltage this results in a no load substation voltage of 1.03pu (237V). In this case

results show (Figure 5.11) the network is no longer voltage constrained and no over voltage issues

are seen on the feeder for a high penetration of PV.

−2

0

2x 10−16

No Regulation PoL

High PV Nodal Voltages

Reg

ulat

ory

Bre

ache

s

Figure 5.11: Real Network Voltages with 60% PV and -5% tap

Severe problems are encountered here in regards to voltage unbalance factor (VUF). As shown

(Table ??) there are two distinct limits on the VUF. It is the limit of 1.3% VUF for no more than

5 minutes in any 30 minute period that is the more frequently breached than the absolute limit

of 2%. Indeed there are no breaches of the 2% limit anywhere in the network for all the scenarios

considered. However Figure 5.12 shows that in some cases, from 101 VUF measurement over the

course of the 24 hour period of study all of the readings breach VUF limits; inclusive of even the LV

5.3. Feeder Relief with Voltage Deregulation 115

branches closest to the transformer. This is a result of the source voltage unbalance (ie unbalance

at the star connected transformer secondary).

0

50

100

No Regulation PoL

High PV Voltage Unbalance

Reg

ulat

ory

Bre

ache

s

Figure 5.12: Real Network VUF with 60% PV

Load balancing and voltage compensation can be used to mitigate against high VUF. Regulation

strategies do not help reduce VUF nor does individual voltage regulation (PoL) as can be seen

from Figure 5.12. However if PoL regulation is assumed with full de-regulation of the voltage

magnitude and VUF limits, then this is not a problem.

Heat Pump Scenarios

Considering high penetration of HP, it is noted the network is not voltage constrained even with the

lower tap settings used to accommodate PV installation. Figure 5.13 shows none of the considered

scenarios have voltage issues so voltage de-regulation doesn’t offer any increase to hosting capacity.

−2

0

2x 10−16

UK EU T&T UK/PoL EU/PoLT&T/PoL

High HP Nodal Voltages

Reg

ulat

ory

Bre

ache

s

Figure 5.13: Real Network VUF with 80% HP

For this network it is actually thermally constrained with a high penetration of HP, as can

be seen if Figure 5.14. Thermal limits are slightly exacerbated by the use of PoL regulation as

during times of low system voltage (i.e. with high loading brought on by HP installations) the PoL

regulation acts to increase the load compared to without, this in turn increases the conduction

losses in the feeder.

As was the case with PV there are severe VUF problems as shown in Figure 5.15. For example

considering a high penetration of HP and PoL regulation we see that in all of the simulations

almost all of the feeder branches breach VUF limits.

5.3. Feeder Relief with Voltage Deregulation 116

0

5

10

15

No Regulation PoL

High HP Feeder Thermal Limits

Bra

nch

Ove

rcur

rent

Figure 5.14: Real Network Branch Thermal Limits with 80% HP

0

50

100

No Regulation PoL

High HP Voltage Unbalance

Reg

ulat

ory

Bre

ache

s

Figure 5.15: Real Network VUF with 80% HP

Electric Vehicle Scenarios

Finally with high levels of EV uptake, UK voltage limits are seen to breached as shown in Figure

5.16. This network compared to the generic network is clearly more thermally constrained and

network planning has meant voltage constraints are not a limitation upon network capacity, hence

in this regard there is no benefit to de-regulation of voltage. Although as shown either EU or TT

limits on regulation reduce the occurrence of regulatory breaches to permissible values.

0

5

10

UK EU T&T UK/PoL EU/PoLT&T/PoL

High EV Nodal Voltages

Reg

ulat

ory

Bre

ache

s

Figure 5.16: Real Network VUF with 71% EV

Significant parts of the network are thermally constrained as shown in Figure 5.17. As with all

cases of high LCT penetration in this particular network VUF is a severe limitation too. For this

network high levels of LCT usage leads to breaches of VUF, thermal limits, and voltage magnitude

limits in that order. As the VUF was show to be problematic over the whole network considered,

replacement of the transformer for a lower loss type is the most effective solution, albeit expensive.

Network feeder upgrades to remove thermal limitations in the feeder will cost �82000.

5.3. Feeder Relief with Voltage Deregulation 117

0

10

20

No Regulation PoL

High EV Feeder Thermal Limits

Bra

nch

Ove

rcur

rent

Figure 5.17: Real Network Branch Thermal Limits with 71% EV

5.3.3 Validation of the Real Network Model

Network efficiency for the UK DNOs in the 10 year period up to 2010 are shown in Figure 5.18.

The figure includes losses across all of the distribution network, including EHV and HV which

where not included in our LV modelling, hence losses in this plot should be approximately double

those in the simulation results.

From this we see significant changes in efficiency whilst the consumed power remains fairly

constant for any given DNOs. Looking across the DNOs (less SSE Hydro) we see that they also

achieve similar overall efficiencies (95% � 1.5%) despite large variations in network size, which

comes as a result of similar network planning methodology and imposed regulators limits.

0.5 1 1.5 2 2.5 3 3.5 4x 104

91

92

93

94

95

96

97

98Consumed Power vs. Network Efficiency

Anual Consumed Power (GWh)

Effic

ienc

y (%

)

CN WestCN EastENWCE NEDLCE YEDLWPD S WalesWPD S WestEDFE LPNEDFE SPNEDFE EPNSP DistrbutionSP ManwebSSE HydroSSE Southern

Figure 5.18: Efficiency and Annual Power Consumed of UK DNOs from 2000-2010

Results for the real network without LCT give losses of 4% (i.e. efficiency of 96%) and with

the most increased loading scenarios the LV network has losses around 6.5%. From the UKPN

allocation of losses (see Table 5.2) our model has accounted for 48% of the total system losses.

This means total network losses would be 8% at nominal loading increasing to 13% for high LCT

scenarios, if the full network was to be considered.

This puts losses in the modelled system at the upper range of losses (for no LCT case) compared

5.3. Feeder Relief with Voltage Deregulation 118

Table 5.2: Network Loss Allocation

Fixed Losses (30%)

Location Amount

Grid/EHV 25%

EHV/HV 20%

HV/LV 55%

Variable Losses (70%)

Location Amount

EHV 30%

HV 25%

LV 45%

to the published losses incurred in the measured distribution networks, where losses are seen to

range from 3.3% to 8.3% depending upon the DNO. The high predicted percentage of network

losses are a results of the high load density, medium feeder length, use of 185mm2 legacy cable,

and LCT use, which leads to increased losses and higher neutral current.

Using a 7:3 ratio of variable to fixed losses at nominal load, and assuming 96% efficiency at

nominal loading, where the variable losses change proportional to the square of the load, and the

fixed losses remain constant, results in the expected losses as shown in Figure 5.19. It is noted

peak efficiency is below nominal loading at 0.65 of the nominal load at which point efficiency is

marginally higher at 96.32%.

0.5 1 1.5 293

94

95

96

97Network Loading vs. Predicted Efficiency

Load Factor

Effic

ency

(%)

Figure 5.19: Expected LV Network Losses

As the maximum increased loading cases have more than doubled the total energy consumption

in these network studies, the efficiency also changes as shown in Table 5.3 and Figure 5.20, which

has normalised network efficiency and power flow to the values with no LCT. The absolute value

of power flow though the substation ��Pt��, that is the input power at the primary side, is then

used to find the overall network efficiency �η� with:

η ��Pt�

�Pt� � Ploss(5.1)

Where the total losses �Ploss� are comprised of:

Ploss � Pfeed � Pserv � Ptran (5.2)

5.3. Feeder Relief with Voltage Deregulation 119

For cases with DG, the network efficiency figure is not directly comparable to the other scenar-

ios, where local consumption must be measured at all the nodes to find accurate efficiency figures.

It is noted however that due to large generation and low load the total system losses increase com-

pared to the scenario without LCT, this is unlike the situation for lower DG penetration, where the

generation supplies load locally, even during times of peak generation, and thus reduces network

losses. This can be confirmed by looking at the substitution columns of the PV scenario where

the absolute value of energy though the substation has increased implying that the load has been

supplied by DG and the reverse power (from DG) is greater than the normal demand without DG,

thus increasing the energy flow via the substation. This is confirmed by comparison of the high PV

substation energy values (2230kWh/day & 2232kWh/day) compared to the same no LCT values

(1922kWh/day & 1897kWh/day) in Table 5.3.

Table 5.3: Substation Energy (kWh/day) and Network Efficiency

ScenarioNo Regulation PoL Regulation

Substation Efficiency Substation Efficiency

No LCT 1922 95.58% 1897 95.55%

High PV 2230 94.03% 2232 93.91%

High HP 3994 93.70% 4003 93.65%

High EV 3786 93.41% 3709 93.58%

Load Factor0.5 1 1.5 2

Effic

ency

(%)

92

93

94

95

96

97

****

No LCTDGHPEV

Network Loading vs. Predicted Efficiency

Figure 5.20: Simulated and Expected Network Losses

5.4. The Benefits of De-regulation in LV Networks 120

5.4 The Benefits of De-regulation in LV Networks

The high cost and disruptive nature of network reinforcement drive alternative solutions to power

quality (PQ) issues brought about by low carbon technologies. This chapter has explored the effect

of changing the voltage tolerance bands. To quantify the benefits of this, 3 new voltage tolerance

bands were suggested, given with their reasoning (section 5.2). Requirements of modelling the

distribution network were (see Chapter 4) implemented, now with particular focus on the load

models required when considering a wider range of supply voltages (section 2.3).

The benefits of de-regulation upon the generic network is that it facilitates medium levels of LCT

uptake. At higher LCT penetrations thermal limits and VUF are encountered meaning network

reinforcement is required for these scenarios. Thus de-regulation is effective in deferring network

investment form the time between, the first voltage constraints encountered prior to medium LCT

uptake and, the first thermal constraints encountered prior to high LCT uptake.

Considering the real network, even with medium levels of LCT the networks is already limited

by: thermal bottlenecks close to the substation (as would be expected from comparison of the

minimum D-LRCS values in the real network relative to the generic network) and high VUF across

much of the network. As a result the benefits of de-regulation to the real network are small.

De-regulation can allow a lower operating voltage and consequently a small reduction in energy

consumption and losses but for future cases of LCT proliferation and deferring investment there

was little advantage.

The contrast seen by de-regulation in these two networks is testament to the highly network

topology dependant nature of the various hosting constraints. Overall de-regulation offers in-

creased LCT hosting capacity to voltage contained networks and as such can help smooth out the

transition to LCT that DNOs need accommodate, generally via network upgrades, expansion and

reinforcement. Growing levels of DG mean this deregulation allows the DNOs greater scope to

lower system voltages, which was also shown to slightly reduce total demand. Ultimately, with

higher levels of LCT voltage problems are however unlikely to be the limiting factors or sole limit-

ing factors, instead VUF and thermal ratings will be problematic. In the case of thermal limits this

can only then be addressed with traditional reinforcement measures or re-routeing of the power

flows.

In reducing the permissible lower voltage limit the benefit to the DNO in terms of hosting

capacity can be very rapidly been seen when PV and DG are considered, this is already know

to be a common voltage quality issue [7]. As mentioned the reason for this is that the DNOs in

choosing to run substation voltage at the upper end of the voltage range [70] limit the capacity for

DG to increase the hosting capacity for additional loads. In reducing the lower band the option

for the DNO to operate lower substation voltages becomes available which in turn increases the

5.4. The Benefits of De-regulation in LV Networks 121

hosting capacity for DG, thus despite not changing the upper band the occurrence of network over

voltage constraints can be reduced by new voltage regulator settings, achieved via automatic tap

changers at primary substation of the off-line taps used on secondary substations.

Point of load regulation has been compared throughout this chapter and in this case the only

relevant limits are the thermal and insulation limits of the network (i.e disregard all voltage based

PQ regulations). With PoL, the networks can be used to thermal limits at all times and DNOs

can consider higher voltages to improve system efficiency and capacity.

Chapter 6

Analysis of LV Networks with

Power Electronic Devices

In this chapter results are presented which show the benefits associated with the PEDs installed

in the generic UK network. Following the method presented in [136], losses for the converters are

not initially considered so that break even or required efficiency ratings can be made for each of

the devices to become economically viable. The PEDs considered are:

� Power Electronic Substation (PES)

� Mid Feeder Compensator (MFC)

� Active Power Filter (APF)

� On-load Tap Changers (OLTC)

A brief review of the aforementioned PEDs is given along with the implementation of the Monte

Carlo analysis methods used for comparing these PEDs is first given before results are presented.

Follwing this the effect of power filtering on network losses is given before the PEDs are compared.

As in Chapter 5, the proliferation scenarios shown in Table 6.1 are used in allocating LCTs to

individual customers.

Table 6.1: LCT Proliferation Scenarios (%)

PV EV HP

Low - 13 -

Mid 30 33 30

High 60 71 80

Much of the work from this chapter was published in the PEDG conference paper “Power

electronic voltage regulation in LV distribution networks.”

122

6.1. PED Device Operation 123

6.1 PED Device Operation

A 24 hour load flow is initially performed with a resolution of 1 minute. After the load flow

completes and the voltage and current (VI) measurements are stored and the process is repeated for

a given number of Monte Carlo trails (runs) or for the next scenario. All of the VI measurements

are then compared with relevant standards or equipment limits, with outlying results flagged.

Network losses, utilisation factor, efficiency, and voltage quality measures are calculated. This

process is then repeated for each of the technologies mentioned in section 2.2. Briefly, these are

given again for reference:

� Base : This represents the case “as is” and indicates the effect of LCT use without any

network changes.

� De-Reg : Deregulation scenarios are easily considered by adjustment of the limits defining

outlying results. The voltage range considered for deregulation is �10% as in the EU. From

Chapter 3 a limit on supply voltages which do not adversely effect domestic loads was given as

+10,-15%, the EU voltage limits fall with in this band.

� PES : The PES is configured so that each feeder is individually regulated. The voltage at

the head of each feeder is continually adjusted between 1.08pu and 0.96pu by the LDC, with the

no load reference voltage as 1.02pu.

� OLTC : The OLTC uses LDC using the same settings as the PES. As the tap changers have a

bandwidth of 2.5% with a maximum tap range of �5%, the limits of the supply voltage (assuming

nominal HV) are 0.96pu to 1.06pu. Unlike with the PES, the secondary winding is connected to a

substation busbar so all 4 feeders are regulated simultaneously.

� APF : The APF is considered to provide reactive compensation and load rebalancing. As

the system is 4 wire, the neutral current is also eliminated, this in practice requires use of a 4-leg

(or split capacitor) inverter. No limit is put on the APF rating. The control strategy used it that

termed perfect harmonic cancellation (PHC), which was also shown to be the most suitable APF

control strategy when non ideal supply voltages were considered [65].

� MFC : The MFC here is operated as a power balancing device. The role of the shunt

converter is solely to supply the active power demand by the series converter. In practice the

shunt converter can also be utilised in the same manner as the APF. The MFC is rated to inject

up to 10% of the nominal voltage; which when considered with the MFC location and the cables

thermal limit give a required rating for each converter of 12kVA.

6.2. Feeder Relief with PEDs 124

6.2 Feeder Relief with PEDs

In this section the benefits of the PEDs are explored, with results given for the detailed generic

UK network. Figure 2.13 is repeated for clarity here and shows the location in the distribution

network that the aforementioned power electronics are installed.

LVSOP

Primary Substation

OLTCSecondary Substation

LV DCNetwork

11kV SOP

MFC

LV AC Network

SST APF

Figure 6.1: Distribution Network with Power Electronics

6.2.1 Generic LV Network

In this chapter results are presented in where the number of instantaneous breaches of voltage

regulation and power quality issues are breached along with thermal ratings, this offers a finer

granularity compared to showing weather a node has, over the low flow time period breached

regulator limits. This measurement is termed occurrence in the following figures and is expressed

as a percentage of the measurements that breach limits. For example is all half of the nodes in the

considered network breeched regulator limits half of the time the occurrence percentage would be

25%.

Zero LCT Scenario

Without consideration of any LCTs the network operates without existing limits being breached as

shown in Fig. 6.2. Some voltages outside tolerance are seen without any PEDs but the frequency

of these is very low.

6.2. Feeder Relief with PEDs 125

0

10

20x 10 3

Base OLTC PES APF MFCO

ccur

ance

(%)

Under Voltage Base

2

0

2x 10 16

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Thermal Limitations Base

Figure 6.2: Outlying Results with no LCTs Considered

PV Generation Scenarios

In the case of PV installations it is over voltage and/or thermal problems we would expect to

encounter [131]. Hence, results presented in this section are for occurrences of over voltages and

breached thermal limits.

0

0.05

0.1

0.15

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Over Voltage Mid PV

2

0

2x 10 16

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Thermal Limitations Mid PV

Figure 6.3: Network with 30% proliferation of PV Installations

With a medium penetration of PV (Fig. 6.3) over voltages are seen when no PED based voltage

regulation is present. Compared to medium penetration of HP (see Fig. 6.5) voltage problems are

encountered more frequently. This is a direct result of the high substation voltages chosen by the

DNOs [70]. In this scenario all regulation devices are able to reduce network over voltages, and

again like the medium HP penetration scenario, the APF is effective in reducing the occurrence of

voltage outside regulator limits. In all cases the thermal limits of the network equipment are not

6.2. Feeder Relief with PEDs 126

exceeded.

As the PV penetration level reaches 60%, over voltages become more common as expected

(Fig. 6.4). In this case the APF is not able to effectively reduce the occurrence of over voltages to

an effective level. The other regulation devices are however all effective in reducing the occurrence

of over voltages.

00.5

11.5

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Over Voltage High PV

2

0

2x 10 16

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Thermal Limitations High PV

Figure 6.4: Network with 60% proliferation of PV Installations

As with the medium penetration of PV scenario in no cases are the thermal limits of the

network equipment breached. The difference in occurrence of thermal limits and voltage limits

(over or under) being breached between the PV scenarios and the HP/EV scenarios is a direct

result of network operation voltages. It is clear as the amount of LV connected PV grows and over

voltage becomes more frequent (already encountered more than under voltages [70]) the DNOs

must act to either upgrade network infrastructure, reduce substation voltages, or improve voltage

regulation.

Heat Pump Scenarios

As the amount of HP used increases under voltage measurements are seen at remote feeder ends.

From Fig. 6.5, which show 30% installation of HP, the voltage limits are breached whist the

networks thermal limits are not exceeded. This clearly indicates the network is voltage constrained

in this scenario.

The PES and MFC are both able to improve voltage regulation such that the network is not

voltage constrained. In the case of the OLTC the cause of the voltages which lye outside regulator

limits is due to the delay time used in the tap selection process. The APF is also seen to reduce

the frequency of under voltage measurements.

As the amount of HP installed is increased to 60% network thermal limits are encountered.

6.2. Feeder Relief with PEDs 127

0

0.05

0.1

Base OLTC PES APF MFCO

ccur

ance

(%)

Under Voltage Mid HP

2

0

2x 10 16

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Thermal Limitations Mid HP

Figure 6.5: Network with 30% proliferation of Heat Pumps

Here the PES and MFC compensate for under voltages such that the network can be said to be

thermally limited. This scenario would therefore need further network reinforcement to be a viable

operating scenario for a UK based DNO. The under voltages with the OLTC are again due ot the

tap selection time but also the limit placed on the tap ratio (�5%) which is not the case for the

PES.

0

2

4

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Under Voltage High HP

00.10.20.3

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Thermal Limitations High HP

Figure 6.6: Network with 80% proliferation of Heat Pumps

Thermal limits are reached more frequently with the MFC as compared to the OLTC and PES

as the power required of the voltage injected by the series converter but be balanced by that of

the shunt converter. As the HP is treated as a constant power load operation with high supply

voltages acts to reduce the current drawn.

6.3. Analysis of Active Power Filters 128

Electric Vehicle Scenarios

For brevity results for low penetration of EV are not shown, however in this scenario all regulation

devices except the APF reduce under voltage occurrences to almost zero and in non of the cases

is the network seen to be thermally limited.

Medium penetration of EVs are given in Fig. 6.7, again the PES and MFC are able to remove

any voltage limitations. Thermal limitations in this scenario occur all with very limited frequency

(similar to the frequency of recorded under voltage in the base scenario without voltage regulation).

0

0.2

0.4

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Under Voltage Mid EV

0

0.01

0.02

0.03

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Thermal Limitations Mid EV

Figure 6.7: Network with 33% proliferation of Electric Vehicles

When the amount of EVs increases to 71% results (Fig. 6.8) again show only the PES and MFC

reduce voltage constraints to a level below their thermal limits. The OLTC is effective in reducing

the occurrence of under voltage, where in this case, the remaining under voltages are due to the

limit of �5% on the tap ratios.

In all cases thermal limits are breached and like in the case of a high penetration of heat pumps

network upgrades would need to be made for this scenario to be a viable in the UK. All regulation

devices are shown to reduce the occurrence of thermal limits

6.3 Analysis of Active Power Filters

The active power filter is used for phase rebalancing which in turn reduces network losses; its ability

to regulate voltage coming as a result of this (by virtue of neutral voltage reduction and balanced

voltage drop across each phase). Namely, the APF is not first and foremost a voltage regulator,

this should be clear from Figures 6.5-6.4. It reduces voltage issues only when the occurrence (hence

magnitude) is low.

The impact of the APF upon network operation and losses is shown for an average of 10

6.3. Analysis of Active Power Filters 129

0123

Base OLTC PES APF MFCO

ccur

ance

(%)

Under Voltage High EV

0

0.2

0.4

0.6

Base OLTC PES APF MFC

Occ

uran

ce (%

)

Thermal Limitations High EV

Figure 6.8: Network with 71% proliferation of Electric Vehicles

simulations with high penetration of HP. At node 13 where the APF is located neutral current is

eliminated and the losses in the phase conductors at this node are also equalised. This can be in

Fig. 6.9 which shows the cable losses over the period of simulation (24 hours) for one trail with a

high proliferation of HP.

5 10 15 20 25 300

0.5

1

1.5

Node

Loss

es (k

Wh/

day)

Cable losses with APF at Node 13

A : 16.9B : 15.8C : 16.6N : 2.34

Figure 6.9: Network with 60% proliferation of PV Installations

For the three high penetration scenarios and the base case the average cable losses (phase and

neutral) are given in Table 6.2. It can be seen the reduction in losses is between 7-10%. In absolute

terms if we take the the cost of network losses as �0.06 /kWh [130] the annual cost in reduction

of losses will be �127.

The greater benefit of the APF lies in its ability to reduce the occurrence of thermal limitations

in network equipment as is evident in Figs. 6.2-6.4, and mitigation of power quality issues should

they become limiting factors.

6.4. Comparison of PED Regulation Approaches 130

Table 6.2: Cable Losses

ScenarioLoss (kWh/day)

ReductionNo APF APF

No LCTs 16.10 14.47 1.63 (10%)

High DG 13.21 12.19 1.02 (7.7%)

High EV 60.93 55.14 5.79 (9.5%)

High HP 60.82 56.45 4.37 (7.1%)

As the network voltage drop is small relative to the level of current imbalance present across

the phases, the shunt connected APF is larger than the series connected MFC, which was able

to regulate system voltage with a 12kVA rating. The rating of the APF was not limited in the

simulation and the rating was calculated using the maximum power for one phase, which was then

used to find the total converter rating. The rating of the converter required varied between 42kVA

and 55kVA dependant upon the LCT scenario considered.

Table 6.3: APF Size

Scenrio Rating (kVA)

No LCTs 42.4

High DG 44.4

High EV 55.1

High HP 47.7

6.4 Comparison of PED Regulation Approaches

For the 8 LCT scenarios and all voltage regulation scenarios the 75th percentile is checked for

values above 0.07%, this corresponds to 1 minute of outlying results a day. Table 6.4 lists the

number of LCT scenarios without these outliers, with the final column listing the percentage of

the 16 considered voltage or thermal limits which were not exceeded. This metric was used instead

of individual application of EN50160 to the consumers so to give an indication of the wider network

performance, but results are very similar with either method.

The reason for the OLTC’s poorer voltage regulation (compared to PES) are: the delay time

implemented in the tap selection process (so voltage changes can go un-regulated for a time), the

smaller range of voltages the OLTC can achieve, and the simultaneous regulation of all 4 feeders.

Non of the regulation scenarios are able to remove thermal limits to passable levels, but from

Figs. 6.2-6.4 it is noted they can be reduced. As the LCTs considered are all assumed to be

inverter connected (constant power loads) operation at higher voltage levels can reduce current

drawn by these loads and in the case of the APF current limits are reduced via load balancing.

6.5. The Benefits of PEDs in LV Networks 131

Table 6.4: Scenarios considered without Constraints

RegulationVoltage

Thermal Overall %Under Over

Base 1 0 6 44

De-Reg 3 0 6 56

OLTC 3 2 6 69

PES 6 2 6 88

APF 2 1 6 56

MFC 5 2 6 81

6.5 The Benefits of PEDs in LV Networks

Here we have presented 4 power electronic based voltage regulation to improve voltage regulation

in LV networks and have compared them to the case at present (base) and a de-regulation scenario.

De-regulation was considered as a lowering of the lower permissible supply voltage with the upper

voltage limit unchanged. For this reason the hosing capacity of DG was not increased by de-

regulation. For increased loading scenario the lower voltage limit allowed further network loading

allowing medium penetration of HP or EV without voltage constrains. De-regulation when utilised

in conjunction with changes to the HV operating voltage or the LV substation taps could allows

greater hosing capacity for all the considered LCTs.

In the cases of the MFC, OLTC, and PES, all were able to improve voltage regulation to

accommodate medium levels of LCTs. For DG (i.e PV) hosting capacity was increased by all of

the regulation devices. Voltage control at either the substation or mid-feeder allows for greatly

improved LCT hosting capacity. In practice the advantages of the PES over the OLTC could be

reduced by increasing the range (or number) of the taps, along with faster tap selection. This later

point due to reliability and operating life of new tap changer technologies [137] not be a cause for

reduced OLTC life. The prominent advantages of he MFC compared to the PES (or APF) is the

reduced size needed along with voltage regulation comparable to the PES.

Chapter 7

Conclusions and Future Work

7.1 Conclusions

This thesis has outlined and compared 2 broad solutions to LV network hosting constraints. First,

voltage de-regulation has been considered to reduce the frequency of network voltage constraints

by simply relaxing the voltage tolerance levels. Secondly, a range of power electronic devices has

been implemented in the network models to assess the efficacy of each of the PEDs. Additionally,

we have assessed the voltage sensitivity of domestic loads and drawing together results from the

literature, along with experimentation and simulation. Building on this work load models were

developed that account not only for the load PQ voltage sensitivity but for the thermal control

requirements of these devices which use thermal controllers, this without necessarily resorting to

dynamic heat flow equitations.

Load & Network Modelling

In Chapter 3 the effect of a changing the supply voltage to common domestic loads was studied.

Firstly, regarding the lighting sector the change from incandescent to CFL, halogen and LED

lighting was outlined, as these latter technologies (less halogen) are less sensitive to supply voltage

than incandescent lighting the greatest visual effect to the consumer of supply voltage, that is

domestic lighting luminosity is reduced. Thus regarding lighting as more and more incandescent

bulbs are phased out the visual disturbance resulting from this is also also diminished. Amongst

all the lighting technologies presented PQ voltage sensitivity figures show that for this transition

of technologies the overall load presented to the network becomes less dependant upon the supply

voltage, this in turn reduces the efficacy of voltage optimisation as a means to reduce demand.

Additionally as the loads tends towards a constant power load (CPL) type characteristics network

stability is reduced. However due to the increased efficiency of new lighting technologies the load

132

7.1. Conclusions 133

presented decreases thus offsetting this effect.

Regarding electric heating systems, which are used mostly for space and water heating, the

PQ sensitivity of loads that are resistive where shown, as would be expected, to have a constant

impedance PQ voltage sensitivity. This affords considerable room for voltage optimisation. For

heating loads that use a thermal controller to adjust the load duty cycle, to meet temperature set

points, dynamic thermal models and constant energy models were developed from load profiles

that indicate only the PQ demand at nominal voltage. These additional controls where shown

to have a large effect on network power flow where the proportion of customers having thermally

controlled loads and where the np and nq values (see (2.54) & (2.55)) are high, ie. networks with

economy 7 heating and electric water heaters.

Motors where shown to represent a significant portion of the LV load (�30%) where they are

used in cold appliances (eg. fridges) and loads where the converted kinetic energy is directly

utilised (eg. vacuums, washers). These motors when not interfaced to the network via a power

electronic converter are normally single phase inductions motors, which where shown to have a

constant current type power demand (np=1) and a constant impedance type reactive power demand

(nq=2). When these motors are used in thermally controlled loads they are again required to meet

temperature set points thus need either thermal models or the developed constant energy models

to be include in for accurate load flow studies, especially when the supply voltage is considered

to fluctuate widely. When an adjustable speed drive (ASD) or variable frequency drive (VFD) is

used with the motor the results from the literature indicated that the power demand falls with an

approximately constant impedance power sensitivity (np=2).

In the vast majority of cases, loads were seen to be able to operate as normal with voltages

reduced by as much as 15% from normal and frequently further still. The same was not true of

higher voltages levels where loads where seen to be damaged or malfunction with only 2% higher

voltages than the present regulatory maximum. As such the voltage band that would minimise

disruption to loads whist maximising the hosting capacity of LCTs was given as -15%,+10%.

In section 4.2 metrics were developed to asses the sensitivity of a distribution network to thermal

and voltage problems. These are used to predict the likelihood of network hosting constraints

without having to complete load flow analysis and are based solely upon the topology of the

network which is known, the amount of, and location of the connected customers, which are also

known. As the load profile of each customer at any one time is a stochastic function, diversity

factors (DF) were utilised so the metrics can account for this uncertainty.

Voltage Deregulation

In Chapter 5 the benefits of voltage de-regulation on a network level were explored. In particular

the ability of de-regulation to off set the need for network reinforcement driven by uptake of LCTs

7.1. Conclusions 134

was studied.

De-regulation was compared in two networks and the efficacy of de-regulation was shown to

vary significantly. Initially PV was considered which was seen to cause rapid overvotlage issues

across all the networks, thus tap settings where then modified to accommodate this. Following this,

in the generic UK network de-regulation facilitated increased loading of the network from below

medium LCT levels up to high LCT levels, without voltage constraints. At high LCT levels the

generic network was thermally constrained. In removing the voltage constraints between these two

loading scenarios �10,000 of network upgrades required for 96 customers was deferred / avoided.

If the network reinforcement costs were deferred the effective period of deferral is the time the

network loading takes to grow from the first encountered voltage constraints without de-regulation

to the time at which the first thermal constraints encountered (with or without de-regulation as

thermal limits are unaffected by de-regulation).

For the case of the real network, with medium LCT penetration levels of HP and EV, the

thermal limits of the network were already encountered, thus network reinforcement is needed. As

such de-regulation cannot initially increase the hosting capacity of this network. De-regulation is

however beneficial after targeted network reinforcement has been performed. The target lines can

be identified by inspection of the D-LRCS plot (Figure 4.7) and the box plots of Figure 5.14 where

the “whiskers” extend to a maximum of 16 (branches) which is also a point at which the sorted

D-LRCS values thereafter increase. Once the feeder thermal constraints have been removed the

additional reinforcement required to further remove supply voltage constraints has been avoided.

Power Electronics

In Chapter 6 PEDs for the purpose of increasing network hosting capacity for LCTs were compared

and assessed in their efficacy.

The APF was the least effective of the devices studied when assessed in terms of removing

voltage constraints, this is unsurprising as it is the only PED considered that does not directly

aim to regulate the voltage and any provision for reactive compensation to control the network

voltage was shown to be infective due to the low X/R ratio of the network. For reducing losses

in the network the APF was effective, and seen to reduce cable losses by up to 10%, however in

terms of direct finical incentives to do so, the annual saving in the case of the generic network

would be around 130 in high loading scenarios and 36 with present levels, thus the case for PEDs

to justify their expense based solely on their ability to reduce system losses in difficult to envisage.

The RIIO-ED1 price control framework by Ofgen does however offer funding incentives to DNOs

which are able to reduce system losses.

All of the other considered power electronic solutions were effective in reducing the over voltage

constraints brought about by DG and the lower voltage limits brought about by electrification (ie.

7.2. Authors Contribution 135

HPs and EVs) up to the medium penetration scenarios considered. The PES was further able to

remove all cases of voltage constraints. In doing so, the PEDs afford considerable scope for deferral

of network reinforcement in voltage constraints networks.

The advantage of the MFC is that it controls the voltage effectively whist only processing a

small faction of the the power at its PCC. This “thin” power electronic solution thus drastically

reduces the device rating and capital costs and operational costs as losses in the absolute terms

from the device are reduced. Thus it is the MFC that is the most viable PED for economically

deferring reinforcement costs.

Comparison of Voltage Deregulation and Power Electronics

Both de-regulation and PEDs where able to increase hosting capacity when constrained by voltage

limits (less the APF). This is true only for under voltage when considering de-regulation without

the previously suggested changes to network regulator settings, whilst for the PEDs the voltage

control is suited for both DG and increased demand. Thermal limits in periods of high demand with

de-regulation where seen to be slightly worsened with de-regulation as a result of large constant

power loads, whilst with PEDs the opposite is true.

In regards to absolute efficacy for high loading scenarios both the T&T and EU regulation

limits are seen via relative comparison of Figures 5.6, 5.8, 6.4, and 6.6 to be just as effective as

the most effective of the PEDs, namely the SST, OLTC and MFC. However as shown in chapter 5

by looking at the thermal breaches caused when using PoL, de-regulation can increase the thermal

stress on the network, particularly being that electrification of heating and transport include power

electronic front ends which appear as constant power loads. Conversely PEDs by operating the

network at higher voltage levels reduce the thermal stress on the network. It is work mentioning

that in the case of simple resistive loads the situation would be reversed, hence the need for the

detailed load models and voltage sensitivity profiles that where presented in chapter 2.

7.2 Authors Contribution

The thesis posed the question of how can LV network hosting constraints be removed by integration

of PEDs and voltage de-regulation. Chapter 3 first answered what voltage tolerance levels are

actually needed by the LV connected loads. Chapter 4 then presented a methodology for simulation

of LV networks where voltages fluctuate widely, along with methods to account for the probabilistic

nature of loading at any one instant. Also developed was the new R-LRCS metric that indicates

the likelihood of thermal limit breaches in parts of the network. In Chapter 5 the benefits of

voltage de-regulation on the network hosting capacity was shown. Finally Chapter 6 answered

how specific PED can be used to remove network hosting constraints.

7.2. Authors Contribution 136

In achieving these goals a detailed load flow model for LV networks has been developed that

uses load models which expand upon the bottom up load modelling approach used in the CREST

simulator tool, such that the voltage sensitivity of the network is profiled much in the same way as

the actual demand is over a 24 hour period. This extension of load profiling becomes increasingly

important as the permissible voltage range is increased. A wide range of tools in MATLAB

to perform the load flow where developed with the option to use either Simulink or MATLAB

environment, these tools encompass:

� Building of the network model / equations

� Performing Monte Carlo low flow analysis with accurate load models

� Analysing large quantities of voltage and current datasets

The network build tools are able to interpret network topology datasets in multiple format

and estimate missing data (which is common with typical DNO data which is very large in scale).

Further more optimisation of the network topology is performed so that load flow can utilise fast

“sweep” or “ladder” based methods to solve the load flow by breaking loops in the network or

re-ordering branch to and from nodes to improve solution speed when using the direct approach.

Having generated the results for numerous networks, with differing levels of LCT penetration and

with enough Monte Carlo trails to gain statistical confidence, the data is analyses to check with

relevant regulations. This process typically involves smoothing high resolution data to the required

averaging time period and then checking converting the results (voltage and current measurements)

into a format that can be checked against regulations or plant limits.

Suggestions where also made regarding relaxation of voltage limits in distribution networks

for domestic customers such that in the short term the hosting capacity of LCTs can increased

without the significant expenditure or indeed delays incurred from network reinforcement. These

limits where suggested such that the impact upon customers would would be minimised whilst

still relaxing voltage tolerances by a significant margin such that noteworthy increases to hosting

capacity can be achieved, albeit with the caveat that DNO practices in regards to voltage levels

would need to be adjusted in order to gain maximum benefits for this de-regulation in particular

where large capacities of DG make high voltages particularly problematic.

There is much work regarding development and / or control of power electronics for use in

distribution networks along with individual assessment of certain technologies but little work that

compare the benefits of a wide range of various PEDs specifically within the distribution network,

where many FACTS devices are not applicable.

The work also detailed the implementation of thermally controlled loads into steady state AC

load flow studies. The method proposed needs only the nominal power demand of the load which

7.3. Future Work 137

is available when load profiles are generated from “bottom-up” modelling techniques. This offers

a fast alternative to integrated electro-thermal modelling of these loads.

7.3 Future Work

Further correlation analysis of the suggested network metrics proposed in section ?? would be

needed to fully validate the efficacy of the metrics in assessing network performance

Experimental validation of the voltage sensitivity derived from the CREST load profile simu-

lator would also enable predictions about the time varying efficacy of voltage optimisation.

A further comparison of the schemes mentioned but not further explored in section 1.4.2 would

quantify the befits of PEDs relative to these other approached, not just other PEDs and voltage

de-regulation as was the case within this work.

Voltage optimisation via setting of the PoL regulated voltage is an interesting possibility but

was not further presented. Further to this, with PoLs, it would also be interesting to asses network

hosting capacity by changing the supply voltages to fully utilise cable insulation limits, or even

transitioning the network to LVDC as in [138].

7.4. Published Works 138

7.4 Published Works

A list of works which the author has written or contributed to, and is related to the material in

this thesis, is listed below:

� T. Frost and P. D. Mitcheson, Impact of Wider Voltage Tolerance on Consumer Electronics

and Wider Socialised Costs, Top and Tail Project Report, 2013

� T. Frost and P. D. Mitcheson, Analysis of Feeder Relief Versus Tolerance Band, Top and Tail

Project Report, 2014

� T. Frost, P. D. Mitcheson, and T. C. Green, Power electronic voltage regulation in lv dis-

tribution networks, in Power Electronics for Distributed Generation Systems (PEDG), 2015

IEEE 6th International Symposium on, June 2015.

� T. C. Green, T. Frost, A. Junyent-Ferre, and P. D. Mitcheson, Power electronics for flexible

distribution networks, Smart Grid Handbook, 3 Volume Set, Book Chapter, 2016

� T. Frost and P. D. Mitcheson, Comparison of Power Electronics for Capacity Release in LV

Networks, Top and Tail Project Report 2016

Bibliography

[1] T. Haggis, EON Network Design Manual, 7th ed., E.ON Central Netwroks, December 2006.

[2] “Climate Change Act 2008,” 2008, c.27. London: The Stationary Office.

[3] DONG Energy Power, “RACE BANK Offshore Wind Farm,” Online, Race Bank Wind Farm

Booklet,, 2015.

[4] Commite on Climate Change, “Meeting Carbon Budgets - 2016 Progress Report to Parlia-

ment,” 2016.

[5] Ofgen, “RIIO-ED1 regulatory instructions and guidance: Annex F Interruptions,” Ofgem,

v1.0 2015.

[6] Voltage characteristics of electricity supplied by public electricity networks, British-Standard-

Institution Std. EN 50 160:2010+A1:2015:, January 2015.

[7] N. Bottrell, E. Ortega, M. Bilton, T. Green, and G. Strbac, “Impact of low voltage con-

nected low carbon technologies on power quality,” Imperial College London, Tech. Rep.,

2014, Report B3 for the Low Carbon London LCNF project:.

[8] Z. Hu and F. Li, “Distribution network reinforcement utilizing active management means,”

in IEEE PES General Meeting, July 2010, pp. 1–3.

[9] Department of Energy & Climate Change, “2015 Provisional GHG emissions estimates: data

tables,” Online, March 2016.

[10] United Nations, “Framework Convention on Climate Change,” 2015, Adoption of the Paris

Agreement, 21st Conference of the Parties.

[11] Department for Business, Energy & Industrial Strategy, “Capacity of, and electricity gener-

ated from, renewable sources (DUKES 6.4),” Digest of UK Energy Statistics (DUKES), July

2016.

[12] ——. (2016, July) Solar photovoltaics deployment. Online. National Statistics. [Online].

Available: https://www.gov.uk/government/statistics/solar-photovoltaics-deployment

139

Bibliography 140

[13] C. Cluzel, E. Standen, B. Lane, and J. Anable, “Pathways to high penetration of electric

vehicles,” Element Energy and Ecolane Consultancy and University of Aberdeen, Tech. Rep.,

December 2013, Report for The Committee on Climate Change.

[14] National Grid, “Future Energy Scenarios,” Online, July 2016,

http://fes.nationalgrid.com/fes-document/,.

[15] G. Strbac, C. Gan, M. Aunedi, V. Stanojevic, P. Djapic, J. Dejvises, P. Mancarella,

A. Hawkes, D. Pudjianto, S. L. Vine, J. Polak, D. Openshaw, S. Burns, P. West, D. Brogden,

A. Creighton, and A. Ciaxton, “Benefits of advanced smart metering for demand response

based control of distribution networks,” Imperial College, Tech. Rep., April 2010, energy

Networks Association.

[16] P. Trichakis, P. Taylor, P. Lyons, and R. Hair, “Predicting the technical impacts of high

levels of small-scale embedded generators on low-voltage networks,” IET Renewable Power

Generation, vol. 2, no. 4, pp. 249–262, Dec. 2008.

[17] H. Markiewicz and A. Klajn, “Voltage distrubances: Standard EN 50160,” 2004.

[18] J. Gomez and M. Morcos, “Impact of ev battery chargers on the power quality of distribution

systems,” Power Delivery, IEEE Transactions on, vol. 18, no. 3, pp. 975–981, July 2003.

[19] J. Enslin and P. J. Heskes, “Harmonic interaction between a large number of distributed

power inverters and the distribution network,” Power Electronics, IEEE Transactions on,

vol. 19, no. 6, pp. 1586–1593, Nov 2004.

[20] P. Barker and R. de Mello, “Determining the impact of distributed generation on power

systems. i. radial distribution systems,” in Power Engineering Society Summer Meeting,

2000. IEEE, vol. 3, 2000, pp. 1645–1656 vol. 3.

[21] P. Richardson, D. Flynn, and A. Keane, “Optimal charging of electric vehicles in low-voltage

distribution systems,” Power Systems, IEEE Transactions on, vol. 27, no. 1, pp. 268–279,

Feb 2012.

[22] D. Reimert, Protective Relaying for Power Generation Systems, ser. Power Engineering

(Willis). Taylor & Francis, 2005. [Online]. Available: http://books.google.co.uk/books?

id=i9hXq4QUhmYC

[23] W. Kersting, Distribution System Modeling and Analysis, 3rd ed., ser. Electric Power Engi-

neering. US: CRC Press, 2012.

[24] S. Papathanassiou, N. Hatziargyriou, and K. Strunz, “A benchmark low voltage micrgrid

netwrok,” Power Systems with Dispersed Generation, 2005.

Bibliography 141

[25] Long Term Devlopment Statement for Southern Electric Power Distrbution plc’s Electric

Distrbution System, Scotish and Southern Energy, May 2014, avaivble on Request from

Scottish and Southern Energy (www.SSEPD.co.uk).

[26] Electric cables - Calculation of the current rating, IEC Std.

[27] Calculation of the cyclic and emergency current rating of cables, IEC Std., 1985.

[28] G. C. Montanari and M. Cacciari, “A probabilistic life model for insulating materials showing

electrical thresholds,” IEEE Transactions on Electrical Insulation, vol. 24, no. 1, pp. 127–134,

Feb 1989.

[29] D. A. Zarchi and B. Vahidi, “Optimal placement of underground cables to maximise total

ampacity considering cable lifetime,” IET Generation, Transmission Distribution, vol. 10,

no. 1, pp. 263–269, 2016.

[30] Long Term Devlopment Statement (Northeast), Nothern Powergrid, November 2013, available

on Rerquest from Nothern Powergrid (www.nothernpowergrid.com).

[31] R. Mehta and V. Mehta, Principles of Power System. S. Chand, 2005, 2005.

[32] UK Power Networks, “LV NETWORK DESIGN,” April 2015, ENGINEERING DESIGN

STANDARD - EDS 08-0136.

[33] IEEE, “Definitions of voltage unbalance,” IEEE Power Engineering Review, vol. 21, no. 5,

pp. 49–51, May 2001.

[34] Pacific Gas and Elelctric Company, “Voltage Unbalance and Motors,” Online, October 2008.

[35] N. G. Hingorani and L. Gyugyi, Understanding FACTS: Concepts and Technology of Flexible

AC Transmission Systems. Wiley, 2000.

[36] R. Rudervall, J. Charpentier, and R. Sharma, “High voltage direct current

(hvdc)transmission systems technology review paper,” in Energy Week 2000, Washington,

D.C, USA, March 2000.

[37] T. Green and R. S. T. Lth, “Power electronics in distribution system management,” HubNet

Position Paper Series, Tech. Rep., 2015.

[38] T. Frost and P. Mitcheson, “Impact of Wider Voltage Tolerance on Consumer Electronics

and Wider Socialised Costs,” Imperial College London, Tech. Rep., 2013, Report for the Top

and Tail Project.

[39] D. J. Start, “A review of the new cenelec standard en 50160,” in Issues in Power Quality,

IEE Colloquium on, Nov 1995, pp. 4/1–4/7.

Bibliography 142

[40] M. Bilton and R. Carmichael, “Consumer attitudes to changes in electricity supply voltage,”

UK Energy Reserch Center, Tech. Rep., 2015.

[41] J. Yang, X. Bai, D. Strickland, L. Jenkins, and A. M. Cross, “Dynamic network rating for

low carbon distribution network operation a u.k. application,” IEEE Transactions on Smart

Grid, vol. 6, no. 2, pp. 988–998, March 2015.

[42] Z. Hu and F. Li, “Cost-benefit analyses of active distribution network management, part i:

Annual benefit analysis,” Smart Grid, IEEE Transactions on, vol. 3, no. 3, pp. 1067–1074,

Sept 2012.

[43] S. Grenard, D. Pudjianto, and G. Strbac, “Benefits of active management of distribution

network in the uk,” in Electricity Distribution, 2005. CIRED 2005. 18th International Con-

ference and Exhibition on, June 2005, pp. 1–5.

[44] G. Strbac, “Demand side management: Benefits and challenges,” Energy Policy, vol. 36,

no. 12, pp. 4419 – 4426, 2008, foresight Sustainable Energy Management and the Built

Environment Project. [Online]. Available: http://www.sciencedirect.com/science/article/

pii/S0301421508004606

[45] P. Palensky and D. Dietrich, “Demand side management: Demand response, intelligent

energy systems, and smart loads,” IEEE Transactions on Industrial Informatics, vol. 7,

no. 3, pp. 381–388, Aug 2011.

[46] C. A. Hill, M. C. Such, D. Chen, J. Gonzalez, and W. M. Grady, “Battery energy storage

for enabling integration of distributed solar power generation,” IEEE Transactions on Smart

Grid, vol. 3, no. 2, pp. 850–857, June 2012.

[47] S. Vazquez, S. M. Lukic, E. Galvan, L. G. Franquelo, and J. M. Carrasco, “Energy storage

systems for transport and grid applications,” IEEE Transactions on Industrial Electronics,

vol. 57, no. 12, pp. 3881–3895, Dec 2010.

[48] E. M. Leung, “Superconducting fault current limiters,” IEEE Power Engineering Review,

vol. 20, no. 8, pp. 15–18, 30, Aug 2000.

[49] I. Richardson, M. Thompson, D. Infield, and C. Cifford, “Domestic electricity

use: A high-resolution energy demand model,” 2010. [Online]. Available: https:

//dspace.lboro.ac.uk/dspace-jspui/handle/2134/5786

[50] Long Term Development Statement (LTDS), UK Power Networks, May 2014, available on

Rerquest from UK Power Networks (www.ukpowernetworks.com).

Bibliography 143

[51] THE DISTRIBUTION CODE - OF LICENSED DISTRIBUTION NETWORK OPERA-

TORS OF GREAT BRITAIN, dcode Std., January 2016.

[52] P. Facey, “Fordingbridge electricity substation, puddleslosh lane,” image Copyright Peter

Facey. This work is licensed under the Creative Commons Attribution-Share Alike 2.0 Generic

Licence. To view a copy of this licence, visit http://creativecommons.org/licenses/by-sa/2.0.

[53] K. Williamson, “Substation,” this work is licensed under the Creative Commons

Attribution-Share Alike 2.0 Generic Licence. To view a copy of this licence, visit

http://creativecommons.org/licenses/by-sa/2.0.

[54] Avoiding Danger from Overhead Power Lines, Health and Safty Excutive, March 2013.

[55] P. Facey, “11kv electricity line, south of harbridge,” this work is licensed under the Creative

Commons Attribution-Share Alike 2.0 Generic Licence. To view a copy of this licence, visit

http://creativecommons.org/licenses/by-sa/2.0.

[56] J. R. Carson, “Wave propagation in overhead wires with ground return,” Bell System Tech-

nical Journal, The, vol. 5, no. 4, pp. 539–554, Oct. 1926.

[57] R. Ciric, A. Padilha Feltrin, and L. Ochoa, “Power flow in four-wire distribution networks-

general approach,” IEEE Transactions on Power Systems, vol. 18, no. 4, pp. 1283–1290, Nov.

2003.

[58] D. Meeker. (2012, April) Finite element magnetics (femm).

[59] A. Urquhart and M. Thomson, “Assumptions and approximations typically applied in mod-

elling lv networks with high penetrations of low carbon technologies,” Solar Integration Work-

shop 2013, Oct 2013.

[60] P. Anderson, Analysis of faulted power systems, ser. IEEE Press power system engineering

series. IEEE Press, 1995.

[61] N. Mohan, T. M. Undeland, and W. P. Robbins, Power Electronics. Converters, Applications

and Design, 3rd ed. John Wiley and Sons, Inc, 2003.

[62] T. C. Green and J. H. Marks, “Control techniques for active power filters,” IEE Proceedings

- Electric Power Applications, vol. 152, no. 2, pp. 369–381, March 2005.

[63] C. Hochgraf and R. Lasseter, “Statcom controls for operation with unbalanced voltages,”

Power Delivery, IEEE Transactions on, vol. 13, no. 2, pp. 538–544, Apr 1998.

[64] Q. C. Zhong, L. Hobson, and M. Jayne, “Generating a neutral point for 3-phase 4-wire dc-ac

converters,” in IEEE Compatibility in Power Electronics, 2005., June 2005, pp. 126–133.

Bibliography 144

[65] M. Montero, E. Cadaval, and F. Gonzalez, “Comparison of control strategies for shunt active

power filters in three-phase four-wire systems,” Power Electronics, IEEE Transactions on,

vol. 22, no. 1, pp. 229–236, Jan 2007.

[66] “Ieee standard definitions for the measurement of electric power quantities under sinusoidal,

nonsinusoidal, balanced, or unbalanced conditions,” IEEE Std 1459-2010 (Revision of IEEE

Std 1459-2000), pp. 1–50, March 2010.

[67] H. Akagi, S. Ogasawara, and H. Kim, “The theory of instantaneous power in three-phase

four-wire systems: a comprehensive approach,” in Industry Applications Conference, 1999.

Thirty-Fourth IAS Annual Meeting. Conference Record of the 1999 IEEE, vol. 1, 1999, pp.

431–439 vol.1.

[68] J. M. Bloemink and T. C. Green, “Increasing distributed generation penetration using soft

normally-open points,” in IEEE PES General Meeting, July 2010, pp. 1–8.

[69] F. Z. Peng, “Harmonic sources and filtering approaches,” IEEE Industry Applications Mag-

azine, vol. 7, no. 4, pp. 18–25, Jul 2001.

[70] F. Li and G. Shaddick, “LV network templates for a low carbon future- stresses on the LV

network caused by low carbon technologies,” 2013.

[71] L. Ochoa and P. Mancarella, “Low-carbon lv networks: Challenges for planning and opera-

tion,” in Power and Energy Society General Meeting, 2012 IEEE, July 2012, pp. 1–2.

[72] S. Bala, D. Das, E. Aeloiza, A. Maitra, and S. Rajagopalan, “Hybrid distribution trans-

former: Concept development and field demonstration,” in Energy Conversion Congress and

Exposition (ECCE), 2012 IEEE, Sept 2012, pp. 4061–4068.

[73] A. J. Collin, G. Tsagarakis, A. E. Kiprakis, and S. McLaughlin, “Development of low-voltage

load models for the residential load sector,” IEEE Transactions on Power Systems, vol. 29,

no. 5, pp. 2180–2188, Sept 2014.

[74] J. Milanovic, K. Yamashita, S. Martinez Villanueva, S. Djokic, and L. Korunovic, “Interna-

tional industry practice on power system load modeling,” Power Systems, IEEE Transactions

on, vol. 28, no. 3, pp. 3038–3046, Aug 2013.

[75] K. Schneider, F. Tuffner, R. Singh, and J. Fuller, “Evaluation of conservation

voltage reduction (CVR) on a national level,” 2010. [Online]. Available: http:

//www.pnl.gov/main/publications/external/technical reports/PNNL-19596.pdf

[76] I. Staffell, D. Brett, N. Brandon, and A. Hawkes, Domestic Microgeneration: Renewable and

Distributed Energy Technologies, Policies and Economics. Taylor & Francis, 2015. [Online].

Available: https://books.google.co.uk/books?id=sZvwCQAAQBAJ

Bibliography 145

[77] P. Owen, “The rise of the machines- a reviews of energy using products in the home from

the 1970s to today,” Online, June 2006, Energy Saving Trust.

[78] Department of Energy & Climate Change, “Energy consumption in the UK (ECUK) 2016

Data Tables,” Online, July 2016, Numbers accurate in October 2013.

[79] N. Kelly, “Future energy demand in the domestic sector,” University of Strathclyde, Tech.

Rep., 2012.

[80] J. Zimmerman, M. Evans, J. Griggs, N. King, L. Harding, P. Roberts, and C. Evans, “House-

hold electrical study: A study of dometic elctrical product useage,” Intertek, Tech. Rep.

R66141, 2012.

[81] P. Owen, “Powering the Nation: Household elelectric-using habits revealed,” Online, June

2012, Energy aving Trust.

[82] Department of Energy & Climate Change, “2015 Provisional GHG emissions estimates: data

tables,” Online, March 2013.

[83] Welch Allyn, “HPX Light Lamps Catalog,” Online, November 2009.

[84] D. Kosterev, S. Yang, and B. Lesieutre, “Load Modeling in WECC,” 2010.

[Online]. Available: http://www.wecc.biz/committees/StandingCommittees/PCC/TSS/

SRWG/11032010/Lists/Presentations/1/2010%20SRWG%20Modeling%20Workshop%20-%

20Load%20Model%20Overview.pdf

[85] C. McLyman, Transformer and Inductor Design Handbook, Third Edition, ser. Electrical

and Computer Engineering Series. Taylor & Francis, 2004. [Online]. Available:

https://books.google.co.uk/books?id=s iMztIS8y4C

[86] G. Berg, “Power-system load representation,” Proceedings of the Institution of Electrical

Engineers, vol. 120, no. 3, pp. 344–348, 1973.

[87] K. Linden, K.n and I. Daut, “Modelling of Load Devices and Studying Load/System Char-

acteristics,” Ph.D. dissertation, Chalmers University of Technology, Sweden, 1992.

[88] K. Schneider, Y. Chen, D. Chassin, R. Pratt, D. Engel, and S. Thompson,

“Modern Grid Initiative Distribution Taxonomy Final Report,” 2008. [Online]. Available:

http://www.gridlabd.org/models/feeders/taxonomy of prototypical feeders.pdf

[89] R. Bravo, D. Martinez, R. Yinger, and L. Gaillac, “Air Conditioner Test Report,” Lawrence

Berkeley National Laboratory, Tech. Rep., 2008.

Bibliography 146

[90] B. Lesieutre, R. Bravo, R. Yinger, D. Chassin, H. Huang, N. Lu, I. Hiskens, and G. Venkatara-

manan, “Final Project Report - Loads Modeling Transmission Research,” Lawrence Berkeley

National Laboratory , Tech. Rep., March 2010.

[91] L. Hajagos and B. Danai, “Laboratory measurements and models of modern loads and their

effect on voltage stability studies,” IEEE Transactions on Power Systems, vol. 13, no. 2, pp.

584–592, 1998.

[92] N. Lu, Y. Xie, Z. Huang, F. Puyleart, and S. Yang, “Load component database of household

appliances and small office equipment,” in 2008 IEEE Power and Energy Society General

Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008, pp. 1–5.

[93] S. Djokic, K. Stockman, J. Milanovic, J. J. M. Desmet, and R. Belmans, “Sensitivity of

AC adjustable speed drives to voltage sags and short interruptions,” IEEE Transactions on

Power Delivery, vol. 20, no. 1, pp. 494–505, 2005.

[94] S. Z. Djokic, J. Desmet, G. Vanalme, J. V. Milanovic, and K. Stockman, “Sensitivity of

personal computers to voltage sags and short interruptions,” IEEE Transactions on Power

Delivery, vol. 20, no. 1, pp. 375–383, Jan 2005.

[95] S. Hardi and I. Daut, “Sensitivity of low voltage consumer equipment to voltage sags,” in

Power Engineering and Optimization Conference (PEOCO), 2010 4th International, June

2010, pp. 396–401.

[96] S. Elphick and V. Smith, “The 230 V CBEMA curve 2014; Preliminary studies,” in Univer-

sities Power Engineering Conference (AUPEC), 2010 20th Australasian, 2010, pp. 1–6.

[97] IEEE, “Bibliography on load models for power flow and dynamic performance simulation,”

IEEE Transactions on Power Systems, vol. 10, no. 1, pp. 523–538, Feb 1995.

[98] ——, “Load representation for dynamic performance analysis of power systems,” IEEE

Transactions on Power Systems, vol. 8, no. 2, pp. 472–482, May 1993.

[99] ——, “Standard load models for power flow and dynamic performance simulation,” IEEE

Transactions on Power Systems, vol. 10, no. 3, pp. 1302–1313, 1995.

[100] S. Elphick, P. Ciufo, and S. Perera, “Supply current characteristics of modern domestic

loads,” in Power Engineering Conference, 2009. AUPEC 2009. Australasian Universities,

2009, pp. 1–6.

[101] K. Stockman, J. Desmet, and R. Belmans, “Impact of Harmonic Voltage Distortion on the

Voltage Sag Behavior of Adjustable Speed Drives,” in Presented at the ICEM 2006, 2006.

Bibliography 147

[102] R. Torquato, Q. Shi, W. Xu, and W. Freitas, “A monte carlo simulation platform for studying

low voltage residential networks,” in 2015 IEEE Power Energy Society General Meeting, July

2015, pp. 1–1.

[103] A. Navarro, L. F. Ochoa, and D. Randles, “Monte carlo-based assessment of pv impacts on

real uk low voltage networks,” in 2013 IEEE Power Energy Society General Meeting, July

2013, pp. 1–5.

[104] D. H. O. McQueen, P. R. Hyland, and S. J. Watson, “Application of a monte carlo simulation

method for predicting voltage regulation on low-voltage networks,” IEEE Transactions on

Power Systems, vol. 20, no. 1, pp. 279–285, Feb 2005.

[105] A. Procopiou, J. Quiros-Tortos, and L. Ochoa, “Hpc-based probabilistic analysis of lv net-

works with evs: Impacts and control,” IEEE Transactions on Smart Grid, vol. PP, no. 99,

pp. 1–1, 2016.

[106] J.-H. Teng, “A direct approach for distribution system load flow solutions,” IEEE Transac-

tions on Power Delivery, vol. 18, no. 3, pp. 882–887, July 2003.

[107] T. H. Chen, M. S. Chen, K. J. Hwang, P. Kotas, and E. A. Chebli, “Distribution system

power flow analysis-a rigid approach,” IEEE Transactions on Power Delivery, vol. 6, no. 3,

pp. 1146–1152, Jul 1991.

[108] F. Teng, “Implementation of a Voltage Sweep Power Flow Method and Comparison with

Other Power Flow Techniques,” Ph.D. dissertation, EEH Power Systems Laboratory Swiss

Federal Institute of Technology (ETH) Zurich, 2014.

[109] S. Ingram, R. Probert, and K. Jackson, “The impact of small scale embedded generation on

the operating parameters of distrbution networks,” DTI, Tech. Rep., 2003.

[110] S. Karmacharya, G. Putrus, C. Underwood, and K. Mahkamov, “Evaluation of domestic elec-

trical demand and its effect on low voltage network,” in 2012 47th International Universities

Power Engineering Conference (UPEC), Sept 2012, pp. 1–4.

[111] P. Trichakis, “Multi Agent Systems for the Active Mangement of Electical Distrbution

Netwroks,” Ph.D. dissertation, Durham University, 2009.

[112] C. Guo, B. Jiang, H. Yuan, Z. Yang, L. Wang, and S. Ren, “Performance comparisons

of parallel power flow solvers on gpu system,” in 2012 IEEE International Conference on

Embedded and Real-Time Computing Systems and Applications, Aug 2012, pp. 232–239.

[113] A. Giannitrapani, S. Paoletti, A. Vicino, and D. Zarrilli, “Optimal allocation of energy

storage systems for voltage control in lv distribution networks,” IEEE Transactions on Smart

Grid, vol. PP, no. 99, pp. 1–1, 2016.

Bibliography 148

[114] S. Nanchian, A. Majumdar, and B. C. Pal, “Three-phase state estimation using hybrid

particle swarm optimization,” IEEE Transactions on Smart Grid, vol. PP, no. 99, pp. 1–1,

2015.

[115] E. Dall’Anese, S. V. Dhople, and G. B. Giannakis, “Photovoltaic inverter controllers seeking

ac optimal power flow solutions,” IEEE Transactions on Power Systems, vol. 31, no. 4, pp.

2809–2823, July 2016.

[116] T. Zang, Z. He, L. Fu, Y. Wang, and Q. Qian, “Adaptive method for harmonic contribu-

tion assessment based on hierarchical k-means clustering and bayesian partial least squares

regression,” IET Generation, Transmission Distribution, vol. 10, no. 13, pp. 3220–3227, 2016.

[117] A. Arefi, A. Abeygunawardana, and G. Ledwich, “A new risk-managed planning of electric

distribution network incorporating customer engagement and temporary solutions,” IEEE

Transactions on Sustainable Energy, vol. 7, no. 4, pp. 1646–1661, Oct 2016.

[118] M. H. F. Wen, R. Arghandeh, A. von Meier, K. Poolla, and V. O. K. Li, “Phase identification

in distribution networks with micro-synchrophasors,” in 2015 IEEE Power Energy Society

General Meeting, July 2015, pp. 1–5.

[119] F. J. Soares, J. A. P. Lopes, and P. M. R. Almeida, “A monte carlo method to evaluate electric

vehicles impacts in distribution networks,” in Innovative Technologies for an Efficient and

Reliable Electricity Supply (CITRES), 2010 IEEE Conference on, Sept 2010, pp. 365–372.

[120] SSE, Statement of Methodology and Charges for Connection to Southern Electic Power Dis-

tribtion PLC’s Electricity Distribution System, 1st ed., Southern Electric Power Distribution

plc, May 2013.

[121] J. Stewart, “Review of WPD unit costs,” Parsosn Brinckerhoff, Tech. Rep., 2013.

[122] “Connection Unit Costs,” http://www.esru.strath.ac.uk/EandE/Web sites/01-

02/RE transmission/connection%20unit%20cost.htm, acessed: 3/2/2015.

[123] T. Frost and P. Mitcheson, “Analysis of Feeder Relief Versus Tollerance Band,” Imperial

College London, Tech. Rep., 2014, Report for the Top and Tail Project.

[124] R. Silversides, T. Green, and M. Merlin, “A high density converter for mid feeder voltage

regulation of low voltage distribution feeders,” in Energy Conversion Congress and Exposition

(ECCE), 2014 IEEE, Sept 2014, pp. 1972–1978.

[125] A. Elserougi, A. S. Abdel-Khalik, S. Ahmed, and A. Massoud, “Active and reactive power

management of photovoltaic-based interline dynamic voltage restorer in low voltage distribu-

tion networks,” in 2012 IEEE Energy Conversion Congress and Exposition (ECCE), 2012,

pp. 3098–3104.

Bibliography 149

[126] K. Turitsyn, P. Sulc, S. Backhaus, and M. Chertkov, “Local control of reactive power by

distributed photovoltaic generators,” in Smart Grid Communications (SmartGridComm),

2010 First IEEE International Conference on, Oct 2010, pp. 79–84.

[127] L. Herman, B. Blazic, and I. Papic, “Voltage profile support in LV distribution networks

with distributed generation,” in Universities Power Engineering Conference (UPEC), 2009

Proceedings of the 44th International, 2009, pp. 1–5.

[128] M. Amin, Y. Arafat, S. Lundberg, and S. Mangold, “Low voltage dc distribution system

compared with 230 v ac,” in Electrical Power and Energy Conference (EPEC), 2011 IEEE,

Oct 2011, pp. 340–345.

[129] M. Fila, G. Taylor, J. Hiscock, M. Irving, and P. Lang, “Flexible voltage control to support

distributed generation in distribution networks,” in Universities Power Engineering Confer-

ence, 2008. UPEC 2008. 43rd International, Sept 2008, pp. 1–5.

[130] T. Stetz, F. Marten, and M. Braun, “Improved low voltage grid-integration of photovoltaic

systems in germany,” Sustainable Energy, IEEE Transactions on, vol. 4, no. 2, pp. 534–542,

April 2013.

[131] M. J. E. Alam, K. Muttaqi, and D. Sutanto, “A comprehensive assessment tool for solar PV

impacts on low voltage three phase distribution networks,” in Developments in Renewable

Energy Technology (ICDRET), 2012 2nd International Conference on the, Jan. 2012, pp.

1–5.

[132] P. Mancarella, C. K. Gan, and G. Strbac, “Evaluation of the impact of electric heat pumps

and distributed CHP on LV networks,” in PowerTech, 2011 IEEE Trondheim, 2011, pp. 1–7.

[133] “Energy saving and equipment life prolongation by voltage reduction,”

http://www.claudelyons.co.uk/energy saving.htm, acessed: 3/2/2015.

[134] The Electricity Safety, Quality and Continuity Regulations 2002, UK Statutory Insruments

Legislation 2665, 2002.

[135] D. Antoniou, A. Tzimas, and S. Rowland, “DC utilization of existing LVAC distribution

cables,” in Electrical Insulation Conference (EIC), 2013 IEEE, June 2013, pp. 518–522.

[136] J. M. Bloemink and T. C. Green, “Required vsc efficiency for zero net-loss distribution net-

work active compensation,” in 2016 IEEE 7th International Symposium on Power Electronics

for Distributed Generation Systems (PEDG), June 2016, pp. 1–8.

[137] D. Rogers and T. Green, “An active-shunt diverter for on-load tap changers,” Power Delivery,

IEEE Transactions on, vol. 28, no. 2, pp. 649–657, Apr. 2013.

Bibliography 150

[138] T. Hakala, T. Lhdeaho, and P. Jrventausta, “Low-voltage dc distribution 2014;utilization

potential in a large distribution network company,” IEEE Transactions on Power Delivery,

vol. 30, no. 4, pp. 1694–1701, Aug 2015.

Appendices

151

Appendix A

Load Goods Table

Table A.1: Classification of Loads in CREST Simulator Worksheet

Device Load Class Device Load Class

Standard Light Bulb L Set Top Box E

Halogen L DVD/VCR E

Fluorescent Strip Light L Games Consoles E

Energy Saving Bulb L Power Supply Units E

LED E HI-FI E

Chest Freezer* M, E Iron H

Fridge-Freezer* M, E Vacuum M

Refrigerator* M, E Telephone Cordless E

Upright Freezer* M, E Electric Oven** H

Washing Machine* H/M, H/E, E Electric Hob** H

Washer-dryer */** H/M, H/E, E Microwave** E

Dishwasher** H/M, H/E, E Kettle* H

Tumble Dryer H/M, H/E, E Water storage Heater* H

Desktops E Electric Water Heater H

Laptops E Electric Shower H

Monitors E Storage Heaters* H

Printers E Other Electric Heating* H

Multi-Function Devices E Heat Pumps* M, E

TV E

* Denotes thermal cycle loads

** Denotes possible thermal cycle loads

152

Appendix B

HV & LV Feeder Impedances

In this section the impedance matrices for both high and low voltage cable, which are most com-

monly used in the UK, are presented. For overhead lines the construction of the supporting poles

and the distances between the phase conductors, effect the phase impedance matrix. Thus to allow

for comparison between the different conductors presented herein conductors the same geometric

spacing is assumed (shown in Figure B.1).

5.2 m

0.9 m

Figure B.1: 11kV Pole

AAAC Hazel (50mm2)

Z �

�����

0.5986� 0.7571i 0.0488� 0.4804i 0.0488� 0.4368i

0.0488� 0.4804i 0.5986� 0.7571i 0.0488� 0.4804i

0.0488� 0.4368i 0.0488� 0.4804i 0.5986� 0.7571i

������km

153

C �

�����

9.048 �3.037 �1.652

�3.037 9.766 �3.037

�1.652 �3.037 9.048

�����nF �km

AAAC Oak (100mm2)

Z �

�����

0.3257� 0.8002i 0.0488� 0.4804i 0.0488� 0.4368i

0.0488� 0.4804i 0.3257� 0.8002i 0.0488� 0.4804i

0.0488� 0.4368i 0.0488� 0.4804i 0.3257� 0.8002i

������km

C �

�����

9.58 �3.34 �1.77

�3.34 10.42 �3.34

�1.77 �3.34 9.58

�����nF �km

AAAC Poplar (200mm2)

Z �

�����

0.1873� 0.8438i 0.0488� 0.4804i 0.0488� 0.4368i

0.0488� 0.4804i 0.1873� 0.8438i 0.0488� 0.4804i

0.0488� 0.4368i 0.0488� 0.4804i 0.1873� 0.8438i

������km

C �

�����

10.44 �3.84 �1.95

�3.84 11.49 �3.84

�1.95 �3.84 10.44

�����nF �km

ACSR (150mm2)

Z �

�����

0.2385� 0.8250i 0.0475� 0.4637i 0.0475� 0.4176i

0.0475� 0.4637i 0.2385� 0.8250i 0.0475� 0.4587i

0.0475� 0.4176i 0.0475� 0.4587i 0.2385� 0.8250i

������km

C �

�����

9.41 �3.66 �2.03

�3.66 10.28 �3.49

�2.03 �3.49 9.41

�����nF �km

B.1 LV Cable

To indicate the frequency dependant effect of the cable impedance, the current density (given a

source current of 1A in the top conductor) is shown in figure B.3.

154

600mm

Figure B.2: 11kV Triplex Single laid direct in ground

Figure B.3: Current Density in 185mm2 Waveform Cableat 50Hz (top) and 5kHz (bottom)

Even at mains frequency the proximity effect and in the 300mm2 cable the skin effect can

be seen, these are not accurately captured in the MATLAB software used for calculating the

impedance matrices, hence the matrices where calculated using finite element software.

155

Appendix C

Direct Load Flow Code

tic; disp('Solving load flow, timestep ...') ; chars=0;

for t = 1 : numel(time)

msg = [num2str(t) ' of ' num2str(numel(time))] ;

fprintf(repmat('\b',1,chars)); fprintf(msg); chars=numel(msg);

k = 0 ;

Pl = Pd(:,t) ;

Ql = Qd(:,t) ;

while 1

W = V ;

Il = conj((Pl + Ql) ./ V );

dV = DLF * Il ;

V = V0 - dV ;

err = max(abs(V-W));

if err <= tol

break

end

k = k + 1 ;

if k >= 20

error([ 'Load flow didnt converge, maxium votlage mismatch %d '...

'greater than tollerance %d at itteration %d, and time %d'],...

err, tol, k, time(t))

end

end

Iline(:,t) = BC * Il ;

Vt(:,t) = V;

It(:,t) = Il;

end

LFt = toc ; fprintf('\nLoad flow took: %d seconds \n',round(LFt));

156