Page 1: RELAI  FREKUENSI ( FREQUENCY  RELAY )

DOK - IBA

Page 2: RELAI  FREKUENSI ( FREQUENCY  RELAY )

RELAI FREKUENSI

BESARAN INPUT DARI RELAI FREKUENSI ADALAHTEGANGAN YANG DIAMBIL DARI TRAFO TEGANGAN [ PT ]

RELAI INI MEMONITOR BESARNYA FREKUENSI SISTEM .

1. RELAI FREKUEN SI KURANG [ UFR ] MEMBANDINGKAN FREKUENSI SISTEM DENGAN FREKUENSI SETTINGNYA . BILA FREKUENSI SISTEM LEBIH KECIL ATAU SAMA DENGAN FREKUENSI SETTING MAKA RELAI AKAN KERJA

2. RELAI FREKUENSI LEBIH BILA FREKUENSI SISTEM LEBIH BEAR ATAU SAMA DENGAN FREKUENSI SETTING MAKA RELAI AKAN KERJA .

DOK - IBA

Page 3: RELAI  FREKUENSI ( FREQUENCY  RELAY )

FUNGSI / APLIKASI UFR

1. DIPASANG PADA PENYULANG TM , UNTUK LOAD SHEDDING SECARA OTOMATIS BILA TERJADI PENURUNAN FREKUENSI SIATEM , AKIBAT KEHILANGAN DAYA PEMBANGKIT . ADA 6 TAHAP PENYETELAN RELAI UFR DI PENYULANG 20 KV PLN YAITU 48,8 – 48,3 Hz

2. DIPASANG DI PEMBANGKIT ,UNTUK MEMISAHKAN PEMBANGKIT DARI SISTEM INTERKONEKSI, BILA TERJADI GANGGUAN PADA SISTEM [ ISLANDING SYSTEM ] DILENGKAPI DENGAN UVR .

FUNGSI / APLIKASI OFR

DIPASANG DI PEMBANGKIT SEBAGAIPENGAMAN KECPATAN LEBIH [ OVERSPEED ]

DOK - IBA

Page 4: RELAI  FREKUENSI ( FREQUENCY  RELAY )

R1

R2

C

f

f

Prinsip kerjaelektrodinamik

Relai frekuensi dengan asas induksi

50

48 52

V

DOK - IBA

Page 5: RELAI  FREKUENSI ( FREQUENCY  RELAY )

T1

T2

T1

T2

T T1

T T2

1

2

T1

T2

V

V

DOK - IBA

Page 6: RELAI  FREKUENSI ( FREQUENCY  RELAY )

sec.0.0.0.0.0.0T1 HzT

1f

11

MFVU

sec.0.0.0.0.0.0T2 Hz2

2 T

1f

0,050.10,20,20,5

1225

10

0000000000

0.050,10,20,20,5

1225

10

0000000000

f1 f1

f2f2f1 ON OFF

ON OFF Pu:do 1:1

f2:f1

Vx=110V=

MFVU210CA00045

f1 f2 Reset Test

sec

)(0,1

t1

sec

)(0,1

t2

DOK - IBA

Page 7: RELAI  FREKUENSI ( FREQUENCY  RELAY )

T1

T2

T1

T2

T T1

T T2

1

2

T1

T2

V

V

RESETSET

SETRESET

SETRESET

RESET

PU DOt2

t1

&

&

V>

TEST

f2:f1

f2:f2

2

2R L

2

1R L

26

27

28

1

3

5

6

4

2

9

11

10

13

12

14RL2-2

RL1-1

RL1-2

RL2-1

f2

f1

>>

>>

+

-0V

17

18V

V=

1

2

DIAGRAM INTERNAL RELAI FREKUENSITIPE MFVU 21 GEC

DOK - IBA

Page 8: RELAI  FREKUENSI ( FREQUENCY  RELAY )

V=

52TC 52TC

52a52a

110V+

-

27

28

17 +

18 -

PT

BUS 20 KV

1

3

9

11

MFVU 21

TRIP PMT 1

TRIP PMT 2

t1

t2

f1

f2

PT

PENGAWATAN

DOK - IBA

Page 9: RELAI  FREKUENSI ( FREQUENCY  RELAY )

250V125V

48VOFF

VA

NORM. FREQ.

FAULT FREQ.

+

-CONTACT

ON

OFF OUTPUTSUPPLY220V

FTS 300 EIL

PORTABLE TESTSET TIPE FTS 300 EIL

6

321

4

5

7

8

910

1112

13

15

14

1. Power Input Connection2. Main Power Switch3. Function Switch4. AC signal Output5. Output Voltage Control6. Output Voltage Meter7. Frequency Range Switch8. Frequency adjust Control9. Frequency meter / Timer10. Contact / DC power

terninal11. DC Power Supplay Control12. Contact mode select

switch13. Contact status Indicator14. Target current control /

range switch15. DC Ammeter

Keterangan Gambar :

DOK - IBA

Page 10: RELAI  FREKUENSI ( FREQUENCY  RELAY )

FUNGSI ALAT KONTROL PADA PANEL DEPAN ALAT UJI FTS 300

1. Power Input Connection Menghubungkan power cord untuk mendapatkan power input pada

alat uji ( suplai 220V).2. Main Power switch Mengontrol input power dan juga sebagai pemutus dalam hal

hubung singkat atau gangguan. Untuk menunjukan bahwa alat uji dienergis maka lampu akan menyala.

3. Function Switch Memilih kondisi kerja dari alat uji4. AC signal Output Memberikan output AC signal dari alat uji5. Output Voltage control Mengatur besarnya AC output signal. Knob “Output control” terdiri

dari dua potensio konsentris, knob luar mengatur besarnya tegangan normal, dan knob dalam mengtur besarnya tegangan gangguan. Tombol Read Fault Voltage memungkinkan tegangan gangguan ada dalam kondisi Set Fault sebelum diswitch ke posisi Test

6. Output Voltage meter Memonitor besarnya tegangan AC signal yang ada pada signal

output.DOK - IBA

Page 11: RELAI  FREKUENSI ( FREQUENCY  RELAY )

7. Frquency range switch Untuk memilih output rentang frekuensi 40 – 70 Hz atau 360 – 440 Hz 8. Frequency Adjust control Potensiometer dengan 15 posisi yang mana mengatur frekuensi

normal dan gangguan9. Frequency meter / Timer Untuk menampilkan frekuensi normal / frekuensi gangguan atau

waktu , tergantung pada kondidsi kerja / mode dari alat uji. Dibawah meter ditunjukan 2 buah lampu Led yang ditandai dengan “Hertz” dan “Second”.

10. Contact DC power supplay terminals Terminal merah dan kuning digunakan untuk memonitor status dray

contact atau scr dalam kondisi Normal ,Set Fault dan Test. Penutupan contact ditandai oleh Led dari kontak closed. Dalam kondisi Test penutupan kontak dapat digunakan untuk menyetop Timer.

11. Dc Power Supplay Control Memilih tegangan output Dc yang ada pada terminal merah dan

hitam. Tiga jenis tegangan yang tersedia yaitu 48V, 125V dan 250V sesuai kebutuhan relai. Indikator On/Reset adalah suatu Led oranye akan menyala bila tegangan ada. Supplay diproteksi terhadap beban lebih,dan dapat direset dengan menekan tombol tekan (Led).

DOK - IBA

Page 12: RELAI  FREKUENSI ( FREQUENCY  RELAY )

12. Contact Mode Select Switch Untuk menentukan apakah timbul atau tidak hubung pendek pada

terminal merah dan kuning, dan akan menyetop timer dalam kondisi Test. Dengan memilih salah satu kontak normally open atau close untuk memonitor test penundaan waktu.

13. Contact status Indicator Led yang menyala untuk menunjukan suatu hubung pendek pada

terminal merah dan kuning.14. Target Current Control/Range Switc Knob luar adalah suatu saklar yang memilih range dari Ammeter

DC yang diinginkan yaitu 0,3 atau 3 A. Knob dalam adalah suatu potensio yang mengtur besarnya arus DC dalam kondisi Target.

15. DC Ammeter Memonitor arus dari internal DC supplay dalam kondisi Normal ,

Set Fault dan Test ,dan mengukur besarnya arus DC pada terminal merah dan kuning dalam kondisi Target.

DOK - IBA

Page 13: RELAI  FREKUENSI ( FREQUENCY  RELAY )

PENGUJIAN INDIVIDUAL RELAI FREKUENSI KURANGTIPE MFVU 21 GEC – TEST SET FTS 300

1. TUJUAN Setelah melaksanakan pengujian siswa diharapkan dapat mengukur: 1. pickup / drop off frequency 2. waktu kerja relai frekuensi

2. ALAT UJI / RELAI 1. Frequency Test Set model FTS 300 (EIL) 2. Relai frekuensi tipe MFVU 21 GEC

3. RANGKAIAN PENGUJIAN 1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian ) 2. Hubungkan sumber tegangan 220V ke alat uji 3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300 sebagai berikut :

DOK - IBA

Page 14: RELAI  FREKUENSI ( FREQUENCY  RELAY )

250V125V

48VOFF

VA

NORM. FREQ.

FAULT FREQ.

+

-CONTACT

ON

OFF OUTPUTSUPPLY220V

FTS 300 EIL

2726

28

18

1

3

17+

-

RANGKAIAN PENGUJIAN RELAI FREKUENSI TIPE MFVU 21 GEC

MFVU 21 GEC

PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI

9

11

DOK - IBA

Page 15: RELAI  FREKUENSI ( FREQUENCY  RELAY )

Kontrol Posisi

Main Power switch . . . . . . . .. . . . . . Off Function Switch . . . . . . . . . . . . . NormalOutput Voltage adjust control . . . . . . . Putar penuh kekiriFrequency range switch . . . . . . . . . . 40 – 70 HzFrequency adjust control . . . . . . . . . Mid rangeContact mode select switch . . . . . . . . NO (open)Target current range switch . . . . . . . . Sesuai yang diinginkanTarget current control . . . . . . . . . . . Putar penuh kekiriDC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan

4. PENGUJIAN PICK UP / DROP OFF FREQUENCY 1. Hidupkan alat uji ( Main power switch pada posisi on ) 2. Putar Output Voltage control ke kanan sampai Voltmeter menunjuk tegangan input nominal relai (100V) 3. Atur normal frequency control sampai frekuensi meter menunjuk harga rated dari normal frekuensi 4. Atur normal frequency control sampai relai mulai pick up ( indikator kontak menyala ) dan naikan frekuensi sampai indikator kontak padam ( reset ) 5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output tegangan yang laian .

DOK - IBA

Page 16: RELAI  FREKUENSI ( FREQUENCY  RELAY )

5. PENGUJIAN WAKTU KERJA RELAI 1. Atur nominal frequency control sehingga frekuensi meter menunjuk harga rated dari normal frekuensi (50Hz) 2. Putar Function swicth ke posisi set fault 3. Atur Fault frequency control sehingga frekuensi meter menunjuk frekuensi yang diinginkan 4. Tekan tombol read voltage control dan atur tegangan gangguan dengan mengatur output voltage control 5. Putar Function switch pada posisi Test maka frekuensi meter akan berubah menjadi Timer (akan mencatat waktu kerja relai ) 6. Ulangi pengujian diatas untuk setting waktu yang lain atau frekuensi gangguan yang lain. 7. Matikan alat uji dan lepas kabel kontrol .

DOK - IBA

Page 17: RELAI  FREKUENSI ( FREQUENCY  RELAY )

A1

6

2345

78

12

910

111211

10987

6

5

1

23

Trip 2

Trip 2Trip 1

Trip 1

PT 110V+

+ _

+

NF921 11

333513

7 7 7

999

UE--UE+

UE+UE--

UE+UE--

33

45 45

45 45 45

4137

3939

37

41

37

3941

29

3131 31

29293333

FC 95 - 22

E

110V DC

AUX. SUPPLY

FCN 950 - 22

INTERNAL DIAGRAM UFRTIPE FCN 950ABB

DOK - IBA

Page 18: RELAI  FREKUENSI ( FREQUENCY  RELAY )

1

0

+_

MODEf(Hz)

dF/dt

t(s)

SAVE

1

2

DC U<

CARA SETTING UFR TIPE FCN 950 MERK ABB

1. Tekan tombol Mode + enable s/d f(Hz) menyala, kemudian tekan tombol Mode + enable s/d lampu 1 (Freq 1) menyala.

2. Untuk menambah / mengurangi nilai setting freq. / waktu dengan cara menekan tombol enable dan tombol + / - .

3. Untuk menyimpan data setting tekan tombol mode + enable s/d lampu save menyala, kemudian tekan tombol enable dan +/- sampai dengan display muncul angka.

Catatan : 1. Untuk merubah fungsi f(Hz) t(sec) Save 2. Tripping freq. 1 muncul indikasi angka 1. Tripping freq 2 muncul angka 2.

Tombol enable ditekan terus dan dengan menekan tombol mode maka fungsi akan berubah

DOK - IBA

ENABLE

Page 19: RELAI  FREKUENSI ( FREQUENCY  RELAY )

PENGUJIAN INDIVIDUAL RELAI FREKUENSI KURANGTIPE FCN 950 ABB – TEST SET FTS 300

1. TUJUAN Setelah melaksanakan pengujian siswa diharapkan dapat mengukur: 1. pickup / drop off frequency 2. waktu kerja relai frekuensi

2. ALAT UJI / RELAI 1. Frequency Test Set model FTS 300 (EIL) 2. Relai frekuensi tipe FCN 950 ABB

3. RANGKAIAN PENGUJIAN 1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian ) 2. Hubungkan sumber tegangan 220V ke alat uji 3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300 sebagai berikut :

DOK - IBA

Page 20: RELAI  FREKUENSI ( FREQUENCY  RELAY )

250V125V

48VOFF

VA

NORM. FREQ.

FAULT FREQ.

+

-CONTACT

ON

OFF OUTPUTSUPPLY220V

FTS 300 EIL

3

1

UE

7

6

UE+

-

RANGKAIAN PENGUJIAN RELAI FREKUENSI TIPE FCN 950 ABB

FCN 950 ABB

PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI

9

8

2

DOK - IBA

Page 21: RELAI  FREKUENSI ( FREQUENCY  RELAY )

Kontrol Posisi

Main Power switch . . . . . . . .. . . . . . Off Function Switch . . . . . . . . . . . . . NormalOutput Voltage adjust control . . . . . . . Putar penuh kekiriFrequency range switch . . . . . . . . . . 40 – 70 HzFrequency adjust control . . . . . . . . . Mid rangeContact mode select switch . . . . . . . . NO (open)Target current range switch . . . . . . . . Sesuai yang diinginkanTarget current control . . . . . . . . . . . Putar penuh kekiriDC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan

4. PENGUJIAN PICK UP / DROP OFF FREQUENCY 1. Hidupkan alat uji ( Main power switch pada posisi on ) 2. Putar Output Voltage control ke kanan sampai Voltmeter menunjuk tegangan input nominal relai (100V) 3. Atur normal frequency control sampai frekuensi meter menunjuk harga rated dari normal frekuensi 4. Atur normal frequency control sampai relai mulai pick up ( indikator kontak menyala ) dan naikan frekuensi sampai indikator kontak padam ( reset ) 5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output tegangan yang laian .

DOK - IBA

Page 22: RELAI  FREKUENSI ( FREQUENCY  RELAY )

5. PENGUJIAN WAKTU KERJA RELAI 1. Atur nominal frequency control sehingga frekuensi meter menunjuk harga rated dari normal frekuensi (50Hz) 2. Putar Function swicth ke posisi set fault 3. Atur Fault frequency control sehingga frekuensi meter menunjuk frekuensi yang diinginkan 4. Tekan tombol read voltage control dan atur tegangan gangguan dengan mengatur output voltage control 5. Putar Function switch pada posisi Test maka frekuensi meter akan berubah menjadi Timer (akan mencatat waktu kerja relai ) 6. Ulangi pengujian diatas untuk setting waktu yang lain atau frekuensi gangguan yang lain. 7. Matikan alat uji dan lepas kabel kontrol .

DOK - IBA

Page 23: RELAI  FREKUENSI ( FREQUENCY  RELAY )

KESIMPULAN ; BANDINGKAN HASIL UJI DENGAN DATA TEKNIK SEHINGGA DIPEROLEH KESIMPULAN BAHWA KONDISI RELAI MASIH STANDAR / NORMAL ATAU MENGALAMI PENURUNAN KUALITAS / CONDONG TIDAK NORMAL DAN PERLU PENGGANTIAN .

DOK - IBA

Page 24: RELAI  FREKUENSI ( FREQUENCY  RELAY )

DOK - IBA