PERATURAN MENTERI TENAGA KERJA RINO. PER-02/MEN/1983
TENTANG INSTALASI ALARM KEBAKARAN OTOMATIK
Ruang lingkup- Perencanaan- Pemasangan,- Pemeriksaan- Pengujian- Pemeliharaan
11/21/2016 Created by ganjar budiarto 2
INSTALASI ALARM KEBAKARAN
OTOMATIK
TUJUANAGAR KEBAKARAN DAPAT TERDETEKSI SEDINI
MUNGKIN, SEHINGGA TINDAKAN YANG DIPERLUKAN DAPAT SEGERA DILAKUKAN.
11/21/2016 Created by ganjar budiarto 3
Detektor
Panel Indikator
Signa
l
alarm
FIRE FOULT
NORMAL
DetektorSigna
l
alarm
FIRE FAULT
NORMAL
11/21/2016 Created by ganjar budiarto 4
11/21/2016 Created by ganjar budiarto 5
AUDIBLE ALARM
MCFA
VISIBLE ALARM
DETEKTOR
ANN
INP
UT
OUTPUT
Panas
Asap
Nyala
HYDRANT
+
11/21/2016 Created by ganjar budiarto 6
1
2
3
4
5
6
7
8
9
10
Merk :Model :Instalatir :Pengesahan No :Tgl :
MCFA
2. Mimic Panel
3. Anounciator Panel
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
11/21/2016 Created by ganjar budiarto 7
JENIS DAN TIPE DETEKTOR
Panas
Asap
Nyala•ULTRA VIOLET
•INFRA RED
•FIXED TEMPERATURE
•RATE OF RISE
•IONIZATION
•OPTIC
•Push bottom •Full down•break glass
Manual
11/21/2016 Created by ganjar budiarto 8
ZONA DETECTION
Panas 40 titik
Asap 20 titik
Nyala 20 titik
•ZONE 1
•ZONE 2
•ZONE 3
EOL
EOL
EOL
Luas tiap zone deteksi - ruang tanpa sekat mak. 2000 m2
- terdapat sekat mak. 1000 m2
11/21/2016 Created by ganjar budiarto 9
INTERCONECTION
FIRE ALARM SYSTEM
MCFA
DETEKTOR
KEBAKARAN
LIFT
Off
POMPA
HYDRANT
supply daya
AC
Off
PRESS FAN
On
SPRINKLER
(FS)
11/21/2016 Created by ganjar budiarto 10
CONTROL FIRE
INDIKATOR
DISCHART
CONTROL
PANEL
BUZER
ALARM
HEATSMOKE
VALVE
INSTALASI PEMADAM KEBAKARAN
AUTOMATIC TOTAL FLOODING SYSTEM
Media pemadam Halon (F, Cl, Br)
!!!!!!!!!!!!Mengandung potensi bahaya
keracunan
HARUS MEMILIKI IJIN K3
11/21/2016 Created by ganjar budiarto 11Double Warning Light
Control
Panel
Manual Abort
StationManual Release
Station
Discharge
Warning SignalCylinders
Heat
Detector
Smoke
Detector
Nozzle
Sirene
Pipe Work
11/21/2016 Created by ganjar budiarto 12
FC-3-1-10 Perfluorobutane C4F10
HBFC-22B-1 Bromodifluoromethane CHF2Br
HCFC Blend A Dichlorotrifluoroethane HCFC-123 (4. 75 %) CHCl2CF2
Chlorodifluoromethane HCFC-22 (82%) CHClF2
Chlorotetrafluoroethane HCFC-124 ( 9. 5%) CHClFCF3
Isopropenyl-1-methylcyclohexene 3. 75 %)
HCFC-124 Chlorotetrafluoroethane CHClFCF3
HFC-125 Pentafluoroethane CHF2CF3
HFC-227 ea Heptafluoropropane CF3CHFCF3
HFC-23 Triflouromethane CHF3
IG-541 Nitrogen (52%) N2
Argon (40%) Ar
Carbondioxide (8%) CO2
MEDIA PEMADAM CLEAN AGENT(Dikutip dari NFPA 2001)
11/21/2016 Created by ganjar budiarto 13
CO2
11/21/2016 Created by ganjar budiarto 14
Clean agent LC 50 NOAEL LOAEL
FC-3-1-10 > 80.0 % 40.0 % > 40.0 %
HBFC-22B-1 10.8 % 2.0 % 3.9 %
HCFC Blend A 64.0 % 10.0 % > 10.0 %
HCFC-124 23-29 % 1.0 % 2.5 %
HFC-125 >70.0 % 7.5 % 10.0 %
HFC-227 ea >80.0 % 9.0 % 10.5 %
HFC-23 > 65.0 % 50 0 % > 50 0 %
IG-541 N/A 43.0 % 7.5 %
Halon 1301 >80.0 % 5.0 % 5.0 %
TABEL 4Toxicity Information
(Dikutip dari NFPA 2001)
LC 50 : Concentration lethal 50 % tikus percobaan mati dalam 4 jamNOAEL : No Observable Adverse Effect Level LOAEL : Lowest Observable Adverse Effect Level
11/21/2016 Created by ganjar budiarto 15
INVESTIGATOR
Media NRL 3M NMER Iferval GLCC Ansul
FC-3-1-10 5.2 5.9 5.0 5.5 - -HFC 124 - - - 6.4 - -HFC 227ea 6.6 - 6.3 5.8 5.9 -HBFC 22B 14.1 - 4.4 3.9 3.9 -HFC 23 12 - 12.6 12 12.7 -HFC-125 9 - 9.4 8.1 - -IG 541 - - - - - 29.1Halon 1301 3.1 3.9 2.9 3 3.5 -
Keterangan NRL:Naval Research laboratory NMERI:New mexico engineering research instituteGLCC: great lakes chemical coMpany
Tabel 5DATA HASIL UJI COBA TERHADAP HEPTANE FLAME
TOTAL FLOODING QUANTITY (W/V: lb/cu ft) (Dikutip dari NFPA 2001)
11/21/2016 Created by ganjar budiarto 16
Media VOLUME % INERTING
i- BUTANE METHANE PROPANE
FC-3-1-10 6.7 10.3HFC 124 - - -HFC 227ea 11.3 - -HBFC 22B1 - - 11.3HFC 23 - 20.2 20.2HFC-125 - 14.7 15.7IG 541 - 43.0 49.0Halon 1301 6.7 - 7.7
Tabel 6
DATA HASIL UJI COBA
INERTING CONCENTRATION (V/V: %)
(Dikutp dari NFPA 2001)
11/21/2016 Created by ganjar budiarto 17
POTENSI PEMANASAN GLOBAL DAN WAKTU TINGGAL DI ATMOSFIR
Nama
Dagang
Nama
Sebutan
Rumus
Kimia
Potensi
Pemanasan
Global
Waktu
Tinggal
di Atmosfir
FE-13
FE-125
FM-200
FE-36
CEA-308
CEA-410
Perfluorohexane
NN-100
Argotec
Argonite
Inergen
Kabut air
Aerosol partikulat padat
HFC 23
HFC 125
HFC 227ea
HFC 236fa
FC-2-1-8
FC-3-1-10
FC-5-1-14
IG-100
IG-01
IG-55
IG-541
CHF3
CF3CHF2
CF3CHFCF3
CF3CH2CF3
C3F8
C4F10
CF
13
0.84
0.6
11.9
-
18.2
-
0
0
0
0.8
264
33
375
209
2600
2600
3200gas permanen
gas permanen
gas permanen
gas permanen
11/21/2016 Created by ganjar budiarto 18
Tekanan mak. 50 barTemp pecah 97o C