The 3AH Vacuum Circuit-Breakers Versatile, High-Performing, Economical
03327_3AH_Englisch 30.09.1999 13:22 Uhr Seite 3
Probedruck
C M Y CM MY CY CMY K
Nowadays circuit-breakers are
used for the most varied of
tasks - they switch all kinds
of devices, including trans-
formers, overhead lines, ca-
bles, capacitors, reactors, mo-
tors, filter circuits and arc
furnaces. They must be suita-
ble for both prolonged idle
times and an extremely high
number of operating cycles.
Low short-circuit ratings re-
quired by supply systems are
up against the demand for
high breaking currents in in-
dustrial applications.
The 3AH circuit-breakersfor medium voltage
The Siemens 3AH vacuum
circuit-breakers cater for all
medium-voltage require-
ments. They are maintenance-
free up to 10,000 operating
cycles, have a long service life
and function with enhanced
reliability.
2
3AH5The economycircuit-breaker formaximumprofitability
Five Circuit-Breakers – any Task
3AH4The frequent-operationcircuit-breaker for a very highnumber of operating cycles
3AH2The frequent-operationcircuit-breaker for a highnumber of operating cycles
3AH3The standardcircuit-breaker for highswitching capacities
3AH1The maintenance-free standardcircuit-breaker
03327_3AH_Englisch 30.09.1999 13:22 Uhr Seite 5
Probedruck
C M Y CM MY CY CMY K
The Five with Three Major Advantages Versatile, Economical and High-Performing
4
Versatile for any application
Thanks to the interplay betweena special contact geometry andcontact material specifically de-veloped for this purpose, the 3AHcircuit-breakers can be applieduniversally for all switching dutiesin the medium-voltage range.Regardless of whether mainte-nance-free standard circuit-breakers, circuit-breakers for aparticularly high number of oper-ating cycles or versions for par-ticularly high switching capacitiesare needed, our 3AH circuit-breakers are the right solutionfor any requirements profile,
whether this involves single-pole or two-pole circuit-breakersfor special applications or three-pole circuit-breakers for standardapplications.
They are suitable for:• rapid load transfer,
synchronizing• auto-reclosing up to 31.5 A• breaking of short-circuit
currents with very highinitial rates-of-rise for the transient recovery voltage
• switching of motorsand generators
• switching of transformersand reactors
• switching of overheadlines and cables
• switching of capacitors• switching of filter circuits
and arc furnaces
Economical in every respect
Our 3AH circuit-breakers allowthe user to economize onboth time and costs. Our 3AHvacuum circuit-breakers soonpay for themselves, particular-ly in systems requiring fre-quent switching.
Even after long idle times, thecircuit-breakers of the 3AHseries do not require any relu-brication up to 10,000 operat-ing cycles and this is all attrib-utable to low-wear materialcombinations at the bearingsand long-lasting greases.
The tight tolerance limits in3AH production rule outimpermissible play. Even forfrequent switching, the 3AHstandard circuit-breaker doesnot require any readjustment– all points in favor ofincreased profitability.
03327_3AH_Englisch 30.09.1999 13:22 Uhr Seite 6
Probedruck
C M Y CM MY CY CMY K
5
Convincing in allapplications
The performance spectrumof the 3AH vacuum circuit-breaker ranges from 7.2 kV to36 kV, covering all of the me-dium-voltage level. And it isprecisely there that the circuit-breakers demonstrate theirefficiency day in day out. Theyfunction reliably in vacuumand thus offer a high level ofavailability. The 3AH circuit-breakers are as suitable forlong idle times as they are fora high number of operatingcycles. This is exactly whythey are so attractive in termsof the stringent demandsplaced on them by the powerdistribution and industrial sec-tors.
The efficiency of these circuit-breakers is clearly attributableto their high standard of qual-ity. And we ensure this qualityright from the preliminarystages: Following assembly,each individual breaker is sub-jected to several hundred op-erating cycles in routine test-ing. The DIN EN ISO 9001certification of our productionprocess also testifies to ourhigh standard of quality, allthe way from developmentthrough manufacture toquality control.
Munich Airport
Arc furnace of a steel plant
Automobile production(Photo VW Plant, Wolfsburg)
Hydropower plant, Xingo(Brazil)
03327_3AH_Englisch 30.09.1999 13:22 Uhr Seite 7
Probedruck
C M Y CM MY CY CMY K
3AH1 – the allrounder in theseries
The 3AH1 is the universal vac-uum circuit-breaker: It com-bines all of the system andproduct advantages of the3AH series, which are signif-icant features for most appli-cations. It covers the conven-tional medium-voltage rangefrom 7.2 to 24 kV, with 10,000operating cycles.
3AH1 and 3AH3 Standard Circuit-Breakers The Allrounders from 7.2 up to 36 kV
3AH3 – maintenance-freefor high switchingcapacities
It requires no maintenance,is extremely efficient andmanages up to 10,000 op-erating cycles. The 3AH3 isused for high short-circuitcurrents up to 63 kA and forrated voltages up to 36 kV.
6
Its compact design permits aswitchgear width of 600 mmat the 12 kV level. The clearstructure of the operatingmechanism permits quick ac-cess to all components. Thisalso allows the secondaryequipment to be supplement-ed at a later stage.
Thanks to its high efficiency,it is the ideal circuit-breakerfor use in generators and forindustrial applications.Naturally, the 3AH3 alsomeets IEC test specifi-cations, as do the othercircuit-breakers.
3AH1: 24 kV, 25 kA, 1250 A 3AH3:17.5 kV, 63 kA, 3150 A
708
662275275
565
190
105
437
60
535
565
192
211
494
105
680275 275
591
776 601�
668
105
03327_3AH_Englisch 30.09.1999 13:22 Uhr Seite 8
Probedruck
C M Y CM MY CY CMY K
3AH2 – allows a highnumber of operatingcycles
In industrial areas in particular,certain applications require ahigh number of operating cy-cles: In the voltage range upto 24 kV, the 3AH2 can handleup to 60,000 operating cycles.
3AH2 and 3AH4 Frequent-Operation Circuit-Breakers The Performers from 7.2 up to 36 kV
3AH4 – the breaker for ahigh number ofoperating cycles
A great number of operatingcycles are required forcertain industrial uses. Forinstance, the switching ofarc furnaces requires morethan 100 operating cyclesper day. The 3AH4 vacuumcircuit-breaker is designedfor this extremely highperformance level up to 36kV: It can manage as manyas 120,000 cycles.
With only minimum mainte-nance work such as greasingof the operating mechanismafter 10,000 switching cyclesand the replacement of thevacuum interrupters after30,000 cycles, the reliabilityof these breakers is ensuredfor their entire service life,despite the high mechanicalstress to which they are sub-jected.
The 3AH4 reliably mastersthis extreme stressthroughout its entire servicelife. The operatingmechanism does notrequire greasing until after10,000 cycles. Furthermore,the vacuum interrupters donot have to be replaced untilafter 30,000 operatingcycles.
680275275
704
773
2 7 51 0 5 1 0 3 0
03327_3AH_Englisch 30.09.1999 13:22 Uhr Seite 9
Probedruck
C M Y CM MY CY CMY K
3AH5 – economical evenfor low switchingcapacities
State-of-the-art vacuumtechnology renders the3AH5 vacuum circuit-breaker economical even inthe low switching capacityrange. Where conventionalcircuit-breakers havehitherto been used, the3AH5 offers suchadvantages as compactdimensions and robustvacuum interrupters.
Compared to conventionalcircuit-breakers, it offers fivetimes the number ofoperating cycles with short-circuit currents.
Particularly for users whothemselves wish to supple-ment their secondary equip-ment or only need to breaklow short-circuit currents,the 3AH5 offers the mostfavorable solution between12 and 17.5 kV up to 25 kAand between 24 and 36 kVup to 16 kA.
3AH5 Economy Circuit-Breakers The Economizerfrom 12 up to 36 kV
3AH5: 12 kV, 20 kA, 1250 A
405160 160
490
9043
5
491
482
491
171
44
8
Special Circuit-Breakers
Single-pole circuit-breakersfor traction power supplyapplications (Fig.)
Rated voltage 27.5 kVRated frequency 50/60 HzRated short-circuit breakingcurrent 25 kA
High-currentcircuit-breaker (no Fig.)
e.g. 3AH3 83 high-currentcircuit-breaker for ratedvoltages up to 17.5 kVRated short-circuit breakingcurrents up to 80 kA
We also supply specialdesigns of the 3AHcircuit-breakers onrequest:
03327_3AH_Englisch 30.09.1999 13:22 Uhr Seite 1
Probedruck
C M Y CM MY CY CMY K
Powerto the
Order No. E50001-U229-A110-X-7600Printed in GermanyDispo-Stelle 3040061D6021 Ra/Mü 101164 WS 08993.
Subject to change without prior noticeSiemens Aktiengesellschaft
BereichEnergieübertragung und -verteilungGeschäftsgebiet MittelspannungP.O. Box 32 20D-91050 Erlangen
http://www.ev.siemens.de