GfS Safetey at doors

GfS – Gesellschaft für Sicherheitstechnik GmbHTempowerkring 15 ∙ 21079 Hamburg ∙ Fon 040-79 01 95-0 ∙ Fax 040-79 01 95 11 ∙ info@gfs-online.com

Assembly instruction GfS e-Bar®

GfS Safety at doors

3

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

Content1. Introduction Seite

1.1.0 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2.0 General functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2.1 Local alarm types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.2.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.3.0 Mechanical versions of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.3.1 Mechatronic versions of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92. Assembly

2.1.0 Mounting instructions of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.1.1 Cut to size with tool kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2.0 Defining the correct length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.3.0 Adjusting main alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 2.4.0 Changing the cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.5.0 Mounting on wooden doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 2.5.1 Mounting on metal doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.5.2 Mounting in combination with security escutcheon (4mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.6.0 Battery operation/mains supply – wiring of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.7.0 Assembly of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.8.0 Placing the stickers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203. Electrical connection

3.1.0 Terminal board GfS e-Bar® 700 71x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3.1.1 Terminal board GfS e-Bar® 700 73x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3.1.2 Terminal board GfS e-Bar® 700 74x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 3.2.0 Wiring diagram GfS e-Bar® 700 71x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 3.2.1 Wiring diagram GfS e-Bar® 700 73x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.2.2 Wiring diagram GfS e-Bar® 700 74x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264. GfS e-Bar® settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.0 Activate automatic alarm switch-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.1 Settings of DIP switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.2 RS485-Interface with MODBUS protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.3 Switching color green/red . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.4 Changing brightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286. Documentation

6.1.0 Service protocol (operator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 6.2.0 Service protocol (installer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

This document has been produced with the utmost care. GfS does not guarantee the accuracy or completeness of the content of this documentation with respect to texts, pictures , references or information contained therein. The company GfS assumes no liability for damages arising directly, indirectly or accidentally from the use of this documentation. The content of this documentation may be adjusted without notice. It shall not lead to any obligations for GfS in the future.© Copyright by GfS – Gesellschaft für Sicherheitstechnik GmbH – Hamburg 2012.This documentation may not be reproduced without written permission of GfS – Gesellschaft für Sicherheitstechnik GmbH in any way, or otherwise used.

*GfS e-Bar® mechanical has no display

4

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

1.0 Introduction1.1.0 Safety instructions

The GfS e-Bar may only be installed acc. to the specifications of the assembly instruction.

• the door must have a smooth running without distortion

• the door leaf should be flat and stiff

• existing door seals must not affect the door function

• the GfS e-Bar® may only be mounted horizontally on doors that open outwards

• the GfS e-Bar® may only be used with approved panic locks and fittings (EN 1125)

• the GfS e-Bar® should be cut to length as required according to the installation instructions

• if used on glass doors, there should be safety glazing

• the GfS e-Bar® is not suitable for use on swing doors

When changing cylinders only use half cylinder with lockable driver! (Type information see technical data)

The assembly must be carried out by qualified staff. After installation the assembly instruction has to be handed over to the operator.

Protect against water and vandalism!

5

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

Function GfS e-Bar® mechanic

700 70*

GfS e-Bar®mechanic with floating contacts

700 71*

GfS e-Bar®mechatronic

700 73*

GfS e-Bar®mechatronic with emergency exit switch700 74*

Communicating display accoustic/visual X X

For door leaf left/right X X X X

Battery-powered (incl. battery control) X

External power supply X X

Main alarm with floating contact X X X

Pre-alarm with floating contact X X X

Single release (local or remote) X X X

Permanent release (local or remote) X X

Visual and acoustic “door-too-long-open” alarm X X

Intrusion alarm X X

Integrated emergency exit switch X

Changing display to green/red X X

RS 485 MODBUS Interface X X

DIP Switch X X

1.2.0 General functions

6

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

1.2.1 Local alarm types

GfS e-Bar® activatedWhen activated the green LEDs of the wired GfS e-Bar is permanently switched on. The green display means that the door is alarm-secured butmight be opened at any time. In case of battery supply, the GfS e-Bar® works in an energy saving mode without background light. The display brightens only for about 15 sec.

Pre-alarmWhile slightly pressing the GfS e-Bar® a red flashing light and an accous-tic alarm (95 dB A/1m) is emitted, which expires as soon as the GfS e-Bar® is released. The moment the pre-alarm turns into a permanent alarm can be adjusted with a little screw (see p. 13). The pre-alarm can be transmitted to a central display.

Main alarmWhen pressing the GfS e-Bar® completely the door is released. At the same time the display flashes an intermittent green light and a permanent alarm sound with 95 dBA. The accoustic and visual alarm can just be switched off by turning the integrated key switch. The main alarm might be transmitted to a central display.

Battery ControlWhen battery operated the GfS e-Bar® a gentle warning signal is emitted every 60 sec. as soon as the voltage drops below 7 V. The display is off. The alarm is active till a new battery is connected or the old battery is empty.

Door-too-long-open-AlarmPre-condition for this feature is a Reed contact which is installed on the door and connected to the GfS e-Bar®. When the single re-lease has been activated by the integrated key switch and the door stays open for more than 15 sec. a gentle ”Door-too-long-open-Alarm” is emitted in an interval of 3 sec. The alarm sound in-dicates that an authorized person has left the door open. As soon as the door is closed the sound is off.

Display: green

Display: red

Display: flashes green

7

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

1.2.2 Operation

ResetBy briefly turning the key clockwise the main alarm is deactivated. The key needs to be turned by 90° and back. The impulse should be no longer than 1 sec. 15 sec. after this operation the GfS e-Bar® is alarm secured again which is indicated by a green display (mains supply). When battery operated the green display fades away after another 15 sec.. If a reed contact is installed the GfS e-Bar® will be alarm secured the moment the door closes.

Single releaseBy using the integrated key switch or by employing an external access control system (p. 22, p.23), an authorized person may pass the emergen-cy exit once without causing an alarm.By briefly turning the key clockwise the single release mode is triggered. The key needs to be turned by 90° and back. The impulse should be no longer than 1 sec. If a reed contact is installed the GfS e-Bar® will be alarm secured the moment the door closes. If the door is kept open for more than 15 sec. a gentle “Door-too-long-open-Alarm” resounds till the door is closed again.

Permanent releaseBy using the integrated key switch an authorized person may deactivate the GfS e-Bar® in order to pass the emergency exit for a longer period of time. The permanent release is triggered by turning the key clockwise for at leat 5 sec. The key needs to be turned by 90° and back.The status is communicated by a raising and lowering brightness of the green display. The key should be removed. The permanent release is activated till thekey is turned again by min. 90° for max. 1 sec. and removed afterwards. Alternatively the permanent release can be set by access control systems, timer etc. (p. 22, p. 23).

RESETPERMANENT OPEN

(hold 5 sec.)

GfS Hamburg ∙ www.gfs-online.com

right

RESET

(hold 5 sec.)

PERMANENT OPEN

GfS Hamburg ∙ www.gfs-online.com

left

RESETPERMANENT OPEN

(hold 5 sec.)

GfS Hamburg ∙ www.gfs-online.com

right

RESET

(hold 5 sec.)

PERMANENT OPEN

GfS Hamburg ∙ www.gfs-online.com

left

8

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

1.3.0 Mechanical versions of GfS e-Bar®

1. GfS e-Bar® mechanic This model is a push bar incl. a picto describing the operation of the GfS e-Bar®. Neither contacts nor electric functions areincluded. The GfS e-Bar® mechanic will be supplied in three different lengths, which might be shortened individually, in order to adjust the length to the width of the door.

Length in mm To be shortened by mm Art. No.

970 180 700 700

1130 160 700 703

1290 160 700 705

2. GfS e-Bar® mechanic with floating contactsThis model is a push bar with floating contacts to generate information on the usage of the push bar.The items will be delivered with a picto describing the operation of the GfS e-Bar®. The GfS e-Bar® mechanic will be supplied in three different lengths, which might be shortened individually, in order to adjust the length to the width of the door.

Length in mm To be shortened by mm Art. No.

970 180 700 710

1130 160 700 713

1290 160 700 715

970/1130/1290

1515

6.5

71.3

84.7

9

To be shortened by 180/160/160 mmDistance between fastening points

9

970/1130/1290

1515

9

43/5

0

71.3

84.7

Display for GfS e-Bar® mechatronic

To be shortened by 180/160/160 mmDistance between fastening points

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

1.3.1 Mechatronic versions of GfS e-Bar®

1. GfS e-Bar® with integrated alarm (battery operated and/or mains supplied)This model works either with a 9 V battery which is controlled by the PCB or with mains supply of 10−30 V/DC. The battery control function checks every 10 hours the voltage. If the voltage drops below 7V, all 60 seconds an accoustic alarm is emitted. The battery has to be changed. When battery operated the GfS e-Bar® works in an energy saving mode which basically means that the green LEDs of the display are permanently switched off. The intelligent PCB recognizes when an external power supply is connected to the GfS e-Bar®. The communicating display shines permanently green. It indicates that the emergency exit is alarm secured. Delivery includes 1 9V battery, 2 keys, 1 picto for display and key switch as well as one sticker explaining the operation on the door.

Length in mm To be shortened by mm Art. No.

970 180 700 730

1130 160 700 733

1290 160 700 735

Power supply surface mounted 901 366

Power supply flush mounted 700 006

2. GfS e-Bar® with integrated alarm and emergency exit switch for opening electrically locked doorsThe GfS e-Bar with integrated emergency exit switch is operated at 10−30 V/DC which is either supplied by an external power supply or the FWS-02 (Emergency exit control unit). The integrated emergency exit switch with 2 opening contacts might be connected to the emergency exit control unit with a max. load of 3A. Adiitionally it is recommended to install a reed contact which offers additional features such as immediate activation after the door has been closed and door-too-long-open-alarm.Delivery includes 1 integrated emergency exit switch, 2 keys, 1 picto for the display and the key switch as well as one sticker explaining the operation on the door.

Length in mm To be shortened by mm Art. No.

970 180 700 740

1130 160 700 743

1290 160 700 745

Power supply surface mounted 901 366

Power supply flush mounted 700 006

10

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.0 Assembly2.1.0 Mounting instructions of GfS e-Bar®

Countersunk screw M3 x 8 Clamping bolt

Lever arm

Lever arm

Lever arm

Cylinder head screw M5 x 20

2a

7a9

4

7

7

7

10

1a

1

2

push bar

base profil

While pressing the push bar profile 4 remove the cylinder head screw M5 x 20 1 .Tear the cover hood 1a out of the bayonet joint towards the lock side.

GfS e-Bar® mechatronicRemove the screw M3 x 8 9 , unlock the cover hood by turning the key clockwise 2a .

GfS e-Bar® mechanic While the push bar is pressed 4 remove the cylinder head screw M5 x 8. Tear the cover hood 2 towards the hinge side.

Remove the protective shield 10 .

Lift the push bar profile 4 up to its maximum. Hold the lever arm 7 with one hand and remove the push bar profile 4 from the clamping bolt in opposite direction 7a .

11

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.1.1 Cut to size with tool kit (not included in scope of delivery)

Connection circuit board(only mechatronic versions)

Assembly/disassembly

4 x M4 x 4 6

7

5

8

Length of base profile

1Shortening tool for base profileArt. No. 770 712

Length of push bar profile

2

Bow saw

Bench vice

Shortening tool for push bar profile

Lug

Bench vice

LugLD/LT ± 1 mm

Order length Length of base profile Length of push bar profileBA 940

BA-67 mm BA-104 mmBA 1100BA 1260

Push bar profile LP ±1 mm

Base Profile LB ± 1 mm

Standard length

Standard length

165always to be shortenedon the hinge side

Just mechatronic versions:Remove carefully the plug of the ribbon cable 5 from the connection circuit board and keep it safe in the base profile. Loosen the slotted grub screws M4x4 6 and remove them together with the console. Keep the shims 8 as you need them again for the assembly.Clamp the profiles in a vice. The jaws of the vice serve as stop for the shortening tool.

ATTENTION:The clamping area should be protected by wood/plastic material in order to avoid scratches on the surface of the profile! Carefully cut the profile with a conventional metal saw along the lug. A straight cut is easier when pressing the blade slightly against the lug. After shortening the profile burr the edges carefully in order to avoid injuries.

ATTENTION:Do not use "lubricants and coolants" when shortening the mechatronic versions od the GfS e-Bar®. Metal chips must not stay in the GfS e-Bar®. Danger of short-circuit! After shortening insert the console 7 into the base profile. Place the shims 8 (0,8 mm thickness) between the console and the base profile.

IMPORTANT:The shims 8 are designed to avoid pressure marks and deformations by the clamp-connection. Fasten the four cylinder pins M4x4 6 with a torque between 0.4 Nm and max. 0.5 Nm! Only mechatronic versions: Insert carefully the plug of the ribbon cable 5 into the connection circuit board.

Tool kit

12

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.2.0 Defining the correct length

6.5

15

158 300

83.5

50

Distance between fastening points

Front vision

Rule of thumb for defining the correct length:door inside width - 2x backset + 2x lockplate thickness + 30mm = GfS e-Bar® length

Distance between fastening points

Door inside width

Door

han

dle

heig

ht

Order length LG = BA + 30

Center of square follower

Order lengths Max. shortening length

970 mm 180 mm

1130 mm 160 mm

1290 mm 160 mm

BA

DM DM

Distance

Square follower

Backset

Front plate shape

Forend plate width

Forend plate length

13

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.3.0 Adjust pre- and main alarm

Screw to adjust alarm setting

Hint: Pre-alarm is not adjustable(preset in the factory).

tighten screw, alarm starts later loosen screw,

alarm starts earlier

Siren

Hall sensor for alarm

Hall sensor for pre-alarm

Dip switch 1– 8

14

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.4.0 Changing the cylinder

Mounting European profile cylinder (PHZ) Mounting Swiss round cylinder (RZ)

Use right drill holes

Use left drill holes

Battery holder

Attention:Use European profile cylinder with lockable cam. Remove key, put cam on 180°!

15

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.5.0 Mounting on wooden doors (Metal cover plate 770 013 for wooden doors are not included in shipment)

X

Image ABA

19 Ø 18

38

43/5

0

21.5/

25

Sunk wood screw Ø 5 x 25

Cylinder head screwwood screw ø 5 x 25

Hinge side Lockside

Standard flat steel base plate

Cover plate lock side

Cover plate hinge sideThickness depending on escutcheon 3 mm, 4 mm, 6 mm)

Counter sunk screw M4x8(respect max. length of screw)

Shoulder bolt M4 x 4

Attention:When assembling pay attention to the orientation of the socket. Cam has to show downwards

Detail X

max. 10

13

Image B

Attention: Cover clip of the standard flat steel base plate has to be mounted before the cover hood is mounted.

16

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.5.1 Mounting on metal doors

Drillings for suitableriveting nuts M5

Cylinder head screw M5 x12

Image ABA 43

/50

21.5/

25

43/5

0

X

max. 10

13

Image B

shoulder bolt M4 x 4

Attention:When assembling pay attention to the orientation of the socket. Cam has to show downwards

Detail X

17

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.5.2 Mounting in combination with security escutcheon (4 mm)

Hinge side Lockside

Cover plate hinge side

Counter sunk screw M4x8 (respect max. length of screw)

X

X

BA

Ø 18

43/5

0

21.5/

25

Cylinder head screw wood screw ø 5 x 25

Escutcheon for GfS e-Bar®

Ø 18

BA 43/5

0

43/5

0

21.5/

25

Escutcheon for GfS e-Bar®

Cylinder head screw M5 x 25

Drillings for suitableriveting nuts M5

Standard flat steel base plate

18

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.6.0 Battery operation/mains supply – wiring of GfS e-Bar®

Installation without cables Installation with cables

Plug with jumper. Only necessary for battery operation. Remove plug when mains supply.

Connection cable 12-wireswith tieGfS Art. No. 770 719

Cable must be fixed with cable tie

Cable length

drilling for connecting cable Ø 10

drilling for connecting cable Ø 10

100 ± 15 mm

Door

han

dle

heig

ht

Door

han

dle

heig

ht

15

15

0.5

0.5

DIN left

DIN right

19

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.7.0 Assembly of GfS e-Bar®

Clamping bolts 3

Soft counter pressure 4

Lever arm 1

Lever arm 1

Cylinder head screw M5 x 20 8

Sunk screw M3 x 8 9

push bar

hinge sideLock side

base profile

27

5

7

6

Lift the lever arms 1 up to its maximum. Hold the lever arm with one hand and pull the push bar profile 2 from the hinge side on the clamping bolt 3 until the push bar profile is engaged. Lift the lever arm with one hand, give some counter pressure on the push bar profile 4 with the other hand in order to avoid that the push bar snaps-out again.

Important: The push bar profile must smoothly but noticably snap-in. Do not force the push bar profile. In case of doubt try again.

Put the protective shield 5 on the support bracket.

Insert the cover hood 7 in the bayonet joint and push it to the end stop. Fix the cover hood with cylinder head screw M5 x 20 8 .a) Mechatronic versions 6 : turn the key anti-clockwise. A noticable click indicates that the cover hood is locked. b) Mechanic versions: Fix cover hoods with M5x8 cylinder head screws (like lock side).

20

IN CASE OF EMERGENCY

PUSH TO OPENwww.gfs-online.com

EMERGENCY EXIT – ALARM PROTECTED

IN CASE OF EMERGENCY

PUSH TO OPENwww.gfs-online.com

EMERGENCY EXIT – ALARM PROTECTED

IN CASE OF EMERGENCY

PUSH TO OPENwww.gfs-online.com

EMERGENCY EXIT – ALARM PROTECTED

RESETPERMANENT OPEN

(hold 5 sec.)

GfS Hamburg ∙ www.gfs-online.com

right

RESET

(hold 5 sec.)

PERMANENT OPEN

GfS Hamburg ∙ www.gfs-online.com

left

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

2.8.0 Placing the stickers

21

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

3. Electrical connection 3.1.0 Terminal board GfS e-Bar® 700 71x

Clamp Signal Wire colour Function

1 NO Relay 1: Pre-alarm

2 NC Relay 1: Pre-alarm

3 COM Relay 1: Pre-alarm

4 NO Relay 2: Main-alarm

5 NC Relay 2: Main-alarm

6 COM Relay 2: Main-alarm

17/18 External key switch message out

19/20 External key switch wiring in

R2–N

O

R2–N

C

R2–C

OM

R1–N

O

R1–N

C

R1–C

OM

1 2 3 4 5 6

1718

1920

22

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

3.1.1 Terminal board GfS e-Bar® 700 73x

Clamp Signal Color Function

1 OV white External door reed contact, recommended otherwise jumper (1-2)

2 GND black Mains supply GND

3 OV brown DIP 8 OFF: DIMM at 10% luminiscence (prgrammable see page) DIP 8 ON: Radar triggered pre-alarm

4 +5V green RS485 A Interface (MODBUS)

5 +5V yellow RS485 B Interface (MODBUS)

6 + 10 V – 30 V red Mains supply 10 V–30 V DC

7 OV violett Electric pulse for single release or permanent signal for permanent opening (2–7) – not avilable when battery operated

8 NC grey Output relay: alarm 30 V/850 mA

9 COM blue Output relay: alarm 30 V/850 mA

10 NO pink Output relay: alarm 30 V/850 mA

11 COM red/blue Output relay: pre-alarm 30 V/850 mA. When pre-alarm contact is opened

12 NO grey/pink Output relay: pre-alarm 30 V/850 mA. When pre-alarm contact is closed

13 COM Internal emergency exit switch 1 min AWG24

Cable diameter LIVY 4x 0,25 14 COM Internal emergency exit switch 2 min AWG24

15 NO Internal emergency exit switch 1 min AWG24

16 NO Internal emergency exit switch 2 min AWG24

17 +9 V +9 V Battery supply

18 GND black GND Battery supply GND

19 GND Key Switch (Reset/Programming)

20 OV Key Switch (Reset/Programming)

}

NC

NO

1

2

4

Incoming Connection COMMON

Normally closed

Normally open

Switching circuit F4

1 2 3 4 5 6 7 8 9 10 11 12

13 14 15 16C1 C2 N1 N2

1718

1920

JP 1

Rele

ase

RC R2–N

C

GN

D

R2–C

DIM

M

R2–N

0

A R1–C

B R1–N

O

UB

Schl

GND

GND

+ 9 V-Bat

23

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

3.1.2 Terminal board GfS e-Bar® 700 74x

FWS

02G

fS e

-Bar

®

31 32

•1

•2

•3

•4

•5

•6

•7

•8

•9

•10

•11

•12

•27

•28

•29

•30

•31

•32

•33

•34

•35

•36

•37

•38

•13

•14

•15

•16

•17

•18

•19

•20

•21

•22

•23

•24

•25

•26

160

mA/

T

on off

1 A/

T

PENL

15

37

26

48

Stan

dard

cl

amps

Cone

ctin

g cl

amps

fo

r net

wor

k D

IP s

witc

h

R1-NO

R1-C

R2-NO

R2-C

R2-NC

Fern

UB

B

A

DIMM

GND

TK

1211

109

87

65

43

21

+ BU

Bat

t

GND

GND

Schl

17181920

C1C2

N1N2

1615

1413

24

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

3.2.0 Wiring diagram GfS e-Bar® 700 71x

Cable with 6 wires LIYY 6 x 0,14

2

3

1

5

6

4

1 2 3 4 5 6

1718

1920

Connection Pre- and Main-alarm GfS e-Bar® 70071x

Floating contact (see page 21) 30 V/300 mA

Floating contact (see page 21) 30 V/300 mA

NC

NC

NO

NO

C

C

Cable with 6 polesLIYY 6 x 0,14

pre-alarm

main-alarm

External key switch17/18 Key switch message (out)19/20 Key switch wiring (in)

A

25

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

12-pole connection cable LIYY 6 x 0,14Art No: 770 719

Jumper 1: Resistance 120 Ohm for RS 485

without reed contact put jumper on 1–2

NOTAUSGANG ALARMGESICHERT

Cable with 12 wiresArt. No. 770 719

Important:All input contacts are 0V shortcut to ground

TK

blackMains supply GNDGND – 2

greenRS 485 A Interface MODBUSRS 485 A 4

blueMain alarm

Pre-alarm

9

white Door reed contact (automatic activation, intrusion alarm)

0 Volt GND 11

violet Electric pulse for single release or permanent signal for permanent opening (2–7) – not available when battery operated

0 Volt GND 7

red/blue11

redMains supply (plus terminal) 10 – 30 V/DC 10–30 V/DC + 6

yellowRS 485 B Interface MODBUSRS 485 A 5

punk10

brown DIP 8 OFF: DIMM at 10% luminiscence DIP 8 ON: Radar triggered pre-alarm

0 Volt GND 3

greyNC

NO

NO

C

C

Floating contact30 V/850 mA

see p. 30

Floating contact30 V/850 mA

see p. 30

8

gray/pink12

2

1

2

1

Timer Acces Control

System Push buttom

switch

1 2 3 4 5 6 7 8 9 10 11 12

13 14 15 16C1 C2 N1 N2

1718

1920

JP 1

Remove connector (A) Insert connector (B) of connecting cable Art. No. 770719

A

3.2.1 Wiring diagram GfS e-Bar® 700 73x

26

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

without reed contact put jumper on 1–2

Important: All input contacts are 0 V shortcut to ground

Electric lock for electrically secured emergency exits

blackMains supply GNDGND – 2

greenRS 485 A Interface MODBUSRS 485 A 4

blueMain-alarm

Pre-alarm

External connecting terminal

9

15

16

white Door reed contact (automatic activation, intrusion alarm)

0 Volt GND 1

violett Electric pulse for single release or permanent signal for permanent opening (2-7)

0 Volt GND 7

red/blue11

redMains supply (plus terminal) 10 – 30 V/DC 10–30 V/DC + 6

yellowRS 485 A Interface MODBUSRS 485 A 5

pink10

brown0 Volt GND 3

greyNC

NC

NC

NO

NO

C

C

C

C

Floating contact30 V/850 mA

see p. 30

Internal emergency exit switch GfS e-Bar® 700 74x

Floating contact see page 22

30 V/850 mA

8

13

14

grey/pink12

2

1

+

2

Timer Acces Control

System Push buttom

Switch

NOTAUSGANG ALARMGESICHERT

ZVCable with 12 wires Art. No. 770719

Cable with 4 wires LIYY 4 x 0,25

TK

Cable with 4 wires LIYY 12 x 0,14 Art. No. 770 719

ZV

1 2 3 4 5 6 7 8 9 10 11 12

13 14 15 16C1 C2 N1 N2

1718

1920

JP 1

Jumper 1: Resistance 120 Ohm for RS 485

Remove jumper (A) Insert connector (B) of connecting cable Art. No. 770 719

A

DIP 8 OFF: DIMM at 10% luminiscence (programmable see page 27), DIP 8 ON: Radar triggered pre-alarm 1

3.2.2 Wiring diagram GfS e-Bar® 700 74x

Cable with 12 wires LIYY 12 x 0,14 Art. No. 770 719

27

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

4.0 GfS e-Bar® settings4.1.0 Activate automatic alarm switch-off If DIP switch 5 is ON the alarm will automatically switched-off after 3 minutes. If DIP switch 5 is OFF a permanente alarm will resound.

4.1.1 Settings of DIP switch

DIP-Nr. Function ON OFF (factory setting)

1 Hold open time + 6 sec.2 Hold open time + 12 sec.3 Back-light while permanent opening no backlight LEDs raising and lowering4 Silent alarm no alarm alarm5 Automatic alarm switch-off 3 min permanent alarm6 Intrusion alarm activated deactivated7 Alarm delay 15 sec. deactivated8 Special options Pre-alarm triggered by radar DIM at 10%

Attention: The settings of the DIP switch will just be changed after the GfS e-Bar® has been switched-on again. The DIP switch setting will be overwritten by a MODBUS command.

4.1.2 RS-485 interface with MODBUS protocol

Up to 127 GfS e-Bar® can be networked. The MODBUS protocol which works with a RS-485 interface offers bi-directional communication. It is thus possibile to monitor and address up to 127 GfS e-Bar® . The communication between different devices is managed by customized masters.

4.1.3 Switching color green/red

When working with mains supply it is up to the operator/dealer to define the color code of the GfS e-Bar®. The following steps have to be taken: • Switch-off the power supply of the GfS e-Bar® and remove the battery. Wait for 10 sec. • Connect the GfS e-Bar® again • Turn the key clockwise by 90° and wait for approx. 5 sec till the display indicates that the GfS e-Bar® is deactivated (permanent opening) • During the following 60 sec press the GfS e-Bar® for about 15 sec. • The color changes every 2 sec. – three times from green to red and back to green • Release the GfS e-Bar® when the desired color shines and confirm this choice by briefly turning the key clockise by 90° • Now the chosen color remains active • The GfS e-Bar® is not in the programming mode anymore but deactivated (permanent opening) .

In case that the color shall be changed again, you have to restart the process all over again (disconnect the power supply).

4.1.4 Changing brightness

• Switch-off the GfS e-Bar®• Press entirely the GfS e-Bar® • Switch-on the GfS e-Bar® again while keeping the GfS e-Bar® pressed for at least 10 sec. untill all LEDs shine• Release the GfS e-Bar® and oberserve LEDs• Brightness of LEDs raise and lower for max. 3 times. A too long wait stops the programming mode automatically the desired brightness is

achieved confirm the result with the integrated key switch for at least 1 sec.• Now the value is stored for future operation, the GfS e-Bar leaves the programming mode automatically

Hint: The brightness and darkness need to be confirmed within 1 sec., enough time to operate the key switch.

28

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

Power supply 9 V battery or 12–30 V/DC power supply

Current draw in battery operation mode Door alarm secured 14 µADoor open 0,5 mA, briefly 90 mA short-term, intermittent Pre-alarm 190 mAMain-alarm in average 160 mA intermittent

Current draw with external power supply (mains supply or FWS 02)Door alarm secured 130 mADoor open 6 mA, briefly 130 mA short-trem intermittentPre-alarm 235 mAMain-alarm in average 190mA intermittent

Battery low signal below 7 V (measured during operation)

Automatic alarm switch off DIP 5 ON: 3 minutes

Turning angle 40° standard 9 mm pin 30° optional 9 mm pin 45° optional 9 mm pin

Power supply 230 V AC/12 – 30 V DC

Reed contact with sabatoge line, incl. 2 m cable, surface or flush mounted (Art-No. 930 110/930 210)

External connection cable for GfS e-Bar® GfS e-Bar® 70071x/70073x 12 wires, 12 x 0,14 LIYY (Art. No. 770 719) GfS e-Bar® 700 74x 20 wires, 20 x 0,25 LIYY

Cable sleeves Metal doors KÜ 480 (Art. No. 901 802) Cable sleeve with housing, INOX Cable sleeve 370 mm, Housing 22 x 480 x 17 mm

Wood doors KÜ-R 480 (Art. No. 901 902) Cable sleeve with housing, INOX Cable sleeve 370 mm, Housing 22 x 480 x 17 mm

Cylinder 30/10 mm European half cylinder with lockable driver

5.0 Technical data

29

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

GfS e-Bar® ______________________________________________________________________________________________

Building ________________________________________________________________________________________________

Manufacturer of lock/lock type ______________________________________________________________________________

Panic function D E B E-SV B-SV

The installation was done properly.

Lock, lock plate and door hardware form a system acc. to EN 1125

The system has been tested and works properly

The door can be unlocked with little effort (< 80 N)

Further comments concerning the building environment:

After installation the escape route is fully accessible

The system has been verified and approved

City, Date Company (stamp)

Signature

6.0 Documentation 6.1.0 Service protocol (operator)

30

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

GfS e-Bar® ______________________________________________________________________________________________

Building ________________________________________________________________________________________________

Manufacturer of lock/lock type ______________________________________________________________________________

Panic function D E B E-SV B-SV

The installer has informed the operator of the following:

Function and use

Resetting the alarm

Special functions

Possibility to transmit the alarm to a central display

The operator received the installation and operating manual

The operator has been informed about the required maintenance activities:

– Battery control (at least 1 per month)

– System check (at least 1 per year)

– Visual check (at least 1 per month)

City, Date Company (stamp)

Signature

6.0 Documentation6.1.0 Service protocol (installer)

31

7007

xx_M

A_Gf

S e-

Bar_

0518

_GB

GfS Safety at doors

GfS – Gesellschaft für Sicherheitstechnik GmbHTempowerkring 15 ∙ 21079 Hamburg ∙ Fon 040-79 01 95-0 ∙ Fax 040-79 01 95 11 ∙ info@gfs-online.com