Assembly instruction GfS e-Bar®
3
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
Content1. Introduction Seite
1.1.0 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2.0 General functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2.1 Local alarm types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.2.2 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 1.3.0 Mechanical versions of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.3.1 Mechatronic versions of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92. Assembly
2.1.0 Mounting instructions of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2.1.1 Cut to size with tool kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 2.2.0 Defining the correct length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2.3.0 Adjusting main alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 2.4.0 Changing the cylinder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 2.5.0 Mounting on wooden doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 2.5.1 Mounting on metal doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 2.5.2 Mounting in combination with security escutcheon (4mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 2.6.0 Battery operation/mains supply – wiring of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 2.7.0 Assembly of GfS e-Bar® . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 2.8.0 Placing the stickers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203. Electrical connection
3.1.0 Terminal board GfS e-Bar® 700 71x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 3.1.1 Terminal board GfS e-Bar® 700 73x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 3.1.2 Terminal board GfS e-Bar® 700 74x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 3.2.0 Wiring diagram GfS e-Bar® 700 71x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 3.2.1 Wiring diagram GfS e-Bar® 700 73x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.2.2 Wiring diagram GfS e-Bar® 700 74x . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264. GfS e-Bar® settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.0 Activate automatic alarm switch-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.1 Settings of DIP switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.2 RS485-Interface with MODBUS protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.3 Switching color green/red . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 4.1.4 Changing brightness . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286. Documentation
6.1.0 Service protocol (operator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 6.2.0 Service protocol (installer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
This document has been produced with the utmost care. GfS does not guarantee the accuracy or completeness of the content of this documentation with respect to texts, pictures , references or information contained therein. The company GfS assumes no liability for damages arising directly, indirectly or accidentally from the use of this documentation. The content of this documentation may be adjusted without notice. It shall not lead to any obligations for GfS in the future.© Copyright by GfS – Gesellschaft für Sicherheitstechnik GmbH – Hamburg 2012.This documentation may not be reproduced without written permission of GfS – Gesellschaft für Sicherheitstechnik GmbH in any way, or otherwise used.
*GfS e-Bar® mechanical has no display
4
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
1.0 Introduction1.1.0 Safety instructions
The GfS e-Bar may only be installed acc. to the specifications of the assembly instruction.
• the door must have a smooth running without distortion
• the door leaf should be flat and stiff
• existing door seals must not affect the door function
• the GfS e-Bar® may only be mounted horizontally on doors that open outwards
• the GfS e-Bar® may only be used with approved panic locks and fittings (EN 1125)
• the GfS e-Bar® should be cut to length as required according to the installation instructions
• if used on glass doors, there should be safety glazing
• the GfS e-Bar® is not suitable for use on swing doors
When changing cylinders only use half cylinder with lockable driver! (Type information see technical data)
The assembly must be carried out by qualified staff. After installation the assembly instruction has to be handed over to the operator.
Protect against water and vandalism!
5
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
Function GfS e-Bar® mechanic
700 70*
GfS e-Bar®mechanic with floating contacts
700 71*
GfS e-Bar®mechatronic
700 73*
GfS e-Bar®mechatronic with emergency exit switch700 74*
Communicating display accoustic/visual X X
For door leaf left/right X X X X
Battery-powered (incl. battery control) X
External power supply X X
Main alarm with floating contact X X X
Pre-alarm with floating contact X X X
Single release (local or remote) X X X
Permanent release (local or remote) X X
Visual and acoustic “door-too-long-open” alarm X X
Intrusion alarm X X
Integrated emergency exit switch X
Changing display to green/red X X
RS 485 MODBUS Interface X X
DIP Switch X X
1.2.0 General functions
6
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
1.2.1 Local alarm types
GfS e-Bar® activatedWhen activated the green LEDs of the wired GfS e-Bar is permanently switched on. The green display means that the door is alarm-secured butmight be opened at any time. In case of battery supply, the GfS e-Bar® works in an energy saving mode without background light. The display brightens only for about 15 sec.
Pre-alarmWhile slightly pressing the GfS e-Bar® a red flashing light and an accous-tic alarm (95 dB A/1m) is emitted, which expires as soon as the GfS e-Bar® is released. The moment the pre-alarm turns into a permanent alarm can be adjusted with a little screw (see p. 13). The pre-alarm can be transmitted to a central display.
Main alarmWhen pressing the GfS e-Bar® completely the door is released. At the same time the display flashes an intermittent green light and a permanent alarm sound with 95 dBA. The accoustic and visual alarm can just be switched off by turning the integrated key switch. The main alarm might be transmitted to a central display.
Battery ControlWhen battery operated the GfS e-Bar® a gentle warning signal is emitted every 60 sec. as soon as the voltage drops below 7 V. The display is off. The alarm is active till a new battery is connected or the old battery is empty.
Door-too-long-open-AlarmPre-condition for this feature is a Reed contact which is installed on the door and connected to the GfS e-Bar®. When the single re-lease has been activated by the integrated key switch and the door stays open for more than 15 sec. a gentle ”Door-too-long-open-Alarm” is emitted in an interval of 3 sec. The alarm sound in-dicates that an authorized person has left the door open. As soon as the door is closed the sound is off.
Display: green
Display: red
Display: flashes green
7
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
1.2.2 Operation
ResetBy briefly turning the key clockwise the main alarm is deactivated. The key needs to be turned by 90° and back. The impulse should be no longer than 1 sec. 15 sec. after this operation the GfS e-Bar® is alarm secured again which is indicated by a green display (mains supply). When battery operated the green display fades away after another 15 sec.. If a reed contact is installed the GfS e-Bar® will be alarm secured the moment the door closes.
Single releaseBy using the integrated key switch or by employing an external access control system (p. 22, p.23), an authorized person may pass the emergen-cy exit once without causing an alarm.By briefly turning the key clockwise the single release mode is triggered. The key needs to be turned by 90° and back. The impulse should be no longer than 1 sec. If a reed contact is installed the GfS e-Bar® will be alarm secured the moment the door closes. If the door is kept open for more than 15 sec. a gentle “Door-too-long-open-Alarm” resounds till the door is closed again.
Permanent releaseBy using the integrated key switch an authorized person may deactivate the GfS e-Bar® in order to pass the emergency exit for a longer period of time. The permanent release is triggered by turning the key clockwise for at leat 5 sec. The key needs to be turned by 90° and back.The status is communicated by a raising and lowering brightness of the green display. The key should be removed. The permanent release is activated till thekey is turned again by min. 90° for max. 1 sec. and removed afterwards. Alternatively the permanent release can be set by access control systems, timer etc. (p. 22, p. 23).
RESETPERMANENT OPEN
(hold 5 sec.)
GfS Hamburg ∙ www.gfs-online.com
right
RESET
(hold 5 sec.)
PERMANENT OPEN
GfS Hamburg ∙ www.gfs-online.com
left
RESETPERMANENT OPEN
(hold 5 sec.)
GfS Hamburg ∙ www.gfs-online.com
right
RESET
(hold 5 sec.)
PERMANENT OPEN
GfS Hamburg ∙ www.gfs-online.com
left
8
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
1.3.0 Mechanical versions of GfS e-Bar®
1. GfS e-Bar® mechanic This model is a push bar incl. a picto describing the operation of the GfS e-Bar®. Neither contacts nor electric functions areincluded. The GfS e-Bar® mechanic will be supplied in three different lengths, which might be shortened individually, in order to adjust the length to the width of the door.
Length in mm To be shortened by mm Art. No.
970 180 700 700
1130 160 700 703
1290 160 700 705
2. GfS e-Bar® mechanic with floating contactsThis model is a push bar with floating contacts to generate information on the usage of the push bar.The items will be delivered with a picto describing the operation of the GfS e-Bar®. The GfS e-Bar® mechanic will be supplied in three different lengths, which might be shortened individually, in order to adjust the length to the width of the door.
Length in mm To be shortened by mm Art. No.
970 180 700 710
1130 160 700 713
1290 160 700 715
970/1130/1290
1515
6.5
71.3
84.7
9
To be shortened by 180/160/160 mmDistance between fastening points
9
970/1130/1290
1515
9
43/5
0
71.3
84.7
Display for GfS e-Bar® mechatronic
To be shortened by 180/160/160 mmDistance between fastening points
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
1.3.1 Mechatronic versions of GfS e-Bar®
1. GfS e-Bar® with integrated alarm (battery operated and/or mains supplied)This model works either with a 9 V battery which is controlled by the PCB or with mains supply of 10−30 V/DC. The battery control function checks every 10 hours the voltage. If the voltage drops below 7V, all 60 seconds an accoustic alarm is emitted. The battery has to be changed. When battery operated the GfS e-Bar® works in an energy saving mode which basically means that the green LEDs of the display are permanently switched off. The intelligent PCB recognizes when an external power supply is connected to the GfS e-Bar®. The communicating display shines permanently green. It indicates that the emergency exit is alarm secured. Delivery includes 1 9V battery, 2 keys, 1 picto for display and key switch as well as one sticker explaining the operation on the door.
Length in mm To be shortened by mm Art. No.
970 180 700 730
1130 160 700 733
1290 160 700 735
Power supply surface mounted 901 366
Power supply flush mounted 700 006
2. GfS e-Bar® with integrated alarm and emergency exit switch for opening electrically locked doorsThe GfS e-Bar with integrated emergency exit switch is operated at 10−30 V/DC which is either supplied by an external power supply or the FWS-02 (Emergency exit control unit). The integrated emergency exit switch with 2 opening contacts might be connected to the emergency exit control unit with a max. load of 3A. Adiitionally it is recommended to install a reed contact which offers additional features such as immediate activation after the door has been closed and door-too-long-open-alarm.Delivery includes 1 integrated emergency exit switch, 2 keys, 1 picto for the display and the key switch as well as one sticker explaining the operation on the door.
Length in mm To be shortened by mm Art. No.
970 180 700 740
1130 160 700 743
1290 160 700 745
Power supply surface mounted 901 366
Power supply flush mounted 700 006
10
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.0 Assembly2.1.0 Mounting instructions of GfS e-Bar®
Countersunk screw M3 x 8 Clamping bolt
Lever arm
Lever arm
Lever arm
Cylinder head screw M5 x 20
2a
7a9
4
7
7
7
10
1a
1
2
push bar
base profil
While pressing the push bar profile 4 remove the cylinder head screw M5 x 20 1 .Tear the cover hood 1a out of the bayonet joint towards the lock side.
GfS e-Bar® mechatronicRemove the screw M3 x 8 9 , unlock the cover hood by turning the key clockwise 2a .
GfS e-Bar® mechanic While the push bar is pressed 4 remove the cylinder head screw M5 x 8. Tear the cover hood 2 towards the hinge side.
Remove the protective shield 10 .
Lift the push bar profile 4 up to its maximum. Hold the lever arm 7 with one hand and remove the push bar profile 4 from the clamping bolt in opposite direction 7a .
11
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.1.1 Cut to size with tool kit (not included in scope of delivery)
Connection circuit board(only mechatronic versions)
Assembly/disassembly
4 x M4 x 4 6
7
5
8
Length of base profile
1Shortening tool for base profileArt. No. 770 712
Length of push bar profile
2
Bow saw
Bench vice
Shortening tool for push bar profile
Lug
Bench vice
LugLD/LT ± 1 mm
Order length Length of base profile Length of push bar profileBA 940
BA-67 mm BA-104 mmBA 1100BA 1260
Push bar profile LP ±1 mm
Base Profile LB ± 1 mm
Standard length
Standard length
165always to be shortenedon the hinge side
Just mechatronic versions:Remove carefully the plug of the ribbon cable 5 from the connection circuit board and keep it safe in the base profile. Loosen the slotted grub screws M4x4 6 and remove them together with the console. Keep the shims 8 as you need them again for the assembly.Clamp the profiles in a vice. The jaws of the vice serve as stop for the shortening tool.
ATTENTION:The clamping area should be protected by wood/plastic material in order to avoid scratches on the surface of the profile! Carefully cut the profile with a conventional metal saw along the lug. A straight cut is easier when pressing the blade slightly against the lug. After shortening the profile burr the edges carefully in order to avoid injuries.
ATTENTION:Do not use "lubricants and coolants" when shortening the mechatronic versions od the GfS e-Bar®. Metal chips must not stay in the GfS e-Bar®. Danger of short-circuit! After shortening insert the console 7 into the base profile. Place the shims 8 (0,8 mm thickness) between the console and the base profile.
IMPORTANT:The shims 8 are designed to avoid pressure marks and deformations by the clamp-connection. Fasten the four cylinder pins M4x4 6 with a torque between 0.4 Nm and max. 0.5 Nm! Only mechatronic versions: Insert carefully the plug of the ribbon cable 5 into the connection circuit board.
Tool kit
12
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.2.0 Defining the correct length
6.5
15
158 300
83.5
50
Distance between fastening points
Front vision
Rule of thumb for defining the correct length:door inside width - 2x backset + 2x lockplate thickness + 30mm = GfS e-Bar® length
Distance between fastening points
Door inside width
Door
han
dle
heig
ht
Order length LG = BA + 30
Center of square follower
Order lengths Max. shortening length
970 mm 180 mm
1130 mm 160 mm
1290 mm 160 mm
BA
DM DM
Distance
Square follower
Backset
Front plate shape
Forend plate width
Forend plate length
13
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.3.0 Adjust pre- and main alarm
Screw to adjust alarm setting
Hint: Pre-alarm is not adjustable(preset in the factory).
tighten screw, alarm starts later loosen screw,
alarm starts earlier
Siren
Hall sensor for alarm
Hall sensor for pre-alarm
Dip switch 1– 8
14
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.4.0 Changing the cylinder
Mounting European profile cylinder (PHZ) Mounting Swiss round cylinder (RZ)
Use right drill holes
Use left drill holes
Battery holder
Attention:Use European profile cylinder with lockable cam. Remove key, put cam on 180°!
15
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.5.0 Mounting on wooden doors (Metal cover plate 770 013 for wooden doors are not included in shipment)
X
Image ABA
19 Ø 18
38
43/5
0
21.5/
25
Sunk wood screw Ø 5 x 25
Cylinder head screwwood screw ø 5 x 25
Hinge side Lockside
Standard flat steel base plate
Cover plate lock side
Cover plate hinge sideThickness depending on escutcheon 3 mm, 4 mm, 6 mm)
Counter sunk screw M4x8(respect max. length of screw)
Shoulder bolt M4 x 4
Attention:When assembling pay attention to the orientation of the socket. Cam has to show downwards
Detail X
max. 10
13
Image B
Attention: Cover clip of the standard flat steel base plate has to be mounted before the cover hood is mounted.
16
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.5.1 Mounting on metal doors
Drillings for suitableriveting nuts M5
Cylinder head screw M5 x12
Image ABA 43
/50
21.5/
25
43/5
0
X
max. 10
13
Image B
shoulder bolt M4 x 4
Attention:When assembling pay attention to the orientation of the socket. Cam has to show downwards
Detail X
17
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.5.2 Mounting in combination with security escutcheon (4 mm)
Hinge side Lockside
Cover plate hinge side
Counter sunk screw M4x8 (respect max. length of screw)
X
X
BA
Ø 18
43/5
0
21.5/
25
Cylinder head screw wood screw ø 5 x 25
Escutcheon for GfS e-Bar®
Ø 18
BA 43/5
0
43/5
0
21.5/
25
Escutcheon for GfS e-Bar®
Cylinder head screw M5 x 25
Drillings for suitableriveting nuts M5
Standard flat steel base plate
18
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.6.0 Battery operation/mains supply – wiring of GfS e-Bar®
Installation without cables Installation with cables
Plug with jumper. Only necessary for battery operation. Remove plug when mains supply.
Connection cable 12-wireswith tieGfS Art. No. 770 719
Cable must be fixed with cable tie
Cable length
drilling for connecting cable Ø 10
drilling for connecting cable Ø 10
100 ± 15 mm
Door
han
dle
heig
ht
Door
han
dle
heig
ht
15
15
0.5
0.5
DIN left
DIN right
19
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.7.0 Assembly of GfS e-Bar®
Clamping bolts 3
Soft counter pressure 4
Lever arm 1
Lever arm 1
Cylinder head screw M5 x 20 8
Sunk screw M3 x 8 9
push bar
hinge sideLock side
base profile
27
5
7
6
Lift the lever arms 1 up to its maximum. Hold the lever arm with one hand and pull the push bar profile 2 from the hinge side on the clamping bolt 3 until the push bar profile is engaged. Lift the lever arm with one hand, give some counter pressure on the push bar profile 4 with the other hand in order to avoid that the push bar snaps-out again.
Important: The push bar profile must smoothly but noticably snap-in. Do not force the push bar profile. In case of doubt try again.
Put the protective shield 5 on the support bracket.
Insert the cover hood 7 in the bayonet joint and push it to the end stop. Fix the cover hood with cylinder head screw M5 x 20 8 .a) Mechatronic versions 6 : turn the key anti-clockwise. A noticable click indicates that the cover hood is locked. b) Mechanic versions: Fix cover hoods with M5x8 cylinder head screws (like lock side).
20
IN CASE OF EMERGENCY
PUSH TO OPENwww.gfs-online.com
EMERGENCY EXIT – ALARM PROTECTED
IN CASE OF EMERGENCY
PUSH TO OPENwww.gfs-online.com
EMERGENCY EXIT – ALARM PROTECTED
IN CASE OF EMERGENCY
PUSH TO OPENwww.gfs-online.com
EMERGENCY EXIT – ALARM PROTECTED
RESETPERMANENT OPEN
(hold 5 sec.)
GfS Hamburg ∙ www.gfs-online.com
right
RESET
(hold 5 sec.)
PERMANENT OPEN
GfS Hamburg ∙ www.gfs-online.com
left
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
2.8.0 Placing the stickers
21
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
3. Electrical connection 3.1.0 Terminal board GfS e-Bar® 700 71x
Clamp Signal Wire colour Function
1 NO Relay 1: Pre-alarm
2 NC Relay 1: Pre-alarm
3 COM Relay 1: Pre-alarm
4 NO Relay 2: Main-alarm
5 NC Relay 2: Main-alarm
6 COM Relay 2: Main-alarm
17/18 External key switch message out
19/20 External key switch wiring in
R2–N
O
R2–N
C
R2–C
OM
R1–N
O
R1–N
C
R1–C
OM
1 2 3 4 5 6
1718
1920
22
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
3.1.1 Terminal board GfS e-Bar® 700 73x
Clamp Signal Color Function
1 OV white External door reed contact, recommended otherwise jumper (1-2)
2 GND black Mains supply GND
3 OV brown DIP 8 OFF: DIMM at 10% luminiscence (prgrammable see page) DIP 8 ON: Radar triggered pre-alarm
4 +5V green RS485 A Interface (MODBUS)
5 +5V yellow RS485 B Interface (MODBUS)
6 + 10 V – 30 V red Mains supply 10 V–30 V DC
7 OV violett Electric pulse for single release or permanent signal for permanent opening (2–7) – not avilable when battery operated
8 NC grey Output relay: alarm 30 V/850 mA
9 COM blue Output relay: alarm 30 V/850 mA
10 NO pink Output relay: alarm 30 V/850 mA
11 COM red/blue Output relay: pre-alarm 30 V/850 mA. When pre-alarm contact is opened
12 NO grey/pink Output relay: pre-alarm 30 V/850 mA. When pre-alarm contact is closed
13 COM Internal emergency exit switch 1 min AWG24
Cable diameter LIVY 4x 0,25 14 COM Internal emergency exit switch 2 min AWG24
15 NO Internal emergency exit switch 1 min AWG24
16 NO Internal emergency exit switch 2 min AWG24
17 +9 V +9 V Battery supply
18 GND black GND Battery supply GND
19 GND Key Switch (Reset/Programming)
20 OV Key Switch (Reset/Programming)
}
NC
NO
1
2
4
Incoming Connection COMMON
Normally closed
Normally open
Switching circuit F4
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16C1 C2 N1 N2
1718
1920
JP 1
Rele
ase
RC R2–N
C
GN
D
R2–C
DIM
M
R2–N
0
A R1–C
B R1–N
O
UB
Schl
GND
GND
+ 9 V-Bat
23
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
3.1.2 Terminal board GfS e-Bar® 700 74x
FWS
02G
fS e
-Bar
®
31 32
•1
•2
•3
•4
•5
•6
•7
•8
•9
•10
•11
•12
•27
•28
•29
•30
•31
•32
•33
•34
•35
•36
•37
•38
•13
•14
•15
•16
•17
•18
•19
•20
•21
•22
•23
•24
•25
•26
160
mA/
T
on off
1 A/
T
PENL
15
37
26
48
Stan
dard
cl
amps
Cone
ctin
g cl
amps
fo
r net
wor
k D
IP s
witc
h
R1-NO
R1-C
R2-NO
R2-C
R2-NC
Fern
UB
B
A
DIMM
GND
TK
1211
109
87
65
43
21
+ BU
Bat
t
GND
GND
Schl
17181920
C1C2
N1N2
1615
1413
24
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
3.2.0 Wiring diagram GfS e-Bar® 700 71x
Cable with 6 wires LIYY 6 x 0,14
2
3
1
5
6
4
1 2 3 4 5 6
1718
1920
Connection Pre- and Main-alarm GfS e-Bar® 70071x
Floating contact (see page 21) 30 V/300 mA
Floating contact (see page 21) 30 V/300 mA
NC
NC
NO
NO
C
C
Cable with 6 polesLIYY 6 x 0,14
pre-alarm
main-alarm
External key switch17/18 Key switch message (out)19/20 Key switch wiring (in)
A
25
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
12-pole connection cable LIYY 6 x 0,14Art No: 770 719
Jumper 1: Resistance 120 Ohm for RS 485
without reed contact put jumper on 1–2
NOTAUSGANG ALARMGESICHERT
Cable with 12 wiresArt. No. 770 719
Important:All input contacts are 0V shortcut to ground
TK
blackMains supply GNDGND – 2
greenRS 485 A Interface MODBUSRS 485 A 4
blueMain alarm
Pre-alarm
9
white Door reed contact (automatic activation, intrusion alarm)
0 Volt GND 11
violet Electric pulse for single release or permanent signal for permanent opening (2–7) – not available when battery operated
0 Volt GND 7
red/blue11
redMains supply (plus terminal) 10 – 30 V/DC 10–30 V/DC + 6
yellowRS 485 B Interface MODBUSRS 485 A 5
punk10
brown DIP 8 OFF: DIMM at 10% luminiscence DIP 8 ON: Radar triggered pre-alarm
0 Volt GND 3
greyNC
NO
NO
C
C
Floating contact30 V/850 mA
see p. 30
Floating contact30 V/850 mA
see p. 30
8
gray/pink12
2
1
2
1
Timer Acces Control
System Push buttom
switch
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16C1 C2 N1 N2
1718
1920
JP 1
Remove connector (A) Insert connector (B) of connecting cable Art. No. 770719
A
3.2.1 Wiring diagram GfS e-Bar® 700 73x
26
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
without reed contact put jumper on 1–2
Important: All input contacts are 0 V shortcut to ground
Electric lock for electrically secured emergency exits
blackMains supply GNDGND – 2
greenRS 485 A Interface MODBUSRS 485 A 4
blueMain-alarm
Pre-alarm
External connecting terminal
9
15
16
white Door reed contact (automatic activation, intrusion alarm)
0 Volt GND 1
violett Electric pulse for single release or permanent signal for permanent opening (2-7)
0 Volt GND 7
red/blue11
redMains supply (plus terminal) 10 – 30 V/DC 10–30 V/DC + 6
yellowRS 485 A Interface MODBUSRS 485 A 5
pink10
brown0 Volt GND 3
greyNC
NC
NC
NO
NO
C
C
C
C
Floating contact30 V/850 mA
see p. 30
Internal emergency exit switch GfS e-Bar® 700 74x
Floating contact see page 22
30 V/850 mA
8
13
14
grey/pink12
2
1
+
2
Timer Acces Control
System Push buttom
Switch
NOTAUSGANG ALARMGESICHERT
ZVCable with 12 wires Art. No. 770719
Cable with 4 wires LIYY 4 x 0,25
TK
Cable with 4 wires LIYY 12 x 0,14 Art. No. 770 719
–
ZV
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 16C1 C2 N1 N2
1718
1920
JP 1
Jumper 1: Resistance 120 Ohm for RS 485
Remove jumper (A) Insert connector (B) of connecting cable Art. No. 770 719
A
DIP 8 OFF: DIMM at 10% luminiscence (programmable see page 27), DIP 8 ON: Radar triggered pre-alarm 1
3.2.2 Wiring diagram GfS e-Bar® 700 74x
Cable with 12 wires LIYY 12 x 0,14 Art. No. 770 719
27
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
4.0 GfS e-Bar® settings4.1.0 Activate automatic alarm switch-off If DIP switch 5 is ON the alarm will automatically switched-off after 3 minutes. If DIP switch 5 is OFF a permanente alarm will resound.
4.1.1 Settings of DIP switch
DIP-Nr. Function ON OFF (factory setting)
1 Hold open time + 6 sec.2 Hold open time + 12 sec.3 Back-light while permanent opening no backlight LEDs raising and lowering4 Silent alarm no alarm alarm5 Automatic alarm switch-off 3 min permanent alarm6 Intrusion alarm activated deactivated7 Alarm delay 15 sec. deactivated8 Special options Pre-alarm triggered by radar DIM at 10%
Attention: The settings of the DIP switch will just be changed after the GfS e-Bar® has been switched-on again. The DIP switch setting will be overwritten by a MODBUS command.
4.1.2 RS-485 interface with MODBUS protocol
Up to 127 GfS e-Bar® can be networked. The MODBUS protocol which works with a RS-485 interface offers bi-directional communication. It is thus possibile to monitor and address up to 127 GfS e-Bar® . The communication between different devices is managed by customized masters.
4.1.3 Switching color green/red
When working with mains supply it is up to the operator/dealer to define the color code of the GfS e-Bar®. The following steps have to be taken: • Switch-off the power supply of the GfS e-Bar® and remove the battery. Wait for 10 sec. • Connect the GfS e-Bar® again • Turn the key clockwise by 90° and wait for approx. 5 sec till the display indicates that the GfS e-Bar® is deactivated (permanent opening) • During the following 60 sec press the GfS e-Bar® for about 15 sec. • The color changes every 2 sec. – three times from green to red and back to green • Release the GfS e-Bar® when the desired color shines and confirm this choice by briefly turning the key clockise by 90° • Now the chosen color remains active • The GfS e-Bar® is not in the programming mode anymore but deactivated (permanent opening) .
In case that the color shall be changed again, you have to restart the process all over again (disconnect the power supply).
4.1.4 Changing brightness
• Switch-off the GfS e-Bar®• Press entirely the GfS e-Bar® • Switch-on the GfS e-Bar® again while keeping the GfS e-Bar® pressed for at least 10 sec. untill all LEDs shine• Release the GfS e-Bar® and oberserve LEDs• Brightness of LEDs raise and lower for max. 3 times. A too long wait stops the programming mode automatically the desired brightness is
achieved confirm the result with the integrated key switch for at least 1 sec.• Now the value is stored for future operation, the GfS e-Bar leaves the programming mode automatically
Hint: The brightness and darkness need to be confirmed within 1 sec., enough time to operate the key switch.
28
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
Power supply 9 V battery or 12–30 V/DC power supply
Current draw in battery operation mode Door alarm secured 14 µADoor open 0,5 mA, briefly 90 mA short-term, intermittent Pre-alarm 190 mAMain-alarm in average 160 mA intermittent
Current draw with external power supply (mains supply or FWS 02)Door alarm secured 130 mADoor open 6 mA, briefly 130 mA short-trem intermittentPre-alarm 235 mAMain-alarm in average 190mA intermittent
Battery low signal below 7 V (measured during operation)
Automatic alarm switch off DIP 5 ON: 3 minutes
Turning angle 40° standard 9 mm pin 30° optional 9 mm pin 45° optional 9 mm pin
Power supply 230 V AC/12 – 30 V DC
Reed contact with sabatoge line, incl. 2 m cable, surface or flush mounted (Art-No. 930 110/930 210)
External connection cable for GfS e-Bar® GfS e-Bar® 70071x/70073x 12 wires, 12 x 0,14 LIYY (Art. No. 770 719) GfS e-Bar® 700 74x 20 wires, 20 x 0,25 LIYY
Cable sleeves Metal doors KÜ 480 (Art. No. 901 802) Cable sleeve with housing, INOX Cable sleeve 370 mm, Housing 22 x 480 x 17 mm
Wood doors KÜ-R 480 (Art. No. 901 902) Cable sleeve with housing, INOX Cable sleeve 370 mm, Housing 22 x 480 x 17 mm
Cylinder 30/10 mm European half cylinder with lockable driver
5.0 Technical data
29
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
GfS e-Bar® ______________________________________________________________________________________________
Building ________________________________________________________________________________________________
Manufacturer of lock/lock type ______________________________________________________________________________
Panic function D E B E-SV B-SV
The installation was done properly.
Lock, lock plate and door hardware form a system acc. to EN 1125
The system has been tested and works properly
The door can be unlocked with little effort (< 80 N)
Further comments concerning the building environment:
After installation the escape route is fully accessible
The system has been verified and approved
City, Date Company (stamp)
Signature
6.0 Documentation 6.1.0 Service protocol (operator)
30
7007
xx_M
A_Gf
S e-
Bar_
0518
_GB
GfS Safety at doors
GfS e-Bar® ______________________________________________________________________________________________
Building ________________________________________________________________________________________________
Manufacturer of lock/lock type ______________________________________________________________________________
Panic function D E B E-SV B-SV
The installer has informed the operator of the following:
Function and use
Resetting the alarm
Special functions
Possibility to transmit the alarm to a central display
The operator received the installation and operating manual
The operator has been informed about the required maintenance activities:
– Battery control (at least 1 per month)
– System check (at least 1 per year)
– Visual check (at least 1 per month)
City, Date Company (stamp)
Signature
6.0 Documentation6.1.0 Service protocol (installer)