Date: 12 th May 2018 Rawafed Libya Proposal for Hatif Libya Company “HLC” TENDER Request to Supply (2)UPS Units Complete with Batteries, (2)Automatic Transfer Switch (ATS) and (1)DC System Unit, and (8+2 Rectifiers) TECHNICAL PROPOSAL

Transcript of Rawafed Libya Proposal for

Date: 12th May 2018

Rawafed Libya Proposal for

Hatif Libya Company

“HLC”

TENDER Request to Supply (2)UPS Units Complete with Batteries, (2)Automatic Transfer Switch

(ATS) and (1)DC System Unit, and (8+2 Rectifiers)

TECHNICAL PROPOSAL

1

Table of Contents:

Technical Proposal

1

1. General.......................................................................................................... 2 2. About RLTT.................................................................................................... 2 3. Summary of Proposal.................................................................................... 3 4. Staff, Technicians and Engineers .................................................................. 4 5. Support.......................................................................................................... 4 6. Proposed Solution …………………………............................................................. 5 7. Spare Parts ………........................................................................................... 36 8. Project Manager ……………………….................................................................. 36 9. Delivery Time …………………………………………………………………………………………… 36 10. Warranty …………………………………….…………………………………………………………… 36 11. Validity of Proposal....................................................................................... 36 12. Terms and Conditions…………………..…………………………………………………………… 37

2

1. General

The aim of this proposal is to assure Hatif Libya Company “HLC” that Rawafed Libya

Telecommunications & Technology can be considered as an excellent and well known

Telecommunications solutions and ISP’s service provider in Libya. This document is our

response to the Invitation for the RFP Request to Supply (2)UPS Units Complete with

Batteries, (2)Automatic Transfer Switch (ATS) and (1)DC System Unit, and (8+2 Rectifiers) for

“HLC” in Libya.

2. About RLTT

RAWAFED Libya is a Telecommunication & Technology firm that offers a wide spectrum of

expertise within telecom solutions, IT solutions and power & electric solutions. Rawafed is

the leading internet service and Telecoms solutions provider and at the forefront of satellite

and wireless internet connectivity in the Libyan market.

Founded in Libya 2012, head office in Tripoli with offices in various locations in Libya and a

fully-operational office in Cyprus. The company is structured with Financial, Sales,

Commercial & Marketing, HR, Technical, Logistics and Customer service departments.

RAWAFED Libya has several years of proven experience in management and implementation

of innovative solutions for telecom & technology infrastructure, nationwide.

We assure you that by choosing RLTT as your solutions provider you will benefit from unique advantage of installation, local support and maintenance all provided by just one company. We demonstrate our ability to deliver the requirements in time with an overview and details of our approach. We are proud to announce that Vertiv (Emerson) on November 2017 awarded & entrusted

us as their partner in Libya, we have their fullest support to promote and implement Vertiv’s

(Emerson’s) products and solutions.

Vertiv designs, builds and services critical infrastructure that enables vital applications for data centers, communication networks and commercial and industrial facilities. Formerly Emerson Network Power, Vertiv’s solutions are deployed in key infrastructure projects throughout the world, solutions supports today’s growing mobile and cloud computing markets with a portfolio of power, thermal and infrastructure management solutions including the ASCO®, Chloride®, Liebert®, NetSure™ and Trellis™ brands.

3

Vertiv has won awards and honors for its Data Center Portfolio, these recognitions are given to organizations that have shown exemplary achievements within the industry, delivering the best value to its customers in the data center market.

We are also the distributor in Libya for the following well-known brands:-

Vsat – Eutelsat and Tooway Microsoft Cloud Services Partner Bridgewave Microwave Netis Altai Technology Company Primoco (Drones) Airspan 4G and LTE OSN

3. Summary of Proposal

Rawafed is pleased to Supply “Hatif Libya Company” requirements from “Vertiv/Emerson”

the world leading Power and Thermal Solutions manufacturer, covering the following

solutions:-

2 Vertiv™ Liebert® EXS (10 – 20kVA) Three-phase Stand-alone UPS.

1 NetSure™ 8100 Series multi cabinet DC power system in three phase (8x5,8 kW) increments up to 46,4 kW per cabinet.

8+2 eSure™ R48-5800e Rectifiers. 2 Automatic Transfer Switch (ATS).

Rawafed Libya is partners of Vertiv the market leader in power and thermal solutions for the

following sectors.

a. Telecommunications; b. Power & Infrastructure; c. Oil and Gas; d. Renewable Energy; e. Government;

The Liebert EXS and NetSure DC Power Systems are equipped with the most advanced

industry technology, which allows the unit to provide efficiency for data centers, server rooms

and power rooms. With proven technology that has been relied upon for decades in

applications such as telecommunications, power supply and power distribution, data centers.

4

4. Staff, Technicians and Engineers

Our local staff, technicians and engineers have years of commissioning experience servicing

Vertiv (Emerson) systems and VSAT & ICT and receive expert training overseas. Many staff

members already had a long-standing track record in telecommunications.

Our engineers and technicians are hands-on and performed servicing, installations and

maintenance of commercial and industrial power and thermal solutions, with our mission-

critical services, we ensure your data centres, server rooms and network operating centres

remain operational and functional.

5. Support

One of the most crucial element for our customers is that they have access to 24/7/365 support. RLTT has been working in the Telecoms business for many years, so we are geared to deal with this high support level. Support calls can be made by CLIENT to directly to the 24/7 NOC who will provide a ticket number for you request and manage the fault until it is cleared.

RLTT is able to provide the best possible end-to-end responsibility for the whole service as we have control over the entire delivery chain. This ensures the shortest response times in troubleshooting as all our people work for the same company.

With our mission-critical services, we ensure your data centres, server rooms and network

operating centres remain operational and functional. We know that downtime is not an

option. Our Vertiv (Emerson) factory-trained service technicians and engineers understand

the evolving complexities in managing and maintaining power and thermal solutions. With

our support programs, we can protect your equipment investment and resolve critical issues

before they negatively impact your business.

Rawafed will proactively work with you in Power & Thermal Studies, Commissioning, Deployment, and Testing to make sure you select optimal technologies, have reliable operations, and stay on schedule and budget. With our industry experience and best-practice knowledge base as your guide, you can reduce delays and rework and maximize your investment.

5

6. Proposed Solution

UPS Offer:-

We are proposing Vertiv “Liebert® EXS (10 – 20kVA) Three-phase Stand-alone UPS”:

Liebert EXS is an optimized and integrated three-phase UPS solution with high efficiency power protection. The Vertiv™ Liebert® EXS UPS is designed for mission critical applications, such as Telecommunications, Transportation, Healthcare, Retail and Government Facilities. It brings exceptional features for mission-critical applications: its extraordinary double conversion efficiency up to 96.2% ensures remarkable operational cost savings. At the same time, with its unity output power factor and high power density, Liebert EXS is able to provide the utmost active power possible in a remarkable compact footprint.

System Description:-

The UPS includes the following operational components: Rectifier. Battery Charger. Inverter. Static Bypass Switch. Maintenance Bypass. Internal Battery (optional).

The UPS will automatically provide continuity

of electrical power, within defined limits and

without interruption, upon failure or degradation

of the commercial AC source.

The duration of autonomy (i.e. backup power time)

in the event of network failure is 1 hour as per HLC’s

request.

Features and Performances:

Output power factor up to 1. Double conversion efficiency up to 96.2%. ECO mode efficiency up to 99%. Compact footprint with multiple internal

runtime configurations. Available in 3/3 and 3/1 versions. Integrated maintenance bypass. Integrated input and output breakers/switches. Parallel capability for capacity and redundancy.

Liebert EXS offers integrated full galvanic isolation, meaning that an isolation transformer may be housed inside the UPS

6

cabinet. This greatly reduces the system footprint, thus providing space saving advantages.

The transformer may be connected to the input or to the output of the UPS, providing: Full galvanic isolation for medical and other critical applications. Installation with two independent input sources (with different neutrals). Installation in distribution without neutral.

The Liebert® EXS proposed UPS ratings and input/output configurations and System Key Features presented herewith:

RATING (kVA) INPUT OUTPUT

20 kVA 380-400-415V 3 Ph+N 380-400-415V 3 Ph+N or 220-230-240V 1 Ph+N

Double Conversion Efficiency up to 96.2% max Input Current Harmonic Distortion (THDi): 3% max

Eco Mode Efficiency up to 99% Backup time: 65 minutes at 100% load and 0.8 Power Factor

Input Power Factor up to 0.99 LIFE™ Compatible

The single-line diagram of the UPS:-

Liebert EXS 20 kVA: Three-phase input / three-phase output

7

Liebert EXS 10-20 kVA: Three-phase input / single-phase output

Neutral Connection:

The Liebert EXS output neutral is electrically isolated from the UPS chassis. The input and

output neutral are solidly tied together; therefore the UPS will not modify the state of the

upstream neutral in any operating mode. As a consequence the neutral state of the

distribution downstream from the UPS is imposed by the mains and distribution switchgear.

Primary Input: The three-phase current taken from the commercial AC source is converted to a regulated DC voltage by the IGBT rectifier. In order to protect the power components within the system, each phase of the rectifier input is individually fitted with a fast-acting fuse.

The IGBT rectifier will provide DC power to the DC/AC output converter (IGBT inverter) and to the DC/ DC battery converter (booster / battery charger) when the UPS is working in “normal mode”. The latter will also boost the DC voltage to the correct level required by the Inverter when working in “battery mode”.

Operating Modes: The UPS inverter continuously supplies the critical AC load. The rectifier draws power from the commercial AC source and converts it into DC power for the inverter and the battery charger. The battery charger maintains the battery in a fully charged and optimum operational condition. The inverter converts the DC power into clean and regulated AC power which is supplied to the critical load (conditioned line). The static switch monitors and ensures that the inverter tracks the bypass supply frequency. In this condition any automatic transfer to the bypass supply (due to an overload etc.) is frequency synchronized and does not cause interruption to the critical load.

8

Electronic Static Switch (Bypass): The UPS comes complete with a Silicon Controlled Rectifier (SCR) static transfer switch rated to conduct full load current continuously in the maximum overload conditions.

The input feed of the bypass can be either the same as the rectifier or independent, provided they share the same neutral. The control logic will be managed by digital algorithms (using vector control techniques), similar to those used for the rectifier and the inverter, sensing the status of the inverter logic signals as well as operating and alarm conditions. If the bypass is within the specified synchronization window, the control logic will automatically transfer the critical AC load to the bypass source, after any of the following conditions:

Inverter overload. Output voltage abnormal. DC bus voltage abnormal. Parallel system transfer. UPS fault condition. End of discharge reached.

Operator Control and Display Panel: The operator control and display panel are located on the front of the UPS. The control panel of Liebert EXS includes a 320x240 pixel multi-lingual, graphic Liquid Crystal Display (LCD), allowing the user to operate and control the UPS checking parameters, as well as UPS and battery status and retrieve up to 2500 events/alarm logs for reference and diagnosis. Complete access to all LCD menus is possible through four software-assigned buttons located below the display. The on-screen icons above the buttons clearly explain the function of the button within each menu. Two LED indicators show the current working state of the UPS as described below.

9

UPS System Quantity & Description:

QTY Description

2 EXS201A0000A1A0: EXS 20kVA STANDARD “NO BATT”. (up to 2x32x9Ah) with Intellislot

4 LI66160MN090AB0: BATTERY CABINET - 10Y: 4x32x9Ah TYPE A3

Physical Characteristics: H, mm W, mm D, mm W, kg

EXS 20kVA STANDARD NO BATT. (up to 2x32x9Ah) with Intellislot

1300 335 650 85

BATTERY CABINET - 10Y: 4x32x9Ah TYPE A3 1600 600 825 480

UPS Communication, Monitoring & Control Solutions:-

Liebert EXS features a multi-lingual LCD user interface allowing close control and monitoring of system status and performance. The UPS offers the following communication features:

Voltage-free contacts. Intellislot for SNMP, Modbus or Relay communication. USB interface. These communication capabilities make Liebert EXS compatible with any building

management system.

Vertiv™ IntelliSlot UNITY-DP card provides Web access, environmental sensor data, and third-party customer protocols for Vertiv UPS. The cards manage a wide range of operating parameters, sending data over Ethernet networks via secure HTTPS protocol and alarms and notification via SNMP traps.

10

Vertiv IntelliSlot UNITY cards allow also monitoring and control of Vertiv UPS through Vertiv SiteScan® Web or any existing Building Management System.

Vertiv Intellislot UNITY-DP card delivers also MODBUS and BACNET protocol via the EIA-485 or Ethernet port.

Vertiv IntelliSlot UNITY cards provide: Compatibility with Vertiv shutdown software. A dedicated web page for monitoring the UPS. Interface with Vertiv Nform™ alarm notification software. Ease of integration with industry standard open protocol. Interface with Vertiv SiteScan Web software. Proactive analysis of parametric data to ensure facility uptime.

11

Batteries Proposed for UPS:-

HR Series: Manufactured by Hitachi Chemical Energy Technology Co., Ltd. HR 1234W 12V 34W – Valve regulated Lead Acid Battery; Maintenance-Free Sealed Lead Acid Battery, Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%. HR stands for High Rate Discharge. This series is a high energy, high intensity, and high quality output electrical energy product series with 20% more energy density than same volume products at high rate discharge characteristics. Main features as follow:

When it is used in safe surroundings, the battery is maintenance free, adding water is unnecessary and it can be recharged repeatedly.

With isolated seal, it can be put in horizontal way, vertical way and side way, its safety and functions totally will not be affected.

With special formula to manufacture lead calcium alloy as well as automatic progresses, gassing will be less.

Long life, low self-discharge rate and high reliability. It has safety, low resistance so recharge is easy and energy output is more remarkable. Container material could be frame retardant ABS or PP with ranking UL 94V-0 by

model. Standby use. High rate discharge construction. Deep discharge recoverability. Batteries are strictly tested by our patented computer charge/discharge system.

ISO9001, 14001, OHSMS 18001 certified.

UL recognized components under UL 1989 (file number MH14533).

12

HR Series Battery Specification;

Nominal Voltage 12V (6 cells per unit)

Nominal Capacity 34W @15min-rate to 1.67V per cell @25℃ (77℉) Weight Approx. 2.50 Kg (5.51 lbs) Maximum Discharge Current

130A (5sec)

Internal Resistance Approx. 19.0 mΩ Short Circuit Current 349A Maximum Charge Current

3.4A

Terminal types F2 -Faston Tab250 Terminal breaking Torque

--

Container Material ABS (UL 94-HB) & Flame Retardant (94-V0) available upon request

Dimensions

Length (L) 150.9±2.0 mm 5.94±0.08 inch Width (W) 64.8±1.0 mm 2.55±0.04 inch Container Height (h) 94.3±1.0 mm 3.71±0.04 inch Overall Height (H) 98.6±1.0 mm 3.88±0.04 inch

13

DC Power System (with 8 Rectifiers) Offer:-

NetSure™ 8100 Series Multi Cabinet DC Power System: The NetSure™ 8100 Multi Cabinet is

an expandable DC Power system with 3-phase rectifiers (8x5,8 kW), especially suitable for

medium to large sized central office telecom and data center applications.

The NetSure™ 8100 Series of multi cabinet DC power systems delivers outstanding reliability within a modular, scalable cabinet platform. Doors can be mounted on both the front and the back side of the cabinet to facilitate extensions and service work. Distribution units can be added, swapped or removed on live sites, making system expansion a standard procedure. Power supply extensions can be made safe and easy to match constantly changing load requirements, without compromising reliability.

14

Key Features: Multi cabinet -48V DC power

systems can be expanded to 2,8 MW for telecom and datacom equipment located in close proximity.

NetSure™ 8100 Multi Cabinet System

1 Battery Connection Unit 2 Cabinet Interconnection 3 Customer Connections 4 NetSure™ Control Unit 5 Load Distribution Units 6 AC Distribution Unit 7 eSure™ 5800 W Rectifiers

Easily adapt to new load

requirements with removable cabinet side panels, hotswappable distribution units.

Individual current measurement feature displays current reading for each fuse/circuit breaker.

Avoid downtime by predefining alarm threshold values and balancing the load in advance.

Site energy consumption mapping displays energy consumption for each DC power fed server rack.

Cabinet efficiency >99,7% from rectifier output to distribution output enabling maximum system efficiency >96,2% from grid to load.

15

Minimizing Energy Loss: The NetSure™ 8100 Series minimizes power conversion energy losses, reducing heat dissipation and lowering energy consumption — both on the power supply and the cooling system. Cabinet infrastructure efficiency is greater than 99,7% from rectifier output to breaker output with maximum system efficiency just over 96,2% from grid to load. Rack load measurement and site energy consumption mapping warn of site load distribution inefficiencies and possible hotspots. Securing Availability: The multi cabinet platform offers plenty of expandable power for load distribution, while minimizing site cabling and voltage drop from grid to load. This system is expandable to 2,8 MW and designed to be placed in close proximity to telecom and datacom equipment. With intelligent load management there is no need to install excess capacity up-front to cover for load build-ups and potential overloads. Each load can be monitored and measured down on the distribution, fuse and circuit breaker level. With this detailed information the NetSure™ Control Unit will provide early warnings before any potential overload. This means that actions to avoid failures can be taken upfront. Site load can continuously evolve while power supply is extended incrementally, without compromising system reliability and power availability. Application: Designed for medium sized central office telecom and data center applications, this multi cabinet DC power platform is ideal for replacing less power efficient solutions at sites where power expandability, efficiency, and availability are critical. When frequent load changes require access to multiple distribution units and backup proximity close to the load, the multi cabinet NetSure™ 8100 Series is the answer.

16

Technical Specifications:

AC Input

NetSure™ 8100

Range 3 phase: 260 VAC to 530 VAC (Nominal: 346 VAC to 415 VAC)

Line Frequency 50 or 60 Hz (45 Hz to 65 Hz)

Connections Terminal or distribution for up to 12 circuit breakers

Surge Protection Optional

DC Output

Adjustable Range -42 VDC to -58 VDC (Nominal: -48 VDC)

Power, Maximum 46,4 kW (8 x 5,8 kW rectifier modules per cabinet)

Efficiency, Peak 96,2% eSure™ R48-5800 rectifier

DC System Units

Distribution Units Available for circuit breakers, cartridge fuses, NH00 fuses, NH2 fuses

Circuit Breakers From 2 A up to 200 A

Fuses NH00-80V (up to 600 A) and NH2 (up to 400 A)

Intelligent Load Management Optional, equipment for all distribution units

Battery Connections Up to 5 x 300 A or 4 x 400 A circuit breakers, Up to 4 x (500 A to 630 A) fuses

Physical Characteristics

Mounting Top and bottom cabling

Dimensions (H x W x D) 1800 or 2020 mm x 600 mm x 600 mm (per cabinet)

Weight 155 kg per cabinet (fully equipped)

Access and Security Front access, IP20, door with lock as option on front and back

Environmental

Temperature Range, Operating -5 °C to +60 °C (full power up to 40 °C)

Relative Humidity, Operating <90%

Altitude 2000 m

Audible Noise 60dB for R48-5800e

Ventilation Forced ventilated (rectifier fans)

Safety and Standards Compliance

Electrical CE EN60950-1

EMC EN 300 386-2, Class B

Environmental REACH, RoHS 6

17

eSure™ Rectifier:-

The eSure™ R48-5800e rectifier converts 260 to 530Vac 3-phase AC supply voltages into stable nominal-48V DC voltage adjustable to the needs of the application. The R48-5800e is a constant power rectifier designed with the latest patented switch-mode technology using DSP (Digital Signaling Processor) functionality for efficient operation. For a higher load capacity, rectifiers can be connected in parallel and intelligent control can

be added with the help of a separate controller.

AC INPUT

Voltage 260 VAC to 530 VAC (see figure 1) 380 VAC to 480 VAC (nominal)

Frequency 45 Hz to 65 Hz

Maximum Current 13 A

Power Factor 0.99

DC OUTPUT

Voltage -42 VDC to -58 VDC

Maximum Power 5800 W @ Vout >48 VDC

Maximum Current 120A @ 48 VDC, limit set point 0 to 120 A (see figure 2)

Peak Efficiency 96.2%

Psophometric Noise (System) <2 mV typical; <32 dBrnc typical

Temperature Derating See figure 3 for derating

18

Key Features: Rectifier, 48 VDC, 5800 W

Optimized depth – reduced footprint allows installation in short-depth racks and cabinets.

Compliant with global standards - delivers quality, performance and reliability no matter what the application or location demands.

DSP (Digital Signal Processor) - means fewer components, optimized operation and active load sharing for increased reliability.

Hot pluggable – facilitates future extensions.

High efficiency, near 96.2% - reduces power consumption for lower operating costs.

Wide input voltage range - operates in the most demanding environments where input voltage changes.

Wide temperature operating range from

-40°C to +65°C/ -40°F to +149°F meets the harshest climatic environment requirements.

CONTROL AND MONITORING

Rectifier Alarm and Signaling Alarm and status reported via CAN bus to system controller

Visual Indications

Green LED = Normal Operation Yellow LED = Alarm Red LED = Failure; Flashing Red LED = Fan Failure

ENVIRONMENTAL

Operating -40°C to +65°C / -40°F to +149°F (see figure 3 for derating)

Storage -40°C to +70°C / -40°F to +158°F

Relative Humidity 0 to 95%

Altitude 2000 m / 6560 ft at full power

STANDARDS COMPLIANCE

Safety 60950 (EN and UL), Telcordia GR-63-CORE

EMC ETSI EN 300 386 class B, FCC CFR 47 Part 15 class B, Telcordia GR-1089-CORE class B

Environment REACH, R5, WEEE

19

NetSure™ Control Unit (NCU):- The advanced NetSure™ Control Unit from Emerson Network Power takes remote monitoring and control to the next level with a user-friendly color interface, secure connectivity, data statistics and multiple communication options.

The NetSure™ Control Unit (NCU) is an advanced controller designed for a wide range of DC power applications. The NCU enables remote monitoring and control of modern communication sites and is backward compatible with existing NetSure™ power systems. The controller is factory installed or can be added in the field to deliver data and control for all aspects of the power chain, including AC mains, DC power plant, battery backup, diesel generator and the local site environment. The addition of optional interface boards enables the user to access an even greater set of site parameters.

The NCU features advanced battery management for temperature compensation and boost charge control, prediction of remaining time and capacity, constant current testing, scheduled battery testing, and short duration battery testing. Thresholds for battery current measurement, detailed alarms, inventory management and three LVD levels can be programmed easily through the controller. Control of rectifiers (24V, 48V and 400V) and converters (24V, 48V, 400V and solar) is possible in this convenient pluggable module.

Expanded information and alarm data can be monitored or controlled via password protected and encrypted web browsers, including Internet Explorer, Firefox, Google Chrome, and Apple Safari. Network element management support for data communication is also available via standard protocols, such as SNMP version 2 and 3, and Modbus. In addition, Modbus device integration for many industry standard monitoring devices is now possible with the versatile NCU controller.

The new patent-pending Intelligent Load Management functionality displays current per fuse and circuit breaker and can measure each site rack’s aggregated current in relation to rack capacity. This feature requires optional system distribution measurement devices for breaker or fuse positions.

20

Key Features:

Simplified user interface includes an installation wizard, graphical color display and user friendly web pages.

Supports encrypted (HTTPS) multibrowsers including IE6.0 or above, FireFox, Chrome, Safari.

Dual Network port option which allows for permanent connection and available craft port for service PC simultaneously.

Modbus as monitoring option – communicates with energy devices and/or a supervisory computer (NOC).

Battery management features include temperature compensation, thermal runaway management, recharge current limit, reserve time prediction, and optional midpoint monitoring.

Intelligent Load Management support for systems that include SMDU+ or SMDUH.

Easily configurable file upload/ download minimizes installation time.

Backwards compatible with ACU, SCU, ACU+ and SCU+.

Ethernet connectivity via IPv4 and/or IPv6.

Supports six user-selectable languages.

NetSure™ Control Unit User Interface Web Interface Home Page

21

Automatic Transfer Switch (ATS):-

Option 1:-

ABB – Motorized change-over and transfer switch OTM_C. – with wall mounted Panel:

Model – 34OTM_C/1SCC303002M0204.

ABB offers a wide variety of open transition motorized change-over switches from 40 to 3200

Amperes in range. All of ABB visually redesigned motorized change-over switches now come

equipped with a new cover with clear operating instructions and improved motor operator

performance.

ABB motorized change-over switches are fast and easy to install. The voltage sensing

connectors have been designed to save time, as there is no need to drill holes into the

busbars. Also, the control and power cables are screw mounted, providing a safe and secure

connection that stays tight even during transportation.

ABB switches come equipped with a comprehensive range of inbuilt safety features such as

mechanical interlock, which ensures the isolation of the two asynchronous power supplies.

22

This eliminates risk of short-circuiting between them. The motorized change-over switches

are also equipped with a handle for manual operation in case of emergency.

Reliable in Extreme Conditions:

Ensuring a high performance level for you is of the utmost importance to ABB. In change-over

applications where the loaded switch may need to be operated remotely, adequate durability

has been ensured by testing against the IEC 60947-6-1 standard in the specification of

endurance requirements.

23

ABB - Change-over Control Panel Type Wall Mounted Electrical Diagram 250A:-

24

25

26

27

28

29

Option 2:-

Technoelectric srl - Motorized Change-over Switch, CS2 (AC23), 4 Pole – with Panel:

Has long been a leader in the field of electro-mechanical engineering, particularly regarding

low voltage load break and fuse-switches.

The three and four pole change-over switches, with motorized operation, allow remote

control of change-over/breaking/disconnection under load of power circuits in low voltage

systems.

General Characteristics:

The motorized change-over switches are made by means of two switch disconnectors of

“Visualcompact” series mechanically interlocked.

Automatic under-load change-over (AC22, AC23) from and to any of positions “1”, “0”,

“2” both electrical and manual (emergency change-over), transfer function with direct

transition from position “1” to position “2” and viceversa.

Front display of positions “1”, “0”, “2” by digital display and/or mechanical indicator (for

MS version).

Safety: locking by padlock preventing any electrical or manual operation, key lock for the

selection of electrical or manual operation (on MS series only).

External signalisation of positions “1”, “0” and “2” by a clean contact (no voltage supply).

Quick operating time from pos. “1” to “2” and viceversa (see tables at pages 144 and

145).

Easy and fast electrical connections by means of terminal blocks of quick connection

type.

Power supply voltage 12-24V DC, 110/220/380V AC, others on request.

30

Compact dimensions.

Selection of operating logic by a micro switch on the PC board and easily accessible for

the following logic:

o a. impulse (150 ms min)

o b. contactor (maintained contact)

Conformity to Standards:

IEC 60947/1-3, IEC 439-1, IEC 204-1

CEI EN 60947/1-3, CEI EN 60439-1, CEI EN 60204-1

VDE 0660 Teil 107.

31

Technoelectric - Control Panel Type Wall Mounted Electrical Diagram 300A:-

32

33

Electronic Panel for Monitoring and Operating:-

34

35

36

7. Spare Parts

We have taken into considerations HLC’s technical team requirements, (2) eSure™ R48-5800e

Rectifier’s as spare-units consisting of:-

Description QTY

eSure™ R48-5800e:- Converts 260 to 530Vac 3-phase AC supply voltages into stable nominal-48V DC voltage adjustable to the needs of the application.

2

8. Project Manager

We will designate a Project Manager, who shall be responsible for the overall project control and coordination of the tasks specified in the contract. The Project Manager shall be the focal point within the organization for providing information relating to the project status, project progress, deliverables, problem areas, plans and all other project related information on a frequent basis.

9. Delivery Time

Delivery lead time for supply is 12 to 14 weeks.

10. Warranty

We provide a warranty of 12 months from the date of delivery of items.

11. Validity of Proposal

This offer is valid for 140 days from date of this proposal.

37

12. Terms and Conditions

This quotation is subject to the terms and conditions stated above and complemented with

enclosed Seller's Standard Terms and Conditions. In case of contradictory terms and

conditions, this Quotation shall apply in the first place, and thereafter the Seller's Standard

Terms and Conditions.

I look forward to your positive response and if you have any questions or require further

information, please channel these directly to us by either calling or emailing us at my contact

details provided below.

Kind Regards,

Mr. Bashir Mahjub

Power Solutions Manager

Rawafed Libya for Telecommunication & Technology

Tel: + 218 21 366 0201 Ext 1036

Email: [email protected]