ductility, overstrength and residual drift in buckling- restrained ...
Large-Scale Testing of Low-Ductility, Concentrically-Braced Frames
Transcript of Large-Scale Testing of Low-Ductility, Concentrically-Braced Frames
Large-Scale Testing of Low-Ductility, Concentrically-Braced Frames
C. Bradley1, J. Sizemore
2, J. Nelson
1, R. Tremblay
3, E. M. Hines
4, L. A. Fahnestock
5
1Graduate Research Assistant, Dept. Civ. & Env. Eng., Tufts University,
[email protected] 2Graduate Research Assistant, Dept. Civ. & Env. Eng., UIUC
3Professor, Dept. Civ., Geo., & Mining Eng., École Polytechnique Montréal
4Professor of Practice, Dept. Civ. & Env. Eng., Tufts University;
Principal, LeMessurier Consultants 5Associate Professor, Dept. Civ. & Env. Eng., UIUC
ABSTRACT
In regions of moderate seismic hazard, the costly structural detailing necessary to
ensure adequate ductile performance of a braced frame during an earthquake event
can be difficult to justify economically. Structural engineers, however, are permitted
to design low-ductility systems if larger demands are assumed. In regions of moderate
seismic hazard, this philosophy has proved to be economical and has resulted in
widespread use of such low-ductility braced frame systems. Despite this popularity,
the inelastic behavior and collapse performance of these systems is not currently
understood at a fundamental level. A broadened understanding of the inelastic
behavior of low-ductility braced frames can lead to an improved seismic design
philosophy and provide practicing structural engineers with a coherent, rational, and
transparent design approach applicable to moderate seismic regions. This research
aims to identify low-ductility braced frame failure mechanisms and the sequence in
which they occur, as well as to draw conclusions on the implications of the observed
behavior contextually in building collapse performance.
INTRODUCTION
While steel concentrically braced frames constitute a significant portion of the
building stock in Eastern North America (ENA), these frames are generally designed
without consideration of seismic detailing with a response modification factor of R =
3, or as Ordinary Concentrically Braced Frames (OCBF) with a response
modification factor of R = 3.25. An OCBF design implies some consideration of
seismic detailing for the purposes of achieving more ductility than an R = 3 design
and less ductility than a Special Concentrically Braced Frame (SCBF), which has a
response modification factor of R = 6. Despite their prevalence, neither the R = 3 nor
the OCBF frame types have been tested to the levels of their more ductile
counterparts. Since 1997, when the AISC Seismic Provisions introduced the concept
of R = 3, the design criteria for OCBFs has changed in every update to the Seismic
Provisions (2002, 2005, 2010). Considering the fact that the OCBF system is one of
only two systems in ASCE 7 with an R-value written to three significant figures, and
considering that the value of 3.25 is only 8% higher than 3, the ambivalence of the
structural engineering community to the actual ductility of this system is quite clear.
In spite of the fact that so little is known about the seismic behavior and collapse
performance of low-ductility braced frames, the structural engineering community
has generally tolerated these frames in moderate seismic regions because of the
general resistance to collapse of steel braced frames during actual earthquakes, the
inherent ductility of structural steel as a material, the general level of redundancy in
most building systems with respect to collapse, and the understanding that buildings
are likely to form some kind of reserve system following the strength and stiffness
that results from brace fracture. The concept of reserve capacity has a long history in
seismic design, and was most clearly expressed in the original concepts behind dual
systems (Hines and Fahnestock 2010). Analysis of low-ductility braced frame
buildings with and without added reserve capacity in the form of column continuity
and beam-to-column moment-rotation capacity has also shown that enhanced reserve
capacity has a significantly greater effect on probabilistic collapse fragilities than
changes in strength of the braces and their connections (Hines et al. 2009).
Since this initial analytical work, however, several questions have been raised
regarding the sources of reserve capacity and their reliability. For instance, braces
that are assumed to reengage after initial fracture provide substantial reserve capacity
(Davaran et al. 2014, Sizemore et al. 2014). Brace gusset plate connections can
provide substantial beam-to-column moment capacity (Stoakes and Fahnestock
2011). Column continuity can also provide reliable reserve capacity when only braces
experience brittle failure in an isolated story.
The purpose of the large scale testing planned for the NEES facility at Lehigh
University this spring is to begin to provide some experimental data related to cyclic
behavior and brittle failure mechanisms of an R = 3 steel concentrically braced frame
and an OCBF. This paper outlines the goals of the testing program, the design of the
prototype, and the design of the test units considering realistic laboratory constraints.
NEES@LEHIGH TEST PROGRAM
During the spring and summer of 2014 two full scale tests of steel concentrically
braced frames (CBF) are underway at Lehigh University’s Advanced Technology for
Large Structural Systems (ATLSS) testing facility. This work is led by the University
of Illinois at Urbana-Champaign (UIUC) and Tufts University as part of a Network
for Earthquake Engineering Simulation Research (NEESR) project funded by the
National Science Foundation (NSF). UIUC and Tufts are collaborating with a team
from the École Polytechnique Montreal (EPM) on this work as part of an
international program to investigate reserve capacity in low-ductility concentrically
braced frames (Fahnestock et al. 2014). This program also includes testing and
analysis of top and seat angle connections for enhanced beam-to-column moment
capacity (Nelson et al. 2014, Beland et al. 2014), testing of tubular brace
reengagement with gusset plates after connection fracture (Davaran et al. 2014), and
collapse analysis of 3-, 6- and 9-story low-ductility braced frame buildings with
varying levels of reserve capacity (Sizemore et al. 2014). The NEES@Lehigh tests
include a two-story, R = 3, chevron brace configuration (Figure 1) and a two-story,
OCBF, split-X brace configuration (Figure 2).
Figure 1. R = 3 chevron braced frame test setup.
Figure 2. OCBF split-X braced frame test setup.
These tests are designed to explore post-elastic behavior in low-ductility braced
frames with a particular emphasis on brittle damage mechanisms. Over a year of
analytical work investigating the 3-story prototype buildings on which these two
frames are based led to the conclusion that while the overall purpose of the research
program is to investigate realistic collapse behavior of low-ductility braced frame
buildings under seismic loads, the purpose of these tests is to observe brittle damage
mechanisms for the purpose of calibrating analytical models. Considering the range
of behaviors that are possible in each frame and the scarcity of data on such frames,
the loading protocols and test setups for each frame are designed to be as simple as
possible.
The R = 3 chevron (or inverted-V) braced frame is generally considered to be an
archetypal low-ductility braced frame. It is widely used in building construction
throughout ENA because of the flexibility that it offers for architectural coordination.
It is also a statically determinate system that does not theoretically share gravity loads
between braces and columns. The AISC Seismic Provisions have always required
special consideration of such frames for OCBF designs such as: requiring the floor
beams to be able to carry gravity loads between columns without support from the
braces below, requiring the floor beams to resist not only gravity loads but also some
tension loads from braces after the compression brace has buckled, and requiring
stockier KL/r ratios for braces. While the Seismic Provisions have not considered
beam yielding as depicted in Figure 3(a) as a viable ductile mechanism for such
frames, such yielding has the potential to provide reserve capacity and will be the
primary focus of the R = 3 test. Floor beams in R = 3 systems are not required to span
between columns without help from the braces below. Nevertheless, the beams in this
frame have been designed both to span under gravity loads and to act as beam
columns under elastic lateral load transfer without consideration of bracing provided
by the floor slab.
Figure 3. NEES@Lehigh test unit post-elastic damage mechanisms.
(a) R = 3 chevron test unit, (b) OCBF split-X test unit.
Figure 3(a) and 3(b) illustrate the expected initial post-elastic behavior of the two test
units. In these figures, primary damage mechanisms are identified with larger circles
and secondary damage mechanisms are identified with smaller circles. The first two
damage mechanisms in both frames are expected to be buckling of the braces and/or
fracture of the compression brace connections. In the prototype building, compression
braces and connections are expected to fail first because their gravity loads and
seismic loads are additive. In the test unit, however, there are no gravity loads, so this
mechanism is not as obvious. Testing of tubular brace-to-gusset plate connections has
shown both that these connections can have actual strengths that exceed expected
strengths by more than 20%, and that minor accidental eccentricities can result in
significant bending of the gusset plates and tearing of the welds (Davaran et al. 2014).
For these reasons, brace buckling is expected prior to connection fracture, and the
investigators still expect to see post-elastic damage begin in the compression braces
and their connections. Inherent in damage mechanism 2 at the compression brace
connections is the possibility of brace reengagement after the weld has fractured and
the end of the slot bears against the edge of the gusset plate.
Damage mechanism 3 consists of yielding of the second floor beam once the
compression brace has buckled and this beam is subjected to an unbalanced load.
This damage mechanism is expected only in the R = 3 chevron frame. Damage
mechanisms 4 and 5 relate to the connections of the brace that is in tension during the
formation of damage mechanisms 1 and 2. Recent testing, conducted by Roeder et al.
of an older CBF typical of high seismic regions, demonstrated that this connection
fractured soon after the failure of the compression brace in buckling and low-cycle
fatigue fracture (Roeder et al. 2013). Of further interest as the Lehigh test units
degrade further in the post-elastic range are the performance of connections
associated with damage mechanisms 6 and 7. The bending in these mechanisms is
expected to be primarily a function of compatibility with overall frame deformations;
however, it may prove significant if it ultimately contributes to reserve capacity,
affects primary damage mechanisms, or experiences some kind of brittle failure that
further jeopardizes the integrity of the overall system. In particular, mechanisms 6
and 7 are expected to become active in the OCBF test unit if braces in both stories
fail. Such conditions would present an ironic twist on the split-X OCBF, rendering
the more intentional seismic system in greater need of reserve capacity in its beam-to-
column connections.
PRACTICAL LIMITATIONS OF THE NEES@LEHIGH TEST SETUP
Practical limitations of the testing equipment and the novelty of testing these brittle
systems have led to several decisions designed to simplify the test setups. The test
setups are full-scale so that member sizes, connection angles, gusset plates, bolts and
welds are inherently realistic. For the purposes of this discussion, the term “test
frame” refers to the Lehigh fixtures and stabilizing frame, and the term “test unit”
refers to a braced frame itself. For a full-scale test setup, the Lehigh test frame
offered a 35-ft bay, which is reasonably consistent with the 30-ft bay prototypes that
have been the subject of previous analysis. The available test frame story heights
were either 7.5 ft or 15 ft. Fifteen feet was chosen because of its general consistency
with designs for steel office buildings. This choice, consistent with the choice to test
at full scale, limited the test units to two stories and led to the decision not to include
column splices in the test units. While column splices had originally been conceived
as an important part of this testing, the investigators determined that such splices
would require backspans in the story both above and below the splice level,
necessitating a minimum of 3 stories. This would have either required the test units to
go to less than full scale, to not match any realistic prototype, or to significantly
change the stabilizing frames and test fixtures. None of these options were deemed to
be practical or necessary considering the number and complexity of behaviors already
expected in these test units.
Consistent with the Lehigh test frame, which stabilizes the test unit directly on either
side of the first and second floor beams, no concrete slabs were considered for the test
unit design. While concrete slabs provide significant post-brittle damage capacity in
steel buildings, this capacity typically depends on continuity of the slabs and decks
beyond the columns in question. Since the test unit consists of only one bay, the
added complexity of concrete slabs that would have to be coordinated with the test
frame and limited in width was not considered to be justified.
The test setup does not provide realistic gravity loads in the braced frame columns.
The test frames will experience a seismic-only load case. The lack of gravity loads
during the test will result in reduced stresses on the order of 15 ksi or 30% of yield
strength in the compression column. Although the stress variation in the columns is
significant, the lack of gravity in the columns is not expected to affect the braces and
connections as dramatically. Brace and connection failure are expected to occur
before column failure regardless of the presence of gravity loads. The absence of
gravity load combined with the likelihood and desirability of a first story mechanism
from an experimental point of view strengthened the argument for modeling the test
frames on a three story building structure as opposed to a taller structure. The three
story prototype was chosen instead of a two story prototype both for consistency with
previous analytical work and for the purpose of not including roof beams in the test
setup.
Columns in the test frames are connected via base plates to clevis fixtures, which
simulate ideal pins; however, the base reaction links intersect the test frame at an
elevation nearly 5 feet above the pinned base fixture. As a result, a pseudo-basement
level is formed below the first floor beam due to column continuity (Figure 4). The
resulting test unit column back spans are stiffer than they would be in a prototype
with a full basement. Analytical work to date has not modeled prototypes with
basements, opting to consider the first story as landing on spread footings with a slab
on grade. Neither realistic column base plates anchored into concrete footings, nor a
slab on grade were considered for the test unit design. Instead, at the ground level, a
steel grade beam was designed to transfer the base shear into an actuator with a load
cell that is braced to the laboratory floor.
Figure 4. Test unit base fixture and reaction link.
LOADING PROTOCOL
Each frame will be loaded quasi-statically with two actuators as shown in Figures 1
and 2. A third actuator is situated at the base beam to measure and resist the total base
shear. In the elastic range, the actuators will be force-controlled according to a regime
representing the equivalent lateral force distribution that served as the basis for the
test unit designs. In this range, the second floor actuator will be the master device,
loading the frame with both second and third story loads. The first floor actuator will
be slaved to the second floor actuator to maintain first floor loads that are
proportional according to the design force distribution. Since the exact moment or
location of failure is unknown, displacement limits will be set on both actuators that
are consistent with 0.2% total drift in the frame, which is equal to 0.72 in. at the
second story. If the system remains elastic up to this displacement level, the test will
proceed in displacement control in 0.1% total drift increments until the first damage
mechanism occurs. During this time, the lower actuator will remain slaved to the
upper actuator in linear proportion to the elastic force distribution.
Once the first damage mechanism occurs, the test will continue to proceed in
displacement control; however, the actuator loading the damaged story will become
the master actuator. For instance, if initial brittle damage commences in the first
story, the lower actuator will become the master. After initial brittle damage occurs,
the remainder of the test will be run in either 0.5% or 1.0% story drift increments for
the story containing damage. Loading of the undamaged story will be displacement-
based in proportion to the displacement recorded at the commencement of brittle
damage. If both stories experience brittle damage simultaneously, the investigators
will chose the master actuator based on the damage mechanism they prefer to
explore. In such a case, the slave actuator will run in linear proportion to its
displacement level recorded at the commencement of brittle damage.
DEVELOPMENT OF THE PROTOTYPE STRUCTURE
In a concerted effort to maintain a strong correlation between the somewhat artificial
test frames and actual braced frame designs, a prototype building was utilized in the
design process. The prototype structure was designed in accordance with ASCE-7
2005, the IBC 2006 and the Massachusetts state building code (8th
edition). Seismic
detailing for the OCBF followed the 2010 AISC Seismic Provisions instead of the
2005 Provisions, which are currently referenced by the Massachusetts Code.
The three-story prototype building (Figure 5) consists of a rectangular floor plan
(150ft x 175ft) with 15-ft story heights. There are two interior braced frames in each
direction, all utilizing strong-axis columns. The remaining columns are oriented such
that each half of the building contains an equal number of strong- and weak-axis
columns. Note that this configuration is intended to be as consistent as possible with
previous studies for steel frames in Boston (SAC 2000b, Hines et al. 2009).
Constraints in the ATLSS laboratory facility, however, required adjustments to bay
width and story height of the prototype structure. Specifically, the bay width was
increased from 30 to 35 feet in one direction, and all the story heights were adjusted
to 15 feet.
Figure 5 – Prototype building floor plan.
Composite slab construction of the prototype structure was assumed to be 3.25-inch
lightweight concrete slab on 3-inch steel deck. The total dead loads accounted for this
slab as well as deck, floor, hung, ponding, and framing loads. The total dead load was
taken to be 75 psf. Per ASCE 7, a 15 psf partition load was added to the baseline
office live load of 50 psf for a total live load of 65 psf. For the roof, dead and live
loads were each assumed to be 30 psf. Note that a façade load of 25 psf was assumed
on all exterior surfaces of the structure. In addition, a 10 psf live load for partitions
was added to the floor dead loads when determining seismic weights for calculation
of seismic loads.
Representative of the moderate seismic region in Boston, Massachusetts, the
prototype design assumes soil Site Class D and Seismic Design Category B in
developing the design acceleration response spectra. The seismic load effects were
determined by the equivalent lateral force procedure set forth in ASCE 7. Similarly,
wind loads were analyzed assuming the prototype to be located in Boston with
Expose Category B. The analytical procedure for wind loads, also presented in ASCE
7, was used for the design. Due to the relatively short height of the building, seismic
loads governed the design of the lateral system.
DEVELOPMENT OF THE TEST FRAMES
Two low-ductility lateral system test units were developed. One test unit will be a
two-story, full-scale, R=3, chevron brace configuration and the other a two-story,
full-scale, OCBF, split-X brace configuration. A summary of the framing members
and connection geometry are shown in Tables 1 and 2, respectively. Specified steel
grades are A992 for beams and columns, A500 Grade B for braces, and A36 for
angles and gusset plates. Additionally, all brace-gusset welds are 5/16 in. fillet welds.
Table 1. Test Frame Member Sizes and Beam Web Angle Sizes.
Table 2. Gusset Dimensions, Brace Weld Lengths, Beam Weld Sizes, and Gusset Angle Sizes.
Bracing connections in the frames consisted of square HSS profiles slotted around
and welded to gusset plates. The gusset plates, in turn, are welded to the connecting
beam. For connections at the supporting columns, the beams and gusset plates are
connected to the column flange by means of all-bolted double angles. In every double
angle connection, 3/4-inch diameter A490N bolts were specified. In order to evaluate
the distribution of brace forces to the connection elements, the Uniform Force
Method (UFM) was used. In addition, the double angles and bolts were analyzed for
prying action and designed to resist these effects.
Because the UFM provides little guidance on the final selection of gusset geometry, a
consistent approach was developed for use in the test unit designs. The final geometry
of the gusset plates can be determined by following these steps:
1. Determine the minimum required brace-to-gusset weld length necessary to
develop the ultimate brace design force. For this study, the weld capacity was
calculated assuming 1/4-inch fillet welds on all four corners of the brace. The
designs, however, specify 5/16-inch fillet welds to maintain single pass
welding while still accounting for a potential 1/8-inch of tolerance in the
width of the brace slot.
2. For connections at a support, assume a length for the gusset leg of the
Frame Story Beam Brace Web Angles Column
Chevron
R=3
3 W12x40 - 2L4x4x1/2
W1
2x
53
2 W12x40 HSS8x8x5/16 2L4x4x5/8
1 W12x72 HSS8x8x3/8 2L8x4x1 LLBB
OCBF
R=3.25
3 W12x40 - 2L4x4x1/2
W1
2x
53
2 W12x26 HSS6x6x3/8 2L4x4x1/4
1 W12x72 HSS6x6x1/2 2L8x4x1 LLBB
Fra
me
Sto
ry
Gu
sset
Po
siti
on
*
Gu
sset
Len
gth
, L
(in
)
Gu
sset
Hei
gh
t,
H (
in)
Gu
sset
Th
ick
nes
s, t
(in
)
Len
gth
of
Bra
ce-G
uss
et
Wel
d (
in)
Siz
e of
Bea
m-
Gu
sset
Wel
d
(in
)
Do
ub
le A
ng
le
Sec
tio
n
Chevron
R=3
3 B - S 16 14.5 3/8 6 1/4 2L4x4x3/8
2 B - S 19 17 1/2 9 5/16 2L4x4x1/2
T - M 48 16 1/2 9 3/8 -
1 B - S 21 19 1/2 11.5 5/16 2L4x4x1/2
T - M 51 17.5 5/8 11.5 7/16 -
OCBF
R=3.25
3 B - S 18 16.5 3/8 8 1/4 2L4x4x3/8
2 B - M 47 15.5 5/8 10.5 3/8 -
T - S 19 17.5 1/2 10.5 3/8 2L4x4x1/2
1 B - S 22 19.5 5/8 14.5 1/2 2L4x4x1/2
T - M 53 18 3/4 14.5 1/2 -
*Gusset positions are marked as Bottom/Top – Side/Middle and are abbreviated as B/T – S/M.
connecting angles. Although this length may change depending on prying
effects, 4 inches is reasonable starting point.
3. Assume a minimum desired spacing between the brace and the nearest
connecting element, which may be either the connecting angle or beam. The
purpose of this distance is to provide additional clearance for erection and
welding considerations.
4. Finally, assume an edge distance perpendicular to the brace that defines the
length of the cut in the gusset plate. In the test units, this value was selected to
be 2 inches because it resulted in reasonable final dimensions. Note that this
value cannot be less than the specified size of the brace-to-gusset fillet weld.
Assuming that the location of the work point of the brace and the angle of the brace
are known, then the above steps can be followed to define the gusset plate geometry
based solely on trigonometry. Once the gusset plate dimensions have been
determined, relevant limit states must be checked and the design adjusted as
necessary. Detail A from Figure 1 is the final design of the second floor support
connection in the chevron test unit and is displayed in Figure 6. This connection was
designed for ultimate brace forces equal to 191 kips in compression and 151 kips in
tension, which were determined from the 1.2D + 0.5L + 1.0E load combination.
General proportions of this connection are representative of typical braced frame
gusset plate connections.
Figure 6 – Chevron connection detail A.
The R=3, concentrically braced frame test unit is a low-ductility frame that considers
no seismic detailing. For this system, the members were designed for strength and
stiffness alone. Connections were not designed for the amplified seismic loads and no
amplification to the fundamental period, T, of the frame was considered.
The R=3.25 OCBF test unit is also a low ductility frame, but some detailing was
required. For V and inverted-V configurations, AISC 341 requires OCBF bracing to
satisfy b/t ≤ 15.4 and KL/r ≤ 96.3. In addition, connection elements, columns, and
beams must consider the amplified seismic load, which is directly proportional to Ω0.
For OCBF systems, ASCE 7 uses Ω0 = 2.0. Additionally, an increase to the
fundamental period was used in the analysis of seismic loads.
CONCLUSIONS
The results of this research will be applicable to braced frame design in moderate
seismic regions and may improve the work of design professionals in the field of
structural engineering as well as developers of seismic design and braced frame
design codes and specifications. The results will be of interest mainly to regions of
moderate seismic hazard, such as Eastern North America, but may also have
implications for design in high seismic regions. The results will provide valuable
insight into the behavior of these widely-used systems; thus, benefits to the structural
engineering profession will be significant.
ACKNOWLEDGMENTS
This study is supported by the National Science Foundation (Grant No. CMMI-
1207976) and the American Institute of Steel Construction. The opinions, findings,
and conclusions in this paper are those of the authors and do not necessarily reflect
the views of those acknowledged here.
REFERENCES
ASCE (2005), Minimum Design Loads for Buildings and Other Structures,
ASCE/SEI 7-05, American Society of Civil Engineers, Reston, VA.
Beland, T., Bradley, C., Nelson, J., Davaran, A., Hines, E.M., Tremblay, R.,
Fahnestock, L.A. (2014), “Experimental Behavior of Bolted Angles and Beam-
Column Connections,” Structures Congress, ASCE, Boston, April 3-5.
Davaran, A., Beland, T., Fahnestock, L.A., Hines, E.M. and Tremblay, R. (2014),
“Experimental Behavior of Low-Ductility Brace Connection Limit States,”
Structures Congress, ASCE, Boston, April 3-5.
Fahnestock, L.A., Hines, E.M., Tremblay, R., Bradley, C., Nelson, J., Beland, T.,
Davaran, A., Sizemore, J. (2014), “Reserve Capacity and Implications for Seismic
Collapse Prevention for Low-Ductility Braced Frames in Moderate Seismic
Regions,” Tenth National Conference on Earthquake Engineering, EERI,
Anchorage, AK, July 21-25.
Hines, E.M., Appel, M.E. and Cheever, P.J. (2009), “Seismic Performance of Low-
Ductility Concentrically Braced Frames in Moderate Seismic Regions,” AISC
Engineering Journal, 46 (3), Third Quarter, pp. 149-180.
Hines, E.M. and Fahnestock, L.A. (2010), “Design Philosophy for Steel Structures in
Moderate Seismic Regions,” 9th US National and 10th Canadian Conference on
Earthquake Engineering, EERI/CAEE, Toronto, Canada, July 25-29.
Massachusetts (1996), The Massachusetts State Building Code: 780 CMR Eighth
Edition. Massachusetts State Board of Building Regulations and Standards,
Boston.
Nelson, J., Davaran, A., Beland, T., Bradley, C., Hines, E.M., Tremblay, R.,
Fahnestock, L.A. (2014), “Cyclic Experimental Behavior of Angles and
Applications for Connection Design and Modeling”, Proceedings of the 2014
ASCE Structures Congress, Boston, MA, April 3-5.
Roeder, C., Lehman, D., Berman, J., Tsai, K.C., Sen, A., Sloat, D. and Li, C.H.
(2013), “NCBF-INV-1 Test Summary,” National Center for Research on
Earthquake Engineering (NCREE), Taiwan, July 20, 19 pp.
SAC (2000b), State of the Art Report on Systems Performance of Steel Moment
Frames Subject to Earthquake Ground Shaking, FEMA 355C, Federal Emergency
Management Agency, Washington, D.C.
Sizemore, J., Davaran, A., Fahnestock, L.A., Tremblay, R. and Hines, E.M. (2014),
“Seismic Behavior of Low-Ductility Concentrically Braced Frames,” Structures
Congress, ASCE, Boston, April 3-5.
Stoakes, C.D. and Fahnestock, L.A. (2011), “Cyclic Flexural Testing of
Concentrically-Braced Frame Beam-Column Connections,” Journal of Structural
Engineering, ASCE, 137 (7): 739-747.