Electro Discharge Machining Version 2 ME, IIT Kharagpur Instructional Objectives
et_nit_2122_28.pdf - IIT Kharagpur
-
Upload
khangminh22 -
Category
Documents
-
view
2 -
download
0
Transcript of et_nit_2122_28.pdf - IIT Kharagpur
INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR
KHARAGPUR, WEST BENGAL 721302
TENDER DOCUMENT
for
Construction of Shallow and Deep Water Maneuvering and Seakeeping Basin Facility for Ocean Engineering and Naval
Architecture Department.
NIT No. IW/CE/NIT/2021-22/028
Tender Serial No. ______________________________Issued to:
…………………………………………………..…………………..…………………..…………
………………………………………………………..……………..…………………..…………
…………………………………………………………..…………..…………………..…………
Page | 1
Contents
1. NOTICE INVITING TENDER 2
1.1. INTRODUCTION ......................................................................................................................................................................................... 2
1.2. PARTICULARS ............................................................................................................................................................................................. 2
1.3. ELIGIBILITY CRITERIA ................................................................................................................................................................................. 2
2. INFORMATION TO BIDDERS 4
2.1. SCOPE OF WORK ........................................................................................................................................................................................ 4
2.2. GENERAL INSTRUCTIONS .......................................................................................................................................................................... 4
2.3. SUBMISSION OF TENDER .......................................................................................................................................................................... 7
2.4. EVALUATION OF BIDS AND AWARD OF WORK ........................................................................................................................................ 7
2.5. BIDDING CAPACITY OF CONTRACTORS…………………………………………………………………………………………………………..8
3. UNDERTAKING BY THE BIDDER 9
Annexure(s)…………………………………………………………………………………………………………………………………………….10-15
4. Checklist for Documents to be uploaded on https://eprocure.gov.in/eprocure/app………………………16
PRICE BID (SOQ)…………………………………………………………………………………………………………………………………… 17-65
Page | 2
1. NOTICE INVITING TENDER
1.1. INTRODUCTION
Indian Institute of Technology (IIT) Kharagpur, hereinafter called IITKGP, invites online tenders from the eligible contractors for Construction of Shallow and Deep Water Maneuvering and Sea keeping Basin Facility at IIT Kharagpur. Particulars of the project are as following.
1.2. PARTICULARS
1.NIT Number NIT No. IW/CE/NIT/2021-22/028
2.Name of Work Construction of Shallow and Deep Water Maneuvering and Sea keeping Basin Facility at IIT Kharagpur
3.Location of Work
Adjoining Ocean Engineering and Naval Architecture department building and Hydrodynamics Laboratory, IIT Kharagpur
4.Estimated Cost(including GST) ₹ 20,47,97,150/- (Rupees Twenty Crore Forty-Seven Lakhs Ninety-Seven Thousand One Hundred and Fifty Only).
5.Earnest Money Deposit NSIC/MSEs Registration Certificate OR Bid Security Declaration Form (Annexure-III).
6.Time Limit for Execution 540 days from Date of Start.
7.Tender Basis and Mode Two stage(Technical Bid & Financial Bid)
8.Date, Time & Venue of Pre-bid Meeting 21.10.2021, 15:00hrs, CCM Meeting Room, 1stFl, Old Bldg., IIT Kharagpur, Kharagpur-721302
9.Closing Date & Time for Receipt of bids 28.10.2021 upto 15:00hrs
10.Date& Time for Opening of Technical Bid 29.10.2021 at 15:30hrs
11.Date& Time for Opening of Price Bid To be intimated to the eligible bidders subsequently.
12. Engineer-in-charge and contact details.
Mr. S K Biswas, Sr. Executive Engineer(Civil) Tel No. 03222-282580, Mobile No. 74071 39556 Email: [email protected]
13. Address for tender issue, submission and opening
Civil Construction & Maintenance Section, 1st Floor, Old Building, IIT Kharagpur, Kharagpur WB 721302
14.Website for full and updated information http://www1.iitkgp.ac.in/topfiles/tenders.php;
https://eprocure.gov.in/eprocure/app
15. Website for tender submission & processing
https://eprocure.gov.in/eprocure/app
1.3. ELIGIBILITY CRITERIA
1.3.1. The bidder must be registered in appropriate class of works with Government organization like CPWD/ PWD/ MES or PSUs or those having experience in similar nature of works awarded by Government / Semi Government Organizations/ Government Funded Autonomous Organization / Public Limited Company.
Page | 3
1.3.2. The bidder must have done at least 1 (ONE) similar work of value of 80% (i.e Rs.16,38,37,720) of the estimated cost or 2 (TWO) similar works for projects each of value 60% (i.e Rs.12,28,78,290) of the estimated cost or 3 (THREE) similar work for projects each of value 40% (i.e Rs.8,19,18,860) of the estimated cost with Government/ Semi-government/PSU/ Government Funded Autonomous Organization during last 7 (seven) years preceding last date of the month of tender submission.
Note:
(i) The estimated is ₹ 20,47,97,150/- (Rupees Twenty Crore Forty-Seven Lakhs Ninety-Seven Thousand One Hundred and Fifty Only).
(ii) The value of executed works shall be brought to current costing level by enhancing the actual value of work at simple rate of 7% per annum; calculated from the date of completion to the last date of receipt of applications for tender.
(iii) Similar work shall consist of :
Any RCC construction with RCC basement OR Industrial Shed with RCC basement.
1.3.3. The bidder must be registered with appropriate government authority as a bona-fide business entity and must have GST registration certificate and Permanent Account Number of income tax.
1.3.4. The registrations and licenses should be valid during the execution phase.
1.3.5. The Average annual turnover of the bidder as per ITCC or profit & loss statement shall not be less than 30% of the estimated cost of project, not having incurred loss in more than two years, during last 5 years ending 31 Mar 2020. The documents submitted should be duly certified and audited by Chartered Accountant.
1.3.6. Net worth Certificate as on 31.03.2020 of minimum 15% of the estimated cost i.e. Rs. 3.08 Crore issued by certified Chartered Accountants is to be submitted. Format for the same is enclosed in Annexure-IV.
Chief Engineer
On behalf of the Director, Indian Institute of Technology Kharagpur
Copy to: 1) Registrar 2) S.E (E&M) 3) Sr. Executive Engineer (Civil/E&M) 4) Assistant / Junior Engineer (Civil/ E&M) 5) Notice Board
6) Office file
Sd/-
Page | 4
2.INFORMATION TO BIDDERS
2.1 SCOPE OF WORK
2.1.1 The IITKGP intends to construct a Shallow and Deep Water Maneuvering and Seakeeping Basin Facility at IIT Kharagpur. The construction work of this facility shall include civil, structural, plumbing and sanitation, electrical (HT & LT), ELV, HVAC, water transfer system, filtration system, fire protection and other piping works. It may be noted that deep excavation up to around 6 m below existing ground level as well as some piling work will be required to be carried out. It may be also noted that water table at the site of construction is generally quite high, being under 1 m below the existing ground in the rainy season to about 3 m below in the fair season.
2.1.2 Constraint: The job needs to be executed in IIT campus area without causing any disturbances to the normal functioning of routine activities/ road networks. Deep excavation needs to be carried out in close proximity to existing buildings and their foundations.
2.1.3 The vendor shall work out execution sequence and methodology so as to complete the project within the envisaged time and the estimated cost, duly handling the constraint mentioned above.
2.2 GENERAL INSTRUCTIONS
2.2.1 Bidding documents are to be obtained electronically through websites: http://www1.iitkgp.ac.in/topfiles/tenders.php; ii)https://eprocure.gov.in/eprocure/app
2.2.2 This bid document shall be read in conjunction with GCC (General Conditions of Contract) available on http://www1.iitkgp.ac.in/topfiles/tenders.php.
2.2.3 The bidder shall visit and inspect the site and obtain all information on his own responsibility and at own cost, which may be necessary for the purpose of quoting and submitting the tender. No excuse or ignorance as to site conditions and local information shall be accepted after awarding of the contract. Access to the site will be granted by the Engineer-in-charge on all working days within working hours.
2.2.4 IITKGP shall not provide any space at site for labour hutments.
2.2.5 All clarifications about the tender shall be sought by bidder on or before pre-bid meeting. The bidders may make suggestions which shall be considered during the Pre Bid Meeting. Intending bidder(s) may also send their queries or suggestion, if any, through e-mail to the Engineer-in-charge [email protected] or before 21.10.2021, 14:30 hrs. No queries shall be entertained after notification of replies to noteworthy queries received till the date of pre-bid meeting.
2.2.6 Completion certificate issued by Competent Authority will only be considered as credential. If the Completion certificate issued by Competent Authority does not reflect the type of work, then Final bill / Schedule of Quantity of the qualifying works also to be attached along with the Completion certificates. Certificate from private individuals / organizations for whom such works have been executed shall not be accepted.
2.2.7 The bidding document (consisting of specifications, the schedule of quantities of various types of items to be executed, the set of terms and conditions of the contract and other documents / drawings, if any), Addendum/Corrigenda, Clarifications to Pre-bid queries can be downloaded from the websites: i)http://www1.iitkgp.ac.in/topfiles/tenders.php; iii)https://eprocure.gov.in/eprocure/app. Corrigenda, if any shall be published only on these websites at any time before the closing time of tender. The institute shall not be responsible for any delay / difficulties / inaccessibility of downloading facility for any reason whatsoever. The tenderers who have downloaded the tender documents from website must visit the website and ensure that such addendum(s)/corrigendum(s) (if any) is also downloaded by them. This shall be the responsibility of the prospective registered bidders to check the web site for any such corrigendum/addendum before closing time of tender and ensure that bid submitted by them are in accordance with all the corrigendum’s/addendums.
2.2.8 All costs, charges & expenses that may be incurred in connection with the preparation of his tender shall be borne by him and the Institute accepts no liability whatsoever therefore.
2.2.9 Rates quoted by the bidders shall be inclusive of GST (Goods and Services Tax - Central, State and Interstate) and all applicable taxes. Income Tax and all other statutory deductions like labour cess etc. will be deducted from the bill as per prevailing rules.
2.2.10 Exemption to IITKGP against any tax/ duty/ fee/ surcharge/ charge/ cost, if any, found applicable or sought later from IITKGP after award shall be passed on to IITKGP by the contractor without dispute.
Page | 5
2.2.11 IITKGP reserves the right to reject any or all of the bids without assigning any reason.
2.2.12 Bid Validity: Bid shall remain valid for 120 days from the date of submission.
2.2.13 Firm Price: Bidder’s quoted Rates/Prices for executing the activities under the Contract shall remain firm till completion of the entire work & shall not attract any escalation under any circumstances whatsoever.
2.2.14 If any information furnished by the bidder is found as false / fabricated, then his bid will be rejected and treated as cancelled. Even if such manipulation is detected at any stage after signing of the contract, it would lead to termination of the contract besides enforcing actions as mentioned in the Bid Security Declaration Form(Annexure-III) and liabilities towards prosecution. In such cases the bidder will be debarred from participation in future tendering process in IITKGP for next 01 (One) year.
2.2.15 Earnest Money Deposit(EMD): As per amendment in GRF-2017, No.F9/4/2020-PPD dated 12.11.2020, no provision for EMD has been kept in this tender. However the bidder has to submit a Bid Security Declaration as per Annexure-III.MSEs registered with District Industries Centers, National Small Industries Corporation and any other body specified by Ministry of MSME or Startups as recognized by Department of Industrial Policy and Promotion shall be exempted from payment of EMD in the bid. The self attested photocopy of their evidence should be submitted by the bidder(s) along with the formal request letter for exemption.
2.2.15.1 In case the NSIC/MSEs registration certificate is found invalid during evaluation, the bid of such bidder shall be rejected.
2.2.15.2 Bidder so exempted for submission of EMD shall have to submit an undertaking as per Annexure-II.
2.2.15.3 Bidder not having NSIC/MSEs registration has to submit Bid Security Declaration Form (Annexure-III) alongwith an undertaking as per Annexure-II.
2.2.16 Defect liability period will be 5 years from date of completion.
2.2.17 Security deposit of 5% will be released @ 1% p.a on satisfactory/ successful completion of any defect notified during the year/previous years.
2.2.18 General: Only Indian Manufacturers/Service provider or their authorized vendors, having registered office in India are invited to quote.
A. Compliance under Rule 144 (xi) of the General Financial Rules (GFRs) 2017
I. As per Ministry of Finance, Department of Expenditure, Public Procurement Division Order (Public Procurement No.1) issued from file No.6/18/2019-PPD dated 23rd July, 2020 & the Order issued from time to time regarding Restrictions under Rule 144 (xi) of the General Financial Rules (GFRs) 2017, it is directed that any bidder from a country which shares a land border with India will be eligible to bid in any procurement whether of goods, services (including consultancy services and non-consultancy services) or works (including turnkey projects) only if the bidder is registered with the Competent Authority i.e. the Department for Promotion of Industry and Internal Trade (DPIIT).
II. “Bidder” (including the term ‘tenderer’, ‘consultant’ or ‘service provider’ in certain contexts) means any person or firm or company, including any member of a consortium or joint venture (that is an association of several persons, or firms or companies), every artificial juridical person not falling in any of the descriptions of bidders stated hereinbefore, including any agency, branch or office controlled by such person, participated in a procurement process.
III. “Bidders from a country which shares a land border with India” for the purpose of this Order means:
a) An entity incorporated, established or registered in such a country; or
b) A subsidiary of an entity incorporated, established or registered in such a country; or
c) An entity substantially controlled through entities incorporated, established or registered in such a country;
or
d) An entity whose beneficial owner is situated in such a country; or
e) An Indian (or other) agent of such an entity; or
f) A natural person who is the citizen of such a country; or
Page | 6
g) A consortium or joint venture where any member of the consortium or joint venture falls under any of the
above
IV. The beneficial owner for the purpose of above will be as under: - (i) In case of a company or Limited Liability Partnership, the beneficial owner is the natural person(s), who,
whether acting alone or together, or through one or more juridical person, has a controlling ownership
interest or who exercise control through other means.
Explanation-
a) “Controlling ownership interest” means ownership of or entitlement to more than twenty-five per cent of
share or capital or profit of the company;
b) “Control” shall include the right to appoint majority of the directors or to control the management of
policy decisions including by virtue of their shareholding or management rights or shareholders
agreements or voting agreements;
(ii) In case of a partnership firm, the beneficial owner is the natural person (s) who, whether acting alone or
together, or through one or more juridical person, has ownership of entitlement to more than fifteen percent
of capital or profits of the partnership;
(iii) In case of an unincorporated association or body of individuals, the beneficial owner is the natural person(s),
who, whether acting alone or together, or through one or more juridical person, has ownership of or
entitlement to more than fifteen percent of the property or capital or profits of such association or body of
individuals;
(iv) Where no natural person is identified under (1) or (2) or (3) above, the beneficial owner is the relevant natural
person who holds the position of senior managing official;
(v) In case of a trust, the identification of beneficial owner(s) shall include identification of the author of the trust,
the trustee, the beneficiaries with fifteen percent or more interest in the trust and any other natural person
exercising ultimate effective control over the trust through a chain of control or ownership
V. An agent is a person employed to do any act for another, or to represent another in dealings with third person.
VI. For Works contracts, including Turnkey contracts, the successful bidder shall not be allowed to subcontract works to any contractor from a country which shares a land border with India unless such contractor is registered with the Competent Authority.
A certificate (duly filled & signed) shall be submitted by bidders in the tender documents regarding their compliance with the said order as per Annexure A. If the certificate submitted by a bidder whose bid is accepted is found to be false, this would be a ground for immediate termination and further legal action in accordance with law.
B. Compliance under Rule 153 (iii) of the General Financial Rules (GFRs) 2017
It is mandatory for bidders to quote items having 20% or more local content. Refer revised Public Procurement (Preference to Make in India), Order 2017 P-45021/2/2017-B.E-II dated 16.09.2020 and the order issued from time to time by Department for Promotion of Industry & Internal Trade (DPIIT), Ministry of Commerce and Industry, Government of India. (Submit duly filled Annexure B for the same).
Also, as per DPIIT, Ministry of Commerce and Industry OM vide no: P-45021/102/2019-BE-II-Part(1) (E-50310) dated 04.03.2021, bidders can’t claim themselves as Class-I local supplier / Class-II local supplier by claiming the services such as transportation, insurance, installation, commissioning, training and after sales service support like AMC/CMC etc. as local value addition.
Page | 7
2.3 SUBMISSION OF TENDER
2.3.1 Help for Contractors, FAQ, Information about DSC and Bidders Manual Kit containing the detailed guidelines for e-Procurement system are also available on Central Public Procurement Portal.[https://eprocure.gov.in/eprocure/app]
2.3.2 It is mandatory for all the bidders to have a valid Class-II/Class-III Digital Signature Certificate (in the name of person having power of attorney to sign the Bid) from any of the licensed Certifying Agency (Bidders can see the list of licensed CA’s from the link www.cca.gov.in) to participate in e-Procurement of IIT KHARAGPUR.
2.3.3 It is mandatory for the bidders to get their firm /company registered with e-procurement portal https:// eprocure.gov.in/eprocure/app to have user ID & password.
2.3.4 Tender documents will be available online on website https://eprocure.gov.in/eprocure/app which can be downloaded free of cost.
2.3.5 Bidders may download and refer the “Instructions for Online Bid Submission” from (https://eprocure.gov.in/eprocure/app;jsessionid=2A56E178EED5C7D8536175EFBB573C9F.eprocgep2?page=HelpForContractors&service=page).
2.3.6 The tender documents shall be submitted online in the prescribed format given on the websites and technical bids received online shall be opened as per NIT or Corrigendum thereof. No other mode of submission is acceptable. Detailed credentials as per the requirement of eligibility criteria and all tender papers except Bill of Quantities are to be submitted in “Technical Bid”.
Bill of Quantities with rates duly filled in are to be submitted in the format provided online in the name of “Financial Bid”. Hence, physical submission of the documents is limited to submission of MSE registration certificate as per provision given in sub-clause 1.2.5 of NIT & 2.2.15 of Information to Bidders.
Representative of the bidder, who chooses to attend, may attend the online opening of the technical bids on the scheduled date and time of Bid opening. However, such representatives shall be allowed to attend the opening of the Technical Bids, only, if such person presents the letter of authority issued in his name by the bidder on his letter head.
2.3.7 Bidders cannot submit the tender after the due date and time of e-bid submission. Time being displayed on Central Public Procurement Portal https://eprocure.gov.in/eprocure/app (“Server System Clock Time”) shall be final and binding on the bidder. e-Bids are required to be submitted by bidders, only as per the Indian Standard Time (IST) and not the time as per their location/country.
2.3.8 The bidders are advised to submit their e-bids well before the e-bid due date. IIT KHARAGPUR shall not be responsible for any delay in submission of e-bids for any reason including server and technical problems.
2.3.9 The Technical and Financial Bid shall be digitally signed by the Authorized Signatory of the bidder & submitted “on-line” only. The authorized signatory of the bidder must be in possession of Power of Attorney before submitting the digitally signed bid. Scanned copies of various documents can be prepared in .pdf file format.
2.3.10 Any tender received without original Earnest Money in the form as specified in clause 1.2.5 of tender documents shall not be considered and shall be summarily rejected.
2.3.11 IIT KHARAGPUR reserves the right to cancel the tenders before submission/opening of tenders, postpone the tender submission/opening date and to accept/reject any or all tenders without assigning any reasons thereof. IIT KHARAGPUR’s assessment of suitability as per eligibility criteria shall be final and binding.
2.3.12 Tenderers may note that they are liable to be disqualified at any time during tendering process in case any of the information furnished by them is not found to be true. The decision of IIT KHARAGPUR in this regard shall be final and binding.
2.4 EVALUATION OF BIDS AND AWARD OF WORK
2.4.1 The Bid of bidder will be opened electronically on the specified date and time of opening at the Civil Construction & Maintenance Section, 1st Floor, Old Building, IIT Kharagpur, Kharagpur WB 721302 in the presence of willing bidders or their authorized representatives.
2.4.2 Date, time and place of opening of Financial Bid will be informed after evaluation of Technical Bid to the Technically Qualified Bidders.
Page | 8
2.4.3 Bids shall, first, be checked for NSIC/MSEs registration certificate or Bid Security Declaration Form (Annexure-III). Only those bids found to have duly submitted NSIC/MSEs registration certificate or Bid Security Declaration Form (Annexure-III) shall be considered for evaluation.
2.4.4 Evaluation of Technical Bid: The bids received will then be assessed on the eligibility criteria mentioned at Para1.3of Notice Inviting Tender. Bids found not meeting the eligibility criteria shall be considered non-responsive and shall be rejected summarily.
2.4.5 IITKGP retains the right to revert back to individual bidders with further clarifications / queries on the Technical Bid. The bidder has to respond to the queries within the specified time mentioned in the covering letter.
2.4.6 On the date & time specified for opening of Financial Bid or the Revised Financial Bids as the case may be will be opened on specified date and time.
2.4.7 EVALUATION OF Financial Bids: The Financial Bid should contain the complete bid document with duly filled in Schedule of Financial Quote. Financial Bids opened as above will be checked for arithmetical errors.
2.4.8 The successful bidder shall be issued Letter of Acceptance (LOA) of the bid, and be required to furnish a Performance Guarantee as per General Conditions of Contract, Program Schedule with specific Milestones to be achieved as to complete the work within the stipulated time limit and details of his Technical Staff to be deployed as per ANNEXURE-I
2.4.9 Letter of Award (Work Order) shall be issued to the successful bidder only after receipt of the Performance Guarantee, along with Program Schedule and the details of Technical Staff to be deployed for the work.
2.4.10 Agreement (Contract) consisting of complete tender document including conditions, bill of quantities, technical proposal and specialized services, drawings, if any, and acceptance thereof together with any correspondence leading thereto, shall be drawn and signed with the awardee after issue of Work Order.
2.4.11 Date of start of work shall be reckoned from 7thday from the date of issue of “Letter of Acceptance”.
2.5 BIDDING CAPACITY OF CONTRACTORS
1) The bidding capacity of the contractor should be equal to or more than the estimated cost of the work put to tender. The bidding capacity shall be worked out by the following formula: Bidding Capacity = {[AxNx2]-B} Where, A= Maximum turnover in construction works executed in any one year during the last five years taking into account the completed as well as works in progress. The value of completed works shall be brought to current costing level by enhancing at a simple rate of 7% per annum. N= Number of years prescribed for completion of work for which bids has been invited. B= Value of existing commitments and ongoing works to be completed during the period of completion of work for which bids have been invited.
Page | 9
3. UNDERTAKING BY THE BIDDER
U N D E R T A K I N G
I / We have read and examined the Tender document including terms & conditions, specifications, bill of quantities, drawings and designs, general rules & directions, General Conditions of Contract, Special Conditions of Contract and all relevant other documents, publications and rules referred to in the Conditions of Contract and all other contents in the tender documents for the work.
I / We, hereby tender for execution of the work specified for the Indian Institute of Technology Kharagpur within the time specified and in accordance in all respects with the specifications, designs, drawings and instructions in writing.
We agree to keep the tender open for 120 days from the last date of its submission and not to make any modifications in its terms and conditions. An undertaking as mentioned in Bid Security Declaration Form (Annexure-III) has been deposited. If I / we, fail to furnish the prescribed performance guarantee within prescribed period, I / we agree that the said Director, Indian Institute of Technology Kharagpur or his authorized officer shall without prejudice to any other right or remedy, be at liberty to enforceactions as mentioned in the Bid Security Declaration Form (Annexure-III). Further, if I / we fail to commence work as specified, I / we agree that the Director, Indian Institute of Technology Kharagpur shall without prejudice to any other right or remedy available in law, be at liberty to enforceactions as mentioned in the Bid Security Declaration Form (Annexure-III) and forfeit the performance guarantee absolutely, to execute all the works referred to in the tender documents upon the terms and conditions contained or referred to therein.
Further, I / We agree that in case of enforcement of actions as mentioned in the Bid Security Declaration Form (Annexure-III) and/or Performance Guarantee as aforesaid, I / We shall be debarred for participation in the re-tendering process of the work.
I / We hereby declare that I / We shall treat the tender documents, drawings and other records connected with the work as secret / confidential documents and shall not communicate information derived there-from to any person other than a person to whom I / We am / are authorized to communicate the same or use the information in any manner prejudicial to the safety of the State.
Seal & Signature of Contractor
Postal Address
Dated
Witness
Address
Occupation
Page | 10
ANNEXURE-I
TECHNICAL STAFF OF CONTRACTOR
DISCIPLINE NAME QUALIFICATION EXPERIENCE CONTACT NUMBER
Overall Project In-charge
Engineer - Structure and Civil Works
Engineer – Electrical & Mechanical Works
In-charge - Safety, Health & Environment
Seal & Signature of Contractor
Page | 11
ANNEXURE - II
UNDERTAKING FOR GCC COMPLIANCE
UNDERTAKING
We hereby undertake that we shall fulfill all the terms & conditions within the specified time frame, after the acceptance of our offer in case our offer is accepted; failing which IIT KHARAGPUR may go ahead to take necessary action such as reporting the non-compliance to appropriate Government authorities and barring us from future participation in IIT KHARAGPUR works.
Seal & Signature of Contractor
DATED:
Page | 12
ANNEXURE - III
Bid Security Declaration Form
Date:__________________________Tender No. ________________________________________
To (Insert complete name and address of the purchaser)
I/We,the undersigned, declare that:
I/We understand that, according to your conditions, bids must be supported by a Bid Security Declaration.
I/We, accept that I/we may be disqualified from bidding for any contract with you for a period of one year from the date of notification if I am/We are in a breach of any obligation under the bid conditions, because I/We
a) Have withdrawn/modified/amended, impairs or derogates from the tender, my/our Bid during the period of bid validity specified in the form of Bid; or
b) Having been notified of the acceptance of our Bid by the purchaser during the period of bid validity (i) fail or reuse to execute the contract, if required, or (ii) fail or refuse to furnish the Performance Security, in accordance with the Instruction to Bidders.
I/We understand this Bid Securing Declaration shall cease to be valid if I am/We are not the successful Bidder, upon the earlier of (i) the receipt of your notification of the name of the successful Bidder; or (ii)thirty days after the expiration of the validity of my/ our Bid.
Signed: (insert signature of person whose name and capacity are shown)
In the capacity of (insert legal capacity of person signing the bid Securing Declaration)
Name: (insert complete name of person signing he Bid Securing Declaration)
Duly authorized to sign the bid for an on behalf of (insert complete name of Bidder)
Dated on …………………………………………….day of ……………………………………….. (Insert date of signing)
Corporate seal (where applicable)
Page | 13
ANNEXURE-IV
Format for Net Worth Certificate
It is to certify that as per the audited balance sheet and profit & loss account during the financial year ………………., the net worth of … (individual/farm/company) having registered address at ….…………………………. as on 31.3.2020 is Rs………..…………………….after considering all liabilities. It is further certified that the net worth of the company has not eroded by more than 30% in the last three years ending on 31.3.2020.
Signature of Chartered Accountant
…………..
Name of Chartered Accountant
…………..
Membership No. of ICAI
Date& Seal
Page | 14
ANNEXURE – A
(For Works Contracts, including Turnkey contracts)
(On Company / firm's Letterhead)
Tender No:………………………………… Dated:………………………..……..
CERTIFICATE
I/we have read the clause regarding restrictions on procurement from a bidder of a country which shares a land border with India and on sub-contracting to contractors from such countries and hereby certify that this bidder is not from such a country and will not sub-contract any work to a contractor from such countries unless such contractor is registered with the Competent Authority.
OR (whichever is applicable)
I/we have read the clause regarding restrictions on procurement from a bidder of a country which shares a land border with India and on sub-contracting to contractors from such countries; I/we hereby certify that this bidder is from ____________(Name of Country) and has been registered with the Competent Authority and will not sub-contract any work to a contractor from such countries unless such contractor is registered with the Competent Authority. I/we also certify that this bidder fulfils all the requirements in this regard and is eligible to be considered.
(Copy/ evidence of valid registration by the Competent Authority is to be attached with the bid document)
Signature of the Authorized Person
Date: -----------------------------
Full Name: ----------------------------
Place: ----------------------------
Company Seal: --------------
Page | 15
ANNEXURE – B
DECLARATION OF LOCAL CONTENT
(To be given on Company Letter Head – For tender value upto Rs.10 Crores)
(To be given by Statutory Auditor/Cost Auditor/ Practising Cost Accountant/ Practising Chartered Accountant for tender value in excess of Rs.10 Crores)
Tender No:………………………………… Dated:………………………..……..
To
The Chairman
Departmental Purchase Committee
Department of …………………..
IIT Kharagpur
PIN: 721302
Subject: Declaration of Local Content-reg.
1. Country of origin of Goods being offered:…………………………………………………………
2. We hereby declare that items offered has ……………..% local content.
(Clarification for Local content calculation as per OM No: P-45021/102/2019-BE-II-Part (1) (E-50310), dated 4th March 2021 of Department of Promotion of Industry and Internal Trade, Ministry of Commerce and Industry, Govt. of India.)
3. The details of the location(s) at which local value addition is made are given in the below table;
Sl. No. Name of the item Location(s) of local value addition
1 2 3
”Local Content” means the amount of value added in India which shall, unless otherwise prescribed by the Nodal Ministry, be the total value of the item procured (excluding net domestic indirect taxes) minus the value of the imported content in the item (including all customs duties) as a proportion of the total value, in percent.
Important:
“False declaration will be in breach of Code of Integrity under Rule 175(1)(i)(h) of the General Financial Rules 2017 for which a bidder or its successors can be debarred for up to two years as per Rule 151(iii) of the General Financial Rules 2017 along with such other actions as may be permissible under law.”
Date:
Yours faithfully,
(Signature of the bidder, with Official Seal)
Page | 16
4. Checklist for Documents to be uploaded on https://eprocure.gov.in/eprocure/app
Sl. No. Documents Reference
1. Tender Documents
2. EMD 1.2.5
3. Document support of Bona-fide Business Entity
1.3.3
4. GST Registration Certificate 1.3.3
5. Permanent Account Number 1.3.3
6. Average annual turnover of the bidder as per ITCC or profit and loss
statement for last 5 year
1.3.5
7. Experience Certificate 1.3.2
8. Net worth Certificate 1.3.6
9. ANNEXURES-I_II_III
10. SOQ
Page I 17
SCHEDULE OF QUANTITIES
Civil & Structural
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
1
Clearing grass and removal of the rubbish up to a distance
of 50 m outside the periphery of the area cleared. sqm 5857.00 6.40 37484.80
2
Transplantation of trees with necessary tools, tackles,
manpower, machineries, chemical and other assessories all
complete.
150 to 300 mm dia. Each 25.00 10497.00 262425.00
301 to 600 mm dia. Each 12.00 15745.00 188940.00
601 to 900 mm dia. Each 15.00 20993.00 314895.00
3
Earth work in excavation by mechanical means (Hydraulic
excavator)/manual means over areas (exceeding 30 cm in
depth, 1.5 m in width as well as 10 sqm on plan) including
getting out and disposal of excavated earth lead upto 50 m
and lift upto 1.5 m, as directed by Engineer-in-charge.
All kinds of soil cum 24000.00 181.85 4364400.00
4
Extra rates for quantities of works, executed:
In or under water and/or liquid mud, including pumping out
water as required
a) From 1m to 2m below EGL cum 5332.00 36.37 193924.84
b) From 2m to 3m below EGL cum 4872.00 72.74 354389.28
c) From 3m to 4m below EGL cum 4234.00 109.11 461971.74
d) From 4m to 5m below EGL cum 3342.00 145.48 486194.16
e) From 5m to 6m below EGL cum 2220.00 181.85 403707.00
5
Extra for every additional lift of 1.5 m or part thereof in
excavation /banking excavated or stacked materials - All
kinds of soils
a) From 1.5 m to 3m below EGL cum 7805.00 90.40 705572.00
b) From 3 m to 4.5m below EGL cum 6372.00 180.80 1152057.60
c) From 4.5 m to 6 below EGL cum 3823.00 271.20 1036797.60
6
Filling available excavated earth (excluding rock) in
trenches, plinth, sides of foundations etc. in layers not
exceeding 20cm in depth, consolidating each deposited
layer by ramming and watering, lead up to 50 m and lift
upto 1.5 m.
cum 14389.51 219.65 3160655.87
7
Extra for every additional lift of 1.5 m or part thereof in
excavation /
banking excavated or stacked materials - All kinds of soilscum 1213.89 90.40 109735.66
Name of Work: Construction of Deep & Shallow Water Maneuvering and Seakeeping Basin Facility for OE &
NA:
CIVIL CONSTRUCTION AND MAINTENANCE SECTION
IIT KHARAGPUR
Page I 18
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
8
Providing and laying 200 mm thick compacted bed of dry
brick aggregate of 40 mm thick nominal size including
spreading, well ramming, consolidating and grouting with
jamuna sand, including finishing smooth etc. complete as
per direction of Engineer-in-charge.
cum 1906.95 530.10 1010874.20
9
Providing and laying in position cement concrete of
specified grade excluding the cost of centering and
shuttering - All work up to plinth level :
1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone
aggregate 20 mm nominal size)
cum 897.25 6259.10 5615977.48
10
Making plinth protection 50mm thick of cement concrete
1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone
aggregate 20 mm nominal size) over 75mm thick bed of dry
brick ballast 40 mm nominal size, well rammed and
consolidated and grouted with fine sand, including
necessary excavation, levelling & dressing & finishing the
top smooth.
sqm 287.00 614.05 176232.35
11
Providing and fixing up to floor five level precast cement
concrete string or lacing courses, copings, bed plates,
anchor blocks, plain window sills, shelves, louvers, steps,
stair cases, etc., including hoisting and setting in position
with cement mortar 1:3 (1 Cement : 3 coarse sand), cost of
required Centering complete.
1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded
stone aggregate 20mm nominal size)
cum 12.67 8537.75 108173.29
12
Providing and laying anti termite treatment to bottom
surface ( in case of masonry foundation and basements)
and the sides (upto a height of 300 mm. from bottom) of the
excavation trenches with chemical emulsion by admixing
chloropyrofos emulsifiable concentrates (1% concentration)
with water by weight at the rate of 5 Litres per sq. m. area.
The work shall be carried out as per specification described
in 6.2.1. of code IS 6313 (part -II) 1981. (Mode of
measurment will be the plan area of foundation treated.)
sqm 4582.00 111.86 512542.52
13
Providing and laying in position machine batched and
machine mixed design mix M-30 grade cement concrete for
reinforced cement concrete work, using cement content as
per approved design mix, including
pumping of concrete to site of laying but excluding the cost
of centering, shuttering, finishing and reinforcement,
including admixtures in recommended proportions as per
IS: 9103 to accelerate, retard setting of concrete, improve
workability without impairing strength and durability as per
direction of Engineer-in-charge. All works upto plinth level
cum 4385.48 8067.05 35377886.43
14As above but M-25 grade in all works above plinth and up to
level Vcum 736.13 9400.85 6920247.71
Page I 19
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
15
Centering and shuttering including strutting, propping etc.
and removal of form for :
Foundations, footings, bases of columns, etc. for mass
concrete sqm 1101.18 284.85 313671.12
Walls (any thickness) including attached pilasters,
butteresses, plinth and string courses, etc.sqm 5349.33 609.30 3259346.77
Suspended floors, roofs, landings, balconies and access
platformsqm 2610.12 693.05 1808943.67
As above but above 3.5 m height sqm 1337.01 980.55 1311005.16
Lintels, beams, plinth beams, girders, bressumers and
cantilevers
Plinth beams sqm 684.56 552.05 377911.35
Tie beams at 2nd level sqm 238.78 2277.05 543714.00
Tie beams at crane level sqm 330.20 2277.05 751881.91
Tie beams at roof level sqm 396.00 3139.55 1243261.80
Columns, Pillars, Piers, Abutments, Posts and Struts sqm 3764.79 733.70 2762226.42
Stairs, (excluding landings) except spiral-staircases sqm 33.21 622.35 20668.24
Small lintels not exceeding 1.5 m clear span, moulding as in
cornices, window sills, string courses, bands, copings, bed
plates, anchor blocks and the like.sqm 336.02 284.85 95715.30
16
Steel reinforcement for R.C.C. work including straightening,
cutting, bending, placing in position and binding all
complete upto plinth level.
Thermo Mechanically Treated bars of grade Fe-500D or
more
Kg 434279.18 83.50 36262311.53
17 As above but above plinth Kg 75846.37 83.50 6333171.90
18
Brick work with common burnt clay F.P.S. (non modular)
bricks of class designation 7.5 in foundation and plinth in:
Cement mortar 1:6 (1 cement : 6 coarse sand) cum 357.95 6157.45 2204059.23
19
Brick work with clay flyash F.P.S. (non modular) brick of
class designation 7.5 in superstructure above plinth level up
to floor five level in:
Cement mortar 1:4 (1 cement : 4 coarse sand) cum 618.00 7971.70 4926518.36
Page I 20
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
20
Providing and fixing factory made uPVC door frame made
of uPVC extruded sections having an overall dimension as
below (tolerance±1mm), with wall thickness 2.0 mm (± 0.2
mm), corners of the door frame to be Jointed with
galvanized brackets and stainless steel screws, joints
mitred and Plastic welded. The hinge side vertical of the
frames reinforced by galvanized M.S. tube of size 19 X 19
mm and 1mm (± 0.1 mm) wall thickness and 3 nos.
stainless steel hinges fixed to the frame complete as per
manufacturer’s specification and direction of Engineerin-
charge(i).Extruded section profile size 48x40 mm
m 47.60 221.65 10550.54
21
Providing and fixing 30 mm thick factory made Polyvinyl
Chloride (PVC) door shutter made of styles and rails of a
uPVC hollow section of size 60x30 mm and wall thickness 2
mm (± 0.2 mm), with inbuilt decorative moulding edging on
one side. The styles and rails mitred and joint at the corners
by means of M.S. galvanised/ plastic brackets of size
75x220 mm having wall thickness 1.0 mm and stainless
steel screws. The styles of the shutter reinforced by
inserting galvanised M.S. tube of size 25x20 mm and 1 mm
(± 0.1 mm) wall thickness. The lock rail made up of 'H'
section, a uPVC hollow section of size 100x30 mm and 2
mm (± 0.2 mm) wall thickness fixed to the shutter styles by
means of plastic/ galvanised M.S. 'U' cleats. The shutter
frame filled with a uPVC multi-chambered single panel of
size not less than 620 mm, having over all thickness of 20
mm and 1 mm (± 0.1 mm) wall thickness . The panels filled
vertically and tie bar at two places by inserting horizontally 6
mm galvanised M.S. rod and fastened with nuts and
washers, complete as per manufacturer's specification and
direction of Engineer-in-charge.
sqm 17.60 1978.65 34824.24
Page I 21
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
22
Providing and fixing factory made uPVC white colour sliding
glazed window upto 1.50 m in height dimension comprising
of uPVC multi-chambered frame with in-built roller track and
sash extruded profiles duly reinforced with 1.60 ± 0.2 mm
thick galvanized mild steel section made from roll forming
process of required length (shape & size according to uPVC
profile), appropriate dimension of uPVC extruded glazing
beads and uPVC extruded interlocks, EPDM gasket, wool
pile, zinc alloy (white powder coated) touch locks with hook,
zinc alloy body with single nylon rollers (weight bearing
capacity to be 40 kg), G.I fasteners 100 x 8 mm size for
fixing frame to finished wall and necessary stainless steel
screws etc. Profile of frame & sash shall be mitred cut and
fusion welded at all corners, including drilling of holes for
fixing hardware's and drainage of water etc. After fixing
frame the gap between frame and adjacent finished wall
shall be filled with weather proof silicon sealent over backer
rod of required size and of approved quality, all complete
as per approved drawing & direction of Engineer-in-Charge.
(Single / double glass panes, wire mesh and silicon sealent
shall be paid separately)
Note: For uPVC frame and sash extruded profiles minus
5% tolerance in dimension i.e. in depth & width of profile
shall be acceptable. Variation in profile dimension in higher
side shall be accepted but no extra payment on this account
shall be made.
Three track three panels sliding window with fly proof SS
wire mesh (Two nos. glazed & one no. wire mesh panels)
made of (small series) frame 92 x 44 mm & sash 32 x 60
mm both having wall thickness of 1.9 ± 0.2 mm and single
glazing bead of appropriate dimension (Area of window
upto 1.80 sqm).
sqm 3.60 8954.20 32235.12
23
Structural steel work riveted, bolted or welded in built up
sections, trusses and framed work, including cutting,
hoisting, fixing in position and applying a priming coat of
approved steel primer all complete.
Kg 174963.28 101.75 17802513.74
Page I 22
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
24
Supplying and fixing rolling shutters of approved make,
made of required size M.S. laths, interlocked together
through their entire length and jointed together at the end
by end locks, mounted on specially designed pipe shaft with
brackets, side guides and arrangements for inside and
outside locking with push and pull operation complete,
including the cost of providing and fixing necessary 27.5 cm
long wire springs manufactured from high tensile steel wire
of adequate strength conforming to IS: 4454 - part 1 and
M.S. top cover of required thickness for rolling shutters.
80x1.25 mm M.S. laths with 1.25 mm thick top cover sqm 25.00 2944.10 73602.50
25 Providing and fixing ball bearing for rolling shutters. Each 2.00 419.85 839.70
26
Extra for providing mechanical device chain and crank
operation for operating rolling shutters.
Exceeding 16.80 sqm in area sqm 25.00 1106.55 27663.75
27
Providing and fixing factory made ISI marked steel glazed
doors, windows and ventilators, side /top /centre hung, with
beading and all members such as F7D, F4B, K11 B and
K12 B etc. complete of standard rolled steel sections, joints
mitred and flash butt welded and sash bars tenoned and
riveted, including providing and fixing of hinges, pivots,
including priming coat of approved steel primer, but
excluding the cost of other fittings, complete all as per
approved design, (sectional weight of only steel members
shall be measured for payment). Fixing with 15x3 mm lugs
10 cm long embedded in cement concrete block 15x10x10
cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded
stone aggregate 20 mm nominal size) Doors
Kg 528.00 166.50 87912.00
28
Steel work welded in built up sections/ framed work,
including cutting, hoisting, fixing in position and applying a
priming coat of approved steel primer using structural steel
etc. as required.
In stringers, treads, landings etc. of stair cases, including
use of chequered plate wherever required, all complete Kg 2397.80 93.65 224553.97
In gratings, frames, guard bar, ladder, railings, brackets,
gates and similar works Kg 966.00 131.00 126546.00
29
Providing and fixing hand rail of approved size by welding
etc. to steel ladder railing, balcony railing, staircase railing
and similar works, including applying priming coat of
approved steel primer.
M.S. Tube Kg 3267.75 145.65 475947.79
Page I 23
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
30
Providing and fixing carbon steel galvanised (minimum
coating 5 micron) dash fastener of 10 mm dia double
threaded 6.8 grade (yield strength
480 N/mm2), counter sunk head, comprising of 10 mm dia
polyamide PA 6 grade sleeve, including drilling of hole in
frame , concrete/ masonry, etc. as per direction of Engineer-
in-charge.
10x80 mm Each 653.55 109.00 71236.95
31
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand :
4 graded stone aggregate) finished with a floating coat of
neat cement, including cement slurry, but excluding the cost
of nosing of steps etc. complete.
40 mm thick with 20 mm nominal size stone aggregate sqm 365.69 498.35 182241.61
32Extra for making chequers of approved pattern on cement
concrete floors, steps, landing, pavements etc. sqm 365.69 63.20 23111.61
33
Kota stone slab flooring over 20 mm (average) thick base
laid over and jointed with grey cement slurry mixed with
pigment to match the shade of the slab, including rubbing
and polishing complete with base of cement mortar 1 : 4 (1
cement : 4 coarse sand)
25 mm thick sqm 130.98 1531.85 200641.71
34
Kota stone slabs 20 mm thick in risers of steps, skirting,
dado and pillars laid on 12 mm (average) thick cement
mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey
cement slurry mixed with pigment to match the shade of the
slabs, including rubbing and polishing complete.
sqm 124.71 1810.05 225731.34
35
Providing and laying Ceramic glazed floor tiles of size
300x300 mm of 1st quality conforming to IS : 15622 of
approved make in colours such as White, Ivory, Grey,
Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1
Cement : 4 Coarse sand), Jointing with grey cement slurry
@ 3.3 kg/sqm including pointing the joints with white
cement and matching pigment etc., complete.
sqm 33.29 926.90 30856.50
36
Providing and fixing 1st quality ceramic glazed floor tiles
conforming to IS : 15622 (thickness to be specified by the
manufacturer ) of approved make in all colours, shades
except burgundy, bottle green, black of any size as
approved by Engineer-in-Charge in skirting, risers of steps
and dados over 12 mm thick bed of cement Mortar 1:3 (1
cement: 3 coarse sand) and jointing with grey cement slurry
@ 3.3kg per sqm including pointing in white cement mixed
with pigment of matching shade
complete.
sqm 138.89 927.90 128876.03
Page I 24
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
37
Providing and laying vitrified floor tiles in different sizes
(thickness to be specified by the manufacturer) with water
absorption less than 0.08% and conforming to IS: 15622, of
approved make, in all colours and shades, laid on 20mm
thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing
with grey cement slurry @ 3.3 kg/ sqm including grouting
the joints with white cement and matching pigments etc.,
complete.
Size of Tile 600x600 mm sqm 33.07 1500.55 49623.19
38
Providing and laying Vitrified tiles in different sizes
(thickness to be specified by manufacturer), with water
absorption less than 0.08 % and conforming to I.S. 15622,
of approved make, in all colours & shade, in skirting, riser of
steps, over 12 mm thick bed of cement mortar 1:3 (1
cement: 3 coarse sand), jointing with grey cement slurry @
3.3 kg/ sqm including grouting the joint with white cement &
matching pigments etc. complete.
Size of Tile 600x600 mm sqm 4.57 1545.85 7064.53
39
Providing and fixing precoated galvanised iron profile
sheets (size, shape and pitch of corrugation as approved by
Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated
thickness with zinc coating 120 grams per sqm as per IS:
277, in 240 mpa steel grade, 5-7 microns epoxy primer on
both side of the sheet and polyester top coat 15-18
microns. Sheet should have protective guard film of 25
microns minimum to avoid scratches during transportation
and should be supplied in single length upto 12 metre or as
desired by Engineer in-charge. The sheet shall be fixed
using self drilling /self tapping screws of size (5.5x 55 mm)
with EPDM seal, complete upto any pitch in horizontal/
vertical or curved surfaces, excluding the cost of purlins,
rafters and trusses and including cutting to size and shape
wherever required.
sqm 671.01 627.55 421092.33
40
Supply of TRACDEK Klippon profiled sheeting 406 mm
cover width, 41 mm crests @ 203 mm c/c manufactured
out of 0.55 mm TCT (total coated thickness) SDP coated
Galvalume (275 Mpa yield stress) steel. The sheet shall
have wide pans with stiffening ribs for effective water
shedding and special male/ female ends on side-laps for
purlin support and anti-capillary flute in side lap. The sheet
shall have a hot-dip metallic coating of zinc aluminium alloy
coating mass total of both sides, AZ-150 as per AS 1397 )
having 275 Mpa yield stress. The sheets shall be fixed to
girts with concealed clips and no fasteners to penetrate the
sheeting. The sheets shall be supplied in lengths maximum
upto 6-12 metres to suit site dimensions.
sqm 4071.00 1874.25 7630071.75
Page I 25
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
41 As in 29 above but on vertical surfaces sqm 2145.86 627.55 1346634.44
42
Providing and fixing precoated galvanised steel sheet
roofing accessories 0.50 mm (+0.05 %) total coated
thickness, Zinc coating 120 grams per sqm as per IS: 277,
in 240 mpa steel grade, 5-7 microns epoxy primer on both
side of the sheet and polyester top coat 15-18 microns
using self drilling/ self tapping screws complete :
Ridges plain (500-600 mm) m 120.00 416.30 49956.00
Flashings/aprons. (upto 600 mm) m 1005.00 368.60 370443.00
Gutters (600 mm overall girth) m 140.00 1041.75 145845.00
43
Providing and fixing tiled false ceiling of specified materials
of size 595x595 mm in true horizontal level, suspended on
inter locking metal grid of hot dipped galvanized steel
sections ( galvanized @ 120 grams/ sqm, both side
inclusive) consisting of main "T" runner with suitably spaced
joints to get required length and of size 24x38 mm made
from 0.30 mm thick (minimum) sheet, spaced at 1200 mm
center to center and cross "T" of size 24x25 mm made of
0.30 mm thick (minimum) sheet, 1200 mm long spaced
between main "T" at 600 mm center to center to form a grid
of 1200x600 mm and secondary cross "T" of length 600
mm and size 24x25 mm made of 0.30 mm thick (minimum)
sheet to be interlocked at middle of the 1200x600 mm panel
to form grids of 600x600 mm and wall angle of size
24x24x0.3 mm and laying false ceiling tiles of approved
texture in the grid including, required cutting/making,
opening for services like diffusers, grills, light fittings,
fixtures, smoke detectors etc. Main "T" runners to be
suspended from ceiling using GI slotted cleats of size 27 x
37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50
mm long dash fasteners, 4 mm GI adjustable rods with
galvanised butterfly level clips of size 85 x 30 x 0.8 mm
spaced at 1200 mm center to center along main T, bottom
exposed width of 24 mm of all T-sections shall be pre-
painted with polyester paint, all complete for all heights as
per specifications, drawings and as directed by Engineer-in-
charge.
12.5 mm thick fully Perforated Gypsum Board tile made
from plasterboard having glass fibre conforming to IS: 2095
part I, of size 595x595 mm, having perforation of 9.7x9.7
mm at 19.4 mm c/c with center borders of 48 mm and the
side borders of 30 mm, backed with non woven tissue on
the back side, having an NRC (Noise Reduction Coefficient)
of 0.79, with 50 mm resin bonded glass wool backing.
sqm 255.14 1171.50 298896.51
Page I 26
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
44
Providing and applying 12 mm thick internal cement plaster
in mix 1:4 (1 cement : 4 fine sand) including curing,
scaffolding, etc. complete, ready to receive wall finish.sqm 11040.31 266.85 2946106.72
45
Providing and applying 18 mm thick external plaster at all
heights, in two coats under layer 12 mm thick cement
plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm
thick cement plaster 1:3 (1 cement : 3 coarse sand) finished
rough with sponge including curing, scaffolding, etc.
complete.
sqm 3214.52 416.55 1339008.31
46
Providing and applying 6 mm cement plaster of mix 1:3 (1
cement : 3 fine sand) in ceilings including curing,
scaffolding, etc. complete.
sqm 623.53 227.35 141759.55
47
Distempering with oil bound washable distemper of
approved brand and manufacture to give an even shade:
New work (two or more coats) over and including water
thinnable priming coat with cement primer.
sqm 11663.84 153.45 1789816.25
48
Applying and finishing walls with 100% Premium acrylic
emulsion paint having VOC less than 50 gm/litre and UV
resistance as per IS 15489:2004, Alkali & fungal resistance,
dirt resistance exterior paint of required shade (Company
Depot Tinted) with silicon additives.
New work (Two or more coats applied @ 1.43 litre/10 sqm.
Over and including priming coat of exterior primer applied
@ 0.90 litre/10 sqm.
sqm 3214.52 146.20 469962.82
49
Painting with synthetic enamel paint, having VOC (Volatile
OrganicCompound) content less than 150 grams/ litre, of
approved brand and manufacture, including applying
additional coats wherever required to achieve even shade
and colour. Two coats
sqm 6803.08 75.00 510231.00
50
Providing and laying 175 mm thick C.C. pavement of mix M-
25 with ready mixed concrete from batching plant. The
ready mixed concrete shall be laid and finished with screed
board vibrator, vacuum dewatering process and finally
finished by floating, brooming with wire brush etc. complete
as per specifications and directions of Engineer-in charge.
(The panel shuttering work shall be paid for separately).
(Note:- Cement content considered in this item is @ 330
kg/cum. Excess/less cement used as per design mix is
payable/ recoverable separately).
cum 386.58 8663.05 3348961.87
Page I 27
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
51
Supplying, fitting & fixing UPVC pipes A- Type and fittings
conforming to IS:13592-1992 with all necessary clamps
nails, including making holes in walls, floor etc. cutting
trenches in any soil through masonry concrete structures
etc if necessary and mending good damages including
joining with jointing materails (Spun Yarn,
Valamoid/Bitumen/M-Seal etc) complete.
UPVC pipes 160 mm dia. m 323.60 577.15 186765.74
UPVC Fiitings Plain T 160 mm dia Each 3.00 603.33 1809.99
UPVC Fittings Bends 87.5 degree Each 39.00 480.76 18749.64
52
Boring, providing and installation bored cast-in-situ
reinforced cement concrete piles of grade M-25 of specified
diameter and length below the pile cap, to carry a safe
working load not less than specified, excluding the cost of
steel reinforcement but including the cost of boring with
bentonite solution and temporary casing of appropriate
length for setting out and removal of same and the length of
the pile to be embedded in the pile cap etc. by percussion
drilling using Direct mud circulation (DMC) or Bailer and
chisel technique by tripod and mechanical Winch Machine
all complete, including removal of excavated earth with all
its lifts and leads (length of pile for payment shall be
measured up to bottom of pile cap). Note: Truck Mounted
rotary/TMR/Tubewell boring machine shall not be used.
- 750 mm dia piles
m 360.00 4482.30 1613628.00
53
Providing and laying integral cement based water proofing
treatment including preparation of surface as required for
treatment of roofs, balconies, terraces etc consisting of
following operations:
(a) Applying a slurry coat of neat cement using 2.75 kg/sqm
of cement admixed with water proofing compound
conforming to IS. 2645 and approved by Engineer-in-
charge over the RCC slab including adjoining walls upto
300 mm height including cleaning the surface before
treatment.
(b) Laying brick bats with mortar using broken bricks/brick
bats 25 mm to 115 mm size with 50% of cement mortar 1:5
(1 cement : 5 coarse sand) admixed with water proofing
compound conforming to IS : 2645 and approved by
Engineer-in-charge over 20 mm thick layer of cement
mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with
water proofing compound conforming to IS : 2645 and
approved by Engineer-in-charge to required slope and
treating similarly the adjoining walls upto 300 mm height
including rounding of junctions of walls and slabs.
Page I 28
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
(c) After two days of proper curing applying a second coat
of cement slurry using 2.75 kg/ sqm of cement admixed
with water proofing compound conforming to IS : 2645 and
approved by Engineer-in-charge.
(d) Finishing the surface with 20 mm thick jointless cement
mortar of mix 1:4 (1 cement :4 coarse sand) admixed with
water proofing compound conforming to IS : 2645 and
approved by Engineerin-charge including laying glass fibre
cloth of approved quality in top layer of plaster and finally
finishing the surface with trowel with neat cement slurry and
making pattern of 300x300 mm square 3 mm deep.
(e) The whole surface so finished shall be flooded with
water for a minimum period of two weeks for curing and for
final test.“All above operations to be done in order and as
directed and specified by the Engineer-in-Charge :
With average thickness of 120 mm and minimum thickness
at khurra as 65 mm over raft of storage tank. sqm 368.12 1398.50 514815.82
54
Providing and applying integral crystalline slurry of
hydrophilic in nature for waterproofing treatment to the RCC
structures like retaining walls of the basement, water tanks,
roof slabs, podiums, reservior, sewage & water treatment
plant, tunnels / subway and bridge deck etc., prepared by
mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry :
2 parts water) for vertical surfaces and 3 : 1 (3 parts integral
crystalline slurry : 1 part water) for horizontal surfaces and
applying the same from negative (internal) side with the
help of synthetic fiber brush. The material shall meet the
requirements as specified in ACI 212-3R-2010 i.e by
reducing permeability of concrete by more than 90%
compared with control concrete as per DIN 1048 and
resistant to 16 bar hydrostatic pressure on negative side.
The crystalline slurry shall be capable of self-healing of
cracks up to a width of 0.50mm. The work shall be carried
out all complete as per specification and the direction of the
engineer-in-charge. The product performance shall carry
guarantee for 10 years against any leakage.
For vertical surface two coats @ 0.70 kg per sqm sqm 2118.37 484.45 1026244.35
For horizontal surface one coat @1.10 kg per sqm. sqm 1962.84 373.40 732924.46
55
Supply, transport, loading / unloading, erection, testing and
commissioning of EOT crane - 3T capacity including rails Each 1.00 3591420.00 3591420.00
Page I 29
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
56
Planting of trees ( Avenue plants) in 0.60m dia holea, 1m
deep dug in the ground, mixing the soil with decayed farm
yard/sludge manure. This includes supply of labour, tools &
plants including materials but excluding cost of tree.Each 40.00 139.23 5569.20
57
Maintanance of trees for one year (Avenue Plants) including
watering, trimming, manuring, spraying insecticide and
guarding as required. This includes supply of labour, tools &
plants including materials.
Each 40.00 567.63 22705.20
58
Providing and fixing aluminium work for doors, windows,
ventilators and partitions with extruded built up standard
tubular sections/ appropriate Z sections and other sections
of approved make conforming to IS: 733 and IS: 1285,
fixing with dash fasteners of required dia and size, including
necessary filling up the gaps at junctions, i.e. at top, bottom
and sides with required EPDM rubber/ neoprene gasket etc.
Aluminium sections shall be smooth, rust free, straight,
mitred and jointed mechanically wherever required including
cleat angle, Aluminium snap beading for glazing / paneling,
C.P. brass / stainless steel screws, all complete as per
architectural drawings and the directions of Engineer-in-
charge. (Glazing, paneling and dash fasteners to be paid
for separately) :Powder coated aluminium (minimum
thicknessof powder coating 50 micron)
Kg 420.33 456.30 191796.58
59
For shutters of doors, windows & ventilators including
providing and fixing hinges/ pivots and making provision for
fixing of fittings wherever required including the cost of
EPDM rubber / neoprene gasket required (Fittings shall be
paid for separately) Powder coated aluminium (minimum
thickness of powder coating 50 micron).
Kg 226.22 546.35 123595.30
60
Providing and fixing 12 mm thick prelaminated particle
board flatpressed three layer or graded wood particle board
conforming to IS: 12823 Grade l Type ll, in panelling fixed in
aluminum doors, windows shutters and partition frames with
C.P. brass / stainless steel screws etc. complete as per
architectural drawings and directions of Engineer-in-charge.
Pre-laminated particle board with decorative lamination on
both sides.
sqm 50.16 1046.90 52512.50
61
Providing and fixing glazing in aluminium door, window,
ventilatorshutters and partitions etc. with EPDM rubber /
neoprene gasket etc. complete as per the architectural
drawings and the directions of Engineer-in-charge With
float glass panes of 5.50 mm thickness plain / frosted.
sqm 3.60 1296.40 4667.04
Page I 30
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
62
Filling the gap in between aluminium frame & adjacent
RCC/ Brick/Stone work by providing weather silicon sealant
over backer rod of approved quality as per architectural
drawings and direction of Engineer-in-charge complete. Up
to 5 mm depth & 5 mm width
m 97.60 79.45 7754.32
63
Providing and fixing double glazed hermetically sealed
glazing in aluminium windows, ventilators and partition etc.
with 6 mm thick clear float glass both side, having 12 mm
air gap, including providing EPDM gasket, perforated
aluminium spacers, desiccants, sealant (Both primary and
secondary sealant) etc. as per specifications, drawings and
direction of Engineer-in-charge complete.
sqm 50.52 6399.35 323295.16
64
Providing and fixing 12 mm thick frameless toughened
glass door shutter of approved brand and manufacture,
including providing and fixing top & bottom pivot & double
action hydraulic floor spring type fixing arrangement and
making necessary holes etc. for fixing required door fittings,
all complete as per direction of Engineer-incharge (Door
handle, lock and stopper etc.to be paid separately).
sqm 5.50 4447.90 24463.45
65Providing and fixing bright finished brass hanging type floor
door stopper Each 19.00 106.70 2027.30
66
Providing and fixing aluminium die cast body tubular type
universal hydraulic door closer (having brand logo with ISI,
IS : 3564, embossed on the body, door weight upto 35 kg
and door width upto 700 mm), with necessary accessories
and screws etc. complete.
Each 23.00 1003.50 23080.50
67
Providing and fixing chromium plated brass 100 mm mortice
latch and lock with 6 levers and a pair of lever handles of
approved quality with necessary screws etc. complete. Each 17.00 806.45 13709.65
68
Providing and fixing panic bar / latch (Double point) fitted
with a single body, Trim Latch & Lock on back side of the
Panic Latch of reputed brand and manufacture to be
approved by the Engineer- in- charge, all complete.
Each 2.00 7134.85 14269.70
69
Providing and fixing bright /matt finished Stainless Steel
handles of approved quality & make with necessary screws
etc all complete. -125 mmEach 21.00 98.75 2073.75
70Providing and fixing in position 3.5 m high, 8 inch wide and
2-3 mm thick PVC curtain strips m 12.00 2979.76 35757.12
71
Providing and Placing in position suitable PVC water stops
conforming to IS:12200 for construction/ expansion joints
between two RCC members and fixed to the reinforcement
with binding wire before pouring concrete etc. complete :
Serrated with central bulb (225 mm wide, 8-11 mm thick)
m 977.42 283.20 276805.34
TOTAL 174605289.74
Say Rs. 174605290.00
Page l 31
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
1
Providing and fixing white vitreous china pedestal type water
closet (European type W.C. pan) with seat and lid, 10 litre low
level white P.V.C. flushing cistern, including flush pipe, with
manually controlled device (handle lever), conforming to IS :
7231, with all fittings and fixtures complete, including cutting and
making good the walls and floors wherever required :W.C.pan
with ISI marked white solid plastic seat and lid
Each 5 5260.95 26304.75
2
Providing and fixing white vitreous china flat back half stall urinal
of size 580x380x350 mm with white PVC automatic flushing
cistern, with fittings, standard size C.P. brass flush pipe,
spreaders with unions and clamps (all in C.P. brass) with waste
fitting as per IS :2556, C.I. trap with outlet grating and other
couplings in C.P. brass, including painting of fittings and cutting
and making good the walls and floors wherever required : Single
half stall urinal with 5 litre P.V.C. automatic flushing cistern
Each 3 9360.6 28081.80
3
Providing and fixing wash basin with C.I. brackets, 15 mm C.P.
brass pillar taps, 32 mm C.P. brass waste of standard pattern,
including painting of fittings and brackets, cutting and making
good the walls wherever require:
White Vitreous China Wash basin size 630x450 mm with a single
15 mm C.P. brass pillar tap
Each 5 3087.7 15438.50
4
Providing and fixing stone slab with table rubbed, edges rounded
and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in
urinal partitions by cutting a chase of appropriate width with
chase cutter and embedding the stone in the chase with epoxy
grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand :
4 graded stone aggregate 6 mm nominal size) as per direction of
Engineer-in-charge and finished smooth. Granite stone of
approved shade
Each 3 3216.9 9650.70
5Supplying, fitting and fixing two way Bib Cock with wall flange
(CAT. No. CQT23041 of JAQUAR make or equivalent).Each 5 1185 5925.00
6
Supplying, fitting and fixing Chromium plated Hand
shower(Health Faucet) with Flexible Tube with long1 mtr&wall
hook (CAT. No. ALD563 of Jaquar make or equivalent).Each 5 1301 6505.00
7
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC)
pipes, having thermal stability for hot & cold water supply
including all CPVC plain & brass threaded fittings This includes
jointing of pipes & fittings with one step CPVC solvent cement,
trenching, refilling & testing of joints complete as per direction of
Engineer in Charge.
m
50 mm nominal outer dia pipes 10.00 791.65 7916.50
40 mm nominal outer dia pipes 82.00 536.75 44013.50
Plumbing
Page l 32
32 mm nominal outer dia pipes 43.00 413.7 17789.10
25 mm nominal outer dia pipes 12.00 326.65 3919.80
20 mm nominal outer dia pipes 8.00 253.7 2029.60
15 mm nominal outer dia pipes 5.00 202.85 1014.25
8
Providing and fixing trap of self cleansing design with screwed
down or hinged grating with or without vent arm complete,
including cost of cutting and making good the walls and floors :
100 mm inlet and 100 mm outlet Sand cast iron S&S as per IS:
3989
Each 6 1512.55 9075.30
9 As above but 100 mm inlet and 75 mm outlet Each 4 1579.45 6317.80
10Providing and fixing toilet paper holder :
CP BrassEach 5 583.75 2918.75
11
Providing and fixing PTMT liquid soap container 109 mm wide,
125 mm high and 112 mm distance from wall of standard shape
with bracket of the same materials with snap fittings of approved
quality and colour, weighing not less than 105 gms.
Each 5 158.55 792.75
12
Providing and fixing C.P. brass long body bib cock of approved
quality conforming to IS standards and weighing not less than
690 gms.
15 mm nominal bore
Each 8 552.35 4418.80
13
Providing and fixing C.P. brass stop cock (concealed) of
standard design and of approved make conforming to IS:8931.
15 mm nominal bore
Each 9 606.25 5456.25
14
Providing and fixing 600x450 mm beveled edge mirror of
superior glass (of approved quality) complete with 6 mm thick
hard board ground fixed to wooden cleats with C.P. Brass screws
and washers complete.
Each 3 1283.05 3849.15
15
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink
as per IS:13983 with C.I. brackets and stainless steel plug 40
mm, including painting of fittings and brackets, cutting and
making good the walls wherever required :
Kitchen sink with drain board 510x1040 mm bowl depth 225 mm
Each 1 5851.7 5851.70
16
Providing and fixing square-mouth S.W. gully trap class SP-1
complete with C.I. grating brick masonry chamber with water
tight C.I. cover with frame of 300 x300 mm size (inside) the
weight of cover to be not less than 4.50 kg and frame to be not
less than 2.70 kg as per standard design:
100x100 mm size P type With common burnt clay F.P.S. (non
modular) bricks of class designation 7.5
Each 2 2307 4614.00
Page l 33
17
Supplying, fitting & fixing UPVC pipes A- Type and fittings
conforming to IS:13592-1992 with all necessary clamps nails,
including making holes in walls, floor etc. cutting trenches in any
soil through masonry concrete structures etc if necessary and
mending good damages including joining with jointing materails
(Spun Yarn, Valamoid/Bitumen/M-Seal etc) complete.
m
75 mm dia 27.00 223.72 6040.44
110 mm dia 26.00 298.69 7765.94
160 mm dia 70.00 577.15 40400.50
18
Constructing brick masonry manhole in cement mortar 1:4 ( 1
cement : 4 coarse sand ) with R.C.C. top slab with 1:1.5:3 mix (1
cement : 1.5 coarse sand (zone- III) : 3 graded stone aggregate
20 mm nominal size), foundation concrete 1:4:8 mix (1 cement :
4 coarse sand (zone- III) : 8 graded stone aggregate 40 mm
nominal size), inside plastering 12 mm thick with cement mortar
1:3 (1 cement : 3 coarse sand) finished with floating coat of neat
cement and making channels in cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size) finished with a floating coat of neat cement
complete as per standard design :Inside size 120x90 cm and 90
cm deep including C.I. cover with frame (medium duty) 500 mm
internal diameter, total weight of cover and frame to be not less
than 116 kg (weight of cover 58 kg and weight of frame 58 kg) :
With common burnt clay F.P.S. (non modular) bricks of class
designation 7.5
Each 7 10905.05 76335.35
19
Providing and placing on terrace (at all floor levels) polyethylene
water storage tank, IS : 12701 marked, with cover and suitable
locking arrangement and making necessary holes for inlet, outlet
and overflow pipes but without fittings and the base support for
tank.
Litre 1000 8.8 8800.00
20
Providing and fixing ball valve (brass) of approved quality, High
or low pressure, with plastic floats complete:
25 mm nominal bore Each 2 394 788.00
21Providing and fixing gun metal gate valve with C.I. wheel of
approved 32 mm nominal boreEach 4 581.25 2325.00
22 as above but 40 mm nominal bore Each 4 678.4 2713.60
23Providing and fixing PTMT Bottle Trap for Wash basin and sink.
Each 7 335.25 2346.75
24
Providing and fixing PTMT Waste Coupling for wash basin and
sink, of approved quality and colour.
Waste coupling 31 mm dia of 79 mm length and 62mm breadth
weighing not less than 45 gms
Each 7 99.75 698.25
Total for Plumbing TOTAL 360096.83
360097.00
Page l 34
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
1
Providing and installing roof mounted wind driven natural
turbo ventilators including making suitable cut outs in roofing
sheets, sealing the openings to provide weathertight and
watertight roof. Etc. complete.
1200 CFM capacity, approx. 600 mm diameter
Each 7 7116.20 49813.40
2
Providing , installing, testing and commissioning of Inverter
AC (Make: Daikin/ Hitachi/ Voltas/ Blue Star) Hi Wall units
with suitable refrigerant complete with power cable from the
unit to the power socket.
2.0 TR x 5 STAR - FS324YBTU Each 4 47610.00 190440.00
1.5 TR x 5 STAR - FS318DLTU Each 2 38720.00 77440.00
3Providing and installing wall mounted powder coated stand for
outdoor unitEach 6 649.00 3894.00
4Providing, installing, testing and commissioning of 5 KVA V-
Guard voltage stabilizerEach 6 2205.00 13230.00
5Providing and laying / fixing copper piping for the above Hi
Wall unitsm 70 737.50 51625.00
6 Providing and fixing microcellular pipe insulation Class O m
6.35 ID x 10 mm thick 70 29.50 2065.00
12.5 ID x 10 mm thick 70 33.00 2310.00
25 mm ID x 9 mm thick 70 41.30 2891.00
7
Providing and laying flexible copper cable (3C x 2.5 sq. mm.)
including clamping / fixing to RCC and wall supports. Make:
Polycab
m 70 123.90 8673.00
8
Providing and fixing 25 mm UPVC drain pipe to the required
line and slope including clamping / fixing to RC and wall
supports. Make: Astral
m 70 70.80 4956.00
Total 407337.40
Say Rs. 407337.00
HVAC
Price l 35
RATE AMOUNT RATE AMOUNT
ELECTRICAL
IMPORTANT NOTES :
A
Quantity UR means Unit Rate to be quoted. The quantity shall be as per site requirement
& as directed by client's site engineer.
B
The quantities mentioned in this document are estimated on the basis of drawings
prepared & submitted to client. The contractor has to physically measure, prepare BOQ &
get written approval before procurement of material from client's site engineer.
CThe contractor shall prepare measurement sheet for the work done & get it certified from
clients site engineer. The billing will be done as per certified measurement sheet & P.O.
D No rates (Supply & Installation) change for the quantity variation up to 25%
EMeasurement of LT Busduct shall be done by contractor at site as per actual location &
then the item should be procured.
1 11kV VCB PANEL
1.1
Supply, erection, testing and commissioning of Two panel vaccum switchgear unit (VCB)
with following features:
a) The panel unit should have 11kV,3pole,50Hz,400Amps,250MVA,13.1kA symmentrical
breaking capacity, single phase motor operated & manual spring charging system with
power pack and intelligent quasar metering with RS485 communication facilities as per
IS:2516
b) Power pack 110 Volts DC unit for control circuit supply for each panel.
c) The PT Should be resin cast bus connected in separate bus PT enclosure, resin cast,
dry type having voltage ration 11kV/110V,3phase,3wire,50Hz horizontal draw out type as
per IS 3156. Burden of 100VA and accuracy class as 1.0
d)CT ratio : 100/5+5, Protection class 5P10 and metering accuracy class 1.0
e) Breaker should have E/F, O/C, S/C Protection with microprocessor based E/F, S/C,
O/C IDMTL Relay, along with Master trip for each panel.
f) ON, OFF, Spring charge, Trip circuit healthy, Indication must be in the panel.
g) WTI, OTI,Bunchhole alarm and trip with annunciation facility for each panel.
h) The above VCB should be eredted on masonary trench in angle iron frame including
supply and fixing of angle iron frame.
i) Provision of a earthing trolley.
j) The GA and SLD are to be submitted for verification and approval from institute.
Make: ABB,Schnider,Siemens
No. 1.00 8,00,000 800000.00 0.00 800000.00
2 TRANSFORMER :
2.1
Installation Testing commissioning of 11kV/415V, 500KVA transformer in substation no –
14 which includes filtration of transformer oil of 2500L.
The details of job include: -
i) Testing of BDV
ii) Megger value, voltage ratio at all tap position
iii) Core Balance
iv) Vector group
v) O/C & S/C test and determination of internal impedance
vi) DGA Test report.
No. 1.00 41,000 41000.00 0.00 41000.00
Following precommissioning tests are included in scope of contractor.
Testing of BDV
Megger value, voltage ratio at all tap position
Core Balance
Vector group
O/C & S/C test and determination of internal impedance
DGA Test report.
3 LOW VOLTAGE SWITCH BOARDS :
Supply, Unloading, Installation Testing and Commissioning of following floor mounted TTA
panels as per SLD enclosed. The rate shall include unloading of Panels from transport
vehicle, shifting to the stores or near by site location & then to the location of panels,
including crane hiring charges, lifting shifting tools tackles, manpower, mounting on
supports etc. as directed by site engineer. Work also involves positioning panel on
prepared trench and support channels panel alignment, assembling transport section of
panels, fixing of panels to based channels with fasteners or on floor / wall with anchor
fasteners as per requirements, bus bar & earth bus interconnections, tightening of joints,
bolts, hardware etc. and wiring of loosely supplied components and accessories as
manufacturers instructions, operational checks but excluding supply of structural steel.
(Supply, fabrication & painting of Structural steel has been included separately elsewhere
in the tender). (rate shall include use of hydra, loading, unloading facility for each pannel)
(Make: Siemense/ABB/L&T/Schneider/Legrand)
3.1 MAIN LT PANEL No. 1.00 4,08,480 408480.00 23940.00 23940.00 432420.00
Panel shall be Indoor type with IP42 Protection.
Electrical:
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
Price l 36
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
FORM 3B
14 SWG CRCA
ALUMINIUM BUS
CURRENT DENSITY :- 0.8 AMP/1 SQ. MM.
IP PROTECTION - IP 42 (SUITABLE FOR INDOOR CONDITION)
ALL CABLES- TOP CABLE ENTRIES
AS PER CALCULATION FAULT CURRENT :- 50 KA
All panels Switchgear will be provided with lockout tagout (LOTO)arrangement.
INDICATIONS POSITION
FOR ALL INCOMERS PHASE INDICATION WITH SWITCH POSITION.
FOR ALL OUTGOINGS FOR SWITCH ON INDICATION
PROTECTIONS: SURGE PROTECTION ON INCOMER
SINGLE PHASING PREVENTER ON INCOMING BUS FOR PHASE IN BALANCE AND
SINGLE PHASE PREVENTIONS
METERING
MULTIFUNCTION METER FOR INCOMING SUPPLY BREAKERS
EB INCOMER
800 A FP ACB FOR TRANSFORMER INCOMER
EDO TYPE MICROPROCESSOR BASED WITH LSIGN PROTECTION.
RACKING HANDLE, RACKING INTERLOCK, SAFTY SHUTTER, DOOR SEALING
FRAME,READY TO CLOSED SHUNT TRIP COIL (230V), UNDER VOLTAGE COIL
(415V), TRIP SIGNAL SWITCH, AUX. CONTACTS ( AS REQUIRED).
PROVIDE RYB + ON&OFF&TRIP INDICATION LAMPS AND MFM METER TO THIS
FFEDER
OUTGOINGS
500 A FP MCCB - 1 NOS
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON&OFF&TRIP INDICATION LAMPS
400 A FP MCCB - 1 NOS
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
100 A FP MCCB - 3 NOS
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
80 A FP MCCB - 3 NOS
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
63 A FP MCCB - 4 NOS
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
40 A FP MCCB - 5 NOS
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
32 A FP MCCB - 1 NOS
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
3.2 240 KVAR AUTOMATIC POWER FACTOR CORRECTION No. 1.00 10,21,200 1021200.00 10640.00 10640.00 1031840.00
240 KVAR Effective @ 415 VOLTS,THYRISTERISED APFC PANEL
Panel shall be Indoor type.
FORM 2B
14 SWG CRCA
ALUMINIUM BUS
CURRENT DENSITY :- 0.8 AMP/ 1 SQ. MM.
ALL CABLES- TOP CABLES ENTRIES
DIGITAL VOLTMETER & AMMETER FOR INCOMING SUPPLY BREAKERS
KA RATING :- 50 KA
INDICATIONS POSITION
FOR ALL CAPACITOR STEPS ON OFF INDICATION SHOULD BE PROVIDED
The Switching of Capacitors should be done with the Thyristors.
"APP" Type Capacitors should be used. With suitable voltage (525 volts)
7 % Detuned Reactors should added in a circuit to neutralise the Harmonics
generated in a circuit
Power Factor Controller should have the provision to Monitor the kVARh lagging
and leading values and operate capacitors accordingly. This needs as per new
MSEDCL Circular.
Adequoate Ventilation should be arranged while designing the General Arrangement of
Panel. Proper Lowers and Exhaust fans of required CFM should be used.
INCOMER
500A TP MCCB FOR REAL TIME POWER FACTOR CORRECTION PANEL
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
OUTGOINGS
100 A FP MCCB - 3 NOS (for 50kVAr capacitor bank with thyristerised switching)
Price l 37
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
63 A FP MCCB - 2 NOS (for 25kVAr capacitor bank with thyristerised switching)
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
40 A FP MCCB - 1 NOS (for 20kVAr capacitor bank with thyristerised switching)
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
25 A FP MCCB - 1 NOS (for 10kVAr capacitor bank with thyristerised switching)
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
16 A FP MCCB - 2 NOS (for 5kVAr capacitor bank with thyristerised switching)
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
3.3 FIRE FIGHTING PANEL No. 1.00 1,92,717 192717.00 13300.00 13300.00 206017.00
Panel shall be Indoor type with IP42 Protection.
FORM 3B
14 SWG CRCA
ALUMINIUM BUS
CURRENT DENSITY :- 0.8 AMP/1 SQ. MM.
IP PROTECTION - IP 42 (SUITABLE FOR INDOOR CONDITION)
ALL CABLES- TOP CABLE ENTRIES
AS PER CALCULATION FAULT CURRENT :- 50 KA
All panels Switchgear will be provided with lockout tagout (LOTO)arrangement.
INDICATIONS POSITION
FOR ALL INCOMERS PHASE INDICATION WITH SWITCH POSITION.
FOR ALL OUTGOINGS FOR SWITCH ON INDICATION
PROTECTIONS: SURGE PROTECTION ON INCOMER
SINGLE PHASING PREVENTER ON INCOMING BUS FOR PHASE IN BALANCE AND
SINGLE PHASE PREVENTIONS
METERING
MULTIFUNCTION METER FOR INCOMING SUPPLY BREAKERS
EB INCOMER
80 A FP MCCB - 1 NOS
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
OUTGOINGS
63 A FP MCCB - 2 NOS
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
40 A FP MCCB - 1 NOS
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
16 A FP MCCB - 1 NOS
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
3.4 WATER MANAGEMENT PANEL No. 1.00 2,82,900 282900.00 13300.00 13300.00 296200.00
Panel shall be Indoor type with IP42 Protection.
FORM 3B
14 SWG CRCA
ALUMINIUM BUS
CURRENT DENSITY :- 0.8 AMP/1 SQ. MM.
IP PROTECTION - IP 42 (SUITABLE FOR INDOOR CONDITION)
ALL CABLES- TOP CABLE ENTRIES
AS PER CALCULATION FAULT CURRENT :- 50 KA
All panels Switchgear will be provided with lockout tagout (LOTO)arrangement.
INDICATIONS POSITION
FOR ALL INCOMERS PHASE INDICATION WITH SWITCH POSITION.
FOR ALL OUTGOINGS FOR SWITCH ON INDICATION
PROTECTIONS: SURGE PROTECTION ON INCOMER
SINGLE PHASING PREVENTER ON INCOMING BUS FOR PHASE IN BALANCE AND
SINGLE PHASE PREVENTIONS
METERING
MULTIFUNCTION METER FOR INCOMING SUPPLY BREAKERS
EB INCOMER
80 A FP MCCB - 1 NOS
3 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
OUTGOINGS
40 A FP MCCB - 5 NOS
4 POLE MCCB LSI PROTECTION WITH THERMAL MAGNETIC BASED RELEASE
WITH ADJUSTABLE OVERLOAD & SHORT CKT PROTECTION
PROVIDE RYB + ON,OFF&TRIP INDICATION LAMPS.
Price l 38
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
4 MCB/MCCB & DISTRIBUTION BOARDS:
4.1
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel,
MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar,
neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc.
as required. (But without MCB/RCCB/Isolator)
4.1.1 8 way (4 + 24), Double door Nos. 4.00 4,601 18404.00 0.00 18404.00
4.2
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V,
TPN MCB distribution board of sheet steel, dust protected, duly powder painted, Inclusive
of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting
MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is
normally used where 3 phase outlets are required.)
4.2.1 8 way (4 + 24), Double door Nos. 3.00 7,744 23232.00 0.00 23232.00
4.2.2 12 way (4 + 36), Double door Nos. 4.00 9,828 39312.00 0.00 39312.00
4.3
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit
breaker suitable for inductive load of following poles in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
4.3.1 Single pole Nos. 129.00 199 25671.00 0.00 25671.00
4.3.2 Double pole Nos. 1.00 556 556.00 0.00 556.00
4.3.3 Triple pole Nos. 12.00 826 9912.00 0.00 9912.00
4.3.4 Triple pole and neutral Nos. 8.00 1,092 8736.00 0.00 8736.00
4.3.5 Four pole Nos. 4.00 1,807 7228.00 0.00 7228.00
4.4
Supplying and fixing 40A to 63A rating, 240/415 V, 10 kA, "C" curve, miniature circuit
breaker suitable for inductive load of following poles in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
4.4.1 Triple pole and neutral Nos. 10.00 2,606 26060.00 0.00 26060.00
4.4.2 Four pole Nos. 3.00 2,606 7818.00 0.00 7818.00
4.5
Supplying and fixing 80A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker
suitable for inductive load of following poles in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
4.5.1 Four pole Nos. 1.00 10,356 10356.00 0.00 10356.00
4.6
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V,
residual current circuit breaker (RCCB), having a sensitivity current 300 mA in the existing
MCB DB complete with connections, testing and commissioning etc. as required.
4.6.1 25A Nos. 13.00 2,236 29068.00 0.00 29068.00
4.7
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V,
residual current circuit breaker (RCBO), having a sensitivity current 100 mA in the existing
MCB DB complete with connections, testing and commissioning etc. as required.
4.7.1 40A Nos. 3.00 5,410 16230.00 0.00 16230.00
4.8
Providing and fixing following rating and breaking capacity and pole MCCB with
thermomagnetic release and terminal spreaders in existing cubicle panel board including
drilling holes in cubicle panel, making connections, etc. as required.
4.9 Surge Protection Device
4.9.1
Supplying, installation & marking of surge arrestor/ surge protection device at the main
distribution board after the incoming breaker of type 1+2 tested for Imax 50 kA for three
phase and neutral
Nos. 3.00 19,419 58258.20 0.00 58258.20
4.9.2
Supplying, installation & marking of surge arrestor/ surge protection device at the sub main
distribution board after the incoming breaker of type 2 tested for Imax 40 kA for three
phase and neutral
Nos. 7.00 15,910 111368.18 0.00 111368.18
5 SWITCH BOXES & SWITCH SOCKET
5.1Supplying and fixing following modular switch/ socket on the existing modular plate &
switch box including connections but excluding modular plate etc. as required.
5.1.1 5/6 amps switch No. 99.00 85 8415.00 0.00 8415.00
5.1.2 15/16 A switch No. 30.00 132 3960.00 0.00 3960.00
5.1.3 3 pin 5/6 A socket outlet No. 61.00 111 6771.00 0.00 6771.00
5.1.4 6 pin 15/16 A socket outlet No. 18.00 175 3150.00 0.00 3150.00
5.1.5 Telephone socket outlet No. 14.00 119 1666.00 0.00 1666.00
5.1.6 RJ45 DATA SOCKET No. 14.00 612 8568.00 0.00 8568.00
5.1.7
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth,
metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on
surface or in recess, with chained metal cover for the socket out
let and complete with connections, testing and commissioning etc. as required.
No. 15.00 1232.00 18480.00 0.00 18480.00
Price l 39
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
5.1.8
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth,
metal enclosed plug top alongwith 30 A "C" curve, TPMCB, in sheet steel enclosure, on
surface or in recess, with chained metal cover for the socket out let and complete with
connections, testing and commissioning etc. as required.
No. 26.00 3048.00 79248.00 0.00 79248.00
5.2 CEILLING FAN AND EXHAUST FAN
5.2.1
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated,
ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos.
blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding,
Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery
minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%,
remote or electronic regulator unit for speed control and all remaining accessories
including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation
resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply,
earthing etc. complete as required.
No. 10.00 2,688 26880.00 0.00 26880.00
5.2.2 Supplying and fixing 510mm Exhaust fan including connections. No. 4.00 1,587 6348.00 0.00 6348.00
5.2.3Wall / Column Mounted Heavy Duty Industrial Almonard Fan.
(Makes-CGL / Khaitan).No. 9.00 11,040 99360.00 0.00 99360.00
5.2.4
Supplying and fixing two module stepped type electronic fan regulator on the existing
modular plate switch box including connections but excluding modular plate etc. as
required.
No. 10.00 342 3420.00 0.00 3420.00
5.2.5
Installation, testing and commissioning of ceiling fan, including wiring the down rods of
standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor,
single core cable etc. as required.
No. 10.00 171 1710.00 0.00 1710.00
5.2.6Installation of exhaust fan in the existing opening, including making good the damage,
connection, testing, commissioning etc. as required.
5.2.6.1 510 mm sweep No. 4.00 523 2092.00 0.00 2092.00
5.3Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate
for modular switches in recess etc. as required.
5.3.1 1 or 2 Module (75mmX75mm) No. 88.00 243 21384.00 0.00 21384.00
5.3.2 3 Module (100mmX75mm) No. 41.00 267 10947.00 0.00 10947.00
5.3.3 4 Module (125mmX75mm) No. 3.00 287 861.00 0.00 861.00
5.3.4 6 Module (200mmX75mm) No. 18.00 333 5994.00 0.00 5994.00
5.4Supplying and fixing following Modular base & cover plate on existing modular metal
boxes etc. as required.
5.4.1 1 or 2 Module No. 88.00 114 10032.00 0.00 10032.00
5.4.2 3 Module No. 41.00 128 5248.00 0.00 5248.00
5.4.3 4 Module No. 3.00 138 414.00 0.00 414.00
5.4.4 6 Module No. 18.00 167 3006.00 0.00 3006.00
6 CABLE SYSTEM.
Installation of cables along with associated work like sleeving for cable entry through wall /
slab / road crossing shall not be paid extra. The same shall be considered as cable laying
part of Power, control, earthing cable laying system activity. GI/Hume pipes rates shall be
considered extra.Supply and laying of HT cables in cable ducts/uPVC conduits as required and including
testing and commissioning of the following sizes of 11KV grade multicore
aluminium/copper conductor XLPE/PVC insulated and PVC sheathed armoured cable
conforming to IS : 7098 (Part-II)
6.1 HT cable.
Supply of PVC insulated and PVC sheathed / XLPE
power cable of 11 KV grade enearthed.
6.1.1 3C X 95Sq. mm. Al, 11 kV, Armoured XLPE (UE) Mtr. 50.00 1,084 54200.00 0.00 54200.00
6.2
Laying of one number PVC insulated and PVC sheathed / XLPE
power cable of 11 KV grade of following size direct in ground
including excavation, sand cushioning, protective covering and
refilling the trench etc as required.
6.2.1 Upto 120 sq. mm Mtr. 50.00 438 21900.00 0.00 21900.00
6.3 LT POWER AND CONTROL CABLES :
6.3.1Supply of 1.1KV Grade XLPE/PVC insulated copper/aluminium conductor steel of
armoured/unarmoured power cables as per the specs.
Supply and laying of LT cables in cable ducts/uPVC conduits as required and including
testing and commissioning of the following sizes of 1.1KV grade multicore
aluminium/copper conductor XLPE/PVC insulated and PVC sheathed armoured cable
conforming to IS : 7098 (Part-I) / IS : 1554 (Part-I).
6.3.1.1 1.5 mm² x 3C CU Armoured XLPE Cable Mtr. 2750.00 92 253000.00 0.00 253000.00
6.3.1.2 1.5 mm² x 4C CU Armoured XLPE Cable Mtr. 600.00 106 63600.00 0.00 63600.00
6.3.1.3 2.5 mm² x 4C CU Armoured XLPE Cable Mtr. 70.00 166 11620.00 0.00 11620.00
6.3.1.4 4 mm² x 4C CU Armoured XLPE Cable Mtr. 900.00 227 204300.00 0.00 204300.00
6.3.1.5 6 mm² x 4C CU Armoured XLPE Cable Mtr. 150.00 327 49050.00 0.00 49050.00
6.3.1.6 10 mm² x 4C CU Armoured XLPE Cable Mtr. 170.00 491 83470.00 0.00 83470.00
6.3.1.7 25 mm² x 3.5C AL Armoured XLPE Cable Mtr. 130.00 175 22750.00 0.00 22750.00
6.3.1.8 35 mm² x 3.5C AL Armoured XLPE Cable Mtr. 300.00 219 65700.00 0.00 65700.00
6.3.1.9 50 mm² x 3.5C AL Armoured XLPE Cable Mtr. 200.00 284 56800.00 0.00 56800.00
6.3.1.10 150 mm² x 3.5C AL Armoured XLPE Cable Mtr. 50.00 691 34550.00 0.00 34550.00
6.3.1.11 300 mm² x 3.5C AL Armoured XLPE Cable Mtr. 500.00 1,343 671500.00 0.00 671500.00
6.3.1.12 300 mm² x 3.5C AL Armoured XLPE Cable Mtr. 105.00 1,343 141015.00 0.00 141015.00
Price l 40
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
6.3.2
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV
grade of following size direct in ground including excavation, sand cushioning, protective
covering and refilling the trench etc as required.
6.3.2.1 Upto 35 sq. mm Mtr. 5070.00 323 1637610.00 0.00 1637610.00
6.3.2.2 Above 35 sq. mm and upto 95 sq. mm Mtr. 200.00 338 67600.00 0.00 67600.00
6.3.2.3 Above 95 sq. mm and upto 185 sq. mm Mtr. 50.00 352 17600.00 0.00 17600.00
6.3.2.4 Above 185 sq. mm and upto 400 sq. mm Mtr. 605.00 396 239580.00 0.00 239580.00
6.4 CABLE END TERMINATION
6.4.1 HT Cable Termination.
supplying and making indoor cable end termination with heat shrinkable jointing kit
complete with all accessories including lugs suitable for following size of 3 core, XLPE
aluminium conductor cable of 11 KV grade as required :
6.4.1.1 95 sq. mm Nos. 6.00 8,900 53400.00 1466.00 8796.00 62196.00
6.4.2 LT Cable Termination.
Supplying and making end termination with brass compression gland and aluminium lugs
for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable
of 1.1 KV grade as required.
6.4.2.1 3 X 1.5 sq. mm Nos. 166.00 217 36022.00 89.00 14774.00 50796.00
6.4.2.2 3½ X 25 sq. mm (28mm) Nos. 4.00 250 1000.00 0.00 1000.00
6.4.2.3 3½ X 35 sq. mm (32mm) Nos. 12.00 300 3600.00 0.00 3600.00
6.4.2.4 3½ X 50 sq. mm (35mm) Nos. 4.00 329 1316.00 0.00 1316.00
6.4.2.5 3½ X 150 sq. mm (50mm) Nos. 4.00 555 2220.00 0.00 2220.00
6.4.2.6 3½ X 300 sq. mm (70mm) Nos. 12.00 936 11232.00 0.00 11232.00
6.4.2.7 3½ X 300 sq. mm (70mm) Nos. 2.00 936 1872.00 0.00 1872.00
6.4.2.8 4 X 10 sq. mm (25mm) Nos. 16.00 219 3504.00 0.00 3504.00
6.4.2.9 4 X 2.5 sq. mm Nos. 10.00 224 2240.00 89.00 890.00 3130.00
6.4.2.10 4 X 4 sq. mm Nos. 64.00 269 17216.00 89.00 5696.00 22912.00
6.4.2.11 4 X 6 sq. mm Nos. 10.00 344 3440.00 89.00 890.00 4330.00
6.4.3 Water Proof Termination
Supply, installation of FLP & WP terminations with Double compression type Brass-Nickel
cable gland , lugs & PVC Shrouds. The gland shall be provided with earth tag , ensures
earth continuity between gland and equipment, etc. complete as required.
6.4.3.1 4 X 1.5 sq. mm Nos. 232.00 535 124120.00 118.00 27376.00 151496.00
7 INTERNAL WIRING
7.1
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS
PVC insulated copper conductor, single core cable in surface/ recessed medium class
PVC conduit as required.
7.1.1 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Mtr. 5600.00 146 817600.00 0.00 817600.00
7.1.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Mtr. 1500.00 167 250500.00 0.00 250500.00
7.1.3 2 X 4 sq. mm + 1 X 4 sq. mm earth wire Mtr. 400.00 200 80000.00 0.00 80000.00
8 LIGHT FITTING
Supply, Unloading, Installation, Testing & Commissioning of standard light fittings and
lighting accessories including lamp. The scope shall includes unpacking assembly of
luminaries, providing of all hardware such as chain, nuts, anchor fasteners, bolts, screws,
cleats, clamps, PVC insulated wires / cables from Junction box to lighting fixtures, ceiling
roses ball and socket 'arrangement with J.B., suspension conduit pipe 0.5 m long 19 mm
black MS conduit down rod for light fitting. The cost of fabrication and installation of
MS supports will be the part of this item only. The scope of work also includes any
modifications required to be carried out on the mounting bracket to suit mounting of light
fixtures & any modification inside control gear box / fixture for proper commissioning of
fixture.
All LED Fittings are with Driver, LED luminaries housing/body shall be pressure die cast
aluminium or extruded Aluminium or CRCA as specified along with finished powder
coating, complete with all accessories.
Price l 41
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
8.1
Fixture shall be supplied with the following along with mounting accessories:
- CRCA Powder coated with white housing
- Recess mounted
- Bottom Opening
- High efficacy long life LEDs
- Aesthetic CRCA powder coated bottom frame
- Special translucent high transmisivity, non yellowing HET diffuser
- Non-Integral multi stage CCCV electronic driver with 3kV surge protection. Driver shall
be pre wired upto the terminal block
- Confirms IS 10322 / Part 5 / sec 1 : 1987
- Suitable for 31 W LED (2x2)
- Suitable for 600MM X 600MM Cutout size in Calcium silicate / non walkable false ceiling.
- The LED source used shall be medium/high power complying with LM80 standards &
LED source efficacy >105 lm/w.
- LED lumen output of the luminaire of a minimum of 3000 lumens.
- Similar to Wipro make, CRCO10R038HP57G1
Immaculate+ : Recess Mounted 2ft x 2ft LED
Nos. 45.00 2,714 122130.00 354.00 15930.00 138060.00
8.2
Fixture shall be supplied with the following along with mounting accessories:
- High power, high efficiency Chip On Board(COB) LED module (medium/high power) only
complying with LM80 standards & LED source efficacy >100 lm/w - Surface
mounting type, Bottom Opening including all necessary hardwares/accessories
- High transmisivity, non yellowing PMMA diffuser
- Pressure die cast aluminium housing with special wave shaped radial fins, black powder
coated for superior thermal performance
- Specially designed, easy to install mounting clips
- Non-integral Driver with constant current constant voltage (CVCC), P.F >0.95 and
Surge Protection of atleast 2KV.Driver shall be pre wired upto the terminal block
- Suitable for 15 W LED downlighter
- LED lumen output of the luminaire of a minimum of 1500 lumens.
- Similar to Wipro make, LD06-171-XXX-57WSM
Nos. 14.00 1,696 23744.00 354.00 4956.00 28700.00
8.3
Fixture shall be supplied with the following along with mounting accessories:
- Surface mounting type including all necessary hardwares/accessories
- CRCA Powder coated housing
- Fitting should be with dust proof polycarbonate body, IP66 with frosted ends & gasket
polycarbonate diffuser with transparent prismatic interior & smooth exterior
- All other necessary Accessories
- Suitable for 40 W LED Industrial Capsule Type and outdoor application
- LED lumen output of the luminaire of a minimum of 4000 lumens.
- Similar to Wipro make, LE20-491-XXX-57-G1 Capsule LED
- IP65 Suface / Pendent Mounted LED Luminaries
Nos. 84.00 3,732 313488.00 354.00 29736.00 343224.00
8.4
Fixture shall be supplied with the following along with mounting accessories:
- Surface mounting type including all necessary hardwares/accessories
- CRCA Powder coated housing
- Fitting should be with polycarbonate body, IP40 with frosted ends & gasket
polycarbonate diffuser with transparent prismatic interior & smooth exterior
- All other necessary Accessories
- Suitable for 40 W LED Industrial Batten Type and outdoor application
- LED lumen output of the luminaire of a minimum of 4000 lumens.
- Similar to Wipro make, LL24R-541-XXX-57-CD Optima
LED Batten - 4FT LED Batten
Nos. 92.00 1,696 156032.00 354.00 32568.00 188600.00
8.5
Fixture shall be supplied with the following along with mounting accessories:
- Surface mounting Highbay type including all necessary hardwares/accessories
- High efficacy long life LEDs
- Special translucent high transmisivity, non yellowing PMMA diffuser
- Non-Integral multi stage CCCV electronic driver with 3kV surge protection. Driver shall
be pre-wired upto the terminal block
- Confirms IS 10322 / Part 5 / sec 1 : 1987
- Suitable for 120 WATT LED
- The LED source used shall be medium/high power complying with LM80 standards &
LED source efficacy >105 lm/w.
- LED lumen output of the luminaire of a minimum of 2100 lumens.
- Similar to Wipro make, WIPRO ENTERPRISES (P) LTD LH21-192-060-
57-XX UNO HIGHBAY LIGHT LUMINAIRE
Nos. 75.00 12,113 908475.00 531.00 39825.00 948300.00
8.6
Fixture shall be supplied with the following along with mounting accessories:
- Premium outdoor Under Water Light including all necessary hardwares/accessories
- High efficacy long life LEDs
- Suitable for 18 W LED Decorative under water Type
- The LED source used shall be medium/high power complying with LM80 standards &
LED source efficacy >105 lm/w.
- LED lumen output of the luminaire of a minimum of 1500 lumens.
- Similar to Wipro make, LU03-211-030-30-XX
Nos. 112.00 26,462 2963744.00 354.00 39648.00 3003392.00
9 EARTHING SYSTEMS
EARTHING STATIONS:
9.1
Price l 42
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
Supply, Installation of earth stations with necessary all materials, labour, excavation & all
civil works, etc. as per IS/IEC etc. Complete with all required hardware as mention below.
9.1.1
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and
providing masonry enclosure with cover plate having locking arrangement and watering
pipe etc. with charcoal/ coke and salt as required.
Nos. 23.00 5,308 122084.00 0.00 122084.00
9.1.2
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and
providing masonry enclosure with cover plate having locking arrangement and watering
pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as
required.
Mtrs. 4.00 5,146 20584.00 0.00 20584.00
9.1.3
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and
providing masonry enclosure with cover plate having locking arrangement and watering
pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as
required.
Mtrs. 2.00 5,146 10292.00 0.00 10292.00
9.2 EARTHING STRIPs/WIREs:
Supply, laying of hot dipped galvanized (GI)/copper bare earth conductor bar / flexible
wire /strip of following sizes along the cable trenches or cable trays or fixing to walls or
structures or buried individually in paved/unpaved areas but excluding civil work finishing
after layering of earthing strips etc. The installation shall include welded joints with 4'' over
lapping of the strips. Welded joints shall be used for G.I. strips. Welded joints after welding
shall be painted with anticorrosive black bitumen paint , applying anti corrosive primer
paint and two coat each of bituminous paint for buried earth strip. Excavation & backfilling
of soil for burying the strip wherever applicable is paid extra as per the rate of excavation
and backfilling rate. Jumper 150 mm x 50 mm shall be provided at every 10 meter interval
for main earthing strip under instruction of engg. in charge and jumper rate paid extra.
9.2.1
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth
electrode, including connection/terminating(Jointing shall be done by overlapping and with
welded joints with 4'' over lapping of the strips)
Mtrs. 1000.00 131 131000.00 0.00 131000.00
9.2.2Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc.
as required.Mtrs. 1186.00 206 244316.00 0.00 244316.00
9.3LIGHTNING PROTECTION SYSTEM (CONVENTIONAL LIGHTNING ARRESTOR):
Air Terminal ( Horizantal ) :
9.3.1
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I.
tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes
etc.complete as required.
No. 5.00 448 2240.00 0.00 2240.00
9.3.2Fixing of lightning conductor finial (single prong) with base plate including holes etc.
complete as required.No. 5.00 280 1400.00 0.00 1400.00
9.3.3Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other
metallic object) by riveting / nut bolting/ sweating and soldering etc as required.No. 16.00 93 1488.00 0.00 1488.00
9.3.4Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for
lightning conductor complete as required.(For horizontal run)Mtrs. 1600.00 104 166400.00 0.00 166400.00
9.3.5Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for
lightning conductor complete as required.(For vertical run)Mtrs. 200.00 163 32600.00 0.00 32600.00
9.3.6Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long,
with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.Mtrs. 16.00 102 1632.00 0.00 1632.00
10 HOT DIPPED GALVANIZED IRON CABLE TRAYS
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray
(Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%,
in convenient sections, joined with connectors, suspended from the ceiling with G.I.
suspenders including G.I. bolts & nuts, etc.as required.
10.1 CABLE TRAYS
10.1.1 100mm wide cable tray perforated type (1.6 mm thick & 50 mm high collar) Mtrs. 550.00 599 329450.00 0.00 329450.00
10.1.2 150mm wide cable tray perforated type (1.6 mm thick & 50 mm high collar) Mtrs. 30.00 644 19320.00 0.00 19320.00
10.1.3 300 mm wide cable tray perforated type (1.6 mm thick & 50 mm high collar) Mtrs. 65.00 875 56875.00 0.00 56875.00
10.1.4 450 mm wide cable tray perforated type (2 mm thick & 50 mm high collar) Mtrs. 40.00 1,213 48520.00 0.00 48520.00
10.1.5 600 mm wide cable tray ladder type (2 mm thick & 62.5 mm high collar) Mtrs. 25.00 1,752 43800.00 0.00 43800.00
10.1.6 750 mm wide cable tray ladder type (2 mm thick & 62.5 mm high collar) Mtrs. 3.00 2,079 6237.00 0.00 6237.00
11 INSTALLATION OF UPS SYSTEM
9.1
Price l 43
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
Unloading, Installation, testing & Commissioning of the following rating of UPS System
including unloading, transportation from store to site ,errection insulation, testing of UPS
System including Battery and Battery rack errection & Installation under the supervision of
supplier of UPS. The scope also includes supply and installation of the flexible wire from
SDF enclosure to UPS and UPS to Main UPS DB. Flexible wire shall be as per the
recommendation of UPS supplier.
11.1 UPS SYSTEM
11.1.1
Unloading at site, handling, erection, alignment and other associated work of 20 kVA UPS
under the supervision of supplier's commissioning engineer. UPS shall have three phase
input as well as output.
No. 1.00 356540.00 1180.00 1180.00 357720.00
11.2 ISOLATOR FOR UPS.
11.2.1
Supply, installation of 16 kA, 40A TP MCCB+N, with rotary handle in enclosure made up
of 1.6mm thick CRCA sheet, pretreated in seven tank process, powder coated with paint
thickness not less than 100 micron ( Shade RAL 7032 ). The MCCB shall be interlocked to
prevent the enclosure Door being opened unless the MCCB in OFF position and Also
Enclosure shall be provided with facilities for Padlocking in the OFF position Cable end
box shall be provided for incoming and outgoing cables.
Makes - Siemens / Schneider
No. 2.00 13,366 26732.00 413.00 826.00 27558.00
11.3Supply & installation of cable of suitable size from UPS isolator to UPS & from UPS to
isolator. (Distance Between Isolator to UPS & UPS to isolator will be max. 5 Mtr.)
11.3.1 4 Runs x 1 core x 6 mm² CU XLPE flexible leads for 20 KVA UPS Mtrs. 20.00 92 1840.00 33.00 660.00 2500.00
12 MISCELLANEOUS ITEMS :
12.1
Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2
coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at
the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including
inscription duly engraved as required.
Nos. 10.00 530 5300.00 0.00 5300.00
12.2
Supplying and fixing cable route marker with 10 cm X 10 cm X 5mm thick G.I. plate with
inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and
fixing the same in ground as required.
Nos. 10.00 383 3830.00 0.00 3830.00
12.3 Safety items
Safety Equipment's: Supply, Installation of below mention safety equipment including all
labour and materials etc., complete as per directions of Engineer-In-Charge.
12.3.1Sand buckets with floor stand and sand (set of 4 buckets of 9 Ltr. capacity) Stand size :
1.5 M x 0.9 M x 0.6 M stand shall be painted with epoxy paint as per IS requirement.Set 1.00 5,065 5065.00 118.00 118.00 5183.00
12.3.2 Caution boards ( 433V each) Nos. 1.00 407 407.00 118.00 118.00 525.00
12.3.3
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at
least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single
red colour on front side as required.
Nos. 1.00 226 226.00 118.00 118.00 344.00
12.3.4 Rubber mats of 11 KV grade 2 Mtrs x 1 Mtrs x 6 mm Thick Nos. 2.00 2,578 5156.00 118.00 236.00 5392.00
12.3.5 Rubber Hand Gloves pair ( 11 KV Grade ) Nos. 1.00 760 760.00 118.00 118.00 878.00
12.3.6Shock treatment chart with teak wood frame and glass cover as approved by Electrical
Inspectorate. In English & Local language.Nos. 1.00 679 679.00 590.00 590.00 1269.00
12.3.7 First aid box with standard items Nos. 1.00 814 814.00 0.00 814.00
12.3.8 Dry powder type fire extinguisher of 5 Kg. Capacity Nos. 1.00 10,856 10856.00 118.00 118.00 10974.00
12.3.9
Supply, Installation of 4.5kg capacity CO2 type fire extinguishers complete with mounting
brackets, spray nozzles, connecting pipes, "OPEN/CLOSE" valves with all other
necessary accessories complete as required.
Nos. 1.00 4,750 4750.00 118.00 118.00 4868.00
12.3.10 Electrical single line diagram (As Built drawing) with teak wood frame and glass cover. Nos. 1.00 2,036 2036.00 118.00 118.00 2154.00
12.4 Structural Steel Fabrication
Supply, transport, unloading, shifting & Fabrication of steel sections and erection of MS
base frames, MS angle channels, flat etc. for supporting various items of equipment such
as various panels/switchgear, dummy panels, adaptor boxes addition support for proper
cable termination, MS Fabricated cable trays, push button stations, junction boxes, light
fittings, DB etc. The scope include welding, bolting, chipping , grouting etc., including
applying one antirust coat of approved primer and two finished coats of approved paint
with primer & paint, breaking and finishing of walls, floors etc. Contractor has to apply one
coat of antirust paint (Red-oxide ) before installation. The scope is inclusive of minor civil
work as required, supply of GI hardware materials, consumables, tools & tackles and
necessary labour with supervision but not limited to, and complete as per approved
drawings, specification and directions of Engineer-In charge. The scope also includes
transportation of material from owner’s issue point to actual place of work by contractor's
own lifting and transporting arrangement.
Tons 3.00 76,700 230100.00 24.00 72.00 230172.00
3,56,540
Price l 44
RATE AMOUNT RATE AMOUNT
INSTALLATIONAMOUNTQTYSR. NO. DESCRIPTION UNIT
SUPPLY
12.5
Making masonry cable trench with floor cutting making 5' inch wall (both side). Size 800
mm width X 800 mm depth x 3000 mm length for erection of 2 panel 11kV VCB on trench
and HT cable laying.
Mtr 4.00 2,931 11724.00 0.00 11724.00
12.6
Supply and Laying of 100mm dia class B G.I. pipe in underground trench, along walls for
cable protection.
Make: TATA. JINDAL, BANSAL
Mtr 60.00 1,065 63900.00 0.00 63900.00
13 Gripple Hangers System -
13.1 M10 Eyebolt with Nut & Washer (2 No Each) Nos. 36.00 94 3384.00 8.00 288.00 3672.00
13.2 M10 Nut & Washer (2No. Each) Nos. 36.00 15 540.00 8.00 288.00 828.00
13.3 GHF NO.4 LOOP WIRE 5.0 MTR Nos. 18.00 1,464 26352.00 120.00 2160.00 28512.00
TOTAL WITH TAX 1,50,58,429 2,89,391 1,53,47,820
Price l 45
A Hydrant System (Refer attached technical data sheets)
1
Supplying, fixing, testing and commissioning of The Pipes of sizes 150mm & below shall be
M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel
pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto
350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above
150 NB mtr 380 2,385.00 906300
80 NB mtr 30 1,432.24 42967
25 NB mtr 24 439.53 10549
-
2Supplying,testing, installing & commissioning of BUTTERFLY VALVE (MANUAL) with C I
body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified-
150 NB Nos 4 5,442.00 21768
-
3
Supply, fixing, testing and commissioning of Single headed SS-304 fire hydrant valve as
per IS: 5290 (ISI Marked Type-A) with 80 mm N.B. flanged inlet, brass spindle, 63 mm dia
instantaneous type SS. coupling blank cap & chain. Including tapping from wet riser
complete as required.
Nos 8 6,422.43 51379
-
4
Supply, fixing, testing and commissioning of swinging type First Aid hose reel in red
colour with 25mm dia x 30 mts long and below mentioned size heavy duty rubber water
hose terminating with ABS nozzle of 5 mm outlet with shut off valve as per IS: 8090 -
1976 complete with drum and brackets for fixing on walls, bolts & nuts conforming to IS:
884 (ISI Makred) complete as required. Nos
8 10,663.59 85309
-
5
Supply, fixing, testing and commissioning of RRL Hose pipe, 63 mm dia and 15 mts long,
conforming to IS: 636 Type-A (ISI marked) suitable for bursting pressure not less than
35.7 Kg/Sqcm. type A with SS-304 heavy duty instantaneous type coupling (Pair male &
female parts) conforming to IS: 903 (ISI makred).. Nos
16 5,933.34 94933
-
6
Supply, fixing, testing and commissioning of 63 mm dia instantaneous pattern branch
short SS-304 branch pipe as per IS: 903 (ISI marked) 20 mm dia nozzle, suitable for inter
connection to hose pipes coupling complete as required. Nos
8 2,259.81 18078
-
7
Supply, fixing, testing and commissioning of fire cabinet of size not less than 0.75 x 0.6 x
0.25 mtr made out of M.S. sheet not less than 1.5 mm thick having central opening and
4 mm thick glazed acryclic sheet doors (Two nos.) suitably marked on the outside 'with
the letters "FIRE HOSE" including necessary locking arrangement and painting in red
colour suitable to accommodate, 2 nos 15 mtr long Hose pipe, branch pipe, nozzle and
painted in red along with GI support angles for internal hydrants. Nos
8 6,500.97 52008
-
8
Supply, fixing, testing and commissioning of brass body Ball valve with lever of pressure
rating 300 PSIg, including providing necessary union/flange and making proper
connection.
-
25 NB Nos 8 680.98 5448
-
7 Supply, fixing of Fire man Axe Nos 8 751.49 6012
-
8
Structural steel work riveted, bolted or welded in built up sections, trusses and framed
work, including cutting, hoisting, fixing in position and applying a priming coat of approved
steel primer all complete.
Kgs 2000 101.75 203500
-
B Automatic Sprinkler System (Refer attached technical data sheets) -
-
1
Supplying, fixing, testing and commissioning of The Pipes of sizes 150mm & below shall be
M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel
pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto
350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above
-
80 NB mtr 72 1,432.24 103121
65 nB mtr 0 970.24
50 NB mtr 0 770.64
40 NB mtr 0 558.53
25 NB mtr 96 439.53 42195
-
2
Installation, testing, & commissioning of Quartzoid bulb Standard response, Standard
coverage sprinklers to be Operated at 68 Deg C, K80 FM Approved /UL Listed upright
type
Nos 35 551.57 19305
Fire protection and Alarm System.
RATE AMOUNTQTY SR. NO. DESCRIPTION UNIT
Price l 46
-
3
Supply, fixing, testing and commissioning of FM approved/ UL listed Alarm control valve
with automatic Alarm Gong to be connected with control valve, drain, test valve as
per manufacturer's specifications complete as required. Including matching flanges,
nut bolts, gaskets, etc.
-
80 NB Nos 1 33,076.76 33077
-
4
Supply, fixing, testing and commissioning of FM/UL listed Flow switch on sprinkler riser for
Aerosol area and shall be connected to fire alarm panel through cable. Cable shall be
measured seperately.
-
80 NB Nos 1 7,766.54 7767
-
5Supply, installation, testing and commissioning of IS 14846 OS & Y , Rising Spindle
Gate valve, PN 10, With flanges nut bolts, etc.-
80 NB Nos 1 10,699.29 10699
-
6
Supply, fixing, testing and commissioning of brass body Ball valve with lever of pressure
rating 300 PSIg, including providing necessary union/flange and making proper
connection.
-
25 NB Nos 2 680.98 1362
-
7
Structural steel work riveted, bolted or welded in built up sections, trusses and framed
work, including cutting, hoisting, fixing in position and applying a priming coat of approved
steel primer all complete.
Kgs 2000 101.75 203500
-
C Fire water Pumping System (Refer attached technical data sheets) -
-
1Supply, Installation Testing commissioning of End suction 96 m3/hr 70 m head, Main
electric Pump along with accessories. Nos 1 2,72,748.00 272748
-
2Supply, Installation Testing commissioning of End suction 96 m3/hr 70 m head, Diesel
Engine Standby Pump with fuel tank and other accessories Nos 1 5,68,893.78 568894
-
3Supply, Installation Testing commissioning of Vertical inline, Electric operated 10.8 m3/hr
70m head, Jockey pump with accessoriesNos 1 98,639.10 98639
-
4Supply, Installation Testing commissioning of MCC panel for above listed pumps as per
attached electrical single line diagram.Nos 1 2,24,088.90 224089
-
5
Supplying, fixing, testing and commissioning of The Pipes of sizes 150mm & below shall be
M.S. ‘C’ class as per IS : 1239 and pipes size above 150mm shall be welded black steel
pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto
350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above
-
150 NB mtr 24 2,385.00 57240
100 NB mtr 24 1,784.00 42816
50 NB mtr 12 917.07 11005
40 NB mtr 12 664.65 7976
-
6Supply, installation, testing and commissioning of IS 14846 OS & Y , Rising Spindle
Gate valve, PN 10, With flanges nut bolts, etc.-
150 NB Nos 2 43,346.94 86694
100 NB Nos 2 25,012.85 50026
50 NB Nos 1 10,220.77 10221
40 NB Nos 1 8,566.22 8566
-
7
Supply, installation, testing and commissioning of NON - RETURN VALVE with dual
plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as
specified.
-
100 NB Nos 2 6,093.99 12188
40 NB Nos 1 7,309.86 7310
-
8 Supply, installation, testing and commissioning of Y type Strainer -
150 NB Nos 2 18,525.92 37052
50 NB Nos 1 6,310.57 6311
-
9
Structural steel work riveted, bolted or welded in built up sections, trusses and framed
work, including cutting, hoisting, fixing in position and applying a priming coat of approved
steel primer all complete.
kg 3000 101.75 305250
-
D Fire Extinguishers (Refer attached technical data sheets) -
1 FIRE EXTINGUISHER 9KG ABC TYPE Nos 0 3,409.50
-
2 FIRE EXTINGUISHER 6KG ABC TYPE Nos 11 2,827.44 31102
Price l 47
-
3 FIRE EXTINGUISHER 4.5KG CO2 TYPE Nos 3 7,841.51 23525
-
4 FIRE EXTINGUISHER 9LTR. FOAM TYPE Nos 1 2,827.44 2827
-
E Fire Alarm System
1
Supplying, installation, testing and commissioning of micro processor based intelligent
addressable main fire alarm panel, central processing unit with the following loop modules
and capable of supporting not less than 240 devices (including detectors) and minimum
120 detectors per loop and loop length up to 2 km, network communication card, minimum
320 character graphics/ LCD display with touch screen or other keypad and minimum 4000
events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50
hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger.
The panel shall have facility to connect printer to printout log and facility to have seamless
integration with analog/digital voice evacuation system (which is part of the schedule of
work under SH: PA System) and shall be complete with all accessories . The panel shall be
compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per
specifications.Two Loop Panel.
nos 1 2,38,907.00 238907
2Supplying, installation, testing & commissioning of addressable manual call point complete
as required. Please refer attached technical data sheet.nos 8 3,859.00 30872
3Supplying, installation, testing & commisssioning of intelligent addressable programmable
sounder complete as required. Please refer attached technical data sheet.nos 8 2,638.00 21104
4
Supply, Installation, testing commissing of addressable Monitor Module,Operating
Temperature-20 ºC to +60 ºC with back box & mounting accessories. Please refer
attached technical data sheet.
nos 8 4,107.46 32860
5
Supply, Installation, testing commissing of Addressable Smoke Detector with built in LED,
mounting base complete with all connection etc. Please refer attached technical data
sheet.
nos 25 1,654.84 41371
6
Supplying, installation, testing & commissioning of heat detector operating at 54ºC/57ºC
with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete
with all connection etc. as required. Please refer attached technical data sheet.
nos 8 1,561.88 12495
7
Supplying, installation, testing & commissioning of addressable beam detector with short
circuit isolator (inbuilt or seperate) complete with emitter and receiver including connections
with remote test features etc complete as required. Please refer attached technical data
sheet.
nos 4 74,778.00 299112
8Supplying, installation, testing & commissioning of fault isolator complete with base as
required.nos 4 3,257.00 13028
9
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with
annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer
sheath complete as required.
Mtrs 1200 141.00 169200
-
F Spares -
-
1 FIRE EXTINGUISHER 6KG ABC TYPE Nos 1 4,416.80 4417
-
2 FIRE EXTINGUISHER 4.5KG CO2 TYPE Nos 1 12,439.31 12439
-
3
Supply of RRL Hose pipe, 63 mm dia and 15 mts long, conforming to IS: 636 Type-A
(ISI marked) suitable for bursting pressure not less than 35.7 Kg/Sqcm. type A with SS-
304 heavy duty instantaneous type coupling (Pair male & female parts) conforming to IS:
903 (ISI makred)..
Nos 2 11,042.01 22084
4Supplying, installation, testing & commissioning of fault isolator complete with base as
required.Nos 2 1,524.41 3049
5
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with
annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer
sheath complete as required.
Nos 1 1,106.25 1106
TOTAL 4685797.30
Say, Rs. 4685797.00
Page l 48
1Supply, Installation, Testing & Commissioning of Negative suction pump-100m3/hr, VFD
18m-14m head with all accessories. Make of pumps- Kirloskar, Crompton.Nos 2 75826.8 151654
2Supply, Installation, Testing & Commissioning of MCC panel for 2 pumps. Refer attached
electrical single line diagram.Nos 1 61261.2 61261
3Supply, Installation, Testing & Commissioning of plastic Priming Tank 200 ltrs (Sintex or
equivalent)Nos 1 12637.8 12638
4
A/G Piping : Supplying, installing and testing & commissioning above ground Mild Steel
Galvanized Pipes of Heavy class ERW of following sizes conforming to IS 1239 C- class (&
IS 3589,6.35 mm thick) including painting with two coats of fire red enamel paint as per IS-
5 Shade 536, over a coat of epoxy primer as per specifications complete with and testing to
hydrostatic pressure of to 1.5 times the working pressure. All work shall be carried out as per
approved shop drawing, specifications and instruction of engineer in charge. Rate shall be
inclusive of fittings.150 NB mtrs 220 3802.05 836451
65 NB mtrs 18 1363.74 24547
50 NB mtrs 36 1078.14 38813
5Supply, installation, testing and commissioning of IS 14846 OS & Y , Rising Spindle
Gate valve, PN 10, With flanges nut bolts, etc. Refer attached technical data sheet.
150 NB Nos 2 26994.912 53990
100 NB Nos 2 15705.858 31412
6
Supplying, fixing, testing and commissioning of following sizes Motorized Butterfly Valve with
CI Body, SS Disc,O - ring and minimum PN-16 pressure rating , conforming to BS 5155, IS
13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20mA electric
signal and providing similar transduced feedback output to control system as required. Refer
attached technical data sheet.65 NB Nos 4 16544 66176
7
Supplying,testing, installing & commissioning of BUTTERFLY VALVE (MANUAL) with C I
body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. Refer attached
technical data sheet.150 NB Nos 5 5442 27210
8Supplying,testing, installing & commissioning of Foot valves including nuts, bolts, neoprene
nitrile gasket, companion flanges etc.complete with all accessories. Refer attached technical
data sheet.150 NB Nos 2 5500.656 11001
50 NB Nos 2 2569.329 5139
9Supply, installation, testing and commissioning of NON - RETURN VALVE with dual
plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as
specified. Refer attached technical data sheet.100 NB Nos 2 4581 9162
50 NB Nos 1 5719.854 5720
10Supply, installation, testing and commissioning of Basket type Strainer including nuts,
bolts, neoprene nitrile gasket, companion flanges etc.complete with all accessories. Refer
attached technical data sheet.150 NB Nos 1 18052.062 18052
11Supply, fixing, testing and commissioning of brass body Ball valve with lever of pressure
rating 300 PSIg, including providing necessary union/flange and making proper connection.
Refer attached technical data sheet.
50 NB Nos 4 2542.554 10170
12Supply, installation, testing and commissioning of Monitor Module. Refer attached
technical data sheet.Nos 4 4230.45 16922
13
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core
cable in the existing surface/ recessed steel/ PVC conduit as required. 2C x 1.5 sq. mm mtrs 1,200 41 49200
14Structural steel work riveted, bolted or welded in built up sections, trusses and framed work,
including cutting, hoisting, fixing in position and applying a priming coat of approved steel
primer all complete.
Kgs 3,000 101.75 305250
Water Transfer System
RATE AMOUNTQTY SR. NO. DESCRIPTION UNIT
Page l 49
RATE AMOUNTQTY SR. NO. DESCRIPTION UNIT
15Supply, installation, testing and commissioning of Radar type level Sensors. Refer
attached technical data sheet.Nos 4 249409.125 997637
16Supply, installation, testing and commissioning of Float type level Sensors. Refer
attached technical data sheet.Nos 8 31416 251328
17Supply, installation of LCD Display for level Sensors. 3 "x 1" Display. Letter size minimum
1". Make Epson, HP, equivalent.Nos 1 89999.7 90000
18
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray
(Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in
convenient sections, joined with connectors, suspended from the ceiling with G.I.
suspenders including G.I. bolts & nuts, etc.as required.
100mm wide cable tray perforated type (1.6 mm thick & 50 mm high collar)
m 800 599 479200
19
Supplying and making end termination with brass compression gland and aluminium lugs for
following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1
KV grade as required.3 X 10 sq. mm (22mm) No 16 211 3376
20
Supply, installation of Filteration system including alum & hypo dosing & sand filters,
(CAPACITY 100 M3/HR), Operating Period-20 hrs. /day, ALUM DOISNG SYSTEM Capacity-
0-20 lit/hr @ 3 kg/cm2, HYPO DOISNG SYSTEM Capacity- 0-10 lit/hr @ 3 kg/cm2.
TREATED WATER QUALITY:
pH- 6.5 to 7.5.
Total Suspended Solid- 5 mg/lit
Nos 1 2531725 2531725
TOTAL 6088032.60
Say, Rs, 6088033.00
Page l 50
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
1
Demolishing brick work manually/ by mechanical means
including stacking of serviceable material and disposal of
unserviceable material within 50 metres lead as per direction of
Engineer-in-charge.In cement mortar.
cum 73.34 1469.90 107802.47
2
Demolishing R.C.C. work manually/ by mechanical means
including stacking of steel bars and disposal of unserviceable
material within 50 metres lead as per direction of Engineer - in-
charge.
cum 56.94 2534.70 144325.82
3
Dismantling cement asbestos or other hard board ceiling or
partition walls including stacking of serviceable materials and
disposal of unserviceable materials within 50 metres lead.sqm 62.17 42.00 2611.14
4
Earth work in excavation by mechanical means (Hydraulic
excavator) /manual means in foundation trenches or drains (not
exceeding 1.5 m in width or 10 sqm on plan), including
dressing of sides and ramming of bottoms, lift upto 1.5 m,
including getting out the excavated soil and disposal of surplus
excavated soil as directed, within a lead of 50 m. All kinds of
soil.
cum 56.81 252.30 14333.16
5
Filling available excavated earth (excluding rock) in trenches,
plinth, sides of foundations etc. in layers not exceeding 20cm in
depth, consolidating each deposited layer by ramming and
watering, lead up to 50 m and lift upto 1.5 m.
Cum 5.00 219.65 1098.25
6
Supplying and filling in plinth with sand under floors, including
watering, ramming, consolidating and dressing complete. Cum 24.53 1953.05 47908.32
7(i)1:3:6 (1 Cement : 3 coarse sand (zone-III):6 graded stone
aggregate 20 mm nominal size).cum 11.57 6126.25 70880.71
8
Providing and laying in position machine batched and machine
mixed design mix M-25 grade cement concrete for reinforced
cement concrete work, using cement content as per approved
design mix, including pumping of concrete to site of laying but
excluding the cost of centering, shuttering, finishing and
reinforcement, including admixtures In recommended
proportions as per IS: 9103 to accelerate, retard setting of
concrete, improve workability without impairing strength and
durability as per direction of Engineer-in-charge.(Note :-
Cement content considered in this item is 330 kg/cum. Excess/
less cement used as per design mix is payable/recoverable
separately).
All works upto plinth level cum 22.91 7997.30 183218.14
All works above plinth level upto floor V level cum 34.97 9400.85 328747.72
9Centering and shuttering including strutting, propping etc. and
removal of form for all heights.
Foundations, footings, bases of columns, etc. for mass
concrete sqm 27.50 284.85 7833.38
Demolition and Reconstruction:
Part A : Civil Works
Page l 51
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
Suspended floors, roofs, landings, balconies and access
platform sqm 145.00 693.05 100492.25
Lintels, beams, plinth beams, girders, bressumers and
cantilevers. sqm 111.10 552.05 61332.76
Columns, Pillars, Piers, Abutments, Posts and Struts sqm 53.25 733.70 39069.53
10
Steel reinforcement for R.C.C. work including straightening,
cutting, bending, placing in position and binding all complete
upto any level.Thermo-Mechanically Treated bars of grade Fe-
500D or more.
Kg 6945.60 83.50 579957.60
11
Brick work with clay fly ash F.P.S. (non modular) brick of class
designation 7.5 in superstructure above plinth level up to floor
five level in :Cement mortar 1:6 (1 cement : 6 coarse sand) cum 52.42 7752.90 406407.02
12
Supplying fitting and fixing of Hexagonal Chicken Mesh of
approved quality with necessary nails etc.at all levels & in any
floor complete in all respect. as per instruction of Engineer in
charge.
sqm 510.10 30.30 15456.03
13Cement plaster in course sand with 20 mm cement plaster of
mix (i) 1:4 (1 cement: 4 coarse sand)sqm 510.10 379.70 193684.97
14
Providing and fixing Ist quality ceramic glazed wall tiles
conforming to IS: 15622 (thickness to be specified by the
manufacturer), of approved make, in all colours, shades except
burgundy, bottle green, black of any size as approved by
Engineer-in-Charge, in skirting, risers of steps and dados, over
12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse
sand) and jointing with grey cement slurry @ 3.3kg per sqm,
including pointing in white cement mixed with pigment of
matching shade complete.
sqm 32.76 1030.30 33752.63
15
Providing and laying Vitrified tiles in different sizes (thickness to
be specified by manufacturer), with water absorption less than
0.08 % and conforming to I.S. 15622, of approved make, in all
colours & shade, in skirting, riser of steps, over 12 mm thick
bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing
with grey cement slurry @ 3.3kg/sqm including grouting the
joint with white cement & matching pigments etc.
complete.Size of Wall Tile 600x600 mm
sqm 71.68 1030.30 73851.90
Page l 52
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
16
Providing and fixing mineral fibre false ceiling tiles at all heights
of size 595X595mm of approved texture, design and pattern.
The tiles should have Humidity Resistance (RH) of 99%, Light
Reflectance > 85%, Thermal Conductivity k = 0.052 - 0.057
w/m K, Fire Performance as per (BS 476 pt - 6 &7)in true
horizontal level suspended on
interlocking T-Grid of hot dipped all round galvanized iron
section of 0.33 mm thick (galvanized @120 gsm) comprising of
main T runners of 15x32 mm of length 3000 mm, cross T of
size 15x32mm of length 1200 mm and secondary intermediate
cross T of size 15x32 mm of length 600 mm to form grid
module of size 600x600 mm suspended from ceiling using
galvanized mild steel item (galvanised@80gsm)
50 mm long 8mm outer diameter M-6 dash fasteners, 6 mm
diameter fully threaded hanger rod up to 1000 mm length and L-
shape level
adjuster of size 85x25x2 mm, spaced at 1200 mm centre to
centre along main ‘T’. The system should rest on periphery
walls /partitions with the help of GI perimeter wall angle of
size24x24X3000 mm made of 0.40 mm thick sheet, to be fixed
to the wall with help of plastic rawl plug at 450 mm centre to
centre & 40 mm long dry wall S.S.
screws. The exposed bottom portion of all T-sections used in
false ceiling support system shall be pre-painted with polyester
baked paint, for all heights. The work shall be carried out as per
specifications, drawings and as per directions of the engineer-
incharge.
With 16 mm thick beveled tegular mineral fibre false ceiling tile
(NRC 0.55 to 0.6)sqm 64.80 2000.85 129655.08
17(a)
Providing and fixing factory made uPVC door frame made of
uPVC extruded sections having an overall dimension as below
(tolerance±1mm), with wall thickness 2.0 mm (± 0.2 mm),
corners of the door
frame to be Jointed with galvanized brackets and stainless
steel screws, joints mitred and Plastic welded. The hinge side
vertical of the frames reinforced by galvanized M.S. tube of size
19 X 19 mm and 1mm (± 0.1 mm) wall thickness and 3 nos.
stainless steel hinges fixed to the frame complete as per
manufacturer’s specification and direction of Engineerin-
charge(i).Extruded section profile size 48x40 mm
meter 10.10 221.65 2238.67
Page l 53
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
17(b)
30 mm thick factory made Polyvinyl Chloride (PVC) door
shutter made of styles and rails of a uPVC hollow section of
size 60x30 mm and wall thickness 2 mm (± 0.2 mm), with
inbuilt decorative moulding edging on one side. The styles and
rails mitred and joint at the corners by means
of M.S. galvanised/ plastic brackets of size 75x220 mm having
wall thickness 1.0 mm and stainless steel screws. The styles of
the shutter
reinforced by inserting galvanised M.S. tube of size 25x20 mm
and 1 mm (± 0.1 mm) wall thickness. The lock rail made up of
'H' section, a
uPVC hollow section of size 100x30 mm and 2 mm (± 0.2 mm)
wall thickness fixed to the shutter styles by means of plastic/
galvanised
M.S. 'U' cleats. The shutter frame filled with a uPVC multi-
chambered single panel of size not less than 620 mm, having
over all thickness of
20 mm and 1 mm (± 0.1 mm) wall thickness . The panels filled
vertically and tie bar at two places by inserting horizontally 6
mm galvanised M.S. rod and fastened with nuts and washers,
complete as
per manufacturer's specification and direction of Engineer-in-
charge.
sqm 3.15 1978.65 6232.75
18
Providing and applying white cement based putty of average
thickness 1 mm, of approved brand and manufacturer, over the
plastered wall surface to prepare the surface even and smooth
complete.
sqm 147.43 115.15 16976.56
19
Applying one coat of water thinnable cement primer of
approved brandand manufacture on wall surface Water
thinnable cement primer
Sqm 147.43 60.00 8845.80
20
Wall painting with premium acrylic emulsion paint of interior
grade, having VOC (Volatile Organic Compound ) content less
than 50 grams/ litre of approved brand and manufacture,
including applying additional coats wherever required to
achieve even shade and colour. Two coats
Sqm 147.43 113.90 16792.28
21
Finishing walls with Acrylic Smooth exterior paint of required
shade: Old work (Two or more coat applied @ 1.67 ltr/ 10 sqm)
on existing cement paint surface
Sqm 60.00 164.70 9882.00
22
Finishing walls with Acrylic Smooth exterior paint of required
shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm
over and including priming coat of exterior primer applied @
2.20 kg/10 sqm)
Sqm 137.41 164.70 22631.43
23
Painting with synthetic enamel paint, having VOC (Volatile
OrganicCompound) content less than 150 grams/ litre, of
approved brand and manufacture, including applying additional
coats wherever required to achieve even shade and colour.
Two coats
Sqm 5.40 75.00 405.00
Page l 54
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
24(a)
Providing and fixing factory made ISI marked steel glazed
doors, windows and ventilators, side /top /centre hung, with
beading and all members
such as F7D, F4B, K11 B and K12 B etc. complete of standard
rolled steel sections, joints mitred and flash butt welded and
sash bars tenoned and riveted, including providing and fixing of
hinges, pivots, including priming coat of approved steel primer,
but excluding the cost of other fittings, complete all as per
approved design, (sectional weight of only steel members shall
be measured for payment). Fixing with 15x3 mm lugs 10 cm
long embedded in cement concrete block 15x10x10 cm of C.C.
1:3:6 (1 Cement : 3 coarse
sand : 6 graded stone aggregate 20 mm nominal size) Window
kg 60.00 166.50 9990.00
(b)
Providing and fixing M.S. grills of required pattern in frames of
windows etc. with M.S. flats, square or round bars etc. including
priming coat
with approved steel primer all complete.Fixed to steel windows
by welding
kg 86.40 165.30 14,281.92
25(a)
Providing and fixing IS : 12817 marked stainless steel butt
hinges with stainless steel screws etc. complete :75x47x1.80
mm
each 8.00 56.60 452.80
(b)
Providing and fixing aluminium handles, ISI marked, anodised
(anodic coating not less than grade AC 10 as per IS : 1868)
transparent or dyed
to required colour or shade, with necessary screws etc.
complete :100 mm
each 8.00 52.85 422.80
(c)
Providing and fixing aluminium tower bolts, ISI marked,
anodised (anodic coating not less than grade AC 10 as per IS :
1868 ) transparent or dyed
to required colour or shade, with necessary screws etc.
complete :100x10 mm
each 4.00 58.15 232.60
(d)
Providing and fixing aluminium sliding door bolts, ISI marked
anodised (anodic coating not less than grade AC 10 as per IS :
1868), transparent or dyed to required colour or shade, with
nuts and screws
etc. complete :250x16 mm
each 4.00 231.70 926.80
Page l 55
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
26(a)
Providing and fixing aluminium work for doors, windows,
ventilators and partitions with extruded built up standard tubular
sections/ appropriate Z sections and other sections of approved
make conforming to IS: 733 and IS: 1285, fixing with dash
fasteners of required dia and size, including necessary filling up
the gaps at junctions, i.e. at top, bottom and sides with required
EPDM rubber/ neoprene gasket etc. Aluminium sections shall
be smooth, rust free, straight, mitred and jointed mechanically
wherever required including cleat angle, Aluminium snap
beading for glazing / paneling, C.P. brass / stainless steel
screws, all complete as per architectural drawings and the
directions of Engineer-in-charge. (Glazing, paneling and dash
fasteners to be paid for separately) :Powder coated aluminium
(minimum thicknessof powder coating 50 micron) Frame .
kg 500.00 456.30 228150
(b)
For shutters of doors, windows & ventilators including
providing and fixing hinges/ pivots and making provision for
fixing of fittings wherever required including the cost of EPDM
rubber / neoprene gasket required (Fittings shall be paid for
separately) Powder coated aluminium (minimum thickness of
powder coating 50 micron).
kg 80.00 546.35 43708.00
(c)
Providing and fixing 12 mm thick prelaminated particle board
flatpressed three layer or graded wood particle board
conforming to IS: 12823 Grade l Type ll, in panelling fixed in
aluminum doors, windows shutters and partition frames with
C.P. brass / stainless steel screws etc. complete as per
architectural drawings and directions of Engineer-in-charge.
Pre-laminated particle board with decorative lamination on both
sides.
sqm 35.00 1046.90 36641.50
Providing and fixing glazing in aluminium door, window,
ventilatorshutters and partitions etc. with EPDM rubber /
neoprene gasket etc. complete as per the architectural
drawings and the directions
of Engineer-in-charge With float glass panes of 5.50 mm
thickness plain / frosted
sqm 15.00 1296.40 19446.00
Page l 56
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
27
Providing and laying APP (Atactic Polypropylene Polymer)
modified prefabricated five layer 3 mm thick water proofing
membrane, black finished reinforced with non-woven polyester
matt consisting of a coat of bitumen primer for bitumen
membrane @ 0.40 litre/sqm by the same membrane
manufacture of density at 25°C, 0.87-0.89 kg/
litre and viscocity 70-160 cps. Over the primer coat the layer of
membrane shall be laid using Butane Torch and sealing all
joints etc, and preparing the surface complete. The vital
physical and chemical parameters of the membrane shall be as
under : Joint strength in longitudinal and transverse direction at
23°C as 650/ 450N/5cm. Tear strength in longitudinal and
transverse direction as 300/250N. Softening point of membrane
not less than 150°C. Cold flexibility shall be upto -2°C when
tested in accordance with ASTM, D - 5147. The laying of
membrane shall be got done through the authorised applicator
of the manufacturer of membrane :3 mm thick
sqm 98.13 512.95 50335.78
28
Providing and fixing stainless steel ( Grade 304) railing made
of Hollow tubes, channels, plates etc., including welding,
grinding, buffing, polishing and making curvature (wherever
required) and fitting the same withnecessary stainless steel
nuts and bolts complete, i/c fixing the railing with necessary
accessories & stainless steel dash fasteners , stainless steel
bolts etc., of required size, on the top of the floor or the side of\
waist slab with suitable arrangement as per approval of
Engineer-incharge, (for payment purpose only weight of
stainless steel members shall be considered excluding fixing
accessories such as nuts, bolts, fasteners etc.).
Kg 160.00 575.45 92072.00
29
Disposal of building rubbish / malba / similar unserviceable,
dismantled or waste materials by mechanical means, including
loading, transporting, unloading to approved municipal
dumping ground or as approved by Engineer-in-charge, beyond
50 m initial lead, for all leads including all lifts involved.
Cum 133.39 138.85 18521.20
3141604.77
1Dismantling E.P. or Anglo-Indian W.C.
Each 1.00 53.55 53.55
2 Dismantling urinal. Each 2.00 39.27 78.54
3Dismantling wash basin with brackets with or without waste
fittings.Each 2.00 41.65 83.30
4
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC)
pipes, having thermal stability for hot & cold water supply,
including all
CPVC plain & brass threaded fittings, including fixing the pipe
with clamps at 1.00 m spacing. This includes jointing of pipes &
fittings with one step CPVC solvent cement and testing of joints
complete as per direction of Engineer in Charge..
Sanitary & Plumbing
Page l 57
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
i) 25 mm nominal outer dia Pipes metre 50.00 369.20 18460.00
ii) 15 mm nominal outer dia Pipes metre 15.00 241.55 3623.25
5Providing and fixing gun metal gate valve with C.I. wheel of
approved quality (screwed end) :
(a) 25 mm nominal bore Each 04 428.20 1712.80
6
A) Supplying, fitting & fixing UPVC pipes A- Type and fittings
conforming to IS:13592-1992 with all necessary clamps nails,
including making holes in walls, floor etc. cutting trenches in
any soil through masonry concrete structures etc if necessary
and mending good damages including joining with jointing
materails (Spun Yarn, Valamoid/Bitumen/M-Seal etc) complete.
a) 110 mm. Dia. metre 64.00 298.69 19116.16
b) 75 mm. Dia. metre 25.00 223.72 5593.00
7
(c) Supply of UPVC pipes (B Type) & fittings conforming to IS
13592-1992. Plain Floor Trap with Top tile & Strainer.75 mm Nos 10 203.49 2034.90
8
Providing and fixing White vitreous china extended wall
mounting closet of size 710x 370x 770 mm of approved shape
including providing & fixing white vitreous china cistern with
dual flush,seat cover & fiting,of flusing capacity and cistern
fittings,nuts,bolts and gasket ctc complete. (Cat no : CRUSE -
Cat No : S1012135 Strap 300mm ,Cat No : B1520110 of
CERA make or equivalent)
Each 1.00 14155.00 14155.00
9
Supplying,fitting and fixing Flat back urinal (half stall urinal) in
white vitreous chinaware of approved make in position with
brass screws on 75 mm x 75mm x75mm wooden blocks
complete. 345mm x280mm x690 ( Cat No : 96008 of
HINDWARE make or equivalent)
Each 2.00 8586.00 17172.00
10
Supplying, fitting and fixing urinal flush pipe fittings of approved
brand.C.P. urinal flush pipe fittings range of one(Urinal Valve
auto closhing system with built in control cock & wall flange
No:( PRS-077 of JAQUAR)
Nos. 02 3026.00 6052.00
11
Providing and fixing PTMT 15 mm Urinal spreader size
95x69x100 mm with 1/2" BSP thread and shapes, weighing not
less than 60 gms.
Each 2.00 106.50 213.00
12
Supplying, fitting and fixing white vitreous china best quality
approved make wash basin with C.I. brackets on 75 mm X 75
mm wooden blocks with C.P. nut 32 mm dia. and painting the
brackets with two coats of approved paint. 580 mm X 450 mm
size.(PARRYWARE ,CARDIFF, Cat No : C0480(SP)/81(CTH)
Basin ,Cat No : C0375 Pedestal or equivalent )
Nos. 02 5211.00 10422.00
13
Supplying, fitting and fixing pillar Cock (Auto closhing System
with built in control cock with wall flange) (Model No. PRS-031
of JAQUAR make or equivalent).
Nos. 02 2223.00 4446.00
14
Supplying, fitting and fixing Chromium plated angular Stop
Cock with wall flange (CAT. No. CQT23059 of JAQUAR make
or equivalent).
Nos. 06 894.00 5364.00
Page l 58
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
15
Supplying, fitting and fixing two way Bib Cock with wall flange
(CAT. No. CQT23041 of JAQUAR make or equivalent). Each 2 1185.00 2370.00
16
Supplying, fitting and fixing Chromium plated Hand
shower(Health Faucet) with Flexible Tube with long1 mtr&wall
hook (CAT. No. ALD563 of Jaquar make or equivalent).Nos. 01 1301.00 1301.00
17
Supplying, fitting and fixing Single Towel Rail 450mm long
(CAT. No.. : ACN- 1111BNM of JAQUAR make or
equivalent)
Nos. 02 1315.00 2630.00
18
Supplying, fitting and fixing of Double coat Hook with Brush
screw.(CAT. No.. : ACN- 1161N of JAQUAR make or
equivalent)
Each 1 546.00 546.00
19
Providing and fixing PTMT liquid soap container 109 mm wide,
125 mm high and 112 mm distance from wall of standard
shape with bracket of the same materials with snap fittings of
approved quality and colour, weighing not less than 105 gms.
Each 3 137.85 413.55
20
Supplying, fitting and fixing porcelain toilet paper holder(Toilet
paper roll holder ) l (Cat No. : ACN-1155N of JAQUAR make
or equivalent)
Each 01 575.00 575.00
21
Providing and fixing PTMT Bottle Trap for Wash basin and
sink. Bottle trap 38 mm single piece moulded with height of 270
mm, effective length of tail pipe 260 mm from the centre of the
waste coupling, 77 mm breadth with 25 mm minimum water
seal, weighing not less than 263 gms
Each 4.00 348.60 1394.40
22
Providing and fixing 600x450 mm beveled edge mirror of
superior glass (of approved quality) complete with 6 mm thick
hard board ground fixed to wooden cleats with C.P. Brass
screws and washers complete.
Each 2 1283.05 2566.10
23
Supplying,fitting and fixing approved brand P.V.C.
CONNECTOR white flexible, with both ends coupling with
heavy brass C.P. nut, 15 mm dia. (v) 900 mm long
Each 5 174.93 874.65
Page l 59
Sl.
No.Description of items Unit Qty Rate(Rs.)
Amount
(Rs.)
24
Constructing Inspection pit of inside measurement 600mm X
600mm X upto 600mm (depth) with 250 mm thick 1st. class
brick work in cement mortar (1:4) on all sides, bottom of the pit
consisting of 100 mm thick cement concrete (1:3:6) with stone
chips over a layer of jhama brick flat soling,15 mm thick (1:4)
cement plaster to inside walls and out-side walls upto G.L. and
20 mm.thick (1:4) plaster to bottom of the pit, providing
necessary invert with cement concrete (1:3:6) with stone chips
as per direction, neat cement finishing to entire internal
surfaces, top of the pit covered with 100 mm thick R.C.C. slab
(1:1.5:3) with stone chips and necessary reinforcements upto
1% and shuttering including 6 mm thick cement plaster (1:4) in
all external surfaces of the slab and one 560 mm dia. R.C.C.
manhole cover of approved make supplied, fitted and fixed in
the slab with necessary fittings, necessary earthwork in
excavation in all sorts of soil, filling sides of the pit with earth
and removing spoils after work complete in all respect with all
costs of labour and materials.With Pakur variety.
Each 03 8421.63 25264.89
25
Providing and fixing 18 mm thick gang saw cut, mirror
polished,premoulded and prepolished, machine cut for kitchen
platforms, vanity counters, window sills, facias and similar
locations of required size,approved shade, colour and texture
laid over 20 mm thick base cement mortar 1:4 (1 cement : 4
coarse sand), joints treated with white cement,mixed with
matching pigment, epoxy touch ups, including rubbing, curing,
moulding and polishing to edges to give high gloss finish etc.
complete at all levels. Udaipur green marble/ Zebra black
marble Area of slab upto 0.50 sqm
sqm 5.00 2777.40 13887.00
26 Supplying, fitting and fixing S.S round grating.100 mm. Each 4 73.78 295.12
27
Providing and fixing PTMT Waste Coupling for wash basin and
sink, of approved quality and colour. Waste coupling 38 mm dia
of 83 mm length and 77mm breadth, weighing not less than 60
gms
Each 4 118.50 474.00
161171.21
3302775.98
33,02,776.00
Part (B) Rs.
Total (A+B) Rs.
Say Rs.
Page l 60
Summary Sheet
Sr. No Item Decription
1 Civil & structural
2 Plumbing
3 HVAC
4 Electrical
5 Fire protection & alarm
6 Water transfer system
7 Demolition & reconstruction
GRAND TOTAL
6088033
3302776
204797150
Cost Estimate
174605290
360097
407337
15347820
4685797
FIRST FLOOR PLAN (+4.20m LVL.)
VOID
ROOF
SLO
PEDO
WN
1:7
ROOF
SLO
PEDO
WN
1:7
ROOF
SLO
PEDO
WN
1:7
600060006000600060006000600060006000600060006000600060006000600060006000 48004600 4600 6760 4830 4830
7150
6250
6250
6750
5850
6000
4230
4653
6200
6422
6424
A
A
F
F
VOID
RCC T
IE BE
AM
RCC T
IE BE
AM
RCC T
IE BE
AM
VOID VOID VOID
RCC T
IE BE
AM
RCC T
IE BE
AM
RCC T
IE BE
AM
RCC T
IE BE
AM
RCC T
IE BE
AM
RCC T
IE BE
AM
2.50m WIDE CHHAJJA / ROOF
FL +5.20 M
UP
PANELS
UP
D6 D6R=168T=280
DN
STAIRVOID
B
B
C
C
D
D
E
E
GG
FIREEXTINGUISHERS
PUMP ROOM18.37m x 6.80m
PANE
L ROO
M3.
10m
x 6.
80m
INSTRUMENTATIONROOM
RAMP UPSLOPE 1:10
FORKLIFTBATTERY
CHARGINGAREA
VERT
ICAL
PER
FORA
TED
SHEE
TS
GROUND FLOOR PLAN
STAIRVOID
R=175T=280
DN
WAL
L MO
UNTE
D AI
R CU
RTAI
N
WAL
L MO
UNTE
D AI
R CU
RTAI
N
WATERFILTRATION
SYSTEM
ACCESS LADDER
servi
ce du
ct
FLOOR CUTOUT WITH HEAVY DUTY MS COVERS
600x600 FLOOR CUTOUT WITH HEAVYDUTY MS COVER
Ø 100 PVC VENT PIPE WITH VENT COWL (ONEFOR EACH COMPARTMENT OF STORAGE TANK)
ED
RS
D1
D2 D4 D4
EXISTING DOOR
D4
D4 D2 D2
D3
600060006000600060006000600060006000600060006000600060006000600060006000 48004600 4600 6760 4830 4830
7150
6250
6250
6750
5850
6000
4230
4653
6200
6422
6424
A
A
F
F
STORM WATER DRAIN
W1
D3D3D3D3
MODEL MAKING AREA
LIF
TING
BEAM
3D PRINTING ROOM
PLA
METAL
PVC CURTAIN PVC CURTAIN
UP
SINK
ED
D3
D2
W1
LASER CUTTINGROOM
WC
WC
UR
UR
JANITOR
WB
WB
GENTS TOILET
WC
JANITOR
TOILET FORPHYSICALLY
CHALLANGED
WB
WB
LADIES TOILET
2.4 m WIDEPASSAGE
UP
SERVICE DUCT
UR
WC
D5
D4T
D6 D6D6 D6D6 D6
D3TD4T
UP
PORCH
R=167T=300
CEILING MOUNTED AIR CURTAIN
D3
OFFICE
RAMP UPSLOPE 1:10
R=153T=300
R=153T=300
SD1
D3
R=187.5T=270
DN
trenc
h
servi
ce du
ct
trenc
h
trenc
h
UP
- 1.50 M LVL
+ 0.00 M LVL
+ 0.00 M LVL
+ 0.00 M LVL
UPR=153T=300
FIRE PUMPS ROOM
DRINKING WATER
R=168T=280
UP
B
B
C
C
D
D
E
E
GGD3
STORE ROOMbelow
staircase
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE· FIRE EXTINGUISHERS
FIREEXTINGUISHER
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE· FIRE EXTINGUISHERS
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE· FIRE EXTINGUISHERS
WALL MOUNTED· HOSE REEL· HOSE BOX· SINGLE HYDRANT VALVE
PVC CURTAIN PVC CURTAIN
CHAMBER
CHAMBER
SECTION G-G
FRONT ELEVATION
DEPARTMENT OF OCEAN ENGINEERING AND NAVAL ARCHITECTURE
SECTION A-A
PVC VENTCOWL
PVC VENT PIPE(TWO FOR EACH
COMPARTMENT OFSTORAGE TANK)
+5.80m LVL
+3.20m LVL
APPROX.
APPROX.
SECTION F-F
PVC VENTCOWL
PVC VENT PIPE(TWO FOR EACH
COMPARTMENT OFSTORAGE TANK)
+4.30m LVL
INSTRUMENTATIONROOM
STORM WATERDRAIN
APPROX.
ROOF SLOPE 1:20
ROOF SLOPE 1:20
SECTION B-B
PVC VENTCOWL
PVC VENT PIPE(TWO FOR EACH
COMPARTMENT OFSTORAGE TANK)
+6.40m LVL
+7.65m LVL
SLOP
E
SLOP
E
APPROX.
APPROX.
SLOP
E
SLOP
E
LASER CUTTINGROOM
ROOF SLOPE 1:20
SECTION C-C
PVC VENTCOWL
PVC VENT PIPE(TWO FOR EACH
COMPARTMENT OFSTORAGE TANK)
+7.65m LVL
+6.75m LVL
MODEL MAKING AREA
APPROX.
APPROX.
ROOF SLOPE 1:20
SECTION D-D
PVC VENTCOWL
PVC VENT PIPE(TWO FOR EACH
COMPARTMENT OFSTORAGE TANK)
+7.65m LVL
+4.30m LVL
MODEL MAKING AREA PVC CURTAIN
APPROX.
APPROX.
ROOF SLOPE 1:20
+7.65m LVL
PUMP ROOM
SECTION E-E
PVC VENTCOWL
PVC VENT PIPE(TWO FOR EACH
COMPARTMENT OFSTORAGE TANK)
MODEL MAKINGAREA
APPROX.
ROOF SLOPE 1:20
HEADER PIPE
HEADER PIPE HEADER PIPE
FIRE PUMPS
RCC
COLU
MN
RCC
COLU
MN
SUMP
RCC
COLU
MN
RCC
COLU
MN
SUMP
RCC
COLU
MN
RCC
COLU
MN
SUMP
RCC
COLU
MN
RCC
COLU
MN
SUMP
RCC
COLU
MN
RCC
COLU
MN
SUMP
RCC
COLU
MN
RCC
COLU
MN
SUMP
ROOF PLAN
500
500 500
500
TRUS
S
600060006000600060006000600060006000600060006000600060006000600060006000 48004600 4600 6760 4830 4830
6250
6250
6750
5850
6000
ROOF
SLO
PEDO
WN
1:7
ROOF
SLO
PEDO
WN
1:7
ROOF
SLO
PEDO
WN
1:7
ROOF
SLO
PEDO
WN
1:7
RIDG
E (+
6.40
m F
ROM
FFL
APP
ROX.
)
ROOFSLOPE
ROOFSLOPE
RIDGE (+5.80m FROM FFL APPROX.)
ROOF
SLOP
ERO
OFSL
OPE
ROOF
SLOP
ERO
OFSL
OPE
ROOF
SLOP
ERO
OFSL
OPE
ROOF
SLOP
ERO
OFSL
OPE
ROOF
SLOP
ERO
OFSL
OPE
ROOF
SLOP
ERO
OFSL
OPE
EAVE (+3.20m FROM FFL APPROX.)
OPEN TERRACE(@ +4.30m FROM FFL APPROX.)
OPEN TERRACE(@ +7.65m FROM FFL APPROX.)
FLAT ROOF(@ +6.75m FROM
FFL APPROX.)
A
A
ROOF
SLO
PEDO
WN
1:20
ROOF
SLO
PEDO
WN
1:20
ROOF
SLO
PEDO
WN
1:20
ROOF
SLO
PEDO
WN
1:20
ROOF
SLO
PEDO
WN
1:20
ROOF
SLO
PEDO
WN
1:20
ROOF
SLO
PEDO
WN
1:20
ROOF
SLO
PEDO
WN
1:20
F
F
ROOFSLOPE
ROOFSLOPE
500
OPEN TERRACE(@ +4.30m FROM
FFL APPROX.)
ROOF MONITOR FOR VENTILATION B
B
C
C
D
D
E
E
GG
TYPE SIZE
SCHEDULE OF OPENINGS
DISCRIPTION
5000 X 5000RS MECHANICALLY GEARED GI ROLLING SHUTTER
1200 X 2200ED SINGLE LEAF HMPS DOOR WITH PANIC BAR
D1
2000 X 2200D2 DOUBLE LEAF ALUMINIUM DOOR
1200 X 2200D3 / D3T SINGLE LEAF ALUMINIUM / PVC DOOR
800 X 2000D6 SINGLE LEAF PVC DOOR
2500 X 2200SD1 DOUBLE LEAF TOUGHENED GLASS DOOR WITHFLOOR SPRINGS
1500 X 1200W1 3 TRACK ALUMINIUM SLIDING WINDOWWITH FLY NET
1000 X 2200D4 / D4T SINGLE LEAF ALUMINIUM / PVC DOOR
900 X 2200D5 SINGLE LEAF HMPS DOOR
1500 X 2200 SINGLE LEAF HMPS DOOR
DRAFT COPYFOR TENDERINGFOR APPROVAL
Client:-
Project:-
Particulars:-
FOR EXECUTION
KUVELKAR SALKAR ASSOCIATESCONSULTING ENGINEERS
INDIAN INSTITUTE OF TECHNOLOGY
OVERALL ARCHITECTURAL DRAWING
KHARAGPUR
PROPOSED DEEP AND SHALLOW WATER MANEUVERINGAND SEAKEEPING BASIN FACILITY FOR OCEAN
ENGINEERING AND NAVAL ARCHITECTURE DEPARTMENT
DRG.NO: IIT_OENA_CYC_KSA_DWG_GA_00_OVERALL ARCHITECTURAL DRAWING
FOR APPROVAL GM RS01.02.2100· INTERNAL FIRE STATIONS REVISED· AIR CURTAINS FOR MODEL MAKING AREA DELETED GM RS03.02.2101
SCHEDULE OF OPENINGS GM RS25.03.2102
Page 62
DRAFT COPYFOR TENDERINGFOR APPROVAL
Client:-
Project:-
Particulars:-
FOR EXECUTION
BASIN & STORAGE TANK LAYOUTS
KUVELKAR SALKAR ASSOCIATESCONSULTING ENGINEERS
INDIAN INSTITUTE OF TECHNOLOGYKHARAGPUR
PROPOSED DEEP AND SHALLOW WATER MANEUVERINGAND SEAKEEPING BASIN FACILITY FOR OCEAN
ENGINEERING AND NAVAL ARCHITECTURE DEPARTMENT
DRG.NO: IIT_OENA_CYC_KSA_DWG_GA_06_BASIN & STORAGE TANK LAYOUTS
·
··
·
·
··
500
1600
050
050
0
30000 30000 3100031000
STORAGE TANK LAYOUT @ -6.800m LVL.
5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5000 5400 5400 5400 5400 4600 44005600
5400
5300
OPENING1000 x 2100
OPENING1000 x 2100
OPENING1000 x 2100
SUMP
RCC COLUMN(TYP.)
INTERNAL RCCWALL (TYP.)
500112000
1600
050
050
0
DEEP & SHALLOW WAVE BASIN LAYOUT @ -2.800m LVL.
ACCESS WELLFOR STORAGE TANK
6750
2500
6750
UP
R=175T=280
STORE / UTILITYROOM
STORE / UTILITYROOM
ACCESS TOSTORAGE TANK
400
B
B
B
B
C
C
C
C
D
D
D
D
E E
E E
W/P SLOPE DOWN
TOWARDS SUMP
(TYP. FOR ALL
COMPARTMENTS)
SUMP SUMP SUMP
VOID
ACCESS TOSTORAGE TANK
9200
2000 400
2.0m
WID
EC
OR
RID
OR
VOID
121200500
SERVICE DUCTFOR PIPING
VOID VOIDSERVICE DUCT
FOR PIPING
VOID
SERVICE DUCTFOR PIPING
SERVICE DUCTFOR PIPING
VOID
SERVICE DUCTFOR PIPING
VOID VOIDSERVICE DUCT
FOR PIPING
VOID
SERVICE DUCTFOR PIPING
SERVICE DUCTFOR PIPING
VOID
SUMP SUMP SUMP SUMP
SUMP AT THE BOTTOM OF SERVICEDUCT FOR DRAINAGE PURPOSE
(TYP. FOR ALL DUCTS)
SUMP SUMP SUMP SUMP
VOID
Ø 100 PVC VENT PIPE WITH VENT COWL(ONE FOR EACH COMPARTMENT OF STORAGE TANK)
Page 63
DRAFT COPYFOR TENDERINGFOR APPROVAL
Client:-
Project:-
Particulars:-
FOR EXECUTION
BASIN & STORAGE TANK SECTIONS
KUVELKAR SALKAR ASSOCIATESCONSULTING ENGINEERS
INDIAN INSTITUTE OF TECHNOLOGYKHARAGPUR
PROPOSED DEEP AND SHALLOW WATER MANEUVERINGAND SEAKEEPING BASIN FACILITY FOR OCEAN
ENGINEERING AND NAVAL ARCHITECTURE DEPARTMENT
DRG.NO: IIT_OENA_CYC_KSA_DWG_GA_07_BASIN & STORAGE TANK SECTIONS
SECTION B-B
(I/I OF RCC WALLS)
W/P PLASTER +SUITABLE PAINT
MAX. WATER LVL.
MIN. WATER LVL.
100 THK. PCC
200 THK. SOLING
COBA W/P(IN SLOPE) SLOPE 1:100
OPENING ININTERNALRCC WALL RC
C CO
LUMN
RCC
COLU
MN
MAX. WATER LVL.
PVC VENTCOWL
Ø 100 PVC VENT PIPEWITH VENT COWL(ONE FOR EACH
COMPARTMENT OFSTORAGE TANK)
SECTION C-C
(I/I OF RCC WALLS)
MAX. WATER LVL.
MIN. WATER LVL.
COBA W/P(IN SLOPE)
OPENING ININTERNALRCC WALL
RCC
COLU
MN
RCC
COLU
MN
MAX. WATER LVL.HEAVY DUTY
COVER
SERVICEDUCT FOR
PIPING
100 THK. PCC
200 THK. SOLING
LADDERSLOPE 1:100
W/P PLASTER +SUITABLE PAINT
SUMP
SUMP AT ONE CORNER AT THE BOTTOM OFSERVICE DUCT FOR DRAINAGE PURPOSE
(TYP. FOR ALL DUCTS)
COBA W/P(IN SLOPE)
MIN. WATER LVL.
MAX. WATER LVL.
(I/I OF RCC WALLS)
LAUNCHINGBAY
SLOPE 1:100
STORE / UTILITYROOM
SECTION D-D
(I/I OF RCC WALLS)
MAX. WATER LVL.
100 THK. PCC
200 THK. SOLING
RCC
COLU
MN
RCC
COLU
MN
STORE / UTILITYROOM
1.10m HT.RAILING (TYP.)
INTERNAL RCCWALL (TYP.)
SECTION E-E
112000 (I/I OF RCC WALLS FOR UPPER BASIN)
100 THK. PCC200 THK. SOLING
COBA W/P(IN SLOPE)
RCC
COLU
MN
LAUNCHING BAY
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
MAX. WATER LVL.
MIN. WATER LVL.
MAX. WATER LVL.
MIN. WATER LVL.
MAX. WATER LVL.
MIN. WATER LVL.
MAX. WATER LVL.
WATER TIGHTGATE
STOPPER (TYP.)
CARRIAGE
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
RCC
COLU
MN
2.0m WIDECORRIDOR
MAX. WATER LVL. MAX. WATER LVL. MAX. WATER LVL.
Page 64
25A DPRCCB30mA
ELDB18WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 1.55KW
10ASP
MCB
R1 R2 R3 R4
R
25A, FPMCB
Y1 Y2 Y3 Y5
Y
B1 B2 B3 B6
B
25A DPRCCB30mA
25A DPRCCB30mA
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
R5
10ASP
MCB
R6
10ASP
MCB
Y6
10ASP
MCB
Y4
10ASP
MCB
B4
10ASP
MCB
B5
10ASP
MCB
RO
OM
NAM
E - A
IR L
OC
K ,P
OR
CH
TOTA
L W
ATT-
120
WTO
TAL
LOAD
- 40
W- 3
NO
S
RO
OM
NAM
E - S
EMIN
AR H
ALL
TOTA
L W
ATT-
80W
TOTA
L LO
AD -
40W
-02N
OS
TOTA
L W
ATT-
160W
RO
OM
NAM
E - C
LASS
RO
OM
-1&2
TOTA
L LO
AD-4
0W-0
4NO
S
RO
OM
NAM
E - G
ENTS
TO
ILET
,TO
ILET
FO
R P
HYS
ICAL
LY
TOTA
L W
ATT-
45W
TOTA
L LO
AD -1
5W-0
3NO
SLA
DIE
S TO
ILET
,LAD
IES
TOIL
ET
TOTA
L W
ATT-
106W
RO
OM
NAM
E - O
FFIC
E,PA
NTR
Y,R
ECEP
TIO
N,P
OR
CH
TO
TAL
LOAD
-31W
-01N
OS,
15W
-01N
OS,
20W
-3N
OS
RO
OM
NAM
E- L
ASER
CU
TTIN
G R
OO
M,3
D P
RIN
TIN
G R
OO
M
TOTA
L W
ATT-
160
WTO
TAL
LOAD
-40W
-4N
OS
TOTA
L W
ATT-
200W
TOTA
L LO
AD-4
0W-5
NO
SR
OO
M N
AME-
MO
NO
RAI
L TR
ACK
TOTA
L W
ATT-
80W
TOTA
L LO
AD-4
0W-2
NO
SR
OO
M N
AME-
MO
NO
RAI
L TR
ACK
TOTA
L W
ATT-
200W
TOTA
L LO
AD-4
0W-5
NO
SR
OO
M N
AME-
MO
NO
RAI
L TR
ACK
TOTA
L W
ATT-
160
W
RO
OM
NAM
E- P
AIN
T &
RES
IN S
TOR
E,M
OD
EL R
AW M
AT. S
TOR
E
TOTA
L LO
AD-4
0W-0
4NO
SIN
STR
UM
ENTA
TIO
N R
OO
M
TOTA
L W
ATT-
120W
RO
OM
NAM
E- E
LEC
TRIC
AL R
OO
M ,U
PS R
OO
M
TOTA
L LO
AD-4
0W-3
NO
S
TOTA
L W
ATT-
120W
TOTA
L LO
AD-4
0W-3
NO
SR
OO
M N
AME-
PAN
EL R
OO
M,P
UM
P R
OO
M
SPAR
E
SPAR
E
SPAR
E
SPAR
E
SPAR
E
SPAR
E
UPSDB18WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 7.8KW
16ASP
MCB
R1 R2 R3 R4
R
40A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
32A DPRCBO100mA
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
TOTA
L W
ATT-
600W
TOTA
L W
ATT-
300W
SPAR
E
32A DPRCBO100mA
32A DPRCBO100mA
ROOM
NAM
E-SE
MIN
AR H
ALL,
CLAS
S RO
OM-1
TOTA
L W
ATT-
300W
TOTA
L W
ATT-
300W
SPAR
E
ROOM
NAM
E-CL
ASS
ROOM
-2
ROOM
NAM
E-PA
NEL R
OOM
SPAR
E
ROOM
NAM
E-RE
CEPT
ION
TOTA
L W
ATT-
1500
W
ROOM
NAM
E-OF
FICE
TOTA
L LOA
D-16
A 1W
AY S
WIT
CH +
2Nos
. 6A
3 PIN
SOC
KET(
UPS)
-2NO
S
TOTA
L LOA
D-16
A 1W
AY S
WIT
CH +
2Nos
. 6A
3 PIN
SOC
KET(
UPS)
-1NO
S
TOTA
L LOA
D-16
A 1W
AY S
WIT
CH +
2Nos
. 6A
3 PIN
SOC
KET(
UPS)
-5NO
S
TOTA
L LOA
D-16
A 1W
AY S
WIT
CH +
2Nos
. 6A
3 PIN
SOC
KET(
UPS)
-1NO
S
TOTA
L LOA
D-16
A 1W
AY S
WIT
CH +
2Nos
. 6A
3 PIN
SOC
KET(
UPS)
-1NO
S
TOTA
L W
ATT-
1200
W
ROOM
NAM
E-FA
CULT
Y R0
0M-1
,2,3,4
TOTA
L LOA
D-16
A 1W
AY S
WIT
CH +
2Nos
. 6A
3 PIN
SOC
KET(
UPS)
-4NO
S
TOTA
L W
ATT-
1200
W
ROOM
NAM
E-CO
NFER
ENCE
ROO
MTO
TAL L
OAD-
16A
1WAY
SW
ITCH
+ 2N
os. 6
A 3 P
IN S
OCKE
T(UP
S)-4
NOS
TOTA
L W
ATT-
1800
W
ROOM
NAM
E-IC
HAIR
MAN
OFFI
CE,R
ESEA
RCH
ROOM
-2,IT
ROO
M
TOTA
L LOA
D-16
A 1W
AY S
WIT
CH +
2Nos
. 6A
3 PIN
SOC
KET(
UPS)
-6NO
S
ROOM
NAM
E-CO
NTRO
L ROO
M TO
TAL L
OAD-
16A
1WAY
SW
ITCH
+ 2N
os. 6
A 3 P
IN S
OCKE
T(UP
S)-2
NOS
TOTA
L W
ATT-
600W
ACDB16WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 34.8KW
40ASP
MCB
R1 R2 R3 R4
R
100A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
D1-3600W
D2-3600W
D7-2400W
D8-1800W
D3-3600WSPARE
D4-2400W
D9-1800WD10-2400W
SPARE D5-2400W
D6-2400W
D11-2400W
D12-2400WSPARE
ACDB26WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 42.6KW
R1 R2 R3 R4
R
100A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
D1-1800W D7-3600W
D8-2400W
D13-3600W D3-1800WSPARE
D4-1800W
D9-1800W SPARE D5-3600W D11-2400W
D12-2400WSPARE
D2-1800W D6-3600WD10-1800WD15-3600WD16-1200W
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
D13-1800WSPARE D12A-1800W
100A, SPMCB
D14-3600W
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
40ASP
MCB
100A, SPMCB
100A, SPMCB
100A, SPMCB
100A, SPMCB
100A, SPMCB
D17-1800W
20kVAUPS
BATTERY
40A,
FP,
ISO
LATO
R40
A, F
P,IS
OLA
TOR
40ATPNMCCB
25ATPNMCB
PANEL NAME :- MAIN UPS DBCONNECTED LOAD :13KWDEMAND LOAD :- 13KW
40ATPNMCB
40ATPNMCB
SPARE
25ATPNMCB
125ATPNMCCB
63ATPNMCB
PANEL NAME :- MAIN POWER DBCONNECTED LOAD :30KWDEMAND LOAD :- 30KW
63ATPNMCB
40ATPNMCB
63ATPNMCB
40ATPNMCB
SPARE SPARE
63ATPNMCB
63ATPNMCCB
32ATPNMCB
PANEL NAME :- MAIN LIGHTING DBCONNECTED LOAD :20.97KWDEMAND LOAD :- 20.97KW
32ATPNMCB
32ATPNMCB
32ATPNMCB
CONNECTED LOAD INkW
DESCRIPTION
AL BUSBAR.80A, 415V, 50Hz TPN
DEMAND LOAD IN kW
80A TP MCCB+NWITH T/M BASEDRELEASESO/C, S/C
F1
PANEL NAME :- FIRE-FIGHTINGPANEL CONNECTED LOAD :- 41KWDEMAND LOAD :- 3.28KW
MAIN PUMP
37KW
JOCKEY PUMP
29.6KW
SPARE SPARE
-
-
-
-
4KW
3.2KW
F2
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
63A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
F3
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
16A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
F4
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
63A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
F5
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
40A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
CONNECTED LOAD INkW
DESCRIPTION
AL BUSBAR80A, 415V, 50Hz TPN
DEMAND LOAD IN kW
80A TP MCCB+NWITH T/M BASEDRELEASESO/C, S/C
PANEL NAME :-WATER PANELCONNECTED LOAD :- 44KWDEMAND LOAD :- 28.16KW
BOOSTER PUMP
22KW
STANDBY PUMP
17.6KW
SPARE SPARE
-
-
-
-
22KW
F2
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
40A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
F3
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
40A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
F4
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
40A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
F5
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
40A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
17.6KW
BOREWELL PUMP
22KW
17.6KW
F6
DOL
C1
C2
C3
ON OFF TRIP
START STOP
SELECTORSWITCH
E.STOP
M
40A TP MCCB+NWITH T/MBASED RELEASES25kA O/C, S/C
F1
CONNECTED LOAD INkW
LOCATION
DESCRIPTION
-
AL BUSBAR,FOR 25kA 1SEC.800A, 415V, 50Hz TPN
DEMAND LOAD IN kW
F2
3
6A, TP MCB 0-500V
CT1:800/5A15VA,CL.1
LM0-800A
A
6A, TP MCB R Y B
V
800A TP MCCB+NWITH M/P BASEDRELEASES25kA O/C, S/C
** # 3.5C x 300 SQ.MM,AL, Armoured XLPE ,CABLE
100ATPMCCB+N
F1F3 F4 F5 F6 F7 F9 F10
630ATP MCCB+N
PANEL NAME :- MAIN PCC PANELCONNECTED LOAD :- 558KWDEMAND LOAD :- 314KW
FIRE FIGHTING PANEL
40ATPMCCB+N
125ATPMCCB+N
63ATPMCCB+N
80ATPMCCB+N
80ATPMCCB+N
3CT1:800/5A15VA,CL.1
TO APFC
40ATPMCCB+N
41KW
WATER PUMPING SYSTEM
44KW
MLDB MPDB
30KW20.97KW
3.28KW 28.16KW
UPS ACDB-1
F11
32ATPMCCB+N
COMPRESSOR
F12
63ATPMCCB+N
PASSENGER ELEVATOR
F13
400ATPMCCB+N
OVERHEAD CRANE (5 TONNE)
F14
100ATPMCCB+N
CARRIAGE
F15
40ATPMCCB+N
WAVE MAKER
------
-
-34.8KW
20KW
13KW
240kVAR APFC
24KW
9.60KW
7.5KW
5.28KW
32KW
22.4KW
180KW
100.8KW
50KW
28KW
WATER FILTRATION SYSTEM
-
15KW
8.4KW
F16
100ATPMCCB+N
F17
63ATPMCCB+N
F18
40ATPMCCB+N
F19
40ATPMCCB+N
SPARE
-
-
-
-
-
-
-
-
-
-
-
-
-----
42.6KW
24KW
-
F8
100ATPMCCB+N
SPARE SPARE SPARE ACDB-2
13KW30KW
11KV,400A VCB 11KV,400A
VCB
11KV,from Substation no .3
11KV,to Nalanda Substation
11KV,400A VCB
Bus PT
11KV,400A VCB
TR-11000kVA,11KV/415VTransformer
TR-2500kVA,11KV/415VTransformer
1600A,ACB 800A,ACB
1000A,ACB
800A,ACB
800A,ACB
800A,ACB
Nalanda Feeder Box(For alternatepower supply)
Spare Spare
Bus Coupler
Proposed
Existing
Existing
25A DPRCCB30mA
SLDB28WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOOR CONNECTED LOAD:-3.71KW
10ASP
MCB
R1 R2 R3 R4
R
32A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
Y5 Y6 B5 B6
TOTA
L W
ATT-
155W
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
R5
10ASP
MCB
R6
10ASP
MCB
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
31W
- 5N
OS
RO
OM
NAM
E - L
AB T
ECH
NIC
IAN
S,PA
SSAG
E
TOTA
L W
ATT-
380
WTO
TAL
LOAD
- 40
W- 8
NO
S,60
W-1
NO
S
RO
OM
NAM
E - I
NC
UBA
TIO
N C
ENTE
R
SPAR
E
TOTA
L W
ATT-
680W
RO
OM
NAM
E - F
ACU
LTY
R00
M-1
,2,3
,4,1
.30m
WID
E PA
SSAG
E TO
TAL
LOAD
- 40
W- 1
1NO
S,60
W-4
NO
S
RO
OM
NAM
E - R
ESEA
RC
H S
CH
OLA
R R
OO
M-2
TOTA
L W
ATT-
320
W
TOTA
L W
ATT-
220W
RO
OM
NAM
E -T
EA R
OO
M ,I
T / S
ERVE
R R
OO
M
RO
OM
NAM
E -,P
ASSA
GE
TOTA
L W
ATT-
120
W
SPAR
E
SPAR
E
RO
OM
NAM
E - C
ON
FER
ENC
E R
OO
M
TOTA
L W
ATT-
368
WTO
TAL
LOAD
- 31
W- 8
NO
S,40
W-3
NO
S
RO
OM
NAM
E -L
IBR
ARY/
MEE
TIN
G
TOTA
L W
ATT-
124
WTO
TAL
LOAD
- 31
W- 4
NO
S
TOTA
L W
ATT-
120W
RO
OM
NAM
E - C
ON
TRO
L R
OO
M
TOTA
L LO
AD -
40W
- 3N
OS
SPAR
E
SPAR
E
TOTA
L W
ATT-
500
WTO
TAL
LOAD
- 40
W- 8
NO
S,60
W-3
NO
S
SPAR
E
TOTA
L LO
AD -
40W
- 05N
OS,
60W
-2N
OS
TOTA
L LO
AD -
40W
- 04N
OS,
60W
-1N
OS
TOTA
L LO
AD -
40W
- 03N
OS
RO
OM
NAM
E - G
ENTS
TO
ILET
,TO
ILET
FO
R P
HYS
ICAL
LY
TOTA
L W
ATT-
445
WTO
TAL
LOAD
-15W
-11N
OS,
40W
-01N
OS,
60W
-4N
OS
SER
VIC
E D
UC
T,LA
DIE
S TO
ILET
,LAD
IES
TOIL
ET
10ASP
MCB
25A DPRCCB30mA
25A DPRCCB30mA
25A DPRCCB30mA
SLDB112WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:-7.93KW
10ASP
MCB
R1 R2 R3 R4
R
4C x 2.5Sqmm, CU.Arm., XLPE , Cable
32A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
16ASP
MCB
10ASP
MCB
R7
10ASP
MCB
R8
10ASP
MCB
Y5 Y6 B5 B6
RO
OM
NAM
E- C
LASS
RO
OM
-2
TOTA
L W
ATT-
400W
TOTA
L LO
AD- 4
0W -0
4NO
S,60
W-4
NO
S
RO
OM
NAM
E- R
ECEP
TIO
N,P
OR
CH
,STA
IRS
TOTA
L W
ATT-
380W
TOTA
L LO
AD-2
0W-0
7NO
S,40
W-3
NO
S,60
W-2
NO
S
TOTA
L W
ATT-
200W
TOTA
L LO
AD-4
0W-5
NO
S
RO
OM
NAM
E - S
EMIN
AR H
ALL
TOTA
L W
ATT-
880
WTO
TAL
LOAD
- 40
W-1
3NO
S
RO
OM
NAM
E- L
ASER
CU
TTIN
G R
OO
M
TOTA
L W
ATT-
400W
TOTA
L LO
AD-4
0W-7
NO
S,60
W-2
NO
S
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
RO
OM
NAM
E - G
ENTS
TO
ILET
,TO
ILET
FO
R P
HYS
ICAL
LY
TOTA
L W
ATT-
565
WTO
TAL
LOAD
-15W
-11N
OS,
40W
-04N
OS,
60W
-4N
OS
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
R5
10ASP
MCB
R6
10ASP
MCB
Y7
10ASP
MCB
Y9
SPAR
E
10ASP
MCB
B7 B8
SPAR
E
10ASP
MCB
10ASP
MCB
TOTA
L W
ATT-
200
W
TOTA
L W
ATT-
200
W
RO
OM
NAM
E- P
AIN
T &
RES
IN S
TOR
E,M
OD
EL R
AW M
AT. S
TOR
E
RO
OM
NAM
E- U
PS R
OO
M
TOTA
L LO
AD-4
0W-0
2NO
S,60
W-2
NO
S
TOTA
L LO
AD-4
0W-5
NO
S
TOTA
L W
ATT-
280W
RO
OM
NAM
E - I
NST
RU
MEN
TATI
ON
RO
OM
TO
TAL
LOAD
-40W
-07N
OS
TOTA
L W
ATT-
260W
RO
OM
NAM
E- E
LEC
TRIC
AL R
OO
M
TOTA
L LO
AD-4
0W-5
NO
S,60
W-1
NO
S
TOTA
L W
ATT-
240W
TOTA
L LO
AD-4
0W-6
NO
SR
OO
M N
AME-
MO
NO
RAI
L TR
ACK
TOTA
L W
ATT-
200W
TOTA
L LO
AD-4
0W-5
NO
SR
OO
M N
AME-
MO
NO
RAI
L TR
ACK
R9
10ASP
MCB
R10
10ASP
MCB
SPAR
E
SPAR
E
SER
VIC
E D
UC
T,LA
DIE
S TO
ILET
,LAD
IES
TOIL
ET
TOTA
L W
ATT
-160
WTO
TAL
LOAD
-40W
-4N
OS
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
TOTA
L W
ATT
- 200
WTO
TAL
LOAD
-40W
-5N
OS
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
TOTA
L W
ATT
- 160
WTO
TAL
LOAD
-40W
-4N
OS
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
Y8
10ASP
MCB
TOTA
L W
ATT-
260W
RO
OM
NAM
E - P
ANEL
RO
OM
TO
TAL
LOAD
-40W
-05N
OS,
60W
-1N
OS
Y10
SPAR
E
10ASP
MCB
TOTA
L W
ATT-
520W
RO
OM
NAM
E - C
LASS
RO
OM
-1,P
ASSA
GE
TOTA
L LO
AD-4
0W-0
7NO
S,60
W-4
NO
S
TOTA
L W
ATT-
385W
RO
OM
NAM
E - O
FFIC
E,PA
NTR
Y,ST
AIR
S
TOTA
L LO
AD-3
1W-0
5NO
S,15
W-0
2NO
S,40
W-2
NO
S,60
W-2
NO
S
TOTA
L W
ATT-
680W
RO
OM
NAM
E - 3
D P
RIN
TIN
G R
OO
M ,P
ASSA
GE
TOTA
L LO
AD-4
0W-1
4NO
S,60
W-2
NO
S
TOTA
L W
ATT
-160
WTO
TAL
LOAD
-40W
-4N
OS
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
TOTA
L W
ATT
- 200
WTO
TAL
LOAD
-40W
-5N
OS
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
TOTA
L W
ATT
- 160
WTO
TAL
LOAD
-40W
-4N
OS
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
TOTA
L W
ATT-
520W
RO
OM
NAM
E- P
UM
P R
OO
M
TOTA
L LO
AD-4
0W-1
3NO
S
B9
10ASP
MCB
SPAR
E
B10
10ASP
MCB
RO
OM
NAM
E - S
EMIN
AR H
ALL
TOTA
L LO
AD -
40W
-13N
OS,
60W
-6N
OS
25A DPRCCB30mA
25A DPRCCB30mA
20.97KW
25A DPRCCB30mA
ELDB28WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 3.38KW
10ASP
MCB
R1 R2 R3 R4
R
4C x 2.5Sqmm, CU.Arm., XLPE , Cable
25A, FPMCB
Y1 Y2 Y3 Y5
Y
B1 B2 B3 B6
B
25A DPRCCB30mA
25A DPRCCB30mA
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
R5
10ASP
MCB
R6
10ASP
MCB
Y6
10ASP
MCB
Y4
10ASP
MCB
B4
10ASP
MCB
B5
10ASP
MCB
RO
OM
NAM
E - F
ACU
LTY
R00
M 3
& 4
,PAS
SAD
E
TOTA
L W
ATT-
120
WTO
TAL
LOAD
- 40
W-0
3NO
S
TOTA
L W
ATT-
62W
RO
OM
NAM
E - C
ON
FER
ENC
E R
OO
M,C
HAI
RM
AN O
FFIC
E
TOTA
L LO
AD-3
1W-0
2NO
S
RO
OM
NAM
E - G
ENTS
TO
ILET
,TO
ILET
FO
R P
HYS
ICAL
LY
TOTA
L W
ATT-
125W
TOTA
L LO
AD -1
5W-0
3NO
S,40
W-2
NO
SLA
DIE
S TO
ILET
,LAD
IES
TOIL
ET,R
ESEA
RC
H S
CH
OLA
R R
OO
M-2
TOTA
L W
ATT-
120W
RO
OM
NAM
E - L
AB T
ECH
NIC
IAN
S ,T
EA R
OO
M ,I
T R
OO
MTO
TAL
LOAD
-40W
-3N
OS
RO
OM
NAM
E- L
IBR
ARY/
MEE
TIN
G,IN
CU
BATI
ON
CEN
TRE
,PAS
SAG
E
TOTA
L W
ATT-
231
WTO
TAL
LOAD
- 31W
-1N
OS,
40W
-5N
OS
SPAR
E
SPAR
E
SPAR
E
SPAR
E
SPAR
E
RO
OM
NAM
E - E
NTR
ANC
E PA
SSAG
E,FA
CU
LTY
R00
M-1
& 2
TOTA
L W
ATT-
160
WTO
TAL
LOAD
- 40
W- 4
NO
S
CO
NTR
OL
RO
OM
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
480
WTO
TAL
LOAD
- 12
0W- 4
NO
S
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
480
WTO
TAL
LOAD
- 12
0W- 4
NO
S
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
480
WTO
TAL
LOAD
- 12
0W- 4
NO
S
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
480
WTO
TAL
LOAD
- 12
0W- 4
NO
S
RO
OM
NAM
E -A
REA
EAR
MAR
KED
FO
R C
ARR
IAG
E
TOTA
L W
ATT-
480
WTO
TAL
LOAD
- 12
0W- 4
NO
S
SPAR
E
RO
OM
NAM
E -S
HIP
MO
DEL
STO
RAG
E AR
EA
TOTA
L W
ATT-
160
WTO
TAL
LOAD
- 40
W- 4
NO
S
25A DPRCCB30mA
SLDB312WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:-7.32KW
10ASP
MCB
R1 R2 R3 R4
R
32A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
W
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
16ASP
MCB
10ASP
MCB
TOTA
L LO
AD -
120W
- 2N
OS
R7
10ASP
MCB
R8
10ASP
MCB
Y5 Y6 B5 B6
TOTA
L W
ATT-
480W
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
R5
10ASP
MCB
R6
10ASP
MCB
Y7
10ASP
MCB
B7 B8
10ASP
MCB
10ASP
MCB
Y8
10ASP
MCB
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
WTO
TAL
LOAD
- 12
0W- 2
NO
S
TOTA
L W
ATT-
480W
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
WTO
TAL
LOAD
- 12
0W- 2
NO
S
TOTA
L W
ATT-
480W
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
RO
OM
NAM
E -S
HIP
MO
DEL
STO
RAG
E AR
EA
TOTA
L W
ATT-
400
WTO
TAL
LOAD
- 40
W- 1
0NO
S
SPAR
E
TOTA
L W
ATT-
480W
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
WTO
TAL
LOAD
- 12
0W- 2
NO
S
TOTA
L W
ATT-
480W
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
WTO
TAL
LOAD
- 12
0W- 2
NO
S
TOTA
L W
ATT-
480W
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
TOTA
L W
ATT-
240W
RO
OM
NAM
E -S
HIP
MO
DEL
STO
RAG
E AR
EA
TOTA
L LO
AD -
120W
- 2N
OS
SPAR
E
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
WTO
TAL
LOAD
- 12
0W- 2
NO
S
TOTA
L W
ATT-
480W
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
WTO
TAL
LOAD
- 12
0W- 2
NO
S
TOTA
L W
ATT-
480W
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L LO
AD -
120W
- 4N
OS
RO
OM
NAM
E -D
EEP
AND
SH
ALLO
W W
AVE
BASI
N
TOTA
L W
ATT-
240
WTO
TAL
LOAD
- 12
0W- 2
NO
S
RO
OM
NAM
E -A
REA
EAR
MAR
KED
FO
R C
ARR
IAG
E
TOTA
L W
ATT-
600
WTO
TAL
LOAD
- 12
0W- 5
NO
S
SPAR
E
SPAR
E
25A DPRCCB30mA
25A DPRCCB30mA
TOTA
L W
ATT-
320W
RO
OM
NAM
E -S
HIP
MO
DEL
STO
RAG
E AR
EA
TOTA
L LO
AD -
40W
- 8N
OS
SPARE
32ATPNMCB
SPARE
32ATPNMCB
25A DPRCCB30mA
SLDB46WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:-2.01KW
10ASP
MCB
R1 R2 R3 R4
R
32A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
180
W
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
16ASP
MCB
10ASP
MCB
TOTA
L LO
AD -
18W
- 10
NO
S
Y5 Y6 B5 B6
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
10ASP
MCB
R5
10ASP
MCB
R6
10ASP
MCB
SPAR
E
SPAR
E
SPAR
E
25A DPRCCB30mA
25A DPRCCB30mA
SPAR
E
SPAR
E
SPAR
E
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
180
WTO
TAL
LOAD
- 18
W -
10N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
180
WTO
TAL
LOAD
- 18
W -
10N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
180
WTO
TAL
LOAD
- 18
W -
10N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E -U
PPER
BAS
IN U
ND
ER W
ATER
LIG
HT
TOTA
L W
ATT-
162
WTO
TAL
LOAD
- 18
W -
09N
OS
RO
OM
NAM
E - A
IR L
OC
K ,P
OR
CH
,STA
IRS,
LIFT
TOTA
L W
ATT-
320
WTO
TAL
LOAD
- 40
W- 8
NO
S
RO
OM
NAM
E - E
NTR
ANC
E PA
SSAG
E,LI
FT
TOTA
L W
ATT-
280
WTO
TAL
LOAD
- 40
W- 7
NO
S
SPDB112WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:-15.36KW
16ASP
MCB
R1 R2 R3 R4
R
4C x 6Sqmm, CU.Arm., XLPE , Cable
63A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
TOTA
L W
ATT-
1100
W
TOTA
L LO
AD-1
6A 1
WAY
SW
ITCH
WIT
H 16
A, 6
PIN
SOCK
ET(R
AW).-
5NO
S
ROOM
NAM
E-GE
NTS
TOILE
T,SE
RVIC
E DU
CT
TOTA
L W
ATT-
420W
ROOM
NAM
E-PA
NTRY
,OFF
ICE
40A DPRCBO100mA
ROOM
NAM
E-AI
R LO
CK,D
RINK
ING
WAT
ER,P
ORCH
,LIF
T
TOTA
L LOA
D-AW
) -6A
3 PI
N MO
DULA
R SW
ITCH
SOC
KET-
3NOS
TOTA
L W
ATT-
400W
TOTA
L W
ATT-
400W
TOTA
L W
ATT-
420W
ROOM
NAM
E-PA
NTRY
,REC
EPTI
ON
TOTA
L W
ATT-
1000
W
ROOM
NAM
E-LA
DIES
TOI
LET
TOTA
L W
ATT-
500W
ROOM
NAM
E-CL
ASS
ROOM
-1 &
2
ROOM
NAM
E-OF
FICE
TOTA
L W
ATT-
300W
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A, 3
PIN
SO
CKET
(RAW
)-3NO
S
ROOM
NAM
E-SE
MINA
R HA
LL
TOTA
L LOA
D-6A
3 PI
N MO
DULA
R SW
ITCH
SOC
KET-
4NOS
TOTA
L LOA
D-6A
1WAY
SW
ITCH
WIT
H 6A
, 3PI
N S
OCKE
T (R
AW)-
5NOS
6A 3
PIN
SOCK
ET-2
No
ROOM
NAM
E- R
ECEP
TION
TOTA
L W
ATT-
300W
R5 R6
16ASP
MCB
16ASP
MCB
ROOM
NAM
E-PA
INT
& RE
SIN
STOR
E,MO
DEL R
AW M
AT.S
TORE
TOTA
L W
ATT-
1000
WTO
TAL
LOAD
-20A
, 1PH
ASE
INDU
STRI
AL S
OCK
ET w
ith 2
0A S
PN M
CB-2
NOS
ROOM
NAM
E-3D
PRI
NTIN
G RO
OM,T
OILE
T
TOTA
L W
ATT-
2380
W
ROOM
NAM
E-EL
ECTR
ICAL
ROO
M,UP
S RO
OM
TOTA
L W
ATT-
900W
TOTA
L LO
AD-1
6A 1
WAY
SW
ITCH
WIT
H 16
A, 6
PIN
SOCK
ET(R
AW)-2
Nos
Y5
16ASP
MCB
ROOM
NAM
E - I
NSTR
UMEN
TATI
ON R
OOM
TOTA
L W
ATT-
2100
W
Y6
16ASP
MCB
B5
16ASP
MCB
B6
16ASP
MCB
TOTA
L LO
AD-2
0A, 1
PHAS
E IN
DUST
RIAL
SO
CKET
with
20A
SPN
MCB
-4No
s
20A,
1PH
ASE
INDU
STRI
AL S
OCK
ET w
ith 2
0A S
PN M
CB-1
Nos
6A 1
WAY
SW
ITC
H W
ITH
6A,
3PI
N S
OC
KET
(RAW
)-1N
OS
TOTA
L LOA
D-AW
) -6A
3 PI
N MO
DULA
R SW
ITCH
SOC
KET-
4NOS
ROOM
NAM
E-LA
SER
CUTT
ING
ROOM
TOTA
L W
ATT-
2060
W
TOTA
L LOA
D-AW
) - 20
A, 1P
HASE
INDU
STRI
AL S
OCKE
T wi
th 20
A SP
N MC
B-4 N
OS
6A 3
PIN
SOCK
ET -1
NOS.
R7
16ASP
MCB
ROOM
NAM
E-PA
NEL R
OOM,
PUMP
ROO
M
TOTA
L W
ATT-
800W
TOTA
L LOA
D-AW
) -6A
3 PI
N MO
DULA
R SW
ITCH
SOC
KET-
3NOS
20
A, 1
PHAS
E IN
DUST
RIAL
SO
CKET
with
20A
SPN
MCB
-1NO
S
TOTA
L LOA
D-6A
3 PI
N MO
DULA
R SW
ITCH
SOC
KET-
3NOS
6A
3 PI
N SO
CKET
-2No
16A
1WAY
SW
ITC
H W
ITH
16A
, 6PI
N S
OC
KET(
RAW
)-5
NO
S
6A 3
PIN
SOCK
ET-3
NOS,
6A 1W
AY S
WIT
CH W
ITH
6A, 3
PIN
SOC
KET
(RAW
)-2No
s
TOTA
L LO
AD-2
0A, 1
PHAS
E IN
DUST
RIAL
SO
CKET
with
20A
SPN
MCB
-4No
s
6A 1W
AY S
WIT
CH W
ITH
6A, 3
PIN
SOC
KET
(RAW
)-1No
s SPAR
E
R8
16ASP
MCB
Y7
SPAR
E
16ASP
MCB
Y8
SPAR
E
16ASP
MCB
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A, 3
PIN
SO
CKET
(RAW
)-3NO
S
ROOM
NAM
E-MO
DEL M
AKIN
G AR
EA
TOTA
L W
ATT-
800W
TOTA
L LO
AD-2
0A 1
WAY
SW
ITCH
WIT
H 20
A, 6
PIN
SOCK
ET(R
AW) -
4NO
S.
B7
SPAR
E
16ASP
MCB
B8
SPAR
E
16ASP
MCB
ROOM
NAM
E-MO
NORA
IL TR
ACK
TOTA
L W
ATT-
180W
6A 3
PIN
SOCK
ET -3
NOS.
ROOM
NAM
E-MO
NORA
IL TR
ACK
TOTA
L W
ATT-
180W
6A 3
PIN
SOCK
ET -3
NOS.
ROOM
NAM
E-FO
RKLIF
T BA
TTER
Y CH
ARGI
NG A
REA
TOTA
L W
ATT-
120W
6A 3
PIN
SOCK
ET -2
NOS.
40A DPRCBO100mA
40A DPRCBO100mA
SPDB28WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 4.44KW
16ASP
MCB
R1 R2 R3 R4
R
4C x 6Sqmm, CU.Arm., XLPE , Cable
40A, FPMCB
Y1 Y2 Y3 Y4
Y
B1 B2 B3 B4
B
32A DPRCBO100mA
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
16ASP
MCB
TOTA
L W
ATT-
500W
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-5
NOS
32A DPRCBO100mA
32A DPRCBO100mA
ROO
M N
AME-
FACU
LTY
R00M
-1,2
,3,5
TOTA
L W
ATT-
300W
ROO
M N
AME-
CHAI
RMAN
OFF
ICE,
RESE
ARCH
SCH
OLA
R RO
OM
-2
ROO
M N
AME-
LAB
TECH
NICI
ANS
TOTA
L W
ATT-
600W
SPAR
E
SPAR
E
ROO
M N
AME-
CONF
EREN
CE R
OO
M
TOTA
L W
ATT-
300W
ROO
M N
AME-
GEN
TS T
OIL
ET,S
ERVI
CE D
UCT
TOTA
L W
ATT-
420W
TOTA
L LOA
D-6A
1WAY
SW
ITCH
WIT
H 6A
,3PIN
SOC
KET(
RAW
)-03N
OS
6A 3
PIN
SO
CKET
-2No
.
ROO
M N
AME-
LADI
ES T
OIL
ET,T
OIL
ET F
OR
PHYS
ICAL
LY C
HALL
ENG
ED
TOTA
L W
ATT-
420W
SPAR
E
ROO
M N
AME-
TEA
ROO
M,IT
/SER
VER
ROO
M,1
.25m
WID
E PA
SSAG
E
TOTA
L W
ATT-
400W
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-0
4NO
S
6A 3
PIN
SO
CKET
-2No
.
ROO
M N
AME-
LIBR
ARY/
MEE
TING
TOTA
L W
ATT-
800W
20A
, 1PH
ASE
INDU
STRI
AL S
OCK
ET w
ith 2
0A S
PN M
CB-1
NO
S
20A
, 1PH
ASE
INDU
STRI
AL S
OCK
ET w
ith 2
0A S
PN M
CB-1
NO
S
ROO
M N
AME-
CONT
ROL
ROO
M
TOTA
L W
ATT-
700W
20A
, 1PH
ASE
INDU
STRI
AL S
OCK
ET w
ith 2
0A S
PN M
CB-1
NO
S
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-3
NOS
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-3
NOS
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-3
NOS
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-3
NOS
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-1
NOS
TOTA
L LO
AD-6
A 1W
AY S
WIT
CH W
ITH
6A,3
PIN
SOCK
ET(R
AW)-1
NOS
TPDB18WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 6 KW
32ATP
MCB
4C x 6Sqmm, CU.Arm., XLPE , Cable
32ATP
MCB
TOTA
L W
ATT-
1000
W
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
C1 C2
TOTA
L W
ATT-
1000
W
32ATP
MCB
C3
32ATP
MCB
C5
SPAR
E
63A, FPMCB
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
32ATP
MCB
C4
32ATP
MCB
C6
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
TOTA
L W
ATT-
1000
W
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K
TOTA
L W
ATT-
1000
W
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K/PV
C C
UR
TAIN
TOTA
L W
ATT-
1000
W
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
RO
OM
NAM
E- M
ON
OR
AIL
TRAC
K/PV
C C
UR
TAIN
TOTA
L W
ATT-
1000
W
32ATP
MCB
C7
32ATP
MCB
C8
SPAR
E
TPDB216WAY, TPN , DBLOCATION-ELECTRICAL PANEL ROOM GROUND FLOORCONNECTED LOAD:- 4 KW
32ATP
MCB
4C x 6Sqmm, CU.Arm., XLPE , Cable
32ATP
MCB
C1 C2
32ATP
MCB
C3
32ATP
MCB
C5
SPAR
E
63A, FPMCB
32ATP
MCB
C4
32ATP
MCB
C6
32ATP
MCB
C7
ROOM
NAM
E- E
LECT
RICA
L RO
OM
TOTA
L W
ATT-
500
W
32ATP
MCB
C8
ROOM
NAM
E- F
ORKL
IFT
BATT
ERY
CHAR
GING
ARE
A
TOTA
L W
ATT-
100
0W
ROOM
NAM
E- F
ORKL
IFT
BATT
ERY
CHAR
GING
ARE
A
TOTA
L W
ATT-
100
0W
ROOM
NAM
E- P
ANEL
ROO
M
TOTA
L W
ATT-
500
W
ROOM
NAM
E- IN
CUBA
TION
CEN
TER
TOTA
L W
ATT-
500
W
ROOM
NAM
E- C
ONTR
OL R
OOM
TOTA
L W
ATT-
500
W
SPAR
E
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
1NO
S
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
2NO
S
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
1NO
S
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
1NO
S
30A,
3PH
ASE
IND
UST
RIA
L SO
CKE
T w
ith 3
0A T
P M
CB-
1NO
S
4C x 2.5Sqmm, CU.Arm., XLPE , Cable
4C x 2.5Sqmm, CU.Arm., XLPE , Cable
4C x 2.5Sqmm, CU.Arm., XLPE , Cable
3.5C x 35Sqmm, AL.Arm., XLPE , Cable
3.5C x 50Sqmm, AL.Arm., XLPE , Cable
4C x 2.5Sqmm, CU.Arm., XLPE , Cable
4C x 6Sqmm, CU.Arm., XLPE , Cable
3.5C x 35Sqmm, AL.Arm., XLPE , Cable
3.5C x 50Sqmm, AL.Arm., XLPE , Cable 240 kVAR APFC PANEL
F1
0-500A
2A, SP MCB-3NOS
ON OFF TRIP
R Y B
L
F2 F3 F4 F5 F6 F7
A
INCOMER500A TP 25kA, MCCBWITH O/C,SC
3PH,433V/50Hz, 500A AL.BUSBAR 25kA FOR 1 SEC.
2RUNS X 150SQ.MMX 3.5C A2XFY CABLE
CT 1- 3500/5A5VA,CL-1
2A, SP MCB-3NOS
0-500VV
TH
L
TH
L
TH
L
TH
L
TH
240KVAR APFC PANELQTY : 1NosCABLE ENTRY - TOP
FEEDER No.BREAKER RATINGBREAKING CAPACITY IN kAFEEDER DESCRIPTION
C C C C C
25kA5KVAR
25kA5KVAR
25kA10KVAR
25kA20KVAR
25kA25KVAR
25kA25KVAR 50KVAR
25kA
16A,TPN,MCCB
16A,TPN,MCCB
25A,TPN,MCCB
40A,TPN,MCCB
63A,TPN,MCCB
16A MCCB 25A MCCB 40A MCCB 63A MCCB 63A MCCB 100A MCCB16A MCCB
L
TH
C
63A,TPN,MCCB
F8
L
TH
C
100A,TPN,MCCB
F9
L
TH
C
100A,TPN,MCCB
25kA50KVAR
100A MCCB25kA
50KVAR
100A MCCB
F10
L
TH
C
100A,TPN,MCCB
APFCRELAYFROM MAIN LT PANEL
CT TERMINAL
9 STAGE APFCRELAY
KEY SLD
KUVELKAR SALKAR ASSOCIATESCONSULTING ENGINEERS
DRAFT COPYFOR TENDERINGFOR APPROVALFOR EXECUTION
INDIAN INSTITUTE OF TECHNOLOGYKHARAGPUR
PROPOSED DEEP AND SHALLOW WATER MANEUVERINGAND SEAKEEPING BASIN FACILITY FOR OCEAN
ENGINEERING AND NAVAL ARCHITECTURE DEPARTMENT
DRG.NO: IIT_OENA_CYC_KSA_DWG_ELE_02_KEY SLD
DK FIRE SERVICES
Page 65