1-800-ASK-4WEG www.weg.net TIMING RELAYS Data is subject to change without notice. B-264 Electronic Relays Protection Relays RPW Timing Relays RTW Level Relays RNW Controls Electronic Relays -RTW, RPW, RNW Series g High precision electronic circuit with noise immunity. g Compact, with a 22.5mm width frame, direct mounting on DIN rail 35mm or fixed with screws. g Equipped with reliability LED for status indications. g Designed in accordance with international standards Standards IEC / EN1812-1 IEC / EN 60947-1 IEC / EN 60947-5-1 UL508 CAN/CSA C22.2 Certifications Ideal for applications such as industrial processes, automation and motor starters, RTW timing relays switch an output signal based on a selected time and function. Setting time ranges from 0.2s to 150h. With a 22.5 mm width frame the RTW is supplied as a competitive solution including the following features: g Direct mounting on DIN rail 35 mm or fixed with screws; g 1 or 2 output contacts (C form); g RTW-RE – On-Delay g RTW-RD – Off-Delay g RTW-RDI – Off-Delay without Control Voltage g RTW-PE – Impulse On g RTW-CI – Assymmetric Flasher Start ON g RTW-CIL – Symmetric Flasher - Start ON g RTW-CID – Symmetric Flasher - Start OFF g RTW-ET – Wye - Delta Timing Relay RTW

Transcript of Electronic Relays - Amazon S3

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-264

Electronic Relays

Protection Relays RPWTiming Relays RTWLevelRelaysRNW

Controls ElectronicRelays-RTW,RPW,RNWSeriesg High precision electronic circuit with noise immunity.gCompact,witha22.5mmwidthframe,directmountingonDINrail35mmorfixedwithscrews.g Equipped with reliability LED for status indications. g Designed in accordance with international standards

StandardsIEC/EN1812-1IEC/EN60947-1IEC/EN60947-5-1UL508CAN/CSAC22.2

Certifications

Idealforapplicationssuchasindustrialprocesses,automationandmotorstarters, RTW timing relays switch an output signal based on a selected timeandfunction.Settingtimerangesfrom0.2sto150h.

Witha22.5mmwidthframetheRTWissuppliedasacompetitivesolution including the following features:

gDirectmountingonDINrail35mmorfixedwithscrews;g1or2outputcontacts(Cform);g RTW-RE – On-Delayg RTW-RD – Off-Delayg RTW-RDI–Off-DelaywithoutControlVoltagegRTW-PE–ImpulseOngRTW-CI–AssymmetricFlasherStartONgRTW-CIL–SymmetricFlasher-StartONgRTW-CID–SymmetricFlasher-StartOFFg RTW-ET – Wye - Delta

Timing Relay RTW

APG2011 B.indd 264 7/27/11 11:52 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-265

Controls ElectronicRelays-RTW,RPW,RNWSeries

LevelRelayRNW

RPW protection relays are a competitive choice for monitoring voltage againstthemostcommontypesofelectricalfailures.Monitoringvoltagesin electric installations are important for several reasons. Overvoltage, or phase loss can overheat machinery and motors, thus reducing their lifetime. Phase sequence inversion can cause machinery to run in a wrong way,thendestroyingtheentiresystem;andundervoltagemayoccurcausing machinery to run in an undefined range, which could cause some parts of a system to run properly while others cease operating.With five different functions, the RPW series are ideal to be used in electric motor control panel applications.

gRPWSF–PhaseSequenceRelaygRPWFF–PhaseLossRelaygRPWFSF–PhaseSequenceandPhaseLossRelaygRPWSS–UnderandOvervoltageRelayg RPW PTC – Thermistor Relay

These electronic control devices enable monitoring and automatic level adjustment of an electrical current liquidconductor. Widely used in general reservoir automation,theRNWseriesrelayscanbeusedinapplicationssuchasprevention of dry pumps, operation, monitoring against fillingtank overflow, activation of solenoids or alarms. This seriesoffers digital electronics that provide high precision,repeatability, and noise resistance. The supply system is isolated from the electronic circuit, therefore ensuring greateruser safety.

The operating principle is based on measuring the electricalresistance of the liquid through electrodes for presence or abscence. To optimize preformance, the relay has a dialfor sensitivity to the liquid's resistance being measured.

gRNWEN-FillinggRNWES-Draining

Protection Relays RPW

APG2011 B.indd 265 7/27/11 11:52 AM

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-266

Timing Relays - Multi-Voltage & Multi-Timing

Controls ElectronicRelays-RTW,RPW,RNWSeries

Function / description output contacts Voltage timing catalog number list PriceMult.

symbol

On-Delay DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc0.2 sec - 150 hours rtW-rE02-MBtE05 $90.00 Z7

Off-Delay (with control command) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc0.2 sec - 150 hours rtW-rd02-MBtE05 $90.00 Z7

Impulse ON DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc0.2 sec - 150 hours rtW-PE02-MBtE05 $90.00 Z7

Symm Flasher - Pulse (Start ON) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc0.2 sec - 150 hours rtW-cIl02-MBtE05 $90.00 Z7

Symm Flasher - Pause (Start OFF) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc0.2 sec - 150 hours rtW-cId02-MBtE05 $90.00 Z7

Wye-Delta Timing Relay DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc0.1 sec - 10 min rtW-Et02-MatE05 $90.00 Z7

Timing Relays - Multi-Voltage & Single-TimingFunction / description output contacts Voltage timing catalog number list Price Mult. symbol

Off-Delay (without control com-mand)

DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc

0.3 sec - 3 sec rtW-rdI02-u003sE05

$81.90 Z7

1 sec - 10 sec rtW-rdI02-u010sE053 sec - 30 sec rtW-rdI02-u030sE05

10 sec - 100 sec rtW-rdI02-u100sE0530 sec - 300 sec rtW-rdI02-u300sE05

180 sec - 1800 sec rtW-rdI02-u010ME05

Asymm Flasher - Pulse (start ON) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc

0.3 sec - 3 sec rtW-cI02-u003sE05

$81.90 Z7

1 sec - 10 sec rtW-cI02-u010sE053 sec - 30 sec rtW-cI02-u030sE05

10 sec - 100 sec rtW-cI02-u100sE0530 sec - 300 sec rtW-cI02-u300sE05

180 sec - 1800 sec rtW-cI02-u030ME05

Asymm Flasher - Pause (start OFF) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz

24-240 Vdc

0.3 sec - 3 sec rtW-cIr02-u003sE05

$81.90

Z7

1 sec - 10 sec rtW-cIr02-u010sE053 sec - 30 sec rtW-cIr02-u030sE05

10 sec - 100 sec rtW-cIr02-u100sE0530 sec - 300 sec rtW-cIr02-u300sE05

180 sec - 1800 sec rtW-cIr02-u030ME05DPDT - Double Pole Double Throw = 2N.O./N.C. changeover contact sets

Function / description output contacts replace “#” by Voltage code catalog number list PriceMult.

symbolThermistor Relay SPDT (1NO/NC) E05 = 24-240Vac/Vdc rPW-Ptc# $105.00 Z7

Phase-loss Protection Relay SPDT (1NO/NC)d66 = 220-240Vac; d74 = 440-480Vac;

rPW-FF# $84.00 Z7

Phase Sequence Protection Relay SPDT (1NO/NC)d66 = 220-240Vac; d74 = 440-480Vac;

rPW-sF# $84.00 Z7

Phase-loss and Phase-sequence Relay

SPDT (1NO/NC)d66 = 220-240Vac;d74 = 440-480Vac;

rPW-FsF# $94.50 Z7

Under and Overvoltage Relay SPDT (1NO/NC)d25 = 240Vac;d39 = 480Vac;

rPW-ss# $99.75 Z7

SPDT - Single Pole Double Throw = 1N.O./N.C. changeover contact set

Function / description output contacts Voltage catalog number list PriceMult.

symbol

Draining Relay SPDT (1NO/NC)100-240 Vac 50Hz/60Hz

100-240 VdcrnW-EsE09 $110.00 Z7

Filling Relay SPDT (1NO/NC)100-240 Vac 50Hz/60Hz

100-240 VdcrnW-EnE09 $110.00 Z7

Pendulum Type Electrode - - EPW $25.00 Z7Shaft Type Electrode - - EHW $79.00 Z7Push-in-Lugs - - PlMP $0.50 Z7SPDT - Single Pole Double Throw = 1N.O./N.C. changeover contact set

Protection Relays

Level Relays

APG2011 B.indd 266 7/27/11 11:52 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-267

Idealforapplicationssuchasindustrialprocesses,automationandmotorstarters,RTW timing relays switch an output signal based on a selected time and function.Witha22.5mmwidthframetheRTWisacompetitivesolutionwith:gDirectmountingonDINrail35mmorfixedwithscrewsusingthePLMPaccessory;g 1 or 2 output contacts (C form).g WideSupplyvoltage:24-240VAC50/60Hz/VDCg2timingranges,adjustablefrom0,1secondsto150hours,with8differentfunctions.

Offered in the following timing functions:g RTW- RE → On-Delayg RTW- RD → Off-DelaygRTW-RDI→ Off-Delay without Control Commandg RTW- PE →ImpulseOngRTW-CI→AssymmetricFlasherStartONgRTW-CIL→SymmetricFlasher-StartONgRTW-CID→SymmetricFlasher-StartOFFg RTW- ET → Wye – Delta (1)

Standards

Certifications

IEC/EN1812-1

IEC/EN60947-1

IEC/EN60947-5-1

RTW - 02 - MBT - E05Timing Relay

Number of Output Contacts01 – 1 Output Contact02 – 2 Output Contacts

Timing RangeMAT – 0,1 second to 10 minutes (2)

MBT – 0,2 second to 150 hours (2)

U001S - 0.1 to 1 secondU003S - 0.3 to 3 secondsU010S - 1 to 10 secondsU030S - 3 to 30 secondsU060S - 6 to 60 secondsU100S - 10 to 100 secondsU300S - 30 to 300 seconds

Voltage Supply:According to following tableType

RE - On-Delay

PE - Impulse On

CI - Assymmetric Flasher Start ON

CIL - Symmetric Flasher - Start ON

CID - Symmetric Flasher - Start OFF

RD - Off-Delay

RDI - Off-Delay without Control Voltage

ET - Wye – Delta (1)

code Voltage rtW-rE rtW-PE rtW-cI rtW-cIl rtW-cId rtW-rd rtW-rdI rtW-Et

E05 24-240VAC 50/60 Hz/ VDC X X X X X X X X

Notes: (1) Star-Delta function requires 2 output contacts and MAT timing range(2) Timing ranges not avaliable for RTW-CI/CIR/RDI

Selection

Controls ElectronicRelays-RTW,RPW,RNWSeries

APG2011 B.indd 267 7/27/11 11:52 AM

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-268

RTW RE (ON - Delay) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the selected time delay begins and the

green LED turns on. After the end of the delay time the output relay picks up (red LED turns on) and remains energized until

the supply voltage is removed. This can be repeated as often as required.

Reset: Removing supply voltage resets the time delay and the output.

RTW PE (Impulse On) – Connecting a supply voltage on terminals A1-A2 / A3-A2 (green LED turns on) the output relay picks

up without delay (red LED turns on) and remains energized until the selected pulse time elapse (red LED turns off). This can

be repeated as often as required.Reset: Removing supply voltage resets the time delay and the output.

RTW RD (OFF Delay) – This function requires continuous supply voltage on terminals A1-A2 (green LED turns on) and timing

is controlled by a command contact at terminals A2-B1. If the command contact is energized, the output relay picks up (red

LED turns on) and after the command contact is removed the selected time delay begins. When the selected time elapse the

output relay is de-energized (red LED turns off). This can be repeated as often as required.Reset: Removing supply voltage

resets the time delay and the output.

RTW RDI (OFF Delay with no control command) – Connecting a supply voltage on terminals A1-A2 / A3-A2, the green LED

turns on and the output relay picks up without delay (red LED turns on). If the supply voltage is de-energized, the selected

time delay begins and when this time elapse, the output relay is de-energized (red LED turns off). This can be repeated as

often as required. Reset: Removing supply voltage resets the time delay and the output.

RTW CI (Assymmetric Flasher-Pulse) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the green LED turns on and

the timer starts to pulse with adjustable ON/OFF cycles. The upper dial presets the ON time (red LED turns ON and output

relay picks up) and the lower select the OFF time when the output relay is de-energized.

Reset: Removing supply voltage resets the time delay and the output.

RTW CIL (Symmetric Flasher - Pulse) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the green LED turns on and

the timer starts to pulse with symmetric ON/OFF cycles.The dial presets a fixed ON time (red LED turns ON and output relay

picks up) and OFF time. Reset: Removing supply voltage resets the time delay and the output.

RTW CID (Symmetric Flasher - Pause) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the green LED turns on

and the timer starts to pulse with symmetric OFF/ON cycles.The dial presets a fixed ON time (red LED turns ON and output

relay picks up) and OFF time. Reset: Removing supply voltage resets the time delay and the output.

RTW ET (Wye-Delta) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the output relay for the wye-connection

picks up and the adjusted time starts (red LED turns ON). When the start-up time elapses, a fixed star-delta changeover

time of 100 ms starts and after this star-delta changeover time elapses the output relay for the delta-connection picks up

and stays energized until the supply is disconnected.

Reset: Removing supply voltage resets the time delay and the output.

SupplyA1 - A2 / A3 - A2

Output15 - 16 - 18 / 25 - 26 - 28

SupplyA1 - A2 / A3 - A2

Output15 - 16 - 18 / 25 - 26 - 28

SupplyA1 - A2 / A3 - A2

Output15-16-18 / 25-26-28

SupplyA1 - A2

CommandA2 - B1

Output15 - 16 - 18 / 25 - 26 - 28

SupplyA1 - A2 / A3 - A2

Output Y 15 - 16 - 18

Output ∆ 25 - 26 - 28

Ton Toff=

SupplyA1 - A2 / A3 - A2

Output15-16-18 / 25-26-28

SupplyA1 - A2 / A3 - A2

Output15-16-18 / 25-26-28

Ton Toff=

Ton Toff=off on

SupplyA1-A2 / A1-A3

Output15-16-18 / 25-26-28

Operation Modes Function Diagram

Controls Timing Relays - RTW Series

APG2011 B.indd 268 7/27/11 11:53 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-269

Controls Timing Relays - RTW Series

connection diagrams

The RTW Timing Relay has status indicator LEDs, as shown below:

The desired timing must be adjusted through its front adjustment DIAL, the scale is presented in seconds for all timing, except for the 3 to 30 minute scale.

timing relay adjustment

Light indications on Relay

Red LEDGreen LED

Wye OutputDelta Output

rtW - Et

The RTW relays can be individually mounted on DIN 35mm rail or with screws using the PLMP accessory.

rtW-cI / cIr / rdI rtW-rE / PE / cIl / cId / rd rtW-Et0.1 sec to 1 sec

0.1 sec to 10 min 0.2 sec to 150 h 0.1 sec to 10 min

0.3 sec to 3 sec1 sec to 10 sec3 sec to 30 sec6 sec to 60 sec30 sec to 300 sec3 min to 30 min

Red LED

Green LED

Energized Output

Energized Relay

rtW - rE rtW-PE rtW-cI/cIr/cIl/cId rtW-rd/rdI

A1 - A2

A2 - B1

15 - 16 - 18

25 - 26 - 28

24-240VAC/VDC (50/60Hz)

X

Output 1

Output 2

24-240VAC/VDC (50/60Hz)

X

Output 1

Output 2

24-240VAC/VDC (50/60Hz)

X

Output 1

Output 2

24-240VAC/VDC (50/60Hz)

24-240VAC/VDC(50/60Hz)

Output 1

Output 2

24-240VAC/VDC (50/60Hz)

X

Output 1

Output 2

rtW Et

Supply voltage

Control voltage

rtW rE

25 26 28

A1 15

16 18 A2

rtW PE

A1 15

16 18 A225 26 28

16 18 A225 26 28

rtW cI

16 18 A225 26 28

A1 15 A1 15

rtW rd

16 18 A225 26 28

A1 15 B1

rtW - rE rtW - PE rtW - rd / rdI rtW - EtrtW - cI / cIl / cId

2E 2E 2E 2E 2E

term

inal

pos

ition

sci

rcui

tdi

agra

m

APG2011 B.indd 269 7/27/11 11:53 AM

1-800-ASK-4WEG

www.weg.net

TIMING RELAYS

Data is subject to change without notice.B-270

Controls Timing Relay - RTW Series

Function contactsSupply Terminals

Timing catalog NumberA1-A2Voltage (V)

2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h RTW-RE 02 - MbT

Function contactsSupply Terminals

Timing catalog NumberA1-A2

2NOC 24-240VAC/VDC (50/60Hz)

0.1 to 1 sec0.3 to 3 sec1 to 10 sec3 to 30 sec

10 to 100 sec 30 to 300 sec1 to 10 min

RTW RdI 02 - uoo1SRTW RdI 02 - uoo3SRTW RdI 02 - uo10SRTW RdI 02 - uo30SRTW RdI 02 - u100SRTW RdI 02 - u300SRTW RdI 02 - uo10M

Function contactsSupply Terminals controls

TerminalsTiming catalog NumberA1-A2 A2-b1

Voltage (V)

2NOC 24-240VAC/VDC (50/60Hz)

24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h RTW-Rd 02 - MbT

On-Delay

Off-Delay

Off-Delay without control voltage

Reference Table

APG2011 B.indd 270 8/2/11 10:52 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-271

Function contactssupply terminals

timing catalog numbera1-a2Voltage (V)

2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h rtW-rE 02 - MBt

Function contactssupply terminals

timing catalog numbera1-a2

2NOC 24-240VAC/VDC (50/60Hz)

0.1 to 1 sec0.3 to 3 sec1 to 10 sec3 to 30 sec

10 to 100 sec 30 to 300 sec1 to 10 min

rtW rdI 02 - uoo1srtW rdI 02 - uoo3srtW rdI 02 - uo10srtW rdI 02 - uo30srtW rdI 02 - u100srtW rdI 02 - u300srtW rdI 02 - uo10M

Function contactssupply terminals controls

terminalstiming catalog numbera1-a2 a2-B1

Voltage (V)

2NOC 24-240VAC/VDC (50/60Hz)

24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h rtW-rd 02 - MBt

Controls Timing Relay - RTW Series

Reference Table

Impulse - ON

Wye-Delta

Assymmetric Flasher - Pulse

Symmetric Flasher - Pulse/Pause

Function contactssupply terminals

timing catalog numbera1-a2

2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150h rtW-PE 02 - MBt

Function contactssupply terminals

timing catalog numbera1-a2

2NOC 24-240VAC/VDC(50/60Hz)

0.1 to 1 sec0.3 to 3 sec1to 10 sec3 to 30 sec

10 to 100 sec30 to 300 sec3 to 30 min

rtW-cI 02 - u001srtW-cI 02 - u003srtW-cI 02 - u020srtW-cI 02 - u030srtW-cI 02 - u100srtW-cI 02 - u300srtW-cI 02 - u030M

Function contactssupply terminals

timing catalog numbera1-a2

2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h rtW-cIl/cId 02 - MBt

contactssupply terminals

timing catalog numbera1-a2

2NOC 24-240VAC/VDC (50/60Hz) 0.1 sec to 10 min rtW Et 02 - Mat

APG2011 B.indd 271 7/27/11 11:53 AM

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-272

dIMEnsIons mm (in)

80 (3

.15)

22.5 (0.89)

80 (3

.15)

104

(4.1

0)

74.6

(2.9

4)

85.5 (3.35)

91.3

(3.6

0)

12.7 (0.50)

4.80 (1.19)

RTW – RE / PE / RD / RDI / CI / CIL / CID / ET

Controls Timing Relays - RTW Series

30024Vac 50/60Hz • 48Vac 50/60Hz

110-130Vac 50/60Hz • 220-240Vac 50/60Hz24Vdc (only RTW RD)

24Vdc (except RTW-RD)

24Vac 50/60Hz • 48Vac 50/60Hz110-130Vac 50/60Hz • 220-240Vac 50/60Hz

24Vdc 0.85...1.1 x Uc for Vac0.8...1.25 x Uc for Vdc

35 for Ue = 24Vdc65 for Ue = 110Vac75 for Ue = 130Vac55 for Ue = 220Vac60 for Ue = 240Vac

100

50±5±1100

31

0.450.350.20.1

A300R300

4

30 x 106

10 x 105

-5 a +60 (23...140)-40 a +85 (-40...125)

Frame IP20 / Terminals IP20

1 x (0.5 to 2.5)2 x (0.5 to 1.5)1 x (0.5 to 1.5)2 x (0.5 to 1.5)

2 x (20 to 16)

0.8 to 14.7 (7.1 to 12.3)M3

any position15/11

10 to 500/100.1(35)

V

Vac

Vdc

Vac

mA

ms

ms%%

ms(le)

A

A

ºC (F)ºC (F)

mm2

mm2

AWG

N.m (lb.in)

rtW

Inpu

tsti

me

adju

stou

tput

s

Rated Insulation Voltage (Ui) Supply Voltage (Ue) A1 – A2 A2 – A3

Comand (Uc) A2 – B1 (Only RTW RD)

Voltage limits

Consumption

Minimum Time for ResetMinimum ON Time (for RTW RD) Setting Accuracy (as % of the full scale value)Repeat AccuracyChangeover time y - ∆Output contacts capacity AC-15 on 230 Vdc DC-13 on 24Vdc DC-13 on 48Vdc DC-13 on 60Vdc DC-13 on 125Vdc DC-13 on 250Vdc

Acc. UL;CSA

Fuse (class gL/Gg)

Mechanical DurabilityElectrical DurabilityAmbient Temperature- Operation - StorageProtection Degree Connection Section (min. to max.)

- Cable without end sleeve

- Cable with end sleeve

- AWG-WireTightening TorqueTerminal ScreewMounting PositionShock ResistanceVibration Resistance

Weight

g/msHz/mmkg (oz)

Mec

hani

cal

Feat

ures

Acc. IEC 60947-5-1

operating cycles

operating cycles

Product

APG2011 B.indd 272 7/27/11 11:53 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-273

Connection Diagram

L1 L2 L3

A B N

Neutral Selection

16 18

15

L1 15 L2

16 18 L3

RPW FSF

A B N

Sensitivity Adjustment

The sensitivity adjustment (threshold) is made by

the DIAL located on the front of the relay.

It ranges from 70% to 90%, which defines the

balance for one phase related to the others.

LED Indication

Output energized

Protector energized

Protection Relay RPW is provided

with LED’s for status indication.

The RPW relay can be mounted directly on DIN rail 35mm or fixed

with screws using the accessory PLMP.

Assembly

rPW- FsFd66

Phase Sequence and Phase Loss

sElEctIon:

WEG Protection Relay

Voltage Selection

Available Voltages:220-240Vac 50/60Hz - D66440-480Vac 50/60Hz - D74

RPW FSF (without neutral selection) The Phase Sequence and Phase Loss Relay -

RPW FSF - is used to monitor three-phase networks against phase loss and incorrect

phase sequence.

Operation: If the phase sequence at the terminals L1-L2-L3 is correct and balanced

with values higher than the selected on the dial, the output relay picks up (close the

15-18 terminals) and the red LED turns ON. In case of an incorrect phase sequence

or a phase fails below the threshold value, the output relay remains in its rest position

(close the 15-16 terminals) and the red LED turns OFF.

RPW FSF (with Neutral selection) The Phase Sequence and Phase Loss Relay - RPW

FSF - is used to monitor three-phase networks and neutral against phase failure and

incorrect phase sequence.

Operation: In the same product, the neutral protection is enabled jumpering the terminals

A and B to monitor the neutral voltage (terminal N). The neutral must be connected to

the protection relay for proper operation.

Note: When one phase fails, connected loads (motor windings, lamps, transformers, coils, etc.) create a feedback voltage at the terminal of the failed phase due to the network coupling. Such phase failure is detected with the RPW FSF.

Controls Protection Relays - RPW Series

t

V

15-18

15 15

16 1616 1618 1818 18

15 15

15-16

LEDON

LEDON

LEDOFF

LEDOFF

L1-L2-L3 L1-L2-L3

Phase or neutral loss

L1-L2

Phaseinversion

L1-L2

Functional Diagram

APG2011 B.indd 273 7/27/11 11:53 AM

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-274

RPW-SF The Phase Sequence Relay - RPW-SF - is used to monitor three-phase networks against incorrect phase sequence.

Operation: If the phase sequence at the terminals L1-L2-L3 is correct, the output relay picks up (close the 15-18 terminals) and the red LED turns ON. In case of an incorrect phase sequence, the output relay remains in its rest position (close the 15-16 terminals) and the red LED is turns OFF.

rPW- sFd66

Phase SequenceWEG Protection Relay

LED Indication

Connection Diagram Functional Diagram

Output energized

Protector energized

Protection Relay RPW is provided

with LED’s for status indication.

L1 15 L2

16 18 L3

RPW SF

L1 L2 L3

16 18

15

The RPW relay can be mounted directly on DIN rail 35mm

or fixed with screws using the accessory PLMP.

Assembly

L1-L3-L2

t

Phase Inversion

LED OFF

LED ON

Voltage Selection

Available Voltages:220-240Vac 50/60Hz - D66440-480Vac 50/60Hz - D74

Controls Protection Relays - RPW Series

APG2011 B.indd 274 7/27/11 11:53 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-275

RPW FF (without neutral selection) The Phase Loss Relay - RPW FF - is used to monitor three-phase networks against phase failure.

Operation: Connected directly to the supply voltage to be monitored, and connecting the three phases with values above than the selected on the dial, the output relay is energized (close the 15-18 terminals) and turns on the red LED indicating that the system is properly working. In case the voltage falls below the threshold value the output relay is de-energized (close the 15-16 terminals) and the red LED is turns OFF.

RPW FF (with neutral selection)The Phase Loss Relay - RPW FF - is used to monitor three-phase networks and the neutral against phase failure.

Operation: In the same product, the neutral protection is enabled jumpering the terminals A and B to monitor the neutral voltage (terminal N). The neutral must be connected to the protection relay for proper operation.

rPW- FFd66

Phase Loss

sElEctIon:

WEG Protection Relay

Sensitivity AdjustmentThe sensitivity adjustment (threshold) is made

by the DIAL located on the front of the relay.

It ranges from 70% to 90%, which defines the

balance for one phase related to the others.

Connection Diagram

L1 L2 L3

A B N

Neutral Selection

16 18

15

Functional Diagram

L1 15 L2

16 18 L3

RPW FF

A B N

t

LED ON

LED OFF

LED ON

LED OFF

LED Indication

Output energized

Protector energized

Protect ion Relay RPW is

provided with LED’s for status

indication.

The RPW relay can be mounted directly on DIN rail 35mm or fixed with screws using the accessory PLMP.

Assembly

Voltage Selection

Available Voltages:220-240Vac 50/60Hz - D66440-480Vac 50/60Hz - D74

Note:Whenonephasefails,connectedloads(motorwindings,lamps,transformers,coils,etc.)createa

feedback voltage at the terminal of the failed phase due to the network coupling. Such phase failure is de-

tectedwithRPWFF.

Controls Protection Relays - RPW Series

APG2011 B.indd 275 7/27/11 11:54 AM

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-276

Connection Diagram

L1 L2 L3

16 18

15

Functional Diagram

L1 15 L2

16 18 L3

RPW SS

Sensititivy Adjustment

The sensitivity adjustment (threshold) is made by

the DIAL located on the front of the relay. It ranges

from -15% to -3% (for under voltage) and +3%

to +15% (for over voltage).

LED Indication

Output energized

Protector energized

Protection Relay RPW is

provided with LED’s for

status indication.

The RPW relay can be mounted directly on DIN rail 35mm or fixed with screws using the accessory PLMP.

Assembly

rPW- ssd25

Under and Over Voltage

WEG Protection Relay

Voltage Selection

Available Voltages:240Vac 50/60Hz – D25480Vac 50/60Hz – D39

Assymmetry

RPW-SS The Under and Over-voltage Relay RPW SS is used to monitor maximum and minimum

variations that three-phase power supplies are able to work. The RPW SS also protects the circuit

against phase unbalance (asymmetry) of 20% or higher between phases.

Operation: Connecting the phases L1-L2-L3 with phase amplitudes within the selected values

and assymmetry between them below the threshold (20%), the output relay picks up (close

the 15-18 terminals) and the red LED turns ON. In case of a phase loss, assymmetry between

phases higher than 20% or under and over-voltage, the output relay remains in its rest position

(close the 15-16 terminals) and the red LED is turns OFF.

Controls Protection Relays - RPW Series

APG2011 B.indd 276 7/27/11 11:54 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-277

rPW-PtcE05

Thermistor Relay

sElEctIon:

WEG Protection Relay

Voltage Selection

Available Voltages:24-240Vac 50/60Hz / Vdc - E05

RPW-PTC The Thermistor Relay RPW PTC is used to measure the motor temperature by using

PTC sensor inside of the motor. When the motor temperature rises above the PTC sensor class,

the output relay is de-energized avoiding damages to the motor.

Operation: Connected directly to the supply voltage and in series to the PTC sensor (maximum of

3 sensors), the output relay is automatically energized (close the 15-18 terminals) and turns on

the red LED indicating that the temperature is within acceptable values. If an over temperature

occurs, the probe resistance is rapidly increased and the output relay is de-energized (close the

15-16 terminals) and the red LED turns OFF, remaining on this situation until the temperature

decreases at a normal value. The RTW PTC is able to evaluate if the PTC sensor has a fault (not

caused by an over temperature) or if is not connected (open circuit). In such situations, the green

LED will start flashing.

Controls Protection Relays - RPW Series

a1 15

16 18 A2

RPW PTC

S1 S2

Functional Diagram

Normal Operation

Elevated Temperature

Energized

Not energized

PTC sensor failure

On

Off

On

Off

Flashing

Relay Light Indications

A1 - A2 Voltage Supply

24...240 VCA / VDC

S1 - S2 PTC sensor input

15 - 16 - 18 Output

Terminals

TheRPWRelayscanbeindividuallymountedonDIN35mmrailorwithscrewsusingthePLMPaccessory.

LEDONA1 - A2 / A3 - A2

Output15 - 18

Power Supply

Red LED

Green LED

500

1000150025003600R [Ω]

LEDOFF

LED LEDFlashing

151515 15

161616 16181818 18

Flashing

Connection Diagram

APG2011 B.indd 277 7/27/11 11:54 AM

1-800-ASK-4WEG

www.weg.net

Data is subject to change without notice.B-278

tIMInG rElaYs

Inpu

tsOu

tput

sM

echa

nica

l Fea

ture

s

DIMENSIONS mm (in)

80 (3

.15)

22.5 (0.89)

80 (3

.15)

104

(4.1

0)

74.6

(2.9

4)

85.5 (3.35)

91.3

(3.6

0)

12.7 (0.50)

4.80 (1.19)

RPW – FF / SF / FSF / SS / PTC

Product

Controls Protection Relays - RPW Series

220 or 480

rPW-FF rPW-sF rPW-FsF rPW-ss rPW-Ptc

APG2011 B.indd 278 7/27/11 11:54 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-279

Controls LevelRelays-RNWSeriesWEG Level Relays are electronic control devices that enable the monitoring and automatic adjustment of levels in electric currentliquidconductors.Widelyusedingeneralreservoirautomation,theRNWrelayscanalsobeutilizedinseveralapplications such as prevention of dry pump operation, monitoring against filling tank overflow, activation of solenoids or alarms/lighting.The operating principle is based on measuring the electrical resistance of the reservoir liquid through electrodes that work asliquidpresence/absencesensors.Tooptimizetheirperformance,therelayhasasensitivityDIALenablingtheelectroniccircuit to be adjusted to the liquid resistance.Availablein2functions,RNW-ENfillingandRNW-ESdraining,thelevelrelayoffersdigitalelectronicsthatprovidehighprecision, repeatability and noise resistance. The supply system is isolated from the electronic circuit therefore ensuring greaterusersafety.Designedinaccordancewithinternationalstandards,theRNWoffersasafeandcompactsolution,in22,5mmwidehousingforassemblyon35mmDINrail,with1outputreversablecontact(Cform)andvoltagesupplyrangeof100-240VAC/VDC.

Available in the following functions:g RNW EN -> Fillingg RNW ES -> Draining

Selection

Functional DiagramTheelectrodesarefixedinthereservoiraccordingtodesiredcontrollevels,minimumormaximum.Thereferenceelectrode(C)mustbepositionedinthelowerpart,belowthemaximumandminimumlevel etectrodes. When the system is energized, an alternating current is applied to the reference electrode and,once the liquid comes into contact with the level electrodes, a path is established for the circulation of electrical current between the electrodes. An electronic current compares the current and switches the relay outputcontactsaccordingtothechosenmodel(RNWESorRNWEN).Theelectrodesareavailablein2versions,shaft(EHW)orpendulum (EPW), the difference between them is the assembly type.TheRNWisavailableintwodistinctfunctions,drainingandfilling. Note: The EHW shaft sensors can be fixed both horizontally and vertically

MaxElec

Min Elec

C Elect.

Pendulum Type Shaft Type

MaxElec

MinElec

C Elect

RNW - EN - E 09

WEG Level Relay

Available Voltage Range E09=100-240 VAC /VDCType: EN - Filling

ES - Draining

Standards

Approval

IEC / EN 60947-1IEC / EN 60947-5-1

APG2011 B.indd 279 7/27/11 11:54 AM

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-280

Controls LevelRelays-RNWSeries

Applications

Sensitivity Adjustment

Liquid resistance can vary according to the liquid in question and the position of the electrodes. To adapt the electronic circuit to the liquid used, sensitivity must be adjusted through the DIAL located in the front part of the RNW, which has a graded scale without values. To perform the sensitivity adjustment, all electrodes must be submersed into the reservoir liquid and the DIAL positioned at its limit anti-clockwise (less resistance). With the relay energized, the DIAL must be turned clockwise (greater resistance) until the relay output switches its contacts (the red LED must change status). To confirm the adjustment, the reference electrode C must be disconnected and then quickly reconnected, the relay must return to its previous status. If this not happen, a new adjustment must be performed. By doing this, the RNW will be adjusted to the ideal sensitivity point.

Relay Light IndicationsThe RNW Level Relay is equipped with indicator LEDs as shown on the right:

Characteristics

Energized OutputEnergized Relay

APG2011 B.indd 280 7/27/11 11:55 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-281

Controls LevelRelays-RNWSeries

Controls 2 levels using 3 electrodes: the reference electrode (C), the maximum level electrode (Max) and the minimum level electrode (Min). Once powered, the RNW ES start monitoring the liquid level in the reservoir. With the liquid being in contact with the Max level electrode, the relay will energize (terminals 15-18 closed), causing the reservoir liquid level begin to drop. Once the Min level electrode is uncovered by the liquid the relay will energize (terminals 15-18 open) and will remain energized until the liquid enters into contact again with the Max level electrode, restarting the process. If there is a supply failure, the RNW ES will restart its initial logic.

RNWES(Draining)

Controls 2 levels using 3 electrodes: the reference electrode (C), the maximum level electrode (Max) and the minimum level electrode (Min). Once powered, the RNW EN start monitoring the liquid level in the reservoir. With the electrode being uncovered at minimum level Min, the output relay will energize (terminals 15-18 closed) causing the liquid level to rise. When the reservoir liquid covers the Max level electrode, the output realy de-energize (terminals 15-18 open) and remains de-energized until the Min level electrode is discovered again. If there is a supply failure, the RNW EN will restart its initial logic.

RNWEN(Filling)

Connection Diagrams Functional Diagram

A1 15

16 18 A2

RNW EN

Max Min C

Level

15 15 15

16 16 1618 18 18

LEDOFF

LEDOFF

LEDOFF

15 15 15

16 16 1618 18 18

LEDON

LEDON

LEDON

t

15 - 18

C

Min

Max

Power Supply A1-A2

Max Min

15

1816

C

Connection Diagrams

A1 15

16 18 A2

RNW ES

Max Min C

Functional diagram

Level

15 15

16 1618 18

LEDOFF

LEDOFF

15 15 15

16 16 1618 18 18

LEDON

LEDON

LEDON

t

15 - 18

C

Min

Max

Power Supply A1-A2

Max Min

15

1816

C

APG2011 B.indd 281 7/27/11 11:55 AM

1-800-ASK-4WEG

www.weg.net

tIMInG rElaYs

Data is subject to change without notice.B-282

Controls LevelRelays-RNWSeries

Teflon coated stainless steel shaft11/4“chromehexscrewLength: 300 mmnote: other lengths upon requestMaximum sensor cable 100m (110yd)

Dimensions (mm)

Adaptor for screw fixing - PLMP

Shaft electrode - EHW

Pendulum electrode - EPW

Body in natural black polypropylene Stainless steel sensor shaft1x10mm2gaugeflexibleconnectioncableCable length: 1000 mmnote: Maximum sensor cable 100m (110yd)

Accessories

Dimensions (mm)

Dimensions (mm)

APG2011 B.indd 282 7/27/11 11:55 AM

WEG Automation - Products and Solutions

www.weg.net

tIM

InG

rEla

Ys

Data is subject to change without notice. B-283

Controls LevelRelays-RNWSeries

RNWTechnicalData

Inpu

tsOu

tput

sCh

arac

teris

tics

Elec

trode

s

Product rnW Es / rnW EnSupply (Un) A1 VAC 100-240 50 /60 Hz

A2 VDC 100-240

Isolated Rated Voltage (Ui) V 300

Operating Limits 0.85 to 1.1 x Ue

Maximum Consumption VA / W 2 / 1

Contacts 15 - 16 / 18 1 SPDT

Output Contact Capacity (Ie)

A

5 (resistive load)

AC-15 in 230 Vca 3

DC-13 in 24 VDC 1

DC-13 in 48 VDC 0.45

DC-13 in 60 VDC 0.35

DC-13 in 125 VDC 0.2

DC-13 in 250 VDC 0.1

A300 : AC-15

R300 : DC-13

Rated thermal current (lth) A10 (for AC)

2.5 (for DC)

Fuse (class gL / gG) A 4

Mechanical Lifespan operations 30 x 106

Temperature

OperationºC (F)

-5 to +60 (23...140)

Storage -40 to +85 (-40...185)

Degree of Protection IP20

Terminal Capacity Rigid or fexible Cable mm21 x (0.5 to 2.5)

2 x (0.5 to 1.5)

Cable with TerminalRigid or fexible Cable/Terminal mm2

1 x (0.5 to 2.5)

2 x (0.5 to 1.5)

AWG Solid conductor AWG 2 x (30 to 14)

Tightening torque N.m 0.8 to 1.2

lb.in 7 to 10.6

Terminal Screws M3

Assembly Position Any

Resistance to Impacts g / ms 15 / 11

Resistance to Vibration Hz / mm 10 to 500 / 10

Weight kg 0.08

Pollution 2

Over voltage category II

Sensitivity Adjustment kΩ 0 to 100

Electrode Voltage VCA 7

Electrode Current mA 0.05

Maximum length of sensor cable m 100 (Maximum cable capacitance 2.2nF)

Detector operating temperature - ShaftºC (F)

0 to + 260 (32...500)

- Pendulum 0 to + 60 (32...140)

Allowable detector pressure - Shaftkgf / cm2

3

- Pendulum -

Detector Weight - Shaftkg

0.230

- Pendulum 0.012

APG2011 B.indd 283 7/27/11 11:55 AM

1-800-ASK-4WEG

www.weg.net

TIMING RELAYS

Data is subject to change without notice.B-284

Controls Level Relays-RNW Series

Dimensions

Relay Assembly

Electronic Relay Technical Data

DIMENSIONS mm (in)

80 (3

.15)

22.5 (0.89)

80 (3

.15)

104

(4.1

0)

74.6

(2.9

4)

85.5 (3.35)

91.3

(3.6

0)

12.7 (0.50)

4.80 (1.19)

APG2011 B.indd 284 7/27/11 12:10 PM