tIMInG rElaYs
Data is subject to change without notice.B-264
Electronic Relays
Protection Relays RPWTiming Relays RTWLevelRelaysRNW
Controls ElectronicRelays-RTW,RPW,RNWSeriesg High precision electronic circuit with noise immunity.gCompact,witha22.5mmwidthframe,directmountingonDINrail35mmorfixedwithscrews.g Equipped with reliability LED for status indications. g Designed in accordance with international standards
StandardsIEC/EN1812-1IEC/EN60947-1IEC/EN60947-5-1UL508CAN/CSAC22.2
Certifications
Idealforapplicationssuchasindustrialprocesses,automationandmotorstarters, RTW timing relays switch an output signal based on a selected timeandfunction.Settingtimerangesfrom0.2sto150h.
Witha22.5mmwidthframetheRTWissuppliedasacompetitivesolution including the following features:
gDirectmountingonDINrail35mmorfixedwithscrews;g1or2outputcontacts(Cform);g RTW-RE – On-Delayg RTW-RD – Off-Delayg RTW-RDI–Off-DelaywithoutControlVoltagegRTW-PE–ImpulseOngRTW-CI–AssymmetricFlasherStartONgRTW-CIL–SymmetricFlasher-StartONgRTW-CID–SymmetricFlasher-StartOFFg RTW-ET – Wye - Delta
Timing Relay RTW
APG2011 B.indd 264 7/27/11 11:52 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-265
Controls ElectronicRelays-RTW,RPW,RNWSeries
LevelRelayRNW
RPW protection relays are a competitive choice for monitoring voltage againstthemostcommontypesofelectricalfailures.Monitoringvoltagesin electric installations are important for several reasons. Overvoltage, or phase loss can overheat machinery and motors, thus reducing their lifetime. Phase sequence inversion can cause machinery to run in a wrong way,thendestroyingtheentiresystem;andundervoltagemayoccurcausing machinery to run in an undefined range, which could cause some parts of a system to run properly while others cease operating.With five different functions, the RPW series are ideal to be used in electric motor control panel applications.
gRPWSF–PhaseSequenceRelaygRPWFF–PhaseLossRelaygRPWFSF–PhaseSequenceandPhaseLossRelaygRPWSS–UnderandOvervoltageRelayg RPW PTC – Thermistor Relay
These electronic control devices enable monitoring and automatic level adjustment of an electrical current liquidconductor. Widely used in general reservoir automation,theRNWseriesrelayscanbeusedinapplicationssuchasprevention of dry pumps, operation, monitoring against fillingtank overflow, activation of solenoids or alarms. This seriesoffers digital electronics that provide high precision,repeatability, and noise resistance. The supply system is isolated from the electronic circuit, therefore ensuring greateruser safety.
The operating principle is based on measuring the electricalresistance of the liquid through electrodes for presence or abscence. To optimize preformance, the relay has a dialfor sensitivity to the liquid's resistance being measured.
gRNWEN-FillinggRNWES-Draining
Protection Relays RPW
APG2011 B.indd 265 7/27/11 11:52 AM
1-800-ASK-4WEG
www.weg.net
tIMInG rElaYs
Data is subject to change without notice.B-266
Timing Relays - Multi-Voltage & Multi-Timing
Controls ElectronicRelays-RTW,RPW,RNWSeries
Function / description output contacts Voltage timing catalog number list PriceMult.
symbol
On-Delay DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc0.2 sec - 150 hours rtW-rE02-MBtE05 $90.00 Z7
Off-Delay (with control command) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc0.2 sec - 150 hours rtW-rd02-MBtE05 $90.00 Z7
Impulse ON DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc0.2 sec - 150 hours rtW-PE02-MBtE05 $90.00 Z7
Symm Flasher - Pulse (Start ON) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc0.2 sec - 150 hours rtW-cIl02-MBtE05 $90.00 Z7
Symm Flasher - Pause (Start OFF) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc0.2 sec - 150 hours rtW-cId02-MBtE05 $90.00 Z7
Wye-Delta Timing Relay DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc0.1 sec - 10 min rtW-Et02-MatE05 $90.00 Z7
Timing Relays - Multi-Voltage & Single-TimingFunction / description output contacts Voltage timing catalog number list Price Mult. symbol
Off-Delay (without control com-mand)
DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc
0.3 sec - 3 sec rtW-rdI02-u003sE05
$81.90 Z7
1 sec - 10 sec rtW-rdI02-u010sE053 sec - 30 sec rtW-rdI02-u030sE05
10 sec - 100 sec rtW-rdI02-u100sE0530 sec - 300 sec rtW-rdI02-u300sE05
180 sec - 1800 sec rtW-rdI02-u010ME05
Asymm Flasher - Pulse (start ON) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc
0.3 sec - 3 sec rtW-cI02-u003sE05
$81.90 Z7
1 sec - 10 sec rtW-cI02-u010sE053 sec - 30 sec rtW-cI02-u030sE05
10 sec - 100 sec rtW-cI02-u100sE0530 sec - 300 sec rtW-cI02-u300sE05
180 sec - 1800 sec rtW-cI02-u030ME05
Asymm Flasher - Pause (start OFF) DPDT (2NO/NC)24-240 Vac 50Hz/60Hz
24-240 Vdc
0.3 sec - 3 sec rtW-cIr02-u003sE05
$81.90
Z7
1 sec - 10 sec rtW-cIr02-u010sE053 sec - 30 sec rtW-cIr02-u030sE05
10 sec - 100 sec rtW-cIr02-u100sE0530 sec - 300 sec rtW-cIr02-u300sE05
180 sec - 1800 sec rtW-cIr02-u030ME05DPDT - Double Pole Double Throw = 2N.O./N.C. changeover contact sets
Function / description output contacts replace “#” by Voltage code catalog number list PriceMult.
symbolThermistor Relay SPDT (1NO/NC) E05 = 24-240Vac/Vdc rPW-Ptc# $105.00 Z7
Phase-loss Protection Relay SPDT (1NO/NC)d66 = 220-240Vac; d74 = 440-480Vac;
rPW-FF# $84.00 Z7
Phase Sequence Protection Relay SPDT (1NO/NC)d66 = 220-240Vac; d74 = 440-480Vac;
rPW-sF# $84.00 Z7
Phase-loss and Phase-sequence Relay
SPDT (1NO/NC)d66 = 220-240Vac;d74 = 440-480Vac;
rPW-FsF# $94.50 Z7
Under and Overvoltage Relay SPDT (1NO/NC)d25 = 240Vac;d39 = 480Vac;
rPW-ss# $99.75 Z7
SPDT - Single Pole Double Throw = 1N.O./N.C. changeover contact set
Function / description output contacts Voltage catalog number list PriceMult.
symbol
Draining Relay SPDT (1NO/NC)100-240 Vac 50Hz/60Hz
100-240 VdcrnW-EsE09 $110.00 Z7
Filling Relay SPDT (1NO/NC)100-240 Vac 50Hz/60Hz
100-240 VdcrnW-EnE09 $110.00 Z7
Pendulum Type Electrode - - EPW $25.00 Z7Shaft Type Electrode - - EHW $79.00 Z7Push-in-Lugs - - PlMP $0.50 Z7SPDT - Single Pole Double Throw = 1N.O./N.C. changeover contact set
Protection Relays
Level Relays
APG2011 B.indd 266 7/27/11 11:52 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-267
Idealforapplicationssuchasindustrialprocesses,automationandmotorstarters,RTW timing relays switch an output signal based on a selected time and function.Witha22.5mmwidthframetheRTWisacompetitivesolutionwith:gDirectmountingonDINrail35mmorfixedwithscrewsusingthePLMPaccessory;g 1 or 2 output contacts (C form).g WideSupplyvoltage:24-240VAC50/60Hz/VDCg2timingranges,adjustablefrom0,1secondsto150hours,with8differentfunctions.
Offered in the following timing functions:g RTW- RE → On-Delayg RTW- RD → Off-DelaygRTW-RDI→ Off-Delay without Control Commandg RTW- PE →ImpulseOngRTW-CI→AssymmetricFlasherStartONgRTW-CIL→SymmetricFlasher-StartONgRTW-CID→SymmetricFlasher-StartOFFg RTW- ET → Wye – Delta (1)
Standards
Certifications
IEC/EN1812-1
IEC/EN60947-1
IEC/EN60947-5-1
RTW - 02 - MBT - E05Timing Relay
Number of Output Contacts01 – 1 Output Contact02 – 2 Output Contacts
Timing RangeMAT – 0,1 second to 10 minutes (2)
MBT – 0,2 second to 150 hours (2)
U001S - 0.1 to 1 secondU003S - 0.3 to 3 secondsU010S - 1 to 10 secondsU030S - 3 to 30 secondsU060S - 6 to 60 secondsU100S - 10 to 100 secondsU300S - 30 to 300 seconds
Voltage Supply:According to following tableType
RE - On-Delay
PE - Impulse On
CI - Assymmetric Flasher Start ON
CIL - Symmetric Flasher - Start ON
CID - Symmetric Flasher - Start OFF
RD - Off-Delay
RDI - Off-Delay without Control Voltage
ET - Wye – Delta (1)
code Voltage rtW-rE rtW-PE rtW-cI rtW-cIl rtW-cId rtW-rd rtW-rdI rtW-Et
E05 24-240VAC 50/60 Hz/ VDC X X X X X X X X
Notes: (1) Star-Delta function requires 2 output contacts and MAT timing range(2) Timing ranges not avaliable for RTW-CI/CIR/RDI
Selection
Controls ElectronicRelays-RTW,RPW,RNWSeries
APG2011 B.indd 267 7/27/11 11:52 AM
1-800-ASK-4WEG
www.weg.net
tIMInG rElaYs
Data is subject to change without notice.B-268
RTW RE (ON - Delay) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the selected time delay begins and the
green LED turns on. After the end of the delay time the output relay picks up (red LED turns on) and remains energized until
the supply voltage is removed. This can be repeated as often as required.
Reset: Removing supply voltage resets the time delay and the output.
RTW PE (Impulse On) – Connecting a supply voltage on terminals A1-A2 / A3-A2 (green LED turns on) the output relay picks
up without delay (red LED turns on) and remains energized until the selected pulse time elapse (red LED turns off). This can
be repeated as often as required.Reset: Removing supply voltage resets the time delay and the output.
RTW RD (OFF Delay) – This function requires continuous supply voltage on terminals A1-A2 (green LED turns on) and timing
is controlled by a command contact at terminals A2-B1. If the command contact is energized, the output relay picks up (red
LED turns on) and after the command contact is removed the selected time delay begins. When the selected time elapse the
output relay is de-energized (red LED turns off). This can be repeated as often as required.Reset: Removing supply voltage
resets the time delay and the output.
RTW RDI (OFF Delay with no control command) – Connecting a supply voltage on terminals A1-A2 / A3-A2, the green LED
turns on and the output relay picks up without delay (red LED turns on). If the supply voltage is de-energized, the selected
time delay begins and when this time elapse, the output relay is de-energized (red LED turns off). This can be repeated as
often as required. Reset: Removing supply voltage resets the time delay and the output.
RTW CI (Assymmetric Flasher-Pulse) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the green LED turns on and
the timer starts to pulse with adjustable ON/OFF cycles. The upper dial presets the ON time (red LED turns ON and output
relay picks up) and the lower select the OFF time when the output relay is de-energized.
Reset: Removing supply voltage resets the time delay and the output.
RTW CIL (Symmetric Flasher - Pulse) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the green LED turns on and
the timer starts to pulse with symmetric ON/OFF cycles.The dial presets a fixed ON time (red LED turns ON and output relay
picks up) and OFF time. Reset: Removing supply voltage resets the time delay and the output.
RTW CID (Symmetric Flasher - Pause) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the green LED turns on
and the timer starts to pulse with symmetric OFF/ON cycles.The dial presets a fixed ON time (red LED turns ON and output
relay picks up) and OFF time. Reset: Removing supply voltage resets the time delay and the output.
RTW ET (Wye-Delta) – Connecting a supply voltage on terminals A1-A2 / A3-A2 the output relay for the wye-connection
picks up and the adjusted time starts (red LED turns ON). When the start-up time elapses, a fixed star-delta changeover
time of 100 ms starts and after this star-delta changeover time elapses the output relay for the delta-connection picks up
and stays energized until the supply is disconnected.
Reset: Removing supply voltage resets the time delay and the output.
SupplyA1 - A2 / A3 - A2
Output15 - 16 - 18 / 25 - 26 - 28
SupplyA1 - A2 / A3 - A2
Output15 - 16 - 18 / 25 - 26 - 28
SupplyA1 - A2 / A3 - A2
Output15-16-18 / 25-26-28
SupplyA1 - A2
CommandA2 - B1
Output15 - 16 - 18 / 25 - 26 - 28
SupplyA1 - A2 / A3 - A2
Output Y 15 - 16 - 18
Output ∆ 25 - 26 - 28
Ton Toff=
SupplyA1 - A2 / A3 - A2
Output15-16-18 / 25-26-28
SupplyA1 - A2 / A3 - A2
Output15-16-18 / 25-26-28
Ton Toff=
Ton Toff=off on
SupplyA1-A2 / A1-A3
Output15-16-18 / 25-26-28
Operation Modes Function Diagram
Controls Timing Relays - RTW Series
APG2011 B.indd 268 7/27/11 11:53 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-269
Controls Timing Relays - RTW Series
connection diagrams
The RTW Timing Relay has status indicator LEDs, as shown below:
The desired timing must be adjusted through its front adjustment DIAL, the scale is presented in seconds for all timing, except for the 3 to 30 minute scale.
timing relay adjustment
Light indications on Relay
Red LEDGreen LED
Wye OutputDelta Output
rtW - Et
The RTW relays can be individually mounted on DIN 35mm rail or with screws using the PLMP accessory.
rtW-cI / cIr / rdI rtW-rE / PE / cIl / cId / rd rtW-Et0.1 sec to 1 sec
0.1 sec to 10 min 0.2 sec to 150 h 0.1 sec to 10 min
0.3 sec to 3 sec1 sec to 10 sec3 sec to 30 sec6 sec to 60 sec30 sec to 300 sec3 min to 30 min
Red LED
Green LED
Energized Output
Energized Relay
rtW - rE rtW-PE rtW-cI/cIr/cIl/cId rtW-rd/rdI
A1 - A2
A2 - B1
15 - 16 - 18
25 - 26 - 28
24-240VAC/VDC (50/60Hz)
X
Output 1
Output 2
24-240VAC/VDC (50/60Hz)
X
Output 1
Output 2
24-240VAC/VDC (50/60Hz)
X
Output 1
Output 2
24-240VAC/VDC (50/60Hz)
24-240VAC/VDC(50/60Hz)
Output 1
Output 2
24-240VAC/VDC (50/60Hz)
X
Output 1
Output 2
rtW Et
Supply voltage
Control voltage
rtW rE
25 26 28
A1 15
16 18 A2
rtW PE
A1 15
16 18 A225 26 28
16 18 A225 26 28
rtW cI
16 18 A225 26 28
A1 15 A1 15
rtW rd
16 18 A225 26 28
A1 15 B1
rtW - rE rtW - PE rtW - rd / rdI rtW - EtrtW - cI / cIl / cId
2E 2E 2E 2E 2E
term
inal
pos
ition
sci
rcui
tdi
agra
m
APG2011 B.indd 269 7/27/11 11:53 AM
1-800-ASK-4WEG
www.weg.net
TIMING RELAYS
Data is subject to change without notice.B-270
Controls Timing Relay - RTW Series
Function contactsSupply Terminals
Timing catalog NumberA1-A2Voltage (V)
2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h RTW-RE 02 - MbT
Function contactsSupply Terminals
Timing catalog NumberA1-A2
2NOC 24-240VAC/VDC (50/60Hz)
0.1 to 1 sec0.3 to 3 sec1 to 10 sec3 to 30 sec
10 to 100 sec 30 to 300 sec1 to 10 min
RTW RdI 02 - uoo1SRTW RdI 02 - uoo3SRTW RdI 02 - uo10SRTW RdI 02 - uo30SRTW RdI 02 - u100SRTW RdI 02 - u300SRTW RdI 02 - uo10M
Function contactsSupply Terminals controls
TerminalsTiming catalog NumberA1-A2 A2-b1
Voltage (V)
2NOC 24-240VAC/VDC (50/60Hz)
24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h RTW-Rd 02 - MbT
On-Delay
Off-Delay
Off-Delay without control voltage
Reference Table
APG2011 B.indd 270 8/2/11 10:52 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-271
Function contactssupply terminals
timing catalog numbera1-a2Voltage (V)
2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h rtW-rE 02 - MBt
Function contactssupply terminals
timing catalog numbera1-a2
2NOC 24-240VAC/VDC (50/60Hz)
0.1 to 1 sec0.3 to 3 sec1 to 10 sec3 to 30 sec
10 to 100 sec 30 to 300 sec1 to 10 min
rtW rdI 02 - uoo1srtW rdI 02 - uoo3srtW rdI 02 - uo10srtW rdI 02 - uo30srtW rdI 02 - u100srtW rdI 02 - u300srtW rdI 02 - uo10M
Function contactssupply terminals controls
terminalstiming catalog numbera1-a2 a2-B1
Voltage (V)
2NOC 24-240VAC/VDC (50/60Hz)
24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h rtW-rd 02 - MBt
Controls Timing Relay - RTW Series
Reference Table
Impulse - ON
Wye-Delta
Assymmetric Flasher - Pulse
Symmetric Flasher - Pulse/Pause
Function contactssupply terminals
timing catalog numbera1-a2
2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150h rtW-PE 02 - MBt
Function contactssupply terminals
timing catalog numbera1-a2
2NOC 24-240VAC/VDC(50/60Hz)
0.1 to 1 sec0.3 to 3 sec1to 10 sec3 to 30 sec
10 to 100 sec30 to 300 sec3 to 30 min
rtW-cI 02 - u001srtW-cI 02 - u003srtW-cI 02 - u020srtW-cI 02 - u030srtW-cI 02 - u100srtW-cI 02 - u300srtW-cI 02 - u030M
Function contactssupply terminals
timing catalog numbera1-a2
2NOC 24-240VAC/VDC(50/60Hz) 0.2 sec to 150 h rtW-cIl/cId 02 - MBt
contactssupply terminals
timing catalog numbera1-a2
2NOC 24-240VAC/VDC (50/60Hz) 0.1 sec to 10 min rtW Et 02 - Mat
APG2011 B.indd 271 7/27/11 11:53 AM
1-800-ASK-4WEG
www.weg.net
tIMInG rElaYs
Data is subject to change without notice.B-272
dIMEnsIons mm (in)
80 (3
.15)
22.5 (0.89)
80 (3
.15)
104
(4.1
0)
74.6
(2.9
4)
85.5 (3.35)
91.3
(3.6
0)
12.7 (0.50)
4.80 (1.19)
RTW – RE / PE / RD / RDI / CI / CIL / CID / ET
Controls Timing Relays - RTW Series
30024Vac 50/60Hz • 48Vac 50/60Hz
110-130Vac 50/60Hz • 220-240Vac 50/60Hz24Vdc (only RTW RD)
24Vdc (except RTW-RD)
24Vac 50/60Hz • 48Vac 50/60Hz110-130Vac 50/60Hz • 220-240Vac 50/60Hz
24Vdc 0.85...1.1 x Uc for Vac0.8...1.25 x Uc for Vdc
35 for Ue = 24Vdc65 for Ue = 110Vac75 for Ue = 130Vac55 for Ue = 220Vac60 for Ue = 240Vac
100
50±5±1100
31
0.450.350.20.1
A300R300
4
30 x 106
10 x 105
-5 a +60 (23...140)-40 a +85 (-40...125)
Frame IP20 / Terminals IP20
1 x (0.5 to 2.5)2 x (0.5 to 1.5)1 x (0.5 to 1.5)2 x (0.5 to 1.5)
2 x (20 to 16)
0.8 to 14.7 (7.1 to 12.3)M3
any position15/11
10 to 500/100.1(35)
V
Vac
Vdc
Vac
mA
ms
ms%%
ms(le)
A
A
ºC (F)ºC (F)
mm2
mm2
AWG
N.m (lb.in)
rtW
Inpu
tsti
me
adju
stou
tput
s
Rated Insulation Voltage (Ui) Supply Voltage (Ue) A1 – A2 A2 – A3
Comand (Uc) A2 – B1 (Only RTW RD)
Voltage limits
Consumption
Minimum Time for ResetMinimum ON Time (for RTW RD) Setting Accuracy (as % of the full scale value)Repeat AccuracyChangeover time y - ∆Output contacts capacity AC-15 on 230 Vdc DC-13 on 24Vdc DC-13 on 48Vdc DC-13 on 60Vdc DC-13 on 125Vdc DC-13 on 250Vdc
Acc. UL;CSA
Fuse (class gL/Gg)
Mechanical DurabilityElectrical DurabilityAmbient Temperature- Operation - StorageProtection Degree Connection Section (min. to max.)
- Cable without end sleeve
- Cable with end sleeve
- AWG-WireTightening TorqueTerminal ScreewMounting PositionShock ResistanceVibration Resistance
Weight
g/msHz/mmkg (oz)
Mec
hani
cal
Feat
ures
Acc. IEC 60947-5-1
operating cycles
operating cycles
Product
APG2011 B.indd 272 7/27/11 11:53 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-273
Connection Diagram
L1 L2 L3
A B N
Neutral Selection
16 18
15
L1 15 L2
16 18 L3
RPW FSF
A B N
Sensitivity Adjustment
The sensitivity adjustment (threshold) is made by
the DIAL located on the front of the relay.
It ranges from 70% to 90%, which defines the
balance for one phase related to the others.
LED Indication
Output energized
Protector energized
Protection Relay RPW is provided
with LED’s for status indication.
The RPW relay can be mounted directly on DIN rail 35mm or fixed
with screws using the accessory PLMP.
Assembly
rPW- FsFd66
Phase Sequence and Phase Loss
sElEctIon:
WEG Protection Relay
Voltage Selection
Available Voltages:220-240Vac 50/60Hz - D66440-480Vac 50/60Hz - D74
RPW FSF (without neutral selection) The Phase Sequence and Phase Loss Relay -
RPW FSF - is used to monitor three-phase networks against phase loss and incorrect
phase sequence.
Operation: If the phase sequence at the terminals L1-L2-L3 is correct and balanced
with values higher than the selected on the dial, the output relay picks up (close the
15-18 terminals) and the red LED turns ON. In case of an incorrect phase sequence
or a phase fails below the threshold value, the output relay remains in its rest position
(close the 15-16 terminals) and the red LED turns OFF.
RPW FSF (with Neutral selection) The Phase Sequence and Phase Loss Relay - RPW
FSF - is used to monitor three-phase networks and neutral against phase failure and
incorrect phase sequence.
Operation: In the same product, the neutral protection is enabled jumpering the terminals
A and B to monitor the neutral voltage (terminal N). The neutral must be connected to
the protection relay for proper operation.
Note: When one phase fails, connected loads (motor windings, lamps, transformers, coils, etc.) create a feedback voltage at the terminal of the failed phase due to the network coupling. Such phase failure is detected with the RPW FSF.
Controls Protection Relays - RPW Series
t
V
15-18
15 15
16 1616 1618 1818 18
15 15
15-16
LEDON
LEDON
LEDOFF
LEDOFF
L1-L2-L3 L1-L2-L3
Phase or neutral loss
L1-L2
Phaseinversion
L1-L2
Functional Diagram
APG2011 B.indd 273 7/27/11 11:53 AM
1-800-ASK-4WEG
www.weg.net
tIMInG rElaYs
Data is subject to change without notice.B-274
RPW-SF The Phase Sequence Relay - RPW-SF - is used to monitor three-phase networks against incorrect phase sequence.
Operation: If the phase sequence at the terminals L1-L2-L3 is correct, the output relay picks up (close the 15-18 terminals) and the red LED turns ON. In case of an incorrect phase sequence, the output relay remains in its rest position (close the 15-16 terminals) and the red LED is turns OFF.
rPW- sFd66
Phase SequenceWEG Protection Relay
LED Indication
Connection Diagram Functional Diagram
Output energized
Protector energized
Protection Relay RPW is provided
with LED’s for status indication.
L1 15 L2
16 18 L3
RPW SF
L1 L2 L3
16 18
15
The RPW relay can be mounted directly on DIN rail 35mm
or fixed with screws using the accessory PLMP.
Assembly
L1-L3-L2
t
Phase Inversion
LED OFF
LED ON
Voltage Selection
Available Voltages:220-240Vac 50/60Hz - D66440-480Vac 50/60Hz - D74
Controls Protection Relays - RPW Series
APG2011 B.indd 274 7/27/11 11:53 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-275
RPW FF (without neutral selection) The Phase Loss Relay - RPW FF - is used to monitor three-phase networks against phase failure.
Operation: Connected directly to the supply voltage to be monitored, and connecting the three phases with values above than the selected on the dial, the output relay is energized (close the 15-18 terminals) and turns on the red LED indicating that the system is properly working. In case the voltage falls below the threshold value the output relay is de-energized (close the 15-16 terminals) and the red LED is turns OFF.
RPW FF (with neutral selection)The Phase Loss Relay - RPW FF - is used to monitor three-phase networks and the neutral against phase failure.
Operation: In the same product, the neutral protection is enabled jumpering the terminals A and B to monitor the neutral voltage (terminal N). The neutral must be connected to the protection relay for proper operation.
rPW- FFd66
Phase Loss
sElEctIon:
WEG Protection Relay
Sensitivity AdjustmentThe sensitivity adjustment (threshold) is made
by the DIAL located on the front of the relay.
It ranges from 70% to 90%, which defines the
balance for one phase related to the others.
Connection Diagram
L1 L2 L3
A B N
Neutral Selection
16 18
15
Functional Diagram
L1 15 L2
16 18 L3
RPW FF
A B N
t
LED ON
LED OFF
LED ON
LED OFF
LED Indication
Output energized
Protector energized
Protect ion Relay RPW is
provided with LED’s for status
indication.
The RPW relay can be mounted directly on DIN rail 35mm or fixed with screws using the accessory PLMP.
Assembly
Voltage Selection
Available Voltages:220-240Vac 50/60Hz - D66440-480Vac 50/60Hz - D74
Note:Whenonephasefails,connectedloads(motorwindings,lamps,transformers,coils,etc.)createa
feedback voltage at the terminal of the failed phase due to the network coupling. Such phase failure is de-
tectedwithRPWFF.
Controls Protection Relays - RPW Series
APG2011 B.indd 275 7/27/11 11:54 AM
1-800-ASK-4WEG
www.weg.net
tIMInG rElaYs
Data is subject to change without notice.B-276
Connection Diagram
L1 L2 L3
16 18
15
Functional Diagram
L1 15 L2
16 18 L3
RPW SS
Sensititivy Adjustment
The sensitivity adjustment (threshold) is made by
the DIAL located on the front of the relay. It ranges
from -15% to -3% (for under voltage) and +3%
to +15% (for over voltage).
LED Indication
Output energized
Protector energized
Protection Relay RPW is
provided with LED’s for
status indication.
The RPW relay can be mounted directly on DIN rail 35mm or fixed with screws using the accessory PLMP.
Assembly
rPW- ssd25
Under and Over Voltage
WEG Protection Relay
Voltage Selection
Available Voltages:240Vac 50/60Hz – D25480Vac 50/60Hz – D39
Assymmetry
RPW-SS The Under and Over-voltage Relay RPW SS is used to monitor maximum and minimum
variations that three-phase power supplies are able to work. The RPW SS also protects the circuit
against phase unbalance (asymmetry) of 20% or higher between phases.
Operation: Connecting the phases L1-L2-L3 with phase amplitudes within the selected values
and assymmetry between them below the threshold (20%), the output relay picks up (close
the 15-18 terminals) and the red LED turns ON. In case of a phase loss, assymmetry between
phases higher than 20% or under and over-voltage, the output relay remains in its rest position
(close the 15-16 terminals) and the red LED is turns OFF.
Controls Protection Relays - RPW Series
APG2011 B.indd 276 7/27/11 11:54 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-277
rPW-PtcE05
Thermistor Relay
sElEctIon:
WEG Protection Relay
Voltage Selection
Available Voltages:24-240Vac 50/60Hz / Vdc - E05
RPW-PTC The Thermistor Relay RPW PTC is used to measure the motor temperature by using
PTC sensor inside of the motor. When the motor temperature rises above the PTC sensor class,
the output relay is de-energized avoiding damages to the motor.
Operation: Connected directly to the supply voltage and in series to the PTC sensor (maximum of
3 sensors), the output relay is automatically energized (close the 15-18 terminals) and turns on
the red LED indicating that the temperature is within acceptable values. If an over temperature
occurs, the probe resistance is rapidly increased and the output relay is de-energized (close the
15-16 terminals) and the red LED turns OFF, remaining on this situation until the temperature
decreases at a normal value. The RTW PTC is able to evaluate if the PTC sensor has a fault (not
caused by an over temperature) or if is not connected (open circuit). In such situations, the green
LED will start flashing.
Controls Protection Relays - RPW Series
a1 15
16 18 A2
RPW PTC
S1 S2
Functional Diagram
Normal Operation
Elevated Temperature
Energized
Not energized
PTC sensor failure
On
Off
On
Off
Flashing
Relay Light Indications
A1 - A2 Voltage Supply
24...240 VCA / VDC
S1 - S2 PTC sensor input
15 - 16 - 18 Output
Terminals
TheRPWRelayscanbeindividuallymountedonDIN35mmrailorwithscrewsusingthePLMPaccessory.
LEDONA1 - A2 / A3 - A2
Output15 - 18
Power Supply
Red LED
Green LED
500
1000150025003600R [Ω]
LEDOFF
LED LEDFlashing
151515 15
161616 16181818 18
Flashing
Connection Diagram
APG2011 B.indd 277 7/27/11 11:54 AM
1-800-ASK-4WEG
www.weg.net
Data is subject to change without notice.B-278
tIMInG rElaYs
Inpu
tsOu
tput
sM
echa
nica
l Fea
ture
s
DIMENSIONS mm (in)
80 (3
.15)
22.5 (0.89)
80 (3
.15)
104
(4.1
0)
74.6
(2.9
4)
85.5 (3.35)
91.3
(3.6
0)
12.7 (0.50)
4.80 (1.19)
RPW – FF / SF / FSF / SS / PTC
Product
Controls Protection Relays - RPW Series
220 or 480
rPW-FF rPW-sF rPW-FsF rPW-ss rPW-Ptc
APG2011 B.indd 278 7/27/11 11:54 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-279
Controls LevelRelays-RNWSeriesWEG Level Relays are electronic control devices that enable the monitoring and automatic adjustment of levels in electric currentliquidconductors.Widelyusedingeneralreservoirautomation,theRNWrelayscanalsobeutilizedinseveralapplications such as prevention of dry pump operation, monitoring against filling tank overflow, activation of solenoids or alarms/lighting.The operating principle is based on measuring the electrical resistance of the reservoir liquid through electrodes that work asliquidpresence/absencesensors.Tooptimizetheirperformance,therelayhasasensitivityDIALenablingtheelectroniccircuit to be adjusted to the liquid resistance.Availablein2functions,RNW-ENfillingandRNW-ESdraining,thelevelrelayoffersdigitalelectronicsthatprovidehighprecision, repeatability and noise resistance. The supply system is isolated from the electronic circuit therefore ensuring greaterusersafety.Designedinaccordancewithinternationalstandards,theRNWoffersasafeandcompactsolution,in22,5mmwidehousingforassemblyon35mmDINrail,with1outputreversablecontact(Cform)andvoltagesupplyrangeof100-240VAC/VDC.
Available in the following functions:g RNW EN -> Fillingg RNW ES -> Draining
Selection
Functional DiagramTheelectrodesarefixedinthereservoiraccordingtodesiredcontrollevels,minimumormaximum.Thereferenceelectrode(C)mustbepositionedinthelowerpart,belowthemaximumandminimumlevel etectrodes. When the system is energized, an alternating current is applied to the reference electrode and,once the liquid comes into contact with the level electrodes, a path is established for the circulation of electrical current between the electrodes. An electronic current compares the current and switches the relay outputcontactsaccordingtothechosenmodel(RNWESorRNWEN).Theelectrodesareavailablein2versions,shaft(EHW)orpendulum (EPW), the difference between them is the assembly type.TheRNWisavailableintwodistinctfunctions,drainingandfilling. Note: The EHW shaft sensors can be fixed both horizontally and vertically
MaxElec
Min Elec
C Elect.
Pendulum Type Shaft Type
MaxElec
MinElec
C Elect
RNW - EN - E 09
WEG Level Relay
Available Voltage Range E09=100-240 VAC /VDCType: EN - Filling
ES - Draining
Standards
Approval
IEC / EN 60947-1IEC / EN 60947-5-1
APG2011 B.indd 279 7/27/11 11:54 AM
1-800-ASK-4WEG
www.weg.net
tIMInG rElaYs
Data is subject to change without notice.B-280
Controls LevelRelays-RNWSeries
Applications
Sensitivity Adjustment
Liquid resistance can vary according to the liquid in question and the position of the electrodes. To adapt the electronic circuit to the liquid used, sensitivity must be adjusted through the DIAL located in the front part of the RNW, which has a graded scale without values. To perform the sensitivity adjustment, all electrodes must be submersed into the reservoir liquid and the DIAL positioned at its limit anti-clockwise (less resistance). With the relay energized, the DIAL must be turned clockwise (greater resistance) until the relay output switches its contacts (the red LED must change status). To confirm the adjustment, the reference electrode C must be disconnected and then quickly reconnected, the relay must return to its previous status. If this not happen, a new adjustment must be performed. By doing this, the RNW will be adjusted to the ideal sensitivity point.
Relay Light IndicationsThe RNW Level Relay is equipped with indicator LEDs as shown on the right:
Characteristics
Energized OutputEnergized Relay
APG2011 B.indd 280 7/27/11 11:55 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-281
Controls LevelRelays-RNWSeries
Controls 2 levels using 3 electrodes: the reference electrode (C), the maximum level electrode (Max) and the minimum level electrode (Min). Once powered, the RNW ES start monitoring the liquid level in the reservoir. With the liquid being in contact with the Max level electrode, the relay will energize (terminals 15-18 closed), causing the reservoir liquid level begin to drop. Once the Min level electrode is uncovered by the liquid the relay will energize (terminals 15-18 open) and will remain energized until the liquid enters into contact again with the Max level electrode, restarting the process. If there is a supply failure, the RNW ES will restart its initial logic.
RNWES(Draining)
Controls 2 levels using 3 electrodes: the reference electrode (C), the maximum level electrode (Max) and the minimum level electrode (Min). Once powered, the RNW EN start monitoring the liquid level in the reservoir. With the electrode being uncovered at minimum level Min, the output relay will energize (terminals 15-18 closed) causing the liquid level to rise. When the reservoir liquid covers the Max level electrode, the output realy de-energize (terminals 15-18 open) and remains de-energized until the Min level electrode is discovered again. If there is a supply failure, the RNW EN will restart its initial logic.
RNWEN(Filling)
Connection Diagrams Functional Diagram
A1 15
16 18 A2
RNW EN
Max Min C
Level
15 15 15
16 16 1618 18 18
LEDOFF
LEDOFF
LEDOFF
15 15 15
16 16 1618 18 18
LEDON
LEDON
LEDON
t
15 - 18
C
Min
Max
Power Supply A1-A2
Max Min
15
1816
C
Connection Diagrams
A1 15
16 18 A2
RNW ES
Max Min C
Functional diagram
Level
15 15
16 1618 18
LEDOFF
LEDOFF
15 15 15
16 16 1618 18 18
LEDON
LEDON
LEDON
t
15 - 18
C
Min
Max
Power Supply A1-A2
Max Min
15
1816
C
APG2011 B.indd 281 7/27/11 11:55 AM
1-800-ASK-4WEG
www.weg.net
tIMInG rElaYs
Data is subject to change without notice.B-282
Controls LevelRelays-RNWSeries
Teflon coated stainless steel shaft11/4“chromehexscrewLength: 300 mmnote: other lengths upon requestMaximum sensor cable 100m (110yd)
Dimensions (mm)
Adaptor for screw fixing - PLMP
Shaft electrode - EHW
Pendulum electrode - EPW
Body in natural black polypropylene Stainless steel sensor shaft1x10mm2gaugeflexibleconnectioncableCable length: 1000 mmnote: Maximum sensor cable 100m (110yd)
Accessories
Dimensions (mm)
Dimensions (mm)
APG2011 B.indd 282 7/27/11 11:55 AM
WEG Automation - Products and Solutions
www.weg.net
tIM
InG
rEla
Ys
Data is subject to change without notice. B-283
Controls LevelRelays-RNWSeries
RNWTechnicalData
Inpu
tsOu
tput
sCh
arac
teris
tics
Elec
trode
s
Product rnW Es / rnW EnSupply (Un) A1 VAC 100-240 50 /60 Hz
A2 VDC 100-240
Isolated Rated Voltage (Ui) V 300
Operating Limits 0.85 to 1.1 x Ue
Maximum Consumption VA / W 2 / 1
Contacts 15 - 16 / 18 1 SPDT
Output Contact Capacity (Ie)
A
5 (resistive load)
AC-15 in 230 Vca 3
DC-13 in 24 VDC 1
DC-13 in 48 VDC 0.45
DC-13 in 60 VDC 0.35
DC-13 in 125 VDC 0.2
DC-13 in 250 VDC 0.1
A300 : AC-15
R300 : DC-13
Rated thermal current (lth) A10 (for AC)
2.5 (for DC)
Fuse (class gL / gG) A 4
Mechanical Lifespan operations 30 x 106
Temperature
OperationºC (F)
-5 to +60 (23...140)
Storage -40 to +85 (-40...185)
Degree of Protection IP20
Terminal Capacity Rigid or fexible Cable mm21 x (0.5 to 2.5)
2 x (0.5 to 1.5)
Cable with TerminalRigid or fexible Cable/Terminal mm2
1 x (0.5 to 2.5)
2 x (0.5 to 1.5)
AWG Solid conductor AWG 2 x (30 to 14)
Tightening torque N.m 0.8 to 1.2
lb.in 7 to 10.6
Terminal Screws M3
Assembly Position Any
Resistance to Impacts g / ms 15 / 11
Resistance to Vibration Hz / mm 10 to 500 / 10
Weight kg 0.08
Pollution 2
Over voltage category II
Sensitivity Adjustment kΩ 0 to 100
Electrode Voltage VCA 7
Electrode Current mA 0.05
Maximum length of sensor cable m 100 (Maximum cable capacitance 2.2nF)
Detector operating temperature - ShaftºC (F)
0 to + 260 (32...500)
- Pendulum 0 to + 60 (32...140)
Allowable detector pressure - Shaftkgf / cm2
3
- Pendulum -
Detector Weight - Shaftkg
0.230
- Pendulum 0.012
APG2011 B.indd 283 7/27/11 11:55 AM
1-800-ASK-4WEG
www.weg.net
TIMING RELAYS
Data is subject to change without notice.B-284
Controls Level Relays-RNW Series
Dimensions
Relay Assembly
Electronic Relay Technical Data
DIMENSIONS mm (in)
80 (3
.15)
22.5 (0.89)
80 (3
.15)
104
(4.1
0)
74.6
(2.9
4)
85.5 (3.35)
91.3
(3.6
0)
12.7 (0.50)
4.80 (1.19)
APG2011 B.indd 284 7/27/11 12:10 PM