7ixf21_2567.pdf - IN.gov
-
Upload
khangminh22 -
Category
Documents
-
view
0 -
download
0
Transcript of 7ixf21_2567.pdf - IN.gov
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
K 0000
Bldg. 01
A Life Safety Code Recertification
Survey was conducted by the Indiana
State Department of Health in accordance
with 42 CFR 416.44(b).
Survey Date: 05/15/17
Facility Number: 012823
Provider Number: 15C0001183
AIM Number: NA
At this Life Safety Code survey, Multi
Specialty Surgery Center was found not
in compliance with Requirements for
Participation in Medicare/Medicaid, 42
CFR Subpart 416.44(b), Life Safety from
Fire and the 2012 edition of the National
Fire Protection Association (NFPA) 101,
Life Safety Code (LSC), Chapter 21,
Existing Ambulatory Health Care
Occupancies.
The facility, located on the first floor of a
two story building with a partial
basement was determined to be of Type II
(000) construction and was fully
sprinklered. The facility has a fire alarm
system with smoke detection in the
corridors.
Quality Review completed on 05/19/17 -
K 0000
FORM CMS-2567(02-99) Previous Versions Obsolete
Any defiencystatement ending with an asterisk (*) denotes a deficency which the institution may be excused from correcting providing it is determined that
other safegaurds provide sufficient protection to the patients. (see instructions.) Except for nursing homes, the findings stated above are disclosable 90 days
following the date of survey whether or not a plan of correction is provided. For nursing homes, the above findings and plans of correction are disclosable 14
days following the date these documents are made available to the facility. If deficiencies are cited, an approved plan of correction is requisite to
continued program participation.
LABORATORY DIRECTOR'S OR PROVIDER/SUPPLIER REPRESENTATIVE'S SIGNATURE
_____________________________________________________________________________________________________Event ID: 7IXF21 Facility ID: 012823
TITLE
If continuation sheet Page 1 of 45
(X6) DATE
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
DA
NFPA 101
Multiple Occupancies
Multiple Occupancies - Sections of
Ambulatory Health Care Facilities
Multiple occupancies shall be in accordance
with 6.1.14.
Sections of ambulatory health care facilities
shall be permitted to be classified as other
occupancies, provided they meet both of the
following:
* The occupancy is not intended to serve
ambulatory health care occupants for
treatment or customary access.
* They are separated from the ambulatory
health care occupancy by a 1 hour fire
resistance rating.
Ambulatory health care facilities shall be
separated from other tenants and
occupancies and shall meet all of the
following:
* Walls have not less than 1 hour fire
resistance rating and extend from floor slab
to roof slab.
* Doors are constructed of not less than
1-3/4 inches thick, solid-bonded wood core
or equivalent and is equipped with positive
latches.
* Doors are self-closing and are kept in the
closed position, except when in use.
* Windows in the barriers are of fixed fire
window assemblies per 8.3.
Per regulation, ASCs are classified as
Ambulatory Health Care Occupancies,
regardless of the number of patients served.
20.1.3.2, 21.1.3.3, 20.3.7.1, 21.3.7.1,42 CFR
416.44
K 0131
Bldg. 01
Based on observation and interview, the
facility failed to ensure 1 of 1 fire barriers
K 0131 1. All fire barriers in the facility
will be inspected by a contractor.
The contractor will ensure that
06/26/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 2 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
that separated other occupancies were
protected to maintain the one hour fire
resistance rating of the fire barrier. NFPA
101 2012 edition 8.3.5.6.1 states
membrane penetrations for cables cable
trays conduits, pipes, tubes, combustion
vents and exhaust vents, wires, and
similar items to accommodate electrical,
mechanical, plumbing, and
communications systems that pass
through a membrane of a wall, floor, or
floor/ceiling assembly constructed as a
fire barrier shall be protected by a
firestop system or device. 8.3.5.6.2 The
firestop system or device shall be tested
in accordance with ASTM E 814,
Standard Test Method for Fire Test of
Through Penetration Fire stops, or
ANSI/UL 1479, Standard for Fire Tests
of Through-Penetration Firestops. This
deficient practice could affect all
occupants.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, all
penetrations of drywall and all gaps in
between drywall sections and the deck of
the flooring above along the north and
west wall of the tenant separation fire
barrier wall in the lobby above the
suspended ceiling by the vending
any gaps or penetrations are
sealed, in an approved manner,
to maintain their rating.
2. The clinical manager
will ensure that all future work is
monitored to ensure that an
approved firestop is used on any
penetrations in fire barriers.
Center policy LSC 8.00 Interim
Life Safety Measures will be
followed to ensure the integrity of
the fire barriers are maintained.
3. The clinical manager is
responsible to ensure that this
deficiency has been corrected
and that on-going compliance is
maintained.
The center's floor plan with fire
barriers is attached as exhibit 2.
Policy LSC 8.00 Interim Life
Safety Measures is attached as
exhibit 4. Statement of work from
contracted service provide is
exhibit 15.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 3 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
machines were filled with foam. Based
on interview at the time of the
observations, the Clinical Manager stated
she was unaware of the fire resistance
rating of the foam used to fill the
penetrations and gaps and acknowledged
the use of foam did not maintain the
minimum fire resistance rating for the
tenant separation fire wall.
NFPA 101
Illumination of Means of Egress
Illumination of Means of Egress
Illumination of means of egress, including
exit discharge, is arranged in accordance
with 7.8 and shall be either continuously in
operation or capable of automatic operation
without manual intervention.
20.2.8, 21.2.8, 7.8
K 0281
Bldg. 01
Based on observation and interview, the
facility failed to ensure continuity of
egress lighting for 1 of 4 exits. For the
purposes of this requirement, exit
discharge shall include only designated
stairs, aisles, corridors, ramps, escalators,
walkways and exit passageways leading
to a public way. This deficient practice
could affect four patients, staff and
visitors if needing to exit the facility from
the south exit door.
K 0281 1. Egress lighting will be added
to the south exit discharge by a
contractor.
2. Egress lighting has been
confirmed at all exits. Visual
confirmation that egress lighting
is visible and functioning has
been added to the facilities
monthly PM checklist.
3. The clinical manager is
responsible to ensure that the
facility performs environmental
rounding on a regular basis.
The center's monthly PM
06/07/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 4 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Finding include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, the
south exit discharge was not provided
with egress lighting. Based on interview
at the time of the observations, the
Clinical Manager acknowledged the
south exit discharge was not provided
with egress lighting.
Checklist is attached as exhibit 1.
Statement of work regarding the
addition of egress lighting is
exhibit 17. Picture of egress
lighting attached as image 2.
NFPA 101
Emergency Lighting
Emergency Lighting
Emergency lighting of at least 1-1/2 hour
duration is provided automatically in
accordance with 7.9.
20.2.9.1, 21.2.9.1, 7.9
K 0291
Bldg. 01
Based on record review, observation and
interview; the facility failed to document
monthly and annual testing for 4 of 4
battery backup lights in accordance with
LSC 7.9. Section 7.9.3.1.1 states testing
of emergency lighting systems shall be
permitted to be conducted as follows:
(1) Functional testing shall be conducted
monthly, with a minimum of 3 weeks and
a maximum of 5 weeks between tests, for
not less than 30 seconds, except as
otherwise permitted by 7.9.3.1.1(2).
(2) The test interval shall be permitted to
be extended beyond 30 days with the
approval of the authority having
K 0291 1. 30 second and 90 minute
testing will be performed on the
center's battery powered
emergency lights. The center's
monthly PM checklist has been
expanded to include the location
of each battery powered light for
the required monthly thirty second
test. The center's equipment and
PM schedule includes
documentation for the annual
ninety minute functional testing.
2. Monthly and testing for
the center's battery powered
lights has been added to
the center's monthly PM
checklist. Annual testing has
been added to the center's
equipment list and PM schedule.
06/09/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 5 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
jurisdiction.
(3) Functional testing shall be conducted
annually for a minimum of 1 1/2 hours if
the emergency lighting system is battery
powered.
(4) The emergency lighting equipment
shall be fully operational for the tests
required by 7.9.3.1.1(1) and (3).
(5) Written records of visual inspections
and tests shall be kept by the owner for
inspection by the authority having
jurisdiction.
This deficient practice could affect all
patients, staff and visitors in the facility.
Findings include:
Based on review of "Preventive
Maintenance - Task: Battery-Powered
Emergency Light Test" & "Preventive
Maintenance - Task: Generator Powered
Emergency Light Test" documentation
dated 04/18/17 and 05/02/17 with the
Clinical Manager during record review
from 9:50 a.m. to 1:30 p.m. on 05/15/17,
monthly testing documentation for each
battery powered light in the facility was
not itemized by location. The
aforementioned documentation stated
"check operation of all lamps" and "push
test button or turn off power for 30
seconds." In addition, based on
telephone interview with the Building
Maintenance Manager at the time of
3. The clinical manager is
responsible to ensure that
environmental rounding and
testing occurs on a routine basis.
The center's monthly PM
Checklist is attached as exhibit 1.
The center's equipment list and
PM schedule has been added as
exhibit 3.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 6 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
record review, it could not be assured the
aforementioned documentation pertained
to monthly battery operated light testing.
The Building Maintenance Manager
stated the aforementioned documentation
pertained to battery testing in facility exit
signs. Annual 90 minute functional
testing documentation for each battery
powered emergency light in the facility
within the most recent twelve month
period was also not available for review.
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17,
battery powered emergency lights were
located in each of three operating rooms
(OR) where general anesthesia is utilized
and one battery powered emergency light
system was located on the exit sign at the
north exit vestibule for biohazard waste
pickup. The north exit battery light
system also illuminated a light for the
generator location which functioned
when its test button was pushed. The
battery powered light in OR1 illuminated
when its test button was pushed but the
lights in OR2 and OR3 could not be
tested because access was restricted due
to surgeries in the rooms.
NFPA 101 K 0341
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 7 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Fire Alarm System - Installation
Fire Alarm - Installation
A fire alarm system is installed with systems
and components approved for the purpose
in accordance with NFPA 70, National
Electric Code, and NFPA 72, National Fire
Alarm Code to provide effective warning of
fire in any part of the building. In areas not
continuously occupied, detection is installed
at each fire alarm control unit. In new
occupancy, detection is also installed at
notification appliance circuit power
extenders, and supervising station
transmitting equipment. Fire alarm system
wiring or other transmission paths are
monitored for integrity.
20.3.4.2.1, 21.3.4.1, 9.6
Bldg. 01
1. Based on observation and interview,
the facility failed to ensure 1 of 1 fire
alarm control units, located in an area
that was not continuously occupied, was
provided with automatic smoke detection
to ensure notification of a fire at that
location before it is incapacitated by fire.
LSC 9.6.1.3 requires a fire alarm system
to be installed, tested, and maintained in
accordance with NFPA 70, National
Electrical Code and NFPA 72, National
Fire Alarm and Signaling Code. NFPA
72, 2010 Edition, Section 10.15 requires
in areas that are not continuously
occupied, automatic smoke detection
shall be provided at the location of each
fire alarm control unit(s), notification
appliance circuit power extenders, and
supervising station transmitting
equipment to provide notification of a
K 0341 1. A contractor has been hired to
add automatic smoke detection to
the main alarm control unit
located in the main entrance
vestibule. A remote annunciator
will also been added to the
surgery center suite.
2. The fire system will be tested
at regular intervals by the center's
contracted service provider.
Testing will be verified by the
center's safety officer utilizing the
Equipment list and PM schedule
checklist.
3. The clinical manager is
responsible to ensure that the
center maintains appropriate
documentation and the
preventative maintenance is
performed on schedule.
The center's equipment list and
PM schedule has been added as
exhibit 3. A work order for the
addition of automatic smoke
detection to the main alarm
06/26/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 8 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
fire in that location. Exception: where
ambient conditions prohibit installation
of automatic smoke detection, automatic
heat detection shall be permitted.
A.10.15 permits the use of a heat detector
if ambient conditions are not suitable for
smoke detection. It is important to also
evaluate whether the area is suitable for
the control unit. This deficient practice
could affect all patients, staff and visitors
in the facility.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17,
automatic smoke detection was not
provided at the main fire alarm control
unit located in the main entrance
vestibule for the facility. A fire alarm
system heat detector was located in the
vestibule but a reason or rationale for the
omission of automatic smoke detection at
the main fire alarm control unit location
was not known. Based on interview at
the time of the observation, the Clinical
Manager acknowledged automatic smoke
detection was not provided at the main
fire alarm control unit location.
2. Based on observation and interview,
the facility failed to ensure 1 of 1 fire
alarm control units, located in an area
control unit and remote
annunciator is attached as exhibit
19.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 9 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
that was not continuously occupied, was
provided with annunciation readily
accessible to responding personnel to
facilitate an efficient response to the fire
situation. LSC 9.6.1.3 requires a fire
alarm system to be installed, tested, and
maintained in accordance with NFPA 70,
National Electrical Code and NFPA 72,
National Fire Alarm and Signaling Code.
NFPA 72, 2010 Edition, Section
10.16.3.1 states all required annunciation
means shall be readily accessible to
responding personnel. Section 10.16.3.2
states all required annunciation means
shall be located as required by the
authority having jurisdiction to facilitate
an efficient response to the fire situation.
Section A.10.16.3 states the primary
purpose of fire alarm system
annunciation is to enable responding
personnel to identify the location of a fire
quickly and accurately and to indicate the
status of emergency equipment or fire
safety functions that might affect the
safety of occupants in a fire situation.
Section 10.12.5 states the trouble
signal(s) shall be located in an area where
it is likely to be heard. This deficient
practice could affect all patients, staff and
visitors in the facility.
Findings include:
Based on observations with the Clinical
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 10 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, the
main fire alarm control unit was located
in the main entrance vestibule for the
building. A remote annunciator was not
located within the surgery center suite.
Based on interview at the time of the
observations, the Clinical Manager
acknowledged a remote annunciator was
not located within the surgery center
suite.
NFPA 101
Fire Alarm System - Testing and
Maintenance
Fire Alarm Systems - Testing and
Maintenance
A fire alarm system is tested and maintained
in accordance with an approved program
complying with the requirements of NFPA
70, National Electric Code, and NFPA 72,
National Fire Alarm and Signaling Code.
Records of system acceptance,
maintenance and testing are readily
available.
9.6.1.3, 9.6.1.5
K 0345
Bldg. 01
Based on observation and interview, the K 0345 1. Access to the electrical panel 06/07/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 11 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
facility failed to ensure 1 of 1 fire alarm
systems was maintained in accordance
with the applicable requirements of
NFPA 72, National Fire Alarm Code.
NFPA 72, 2010 Edition, Section 10.5.5.1
states connections to the light and power
service shall be on a dedicated branch
circuit(s). Circuit disconnecting means
shall have a red marking, shall be
accessible only to authorized personnel,
and shall be identified as FIRE ALARM
CIRCUIT. The location of the circuit
disconnecting means shall be
permanently identified at the fire alarm
control unit. Section 10.5.5.4 states an
overcurrent protective device of suitable
current carrying capacity and capable of
interrupting the maximum short circuit
current to which it may be subject shall
be provided in each ungrounded
conductor. The dedicated branch
circuit(s) and connections shall be
protected against physical damage. This
deficient practice could affect all patients,
staff and visitors.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17,
access to the fire alarm system breaker
located in the electrical panel in the first
floor electrical room by the elevator
containing the fire alarm circuit
will be restricted to authorized
personnel and locked at all
times. Building management has
added a lock to the electrical
room and signage indicating
authorized personnel only.
2. The electrical panel has been
added to the facilities
environmental rounding checklist
to ensure it is secured from
unauthorized access.
3. The clinical manager is
responsible to ensure that
environmental rounding occurs on
a routine basis.
The center's monthly PM
Checklist is attached as exhibit 1.
A picture of the door lock and
signage is included as image 1.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 12 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
machine room was not restricted to
authorized personnel. The corridor entry
door to the room, the electrical panel
containing the breaker and the breaker
were each not locked. Based on
interview at the time of the observations,
the Clinical Manager acknowledged
access to the fire alarm system breaker
was not restricted to authorized
personnel.
NFPA 101
Fire Alarm System - Out of Service
Fire Alarm - Out of Service
Fire alarms that are out of service for 4
hours in a 24 hour period, the authority
having jurisdiction shall be notified, and the
building shall be evacuated or an approved
fire watch shall be provided for all parties left
unprotected by the shutdown until the fire
alarm system has been returned to service.
9.6.1.6
K 0346
Bldg. 01
Based on record review and interview,
the facility failed to provide a complete
written plan containing procedures to be
followed in the event the fire alarm
system has to be placed out of service for
4 hours or more in a 24 hour period. This
deficient practice could affect all patients,
staff, and visitors.
Findings include:
Based on review of "Fire Watch -
Incident Action Plan" documentation
K 0346 1. The center's policy for interim
life safety measures (LSC 8.00)
includes detailed instructions for
providing notice to the local fire
department and the Indiana State
Department of Health whenever
the fire alarm or automatic
sprinkler system is out of service
for more than 4 hours in a 24
hour period. The policy includes
a requirement for notification to
the Indiana State Departement of
Health if either system is out of
service for 4 hours or more in a
24 hour period.
2. The clinical manager has been
06/09/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 13 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
with the Clinical Manager during record
review from 9:50 a.m. to 1:30 p.m. on
05/15/17, the facility's written policy in
the event the fire alarm system is out of
service for four hours or more in a twenty
four hour period did not include
notification of the Indiana State
Department of Health (ISDH) which is an
authority having jurisdiction. Based on
interview at the time of record review,
the Clinical Manager stated additional
written fire watch policy documentation
was not available for review and
acknowledged the facility's written policy
in the event the fire alarm system is out
of service for four hours or more in a
twenty four hour period did not include
notification of ISDH.
provided an in-service on the
center policy for interim life safety
measures. The clinical manager
has also performed an inservice
for the center's staff on the policy.
3. The administrator is
responsible to ensure that all staff
are knowledgeable about the
center's policy regarding interim
life safety measures.
Policy LSC 8.00 Interim Life
Safety Measures is attached as
exhibit 4.
NFPA 101
Sprinkler System - Installation
Sprinkler System - Installation
Sprinkler systems (if installed) are installed
per NFPA 13.
Where more than two sprinklers are
installed in a single area for protection,
waterflow devices shall be provided to sound
the building fire alarm system or to notify a
constantly attended location such as a PBX,
security office, or emergency room.
20.3.5.1, 20.3.5.2, 21.3.5.1, 21.3.5.2,
9.7.1.2, 9.7, NFPA 13
K 0351
Bldg. 01
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 14 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Based on observation and interview, the
facility failed to maintain 2 of over 50
automatic sprinklers in accordance with
NFPA 13, Standard for the Installation of
Sprinkler Systems. NFPA 13, 2010
edition, Section 6.2.7.1 states plates,
escutcheons, or other devices used to
cover the annular space around a
sprinkler shall be metallic, or shall be
listed for use around a sprinkler.
Escutcheons used with recessed,
flush-type, or concealed sprinklers shall
be part of a listed sprinkler assembly.
Cover plates used with concealed
sprinklers shall be part of the listed
sprinkler assembly. This deficient
practice could affect two staff.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, two
recessed sprinkler locations in the
overflow supply room were missing their
cover plates. Based on interview at the
time of the observations, the Clinical
Manager acknowledged the
aforementioned recessed sprinkler
locations were missing their cover plates.
K 0351 1. Cover plates will be added to
the two sprinkler heads in the
overflow supply room. The rest
of the center has been toured to
ensure that all sprinkler heads are
in place.
2. The center's Monthly
PM checklist has been updated to
include a visual verification of
sprinkler heads throughout the
premise.
3. The clinical manager is
responsible to ensure that
environmental rounding occurs on
a regular basis.
The center's monthly PM
Checklist is attached as exhibit
1. Statement of work for adding
the cover plates is attached as
exhibit 16.
06/07/2017 12:00:00AM
NFPA 101 K 0353
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 15 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Sprinkler System - Maintenance and Testing
Sprinkler System - Maintenance and Testing
Automatic sprinkler and standpipe systems
are inspected, tested, and maintained in
accordance with NFPA 25, Standard for the
Inspection, Testing, and Maintaining of
Water-based Fire Protection Systems.
Records of system design, maintenance,
inspection and testing are maintained in a
secure location and readily available.
a) Date sprinkler system last checked
_____________________
b) Who provided system test
____________________________
c) Water system supply source
__________________________
Provide in REMARKS information on
coverage for any non-required or partial
automatic sprinkler system.
9.7.5, 9.7.7, 9.7.8, and NFPA 25
Bldg. 01
1. Based on record review, observation
and interview; the facility failed to ensure
2 of 2 private fire hydrants was
continuously maintained in reliable
operating condition and inspected and
tested periodically. NFPA 25, 2011
Edition, the Standard for the Inspection,
Testing, and Maintenance of
Water-Based Fire Protection Systems,
Table 7.1.1.2 requires wet and dry barrel
hydrants to be inspected annually and
after each operation. This deficient
practice affects all patients, staff and
visitors.
Findings include:
Based on review of Tyco
K 0353 1. The center's contracted fire
system service provider will
complete the following:
a.) Annual flow testing
for the single private fire hydrant
on the premises. The testing
documentation will include the
location and flow test results
for the single private hydrant on
the premises. Note there are two
private hydrants listed in the
inspection report.
b.) Quarterly sprinkler
system testing and waterflow
alarm testing.
c.) Verification of the number
and type of spare sprinkler heads
available in the center.
Building management and the
center's safety officer are
responsible to ensure that gauges
on the wet pipe sprinkler system
06/29/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 16 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
SimplexGrinnell "Report of Inspection"
documentation dated 05/07/16 with the
Clinical Manager during record review
from 9:50 a.m. to 1:30 p.m. on 05/15/17,
facility fire hydrants were stated as being
flow tested but documentation of the
location of each fire hydrant and the
results of the flow tests was not available
for review. Based on observations with
the Clinical Manager during a tour of the
facility from 1:30 p.m. to 3:00 p.m. on
05/15/17, the facility had two private fire
hydrants located at the northeast and
northwest side of the building. Based on
interview at the time of record review
and of the observations, the Clinical
Manager acknowledged documentation
of the location of each fire hydrant and
the results of the flow tests was not
available for review.
2. Based on record review, observation
and interview; the facility failed to
provide written documentation or other
evidence the sprinkler system
components had been inspected and
tested for 3 of 4 quarters. LSC 4.6.12.1
requires any device, equipment or system
required for compliance with this Code
be maintained in accordance with
applicable NFPA requirements.
Sprinkler systems shall be properly
maintained in accordance with NFPA 25,
Standard for the Inspection, Testing, and
are inspected monthly and the the
pressure is recorded. Building
management and the center's
safety officer are responsible to
ensure that sprinkler pipe is not
used to support any non system
components.
2. The center's equipment list
and preventative maintenance sc
hedule checklist includes a
verification of Fire Hydrant
testing, Wet sprinkler gauge
testing, sprinkler system
testing and a spare sprinkler head
inspection.
3. The clinical manager is
responsible to ensure that
documentation of all required
testing is onsite and available
upon request. The clinical
manager is responsible to ensure
that the center's equipment list
and preventative maintenance
checklist is updated monthly.
The center's monthly equipment
list and preventative maintenance
schedule is attached as exhibit 3.
The center's monthly PM
checklist is attached as exhibit 1.
Results of fire system testing is
attached as exhibit 22.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 17 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Maintenance of Water-Based Fire
Protection Systems. NFPA 25, 4.3.1
requires records shall be made for all
inspections, tests, and maintenance of the
system components and shall be made
available to the authority having
jurisdiction upon request. 4.3.2 requires
that records shall indicate the procedure
performed (e.g., inspection, test, or
maintenance), the organization that
performed the work, the results, and the
date. NFPA 25, 5.2.5 requires that
waterflow alarm devices shall be
inspected quarterly to verify they are free
of physical damage. NFPA 25, 5.3.3.1
requires the mechanical waterflow alarm
devices including, but not limited to,
water motor gongs, shall be tested
quarterly. 5.3.3.2 requires vane-type and
pressure switch-type waterflow alarm
devices shall be tested semiannually.
This deficient practice could affect all
patients, staff, and visitors in the facility.
Findings include:
Based on review of Tyco
SimplexGrinnell "Report of Inspection"
documentation dated 05/07/16 with the
Clinical Manager during record review
from 9:50 a.m. to 1:30 p.m. on 05/15/17,
documentation of quarterly sprinkler
system inspection for the third quarter
(July, August, September) and fourth
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 18 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
quarter (October, November, December)
2016 was not available for review. In
addition, documentation of quarterly
sprinkler system inspection for the first
quarter (January, February, March) 2016
was not available for review. Based on
observations with the Clinical Manager
during a tour of the facility from 1:30
p.m. to 3:00 p.m. on 05/15/17, hanging
tags affixed to the sprinkler system risers
in the basement only documents annual
waterflow alarm inspection and testing
with the most recent being performed by
Tyco SimplexGrinnell in May 2016.
Based on interview at the time of record
review and of the observations, the
Clinical Manager acknowledged
waterflow alarm inspection and testing
for the aforementioned quarters was not
available for review.
3. Based on record review, observation
and interview; the facility failed to
document sprinkler system gauge
inspections in accordance with NFPA 25.
NFPA 25, Standard for the Inspection,
Testing, and Maintenance of
Water-Based Fire Protection Systems,
2011 Edition, Section 5.2.4.1 states
gauges on wet pipe sprinkler systems
shall be inspected monthly to ensure that
they are in good condition and that
normal water supply pressure is being
maintained. Section 5.1.2 states valves
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 19 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
and fire department connections shall be
inspected, tested, and maintained in
accordance with Chapter 13. Section
13.1.1.2 states Table 13.1.1.2 shall be
utilized for inspection, testing and
maintenance of valves, valve components
and trim. Section 4.3.1 states records
shall be made for all inspections, tests,
and maintenance of the system and its
components and shall be made available
to the authority having jurisdiction upon
request. This deficient practice could
affect all patients, staff, and visitors in
the facility.
Findings include:
Based on review of "MSCC Sprinkler
Check List" documentation with the
Clinical Manager during record review
from 9:50 a.m. to 1:30 p.m. on 05/15/17,
monthly wet sprinkler system gauge
inspection documentation for the most
recent 12 month period was not available
for review. Based on telephone interview
with the Building Maintenance Manager
at the time of record review, the
aforementioned documentation pertained
to sprinkler system valve and seal checks
not sprinkler system gauge inspections.
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, the
facility has a supervised wet sprinkler
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 20 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
system and had two pressure gauges.
4. Based on observation and interview,
the facility failed to ensure the supply of
spare sprinklers maintained on the
premises corresponded to the types and
temperature ratings of the sprinklers in
the property. NFPA 25, Standard for the
Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems,
2011 Edition, Section 5.4.1.4 states a
supply of spare sprinklers (never fewer
than six) shall be maintained on the
premises so that any sprinklers that have
operated or been damaged in any way can
be promptly replaced. The sprinklers
shall correspond to the types and
temperature ratings of the sprinklers in
the property. The sprinklers shall be kept
in a cabinet located where the
temperature in which they are subjected
will at no time exceed 100 degrees
Fahrenheit. This deficient practice could
affect all patients, staff, and visitors in
the facility.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, one
sidewall sprinkler was observed installed
in the piped gas room in the basement.
No sidewall spare sprinklers were noted
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 21 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
in the spare sprinkler cabinet at the
sprinkler system risers in the basement or
on the premises. Based on interview at
the time of the observations, the Clinical
Manager acknowledged no sidewall spare
sprinklers were in the spare sprinkler
cabinet or on the premises.
5. Based on observation and interview,
the facility failed to maintain 1 of 1
sprinkler systems in accordance with
NFPA 25. NFPA 25, Standard for the
Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems,
2011 edition, Section 5.2.2.2 states
sprinkler piping shall not be subjected to
external loads by materials either resting
on the pipe or hung from the pipe. This
deficient practice could affect three
patients, staff and visitors in the vicinity
of the entrance lobby.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, one
blue cable was wrapped around a three
inch section of sprinkler pipe above the
suspended ceiling in the entrance lobby
for the facility near the vending
machines. Based on interview at the time
of the observations, the Clinical Manager
acknowledged the aforementioned
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 22 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
sprinkler pipe location was used to
support non-system components.
NFPA 101
Sprinkler System - Out of Service
Sprinkler System - Out of Service
Where the sprinkler system is impaired, the
extent and duration of the impairment has
been determined, areas or buildings
involved are inspected and risks are
determined, recommendations are
submitted to management or designated
representative, and the fire department and
other authorities having jurisdiction have
been notified. Where the sprinkler system is
out of service for more than 10 hours in a 24
hour period, the building or portion of the
building affected are evacuated or an
approved fire watch is provided until the
sprinkler system has been returned to
service.
9.7.5, 15.5.2 (NFPA 25)
K 0354
Bldg. 01
Based on record review and interview,
the facility failed to provide a complete
written policy for 1 of 1 written fire
safety plans for the protection of
residents indicating procedures to be
followed in the event the automatic
sprinkler system has to be placed
out-of-service for 10 hours or more in a
24-hour period in accordance with LSC
K 0354 1. The center's policy for interim
life safety measures (LSC 8.00)
provides detailed instructions for
sprinkler impairment
procedures whenever the
automatic sprinkler system is out
of service for more than 4 hours
in a 24 hour period. The policy
requires notification to the Indiana
State Department of Health, the
center's insurance carrier and the
06/05/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 23 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Section 9.7.5. LSC 9.7.5 requires
sprinkler impairment procedures comply
with NFPA 25, Standard for the
Inspection, Testing and Maintenance of
Water-Based Fire Protection Systems.
NFPA 25, 2011 Edition, Section 15.5.2
requires the fire department, insurance
carrier, the alarm company, the property
owner or designated representative and
other authorities having jurisdiction be
notified. This deficient practice could
affect all patients, staff and visitors.
Findings include:
Based on review of "Fire Watch -
Incident Action Plan" documentation
with the Clinical Manager during record
review from 9:50 a.m. to 1:30 p.m. on
05/15/17, the written fire watch policy for
automatic sprinkler system impairment
did not include notification of the
insurance carrier, the alarm monitoring
company and the Indiana State
Department of Health (ISDH) which is an
authority having jurisdiction. Based on
interview at the time of record review,
the Clinical Manager stated additional
written fire watch policy documentation
was not available for review and
acknowledged the facility's written policy
in the event the automatic sprinkler
system is out of service for ten hours or
more in a twenty four hour period did not
alarm monitoring company.
2. The clinical manager has been
provided an in-service on the
center policy for interim life safety
measures. The clinical manager
has also performed an inservice
for the center's staff on the policy.
3. The administrator is
responsible to ensure that all staff
are knowledgeable about the
center's policy regarding interim
life safety measures.
Policy LSC 8.00 Interim Life
Safety Measures is attached as
exhibit 4.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 24 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
include notification of ISDH, the
insurance carrier and the alarm
monitoring company.
NFPA 101
Portable Fire Extinguishers
Portable Fire Extinguishers
Portable fire extinguishers are selected,
installed, inspected, and maintained in
accordance with NFPA 10, Standard for
Portable Fire Extinguishers.
20.3.5.3, 21.3.5.3, 9.7.4.1, NFPA 10
K 0355
Bldg. 01
1. Based on observation and interview,
the facility failed to ensure 2 of 8
portable fire extinguishers had
documented annual maintenance in
accordance with NFPA 10. NFPA 10,
2010 Edition, Section 7.3.1.1.1 states fire
extinguishers shall be subject to
maintenance at intervals of not more than
one year, at the time of hydrostatic test,
or when specifically indicated by an
inspection or electronic notification.
Section 7.3.3 states each fire extinguisher
shall have a tag or label securely attached
that indicates the month and year the
maintenance was performed, identifies
the person performing the work, and
identifies the name of the agency
performing the work. This deficient
practice could affect all patients, staff and
visitors.
K 0355 1. Fire extinguisher inspections
are required monthly in the
center. The center's safety officer
has verified that all extinguishers
are up to date on their
inspections. The center's
contracted service provider has
performed annual maintenance
on all fire extinguishers on the
premise.
2. The center's life safety officer
will inspect all fire extinguishers
monthly and document those
inspections on the center's
Equipment List and Preventative
Maintenance checklist.
Verification of annual
maintenance has been added to
the center's equipment list and
PM schedule.
3. The clinical manager is
responsible to ensure that
environmental walkthroughs are
completed monthly and
documentation of annual
maintenance is maintained
06/07/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 25 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, the
ABC type portable fire extinguisher
located in the basement by the sprinkler
system risers had an affixed tag
indicating the most recent annual
maintenance was performed in April
2016. In addition, the ABC type portable
fire extinguisher located in the elevator
machine room on the first floor had an
affixed tag indicating the most recent
annual maintenance was performed in
June 2015. Based on interview at the
time of the observations, the Clinical
Manager stated SimplexGrinnell
performed annual maintenance for
facility fire extinguishers in April 2017
but acknowledged the aforementioned
two portable fire extinguishers did not
have annual maintenance documented
within the most recent twelve month
period.
3-1.19(b)
2. Based on observation and interview,
the facility failed to ensure 1 of 8
portable fire extinguishers located in the
facility were inspected at least monthly
and the inspections were documented
including the date and initials of the
onsite.
The center's monthly PM
Checklist is attached as exhibit 1.
The center's equipment list and
PM schedule has been added as
exhibit 3. Statement of work from
center's contracted service
provider on the fire extinguishers
is attached as exhibit 18.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 26 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
person performing the inspection in
accordance with NFPA 10. NFPA 10,
the Standard for Portable Fire
Extinguishers, 2010 Edition, Section
7.2.1.2 states fire extinguishers shall be
inspected either manually or by means of
an electronic monitoring device/system at
a minimum of 30-day intervals. Where
monthly manual inspections are
conducted, the date the manual inspection
was performed and the initials of the
person performing the inspection shall be
recorded. Where manual inspections are
conducted, records for manual
inspections shall be kept on a tag or label
attached to the fire extinguisher, on an
inspection checklist maintained on file,
or by an electronic method. Records
shall be kept to demonstrate that at least
the last 12 monthly inspections have been
performed. This deficient practice could
affect two staff and visitors.
Findings include:
Based on observation with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, the
ABC type portable fire extinguisher
located in the elevator machine room on
the first floor had an affixed tag lacking
monthly inspections after October 2016.
Based on interview at the time of
observation, the Clinical Manager stated
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 27 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
no other documentation of monthly fire
extinguisher inspections was available for
review and acknowledged documentation
of monthly inspections for the portable
fire extinguisher located in the elevator
machine room after October 2016 was
not available for review.
NFPA 101
Utilities - Gas and Electric
Utilities - Gas and Electric
Equipment using gas or related gas piping
complies with NFPA 54, National Fuel Gas
Code, electrical wiring and equipment
complies with NFPA 70, National Electric
Code. Existing installations can continue in
service provided no hazard to life.
20.5.1, 21.5.1, 21.5.1.2, 9.1.1, 9.1.2
K 0511
Bldg. 01
Based on observation and interview, the
facility failed to ensure electrical wiring
for 1 of 1 basement electrical fixtures
was maintained in safe operating
condition. LSC 21.5.1.1 requires utilities
comply with Section 9.1. LSC 9.1.2
requires electrical wiring and equipment
to comply with NFPA 70, National
Electrical Code. NFPA 70, 2011 Edition,
Article 300.15 states a box or conduit
body shall be installed at each junction
point unless otherwise permitted by
300.15(A) through (I). Article 314.28
states boxes and conduit bodies used as
pull or junction boxes shall be comply
K 0511 1. The building maintenance
provider has inspected the
basement area for any exposed
wiring and made corrections to
ensure that all connections are
contained in a junction box or
conduit body.
2. The facility safety officer shall
observe for any spliced or
exposed electrical wiring during
environmental walk throughs.
Any issues will be reported to
facilities maintenance for
immediate action. Exposed wiring
has been added to the center's
monthly PM checklist.
3. The clinical manager is
responsible to ensure that
environmental walkthroughs are
06/20/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 28 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
with 314.28 (A) through (E). This
deficient practice could affect three
patients.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17,
spliced and exposed electrical wiring was
noted for an electrical fixture in the
basement above the entry door to the
basement. Based on interview at the time
of the observations, the Clinical Manager
acknowledged exposed electrical wiring
in the basement was not contained within
a junction box or conduit body.
completed at regular intervals and
that any issues are reported to
facilities maintenance in writing.
The center's monthly PM
Checklist is attached as exhibit 1.
NFPA 101
Fire Drills
Fire Drills
Fire drills include the transmission of a fire
alarm signal and simulation of emergency
fire conditions. Fire drills are held at
unexpected times under varying conditions,
at least quarterly on each shift. The staff is
familiar with procedures and is aware that
drills are part of established routine.
Responsibility for planning and conducting
drills is assigned only to competent persons
who are qualified to exercise leadership.
Where drills are conducted between 9:00
PM and 6:00 AM, a coded announcement
K 0712
Bldg. 01
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 29 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
may be used instead of audible alarms.
20.7.1.4 through 20.7.14.7
Based on record review and interview,
the facility failed to document activation
of the fire alarm system for first shift fire
drills conducted between 6:00 a.m. and
9:00 p.m. for 1 of 4 quarters. LSC
21.7.1.4 states fire drills in health care
occupancies shall include the
transmission of the fire alarm signal and
simulation of emergency fire conditions.
When drills are conducted between 9:00
p.m. (2100 hours) and 6:00 a.m. (0600
hours), a coded announcement shall be
permitted to be used instead of audible
alarms. This deficient practice could
affect all patients, staff and visitors in the
facility.
Findings include:
Based on review of "Code Red Drill
Evaluation Report" documentation with
the Clinical Manager during record
review from 9:50 a.m. to 1:30 p.m. on
05/15/17, documentation for the first
shift fire drill conducted on 08/14/16 at
6:00 p.m. indicated the drill was
conducted after 6:00 a.m. but before 9:00
p.m. and did not include activation of the
fire alarm system and transmission of the
fire alarm signal. The aforementioned
first shift fire drill documentation stated
"Alarm not activated." Based on
K 0712 1. Center policy FP 8.00 Fire
Response requires quarterly fire
drills for all shifts. It further
outlines that the drills must
include the transmission of a fire
alarm signal and simulation of
emergency fire conditions.
Documentation is required for
each drill including staff
participation. The clinical
manager has held drills for both
shifts that include signal
transmission and emergency
simulation.
2. The center's safety officer is
responsible to ensure that
quarterly fire drills are held in the
center. Those drills will include
the transmission of a alarm signal
and simulation of emergency
conditions. Documentation of
the required drills will be verified
and recorded on the center's
environmental compliance
checklist.
3. The clinical manager is
responsible to ensure that fire
drills are performed at required
intervals and that they follow
center policy.
The center's equipment list and
PM schedule has been added as
exhibit 3. Policy FP 8.00 is
attached as exhibit 9.00.
06/14/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 30 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
interview at the time of record review,
the Clinical Manager acknowledged
documentation for the first shift fire drill
conducted after 6:00 a.m. but before 9:00
p.m. did not include activation of the fire
alarm system and transmission of the fire
alarm signal.
NFPA 101
Gas and Vacuum Piped Systems - Warning
System
Gas and Vacuum Piped Systems - Warning
Systems
All master, area, and local alarm systems
used for medical gas and vacuum systems
comply with appropriate Category warning
system requirements, as applicable.
5.1.9, 5.2.9, 5.3.6.2.2 (NFPA 99)
K 0904
Bldg. 01
Based on record review, observation and
interview; the facility failed to install and
maintain the facility's piped gas and
vacuum systems in accordance with
NFPA 99. NFPA 99, Health Care
Facilities Code, 2012 Edition, Section
5.1.9.2 states a master alarm shall be
provided to monitor the operation and
condition of the source of supply, the
K 0904 1. The center has contracted with
their medical gas
systems provider to add a second
master alarm panel to the center.
2. Verification of the presence
and operation of the center's two
medical gas alarm panels will be
included on the center's monthly
PM checklist.
3. The center's safety officer is
responsible to ensure that
06/26/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 31 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
reserve source (if any), and the pressure
in the main lines of each medical gas and
vacuum piping system. Section 5.1.9.2.1
states the master alarm system shall
consist of two or more alarm panels
located in at least two separate locations,
as follows:
(1) One master alarm panel shall be
located in the office or work space of the
on-site individual responsible for the
maintenance of the medical gas and
vacuum piping systems.
(2) In order to ensure continuous
surveillance of the medical gas and
vacuum systems while the facility is in
operation, the second master alarm panel
shall be located in an area of continuous
observation (e.g., the telephone
switchboard, security office, or other
continuously staffed located).
Section 5.1.9.4 states computer systems
used as substitute master alarms as
required by 5.1.9.2.1(2) shall have the
mechanical and electrical characteristics
described in 5.1.9.4.1 and the
programming characteristics described in
5.1.9.4.2. This deficient practice could
affect all patients, staff and visitors.
Findings include:
Based on review of Artec Environmental
Monitoring's "Master Warning Alarms -
Mechanism in Disrepair" section of
environmental walkthroughs are
completed in the center at routine
intervals.
The center's monthly PM
Checklist is attached as exhibit 1.
Contractor statement of work for
second alarm panel is attached
as exhibit 20.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 32 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
"Medical Gas PM Inspection
(Addendum)" documentation dated
02/29/16 with the Clinical Manager
during record review from 9:50 a.m. to
1:30 p.m. on 05/15/17, the Medical
Oxygen Manifold System, the Medical
Vacuum System and the Nitrogen
Manifold "has one master alarm (2 are
required)." Based on interview at the
time of record review, the Clinical
Manager stated the facility has not
installed a second master alarm location,
does not utilize computer systems for
substitute master alarms and
acknowledged the facility has only one
master alarm location for piped gas and
vacuum systems. Based on observations
with the Clinical Manager during a tour
of the facility from 1:30 p.m. to 3:00 p.m.
on 05/15/17, the facility has one master
alarm location for piped gas and vacuum
systems in the Post Op area of the
facility.
NFPA 101
Gas and Vacuum Piped Systems -
Maintenance Pr
Gas and Vacuum Piped Systems -
K 0907
Bldg. 01
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 33 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Maintenance Program
Medical gas, vacuum, WAGD, or support
gas systems have documented maintenance
programs. The program includes an
inventory of all source systems, control
valves, alarms, manufactured assemblies,
and outlets. Inspection and maintenance
schedules are established through risk
assessment considering manufacturer
recommendations. Inspection procedures
and testing methods are established through
risk assessment. Persons maintaining
systems are qualified as demonstrated by
training and certification or credentialing to
the requirements of AASE 6030 or 6040.
5.1.14.2.1, 5.1.14.2.2, 5.1.15, 5.2.14,
5.3.13.4.2 (NFPA 99)
Based on record review and interview,
the facility failed to maintain the facility's
piped gas and vacuum systems in
accordance with NFPA 99, Health Care
Facilities Code, 2012 Edition. This
deficient practice could affect all patients,
staff and visitors.
Findings include:
Based on review of Artec Environmental
Monitoring's "Medical Vacuum System"
section of "Medical Gas PM Inspection"
documentation dated 02/29/16 with the
Clinical Manager during record review
from 9:50 a.m. to 1:30 p.m. on 05/15/17,
the medical-surgical vacuum receiver(s),
pressure-sensing devices, mainline
pressure gauges and alarm indicators
were listed as "Fail" as the result of the
K 0907 1. The center's contracted service
provider will performed complete
tests of the vacuum system.
Those tests will include receivers,
pressure sensing devices,
mainline pressure gauges and
alarm indicators. Zone valves,
master alarm signal activation
and vacuum lag will be verified in
good working order. The results
of that testing will be maintained
onsite and any needed repairs will
be performed.
2. Annual testing will be
verified via the
center's equipment list and
preventative maintenance
checklist.
3. The clinical manager is
responsible to ensure that annual
testing occurs for the center's
medical gas and vacuum
systems.
The center's equipment list and
PM schedule has been added as
06/26/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 34 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
PM inspection. The "Zone Valves"
section of the aforementioned PM
Inspection stated the zone valves were
located in the same room as the outlets
served for vacuum systems and oxygen
and were also listed as "Fail." In
addition, the "Comments" section of the
"Master Alarm Signal Activation" section
of the aforementioned report stated "No
Vacuum Lag Present At Master Panel."
Based on interview at the time of record
review, the Clinical Manager stated piped
gas and vacuum systems repair or
replacement on or after 02/29/16 has not
been performed and acknowledged
documentation of piped gas and vacuum
systems repair or replacement on or after
02/29/16 was not available for review.
exhibit 3. Statement of work for
Medical Gas/Vacuum pump
contractor attached as exhibit 20.
NFPA 101
Electrical Systems - Other
Electrical Systems - Other
List in the REMARKS section, any NFPA 99
Chapter 6 Electrical Systems requirements
that are not addressed by the provided
K-Tags, but are deficient. This information,
along with the applicable Life Safety Code or
K 0911
Bldg. 01
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 35 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
NFPA standard citation, should be included
on Form CMS-2567.
Chapter 6 (NFPA 99)
Based on observation and interview, the
facility failed to ensure access and
working space was maintained for 3 of
over 5 electrical panels. NFPA 99,
Health Care Facilities Code, 2012
Edition, Section 6.3.2.1 states electrical
installation shall be in accordance with
NFPA 70, National Electric Code. NFPA
70, 2011 Edition, Article 110.26 states
access and working space shall be
provided and maintained about all
electrical equipment to permit ready and
safe operation and maintenance of such
equipment. Working space for
equipment operating at 600 volts,
nominal, or less and likely to require
examination, adjustment, servicing, or
maintenance while energized shall
comply with the dimensions of 110.26(A)
(1), (2) and (3). 110.26(A)(1) states the
depth of the working space in the
direction of live parts shall not be less
than that specified in Table 110.26(A)(1)
which the minimum clear distance is 3
feet. 110.26(A)(2) states the width of the
working space in front of the electrical
equipment shall be the width of the
equipment or 762 mm (30 in.), whichever
is greater. In all cases, the work space
shall permit at least a 90 degree opening
of equipment doors or hinged panels.
K 0911 1. The facility manager has
performed a walkthrough of the
facility. The nine doors propped
against the wall and stored 18
inches in front of the "Main
SWBD" electrical panel in the
basement electrical room have
been relocated. Any boxes
stored within one foot in front of
the "1E1A" and "IL3" electrical
panels have been relocated. . All
miscellaneous items were stored
on the floor underneath any
electrical panel have been
moved.
2. This deficiency will be
prevented by the performance of
environmental compliance
walkthroughs of the center.
Conditions will be verified at
regular intervals.
3. The clinical manager is
responsible to ensure that
environmental walkthroughs are
performed in the center.
The center's monthly PM
Checklist is attached as exhibit
1. See statement of work
exhibit 17.
06/07/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 36 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
110.26(A)(3) states the work space shall
be clear and extend from the grade, floor,
or platform to a height of 6 1/2 feet or the
height of the equipment, whichever is
greater. Article 110.26(B) states the
working space required by this section
shall not be used for storage. This
deficient practice could affect all patients,
staff and visitors.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, the
following was noted:
a. nine doors were propped against the
wall and stored 18 inches in front of the
"Main SWBD" electrical panel in the
basement electrical room.
b. boxes were stored one foot in front of
the "1E1A" electrical panel in the first
floor electrical room by the elevator
machine room. Boxes were also stored
one foot in front of the "IL3" electrical
panel in the room. Miscellaneous items
were stored on the floor underneath each
electrical panel.
Based on interview at the time of the
observations, the Clinical Manager
acknowledged the miscellaneous items
were stored within the working space in
front of the three electrical panels.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 37 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
NFPA 101
Electrical Systems - Essential Electric Syste
Electrical Systems - Essential Electric
System Maintenance and Testing
The generator or other alternate power
source and associated equipment is capable
of supplying service within 10 seconds. If the
10-second criterion is not met during the
monthly test, a process shall be provided to
annually confirm this capability for the life
safety and critical branches. Maintenance
and testing of the generator and transfer
switches are performed in accordance with
NFPA 110.
Generator sets are inspected weekly,
exercised under load 30 minutes 12 times a
year in 20-40 day intervals, and exercised
once every 36 months for four continuous
hours. Scheduled test under load conditions
include a complete simulated cold start and
automatic or manual transfer of all EES
loads, and are conducted by competent
personnel. Maintenance and testing of
stored energy power sources (Type 3 EES)
are in accordance with NFPA 111. Main and
feeder circuit breakers are inspected
annually, and a program for periodically
exercising the components is established
according to manufacturer requirements.
Written records of maintenance and testing
are maintained and readily available. EES
electrical panels and circuits are marked and
readily identifiable. Minimizing the possibility
of damage of the emergency power source
is a design consideration for new
installations.
K 0918
Bldg. 01
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 38 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110,
NFPA 111, 700.10 (NFPA 70)
1. Based on observation and interview,
the facility failed to ensure 1 of 1
emergency generators was kept in
reliable operating mode in accordance
with NFPA 110, Standard for Emergency
and Standby Power Systems. NFPA 110,
2010 Edition, Section 8.3.1 states the
Emergency Power Supply Systems
(EPSS) shall be maintained to ensure that
the system is capable of supplying service
within the time specified for the type and
for the time duration specified for the
class. Section 8.3.7.2 states defective
batteries shall be replaced immediately
upon discovery of defects. This deficient
practice could affect all patients, staff and
visitors.
Findings include:
Based on observations with the Clinical
Manager at 3:10 p.m. on 05/15/17, the
horn switch for the Generac Standby
Power Monitor remote annunciator
located at the nurse's station for the
facility's emergency generator was turned
to the off position. The "Low Water
Temp" trouble light was illuminated on
the annunciator panel. The annunciator
horn sounded when the horn switch was
turned to the on position two separate
times. Based on interview at time of the
K 0918 1. The center's contracted
service provider for generator
maintenance has performed all
required testing and
provided documentation
on transfer time for monthly load
tests and cool down time. The
annunciator panel including all
panel lights and the horn switch
have been tested and are
operating correctly. Center staff
have been in-serviced on how to
respond to warning lights and
alarms regarding the center's
emergency generator.
2. The center's safety officer
shall confirm monthly generator
testing on the center's equipment
list and preventative maintenance
schedule checklist. Any
deficiencies will be reported the
center's contracted service
provider.
3. The clinical manager is
responsible to ensure that facility
maintenance is performed at
specified intervals and the results
are made available upon request.
The center's equipment list and
PM schedule has been added as
exhibit 3.
06/20/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 39 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
observations, the Clinical Manager stated
she was unaware of any issues with the
emergency generator, it started and ran
during the most recent load test but
acknowledged the aforementioned
annunciator trouble light was illuminated
with the annunciator horn silenced.
2. Based on record review and interview,
the facility failed to document the
transfer time to the alternate power
source on the monthly load tests for 5 of
the most recent 12 months to ensure the
alternate power supply was capable of
supplying service within 10 seconds.
NFPA 99, Health Care Facilities Code,
2012 Edition, Section 6.4.4.1.1.1 states
the generator set or other alternate power
source and associated equipment,
including all appurtenance parts shall be
so maintained as to be capable of
supplying service within the shortest time
frame practicable an within the 10 second
interval specified in 6.4.1.1.10 and
6.4.3.1. This deficient practice could
affect all patients, staff and visitors.
Findings include:
Based on review of "Emergency
Generator - Monthly Test Log"
documentation with the Clinical Manager
during record review from 9:50 a.m. to
1:30 p.m. on 05/15/17, monthly load
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 40 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
testing documentation for 01/10/17
through 05/06/17 did not include transfer
time from normal power to emergency
power. Based on interview at the time of
record review, the Clinical Manager
acknowledged monthly load testing
documentation for the aforementioned
period did not include transfer time from
normal power to emergency power.
3. Based on record review and interview,
the facility failed to ensure 1 of 1
emergency generators was allowed a 5
minute cool down period after a load test
for 5 of the most recent 12 months in
accordance with NFPA 110, Standard for
Emergency and Standby Power Systems.
NFPA 110, 2010 Edition, Section 6.2.10
Time Delay on Engine Shutdown
requires a minimum time delay of 5
minutes shall be provided for unloaded
running of the Emergency Power Supply
(EPS) prior to shutdown to allow for
engine cooldown. This time delay shall
not be required on small (15 kW or less)
air-cooled prime movers. NFPA 110,
Section 8.3.4 states a permanent record of
the Emergency Power Supply Systems
(EPSS) inspections, tests, exercising,
operation, and repairs shall be maintained
and readily available. This deficient
practice could affect all patients, staff and
visitors.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 41 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
Findings include:
Based on review of "Emergency
Generator - Monthly Test Log"
documentation with the Clinical Manager
during record review from 9:50 a.m. to
1:30 p.m. on 05/15/17, monthly load
testing documentation for 01/10/17
through 05/06/17 did not include did not
include cool down time. Based on
interview at the time of record review,
the Clinical Manager stated the
emergency generator is load tested
monthly for at least 30 minutes but
acknowledged cool down time is not
specifically recorded in monthly load
testing documentation for the
aforementioned five month period.
NFPA 101
Gas Equipment - Cylinder and Container
Storag
Gas Equipment - Cylinder and Container
Storage
*Greater than or equal to 3,000 cubic feet
Storage locations are designed, constructed,
and ventilated in accordance with 5.1.3.3.2
and 5.1.3.3.3.
*Greater than 300 but less than 3,000 cubic
feet
Storage locations are outdoors in an
enclosure or within an enclosed interior
space of non- or limited- combustible
construction, with door (or gates outdoors)
that can be secured. Oxidizing gases are not
K 0923
Bldg. 01
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 42 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
stored with flammables, and are separated
from combustibles by 20 feet (5 feet if
sprinklered) or enclosed in a cabinet of
noncombustible construction having a
minimum 1/2 hour fire protection rating.
*Less than or equal to 300 cubic feet
In a single smoke compartment, individual
cylinders available for immediate use in
patient care areas with an aggregate volume
of less than or equal to 300 cubic feet are
not required to be stored in an enclosure.
Cylinders must be handled with precautions
as specified in 11.6.2.
A precautionary sign readable from 5 feet is
on each door or gate of a cylinder storage
room, where the sign includes the wording
as a minimum "CAUTION: OXIDIZING
GAS(ES) STORED WITHIN NO
SMOKING."
Storage is planned so cylinders are used in
order of which they are received from the
supplier. Empty cylinders are segregated
from full cylinders. When facility employs
cylinders with integral pressure gauge, a
threshold pressure considered empty is
established. Empty cylinders are marked to
avoid confusion. Cylinders stored in the
open are protected from weather.
11.3.1, 11.3.2, 11.3.3, 11.3.4, 11.6.5 (NFPA
99)
Based on observation and interview, the
facility failed to ensure 1 of 1 piped gas
system supply areas was enclosed with a
separation of 1 hour fire resistive
construction. NFPA 99, Health Care
Facilities Code, 2012 Edition, Section
11.3.1 states storage for nonflammable
gases equal to or greater than 3000 cubic
feet at STP shall comply with 5.1.3.3.2
and 5.1.3.3.3. Section 5.1.3.3.2(4) states
K 0923 1. Building maintenance has
corrected the latching
mechanisms on the east door
serving as entry to the medical
gas room.
2. Confirmation that door latching
mechanisms are functioning has
been added to the
center's monthly PM checklist.
3. The center's safety officer is
responsible for environmental
rounding at regular intervals.
06/09/2017 12:00:00AM
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 43 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
central supply systems, if indoors, shall
be constructed and use interior finishes of
noncombustible or limited combustible
materials such that all walls, floors,
ceilings, and doors are of a minimum
1-hour fire resistance rating. This
deficient practice could affect all patients
and staff.
Findings include:
Based on observations with the Clinical
Manager during a tour of the facility from
1:30 p.m. to 3:00 p.m. on 05/15/17, the
piped gas system supply room in the
basement has two separate door sets
serving as the entry doors to the room.
The east door in the northeast door set
failed to latch into the door frame as the
latching mechanism at the top of the door
failed to protrude into the door frame.
Fourteen 'H' type oxygen cylinders were
observed stored in the room. Based on
interview at the time of the observations,
the Clinical Manager acknowledged the
aforementioned entry door to the piped
gas supply room would not latch into the
door frame and did not provide the room
with one hour fire resistive construction.
The center's monthly PM
Checklist is attached as exhibit 1.
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 44 of 45
(X1) PROVIDER/SUPPLIER/CLIA
DEPARTMENT OF HEALTH AND HUMAN SERVICES
CENTERS FOR MEDICARE & MEDICAID SERVICES
07/27/2017PRINTED:
FORM APPROVED
OMB NO. 0938-0391
STATEMENT OF DEFICIENCIES
AND PLAN OF CORRECTION IDENTIFICATION NUMBER:
(X2) MULTIPLE CONSTRUCTION
A. BUILDING
B. WING
(X3) DATE SURVEY
COMPLETED
NAME OF PROVIDER OR SUPPLIERSTREET ADDRESS, CITY, STATE, ZIP CODE
(X4) ID
PREFIX
TAG
SUMMARY STATEMENT OF DEFICIENCIES
(EACH DEFICIENCY MUST BE PRECEDED BY FULL
REGULATORY OR LSC IDENTIFYING INFORMATION)
PREFIX
TAG
IDPROVIDER'S PLAN OF CORRECTION
(EACH CORRECTIVE ACTION SHOULD BE
DEFICIENCY)
(X5)
COMPLETION
DATECROSS-REFERENCED TO THE APPROPRIATE
INDIANAPOLIS, IN 46290
15C0001183 05/15/2017
MULTI SPECIALTY SURGERY CENTER
10601 N MERIDIAN ST SUITE 100
01
FORM CMS-2567(02-99) Previous Versions Obsolete Event ID: 7IXF21 Facility ID: 012823 If continuation sheet Page 45 of 45