TELEINFORMASI DATA DAN TAMPILANUNTUK SISTEM OTOMASI GARDU INDUK
Bagian 1:FUNGSI OPERASI
PT PLN (Persero)Jl. Trunojoyo Blok M-1/135 Kebayoran Baru
Jakarta Selatan 12160
STANDARPT PLN (PERSERO)
SPLN S5.003-1: 2014
Lampiran Keputusan DireksiPT PLN (Persero) No. 0952.K/DIR/2014
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 2/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 3/118
TELEINFORMASI DATA DAN TAMPILANUNTUK SISTEM OTOMASI GARDU INDUK
Bagian 1:FUNGSI OPERASI
STANDARPT PLN (PERSERO)
SPLN S5.003-1: 2014
Lampiran Keputusan DireksiPT PLN (PERSERO) No. 0952. K/DIR/2014
PT PLN (Persero)
Jl. Trunojoyo Blok M-1/135 Kebayoran BaruJakarta Selatan 12160
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 4/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 5/118
TELEINFORMASI DATA DAN TAMPILANUNTUK SISTEM OTOMASI GARDU INDUK
Bagian 1:FUNGSI OPERASI
Disusun oleh :
Kelompok Bidang SCADA Standardisasidengan Keputusan Direksi
PT PLN (Persero)
No. 0448.K/DIR/2014
Kelompok Kerja StandardisasiTeleinformasi Data Untuk Sistem Otomasi Gardu Induk
dengan Keputusan KepalaPT PLN (Persero) Puslitbang Ketenagalistrikan
No. 0236.K/PUSLITBANG/2014
Diterbitkan oleh :
PT PLN (Persero)Jl. Trunojoyo Blok M -1/135, Kebayoran Baru
Jakarta Selatan 12160
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 6/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 7/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 8/118
Susunan Kelompok Bidang SCADA StandardisasiKeputusan Direksi PT PLN (Persero)
No. 0448.K/DIR/2014
1. Ir. I Putu Riasa : Sebagai Ketua merangkap Anggota
2. Tri Hardimasyar,ST,MSc : Sebagai Sekretaris merangkap Anggota
3. Agus Harya Maulana, ST, MT : Sebagai Anggota
4. Novrizal Erdiyansyah, ST, MSc : Sebagai Anggota
5. Ir. Hesti Sayoga : Sebagai Anggota
6. Ir. Ruly Chaerul : Sebagai Anggota
7. Ir. Ridwan Nainggolan : Sebagai Anggota
8. A Sugeng Sugarjito,ST : Sebagai Anggota
9. Made Yusadana, ST, MSc : Sebagai Anggota10. Denden Ruhdani, ST : Sebagai Anggota
11. Erwan Herdiyanto, ST, MSc : Sebagai Anggota
12. Muchsin Akuba Gani, ST : Sebagai Anggota
13. Akbar Patonangi, ST : Sebagai Anggota
Susunan Kelompok Kerja StandardisasiTeleinformasi Data Untuk Sistem Otomasi Gardu Induk
Keputusan Kepala PT PLN (Persero) Puslitbang KetenagalistrikanNo. 0236.K/PUSLITBANG/2014
1. Joko Pitoyo, ST : Sebagai Ketua merangkap Anggota
2. Tri Hardimasyar, ST, M.Sc : Sebagai Sekretaris merangkap Anggota
3. Suci Rositawati, ST : Sebagai Anggota
4. Lukman Hakim, ST : Sebagai Anggota
5. Ricci Fajar, ST : Sebagai Anggota
6. Riko Ramadhano Budiawan, ST : Sebagai Anggota
7. Amiruddin, ST : Sebagai Anggota
8. Lugito Nurwahono, ST : Sebagai Anggota
9. Novrizal Erdiansyah, ST,MSc : Sebagai Anggota
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 9/118
SPLN S5.003-1: 2014
i
Daftar Isi
Daftar Isi ............................................................................................................................. iDaftar Gambar ................................................................................................................... ii
Daftar Tabel ...................................................................................................................... iii
Daftar LAMPIRAN ............................................................................................................. iv
Prakata ............................................................................................................................. v
1 Ruang Lingkup ............................................................................................................. 1
2 Tujuan .......................................................................................................................... 1
3
Acuan Normatif ............................................................................................................. 1
4 Istilah dan Definisi ........................................................................................................ 2
4.1
Alarm ................................................................................................................... 2
4.2 Control center ...................................................................................................... 2
4.3
Distribution control center (DCC) ......................................................................... 2
4.4 Feeder colouring .................................................................................................. 2
4.5 Gardu hubung ...................................................................................................... 2
4.6 Gardu induk ......................................................................................................... 2
4.7 Gardu tengah ....................................................................................................... 2
4.8 Human Machine Interface (HMI) .......................................................................... 2
4.9 Inter Distribution Control Center (IDCC) ............................................................... 3
4.10
Inter Regional Control Center (IRCC) .................................................................. 3
4.11 Maintenance Center ............................................................................................ 3
4.12
National Control Center (NCC) ............................................................................ 3
4.13 Operator .............................................................................................................. 3
4.14
Regional Control Center (RCC) ........................................................................... 3
4.15 Regu pemeliharaan ............................................................................................. 3
4.16 Remote station .................................................................................................... 3
4.17 Sistem Otomasi Gardu Induk (SOGI) ................................................................... 3
4.18 Supervisory Control and Data Acquisition (SCADA) ............................................ 3
4.19 Telecontrol ........................................................................................................... 4
4.20 Telesignal ............................................................................................................ 4
4.21
Telemetering ........................................................................................................ 4
5 Umum ........................................................................................................................... 4
5.1
Fasilitas SCADA untuk SOGI ............................................................................... 4
5.2 Teleinformasi data (TID) ...................................................................................... 4
5.3
Struktur informasi................................................................................................. 4
5.4 Simbol dan warna ................................................................................................ 5
5.5 Tampilan HMI Fungsi Operasi ............................................................................. 5
5.6 Gambar tipikal HMI Fungsi Operasi ..................................................................... 5
5.7 Penjelasan gambar tipikal HMI Fungsi Operasi ................................................... 7
6
Perbatasan Kebutuhan Teleinformasi Data .................................................................. 9
6.1 Perbatasan Kebutuhan Teleinformasi Data antara IRCC dan RCC ..................... 9
6.2
Perbatasan kebutuhan teleinformasi data antara RCC dan DCC ....................... 11
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 10/118
SPLN S5.003-1: 2014
ii
Daftar Gambar
Gambar 1. Tipikal HMI fungsi operasi ................................................................................ 5
Gambar 2. Topologi ........................................................................................................... 6
Gambar 3. Single Diagram fungsi operasi ......................................................................... 7 Gambar 4. Tipikal HMI fungsi operasi ................................................................................ 8
Gambar 5. Batas wewenang antara IRCC dengan RCC (Tipe-a) ...................................... 9
Gambar 6. Batas wewenang antara IRCC dengan RCC (Tipe-b) .................................... 10
Gambar 7. Batas wewenang antara RCC dengan DCC .................................................. 11
Gambar 8. Konfigurasi SLD 1 ½ breaker ......................................................................... 18
Gambar 9. Konfigurasi umum pada 1 ½ breaker 150 kV ................................................. 22
Gambar 10. Konfigurasi umum pada double busbar ........................................................ 26
Gambar 11. Konfigurasi umum pada single busbar ......................................................... 30
Gambar 12. Interbus transformer (secondary side connected to 1½ breaker) ................ 34
Gambar 13. Interbus transformer (secondary side connected to double busbar ) ............. 36
Gambar 14. Interbus transformer (secondary side connected to single busbar ) ............. 38
Gambar 15. Secondary side terhubung 1½ breaker dilengkapi dhunt reaktor pada
kumparan tersier ............................................................................................................. 40
Gambar 16. Secondary side connected to double busbar dilengkapi shunt reaktor pada
kumparan tersier ............................................................................................................. 42
Gambar 17. Secondary side connected to single busbar dilengkapi shunt reaktor pada
kumparan tersier ............................................................................................................. 44
Gambar 18. Bay trafo tenaga pada konfigurasi 1½ breaker ............................................. 46
Gambar 19. Bay trafo tenaga pada konfigurasi double busbar ........................................ 48
Gambar 20. Bay trafo tenaga pada konfigurasi single busbar ........................................ 50
Gambar 21. Bay reaktor pada konfigurasi 1 ½ breaker.................................................... 52
Gambar 22. Bay reaktor pada konfigurasi double busbar ................................................ 53
Gambar 23. Bay reaktor pada konfigurasi single busbar ................................................. 54
Gambar 24. Bay capasitor pada konfigurasi double busbar ............................................. 55
Gambar 25. Bay capasitor pada konfigurasi single busbar .............................................. 56
Gambar 26. Bay penghantar pada konfigurasi 1 ½ breaker ............................................. 57
Gambar 27. Bay penghantar pada konfigurasi double busbar ......................................... 58
Gambar 28. Bay penghantar pada konfigurasi single busbar .......................................... 60
Gambar 29. Bay penghantar paralel dengan reaktor pada konfigurasi double busbar ..... 62
Gambar 30. Bay penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker ...... 63
Gambar 31. Bay kopel pada konfigurasi double busbar ................................................... 65
Gambar 32. Konfigurasi umum pada double busbar ........................................................ 70 Gambar 33. Konfigurasi umum pada single busbar ........................................................ 73
Gambar 34. Trafo 150/20 kV dan 70/20 kV tipe 1 ............................................................ 76
Gambar 35. Trafo 150/20 kV dan 70/20 kV tipe 2 ............................................................ 77
Gambar 36. Trafo 150/20 kV dan 70/20 kV tipe 3 ............................................................ 78
Gambar 37. Generator pada konfigurasi double busbar .................................................. 79
Gambar 38. Generator pada konfigurasi single busbar .................................................... 80
Gambar 39. Feeder 20 kV tipe 1 ..................................................................................... 81
Gambar 40. Feeder 20 kV tipe 1 ..................................................................................... 83
Gambar 41. Bus section 20 kV tipe 1 .............................................................................. 84
Gambar 42. Bus section 20 kV tipe 2 .............................................................................. 85
Gambar 43. Kopel ........................................................................................................... 86
Gambar 44. Capacitor bay .............................................................................................. 87
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 11/118
SPLN S5.003-1: 2014
iii
Gambar 45. Struktur informasi khusus (bay diameter) ..................................................... 95
Gambar 46. Struktur informasi khusus (gardu induk 1½ breaker ) .................................... 96
Gambar 47. Simbol gambar ............................................................................................. 97
Gambar 48. Tampilan status ............................................................................................ 98
Daftar Tabel
Tabel 1. Daftar telesignal fungsi operasi .......................................................................... 12
Tabel 2. Daftar telemeasurement ..................................................................................... 16
Tabel 3. Daftar tap changer position ................................................................................ 17
Tabel 4. Daftar remote control ......................................................................................... 17
Tabel 5. Teleinformasi data untuk konfigurasi umum pada 1½ breaker ........................... 19
Tabel 6.Teleinformasi data untuk konfigurasi umum pada 1½ breaker ........................... 23
Tabel 7. Teleinformasi data untuk konfigurasi umum pada double busbar ....................... 27
Tabel 8. Teleinformasi data untuk konfigurasi umum pada single busbar ........................ 31
Tabel 9. Teleinformasi data untuk interbus transformer (secondary side connected to 1½
breaker ) ........................................................................................................................... 35
Tabel 10. Teleinformasi data untuk interbus transformer (secondary side connected to
double busbar) ................................................................................................................. 37
Tabel 11. Teleinformasi data untuk interbus transformer (secondary side connected to
single busbar) .................................................................................................................. 39
Tabel 12. Teleinformasi data untuk interbus transformer (secondary side connected to 1½
breaker dilengkapi shunt reaktor pada kumparan tersier) ................................................ 41
Tabel 13.Teleinformasi data untuk interbus transformer (secondary side connected to
double busbar dilengkapi shunt reaktor pada kumparan tersier) ...................................... 43
Tabel 14. Teleinformasi data untuk interbus transformer (secondary side connected to single busbar dilengkapi shunt reaktor pada kumparan tersier) ....................................... 45
Tabel 15. Teleinformasi data untuk bay trafo tenaga pada konfigurasi 1½ breaker .......... 47
Tabel 16. Teleinformasi data untuk bay trafo tenaga pada konfigurasi double busbar ..... 49
Tabel 17. Teleinformasi data untuk bay trafo tenaga pada konfigurasi single busbar ....... 51
Tabel 18. Teleinformasi data untuk bay reaktor pada konfigurasi 1 ½ breaker ................. 52
Tabel 19. Teleinformasi data untuk bay reaktor pada konfigurasi double busbar ............. 53
Tabel 20. Teleinformasi data untuk bay reaktor pada konfigurasi single busbar ............... 54
Tabel 21. Teleinformasi data untuk bay kapasitor pada konfigurasi double busbar .......... 55
Tabel 22. Teleinformasi data untuk bay kapasitor pada konfigurasi single busbar ........... 56
Tabel 23. Teleinformasi data untuk bay penghantar pada konfigurasi 1 ½ breaker .......... 57
Tabel 24. Teleinformasi data untuk bay penghantar pada konfigurasi double busbar ...... 59Tabel 25. Teleinformasi data untuk bay penghantar pada konfigurasi single busbar ........ 60
Tabel 26. Teleinformasi data untuk bay penghantar serial dengan reaktor pada konfigurasi
double busbar .................................................................................................................. 62
Tabel 27. Teleinformasi data untuk bay penghantar paralel dengan 1 reaktor pada
konfigurasi 1½ breaker .................................................................................................... 64
Tabel 28. Teleinformasi data untuk bay kopel pada konfigurasi double busbar ................ 65
Tabel 29. Daftar telesignal distribusi ................................................................................ 66
Tabel 30. Daftar telemeasurement ................................................................................... 68
Tabel 31. Daftar tap changer ........................................................................................... 69
Tabel 32. Daftar remote control digital ............................................................................. 69
Tabel 33. Teleinformasi data untuk konfigurasi umum pada double busbar ..................... 70Tabel 34. Teleinformasi data untuk konfigurasi umum pada single busbar ...................... 73
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 12/118
SPLN S5.003-1: 2014
iv
Tabel 35. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 1 .......................... 76
Tabel 36. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 2 .......................... 77
Tabel 37. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 3 .......................... 78
Tabel 38. Teleinformasi data untuk generator pada konfigurasi double busbar ............... 80
Tabel 39. Teleinformasi data untuk generator pada konfigurasi single busbar ................. 81Tabel 40. Teleinformasi data untuk feeder 20 kv tipe 1.................................................... 82
Tabel 41. Teleinformasi data untuk feeder 20 kv tipe 1.................................................... 83
Tabel 42. Teleinformasi data untuk bus section 20 kv tipe 1 ............................................ 84
Tabel 43.Teleinformasi data untuk bus section 20 kv tipe 2 ............................................. 85
Tabel 44. Teleinformasi data untuk kopel ........................................................................ 86
Tabel 45. Teleinformasi data untuk capasitor bay ............................................................ 87
Tabel 46. Struktur informasi ............................................................................................ 89
Tabel 47. Level tegangan ................................................................................................ 91
Tabel 48. Nama bay atau feeder ..................................................................................... 92
Tabel 49. Kode tegangan dari primer dan sekunder trafo ................................................ 93
Tabel 50. Kode nama peralatan/alarm/elemen ................................................................ 93Tabel 51. Warna tampilan ............................................................................................... 99
Daftar LAMPIRAN
LAMPIRAN 1. Daftar Teleinformasi ................................................................................. 12
LAMPIRAN 2. Teleinformasi pada Berbagai Konfigurasi Gardu Induk ............................. 18
LAMPIRAN 3. Daftar Teleinformasi (Distribusi) ............................................................... 66
LAMPIRAN 4. Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi ................... 70
LAMPIRAN 5. Struktur Informasi ..................................................................................... 89
LAMPIRAN 6. Simbol dan Warna .................................................................................... 97
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 13/118
SPLN S5.003-1: 2014
v
Prakata
Standar SCADA ini merupakan pedoman dalam rangka mengikuti perkembanganteknologi SCADA dan Telekomunikasi.
Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasidata, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi danpemeliharaan yang memiliki hubungan dengan sistem SCADA.
Standar ini terdiri dari dua bagian, yaitu:
1. S5.003-1: 2014 Teleinformasi Data dan Tampilan Untuk Sistem Otomasi Gardu IndukBagian 1: Fungsi Operasi
2. S5.003-2: 2014 Teleinformasi Data dan Tampilan Untuk Sistem Otomasi Gardu IndukBagian 2: Fungsi Pemeliharaan
Standar ini harus menjadi acuan dalam setiap perencanaan, pembangunan, operasi danpemeliharaan sistem SCADA di PT PLN (Persero) secara nasional.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 14/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 15/118
SPLN S5.003-1: 2014
1
Teleinformasi Data dan Tampilan UntukSistem Otomasi Gardu Induk
Bagian 1: Fungsi Operasi
1 Ruang Lingkup
Teleinformasi data terdiri dari telecontrol , telesignal dan telemetering . Sesuai denganperkembangan teknologi peralatan di Gardu Induk, teleinformasi data ini dibuat untukkepentingan operasi dan kebutuhan pemeliharaan pada Gardu Induk otomasi. Standar inidimaksudkan untuk menetapkan standar teleinformasi data yang diaplikasikan untukkebutuhan operasi sistem tenaga listrik dan mencakup sistem transmisi dan sistemdistribusi.
Standar ini, berlaku untuk sistem SCADA:
a. National Control Center , disingkat NCC;b. Inter Regional Control Center , disingkat IRCC;c. Regional Control Center , disingkat RCC;d. Inter Distribution Control Center , disingkat IDCC;e. Distribution Control Center , disingkat DCC.
2 Tujuan
Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalampenerapan teleinformasi data dan tampilan HMI 1yste bagi penerapan gardu induk
otomasi yang mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakanacuan dalam pembangunan System SCADA untuk Gardu Induk otomasi baru dan 1ystemSCADA untuk penambahan bay baru (migrasi RTU). Untuk bay lama, tetap menggunakanteleinformasi data fungsi operasi sesuai dengan SPLN S5.001: 2008 yang akandisetarakan dengan TID untuk SOGI.
3 Acuan Normatif
Dokumen-dokumen referensi/acuan berikut sangat diperlukan dalam penggunaan standarini. Untuk referensi yang bertanggal, maka hanya terbitan tersebut yang berlakusedangkan referensi yang tidak bertanggal, yang berlaku adalah terbitan terakhir dari
dokumen referensi tersebut (termasuk amandemennya).Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalampembuatan standar SCADA: Teleinformasi Data Untuk Sistem Otomasi Gardu Induk.
a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol – Bagian 1:Pertimbangan Umum – Seksi 1: Prinsip Umum;
b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali ;
c. SPLN S3.001: 2008 “Peralatan SCADA Sistem Tenaga Listrik”; d. SPLN T5.002-1: 2010 ”Pola Proteksi Saluran Transmisi Bagian 1 : Tegangan Tinggi
66 kV dan 150 kV”; e. SPLN T5.002-2: 2010”Pola Proteksi Saluran Transmisi Bagian 2 : Tegangan Ekstra
Tinggi 275 kV dan 500 kV”;
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 16/118
SPLN S5.003-1: 2014
2
f. IEC 61850-1 ” Communication networks systems in substations – Part 1: Introductionand overview ”;
g. IEC 61850-2 ” Communication networks systems in substations – Part 2: Glossary ”; h. IEC 61850-3 ” Communication networks systems in substations – Part 3: General
Requirement ”;
4 Istilah dan Definisi
4.1 Alarm
Perubahan kondisi dari peralatan atau System yang telah terdeteksi sebelumnya karenafungsi yang tidak dilakukan oleh operator/dispatcher , atau kegagalan peralatan untukmerespon secara benar. Indikasi alarm berupa audible atau visual , atau keduanya.
4.2 Control c enter
Pusat kendali pengoperasian sistem tenaga listrikdimana master station ditempatkan.
4.3 Distr ibut ion con trol center (DCC)
Pusat kendali jaringan distribusi.
4.4 Feeder colouring
Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi bertegangan.
4.5 Gardu hubung
Gardu yang mempunyai fungsi utama melakukan manuver antar feeder.
4.6 Gardu induk
Gardu yang mempunyai fungsi sebagai pusat pembagi beban.
4.7 Gardu tengah
Gardu yang merupakan titik tengah beban atau titik tengah feeder.
4.8 Human Mach ine Interface (HMI)
Perangkat dimana pengguna berinteraksi dengan system SCADA. HMI menyediakanfasilitas dimana pengguna dapat memberikan input kepada system dan system dapatmemberikan output kepada pengguna.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 17/118
SPLN S5.003-1: 2014
3
4.9 Inter Distr ibut ion Control Center (IDCC)
Pusat kendali yang terhubung dengan beberapa distribution control center .
4.10 Inter Regio nal Contro l Center (IRCC)
Pusat kendali yang terhubung dengan beberapa regional control center .
4.11 Maintenance Center
Workstation di luar control center yang digunakan untuk keperluan pemeliharaan.
4.12 National Contro l Center (NCC)
Pusat kendali yang terhubung dengan beberapa inter regional control center .
4.13 Operator
Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk.
4.14 Region al Contr ol Center (RCC)
Pusat kendali jaringan transmisi tegangan tinggi.
4.15 Regu pemeliharaan
Petugas yang melakukan pemeliharaan pada instalasi sistem tenaga listrik.
4.16 Remote station
Stasiun yang dipantau, atau diperintah dan dipantau oleh master station, yang terdiri darigateway , IED, HMI lokal, RTU, dan meter energi.
4.17 Sistem Otomasi Gardu Induk (SOGI)
Sistem untuk mengelola, mengendalikan, dan proteksi system tenaga listrik. Hal ini dapatdicapai dengan mengambil informasi real time dari system, didukung oleh aplikasi localdan remote control yang handal dan proteksi system tenaga listrik. Sebuah Substation Automation terdiri dari local intelligence, komunikasi data dan supervisory control , sertamonitoring .
4.18 Supervisory Con trol and Data Acquisi t ion (SCADA)
Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara
geografis. [ IEC 870-1-3 ]
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 18/118
SPLN S5.003-1: 2014
4
4.19 Telecontro l
Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan tekniktelekomunikasi. [IEV 371-01-01]CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering /pengukuran,
proteksi dan fasilitas tripping , tidak menggunakan pesan suara.
4.20 Telesignal
Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakanteknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-04]
4.21 Telemetering
Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV371-01-03]
5 Umum
5.1 Fasilitas SCADA untuk SOGI
Setiap pembangunan gardu induk yang baru dan penambahan bay baru pada gardu induklama harus dapat dipantau dari control center dan dilakukan pengujian sebelumdiintegrasikan ke system transmisi atau system distribusi tenaga listrik.
5.2 Teleinformasi data (TID)
Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasidata untuk Sistem Otomasi Gardu Induk (SOGI) dapat dilihat pada pada LAMPIRAN 1.Daftar Teleinformasi.
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi makamaster station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasiyang digunakan mengacu pada teleinformasi data transmisi dan distribusi.
Teleinformasi data untuk sistem SOGI ditampilkan pada Master Station, MaintenanceCenter dan HMI (Human Machine Interface) lokal pada gardu induk setempat.Konfigurasi workstation di luar control center yang difungsikan untuk Maintenance Center dan juga HMI (Human Machine Interface) lokal yang bertempat di Gardu Induk setempat,menampilkan kebutuhan teleinformasi data fungsi pemeliharaan. Untuk Dispatcher padacontrol center , ditampilkan kebutuhan teleinformasi data fungsi operasi.
5.3 Struktur informasi
Event dan alarm merupakan pemberitahuan kepada dispatcher atau operator tentangkejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di datahistorikal. Struktur informasi event dan alarm SCADA dapat dilihat pada LAMPIRAN 5.Struktur Informasi.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 19/118
SPLN S5.003-1: 2014
5
5.4 Simbol dan warna
Simbol dan warna diperlukan untuk penyajian diagram system tenaga listrik pada monitordan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat systemdan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenalioleh regu pemeliharaan dan operator . Simbol dan warna dapat dilihat pada LAMPIRAN 6.
Simbol dan Warna.
5.5 Tampilan HMI Fungsi Operasi
Tampilan pada HMI fungsi operasi harus diatur agar seragam. Eksekusi manuver peralatan harus dapat dilakukan dengan cara yang mudah dan cepat dengan maksimal 3langkah yaitu:
1. Klik peralatannya.2. Pilih tombol Close atau Open 3. Execute atau Cancel.
Kategori tampilan yang harus ada pada HMI Fungsi Operasi adalah:
1. Single Line Diagram Gardu Induk sesuai dengan TID SOGI Fungsi Operasi:a. Single Line Diagram untuk Tegangan Ekstra Tinggib. Single Line Diagram untuk Tegangan Tinggi.c. Single Line Diagram untuk Tegangan Menengah.d. Single Line Diagram untuk Daya Pemakaian Sendiri.e. Overview keseluruhan SLD Gardu Induk, diusahakan untuk ditampilkan dalam
1 layar.2. Pengukuran keseluruhan Gardu Induk sesuai TID SOGI Fungsi Operasi
a. Tabel Measurement realtime.b. Log sheet pengukuran.
3. Event list yang dapat dilakukan proses filter dan diekspor ke dalam bentuk
database (Oracle dan/atau SQL dan/atau Spreadsheet )4. Alarm list yang dapat dilakukan proses filter dan diekspor ke dalam bentukdatabase (Oracle dan/atau SQL dan/atau Spreadsheet )
5. Simbol.
5.6 Gambar tipikal HMI Fungsi Operasi
5.6.1 Umum
Gambar 1. Tipikal HMI fungsi operasi
Lambang PLN Nama Gardu Induk & Level Tegangan Hari + Tanggal + Jam
Na ma Us er Lo cal/Remote
Dummy CB
Jenis AlarmPrint
Ikon Baterai
Catatan: Isi tampilan untuk bagian header kelengkapan informasinya harus
mengikuti informasi yang ada pada lay out ini, sedangkan penempatan
informasinya adalah bebas tergantung masing-masing aplikasi HMI.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 20/118
SPLN S5.003-1: 2014
6
5.6.2 Topologi
4. Control Centre
2. Relay & Control Panel
(Urutan Panel di Ruang
Kontrol GI)
1. Switchyard
3.HMI SOGI
BUS - A
BUS - B
1 2 34
BUS - A
BUS - B
1 2 3
4
BUS - A
BUS - B
1 2 3
4
BUS - A
BUS - B
1 2 3
4
Gambar 2. Topologi
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 21/118
SPLN S5.003-1: 2014
7
5.6.3 Contoh Single line diagram fungsi operasi
Di atas SLD ada:
1. Dummy CB2. Kontrol Disable/Enable (Diganti menjadi Local Remote)
3. Nama GI4. Kondisi alarm Baterai (dlm bentuk ikon), RTU, Komunikasi,5. Kondisi GI (General Interrogation, In service atau Out service)6. Jenis-jenis alarm (Emergency, Critical, General, Limit violation, Station )7. Hari, tanggal, jam.
Lambang PLN Nama Gardu Induk & Level Tegangan Hari + Tanggal + Jam
Nama User Local/Remote
Dummy CB
Jenis AlarmPrint
BB - A
LFC
(Po,Pr,N)
BB - B
Q
P
PQ
I
BAY
GENERATOR
BAY
REAKTOR
BAY
IBT
BAY
TRAFO
TENAGA
L/R
Q
BAYKOPEL
V
PQ
L/R L/R
150 kV
I
QP
V
150/20 kV
L/R
L/R
PQV
BAY
TRANSMISI
I
150 kV
150/70 kV
Catatan :
1. arah panah pada bay menunjukan arah
pengiriman daya
Ikon Baterai
Gambar 3. Single Diagram fungsi operasi
5.7 Penjelasan gambar tipikal HMI Fungsi Operasi
Alarm gangguan rectifier dan baterai ditampilkan dalam bentuk ikon (bisa berupa
ikon baterai atau aki). Peletakannya dilakukan di sudut kiri atas. Ukurannya 2x
gambar CB. Ikon tersebut akan blinking apabila terjadi gangguan.
Posisi kontrol GI dalam mode local atau remote secara general harus ditampilkan
di bagian atas.
“Dummy CB” adalah indikasi dan soft button dummy circuit breaker .
Tampilan overview adalah tampilan yang menampilkan keseluruhan SLD dengan
level tegangan yang sama, misalnya tampilan keseluruhan SLD 500 kV, SLD 150
kV, SLD 66 kV dan SLD 20 kV.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 22/118
SPLN S5.003-1: 2014
8
Untuk bay yang sedang dalam posisi interlock (PMT dan PMS) dipersyaratkan
menampilkan gambar gembok untuk menginformasikan status tersebut ke
dispatcher . Contohnya dapat dilihat pada gambar berikut:
L/R
L/RL/R
BB - A
BB - B
150 kV
150 kV
Gembok
berwarna kuning
Gambar 4. Tipikal HMI fungsi operasi
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 23/118
SPLN S5.003-1: 2014
9
6 Perbatasan Kebutuhan Teleinformasi Data
Teleinformasi data yang dikirim ke/dari suatu control center ditentukan olehkewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelasantara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskanperbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC danDCC.
6.1 Perbatasan Kebutuhan Teleinformasi Data antara IRCC dan RCC
Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanantegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 55dan Gambar 66.
a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar
IRCC
RCC
BUSBAR TT
BUSBAR TET/TT
Gambar 5. Batas wewenang antara IRCC dengan RCC (Tipe-a)
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 24/118
SPLN S5.003-1: 2014
10
b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1½ Breaker
IRCC
RCC
BUSBARTT
BUSBARTT
BUSBAR TET/TT
Gambar 6. Batas wewenang antara IRCC dengan RCC (Tipe-b)
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 25/118
SPLN S5.003-1: 2014
11
6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC
Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan
pada Gambar 77.
BUSBAR TT
BUSBAR TM
L/R
P
Q
V
I
RCC
DCC
Gambar 7. Batas wewenang antara RCC dengan DCC
Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belumdipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi datadapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOPyang berlaku di daerah tersebut.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 26/118
SPLN S5.003-1: 2014
12
LAMPIRAN 1. Daftar Teleinformasi
1-1: Telesignal
Tabel 1. Daftar telesignal fungsi operasi
No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event
TSS/TSD H/LN D/B/G/P F/C A/I
1 AQR Automatic power factor active Generator, TSS H B C I
2 ARCircuit breaker auto reclosesuccess
OHL feeder, TSS LN B C A
3 ARLCircuit breaker auto recloselock out
OHL feeder, TSS LN B C A
4 ARO Auto reclose on/off OHL feeder, TSD LN B C I
5 AVR Automatic voltage regulatoron/off
Generator, TSS H B C I
6 AVRAM Avr Auto/ manual IBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),
TSD LN D C I
7 BF Bay fault
Bus coupler,Bus section,OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),Capacitor,Reactor,Diameter,Gen transf,
TSS LN B C A
8 BIBus isolator switchclosed/opened
Bus coupler,Bus section,
OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),TRF 150(70)/20 sisi 20,Capacitor,Reactor,Gen Transf,
TSD H D C I
9 BP Busbar protection Busbar, TSS LN B C A
10 BRF Breaker fault
Bus coupler,
Bus section,OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),Capacitor,Reactor,Diameter,Gen transf,
TSS LN B C A
11 BUAL Building alarm Gardu induk, TSS H G C A
12 CB Circuit breaker closed/opened
Bus coupler,Bus section,Ohl feeder,
Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,
TSD H D C I
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 27/118
SPLN S5.003-1: 2014
13
No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event
TSS/TSD H/LN D/B/G/P F/C A/I
IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),TRF 150(70)/20 sisi 20,Capacitor,
Reactor,Diameter,
13 COM Communication faulty Gardu induk, TSS LN P C A
14 CSO Check synchronizing override Gardu induk, TSD LN B C I
15 CSPCheck synchronizing in
progress
Bus coupler,OHL feeder,Cable feeder,IBT 150/70 sisi 70,
TSS LN B C A
16 DEF Directional earth faultOHL feeder,Cable feeder,
TSS LN B F A
17 DIDiameter isolator switchclosed/opened
Diameter, TSD H D C I
18 DISZ1 Distance protection zone 1
OHL feeder,
Cable feeder, TSS LN B F A
19 DISZ2 Distance protection zone 2OHL feeder,Cable feeder,
TSS LN B F A
20 DISZ3 Distance protection zone 3OHL feeder,Cable feeder,
TSS LN B F A
21 DISZ4 Distance protection zone 4OHL feeder,Cable feeder,
TSS LN B F A
22 DTT Direct transfer trip OHL feeder, TSS LN P C A
23 ES Earth switch closed/openedBusbar,OHL feeder,CABLE feeder,
TSD H D C I
24 GOV Free acting governor active Generator, TSS H B C I
25 GRM Genset ready/maintenance Gardu induk, TSD H G C I
26 GTT Generator transformer trip Gen transf, TSS H B C A
27 GUC Generator unit run/stop Generator, TSD H P C I
28 IEDF Ied bay level faulty Gardu induk, TSS LN G C A
29 LCD Line current differentialOHL feeder,Cable feeder,
TSS LN B F A
30 LFALoad freq available/notavailable
Generator,blok, TSD H P C I
31 LFC Load freq control on/off switch Generator,blok, TSD H P C I
32 LFF Load freq control unit failureGenerator,blok,
TSS H B C I
33 LFR Load freq request on/off Generator,blok, TSD H P C I
34 LILine isolator switchclosed/opened
OHL feeder,Cable feeder,Capacitor,Reactor,Gen transf,
TSD H D C I
35 LOR Lock out relay trip Gardu Induk, TSS LN B C A
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 28/118
SPLN S5.003-1: 2014
14
No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event
TSS/TSD H/LN D/B/G/P F/C A/I
36 LRBCU Local/Remote for bcu
Bus Coupler,OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,
IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),TRF 150(70)/20 sisi 20,Capacitor,Reactor,Diameter,Gen transf,
TSD LN B C I
37 LRHMI Local/Remote for local hmi Gardu Induk, TSD LN G C I
38 OCGF Over current ground fault
Bus coupler,OHL feeder,Cable feeder,Capacitor,Reactor,Diameter,
TSS LN B C A
39 OCPT Oil cable pressure trip Cable feeder, TSS H B F A
40 PSO Power station operated Generator,blok, TSD H P C I
41 RA Reaktor alarm Reactor, TSS LN B C A
42 RT Reaktor trip Reactor, TSS LN B C A
43 SF Supply failure Gardu induk, TSS H B C A
44 SIBSoftware interlocking by
passedGardu induk, TSD LN B C I
45 SLF Station level faulty Gardu induk, TSS LN P C A
46 SOTF Switch on to faultOHL feeder,Cable feeder,
TSS LN B C A
47 TCH Tap changer high limitIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),
TSS H B C A
48 TCIP Tap changer in progressIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),
TSS H B C A
49 TCL Tap changer low limitIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),
TSS H B C A
50 TEA Temperature alarmIBT 150/70 sisi 150,TRF 150(70)/20 sisi
150(70),
TSS LN B C A
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 29/118
SPLN S5.003-1: 2014
15
No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event
TSS/TSD H/LN D/B/G/P F/C A/I
51 TRA Transformer alarmIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),
TSS LN B C A
52 TRBPTTransformer back up
protection trip
IBT 150/70 sisi 150,TRF 150(70)/20 sisi
150(70),
TSS LN B C A
53 TRMPTTransformer main protectiontrip
IBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),
TSS LN B C A
54 TTR Teleprotection trip receiveOHL feeder,Cable feeder,
TSS LN P C A
55 TTT Teleprotection trip transmitOHL feeder,Cable feeder,
TSS LN P C A
56 UFRT Under frequency relay trip
Bus Coupler,OHL feeder,Cable feeder,TRF 150(70)/20 sisi 20,
TSS LN B C A
57 UT Unit trip Generator, TSS H B C A
58 VACF VAC failure Gardu induk, TSS H G C A
59 VDCF VDC failure Gardu induk, TSS H G C A
60 VRT Voltage relay trip
OHL feeder,Cable feeder,TRF 150(70)/20 sisi 20,Capacitor,Reactor,
TSS LN B C A
61 VS Voltage status Busbar, TSS LN B C I
KETERANGAN:
A = Alarm (audible alarm, flashing display, etc)I = Indikasi (normal condition)TSS = Telesignal singleTSD = Telesignal doubleH = Hardwiring
LN = Logical NetworkD = per Device (peralatan)B = per BayG = per GIP = per PembangkitF = per FasaC = Common
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 30/118
SPLN S5.003-1: 2014
16
1-2: Telemeasurement
Tabel 2. Daftar telemeasurement
No Kode Fungsi Implementasi
Sumber
H/LN
Bagian
D/B/G/P
Jumlah
F/C
1 F FrekuensiBusbar,Ohl feeder,Cable feeder,
H G C
2 I Arus
Bus Coupler,Bus Section,OHL Feeder,Cable Feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 SISI 70,Gen Transf,
H B F
3 P Daya Aktif
OHL Feeder,Cable Feeder,
IBT 500(275)/150 SISI 150,IBT 150/70 SISI 70,TRF 150(70)/20 SISI 20,Gen Transf,Generator
LN B C
4 POAQ Real Power SettingGenerator,Blok
H D C
5 PRAQ Max Power Variation SettingGenerator,Blok
H D C
6 Q Daya Reaktif
OHL Feeder,Cable Feeder,IBT 500(275)/150 SISI 150,IBT 150/70 SISI 70,TRF 150(70)/20 SISI 20,
Kapasitor,Reaktor,Gen Transf,Generator
LN B C
7 V Tegangan
Busbar,Ohl feeder,Cable feeder,IBT 150/70 sisi 70,Generator,
H B F
KETERANGAN:
Logical Node pada TM apabila nilai didapat melalui perhitungan beberapa parameter.Hardwiring pada TM apabila nilai didapat melalui pengukuran dari sinyal masukan.* Per fasa untuk single phase.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 31/118
SPLN S5.003-1: 2014
17
1-3: Tap Changer Posit ion
Tabel 3. Daftar tap changer posi t ion
No Kode Fungsi ImplementasiSumber
H/LN BagianD/B/G/P
JumlahF/C
1 TPI Tap position indication Trafo, IBT H B C/F*
KETERANGAN:
* Per fasa untuk single phase.
1-4: Remote Control
Tabel 4. Daftar remote contro l
No Kode Fungsi Implementasi IndikasiRCD/RCA
SumberH/LN
BagianD/B/G/P
JumlahF/C
1 ARO Auto reclose on/off
Remote station,Gardu induk,Busbar,Bus coupler, Bus section, Ohl feeder, Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi 150(70),TRF 150(70)/20 sisi 20,Capacitor,Reactor,Diameter,
Gen transf,Generator,Blok,
RCD LN P C
2 AVRAM AVR auto/manual IBT 150/70 SISI 150,TRF 150(70)/20 sisi 150(70),
RCD LN D C
3 CB Circuit breaker closed/opened
Bus coupler,Bus section,Ohl feeder,Cable feeder,Ibt 150/70 sisi 150,Ibt 150/70 sisi 70,Trf 150(70)/20 sisi 150(70),Trf 150(70)/20 sisi 20,Capacitor,Reactor,Diameter,
RCD H D C
4 N Load freq control n_levelGENERATOR,BLOK,
RCA H P C
5 POOP Real power set pointGENERATOR,BLOK,
RCA H P C
6 PROP Max power variation set pointGENERATOR,BLOK,
RCA H P C
7 TC Tap changer raise/lowerIBT 150/70 SISI 150,TRF 150(70)/20 SISI 150(70),
RCD LN D C
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 32/118
SPLN S5.003-1: 2014
18
LAMPIRAN 2. Teleinformasi pada Berbagai Konfigurasi Gardu Induk
TA-01: Konfigurasi Umum Pada 1½ Breaker GITET
KONFIGURASI UMUM PADA 1½ BREAKER GITET
BUSBAR - A
TA-01
BUSBAR - B
Q
L/R
PQV
P
Q
I
P
Q
V
BAY GENERATOR
BAY FEEDER
BAY REAKTOR
BAY IBT
VI
PQ
L/R
L/R
L/R
L/R
L/R
L/R
L/R
V
V
I
Gambar 8. Konfigurasi SLD 1 ½ breaker
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 33/118
SPLN S5.003-1: 2014
19
Tabel 5. Teleinformasi data untuk konfigurasi umum pada 1½ breaker
Group Bay Data No Kode Fungsi Tipe Jmlh
GARDUINDUK
TSS
BUAL Building alarm A 1
COM Communication faulty A 1 IEDF Ied bay level faulty A 1
LOR Lock out relay trip A 1
SLF Station level faulty A 1
SF Supply failure A 1
VACF VAC failure A 1
VDCF VDC failure A 1
TSD
CSO Check synchronizing override I 1
DCB Dummy circuit breaker closed/opened I 1
GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIBSoftware interlocking by passed
I 1
RCDCSO Check synchronizing override 1
DCB Dummy circuit breaker closed/opened 1
BUSBAR
TMF Frekuensi 2
V Tegangan 2
TSS
MPUF IED MPU faulty A 2
BP Busbar protection A 1
VS Voltage status I 2
VTMT Voltage transformer MCB trip A 2
TSD ES Earth switch closed/opened I 2
DIAMETER
TSS
BF Bay fault A 1
BRF Breaker fault A 1
DTT Direct transfer trip A 1 CCP Circulating current protection trip A 1
CBF Circuit breaker failure trip A 1
OCGF Over current ground fault A 1
SZP Short zone protection trip A 1
TSD
DI Diameter isolator switch closed/opened I 6
CB Circuit breaker closed/opened I 3
LRBCU Local remote for BCU I 3
RCD CB Circuit breaker closed/opened 3
TM
F Frekuensi 1
V Tegangan 1
I Arus 1P Daya aktif 1
Q Daya reaktif 1
AMF Amperes fault 8
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
ARL Circuit breaker auto reclose lock out I 1
AR Circuit breaker auto reclose success I 1
CBF Circuit breaker failure trip A 1
DTT Direct transfer trip A 1
DEF Directional earth fault A 1DISZ1 Distance protection zone 1 A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 34/118
SPLN S5.003-1: 2014
20
Group Bay Data No Kode Fungsi Tipe Jmlh
BAY FEEDER TSS
DISZ2 Distance protection zone 2 A 1
DISZ3 Distance protection zone 3 A 1
DISZ4 Distance protection zone 4 A 1
LCD Line current differential A 1OCPT Oil cable pressure trip (Cable feeder) A 1
OCGF Over current ground fault A 1
SOTF Switch on to fault A 1
TTR Teleprotection trip receive A 1
TTT Teleprotection trip transmit A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
ARO Auto reclose on/off I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1
BAY IBT
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limitI 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
VRT Voltage relay trip A 1
TSD
AVRAM AVR auto/manual I 1
CB Circuit breaker closed/opened I 1
LI Line isolator switch closed/opened I 2
LRBCU Local/remote for BCU I 1
RCD
CB Circuit breaker closed/opened
AVRAM AVR auto/manual
TC Tap changer raise/lower
BAYREAKTOR
TM Q Daya reaktif 1
TSS
BF Bay fault A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
TSD
CB Circuit breaker closed/opened I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1PRAQ Max power variation setting 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 35/118
SPLN S5.003-1: 2014
21
Group Bay Data No Kode Fungsi Tipe Jmlh
BAYGENERATOR
POAQ Real power setting 1
V Tegangan 1
TSS
AQR Automatic power factor active I 1
AVR Automatic voltage regulator on/offI 1
BF Bay fault A 1
CSP Check synchronizing in progress I 1
GTT Generator transformer trip A 1
GOV Governor free I 1
LFF Load freq control unit failure A 1
UT Unit trip A 1
VRT Voltage relay trip A 1
TSD
ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LI Line isolator switch closed/opened I 1
LFA Load freq available/not available I 1
LFC Load freq control on/off switch I 1
LFR Load freq request on/off I 1
KETERANGAN:
A = AlarmI = IndikasiRincian Teleinformasi diatas adalah rincian per bay * GRM untuk Genset di Control Center
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 36/118
SPLN S5.003-1: 2014
22
TA-02: Konfigurasi Umum Pada 1 ½ Breaker 150 kV
KONFIGURASI UMUM PADA 1½ BREAKER 150 KV
BUSBAR - A
TA-02
BUSBAR - B
Q
L/R
PQV
P
Q
I
P
Q
V
BAY GENERATOR
BAY TRANSMISI
BAY REAKTOR
BAY IBT BAY TRAFO TENAGA
V
I
PQ
L/R
L/R
L/R
L/R
L/R
L/R
L/R
L/R
L/R
V
V
I
P
Q
I
V
Gambar 9. Konfigurasi umum pada 1 ½ breaker 150 kV
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 37/118
SPLN S5.003-1: 2014
23
Tabel 6.Teleinformasi data untuk konfigurasi umum pada 1½ breaker
Group Bay Data No Kode Fungsi Tipe Jmlh
GARDUINDUK
TSS
BUAL Building alarm A 1
COM Communication faulty A 1
IEDF IED bay level faulty A 1
LOR Lock out relay trip A 1
SLF Station level faulty A 1
SF Supply failure A 1
VACF VAC failure A 1
VDCF VDC failure A 1
TSD
CSO Check synchronizing override I 1
DCB Dummy circuit breaker closed/opened I 1
GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIB Software interlocking by passed I 1
RCD CSO Check synchronizing override 1DCB Dummy circuit breaker closed/opened 1
BUSBAR
TMF Frekuensi 2
V Tegangan 2
TSS
MPUF IED MPU faulty A 2
BP Busbar protection A 1
VS Voltage status I 2
VTMT Voltage transformer MCB trip A 2
TSD ES Earth switch closed/opened I 2
DIAMETER
TSS
BF Bay fault A 1
BRF Breaker fault A 1
DTT Direct transfer trip A 1 CCP Circulating current protection trip A 1
CBF Circuit breaker failure trip A 1
OCGF Over current ground fault A 1
SZP Short zone protection trip A 1
TSD
DI Diameter isolator switch closed/opened I 6
CB Circuit breaker closed/opened I 3
LRBCU Local remote for BCU I 3
RCD CB Circuit breaker closed/opened 3
TM
F Frekuensi 1
V Tegangan 1
I Arus 1P Daya aktif 1
Q Daya reaktif 1
AMF Amperes fault 8
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
ARL Circuit breaker auto reclose lock out I 1
AR Circuit breaker auto reclose success I 1
CBF Circuit breaker failure trip A 1
DTT Direct transfer trip A 1
DEF Directional earth fault A 1
DISZ1 Distance protection zone 1 A 1
DISZ2 Distance protection zone 2 A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 38/118
SPLN S5.003-1: 2014
24
Group Bay Data No Kode Fungsi Tipe Jmlh
BAY FEEDER TSS
DISZ3 Distance protection zone 3 A 1
DISZ4 Distance protection zone 4 A 1
LCD Line current differential A 1
OCPT Oil cable pressure trip (Cable feeder) A 1OCGF Over current ground fault A 1
SOTF Switch on to fault A 1
TTR Teleprotection trip receive A 1
TTT Teleprotection trip transmit A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
ARO Auto reclose on/off I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1
BAY IBT
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
TSD
AVRAM AVR auto/manual I 1
CB Circuit breaker closed/opened I 1
LI Line isolator switch closed/opened I 2
LRBCU Local/remote for BCU I 1
RCD
CB Circuit breaker closed/opened
AVRAM AVR auto/manual
TC Tap changer raise/lower
BAYTRAFOTENAGA
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperature alarm A 1
TET Temperature trip A 1
TRA Transformer alarm A 1TRBPT Transformer back up protection trip A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 39/118
SPLN S5.003-1: 2014
25
Group Bay Data No Kode Fungsi Tipe Jmlh
TRMPT Transformer main protection trip A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD AVRAM AVR auto/manual
I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD AVRAM Avr auto/manual 1
TC Tap changer raise/lower 1
BAYREAKTOR
TM Q Daya reaktif 1
TSS
BF Bay fault A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
TSD
CB Circuit breaker closed/opened I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
BAYGENERATOR
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
PRAQ Max power variation setting 1
POAQ Real power setting 1
V Tegangan 1
TSS
AQR Automatic power factor active I 1
AVR Automatic voltage regulator on/off I 1
BF Bay fault A 1
CSP Check synchronizing in progress I 1
GTT Generator transformer trip A 1
GOV Governor free I 1
LFF Load freq control unit failure A 1
UT Unit trip A 1
TSD
ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LI Line isolator switch closed/opened I 1
LFA Load freq available/not available I 1
LFC Load freq control on/off switch I 1
LFR Load freq request on/off I 1
KETERANGAN: A = Alarm
I = IndikasiRincian Teleinformasi diatas adalah rincian per bay
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 40/118
SPLN S5.003-1: 2014
26
TA-03: Konfigurasi Umum Pada Double Busbar
KONFIGURASI UMUM PADA DOUBLE BUSBAR
BUSBAR - A
TA-03
BUSBAR - B
QP
P
Q
I
P
Q
V
BAY GENERATOR
BAY FEEDER
BAY REAKTOR
BAY IBTBAY TRAFO TENAGA
L/R
Q
BAY KOPEL
VI
L/R L/R
V
V
I
QP
V
L/R
L/R L/R L/R
P
Q
I
V
I
Gambar 10. Konfigurasi umum pada double busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 41/118
SPLN S5.003-1: 2014
27
Tabel 7. Teleinformasi data untuk konfigurasi umum pada double busbar
Group Bay Data No Kode Fungsi Tipe Jmh
GARDUINDUK
TSS
BUAL Building alarm A 1
COM Communication faulty A 1
IEDF IED bay level faulty A 1
LOR Lock out relay trip A 1
SLF Station level faulty A 1
SF Supply failure A 1
VACF VAC failure A 1
VDCF VDC failure A 1
TSD
CSO Check synchronizing override I 1
DCBDummy circuit breakerclosed/opened
I 1
GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIB Software interlocking by passed I 1
RCDCSO Check synchronizing override 1
DCBDummy circuit breakerclosed/opened
1
BUSBAR
TMF Frekuensi 2
V Tegangan 2
TSS
BP Busbar protection A 1
VS Voltage status I 2
VTMT Voltage transformer MCB trip A 2
TSD ES Earth switch closed/opened I 2
KOPEL
TM I Arus 1
BF Bay fault A 1
TSS
BRF Breaker fault A 1
CSP Check Synchronizing In Progress A 1
OCGF Over current ground fault A 1
UFRT Under frequency relay trip A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
RCD CB Circuit breaker closed/opened 1
BAYFEEDER
TM
AMF Amperes fault 8
F Frekuensi 1
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
AR Circuit breaker auto reclose success I 1
ARL Circuit breaker auto reclose lock out I 1
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
DEF Directional earth fault A 1
DISZ1 Distance protection zone 1 A 1
DISZ2 Distance protection zone 2 A 1
DISZ3 Distance protection zone 3 A 1DISZ4 Distance protection zone 4 A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 42/118
SPLN S5.003-1: 2014
28
Group Bay Data No Kode Fungsi Tipe Jmh
DTT Direct transfer trip A 1
LCD Line current differential A 1
OCGF Over current ground fault A 1
OCPT** Oil cable pressure trip A 1SOTF Switch on to fault A 1
TTR Teleprotection trip receive A 1
TTT Teleprotection trip transmit A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
ARO Auto reclose on/off I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1RCD CB Circuit breaker closed/opened I 1
BAY IBT
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit A 1
TCIP Tap changer in progress I 1TCL Tap changer low limit A 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
TSD
AVRAM Avr auto/manual I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD
AVRAM Avr auto/manual 1
CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
BAYTRAFO
TENAGA
TC TPI Tap position indication I 1
TMP Daya aktif 1
Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
TCH Tap changer high limit A 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit A 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 43/118
SPLN S5.003-1: 2014
29
Group Bay Data No Kode Fungsi Tipe Jmh
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
AVRAM AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 2
LRBCU Local remote for BCU I 1
RCD
AVRAM AVR auto/manual 1
CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
BAYREAKTOR
TM Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
VRT Voltage relay trip A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened 1
BAYGENERATOR
TM
I Arus 1
P Daya aktif 2
POAQ Real power setting 1
PRAQ Max power variation setting 1
Q Daya reaktif 2
V Tegangan 1
TSS
AQR Automatic power factor active I 1
AVR Automatic voltage regulator on/off I 1
BF Bay fault A 1
BRF Breaker fault A 1
GOV Free acting governor active I 1
GTT Generator transformer trip A 1
LFF Load freq control unit failure A 1
UT Unit trip A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
GUC Generator unit run/stop I 1LFA Load freq available/not available I 1
LFC Load freq control on/off switch I 1
LFR Load freq request on/off I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
PSO Power station operated I 1
RCA
N Load freq control n_level 1
POOP Real power set point 1
PROP Max power variation set point 1
RCD LFR Load freq request on/off 1
KETERANGAN:*) = GRM untuk Genset contro center
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 44/118
SPLN S5.003-1: 2014
30
A = Alarm I = IndikasiRincian Teleinformasi diatas adalah rincian per bay
TA-04: Konfigurasi Umum Pada Single Busbar
KONFIGURASI UMUM PADA SINGLE BUSBAR
BUSBAR
TA-04
Q
P
V
P
Q
I
P
Q
V
PQ
BAY GENERATOR
BAY TRANSMISI
BAY REAKTOR
BAY IBTBAY TRAFO TENAGA
Q
VI
V
I
PQ
L/R L/R L/R
L/R
L/R L/R
I
V
Gambar 11. Konfigurasi umum pada single busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 45/118
SPLN S5.003-1: 2014
31
Tabel 8. Teleinformasi data untuk konfigurasi umum pada single busbar
Group Bay Data No Kode Fungsi Tipe Jmh
GARDUINDUK
TSS
BUAL Building alarm A 1
COM Communication faulty A 1
IEDF Ied bay level faulty A 1
LOR Lock out relay trip A 1
SLF Station level faulty A 1
SF Supply failure A 1
VACF VAC failure A 1
VDCF VDC failure A 1
TSD
CSO Check synchronizing override I 1
DCBDummy circuit breakerclosed/opened
I 1
GRM Genset ready/maintenance I 1)*
LRHMI Local/remote for local hmi I 1
SIB Software interlocking by passed I 1
RCDCSO Check synchronizing override 1
DCBDummy circuit breakerclosed/opened
1
BUSBAR
TMF Frekuensi 1
V Tegangan 1
TSS
BP Busbar protection A 1
VS Voltage status I 1
VTMT Voltage transformer MCB trip A 1
TSD ES Earth switch closed/opened I 1
BAYFEEDER
TM
AMF Amperes fault 8
F Frekuensi 1
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
AR Circuit breaker auto reclose success I 1
ARL Circuit breaker auto reclose lock out I 1
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
DEF Directional earth fault A 1
DISZ1 Distance protection zone 1 A 1
DISZ2 Distance protection zone 2 A 1
DISZ3 Distance protection zone 3 A 1
DISZ4 Distance protection zone 4 A 1
DTT Direct transfer trip A 1
LCD Line current differential A 1
OCGF Over current ground fault A 1
OCPT** Oil cable pressure trip A 1
SOTF Switch on to fault A 1
TTR Teleprotection trip receive A 1
TTT Teleprotection trip transmit A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1TSD ARO Auto reclose on/off I 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 46/118
SPLN S5.003-1: 2014
32
Group Bay Data No Kode Fungsi Tipe Jmh
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened I 1
BAY IBT
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit A 1TCIP Tap changer in progress I 1
TCL Tap changer low limit A 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
TSD
AVRAM Avr auto/manual I 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD AVRAM Avr auto/manual 1CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
BAYTRAFOTENAGA
TC 1 TPI Tap position indication I 1
TMP Daya aktif 1
Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
TCH Tap changer high limit A 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit A 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
AVRAM AVR auto/manual I 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 2
LRBCU Local remote for BCU I 1
RCD
AVRAM AVR auto/manual 1
CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
BAY TM Q Daya reaktif 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 47/118
SPLN S5.003-1: 2014
33
Group Bay Data No Kode Fungsi Tipe Jmh
REAKTOR
TSS
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A
1RT Reaktor trip A 1
VRT Voltage relay trip A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened 1
BAYGENERATOR
TM
I Arus 1
P Daya aktif 2
POAQ Real power setting 1
PRAQ Max power variation setting 1
Q Daya reaktif 2
V Tegangan 1
TSS
AQR Automatic power factor active I 1
AVR Automatic voltage regulator on/off I 1
BF Bay fault A 1
BRF Breaker fault A 1
GOV Free acting governor active I 1
GTT Generator transformer trip A 1
LFF Load freq control unit failure A 1
UT Unit trip A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
GUC Generator unit run/stop I 1
LFA Load freq available/not available I 1
LFC Load freq control on/off switch I 1
LFR Load freq request on/off I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for bcu I 1
PSO Power station operated I 1
RCA
N Load freq control n_level 1
POOP Real power set point 1
PROP Max power variation set point 1
RCD LFR Load freq request on/off 1
KETERANGAN:
A = AlarmI = IndikasiRincian Teleinformasi diatas adalah rincian per bay * = GRM untuk Genset control center
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 48/118
SPLN S5.003-1: 2014
34
TB-01: Interbus Transformer
(Secondary Sid e Conn ected to 1½ Breaker )
INTERBUS TRANSFORMER
Secondary Side Connected to 1½ Breaker
BUSBAR - A
TB-01
BUSBAR - B
PQ
I
Dioperasikan dari IRCC
Dioperasikan dari RCC
}
Download to RCC
BUSBAR (IRCC)
V
L/R
Gambar 12. Interbus tran sform er (secondary side co nnected to 1½ breaker)
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 49/118
SPLN S5.003-1: 2014
35
Tabel 9. Teleinformasi data untuk in terbus transformer (secondary side con nected to 1½breaker )
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I
1TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
TSD
AVRAM AVR auto/manual I 1
ES Earth switch closed/opened I 2
LI Line isolator switch closed/opened I 2
LRBCU Local/remote for bcu I 1
RCD AVRAM Avr auto/manual 1
TC Tap changer raise/lower 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 50/118
SPLN S5.003-1: 2014
36
TB-02: Interbus Transformer
(Secondary Side Connected to Dou ble Busb ar )
INTERBUS TRANSFORMER
Secondary Side Connected to Double Busbar
BUSBAR - A
TB-02
BUSBAR - B
BUSBAR (IRCC or RCC)
PQ
I
V }Operation Responsibility
by IRCC or RCC
Operation Responsibility
by RCCDownload to RCC
L/R
L/R
Gambar 13. In terbus transformer (secondary side connected to double bus bar )
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 51/118
SPLN S5.003-1: 2014
37
Tabel 10. Teleinformasi data untuk in terbus transformer (secondary side connected todouble bus bar)
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
TSD
AVRAM AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2-4*)
CB Circuit breaker closed/opened I 2
CSO Check synchronizing override I 1
ES Earth switch closed/opened I 2
LI Line isolator switch closed/opened I 1-0*)
LRBCU Local/remote for bcu I 1
RCD
AVRAM Avr auto/manual 1
CB Circuit breaker closed/opened I 2TC Tap changer raise/lower 1
KETERANGAN:*) = (Primary Side Connected to 1½ Breaker) –(Primary Side Connected to Double Busbar)
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 52/118
SPLN S5.003-1: 2014
38
TB-03: Interbus Transformer
(Secondary Side Connected to Single Busbar)
INTERBUS TRANSFORMER
Secondary Side Connected to Single Busbar
BUSBAR
TB-03
BUSBAR (IRCC or RCC)
PQ
IV }
Operation Responsibility
by IRCC or RCC
Operation Responsibility
by RCCDownload to RCC
L/R
L/R
Gambar 14. In terbus transformer (secondary side connected to single busb ar )
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 53/118
SPLN S5.003-1: 2014
39
Tabel 11. Teleinformasi data untuk in terbus transformer (secondary side connected tosingle busbar)
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
TSD
AVRAM AVR auto/manual I 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
CSO Check synchronizing override I 1
ES Earth switch closed/opened I 2
LI Line isolator switch closed/opened I 1-0*)
LRBCU Local/remote for bcu I 1
RCD
AVRAM Avr auto/manual 1
CB Circuit breaker closed/opened I 2TC Tap changer raise/lower 1
KETERANGAN:*) = (Primary Side Connected to 1½ Breaker) –(Primary Side Connected to Double Busbar )
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 54/118
SPLN S5.003-1: 2014
40
TB-04: Interbus Transformer
(Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor PadaKumparan Tersier)
INTERBUS TRANSFORMER
Secondary Side Connected to 1½ Breaker
Dilengkapi Shunt Reaktor Pada Kumparan Tersier
BUSBAR - A
TB-04
BUSBAR - B
P
Q
IV
Operation Responsibility
by IRCC
Operation Responsibility
by RCC
}
Download to RCC
BUSBAR (IRCC)
Q
L/R
Gambar 15. Secondary sid e terhubung 1½ breaker dilengkapi dhunt reaktor pada kumparantersier
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 55/118
SPLN S5.003-1: 2014
41
Tabel 12. Teleinformasi data untuk in terbus transformer (secondary side conn ected to 1½breaker dilengkapi shunt reaktor pada kumparan tersier)
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 2
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1TCL Tap changer low limit I 1
TEA Temperature alarm A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
VRT Voltage relay trip A 1
TSD
AVRAM AVR auto/manual I 1
ES Earth switch closed/opened I 2
LI Line isolator switch closed/opened I 3
LRBCU Local/remote for bcu I 1
RCD AVRAM Avr auto/manual 1TC Tap changer raise/lower 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 56/118
SPLN S5.003-1: 2014
42
TB-05: Interbus Transformer
(Second ary Side Connected to Doub le Busbar Dilengkapi Shunt ReaktorPada Kumparan Tersier)
INTERBUS TRANSFORMER
Secondary Side Connected to Double Busbar
Dilengkapi Shunt Reaktor Pada Kumparan Tersier
BUSBAR - A
TB-05
BUSBAR - B
BUSBAR (IRCC or RCC)
PQ
IV }
Operation Responsibility
by IRCC or RCC
Operation Responsibility
by RCCDownload to RCC
Q
L/R
L/R
Gambar 16. Secondary side con nected to double busbar dilengkapi shunt reaktor pada
kumparan tersier
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 57/118
SPLN S5.003-1: 2014
43
Tabel 13.Teleinformasi data untuk in terbus transformer (secondary side connected todouble busbar dilengkapi shunt reaktor pada kumparan tersier)
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indication I 1
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 2
V Tegangan 1
TSS
BF Bay fault A 3
BRF Breaker fault A 3
CSP Check synchronizing in progress A 1
OCGF Over current ground fault A 1
OLSRX Overload shedding receive A 1
OLSTX Overload shedding transmit A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
TCH Tap changer high limit A 1
TCIP Tap changer in progress A 1
TCL Tap changer low limit A 1
TRA Temperatur alarm A 1
TEA Temperatur alarm A 1
TET Temperatur trip A 1
TRBPT Transformer backup protection trip A 1
TRMPT Transformer main protection trip A 1
VRT Volage relay trip A 1
TSD
AVRAM AVR auto/manual I 1
CB Circuit breaker closed/opened I 2
ES Earthing switch closed/opened I 3
LI Line isolator switch closed/opened I 3
LRBCU Local/remote for BCU I 2
RCD
AVRAM AVR auto/manual 1
CB Circuit breaker closed/opened 2
TC Tap changer raise/lower 1
KETERANGAN:*) = (Primary Side Connected to 1½ Breaker )-(Primary Side Connected to Double Busbar )
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 58/118
SPLN S5.003-1: 2014
44
TB-06: Interbus Transformer
(Secondary Side Connected to Single Busbar Dilengkapi Shunt Reaktor PadaKumparan Tersier)
INTERBUS TRANSFORMER
Secondary Side Connected to Single Busbar
Dilengkapi Shunt Reaktor Pada Kumparan Tersier
BUSBAR
TB-06
BUSBAR (IRCC or RCC)
PQ
IV }
Operation Responsibility
by IRCC or RCC
Operation Responsibility
by RCCDownload to RCC
Q
L/R
L/R
Gambar 17. Secondary sid e connected to single busb ar dilengkapi shunt reaktor padakumparan tersier
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 59/118
SPLN S5.003-1: 2014
45
Tabel 14. Teleinformasi data untuk in terbus transformer (secondary side conn ected to single busbar dilengkapi shunt reaktor pada kumparan tersier)
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indication I 1
TM
AMF Amperes fault 8
I Arus 6
P Daya aktif 1
Q Daya reaktif 2
V Tegangan 6
TSS
BF Bay fault A 3
BRF Breaker fault A 3
CSP Check synchronizing in progress I 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperature alarm A 1
TET Temperature trip A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
AVRAM AVR auto/manual I 1BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 4
LI Line isolator switch closed/opened I 3
LRBCU Local/remote for BCU I 2
RCD
AVRAM AVR auto/manual 1
CB Circuit breaker closed/opened 4
TC Tap changer raise/lower 1
KETERANGAN:*) = (Primary Side Connected to 1½ Breaker) – (Secondary Side Connected to Single Busbar)
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 60/118
SPLN S5.003-1: 2014
46
TB-07: Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker
BAY TRAFO TENAGAPADA KONFIGURASI 1½ BREAKER
BUSBAR - A
TB-07
BUSBAR - B
PQ
TEGANGAN TINGGI
TEGANGAN MENENGAH
DOUBLE BUSBAR
Batas wewenang
V
I
Gambar 18. Bay trafo tenaga pada konfigurasi 1½ breaker
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 61/118
SPLN S5.003-1: 2014
47
Tabel 15. Teleinformasi data untuk bay trafo tenaga pada konfigurasi 1½ breaker
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indicatioan I 1
TM
AMF Amperes fault 8
I Arus 6
P Daya aktif 1
Q Daya reaktif 1
V Tegangan 3
TSS
BF Bay fault A 2
BRF Breaker fault A 2
CSP Check synchronizing in progress I 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperature alarm A 1
TET Temperature trip A 1
TRA Transformer alarm A 1
TRBPT Transformer back up protection trip A 1
TRMPT Transformer main protection trip A 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
AVRAM AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 2
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD AVRAM AVR auto/manual 1CB Circuit breaker closed/opened 2
TC Tap changer raise/lower 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 62/118
SPLN S5.003-1: 2014
48
TB-08: Bay Trafo Tenaga Pada Konfigurasi Double Busbar
BAY TRAFO TENAGA
PADA KONFIGURASI DOUBLE BUSBARBUSBAR - A
TB-08
BUSBAR - B
PQ
TEGANGAN TINGGI
TEGANGAN MENENGAH
DOUBLE BUSBAR
Batas wewenang
L/R
VI
Gambar 19. Bay trafo tenaga pada konfigurasi double busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 63/118
SPLN S5.003-1: 2014
49
Tabel 16. Teleinformasi data untuk bay trafo tenaga pada konfigurasi double busbar
Data No Kode Fungsi Tipe Jmh
TC TPI Tap position indication I 1
TM
P Daya aktif 1
Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker Fault A 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperatur Alarm A 1
TET Temperatur trip A 1
TRA Transformer Alarm A 1
TRBPT Transformer Backup Protection Trip A 1
TRMPT Transformer main Protection Trip A 1
TSD
AVRAM AVR auto/manual I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
RCD
AVRAM AVR auto/manual 1
CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 64/118
SPLN S5.003-1: 2014
50
TB-09: Bay Trafo Tenaga Pada Konfigurasi Single Busbar
BAY TRAFO TENAGA
PADA KONFIGURASI SINGLE BUSBAR
TB-09
BUSBAR
P
QTEGANGAN TINGGI
TEGANGAN MENENGAH
DOUBLE BUSBAR
Batas wewenang
L/R
V
I
Gambar 20. Bay trafo tenaga pada konfigurasi single busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 65/118
SPLN S5.003-1: 2014
51
Tabel 17. Teleinformasi data untuk bay trafo tenaga pada konfigurasi single busbar
Data No Kode Fungsi Tipe Jmh
TC 1 TPI Tap position indication I 1
TM
P Daya aktif 1
Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker Fault A 1
TCH Tap changer high limit I 1
TCIP Tap changer in progress I 1
TCL Tap changer low limit I 1
TEA Temperatur Alarm A 1
TET Temperatur trip A 1
TRA Transformer Alarm A 1
TRBPT Transformer Backup Protection Trip A 1
TRMPT Transformer main Protection Trip A 1
TSD
AVRAM AVR auto/manual I 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
RCD
AVRAM AVR auto/manual 1
CB Circuit breaker closed/opened 1
TC Tap changer raise/lower 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 66/118
SPLN S5.003-1: 2014
52
TB-10: Bay Reaktor Pada Konfigurasi 1 ½ Breaker
BAY REAKTOR
PADA KONFIGURASI 1½ BREAKER
BUSBAR - A
TB-10
BUSBAR - B
Q
Reaktor
Gambar 21. Bay reaktor pada konfigurasi 1 ½ breaker
Tabel 18. Teleinformasi data untuk bay reaktor pada konfigurasi 1 ½ breaker
Data No Kode Fungsi Tipe Jmh
TM Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
VRT Voltage relay trip A 1
TSD
ES Earth switch closed/opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/remote for BCU I 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 67/118
SPLN S5.003-1: 2014
53
TB-11: Bay Reaktor Pada Konfigurasi Double Busbar
BAY REAKTOR
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
TB-11
BUSBAR - B
Q
Reaktor
L/R
Gambar 22. Bay reaktor pada konfigurasi double busbar
Tabel 19. Teleinformasi data untuk bay reaktor pada konfigurasi double busbar
Data No Kode Fungsi Tipe Jmh
TM Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
VRT Voltage relay trip A 1
TSD
BI Bus Isolator Switch closed/opened I 2
CB Circuit breaker closed/opened I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD CB Circuit breaker closed/opened 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 68/118
SPLN S5.003-1: 2014
54
TB-12: Bay Reaktor Pada Konfigurasi Single Busbar
BAY REAKTORPADA KONFIGURASI SINGLE BUSBAR
TB-12
BUSBAR
Q
Reaktor
L/R
Gambar 23. Bay reaktor pada konfigurasi single busbar
Tabel 20. Teleinformasi data untuk bay reaktor pada konfigurasi single busbar
Data No Kode Fungsi Tipe JmhTM Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
VRT Voltage relay trip A 1
TSD
BI Bus Isolator Switch closed/opened I 1
CB Circuit breaker closed/opened I 1ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD CB Circuit breaker closed/opened 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 69/118
SPLN S5.003-1: 2014
55
TB-13: Bay Capasitor Pada Konfigurasi Double Busbar
BAY KAPASITORPADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
TB-13
BUSBAR - B
Q
Capasitor
L/R
Gambar 24. Bay capasi tor pada konfigurasi double busbar
Tabel 21. Teleinformasi data untuk bay kapasitor pada konfigurasi double busbar
Data No Kode Fungsi Tipe Jmh
TM Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
VRT Voltage relay trip A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
RCD CB Circuit breaker closed/opened 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 70/118
SPLN S5.003-1: 2014
56
TB-14: Bay Capasitor Pada Konfigurasi Single Busbar
BAY KAPASITOR
PADA KONFIGURASI SINGLE BUSBAR
TB-14
BUSBAR
Q
L/R
Capasitor
Gambar 25. Bay capasi tor pada konfigurasi single busbar
Tabel 22. Teleinformasi data untuk bay kapasitor pada konfigurasi single busbar
Data No Kode Fungsi Tipe JmhTM Q Daya reaktif 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
VRT Voltage relay trip A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
RCD CB Circuit breaker closed/opened 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 71/118
SPLN S5.003-1: 2014
57
TB-15: Bay Penghantar Pada Konfigurasi 1 ½ Breaker
BAY PENGHANTAR
PADA KONFIGURASI 1½ BREAKER
BUSBAR - A
TB-15
BUSBAR - B
PQVI
Gambar 26. Bay penghantar pada konfigurasi 1 ½ breaker
Tabel 23. Teleinformasi data untuk bay penghantar pada konfigurasi 1 ½ breaker
Data No Kode Fungsi Tipe Jmh
TM
F Frekuensi 1
V Tegangan 1
I Arus 1P Daya aktif 1
Q Daya reaktif 1
AMF Amperes fault 8
TSS
DISZ1 Distance protection zone 1 A 2
DISZ2 Distance protection zone 2 A 2
DISZ3 Distance protection zone 3 A 2
DISZ4 Distance protection zone 4 A 2
SOTF Switch on to fault A 2
DEF Directional earth fault A 2
LCD Line current differential A 2
AR Circuit breaker auto reclose success A
1 ARL Circuit breaker auto reclose lock out A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 72/118
SPLN S5.003-1: 2014
58
CSP Check synchronizing in progress A 1
OCGF Over current ground fault A 1
OGSTX Overgenerating shedding transmit I 1
OLSTX Overload shedding transmit I 1
OVR Over voltage relay trip A 1
DTT Direct transfer trip A 1
TTR Teleprotection trip receive A 1
TTT Teleprotection trip transmit I 1
OLSTX Overload shedding transmit I 1
OGSTX Overgenerating shedding transmit I 1
BF Bay fault A 1
TSD
ARO Auto reclose On/Off I 1
LI Line isolator switch closed/opened I 1
ES Earth switch closed/opened I 1
TB-16: Bay Penghantar Pada Konfigurasi Double Busbar
BAY PENGHANTAR
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
TB-16
BUSBAR - B
L/R
QVI
P
Gambar 27. Bay penghantar pada konfigurasi double busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 73/118
SPLN S5.003-1: 2014
59
Tabel 24. Teleinformasi data untuk bay penghantar pada konfigurasi double busbar
Data No Kode Fungsi Tipe Jmh
TM
AMF Amperes fault 8
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker Fault A 1
CSP Check synchronizing in progress I 1
ARL Circuit breaker auto reclose lock out A 1
AR Circuit breaker auto reclose success A 1
CBF Circuit Breaker Failure Trip A 1
DTT Direct Transfer Trip A 1
DEF Directional earth fault A 1
DISZ1 Distance protection zone 1 A 1
DISZ2 Distance protection zone 2 A 1
DISZ3 Distance protection zone 3 A 1
DISZ4 Distance protection zone 4 A 1
LCD Line current differential A 1
OCGF Over Current Ground Fault A 1
OCPT Oil cable pressure trip A 1*)
OGSTX Overgenerating shedding transmit I 1
OLSTX Overload shedding transmit I 1
SOTF Switch on to fault A 1
TTR Teleprotection trip receive I 1
TTT Teleprotection trip transmit I 1UFRT Under Frequency Relay Trip A 1
VRT Voltage relay trip A 1
TSD
ARO Auto Reclose On Off I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
ES Earth Switch Closed/Opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/Remote For BCU I 1
RCD CB Circuit breaker closed/opened 1
KETERANGAN:*) = Khusus untuk OHL Feeder **)
= Khusus untuk Cable Feeder
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 74/118
SPLN S5.003-1: 2014
60
TB-17: Bay Penghantar Pada Konfigurasi Single Busbar
BAY PENGHANTAR
PADA KONFIGURASI SINGLE BUSBAR
TB-17
BUSBAR
PQVI
L/R
Gambar 28. Bay penghantar pada konfigurasi single busbar
Tabel 25. Teleinformasi data untuk bay penghantar pada konfigurasi single busbar
Data No Kode Fungsi Tipe Jmh
TM
AMF Amperes fault 8
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker Fault A 1
CSP Check synchronizing in progress I 1
ARL Circuit breaker auto reclose lock out A 1
AR Circuit breaker auto reclose success A 1
CBF Circuit Breaker Failure Trip A 1DTT Direct Transfer Trip A 1
DEF Directional earth fault A 1
DISZ1 Distance protection zone 1 A 1
DISZ2 Distance protection zone 2 A 1
DISZ3 Distance protection zone 3 A 1
DISZ4 Distance protection zone 4 A 1
LCD Line current differential A 1
OCGF Over Current Ground Fault A 1
OCPT Oil cable pressure trip A 1*)
OGSTX Overgenerating shedding transmit I 1
OLSTX Overload shedding transmit I 1SOTF Switch on to fault A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 75/118
SPLN S5.003-1: 2014
61
TTR Teleprotection trip receive I 1
TTT Teleprotection trip transmit I 1
UFRT Under Frequency Relay Trip A 1
VRT Voltage relay trip A 1
TSD
ARO Auto Reclose On Off I 1
BI Bus isolator switch closed/opened I 1CB Circuit breaker closed/opened I 1
ES Earth Switch Closed/Opened I 1
LI Line isolator switch closed/opened I 1
LRBCU Local/Remote For BCU I 1
RCD CB Circuit breaker closed/opened 1
KETERANGAN:*)
= Khusus untuk OHL Feeder **)
= Khusus untuk Cable Feeder
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 76/118
SPLN S5.003-1: 2014
62
TB-18: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi DoubleBusbar
BAY PENGHANTAR
PARALEL DENGAN REAKTORPADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
TB-18
BUSBAR - B
PQV
Q
I
L/R
Gambar 29. Bay penghantar paralel dengan reaktor pada konfigurasi double busbar
Tabel 26. Teleinformasi data untuk bay penghantar serial dengan reaktor pada konfigurasidouble busbar
Data No Kode Fungsi Tipe Jmh
TM
AMF Amperes fault 8I Arus 1
P Daya aktif 1
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
ARL Circuit breaker auto reclose lock out A 1
AR Circuit breaker auto reclose success A 1
CBF Circuit breaker failure trip A 1
DTT Direct transfer trip A 1
DEF Directional earth fault A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 77/118
SPLN S5.003-1: 2014
63
DISZ1 Distance protection zone 1 A 1
DISZ2 Distance protection zone 2 A 1
DISZ3 Distance protection zone 3 A 1
DISZ4 Distance protection zone 4 A 1
LCD Line current differential A 1
OCGF Over current ground fault A 1OGSTX Overgenerating shedding transmit I 1
OLSTX Overload shedding transmit I 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
SOTF Switch on to fault A 1
TTR Teleprotection trip receive I 1
TTT Teleprotection trip transmit I 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
CB Circuit breaker closed/opened I 1
ARO Auto Reclose On Off I 1
BI Bus isolator switch closed/opened I 2
LI Line isolator switch closed/opened I 2
ES Earth Switch Closed/Opened I 1
LRBCU Local/Remote For BCU I 1
RCD CB Circuit breaker closed/opened 1
TB-19: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½Breaker
BAY PENGHANTAR
PARALEL DENGAN 1 REAKTORPADA KONFIGURASI 1½ BREAKER
BUSBAR - A
TB-19
BUSBAR - B
PQVQI
L/R
Gambar 30. Bay penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 78/118
SPLN S5.003-1: 2014
64
Tabel 27. Teleinformasi data untuk bay penghantar paralel dengan 1 reaktor padakonfigurasi 1½ breaker
Data No Kode Fungsi Tipe Jmh
TM
AMF Amperes fault 8
I Arus 1P Daya aktif 1
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
TSS
BF Bay fault A 1
BRF Breaker fault A 1
CSP Check synchronizing in progress I 1
ARL Circuit breaker auto reclose lock out A 1
AR Circuit breaker auto reclose success A 1
CBF Circuit breaker failure trip A 1
DTT Direct transfer trip A 1DEF Directional earth fault A 1
DISZ1 Distance protection zone 1 A 1
DISZ2 Distance protection zone 2 A 1
DISZ3 Distance protection zone 3 A 1
DISZ4 Distance protection zone 4 A 1
LCD Line current differential A 1
OCGF Over current ground fault A 1
RA Reaktor alarm A 1
RT Reaktor trip A 1
SOTF Switch on to fault A 1
TTR Teleprotection trip receive I 1
TTT Teleprotection trip transmit I 1
UFRT Under frequency relay trip A 1
VRT Voltage relay trip A 1
TSD
ARO Auto reclose On/Off I 1
LI Line isolator switch closed/opened I 2
ES Earth switch closed/opened I 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 79/118
SPLN S5.003-1: 2014
65
TB-20: Bay Kopel Pada Konfigurasi Double Busbar
BAY KOPEL
PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
TB-20
BUSBAR - B
L/R
I
Gambar 31. Bay kopel pada konfigurasi double busbar
Tabel 28. Teleinformasi data untuk bay kopel pada konfigurasi double busbar
Data No Kode Fungsi Tipe Jmh
TM I Arus 1
TSS
CSP Check synchronizing in progress I 1
BF Bay fault A 1
BRF Breaker fault A 1
OCGF Over current ground fault A 1
UFRT Under frequency relay trip A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
LRBCU Local remote for BCU I 1
SIB Software Interlocking Bypassed I 1
RCD CB Circuit breaker closed/opened 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 80/118
SPLN S5.003-1: 2014
66
LAMPIRAN 3. Daftar Teleinformasi (Distribusi)
3-1: Telesignal
Tabel 29. Daftar telesignal distribusi
No Kode Fungsi ImplementasiIndikasiTSS/TSD
SumberH/LN
BagianD/B/G/P
JumlahF/C
EventA/I
1 ARO Auto reclose on/offOutgoingfeeder
TSD LN B C I
2 AVRAM Avr auto/manual Trafo TSD LN B C I
3BI
Bus isolator switch
closed/opened
Kopel,OutgoingFeeder, Trafo,Incoming 20
KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSD H D C I
4 CBCircuit breakerclosed/opened
Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSD H D C I
5 RACKCircuit breakerrackin/rackout
Kopel,Outgoing
Feeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSD H B C I
6 DCBDummy circuit breakerclosed/opened
Gardu induk TSD H G C I
7 ESEarth switchclosed/opened
Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,
Bus Section,Gen Trafo,Generator
TSD H D C I
8 GUC Generator unit run/stop Generator TSD H P C I
9 LBSLoad break switchclosed/opened
Gardu induk TSD H G C I
10 LRBCU Local/remote for bcu
Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,
Generator
TSD LN B C I
11 LRHMI Local/remote for local hmi Gardu induk TSD LN G C I
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 81/118
SPLN S5.003-1: 2014
67
No Kode Fungsi ImplementasiIndikasiTSS/TSD
SumberH/LN
BagianD/B/G/P
JumlahF/C
EventA/I
12 PSO Power station operated Generator TSD H P C I
13 BF Bay fault
Busbar, Kopel,Outgoing
Feeder, Trafo,Incoming 20 KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSS H B C A
14 BRF Breaker fault
Kopel,OutgoingFeeder, Trafo,Incoming 20 KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSS H B C A
15 BUAL Building alarm Gardu induk TSS LN D C A
16 ARLCircuit breaker autoreclose lock out
Outgoingfeeder
TSS LN B C A
17 ARCircuit breaker autoreclose success
Outgoingfeeder
TSS LN B C A
18 COM Communication faulty Gardu Induk TSS H D C A
19 DEF Directional earth faultOutgoingfeeder
TSS LN B F A
20 GFT Ground fault trip
Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,
Gen Trafo,Generator
TSS LN B C A
21 IEDF IED bay level faulty Gardu Induk TSS LN G C A
22 IGFTInstantaneous groundfault trip
Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSS LN B C A
23 IOCT Instantaneous overcurrent trip
Kopel,OutgoingFeeder, Trafo,
Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSS LN B C A
24 OCT Over current trip
Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator
TSS LN B C A
25 SLF Station level faulty Gardu Induk TSS H B C A
26 SF Supply failure Gardu Induk TSS LN B C A
27 TCH Tap changer high limit Trafo TSS H B C I
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 82/118
SPLN S5.003-1: 2014
68
No Kode Fungsi ImplementasiIndikasiTSS/TSD
SumberH/LN
BagianD/B/G/P
JumlahF/C
EventA/I
28 TCIP Tap changer in progress Trafo TSS H B C I
29 TCL Tap changer low limit Trafo TSS H B C I
30 UFRT Under frequency relay trip Outgoingfeeder TSS LN B C A
31 UVRT Under voltage relay tripOutgoingfeeder
TSS LN B C A
32 VACF VAC failure Gardu induk TSS H G C A33 VDCF VDC failure Gardu induk TSS H G C A34 VS Voltage status Busbar TSS H B C I
KETERANGAN:
A = Alarm (audible alarm, flashing display, etc )I = Indikasi (normal condition)TSS = Telesignal single TSD = Telesignal double H = Hardwiring
LN = Logical NetworkD = per Device (peralatan)B = per Bay G = per GIP = per PembangkitF = per FasaC = Common
3-2: Telemeasurement
Tabel 30. Daftar telemeasurement
No Kode Fungsi ImplementasiSumber
H/LN BagianD/B/G/P
JumlahF/C
1 AMF Amperes fault ( per phase )Kopel, Bus section,Outgoing Feeder,Incoming 20 kV
LN B F
2 F FrekuensiGardu induk, GenTrafo
H G C
3 I ArusOutgoing Feeder,Incoming 20 kV, GenTrafo
H B F
4 P Daya aktifOutgoing Feeder ,Incoming 20 kV, Gen
Trafo
LN B C
5 Q Daya reaktifOutgoing Feeder ,Incoming 20 kV, GenTrafo
LN B C
6 V TeganganBusbar,Gen Trafo
H B F
KETERANGAN:
Logical Node pada TM apabila nilai didapat melalui perhitungan beberapa parameter.Hardwiring pada TM apabila nilai didapat melalui pengukuran dari sinyal masukan.* Per fasa untuk single phase.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 83/118
SPLN S5.003-1: 2014
69
3-3: Tap Changer Posit ion
Tabel 31. Daftar tap changer
No Kode Fungsi ImplementasiSumber
H/LN BagianD/B/G/P
JumlahF/C
1 TPI Tap position indication Trafo H B C/F*
Keterangan :* Per fasa untuk single phase.
3-4: Remote Control Digi ta l
Tabel 32. Daftar remote contro l dig i ta l
No Kode Fungsi Implementasi SumberH/LN BagianD/B/G/P JumlahF/C
1 ARO Auto reclose on/off Feeder LN B C
2 AVRAM Automatic Voltage Regulatorauto/manual
Trafo LN D C
3 CB Circuit breaker closed/opened
Kopel,OutgoingFeeder, Reaktor,Kapasitor, BusSection, Incoming 20kV
H D C
4 CAM Capacitor auto manual Kapasitor LN B C
5 DCBDummy circuit breakerclosed/opened
Gardu induk H G C
6 RPB Reset per bay
Kopel,OutgoingFeeder, Reaktor, Kapasitor, BusSection, Incoming 20
kV
H B C
7 TC Tap changer raise/lower Trafo H B C
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 84/118
SPLN S5.003-1: 2014
70
LAMPIRAN 4. Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi
DA-01: Konfigurasi Umum Pada Double Busbar
KONFIGURASI UMUM PADA DOUBLE BUSBAR
BUSBAR- A
DA- 01
BUSBAR- B
Q
P
GENERATOR
FEEDERCAPASITOR
L/R
Q
PQ
L/R I
QP
V
L/R
L/R L/R
I
PF
V(R)V(S)V(T)
V(R)V(S)V(T)
P
KOPEL
I (R)
I (S)I (T)
INCOMING 20 KV
Gambar 32. Konfigurasi umum pada double busbar
Tabel 33. Teleinformasi data untuk konfigurasi umum pada double busbar
Group Bay Data No Kode Fungsi Tipe Jmlh
GARDUINDUK
TM F Frekuensi 1
TSS
SLF Station level faulty A 1
IEDF Ied bay level faulty A 1
COM Communication faulty A 1
BUAL Building alarm A 1
VACF VAC failure A 1
VDCF VDC failure A 1
SF Supply failure A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 85/118
SPLN S5.003-1: 2014
71
Group Bay Data No Kode Fungsi Tipe Jmlh
TSD LBS Load break switch closed/opened I 1
RCD DCB Dummy CB closed/opened
BUSBAR
TM V Tegangan 2
TSSVS Voltage status I 2
BF Bay fault A 1
BAYOUTGOINGFEEDER
TM
AMF Amperes fault 4
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
TSS
DEF Directional earth fault A 1
AR Circuit breaker auto reclose success A 1
ARL Circuit breaker auto reclose lock out A 1
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
UFRT Under frequency relay trip A 1
UVRT Under voltage relay trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
ARO Auto reclose on/off I 1
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1LRBCU Local/remote for BCU I 1
RCD
ARO Auto reclose On/Off 1
CB Circuit breaker closed/opened 1
RPB Reset per bay 1
BAYINCOMING 20KV
TM
AMF Amperes fault 4
I Arus 3
P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1TM AMF Amperes fault 4
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 86/118
SPLN S5.003-1: 2014
72
Group Bay Data No Kode Fungsi Tipe Jmlh
KOPEL
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD
CB Circuit breaker closed/opened 1
RPB Reset per bay 1
BAYKAPASITOR
TM Q Daya reaktif 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD CB Circuit breaker closed/opened 1RPB Reset per bay 1
BAYGENERATOR
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A
1BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LRBCU Local/remote for BCU I 1
PSO Power station operated I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 87/118
SPLN S5.003-1: 2014
73
DA-02: Konfigurasi Umum Pada Single Busbar
KONFIGURASI UMUM PADA SINGLE BUSBAR
BUSBAR - A
DA- 02
Q
P
GENERATOR
CAPASITOR
L/R
Q
PQ
L/R I
QP
V
L/R
L/R
I
PF
V(R)V(S)
V(T)
P
I (R)I (S)I (T)
INCOMING 20 KV
FEEDER
Gambar 33. Konfigurasi umum pada single busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 88/118
SPLN S5.003-1: 2014
74
Tabel 34. Teleinformasi data untuk konfigurasi umum pada single busbar
Group Bay Data No Kode Fungsi Tipe Jmlh
GARDUINDUK
TM F Frekuensi 1
TSS
SLF Station level faulty A 1 IEDF Ied bay level faulty A 1
COM Communication faulty A 1
BUAL Building alarm A 1
VACF VAC failure A 1
VDCF VDC failure A 1
SF Supply failure A 1
TSD LBS Load break switch closed/opened I 1
RCD DCB Dummy CB closed/opened
BUSBAR
TM V Tegangan 1
TSSVS Voltage status I 1
BF Bay fault A 1
BAYOUTGOINGFEEDER
TM
AMF Amperes fault 4
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
TSS
DEF Directional earth fault A 1
AR Circuit breaker auto reclose success A 1
ARL Circuit breaker auto reclose lock out A 1
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
UFRT Under frequency relay trip A 1
UVRT Under voltage relay trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
ARO Auto reclose on/off I 1
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD
ARO Auto reclose On/Off 1
CB Circuit breaker closed/opened 1
RPB Reset per bay 1
TM
AMF Amperes fault 4
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1IOCT Instantaneous over current trip A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 89/118
SPLN S5.003-1: 2014
75
Group Bay Data No Kode Fungsi Tipe Jmlh
BAYINCOMING 20
KV
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/openedI 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
KOPEL
TM AMF Amperes fault 4
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD
CB Circuit breaker closed/opened 1
RPB Reset per bay 1
BAYKAPASITOR
TM Q Daya reaktif 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
BAYGENERATOR
TM
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
F Frekuensi 1
V Tegangan 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
BI Bus isolator switch closed/opened I 1CB Circuit breaker closed/opened I
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 90/118
SPLN S5.003-1: 2014
76
Group Bay Data No Kode Fungsi Tipe Jmlh
TSD
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LRBCU Local/remote for BCU I 1PSO Power station operated I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-01: Trafo 150/20 kV dan 70/20 kV Tipe 1
TRAFO 150/20 KV DAN 70/20 KVDB- 01
TYPE 1
RCC
DCC
L/RP
Q
I
PF
Gambar 34. Trafo 150/20 kV dan 70/20 kV tipe 1
Tabel 35. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 1
Group Bay Data No Kode Fungsi Tipe Jmh
Busbar
TM V Tegangan 2
TSSVS Voltage status I 2
BF Bay fault A 1
BAYINCOMING
20 KV
TM
AMF Amperes fault 4
I Arus 1
P Daya aktif 1
Q Daya reaktif 1PF Power factor 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 91/118
SPLN S5.003-1: 2014
77
Group Bay Data No Kode Fungsi Tipe Jmh
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A
1BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 0
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-02: Trafo 150/20 kV dan 70/20 kV Tipe 2
TRAFO 150/20 KV DAN 70/20 KVDB -02
TYPE 2
RCC
DCC
P
Q
I
PF
L/R
Gambar 35. Trafo 150/20 kV dan 70/20 kV tipe 2
Tabel 36. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 2
Group Bay Data No Kode Fungsi Tipe Jmh
Busbar
TM V Tegangan 2
TSSVS Voltage status I 2
BF Bay fault A 1
BAYINCOMING
TM AMF Amperes fault 4
I Arus 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 92/118
SPLN S5.003-1: 2014
78
Group Bay Data No Kode Fungsi Tipe Jmh
20 KV P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCD RPB Reset per bay 1
DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3
TRAFO 150/20 KV DAN 70/20 KVDB -03
TYPE 3
RCC
DCC
P
Q
I
PF
L/R
Gambar 36. Trafo 150/20 kV dan 70/20 kV tipe 3
Tabel 37. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 3
Group Bay Data No Kode Fungsi Tipe Jmh
Busbar
TM V Tegangan 1
TSS VS Voltage status I 1
BF Bay fault A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 93/118
SPLN S5.003-1: 2014
79
Group Bay Data No Kode Fungsi Tipe Jmh
BAYINCOMING 20 KV
TM
AMF Amperes fault 4
I Arus 1
P Daya aktif 1
Q Daya reaktif 1PF Power factor 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 0
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-04: Generator Pada Konfigurasi Double Busbar
GENERATOR PADA KONFIGURASI DOUBLE BUSBAR
BUSBAR - A
DB-04
BUSBAR - B
P
V
QI
PQ
L/R
Gambar 37. Generator pada konfigurasi double busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 94/118
SPLN S5.003-1: 2014
80
Tabel 38. Teleinformasi data untuk generator pada konfigurasi double busbar
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 1
TSS VS Voltage status I 1
BF Bay fault A 1
BAYGENERATOR
TM
I Arus 1
P Daya aktif 2
Q Daya reaktif 2
F Frekuensi 1
V Tegangan 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 0
ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LRBCU Local/remote for BCU I 1
PSO Power station operated I 1
RCD
CB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-05: Generator Pada Konfigurasi Single Busbar
GENERATOR PADA KONFIGURASI SINGLE BUSBAR
BUSBAR
DB-05
P
V
QI
PQ
L/R
Gambar 38. Generator pada konfigurasi single busbar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 95/118
SPLN S5.003-1: 2014
81
Tabel 39. Teleinformasi data untuk generator pada konfigurasi single busbar
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 1
TSSVS Voltage status I 1
BF Bay fault A 1
BAY
GENERATOR
TM
I Arus 1
P Daya aktif 2
Q Daya reaktif 2
F Frekuensi 1
V Tegangan 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 0
ES Earth switch closed/opened I 1
GUC Generator unit run/stop I 1
LRBCU Local/remote for BCU I 1
PSO Power station operated I 1
RCD
CB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-06: Feeder 20 kV Tipe 1
FEEDER 20 KVDB-06
TYPE 1
L/R
P
I ( R)
I ( S)
I ( T)
Gambar 39. Feeder 20 kV tipe 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 96/118
SPLN S5.003-1: 2014
82
Tabel 40. Teleinformasi data untuk feeder 20 kv tipe 1
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 2
TSS VS Voltage status I 2
BF Bay fault A 1
BAYOUTGOINGFEEDER
TM
AMF Amperes fault 4
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
TSS
DEF Directional earth fault A 1
AR Circuit breaker auto reclose success A 1
ARL Circuit breaker auto reclose lock out A 1
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
UFRT Under frequency relay trip A 1
UVRT Under voltage relay trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSD
ARO Auto reclose on/off I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCUI 1
RCD
ARO Auto reclose On/Off 1
CB Circuit breaker closed/opened I 1
RPB Reset per bay 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 97/118
SPLN S5.003-1: 2014
83
DB-07: Feeder 20 kV Tipe 2
FEEDER 20 KVDB-07
TYPE 2
L/R
P
I ( R)
I ( S)
I ( T )
Gambar 40. Feeder 20 kV tipe 1
Tabel 41. Teleinformasi data untuk feeder 20 kv tipe 1
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 1
TSSVS Voltage status I 1
BF Bay fault A 1
BAYOUTGOINGFEEDER
TM
AMF Amperes fault 4
I Arus 1
P Daya aktif 1
Q Daya reaktif 1
PF Power factor 1
TSS
DEF Directional earth fault A 1
AR Circuit breaker auto reclose success A 1
ARL Circuit breaker auto reclose lock out A 1
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
UFRT Under frequency relay trip A 1
UVRT Under voltage relay trip A 1
BRF Breaker fault A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 98/118
SPLN S5.003-1: 2014
84
Group Bay Data No Kode Fungsi Tipe Jmh
BF Bay fault A 1
TSD
ARO Auto reclose on/off I 1
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for BCU I 1
RCD
ARO Auto reclose On/Off 1
CB Circuit breaker closed/opened I 1
RPB Reset per bay 1
DB-09: Bus Section 20 kV Tipe 1
BUS SECTION 20 KVTYPE 1
DB- 09
L/R
Gambar 41. Bus sect ion 20 kV tipe 1
Tabel 42. Teleinformasi data untuk bus section 20 kv tipe 1
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 2
TSSVS Voltage status I 2
BF Bay fault A 1
TM AMF Amperes fault 4
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 99/118
SPLN S5.003-1: 2014
85
Group Bay Data No Kode Fungsi Tipe Jmh
BAYBUSSECTION
BRF Breaker fault A 1
BF Bay fault A 1
TSD
BI Bus isolator switch closed/opened I 2
CB Circuit breaker closed/opened I 1RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-10: Bus section 20 kV Tipe 2
BUS SECTION 20 KVTYPE 2
DB -10
L/R
Gambar 42. Bus sect ion 20 kV tipe 2
Tabel 43.Teleinformasi data untuk bus section 20 kv tipe 2
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 2
TSSVS Voltage status I 2
BF Bay fault A 1
TM AMF Amperes fault 4
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1IOCT Instantaneous over current trip A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 100/118
SPLN S5.003-1: 2014
86
Group Bay Data No Kode Fungsi Tipe Jmh
BAYBUSSECTION
BRF Breaker fault A 1
BF Bay fault A 1
TSD
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-11: Kopel
KOPELDB -11
L/R
Gambar 43. Kopel
Tabel 44. Teleinformasi data untuk kopel
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 2
TSSVS Voltage status I 2
BF Bay fault A 1
BAY
TM AMF Amperes fault 4
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A
1IOCT Instantaneous over current trip A 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 101/118
SPLN S5.003-1: 2014
87
Group Bay Data No Kode Fungsi Tipe Jmh
KOPEL BRF Breaker fault A 1
BF Bay fault A 1
TSD
CB Circuit breaker closed/opened I 1
RACK Circuit breaker rackin/rackout I 1ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
DB-12: Capacitor Bay
CAPACITOR BAYDB-12
Q L/R
Gambar 44. Capaci tor bay
Tabel 45. Teleinformasi data untuk capasitor bay
Group Bay Data No Kode Fungsi Tipe Jmh
BUSBAR
TM V Tegangan 2
TSSVS Voltage status I 2
BF Bay fault A 1
BAYKAPASITOR
TM Q Daya reaktif 1
TSS
GFT Ground fault trip A 1
IGFT Instantaneous ground fault trip A 1
OCT Over current trip A 1
IOCT Instantaneous over current trip A 1
BRF Breaker fault A 1
BF Bay fault A 1
TSDBI Bus isolator switch closed/opened I 2CB Circuit breaker closed/opened I 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 102/118
SPLN S5.003-1: 2014
88
Group Bay Data No Kode Fungsi Tipe Jmh
RACK Circuit breaker rackin/rackout I 1
ES Earth switch closed/opened I 1
LRBCU Local/remote for bcu I 1
RCDCB Circuit breaker closed/opened 1
RPB Reset per bay 1
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 103/118
SPLN S5.003-1: 2014
89
LAMPIRAN 5. Struktur Informasi
STRUKTUR INFORMASI
Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilanbagian, yaitu:
A B C D E F G H I
Bagian A: Nomor ID, terdiri dari 6 digit (sebagai primary key )Bagian B: Time stamp, sebanyak karakter 23 karakterBagian C: Nama GI/GH/GT/KP, sebanyak 20 karakterBagian D: Level tegangan, sebanyak 5 karakterBagian E: Nama bay / feeder, sebanyak 20 karakterBagian F: Kode nama peralatan atau nama alarm atau nama elemen, sebanyak 5
karakterBagian G: Status peralatan atau status alarm, sebanyak 15 karakterBagian H: Nama user yang melakukan aksi (seperti remote control, dan sebagainya),
sebanyak 10 karakterBagian I: Prioritas alarm, sebanyak 8 karakter
Struktur di atas ditentukan dalam field yang berbeda.Contohnya dapat dilihat pada tabel 62.
Tabel 46. Struktur informasi
A B C D E F G H IRCC Cawang110007 02/03/2007 11:10:05.320 Cawang 150 Gandul-1 BI1 Close Class-3
110009 05/03/2007 07:00:55.115 Gandul 150 Cawang-1 ARO Appear Class-2
RCC Waru140104 11/04/2007 17:44:21.220 Rungkut 150 Waru-1 LT Disappear Class-1
140085 12/04/2007 20:11:51.312 Waru 150 Bangil-1 CB Invalid Class-4
DCC Pasuruan430011 25/04/2007 00:30:35.000 Gondang Wetan 20 Bromo CB Open Adi Class-1430012 19/11/2007 10:00:05.520 Gondang Wetan 20 Semeru CBTR Appear Class-1
1. A. Nomor ID
Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yangmenyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTUbersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut
A1 A2
Bagian A1: Kode areaBagian A2: Nomor RTU
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 104/118
SPLN S5.003-1: 2014
90
Kode area
Kode area yang terdiri dari 3 karakter adalah sebagai berikut:NCC : 900
IRCC : x00IRCC Jawa-Bali : 100IRCC Sumatera : 200IRCC Kalimantan : 300IRCC Sulawesi : 400IRCC di Indonesia Timur : 500
RCC di Jawa-Bali : 1xxRCC Cawang : 110RCC Cigereleng : 120RCC Ungaran : 130
RCC Waru : 140RCC di Sumatera : 2xxRCC Medan : 210RCC Padang : 220RCC Palembang : 230RCC di Kalimantan : 3xxRCC Banjarbaru : 310RCC Balikpapan : 320RCC di Sulawesi : 4xxRCC Makassar : 410RCC Manado : 420RCC di Indonesia Timur : 5xx
IDCC : x00IDCC Jawa-Bali : 100, 200, 300, 400IDCC Sumatera : 500, 600IDCC Kalimantan : 700IDCC Sulawesi : 800IDCC di Indonesia Timur : 900
DCC di Jakarta : 0xx – 1xxDCC daerah Jawa bagian Barat : 2xxDCC daerah Jawa bagian Tengah : 3xxDCC daerah Jawa bagian Timur dan Bali : 4xx
DCC daerah Sumatera : 5xx – 6xxDCC daerah Kalimantan : 7xxDCC daerah Sulawesi : 8xxDCC daerah Indonesia Timur : 9xx
Nomor RTU
Nomor RTU terdiri dari 3 digit (001 – 999)
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 105/118
SPLN S5.003-1: 2014
91
B. Time stamp
Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakteratau sampai dengan orde milidetik). Contohnya:
25/04/2007 00:30:35.000
19/11/2007 10:00:05.520
C. Nama GI/GH/GT
Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter).Contohnya adalah sebagai berikut:
CawangGandulGondang WetanRungkutWaru
Cawang : menyatakan GI Cawang (dikontrol oleh RCC Cawang).Gandul : menyatakan GI Gandul (dikontrol oleh RCC Cawang).Waru : menyatakan GI Waru (dikontrol oleh RCC Waru).Rungkut : menyatakan GI Rungkut (dikontrol oleh RCC Waru).Gondang Wetan : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC
Pasuruan).
D. Level Tegangan
Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada tabel 47.
Tabel 47. Level tegangan
Tegangan Level Tegangan
500 kV 500
275 kV 275
150 kV 150
66 kV 66
30 kV 30
20 kV 20
11 kV 11
6.6 kV 6
3.3 KV 3
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 106/118
SPLN S5.003-1: 2014
92
E. Nama Bay / Feeder
Nama Bay/Feeder terdiri dari 20 karakter. Contohnya dapat dilihat pada tabel 48.
Tabel 48. Nama bay atau feeder
Nama Bay / Feeder Kode
Pusat Listrik
Pusat Listrik Tenaga Air PLTA
Pusat Listrik Tenaga Diesel PLTD
Pusat Listrik Tenaga Gas PLTG
Pusat Listrik Tenaga Panas Bumi PLTP
Pusat Listrik Tenaga Nuklir PLTN
Pusat Listrik Tenaga Uap PLTU
Pusat Listrik Gas/Uap (Combine Cycle) PLTGU
Pusat Listrik Tenaga Mikrohidro PLTMH
Pusat Listrik Tenaga Angin/Bayu PLTB
Pusat Listrik Tenaga Surya PLTS
Peralatan di Gardu Induk
LineBay (FeederBay) Format penulisan: IRCC/RCC:
Nama GI lawan + ”-” + nomor
penghantar. Contohnya:o Gandul-1
o Cawang-1 DCC:
Nama Feeder. Contohnya:o Bromoo Semeru
Bay ke Unit Generator UNIT
Busbar BUSBAR
Kopel (Bus Tie) KOPEL
Bus Section BUSSECT
Trafo TRAFOx (X adalah Kode Tegangandari primer dan sekunder trafo)
Diameter DAMTR
Shunt Reactor SHTXL
Shunt Capacitor SHTXC
Cadangan SPARE
Nama Bay
Bay 500 kV diameter 1 busbar A 7A1
Bay 500 kV diameter 3 antara busbar Adan B
7AB3
Bay 500 kV diameter 5 busbar B 7B5
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 107/118
SPLN S5.003-1: 2014
93
Kode tegangan dari primer dan sekunder trafo dapat dilihat pada tabel 49.
Tabel 49. Kode tegangan dari primer dan sekunder trafo
Tegangan (KV) Range IEC
Tegangan Rendah (TR) < 1 kV NTegangan Menengah (TM) 1 sampai<6 kV M
Tegangan Menengah (TM) 6 sampai <10 kV L
Tegangan Menengah (TM) 10 sampai <20 kV K
Tegangan Menengah (TM) 20 sampai <30 kV J
Tegangan Menengah (TM) 30 sampai <45 kV H
Tegangan Tinggi (TT) 45 sampai <60 kV G
Tegangan Tinggi (TT) 60 sampai <110 kV F
Tegangan Tinggi (TT) 110 sampai <220 kV E
Tegangan Ekstra Tinggi (TET) 220 sampai <380 kV D
Tegangan Ekstra Tinggi (TET) 380 sampai ≤ 420 kV CTegangan Ekstra Tinggi (TET) > 420 kV B
F. Kode Nama Peralatan atau Nama Alarm atau Nama Elemen
Kode nama peralatan atau nama alarm atau nama elemen terdiri dari maksimal 5karakter. Contohnya dapat dilihat pada tabel 50.
Tabel 50. Kode nama peralatan/alarm /elemen
Nama Kode
Circuit Breaker CB
Bus Isolator #1 BI1
Bus Isolator #2 BI2
Line Isolator LI
Ground Fault GF
Over Current OC
Line Trip LT
Breaker Fault BRF
Power Supply Faulty PSF
Daya MW PDaya MVAr Q
Arus I
Load Break Switch LBS
Recloser REC
Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal, telemeasurement atau r emote kontrol seperti ditunjukan pada Lampiran A-D).
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 108/118
SPLN S5.003-1: 2014
94
G. Status Peralatan atau Status Alarm
Status peralatan atau status alarm terdiri dari 15 karakter, menunjukkan status dariperalatan atau alarm pada bagian E.Contohnya adalah sebagai berikut:
- Close;- Open;- Invalid;- Appear;- Disappear;- On;- Off.
H. Nama user yang melakukan aksi
Nama user terdiri dari maksimal 10 karakter, menunjukkan nama user yang login padasaat melakukan aksi tertentu seperti Remote Control , Overall Check , start dan stopperangkat keras, out of service RTU dan Inter Center Link , dan sebagainya.
Contohnya adalah sebagai berikut:
TriLukmanJufriJokoParlinRiko
I. Prioritas Alarm
Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1merupakan kelas alarm yang menempati prioritas paling tinggi.
Contohnya sebagai berikut:
Class-1Class-2Class-3Class-4
Struktur Informasi Khusus
Penamaan Pemutus Tenaga Pada Gardu Induk 1 ½ Breaker.
Struktur informasi khusus untuk pemutus tenaga pada gardu induk 1 ½ breaker dipakaiuntuk tujuan komunikasi verbal diantara operator. Kode tersebut hanya ditampilkan diVDU (Video Display Unit ), dan dipergunakan di dalam database. Struktur informasidinyatakan dengan susunan sebagai berikut:
X Y Z
Bagian X: kode referensi teganganBagian Y: kode nama CB
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 109/118
SPLN S5.003-1: 2014
95
Bagian Z: nomor diameter
Contoh: A untuk breaker yang terhubung langsung ke busbar AB untuk breaker yang terhubung langsung ke busbar B AB untuk breaker yang terhubung ke breaker A dan breaker B
Contohnya dapat dilihat pada Gambar 4545.
Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4
Gambar 45. Struktur informasi khusus (bay diameter)
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 110/118
SPLN S5.003-1: 2014
96
Contoh :
GITET 500 kVSAGULING
UNIT 2 UNIT 3 UNIT 4UNIT 1
CIRATA 1 CIRATA 2
BANDUNG SELATAN 2
BUSBAR A
BUSBAR B
CIBINONG 1
7A1
7AB1
7B1
~ ~
7A3
7AB3
7B3
7AB4
7B4
7AB5
7B5
BANDUNGSELATAN 1
~ ~
CIBINONG 2
7A2
7AB2
7B2
Gambar 46. Struktur informasi khusus (gardu induk 1½ breaker )
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 111/118
SPLN S5.003-1: 2014
97
LAMPIRAN 6. Simbol dan Warna
Simbol-simbol gambar yang digunakan mengacu pada gambar 47.
SIMBOL GAMBAR
Generator
Circuit Breaker
Circuit Breaker Rack
Isolating Switch
Earthing Switch
Current Transformer
Voltage Transformer
Reaktor
Capacitor Voltage
Transformer
Trafo Daya Dua Belitan
Trafo Daya Tiga Belitan
Arus
Tegangan
Frekuensi
Daya aktif
Daya reaktif
Tap Position Indication
Remote Control Digital
Telesignal Single
Local/ Remote
Load Frequency Control
I
V
F
P
Q
TPI
RCD
TSS
L/R
LFC(Po, Pr,N)
Kapasitor Remote Control AnalogRCA
Telesignal DoubleTSS
Surge /Lightning Arrester
(Disconnecting Switch)
(3 phases )
PBO
Pemutus Balik Otomatis
Load Break Switch
Gardu Distribusi
Cut out fuse
Inverter
Rectifier
Battery
Battery
AGC Automatic Gain Control
Neutral Ground Resistor
Gambar 47. Simbol gambar
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 112/118
SPLN S5.003-1: 2014
98
Tampilan-tampilan status yang digunakan mengacu pada gambar 48.
Tampilan Status
GENERATOR
ITEMS SYMBOL R E M A R K
CB CLOSED
CB OPENED
DS CLOSED
DS OPENED
ES CLOSED
ES OPENED
RACKED IN CB CLOSED
Busbar ' s color, filled
Busbars color, blank
TRANSF. 2 WINDINGS
TRANSF. 3 WINDINGS
REACTOR
CAPACITOR
LBS CLOSED
LBS OPENED
RACKED OUT CB CLOSED
Feeder’s color
Feeder’s color
Feeder’s color , filled
Feeder’s color blank
Ground’s color
Feeder’s color
Feeder’s color , filled
Feeder’s color , filled
Feeder’s color
Feeder’s color
Feeder’s color
Feeder’s color
Feeder’s color
VOLTAGE STATUS: LIVE
DEAD
CB INVALID Purple,
LBS INVALID Purple
DS INVALID Purple, half- filled
ES INVALID Purple
RACKED INVALID CB CLOSED Feeder’s color , filled
RACKED IN CB OPENED
RACKED OUT CB OPENED
Feeder’s color , blank
Feeder’s color , blank
RACKED INVALID CB OPENED Feeder’s color , blank
RACKED IN CB INVALID
RACKED OUT CB INVALID
Feeder’s color , half-filled
Feeder’s color , half- filled
RACKED INVALID CB INVALID Feeder’s color , half- filled
CB UNKNOWN Orange, Half-filled
Half-filled
DS UNKNOWN Orange, half-filled
ES UNKNOWN Orange
Gambar 48. Tampilan status
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 113/118
SPLN S5.003-1: 2014
99
WARNA TAMPILAN
Tabel 51 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitordan layar tayang. Pewarnaan SLD yang dinamis didasarkan atas dua sumber yaitu:
- Secara logika (berdasarkan posisi PMT dan PMS) dan pengukuran tegangan.- Secara logika (berdasarkan posisi PMT dan PMS) untuk bagian yang tidakmemiliki VT.
Tabel 51. Warna tampilan
URAIAN WARNA (R,G,B)
Single line diagram 500 kV Biru (0,100,255)Single line diagram 275 kV Biru-muda (0,200,255)Single line diagram 150 kV Merah (255,0,0)Single line diagram 66 kV Kuning (255,255,0)Single line diagram 30 kV Hijau (0, 255, 0)Single line diagram 20 kV Coklat (200, 150, 0)Single line diagram 11 kV Abu-abu (180, 180, 180)Single line diagram 6 kV Merah muda (255, 150, 180)Single line diagram 3,3 kV Hijau-muda (0, 255, 150)
All devices Warna BusbarInvalid device Ungu dan perubahan simbol (220, 0, 255)Device saat loss connection (out of poll) Oranye (255, 150, 50)Background color Hitam (0, 0, 0)Ground color Biru-tua (10, 10, 180)Kondisi tidak bertegangan Putih (255, 255, 255)Perubahan status karena gangguan Frame CB warna merah, blinkingPerubahan status karena local dari gardu induk Warna Busbar, blinking + karakter”L” Perubahan status karena r emote dari Warna Busbar, blinking dispatcherTelemetering Putih (255, 255, 255)
Invalid telemetering Ungu (220, 0, 255)Unknown Oranye (255, 150, 50)Telesignal Alarm :
Off : sesuai warna latar kotak annunciator Aktif : Terisi solid warna Merah, blinking.
Setelah di acknowledge tidak blinking.
Keterangan:
Untuk change of state gangguan, setelah acknowledge blinking hilang, warna merahpada frame CB mengikuti warna busbar.
Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan warna
pada single line diagram level tegangan terdekat. Warna jaringan sesuai dengan feeder colouring .
Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol danwarna.
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 114/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 115/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 116/118
Pengelola Standardisasi :
PT PLN (Persero) Pusat Penelitian dan Pengembangan Ketenagalistrikan
Jl. Durentiga, Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762,
www.pln-litbang.co.id
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 117/118
7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan
http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 118/118