7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 1/118  i TELEINFORMASI DATA DAN TAMPILAN UNTUK SISTEM OTOMASI GARDU INDUK Bagian 1: FUNGSI OPERASI PT PLN (Persero) Jl. Trunojoyo Blok M-1/135 Kebayoran Baru Jakarta Selatan 12160 STANDAR PT PLN (PERSERO)  SPLN S5.003-1: 2014 Lampiran Keputusan Direksi PT PLN (Persero) No. 0952.K/DIR/2014 

Transcript of Spln s5.003-1 2014 Tele Informasi Plan

Page 1: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 1/118

 

i

TELEINFORMASI DATA DAN TAMPILANUNTUK SISTEM OTOMASI GARDU INDUK

Bagian 1:FUNGSI OPERASI

PT PLN (Persero)Jl. Trunojoyo Blok M-1/135 Kebayoran Baru

Jakarta Selatan 12160

STANDARPT PLN (PERSERO)  

SPLN S5.003-1: 2014

Lampiran Keputusan DireksiPT PLN (Persero) No. 0952.K/DIR/2014 

Page 2: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 2/118

 

Page 3: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 3/118

 

TELEINFORMASI DATA DAN TAMPILANUNTUK SISTEM OTOMASI GARDU INDUK

Bagian 1:FUNGSI OPERASI

STANDARPT PLN (PERSERO)  

SPLN S5.003-1: 2014

Lampiran Keputusan DireksiPT PLN (PERSERO) No. 0952. K/DIR/2014 

PT PLN (Persero)

Jl. Trunojoyo Blok M-1/135 Kebayoran BaruJakarta Selatan 12160

Page 4: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 4/118

 

Page 5: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 5/118

 

TELEINFORMASI DATA DAN TAMPILANUNTUK SISTEM OTOMASI GARDU INDUK

Bagian 1:FUNGSI OPERASI

Disusun oleh :

Kelompok Bidang SCADA Standardisasidengan Keputusan Direksi

PT PLN (Persero)

No. 0448.K/DIR/2014 

Kelompok Kerja StandardisasiTeleinformasi Data Untuk Sistem Otomasi Gardu Induk

dengan Keputusan KepalaPT PLN (Persero) Puslitbang Ketenagalistrikan 

No. 0236.K/PUSLITBANG/2014 

Diterbitkan oleh :

PT PLN (Persero)Jl. Trunojoyo Blok M -1/135, Kebayoran Baru

Jakarta Selatan 12160

Page 6: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 6/118

Page 7: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 7/118

Page 8: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 8/118

 

Susunan Kelompok Bidang SCADA StandardisasiKeputusan Direksi PT PLN (Persero)

No. 0448.K/DIR/2014

1. Ir. I Putu Riasa : Sebagai Ketua merangkap Anggota

2. Tri Hardimasyar,ST,MSc : Sebagai Sekretaris merangkap Anggota

3. Agus Harya Maulana, ST, MT : Sebagai Anggota

4. Novrizal Erdiyansyah, ST, MSc : Sebagai Anggota

5. Ir. Hesti Sayoga : Sebagai Anggota

6. Ir. Ruly Chaerul : Sebagai Anggota

7. Ir. Ridwan Nainggolan : Sebagai Anggota

8. A Sugeng Sugarjito,ST : Sebagai Anggota

9. Made Yusadana, ST, MSc : Sebagai Anggota10. Denden Ruhdani, ST : Sebagai Anggota

11. Erwan Herdiyanto, ST, MSc : Sebagai Anggota

12. Muchsin Akuba Gani, ST : Sebagai Anggota

13. Akbar Patonangi, ST : Sebagai Anggota

Susunan Kelompok Kerja StandardisasiTeleinformasi Data Untuk Sistem Otomasi Gardu Induk

Keputusan Kepala PT PLN (Persero) Puslitbang KetenagalistrikanNo. 0236.K/PUSLITBANG/2014

1. Joko Pitoyo, ST : Sebagai Ketua merangkap Anggota

2. Tri Hardimasyar, ST, M.Sc : Sebagai Sekretaris merangkap Anggota

3. Suci Rositawati, ST : Sebagai Anggota

4. Lukman Hakim, ST : Sebagai Anggota

5. Ricci Fajar, ST : Sebagai Anggota

6. Riko Ramadhano Budiawan, ST : Sebagai Anggota

7. Amiruddin, ST : Sebagai Anggota

8. Lugito Nurwahono, ST : Sebagai Anggota

9. Novrizal Erdiansyah, ST,MSc : Sebagai Anggota

Page 9: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 9/118

  SPLN S5.003-1: 2014

i

Daftar Isi

Daftar Isi ............................................................................................................................. iDaftar Gambar ................................................................................................................... ii

Daftar Tabel ...................................................................................................................... iii

Daftar LAMPIRAN ............................................................................................................. iv

Prakata ............................................................................................................................. v

1  Ruang Lingkup ............................................................................................................. 1 

2  Tujuan .......................................................................................................................... 1 

 Acuan Normatif ............................................................................................................. 1 

4  Istilah dan Definisi ........................................................................................................ 2 

4.1 

 Alarm ................................................................................................................... 2 

4.2  Control center ...................................................................................................... 2 

4.3 

Distribution control center  (DCC) ......................................................................... 2 

4.4  Feeder colouring .................................................................................................. 2 

4.5  Gardu hubung ...................................................................................................... 2 

4.6  Gardu induk ......................................................................................................... 2 

4.7  Gardu tengah ....................................................................................................... 2 

4.8  Human Machine Interface (HMI) .......................................................................... 2

 

4.9  Inter Distribution Control Center  (IDCC) ............................................................... 3 

4.10 

Inter Regional Control Center  (IRCC) .................................................................. 3 

4.11  Maintenance Center  ............................................................................................ 3 

4.12 

National Control Center  (NCC) ............................................................................ 3 

4.13  Operator .............................................................................................................. 3 

4.14 

Regional Control Center  (RCC) ........................................................................... 3 

4.15  Regu pemeliharaan ............................................................................................. 3 

4.16  Remote station .................................................................................................... 3 

4.17  Sistem Otomasi Gardu Induk (SOGI) ................................................................... 3 

4.18  Supervisory Control and Data Acquisition (SCADA) ............................................ 3 

4.19  Telecontrol ........................................................................................................... 4 

4.20  Telesignal ............................................................................................................ 4 

4.21 

Telemetering ........................................................................................................ 4 

5  Umum ........................................................................................................................... 4 

5.1 

Fasilitas SCADA untuk SOGI ............................................................................... 4 

5.2  Teleinformasi data (TID) ...................................................................................... 4 

5.3 

Struktur informasi................................................................................................. 4 

5.4  Simbol dan warna ................................................................................................ 5 

5.5  Tampilan HMI Fungsi Operasi ............................................................................. 5 

5.6  Gambar tipikal HMI Fungsi Operasi ..................................................................... 5 

5.7  Penjelasan gambar tipikal HMI Fungsi Operasi ................................................... 7 

Perbatasan Kebutuhan Teleinformasi Data .................................................................. 9 

6.1  Perbatasan Kebutuhan Teleinformasi Data antara IRCC dan RCC ..................... 9 

6.2 

Perbatasan kebutuhan teleinformasi data antara RCC dan DCC ....................... 11 

Page 10: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 10/118

SPLN S5.003-1: 2014

ii

Daftar Gambar

Gambar 1. Tipikal HMI fungsi operasi ................................................................................ 5 

Gambar 2. Topologi ........................................................................................................... 6 

Gambar 3. Single Diagram fungsi operasi ......................................................................... 7 Gambar 4. Tipikal HMI fungsi operasi ................................................................................ 8 

Gambar 5. Batas wewenang antara IRCC dengan RCC (Tipe-a) ...................................... 9 

Gambar 6. Batas wewenang antara IRCC dengan RCC (Tipe-b) .................................... 10 

Gambar 7. Batas wewenang antara RCC dengan DCC .................................................. 11 

Gambar 8. Konfigurasi SLD 1 ½ breaker ......................................................................... 18 

Gambar 9. Konfigurasi umum pada 1 ½ breaker  150 kV ................................................. 22 

Gambar 10. Konfigurasi umum pada double busbar ........................................................ 26 

Gambar 11. Konfigurasi umum pada single busbar ......................................................... 30 

Gambar 12. Interbus transformer (secondary side connected to 1½ breaker) ................ 34 

Gambar 13. Interbus transformer (secondary side connected to double busbar ) ............. 36 

Gambar 14. Interbus transformer (secondary side connected to single busbar ) ............. 38 

Gambar 15. Secondary side  terhubung 1½ breaker dilengkapi dhunt reaktor pada

kumparan tersier ............................................................................................................. 40 

Gambar 16. Secondary side connected to double busbar   dilengkapi shunt reaktor pada

kumparan tersier ............................................................................................................. 42 

Gambar 17. Secondary side connected to single busbar  dilengkapi shunt reaktor pada

kumparan tersier ............................................................................................................. 44 

Gambar 18. Bay  trafo tenaga pada konfigurasi 1½ breaker  ............................................. 46 

Gambar 19. Bay  trafo tenaga pada konfigurasi double busbar  ........................................ 48 

Gambar 20. Bay  trafo tenaga pada konfigurasi single busbar  ........................................ 50 

Gambar 21. Bay reaktor pada konfigurasi 1 ½ breaker.................................................... 52 

Gambar 22. Bay  reaktor pada konfigurasi double busbar  ................................................ 53 

Gambar 23. Bay  reaktor pada konfigurasi single busbar  ................................................. 54 

Gambar 24. Bay capasitor  pada konfigurasi double busbar  ............................................. 55 

Gambar 25. Bay capasitor  pada konfigurasi single busbar  .............................................. 56 

Gambar 26. Bay penghantar pada konfigurasi 1 ½ breaker  ............................................. 57 

Gambar 27. Bay  penghantar pada konfigurasi double busbar  ......................................... 58 

Gambar 28. Bay penghantar pada konfigurasi single busbar  .......................................... 60 

Gambar 29. Bay  penghantar paralel dengan reaktor pada konfigurasi double busbar  ..... 62 

Gambar 30. Bay  penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker  ...... 63 

Gambar 31. Bay kopel pada konfigurasi double busbar ................................................... 65 

Gambar 32. Konfigurasi umum pada double busbar ........................................................ 70 Gambar 33. Konfigurasi umum pada single busbar ........................................................ 73 

Gambar 34. Trafo 150/20 kV dan 70/20 kV tipe 1 ............................................................ 76 

Gambar 35. Trafo 150/20 kV dan 70/20 kV tipe 2 ............................................................ 77 

Gambar 36. Trafo 150/20 kV dan 70/20 kV tipe 3 ............................................................ 78 

Gambar 37. Generator pada konfigurasi double busbar  .................................................. 79 

Gambar 38. Generator pada konfigurasi single busbar .................................................... 80 

Gambar 39. Feeder  20 kV tipe 1 ..................................................................................... 81 

Gambar 40. Feeder  20 kV tipe 1 ..................................................................................... 83 

Gambar 41. Bus section 20 kV tipe 1 .............................................................................. 84 

Gambar 42. Bus section 20 kV tipe 2 .............................................................................. 85 

Gambar 43. Kopel ........................................................................................................... 86 

Gambar 44. Capacitor bay .............................................................................................. 87 

Page 11: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 11/118

  SPLN S5.003-1: 2014

iii

Gambar 45. Struktur informasi khusus (bay diameter) ..................................................... 95 

Gambar 46. Struktur informasi khusus (gardu induk 1½ breaker ) .................................... 96 

Gambar 47. Simbol gambar ............................................................................................. 97 

Gambar 48. Tampilan status ............................................................................................ 98 

Daftar Tabel

Tabel 1. Daftar telesignal fungsi operasi .......................................................................... 12

Tabel 2. Daftar telemeasurement ..................................................................................... 16

Tabel 3. Daftar tap changer position ................................................................................ 17

Tabel 4. Daftar remote control ......................................................................................... 17

Tabel 5. Teleinformasi data untuk konfigurasi umum pada 1½ breaker ........................... 19

Tabel 6.Teleinformasi data untuk konfigurasi umum pada 1½ breaker  ........................... 23

Tabel 7. Teleinformasi data untuk konfigurasi umum pada double busbar ....................... 27

Tabel 8. Teleinformasi data untuk konfigurasi umum pada single busbar  ........................ 31

Tabel 9. Teleinformasi data untuk interbus transformer  (secondary side connected  to 1½

breaker ) ........................................................................................................................... 35

Tabel 10. Teleinformasi data untuk interbus transformer   (secondary side connected to

double busbar) ................................................................................................................. 37

Tabel 11. Teleinformasi data untuk interbus transformer   (secondary side connected to

single busbar) .................................................................................................................. 39

Tabel 12. Teleinformasi data untuk interbus transformer  (secondary side connected to 1½

breaker  dilengkapi shunt  reaktor pada kumparan tersier) ................................................ 41

Tabel 13.Teleinformasi data untuk interbus transformer   (secondary side connected to

double busbar  dilengkapi shunt  reaktor pada kumparan tersier) ...................................... 43

Tabel 14. Teleinformasi data untuk interbus transformer (secondary side connected to single busbar  dilengkapi shunt  reaktor pada kumparan tersier) ....................................... 45

Tabel 15. Teleinformasi data untuk bay trafo tenaga pada konfigurasi 1½ breaker  .......... 47

Tabel 16. Teleinformasi data untuk bay  trafo tenaga pada konfigurasi double busbar  ..... 49

Tabel 17. Teleinformasi data untuk bay  trafo tenaga pada konfigurasi single busbar  ....... 51

Tabel 18. Teleinformasi data untuk bay reaktor pada konfigurasi 1 ½ breaker  ................. 52

Tabel 19. Teleinformasi data untuk bay  reaktor pada konfigurasi double busbar  ............. 53

Tabel 20. Teleinformasi data untuk bay  reaktor pada konfigurasi single busbar  ............... 54

Tabel 21. Teleinformasi data untuk bay  kapasitor pada konfigurasi double busbar  .......... 55

Tabel 22. Teleinformasi data untuk bay  kapasitor pada konfigurasi single busbar  ........... 56

Tabel 23. Teleinformasi data untuk bay penghantar pada konfigurasi 1 ½ breaker  .......... 57

Tabel 24. Teleinformasi data untuk bay  penghantar pada konfigurasi double busbar  ...... 59Tabel 25. Teleinformasi data untuk bay  penghantar pada konfigurasi single busbar  ........ 60

Tabel 26. Teleinformasi data untuk bay  penghantar serial dengan reaktor pada konfigurasi

double busbar .................................................................................................................. 62

Tabel 27. Teleinformasi data untuk bay   penghantar paralel dengan 1 reaktor pada

konfigurasi 1½ breaker .................................................................................................... 64

Tabel 28. Teleinformasi data untuk bay  kopel pada konfigurasi double busbar  ................ 65

Tabel 29. Daftar telesignal  distribusi ................................................................................ 66

Tabel 30. Daftar telemeasurement ................................................................................... 68

Tabel 31. Daftar tap changer ........................................................................................... 69

Tabel 32. Daftar remote control digital ............................................................................. 69

Tabel 33. Teleinformasi data untuk konfigurasi umum pada double busbar  ..................... 70Tabel 34. Teleinformasi data untuk konfigurasi umum pada single busbar  ...................... 73

Page 12: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 12/118

SPLN S5.003-1: 2014

iv

Tabel 35. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 1 .......................... 76

Tabel 36. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 2 .......................... 77

Tabel 37. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 3 .......................... 78

Tabel 38. Teleinformasi data untuk generator pada konfigurasi double busbar ............... 80

Tabel 39. Teleinformasi data untuk generator pada konfigurasi single busbar ................. 81Tabel 40. Teleinformasi data untuk feeder 20 kv tipe 1.................................................... 82

Tabel 41. Teleinformasi data untuk feeder  20 kv tipe 1.................................................... 83

Tabel 42. Teleinformasi data untuk bus section 20 kv tipe 1 ............................................ 84

Tabel 43.Teleinformasi data untuk bus section 20 kv tipe 2 ............................................. 85

Tabel 44. Teleinformasi data untuk kopel ........................................................................ 86

Tabel 45. Teleinformasi data untuk capasitor bay ............................................................ 87

Tabel 46. Struktur informasi ............................................................................................ 89

Tabel 47. Level tegangan ................................................................................................ 91

Tabel 48. Nama bay atau feeder ..................................................................................... 92

Tabel 49. Kode tegangan dari primer dan sekunder trafo ................................................ 93

Tabel 50. Kode nama peralatan/alarm/elemen ................................................................ 93Tabel 51. Warna tampilan ............................................................................................... 99 

Daftar LAMPIRAN

LAMPIRAN 1. Daftar Teleinformasi ................................................................................. 12 

LAMPIRAN 2. Teleinformasi pada Berbagai Konfigurasi Gardu Induk ............................. 18 

LAMPIRAN 3. Daftar Teleinformasi (Distribusi) ............................................................... 66 

LAMPIRAN 4. Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi ................... 70 

LAMPIRAN 5. Struktur Informasi ..................................................................................... 89 

LAMPIRAN 6. Simbol dan Warna .................................................................................... 97 

Page 13: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 13/118

  SPLN S5.003-1: 2014

v

Prakata

Standar SCADA ini merupakan pedoman dalam rangka mengikuti perkembanganteknologi SCADA dan Telekomunikasi.

Standar ini mencakup definisi, perangkat keras, perangkat lunak, kebutuhan teleinformasidata, pengujian, kinerja, kajian kelayakan dalam pembangunan, operasi danpemeliharaan yang memiliki hubungan dengan sistem SCADA.

Standar ini terdiri dari dua bagian, yaitu:

1. S5.003-1: 2014 Teleinformasi Data dan Tampilan Untuk Sistem Otomasi Gardu IndukBagian 1: Fungsi Operasi

2. S5.003-2: 2014 Teleinformasi Data dan Tampilan Untuk Sistem Otomasi Gardu IndukBagian 2: Fungsi Pemeliharaan

Standar ini harus menjadi acuan dalam setiap perencanaan, pembangunan, operasi danpemeliharaan sistem SCADA di PT PLN (Persero) secara nasional.

Page 14: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 14/118

Page 15: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 15/118

SPLN S5.003-1: 2014

1

Teleinformasi Data dan Tampilan UntukSistem Otomasi Gardu Induk

Bagian 1: Fungsi Operasi

1 Ruang Lingkup

Teleinformasi data terdiri dari telecontrol , telesignal dan telemetering . Sesuai denganperkembangan teknologi peralatan di Gardu Induk, teleinformasi data ini dibuat untukkepentingan operasi dan kebutuhan pemeliharaan pada Gardu Induk otomasi. Standar inidimaksudkan untuk menetapkan standar teleinformasi data yang diaplikasikan untukkebutuhan operasi sistem tenaga listrik dan mencakup sistem transmisi dan sistemdistribusi.

Standar ini, berlaku untuk sistem SCADA:

a. National Control Center , disingkat NCC;b. Inter Regional Control Center , disingkat IRCC;c. Regional Control Center , disingkat RCC;d. Inter Distribution Control Center , disingkat IDCC;e. Distribution Control Center , disingkat DCC.

2 Tujuan

Standar ini ditujukan untuk memberikan pedoman yang terarah dan seragam dalampenerapan teleinformasi data dan tampilan HMI 1yste bagi penerapan gardu induk

otomasi yang mengutamakan mutu, keandalan dan ekonomi. Standar ini merupakanacuan dalam pembangunan System SCADA untuk Gardu Induk otomasi baru dan 1ystemSCADA untuk penambahan bay  baru (migrasi RTU). Untuk bay  lama, tetap menggunakanteleinformasi data fungsi operasi sesuai dengan SPLN S5.001: 2008 yang akandisetarakan dengan TID untuk SOGI.

3 Acuan Normatif

Dokumen-dokumen referensi/acuan berikut sangat diperlukan dalam penggunaan standarini. Untuk referensi yang bertanggal, maka hanya terbitan tersebut yang berlakusedangkan referensi yang tidak bertanggal, yang berlaku adalah terbitan terakhir dari

dokumen referensi tersebut (termasuk amandemennya).Dokumen normatif berikut berisi persyaratan-persyaratan yang menjadi referensi dalampembuatan standar SCADA: Teleinformasi Data Untuk Sistem Otomasi Gardu Induk.

a. SNI 04-7021.1.1-2004: 2004, Peralatan dan Sistem Telekontrol    –  Bagian 1:Pertimbangan Umum – Seksi 1: Prinsip Umum; 

b. Keputusan Menteri Energi dan Sumberdaya Mineral Nomor: 150K/30/MEM/2004, Aturan Jaringan Sistem Tenaga Listrik Jawa-Madura-Bali ; 

c. SPLN S3.001: 2008 “Peralatan SCADA Sistem Tenaga Listrik”; d. SPLN T5.002-1: 2010 ”Pola Proteksi Saluran Transmisi Bagian 1 : Tegangan Tinggi

66 kV dan 150 kV”; e. SPLN T5.002-2: 2010”Pola Proteksi Saluran Transmisi Bagian 2 : Tegangan Ekstra

Tinggi 275 kV dan 500 kV”; 

Page 16: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 16/118

SPLN S5.003-1: 2014

2

f. IEC 61850-1 ” Communication networks systems in substations  – Part 1: Introductionand overview ”; 

g. IEC 61850-2 ” Communication networks systems in substations – Part 2: Glossary ”; h. IEC 61850-3 ” Communication networks systems in substations  –  Part 3: General

Requirement ”; 

4 Istilah dan Definisi

4.1 Alarm

Perubahan kondisi dari peralatan atau System yang telah terdeteksi sebelumnya   karenafungsi yang tidak dilakukan oleh operator/dispatcher , atau kegagalan peralatan untukmerespon secara benar. Indikasi alarm berupa audible atau visual , atau keduanya. 

4.2 Control c enter

Pusat kendali pengoperasian sistem tenaga listrikdimana master station ditempatkan.

4.3 Distr ibut ion con trol center  (DCC)

Pusat kendali jaringan distribusi.

4.4 Feeder colouring

Pewarnaan penyulang pada jaringan tenaga listrik dalam kondisi bertegangan.

4.5 Gardu hubung

Gardu yang mempunyai fungsi utama melakukan manuver antar feeder.

4.6 Gardu induk

Gardu yang mempunyai fungsi sebagai pusat pembagi beban.

4.7 Gardu tengah

Gardu yang merupakan titik tengah beban atau titik tengah feeder.

4.8 Human Mach ine Interface  (HMI)

Perangkat dimana pengguna berinteraksi dengan system  SCADA. HMI menyediakanfasilitas dimana pengguna dapat memberikan input kepada system  dan system  dapatmemberikan output kepada pengguna.

Page 17: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 17/118

SPLN S5.003-1: 2014

3

4.9 Inter Distr ibut ion Control Center  (IDCC)

Pusat kendali yang terhubung dengan beberapa distribution control center .

4.10 Inter Regio nal Contro l Center  (IRCC)

Pusat kendali yang terhubung dengan beberapa regional control center .

4.11 Maintenance Center

Workstation di luar control center  yang digunakan untuk keperluan pemeliharaan.

4.12 National Contro l Center  (NCC)

Pusat kendali yang terhubung dengan beberapa inter regional control center .

4.13 Operator

Petugas yang mengawasi dan mengeksekusi secara lokal peralatan di gardu induk.

4.14 Region al Contr ol Center  (RCC)

Pusat kendali jaringan transmisi tegangan tinggi.

4.15 Regu pemeliharaan

Petugas yang melakukan pemeliharaan pada instalasi sistem tenaga listrik.

4.16 Remote station

Stasiun yang dipantau, atau diperintah dan dipantau oleh master station, yang terdiri darigateway , IED, HMI lokal, RTU, dan meter energi.

4.17 Sistem Otomasi Gardu Induk (SOGI)

Sistem untuk mengelola, mengendalikan, dan proteksi system tenaga listrik. Hal ini dapatdicapai dengan mengambil informasi real time dari system, didukung oleh aplikasi localdan remote control yang handal dan proteksi system  tenaga listrik. Sebuah Substation Automation terdiri dari local intelligence, komunikasi data dan supervisory control , sertamonitoring .

4.18 Supervisory Con trol and Data Acquisi t ion  (SCADA)

Sistem yang mengawasi dan mengendalikan peralatan proses yang tersebar secara

geografis. [ IEC 870-1-3 ]

Page 18: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 18/118

SPLN S5.003-1: 2014

4

4.19 Telecontro l

Kendali peralatan operasional jarak jauh menggunakan transmisi informasi dengan tekniktelekomunikasi. [IEV 371-01-01]CATATAN: Telekontrol dapat berisi kombinasi perintah, alarm, indikasi, metering /pengukuran,

proteksi dan fasilitas tripping , tidak menggunakan pesan suara. 

4.20 Telesignal

Pengawasan status dari peralatan operasional dalam jarak tertentu dengan menggunakanteknik telekomunikasi seperti kondisi alarm, posisi switch atau posisi katup. [IEV 371-01-04]

4.21 Telemetering

Transmisi nilai variabel yang diukur dengan menggunakan teknik telekomunikasi. [IEV371-01-03]

5 Umum

5.1 Fasilitas SCADA untuk SOGI

Setiap pembangunan gardu induk yang baru dan penambahan bay baru pada gardu induklama harus dapat dipantau dari control center   dan dilakukan pengujian sebelumdiintegrasikan ke system transmisi atau system distribusi tenaga listrik.

5.2 Teleinformasi data (TID)

Standar ini membedakan teleinformasi data untuk transmisi dan distribusi. Teleinformasidata untuk Sistem Otomasi Gardu Induk (SOGI) dapat dilihat pada pada LAMPIRAN 1.Daftar Teleinformasi. 

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi makamaster station dapat digunakan untuk fungsi RCC dan DCC. Dalam hal ini teleinformasiyang digunakan mengacu pada teleinformasi data transmisi dan distribusi.

Teleinformasi data untuk sistem SOGI ditampilkan pada Master Station, MaintenanceCenter   dan HMI (Human Machine Interface) lokal pada gardu induk setempat.Konfigurasi workstation di luar control center  yang difungsikan untuk Maintenance Center  dan juga HMI (Human Machine Interface) lokal yang bertempat di Gardu Induk setempat,menampilkan kebutuhan teleinformasi data fungsi pemeliharaan. Untuk Dispatcher  padacontrol center , ditampilkan kebutuhan teleinformasi data fungsi operasi.

5.3 Struktur informasi

Event dan alarm merupakan pemberitahuan kepada dispatcher   atau operator tentangkejadian pada peralatan sistem tenaga listrik yang tampil di monitor dan disimpan di datahistorikal. Struktur informasi event   dan alarm SCADA dapat dilihat pada LAMPIRAN 5.Struktur Informasi. 

Page 19: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 19/118

SPLN S5.003-1: 2014

5

5.4 Simbol dan warna

Simbol dan warna diperlukan untuk penyajian diagram system tenaga listrik pada monitordan layar tayang. Simbol dan warna untuk tiap jenis dan kondisi peralatan bersifat systemdan dipilih sedemikian rupa sehingga jenis dan kondisi peralatan tersebut mudah dikenalioleh regu pemeliharaan dan operator . Simbol dan warna dapat dilihat pada  LAMPIRAN 6.

Simbol dan Warna. 

5.5 Tampilan HMI Fungsi Operasi

Tampilan pada HMI fungsi operasi harus diatur agar seragam. Eksekusi manuver  peralatan harus dapat dilakukan dengan cara yang mudah dan cepat dengan maksimal 3langkah yaitu:

1. Klik peralatannya.2. Pilih tombol Close atau Open 3. Execute atau Cancel. 

Kategori tampilan yang harus ada pada HMI Fungsi Operasi adalah:

1. Single Line Diagram Gardu Induk sesuai dengan TID SOGI Fungsi Operasi:a. Single Line Diagram untuk Tegangan Ekstra Tinggib. Single Line Diagram untuk Tegangan Tinggi.c. Single Line Diagram untuk Tegangan Menengah.d. Single Line Diagram untuk Daya Pemakaian Sendiri.e. Overview  keseluruhan SLD Gardu Induk, diusahakan untuk ditampilkan dalam

1 layar.2. Pengukuran keseluruhan Gardu Induk sesuai TID SOGI Fungsi Operasi

a. Tabel Measurement realtime.b. Log sheet  pengukuran.

3. Event list   yang dapat dilakukan proses filter dan diekspor ke dalam bentuk

database (Oracle dan/atau SQL dan/atau Spreadsheet )4.  Alarm list   yang dapat dilakukan proses filter dan diekspor ke dalam bentukdatabase (Oracle dan/atau SQL dan/atau Spreadsheet )

5. Simbol.

5.6 Gambar tipikal HMI Fungsi Operasi

5.6.1 Umum

Gambar 1. Tipikal HMI fungsi operasi

Lambang PLN Nama Gardu Induk & Level Tegangan Hari + Tanggal + Jam

Na ma Us er Lo cal/Remote

Dummy CB

Jenis AlarmPrint

Ikon Baterai

Catatan: Isi tampilan untuk bagian header kelengkapan informasinya harus

mengikuti informasi yang ada pada lay out ini, sedangkan penempatan

informasinya adalah bebas tergantung masing-masing aplikasi HMI.

Page 20: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 20/118

SPLN S5.003-1: 2014

6

5.6.2 Topologi

4. Control Centre

2. Relay & Control Panel

(Urutan Panel di Ruang

Kontrol GI)

1. Switchyard

3.HMI SOGI

BUS - A

BUS - B

1 2 34

BUS - A

BUS - B

1 2 3

4

BUS - A

BUS - B

1 2 3

4

BUS - A

BUS - B

1 2 3

4

 

Gambar 2. Topologi

Page 21: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 21/118

SPLN S5.003-1: 2014

7

5.6.3 Contoh Single line diagram fungsi operasi

Di atas SLD ada:

1. Dummy CB2. Kontrol Disable/Enable (Diganti menjadi Local Remote)

3. Nama GI4. Kondisi alarm Baterai (dlm bentuk ikon), RTU, Komunikasi,5. Kondisi GI (General Interrogation, In service atau Out service)6. Jenis-jenis alarm (Emergency, Critical, General, Limit violation, Station )7. Hari, tanggal, jam.

Lambang PLN Nama Gardu Induk & Level Tegangan Hari + Tanggal + Jam

Nama User Local/Remote

Dummy CB

Jenis AlarmPrint

BB - A

LFC

(Po,Pr,N)

BB - B

Q

P

PQ

I

BAY

GENERATOR

BAY

REAKTOR

BAY

IBT

BAY

TRAFO

TENAGA

L/R

Q

BAYKOPEL

V

PQ

L/R L/R

150 kV

I

QP

V

150/20 kV

L/R

L/R

PQV

BAY

TRANSMISI

I

150 kV

150/70 kV

Catatan :

1. arah panah pada bay menunjukan arah

pengiriman daya

Ikon Baterai

 

Gambar 3. Single Diagram  fungsi operasi

5.7 Penjelasan gambar tipikal HMI Fungsi Operasi

   Alarm gangguan rectifier dan baterai ditampilkan dalam bentuk ikon (bisa berupa

ikon baterai atau aki). Peletakannya dilakukan di sudut kiri atas. Ukurannya 2x

gambar CB. Ikon tersebut akan blinking apabila terjadi gangguan.

  Posisi kontrol GI dalam mode local  atau remote secara general harus ditampilkan

di bagian atas.

  “Dummy  CB” adalah indikasi dan soft button dummy circuit breaker .

  Tampilan overview   adalah tampilan yang menampilkan keseluruhan SLD dengan

level tegangan yang sama, misalnya tampilan keseluruhan SLD 500 kV, SLD 150

kV, SLD 66 kV dan SLD 20 kV.

Page 22: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 22/118

SPLN S5.003-1: 2014

8

  Untuk bay   yang sedang dalam posisi interlock (PMT dan PMS) dipersyaratkan

menampilkan gambar gembok untuk menginformasikan status tersebut ke

dispatcher . Contohnya dapat dilihat pada gambar berikut:

L/R

L/RL/R

BB - A

BB - B

150 kV

150 kV

Gembok

berwarna kuning

 

Gambar 4. Tipikal HMI fungsi operasi

Page 23: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 23/118

SPLN S5.003-1: 2014

9

6 Perbatasan Kebutuhan Teleinformasi Data

Teleinformasi data yang dikirim ke/dari suatu control center   ditentukan olehkewenangannya dalam operasi sistem, sehingga dibutuhkan adanya batas yang jelasantara kewenangan IRCC dan RCC serta RCC dan DCC. Berikut ini dijelaskanperbatasan kebutuhan teleinformasi data antara IRCC dan RCC serta antara RCC danDCC.

6.1 Perbatasan Kebutuhan Teleinformasi Data antara IRCC dan RCC

Perbatasan kebutuhan teleinformasi data antara IRCC dan RCC adalah di titik pelayanantegangan ekstra tinggi atau tegangan tinggi yang ditentukan, dan atau seperti Gambar 55dan Gambar 66.

a. Bila sisi sekunder IBT terhubung dengan konfigurasi double busbar

IRCC

RCC

BUSBAR TT

BUSBAR TET/TT

 Gambar 5. Batas wewenang antara IRCC dengan RCC (Tipe-a)

Page 24: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 24/118

SPLN S5.003-1: 2014

10

b. Bila sisi sekunder IBT terhubung dengan konfigurasi 1½ Breaker  

IRCC

RCC

BUSBARTT

BUSBARTT

BUSBAR TET/TT

 Gambar 6. Batas wewenang antara IRCC dengan RCC (Tipe-b)

Page 25: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 25/118

SPLN S5.003-1: 2014

11

6.2 Perbatasan kebutuhan teleinformasi data antara RCC dan DCC

Perbatasan kebutuhan teleinformasi data antara RCC dan DCC di gardu induk ditunjukan

pada Gambar 77.

BUSBAR TT

BUSBAR TM

L/R

P

Q

V

I

RCC

DCC

 

Gambar 7. Batas wewenang antara RCC dengan DCC

Untuk daerah yang fungsi transmisi dan distribusi masih dalam satu organisasi (belumdipisahkan antara fungsi RCC dan DCC) maka perbatasan kebutuhan teleinformasi datadapat mengacu pada perbatasan fungsi RCC dan DCC atau disesuaikan dengan SOPyang berlaku di daerah tersebut. 

Page 26: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 26/118

SPLN S5.003-1: 2014

12

LAMPIRAN 1. Daftar Teleinformasi

1-1: Telesignal  

Tabel 1. Daftar telesignal fungsi operasi

No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event

TSS/TSD H/LN D/B/G/P F/C A/I

1 AQR  Automatic power factor active Generator, TSS H B C I

2 ARCircuit breaker auto reclosesuccess

OHL feeder, TSS LN B C A

3 ARLCircuit breaker auto recloselock out

OHL feeder, TSS LN B C A

4 ARO  Auto reclose on/off OHL feeder, TSD LN B C I

5 AVR Automatic voltage regulatoron/off

Generator, TSS H B C I

6 AVRAM  Avr Auto/ manual IBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),

TSD LN D C I

7 BF Bay fault

Bus coupler,Bus section,OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),Capacitor,Reactor,Diameter,Gen transf,

TSS LN B C A

8 BIBus isolator switchclosed/opened

Bus coupler,Bus section,

OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),TRF 150(70)/20 sisi 20,Capacitor,Reactor,Gen Transf,

TSD H D C I

9 BP Busbar protection  Busbar, TSS LN B C A

10 BRF Breaker fault

Bus coupler,

Bus section,OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),Capacitor,Reactor,Diameter,Gen transf, 

TSS LN B C A

11 BUAL Building alarm Gardu induk, TSS H G C A

12 CB Circuit breaker closed/opened

Bus coupler,Bus section,Ohl feeder,

Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,

TSD H D C I

Page 27: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 27/118

SPLN S5.003-1: 2014

13

No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event

TSS/TSD H/LN D/B/G/P F/C A/I

IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),TRF 150(70)/20 sisi 20,Capacitor,

Reactor,Diameter,

13 COM Communication faulty Gardu induk, TSS LN P C A

14 CSO Check synchronizing override Gardu induk, TSD LN B C I

15 CSPCheck synchronizing in

 progress

Bus coupler,OHL feeder,Cable feeder,IBT 150/70 sisi 70,

TSS LN B C A

16 DEF Directional earth faultOHL feeder,Cable feeder, 

TSS LN B F A

17 DIDiameter isolator switchclosed/opened

Diameter, TSD H D C I

18 DISZ1 Distance protection zone 1

OHL feeder,

Cable feeder, TSS LN B F A

19 DISZ2 Distance protection zone 2OHL feeder,Cable feeder,

TSS LN B F A

20 DISZ3 Distance protection zone 3OHL feeder,Cable feeder,

TSS LN B F A

21 DISZ4 Distance protection zone 4OHL feeder,Cable feeder,

TSS LN B F A

22 DTT Direct transfer trip OHL feeder, TSS LN P C A

23 ES Earth switch closed/openedBusbar,OHL feeder,CABLE feeder,

TSD H D C I

24 GOV Free acting governor active Generator, TSS H B C I

25 GRM Genset ready/maintenance Gardu induk, TSD H G C I

26 GTT Generator transformer trip Gen transf, TSS H B C A

27 GUC Generator unit run/stop Generator, TSD H P C I

28 IEDF Ied bay level faulty Gardu induk, TSS LN G C A

29 LCD Line current differentialOHL feeder,Cable feeder,

TSS LN B F A

30 LFALoad freq available/notavailable

Generator,blok, TSD H P C I

31 LFC Load freq control on/off switch Generator,blok, TSD H P C I

32 LFF Load freq control unit failureGenerator,blok,

TSS H B C I

33 LFR Load freq request on/off Generator,blok, TSD H P C I

34 LILine isolator switchclosed/opened

OHL feeder,Cable feeder,Capacitor,Reactor,Gen transf,

TSD H D C I

35 LOR Lock out relay trip Gardu Induk, TSS LN B C A

Page 28: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 28/118

SPLN S5.003-1: 2014

14

No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event

TSS/TSD H/LN D/B/G/P F/C A/I

36 LRBCU Local/Remote for bcu

Bus Coupler,OHL feeder,Cable feeder,IBT 500(275)/150 sisi 150,

IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi150(70),TRF 150(70)/20 sisi 20,Capacitor,Reactor,Diameter,Gen transf, 

TSD LN B C I

37 LRHMI Local/Remote for local hmi Gardu Induk, TSD LN G C I

38 OCGF Over current ground fault

Bus coupler,OHL feeder,Cable feeder,Capacitor,Reactor,Diameter,

TSS LN B C A

39 OCPT Oil cable pressure trip Cable feeder, TSS H B F A

40 PSO Power station operated Generator,blok, TSD H P C I

41 RA Reaktor alarm Reactor, TSS LN B C A

42 RT Reaktor trip Reactor, TSS LN B C A

43 SF Supply failure Gardu induk, TSS H B C A

44 SIBSoftware interlocking by

 passedGardu induk, TSD LN B C I

45 SLF Station level faulty Gardu induk, TSS LN P C A

46 SOTF Switch on to faultOHL feeder,Cable feeder, 

TSS LN B C A

47 TCH Tap changer high limitIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),

TSS H B C A

48 TCIP Tap changer in progressIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),

TSS H B C A

49 TCL Tap changer low limitIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),

TSS H B C A

50 TEA Temperature alarmIBT 150/70 sisi 150,TRF 150(70)/20 sisi

150(70),

TSS LN B C A

Page 29: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 29/118

SPLN S5.003-1: 2014

15

No Kode Fungsi ImplementasiIndikasi Sumber Bagian Jumlah Event

TSS/TSD H/LN D/B/G/P F/C A/I

51 TRA Transformer  alarmIBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),

TSS LN B C A

52 TRBPTTransformer back up

 protection trip

IBT 150/70 sisi 150,TRF 150(70)/20 sisi

150(70),

TSS LN B C A

53 TRMPTTransformer main protectiontrip

IBT 150/70 sisi 150,TRF 150(70)/20 sisi150(70),

TSS LN B C A

54 TTR Teleprotection trip receiveOHL feeder,Cable feeder,

TSS LN P C A

55 TTT Teleprotection trip transmitOHL feeder,Cable feeder,

TSS LN P C A

56 UFRT Under frequency relay trip

Bus Coupler,OHL feeder,Cable feeder,TRF 150(70)/20 sisi 20,

TSS LN B C A

57 UT Unit trip Generator, TSS H B C A

58 VACF VAC failure  Gardu induk, TSS H G C A

59 VDCF VDC failure  Gardu induk, TSS H G C A

60 VRT Voltage relay trip

OHL feeder,Cable feeder,TRF 150(70)/20 sisi 20,Capacitor,Reactor, 

TSS LN B C A

61 VS Voltage status Busbar, TSS LN B C I

KETERANGAN:

 A =  Alarm (audible alarm, flashing display, etc)I = Indikasi (normal condition)TSS = Telesignal singleTSD = Telesignal doubleH = Hardwiring

LN = Logical NetworkD = per Device (peralatan)B = per BayG = per GIP = per PembangkitF = per FasaC = Common

Page 30: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 30/118

SPLN S5.003-1: 2014

16

1-2: Telemeasurement  

Tabel 2. Daftar telemeasurement

No Kode Fungsi Implementasi

Sumber

H/LN

Bagian

D/B/G/P

Jumlah

F/C

1 F FrekuensiBusbar,Ohl feeder,Cable feeder, 

H G C

2 I Arus

Bus Coupler,Bus Section,OHL Feeder,Cable Feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 SISI 70,Gen Transf,

H B F

3 P Daya Aktif

OHL Feeder,Cable Feeder,

IBT 500(275)/150 SISI 150,IBT 150/70 SISI 70,TRF 150(70)/20 SISI 20,Gen Transf,Generator

LN B C

4 POAQ Real Power SettingGenerator,Blok

H D C

5 PRAQ Max Power Variation SettingGenerator,Blok

H D C

6 Q Daya Reaktif

OHL Feeder,Cable Feeder,IBT 500(275)/150 SISI 150,IBT 150/70 SISI 70,TRF 150(70)/20 SISI 20,

Kapasitor,Reaktor,Gen Transf,Generator

LN B C

7 V Tegangan

Busbar,Ohl feeder,Cable feeder,IBT 150/70 sisi 70,Generator,

H B F

KETERANGAN:

Logical Node pada TM apabila nilai didapat melalui perhitungan beberapa parameter.Hardwiring pada TM apabila nilai didapat melalui pengukuran dari sinyal masukan.* Per fasa untuk single phase.

Page 31: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 31/118

SPLN S5.003-1: 2014

17

1-3: Tap Changer Posit ion

Tabel 3. Daftar tap changer posi t ion

No Kode Fungsi ImplementasiSumber

H/LN BagianD/B/G/P

JumlahF/C

1 TPI Tap position indication Trafo, IBT H B C/F*

KETERANGAN:

* Per fasa untuk single phase.

1-4: Remote Control

Tabel 4. Daftar remote contro l

No Kode Fungsi Implementasi IndikasiRCD/RCA

SumberH/LN 

BagianD/B/G/P

JumlahF/C

1 ARO  Auto reclose on/off

Remote station,Gardu induk,Busbar,Bus coupler, Bus section, Ohl feeder, Cable feeder,IBT 500(275)/150 sisi 150,IBT 150/70 sisi 150,IBT 150/70 sisi 70,TRF 150(70)/20 sisi 150(70),TRF 150(70)/20 sisi 20,Capacitor,Reactor,Diameter,

Gen transf,Generator,Blok, 

RCD LN P C

2 AVRAM AVR auto/manual  IBT 150/70 SISI 150,TRF 150(70)/20 sisi 150(70),

RCD LN D C

3 CB Circuit breaker closed/opened

Bus coupler,Bus section,Ohl feeder,Cable feeder,Ibt 150/70 sisi 150,Ibt 150/70 sisi 70,Trf 150(70)/20 sisi 150(70),Trf 150(70)/20 sisi 20,Capacitor,Reactor,Diameter,

RCD H D C

4 N Load freq control n_levelGENERATOR,BLOK,

RCA H P C

5 POOP Real power set pointGENERATOR,BLOK,

RCA H P C

6 PROP Max power variation set pointGENERATOR,BLOK,

RCA H P C

7 TC Tap changer raise/lowerIBT 150/70 SISI 150,TRF 150(70)/20 SISI 150(70),

RCD LN D C

Page 32: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 32/118

SPLN S5.003-1: 2014

18

LAMPIRAN 2. Teleinformasi pada Berbagai Konfigurasi Gardu Induk

TA-01: Konfigurasi Umum Pada 1½ Breaker GITET

KONFIGURASI UMUM PADA 1½ BREAKER GITET

BUSBAR - A

TA-01

BUSBAR - B

Q

L/R

PQV

P

Q

I

P

Q

V

BAY GENERATOR

BAY FEEDER

BAY REAKTOR

BAY IBT

VI

PQ

L/R

L/R

L/R

L/R

L/R

L/R

L/R

V

V

I

 

Gambar 8. Konfigurasi SLD 1 ½ breaker

Page 33: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 33/118

SPLN S5.003-1: 2014

19

Tabel 5. Teleinformasi data untuk konfigurasi umum pada 1½ breaker

Group Bay Data No Kode Fungsi Tipe Jmlh

GARDUINDUK

TSS

BUAL Building alarm  A  1 

COM Communication faulty  A  1 IEDF Ied bay level faulty  A  1 

LOR Lock out relay trip  A  1 

SLF Station level faulty  A  1 

SF Supply failure  A  1 

VACF VAC failure  A  1 

VDCF VDC failure  A  1 

TSD

CSO Check synchronizing override I 1

DCB Dummy circuit breaker closed/opened I 1

GRM Genset ready/maintenance I 1)*

LRHMI Local/remote for local hmi I 1

SIBSoftware interlocking by passed

I 1

RCDCSO Check synchronizing override 1

DCB Dummy circuit breaker closed/opened 1

BUSBAR

TMF Frekuensi 2

V Tegangan 2

TSS

MPUF IED MPU faulty  A 2

BP Busbar protection  A 1

VS Voltage status I 2 

VTMT Voltage transformer MCB trip  A  2 

TSD ES Earth switch closed/opened I 2 

DIAMETER

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

DTT Direct transfer trip  A  1 CCP Circulating current protection trip  A  1 

CBF Circuit breaker failure trip  A 1 

OCGF Over current ground fault  A 1

SZP Short zone protection trip  A  1 

TSD

DI Diameter isolator switch closed/opened I 6

CB Circuit breaker closed/opened I 3

LRBCU Local remote for BCU I 3

RCD CB Circuit breaker closed/opened 3

TM

F Frekuensi 1

V Tegangan 1

I Arus 1P Daya aktif 1

Q Daya reaktif 1

 AMF  Amperes fault 8

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I 1

 ARL Circuit breaker auto reclose lock out I 1

 AR Circuit breaker auto reclose success I 1

CBF Circuit breaker failure trip  A  1

DTT Direct transfer trip  A  1

DEF Directional earth fault  A  1DISZ1 Distance protection zone 1  A  1

Page 34: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 34/118

SPLN S5.003-1: 2014

20

Group Bay Data No Kode Fungsi Tipe Jmlh

BAY FEEDER TSS

DISZ2 Distance protection zone 2  A  1

DISZ3 Distance protection zone 3  A  1

DISZ4 Distance protection zone 4  A  1

LCD Line current differential  A  1OCPT Oil cable pressure trip (Cable feeder)  A  1

OCGF Over current ground fault  A  1

SOTF Switch on to fault  A  1

TTR Teleprotection trip receive  A  1

TTT Teleprotection trip transmit  A  1

UFRT Under frequency relay trip  A  1

VRT Voltage relay trip  A  1

TSD

 ARO  Auto reclose on/off I  1

ES Earth switch closed/opened I  1

LI Line isolator switch closed/opened I  1

LRBCU Local/remote for BCU I  1

BAY IBT

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I  1

TCH Tap changer high limit I  1

TCIP Tap changer in progress I  1

TCL Tap changer low limitI  1

TEA Temperature alarm  A  1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

VRT Voltage relay trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

CB Circuit breaker closed/opened I 1

LI Line isolator switch closed/opened I  2

LRBCU Local/remote for BCU I 1

RCD

CB Circuit breaker closed/opened

 AVRAM  AVR auto/manual

TC Tap changer raise/lower

BAYREAKTOR

TM Q Daya reaktif 1

TSS

BF Bay fault  A  1

OCGF Over current ground fault  A  1

RA Reaktor alarm  A  1

RT Reaktor trip  A 1

TSD

CB Circuit breaker closed/opened I 1

ES Earth switch closed/opened I 1

LI Line isolator switch closed/opened I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1PRAQ Max power variation setting 1

Page 35: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 35/118

SPLN S5.003-1: 2014

21

Group Bay Data No Kode Fungsi Tipe Jmlh

BAYGENERATOR

POAQ Real power setting 1

V Tegangan 1

TSS

 AQR  Automatic power factor active I 1

 AVR  Automatic voltage regulator on/offI 1

BF Bay fault  A 1

CSP Check synchronizing in progress I 1

GTT Generator transformer trip  A 1

GOV Governor free I 1

LFF Load freq control unit failure  A 1

UT Unit trip  A 1

VRT Voltage relay trip  A 1

TSD

ES Earth switch closed/opened I  1

GUC Generator unit run/stop I  1

LI Line isolator switch closed/opened I  1

LFA Load freq available/not available I  1

LFC Load freq control on/off switch I  1

LFR Load freq request on/off I 1

KETERANGAN:

 A =  AlarmI = IndikasiRincian Teleinformasi diatas adalah rincian per bay  * GRM untuk Genset di Control Center  

Page 36: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 36/118

SPLN S5.003-1: 2014

22

TA-02: Konfigurasi Umum Pada 1 ½ Breaker 150 kV

KONFIGURASI UMUM PADA 1½ BREAKER 150 KV

BUSBAR - A

TA-02

BUSBAR - B

Q

L/R

PQV

P

Q

I

P

Q

V

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBT BAY TRAFO TENAGA

V

I

PQ

L/R

L/R

L/R

L/R

L/R

L/R

L/R

L/R

L/R

V

V

I

P

Q

I

V

 

Gambar 9. Konfigurasi umum pada 1 ½ breaker  150 kV

Page 37: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 37/118

SPLN S5.003-1: 2014

23

Tabel 6.Teleinformasi data untuk konfigurasi umum pada 1½ breaker

Group Bay Data No Kode Fungsi Tipe Jmlh

GARDUINDUK

TSS

BUAL Building alarm  A  1 

COM Communication faulty  A  1 

IEDF IED bay level faulty  A  1 

LOR Lock out relay trip  A  1 

SLF Station level faulty  A  1 

SF Supply failure  A  1 

VACF VAC failure  A  1 

VDCF VDC failure  A  1 

TSD

CSO Check synchronizing override I 1

DCB Dummy circuit breaker closed/opened I 1

GRM Genset ready/maintenance I 1)*

LRHMI Local/remote for local hmi I 1

SIB Software interlocking by passed I 1

RCD CSO Check synchronizing override 1DCB Dummy circuit breaker closed/opened 1

BUSBAR

TMF Frekuensi 2

V Tegangan 2

TSS

MPUF IED MPU faulty  A 2

BP Busbar protection  A 1

VS Voltage status I 2 

VTMT Voltage transformer MCB trip  A  2 

TSD ES Earth switch closed/opened I 2 

DIAMETER

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

DTT Direct transfer trip  A  1 CCP Circulating current protection trip  A  1 

CBF Circuit breaker failure trip  A 1 

OCGF Over current ground fault  A 1

SZP Short zone protection trip  A  1 

TSD

DI Diameter isolator switch closed/opened I 6

CB Circuit breaker closed/opened I 3

LRBCU Local remote for BCU I 3

RCD CB Circuit breaker closed/opened 3

TM

F Frekuensi 1

V Tegangan 1

I Arus 1P Daya aktif 1

Q Daya reaktif 1

 AMF  Amperes fault 8

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I 1

 ARL Circuit breaker auto reclose lock out I 1

 AR Circuit breaker auto reclose success I 1

CBF Circuit breaker failure trip  A  1

DTT Direct transfer trip  A  1

DEF Directional earth fault  A  1

DISZ1 Distance protection zone 1  A  1

DISZ2 Distance protection zone 2  A  1

Page 38: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 38/118

SPLN S5.003-1: 2014

24

Group Bay Data No Kode Fungsi Tipe Jmlh

BAY FEEDER TSS

DISZ3 Distance protection zone 3  A  1

DISZ4 Distance protection zone 4  A  1

LCD Line current differential  A  1

OCPT Oil cable pressure trip (Cable feeder)  A  1OCGF Over current ground fault  A  1

SOTF Switch on to fault  A  1

TTR Teleprotection trip receive  A  1

TTT Teleprotection trip transmit  A  1

UFRT Under frequency relay trip  A  1

VRT Voltage relay trip  A  1

TSD

 ARO  Auto reclose on/off I  1

ES Earth switch closed/opened I  1

LI Line isolator switch closed/opened I  1

LRBCU Local/remote for BCU I  1

BAY IBT

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I  1

TCH Tap changer high limit I  1

TCIP Tap changer in progress I  1

TCL Tap changer low limit I  1

TEA Temperature alarm A  1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

CB Circuit breaker closed/opened I 1

LI Line isolator switch closed/opened I  2

LRBCU Local/remote for BCU I 1

RCD

CB Circuit breaker closed/opened

 AVRAM  AVR auto/manual

TC Tap changer raise/lower

BAYTRAFOTENAGA

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

TCH Tap changer high limit I  1

TCIP Tap changer in progress I  1

TCL Tap changer low limit I  1

TEA Temperature alarm  A  1

TET Temperature trip  A  1

TRA Transformer alarm  A  1TRBPT Transformer back up protection trip  A  1

Page 39: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 39/118

SPLN S5.003-1: 2014

25

Group Bay Data No Kode Fungsi Tipe Jmlh

TRMPT Transformer main protection trip  A  1

UFRT Under frequency relay trip  A  1

VRT Voltage relay trip  A  1

TSD AVRAM  AVR auto/manual

I 1

ES Earth switch closed/opened I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for BCU I 1

RCD AVRAM  Avr auto/manual 1

TC Tap changer raise/lower 1

BAYREAKTOR

TM Q Daya reaktif 1

TSS

BF Bay fault  A  1

OCGF Over current ground fault  A  1

RA Reaktor alarm  A  1

RT Reaktor trip  A 1

TSD

CB Circuit breaker closed/opened I 1

ES Earth switch closed/opened I 1

LI Line isolator switch closed/opened I 1

BAYGENERATOR

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

PRAQ Max power variation setting 1

POAQ Real power setting 1

V Tegangan 1

TSS

 AQR  Automatic power factor active I 1

 AVR  Automatic voltage regulator on/off I 1

BF Bay fault  A 1

CSP Check synchronizing in progress I 1

GTT Generator transformer trip  A 1

GOV Governor free I 1

LFF Load freq control unit failure  A 1

UT Unit trip  A 1

TSD

ES Earth switch closed/opened I  1

GUC Generator unit run/stop I  1

LI Line isolator switch closed/opened I  1

LFA Load freq available/not available I  1

LFC Load freq control on/off switch I  1

LFR Load freq request on/off I 1

KETERANGAN: A =  Alarm

I = IndikasiRincian Teleinformasi diatas adalah rincian per bay  

Page 40: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 40/118

SPLN S5.003-1: 2014

26

TA-03: Konfigurasi Umum Pada Double Busbar

KONFIGURASI UMUM PADA DOUBLE BUSBAR

BUSBAR - A

TA-03

BUSBAR - B

QP

P

Q

I

P

Q

V

BAY GENERATOR

BAY FEEDER

BAY REAKTOR

BAY IBTBAY TRAFO TENAGA

L/R

Q

BAY KOPEL

VI

L/R L/R

V

V

I

QP

V

L/R

L/R L/R L/R

P

Q

I

V

I

 

Gambar 10. Konfigurasi umum pada double busbar

Page 41: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 41/118

SPLN S5.003-1: 2014

27

Tabel 7. Teleinformasi data untuk konfigurasi umum pada double busbar

Group Bay Data No Kode Fungsi Tipe Jmh

GARDUINDUK

TSS

BUAL Building alarm  A 1

COM Communication faulty  A 1

IEDF IED bay level faulty  A 1

LOR Lock out relay trip  A 1

SLF Station level faulty  A 1

SF Supply failure  A 1

VACF VAC failure  A 1

VDCF VDC failure  A 1

TSD

CSO Check synchronizing override I 1

DCBDummy circuit breakerclosed/opened

I 1

GRM Genset ready/maintenance I 1)*

LRHMI Local/remote for local hmi I 1

SIB Software interlocking by passed I 1

RCDCSO Check synchronizing override 1

DCBDummy circuit breakerclosed/opened

1

BUSBAR

TMF Frekuensi 2

V Tegangan 2

TSS

BP Busbar protection  A 1

VS Voltage status I 2 

VTMT Voltage transformer MCB trip  A  2 

TSD ES Earth switch closed/opened I 2 

KOPEL

TM I  Arus 1

BF Bay fault  A 1

TSS

BRF Breaker fault  A 1

CSP Check Synchronizing In Progress  A 1

OCGF Over current ground fault  A 1

UFRT Under frequency relay trip  A 1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

LRBCU Local remote for BCU I 1

RCD CB Circuit breaker closed/opened 1

BAYFEEDER

TM

 AMF  Amperes fault 8

F Frekuensi 1

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

 AR Circuit breaker auto reclose success I 1

 ARL Circuit breaker auto reclose lock out I 1

BF Bay fault  A 1

BRF Breaker fault  A 1

CSP Check synchronizing in progress I 1

DEF Directional earth fault  A 1

DISZ1 Distance protection zone 1  A 1

DISZ2 Distance protection zone 2  A 1

DISZ3 Distance protection zone 3  A 1DISZ4 Distance protection zone 4  A 1

Page 42: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 42/118

SPLN S5.003-1: 2014

28

Group Bay Data No Kode Fungsi Tipe Jmh

DTT Direct transfer trip  A 1

LCD Line current differential  A 1

OCGF Over current ground fault  A 1

OCPT** Oil cable pressure trip  A 1SOTF Switch on to fault  A 1

TTR Teleprotection trip receive  A 1

TTT Teleprotection trip transmit  A 1

UFRT Under frequency relay trip  A 1

VRT Voltage relay trip  A 1

TSD

 ARO  Auto reclose on/off I 1

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

ES Earth switch closed/opened I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for bcu I 1RCD CB Circuit breaker closed/opened I 1

BAY IBT

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

CSP Check synchronizing in progress I 1

TCH Tap changer high limit  A 1

TCIP Tap changer in progress I 1TCL Tap changer low limit  A 1

TEA Temperature alarm  A 1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

TSD

 AVRAM  Avr auto/manual I 1

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD

 AVRAM  Avr auto/manual 1

CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

BAYTRAFO

TENAGA

TC TPI Tap position indication I 1

TMP Daya aktif 1

Q Daya reaktif 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

TCH Tap changer high limit  A  1

TCIP Tap changer in progress I  1

TCL Tap changer low limit  A  1

TEA Temperature alarm  A  1

TRA Transformer alarm  A  1

TRBPT Transformer back up protection trip  A  1

TRMPT Transformer main protection trip  A  1

Page 43: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 43/118

SPLN S5.003-1: 2014

29

Group Bay Data No Kode Fungsi Tipe Jmh

UFRT Under frequency relay trip  A  1

VRT Voltage relay trip  A  1

TSD

 AVRAM  AVR auto/manual I 1

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 2

LRBCU Local remote for BCU I 1

RCD

 AVRAM  AVR auto/manual 1

CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

BAYREAKTOR

TM Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

VRT Voltage relay trip  A 1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD CB Circuit breaker closed/opened 1

BAYGENERATOR

TM

I Arus 1

P Daya aktif 2

POAQ Real power setting 1

PRAQ Max power variation setting 1

Q Daya reaktif 2

V Tegangan 1

TSS

 AQR  Automatic power factor active I 1

 AVR  Automatic voltage regulator on/off I 1

BF Bay fault  A 1

BRF Breaker fault  A 1

GOV Free acting governor active I 1

GTT Generator transformer trip  A 1

LFF Load freq control unit failure  A 1

UT Unit trip  A 1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

GUC Generator unit run/stop I 1LFA Load freq available/not available I 1

LFC Load freq control on/off switch I 1

LFR Load freq request on/off I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for bcu I 1

PSO Power station operated I 1

RCA

N Load freq control n_level 1

POOP Real power set point 1

PROP Max power variation set point 1

RCD LFR Load freq request on/off 1

KETERANGAN:*)  = GRM untuk Genset contro center  

Page 44: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 44/118

SPLN S5.003-1: 2014

30

 A =  Alarm I = IndikasiRincian Teleinformasi diatas adalah rincian per bay  

TA-04: Konfigurasi Umum Pada Single Busbar  

KONFIGURASI UMUM PADA SINGLE BUSBAR

BUSBAR

TA-04

Q

P

V

P

Q

I

P

Q

V

PQ

BAY GENERATOR

BAY TRANSMISI

BAY REAKTOR

BAY IBTBAY TRAFO TENAGA

Q

VI

V

I

PQ

L/R L/R L/R

L/R

L/R L/R

I

V

 

Gambar 11. Konfigurasi umum pada single busbar

Page 45: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 45/118

SPLN S5.003-1: 2014

31

Tabel 8. Teleinformasi data untuk konfigurasi umum pada single busbar

Group Bay Data No Kode Fungsi Tipe Jmh

GARDUINDUK

TSS

BUAL Building alarm  A 1

COM Communication faulty  A 1

IEDF Ied bay level faulty  A 1

LOR Lock out relay trip  A 1

SLF Station level faulty  A 1

SF Supply failure  A 1

VACF VAC failure  A 1

VDCF VDC failure  A 1

TSD

CSO Check synchronizing override I 1

DCBDummy circuit breakerclosed/opened

I 1

GRM Genset ready/maintenance I 1)*

LRHMI Local/remote for local hmi I 1

SIB Software interlocking by passed I 1

RCDCSO Check synchronizing override 1

DCBDummy circuit breakerclosed/opened

1

BUSBAR

TMF Frekuensi 1

V Tegangan 1

TSS

BP Busbar protection  A 1

VS Voltage status I 1 

VTMT Voltage transformer MCB trip  A  1 

TSD ES Earth switch closed/opened I 1 

BAYFEEDER

TM

 AMF  Amperes fault 8

F Frekuensi 1

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

 AR Circuit breaker auto reclose success I 1

 ARL Circuit breaker auto reclose lock out I 1

BF Bay fault  A 1

BRF Breaker fault  A 1

CSP Check synchronizing in progress I 1

DEF Directional earth fault  A 1

DISZ1 Distance protection zone 1  A 1

DISZ2 Distance protection zone 2  A 1

DISZ3 Distance protection zone 3  A 1

DISZ4 Distance protection zone 4  A 1

DTT Direct transfer trip  A 1

LCD Line current differential  A 1

OCGF Over current ground fault  A 1

OCPT** Oil cable pressure trip  A 1

SOTF Switch on to fault  A 1

TTR Teleprotection trip receive  A 1

TTT Teleprotection trip transmit  A 1

UFRT Under frequency relay trip  A 1

VRT Voltage relay trip  A 1TSD  ARO  Auto reclose on/off I 1

Page 46: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 46/118

SPLN S5.003-1: 2014

32

Group Bay Data No Kode Fungsi Tipe Jmh

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

ES Earth switch closed/opened I 1

LI Line isolator switch closed/opened I 1LRBCU Local/remote for bcu I 1

RCD CB Circuit breaker closed/opened I 1

BAY IBT

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

CSP Check synchronizing in progress I 1

TCH Tap changer high limit  A 1TCIP Tap changer in progress I 1

TCL Tap changer low limit  A 1

TEA Temperature alarm  A 1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

TSD

 AVRAM  Avr auto/manual I 1

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD AVRAM  Avr auto/manual 1CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

BAYTRAFOTENAGA

TC 1 TPI Tap position indication I 1

TMP Daya aktif 1

Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

TCH Tap changer high limit  A 1

TCIP Tap changer in progress I 1

TCL Tap changer low limit  A 1

TEA Temperature alarm  A 1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

UFRT Under frequency relay trip  A 1

VRT Voltage relay trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 2

LRBCU Local remote for BCU I 1

RCD

 AVRAM  AVR auto/manual 1

CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

BAY TM Q Daya reaktif 1

Page 47: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 47/118

SPLN S5.003-1: 2014

33

Group Bay Data No Kode Fungsi Tipe Jmh

REAKTOR

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

RA Reaktor alarm A

1RT Reaktor trip  A 1

VRT Voltage relay trip  A 1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD CB Circuit breaker closed/opened 1

BAYGENERATOR

TM

I Arus 1

P Daya aktif 2

POAQ Real power setting 1

PRAQ Max power variation setting 1

Q Daya reaktif 2

V Tegangan 1

TSS

 AQR  Automatic power factor active I 1

 AVR  Automatic voltage regulator on/off I 1

BF Bay fault  A 1

BRF Breaker fault  A 1

GOV Free acting governor active I 1

GTT Generator transformer trip  A 1

LFF Load freq control unit failure  A 1

UT Unit trip  A 1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

GUC Generator unit run/stop I 1

LFA Load freq available/not available I 1

LFC Load freq control on/off switch I 1

LFR Load freq request on/off I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for bcu I 1

PSO Power station operated I 1

RCA

N Load freq control n_level 1

POOP Real power set point 1

PROP Max power variation set point 1

RCD LFR Load freq request on/off 1

KETERANGAN:

 A =  AlarmI = IndikasiRincian Teleinformasi diatas adalah rincian per bay  * = GRM untuk Genset control center  

Page 48: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 48/118

SPLN S5.003-1: 2014

34

TB-01: Interbus Transformer  

(Secondary Sid e Conn ected to 1½ Breaker )

INTERBUS TRANSFORMER

Secondary Side Connected to 1½ Breaker 

BUSBAR - A

TB-01

BUSBAR - B

PQ

I

Dioperasikan dari IRCC

Dioperasikan dari RCC

}

Download to RCC

BUSBAR (IRCC)

V

L/R

 

Gambar 12. Interbus tran sform er (secondary side co nnected to 1½ breaker)

Page 49: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 49/118

SPLN S5.003-1: 2014

35

Tabel 9. Teleinformasi data untuk in terbus transformer  (secondary side con nected  to 1½breaker )

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I  1

TCH Tap changer high limit I  1

TCIP Tap changer in progress I  1

TCL Tap changer low limit I 

1TEA Temperature alarm  A  1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

ES Earth switch closed/opened I 2

LI Line isolator switch closed/opened I  2

LRBCU Local/remote for bcu I 1

RCD AVRAM  Avr auto/manual 1

TC Tap changer raise/lower 1

Page 50: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 50/118

SPLN S5.003-1: 2014

36

TB-02: Interbus Transformer

(Secondary Side Connected to Dou ble Busb ar )

INTERBUS TRANSFORMER

Secondary Side Connected to Double Busbar 

BUSBAR - A

TB-02

BUSBAR - B

BUSBAR (IRCC or RCC)

PQ

I

V }Operation Responsibility

by IRCC or RCC

Operation Responsibility

by RCCDownload to RCC

L/R

L/R

 

Gambar 13. In terbus transformer (secondary side connected to double bus bar ) 

Page 51: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 51/118

SPLN S5.003-1: 2014

37

Tabel 10. Teleinformasi data untuk in terbus transformer  (secondary side connected todouble bus bar)

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I  1

TCH Tap changer high limit I  1

TCIP Tap changer in progress I  1

TCL Tap changer low limit I  1

TEA Temperature alarm  A  1

TRA Transformer alarm  A 1TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

BI Bus isolator switch closed/opened I 2-4*)

CB Circuit breaker closed/opened I 2

CSO Check synchronizing override I 1

ES Earth switch closed/opened I 2

LI Line isolator switch closed/opened I  1-0*)

LRBCU Local/remote for bcu I 1

RCD

 AVRAM  Avr auto/manual 1

CB Circuit breaker closed/opened I 2TC Tap changer raise/lower 1

KETERANGAN:*) = (Primary Side Connected to 1½ Breaker) –(Primary Side Connected to Double Busbar)

Page 52: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 52/118

SPLN S5.003-1: 2014

38

TB-03: Interbus Transformer

(Secondary Side Connected to Single Busbar)

INTERBUS TRANSFORMER

Secondary Side Connected to Single Busbar 

BUSBAR

TB-03

BUSBAR (IRCC or RCC)

PQ

IV }

Operation Responsibility

by IRCC or RCC

Operation Responsibility

by RCCDownload to RCC

L/R

L/R

 

Gambar 14. In terbus transformer (secondary side connected to single busb ar ) 

Page 53: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 53/118

SPLN S5.003-1: 2014

39

Tabel 11. Teleinformasi data untuk in terbus transformer  (secondary side connected tosingle busbar)  

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I  1

TCH Tap changer high limit I  1

TCIP Tap changer in progress I  1

TCL Tap changer low limit I  1

TEA Temperature alarm  A  1

TRA Transformer alarm  A 1TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

CSO Check synchronizing override I 1

ES Earth switch closed/opened I 2

LI Line isolator switch closed/opened I  1-0*)

LRBCU Local/remote for bcu I 1

RCD

 AVRAM  Avr auto/manual 1

CB Circuit breaker closed/opened I 2TC Tap changer raise/lower 1

KETERANGAN:*) = (Primary Side Connected to 1½ Breaker) –(Primary Side Connected to Double Busbar )

Page 54: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 54/118

SPLN S5.003-1: 2014

40

TB-04: Interbus Transformer

(Secondary Side Connected to 1½ Breaker Dilengkapi Shunt Reaktor PadaKumparan Tersier)

INTERBUS TRANSFORMER

Secondary Side Connected to 1½ Breaker 

Dilengkapi Shunt Reaktor Pada Kumparan Tersier 

BUSBAR - A

TB-04

BUSBAR - B

P

Q

IV

Operation Responsibility

by IRCC

Operation Responsibility

by RCC

}

Download to RCC

BUSBAR (IRCC)

Q

L/R

 

Gambar 15. Secondary sid e  terhubung 1½ breaker dilengkapi dhunt reaktor pada kumparantersier

Page 55: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 55/118

SPLN S5.003-1: 2014

41

Tabel 12. Teleinformasi data untuk in terbus transformer  (secondary side conn ected to  1½breaker  dilengkapi shunt  reaktor pada kumparan tersier)

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 2

V Tegangan 1

TSS

BF Bay fault  A  1

BRF Breaker fault  A  1

CSP Check synchronizing in progress I  1

OCGF Over current ground fault  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

TCH Tap changer high limit I  1

TCIP Tap changer in progress I  1TCL Tap changer low limit I  1

TEA Temperature alarm  A  1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

VRT Voltage relay trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

ES Earth switch closed/opened I 2

LI Line isolator switch closed/opened I  3

LRBCU Local/remote for bcu I 1

RCD  AVRAM  Avr auto/manual 1TC Tap changer raise/lower 1

Page 56: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 56/118

SPLN S5.003-1: 2014

42

TB-05: Interbus Transformer  

(Second ary Side Connected to Doub le Busbar   Dilengkapi Shunt ReaktorPada Kumparan Tersier)

INTERBUS TRANSFORMER

Secondary Side Connected to Double Busbar 

Dilengkapi Shunt Reaktor Pada Kumparan Tersier 

BUSBAR - A

TB-05

BUSBAR - B

BUSBAR (IRCC or RCC)

PQ

IV }

Operation Responsibility

by IRCC or RCC

Operation Responsibility

by RCCDownload to RCC

Q

L/R

L/R

 

Gambar 16. Secondary side con nected to double busbar  dilengkapi shunt reaktor pada

kumparan tersier

Page 57: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 57/118

SPLN S5.003-1: 2014

43

Tabel 13.Teleinformasi data untuk in terbus transformer  (secondary side connected todouble busbar  dilengkapi shunt  reaktor pada kumparan tersier)

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 2

V Tegangan 1

TSS

BF Bay fault  A 3

BRF Breaker fault  A 3

CSP Check synchronizing in progress  A 1

OCGF Over current ground fault  A 1

OLSRX Overload shedding receive  A 1

OLSTX Overload shedding transmit  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

TCH Tap changer high limit  A 1

TCIP Tap changer in progress  A 1

TCL Tap changer low limit  A 1

TRA Temperatur alarm  A 1

TEA Temperatur alarm  A 1

TET Temperatur trip  A 1

TRBPT Transformer backup protection trip  A 1

TRMPT Transformer main protection trip  A 1

VRT Volage relay trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

CB Circuit breaker closed/opened I 2

ES Earthing switch closed/opened I 3

LI Line isolator switch closed/opened I 3

LRBCU Local/remote for BCU I 2

RCD

 AVRAM  AVR auto/manual 1

CB Circuit breaker closed/opened 2

TC Tap changer raise/lower 1

KETERANGAN:*) = (Primary Side Connected to 1½ Breaker )-(Primary Side Connected to Double Busbar ) 

Page 58: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 58/118

SPLN S5.003-1: 2014

44

TB-06: Interbus Transformer  

(Secondary Side Connected to Single Busbar  Dilengkapi Shunt Reaktor PadaKumparan Tersier)

INTERBUS TRANSFORMER

Secondary Side Connected to Single Busbar 

Dilengkapi Shunt Reaktor Pada Kumparan Tersier 

BUSBAR

TB-06

BUSBAR (IRCC or RCC)

PQ

IV }

Operation Responsibility

by IRCC or RCC

Operation Responsibility

by RCCDownload to RCC

Q

L/R

L/R

 

Gambar 17. Secondary sid e connected to single busb ar  dilengkapi shunt reaktor padakumparan tersier

Page 59: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 59/118

SPLN S5.003-1: 2014

45

Tabel 14. Teleinformasi data untuk in terbus transformer (secondary side conn ected to  single busbar  dilengkapi shunt  reaktor pada kumparan tersier) 

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1

TM

 AMF  Amperes fault 8

I Arus 6

P Daya aktif 1

Q Daya reaktif 2

V Tegangan 6

TSS

BF Bay fault  A 3

BRF Breaker fault  A 3

CSP Check synchronizing in progress I 1

OCGF Over current ground fault  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1TCH Tap changer high limit I 1

TCIP Tap changer in progress I 1

TCL Tap changer low limit I 1

TEA Temperature alarm  A 1

TET Temperature trip  A 1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

UFRT Under frequency relay trip  A 1

VRT Voltage relay trip  A 1

TSD

 AVRAM  AVR auto/manual I 1BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 4

LI Line isolator switch closed/opened I 3

LRBCU Local/remote for BCU I 2

RCD

 AVRAM  AVR auto/manual 1

CB Circuit breaker closed/opened 4

TC Tap changer raise/lower 1

KETERANGAN:*) = (Primary Side Connected to 1½ Breaker) – (Secondary Side Connected to Single Busbar)  

Page 60: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 60/118

SPLN S5.003-1: 2014

46

TB-07: Bay Trafo Tenaga Pada Konfigurasi 1½ Breaker  

BAY TRAFO TENAGAPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-07

BUSBAR - B

PQ

TEGANGAN TINGGI

TEGANGAN MENENGAH

DOUBLE BUSBAR

Batas wewenang

V

I

 

Gambar 18. Bay  trafo tenaga pada konfigurasi 1½ breaker

Page 61: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 61/118

SPLN S5.003-1: 2014

47

Tabel 15. Teleinformasi data untuk bay trafo tenaga pada konfigurasi 1½ breaker  

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indicatioan I 1

TM

 AMF Amperes fault 8

I Arus 6

P Daya aktif 1

Q Daya reaktif 1

V Tegangan 3

TSS

BF Bay fault  A 2

BRF Breaker fault  A 2

CSP Check synchronizing in progress I 1

TCH Tap changer high limit I 1

TCIP Tap changer in progress I 1

TCL Tap changer low limit I 1

TEA Temperature alarm  A 1

TET Temperature trip  A 1

TRA Transformer alarm  A 1

TRBPT Transformer back up protection trip  A 1

TRMPT Transformer main protection trip  A 1

UFRT Under frequency relay trip  A 1

VRT Voltage relay trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 2

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for BCU I 1

RCD AVRAM  AVR auto/manual 1CB Circuit breaker closed/opened 2

TC Tap changer raise/lower 1

Page 62: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 62/118

SPLN S5.003-1: 2014

48

TB-08: Bay Trafo Tenaga Pada Konfigurasi Double Busbar

BAY TRAFO TENAGA

PADA KONFIGURASI DOUBLE BUSBARBUSBAR - A

TB-08

BUSBAR - B

PQ

TEGANGAN TINGGI

TEGANGAN MENENGAH

DOUBLE BUSBAR

Batas wewenang

L/R

VI

 

Gambar 19. Bay  trafo tenaga pada konfigurasi double busbar

Page 63: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 63/118

SPLN S5.003-1: 2014

49

Tabel 16. Teleinformasi data untuk bay  trafo tenaga pada konfigurasi double busbar  

Data No Kode Fungsi Tipe Jmh

TC TPI Tap position indication I 1

TM

P Daya aktif 1

Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker Fault  A 1

TCH Tap changer high limit I 1

TCIP Tap changer in progress I 1

TCL Tap changer low limit I 1

TEA Temperatur Alarm  A 1

TET Temperatur trip  A 1

TRA Transformer Alarm  A 1

TRBPT Transformer Backup Protection Trip  A 1

TRMPT Transformer main Protection Trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

LRBCU Local remote for BCU I 1

RCD

 AVRAM  AVR auto/manual 1

CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

Page 64: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 64/118

SPLN S5.003-1: 2014

50

TB-09: Bay Trafo Tenaga Pada Konfigurasi Single Busbar

BAY TRAFO TENAGA

PADA KONFIGURASI SINGLE BUSBAR

TB-09

BUSBAR

P

QTEGANGAN TINGGI

TEGANGAN MENENGAH

DOUBLE BUSBAR

Batas wewenang

L/R

V

I

 

Gambar 20. Bay  trafo tenaga pada konfigurasi single busbar

Page 65: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 65/118

SPLN S5.003-1: 2014

51

Tabel 17. Teleinformasi data untuk bay  trafo tenaga pada konfigurasi single busbar  

Data No Kode Fungsi Tipe Jmh

TC 1 TPI Tap position indication I 1

TM

P Daya aktif 1

Q Daya reaktif 1

TSS

BF Bay fault A 1

BRF Breaker Fault  A 1

TCH Tap changer high limit I 1

TCIP Tap changer in progress I 1

TCL Tap changer low limit I 1

TEA Temperatur Alarm  A 1

TET Temperatur trip  A 1

TRA Transformer Alarm  A 1

TRBPT Transformer Backup Protection Trip  A 1

TRMPT Transformer main Protection Trip  A 1

TSD

 AVRAM  AVR auto/manual I 1

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

LRBCU Local remote for BCU I 1

RCD

 AVRAM  AVR auto/manual 1

CB Circuit breaker closed/opened 1

TC Tap changer raise/lower 1

Page 66: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 66/118

SPLN S5.003-1: 2014

52

TB-10: Bay Reaktor Pada Konfigurasi 1 ½ Breaker

BAY REAKTOR

PADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-10

BUSBAR - B

Q

Reaktor 

 

Gambar 21. Bay reaktor pada konfigurasi 1 ½ breaker

Tabel 18. Teleinformasi data untuk bay reaktor pada konfigurasi 1 ½ breaker

Data No Kode Fungsi Tipe Jmh

TM Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

VRT Voltage relay trip  A 1

TSD

ES Earth switch closed/opened I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/remote for BCU I 1

Page 67: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 67/118

SPLN S5.003-1: 2014

53

TB-11: Bay Reaktor Pada Konfigurasi Double Busbar

BAY REAKTOR

PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-11

BUSBAR - B

Q

Reaktor 

L/R

 

Gambar 22. Bay  reaktor pada konfigurasi double busbar

Tabel 19. Teleinformasi data untuk bay  reaktor pada konfigurasi double busbar  

Data No Kode Fungsi Tipe Jmh

TM Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

VRT Voltage relay trip  A 1

TSD

BI Bus Isolator Switch closed/opened I 2

CB Circuit breaker closed/opened I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for BCU I 1

RCD CB Circuit breaker closed/opened 1

Page 68: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 68/118

SPLN S5.003-1: 2014

54

TB-12: Bay Reaktor Pada Konfigurasi Single Busbar

BAY REAKTORPADA KONFIGURASI SINGLE BUSBAR

TB-12

BUSBAR

Q

Reaktor 

L/R

 

Gambar 23. Bay  reaktor pada konfigurasi single busbar  

Tabel 20. Teleinformasi data untuk bay  reaktor pada konfigurasi single busbar

Data No Kode Fungsi Tipe JmhTM Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

VRT Voltage relay trip  A 1

TSD

BI Bus Isolator Switch closed/opened I 1

CB Circuit breaker closed/opened I 1ES Earth switch closed/opened I 1

LRBCU Local/remote for BCU I 1

RCD CB Circuit breaker closed/opened 1

Page 69: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 69/118

SPLN S5.003-1: 2014

55

TB-13: Bay Capasitor Pada Konfigurasi Double Busbar

BAY KAPASITORPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-13

BUSBAR - B

Q

Capasitor 

L/R

 

Gambar 24. Bay capasi tor  pada konfigurasi double busbar  

Tabel 21. Teleinformasi data untuk bay  kapasitor pada konfigurasi double busbar

Data No Kode Fungsi Tipe Jmh

TM Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

VRT Voltage relay trip  A 1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

LRBCU Local remote for BCU I 1

RCD CB Circuit breaker closed/opened 1

Page 70: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 70/118

SPLN S5.003-1: 2014

56

TB-14: Bay Capasitor Pada Konfigurasi Single Busbar

BAY KAPASITOR

PADA KONFIGURASI SINGLE BUSBAR

TB-14

BUSBAR

Q

L/R

Capasitor 

 

Gambar 25. Bay capasi tor  pada konfigurasi single busbar  

Tabel 22. Teleinformasi data untuk bay  kapasitor pada konfigurasi single busbar  

Data No Kode Fungsi Tipe JmhTM Q Daya reaktif 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

VRT Voltage relay trip  A 1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

LRBCU Local remote for BCU I 1

RCD CB Circuit breaker closed/opened 1

Page 71: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 71/118

SPLN S5.003-1: 2014

57

TB-15: Bay Penghantar Pada Konfigurasi 1 ½ Breaker

BAY PENGHANTAR

PADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-15

BUSBAR - B

PQVI

 

Gambar 26. Bay penghantar pada konfigurasi 1 ½ breaker

Tabel 23. Teleinformasi data untuk bay penghantar pada konfigurasi 1 ½ breaker  

Data No Kode Fungsi Tipe Jmh

TM

F Frekuensi 1

V Tegangan 1

I Arus 1P Daya aktif 1

Q Daya reaktif 1

 AMF  Amperes fault 8

TSS

DISZ1 Distance protection zone 1  A  2

DISZ2 Distance protection zone 2  A  2

DISZ3 Distance protection zone 3  A  2

DISZ4 Distance protection zone 4  A  2

SOTF Switch on to fault  A  2

DEF Directional earth fault  A  2

LCD Line current differential  A  2

 AR Circuit breaker auto reclose success  A 

1 ARL Circuit breaker auto reclose lock out  A  1

Page 72: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 72/118

SPLN S5.003-1: 2014

58

CSP Check synchronizing in progress  A  1

OCGF Over current ground fault  A  1

OGSTX Overgenerating shedding transmit I 1

OLSTX Overload shedding transmit I 1

OVR Over voltage relay trip  A  1

DTT Direct transfer trip  A  1

TTR Teleprotection trip receive  A 1

TTT Teleprotection trip transmit I 1

OLSTX Overload shedding transmit I 1

OGSTX Overgenerating shedding transmit I 1

BF Bay fault  A  1

TSD

 ARO  Auto reclose On/Off I 1

LI Line isolator switch closed/opened I 1

ES Earth switch closed/opened I 1

TB-16: Bay Penghantar Pada Konfigurasi Double Busbar

BAY PENGHANTAR

PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-16

BUSBAR - B

L/R

QVI

P

 

Gambar 27. Bay  penghantar pada konfigurasi double busbar  

Page 73: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 73/118

SPLN S5.003-1: 2014

59

Tabel 24. Teleinformasi data untuk bay  penghantar pada konfigurasi double busbar  

Data No Kode Fungsi Tipe Jmh

TM

 AMF  Amperes fault 8

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

F Frekuensi 1

V Tegangan 1

TSS

BF Bay fault  A 1

BRF Breaker Fault  A 1

CSP Check synchronizing in progress I 1

 ARL Circuit breaker auto reclose lock out  A 1

 AR Circuit breaker auto reclose success  A 1

CBF Circuit Breaker Failure Trip  A 1

DTT Direct Transfer Trip  A 1

DEF Directional earth fault  A 1

DISZ1 Distance protection zone 1  A 1

DISZ2 Distance protection zone 2  A 1

DISZ3 Distance protection zone 3  A 1

DISZ4 Distance protection zone 4  A 1

LCD Line current differential  A 1

OCGF Over Current Ground Fault  A 1

OCPT Oil cable pressure trip  A 1*)

OGSTX Overgenerating shedding transmit I 1

OLSTX Overload shedding transmit I 1

SOTF Switch on to fault  A 1

TTR Teleprotection trip receive I 1

TTT Teleprotection trip transmit I 1UFRT Under Frequency Relay Trip  A 1

VRT Voltage relay trip  A 1

TSD

 ARO  Auto Reclose On Off I 1

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

ES Earth Switch Closed/Opened I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/Remote For BCU I 1

RCD CB Circuit breaker closed/opened 1

KETERANGAN:*) = Khusus untuk OHL Feeder  **)

= Khusus untuk Cable Feeder  

Page 74: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 74/118

SPLN S5.003-1: 2014

60

TB-17: Bay Penghantar Pada Konfigurasi Single Busbar

BAY PENGHANTAR

PADA KONFIGURASI SINGLE BUSBAR

TB-17

BUSBAR

PQVI

L/R

 

Gambar 28. Bay penghantar pada konfigurasi single busbar  

Tabel 25. Teleinformasi data untuk bay  penghantar pada konfigurasi single busbar  

Data No Kode Fungsi Tipe Jmh

TM

 AMF  Amperes fault 8

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

F Frekuensi 1

V Tegangan 1

TSS

BF Bay fault  A 1

BRF Breaker Fault  A 1

CSP Check synchronizing in progress I 1

 ARL Circuit breaker auto reclose lock out  A 1

 AR Circuit breaker auto reclose success  A 1

CBF Circuit Breaker Failure Trip  A 1DTT Direct Transfer Trip  A 1

DEF Directional earth fault  A 1

DISZ1 Distance protection zone 1  A 1

DISZ2 Distance protection zone 2  A 1

DISZ3 Distance protection zone 3  A 1

DISZ4 Distance protection zone 4  A 1

LCD Line current differential  A 1

OCGF Over Current Ground Fault  A 1

OCPT Oil cable pressure trip  A 1*)

OGSTX Overgenerating shedding transmit I 1

OLSTX Overload shedding transmit I 1SOTF Switch on to fault  A 1

Page 75: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 75/118

SPLN S5.003-1: 2014

61

TTR Teleprotection trip receive I 1

TTT Teleprotection trip transmit I 1

UFRT Under Frequency Relay Trip  A 1

VRT Voltage relay trip  A 1

TSD

 ARO  Auto Reclose On Off I 1

BI Bus isolator switch closed/opened I 1CB Circuit breaker closed/opened I 1

ES Earth Switch Closed/Opened I 1

LI Line isolator switch closed/opened I 1

LRBCU Local/Remote For BCU I 1

RCD CB Circuit breaker closed/opened 1

KETERANGAN:*)

= Khusus untuk OHL Feeder  **)

= Khusus untuk Cable Feeder  

Page 76: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 76/118

SPLN S5.003-1: 2014

62

TB-18: Bay Penghantar Paralel Dengan Reaktor Pada Konfigurasi DoubleBusbar

BAY PENGHANTAR

PARALEL DENGAN REAKTORPADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-18

BUSBAR - B

PQV

Q

I

L/R

 

Gambar 29. Bay  penghantar paralel dengan reaktor pada konfigurasi double busbar  

Tabel 26. Teleinformasi data untuk bay  penghantar serial dengan reaktor pada konfigurasidouble busbar  

Data No Kode Fungsi Tipe Jmh

TM

 AMF  Amperes fault 8I Arus 1

P Daya aktif 1

Q Daya reaktif 1

F Frekuensi 1

V Tegangan 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

CSP Check synchronizing in progress I 1

 ARL Circuit breaker auto reclose lock out  A 1

 AR Circuit breaker auto reclose success  A 1

CBF Circuit breaker failure trip  A 1

DTT Direct transfer trip  A 1

DEF Directional earth fault  A 1

Page 77: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 77/118

SPLN S5.003-1: 2014

63

DISZ1 Distance protection zone 1  A 1

DISZ2 Distance protection zone 2  A 1

DISZ3 Distance protection zone 3  A 1

DISZ4 Distance protection zone 4  A 1

LCD Line current differential  A 1

OCGF Over current ground fault  A 1OGSTX Overgenerating shedding transmit I 1

OLSTX Overload shedding transmit I 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

SOTF Switch on to fault  A 1

TTR Teleprotection trip receive I 1

TTT Teleprotection trip transmit I 1

UFRT Under frequency relay trip  A 1

VRT Voltage relay trip  A 1

TSD

CB Circuit breaker closed/opened I 1

 ARO  Auto Reclose On Off I 1

BI Bus isolator switch closed/opened I 2

LI Line isolator switch closed/opened I 2

ES Earth Switch Closed/Opened I 1

LRBCU Local/Remote For BCU I 1

RCD CB Circuit breaker closed/opened 1

TB-19: Bay Penghantar Paralel Dengan 1 Reaktor Pada Konfigurasi 1½Breaker

BAY PENGHANTAR

PARALEL DENGAN 1 REAKTORPADA KONFIGURASI 1½ BREAKER

BUSBAR - A

TB-19

BUSBAR - B

PQVQI

L/R

 

Gambar 30. Bay  penghantar paralel dengan 1 reaktor pada konfigurasi 1½ breaker  

Page 78: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 78/118

SPLN S5.003-1: 2014

64

Tabel 27. Teleinformasi data untuk bay  penghantar paralel dengan 1 reaktor padakonfigurasi 1½ breaker

Data No Kode Fungsi Tipe Jmh

TM

 AMF  Amperes fault 8

I Arus 1P Daya aktif 1

Q Daya reaktif 1

F Frekuensi 1

V Tegangan 1

TSS

BF Bay fault  A 1

BRF Breaker fault  A 1

CSP Check synchronizing in progress I 1

 ARL Circuit breaker auto reclose lock out  A 1

 AR Circuit breaker auto reclose success  A 1

CBF Circuit breaker failure trip  A 1

DTT Direct transfer trip  A 1DEF Directional earth fault  A 1

DISZ1 Distance protection zone 1  A 1

DISZ2 Distance protection zone 2  A 1

DISZ3 Distance protection zone 3  A 1

DISZ4 Distance protection zone 4  A 1

LCD Line current differential  A 1

OCGF Over current ground fault  A 1

RA Reaktor alarm  A 1

RT Reaktor trip  A 1

SOTF Switch on to fault  A 1

TTR Teleprotection trip receive I 1

TTT Teleprotection trip transmit I 1

UFRT Under frequency relay trip  A 1

VRT Voltage relay trip  A 1

TSD

 ARO  Auto reclose On/Off I 1

LI Line isolator switch closed/opened I 2

ES Earth switch closed/opened I 1

Page 79: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 79/118

SPLN S5.003-1: 2014

65

TB-20: Bay Kopel Pada Konfigurasi Double Busbar

BAY KOPEL

PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

TB-20

BUSBAR - B

L/R

I

 

Gambar 31. Bay kopel pada konfigurasi double busbar  

Tabel 28. Teleinformasi data untuk bay  kopel pada konfigurasi double busbar  

Data No Kode Fungsi Tipe Jmh

TM I Arus 1

TSS

CSP Check synchronizing in progress I 1

BF Bay fault  A 1

BRF Breaker fault  A 1

OCGF Over current ground fault  A 1

UFRT Under frequency relay trip  A 1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

LRBCU Local remote for BCU I 1

SIB Software Interlocking Bypassed I 1

RCD CB Circuit breaker closed/opened 1

Page 80: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 80/118

SPLN S5.003-1: 2014

66

LAMPIRAN 3. Daftar Teleinformasi (Distribusi)

3-1: Telesignal

Tabel 29. Daftar telesignal  distribusi

No Kode Fungsi ImplementasiIndikasiTSS/TSD

SumberH/LN 

BagianD/B/G/P

JumlahF/C

EventA/I

1  ARO  Auto reclose on/offOutgoingfeeder

TSD  LN B C I

2  AVRAM  Avr auto/manual Trafo TSD  LN B C I

3BI

Bus isolator switch

closed/opened

Kopel,OutgoingFeeder, Trafo,Incoming 20

KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSD  H D C I

4 CBCircuit breakerclosed/opened

Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSD  H D C I

5 RACKCircuit breakerrackin/rackout

Kopel,Outgoing

Feeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSD  H B C I

6 DCBDummy circuit breakerclosed/opened

Gardu induk TSD  H G C I

7 ESEarth switchclosed/opened

Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,

Bus Section,Gen Trafo,Generator

TSD  H D C I

8 GUC Generator unit run/stop Generator TSD  H P C I

9 LBSLoad break switchclosed/opened

Gardu induk TSD  H G C I

10 LRBCU Local/remote for bcu

Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,

Generator

TSD  LN B C I

11 LRHMI Local/remote for local hmi Gardu induk TSD  LN G C I

Page 81: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 81/118

SPLN S5.003-1: 2014

67

No Kode Fungsi ImplementasiIndikasiTSS/TSD

SumberH/LN 

BagianD/B/G/P

JumlahF/C

EventA/I

12 PSO Power station operated Generator TSD  H P C I

13 BF Bay fault

Busbar, Kopel,Outgoing

Feeder, Trafo,Incoming 20  KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSS  H B C A

14 BRF Breaker fault

Kopel,OutgoingFeeder, Trafo,Incoming 20  KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSS  H B C A

15 BUAL Building alarm Gardu induk TSS  LN D C A

16 ARLCircuit breaker autoreclose lock out

Outgoingfeeder

TSS  LN B C A

17 ARCircuit breaker autoreclose success

Outgoingfeeder

TSS  LN B C A

18 COM Communication faulty Gardu Induk TSS  H D C A

19 DEF Directional earth faultOutgoingfeeder

TSS  LN B F A

20 GFT Ground fault trip

Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,

Gen Trafo,Generator

TSS  LN B C A

21 IEDF IED bay level faulty Gardu Induk TSS  LN G C A

22 IGFTInstantaneous groundfault trip

Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSS  LN B C A

23 IOCT Instantaneous overcurrent trip

Kopel,OutgoingFeeder, Trafo,

Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSS  LN B C A

24 OCT Over current trip

Kopel,OutgoingFeeder, Trafo,Incoming 20KV, Kapasitor,Bus Section,Gen Trafo,Generator

TSS  LN B C A 

25 SLF Station level faulty Gardu Induk TSS  H B C A 

26 SF Supply failure Gardu Induk TSS  LN B C A

27 TCH Tap changer high limit Trafo TSS  H B C I

Page 82: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 82/118

SPLN S5.003-1: 2014

68

No Kode Fungsi ImplementasiIndikasiTSS/TSD

SumberH/LN 

BagianD/B/G/P

JumlahF/C

EventA/I

28 TCIP Tap changer in progress Trafo TSS  H B C I

29 TCL Tap changer low limit Trafo TSS  H B C I

30 UFRT Under frequency relay trip Outgoingfeeder TSS  LN B C A

31 UVRT Under voltage relay tripOutgoingfeeder

TSS  LN B C A

32 VACF VAC failure Gardu induk TSS  H G C A33 VDCF VDC failure Gardu induk TSS  H G C A34 VS Voltage status Busbar TSS  H B C I

KETERANGAN:

 A =  Alarm (audible alarm, flashing display, etc )I = Indikasi (normal condition)TSS = Telesignal single TSD = Telesignal double H = Hardwiring  

LN = Logical NetworkD =  per Device (peralatan)B =  per Bay  G = per GIP = per PembangkitF = per FasaC = Common 

3-2: Telemeasurement  

Tabel 30. Daftar telemeasurement

No Kode Fungsi ImplementasiSumber

H/LN BagianD/B/G/P

JumlahF/C

1 AMF  Amperes fault ( per phase )Kopel, Bus section,Outgoing Feeder,Incoming 20 kV

LN B F

2 F FrekuensiGardu induk, GenTrafo

H G C

3 I ArusOutgoing Feeder,Incoming  20 kV, GenTrafo

H B F

4 P Daya aktifOutgoing Feeder ,Incoming  20 kV, Gen

Trafo

LN B C

5 Q Daya reaktifOutgoing Feeder ,Incoming  20 kV, GenTrafo

LN B C

6 V TeganganBusbar,Gen Trafo

H B F

KETERANGAN:

Logical Node pada TM apabila nilai didapat melalui perhitungan beberapa parameter.Hardwiring  pada TM apabila nilai didapat melalui pengukuran dari sinyal masukan.* Per fasa untuk single phase.

Page 83: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 83/118

SPLN S5.003-1: 2014

69

3-3: Tap Changer Posit ion

Tabel 31. Daftar tap changer

No Kode Fungsi ImplementasiSumber

H/LN BagianD/B/G/P

JumlahF/C

1 TPI Tap position indication Trafo H B C/F*

Keterangan :* Per fasa untuk single phase.

3-4: Remote Control Digi ta l

Tabel 32. Daftar remote contro l dig i ta l

No Kode Fungsi Implementasi SumberH/LN  BagianD/B/G/P JumlahF/C

1 ARO  Auto reclose on/off Feeder LN B C

2 AVRAM Automatic Voltage Regulatorauto/manual

Trafo LN D C

3 CB Circuit breaker closed/opened

Kopel,OutgoingFeeder, Reaktor,Kapasitor, BusSection, Incoming  20kV

H D C

4 CAM Capacitor auto manual Kapasitor LN B C

5 DCBDummy circuit breakerclosed/opened

Gardu induk H G C

6 RPB Reset per bay

Kopel,OutgoingFeeder, Reaktor, Kapasitor, BusSection, Incoming 20

kV

H B C

7 TC Tap changer raise/lower Trafo H B C

Page 84: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 84/118

SPLN S5.003-1: 2014

70

LAMPIRAN 4. Teleinformasi pada Berbagai Konfigurasi Jaringan Distribusi

DA-01: Konfigurasi Umum Pada Double Busbar

KONFIGURASI UMUM PADA DOUBLE BUSBAR

BUSBAR- A

DA- 01

BUSBAR- B

Q

P

GENERATOR

FEEDERCAPASITOR

L/R

Q

PQ

L/R I

QP

V

L/R

L/R L/R

I

PF

V(R)V(S)V(T)

V(R)V(S)V(T)

P

KOPEL

I (R)

I (S)I (T)

INCOMING 20 KV

 

Gambar 32. Konfigurasi umum pada double busbar  

Tabel 33. Teleinformasi data untuk konfigurasi umum pada double busbar

Group Bay Data No Kode Fungsi Tipe Jmlh

GARDUINDUK

TM F Frekuensi 1

TSS

SLF Station level faulty  A  1 

IEDF Ied bay level faulty  A  1 

COM Communication faulty  A  1 

BUAL Building alarm  A  1 

VACF VAC failure  A  1 

VDCF VDC failure  A  1 

SF Supply failure  A  1 

Page 85: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 85/118

SPLN S5.003-1: 2014

71

Group Bay Data No Kode Fungsi Tipe Jmlh

TSD LBS Load break switch closed/opened I 1

RCD DCB Dummy CB closed/opened

BUSBAR

TM V Tegangan 2

TSSVS Voltage status I 2 

BF Bay fault  A  1 

BAYOUTGOINGFEEDER

TM

 AMF  Amperes fault 4

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

PF Power factor 1

TSS

DEF Directional earth fault  A  1

 AR Circuit breaker auto reclose success  A  1

 ARL Circuit breaker auto reclose lock out  A 1

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

UFRT Under frequency relay trip  A  1

UVRT Under voltage relay trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

 ARO  Auto reclose on/off I 1

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1LRBCU Local/remote for BCU I 1

RCD

 ARO  Auto reclose On/Off 1

CB Circuit breaker closed/opened 1

RPB Reset per bay 1

BAYINCOMING 20KV

TM

 AMF  Amperes fault 4

I Arus 3

P Daya aktif 1

Q Daya reaktif 1

PF Power factor 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1TM  AMF  Amperes fault 4

Page 86: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 86/118

SPLN S5.003-1: 2014

72

Group Bay Data No Kode Fungsi Tipe Jmlh

KOPEL

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD

CB Circuit breaker closed/opened 1

RPB Reset per bay 1

BAYKAPASITOR

TM Q Daya reaktif 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD CB Circuit breaker closed/opened 1RPB Reset per bay 1

BAYGENERATOR

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

F Frekuensi 1

V Tegangan 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A 

1BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

GUC Generator unit run/stop I 1

LRBCU Local/remote for BCU I 1

PSO Power station operated I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

Page 87: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 87/118

SPLN S5.003-1: 2014

73

DA-02: Konfigurasi Umum Pada Single Busbar

KONFIGURASI UMUM PADA SINGLE BUSBAR

BUSBAR - A

DA- 02

Q

P

GENERATOR

CAPASITOR

L/R

Q

PQ

L/R I

QP

V

L/R

L/R

I

PF

V(R)V(S)

V(T)

P

I (R)I (S)I (T)

INCOMING 20 KV

FEEDER

 

Gambar 33. Konfigurasi umum pada single busbar 

Page 88: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 88/118

SPLN S5.003-1: 2014

74

Tabel 34. Teleinformasi data untuk konfigurasi umum pada single busbar

Group Bay Data No Kode Fungsi Tipe Jmlh

GARDUINDUK

TM F Frekuensi 1

TSS

SLF Station level faulty  A  1 IEDF Ied bay level faulty  A  1 

COM Communication faulty  A  1 

BUAL Building alarm  A  1 

VACF VAC failure  A  1 

VDCF VDC failure  A  1 

SF Supply failure  A  1 

TSD LBS Load break switch closed/opened I 1

RCD DCB Dummy CB closed/opened

BUSBAR

TM V Tegangan 1

TSSVS Voltage status I 1 

BF Bay fault  A  1 

BAYOUTGOINGFEEDER

TM

 AMF  Amperes fault 4

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

PF Power factor 1

TSS

DEF Directional earth fault  A  1

 AR Circuit breaker auto reclose success  A  1

 ARL Circuit breaker auto reclose lock out  A 1

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

UFRT Under frequency relay trip  A  1

UVRT Under voltage relay trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

 ARO  Auto reclose on/off I 1

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for BCU I 1

RCD

 ARO  Auto reclose On/Off 1

CB Circuit breaker closed/opened 1

RPB Reset per bay 1

TM

 AMF  Amperes fault 4

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

PF Power factor 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1IOCT Instantaneous over current trip  A  1

Page 89: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 89/118

SPLN S5.003-1: 2014

75

Group Bay Data No Kode Fungsi Tipe Jmlh

BAYINCOMING 20

KV

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/openedI 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

KOPEL

TM  AMF  Amperes fault 4

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD

CB Circuit breaker closed/opened 1

RPB Reset per bay 1

BAYKAPASITOR

TM Q Daya reaktif 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

BAYGENERATOR

TM

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

F Frekuensi 1

V Tegangan 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

BI Bus isolator switch closed/opened I 1CB Circuit breaker closed/opened I

Page 90: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 90/118

SPLN S5.003-1: 2014

76

Group Bay Data No Kode Fungsi Tipe Jmlh

TSD

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

GUC Generator unit run/stop I 1

LRBCU Local/remote for BCU I 1PSO Power station operated I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-01: Trafo 150/20 kV dan 70/20 kV Tipe 1

TRAFO 150/20 KV DAN 70/20 KVDB- 01

TYPE 1

RCC

DCC

L/RP

Q

I

PF

 

Gambar 34. Trafo 150/20 kV dan 70/20 kV tipe 1  

Tabel 35. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 1

Group Bay   Data No Kode Fungsi Tipe Jmh

Busbar

TM V Tegangan 2

TSSVS Voltage status I 2 

BF Bay fault  A  1 

BAYINCOMING

20 KV

TM

 AMF  Amperes fault 4

I Arus 1

P Daya aktif 1

Q Daya reaktif 1PF Power factor 1

Page 91: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 91/118

SPLN S5.003-1: 2014

77

Group Bay   Data No Kode Fungsi Tipe Jmh

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A 

1BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 0

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-02: Trafo 150/20 kV dan 70/20 kV Tipe 2

TRAFO 150/20 KV DAN 70/20 KVDB -02

TYPE 2

RCC

DCC

P

Q

I

PF

L/R

 

Gambar 35. Trafo 150/20 kV dan 70/20 kV tipe 2

Tabel 36. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 2

Group Bay   Data No Kode Fungsi Tipe Jmh

Busbar

TM V Tegangan 2

TSSVS Voltage status I 2 

BF Bay fault  A  1 

BAYINCOMING 

TM AMF  Amperes fault 4

I Arus 1

Page 92: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 92/118

SPLN S5.003-1: 2014

78

Group Bay   Data No Kode Fungsi Tipe Jmh

20 KV P Daya aktif 1

Q Daya reaktif 1

PF Power factor 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCD RPB Reset per bay 1

DB-03: Trafo 150/20 kV dan 70/20 kV Tipe 3

TRAFO 150/20 KV DAN 70/20 KVDB -03

TYPE 3

RCC

DCC

P

Q

I

PF

L/R

 

Gambar 36. Trafo 150/20 kV dan 70/20 kV tipe 3

Tabel 37. Teleinformasi data untuk trafo 150/20 kv dan 70/20 kv tipe 3

Group Bay   Data No Kode Fungsi Tipe Jmh

Busbar

TM V Tegangan 1

TSS VS Voltage status I 1 

BF Bay fault  A  1 

Page 93: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 93/118

SPLN S5.003-1: 2014

79

Group Bay   Data No Kode Fungsi Tipe Jmh

BAYINCOMING 20 KV

TM

 AMF Amperes fault 4

I Arus 1

P Daya aktif 1

Q Daya reaktif 1PF Power factor 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 0

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-04: Generator Pada Konfigurasi Double Busbar

GENERATOR PADA KONFIGURASI DOUBLE BUSBAR

BUSBAR - A

DB-04

BUSBAR - B

P

V

QI

PQ

L/R

 

Gambar 37. Generator pada konfigurasi double busbar

Page 94: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 94/118

SPLN S5.003-1: 2014

80

Tabel 38. Teleinformasi data untuk generator pada konfigurasi double busbar

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 1

TSS VS Voltage status I 1 

BF Bay fault  A  1 

BAYGENERATOR  

TM

I Arus 1

P Daya aktif 2

Q Daya reaktif 2

F Frekuensi 1

V Tegangan 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 0

ES Earth switch closed/opened I 1

GUC Generator unit run/stop I 1

LRBCU Local/remote for BCU I 1

PSO Power station operated I 1

RCD

CB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-05: Generator Pada Konfigurasi Single Busbar

GENERATOR PADA KONFIGURASI SINGLE BUSBAR

BUSBAR

DB-05

P

V

QI

PQ

L/R

 

Gambar 38. Generator pada konfigurasi single busbar  

Page 95: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 95/118

SPLN S5.003-1: 2014

81

Tabel 39. Teleinformasi data untuk generator pada konfigurasi single busbar

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 1

TSSVS Voltage status I 1 

BF Bay fault  A  1 

BAY

GENERATOR  

TM

I Arus 1

P Daya aktif 2

Q Daya reaktif 2

F Frekuensi 1

V Tegangan 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 1

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 0

ES Earth switch closed/opened I 1

GUC Generator unit run/stop I 1

LRBCU Local/remote for BCU I 1

PSO Power station operated I 1

RCD

CB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-06: Feeder 20 kV Tipe 1

FEEDER 20 KVDB-06

TYPE 1

L/R

P

I ( R)

I ( S)

I ( T)

 

Gambar 39. Feeder  20 kV tipe 1 

Page 96: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 96/118

SPLN S5.003-1: 2014

82

Tabel 40. Teleinformasi data untuk feeder 20 kv tipe 1

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 2

TSS VS Voltage status I 2 

BF Bay fault  A  1 

BAYOUTGOINGFEEDER  

TM

 AMF  Amperes fault 4

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

PF Power factor 1

TSS

DEF Directional earth fault  A  1

 AR Circuit breaker auto reclose success  A  1

 ARL Circuit breaker auto reclose lock out  A 1

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

UFRT Under frequency relay trip  A  1

UVRT Under voltage relay trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

 ARO  Auto reclose on/off I 1

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for BCUI 1

RCD

 ARO  Auto reclose On/Off 1

CB Circuit breaker closed/opened I 1

RPB Reset per bay 1

Page 97: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 97/118

SPLN S5.003-1: 2014

83

DB-07: Feeder 20 kV Tipe 2

FEEDER 20 KVDB-07

TYPE 2

L/R

P

I ( R)

I ( S)

I ( T )

 

Gambar 40. Feeder  20 kV tipe 1 

Tabel 41. Teleinformasi data untuk feeder  20 kv tipe 1

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 1

TSSVS Voltage status I 1 

BF Bay fault  A  1 

BAYOUTGOINGFEEDER  

TM

 AMF  Amperes fault 4

I Arus 1

P Daya aktif 1

Q Daya reaktif 1

PF Power factor 1

TSS

DEF Directional earth fault  A  1

 AR Circuit breaker auto reclose success  A  1

 ARL Circuit breaker auto reclose lock out  A 1

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

UFRT Under frequency relay trip  A  1

UVRT Under voltage relay trip  A  1

BRF Breaker fault  A  1

Page 98: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 98/118

SPLN S5.003-1: 2014

84

Group Bay   Data No Kode Fungsi Tipe Jmh

BF Bay fault  A  1

TSD

 ARO  Auto reclose on/off I 1

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for BCU I 1

RCD

 ARO  Auto reclose On/Off 1

CB Circuit breaker closed/opened I 1

RPB Reset per bay 1

DB-09: Bus Section 20 kV Tipe 1

BUS SECTION 20 KVTYPE 1

DB- 09

L/R

 

Gambar 41. Bus sect ion  20 kV tipe 1

Tabel 42. Teleinformasi data untuk bus section 20 kv tipe 1

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 2

TSSVS Voltage status I 2 

BF Bay fault A  1 

TM  AMF Amperes fault 4

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

Page 99: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 99/118

SPLN S5.003-1: 2014

85

Group Bay   Data No Kode Fungsi Tipe Jmh

BAYBUSSECTION

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

BI Bus isolator switch closed/opened I 2

CB Circuit breaker closed/opened I 1RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-10: Bus section 20 kV Tipe 2

BUS SECTION 20 KVTYPE 2

DB -10

L/R

 

Gambar 42. Bus sect ion  20 kV tipe 2 

Tabel 43.Teleinformasi data untuk bus section 20 kv tipe 2

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 2

TSSVS Voltage status I 2 

BF Bay fault  A  1 

TM  AMF  Amperes fault 4

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1IOCT Instantaneous over current trip  A  1

Page 100: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 100/118

SPLN S5.003-1: 2014

86

Group Bay   Data No Kode Fungsi Tipe Jmh

BAYBUSSECTION

BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-11: Kopel

KOPELDB -11

L/R

 

Gambar 43. Kopel

Tabel 44. Teleinformasi data untuk kopel

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 2

TSSVS Voltage status I 2 

BF Bay fault  A  1 

BAY

TM  AMF  Amperes fault 4

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A 

1IOCT Instantaneous over current trip  A  1

Page 101: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 101/118

SPLN S5.003-1: 2014

87

Group Bay   Data No Kode Fungsi Tipe Jmh

KOPEL BRF Breaker fault  A  1

BF Bay fault  A  1

TSD

CB Circuit breaker closed/opened I 1

RACK Circuit breaker rackin/rackout I 1ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

DB-12: Capacitor Bay

CAPACITOR BAYDB-12

Q L/R

 

Gambar 44. Capaci tor bay

Tabel 45. Teleinformasi data untuk capasitor bay

Group Bay   Data No Kode Fungsi Tipe Jmh

BUSBAR

TM V Tegangan 2

TSSVS Voltage status I 2 

BF Bay fault  A  1 

BAYKAPASITOR

TM Q Daya reaktif 1

TSS

GFT Ground fault trip  A 1

IGFT Instantaneous ground fault trip  A 1

OCT Over current trip  A  1

IOCT Instantaneous over current trip  A  1

BRF Breaker fault  A  1

BF Bay fault  A  1

TSDBI Bus isolator switch closed/opened I 2CB Circuit breaker closed/opened I 1

Page 102: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 102/118

SPLN S5.003-1: 2014

88

Group Bay   Data No Kode Fungsi Tipe Jmh

RACK Circuit breaker rackin/rackout I 1

ES Earth switch closed/opened I 1

LRBCU Local/remote for bcu I 1

RCDCB Circuit breaker closed/opened 1

RPB Reset per bay 1

Page 103: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 103/118

SPLN S5.003-1: 2014

89

LAMPIRAN 5. Struktur Informasi

STRUKTUR INFORMASI 

Struktur informasi terdiri dari 112 karakter yang dapat dikelompokkan menjadi sembilanbagian, yaitu:

 A B C D E F G H I

Bagian A: Nomor ID, terdiri dari 6 digit (sebagai primary key )Bagian B: Time stamp, sebanyak karakter 23 karakterBagian C: Nama GI/GH/GT/KP, sebanyak 20 karakterBagian D: Level tegangan, sebanyak 5 karakterBagian E: Nama bay / feeder, sebanyak 20 karakterBagian F: Kode nama peralatan atau nama alarm atau nama elemen, sebanyak 5

karakterBagian G: Status peralatan atau status alarm, sebanyak 15 karakterBagian H: Nama user yang melakukan aksi (seperti remote control, dan sebagainya),

sebanyak 10 karakterBagian I: Prioritas alarm, sebanyak 8 karakter

Struktur di atas ditentukan dalam field yang berbeda.Contohnya dapat dilihat pada tabel 62.

Tabel 46. Struktur informasi

A B C D E F G H IRCC Cawang110007 02/03/2007 11:10:05.320 Cawang 150 Gandul-1 BI1 Close Class-3

110009 05/03/2007 07:00:55.115 Gandul 150 Cawang-1 ARO Appear Class-2

RCC Waru140104 11/04/2007 17:44:21.220 Rungkut 150 Waru-1 LT Disappear Class-1

140085 12/04/2007 20:11:51.312 Waru 150 Bangil-1 CB Invalid Class-4

DCC Pasuruan430011 25/04/2007 00:30:35.000 Gondang Wetan 20 Bromo CB Open Adi Class-1430012 19/11/2007 10:00:05.520 Gondang Wetan 20 Semeru CBTR Appear Class-1

1. A. Nomor ID

Nomor ID (bagian A) terdiri dari dua bagian. Bagian A1 terdiri dari 3 digit yangmenyatakan kode area. Bagian A2 terdiri dari 3 digit merupakan nomor RTUbersangkutan. Nomor ID dinyatakan dengan susunan sebagai berikut

 A1 A2

Bagian A1: Kode areaBagian A2: Nomor RTU

Page 104: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 104/118

SPLN S5.003-1: 2014

90

Kode area

Kode area yang terdiri dari 3 karakter adalah sebagai berikut:NCC : 900

IRCC : x00IRCC Jawa-Bali : 100IRCC Sumatera : 200IRCC Kalimantan : 300IRCC Sulawesi : 400IRCC di Indonesia Timur : 500

RCC di Jawa-Bali : 1xxRCC Cawang : 110RCC Cigereleng : 120RCC Ungaran : 130

RCC Waru : 140RCC di Sumatera : 2xxRCC Medan : 210RCC Padang : 220RCC Palembang : 230RCC di Kalimantan : 3xxRCC Banjarbaru : 310RCC Balikpapan : 320RCC di Sulawesi : 4xxRCC Makassar : 410RCC Manado : 420RCC di Indonesia Timur : 5xx

IDCC : x00IDCC Jawa-Bali : 100, 200, 300, 400IDCC Sumatera : 500, 600IDCC Kalimantan : 700IDCC Sulawesi : 800IDCC di Indonesia Timur : 900

DCC di Jakarta : 0xx – 1xxDCC daerah Jawa bagian Barat : 2xxDCC daerah Jawa bagian Tengah : 3xxDCC daerah Jawa bagian Timur dan Bali : 4xx

DCC daerah Sumatera : 5xx – 6xxDCC daerah Kalimantan : 7xxDCC daerah Sulawesi : 8xxDCC daerah Indonesia Timur : 9xx

Nomor RTU

Nomor RTU terdiri dari 3 digit (001 – 999)

Page 105: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 105/118

SPLN S5.003-1: 2014

91

B. Time stamp

Struktur informasi yang menggambarkan time stamp atau waktu suatu kejadian terdiri dari23 karakter. Struktur informasinya berturut-turut terdiri dari tanggal (2 karakter), bulan (2karakter), tahun (4 karakter), jam (2 karakter), menit (2 karakter), dan detik (6 karakteratau sampai dengan orde milidetik). Contohnya:

25/04/2007 00:30:35.000

19/11/2007 10:00:05.520

C. Nama GI/GH/GT

Nama GI/GH/GT dituliskan dalam bentuk nama lengkap (maksimal 20 karakter).Contohnya adalah sebagai berikut:

CawangGandulGondang WetanRungkutWaru

Cawang : menyatakan GI Cawang (dikontrol oleh RCC Cawang).Gandul : menyatakan GI Gandul (dikontrol oleh RCC Cawang).Waru : menyatakan GI Waru (dikontrol oleh RCC Waru).Rungkut : menyatakan GI Rungkut (dikontrol oleh RCC Waru).Gondang Wetan : menyatakan GI/GH/GT Gondang Wetan (dikontrol oleh DCC

Pasuruan).

D. Level Tegangan

Level tegangan terdiri dari 5 karakter. Contohnya dapat dilihat pada tabel 47.

Tabel 47. Level tegangan 

Tegangan Level Tegangan

500 kV 500

275 kV 275

150 kV 150

66 kV 66

30 kV 30

20 kV 20

11 kV 11

6.6 kV 6

3.3 KV 3

Page 106: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 106/118

SPLN S5.003-1: 2014

92

E. Nama Bay / Feeder  

Nama Bay/Feeder  terdiri dari 20 karakter. Contohnya dapat dilihat pada tabel 48.

Tabel 48. Nama bay atau feeder

Nama Bay / Feeder   Kode

Pusat Listrik

Pusat Listrik Tenaga Air PLTA

Pusat Listrik Tenaga Diesel PLTD

Pusat Listrik Tenaga Gas PLTG

Pusat Listrik Tenaga Panas Bumi PLTP

Pusat Listrik Tenaga Nuklir PLTN

Pusat Listrik Tenaga Uap PLTU

Pusat Listrik Gas/Uap (Combine Cycle) PLTGU

Pusat Listrik Tenaga Mikrohidro PLTMH

Pusat Listrik Tenaga Angin/Bayu PLTB

Pusat Listrik Tenaga Surya PLTS

Peralatan di Gardu Induk

LineBay (FeederBay)  Format penulisan:  IRCC/RCC:

Nama GI lawan + ”-” + nomor

penghantar. Contohnya:o  Gandul-1

o  Cawang-1  DCC:

Nama Feeder. Contohnya:o  Bromoo  Semeru

Bay ke Unit Generator UNIT

Busbar BUSBAR

Kopel (Bus Tie) KOPEL

Bus Section BUSSECT

Trafo TRAFOx (X adalah Kode Tegangandari primer dan sekunder trafo)

Diameter DAMTR

Shunt Reactor SHTXL

Shunt Capacitor SHTXC

Cadangan SPARE

Nama Bay

Bay 500 kV diameter 1 busbar A 7A1

Bay 500 kV diameter 3 antara busbar Adan B

7AB3

Bay 500 kV diameter 5 busbar B 7B5

Page 107: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 107/118

SPLN S5.003-1: 2014

93

Kode tegangan dari primer dan sekunder trafo dapat dilihat pada tabel 49.

Tabel 49. Kode tegangan dari primer dan sekunder trafo

Tegangan (KV) Range IEC

Tegangan Rendah (TR) < 1 kV NTegangan Menengah (TM) 1 sampai<6 kV M

Tegangan Menengah (TM) 6 sampai <10 kV L

Tegangan Menengah (TM) 10 sampai <20 kV K

Tegangan Menengah (TM) 20 sampai <30 kV J

Tegangan Menengah (TM) 30 sampai <45 kV H

Tegangan Tinggi (TT) 45 sampai <60 kV G

Tegangan Tinggi (TT) 60 sampai <110 kV F

Tegangan Tinggi (TT) 110 sampai <220 kV E

Tegangan Ekstra Tinggi (TET) 220 sampai <380 kV D

Tegangan Ekstra Tinggi (TET) 380 sampai ≤ 420 kV CTegangan Ekstra Tinggi (TET) > 420 kV B

F. Kode Nama Peralatan atau Nama Alarm  atau Nama Elemen

Kode nama peralatan atau nama alarm atau nama elemen terdiri dari maksimal 5karakter. Contohnya dapat dilihat pada tabel 50.

Tabel 50. Kode nama peralatan/alarm  /elemen 

Nama Kode

Circuit Breaker CB

Bus Isolator #1 BI1

Bus Isolator #2 BI2

Line Isolator LI

Ground Fault GF

Over Current OC

Line Trip LT

Breaker Fault BRF

Power Supply Faulty PSF

Daya MW PDaya MVAr Q

 Arus I

Load Break Switch LBS

Recloser REC

Kode nama peralatan dapat juga berupa kode teleinformasi (telesignal, telemeasurement  atau r emote kontrol seperti ditunjukan pada Lampiran A-D).

Page 108: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 108/118

SPLN S5.003-1: 2014

94

G. Status Peralatan atau Status Alarm

Status peralatan atau status alarm terdiri dari 15 karakter, menunjukkan status dariperalatan atau alarm pada bagian E.Contohnya adalah sebagai berikut:

- Close;- Open;- Invalid;- Appear;- Disappear;- On;- Off.

H. Nama user yang melakukan aksi

Nama user terdiri dari maksimal 10 karakter, menunjukkan nama user yang login padasaat melakukan aksi tertentu seperti Remote Control , Overall Check , start dan stopperangkat keras, out of service RTU dan Inter Center Link , dan sebagainya.

Contohnya adalah sebagai berikut:

TriLukmanJufriJokoParlinRiko

I. Prioritas Alarm

Prioritas alarm terdiri dari 8 karakter, menunjukkan kelas alarm yang ditampilkan. Class 1merupakan kelas alarm yang menempati prioritas paling tinggi.

Contohnya sebagai berikut:

Class-1Class-2Class-3Class-4

Struktur Informasi Khusus

Penamaan Pemutus Tenaga Pada Gardu Induk 1 ½ Breaker.

Struktur informasi khusus untuk pemutus tenaga pada gardu induk 1 ½ breaker dipakaiuntuk tujuan komunikasi verbal diantara operator. Kode tersebut hanya ditampilkan diVDU (Video Display Unit ), dan dipergunakan di dalam database. Struktur informasidinyatakan dengan susunan sebagai berikut:

X Y Z

Bagian X: kode referensi teganganBagian Y: kode nama CB

Page 109: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 109/118

SPLN S5.003-1: 2014

95

Bagian Z: nomor diameter

Contoh: A untuk breaker yang terhubung langsung ke busbar AB untuk breaker yang terhubung langsung ke busbar B AB untuk breaker yang terhubung ke breaker A dan breaker  B

Contohnya dapat dilihat pada Gambar 4545.

Untuk tegangan 500 kV diameter no. 1 Untuk tegangan 150 kV diameter no.4

Gambar 45. Struktur informasi khusus (bay diameter)

Page 110: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 110/118

SPLN S5.003-1: 2014

96

Contoh :

GITET 500 kVSAGULING

UNIT 2 UNIT 3 UNIT 4UNIT 1

CIRATA 1 CIRATA 2

BANDUNG SELATAN 2

BUSBAR A

BUSBAR B

CIBINONG 1

7A1

7AB1

7B1

~ ~

7A3

7AB3

7B3

7AB4

7B4

7AB5

7B5

BANDUNGSELATAN 1

~ ~

CIBINONG 2

7A2

7AB2

7B2

 

Gambar 46. Struktur informasi khusus (gardu induk 1½ breaker )

Page 111: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 111/118

 SPLN S5.003-1: 2014

97

LAMPIRAN 6. Simbol dan Warna

Simbol-simbol gambar yang digunakan mengacu pada gambar 47.

SIMBOL GAMBAR

Generator 

Circuit Breaker 

Circuit Breaker Rack

Isolating Switch

Earthing Switch

Current Transformer 

Voltage Transformer 

Reaktor 

Capacitor Voltage

Transformer 

Trafo Daya Dua Belitan

Trafo Daya Tiga Belitan

 Arus

Tegangan

Frekuensi

Daya aktif 

Daya reaktif 

Tap Position Indication

Remote Control Digital

Telesignal Single

Local/ Remote

Load Frequency Control

I

V

F

P

Q

TPI

RCD

TSS

L/R

LFC(Po, Pr,N)

Kapasitor  Remote Control AnalogRCA

Telesignal DoubleTSS

Surge /Lightning Arrester 

(Disconnecting Switch)

(3 phases )

PBO

 

Pemutus Balik Otomatis

Load Break Switch

Gardu Distribusi

Cut out fuse

Inverter 

Rectifier 

Battery

Battery

AGC  Automatic Gain Control

Neutral Ground Resistor 

 

Gambar 47. Simbol gambar

Page 112: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 112/118

SPLN S5.003-1: 2014

98

Tampilan-tampilan status yang digunakan mengacu pada gambar 48.

Tampilan Status

GENERATOR

ITEMS SYMBOL R E M A R K

CB CLOSED

CB OPENED

DS CLOSED

DS OPENED

ES CLOSED

ES OPENED

RACKED IN CB CLOSED

Busbar ' s color, filled

Busbars color, blank

TRANSF. 2 WINDINGS

TRANSF. 3 WINDINGS

REACTOR

CAPACITOR

LBS CLOSED

LBS OPENED

RACKED OUT CB CLOSED

Feeder’s color 

Feeder’s color 

Feeder’s color , filled

Feeder’s color  blank

Ground’s color 

Feeder’s color 

Feeder’s color , filled

Feeder’s color , filled

Feeder’s color 

Feeder’s color 

Feeder’s color 

Feeder’s color 

Feeder’s color 

VOLTAGE STATUS: LIVE

DEAD

CB INVALID Purple,

LBS INVALID Purple

DS INVALID  Purple, half- filled

ES INVALID Purple

RACKED INVALID CB CLOSED Feeder’s color , filled

RACKED IN CB OPENED

RACKED OUT CB OPENED

Feeder’s color , blank

Feeder’s color , blank

RACKED INVALID CB OPENED Feeder’s color , blank

RACKED IN CB INVALID

RACKED OUT CB INVALID

Feeder’s color , half-filled

Feeder’s color , half- filled

RACKED INVALID CB INVALID Feeder’s color , half- filled

CB UNKNOWN Orange, Half-filled

Half-filled

DS UNKNOWN Orange, half-filled

ES UNKNOWN Orange

 

Gambar 48. Tampilan status 

Page 113: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 113/118

 SPLN S5.003-1: 2014

99

WARNA TAMPILAN

Tabel 51 berikut ini menjelaskan mengenai warna tampilan yang berlaku untuk monitordan layar tayang. Pewarnaan SLD yang dinamis didasarkan atas dua sumber yaitu:

- Secara logika (berdasarkan posisi PMT dan PMS) dan pengukuran tegangan.- Secara logika (berdasarkan posisi PMT dan PMS) untuk bagian yang tidakmemiliki VT.

Tabel 51. Warna tampilan 

URAIAN WARNA (R,G,B)

Single line diagram 500 kV Biru (0,100,255)Single line diagram 275 kV Biru-muda (0,200,255)Single line diagram 150 kV Merah (255,0,0)Single line diagram 66 kV Kuning (255,255,0)Single line diagram 30 kV Hijau (0, 255, 0)Single line diagram 20 kV Coklat (200, 150, 0)Single line diagram 11 kV Abu-abu (180, 180, 180)Single line diagram 6 kV Merah muda (255, 150, 180)Single line diagram 3,3 kV Hijau-muda (0, 255, 150)

 All devices  Warna BusbarInvalid device  Ungu dan perubahan simbol (220, 0, 255)Device saat loss connection (out of poll)  Oranye (255, 150, 50)Background color   Hitam (0, 0, 0)Ground color   Biru-tua (10, 10, 180)Kondisi tidak bertegangan Putih (255, 255, 255)Perubahan status karena gangguan Frame CB warna merah, blinkingPerubahan status karena local dari gardu induk Warna Busbar, blinking + karakter”L” Perubahan status karena r emote dari Warna Busbar, blinking  dispatcherTelemetering   Putih (255, 255, 255)

Invalid telemetering   Ungu (220, 0, 255)Unknown  Oranye (255, 150, 50)Telesignal Alarm :

Off   : sesuai warna latar kotak annunciator   Aktif : Terisi solid warna Merah, blinking.

Setelah di acknowledge tidak blinking.

Keterangan:

  Untuk change of state gangguan, setelah acknowledge  blinking hilang, warna merahpada frame CB mengikuti warna busbar.

  Untuk level tegangan yang tidak tercantum dalam tabel di atas, menggunakan warna

pada single line diagram level tegangan terdekat.  Warna jaringan sesuai dengan feeder colouring .

  Untuk detail kode warna akan dijelaskan pada SPLN mengenai kode simbol danwarna.

Page 114: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 114/118

Page 115: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 115/118

Page 116: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 116/118

Pengelola Standardisasi :

PT PLN (Persero) Pusat Penelitian dan Pengembangan Ketenagalistrikan

Jl. Durentiga, Jakarta 12760, Telp. 021-7973774, Fax. 021-7991762,

www.pln-litbang.co.id

Page 117: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 117/118

Page 118: Spln s5.003-1 2014 Tele Informasi Plan

7/23/2019 Spln s5.003-1 2014 Tele Informasi Plan

http://slidepdf.com/reader/full/spln-s5003-1-2014-tele-informasi-plan 118/118