Sidoarjo Total

46
7/23/2019 Sidoarjo Total http://slidepdf.com/reader/full/sidoarjo-total 1/46  FINAL REPORT PELATIHAN TEKNIS EFISIENSI ENERGI DI PDAM SIDOARJO KERJASAMA : ETC  ESP MLD PDAM SIDOARJO AKADEMI TEKNIK TIRTA WIYATA

Transcript of Sidoarjo Total

Page 1: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 1/46

 

FINAL REPORT

PELATIHAN TEKNIS EFISIENSI ENERGI

DI PDAM SIDOARJO 

KERJASAMA :

ETC – ESP

MLD

PDAM SIDOARJO

AKADEMI TEKNIK TIRTA WIYATA

Page 2: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 2/46

1

DAFTAR ISI

DAFTAR ISI ................................................................................................................................... 1

DAFTAR GAMBAR....................................................................................................................... 3

DAFTAR TABEL ........................................................................................................................... 4

DAFTAR ISTILAH ........................................................................................................................ 6

RINGKASAN ................................................................................................................................. 8 

1. PENDAHULUAN ................................................................................................................ 11

1.1 LATAR BELAKANG ..................................................................................................................................... 11

1.2 TUJUAN .......................................................................................................................................................... 11

1.3 RUANG LINGKUP KEGIATAN ............................................................................................................... 12

1.4 METODOLOGI ............................................................................................................................................. 12

1.5 GAMBARAN UMUM PDAM SIDOARJO ............................................................................................... 13

2. PENGUMPULAN DAN PENGOLAHAN DATA SEKUNDER ....................................... 17

2.1 SPESIFIKASI POMPA DAN MOTOR ....................................................................................................... 17

2.2 KONSUMSI DAN BIAYA ENERGI ........................................................................................................... 18

2.3 PRODUKSI AIR ............................................................................................................................................. 21

3. PENGUKURAN LAPANGAN (DATA PRIMER) .............................................................. 22

3.1 PERPOMPAAN TAWANGSARI ............................................................................................................... 23

3.2 PERPOMPAAN UNIT WARU II ............................................................................................................... 25

4. ANALISIS DAN PEMBAHASAN DATA .............................................................................. 27

4.1 UMUM.............................................................................................................................................................. 27

4.2 ANALISIS DAN PEMBAHASAN DATA.................................................................................................. 29

5. KENDALA  –  KENDALA YANG DIHADAPI ........................................................................ 41 

Page 3: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 3/46

2

6. KESIMPULAN ...................................................................................................................... 41

7. REKOMENDASI DAN PELUANG PENGHEMATAN ..................................................... 43

Page 4: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 4/46

3

DAFTAR GAMBAR

Gambar 1. Grafik Konsumsi Energy Bulanan Unit Tawangsari  .................................................................. 19

Gambar 2. Grafik Konsumsi Energy Bulanan Unit Waru II ........................................................................ 20

Gambar 3. Skematik Jaringan Pompa Boster Tawangsari  ........................................................................... 23

Gambar 4. Skematik Jaringan Pompa Waru II  ............................................................................................ 25

Gambar 5. Pengukuran Debit Pompa Di Unit Waru II  ............................................................................. 25

Page 5: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 5/46

4

DAFTAR TABEL

Tabel 1. Hasil Ringkasan Kegiatan Efisiensi PDAM Sidoarjo  ..................................................................... 9

Tabel 2. Hasil Ringkasan Kegiatan Efisiensi PDAM Sidoarjo ....................................................................... 9

Tabel 3. Potensi Penghematan di Tawangsari ........................................................................................... 10

Tabel 4. Potensi Penghematan di Waru II  ................................................................................................ 10

Tabel 5. Produksi Air PDAM Delta Tirta Sidoarjo ................................................................................... 16

Tabel 6. Data Name Plate Motor & Pompa Tawangsari  .......................................................................... 17

Tabel 7. Data Nameplate Motor dan Pompa Unit Waru II ...................................................................... 18

Tabel 8. Konsumsi dan Biaya Listrik Unit Tawangsari .............................................................................. 19

Tabel 9. Konsumsi dan Biaya Energy Listrik Untuk Pompa Waru II ........................................................ 20

Tabel 10. Produksi Air Tawangsari  ............................................................................................................. 21

Tabel 11. Produksi Air Waru II  .................................................................................................................. 21

Tabel 12. Data Hasil Pengukuran Lapangan di Unit Tawangsari  ................................................................. 24

Tabel 13. Data Hasil Pengukuran Motor Listrik Tiap Phasa Pompa Tawangasari  ...................................... 24

Tabel 14. Data Hasil Pengukuran Lapangan di Unit Waru II  ...................................................................... 26

Tabel 15. Data Hasil Pengukuran Motor Listrik Tiap Phasa Pompa Waru II ............................................. 26

Tabel 16. Konsumsi Energi Spesifik (SEC) Perpompaan Unit Tawangsari :  ................................................ 29

Tabel 17. Konsumsi Energi Spesifik (SEC) Perpompaan Tawangsari .......................................................... 30

Tabel 18. Konsumsi Energi Spesifik (SEC) System II, Tawangsari  .............................................................. 30

Tabel 19. Analisis Efisiensi dan Konsumsi Energy Spesifik, Unit Tawangsari .............................................. 31

Tabel 20. Analisis/ Penilaian Energy Motor, Unit Tawangsari ..................................................................... 34

Tabel 21. SEC Global Unit Waru II  ............................................................................................................ 34

Tabel 22. Konsumsi Energi Spesifik (SEC) Sistem I, Waru II ...................................................................... 35

Tabel 23. SEC System II, Waru II  ................................................................................................................ 35

Tabel 24. Analisis Efisiensi Dan Konsumsi Energy Spesifik di Unit Waru II, Sistem I ................................. 36

Tabel 25. Analisis Efisiensi Dan Konsumsi Energy Spesifik di Unit Waru II, Sistem II ................................ 37

Tabel 26. Analisis/ Penilaian Energy Motor Unit Waru II ........................................................................... 38

Tabel 27. Potensi Saving System I, Unit Waru II   ........................................................................................ 39

Tabel 28. Potensi Saving System II, Unit Waru II  ....................................................................................... 39

Tabel 29. Kelayakan Investasi Pompa Waru II  ............................................................................................ 40

Tabel 30. Ringkasan Evaluasi Efisiensi Pompa Tawangsari  .......................................................................... 43

Page 6: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 6/46

5

Tabel 31. Ringkasan Evaluasi Efisiensi Pompa Waru II ................................................................................ 44

Tabel 32. Tabel Rekomendasi Unit Tawangsari .......................................................................................... 44

Tabel 33.Tabel Rekomendasi Unit Waru II  ................................................................................................ 45

Page 7: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 7/46

6

DAFTAR ISTILAH

Nama Keterangan 

Ampere (A) Satuan Arus Listrik

Cos phi factor daya

Faktor daya atau Cos perbandingan antara pemakaian daya dalam Watt

dengan pemakaian daya dalam Volt- Ampere

Faktor Ketidak Seimbangan Tegangan perbandingan komponen tegangan urutan negative

terhadap komponen tegangan urutan positif

Hertz (HZ) Satuan frekuensi listrik

Jam nyala pemakaian kWH dalam satu bulan dibagi dengan kVA tersambung

Kilo VoIt Ampere (KVA) Seribu VoItAmpere adalah satuan daya

Kilo Volt (KV) Seribu Volt, adalah satuan tegangan listrik

Kilo Watt (KW) Satuan daya listrik nyata (aktif)

Kilo Watt Hour (KWh) Satuan energi listrik nyata (aktif)

LWBP Luar Waktu Beban puncak (Jam 22.00-18.00)

SEC Spesifik Energi Consumption adalah perbandingan

 jumlah masukan Energi kWh dan jumlah air yang

diproduksi dalam satu juta liter

Tagihan Listrik perhitungan biaya atas pemakaian daya dan energi

listrik oleh Pelanggan setiap bulan

Tarif Dasar Listrik (TDL) ketentuan Pemerintah yang berlaku mengenai

Golongan Tarif dan ha rga jual Tenaga Listrik yang

disediakan oleh PLN

VAR Daya Reaksi

Page 8: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 8/46

7

VoIt Ampere (VA) satuan daya (daya buta)

Volt (V) Satuan Tegangan Listrik

Waktu Beban puncak (WBP) waktu jam 18.00 sampai dengan jam 22.00 waktu

setempat

Watt Satuan Daya Listrik Nyata 

Page 9: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 9/46

8

RINGKASAN

Sumber air baku dan Instalasi Pengolahan Air (IPA) berasal dari sungai, afvoer, dan air

bawah tanah (ABT) di lokasi IPA, yaitu : IPA Sedati dari Afvoer Joblong, IPA Siwalanpanji dari

Afvoer Buduran, IPA Wonoayu dari ABT di Desa Wonoayu, IPA Tulangan dari ABT di DesaTulangan, IPA Porong dari Kanal Porong. Untuk IPA yang dikelola oleh mitra swasta, air baku

adalah : IPA PT. Taman Tirta Sidoarjo dari Sungai Pelayaran. IPA PT Hanarida Tirta Birawa dari

Sungai Pelayaran. Unit produksi yang ada pada system penyediaan air bersih PDAM sidoarjo

terdiri dari : Bangunan Penangkap Air (BPA), Bangunan rumah pompa dan peralatan pompa, Unit

Pengolahan IPA, Meter Induk. Produksi Air PDAM “Delta Tirta” Sidoarjo terdiri dari : IPA milik

sendiri yang berlokasi di Wonoayu, Siwalanpanji, Porong, Tulangan dan Sedati. Pembelian dari

mitra : PDAM Surabaya, PT Taman Tirta Sidoarjo (PT. TTS), PT Hanarida Tirta Birawa (PT.

HTB). Komponen unit Transmisi dan Distribusi pada system penyedia air bersih PDAM Sidoarjo

terdiri dari :Pipa Transmisi, Reservoir Distribusi, Perpipaan Distribusi, Meter Induk Distribusi.

Laporan ini adalah hasil pelatihan audit efisiensi energy di PDAM Sidoarjo yang

dilaksanakan oleh team dari PDAM Sidoarjo, ESP, MLD dan Akatirta. Pelatihan Audit efisiensi

energy di PDAM Sidoarjo ini mencakup pompa –  pompa yang terdapat di Tawangsari, dan Waru

II dengan tujuan utama untuk melakukan identifikasi kemungkinan dilakukan efisiensi energy dan

peningkatan skiil dan SDM PDAM agar kedepannya dapat melakukan efisiensi energy sendiri .

Sumber dari intake Tawangsari dialirkan menuju ke Taman Sidoarjo, dan Waru II

dengan menggunakan 9 pompa yang mempunyai debit 100 L/dt perpompa dengan tekanan 48m

dengan menggunakan daya 110 kW tiap pompa. Dan 2 pompa yang dialirkan menuju Krian.

Sumber dari Waru II berasal dari Unit Tawangsari. Perpompaan diunit Waru II ini

menggunakan 7 pompa yang mempunyai debit total 500 L/dt. Air yang berasal dari pompa Waru

II ini dialirkan menuju ke Bandara Juanda dan Pondok Chandra dengan menggunakan 4 buah

pompa yang beroperasi dan 3 dalam keadaan off.

Dari hasil pengolahan dan analisis data maka di dapat ringkasan evaluasi efisiensi energy

untuk pompa Tawangsari dan pompa Waru II sebagai berikut :

Page 10: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 10/46

9

Tabel 1. Hasil Ringkasan Kegiatan Efisiensi PDAM Sidoarjo

PompaName plate pompa lama Pengukuran

Effisiensipompa Selisih SEC

Daya (Kw) Q (lps) h (m) Daya (Kw) Q (lps) h (m) (%) sistem personal pump

Tawangsari

1 110 100 48 87.8 94.67 6.5 72

4%

16%

2 110 100 48 97.8 95.83 6.5 65 7%

3 110 100 48 86.8 84.5 6.4 64 7%

4 110 100 60 95.4 86.83 6.5 61 0.30%

5 110 100 60 97.1 83.33 6.5 57 5.60%

6 110 100 60 80 70.5 6.4 58 2.90%

7 110 100 48 88.7 83.67 6.5 63 4%

8 110 100 48 96.3 83.67 6.5 58

1%

4%

9 110 100 48 91.5 89 6.5 65 7%

Tabel 2. Hasil Ringkasan Kegiatan Efisiensi PDAM Sidoarjo

PompaName plate pompa lama Pengukuran

Effisiensipompa Selisih SEC

Daya (Kw) Q (lps) h (m) Daya (Kw) Q (lps) h (m) (%) sistem personal pump

 Waru II

1 110 100 104.1 73.33 5.5 41%

50%

23%

2 110 100 83.9 22.17 5.2 14% 71%

3 110 100 112.6 39.83 5.5 20% 61%

5 75 50 Stand by

4 60hp/45kw 50 Stand by

6 110 100 50.19 33.17 6.4 44% 27% 27%

7 110 100 Stand by

Page 11: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 11/46

10

Tabel 3. Potensi Penghematan di Tawangsari

Tabel 4. Potensi Penghematan di Waru II

 Wilayah PompaRekomendasi Rekomendasi Rekomendasi

biaya tinggi Investasi (Rp) savingsPaybackperiod

biayasedang

Investasi(Rp) savings

Paybackperiod biaya rendah

 Waru II

1

Penggantianpompa

900 juta 720 juta 1,2 th ganti impeller/renovasi

rumah pompa

Pemeliharaan rutin seperti :- Periksa jaringan perpipaan

dari kemungkinan kebocoranpipa

- Periksa dan bersihkanimpeller

- Periksa koneksi –  koneksiantar kabel pada panel controlmotor

- Memasang manometeryang dilengkapi keran pada

suction dan discharge pompa- Cek Billink

2

3

off

off

6Penggantianpompa 300 juta 39 juta 5,7 th

off

 Wilayah Pompa

Rekomendasi Rekomendasi

biayasedang

Investasi(Rp) savings

Paybackperiod biaya rendah

Tawangsari

1

ganti impeller/

renovasirumah pompa

Pemeliharaan rutin seperti :

- Periksa jaringan perpipaan dari kemungkinan kebocoran pipa- Periksa dan bersihkan impeller- Periksa koneksi –  koneksi antar kabel pada panel control

motor- Memasang manometer yang dilengkapi keran pada suction dan

discharge pompa- Cek Billink

2

3

45

6

7

8

9

Page 12: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 12/46

11

1. PENDAHULUAN

1.1 LATAR BELAKANG

Pembiayaan terbesar untuk operasional (25-40%) di beberapa PDAM se-Indonesia

terletak pada pembiayaan kelistrikan yang digunakan untuk system pompa. Bagian untuk

pembiayaan ini tidak dapat dihindarkan, karena untuk sebagian PDAM biaya ini akan menjadi

tinggi karena system operasi pompa yang tidak efektif, ukuran pompa yang tidak sesuai ataupun

sudah tua, pemeliharaan yang kurang baik, tidak adanya alokasi biaya untuk penggantian pompa

ataupun pemeliharaan secara berkala, dll.

Untuk mendukung PDAM dalam memecahkan permasalahan ETC Netherlands dan ESP

sebagai lembaga donor dan lembaga pelayanan lingkungan bekerjasama dengan Akademi Teknik

Tirta Wiyata Magelang dan PT MLD (Mitra Lingkungan Duta Consult) untuk melaksanakan

pelatihan teknis program Audit Efisiensi Energy dengan 3 PDAM di Jawa Timur : PDAM Sidoarjo,

PDAM Gresik, dan PDAM Kota Malang. Dalam kegiatan ini juga termasuk memberikan pelatihan

yang berkaitan dengan penyusunan dan pelaksanaan program kepada staff PDAM Gresik,

Sidoarjo dan Kota Malang.

1.2 TUJUAN

Sasaran dari program pelatihan teknik ini memberikan penilaian efisiensi energy kepada

masing-masing PDAM serta pelatihan kepada staf dan juga manager PDAM Sidoarjo, PDAM

Gresik, dan PDAM Kota Malang serta analisis pembiayaan yang menguntungkan, yang mana akan

ditunjukkan ke Management PDAM investasi yang dibutuhkan untuk EE ini agar dapat diterima.

Pelatihan teknis dan audit efisiensi energy ini diarahkan untuk meningkatkan skill dan

pengetahuan dari sumber daya manusia di PDAM sehingga pada akhirnya PDAM mampu

melakukan program Efisiensi Energi ini sendiri.

Page 13: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 13/46

12

1.3 RUANG LINGKUP KEGIATAN

Ruang lingkup kegiatan dari program pelatihan teknik dan audit efisiensi energy ini adalah

penilaian pada system jaringan pompa di PDAM (bangunan pengolahan air serta jaringan

distribusi), tetapi focus pada efisiensi energy, pelatihan teknis staff PDAM dengan topik pelatihandasar yang berhubungan dengan system pompa seperti ilmu hidrolika, pemilihan pompa dan

motor yang mempunyai efisiensi tinggi, penentuan perbaikan secara teknik, dan analisis keuangan

(cost-benefit).

Audit efisiensi energy di PDAM Sidoarjo ini mencakup pengumpulan data sekunder serta

melakukan beberapa jenis pengukuran dan analisa untuk mengevaluasi pemakaian energy dan

identifikasi kegiatan/ program yang diperlukan untuk peningkatan efisiensi energy termasuk

membuat perkiraan biaya investasi yang dibutuhkan serta manfaat dan jangka waktu pengembalian

biaya investasi. Objek studi pada program ini hanya pada pompa  –   pompa yang mempunyai

potensi cukup besar untuk dilakukan investasi.

Secara garis besar, parameter –  parameter yang dikumpulkan / diukur dalam audit energy

ini mencakup :

  Parameter yang berhubungan dengan kinerja pompa, seperti tekanan, debit aliran

  Parameter yang berhubungan dengan motor listrik, seperti data KW, KVA, Voltase,

Ampere, Pf dan KVAR

  Data penunjang lainnya seperti produksi air, rekening listrik, dan lainnya.

1.4 METODOLOGI

Proses pelaksanaan kegiatan ini dilakukan dengan urutan sebagai berikut :

 Pengenalan EE dan Pelatihan Awal ke AKATIRTA

 Koordinasi dan kunjungan di 3 PDAM

 Training Teori ME & IK

 Pengumpulan Data Sekunder

 Pengukuran / Pengumpulan Data Lapangan

 Olah Data dan Diskusi hasil kegiatan dengan PDAM

 Membuat Draft Laporan dan analisis (ke ESP, MLD & PDAM)

Page 14: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 14/46

13

Dari hasil olah data dan diskusi dengan PDAM, draft laporan dikirim ke PDAM, ESP dan

MLD untuk dipelajari.

 Diskusi internal PDAM tentang draft laporan

Diskusi dengan tim dari masing  –   masing PDAM untuk membahas draft laporan dan

analisis hasil pengukuran

 Revisi draft laporan

Dari hasil diskusi dengan team dari masing  –   masing PDAM ini apabila masih ada

kekurangan, Akatirta membuat revisi dari draft laporan

 Eksternal Workshop (workshop gabungan)

Workshop dengan ketiga PDAM yaitu PDAM Gresik, PDAM Sidoarjo dan PDAM Malang

pada satu tempat.

 Final Report

1.5 GAMBARAN UMUM PDAM SIDOARJO 

Pelayanan air bersih di Wilayah Kabupaten Sidoarjo sudah mulai sejak Jaman Hindia

Belanda oleh Waterleiding Bedrijven. Pada masa kemerdekaan kepengurusannya dilimpahkan

kepada Dinas Pekerjaan Umum Propinsi Jawa Timur.

Dengan adanya Perda. Propinsi Dati I : No 4. Pada masa kemerdekaan kepengurusannyadilimpahkan kepada Dinas Pekerjaan Umum Propinsi Jawa Timur.

Dengan adanya Perda. Propinsi Dati I : No 4/1976, tanggal 10 Juli 1976, Pemerintah

Kabupaten Sidoarjo menerima penyerahan sebanyak 1.904 unit pelanggan yang meliputi wilayah :

Larangan, Candi, Candi Selatan, Porong, Gedangan, Waru, Buduran Selatan, Buduran Utara,

Tanggulangin, Sepanjang, Kedurus, Driyorejo, Krian, Prambon dan Watu Tulis.

Pada tanggal 5 Juli 1978 terbit Peraturan Daerah kabupaten Dati II Sidoarjo No. 5/1978

tentang Pembentukan Perusahaan Daerah Air Minum (PDAM) dan disyahkan oleh Gubernur

KDH. Tingkat I jawa Timur, dengan Nomor : HK/498/1978

Page 15: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 15/46

14

Cakupan, Wilayah Pelayanan dan Jumlah Pelanggan

Secara administrasi PDAM “Delta Tirta” Sidoarjo terdiri dari : 

  1 Kantor Pusat, terletak di Kota Sidoarjo

  7 Kantor Cabang, yaitu :

a.  Cabang Krian, dengan wilayah Kec. Krian, Kec Prambon

b.  Cabang Sepanjang, dengan Wilayah Kec Sepanjang, sebagian Kec Sukodono

c.  Cabang Sidoarjo, dengna Wilayah Kec. Kota Sidoarjo, Kec Candi

d.  Cabng Waru 1, dengan Wilayah sebagian Kec Waru, Kec. Sedati.

e.  Cabang Waru 2, dengan wilayah sebagian Kec Waru.

f.  Cabang Gedangan, Wilayah sebagian Kec. Waru

g.  Cabang Porong, Wilayah Kec. Porong, Tanggulangin dan Tulangan

Cakupan Pelayanan :

Cakupan pelayanan PDAM “Delta Tirta” Sidoarjo sampai Tahun 2006 adalah 29.89%,

masih jauh dari target nasional yaitu 80% untuk perkotaan dan 60% untuk perdesaan, hal ini

disebabkan :

  Pertumbuhan penduduk Kabupaten Sidoarjo cukup tinggi.

  Air baku untuk air minum sulit didapatkan.

  Sebagian IPA sudah termakan usia dan konvensional.

   Jaringan perpipaan sangat terbatas

Air Baku dan Instalasi Pengolahan Air (IPA) berasal dari sungai, afvoer, dan Air Bawah

Tanah (ABT) di lokasi IPA, yaitu :

1.  IPA Sedati dari Afvoer Joblong

2.  IPA Siwalanpanji dari Afvoer Buduran

3.  IPA Wonoayu dari ABT di Desa Wonoayu

4.  IPA Tulangan dari ABT di Desa Tulangan

5.  IPA Porong dari Kanal Porong.

Untuk IPA yang dikelola oleh mitra swasta, air baku adalah :

1.  IPA PT. Taman Tirta Sidoarjo dari Sungai Pelayaran.

2.  IPA PT. Hanarida Tirta Birawa dari Sungai Pelayaran.

Page 16: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 16/46

15

Instalasi Pengolahan Air (IPA) yang dimiliki PDAM Sidoarjo ada 7 unit milik PDAM Delta

Tirta :

1.  IPA Sedati terletak di Desa Pepe Sedati.

2.  IPA Siwalanpanji terletak di Desa Siwalanpanji, Buduran.

3.  IPA Wonoayu yang terletak di Desa Wonoayu.

4.  IPA Tulangan terletak di Desa Tulangan

5.  IPA Porong yang terletak di Porong

Dan 2 unity di kelola oleh swasta :

1.  IPA PT. Taman Tirta Sidoarjo di Desa Tawangsari, Sepanjang.

2.  IPA PT. Hanarida Tirta Birawa di Desa Tawangsari, Sepanjang.

Unit Produksi

Unit produksi yang ada pada system penyediaan air bersih PDAM Kabupaten

Sidoarjo terdiri dari :

a.  Bangunan Penangkap Air (BPA)

b.  Bangunan rumah pompa dan peralatan pompa

c.  Unit Pengolahan IPA

d.  Meter Induk

Produksi Air :

Unit produksi air PDAM “Delta Tirta” Sidoarjo terdiri dari :

  IPA milik sendiri yang berlokasi di : Wonoayu, Siwalanpanji, Porong, Tulangan dan

Sedati.

  Pembelian dari mitra :

-  PDAM Surabaya

-  PT. Taman Tirta Sidoarjo (PT. TTS)

-  PT. Hanarida Tirta Birawa (PT. HTB)

Page 17: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 17/46

16

Tabel 5. Produksi air PDAM Delta Tirta Sidoarjo

Unit Transmisi dan Distribusi.

Komponen unit transmisi dan distribusi pada system penyedia air bersih PDAM

Kabupaten Sidoarjo terdiri dari :

1.  Pipa transmisi

2.  Reservoir distribusi

3.  Perpipaan distribusi

4.  Meter induk distribusi

Sistem transmisi di PDAM kabupaten Sidoarjo pada umumnya menggunakan pipa GI

karena sumber air berasal dari sungai dengan cara pemompaan. Sedangkan untuk pipa distribusi

pada umumnya menggunakan pipa PVC kecuali pada inlet dan outlet pompa distribusi serta

 jembatan pipa.

Sistem Distribusi

Sistem distribusi kabupaten Sidoarjo dari komponen –  komponen sebagai berikut :

a.  Reservoir distribusi

b.  Perpipaan distribusi

c.  Meter induk ditribusi Pompa distribusi

Kondisi topografi wilayah sidoarjo relative datar oleh karena itu secara keseluruhan

dalam system pengaliran air bersih di PDAM Kabupaten Sidoarjo dilakukan dengan cara system

pemompaan kecuali pada unitv Sidoarjo dengan system gravitasi karena memanfaatkan reservoir.

No Produksi IPA Sistem Terpasang Operasi %

1 PDAM Surabaya 170 169.17 99.51

2 IPA Wonoayu Lengkap 75 6.92 9.23

3

IPA

Siwalanpanji Lengkap 65 55.81 85.86

4 IPA Porong Lengkap 35 14.35 41.01

5 IPA Tulangan

Tidak

Lengkap 10 10.08 100.78

6 IPA Sedati Lengkap 60 20.28 33.8

7 IPA PT. HTB Lengkap 450 470.65 104.59

8 IPA PT.TTS Lengkap 200 205.98 102.99

1065 961.2 90.25

Page 18: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 18/46

17

2. PENGUMPULAN DAN PENGOLAHAN

DATA SEKUNDER

Pengumpulan data sekunder di PDAM Sidoarjo mulai dilaksanakan pada tanggal 10 s.d 11 Juni 2009. Beberapa data sekunder yang dibutuhkan untuk mendukung kegiatan ini adalah semua

data tentang pompa (jumlah, data name plate, kurva pompa, riwayat perbaikan, dsb), data

rekening listrik, layout, dll. Beberapa data tersebut setelah diolah didapat hasil sebagai berikut :

2.1 SPESIFIKASI POMPA DAN MOTOR

Data spesifikasi pompa dan motor di ambil berdasarkan data name plate yang tertera

pada bagian pompa dan motor yang kemudian di cocokkan dengan kartu inventarisir

perpompaan dan panel di tiap unit perpompaan. Semua data tentang pompa dan motor di tiap

unit perpompaan dapat dilihat pada tabel di bawah ini :

Tabel 6. Data Name Plate Motor & Pompa Tawangsari

Pompa

Name plate

Motor Pompa

Merk Daya(kW) rpm Voltage/Phase Amp

Th

pemasangan Merk

Capacity

(L/dt)

Head

(m)

P1 TECO 110 1480

380-415/660-

690 195 2006 Grundfos 100 48

P 2 TECO 110 1480

380-

415/660-

690 195 2006 Grundfos 100 48

P3 TECO 110 1480

380-

415/660-

690 195 2006 Grundfos 100 48

P4 TECO 110 1450-1480 380-415 205 2000 Grundfos 100 60

P5 TECO 110 1450-1480 380-415 205 2000 Grundfos 100 60

P6 TECO 110 1450-1480 380-415 205 2000 Grundfos 100 60

P7 TECO 110 1780-1786 380-480 195 Grundfos 100 48

P8 TECO 110 1780-1786 380-480 195 Grundfos 100 48

P9 TECO 110 1780-1786 380-480 195 Grundfos 100 48

Page 19: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 19/46

18

Tabel 7. Data Nameplate Motor dan Pompa unit Waru II

Pump

Name plate

Motor Pompa

MerkDaya(kW) rpm

Voltage/Phase Amp Hz Thpemasangan Merk

Capacity(L/dt)

Head(m)

P1 MEZFRENSTAT 110 1450 380/440 205 50/60 ITT 100

P 2 MEZFRENSTAT 110 1450 380/440 205 50 ITT 100

P3 MEZFRENSTAT 110 1450 380/440 205 50/60 ITT 100

P4 ELEKTRIM60 HP/45 kw 1480 380 83 1993 KSB 50

P5 VDE 75 1480 380/660 141 50/60 GAE 50

P6 TECO 110 1450 380 205 50 GRUNDFOS 100

P7 TECO 110 GRUNDFOS 100

Data di atas adalah data pompa yang pada saat pengukuran sedang di operasikan

(sedangkan data pompa yang tidak dioperasikan (off) yaitu pompa 4, 5 & 7 tidak dicatat.

2.2 KONSUMSI DAN BIAYA ENERGI

Berikut ini adalah tabel konsumsi dan biaya listrik pada bulan Januari sampai dengan

Desember 2008 pada unit perpompaan unit Tawangsari :

Page 20: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 20/46

19

I. Tawangsari

Tabel 8.Konsumsi Dan Biaya Listrik Unit Tawangsari

Gambar 1. Grafik Konsumsi Energy Bulanan Unit Tawangsari

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;  ;   0   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;   J   a   n   u   a   r   i  ;

   7   3   4 .   8

   2   0

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;

   F   e    b   r   u   a   r   i  ;   7   1   2 .   1

   0   0

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;   M   a   r   e   t  ;

   6   8   5 .   4

   2   0

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;   A   p   r   i    l  ;

   7   4   0 .   6

   6   0

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;   M   e   i  ;

   5   7   7 .   6

   8   1

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;   J   u   n   i  ;

   5   8   7 .   6

   8   1

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;   J   u    l   i  ;

   5   3   7 .   0

   1   1

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;

   A   g   u   s   t   u   s  ;   5   7   5 .   4

   0   0

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;

   S   e   p   t   e   m    b   e   r  ;   5   9   3 .   3

   7   4

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;

   O    k   t   o    b   e   r  ;   5   2   9 .   5

   8   8

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;

   N   o   v   e   m    b   e   r  ;   5   6   3 .   9

   8   2

   T   o   t   a    l    k   W    h

    (   T   a   w   a   n   g   s   a   r   i    )  ;

   e   s   e

    b   e   r  ;   5   4   5 .   1

   7   9

Chart Title

Januari

Februari

Maret

April

Mei

Juni

Juli

Agustus

 

Bulan (2008)

Tawangsari

Kwh Rp

Januari 734.820 484,687,330

Februari 712.100 472,148,595

Maret 685.420 455,168,855

April 740.660 489,544,510

Mei 577.681 469,066,475

Juni 587.681 475,879,195

Juli 537.011 438,130,645

Agustus 575.400 466,554,705

September 593.374 480,447,975

Oktober 529.588 431,435,730

November 563.982 459,214,815

Desember 545.179 443,014,145

Page 21: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 21/46

20

2.Waru II

Berdasar data yang sudah diperoleh, berikut ini tabel konsumsi dan biaya energy listrik

untuk perpompaan Waru II pada bulan Januari sampai dengan Juni 2009 :

Tabel 9. Konsumsi Dan Biaya Energy Listrik Untuk Pompa Waru II

Bulan (2009) Total kWh Rp

Januari 270.184 159.824.325

Maret 231.712 163.052.815

April 270.856 154.328.430

Mei 260.600 149.427.820

Juni 286.816 162.666.265

Gambar 2. Grafik Konsumsi Energy Bulanan Unit Waru II

   T   o   t   a    l    k   W    h    (   W   a   r   u    )  ;  ;   0

   T   o   t   a    l    k   W    h    (   W   a   r   u    )  ;

   J   a   n   u   a   r   i  ;

   2   7   0 .   1

   8   4

   T   o   t   a    l    k   W    h    (   W   a   r   u    )  ;

   M   a   r   e   t  ;   2   3   1 .   7

   1   2

   T   o   t   a    l    k   W    h    (   W   a

   r   u    )  ;   A   p   r   i    l  ;

   2   7   0 .   8   5

   6

   T   o   t   a    l    k   W    h    (   W   a   r   u    )  ;   M   e   i  ;

   2   6   0 .   6   0   0

   T   o   t   a    l    k   W    h    (   W   a   r   u    )  ;   J   u   n   i  ;

   2   8   6 .   8

   1   6

Total kWh (Waru II)

Januari

Maret

April

Mei

Juni

Page 22: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 22/46

21

2.3 PRODUKSI AIR

Berikut ini adalah data produksi air perpompaan unit Tawangsari dan Waru II :

Tabel 10. Produksi Air Tawangsari

Bulan (2008) Produksi air/m3 

Januari 2.451.548

Februari 2.285.207

Maret 2.437.850

April 2.420.613

Mei 2.452.526

Juni 2.404.975

Juli 2.383.188

Agustus 2.443.043

September 2.298.289

Oktober 2.387.066November 2.312.980

Desember 2.385.992

Tabel 11. Produksi Air Waru II

Bulan (2009)Waru II

Produksi air/m3

Januari 74.502

Maret 70.502

April 80.016

Mei 73.106

Juni 85.224

Page 23: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 23/46

22

3.PENGUKURAN LAPANGAN (DATA PRIMER)

Pengukuran lapangan di PDAM Sidoarjo dilaksanakan pada tanggal 10 sampai dengan

11Juni 2009 dengan 2 lokasi pengukuran yaitu unit Tawangsari dan unit Waru. Pengukuran

meliputi pengukuran pompa yaitu flow rate (debit), dan head pompa, pengukuran motor listrikyaitu pada panel control motor dan pengukuran putaran pompa. Pengukuran pompa bertujuan

untuk mengetahui effisiensi operasi pompa, sedangkan pengukuran motor listrik bertujuan untuk

mengetahui kinerja motor. Peralatan utama yang digunakan dalam pengukuran ini adalah sebagai

berikut :

1.  Ultrasonic Flow Meter (UFM)

Tujuan utama dari penggunaan UFM ini adalah untuk mengetahui debit/ kapasitas aktual

pada pompa. Selain itu, output dari UFM ini adalah kecepatan air dan integral. System kerja dari

alat ini adalah menggunakan bantuan kerja sensor dimana sensor pada UFM dipasang/

ditempelkan secara khusus pada pipa outlet pompa yang akan di ukur. Pengukuran ini hanya

dilakukan sesaat / sekali sehingga data hasil pengukuran dan pergitungan hanya merefleksikan

kondisi pompa saat pengukuran saja. Namun demikian dalam studi ini diasumsikan bahwa kondisi

pompa stabil.

2.  Manometer

Digunakan untuk mengukur tekanan air (head) pada pompa. Manometer di pasang pada

sisi suction dan discharge (outlet) dari pompa.

3.  Power meter/ power Analyzer

Power meter/ power Analyzer digunakan untuk mengetahui kinerja motor yang

dilakukan secara sesaat pada panel motor. Data / parameter listrik yang diperoleh dari alat ini

adalah Kw, KVA, KVAR, arus, tegangan, cos phi, frekwensi, Uunbalance, dsb. Pengukuran

dilakukan pada motor yang sedang beroperasi saja. Merk yang digunakan pada pengukuran ini

adalah Hioki tipe 3197.

4.  Stroboscope

Untuk mengetahui putaran motor pompa maka digunakan alat stroboscope.

Stroboscope yang digunakan dalam pengukuran ini adalah Digital Stroboscope model : DT  –  

2239A, dengan tingkat akurasi 0,05 % + 1 digit 

5.  Kamera

Digunakan untuk merekam semua kegiatan pengukuran termasuk data  –  data lapangan

yang membutuhkan dokumentasi.

Page 24: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 24/46

23

Berikut ini adalah kegiatan pengukuran dan hasilnya pada :

3.1 PERPOMPAAN TAWANGSARI

Sumber dari intake Tawangsari dialirkan menuju ke Taman Sidoarjo, dan Waru II.

Dengan menggunakan 9 pompa yang mempunyai debit 100 L/dt perpompa, dengan tekanan

48m serta menggunakan daya 110 kW tiap pompa.

 G am

 b  ar 

 J  ar i  n

 g anP 

 om

 p aB 

 o s  t   er T 

 aw

 an

 g s  ar i  

N

K  a b  a gT r  an

 d i   s 

 t  

K  a s  u b  a g

P  er  aw

 a t   an

 J  ar 

i  n g an

Di  

 G am

 b  ar 

 Ol   eh 

 S  UT A D

 J I   ,

 S .

 S  o s 

 S  UHA R

T  ON

 O

I  MA N

N U GR

 OH

 O

RESERVOIR RESERVOIR

.

D : 350 mm

P : 9 .100 L/dt

.

P : 8 .100 L/dtPomp 1.100 L/dt Pomp 2.100 L/dt

Pomp 3.100 L/dt

D : 350 mm

D : 400 mm D : 500 mm

PompKrian50 L/dtPompKrian50 L/dt Pomp 7.100 L/dt

D : 500 mm

D : 500 mm

WM

Waru

D : 500 mm

Pomp 4.100 L/dt Pomp 5.100 L/dt Pomp 6. L/dt

D : 500 mm

Break Tank

D : 200 mm

WM

Waru

Krian

WM

Sidoarjo

P i   p

 a d i   a

 5  0  0 mm

: : : : P i   p

 a d i   a

4  0  0 mm

P i   p

 a d i   a

 3  5  0 mm

P i   p

 a d i   a

2  0  0 mm

 

Gambar 3. Skematik Jaringan pompa boster Tawangsari

Pelaksanaan pengukuran

Waktu : tanggal 10 Juni 2009

Pelaksana : staff PDAM Sidoarjo, MLD, ESP, dan AKATIRTA

Metodologi : pengukuran pada panel listrik, putaran motor pompa, tekanan dan

kapasitas air yang dialirkan oleh pompa (Q pompa).

Page 25: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 25/46

24

Tabel 12. Data Hasil Pengukuran Lapangan Di Unit Tawangsari

Pump

Actual data

Frekw. kW Amp Volt

Cos

phi KVA KVAR Uunb rpm Q v P

Diameter

(mm)

m3/min l/dt m/s inlet outle

1 49.97 87.8 152.7 376,7 0.77 99.6 47.8 0.3 1481 5.68 94.67 2,81 6.5 250 200

2 50.17 97.8 169.4 378,2 0.878 110.9 53 0.3 1480 5.75 95.83 2,05 6.5 273 200

3 49.91 86.8 151.5 380,4 0.869 99.8 49.5 0.4 1482 5.07 84.5 2,50 6.4 250 200

4 50.03 95.4 158.6 391,6 0.889 107.5 49.3 0.4 1484 5.21 86.83 2,57 6.5 250 200

5 50.13 97.1 162 387,1 0.893 108.6 48.9 0.5 1482 5 83.33 2,47 6.5 250 200

6 49.86 80 138.3 377,7 0.885 90.5 42.2 0.5 1488 4.23 70.5 2,08 6.4 250 200

7 50.36 88.7 152.5 387,1 0.87 102.3 50.5 0.1 1488 5.02 83.67 2,47 6.5 200 200

8 50.17 96.3 162.9 392,0 0.872 110.6 54.2 0.4 1482 5.02 83.67 2,47 6.5 200 250

9 50.04 91.5 157 384,2 0.872 104.4 51.2 0.2 1490 5.34 89 2,63 6.5 200 250

Tabel 13. Data Hasil Pengukuran Motor Listrik Tiap Phasa Pompa Tawangasari

Pompa I V

Dayainput

motor

 WTP1 R S T ave R S T ave kW

Pump 1 152 152.8 153.4 152.73 375.9 376.5 377.7 376.70 87.4

pump 2 168.8 169.5 169.8 169.37 377.5 378 379.1 378.20 97.4

Pump 3 150.9 151.4 152.1 151.47 379.7 380.3 381.3 380.43 86.7

Pump 4 155.5 161.7 158.5 158.57 392.7 392.4 389.7 391.60 95.6

Pump 5 159 165.2 161.6 161.93 388.3 387.8 385.2 387.10 97

Pump 6 135.4 141.5 138 138.30 378.9 378.5 375.8 377.73 138

Pump 7 149.7 155.8 152.1 152.53 388.2 387.9 385.4 387.17 88.9

Pump 8 165.8 162.4 160.6 162.93 392.3 391.4 392.4 392.03 96.5

Pump 9 159.5 156.9 154.4 156.93 384.5 383.6 384.5 384.20 91

Page 26: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 26/46

25

3.2 PERPOMPAAN UNIT WARU II

Sumber dari Waru II berasal dari Unit Tawangsari. Perpompaan diunit Waru II ini

menggunakan 7 pompa yang mempunyai debit total 500 L/dt. Air yang berasal dari pompa Waru

II ini dialirkan menuju ke Bandara Juanda dan Pondok Chandra dengan menggunakan 4 buah

pompa yang beroperasi dan 3 dalam keadaan off.

WARU I

Pipa dia Ø 300 mmPipa dia Ø 500 mm

Pomp 1.100 L/dt Pomp 2.100 L/dt Pomp 3.100 L/dt

Pomp 4.50 L/dt

Pomp 7.50 L/dt

Pomp 5.100 L/dt

Pomp 6.100 L/dt

Pipa dia Ø 600 mm

 Ø 200 mm  Ø 200 mm Ø 200 mm

Pipa dia Ø 250 mm

 Ø 200 mm Ø 200 mm

 Ø 200 mmØ 250 mmØ 200 mmØ 250 mmØ 250 mm  Ø 200 mm

JUANDA

Plt Kabag Trandist Kasubag PerawatanJaringan

Di Gambar Oleh

SU SETYO BUDI SUHARTONO IMAN NUGROHO

Gambar Jaringan Pompa Boster Makarya, Waru II

PDAM “DELTA TIRTA” SIDOARJO

 Jl. Pahlawan No. 1 Tlp. 031 8942886

SIDOARJO

Gambar Jaringan Pompa Boster Makarya, Waru II

Tgl. 20 - Agustus - 2009

::::

Pipa dia Ø 300 mm

Pipa dia Ø 600 mm

Pipa dia Ø 500 mm

Pipa dia Ø 200 mm

:::

Valve Posisi Terbuka

Valve Posisi Tertutup

Pompa Centrifugal

: Pipa dia Ø 250 mm

: Check Valve

IN

WM

 

Gambar 4. Skematik Jaringan Pompa Waru II

Gambar 5 Pengukuran Debit

Pompa Di Unit Waru II

Page 27: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 27/46

26

Pelaksanaan pengukuran

Waktu : tanggal 11Juni 2009

Pelaksana : staff PDAM Sidoarjo, MLD, ESP, dan AKATIRTA

Metodologi : pengukuran pada panel listrik, putaran motor pompa, tekanan dan

kapasitas air yang dialirkan oleh pompa (Q pompa)

Tabel 14.Data Hasil Pengukuran Lapangan Di Unit Waru II

Tabel 15. Data Hasil Pengukuran Motor Listrik Tiap Phasa Pompa Waru II

Pompa I V

Dayainput

motor

 WTP1 R S T ave R S T ave kW

Pump 1 179.3 180 172.1 177.13 382.7 382.3 382.8 382.60 103.7

pump 2 166.4 128.3 124.9 139.87 395.2 397.1 398.1 396.80 84.1

Pump 3 196.3 193.4 184.7 191.47 383.1 383 383 383.03 112.8

Pump 4 off

Pump 5 182.1 181.8 178.1 180.67 386.2 386.1 386.5 386.27 107.8

Pump 6 128.3 127.8 125.1 127.07 387.7 387.5 387.9 387.70

Pompa

Actual data

Frekw. kW Amp Volt

Cos

phi KVA KVAR Uunb rpm Kapasitas Kecepatan Tekanan Diameter

l/dt inlet outlet

P1 50.06 104.1 177.1 382.6 0.884 117.4 54.9 0,1 1485 73.33 1,33 5.5 200 250

P2 50.26 83.9 139.9 396.8 -875 139.9 -466 0,6 _ 22.17 5.2 200 250

P3 50.04 112.6 191.5 383.2 0.888 127.1 58.5 0,1 1486 39.83 2,39 5.5 250 200

P4 0.00

P5 50.25 50.25 180.7 386.3 0.891 120.9 54.8 0,3 0.00 1,94

P6 50.19 50.19 127.1 387.7 0.876 85.3 41.2 0,2 1497 33.17 1,99 6.4 200 200

Page 28: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 28/46

27

4. ANALISIS DAN PEMBAHASAN DATA

4.1 UMUM

I.  Analisis Teknis

a.  Analisis Effisiensi Pompa dan Analisis Konsumsi Energy Specific

Konsumsi energy specific air didefinisikan sebagai jumlah energy listrik yang diperlukan

untuk memperoleh sejuta liter air. Tujuan dari perhitungan efisiensi dan konsumsi energy spesifik

pompa adalah untuk mengetahui efisiensi dan konsumsi energy spesifik dari data yang diperoleh

berdasarkan pengukuran actual dibandingkan dengan perhitungan berdasarkan data spesifikasi

pompa yang tertera pada name plate pompa dari masing  –   masing pompa. Konsumsi energy

specific ini bisa dihitung berdasarkan tagihan listrik atau berdasarkan pengukuran langsung daya

yang masuk per pompa di lapangan. Hasil perhitungan dalam bentuk efisiensi dan tingkat

konsumsi spesifik dari tiap pompa akan memperlihatkan kelayakan dari pompa tersebut atau

perlu rangkaian perbaikan guna meningkatkan performansinya atau jika perlu dengan penggantian

pompa.

Menurut pengalaman di beberapa Negara Eropa, jika di dapat efisiensi pompa kurang dari

50% maka dianjurkan untuk penggantian pompa, jika efisiensi pompa antara 51 sampai dengan 59

%, dianjurkan untuk renovasi pompa (misal housing, propeler, dsb), sedangkan jika efisiensi

pompa lebih dari 60 %, maka pompa masih tergolong bagus.

b.  Analisis Effisiensi Motor

Tegangan tidak stabil pada motor (Vunbalance) akan menurunkan kinerja dan

memperpendek usia motor 3 phase dari waktu teknis sesuai desain. Ketidakstabilan tegangan

pada terminal stator motor menyebabkan phase ketidakstabilan arus (I unbalance) jauh dari

proporsi ke tegangan unbalance.

Ketidakstabilan arus mengakibatkan ketidakstabilan torsi, meningkatkan terjadinya

getaran dan stress mesin, meningkatkan losses dan motor menjadi overheating, yang pada akhirnya

akan menyebabkan usia insulasi gulungan menjadi pendek. Ketidakstabilan tegangan menyebabkan

terjadinya ketidakstabilan arus yang tinggi bahkan ekstrem. Besarnya ketidakstabilan arus berkisar

antara 6 hingga 10 kali lebih besar dari ketidakstabilan tegangan. Sebagai contoh untuk motor

100 hp, aliran arus pada beban penuh dengan 2.5 % ketidakstabilan tegangan akan mengakibatkan

ketidakstabilan arus sekitar 27.7 %.

Page 29: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 29/46

28

Sebuah motor akan lebih panas ketika beroperasi pada suplai daya dengan tegangan yang

tidak stabil. Pertambahan suhu diperkirakan dengan persamaan sebagai berikut :

% pertambahan kenaikan suhu = 2 x (% ketidakstabilan tegangan)

Penyebab terjadinya ketidakstabilan tegangan antara lain :

-  Kesalahan pengoperasian akibat dari koreksi factor daya peralatan

-  Ketidakstabilan supply listrik dari PLN 

-  Ketidakstabilan trafo bank dalam menyuplai ke beban 3 phasa sehingga terlalu besar untuk

bank  

-  Tidak terdistribusi beban –  beban phasa 1 dalam system daya (power) yang sama 

-  Tidak teridentifikasi kesalahan phasa1 terhadap ground 

-  Terjadi sirkuit terbuka pada system distribusi primer. 

Ketidakstabilan tegangan nantinya akan menimbulkan persoalan pada kualitas daya dan

akan menyebabkan motor overheating dan motor menjadi cepat rusak. Jika tegangan  –  tegangan

tidak stabil terdeteksi sedini mungkin, maka perlu dilakukan pengecekan menyeluruh untuk

menentukan penyebabnya.

Berdasarkan standar NEMA, kinerja motor listrik dapat dikatakan baik jika deviasi

tegangan kurang dari 10 %, ketidakseimbangan fasa tegangan kurang dari 1%, ketidakseimbangan

arus kurang dari 10 % (juga standart US DOE) dan factor daya lebih dari 85 %.

II.  Analisis Keuangan

a.  Biaya dan Manfaat (Analisis potensi saving/ penghematan)

Saving/ penghematan adalah dari pemasangan kapasitor bank. Peluang penghematan

energy dalam bentuk mengurangi atau menghilangkan denda KVAR yang disebabkan oleh

rendahnya nilai factor daya yang diperlihatkan tiap individual motor. Scenario penghematan

energy pada sisi motor listrik ini dilakukan dengan melakukan pemasangan kapasitor bank pada

beberapa motor untuk menaikkan factor daya (cos phi) diatas 85% seperti disyaratkan oleh PLN.

Keuntungan yang diperoleh dengan dipasangnya kapasitor bank :

  Menghilangkan denda PLN atas kelebihan pemakaian daya reaktif.  Menurunkan pemakaian kVA total karena pemakaian kVA lebih mendekati kW yang

terpakai, akibatnya pemakaian energi listrik lebih hemat.

Page 30: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 30/46

29

  Optimasi Jaringan:

- Memberikan tambahan daya yang tersedia pada trafo sehingga trafo tidak kelebihan

beban (overload).

- Mengurangi penurunan tegangan (voltage drop) pada line ends dan meningkatkan daya

pakai alat-alat produksi.

- Terhindar dari kenaikan arus/suhu pada kabel sehingga mengurangi rugi-rugi.

Peluang penghematan energy lainnya adalah penggantian pompa dengan pompa baru yang

sesuai dengan instalasi jaringan yang terpasang.

b.  Analisis investasi

Analisis kelayakan investasi akan dilakukan dengan menggunakan metode penilaian

investasi : Payback Period (PP), Net Present Value (NPV), dan Internal Rate of Return (IRR).

4.2 ANALISIS DAN PEMBAHASAN DATA

a.  Perpompaan Tawangsari

  SEC :

  SEC global :

Tabel 16. Konsumsi Energi Spesifik (SEC) Perpompaan Unit Tawangsari :

Bulan (2008)Produksi air/m3 

Total kWhSEC 2008

kWh/juta literJanuari 2,451,548 734,820 300

Februari 2,285,207 712,100 312

Maret 2,437,850 685,420 281

April 2,420,613 740,660 306

Mei 2,452,526 577,681 236

Juni 2,404,975 587,681 244

Juli 2,383,188 537,011 225

Agustus 2,443,043 575,400 236

September 2,298,289 593,374 258

Oktober 2,387,066 529,588 222

November 2,312,980 563,982 244Desember 2,385,992 545,179 228

Page 31: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 31/46

30

  SEC system :

System I :

Pompa 1 sampai dengan 7 unit Tawangsari ini adalah pompa parallel menuju Waru

II, sehingga SEC untuk system ini adalah sebagai berikut :

Tabel 17.Konsumsi Energi Spesifik (SEC) Perpompaan Tawangsari

T

a

b

e

l

 

Terdapat hanya selisih 4% antara SEC rated dengan SEC actual dimana SEC actual lebih

rendah. Hal ini berarti system perpompaan pada unit ini masih bagus.

System II :

Tabel 18.Konsumsi Energi Spesifik (SEC) System II, Tawangsari

Parameter

Pompa

8 9 Total

Rated :

kw 110 110 220

m3/h 360 360 720

SEC 306

Actual :

kw 96,3 91,5 187,8

m3/h 301 320 622

SEC 302

Dari tabel di atas terlihat bahwa pompa parallel antara pompa 8 dan pompa 9 Tawangsari

ini masih bagus, selisih SEC hanya 1 % (SEC actual lebih rendah).

Parameter

Pompa

1 2 3 4 5 6 7 Total

Rated :

kw 110 110 110 110 110 110 110 770

m3/h 360 360 360 360 360 360 360 2520

SEC 306

Actual :

kw 87,8 97,8 86,8 95,4 97,1 80 88,7 633,6

m3/h 341 345 304 311 300 254 301 2156

SEC 294

Page 32: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 32/46

31

Efisiensi Pompa :

Tabel di bawah ini memperlihatkan hasil perhitungan analisis Efisiensi dan Konsumsi

Energy Spesifik di unit Tawangsari :

Tabel 19. Analisis Efisiensi Dan Konsumsi Energy Spesifik, Unit Tawangsari

Keterangan

Pompa Tawangsari

1 2 3

Rated Parameter unit

Merk

Grundfos/0604/

1732505040

Grundfos/0604/

1732505040

Grundfos/0604

/1732505040

Model Centrifugal /Hs

200 x 150 x480

Centrifugal /Hs

200 x 150 x480

Centrifugal /Hs

200 x 150 x480type

Flow lps 100 100 100

Head m 48 48 48

Motor Kw kW 110 110 110

Motor efficiency %

Pump efficiency %

Speed rpm 1480 1480 1480

Operating hours jam 24 24 24

SEC rated 305,56 305,56 305,56

Measured DataActual Flow m3/min 5,7 5,7 5,1

lps 94,67 95,83 84,50

Discharge pressure bar 6,5 6,5 6,4

Suction pressure bar 0,2 0,2 0,2

Head m 63 63 62

Power kW 87,8 97,8 86,8

Hidraulic Kw kW 60.18 60.92 52.89

Speed rpm 1481 1480 1482

Over all efficiency % 69 62 61

Pump efficiency (%)

- 72 65 64Current

metod 70 642 62

SEC 258 283 285

Page 33: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 33/46

32

Keterangan

Pompa Tawangsari

4 5 6

Rated Parameter unit

Merk

GRUNDFOS/060

4/1732505040

GRUNDFOS/060

4/1732505040

GRUNDFOS/060

4/1732505040

Model Centifugal/CI/B

R…/TIPE HS 220

x 130 x 48

Centifugal/CI/B

R…/TIPE HS 220

x 130 x 48

Centifugal/CI/B

R…/TIPE HS 220

x 130 x 48type

Flow lps 100 100 100

Head m 48 48 48

Motor Kw kW 110 110 110

Motor efficiency %

Pump efficiency %

Speed rpm 1450-1480 1450-1480 1450-1480

Operating hours jam

SEC rated 306 306 306

Measured Data

Actual Flow m3/min

lps 86,43 83,33 70,50

Discharge pressure bar 6,50 6,5 6,4

Suction pressure bar 0,2 0,2 0,2

Head m 63 63 62

Power kW 95,4 97,1 80

Hidraulic Kw kW 55.20 52.98 44.13

Speed rpm 1484 1482 1488

Over all efficiency % 58 55 55

Pump efficiency(%)

% 61 57 58

Current

metod 65 61 59

SEC Actual 307 324 315

Page 34: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 34/46

33

Keterangan

Pompa Tawangsari

7 8 9

Rated Parameter unit

Merk

GRUNDFOS/060

4/1732505040

GRUNDFOS/060

4/1732505040

GRUNDFOS/060

4/1732505040

Modeltype

Flow lps 100 100 100

Head m 48 48 48

Motor Kw kW 110 110 110

Motor efficiency %

Pump efficiency %

Speed rpm 1780-1786 1780-1786 1780-1786

Operating hours jam

SEC rated 305,56 305,56 305,56

Actual Data

Actual Flow m3/min

lps 83,67 83,67 89

Discharge pressure bar 6,5 6,5 6,5

Suction pressure bar 0,2 0,2 0,2

Head m 63 63 63

Power kW 88,7 96,3 91,5

Hidraulic Kw kW 53.19 53.19 56.58

Speed rpm 1488 1482 1490

Over all efficiency % 60 55 62

Pump efficiency(%)

% 63 58 65

Current

metod 62 58 64

SEC Actual 294,477 319,7084 285,5805

Dari tabel di atas, terlihat bahwa pompa  –  pompa pada unit Tawangsari masih bagus,

dilihat dari efisiensi pompa yang semuanya ≥50 %. Begitu juga dengan SEC yang relative rendah.

Page 35: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 35/46

34

  Efisiensi Motor :

Tabel 20. Analisis/ Penilaian Energy Motor, Unit Tawangsari

Pompa I V

Deviasi frek.

Terukurterhadap

frek.rated

Deviasi tegangan

faktor daya

terukur

% beban

motor

terhadapdaya motor

rated

Efisiensi

motor

R S T

P1 0,5% 0,21% 0.01 0,21% 0,05% -0,3% 0,87 0,9

P2 0,3% 0,19% 0.00 0,19% 0,05% -0,2% 0,87 0,9

P3 0,4% 0,19% 0.00 0,19% 0,04% -0,2% 0,86 0,9

P4 1,9% -0,28% -0.03 -0,28% -0,20% 0,5% 0,88 0,9

P5 1,8% -0,31% -0.02 -0,31% -0,18% 0,5% 0,89 0,9

P6 2,1% -0,31% 0.01 -0,31% -0,20% 0,5% 0,88 0,9

P7 1,9% -0,27% -0.02 -0,27% -0,19% 0,5% 0,87 0,9P8 -1,8% -0,07% 0.03 -0,07% 0,16% -0,1% 0,87 0,9

P9 -1,6% -0,08% -0.01 -0,08% 0,16% -0,1% 0,87 0,9

Kinerja motor untuk pompa  –  pompa di unit Tawangsari ini masih bagus. Semua hasil

masih memenuhi standar (NEMA).

b.  Perpompaan unit Waru II

  SEC :

  SEC global :

Tabel 21. SEC Global Unit Waru II

Bulan (2008)Produksi air  

Total kWhSEC 2009

m3 kWh/juta liter

Januari 74,502 270,184 3,627

Maret 70,502 231,712 3,287

April 80,016 270,856 3,385

Page 36: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 36/46

35

  SEC Waru II Sistem I:

Sistem I terdiri dari pompa 1,2,3,4 dan 5 namun pengukuran hanya dilakukan untuk

pompa 1,2,3 karena pompa 4, dan 5 dalam keadaan off. Hasilnya sebagai berikut :

Tabel 22. Konsumsi Energi Spesifik (SEC) Sistem I, Waru II

ParameterPompa

Total1 2 3 5

rated

kw 110 110 110

off

330

m3/h 360 360 360 1080

SEC act 306

actual

kw 104,1 83,9 112,6 300,6

m3/h 263,988 79,812 143,388 487,188

SEC calc. 617

Tabel di atas menunjukkan bahwa pompa  –   pompa pada system I sudah tidak

efisien. Terdapat selisih SEC yang sangat besar antara SEC rated dengan SEC actual

dimana SEC actual lebih besar 50 %.

  SEC Waru II system II :

System II ini terdiri dari pompa 6 dan pompa 7. Namun pengukuran hanya

dilakukan pada pompa 6 (pompa 7 off) , maka hanya pompa 6 yang dikaji. Hasilnya

sebagai berikut :

Tabel 23. SEC System II, Waru II

Pompa 6

Parameter Total

Rated :

kw 110

m3/h 360

SEC act 306

Actual :

kw 50,19

m3/h 119

SEC calc. 420

Page 37: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 37/46

36

Dari tabel di atas, terlihat bahwa pompa 6 sudah kurang efisien dalam bekerja. SEC

actual lebih tinggi 27 % dibanding SEC rated.

Effisiensi Pompa

Tabel di bawah ini memperlihatkan hasil perhitungan analisis Efisiensi dan Konsumsi

Energy Spesifik di unit Waru II :

Tabel 24. Analisis Efisiensi dan Konsumsi Energy Spesifik Sistem I di unit Waru II

Keterangan

Pompa Waru II

P1 P2 P3

Rated

Parameter unit

Merk ITT ITT ITT

ModelType

Flow lps 100 100 100

Head m

Motor Kw kW 110 110 110

Motor efficiency %

%

Speed rpm

Operating hours jam

SEC rated 305,56 305,56 305,56

Measured Data

Actual Flow m3/min

lps 73,33 22,17 39,83

Discharge

pressure bar 5,50 5,2 5,5

Suction pressure bar 0,2 0,2 0,2

Head m 53 50 53

Power kW 104,1 83,9 112,6

Hidraulic Kw kW 39.45 11.27 21.43

Speed rpm 1485 1486

Over allefficiency % 38 13 19

Pump

efficiency(%)

% 41 14 20

current

metod 42 15 21

SEC Actual 394,34 1051,22 785,28

Page 38: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 38/46

37

Tabel 25.Analisis Efisiensi Dan Konsumsi Energy Spesifik Di Unit Waru II, Sistem II

Keterangan

Rekomendasi

P6

Rated Parameter unit

Merk

Model

Type

Flow lps 100

Head m

Motor Kw kW 110

Motor efficiency %

Pump efficiency %

Speed rpm

Operating hours jam

SEC rated 305,56

Measured Data

Actual Flow m3/min 1,99

lps 33,17

Discharge pressure bar 6,4

Suction pressure bar 0,2

Head m 62

Power kW 50,19

Hidraulic Kw kW 20.76

Speed rpm 1497

Over all efficiency % 41

Pump efficiency(%)% 44

current metod 30

SEC Actual 420,31

Page 39: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 39/46

38

Efisiensi motor :

Tabel 26. Analisis/ Penilaian Energy Motor Unit Waru II

Pompa V I

Deviasi

frek.

Terukurterhadap

frek.rated

Deviasi tegangan

faktordaya

terukur

Efisiensi

motor

R S T

P1 0,08% 3% 0.01 -0,03% 0,08% -0,05% 0,88 0,9

P2 -0,08% 11% -0.04 0,40% -0,08% -0,33% 0,87 0,9

P3 0,01% 4% -0.01 -0,02% 0,01% 0,01% 0,88 0,9

P4 0,9

P5 0,04% 1% -0.02 0,02% 0,04% -0,06% 0,9

P6 0,05% 2% -0.02 0,00% 0,05% -0,05% 0,87 0,9

Secara umum kinerja motor untuk perpompaan unit tawangsari ini masih bagus , dilihat dari

parameter penilaian energy motor semuanya sudah sesuai tandar (NEMA).

II. Analisis Keuangan :

a.  Biaya dan Manfaat (Potensi Savings/ penghematan) :

Penggantian pompa baru

Apabila pompa 1,2,3, dan 6 di ganti dengan pompa yang baru, maka didapat hasil

perhitungan saving/ penghematan seperti dibawah ini :

Page 40: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 40/46

39

Tabel 27.Potensi Saving System I, Unit Waru II

Waru II

P1 P2 P3 SEC sistem

Produksi(m3/h) 264 79.8 143.4 487.2

kW 104.10 83.90 112.60 300.60SEC lama 394 1051 785 617.00

Calculated

kW 110 110 110 330

m3/h 360 360 360 1080

SEC 306 306 306 305.56

lost operation 30.56 30.56 30.56 30.56

SEC baru 336 336 336 336.11

Selisih SEC 15% 68% 57% 46%

Saving

Kwh/bulan 98529.6Rp/bulan Rp 60,072,512

Rp /th Rp 720,870,142

Investasi Rp 900,000,000

I/S 1.25

Tabel 28. Potensi Saving System II, Unit Waru II

Waru II

P6

Produksi(m3/h) 119.8

kW 50.19

SEC lama 419

Calculated

kW 110

m3/h 360

SEC 306

lost operation 30.56

SEC baru 336

Selisih SEC 20%

Saving

Kwh/bulan 7145.2

Rp/bulan Rp 4,356,356.99

Rp /th Rp 52,276,283.86

Investasi Rp 300,000,000

I/S 5.7

Page 41: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 41/46

40

b.  Analisis Investasi:

Analisis kelayakan investasi akan dilakukan dengan menggunakan metode penelitian

investasi : Payback Period (PP), Net Present Value (NPV), dan Internal Rate of Return ( IRR)

  Penggantian pompa :

Tabel 29. Kelayakan Investasi Pompa Waru II

Dari data tersebut penggantian pompa Sistem 1 didapat IRR sebesar 54,34% dengan

pengembalian 1,34 tahun maka disimpulkan pompa tersebut layak investasi. Namun untuk

penggantian pompa di system II atau pompa 6 didapat nilai IRR 9,73% dengan pengembalian 6,14

tahun. Dan untuk pemasangan pompa 6 di simpulkan tidak layak untuk investasi. Tetapi tidakmenutup kemungkinan apabila menggunakan pompa merk lain yang spesifikasinya memenuhi

dengan harga yang lebih rendah, maka investasi akan layak dilakukan.

.

Penggantian PompaPP NPV IRR

(tahun) (Rp) (%)

Waru II Pompa 1 3.96124,077,449

17.30

Waru II Pompa 2 1.071,158,089,483

64.26

Waru II Pompa 3 0.951,339,631,373

72.01

Waru II Sistem I (Pompa

1,2,3)1.34

2,621,798,30554.34

Waru II Pompa 6 6.14(10,846,379)

9.73

Total 4 pompa 1.662,610,951,926

43.98

Page 42: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 42/46

41

5. KENDALA  –  KENDALA YANG DIHADAPI

Beberapa kendala yang dihadapi dalam pelaksanaan program pada saat pengukuran adalah

sebagai berikut :

-  Space/ jarak kabel pada panel control motor di beberapa pompa yang terlalu dekat sehinggaclamp sensor tidak dapat masuk pada kabel

-  Data pada nameplate yang sudah tidak terbaca

-  Data pada nameplate yang tidak sesuai dengan kartu inventarisir pompa

-  Kurva pompa yang sudah tidak ada pada beberapa pompa

-  Tidak adanya tempat untuk pemasangan manometer pada sisi suction (isap)

6.  KESIMPULAN

Efisiensi pompa dan SEC :

Efisiensi pompa < 50%

Pompa  – pompa pada unit dibawah ini sudah mengalami penurunan efisiensi (efisiensi pompa

<50%) dan selisih SEC yang cukup tinggi (>20%), yaitu :

Waru II : pompa 1,2,3,6

Efisiensi pompa antara 51% s.d 59% :

Pompa-pompa pada unit Tawangsari : pompa 5,6,dan 8

Efisiensi pompa >60% :

Pompa Tawangsari : pompa 1,2,3,4,7,9

Kinerja motor :

Kinerja motor untuk semua pompa yang diukur masih cukup bagus/ memenuhi standar NEMA

maupun US DOE

Potensi saving :

Sistem I, Waru II (pompa 1,2,dan 3) :

Dari penggantian pompa , IRR investasi menghasilkan 13% dan tingkat pengembalian selama 1,34

tahun→ layak investasi.

Sistem II, Waru II (pompa 6)

Page 43: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 43/46

42

Dari penggantian pompa, IRR investasi menghasilkan 10% dan tingkat pengembalian selama 6,14

tahun.

Dengan menggunakan data yaitu pompa dengan spek dan harga Grundfos, hasilnya adalah tidak

layak investasi.

Tetapi tidak menutup kemungkinan apabila pompa menggunakanpompa dari merk lain yang

spesifikasinya memenuhi dengan harga yang lebih rendah, maka investasi layak dilakukan

Page 44: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 44/46

43

7. REKOMENDASI DAN PELUANG

PENGHEMATAN

Ringkasan evaluasi efisiensi Pompa Tawangsari & Waru IITabel 30. Ringkasan Evaluasi Efisiensi Pompa Tawangsari

Pompa Evaluasi efisiensi

P1

  Debit pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 72% (≥50%)

  Kinerja motor sesuai standar  

P2

  Debit pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 65% (≥50%)

  Kinerja motor sesuai standar

P3

  Debit pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 64% (

50%)  Kinerja pompa sesuai standar

P4

  Debit pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 61% (≥50%)

  Kinerja pompa sesuai standar

P5

  Debit Pengukuran lebih rendah dibanding data name plate

  Efisiensi Pompa 57%(≥50%)

  Kinerja pompa sesuai standar

P6

  Debit Pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 58% (≥50%)

  Kinerja pompa sesuai standar

P7

  Debit Pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 63% (≥50%)

  Kinerja pompa sesuai standar

P8

  Debit Pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 58% (≥50%)

  Kinerja motor sesuai standar

P9

  Debit Pengukuran lebih rendah dibanding data name plate

  Efisiensi pompa 65%(≥50%)

  Kinerja motor sesuai standar

Page 45: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 45/46

44

Tabel 31. Ringkasan Evaluasi Efisiensi Pompa Waru II

Pompa Evaluasi efisiensi

P1

  Debit Pengukuran lebih rendah dibanding data name

plate  Efisiensi pompa 41%( ≤50%)

  Kinerja motor sesuai standar

P2

  Debit Pengukuran lebih rendah dibanding data name

plate

  Efisiensi pompa 14%( ≤50%)

  Kinerja motor sesuai standar

P3

  Debit Pengukuran lebih rendah dibanding data name

plate

  Efisiensi pompa 20%( ≤50%)

  Kinerja motor sesuai standar

P4  off

P5   off

P6

  Debit Pengukuran lebih rendah dibanding data name

plate

  Efisiensi pompa 44%( ≤50%)

  Kinerja motor sesuai standar

P7   off

REKOMENDASI :

Tabel 32.Tabel Rekomendasi Unit Tawangsari

Kategori Pompa Rekomendasi

BiayaTinggi

Tawangsari

Biaya

Sedang -

Biaya

Rendah

Periksa Jaringan perpipaan dari kemungkinan kebocoran pipa

Periksa dan bersihkan impeller

Periksa koneksi-koneksi antar kabel pada panel kontrol motor

Memasang manometer yang dilengkapi kran pada suction dan discharge pomCek Billink PLN

Periksa dan kalibrasi alat ukur debit yang ada secara rutin

Page 46: Sidoarjo Total

7/23/2019 Sidoarjo Total

http://slidepdf.com/reader/full/sidoarjo-total 46/46

Tabel 33.Rekomendasi Unit Waru Ii

Kategori Pompa Rekomendasi Investasi Saving Payba

Biaya

Tinggi

1

Penggantian Pompa 900 juta 720 juta 1,2

2

36 Penggantian Pompa 300 juta 39 juta 5,7

Biaya

Sedang -

Biaya

Rendah

Semua

pompa

Periksa Jaringan perpipaan dari

kemungkinan kebocoran pipa

Periksa dan bersihkan impeller

Periksa koneksi-koneksi antar kabel pada

panel kontrol motor

Memasang manometer yang dilengkapi

kran pada suction dan discharge pompa

Cek Billink PLN

Periksa dan kalibrasi alat ukur debit yang

ada secara rutin