Fault Diagnostic 3, 4 Dan 5

15
FAULT DIAGNOSTIC

description

Presentation about fault diagnosis in refrigerantion system

Transcript of Fault Diagnostic 3, 4 Dan 5

Page 1: Fault Diagnostic 3, 4 Dan 5

FAULT DIAGNOSTIC

Page 2: Fault Diagnostic 3, 4 Dan 5

Anggota :Nugroho Purwoko (02834)Ananto Wijanarko (02835)Ilham Romadhona (02858)Aditya Firmansyah (02868)Bagas Satria Buana (02872)

KELOMPOK 2

Page 3: Fault Diagnostic 3, 4 Dan 5

NORMAL CONDITION

Page 4: Fault Diagnostic 3, 4 Dan 5

NORMAL CONDITION

Page 5: Fault Diagnostic 3, 4 Dan 5

KONDISI 3Capilary Tube

: Kondisi dimana capilary tube tersumbat

Kondisi Awal

Page 6: Fault Diagnostic 3, 4 Dan 5

Kondisi setelah terjadi penyumbatan

Page 7: Fault Diagnostic 3, 4 Dan 5

KONDISI 3Ambient Temperature 29,4 C

Compoun gauge -0,6 BAR

Temperatur phial 1 22,4 C

Temperatur phial 2 22,2 C

Temperatur phial 3 22,2 C

Temperatur phial 4 22,1 C

Evaporator superheat 0,2 C

Pressure Gauge 7 BAR

Condensing Temperature 24,7 C

Condenser Outlet Temperature 24,7 C

Sub Cooling 0 C

Condensing Temperature Ambient

24,5 C

Percentage frost 0 %

Page 8: Fault Diagnostic 3, 4 Dan 5

PENYEBAB TERJADINYA PENYUMBATAN

1. Rusaknya filter,hal ini menyebabkan sirkulasi refrigeran menjadi terganggu dan biasanya kotoran yang menyebabkan tersumbat adalah serpihan logam.

2. rusaknya pipa kapiler ,karena saat pemasangan terjadi pembengkokan pada pipa

Page 9: Fault Diagnostic 3, 4 Dan 5

SOLUSI PENYUMBATAN PIPA

1. dengan penggantian pipa atau filter 2. pembersihan pipa atau filter

DAMPAK YANG DITIMBULKAN

Dingin yang dihasilkan tidak maksimal dan tidak terjadi frost

Page 10: Fault Diagnostic 3, 4 Dan 5

KONDISI 4Over Charge

: Kondisi dimana refrigerant berlebih

Page 11: Fault Diagnostic 3, 4 Dan 5

KONDISI 4

Ambient Temperature 29,4 C

Compoun gauge 2 BAR

Temperatur phial 1 6,1 C

Temperatur phial 2 5.3 C

Temperatur phial 3 4.8 C

Temperatur phial 4 2.5 C

Evaporator superheat 1.3 C

Pressure Gauge 10.5 BAR

Condensing Temperature 28 C

Condenser Outlet Temperature 26.6 C

Sub Cooling 1.4 C

Condensing Temperature Ambient

31.2 C

Percentage frost 0 %

Page 12: Fault Diagnostic 3, 4 Dan 5

Pengisian refrigerant yang berlebih hal ini menyebabkan beban kerja compresor menjadi berat dan memumbutuhkan daya yang lebih besar (boros)

SOLUSI OVER CHARGEMengurangi refrigerant secara bertahap, hingga

sesuai spesifikasi yang telah ditentukan

PENYEBAB OVER CHARGE

Page 13: Fault Diagnostic 3, 4 Dan 5

KONDISI 5UNDER CHARGE : Kondisi dimana refrigerant kurang

Page 14: Fault Diagnostic 3, 4 Dan 5

KONDISI 5Ambient Temperature 29.4 C

Compoun gauge 0 BAR

Temperatur phial 1 -7,4 C

Temperatur phial 2 17.7 C

Temperatur phial 3 18.4 C

Temperatur phial 4 20.4 C

Evaporator superheat 11 C

Pressure Gauge 7 BAR

Condensing Temperature 27.3 C

Condenser Outlet Temperature 24.5 C

Sub Cooling 2.8 C

Condensing Temperature Ambient

23.8 C

Percentage frost 25 %

Page 15: Fault Diagnostic 3, 4 Dan 5

PENYEBAB UNDER CHARGE

Kurangnya refrigerant pada saat pengisian Adanya kebocoran refrigerant pada sistem

SOLUSI UNDER CHARGER Dengan menambahkan refrigerant secara bertahap

sambil diukur arus pada compressor, agar tercapai arus sesuai dengan spesifikasi compressor

Mengganti/Memperbaiki pipa atau selang yang bocor