Analisa Kebutuhan Daya PLTS

2
ANALISA KEBUTUHAN DAYA 1. PERHITUNGAN BEBAN PUNCAK Beban puncak dari sistem yang ada adalah sebesar 7138 W dan Energi yang harus dipenuhi adalah sebesar 163,212 kWh / hari 2. ANALISA POWER PLTS Data Radiasi *Sumber : https://eosweb.larc.nasa.gov/ Unit Climate data location Latitude °N 3.108 Longitude °E 103.083 Month Air temperature Daily solar radiation Wind speed °C kWh/m 2 /d m/s January 25.5 4.24 4.0 February 25.6 5.09 3.3 March 26.1 5.24 2.7 April 26.7 5.42 1.8 May 27.0 5.15 1.8 June 26.9 5.02 2.7 July 26.7 4.96 2.7 August 26.6 5.05 3.0 September 26.5 5.12 2.4 BEBAN JUMLAH DAYA (W) TOTAL DAYA (W) WAKTU PENGGUNAAN KONSUMSI ENERGI (KWH) INSTALASI RUMAH LAMPU LED 5 W 900 5 4500 24 108 LAMPU SEHEN 300 4 1200 24 28,8 FASILITAS UMUM LAMPU LED 5 W 3 5 15 24 0,36 TV LED 32" 40 1 40 24 0,96 PARABOLA + DECODER 50 1 50 24 1,2 RUMAH PEMBANGKIT LAMPU LED 5 W 3 6 18 24 0,432 STOP KONTAK 1 440 440 24 10,56 EXHAUST FAN 2 100 200 24 4,8 LAMPU JALAN 9W 75 9 675 12 8,1 TOTAL 7138 163,212

description

MEMBERIKAN PENJELASAN MENGENAI CARA DARI ANALISA KEBUTUHAN DAYA DARI PROJECT PLTS.

Transcript of Analisa Kebutuhan Daya PLTS

Page 1: Analisa Kebutuhan Daya PLTS

ANALISA KEBUTUHAN DAYA

1. PERHITUNGAN BEBAN PUNCAK

Beban puncak dari sistem yang ada adalah sebesar 7138 W dan Energi yang harus dipenuhi

adalah sebesar 163,212 kWh / hari

2. ANALISA POWER PLTS

Data Radiasi

*Sumber : https://eosweb.larc.nasa.gov/

Unit Climate data

location

Latitude °N 3.108

Longitude °E 103.083

Month Air temperature Daily solar radiation Wind speed

°C kWh/m2/d m/s

January 25.5 4.24 4.0

February 25.6 5.09 3.3

March 26.1 5.24 2.7

April 26.7 5.42 1.8

May 27.0 5.15 1.8

June 26.9 5.02 2.7

July 26.7 4.96 2.7

August 26.6 5.05 3.0

September 26.5 5.12 2.4

BEBAN JUMLAH DAYA (W) TOTAL DAYA (W) WAKTU PENGGUNAAN KONSUMSI ENERGI (KWH)

INSTALASI RUMAH

LAMPU LED 5 W 900 5 4500 24 108

LAMPU SEHEN 300 4 1200 24 28,8

FASILITAS UMUM

LAMPU LED 5 W 3 5 15 24 0,36

TV LED 32" 40 1 40 24 0,96

PARABOLA + DECODER 50 1 50 24 1,2

RUMAH PEMBANGKIT

LAMPU LED 5 W 3 6 18 24 0,432

STOP KONTAK 1 440 440 24 10,56

EXHAUST FAN 2 100 200 24 4,8

LAMPU JALAN 9W 75 9 675 12 8,1

TOTAL 7138 163,212

Page 2: Analisa Kebutuhan Daya PLTS

October 26.6 4.71 1.9

November 26.3 3.89 2.6

December 25.9 3.55 3.9

Annual 26.4 4.79 2.7

Perhitungan Produksi PLTS

𝐸 = 𝐴 ∗ 𝑟 ∗ 𝐻 ∗ 𝑃𝑅

E = Energy (kWh) A ( Total solar panel Area (m²) ) = 324,72 m² r ( solar panel yield (%) ) = 15,4% H ( Annual average solar radiation ) = 4.79 kWh/ m²/ day PR ( Performance ratio, coefficient for losses (range between 0.5 and 0.9, default value = 0.75) ) = 0,75

𝐸 = 324,72 ∗ 15,4% ∗ 4,79 ∗ 0,75

𝐸 = 179,6497 𝑘𝑊ℎ/𝑑𝑎𝑦